ZTE WF 600T Series Sb 2000 Manual 20130620
User Manual: ZTE sb-2000 manual-20130620
Open the PDF directly: View PDF
.
Page Count: 64
| Download | |
| Open PDF In Browser | View PDF |
SB Series USER MANUAL PURE SINE WAVE INVERTER / CHARGER COMBI WITH SHARING / SUPPORT / GENERATOR Inverter / Charger COMBI Contents 1 2 3 4 5 Important Safety Instructions…………………………………………………………… 3 1-1 Warnings And Symbols…………………………………………………………… 3 1-2 Use For Intended Purpose General Safety Precautions……………………… 3 1-3 Other Safety Notes And Installation Precautions……………………………… 4 1-4 Warning Regarding The Use Of Batteries……………………………………… 4 Functional Characteristics Introduction……………………………………………… 5 2-1 System…………………………………………………….……………………….. 5 2-2 Electrical Performance……………………………………………………………. 6 2-3 Mechanical Drawing………………………………………………………………. 8 2-4 LCD Panel Mechanical Drawing………………………………………………… 9 How It Works………………………………………………………………………………. 9 3-1 Battery Charger Introduction…………………………………………………….. 9 3-2 Inverter Introduction………………………………………………………………. 12 3-3 Operation Modes………………………………………………………………….. 12 3-4 Equalization Batteries…....……………………………………………………….. 19 Operation…………………………………………………………………………………… 24 4-1 Power “ON” ……………...………………………………………………………... 24 4-2 Power “OFF………………………………………………………………………... 24 4-3 Selectable “CHR. Power ON” mode…………………………………………….. 24 4-4 Protections…………………………………………………………………………. 24 Installation And Maintenance…………………………………………………………… 24 5-1 Unpacking...……………………………………...……………………………….. 25 5-2 Front Panel...……………………………………...………………………………. 25 5-3 Move the LCD Control Panel Place..………...……………………………….. 34 1 Inverter / Charger COMBI 6 7 8 2 5-4 Rear Panel...……………………………………...……………………………….. 38 5-5 Installation Drawing...……………………………………...……………………... 39 LCD Remote Control Panel – Display & Setup...………………..…………………… 40 6-1 LCD Panel Indications……………………………………………………………. 40 6-2 LCD Rear View Introduction……………………………………………………... 43 6-3 Startup Sequence and Standby Status…………………………………………. 46 6-4 Setup Menu – Operation and Instructions Entering Setup Menu……………. 47 RS-232 Communication and Operation...…………………………………………….. 53 7-1 Operation of RS-232 serial port…………………………………………………. 53 7-2 Example of the RS232 Operation……………………………………………….. 54 Trouble Shooting………………………………………………………………………….. 63 8-1 Fault Indicator……………………………………………………………………… 63 8-2 Warranty……………………………………………………………………………. 64 Inverter / Charger COMBI 1 Important Safety Instructions 1.1 Warnings And Symbols Safety instructions and warnings are marked in this manual by the following pictograms: Supplementary information on operating the device. CAUTION Safety instruction: Failure to observe this instruction can cause material damage and impair the function of the device. CAUTION Safety instruction relating to a danger from an electrical current or voltage. Failure to observe this instruction can cause material damage and personal injury and impair the function of the device. WARNING! SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the Combi unit. 1.2 Use For Intended Purpose General Safety Precautions The Combi unit is constructed as per the applicable safety-technical guidelines. For the charging of lead acid batteries and the supply of users attached to these batteries, in permanent systems. For the conversion of a DC voltage from a battery to and AC voltage. Connected to a dedicated double pole circuit breaker and earth leakage switch. With a fuse, protection the wiring between Combi unit and battery. In a technical correct condition. Do not expose the Combi unit to rain, snow, spray or dust. To reduce the risk of fire hazard, do not cover or obstruct the ventilation openings and. do not install the Combi unit in a zero-clearance compartment. To avoid the risk of fire and electric shock, make sure that the existing wiring is in good electrical condition; and that the wire size is not undersized. Do not operate the Combi unit with damaged or substandard wiring. Depending on the use, the AC output of the Combi unit may require user installed breaker or fusing. For telecom use, a GFCI has not been provided. The Combi unit incorporates standard AC short circuit protection. The following precautions should be taken when working on the Inverter Charger: Remove watches, rings, or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. 3 Inverter / Charger COMBI 1.3 Other Safety Notes And Installation Precautions Upon receipt, examine the shipment box for damage. Notify the carrier immediately, before opening, if damage is evident. Do not operate near water or in excessive humidity. Do not open or disassemble the Combi unit, warranty may be voided. The DC and AC side connections should be firm and tight. Grounding: Reliable grounding of rack-mounted equipment should be maintained. Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery or on the other electrical part may cause an explosion. Wiring: Adequate input power must be supplied to the Combi unit for proper use; correct wiring sizes must be ensured. Do not operate the Combi unit close to combustible gas or open fire. Temperature: The Combi unit should be operated in an ambient temperature range of -20 to 40°C or else the output efficiency may be affected. Air flow to the Combi unit must not be restricted. In case of fire, you must use the fire extinguisher which is appropriate for electrical equipment. Short circuiting or reversing polarity will lead to serious damage to batteries, Combi unit and the wiring. Fuses between the batteries and the Combi unit can not prevent damage caused by reversed polarity and the warranty will be void. Do not work on Combi unit or system if it is still connected to a power source. Only allow changes in your electrical system to be carried out by qualified electricians. Check the wiring and connections at least once a year. Defects such as loose connections, burned cables etc. must be corrected immediately. Do not touch the equipment when wet or if your hands are clammy. The Combi unit products are not for applications in any medical equipment intended. The cabinet of the Combi unit must not be opened. There are no serviceable parts inside the cabinet. Only qualified, authorized and trained electrician installers are authorized to open the connection compartment. 1.4 Warning Regarding The Use Of Batteries Excessive battery discharge and/or high charging voltage can cause serious damage to batteries. Do not exceed the recommended limits of discharge level of your batteries. Avoid short circuiting batteries, as this may result in explosion and fire hazard. Installation of the batteries and adjustments of the Combi unit should only be undertaken by authorized personnel! 4 Inverter / Charger COMBI 2 Functional Characteristics Introduction 2.1 System The SB Series is a Combi inverter / charger system, designed with advanced power electronic and digital signal processor technology offering the following features: The Combi unit is equipped with a self diagnosis microprocessor that is able to identify and show all failure messages on the LED/LCD display, with associated visual/audio alarms. Can use parallel with the grid AC. Battery charger current 100A max. @12VDC / 50A max. @24VDC Pure sine wave output to operate higher-end electronic equipment 5A max second charger. Equalization function for the batteries. Built in 25A rated bypass switch Power sharing functions Intelligent software for power management Hard-wire connection model option Loading and temperature controlled cooling fan Fan aging, failure, disconnection and blockage alarm Local and remote management and control RS-232 and CAN Bus communication CAN Bus LCD remote control panel By a dry contact terminal Advanced protection features : DC input over/under voltage protection Internal over temperature, battery over temperature and heat sink over temperature DC input reverse polarity protection (Fuse) Inverter AC output overload protection Inverter AC output short circuit protection AC input short circuit protection: Breaker (30Amp) AC input under voltage protection 5 Inverter / Charger COMBI 2.2 Electrical Performance SB-2000 Inverter / Charger Specification Electrical Input Characteristics Specification Model No. Item SB2000-112 SB2000-124 SB2000-212 SB2000-224 Nominal Voltage 12 VDC 24 VDC 12 VDC 24 VDC Input Voltage Range 10.5 ~ 16 VDC 21 ~ 32 VDC 10.5 ~ 16 VDC 21 ~ 32 VDC Input Over-Voltage Protection 15 ~ 16 VDC 30 ~ 32 VDC 15 ~ 16 VDC 30 ~ 32 VDC Input Under-Voltage Protection 10.5 ~ 11.5 VDC 21 ~ 23 VDC 10.5 ~ 11.5 VDC 21 ~ 23 VDC No Load Current 5A 2.5 A 5A 2.5 A Stand-By Current 1.5 A 0.75 A 1.5 A 0.75 A Continuous Output Power(Resistive load) 2000 W Surge Power (Resistive load) Load 101%~115% (3 Min) Frequency 47 ~ 63 Hz +/- 0.01% (User-selectable) 4000 W Output Characteristics Output Voltage Efficiency (Full Load) 115 VAC (100~120 VAC)+/-5% >84% (At DC 12V) >86% (At DC 24V) >85% (At DC 12V) Short-Circuit Protection Output Waveform AC Input / Output Terminal Protection AC Input Characteristics >88% (At DC 24V) Yes , Ipk Pure Sine Wave (THD < 5%) Pure Sine Wave (THD < 3%) AC Input 50 A MAX. AC Output 50 A MAX. INV. AC Output 25 A MAX. DC Input Protection Over / Under Voltage, Reverse Polarity (Internal Fuse) AC Output Protection Short-Circuit, Overload AC Input Protection 30 Amp Circuit Breaker Temperature protection Shutdown Battery Temperature protection By a RJ-11 connector to battery Temperature sensor Nominal Voltage / Frequency 115 VAC / 60Hz 230 VAC / 50Hz Input Voltage Range 90 ~ 130 VAC 180 ~ 260 VAC Input Frequency Range Nominal Current 6 230 VAC (200~240 VAC)+/-3% 47 ~ 63 Hz 15A 7.4A Inverter / Charger COMBI Electrical Specification Model No. Efficiency (Full Load) >85% >87% Power Factor Correction(PFC) >0.98 (40% Load) >0.98 (40% Load) Charging Current Range 20 ~ 100A 10~50A Second Charger Output DC Output Characteristics 20 ~ 100A 10~50A 5A , 3-Stage Battery Chargers Max. Output Voltage 14.8 VDC 29.6 VDC 14.8 VDC 29.6 VDC Battery Temperature Compensation -25 mV per ℃ -50 mV per ℃ -25 mV per ℃ -50 mV per ℃ Bulk Voltage 14.4 V 28.8 V 14.4 V 28.8 V Absorption Voltage 14.4 V 28.8 V 14.4 V 28.8 V Float Voltage 13.5 V 27 V 13.5 V 27 V Note. Charger Voltage @Battery Type Setting “Standard”, Temperature@ 25℃ Equalization Max. output Voltage 16VDC 32VDC 16VDC 32VDC Characteristics Max. output Current 10A 5A 10A 5A LCD Panel 2 Lines LCD Panel with keypad for navigation and Red / Orange / Green LED Remote Control Terminal Controls the inverter ON / OFF operation Dry Contact Terminal By a relay Bypass Relay Relay Specification 25 Amp / 250 VAC Full Load Operating Temperature Range -25 ℃ ~ 40 ℃ Power de-rating 50 W / ℃, 41~60 ℃ Storage -30 ℃~70 ℃ Signal and Control Operating Humidity Range Fan Operation and Indicator 0~93% Non-condensing Failure Indication Buzzer alarm Switches On/ Off The fan does operate in load and internal temperature control related PWM variable speed control Sharing Mode Inverter mode / Charger mode / Power sharing (Generator mains support function / Power support ) / Charger Sharing Power Sharing Function AC Input Current Ground Relay Mechanical Specification Safety and EMS 10 ~ 50A(User-selectable) 3 ~ 25A (User-selectable) Ground relay included for connection of neutral of inverter to ground only at inverter mode. Standard disable Size (W x H x D) 13.03”x6.14”x18.3” (331mmX156mmX465mm) Weight 10.5 Kg (23.1 Lbs) Safety Standards Meet EN60950-1 EMC Standards FCC Class A EN55022:1998+A1:2000+A2:2003 Class A EN55024:1997+A1:2001+A2:2003 EN61000-3-2:2006 Class A EN61000-3-3:1995+A1:2001 7 Inverter / Charger COMBI 2.3 Mechanical Drawings 8 Inverter / Charger COMBI SB Series Inverter / Charger Combi Ordering Information Model Number SB2000-112 SB2000-124 SB2000-212 SB2000-224 Output Voltage Input Voltage Nominal Range 12 VDC 24 VDC 12 VDC 24 VDC 110VAC 110VAC 230VAC 230VAC Frequency Range AC Input 47~63 Hz 47~63 Hz 47~63 Hz 47~63 Hz 90 ~ 130 VAC 90 ~ 130 VAC 180 ~ 260 VAC 180 ~ 260 VAC 100~120 VAC 100~120 VAC 200~240 VAC 200~240 VAC Charger Current Max. voltage Max. 100A 50A 100A 50A 14.8 VDC 29.6VDC 14.8 VDC 29.6VDC 2.4 LCD Panel Mechanical Drawing: 3 How It Works This chapter describes the various applications of the Combi unit series from COTEK. The Combi unit is a battery charger, a pure sine wave inverter and an AC transfer system in one compact enclosure. The three-step Plus charging method guarantees that the batteries are always charged 100% The pure sine wave inverter assures that the AC output voltage is perfectly reliable even when limited external AC power is available. External AC power can be supplied by a public grid or a generator. DC power can be delivered by charged batteries. 3.1 Battery Charger Introduction The built-in battery charger is electronically controlled. It is designed for optimal recharging of both wet cell, gel cell and AGM deep cycle batteries. Battery charging is accomplished in three automatic stages: BULK, ABSORPTION and FLOAT. With an external AC source connected, the Combi unit charger also serves the functions of an AC to DC converter to supply DC loads which are connected to the battery. Simple, automatic operation is made possible by the microprocessor that is the brain of the inverter/charger Combination. In most cases, the unit is left on and no attention or maintenance is required. 9 Inverter / Charger COMBI Fig 1: Three step charge system 3.1.1 Three step Plus charge system See fig 1. The first step of the three step Plus charge system is the BULK phase, in which the output current of the charger is 100%, and the greater part of the capacity of the battery is rapidly charged. The current charges the batteries and gradually the voltage rises to the absorption voltage of 14.4V (12V models) or 28.8V (24V models) @ 25°C / 77°F. The duration of this phase depends on the ration of battery to charger capacity, and naturally also on the degree to which the batteries were discharged to begin with. The bulk phase is followed by the absorption phase. Absorption charging starts when the voltage on the batteries has reached 14.4V (12V models) / 28.8V (24V models) @ 25°C / 77°F, and ends when the battery is completely full. Battery voltage remains constant at 14.25V (12V models) / 28.5V (24V models) @ 25°C / 77°F throughout this stage, and the charge current depends on the degree to which the battery was initially discharged, the battery type, the ambient temperature, and so on. With a wet cell battery this stage lasts some four hours, with gel and AGM around three. Once the battery is 100% full, the charger automatically switches over to the float phase. (see Fig 12.) During the float phase the Combi unit switches to 13.5V (12V models) or 27 (24V models) @ 25°C / 77°F and stabilizes this voltage to maintain the batteries in an optimum condition. Connected DC-loads are powered directly by the charger. If the load is higher than charger capacity, the required additional power comes from the battery, which will be progressively discharged until the charger 10 Inverter / Charger COMBI automatically switches back to the bulk phase. Once consumption decreases, the charger goes back to normal operation of the three-step charge system. As the Combi unit is equipped with a three-step Plus charge system, the batteries can also remain connected to the Combi unit in winter. One hour every 12 days the charger automatically switches to absorption to keep the battery running properly and prolong its life span. The three-step Plus charge system is also safe for all the connected equipment. 3.1.2 Temperature compensated charging The Combi unit is delivered with a battery temperature sensor. By installing this battery temperature sensor the charge voltages are automatically adapted for deviating temperatures. Fig 2 : Temperature compensated charging See fig 2. When the battery temperature is low, the charge voltage increases. On the other hand, when the battery temperature is high, the charge voltage is decreased. Over charge and gassing are prevented this way. This will extend the life of your batteries. 3.1.3 Connection of a second battery The Combi unit is equipped with second charge output which can be used to give a maintenance charge to a small battery set like a starter battery Maximum output current: 5 Amps. Output voltage:14.4V @ 12V Model , 28.8V @ 24V Model , three-step, user can set ON or OFF. 11 Inverter / Charger COMBI 3.2 Inverter Introduction 3.2.1 General The inverter provides voltage and frequency regulated AC power from a battery bank. Fast acting electronic circuits protect the inverter against extreme overloads, low and high battery voltage , overheating and short circuit of the inverter. Considerable momentary surge power is available for starting-up electric motors. A built in power saving feature can reduce battery power consumption when the inverter is unloaded. 3.2.2 Power saving mode (selectable) In the inverter mode the Combi unit has a built-in automatic power saving feature that reduces battery power consumption when no load is present on the “INV. AC output”. Response from idle is instant, eight modes can be set by means of DIP-switches or LCD remote control. 3.3 Operation Modes The Combi unit is not just a Combination of an inverter and a battery charger. It has many additional features which can be used to increase the total available AC power, even when external AC power is limited. 3.3.1 Basic operation When there is no external “AC input” power available, the inverter of the Combi unit provides AC power on the “INV. AC output” output from the batteries. There is no AC power available on the “AC output”. See fig 3 Fig 3 : Inverter mode When external AC power comes available, the transfer relay switches on. See fig 4. Both outputs as well as the battery charger are supplied by the external AC power. The batteries are recharged now. 12 Inverter / Charger COMBI Fig 4 : Charger mode 3.3.2 Transfer Switch And Connector on The Front The Combi unit has two AC-outputs available: INV. AC output: The “INV. AC output” output switches between the AC-input and the output of the inverter. The AC input has the highest priority. In principle, AC-power is always available on this output. However during a switchover the loads connected to this output are not supplied with ACpower for a very short period of time (short break). It is the ideal output for loads that need AC-power permanently like personal computers, interior lighting and the refrigerator. AC output: This output is always internally connected to the AC-input. It is therefore only available when an external AC-source like shore power, a generator or an outlet is present. Larger loads like a hot water boiler, electric cooking appliance or washing machine should be connected to this output . See fig 5. Fig 5 : AC Input / Output contact 13 Inverter / Charger COMBI 3.3.3 Power sharing function (selectable) If the available power at the AC-input is limited, and the load connected to the AC output increases, the external AC circuit breaker may trip if nothing is done. To avoid this, the Combi unit can automatically reduce the battery charger output, and thus the AC power consumption. This Power sharing feature constantly senses the incoming AC current which is used to supply both the battery charger and the appliances connected to the AC outputs. The Power Sharing level should be set to match the value of the external circuit breaker, which protects the incoming AC power. For instance, when the external AC power is limited by a 10A circuit breaker or fuse, the Power Sharing level must be set to 10A. Fig 6 : Power Sharing Function I Here the Power Sharing level is set to a 10 Amps while the AC outputs consume a total of 2 + 5 = 7 Amps. This means that only 10 – 7 = 3 Amps is left over for charging. With 12V batteries 230 VAC this will result in a maximum charge current of approx. 45A DC. The Power Sharing level can be set by means of the DIP-switches or LCD remote control locally on the Combi unit When the total connected AC load reaches the level of the Power Sharing setting (10A), there will be no power left over to charge the battery. This means that the charge current of the Combi unit will be reduced to 0A. See fig 7. 14 Inverter / Charger COMBI Fig 7 : Power Sharing Function II 3.3.4 Generator function (selectable) If the demand for AC power still increases, the external AC circuit breaker may still trip if nothing is done. This problem can be solved by the Generator function. If the total demand for energy exceeds the maximum external power supply, energy can be added to the “AC outputs” and “INV.AC Output” by means of the inverter. This appliance can be automatically connected in parallel with the external power supply. Fig 8 : Generator Function See fig 8. Here the AC-input is still limited to 10 Amps. This is not enough to supply the total load (6 + 11A = 17A) connected to the AC outputs. When the Generator function is enabled, the inverter will supply the remaining 17 – 10 = 7A. This means that the restricted amount of external AC power will be compensated by energy which is stored in the batteries. Later, when the AC load has dropped below the setting of the Power sharing 15 Inverter / Charger COMBI function again, the battery charger of the Combi unit will commence to recharge the batteries. For safety unit the transfer relay is immediately switched off when incoming AC power fails in operation so that there will never be a high voltage on the shore cable inlet when it is not connected. 3.3.5 Support function (selectable) As explained above, when the Generator function is enabled, the inverter will operate in parallel with the external AC power source. This means that energy from the batteries is added to the AC-output only. Under no circumstance AC power from the inverter can be fed back into the AC grid. This may mean that in some situations the use of the Generator / Support function is not allowed. Please acquaint yourself with local regulations on this issue. Never use the Generator function if this is not allowed! Even if the use of the Generator function is not allowed, it is still possible to supply more energy than the external AC sourced can deliver This can be achieved by using the support function. Fig 9: Support function See fig 9. The AC input is still limited to 6Amps. This is not enough to supply the total load (6 + 9A = 15A) connected to the AC outputs. Now when the support function is enabled, the transfer relay will open. When opened, the external power source will deliver 6Amps to supply the load connected to the “AC output” output only, while the inverter will deliver 9Amps for the load connected to the “INV. AC output” . If the power consumption of the “AC output” output exceeds the setting of the support function, the external AC fuse or circuit breaker will still trip 16 Inverter / Charger COMBI 3.3.6 Support and Generator function (selectable) If user will support function and generator function both simultaneously enable. The Combi unit inverter will operate in parallel with the external AC power source, and when not enough to supply the total load connected to the “AC output” and “INV. AC output”. The transfer relay will open. Fig 10 : Generator and support function See fig 10. The AC input is still limited to 6 Amps. If the demand for AC power still increases, the external AC circuit breaker may still trip. The inverter will automatically to compensated by energy which is stored in the batteries. But when AC power still increases. This is not enough to the total load ( 7 + 9A = 16A ) connected to the AC outputs. The transfer relay will open. 3.3.7 Charger sharing (selectable) The Combi unit used “CHR.mode” startup. When external AC power comes available, the transfer relay switches ON. The Combi unit is constantly senses the AC power current witch is used to supply both the battery charger and the load Connected to the AC output. Fig 11 : Charger Sharing 17 Inverter / Charger COMBI See fig 11. The AC input is still limited to 10Amps. Supply the total load ( 5 + 2A = 7A ) connected to the AC outputs. That only 10 – 7A = 3Amps is left over or sharing, if the AC outputs load increases more 10 Amps. The transfer relay will open. When opened, the AC power will deliver 5 Amps to supply the load connected to the “AC output” only. But the inverter not to supply 2Amps load connected to the “INV. AC output”. As explained above operation must will sharing function enable. Fig 12. Charge characteristic of the three – step plus charging method. (@25℃ / 77℉) 3.3.8 Function Summary of the power sharing What is it used for ? The sharing level should be set to match the value of the external circuit Sharing breaker, then to protects the incoming AC power. Then AC input not enough to supply the total load connected to the AC Generator outputs. The appliance can be automatically compensated by energy which is stored in the batteries. When AC input not enough to supply the total load connected to the AC Support outputs, the transfer relay will open. When external AC power comes available. The Combi unit to charge batteries Charger only. 18 X 0 0 1 1 X X 1 1 1 1 0 1 Support 0 Sharing X X 1 0 1 0 X Generator Selectable Function 1 1 0 0 0 0 0 Charger 6A 7A 1 1A 1 1 0A 0 6 Amps 2A 1 0A 0 6 Amps 7A 1 1A 1 6A 0A 0 1 7A 1 6 Amps 1A 1A 1 1 0A 0 6 Amps 7A 1 1A 1 6A 0A 0 1 1A 1 6 Amps 1A 1 1A 1 6 Amps 0A 0 0A Output (I1) AC 2A 6 Amps limited Iac current 1 0 Synchronizatio n AC input 9A 9A 2A 9A 4A 9A 9A 9A 2A 9A 9A 9A 2A 9A 9A 9A 2A 9A 6A 5A 2A 9A 4A 9A Output (I2) INV. AC AC Output (LOAD) 0A 0A 3A 0A MAX. 0A 0A 0A 3A 0A 0A 0A 3A 0A 0A 0A 3A 0A 0A 0A 3A 0A MAX. 0A Current (I3) Charge 0A 0A 45A 0A 20~100A 0A 0A 0A 45A 0A 0A 0A 45A 0A 0A 0A 45A 0A 0A 0A 45A 0A 20~100A 0A (Selectable) Charge 0A 0A 0A 0A 0A 0A 200A 200A 0A 200A 200A 200A 0A 200A 200A 200A 0A 200A 0A 0A 0A 200A 0A 200A Discharger Battery current (Approx.) OPEN OPEN CLOSE OPEN CLOSE OPEN OPEN CLOSE CLOSE OPEN OPEN OPEN CLOSE OPEN CLOSE CLOSE CLOSE OPEN CLOSE CLOSE CLOSE OPEN COLSE OPEN Relay Transfer NG (I1>6A) OK OK OK NG (I1+I2+I3>6A) OK NG (I1>6A) OK OK OK NG (I1>6A) OK OK OK NG (I1+I2+I3>15A) OK OK OK NG (I1+I2+I3>6A) OK OK OK NG (I1+I2+I3>6A) OK Circuit breaker External AC Inverter / Charger COMBI Note. “0” is Disable / “1” is Enable / “X” is Don’t care / Current @Batteries 12VDC , 230VAC Model 19 Inverter / Charger COMBI 3.4 Equalization Batteries 3.4.1 Construction of Battery Cells: A Lead Acid battery consists of a number of 2 V nominal cells (actual voltage of the cell is 2.105 V) that are connected in series e.g. a 12 V nominal battery will have six, 2 V nominal cells in series (actual voltage of the 6 cells will be 2.105 x 6 = 12.63 V). Each 2 V nominal cell in this battery consists of an independent enclosed compartment that has Positive and Negative Plates (also called Electrodes) dipped in electrolyte that is composed of diluted Sulphuric Acid – solution of 33.5% v/v Sulphuric Acid and water. In a fully charged battery, the Positive Plate is in the form of Lead Dioxide, the Negative Plate is in the form of Sponge Lead and the Sulphuric Acid in the electrolyte has the maximum concentration of 33.5% v/v . 3.4.2 Electrical power in the Lead Acid Battery is produced by reversible electrochemical reactions as follows: During discharging, the Sulphuric Acid in the electrolyte reacts with the Positive and Negative plates resulting in conversion of the active materials in both the two plates (Lead Dioxide on the Positive plate and Sponge Lead on the Negative plate) to soft Lead Sulfate crystals. At the same time, electrons are released that create the electrical current that flows to the load. The concentration of Sulphuric Acid in the electrolyte is reduced as the battery gets discharged (the electrolyte becomes pure water when the battery is fully discharged). During charging, reverse electrochemical reactions take place. Under the influence of the charging voltage fed to the battery by the external battery charger / charge controller, electrons are fed back to the battery and the soft Lead Sulfate crystals at the Positive and Negative Plates are converted back to Lead Dioxide at the Positive Plate and Sponge Lead at the Negative Plate and the concentration of Sulphuric Acid is restored (will revert to 33.5% v/v when the battery is fully charged). 3.4.3 Gassing during Charging: During charging, the battery is required to be charged in a controlled manner in the final Absorption Stage (2.4 V per cell at 25 º C / 77 º F or 14.4 V for a 12 V battery at 25 º C / 77 º F) that restores the last 20% to 30% of the capacity. On successful completion of this stage of charging, the Lead Sulfate at the Positive and Negative Plates should have fully converted back to Lead Dioxide at the Positive Plate and Sponge Lead at the Negative Plate. Any further charging at this voltage or higher than this voltage results in electrolysis of water in the electrolyte to Hydrogen and Oxygen and this undesirable condition contributes to waste of energy. This process is known as "gassing". Gassing is also produced during the timed Equalization Stage when the battery is intentionally overcharged (2.5 to 2.7 V per cell / 15 to 16 V for 12 V batteries) to equalize the cells and remove stratification. 20 Inverter / Charger COMBI 3.4.4 Necessity for Equalizing Batteries: For proper health and long life of a Lead Acid battery, it is required to undergo an Equalization Stage during the charging process to prevent / reduce the following undesirable effects: Sulfation: If the charging process is not complete due to the inability of the charger to provide the required voltage levels or if the battery is left uncharged for a long duration of time, the Lead Sulfate crystals on the Positive and Negative plates that are formed during discharging / self discharge are not fully converted back to Lead Dioxide on the Positive plate and Sponge Lead on the Negative plate and get hardened and are difficult to dislodge through normal charging. These crystals are non conducting and hence, introduce increased internal resistance in the battery. This increased internal resistance introduces internal voltage drop during charging and discharging. Voltage drop during charging results in overheating and undercharging and formation of more Lead Sulfate crystals. Voltage drop on discharging results in overheating and excessive voltage drop in the terminal voltage of the battery. Overall, this results in poor performance of the battery. To dislodge these hardened Lead Sulfate crystals, some chargers are designed to detect a sulfated condition at the start of the charging process and go through an initial De-sulfation Mode that sends high frequency, high voltage pulses at the natural oscillation frequency of the crystals to dislodge the hardened crystals. Sulfation may also be reduced partially by the stirring / mixing action of the electrolyte due to gassing and bubbling because of intentional overcharging during the Equalization Stage. 3.4.5 Electrolyte Stratification: Electrolyte stratification can occur in all types of flooded batteries. As the battery is discharged and charged, the concentration of acid becomes higher at the bottom of the cell and becomes lower at the top of the cell. The low acid concentration reduces capacity at the top of the plates, and the high acid concentration accelerates corrosion at the bottom of the plates and shortens the battery life. Stratification can be minimized by the Equalization Stage by raising the charging voltage so that the increased gassing and bubbling agitates / stirs the electrolyte and ensures that the electrolyte has uniform concentration from top to bottom. The stirring action also helps to break up any Lead Sulfate crystals, which may remain after normal charging. 3.4.6 Unequal charging of cells: During normal charging, temperature and chemical imbalances prevent some cells from reaching full charge. As a battery is discharged, the cells with the lower voltage will be drained further than the cells at the higher voltage. When recharged, the cells with the higher voltage will be fully charged before the cells with the lower voltage. The more a battery is cycled, the more cell voltage separation takes place. In a healthy battery, all the individual cells will have the same voltage and same specific gravity. If there is a substantial difference in the 21 Inverter / Charger COMBI cell voltages (0.2 V or more) and in the specific gravities (0.015 or more) of the individual cells, the cells will require equalization. Equalizing batteries helps to bring all the cells of a battery to the same voltage. During the Equalization Stage, fully charged cells will dissipate the charging energy by gassing while incompletely charged cells continue to charge. 3.4.7 Equalization Stage: Normally, only the vented / wet cell / flooded batteries are equalized. Some sealed AGM batteries may be equalized if recommended by the manufacturer (e.g. Life Line brand of sealed, AGM batteries). The Equalization Stage is carried out only after completion of the Bulk and Absorption Stages. During the Equalization Stage, the battery is intentionally held above the Gassing Voltage for a specified period of time that is normally proportional to the depth of discharge of the battery or to the AH capacity of the battery. Recommendations of the battery manufacturer are to be followed for equalizing the batteries as the equalization voltage, time and frequency will depend upon the specific design of the battery. The Equalization Voltage will normally be in the region of 2.5 to 2.7 V per cell at 25 º C / 77 º F e.g. 15 to 16 V for 12 V batteries and 30 to 32 V for 24 V batteries. As a guide, a heavily used flooded battery may need to be equalized once per month and a battery in light duty service, every two to four months.(See fig13) Fig 13. Equalization stage (@12V battery) 3.4.8 The Table below gives the Absorption, Float and Equalization voltage settings for common batteries used : 22 Inverter / Charger COMBI Battery Type Inverter Voltage Bulk Voltage Absorption Voltage Float Voltage Equalization Voltage (Lifeline brand) 12 VDC 24 VDC 12 VDC 24 VDC 12 VDC 24 VDC 14.1VDC 28.2VDC 14.6VDC 29.2VDC 14.3VDC 28.6VDC 14.1VDC 28.2VDC 14.6VDC 29.2VDC 14.3VDC 28.6VDC 13.6VDC 27.2VDC 13.4VDC 26.8VDC 13.1VDC 26.2VDC NOTE! NOTE! 15.5VDC 31VDC 15.5VDC 31VDC AGM 2 12 VDC 14.5VDC 14.5VDC 13.5VDC NOTE! 24 VDC 29VDC 29VDC 27VDC NOTE! 12 VDC 12~16VDC 12~16VDC 12~16VDC 12~16VDC 24 VDC 24~32VDC 24~32VDC 24~32VDC 24~32VDC Gel Flooded AGM 1 (East Penn/Deka/ Discover/Trojan brand ) Custom* (To be selected by the customer based on the manufacturers’ recommendations, if available) *User can be setting the custom function voltage, but must use LCD Panel(See 6.4.4 for more information). NOTE! Gel and the AGM 2 Group (East Penn/ Deka /Discover/Trojan brand) batteries are not equalized. Hence, their Equalization Voltages are same as the Absorption Voltages When using the Custom setting, the Equalization voltage setting should not allow voltage lower than the Absorption Voltage setting. Also, the Equalization Voltage setting should not allow a setting higher than 2-volts (for 12V systems), or 4-volts (for 24V systems) above the Absorb Voltage setting. 3.4.9 Calculation of Equalization Charge Current: The Equalization Charge Current should be a relatively low current of around 1% of the charge current of the battery. Such a low current prevents an overcharge condition that results in excessive gassing and excessive loss of water. Also the equalization charge current should preferably be a variable value that is automatically set by the microcontroller as a function of the degree of charge of the battery. NOTE! Equalization Current is related to the charge current capacity of the battery and is normally calculated at 1% of the charge current of the battery. Hence, We has provided for the user to input the charge current capacity of the battery being used.(See 6.4.4) 3.4.10 Calculation of Absorption and Equalization Times: Equalization is required to be carried out after completion of the Bulk and Absorption Stages. It is preferred that the time periods for the Absorption and Equalization Stages be proportional to the discharged state of the battery. A more discharged battery will take longer time in the Absorption and Equalization Stages. The discharged state of the battery will be proportional to the time the charger remains in the Bulk Stage. Hence, a software timer may be used to measure the time the charger is in the Bulk Stage and then calculate and set the Absorption Stage and Equalization Stage Timers. Let the time 23 Inverter / Charger COMBI taken in the Bulk Stage be designated by “Bulk Timer” and the calculated Absorption Time by “Absorption Timer and the Equalization time by “Equalization Timer”. One of the recommended logics for calculations is as follows(See Fig 13): Absorption Timer = 0.5 x Bulk Timer Equalization Timer = Absorption Timer + 1 Hour if T1 < 2 Hours, or Equalization Timer = Absorption Timer + 2 Hours if 2< T1 < 4 Hours, or Equalization Timer = Absorption Timer + 4 Hours if T1 > 4 Hours 4 Operation 4.1 Power “ON” You use the remote control panel, and press the ON / OFF button on the front. After switching on expect a five till ten second delay before the Combi unit activated. If AC power is available on the AC input and within the specified limits, the Combi unit will switch to Charger Mode and will commence to charge the batteries. At the same time the internal transfer relay will pass the AC power to the AC output “INV. AC output”. If the AC power from the external AC-source is unavailable or outside the specified limits, the unit will come on as an inverter. Inverter overload protection, built-in idle mode circuitry, transfer switching, sharing and battery charger regulation will all function automatically. 4.2 Power “OFF” Move the main switch to the “OFF” position to switch off the Combi unit. Or can you use remote control panel, press the on/off button delay three second on the remote control panel. The Combi unit stops and all the indicators go off. The “INV. AC output” is disconnected and will become powerless. WARNING! Power OFF the Combi unit not cut off the connection to the batteries or the AC-source. Therefore the “AC output” output is still active. 4.3 Selectable “CHR. Power ON” mode When the main switch is set to the “ON” position, then to press LCD remote control panel “ON / OFF” button. You can to setting change the “CHR. Power ON” mode. The Combi unit is only able to work as a charger. This means that the inverter mode is disabled. This setting is useful if you want to keep your batteries charged and maintained in case you are away i.e. in the winter time. Now your batteries are spared when the incoming AC-source fails in operation.See Chapter 6 for detailed operation instructions of the remote panel. 24 Inverter / Charger COMBI 4.4 Protections The Combi unit is protected against overload, short circuit, overheating and under and over voltage. The user can detect failures from the remote control panels by means of the indicators .See chapter 8 for explanation of this readout. 5 Installation And Maintenance During installation and commissioning of the Combi unit, the Safety Guidelines & Measures are applicable at all times. See chapter 1 of this manual. 5.1 Unpacking In addition to the Combi unit the delivery includes: a battery temperature sensor. user’s manual. After unpacking, check the contents for possible damage. Do not use the product if it is damaged. If in doubt, contact your supplier. Check from the identification label whether the battery voltage is the same as the DCinput voltage of the Combi unit (e.g. 24V battery set for a 24V input voltage). Also check that the AC output voltage and output power of the Combi unit satisfies loading requirements. 5.2 Front Panel 5.2.1 AC Input Breaker: (reference ①) The AC input circuit breaker protects the Combi unit from overload. When an overload or shirt circuit condition occurs, the circuit breaker trips and disconnects the incoming AC power input. To reset it, push the circuit breaker button. The cause of tripping should be ascertained and corrected before the unit is reset. 25 Inverter / Charger COMBI 5.2.2 Hard-Wire Installation (AC wiring connections terminal): (reference ②) The AC wiring compartment is located on the front panel. Remove the AC wiring compartment cover to gain access to the AC terminal. WARNING! Before you connect AC wiring to the terminals of compartment cover, ensure to check the label in the compartment for correct connections. Wrong connection will damage the Combi unit. AC input and AC output terminal Connect AC output and AC input wiring to the inverter terminals Please use the following information as your reference: Terminal AC Output AC Input INV. AC Output Line (L) Neutral (N) Line (L) Neutral (N) Line (L) Neutral (N) Chassis Ground Wire color AC Current inch A.W.G Black White Brown Blue Red Yellow Green / Yellow or Bare copper 20~25A 25~30A 30~40A 40~55A 55~70 2 3.5 5.5 8 14 14 12 10 8 6 26~32 feet / AWG# 12~14 Note. Please double check and review all the connections to ensure that the wires are connected to the correct terminals and that the connections are tight. 5.2.3 26 Chassis Ground: (reference ③) WARNING! The ground wire offers protection only if the cabinet of the Combi unit is connected to the safety ground. Connect the chassis ground terminal to the hull or the chassis. Inverter / Charger COMBI Refer to local regulations on these issues! For safety purposes the neutral conductor (N) of the AC output must be connected to the earth (PE / GND) when the Combi unit is in inverter operation. When utility power is available on the AC input, and the Combi unit is in charger mode, this connection must be disabled again. In some applications automatic connection between the neutral conductor (N) and earth (PE / GND) is not required or acceptable. Therefore the automatic connection between the neutral conductor (N) and earth (PE / GND) is disabled by default. (see fig 5.) 5.2.4 DIP Switch Setting: (reference④) The Combi unit is provided with two groups of DIP-switches to adjust the apparatus according to the specifications of the electrical installation. The DIPswitches are located in the front panel. SWA A1 A2 A3 Setting A4 Setting 0 0 0 Disable 0 50Hz 1 0 0 Pow40W 0 1 0 Pow80W 1 1 0 Pow100W 0 0 1 Pow120W 1 0 1 Pow160W 0 1 1 Pow180W 1 1 1 1 60Hz Pow220W Power Saving Frequency A5 A6 0 0 1 0 0 1 1 1 Setting A7 Setting A8 Setting 100V 0 OFF 0 ON 200V 1 ON 1 ON 110V 220V 115V 230V 120V 240V Output Voltage Ground Relay Reset Power Saving: If you want to setting the Combi unit to power saving mode, to reduction consumption from the batteries. This means when it detects a load that is above setting value, it output power automatically on. By adjust DIP switch SWA1,SWA2 and SWA3. Default is “Disable”. Frequency: If you want to setting the Combi unit output power frequency of the inverter. By adjust DIP switch SWA4. Default is “60Hz”@110VAC Model / “50Hz”@230VAC Model . Output Voltage: If you want to setting the Combi unit output power voltage of the inverter. By adjust DIP switch SWA5 and SWA6. Ground Relay: The function allows you to connect the Neutral conductor of the Combi unit to the Safety Ground automatically when the Combi unit is working as an inverter. This means if you to set adjust the DIP switch SWA7 to “ON”. The internal Neutral of the inverter connected to the Safety Ground when the Combi unit is working as an inverter and disconnected when incoming AC input power is applied. Default is “OFF”. Reset: If you want will the Combi unit reset to default set value of the DIP switch. By adjust DIP switch SWA8. 27 Inverter / Charger COMBI SWB B1 Setting B2 Setting B3 B4 Setting B5 Setting B6 B7 Setting 0 Disable 0 Disable 0 0 6A 10A 0 Disable 0 0 Gel 1 Enable 1 Enable 1 0 10A 15A 1 Enable 0 1 Flooded 0 1 16A 25A 1 0 AGM1 1 1 25A 30A 1 1 AGM2 0 Support @230VAC Generator Setting COMBI 0 Mode CHR 1 Mode Power ”ON” Mode Selection @110VAC Battery Type Selection @110VAC Sharing Current Limit B8 Power Sharing DIP switch SWB3 and SWB4 to setting sharing current limit in 6A min. But! user can to use LCD panel setting the current in 3A min. Support: If you want to disable or enable the support function. See 3.3.5 for more information. Default is “Enable”. Generator: If you want to disable or enable the generator function. See 3.3.4 for more information. Default is “Enable”. Sharing Current Limit: If you want to setting limit the AC input current, Default is “6A”@230VAC Model / “10A”@110VAC Model. See 3.3.3 for more information. Sharing:If you want to disable or enable power sharing function. Default is “Enable”. See 3.3.3 for more information. Battery Type Selection: The factory setting for the battery type is optimal for most installations. In some applications however, it is desirable to change this setting. Adjust the Combi unit to the applied batteries by adjusting DIP switches SWB6 and SWB7. Default is “Standard”. . Wrong adjustment can cause damage to your batteries which is not covered by the warranty. The setting for traction battery should never be used with a battery bank that consists of 2V GEL cells! Battery Type Stage Bulk Voltage Absorption Voltage Float Voltage Gel @12VDC 14.1VDC 14.1VDC 13.6VDC @24VDC 28.2VDC 28.2VDC 27.2VDC Flooded @12VDC 14.6VDC 14.6VDC 13.4VDC @24VDC 28.2VDC 28.2VDC 26.8VDC AGM 1 @12VDC 14.3VDC 14.3VDC 13.1VDC @24VDC 28.6VDC 28.6VDC 26.2VDC AGM 2 @12VDC 14.5VDC 14.5VDC 13.5VDC @24VDC 29VDC 29VDC 27VDC Power ”ON” Mode Selection: If want to use “COMBI Mode” or “CHR Mode” to startup of the Combi unit. By adjusting DIP switches SWB8. Default is “COMBI Mode”. NOTE! When after adjusting DIP switches must will the Combi unit re-start. 28 Inverter / Charger COMBI 5.2.5 5A Charger: (reference ⑤) The Combi unit has a second charge output switch can be used to give a maintenance charge to a small battery. Characteristics introduction Battery maximum charger current: 5Amps Battery maximum charger voltage: 14.4VDC @ 12V / 28.8VDC @ 24V Battery charger status: three – step Charger enable / Disable user selectable 5.2.6 DC Input Connection: (reference ⑥) Follow the instructions to connect the battery cables to the DC input terminals of the Combi unit. The cables should be as short as possible (less than 6 feet / 1.8 meters ideally) so that they can handle the required current in accordance with the Electrical Codes and Regulations. The size of the cable should be thick enough to limit the voltage drop to less than 2% when carrying the maximum input current to prevent frequent low-input voltage warnings, and shutdown. UVP (Under Voltage Protection) warning may result if there is excessive voltage drop across the DC cables between the batteries and the Combi unit. Increasing your DC cable size will help improve the situation. Batteries are capable of providing very large currents in case of short circuit. In case there is a short circuit in the cable run between the batteries and the input terminals of the Combi unit, it will result in overheating / melting of the cables and consequent risk of fire and injury, To prevent possibility of this hazard, use Very Fast Acting DC Fuse in line with the positive cable. The fuse should be as close to the positive battery terminal as possible. Use Busman ANN series fuses ( will also require Fuse Block 4164) or equivalent. The following sizes of cables and fuses are recommended for up to 6 ft. distance between the batteries and the Combi unit. (Applies to both 120 VAC and 230 VAC versions): Model No Wire AWG Inline Fuse SB2000-112 / 212 #2/0 250 A SB2000-124 / 224 #1/0 125 A Connect DC input terminals to 12V / 24V battery or other DC power source. [ + ] is positive, [ - ] is negative. Reverse polarity connection can blow the internal fuse and may damage the Combi unit permanently. WARNING! Make sure that all the DC connections are tight (torque to 9 – 10 ft-lbs, 11.7 - 13 Nm). Loose connections could result in overheating and can be a potential hazard. 29 Inverter / Charger COMBI WARNING! The recommended inline fuse should be installed as close to the battery positive terminal as possible failure to use a fuse on the “+” cable running between the Combi unit and battery may cause damage to the cable / Combi unit and will void warranty Also, only use high quality copper wire and keep the cable length short which is as maximum of 3 – 6 feet. 30 Inverter / Charger COMBI 5.2.7 Remote control green terminal: (reference ⑦) 1.) Before installing the functions of the Combi unit, ensure the Combi unit to turn off. 2.) Use 20 ~ 24 #AWG wire to connect the remote control terminals. 3.) Remote control ON / OFF Combi unit setup status : NOTE: At one time, only one remote function should used to control the Combi unit. The maximum voltage value is 60VDC in the ENB. 5.2.8 Dry Contact Green Terminal: (reference ⑧) Dry contact terminals may be connected to a Form C relay for “FAULT” indication. When “FAULT” occurs are provided with two sets of alarm contacts. NOTE: Fault conditions include Input under/over voltage, Output Short Circuit, Over Temperature, Over-load and, Fan Failure. 31 Inverter / Charger COMBI Specifications of the Relay 5.2.9 Maximum Voltage Load 250 VAC 250 VAC 24 VDC 24 VDC Resistive Resistive Resistive Resistive Number of operations Operating/Storage Temperature 100,000 -30℃~75℃ Remote Control Of The Phone Jack On The Front Panel: (reference ⑨) 1.) BAT. TEMP. Port : The Combi unit is delivered with a battery temperature sensor. When the battery temperature is high, the charge voltage is automatically decreased. Pin Num. 1 2 3 4 5 6 32 Contact Rating N.O. N.C. 1A 1A 1A 1A Signal Description Not used GND Batteries temperature sensor GND +5V Not used Pin Num. 1 2 3 4 5 6 Inverter / Charger COMBI 2.) RS-232 Port : Serial port monitoring and control through computer interface. Combi unit PIN Num. Signal Description 1 Not used 2 GND 3 RXD 4 TXD 5 Not used 6 Not used Computer Signal Description PIN Num. Not used 1 RXD 2 TXD 3 DTR 4 GND 5 DSR 6 RTS 7 CTS 8 Not used 9 The connection between this Combi unit and the computer is as follows : Combo unit Computer RXD RXD TXD TXD GND GND DTR DSR RTS CTS 3.) LCM Port : Connection for LCD remote control panel, can you setting and display the Combi unit operation status. 33 Inverter / Charger COMBI LCD Remote Control Panel PIN Num. Signal Description 1 CANH 2 CANL 3 PON 4 VCC5 VCC+ 6 DIS 7 5VS8 5VS+ Combi unit PIN Num. 1 2 3 4 5 6 7 8 The cables should be as short as possible (less than 32.8 feet / 10 meters ) so that they can handle the signal. 4.) CANⅠand CANⅡ Port : At present has not used, the reservation may make the parallel use in the future. 5.) Ethernet Port : The user can use RJ-45 cable line to connect to this port to manage and control the COMBI unit through SNMP. NOTE: Ethernet function at user option and can be purchased upon request. 5.2.10 Reset : Press the reset button when the Ethernet is not working normally. 5.3 Move The LCD Remote Control Panel Place: 5.3.1 How remove the LCD remote control panel User can remove LCD remote control panel on the Combi unit. And can fixed in the operation convenient place or is position. As followers fig. Step 1. Loosening the screw in the front of the Combi unit, then will plastic pushes forward. Remove the front. (1) 34 (2) Inverter / Charger COMBI Step 2. Loosening the screw in the top of the Combi unit, then first will the top plastic push front way. Remove the top plastic. (1) (2) (3) (4) Step 3. Loosening the screw in the lcd remote control panel of the Combi unit, then remove the LCD remote control panel, and will the cable wire taking in the rear.The cable wire can fixed in the “RJ-45 fixed Position” connector. (1) (2) 35 Inverter / Charger COMBI 5.3.2 (3) Combination the Combi unit (4) In remove LCD remote control panel after on the Combi unit. You must Combination the Combi unit. As followers fig. Step 1. Will lock in the top head sheet iron takes down, and will the LCD remote control panel hole cap. Loosening the screw. (1) (2) Step 2. Will the top plastic Combination in the Combi unit on the front, and make sure that all the screw are tight. (1) 36 (2) Inverter / Charger COMBI Step 3. Will the front plastic Combination in the Combi unit on the top, and make sure that all the screw are tight. 5.3.3 Installation LCD remote control panel User can be installation the LCD remote control panel in anywhere, and you can using the LCD remote panel to control the Combi unit(see Chapter 6). The cable wire you can reference 5.2.9 of the LCM PORT( the wire less than 32.8 feet / 10 meters). As followers fig. 37 Inverter / Charger COMBI 5.4 Rear Panel: Rear Panel View FAN ventilation grille (1) ~ (2): The fans behind the ventilation grilles provides cooling. DOT NOT obstruct these vents! Maintenance: 5.4.1 Make sure that the fan vents are not blocked. 38 5.4.2 Use a vacuum cleaner to remove any dust from the fan area. 5.4.3 When cleaning the case or rear panel, use a soft, dry cloth, only. If the case or rear panel is very dirty, use a neutral, non-abrasive detergent. Do not use alcohol or ammonia based solutions. 5.4.4 Regular service, and relocation of the Combi unit, should be performed by a qualified service technician. 5.4.5 Avoid spilling liquid on the Combi unit. Inverter / Charger COMBI 5.5 Installation Drawing This schematic is to illustrate the general placement of the Combi unit a circuit. It is not meant to provide detailed wiring instructions for any particular electrical installation. Fig 14. Installation Drawing 39 Inverter / Charger COMBI 5.5.1 Wiring instructions for one Combi unit (stand alone operation) See fig 13. 1.) See reference ①. Connect the external AC-source to the AC-input of the 2.) Combi unit. Integrate a fuse (value depending on the used wire diameter with a maximum of 50Amps) and a Residual Current Device (RCD) into this wiring. See reference ②. Connect the AC-output POWER of the Combi unit to the 3.) power distribution group. See reference ③. Connect the INV. AC output of the Combi unit to the INV. 4.) AC output distribution group. Integrate a Residual Current Device (RCD) into this wiring. See reference ④. Run the DC-cables between the batteries and the 5.) Combi unit. Connect the red cable to the plus (+) connection, the black cable to the minus (–) connection. See reference ⑤. Attach the temperature sensor to the battery and run the 6.) cable into the Combi unit. Option: if you want to make use of the possibility to give a maintenance charge to a small battery set (like a starter battery), run a AWG14 red cable with a fuse holder between the positive pole of the starter battery and Combi unit. reference ⑥. Fix the cable with an insulated fasten to the “+5A”connection. Integrate a 10 Amps fuse in this wire. The negative pole 7.) of this battery must be connected to the negative pole of the service battery. See reference ⑦. If you want to install the LCD remote control panel, run 8.) the communication cable between the Combi unit and the panel. NOTE! The Combi unit can also be operated without the LCD remote control panel connected. See reference ⑧. If you want to install a computer. To monitoring and 9.) control the Combi unit. See reference ⑨. The user can use RJ-45 cable line to connect to this port and manage it through remote to control the Combi unit. 6 LCD Remote Control Panel – Display & Setup 6.1 LCD Panel Indications 6.1.1 40 Press the ON / OFF button on the front. The Combi unit starts working normally. After switching on expect a five till ten second delay. The Combi unit will be operating in normal condition when either of the following messages are displayed on the LCD panel screen : Inverter / Charger COMBI 6.1.2 LED Indications : AC GRID: Displays incoming AC input status. AC Input LED Status AC input ON AC input OFF Green OFF Inverter: Displays the Combi unit working in the “Inverter mode” statues. DC-AC Inverter LED Status Inverter AC Power OK Inverter AC Power Not Good Green Red Charger: Displays the Combi unit working in the “Charger mode “ status. Bypass LED Status Charger OK Charger Not Good Green OFF ALARM: Displays the Combi unit status of the Failure Alarm. Alarm Over / Under Alarm / FAN Alarm Set alarm in the inverter to operate normally LED Status Orange OFF NOTE. For instructions on setting the alarm, see details in Section 6.3.3 6.1.3 LCD Remote Control Panel Selection Buttons : Function of Various Buttons : Function: You can use the “up” button to scroll through the menus. or to select the value for set up under setting mode. 41 Inverter / Charger COMBI Function : You can use the “Down” button to scroll through the menus or to select the value for set up under setting mode. Function : You can use the “Page Up” button to scroll through the menus. Function : You can use the “Page Down” button to scroll through the menus. Function : Press the button longer than 2 seconds, The Combi unit will change to “Select Menu” which appears on the LCD screen for the user to set functions. Function : Confirms a selection or value. Function : The Combi unit can be activated by the button. Press “ON / OFF” button, the Combi unit to startup. If you want to turn OFF the Combi unit. Press the “ON / OFF” button longer than 3 seconds. 6.1.4 LCD Display: Displays Combi unit operational status (See also section 6.3 for detailed). 6.2 LCD Rear View Introduction 42 Inverter / Charger COMBI 6.2.1 Jump (reference ①) The “J1 jump” is placed inside the remote controller and it is to indicate either “Return Override Function” or ‘Ignition Lockout Function” J1 jump “open” – Return Override Function J2 jump “short” – Ignition Lockout Function Note. The “J1” jump default mode is “short”. 6.2.2 Green Terminal (reference ②) PIN Function 1 ALM 2 CTL 3 -ENB 4 -VCC ALM (PIN1) When the Combi unit has the warning or the protection produce, simultaneously this “ALM” pin will changing output to 5 Volt / 10mA control signal to provides the user. 43 Inverter / Charger COMBI CTL (PIN2) User can be use this “CTL” pin to force the Combi unit to turn ON or turn OFF, and the function must with the “J1” jump coordination use (see 6.2.1). * J1 jump is “open” : Turn OFF the Combi unit. When have a power provision the “CTL” pin, then the Combi unit to turn ON. If the power havn’t provision the “CTL” pin, this time the Combi unit to turn ON. As follows shows : J1 Jump “CTL” Input Voltage Combi Unit 5 ~ 60 VDC Turn ON 0V Turn OFF Open * J1 jump is “short” : Turn ON the Combi unit. When have a power provision the “CTL” pin, then the Combi unit to turn OFF. If the power havn’t provisions the “CTL” pin, this times the Combi unit to turn ON. As follows shows : J1 Jump “CTL” Input Voltage Combi Unit 5 ~ 60 VDC Turn OFF 0V Turn ON Short -ENB (PIN3) User can be this “-ENB” pin to control the Combi unit to turn ON or turn OFF. WARNING! To turn “ON” the combi unit by operating the –ENB function of LCD Panel, the combi inverter cannot be turn OFF by any others operations, only if to turn the MAIN SWITCH “OFF”. -Vcc (PIN4) This is LCD remote control panel ground This is LCD remote control panel ground, and with battery negative (-) is different. 44 Inverter / Charger COMBI 6.3 Startup Sequence and Standby Status 6.3.1 Once turn on the Combi unit. The LCD display shows “System startup please wait”, then checks the Combi unit. Status flow is as follows: 45 Inverter / Charger COMBI 6.4 Setup Menu – Operation and Instructions Entering Setup Menu: Press Button longer than 2 seconds. The Combi unit, enters the select Menus consisting of four layers: (1)Select Menu Heading: (3)Select Menu Item: 46 (2)Select Menu : (4)Setting Value: Inverter / Charger COMBI 6.4.1 Select Menu Heading: The manual is used to show the status of the running Combi unit. The user can make selections by switching on or Ig = xx.x →Display the Grid O/P current. Vg = xxx.x →Display GRID O/P voltage FQ = xx.x →Display the Grid frequency W = xxx →Display the Grid O/P Power. Ib = xxx →Display the current status of Battery : “Ib = -xxx” to indicate the value of discharging current in discharge mode. ”Ib = xxx ” to indicate the value of charging current in charge mode. ℃ = xx.x →Display “BAT. Temp.” to indicate the ambient temperature. Vb = xx.x →Display the charge or discharge voltage of the battery. →Displays the status of charging cycle: BULK, ABSORPTION or FLOAT :BULK Phase. :ABSORPTION Phase. :FLOAT Phase. Ii = xx.x →Display the INV output current. Vi = xxx.x →Display the INV output voltage. FQ = xx.x →Display the INV frequency. W = xx.x →Display the INV output power. 6.4.2 Change Run Mode : Combi / Charger mode control, when the Combi unit there is no external AC power available, the inverter will provides AC power, and when there is external AC power available, the Combi unit can constantly senses the incoming AC current which is used to supply both the battery charger and the appliances connected the AC output. This functions on the setting of “Combi power ON”. (See also section 3.3.3 for detailed) 47 Inverter / Charger COMBI If you want to charge you batteries only and you do not want to start the inverter function when incoming AC fails. Then the function must be setting of “CHR power ON”. (Charger See also section 3.3.7 for detailed) 6.4.3 P. S. Mode Param Power sharing mode parameter control. Setting the Combi unit “ Sharing / Support / Generator “ function of the enable or disable, and setting the AC input current limited. Iac setup : Setting the available power at the AC input current limited. To protect the incoming AC input current from overload. Default : 10A @ 110VAC model / 3A @ 230VAC model Setting range : 10 ~ 50A @ 110VAC model / 3 ~ 25A @ 230 VAC model Power sharing : Setting the Combi unit “Sharing / Support / Generator “ function of the enable or disable. When set the function have display on the LCD screen. Mean the function enable. When no have appears on the LCD screen is disable. Default = Disable. Setting range: Disable / GEN. / SUPP. / SUPP. GEN. / SHAR. / SHAR. GEN. / SHAR. SUPP. / SHAR. SUPP. GEN. 6.4.4 Another Parm : Press button before of enters, the “Another Parm” menus. To access the settings menu contents a level password must be provided. For increased protection certain sensitive parameters are protected by a level password than an authorized operator must provide. User interface 1. LCD contrast : Sets the LCD screen contrast. Default = 50% Setting range = 0% ~ 100% 2. LCD Auto-off : Sets the LCD screen backlight auto off timer. Default = 120 seconds Setting range = 0 ~ 250 seconds. 3. Buzzer setting : Sets the LCD remote control panel internal buzzer sound ON / OFF. When set the function have appears on the LCD screen. The buzzer will occurs “Beep” sounds. Default = MSG, Alert, SHDN Setting range = Disable / SHDN / Alert / Alert, SHDN / MSG / MSG, SHDN / MSG, Alert / MSG, Alert, SHDN 48 Inverter / Charger COMBI Menu MSG Alert SHDN Disable Status Power on or push keypad Fan fail or UV alarm or overload alarm or OT alarm OVP or UVP or OLP or OTP Any Buzzer ON ON ON OFF 4. Alert Setting: When alert occurs, the Combi unit internal dry contact relay will open / close. (see details in section 5.2.8) Default = Alert, SHDN Setting Range = Disable / SHDN / Alert / Alert, SHDN Menu Alert SHDN Disable Status Fan fail or UV alarm or Overload alarm OVP or UVP or OLP or OTP Any Relay ON ON OFF 5. Shutdown retry: when the Combi unit occurs OVP shutdown or UVP shutdown or overload or short circuit shutdown, anyway. The Combi unit can be automatically restart, and should according to setting value. Default = 5 Setting range: Disable ~ 15 6. INV. OFF delay: When external AC power incoming available, the transfer relay switch turn ON. If the external AC power cutoff, the transfer relay will open. When opened, the external power source the supply the load connected to the “AC output “ only, the inverter will deliver current for the load connected to the “INV. AC power”. However this time will to consumption by energy switch is stored in the batteries. So, when external AC power cutoff. The Combi unit can be automatically power OFF, and should according the setting timing. Default = Disable Setting range: Disable ~ 10Min 7. Language : The Combi unit have different language be provided selectable. Default = English Setting: English / Italian / Spanish / French / German 8. New password: This option allows to change the current password. To set the new password digits use the and keys. Maximum password length = 4 word Factory setting = 0000 9. Iac setup switch: when the External AC power is connected, the system will automatically constrain at the lowest value of AC input current, at the same time, the LCD display will show “Iac setup: xxA” message on the screen so that the Users may change the constrained value of AC current randomly . The system allows the Users to set up the value within 60 sec. if the time passed, the system will resume automatically and back to the system previous setting. Default = Disable Setting: Enable / Disable 49 Inverter / Charger COMBI I/P Parameter : 1. OVP Setting: Setting Combi unit the Over Voltage Protection (OVP) and shutdown on the inverter operate. Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model Model 12 V 24 V Setting value range 15 VDC ~ 16 VDC 30 VDC ~ 32 VDC 2. OVP Recovery: When the dc input voltage is higher than the OVP setting, the Combi unit shuts-down; once the input voltage falls below the set OVP value, the Combi unit will automatically restart. Default = 14.5 VDC @ 12V Model, 29 VDC @ 24V Model Model 12 V 24 V 3. UVP Setting: Setting the Combi unit Under Voltage Protection (UVP) and Shutdown on the inverter operate. Default= 10.5 @ 12V Model, 21 VDC @ 24V Model Model 12 V 24 V 4. Setting value range 13.5 VDC ~ 14.5 VDC 27 VDC ~ 29 VDC Setting value range 10.5 VDC ~ 11.5 VDC 21 VDC ~ 23 VDC UVP Recovery: When the DC input voltage is below the set UVP value The Combi unit shuts-down; Once the input voltage rises Above the set UVP value, the Combi unit will automatically Restart. Default= 12.5VDC @ 12V Model, 25 VDC @ 24V Model Model 12 V 24 V Setting value range 12.5 VDC ~ 13.5 VDC 25 VDC ~ 27 VDC 5. UV Alarm: Setting Under Voltage (UV) alarm. When the input voltage is lower than the set value, the Combi unit will sound “beep” to remind that the unit is going to shutdown. At the meantime, the contact in the internal Dry Contact Relay will open / close. (See details in Section 5.2.8) Default= 10.5 VDC @ 12 V Model, 21 VDC @ 24 V Model Model 12 V 24 V Setting value range 10.5 VDC ~ 11.5 VDC 21 VDC ~ 23 VDC NOTE! The value of voltage set for the “UV Alarm” should be equal to or higher than the value set for “UVP” or else the unit will shutdown without any audible warning. O/P Parameters: 1. O/P Voltage: Setting the Combi unit output voltage on the inverter operate. Default= 110 VAC @110 V Model, 230 VAC @ 230 V Model 50 Inverter / Charger COMBI Model 110 V 230 V Setting value range 100 VAC ~ 120 VAC 200 VAC ~ 240 VAC 2. O/P Frequency: Setting the Combi unit output frequency on the inverter operate. Default= 60 Hz @ 110 V Model, 50 Hz @ 230 V Model. Model 110 V 230 V Setting value range 47 Hz ~ 63 Hz 47 Hz ~ 63 Hz 3. Sync Frequency: If a generator with distorted. Output waveform (too low frequency) is used as AC source. The allowed frequency window for the incoming AC power can be enlarged. Example1: AC input = 230 VAC / 50Hz, User setting Value= 7Hz When the Combi unit “Output frequency” is within The Range of 43 Hz~57 Hz, the internal transfer relay will close. When the output frequency is less than 43 Hz or more than 57 Hz, the internal transfer relay will still open. Example2: When user setting Value= Disable,the Combi unit “Output frequency” is within The Range of 47 Hz~63 Hz, the internal transfer relay will close. Default= 7Hz Model 110 V 230 V Setting value range Disable ~ 7 Hz Disable ~ 7 Hz 4. Overload Alarm: Sets the overload alarm. When the Combi unit output power is higher than the set value, the Combi unit will sound “beep” to remind that the unit is going to shutdown. At the same time, the internal Dry Contact Relay will open/close. (See details in Section 5.2.8) Default= 100% Setting range= 50%~110% 5. Saving Level: Setting the Combi unit to power saving to reduction consumption from the batteries.(level setting refer See 5.2.10) Default = Disable Setting range = Disable ~ 7 6. Saving Interval: When the Combi unit in working for the power saving mode. And the Combi unit must to sensitive. This time the Combi unit must to AC output (LOAD) sensitive load. When the load increases more than set value of the power saving level, the Combi unit of awaking on the output power automatically. However, to the load sensitive time. The Combi unit can be adjust on the power saving interval. Default = 2.0 Seconds Setting range = 0.1S ~ 2.0S 7. Ground Relay: Setting the Combi unit ground relay allows you to connect the Neutral. (See details in section 5.2.3) Default = OFF Setting range = ON / OFF 51 Inverter / Charger COMBI Charge parameter : 1. Ibat setup: When external AC power comes available. The battery charger are supplied by the external AC power. The batteries are recharged now. However, the charger current can be adjust on the “Ibat setup”. Default = 50.0 A @12V model / 25.0A @24V model Model 12 V 24 V Setting value range 20.0A ~ 100A 10.0A ~ 50.0A 2. Second charger : The Combi unit can be used to give a maintenance charge to a small battery. The second charger output current 5A maximum. Users can be set turn ON or turn OFF on the charger power output. Default = ON Setting range = ON / OFF Battery Type Stage Bulk Voltage Absorption Voltage Float Voltage Battery Type Stage Vbulk CTM Vabs CTM Vfloat CTM 3. Max. Bulk timer: The Combi unit is a three – step plus charging method and guarantees that the batteries are always charged 100%. This three automatic stages: BULK, ABSORPTION and FLOAT. The first step of the three plus charge system is the BULK phase. The Combi unit can be adjust on the phase timer.(See details in fig 12) Default = 8 hours Setting range = 8 ~ 18 hours 4. Battery type: Users can be setting for the battery type. (see details in section 5.2.10) Default = Gel Setting range = Gel / Flooded / AGM 1 / AGM 2 / Customer. be used with a battery bank that consists of 2V GEL cells! Gel Flooded AGM 1 @12VDC 14.1VDC 14.1VDC 13.6VDC @24VDC 28.2VDC 28.2VDC 27.2VDC @12VDC 14.6VDC 14.6VDC 13.4VDC @24VDC 28.2VDC 28.2VDC 26.8VDC @12VDC 14.3VDC 14.3VDC 13.1VDC @24VDC 28.6VDC 28.6VDC 26.2VDC AGM 2 @12VDC 14.5VDC 14.5VDC 13.5VDC @24VDC 29VDC 29VDC 27VDC Customer @12VDC 14.0 ~ 15.0VDC 14.0 ~ 15.0VDC 13.0 ~ 14.0VDC @24VDC 28.0 ~ 30.0VDC 28.0 ~ 30.0VDC 26.0 ~ 28.0VDC To be selected by the customer on the manufacturers’ recommendations, if available. 5. RST to default: The Combi unit you can restore all the factory settings. Select the items “RST to default “ and press .The screen “ON” appears on the display. press to restore the factory settings. 52 Inverter / Charger COMBI 7 RS-232 Communication and Operation 7.1 Operation of RS-232 serial port : 7.1.1 See reference 5.2.9. If you want to install a the computer, run the communication cable between Combi unit and the computer. Connect the RS-232 port to front on the Combi unit. However you can be remote control and monitoring to the Combi unit. 7.1.2 The RS232 interface of this unit employs ASCII code to implement the asynchronous serial transmission control. The byte structure is START-BIP – 8 BIT DATA-STOP BIT. Baud rate: 9600. 7.1.3 Coupled with PC software application port. Operation is as detailed in Section 72. 7.2 Example of the RS232 Operation: 7.2.1 RS-232 command: Command format: This unit uses high-level language commands with a CR (0DH) as the end of the command. The system would interpret and execute the command only after these two characters are received. After the unit execute the command, it would send a response string to the computer. The response string is as follows: = > CR : Command executed successfully ? > CR : Command error, not accepted ! > CR : Command correct but execution error (e.g. parameters out of range). If the command needs any information from the unit, the unit would send the information back to the computer (with CR ) and then send the response string to the computer. 7.2.2 Command format: This unit supports the following command format. There should always be a CR (0DH) appended to the command while sending the command to this unit. 1.) Users can be the command to control the Combi unit to turn ON or turn OFF. Format : Power Example : A space (ASCII code 20H) is needed between power and can be one of the following. “0” : Power OFF “1” : Power ON 2.) Users can be the command to query the Combi unit output frequency of the inverter. Format : FRQ? After “Enter”, the unit’s “Output Frequency” appears on the PC screen. 53 Inverter / Charger COMBI 3.) Users can be the command to query the Combi unit output voltage of the inverter. Format: VINV? After “Enter”, the unit’s “Output Voltage” appears on the PC screen. 4.) Users can be the command to query the Combi unit output current of the inverter. Format: IINV? After “Enter”, the unit’s “Output Current” appears on the PC screen. 5.) Users can be the command to query the Combi unit status. Format: STA? After “Enter”, the unit’s working status will appears on the PC screen. As follows status on behalf of the Combi unit Bit S T U V W X Y Z 54 Binary code 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ASC II Code 0 128 0 64 0 32 0 16 0 8 0 4 0 2 0 1 Status on behalf Power turn off Power turn on Battery no high voltage Battery high voltage Battery no low voltage Battery low voltage Temperature normal Temperature failure Fan normal Fan failure No power saving power saving mode No overload or short circuit overload or short circuit Battery no under voltage alarm Battery under voltage alarm 6.) Users can be the command to query the Combi unit AC input of the grid power. Format: VGRID? After “Enter”, the unit’s “AC input voltage” appears on the PC screen. 7.) Users can be the command to query the Combi unit AC input of the grid current. Format: IGRID? After “Enter”, the unit’s “AC input current” appears on the PC screen. 8.) Users can be the command to query the Combi unit DC input voltage of the battery. Format: VBAT? After “Enter”, the unit’s “DC input voltage” appears on the PC screen. 9.) Users can be the command to query the Combi unit DC input current of the battery. Format: IBAT? After “Enter”, the unit’s “DC input voltage” appears on the PC screen. Inverter / Charger COMBI 10.) Users can be the command to query the Combi unit contact temperature sensor on the battery. Format: TBAT? After “Enter”, the unit’s “Battery Temperature” appears on the PC screen. 11.) Users can be the command to query the Combi unit internal temperature. Format: TENIR? After “Enter”, the unit’s “Internal Temperature” appears on the PC screen. 12.) Users can be the command to query the Combi unit output power of the inverter. Format: PINV? After “Enter”, the unit’s “Output Power” appears on the PC screen. 13.) Users can be the command to query the Combi unit AC input of the grid power. Format: PGRID? After “Enter”, the unit’s “AC input power” appears on the PC screen. 14.) Users can be the command to query the Combi unit model number. Format: Model? After “Enter”, the unit’s “Model Number” appears on the PC screen. 15.) Users can be the command to reset default the Combi unit . Format: RST? After “Enter”, the unit’s will reset to default. 7.2.3 Command for accessing Setup Menus and adjusting values: 1.) Select the Setup Menus with the help of Function Codes: Format : FUNC After “Enter”, the Setup Menu for the Function Code will be called. The = 0~33, as follows: Function Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Setting Menu LCD_Contrast LCD_Auto-off Not used Buzzer Setting Alert Setting Shutdown Retry Sync Frequency Battery Type Saving Level Ground Relay Second Charger(5A) Change Run Mode Power Sharing Mode Parameter Inv Off Delay Overload load Alarm Saving Interval Iac Setup Max. Bulk Timer Function Code 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 Setting Menu OVP Setting OVP Recovery UVP Setting UVP Recovery UV Alarm O/P Voltage O/P Frequency Ibat Setup EE_SWLed SN[0] SN[1] Not use EE_Vbulk_CTM EE_Vabs_CTM EE_Vfloat_CTM EE_Veq_CTM EE_Teq_CTM EnEq 55 Inverter / Charger COMBI 1. Command to query the functions No : Format: FUNC? After “Enter”, the unit’s “Function Code” appears on the PC screen. 2. Command to query the set value of the function : Format: SETT? After “Enter”, the existing set value of the function appears on the PC screen. 3. Command to set or adjust the value of the function : Format: SETT After “Enter”, the new value of the function is set choose the of the function as follows: FUNC 0: LCD Contrast SETT 0 ~ 100 Default 50% FUNC 1: LCD Auto-off SETT 0 ~ 250 Default 120 S FUNC 3: Buzzer Setting SETT 0 Buzzer (Beep sound) Disable 1 2 SHDN Alert 3 Alert , SHDN 4 5 MSG MSG , SHDN 6 7 MSG , Alert MSG , Alert , SHDN Default 7 FUNC 4: Alert Setting 56 SETT 0 Alert Disable 1 2 3 SHDN Alert Alert, SHDN Default 3 Inverter / Charger COMBI FUNC 5: Shutdown Retry SETT 0 ~ 15 Default 5 FUNC 6: Sync Frequency SETT Disable ~ 70 @10=1Hz Default 7.0Hz <70> FUNC 7: Battery Type SETT 0 1 2 3 Type Gel Flooded AGM 1 AGM 2 Default LOAD Disable >40W >80W >100W >120W >160W >180W >220W Default Relay OFF ON Default 0 FUNC 8: Saving Level SETT 0 1 2 3 4 5 6 7 0 FUNC 9: Ground Relay SETT 0 1 0 FUNC 10: Second Charger SETT 0 1 5A Output OFF ON Default 1 FUNC 11:Change Run Mode SETT 0 3 Mode CHR. Power ON COMBI Power ON Default 3 57 Inverter / Charger COMBI FUNC 12: P. S. Mode Parameter SETT 0 1 2 3 4 5 6 7 Power Sharing Mode Disable GEN. SUPP. SUPP. , GEN. SHAR. SHAR. , GEN. SHAR. , SUPP. SHAR. , SUPP. , GEN. Default 0 FUNC 13: Inv Off Delay SETT 0 ~ 100 @10=1 min Default 5.0 min <50> FUNC 14: Overload Alarm SETT 50 ~ 110 Default 100% FUNC 15: Saving Interval SETT 1 ~ 20 @10=1 sec Default 2.0 sec <20> FUNC 16: Iac Setup SETT Default 100 ~ 500 @10=1 A 10.0A <100> 30 ~ 250@10=1 A 3.0A <30> Model SB2000-112 SB2000-124 SB2000-212 SB2000-224 FUNC 17: Max. Bulk Timer SETT 8 ~ 180 @10=1 Hour Default 8.0 Hr <80> FUNC 18: OVP Setting SETT Default 1500 ~ 1600 @100=1V 16.0V <1600> 3000 ~ 3200 @100=1V 32.0V <3200> 58 Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 Inverter / Charger COMBI FUNC 19: OVP Recovery SETT Default 1350 ~ 1450 @100=1V 14.5V <1450> 2700 ~ 2900 @100=1V 29.0V <2900> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 20: UVP Setting SETT Default 1050 ~ 1150 @100=1V 10.5V <1050> 2100 ~ 2300 @100=1V 21.0V <2100> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 21: UVP Recovery SETT Default 1250 ~ 1350 @100=1V 12.5V <1250> 2500 ~ 2700 @100=1V 25.0V <2500> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 22: UV Alarm SETT Default 1050 ~ 1150 @100=1V 10.5V <1050> 2100 ~ 2300 @100=1V 21.0V <2100> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 23: O/P Voltage SETT Default 1000 ~ 1200 @100=1V 110V <1100> 2000 ~ 2400 @100=1V 230V <2300> Model SB2000-112 SB2000-124 SB2000-212 SB2000-224 FUNC 24: O/P Frequency SETT Default 470 ~ 630 @10=1Hz 60Hz <600> 470 ~ 630 @10=1Hz 50Hz <500> Model SB2000-112 SB2000-124 SB2000-212 SB2000-224 59 Inverter / Charger COMBI FUNC 25: Ibat Setup SETT Default 200 ~ 1000 @10=1A 50.0A <500> 100 ~ 500 @10=1A 25.0A <250> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 26: After “Enter”, will the combi unit dip switch (on the front) set value appears on the PC screen. FUNC 27: After “Enter”, will the combi unit series number [0] appears on the PC screen. FUNC 28: After “Enter”, will the combi unit series number [1] appears on the PC screen. FUNC 30: Bulk-stage voltage setting SETT Default 1400 ~ 1500 @100=1V 14.5V <1450> 2800 ~ 3000 @100=1V 29.0V <2900> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 31: Absorption-stage voltage setting SETT Default 1400 ~ 1500 @100=1V 14.5V <1450> 2800 ~ 3000 @100=1V 29.0V <2900> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 32: Float-stage voltage setting SETT Default 1300 ~ 1400 @100=1V 13.5V <1350> 2600 ~ 2800 @100=1V 27.0V <2700> Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 FUNC 33: Equalization-stage voltage setting SETT Default 1400 ~ 1600 @100=1V 14.5V <1450> 2800 ~ 3200 @100=1V 29.0V <2900> 60 Model SB2000-112 SB2000-212 SB2000-124 SB2000-224 Inverter / Charger COMBI FUNC 34: Equalization-stage timer setting SETT 10 ~ 1200 @100=1 Hr Default 8 Hr <80> FUNC 35: Equalization-stage Enable / Disable setting SETT 0 1 2.) Power Sharing Mode Disable Enable. Default 0 Select the “REHTY Menus” with the help of Function Codes: Format : FUNC After “Enter”, the Setup Menu for the Function Code will be called. The = 0~17, as follows: Function Code 0 1 2 3 4 5 6 7 8 3.) REHTY Menus Power output W/H Power output Time Power input W/H Power input Time Charging AH Charging Time DisCharging AH DisCharging Time OLP time Function REHTY Menus Code 9 Short time 10 Heat sink temp. fail time 11 Environment temp. fail time 12 Battery Max. voltage 13 Battery Min. voltage 14 Battery OVP time 15 Battery UVP time 16 Battery OTP time 17 Charging cycle 1. Users can be the command to query the Functions No: Format : FUNC? After “Enter”, the unit’s “Function Code” appears on the PC screen. 2. Users can be the command to query the Combi unit history data : Format : REHTY After “Enter”, the Combi unit history data of the function appears on the PC screen. Select the “REUDF/WRUDF Menus” with the help of Function Codes: Format : FUNC After “Enter”, the Setup Menu for the Function Code will be called. The = 0~31, as follows: Function Code 0 1 2 3 4 5 Setting Menu UserDef[0] UserDef[1] UserDef[2] UserDef[3] UserDef[4] UserDef[5] Function Code 16 17 18 19 20 21 Setting Menu UserDef[16] UserDef[17] UserDef[18] UserDef[19] UserDef[20] UserDef[21] 61 Inverter / Charger COMBI 6 7 8 9 10 11 12 13 14 15 UserDef[6] UserDef[7] UserDef[8] UserDef[9] UserDef[10] UserDef[11] UserDef[12] UserDef[13] UserDef[14] UserDef[15] 22 23 24 25 26 27 28 29 30 31 UserDef[22] UserDef[23] UserDef[24] UserDef[25] UserDef[26] UserDef[27] UserDef[28] UserDef[29] UserDef[30] UserDef[31] 1. Users can be the command to query the Functions No : Format: FUNC? After “Enter”, the unit’s “Function Code” appears on the PC screen. 2. Users if want to read the Combi unit set value. This setting value defers to the user meaning to do set. can be the command to read the Combi unit set value: Format: REUDF After “Enter”, the existing set value will appears on the PC screen. 3. Users if want to set a word to the Combi unit by means. can be the command to set value of the Function: Format: WRUDF The value maximum is two words only. After “Enter”, the new value will save of the Combi unit. 8. Trouble Shooting 8.1 Fault Indicators WARNING: Do not open or disassemble the Combi unit. Attempting to service the unit may cause risk of electrical shock or fire.If a failure occurs, the origin of the failure is displayed by means of the LCD remote control panel LEDS and display. Mode XX 62 Problems and Symptoms Possible Cause No output and LCD none Illuminating The Combi unit power a. The Combi unit not working switch turn off Damage or voltage b. DC input battery error error of the battery c. DC input terminal none DC fuse is blown voltage of the Combi unit LCD panel “Alarm LED” Indicators red lamp The Combi unit is load a. LCD panel appears with than 100%, but “Overload alert” the inverter still on. b. LCD panel appears The battery voltage is Solutions Check the on/off switch of the LCD panel Check and Confirmation of the voltage to the battery Investigate the cause of the failure and replace the fuse. Reduce the connected load by switching off some equipment. Check the batteries. Inverter / Charger COMBI “UV alert” Combi Charger No AC power output a. LCD panel appears “OLP shutdown” and “Inverter LED” solid red. b. LCD Panel appears “OVP Shutdown” and “Inverter LED” solid red. c. LCD Panel appears “UVP Shutdown” and “Inverter LED” solid red. d. LCD Panel appears “ENIR TEMP. shutdown” or “H.S. TEMP. shutdown” or “BAT. TEMP. shutdown” and “Inverter LED” solid red. No charge current to the batteries running too low, but The inverter will switch off if the the inverter still on. battery voltage stays low. Short circuit , wiring error. over loading. Check AC wiring for short circuit . Reduce load. Over dc input voltage (OVP) Check dc input voltage and reduce the voltage Low dc input voltage. Recharge to the battery. Check (UVP) connections and cables wire. Over Thermal shutdown. (OTP) a. LCD panel display none charge current. Bypass relay not to close b. LCD panel “Charger LED” and “ AC Grid LED” not illuminating. Not AC input power To restart the Combi unit always. DC input terminal no connections to the batteries c. Improve ventilation. Make sure ventilation, grilles / slots of the Combi unit are not obstructed. Lower ambient temperature. Check frequency of the Combi unit setting and AC input both same Check AC input terminal connections, and to the make sure external AC input or AC circuit breaker is OK. Check the DC input terminal. 8.2 Warranty We guarantee this product against defects in materials and workmanship for a period of 24 months from the date of purchase and will repair or replace any defective Combi units if you directly returned them to us with postage paid. Please note that Cotek is only responsible for ensuring our products are operational before delivering. This warranty will be considered void if the unit has been misused, altered, or accidentally damaged. Cotek is not liable for anything that occurs as a result of the user’s fault. No. 33, Rong Hsin Rd., Pa Teh City, Tao Yuan County, Taiwan Phone:886-3-3661581 FAX:886-3-3676029 E-mail:sales@cotek.com.tw http:// www.cotek.com.tw 63
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 64 Language : zh-TW Tagged PDF : Yes Title : WF-600T Series Author : Joseph A. Namenye Creator : Microsoft® Office Word 2007 Create Date : 2013:07:03 21:22:36+08:00 Modify Date : 2013:07:03 21:22:36+08:00 Producer : Microsoft® Office Word 2007EXIF Metadata provided by EXIF.tools