DESCRIPTION
YORK Sunline 2000™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.

TECHNICAL GUIDE

SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)

All units include:
•

Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards

•

Permanently lubricated motors

•

Bottom or side air discharge configuration capability
(field convertible)

•

Manufactured under the quality standards of ISO9001

•

SimplicityTM Control Board

•

Copper tube/aluminum fin coils

•

Easy access to all components

•

Rigging holes in base rails for lifting

•

Fork lift slots on three sides

•

Single point power connection

•

Complete factory package - tested, charged and wired

•

CSA agency listing on all units

WARRANTY
•

Factory Limited Parts Warranty

•

One-year parts warranty

•

A Five-year parts warranty on the compressor and
electric heat elements.

•

Ten-year parts warranty on the gas-fired heat
exchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21502-003-A-1105

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13

9

SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 20

10 SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 21
11 SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 22

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 42

12 SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 23

LIST OF FIGURES

13 SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON
DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . . 24

Fig. #

Pg. #

14 BELT DRIVE BLOWER MOTOR AND DRIVE DATA. . 24
15 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 25

1

UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2

TYPICAL FIELD POWER & CONTROL WIRING . . . . 35

3

UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . 36

4

UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

5

UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 37

19 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 28

6

UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . . 37

20 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 29

7

UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . . 38

8

DISCONNECT/BLOWER ACCESS LOCATION . . . . . 38

21 ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . 30

9

TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 39

10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 40

16 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 25
17 ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 26
18 ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 27

22 ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . 31

11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 41

23 ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . 32

LIST OF TABLES

24 ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . 33

Tbl. #

Pg. #

1

SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . 15

2

CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . 15

3

GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 15

4

2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . 15

5

DM036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 16

6

DM048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 17

7

DM060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 18

8

DM072 COOLING CAPACITIES (6 TON) . . . . . . . . . . 19

2

25 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
26 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 34
27 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 34
28 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
29 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 38
30 DM 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 40
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 41

Unitary Products Group

036-21502-003-A-1105

PRODUCT NOMENCLATURE

7RQ6XQOLQH0RGHO1XPEHU1RPHQFODWXUH
' 0  1 $  $ $$ 
3URGXFW*HQHUDWLRQ
3URGXFW&DWHJRU\

 )LUVW*HQHUDWLRQ

' $LU&RQG6LQJOH3DFNDJH

9ROWDJH
3URGXFW,GHQWLILHU






0 56WDQGDUG(IILFLHQF\'&*'&(

1RPLQDO&RROLQJ
&DSDFLW\0%+










,QVWDOODWLRQ2SWLRQV
$ 1R2SWLRQV,QVWDOOHG
% 2SWLRQ
& 2SWLRQ
' 2SWLRQV	
( 2SWLRQ
) 2SWLRQ
* 2SWLRQV	
+ 2SWLRQV	
- 2SWLRQV	
. 2SWLRQV	
/ 2SWLRQV	
0 2SWLRQV	
1 2SWLRQV	
3 2SWLRQV	
4 2SWLRQV	
5 2SWLRQV	
6 2SWLRQ
7 2SWLRQV	
8 2SWLRQV	
9 2SWLRQV	
: 2SWLRQV	
; 2SWLRQV	
< 2SWLRQV	
= 2SWLRQV	

7RQ
7RQ
7RQ
7RQ

+HDW7\SH	1RPLQDO+HDW&DSDFLW\
& &RROLQJ2QO\6XLWDEOHIRUILHOGLQVWDOOHGHOHFWULFKHDW

*DV+HDW2SWLRQV
1
1
1
1
'
'
6

0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH

0%+2XWSXW6WDLQOHVV6WHHO6WDJH

6
6
6
7
7

0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH


(
(
(
(
(
(

N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW

$GGLWLRQDO2SWLRQV
6HH1H[W3DJH

2SWLRQV






(OHFWULF+HDW2SWLRQV

'LVFRQQHFW
1RQ3ZU
G&RQY2XOWHW
6PRNH'HWHFWRU6$
6PRNH'HWHFWRU5$
3ZU
G&RQY2XWOHW


'7 0%+2XWSXWRQ0RGHOV

$LUIORZ
$
%
'
/
1
3
5
<

Unitary Products Group

'LUHFW'ULYH
'LUHFW'ULYH6LQJOH,QSXW(FRQR
'LUHFW'ULYH0RWRUL]HG'DPSHU
'LUHFW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHU3OHDWHG)LOWHUV([WUD[IUPU	FLUFXLWENU
%HOW'ULYH
%HOW'ULYH6LQJOH,QSXW(FRQR
%HOW'ULYH0RWRUL]HG'DPSHU
%HOW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHUZ3OHDWHG)LOWHUV

3

036-21502-003-A-1105

PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature

Standard Cabinet
AA
AB
AC
AD
AE
AF
AG
AH
AJ
AK
AL
AM
AN
AS
CA
CB
CC
CD
CE
CF
CG
CH
CJ
CK
CL
CM
CN
CP
CQ
CR
CS
CT
CU
CV
CW
CX
JA
JB
JC
JD
JE
JF
JG
JH
JJ
JK
JL
JM
JN
JP
JQ

4

None
Phase Monitor
Coil Guard
Dirty Filter Switch
Phase Monitor & Coil Guard
Phase Monitor & Dirty Filter Switch
Coil Guard & Dirty Filter Switch
Phase Monitor, Coil Guard, & Dirty Filter Switch
SS Drain Pan
SS Drain Pan & Phase Monitor
SS Drain Pan & Coil Guard
SS Drain Pan & Dirty Filter Switch
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
Bottom Drain Connection
CPC Controller with Dirty Filter Switch & Air Proving Switch
CPC Controller, DFS, APS & Phase Monitor
CPC Controller, DFS, APS & Coil Guard
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Cond. Coil
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. Coil
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Johnson UNT Controller, DFS, APS & Phase Monitor
Johnson UNT Controller, DFS, APS & Coil Guard
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

Unitary Products Group

036-21502-003-A-1105

Standard Cabinet
JR
JS
JT
JU
JV
JW
JX
HA
HB
HC
HD
HE
HF
HG
HH
HJ
HK
HL
HM
HN
HP
HQ
HR
HS
HT
HU
HV
HW
HX
NA
NB
NC
ND
NE
NF
NG
NH
NJ
NK
NL
NM
NN
NP
NQ
NR
NS
NT
NU
NV
NW
NX
TA
TB
TC

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
Novar ETC-3 Controller, DFS, APS & Phase Monitor
Novar ETC-3 Controller, DFS, APS & Coil Guard
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Technicoat Condenser Coil
Technicoat Condenser Coil & Phase Monitor
Technicoat Condenser Coil & Coil Guard

Unitary Products Group

5

036-21502-003-A-1105

Standard Cabinet
TD
TE
TF
TG
TH
TJ
TK
TL
TM
TN
TP
TQ
TR
TS
TT
TU
TV
TW
TX
TY
TZ
T1
T3
T4
T6
T7
T9
LA
LB
LC
LD
LE
LF
LG
LH
LJ
LK
LL
LM
LN
LP
LQ
LR
LS
LT
LU
LV
LW
LX
WA
WB
WC
WD
WE

6

Technicoat Condenser Coil & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil
Technicoat Evaporator Coil & Phase Monitor
Technicoat Evaporator Coil & Coil Guard
Technicoat Evaporator Coil & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils
Technicoat Evaporator & Condenser Coils & Phase Monitor
Technicoat Evaporator & Condenser Coils & Coil Guard
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Condenser & SS Drain Pan
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & SS Drain Pan
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils & SS Drain Pan
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Simplicity Intelli-Comfort Controller
Simplicity Intelli-Comfort Controller, & Phase Monitor
Simplicity Intelli-Comfort Controller, & Coil Guard
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller
Intelli-Comfort w/Mod Link Controller, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil

Unitary Products Group

036-21502-003-A-1105

Standard Cabinet
WF
WG
WH
WJ
WK
WL
WM
WN
WP
WQ
WR
WS
WT
WU
WV
WW
WX

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

Hinged Filter Door & Toolless Access Cabinet
BA
BB
BC
BD
BE
BF
BG
BH
BJ
BK
BL
BM
BN
BS
DA
DB
DC
DD
DE
DF
DG
DH
DJ
DK
DL
DM
DN
DP
DQ
DR
DS
DT
DU
DV
DW

Hinged Filter Door & Toolless Access Panels
Phase Monitor, Hinged Filter Door & Toolless Access Panels
Coil Guard, Hinged Filter Door & Toolless Access Panels
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

Unitary Products Group

7

036-21502-003-A-1105

Hinged Filter Door & Toolless Access Cabinet
DX
EA
EB
EC
ED
EE
EF
EG
EH
EJ
EK
EL
EM
EN
EP
EQ
ER
ES
ET
EU
EV
EW
EX
GA
GB
GC
GD
GE
GF
GG
GH
GJ
GK
GL
GM
GN
GP
GQ
GR
GS
GT
GU
GV
GW
GX
PA
PB
PC
PD

8

CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

Unitary Products Group

036-21502-003-A-1105

Hinged Filter Door & Toolless Access Cabinet
PE
PF
PG
PH
PJ
PK
PL
PM
PN
PP
PQ
PR

Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
QF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

Unitary Products Group

9

036-21502-003-A-1105

Hinged Filter Door & Toolless Access Cabinet
QG
QH
QJ
QK
QL
QM
QN
QP
QQ
QR
QS
QT
QU
QV
QW
QX

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels

10

Unitary Products Group

036-21502-003-A-1105

FEATURES

switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.

All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard
to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. For bottom duct,
remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct,
remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
•

Single enthalpy economizer

•

Motorized outdoor air damper

Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•

Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.

•

Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.

•

Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.

•

Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit

Unitary Products Group

Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.

•

On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.

All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
•

Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.

•

Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module for
100% shut-off and all of the safety controls required to
meet the latest ANSI standards.

Simplicity™ Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•

•

The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•

Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.

•

BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as Simplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC.

11

036-21502-003-A-1105

FIGURE 1 -

UNIT CUTAWAY

FACTORY-INSTALLED OPTIONS
•

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

•

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

12

PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes

Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•

ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.

•

FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.

•

CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.

•

DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.

•

BAS - Building Automation System Controls
Simplicity™ INTELLI-Comfort™ CONTROL - The
York® Simplicity™ INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving

Unitary Products Group

036-21502-003-A-1105

switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor
to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to
provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity™
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate
comfort.
•

•

•

•

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.

•

STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.

•

BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.

•

PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.

•

DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.

•

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.

Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.

NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.

FIELD-INSTALLED ACCESSORIES
•

JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.

•

HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.

•

SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.

•

•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

Unitary Products Group

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.

•

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.

•

ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.

13

036-21502-003-A-1105

•

ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.

•

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.

•

ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.

•

BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.

•

FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.

•

CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.

•

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

•

HAIL GUARD -Hail Guard Kit is available to protect coils
from damage. This is a sloped hood that fits above the
outdoor coil.

•

GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.

Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•

HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.

•

PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.

•

HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.

•

LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.

•

POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.

14

Unitary Products Group

036-21502-003-A-1105

TABLE 1: SOUND POWER RATING1

UNIT
SIZE

ESP

SOUND POWER (db 10-12 Watts)

BLOWER

Octave Band Centerline Frequency (Hz)

CFM
IWG

SPEED

KW

63

125

250

500

1,000

2,000

4,000

8,000

SWL
dB(A)

dB(A)
@
10Ft.2

036

1,200

0.6

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1,600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2,000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

072

2,200

0.3

HIGH

1.35

87

87

77

70

72

65

60

55

77

44

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)1

TABLE 3: GAS HEAT RATINGS1

MODEL

MBH

EER2

SEER3

DM036

36.0

9.1

10.0

DM048

47.4

9.0

10.0

DM060

59.0

9.1

10.0

DM072

72.0

9.0

-

1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.

MODEL

MBH
INPUT

MBH
OUTPUT

AFUE
(%)

TEMP
RISE ºF

DM036N04
DM036N08

50
100

40
80

80.9
80.5

15 - 45
40 - 70

DM048N06
DM048N10

75
125

60
100

80.9
80.3

25 - 55
45 - 75

DM060N08
DM060N10

100
125

80
100

80.5
80.3

25 - 55
35 - 65

DM072N08
DM072N10

100
125

80
100

80.5
80.3

25 - 55
35 - 65

1. All units are single-stage heating.

TABLE 4: 2 STAGE GAS HEAT RATINGS
MODEL1

MBH INPUT

MBH OUTPUT

1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE

STEADY STATE EFFICIENCY
1ST STAGE

2ND STAGE

RISE
MIN.

MAX.

MINIMUM HEATING
AIRFLOW (CFM)

DM036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DM036D10

69

115

55.2

92

80.0

80.2

55

90

950

DM048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DM048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM060D06

45

75

35.8

60.8

79.4

81.1

35

70

1010

DM060D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM072D06

45

75

35.8

60.8

79.4

81.1

35

70

1230

DM072D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

1. Models are 3Ø only.

Unitary Products Group

15

036-21502-003-A-1105

TABLE 5: DM036 COOLING CAPACITIES (3 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

85°F
TOTAL
1

CFM

1750

1475

1200

1050

900

POWER

CAP.
MBH

INPUT2 kW

WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

45
43
39
40
44
41
38
39
42
40
36
37
41
38
35
36
39
37
34
34

3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9

95°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

TOTAL
1

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

83

80

77

74

71

68

CAP.
MBH

INPUT2 kW

86
35
43
39
40
31
39
38
39
28
35
36
37
26
32
35
36
24
30
34
34

30
38
39
40
28
35
38
39
25
32
36
37
23
30
35
36
21
27
33
34

26
34
39
40
24
31
37
39
22
28
35
37
20
27
33
35
19
25
30
33

21
29
34
35
20
27
33
35
18
25
31
34
17
24
30
32
16
22
28
30

17
25
30
31
16
23
29
31
15
22
28
31
14
21
27
29
14
20
25
27

20
25
26
19
25
27
18
25
27
18
24
26
17
23
25

16
21
22
16
21
23
15
21
24
15
21
23
15
20
22

43
41
36
38
42
39
36
37
41
38
35
36
39
37
33
34
38
36
32
33

3.3
3.3
3.3
3.2
3.3
3.3
3.3
3.2
3.3
3.2
3.3
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.1

86

83

80

77

74

71

68

35
41
36
38
31
37
36
37
28
34
35
36
26
32
33
34
23
29
32
33

30
38
36
38
27
35
36
37
24
31
35
36
23
29
33
34
21
26
31
33

26
34
36
38
23
31
35
36
21
28
34
35
20
26
31
32
18
24
29
30

21
29
32
33
20
27
31
32
18
25
30
32
17
23
28
30
16
21
26
27

17
25
27
29
16
23
27
28
14
21
27
28
14
20
25
27
13
19
24
25

21
23
24
19
23
25
18
24
25
17
22
24
16
21
22

16
18
20
15
19
21
15
20
22
14
20
21
14
19
20

TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

105°F
TOTAL
1

CFM

1750

1475

1200

1050

900

POWER

CAP.
MBH

INPUT2 kW

WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

41
38
34
35
40
37
33
34
39
36
32
33
37
35
31
32
36
33
30
31

3.7
3.7
3.7
3.6
3.7
3.6
3.7
3.6
3.7
3.6
3.6
3.6
3.6
3.6
3.6
3.5
3.6
3.6
3.6
3.5

115°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

TOTAL
1

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

83

80

77

74

71

68

CAP.
MBH

INPUT2 kW

86
34
38
34
35
30
36
33
34
27
34
32
33
25
31
31
32
22
28
30
31

29
37
34
35
26
34
33
34
24
30
32
33
22
28
31
32
20
25
29
30

25
33
34
35
23
30
33
34
20
27
32
33
19
25
29
30
17
23
27
28

20
28
30
31
19
26
29
30
17
24
29
29
16
22
27
27
15
20
24
25

16
24
25
26
15
22
25
26
14
20
25
26
13
19
24
24
12
18
22
22

19
21
22
18
21
22
17
22
23
16
21
21
15
19
20

15
16
17
14
17
18
14
19
19
13
18
18
13
17
17

39
36
32
33
38
35
31
32
37
34
30
31
36
32
29
30
34
31
28
28

4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
4.1
4.0
4.0
3.9
4.1
4.0
4.0
3.9
4.0
4.0
4.0
3.9

86

83

80

77

74

71

68

33
36
32
33
30
34
31
32
26
33
30
31
24
30
29
30
21
27
28
28

28
36
32
33
26
33
31
32
23
30
30
31
21
27
29
29
19
24
28
28

24
32
32
33
22
29
31
32
20
26
30
31
18
24
28
28
16
22
25
25

19
27
27
28
18
25
27
28
16
23
27
27
15
21
25
25
14
19
22
23

15
23
23
24
14
21
23
24
13
20
24
24
12
18
22
22
11
17
20
20

18
18
19
17
19
20
16
20
21
15
19
19
14
17
17

14
14
15
13
15
16
13
17
17
12
16
16
11
15
15

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

NOMINAL RATING

16

Unitary Products Group

036-21502-003-A-1105

TABLE 6: DM048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

TOTAL

INPUT2 kW

CFM

WB °F

CAP.1
MBH

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

60
55
51
49
58
53
49
47
56
51
47
46
54
49
45
44
52
47
43
42

4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9

2000

1800

1600

1400

1200

85°F

95°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

TOTAL

86

83

80

77

74

71

68

CAP.1
MBH

44
53
51
49
41
49
49
47
38
46
47
46
35
42
45
44
32
39
43
42

39
48
51
49
36
45
49
47
34
41
47
46
31
38
45
44
29
35
43
42

33
42
51
49
31
40
48
47
29
37
45
46
27
34
42
43
25
32
39
39

28
37
45
44
26
35
43
43
25
32
41
41
23
30
38
39
22
28
36
36

23
32
40
39
21
30
38
38
20
28
36
37
19
26
34
35
18
25
32
32

26
34
33
25
33
33
24
32
32
22
30
31
21
29
29

21
29
28
20
28
28
19
27
28
19
26
27
18
25
25

60
52
48
47
57
50
46
45
55
48
44
44
53
47
43
42
51
45
41
41

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER
INPUT2 kW
4.5
4.5
4.4
4.3
4.5
4.5
4.4
4.3
4.6
4.5
4.4
4.4
4.5
4.5
4.4
4.3
4.5
4.4
4.3
4.3

86

83

80

77

74

71

68

44
52
48
47
41
49
46
45
38
45
44
44
35
41
43
42
32
38
41
41

39
47
48
47
36
44
46
45
33
40
44
44
31
38
43
42
28
35
41
41

33
42
48
47
31
39
46
45
29
36
44
44
27
34
41
41
25
31
38
38

28
36
42
42
26
34
41
40
24
31
40
39
23
30
37
37
21
28
35
34

23
31
37
36
21
29
36
36
20
27
35
35
19
26
33
33
18
24
31
31

25
32
31
24
31
31
23
31
30
22
29
29
21
28
27

20
26
26
19
26
26
18
26
26
18
25
25
17
24
24

TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

105°F
TOTAL
1

CFM

2000

1800

1600

1400

1200

POWER

CAP.
MBH

INPUT2 kW

WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

56
49
45
44
55
48
43
43
53
46
42
41
51
44
40
40
49
42
38
38

5.1
5.0
4.9
4.9
5.0
5.0
4.9
4.9
5.0
4.9
4.9
4.8
5.0
4.9
4.8
4.8
4.9
4.9
4.8
4.8

115°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

TOTAL
1

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

83

80

77

74

71

68

CAP.
MBH

INPUT2 kW

86
42
49
45
44
39
47
43
43
36
44
42
41
33
41
40
40
30
37
38
38

37
46
45
44
34
43
43
43
32
40
42
41
29
37
40
40
27
34
38
38

31
40
45
44
29
38
43
43
28
35
42
41
26
33
39
38
23
30
36
35

26
35
39
39
24
33
38
38
23
31
37
37
22
29
35
34
20
27
32
32

21
29
34
33
20
28
33
33
19
26
33
32
18
25
31
30
16
23
29
28

24
28
28
23
28
28
22
28
28
21
27
26
20
25
25

19
23
22
18
23
23
17
24
23
17
23
22
16
22
21

53
46
41
41
52
45
40
40
51
44
39
39
48
42
37
37
46
39
35
35

5.6
5.5
5.4
5.4
5.5
5.4
5.4
5.4
5.5
5.4
5.3
5.3
5.5
5.3
5.3
5.3
5.4
5.3
5.3
5.3

86

83

80

77

74

71

68

40
46
41
41
38
45
40
40
35
44
39
39
32
40
37
37
29
36
35
35

35
44
41
41
33
42
40
40
31
39
39
39
28
36
37
37
26
33
35
35

29
39
41
41
28
37
40
40
26
35
39
39
24
32
36
36
22
29
33
33

24
33
36
35
23
32
35
35
22
30
35
34
20
28
32
32
19
26
29
29

19
28
30
30
18
27
30
30
17
26
30
30
16
24
28
28
15
22
26
26

23
25
25
22
26
25
21
26
25
20
24
24
19
22
22

17
20
19
17
21
20
17
21
21
16
20
20
15
19
19

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

NOMINAL RATING

Unitary Products Group

17

036-21502-003-A-1105

TABLE 7: DM060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

TOTAL

INPUT2 kW

CFM

WB °F

CAP.1
MBH

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

68
62
57
55
67
62
56
54
66
61
55
53
63
58
53
51
60
56
51
49

4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.6
4.8
4.7
4.6
4.6
4.8
4.7
4.6
4.6

2500

2250

2000

1750

1500

85°F

95°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

TOTAL

86

83

80

77

74

71

68

CAP.1
MBH

50
62
57
55
48
59
56
54
45
55
55
53
41
51
53
51
37
46
51
49

44
56
57
55
42
53
56
54
39
50
55
53
36
46
53
51
33
42
51
49

38
50
57
55
36
47
56
54
34
44
55
53
31
41
51
49
29
38
47
45

32
43
51
48
30
41
50
48
29
39
50
48
27
36
47
44
25
34
43
41

25
37
44
42
24
35
45
42
23
34
45
42
22
32
42
40
21
30
39
37

31
38
36
30
39
36
28
39
37
27
37
35
26
35
33

24
32
29
24
33
31
23
34
32
22
32
30
21
31
29

65
60
53
51
65
59
53
50
64
58
52
50
61
56
50
47
58
53
47
45

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER
INPUT2 kW
5.6
5.3
5.3
5.4
5.4
5.2
5.2
5.3
5.3
5.1
5.1
5.2
5.4
5.1
5.2
5.2
5.4
5.2
5.2
5.3

86

83

80

77

74

71

68

50
60
53
51
47
57
53
50
44
54
52
50
40
49
50
47
36
44
47
45

43
54
53
51
41
51
53
50
39
48
52
50
35
44
50
47
32
40
47
45

37
48
53
51
35
45
53
50
33
43
52
50
31
39
48
46
28
36
44
42

31
42
47
44
29
40
47
44
28
38
47
44
26
35
43
41
24
32
40
38

24
35
41
38
23
34
41
39
22
32
42
39
21
30
39
36
20
28
36
34

29
34
32
28
35
33
27
36
34
25
34
32
24
32
29

23
28
25
22
29
27
22
31
28
21
29
27
20
27
25

TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

105°F
TOTAL
1

CFM

2500

2250

2000

1750

1500

POWER

CAP.
MBH

INPUT2 kW

WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

61
55
49
47
61
54
48
46
60
54
48
46
57
51
45
43
54
48
43
41

6.1
5.9
5.9
5.9
6.0
5.9
5.8
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8

115°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

TOTAL
1

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

83

80

77

74

71

68

CAP.
MBH

INPUT2 kW

86
48
55
49
47
45
53
48
46
42
52
48
46
38
47
45
43
34
42
43
41

41
52
49
47
39
49
48
46
37
47
48
46
34
42
45
43
30
38
43
41

35
46
49
47
33
44
48
46
32
41
48
46
29
38
44
42
26
34
39
38

29
39
42
40
28
38
42
40
26
36
43
41
24
33
39
37
22
30
35
34

22
33
36
34
22
32
37
35
21
31
37
35
19
28
34
32
18
26
31
30

27
30
28
26
31
29
25
32
30
24
30
28
22
27
26

20
23
21
20
25
23
20
27
25
19
25
23
18
23
21

57
50
44
42
57
50
44
42
57
50
44
42
53
46
41
39
49
43
38
37

6.7
6.6
6.5
6.5
6.6
6.5
6.4
6.4
6.6
6.5
6.4
6.3
6.5
6.4
6.3
6.3
6.5
6.4
6.3
6.2

86

83

80

77

74

71

68

46
50
44
42
43
50
44
42
41
50
44
42
37
45
41
39
33
40
38
37

39
50
44
42
38
47
44
42
36
45
44
42
32
41
41
39
28
36
38
37

33
43
44
42
32
42
44
42
30
40
44
42
27
36
39
38
24
32
35
34

27
37
38
36
26
36
38
36
25
34
38
37
23
31
35
33
20
28
31
30

20
31
31
30
20
30
32
31
20
29
33
32
18
26
30
29
16
24
27
26

24
25
23
24
26
25
24
28
26
22
25
24
20
23
22

18
19
17
18
20
19
18
22
21
17
21
19
16
19
18

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

NOMINAL RATING

18

Unitary Products Group

036-21502-003-A-1105

TABLE 8: DM072 COOLING CAPACITIES (6 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

TOTAL

INPUT2 kW

CFM

WB °F

CAP.1
MBH

72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

80
80
70
68
82
82
71
69
83
83
73
71
79
79
69
67
74
74
65
63

5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.6
5.6
5.4
5.5

2700

2550

2400

2100

1800

85°F

95°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

TOTAL

86

83

80

77

74

71

68

CAP.1
MBH

63
76
70
68
60
73
71
69
58
70
73
71
54
65
69
67
50
60
65
63

55
68
70
68
53
65
71
69
51
63
73
71
48
59
69
67
44
55
65
63

47
60
70
68
46
58
70
69
44
56
70
71
41
53
66
67
39
50
62
63

40
53
62
60
38
51
62
62
37
49
63
64
35
47
60
61
34
44
57
58

32
45
55
52
31
43
55
55
30
42
56
57
29
40
54
54
28
39
51
52

37
47
45
36
48
47
35
49
50
34
47
48
34
46
47

30
39
37
29
41
40
28
42
43
28
41
42
28
41
42

77
77
71
71
76
76
70
70
75
75
69
69
73
73
67
67
71
71
65
65

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER
INPUT2 kW
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.2
6.3

86

83

80

77

74

71

68

63
75
71
71
60
73
70
70
58
70
69
69
53
65
67
67
49
59
65
65

55
68
71
71
53
66
70
70
51
64
69
69
47
59
66
66
43
54
63
63

47
60
71
71
46
58
69
70
44
57
68
68
41
52
63
63
38
48
58
58

40
53
63
63
39
51
62
62
37
50
61
61
35
46
57
57
33
43
53
53

32
45
56
56
31
44
55
55
30
43
54
54
29
40
51
51
27
38
47
47

37
48
48
36
48
48
36
47
47
34
45
45
32
42
42

30
40
40
29
40
40
29
40
40
28
38
39
27
37
37

TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL

105°F
TOTAL
1

CFM

2700

2550

2400

2100

1800

POWER

CAP.
MBH

INPUT2 kW

WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57

76
71
64
64
76
71
64
64
75
70
64
64
73
68
61
61
70
65
59
59

7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.0
7.0
6.9

115°F

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

TOTAL
1

SENSIBLE CAPACITY1
ENTERING DRY BULB, °F

POWER

83

80

77

74

71

68

CAP.
MBH

INPUT2 kW

86
61
70
64
64
59
69
64
64
56
68
64
64
52
63
61
61
47
57
59
59

53
66
64
64
51
64
64
64
49
61
64
64
45
56
61
61
41
51
58
58

45
58
64
64
44
56
64
64
43
54
63
63
39
50
58
58
36
46
54
53

38
50
56
56
37
49
56
56
36
48
56
56
33
44
52
52
31
41
48
48

30
43
49
49
29
42
49
49
29
41
49
49
27
38
46
46
25
35
43
43

35
41
41
34
42
42
34
42
42
32
40
40
30
38
37

27
34
34
27
35
34
27
35
35
26
34
34
25
32
32

75
65
57
57
76
66
58
58
76
66
59
59
73
63
56
56
69
60
53
53

7.9
7.8
7.8
7.7
7.9
7.9
7.8
7.7
8.0
7.9
7.8
7.7
7.9
7.8
7.7
7.7
7.8
7.8
7.7
7.6

86

83

80

77

74

71

68

59
65
57
57
57
66
58
58
55
66
59
59
50
61
56
56
45
55
53
53

51
64
57
57
49
61
58
58
48
59
59
59
44
54
56
56
40
49
53
53

43
56
57
57
42
54
58
58
41
52
59
58
37
48
54
53
34
44
49
49

36
48
50
50
35
47
51
50
34
45
52
51
31
42
48
47
29
39
44
44

28
41
42
42
27
40
43
43
27
38
45
44
25
36
42
41
23
33
39
38

33
34
34
32
36
36
32
38
37
30
35
35
28
33
33

25
27
27
25
29
29
25
31
30
24
29
29
23
28
27

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.

NOMINAL RATING

Unitary Products Group

19

036-21502-003-A-1105

TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION

AIR
UNIT
FLOW
TONNAGE
CFM

3

1,2

1, 2

0.30

0.70

0.80

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

1700

835

705

880

745

923

795

969

860

1013

970

-

-

-

-

1600

811

655

854

695

898

740

942

790

986

840

1029

900

-

-

1500

782

610

827

650

871

685

917

730

960

775

1003

825

1046

905

1400

-

-

798

595

844

640

889

680

932

720

975

765

1018

790

1300

-

-

-

-

816

590

862

635

907

675

951

715

995

750

1200

-

-

-

-

-

-

834

585

881

630

927

665

970

705

1100

-

-

-

-

-

-

809

550

855

590

900

625

942

665

1000

-

-

-

-

-

-

782

510

829

545

872

858

919

625

900

-

-

-

-

-

-

-

-

797

500

843

540

890

580

AIR
UNIT
FLOW
TONNAGE
CFM

3

0.20

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50

0.90

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30

1.00

1.40

WATTS

1.50

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

1700

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1600

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1400

1055

875

-

-

-

-

-

-

-

-

-

-

-

-

1300

1036

780

1066

850

-

-

-

-

-

-

-

-

-

-

1200

1011

735

1047

765

1075

800

-

-

-

-

-

-

-

-

1100

987

690

1028

720

1060

750

1084

775

-

-

-

-

-

-

1000

963

655

1005

680

1040

695

1068

715

1089

735

-

-

-

-

900

936

615

980

645

1020

660

1050

670

1053

680

1090

690

-

-

1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.

20

Unitary Products Group

036-21502-003-A-1105

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION

UNIT
TONNAGE

4

1, 2

UNIT
TONNAGE

4

1, 2

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50

AIR
FLOW
CFM

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

0.20

0.30

0.70

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30

0.80

AIR
FLOW
CFM

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

0.90

1.00

1.40

1.50

1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.

Unitary Products Group

21

036-21502-003-A-1105

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION

AIR FLOW
UNIT
TONNAGE
CFM

5

1, 2

0.20

1, 2

0.30

0.70

0.80

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

2500

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

1181

1720

2400

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

2300

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

2200

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

2100

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

2000

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

1900

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

1800

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

1700

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

1600

-

-

-

-

-

-

864

770

908

805

948

835

987

870

1500

-

-

-

-

-

-

-

-

882

740

926

780

965

830

UNIT
AIR FLOW
TONNAGE
CFM

5

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.40
0.50
0.60

0.90

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30

1.00

1.40

1.50

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

WATTS
-

2400

1193

1665

-

-

-

-

-

-

-

-

-

-

-

-

2300

1170

1580

1202

1620

-

-

-

-

-

-

-

-

-

-

2200

1148

1480

1180

1530

-

-

-

-

-

-

-

-

-

-

2100

1121

1385

1155

1425

1190

1475

-

-

-

-

-

-

-

-

2000

1100

1285

1133

1340

1169

1385

1205

1445

-

-

-

-

-

-

1900

1079

1180

1110

1240

1143

1280

1178

1330

1222

1375

-

-

-

1800

1058

1060

1090

1135

1122

1190

1158

1240

1196

1295

-

-

-

-

1700

1035

960

1071

1030

1103

1100

1134

1140

1164

1175

1197

1205

-

-

1600

1020

900

1056

965

1088

1035

1118

1065

1145

1105

1170

1130

1198

1150

1500

1004

860

1038

880

1070

925

1101

980

1130

1045

1158

1075

1184

1110

1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.

22

Unitary Products Group

036-21502-003-A-1105

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION

UNIT
TONNAGE

6

1, 2

UNIT
TONNAGE

6

1, 2

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50

AIR
FLOW
CFM

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

3200

1150

2325

1182

2425

1212

2525

-

-

-

-

-

-

-

-

3000

1100

2010

1129

2090

1157

2150

1185

2225

1215

2290

1242

2360

-

-

2800

1045

1700

1074

1780

1102

1850

1131

1940

1160

2025

1190

2075

1217

2130

2600

985

1425

1015

1475

1045

1540

1075

1630

1103

1715

1135

1760

1163

1825

2400

930

1240

958

1300

990

1350

1020

1400

1051

1430

1081

1490

1111

1600

2200

-

-

905

1070

933

1160

965

1210

997

1250

1028

1285

1060

1325

2000

-

-

-

-

-

-

919

1025

950

1100

982

1130

1014

1160

1800

-

-

-

-

-

-

-

-

909

925

939

1005

968

1030

0.20

0.30

0.70

AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30

0.80
WATTS

AIR
FLOW
CFM

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

3200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2800

1245

2190

-

-

-

-

-

-

-

-

-

-

-

-

2600

1193

1920

1222

1990

1250

2060

-

-

-

-

-

-

-

-

2400

1142

1675

1173

1730

1205

1800

1234

1885

-

-

-

-

-

-

2200

1090

1380

1124

1450

1155

1550

1186

1640

1217

1710

1249

1775

-

-

2000

1045

1175

1077

1200

1109

1275

1140

1360

1170

1460

1205

1545

1235

1600

1800

998

1050

1028

1060

1058

1060

1087

1075

1118

1150

1148

1250

1176

1360

0.90

1.00

1.40

1.50

1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.

Unitary Products Group

23

036-21502-003-A-1105

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION

UNIT
TONNAGE

AVAILABLE EXTERNAL STATIC PRESSURE-IWG2
MOTOR SPEED

1

3

1

4

1

5

1

6

UNIT
TONNAGE)

0.20

1

1

4

1

5

1

6

0.40

0.50

0.60

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

HI

-

-

-

-

1699

825

1650

785

1570

755

MED

1684

800

1631

780

1582

750

1524

720

1410

690

LOW

1487

710

1464

690

1421

670

1367

650

1315

620

HI

1996

960

1933

936

1868

910

1795

880

1722

845

MED

1804

838

1765

810

1714

785

1650

765

1589

735

LOW

1681

760

1640

738

1604

715

1541

695

1490

670

HI

2400

1155

2338

1125

2274

1095

2167

1045

2096

1010

WATTS

950

MED

2290

1105

2214

1065

2145

1030

2071

990

1990

LOW

2150

1020

2100

990

2029

950

1965

910

1905

880

HI

2461

1480

2402

1440

2361

1395

2260

1350

2178

1305

MOTOR SPEED

3

0.30

CFM

AVAILABLE EXTERNAL STATIC PRESSURE-IWG2
0.80
0.90

0.70

1.00

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

HI

1430

725

1360

700

1280

680

1180

655

MED

1324

650

1260

630

1185

610

1100

590

LOW

1246

605

1185

590

1110

570

1020

545

HI

1635

820

1544

790

1419

765

1300

740

MED

1508

705

1407

675

1306

645

1195

625

LOW

1416

645

1337

620

1230

595

1120

575

HI

1990

980

1887

945

1771

905

1629

855

MED

1911

920

1828

885

1724

835

1604

798

LOW

1816

838

1724

800

1644

770

1531

710

HI

2101

1260

2000

1205

1914

1155

1830

1110

1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.

TABLE 14: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MOTOR1

ADJUSTABLE MOTOR PULLEY

BELT
(NOTCHED)

FIXED BLOWER PULLEY

MODEL
SIZE

BLOWER
RANGE
(RPM)

HP

FRAME

DESIGNATION

OUTSIDE
DIA.
(IN.)

PITCH
DIA.
(IN.)

BORE
(IN.)

DESIGNATION

OUTSIDE
DIA.
(IN.)

PITCH
DIA.
(IN.)

BORE
(IN.)

DESIGNATION

PITCH
LENGTH
(IN.)

QTY.

3 TON

790/1120

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK61

5.9

5.7

1

A36

37.3

1

4 TON

790/1120

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK61

5.9

5.7

1

A36

37.3

1

5 TON

850/1220

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK56

5.4

5.2

1

A36

37.3

1

6 TON

900/1250

1 1/2

56

1VL44

3.1-4.1

2.8-3.8

7/8

AK56

5.4

5.2

1

A36

37.3

1

1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.

24

Unitary Products Group

036-21502-003-A-1105

TABLE 15: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
1200

1400

1600

1800

2000

2200

2400

2600

2800

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20-30KW

ECONOMIZER1 3
ELECTRIC
HEATERS1

CFM
1000

3000

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

BOTTOM DUCT CONNECTIONS1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 16: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNITMODEL SIZE NOMINAL
TONS

VOLTAGE

HEATER SIZE NOMINAL KW
5

7

10

15

20

30

208/230-1-60

1100

1100

1200

1200

1300

-

208/230-3-60

1100

1100

1200

1200

1300

-

460-3-60

-

1100

1200

1200

1300

-

575-3-60

-

-

1200

1200

1300

-

208/230-1-60

1300

1300

1300

1300

1300

-

208/230-3-60

1300

1300

1300

1300

1300

-

460-3-60

-

1300

1300

1300

1300

-

575-3-60

-

-

1300

1300

1400

-

208/230-1-60

1600

1600

1600

1600

1600

1600

208/230-3-60

1600

1600

1600

1600

1600

1600

460-3-60

-

1600

1600

1600

1600

1600

575-3-60

-

1600

1600

1600

1600

1800

208/230-3-60

1800

1800

1800

1800

1800

1800

460-3-60

-

1800

1800

1800

1800

1800

575-3-60

-

-

1800

1800

1800

1800

3

4

5

6

Unitary Products Group

25

036-21502-003-A-1105

TABLE 17: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan ID Blower
Motor
Motor
FLA
FLA

Conv
Outlet
Amps

208-1-60

18.0

105

1.3

4.4

0.0

230-1-60

18.0

105

1.3

4.4

0.0

208-3-60

11.4

90

1.3

4.4

0.0

230-3-60

11.4

90

1.3

4.4

0.0

460-3-60

6.2

45

0.8

2.2

0.0

575-3-60

5.0

36

0.8

2.2

0.0

208-1-60

24.4

140

1.3

5.0

0.0

230-1-60

24.4

140

1.3

5.0

0.0

208-3-60

14.1

105

1.3

5.0

0.0

230-3-60

14.1

105

1.3

5.0

0.0

460-3-60

7.1

55

0.8

2.2

0.0

575-3-60

5.8

44

0.8

2.2

0.0

3

4

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2CE04511546 2
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058

0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2

0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4

28.2
29.5
39.2
53.6
77.0
101.1
28.2
33.1
44.6
60.7
88.3
115.9
19.9
19.9
24.9
33.3
46.8
60.7
19.9
21.4
28.1
37.4
53.3
69.2
10.8
13.0
17.9
23.2
32.1
8.7
14.9
21.3
27.7
36.8
36.8
39.9
54.3
77.8
101.8
36.8
36.8
45.3
61.5
89.1
116.7
23.9
23.9
25.7
34.0
47.5
61.4
23.9
23.9
28.8
38.1
54.1
70.0
11.9
13.0
17.9
23.2
32.1
9.7
14.9
21.3
27.7

Max Fuse /
BRKR1 Size
Amps
45
45
45
60
80
110
45
45
45
70
90
125
30
30
30
35
50
70
30
30
30
40
60
70
15
15
20
25
35
15
15
25
30
60
60
60
60
80
110
60
60
60
70
90
125
35
35
35
35
50
70
35
35
35
40
60
70
15
15
20
25
35
15
15
25
30

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

26

Unitary Products Group

036-21502-003-A-1105

TABLE 18: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

28.9

165

1.3

6.6

0.0

230-1-60

28.9

165

1.3

6.6

0.0

208-3-60

16.0

125

1.3

6.6

0.0

230-3-60

16.0

125

1.3

6.6

0.0

460-3-60

8.0

66.5

0.8

3.3

0.0

575-3-60

6.4

50

0.8

3.3

0.0

208-3-60

18.9

146

1.3

6.8

0.0

230-3-60

18.9

146

1.3

6.8

0.0

460-3-60

9.5

73

0.8

3.6

0.0

575-3-60

7.6

58.4

0.8

3.6

0.0

5

6

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058

0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4

0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3

44.0
44.0
44.0
56.3
79.8
103.8
141.7
44.0
44.0
47.3
63.5
91.1
118.7
162.4
27.9
27.9
27.9
36.0
49.5
63.4
85.3
27.9
27.9
30.8
40.1
56.1
72.0
97.3
14.1
14.3
19.3
24.6
33.4
47.4
11.3
16.0
22.4
28.8
39.9
31.7
31.7
31.7
36.3
49.8
63.7
85.5
31.7
31.7
31.7
40.4
56.3
72.2
97.5
16.3
16.3
19.7
24.9
33.8
47.8
13.0
16.3
22.7
29.1
40.2

Max Fuse /
BRKR1 Size
Amps
70
70
70
70
80
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
45
60
80
100
20
20
20
25
35
50
15
20
25
30
40
50
50
50
50
50
70
90
50
50
50
50
60
80
100
25
25
25
25
35
50
15
20
25
30
40

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

Unitary Products Group

27

036-21502-003-A-1105

TABLE 19: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

18.0

105

1.3

7.6

0.0

230-1-60

18.0

105

1.3

7.6

0.0

208-3-60

11.4

90

1.3

5.2

0.0

230-3-60

11.4

90

1.3

5.2

0.0

460-3-60

6.2

45

0.8

2.6

0.0

575-3-60

5.0

36

0.8

2

0.0

208-1-60

24.4

140

1.3

7.6

0.0

230-1-60

24.4

140

1.3

7.6

0.0

208-3-60

14.1

105

1.3

5.2

0.0

230-3-60

14.1

105

1.3

5.2

0.0

460-3-60

7.1

55

0.8

2.6

0.0

575-3-60

5.8

44

0.8

2

0.0

3

4

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058

0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2

0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4

31.4
33.5
43.2
57.6
81.0
105.1
31.4
37.1
48.6
64.7
92.3
119.9
20.8
20.8
25.9
34.3
47.8
61.7
20.8
22.4
29.1
38.4
54.3
70.2
11.1
13.5
18.4
23.7
32.6
8.5
14.7
21.1
27.5
39.4
39.4
43.2
57.6
81.0
105.1
39.4
39.4
48.6
64.7
92.3
119.9
24.1
24.1
25.9
34.3
47.8
61.7
24.1
24.1
29.1
38.4
54.3
70.2
12.3
13.5
18.4
23.7
32.6
9.5
14.7
21.1
27.5

Max Fuse /
BRKR1 Size
Amps
45
45
45
60
90
110
45
45
50
70
100
125
30
30
30
35
50
70
30
30
30
40
60
80
15
15
20
25
35
15
15
25
30
60
60
60
60
90
110
60
60
60
70
100
125
35
35
35
35
50
70
35
35
35
40
60
80
15
15
20
25
35
15
15
25
30

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

28

Unitary Products Group

036-21502-003-A-1105

TABLE 20: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

28.9

165

1.3

7.6

0.0

230-1-60

28.9

165

1.3

7.6

0.0

208-3-60

16.0

125

1.3

5.2

0.0

230-3-60

16.0

125

1.3

5.2

0.0

460-3-60

8.0

66.5

0.8

2.6

0.0

575-3-60

6.4

50

0.8

2

0.0

208-3-60

18.9

146

1.3

5.0

0.0

230-3-60

18.9

146

1.3

5.0

0.0

460-3-60

9.5

73

0.8

2.5

0.0

575-3-60

7.6

58.4

0.8

2

0.0

5

6

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058

0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4

0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3

45.0
45.0
45.0
57.6
81.0
105.1
142.9
45.0
45.0
48.6
64.7
92.3
119.9
163.7
26.5
26.5
26.5
34.3
47.8
61.7
83.5
26.5
26.5
29.1
38.4
54.3
70.2
95.5
13.4
13.5
18.4
23.7
32.6
46.6
10.2
14.7
21.1
27.5
38.6
29.9
29.9
29.9
34.0
47.5
61.4
83.3
29.9
29.9
29.9
38.1
54.1
70.0
95.3
15.2
15.2
18.3
23.6
32.4
46.4
11.7
14.7
21.1
27.5
38.6

Max Fuse /
BRKR1 Size
Amps
70
70
70
70
90
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
40
60
80
100
20
20
20
25
35
50
15
15
25
30
40
45
45
45
45
50
70
90
45
45
45
45
60
70
100
20
20
20
25
35
50
15
15
25
30
40

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

Unitary Products Group

29

036-21502-003-A-1105

TABLE 21: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

18.0

105

1.3

4.4

10.0

230-1-60

18.0

105

1.3

4.4

10.0

208-3-60

11.4

90

1.3

4.4

10.0

230-3-60

11.4

90

1.3

4.4

10.0

460-3-60

6.2

45

0.8

2.2

5.0

575-3-60

5.0

36

0.8

2.2

4.0

208-1-60

24.4

140

1.3

5.0

10.0

230-1-60

24.4

140

1.3

5.0

10.0

208-3-60

14.1

105

1.3

5.0

10.0

230-3-60

14.1

105

1.3

5.0

10.0

460-3-60

7.1

55

0.8

2.2

5.0

575-3-60

5.8

44

0.8

2.2

4.0

3

4

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058

0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2

0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4

38.2
42.0
51.7
66.1
89.5
113.6
38.2
45.6
57.1
73.2
100.8
128.4
29.9
31.9
37.4
45.8
59.3
73.2
29.9
33.9
40.6
49.9
65.8
81.7
15.8
19.2
24.2
29.4
38.3
12.7
19.9
26.3
32.7
46.8
46.8
52.4
66.8
90.3
114.3
46.8
46.8
57.8
74.0
101.6
129.2
33.9
33.9
38.2
46.5
60.0
73.9
33.9
34.7
41.3
50.6
66.6
82.5
16.9
19.2
24.2
29.4
38.3
13.7
19.9
26.3
32.7

Max Fuse /
BRKR1 Size
Amps
50
50
60
70
90
125
50
50
60
80
110
150
40
40
40
50
60
80
40
40
45
50
70
90
20
20
25
30
40
15
20
30
35
70
70
70
70
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

30

Unitary Products Group

036-21502-003-A-1105

TABLE 22: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

28.9

165

1.3

6.6

10.0

230-1-60

28.9

165

1.3

6.6

10.0

208-3-60

16.0

125

1.3

6.6

10.0

230-3-60

16.0

125

1.3

6.6

10.0

460-3-60

8.0

66.5

0.8

3.3

5.0

575-3-60

6.4

50

0.8

3.3

4.0

208-3-60

18.9

146

1.3

6.8

10.0

230-3-60

18.9

146

1.3

6.8

10.0

460-3-60

9.5

73

0.8

3.6

5.0

575-3-60

7.6

58.4

0.8

3.6

4.0

5

6

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058

0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4

0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3

54.0
54.0
54.4
68.8
92.3
116.3
154.2
54.0
54.0
59.8
76.0
103.6
131.2
174.9
37.9
37.9
40.2
48.5
62.0
75.9
97.8
37.9
37.9
43.3
52.6
68.6
84.5
109.8
19.1
20.6
25.6
30.8
39.7
53.7
15.3
21.0
27.4
33.8
44.9
41.7
41.7
41.7
48.8
62.3
76.2
98.0
41.7
41.7
43.6
52.9
68.8
84.7
110.0
21.3
21.3
25.9
31.2
40.1
54.1
17.0
21.3
27.7
34.1
45.2

Max Fuse /
BRKR1 Size
Amps
80
80
80
80
100
125
175
80
80
80
80
110
150
175
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
30
35
40
60
20
25
30
35
45
60
60
60
60
70
80
100
60
60
60
60
70
90
125
30
30
30
35
45
60
20
25
30
35
45

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

Unitary Products Group

31

036-21502-003-A-1105

TABLE 23: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

18.0

105

1.3

7.6

10.0

230-1-60

18.0

105

1.3

7.6

10.0

208-3-60

11.4

90

1.3

5.2

10.0

230-3-60

11.4

90

1.3

5.2

10.0

460-3-60

6.2

45

0.8

2.6

5.0

575-3-60

5.0

36

0.8

2

4.0

208-1-60

24.4

140

1.3

7.6

10.0

230-1-60

24.4

140

1.3

7.6

10.0

208-3-60

14.1

105

1.3

5.2

10.0

230-3-60

14.1

105

1.3

5.2

10.0

460-3-60

7.1

55

0.8

2.6

5.0

575-3-60

5.8

44

0.8

2

4.0

3

4

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058

0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2

0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4

41.4
46.0
55.7
70.1
93.5
117.6
41.4
49.6
61.1
77.2
104.8
132.4
30.8
32.9
38.4
46.8
60.3
74.2
30.8
34.9
41.6
50.9
66.8
82.7
16.1
19.7
24.7
29.9
38.8
12.5
19.7
26.1
32.5
49.4
49.4
55.7
70.1
93.5
117.6
49.4
49.6
61.1
77.2
104.8
132.4
34.1
34.1
38.4
46.8
60.3
74.2
34.1
34.9
41.6
50.9
66.8
82.7
17.3
19.7
24.7
29.9
38.8
13.5
19.7
26.1
32.5

Max Fuse /
BRKR1 Size
Amps
50
50
60
80
100
125
50
50
70
80
110
150
40
40
40
50
70
80
40
40
45
60
70
90
20
20
25
30
40
15
20
30
35
70
70
70
80
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

32

Unitary Products Group

036-21502-003-A-1105

TABLE 24: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET

Model
Tonnage

Compressors
Voltage

RLA
Each

LRA
Each

OD Fan
Motor
FLA

ID Blower
Motor
FLA

Conv
Outlet
Amps

208-1-60

28.9

165

1.3

7.6

10.0

230-1-60

28.9

165

1.3

7.6

10.0

208-3-60

16.0

125

1.3

5.2

10.0

230-3-60

16.0

125

1.3

5.2

10.0

460-3-60

8.0

66.5

0.8

2.6

5.0

575-3-60

6.4

50

0.8

2

4.0

208-3-60

18.9

146

1.3

5.0

10.0

230-3-60

18.9

146

1.3

5.0

10.0

460-3-60

9.5

73

0.8

2.5

5.0

575-3-60

7.6

58.4

0.8

2

4.0

5

6

Electric Heater
Model No.

Heater
kW

Heater
Amps

Minimum
Circuit
Ampacity
Amps

NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058

0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4

0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3

55.0
55.0
55.7
70.1
93.5
117.6
155.4
55.0
55.0
61.1
77.2
104.8
132.4
176.2
36.5
36.5
38.4
46.8
60.3
74.2
96.0
36.5
36.5
41.6
50.9
66.8
82.7
108.0
18.4
19.7
24.7
29.9
38.8
52.8
14.2
19.7
26.1
32.5
43.6
39.9
39.9
39.9
46.5
60.0
73.9
95.8
39.9
39.9
41.3
50.6
66.6
82.5
107.8
20.2
20.2
24.6
29.8
38.7
52.7
15.7
19.7
26.1
32.5
43.6

Max Fuse /
BRKR1 Size
Amps
80
80
80
80
100
125
175
80
80
80
80
110
150
200
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45

1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.

Unitary Products Group

33

036-21502-003-A-1105

TABLE 25: PHYSICAL DATA
DM

MODELS
Centrifugal Blower (Dia. x Wd. in.)

EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE

VOLTAGE

048

060

072

12 X 10

12 X 10

12 X 10

12 X 11

Fan Motor HP (Direct Drive)

1/2

3/4

1

1

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

1 1/2

1 1/2

Rows Deep

3

3

3

4

Fins Per Inch

13

13

13

13

Face Area (Sq. Ft.)

3.6

4.3

5.1

5.1

Propeller Dia. (in.)

24

24

24

24

Fan Motor Hp

1/4

1/4

1/4

1/4
3400

Nom. CFM

3400

3400

3400

Rows Deep

1

1

1

2

Fins Per Inch

16

16

22

16

Face Area (Sq. Ft.)

17.1

17.1

17.1

16.7

Scroll Type

1

1

1

1

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

1

Total Face Area (sq. ft.)

6.3

6.3

6.3

6.3

Refrigerant 22
(lbs./oz.)

5/8

6/8

6/8

10/0

TABLE 26: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE

036

kW CAP. MULTIPLIER

TABLE 27: VOLTAGE LIMITATIONS1
VOLTAGE

POWER SUPPLY
MIN.

MAX.

208/230-1-60

187

253

208

208

1.00

208/230-3-60

187

253

240

230

0.92

460-3-60

414

506

480

460

0.92

575-3-60

540

630

600

575

0.92

1. Utilization Range “A” in accordance with ARI Standard
110.

34

Unitary Products Group

036-21502-003-A-1105

TYPICAL POWER WIRING

REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.

TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)

COOLING ONLY (24 VOLT THERMOSTAT)

THERMOSTAT 1
TERMINALS

THERMOSTAT1 UNIT TERMINAL
TERMINALS
STRIP TB1

ADD
JUMPER

R

RV

Y1

YC

RH

UNIT TERMINAL
STRIP TB1

RC

R

Y

Y1

24 VOLT
TRANSFORMER

24 VOLT
TRANSFORMER

Y2

Y2
W

W1

G

GF

W2

C

G

G
C

1 24

VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.

1

24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.

COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER

RC

UNIT TERMINAL
STRIP TB1

RH

R

Y1

Y1

2

Y2
W1

4

RH

Y2

3

W2

ADD
JUMPER

UNIT TERMINAL
STRIP TB1

RC

R

Y

Y1

G

G

B

C

W

W1

LED 1

X

G

G

COM

NOT
USED

OCC

C

4

24 VOLT
TRANSFORMER

A1
A2
T
T

TO REMOTE SENSOR
2TH040702224 IF USED

1

ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).

2

SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3

SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4

THERMOSTAT1
TERMINALS

24 VOLT
TRANSFORMER

W1

W2

LED 2

ADD
JUMPER

COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE

1 ELECTRONIC

PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.

REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

FIGURE 2 -

TYPICAL FIELD POWER & CONTROL WIRING

Unitary Products Group

35

036-21502-003-A-1105

FIGURE 3 -

UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW

FIGURE 4 -

UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW

36

Unitary Products Group

036-21502-003-A-1105

DETAIL “A”
FIGURE 5 -

UNIT WITH ECONOMIZER RAINHOOD

DETAIL “B”

FIGURE 6 -

UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD

Unitary Products Group

37

036-21502-003-A-1105

FIGURE 7 -

UNIT DIMENSIONS (REAR VIEW)
TABLE 29: MINIMUM CLEARANCES

FILTER
ACCESS

BLOWER MOTOR
ACCESS

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)
32” (Gas Heat)

Rear

12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)
36” (With Economizer)

Right Side (Cond. Coil)

24”

DOT PLUGS

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)

Below Unit
A,B
WIRING ENTRY
(See Detail “B”)

0”

2

72” (For
Condenser Air Discharge)

Above Unit

CONTROL BOX
ACCESS

DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION

FIGURE 8 -

1

DISCONNECT/BLOWER ACCESS
LOCATION

1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.

TABLE 28: UTILITIES ENTRY
HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO1

Control Wiring2

B

2” KO1

Power Wiring

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

Side
Bottom
Side
Bottom

1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.

38

Unitary Products Group

036-21502-003-A-1105

FIGURE 9 -

TYPICAL APPLICATIONS

Unitary Products Group

39

036-21502-003-A-1105

BACK OF UNIT

A

447/8

BACK OF UNIT

A

447/8

821/4

821/4
D

B

F
X

X
B
APPROXIMATE
CENTER OF GRAVITY

CONDENSER COIL
END OF UNIT

C
Y

FRONT OF UNIT

C

E
APPROXIMATE
CENTER OF GRAVITY

CONDENSER COIL
END OF UNIT

D
Y

FRONT OF UNIT

FIGURE 10 - FOUR AND SIX POINT LOADING

TABLE 30: DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT

TOTAL

4-Point Loading (lb)

6-Point Loading (lb)

A

B

C

D

A

B

C

D

E

F

DM036 Cooling/ Electric

565

125

123

157

160

84

83

82

104

105

107

DM036N04

605

134

132

168

171

90

89

88

112

113

114

DM036D06

615

137

134

171

174

91

90

89

113

115

116

DM036N08

625

139

136

173

177

93

92

91

115

117

118

DM036D10

635

141

138

176

179

94

93

92

117

119

120

DM048 Cooling/ Electric

615

137

134

171

174

91

90

89

113

115

116

DM048(D,N)06

665

148

145

184

188

99

98

96

123

124

126

DM048(D,N)10

685

152

149

190

194

102

100

99

126

128

129

DM060 Cooling/ Electric

640

142

140

178

181

95

94

93

118

119

121

DM060D06

690

153

150

191

195

102

101

100

127

129

130

DM060N08

700

155

153

194

198

104

103

101

129

131

132

DM060(D,N)10

710

158

155

197

201

105

104

103

131

132

134

DM072 Cooling/ Electric

720

160

157

200

203

107

106

104

133

134

136

DM072D06

770

171

168

214

218

114

113

112

142

144

145

DM072N08

780

173

170

216

220

116

114

113

144

146

147

DM072(D,N)10

790

175

172

219

223

117

116

114

146

147

149

TABLE 31: CENTER OF GRAVITY
DIMENSION

3 - 5 TON

6 TON

X

40-¾”

44”

Y

19-¾”

22”

40

Unitary Products Group

036-21502-003-A-1105

TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE

3 TON

4 TON

5 TON

6 TON

565

615

640

720

N04

605

-

-

-

N06

-

665

-

-

N08

625

-

700

780

DM (Cooling Only)

BASIC
UNIT

DM
(Gas/Electric)

N10

-

685

710

790

D06

615

665

690

770

D10

635

685

710

790

Economizer

50

Motorized Damper

OPTIONS
Electric Heater

26
5 - 7 kW

18

10 - 15 kW

23

20 - 30 kW

ACCY.

28

Roof Curb

92

Barometric Relief / Fixed Air Damper

10

Belt-Drive Blower

5

FIGURE 11 - ROOF CURB DIMENSIONS

Unitary Products Group

41

036-21502-003-A-1105

GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000TM units are convertible single packageunits. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 1000 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 3 thru 5 ton units shall have minimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER ratings of
9.0. They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or
field installed accessories. The units shall be factory wired,
piped, charged with R-22 refrigerant and factory tested prior
to shipment. All unit wiring shall be both numbered and color
coded. All units the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall be
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236
standards.

42

UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower shall
not exceed the motors nameplate horsepower rating, plus the
service factor. Units shall be designed not to operate above
service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.

Shall be internally protected with internal high-pressure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.

Coils:
a.

Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless

Unitary Products Group

036-21502-003-A-1105

internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.

Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.

Independent fixed-orifice expansion devices.

b.

Filter drier/strainer to eliminate any moisture or foreign matter.

c.

Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.

d.

dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:

The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.

UNIT CONTROLS
a.

Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

d.

High-pressure switch.

e.

Freeze-protection thermostat, evaporator coil.

f.

If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.

g.

Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.

h.

Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.

i.

Unit control board shall have on-board diagnostics
and fault code display.

j.

Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.

k.

Control board shall monitor each refrigerant safety
switch independently.

l.

Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.

a.

Primary and auxiliary high-temperature limit
switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch (manual reset).

d.

Flame proving controls.

ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where
required).
UNIT OPERATING CHARACTERISTICS
a.

Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be
provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat
only).

ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•

Compressor 5 Years

•

Heat Exchanger 10 Years

GAS HEATING SECTION (SINGLE OR 2 STAGE)

•

Electric Heat Element 5 Years

Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-

•

Other Parts 1 Year

Unitary Products Group

43

OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•

•

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•

ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).

•

BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.

•

•

PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.

•

HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.

•

LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.

•

GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.

•

POWER EXHAUST OPTION - To work in conjunction
with economizers.

•

ELECTRIC HEATERS

•

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.

•

MANUAL OUTDOOR AIR DAMPER

•

COIL GUARD KIT - Guard for cooling coil.

•

HAIL GUARD

•

FLUE EXHAUST EXTENSION

OTHER FACTORY INSTALLED OPTIONS
•

POWER EXHAUST OPTION - To work in conjunction
with economizers.

•

STAINLESS STEEL HEAT EXCHANGER

•

STAINLESS STEEL DRAIN PAN

•

BOTTOM DRAIN CONNECTION

•

TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL

•

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

•

DIRTY FILTER SWITCH

•

PHASE MONITOR

•

COIL GUARD

•

POWERED GFI CONVENIENCE OUTLET

•

NON-POWERED GFI CONVENIENCE OUTLET

•

BAS CONTROLS (Simplicity™ INTELLI- Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)

•

BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)

•

HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS

•

2" PLEATED FILTERS

•

DISCONNECT SWITCH

•

SUPPLY AIR SMOKE DETECTOR

•

RETURN AIR SMOKE DETECTOR

Subject to change without notice. Printed in U.S.A.
Copyright © 2005 by Unitary Products. All rights reserved.
Unitary
Products
Group

036-21502-003-A-1105
Supersedes: 036-21502-002-B-0504
5005
York
Drive

Norman
OK
73069



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseThumbs
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Create Date                     : 2005:12:05 10:54:13-06:00
Modify Date                     : 2005:12:05 10:55:17-06:00
Metadata Date                   : 2005:12:05 10:55:17-06:00
Document ID                     : uuid:A0E002B5AF65DA11843CDE727AC9DB77
Instance ID                     : uuid:1555dee5-c815-4586-bd86-16ede6cc0999
Derived From Instance ID        : uuid:478bb361-afaa-4321-b816-d1f551f795c5
Derived From Document ID        : uuid:385f6c04-6516-47f3-abb4-2a4eaefb1430
Format                          : application/pdf
Title                           : 036-21502-003-A-1105.fm
Creator                         : yi007725
Page Count                      : 44
Page Layout                     : OneColumn
Author                          : yi007725
EXIF Metadata provided by EXIF.tools

Navigation menu