York Sunline 2000 Dm 072 Users Manual 036 21502 003 A 1105
DM 072 to the manual df4d73cd-c2b3-4d2f-83b4-3e069be2e0f4
2015-02-02
: York Sunline-2000-Dm-072-Users-Manual york-sunline-2000-dm-072-users-manual-455166 york pdf
Open the PDF directly: View PDF .
Page Count: 44
036-21502-003-A-1105
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
®
TECHNICAL GUIDE
DESCRIPTION
YORK Sunline 2000™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.
All units include:
• Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
• Permanently lubricated motors
• Bottom or side air discharge configuration capability
(field convertible)
• Manufactured under the quality standards of ISO9001
•
Simplicity
TM Control Board
• Copper tube/aluminum fin coils
• Easy access to all components
• Rigging holes in base rails for lifting
• Fork lift slots on three sides
• Single point power connection
• Complete factory package - tested, charged and wired
• CSA agency listing on all units
WARRANTY
• Factory Limited Parts Warranty
• One-year parts warranty
• A Five-year parts warranty on the compressor and
electric heat elements.
• Ten-year parts warranty on the gas-fired heat
exchangers.
036-21502-003-A-1105
2Unitary Products Group
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 42
Fig. # Pg. #
LIST OF FIGURES
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2 TYPICAL FIELD POWER & CONTROL WIRING . . . . 35
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . 36
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 37
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . . 37
7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . . 38
8 DISCONNECT/BLOWER ACCESS LOCATION . . . . . 38
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 39
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 40
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 41
Tbl. # Pg. #
LIST OF TABLES
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . 15
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . 15
3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . 15
5 DM036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 16
6 DM048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 17
7 DM060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 18
8 DM072 COOLING CAPACITIES (6 TON) . . . . . . . . . . 19
9 SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 20
10 SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 21
11 SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 22
12 SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 23
13 SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON
DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . . 24
14 BELT DRIVE BLOWER MOTOR AND DRIVE DATA. . 24
15 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 25
16 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 25
17 ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 26
18 ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 27
19 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 28
20 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 29
21 ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . 30
22 ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . 31
23 ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . 32
24 ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . 33
25 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
26 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 34
27 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 34
28 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
29 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 38
30 DM 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 40
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 41
036-21502-003-A-1105
Unitary Products Group 3
PRODUCT NOMENCLATURE
7RQ6XQOLQH0RGHO1XPEHU1RPHQFODWXUH
' 0 1 $$ $$
3URGXFW&DWHJRU\
' $LU&RQG6LQJOH3DFNDJH
3URGXFW,GHQWLILHU
0 56WDQGDUG(IILFLHQF\'&*'&(
$LUIORZ
$ 'LUHFW'ULYH
% 'LUHFW'ULYH6LQJOH,QSXW(FRQR
' 'LUHFW'ULYH0RWRUL]HG'DPSHU
/ 'LUHFW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHU3OHDWHG)LOWHUV([WUD[IUPUFLUFXLWENU
1 %HOW'ULYH
3 %HOW'ULYH6LQJOH,QSXW(FRQR
5 %HOW'ULYH0RWRUL]HG'DPSHU
< %HOW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHUZ3OHDWHG)LOWHUV
,QVWDOODWLRQ2SWLRQV
$ 1R2SWLRQV,QVWDOOHG
% 2SWLRQ
& 2SWLRQ
' 2SWLRQV
( 2SWLRQ
) 2SWLRQ
* 2SWLRQV
+ 2SWLRQV
- 2SWLRQV
. 2SWLRQV
/ 2SWLRQV
0 2SWLRQV
1 2SWLRQV
3 2SWLRQV
4 2SWLRQV
5 2SWLRQV
6 2SWLRQ
7 2SWLRQV
8 2SWLRQV
9 2SWLRQV
: 2SWLRQV
; 2SWLRQV
< 2SWLRQV
= 2SWLRQV
2SWLRQV
'LVFRQQHFW
1RQ3ZUG&RQY2XOWHW
6PRNH'HWHFWRU6$
6PRNH'HWHFWRU5$
3ZUG&RQY2XWOHW
$GGLWLRQDO2SWLRQV
6HH1H[W3DJH
3URGXFW*HQHUDWLRQ
)LUVW*HQHUDWLRQ
9ROWDJH
1RPLQDO&RROLQJ
&DSDFLW\0%+
7RQ
7RQ
7RQ
7RQ
+HDW7\SH1RPLQDO+HDW&DSDFLW\
& &RROLQJ2QO\6XLWDEOHIRUILHOGLQVWDOOHGHOHFWULFKHDW
*DV+HDW2SWLRQV
(OHFWULF+HDW2SWLRQV
( N:(OHFWULF+HDW
( N:(OHFWULF+HDW
( N:(OHFWULF+HDW
( N:(OHFWULF+HDW
( N:(OHFWULF+HDW
( N:(OHFWULF+HDW
1 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
1 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
1 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
1 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
' 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
' 0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
6 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
6 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
6 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
6 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
7 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
7 0%+2XWSXW6WDLQOHVV6WHHO6WDJH
'7 0%+2XWSXWRQ0RGHOV
036-21502-003-A-1105
4Unitary Products Group
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Standard Cabinet
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AJ SS Drain Pan
AK SS Drain Pan & Phase Monitor
AL SS Drain Pan & Coil Guard
AM SS Drain Pan & Dirty Filter Switch
AN SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
AS Bottom Drain Connection
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CS CPC Controller, DFS, APS, SS Drain Pan
CT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
036-21502-003-A-1105
Unitary Products Group 5
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JS Johnson UNT Controller, DFS, APS, SS Drain Pan
JT Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
JU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
JV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
JW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
JX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
HS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
HT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
HU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
HV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
HW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
HX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
NT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
NU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
NV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
NW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
NX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
Standard Cabinet
036-21502-003-A-1105
6Unitary Products Group
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
T1 Technicoat Condenser & SS Drain Pan
T3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T4 Technicoat Evaporator & SS Drain Pan
T6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T7 Technicoat Evaporator & Condenser Coils & SS Drain Pan
T9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
LA Simplicity Intelli-Comfort Controller
LB Simplicity Intelli-Comfort Controller, & Phase Monitor
LC Simplicity Intelli-Comfort Controller, & Coil Guard
LD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
LE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
LF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
LG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
LH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
LJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
LK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
LL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
LM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
LN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
LP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
LQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
LR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
LS Simplicity Intelli-Comfort Controller, SS Drain Pan
LT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
LU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
LV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
LW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
LX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
WA Intelli-Comfort w/Mod Link Controller
WB Intelli-Comfort w/Mod Link Controller, & Phase Monitor
WC Intelli-Comfort w/Mod Link Controller, & Coil Guard
WD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
WE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil
Standard Cabinet
036-21502-003-A-1105
Unitary Products Group 7
WF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
WG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
WH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
WJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
WK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
WL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
WM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
WN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
WP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
WQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
WR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
WS Intelli-Comfort w/Mod Link Controller, SS Drain Pan
WT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
WU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
WV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
WW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
WX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Hinged Filter Door & Toolless Access Cabinet
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BJ SS Drain Pan & Hinged Filter Door & Toolless Access Panels
BK SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
BL SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
BM SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BN SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BS Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DS CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
DT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
DU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
DV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
DW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Standard Cabinet
036-21502-003-A-1105
8Unitary Products Group
DX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
ES Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
ET Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
EU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
EV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
EW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
EX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
GS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
GT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
GU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
GV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
GW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
GX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Hinged Filter Door & Toolless Access Cabinet
036-21502-003-A-1105
Unitary Products Group 9
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
QF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Hinged Filter Door & Toolless Access Cabinet
036-21502-003-A-1105
10 Unitary Products Group
QG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
QJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
QK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
QN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
QP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
QQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
QS Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
QT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
QU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
QV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
QW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
QX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
Hinged Filter Door & Toolless Access Cabinet
036-21502-003-A-1105
Unitary Products Group 11
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard
to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. For bottom duct,
remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct,
remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
• Single enthalpy economizer
• Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact require-
ments of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system compo-
nents.
•
Simplicity
™ Controls -
Simplicity
™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
•Fan Delays - Fan on and fan off delays are fully pro-
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
•Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
•Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each sec-
tion includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module for
100% shut-off and all of the safety controls required to
meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements.
Every element is fully protected against excessive tem-
perature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as Simplicity™ INTELLI-
Comfort™, Novar, Honeywell, Johnson, and CPC.
036-21502-003-A-1105
12 Unitary Products Group
FACTORY-INSTALLED OPTIONS
•SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•BAS - Building Automation System Controls
Simplicity
™ INTELLI-Comfort™ CONTROL - The
York® Simplicity™ INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
FIGURE 1 - UNIT CUTAWAY
036-21502-003-A-1105
Unitary Products Group 13
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Com-
fort™using CO2 sensors. It uses an inside CO2 sensor
to perform Demand Ventilation. It can also use an Out-
side CO2 sensor to perform Differential Demand Ventila-
tion. It uses a Patented Comfort Ventilation algorithm to
provide comfortable ventilation air temperature. The pat-
ented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy sav-
ings by recovering the building from the Unoccupied Set-
points to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity™
INTELLI-Comfort™ balances space temperature, venti-
lation air temperature, CO2 and humidity for ultimate
comfort.
•
Simplicity
™ INTELLI-Comfort™ with MOD LINK CON-
TROL - The York® Simplicity™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
•Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
•CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
•SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•STAINLESS STEEL DRAIN PAN - An optional rust-
proof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environ-
ments.
•BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connec-
tions for applications in cold environments to reduce
freezing drain lines.
•PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
•DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
036-21502-003-A-1105
14 Unitary Products Group
•ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
•POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
The power exhaust option can only be used on bot-
tom duct configurations.
•BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•HAIL GUARD -Hail Guard Kit is available to protect coils
from damage. This is a sloped hood that fits above the
outdoor coil.
•GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
036-21502-003-A-1105
Unitary Products Group 15
TABLE 1: SOUND POWER RATING1
UNIT
SIZE CFM
ESP BLOWER SOUND POWER (db 10-12 Watts)
Octave Band Centerline Frequency (Hz) SWL
dB(A)
dB(A)
@
10Ft.2
IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41
048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42
060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
072 2,2000.3HIGH1.3587877770726560557744
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)1
1. 80/67°F Indoor and 95°F outdoor.
MODEL MBH EER2
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER3
3. SEER = Seasonal Energy Efficiency Ratio.
DM036 36.0 9.1 10.0
DM048 47.4 9.0 10.0
DM060 59.0 9.1 10.0
DM072 72.0 9.0 -
TABLE 3: GAS HEAT RATINGS1
1. All units are single-stage heating.
MODEL MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DM036N04
DM036N08
50
100
40
80
80.9
80.5
15 - 45
40 - 70
DM048N06
DM048N10
75
125
60
100
80.9
80.3
25 - 55
45 - 75
DM060N08
DM060N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
DM072N08
DM072N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
TABLE 4: 2 STAGE GAS HEAT RATINGS
MODEL1
1. Models are 3Ø only.
MBH INPUT MBH OUTPUT STEADY STATE EFFICIENCY RISE MINIMUM HEATING
AIRFLOW (CFM)
1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE MIN. MAX.
DM036D06 45 75 35.8 60.8 79.4 81.1 35 70 790
DM036D10 69 115 55.2 92 80.0 80.2 55 90 950
DM048D06 45 75 35.7 60.8 79.4 81.1 25 70 790
DM048D10 75 125 60.4 100.6 80.5 80.5 45 75 1230
DM060D06 45 75 35.8 60.8 79.4 81.1 35 70 1010
DM060D10 75 125 60.4 100.6 80.5 80.5 45 75 1230
DM072D06 45 75 35.8 60.8 79.4 81.1 35 70 1230
DM072D10 75 125 60.4 100.6 80.5 80.5 45 75 1230
036-21502-003-A-1105
16 Unitary Products Group
TABLE 5: DM036 COOLING CAPACITIES (3 TON)
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 45 3.1 35 30 26 21 17 - - 43 3.3 35 30 26 21 17 - -
67 43 3.0 43 38 34 29 25 20 16 41 3.3 41 38 34 29 25 21 16
62 39 3.0 39 39 39 34 30 25 21 36 3.3 36 36 36 32 27 23 18
57 40 2.9 40 40 40 35 31 26 22 38 3.2 38 38 38 33 29 24 20
72 44 3.1 31 28 24 20 16 - - 42 3.3 31 27 23 20 16 - -
67 41 3.0 39 35 31 27 23 19 16 39 3.3 37 35 31 27 23 19 15
62 38 3.0 38 38 37 33 29 25 21 36 3.3 36 36 35 31 27 23 19
57 39 2.9 39 39 39 35 31 27 23 37 3.2 37 37 36 32 28 25 21
72 42 3.1 28 25 22 18 15 - - 41 3.3 28 24 21 18 14 - -
67 40 3.0 35 32 28 25 22 18 15 38 3.2 34 31 28 25 21 18 15
62 36 3.0 36 36 35 31 28 25 21 35 3.3 35 35 34 30 27 24 20
57 37 2.9 37 37 37 34 31 27 24 36 3.2 36 36 35 32 28 25 22
72 41 3.1 26 23 20 17 14 - - 39 3.2 26 23 20 17 14 - -
67 38 3.0 32 30 27 24 21 18 15 37 3.2 32 29 26 23 20 17 14
62 35 3.0 35 35 33 30 27 24 21 33 3.2 33 33 31 28 25 22 20
57 36 2.9 36 36 35 32 29 26 23 34 3.2 34 34 32 30 27 24 21
72 39 3.1 24 21 19 16 14 - - 38 3.2 23 21 18 16 13 - -
67 37 3.0 30 27 25 22 20 17 15 36 3.2 29 26 24 21 19 16 14
62 34 3.0 34 33 30 28 25 23 20 32 3.2 32 31 29 26 24 21 19
57 34 2.9 34 34 33 30 27 25 22 33 3.1 33 33 30 27 25 22 20
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 41 3.7 34 29 25 20 16 - - 39 4.1 33 28 24 19 15 - -
67 38 3.7 38 37 33 28 24 19 15 36 4.0 36 36 32 27 23 18 14
62 34 3.7 34 34 34 30 25 21 16 32 4.0 32 32 32 27 23 18 14
57 35 3.6 35 35 35 31 26 22 17 33 4.0 33 33 33 28 24 19 15
72 40 3.7 30 26 23 19 15 - - 38 4.1 30 26 22 18 14 - -
67 37 3.6 36 34 30 26 22 18 14 35 4.0 34 33 29 25 21 17 13
62 33 3.7 33 33 33 29 25 21 17 31 4.0 31 31 31 27 23 19 15
57 34 3.6 34 34 34 30 26 22 18 32 4.0 32 32 32 28 24 20 16
72 39 3.7 27 24 20 17 14 - - 37 4.1 26 23 20 16 13 - -
67 36 3.6 34 30 27 24 20 17 14 34 4.0 33 30 26 23 20 16 13
62 32 3.6 32 32 32 29 25 22 19 30 4.0 30 30 30 27 24 20 17
57 33 3.6 33 33 33 29 26 23 19 31 3.9 31 31 31 27 24 21 17
72 37 3.6 25 22 19 16 13 - - 36 4.1 24 21 18 15 12 - -
67 35 3.6 31 28 25 22 19 16 13 32 4.0 30 27 24 21 18 15 12
62 31 3.6 31 31 29 27 24 21 18 29 4.0 29 29 28 25 22 19 16
57 32 3.5 32 32 30 27 24 21 18 30 3.9 30 29 28 25 22 19 16
72 36 3.6 22 20 17 15 12 - - 34 4.0 21 19 16 14 11 - -
67 33 3.6 28 25 23 20 18 15 13 31 4.0 27 24 22 19 17 14 11
62 30 3.6 30 29 27 24 22 19 17 28 4.0 28 28 25 22 20 17 15
57 31 3.5 31 30 28 25 22 20 17 28 3.9 28 28 25 23 20 17 15
NOMINAL RATING
900
1050
85°F
POWER
INPUT2 kW
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
1750
1475
1200
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1050
POWER
INPUT2 kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY1SENSIBLE CAPACITY1
900
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
1750
1475
1200
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-003-A-1105
Unitary Products Group 17
TABLE 6: DM048 COOLING CAPACITIES (4 TON)
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 60 4.1 44 39 33 28 23 - - 60 4.5 44 39 33 28 23 - -
67 55 4.1 53 48 42 37 32 26 21 52 4.5 52 47 42 36 31 25 20
62 51 4.0 51 51 51 45 40 34 29 48 4.4 48 48 48 42 37 32 26
57 49 3.9 49 49 49 44 39 33 28 47 4.3 47 47 47 42 36 31 26
72 58 4.1 41 36 31 26 21 - - 57 4.5 41 36 31 26 21 - -
67 53 4.1 49 45 40 35 30 25 20 50 4.5 49 44 39 34 29 24 19
62 49 4.0 49 49 48 43 38 33 28 46 4.4 46 46 46 41 36 31 26
57 47 3.9 47 47 47 43 38 33 28 45 4.3 45 45 45 40 36 31 26
72 56 4.1 38 34 29 25 20 - - 55 4.6 38 33 29 24 20 - -
67 51 4.1 46 41 37 32 28 24 19 48 4.5 45 40 36 31 27 23 18
62 47 4.0 47 47 45 41 36 32 27 44 4.4 44 44 44 40 35 31 26
57 46 3.9 46 46 46 41 37 32 28 44 4.4 44 44 44 39 35 30 26
72 54 4.1 35 31 27 23 19 - - 53 4.5 35 31 27 23 19 - -
67 49 4.1 42 38 34 30 26 22 19 47 4.5 41 38 34 30 26 22 18
62 45 4.0 45 45 42 38 34 30 26 43 4.4 43 43 41 37 33 29 25
57 44 3.9 44 44 43 39 35 31 27 42 4.3 42 42 41 37 33 29 25
72 52 4.1 32 29 25 22 18 - - 51 4.5 32 28 25 21 18 - -
67 47 4.1 39 35 32 28 25 21 18 45 4.4 38 35 31 28 24 21 17
62 43 4.0 43 43 39 36 32 29 25 41 4.3 41 41 38 35 31 28 24
57 42 3.9 42 42 39 36 32 29 25 41 4.3 41 41 38 34 31 27 24
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 56 5.1 42 37 31 26 21 - - 53 5.6 40 35 29 24 19 - -
67 49 5.0 49 46 40 35 29 24 19 46 5.5 46 44 39 33 28 23 17
62 45 4.9 45 45 45 39 34 28 23 41 5.4 41 41 41 36 30 25 20
57 44 4.9 44 44 44 39 33 28 22 41 5.4 41 41 41 35 30 25 19
72 55 5.0 39 34 29 24 20 - - 52 5.5 38 33 28 23 18 - -
67 48 5.0 47 43 38 33 28 23 18 45 5.4 45 42 37 32 27 22 17
62 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 26 21
57 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 25 20
72 53 5.0 36 32 28 23 19 - - 51 5.5 35 31 26 22 17 - -
67 46 4.9 44 40 35 31 26 22 17 44 5.4 44 39 35 30 26 21 17
62 42 4.9 42 42 42 37 33 28 24 39 5.3 39 39 39 35 30 26 21
57 41 4.8 41 41 41 37 32 28 23 39 5.3 39 39 39 34 30 25 21
72 51 5.0 33 29 26 22 18 - - 48 5.5 32 28 24 20 16 - -
67 44 4.9 41 37 33 29 25 21 17 42 5.3 40 36 32 28 24 20 16
62 40 4.8 40 40 39 35 31 27 23 37 5.3 37 37 36 32 28 24 20
57 40 4.8 40 40 38 34 30 26 22 37 5.3 37 37 36 32 28 24 20
72 49 4.9 30 27 23 20 16 - - 46 5.4 29 26 22 19 15 - -
67 42 4.9 37 34 30 27 23 20 16 39 5.3 36 33 29 26 22 19 15
62 38 4.8 38 38 36 32 29 25 22 35 5.3 35 35 33 29 26 22 19
57 38 4.8 38 38 35 32 28 25 21 35 5.3 35 35 33 29 26 22 19
NOMINAL RATING
1200
1400
85°F
POWER
INPUT2 kW
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
2000
1800
1600
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1400
POWER
INPUT2 kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY1SENSIBLE CAPACITY1
1200
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
2000
1800
1600
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-003-A-1105
18 Unitary Products Group
TABLE 7: DM060 COOLING CAPACITIES (5 TON)
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - -
67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 23
62 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 28
57 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 25
72 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - -
67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 22
62 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 29
57 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 27
72 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - -
67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 22
62 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 31
57 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 28
72 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - -
67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 21
62 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 29
57 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 27
72 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - -
67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 20
62 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 27
57 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - -
67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24 18
62 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 19
57 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 17
72 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - -
67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 18
62 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 26 20
57 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 19
72 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - -
67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 18
62 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 22
57 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 21
72 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - -
67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 17
62 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 21
57 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 38 33 29 24 19
72 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - -
67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 16
62 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 19
57 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18
NOMINAL RATING
1500
1750
85°F
POWER
INPUT2 kW
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
2500
2250
2000
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
1750
POWER
INPUT2 kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY1SENSIBLE CAPACITY1
1500
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
2500
2250
2000
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-003-A-1105
Unitary Products Group 19
TABLE 8: DM072 COOLING CAPACITIES (6 TON)
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 80 5.7 63 55 47 40 32 - - 77 6.3 63 55 47 40 32 - -
67 80 5.7 76 68 60 53 45 37 30 77 6.3 75 68 60 53 45 37 30
62 70 5.5 70 70 70 62 55 47 39 71 6.3 71 71 71 63 56 48 40
57 68 5.6 68 68 68 60 52 45 37 71 6.3 71 71 71 63 56 48 40
72 82 5.7 60 53 46 38 31 - - 76 6.3 60 53 46 39 31 - -
67 82 5.7 73 65 58 51 43 36 29 76 6.3 73 66 58 51 44 36 29
62 71 5.5 71 71 70 62 55 48 41 70 6.3 70 70 69 62 55 48 40
57 69 5.6 69 69 69 62 55 47 40 70 6.3 70 70 70 62 55 48 40
72 83 5.7 58 51 44 37 30 - - 75 6.3 58 51 44 37 30 - -
67 83 5.7 70 63 56 49 42 35 28 75 6.3 70 64 57 50 43 36 29
62 73 5.5 73 73 70 63 56 49 42 69 6.3 69 69 68 61 54 47 40
57 71 5.6 71 71 71 64 57 50 43 69 6.3 69 69 68 61 54 47 40
72 79 5.7 54 48 41 35 29 - - 73 6.3 53 47 41 35 29 - -
67 79 5.7 65 59 53 47 40 34 28 73 6.3 65 59 52 46 40 34 28
62 69 5.5 69 69 66 60 54 47 41 67 6.3 67 66 63 57 51 45 38
57 67 5.6 67 67 67 61 54 48 42 67 6.3 67 66 63 57 51 45 39
72 74 5.6 50 44 39 34 28 - - 71 6.3 49 43 38 33 27 - -
67 74 5.6 60 55 50 44 39 34 28 71 6.3 59 54 48 43 38 32 27
62 65 5.4 65 65 62 57 51 46 41 65 6.2 65 63 58 53 47 42 37
57 63 5.5 63 63 63 58 52 47 42 65 6.3 65 63 58 53 47 42 37
CFM WB °F 86 8380 77 74 71 68 86 8380 77 74 71 68
72 76 7.1 61 53 45 38 30 - - 75 7.9 59 51 43 36 28 - -
67 71 7.1 70 66 58 50 43 35 27 65 7.8 65 64 56 48 41 33 25
62 64 7.0 64 64 64 56 49 41 34 57 7.8 57 57 57 50 42 34 27
57 64 7.0 64 64 64 56 49 41 34 57 7.7 57 57 57 50 42 34 27
72 76 7.1 59 51 44 37 29 - - 76 7.9 57 49 42 35 27 - -
67 71 7.1 69 64 56 49 42 34 27 66 7.9 66 61 54 47 40 32 25
62 64 7.0 64 64 64 56 49 42 35 58 7.8 58 58 58 51 43 36 29
57 64 7.0 64 64 64 56 49 42 34 58 7.7 58 58 58 50 43 36 29
72 75 7.1 56 49 43 36 29 - - 76 8.0 55 48 41 34 27 - -
67 70 7.1 68 61 54 48 41 34 27 66 7.9 66 59 52 45 38 32 25
62 64 7.0 64 64 63 56 49 42 35 59 7.8 59 59 59 52 45 38 31
57 64 7.0 64 64 63 56 49 42 35 59 7.7 59 59 58 51 44 37 30
72 73 7.1 52 45 39 33 27 - - 73 7.9 50 44 37 31 25 - -
67 68 7.1 63 56 50 44 38 32 26 63 7.8 61 54 48 42 36 30 24
62 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 54 48 42 35 29
57 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 53 47 41 35 29
72 70 7.1 47 41 36 31 25 - - 69 7.8 45 40 34 29 23 - -
67 65 7.0 57 51 46 41 35 30 25 60 7.8 55 49 44 39 33 28 23
62 59 7.0 59 58 54 48 43 38 32 53 7.7 53 53 49 44 39 33 28
57 59 6.9 59 58 53 48 43 37 32 53 7.6 53 53 49 44 38 33 27
NOMINAL RATING
1800
2100
85°F
POWER
INPUT2 kW
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
2700
2550
2400
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
2100
POWER
INPUT2 kW
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
SENSIBLE CAPACITY1SENSIBLE CAPACITY1
1800
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
TOTAL
CAP.1
MBH
POWER
INPUT2 kW
TOTAL
CAP.1
MBH
2700
2550
2400
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
036-21502-003-A-1105
20 Unitary Products Group
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 835 705 880 745 923 795 969 860 1013 970 ----
1600 811 655 854 695 898 740 942 790 986 840 1029 900 - -
1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905
1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790
1300 ----816590862635907675951715995750
1200 ------834585881630927665970705
1100 ------809550855590900625942665
1000 ------782510829545872858919625
900--------797500843540890580
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 --------------
1600 --------------
1500 --------------
1400 1055 875 ------------
1300 1036 780 1066 850 ----------
1200 1011 735 1047 765 1075 800 --------
1100 987 690 1028 720 1060 750 1084 775 ------
1000 963 655 1005 680 1040 695 1068 715 1089 735 ----
900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - -
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
TONNAGE
AIR
FLOW
CFM
3
1,2
UNIT
TONNAGE
AIR
FLOW
CFM
3
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on a
pp
lications other than
g
as / electric units with side duct airflows.
036-21502-003-A-1105
Unitary Products Group 21
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170
1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100
1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030
1600 ----818665858740898820940890980950
1500 ------842695882755922835962895
1400 ------833650867705904765942820
1300 --------858665893725932785
1200 --------847640880680916730
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2000 1103 1270 ------------
1900 1085 1210 ------------
1800 1064 1145 1102 1180 ----------
1700 1040 1075 1081 1115 1121 1140 --------
1600 1020 1005 1060 1050 1100 1085 --------
1500 1003 945 1044 995 1086 1035 --------
1400 982 880 1024 920 1067 965 1107 1000 ------
1300 970 835 1010 870 1053 920 1099 960 ------
1200 953 780 992 815 1034 855 1080 905 ------
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
TONNAGE
AIR
FLOW
CFM
41, 2
UNIT
TONNAGE
AIR
FLOW
CFM
41, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-003-A-1105
22 Unitary Products Group
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640
2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535
2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440
2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340
2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225
1900 ----8948859409409809801014 1020 1047 1095
1800 ----8558159038609509059889401022 970
1700 ------8848159258509648801001 910
1600 ------864770908805948835987870
1500 --------882740926780965830
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 --------------
2400 1193 1665 ------------
2300 1170 1580 1202 1620 ----------
2200 1148 1480 1180 1530 ----------
2100 1121 1385 1155 1425 1190 1475 --------
2000 1100 1285 1133 1340 1169 1385 1205 1445 ------
1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 ----
1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 ----
1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -
1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150
1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
51, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
UNIT
T
ONNAGE
AIR FLOW
CFM
51, 2
UNIT
T
ONNAGE
AIR FLOW
CFM
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-003-A-1105
Unitary Products Group 23
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 1150 2325 1182 2425 1212 2525 --------
3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - -
2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130
2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
2000 ------9191025 950 1100 982 1130 1014 1160
1800 --------9099259391005 968 1030
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 --------------
3000 --------------
2800 1245 2190 ------------
2600 1193 1920 1222 1990 1250 2060 --------
2400 1142 1675 1173 1730 1205 1800 1234 1885 ------
2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - -
2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600
1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
TONNAGE
AIR
FLOW
CFM
6
1, 2
UNIT
TONNAGE
AIR
FLOW
CFM
6
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
036-21502-003-A-1105
24 Unitary Products Group
TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI ----1699 825 1650 785 1570 755
MED 1684 800 1631 780 1582 750 1524 720 1410 690
LOW 1487 710 1464 690 1421 670 1367 650 1315 620
HI 1996 960 1933 936 1868 910 1795 880 1722 845
MED 1804 838 1765 810 1714 785 1650 765 1589 735
LOW 1681 760 1640 738 1604 715 1541 695 1490 670
HI 2400 1155 2338 1125 2274 1095 2167 1045 2096 1010
MED 2290 1105 2214 1065 2145 1030 2071 990 1990 950
LOW 2150 1020 2100 990 2029 950 1965 910 1905 880
61HI 2461 1480 2402 1440 2361 1395 2260 1350 2178 1305
CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI 1430 725 1360 700 1280 680 1180 655
MED 1324 650 1260 630 1185 610 1100 590
LOW 1246 605 1185 590 1110 570 1020 545
HI 1635 820 1544 790 1419 765 1300 740
MED 1508 705 1407 675 1306 645 1195 625
LOW 1416 645 1337 620 1230 595 1120 575
HI 1990 980 1887 945 1771 905 1629 855
MED 1911 920 1828 885 1724 835 1604 798
LOW 1816 838 1724 800 1644 770 1531 710
61HI 2101 1260 2000 1205 1914 1155 1830 1110
51
0.600.20 0.30 0.40 0.50
UNIT
TONNAGE MOTOR SPEED
UNIT
TONNAGE) MOTOR SPEED
31
41
51
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.900.80 1.00
31
41
0.70
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.
TABLE 14: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
BLOWER
RANGE
(RPM)
MOTOR1ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT
(NOTCHED)
HP FRAME DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
PITCH
LENGTH
(IN.)
QTY.
3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1
4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1
5 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1
6 TON 900/1250 1 1/2 56 1VL44 3.1-4.1 2.8-3.8 7/8 AK56 5.4 5.2 1 A36 37.3 1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
036-21502-003-A-1105
Unitary Products Group 25
TABLE 15: STATIC RESISTANCES
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30
7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22
20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26
0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22
0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32
COOLING ONLY2
RESISTANCE, IWG
CFM
DESCRIPTION
ECONOMIZER1 3
BOTTOM DUCT CONNECTIONS1
ELECTRIC
HEATERS1
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
TABLE 16: ELECTRIC HEATER CFM LIMITATIONS
UNITMODEL SIZE NOMINAL
TONS VOLTAGE
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
5 7 10 15 20 30
3
208/230-1-60 1100 1100 1200 1200 1300 -
208/230-3-60 1100 1100 1200 1200 1300 -
460-3-60 - 1100 1200 1200 1300 -
575-3-60 - - 1200 1200 1300 -
4
208/230-1-60 1300 1300 1300 1300 1300 -
208/230-3-60 1300 1300 1300 1300 1300 -
460-3-60 - 1300 1300 1300 1300 -
575-3-60 - - 1300 1300 1400 -
5
208/230-1-60 1600 1600 1600 1600 1600 1600
208/230-3-60 1600 1600 1600 1600 1600 1600
460-3-60 - 1600 1600 1600 1600 1600
575-3-60 - 1600 1600 1600 1600 1800
6
208/230-3-60 1800 1800 1800 1800 1800 1800
460-3-60 - 1800 1800 1800 1800 1800
575-3-60 - - 1800 1800 1800 1800
036-21502-003-A-1105
26 Unitary Products Group
TABLE 17: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 28.2 45
2CE04510506 4.0 19.2 29.5 45
2CE04510706 5.6 26.9 39.2 45
2CE04511006 8.0 38.5 53.6 60
2CE04511506 11.9 57.2 77.0 80
2CE04512006 15.9 76.4 101.1 110
NONE 0.0 0.0 28.2 45
2CE04510506 5.3 22.1 33.1 45
2CE04510706 7.5 31.3 44.6 45
2CE04511006 10.6 44.2 60.7 70
2CE04511506 15.9 66.3 88.3 90
2CE04512006 21.2 88.3 115.9 125
NONE 0.0 0.0 19.9 30
2CE04510525
2
4.0 11.1 19.9 30
2CE04510725
2
5.6 15.5 24.9 30
2CE04511025 8.0 22.2 33.3 35
2CE04511525 11.9 33.0 46.8 50
2CE04512025 15.9 44.1 60.7 70
NONE 0.0 0.0 19.9 30
2CE04510525
2
5.3 12.7 21.4 30
2CE04510725
2
7.5 18.0 28.1 30
2CE04511025 10.6 25.5 37.4 40
2CE04511525 15.9 38.2 53.3 60
2CE04512025 21.2 51.0 69.2 70
NONE 0.0 0.0 10.8 15
2CE04510746
2
6.8 8.2 13.0 15
2CE04511046
2
10.1 12.1 17.9 20
2CE04511546
2
13.6 16.4 23.2 25
2CE04512046
2
19.5 23.5 32.1 35
NONE 0.0 0.0 8.7 15
2CE04511058 10.6 10.2 14.9 15
2CE04511558 15.9 15.3 21.3 25
2CE04512058 21.2 20.4 27.7 30
NONE 0.0 0.0 36.8 60
2CE04510506 4.0 19.2 36.8 60
2CE04510706 5.6 26.9 39.9 60
2CE04511006 8.0 38.5 54.3 60
2CE04511506 11.9 57.2 77.8 80
2CE04512006 15.9 76.4 101.8 110
NONE 0.0 0.0 36.8 60
2CE04510506 5.3 22.1 36.8 60
2CE04510706 7.5 31.3 45.3 60
2CE04511006 10.6 44.2 61.5 70
2CE04511506 15.9 66.3 89.1 90
2CE04512006 21.2 88.3 116.7 125
NONE 0.0 0.0 23.9 35
2CE04510525
2
4.0 11.1 23.9 35
2CE04510725
2
5.6 15.5 25.7 35
2CE04511025 8.0 22.2 34.0 35
2CE04511525 11.9 33.0 47.5 50
2CE04512025 15.9 44.1 61.4 70
NONE 0.0 0.0 23.9 35
2CE04510525
2
5.3 12.7 23.9 35
2CE04510725
2
7.5 18.0 28.8 35
2CE04511025 10.6 25.5 38.1 40
2CE04511525 15.9 38.2 54.1 60
2CE04512025 21.2 51.0 70.0 70
NONE 0.0 0.0 11.9 15
2CE04510746
2
6.8 8.2 13.0 15
2CE04511046
2
10.1 12.1 17.9 20
2CE04511546
2
13.6 16.4 23.2 25
2CE04512046
2
19.5 23.5 32.1 35
NONE 0.0 0.0 9.7 15
2CE04511058 10.6 10.2 14.9 15
2CE04511558 15.9 15.3 21.3 25
2CE04512058 21.2 20.4 27.7 30
Model
Tonnage Voltage
Compressors
3
45
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
1.3
1.3
0.8
105
90
4.4 0.0
230-1-60 18.0 105 1.3 4.4 0.0
208-1-60 18.0
4.4 0.0
230-3-60 11.4 90 1.3 4.4 0.0
208-3-60 11.4
2.2 0.0
575-3-60 5.0 36 0.8 2.2 0.0
460-3-60 6.2
4
208-1-60 24.4 140
208-3-60 14.1 105
460-3-60 7.1 55
1.3 5.0 0.0
230-1-60 24.4 140 1.3 5.0 0.0
1.3 5.0 0.0
230-3-60 14.1 105 1.3 5.0 0.0
575-3-60 5.8 44 0.8
0.0
2.2 0.0
0.8 2.2
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
Unitary Products Group 27
TABLE 18: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 44.0 70
2CE04510506 4.0 19.2 44.0 70
2CE04510706 5.6 26.9 44.0 70
2CE04511006 8.0 38.5 56.3 70
2CE04511506 11.9 57.2 79.8 80
2CE04512006 15.9 76.4 103.8 110
2CE04513006 22.2 106.7 141.7 150
NONE 0.0 0.0 44.0 70
2CE04510506 5.3 22.1 44.0 70
2CE04510706 7.5 31.3 47.3 70
2CE04511006 10.6 44.2 63.5 70
2CE04511506 15.9 66.3 91.1 100
2CE04512006 21.2 88.3 118.7 125
2CE04513006 29.6 123.3 162.4 175
NONE 0.0 0.0 27.9 40
2CE0451052524.0 11.1 27.9 40
2CE0451072525.6 15.5 27.9 40
2CE04511025 8.0 22.2 36.0 40
2CE04511525 11.9 33.0 49.5 50
2CE04512025 15.9 44.1 63.4 70
2CE04513025 22.2 61.6 85.3 90
NONE 0.0 0.0 27.9 40
2CE0451052525.3 12.7 27.9 40
2CE0451072527.5 18.0 30.8 40
2CE04511025 10.6 25.5 40.1 45
2CE04511525 15.9 38.2 56.1 60
2CE04512025 21.2 51.0 72.0 80
2CE04513025 29.6 71.2 97.3 100
NONE 0.0 0.0 14.1 20
2CE0451074626.8 8.2 14.3 20
2CE04511046210.1 12.1 19.3 20
2CE04511546213.6 16.4 24.6 25
2CE04512046219.5 23.5 33.4 35
2CE04513046228.8 34.6 47.4 50
NONE 0.0 0.0 11.3 15
2CE04511058 10.6 10.2 16.0 20
2CE04511558 15.9 15.3 22.4 25
2CE04512058 21.2 20.4 28.8 30
2CE04513058 30.4 29.3 39.9 40
NONE 0.0 0.0 31.7 50
2CE0451052524.0 11.1 31.7 50
2CE0451072525.6 15.5 31.7 50
2CE04511025 8.0 22.2 36.3 50
2CE04511525 11.9 33.0 49.8 50
2CE04512025 15.9 44.1 63.7 70
2CE04513025 22.2 61.6 85.5 90
NONE 0.0 0.0 31.7 50
2CE0451052525.3 12.7 31.7 50
2CE0451072527.5 18.0 31.7 50
2CE04511025 10.6 25.5 40.4 50
2CE04511525 15.9 38.2 56.3 60
2CE04512025 21.2 51.0 72.2 80
2CE04513025 29.6 71.2 97.5 100
NONE 0.0 0.0 16.3 25
2CE0451074626.8 8.2 16.3 25
2CE04511046210.1 12.1 19.7 25
2CE04511546213.6 16.4 24.9 25
2CE04512046219.5 23.5 33.8 35
2CE04513046228.8 34.6 47.8 50
NONE 0.0 0.0 13.0 15
2CE04511058 10.6 10.2 16.3 20
2CE04511558 15.9 15.3 22.7 25
2CE04512058 21.2 20.4 29.1 30
2CE04513058 30.4 29.3 40.2 40
6
18.9
5
Heater
Amps
OD Fan
Motor
FLA
Model
Tonnage Voltage
0.8 3.6 0.0
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR1 Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Compressors
575-3-60 7.6 58.4 0.8
1.3
3.6 0.0
1.3 6.8 0.0
6.8 0.0
208-3-60 146
460-3-60 9.5 73
230-3-60 18.9 146
3.3 0.0
575-3-60 6.4 50 0.8 3.3 0.0
460-3-60 8.0
6.6 0.0
208-3-60 16.0
230-3-60 16.0 125 1.3
6.6 0.0
0.0
6.6 0.0
165
165 1.3
6.6
66.5
1.3
1.3
0.8
125
208-1-60
230-1-60 28.9
28.9
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
28 Unitary Products Group
TABLE 19: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 31.4 45
2CE04510506 4.0 19.2 33.5 45
2CE04510706 5.6 26.9 43.2 45
2CE04511006 8.0 38.5 57.6 60
2CE04511506 11.9 57.2 81.0 90
2CE04512006 15.9 76.4 105.1 110
NONE 0.0 0.0 31.4 45
2CE04510506 5.3 22.1 37.1 45
2CE04510706 7.5 31.3 48.6 50
2CE04511006 10.6 44.2 64.7 70
2CE04511506 15.9 66.3 92.3 100
2CE04512006 21.2 88.3 119.9 125
NONE 0.0 0.0 20.8 30
2CE04510525
2
4.0 11.1 20.8 30
2CE04510725
2
5.6 15.5 25.9 30
2CE04511025 8.0 22.2 34.3 35
2CE04511525 11.9 33.0 47.8 50
2CE04512025 15.9 44.1 61.7 70
NONE 0.0 0.0 20.8 30
2CE04510525
2
5.3 12.7 22.4 30
2CE04510725
2
7.5 18.0 29.1 30
2CE04511025 10.6 25.5 38.4 40
2CE04511525 15.9 38.2 54.3 60
2CE04512025 21.2 51.0 70.2 80
NONE 0.0 0.0 11.1 15
2CE04510746
2
6.8 8.2 13.5 15
2CE04511046
2
10.1 12.1 18.4 20
2CE04511546
2
13.6 16.4 23.7 25
2CE04512046
2
19.5 23.5 32.6 35
NONE 0.0 0.0 8.5 15
2CE04511058 10.6 10.2 14.7 15
2CE04511558 15.9 15.3 21.1 25
2CE04512058 21.2 20.4 27.5 30
NONE 0.0 0.0 39.4 60
2CE04510506 4.0 19.2 39.4 60
2CE04510706 5.6 26.9 43.2 60
2CE04511006 8.0 38.5 57.6 60
2CE04511506 11.9 57.2 81.0 90
2CE04512006 15.9 76.4 105.1 110
NONE 0.0 0.0 39.4 60
2CE04510506 5.3 22.1 39.4 60
2CE04510706 7.5 31.3 48.6 60
2CE04511006 10.6 44.2 64.7 70
2CE04511506 15.9 66.3 92.3 100
2CE04512006 21.2 88.3 119.9 125
NONE 0.0 0.0 24.1 35
2CE04510525
2
4.0 11.1 24.1 35
2CE04510725
2
5.6 15.5 25.9 35
2CE04511025 8.0 22.2 34.3 35
2CE04511525 11.9 33.0 47.8 50
2CE04512025 15.9 44.1 61.7 70
NONE 0.0 0.0 24.1 35
2CE04510525
2
5.3 12.7 24.1 35
2CE04510725
2
7.5 18.0 29.1 35
2CE04511025 10.6 25.5 38.4 40
2CE04511525 15.9 38.2 54.3 60
2CE04512025 21.2 51.0 70.2 80
NONE 0.0 0.0 12.3 15
2CE04510746
2
6.8 8.2 13.5 15
2CE04511046
2
10.1 12.1 18.4 20
2CE04511546
2
13.6 16.4 23.7 25
2CE04512046
2
19.5 23.5 32.6 35
NONE 0.0 0.0 9.5 15
2CE04511058 10.6 10.2 14.7 15
2CE04511558 15.9 15.3 21.1 25
2CE04512058 21.2 20.4 27.5 30
0.8
4
24.4 140
14.1 105
55
1.3
1.3
2.6 0.0
575-3-60 5.8 44 0.8 2 0.0
460-3-60 7.1
5.2 0.0
230-3-60 14.1 105 1.3 5.2 0.0
208-3-60
7.6 0.0
230-1-60 24.4 140 1.3 7.6 0.0
208-1-60
0.8 2.6 0.0
575-3-60 5.0 36 0.8 2 0.0
1.3 5.2 0.0
230-3-60 11.4 90 1.3 5.2 0.0
1.3 7.6 0.0
230-1-60 18.0 105 1.3 7.6 0.0
3
208-1-60 18.0 105
208-3-60 11.4 90
460-3-60 6.2 45
OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR
1
Size
Amps
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Model
Tonnage Voltage
Compressors
RLA
Each
LRA
Each
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
Unitary Products Group 29
TABLE 20: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 45.0 70
2CE04510506 4.0 19.2 45.0 70
2CE04510706 5.6 26.9 45.0 70
2CE04511006 8.0 38.5 57.6 70
2CE04511506 11.9 57.2 81.0 90
2CE04512006 15.9 76.4 105.1 110
2CE04513006 22.2 106.7 142.9 150
NONE 0.0 0.0 45.0 70
2CE04510506 5.3 22.1 45.0 70
2CE04510706 7.5 31.3 48.6 70
2CE04511006 10.6 44.2 64.7 70
2CE04511506 15.9 66.3 92.3 100
2CE04512006 21.2 88.3 119.9 125
2CE04513006 29.6 123.3 163.7 175
NONE 0.0 0.0 26.5 40
2CE0451052524.0 11.1 26.5 40
2CE0451072525.6 15.5 26.5 40
2CE04511025 8.0 22.2 34.3 40
2CE04511525 11.9 33.0 47.8 50
2CE04512025 15.9 44.1 61.7 70
2CE04513025 22.2 61.6 83.5 90
NONE 0.0 0.0 26.5 40
2CE0451052525.3 12.7 26.5 40
2CE0451072527.5 18.0 29.1 40
2CE04511025 10.6 25.5 38.4 40
2CE04511525 15.9 38.2 54.3 60
2CE04512025 21.2 51.0 70.2 80
2CE04513025 29.6 71.2 95.5 100
NONE 0.0 0.0 13.4 20
2CE0451074626.8 8.2 13.5 20
2CE04511046210.1 12.1 18.4 20
2CE04511546213.6 16.4 23.7 25
2CE04512046219.5 23.5 32.6 35
2CE04513046228.8 34.6 46.6 50
NONE 0.0 0.0 10.2 15
2CE04511058 10.6 10.2 14.7 15
2CE04511558 15.9 15.3 21.1 25
2CE04512058 21.2 20.4 27.5 30
2CE04513058 30.4 29.3 38.6 40
NONE 0.0 0.0 29.9 45
2CE0451052524.0 11.1 29.9 45
2CE0451072525.6 15.5 29.9 45
2CE04511025 8.0 22.2 34.0 45
2CE04511525 11.9 33.0 47.5 50
2CE04512025 15.9 44.1 61.4 70
2CE04513025 22.2 61.6 83.3 90
NONE 0.0 0.0 29.9 45
2CE0451052525.3 12.7 29.9 45
2CE0451072527.5 18.0 29.9 45
2CE04511025 10.6 25.5 38.1 45
2CE04511525 15.9 38.2 54.1 60
2CE04512025 21.2 51.0 70.0 70
2CE04513025 29.6 71.2 95.3 100
NONE 0.0 0.0 15.2 20
2CE0451074626.8 8.2 15.2 20
2CE04511046210.1 12.1 18.3 20
2CE04511546213.6 16.4 23.6 25
2CE04512046219.5 23.5 32.4 35
2CE04513046228.8 34.6 46.4 50
NONE 0.0 0.0 11.7 15
2CE04511058 10.6 10.2 14.7 15
2CE04511558 15.9 15.3 21.1 25
2CE04512058 21.2 20.4 27.5 30
2CE04513058 30.4 29.3 38.6 40
5
6
18.9 146
9.5 73
575-3-60 7.6 58.4
18.9
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR1 Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Compressors OD Fan
Motor
FLA
Model
Tonnage Voltage Heater
Amps
0.8 2.5 0.0
1.3 5.0 0.0
230-3-60
0.8 2 0.0
460-3-60
146 1.3 5.0 0.0
208-3-60
0.0
575-3-60 6.4 50 0.8 2 0.0
8.0 66.5
0.0
230-3-60 16.0 125 1.3 5.2 0.0
208-3-60 16.0 1.3
0.0
230-1-60 28.9 165 1.3 7.6 0.0
1.3 7.6208-1-60 28.9
460-3-60
5.2
0.8 2.6
165
125
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
30 Unitary Products Group
TABLE 21: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 38.2 50
2CE04510506 4.0 19.2 42.0 50
2CE04510706 5.6 26.9 51.7 60
2CE04511006 8.0 38.5 66.1 70
2CE04511506 11.9 57.2 89.5 90
2CE04512006 15.9 76.4 113.6 125
NONE 0.0 0.0 38.2 50
2CE04510506 5.3 22.1 45.6 50
2CE04510706 7.5 31.3 57.1 60
2CE04511006 10.6 44.2 73.2 80
2CE04511506 15.9 66.3 100.8 110
2CE04512006 21.2 88.3 128.4 150
NONE 0.0 0.0 29.9 40
2CE04510525
2
4.0 11.1 31.9 40
2CE04510725
2
5.6 15.5 37.4 40
2CE04511025 8.0 22.2 45.8 50
2CE04511525 11.9 33.0 59.3 60
2CE04512025 15.9 44.1 73.2 80
NONE 0.0 0.0 29.9 40
2CE04510525
2
5.3 12.7 33.9 40
2CE04510725
2
7.5 18.0 40.6 45
2CE04511025 10.6 25.5 49.9 50
2CE04511525 15.9 38.2 65.8 70
2CE04512025 21.2 51.0 81.7 90
NONE 0.0 0.0 15.8 20
2CE04510746
2
6.8 8.2 19.2 20
2CE04511046
2
10.1 12.1 24.2 25
2CE04511546
2
13.6 16.4 29.4 30
2CE04512046
2
19.5 23.5 38.3 40
NONE 0.0 0.0 12.7 15
2CE04511058 10.6 10.2 19.9 20
2CE04511558 15.9 15.3 26.3 30
2CE04512058 21.2 20.4 32.7 35
NONE 0.0 0.0 46.8 70
2CE04510506 4.0 19.2 46.8 70
2CE04510706 5.6 26.9 52.4 70
2CE04511006 8.0 38.5 66.8 70
2CE04511506 11.9 57.2 90.3 100
2CE04512006 15.9 76.4 114.3 125
NONE 0.0 0.0 46.8 70
2CE04510506 5.3 22.1 46.8 70
2CE04510706 7.5 31.3 57.8 70
2CE04511006 10.6 44.2 74.0 80
2CE04511506 15.9 66.3 101.6 110
2CE04512006 21.2 88.3 129.2 150
NONE 0.0 0.0 33.9 45
2CE04510525
2
4.0 11.1 33.9 45
2CE04510725
2
5.6 15.5 38.2 45
2CE04511025 8.0 22.2 46.5 50
2CE04511525 11.9 33.0 60.0 70
2CE04512025 15.9 44.1 73.9 80
NONE 0.0 0.0 33.9 45
2CE04510525
2
5.3 12.7 34.7 45
2CE04510725
2
7.5 18.0 41.3 45
2CE04511025 10.6 25.5 50.6 60
2CE04511525 15.9 38.2 66.6 70
2CE04512025 21.2 51.0 82.5 90
NONE 0.0 0.0 16.9 20
2CE04510746
2
6.8 8.2 19.2 20
2CE04511046
2
10.1 12.1 24.2 25
2CE04511546
2
13.6 16.4 29.4 30
2CE04512046
2
19.5 23.5 38.3 40
NONE 0.0 0.0 13.7 15
2CE04511058 10.6 10.2 19.9 20
2CE04511558 15.9 15.3 26.3 30
2CE04512058 21.2 20.4 32.7 35
Heater
Amps
3
Minimum
Circuit
Ampacity
Amps
Model
Tonnage Voltage
Compressors
460-3-60 6.2 45
1.3105
208-3-60
Max Fuse /
BRKR1 Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
OD Fan
Motor
FLA
4.4 10.0
230-1-60 18.0 105 1.3 4.4 10.0
208-1-60 18.0
10.0
230-3-60 11.4 90 1.3 4.4 10.0
9011.4 4.4
575-3-60 5.0 36 0.8
1.3
55
0.8 2.2
5.0
105 1.3
0.8 2.2
5.0
140 1.3
5.0
2.2 4.0
140 5.0 10.01.3
10.0
1.3 5.0 10.0208-3-60 14.1 105
10.0
5.0
575-3-60 5.8 44 0.8 2.2 4.0
4
24.4
460-3-60 7.1
230-3-60 14.1
208-1-60
230-1-60 24.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
Unitary Products Group 31
TABLE 22: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 54.0 80
2CE04510506 4.0 19.2 54.0 80
2CE04510706 5.6 26.9 54.4 80
2CE04511006 8.0 38.5 68.8 80
2CE04511506 11.9 57.2 92.3 100
2CE04512006 15.9 76.4 116.3 125
2CE04513006 22.2 106.7 154.2 175
NONE 0.0 0.0 54.0 80
2CE04510506 5.3 22.1 54.0 80
2CE04510706 7.5 31.3 59.8 80
2CE04511006 10.6 44.2 76.0 80
2CE04511506 15.9 66.3 103.6 110
2CE04512006 21.2 88.3 131.2 150
2CE04513006 29.6 123.3 174.9 175
NONE 0.0 0.0 37.9 50
2CE0451052524.0 11.1 37.9 50
2CE0451072525.6 15.5 40.2 50
2CE04511025 8.0 22.2 48.5 50
2CE04511525 11.9 33.0 62.0 70
2CE04512025 15.9 44.1 75.9 80
2CE04513025 22.2 61.6 97.8 100
NONE 0.0 0.0 37.9 50
2CE0451052525.3 12.7 37.9 50
2CE0451072527.5 18.0 43.3 50
2CE04511025 10.6 25.5 52.6 60
2CE04511525 15.9 38.2 68.6 70
2CE04512025 21.2 51.0 84.5 90
2CE04513025 29.6 71.2 109.8 110
NONE 0.0 0.0 19.1 25
2CE0451074626.8 8.2 20.6 25
2CE04511046210.1 12.1 25.6 30
2CE04511546213.6 16.4 30.8 35
2CE04512046219.5 23.5 39.7 40
2CE04513046228.8 34.6 53.7 60
NONE 0.0 0.0 15.3 20
2CE04511058 10.6 10.2 21.0 25
2CE04511558 15.9 15.3 27.4 30
2CE04512058 21.2 20.4 33.8 35
2CE04513058 30.4 29.3 44.9 45
NONE 0.0 0.0 41.7 60
2CE0451052524.0 11.1 41.7 60
2CE0451072525.6 15.5 41.7 60
2CE04511025 8.0 22.2 48.8 60
2CE04511525 11.9 33.0 62.3 70
2CE04512025 15.9 44.1 76.2 80
2CE04513025 22.2 61.6 98.0 100
NONE 0.0 0.0 41.7 60
2CE0451052525.3 12.7 41.7 60
2CE0451072527.5 18.0 43.6 60
2CE04511025 10.6 25.5 52.9 60
2CE04511525 15.9 38.2 68.8 70
2CE04512025 21.2 51.0 84.7 90
2CE04513025 29.6 71.2 110.0 125
NONE 0.0 0.0 21.3 30
2CE0451074626.8 8.2 21.3 30
2CE04511046210.1 12.1 25.9 30
2CE04511546213.6 16.4 31.2 35
2CE04512046219.5 23.5 40.1 45
2CE04513046228.8 34.6 54.1 60
NONE 0.0 0.0 17.0 20
2CE04511058 10.6 10.2 21.3 25
2CE04511558 15.9 15.3 27.7 30
2CE04512058 21.2 20.4 34.1 35
2CE04513058 30.4 29.3 45.2 45
28.9 165 1.3
10.06.6
6.6 10.0
6.6 10.0
6.6 10.0208-3-60 16.0
230-3-60 16.0 125 1.3
1.3125
0.8
0.8 3.3 5.0
4.0
10.0
6.8 10.0
0.8 3.3
6.8
3.6
5.0
230-3-60 18.9 146 1.3
73
4.058.4
Heater
Amps
575-3-60
460-3-60
575-3-60 7.6
208-3-60
460-3-60 0.8 3.6
1.3
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR1 Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Compressors OD Fan
Motor
FLA
Model
Tonnage Voltage
1.316528.9208-1-60
66.58.0
6
18.9
5
146
9.5
6.4 50
230-1-60
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
32 Unitary Products Group
TABLE 23: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 41.4 50
2CE04510506 4.0 19.2 46.0 50
2CE04510706 5.6 26.9 55.7 60
2CE04511006 8.0 38.5 70.1 80
2CE04511506 11.9 57.2 93.5 100
2CE04512006 15.9 76.4 117.6 125
NONE 0.0 0.0 41.4 50
2CE04510506 5.3 22.1 49.6 50
2CE04510706 7.5 31.3 61.1 70
2CE04511006 10.6 44.2 77.2 80
2CE04511506 15.9 66.3 104.8 110
2CE04512006 21.2 88.3 132.4 150
NONE 0.0 0.0 30.8 40
2CE04510525
2
4.0 11.1 32.9 40
2CE04510725
2
5.6 15.5 38.4 40
2CE04511025 8.0 22.2 46.8 50
2CE04511525 11.9 33.0 60.3 70
2CE04512025 15.9 44.1 74.2 80
NONE 0.0 0.0 30.8 40
2CE04510525
2
5.3 12.7 34.9 40
2CE04510725
2
7.5 18.0 41.6 45
2CE04511025 10.6 25.5 50.9 60
2CE04511525 15.9 38.2 66.8 70
2CE04512025 21.2 51.0 82.7 90
NONE 0.0 0.0 16.1 20
2CE04510746
2
6.8 8.2 19.7 20
2CE04511046
2
10.1 12.1 24.7 25
2CE04511546
2
13.6 16.4 29.9 30
2CE04512046
2
19.5 23.5 38.8 40
NONE 0.0 0.0 12.5 15
2CE04511058 10.6 10.2 19.7 20
2CE04511558 15.9 15.3 26.1 30
2CE04512058 21.2 20.4 32.5 35
NONE 0.0 0.0 49.4 70
2CE04510506 4.0 19.2 49.4 70
2CE04510706 5.6 26.9 55.7 70
2CE04511006 8.0 38.5 70.1 80
2CE04511506 11.9 57.2 93.5 100
2CE04512006 15.9 76.4 117.6 125
NONE 0.0 0.0 49.4 70
2CE04510506 5.3 22.1 49.6 70
2CE04510706 7.5 31.3 61.1 70
2CE04511006 10.6 44.2 77.2 80
2CE04511506 15.9 66.3 104.8 110
2CE04512006 21.2 88.3 132.4 150
NONE 0.0 0.0 34.1 45
2CE04510525
2
4.0 11.1 34.1 45
2CE04510725
2
5.6 15.5 38.4 45
2CE04511025 8.0 22.2 46.8 50
2CE04511525 11.9 33.0 60.3 70
2CE04512025 15.9 44.1 74.2 80
NONE 0.0 0.0 34.1 45
2CE04510525
2
5.3 12.7 34.9 45
2CE04510725
2
7.5 18.0 41.6 45
2CE04511025 10.6 25.5 50.9 60
2CE04511525 15.9 38.2 66.8 70
2CE04512025 21.2 51.0 82.7 90
NONE 0.0 0.0 17.3 20
2CE04510746
2
6.8 8.2 19.7 20
2CE04511046
2
10.1 12.1 24.7 25
2CE04511546
2
13.6 16.4 29.9 30
2CE04512046
2
19.5 23.5 38.8 40
NONE 0.0 0.0 13.5 15
2CE04511058 10.6 10.2 19.7 20
2CE04511558 15.9 15.3 26.1 30
2CE04512058 21.2 20.4 32.5 35
Model
Tonnage Voltage
Compressors OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
3
208-1-60 18.0 105
208-3-60 11.4 90
460-3-60 6.2 45
1.3 7.6 10.0
230-1-60 18.0 105 1.3 7.6 10.0
1.3 5.2 10.0
230-3-60 11.4 90 1.3 5.2 10.0
0.8 2.6 5.0
575-3-60 5.0 36 0.8 2 4.0
7.6 10.0
230-1-60 24.4 140 1.3 7.6 10.0
208-1-60
5.2 10.0
230-3-60 14.1 105 1.3 5.2 10.0
208-3-60
2.6 5.0
575-3-60 5.8 44 0.8 2 4.0
460-3-60 7.1 0.8
4
24.4 140
14.1 105
55
1.3
1.3
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
Unitary Products Group 33
TABLE 24: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 55.0 80
2CE04510506 4.0 19.2 55.0 80
2CE04510706 5.6 26.9 55.7 80
2CE04511006 8.0 38.5 70.1 80
2CE04511506 11.9 57.2 93.5 100
2CE04512006 15.9 76.4 117.6 125
2CE04513006 22.2 106.7 155.4 175
NONE 0.0 0.0 55.0 80
2CE04510506 5.3 22.1 55.0 80
2CE04510706 7.5 31.3 61.1 80
2CE04511006 10.6 44.2 77.2 80
2CE04511506 15.9 66.3 104.8 110
2CE04512006 21.2 88.3 132.4 150
2CE04513006 29.6 123.3 176.2 200
NONE 0.0 0.0 36.5 50
2CE0451052524.0 11.1 36.5 50
2CE0451072525.6 15.5 38.4 50
2CE04511025 8.0 22.2 46.8 50
2CE04511525 11.9 33.0 60.3 70
2CE04512025 15.9 44.1 74.2 80
2CE04513025 22.2 61.6 96.0 100
NONE 0.0 0.0 36.5 50
2CE0451052525.3 12.7 36.5 50
2CE0451072527.5 18.0 41.6 50
2CE04511025 10.6 25.5 50.9 60
2CE04511525 15.9 38.2 66.8 70
2CE04512025 21.2 51.0 82.7 90
2CE04513025 29.6 71.2 108.0 110
NONE 0.0 0.0 18.4 25
2CE0451074626.8 8.2 19.7 25
2CE04511046210.1 12.1 24.7 25
2CE04511546213.6 16.4 29.9 30
2CE04512046219.5 23.5 38.8 40
2CE04513046228.8 34.6 52.8 60
NONE 0.0 0.0 14.2 20
2CE04511058 10.6 10.2 19.7 20
2CE04511558 15.9 15.3 26.1 30
2CE04512058 21.2 20.4 32.5 35
2CE04513058 30.4 29.3 43.6 45
NONE 0.0 0.0 39.9 50
2CE0451052524.0 11.1 39.9 50
2CE0451072525.6 15.5 39.9 50
2CE04511025 8.0 22.2 46.5 50
2CE04511525 11.9 33.0 60.0 70
2CE04512025 15.9 44.1 73.9 80
2CE04513025 22.2 61.6 95.8 100
NONE 0.0 0.0 39.9 50
2CE0451052525.3 12.7 39.9 50
2CE0451072527.5 18.0 41.3 50
2CE04511025 10.6 25.5 50.6 60
2CE04511525 15.9 38.2 66.6 70
2CE04512025 21.2 51.0 82.5 90
2CE04513025 29.6 71.2 107.8 110
NONE 0.0 0.0 20.2 25
2CE0451074626.8 8.2 20.2 25
2CE04511046210.1 12.1 24.6 25
2CE04511546213.6 16.4 29.8 30
2CE04512046219.5 23.5 38.7 40
2CE04513046228.8 34.6 52.7 60
NONE 0.0 0.0 15.7 20
2CE04511058 10.6 10.2 19.7 20
2CE04511558 15.9 15.3 26.1 30
2CE04512058 21.2 20.4 32.5 35
2CE04513058 30.4 29.3 43.6 45
28.9
460-3-60
5.2
0.8 2.6
165
125
10.0
230-1-60 28.9 165 1.3 7.6 10.0
1.3 7.6208-1-60
10.0
230-3-60 16.0 125 1.3 5.2 10.0
208-3-60 16.0 1.3
2 4.0
8.0 66.5
1.3 5.0 10.0
230-3-60 18.9 146 1.3 5.0 10.0
208-3-60
0.8 2.5 5.0
575-3-60 7.6 58.4 0.8 2 4.0
460-3-60
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR1 Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Compressors
5
Heater
Amps
OD Fan
Motor
FLA
Model
Tonnage Voltage
5.0
575-3-60 6.4 50 0.8
6
18.9 146
9.5 73
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
036-21502-003-A-1105
34 Unitary Products Group
TABLE 25: PHYSICAL DATA
MODELS DM
036 048 060 072
EVAPORATOR
BLOWER
Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 12 X 11
Fan Motor HP (Direct Drive) 1/2 3/4 1 1
Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2 1 1/2
EVAPORATOR
COIL
Rows Deep 3 3 3 4
Fins Per Inch 13 13 13 13
Face Area (Sq. Ft.) 3.6 4.3 5.1 5.1
CONDENSER
FANS
Propeller Dia. (in.) 24 24 24 24
Fan Motor Hp 1/4 1/4 1/4 1/4
Nom. CFM 3400 3400 3400 3400
CONDENSER
COILS
Rows Deep 1 1 1 2
Fins Per Inch 16 16 22 16
Face Area (Sq. Ft.) 17.1 17.1 17.1 16.7
COMPRESSOR
(Qty. Per Unit) Scroll Type 1111
AIR
FILTERS
Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2 2
Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1 1
Total Face Area (sq. ft.) 6.3 6.3 6.3 6.3
CHARGE Refrigerant 22
(lbs./oz.) 5/8 6/8 6/8 10/0
TABLE 26: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI-
PLIER
208 208 1.00
240 230 0.92
480 460 0.92
600 575 0.92
TABLE 27: VOLTAGE LIMITATIONS1
1. Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY VOLTAGE
MIN. MAX.
208/230-1-60 187 253
208/230-3-60 187 253
460-3-60 414 506
575-3-60 540 630
036-21502-003-A-1105
Unitary Products Group 35
TYPICAL POWER WIRING
TYPICAL CONTROL WIRING
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
RV
YC
GF
R
Y1
C
Y2
THERMOSTAT1
TERMINALS
UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
COOLING ONLY (24 VOLT THERMOSTAT)
1
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
G
RC
Y
R
Y1
Y2
W1
W
W2
G
C
G
RH
THERMOSTAT
TERMINALS
UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
ADD
JUMPER
1
COOLING / HEATING (24 VOLT THERMOSTAT)
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
1
RC
RH
Y1
Y2
W1
W2
G
LED 1
LED 2
COM
A1
A2
T
T
B
R
Y1
Y2
G
C
X
OCC
W2
W1
THERMOSTAT
1
TERMINALS UNIT TERMINAL
STRIP TB1 24 VOLT
TRANSFORMER
TO REMOTE SENSOR
2TH040702224 IF USED
NOT
USED
ADD
JUMPER
ADD
JUMPER
4
4
3
2
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
RH
RC
Y
W
G
R
Y1
W1
C
G
ADD
JUMPER
THERMOSTAT
1
TERMINALS UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
036-21502-003-A-1105
36Unitary Products Group
FIGURE 3 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
036-21502-003-A-1105
Unitary Products Group 37
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD
DETAIL “A”
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
DETAIL “B”
036-21502-003-A-1105
38 Unitary Products Group
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
FIGURE 8 - DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 28: UTILITIES ENTRY
HOLE OPENING SIZE (DIA.) USED FOR
A7/8” KO1Control Wiring2Side
Bottom
B2” KO1Power WiringSide
Bottom
C1-5/8” KO Gas Piping (Front)
D1-1/2” KO Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
A,B
WIRING ENTRY
(See Detail “B”)
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR
ACCESS
FILTER
ACCESS
DOT PLUGS
TABLE 29: MINIMUM CLEARANCES
LOCATION CLEARANCE
Front 24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access) 24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil) 24”
Below Unit10”
Above Unit272” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
036-21502-003-A-1105
Unitary Products Group 39
FIGURE 9 - TYPICAL APPLICATIONS
036-21502-003-A-1105
40 Unitary Products Group
FIGURE 10 - FOUR AND SIX POINT LOADING
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
E
F
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
TABLE 30: DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL 4-Point Loading (lb) 6-Point Loading (lb)
ABCDABCDEF
DM036 Cooling/ Electric 565 125123157160848382104 105 107
DM036N04 605 134 132168171908988112113 114
DM036D06 615 137134 171174919089113115116
DM036N08 625 139 136173177 93 9291 115 117118
DM036D10 635 141 138 176 179949392117119 120
DM048 Cooling/ Electric 615 137134 171174919089113115116
DM048(D,N)06 665 148 145 184 188 99 98 96123124126
DM048(D,N)10 685 152149 190 194 102100 99 126 128129
DM060 Cooling/ Electric 640 142140 178 181 95 94 93 118 119 121
DM060D06 690 153 150 191 195 102101 100 127 129130
DM060N08 700 155 153 194 198 104 103 101 129131132
DM060(D,N)10 710 158 155 197201 105 104 103 131 132134
DM072 Cooling/ Electric 720 160157200 203 107106104 133 134 136
DM072D06 770 171168214 218 114 113 112142144 145
DM072N08 780 173170216220116114 113 144 146147
DM072(D,N)10 790 175172 219 223117116114 146147149
TABLE 31: CENTER OF GRAVITY
DIMENSION 3 - 5 TON 6 TON
X40-¾”44”
Y19-¾” 22”
036-21502-003-A-1105
Unitary Products Group 41
TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE 3 TON 4 TON 5 TON 6 TON
BASIC
UNIT
DM (Cooling Only) 565615 640 720
DM
(Gas/Electric)
N04 605 - - -
N06-665- -
N08 625-700 780
N10 - 685 710 790
D06615 665690 770
D10 635 685 710 790
OPTIONS
Economizer 50
Motorized Damper 26
Electric Heater
5 - 7 kW18
10 - 15 kW23
20 - 30 kW28
ACCY.
Roof Curb 92
Barometric Relief / Fixed Air Damper 10
Belt-Drive Blower 5
FIGURE 11 - ROOF CURB DIMENSIONS
036-21502-003-A-1105
42Unitary Products Group
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000TM units are convertible single package-
units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 1000 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 3 thru 5 ton units shall have minimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER ratings of
9.0. They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge sup-
ply/return, and be available with factory installed options or
field installed accessories. The units shall be factory wired,
piped, charged with R-22 refrigerant and factory tested prior
to shipment. All unit wiring shall be both numbered and color
coded. All units the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall be
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236
standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower shall
not exceed the motors nameplate horsepower rating, plus the
service factor. Units shall be designed not to operate above
service factor. Fan wheel shall be double-inlet type with for-
ward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.Shall be internally protected with internal high-pres-
sure relief and over temperature protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent
mounting.
Coils:
a.Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
036-21502-003-A-1105
Unitary Products Group 43
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice expansion devices.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d. The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
d. High-pressure switch.
e. Freeze-protection thermostat, evaporator coil.
f.If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i. Unit control board shall have on-board diagnostics
and fault code display.
j. Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k. Control board shall monitor each refrigerant safety
switch independently.
l. Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
GAS HEATING SECTION (SINGLE OR 2 STAGE)
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
a. Primary and auxiliary high-temperature limit
switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heat-
ers and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and auto-
matic reset to prevent the heating element system from oper-
ating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where
required).
UNIT OPERATING CHARACTERISTICS
a. Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240. The compres-
sor, with standard controls, shall be capable of oper-
ation down to 0°F outdoor temperature. Unit shall be
provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat
only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•Compressor 5 Years
•He
at Exchanger 10 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
Subject to change without notice. Printed in U.S.A.036-21502-003-A-1105
Copyright © 2005 by Unitary Products. All rights reserved. Supersedes: 036-21502-002-B-0504
Unitary 5005 Norman
Products York O
K
Group Drive 73069
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER- Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
•MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
•HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
•GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•POWER EXHAUST OPTION - To work in conjunction
with economizers.
• ELECTRIC HEATERS
•ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assem-
bling.
• MANUAL OUTDOOR AIR DAMPER
•COIL GUARD KIT - Guard for cooling coil.
• HAIL GUARD
• FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•POWER EXHAUST OPTION - To work in conjunction
with economizers.
• STAINLESS STEEL HEAT EXCHANGER
• STAINLESS STEEL DRAIN PAN
• BOTTOM DRAIN CONNECTION
• TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
• ELECTRONIC SINGLE ENTHALPY ECONOMIZER
• DIRTY FILTER SWITCH
• PHASE MONITOR
• COIL GUARD
• POWERED GFI CONVENIENCE OUTLET
• NON-POWERED GFI CONVENIENCE OUTLET
• BAS CONTROLS (
Simplicity
™ INTELLI- Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
• BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
• HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
• 2" PLEATED FILTERS
• DISCONNECT SWITCH
• SUPPLY AIR SMOKE DETECTOR
• RETURN AIR SMOKE DETECTOR