505428-YTG-R-1114

®

Description

TECHNICAL GUIDE
R-410A
SPLIT-SYSTEM
AIR-COOLED CONDENSING UNITS
AND AIR HANDLERS

PREDATOR® SERIES
YC090-300 and YD120-240
CONDENSING UNIT MODELS

PC090-180 and PD180-240
HEAT PUMP UNIT MODELS

NC090-300 and ND120-240
AIR HANDLING UNIT MODELS

7.5 - 25 Ton
60 Hertz

Predator® condensing units and heat pumps are completely
assembled, piped and wired at the factory to provide a single-piece
unit for shipment and rigging. Each unit is pressurized with a holding
charge of refrigerant R-410A for storage and/or shipping.
The compact design, clean styling, small footprint, and quiet operation
make these condensing units and heat pumps suitable for almost any
outdoor location. On rooftops... because they weigh much less than a
single package unit of similar capacity and are much easier to rig and
support. On the ground... because the footprint is compact allowing a
variety of applications.
Both the Predator® condensing units and heat pumps are equipped
with reliable Simplicity® SE microprocessor controls to assure proper
operation and unit protection for long product life. Products from 10 to
20 tons are available in single or dual (2 or 4 pipe) refrigerant circuits
for redundancy in operation and various application choices such as
one outdoor unit matched with two indoor units.
The Predator® air handling units are completely assembled units,
including a well-insulated cabinet, a DX cooling coil with copper tubing,
aluminum fins, expansion valve(s), distributor(s), 2” throwaway filters,
a centrifugal blower, a blower motor, an adjustable belt drive, a blower
motor contactor and a small holding charge of nitrogen.
Units are shipped in the vertical
position ready for field installation,
but can be easily converted to
horizontal position. An added
benefit of the Predator® air
handling units is they are designed
to operate with either a
condensing unit or a heat pump
and no field modification or special
unit is required for heat pump
applications.

(Except YC300)

YC/YD/PC Outdoor Units

ISO 9001
Certified Quality
Management System

NC/ND Indoor Units

YC/YD/PC/PD Outdoor Units

505428-YTG-R-1114

Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Condensing Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor Unit Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Handling Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling and Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air Handling and Hot Water Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Air Handling and Steam Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Weights And Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

2

Johnson Controls Unitary Products

505428-YTG-R-1114

Nomenclature
Configured Split Condenser Model Number Nomenclature
Y C 300 C00 A 2 A AA 4 A

Product Style
A = Style A

Product Category
Y = Split System, Condenser, AC, R-410A
P = Split System, Condenser, HP, R-410A

Product Generation
4 = Fourth Generation

Product Identifier

Product Options

C = Standard Efficiency, 2-Pipe, R-410A
D = Standard Efficiency, 4-Pipe, R-410A

Nominal Cooling Capacity - MBH
090 = 7.5 Ton
120 = 10 Ton
150 = 12.5 Ton
180 = 15 Ton
240 = 20 Ton
300 = 25 Ton

Heat Type & Nominal Heat Capacity
C00 = Cooling Only

Installation Options
A = None
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 2 & 3
J = Options 1, 2 & 3
K = Options 1 & 4
L = Options 2 & 4
M = Options 1, 2 &4
P = Options 3 & 5
Q = Options 1, 3 & 5
R = Options 4 & 5
S = Option 5
T = Options 1 & 5
V = Options 1, 4 & 5

Options
1 = Disconnect
2 = Non Pwr’d Conv Outlet
3 = BACnet MS/TP on Simplicity SE
4 = Fault Detection Device
5 = Pwr’d Conv Outlet

Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60

AA = None
AB = Phase Monitor
AC = Coil Guard
AE = Phase Monitor + Coil Guard
EA = E-Coat Condenser Coil
EB = E-Coat Condenser Coil + Phase Monitor
EC = E-Coat Condenser Coil + Coil Guard
EE = E-Coat Condenser Coil + Coil Guard
+ Phase Monitor
LA = Low Ambient
LB = Low Ambient + Phase Monitor
LC = Low Ambient + Coil Guard
LD = Low Ambient + Phase Monitor
+ Coil Guard
LE = Low Ambient + Technicoat Cond. Coil
LF = Low Ambient + Technicoat Cond. Coil
+ Phase Monitor
LG = Low Ambient + Technicoat Cond. Coil
+ Coil Guard
LH = Low Ambient + Technicoat Cond. Coil
+ Phase Monitor + Coil Guard
LJ = Low Ambient + ElectroFin Cond. Coil
LK = Low Ambient + ElectroFin Cond. Coil
+ Phase Monitor
LL = Low Ambient + ElectroFin Cond. Coil
+ Coil Guard
LM = Low Ambient + ElectroFin Cond. Coil
+ Phase Monitor + Coil Guard
TA = Technicoat Condenser Coil
TB = Technicoat Condenser Coil + Phase
Monitor
TC = Technicoat Condenser Coil + Coil Guard
TE = Technicoat Condenser Coil + Coil Guard
+ Phase Monitor

Airflow
A = Standard Motor

Configured Split Air Handler Model Number Nomenclature
N C 240 C00 B 6 A AA 3 A
Product Style

Product Category

A = Style A

N = Split System, Air Handler, AC & HP R-410A

Product Generation
1 = First Generation
2 = Second Generation
3 = Third Generation

Product Identifier
C = Standard Efficiency, 2-Pipe, R-410A
D = Standard Efficiency, 4-Pipe, R-410A

Nominal Cooling Capacity - MBH
090 = 7-1/2 Ton
120 = 10 Ton
180 = 15 Ton
240 = 20 Ton
300 = 25 Ton

Product Options
AA = No Options Installed
EJ = E-Coat Evaporator Coil
TJ = Technicoat Evaporator Coil

Installation Options
A = None

Heat Type & Nominal Heat Capacity
C00 = Cooling Only

Airflow
B = 1.5 HP Motor
C = 2.0 HP Motor
D = 3.0 HP Motor
E = 5.0 HP Motor
F = 7.5 HP Motor
N = None (Motor Drive Kit Reg)1

Voltage
2 = 208/230-3-602
4 = 460-3-602
5 = 575-3-60
6 = 208/230/460-3-60
2. Models NC/ND240 Airflow Option "F" Only.

1. Motors are not shipped with 25 ton AH units.

Johnson Controls Unitary Products

3

505428-YTG-R-1114

Condensing Unit Features and Benefits

• Factory installed powered or non-powered 115 volt GFI
outlet.

Features

• Factory installed phase monitor to protect the unit from
phase loss or phase reversal.

• Meets or exceeds ASHRAE 90.1 standards.
• Scroll compressors provide both high efficiency and
reliability.
• Simplicity ® SE Controls
• Dual refrigerant circuits on PD and YD models.
• Condensing unit coils are constructed of reliable and
durable Micro-Channel aluminum tube and fins for long
lasting, efficient operation. Mirco-Channel technology
provides exceptional durability along with reduced
product weight and less refrigerant charge. Heat pumps
units are equipped with aluminum fin, copper tube coils
providing durability, reliability and value.
• Multiple condensing unit and air handler match-ups
provide a wide range of application choices from
oversized indoor motors to dual indoor units matchedup with single outdoor units.
• Crankcase heaters that de-energize when compressors
are operating.
• Both high and low pressure controls. Since these
controls are self-contained, there are no capillary lines
to be damaged.
• Internal compressor motor protection.
• Class 2, 24-volt thermostat control circuit protected by a
re-settable breaker.
• Standard factory installed service valves.
• Filter-driers are shipped in the unit's control box for field
installation in the liquid line leaving the outdoor unit.
• Copper stub-outs are factory mounted on the suction
and liquid lines to simplify the field piping connections.
• Simplicity® SE Controls provide stable cooling
operation at ambient temperatures down to 40°F with
low ambient kits available for operation to 0°F.
• Capacity staging for more economical operation and
stable temperature levels within the conditioned space.
• Simplicity® SE Controls control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating
high limit must trip three times within two hours before
the unit control board will lock out the associated
compressor. An alarm message will be displayed on the
LCD screen
• Simplicity® SE Controls monitor each safety
independently (High pressure, low pressure, low
voltage) allowing ease of troubleshooting if any
problems arise.
• Inherently protected condenser fan motors.
• Technicoat or E-coat coated outdoor coils for sea coast
or corrosive environment applications.
• Factory installed disconnect to allow power to be
removed from the unit when performing periodic
maintenance or for service.

4

Benefits
The Predator® condensing units and heat pumps can be
applied on a rooftop or at ground level... due to their ample
sub-cooling capacity which allows them to be located three or
more stories below the evaporator coil.
After assembly, the unit is pressurized with a combination of
Refrigerant R-410A and nitrogen for pressure testing and
additional leak testing. During this pressure test, the
operation of the high pressure control is checked. As the unit
is being evacuated and dehydrated, the operation of the low
pressure control is also checked.
Every compressor, condenser fan motor, crankcase heater,
and electrical control circuit is checked to assure a troublefree start-up and years of reliable operation. The condenser
fan guards are vinyl-coated to provide additional rust
protection and to enhance the appearance of the unit.
Compressors are mounted on rubber isolators to reduce the
transmission of vibration. Vertical discharge condenser fans
direct sound upward and away from any surrounding
structures.
All sheet metal parts are constructed of commercial grade
galvanized steel. After fabrication, each part is thoroughly
cleaned to remove any grease or dirt from its surfaces. The
external parts are coated with a powder paint to assure a
quality finish for many years. This UL approved coating
system has passed the 1000 hour, 20% salt spray test per
ASTM Standard B117.
All condensing unit and heat pump models include a 5-year
limited warranty on the compressor(s) and 1-year limited
warranty on all other parts. The matching line of air handling
units carries a 1-year limited parts warranty.

Outdoor Unit Accessories
Coil Guards: Wire-form coil guards for added protection of
outdoor coils. Designed to mount on each side of the product
if required to provide protection from minor impacts or large
debris.
Hail Guards: Hood type hail guards designed to protect the
outdoor coils from hail. Can be installed on a single side or
both to provide protection from storms that may produce hail.
Low Ambient Kits: Kits designed to allow the cooling only
units to operate between 0°F and 40°F in the cooling mode.
Standard cooling is allowed to 40°F. (Not designed for
operation on heat pump units).

Air Handling Unit Features and Benefits
Features
These air handlers can be arranged for a variety of air
discharge patterns in either the horizontal or vertical position.
Johnson Controls Unitary Products

505428-YTG-R-1114
Refer to the unit installation instructions for other application
possibilities.
Benefits
Air handling units are designed with two distinct modules to
provide maximum application flexibility. All are shipped as
single packages with the blower module mounted on top of
the coil module. The blower module can be repositioned in
the field to meet a large number of vertical and horizontal
applications.
The 7.5 thru 20 Ton blower module includes the blower
wheels along with factory-mounted motor and drive. The 25
Ton blower module includes the blower wheels with field
mounted motor and drives. All models offer two motor
horsepower options to meet both standard and high static
airflow requirements.
The coil module includes direct expansion coils, 2 in.
throwaway filters with the option to accept 4” filters, liquid line
solenoid valves for capacity reduction, thermal expansion
valves, distributors and a non-corrosive, composite
condensate drain pan.
Every air handling coil is pressurized with air and leak tested
under water. After the headers are brazed onto the coil and
the coil is installed in the unit, the coil is pressurized with
nitrogen for pressure testing and additional leak testing. After
the coil is evacuated and dehydrated, it is pressurized with a
holding charge of nitrogen for storage and/or shipping.
These air handlers, combined with condensing units, provide
years of quiet, efficient and dependable operation. These
units are manufactured under ISO 9001 Quality System
Certification.
Unit Installation
Units may be bottom-supported or ceiling-suspended and
can be arranged to meet almost any space or duct
requirements. Each unit is available with a choice of blower
motors horsepower and other accessories to make them
suitable for most applications.
Air Handling units are available in either two or four pipe
configurations from 7.5 to 25 tons. The dual and single circuit
options provide a wide variety of application and unit matchup possibilities.
Blower Motors: Different HP motors are available for each
unit to meet almost any air delivery requirement. All motors
are UL approved, have permanently lubricated ball bearings
and are mounted within the insulated cabinet of the units to
minimize the transmission of sound to the surrounding space.
1.5-5 HP motors are inherently protected. 7.5 HP motors
require motor overload protection.
Overload Relay (7.5HP): These blower motors do not have
inherent protection and require external motor overload
protection. NC/ND240 "F" models Overload Relays are
factory installed. NC300 models Overload Relays are field
installed. Power wiring for blower motor is supplied in the
Overload Relay Kit. See details in Overload Relay Kit and
Overload Relay Setting Tables on Page 70.

Johnson Controls Unitary Products

Factory-Mounted Components
Part Load Operation: These air handlers with DX (Direct
Expansion) coils rated at 10 tons of capacity and above have
multiple coils with pre-piped distributors, expansion valves
and solenoid valves. Field modifications are not required for
part load operations. Capacity reduction not only provides
economical operation, but also maintains stable temperature
and humidity levels in the conditioned space.
BAS Control: Simplicity® SE with Communication Option
Control - The York® Simplicity® SE with Communication
Option Control is factory installed. It includes all the features
of the Simplicity® SE control with an additional gateway to
BACnet MS/TP (programmable to Modbus or N2 protocols).
Easy Service: Serviceable expansion valves are provided on
every unit. These valves are factory-installed to provide many
years of trouble-free operation. If service is required, it is not
necessary to unbraze any joints. The expansion valves also
include a tee fitting to allow easy installation of hot gas
bypass if required.
Coil Protection: The indoor coils of these air handlers can
have factory applied Technicoat or Electrofin coating to
provide extended life to the indoor coil in standard
applications and additional corrosion protection on those
applications in sea coast or corrosive environments.
Accessories
Base Sections: Base sections can be used to elevate units
above the floor. If desired, a moderate percentage of outdoor
air may be introduced through these sections by cutting an
access opening to accommodate the outdoor air duct
connection. These bases include a durable finish to match
the evaporator blower unit. The base may have to be
insulated for certain applications.
Hot Water Coils: Drain-able water coils are available for field
installation between the blower and the coil modules of both
horizontal and vertical units. Since their casings match the
dimensions and the finish of the basic units, they become an
integral part of the unit after installation. The coils slide out of
their casings for easy installation. Hot water coils have
copper tubes that have been mechanically expanded into
aluminum fins. Both headers are located on the same end of
the coil. Coils are leak-tested at 325 psig under water and
dried before their connections are capped for storage and
shipping.
Steam Coils: Steam coils are available for installation
between the blower and coil modules of both horizontal and
vertical units. Since the casing matches the dimensions and
the finish of the basic unit, it becomes an integral part of the
unit after installation. The coil slides out of the casings for
easy installation and is pitched in the casings to facilitate
condensate drainage. The coil has copper tubes that have
been mechanically expanded into aluminum fins. Both
headers are located on the same end of the coil. The coil is
leak-tested at 325 psig and dried before the connections are
capped for storage and shipping.
Bottom Return: Air handling unit can be quickly converted to
bottom return for both vertical and horizontal applications. All
that is required is the removal of several screws and a single
5

505428-YTG-R-1114
panel on 7.5-15 ton and two panels on the 20 ton AHU.
Optional painted panel can be ordered to cover the side
return opening when utilizing the bottom return.
Supply Air Plenums: These fully insulated plenums are
available for free standing units located within the conditioned
space. They are shipped fully assembled for easy field
installation, are finished to match the exterior of the basic
unit, and include double deflection grills that can be adjusted
to vary the throw, spread and drop of the supply air.

• Unit shall be stored and handled in accordance with unit
manufacturer's instructions.
• Install each unit as shown on the plans in accordance
with the manufacturer’s recommendations and all
applicable national and local codes
Unit Construction
• Constructed of zinc-coated, galvanized steel.

Guide Specifications

• Exterior surfaces bonded and coated with baked
enamel finish by a powder paint process capable of
withstanding a minimum of 1000 salt spray hours
according to ASTM B117.

Split System Cooling Only Condensing Units
Models: YC090-300, YD120-240 & Split System Heat
Pump Models: PC090-240, PD180-240

• Cabinet screws that comply with ASTM B117 salt spray
test for a minimum of 750 hours.

General
• Factory assembled, single piece, air cooled condensing
unit designed for outdoor installation.
• Factory wired, piped, and tested for leakage and
functionality to assure trouble-free installation and startup.
• Rated in accordance with AHRI Standard 340/360.
• Manufactured in a facility registered under the ISO 9002
manufacturing quality standard.
• Designed and tested in accordance with ASHRAE 15
Safety Code for Mechanical Refrigeration and comply
with NEC.
• Cooling performance rated in accordance with DOE
and AHRI test procedures.
• CSA listed and classified to UL 1995/CAN/CSA No.
236- M90 standards.
• One year limited parts warranty on complete unit with
an additional four year compressor warranty.

• Permanently attached heavy-gage perimeter base rails
with forklift slots and lifting holes.
• Removable access panels to all internal components.
• Separate access panel to controls.
• Access panels to allow outdoor coil cleaning.
Compressor(s)
• Hermetic scroll type, internally protected with highpressure relief and over temperature protection.
• Two stage units operate in 50% capacity increments.
• Suction gas cooled
• Voltage range of ±10% of unit nameplate voltage.
• Neoprene isolators minimize sound transmission and
vibration.
• Belly-band crankcase heaters keep refrigerant from
diluting sump oil.
• Full charge of compressor oil
Outdoor Condenser Unit Coils

Unit Operating Characteristics

• Draw thru configuration

Operating Range shall be between 125° F to 40° F in cooling
as standard from factory.

• Constructed with Micro-channel aluminum fins and
aluminum tubing. All refrigerant tubing must share a
common header.

• The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of _____
F. The power consumption at full load shall not exceed
_____ kW.
• The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling
capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator at
_____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____F.
• The system shall have an EER of _____ Btuh/ Watt or
greater at standard AHRI conditions.
Installer Shall
• Furnish York® air-cooled condensing units, heat pump
or equivalent in accordance with the performance
schedule shown on the plans, and
6

Heat Pump Unit Outdoor Unit Coils
• Draw thru configuration
• Constructed with aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
Condenser Fans
• Direct driven propeller-type fans
• Statically and dynamically balanced
• Aluminum blades riveted to corrosion resistant steel
spider brackets.
• Arranged for vertical air discharge.
• Equipped with PVC coated steel wire safety guards.

Johnson Controls Unitary Products

505428-YTG-R-1114

Condenser Motors
• Totally enclosed, air over cooled.

BAS system (if applicable). The UCB will provide fault
messages in plain English to ensure the user can
easily understand the specific fault.

• Inherent overload protection.
• Permanently lubricated bearings.
• Must cycle to allow cooling operation down to 40°F.
Refrigerant Piping
• Solid core filter-drier(s) ship loose for field installation.

Non-fused Disconnect Switch
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• NEC and UL approved non-fused switch.
• Provides power off lockout capability.

• Liquid and suction line service valves with gauge ports.
• Suction and discharge line service ports accessible
from unit. Ports capped for leak prevention.

Convenience Outlet
• Factory-installed, internally mounted.

• Liquid line magnetic check valves

• Accessible from outside the unit.

• Holding charge of R410A refrigerant.

• 115V, 15 amp GFI receptacle with independent fuse
protection.

Electrical Requirements
• Single-point connection electrical power.
• Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of ____ v to _____ v.
• Condenser fan motors and secondary of transformers
shall be grounded.
Unit Controls
• All 24-volt control circuit, powered by a 24 volt
transformer(s) and protected by a resettable breaker.
• Conventional thermostat must provide operation for
both condensing units and heat pumps without an “O”
output from the thermostat.
• Low voltage terminal strip for simple hook-up.
• Compressor motor protection shuts down unit for motor
over-current, over-temperature or low voltage
conditions.
• Safety lockouts provide reset capability at the space
thermostat or base unit should any of the following
standard safety devices trip and shut off compressor:
a. Loss-of-charge/Low-pressure switch.
b. High-pressure switch.
c. Control board diagnostics and fault message display.
d. Safety lockouts send a 24 volt signal to the control
board's "X" terminal, allowing notification to the user
via the thermostat fault light (if present).
e. In the unlikely event any faults should occur, the unit
control board will store the faults in its internal
memory. The LCD display will scroll the 5 MOST
critical faults, however, all fault messages can be
extracted via USB device, displayed real-time via the
MAP Gateway as well as be broad-casted through a

Johnson Controls Unitary Products

• Required voltage provided by factory-installed stepdown transformer or field supplied 115v circuit.
Low-ambient Head Pressure Control
• Standard operation down to 40 °F without a low
ambient kit.
• Operation down to 0°F with a field-installed low ambient
kit accessory. The controller modulates the fan motor
speed in response to liquid line temperature or
pressure.
Coil Guard
Factory or field installed decorative grille shall be placed on
the units to protect condenser coil after installation.
Hail Guard Package
Field installed hail guard package shall protect coils against
damage from hail and other flying debris.
Coated Condenser Coils
Special phenolic or epoxy polymer coating available as a
factory option on both outdoor and indoor coils.
Each Unit Shall Be:
• Covered by a 1-year limited parts warranty on the
complete unit and 5-year on compressor(s).
• In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance.
• Indoor unit shall be equipped with a V-belt drive option
that will permit the blower RPM to be adjusted to meet
the CFM requirements of the air delivery system. (Refer
to Technical Guide for Airflow Capabilities.)

7

505428-YTG-R-1114

Each Unit Enclosure Shall Have:
• Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
• Removable panels to provide easy access to the
internal components for maintenance and service on
condensing units, heat pumps and air handlers
• Air handling units must have a filter rack that accepts
both 2” and 4” filters.
• The dimensions of each unit shall not exceed those
specified in the manufacturers literature.
• The minimum application clearances for condensing
units, heat pumps and air handlers must meet those
specified in the manufacturer’s literature.

The Blower Motor Shall:
• Be mounted within the insulated cabinet to minimize the
transmission of sound to the surrounding space, and
any motor 7.5 HP or greater must have a service factor
of 1.15.
The Evaporator Coil Shall:
• Consist of copper tubes arranged in staggered rows,
mechanically expanded into aluminum fins,
• Be draw-through, and
• Include factory-mounted distributors, expansion valves
and solenoid valves for capacity reduction.
The Blower Wheels Shall:
Be dynamically balanced to minimize the levels of sound and
vibration generated by the unit.

8

Johnson Controls Unitary Products

505428-YTG-R-1114

Physical Data
YC090 - 300 and YD120 - 240 Physical Data
Component
Nominal Tonnage
REFRIGERANT
Refrigerant type
Holding charge (lb)1 (each system)
System #1
Operating Charge (lb)2
System #2
DIMENSIONS (inches)
Length
Width
Height
WEIGHTS (lb)
Shipping
Operating
COMPRESSORS
Type
Quantity
Nominal Capacity (Tons)
Capacity Stages

System #1
System #2
System #1
System #2

SYSTEM DATA3
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)
OUTDOOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (in./MM)
Circuitry Type
Refrigerant Control
CONDENSER FAN DATA
No. Fans / Diameter (in.)
Type
Drive type
No. speeds
Number of motors

System #1
System #2

Motor HP (ea.)
Rotation4
RPM
Nominal CFM
1
2

3
4

System #1
System #2

YC090
7.5

YC120
10

YD120
10

YC150
12.5

Models
YD150
YC180
12.5
15

YD180
15

YC240
20

YD240
20

YC300
25

R-410A
1.0
14.0
---

R-410A
1.0
18.0
---

R-410A
1.0
9.9
9.9

R-410A
1.0
24.0
---

R-410A
1.0
11.5
11.5

R-410A
1.0
27.0
---

R-410A
1.0
13.5
13.5

R-410A
1.0
33.5
---

R-410A
1.0
18.8
18.8

R-410A
1.0
35
---

59.1
31.9
44.5

59.1
31.9
50.0

59.1
31.9
50.0

59.1
31.9
50.0

59.1
31.9
50.0

59.1
64.1
44.5

59.1
64.1
44.5

59.1
64.1
50.0

59.1
64.1
50.0

59.1
64.1
50.0

390
387

499
497

493
490

499
497

493
490

914
909

899
894

945
942

930
927

945
942

Single
Scroll
1
7.5
--1
---

Tandem
Scroll
1
10
--2
---

Single
Scroll
2
5
5
1
1

Tandem
Scroll
1
12.5
--2
---

Single
Scroll
2
6.3
6.3
1
1

Tandem
Scroll
1
15
--2
---

Single
Scroll
2
7.5
7.5
1
1

Tandem
Scroll
1
20
--2
---

Single
Scroll
2
10
10
1
1

Tandem
Scroll
1
25
--2
---

1
1 1/8
5/8

1
1 3/8
7/8

2
1 1/8
5/8

1
1 3/8
7/8

2
1 1/8
5/8

1
1 5/8
7/8

2
1 3/8
5/8

1
1 5/8
7/8

2
1 3/8
5/8

1
1 5/8
7/8

23.8
1
23
0.71 / 18
2-pass
---

29.0
1
23
0.71 / 18
2-pass
---

29.0
1
23
0.71 / 18
2-pass
---

29.0
1
23
0.71 / 18
2-pass
---

29.0
1
23
0.71 / 18
2-pass
---

47.5
1
23
0.71 / 18
2-pass
---

47.5
1
23
0.71 / 18
2-pass
---

58.1
1
23
0.71 / 18
2-pass
---

58.1
1
23
0.71 / 18
2-pass
---

58.1
1
23
0.71 / 18
2-pass
---

2/24
Axial
Direct
1
2
--1/3
CW
850
7500
---

2/24
Axial
Direct
1
2
--3/4
CW
1100
9800
---

2/24
Axial
Direct
1
2
--3/4
CW
1100
9800
---

2/24
Axial
Direct
1
2
--3/4
CW
1100
9800
---

2/24
Axial
Direct
1
2
--3/4
CW
1100
9800
---

4/24
Axial
Direct
1
4
--1/3
CW
850
15000
---

4/24
Axial
Direct
1
2
2
1/3
CW
850
7500
7500

4/24
Axial
Direct
1
4
--3/4
CW
1100
19600
---

4/24
Axial
Direct
1
2
2
3/4
CW
1100
9800
9800

4/24
Axial
Direct
1
4
--3/4
CW
1100
19600
---

Holding Charge is the amount in the unit as shipped from the factory.
Includes matched indoor blower unit with 25 ft of piping.
All compressors include crankcase heaters.
When viewing the shaft end of the motor.

Johnson Controls Unitary Products

9

505428-YTG-R-1114

PC090 - 240 and PD180 - 240 Physical Data
PC090
7.5

PC120
10

Models
PC180
15

PD180
15

PD240
20

R-410A
1.0
23.9
---

R-410A
1.0
31.75
---

R-410A
1.0
54.0
---

R-410A
1.0
27.0
27.0

R-410A
1.0
34.0
34.0

59.1
31.9
44.5

59.1
31.9
50.0

59.1
64.1
44.5

59.1
64.1
44.5

59.1
64.1
50.0

421
430

543
574

947
968

921
942

1090
1126

Single Scroll
1

Tandem Scroll
1

Tandem Scroll
1

Single Scroll
2

Single Scroll
2

System #1
System #2
System #1
System #2

7.5
--1
---

10
--2
---

15
--2
---

7.5
7.5
1
1

10
10
1
1

System #1 & #2
System #1 & #2

7.5
1

10
1

15
1

15
1

20
1

1
1 1/8
5/8

1
1 3/8
7/8

1
1 5/8
7/8

2
1 3/8
5/8

2
1 3/8
5/8

23.8
2
20
0.38 / 10
Interlaced
TXV

29.0
2
20
0.38 / 10
Interlaced
TXV

47.5
2
20
0.38 / 10
Interlaced
TXV

47.5
2
20
0.38 / 10
Interlaced
TXV

58.1
2
20
0.38 / 10
Interlaced
TXV

2/24
Axial
Direct
1
2
--1/3
CW
850
7500
---

2/24
Axial
Direct
1
2
--3/4
CW
1100
9800
---

4/24
Axial
Direct
1
4
--1/3
CW
850
15000
---

4/24
Axial
Direct
1
2
2
1/3
CW
850
7500
7500

4/24
Axial
Direct
1
2
2
3/4
CW
1100
9800
9800

Component
Nominal Tonnage
REFRIGERANT
Refrigerant type
Holding charge (lb)1
Operating Charge (lb)2

System #1
System #2

DIMENSIONS (inches)
Length
Width
Height
WEIGHTS (lb)
Shipping
Operating
COMPRESSORS3
Type
Quantity
Cooling
Nominal Capacity (Tons)
Capacity Stages
Heating
Nominal Capacity (Tons)
Capacity Stages
SYSTEM DATA
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)
OUTDOOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (in./MM)
Circuitry Type
Refrigerant Control
CONDENSER FAN DATA
No. Fans / Diameter (in.)
Type
Drive type
No. speeds
Number of motors

System #1
System #2

Motor HP (ea.)
Rotation4
RPM
Nominal CFM
1
2

3
4

10

System #1
System #2

Holding Charge is the amount in the unit as shipped from the factory.
Includes matched evaporator unit with 25 ft of piping.
All compressors include crankcase heaters.
When viewing the shaft end of the motor.

Johnson Controls Unitary Products

505428-YTG-R-1114

NC090 - 240 and ND120 - 240 Indoor Unit Physical Data
NC090
7 1/2

NC120
10

ND120
10

Models
NC180
15

ND180
15

NC240
20

ND240
20

Length

56.0

56.0

56.0

74.5

74.5

98.5

98.5

Width

30.0

30.0

30.0

33.0

33.0

30.0

30.0

Height

65.0

65.0

65.0

75.0

75.0

65.0

65.0

526

573

575

796

796

938

938

Standard Motor and Drive

498

539

541

764

764

873

873

High Static Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width
Quantity
INDOOR COIL
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant Control
SYSTEM DATA
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)
FILTERS
16 x 25 x 2
Size and Quantity Per
Model (In.)
20 x 24 x 2
FACE AREA (SQ. FT.)
16 x 25 x 4
Size and Quantity Per
Model (In.)
20 x 24 x 4
FACE AREA (SQ. FT.)

500

550

552

792

792

903

903

12 x 12
1

15 x 15
1

15 x 15
1

18 x 18
1

18 x 18
1

15 x 15
2

15 x 15
2

10.6
3
15
3/8
Interlaced
TXV

10.6
4
15
3/8
Interlaced
TXV

10.6
4
15
3/8
Interlaced
TXV

18.3
3
15
3/8
Interlaced
TXV

18.3
4
15
3/8
Interlaced
TXV

20.0
4
15
3/8
Interlaced
TXV

20.0
4
15
3/8
Interlaced
TXV

1
1 1/8
5/8

1
1 3/8
7/8

2
1 1/8
5/8

1
1 5/8
7/8

2
1 3/8
5/8

1
1 5/8
7/8

2
1 3/8
7/8

4
--11.1
4
--11.1

4
--11.1
4
--11.1

4
--11.1
4
--11.1

--6
20.0
--6
18.0

--6
20.0
--6
18.0

8
--22.2
8
--22.2

8
--22.2
8
--22.2

Component
Nominal Tonnage
DIMENSIONS (inches)

WEIGHTS (lb)
Unit Shipping
Unit Operating With

Johnson Controls Unitary Products

11

505428-YTG-R-1114

NC300 Indoor Unit Physical Data
Component
Nominal Tonnage
DIMENSIONS (inches)

Models
NC300
25

Length

100.1

Width

38.1
74.6

Height
WEIGHTS1 (lb)
Unit Shipping

1067

Unit Operating With
5 hp Motor and Drive

1130

7.5 hp Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width
Quantity
INDOOR COIL
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant Control
SYSTEM DATA
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)
FILTERS
Size and Quantity Per
20 x 25 x 2
Model (In.)
FACE AREA (SQ. FT.)
ACCESSORY
HOT WATER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (Copper) OD (In.)
Connections (Supply and Return) OD (In.)
Weight (lb)
SYSTEM COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (Copper) (In.)
Connection, (NPTE) (In.)
Inlet
Outlet
Weight (lb)

1157

1

12

18 X 18
2
25.8
4
16
3/8
Interlaced
TEV
1
2 1/8
7/8

10
34.7

21.2
2
12
1/2
1 3/8
150
18.2
1
8
1
2
1-1/2
160

Motors, Drive and Overload Kits must be
ordered separately for the NC300. The Motor
Drive and Overload Kits are to be field installed.

Johnson Controls Unitary Products

505428-YTG-R-1114

Unit Limitations
Condenser Unit limitations
Size
(Tons)

Model

090
(7.5)

PC

090
(7.5)

YC

120
(10)

PC

120
(10)

YC/YD

150
(12.5)

YC/YD

180
(15)

PC/PD

180
(15)

YC/YD

240
(20)

PC/PD

240
(20)

YC/YD

300
(25)

YC

Unit Voltage

Applied Voltage1

208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60

Min

Max

187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540

252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630

Outdoor DB Temp
Cooling (°F)
Max
Min†

Indoor DB Temp
Cooling (°F)
Max
Min

Outdoor DB Temp
Heating (°F)
Max
Min

Indoor DB Temp
Heating (°F)
Max
Min

125

40

86

68

70

0

80

50

125

40

86

68

-

-

-

-

125

40

86

68

70

0

80

50

125

40

86

68

-

-

-

-

125

40

86

68

-

-

-

-

125

40

86

68

70

0

80

50

125

40

86

68

-

-

-

-

125

40

86

68

70

0

80

50

125

40

86

68

-

-

-

-

125

40

86

68

-

-

-

-

1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.

Johnson Controls Unitary Products

13

505428-YTG-R-1114

Air Handling Unit Limitations
Entering Air Temperature Degrees °F
Model

NC090

NC120

ND120

NC180

ND180

NC240

ND240

NC300

1

14

Power Supply Voltage

Voltage Variation

Supply Air Range CFM

Cooling
DB/WB

Heating DB1

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

208/230-3-60

187

253

2,250

3,750

65/57

90/77

40

80

460-3-60

414

506

2,250

3,750

65/57

90/77

40

80

575-3-60

540

630

2,250

3,750

65/57

90/77

40

80

208/230-3-60

187

253

3,000

5,000

65/57

90/77

40

80

460-3-60

414

506

3,000

5,000

65/57

90/77

40

80

575-3-60

540

630

3,000

5,000

65/57

90/77

40

80

208/230-3-60

187

253

3,000

5,000

65/57

90/77

40

80

460-3-60

414

506

3,000

5,000

65/57

90/77

40

80

575-3-60

540

630

3,000

5,000

65/57

90/77

40

80

208/230-3-60

187

253

4,500

7,500

65/57

90/77

40

80

460-3-60

414

506

4,500

7,500

65/57

90/77

40

80

575-3-60

540

630

4,500

7,500

65/57

90/77

40

80

208/230-3-60

187

253

4,500

7,500

65/57

90/77

40

80

460-3-60

414

506

4,500

7,500

65/57

90/77

40

80

575-3-60

540

630

4,500

7,500

65/57

90/77

40

80

208/230-3-60

187

253

6,000

10,000

65/57

90/77

40

80

460-3-60

414

506

6,000

10,000

65/57

90/77

40

80

575-3-60

540

630

6,000

10,000

65/57

90/77

40

80

208/230-3-60

187

253

6,000

10,000

65/57

90/77

40

80

460-3-60

414

506

6,000

10,000

65/57

90/77

40

80

575-3-60

540

630

6,000

10,000

65/57

90/77

40

80

208/230-3-60

187

253

8,000

12,000

65/57

90/77

40

80

460-3-60

414

506

8,000

12,000

65/57

90/77

40

80

575-3-60

540

630

8,000

12,000

65/57

90/77

40

80

Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.

Johnson Controls Unitary Products

505428-YTG-R-1114

Cooling and Heating Ratings
Cooling And Heating Rating
System Cooling Capacity1

Condensing Unit Only
Outdoor Unit

Gross Capacity2
(MBH)

KW

EER

Indoor
Unit

Heating Capacity1
High Outdoor

Gross Capacity3
(MBH)

EER

IEER

IPLV

Gross
Capacity2
(MBh)

COP

Low Outdoor
Gross
Capacity2
(MBh)

COP

Rated
Airflow
(CFM)

PC0904

N/A

N/A

N/A

NC090

92

11.0

11.4

---

82

3.3

49

2.3

3000

PC1204

N/A

N/A

N/A

NC120

124

11.0

11.4

11.8

109

3.3

63

2.1

4000

PC1804

N/A

N/A

N/A

NC180

180

10.6

11.5

12.4

168

3.3

104

2.3

6000

PD1804

N/A

N/A

N/A

ND180

180

10.6

11.5

12.0

168

3.4

103

2.4

6000

PD2404

N/A

N/A

N/A

ND240

238

10.6

11.7

12.1

220

3.4

124

2.2

8000

YC090

85

6.8

12.4

NC090

94

11.2

13.0

---

N/A

N/A

N/A

N/A

3000

YC090

85

6.8

12.4

NC120

99

11.9

13.0

---

N/A

N/A

N/A

N/A

3000

YC120

110

9.3

11.9

NC120

124

11.4

12.5

12.9

N/A

N/A

N/A

N/A

4000

YD120

108

9.1

11.8

ND120

124

11.2

11.2

11.6

N/A

N/A

N/A

N/A

4000

YC150

133

11.6

11.5

NC180

150

11.0

13.3

13.8

N/A

N/A

N/A

N/A

5000

YD150

136

11.5

11.8

ND180

150

11.0

12.1

12.3

N/A

N/A

N/A

N/A

5000

YC180

160

13.4

12.0

NC180

181

11.2

12.2

12.5

N/A

N/A

N/A

N/A

6000

YC180

160

13.4

12.0

NC240

190

11.7

12.7

12.5

N/A

N/A

N/A

N/A

6000

YD180

166

12.3

13.4

ND180

181

11.2

11.6

12.4

N/A

N/A

N/A

N/A

6000

YD180

166

12.3

13.4

(2)NC090

187

11.2

--

--

N/A

N/A

N/A

N/A

6000

YD180

166

12.3

13.4

(2)NC120

187

11.2

--

--

N/A

N/A

N/A

N/A

6000

YD180

166

12.3

13.4

ND240

190

11.7

13.4

11.2

N/A

N/A

N/A

N/A

6000

YC240

233

17.5

13.2

NC240

242

11.3

13.6

13.1

N/A

N/A

N/A

N/A

8000

YD240

222

17.3

12.8

ND240

242

11.3

11.9

12.6

N/A

N/A

N/A

N/A

8000

YD240

222

17.3

12.8

(2)NC120

240

11.6

--

--

N/A

N/A

N/A

N/A

8000

YC300

271

23.7

11.4

NC300

299

10.2

12.2

--

N/A

N/A

N/A

N/A

10000

1
2
3
4

Certified in accordance with the Unitary Large Equipment certification program, which is based on AHRI Standard 340/360. (Except
YC300)
Condensing unit only ratings are at 45°F SST and 95°F entering-air temperature.
Gross capacity does not include heat added by blower motor. Refer to appropriate table for blower horsepower.
Heat Pumps designed for matched systems only.

LEGEND
EER = Energy Efficiency Ratio
AHRI = Air Conditioning and Refrigeration Institute
IPLV = Integration Part-Load Value
IEER = Integrated Energy Efficiency Ratio

Johnson Controls Unitary Products

15

505428-YTG-R-1114

Capacity Performance
Condenser and Air Handling Cooling Capacities
YC090/NC090
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

2250

2625

3000

3375

3750

16

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

110.8
103.3
95.9
88.0
77.7
114.0
106.3
98.7
90.6
79.9
117.2
109.3
101.4
93.1
82.2
109.2
101.3
93.0
82.1
109.1
101.2
92.9
82.0

6.0
5.7
5.5
5.4
5.2
6.0
5.7
5.4
5.4
5.2
5.9
5.7
5.4
5.4
5.2
5.8
5.5
5.5
5.3
5.9
5.6
5.6
5.4

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

103.7
96.5
89.4
81.6
82.5
106.4
99.0
91.7
83.7
84.6
109.0
101.5
94.0
85.8
86.8
101.7
94.2
86.0
86.9
101.9
94.3
86.1
87.1

6.9
6.9
6.9
6.7
6.7
7.0
7.0
6.9
6.8
6.7
7.1
7.0
7.0
6.8
6.8
7.1
7.0
6.8
6.8
7.1
7.0
6.9
6.9

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
75°F
51.5
42.0 32.6
107.2
6.5
66.5
57.0 47.6 38.1
99.9
6.3
81.5
72.0 62.6 53.1 43.6
92.6
6.2
88.0
86.3 76.8 67.3 57.8 48.3
84.8
6.1
77.7
77.7 72.2 62.8 53.3 43.8
80.1
6.0
56.3
45.6 34.8
110.2
6.5
72.3
61.6 50.9 40.1
102.7
6.3
88.4
77.6 66.9 56.2 45.5
95.2
6.2
90.6
89.7 82.2 71.9 60.7 50.0
87.1
6.1
79.9
79.9 77.2 67.3 55.8 45.0
82.3
6.0
61.0
49.1 37.1
113.1
6.5
78.1
66.2 54.2 42.2
105.4
6.4
95.2
83.2 71.3 59.3 47.3
97.7
6.2
93.1
93.1 87.5 76.5 63.6 51.6
89.5
6.1
82.2
82.2 82.2 71.7 58.3 46.3
84.5
6.0
83.0
70.2 57.3 44.4
105.4
6.4
98.2
88.2 75.3 62.5 49.6
97.7
6.3
93.0
93.0 90.2 77.8 64.5 51.6
89.5
6.2
82.1
82.1 82.1 70.0 56.4 43.5
84.5
6.1
87.9
74.2 60.4 46.6
105.5
6.5
101.2 93.2 79.4 65.7 51.9
97.8
6.3
92.9
92.9 92.9 79.1 65.3 51.6
89.5
6.2
82.0
82.0 82.0 68.2 54.4 40.7
84.5
6.1
95°F
48.1
38.7 29.2
99.2
8.0
63.3
53.8 44.4 35.0
92.2
8.0
78.4
69.0 59.5 50.1 40.7
85.2
8.0
81.6
81.6 72.1 62.7 53.3 43.8
77.9
7.7
82.5
82.5 74.0 64.5 55.1 45.7
78.8
7.8
52.9
42.3 31.8
101.7
8.1
69.4
58.8 48.2 37.7
94.5
8.1
85.8
75.3 64.7 54.1 43.6
87.3
8.0
83.7
83.7 78.4 67.3 57.2 46.7
79.9
7.8
84.6
84.6 80.4 69.1 59.2 48.7
80.7
7.9
57.7
46.0 34.3
104.1
8.1
75.5
63.8 52.1 40.4
96.8
8.1
93.3
81.5 69.8 58.1 46.4
89.4
8.1
85.8
85.8 84.6 72.0 61.2 49.5
81.8
7.9
86.8
86.8 86.8 73.6 63.4 51.7
82.7
7.9
80.2
67.5 54.7 41.9
96.9
8.1
93.8
86.1 73.3 60.5 47.7
89.5
8.1
86.0
86.0 85.4 72.1 59.8 47.0
82.0
7.9
86.9
86.9 86.9 73.4 61.4 48.6
82.8
7.9
85.0
71.1 57.3 43.4
97.1
8.1
94.3
90.7 76.8 62.9 49.1
89.7
8.1
86.1
86.1 86.1 72.3 58.4 44.5
82.1
7.9
87.1
87.1 87.1 73.2 59.4 45.5
83.0
7.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
85°F
49.8 40.4 30.9
64.9 55.4 46.0 36.5
80.0 70.5 61.0 51.6 42.1
84.8 83.9 74.5 65.0 55.5
80.1 80.1 73.1 63.6 54.2
54.6 44.0 33.3
70.8 60.2 49.6 38.9
87.1 76.4 65.8 55.2 44.5
87.1 86.7 80.3 69.6 59.0
82.3 82.3 78.8 68.2 57.5
59.4 47.5 35.7
76.8 65.0 53.1 41.3
94.2 82.4 70.5 58.7 46.9
89.5 89.5 86.1 74.2 62.4
84.5 84.5 84.5 72.7 60.8
81.6 68.8 56.0 43.2
96.0 87.2 74.3 61.5 48.7
89.5 89.5 87.8 75.0 62.1
84.5 84.5 84.5 71.7 58.9
86.5 72.6 58.8 45.0
97.8 91.9 78.1 64.3 50.5
89.5 89.5 89.5 75.7 61.9
84.5 84.5 84.5 70.7 56.9
105°F
47.5 38.1 28.6
62.1 52.6 43.2 33.7
76.6 67.2 57.7 48.3 38.8
77.9 77.9 69.2 59.7 50.3
78.8 78.8 70.0 60.5 51.1
53.5 41.7 31.1
68.1 57.5 46.9 36.3
82.8 73.3 62.7 52.1 41.5
79.9 79.9 75.2 64.4 54.0
80.7 80.7 76.1 65.1 54.8
59.4 45.4 33.6
74.2 62.5 50.7 38.9
89.0 79.5 67.8 56.0 44.3
81.8 81.8 81.2 69.0 57.7
82.7 82.7 82.1 69.6 58.6
79.2 66.3 53.5 40.7
89.4 83.7 71.5 58.7 45.8
82.0 82.0 81.7 68.6 56.0
82.8 82.8 82.6 69.3 56.9
84.1 70.2 56.3 42.4
89.7 87.9 75.3 61.4 47.4
82.1 82.1 82.1 68.2 54.3
83.0 83.0 83.0 69.1 55.2

65
46.1
44.7
48.3
46.9
50.6
49.0
49.3
46.0
48.1
43.1
40.9
41.6
43.4
44.2
46.0
46.9
43.2
44.1
40.4
41.2

Johnson Controls Unitary Products

505428-YTG-R-1114

YC090/NC090 (Continued)
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

94.7
87.8
80.9
74.3
75.0
97.0
89.9
82.8
76.1
76.8
99.2
92.0
84.8
77.8
78.6
92.2
84.9
78.0
78.7
92.3
85.1
78.1
78.9

9.0
9.1
9.1
8.8
8.9
9.1
9.1
9.2
8.8
9.0
9.1
9.2
9.2
8.9
9.0
9.2
9.2
8.9
9.0
9.1
9.2
8.9
9.0

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
115°F
46.9
37.5 28.0
90.2
10.1
60.9
51.4 42.0 32.5
83.4
10.2
74.8
65.4 55.9 46.5 37.0
76.7
10.3
74.3
74.3 66.2 56.8 47.3 37.9
70.6
9.9
75.0
75.0 66.0 56.5 47.0 37.6
71.3
10.0
54.0
41.1 30.5
92.3
10.1
66.9
56.3 45.6 35.0
85.3
10.2
79.8
71.4 60.8 50.2 39.5
78.4
10.3
76.1
76.1 72.0 61.4 50.8 40.1
72.2
9.9
76.8
76.8 71.7 61.1 50.5 39.8
72.9
10.1
61.1
44.7 32.9
94.3
10.2
72.9
61.1 49.3 37.5
87.2
10.3
84.8
77.5 65.7 53.9 42.1
80.2
10.3
77.8
77.8 77.8 66.0 54.2 42.4
73.8
9.9
78.6
78.6 77.5 65.7 53.9 42.1
74.5
10.1
78.1
65.2 52.3 39.4
87.4
10.2
84.9
81.3 69.7 56.8 44.0
80.3
10.3
78.0
78.0 78.0 65.1 52.2 39.3
74.0
9.9
78.7
78.7 78.2 65.3 52.4 39.5
74.6
10.1
83.3
69.3 55.4 41.4
87.5
10.2
85.1
85.1 73.8 59.8 45.8
80.4
10.3
78.1
78.1 78.1 64.1 50.2 36.2
74.1
9.9
78.9
78.9 78.9 64.9 51.0 37.0
74.8
10.0

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
125°F
46.3 36.9 27.4
59.7 50.2 40.8 31.3
73.0 63.6 54.1 44.6 35.2
70.6 70.6 63.3 53.8 44.3
71.3 71.3 61.9 52.5 43.0
54.6 40.5 29.8
65.7 55.0 44.3 33.7
76.8 69.5 58.9 48.2 37.5
72.2 72.2 68.9 58.4 47.5
72.9 72.9 67.4 57.1 46.1
62.8 44.1 32.2
71.7 59.8 47.9 36.1
80.2 75.5 63.6 51.8 39.9
73.8 73.8 73.8 63.0 50.7
74.5 74.5 72.9 61.8 49.1
77.0 64.1 51.2 38.2
80.3 78.9 67.9 55.0 42.1
74.0 74.0 74.0 61.5 48.4
74.6 74.6 73.8 61.3 47.9
82.4 68.4 54.4 40.4
80.4 80.4 72.2 58.2 44.2
74.1 74.1 74.1 60.1 46.1
74.8 74.8 74.8 60.8 46.8

65
34.9
33.5
36.9
35.4
38.8
37.3
35.4
35.0
32.1
32.8

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

17

505428-YTG-R-1114

YC090/NC120
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

2250

2625

3000

3375

3750

18

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

105.1
100.1
95.1
87.9
83.1
109.8
104.5
99.3
91.8
86.7
114.5
109.0
103.5
95.7
90.4
110.2
104.6
96.7
91.4
111.4
105.8
97.8
92.4

6.0
5.8
5.7
5.6
5.5
6.0
5.9
5.7
5.6
5.6
6.1
5.9
5.8
5.7
5.6
6.0
5.8
5.7
5.6
6.0
5.9
5.7
5.7

49.2
63.3
77.3
87.9
83.1
53.6
68.6
83.5
91.8
86.7
58.0
73.9
89.8
95.7
90.4
77.6
94.1
96.7
91.4
81.3
98.4
97.8
92.4

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

111.4
102.8
94.2
87.4
85.2
114.2
105.4
96.6
89.6
87.4
117.1
108.0
99.0
91.9
89.6
110.4
101.2
93.9
91.5
112.8
103.3
95.9
93.5

7.2
7.1
7.0
6.8
6.8
7.3
7.2
7.0
6.9
6.8
7.3
7.2
7.1
6.9
6.9
7.2
7.1
7.0
6.9
7.3
7.1
7.0
6.9

51.3
64.0
76.7
87.4
85.2
55.3
68.7
82.1
89.6
87.4
59.3
73.4
87.5
91.9
89.6
77.7
92.5
93.9
91.5
82.1
97.4
95.9
93.5

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
40.2 31.1
108.2
6.6
54.2 45.1 36.0
101.4
6.5
68.2 59.1 50.0 40.9
94.6
6.3
80.9 71.8 62.7 53.7 44.6
87.7
6.2
83.1 76.8 67.7 58.6 49.5
84.1
6.2
43.4 33.2
112.0
6.7
58.3 48.1 37.9
105.0
6.5
73.3 63.1 52.9 42.6
97.9
6.4
86.9 76.7 66.8 56.2 46.0
90.7
6.2
86.7 82.0 72.3 61.5 51.3
87.1
6.2
46.6 35.3
115.8
6.7
62.5 51.2 39.8
108.5
6.6
78.4 67.1 55.7 44.4
101.2
6.4
92.9 81.5 70.8 58.8 47.5
93.8
6.3
90.4 87.1 76.9 64.4 53.1
90.0
6.3
65.3 53.1 40.8
110.3
6.6
81.8 69.5 57.3 45.0
102.9
6.5
95.3 84.5 72.6 60.0 47.7
95.3
6.3
91.4 89.8 78.0 65.2 53.0
91.5
6.3
68.1 54.9 41.8
112.1
6.6
85.2 72.0 58.8 45.6
104.5
6.5
97.8 87.5 74.3 61.1 47.9
96.8
6.4
92.4 92.4 79.2 66.0 52.8
93.0
6.3
95°F
42.3 33.2
107.2
8.2
54.9 45.9 36.8
99.1
8.0
67.6 58.5 49.5 40.4
90.9
7.9
80.9 71.8 62.7 53.6 44.6
84.0
7.8
85.2 77.7 68.6 59.6 50.5
82.3
7.7
45.2 35.0
110.2
8.3
58.5 48.4 38.2
101.8
8.1
71.9 61.8 51.6 41.5
93.4
8.0
85.9 75.8 65.3 55.5 45.3
86.3
7.9
87.4 82.0 71.3 61.7 51.6
84.6
7.8
48.1 36.9
113.1
8.3
62.2 50.9 39.7
104.5
8.2
76.2 65.0 53.8 42.5
95.9
8.1
91.0 79.7 67.9 57.3 46.0
88.6
7.9
89.6 86.3 74.0 63.8 52.6
86.9
7.8
65.5 53.3 41.1
106.7
8.2
80.2 68.0 55.8 43.6
97.9
8.1
93.4 83.4 70.9 59.0 46.8
90.5
8.0
91.5 89.9 77.1 65.5 53.2
88.7
7.9
68.9 55.7 42.4
108.9
8.3
84.2 71.0 57.8 44.6
100.0
8.1
95.9 87.1 73.9 60.7 47.5
92.4
8.0
93.5 93.5 80.3 67.1 53.9
90.5
7.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
85°F
50.3 41.2 32.1
63.6 54.6 45.5 36.4
77.0 67.9 58.8 49.7 40.7
87.7 80.9 71.8 62.7 53.7
84.1 84.1 77.2 68.2 59.1
54.5 44.3 34.1
68.6 58.4 48.3 38.1
82.8 72.6 62.4 52.2 42.1
90.7 86.4 76.2 66.0 55.8
87.1 87.1 82.0 71.8 61.6
58.7 47.4 36.1
73.6 62.3 51.1 39.8
88.6 77.3 66.0 54.7 43.4
93.8 91.9 80.6 69.3 58.0
90.0 90.0 86.7 75.4 64.1
77.7 65.4 53.2 40.9
93.3 81.0 68.8 56.5 44.3
95.3 94.4 84.0 71.7 59.5
91.5 91.5 89.8 77.6 65.3
81.7 68.5 55.3 42.1
97.9 84.7 71.5 58.3 45.1
96.8 96.8 87.3 74.1 60.9
93.0 93.0 93.0 79.8 66.6
105°F
49.9 40.9 31.8
62.6 53.5 44.5 35.4
75.3 66.2 57.1 48.1 39.0
84.0 79.3 70.2 61.1 52.0
82.3 82.3 74.9 65.8 56.8
53.9 43.8 33.6
67.4 57.2 47.0 36.9
80.8 70.6 60.5 50.3 40.1
86.3 83.7 74.3 63.9 53.9
84.6 84.6 79.3 68.8 58.9
58.0 46.7 35.5
72.1 60.9 49.6 38.4
86.3 75.0 63.8 52.5 41.3
88.6 88.2 78.3 66.8 55.8
86.9 86.9 83.6 71.8 61.1
76.4 64.2 52.0 39.7
91.3 79.0 66.8 54.6 42.3
90.5 90.3 82.0 69.7 57.6
88.7 88.7 87.1 74.6 62.6
80.8 67.6 54.3 41.1
96.3 83.0 69.8 56.6 43.4
92.4 92.4 85.8 72.5 59.3
90.5 90.5 90.5 77.3 64.1

65
44.6
50.0
45.7
51.4
46.7
52.8
47.2
53.1
47.7
53.4
43.0
47.7
43.8
48.8
44.6
49.8
45.3
50.4
46.1
50.9

Johnson Controls Unitary Products

505428-YTG-R-1114

YC090/NC120 (Continued)
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

103.1
95.4
87.6
80.6
79.5
106.1
98.2
90.3
83.0
81.8
109.2
101.0
92.9
85.4
84.2
103.1
94.7
87.1
85.9
105.1
96.6
88.8
87.6

9.1
9.0
8.9
8.7
8.6
9.2
9.1
9.0
8.8
8.7
9.3
9.2
9.1
8.9
8.8
9.2
9.1
9.0
8.8
9.2
9.1
9.0
8.8

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
115°F
48.5 39.5 30.4
98.9
10.1
61.2 52.1 43.1 34.0
91.6
9.9
73.9 64.8 55.8 46.7 37.6
84.4
9.8
80.6 77.7 68.6 59.5 50.4 41.4
77.2
9.7
79.5 79.5 72.1 63.0 54.0 44.9
76.6
9.5
52.6 42.4 32.2
102.1
10.2
66.0 55.9 45.7 35.5
94.6
10.1
79.5 69.3 59.1 49.0 38.8
87.1
9.9
83.0 81.5 72.8 62.6 52.4 42.3
79.7
9.8
81.8 81.8 76.5 66.3 56.2 46.0
79.0
9.6
56.6 45.3 34.1
105.3
10.3
70.8 59.6 48.3 37.0
97.5
10.2
85.1 73.8 62.5 51.3 40.0
89.8
10.1
85.4 85.4 76.9 65.7 54.4 43.1
82.2
10.0
84.2 84.2 80.9 69.6 58.4 47.1
81.5
9.8
75.2 62.9 50.7 38.4
99.4
10.2
90.1 77.8 65.6 53.3 41.1
91.5
10.1
87.1 87.1 80.7 68.4 56.2 43.9
83.7
10.0
85.9 85.9 84.2 72.0 59.7 47.5
83.0
9.8
79.5 66.2 53.0 39.8
101.3
10.2
95.1 81.9 68.6 55.4 42.1
93.2
10.1
88.8 88.8 84.4 71.2 57.9 44.7
85.3
10.0
87.6 87.6 87.6 74.3 61.1 47.8
84.6
9.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
125°F
47.1 38.0 29.0
59.8 50.7 41.7 32.6
72.5 63.4 54.4 45.3 36.2
77.2 76.0 67.0 57.9 48.8
76.6 76.6 69.3 60.2 51.2
51.2 41.0 30.8
64.7 54.5 44.3 34.2
78.2 68.0 57.8 47.7 37.5
79.7 79.3 71.2 61.2 50.9
79.0 79.0 73.7 63.8 53.4
55.2 44.0 32.7
69.5 58.3 47.0 35.7
83.9 72.6 61.3 50.0 38.7
82.2 82.2 75.5 64.5 53.0
81.5 81.5 78.2 67.4 55.6
73.9 61.6 49.3 37.1
88.9 76.6 64.4 52.1 39.8
83.7 83.7 79.3 67.2 54.7
83.0 83.0 81.4 69.4 56.8
78.2 64.9 51.7 38.4
93.2 80.7 67.4 54.2 40.9
85.3 85.3 83.1 69.8 56.5
84.6 84.6 84.6 71.3 58.1

65
39.8
42.1
40.7
43.2
41.7
44.3
42.5
44.6
43.3
44.8

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

19

505428-YTG-R-1114

YC120/NC120
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

3000

3500

4000

4500

5000

20

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

142.3
133.9
125.5
115.0
111.2
151.4
142.4
133.4
122.3
118.3
160.5
150.9
141.4
129.6
125.4
154.4
144.7
132.6
128.3
157.9
148.0
135.6
131.2

7.5
7.4
7.3
7.3
7.2
7.5
7.4
7.3
7.3
7.2
7.5
7.4
7.3
7.3
7.2
7.5
7.4
7.3
7.3
7.5
7.4
7.3
7.3

64.7
84.4
104.0
115.0
111.2
72.3
94.1
116.0
122.3
118.3
79.8
103.9
128.0
129.6
125.4
110.8
138.0
132.6
128.3
117.6
148.0
135.6
131.2

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

136.4
125.1
113.7
107.7
106.5
142.6
130.7
118.9
112.6
111.3
148.8
136.4
124.0
117.4
116.1
142.0
129.1
122.2
120.8
147.5
134.1
127.0
125.6

9.5
9.4
9.3
9.2
9.3
9.5
9.4
9.4
9.2
9.4
9.6
9.5
9.4
9.2
9.4
9.5
9.4
9.3
9.4
9.5
9.4
9.3
9.4

69.6
86.2
102.9
107.7
106.5
76.1
94.0
111.9
112.6
111.3
82.7
101.8
120.9
117.4
116.1
110.7
127.5
122.2
120.8
119.5
134.1
127.0
125.6

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
52.6
40.5
139.4
8.5
72.2
60.1
48.0
129.5
8.4
91.9
79.8
67.7 55.6
119.6
8.3
109.5
94.2
82.0 69.9 57.8
111.3
8.2
111.2
99.9
87.8 75.7 63.6
108.8
8.3
58.7
45.2
147.0
8.5
80.6
67.0
53.5
136.6
8.4
102.5
88.9
75.4 61.8
126.1
8.3
119.6 105.0
92.1 77.9 64.4
117.4
8.3
118.3 111.3
98.6 84.2 70.7
114.8
8.3
64.9
49.9
154.6
8.6
88.9
73.9
59.0
143.7
8.5
113.0
98.0
83.0 68.1
132.7
8.4
129.6 115.9 102.2 86.0 71.0
123.5
8.3
125.4 122.8 109.5 92.8 77.8
120.7
8.3
94.3
77.8
61.4
148.2
8.5
119.7 103.2
86.8 70.3
136.9
8.4
132.6 124.4 108.6 91.5 75.0
127.4
8.3
128.3 127.0 111.4 94.0 77.6
124.6
8.3
99.7
81.7
63.8
152.7
8.5
126.4 108.5
90.5 72.6
141.1
8.4
135.6 132.9 114.9 97.0 79.1
131.3
8.3
131.2 131.2 113.2 95.3 77.4
128.4
8.4
95°F
56.7
43.8
127.0
10.7
73.3
60.5
47.6
117.1
10.7
90.0
77.1
64.2 51.3
107.2
10.6
107.7
98.1
85.2 72.3 59.4
100.8
10.5
106.5
98.6
85.7 72.8 59.9
100.2
10.6
61.6
47.1
133.4
10.8
79.5
64.9
50.4
123.1
10.7
97.4
82.8
68.3 53.7
112.7
10.6
112.6 105.3
90.2 76.3 61.7
106.0
10.5
111.3 105.9
90.5 76.8 62.3
105.3
10.6
66.5
50.3
139.9
10.8
85.6
69.4
53.2
129.0
10.7
104.7
88.5
72.3 56.1
118.2
10.6
117.4 112.6
95.1 80.2 64.0
111.1
10.5
116.1 113.2
95.3 80.8 64.6
110.5
10.6
93.0
75.4
57.7
133.3
10.7
113.8
96.1
78.5 60.8
122.1
10.6
122.2 119.8 101.5 84.5 66.9
114.8
10.5
120.8 119.4 100.9 84.1 66.4
114.1
10.6
100.4
81.3
62.2
137.7
10.7
122.8 103.7
84.6 65.5
126.1
10.7
127.0 127.0 107.9 88.8 69.7
118.5
10.5
125.6 125.6 106.5 87.4 68.3
117.8
10.6

90
67.1
85.3
103.4
111.3
108.8
74.2
94.1
114.0
117.4
114.8
81.3
102.9
124.5
123.5
120.7
110.7
132.8
127.4
124.6
118.6
141.1
131.3
128.4
66.5
83.6
100.7
100.8
100.2
75.3
92.0
108.7
106.0
105.3
84.1
100.4
116.6
111.1
110.5
109.1
121.3
114.8
114.1
117.9
126.1
118.5
117.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
54.6
42.1
72.8
60.3
47.8
90.9
78.5
66.0 53.5
108.6
96.1
83.6 71.1
108.8
99.2
86.7 74.2
60.2
46.1
80.0
66.0
51.9
99.9
85.9
71.8 57.8
116.1 105.2
91.1 77.1
114.8 108.6
94.6 80.5
65.7
50.1
87.3
71.7
56.1
108.9
93.3
77.7 62.1
123.5 114.3
98.7 83.1
120.7 118.0 102.4 86.8
93.7
76.6
59.6
116.7
99.7
82.6 65.6
127.4 122.1 105.1 88.0
124.6 123.2 106.1 89.1
100.0
81.5
63.0
124.6 106.1
87.6 69.1
131.3 129.9 111.4 92.9
128.4 128.4 109.9 91.4
105°F
53.5
40.6
70.6
57.7
44.8
87.8
74.8
61.9 48.9
100.8
93.7
80.8 67.9
100.2
91.6
78.7 65.8
58.7
44.1
77.3
62.7
48.1
96.0
81.3
66.7 52.0
106.0 101.9
86.9 72.6
105.3
99.5
84.5 70.3
63.9
47.6
84.0
67.7
51.3
104.1
87.8
71.5 55.1
111.1 110.0
93.0 77.3
110.5 107.4
90.2 74.7
91.2
73.2
55.2
112.3
95.0
77.0 59.0
114.8 114.3
96.0 78.3
114.1 112.6
94.2 76.7
98.3
78.7
59.1
120.4 102.1
82.5 62.9
118.5 118.5
99.0 79.4
117.8 117.8
98.2 78.7

65
58.6
61.7
63.1
66.5
67.5
71.2
70.9
72.0
74.4
72.8
54.9
52.8
57.9
55.6
60.9
58.4
60.4
58.7
59.8
59.1

Johnson Controls Unitary Products

505428-YTG-R-1114

YC120/NC120 (Continued)
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

117.5
109.1
100.8
94.0
94.0
124.2
115.4
106.6
99.4
99.4
131.0
121.7
112.3
104.8
104.8
124.7
115.2
107.4
107.4
127.8
118.0
110.1
110.1

12.0
11.9
11.9
11.8
11.8
12.0
11.9
11.9
11.8
11.8
12.0
11.9
11.9
11.8
11.8
11.9
11.9
11.8
11.8
12.0
11.9
11.8
11.9

63.4
81.0
98.6
94.0
94.0
74.4
89.9
105.5
99.4
99.4
85.5
98.9
112.3
104.8
104.8
107.6
115.2
107.4
107.4
116.3
118.0
110.1
110.1

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
50.4
37.4
108.0
13.2
68.0
55.0
41.9
101.2
13.2
85.6
72.6
59.5 46.5
94.3
13.1
94.0
89.4
76.4 63.4 50.4
87.2
13.0
94.0
84.7
71.7 58.7 45.7
87.8
13.1
55.8
41.1
115.1
13.2
75.2
60.4
45.7
107.7
13.2
94.6
79.8
65.1 50.3
100.4
13.1
99.4
98.4
83.6 68.9 54.1
92.8
13.0
99.4
93.2
78.5 63.7 49.0
93.5
13.1
61.3
44.8
122.1
13.2
82.4
65.9
49.5
114.3
13.2
103.5
87.1
70.6 54.1
106.5
13.1
104.8 107.3
90.8 74.4 57.9
98.5
13.1
104.8 101.7
85.2 68.7 52.2
99.2
13.1
89.3
71.0
52.8
116.1
13.2
110.8
93.8
75.5 57.2
108.2
13.1
107.4 108.7
90.4 72.1 53.8
100.0
13.1
107.4 105.9
87.6 69.3 51.0
100.7
13.1
96.2
76.1
56.1
117.9
13.2
118.0 100.5
80.4 60.4
109.9
13.1
110.1 110.1
90.0 69.9 49.8
101.6
13.0
110.1 110.1
90.0 69.9 49.8
102.3
13.1

90
60.3
78.4
94.3
87.2
87.8
73.6
87.9
100.4
92.8
93.5
86.9
97.5
106.5
98.5
99.2
106.1
108.2
100.0
100.7
114.7
109.9
101.6
102.3

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
47.2
34.1
65.3
52.2
39.1
83.4
70.3
57.2 44.1
87.2
85.1
72.0 59.0
87.8
77.8
64.7 51.7
53.0
38.1
73.1
58.2
43.4
93.2
78.3
63.5 48.6
92.8
92.8
80.4 65.2
93.5
86.9
72.4 57.2
58.7
42.1
80.8
64.2
47.6
103.0
86.3
69.7 53.1
98.5
98.5
88.7 71.4
99.2
95.9
80.1 62.7
87.5
68.9
50.3
108.2
92.6
74.0 55.4
100.0 100.0
84.9 65.9
100.7
99.1
80.9 61.9
94.1
73.6
53.0
109.9
98.9
78.4 57.8
101.6 101.6
81.0 60.4
102.3 102.3
81.7 61.2

65
45.9
38.6
50.3
42.3
54.8
46.0
47.3
43.3
39.9
40.6

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

21

505428-YTG-R-1114

YD120/ND120
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

3000

3500

4000

4500

5000

22

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

138.1
130.1
122.0
112.3
108.2
147.1
138.4
129.8
119.5
115.1
156.0
146.8
137.7
126.8
122.1
152.4
142.9
131.5
126.7
157.9
148.1
136.3
131.3

7.5
7.4
7.2
7.2
7.1
7.5
7.4
7.3
7.2
7.2
7.6
7.4
7.3
7.2
7.2
7.5
7.3
7.2
7.2
7.5
7.4
7.3
7.3

63.6
82.9
102.2
112.3
108.2
70.5
91.8
113.1
119.5
115.1
77.5
100.8
124.1
126.8
122.1
108.1
136.1
131.5
126.7
115.3
148.1
136.3
131.3

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

127.4
118.7
109.9
100.4
103.2
135.6
126.3
116.9
106.8
109.9
143.8
133.9
124.0
113.3
116.5
139.2
128.9
117.7
121.1
144.5
133.8
122.2
125.7

9.6
9.5
9.3
9.2
9.2
9.6
9.5
9.3
9.2
9.2
9.6
9.5
9.3
9.2
9.2
9.5
9.3
9.2
9.2
9.5
9.3
9.2
9.2

62.2
80.6
99.0
100.4
103.2
69.7
90.2
110.6
106.8
109.9
77.3
99.8
122.3
113.3
116.5
107.4
128.0
117.7
121.1
115.0
133.8
122.2
125.7

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
51.7
39.9
132.8
8.6
71.0
59.2
47.4
124.4
8.4
90.4
78.5
66.7 54.8
115.9
8.3
108.5
94.8
83.0 71.1 59.3
106.3
8.2
108.6
99.9
88.0 76.2 64.3
105.7
8.2
57.3
44.0
141.3
8.6
78.6
65.3
52.0
132.4
8.4
99.9
86.6
73.3 60.0
123.4
8.3
117.6 104.6
91.9 78.0 64.7
113.2
8.2
115.4 110.1
97.8 83.6 70.3
112.5
8.2
62.8
48.1
149.9
8.6
86.1
71.4
56.7
140.4
8.4
109.4
94.6
79.9 65.2
130.9
8.3
126.8 114.3 100.8 84.9 70.2
120.0
8.2
122.1 120.4 107.5 91.0 76.3
119.3
8.2
92.0
76.0
60.0
145.8
8.5
116.8 100.8
84.8 68.8
135.9
8.3
131.5 123.1 107.7 91.1 75.1
124.6
8.2
126.7 125.9 110.8 93.9 77.8
123.9
8.2
98.0
80.7
63.4
151.2
8.5
124.3 107.0
89.7 72.4
141.0
8.3
136.3 132.0 114.6 97.3 80.0
129.3
8.3
131.3 131.3 114.0 96.7 79.4
128.5
8.2
95°F
49.8
37.4
122.1
10.8
68.2
55.9
43.5
112.7
10.7
86.6
74.3
61.9 49.5
103.2
10.6
100.4
89.8
77.5 65.1 52.7
95.0
10.5
102.8
90.4
78.0 65.7 53.3
98.1
10.5
55.6
41.6
129.2
10.8
76.1
62.0
47.9
119.2
10.7
96.6
82.5
68.4 54.3
109.2
10.6
106.8
99.7
85.0 71.5 57.4
100.5
10.5
109.6 100.4
85.4 72.2 58.1
103.8
10.5
61.5
45.7
136.2
10.8
84.0
68.2
52.3
125.7
10.7
106.5
90.6
74.8 59.0
115.1
10.6
113.3 109.6
92.6 78.0 62.2
106.0
10.5
116.5 110.3
92.7 78.7 62.9
109.4
10.5
90.2
72.9
55.7
131.0
10.7
114.2
97.0
79.7 62.5
120.1
10.6
117.7 115.9
98.1 81.4 64.2
110.5
10.5
121.1 118.0
99.9 83.5 66.3
114.1
10.5
96.3
77.7
59.0
136.4
10.7
121.9 103.3
84.6 66.0
125.0
10.6
122.2 122.2 103.5 84.9 66.2
115.0
10.5
125.7 125.7 107.0 88.4 69.7
118.7
10.5

90
62.9
81.7
100.6
106.3
105.7
70.1
91.0
111.9
113.2
112.5
77.4
100.3
123.2
120.0
119.3
107.7
132.1
124.6
123.9
115.2
141.0
129.3
128.5
60.4
78.3
96.1
95.0
98.1
70.6
87.9
105.2
100.5
103.8
80.8
97.5
114.3
106.0
109.4
105.2
119.6
110.5
114.1
112.9
125.0
115.0
118.7

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
50.8
38.7
69.6
57.5
45.4
88.5
76.4
64.3 52.2
104.4
92.3
80.2 68.1
105.7
95.1
83.0 70.9
56.5
42.8
77.3
63.6
50.0
98.2
84.5
70.8 57.1
112.2 102.1
88.5 74.8
112.5 105.3
91.6 77.9
62.1
46.9
85.0
69.8
54.5
107.9
92.6
77.4 62.1
120.0 112.0
96.7 81.4
119.3 115.4 100.1 84.9
91.1
74.5
57.9
115.5
98.9
82.3 65.7
124.6 119.5 102.9 86.3
123.9 121.9 105.3 88.7
97.2
79.2
61.2
123.1 105.1
87.2 69.2
129.3 127.1 109.1 91.1
128.5 128.5 110.5 92.5
105°F
48.0
35.6
65.8
53.4
41.0
83.7
71.2
58.8 46.4
95.0
86.6
74.1 61.7
97.9
85.4
73.0 60.5
53.8
39.6
73.7
59.5
45.3
93.6
79.4
65.2 51.0
100.5
96.5
82.0 68.1
103.6
95.2
80.5 66.8
59.7
43.7
81.6
65.6
49.6
103.5
87.5
71.6 55.6
106.0 106.4
89.8 74.4
109.4 104.9
88.1 73.0
87.7
70.3
52.8
111.2
93.7
76.3 58.8
110.5 110.7
92.9 75.8
114.1 111.8
93.9 76.9
93.9
74.9
56.0
118.9
99.9
81.0 62.0
115.0 115.0
96.1 77.1
118.7 118.7
99.8 80.8

65
56.0
58.8
61.1
64.2
66.2
69.6
69.7
72.1
73.1
74.6
49.3
48.1
53.9
52.6
58.5
57.1
58.3
59.4
58.1
61.8

Johnson Controls Unitary Products

505428-YTG-R-1114

YD120/ND120 (Continued)
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

116.8
106.7
96.6
89.7
93.0
122.7
112.1
101.4
94.2
97.7
128.6
117.4
106.3
98.8
102.3
122.9
111.2
103.3
107.1
128.3
116.1
107.9
111.8

12.1
11.9
11.8
11.7
11.7
12.1
11.9
11.8
11.7
11.7
12.1
11.9
11.8
11.7
11.7
12.0
11.8
11.7
11.7
12.0
11.9
11.7
11.8

58.7
75.9
93.2
89.7
93.0
71.5
85.6
99.7
94.2
97.7
84.3
95.3
106.3
98.8
102.3
103.0
111.2
103.3
107.1
110.8
116.1
107.9
111.8

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
46.2
33.7
111.5
13.3
63.4
50.9
38.4
100.7
13.2
80.7
68.2
55.7 43.2
89.9
13.1
89.7
83.3
70.8 58.3 45.8
84.4
12.9
92.9
80.4
67.9 55.4 42.9
87.9
12.9
52.0
37.7
116.2
13.3
71.3
57.0
42.7
105.0
13.2
90.6
76.3
62.0 47.7
93.7
13.1
94.2
93.2
78.9 64.6 50.3
88.0
12.9
97.6
90.0
75.7 61.4 47.1
91.5
13.0
57.8
41.7
120.9
13.3
79.2
63.1
46.9
109.2
13.2
100.5
84.4
68.3 52.2
97.4
13.1
98.8
103.1
87.0 70.9 54.8
91.5
12.9
102.3
99.6
83.5 67.3 51.2
95.2
13.0
85.3
67.6
49.9
114.7
13.2
108.2
90.5
72.8 55.1
102.4
13.1
103.3 105.5
87.8 70.1 52.4
96.1
12.9
107.1 105.7
88.0 70.3 52.6
100.0
13.0
91.5
72.2
52.9
120.2
13.3
115.9
96.6
77.3 58.0
107.3
13.2
107.9 107.9
88.6 69.3 50.0
100.7
13.0
111.8 111.8
92.5 73.2 53.9
104.8
13.0

90
57.0
73.6
89.9
84.4
87.9
72.4
83.3
93.7
88.0
91.5
87.7
93.0
97.4
91.5
95.2
100.8
102.4
96.1
100.0
108.7
107.3
100.7
104.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
44.4
31.8
61.1
48.5
35.9
77.7
65.1
52.6 40.0
84.4
80.0
67.5 54.9
87.9
75.5
62.9 50.3
50.2
35.8
68.9
54.5
40.1
87.6
73.2
58.8 44.4
88.0
88.0
75.8 61.1
91.5
84.8
70.9 56.0
56.0
39.7
76.8
60.5
44.2
97.4
81.3
65.0 48.8
91.5
91.5
84.2 67.3
95.2
94.2
78.8 61.7
82.9
65.0
47.0
102.4
87.3
69.3 51.4
96.1
96.1
82.6 64.4
100.0
99.5
82.0 63.6
89.0
69.4
49.8
107.3
93.3
73.7 54.1
100.7 100.7
81.1 61.5
104.8 104.8
85.2 65.6

65
42.3
37.8
46.7
41.6
51.1
45.4
46.5
45.7
41.9
46.0

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

23

505428-YTG-R-1114

YC150/NC180
Air on
Evaporator Coil
CFM

3750

4375

5000

5625

6250

3750

4375

5000

5625

6250

24

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

178.5
168.2
157.9
144.8
149.7
184.7
174.0
163.4
149.9
154.9
190.9
179.9
168.8
154.9
160.1
182.3
171.1
157.0
162.2
184.7
173.4
159.0
164.4

10.2
9.9
9.6
9.4
9.5
10.2
9.9
9.6
9.4
9.5
10.3
9.9
9.6
9.4
9.6
10.1
9.8
9.6
9.7
10.2
9.9
9.7
9.8

87.6
111.9
136.1
144.8
149.7
94.2
121.8
149.5
149.9
154.9
100.7
131.8
162.9
154.9
160.1
142.7
168.1
157.0
162.2
153.7
173.4
159.0
164.4

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

166.0
154.1
142.3
132.9
138.2
170.5
158.3
146.1
136.5
142.0
175.0
162.5
150.0
140.1
145.7
165.9
153.1
143.1
148.7
169.3
156.3
146.0
151.8

12.3
12.1
11.9
11.7
11.8
12.3
12.1
11.9
11.7
11.8
12.3
12.1
11.9
11.7
11.8
12.2
12.0
11.8
11.9
12.3
12.1
11.9
12.0

80.3
104.7
129.0
132.9
138.2
90.6
115.0
139.5
136.5
142.0
100.8
125.4
150.0
140.1
145.7
135.3
153.1
143.1
148.7
145.2
156.3
146.0
151.8

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
71.1
54.7
172.2
11.3
95.4
78.9
62.4
161.2
11.0
119.6 103.1 86.7
70.2
150.1
10.7
144.8 129.3 112.8 96.3 79.8
138.9
10.6
149.7 137.7 121.2 104.7 88.3
143.9
10.7
77.2
58.5
177.6
11.3
103.1 84.4
65.7
166.2
11.0
129.0 110.3 91.6
72.9
154.7
10.8
149.9 138.2 119.8 100.8 82.1
143.2
10.6
154.9 147.3 129.1 109.8 91.1
148.4
10.7
83.2
62.3
182.9
11.3
110.8 89.9
68.9
171.2
11.0
138.4 117.5 96.5
75.5
159.4
10.8
154.9 147.2 126.8 105.3 84.3
147.5
10.6
160.1 156.9 137.0 114.9 94.0
152.9
10.7
119.7 96.7
73.7
174.1
11.2
149.4 126.4 103.4 80.4
162.1
10.9
157.0 153.1 130.4 107.1 84.1
150.0
10.7
162.2 160.6 138.1 114.6 91.6
155.5
10.8
128.6 103.6 78.5
177.0
11.3
160.4 135.4 110.4 85.3
164.8
11.0
159.0 159.0 134.0 108.9 83.9
152.5
10.8
164.4 164.4 139.3 114.3 89.2
158.1
10.9
95°F
64.1
47.8
159.9
14.1
88.4
72.2
55.9
148.2
13.8
112.7 96.5
80.2
64.0
136.4
13.5
132.9 123.6 107.4 91.1 74.9
130.6
13.4
138.2 123.6 107.3 91.1 74.8
134.7
13.5
70.2
51.6
163.0
14.0
96.4
77.8
59.1
151.0
13.7
122.6 104.0 85.3
66.7
139.1
13.5
136.5 133.2 114.3 95.9 77.3
133.1
13.4
142.0 133.2 114.0 95.9 77.3
137.3
13.5
76.3
55.3
166.1
13.9
104.4 83.4
62.3
153.9
13.7
132.5 111.5 90.4
69.4
141.7
13.4
140.1 142.8 121.2 100.7 79.7
135.6
13.3
145.7 142.8 120.7 100.7 79.7
140.0
13.4
112.4 89.5
66.7
157.7
13.8
142.6 119.7 96.8
73.9
145.2
13.5
143.1 144.4 121.2 98.6 75.7
138.9
13.4
148.7 147.3 123.9 101.5 78.6
143.4
13.5
120.5 95.7
71.0
161.4
14.0
152.7 128.0 103.2 78.5
148.6
13.7
146.0 146.0 121.3 96.5 71.8
142.2
13.6
151.8 151.8 127.0 102.3 77.6
146.8
13.7

90
84.0
108.3
132.5
138.9
143.9
92.4
118.4
144.5
143.2
148.4
100.8
128.6
156.5
147.5
152.9
139.0
160.6
150.0
155.5
149.4
164.8
152.5
158.1
79.0
102.8
126.7
130.6
134.7
91.5
112.8
134.2
133.1
137.3
104.0
122.9
141.7
135.6
140.0
133.0
145.2
138.9
143.4
143.0
148.6
142.2
146.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
67.6
51.2
91.9
75.5
59.2
116.2 99.8
83.4
67.1
138.9 126.4 110.1 93.7
143.9 130.6 114.3 97.9
73.7
55.0
99.8
81.1
62.4
125.8 107.1 88.4
69.8
143.2 135.7 117.0 98.4
148.4 140.2 121.6 102.9
79.8
58.8
107.6 86.6
65.6
135.5 114.5 93.5
72.5
147.5 145.0 124.0 103.0
152.9 149.8 128.8 107.8
116.1 93.1
70.2
146.0 123.1 100.1 77.2
150.0 148.8 125.8 102.9
155.5 153.9 131.0 108.1
124.5 99.7
74.8
156.6 131.7 106.8 81.9
152.5 152.5 127.6 102.7
158.1 158.1 133.2 108.3
105°F
62.8
46.6
86.6
70.4
54.2
110.5 94.2
78.0
61.8
130.6 122.0 105.8 89.6
134.7 119.4 103.2 87.0
68.6
50.0
94.2
75.6
56.9
119.8 101.2 82.5
63.9
133.1 130.9 112.1 93.6
137.3 128.1 109.2 90.9
74.4
53.4
101.8 80.7
59.6
129.1 108.1 87.0
65.9
135.6 139.8 118.5 97.7
140.0 136.9 115.3 94.8
110.0 87.1
64.2
138.0 116.6 93.7
70.8
138.9 141.0 118.0 95.2
143.4 141.8 118.6 96.0
118.3 93.5
68.7
146.9 125.2 100.4 75.6
142.2 142.2 117.5 92.7
146.8 146.8 122.0 97.2

65
77.3
81.5
79.7
84.2
82.0
86.8
79.9
85.1
77.8
83.4
73.4
70.8
75.0
72.2
76.6
73.7
72.3
73.1
67.9
72.5

Johnson Controls Unitary Products

505428-YTG-R-1114

YC150/NC180 (Continued)
Air on
Evaporator Coil
CFM

3750

4375

5000

5625

6250

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

153.8
142.2
130.5
128.2
131.2
155.5
143.8
132.0
129.7
132.7
157.3
145.4
133.5
131.1
134.2
149.5
137.3
134.8
138.0
153.6
141.0
138.5
141.8

15.8
15.5
15.1
15.1
15.2
15.7
15.3
15.0
15.0
15.1
15.5
15.2
14.9
14.9
15.0
15.4
15.1
15.1
15.2
15.6
15.3
15.3
15.4

77.6
101.0
124.4
128.2
131.2
92.3
110.6
128.9
129.7
132.7
107.1
120.3
133.5
131.1
134.2
130.6
137.3
134.8
138.0
140.9
141.0
138.5
141.8

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
61.4
45.3
147.7
17.5
84.8
68.7
52.5
136.2
17.2
108.2 92.0
75.9
59.7
124.7
16.8
128.2 120.4 104.2 88.0 71.9
125.8
16.8
131.2 115.2 99.0
82.8 66.7
127.8
17.0
67.0
48.4
148.1
17.3
92.0
73.4
54.7
136.5
17.0
117.0 98.3
79.7
61.1
125.0
16.6
129.7 128.6 110.0 91.3 72.7
126.2
16.7
132.7 123.1 104.4 85.8 67.2
128.1
16.8
72.6
51.5
148.4
17.1
99.2
78.1
57.0
136.8
16.8
125.8 104.7 83.6
62.5
125.2
16.4
131.1 136.9 115.8 94.7 73.6
126.6
16.5
134.2 131.0 109.9 88.8 67.7
128.5
16.6
107.6 84.7
61.7
141.3
17.0
133.4 113.5 90.6
67.6
129.3
16.6
134.8 137.7 114.7 91.8 68.8
130.7
16.7
138.0 136.4 113.4 90.5 67.5
132.6
16.8
116.1 91.3
66.5
145.7
17.2
141.0 122.4 97.6
72.8
133.4
16.8
138.5 138.5 113.7 88.9 64.1
134.7
16.9
141.8 141.8 117.0 92.2 67.4
136.7
17.1

90
76.3
99.2
122.1
125.8
127.8
93.2
108.4
123.7
126.2
128.1
110.2
117.7
125.2
126.6
128.5
128.2
129.3
130.7
132.6
138.7
133.4
134.7
136.7

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
60.1
44.0
83.0
66.9
50.8
105.9 89.8
73.7
57.6
125.8 118.7 102.6 86.5
127.8 111.0 94.9
78.7
65.4
46.8
89.8
71.2
52.5
114.2 95.5
76.9
58.3
126.2 126.2 107.8 89.1
128.1 118.0 99.7
80.8
70.7
49.6
96.6
75.4
54.3
122.4 101.3 80.1
59.0
126.6 126.6 113.1 91.6
128.5 125.1 104.5 82.8
105.2 82.3
59.3
128.8 110.4 87.5
64.5
130.7 130.7 111.5 88.4
132.6 130.9 108.2 84.9
113.9 89.1
64.3
133.4 119.6 94.8
69.9
134.7 134.7 109.9 85.1
136.7 136.7 111.9 87.1

65
70.4
62.6
70.4
62.1
70.5
61.7
65.4
62.0
60.2
62.3

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

25

505428-YTG-R-1114

YD150/ND180
Air on
Evaporator Coil
CFM

3750

4375

5000

5625

6250

3750

4375

5000

5625

6250

26

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

170.2
164.1
157.9
142.4
141.3
182.4
175.5
168.7
152.3
151.2
194.5
187.0
179.5
162.2
161.1
187.6
180.3
162.8
161.6
188.2
181.0
163.3
162.1

10.0
9.7
9.5
9.3
9.3
10.0
9.7
9.5
9.4
9.3
10.0
9.8
9.5
9.4
9.4
9.8
9.6
9.5
9.4
9.9
9.7
9.5
9.5

80.1
106.1
132.0
142.4
141.3
89.5
119.7
149.8
152.3
151.2
98.9
133.3
167.6
162.2
161.1
141.9
174.3
162.8
161.6
150.6
181.0
163.3
162.1

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

177.3
159.8
142.3
136.2
138.7
182.1
164.1
146.2
139.8
142.5
186.8
168.4
150.0
143.5
146.2
173.8
154.8
148.1
150.9
179.2
159.6
152.7
155.6

12.0
11.9
11.8
11.5
11.5
12.1
12.0
11.9
11.6
11.6
12.2
12.1
12.0
11.7
11.7
12.1
12.0
11.7
11.7
12.1
12.0
11.7
11.7

82.9
105.3
127.7
136.2
138.7
92.8
115.8
138.8
139.8
142.5
102.7
126.4
150.0
143.5
146.2
139.0
154.8
148.1
150.9
151.7
159.6
152.7
155.6

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
64.2
48.3
173.7
11.0
90.2
74.3
58.4
161.9
10.8
116.1 100.2 84.3
68.5
150.1
10.6
140.8 122.7 106.8 90.9 75.1
139.3
10.4
141.3 129.9 114.0 98.1 82.2
140.0
10.4
72.3
53.8
182.2
11.1
101.2 82.7
64.2
169.8
10.9
130.0 111.5 93.0
74.5
157.4
10.7
151.5 136.6 118.9 99.7 81.2
146.1
10.5
151.2 144.6 126.8 107.6 89.1
146.8
10.5
80.4
59.3
190.7
11.1
112.2 91.1
70.0
177.7
10.9
143.9 122.8 101.7 80.6
164.8
10.7
162.2 150.6 131.0 108.4 87.3
152.9
10.5
161.1 159.2 139.6 117.0 95.9
153.7
10.5
119.6 97.2
74.8
180.7
11.0
153.5 131.1 108.7 86.4
167.5
10.8
162.8 156.9 135.3 112.2 89.8
155.4
10.6
161.6 160.7 139.0 115.9 93.5
156.3
10.6
126.9 103.3 79.6
183.7
11.0
163.0 139.4 115.7 92.1
170.3
10.8
163.3 163.3 139.7 116.0 92.3
158.0
10.6
162.1 162.1 138.5 114.8 91.1
158.8
10.6
95°F
66.6
50.4
162.9
13.7
89.0
72.8
56.6
149.2
13.5
111.4 95.2
79.0
62.7
135.4
13.3
136.2 122.1 105.9 89.7 73.4
128.0
13.0
138.7 124.1 107.9 91.7 75.5
131.1
13.1
73.1
54.7
168.7
13.7
97.4
79.0
60.6
154.5
13.5
121.7 103.3 84.9
66.5
140.3
13.4
139.8 132.5 113.4 95.7 77.3
132.6
13.1
142.5 134.7 115.6 97.9 79.5
135.8
13.2
79.6
59.0
174.5
13.8
105.8 85.2
64.7
159.9
13.6
132.0 111.5 90.9
70.3
145.2
13.4
143.5 142.9 120.8 101.8 81.2
137.2
13.1
146.2 145.3 123.3 104.2 83.6
140.5
13.2
116.3 93.5
70.7
164.1
13.6
145.1 122.3 99.5
76.7
149.0
13.5
148.1 147.8 124.3 102.3 79.5
140.7
13.2
150.9 150.4 126.9 104.9 82.1
144.2
13.2
126.8 101.8 76.8
168.3
13.7
158.1 133.1 108.1 83.2
152.8
13.5
152.7 152.7 127.7 102.8 77.8
144.3
13.2
155.6 155.6 130.6 105.6 80.6
147.8
13.3

90
81.5
105.7
129.8
139.3
140.0
91.1
117.7
144.3
146.1
146.8
100.8
129.8
158.8
152.9
153.7
140.5
164.6
155.4
156.3
151.2
170.3
158.0
158.8
78.3
101.4
124.6
128.0
131.1
90.6
112.8
134.9
132.6
135.8
103.0
124.1
145.2
137.2
140.5
136.3
149.0
140.7
144.2
148.5
152.8
144.3
147.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
65.4
49.3
89.6
73.5
57.5
113.8 97.7
81.7
65.6
138.5 122.4 106.4 90.3
140.0 127.0 111.0 94.9
72.7
54.3
99.3
80.8
62.4
125.9 107.4 89.0
70.5
145.7 134.6 116.1 97.7
146.8 139.7 121.2 102.8
80.0
59.2
109.0 88.2
67.3
138.0 117.1 96.3
75.5
152.9 146.8 125.9 105.1
153.7 152.3 131.4 110.6
117.9 95.3
72.8
149.3 126.7 104.1 81.5
155.4 152.4 129.8 107.2
156.3 155.6 133.0 110.4
126.8 102.5 78.2
160.6 136.2 111.9 87.6
158.0 158.0 133.7 109.4
158.8 158.8 134.5 110.2
105°F
62.1
45.9
85.2
69.0
52.8
108.4 92.2
76.0
59.7
128.0 118.2 102.0 85.7
131.1 116.6 100.4 84.2
68.8
50.3
94.2
75.6
57.1
119.6 101.0 82.4
63.9
132.6 129.5 110.6 92.4
135.8 127.7 108.8 90.6
75.6
54.7
103.2 82.3
61.3
130.8 109.9 88.9
68.0
137.2 140.9 119.2 99.0
140.5 138.9 117.2 97.1
113.3 90.3
67.2
141.4 120.5 97.5
74.5
140.7 142.6 119.2 96.6
144.2 143.4 120.0 97.3
123.4 98.3
73.1
152.0 131.2 106.1 81.0
144.3 144.3 119.2 94.1
147.8 147.8 122.7 97.6

65
74.2
78.8
79.2
84.3
84.3
89.8
84.7
87.8
85.1
85.9
69.5
68.0
73.8
72.1
78.1
76.2
73.5
74.3
69.0
72.5

Johnson Controls Unitary Products

505428-YTG-R-1114

YD150/ND180 (Continued)
Air on
Evaporator Coil
CFM

3750

4375

5000

5625

6250

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

148.6
138.6
128.6
119.7
123.4
155.4
145.0
134.5
125.3
129.1
162.3
151.3
140.4
130.8
134.8
154.3
143.2
133.4
137.4
157.3
146.0
136.0
140.1

15.3
15.1
14.8
14.5
14.7
15.4
15.1
14.8
14.5
14.7
15.4
15.1
14.8
14.5
14.7
15.2
14.9
14.6
14.8
15.3
15.0
14.7
14.9

73.8
97.6
121.5
119.7
123.4
88.5
109.7
130.9
125.3
129.1
103.2
121.8
140.4
130.8
134.8
133.5
143.2
133.4
137.4
145.3
146.0
136.0
140.1

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
57.6
41.4
134.2
17.0
81.4
65.3
49.1
128.0
16.7
105.3 89.1
72.9
56.7
121.7
16.3
119.7 114.2 98.0
81.8 65.7
111.5
16.0
123.4 109.0 92.8
76.7 60.5
115.7
16.3
64.6
45.9
142.1
17.0
91.0
72.3
53.6
135.4
16.6
117.4 98.7
80.0
61.2
128.7
16.3
125.3 126.5 107.8 89.0 70.3
118.0
16.0
129.1 120.7 102.0 83.3 64.6
122.4
16.3
71.6
50.3
150.0
16.9
100.6 79.3
58.0
142.8
16.6
129.5 108.3 87.0
65.7
135.6
16.3
130.8 138.8 117.5 96.2 75.0
124.4
16.0
134.8 132.5 111.2 90.0 68.7
129.0
16.2
110.3 87.0
63.8
144.6
16.7
137.8 118.8 95.5
72.3
137.4
16.4
133.4 137.4 114.1 90.8 67.6
126.0
16.1
137.4 136.3 113.0 89.8 66.5
130.7
16.3
120.0 94.7
69.5
146.4
16.8
146.0 129.3 104.1 78.8
139.2
16.5
136.0 136.0 110.7 85.4 60.2
127.6
16.2
140.1 140.1 114.8 89.6 64.3
132.4
16.5

90
69.2
93.8
118.3
111.5
115.7
86.4
106.7
127.0
118.0
122.4
103.5
119.6
135.6
124.4
129.0
130.8
137.4
126.0
130.7
142.0
139.2
127.6
132.4

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
53.1
36.9
77.6
61.5
45.3
102.2 86.0
69.9
53.7
111.5 110.2 94.1
77.9
115.7 101.5 85.3
69.2
60.4
41.5
87.8
68.9
50.0
115.2 96.4
77.5
58.6
118.0 118.0 105.0 85.7
122.4 113.8 95.2
76.0
67.6
46.0
98.0
76.3
54.7
128.3 106.7 85.1
63.5
124.4 124.4 115.8 93.5
129.0 126.0 105.2 82.8
107.3 83.8
60.3
134.1 117.1 93.6
70.1
126.0 126.0 109.0 85.1
130.7 129.2 106.1 82.2
116.6 91.2
65.8
139.2 127.5 102.1 76.7
127.6 127.6 102.2 76.8
132.4 132.4 107.0 81.6

65
61.8
53.0
66.8
57.1
71.9
61.2
61.6
58.7
51.4
56.2

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

27

505428-YTG-R-1114

YC180/NC180
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

28

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

223.5
207.2
191.0
176.0
175.0
229.4
212.8
196.1
180.7
179.7
235.4
218.3
201.2
185.4
184.4
221.3
204.0
187.9
186.8
224.2
206.7
190.4
189.3

11.8
11.5
11.1
10.8
10.8
11.9
11.6
11.2
11.0
10.9
12.0
11.7
11.3
11.1
11.0
11.3
11.0
10.7
10.6
10.9
10.6
10.3
10.3

104.0
132.3
160.6
176.0
175.0
113.7
144.1
174.5
180.7
179.7
123.5
155.9
188.3
185.4
184.4
165.2
197.5
187.9
186.8
174.4
206.7
190.4
189.3

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

205.8
189.3
172.8
161.0
161.3
210.7
193.8
176.9
164.8
165.1
215.5
198.3
181.0
168.6
168.9
206.1
188.1
175.2
175.5
213.9
195.2
181.9
182.2

14.4
14.0
13.7
13.5
13.5
14.4
14.1
13.8
13.5
13.6
14.5
14.2
13.8
13.6
13.6
15.9
15.6
15.3
15.3
17.7
17.3
17.0
17.0

98.3
125.7
153.0
161.0
161.3
107.7
137.2
166.7
164.8
165.1
117.1
148.7
180.4
168.6
168.9
166.4
187.8
175.2
175.5
184.0
195.2
181.9
182.2

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
85.0
66.0
214.6
13.1
113.3 94.4
75.4
198.3
12.8
141.7 122.7 103.7 84.7
181.9
12.4
171.9 151.4 132.5 113.5 94.5
168.5
12.2
175.0 158.1 139.1 120.1 101.1
168.1
12.1
92.3
70.8
220.1
13.2
122.7 101.2 79.7
203.3
12.8
153.0 131.6 110.1 88.7
186.5
12.5
178.6 162.4 141.9 119.5 98.1
172.7
12.2
179.7 169.6 149.6 126.6 105.2
172.4
12.2
99.5
75.6
225.5
13.3
132.0 108.0 84.1
208.3
12.9
164.4 140.5 116.5 92.6
191.1
12.6
185.4 173.4 151.3 125.5 101.6
177.0
12.3
184.4 181.0 160.1 133.2 109.2
176.6
12.3
139.4 113.7 88.0
213.7
13.6
174.0 147.8 122.0 96.3
196.0
13.3
187.9 181.9 157.1 130.4 104.7
181.5
13.0
186.8 185.2 161.0 133.7 108.0
181.2
13.0
146.9 119.4 91.8
219.0
14.3
183.6 155.1 127.6 100.0
201.0
14.0
190.4 190.4 162.8 135.3 107.8
186.1
13.7
189.3 189.3 161.8 134.3 106.7
185.7
13.7
95°F
79.5
60.6
195.5
15.9
106.8 87.9
69.1
179.9
15.7
134.1 115.3 96.4
77.5
164.3
15.4
161.0 143.6 124.7 105.9 87.0
153.2
15.2
161.3 143.1 124.3 105.4 86.6
154.3
15.2
86.6
65.4
199.9
16.0
116.1 94.9
73.8
183.9
15.8
145.6 124.4 103.3 82.2
168.0
15.5
164.8 155.0 132.9 112.7 91.6
156.6
15.2
165.1 154.5 131.9 112.2 91.1
157.7
15.2
93.7
70.2
204.2
16.1
125.3 101.9 78.5
187.9
15.8
157.0 133.6 110.2 86.8
171.6
15.6
168.6 166.4 141.1 119.6 96.2
160.0
15.3
168.9 165.9 139.4 119.1 95.6
161.2
15.3
140.8 115.2 89.7
192.5
16.7
176.1 151.0 125.5 99.9
175.8
16.4
175.2 174.1 147.6 123.0 97.4
164.0
16.2
175.5 174.0 146.9 122.9 97.3
165.1
16.2
156.3 128.5 100.8
197.2
17.6
195.2 168.5 140.7 113.0
180.0
17.3
181.9 181.9 154.1 126.4 98.6
167.9
17.0
182.2 182.2 154.4 126.7 99.0
169.0
17.0

90
101.2
129.0
156.8
168.5
168.1
110.7
140.7
170.6
172.7
172.4
120.3
152.3
184.4
177.0
176.6
165.8
192.7
181.5
181.2
179.2
201.0
186.1
185.7
95.5
122.5
149.5
153.2
154.3
107.5
134.0
160.4
156.6
157.7
119.5
145.4
171.3
160.0
161.2
159.1
175.7
164.0
165.1
172.7
180.0
167.9
169.0

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
82.2
63.3
110.1 91.2
72.2
137.9 119.0 100.1 81.1
166.4 147.5 128.6 109.7
168.1 150.6 131.7 112.8
89.4
68.1
119.4 98.1
76.8
149.3 128.0 106.7 85.4
171.7 158.7 137.4 116.1
172.4 162.0 140.7 119.4
96.6
72.9
128.6 105.0 81.3
160.7 137.0 113.4 89.7
177.0 169.9 146.2 122.6
176.6 173.5 149.8 126.1
140.1 114.5 88.8
175.1 149.4 123.8 98.1
181.5 178.0 152.4 126.7
181.2 179.6 153.9 128.3
151.6 123.9 96.3
189.4 161.8 134.1 106.5
186.1 186.1 158.5 130.9
185.7 185.7 158.1 130.5
105°F
76.6
57.7
103.6 84.7
65.9
130.7 111.8 92.9
74.0
153.2 139.8 120.9 102.0
154.3 136.3 117.4 98.5
83.6
62.4
112.8 91.6
70.4
142.0 120.8 99.6
78.3
156.6 151.0 129.4 108.6
157.7 147.2 125.3 104.8
90.5
67.0
121.9 98.4
74.9
153.3 129.7 106.2 82.7
160.0 162.3 137.8 115.3
161.2 158.2 133.2 111.2
133.4 107.7 82.0
166.6 142.0 116.3 90.7
164.0 165.1 139.0 113.7
165.1 163.6 137.2 112.3
144.9 117.0 89.2
180.0 154.3 126.5 98.6
167.9 167.9 140.1 112.2
169.0 169.0 141.2 113.4

65
90.8
93.8
94.8
98.1
98.9
102.4
101.1
102.6
103.2
102.9
83.1
79.6
87.4
83.6
91.7
87.6
88.1
86.6
84.4
85.6

Johnson Controls Unitary Products

505428-YTG-R-1114

YC180/NC180 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

185.3
170.5
155.8
145.5
147.3
189.1
174.1
159.0
148.5
150.4
192.9
177.6
162.2
151.5
153.4
179.0
163.5
152.7
154.7
180.4
164.8
153.9
155.9

17.5
17.3
17.1
16.9
16.8
17.6
17.4
17.2
17.0
16.9
17.7
17.5
17.3
17.0
17.0
17.5
17.3
17.0
17.0
17.5
17.3
17.0
17.0

92.7
119.4
146.1
145.5
147.3
107.3
130.7
154.2
148.5
150.4
121.9
142.1
162.2
151.5
153.4
151.7
163.5
152.7
154.7
161.4
164.8
153.9
155.9

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
73.7
54.8
175.0
19.1
100.5 81.5
62.6
161.1
18.9
127.2 108.3 89.3
70.4
147.2
18.8
145.5 136.0 117.1 98.2
79.3
137.7
18.6
147.3 129.4 110.5 91.6
72.7
140.3
18.5
80.6
59.3
178.3
19.2
109.5 88.2
66.9
164.2
19.1
138.3 117.1 95.8
74.5
150.1
18.9
148.5 147.1 125.8 104.5 83.3
140.3
18.7
150.4 140.0 118.7 97.4
76.2
143.0
18.6
87.4
63.8
181.6
19.3
118.5 94.8
71.2
167.3
19.2
149.5 125.9 102.3 78.6
152.9
19.0
151.5 158.2 134.5 110.9 87.3
142.9
18.8
153.4 150.5 126.9 103.3 79.6
145.7
18.7
126.0 100.2 74.4
165.5
18.3
157.2 133.0 107.2 81.5
151.3
18.2
152.7 156.0 130.3 104.5 78.7
141.4
17.9
154.7 153.2 127.4 101.7 75.9
144.2
17.9
133.5 105.5 77.6
163.7
17.4
164.8 140.1 112.2 84.3
149.7
17.3
153.9 153.9 126.0 98.1
70.2
140.0
17.1
155.9 155.9 128.0 100.1 72.1
142.7
17.0

90
89.8
116.2
142.6
137.7
140.3
107.1
127.5
147.9
140.3
143.0
124.4
138.8
152.9
142.9
145.7
144.4
151.3
141.4
144.2
150.1
149.7
140.0
142.7

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
70.9
51.9
97.3
78.4
59.4
123.7 104.8 85.8
66.9
137.7 132.2 113.3 94.3
140.3 122.6 103.6 84.7
77.6
56.2
106.2 84.8
63.5
134.7 113.4 92.1
70.7
140.3 140.3 122.2 100.4
143.0 132.7 112.1 90.0
84.3
60.5
115.0 91.3
67.6
145.8 122.1 98.3
74.6
142.9 142.9 131.2 106.6
145.7 142.8 120.6 95.4
118.5 92.7
66.8
147.7 124.0 98.1
72.3
141.4 141.4 121.6 95.3
144.2 142.8 117.7 91.0
122.1 94.1
66.0
149.7 125.9 97.9
69.9
140.0 140.0 112.0 83.9
142.7 142.7 114.7 86.7

65
75.4
65.8
79.1
68.7
82.8
71.6
69.4
65.2
55.9
58.7

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

29

505428-YTG-R-1114

YC180/NC240
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

30

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

214.3
201.7
189.0
181.2
177.1
220.7
207.6
194.6
186.5
182.3
227.1
213.6
200.2
191.9
187.6
218.3
204.5
196.0
191.6
223.0
208.9
200.2
195.7

12.1
11.8
11.6
11.3
11.3
12.2
11.9
11.7
11.4
11.4
12.3
12.0
11.8
11.5
11.5
12.1
11.9
11.6
11.6
12.2
11.9
11.7
11.6

111.5
138.5
165.4
181.2
177.1
121.6
150.4
179.1
186.5
182.3
131.7
162.3
192.8
191.9
187.6
172.7
200.9
196.0
191.6
183.1
208.9
200.2
195.7

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

212.3
196.3
180.3
162.6
163.6
218.0
201.6
185.2
167.0
167.9
223.7
206.8
190.0
171.4
172.3
209.6
192.6
173.7
174.7
212.4
195.1
176.0
177.0

14.6
14.2
13.9
13.6
13.6
14.6
14.3
14.0
13.7
13.7
14.7
14.4
14.1
13.8
13.8
14.5
14.2
13.9
13.9
14.5
14.2
13.9
13.9

109.7
135.5
161.2
162.6
163.6
119.7
147.2
174.6
167.0
167.9
129.7
158.9
188.1
171.4
172.3
168.9
191.6
173.7
174.7
178.8
195.1
176.0
177.0

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
92.2
72.8
213.3
13.3
119.1 99.8
80.4
199.0
13.0
146.1 126.7 107.3 88.0
184.6
12.7
177.5 156.5 137.1 117.7 98.4
171.9
12.5
177.1 160.6 141.3 121.9 102.5
170.3
12.5
99.7
77.7
219.3
13.4
128.4 106.4 84.5
204.6
13.1
157.2 135.2 113.2 91.2
189.9
12.8
184.7 167.0 145.2 123.0 101.0
176.8
12.6
182.3 171.4 150.0 127.4 105.5
175.1
12.6
107.1 82.6
225.4
13.5
137.7 113.1 88.5
210.2
13.2
168.2 143.7 119.1 94.5
195.1
12.9
191.9 177.4 153.3 128.3 103.7
181.6
12.7
187.6 182.1 158.8 133.0 108.4
179.9
12.7
145.8 118.9 92.0
214.0
13.3
177.9 151.0 124.1 97.2
198.6
13.0
196.0 188.7 162.0 134.9 108.0
184.9
12.7
191.6 188.9 162.6 135.1 108.2
183.1
12.7
153.9 124.7 95.5
217.7
13.4
187.5 158.3 129.2 100.0
202.0
13.1
200.2 199.9 170.7 141.5 112.3
188.1
12.8
195.7 195.7 166.5 137.3 108.1
186.3
12.8
95°F
90.4
71.0
207.7
16.7
116.1 96.8
77.4
191.8
16.2
141.8 122.5 103.1 83.8
175.9
15.8
162.6 144.9 125.5 106.2 86.8
158.2
15.4
163.6 147.1 127.7 108.4 89.0
160.7
15.4
97.8
75.8
213.3
16.8
125.2 103.3 81.3
197.0
16.3
152.7 130.7 108.8 86.8
180.7
15.9
167.0 154.6 132.5 110.7 88.8
162.4
15.5
167.9 157.0 134.4 113.1 91.1
165.0
15.5
105.1 80.6
218.9
16.9
134.3 109.8 85.3
202.1
16.4
163.5 139.0 114.5 89.9
185.4
16.0
171.4 164.4 139.4 115.3 90.8
166.7
15.6
172.3 166.9 141.1 117.8 93.3
169.3
15.6
142.0 115.1 88.3
205.1
16.5
172.6 145.7 118.9 92.0
188.1
16.0
173.7 170.2 143.1 116.5 89.6
169.1
15.6
174.7 172.0 144.5 118.2 91.4
171.8
15.6
149.6 120.4 91.3
208.0
16.5
181.7 152.5 123.3 94.1
190.8
16.1
176.0 176.0 146.8 117.6 88.4
171.5
15.7
177.0 177.0 147.8 118.6 89.5
174.2
15.6

90
110.6
137.0
163.3
171.9
170.3
120.7
148.8
176.9
176.8
175.1
130.7
160.6
190.5
181.6
179.9
170.8
196.2
184.9
183.1
180.9
202.0
188.1
186.3
107.9
133.6
159.2
158.2
160.7
118.7
145.3
171.8
162.4
165.0
129.6
157.0
184.4
166.7
169.3
167.0
187.6
169.1
171.8
176.9
190.8
171.5
174.2

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
91.3
71.9
117.6 98.3
78.9
144.0 124.6 105.2 85.9
170.0 150.7 131.3 112.0
170.3 153.8 134.5 115.1
98.7
76.7
126.8 104.9 82.9
154.9 133.0 111.0 89.0
175.8 160.8 138.8 116.9
175.1 164.2 142.2 120.3
106.1 81.6
136.0 111.5 86.9
165.9 141.3 116.8 92.2
181.6 170.9 146.4 121.8
179.9 174.5 150.0 125.4
143.9 117.0 90.1
175.2 148.4 121.5 94.6
184.9 179.4 152.6 125.7
183.1 180.4 153.6 126.7
151.7 122.6 93.4
184.6 155.4 126.2 97.0
188.1 187.9 158.8 129.6
186.3 186.3 157.1 128.0
105°F
88.6
69.2
114.2 94.9
75.5
139.9 120.5 101.2 81.9
158.2 141.1 121.7 102.4
160.7 144.1 124.7 105.4
95.9
74.0
123.3 101.4 79.4
150.8 128.8 106.9 84.9
162.4 150.8 128.7 106.9
165.0 154.0 131.7 110.1
103.3 78.7
132.5 107.9 83.4
161.6 137.1 112.6 88.0
166.7 160.4 135.7 111.4
169.3 163.8 138.7 114.8
140.1 113.2 86.4
170.7 143.9 117.0 90.2
169.1 166.0 139.0 112.2
171.8 169.0 141.9 115.3
147.8 118.6 89.4
179.8 150.7 121.5 92.3
171.5 171.5 142.3 113.1
174.2 174.2 145.0 115.9

65
92.6
95.8
94.9
98.3
97.2
100.8
98.8
99.8
100.4
98.8
83.0
86.0
84.9
88.1
86.8
90.2
85.4
88.5
84.0
86.7

Johnson Controls Unitary Products

505428-YTG-R-1114

YC180/NC240 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

203.2
187.4
171.6
153.7
157.8
208.6
192.4
176.2
157.8
162.0
214.1
197.4
180.8
162.0
166.3
200.5
183.6
164.5
168.8
203.6
186.4
167.0
171.4

18.8
18.3
17.7
17.2
17.1
19.0
18.4
17.8
17.3
17.2
19.1
18.5
17.9
17.4
17.3
18.5
17.9
17.4
17.3
18.5
17.9
17.4
17.3

106.1
131.7
157.3
153.7
157.8
117.7
143.4
169.0
157.8
162.0
129.4
155.1
180.8
162.0
166.3
165.1
183.6
164.5
168.8
175.0
186.4
167.0
171.4

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
86.7
67.4
198.7
21.0
112.3 93.0
73.7
182.9
20.3
137.9 118.6 99.3
79.9
167.2
19.6
153.7 137.3 117.9 98.6
79.3
149.3
19.0
157.8 141.1 121.7 102.4 83.0
154.9
18.9
94.1
72.1
204.0
21.1
121.4 99.5
77.6
187.8
20.4
148.8 126.9 105.0 83.0
171.7
19.7
157.8 146.9 124.9 103.0 81.1
153.3
19.1
162.0 150.9 129.0 107.0 85.1
159.1
19.0
101.4 76.8
209.3
21.2
130.6 106.0 81.5
192.8
20.5
159.7 135.2 110.7 86.1
176.2
19.8
162.0 156.5 131.9 107.4 82.8
157.3
19.2
166.3 160.8 136.3 111.7 87.2
163.2
19.1
138.2 111.4 84.5
195.9
20.5
168.9 142.0 115.2 88.3
179.1
19.7
164.5 161.7 134.9 108.0 81.2
159.9
19.2
168.8 166.1 139.3 112.4 85.6
165.9
19.0
145.9 116.7 87.6
199.1
20.4
178.0 148.8 119.7 90.5
182.0
19.7
167.0 167.0 137.8 108.7 79.5
162.5
19.2
171.4 171.4 142.3 113.1 83.9
168.6
19.0

90
104.2
129.8
155.3
149.3
154.9
116.8
141.5
166.2
153.3
159.1
129.3
153.2
176.2
157.3
163.2
163.2
179.1
159.9
165.9
173.1
182.0
162.5
168.6

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
84.9
65.6
110.4 91.1
71.8
136.0 116.7 97.3
78.0
149.3 133.5 114.1 94.8
154.9 138.0 118.7 99.4
92.2
70.3
119.6 97.6
75.7
146.9 125.0 103.0 81.1
153.3 143.0 121.2 99.1
159.1 147.9 126.3 104.0
99.5
74.9
128.7 104.1 79.6
157.8 133.3 108.8 84.2
157.3 152.5 128.2 103.4
163.2 157.8 133.8 108.7
136.3 109.5 82.6
167.0 140.2 113.3 86.5
159.9 157.5 130.8 103.8
165.9 163.2 136.7 109.5
144.0 114.9 85.7
176.2 147.0 117.9 88.7
162.5 162.5 133.3 104.2
168.6 168.6 139.5 110.3

65
75.5
80.1
77.2
82.1
78.9
84.1
77.0
82.7
75.0
81.2

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

31

505428-YTG-R-1114

YD180 / Two NC090
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

32

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

216.0
200.4
184.8
173.1
165.6
222.3
206.2
190.2
178.1
170.4
228.6
212.1
195.6
183.2
175.2
216.4
199.6
186.9
178.8
220.7
203.5
190.6
182.4

12.0
11.7
11.4
11.2
11.1
12.1
11.8
11.5
11.2
11.2
12.1
11.9
11.6
11.3
11.3
11.9
11.6
11.4
11.3
12.0
11.7
11.4
11.4

105.9
130.4
154.8
173.1
165.6
114.8
140.8
166.9
178.1
170.4
123.6
151.3
178.9
183.2
175.2
159.1
188.8
186.9
178.8
166.9
198.6
190.6
182.4

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

201.7
188.0
174.3
157.8
159.0
209.0
194.9
180.7
163.5
164.8
216.4
201.7
187.0
169.3
170.5
203.1
188.3
170.5
171.7
204.5
189.6
171.7
173.0

14.3
14.1
13.8
13.5
13.5
14.4
14.2
13.9
13.6
13.6
14.5
14.2
14.0
13.7
13.7
14.3
14.0
13.8
13.7
14.3
14.1
13.8
13.8

100.9
125.7
150.5
157.8
159.0
109.7
136.3
162.8
163.5
164.8
118.5
146.8
175.1
169.3
170.5
153.9
182.4
170.5
171.7
160.9
189.6
171.7
173.0

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
88.7
71.5
208.8
13.2
113.2 96.0
78.8
194.2
12.9
137.7 120.5 103.3 86.1
179.6
12.6
164.2 147.0 129.8 112.6 95.4
165.4
12.4
165.6 150.2 133.0 115.8 98.6
162.3
12.3
95.5
76.2
215.7
13.2
121.5 102.3 83.0
200.5
13.0
147.6 128.3 109.0 89.8
185.4
12.7
173.7 156.5 137.8 118.0 98.7
170.8
12.4
170.4 159.9 141.5 121.4 102.1
167.6
12.4
102.2 80.9
222.5
13.3
129.9 108.5 87.1
206.9
13.1
157.6 136.2 114.8 93.4
191.3
12.8
183.2 166.1 145.8 123.4 102.0
176.2
12.5
175.2 169.7 149.9 127.0 105.6
172.9
12.5
136.1 113.1 90.1
209.8
13.1
164.9 141.9 118.9 95.9
193.9
12.8
186.9 173.4 150.9 127.4 104.4
178.7
12.6
178.8 176.1 153.9 130.1 107.1
175.3
12.5
142.3 117.7 93.0
212.6
13.2
172.3 147.7 123.0 98.4
196.6
12.9
190.6 180.6 156.0 131.4 106.8
181.1
12.6
182.4 182.4 157.8 133.2 108.6
177.7
12.6
95°F
83.7
66.6
197.4
16.0
108.5 91.4
74.2
183.8
15.7
133.4 116.2 99.1
81.9
170.2
15.4
157.8 140.6 123.4 106.3 89.1
156.2
15.2
159.0 144.7 127.6 110.4 93.3
155.4
15.2
90.5
71.2
204.0
16.1
117.0 97.8
78.6
189.9
15.8
143.6 124.4 105.1 85.9
175.8
15.5
163.5 150.5 130.7 112.0 92.7
161.4
15.3
164.8 154.9 134.8 116.4 97.2
160.6
15.3
97.2
75.9
210.6
16.2
125.5 104.2 82.9
196.1
15.9
153.8 132.5 111.2 89.9
181.5
15.6
169.3 160.3 137.9 117.7 96.4
166.6
15.4
170.5 165.0 142.1 122.4 101.1
165.8
15.3
131.0 108.0 85.1
197.7
15.9
160.3 137.4 114.5 91.6
183.1
15.7
170.5 166.0 142.5 120.2 97.2
168.0
15.4
171.7 169.0 145.3 123.2 100.2
167.2
15.4
136.4 111.9 87.4
199.4
16.0
166.8 142.3 117.8 93.2
184.7
15.7
171.7 171.7 147.1 122.6 98.1
169.5
15.5
173.0 173.0 148.4 123.9 99.4
168.6
15.4

90
103.4
128.0
152.7
165.4
162.3
112.2
138.5
164.9
170.8
167.6
121.1
149.0
177.0
176.2
172.9
156.5
185.6
178.7
175.3
163.9
194.1
181.1
177.7
98.8
123.8
148.7
156.2
155.4
107.4
134.1
160.9
161.4
160.6
116.1
144.5
173.0
166.6
165.8
151.6
178.8
168.0
167.2
158.7
184.7
169.5
168.6

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
86.2
69.0
110.9 93.7
76.5
135.5 118.3 101.2 84.0
161.0 143.8 126.6 109.4
162.3 147.5 130.3 113.1
93.0
73.7
119.3 100.0 80.8
145.6 126.3 107.1 87.8
168.6 153.5 134.2 115.0
167.6 157.4 138.2 118.9
99.7
78.4
127.7 106.4 85.0
155.7 134.3 113.0 91.6
176.2 163.2 141.9 120.5
172.9 167.4 146.0 124.7
133.5 110.6 87.6
162.6 139.7 116.7 93.7
178.7 169.7 146.7 123.8
175.3 172.5 149.6 126.6
139.3 114.8 90.2
169.5 145.0 120.4 95.8
181.1 176.1 151.6 127.0
177.7 177.7 153.1 128.5
105°F
81.6
64.5
106.6 89.4
72.3
131.6 114.4 97.2
80.0
156.2 139.1 121.9 104.8
155.4 140.6 123.4 106.2
88.2
69.0
114.9 95.7
76.4
141.6 122.4 103.1 83.9
161.4 148.8 129.3 110.4
160.6 150.4 130.8 111.9
94.8
73.5
123.2 101.9 80.6
151.7 130.4 109.1 87.8
166.6 158.6 136.7 116.0
165.8 160.2 138.1 117.6
128.7 105.8 83.0
158.3 135.4 112.5 89.6
168.0 164.0 140.9 118.2
167.2 164.4 141.1 118.7
134.2 109.8 85.3
164.9 140.4 115.9 91.4
169.5 169.5 145.0 120.5
168.6 168.6 144.1 119.7

65
92.3
95.9
95.7
99.6
99.2
103.3
100.8
103.7
102.4
104.0
87.6
89.1
91.1
92.7
94.7
96.3
95.4
95.8
96.1
95.2

Johnson Controls Unitary Products

505428-YTG-R-1114

YD180 / Two NC090 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

193.0
179.5
166.0
154.6
151.8
198.9
185.0
171.0
159.2
156.4
204.7
190.4
176.1
163.9
161.0
192.4
177.9
165.6
162.6
194.3
179.7
167.3
164.3

17.7
17.4
17.1
16.8
16.8
17.8
17.5
17.2
16.9
16.9
17.9
17.6
17.2
17.0
17.0
17.6
17.3
17.1
17.0
17.7
17.4
17.1
17.1

96.7
121.8
146.9
154.6
151.8
105.2
132.0
158.9
159.2
156.4
113.7
142.3
170.9
163.9
161.0
149.4
175.3
165.6
162.6
156.5
179.7
167.3
164.3

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
79.6
62.4
188.7
19.3
104.6 87.5
70.3
175.3
19.0
129.7 112.6 95.4
78.2
161.9
18.7
154.6 137.6 120.4 103.3 86.1
152.9
18.5
151.8 136.4 119.2 102.1 84.9
148.2
18.4
86.0
66.7
193.8
19.4
112.8 93.6
74.3
180.0
19.1
139.6 120.4 101.2 81.9
166.2
18.8
159.2 147.2 128.0 108.7 89.5
157.1
18.6
156.4 145.9 126.7 107.5 88.2
152.2
18.5
92.4
71.1
198.9
19.5
121.0 99.7
78.4
184.8
19.2
149.6 128.3 107.0 85.7
170.6
18.9
163.9 156.8 135.5 114.2 92.9
161.3
18.7
161.0 155.4 134.2 112.9 91.6
156.2
18.6
126.5 103.6 80.8
187.0
19.3
156.2 133.4 110.5 87.7
172.7
18.9
165.6 162.1 139.2 116.3 93.5
163.2
18.7
162.6 159.9 137.0 114.1 91.3
158.1
18.7
132.0 107.6 83.2
189.2
19.3
162.9 138.5 114.1 89.6
174.7
19.0
167.3 167.3 142.9 118.4 94.0
165.1
18.8
164.3 164.3 139.8 115.4 91.0
159.9
18.7

90
94.6
119.9
145.1
152.9
148.2
103.0
129.9
156.9
157.1
152.2
111.3
140.0
168.7
161.3
156.2
147.1
171.7
163.2
158.1
154.2
174.7
165.1
159.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
77.5
60.3
102.7 85.5
68.3
127.9 110.7 93.5
76.4
152.9 136.1 118.9 101.7
148.2 132.2 115.1 97.9
83.7
64.5
110.7 91.5
72.2
137.7 118.4 99.2
80.0
157.1 145.6 126.6 107.1
152.2 141.4 122.6 103.0
90.0
68.7
118.7 97.4
76.1
147.4 126.1 104.9 83.6
161.3 155.1 134.3 112.5
156.2 150.7 130.2 108.1
124.3 101.4 78.6
154.2 131.4 108.5 85.7
163.2 160.1 137.5 114.4
158.1 155.3 132.9 109.6
129.9 105.5 81.1
161.0 136.6 112.2 87.8
165.1 165.1 140.7 116.3
159.9 159.9 135.6 111.2

65
84.6
80.7
87.9
83.7
91.2
86.8
91.6
86.8
92.0
86.8

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

33

505428-YTG-R-1114

YD180 / Two NC120
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

6000

7000

8000

9000

10000

34

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

241.0
222.0
203.0
191.6
189.3
247.3
227.8
208.3
196.6
194.3
253.6
233.6
213.6
201.6
199.3
238.5
218.1
205.8
203.4
243.3
222.5
210.0
207.6

12.0
11.7
11.4
11.2
11.2
12.1
11.8
11.5
11.2
11.3
12.2
11.9
11.5
11.3
11.4
11.9
11.6
11.4
11.4
12.0
11.7
11.4
11.5

121.2
154.8
188.4
191.6
189.3
136.7
168.9
201.0
196.6
194.3
152.2
182.9
213.6
201.6
199.3
193.5
218.1
205.8
203.4
204.1
222.5
210.0
207.6

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

233.2
216.5
199.8
184.5
189.1
238.5
221.5
204.4
188.8
193.4
243.9
226.4
209.0
193.0
197.8
229.5
211.8
195.6
200.5
232.6
214.7
198.3
203.2

14.3
14.0
13.7
13.4
13.5
14.4
14.1
13.8
13.5
13.6
14.5
14.2
13.9
13.6
13.7
14.2
13.9
13.7
13.7
14.3
14.0
13.7
13.8

118.3
152.7
187.1
184.5
189.1
134.9
166.5
198.1
188.8
193.4
151.5
180.2
209.0
193.0
197.8
190.6
211.8
195.6
200.5
200.9
214.7
198.3
203.2

Return Dry Bulb (°F)
85
80
75
70
75°F
97.8
74.3
131.4 107.9
84.4
165.0 141.5 118.0
94.5
191.6 168.1 144.6 121.1
189.5 166.0 142.6 119.1
106.3
79.7
142.3 115.8
89.2
178.4 151.8 125.3
98.7
196.6 180.4 153.4 127.3
194.4 178.2 152.5 125.1
114.8
85.1
153.3 123.7
94.1
191.8 162.2 132.6 103.0
201.6 192.7 162.3 133.5
199.3 190.3 162.5 131.1
161.5 129.6
97.6
201.9 169.9 138.0 106.1
205.8 201.3 169.0 137.4
203.4 199.0 167.9 135.1
169.8 135.5 101.2
212.0 177.7 143.4 109.1
210.0 210.0 175.7 141.4
207.6 207.6 173.3 139.0
95°F
94.6
71.0
129.1 105.5
81.9
163.5 139.9 116.3
92.7
184.1 160.5 136.8 113.2
188.2 164.6 141.0 117.4
102.9
76.3
139.8 113.2
86.6
176.8 150.2 123.6
97.0
188.5 172.3 146.1 119.0
193.0 176.7 149.3 123.5
111.1
81.5
150.6 121.0
91.4
190.1 160.5 130.9 101.3
193.0 184.1 155.3 124.9
197.8 188.9 157.5 129.6
158.6 126.6
94.5
199.9 167.9 135.9 103.9
195.6 191.2 159.6 127.2
200.5 196.0 163.1 132.0
166.5 132.1
97.7
209.6 175.2 140.8 106.5
198.3 198.3 163.9 129.5
203.2 203.2 168.8 134.4

65

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

97.6
95.6
100.8
98.5
103.9
101.5
105.5
103.1
107.1
104.7

237.1
219.2
201.4
188.1
189.2
242.9
224.6
206.4
192.7
193.9
248.7
230.0
211.3
197.3
198.5
234.0
215.0
200.7
201.9
238.0
218.6
204.1
205.4

13.2
12.9
12.6
12.3
12.4
13.3
13.0
12.6
12.4
12.5
13.3
13.0
12.7
12.5
12.5
13.1
12.8
12.5
12.6
13.1
12.8
12.6
12.6

119.7
153.8
187.8
188.1
189.2
135.8
167.7
199.5
192.7
193.9
151.8
181.6
211.3
197.3
198.5
192.0
215.0
200.7
201.9
202.5
218.6
204.1
205.4

89.6
93.8
92.4
96.9
95.2
100.0
95.2
100.0
95.1
100.0

229.8
213.6
197.4
185.1
187.3
233.4
216.9
200.5
187.9
190.3
237.0
220.3
203.6
190.8
193.2
222.9
206.0
193.1
195.5
225.4
208.3
195.3
197.7

15.1
14.8
14.5
14.2
14.3
15.8
15.5
15.2
14.9
14.9
16.4
16.1
15.8
15.5
15.5
16.1
15.8
15.5
15.5
16.1
15.8
15.5
15.5

117.0
151.7
186.4
185.1
187.3
135.0
165.0
195.0
187.9
190.3
153.0
178.3
203.6
190.8
193.2
188.2
206.0
193.1
195.5
198.2
208.3
195.3
197.7

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
85°F
96.2
72.6
130.2 106.7 83.1
164.2 140.7 117.1 93.6
187.8 164.3 140.7 117.2
188.9 165.3 141.8 118.2
104.6 78.0
141.1 114.5 87.9
177.6 151.0 124.4 97.8
192.6 176.3 149.8 123.2
193.7 177.5 150.9 124.3
112.9 83.3
151.9 122.3 92.7
191.0 161.3 131.7 102.1
197.3 188.4 158.8 129.2
198.5 189.6 160.0 130.4
160.0 128.1 96.1
200.9 168.9 136.9 105.0
200.7 196.3 164.3 132.3
201.9 197.5 165.5 133.5
168.1 133.8 99.5
210.8 176.5 142.1 107.8
204.1 204.1 169.8 135.4
205.4 205.4 171.0 136.7
105°F
93.3
69.7
128.1 104.5 80.8
162.8 139.2 115.6 92.0
183.8 160.2 136.5 112.9
185.9 162.2 138.6 115.0
101.2 74.6
138.4 111.7 85.1
175.5 148.9 122.3 95.6
187.3 171.3 144.9 118.1
189.5 173.6 146.5 120.3
109.1 79.5
148.7 119.0 89.4
188.2 158.6 129.0 99.3
190.8 182.5 153.3 123.2
193.2 184.9 154.4 125.6
156.3 124.3 92.3
197.0 165.6 133.6 101.7
193.1 188.9 157.1 124.9
195.5 191.3 158.9 127.4
163.9 129.6 95.3
205.8 172.6 138.3 104.0
195.3 195.3 161.0 126.7
197.7 197.7 163.4 129.1

65
93.6
94.7
96.6
97.7
99.6
100.8
100.3
101.6
101.1
102.4
89.3
91.4
91.5
93.7
93.6
96.0
93.0
95.4
92.4
94.8

Johnson Controls Unitary Products

505428-YTG-R-1114

YD180 / Two NC120 (Continued)
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

1

2

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

226.4
210.6
194.9
185.6
185.6
228.3
212.4
196.5
187.1
187.1
230.2
214.2
198.2
188.7
188.7
216.2
200.1
190.5
190.5
218.3
202.0
192.3
192.3

15.9
15.6
15.3
15.0
15.0
17.1
16.8
16.5
16.2
16.2
18.3
18.0
17.7
17.3
17.3
17.9
17.6
17.3
17.3
17.9
17.6
17.2
17.2

115.7
150.7
185.7
185.6
185.6
135.1
163.5
191.9
187.1
187.1
154.5
176.3
198.2
188.7
188.7
185.9
200.1
190.5
190.5
195.5
202.0
192.3
192.3

Return Dry Bulb (°F)
85
80
75
70
115°F
92.1
68.4
127.1 103.5
79.8
162.1 138.5 114.9
91.2
183.5 159.8 136.2 112.6
183.5 159.9 136.3 112.6
99.6
72.9
136.9 110.3
83.6
174.2 147.6 121.0
94.3
186.1 170.4 143.7 117.1
186.1 170.4 143.8 117.1
107.1
77.4
146.7 117.1
87.4
186.3 156.7 127.1
97.4
188.7 180.9 151.2 121.6
188.7 180.9 151.3 121.6
154.0 122.0
90.1
194.1 163.4 131.4
99.5
190.5 186.6 154.7 122.7
190.5 186.6 154.7 122.8
161.3 127.0
92.8
202.0 170.0 135.8 101.6
192.3 192.3 158.1 123.8
192.3 192.3 158.1 123.9

65

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

89.0
89.0
90.5
90.5
92.0
92.0
90.8
90.8
89.6
89.6

223.0
207.7
192.4
186.1
183.8
223.2
207.9
192.6
186.3
184.0
223.4
208.1
192.7
186.5
184.2
209.6
194.2
187.9
185.5
211.1
195.6
189.3
186.9

16.7
16.4
16.1
15.8
15.8
18.5
18.2
17.9
17.5
17.5
20.2
19.9
19.6
19.2
19.1
19.8
19.5
19.1
19.0
19.7
19.4
19.0
18.9

114.4
149.7
185.0
186.1
183.8
135.2
162.0
188.9
186.3
184.0
156.0
174.4
192.7
186.5
184.2
183.6
194.2
187.9
185.5
192.8
195.6
189.3
186.9

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
125°F
90.8
67.1
126.1 102.5 78.8
161.4 137.8 114.1 90.5
183.2 159.5 135.9 112.3
181.1 157.5 133.9 110.3
97.9
71.3
135.4 108.8 82.1
172.9 146.3 119.6 93.0
184.8 169.4 142.6 116.1
182.6 167.2 141.0 114.0
105.1 75.4
144.7 115.1 85.5
184.4 154.8 125.1 95.5
186.5 179.3 149.2 120.0
184.2 176.9 148.2 117.7
151.7 119.8 87.9
191.3 161.1 129.2 97.3
187.9 184.3 152.2 120.5
185.5 181.9 150.5 118.1
158.6 124.5 90.3
195.6 167.4 133.3 99.1
189.3 189.3 155.2 121.0
186.9 186.9 152.8 118.6

65
88.7
86.7
89.5
87.3
90.3
88.0
88.6
86.2
86.9
84.5

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

35

505428-YTG-R-1114

YD180/ND180
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

36

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

208.6
198.3
188.0
170.5
177.8
217.2
206.4
195.7
177.6
185.1
225.8
214.6
203.4
184.6
192.4
214.6
203.4
184.6
192.4
214.6
203.5
184.6
192.5

11.7
11.4
11.0
10.9
11.0
11.7
11.4
11.1
10.9
11.0
11.8
11.4
11.1
11.0
11.1
11.5
11.2
11.1
11.1
11.6
11.3
11.1
11.2

106.3
132.6
158.8
170.5
177.8
117.1
145.5
173.8
177.6
185.1
128.0
158.4
188.9
184.6
192.4
167.9
196.2
184.6
192.4
177.4
203.5
184.6
192.5

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

203.1
187.3
171.5
162.0
166.8
208.8
192.5
176.2
166.5
171.4
214.4
197.7
181.0
171.0
176.1
198.8
182.0
171.9
177.0
199.8
183.0
172.9
178.0

14.3
14.0
13.7
13.5
13.5
14.3
14.1
13.8
13.5
13.6
14.4
14.2
13.9
13.6
13.7
14.2
13.9
13.7
13.7
14.3
14.0
13.7
13.8

101.0
127.2
153.5
162.0
166.8
110.9
139.0
167.2
166.5
171.4
120.8
150.9
180.9
171.0
176.1
160.7
181.9
171.9
177.0
170.5
183.0
172.9
178.0

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
87.7
69.0
205.9
13.0
113.9 95.3
76.6
192.8
12.7
140.2 121.5 102.9 84.2
179.7
12.4
170.5 152.4 133.8 115.1 96.5
166.3
12.2
177.8 161.5 142.9 124.2 105.6
172.3
12.2
95.9
74.6
213.0
13.0
124.2 102.9 81.6
199.5
12.7
152.5 131.2 110.0 88.7
186.0
12.5
177.6 164.6 144.0 122.0 100.8
172.0
12.2
185.1 174.5 153.9 131.9 110.6
178.3
12.3
104.0 80.1
220.1
13.1
134.5 110.5 86.6
206.1
12.8
164.9 141.0 117.0 93.1
192.2
12.5
184.6 176.9 154.2 129.0 105.1
177.8
12.3
192.4 187.4 165.0 139.5 115.6
184.2
12.4
142.4 116.8 91.2
206.7
12.9
174.5 149.0 123.4 97.8
192.7
12.6
184.6 180.7 155.8 129.6 104.0
178.3
12.4
192.4 189.9 165.1 138.8 113.2
184.7
12.4
150.3 123.1 95.9
207.2
12.9
184.1 157.0 129.8 102.6
193.2
12.6
184.6 184.6 157.4 130.2 103.0
178.7
12.4
192.5 192.5 165.3 138.1 110.9
185.2
12.5
95°F
82.1
63.3
189.1
16.0
108.4 89.5
70.7
175.6
15.7
134.6 115.8 96.9
78.1
162.1
15.5
162.0 147.9 129.0 110.2 91.3
153.3
15.3
166.8 150.2 131.4 112.5 93.7
156.8
15.2
89.4
67.9
195.1
16.0
117.6 96.1
74.6
181.2
15.8
145.7 124.2 102.7 81.2
167.3
15.5
166.5 158.7 136.5 115.7 94.2
158.2
15.3
171.4 161.2 139.0 118.2 96.7
161.8
15.3
96.7
72.5
201.1
16.1
126.7 102.6 78.5
186.8
15.8
156.8 132.7 108.5 84.4
172.4
15.6
171.0 169.5 144.0 121.2 97.1
163.0
15.4
176.1 172.2 146.5 123.9 99.8
166.8
15.4
134.9 109.1 83.3
186.7
15.9
166.9 141.1 115.3 89.5
172.4
15.6
171.9 171.2 144.7 119.6 93.8
163.0
15.4
177.0 175.1 148.5 123.5 97.7
166.7
15.4
143.0 115.6 88.2
186.7
15.9
176.9 149.5 122.0 94.6
172.3
15.7
172.9 172.9 145.4 118.0 90.6
162.9
15.5
178.0 178.0 150.5 123.1 95.6
166.7
15.4

90
103.7
129.9
156.1
166.3
172.3
114.0
142.3
170.5
172.0
178.3
124.4
154.6
184.9
177.8
184.2
164.3
189.0
178.3
184.7
174.0
193.2
178.7
185.2
95.4
122.5
149.7
153.3
156.8
108.5
134.8
161.0
158.2
161.8
121.6
147.0
172.4
163.0
166.8
156.8
172.4
163.0
166.7
166.7
172.3
162.9
166.7

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
84.9
66.2
111.1 92.4
73.6
137.4 118.6 99.9
81.1
166.3 150.1 131.4 112.6
172.3 155.9 137.1 118.4
92.6
71.2
120.9 99.5
78.1
149.1 127.7 106.3 84.9
172.0 161.7 140.3 118.9
178.3 167.8 146.5 125.1
100.3 76.3
130.6 106.6 82.5
160.9 136.8 112.8 88.8
177.8 173.2 149.1 125.1
184.2 179.8 155.8 131.7
138.6 113.0 87.3
170.7 145.0 119.3 93.7
178.3 176.0 150.3 124.6
184.7 182.5 156.8 131.2
146.6 119.3 92.0
180.5 153.2 125.9 98.6
178.7 178.7 151.4 124.1
185.2 185.2 157.9 130.6
105°F
76.6
57.9
103.8 85.0
66.3
130.9 112.2 93.5
74.7
153.3 141.3 122.5 103.8
156.8 145.7 126.9 108.2
84.0
62.7
113.4 92.1
70.8
142.8 121.5 100.2 78.8
158.2 153.0 131.3 110.3
161.8 157.8 136.1 115.1
91.4
67.4
123.1 99.1
75.2
154.8 130.8 106.9 83.0
163.0 164.7 140.1 116.8
166.8 169.9 145.2 122.0
131.0 105.1 79.2
162.0 138.7 112.8 86.9
163.0 163.8 137.6 112.1
166.7 168.3 142.0 116.5
138.9 111.0 83.2
169.3 146.5 118.7 90.9
162.9 162.9 135.1 107.3
166.7 166.7 138.8 111.0

65
93.9
99.6
97.5
103.7
101.1
107.7
98.9
105.5
96.8
103.3
85.0
89.5
89.0
93.8
92.9
98.1
86.2
90.6
79.5
83.2

Johnson Controls Unitary Products

505428-YTG-R-1114

YD180/ND180 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

175.1
163.9
152.8
144.6
146.8
181.4
169.9
158.3
149.8
152.1
187.8
175.8
163.9
155.1
157.5
174.6
162.8
154.0
156.4
173.5
161.7
153.0
155.4

17.7
17.4
17.2
17.1
17.0
17.7
17.5
17.2
17.1
17.0
17.8
17.5
17.3
17.2
17.1
17.6
17.3
17.2
17.1
17.6
17.3
17.2
17.1

89.8
117.8
145.9
144.6
146.8
106.1
130.5
154.9
149.8
152.1
122.4
143.1
163.9
155.1
157.5
153.0
162.8
154.0
156.4
162.9
161.7
153.0
155.4

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
71.1
52.5
161.0
19.4
99.2
80.6
61.9
152.2
19.1
127.3 108.6 90.0
71.4
143.4
18.9
144.6 134.7 116.0 97.4
78.8
135.8
18.8
146.8 141.1 122.5 103.9 85.2
136.8
18.7
78.6
57.4
167.8
19.4
109.3 88.1
66.9
158.6
19.2
140.0 118.8 97.6
76.4
149.4
18.9
149.8 147.3 126.1 104.9 83.7
141.5
18.9
152.1 154.3 133.1 112.0 90.8
142.5
18.7
86.1
62.3
174.5
19.4
119.4 95.6
71.9
164.9
19.2
152.7 129.0 105.2 81.5
155.3
19.0
155.1 159.9 136.1 112.4 88.7
147.1
18.9
157.5 167.5 143.8 120.1 96.3
148.2
18.8
127.0 101.1 75.1
162.6
19.2
157.2 136.3 110.3 84.3
153.2
19.0
154.0 156.4 130.5 104.5 78.5
145.1
19.0
156.4 161.4 135.5 109.5 83.5
146.1
18.8
134.7 106.5 78.3
160.3
19.3
161.7 143.6 115.4 87.2
151.0
19.0
153.0 153.0 124.8 96.6
68.4
143.0
19.0
155.4 155.4 127.2 99.0
70.8
144.0
18.8

90
84.1
113.1
142.1
135.8
136.8
103.6
126.2
148.7
141.5
142.5
123.1
139.2
155.3
147.1
148.2
149.2
153.2
145.1
146.1
159.1
151.0
143.0
144.0

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
65.6
47.1
94.6
76.1
57.6
123.6 105.1 86.6
68.0
135.8 128.1 109.5 91.0
136.8 136.6 118.0 99.5
73.2
52.2
105.2 84.1
63.1
137.1 116.1 95.1
74.0
141.5 141.5 120.9 99.5
142.5 142.5 130.2 108.8
80.8
57.2
115.7 92.2
68.6
150.7 127.1 103.6 80.0
147.1 147.1 132.2 108.0
148.2 148.2 142.4 118.1
123.1 97.0
71.0
152.4 133.9 107.8 81.8
145.1 145.1 123.3 96.9
146.1 146.1 128.9 102.5
130.5 101.9 73.3
151.0 140.6 112.0 83.5
143.0 143.0 114.5 85.9
144.0 144.0 115.5 86.9

65
72.5
81.0
78.5
87.8
84.4
94.6
70.9
76.4
57.3
58.3

1

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

37

505428-YTG-R-1114

YD180/ND240
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

38

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

213.8
201.0
188.1
171.4
175.2
220.6
207.3
194.1
176.8
180.7
227.3
213.6
200.0
182.2
186.3
217.5
203.6
185.5
189.6
221.4
207.3
188.8
193.0

12.1
11.8
11.5
11.3
11.3
12.2
11.9
11.6
11.4
11.4
12.3
12.0
11.7
11.5
11.5
12.1
11.8
11.6
11.5
12.2
11.9
11.6
11.6

109.1
136.0
162.8
171.4
175.2
120.2
149.2
178.1
176.8
180.7
131.3
162.3
193.3
182.2
186.3
172.8
200.3
185.5
189.6
183.2
207.3
188.8
193.0

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

210.9
194.8
178.7
161.6
162.4
217.5
200.9
184.4
166.7
167.5
224.2
207.1
190.0
171.8
172.7
209.6
192.3
173.9
174.7
212.0
194.5
175.9
176.8

14.5
14.2
13.9
13.6
13.6
14.6
14.3
14.0
13.7
13.7
14.7
14.4
14.1
13.8
13.8
14.4
14.2
13.9
13.9
14.5
14.2
13.9
13.9

108.6
133.5
158.4
161.6
162.4
119.8
146.7
173.6
166.7
167.5
131.1
160.0
188.9
171.8
172.7
170.1
191.7
173.9
174.7
180.2
194.5
175.9
176.8

Return Dry Bulb (°F)
85
80
75
70
75°F
89.8
70.5
116.7
97.4
78.1
143.5 124.2 104.9
85.6
168.3 149.0 129.7 110.4
175.2 157.4 138.1 118.8
98.1
76.0
127.0 104.9
82.8
156.0 133.8 111.7
89.6
175.2 160.5 138.7 116.3
180.7 169.6 148.2 125.4
106.4
81.5
137.4 112.5
87.5
168.4 143.5 118.5
93.6
182.2 172.1 147.8 122.2
186.3 181.8 158.2 132.0
145.5 118.2
90.9
178.1 150.8 123.5
96.2
185.5 180.5 153.5 125.9
189.6 187.4 160.8 132.8
153.5 123.9
94.3
187.7 158.1 128.4
98.8
188.8 188.8 159.2 129.5
193.0 193.0 163.4 133.7
95°F
89.3
70.0
114.2
94.9
75.7
139.1 119.8 100.6
81.3
161.5 142.2 122.9 103.6
162.4 144.9 125.7 106.4
97.7
75.6
124.6 102.5
80.4
151.5 129.4 107.3
85.2
166.7 153.6 131.2 109.4
167.5 156.5 133.8 112.3
106.2
81.2
135.0 110.1
85.2
163.9 139.0 114.1
89.1
171.8 164.9 139.4 115.1
172.7 168.1 141.8 118.3
142.8 115.6
88.3
173.1 145.9 118.6
91.4
173.9 170.4 142.9 115.9
174.7 172.4 144.5 117.9
150.6 121.0
91.4
182.3 152.8 123.2
93.6
175.9 175.9 146.3 116.8
176.8 176.8 147.2 117.6

65

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

91.1
99.5
94.2
103.2
97.3
107.0
98.6
105.6
99.9
104.1

212.3
197.9
183.4
166.5
168.8
219.0
204.1
189.2
171.8
174.1
225.7
210.4
195.0
177.0
179.5
213.5
197.9
179.7
182.2
216.7
200.9
182.4
184.9

13.3
13.0
12.7
12.5
12.5
13.4
13.1
12.8
12.6
12.5
13.5
13.2
12.9
12.7
12.6
13.3
13.0
12.7
12.7
13.3
13.0
12.8
12.8

108.9
134.7
160.6
166.5
168.8
120.0
147.9
175.9
171.8
174.1
131.2
161.2
191.1
177.0
179.5
171.4
196.0
179.7
182.2
181.7
200.9
182.4
184.9

84.4
87.1
87.2
90.2
90.1
93.3
88.7
90.7
87.2
88.0

205.7
190.4
175.1
157.3
159.4
212.5
196.6
180.8
162.5
164.7
219.2
202.9
186.6
167.6
169.9
205.0
188.5
169.4
171.7
207.1
190.5
171.2
173.5

16.4
16.0
15.6
15.3
15.3
16.5
16.1
15.8
15.4
15.4
16.6
16.2
15.9
15.5
15.5
16.3
15.9
15.5
15.5
16.3
15.9
15.5
15.5

106.6
131.6
156.7
157.3
159.4
118.4
144.9
171.3
162.5
164.7
130.3
158.2
186.0
167.6
169.9
168.2
188.2
169.4
171.7
178.2
190.5
171.2
173.5

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
85°F
89.6
70.3
115.4 96.1
76.9
141.3 122.0 102.7 83.4
164.9 145.6 126.3 107.0
168.8 151.2 131.9 112.6
97.9
75.8
125.8 103.7 81.6
153.7 131.6 109.5 87.4
170.9 157.1 134.9 112.8
174.1 163.1 141.0 118.8
106.3 81.3
136.2 111.3 86.4
166.2 141.2 116.3 91.4
177.0 168.5 143.6 118.7
179.5 175.0 150.0 125.1
144.1 116.9 89.6
175.6 148.3 121.1 93.8
179.7 175.4 148.2 120.9
182.2 179.9 152.7 125.4
152.1 122.5 92.8
185.0 155.4 125.8 96.2
182.4 182.4 152.8 123.1
184.9 184.9 155.3 125.7
105°F
87.3
68.0
112.3 93.1
73.8
137.4 118.1 98.9
79.6
157.2 139.1 119.9 100.6
159.4 142.1 122.8 103.6
95.7
73.6
122.8 100.7 78.6
149.9 127.8 105.7 83.6
162.4 150.5 128.3 106.3
164.7 153.7 131.3 109.5
104.1 79.1
133.2 108.3 83.4
162.4 137.5 112.5 87.6
167.6 161.9 136.7 112.0
169.9 165.3 139.7 115.5
140.9 113.7 86.4
171.5 144.3 117.0 89.7
169.4 166.5 139.1 112.0
171.7 169.4 141.8 114.9
148.6 119.0 89.4
180.6 151.0 121.5 91.9
171.2 171.2 141.6 112.0
173.5 173.5 143.9 114.3

65
87.7
93.3
90.7
96.7
93.7
100.2
93.6
98.1
93.5
96.1
81.3
84.3
84.2
87.4
87.1
90.6
84.8
87.6
82.4
84.7

Johnson Controls Unitary Products

505428-YTG-R-1114

YD180/ND240 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

200.6
186.0
171.4
153.0
156.4
207.4
192.3
177.2
158.2
161.8
214.3
198.7
183.1
163.5
167.1
200.5
184.7
164.9
168.6
202.3
186.4
166.4
170.1

18.3
17.8
17.4
16.9
16.9
18.4
18.0
17.5
17.0
17.0
18.6
18.1
17.6
17.1
17.1
18.1
17.6
17.1
17.1
18.1
17.6
17.1
17.1

104.5
129.7
154.9
153.0
156.4
117.0
143.0
169.0
158.2
161.8
129.6
156.3
183.1
163.5
167.1
166.3
184.7
164.9
168.6
176.2
186.4
166.4
170.1

Return Dry Bulb (°F)
85
80
75
70
115°F
85.3
66.0
110.5
91.2
72.0
135.7 116.4
97.2
77.9
153.0 136.1 116.8
97.6
156.4 139.2 120.0 100.7
93.6
71.5
120.9
98.9
76.8
148.3 126.2 104.1
82.0
158.2 147.5 125.4 103.3
161.8 150.9 128.8 106.7
102.0
77.1
131.4 106.5
81.6
160.9 135.9 111.0
86.1
163.5 158.8 133.9 109.0
167.1 162.6 137.6 112.7
139.0 111.8
84.5
169.9 142.6 115.4
88.1
164.9 162.6 135.4 108.1
168.6 166.3 139.1 111.8
146.6 117.0
87.4
178.9 149.3 119.7
90.1
166.4 166.4 136.8 107.2
170.1 170.1 140.5 110.9

65

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

78.3
81.5
81.2
84.6
84.1
87.8
80.8
84.6
77.6
81.3

195.5
181.6
167.7
148.7
153.5
202.4
188.1
173.7
154.0
158.9
209.4
194.5
179.7
159.3
164.4
196.0
181.0
160.4
165.6
197.4
182.3
161.6
166.8

20.2
19.6
19.1
18.5
18.5
20.4
19.8
19.2
18.7
18.7
20.5
20.0
19.4
18.8
18.8
19.9
19.4
18.8
18.8
19.9
19.3
18.7
18.7

102.5
127.9
153.2
148.7
153.5
115.6
141.2
166.7
154.0
158.9
128.8
154.5
179.7
159.3
164.4
164.4
181.0
160.4
165.6
174.2
182.3
161.6
166.8

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
125°F
83.2
64.0
108.6 89.4
70.1
134.0 114.7 95.5
76.3
148.7 133.0 113.8 94.5
153.5 136.4 117.1 97.9
91.6
69.5
119.1 97.0
75.0
146.6 124.6 102.5 80.4
154.0 144.4 122.5 100.2
158.9 148.1 126.3 103.9
99.9
75.0
129.6 104.7 79.8
159.3 134.4 109.5 84.6
159.3 155.8 131.2 106.0
164.4 159.8 135.5 110.0
137.1 109.8 82.6
168.3 141.0 113.8 86.5
160.4 158.7 131.6 104.2
165.6 163.3 136.4 108.8
144.6 115.0 85.4
177.2 147.6 118.0 88.4
161.6 161.6 132.0 102.4
166.8 166.8 137.2 107.6

65
75.3
78.7
78.2
81.9
81.1
85.1
76.9
81.5
72.8
78.0

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

39

505428-YTG-R-1114

YC240/NC240
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

6000

7000

8000

9000

10000

40

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

286.3
267.4
248.5
228.9
227.5
296.6
277.0
257.5
237.1
235.7
306.9
286.6
266.4
245.4
243.8
296.2
275.2
253.5
251.9
305.7
284.0
261.7
260.0

15.3
14.8
14.4
14.1
14.0
15.4
14.9
14.5
14.2
14.1
15.5
15.0
14.6
14.3
14.2
15.1
14.7
14.4
14.3
15.2
14.8
14.5
14.4

136.1
169.4
202.7
228.9
227.5
148.2
184.0
219.8
237.1
235.7
160.3
198.6
236.9
245.4
243.8
209.5
251.9
253.5
251.9
220.5
266.9
261.7
260.0

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

273.6
253.1
232.5
217.9
214.0
279.2
258.2
237.3
222.3
218.4
284.7
263.4
242.0
226.8
222.7
268.5
246.7
231.2
227.1
273.6
251.4
235.6
231.4

18.5
18.1
17.7
17.3
17.4
18.6
18.2
17.8
17.4
17.5
18.7
18.3
17.9
17.5
17.5
18.3
17.9
17.5
17.5
18.3
17.9
17.5
17.5

126.9
163.1
199.3
217.9
214.0
138.0
176.9
215.8
222.3
218.4
149.2
190.7
232.2
226.8
222.7
201.0
241.8
231.2
227.1
211.3
251.4
235.6
231.4

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
113.4 90.6
280.0
16.9
146.7 123.9 101.2
260.2
16.5
180.0 157.2 134.5 111.7
240.5
16.1
216.8 194.0 171.3 148.5 125.8
223.4
15.7
227.5 205.1 182.4 159.6 136.9
220.8
15.7
122.8 97.4
287.9
17.0
158.6 133.2 107.8
267.6
16.6
194.4 169.0 143.6 118.3
247.4
16.1
231.1 208.6 184.8 157.8 132.4
229.7
15.8
235.7 220.5 197.5 169.7 144.3
227.0
15.8
132.3 104.2
295.8
17.1
170.6 142.5 114.5
275.0
16.7
208.9 180.8 152.8 124.8
254.2
16.2
245.4 223.1 198.3 167.1 139.0
236.1
15.9
243.8 235.9 212.7 179.8 151.8
233.3
15.9
179.3 149.0 118.8
282.3
16.7
219.4 189.1 158.9 128.6
261.0
16.3
253.5 233.4 204.7 172.9 142.6
242.4
15.9
251.9 248.0 220.1 187.5 157.2
239.5
15.9
188.0 155.6 123.1
289.7
16.8
229.9 197.4 165.0 132.5
267.7
16.3
261.7 243.6 211.1 178.7 146.2
248.7
16.0
260.0 260.0 227.6 195.1 162.7
245.7
16.0
95°F
103.1 79.2
259.0
21.0
139.3 115.4 91.6
239.6
20.4
175.5 151.6 127.8 103.9
220.3
19.9
210.8 186.9 163.1 139.2 115.4
205.1
19.5
214.0 198.6 174.7 150.9 127.0
204.2
19.6
111.6 85.1
264.6
21.0
150.4 123.9 97.5
244.8
20.5
189.3 162.8 136.3 109.9
225.0
20.0
218.8 200.7 172.6 147.8 121.3
209.5
19.5
218.4 213.2 184.3 160.3 133.8
208.6
19.6
120.1 90.9
270.2
21.1
161.6 132.5 103.4
250.0
20.6
203.1 174.0 144.9 115.8
229.8
20.0
226.8 214.5 182.2 156.3 127.2
213.9
19.6
222.7 227.9 193.9 169.6 140.5
213.0
19.7
169.2 137.4 105.7
255.2
20.7
212.3 180.5 148.7 117.0
234.6
20.1
231.2 222.6 189.2 159.0 127.2
218.4
19.7
227.1 229.6 195.4 166.1 134.3
217.5
19.8
176.8 142.4 108.0
260.4
20.7
221.5 187.0 152.6 118.2
239.3
20.2
235.6 230.6 196.2 161.7 127.3
222.8
19.8
231.4 231.4 196.9 162.5 128.1
221.9
19.9

90
131.5
166.3
201.0
223.4
220.8
143.1
180.5
217.8
229.7
227.0
154.7
194.7
234.6
236.1
233.3
205.3
246.8
242.4
239.5
215.9
259.1
248.7
245.7
123.8
159.8
195.8
205.1
204.2
137.3
173.8
210.4
209.5
208.6
150.8
187.8
224.9
213.9
213.0
198.4
232.1
218.4
217.5
209.0
239.3
222.8
221.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
108.2 84.9
143.0 119.7 96.4
177.7 154.4 131.1 107.8
213.8 190.5 167.2 143.9
220.8 201.8 178.5 155.2
117.2 91.3
154.5 128.6 102.7
191.9 165.9 140.0 114.1
224.9 204.7 178.7 152.8
227.0 216.9 190.9 165.0
126.2 97.6
166.1 137.5 108.9
206.0 177.4 148.8 120.3
236.1 218.8 190.3 161.7
233.3 231.9 203.3 174.7
174.3 143.2 112.2
215.8 184.8 153.8 122.8
242.4 228.0 197.0 165.9
239.5 238.8 207.8 176.8
182.4 149.0 115.5
225.7 192.2 158.8 125.3
248.7 237.1 203.7 170.2
245.7 245.7 212.3 178.8
105°F
99.6
75.3
135.6 111.3 87.1
171.6 147.4 123.1 98.9
201.5 182.5 158.3 134.0
204.2 186.7 162.4 138.2
108.0 81.0
146.8 119.7 92.7
185.5 158.5 131.4 104.4
207.7 196.3 168.4 142.2
208.6 200.7 172.5 146.6
116.5 86.7
158.0 128.1 98.2
199.4 169.6 139.7 109.8
213.9 210.0 178.5 150.3
213.0 214.8 182.5 155.0
166.0 133.5 101.1
209.2 176.8 144.3 111.9
218.4 215.2 181.9 150.3
217.5 218.3 184.7 153.4
174.0 139.0 104.0
219.0 184.0 148.9 113.9
222.8 220.3 185.3 150.3
221.9 221.9 186.9 151.8

65
120.6
131.9
126.9
139.0
133.1
146.2
134.9
145.8
136.8
145.4
109.8
114.0
115.1
119.6
120.4
125.2
117.8
121.0
115.2
116.8

Johnson Controls Unitary Products

505428-YTG-R-1114

YC240/NC240 (Continued)
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

244.4
226.2
208.0
192.2
194.4
250.0
231.4
212.8
196.7
198.9
255.7
236.6
217.6
201.1
203.3
241.9
222.4
205.6
207.9
247.2
227.3
210.0
212.4

23.4
22.8
22.1
21.6
21.8
23.5
22.8
22.1
21.7
21.8
23.5
22.8
22.2
21.7
21.8
23.0
22.3
21.9
22.0
23.2
22.5
22.0
22.2

120.7
156.5
192.4
192.2
194.4
136.5
170.8
205.0
196.7
198.9
152.4
185.0
217.6
201.1
203.3
195.9
222.4
205.6
207.9
206.8
227.3
210.0
212.4

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
96.0
71.4
229.9
25.9
131.9 107.2 82.6
212.8
25.1
167.7 143.1 118.5 93.8
195.7
24.3
192.2 178.1 153.5 128.8 104.2
179.4
23.8
194.4 174.8 150.2 125.5 100.9
184.6
23.9
104.5 76.9
235.5
25.9
143.1 115.5 87.9
218.0
25.1
181.7 154.1 126.5 98.9
200.5
24.3
196.7 191.8 164.2 136.5 108.9
183.8
23.8
198.9 188.3 160.6 133.0 105.4
189.1
24.0
113.0 82.4
241.1
25.9
154.4 123.7 93.1
223.2
25.1
195.7 165.1 134.5 103.9
205.3
24.3
201.1 205.5 174.9 144.3 113.6
188.2
23.9
203.3 201.7 171.1 140.5 109.8
193.6
24.0
162.8 129.7 96.5
228.6
25.4
206.1 173.0 139.9 106.8
210.3
24.6
205.6 207.8 174.6 141.5 108.4
192.7
24.1
207.9 207.0 173.9 140.8 107.7
198.3
24.2
171.2 135.6 100.0
233.9
25.6
216.5 180.9 145.3 109.7
215.2
24.8
210.0 210.0 174.4 138.8 103.2
197.3
24.3
212.4 212.4 176.8 141.2 105.6
202.9
24.5

90
117.5
153.2
188.9
179.4
184.6
135.8
167.7
199.6
183.8
189.1
154.0
182.1
205.3
188.2
193.6
193.3
210.3
192.7
198.3
204.5
215.2
197.3
202.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
92.5
67.5
128.2 103.2 78.1
163.9 138.9 113.8 88.8
179.4 173.7 148.6 123.6
184.6 162.9 137.9 112.9
101.0 72.8
139.5 111.3 83.1
178.0 149.8 121.6 93.4
183.8 183.8 159.9 130.9
189.1 175.8 148.8 119.4
109.5 78.1
150.8 119.4 88.0
192.1 160.7 129.3 97.9
188.2 188.2 171.2 138.2
193.6 188.6 159.7 125.9
159.5 125.8 92.0
203.0 169.3 135.5 101.7
192.7 192.7 167.4 132.8
198.3 195.8 163.2 128.2
168.3 132.1 95.9
214.0 177.8 141.6 105.4
197.3 197.3 163.5 127.4
202.9 202.9 166.7 130.5

65
98.6
87.8
102.7
91.2
106.9
94.5
99.0
94.4
91.2
94.3

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

41

505428-YTG-R-1114

YD240 / Two NC120
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

6000

7000

8000

9000

10000

42

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

268.6
253.5
238.3
214.5
213.5
280.9
265.0
249.1
224.2
223.1
293.1
276.4
259.8
234.0
232.8
278.2
261.5
235.5
234.3
280.0
263.2
236.9
235.7

15.0
14.6
14.2
13.9
13.9
15.1
14.7
14.3
14.0
14.0
15.2
14.8
14.4
14.1
14.1
14.9
14.5
14.2
14.1
15.0
14.6
14.2
14.2

134.0
166.7
199.5
214.5
213.5
145.1
179.9
214.8
224.2
223.1
156.2
193.1
230.1
234.0
232.8
206.2
246.7
235.5
234.3
219.3
263.2
236.9
235.7

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

272.5
250.7
228.9
212.2
212.1
279.1
256.8
234.5
217.3
217.2
285.6
262.8
240.0
222.4
222.3
270.4
246.9
228.9
228.7
278.0
253.9
235.3
235.1

18.0
17.6
17.3
17.0
17.0
18.1
17.7
17.4
17.1
17.1
18.2
17.8
17.5
17.2
17.2
17.9
17.6
17.2
17.2
18.0
17.6
17.3
17.3

129.1
162.4
195.8
212.2
212.1
140.3
175.9
211.5
217.3
217.2
151.5
189.3
227.2
222.4
222.3
202.6
240.5
228.9
228.7
215.8
253.9
235.3
235.1

Return Dry Bulb (°F)
85
80
75
75°F
111.2
88.5
144.0
121.3
98.6
176.8
154.1
131.3
210.2
187.4
164.7
216.8
196.1
173.3
119.6
94.1
154.5
129.0
103.5
189.3
163.9
138.4
222.1
199.4
174.6
224.8
208.6
184.1
128.0
99.8
164.9
136.7
108.5
201.9
173.7
145.5
234.0
211.3
184.5
232.8
221.0
194.8
175.3
144.3
113.4
214.3
183.3
152.4
235.5
223.0
192.8
234.3
228.4
198.5
185.6
151.9
118.3
226.7
193.0
159.3
236.9
234.8
201.1
235.7
235.7
202.1
95°F
106.2
83.3
139.5
116.6
93.7
172.9
150.0
127.1
206.2
183.3
160.5
208.7
185.8
162.9
114.6
88.8
150.1
124.4
98.7
185.7
160.0
134.3
214.3
195.6
169.1
215.5
198.2
171.5
123.0
94.4
160.8
132.2
103.6
198.6
170.0
141.4
222.4
207.8
177.8
222.3
210.6
180.1
171.4
140.1
108.9
211.4
180.2
149.0
228.9
220.3
188.4
228.7
222.9
190.7
181.9
148.1
114.3
224.3
190.5
156.6
235.3
232.8
199.0
235.1
235.1
201.3

70

65

Total
Capacity1
(MBh)

108.6
142.0
150.6
112.9
148.4
157.6
117.3
154.9
164.6
121.5
161.2
166.5
125.6
167.4
168.4

119.3
127.9
123.0
132.2
126.7
136.4
130.2
135.6
133.8
134.7

270.6
252.1
233.6
213.4
212.8
280.0
260.9
241.8
220.8
220.2
289.4
269.6
249.9
228.2
227.5
274.3
254.2
232.2
231.5
279.0
258.6
236.1
235.4

16.5
16.1
15.7
15.4
15.4
16.6
16.2
15.8
15.5
15.5
16.7
16.3
16.0
15.6
15.6
16.4
16.0
15.7
15.7
16.5
16.1
15.8
15.8

131.5
164.6
197.6
213.4
212.8
142.7
177.9
213.1
220.8
220.2
153.9
191.2
228.6
228.2
227.5
204.4
243.6
232.2
231.5
217.5
258.6
236.1
235.4

104.2
137.6
140.0
108.5
144.1
146.8
112.8
150.7
153.5
117.8
157.9
160.5
122.8
165.2
167.5

114.7
117.2
118.4
121.0
122.1
124.9
126.7
129.3
131.4
133.7

233.1
228.1
223.1
206.1
197.7
243.8
239.1
234.3
216.4
207.4
254.6
250.0
245.4
226.7
217.0
258.5
253.9
234.5
224.4
267.0
262.3
242.2
231.8

17.0
18.4
19.7
19.3
19.2
17.2
18.5
19.9
19.5
19.4
17.3
18.7
20.0
19.7
19.6
18.8
20.1
19.8
19.6
18.8
20.2
19.8
19.7

161.4
184.0
193.2
206.1
197.7
183.8
194.4
198.4
213.5
207.4
206.2
204.9
203.7
220.9
217.0
220.4
228.3
231.6
224.4
235.9
252.9
242.2
231.8

Total
Input
(kW)2

90

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
65
85°F
108.7 85.9
141.8 119.0 96.1
174.8 152.0 129.2 106.4 208.2 185.4 162.6 139.8 117.0
212.8 190.9 168.1 145.3 122.5
117.1 91.5
152.3 126.7 101.1
187.5 161.9 136.3 110.7 218.2 197.5 171.9 146.3 120.7
220.2 203.4 177.8 152.2 126.6
125.5 97.1
162.8 134.5 106.1
200.2 171.8 143.4 115.1 228.2 209.6 181.2 152.8 124.4
227.5 215.8 187.4 159.1 130.7
173.3 142.2 111.2
212.8 181.8 150.7 119.6 232.2 221.7 190.6 159.5 128.5
231.5 225.6 194.6 163.5 132.4
183.8 150.0 116.3
225.5 191.7 158.0 124.2 236.1 233.8 200.1 166.3 132.6
235.4 235.4 201.7 167.9 134.2
105°F
149.9 138.5
172.5 153.8 131.0
170.4 147.5 124.7 101.9 203.1 186.5 163.7 140.8 118.0
196.1 184.6 161.8 138.9 116.1
164.3 144.9
175.0 151.9 126.8
173.3 148.2 123.0 97.9
205.4 186.9 161.4 136.6 111.5
206.5 195.0 169.3 144.7 119.6
178.8 151.3
177.5 150.1 122.6
176.2 148.8 121.4 93.9
207.8 187.3 159.1 132.4 105.0
217.0 205.4 176.9 150.5 123.0
198.2 172.7 142.1
198.7 168.1 137.5 106.9 225.0 212.1 181.2 150.9 120.3
224.4 218.6 187.5 157.4 126.8
219.0 195.4 161.7
221.2 187.5 153.7 119.9 242.2 237.0 203.2 169.4 135.6
231.8 231.8 198.0 164.3 130.5

Johnson Controls Unitary Products

505428-YTG-R-1114

YD240 / Two NC120 (Continued)
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

1

2

Temperature of Air on Condenser Coil

Sensible Capacity (MBh)1

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

193.7
205.5
217.3
200.0
183.4
208.6
221.4
234.1
215.5
197.5
223.6
237.2
250.9
230.9
211.7
246.6
260.8
240.1
220.1
256.0
270.8
249.2
228.5

16.1
19.1
22.1
21.7
21.4
16.3
19.3
22.3
22.0
21.7
16.5
19.6
22.6
22.3
22.0
19.6
22.7
22.3
22.0
19.6
22.7
22.4
22.1

193.7
205.5
190.7
200.0
183.4
227.3
213.0
185.4
209.7
197.5
260.9
220.5
180.2
219.4
211.7
238.3
216.1
234.3
220.1
256.0
251.9
249.2
228.5

Return Dry Bulb (°F)
85
80
75
115°F
193.7
193.7
205.5
190.9
168.2
167.9
145.1
122.3
200.0
189.6
166.9
183.4
183.4
160.6
214.1
201.0
199.9
179.4
154.9
160.9
136.4
111.8
196.6
178.2
153.7
197.5
191.7
167.2
234.6
208.3
194.2
167.9
141.6
153.9
127.6
101.3
193.1
166.8
140.5
211.7
200.1
173.8
225.1
205.3
175.3
186.0
156.0
126.0
221.1
203.9
173.9
220.1
214.3
184.3
256.0
242.8
209.0
218.2
184.5
150.7
249.2
241.1
207.4
228.5
228.5
194.8

70

65

Total
Capacity1
(MBh)

99.5
144.1
137.8
87.3
129.1
142.7
75.0
114.2
147.5
96.0
143.9
154.3
117.0
173.7
161.0

121.3
115.1
104.6
118.1
87.9
121.2
113.9
124.3
139.9
127.3

154.3
182.9
211.5
194.0
169.1
173.4
203.6
233.9
214.5
187.7
192.5
224.4
256.3
235.1
206.4
234.7
267.7
245.6
215.8
245.0
279.2
256.2
225.1

Total
Input
(kW)2

90

15.2
19.8
24.5
24.1
23.7
15.4
20.1
24.8
24.5
24.0
15.7
20.4
25.2
24.8
24.4
20.5
25.2
24.9
24.4
20.5
25.3
24.9
24.4

154.3
182.9
188.1
194.0
169.1
173.4
203.6
172.4
205.9
187.7
192.5
224.4
156.8
217.9
206.4
234.7
203.8
237.0
215.8
245.0
250.9
256.2
225.1

Sensible Capacity (MBh)1
Return Dry Bulb (°F)
85
80
75
70
65
125°F
154.3 154.3
182.9 182.9 182.9
165.4 142.6 119.9 97.2
194.0 192.8 170.1 147.3 124.6
169.1 169.1 159.4 136.7 114.0
173.4 173.4
203.6 203.6 183.0
148.5 124.5 100.6 76.6
187.7 169.5 145.9 121.6 97.7
187.7 187.7 165.1 140.6 116.7
192.5 192.5
211.0 185.8 160.6
131.6 106.4 81.2 56.1
178.4 146.3 121.8 95.9 70.8
206.4 194.8 170.7 144.5 119.3
234.7 234.7 208.5
173.3 143.9 114.5 85.1
217.3 195.7 166.7 136.9 107.5
215.8 210.0 181.1 151.2 121.7
245.0 245.0 245.0
215.1 181.5 147.8 114.1 256.2 245.2 211.6 177.9 144.2
225.1 225.1 191.5 157.8 124.2

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

43

505428-YTG-R-1114

YD240/ND240
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

6000

7000

8000

9000

10000

44

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

292.8
272.9
253.0
231.8
224.6
302.2
281.7
261.1
239.3
231.8
311.7
290.5
269.3
246.8
239.1
299.4
277.5
254.3
246.4
308.2
285.7
261.9
253.7

14.7
14.4
14.0
13.8
13.7
14.8
14.5
14.2
13.9
13.9
14.9
14.6
14.3
14.0
14.0
14.9
14.6
14.3
14.2
15.2
14.8
14.6
14.5

136.9
174.4
211.9
231.8
224.6
149.9
190.2
230.5
239.3
231.8
162.8
206.0
249.1
246.8
239.1
217.9
267.1
254.3
246.4
229.9
285.0
261.9
253.7

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

275.8
254.0
232.2
219.1
214.1
281.7
259.4
237.1
223.7
218.6
287.5
264.8
242.0
228.4
223.1
270.1
246.9
233.0
227.6
275.4
251.8
237.6
232.1

18.1
17.8
17.5
17.2
17.3
18.2
17.9
17.6
17.3
17.4
18.3
18.0
17.7
17.4
17.4
18.3
18.0
17.7
17.7
18.6
18.2
18.0
18.0

133.4
169.0
204.5
219.1
214.1
144.7
182.5
220.4
223.7
218.6
155.9
196.1
236.3
228.4
223.1
206.1
244.1
233.0
227.6
216.0
251.8
237.6
232.1

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
111.9 87.0
284.3
16.4
149.4 124.5 99.5
263.5
16.1
186.9 162.0 137.0 112.0
242.6
15.8
220.2 195.2 170.2 145.2 120.2
225.5
15.5
224.6 207.1 182.1 157.1 132.1
219.3
15.5
121.7 93.5
292.0
16.5
162.0 133.8 105.6
270.5
16.2
202.3 174.1 145.9 117.7
249.1
15.9
233.5 209.9 182.9 153.5 125.3
231.5
15.6
231.8 222.6 196.1 166.2 138.0
225.2
15.6
131.4 100.0
299.6
16.6
174.5 143.1 111.7
277.6
16.3
217.7 186.2 154.8 123.4
255.6
16.0
246.8 224.5 195.6 161.7 130.3
237.6
15.7
239.1 238.1 210.2 175.3 143.9
231.1
15.7
184.4 150.9 117.3
284.7
16.6
229.8 196.3 162.8 129.3
262.2
16.3
254.3 236.8 204.5 169.7 136.2
243.7
16.0
246.4 245.9 214.1 178.9 145.4
237.0
16.0
194.2 158.6 123.0
291.8
16.9
242.0 206.4 170.8 135.2
268.7
16.5
261.9 249.0 213.4 177.7 142.1
249.7
16.3
253.7 253.7 218.1 182.5 146.9
242.9
16.3
95°F
108.4 83.3
262.8
20.3
143.9 118.8 93.8
242.0
20.1
179.5 154.4 129.3 104.3
221.1
19.8
218.4 193.3 168.3 143.2 118.2
208.7
19.6
214.1 196.0 170.9 145.9 120.8
205.0
19.6
116.7 88.8
268.8
20.4
154.6 126.7 98.7
247.4
20.1
192.5 164.6 136.6 108.7
226.1
19.9
223.4 206.1 176.9 150.2 122.3
213.4
19.7
218.6 208.9 179.2 153.0 125.1
209.7
19.7
125.1 94.3
274.7
20.5
165.3 134.5 103.7
252.9
20.2
205.5 174.7 143.9 113.1
231.1
19.9
228.4 218.8 185.5 157.2 126.4
218.1
19.7
223.1 221.8 187.5 160.1 129.3
214.3
19.8
172.7 139.4 106.1
258.4
20.5
214.5 181.1 147.8 114.5
236.1
20.2
233.0 226.8 192.3 160.2 126.9
222.8
20.0
227.6 226.9 191.9 160.3 127.0
218.9
20.0
180.2 144.4 108.6
263.8
20.8
223.4 187.6 151.8 116.0
241.1
20.5
237.6 234.9 199.1 163.3 127.5
227.5
20.3
232.1 232.1 196.3 160.5 124.7
223.6
20.3

90
135.2
171.7
208.2
225.5
219.3
147.3
186.4
225.5
231.5
225.2
159.4
201.0
242.7
237.6
231.1
212.0
255.6
243.7
237.0
222.9
268.4
249.7
242.9
129.8
164.8
199.8
208.7
205.0
144.0
179.0
214.1
213.4
209.7
158.2
193.2
228.3
218.1
214.3
202.9
234.7
222.8
218.9
212.6
241.1
227.5
223.6

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
110.2 85.1
146.7 121.7 96.6
183.2 158.2 133.2 108.1
219.3 194.3 169.2 144.2
219.3 201.5 176.5 151.5
119.2 91.1
158.3 130.2 102.2
197.4 169.3 141.3 113.2
228.4 208.0 179.9 151.8
225.2 215.7 187.7 159.6
128.2 97.1
169.9 138.8 107.7
211.6 180.5 149.4 118.3
237.6 221.7 190.5 159.4
231.1 229.9 198.8 167.7
178.6 145.2 111.7
222.1 188.7 155.3 121.9
243.7 231.8 198.4 165.0
237.0 236.4 203.0 169.6
187.2 151.5 115.8
232.7 197.0 161.3 125.6
249.7 241.9 206.2 170.5
242.9 242.9 207.2 171.5
105°F
104.7 79.5
139.7 114.6 89.5
174.7 149.6 124.5 99.4
208.3 185.8 160.7 135.6
205.0 186.2 161.1 136.0
113.4 85.3
150.9 122.8 94.7
188.4 160.3 132.2 104.1
213.2 199.1 170.4 142.9
209.7 199.6 170.6 143.4
122.1 91.0
162.1 131.0 99.9
202.2 171.1 140.0 108.8
218.1 212.5 180.1 150.3
214.3 212.9 180.1 150.7
169.4 136.0 102.5
211.0 177.5 144.1 110.6
222.8 219.3 185.2 152.4
218.9 218.2 183.9 151.3
176.7 140.9 105.1
219.8 184.0 148.2 112.3
227.5 226.1 190.3 154.5
223.6 223.6 187.7 151.9

65
119.2
126.5
123.8
131.5
128.3
136.6
131.5
136.2
134.8
135.8
110.5
110.9
114.8
115.2
119.1
119.6
118.9
117.8
118.6
116.1

Johnson Controls Unitary Products

505428-YTG-R-1114

YD240/ND240 (Continued)
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

249.8
229.9
210.1
198.2
196.0
255.8
235.5
215.2
203.0
200.8
261.9
241.1
220.3
207.8
205.5
246.6
225.3
212.6
210.3
252.2
230.4
217.4
215.0

22.6
22.3
22.0
21.9
21.9
22.7
22.4
22.1
22.0
22.0
22.8
22.5
22.2
22.1
22.1
22.7
22.4
22.3
22.3
23.0
22.7
22.5
22.5

126.1
160.6
195.1
198.2
196.0
143.3
175.5
207.7
203.0
200.8
160.5
190.4
220.3
207.8
205.5
199.8
225.3
212.6
210.3
209.2
230.4
217.4
215.0

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
101.0 75.8
236.8
24.9
135.4 110.3 85.1
217.9
24.6
169.9 144.8 119.6 94.4
199.0
24.3
198.2 178.3 153.1 128.0 102.8
187.8
24.3
196.0 176.5 151.3 126.1 101.0
187.0
24.2
110.0 81.7
242.9
24.9
147.2 118.9 90.6
223.6
24.7
184.4 156.1 127.8 99.5
204.2
24.4
203.0 192.2 163.9 135.7 107.4
192.7
24.3
200.8 190.3 162.0 133.7 105.4
191.9
24.3
119.1 87.7
249.1
25.0
159.0 127.5 96.1
229.3
24.8
198.8 167.4 136.0 104.6
209.4
24.5
207.8 206.2 174.8 143.3 111.9
197.6
24.4
205.5 204.1 172.7 141.3 109.8
196.7
24.4
166.1 132.5 98.8
234.9
25.0
207.6 173.9 140.3 106.6
214.6
24.7
212.6 211.8 178.2 144.5 110.9
202.4
24.6
210.3 209.5 175.9 142.3 108.6
201.6
24.6
173.3 137.4 101.6
240.5
25.2
216.3 180.4 144.6 108.7
219.7
24.9
217.4 217.4 181.5 145.7 109.8
207.3
24.8
215.0 215.0 179.1 143.3 107.4
206.4
24.8

90
122.5
156.4
190.3
187.8
187.0
142.6
172.0
201.3
192.7
191.9
162.8
187.5
209.4
197.6
196.7
196.6
214.6
202.4
201.6
205.7
219.7
207.3
206.4

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
97.3
72.0
131.2 106.0 80.8
165.1 139.9 114.7 89.5
187.8 170.7 145.5 120.3
187.0 166.7 141.5 116.3
106.7 78.2
143.5 115.0 86.6
180.3 151.8 123.4 94.9
192.7 185.3 157.5 128.4
191.9 181.0 153.4 124.1
116.1 84.4
155.8 124.1 92.3
195.5 163.8 132.0 100.3
197.6 197.6 169.4 136.4
196.7 195.3 165.3 131.8
162.8 129.0 95.2
204.1 170.3 136.5 102.7
202.4 202.4 171.1 136.7
201.6 200.8 167.9 133.2
169.9 134.0 98.1
212.7 176.8 141.0 105.1
207.3 207.3 172.8 136.9
206.4 206.4 170.5 134.7

65
95.1
91.1
99.9
95.6
104.7
100.1
102.9
99.4
101.0
98.8

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

45

505428-YTG-R-1114

YC300/NC300
Air on
Evaporator Coil
CFM

7500

8750

10000

11250

12500

7500

8750

10000

11250

12500

46

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

390.0
360.6
331.2
305.3
308.5
399.4
369.3
339.2
312.8
316.1
408.8
378.0
347.2
320.3
323.7
390.1
358.3
330.5
334.0
402.1
369.4
340.7
344.3

20.3
19.9
19.5
18.6
18.5
20.7
20.4
20.0
19.0
18.9
21.2
20.8
20.4
19.4
19.3
20.5
20.2
19.2
19.1
20.3
19.9
18.9
18.8

208.7
242.2
275.6
305.3
308.5
217.9
258.8
299.8
312.8
316.1
227.1
275.5
323.9
320.3
323.7
302.2
346.7
330.5
334.0
328.9
369.4
340.7
344.3

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

334.1
313.0
291.9
286.0
288.6
337.6
316.3
294.9
289.0
291.6
341.1
319.6
298.0
292.0
294.6
330.4
308.1
301.9
304.6
341.2
318.2
311.8
314.6

25.7
25.0
24.3
24.3
24.1
25.6
25.0
24.3
24.3
24.1
25.6
24.9
24.3
24.2
24.0
25.2
24.5
24.4
24.3
25.4
24.7
24.7
24.5

152.2
206.4
260.5
286.0
288.6
174.7
226.9
279.2
289.0
291.6
197.1
247.5
298.0
292.0
294.6
268.6
308.1
301.9
304.6
289.6
318.2
311.8
314.6

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
177.2 145.6
362.1
23.0
210.6 179.1 147.5
336.8
22.5
244.1 212.5 181.0 149.4
311.5
21.9
311.5 279.9 248.4 216.8 185.2
295.7
21.4
314.3 282.8 251.2 219.7 188.1
298.5
21.3
188.8 153.3
368.5
23.2
223.4 187.9 152.4
342.8
22.7
258.0 222.5 187.0 151.5
317.1
22.2
315.9 293.5 259.6 222.5 187.0
300.9
21.6
319.0 296.4 262.8 225.5 190.0
303.8
21.5
200.4 161.0
374.9
23.4
236.1 196.7 157.3
348.8
22.9
271.8 232.4 193.0 153.6
322.6
22.4
320.3 307.0 270.9 228.2 188.8
306.2
21.8
323.7 310.1 274.3 231.3 191.9
309.1
21.7
259.4 216.7 173.9
360.2
22.9
299.2 256.5 213.7 170.9
333.2
22.3
330.5 323.9 282.8 238.4 195.6
316.2
21.8
334.0 327.2 286.2 241.7 198.9
319.3
21.7
282.7 236.6 190.5
371.7
22.8
326.6 280.5 234.4 188.3
343.8
22.3
340.7 340.7 294.6 248.5 202.4
326.3
21.8
344.3 344.3 298.2 252.1 205.9
329.4
21.6
95°F
120.6 89.0
325.6
28.6
174.7 143.1 111.4
300.7
27.9
228.8 197.2 165.5 133.9
275.8
27.3
267.3 235.6 204.0 172.3 140.7
266.2
27.0
272.7 241.0 209.4 177.8 146.1
273.7
26.8
132.3 96.4
328.2
28.6
191.0 155.0 119.0
303.2
28.0
249.6 213.6 177.6 141.6
278.1
27.3
279.6 255.2 217.6 183.2 147.3
268.4
27.1
283.7 261.1 223.3 189.1 153.1
275.9
26.9
144.1 103.8
330.9
28.7
207.2 166.9 126.5
305.6
28.1
270.3 230.0 189.7 149.3
280.4
27.4
292.0 274.8 231.2 194.2 153.8
270.6
27.1
294.6 281.1 237.2 200.5 160.2
278.2
27.0
224.1 179.7 135.3
316.3
28.2
292.1 247.7 203.3 158.8
290.2
27.5
301.9 293.3 247.2 204.4 160.0
280.0
27.2
304.6 297.9 251.6 209.0 164.6
287.9
27.1
241.1 192.5 144.0
327.0
28.3
313.9 265.4 216.8 168.3
300.0
27.6
311.8 311.8 263.3 214.7 166.2
289.5
27.4
314.6 314.6 266.1 217.6 169.0
297.6
27.2

90
180.5
224.3
268.0
295.7
298.5
196.3
242.9
289.5
300.9
303.8
212.1
261.5
311.0
306.2
309.1
285.4
327.4
316.2
319.3
309.2
343.8
326.3
329.4
147.7
200.5
253.3
266.2
273.7
177.7
222.3
266.8
268.4
275.9
207.8
244.1
280.4
270.6
278.2
265.2
290.2
280.0
287.9
286.4
300.0
289.5
297.6

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
148.9 117.3
192.7 161.1 129.5
236.5 204.9 173.3 141.7
289.4 257.8 226.2 194.6
293.5 261.9 230.3 198.7
160.6 124.8
207.2 171.4 135.7
253.8 218.0 182.3 146.6
297.8 274.3 238.6 202.9
301.3 278.8 243.0 207.3
172.2 132.4
221.7 181.8 141.9
271.1 231.2 191.3 151.5
306.2 290.9 251.1 211.2
309.1 295.6 255.7 215.9
241.8 198.2 154.6
295.7 252.1 208.5 164.9
316.2 308.6 265.0 221.4
319.3 312.5 268.9 225.3
261.9 214.6 167.3
320.3 272.9 225.6 178.3
326.3 326.3 278.9 231.6
329.4 329.4 282.1 234.8
105°F
116.1 84.4
168.9 137.2 105.6
221.6 190.0 158.4 126.7
251.2 219.5 187.9 156.3
255.7 224.1 192.5 160.8
128.5 92.4
186.2 150.2 114.1
244.0 207.9 171.9 135.8
260.9 240.2 203.3 168.1
266.9 245.2 208.2 173.1
140.8 100.4
203.6 163.1 122.6
266.3 225.9 185.4 144.9
270.6 260.8 218.7 179.8
278.2 266.2 223.9 185.3
220.4 175.6 130.8
282.1 243.2 198.4 153.5
280.0 275.1 229.5 185.5
287.9 281.9 236.2 192.3
237.2 188.1 139.0
297.8 260.5 211.3 162.2
289.5 289.5 240.4 191.2
297.6 297.6 248.5 199.3

65
163.0
167.1
167.1
171.6
171.3
176.0
177.8
181.7
184.3
187.5
124.6
129.2
132.0
137.0
139.4
144.8
140.7
147.5
142.1
150.2

Johnson Controls Unitary Products

505428-YTG-R-1114

YC300/NC300 (Continued)
Air on
Evaporator Coil
CFM

7500

8750

10000

11250

12500

1

2

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

317.1
288.5
259.8
246.4
258.8
318.9
290.1
261.3
247.8
260.2
320.7
291.7
262.7
249.2
261.7
302.2
272.2
258.2
271.1
312.8
281.7
267.2
280.6

31.5
30.8
30.2
29.7
29.6
31.6
31.0
30.4
29.9
29.7
31.8
31.2
30.5
30.0
29.9
31.2
30.5
30.0
29.9
31.2
30.6
30.0
29.9

143.2
194.6
246.1
246.4
258.8
180.8
217.6
254.4
247.8
260.2
218.4
240.6
262.7
249.2
261.7
261.9
272.2
258.2
271.1
283.2
281.7
267.2
280.6

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
111.6 79.9
308.6
34.3
163.0 131.4 99.7
276.2
33.7
214.4 182.8 151.2 119.5
243.8
33.1
235.1 203.5 171.8 140.2 108.6
226.6
32.4
238.8 207.2 175.5 143.9 112.3
243.9
32.3
124.6 88.5
309.5
34.7
181.5 145.4 109.2
277.0
34.0
238.4 202.3 166.1 130.0
244.4
33.4
242.1 225.1 189.0 152.9 116.7
227.2
32.6
250.2 229.2 193.1 157.0 120.9
244.6
32.6
137.6 97.0
310.4
35.0
200.0 159.3 118.7
277.7
34.3
262.3 221.7 181.1 140.5
245.1
33.7
249.2 246.8 206.1 165.5 124.9
227.8
32.9
261.7 251.3 210.7 170.0 129.4
245.2
32.9
216.7 171.5 126.3
288.2
34.2
272.0 238.6 193.5 148.3
254.3
33.6
258.2 257.0 211.8 166.6 121.4
236.3
32.8
271.1 265.9 220.8 175.6 130.4
254.4
32.8
233.4 183.7 133.9
298.6
34.1
281.7 255.6 205.8 156.0
263.5
33.5
267.2 267.2 217.4 167.7 117.9
244.9
32.7
280.6 280.6 230.9 181.1 131.4
263.6
32.7

90
138.7
188.8
238.9
226.6
243.9
183.9
212.9
242.0
227.2
244.6
229.1
237.1
245.1
227.8
245.2
258.5
254.3
236.3
254.4
279.9
263.5
244.9
263.6

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
107.1 75.4
157.2 125.5 93.9
207.2 175.6 144.0 112.4
219.0 187.4 155.7 124.1
221.9 190.3 158.6 127.0
120.7 84.5
176.7 140.6 104.4
232.8 196.6 160.4 124.2
223.4 210.1 174.7 137.7
233.5 213.3 178.0 140.9
134.3 93.6
196.3 155.6 114.8
245.1 217.6 176.8 136.1
227.8 227.8 193.6 151.2
245.2 236.3 197.4 154.8
213.0 167.4 121.8
254.3 234.1 188.5 143.0
236.3 236.3 194.1 147.7
254.4 250.0 205.3 158.9
229.6 179.2 128.8
263.5 250.6 200.3 149.9
244.9 244.9 194.5 144.2
263.6 263.6 213.2 162.9

65
92.5
95.4
101.5
104.7
110.4
114.1
102.1
113.3
93.8
112.5

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

47

505428-YTG-R-1114

Condenser Only Cooling Capacities
Condenser Only Ratings
Suction Press.
Temperature of Air on Condenser Coil °F
and
Model
65
75
85
95
105
115
Corresponding Temp.
PSIG
°F
MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER

YC090

YC120

YD120

YC150

YD150

YC180

YD180

YC240

YD240

YC300

48

108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157
108
120
131
143
157

35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55
35
40
45
50
55

78
88
98
108
118
102
120
138
155
173
106
120
136
152
168
190
190
190
190
190
132
149
166
183
200
169
184
198
213
227
160
179
199
218
238
215
244
274
303
332
210
237
264
291
317
271
310
348
387
425

4.8
5.0
5.1
5.3
5.4
6.5
6.6
6.7
6.9
7.0
6.4
6.5
6.7
6.8
6.9
8.2
8.5
8.8
9.1
9.3
8.4
8.6
8.7
8.9
9.1
9.7
10.1
10.4
10.7
11.0
10.1
10.2
10.3
10.5
10.6
12.5
13.1
13.6
14.2
14.8
12.4
12.7
13.1
13.5
13.8
17.3
17.8
18.4
18.9
19.5

16.1
17.6
19.1
20.5
21.8
15.8
18.1
20.4
22.6
24.7
16.3
18.4
20.5
22.5
24.4
23.2
22.4
21.7
21.0
20.3
15.7
17.4
19.0
20.5
21.9
17.4
18.2
19.1
19.8
20.6
15.9
17.6
19.2
20.8
22.4
17.2
18.7
20.1
21.4
22.5
17.0
18.6
20.1
21.6
22.9
15.7
17.4
19.0
20.4
21.8

75
84
94
103
112
95
111
128
145
161
96
111
126
142
157
190
190
190
190
190
124
140
156
173
189
153
170
186
203
219
149
168
186
205
224
200
228
257
286
315
196
221
247
273
299
245
282
320
357
395

5.3
5.5
5.6
5.8
5.9
7.3
7.4
7.5
7.6
7.7
7.2
7.3
7.4
7.5
7.7
9.1
9.4
9.6
9.8
10.1
9.2
9.4
9.6
9.8
10.0
10.8
11.0
11.3
11.6
11.9
11.0
11.2
11.3
11.5
11.7
13.6
14.2
14.8
15.4
15.9
13.6
14.0
14.3
14.7
15.0
18.6
19.3
20.0
20.6
21.3

14.2
15.5
16.7
17.8
18.9
13.1
15.1
17.1
19.0
20.8
13.4
15.2
17.0
18.7
20.4
20.8
20.3
19.8
19.3
18.9
13.5
14.9
16.3
17.6
18.8
14.3
15.4
16.4
17.5
18.4
13.6
15.0
16.5
17.8
19.2
14.7
16.1
17.4
18.6
19.7
14.3
15.8
17.3
18.6
19.9
13.2
14.6
16.0
17.3
18.5

72
81
89
98
107
89
104
119
134
149
88
103
117
132
146
113
127
140
154
168
119
133
148
163
177
135
154
172
191
210
141
158
175
192
209
185
213
240
268
296
184
208
231
255
279
215
253
290
328
365

5.8
5.9
6.1
6.2
6.4
8.0
8.2
8.3
8.4
8.5
7.9
8.0
8.2
8.3
8.5
9.8
10.1
10.3
10.6
10.9
9.9
10.2
10.4
10.7
10.9
11.5
11.9
12.2
12.6
12.9
11.6
11.9
12.2
12.5
12.8
14.8
15.3
15.9
16.4
17.0
15.1
15.4
15.7
15.9
16.2
20.0
20.7
21.4
22.2
22.9

12.4
13.6
14.7
15.7
16.7
11.1
12.8
14.4
16.0
17.5
11.2
12.8
14.3
15.8
17.2
11.5
12.6
13.6
14.5
15.4
11.9
13.1
14.2
15.2
16.2
11.7
13.0
14.1
15.2
16.2
12.2
13.3
14.4
15.4
16.4
12.5
13.9
15.2
16.4
17.5
12.2
13.5
14.8
16.0
17.2
10.8
12.2
13.6
14.8
16.0

68
76
85
93
102
84
97
110
123
136
82
95
108
120
133
105
118
131
144
156
109
123
136
149
163
125
142
160
178
196
136
151
166
180
195
171
197
223
249
275
173
195
217
239
261
201
236
271
306
340

6.5
6.7
6.8
6.9
7.1
9.0
9.1
9.3
9.4
9.5
8.8
9.0
9.1
9.3
9.4
11.1
11.3
11.5
11.8
12.0
11.0
11.2
11.5
11.7
12.0
12.7
13.0
13.4
13.7
14.0
12.8
13.1
13.4
13.8
14.1
16.3
16.9
17.4
18.0
18.6
16.7
17.0
17.3
17.6
17.9
22.5
23.1
23.7
24.2
24.8

10.3
11.4
12.4
13.4
14.4
9.3
10.6
11.9
13.2
14.4
9.3
10.5
11.8
13.0
14.1
9.5
10.4
11.3
12.2
13.0
9.9
10.9
11.8
12.7
13.6
9.8
10.9
12.0
13.0
14.0
10.6
11.5
12.3
13.1
13.9
10.5
11.7
12.8
13.8
14.8
10.4
11.5
12.6
13.6
14.6
9.0
10.2
11.4
12.6
13.7

61
70
79
87
96
78
90
102
114
126
73
85
97
109
121
102
113
123
134
145
103
116
128
141
153
116
133
149
166
182
127
141
154
168
181
155
180
204
229
253
157
179
201
223
245
193
223
253
283
313

7.6
7.7
7.8
8.0
8.1
10.3
10.4
10.5
10.6
10.7
9.8
10.0
10.2
10.4
10.6
12.4
12.6
12.8
13.0
13.2
12.4
12.7
13.0
13.3
13.5
14.5
14.8
15.1
15.4
15.7
14.5
14.8
15.1
15.4
15.7
18.2
18.8
19.4
20.0
20.6
18.9
19.2
19.5
19.8
20.1
24.9
25.6
26.3
27.1
27.8

8.1
9.1
10.0
10.9
11.8
7.6
8.7
9.7
10.8
11.8
7.5
8.5
9.5
10.5
11.4
8.2
8.9
9.6
10.3
10.9
8.3
9.1
9.9
10.6
11.3
8.0
9.0
9.9
10.7
11.6
8.8
9.5
10.2
10.9
11.5
8.5
9.6
10.5
11.4
12.3
8.3
9.4
10.3
11.3
12.2
7.8
8.7
9.6
10.4
11.2

55
64
72
81
90
73
84
94
105
115
65
78
90
103
115
98
108
118
127
137
94
107
119
131
144
104
121
137
153
169
121
133
145
157
169
139
163
186
210
233
137
161
184
207
230
188
213
238
263
288

8.6
8.7
8.9
9.0
9.2
11.4
11.5
11.6
11.7
11.8
11.1
11.3
11.5
11.6
11.8
13.8
14.1
14.4
14.6
14.9
13.6
13.9
14.3
14.6
14.9
16.0
16.4
16.7
17.0
17.3
16.3
16.6
16.8
17.1
17.4
19.7
20.5
21.2
21.9
22.6
21.2
21.4
21.7
22.0
22.3
26.9
27.9
28.8
29.7
30.7

6.4
7.3
8.2
9.0
9.8
6.4
7.3
8.1
8.9
9.7
5.9
6.9
7.9
8.8
9.8
7.1
7.7
8.2
8.7
9.2
6.9
7.7
8.3
9.0
9.6
6.5
7.4
8.2
9.0
9.8
7.4
8.0
8.6
9.2
9.7
7.0
7.9
8.8
9.6
10.3
6.5
7.5
8.5
9.4
10.4
7.0
7.6
8.3
8.8
9.4

Johnson Controls Unitary Products

505428-YTG-R-1114

Heat Pump and Air Handling Cooling Capacities
PC090/NC090 Cooling Capacities
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

2250

2625

3000

3375

3750

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

112.8
104.8
96.7
89.0
88.9
117.0
108.6
100.3
92.3
92.2
121.1
112.5
103.8
95.6
95.4
114.6
105.7
97.4
97.2
116.6
107.7
99.1
99.0

5.9
5.8
5.7
5.5
5.6
5.9
5.8
5.7
5.6
5.6
5.9
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.6

54.5
68.7
82.9
89.0
88.9
58.7
74.8
90.9
92.3
92.2
63.0
80.9
98.9
95.6
95.4
88.6
103.3
97.4
97.2
96.3
107.7
99.1
99.0

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

101.2
93.9
86.6
79.8
80.3
104.3
96.8
89.3
82.3
82.8
107.5
99.7
92.0
84.7
85.3
102.7
94.8
87.3
87.8
105.7
97.5
89.8
90.4

7.2
7.1
7.0
6.9
6.8
7.3
7.1
7.0
6.9
6.9
7.3
7.2
7.0
6.9
6.9
7.2
7.1
6.9
6.9
7.2
7.1
7.0
6.9

49.3
63.9
78.6
79.8
80.3
55.2
70.2
85.3
82.3
82.8
61.0
76.5
92.0
84.7
85.3
83.2
94.8
87.3
87.8
89.9
97.5
89.8
90.4

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
44.9
35.3
107.0
6.5
59.1
49.5 40.0
99.3
6.4
73.4
63.8 54.2 44.6
91.7
6.3
89.0
80.5 70.9 61.3 51.7
84.4
6.2
88.9
80.5 70.9 61.4 51.8
84.6
6.2
48.7
37.9
110.7
6.6
64.0
53.2 42.5
102.7
6.5
79.3
68.5 57.8 47.0
94.8
6.3
92.3
86.5 76.2 64.9 54.1
87.3
6.2
92.2
86.6 76.3 65.0 54.2
87.5
6.2
52.6
40.6
114.3
6.6
68.9
56.9 45.0
106.1
6.5
85.3
73.3 61.3 49.3
97.9
6.4
95.6
92.5 81.5 68.6 56.6
90.2
6.3
95.4
92.6 81.7 68.6 56.6
90.4
6.2
75.6
62.6 49.6
108.6
6.5
93.6
80.6 67.6 54.6
100.3
6.4
97.4
95.8 83.3 69.8 56.8
92.3
6.3
97.2
95.8 83.3 69.7 56.7
92.5
6.3
82.3
68.3 54.2
111.2
6.5
101.9 87.9 73.8 59.8
102.6
6.4
99.1
99.1 85.1 71.0 57.0
94.5
6.3
99.0
99.0 84.9 70.9 56.8
94.7
6.3
95°F
39.9
30.6
100.5
8.0
54.6
45.2 35.8
90.2
7.9
69.2
59.8 50.4 41.0
79.9
7.8
79.8
72.5 63.1 53.7 44.4
74.8
7.7
80.3
70.9 61.5 52.1 42.8
74.9
7.7
43.8
33.1
103.7
8.0
59.6
49.0 38.3
93.0
8.0
75.4
64.8 54.2 43.5
82.4
7.9
82.3
78.6 67.5 57.4 46.7
77.2
7.7
82.8
76.9 65.7 55.6 45.0
77.2
7.7
47.6
35.7
106.8
8.1
64.6
52.8 40.9
95.9
8.0
81.7
69.8 57.9 46.1
84.9
7.9
84.7
84.7 71.9 61.0 49.1
79.6
7.8
85.3
82.9 69.9 59.1 47.2
79.6
7.7
70.3
57.4 44.6
98.8
8.0
88.9
76.0 63.1 50.2
87.5
7.9
87.3
87.3 73.9 61.5 48.6
82.0
7.8
87.8
86.6 73.2 60.8 48.0
82.0
7.8
76.0
62.1 48.2
101.7
8.0
96.1
82.2 68.3 54.4
90.1
7.9
89.8
89.8 75.9 62.0 48.1
84.4
7.8
90.4
90.4 76.5 62.6 48.7
84.4
7.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
85°F
51.9
42.4 32.9
66.3
56.8 47.3 37.9
80.8
71.3 61.8 52.3 42.8
84.4
84.4 76.5 67.0 57.5
84.6
84.6 75.7 66.2 56.8
57.0
46.2 35.5
72.5
61.8 51.1 40.4
88.1
77.4 66.7 56.0 45.3
87.3
87.3 82.6 71.9 61.1
87.5
87.5 81.7 71.0 60.3
62.0
50.1 38.1
78.7
66.8 54.9 42.9
95.4
83.5 71.6 59.6 47.7
90.2
90.2 88.6 76.7 64.8
90.4
90.4 87.7 75.8 63.9
85.9
73.0 60.0 47.1
99.0
91.3 78.3 65.4 52.4
92.3
92.3 91.6 78.6 65.7
92.5
92.5 91.2 78.3 65.3
93.1
79.2 65.2 51.2
102.6 99.0 85.1 71.1 57.1
94.5
94.5 94.5 80.5 66.5
94.7
94.7 94.7 80.7 66.7
105°F
59.5
50.1 40.7
67.7
58.3 48.9 39.4
75.8
66.4 57.0 47.6 38.2
74.8
74.8 67.3 57.9 48.5
74.9
74.9 65.7 56.2 46.8
68.8
55.1 44.4
74.6
63.9 53.3 42.6
80.4
72.8 62.1 51.4 40.8
77.2
77.2 73.3 62.4 52.0
77.2
77.2 71.5 60.6 50.2
78.1
60.0 48.1
81.5
69.6 57.7 45.8
84.9
79.1 67.2 55.3 43.4
79.6
79.6 79.3 66.9 55.5
79.6
79.6 77.4 64.9 53.6
87.6
76.1 63.2 50.2
87.5
84.2 73.6 60.6 47.7
82.0
82.0 81.8 68.6 55.9
82.0
82.0 80.9 67.7 55.0
93.8
82.7 68.7 54.7
90.1
89.4 79.9 65.9 52.0
84.4
84.4 84.4 70.4 56.4
84.4
84.4 84.4 70.5 56.5

65
48.0
47.3
50.4
49.6
52.8
51.9
52.7
52.3
52.6
52.8
39.0
37.4
41.3
39.5
43.6
41.6
43.0
42.1
42.4
42.5

49

505428-YTG-R-1114

PC090/NC090 Cooling Capacities (Continued)
Air on
Evaporator Coil
CFM

2250

2625

3000

3375

3750

1

2

50

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

99.8
86.5
73.1
69.9
69.5
103.0
89.2
75.5
72.1
71.7
106.2
92.0
77.8
74.4
73.9
94.8
80.2
76.7
76.2
97.7
82.6
79.0
78.5

8.8
8.7
8.7
8.5
8.5
8.8
8.8
8.7
8.6
8.6
8.9
8.8
8.7
8.6
8.6
8.8
8.8
8.6
8.6
8.8
8.8
8.7
8.6

69.7
71.4
73.1
69.9
69.5
82.4
78.9
75.5
72.1
71.7
95.1
86.4
77.8
74.4
73.9
92.1
80.2
76.7
76.2
97.7
82.6
79.0
78.5

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Capacity1
Return Dry Bulb (°F)
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
60.3
50.9
99.1
9.6
62.0
52.6 43.1
82.7
9.5
63.7
54.2 44.8 35.4
66.4
9.5
69.9
62.0 52.6 43.2 33.7
64.9
9.4
69.5
60.4 50.9 41.5 32.1
64.1
9.4
66.4
55.7
102.3
9.6
68.2
57.6 46.9
85.4
9.6
70.1
59.4 48.7 38.0
68.5
9.6
72.1
67.9 57.3 46.6 35.9
67.0
9.4
71.7
66.1 55.4 44.8 34.1
66.2
9.4
72.5
60.5
105.6
9.7
74.5
62.6 50.6
88.1
9.6
76.5
64.6 52.6 40.7
70.7
9.6
74.4
73.8 61.9 50.0 38.0
69.2
9.5
73.9
71.9 59.9 48.0 36.1
68.3
9.5
81.9
68.9 55.9
90.9
9.7
79.6
71.1 58.1 45.1
72.9
9.6
76.7
76.4 63.4 50.4 37.4
71.3
9.5
76.2
75.2 62.2 49.2 36.2
70.4
9.5
89.3
75.2 61.1
93.7
9.7
82.6
77.7 63.6 49.5
75.2
9.6
79.0
79.0 64.9 50.8 36.7
73.5
9.5
78.5
78.5 64.4 50.3 36.3
72.6
9.5

Sensible Capacity (MBh)
Return Dry Bulb (°F)
90
85
80
75
70
125°F
79.9
70.5 61.0
75.2
65.7 56.3 46.8
66.4
60.9 51.5 42.0 32.6
64.9
64.9 56.8 47.3 37.9
64.1
64.1 55.1 45.6 36.2
92.7
77.7 67.0
83.3
72.6 61.9 51.2
68.5
67.4 56.7 46.0 35.3
67.0
67.0 62.6 52.1 41.2
66.2
66.2 60.7 50.3 39.3
105.6 84.9 73.0
88.1
79.4 67.5 55.5
70.7
70.7 62.0 50.0 38.0
69.2
69.2 68.4 56.9 44.5
68.3
68.3 66.4 54.9 42.4
90.9
87.7 74.6 61.5
72.9
72.9 68.7 55.6 42.5
71.3
71.3 71.0 58.1 44.8
70.4
70.4 69.5 56.7 43.3
93.7
93.7 81.8 67.6
75.2
75.2 75.2 61.2 47.0
73.5
73.5 73.5 59.3 45.2
72.6
72.6 72.6 58.4 44.2

65
28.4
26.7
30.5
28.6
32.5
30.5
31.7
30.3
31.0
30.0

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

505428-YTG-R-1114

PC120/NC120
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

3000

3500

4000

4500

5000

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

140.5
133.6
126.6
120.2
121.8
147.3
140.0
132.8
126.0
127.7
154.1
146.5
138.9
131.8
133.6
148.2
140.5
133.4
135.2
150.0
142.2
134.9
136.7

7.5
7.5
7.4
7.4
7.3
7.7
7.6
7.6
7.6
7.5
7.8
7.8
7.8
7.8
7.6
7.7
7.7
7.7
7.5
7.6
7.5
7.5
7.4

70.2
87.5
104.8
120.2
121.8
74.8
93.9
112.9
126.0
127.7
79.4
100.2
121.1
131.8
133.6
110.0
131.6
133.4
135.2
119.7
142.2
134.9
136.7

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

128.0
121.0
114.1
106.3
112.4
133.6
126.3
119.0
111.0
117.3
139.1
131.6
124.0
115.6
122.2
133.5
125.8
117.3
124.0
135.4
127.6
119.0
125.8

9.7
9.6
9.5
9.3
9.5
9.8
9.7
9.6
9.4
9.6
9.9
9.8
9.7
9.5
9.7
9.7
9.6
9.5
9.6
9.6
9.5
9.4
9.5

59.9
81.3
102.8
106.3
112.4
68.0
90.7
113.4
111.0
117.3
76.2
100.1
124.0
115.6
122.2
106.3
125.8
117.3
124.0
112.5
127.6
119.0
125.8

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
58.2
46.2
134.2
8.6
75.5
63.5
51.5
127.3
8.5
92.8
80.8
68.9
56.9
120.3
8.5
120.2 107.7 95.7
83.8 71.8
113.2
8.4
123.0 114.5 102.5 90.5 78.6
117.1
8.4
62.4
49.1
140.4
8.7
80.6
67.3
54.1
133.2
8.7
98.8
85.5
72.3
59.0
125.9
8.6
126.0 114.2 101.0 87.6 74.4
118.5
8.5
128.3 121.4 108.7 94.9 81.6
122.5
8.5
66.6
52.0
146.6
8.9
85.7
71.1
56.6
139.0
8.8
104.8 90.2
75.7
61.1
131.5
8.7
131.8 120.6 106.3 91.5 76.9
123.7
8.7
133.6 128.3 114.8 99.2 84.6
127.9
8.6
94.1
78.1
62.2
140.9
8.7
115.2 99.3
83.4
67.5
133.2
8.6
133.4 127.8 112.0 95.9 80.0
125.3
8.6
135.2 132.5 117.2 100.7 84.8
129.6
8.6
102.4 85.1
67.9
142.7
8.6
125.6 108.3 91.1
73.8
134.9
8.5
134.9 134.9 117.6 100.4 83.1
127.0
8.5
136.7 136.7 119.5 102.2 84.9
131.3
8.5
95°F
47.4
34.9
120.6
10.9
68.8
56.3
43.8
113.1
10.8
90.3
77.8
65.3
52.8
105.6
10.7
106.3 94.7
82.2
69.7 57.2
101.1
10.6
111.3 98.8
86.3
73.8 61.3
104.8
10.7
52.7
38.3
126.1
11.0
76.3
61.9
47.4
118.3
10.9
99.8
85.4
71.0
56.5
110.4
10.8
111.0 103.9 89.4
75.1 60.6
105.7
10.7
116.7 108.4 93.4
79.6 65.1
109.5
10.8
58.1
41.7
131.6
11.1
83.7
67.4
51.0
123.4
11.0
109.4 93.0
76.6
60.3
115.2
10.9
115.6 113.2 96.5
80.5 64.1
110.3
10.8
122.2 118.1 100.6 85.4 69.0
114.3
10.9
88.9
71.5
54.0
124.9
10.9
116.1 98.6
81.2
63.8
116.6
10.8
117.3 116.1 98.5
81.2 63.8
111.6
10.7
124.0 122.0 104.0 87.1 69.7
115.7
10.8
94.0
75.5
57.0
126.3
10.9
122.8 104.3 85.8
67.3
118.0
10.8
119.0 119.0 100.5 82.0 63.5
112.9
10.7
125.8 125.8 107.3 88.8 70.3
117.0
10.7

90
65.0
84.4
103.8
113.2
117.1
71.4
92.3
113.2
118.5
122.5
77.8
100.2
122.5
123.7
127.9
108.1
128.7
125.3
129.6
116.1
134.9
127.0
131.3
59.2
79.6
100.0
101.1
104.8
69.7
88.6
107.6
105.7
109.5
80.1
97.7
115.2
110.3
114.3
104.6
116.6
111.6
115.7
111.5
118.0
112.9
117.0

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
52.8
40.6
72.2
59.9
47.7
91.5
79.3
67.1 54.8
113.2 101.2 88.9 76.7
117.1 106.6 94.4 82.2
57.6
43.7
78.4
64.6
50.7
99.3
85.5
71.6 57.8
118.5 109.0 95.2 81.3
122.5 114.9 101.1 87.2
62.3
46.9
84.7
69.2
53.8
107.1 91.6
76.2 60.7
123.7 116.9 101.4 86.0
127.9 123.2 107.7 92.3
91.5
74.8
58.1
115.6 99.0
82.3 65.6
125.3 121.9 105.3 88.6
129.6 127.2 110.6 93.9
98.2
80.3
62.5
124.2 106.3 88.4 70.5
127.0 127.0 109.1 91.2
131.3 131.3 113.4 95.5
105°F
46.6
34.0
67.0
54.4
41.8
87.4
74.7
62.1 49.5
101.1 90.6
78.0 65.4
104.2 92.7
80.1 67.5
51.8
37.3
74.1
59.6
45.1
96.5
82.0
67.5 53.0
105.7 99.3
84.8 70.3
109.3 101.6 86.9 72.6
56.9
40.5
81.3
64.9
48.5
105.6 89.2
72.8 56.4
110.3 108.1 91.6 75.3
114.3 110.6 93.6 77.8
86.9
69.3
51.7
110.6 95.3
77.7 60.1
111.6 110.5 92.8 75.3
115.7 113.8 95.9 78.6
92.6
73.8
55.0
115.5 101.5 82.6 63.8
112.9 112.9 94.1 75.2
117.0 117.0 98.2 79.4

65
64.5
69.9
67.5
73.4
70.5
76.8
71.9
77.2
73.3
77.6
52.8
54.9
55.8
58.1
58.9
61.4
57.6
61.0
56.4
60.5

51

505428-YTG-R-1114

PC120/NC120 (Continued)
Air on
Evaporator Coil
CFM

3000

3500

4000

4500

5000

1

2

52

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

113.3
105.2
97.2
95.9
97.1
118.7
110.2
101.8
100.4
101.8
124.1
115.3
106.4
105.0
106.4
116.3
107.3
105.9
107.3
117.2
108.3
106.8
108.2

12.1
12.0
11.9
11.8
11.8
12.2
12.1
12.0
11.9
12.0
12.3
12.2
12.1
12.1
12.1
12.1
12.0
12.0
12.0
12.1
12.0
11.9
11.9

58.5
77.8
97.2
95.9
97.1
71.3
86.5
101.8
100.4
101.8
84.0
95.2
106.4
105.0
106.4
102.8
107.3
105.9
107.3
110.4
108.3
106.8
108.2

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Capacity1
Return Dry Bulb (°F)
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
45.8
33.1
105.9
13.2
65.1
52.4
39.7
97.3
13.2
84.4
71.7
59.0
46.3
88.7
13.1
95.9
86.5
73.8
61.1 48.4
90.6
13.1
97.1
86.6
73.9
61.2 48.4
89.5
13.0
50.8
36.2
111.3
13.4
72.0
57.4
42.8
102.2
13.3
93.1
78.5
64.0
49.4
93.2
13.2
100.4 94.8
80.2
65.6 51.0
95.2
13.2
101.8 94.8
80.3
65.7 51.1
94.0
13.2
55.8
39.4
116.6
13.5
78.8
62.4
45.9
107.1
13.4
101.8 85.4
68.9
52.5
97.7
13.3
105.0 103.0 86.6
70.1 53.7
99.7
13.3
106.4 103.1 86.7
70.2 53.8
98.5
13.3
85.0
67.2
49.4
107.6
13.3
105.0 92.0
74.2
56.4
98.1
13.3
105.9 104.9 87.1
69.3 51.5
100.2
13.2
107.3 105.7 87.9
70.1 52.3
98.9
13.2
91.2
72.0
52.9
108.1
13.3
108.3 98.6
79.5
60.3
98.6
13.2
106.8 106.8 87.6
68.5 49.3
100.7
13.2
108.2 108.2 89.0
69.9 50.7
99.4
13.1

90
57.8
76.1
88.7
90.6
89.5
72.9
84.4
93.2
95.2
94.0
88.0
92.8
97.7
99.7
98.5
101.0
98.1
100.2
98.9
108.1
98.6
100.7
99.4

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
45.0
32.1
63.2
50.4
37.6
81.5
68.7
55.8 43.0
90.6
82.5
69.6 56.8
89.5
80.5
67.7 54.8
49.8
35.2
69.8
55.1
40.5
89.8
75.1
60.4 45.8
95.2
90.2
75.6 60.9
94.0
88.1
73.7 58.8
54.6
38.2
76.3
59.9
43.4
97.7
81.5
65.1 48.6
99.7
97.9
81.6 65.0
98.5
95.6
79.7 62.7
83.1
65.1
47.1
98.1
88.7
70.7 52.7
100.2 99.3
81.4 63.3
98.9
97.5
79.8 61.5
89.8
70.3
50.8
98.6
95.8
76.3 56.8
100.7 100.7 81.2 61.7
99.4
99.4
79.9 60.4

65
43.9
42.0
46.2
44.1
48.5
46.2
45.4
43.6
42.2
40.9

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

505428-YTG-R-1114

PC180/NC180
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

223.0
209.3
195.7
176.7
179.6
229.0
215.0
200.9
181.4
184.5
235.0
220.6
206.2
186.2
189.3
223.2
208.6
188.4
191.6
225.9
211.1
190.6
193.8

12.5
12.3
12.1
11.8
11.8
12.6
12.4
12.2
11.8
11.9
12.6
12.4
12.2
11.9
11.9
12.5
12.3
11.9
12.0
12.6
12.4
12.0
12.1

104.1
134.7
165.2
176.7
179.6
113.8
147.9
181.9
181.4
184.5
123.5
161.0
198.5
186.2
189.3
170.5
204.8
188.4
191.6
179.9
211.1
190.6
193.8

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

210.5
192.4
174.4
162.0
166.6
213.8
195.5
177.2
164.7
169.2
217.2
198.6
180.0
167.3
171.9
202.8
183.8
170.8
175.6
207.0
187.6
174.3
179.2

15.1
14.9
14.6
14.3
14.4
15.2
14.9
14.6
14.4
14.4
15.2
14.9
14.6
14.4
14.4
15.0
14.7
14.4
14.5
15.0
14.7
14.4
14.5

105.4
131.3
157.1
162.0
166.6
115.9
142.2
168.6
164.7
169.2
126.3
153.1
180.0
167.3
171.9
166.5
183.8
170.8
175.6
179.8
187.6
174.3
179.2

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
85.2
66.4
216.7
13.8
115.8 97.0
78.1
200.9
13.6
146.4 127.6 108.7 89.9
185.0
13.4
176.7 152.0 133.2 114.3 95.5
169.4
13.0
179.6 159.1 140.3 121.4 102.6
173.1
13.1
93.3
71.8
221.4
13.9
126.3 104.8 83.3
205.2
13.6
159.4 137.8 116.3 94.8
189.1
13.4
181.4 164.3 143.6 121.3 99.8
173.0
13.1
184.5 171.9 151.4 128.9 107.4
176.9
13.1
101.4 77.2
226.1
13.9
136.9 112.7 88.5
209.6
13.7
172.3 148.1 123.9 99.8
193.1
13.4
186.2 176.7 154.1 128.3 104.1
176.7
13.1
189.3 184.8 162.6 136.4 112.2
180.6
13.2
144.3 118.1 91.9
213.0
13.7
181.5 155.3 129.1 102.9
196.2
13.5
188.4 183.6 158.3 131.3 105.1
179.6
13.2
191.6 189.3 164.1 136.9 110.7
183.6
13.2
151.7 123.5 95.3
216.4
13.8
190.7 162.5 134.3 106.1
199.4
13.5
190.6 190.6 162.4 134.2 106.0
182.5
13.2
193.8 193.8 165.6 137.4 109.2
186.5
13.3
95°F
86.5
67.6
192.8
16.7
112.4 93.4
74.5
177.2
16.5
138.2 119.3 100.4 81.4
161.6
16.3
162.0 150.5 131.6 112.6 93.7
150.1
16.0
166.6 149.8 130.8 111.9 93.0
155.1
16.1
93.2
71.6
196.5
16.7
120.6 99.0
77.3
180.6
16.5
148.0 126.3 104.7 83.1
164.7
16.3
164.7 159.4 136.9 116.1 94.5
153.0
16.1
169.2 158.6 136.0 115.3 93.7
158.1
16.1
99.9
75.6
200.2
16.8
128.8 104.5 80.1
184.1
16.5
157.7 133.4 109.0 84.7
167.9
16.3
167.3 168.3 142.3 119.6 95.3
155.9
16.1
171.9 167.5 141.1 118.8 94.5
161.1
16.1
139.9 113.4 86.8
187.4
16.6
171.3 144.7 118.2 91.6
170.9
16.4
170.8 171.3 143.9 118.2 91.6
158.7
16.1
175.6 173.3 145.8 120.2 93.6
164.0
16.2
151.0 122.2 93.5
190.7
16.6
184.9 156.1 127.3 98.5
173.9
16.4
174.3 174.3 145.5 116.7 87.9
161.5
16.2
179.2 179.2 150.4 121.6 92.8
166.8
16.2

90
104.7
133.0
161.2
169.4
173.1
114.8
145.0
175.2
173.0
176.9
124.9
157.1
189.3
176.7
180.6
168.5
194.3
179.6
183.6
179.9
199.4
182.5
186.5
98.9
125.6
152.4
150.1
155.1
114.1
137.1
160.1
153.0
158.1
129.3
148.6
167.9
155.9
161.1
160.8
170.9
158.7
164.0
173.1
173.9
161.5
166.8

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
85.9
67.0
114.1 95.2
76.3
142.3 123.4 104.5 85.7
169.4 151.2 132.4 113.5
173.1 154.4 135.5 116.7
93.3
71.7
123.5 101.9 80.3
153.7 132.1 110.5 88.9
173.0 161.9 140.3 118.7
176.9 165.3 143.7 122.1
100.6 76.4
132.8 108.6 84.3
165.0 140.8 116.5 92.2
176.7 172.5 148.2 124.0
180.6 176.1 151.8 127.6
142.1 115.7 89.3
176.4 150.0 123.6 97.3
179.6 177.5 151.1 124.7
183.6 181.3 154.9 128.5
151.4 122.9 94.4
187.8 159.3 130.8 102.3
182.5 182.5 154.0 125.5
186.5 186.5 158.0 129.5
105°F
80.0
61.1
106.7 87.8
68.9
133.5 114.6 95.7
76.8
150.1 142.4 123.5 104.6
155.1 137.9 119.0 100.1
86.9
65.3
115.5 93.8
72.2
144.1 122.4 100.8 79.2
153.0 152.2 130.1 108.9
158.1 147.3 125.2 104.1
93.8
69.4
124.2 99.9
75.5
154.7 130.3 106.0 81.6
155.9 162.0 136.8 113.2
161.1 156.7 131.4 108.0
134.3 107.7 81.1
163.6 140.5 113.9 87.3
158.7 161.7 134.7 108.6
164.0 161.8 134.7 108.6
144.3 115.5 86.7
172.5 150.7 121.9 93.1
161.5 161.5 132.7 103.9
166.8 166.8 138.1 109.3

65
94.6
97.8
97.1
100.6
99.7
103.3
98.3
102.2
97.0
101.0
85.7
81.2
87.3
82.4
88.9
83.7
82.0
82.1
75.1
80.5

53

505428-YTG-R-1114

PC180/NC180 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

54

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

175.1
162.0
148.8
138.1
143.6
179.2
165.7
152.3
141.3
146.9
183.2
169.5
155.8
144.5
150.2
171.9
158.0
146.6
152.4
174.3
160.2
148.6
154.5

18.3
18.1
18.0
17.8
17.8
18.3
18.1
18.0
17.8
17.8
18.3
18.1
18.0
17.8
17.9
18.2
18.0
17.8
17.9
18.2
18.1
17.9
18.0

92.4
120.0
147.6
138.1
143.6
112.3
132.0
151.7
141.3
146.9
132.3
144.0
155.8
144.5
150.2
155.2
158.0
146.6
152.4
166.3
160.2
148.6
154.5

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
73.5
54.6
157.4
19.9
101.1 82.2
63.3
146.7
19.8
128.7 109.8 91.0
72.1
136.1
19.6
138.1 134.4 115.5 96.6
77.7
126.2
19.5
143.6 126.1 107.2 88.3
69.4
132.1
19.6
80.6
58.9
161.8
19.9
110.4 88.7
67.1
150.8
19.8
140.2 118.6 96.9
75.3
139.9
19.6
141.3 145.0 123.4 101.7 80.1
129.7
19.5
146.9 136.1 114.4 92.8
71.1
135.7
19.6
87.6
63.3
166.2
19.9
119.6 95.3
70.9
154.9
19.8
151.6 127.3 102.9 78.5
143.6
19.6
144.5 155.7 131.3 106.9 82.5
133.2
19.5
150.2 146.0 121.6 97.3
72.9
139.4
19.6
128.6 102.0 75.4
156.4
19.8
155.9 136.3 109.7 83.1
145.1
19.7
146.6 152.1 125.6 99.0
72.4
134.5
19.5
152.4 150.3 123.7 97.1
70.5
140.8
19.6
137.5 108.8 80.0
158.0
19.9
160.2 145.3 116.5 87.7
146.5
19.8
148.6 148.6 119.8 91.0
62.3
135.8
19.6
154.5 154.5 125.7 96.9
68.1
142.2
19.7

90
85.8
114.3
136.1
126.2
132.1
110.6
126.9
139.9
129.7
135.7
135.3
139.5
143.6
133.2
139.4
149.5
145.1
134.5
140.8
158.0
146.5
135.8
142.2

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
67.0
48.1
95.5
76.6
57.8
124.0 105.1 86.3
67.4
126.2 126.2 107.5 88.6
132.1 114.2 95.4
76.5
74.3
52.6
105.3 83.6
62.0
136.3 114.7 93.0
71.4
129.7 129.7 116.6 94.6
135.7 124.8 103.6 81.5
81.5
57.1
115.1 90.6
66.2
143.6 124.2 99.8
75.4
133.2 133.2 125.8 100.5
139.4 135.3 111.9 86.5
122.9 96.3
69.7
145.1 132.0 105.4 78.8
134.5 134.5 116.4 89.4
140.8 138.8 112.7 85.5
130.8 102.0 73.2
146.5 139.9 111.1 82.3
135.8 135.8 107.0 78.2
142.2 142.2 113.4 84.6

65
69.7
57.6
72.9
59.9
76.1
62.1
62.7
58.9
49.4
55.8

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor

Johnson Controls Unitary Products

505428-YTG-R-1114

PD180/ND180
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

4500

5250

6000

6750

7500

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

231.4
215.6
199.7
183.7
184.6
233.6
217.6
201.6
185.5
186.3
235.8
219.7
203.5
187.2
188.0
222.5
206.2
189.7
190.5
225.4
208.9
192.1
193.0

12.4
12.0
11.7
11.4
11.4
12.4
12.1
11.7
11.4
11.4
12.4
12.1
11.7
11.4
11.4
12.1
11.8
11.5
11.5
12.2
11.8
11.5
11.5

111.6
142.9
174.3
183.7
184.6
117.3
151.9
186.5
185.5
186.3
123.1
160.9
198.8
187.2
188.0
171.1
203.8
189.7
190.5
181.3
208.9
192.1
193.0

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

208.3
192.4
176.4
164.9
166.1
210.5
194.3
178.2
166.5
167.8
212.6
196.3
180.0
168.2
169.5
198.7
182.2
170.3
171.6
201.2
184.5
172.4
173.7

15.1
14.8
14.5
14.3
14.3
15.1
14.8
14.5
14.3
14.3
15.1
14.8
14.5
14.3
14.3
14.9
14.6
14.3
14.4
14.9
14.6
14.4
14.5

101.3
133.4
165.5
164.9
166.1
110.9
141.9
172.8
166.5
167.8
120.6
150.3
180.0
168.2
169.5
160.3
182.2
170.3
171.6
170.3
184.5
172.4
173.7

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
93.0
74.5
219.9
13.7
124.4 105.8 87.2
204.0
13.4
155.7 137.2 118.6 100.0
188.1
13.1
183.7 170.7 152.1 133.6 115.0
174.3
12.8
184.6 173.2 154.6 136.1 117.5
175.3
12.8
98.2
76.9
222.0
13.7
130.6 109.3 88.0
206.0
13.4
163.0 141.7 120.4 99.1
189.9
13.1
185.5 176.3 155.6 133.7 112.4
176.0
12.8
186.3 178.9 158.5 136.3 115.0
177.0
12.8
103.4 79.4
224.2
13.7
136.9 112.8 88.7
208.0
13.4
170.3 146.2 122.2 98.1
191.8
13.1
187.2 182.0 159.2 133.8 109.8
177.7
12.9
188.0 184.6 162.4 136.5 112.4
178.7
12.9
144.6 118.1 91.7
210.6
13.5
179.6 153.2 126.7 100.2
194.2
13.2
189.7 187.0 161.2 134.1 107.6
180.0
12.9
190.5 188.8 163.3 135.9 109.4
181.0
12.9
152.4 123.5 94.6
213.3
13.6
189.0 160.1 131.2 102.3
196.7
13.2
192.1 192.1 163.2 134.3 105.5
182.2
13.0
193.0 193.0 164.1 135.2 106.3
183.3
13.0
95°F
82.9
64.5
192.0
17.0
115.0 96.6
78.3
177.3
16.7
147.2 128.8 110.4 92.0
162.5
16.4
164.9 156.9 138.5 120.2 101.8
153.2
16.2
166.1 156.3 138.0 119.6 101.2
155.2
16.2
87.6
66.5
193.9
17.0
120.8 99.7
78.5
179.0
16.7
153.9 132.8 111.7 90.6
164.1
16.4
166.5 161.8 140.1 119.6 98.5
154.7
16.2
167.8 161.2 139.2 119.0 97.9
156.8
16.2
92.3
68.5
195.8
17.0
126.5 102.7 78.8
180.8
16.7
160.6 136.8 113.0 89.2
165.7
16.4
168.2 166.7 141.6 119.0 95.2
156.2
16.2
169.5 166.1 140.4 118.4 94.6
158.3
16.2
134.2 108.2 82.1
183.0
16.8
170.2 144.1 118.0 92.0
167.8
16.5
170.3 169.5 142.8 117.4 91.3
158.2
16.2
171.6 169.9 142.9 117.7 91.6
160.3
16.3
142.0 113.6 85.3
185.3
16.8
179.8 151.4 123.1 94.8
169.9
16.5
172.4 172.4 144.1 115.7 87.4
160.1
16.3
173.7 173.7 145.3 117.0 88.7
162.3
16.4

90
106.4
138.2
169.9
174.3
175.3
114.1
146.9
179.7
176.0
177.0
121.8
155.6
189.4
177.7
178.7
165.7
193.0
180.0
181.0
175.8
196.7
182.2
183.3
96.4
128.6
157.1
153.2
155.2
110.4
136.8
161.4
154.7
156.8
124.4
145.0
165.7
156.2
158.3
155.6
167.8
158.2
160.3
166.3
169.9
160.1
162.3

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
87.9
69.5
119.7 101.2 82.8
151.4 133.0 114.5 96.0
174.3 163.8 145.3 126.9
175.3 164.8 146.3 127.8
92.9
71.7
125.7 104.5 83.3
158.5 137.2 116.0 94.8
176.0 169.1 147.9 126.6
177.0 170.1 148.8 127.6
97.9
73.9
131.7 107.7 83.8
165.5 141.5 117.6 93.6
177.7 174.3 150.4 126.4
178.7 175.4 151.4 127.5
139.4 113.2 86.9
174.9 148.6 122.4 96.1
180.0 178.3 152.0 125.7
181.0 179.3 153.1 126.8
147.2 118.6 90.0
184.4 155.8 127.2 98.6
182.2 182.2 153.6 125.0
183.3 183.3 154.7 126.1
105°F
77.9
59.4
110.2 91.7
73.2
142.5 124.0 105.5 87.0
153.2 149.2 130.7 112.3
155.2 146.0 127.5 109.0
82.4
61.2
115.7 94.5
73.4
149.0 127.8 106.6 85.5
154.7 154.2 132.7 111.9
156.8 150.5 128.9 108.2
86.9
63.1
121.2 97.3
73.5
155.5 131.6 107.8 83.9
156.2 159.2 134.7 111.5
158.3 155.0 130.2 107.3
129.3 103.0 76.7
161.5 139.3 113.0 86.7
158.2 159.7 133.0 107.1
160.3 158.6 131.9 106.0
137.5 108.8 80.0
167.5 147.1 118.3 89.6
160.1 160.1 131.4 102.6
162.3 162.3 133.5 104.8

65
108.4
109.4
105.4
106.4
102.5
103.5
99.5
100.5
96.4
97.5
93.8
90.6
90.7
87.0
87.6
83.4
80.8
79.7
73.9
76.0

55

505428-YTG-R-1114

PD180/ND180 (Continued)
Air on
Evaporator Coil
CFM

4500

5250

6000

6750

7500

1

2

56

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

175.7
162.2
148.6
141.5
144.4
177.4
163.7
150.0
142.9
145.8
179.0
165.2
151.4
144.2
147.1
167.3
153.3
146.0
149.0
169.4
155.3
147.9
150.9

18.9
18.6
18.2
18.1
18.1
18.9
18.6
18.3
18.1
18.1
18.9
18.6
18.3
18.1
18.2
18.7
18.3
18.1
18.2
18.7
18.4
18.2
18.3

91.5
123.9
148.6
141.5
144.4
109.8
131.8
150.0
142.9
145.8
128.1
139.8
151.4
144.2
147.1
151.0
153.3
146.0
149.0
162.2
155.3
147.9
150.9

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
72.9
54.3
159.4
20.8
105.3 86.8
68.2
147.1
20.5
137.8 119.2 100.6 82.0
134.7
20.1
141.5 141.5 123.0 104.4 85.8
129.9
20.0
144.4 135.6 117.1 98.5
79.9
133.6
20.1
77.2
56.0
160.8
20.9
110.6 89.4
68.2
148.4
20.5
144.0 122.8 101.6 80.4
135.9
20.1
142.9 146.6 125.4 104.2 82.9
131.0
20.0
145.8 139.8 118.5 97.3
76.1
134.8
20.1
81.5
57.6
162.3
20.9
115.9 92.0
68.2
149.7
20.5
150.3 126.4 102.6 78.7
137.1
20.1
144.2 151.7 127.8 103.9 80.1
132.2
20.0
147.1 143.9 120.0 96.1
72.3
136.0
20.1
124.5 97.9
71.4
151.6
20.6
152.8 134.6 108.0 81.5
138.9
20.2
146.0 149.8 123.2 96.7
70.2
133.9
20.0
149.0 147.4 120.9 94.3
67.8
137.7
20.1
133.0 103.9 74.7
153.5
20.6
155.3 142.7 113.5 84.3
140.7
20.3
147.9 147.9 118.7 89.5
60.3
135.6
20.1
150.9 150.9 121.7 92.5
63.3
139.5
20.2

90
86.6
119.1
134.7
129.9
133.6
109.2
126.8
135.9
131.0
134.8
131.9
134.5
137.1
132.2
136.0
146.3
138.9
133.9
137.7
153.5
140.7
135.6
139.5

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
67.9
49.2
100.5 81.8
63.1
133.1 114.4 95.7
77.1
129.9 129.9 115.2 96.5
133.6 125.3 106.6 88.0
72.0
50.7
105.5 84.3
63.0
135.9 117.8 96.5
75.3
131.0 131.0 118.0 96.4
134.8 129.1 108.2 86.5
76.1
52.2
110.6 86.7
62.8
137.1 121.3 97.4
73.5
132.2 132.2 120.9 96.4
136.0 132.8 109.8 85.0
119.6 92.8
66.1
138.9 129.8 103.0 76.3
133.9 133.9 113.5 86.4
137.7 136.1 109.9 82.6
128.6 99.0
69.4
140.7 138.3 108.7 79.1
135.6 135.6 106.0 76.4
139.5 139.5 109.9 80.3

65
77.8
69.3
75.2
65.2
72.5
61.1
59.6
55.9
46.8
50.6

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

505428-YTG-R-1114

PD240/ND240
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

6000

7000

8000

9000

10000

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

314.8
285.9
257.1
239.1
239.5
321.1
291.7
262.3
243.9
244.3
327.5
297.5
267.5
248.8
249.2
303.3
272.7
253.6
254.0
309.0
277.8
258.4
258.8

15.1
14.8
14.5
14.2
14.3
15.2
14.9
14.6
14.3
14.5
15.3
15.0
14.8
14.4
14.6
15.2
14.9
14.6
14.7
15.4
15.1
14.7
14.9

142.6
177.4
212.3
239.1
239.5
154.7
192.0
229.3
243.9
244.3
166.9
206.6
246.3
248.8
249.2
219.3
262.1
253.6
254.0
231.9
277.8
258.4
258.8

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

285.2
257.5
229.9
216.0
220.8
290.2
262.1
234.0
219.8
224.7
295.2
266.6
238.0
223.6
228.6
271.1
242.1
227.4
232.5
275.7
246.1
231.2
236.4

18.9
18.6
18.2
18.0
18.1
19.0
18.6
18.3
18.0
18.2
19.0
18.7
18.4
18.1
18.3
19.0
18.6
18.3
18.5
19.2
18.8
18.6
18.7

131.3
166.4
201.5
216.0
220.8
143.1
180.8
218.5
219.8
224.7
154.9
195.2
235.5
223.6
228.6
204.8
240.8
227.4
232.5
214.3
246.1
231.2
236.4

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
118.0 93.5
300.0
17.0
152.9 128.3 103.8
271.7
16.7
187.7 163.2 138.6 114.0
243.5
16.4
225.1 200.5 175.9 151.4 126.8
227.5
16.1
237.8 213.3 188.7 164.1 139.6
230.2
16.2
127.4 100.0
305.7
17.1
164.7 137.3 110.0
276.9
16.8
201.9 174.6 147.2 119.9
248.1
16.5
236.9 214.5 188.2 159.8 132.5
231.9
16.2
243.5 228.2 203.0 173.5 146.1
234.5
16.3
136.7 106.6
311.4
17.2
176.5 146.3 116.2
282.1
16.9
216.2 186.0 155.9 125.7
252.8
16.6
248.8 228.6 200.4 168.3 138.1
236.2
16.2
249.2 243.2 217.3 182.9 152.7
238.9
16.4
184.7 150.2 115.7
287.2
17.1
225.5 191.0 156.5 122.0
257.4
16.8
253.6 234.7 201.2 165.6 131.1
240.5
16.4
254.0 249.7 217.3 180.6 146.1
243.3
16.6
193.0 154.1 115.2
292.4
17.3
234.9 196.0 157.1 118.2
262.0
17.0
258.4 240.8 201.9 163.0 124.1
244.8
16.6
258.8 256.2 217.3 178.4 139.5
247.6
16.8
95°F
106.8 82.2
264.8
21.2
141.9 117.3 92.8
240.1
20.9
177.0 152.4 127.9 103.3
215.3
20.5
213.5 189.0 164.4 139.9 115.3
203.2
20.2
217.8 193.2 168.7 144.1 119.6
209.8
20.4
115.7 88.3
269.2
21.3
153.4 126.0 98.5
244.1
20.9
191.1 163.7 136.3 108.8
219.0
20.6
218.6 202.9 174.5 148.1 120.7
206.6
20.3
223.2 207.5 177.9 152.6 125.2
213.3
20.5
124.6 94.3
273.7
21.4
164.9 134.6 104.3
248.1
21.0
205.2 174.9 144.6 114.3
222.6
20.7
223.6 216.9 184.6 156.3 126.0
210.0
20.4
228.6 221.8 187.2 161.2 130.9
216.9
20.6
171.3 137.9 104.4
252.2
21.2
212.6 179.1 145.7 112.3
226.2
20.9
227.4 222.1 187.7 155.2 121.8
213.4
20.6
232.5 227.1 191.5 160.2 126.8
220.4
20.8
177.7 141.1 104.5
256.2
21.5
219.9 183.4 146.8 110.2
229.8
21.1
231.2 227.3 190.8 154.2 117.6
216.8
20.8
236.4 232.5 195.9 159.3 122.7
223.9
21.0

90
137.0
171.9
206.9
227.5
230.2
148.9
186.4
223.9
231.9
234.5
160.9
200.9
240.9
236.2
238.9
212.0
251.5
240.5
243.3
223.1
262.0
244.8
247.6
126.0
161.0
195.9
203.2
209.8
142.0
175.3
208.6
206.6
213.3
158.1
189.7
221.3
210.0
216.9
199.3
225.6
213.4
220.4
208.9
229.8
216.8
223.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
112.4 87.8
147.4 122.8 98.3
182.4 157.8 133.2 108.7
219.3 194.7 170.2 145.6
227.8 203.3 178.7 154.1
121.5 94.1
159.0 131.6 104.2
196.5 169.1 141.7 114.4
227.7 208.7 181.3 154.0
233.4 217.9 190.5 163.1
130.7 100.5
170.7 140.5 110.2
210.7 180.5 150.2 120.0
236.2 222.7 192.5 162.3
238.9 232.5 202.2 172.0
178.0 144.0 110.1
219.1 185.1 151.1 117.1
240.5 228.4 194.4 160.4
243.3 238.4 204.4 170.4
185.4 147.6 109.9
227.4 189.7 151.9 114.2
244.8 234.1 196.4 158.6
247.6 244.3 206.6 168.8
105°F
101.4 76.8
136.3 111.7 87.1
171.3 146.7 122.1 97.5
202.0 183.1 158.5 133.9
206.5 181.9 157.3 132.6
110.2 82.7
147.8 120.3 92.8
185.4 157.9 130.4 102.9
206.0 197.1 169.1 142.1
211.7 195.8 167.2 140.8
119.0 88.5
159.3 128.9 98.4
199.6 169.2 138.8 108.3
210.0 211.2 179.7 150.3
216.9 209.7 177.2 148.9
165.7 132.2 98.6
207.1 173.6 140.0 106.4
213.4 213.0 179.0 145.9
220.4 215.2 180.5 148.0
172.2 135.5 98.8
214.6 177.9 141.2 104.6
216.8 214.9 178.2 141.5
223.9 220.6 183.9 147.2

65
121.1
129.6
126.6
135.7
132.1
141.8
126.5
136.4
120.9
131.1
109.2
108.0
114.6
113.3
119.9
118.5
112.4
114.5
104.8
110.5

57

505428-YTG-R-1114

PD240/ND240 (Continued)
Air on
Evaporator Coil
CFM

6000

7000

8000

9000

10000

1

2

58

WB
(°F)

Total
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

244.4
222.6
200.8
190.4
198.8
248.3
226.1
204.0
193.4
201.9
252.1
229.6
207.1
196.4
205.1
233.2
210.3
199.4
208.3
236.7
213.5
202.5
211.4

23.6
23.2
22.8
22.5
22.8
23.6
23.2
22.9
22.6
22.8
23.7
23.3
22.9
22.6
22.9
23.5
23.2
22.8
23.1
23.8
23.4
23.1
23.4

120.7
155.5
190.3
190.4
198.8
140.9
169.8
198.7
193.4
201.9
161.2
184.1
207.1
196.4
205.1
193.9
210.3
199.4
208.3
203.6
213.5
202.5
211.4

Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
96.0
71.4
224.0
25.9
130.8 106.2 81.5
205.1
25.5
165.6 140.9 116.3 91.6
186.2
25.1
190.4 177.2 152.5 127.8 103.2
177.6
24.8
195.2 170.5 145.8 121.2 96.5
187.8
25.1
104.7 77.1
227.3
25.9
142.2 114.6 87.0
208.1
25.5
179.8 152.2 124.6 97.0
188.9
25.2
193.4 191.3 163.7 136.1 108.5
180.2
24.8
200.1 184.1 156.5 128.9 101.3
190.6
25.1
113.3 82.7
230.6
26.0
153.6 123.1 92.5
211.1
25.6
194.0 163.4 132.9 102.4
191.7
25.2
196.4 205.4 174.9 144.4 113.8
182.8
24.9
205.1 197.7 167.2 136.6 106.1
193.3
25.2
160.2 126.5 92.8
214.2
25.8
201.6 168.0 134.3 100.6
194.5
25.5
199.4 203.9 170.3 136.6 102.9
185.4
25.1
208.3 203.2 169.5 135.9 102.2
196.1
25.4
166.8 129.9 93.1
217.2
26.1
209.3 172.5 135.7 98.9
197.2
25.7
202.5 202.5 165.6 128.8 92.0
188.1
25.4
211.4 208.7 171.9 135.1 98.3
198.9
25.7

90
115.4
150.0
184.7
177.6
187.8
139.8
164.3
188.8
180.2
190.6
164.3
178.6
191.7
182.8
193.3
188.4
194.5
185.4
196.1
198.2
197.2
188.1
198.9

Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
90.7
65.9
125.3 100.6 75.8
159.9 135.2 110.5 85.7
177.6 171.3 146.5 121.8
183.9 159.2 134.4 109.7
99.1
71.4
136.6 108.9 81.3
174.1 146.4 118.7 91.1
180.2 180.2 158.3 130.1
188.6 172.4 145.8 117.0
107.6 76.9
148.0 117.3 86.7
188.3 157.7 127.0 96.4
182.8 182.8 170.1 138.4
193.3 185.7 157.2 124.4
154.6 120.8 87.0
194.5 162.4 128.6 94.8
185.4 185.4 161.6 127.3
196.1 191.3 158.5 123.7
161.3 124.3 87.4
197.2 167.1 130.2 93.2
188.1 188.1 153.1 116.1
198.9 196.8 159.9 123.0

65
97.1
85.0
102.4
89.3
107.8
93.7
93.5
89.9
79.2
86.0

These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

505428-YTG-R-1114

Heat Pump And Air Handler Heating Capacities
PC090 / NC090
Air Over Evaporator Coil
CFM

DB (°F)
55

2250

70
80
55

3000

70
80
55

3750

70
80

1

Outdoor Temperature (°F @ 72% RH)

Capacity1 &
kW

-10

0

10

20

30

40

50

60

MBH

34.0

39.6

46.2

53.9

62.9

73.5

86.0

100.6

KW

4.9

5.3

5.6

6.0

6.3

6.7

7.0

7.3

MBH

31.0

36.6

43.2

50.9

60.0

70.6

83.0

97.6

KW

5.8

6.1

6.5

6.8

7.1

7.5

7.8

8.2

MBH

28.7

34.3

40.9

48.6

57.7

68.3

80.7

95.3

KW

6.4

6.8

7.1

7.4

7.8

8.1

8.5

8.8

MBH

35.3

40.9

47.5

55.2

64.3

74.9

87.3

101.9

KW

4.7

5.1

5.4

5.8

6.1

6.5

6.8

7.1

MBH

32.4

38.0

44.5

52.3

61.3

71.9

84.4

99.0

KW

5.6

5.9

6.3

6.6

6.9

7.3

7.6

8.0

MBH

30.1

35.7

42.3

50.0

59.0

69.6

82.1

96.7

KW

6.2

6.5

6.9

7.2

7.6

7.9

8.3

8.6

MBH

36.6

42.2

48.8

56.5

65.6

76.2

88.6

103.2

KW

5.2

5.6

5.9

6.3

6.6

7.0

7.3

7.6

MBH

33.7

39.3

45.8

53.6

62.6

73.2

85.7

100.3

KW

6.1

6.4

6.8

7.1

7.4

7.8

8.1

8.5

MBH

31.4

37.0

43.6

51.3

60.3

70.9

83.4

98.0

KW

6.7

7.0

7.4

7.7

8.1

8.4

8.8

9.1

These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate

Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

PC120 / NC120
Air Over Evaporator Coil
CFM

DB (°F)
55

3000

70
80
55

4000

70
80
55

5000

70
80

1

Outdoor Temperature (°F @ 72% RH)

Capacity1 &
kW

-10

0

10

20

30

40

50

60

MBH

29.1

36.4

45.3

56.0

69.0

84.7

103.8

126.8

KW

6.9

7.3

7.6

8.0

8.3

8.7

9.1

9.4

MBH

26.3

33.6

42.4

53.1

66.1

81.8

100.9

124.0

KW

8.2

8.6

8.9

9.3

9.7

10.0

10.4

10.7

MBH

24.2

31.5

40.4

51.1

64.1

79.8

98.8

121.9

KW

9.2

9.6

10.0

10.3

10.7

11.1

11.4

11.8

MBH

37.4

44.7

53.5

64.3

77.2

93.0

112.0

135.1

KW

6.7

7.1

7.4

7.8

8.1

8.5

8.9

9.2

MBH

34.5

41.8

50.7

61.4

74.4

90.1

109.2

132.2

KW

8.0

8.4

8.7

9.1

9.5

9.8

10.2

10.6

MBH

32.5

39.8

48.6

59.3

72.3

88.0

107.1

130.2

KW

9.0

9.4

9.8

10.1

10.5

10.9

11.2

11.6

MBH

44.1

51.4

60.3

71.0

84.0

99.7

118.7

141.8

KW

6.9

7.2

7.6

8.0

8.3

8.7

9.0

9.4

MBH

41.3

48.6

57.4

68.1

81.1

96.8

115.9

138.9

KW

8.2

8.6

8.9

9.3

9.6

10.0

10.4

10.7

MBH

39.2

46.5

55.3

66.1

79.0

94.8

113.8

136.9

KW

9.2

9.6

9.9

10.3

10.7

11.0

11.4

11.7

These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate

Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

Johnson Controls Unitary Products

59

505428-YTG-R-1114

PC180 / NC180
Air Over Evaporator Coil
CFM

DB (°F)
55

4500

70
80
55

6000

70
80
55
70

7500

80
1

Outdoor Temperature (°F @ 72% RH)

Capacity1 &
kW

-10

0

10

20

30

40

50

60

MBH

68.2

80.0

93.8

110.0

129.1

151.5

177.8

208.7

KW

11.8

12.2

12.7

13.2

13.7

14.1

14.6

15.1

MBH

61.5

73.2

87.0

103.2

122.3

144.7

171.0

201.9

KW

13.5

14.0

14.4

14.9

15.4

15.9

16.3

16.8

MBH

57.6

69.3

83.1

99.3

118.4

140.8

167.1

198.0

KW

15.0

15.5

16.0

16.4

16.9

17.4

17.9

18.3

MBH

74.0

85.8

99.6

115.8

134.9

157.3

183.6

214.5

KW

11.2

11.7

12.2

12.6

13.1

13.6

14.1

14.6

MBH

67.3

79.0

92.8

109.0

128.1

150.5

176.8

207.7

KW

12.9

13.4

13.9

14.4

14.8

15.3

15.8

16.3

MBH

63.4

75.1

88.9

105.1

124.2

146.6

172.9

203.8

KW

14.5

14.9

15.4

15.9

16.4

16.8

17.3

17.8

MBH

72.4

84.1

97.9

114.1

133.2

155.6

181.9

212.8

KW

12.0

12.5

13.0

13.4

13.9

14.4

14.9

15.4

MBH

65.6

77.3

91.1

107.4

126.4

148.8

175.1

206.0

KW

13.7

14.2

14.7

15.2

15.6

16.1

16.6

17.1

MBH

61.7

73.4

87.3

103.5

122.5

144.9

171.2

202.1

KW

15.3

15.7

16.2

16.7

17.2

17.6

18.1

18.6

These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate

Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

PD180 / ND180
Air Over Evaporator Coil
CFM

DB (°F)
55

4500

70
80
55

6000

70
80
55

7500

70
80

1

60

Outdoor Temperature (°F @ 72% RH)

Capacity1 &
kW

-10

0

10

20

30

40

50

60

MBH

65.6

77.0

90.3

105.8

123.9

145.1

169.7

198.5

KW

10.0

10.5

11.1

11.6

12.2

12.7

13.3

13.8

MBH

62.2

73.6

86.9

102.4

120.5

141.6

166.3

195.1

KW

12.0

12.5

13.1

13.6

14.2

14.7

15.3

15.8

MBH

59.5

70.9

84.1

99.7

117.8

138.9

163.6

192.4

KW

13.4

13.9

14.5

15.0

15.6

16.1

16.7

17.2

MBH

71.6

83.0

96.3

111.8

129.9

151.0

175.7

204.5

KW

9.6

10.2

10.7

11.3

11.8

12.4

12.9

13.4

MBH

68.1

79.5

92.8

108.3

126.5

147.6

172.3

201.1

KW

11.6

12.2

12.7

13.3

13.8

14.3

14.9

15.4

MBH

65.4

76.8

90.1

105.6

123.7

144.9

169.6

198.3

KW

13.0

13.6

14.1

14.7

15.2

15.8

16.3

16.9

MBH

74.0

85.4

98.7

114.2

132.4

153.5

178.2

207.0

KW

11.3

11.8

12.4

12.9

13.5

14.0

14.6

15.1

MBH

70.6

82.0

95.3

110.8

128.9

150.1

174.7

203.5

KW

13.3

13.8

14.4

14.9

15.5

16.0

16.6

17.1

MBH

67.9

79.3

92.6

108.1

126.2

147.4

172.0

200.8

KW

14.7

15.3

15.8

16.4

16.9

17.5

18.0

18.5

These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate

Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

Johnson Controls Unitary Products

505428-YTG-R-1114

PD240 / ND240
Air Over Evaporator Coil
CFM

DB (°F)
55

6000

70
80
55

8000

70
80
55

10000

70
80

1

Outdoor Temperature (°F @ 72% RH)

Capacity1 &
kW

-10

0

10

20

30

40

50

60

MBH

64.6

79.5

97.4

118.8

144.3

174.9

211.4

255.1

KW

15.7

16.5

17.3

18.1

19.0

19.8

20.6

21.4

MBH

69.5

84.4

102.3

123.7

149.2

179.8

216.3

260.0

KW

15.4

16.2

17.0

17.9

18.7

19.5

20.3

21.2

MBH

63.3

78.3

96.2

117.5

143.1

173.6

210.2

253.8

KW

17.2

18.0

18.8

19.6

20.5

21.3

22.1

23.0

MBH

71.6

86.6

104.5

125.8

151.4

181.9

218.5

262.1

KW

15.1

15.9

16.8

17.6

18.4

19.2

20.1

20.9

MBH

76.5

91.5

109.4

130.7

156.3

186.8

223.4

267.0

KW

14.8

15.6

16.5

17.3

18.1

19.0

19.8

20.6

MBH

70.4

85.3

103.2

124.6

150.1

180.7

217.2

260.9

KW

16.6

17.4

18.3

19.1

19.9

20.7

21.6

22.4

MBH

73.3

88.3

106.1

127.5

153.1

183.6

220.1

263.8

KW

15.3

16.1

17.0

17.8

18.6

19.4

20.3

21.1

MBH

78.2

93.2

111.0

132.4

158.0

188.5

225.0

268.7

KW

15.0

15.8

16.7

17.5

18.3

19.1

20.0

20.8

MBH

72.1

87.0

104.9

126.3

151.8

182.4

218.9

262.6

KW

16.8

17.6

18.5

19.3

20.1

20.9

21.8

22.6

These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate

Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

Johnson Controls Unitary Products

61

505428-YTG-R-1114

Air Handling and Hot Water Coil Accessory Heating Capacity
NC300 / 1HW04061
CAPACITY (MBH)
UNIT
MODEL

HOT WATER
COIL MODEL

NC300

GPM

1HW0406

CFM

ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F.
70

90

110

130

150

6,000

204

263

325

384

443

8,000

236

304

372

440

508

10,000

265

341

416

492

568

12,000

291

374

457

540

623

50

1

These capacities do not include any blower motor heat.
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.

Hot Water Coil Capacity Correction And Pressure Drop Vs GPM1
HOT WATER COIL MODEL

GPM

PRESSURE DROP
PSI

CAPACITY CORRECTION
FACTOR

25

0.4

0.79

50

1.0

1.00

75

1.8

1.04

100

3.4

1.07

1HW0406

1

For pressure drop in feet (water), multiply these values by 2.31.

Air Handling and Steam Coil Accessory Heating Capacity
NC300 / 1NF0454
CAPACITY (MBH) @ 2 PSIG1
UNIT
MODEL

NC300

1

STEAM COIL
MODEL

CFM

DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)
10

30

50

70

6,000

471

424

380

330

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

1NF0454

These capacities do not include any blower motor heat.

Steam Coil Capacity Correction Factors For High Steam Pressure
STEAM PRESSURE (PSIG)

5

10

15

20

25

CAPACITY CORRECTION FACTOR

1.05

1.12

1.19

1.25

1.30

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH

62

Johnson Controls Unitary Products

505428-YTG-R-1114

Airflow Performance
NC090 Upflow and Horizontal Airflow Performance
NC090 Upflow
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive

2250
2500
2750
3000
3250
3500
3750

705
741
780
823

1.0
1.1
1.4
1.6

707
735
767
802
842
884

Standard 1.5 HP & Drive

0.8
0.9
1.1
1.3
1.5
1.7

754
777
805
837
872
912
954

0.8
0.9
1.1
1.2
1.4
1.6
1.9

828
851
879
911
947
974
1012

0.9
1.0
1.2
1.3
1.5
1.8
2.0

902
925
953
973
1002
1035
1072

High Static 2 HP & Drive
1.0
1.1
1.3
1.5
1.7
1.9
2.2

988
996
1012
1035
1064
1097
1134

1.1
1.3
1.4
1.6
1.8
2.1
2.3

1051
1059
1076
1099
1127
1161

1.3
1.4
1.6
1.7
2.0
2.2

1116
1124
1141
1164

1.4
1.5
1.7
1.9

1183
1191

1.5
1.7

Exceeds BHP Limitations

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NC090 Horizontal
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive

2250
2500
2750
3000
3250
3500
3750

696
729
766
806

0.9
1.1
1.3
1.6

703
728
757
790
826
867

Standard 1.5 HP & Drive

0.8
0.9
1.1
1.3
1.5
1.7

747
768
793
822
855
892
932

0.8
0.9
1.0
1.2
1.4
1.6
1.8

816
837
862
891
924
953
984

0.9
1.0
1.1
1.3
1.5
1.6
1.9

889
909
934
961
984
1010
1041

High Static 2 HP & Drive
1.0
1.1
1.2
1.4
1.6
1.9
2.1

954
977
998
1019
1042
1069
1099

1.2
1.2
1.4
1.6
1.8
2.0
2.3

1013
1036
1056
1077
1100
1127

1.3
1.4
1.5
1.7
1.9
2.2

1071
1094
1114
1135
1159

1.5
1.5
1.7
1.9
2.1

1128
1151

1.6
1.7

Exceeds BHP Limitations

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

Johnson Controls Unitary Products

63

505428-YTG-R-1114

NC/ND120 Upflow and Horizontal Airflow Performance
NC/ND120 Upflow
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive

2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000

653
679
707
737
768
801

1.1
1.3
1.5
1.7
1.9
2.1

664
685
709
735
762
792
824
856

Standard 2 HP & Drive

1.0
1.1
1.3
1.5
1.6
1.9
2.1
2.3

671
684
701
719
741
764
790
818
850
877
906

0.8
0.9
1.0
1.1
1.3
1.4
1.6
1.8
2.0
2.2
2.5

728
741
757
776
797
821
847
875
899
926
956

0.9
1.0
1.1
1.3
1.4
1.6
1.8
1.9
2.2
2.5
2.8

788
801
817
836
858
884
903
924
948
975
1005

1.0
1.1
1.3
1.4
1.5
1.7
1.9
2.1
2.4
2.7
3.0

High Static 3 HP & Drive
853
866
882
903
917
933
952
973
997
1024
1053

1.1
1.2
1.4
1.5
1.7
1.9
2.1
2.3
2.6
2.9
3.2

926
933
941
952
966
982
1001
1022
1046
1073

1.3
975
1.5 1026 1.6 1077
1.4
982
1.6 1032 1.7 1084
1.5
991
1.7 1041 1.8 1092
1.7
1002
1.8 1052 2.0
1.9
1015
2.0 1066 2.2
2.0
1031
2.2 1082 2.3
2.3
1050
2.4
2.5
1072
2.7
2.8
3.0
High Static 3 HP & Field Supplied Drive

1.7
1.8
2.0

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NC/ND120 Horizontal
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive

2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000

669
699
732
769
808
850

1.2
1.4
1.6
1.8
2.1
2.3

684
707
734
764
798
834
874
873

Standard 2 HP & Drive

1.0
1.2
1.4
1.6
1.8
2.0
2.3
2.4

686
698
714
734
757
784
814
847
884
891
919

0.8
0.9
1.0
1.2
1.3
1.5
1.7
1.9
2.1
2.3
2.6

730
742
758
778
801
828
858
887
911
937
965

0.9
1.0
1.1
1.2
1.4
1.6
1.8
2.0
2.3
2.5
2.8

778
790
806
826
849
890
910
933
957
983
1011

0.9
1.0
1.1
1.3
1.4
1.7
2.0
2.2
2.4
2.7
3.0

High Static 3 HP & Drive
840
852
868
902
917
936
956
978
1003
1029
1057

1.0
1.1
1.2
1.6
1.7
1.9
2.1
2.4
2.6
2.9
3.2

917
924
935
948
964
982
1002
1025
1049
1075

1.3
964
1.5 1011 1.6 1060
1.4
971
1.6 1019 1.7 1067
1.6
981
1.7 1029 1.9 1078
1.7
995
1.9 1042 2.0
1.9
1010
2.0 1058 2.2
2.1
1029
2.2 1076 2.4
2.3
1049
2.4
2.5
1071
2.7
2.8
3.1
High Static 3 HP & Field Supplied Drive

1.7
1.9
2.0

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

64

Johnson Controls Unitary Products

505428-YTG-R-1114

NC/ND180 Upflow and Horizontal Airflow Performance
NC/ND180 Upflow
(CFM)

4500
4750
5000
5250
5500
5750
6000
6250
6500
6750
7000
7250
7500

0.2
RPM BHP

0.4
RPM BHP

0.6
RPM BHP

Std. 3 HP & Field Supplied Drive
583
592
602
613
577
1.1
625
590
1.2
638
603
1.3
651
617
1.5
664
587
1.4
631
1.6
679
601
1.6
645
1.8
693
616
1.8
660
2.0
710
632
2.1
675
2.3
725
647
2.3
691
2.5
740

1.1
1.2
1.2
1.3
1.4
1.4
1.6
1.7
1.8
2.0
2.9
3.2
3.5

Available External Static Pressure - IWG
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP
Standard 3 HP & Drive
634
1.3
688
643
1.4
700
653
1.4
707
664
1.5
716
676
1.6
725
689
1.7
735
702
2.3
745
714
2.6
757
726
2.8
769
739
3.0
782
753
3.3
796
767
3.6
810
782
3.9
825

1.5
1.8
1.9
2.1
2.3
2.5
2.7
2.9
3.1
3.4
3.6
3.9
4.2

738
744
751
759
768
778
789
801
813
826
839
854

1.4
RPM BHP

1.6
RPM BHP

1.8
RPM BHP

High Static 5 HP & Drive
1.9
782
2.3
827
2.6
2.1
788
2.4
833
2.7
2.2
795
2.6
840
2.9
2.4
804
2.7
848
3.1
2.6
813
2.9
857
3.2
2.8
822
3.1
3.0
833
3.3
3.2
845
3.5
3.4
857
3.8
3.7
3.9
4.2
High Static 5 HP & Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NC/ND180 Horizontal
(CFM)

4500
4750
5000
5250
5500
5750
6000
6250
6500
6750
7000
7250
7500

0.2
RPM BHP

0.4
RPM BHP

0.6
RPM BHP

Std. 3 HP & Field Supplied Drive
585
595
605
617
582
1.8
629
594
1.9
642
608
2.1
655
622
2.2
670
589
2.2
637
2.4
684
604
2.4
652
2.6
699
620
2.6
667
2.8
715
636
2.8
683
3.0
731
652
3.0
700
3.2
738

1.5
1.6
1.7
1.8
1.9
2.1
2.2
2.4
2.6
2.8
3.0
3.2
4.0

Available External Static Pressure - IWG
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP
634
644
655
666
678
691
705
719
733
738
752
766
781

Standard 3 HP & Drive
1.6
687
1.8
1.7
697
1.9
1.8
708
2.0
2.0
719
2.1
2.1
731
2.3
2.2
737
2.4
2.4
744
3.1
2.6
756
3.3
2.7
769
3.6
3.5
782
3.8
3.8
796
4.1
4.1
811
4.4
4.4
825
4.7

735
741
749
757
767
778
789
801
814
827
841
856

1.4
RPM BHP

1.6
RPM BHP

1.8
RPM BHP

High Static 5 HP & Drive
2.0
780
2.5
827
2.7
875
2.4
787
2.7
834
2.9
2.6
795
2.9
842
3.1
2.8
804
3.1
851
3.3
3.0
813
3.2
860
3.4
3.2
824
3.4
871
3.7
3.4
835
3.7
3.6
847
3.9
3.9
860
4.1
4.1
873
4.4
4.4
4.7
High Static 5 HP & Field Supplied Drive

2.9

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

Johnson Controls Unitary Products

65

505428-YTG-R-1114

NC/ND240 Upflow and Horizontal Airflow Performance
NC/ND240 Upflow
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field Supplied Drive

6000
6250
6500
6750
7000
7250
7500
7750
8000
8250
8500
8750
9000
9250
9500
9750
10000

700
712
726
740
754
768
783
799
815
831

2.6
2.8
3.0
3.2
3.4
3.6
3.9
4.1
4.4
4.7

685
696
706
718
729
741
754
767
780
794
808
823
838
853
869
885

1.9
2.1
2.2
2.4
2.6
2.8
2.9
3.1
3.3
3.6
3.8
4.0
4.3
4.5
4.8
5.0

High Static 5 HP & Drive
732
742
752
763
774
786
798
810
823
837
850
865
879
894
910
925
939

2.2
2.3
2.5
2.6
2.8
3.0
3.1
3.3
3.5
3.7
3.9
4.2
4.4
4.6
4.9
5.5
5.9

789
799
809
820
831
843
855
868
881
894
908
922
934
947
961
974
988

2.6
2.7
2.8
3.0
3.2
3.3
3.5
3.7
3.9
4.1
4.3
4.8
5.1
5.4
5.8
6.1
6.5

846
856
866
877
888
900
912
925
936
948
959
972
984
997
1011
1024
1038

2.9
3.0
3.2
3.3
3.5
3.6
3.8
4.3
4.6
4.9
5.1
5.4
5.7
6.1
6.4
6.7
7.1

High Static 7.5 HP & Drive
900
910
920
935
945
954
965
975
986
998
1010
1022
1034
1047
1061
1074
1088

3.1
3.3
3.4
4.0
4.2
4.5
4.7
4.9
5.2
5.5
5.8
6.0
6.4
6.7
7.0
7.3
7.7

959
967
976
985
994
1004
1014
1025
1036
1047
1059
1071
1084
1097
1110
1124
1138

4.0
4.2
4.4
4.6
4.8
5.0
5.3
5.5
5.8
6.0
6.3
6.6
6.9
7.2
7.6
7.9
8.3

1008
1016
1025
1034
1043
1053
1063
1074
1085
1096
1108
1120
1133

4.5
4.7
4.9
5.1
5.3
5.5
5.8
6.0
6.3
6.5
6.8
7.1
7.4

1056
1064
1072
1081
1091
1100
1111
1121
1132
1144

4.9
5.1
5.3
5.5
5.7
5.9
6.2
6.4
6.7
6.9

1102
1110
1118
1127
1137
1146

5.2
5.4
5.6
5.8
6.0
6.2

1146
1154

5.3
5.5

High Static 7.5 HP & Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NC/ND240 Horizontal
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field
Supplied
Drive

6000
6250
6500
6750
7000
7250
7500
7750
8000
8250
8500
8750
9000
9250
9500
9750
10000

712
722
733
745
757
770
784
798
812
827
842

2.6
2.8
2.9
3.1
3.3
3.6
3.8
4.0
4.3
4.5
4.8

Standard 5 HP & Drive
708
715
723
731
740
749
759
770
781
793
805
818
831
845
859
908
921

2.0
2.1
2.3
2.4
2.5
2.7
2.9
3.0
3.2
3.4
3.6
3.8
4.1
4.3
4.6
5.1
5.4

754
761
769
777
786
796
806
816
827
839
851
864
878
923
935
947
960

2.3
2.4
2.6
2.7
2.8
3.0
3.2
3.3
3.5
3.7
3.9
4.1
4.4
4.9
5.2
5.5
5.8

801
808
816
824
833
842
852
863
874
886
898
942
953
964
976
988
1001

2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.6
3.8
4.0
4.2
4.8
5.1
5.4
5.7
6.0
6.3

849
856
864
872
881
890
900
945
954
964
974
984
995
1006
1018
1030
1043

High Static 7.5 HP & Drive
2.8
2.9
3.0
3.2
3.3
3.5
3.6
4.4
4.6
4.8
5.1
5.3
5.6
5.9
6.2
6.5
6.8

898
906
947
955
963
971
979
988
998
1007
1017
1028
1039
1050
1062
1074
1087

2.9
3.0
3.9
4.1
4.3
4.5
4.7
4.9
5.1
5.3
5.6
5.8
6.1
6.3
6.6
6.9
7.3

976
984
991
999
1007
1015
1024
1033
1042
1052
1062
1072
1083
1094
1106
1118
1131

4.0
4.2
4.4
4.6
4.7
4.9
5.1
5.3
5.5
5.8
6.0
6.3
6.5
6.8
7.1
7.4
7.7

1021
1029
1036
1044
1052
1060
1069
1078
1087
1096
1107
1117
1128
1139
1151

4.4
4.6
4.8
5,0
5.2
5.3
5.5
5.8
6.0
6.2
6.4
6.7
6.9
7.2
7.5

1066
1074
1081
1089
1097
1105
1114
1123
1132
1141
1152

4.8
5.0
5.2
5.3
5.5
5.7
5.9
6.1
6.3
6.5
6.8

1111
1118
1126
1134
1142
1150
1158

5.1
5.3
5.4
5.6
5.8
6.0
6.2

1155
1163

5.3
5.5

High Static 7.5 HP & Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

66

Johnson Controls Unitary Products

505428-YTG-R-1114

NC300 Airflow Performance1
Avaiable External Static Pressure - IWG
CFM

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

2.2

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Motor & Drive
7500

7.5 HP Motor & Drive

600

2.04

648

2.50

694

3.00

738

3.54

781

4.08

823

4.63

863

5.16

903

5.66

942

6.10

981

6.49

603

2.17

652

2.63

698

3.13

742

3.67

785

4.22

827

4.76

867

5.29

907

5.79

946

6.24

984

6.62

608

2.32

656

2.78

702

3.28

747

3.81

789

4.36

831

4.91

871

5.44

911

5.93

950

6.38

989

6.77

8250

613

2.48

661

2.93

707

3.44

752

3.97

795

4.52

836

5.07

877

5.60

916

6.09

955

6.54

994

6.92

8500

619

2.65

667

3.10

713

3.61

758

4.14

800

4.69

842

5.24

882

5.77

922

6.26

961

6.71 1000 7.09

7750
8000

5 HP & Field
supplied
Drive

8750

575

2.43

625

2.83

673

3.28

720

3.79

764

4.32

807

4.87

848

5.42

889

5.95

928

6.44

967

6.89 1006 7.27

9000

581

2.62

632

3.02

680

3.47

726

3.98

771

4.51

814

5.06

855

5.61

896

6.14

935

6.63

974

7.08 1013 7.46

9250

589

2.82

639

3.21

687

3.67

734

4.17

778

4.71

821

5.26

862

5.80

903

6.33

942

6.83

982

7.28

9500

596

3.02

647

3.42

695

3.88

741

4.38

786

4.91

829

5.46

870

6.01

910

6.54

950

7.03

989

7.48

9750

604

3.23

655

3.63

703

4.09

749

4.59

794

5.13

836

5.67

878

6.22

918

6.75

958

7.25

10000

613

3.45

663

3.85

711

4.31

758

4.81

802

5.34

845

5.89

886

6.44

927

6.97

966

7.46

10250

621

3.68

672

4.07

720

4.53

766

5.03

811

5.57

853

6.12

895

6.66

935

7.19

10500

630

3.9

680

4.30

729

4.76

775

5.26

819

5.80

862

6.34

904

6.89

944

7.42

10750

639

4.14

689

4.53

738

4.99

784

5.50

828

6.03

871

6.58

913

7.12

11000

648

4.37

699

4.77

747

5.23

793

5.73

837

6.27

880

6.82

922

7.36

11250

657

4.62

708

5.01

756

5.47

802

5.97

847

6.51

890

7.06

11500

667

4.86

717

5.26

766

5.71

812

6.22

856

6.75

899

7.30

11750

676

5.11

727

5.50

775

5.96

821

6.46

866

7.00

12000

686

5.36

737

5.75

785

6.21

831

6.71

876

7.25

12250

696

5.61

746

6.00

795

6.46

841

6.97

885

7.50

12500

706

5.86

756

6.26

805

6.72

851

7.22

High static 7.5 HP & Field Supplied Drive

1. NC300 requires the selection, purchase and field installation of the Supply Fan Motor, Drive Kit and Motor Overloads (See Following Page for Item
Selection Tables).

RPM Selection
Unit Model
NC090
NC/ND120
NC/ND180
NC/ND240
1
2

HP Max BHP

Motor Sheave

Blower Sheave

6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Open
Open
Open
Open
Open
Open Closed

Std. 1.5

1.73

1VL40

AK69

-1

690

743

796

849

902

955

HS

2

2.30

1VL40

AK56

-1

863

929

995

1062

1128

1194

Std.

2

2.30

1VL40

AK74

-1

641

690

739

789

838

887

HS

3

3.45

1VP56

AK84

-1

906

949

992

1035

1078

1121

Std.

3

3.45

1VP50

AK114

-1

565

596

627

659

690

721

HS

5

5.75

2VP50

2B5V94

707

745

782

819

856

894

-2

Std.

5

5.75

2VP50

2B5V94

686

722

758

794

830

866

-2

HS

7.5

8.63

2VP65

2B5V94

925

960

996

1031

1067

1103

1138

Setting not available.
Setting not recommended for use with Type B v-belts.

NC090 - 240 And ND120 - 240 Blower Motor And Drive Data
Blower Motor Data
Unit
Model

HP

RPM

SF

Std 1.5
1725 1.15
HS 2
Std. 2
NC/ND120
1725 1.15
HS 3
Std. 3
NC/ND180
1725 1.15
HS 5
Std. 5
NC/ND240
1725 1.15
HS 7.5
NC090

Frame Model
Size Number
56
56HZ
56HZ
56HZ
56HZ
184T
184T
213T

Johnson Controls Unitary Products

1VL40
1VL40
1VL40
1VP56
1VP50
2VP50
2VP50
2VP65

Blower
RPM
Range
690 - 955
863 - 1194
641 - 887
906 - 1121
565 - 721
707 - 894
686 - 866
925 - 1138

Drive Data
Adjustable Motor Sheave
Model
Pitch
Bore
Number
Diameter
(in.)
(in.)
2.6 - 3.6
0.875
AK69
2.6 - 3.6
0.875
AK56
2.6 - 3.6
0.875
AK74
4.2 - 5.2
0.875
AK84
3.6 - 4.6
0.875
AK114
3.7 - 4.7
1.125
2B5V94
3.7 - 4.7
1.125
2B5V94
5.2 - 6.4
1.375
2B5V94

Fixed Blower Sheave
Pitch
Diameter Bore (in.)
(in.)
6.5
1.000
5.2
1.000
7.0
1.000
8.0
1.000
11.0
1.000
9.7
1.000
9.7
1.188
9.7
1.188

Belts
Pitch
DesigQty. Length
nation
(in.)
1
42.3
A41
1
40.3
A39
1
45.3
A44
1
48.3
A47
1
45.3
A44
2
41.8
B40
2
41.8
B40
2
46.8
B45

67

505428-YTG-R-1114

NC300 Drive Kit Data
Unit
Model

Drive Kit Model
Number

NC300

1LD0440
1LD0407
1LD0442

Sheave
Model
Number
2VP56
2VP60
2VP71

Adjustable Motor Sheave
Blower
Pitch
RPM
Diameter
Range
(in.)
575 - 719
4.0 - 5.0
659 - 815
4.2 - 5.2
762 - 906
5.3 - 6.3

Bore
(in.)
1 1/8
1 3/8
1 3/8

Fixed Blower Sheave
Sheave
Pitch
Bore
Model
Diameter
(in.)
Number
(in.)
2AK124
12.0
1 3/16
2AK114
11.0
1 3/16
2AK124
12.0
1 3/16

Qty.
2
2
2

Belts
Pitch
Length
(in.)
63.3
63.3
63.3

Designation
A62
A62
A62

NC300 Motor Kit Data
Unit Model HP

5
NC300
7.5

Motor Kit
Model
Number
2LP04605133
2LP04605158
2LP04607133
2LP04607158

Frame
Size
184
213

Voltage
(3PH-60HZ)
208/230/460
575
208/230/460
575

NC300 Overload Relay Kit
UNIT

VOLTAGE

MODEL

MOTOR HP

NC300

208/230V

460V

575V

OVERLOAD RELAY KIT

5

2MP04708500

2MP04708300

2MP04708300

7.5

2MP04708700

2MP04708400

2MP04708300

NC300 Overload Relay Setting
UNIT
MODEL

VOLTAGE
MOTOR HP

208/230V
460V
575V
OVERLOAD RELAY SETTING (Full Load Amps) 1,2

5

14/13

6.5

5

7.5

21/20

9.5

7.5

NC300

1
2

68

Motors with Service Factor of 1.15 or Greater: Adjust overload relay
dial to the motor nameplate Full Load Amps (FLA).
Motors with Service Factor Less Than 1.15: Adjust overload relay dial
based on the formula: Motor nameplate FLA x 0.90 = relay setting

Johnson Controls Unitary Products

505428-YTG-R-1114

Additional Static Resistance
CFM

Wet Indoor1
Coil

2” Filters

Bottom
Return

2250
2500
2750
3000
3250
3500
3750
3000
3250
3500
3750
4000
4250
4500
4750
5000
4500
4750
5000
5250
5500
5750
6000
6250
6500
6750
7000
7250
7500

0.03
0.03
0.02
0.02
0.01
0.00
0.00
0.08
0.07
0.07
0.06
0.05
0.04
0.03
0.02
0.00
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04
0.03
0.03
0.02
0.01
0.00

0.10
0.11
0.11
0.12
0.13
0.14
0.15
0.12
0.13
0.14
0.15
0.16
0.18
0.19
0.21
0.23
0.11
0.11
0.11
0.12
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.16
0.17

0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.03
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08

Model

CFM

Wet Indoor
Coil

2” Filters

Bottom
Return

NC/ND240

6000
6250
6500
6750
7000
7250
7500
7750
8000
8250
8500
8750
9000
9250
9500
9750
10000

0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05
0.04
0.04
0.03
0.02
0.01
0.00
0.00
0.00

0.12
0.13
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.25

0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.00
0.00
0.00

Model

NC090

NC/ND120

NC/ND180

1

10
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.01
0.02
0.02
0.02
0.03
0.03
0.03
0.04
0.04
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.10

Electric Heat kW
16
26
36
0.02
0.03
0.04
0.02
0.03
0.05
0.03
0.04
0.07
0.03
0.05
0.08
0.04
0.06
0.09
0.04
0.07
0.10
0.05
0.08
0.12
0.03
0.05
0.08
0.04
0.06
0.09
0.04
0.07
0.10
0.05
0.08
0.12
0.06
0.09
0.14
0.06
0.10
0.15
0.07
0.11
0.17
0.08
0.13
0.19
0.09
0.14
0.21
0.07
0.11
0.17
0.08
0.13
0.19
0.09
0.14
0.21
0.10
0.15
0.23
0.11
0.17
0.25
0.12
0.19
0.28
0.13
0.20
0.30
0.14
0.22
0.33
0.15
0.24
0.35
0.17
0.26
0.38
0.18
0.28
0.41
0.19
0.30
0.44
0.20
0.32
0.47

50
--------------------------------0.21
0.22
0.24
0.26
0.29
0.32
0.35
0.38
0.42
0.47
0.50
0.53
0.56

Electric Heat kW
20
32
52
0.01
0.03
0.05
0.02
0.03
0.05
0.02
0.04
0.06
0.02
0.04
0.06
0.02
0.04
0.07
0.02
0.05
0.07
0.02
0.05
0.08
0.02
0.05
0.08
0.03
0.06
0.09
0.03
0.06
0.09
0.03
0.06
0.10
0.03
0.07
0.11
0.03
0.07
0.11
0.04
0.08
0.12
0.04
0.08
0.13
0.04
0.09
0.13
0.04
0.09
0.14

Pressure drop added by condensate over a dry coil.

Johnson Controls Unitary Products

69

505428-YTG-R-1114
Additional Static Resistance (Continued)
Model

NC300

CFM

Hot Water Coil

Steam Coil

8000

0.06

0.11

9000

0.07

0.14

10000

0.08

0.17

11000

0.09

0.20

12000

0.10

0.23

CFM Static Pressure and Power-Altitude and
Temperature Corrections

order to use the indoor blower tables for high altitude
applications, certain corrections are necessary.

The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.

A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
shown in Altitude Factors Table and Temperature Correction
Figure.

The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In

70

Johnson Controls Unitary Products

505428-YTG-R-1114

Altitude/Temperature Correction Factors Table
Air
Temp.
40
50
60
70
80
90
100

0
1.060
1.039
1.019
1.000
0.982
0.964
0.946

1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912

2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880

3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848

4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817

Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787

6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758

7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730

8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703

9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676

10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651

1.100
1.050

Correction Factor

1.000
Sea Level

0.950

1000 ft

0.900

2000 ft

0.850

3000 ft

0.800

5000 ft

0.750

6000 ft
7000 ft

4000 ft

8000 ft

0.700

9000 ft
10000 ft

0.650
0.600
40

50

60

70

80

90

100

Air Temperature (ºF)

Altitude/Temperature Correction Factors Figure
The examples below will assist in determining the airflow
performance of the product at altitude.

blower tables to select the blower speed and the BHP
requirement.

Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower
performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: As in the example above, no temperature
information is given so 70°F is assumed.

Solution: At an elevation of 5,000 ft. the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, the
Altitude/Temperature Correction Factors table must be used to
determine the static pressure and BHP. Since no temperature
data is given, we will assume an air temperature of 70°F. The
table shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit

Johnson Controls Unitary Products

The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66

71

505428-YTG-R-1114

Drive Selection
1.

Determine Upflow or Horizontal supply duct Application.

2.

Determine desired airflow.

3.

Calculate or measure the amount of external static pressure.

4.

Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower
performance table. (Linear interpolation may be necessary.)

5.

Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.

6.

Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.

7.

Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.

8.

Determine turns open to obtain the desired operation point.

Example
1.

3250 CFM

2.

1.4 iwg

3.

Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.

4.

Using the RPM selection table below, Model X is found.

5.

1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6.

1100 RPM is within the range of the 2 HP drives.

7.

Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.

Airflow Performance
Example Supply Air Blower Performance
(CFM)

Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive

3000
3250
3500

696
729
766

0.9
1.1
1.3

757
790
826

1.1
1.3
1.5

822
855
892

1.2
1.4
1.6

891
924
953

1.3
1.5
1.6

961
984
1010

High Static 2 HP & Drive

1.3
1.6
1.8

1019
1042
1069

1.5
1.7
1.9

1077
1100
1127

1.6
1.8
2.0

1135
1159

1.8
2.0

RPM Selection
Unit Model
X

72

HP
Std.
HS

1.5
2

Max
BHP
1.73
2.30

Motor
Sheave
1VL40
1VL40

Blower
Sheave
AK69
AK56

6 Turns
Open
N/A
N/A

5 Turns
Open
690
863

4 Turns
Open
743
929

3 Turns
Open
796
995

2 Turns
Open
849
1062

1 Turn
Open
902
1128

Fully
Closed
955
1194

Johnson Controls Unitary Products

505428-YTG-R-1114

Sound Performance
Outdoor Sound Power Levels (dB), 60 Hz
Size
(Tons)
090
(7.5)
120
(10.0)
150
(12.5)
180
(15.0)

240
(20.0)
300
(25.0)
1

Model

Sound
Rating1

PC090
YC090
PC120
YC120
YD120
YC150
YD150
PC180
PD180
YC180
YD180
PC240
PD240
YC240
YD240
YC300

89
89
89
90
90
91
91
93
93
89
89
93
93
93
93

63
88
88
88
91
92
96
92
93
93
88
88
93
93
93
93

125
90
89
90
87
89
88
92
96
96
90
90
96
96
96
96

250
89
89
89
90
91
90
92
93
93
89
89
93
93
93
93

93

93

96

93

Octave Bands (Hz)
500
1000
87
84
87
84
87
84
88
85
88
85
89
86
89
86
90
89
90
89
87
84
87
84
90
89
90
89
90
89
90
89
90

89

2000
81
81
81
80
80
82
81
84
84
81
81
84
84
84
84

4000
77
78
77
76
77
77
78
77
77
77
77
77
77
77
77

8000
72
73
72
70
71
71
73
71
71
72
72
71
71
71
71

84

77

71

Rated in accordance with AHRI 270 Standard.

Johnson Controls Unitary Products

73

505428-YTG-R-1114

Electrical Data
Electrical Data For Outdoor Models
Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Compressors
Model

YC090

YC120

YD120

YC150

YD150

YC180

YD180

YC240

YD240

YC300

1
2

74

Outdoor Fan Motor

Pwr Conv Outlet

Qty

FLA
(each)

FLA

Minimum
Circuit
Ampacity1

Maximum
Fuse Size
(A)2

1/3

2

2.1

-

35.5

45

1/3

2

1.2

-

17.6

25

575-1-60

1/3

2

0.9

-

13.1

20

137

208/230-1-60

3/4

2

3.0

-

46.8

60

14.0

62

460-1-60

3/4

2

1.6

-

23.5

30

10.6

50

575-1-60

3/4

2

1.4

-

18.0

20

16.0

25

110

208/230-1-60

3/4

2

3.0

-

42.1

50

2

7.8

12

52

460-1-60

3/4

2

1.6

-

20.8

25

2

5.7

9

39

575-1-60

3/4

2

1.4

-

15.5

20

2

22.4

35

149

208/230-1-60

3/4

2

3.0

-

56.5

70

460-3-60

2

10.6

17

75

460-1-60

3/4

2

1.6

-

27.1

35

575-3-60

2

7.7

12

54

575-1-60

3/4

2

1.4

-

20.0

25

208/230-3-60

2

22.4

35

149

208/230-1-60

3/4

2

3.0

-

56.5

70

460-3-60

2

10.6

17

75

460-1-60

3/4

2

1.6

-

27.1

35

575-3-60

2

7.7

12

54

575-1-60

3/4

2

1.4

-

20.0

25

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

208/230-3-60

2

48.1

75

245

208/230-1-60

3/4

4

3.0

-

120.3

150

460-3-60

2

18.6

29

125

460-1-60

3/4

4

1.6

-

48.3

60

575-3-60

2

14.7

23

100

575-1-60

3/4

4

1.4

-

38.5

50

Qty

RLA
(each)

MCC
(each)

LRA
(each)

Power
Supply

HP

208/230-3-60

1

25.0

39

164

208/230-1-60

460-3-60

1

12.2

19

100

460-1-60

575-3-60

1

9.0

14

78

208/230-3-60

2

18.1

28.3

460-3-60

2

9.0

575-3-60

2

6.8

208/230-3-60

2

460-3-60
575-3-60
208/230-3-60

Power
Supply

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Unitary Products

505428-YTG-R-1114

Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet
Compressors
Model

YC090

YC120

YD120

YC150

YD150

YC180

YD180

YC240

YD240

YC300

1
2

Outdoor Fan Motor

Pwr Conv Outlet

Qty

FLA
(each)

FLA

Minimum
Circuit
Ampacity1

Maximum
Fuse Size
(A)2

1/3

2

2.1

10.0

45.5

60

1/3

2

1.2

5.0

22.6

30

575-1-60

1/3

2

0.9

4.0

17.1

25

137

208/230-1-60

3/4

2

3.0

10.0

56.8

70

14.0

62

460-1-60

3/4

2

1.6

5.0

28.5

35

10.6

50

575-1-60

3/4

2

1.4

4.0

22.0

25

16.0

25

110

208/230-1-60

3/4

2

3.0

10.0

52.1

60

2

7.8

12

52

460-1-60

3/4

2

1.6

5.0

25.8

30

2

5.7

9

39

575-1-60

3/4

2

1.4

4.0

19.5

25

208/230-3-60

2

22.4

35

149

208/230-1-60

3/4

2

3.0

10.0

66.5

80

460-3-60

2

10.6

17

75

460-1-60

3/4

2

1.6

5.0

32.1

40

575-3-60

2

7.7

12

54

575-1-60

3/4

2

1.4

4.0

24.0

30

208/230-3-60

2

22.4

35

149

208/230-1-60

3/4

2

3.0

10.0

66.5

80

460-3-60

2

10.6

17

75

460-1-60

3/4

2

1.6

5.0

32.1

40

575-3-60

2

7.7

12

54

575-1-60

3/4

2

1.4

4.0

24.0

30

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

10.0

89.8

110

Power
Supply

Qty

RLA
(each)

MCC
(each)

LRA
(each)

Power
Supply

HP

208/230-3-60

1

25.0

39

164

208/230-1-60

460-3-60

1

12.2

19

100

460-1-60

575-3-60

1

9.0

14

78

208/230-3-60

2

18.1

28.3

460-3-60

2

9.0

575-3-60

2

6.8

208/230-3-60

2

460-3-60
575-3-60

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

5.0

49.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

4.0

36.9

45

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

10.0

89.8

110

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

5.0

49.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

4.0

36.9

45

208/230-3-60

2

48.1

75

245

208/230-1-60

3/4

4

3.0

10.0

130.3

175

460-3-60

2

18.6

29

125

460-1-60

3/4

4

1.6

5.0

53.3

70

575-3-60

2

14.7

23

100

575-1-60

3/4

4

1.4

4.0

42.5

50

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Unitary Products

75

505428-YTG-R-1114

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
Compressors
Model

PC090

PC120

PC180

PD180

PD240

1
2

Power
Supply

Outdoor Fan Motor

Pwr Conv Outlet

Qty

FLA
(each)

FLA

Minimum
Circuit
Ampacity1

Maximum
Fuse Size
(A)2

1/3

2

2.1

-

35.5

45

1/3

2

1.2

-

17.6

25

575-1-60

1/3

2

0.9

-

13.1

20

208/230-1-60

3/4

2

3.0

-

41.4

50

Qty

RLA
(each)

MCC
(each)

LRA
(each)

Power
Supply

HP

208/230-3-60

1

25.0

39

164

208/230-1-60

460-3-60

1

12.2

19

100

460-1-60

575-3-60

1

9.0

14

78

208/230-3-60

2

15.7

24.5

110

460-3-60

2

7.7

12.0

52

460-1-60

3/4

2

1.6

-

20.8

25

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

Pwr Conv Outlet

Maximum
Fuse Size
(A)2

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
Compressors
Model

PC090

PC120

PC180

PD180

PD240

1
2

76

Power
Supply

Outdoor Fan Motor
Qty

FLA
(each)

FLA

Minimum
Circuit
Ampacity1

1/3

2

2.1

10.0

45.5

60

1/3

2

1.2

5.0

22.6

30

575-1-60

1/3

2

0.9

4.0

17.1

25

208/230-1-60

3/4

2

3.0

10.0

51.4

60

Qty

RLA
(each)

MCC
(each)

LRA
(each)

Power
Supply

HP

208/230-3-60

1

25.0

39

164

208/230-1-60

460-3-60

1

12.2

19

100

460-1-60

575-3-60

1

9.0

14

78

208/230-3-60

2

15.7

24.5

110

460-3-60

2

7.7

12.0

52

460-1-60

3/4

2

1.6

5.0

25.8

30

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

10.0

89.8

110

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

5.0

49.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

4.0

36.9

45

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Unitary Products

505428-YTG-R-1114

Electrical Data For Indoor Models
Electrical Data - Indoor Units
Motor HP

Power Supply

Supply
Blower
Motor
FLA

208-3-60

5.0

230-3-60

5.2

460-3-60

2.5

575-3-60

2.0

1.5

208-3-60

6.6

230-3-60

6.8

460-3-60

3.4

575-3-60

2.4

2.0

Johnson Controls Unitary Products

MCA1
(Amps)

Max Fuse2/
Breaker3 Size
(Amps)

--20.8
33.4
54.2
75.1
--24.1
38.5
62.5
86.6
--12.0
19.2
31.3
43.3
--9.6
15.4
25.0
34.6

6.3
32.3
47.9
73.9
99.9
6.5
36.6
54.6
84.7
114.8
3.1
18.2
27.2
42.2
57.3
2.5
14.5
21.7
33.8
45.8

15
35
50
80
100
15
40
60
90
125
15
20
30
45
60
15
15
25
35
50

--20.8
33.4
54.2
75.1
--24.1
38.5
62.5
86.6
--12.0
19.2
31.3
43.3
--9.6
15.4
25.0
34.6

8.3
34.3
49.9
75.9
101.9
8.5
38.6
56.6
86.7
116.8
4.3
19.3
28.3
43.3
58.4
3.0
15.0
22.2
34.3
46.3

15
35
50
80
110
15
40
60
90
125
15
20
30
45
60
15
15
25
35
50

Electric Heat Option
Model
KW
Stages
NC090C00B
None
----10 KW
7.5
1
16 KW
12
2
26 KW
19.5
2
36 KW
27
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2
NC090C00C, (NC/ND)120C00C
None
----10 KW
7.5
1
16 KW
12
2
26 KW
19.5
2
36 KW
27
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2
None
----10 KW
10
1
16 KW
16
2
26 KW
26
2
36 KW
36
2

Amps

77

505428-YTG-R-1114

Electrical Data - Indoor Units (Continued)
Motor HP

Power Supply

208-3-60

230-3-60

3.0

460-3-60

575-3-60

208-3-60

230-3-60

5.0

460-3-60

575-3-60

78

Supply
Blower
Motor
FLA

MCA1
(Amps)

Max Fuse2/
Breaker3 Size
(Amps)

--20.8
33.4
54.2
75.1
104.2
--24.1
38.5
62.5
86.6
120.3
--12.0
19.2
31.3
43.3
60.1
--9.6
15.4
25.0
34.6
48.1

12.0
38.0
53.6
79.7
105.7
142.5
11.8
41.8
59.9
89.9
120.0
132.0
5.9
20.9
29.9
45.0
60.0
66.0
4.5
16.5
23.7
35.8
47.8
52.6

15
40
60
80
110
150
15
45
60
90
125
150
15
25
30
45
60
70
15
20
25
40
50
60

--20.8
33.4
54.2
75.1
104.2
--24.1
38.5
62.5
86.6
120.3
--12.0
19.2
31.3
43.3
60.1
--9.6
15.4
25.0
34.6
48.1

17.5
43.5
59.1
85.2
111.2
148.0
17.5
47.6
65.6
95.7
125.8
137.8
8.8
23.8
32.8
47.8
62.9
68.9
6.5
18.5
25.7
37.8
49.8
54.6

20
45
60
90
125
150
20
50
70
100
150
150
15
25
35
50
70
70
15
20
30
40
50
60

Electric Heat Option

Model
KW
Stages
(NC/ND)120C00D, (NC/ND)180C00D
None
----10 KW
7.5
1
16 KW
12
2
9.6
26 KW
19.5
2
36 KW
27
2
37.6
2
50 KW4
None
----10 KW
10
1
16 KW
16
2
9.4
26 KW
26
2
36 KW
36
2
50
2
50 KW4
None
----10 KW
10
1
16 KW
16
2
4.7
26 KW
26
2
36 KW
36
2
50
2
50 KW4
None
----10 KW
10
1
16 KW
16
2
3.6
26 KW
26
2
36 KW
36
2
50
2
50 KW4
(NC/ND)180C00E
None
----10 KW
7.5
1
16 KW
12
2
14.0
26 KW
19.5
2
36 KW
27
2
50 KW
37.6
2
None
----10 KW
10
1
16 KW
16
2
14.0
26 KW
26
2
36 KW
36
2
50 KW
50
2
None
----10 KW
10
1
16 KW
16
2
7.0
26 KW
26
2
36 KW
36
2
50 KW
50
2
None
----10 KW
10
1
16 KW
16
2
5.2
26 KW
26
2
36 KW
36
2
50 KW
50
2

Amps

Johnson Controls Unitary Products

505428-YTG-R-1114

Electrical Data - Indoor Units (Continued)
Motor HP

Power Supply

Supply
Blower
Motor
FLA

208-3-60

14.0

230-3-60

14.0

460-3-60

7.0

575-3-60

5.2

208-3-60
230-3-60
460-3-60
575-3-60

16.7
15.2
7.6
6.1

5.0

5.0

208-3-60

21.7

230-3-60

20.0

460-3-60

10.0

575-3-60

7.8

208-3-60
230-3-60
460-3-60
575-3-60

24.2
22.0
11.0
9.0

7.5

7.5

1
2
3
4
5

Electric Heat Option
Model
KW
(NC/ND)240C00E
None
--20 KW
15
32 KW
24
52 KW
39.1
None
-20 KW
20
32 KW
32
52 KW
52
None
--20 KW
20
32 KW
32
52 KW
52
None
--20 KW
20
32 KW
32
52 KW
52
NC300C00N5
None
--None
--None
--None
--(NC/ND)240C00F
None
--20 KW
15
32 KW
24
52 KW
39.1
None
-20 KW
20
32 KW
32
52 KW
52
None
--20 KW
20
32 KW
32
52 KW
52
None
--20 KW
20
32 KW
32
52 KW
52
NC300C00N5
None
--None
--None
--None
---

MCA1
(Amps)

Max Fuse2/
Breaker3 Size
(Amps)

Stages

Amps

--1
2
2
--1
2
2
--1
2
2
--1
2
2

--41.7
66.7
108.4
--48.1
77.0
125.1
--24.1
38.5
62.5
--19.2
30.8
50.0

17.5
69.5
100.8
153.2
17.5
77.6
113.7
142.6
8.8
38.8
56.9
71.3
6.5
30.6
45.0
56.5

20
70
110
175
20
80
125
150
15
40
60
80
15
35
45
60

---------

---------

21.0
19.0
10.0
8.0

35
30
15
15

--1
2
2
--1
2
2
--1
2
2
--1
2
2

--41.7
66.7
108.4
--48.1
77.0
125.1
--24.1
38.5
62.5
--19.2
30.8
50.0

27.1
79.2
110.4
162.8
25.0
85.1
121.2
150.1
12.5
42.6
60.6
75.0
9.8
33.8
48.2
59.8

30
80
125
175
25
90
125
175
15
45
70
80
15
35
50
60

---------

---------

30.0
28.0
14.0
8.0

35
30
15
15

Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC.
(NC/ND)180C00D Models Only
Motors are not shipped with these models. Motor and Drive Kits are required.

Johnson Controls Unitary Products

79

505428-YTG-R-1114

Typical Wiring Diagrams
Air Conditioning Condensing Units
Typical YC090 Wiring Diagram

80

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical YC120 - 150 Wiring Diagram

Johnson Controls Unitary Products

81

505428-YTG-R-1114

Typical YD120 - 150 Wiring Diagram

82

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical YC180 Wiring Diagram

Johnson Controls Unitary Products

83

505428-YTG-R-1114

Typical YC240 Wiring Diagram

84

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical YC300 Wiring Diagram

Johnson Controls Unitary Products

85

505428-YTG-R-1114

Typical YD180 - 240 Wiring Diagram

86

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical YD300 Wiring Diagram

Johnson Controls Unitary Products

87

505428-YTG-R-1114

Heat Pump Units
Typical PC090 Wiring Diagram

88

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical PC120 Wiring Diagram

Johnson Controls Unitary Products

89

505428-YTG-R-1114

Typical PC180 Wiring Diagram

90

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical PC240 Wiring Diagram

Johnson Controls Unitary Products

91

505428-YTG-R-1114

Typical PD180 - 240 Wiring Diagram

92

Johnson Controls Unitary Products

505428-YTG-R-1114

Air Handling Units
Typical NC090 Wiring Diagram

Johnson Controls Unitary Products

93

505428-YTG-R-1114

Typical NC120 thru 240, 1.5 thru 5 HP Blower Motor Only Wiring Diagram

94

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical NC 240, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram

Johnson Controls Unitary Products

95

505428-YTG-R-1114

Typical NC 240, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram

96

Johnson Controls Unitary Products

505428-YTG-R-1114
Typical NC300 Indoor Unit Wiring Diagram

Johnson Controls Unitary Products

97

505428-YTG-R-1114

Typical ND120 thru 240, 1.5 thru 5 HP Blower Motor Only Wiring Diagram

98

Johnson Controls Unitary Products

505428-YTG-R-1114

Typical ND 240, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram

Johnson Controls Unitary Products

99

505428-YTG-R-1114
Typical ND 240, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram

100

Johnson Controls Unitary Products

505428-YTG-R-1114

Weights And Dimensions
Corner Weights & Center of Gravity AC/HP Units
Weight (lbs.)
Shipping
Operating
421
430
543
574
947
968
921
942
1090
1126
390
387
499
497
493
490
499
497
493
490
914
909
899
894
945
942
930
927
945
942

Model
PC090
PC120
PC180
PD180
PD240
YC090
YC120
YD120
YC150
YD150
YC180
YD180
YC240
YD240
YC300

Center of Gravity (in.)
X
Y
17.3
33
16.4
32.3
32.5
33
34
32.5
31.2
31.8
17
32.3
17.3
32.3
17.4
32.5
17
32.3
17.4
32.5
32.5
31.5
32.5
31.5
30.3
31.0
32.7
31.8
30.3
31.0

A
110
153
266
243
311
99
124
123
127
123
239
235
261
244
261

4 Point Load Location (lbs.)
B
C
130
103
161
134
274
217
275
225
295
253
113
94
147
122
147
120
145
120
147
120
246
215
242
212
234
212
255
218
234
212

D
87
127
211
199
267
82
103
100
105
100
209
206
236
210
236

LEFT

A

D
LEFT
DIM X

A

D
CG

DIM X

CG
FRONT

REAR

FRONT

REAR

WIDTH

B

C

WIDTH
DIM Y
LENGTH
RIGHT
PC090, PC120,
YC090, YC120, YD120,
YC150, YD150

B

C
DIM Y
LENGTH
RIGHT
PC180, PD180,
PC240, PD240,
YC180, YD180,
YC240, YD240,
YC300

NOTE: Front of unit is considered the side having the unit
control box.

Johnson Controls Unitary Products

101

505428-YTG-R-1114

RIGHT

31.90

REAR

FRONT

LEFT
59.10

CONVENIENCE
OUTLET

BASE RAIL
DETAIL

A

2.375

30.994

2X (Ø 1.375)
KNOCKOUT

TOP

2X (Ø 0.875)
KNOCKOUT

1.33

12.126

3.43
3.75

9.876
4.751

2.097
BOTTOM

7.000
2.923
3.563

10.000

3.883

7.000

3.664

24.000

2.933

31.758

1.664

7.000

23.000

7.000

37.000

58.500

FRONT

RIGHT

SYSTEM 2

2X (Ø 0.875)
KNOCKOUT
2X (Ø 1.375)
KNOCKOUT
15.53
12.70
10.000

SYSTEM 1

12.000

4.875
6.26
7.52
8.98

REAR

10.60

4.132
2.382

LEFT

1.882

Unit Dimensions PC090, PC120, YC090, YC/YD120, YC/YD150

Unit Height Dimensions
MODEL
PC090
PC120
YC090
YC120
YD120
YC150
YD150

102

A
44.5
50.0
44.5
50.0
50.0
50.0
50.0

Johnson Controls Unitary Products

505428-YTG-R-1114

REAR

59.10

RIGHT

LEFT

FRONT
64.10

BASE RAIL
DETAIL
A
2.375

SYSTEM 2
SYSTEM 1

TOP

2X (Ø 1.375)
KNOCKOUT

30.994
1.33

3.43

11.375

3.75

2X (Ø 0.875)
KNOCKOUT
9.125
4.750

2.097
BOTTOM
2.923

7.000

23.000

7.000

37.000
64.000

3.563

4.132
3.913
3.181
1.913

FRONT

7.000

23.000
37.000

7.000

59.000

RIGHT

SYSTEM 2

SYSTEM 1

16.133
13.133

17.367
18.867
20.617
22.617

FRONT
(PIPING DETAIL)

Unit Dimensions PC/PD180, PC/PD240, YC/YD180, YC/YD240

Johnson Controls Unitary Products

103

505428-YTG-R-1114

Unit Height Dimensions
MODEL

A

PC180

44.5

PD180

44.5

PC240

50.0

PD240

50.0

YC180

44.5

YD180

44.5

YC240

50.0

YD240

50.0

YC300

50.0

PIPING AND ELECTRICAL CONNECTIONS
Piping connections are made from the rear of 7.5 thru 12.5
Ton units and the front of 15 thru 20 Ton units. Connections
can be made directly to the suction and liquid line service
valves.

and Piping and Electrical Connection Sizes tables for piping
sizes and electrical knockout details.

UNIT CLEARANCES

With the piping connections being made at the rear of 7.5
thru 12.5 Ton units and the front of 15 thru 20 Ton units, the
piping can be routed to the units from the left or right side.
Electrical connections for power and control wiring are made
from the front of the units, right or left of 7.5 thru 12.5 Ton
electrical control box access or left of the electrical control
box access on 15 thru 20 Ton units. See Unit Dimensions

1

Location

Dimensions

Overhead (Top)1
Front access panels
Left Side
Right Side
Rear
Bottom2

120”
36”
30”
30”
24”
0”

Units must be installed outdoors. Overhanging structures or shrubs
should not obstruct condenser air discharge.

Piping And Electrical Connection Sizes (Inches)
MODEL

PC090

PC120

YC090

YC120

YD120

YC150

YD150

1

1

1

1

2

1

2

1 1/8

1 3/8

1 3/8

1 3/8

1 1/8

1 3/8

1 1/8

5/8

7/8

5/8

7/8

5/8

7/8

5/8

Power Wiring Knockout

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

Control Wiring Knockout

7/8

7/8

7/8

7/8

7/8

7/8

7/8

PC180

PD180

PC240

PD240

YC180

YD180

YC240

YD240

YC300

1

2

1

2

1

2

1

2

1

1 5/8

1 3/8

1 5/8

1 3/8

1 5/8

1 3/8

1 5/8

1 3/8

1 5/8

7/8

5/8

7/8

5/8

7/8

5/8

7/8

5/8

7/8

Power Wiring Knockout

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

1 3/8

Control Wiring Knockout

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)

MODEL
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)

104

Johnson Controls Unitary Products

505428-YTG-R-1114

Corner Weights & Center of Gravity NC/ND 090 Thru 240 Units
Model

Center of Gravity
4 Point Load Location (lbs.)
(in.)
Shipping Operating
X
Y
A
B
C
D

6 Point Load Location (lbs.)

Weight (lbs.)

Drive Options

A

B

C

D

E

F

Vertical Airflow
NC090
NC120
ND120
NC180
ND180
NC240
ND240

Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.

524
526
562
573
564
575
769
797
769
797
908
938
908
938

498
500
539
550
541
552
737
765
737
765
873
903
873
903

16.2
16.2
15.5
15.5
15.5
15.5
18.0
18.0
18.0
18.0
15.8
15.7
15.8
15.7

26.7
26.7
26.8
26.7
26.9
26.9
34.4
34.4
34.4
34.4
42.6
42.4
42.6
42.4

109
110
125
127
126
128
155
161
155
161
179
185
179
185

128
129
134
136
135
137
185
192
185
192
198
204
198
204

141
142
146
148
145
148
216
224
216
224
260
269
260
269

120
120
136
139
136
138
181
188
181
188
235
245
235
245

71
71
82
84
83
84
101
104
101
104
118
122
118
122

79
79
86
87
87
88
113
117
113
117
125
129
125
129

88
88
90
91
91
92
127
132
127
132
134
138
134
138

97
97
98
100
98
100
148
154
148
154
176
182
176
182

86
87
94
96
94
95
131
136
131
136
165
171
165
171

78
78
89
91
89
91
117
122
117
122
154
161
154
161

524
526
562
573
564
575
769
797
769
797
908
938
908
938

498
500
539
550
541
552
737
765
737
765
873
903
873
903

30.1
30.1
29.9
30.2
29.9
30.2
33.2
33.8
33.2
33.8
30.1
30.6
30.1
30.6

26.7
26.7
26.8
26.7
26.9
26.9
34.4
34.4
34.4
34.4
42.6
42.4
42.6
42.4

118
119
129
130
131
132
169
172
169
172
188
191
188
191

119
120
129
132
130
133
171
181
171
181
189
198
189
198

131
132
140
145
140
144
199
211
199
211
249
262
249
262

130
130
141
142
141
142
197
201
197
201
247
252
247
252

79
79
86
87
87
88
113
114
113
114
125
126
125
126

79
79
86
87
87
88
114
118
114
118
126
130
126
130

79
80
86
88
86
89
114
122
114
122
126
133
126
133

87
88
94
97
93
96
133
142
133
142
166
176
166
176

87
87
94
96
94
96
132
137
132
137
165
171
165
171

87
87
94
95
94
95
131
133
131
133
164
167
164
167

Horizontal Airflow
NC090
NC120
ND120
NC180
ND180
NC240
ND240

Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
Std. Mtr. and Drv.
High Static Mtr. and Drv.
LEFT

LEFT

A
A

B
C

B

A
A

B
C

B

WIDTH

WIDTH
FRONT

CG

REAR

CG

REAR

FRONT

DIM Y

DIM Y

F
D

E

D
C

E

F
D

D
C

DIM X

DIM X
LENGTH
RIGHT

LENGTH
RIGHT

HORIZONTAL POSITION

VERTICAL POSITION

Johnson Controls Unitary Products

105

505428-YTG-R-1114

Corner Weights & Center of Gravity NC300 Unit
Model

Drive HP

Evaporator
Section
Cabinet
Wt (lb)

Blower Drive
Weight
Center of
Section Section
(lbs.)
Gravity
Cabinet Cabinet Ship Opera
CG X CG Y
Wt (lb) Wt (lb) ping ting

4 Point Load Location
(lbs.)
A

B

C

D

6 Point Load Location
(lbs.)
A

B

C

D

E

F

Vertical Airflow
NC300

5
7.5

539
539

463
463

111
138

1067 1130
1067 1157

19.0
19.3

45.5
45.1

296
301

321
335

267
274

247
246

204 220 194 172 159 180
206 229 202 179 161 181

463
463

111
137.8

1067 1130
1067 1157

35.2
35.4

45.5
45.1

320
329

297
307

247
252

266
269

220 204 180 160 172 194
225 210 185 164 176 198

Horizontal Airflow
5
7.5

539
539

D (E)

Y

(D) C

CG
(F)

(C)

A (A)

(B) B
Vertical

106

Y

(D) C

CG
(F)
X

MOTOR

X

D (E)

(C)
MOTOR

NC300

A (A)

(B) B
Horizontal

Johnson Controls Unitary Products

505428-YTG-R-1114

TOP VIEW
Ø 1.72 KNOCKOUT
ELECTRIC HEAT

Ø 1.718 KNOCKOUT FOR
ELECTRIC HEAT

20.31

20.313

8.84

8.837

9.25

9.246

13.44
15.920

8.22

5.135

17.59

15.63

14.590

18.628

TOP VIEW - BLOWER OUTLET
NC/ND120 INDOOR

TOP VIEW - BLOWER OUTLET
NC090 INDOOR

FRONT AND SIDE VIEW
Ø 1.718 KNOCKOUT
POWER ACCESS

3.66

4.56

7.06

Ø 0.875 KNOCKOUT
POWER ACCESS

65.000

6.38
FIELD PIPING
CONNECTIONS
35.000
SYSTEM 2
20.531

17.85
15.50

SYSTEM 1
13.13
10.73
2.000

52.000
56.000

FRONT VIEW - RETURN AIR
NC090 / NC/ND120 INDOOR

2.000

DRAIN 3/4” ABS
PIPE CONNECTION

1.88

7.12

30.00

RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS

Unit Dimensions NC090/120 and ND120

Johnson Controls Unitary Products

107

505428-YTG-R-1114

BOTTOM VIEW
56.00
50.75

2.72

2.72

2.66

AIR IN

11.43

30.00

HORIZONTAL CONFIGURATION
30.00

35.00
30.00

60.00

Unit Dimensions NC090/120 and ND120 (Continued)

108

Johnson Controls Unitary Products

505428-YTG-R-1114

TOP VIEW
Ø 1.718 KNOCKOUT FOR
ELECTRIC HEAT

23.85

10.00

10.50

18.84

3.79

26.34

21.82
TOP VIEW - BLOWER OUTLET

FRONT AND SIDE VIEW
3.66
4.56

7.06

1-1/4” CONDUIT
KNOCKOUT Ø 1.718
POWER ACCESS
1/2” CONDUIT
KNOCKOUT Ø 0.875
CONTROLS ACCESS

75.00

6.44
FIELD PIPING
CONNECTIONS

42.00
27.53

SYSTEM 2

17.85
15.50
13.13

SYSTEM 1
10.73
2.00

70.50
74.50
FRONT VIEW - RETURN AIR
NC/ND180 INDOOR

2.00

DRAIN 3/4” ABS
PIPE CONNECTION

7.12

1.88

33.00
RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS

Unit Dimensions NC/ND180

Johnson Controls Unitary Products

109

505428-YTG-R-1114

BOTTOM VIEW
74.50
2.72

69.25

2.72

2.66

AIR IN

14.43

33.00

HORIZONTAL CONFIGURATION
33.000

42.000

33.000

66.000

Unit Dimensions NC/ND180 (Continued)

110

Johnson Controls Unitary Products

505428-YTG-R-1114

TOP VIEW
1-1/4” CONDUIT KNOCKOUT
(Ø 1.718)
ELECTRIC HEAT CONTROL
WIRE CONNECTION

1-1/4” CONDUIT KNOCKOUT
(Ø 1.718)
ELECTRIC HEAT POWER
CONNECTION

22.86

8.83

9.25
15.90
BLOWER OPENING
9.25

5.14

4.14
1-1/4” CONDUIT KNOCKOUT
(Ø 1.718)
ELECTRIC HEAT CONTROL
WIRE CONNECTION
25.30

1-1/4” CONDUIT KNOCKOUT
(Ø 1.718)
ELECTRIC HEAT POWER
CONNECTION
18.63
BLOWER OPENING
18.63
BLOWER OPENING

54.57
75.64

TOP VIEW BLOWER OUTLET
NC/ND240 INDOOR

FRONT AND SIDE VIEW
3.66

4.56

7.06

1-1/4” CONDUIT
KNOCKOUT (Ø 1.718)
POWER ACCESS
1/2” CONDUIT
KNOCKOUT (Ø 0.875)
CONTROLS ACCESS
65.13

6.44
FIELD PIPING
CONNECTIONS

SYSTEM 2
35.00

17.85
15.50
13.13
10.73

19.19
SYSTEM 1

2.56
44.91

3.56
93.37
98.50

FRONT VIEW - RETURN AIR
NC/ND240 INDOOR

2.56

1.88

DRAIN 3/4” ABS
PIPE CONNECTION

7.12

30.00

RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS

Unit Dimensions NC/ND240

Johnson Controls Unitary Products

111

505428-YTG-R-1114

BOTTOM VIEW
98.50
2.72

45.38

50.59
45.38

2.72
2.66

AIR IN

AIR IN

11.43

30.00

HORIZONTAL CONFIGURATION
30.00

35.00
30.00

60.00

Unit Dimensions NC/ND240 (Continued)

112

Johnson Controls Unitary Products

505428-YTG-R-1114

BLOWER

POSITION
1

EVAPORATOR
COIL

POSITION
5

POSITION
2

POSITION
6

POSITION
3

POSITION
7

POSITION
4

POSITION
8

Vertical Airflow Arrangements NC090-240 and ND120-240

POSITION
1

POSITION
2

POSITION
3

POSITION
4

POSITION
5

POSITION
6

POSITION
7

POSITION
8

Horizontal Airflow Arrangements NC090-240 and ND120-240

Johnson Controls Unitary Products

113

505428-YTG-R-1114

TOP VIEW
22.03

62.37
22.49

5.31

22.02

5.31

2.58
9.05

3.00
19.03

4X Ø.88 K0
CONTROLS
CONNECTION

15.92

Ø 0.88 K0
ELECTRIC HEAT
CONNECTION

57.69

FRONT AND SIDE VIEW

36.69

74.59

Ø 1.38 KO
Ø 0.88 LIQUID
CONNECTION

37.28
33.22

Ø 2.13 SUCTION
CONNECTION
Ø 1.38 KO
24.98
Ø 0.88 DRAIN
CONNECTION
7.64
3.53

2.36
46.97

3.37
4.08
4.22

0.63
95.59
100.13
FRONT (RETURN AIR) VIEW

38.06
RIGHT SIDE
(SERVICE CONNECTION) VIEW

Unit Dimensions NC300

114

Johnson Controls Unitary Products

505428-YTG-R-1114

HORIZONTAL CONFIGURATION

RETURN
AIR

SUPPLY
AIR

73.3
74.0

Unit Dimensions NC300 (Continued)

1
AIR

BLOWER

3

2
AIR

AIR

AIR

EVAPORATOR
COIL

AIR

4

AIR

5

6
AIR

AIR

AIR

AIR

AIR

Vertical Airflow Arrangements NC300
NOTE: *If required, some air can be returned through the bottom of the evaporator section

Johnson Controls Unitary Products

115

7

AIR

505428-YTG-R-1114

8

9

AIR
AIR

AIR

AIR

11

AIR

AIR

10

12
AIR

AIR

AIR
AIR

AIR

Horizontal Airflow Arrangements NC300
PIPING, ELECTRICAL AND DUCT OPENING CONNECTION SIZES
MODEL

NC090

NC120

ND120

NC180

ND180

NC240

ND240

NC300

SYSTEM DATA
No. Refrigeration Circuits
Suction Line OD (in.)
Liquid Line OD (in.)
Power Wiring Knockout
Control Wiring Knockout
Electric Heat Wiring Knockout
Drain Line Fitting PVC Stub

1

1

2

1

2

1

2

1

1 1/8

1 3/8

1 1/8

1 5/8

1 3/8

1 5/8

1 3/8

2 1/8

5/8

7/8

5/8

7/8

5/8

7/8

7/8

7/8

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

7/8
7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

1 3/4

7/8

3/4

3/4

3/4

3/4

3/4

3/4

3/4

7/81

BLOWER OUTLET
Number
Width
Length

1

1

1

1

1

2

2

2

13.4

15.9

15.9

18.9

18.9

15.9

15.9

22

15.6

18.6

18.6

21.6

21.6

18.6

18.6

22

RETURN AIR INLET
Width

20.5

20.5

20.5

27.3

27.3

19.2

19.2

33.2

Length

52.0

52.0

52.0

71.9

71.9

93.4

93.4

95.6

1

7/8 In Steel pipe

Minimum Clearances
Minimum Clearances
Top with Supply Air Opening1
Front with Return Air Opening
Right Side with access for Piping, Power &
Control Wiring Connections2
Left Side
Rear3
Bottom4
1
2
3

4

116

24”
24”
24”
24”
N/A
N/A

This dimension will vary if an electric heater, a supply air
plenum or a base is used.
This dimension is required for normal installation and
service.
Although no clearance is required for service and
operation, some clearance may be required for routing
the power and control wiring.
Allow enough clearance to trap the condensate drain
line.
Note: If the coil has to be removed, the blower section
can be unbolted and set aside and the coil can be
lifted out the top of the evaporator section.

Johnson Controls Unitary Products

505428-YTG-R-1114
Unit Mounting - NC/ND 090 Thru 240
The split air handling units can be applied in various
horizontal positions. The Typical Suspension of AHU’s From
Ceiling Figure shows recommended suspension rigging
using properly sized all-thread and metal c-channel. All

components to suspend an AHU must be field supplied.
Please refer to the units total weight, center of gravity and
corner weights. (Horizontal position) shown in the appropriate
table for proper support sizing.

END VIEW

MOUNTING DETAIL
All Thread
Steel Rod
Mounting
Bracket
Flat Washer /
Lock Washer
and Nut
Steel Cchannel

SIDE VIEW

Typical Suspension of AHU’s From Ceiling

Johnson Controls Unitary Products

117

505428-YTG-R-1114

Unit Mounting - NC300

channels and hardware. The channels extend across the
evaporator coil section, the heating coil section (if included)
and the blower section. Each channel is to be bolted to each
section as shown.

The NC300 evaporator blower may be suspended from the
joists with isolation type hangers or hooks. Suspension
accessories 1HH0403 (NC300) may be ordered separately.
All Suspension accessories include three suspension

HORIZONTAL
UNIT SUSPENDED
FROM ABOVE 3
AX

D

BX

C

E

BX

VERTICAL UNIT SUPPORTED
FROM BELOW

3
BLOWER
SECTION

F
1-1/2
EVAP . COIL
SECTION
U3

O
U

B
BLOWER
SECTION

A

EVAP.
COIL
SECTION
A

HEATING COIL 2
F
SUSPENSION
ANGLES 1

E

C
D

CX

4

B

BX
BX

1 The same channels can be used in either position. When used to

support a vertical unit, these channels should be cut to match the
bottom dimension of the evaporator section.

2

The suspension channels have two sets of mounting holes to
accommodate horizontal units with or without a heating coil. On
a horizontal unit without a heating coil, the suspension channels
will extend 3” beyond both ends of the unit.

3 The same channels can be used to support a horizontal, floor-

mounted unit from below.

4 After these bottom channels are cut per Note 1, a new hole will have
to be drilled at the cut end if the unit is to be mounted on isolators.

Typical Suspension of NC300

Unit Mounting Dimensions- NC300
UNIT
NC300

118

DIMENSIONS, INCHES
AX
69-1/4

BX
49-1/16

CX
26-5/8

Johnson Controls Unitary Products

505428-YTG-R-1114

NOTE: Do not use a heat pump thermostat.
R C Y1 G W1 W2

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is not included or required
on 7.5 Ton Single Stage Units.

Typical Field Wiring Diagram - NC090 Evaporator Unit with PC090 Heat Pump

Johnson Controls Unitary Products

119

505428-YTG-R-1114

NOTE: Do not use a heat pump thermostat.
R C Y1 G Y2 W1 W2

THERMOSTAT
TWO STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is only activated during
second stage cooling operation.

Typical Field Wiring Diagram - NC120 thru 240 Evaporator Unit with PC120 thru 240 Heat Pump

C

O

VALVE SYS 2
BLK
1LLS
BLK

218 / BR
219 / Y

I

L

NC120 - 240 Liquid Line Solenoid Wiring

120

Johnson Controls Unitary Products

505428-YTG-R-1114

R C Y1 G Y2 W1 W2

NOTE: Do not use a heat pump thermostat.

THERMOSTAT
TWO STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is not included or required
on any 4 pipe units.

Typical Field Wiring Diagram - ND180 thru 240 Evaporator Unit with PD180 thru 240 Heat Pump

Johnson Controls Unitary Products

121

505428-YTG-R-1114

W1 W2 G C Y1 X R

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is not included or required
on 7.5 Ton Single Stage Units.

Typical Field Wiring Diagram - NC090 Evaporator Unit with YC090 Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

122

Johnson Controls Unitary Products

505428-YTG-R-1114

W1 W2 G C Y1 Y2 X R

THERMOSTAT
TWO STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is only activated during
second stage cooling operation.

Typical Field Wiring Diagram - NC120 thru 240 Evaporator Unit with YC120 thru 240 Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

C

O

VALVE SYS 2
BLK
1LLS
BLK

218 / BR
219 / Y

I

L

Johnson Controls Unitary Products

123

505428-YTG-R-1114
NC120 - 240 Liquid Line Solenoid Wiring

Typical Field Wiring Diagram - NC300 Evaporator Unit with YC300 Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

NC300 Liquid Line Solenoid Wiring

124

Johnson Controls Unitary Products

505428-YTG-R-1114

W1 W2 G C X Y1 Y2 R

THERMOSTAT
TWO STAGE COOLING
TWO STAGE HEATING

NOTE: Liquid line solenoid is not included or required
on any 4 pipe units.

Typical Field Wiring Diagram - ND120 thru 240 Evaporator Unit with YD120 thru 240 Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

Johnson Controls Unitary Products

125

505428-YTG-R-1114

Y1 R C G X W1 W2

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

Y1 R C G X W1 W2

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

Typical Field Wiring Diagram - Twin NC120 thru 240 Evaporator Units with 4-Pipe Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the
condensing unit.

C

O

VALVE SYS 2
BLK
1LLS
BLK

218 / BR
219 / Y

I

L

NC120 - 240 Liquid Line Solenoid Wiring

126

NOTE: Refer to Evaporator unit wiring diagram for control of
liquid line solenoid valve.
Johnson Controls Unitary Products

505428-YTG-R-1114

Y1 Y2 G X C R W1

THERMOSTAT
TWO STAGE COOLING
SINGLE STAGE HEATING

THERMOSTAT
TWO STAGE COOLING
SINGLE STAGE HEATING

Y1 Y2 G X C R W1

Typical Field Wiring Diagram - Single 4-Pipe Evaporator Unit with Twin Condenser Units
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

Johnson Controls Unitary Products

127

Y1 R C G X W1 W2

Y1 R C G X W1 W2

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

THERMOSTAT
SINGLE STAGE COOLING
TWO STAGE HEATING

Typical Field Wiring Diagram - Twin NC090 Evaporator Units with 4-Pipe Condenser Unit
NOTE: On non NC/ND Evaporator models, isolation relays
must be installed to avoid overloading on 75 VA
transformers on the condensing unit.

Subject to change without notice. Printed in U.S.A.
Copyright © 2014 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069

505428-YTG-R-1114
Supersedes: 505428-YTG-Q-0314



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Create Date                     : 2000:05:02 13:19:26Z
Creator                         : FrameMaker 12.0.3
Modify Date                     : 2014:11:18 16:05:34-06:00
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.150055, 2012/11/19-18:45:32
Creator Tool                    : FrameMaker 12.0.3
Metadata Date                   : 2014:11:18 16:05:34-06:00
Producer                        : Acrobat Distiller 11.0 (Windows)
Format                          : application/pdf
Title                           : untitled
Document ID                     : uuid:dafe662c-2fd3-43b0-a2b5-a44a30117f57
Instance ID                     : uuid:2bd61885-c709-4a60-ac93-417ed7eab78b
Page Mode                       : UseOutlines
Page Count                      : 128
EXIF Metadata provided by EXIF.tools

Navigation menu