100W

QP-100

1~3 Output with battery Charger

series

Features :
Universal AC input / Full range
Auto switch when power off (UPS function)
Built-in constant current limiting circuit
Alarm signal for AC OK and Battery low
(TTL open collector output or Relay contact output)
Protections: Short circuit / Over load / Over voltage
Brown-out (Low AC Input Voltage)
Battery low protection
Battery polarity protection
(by Resettable Fuses)
Cooling by free air convection
High efficiency, long life and high reliability
Withstand 2G vibration test
All using 105°c long life electrolytic capacitors
3 years warranty
QP-100-G

MODEL

Output

Input

Output Number
DC Voltage Range
Rated Current
Current Range
Rated Power
Ripple & Noise (max.)
Voltage Adj. Range
Voltage Tolerance
Line Regulation
Load Regulation
Setup, Rise Time
Hold up Time (Typ.)
Voltage Range
Frequency Range
Efficiency (Typ.) at 230Vac
AC Current (Typ.)
Inrush Current (Typ.)
Leakage Current
Over Load

Protection

Function

Environment

Safety & EMC

Others

Note

Over Voltage

QP-100-GB

QP-100-LB

CH1

CH2

CH1

CH2

CH3

CH1

CH2

CH1

CH2

CH3

13.8V

13.8V

13.8V

13.8V

5V

27.6V

27.6V

27.6V

27.6V

5V

5.3A

2A

4.2A

2A

3A

2.15A

1.5A

1.6A

1.5A

3A

0~7A

---------

0~6.5A

---------

0~3.2A

0~3.4A

---------

0~3.3A

---------

0~3.2A

---------

100mV

---------

100mV

100mV

---------

100mV

---------

100mV

±1%

---------

±1%

---------

±3%

±0.5%

---------

±0.5%

±0.5%

---------

±1%

100.56W

100.74W
100mV

100.74W

CH1:10%

100.56W

CH1:10%

±1%

---------

±1%

---------

±0.5%

---------

±0.5%

---------

±0.5%

±0.5%

---------

±0.5%

---------

±0.5%

---------

±1%

±0.5%

---------

800ms, 50ms/230VAC
50ms / 230VAC
90 ~ 264VAC

±3%

800ms, 50ms/115VAC at full load

10ms /115VAC at full load
127 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)

47Hz ~ 63Hz
86%

85%

2A /115VAC
Cold Start

87%

85%

1.2A / 230VAC
35A / 115VAC

70A / 230VAC

For earth <1mA / 264VAC
Above 110% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
115% ~ 140% rated output voltage
Protection type : latch-off mode

Battery cut off

10V±4%

AC OK
BAT Low
Working Temp.
Working Humidity
Storage Temp., Humidity
Temp. Coefficient
Vibration
Safety Standards
Withstand Voltage
Isolation Resistance
EMI Conduction & Radiation
Harmonic Current
EMS Immunity
MTBF

TTL open collector output

Dimension (L*W*H)(mm)
Packing

QP-100-L

20V±5%
Relay contact output

Battery low voltage <12V±3%

TTL open collector output

Relay contact output

Battery low voltage <22V±3%

-20°C ~ +70°C (Refer to output load de-rating curve)
20 ~ 90% RH non-condensing
-40 ~ +85°C, 10 ~90%
±0.03%/°C (0 ~ 50°C) on CH1
10 ~ 500Hz, 2G 10min./1 cycle, period for 60 min. each along X,Y,Z axes
Meet UL60950-1 / TUV EN60950-1 Approved
I/P - O/P : 3KVAC

I/P - FG : 1.5KVAC O/P-FG : 0.5KVAC

I/P - O/P: 100M Ω / 500VDC
EN55022 : 2006+A1:2007 Class B
EN61000-3-2 :2006 Class A, EN61000-3-3 : 1995+A1 : 2005
EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024
123x95x31mm

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47 uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rayed load.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still
meets EMC directives.
7.Length of aet up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.
REV. A6
10/12/08
1

100W

QP-100

1~3 Output with battery Charger

series

Mechanical Specification
Unit:mm

123
5
4

5.5

5

CN1

0.2

1
2
3

95

6.65

4
5
6
8.25

7

CN2 1

6.5

3.9

8
CN2

9

0.4

6.5
103.9

3

31

19.1

QP-100-G/L
Alarm output Connector(CN2): JST B3B-XH or equivalent

Terminal Pin No. Assignment(CN1)

Pin No.

Assignment

1

AC OK

Pin No.

Assignment

Pin No.

Assignment

2

BAT LOW

1

AC/L

5

DC output V+

3

G (13.8V/20mA)
L (27.6V/20mA)

2

AC/N

6

BAT+

3

FG

7

BAT-

8

DC/DC Output +5V
(GB/LB only)

DC Output com

4

Mating Housing
JST XHP-3
or equivalent

Terminal
JST
SXH-001 T-P0.6
or equivalent

QP-100-GB/LB
Alarm output Connector(CN2): JST B4B-XH or equivalent
Assignment

Pin No.
1 2

Mating Housing

Terminal

JST XHP-4
or equivalent

JST
SXH-001 T-P0.6
or equivalent

AC OK

3 4

Bat. Low

Mechanical Specification
Output Derating VS Input Voltage
Ta=25
100

100

90
80
80
70

LOAD (%)

LOAD (%)

60

40

20

-20

0

10

20

30 35 40

50

AMBIENT TEMPERATURE (

60

)

70 (HORIZONTAL)

60
50
40

90

95

100 115

120 140

160 180

200 220

240 264

INPUT VOLTAGE (VAC) 60Hz
REV. A6
10/12/08
2

100W

1~3 Output with battery Charger

QP-100

series

For QP-100-G/L
Block Diagram
AC OK

ALARM
CIRCUIT

EMI FILTER

I/P

RECTIFIER
&
FILTER

Bat. Low

V+

RECTIFIERS
&
FILTER

POWER
SWITCHING

COM
B+

FG
DETECTION
CIRCUIT
PWM
CONTROL

O.L.P.

O.V.P.

B-

Battery Charger
&
Back up Control

Alarm Signal for AC OK and Battery Low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins.
(2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA.
(3) Table3.1 explain the alarm function built-in the power supply
Function

AC OK

Battery
Low

Output of alarm

Description
The signal is "Low" when the power supply

Low

turns on

(0.3V max. at 30mA)

The signal turns to be "High" when the power

High or open(External applied

supply turns OFF

voltage 30mA max.)

The signal is "Low" when the voltage of

Low

battery is under G:12V , L:22V

(0.3V max. at 30mA)

The signal is "High" when the voltage of

High or open(External applied

battery is above G:12V , L:22V

voltage 30mA max.)

Table 3.1 Explanation of Alarm Signal

AC OK (Battery low)

V+

CN2 Pin3
G: 13.8V/20mA
L: 27.6V/20mA

CN2 Pin1(Pin2)

CN2 Pin3

R
V
CN1 Pin4 DC output com

Internal circuit of AC OK (Battery Low)

or
CN2 Pin1(Pin2)

External voltage and R
(The max. Sink is 30mA and 50V)

REV. A6
10/12/08
3

100W

1~3 Output with battery Charger

QP-100

series

For QP-100-GB/LB
Block Diagram
ALARM
CIRCUIT
&
SWITCHING
FILTER

I/P

EMI FILTER

RECTIFIER
&
FILTER

AC OK
Bat. Low
+5V

V+

RECTIFIERS
&
FILTER

POWER
SWITCHING

COM
B+

FG
DETECTION
CIRCUIT
O.L.P.

PWM
CONTROL
O.V.P.

B-

Battery Charger
&
Back up Control

Alarm Signal for AC OK and Battery Low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins. (relay contact type)
(2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1 A.
(3) Table 4.1 explain the alarm function built-in the power supply

AC OK(Battery low)
Function

Description
The signal is "Low" when the power supply

AC OK

turns on

High or open(External applied

supply turns OFF

voltage 1A max.)

battery is under GB:12V , LB:22V

CN2 Pin1(Pin3)

Low or short

The signal turns to be "High" when the power

The signal is "Low" when the voltage of

Battery
Low

Output of alarm

Low or short

The signal is "High" when the voltage of

High or open(External applied

battery is above GB:12V , LB:22V

voltage 1A max.)

Table 4.1 Explanation of Alarm Signal

Externalvoltagesource(V)
andresistor(R)
(Themax.Sinkis1A and30V)
lnternalcircuitof AC OK(BatteryLow)

CN2 Pin2(Pin4)

REV. A6
10/12/08
4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Print high-res
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Creation Date--Text             : 
Producer                        : Corel PDF Engine Version 3.0.0.739
Mod Date--Text                  : 
Format                          : application/pdf
Creator                         : esther
Title                           : QP-100_A6 1208
Creator Tool                    : CorelDRAW
Modify Date                     : 2010:12:09 10:42:53+08:00
Metadata Date                   : 2010:12:09 10:42:53+08:00
Document ID                     : uuid:73b69d5d-3344-4bcb-8b15-295155486ca7
Instance ID                     : uuid:8ade7d8a-ddaa-43c3-93e5-e4c9050cd17a
Page Count                      : 4
Create Date                     : D:20101208064622
Author                          : esther
EXIF Metadata provided by EXIF.tools

Navigation menu