IEC Contactor Specifications

100-TD013, IEC, contactor, specifications, technical data, 100-C, 100-K, 100-Q, 100S, 100C, 100K, 100S-C, 100Q, safety, miniature, 100-E, 104-E, 100S-E, 100E, 104E, 104-C, 104S-C

Rockwell Automation

IEC Contactor Specifications - Literature Library | Rockwell ...

Rockwell Automation Publication 100-TD013J-EN-P - April 2021. Summary of ... Switching of Hermetically Sealed Cooling Compressor Motors - manual reset.

IEC Contactor Specifications

– Permanently fixed – Protective cover to prevent manual operation – Red contact ... 10 Rockwell Automation Publication 100-TD013J-EN-P - April 2021. Specifications.

100-td013 -en-p
Technical Data
Original Instructions

IEC Contactor Specifications
Bulletin Numbers 100/104-K, 100/104-C, 100/104S-C, 100/104-E, 100S-E, 100Q-C

Topic

Page

Summary of Changes

2

Product Line Overview

3

IEC Contactors

3

Safety Contactors

4

100-K/104-K Miniature Contactors

5

Product Selection

5

Accessories

8

Specifications

11

Life-Load Curves

15

Approximate Dimensions

16

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors

17

Product Selection--100-C/104-C Contactors

17

Product Selection--100S-C/104S-C Safety Contactors

22

Product Selection--100Q-C Capacitor-switching Contactors

30

Accessories

31

Renewal Parts

36

Specifications

38

Life-Load Curves

49

Approximate Dimensions

56

100-E/104-E, 100S-E/104S-E Contactors

59

Product Selection--100-E/104-E Contactors

59

Product Selection--100S-E Safety Contactors

62

Accessories

66

Renewal Parts

73

Specifications

75

Life-Load Curves

96

Approximate Dimensions

101

Additional Resources

113

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.

Topic

Page

Corrected pkg. qty. for mechanical interlocks

68

Corrected Cat. Nos. for mechanical latches

69

2

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

IEC Contactors

Product Line Overview

Bulletin No. Screw Terminals

100-K/104-K 

100-C/104-C 

100-E/104-E  (9...96 A), Thru-hole (116...2650 A)

Spring Terminals

(5...9 A)

 (9...16 A)

--

Max.Current Ie

12 A

97 A

2650 A

Current Rating

5...12 A

9...97 A

9...2650 A

Features

· Panel mounting or mounting on 35 mm DIN

· Mini-contactors

· Panel mounting or mounting on 35 mm DIN Rail Rail

· Uniform panel mounting dimensions

· AC or DC coil control

· Panel mounting or mounting on 35 mm DIN Rail · Reversible coil terminals (line or load side)

· AC or DC coil control

· Common accessories

· E09...E370 AC/DC electronic coil; with optional PLC interface on E116...E370 E400...E2650

· Made of environmentally friendly materials · Made of environmentally friendly materials

AC/DC with PLC interface

· Made of environmentally friendly materials

Contacts

· 3 power poles with internal N.O. or N.C. auxiliary contact, or 4 power poles.
· Optional front-mounted 2- or 4-pole external auxiliary contact block.

· 3 power poles with internal N.O. or N.C.

· 3 main poles with 2 auxiliary contacts

auxiliary contact or 4 power poles (9...23 A). (1 N.O. and 1 N.C.) on E116...E2650

· Optional front- or side-mounted 1-, 2- or 4-pole · Optional side- or front-mounted external

external auxiliary contact block.

auxiliary contact block.

Coil Voltages

AC = 24...600V, 50/60Hz DC = 12...250V

AC = 12...600V, 50/60Hz DC = 9...250V

20...500V 50/60 Hz/DC

Optional Overload Relays

Electronic or bimetallic

Electronic or bimetallic

Electronic

· Front-mount auxiliary contacts

Optional Accessories

· Surge suppressors · Electronic timers

· Mechanical interlocks

· Front or side-mount auxiliary contacts · Surge suppressors · Electronic or pneumatic timers · Mechanical interlocks · Mechanical latches

· Side- or front-mount auxiliary contacts · Mechanical interlocks · Terminal lugs · Terminal shields · Connecting bars

Standards/ Certifications

· UL · CSA · IEC · CE Marked · CCC

· UL · CSA · IEC · CE Marked · CCC

· EN/IEC · CE Marked · cULus · CCC · EAC · C-tick · KC

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

3

Product Line Overview Safety Contactors
Safety Contactors

Bulletin No. Screw Terminals Max.Current Ie Current Rating
Features
Contacts Coil Voltages

100S-C/104S-C
3
97 A
9...97 A
· Positively guided/mechanically linked auxiliary contacts · Front-mounted auxiliary contacts:
­ Permanently fixed ­ Protective cover to prevent manual operation ­ Red contact housing for easy identification ­ Incorporates IEC 947-5-1 "Mechanically Linked" symbol ­ Optional gold-plated bifurcated versions · AC and DC operating coils · SUVA third-party certification
3 main poles with N.C. mechanically linked or mirror feedback contacts
AC = 12...600V, 50/60Hz DC = 12...250V

Optional Accessories

· Side-mount auxiliary contacts · Surge suppressors · Electronic timers · Mechanical interlocks

· EN/IEC 60947-4

· IEC 60947-5-1 Annex L -- Mechanically Linked Contacts

Standards Compliance

· ·

IEC 60947-4-1 Annex H -- Mirror Contacts UL 508

· CSA C22.2 No. 14

· EN50205

Certifications

· cULus Listed (File No. E3125; Guide NLDX, NLDX7) · SUVA Third-Party Certified · CE Marked

100S-E Thru-hole
750 A 9...750 A
· Mirror contact performance on auxiliary contacts · Red N.C. low-power auxiliary contacts used for feedback circuit · SUVA third-party certification · AC/ DC operating coils · "Mirror Contact" symbol on front
3 main poles with N.C. mirror feedback contacts
20...500V 50/60 Hz/DC
· Side-mount auxiliary contacts · Terminal shields · Terminal lugs · Terminal enlargements · Terminal extensions · Connection bars for 140G molded case circuit breakers, 140MG
motor protection circuit breakers, and 140MG motor circuit protectors
· EN/IEC 60947-4-1 · IEC 60947-4-1, Annex F -- Mirror Contacts · UL 60947-4-1 · CSA C22.2, No. 60947-4-1
· cULus Listed (File No. E41850; Guide No. NLDX, NLDX7) · CE Marked · CCC · UL · CSA · EAC · RCM (C-tick) · SUVA Third-Party Certified · KC

4

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors

Product Selection

· 3-Pole AC- and DC-operated contactors

· Compact size

· Same dimensions for AC and DC

· Full-voltage non-reversing and reversing contactors · 5, 9, and 12 A contactors rated at 690V

100-K Miniature Contactor

· IP2X finger protection

· Optional integrated surge suppressor

· Compatible with Bulletin 193-K bimetallic overload relay

· Mirror contacts per IEC 60947-4-1 and mechanically linked contacts per IEC 60947-5-1 on main unit

104-K Reversing Miniature Contactor

Bulletin 100-K miniature contactors are designed for commercial and light industrial applications where panel space is at a premium. These miniature devices, while 45 mm wide, are shallower and have less panel depth requirements than standard IEC contactors.

The miniature contactors have been designed with flexibility in mind. They are available with AC or DC operating coils, several contact ratings, and optional 2- or 4-pole adder decks in a variety of auxiliary contact configurations.

3-Pole AC- and DC-operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

Hp (60 Hz)

40 °C (104 °F)

AC-3

AC-1

1-Phase

3-Phase

230V 400/415V 500V 690V

115V 230V 200V 230V 460V 575V

Screw Terminals

5

20

1.5

2.2

2.2 2.2 1/2 1 1-1/2 1-1/2 3

3

9

20

3

4

4

4 1/2 1-1/2 2

2

5

5

12

20

3

5.5

5.5 5.5 3/4 2

3

3 7-1/2 7-1/2

Spring Clamp Terminals

5

10

1.5

2.2

2.2 2.2 1/3 3/4 1-1/2 1-1/2 3

3

9

10

2.2

4

4

4 1/3 1

2

2

5

5

(1) May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ10M.  Coil voltage code -- see page 6.

Auxiliary Contacts

N.O. N.C.

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

Pkg. Qty.(1)

Cat. No.

1

100-K0510

1

100-K0501

1

100-K0910

1

100-K0901

1

100-K1210

1

100-K1201

1 100-KR0510 1 100-KR0501 1 100-KR0910 1 100-KR0901

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

5

100-K/104-K Miniature Contactors Product Selection

4-Pole AC- and DC-operated Contactors

Rated Operational Current Ie [A]
40 °C (104 °F) AC-3 AC-1

Ratings for switching AC motors - AC-2, AC-3

3-phase kW (50 Hz)

230V

400/ 415V

500V 690V

1-Phase 115V 230V

Hp (60 Hz) 3-Phase
200V 230V 460V

5

20

1.5 2.2 2.2 2.2 1/2

1 1-1/2 1-1/2 3

9

20

3

4

4 4 1/2 1-1/2 2

2

5

12

20

3 5.5 5.5 5.5 3/4 2

3

3 7-1/2

(1) May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ400M.

Contact Configuration, Main Poles
Pkg. Qty.(1)

Cat. No.

575V N.O.

N.C.

4

0

3

3

1

2

2

4

0

5

3

1

2

2

4

0

7-1/2

3

1

2

2

1

100-K05400

1

100-K05300

1

100-K05200

1

100-K09400

1

100-K09300

1

100-K09200

1

100-K12400

1

100-K12300

1

100-K12200

Reversing AC- and DC-operated Contactors

Rated Operational Current Ie [A]

40 °C (104 °F)

AC-3

AC-1

5

20

9

20

12

20

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

230V 400/415V 500V 690V

1.5

2.2

2.2 2.2

3

4

4

4

3

5.5

5.5 5.5

1-Phase 115V 230V ---- ---- ----

Hp (60 Hz)

3-Phase

200V 230V 460V

1-1/2 1-1/2 3

2

2

5

3 3 7-1/2

Auxiliary Contacts per Contactor(1)

575V N.O.

N.C.

3

0

1

5

0

1

7-1/2

0

1

Cat. No.(2)
104-K0502 104-K0902 104-K1202

(1) Used for electrical interlocking (2) Bulletin 104-K reversing contactors are factory assembled and include contactors, mechanical interlock (Cat. No. 100-KMCH) and wiring kit (Cat. No. 100-KPR) for power and control circuit
(electrical interlock).

Coil Voltage Codes

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100-K0910 becomes Cat. No.100-K09D10.

Screw type terminal versions

AC Voltages [V] 24 110 120 230 240 400 480 600 DC Voltages [V]

12 24 110 125 220 250

50 Hz

--

D

--

--

--

--

--

-- Standard

ZQ ZJ ZD ZS ZA ZT

60 Hz

--

--

D

--

--

--

B

VC

with Integrated Diode -- DJ -- -- -- --

50/60 Hz

KJ

--

--

KF KA KN --

--

Spring clamp type terminal versions

AC Voltages [V] 24

110

120

230

50 Hz

--

D

--

--

60 Hz

--

--

D

--

50/60 Hz

KJ

--

--

KF

DC Voltages [V] Standard with Integrated Diode

24

110

ZJ

ZD

DJ

--

6

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Product Selection

Assignment of Contacts

Table valid for: AC / DC = 0.85...1.1 x Us, Tamb. = -25 °C...+60 °C (-13...140 °F), normal position (horizontal rail mounting)

Device Combinations in Accordance with IEC 60947-1 / -4-1

Auxiliary Contact Blocks(1) Circuit Diagram

Control

100-K Miniature Contactors (AC and DC Control)

100-K0510 100-K0910 100-K1210

100-K0501 100-K0901 100-K1201

100-K05400 100-K09400 100-K12400

100-K05300 100-K09300 100-K12300

100-K05200 100-K09200 100-K12200

A1 1 3 5 13

A1 1 3 5 21

A1 1 3 5 7

A1 1 3 5 R7

A1 1 3 R5 R7

K1

K1

K1

K1

K1

A2 2 4 6 14

A2 2 4 6 22

A2 2 4 6 8

A2 2 4 6 R8

A2 2 4 R6 R8

100-KFA02E 100-KFC02 100-KFA11E 100-KFB11 100-KFC11

51 61 52 62 21 31 22 32 53 61 54 62 21 33 22 34 23 31 24 32

AC/DC AC/DC AC/DC AC/DC AC/DC

(2)

01 + 02 = 03 (3)

(2)

(2)(3)

--

10 + 02 = 12

--

00 + 02 = 02

00 + 02 = 02 (3)

--

(2)

01 + 11 = 12

(2)

(2)

(2)

10 + 11 = 21

--

00 + 11 = 11

00 + 11 = 11

00 + 11 = 11

10 + 11 = 21

(2)

00 + 11 = 11

00 + 11 = 11

00 + 11 = 11

100-KFA20E 100-KFC20

53 63 54 64 23 33 24 34

AC/DC AC/DC

(2)
10 + 20 = 30

01 + 20 = 21
(2)

(2)

(2)

00 + 20 = 20

00 + 20 = 20

(2)
00 + 20 = 20

51 61 71 81

100-KFA04E

AC/DC

(2)(3)

--

(2)(3)

--

--

52 62 72 82

21 31 41 51

100-KFC04

AC/DC

10 + 04 = 14 (3)

--

00 + 04 = 04 (3)

--

--

22 32 42 52

53 61 71 81

100-KFA13E

AC/DC

(2)

01 + 13 = 14 (3)

(2)

(2)(3)

--

54 62 72 82

23 31 41 51

100-KFC13

AC/DC

10 + 13 = 23

(2)(3)

00 + 13 = 13

00 + 13 = 13 (3)

--

24 32 42 52

53 83 61 71

100-KFA22Z

AC/DC

(2)

01 + 22 = 23 (3)

(2)

(2)(3)

--

54 84 62 72

100-KFB22

43 53 21 31 44 54 22 32

AC/DC

10 + 22 = 32

--

00 + 22 = 22

00 + 22 = 22 (3)

--

100-KFC22

23 53 31 41

AC/DC

10 + 22 = 32

(2)(3)

00 + 22 = 22

00 + 22 = 22 (3)

--

24 54 32 42

100-KFA31Z

53 73 83 61

AC/DC

(2)

--

(2)(4)

--

--

54 74 84 62

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

7

100-K/104-K Miniature Contactors Accessories

Device Combinations in Accordance with IEC 60947-1 / -4-1 (Continued)

Auxiliary Contact Blocks(1) Circuit Diagram

Control

100-K Miniature Contactors (AC and DC Control)

100-K0510 100-K0910 100-K1210

100-K0501 100-K0901 100-K1201

100-K05400 100-K09400 100-K12400

100-K05300 100-K09300 100-K12300

100-K05200 100-K09200 100-K12200

A1 1 3 5 13

A1 1 3 5 21

A1 1 3 5 7

A1 1 3 5 R7

A1 1 3 R5 R7

K1

K1

K1

K1

K1

A2 2 4 6 14

A2 2 4 6 22

A2 2 4 6 8

A2 2 4 6 R8

A2 2 4 R6 R8

100-KFC31

23 43 53 31

AC/DC

10 + 31 = 41 (4)

--

24 44 54 32

100-KFA40E

53 63 73 83

AC/DC

(2)

54 64 74 84

100-KFC40

23 33 43 53

AC/DC

10 + 40 = 50

(2)

24 34 44 54

(1) For other operating limits, please contact your local Rockwell Automation sales office or Allen-Bradley distributor (2) Combination possible but not recommended, due to repeating or not consecutive sequence numbering (3) Tamb max. +40 °C (104 °F) (4) Tamb max. +40 °C (104 °F) and only allowed for coil voltage 24V DC or 230V AC

00 + 31 = 31 (4)
(2)
00 + 40 = 40

--
(2)
00 + 40 = 40

--
(2)
00 + 40 = 40

Accessories

Auxiliary Contact Blocks

Description

Front-mounted Auxiliary Contacts
· Auxiliary contact blocks 2- and 4-pole versions
· Choice of contact configurations
· Snap on, no tools required
· Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
· Mirror Contact performance per IEC 60947-4-1

Connection Diagrams
21 31 22 32 23 31 24 32 23 33 24 34 21 31 41 51 22 32 42 52 23 31 41 51 24 32 42 52 23 43 53 31 24 44 54 32 23 53 31 41 24 54 32 42 23 33 43 53 24 34 44 54

Cat. No.

For Use With Pkg. Qty.

N.O. N.C.

Screw Type Spring Clamp Terminals Terminals

0 2 100-K05...K12 1

100-KFC02 100-KRFC02

1 1 100-K05...K12 1

100-KFC11 100-KRFC11

2 0 100-K05...K12 1

100-KFC20 100-KRFC20

0 4 100-K05...K12 1

100-KFC04 100-KRFC04

1 3 100-K05...K12 1

100-KFC13 100-KRFC13

3 1 100-K05...K12 1

100-KFC31 100-KRFC31

2 2 100-K05...K12 1

100-KFC22 100-KRFC22

4 0 100-K05...K12 1

100-KFC40 100-KRFC40

8

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Accessories

Auxiliary Contact Blocks (Continued)
Description
Front-mounted Auxiliary Contacts · Auxiliary contact blocks 2- and 4-pole
versions · Choice of contact configurations · Snap on, no tools required · Electronic-compatible bifurcated
contacts for signals down to 15V/2 mA · Mirror Contact performance per
IEC 60947-4-1

Connection Diagrams
51 61 52 62 53 61 54 62 53 63 54 64 51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84

Cat. No.

For Use With Pkg. Qty.

N.O. N.C.

Screw Type Spring Clamp Terminals Terminals

0

2

100/104-K, 700-K

1

100-KFA02E 100-KRFA02E

1

1

100/104-K, 700-K

1

100-KFA11E 100-KRFA11E

2

0

100/104-K, 700-K

1

100-KFA20E 100-KRFA20E

0

4

100/104-K, 700-K

1

100-KFA04E 100-KRFA04E

1

3

100/104-K, 700-K

1

100-KFA13E 100-KRFA13E

2

2

100/104-K, 700-K

1

100-KFA22Z 100-KRFA22Z

3

1

100/104-K, 700-K

1

100-KFA31Z 100-KRFA31Z

4

0

100/104-K, 700-K

1

100-KFA40E 100-KRFA40E

Control Modules

Description

Mechanical Interlock · For interlocking of two adjacent contactors No added width to contactor assembly · Front mount plug-in type · Optional auxiliary contact blocks and suppressor modules mount onto the interlock
24...48V AC

RC Suppressor

110...280V AC

Surge Suppressor
· Plug-in type · Limits surge voltage on coil drop- MOV Suppressor
off

380...480V AC 12...55V AC, 12...77V DC 56...136V AC, 78...180V DC 137...277V AC, 181...250V DC

Connection Diagrams

For Use With Pkg. Qty. Cat. No.

100/104-K/-KR, 700-K/-KR

1

1(1)

100/104-K/-KR, 700-K/-KR

1(1)

1(1)

1(1)

100/104-K/-KR, 700-K/-KR

1(1)

1(1)

100-KMCH
100-KFSC50 100-KFSC280 100-KFSC480 100-KFSV55 100-KFSV136 100-KFSV277

Diode Suppressor

12...250V DC

100/104-K/-KR, 700-K/-KR

1(1)

100-KFSD250

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

Timers

Description
Solid-State Timing Element · 110...250V AC or DC · Includes 35 mm Hat Rail adapter

On-Delay, 0.1...3 s
On-Delay, 1...30 s

Connection Diagrams
~ S1 O / I
1
2
K1 N

For Use With

Pkg. Qty.

100/104-K, 700-K

10

Cat. No. 100-KT3S
100-KT30S

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

9

100-K/104-K Miniature Contactors Accessories

Connecting Components
Description
ECO Connecting Module -- 12 A · For DOL and reversing starters · Eco-starters mount on single DIN Rail (140M on DIN Rail) · Electrical and mechanical interconnection of 140M and
100-K contactors
Power Wiring Kit · For Reversing and Star/Delta combinations. Star-point
bridge not included. · Min. interruption time 50 ms

Connects: 140M-C circuit breakers with 100-K
contactors

1 3 5 21 K1M
2 4 6 22
- (L2)

1 3 5 21 K2M
2 4 6 22

Feeder Terminal for Compact Bus Bars · Max. current 34 A

Supply of compact bus bars

Three-phase Compact Bus Bars · Max. current 34 A · For 100-K, 5...12 A contactors

45 mm spacing (3 connections)(2) 45 mm spacing (4 connections)(2)

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 140M-C-PEK12M. (2) Combinations possible. Example: For 6 contactor connections use one cat. no. 100-KW453 and one cat. no. 100-KW454.

Marking Systems

Description
Label Sheet · 105 self-adhesive paper labels each, 6 x 17 mm

For Use With Pkg. Qty. Cat. No.

140M-C to 100-K

1(1) 140M-C-PEK12

100-K

1

100-KPR

100-K

1

100-KWT

100-K, 5...12 A 1 100-K, 5...12 A 1

100-KW453 100-KW454

Pkg. Qty. 10

Cat. No. 100-FMS

Snap-In Marker Card

5

1492-M6X12

10

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Specifications

100-K/104-K Miniature Contactors Specifications

Table 1 - Main Circuits

100-KR

100/104-K

05 09 05 09 12

AC-1 Active Power Load (50 Hz); Ambient temperature 40 °C (104 °F)

Rated Operational Current, Ie

 500V 690V

[A] 10 [A] 10

10 20 20 20 10 20 20 20

230V [kW] 4 4 8 8 8

240V [kW] 4 4 8.3 8.3 8.3

Rated Operational Power, 400V [kW] 6.9 6.9 14 14 14

Pe

415V [kW] 7 7 14 14 14

500V [kW] 8.7 8.7 17 17 17

690V [kW] 12 12 24 24 24

AC-1 Active Power Load (50 Hz); Ambient temperature 60 °C (140 °F)

Rated Operational Current, Ie

 500V [A] 10 10 16 16 16 690V [A] 10 10 16 16 16

230V [kW] 4 4 6.4 6.4 6.4

240V [kW] 4 4 6.7 6.7 6.7

Rated Operational Power, 400V [kW] 6.9 6.9 11 11 11

Pe

415V [kW] 7 7 12 12 12

500V [kW] 8.7 8.7 14 14 14

690V [kW] 12 12 19 19 19

Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F), AC-2, AC-3

230V [A] 6.3 8.5 6.3 11.3 11.3

240V [A] 6.3 8.5 6.3 11.3 11.3

Rated Operational Current, Ie

400V [A] 4.9 8.5 4.9 8.5 11.5 415V [A] 4.9 8.5 4.9 8.5 11.5

500V [A] 3.9 6.8 3.9 6.8 9.2

690V [A] 2.8 4.9 2.8 4.9 6.7

230V [kW] 1.5 2.2 1.5 3 3

240V [kW] 1.5 2.2 1.5 3 3

Rated Operational Power, 400V [kW] 2.2 4 2.2 4 5.5

Pe

415V [kW] 2.2 4 2.2 4 5.5

500V [kW] 2.2 4 2.2 4 5.5

690V [kW] 2.2 4 2.2 4 5.5

Load Carrying Capacity per UL/CSA

General Purpose Current (enclosed)

[A] 9 9 12 15 18

Rated current (enclosed), 115V

1-phase

230V

[A] 7.2 7.2 9.8 9.8 13.8 [A] 6.9 8 8 10 12

Rated power (enclosed), 115V

1-phase

230V

[Hp] 1/3 1/3 0.5 0.5 0.75 [Hp] 3/4 1 1 1.5 2

200V [A] 6.9 7.8 6.9 7.8 11

Rated current (enclosed), 230V

3-phase

460V

[A] 6 6.8 6 6.8 9.6 [A] 4.8 7.6 4.8 7.6 11

575V [A] 3.9 6.1 3.9 6.1 9

200V [Hp] 1.5 2 1.5 2 3

Rated power (enclosed), 230V [Hp] 1.5 2 1.5 2 3

3-phase

460V [Hp] 3 5 3 5 7.5

575V [Hp] 3 5 3 5 7.5

Table 2 - Main Circuits

100/104-K

05 09 12

Switching of 3-phase Motors, (50 Hz); Ambient temperature 60 °C (140 °F), AC-4

230V

[A] 6.3 11.3 11.3

240V

[A] 6.3 11.3 11.3

Rated Operational Current, Ie

400V 415V

[A] 4.9 8.5 11.5 [A] 4.9 8.5 11.5

500V

[A] 3.9 6.8 9.2

690V

[A] 2.8 4.9 6.7

230V

[Hp] 1.5

3

3

240V

[Hp] 1.5

3

3

Rated Operational Power, Pe

400V 415V

[Hp] 2.2 4 5.5 [Hp] 2.2 4 5.5

500V

[Hp] 2.2 4 5.5

690V

[Hp] 2.2 4 5.5

AC-4 at approximately 200,000 operations

230V

[A] 2.3 3.9 3.9

Rated Operational Current, Ie

240V 400/415V

[A] 2.3 3.9 3.9 [A] 2 3.6 3.6

500V

[A] 1.9 3.2 3.2

230V (1)

[Hp] 0.37 0.75 0.75

240V (1)

[Hp] 0.37 0.75 0.75

Rated Operational Power, Pe 400V (1)

[Hp] 0.75 1.5 1.5

415V (1)

[Hp] 0.75 1.5 1.5

500V (1)

[Hp] 0.75 1.5 1.5

Max. switching frequency

Ops/hour 250 250 250

Wye-Delta (60 Hz)

200V

[Hp] 2.2 3

5

Rated Operational Power, Pe

230V 460V

[Hp] 2.2 3

5

[Hp] 5 7.5 10

575V

[Hp] 5 7.5 10

Star-Delta Starting (50 Hz)

 230V

[A] 11.3 20 20

 240V

[A] 11.3 20 20

Rated Operational Current, Ie

400V 415V

[A] 8.5 15.5 15.5 [A] 8.5 15.5 15.5

500V

[A] 6.8 12.4 12.4

690V

[A] 4.9 8.9 8.9

230V (1)

[kW] 3

5.5 5.5

240V (1)

[kW] 3

5.5 5.5

Rated Operational Power, Pe

400V (1) 415V (1)

[kW] 4 [kW] 4

7.5 7.5 7.5 7.5

500V (1)

[kW] 4

7.5 7.5

690V (1)

[kW] 4

7.5 7.5

(1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

11

100-K/104-K Miniature Contactors Specifications

Table 3 - Main Circuits

100/104-K

05 09 12

Switching of Power Transformers, AC-6a (50 Hz)

Inrush Current

= n

Rated transformer current

 230V

[A] 2.9 5.4 5.4

 240V

[A] 2.9 5.4 5.4

n= 30

 400V

[A] 2.4 4.1 5.4

 415V

[A] 2.4 4.1 5.4

 500V

[A] 1.8 3.2 3.2

230V

[kVA] 1.2 2 2

240V

[kVA] 1.2 2 2

Apparent Power

400V

[kVA] 1.7 2.8 3.4

415V

[kVA] 1.7 2.8 3.4

500V

[kVA] 1.7 2.8 3.4

690V

[kVA] 2 4 5

Switching of Lamps

Gas discharge lamps AC-5a, 40 °C (104 °F)

open

[A] 18 18 18

enclosed

[A] 14.5 14.5 14.5

Individually compensated:

Max. capacitance at expected

Short-circuit current of

10 kA

[µF] 750 750 750

20 kA

[µF] 400 400 400

Filament AC-5b

230/240V

[A] 5 9 9

Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)

230V

[A] 20 20 20

AC-7a

400V

[A] 20 20 20

Switching of Motor Load for Home Appliances (50 Hz)

230V

[A] 6 11 11

AC-7b

400V

[A] 6 11 11

Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)

AC-8a

400V

[A] 11 18 18

500V

[A] 10 15 15

Switching of DC Loads

Non-inductive or slightly inductive loads or resistance furnaces DC-1, 60 °C (140 °F)

24V

[A] 6 9 9

48/60V

[A] 4/1 6/1.5 6/1.5

1 pole

110V

[A] 0.6 1 1

220V

[A] 0.2 0.3 0.3

440V

[A] 0.08 0.1 0.1

24V

[A] 6 9 9

48/60V

[A] 6 8 8

2 poles in series

110V

[A] 4 6 6

220V

[A] 0.8 1.2 1.2

440V

[A] 0.2 0.3 0.3

24V

[A] 6 9 9

48/60V

[A] 6 9 9

3 poles in series

110V

[A] 6 9 9

220V

[A] 3 4 4

440V

[A] 0.4 0.6 0.6

Table 3 - Main Circuits (Continued)

100/104-K

05 09 12

Shunt-wound Motors Starting, reverse current braking, reversing, stepping DC-3, 60 °C (140 °F)

24V

[A] 5 9 9

48/60V

[A] 4 6 6

3 poles in series

110V

[A] 2 3 3

220V

[A] 0.8 1.2 1.2

440V

[A] 0.15 0.2 0.2

Series-wound Motors Starting, reverse current braking, reversing, stepping DC-5, 60 °C (140 °F)

24V

[A] 5 9 9

3 poles in series

48/60V 110V

[A] 2 3 3 [A] 0.6 1 1

220V

[A] 0.1 0.1 0.1

Short Time Withstand ICW, 60 °C (140 °F

10 s

[A] 60 96 96

Resistance and Power Dissipation

Main current circuit resistance

[m] 2.2 2.2 2.2

Power dissipation by all circuits at Ie AC-3/ 400V

[W] 0.3 0.9 0.9

Total power dissipation

At Ie AC-3/400V

AC control
DC control (electronic)

[W] 2.1 2.7 2.7 [W] 2.9 3.5 3.5

Lifespan

Mechanical AC control

[Million operations]

15 15 15

Mechanical DC control

[Million operations]

15 15 15

Electrical AC-3 (400 V)

[Million operations]

0.7 0.7 0.7

Weight

Non-Rev. [kg (lbs.)] 0.16 (0.35)

AC

Rev. [kg (lbs.)]

0.4 (0.88)

Non-Rev. [kg (lbs.)]

0.2 (0.44)

DC

Rev. [kg (lbs.)]

0.48 (1.06)

Table 4 - Conductors

Conductor Cross Sections - Main Contacts Terminal type

100-KR 05 09

100/104-K 05 09 12
(1)

1 conductor [mm2] 0.50...2.5

2 conductors [mm2] 0.50...2.5

1 conductor [mm2] 0.75...2.5 (2)

2 conductors [mm2] 0.75...2.5 (2)

Recommended torque

[N·m] --

Cross section per UL/CSA

[AWG] 18...14(2)

Recommended torque

[lb·in] --

(1) Pozidriv No. 2 / Blade No. 3 screw (2) Fine- or coarse-stranded only

0.75...2.5 0.75...2.5
1...4 1...2.5+ 1...4
1.2 18...12 10.6

12

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Specifications

Table 5 - Short-Circuit Coordination Data(1)

100/104-K

05

09

12

Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 (contactor and fuses only)

DIN Fuses- gG, gL

50 kA Available Fault Current

Type "1" (690V)

[A] 35

35

35

Type "2" (400V)

[A] 16

20

20

Per UL 508 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only)

UL Class K5 and RK5 Fuses

5 kA Available Fault Current

UL Listed Combination (600V)

[A] 40

40

40

UL Class CC and CSA HRCI-MISC Fuses

50 kA Available Fault Current

UL Listed Combination (600V)

[A] 30

30

30

UL Class J and CSA HRCI-J Fuses

50 kA Available Fault Current

UL Listed Combination (600V)

[A] 30

30

30

(1) See the Rockwell Automation Global SCCR Tool at rok.auto/sccr for complete shortcircuit current ratings.

Table 6 - Coil Data

100/104-K

Operating Limits

50 Hz, 60 Hz, 50/60 Hz

pick-up dropout

DC (conventional)

pick-up dropout

Coil Consumption 50 Hz, 60 Hz, 50/60 Hz
DC (conventional) Operating Times AC With RC module DC (conventional) With integrated diode

pick-up hold-in pick-up hold-in
closing delay opening delay closing delay opening delay closing delay opening delay

With external diode

opening delay

(1) For 9, 12, 24, and 110V DC coils

05 09 12

[x Us] [x Us]
[x Us]
[x Us]

0.85...1.1
0.2...0.75 0.8...1.1 0.7...1.25(1) 0.1...0.75

[VA] [VA/W]
[W] [W]

35 5/1.8 cold 3.0, warm 2.6 cold 3.0, warm 2.6

[ms]

15...40

[ms]

15...33

[ms]

15...28

[ms]

18...40

[ms]

6...12

[ms]

8...12

[ms]

35...50

Table 7 - Auxiliary Contacts and Auxiliary Contact Blocks

Conventional Coils

Internal

Front mounted

Switching of AC Loads

AC-12 Ith

at 40 °C (104 °F) [A] 10

10

at 60 °C (140 °F) [A] 6

6

24V

[A] 6

3

42/48V

[A] 6

3

120V

[A] 6

3

230V

[A] 3

2

AC-15 at rated voltage of

240V

[A] 3

2

400V

[A] 1.8

1.2

415V

[A] 1.8

1.2

500V

[A] 1.4

1.0

690V

[A] 1.0

0.6

Switching of DC Loads

24V DC

[A] 6

--

48V DC

[A] 4

--

DC-12 L/R < 1 ms resistive loads at

110V DC

[A] 0.6

--

220V DC

[A] 0.2

--

440V DC

[A] 0.08

--

24V DC

[A] 4

--

DC-14L/R <15 ms inductive

48V DC

[A] 2.5

--

loads with economy resistor in 110V DC

[A] 0.4

--

series at

220V DC

[A] 0.12

--

440V DC

[A] 0.05

--

24V DC

[A] 2.8

2.3

DC-13 switching electromagnets at

48V DC

[A] 1.2

1

110V DC

[A] 0.55

0.55

220V DC

[A] 0.27

0.27

440V DC

[A] 0.15

0.15

Fuse gG

[A] 10

10

[A] 10

10

Min. switching capacity according to IEC 60947-5-4 15V/ 10 mA 15V/ 2 mA

Load Carrying Capacity per UL/CSA

Rated voltage

AC

[V]

max.600

Continuous rating

at 40 °C (104 °F) [A]

10

Switching capacity

AC

[A] A600

B600

Rated voltage

DC

[V]

max.600

Switching capacity

DC

[A]

Q600

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

13

100-K/104-K Miniature Contactors Specifications

Table 8 - General

Attribute

Value

Rated Isolation Voltage Ui

IEC

[V]

690

UL, CSA

[V]

600

Rated Impulse Voltage Withstand Uimp

[kV]

6

Rated Voltage Ue

AC 50/60 Hz

[V] 230, 240, 400, 415, 460, 500, 575, 690

DC

[V]

24, 48, 110, 220, 440

Insulation Class of the Coil

Class F per IEC 60085 Class 105 insulation system per
UL 508

Rated coil frequency

AC 50/60 Hz, DC

Ambient Temperature

Storage

[ °C ( °F)]

-55...+80 (-67...176)

Operation at rated voltage

[ °C ( °F)]

-25...+60 (-13...140)

at 70 °C (158 °F)

15% current reduction against 60 °C (140 °F) values

Climatic Withstand

IEC60068-2-30

Max. Altitude of Installation Site

[m] 2000 NN, per IEC60947-4

Protection Class

IP2X

Single contactor cover

--

Contactor with frame terminal block

--

Auxiliary contact

IP2X

Protection against Accidental Contact

--

Resistance to Shock

IEC60068-2

Resistance to Vibration

IEC60068-2

Mechanically Linked Contacts IEC60947-5-1,AnnexL

100-K... (on main device)

Mirror Contacts IEC60947-4 Annex F

100-K...+100-KF...

Table 9 - Standards Compliance and Certifications

Standards Compliance Certifications

IEC/EN 60947-1,-4-1,-5-1,-5-4 CE Marked

UL 508

CCC

CSA 22.2. No. 14 NF F 62-000

cULus Listed (File No. E41850, Guide NLDX, NLDX7)

Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

14

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Life-Load Curves
Life-Load Curves
Figure 1 - AC-3, Switching of squirrel-cage motors while starting /AC-1, Non- or slightly inductive loads, resistance furnaces
10

Contact Life (millions of operations)

1
100-K12 100-K09 0.1 100-K05

0.01 1

10

100

Rated current Ie AC-3 [A] (Dashed curves - - - - AC-1 only, open)
Electrical life; Ue = 400...460V AC

Figure 2 - AC-4, Stepping of squirrel-cage motors
10

100-K09; 100-K12

100-K05

1

Contact Life (millions of operations)

0.1

0.01 0.1

1
Rated current Ie AC-4 [A] Electrical life; Ue = 400...460V AC
Rockwell Automation Publication 100-TD013J-EN-P - April 2021

10
15

100-K/104-K Miniature Contactors Approximate Dimensions

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Figure 3 - 100-K Miniature Contactor with 193-K Overload Relay

44.9 (1-25/32) 35 (1-25/64)

4 (5/32)

78.7 (3-7/64) 49 (1-15/16) 35.2 (1-25/64)

50 (1-31/32) 49.2 (1-15/16) 108.2 (4-1/4)
56 (2-13/64) 54 (2-1/8)

Figure 4 - Mounting Position

36.9 (1-29/64)
25° 25°

63.5 (2-1/2)
180°

12 *) *) -Minimum distance to grounded parts or walls

16

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors

Product Selection--100-C/104-C Contactors
· Compact sizes from 4...55 kW/5...75 Hp (9...97 A) · Common accessories for all contactor sizes · Front and side mounting of auxiliary contacts · Electronic and pneumatic timing modules · Space-saving coil-mounted control modules · Reversible coil terminations (line or load side) · All devices can be attached to 35 mm DIN mounting Rail · Environmentally friendly materials

100-C Contactor

104-C Reversing Contactor

The Bulletin 100-C/104-C IEC contactor family, along with a wide range of common accessories and Bulletin 193 solid-state overload relays, provides the most compact and flexible starter component system available.

3-Pole AC- and DC-operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

Hp (60 Hz)

Auxiliary Contacts

40 °C (104 °F)

AC-3

AC-1

1-Phase

3-Phase

230V 400/415V 500V 690V

115V 230V 200V 230V 460V 575V N.O.

N.C.

1

0

9

32

3

4

4

4

1/2 1-1/12 2

2

5 7-1/12

0

1

1

0

12

32

4

5.5

5.5 5.5 1/2

2

3

3 7-1/2 10

0

1

1

0

16

32

5.5

7.5

7.5

7.5

1

3

5

5

10

15

0

1

1

0

23

32

7.5

11

13

10

2

3

5 7-1/2 15

15

0

1

0

0

30

65

10

15

15

15

2

5 7-1/2 10

20

25

1

0

0

1

0

0

37

65

11

18.5/20

20 18.5

3

5

10

10

25

30

1

0

0

1

0

0

43

85

13

22

25

22

3 7-1/2 10

15

30

30

1

0

0

1

0

0

55

85

15

30

30

30

5

10

15

20

40

40

1

0

0

1

0

0

60

100

18.5

32

37

32

5

10

15

20

40

50

1

0

0

1

0

0

72

100

22

40

45

40

5

15

20

25

50

60

1

0

0

1

0

0

85

100

25

45

55

45 7-1/2 15

25

30

60

60

1

0

0

1

0

0

97

130

30

55

55

55

10

20

30

30

75

75

1

0

0

1

Cat. No.(1)
100-C0910 100-C0901 100-C1210 100-C1201 100-C1610 100-C1601 100-C2310 100-C2301 100-C3000 100-C3010 100-C3001 100-C3700 100-C3710 100-C3701 100-C4300 100-C4310 100-C4301 100-C5500 100-C5510 100-C5501 100-C6000 100-C6010 100-C6001 100-C7200 100-C7210 100-C7201 100-C8500 100-C8510 100-C8501 100-C9700 100-C9710 100-C9701

(1) For screwless terminals on 100-C09...C16, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C0910 becomes 100-CR0910. The AC-1 rating for the 100-CR is limited to 25 A.

 Coil voltage code and terminal position--see page 19

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

17

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100-C/104-C Contactors

4-Pole AC- and DC-Operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

3-phase kW (50 Hz)(2)

Hp (60 Hz)

Contact Configuration, Main Poles

40 °C (104 °F) 230V 400/415V 500V 690V

1-Phase

3-Phase(2)

AC-3

AC-1

115V 230V 200V 230V 460V 575V N.O.

N.C.

Cat. No.(1)

4

0

100-C09400

9

32

3

4

4 4 1/2 1-1/2 2

2

5 7-1/2

3

1

100-C09300

2

2

100-C09200

4

0

100-C12400

12

32

4

5.5

5.5 5.5 1/2

2

3

3 7-1/2 10

3

2

4

16

32

5.5

7.5

7.5 7.5

1

3

5

5

10

10

3

2

4

23

32

7.5

11

13 10

2

3

5 7-1/2 15

15

3

2

4

37

75

11 18.5/20 20 18.5 3

5

10

10

25

30

2

4

85

130 25

45

55 45 7-1/2 15

25 30 60 50

2

1

100-C12300

2

100-C12200

0

100-C16400

1

100-C16300

2

100-C16200

0

100-C23400

1

100-C23300

2

100-C23200

0

100-C40400

2

100-C40200

0

100-C90400

2

100-C90200

(1) For screwless terminals on 100-C09...C16, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C0910 becomes 100-CR0910. The AC-1 rating for the 100-CR is limited to 25 A.
(2) Three-phase ratings apply only to contactors with at least three N.O. power poles.  Coil voltage code and terminal position-- see page 19.
Reversing AC- and DC-Operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

Hp (60 Hz)

Auxiliary Contacts per Contactor

40 °C (104 °F)

AC-3

AC-1

1-Phase

3-Phase

230V 400/415V 500V 690V

115V 230V 200V 230V 460V 575V N.O.

N.C. (1)

9

32

3

4

4 4 1/2 1-1/2 2

2

5 7-1/2

1

1

12

32

4

5.5

5.5 5.5 1

2

3

3 7-1/2 10

1

1

16

32

5.5

7.5

7.5 7.5 1

3

5

5

10 15

1

1

23

32

7.5

11

13 10 2

3

5 7-1/2 15 20

1

1

0

1

30

65

10

15

15 15 2

5 7-1/2 10 20 25

1

1

0

1

37

65

11 18.5/20 20 18.5 3

5

10 10 25 30

1

1

0

1

43

85

13

22

25 22 3 7.5 10 15 30 30

1

1

0

1

55

85

15

30

30 30 5 10 15 20 40 40

1

1

0

1

60

100

18.5

32

37 32 5 10 15 20 40 50

1

1

0

1

72

100

22

40

45 40 5 15 20 25 50 60

1

1

0

1

85

100

25

45

55 45 7-1/2 15 25 30 60 60

1

1

0

1

97

130

30

55

55 55 10 15 30 30 75 75

1

1

(1) The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.  Coil voltage code and terminal position-- see page 19.

Cat. No.
104-C0922 104-C1222 104-C1622 104-C2322 104-C3002 104-C3022 104-C3702 104-C3722 104-C4302 104-C4322 104-C5502 104-C5522 104-C6002 104-C6022 104-C7202 104-C7222 104-C8502 104-C8522 104-C9702 104-C9722

18

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100-C/104-C Contactors

Coil Voltage Codes

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100-C0910 becomes Cat. No.100-C09D10.

AC Voltages [V] 12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

50 Hz

R

K

V

W

X

Y

KP

--

D

P

S

KG

L

--

--

60 Hz

Q

J

--

V

--

X

--

KP

--

D

--

--

KG

H

L

50/60 Hz

--

KJ

--

--

--

KY KP

--

KD

--

--

KG

KL(1)

--

--

(1) Not available on 100/104-C90 or -C97 contactors.

AC Voltages [V]

220... 230

230

230... 240

240

277

347

380

380... 400

400

400... 415

440

480

500

550 600

50 Hz

F

--

VA

T

--

--

--

N

--

G

B

--

M

C

--

60 Hz

--

--

--

A

T

I

E

--

--

--

N

B

--

--

C

50/60 Hz

KL(1)

KF

--

KA

--

--

--

--

KN

--

KB

--

--

--

--

(1) Not available on 100/104-C90 or -C97 contactors.

DC Voltages [V]

9

12

24

24

36

36...48

48

48...72

60

64

100-C09...C55

Electronic with Integrated Diode

--

EQ

EJ

QJ(1)

--

EW

--

EY

--

--

100-C60...C97 with Integrated Diode DR

DQ

DJ

--

DW

--

DY

--

DZ

DB

(1) "QJ" coil has faster dropout time (16...21 ms).

DC Voltages [V]

72

80

110 110...125 115

125

220 220...250 230

250

100-C09...C55

Electronic with Integrated Diode

--

--

--

ED

--

--

--

EA

--

--

100-C60...C97 with Integrated Diode DG

DE

DD

--

DP

DS

DA

--

DF

DT

Coil Terminal Position
All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a "U" prior to the coil voltage code. Ordering example: Cat. No. 100-C09UD10.

Cat. No.100-C0910 Line Side

Cat. No.100-C09U10 Load Side

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

19

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100-C/104-C Contactors

Assignment of Contacts

Table valid for: AC / DC = 0.85...1.1 x Us, Tamb = -25 °C...+60 °C (-13...140 °F), normal position (horizontal rail mounting)

Device Combinations in Accordance with IEC 60947-1 / -4-1

Auxiliary Contact Blocks

Circuit Diagram

Control

100-C09_10 100-C12_10 100-C16_10 100-C23_10

100-C Contactors (AC and DC Control)

100-C09_01 100-C12_01 100-C16_01 100-C23_01

100-C30_00 100-C37_00 100-C43_00 100-C55_00 100-C60_00 100-C72_00 100-C85_00 100-C97_00

100-C09_400 100-C12_400 100-C16_400 100-C23_400 100-C40_400 100-C90_400

100-C09_300 100-C12_300 100-C16_300 100-C23_300

100-C09_200 100-C12_200 100-C16_200 100-C23_200 100-C40_200 100-C90_200

Side Mounting (1)

A1 1 K1
A2 2

3 5 13 4 6 14

A1 1 3 5 21 K1
A2 2 4 6 22

A1 1 3 5 K1
A2 2 4 6

A1 1 3 5 7

A1 1 3 5 R7

A1 1 R3 R5 7

K1

K1

K1

A2 2 4 6 8

A2 2 4 6 R8

A2 2 R4 R6 8

21

100-SB01

AC/DC

10 + 01 = 11

01 + 01 = 02 (2)

00 + 01 = 01

00 + 01 = 01

00 + 01 = 01

00 + 01 = 01

22

100-SB10

13

AC/DC

10 + 10 = 20 (2)

01 + 10 = 11

00 + 10 = 10

00 + 10 = 10

00 + 10 = 10

00 + 10 = 10

14

35 47 36 48 33 43 34 44 31 43 32 44 31 41 32 42
43 44 31 32

11 21

100-SB02

AC/DC

10 + 02 = 12 (2)

--

00 + 02 = 02

00 + 02 = 02

00 + 02 = 02

00 + 02 = 02

12 22

100-SB11

13 21

AC/DC

10 + 11 = 21 (2)

01 + 11 = 12 (2)

00 + 11 = 11

14 22

00 + 11 = 11

00 + 11 = 11

00 + 11 = 11

13 23

100-SB20

AC/DC

10 + 20 = 30 (2)

01 + 20 = 21 (2)

00 + 20 = 20

00 + 20 = 20

00 + 20 = 20

00 + 20 = 20

14 24

17 25
100-SBL11 (3)
18 26

AC/DC 10 + L11 = L21 (2) 01 + L11 = L12 (2) 00 + L11 = L11

00 + L11 = L11

00 + L11 = L11

(1) Up to 8 auxiliary contacts possible: contactor + front mounted (AC max. 4 N.C. / DC max. 4 N.C.), side mounted (AC max. 2 N.O. / DC max. 2 N.O. and max. 2 N.C.). (2) Double numbering: because of double numbering only left-side mounting is recommended. (3) Early make and/or late break.

00 + L11 = L11

20

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100-C/104-C Contactors

Device Combinations in Accordance with IEC 60947-1 / -4-1

Auxiliary Contact Blocks

Circuit Diagram

Control

100-C09_10 100-C12_10 100-C16_10 100-C23_10

100-C Contactors (AC and DC Control)

100-C09_01 100-C12_01

100-C30_00 100-C37_00 100-C43_00 100-C55_00

100-C09_400 100-C12_400 100-C16_400

100-C16_01 100-C23_01

100-C60_00 100-C72_00 100-C85_00 100-C97_00

100-C23_400 100-C40_400 100-C90_400

100-C09_300 100-C12_300 100-C16_300 100-C23_300

100-C09_200 100-C12_200 100-C16_200 100-C23_200 100-C40_200 100-C90_200

Front Mounting (1)

A1 1 3 5 13

A1 1 3 5 21

K1

K1

A2 2 4 6 14

A2 2 4 6 22

A1 1 3 5 K1
A2 2 4 6

A1 1 3 5 7

A1 1 3 5 R7

A1 1 R3 R5 7

K1

K1

K1

A2 2 4 6 8

A2 2 4 6 R8

A2 2 R4 R6 8

100-FA02, 100-FAB02
100-FA11, 100-FAB11
100-FB11, 100-FBB11
100-FC11, 100-FCB11

51 61
52 62 53 61
54 62 13 21
14 22 23 31
24 32

AC/DC AC/DC AC/DC AC/DC

10 + 02 = 12 10 + 11 = 21
-- 10 + 11 = 21

01 + 02 = 03 01 + 11 = 12
-- --

00 + 02 = 02 00 + 11 = 11 00 + 11 = 11
--

00 + 02 = 02 00 + 11 = 11 00 + 11 = 11
--

00 + 02 = 02 00 + 11 = 11 00 + 11 = 11
--

00 + 02 = 02 00 + 11 = 11 00 + 11 = 11
--

100-FA20, 100-FAB20

53 63 54 64

AC/DC

10 + 20 = 30

01 + 20 = 21

00 + 20 = 20

00 + 20 = 20

00 + 20 = 20

17 25

100-FBL11 (2)

AC/DC

--

18 26

--

00 + L11 = L11

00 + L11 = L11

00 + L11 = L11

100-FA22, 100-FAB22

53 61 71 83 54 62 72 84

AC/DC

10 + 22 = 32

01 + 22 = 23

00 + 22 = 22

00 + 22 = 22

00 + 22 = 22

100-FB22, 100-FBB22

13 21 31 43

AC/DC

--

14 22 32 44

--

00 + 22 = 22

00 + 22 = 22

00 + 22 = 22

100-FC22, 100-FCB22

21 31 43 53

AC/DC

10 + 22 = 32

--

--

--

--

22 32 44 54

100-FA31, 100-FAB31

53 61 73 83 54 62 74 84

AC/DC

10 + 31 = 41

01 + 31 = 32

00 + 31 = 31

00 + 31 = 31

00 + 31 = 31

100-FA40, 100-FAB40

53 63 73 83 54 64 74 84

AC/DC

10 + 40 = 50

01 + 40 = 41

00 + 40 = 40

00 + 40 = 40

00 + 40 = 40

100-FAL22 (2)

53 61 75 87 54 62 76 88

AC/DC

10 + L22 = L32

01 + L22 = L23 00 + L22 = L22 00 + L22 = L22 00 + L22 = L22

100-FA04, 100-FAB04

51 61 71 81 52 62 72 82

AC/DC

10 + 04 = 14

01 + 04 = 05

00 + 04 = 04

00 + 04 = 04

00 + 04 = 04

100-FA13, 100-FAB13

53 61 71 81 54 62 72 82

AC/DC

10 + 13 = 23

01 + 13 = 14

00 + 13 = 13

00 + 13 = 13

00 + 13 = 13

100-FB02, 100-FBB02

11 21 12 22

AC/DC

10 + 02 = 12

01 + 02 = 03

00 + 02 = 02

00 + 02 = 02

00 + 02 = 02

100-FB20, 100-FBB20

13 23 14 24

AC/DC

10 + 20 = 30

01 + 20 = 21

00 + 20 = 20

00 + 20 = 20

00 + 20 = 20

100-FC31, 100-FCB31

23 31 43 53 24 32 44 54

AC/DC

10 + 31 = 41

01 + 31 = 32

00 + 31 = 31

00 + 31 = 31

00 + 31 = 31

(1) Up to 8 auxiliary contacts possible: contactor + front mounted (AC max. 4 N.C. / DC max. 4 N.C.), side mounted (AC max. 2 N.O. / DC max. 2 N.O. and max. 2 N.C.). (2) Early make and/or late break.

00 + 20 = 20 00 + L11 = L11 00 + 22 = 22 00 + 22 = 22
-- 00 + 31 = 31 00 + 40 = 40 00 + L22 = L22 00 + 04 = 04 00 + 13 = 13 00 + 02 = 02 00 + 20 = 20 00 + 31 = 31

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

21

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Product Selection--100S-C/104S-C Safety Contactors

· Mechanically linked N.C. auxiliary contacts

· Front-mounted auxiliary contacts

- Gold bifurcated

- Protective cover to prevent manual operation

- Permanently fixed

- Red contact housing for easy identification

- "Mechanically Linked" or "Mirror Contact" symbol

· AC and DC operating coils

· SUVA Third-party certification · Reversing contactors:

100S-C Safety Contactor

- 3 Main contacts

- Include reversing power wiring

· Include mechanical/electrical Interlock

104S-C Reversing Safety Contactor

Bulletin 100S-C/104S-C safety contactors provide mechanically linked positively guided contacts, required in feedback circuits of modern safety applications. The mechanically linked N.C. auxiliary contacts do not change state when a power pole welds. In addition, the goldplated bifurcated auxiliary contacts are ideally suited for low-energy applications or feedback control circuits with multiple seriesconnected N.C. auxiliary contacts.

3-Pole AC- and DC-operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

Hp (60 Hz)

Auxiliary Contacts

40 °C (104 °F)

230V 400/415V 500V 690V

1-Phase

3-Phase

Cat. No.(1) (2)

AC-3

AC-1

115V 230V 200V 230V 460V 575V N.O.

N.C.

0

5

100S-C0905BC

9

32

3

4

4

4

1/2 1-1/2 2

2

5

7-1/2

1

4

100S-C0914BC

0

5

100S-C1205BC

12

32

4

5.5

5.5

5.5

1/2

2

3

3

7-1/2

10

1

4

100S-C1214BC

0

5

100S-C1605BC

16

32

5.5

7.5

7.5

7.5

1

3

5

5

10

15

1

4

100S-C1614BC

0

5

100S-C2305BC

23

32

7.5

11

13

10

2

3

5 7-1/2 15

15

1

4

100S-C2314BC

0

4

100S-C3004BC

30

65

10

15

15

15

2

5 7-1/2 10

20

25

1

4

100S-C3014BC

0

4

100S-C3704BC

37

65

11

18.5/20 20 18.5

3

5

10

10

25

30

1

4

100S-C3714BC

0

4

100S-C4304BC

43

85

13

22

25

22

3 7-1/2 10

15

30

30

1

4

100S-C4314BC

0

4

100S-C5504BC

55

85

15

30

30

30

5

10

15

20

40

40

1

4

100S-C5514BC

0

4

100S-C6004BC(3)

60

100

18.5

32

37

32

5

10

15

20

40

50

1

4

100S-C6014BC(3)

0

4

100S-C7204BC(3)

72

100

22

40

45

40

5

15 20 25

50

60

1

4

100S-C7214BC(3)

0

4

100S-C8504BC(3)

85

100

25

45

55

45 7-1/2 15

25

30

60

60

1

4

100S-C8514BC(3)

0

4

100S-C9704BC(3)

97

130

30

55

55

55

10

15 30 30

75

75

1

4

100S-C9714BC(3)

(1) For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C0905BC becomes
Cat. No. 100S-C0905C.
(3) Front- and side-mount auxiliary contacts on Cat. Nos. 100S-C60...C97 conform to mirror contact performance only.

 Coil voltage code and terminal position-- see page 25.

22

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

4-Pole AC- and DC-operated Contactors

Rated Operational Current Ie
[A]

Ratings for Switching AC Motors

AC-2, AC-3, AC-4 3-Phase kW (50 Hz)(3)

Hp (60 Hz)

40 °C (104 °F) 230V

400V/ 415V

500V

690V

1-Phase

3-Phase(3)

Contact Configuration

Main Pole

Auxiliary Contacts

Cat. No.(1) (2)

AC-3 AC-1

115V 230V 200V 230V 460V 575V N.O.

N.C.

N.O.

N.C.

4

0

0

4

100S-C09404BC

9 32 3

4

4 4 1/2 1-1/2 2 2 5 7-1/2

3

1

0

4

100S-C09304BC

4

0

0

4

100S-C12404BC

12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 3

1

0

4

100S-C12304BC

4

0

0

4

100S-C16404BC

16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15

3

1

0

4

100S-C16304BC

4

0

0

4

100S-C23404BC

23 32 7.5

11

13 10 2

3 5 7-1/2 15 15

3

1

0

4

100S-C23304BC

(1) For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09404BC becomes
Cat. No. 100S-C09404C.
(3) Three-phase ratings only apply to contactors with at least three N.O. power poles.

 Coil voltage code and terminal position-- see page 25.

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

23

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Reversing AC- and DC-operated Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3, AC-4

3-phase kW (50 Hz)

Hp (60 Hz)

Auxiliary Contacts

40 °C (104 °F)

230V

400/ 415V

500V

690V

1-Phase

3-Phase

Cat. No.(1) (2)

AC-3 AC-1

115V 230V 200V 230V 460V 575V N.O. N.C.(3)

0

6 104S-C09012BC

9

32

3

4

4

4

1/2

1-1/2

2

2

5

7-1/2

1

5 104S-C09210BC

0

6 104S-C12012BC

12

32

4

5.5 5.5 5.5

1/2

2

3

3

7-1/2

10

1

5 104S-C12210BC

0

6 104S-C16012BC

16

32 5.5 7.5 7.5 7.5

1

3

5

5

10

15

1

5 104S-C16210BC

0

6 104S-C23012BC

23

32

7.5

11

13

10

2

3

5

7-1/2

15

15

1

5 104S-C23210BC

30

65

10

15

15

15

2

0

5 104S-C30010BC

5

7-1/2

10

20

25

1

5 104S-C30210BC

0

5 104S-C37010BC

37

65

11 18.5/20 20 18.5

3

5

10

10

25

30

1

5 104S-C37210BC

0

5 104S-C43010BC

43

85

13

22 25 22

3

7-1/2

10

15

30

30

1

5 104S-C43210BC

55

85

15 30 30 30

5

0

5 104S-C55010BC

10

15

20

40

40

1

5 104S-C55210BC

0

5 104S-C60010BC(4)

60

100 18.5 32

37

32

5

10

15

20

40

50

1

5 104S-C60210BC(4)

72

100

22

40

45

40

5

0

5 104S-C72010BC(4)

15

20

25

50

60

1

5 104S-C72210BC(4)

0

5 104S-C85010BC(4)

85

100 25 45 55 45 7-1/2

15

25

30

60

60

1

5 104S-C85210BC(4)

97

130 30 55 55 55

10

15

30

30

75

75

0

5 104S-C97010BC(4)

1

5 104S-C97210BC(4)

(1) For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C0905BC becomes
Cat. No. 104S-C0905C.
(3) One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
(4) Front- and side-mount auxiliary contacts on Cat. Nos. 104S-C60...C97 conform to mirror contact performance only.

 Coil voltage code and terminal position-- see page 25.

24

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Coil Voltage Codes

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100S-C0905BC becomes Cat. No.100S-C09D05BC.

AC Voltages [V] 12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

50 Hz

R

K

V

W

X

Y

KP

--

D

P

S

KG

L

--

--

60 Hz

Q

J

--

V

--

X

--

KP

--

D

--

--

KG

H

L

50/60 Hz

--

KJ

--

--

--

KY

KP

--

KD

--

--

KG

KL(1)

--

--

(1) Not available on 100S/104S-C97 contactors.

AC Voltages [V]

220... 230

230

230... 240

240

277

347

380

380... 400

400

400... 415

440

480

500 550 600

50 Hz

F

--

VA

T

--

--

--

N

--

G

B

--

M

C

--

60 Hz

--

--

--

A

T

I

E

--

--

--

N

B

--

--

C

50/60 Hz

KL(1)

KF

--

KA

--

--

--

--

KN

--

KB

--

--

--

--

(1) Not available on 100S/104S-C97 contactors.

DC Voltages [V]

9

12

24

24

36

36...48

48

48...72

60

64

100S-C09...C55

Electronic with Integrated Diode

--

EQ

EJ

QJ(1)

--

EW

--

EY

--

--

100S-C60...C97 with Integrated Diode DR

DQ

DJ

--

DW

--

DY

--

DZ

DB

(1) "QJ" coil has faster dropout time (16...21 ms).

DC Voltages [V]

72

80

110 110...125 115

125

220 220...250 230

250

100S-C09...C55

Electronic with Integrated Diode

--

--

--

ED

--

--

--

EA

--

--

100S-C60...C97 with Integrated Diode DG

DE

DD

--

DP

DS

DA

--

DF

DT

Coil Terminal Position
All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a "U" prior to the coil voltage code. Ordering example: Cat. No. 100S-C09UD05BC.

Cat. No.100S-C0905CLine Side Cat. No.100S-C09U05CLoad Side

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

25

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Assignment of Contacts

Figure 5 - Safety Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts

51 61 71 81

51 61 71 81

52 62 72 82 A1 1 3 5 21 K1 A2 2 4 6 22
100S-C0905C...C2305C
11 21 31 41

52 62 72 82 A1 1 3 5 13 K1 A2 2 4 6 14
100S-C0914C...C2314C
13 21 31 43

12 22 32 42 A1 1 3 5 K1 A2 2 4 6
100S-C3004C...C5504C
11 21 31 41

14 22 32 44 A1 1 3 5 K1 A2 2 4 6
100S-C3022C...C5522C
13 21 31 43

12 22 32 42

14 22 32 44

A1 1 3 5 K1

A1 1 3 5 K1

A2 2 4 6
100S-C6004C...C9704C

A2 2 4 6
100S-C6022C...C9722C

Figure 6 - Safety Contactors with 4 Main Contacts and Standard Front-mount Auxiliary Contacts

53 61 71 83
54 62 72 84 A1 1 3 5 21 K1 A2 2 4 6 22
100S-C0923C...C2323C
11 21 31 41
12 22 32 42 A1 1 3 5 _3 K1 A2 2 4 6 _4
100S-C3014C...C5514C
11 21 31 41
12 22 32 42 A1 1 3 5 _3 K1 A2 2 4 6 _4
100S-C6014C...C9714C

11 21 31 41
12 22 32 42 A1 1 3 5 7 K1 A2 2 4 6 8
100S-C09404C...C23404C
13 21 31 43
14 22 32 44 A1 1 3 5 7 K1 A2 2 4 6 8
100S-C09422C...C23422C

11 21 31 41
12 22 32 42 A1 1 3 5 R7 K1 A2 2 4 6 R8
100S-C09304C...C23304C
13 21 31 43
14 22 32 44 A1 1 3 5 R7 K1 A2 2 4 6 R8
100S-C09322C...C23322C

26

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Figure 7 - Safety Reversing Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts

51 61 71 81

21

51 61 71 81

51 61 71 81

21

51 61 71 81

52 62 72 82

22

52 62 72 82

A1 1 3 5 21

21

A1 1 3 5 21

K1

K2

A2 2 4 6 22

22

A2 2 4 6 22

104S-C09012C...C23012C

52 62 72 82

22

52 62 72 82

A1 1 3 5 13

21

A1 1 3 5 13

K1

K2

A2 2 4 6 14

22

A2 2 4 6 14

104S-C09210C...C23210C

11 21 31 41

21

11 21 31 41

11 21 31 41

21

11 21 31 41

12 22 32 42

22

12 22 32 42

A1 1 3 5 K1

21

A1 1

K2

35

A2 2 4 6

22

A2 2 4 6

104S-C30010C...C55010C

12 22 32 42

22

12 22 32 42

A1 1 3 5

_3 21

A1 1 3 5

_3

K1

K2

A2 2 4 6

_4

22

A2 2 4 6

_4

104S-C30210C...C55210C

11 21 31 41

21

11 21 31 41

11 21 31 41

21

11 21 31 41

12 22 32 42

22

12 22 32 42

A1 1 3 5 K1

21

A1 1 3 5

K1

A2 2 4 6

22

A2 2 4 6

104S-C60010C...C97010C

12 22 32 42

22

12 22 32 42

A1 1 3 5

_3

21

A1 1 3 5

_3

K1

K1

A2 2 4 6

_4

22

A2 2 4 6

_4

104S-C60210C...C97210C

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

27

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Figure 8 - Safety Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

51 61 71 81

51 61 71 81

53 61 71 83

52 62 72 82 A1 1 3 5 21 K1 A2 2 4 6 22
100S-C0905BC...C2305BC
11 21 31 41

52 62 72 82 A1 1 3 5 13 K1 A2 2 4 6 14
100S-C0914BC...C2314BC
13 21 31 43

54 62 72 84 A1 1 3 5 21 K1 A2 2 4 6 22
100S-C0923BC...C2323BC
11 21 31 41

12 22 32 42

A1 1 K1

35

A2 2 4 6
100S-C3004BC...C5504BC

11 21 31 41

14 22 32 44 A1 1 3 5 K1 A2 2 4 6
100S-C3022BC...C5522BC
13 21 31 43

12 22 32 42 A1 1 3 5 _3 K1 A2 2 4 6 _4
100S-C3014BC...C5514BC
11 21 31 41

12 22 32 42

14 22 32 44

12 22 32 42

A1 1 K1

35

A2 2 4 6
100S-C6004BC...C9704BC

A1 1 3 5 K1
A2 2 4 6
100S-C6022BC...C9722BC

A1 1 3 5 _3 K1
A2 2 4 6 _4
100S-C6014BC...C9714BC

Figure 9 - Safety Contactors with 4 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

11 21 31 41

11 21 31 41

12 22 32 42 A1 1 3 5 7 K1 A2 2 4 6 8
100S-C09404BC...C23404BC
13 21 31 43

12 22 32 42 A1 1 3 5 R7 K1 A2 2 4 6 R8
100S-C09304BC...C23304BC
13 21 31 43

14 22 32 44
A1 1 3 5 7 K1
A2 2 4 6 8
100S-C09422BC...C23422BC

14 22 32 44
A1 1 3 5 R7 K1
A2 2 4 6 R8
100S-C09322BC...C23322BC

28

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100S-C/104S-C Safety Contactors

Figure 10 - Safety Reversing Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

51 61 71 81

21

51 61 71 81

51 61 71 81

21

51 61 71 81

52 62 72 82

22

52 62 72 82

A1 1 3 5 21 K1

21

A1 1 3 5 21

K2

A2 2 4 6 22

22

A2 2 4 6 22

104S-C09012BC...C23012BC

52 62 72 82

22

52 62 72 82

A1 1 3 5 13 K1

21

A1 1 3 5 13

K2

A2 2 4 6 14

22

A2 2 4 6 14

104S-C09210BC...C23210BC

11 21 31 41

21

11 21 31 41

11 21 31 41

21

11 21 31 41

12 22 32 42

22

12 22 32 42

12 22 32 42

22

12 22 32 42

A1 1 3 5

21

A1 1 3 5

A1 1 3 5

_3 21

A1 1 3 5 _3

K1

K2

K1

K2

A2 2 4 6

22

A2 2 4 6

104S-C30010BC...C55010BC

A2 2 4 6

_4 22

A2 2 4 6 _4

104S-C30210BC...C55210BC

11 21 31 41

21

11 21 31 41

11 21 31 41

21

11 21 31 41

12 22 32 42

22

12 22 32 42

A1 1 3 5

21

A1 1 3 5

K1

K1

A2 2 4 6

22

A2 2 4 6

104S-C60010BC...C97010BC

12 22 32 42

22

12 22 32 42

A1 1 3 5 _3 21

A1 1 3 5 _3

K1

K1

A2 2 4 6 _4 22

A2 2 4 6 _4

104S-C60210BC...C97210BC

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

29

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection--100Q-C Capacitor-switching Contactors
Product Selection--100Q-C Capacitor-switching Contactors

· Compact sizes · Limits high inrush currents · AC and DC coil control · Reversible coil terminals · Panel or 35 mm DIN Rail mounting · Environmentally friendly materials

The Bulletin 100Q-C Capacitor-Switching contactors are designed for switching banks of capacitors. The unique design uses front-mounted resistor elements that limit the severely high inrush currents seen in these applications. This reduces stress to the contactors and the capacitors, as well as allowing a more compact and economical design without the use of air-core reactors.

For Applications per IEC 60947-4 (AC-6b)

Ratings for Switching Capacitor Banks @ 40 °C (104 °F)

1-Phase 50 Hz [kVAR]

3-Phase 50 Hz [kVAR]

230V 240V 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V

5

5

8.5

9

10.5

15

8.5

8.5

15

15.5 18.5

25

8

8.5

14

14.5 17.5

24

14

14

25

25

30

40

Aux. Contacts

N.O. N.C.

1

1

2

0

1

1

2

0

Cat. No.
100Q-C1611 100Q-C1620 100Q-C3711 100Q-C3720

For Applications per UL/CSA

1-Phase 60 Hz [kVAR]

115V

230V

200V

2.2

4.5

6.5

3.6

7.5

11

Ratings for Switching Capacitor Banks

3-Phase 60 Hz [kVAR]

230V

460V

600V

7.5

15

18.5

12.5

20

25

Aux. Contacts

N.O.

N.C.

1

1

2

0

1

1

2

0

Cat. No.
100Q-C1611 100Q-C1620 100Q-C3711 100Q-C3720

Coil Voltage Codes
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100Q-C1611 becomes Cat. No.100Q-C16D11.

AC Voltages [V] 12 24 32 36 42 48 100 100...110 110 120 127 200 200...220 208 208...240

50 Hz

R

K

V

W

X

Y

KP

--

D

P

S

KG

L

--

--

60 Hz

Q

J

--

V

--

X

--

KP

--

D

--

--

KG

H

L

50/60 Hz

--

KJ

--

--

--

KY KP

--

KD

--

--

KG

KL

--

--

AC Voltages [V] 220...230 230 230...240 240 277 347 380 380...400 400 400...415 440 480 500 550 600

50 Hz

F

--

VA

T

--

--

--

N

--

G

B

--

M

C

--

60 Hz

--

--

--

A

T

I

E

--

--

--

N

B

--

--

C

50/60 Hz

KL

KF

--

KA

--

--

--

--

KN

--

KB

--

--

--

--

DC Voltages [V]

9 12 24 36 48 60 64 72 80 110 110...125 115 125 220 220...250 230 250

Electronic with Integrated Diode -- EQ EJ -- -- -- -- -- -- -- ED -- -- --

EA

----

Maximum Operational Rates

· 100Q-C16 200 operations/hour · 100Q-C37 100 operations/hour

30

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Accessories

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories

Auxiliary Contact Blocks

Description(1)
Auxiliary Contact Blocks for Front Mounting · 2- and 4-pole · Quick and easy mounting without tools · Electronic-compatible contacts down to
17V, 5mA · Mechanically linked performance between
N.O. and N.C. poles and to the main contactor poles (except for L types) · Models with equal function with several terminal numbering choices · 1L = Late break N.C. / early make N.O. · Bifurcated version for switching down to 5V, 3 mA also available
Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations · 1- and 2-pole · Two-way numbering for right or left
mounting on the contactor · Quick and easy mounting without tools · Electronic-compatible contacts down to
17V, 10 mA · Mirror contact performance to the main
contactor poles · 1L = Late break N.C. / early make N.O.

Connection Diagrams

For Use With N.O. N.C.

100-C all 0 2 C3000...C9700

100-C all

1 1 C3000...C9700

C0910...C2310

100-C all 20
C3000...C9700

100-C all 1L 1L C3000...C9700

04

100-C all

13

100-C all

100-C all

2 2 C3000...C9700

C0910...C2310

100-C all 31
C0910...C2310

40

100-C all

1 + 1L 1+1L

100-C all

01

100-C all

10

100-C all

02

100-C all

11

100-C all

20

100-C all

Cat. No.

Standard Auxiliary Contact(2) 100-FA02 100-FB02 100-FA11 100-FB11 100-FC11 100-FA20 100-FB20 100-FAL11 100-FBL11 100-FA04 100-FA13 100-FA22 100-FB22 100-FC22 100-FA31 100-FC31 100-FA40 100-FAL22 100-SA01 100-SA10 100-SA02 100-SA11 100-SA20

Bifurcated Auxiliary Contact
100-FAB02 100-FBB02 100-FAB11 100-FBB11 100-FCB11 100-FAB20 100-FBB20
-- -- 100-FAB04 100-FAB13 100-FAB22 100-FBB22 100-FCB22 100-FAB31 100-FCB31 100-FAB40 -- -- -- -- -- --

1L 1L

100-C all

100-SAL11

--

Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations
· 1- and 2-pole
· Two-way numbering for right or left mounting on the contactor
· Quick and easy mounting without tools
· Electronic-compatible contacts down to 17V, 10 mA
· Mirror contact performance to the main contactor poles
· 1L = Late break N.C. / early make N.O.

01

100-C

100-SB01

--

10

100-C(3)

100-SB10

--

02

100-C(3)

100-SB02

--

11

100-C(3)

100-SB11

--

20

100-C(3)

100-SB20

--

1L 1L

100-C(3)

100-SBL11

--

(1) Max. number of auxiliary contacts that may be mounted: AC and 24V DC electronic coil contactors--max. 4 N.O contacts on the front of the contactor, 2 N.O. contacts on the side, 4 N.C. front or side, 6 total. DC Coil contactors--max. 4 N.O. contacts on the front of the contactor or max. 2 N.O. contacts on the side, 4 N.C. front or side, 4 total.
(2) For screwless terminals (front mount only), insert "CR" after the "100-" in the catalog number. Example: Cat. No. 100-FA02 becomes Cat. No. 100-CRFA02. (3) Double numbering--Left-side mounting only is recommended for Cat. No. 100-C09...100-C23 due to double numbering.

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

31

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories

Control Modules

Timers

Description

Pneumatic Timing Modules

On-Delay

· Pneumatic timing element contacts switch after the delay

time. The contacts on the main control relay continue to

operate without delay

Off-Delay

0.3...30 s 2...180 s 0.3...30 s 2...180 s 0.1...3 s 1...30 s

Electronic Timing Modules -- On-delay
· Delay of the contactor or control relay solenoid. The contactor or control relay is energized at the end of the delay time.

10...180 s
0.1...3 s 1...30 s
10...180 s

Connection Diagrams

For Use With 100-C or 700-CF with
AC or 24V DC electronic coils(1)
100-C all, 700-CF all
100-C or 700-CF with 110...240V, 50/60Hz
coils

Cat. No. 100-FPTA30 100-FPTA180 100-FPTB30 100-FPTB180 100-ETA3 100-ETA30
100-ETA180

100-C or 700-CF with 24VDC coils

100-ETAZJ3 100-ETAZJ30
100-ETAZJ180

Electronic Timing Modules -- Off-delay
· Delay of the contactor or control relay solenoid. After interruption of the control signal, the contactor or control relay is de-energized at the end of the delay time.

0.3...3 s 1...30 s 10...180 s 0.3...3 s 1...30 s 10...180 s

100-C09...C37 or 700CF with 24V 50/60Hz
100-C or 700-CF with 110...240V 50/60Hz
coils

100-ETBKJ3 100-ETBKJ30 100-ETBKJ180
100-ETB3 100-ETB30 100-ETB180

Electronic Timing Modules
· Delay of the contactor solenoid. Contactor K 3(Y) is deenergized (off) and K 2 () is energized (on) after the end of the set Y end time. (Switching delay at 50 ms.)
· Continuous adjustment range
· High repeat

Transition Time Y Contactor 1...30 s

100-C with 110...240V 50/60Hz coils

100-ETY30

Mechanical Interlocks · For interlocking of two contactors. · Common interlock for most Bul. 100-C contactor sizes · Interlocking of different sizes possible · Mechanical and electrical interlocking possible in one
module by means of integrated auxiliary contacts · 9 mm dovetail connector included
Mechanical Latch · Following contactor latching, the contactor coil is
immediately de-energized (off) by the N.C. auxiliary contact (65-66). · Electrical or manual release · 1 N.O. + 1 N.C. auxiliary contacts · Suitable for all Bul. 100-C contactor sizes, 9...97 A
(1) Cannot be used with side-mounted auxiliary contacts on 700-CF DC relays.

Mechanical only, without auxiliary contacts
Mechanical/ electrical interlock with 2 N.C. auxiliary contacts
Maximum command duration 0.03...10 s

100-C (except 100C40, -C90)

100-MCA00

100-C (except 100C40, -C90)

100-MCA02

100-C with AC or 24V DC electronic coils (except 100-C90)

100-FL11

Coil Voltage Code: The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No. 100-FL11 becomes Cat. No.100-FL11D

AC Voltages [V](1) 50 Hz

24

48

100

110

120 230...240 240

277 380...400 400...415 440

480

K

Y

KP

D

--

VA

KA

--

N

G

B

--

60 Hz

J

--

--

--

D

--

KA

T

--

--

N

B

(1) For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

32

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories

Additional Control Modules

Description

Voltage Range

DC Interface (Electronic)
· Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor.
· Requires no additional surge suppression on the relay coils.

Input: 12V DC Output: 110...240V AC
Input: 18...30V DC Output: 110...240V AC
Input: 48V DC Output: 110...240V AC

Surge Suppressors
· For limitation of coil switching transients.
· Plug-in, coil mounted.
· Suitable for 100-C contactor sizes, 9...97 A.
· RC, varistor, and diode versions.

RC Module AC operating mechanism
Varistor Module AC/DC operating
mechanism

24...48V AC, 50/60 Hz 110...280V AC, 50/60 Hz 380...480V AC, 50/60 Hz 12...55V AC, 12...77V DC 56...136V AC/78...180V DC 137...277V AC/ 181...350V DC
278...575V AC

Diode Module DC operating mechanism

1...30 s 10...180 s

Connection Diagrams

(1) For screwless terminals, insert "CR" after the "100-" in the catalog number. Example: Cat No. 100-FSC48 becomes Cat. No.-CRFSC48.

For Use With

Cat. No.

100-JE12

100-C with AC coils 110...240V AC

100-JE 100-JE48

100-C with Coils
100-C with AC coils or 100-C09...-C43
with DC coils

100-FSC48(1) 100-FSC280(1) 100-FSC480(1) 100-FSV55(1) 100-FSV136(1) 100-FSV277(1) 100-FSV575(1)

100-C09...-C43 with DC coils

100-FSD250(1)

Assembly Components (For 100-C09...C97 contactors)
Description Dovetail Connectors · For use in contactor and starter assemblies · Single Connector -- 0 mm spacing Dovetail Connectors · For use in contactor and starter assemblies · Single Connector -- 9 mm spacing
Protective Covers · Provides protection against unintended manual operation · For contactors and front-mounted auxiliary contacts, pneumatic
timers, and latches

For Use With 100-C 100-C all

Pkg. Qty. 10

Cat. No. 100-S0

10

100-S9

1

100-SCCA

100-FA, -FB, -FC, -FP, -FL

10

100-SCFA

Reversing Power Wiring Kits · For reversing connection with a solid-state or thermal overload relay
DIN (#3) symmetrical hat rail · 35 x 7.5 x 1 m

100-C09...C23 100-C30...C37 100-C43...C55 100-C60...C97
140M-D 140M-F 100-C all

1

105-PW23

1

105-PW37

1

105-PW55

1

105-PW85

10

199-DR1

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

33

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories

Wye-Delta/Star-Delta Starter Kits

Wye-Delta power wiring kits are designed to aid in the field assembly of open-transition Wye-delta starters that use Bulletin 100-C contactors. These kits include line, load, and start-point (shorting) connections. Assembling a Wye-delta starter requires the following additional components:
· Contactors · Overload Relay · Cat. No. 100-MCA02 Mechanical/Electrical Interlock Cat. No. 100-ETY30 Electronic Y-Timer · Cat. No. 100-S9 Base Coupler for 1M to 2M contactor (optional)

3-Phase Rating

kW (50 Hz)

Hp (60 Hz)

Use with Cat. No. 100- Pkg

230V

380/ 415V

500V

690V

200V

230V

460V

575V

Delta 1M 2M

Wye Qty. 1S

5.5 7.5 7.5 7.5 5

5

10 10 C09 C09 C09

1

7.5 11

11

10

5

7.5 15

15 C12 C12

C09

1

10

15

15

13 7.5 10 20 20 C16 C16

C12

1

13 22 22 18.5 7.5 10 25 25 C23 C23 C12

1

17 25 25 25 10 15 30 30 C30 C30 C16

1

20 37 32 32 15 20 40 40 C37 C37 C23

1

22 40 40 40 20 25 50 50 C43 C43 C30

1

30 45 45 45 25 30 60 60 C55 C55 C37

1

32 55 55 55 30 40 75 75 C60 C60 C37

1

40 63 63 63 40 50 100 100 C72 C72 C43

1

50 80 80 80 50 60 125 125 C85 C85 C60

1

50 90 90 90 50 60 125 125 C97 C97 C60

1

Cat. No.
170-PW23 170-PW23 170-PW23 170-PW23 170-PW37 170-PW37 170-PW55 170-PW55 170-PW72 170-PW72 170-PW85 170-PW85

Marking Systems (For 100-C09...C97 contactors)

Description

Label Sheet · 105 self-adhesive paper labels each, 6 x 17 mm

Marking Tag Sheet · 106 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
Transparent Cover · To be used with marking tag sheets

Pkg. Qty.(1) 10 10 100

Cat. No. 100-FMS 100-FMP 100-FMC

Marking Tag Adapters · To be used with 1492W marking tag system

100

100-FMA2

(1) Must be ordered in multiples of package quantities

34

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories

Terminal Kits (For 100C09...C97 contactors)

Description

Max. Current Ratings and Wire Sizes

Stab Connector Kit · Dual stab (0.250 in.) for 100-C coil terminals · For 100-C09...C97 contactors

Stab Connector Kit · Dual stab (0.250 in.) for 100-C power terminals · For 100-C09...C23 contactors

3-Pole Terminal Lug Kit · For Cat. No. 100-C09...C23 (Line side)

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

3-Pole Terminal Lug Kit · For Cat. No. 100-C09...C23 (Load side)

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

3-Pole Terminal Lug Kit

IEC @ 40 °C

· For Cat. No. 100-C30...C37 (Line and load IEC @ 40 °C

side)

UL/CSA (Encl.)

1-Pole Terminal Lug Kit · For Cat. No. 100-C43

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

1-Pole Terminal Lug Kit · For Cat. No. 100-C60...C97

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

3-Pole Paralleling Kit · For Cat. No. 100-C09...C23

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

3-Pole Paralleling Kit · For Cat. No. 100-C30...C37

IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

(1) Must be ordered in multiples of the package quantity. (2) 16 mm2 max. according to IEC 60947; actual max. 25 mm2

45 A (4...16 mm2, fine stranded w/ ferrule)(2) 45 A (4...25 mm2, coarse stranded/solid) 40 A (#10...4 AWG, stranded/solid)
45 A (4...16 mm2, fine stranded w/ ferrule) 45 A (4...25 mm2, coarse stranded/solid) 40 A (#10...4 AWG, stranded/solid)
60 A (4...16 mm2, fine stranded w/ ferrule) 60 A (4...25 mm2, coarse stranded/solid) 55 A (#10...4 AWG, stranded/solid)
90 A (6...35 mm2, fine stranded w/ ferrule) 90 A (6...50 mm2, coarse stranded/solid) 75 A (#8...2 AWG, stranded/solid)
130 A (10...70 mm2, fine stranded w/ ferrule) 130 A (10...95 mm2, coarse stranded/solid) 130 A (#8...2/0 AWG, stranded/solid)
100 A (35...70 mm2, fine stranded w/ ferrule) 100 A (35...95 mm2, coarse stranded/solid) 100 A (#0...2/0 AWG, stranded/solid)
150 A (35...70 mm2, fine stranded w/ ferrule) 150 A (35...95 mm2, coarse stranded/solid) 150 A (#0...2/0 AWG, stranded/solid)

Pkg. Qty(1) Cat. No.

20

199-SC2

100

199-SC10

1

100-CTN23

1

100-CTL23

1

100-CT37

3

100-CT43

3

100-CT85

2

100-CP23

2

100-CP37

SEMI-F47 Voltage Sag Immunity Module

Description
SEMI-F47 Module · Meets SEMI-F47 voltage sag immunity requirements · Direct mounting to coil terminals of 100-C contactors and 700-CF control relays · Requires DC coil contactor · Optional 1...30 s ON-delay timer version

Input Voltage

For Use With(1)

24...240V AC 100-C60...C97

110...240V AC 100-C60...C97

Options without timer

Cat. No. 100-CSF47

with 1...30 s ON-delay timer

100-CSF47A30

(1) Contactor must have DC coil at the same voltage as AC input. Example: for 24V AC control, select Cat. No. 100-C09ZJ10 (24V DC coil).

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

35

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Renewal Parts
Renewal Parts
Replacement Coils for AC Contactors

AC Standard Control Voltages [V]

50 Hz -- 12 -- 24 -- 32 36 42 48 -- 100 110 -- 120 127 200 --
200...220 -- 220
220...230 --
230...240 240 -- -- --
380...400 --
400...415 440 -- 500 550

60 Hz 12 -- 24 -- -- 36 42 48 -- --
100...110 120 -- -- --
200...220 208
208...240 -- 240 260 -- -- 277 -- 347 380 440 -- -- 480 -- -- 600

50/60 Hz -- -- -- -- 24 -- -- -- -- 48 100 -- 110 -- -- 200 -- --
200...230 -- -- 230 -- -- 240 -- -- -- 400 -- -- 440 -- --

AC Coil Code
Q R J K KJ V W X Y KY KP D KD P S KG H L KL A F KF VA T KA I E N KN G B KB M C

100-C09...100-C16
Cat. No. TA006 TA404 TA013 TA407 TA855 TA481 TA410 TA482 TA414 TA860 TA861 TA473 TA856 TA425 TA428 TA862 TA049 TA296 TA864 TA474 TA441 TA851 TA440 TA480 TA858 TA065 TA067 TA071 TA863 TA457 TA475 TA859 TA479 TA476

100-C23...100-C37, 100L-C20 Cat. No. TC006 TC404 TC013 TC407 TC855 TC481 TC410 TC482 TC414 TC860 TC861 TC473 TC856 TC425 TC428 TC862 TC049 TC296 TC864 TC474 TC441 TC851 TC440 TC480 TC858 TC065 TC067 TC071 TC863 TC457 TC475 TC859 TC479 TC476

100-C40...100-C55
Cat. No. TD006 TD404 TD013 TD407 TD855 TD481 TD410 TD482 TD414 TD860 TD861 TD473 TD856 TD425 TD428 TD862 TD049 TD296 TD864 TD474 TD441 TD851 TD440 TD480 TD858 TD065 TD067 TD071 TD863 TD457 TD475 TD859 TD479 TD476

100-C60...100-C85
Cat. No. TE006 TE404 TE013 TE407 TE855 TE481 TE410 TE482 TE414 TE860 TE861 TE473 TE856 TE425 TE428 TE862 TE049 TE296 TE864 TE474 TE441 TE851 TE440 TE480 TE858 TE065 TE067 TE071 TE863 TE457 TE475 TE859 TE479 TE476

100-C90...100-C97
Cat. No. TF006 TF404 TF013 TF407 TF855 TF481 TF410 TF482 TF414 TF860 TF861 TF473 TF856 TF425 TF428 TF862 TF049 TF296
-- TF474 TF441 TF851 TF440 TF480 TF858 TF065 TF067 TF071 TF863 TF457 TF475 TF859 TF479 TF476

36

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Replacement Coils for DC Contactors

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Renewal Parts

DC Control Voltage [V]
9V Diode(1) 12V Electronic(2) 12V Diode 24V Electronic(2) 24V Electronic (3) 24V Diode(2)

DC Coil Code
DR EQ DQ EJ QJ DJ

100-C09...100-C16, 100Q-C16 Cat. No. --
TC708E --
TC714E
TC714Q
--

36...48V Electronic(2)

EW

36V Diode

DW

48...72V Electronic

EY

48V Diode

DY

60V Diode

DZ

64V Diode

DB

72V Diode

DG

80V Diode

DE

110...125V Electronic (4) ED

TC719E --
TC724E -- -- -- -- --
TC733E

110V Diode

DD

115V Diode

DP

125V Diode

DS

220...250V Electronic EA

220V Diode

DA

230V Diode

DF

250V Diode

DT

-- -- -- TC747E -- -- --

(1) Voltage operating range: 0.65...1.3 Us (2) Voltage operating range: 0.7...1.25 Us (3) Faster drop-out time (16...21 ms)
(4) Voltage operating range: 0.7...1.25 Us at 110V DC

100-C23...100-C37, 100Q-C37 Cat. No. --
TC708E --
TC714E
TC714Q
--
TC719E --
TC724E -- -- -- -- --
TC733E -- -- --
TC747E -- -- --

100-C40...100-C55 (Series A) Cat. No. --
TD708E --
TD714E
TD714Q
--
TD719E --
TD724E -- -- -- -- --
TD733E -- -- --
TD747E -- -- --

100-C40...100-C55 (Series B) Cat. No. --
TD708E2 --
TD714E2
TD714Q2
--
TD719E2 --
TD724E2 -- -- -- -- --
TD733E2 -- -- --
TD747E2 -- -- --

100-C60...100-C85
Cat. No. TE766M
-- TE708M
--
--
TE714M
-- TE719M
-- TE724M TE774M TE727M TE728M TE729M
-- TE733M TE734M TE737M
-- TE747M TE749F TE751F

100-C90...100-C97
Cat. No. TF766M
-- TF708M
--
--
TF714M
-- TF719M
-- TF724M TF774M TF727M TF728M TF729M
-- TF733M TF734M TF737M
-- TF747M TF749F TF751F

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

37

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Specifications
Table 10 - Main Circuits

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97

Coil Type:

Conventional X X X X X X X Electronic -- EI X X X X X X X

X XXXXX X X X X------ --

XX ----

AC-1 Active Power Load (50 Hz); Ambient temperature 40 °C (104 °F)

Rated Operational 500V [A] 32 32 32 32(40)(1) 65 65 75

Current, Ie

690V

[A] 32 32 32 32(40)(1) 65 65 75

230V [kW] 13 13 13 13 26 26 30

240V [kW] 13 13 13 13 27 27 31

Rated Operational 400V [kW] 22 22 22 22 45 45 52

Power, Pe

415V [kW] 23 23 23 23 47 47 54

500V [kW] 28 28 28 28 56 56 65

75 85 85 100 100 100 130 130 130
75 85 85 100 100 100 130 130 130 30 34 34 40 40 40 52 52 52 31 35 35 42 42 42 54 54 54 52 59 59 69 69 69 90 90 90 54 61 61 72 72 72 93 93 93 65 74 74 87 87 87 113 113 113

690V [kW] 38 38 38 38 78 78 90 90 102 102 120 120 120 155 155 155

AC-1 Active Power Load (50 Hz); Ambient temperature 60 °C (140 °F)

Rated Operational Current, Ie

500V 690V

[A] 32 32 32 [A] 32 32 32

32 65 65 60 32 65 65 60

230V [kW] 13 13 13 13 26 26 24

240V [kW] 13 13 13 13 27 27 25

Rated Operational 400V [kW] 22 22 22 22 45 45 42

Power, Pe

415V [kW] 23 23 23 23 47 47 43

500V [kW] 28 28 28 28 56 56 52

60 75 75 100 100 100 110 60 75 75 100 100 100 110 24 25 25 40 40 40 44 25 26 26 42 42 42 46 42 44 44 69 69 69 76 43 45 45 72 72 72 79 52 55 55 87 87 87 95

110 110 110 110 44 44 46 46 76 76 79 79 95 95

690V [kW] 38 38 38 38 78 78 72 72 75 75 120 120 120 131 131 131

Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F), AC-2, AC-3

230V [A] 12 15 20 26.5 35 38 38

240V [A] 12 15 20 26.5 35 38 38

Rated Operational 400V

Current, Ie

415V

[A] 9 12 16 23 30 37 37 [A] 9 12 16 23 30 37 37

500V [A] 7 10 14 20 25 30 29

690V [A] 5 7 9 12 18 21 9

230V [kW] 3 4 5.5 7.5 10 11 11

38 44 56 62 72 85 85 38 44 56 62 72 85 85 37 43 55 60 72 85 85 37 43 55 60 72 85 85 30 38 44 55 67 80 80 21 25 25 34 42 49 22 11 13 15 18.5 22 25 25

85 96 85 95 85 97 85 97 80 78 49 57 25 30

240V [kW] 3 4 5.5 7.5 10 11 11

11 13 15 18.5 22 25 25 25 30

Rated Operational 400V [kW] 4 5.5 7.5 11

Power, Pe

415V [kW] 4 5.5 7.5 11

15 18.5 18.5 18.5 22 30 32 40 45 45 15 20 20 20 22 30 32 40 45 45

45 55 45 55

500V [kW] 4 5.5 7.5 13 15 20 18.5 20 25 30 37 45 55 55 55 55

690V [kW] 4 5.5 7.5 10 15 18.5 7.5 18.5 22 22 32 40 45 18.5 45 55

Load Carrying Capacity per UL/CSA

General Purpose Current (enclosed)

[A] 25 25 30 30 55 60 60 60 75 75 90 90 100 125 130 120

Rated current

115V

(enclosed), 1-phase 230V

[A] 9.8 9.8 16 24 24 34 34 [A] 10 12 17 17 28 28 28

34 34 56 56 56 80 80 28 40 50 50 68 68 68

80 100 68 88

Rated power

115V

(enclosed), 1-phase 230V

200V

Rated current

230V

(enclosed), 3-phase 460V

575V

200V

Rated power

230V

(enclosed), 3-phase 460V

575V

[Hp] 0.5 0.5 1 2 2 3 3

3 3 5 5 5 7.5 7.5 7.5 10

[Hp] 1.5 2 3 3 5 5 5

5 7.5 10 10 15 15 15 15 20

[A] 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3 48.3 62.1 78.2 78.2 78.2 92

[A] 6.8 9.6 15.2 22 28 28 28 28 42 54 54 68 80 80 80 80

[A] 7.6 11 14 21 27 34 34 34 40 52 52 65 77 65 77 96

[A] 9 11 17 17 27 32 17 32 32 41 52 62 62 22 52 77

[Hp] 2 3 5 5 7.5 10 10 10 10 15 15 20 25 25 25 30

[Hp] 2 3 5 7.5 10 10 10 10 15 20 20 25 30 30 30 30

[Hp] 5 7.5 10 15 20 25 25 25 30 40 40 50 60 50 60 75

[Hp] 7.5 10 15 15 25 30 15 30 30 40 50 60 60 20 50 75

(1) Values in () with increased cross-section and cable lug.

38

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 11 - Main Circuits

Coil Type:

Conventional Electronic -- EI

100/104-C, 100S/104S-C

09

12

16

23

30

37

43

55

60

72

85

97

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

--

--

--

--

Switching of 3-phase Motors, (50 Hz); Ambient temperature 60 °C (140 °F), AC-4

230V

[A] 12

15

20 26.5 35

38

44

56

62

72

85

96

Rated Operational Current, Ie

240V

[A] 12

15

20 26.5 35

38

44

56

62

72

85

95

400V

[A] 9

12

16

23 30

37

43

55

60

72

85

97

415V

[A] 9

12

16

23 30

37

43

55

60

72

85

97

500V

[A] 7

10

14

20

25

30

38

44

55

67 80 78

690V

[A] 5

7

9

12

18

21

25

25

34

42

49

57

230V

[kW] 3

4

5.5

7.5

10

11

13

15

18.5 22

25

30

240V

[kW] 3

4

5.5

7.5

10

11

13

15

18.5 22

25

30

Rated Operational Power, 400V

Pe

415V

[kW] 4

5.5 7.5

11

[kW] 4

5.5 7.5

11

15 18.5 22

15

20

22

30

32

40

45

55

30

32

40

45

55

500V

[kW] 4

5.5 7.5

13

15

20

25

30

37

45

55

55

690V

[kW] 4

5.5 7.5

10

15 18.5

22

22

32

40

45

55

AC-4 at approximately 200,000 operations

230V

[A] 4.3 6.6

9

9

12

14

16.5

22 25.5 31

38

44

240V

[A] 4.3 6.6

9

9

12

14

16.5

22 25.5 31

38

44

Rated Operational Current, Ie

400/415V

[A] 4.3 6.6

9

9

12

14

16.5

22 25.5 31

38

44

500V

[A] 4.3 6.6

9

9

12

14

16.5

22 25.5 31

38

44

690V

[A] 4.3 6.6

9

9

12

14

16.5

22 25.5 31

38

44

230V (1)

[kW] 0.75

1.5

2.2

2.2

3

3.7

4

5.5

6.3 7.5

11

11

240V (1)

[kW] 0.75

1.5

2.2

2.2

3

4

4

5.5

7.5

7.5

11

11

Rated Operational Power, 400V (1)

[kW] 1.8

3

4

4

5.5 6.3

7.5

11

13

15

20

22

Pe

415V (1)

[kW] 1.8

3

4

4

5.5 6.3

7.5

11

13

17

20

22

500V (1)

[kW] 2.2

3.7

5.5

5.5

7.5

7.5

10

11

15

20

25

30

690V (1)

[kW] 3

5.5 7.5 7.5

10

11

15

18.5 22

25

32

37

Max. switching frequency

Ops/hour 250 250 220 200 200 200 200 200 120 120 120 120

200V

[Hp] 5

5 7-1/2 7-1/2 10

15

20

25

30

40

50

50

Wye-Delta (60 Hz)

230V

Rated Operational Power 460V

575V

200V

UL/CSA Elevator Duty

230V

Rated

Operational Current

460V

575V

200V

UL/CSA Elevator Duty

230V

Rated Operational Power 460V

[Hp] 5 7-1/2 10

10

15

20

25

[Hp] 10

15

20

25

30

40

50

[Hp] 10

15

20

25

30

40

50

[A] 7.8 11.0 11.0 17.5 25.3 25.3 32.2

[A] 6.8 9.6 15.2 15.2 22.0 28.0 28.0

[A] 7.6 11.0 14.0 21.0 27.0 27.0 34.0

[A] 6.1 9.0 11.0 17.0 22.0 27.0 32.0

[Hp] 2

3

3

5 7-1/2 7-1/2 10

[Hp] 2

3

5

5 7-1/2 10

10

[Hp] 5 7-1/2 10

15

20

20

25

30

40 50 60

60

60

75 100 125 125

60

75 100 125 125

TBD 32.2 48.3 62.1 TBD

TBD 42.0 54.0 68.0 TBD

TBD 40.0 52.0 65.0 TBD

TBD 41.0 52.0 62.0 TBD

TBD 10

15

20 TBD

TBD

15

20

25 TBD

TBD 30 40 50 TBD

575V

[Hp] 5 7-1/2 10

15

20

25

30

TBD 40 50 60 TBD

(1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

39

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 12 - Main Circuits

100/104-C, 100S/104S-C

09

12

16

23 30

37

43

55

60 72 85 97

Coil Type:

Conventional

X

X

X

X

X

X

X

X

X

X

X

X

Electronic -- EI

X

X

X

X

X

X

X

X

--

--

--

--

Star-Delta Starting (50 Hz)

 230V

[A] 21

26

35

46

61

66

76

96

107 125 147 166

 240V

[A] 21

26

35

46

61

66

76

96

107 125

47

165

Rated Operational Current, Ie

400V

[A] 16

21

28

40

52

64

74

95.3 104 125 147 168

415V

[A] 16

21

28

40

52

64

74

95.3 104 125 47 168

500V

[A] 12

17

24

35

43

52

66

76.2 95 116 139 135

690V

[A] 8.6 12

16

21

31

36

43

55.4

59

73

85

99

230V (1)

[kW] 5.5

7.5

10

13

17

20

22

30

32

37

45

50

240V (1)

[kW] 5.5

7.5

10

13 18.5 20

22

30

32 40 50

50

Rated Operational Power, 400V (1)

[kW] 7.5

10

13

20

25

32

40

45

55

63

80

90

Pe

415V (1)

[kW] 7.5

11

15

22

25

32

40

45

55

63

80

90

500V (1)

[kW] 7.5

11

15

22

25

32

45

45

63

80

90

90

690V (1)

[kW] 7.5

10

13 18.5 25

32

40

45

55

63

80

90

Switching of Power Transformers, AC-6a (50 Hz))

Inrush Current

= n

Rated transformer current

 230V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

 240V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

 400V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

n= 30

 415V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

 500V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

 690V

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

230V

[kVA] 4.3 4.3 4.3 4.3

8

8

9.2

9.2

16

16

16 19.3

240V

[kVA] 4.5 4.5 4.5 4.5 8.3 8.3

10

10

17

17

17 20.2

Apparent Power

400V

[kVA] 7.5 7.5 7.5 7.5

14

14

16

16

28

28

28 33.6

415V

[kVA] 7.8 7.8 7.8 7.8

14

14

17

17

29

29

29 34.9

500V

[kVA] 9.4 9.4 9.4 9.4

17

17

20

20

35

35

35

42

690V

[kVA] 13

13

13

13

24 24

27

27

49

49

49

58

n=20

 690V

[A] 16.3 16.3 16.3 16.3 30 30 34.5 34.5 61.3 61.3 61.3 72.8

n=15

 690V

[A] 22

22

22

22

40 40

46

46

82 82

82

97

60 Hz Peak Inrush/peak rated transformer current

n=30

[A] 10.9 10.9 10.9 10.9 20 20

23

23 40.8 40.8 40.8 48.5

200V

[kVA] 3.8 3.8 3.8 3.8 6.9 6.9

8.0

8

14.1 14.4 14.4 16.8

208V

[kVA] 3.9 3.9 3.9 3.9 7.2 7.2

8.3

8.3 14.7 14.7 14.7 17.5

Apparent Power

240V

[kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6

9.6 17.0 17.0 17.0 20.2

480V

[kVA] 9.1

9.1

9.1

9.1 16.6 16.6 19.1

19.1 33.9 33.9 33.9 40.3

600V

[kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 23.9 42.4 42.4 42.4 50.4

660V

[kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 26.3 46.6 46.6 46.6 55.4

60 Hz Peak Inrush/peak rated transformer current

n=20

[A] 16.3 16.3 16.3 16.3 30 30 34.5 34.5 61.3 61.3 61.3 72.8

200V

[kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12.0

12

21.2 21.2 21.2 25.2

208V

[kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4

12.4 22.1 22.1 22.1 26.2

Apparent Power

240V

[kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3

14.3 25.5 25.5 25.5 30.3

480V

[kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 28.7 51.0 51.0 51.0 60.5

600V

[kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 35.9 63.7 63.7 63.7 75.7

660V

[kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 39.4 70.1 70.1 70.1 83.2

(1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1

40

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 13 - Main Circuits

100/104-C, 100S/104S-C

09

12

16

23

30

37

43

55

Coil Type:

Conventional

X

X

X

X

X

X

X

X

Electronic -- EI

X

X

X

X

X

X

X

X

60 Hz Peak Inrush/peak rated transformer current

n=15

[A] 22

22

22

22 40 40

46

46

200V

[kVA] 7.5

7.5

7.5

7.5 13.9 13.9 15.9

15.9

208V

[kVA] 7.8

7.8

7.8

7.8 14.4 14.4 16.6

16.6

Apparent Power

240V

[kVA] 9.0 9.0 9.0 9.0 16.6 16.6 19.1

19.1

480V

[kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 38.2

600V

[kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8

47.8

660V

[kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 52.6

Table 14 - Main Circuits

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60

Coil Type:

Conventional

XXXXXX

X

Electronic -- EI X X X X X X X

X XXX X XX--

Switching of 3-phase Capacitors, AC-6b (50 Hz)(1)

230V [kVAR] 8 8 8.5 9 14 14 --

-- 24 24 28

240V [kVAR] 8 8 8.5 9 14 14 --

-- 25 25 29

Single capacitor 40 °C (104 °F)

400V [kVAR] 8 8 10 12.5 20 24 -- 415V [kVAR] 8 8 10 12.5 20 25 --

-- 35 35 48 -- 35 35 50

500V [kVAR] 8 8 10 12.5 20 25 --

-- 35 35 50

690V [kVAR] 8 8 10 12.5 20 25 --

-- 35 35 50

230V [kVAR] 8 8 8.5 9 12.5 12.5 --

-- 18 18 28

240V [kVAR] 8 8 8.5 9 12.5 12.5 --

-- 18 18 29

Single capacitor 60 °C (140 °F)

400V [kVAR] 8 8 10 12.5 20 21.5 -- 415V [kVAR] 8 8 10 12.5 20 22 --

-- 30 30 42 -- 30 30 42

500V [kVAR] 8 8 10 12.5 20 25 --

-- 30 30 42

690V [kVAR] 8 8 10 12.5 20 25 --

-- 30 30 42

230V [kVAR] 5 5 8 9 12.5 14 --

-- 20 20 28

240V [kVAR] 5 5 8 9 12.5 14 --

-- 20 20 29

Group capacitors 40 °C (104 °F)

400V [kVAR] 5 5 8 10 15 20 -- 415V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40 -- 25 25 40

500V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40

690V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40

230V [kVAR] 5 5 8 9 12.5 12.5 --

-- 18 18 28

240V [kVAR] 5 5 8 9 12.5 12.5 --

-- 18 18 29

Group capacitors 60 °C (140 °F)

400V [kVAR] 5 5 8 10 15 20 -- 415V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40 -- 25 25 40

500V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40

690V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40

200V [kVAR] 5 5 8 9 12.5 14 --

-- 20 20 28

60 Hz Single Capacitor 230V [kVAR] 5 5 8 9 12.5 14 --

-- 40 °C (104 °F)

460V [kVAR] 5 5 8 10 15 20 --

-- 20 20 29 -- 25 25 40

600V [kVAR] 5 5 8 10 15 20 --

-- 25 25 40

60 Hz Group Capacitors -- 40 °C (104 °F)

200V [kVAR] 5 5 8 9 12.5 12.5 -- 230V [kVAR] 5 5 8 9 12.5 12.5 -- 460V [kVAR] 5 5 8 10 15 20 -- 600V [kVAR] 5 5 8 10 15 20 --

-- 18 18 28 -- 18 18 29 -- 25 25 40 -- 25 25 40

(1) Inductance of leads between capacitors in parallel: min. 6 µH (100-C09...C30 contactors: min 30 µH)

60 72 85 97

X

X

X

X

--

--

--

--

82

82

82

97

28.4 28.4 28.4 33.6

29.5 29.5 29.5 34.9

34.1 34.1 34.1 40.3

68.2 68.2 68.2 80.6

85.2 85.2 85.2 100.8

93.7 93.7 93.7 110.9

72 85 90*200 90*400 97

XX X

XX

---- --

----

28 28 -- 29 29 -- 48 48 -- 50 50 -- 55 60 -- 55 60 -- 28 28 -- 29 29 -- 48 48 -- 50 50 -- 50 55 -- 50 55 -- 28 28 -- 29 29 -- 48 48 -- 50 50 -- 50 50 -- 50 50 -- 28 28 -- 29 29 -- 48 48 -- 50 50 -- 50 50 -- 50 50 -- 28 28 -- 29 29 -- 50 50 -- 50 50 -- 28 28 -- 29 29 -- 50 50 -- 50 50 --

-- 28 -- 29 -- 48 -- 50 -- 60 -- 60 -- 28 -- 29 -- 48 -- 50 -- 55 -- 55 -- 28 -- 29 -- 48 -- 50 -- 50 -- 50 -- 28 -- 29 -- 48 -- 50 -- 50 -- 50 -- 28 -- 29 -- 50 -- 50 -- 28 -- 29 -- 50 -- 50

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

41

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 15 - Main Circuits

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97

Coil Type:

Conventional

XXXXXX X

Electronic -- EI X X X X X X X

X XXXXX X X X X------ --

XX ----

Switching of Lamps

Gas discharge lamps AC-5a, 40 °C (104 °F)

open

[A] 22.5 25 28 29 40.5 45 65 65 77 77 81 85 90 115 115 115

enclosed

[A] 22.5 25 28 29 37 41 54 54 57 57 77 81 90 95 95 100

Individually compensated:

Max. capacitance at expected

Short-circuit current of

10 kA [µF] 1000 1000 1000 1000 2700 2700 -- 20 kA [µF] 500 500 500 500 1350 1350 -- 50 kA [µF] 200 200 200 200 540 540 --

-- 3200 3200 4000 4000 4700 -- -- 1600 1600 2000 2000 2350 -- -- 640 640 800 800 940 --

-- 4700 -- 2350 -- 940

Filament AC-5b 230/240V [A] 12 16 18 22 30 37 18 25 43 51 60 70 76 60 75 90

Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)

230V

[A] 32 32 32 32 45 45 --

-- 63 63 -- -- -- --

----

AC-7a

400V

[A] 32 32 32 32 45 45 --

-- 63 63 -- -- -- --

----

440V

[A] 32 32 32 32 45 45 --

-- 63 63 -- -- -- --

----

Switching of Motor Load for Home Appliances (50 Hz)

230V

[A] 10.5 14 19 23 30 -- --

-- ---------- --

----

AC-7b

400V

[A] 9 12 16 20 30 -- --

-- ---------- --

----

440V

[A] 7.5 10 13.5 18 27 -- --

-- ---------- --

----

Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)

400V

[A] 12 16 22 32 38 45 --

-- 63 63 72 85 100 --

-- 115

AC-8a

500V

[A] 12 16 22 32 38 45 --

-- 63 63 72 85 100 --

-- 115

690V

[A] 8 10 14 20 28 35 --

-- 42 42 56 67 80 --

-- 90

- automatic reset of overload release

400V

[A] 5.5 7 9.3 12 13 14 --

-- 16 16 24 30 35 --

-- 35

AC-8b

500V

[A] 5.5 7 9.3 12 13 14 --

-- 16 16 24 30 35 --

-- 35

690V

[A] 5.5 7 9.3 12 13 14 --

-- 16 16 24 30 35 --

-- 35

Switching of DC Loads

Non-inductive or slightly inductive loads or resistance furnaces DC-1, 60 °C (140 °F)

24V

[A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80

48/60V [A] 20 20 20 20 25 25 25 25 30 30 40 40 40 40 40 40

1 pole

110V

[A] 6 6 6 6 8 8 10 10 9 9 11 11 11 11

11 11

220V

[A] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 1.8 1.8 2

440V

[A] 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

24V

[A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80

48/60V [A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80

2 poles in series 110V

[A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80

220V

[A] 8 8 8 10 10 10 10

10 10 10 15 15 15 15

15 15

440V

[A] 1 1 1 1 1 1

1

1

1 1 1.5 1.5 1.5 1.5 1.5 1.5

24V

[A] 25 25 32 32 45 45 -- 45 63 63 90 90 100 -- 100 100

48/60V [A] 25 25 32 32 45 45 -- 45 63 63 90 90 100 -- 100 100

3 poles in series 110V

[A] 25 25 32 32 45 45 -- 45 63 63 90 90 100 -- 100 100

220V

[A] 25 25 32 32 45 45 --

45 50 50 70 80 80 --

80 80

440V

[A] 3 3 3 3 3.5 3.5 -- 3.5 4 4 5 5 5 --

55

42

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 16 - Main Circuits

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97

Coil Type:

Conventional X X X X X X X Electronic -- EI X X X X X X X

X XXXXX X X X X------ --

XX ----

Switching of DC Loads, Continued

Shunt-wound Motors, Starting, reverse current braking, reversing, stepping DC-3, 60 °C (140 °F)

24V

[A] 25 25 32 32 45 45 --

-- 63 63 90 90 100 --

-- 100

48/60V [A] 25 25 32 32 45 45 --

-- 50 50 70 70 80 --

-- 80

3 poles in series 110V

[A] 20 20 25 25 30 30 --

-- 35 35 70 70 80 --

-- 80

220V [A] 6 6 6 10 15 15 --

-- 20 20 25 25 30 --

-- 30

440V [A] 0.6 0.6 0.6 0.6 0.6 0.6 --

-- 0.6 0.6 0.6 0.6 0.6 --

-- 0.6

Series-wound Motors, Starting, reverse current braking, reversing, stepping DC-5, 60 °C (140 °F)

24V

[A] 25 25 32 32 45 45 --

-- 63 63 90 90 100 --

-- 100

48/60V [A] 25 25 32 32 45 45 --

-- 50 50 70 70 80 --

-- 80

3 poles in series 110V

[A] 20 20 25 25 30 30 --

-- 35 35 70 70 80 --

-- 80

220V [A] 6 6 6 10 15 15 --

-- 20 20 25 25 30 --

-- 30

440V [A] 0.6 0.6 0.6 0.6 0.6 0.6 --

-- 0.6 0.6 0.6 0.6 0.6 --

-- 0.6

Short Time

Withstand ICW,

10 s

[A] 170 170 170 215 300 304 304 304 375 375 700 700 700 700 700 840

60 °C (140 °F)

Resistance and Power Dissipation

Main current circuit resistance

[m] 2.7 2.7 2.7 2 2 2

2

1.5 1.5 1 0.9 0.9 0.9 0.8 0.7 0.6

Power dissipation by all circuits at Ie AC-3/400V

[W] 0.66 1.2 2.1 3.2 5.4 8.2 11.3 8.4 8.3 9.1 9.7 14 19.5 11.6 20.2 17

AC control

[W] 3.4 3.9 4.8 6.3 8.5 11.3

8.8

9.5 11.6 12.4 14.2 18.5 24 20.6 29.2 26

Total power dissipation At Ie AC-3/400V

DC control (conv.)

[W] --

--

--

--

--

--

--

DC

control [W] 2.4 2.9 3.8 4.9 7.1 9.9 8

(elect.)

-- -- -- 13.7 18 23.5 16.6 25.2 22

8.7 10.8 11.6 -- -- -- --

----

Lifespan

Mechanical AC control

[Million ops.] 13 13 13 13 13 13 10 10 12 12 6 6 6 6

6

6

Mechanical DC control

[Million ops.] 13 13 13 13 13 13 10 10 13 13 6 6 6 6

6

6

Electrical AC-3 (400 V)

[Million ops.] 1.3 1.3 1.3 1.3 1.3 1.3 --

--

1 0.8 1 1 1

--

--

1

Weight

NonRev.

[kg 0.39 0.39 0.39 0.39 0.48 0.49 0.63 (lbs)] (0.86) (0.86) (0.86) (0.86) (1.06) (1.08) (1.39)

0.63 0.51 0.51 1.45 1.45 1.45 (1.39) (1.12) (1.12) (3.20) (3.20) (3.20)

--

--

1.45 (3.20)

AC

Rev.

[kg 0.85 0.85 0.85 0.85 1.08 1.08 (lbs)] (1.89) (1.89) (1.89) (1.89) (2.39) (2.39)

--

--

1.15 1.15 3.14 3.14 3.14 (2.54) (2.54) (6.92) (6.92) (6.92)

--

--

3.14 (6.92)

NonRev.

[kg 0.6 (lbs)] (1.32)

--

--

--

--

--

--

--

--

--

1.47 1.47 1.47 (3.24) (3.24) (3.24)

--

--

1.47 (3.24)

DC

Rev.

[kg 1.27 (lbs)] (2.81)

--

--

--

--

--

--

--

--

--

3.22 3.22 3.22 (7.1) (7.1) (7.1)

--

--

3.22 (7.1)

Non- [kg DC (Electronic-EQ, Rev. (lbs)]

--

0.40 0.40 0.40 0.40 0.49 (0.88) (0.88) (0.88) (0.88) (1.08)

0.49 (1.08)

0.57 0.57 0.57 0.57 (1.25) (1.25) (1.25) (1.25)

--

--

--

EJ)

Rev.

[kg (lbs)]

--

0.87 0.87 0.87 0.87 1.08 1.08 (1.91) (1.91) (1.91) (1.91) (2.39) (2.39)

--

--

1.27 1.27 (2.79) (2.79)

--

--

--

---- ----

Non- [kg DC (Electronic- EW, Rev. (lbs)]

--

0.43 0.43 0.43 0.43 0.52 (0.95) (0.95) (0.95) (0.95) (1.14)

0.52 (1.14)

0.60 0.60 0.60 0.60 (1.32) (1.32) (1.32) (1.32)

--

--

--

EY, ED, EA)

Rev.

[kg (lbs)]

--

0.93 0.93 0.93 0.93 1.14 1.14 (2.05) (2.05) (2.05) (2.05) (2.51) (2.51)

--

--

1.33 1.33 (2.93) (2.93)

--

--

--

---- ----

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

43

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 17 - Conductors

100/104-C, 100S/104S-C

09 12 16 23 30 37 40 43 55 60 72 85 90 97

Coil Type:

Conventional Electronic -- EI

XXXXXXXXXXXXX X X X X X X X X X X-------- --

(1)

(2)

(3)

Conductor Cross Sections - Main Contacts Terminal type

Recommended torque Cross section per UL/CSA Recommended torque

1 conductor 2 conductors 1 conductor 2 conductors

[mm2] [mm2] [mm2] [mm2] [N·m] [AWG] [lb·in]

Conductor Cross Sections - Coil Terminal type

1...4 1...4 1.5...6 1.5...6 1.5...2.0 16...10 13.3...17.7

2.5...10 2.5...10 2.5...16 2.5...16 2.5...3.5 14...4 22...31

2.5...16 2.5...10 2.5...25 2.5...16 2.5...3.5 14...6 14...4 22...31
(1)

2.5...35 2.5...25 2.5...50 2.5...35 4.5...6 14...1 40...53

1 conductor
2 conductors
1 conductor
2 conductors Recommended torque Cross section per UL/CSA Recommended torque
(1) Pozidriv No. 2 / Blade No. 3 screw (2) Pozidriv No. 2 / Blade No. 4 screw (3) Hexagonal socket screw

[mm2] [mm2] [mm2] [mm2] [N·m] [AWG] [lb·in]

1...2.5 1...2.5 1...4 1...4 1...1.5 16...12 9...13

44

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 18 - Short-Circuit Coordination Data(1)

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97

Coil Type:

Conventional Electronic - EI

XXXXXX X XXXXXX X

X XXXX X X

XX

X XX------ -- -- --

Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 (contactor and fuses only)

50 kA Available Fault Current

Type"1"(690V) DIN Fuses- gG, gL
Type"2"(400V)

[A] 50 50 50 80 125 125 160 [A] 25 35 35 40 80 80 63

160 160 160 250 250 250 250 250 250 80 100 100 160 160 160 160 100 200

Type"2"(690V)

[A] 25 35 35 40 80 80 63 80 100 100 160 160 160 160 100 200

65kA Available Fault Current

BS88Fuses

Type"1"(415V)

[A] 25 32 40 50 63 80 --

-- 80 TBD 100 160 160 --

-- TBD

Type"2"(415V)

[A] 20 25 32 50 63 80

Per UL 508 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only)

UL Class K5 and UL Listed

[A] 35 40 70 90 110 125

RK5 Fuses

Combination (600V)

UL verified UL Class CC and CSA combination to HRCI-MISC Fuses IEC60947-4-1
"Type2"

[A] -- -- -- -- -- -- [A] 20(2) 20 30 40 -- --

--

-- 80 TBD 100 125 160 --

5 kA Available Fault Current

125 125 150 200 200 -- -- --

10 kA Available Fault Current

--

-- -- -- -- 250 300 300

100 kA Available Fault Current

--

-- -------- -- --

-- TBD
---- 300 350 ----

UL Class J and CSA HRCI-J Fuses

UL verified combination to IEC60947-4-1 "Type 2"

100 kA Available Fault Current

[A] 20(2) 20 30 40 50 50 --

-- 70 80 80 100 150 --

-- 175

UL Inverse-time Circuit Breaker

UL Listed

5 kA Available Fault Current

Combination (480V) [A] 30 30 50 50 125 125 --

-- 125 150 250 -- -- --

[A] -- -- -- -- 125 125 --

-- 125 150 250 -- -- --

UL Listed Combination (600V)

[A]

--

--

--

--

--

--

10 kA Available Fault Current

--

-- -- -- -- 250 250 --

18 kA Available Fault Current

[A] -- -- -- -- -- -- --

-- -------- -- --

UL Listed Combination (600Y/347V)

25 kA Available Fault Current

[A] 30(3) 30(3) 30(3) 30(3) 50(4) 50(4) --

-- 50(4) -- 110 110 110 --

UL Listed Combination (600V)

[A]

--

--

--

-- 100(5) 100(5) --

-- 100(5) 125 200(5) 225(5) 225(5) --

---- ---- -- 250 ----
---- -- 225(5)

UL Listed

50 kA Available Fault Current

Combination (480V) [A] -- -- -- -- 50(4) 50(4) --

-- 50(4) -- -- -- -- --

----

UL Listed

65 kA Available Fault Current

Combination (480Y/ 277V)

[A] 30(3) 30(3) 30(3) 30(3)

--

--

--

-- -------- -- --

----

UL Listed Combination (480V)

[A]

--

--

--

-- 100(5) 100(5) --

-- 100(5) 125 200(5) 225(5) 225(5) --

-- 225(5)

(1) See the Rockwell Automation Global SCCR Tool at rok.auto/sccr for complete short-circuit current ratings. (2) 15 A max. fuse for Type 2 coordination. (3) Ratings apply when used with Bulletin 140U-D circuit breakers only. (4) Minimum enclosure size 12-3/8 x 7-5/8 s 7-1/4 inches (5) Minimum enclosure size 20 x 12 x 8 inches with two latches.

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

45

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 19 - Coil Data

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55

Coil Type:

Conventional Electronic - EI

XXX X X X X XXX X X X X

XXX XXX

Operating Limits

50 Hz, 60 Hz, 50/60 Hz

pick-up dropout

[x Us] [x Us]

DC (conventional)

pick-up dropout

[x Us] [x Us]

DC (electronic--EQ, pick-up

[x Us]

EJ, EW, QJ)

dropout

[x Us]

DC (electronic--EY)

pick-up dropout

[x Us] [x Us]

DC (electronic--ED)

pick-up dropout

[x Us] [x Us]

DC (electronic--EA)

pick-up dropout

[x Us] [x Us]

0.85...1.1 0.3...0.6
-- --

0.7...1.25 0.3...0.4 0.8...1.25 0.3...0.4 0.7...1.12(1) 0.3...0.4 0.8...1.1 0.3...0.4

0.85....1.1 0.3...0.6
-- --

Coil Consumption

50 Hz, 60 Hz, 50/60 Hz

pick-up hold-in

[VA] [VA/W]

75 9.5/2.7

105 12.3/3.1

135 13.3/3.3

pick-up

[W]

--

--

--

DC (conventional)

hold-in

[W]

--

--

--

pick-up DC (electronic--EQ, (avg/peak)

[W]

10/17

16/25

EJ, QJ)

hold-in

[W]

1.7

2.5

pick-up DC (electronic--EY, (avg/peak)

[W]

10/17

16/25

EW)

hold-in

[W]

1.9

2.7

pick-up DC (electronic--ED) (avg/peak)

[W]

12/19

16/26

hold-in

[W]

2.1

2.8

pick-up DC (electronic--EA) (avg/peak)

[W]

14/22

18/29

hold-in

[W]

3.0

4.0

Operating Times

closing delay [ms] 15...30 15...30 15...30

15...30

AC

opening delay [ms] 10...60 10...60 10...60

10...60

With RC module closing delay [ms] 10...60 10...60 10...60

10...60

10...60

opening delay [ms]

--

DC (conventional)

closing delay [ms]

--

--

--

--

--

--

50...80

--

7...15

With integrated diode

opening delay [ms]

--

--

--

--

17...23

With external diode opening delay [ms]

--

--

--

--

-- 80...125

closing delay [ms]

20...50

--

DC (electronic--EQ, opening delay [ms]

20...50

--

EJ)

Max. Ripple

±15%

--

min. OFF time [ms]

50

--

closing delay [ms]

20...50

--

DC (electronic--EW, opening delay [ms]

23...33

--

EY, ED, EA)

Max. Ripple

±15%

--

min. OFF time [ms]

50

--

60 72 85 90*200 90*400 97

XXX X

X

X

------ -- -- --

0.85....1.1 0.3...0.6 0.8...1.1 0.1...0.6
-- -- -- -- -- -- -- --

235

400

19.6/5

24/9

200

325

4

5

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

20...40 10...60 10...60 20...40 20...40
 220V 20...35
-- -- -- -- -- -- -- -- --

20...40 20...40 20...40 15...25 20...25 20...25 15...25 20...25 20...25
 220V 20...35
-- -- -- -- -- -- -- -- --

46

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 19 - Coil Data (Continued)

100/104-C, 100S/104S-C

09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97

Coil Type:

Conventional Electronic - EI

XXX X X X X XXX X X X X

X X X XXX X X X X ------ --

XX ----

closing delay [ms]

20...50

--

--

--

opening delay [ms]

16...21

DC (electronic--QJ)

Max. Ripple

±15%

--

--

--

--

--

--

min. OFF time [ms]

50

--

--

--

(1) 0.7...1.25 at 110V DC

Table 20 - Auxiliary Contacts, Auxiliary Contact Blocks, and Pneumatic Timers

Switching of AC Loads AC-12 Ith
AC-15 at rated voltage of
Switching of DC Loads DC-12 L/R < 1 ms resistive loads at
DC-14L/R <15 ms inductive loads with economy resistor in series at
DC-13 switching electromagnets at Fuse gG

at 40 °C (104 °F) at 60 °C (140 °F)
24V 42/48V 120V 230V 240V 400V 415V 500V 690V
24V DC 48V DC 110V DC 220V DC 440V DC 24V DC 48V DC 110V DC 220V DC 440V DC 24V DC 48V DC 110V DC 220V DC 440V DC

Short-circuit protection with no welding of contacts per IEC 60947-5-1

Protective Separation per IEC 60947-1, Annex N

Min. switching capacity according to IEC 60947-5-4

Load Carrying Capacity per UL/CSA

Rated voltage

AC

Continuous rating

40 °C (104 °F)

Switching capacity

AC

Rated voltage

DC

Switching capacity

DC

Internal

Front mounted

Front mounted (Bifurcated)

Side-mounted

[A]

20

[A]

20

[A]

10

[A]

10

[A]

10

[A]

10

[A]

10

[A]

6

[A]

6

[A]

2.5

[A]

1

10

10

10

6

6

6

6

3

6

6

3

6

6

3

6

5.5

3

5.5

5

3

5

3

2

3

3

2

3

1.6

1.2

1.6

1

0.7

1

[A]

12

[A]

9

[A]

3.5

[A]

0.55

[A]

0.2

[A]

9

[A]

5

[A]

2

[A]

0.4

[A]

0.16

[A]

5

[A]

3

[A]

1.2

[A]

0.6

[A]

0.3

12

6

6

9

3.2

3.2

3.5

1

1

0.55

0.5

0.5

0.2

0.2

0.2

9

2

2

5

1.6

1.6

2

0.3

0.3

0.4

0.12

0.12

0.16

0.05

0.05

5

2.5

5

3

1.5

2.5

1.2

0.6

0.68

0.6

0.3

0.32

0.15

0.15

0.15

[A]

20

[A]

20

between load and auxiliary circuit 320V

17V/10mA

10

10

10

10

10

10

between load and auxiliary circuit 440V

17V/5mA

5V/3mA

17V/10mA

[V]

[A]

10

[A]

[V]

[A]

P600

max.600 10 A600 max.600 Q600

10

10

Q600

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

47

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications

Table 21 - General Specifications

Attribute Rated Isolation Voltage Ui IEC UL, CSA Rated Impulse Voltage Withstand Uimp Rated Voltage Ue AC 50/60 Hz DC Insulation Class of the Coil Rated coil frequency Ambient Temperature Storage Operation at rated voltage at 70 °C (158 °F) Climatic Withstand Max. Altitude of Installation Site

[V] [V] [kV] [V] [V]
[ °C ( °F)] [ °C ( °F)]
[m]

Protection Class

Single contactor cover Contactor with frame terminal block Auxiliary contact Protection against Accidental Contact Resistance to Shock Resistance to Vibration Mechanically Linked Contacts IEC60947-5-1,Annex L
Mirror Contacts IEC60947-4 Annex F

Value
690 600 6
115, 200, 230, 240, 400, 415, 460, 500, 575, 690 24, 48, 110, 220, 440
Class F per IEC 60085, UL Class 105 AC 50/60Hz, DC
-55...+80 (-67...176) -40...+60 (-40...140) 15% current reduction against 60 °C (140 °F) values IEC 60068-2-1/-2/-30 2000 NN, per IEC60947-1 100-C09...C23: IP2X from all directions 100-C30...C55: IP2X from front with front (upper) terminal wired 100-C60...C97: IP2X from front with front (upper) terminal wired (min. wire size 16 mm2 or #6 AWG)
-- -- IP2X Finger- and back-of-hand proof per VDE0106, part100 IEC60068-2-27 IEC60068-2-6 100-/100S-C09...C55+100-FA/-FB/-FC, (except L11, L22),100-/100S-C09...C55+ 100-FAB/-FBB/-FCB 100-/100S-C09...C97+100-FA/-FB/-FC, (except L11, L22),100-/100S-C09...C97+ 100-SA/SB, 100-/100S-C09...C97+100-FAB/-FBB/-FCB

Table 22 - Standards Compliance and Certifications

Standards Compliance

Certifications

100-C IEC Contactors

EN/IEC 60947-4-1, 60947-5-1 CE Marked

IEC 60947 Type "2" Coordination CCC

CSA 22.2. No. 14

cULus Listed (File No. E3125; Guide NLDX, NLDX7)

UL 508

Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

100S-C IEC Safety Contactors

EN50205

CE Marked

CSA C22.2 No. 14

SUVA Third-Party Certified

UL 508

cULus Listed (File No. E3125; Guide NLDX, NLDX7)

EN/IEC 60947-4

IEC 60947-4-1 Annex F -- Mirror Contacts

IEC 60947-5-1 Annex L -- Mechanically Linked Contacts

Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

Standards Compliance Certifications

100Q-C Capacitor-switching Contactors

IEC 60947-4

CE Marked

CSA C22.2 No. 14

cULus Listed (File No. E 41850, Guide NLDX, NLDX7)

UL 508

Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

48

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves
Life-Load Curves
Bulletin 100-C/104-C IEC contactors are designed for superior performance in a wide variety of applications. When selecting IEC products, the user must give consideration to the specific load, utilization category, and required electrical life of the application. The life-load curves shown here are based on Rockwell Automation tests according to the requirements defined in IEC 60947-4-1. Since contact life in application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here.
To find the estimated electrical life of the contactor, follow these guidelines: 1. Identify the appropriate utilization category from Table 23. 2. Choose the graph for the utilization category selected. 3. Locate the intersection of the life-load curve for the appropriate contactor with the application's operational current (Ie) found on the horizontal axis. 4. Read the estimated contact life along the vertical axis.

Contact Life for Mixed Utilization Categories AC-3 and AC-4:

In many applications, the utilization category cannot be defined as either purely AC-3 or AC-4. In those applications, the electrical life of the contactor can be estimated from the following equation:

Lmixed = Lac3/[1 + Pac4*(Lac3/Lac4 ­ 1)], where:

Lmixed = Approximate contact life in operations for a mixed AC-3/AC-4 utilization category application

Lac3 = Approximate contact life in operations for a pure AC-3 utilization category (from the AC-3 life-load curves)

Lac4 = Approximate contact life in operations for a pure AC-4 utilization category (from the AC-4 life-load curves)

Pac4 = Percentage of AC-4 operations

Table 23 - Utilization Category Determination

Test Conditions

AC-1

Resistance Furnaces: Non inductive or slightly inductive loads

AC-2

Slip-ring motors: Starting and reversing

AC-3

Squirrel-cage motors: Starting and stopping of running motors

AC-4

Squirrel-cage motors: Starting, plugging(1), inching(2)

AC-15

Solenoids: Contactors, valves and lifting magnets

Ie < 17 A Ie > 17 A
Ie < 17 A Ie > 17 A

Making

I/Ie

U/Ue

cos

Ic/Ie

1

1

0.95

1

2.5

1

0.65

2.5

6

1

0.65

1

6

1

0.35

1

6

1

0.65

6

6

1

0.35

6

10

1

0.7

1

(1) Plugging is understood as stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running. (2) Inching (jogging) is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.

Breaking Ur/Ue 1
1
0.17 0.17 1 1
1

cos
0.95
0.65
0.65 0.35 0.65 0.35
0.4

· Ie Rated operational current · I Making Current

· Ic Breaking Current · U Off-load voltage

· Ue Rated voltage · Ur Recovery voltage

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

49

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves Figure 11 - AC-1, 40 °C (104 °F) Non- or slightly inductive loads, resistance furnaces; Ue = 230...690V
10E+06

C09 C12 C16 C23 C30 C40 C37 C43 C60 C72 C85 C97 / C90

Operating cycles

01E+06
C90

10E+04 1

10

100

Rated operating current I AC-1 [A] e

Figure 12 - AC-2, Switching of slip-ring motors; Ue = 230...400...460V

10E+06

C16

C23 C30 C37 C43

C12

C60 C72 C85 C97

C09

01E+06

1000

Operating cycles

10E+04 1
50

10

100

Rated operating current Ie AC-2 [A]

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves

Figure 13 - AC-3, Switching of squirrel-cage motors while starting; Ue = 230...400...460V

C09

C12

C16

10E+06

C23

C30 C37

C43

C60 C72 C85 C97

01E+06

Operating cycles

10E+04 1

10

100

Rated operating current Ie AC-3 [A]

Figure 14 - AC-3, Switching of squirrel-cage motors while starting; Ue = 500...575V

10E+06 C09

C12

C16

C23

C30 C37 C43

C60 C72 C85 C97

01E+06

Operating cycles

10E+04 1

10 Rated operating current Ie AC-3 [A]

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100
51

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves

Figure 15 - AC-3, Switching of squirrel-cage motors while starting; Ue = 690V

C09

C12

C16

10E+06

C23

C30 C37 C43

C60 C72 C85 C97

01E+06

Operating cycles

Operating cycles
C09 C12 C16 C23 C30 C37 C43 C60 C72 C85

10E+04

1

10

Rated operational current Ie AC-3 [A]

Figure 16 - AC-4, Switching of squirrel-cage motors; Ue = 230...690V
10E+06

01E+06

10E+04

01E+04 1
52

10 Rated operating current Ie AC-4 [A]
Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100
C97
100

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves

Figure 17 - AC-3 & AC-4, 10% AC-4 Mixed operation of squirrel-cage motors; Ue = 230...400...460V

C12
10E+06

C16

C23 C30 C37 C43

C09

C60 C72 C85 C97

01E+06

Operating cycles

10E+04

1

10

Rated operating current Ie AC-3 / AC-4 [A]
Figure 18 - Heavy Duty Starting and Regular Short-time Operation

100

max. Starting time / Loading time [s] C09/12/16 C23 C30/37 C43 C60/72/85 C97

10

1

10

100

1000

Starting current / Short time current [A]

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100
10000
53

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves
Maximum Operating Rates
Figure 19 - AC-1, 40 °C (104 °F) Non- or slightly inductive loads, resistance furnaces; Ue = 230...690V
30E+02

25E+02

Permissible switching rate [ops/hr]

20E+02

15E+02

10E+02

C09/C12/C16/C23

05E+02

C60/C72/C85
C30/C37 C40/43 C90/C97

00E+00 0

10

20

30

40

50

60

70

80

90

100

P/Pn [%]

Figure 20 - AC-2, Stepping of slip-ring motors; Ue = 230...460V
01E+04

Permissible switching rate [ops/hr]

10E+02

C09/C12/C16 C23/C30/C37/C43 C60/C72
C85/C97

01E+02 0

10

20

30

40

50

60

70

80

90

100

P/Pn [%]

54

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves
Figure 21 - AC-3, Switching of squirrel-cage motors while starting; Ue = 230...460V; Relative operating time 40%, Starting time tA = 0.25 s
01E+04

Permissible switching rate [ops/hr]

10E+02

C09/C12/C16
C23/C30/C37/C43 C60/C72/C85/C97

01E+02 0

10

20

30

40

50

60

70

80

90

100

P/Pn [%]

Figure 22 - AC-4, Inching of squirrel-cage motors; Ue = 230...460V, Starting time tA = 0.25 s
10E+02

Permissible switching rate [ops/hr]

01E+02

C09
C12 C16
C23/C30 C37/C43/C60 C72 C85/C97

10E+00 0

10

20

30

40

50

60

70

80

90

100

P/Pn [%]

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

55

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Bulletin 100-C/104-C, 100S-C/104S-C Approximate Dimensions
Figure 23 - Bulletin 100-C/100S-C Contactors and Accessories
c2
c1 c
Figure 24 - Mounting Position -- 100-C Contactors; 100S-C AC Contactors and DC Contactors with Electronic Coils
Figure 25 - Mounting Position -- 100S-C DC Contactors with Conventional Coils

56

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions

Table 24 - AC Contactors and DC Contactors with 12V or 24V Electronic Coils

Cat. No. 100-C09...100-C23 100-C30, 100-C37 100-C40 100-C43, 100-C55 100-C60...100-C97 100-C90 100S-C09...100S-C23 100S-C30, 100S-C37 100S-C43, 100S-C55 100S-C60...100S-C97

a 45 (1-25/32) 45 (1-25/32) 59 (2-21/64) 54 (2-1/8) 72 (2-53/64) 95 (3-47/64) 45 (1-25/32) 45 (1-25/32) 54 (2-1/8) 72 (2-53/64)

b 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 122 (4-51/64) 122 (4-51/64) 81 (3-3/16) 81 (3-3/16) 81 (3-3/16) 122 (4-51/64)

c 80.5 (3-11/64)
97.5 (4) 100.5 (3-61/64) 100.5 (3-61/64) 117 (4-39/64) 117 (4-39/64) 119.5 (4-3/4) 136.5 (5-37/64) 139.5 (5-11/16) 156 (6-11/32)

c1 75.5 (2-31/32) 92.5 (3-41/64) 95.5 (3-49/64) 95.5 (3-49/64) 111.5 (4-25/64) 111.5 (4-25/64) 114.5 (4-43/64) 131.6 (5-11/32) 134.6 (5-29/64) 150.5 (6-1/8)

c2 6 (15/64) 6.5 (1/4) 6.5 (1/4) 6.5 (1/4) 8.5 (21/64) 8.5 (21/64) 6 (15/64) 6.5 (1/4) 6.5 (1/4) 8.5 (21/64)

Ød 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 4 - 5.4 (4 - 7/32) 4 - 5.4 (4 - 7/32) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 4 - 5.4 (4 - 7/32)

d1 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 100 (3-15/16) 100 (3-15/16) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 100 (3-15/16)

d2 35 (1-3/8) 35 (1-3/8) 45 (1-25/32) 45 (1-25/32) 55 (2-11/64) 55 (2-11/64) 35 (1-3/8) 35 (1-3/8) 45 (1-25/32) 55 (2-11/64)

Table 25 - DC Contactors with Conventional Coils

Cat. No. 100-C60D...100-C97D 100-C90D 100S-C60D...100S-C97D

a 72 (2-53/64) 95 (3-47/64) 72 (2-53/64)

b 122 (4-51/64) 81 (3-3/16) 122 (4-51/64)

c 117 (4-39/64) 117 (4-39/64) 156 (6-11/32)

c1 111.5 (4-25/64) 111.5 (4-25/64) 150.5 (6-1/8)

c2 8.5 (21/64) 8.5 (21/64) 8.5 (21/64)

Ød 4 - 5.4 (4 -7/32) 4 - 5.4 (4 - 7/32) 4 - 5.4 (4 - 7/32)

d1 100 (3-15/16) 100 (3-15/16) 100 (3-15/16)

d2 55 (2-11/64) 55 (2-11/64) 55 (2-11/64)

Table 26 - DC Contactors with 36...48V, 48...72V, 110...125V, or 200...250V DC Electronic Coils

Cat. No. 100-C09E...100-C23E 100-C30E...100-C37E 100-C40E 100-C43E...100-C55E 100S-C09E...100S-C23E 100S-C30E...100S-C37E 100S-C43E...100S-C55E

a 45 (1-25/32) 45 (1-25/32) 59 (2-21/64) 54 (2-1/8) 45 (1-25/32) 45 (1-25/32) 54 (2-1/8)

b 105 (4-1/8) 105 (4-1/8) 105 (4-1/8) 105 (4-1/8) 105 (4-1/8) 105 (4-1/8) 105 (4-1/8)

c 80.5 (3-11/64)
97.5 (4) 100.5 (3-61/64) 100.5 (3-61/64) 119.5 (4-3/4) 136.5 (5-37/64) 139.5 (5-11/16)

c1 75.5 (2-31/32) 92.5 (3-41/64) 95.5 (3-49/64) 95.5 (3-49/64) 114.5 (4-43/64) 131.6 (5-11/32) 134.6 (5-29/64)

c2 6 (15/64) 6.5 (1/4) 6.5 (1/4) 6.5 (1/4) 6 (15/64) 6.5 (1/4) 6.5 (1/4)

Ød 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16)

d1 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64) 60 (2-23/64)

d2 35 (1-3/8) 35 (1-3/8) 45 (1-25/32) 45 (1-25/32) 35 (1-3/8) 35 (1-3/8) 45 (1-25/32)

Table 27 - 100-C/104-C Accessories
Auxiliary contact block for front mounting Auxiliary contact block for side mounting Pneumatic Timing Module Electronic Timing Module Mechanical Interlock Mechanical Latch Interface Module Surge Suppressor
Labeling with...
Terminal Lug Kit
Paralleling Links
Auxiliary contact block for side mounting Electronic Timing Module

Contactors with

2- or 4-pole 1- or 2-pole

on coil terminal side on side of contactor

on coil terminal side on coil terminal side
label sheet marking tag sheet with clear cover marking tag adapter for System Bul. 1492W
100-C09...C23 100-C30...C37 100-C43...C55 100-C60...C97
100-C09...C23
100-C30...C37 1- or 2-pole on coil terminal side

mm c/c1 + 39
a + 9 c/c1 + 58 b + 24
a + 9 c/c1 + 61
b + 9 b + 3 + 0 + 0 + 5.5 b + 53 b + 44 b + 52 b + 99 b + 78 c + 9/5 b + 85 a + 9 b + 24

(inches) (c/c1 + 1-37/64)
(a + 23/64) (c/c1 + 2-23/64)
(b + 15/16) (a + 23/64) (c/c1 + 2-31/64) (b + 23/64) (b + 1/8)
(+ 0) (+ 0) (+ 7/32) (b + 2-3/32) (b + 1-47/64) (b+ 2-3/64) (b + 3-7/8) (b + 3-1/16) (c + 3/8) (b + 3-11/32) (a + 23/64) (b + 15/16)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

57

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions

Table 27 - 100-C/104-C Accessories (Continued)

Mechanical Interlock Interface Module Surge Suppressor
Labeling with

Contactors with on side of contactor on coil terminal side on coil terminal side label sheet
marking tag sheet with clear cover marking tag adapter for System Bul. 1492W

Bulletin 100Q-C Approximate Dimensions
Figure 26 - Bulletin 100Q- Contactors

mm a + 9 b + 9 b + 3 + 0 + 0 + 5.5
c2

(inches) (a + 23/64) (b + 23/64) (b + 1/8)
(+ 0) (+ 0) (+ 7/32)

c1 c

Table 28 - AC Contactors and DC Contactors with 12V or 24V Electronic Coils

Cat. No. 100Q-C16 100Q-C37

a 45 (1-25/32) 45 (1-25/32)

b 81 (3-3/16) 81 (3-3/16)

c 119.5 (4-3/4) 136.5 (5-37/64)

c1 114.5 (4-43/64) 131.6 (5-11/32)

c2 6 (15/64) 6.5 (1/4)

Ød 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16)

d1 60 (2-23/64) 60 (2-23/64)

d2 35 (1-3/8) 35 (1-3/8)

Table 29 - DC Contactors with Conventional Coils

Cat. No. 100Q-C16 100Q-C37

a 45 (1-25/32) 45 (1-25/32)

b 81 (3-3/16) 81 (3-3/16)

c 145.5 (5-49/64) 180.5 (7-5/32)

c1 140.5 (5-37/64) 175.5 (6-61/64)

c2 6 (15/64) 6.5 (1/4)

Ød 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16)

d1 60 (2-23/64) 60 (2-23/64)

d2 35 (1-3/8) 35 (1-3/8)

Table 30 - DC Contactors with 36...48V, 48...72V, 110...125V, or 200...250V DC Electronic Coils

Cat. No. 100Q-C16EA, -ED, or -EY 100Q-C37EA, -ED, or -EY

a 45 (1-25/32) 45 (1-25/32)

b 105 (4-1/8) 105 (4-1/8)

c 119.5 (4-3/4) 136.5 (5-37/64)

c1 114.5 (4-43/64) 131.6 (5-11/32)

c2 6 (15/64) 6.5 (1/4)

Ød 2 - 4.5 (2 -3/16) 2 - 4.5 (2 -3/16)

d1 60 (2-23/64) 60 (2-23/64)

d2 35 (1-3/8) 35 (1-3/8)

58

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors

Product Selection--100-E/104-E Contactors

· 4...560 kW @ 400V · 5...900 Hp @ 460V · AC-1 ratings up to 2650 A · Compact dimensions · Electronic coils
- AC/DC - Wide voltage range - Low power pick-up and hold-in - Optional PLC interface

· Direct-on-line or reversing · 3 Main contacts · Complete range of accessories · Environmentally friendly

100-E09 Contactor 100-E116 Contactor

100-E860 Contactor

The Bulletin 100-E/104-E contactor family, along with a wide range of accessories, provides the most compact and flexible contactor system available.

3-Pole AC- and DC-operated Direct-on-line Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

Auxiliary Contacts

60 °C

40 °C

kW (50 Hz)

Hp (60 Hz)

AC-3 (400V) AC-1 (690V) 220-240V 380-400V 415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C.

9

25

2.2

4

4

4

5.5 5.5 --

2

2

5

7.5

1

0

0

1

1

0

12

28

3

5.5

5.5 5.5 7.5 7.5 --

3

3

7.5

10

0

1

1

0

16

30

4

7.5

9

9

9

9

--

5

5

10 15

0

1

26

45

6.5

11

11

15

15

15

--

7.5 7.5 15 20

0

0

32

50

9

15

15 18.5 18.5 18.5 -- 10 10 20 25

0

0

38

50

11

18.5

18.5 22

22

22

--

10

10

25 30

0

0

40

70

11

18.5

22

22

22

22

--

10

15

30 40

0

0

52

100

15

22

30 30 30 30

--

15

20 40 50

0

0

65

105

18.5

30

37

37

37

37

--

20 25 50 60

0

0

80

125

22

37

45 45 45 45 35 25 30 60 75

0

0

96

130

25

45

55 55 55 55 40 30 30 60 75

0

0

116

160

37

55

55 75 75 63 55 30 40 75 100

1

1

146

225

45

75

75 90 90 90 75 40 50 100 125

1

1

190

275

55

90

90 110 110 132 110 50 60 125 150

1

1

205

350

55

110

110 132 132 160 132 60 75 150 200

1

1

265

400

75

132

132 160 160 200 160 75 100 200 250

1

1

305

500

90

160

160 160 200 250 185 100 125 250 300

1

1

370

600

110

200

200 200 250 315 200 125 150 300 350

1

1

400

600

110

200

220 220 250 315 220 125 150 350 400

1

1

460

700

132

250

250 250 315 355 280 150 200 400 500

1

1

580

800

160

315

355 355 400 500 355 200 250 500 600

1

1

750

1050

220

400

425 450 530 600 400 250 300 600 700

1

1

860

1350

250

475

500 560 630 800 555 -- 400 800 1000

1

1

1060

1650

315

560

630 710 710 1000 600 -- 450 900 1150

1

1

--

1260

--

--

--

--

--

--

--

--

--

--

--

1

1

--

2050

--

--

--

--

--

--

--

--

--

--

--

1

1

--

2650

--

--

--

--

--

--

--

--

--

--

--

1

1

(1) To order with built-in terminal lugs, add the letter "L" to the end of the catalog number (example: 100-E11611L)

 Coil voltage code and terminal position--see page 61

Cat No.
100-E0910 100-E0901 100-E1210 100-E1201 100-E1610 100-E1601 100-E2600 100-E3000 100-E3800 100-E4000 100-E5200 100-E6500 100-E8000 100-E9600 100-E11611 (1) 100-E14611 (1) 100-E19011 100-E20511 100-E26511 100-E30511 100-E37011 100-E40011 100-E46011 100-E58011 100-E75011 100-E86011 100-E106011 100-E126011 100-E205011 100-E265011

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

59

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100-E/104-E Contactors

4-Pole AC- and DC-operated Direct-on-line Contactors

Rated Current at 40 °C [A]

Main Poles

Ie

UL General Use (enclosed)

AC-1 (690V)

600V

N.O.

N.C.

4

0

25

25

2

2

4

0

30

30

2

2

4

0

45

45

2

2

4

0

55

55

2

2

4

0

70

60

2

2

100

80

4

0

4

0

125

105

2

2

 Coil voltage code and terminal position--see page 61

Auxiliary Contacts

N.O.

N.C.

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

3-Pole AC- and DC-operated Reversing Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

60 °C

40 °C

kW (50 Hz)

Hp (60 Hz)

Cat No.
100-E09400 100-E09200 100-E16400 100-E16200 100-E26400 100-E26200 100-E38400 100-E38200 100-E40400 100-E40200 100-E52400 100-E80400 100-E80200

Auxiliary Contacts

Cat No.

AC-3 (400V) AC-1 (690V) 220-240V 380-400V 415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C.

0

1

104-E0902

9

25

2.2

4

4

4 5.5 5.5 --

2

2

5

7.5

1

1(1)

104-E0922(2)

0

1

104-E1202

12

28

3

5.5

5.5 5.5 7.5 7.5 --

3

3

7.5

10

1

1(1)

104-E1222(2)

0

1

104-E1602

16

30

4

7.5

9

9

9

9

--

5

5

10

15

1

1(1)

104-E1622(2)

26

45

6.5

11

11

15

15

15

--

7.5 7.5 15

20

0

1(1)

104-E2602(2)

1

1

104-E2622

32

50

9

15

15 18.5 18.5 18.5 --

10

10

20

25

0

1(1)

104-E3002(2)

1

1

104-E3022

38

50

11

18.5

18.5 18.5 22 22

--

10

10

25 30

0

1(1)

104-E3802(2)

1

1

104-E3822

40

70

11

18.5

22 22

22

22

--

10

15

30 40

1

1

104-E4022

52

100

15

22

30 30 30 30

--

15

20 40 50

1

1

104-E5222

65

105

18.5

30

37

37

37

37

--

20

25 50 60

1

1

104-E6522

80

125

22

37

45 45 45 45 35 25 30 60 75

1

1

104-E8022

96

130

25

45

55 55 55 55 40 30 30 60 75

1

1

104-E9622

116

160

55

55

55 75

75 63 55 30 40 75 100

1

1

104-E11622(3)

146

225

75

75

75 90 90 90 75 40 50 100 125

1

1

104-E14622(3)

190

275

90

90

90 110 110 132 110 50 60 125 150

1

1

104-E19022

205

350

110

110

110 132 132 160 132 60

75 150 200

1

1

104-E20522

265

400

132

132

132 160 160 200 160 75 100 200 250

1

1

104-E26522

305

500

160

160

160 160 200 250 185 100 125 250 300

1

1

104-E30522

370

600

200

200

200 200 250 315 200 125 150 300 350

1

1

104-E37022

400

600

200

200

220 220 250 315 220 125 150 350 400

1

1

104-E40022

460

700

250

250

250 250 315 355 280 150 200 400 500

1

1

104-E46022

580

800

315

315

355 355 400 500 355 200 250 500 600

1

1

104-E58022

750

1050

400

400

425 450 530 600 400 250 300 600 700

1

1

104-E75022

(1) The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.
(2) For AC control voltages only. (3) To order with built-in terminal lugs, add the letter "L" to the end of the catalog number (Example: 104-E11622L)

 Coil voltage code and terminal position--see page 61

60

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100-E/104-E Contactors

Coil Voltage Codes
For 3-Pole Contactors

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 100-E116KJ11

Electronic Coils

V(1)

12-20V DC

100-E09...100-E370

Standard AC/DC

--

100-E09...100-E38

Low Consumption AC/DC EQ

100-E09...100-E38

Low Consumption/ Faster Drop-out DC

--

100-E116...100-E370(2) 100-E400...100-E750, 100-E1260

--

Standard AC/DC with PLC Input

--

100-E860...100-1060, 100-E2050...100-E2650

--

(1) AC voltages are at 50/60 Hz (2) When ordering coil with PLC input, the PLC input must be used (3) 24V...60V DC only

For 3-Pole Reversing Contactors

24V DC -- -- QJ
-- -- --

24-60V AC, 20-60V DC

48-130V AC/DC 100-250V AC/DC 250-500V AC/DC

KJ

KY

KD

KN

EJ

--

--

--

--

--

--

--

--

--

ED

EN

EJ (3)

EY

ED

EN

--

--

ED

--

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 104-E116KJ11

Electronic Coils

V(1)

12-20V DC

104-E09...104-E370

Standard AC/DC

--

104-E09...104-E38

Low Consumption AC/DC EQ

104-E09...104-E38

Low Consumption/ Faster Drop-out DC

--

104-E116...104-E370(2) 100-E400...104-E750, 104-E1260

--

Standard AC/DC with PLC Input

--

104-E860...104-1060, 104-E2050...104-E2650

--

(1) AC voltages are at 50/60 Hz (2) When ordering coil with PLC input, the PLC input must be used (3) 24V...60V DC only

PLC Interface

24V 0V
ON OFF

Supply voltage A1 A2
X5 Contactor 1 ON 2 OFF_N
3 COMMON

24V DC -- -- QJ
-- -- --

24-60V AC, 20-60V DC

48-130V AC/DC 100-250V AC/DC 250-500V AC/DC

KJ

KY

KD

KN

EJ

--

--

--

--

--

--

--

--

--

ED

EN

EJ (3)

EY

ED

EN

--

--

ED

--

For 4-Pole Contactors

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 100-E09KD400.

Electronic Coils

V(1)

100-E09...100-E80 100-E09...100-E38 100-E09...100-E38

Standard AC/DC Low Consumption AC/DC Low Consumption/Faster Drop-out DC

(1) AC voltages are at 50/60 Hz

12-20V DC
-- EQ --

24V DC
-- -- QJ

24-60V AC, 20-60V DC
KJ
EJ
--

48-130V AC/DC 100-250V AC/DC 250-500V AC/DC

KY

KD

KN

--

--

--

--

--

--

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

61

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100S-E Safety Contactors
Product Selection--100S-E Safety Contactors

· Electronic Coils · 3 Main Contacts · Direct-on-line · Low-power auxiliary contacts for feedback circuit · Mirror contact performance

3-Pole AC- and DC-operated Safety Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

60 °C 40 °C

kW (50 Hz)

100S-E09 Contactor

100S-E80 Contactor

Hp (60 Hz)

Auxiliary contacts per contactor

Direct-on-line Contactor

AC-3 AC-1 (400V) (690V)

220240V

380400V

415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C. N.C.(1)

Cat No.

0 0 5 100S-E0905C

9

25

2.2

4

4

4

5.5 5.5

--

2

2

5

7.5

2 1

0 0

3 100S-E0923C 4 100S-E0914C

3 0 2 100S-E0932C

0 0 5 100S-E1205C

2 0 3 100S-E1223C

12

28

3

5.5

5.5 5.5 7.5 7.5

--

3

3

7.5

10

1

0

4 100S-E1214C

3 0 2 100S-E1232C

0 0 5 100S-E1605C

16

30

4

7.5

9

9

9

9

--

5

5

10

15

2 1

0 0

3 100S-E1623C 4 100S-E1614C

3 0 2 100S-E1632C

0 0 4 100S-E2604C

26

45

6.5

11

11

15

15

15

--

7.5 7.5

15

20

1 2

0 0

3 100S-E2613C 2 100S-E2622C

3 0 1 100S-E2631C

0 0 4 100S-E3004C

1 0 3 100S-E3013C

32

50

9

15

15 18.5 18.5 18.5 --

10 10 20 25 2 0 2 100S-E3022C

3 0 1 100S-E3031C

0 0 4 100S-E3804C

38

50

11

18.5 18.5 22

22 22

--

10

10

25

30

1 2

0 0

3 100S-E3813C 2 100S-E3822C

3 0 1 100S-E3831C

0 0 4 100S-E4004C

40

70

11

18.5

22

22

22 22

--

10

15

30 40

1 2

0 0

3 100S-E4013C 2 100S-E4022C

3 0 1 100S-E4031C

0 0 4 100S-E5204C

1 0 3 100S-E5213C

52

100

15

22

30 30 30 30

--

15 20 40 50 2 0 2 100S-E5222C

3 0 1 100S-E5231C

(1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance.

62

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100S-E Safety Contactors

3-Pole AC- and DC-operated Safety Contactors (Continued)

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

60 °C 40 °C

kW (50 Hz)

Hp (60 Hz)

Auxiliary contacts per contactor

Direct-on-line Contactor

AC-3 AC-1 (400V) (690V)

220240V

380400V

415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C. N.C.(1)

Cat No.

0 0 4 100S-E5204C

52

100

15

22

30 30 30 30

--

15

20

40

50

1 2

0 0

3 100S-E5213C 2 100S-E5222C

3 0 1 100S-E5231C

0 0 4 100S-E6504C

1 0 3 100S-E6513C

65

105

18.5

30

37

37

37

37

--

20 25 50 60 2 0 2 100S-E6522C

3 0 1 100S-E6531C

0 0 4 100S-E8004C

80

125

22

37

45

45

45

45

35

25 30 60 75

1 2

0 0

3 100S-E8013C 2 100S-E8022C

3 0 1 100S-E8031C

0 0 4 100S-E9604C

96

130

25

45

55

55

55

55

40

30 30 60

75

1 2

0 0

3 100S-E9613C 2 100S-E9622C

3 0 1 100S-E9631C

116

160

37

55

55 75 75 55 55 30 40 75 100 1 1 1 100S-E11612C (2)

146

225

45

75

75 90 90 90 75 40 50 100 125 1 1 1 100S-E14612C (2)

190

275

55

90

90 110 90 132 110 50 60 125 150 1 1 1 100S-E19012C

205

350

55

110 110 132 110 160 132 60 75 150 200 1 1 1 100S-E20512C

265

400

75

132 132 160 160 200 132 75 100 200 250 1 1 1 100S-E26512C

305

500

90

160 160 160 200 250 132 100 125 250 300 1 1 1 100S-E30512C

370

600

110

200 200 200 220 315 132 125 150 300 350 1 1 1 100S-E37012C

400

600

110

200 220 220 250 315 220 125 150 350 400 1 1 1 100S-E40012C

460

700

132

250 250 250 315 355 280 150 200 400 500 1 1 1 100S-E46012C

580

800

160

315 355 355 400 500 355 200 250 500 600 1 1 1 100S-E58012C

750

1050

220

400 425 450 530 600 400 250 300 600 700 1 1 1 100S-E75012C

(1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance. (2) To order with built-in terminal lugs, add the letter "L" to the end of the catalog number (example: 100S-E11612CL)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

63

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100S-E Safety Contactors

4-Pole AC- and DC-operated Safety Contactors

Rated Operational Current Ie [A] 40 °C

Main Poles per contactor Auxiliary contacts per contactor

AC-1

UL General Use (Enclosed)

690V

600V

N.O.

N.C.

N.O.

0

25

25

4

0

1

2

3

0

30

30

4

0

1 2

3

0

1

45

45

4

0

2

3

70

60

4

0

2

100

80

4

0

2

125

105

4

0

2

(1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance.

N.C.(1) 4 3 2 1 4 3 2 1 4 3 2 1 2 2 2

Direct-on-line Contactor
Cat No. 100S-E09404C 100S-E09413C 100S-E09422C 100S-E09431C 100S-E16404C 100S-E16413C 100S-E16422C 100S-E16431C 100S-E26404C 100S-E26413C 100S-E26422C 100S-E26431C 100S-E40422C 100S-E52422C 100S-E80422C

3-Pole AC- and DC-operated Reversing Safety Contactors

Rated Operational Current Ie [A]

Ratings for switching AC motors - AC-2, AC-3

60 °C 40 °C

kW (50 Hz)

Hp (60 Hz)

Auxiliary contacts per contactor

Direct-on-line Contactor

AC-3 AC-1 (400V) (690V)

220240V

380400V

415V 440V 500V 690V 1000V 200V 230V 460V 575V

N.O.

9

25

2.2

4

4

4 5.5 5.5 -- 2 2 5 7.5

1

12

28

3

5.5 5.5 5.5 7.5 7.5 -- 3 3 7.5 10

1

16

30

4

7.5

9

9

9

9

-- 5 5 10 15

1

26

45

6.5

11

11

15

15

15

-- 7.5 7.5 15 20

3

32

50

9

15

15 18.5 18.5 18.5 -- 10 10 20 25

3

38

50

11

18.5 18.5 18.5 22 22

--

10 10 25 30

3

3

40

70

11

18.5 22 22 22 22 -- 10 15 30 40

1

3

52

100

15

22

30 30 30 30

--

15 20 40 50

1

3

65

105

18.5

30

37 37 37 37 -- 20 25 50 60

1

3

80

125

22

37

45 45 45 45 35 25 30 60 75

1

3

96

130

25

45

55 55 55 55 40 30 30 60 75

1

(1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance.

N.C.(1)
4 4 4 3 3 3 3 5 3 5 3 5 3 5 3 5

Cat No.
104S-E0928C 104S-E1228C 104S-E1628C 104S-E2666C 104S-E3066C 104S-E3866C 104S-E4066C 104S-E40210C 104S-E5266C 104S-E52210C 104S-E6566C 104S-E65210C 104S-E8066C 104S-E80210C 104S-E9666C 104S-E96210C

64

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection--100S-E Safety Contactors

Coil Voltage Codes
For 3-Pole Safety Contactors

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 100S-E09EJ14C

Electronic Coils

V(1)

12-20V DC

24V DC

24-60V AC, 20-60V DC

100S-E09...100S-E370

Standard AC/DC

--

--

KJ

100S-E09...100S-E38 Low Consumption AC/DC EQ

--

EJ

100S-E09...100S-E38

Low Consumption/ Faster Drop-out DC

--

QJ

--

100S-E116...100S-E370(2)

--

--

--

100S-E400...100S-E750, 100S-E1260

Standard AC/DC with 24V DC PLC Interface

--

100S-E860...100S-E1060, 100S-E2050...100S-E2650

--

--

EJ (3)

--

--

(1) AC voltages are at 50/60 Hz (2) When ordering coil with PLC input, the PLC input must be used (3) 24V...60V DC only

48-130V AC/DC
KY -- --
--
EY
--

100-250V 250-500V AC/DC AC/DC

KD

KN

PLC Interface

--

--

--

--

24V 0V

Supply voltage A1 A2

ED

EN

ED

EN

ON OFF

X5 Contactor
1 ON 2 OFF_N

ED

--

3 COMMON

For 3-Pole Reversing Safety Contactors

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 104S-E09KD28C

Electronic Coils 104S-E09...104S-E96 104S-E09...104S-E38

V(1) Standard AC/DC Low Consumption AC/DC

(1) AC voltages are at 50/60 Hz

For 4-Pole Safety Contactors

12-20V DC -- EQ

24V DC -- --

24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC

KJ

KY

KD

KN

EJ

--

--

--

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 100S-E09KD422C

Electronic Coils 100S-E09...100S-E96 100S-E09...100S-E38
100S-E09...100S-E38

V(1)
Standard AC/DC
Low Consumption AC/DC
Low Consumption/ Faster Drop-out DC

(1) AC voltages are at 50/60 Hz

12-20V DC -- EQ
--

24V DC -- --
QJ

24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC

KJ

KY

KD

KN

EJ

--

--

--

--

--

--

--

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

65

100-E/104-E, 100S-E/104S-E Contactors Accessories
Accessories

Auxiliary Contact Blocks with Standard Auxiliary Contacts

Description
Auxiliary Contact Blocks for Front Mounting · 1-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V, 3mA · Mirror contact performance to the main contactor poles · L= Late break N.C./early make N.O.

Connection Diagrams

N.O. N.C.

10

-3

-1

NO

NC

01

-4

-2

1L 0

-7

-5

NO

NC

0 1L

-8

-6

For Use With 100-E09...100-E96 100-E09...100-E96

Cat. No.
100-EFA10 100-EFA01 100-EFAL10 100-EFAL01

Auxiliary Contact Blocks for Front Mounting · 4-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V 3mA · Mirror contact performance to the main contactor poles
Auxiliary Contact Blocks for Front Mounting · 4-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V 3mA · Mirror contact performance to the main contactor poles

21

31

43

53

2

2

NC

NC

NO NO

100-EFC22

22

32

44

54

21

33

43

53

3

1

NC

NO

NO NO

100-EFC31

22

34

44

54

100-E0910...100-E1610

21

31

43

53

1

3

NC

NC

NC NO

100-EFC13

22

32

44

54

21

31

41

51

0

4

NC

NC

NC

NC

22

32

42

52

13

21

31

43

2

2

NO

NC

NC NO

14

22

32

44

100-EFC04 100-EFB22

13

21

33

43

3

1

NO

NC

NO

NO

100-EFB31

14

22

13

23

100-E2600...100-E9600 34 44 100-E09400...100-E80400 33 43 100-E09200...100-E80200

4

0

NO NO

NO

NO

100-EFB40

14

24

34

44

11

21

31

41

0

4

NC

NC

NC

NC

100-EFB04

12

22

32

42

53

61

71

83

2

2

NO

NC

NC NO

54

62

72

84

53

61

73

83

3

1

NO

NC

NO

NO

54

62

74

84

100-EFA22 100-EFA31

53

63

73

83

4

0

NO NO

NO

NO

54

64

74

84

100-E09...100-E96

100-EFA40

53

61

71

81

1

3 NO

NC

NC

NC

100-EFA13

54

62

72

82

51

61

71

81

0

4

NC

NC

NC

NC

52

62

72

82

100-EFA04

66

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Auxiliary Contact Blocks with Standard Auxiliary Contacts (Continued)

100-E/104-E, 100S-E/104S-E Contactors Accessories

Description
Auxiliary Contact Blocks for Front Mounting with A1/A2 Coil Terminal Blocks · 2-pole · Quick and easy mounting without tools · Screw connection terminals · Switching down to 12V, 3mA · Mirror contact performance to the main contactor poles
Auxiliary Contact Blocks for Side Mounting · 2-pole · Two-way numbering for right or left mounting on the
contactor · With or without sequence terminal designations · Quick and easy mounting without tools · Screw connecting terminals · Switching down to 12V, 3mA · Mirror contact performance to the main contactor poles

Connection Diagrams

For Use With

Cat. No.

N.O. N.C.

11

21

33

NC

NO

100-E0910...100-E1610 100-EFC11T

11

22

34

13

21

NO

NC

14

22

100-E2600...100-E6500 100-E09400...100-E52400 100-EFB11T 100-E09200...100-E40200

11

13

21

NO

NC

100-E26...100-E96

100-ESB11

14

22

11

-3

-1

NO

NC

-4

-2

100-E09...100-E96

100-ESA11

Auxiliary Contact Blocks for Front Mounting for Severe

10

Industrial Applications

01

· 1-pole · Available in two IP degrees of ingress protection

10

­ B, B2 with built-in microswitch, IP40 degree of protection 0 1

­ (IP20 terminals) ­ B3, B4 with built-in microswitch, IP67 degree of
protection ­ (IP20 terminals), 250V, 2 A max.

10 01 10

· Available in two voltage and current ratings

­ B, B3: 125V, 0.1 A max., 3V, 1 mA min.

01

­ B2, B4: 250V, 2 A max., 17V, 1 mA min.

Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations · 2-pole · Two-way numbering for right or left mounting on the
contactor · Quick and easy mounting without tools · Mirror contact performance to the main contactor poles · Low power switching down to 24V 50 mA

11 11

Low-power Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations (1) · 1-pole · Two-way numbering for right or left mounting on the
contactor · Quick and easy mounting without tools · Mirror contact performance to the main contactor poles · Electronic compatible, 3V 1 mA

10 01

Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations · 2-pole · Two-way numbering for right or left mounting on the
contactor · Quick and easy mounting without tools · Mirror contact performance to the main contactor poles · Low power switching down to 24V 50 mA

11 11

Low-power Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations (1) · 1-pole · Two-way numbering for right or left mounting on the
contactor · Quick and easy mounting without tools · Mirror contact performance to the main contactor poles · Electronic compatible, 3V 1 mA

10 01

(1) No auxiliary contacts blocks can be mounted on the outside of the 100-ES1-B* or 100-ES3-B* devices.

NC 25

-3

-1

NO

NC

-4

-2

100-E09...100-E96

100-ESA10B 100-ESA01B 100-ESA10B2 100-ESA01B2 100-ESA10B3 100-ESA01B3 100-ESA10B4
100-ESA01B4

NO 13 NC 21

NC 32 NO 44

NC 72 NO 84 NC 31 NO 43

NO 14 NO 53

NC 22 NC 61

NO 28 NC 71 NO 83

NO 54 NC 62 NO 17

NC 26 NO 27

NO 18 NC 15

NC 32 NO 44 NC 25

NC 16 NO 13 NC 21

NC 72 NC 31

NO 84 NO 43

NO 14 NO 53

NC 22 NC 61

NO 28 NC 71 NO 83

NO 54 NC 62 NO 17

NC 26 NO 27

NO 18 NC 15

NC 16

100-E116...E370, left or right inside mounting

100-ES1-11

100-E116...E370, left or right outside mounting

100-ES2-11

100-E116...E370, left or right inside or outside 100-ES1-B10
mounting
100-E116...E370, left or right inside or outside 100-ES1-B01
mounting

100-E400...E2650, left or right inside mounting

100-ES3-11

100-E400...E2650, left or right outside mounting

100-ES4-11

100-E400...E2650, left or right inside or outside 100-ES3-B10
mounting
100-E400...E2650, left or right inside or outside 100-ES3-B01
mounting

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

67

100-E/104-E, 100S-E/104S-E Contactors Accessories

Mechanical Interlocks

Description

Connection Diagrams

Mechanical Interlock · For interlocking of two contactors · Two fixing clips included

Mechanical only, without auxiliary contacts

For Use With
100-E09...100-E38 (3 pole), 100-E09400...100-E38400
100-E40...100-E96 (3 pole), 100-E40400...100-E80400

Cat. No. 100-EMCA00A(1) 100-EMCA00B(1)

Mechanical Interlock · For interlocking of two contactors. · Interlocking of different sizes possible

Mechanical only, without auxiliary contacts

Mechanical and Electrical Interlock

· For interlocking of two contactors

· Two fixing clips, a mechanical interlock

and an electrical interlock block with A2-

01NC

A2 connection included
· Front-face connection of the electrical interlock block connects the 2 built-in

Mechanical/electrical interlock

KM1

N.C. interlocking contacts with the

A2

two coils

· The electrical diagram is used with the

A2-A2 connection

(1) Must be ordered in multiples of 10 pieces. (2) Mounting plate ordered separately (3) Mounting plate included

100-E116...100-E146
100-E190...100-E205
100-E265...100-E370
100-E116...100-E146 to 100-E190...100-E205
100-E190...100-E205 to 100-E265...100-E370
100-E400...100-E750, 100-E1260 (2)
100-E860...100-E1060, 100-E2050...100-E2650 (3)
Rod for vertical mounting 100-E400...E750 reversing contactors

100-EM1-00
100-EM4-00 100-EM5-00 100-EM2-00 100-EM3-00 100-EVR750

01NC

100-E09...100-E38 (3 pole), 100-E09400...100-E38400

100-EMCA02

KM2

A2

Electronic Timers

Description
Electronic Timing Module--ON-Delay · Delay of the contactor solenoid · The contactor is energized at the end of the delay time
Electronic Timing Module--OFF-Delay · Delay of the contactor solenoid · After interruption of the control signal, the contactor is
de-energized a the end of the delay time

ON-Delay 0.1...1 s 1...10 s 10...100 s
OFF-Delay 0.1...1 s 1...10 s 10...100 s

N.O. N.C. 11
11

Connection Diagrams

For Use With

55NC 67NO A1 KM1
A2 56NC 68NO
55NC 67NO A1 KM1
A2 56NC 68NO

100-E09...100-E96 100-E09...100-E96

Cat. No. 100-ETA 100-ETB

DC Interface Module

Description
DC Interface · Receives 24V DC signals from PLCs or other low output power sources and
switches AC control power to operate the coils of the contactor · Coil voltage: 24...250V AC 50/60 Hz · Rated control circuit voltage Uc: 24VDC

For Use With Pkg. Qty. 1

Cat. No. 100-EJE

100-E09...100-E96

10

100-EJEM

68

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories

Mechanical Latch

Description
Mechanical Latch · Ensures contactor or contactor relay is
switched on even if there is a voltage failure · Opening controlled either electrically by AC or
DC impulse or manually by button · Front mounting

Rated Voltage [V]

V AC, 50/60 Hz V DC

24...60

24...60

48...130 48...130

100...250 100...250

250...500 250...500

24...60

24...60

48...130 48...130

100...250 100...250

250...500 250...500

Connection Diagram

For Use With

100-E09...100-E65

E1

Uc

A1

E2

A2
100-E80, 100-E96

Additional Coil Terminal Block

Description

For Use With

Pkg. Qty.

Additional Coil Terminal Block · Allows bottom access to the coil terminals in addition to top access

100-E09...100-E96

10

Cat. No. 100-EFL11KJ 100-EFL11KY 100-EFL11KD 100-EFL11KN 100-EFL12KJ 100-EFL12KY 100-EFL12KD 100-EFL12KN
Cat. No.
100-ECT

Protective Covers

Description
Protective Cover · Provides protection against unintended manual operation · Sealable and Transparent

For Use With 100-E09...100-E96

Pkg. Qty. 10

100-EF (4-pole only)

10

Cat. No. 100-ESCCA
100-ESCFA

Functional Markers

Description
Functional Markers · 256 markers (16 per card) printable on HTP500 thermal transfer printer
and AMS 500 marking table · 7 x 20 mm (0.276 x 0.787 in)

For Use With

Pkg. Qty.

100-E09...100-E96

16

Terminal Block

Description
Additional Terminal Blocks · Designed to increase wire size capacity of 3-pole contactors · 3-pole terminal blocks with IP20 terminals

For Use With

Pkg. Qty.

100-E26...100-E38

2

Terminal Shrouds

Description
Terminal Shrouds · IP20 terminal protection against accidental direct contact after wiring
(EN 50274) · 3-pole and 4-pole

No. of Poles 3-pole 3-pole 4-pole

For Use With 100-E40...100-E65 100-E80, 100-E96 100-E40, 100-E52

4-pole

100-E80

Cat. No. 100-EFMS
Cat. No. 100-ECT38
Cat. No. 100-ESC65 100-ESC96 100-ESC52 100-ESC80

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

69

100-E/104-E, 100S-E/104S-E Contactors Accessories

Paralleling Terminals

Description

Paralleling Terminals
· To connect poles in parallel and thus increase the AC-1 load passing through the flow path made up of the parallel-connected poles

For Use With 100-E09, 100-E12, 100-E16
100-E26, 100-E30, 100-E38

Cat. No. 100-ECP16
100-ECP38

Terminal Lugs

Description
Terminal Lug Kit · Standard on 100-E116*L...100-E146*L contactors · Set of two

Terminal Lugs · Set of three

Wire Sizes
2 x 6 AWG...3/0 AWG
6 AWG...300 MCM 4 AWG...400 MCM (2x) 4 AWG...500 MCM (2x) 2/0 AWG...500 MCM (3x) 2/0 AWG...500 MCM (4x) 4/0 AWG...500 MCM (4x) 1/0 AWG...750 MCM (6x) 1/0 AWG...750 MCM

For Use With
100-E116...100-E146
100-E190...100-E205 100-E265...100-E370 100-E265...100-E370 100-E400...100-E460
100-E580...E750 100-E860 100-E1060 100-E1060

Cat. No.
100-ECL146
100-ETL205 100-ETL370 100-ETL370B 100-ETL580 100-ETL750 100-ETL860 100-ETL1060 100-ETL1060B

Terminal Shrouds and Shields

Description

Wires with Compression Contactor with Terminal

Lugs

Lugs

For Use With

X

--

100-E116...100-E146

--

X

100-E190...100-E205

X

Terminal Shrouds

· Not applicable when using

--

105-PW* or 170-PW* power

X

wiring kits · Pkg. Qty:2

--

X

--

100-E190...100-E205

X

100-E265...100-E370

--

100-E265...100-E370

X

100-E400...100-E460

--

100-E400...100-E460

--

X

100-E580...100-E750

X

--

100-E580...100-E750, 100-E1260

IP20 terminal shield between contactor and 193-E overload relay on an assembled direct-online starter

100-E116...100-E146 100-E190...100-E205

IP20 terminal shield between contactor and 193-E overload relay on an assembled reversing starter

100-E116...100-E146 100-E190...100-E205

(1) Not applicable when using the 100-ETL370B lug kit.

Cat. No.
100-ETS146L 100-ETS205L 100-ETS205C 100-ETS370L(1) 100-ETS370C 100-ETS460L 100-ETS460C 100-ETS750L 100-ETS750C 100-ETC146 100-ETC205 100-ETCR146 100-ETCR205

70

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories

Power Wiring Kits

Description
Reversing Power Wiring Kits · Used to connect the main poles of two 3-pole
contactors mounted side by side · 1 line-side paralleling and 1 load-side reversing
connection · Insulated, solid copper bars

For Use With 100-E09...100-E16 100-E26...100-E38 100-E40...100-E65
100-E80, 100-E96

Cat. No. 105-PW16 105-PW38 105-PW65
105-PW96

Reversing Power Wiring Kits

100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460

105-PW146 105-PW205 (1) 105-PW370 (1) 105-PW460 (2)

100-E580...100-E750

Wye-Delta Power Wiring Kits

Delta Contactor (1M/2M)

· Used to connect the main poles of the Line, Delta and Star contactors of a star-delta starter.
· Connection sets are made up of: ­ Line contactor / delta contactor, line-side

100-E09...100-E16 100-E26...100-E38 100-E40...100-E65

phase-to-phase connection

­ Delta contactor / star contactor, load-side

connection in parallel

100-E80, 100-E96

­ Star contactor: star point line-side

­ Insulated, solid copper bars

Delta Contactor (1M/2M)

100-E116...100-E146

100-E190...100-E205

100-E190...100-E205

Wye-Delta Power Wiring Kits

100-E265...100-E370

100-E265...100-E370

100-E400...100-E460

100-E580...100-E750

100-E580...100-E750

Shorting Bars

Wye Contactor (1S) 100-E09...100-E16 100-E26...100-E38 100-E40...100-E65
100-E80, 100-E96
Wye Contactor (1S) 100-E116...100-E146 100-E116...100-E146 100-E190...100-E205 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460 100-E400...100-E460 100-E580...100-E750 100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460 100-E580...100-E750

105-PW750 (2) Cat. No. 170-PW16 170-PW38 170-PW65
170-PW96
Cat. No. 170-PW146 170-PW190 170-PW205 170-PW265 170-PW370 170-PW460 170-PW580 170-PW750 170-PWY146 170-PWY205 170-PWY370 170-PWY460 170-PWY750

(1) Kits includes one set of terminal extensions. If 100-ETL* terminal lugs are to be used on line and load side of reversing contactor, and second set of 100-ETX terminal extensions is required. (2) If 100-ETL* terminal lugs are to be used on line and load side of reversing contactor, two sets of 100-ETX terminal extensions are also required.

Mounting Plates

For direct-on-line starters

Description

For reversing contactors

For reversing starters

For Use With 100-E116...100-E146 100-E190...100-E205 100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460 100-E580...100-E750 100-E116...100-E146 100-E190...100-E205

Cat. No. 100-EMS146 100-EMS205 100-EMR146 100-EMR205 100-EMR370 100-EMR460 100-EMR750 100-EMRS146 100-EMRS205

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

71

100-E/104-E, 100S-E/104S-E Contactors Accessories

Connectors

Description
For connection to 140G or 140MG · Connection between contactors/starters and molded
case circuit breakers. · These connection sets are solid copper bars.

For Use With Circuit Breaker 140G-H, 140MG-H 140G-I, 140MG-I 140G-J, 140MG-J 140G-J, 140MG-J 140G-K, 140MG-K 140G-M, 140MG-M 140G-K, 140MG-K

For Use With Contactor 100-E116...100-E146 100-E116...100-E146 100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E750 100-E400...100-E750

Terminal Accessories

Description

Terminal Enlargements
· Enlargement pieces designed to increase the width of the contactor terminal pads in order to allow larger connections to be mounted.

Terminal Extensions
· Extension pieces designed to extend the main terminals of contactors for combined mounting of contactors and connection sets

For Use With Contactor 100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460 100-E580...100-E750 100-E1260 100-E116...100-E146 100-E190...100-E205 100-E265...100-E370 100-E400...100-E460
100-E580...100-E750

Cat. No. 100-PCE1 100-PCE2 100-PCE3 100-PCE4 100-PCE5 100-PCE6 100-PCE7
Cat. No. 100-ETE146 100-ETE205 100-ETE370 100-ETE460 100-ETE750 100-ETE1260 100-ETX146 100-ETX205 100-ETX370 100-ETX460 100-ETX750

72

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Renewal Parts
Coil Modules

Description

Coil Modules

(1) One set of two coils (2) Printed circuit board

100-E/104-E, 100S-E/104S-E Contactors Renewal Parts

For Use With
100-E116
100-E146
100-E190, 100-E205 100-E190 100-E205
100-E265, 100-E305, 100-E370 100-E265 100-E305 100-E370
100-E400, 100-E460
100-E580, 100-E750, 100-E1260
100-E860, 100-E1060, 100-E2050 100-E2650

Voltage 24...60V AC/DC 48...130V AC/DC 100...250V AC/DC 250...500V AC/DC 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 24...60V AC/DC 48...130V AC/DC 100...250V AC/DC 250...500V AC/DC 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 24...60V AC/DC 48...130V AC/DC 100...250V AC/DC 250...500V AC/DC 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 24...60V AC/DC 48...130V AC/DC 100...250V AC/DC 250...500V AC/DC 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 24...60V DC w/ PLC Interface 48...130V AC/DC w/ PLC Interface 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface 24...60V DC w/ PLC Interface 48...130V AC/DC w/ PLC Interface 100...250V AC/DC w/ PLC Interface 250...500V AC/DC w/ PLC Interface
100...250V AC/DC w/ PLC Interface
100...250V AC/DC w/ PLC Interface

Cat. No. TG913 TG914 TG915 TG916 TGE913 TGE914 TG901 TG902 TG903 TG904 TGE903 TGE904 TG905 TG906 TG907 TG908 TGE915 TGE916 TGE907 TGE908 TG909 TG910 TG911 TG912 TGE917 TGE918 TGE919 TGE920 TGE911 TGE912 THE901 THE902 THE903 THE904 TJE901 TJE902 TJE903 TJE904 TKE903 (1) TKE904 (2) TLE903 (1) TLE904 (2)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

73

100-E/104-E, 100S-E/104S-E Contactors Renewal Parts

Contact Kits

Description

Contact Kits

(1) Movable contacts only
Terminal and Mounting Hardware Kits

Arc Chutes Description

Terminal and Mounting Hardware Kits

(1) Mounting hardware only.

For Use With 100-E116 100-E146 100-E190 100-E205 100-E2650 100-E305 100-E370 100-E400 100-E460 100-E580 100-E750 100-E1260 100-E860 100-E1060 100-E2050
100-E2650 (1) 100-E400, 100-E460 100-E580, 100-E750, 100-E1260 100-E860, 1060, 100-E2050
100-E2650

Cat. No. 100-EA116 100-EA146 100-EA190 100-EA205 100-EA265 100-EA305 100-EA370 100-EA400 100-EA460 100-EA580 100-EA750 100-EA1260 100-EA860 100-EA1060 100-EA2050
100-EA2650
100-EC460 100-EC750 100-EC1060 100-EC2650

For Use With 100-E116*L, 100-E146*L
100-E116, 100-E146 100-E190, 100-E205 100-E265, 100-E305, 100-E370 100-E400, 100-E460 100-E580, 100-E750, 100-E1260 100-E860, 100-E1060, 100-E2050
100-E2650

Cat. No. 100-EHS146(1) 100-EHF146 100-EHF205 100-EHF370 100-EHF460 100-EHF750 100-EHF2050 100-EHF2650

74

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Specifications

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 31 - General Specifications

Rated Isolation Voltage Ui

IEC

[V]

UL, CSA

[V]

Rated Impulse Voltage Withstand Uimp

[kV]

Rated Voltage Ue

AC 50/60 Hz

[V]

DC

[V]

100-E, 100S-E, 104-E, 104S-E09...65

100-E, 100S-E, 104S-E80...96, 104-E80...2650

690

1000

600

600

6

8

115, 200, 230, 240, 400, 415, 460 500, 575, 690, 1000

24, 48, 110, 220, 440

Electromagnetic compatibility Insulation Class of the Coil Rated coil frequency
Ambient Temperature

Storage [°C ( °F)]

Operation at rated voltage

[°C ( °F)]

IEC 60947-1 - Environment A and B(1)

Class F per IEC 60947-4-1

AC 50/60 Hz, DC

-60...+80 (-76...+176)

-40...+70 (-40...+158)

-40...+70 (-40...+158)

-40...+70 (-40...+158)

Max. Altitude of Installation Site

[m]

Climatic Withstand

Resistance to Shock

Resistance to Vibration

Contactor main contacts

Protection Class

Contactor coil terminals

Auxiliary contacts

Functional Safety Data (100S-E116...-E750): Usable for ISO 13849-1 and IEC 62061. Data is based on the B10 value given and: Mission time/Proof test interval of 20 years.

100S-E116...100S-E370 100S-E116...100S-E205 100S-E265...100S-E370 100S-E400...100S-E750 100S-E400...100S-E460 100S-E570...100S-E750

3000

Category B according to IEC 60947-1, Annex Q

IEC 60068-2-27

IEC 60068-2-6

IP2X(2)

IP00

IP2X (in connected state)

IP2X (in connected state)

B10: 1.0E+06 operations at 50% max. AC-3 load; failure ratio: 75% failure to open, 25% failure to close

B10: 5.0E+06 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close

B10: 2.5E+06 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close

B10: 5.0E+05 operations at 50% max. AC-3 load; failure ratio: 75% failure to open, 25% failure to close

B10: 3.0E+06 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close

B10: 7.0E+05 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close

(1) 100-E09...E38 only. (2) 100-E40...E96 meet IP2X when used with 100-ESC... terminal shrouds.

Table 32 - Standards Compliance and Certifications

Standards Compliance

Certifications

· IEC/EN 60947-1, Low-voltage switchgear and controlgear

· cULus, File No. E41850 / E196120 (contactors, reversing contactors)

· IEC/EN 60947-4-1, Low-voltage switchgear and controlgear, Contactors and motor-starters

· UL

· IEC/EN 60947-5-1, Low-voltage switchgear and controlgear, Control circuit devices and switching · CSA

elements

· CCC

· UL 60947-4-1, Industrial Control Equipment (USA)

· EAC

· CSA C22.2 No. 60947-4-1 Industrial Control Equipment (Canada).

· RCM

· Mechanically Linked Contacts: IEC 60947-5-1, Annex L (100/100S-E09...100/100S-E96 with all 100-E* front- and side-mounted N.C. auxiliary contacts)

· RINA · KC

· Mirror Contacts: IEC 60947-4-1, Annex F (100/100S-E116...100/100S-E750 with all 100-ES* side-mounted N.C. auxiliary contacts)

· CE · SUVA · SEMI-F47 (Conditions of use on request)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

75

100-E/104-E, 100S-E/104S-E Contactors Specifications

9...96 A Contactor Specifications

Table 33 - Main Circuits

100/104-E, 100S/104S-E

9

12

16

26

30

38

40

52

65

80

96

AC-1 Active Power Load (50/60Hz); Ambient temperature 40 °C (104 °F)

Rated Operational 690V [A] 25

28

30

45

50

50

70

100

105

125

130

Current, Ie

1000V [A] --

--

--

--

--

--

--

--

--

35

40

230 [kW] 10

11

12

18

20

20

28

40

42

50

52

240 [kW] 10

12

12

19

21

21

29

42

44

52

54

400 [kW] 17

19

21

31

35

35

48

69

73

87

90

Rated Operational Power, Pe

415 [kW] 18

20

22

32

36

36

50

72

75

90

93

500 [kW] 22

24

26

39

43

43

61

87

91

108

113

690 [kW] 30

33

36

54

60

60

84

120

125

149

155

1000 [kW] --

--

--

--

--

--

--

--

--

61

69

Ambient temperature 60 °C (140 °F)

Rated Operational 690V [A] 25

28

30

40

42

42

60

80

90

100

105

Current, Ie

1000V [A] --

--

--

--

--

--

--

--

--

35

40

230 [kW] 10

11

12

16

17

17

24

32

36

40

42

240 [kW] 10

12

12

17

17

17

25

33

37

42

44

400 [kW] 17

19

21

28

29

29

42

55

62

69

73

Rated Operational Power, Pe

415 [kW] 18

20

22

29

30

30

43

58

65

72

75

500 [kW] 22

24

26

35

36

36

52

69

78

87

91

690 [kW] 30

33

36

48

50

50

72

96

108

120

125

1000 [kW] --

--

--

--

--

--

--

--

--

61

69

Ambient temperature 70 °C (158 °F)

Rated Operational 690V [A] 22

24

26

32

37

37

50

70

80

85

90

Current, Ie

1000V [A] --

--

--

--

--

--

--

--

--

35

40

230 [kW] 9

10

10

13

15

15

20

28

32

34

36

240 [kW] 9

10

11

13

15

15

21

29

33

35

37

400 [kW] 15

17

18

22

26

26

35

48

55

59

62

Rated Operational Power, Pe

415 [kW] 16

17

19

23

27

27

36

50

58

61

65

500 [kW] 19

21

23

28

32

32

43

61

69

74

78

690 [kW] 26

29

31

38

44

44

60

84

96

102

108

1000 [kW] --

--

--

--

--

--

--

--

--

61

69

With Conductor sizes

[mm2] 4

6

6

10

10

10

25

35

35

50

50

76

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 34 - Main Circuits

100/104-E, 100S/104S-E

9

12

16

26

30

38

40

52

65

80

96

Switching of 3-phase Motors; (50Hz) Ambient temperature 60 °C (140 °F) AC-2, AC-3

220-240V [A] 9

12

18

26

33

40

40

53

65

80

96

380-400V [A] 9

12

18

26

32

38

40

53

65

80

96

415V

[A] 9

12

18

26

32

38

40

53

65

80

96

Rated Operational Current, Ie

440V

[A] 9

12

18

26

32

38

40

53

65

80

96

500V

[A] 9.5

12.5

15

23

28

33

40

45

55

65

80

690V

[A] 7

9

10.5

17

21

24

25

35

39

49

57

1000V

[A] --

--

--

--

--

--

--

--

--

25

30

220-240V [kW] 2.2

3

4

6.5

9

11

11

15

18.5

22

25

380-400V [kW] 4.0

5.5

7.5

11

15

18.5

18.5

22

30

37

45

415V [kW] 4.0

5.5

9

11

15

18.5

22

30

37

45

55

Rated Operational Power, Pe

440V [kW] 4.0

5.5

9

15

18.5 22.0

22

30

37

45

55

500V [kW] 5.5

7.5

9

15

18.5 22.0

22

30

37

45

55

690V [kW] 5.5

7.5

9

15

18.5 22.0

22

30

37

45

55

1000V [kW] --

--

--

--

--

--

--

--

--

35

40

Load Carrying Capacity per UL/CSA

General Purpose Current (enclosed)

600V

[A] 13.8

16.0

20

24

24.0 24.0

34

34

56

80

80

120V

[A] 13.8

16.0

20

24

24.0 24.0

34

34

56

80

80

Rated Operational

240V

[A] 10.0

12.0

17

17

28.0 28.0

40

50

68

68

88

Current and Power

(enclosed), 1-Phase

120V [Hp] 0.75

1

1.5

2

2

2

3

3

5

7.5

7.5

240V [Hp] 1.5

2

3

3

5

5

7.5

10

15

15

20

200-208 [A] 7.8

11

17.5

25.3

32.2

32.2

32.2

48.3

62.1

78.2

92

220-240 [A] 6.8

9.6

15.2

22.0

28

28

42

54

68

80

80

440-480 [A] 7.6

11

14

21.0

27

34

40

52

65

77

77

Rated Operational 550-600 [A] 9

11

17

22.0

27

32

41

52

62

77

77

Current and Power

(enclosed), 3-Phase 200-208 [Hp] 2

3

5

7.5

10

10

10

15

20

25

30

220-240 [Hp] 2

3

5

7.5

10

10

15

20

25

30

30

440-480 [Hp] 5

7.5

10

15.0

20

25

30

40

50

60

60

550-600 [Hp] 7.5

10

15

20.0

25

30

40

50

60

75

75

Rated Operational

125V DC [A] 9.5

13.2

17

25.0

25

25

40

58

76

76

110

Current and Power 250V DC [A] 8.5

8.5

12.2

12.2

20

29

38

55

72

89

106

(enclosed), with 3

125V DC [Hp] 1

1.5

2

poles in series

250V DC [Hp] 2

3

3

3

3

3

5

7.5

10

10

15

5

7.5

7.5

10

15

20

25

30

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

77

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 35 - Main Circuits

100/104-E, 100S/104S-E

9

12

16

26

30

38

40

52

65

80

96

Wye-Delta (60 Hz)

200V [Hp] 3

5

7.5

10

15

15

15

25

30

40

50

Rated Operational 230V [Hp] 3

5

7.5

10

15

15

25

30

40

50

50

Power, Pe

460V [Hp] 7.5

10

15

25

30

40

50

60

75

100

100

575V [Hp] 10

15

25

30

40

50

60

75

100

125

125

Star-Delta Starting (50 Hz)

230V [A] 9

12

18

26

33

40

40

53

65

80

96

 240V [A] 9

12

18

26

32

38

40

53

65

80

96

400V [A] 9

12

18

26

32

38

40

53

65

80

96

Rated Operational Current, Ie

415V

[A] 9

12

18

26

32

38

40

53

65

80

96

500V [A] 9.5

12.5

15

23

28

33

40

45

55

65

80

690V [A] 7

9

10.5

17

21

24

25

35

39

49

57

1000V [A] --

--

--

--

--

--

--

--

--

25

30

230V [kW] 4

5.5

7.5

11

15

18.5

18.5

22

30

37

45

240V [kW] 4

5.5

7.5

11

15

18.5

18.5

22

30

37

45

400V [kW] 7.5

7.5

15

22

30

30

37

45

55

75

90

Rated Operational Power, Pe

415V

[kW] 7.5

7.5

15

22

30

37

37

45

55

75

90

500V [kW] 7.5

11

15

22

30

37

45

45

55

75

90

690V [kW] 7.5

11

15

22

30

37

37

55

55

75

90

1000V [kW] --

--

--

--

--

--

--

--

--

--

--

Table 36 - Main Circuits

100/104-E, 100S/104S-E

9

12

16 26 30 38 40 52 65 80 96

UL/CSA Elevator Duty

Rated Operational Current and Power, 500,000 electrical operations, 1-Phase

115V AC 230V AC 115V AC 230V AC

[A] 5.8 7.20 --

20

24

24

34

34

34

56

56

[A] 2.20 3.20 -- 9.6 10 15.2 15.2 22 28 28 28

[Hp] 0.25 0.33 --

1.5

2

2

3

3

3

5

5

[Hp] 0.50 0.75 --

3

3

5

5

7.5

10

10

10

200V AC

[A] 4.60 7.50 -- 16.7 24.2 24.2 30.8 30.8 46.2 46.2 46.2

230V AC

[A] 4.20 6.80 -- 15.2 22 22 28 28 42 42 42

Rated Operational Current and Power, 500,000 electrical operations 3-Phase

460V AC 575V AC 200V AC 230V AC

[A] 4.80 7.60 -- 21.0 27 27 34 40 52 52 52

[A] 3.90 6.10 --

17

22 22 32

41

41

52 52

[Hp] 1

2

--

5

7.5 7.5

10

10

15

15

15

[Hp] 1

2

--

5

8

10

10

15 20 20 20

460V AC

[Hp] 3

5

--

15

20 20

25

30 40 40 40

575V AC

[Hp] 3

5

--

15 20 20 30 40 40 50 50

UL/CSA HVAC Applications Definite purpose rating (3-phase)

FLA

600V

[A] 20 25 30 45 50 50 60 80 90 105 115

200-208V AC

[A] 120 150 180 270 300 300 360 480 540 630 690

220-240V AC

[A] 120 150 180 270 300 300 360 480 540 630 690

LRA

440-480V AC

[A] 120 150 180 270 300 300 360 480 540 630 690

550-600V AC

[A] 80 100 120 180 200 200 240 320 360 420 460

78

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 37 - Main Circuits

100/104-E, 100S/104S-E

9

12

16

26

30

38

40

52

65

80

96

Switching of Power Transformers, AC-6a (50 Hz)

Inrush Current Rated transformer

current

=

n

230V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

240V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

400V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0 n=30
415V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

500V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

690V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

230V [kVA] 5

5

7

11

13

16

17

21

23

25

28

240V [kVA] 5

6

7

11

14

17

17

21

24

26

29

Apparent Power

400V [kVA] 8

9

12

18

23

28

29

36

40

44

48

415V [kVA] 8

10

12

19

24

29

30

37

42

45

50

500V [kVA] 10

12

14

23

29

35

36

45

50

55

61

690V [kVA] 14

16

20

32

40

48

50

62

70

76

84

n=20

690V [A] 17.5 20

25

40

50

60 62.5 77.5 87.5 95

105

n=15

690V [A] 23.3 26.7 33.3 53.3 66.7 80.0 83.3 103 117 127 140

60 Hz Peak Inrush/peak rated transformer current

n=30

600V [A] 11.7 13.3 16.7 26.7 33.3 40.0 41.7 51.7 58.3 63.3 70.0

200V [kVA] 4

5

6

9

12

14

14

18

20

22

24

208V [kVA] 4

5

6

10

12

14

15

19

21

23

25

Apparent Power

240V [kVA] 5

6

7

11

14

17

17

21

24

26

29

480V [kVA] 10

11

14

22

28

33

35

43

48

53

58

600V [kVA] 12

14

17

28

35

42

43

54

61

66

73

n=20

600V [A] 17.5 20.0 25.0 40.0 50.0 60.0 62.5 77.5 87.5 95.0 105

200V [kVA] 6

7

9

14

17

21

22

27

30

33

36

208V [kVA] 6

7

9

14

18

22

22

28

31

34

38

Apparent Power

240V [kVA] 7

8

10

17

21

25

26

32

36

39

44

480V [kVA] 15

17

21

33

42

50

52

64

73

79

87

600V [kVA] 18

21

26

42

52

62

65

80

91

99 109

n=15

600V [A] 23.3 26.7 33.3 53.3 66.7 80.0 83.3 103 117 127 140

200V [kVA] 8

9

12

18

23

28

29

36

40

44

48

208V [kVA] 8

10

12

19

24

29

30

37

42

46

50

Apparent Power

240V [kVA] 10

11

14

22

28

33

35

43

48

53

58

480V [kVA] 19

22

28

44

55

66

69

86

97 105 116

600V [kVA] 24

28

35

55

69

83

87

107 121

131 145

Switching of Lighting Loads (UL/CSA)

1-phase per pole

347V [A] 20

25

30

45

50

50

65

80

90 105 115

Tungsten lamps 3-phase (break all lines)

600V [A] 20

25

30

45

50

50

65

80

90

105 115

Electrical

1-phase per pole

347V [A] 20

25

30

45

50

50

65

80

90 105 115

discharge

3-phase (break all

lamps (ballast) lines)

600V [A] 20

25

30

45

50

50

65

80

90

105 115

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

79

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 38 - Main Circuits

100/104-E, 100S/104S-E

9 12 16

26

30

38

40 52 65 80 96

3- or 4-Pole

3-Pole 4-Pole 3-Pole 3-Pole 4-Pole 3-Pole 3-Pole 3-Pole 3-Pole 3-Pole

Switching of DC Loads--Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C

 72V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

1 pole

110V

[A] 10 15 20 -- -- -- -- -- -- -- -- -- --

220V

[A] -- -- -- -- -- -- -- -- -- -- -- -- --

 72V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

2 poles in series

110V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

220V

[A] 10 15 20 -- -- -- -- -- -- -- -- -- --

 72V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

3 poles in series

110V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

220V

[A] 25 27 30 45 45 50 50 55 70 100 105 125 130

 72V

[A] 25 -- 30 -- 45 -- -- 55 -- -- -- -- --

4 poles in series

110V

[A] 25 -- 30 -- 45 -- -- 55 -- -- -- -- --

220V

[A] 25 -- 30 -- 45 -- -- 55 -- -- -- -- --

440V

[A] 10 -- 20 -- -- -- -- -- -- -- -- -- --

Shunt-wound Motors--Starting, reverse current breaking, reversing, stepping: DC-3 at 60 °C

 72V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

1 pole

110V

[A] 6

7

8

--

--

--

--

--

--

--

--

--

--

220V

[A] -- -- -- -- -- -- -- -- -- -- -- -- --

 72V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

2 poles in series

110V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

220V

[A] 6

7

8

--

--

--

--

--

--

--

--

--

--

 72V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

3 poles in series

110V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

220V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

 72V

[A] 25 -- 30 -- -- -- -- -- -- -- -- -- --

4 poles in series

110V

[A] 25 -- 30 -- -- -- -- -- -- -- -- -- --

220V

[A] 25 -- 30 -- -- -- -- -- -- -- -- -- --

440V

[A] 6 -- 8 -- -- -- -- -- -- -- -- -- --

Series-wound Motors--Starting, reverse current breaking, reversing, stepping: DC-5 at 60 °C

 72V

[A] 9 12 16 20 -- 25 25 -- 70 100 105 125 130

1 pole

110V

[A] 4

4

4

--

--

--

--

--

--

--

--

--

--

220V

[A] -- -- -- -- -- -- -- -- -- -- -- -- --

 72V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

2 poles in series

110V

[A] 10 15 20 45 -- 50 50 -- 70 100 105 125 130

220V

[A] 4

4

4

--

--

--

--

--

--

--

--

--

--

 72V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

3 poles in series

110V

[A] 25 27 30 45 -- 50 50 -- 70 100 105 125 130

220V

[A] 9 12 16 20 -- 25 25 -- 70 100 105 125 130

 72V

[A] 25 -- 30 -- -- -- -- -- -- -- -- -- --

4 poles in series

110V

[A] 25 -- 30 -- -- -- -- -- -- -- -- -- --

220V

[A] 10 -- 20 -- -- -- -- -- -- -- -- -- --

440V

[A] 4 -- 4 -- -- -- -- -- -- -- -- -- --

Short Time Withstand ICW 40 °C

1 s

[A] 300 300 300 700 700 700 1000 1000 1000 1200 1200

10 s

[A] 150 150 150 350 350 350 600 600 600 780 780

3- Pole

30 s

[A] 80 80 80 225 225 225 350 350 350 450 450

1 min

[A] 60 60 60 150 150 150 250 250 250 300 300

15 min

[A] 35 35 35 50 50 50 110 110 110 140 140

80

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 38 - Main Circuits (Continued)

100/104-E, 100S/104S-E

9 12 16

26

30

38

40 52 65 80 96

3- or 4-Pole

3-Pole 4-Pole 3-Pole 3-Pole 4-Pole 3-Pole 3-Pole 3-Pole 3-Pole 3-Pole

Resistance and Power Dissipation

Main current circuit resistance

[m] 0.41 0.46 0.36 0.30 0.29 0.30 0.21 0.20 0.21 0.16 0.16

Power dissipation per pole at Ie AC-1, 400V

[W] 0.8 1 1.2 1.8 2.4 2.4 3 6.3 7 7.6 8.2

Power dissipation per pole at Ie AC-3, 400V

[W] 0.1 0.2 0.35 0.6 0.9 1.3 1 1.7 2.7 3 4.5

Total Power dissipation at: Ie AC-3, 400V; AC/DC control (120-250V)

[W] 2.3 2.6 3.05 3.8 4.7 5.9 5 7.1 10.1 11 15.5

AC-1 ops/hr

600 cycles/h

Maximum Switching Frequency

AC-3 ops/hr

AC-2, AC-4

ops/hr

300 cycles/h

1200 cycles/h 150 cycles/h

Weight: AC/DC (Electronic)

[kg (lbs.)]

0.43 (0.95)

0.43 (0.95)

0.43 (0.95)

0.48 (1.06)

0.48 (1.06)

0.48 (1.06)

0.99 (2.18)

0.99 (2.18)

0.98 (2.16)

1.23 (2.7)

1.25 (2.76)

Table 39 - Short-circuit Current Ratings

100/104-E, 100S/104S-E

9

12

16

26

30 38 40 52 65

80

96

Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1

100 kA Available Fault Current

DIN FUSES- gG

Type "2" (400V)

[A] 32 32 35 62 80 80 100 125 125 160

160

60 kA Available Fault Current

Type "2" (690V)

[A] 6

10

16

32

32 40 40 63 80

80

100

70 kA Available Fault Current

MCCB

Type "2" (400V)

[A] 28 28 28 56 56 240 520 800 800 880

880

Short Circuit Current Rating (Max. Fuse or Circuit Breaker Rating) Per UL 60947 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only)

5 kA Available Fault Current

UL Class RK5 Fuses

Type 1 Combination (600V)

[A] 30 30 60

60 100 100 150 150 --

--

--

10 kA Available Fault Current

UL Class RK5 Fuses

Type 1 Combination (600V)

[A] --

--

--

--

-- -- -- -- 150 200

200

UL Class J and CSA HRCI-J Fuses

100 kA Available Fault Current

Type 1 Combination (600V)

[A] 30 30 60 60 100 100 150 150 150 200

200

5 kA Available Fault Current

Type 1 Combination (480V)

[A] 60 60 60 100 125 125 250 250 --

--

--

10 kA Available Fault Current

Type 1 Combination (480V)

[A] 60 60 60

--

-- -- -- -- 250 250

250

65 kA Available Fault Current

Type 1 Combination (480V)

[A] --

--

-- 100 -- -- 250 250 250 250

250

100 kA Available Fault Current

Type 1 Combination (480V)

[A] --

--

--

-- 125 125 -- -- -- 100

100

UL Inverse-Time Circuit Breaker

5 kA Available Fault Current

Type 1 Combination (600V)

[A] 60 60

--

-- 125 125 250 250 --

--

--

10 kA Available Fault Current

Type 1 Combination (600V)

[A] --

--

60

--

-- -- 250 250 250 250

250

25 kA Available Fault Current

Type 1 Combination (600V)

[A] --

--

-- 100 -- -- -- -- --

--

--

35 kA Available Fault Current

Type 1 Combination (600V)

[A] --

--

--

-- 125 125 -- -- 250 --

--

50 kA Available Fault Current

Type 1 Combination (600V)

[A] --

--

--

--

-- -- -- -- -- 250

250

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

81

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 40 - Coil Data

100/104-E, 100S/104S-E

9

Operating Limits

50/60Hz

pick-up dropout

[x Us] [x Us]

DC Control

pick-up dropout

[x Us] [x Us]

Standard Coil

pick-up 24-60V AC, 20-60V DC (KJ)
hold-in

[VA]/[W] [VA]/[W]

48...130V AC/DC (KY)

pick-up hold-in

[VA]/[W] [VA]/[W]

100...250V AC/DC (KD)

pick-up hold-in

[VA]/[W] [VA]/[W]

250...500V AC/DC (KN)

pick-up hold-in

[VA]/[W] [VA]/[W]

Operating Times

closing delay [ms] opening delay [ms]

Energy-efficient Coil

12-20V DC (EQ)

pick-up

[W]

hold-in

[W]

pick-up 24-60V AC, 20-60V DC (EJ)
hold-in

[VA]/[W] [VA]/[W]

Operating Times

closing delay [ms] opening delay [ms]

High Energy Efficient Coil

24V DC (QJ)

pick-up

[W]

hold-in

[W]

Operating Times

closing delay [ms] opening delay [ms]

12 16 26 30 38 40 52

65

80

96

0.85...1.1  0.60 0.80...1.1  0.60

50/50 2.2/2 50/50 2.2/2 50/50 2.2/2 50/50 2.2/2 40...95 11...95

25/25 4/2 25/25 4/2 25/25 4/2 25/25 4/2
42...100 17...100

40/40 4/2 40/40 4/2 40/40 4/2 40/40 4/2

12...16 1.7
16/12...16 1.7/1.7 40...95 11...95

----

--

--

--

----

--

--

--

----

--

--

--

----

--

--

--

----

--

--

--

----

--

--

--

6 1.7 27...53 17...29

----

--

--

--

----

--

--

--

----

--

--

--

----

--

--

--

82

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

116...2650 A Contactors

Table 41 - Main Circuits

100/104-E, 100S-E

116 146

AC-1 Active Power Load (50/60 Hz); Ambient temperature 40 °C (104 °F)

Rated Operational Current, Ie

690V 1000V

[A] 160 225 [A] 160 225

230V [kW] 64 90

240V [kW] 67 94

Rated Operational Power, Pe

400V [kW] 111 156 415V [kW] 115 162 500V [kW] 139 195

690V [kW] 191 269

1000V [kW] 277 390

Ambient temperature 60 °C (140 °F)

Rated Operational Current, Ie

690V 1000V

[A] 145 200 [A] 145 200

230V [kW] 58 80

240V [kW] 60 83

Rated Operational Power, Pe

400V [kW] 100 139 415V [kW] 104 144 500V [kW] 126 173

690V [kW] 173 239

1000V [kW] 251 346

Ambient temperature 70 °C (158 °F)

Rated Operational Current, Ie

690V 1000V

[A] 130 175 [A] 130 175

230V [kW] 52 70

240V [kW] 54 73

Rated Operational Power, Pe

400V [kW] 90 121 415V [kW] 93 126 500V [kW] 113 152

690V [kW] 155 209

1000V [kW] 225 303

With conductor sizes

[mm2] 70 95

(1) For currents above 275 A, use terminal extensions. (2) For currents above 450 A, use terminal extensions. (3) Maximum connection bar width 50 mm. (4) Maximum connection bar width 100 mm.

190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650
275 350 400 500 600 600 700 800 1050 1350 1650 1260 2050 2650 250 275 350 375 400 600 700 800 1050 1350 1650 1260 2050 2650 110 139 159 199 239 239 279 319 418 538 657 502 817 1056 114 145 166 208 249 249 291 333 436 561 686 524 852 1102 191 242 277 346 416 416 485 554 727 935 1143 873 1420 1836 198 252 288 359 431 431 503 575 755 970 1186 906 1474 1905 238 303 346 433 520 520 606 693 909 1169 1429 1091 1775 2295 329 418 478 598 717 717 837 956 1255 1613 1972 1506 2450 3167 433 476 606 650 693 1039 1212 1386 1819 2338 2858 2182 3551 4590
250 300 350 400 500 500 600 700 875 1150 1450 1040 1750 2350 225 250 300 325 350 500 600 700 875 1150 1450 1040 1750 2350 100 120 139 159 199 199 239 279 349 458 578 414 697 936 104 125 145 166 208 208 249 291 364 478 603 432 727 977 173 208 242 277 346 346 416 485 606 797 1005 721 1212 1628 180 216 252 288 359 359 431 503 629 827 1042 748 1258 1689 217 260 303 346 433 433 520 606 758 996 1256 901 1516 2035 299 359 418 478 598 598 717 837 1046 1374 1733 1243 2091 2809 390 433 520 563 606 866 1039 1212 1516 1992 2511 1801 3031 4070
200 240 290 325 400 400 480 580 720 1000 1270 875 1500 2120 185 200 240 260 290 400 480 580 720 1000 1270 875 1500 2120 80 96 116 129 159 159 191 231 287 398 506 349 598 845 83 100 121 135 166 166 200 241 299 416 528 364 624 881 139 166 201 225 277 277 333 402 499 693 880 606 1039 1469 144 173 208 234 288 288 345 417 518 719 913 629 1078 1524 173 208 251 281 346 346 416 502 624 866 1100 758 1299 1836 239 287 347 388 478 478 574 693 860 1195 1518 1046 1793 2534 320 346 416 450 502 693 831 1005 1247 1732 2200 1516 2598 3672 150 240 (1) 240 300 (2) 2x185 (2) 2x185 2x240 2x240 800 (3) 1000 (4) 1500 (4) 1000 (3) 2000 (4) 3000 (4)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

83

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 42 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F) AC-2, AC-3

220-240V [A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 -- -- --

380-400V [A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 -- -- --

Rated Operational Current, Ie

415V

[A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 -- -- --

440V

[A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 -- -- --

500V

[A] 110 130 156 185 250 290 350 400 460 580 750 860 970 -- -- --

690V

[A] 66 93 135 165 250 290 315 350 400 500 650 800 970 -- -- --

1000V [A] 46 60 85 100 113 131 141 155 200 250 300 375 400 -- -- --

220-240V [kW] 37 45 55 55 75 90 110 110 132 160 220 250 315 -- -- --

380-400V [kW] 55 75 90 110 132 160 200 200 250 315 400 475 560 -- -- --

Rated Operational Power, Pe

415V [kW] 55 75 90 110 132 160 200 220 250 355 425 500 630 -- -- -- 440V [kW] 75 90 110 132 160 160 200 220 250 355 450 560 710 -- -- -- 500V [kW] 75 90 110 132 160 200 250 250 315 400 530 630 710 -- -- --

690V [kW] 63 90 132 160 200 250 315 315 355 500 600 800 1000 -- -- --

1000V [kW] 55 75 110 132 160 185 200 220 280 355 400 555 600 -- -- --

Load Carrying Capacity per UL/CSA

General-purpose Current (enclosed)

[A] 160 200 250 300 350 400 520 550 650 750 900 1350 1650 1210 2100 2700

200V

[A] 92 120 150 177 221 285 359 359 414 552 692 954 1030 -- -- --

230V

[A] 104 130 154 192 248 312 360 360 480 604 722 954 1030 -- -- --

Rated Operational Current and Power (enclosed), 3-Phase

460V

[A] 96 124 156 180 240 302 361 414 477 590 722 954 1030 -- -- --

575V

[A] 99 125 144 192 242 289 336 382 472 578 672 944 1050 -- -- --

200V [Hp] 30 40 50 60 75 100 125 125 150 200 250 -- -- -- -- --

230V [Hp] 40 50 60 75 100 125 150 150 200 250 300 400 450 -- -- --

460V [Hp] 75 100 125 150 200 250 300 350 400 500 600 800 900 -- -- --

575V [Hp] 100 125 150 200 250 300 350 400 500 600 700 1000 1150 -- -- --

Rated Current (enclosed), with 3 poles in series

260V DC 300V DC 340V DC 600V DC

[A] 160 200 -- -- -- -- -- -- -- -- -- -- -- -- -- -- [A] -- -- 230 250 -- -- -- -- -- -- -- -- -- -- -- -- [A] -- -- -- -- 350 400 520 -- -- -- -- -- -- -- -- -- [A] -- -- -- -- -- -- -- 550 650 750 900 1050 1350 1210 1900 --

84

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 43 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Switching of 3-phase Motors, (50Hz); Ambient temperature 60°C, AC-4

230V [A] 84 103 128 156 195 230 280 307 377 -- -- -- -- -- -- --

240V [A] 84 103 128 156 195 230 280 307 377 -- -- -- -- -- -- --

400V

Rated Operational Current, Ie

415V

500V

[A] 84 103 128 156 195 230 280 307 377 -- -- -- -- -- -- -- [A] 84 103 128 156 195 230 280 307 377 -- -- -- -- -- -- -- [A] 84 103 128 156 195 230 280 307 377 -- -- -- -- -- -- --

690V [A] 66 80 93 104 153 162 188 334 350 -- -- -- -- -- -- --

1000V [A] 40 48 72 85 90 95 100 141 155 -- -- -- -- -- -- --

230V [kW] 25 32 40 50 55 75 90 90 110 -- -- -- -- -- -- --

240V [kW] 25 32 40 50 63 75 90 100 125 -- -- -- -- -- -- --

400V [kW] 45 55 63 80 110 132 160 160 200 -- -- -- -- -- -- --

Rated Operational Power, Pe

415V

[kW] 45 55 63 90 110 132 160 160 220 --

--

--

--

--

--

--

500V [kW] 55 63 90 110 132 160 200 220 250 -- -- -- -- -- -- --

690V [kW] 63 75 90 100 150 160 185 315 335 -- -- -- -- -- -- --

1000V [kW] 55 63 100 110 125 132 132 200 220 -- -- -- -- -- -- --

AC-4 at approximately 200,000 operations

230V [A] 38 38 49 55 73 89 100 118 135 -- -- -- -- -- -- --

240V [A] 38 38 49 55 73 89 100 118 135 -- -- -- -- -- -- --

Rated Operational 400/415V [A] 38 38 49 55 73 89 100 118 135 -- -- -- -- -- -- --

Current, Ie

500V [A] 33 33 37 44 53 59 68 78 89 -- -- -- -- -- -- --

690V [A] 33 33 37 44 53 59 68 78 89 -- -- -- -- -- -- --

1000V [A] -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

230V [kW] 11 11 13 15 22 25 30 37 40 -- -- -- -- -- -- --

240V [kW] 11 11 15 15 22 25 32 37 45 -- -- -- -- -- -- --

400V [kW] 20 20 25 30 40 50 55 63 75 -- -- -- -- -- -- --

Rated Operational Power, Pe

415V

[kW] 20 20 25 30 40 50 55 63 75

--

--

--

--

--

--

--

500V [kW] 22 22 25 30 37 40 45 55 63 -- -- -- -- -- -- --

690V [kW] 30 30 32 40 50 55 63 75 80 -- -- -- -- -- -- --

1000V [kW] -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

Max. switching frequency

Ops/h 150 150 150 150 150 150 150 60 60 -- -- -- -- -- -- --

Wye-Delta (60 Hz)

200V [Hp] 50 60 75 100 125 150 200 200 250 -- -- -- -- -- -- --

Rated Operational 230V [Hp] 60 75 100 125 150 200 250 250 350 450 500 -- -- -- -- --

Power, Pe

460V [Hp] 125 150 200 250 350 450 500 500 600 800 -- -- -- -- -- --

575V [Hp] 150 200 250 300 450 500 600 600 700 1000 -- -- -- -- -- --

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

85

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 44 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

UL/CSA Elevator Duty

200V [A] 54 54 77 99 125 149 156 -- -- -- -- -- -- -- -- --

Rated Operational Current, Ie

230V [A] 54 54 77 99 125 149 156 -- -- -- -- -- -- -- -- -- 460V [A] 54 54 77 99 125 149 156 -- -- -- -- -- -- -- -- --

575V [A] 54 54 77 99 125 149 156 -- -- -- -- -- -- -- -- --

200V [Hp] 15 15 20 30 40 40 50 -- -- -- -- -- -- -- -- --

Rated Operational Power, Pe

230V [Hp] 20 20 25 30 40 50 60 -- -- -- -- -- -- -- -- -- 460V [Hp] 40 40 60 75 100 100 125 -- -- -- -- -- -- -- -- --

575V [Hp] 50 50 75 100 125 150 150 -- -- -- -- -- -- -- -- --

UL/CSA HVAC Applications Definite purpose rating (3-phase)

FLA

600V [A] 116 160 200 250 300 350 520 -- -- -- -- -- -- -- -- --

230V [A] 700 960 1200 1500 1800 2100 3120 -- -- -- -- -- -- -- -- --

LRA

460V [A] 580 800 1000 1250 1500 1750 2600 -- -- -- -- -- -- -- -- --

575V [A] 470 640 800 1000 1200 1400 2080 -- -- -- -- -- -- -- -- --

AC resistance heating 600V [A] 160 200 250 300 400 450 520 -- -- -- -- -- -- -- -- --

Star-Delta Starting (50 Hz)

 230V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 -- -- --

 240V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 -- -- --

Rated Operational Current, Ie

400V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 -- -- -- 415V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 -- -- -- 500V [A] 190 225 233 285 433 502 545 692 796 1004 1299 1385 1680 -- -- --

690V [A] 112 161 233 285 433 502 545 606 692 866 1125 1385 1680 -- -- --

1000V [A] -- 103 147 173 173 173 173 268 346 433 519 -- -- -- -- --

230V (1) [kW] 55 75 90 110 132 160 200 200 250 315 400 500 560 -- -- --

240V (1) [kW] 55 75 110 110 132 160 200 200 250 315 400 500 630 -- -- --

400V (1) [kW] 110 132 160 200 250 250 355 400 400 560 710 800 1000 -- -- --

Rated Operational Power, Pe

415V (1) [kW] 110 132 160 200 250 315 355 400 400 560 800 900 1100 --

----

500V (1) [kW] 132 160 160 200 315 355 355 500 500 710 800 1000 1300 -- -- --

690V (1) [kW] 90 132 200 250 400 500 500 560 710 800 1100 1400 1700 -- -- --

1000V (1) [kW] -- 132 200 250 250 250 250 355 500 630 710 -- -- -- -- --

(1) Power ratings at 50 Hz: Preferred values according to IEC 60947-4-1

86

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 45 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Switching of Power Transformers, AC-6a (50 Hz)

Inrush Current Rated transformer

current

=

n

 230V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 -- --

 240V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 -- --

 400V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 -- --

n = 30

 415V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 -- --

 500V [A] 70 79 111 115 143 143 165 200 252 263 286 -- -- 362 -- --

 690V [A] 70 79 111 115 143 143 165 200 252 263 286 -- -- 362 -- --

 1000V [A] -- -- -- -- -- -- -- -- -- -- -- -- --

----

230V [kVA] 28 31 44 46 57 57 66 80 100 105 114 171 209 144 -- --

240V [kVA] 29 33 46 48 59 59 69 83 105 109 119 179 218 150 -- --

400V [kVA] 48 55 77 80 99 99 114 139 175 182 198 298 363 251 -- --

Apparent Power

415V [kVA] 50 56 79 82 102 102 117 142 179 187 203 305 372 257 -- --

500V [kVA] 61 68 96 100 124 124 143 173 218 228 248 -- -- 314 -- --

690V [kVA] 84 94 133 137 171 171 197 239 301 314 342 -- -- 433 -- --

1000V [kVA] -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

n = 20

 690V [A] 105 119 167 173 215 215 248 300 378 395 429 -- -- 543 -- --

n = 15

 690V [A] 140 158 222 230 286 286 330 400 504 526 572 -- -- 724 -- --

60 Hz Peak Inrush/peak rated transformer current

n = 30

 660V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 -- --

200V [kVA] 24 27 38 40 50 50 57 69 87 91 99 149 182 125 -- --

208V [kVA] 25 28 40 41 52 52 59 72 91 95 103 155 189 130 -- --

Apparent Power

240V [kVA] 29 33 46 48 59 59 69 83 105 109 119 179 218 150 -- -- 480V [kVA] 58 66 92 96 119 119 137 166 210 219 238 357 436 301 -- --

600V [kVA] 73 82 115 120 149 149 171 208 262 273 297 447 545 376 -- --

660V [kVA] 80 90 127 131 163 163 189 229 288 301 327 492 599 414 -- --

n = 20

 660V [A] 105 119 167 173 215 215 248 300 378 395 429 645 786 543 -- --

200V [kVA] 36 41 58 60 74 74 86 104 131 137 149 223 272 188 -- --

208V [kVA] 38 43 60 62 77 77 89 108 136 142 155 232 283 196 -- --

Apparent Power

240V [kVA] 44 49 69 72 89 89 103 125 157 164 178 268 327 226 -- -- 480V [kVA] 87 99 139 144 179 179 206 249 314 328 357 536 653 451 -- --

600V [kVA] 109 124 174 180 223 223 258 312 393 410 446 670 817 564 -- --

660V [kVA] 120 136 191 198 246 246 284 343 432 452 490 737 899 621 -- --

n = 15

 660V [A] 140 158 222 230 286 286 330 400 504 526 572 860 1048 724 -- --

200V [kVA] 48 55 77 80 99 99 114 139 175 182 198 298 363 251 -- --

208V [kVA] 50 57 80 83 103 103 119 144 182 190 206 310 378 261 -- --

Apparent Power

240V [kVA] 58 66 92 96 119 119 137 166 210 219 238 357 436 301 -- -- 480V [kVA] 116 131 185 191 238 238 274 333 419 437 476 715 871 602 -- --

600V [kVA] 145 164 231 239 297 297 343 416 524 547 594 894 1089 752 -- --

660V [kVA] 160 181 254 263 327 327 377 457 576 601 654 983 1198 828 -- --

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

87

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 46 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Switching of 3-phase Capacitors, AC-6b (50 Hz)

230V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 -- -- --

240V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 -- -- --

Single capacitor 40 °C

400V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 -- -- -- 415V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 -- -- -- 500V [kVAR] 83 110 140 160 180 210 240 260 325 350 490 550 600 -- -- --

690V [kVAR] 80 110 135 170 200 240 280 300 325 440 600 650 800 -- -- --

1000V [kVAR] -- 100 140 150 155 160 170 250 300 350 450 -- -- -- -- --

230V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 -- -- --

240V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 -- -- --

Single capacitor 55 °C

400V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 -- -- -- 415V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 -- -- -- 500V [kVAR] 83 110 140 160 180 210 240 260 325 350 490 550 600 -- -- --

690V [kVAR] 80 110 135 170 200 240 280 300 325 440 600 650 800 -- -- --

1000V [kVAR] -- 100 140 150 155 160 170 250 300 350 450 -- -- -- -- --

230V [kVAR] 35 42 45 57 70 85 100 105 120 160 190 230 280 -- -- --

240V [kVAR] 35 42 45 57 70 85 100 105 120 160 190 230 280 -- -- --

Single capacitor 70 °C

400V [kVAR] 65 74 83 105 135 155 180 195 225 275 370 430 480 -- -- -- 415V [kVAR] 65 74 83 105 135 155 180 195 225 275 370 430 480 -- -- -- 500V [kVAR] 78 96 102 130 165 196 220 241 300 340 435 530 570 -- -- --

690V [kVAR] 75 110 135 160 200 240 260 300 325 440 600 630 750 -- -- --

1000V [kVAR] -- 95 120 130 140 150 160 220 270 300 400 -- -- -- -- --

60 Hz Single Capacitor (cULus)

208V [kVAR] 33 41 50 67 83 100 125 119 142 178 214 -- 346 -- -- --

Single capacitor 40 °C

240V [kVAR] 38 48 57 77 95 115 144 137 164 205 247 -- 398 -- -- -- 480V [kVAR] 75 100 125 150 200 250 300 274 329 411 494 -- 832 -- -- --

600V [kVAR] 100 125 150 200 250 300 350 343 410 514 618 -- 1040 -- -- --

Switching of Lamps

Gas discharge lamps AC-5a

open

[A] 116 146 190 205 265 305 370 400 460 580 750 877 1072 812 1332 1722

UL Ballast Ratings

[A] 160 200 250 300 400 450 520 -- -- -- -- -- -- -- -- --

Filament AC-5b

230/ 240V

[A] 116 146 190 205 265 305 370 400 460 580 750 877 1072 812 1332 1722

88

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 47 - Main Circuits

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Switching of DC Loads--Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C

 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

90V [A] 160 200 250 350 400 500 520 -- -- -- -- -- -- -- -- -- 1 pole
100V [A] -- -- 250 350 400 500 520 -- -- -- -- -- -- -- -- --

110V [A] -- -- -- -- 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

110V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

2 poles in series

175V [A] 160 200 250 350 400 500 520 600 700 800 1050 -- -- -- -- --

200V [A] -- -- 250 350 400 500 520 600 700 800 1050 -- -- -- -- --

220V [A] -- -- -- -- 400 500 520 600 700 800 1050 -- -- -- -- --

 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

110V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

175V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

220V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

3 poles in series

260V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

300V [A] -- -- 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

340V [A] -- -- -- -- 400 500 520 600 700 800 1050 1350 1650 1250 2050 --

600V [A] -- -- -- -- -- -- -- 600 700 800 1050 1350 1650 1250 2050 --

850V [A] -- -- -- -- -- -- -- -- -- 800 1050 1350 1650 1250 2050 --

Shunt-wound Motors--Starting, reverse current breaking, reversing, stepping DC-3, 60 °C (L/R  2 ms)

24V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

48/60V [A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

3 poles in series

110V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

220V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

600V

[A] -- -- -- -- -- -- -- 600 700 800 1050 -- -- -- -- --

Series-wound Motors--Starting, reverse current breaking, reversing, stepping DC-5, 60 °C (L/R  7.5 ms)

24V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

48/60V [A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

3 poles in series

110V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

220V

[A] 145 160 250 275 350 400 450 600 700 800 1050 -- -- -- -- --

600V

[A] -- -- -- -- -- -- -- 600 700 800 1050 -- -- -- -- --

Short Time Withstand ICW

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

89

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 47 - Main Circuits (Continued)

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

1 s

[A] 1300 1460 1900 2050 2650 3050 3700 4600 4600 7000 7000 10000 12000 8000 12000 12000

10 s

[A] 928 1168 1520 1640 2120 2440 2960 4400 4400 6400 6400 8000 10000 7200 10000 10000

40 °C

30 s

[A] 536 674 878 947 1224 1409 1709 3100 3100 4500 4500 6000 7500 5200 7500 7500

1 min

[A] 379 477 621 670 865 996 1208 2500 2500 3500 3500 4500 5500 4000 5500 5500

15 min [A] 160 225 275 350 400 500 600 840 840 1300 1300 1600 2200 1500 2200 2800

Resistance and Power Dissipation

Main current circuit resistance

[m] 0.469 0.454 0.198 0.204 0.200 0.200 0.200 0.083 0.086 0.050 0.045 0.044 0.029 0.050 0.030 0.028

Power dissipation per pole at Ie AC-1, 400V

[W] 12 23 15 25 32 50 72 30 42 32 50 80 80 80 125 200

Power dissipation per pole at Ie AC-3/ 400V

[W] 6 10 7

8 14 19 27 16 21 17 28 50 50 -- -- --

Total power dissipation at:

Ie AC-3, 400V; AC/DC control (120-250V) [W] 21 33 23.5 26.5 46.5 61.5 85.5 53 68 56 89 171 171 -- -- --

AC-1

ops / hr

300

300

60

300 60 15

Maximum Switching Frequency

AC-3

ops / hr

300

300

60

------

AC-2, AC-4

ops / hr

150

60

60

------

Weight

AC/DC (Electronic) with bar connections

kg 1.50 1.50 3 3 4.64 4.64 4.64 12 12 15 15 34 35 16 35 45 (lbs.) (3.3) (3.3) (6.6) (6.6) (10.2) (10.2) (10.2) (26.4) (26.4) (33) (33) (74.8) (77) (35.2) (77) (99)

with built-in cable clamps

kg 1.75 1.75 (lbs.) (3.85) (3.85)

--

--

--

--

--

--

--

--

--

--

--

--

--

--

90

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 48 - Short-circuit Current Ratings

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1

100 kA Available Fault Current

DIN Fuses - Type "2" (400V) gG

[A] 250 250 315 315 400 500 630 630 630 800 800 1000 1250 -- -- -- 80 kA Available Fault Current

Type "2" (690V)

[A] 160 200 315 315 400 425 500 500 630 800 800 1000 1600 -- -- --

MCCB Type "2" (400V)

70 kA Available Fault Current [A] 160 160 320 320 400 630 630 630 630 800 1000 1600 1600 -- -- --

Short Circuit Current Rating (Max. Fuse or Circuit Breaker Rating) Per UL 60947 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only)

UL Class RK5 Fuses Type 1 Combination (600V)

10 kA Available Fault Current [A] 250 250 400 400 -- -- -- -- -- -- -- -- -- -- -- --

18 kA Available Fault Current

Type 1 Combination (600V)

[A] -- -- -- -- 800 800 800 1000 -- -- -- -- -- -- -- --

UL Class L

Fuses

Type 1 Combination (600V)

30 kA Available Fault Current [A] -- -- -- -- -- -- -- -- 1000 -- -- -- -- -- -- --

85 kA Available Fault Current

Type 1 Combination (600V)

[A] -- -- -- -- -- -- -- -- -- -- -- 1600 2000 -- -- --

UL Class J

and CSA HRCI-J

Type 1 Combination (600V)

Fuses Type 2 Combination (600V)

100 kA Available Fault Current [A] 250 250 400 400 600 600 600 600 600 -- -- -- -- -- -- -- [A] 200 200 400 400 600 600 600 600 600 -- -- -- -- -- -- --

UL Class L Fuses

Type 1 Combination (600V)

Type 2 Combination (600V)

100 kA Available Fault Current [A] -- -- -- -- -- -- -- 800 800 1200 1200 -- -- 1600 -- -- [A] -- -- -- -- -- -- -- -- -- 1200 1200 -- -- -- -- --

42 kA Available Fault Current

Type 1 Combination (480V)

[A] -- -- -- -- -- -- -- -- -- 1200 1200 2000 2000 -- -- --

65 kA Available Fault Current

Type 2 Combination (480V)

[A] 250 250 400 400 800 800 800 800 800 800 800 -- -- -- -- --

84 kA Available Fault Current

Type 1 Combination (480V)

[A] -- -- -- -- -- -- -- 800 800 -- -- -- -- -- -- --

89 kA Available Fault Current

Type 1 Combination (480V)

[A] -- -- -- -- -- -- -- -- -- 800 800 -- -- -- -- --

UL Inverse-

Time

Type 1 Combination (480V)

Circuit

Breaker Type 2 Combination (600V)

100 kA Available Fault Current [A] 250 250 400 400 800 800 800 -- -- -- -- -- -- -- -- --
25 kA Available Fault Current [A] 250 250 -- -- -- -- -- -- -- -- -- -- -- -- -- --

35 kA Available Fault Current

Type 2 Combination (600V)

[A] -- -- 400 400 800 800 800 800 800 800 800 -- -- -- -- --

42 kA Available Fault Current

Type 1 Combination (600V)

[A] -- -- -- -- 800 800 800 800 800 800 800 -- -- -- -- --

50 kA Available Fault Current

Type 1 Combination (600V)

[A] 250 250 -- -- -- -- -- -- -- -- -- -- -- -- -- --

65 kA Available Fault Current

Type 1 Combination (600V)

[A] -- -- 400 400 400 400 400 -- -- -- -- -- -- -- -- --

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

91

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 49 - Coil Data

100/104-E, 100S-E

Operating Limits 50/60 Hz DC control

pick-up dropout pick-up dropout

[x Us] [x Us] [x Us] [x Us]

24...60V AC

pick-up [VA] hold-in [VA]

48...130V AC

pick-up [VA] hold-in [VA]

100...250V AC

pick-up [VA] hold-in [VA]

250...500V AC

pick-up [VA] hold-in [VA]

24...60V DC

pick-up [W]

hold-in

[W]

48...130V DC

pick-up [W]

hold-in

[W]

100...250V DC

pick-up [W]

hold-in

[W]

250...500V DC

pick-up [W]

hold-in

[W]

PLC Interface

Operating Times

AC or DC

closing delay [ms] opening delay [ms]

With PLC Interface

closing delay [ms] opening delay [ms]

116 146
225 5.5 170 4 130 6 205 16 210 2.5 130 2.5 135 3 205 4
20...55 40...70 20...31 24...34

190 205
165 6 175 4 220 7 185 16 205 2.5 130 2.5 190 2.5 190 4
25...60 45...80 25...45 25...45

265 305 370 400 460 580 750

0.85...1.1

0.55

0.80...1.1

0.55

475

--

--

8.5

--

--

340

1215

1100

17

12

12

385

955

880

17.5

12

12

420

950

985

21

12

12

400

900

785

3.5

5

5.5

360

1150

1020

2.5

5

5

410

895

880

4.5

5

5

600

885

910

4.7

7.5

7.5

10 mA @ 24V DC

30...60 45...80 25...45 25...45

50...120 33...70 40...60 10...30

50...120 33...70 40...90 10...30

860 1060 1260 2050 2650

--

--

--

--

--

--

--

1100

--

--

12

--

2450

880

2450

48

12

48

--

985

--

--

12

--

--

785 -- --

--

5.5 -- --

--

1020 -- --

--

5 ----

2290

880

2290

20.5

5

20.5

--

910 -- --

--

7.5 -- --

50...80 35...55 40...65 10...30

50...120 33...70 40...90 10...30

50...80 35...55 40...65 10...30

92

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Conductors

Table 50 - Cross Sections, Screw Type Terminals

100/104-E, 100S/104S-E

9

12

16

26

30

38

40

52

65

80

96

Conductor Cross Sections--Main Contacts Terminal Type

(1)

(2)

(3)

1 conductor

[mm2] 0.75...6 0.75...6 0.75...6 1.5...10 1.5...10 1.5...10 4...35 4...35 4...35 6...50 6...50

2 conductors [mm2] 0.75...6 0.75...6 0.75...6 1.5...10 1.5...10 1.5...10 4...35 4...35 4...35 6...50 6...50

1 conductor

[mm2] 1...6 1...6 1...6 2.5...10 2.5...10 2.5...10 6...35 6...35 6...35 6...70 6...70

2 conductors [mm2] 1...6 1...6 1...6 2.5...10 2.5...10 2.5...10 6...35 6...35 6...35 6...50 6...50

Recommended torque

[N·m] 1.5

1.5

1.5

2.5

2.5

2.5

4

4

4

6

6

Cross Section per UL/CSA

[AWG] 16...10 16...10 16...10 14...8 14...8 14...8 10...2 10...2 10...2 6...1 6...1

Recommended torque

[lb·in] 13

13

13

22

22

22

35

35

35

53

53

Conductor Cross Sections- Coil and Auxiliary Contact

(1)

Terminal Type

1 conductor 2 conductors 1 conductor 2 conductors Recommended torque Cross Section per UL/CSA Recommended torque

[mm2] 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5

[mm2] 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5 0.75...2.5

[mm2] 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5

[mm2] 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5 1...2.5

[N·m] 1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

[AWG] 18...14 18...14 18...14 18...14 18...14 18...14 18...14 18...14 18...14 18...14 18...14

[lb·in] 11

11

11

11

11

11

11

11

11

11

11

(1) Pozidriv No. 2 / Blade No. 3 screw (2) Pozidriv No. 2 / Blade No. 4 screw (3) Hexagonal socket screw

Table 51 - Cross Sections, Screw Type Terminals

100/104-E, 100S-E

116 146 190 205 265 305 370 400 460 580 750 860

1060

1260 2050 2650

Main Terminals

7 10
14.3 10 30 17
25 15.5 40 17

Conductor Cross Sections -- Main Contacts (Terminal type)

13

17.5

Ø 6.5 3

Ø 8.5 5

(1) conductor [mm2] 10...95 10...150

19.5 Ø 10.5 5
16...185

40

25

22.5

22.5

Ø 10.5 Ø 6.5

6

Ø 6.5 Ø 12.5

6

--

--

80 40
27

Ø 13

10

--

50 27

80 40

Ø 13 8
--

Ø 13(AF2050) 10 (AF2650) 25
--

Clamp Type

100-ECL146 100-ETL205 100-ETL370

--

--

--

--

--

Recommended torque

[N·m] 8

34

42

--

--

--

--

--

(2) conductors [mm2] 10...95

--

16...500

70...240 70...240 120...240 70...300

--

--

Clamp Type

100-ECL146 --

100-ETL370B 100-ETL580 100-ETL750 100-ETL860 100-ETL1060 --

--

Recommended torque

[N·m] 8

--

42

31

43

43

57

--

--

(3) conductors [mm2] --

--

--

--

70...500 120...500 70...750 70...240

--

Clamp Type

--

--

--

-- 100-ETL750 100-ETL860 100-ETL1060 100-ETL750

--

Recommended torque

[N·m] --

--

--

--

43

43

57

43

--

(4) conductors [mm2] --

--

--

--

--

120...500 70...750

--

--

Clamp Type

--

--

--

--

-- 100-ETL860 100-ETL1060 --

--

Recommended torque

[N·m] --

--

--

--

--

43

57

--

--

(6) conductors [mm2] --

--

--

--

--

--

70...750

--

--

Clamp Type

--

--

--

--

--

--

100ETL1060B

--

--

Recommended torque

[N·m] --

--

--

--

--

--

57

--

--

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

93

100-E/104-E, 100S-E/104S-E Contactors Specifications

Table 51 - Cross Sections, Screw Type Terminals (Continued)

100/104-E, 100S-E

L max.

L

Ø

Ø min.

Recommended torque

116 146 [mm] 22 [mm] 6 [N·m] 9

190 205 265 305 370 400 460 580 750

24

32

47

50

8

10

10

12

18

28

35

45

860

1060

100

12

45

1260 2050 2650

50

100

12

12

45

45

Cross section per UL/CSA

(1) conductor [AWG] 6...3/0 6...300 (1)

4...400 (1)

--

--

--

--

--

--

Clamp Type

100-ECL146 100-ETL205 100-ETL370

--

--

--

--

--

--

Recommended torque

[lb·in] 80

300

375

--

--

--

--

--

--

(2) conductors [AWG] 6...3/0

--

4...500 (1) 2/0...500 (1) 2/0...500 (1) 4/0...500 (1) 1/0...750 (1) 2/0...500 (1)

--

Clamp Type

100-ECL146 --

100-ETL370B 100-ETL580 100-ETL750 100-ETL860 100-ETL1060 100-ETL750

--

Recommended torque

[lb·in] 80

--

375

275

375

375

500

375

--

(3) conductors [AWG] --

--

--

--

2/0...500 (1) 4/0...500 (1) 1/0...750 (1) 2/0...500 (1)

--

Clamp Type

--

--

--

-- 100-ETL750 100-ETL860 100-ETL1060 100-ETL750

--

Recommended torque

[lb·in] --

--

--

--

375

375

500

375

--

(4) conductors [AWG] --

--

--

--

--

4/0...500 (1) 1/0...750 (1)

--

--

Clamp Type

--

--

--

--

-- 100-ETL860 100-ETL1060 --

--

Recommended torque

[lb·in] --

--

--

--

--

375

500

--

--

(6) conductors [AWG] --

--

--

--

--

--

1/0...750 (1)

--

--

Clamp Type

--

--

--

--

--

--

100ETL1060B

--

--

Recommended torque

[lb·in] --

--

--

--

--

--

500

--

--

L max.

[in] 0.866

0.945

1.26

1.85

1.97

3.94

1.97

3.94

L

Ø

Ø min.

[in] 0.236

0.315

0.394

0.394

0.472

0.472

0.472

0.472

Recommended torque

[lb·in] 80

160

248

310

398

398

398

398

Conductor Cross Sections -- Coil and Auxiliary Contact Terminals (Terminal Type)

(1) conductor [mm2]

0.75...2.5

(2) conductors [mm2]

0.75...2.5

(1) conductor [mm2]

1...4

(2) conductors [mm2]

1...4

Recommended torque

[N·m]

1...1.2

Cross section per UL/CSA Recommended torque

[AWG] [lb·in]

18...14 8.9...10.6

(1) MCM

94

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications

Auxiliary Contacts

Table 52 - Auxiliary Contacts

Internal 100-E09...E16

Switching of AC Loads

Rated Insulation voltage Ui

690V

Rated operational voltage Ue

690V

Rated impulse withstand voltage Uimp

6kV

AC-12 Ith

at 40 °C [A]

16

at 60 °C [A]

--

24V [A]

--

AC-14 at rated voltage of

42/48V [A]

--

120V [A]

--

24V [A]

6

42/48V [A]

6

120V [A]

6

230V [A]

4

AC-15 at rated voltage of

240V [A]

4

400V [A]

3

415V [A]

3

500V [A]

2

690V [A]

2

Switching of DC Loads

24V DC [A]

--

48V DC [A]

--

DC-12 L/R< 1 ms resistive loads at

110V DC [A]

--

220V DC [A]

--

440V DC [A]

--

24V DC [A]

--

48V DC [A]

--

DC-14 L/R< 15 ms inductive loads with economy resistor in series at

110V DC [A]

--

220V DC [A]

--

440V DC [A]

--

24V DC [A]

6

48V DC [A] 2.8

DC-13 switching electromagnets at

110V DC [A] 0.55

220V DC [A] 0.27

440V DC [A] 0.13

Fuse gG

Short-circuit protection with no welding of contacts per IEC 60947-5-2

[A]

10

[A]

10

Protective Separation per IEC 60947-1, Annex N

Min. switching capacity at 12V IEC 60947-5-4

[mA]

3

Min. switching capacity at 3V IEC 60947-5-4

[mA]

--

Load Carrying Capacity per UL/CSA

Rated voltage

AC [V] 600

Continuous rating

40 °C [A]

10

Switching capacity

AC

A600

Rated voltage

DC [V] 600

Continuous rating

40 °C [A] 2.5

Switching capacity

DC

Q600

Standard 100-EF/ESA*
690V 690V 6kV
16 -- -- -- -- 6 6 6 4 4 3 3 2 2
-- -- -- -- -- -- -- -- -- -- 6 2.8 0.55 0.27 0.13
10 10
3 --
600 10 A 600 600 2.5 Q 600

Auxiliary contact for 100/104-E, 100S-E
Severe Appl. Severe Appl. Standard 100-ES*B/B3 100-ES*B/B3 100-ES1/2*

250V

250V

690V

125V

250V

690V

--

--

6kV

0.1

2

16

--

--

--

0.1

--

--

0.1

--

--

0.1

--

--

--

2

6

--

2

6

--

2

6

--

2

4

--

2

4

--

--

3

--

--

3

--

--

2

--

--

2

0.1

2

--

0.1

1

--

0.1

0.2

--

--

0.1

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

3

--

--

1.5

--

--

0.55

--

--

0.3

--

--

--

0.1

10

10

0.1

10

10

--

--

50

--

1

--

125

250

600

0.1

2

10

--

--

A 600

110

220

250

0.1

0.1

2.5

--

--

P 600

Standard 100-ES3/4*
690V 690V 6kV
16 -- -- -- -- 6 6 6 4 4 3 3 2 2
-- -- -- -- -- -- -- -- -- -- 6 2.8 0.55 0.3 --
10 10
50 --
600 10 A 600 250 2.5 Q 300

Low Power 100-ES*-B*
250V 125V 1.5kV 0.1 -- 0.1 0.1 0.1 -- -- -- -- -- -- -- -- --
0.1 0.1 0.1 -- -- -- -- -- -- -- -- -- -- -- --
0.1 0.1
-- 1
125 0.1 -- 125 0.1 --

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

95

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves
Life-Load Curves

3-pole Contactors -- Electrical Durability
Figure 27 - Electrical durability for AC-1 utilization category - Ue  690V Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of the load.

Ambient temperature (see page 83) and maximum electrical switching frequency (see page 90).

E09 E12 E16
10

E26 E30, E38

E40 E52 E65 E80, E96

E116

E146 E190 E205 E265 E305 E370

E400 E460 E580 E750

5

3

9

7

5

3

2

9

1

7

5

3

1
1

Millions of operating cycles

0.5

0.3

9

7

5

3

0.2

1

0.1

2

3

5

1 3 5 79

1 59

1 3 5 79

10

20

30

50

26.5

Breaking current Ic [A]

1 3 579

1 3 5 79

1 3 579

1 59

100

200 300

500

1000

Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles.

96

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves

Figure 28 - Electrical durability for AC-3 utilization category - Ue  440V

Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated operational current Ie (Ie = motor full load current).

For ambient temperature (see page 83) and maximum electrical switching frequency (see page 90).

E09

E12

10

E16

E26 E30, E38

E40

E52 E65 E80, E96

E116 E146 E190 E205 E265 E305 E370 E400 E460 E580 E750

Millions of operating cycles

5

3

9

7

5

3

2

9

1

1.8 7

5

3

1
1

0.5

1 3 5 79
0.3

0.2

2

3

5

1 3 5 79

1 59

1 3 5 79

10

20

1 59

30

50 55

Breaking current Ic [A]

1 3 579

1 3 5 79

1 3 579

100

200 300

500

1000

Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles.

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

97

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves

Figure 29 - Electrical durability for AC-3 utilization category - 440V < Ue  690V
Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated operational current Ie (Ie = motor full load current).

For ambient temperature (see page 83) and maximum electrical switching frequency (see page 90).

E09 E12 E16
10

E26 E30, E38

E40

E52 E65 E80, E96

E116

E146 E190 E205 E265E305

E370E400E460 E580 E750

Millions of operating cycles

5

3

9

7

5

3

2

9

1

7

1.5

5

3

1
1

0.5

0.3

0.2 1 3 5 7 9

2

3

5

1 3 5 79

1 59

1 3 5 79

10

20

1 3 579

30

50

Breaking current Ic [A]

1 3 579

1 3 5 79

1 3 579

100 140 200 300

500

1000

Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles.

98

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves

Figure 30 - Electrical durability for AC-2 or AC-4 utilization category - Ue  440V

Switching cage motors: starting, reverse operation and step-by-step operation. The breaking current Ic is equal to 2.5 x Ie for AC-2 and 6 x Ie for AC-4, keeping in mind that Ie is the motor rated operational current (Ie = motor full-load current). For maximum electrical switching frequency (see page 90).

E80, E96

E38

E116, E146

E190 E205 E265E305E370

E400 E460 E580 E750

E52 E65

E30, E40

E26

E16

E09 E12

10

5

3

29

7 5

3

1

1

Millions of operating cycles

0.5
0.3
0.2 9
7 5 3
0.1 1

0.05
0.03
0.02 9
7 5 3
0.01 1

0.005

23

5

1 3 579

1 3 579

1 3 579

10

20 30

1 3 579

50

100

200 300 500

Breaking current Ic [A]

1 3 579

1000

2000 3000 5000

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

99

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves
Figure 31 - Electrical durability for AC-2 or AC-4 utilization category - 440V < Ue  690V
Switching cage motors: starting, reverse operation and step-by-step operation. The breaking current Ic is equal to 2.5 x Ie for AC-2 and 6 x Ie for AC-4, keeping in mind that Ie is the motor rated operational current (Ie = motor full load current). For maximum electrical switching frequency (see page 90).

E09 E12 E16 E26 E30 E38 E40 E52 E65 E80, E96

Millions of operating cycles

10

5

3

29

7 5

3

1

1

0.5
0.3
0.2 9
7 5 3
0.1 1
0.05
0.03
0.02 9
7 5 3
0.01 1

0.005

23

5

E116E146 E190 E205E265E305 E370 E400E460 E580E750

1 3 579 1 3 579

10

20 30

1 3 579

50

100

200 300 500

Breaking current Ic [A]

1 3 579

1000

2000 3000 5000

100

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Figure 32 - Mounting Position for 100-E09...100-E96 Devices-- AC/DC and AC/DC with PLC input

Position 2

+30° -30°

Position 4

Position 3

Position 1

Position 1 ± 30°

Position 5

9...16 A Contactors

Figure 33 - 100-E09...100-E16 Contactors with Standard Coils

77 (3.03)

6 (0.24)

45 (1.77)

71 (2.80) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

Figure 36 - 100-E09...100-E16 Contactors with Standard Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

77 (3.03) 71 (2.80) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 34 - 100-E09...100-E16 Contactors with Low-consumption Coils

77 (3.03)

6 (0.24)

45 (1.77)

71 (2.80) 5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 37 - 100-E09...100-E16 Contactors with Low-consumption Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 35 - 100-E09...100-E16 Contactors with Standard Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

110.5 (4.35) 71 (2.80)
5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 38 - 100-E09...100-E16 Contactors with Low-consumption Coils and Side-mounted Auxiliary Contact

77 (3.03)

12 (0.47)

45 (1.77)

6 (0.24)

71 (2.80) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

10 (0.39)
101

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 39 - 104-E09...104-E16 Reversing Contactors with Cat. No. 100-EMCA02 Mechanical and Electrical Interlock

90 (3.54)

102.5 (4.04) 71 (2.80)
5.5 (0.22)

91.5 (3.60)

35 mm EN/IEC 60715

43 (1.69) 10 (0.39)

Figure 40 - Drilling Template for 9...16 A Contactors

35 (1.38) ø 4.2 (0.17)

2 x M4 8...32 UNC

80 (3.15)

2 x M4 8...32 UNC

60 (2.36)

70 (2.76)

60 (2.36)

5 (0.20)

5 (0.20)

Non reversing contactors

70 (2.76)

ø 4.2 (0.17)

5 (0.20)

Reversing contactors

5 (0.20)

26...38 A Contactors

Figure 41 - 100-E26...100-E38 3-Pole Contactors with Standard Coils

6 (0.24)

45 (1.77)

86 (3.39) 80 (3.15) 5.5 (0.22)

Figure 43 - 100-E26...100-E38 3-Pole Contactors with Lowconsumption Coils

6 (0.24)

45 (1.77)

86 (3.39) 80 (3.15) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 42 - 100-E26...100-E38 4-Pole Contactors with Standard Coils

6 (0.24)

45 (1.77)

101 (3.98) 96 (3.74) 5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 44 - 100-E26...100-E38 4-Pole Contactors with Lowconsumption Coils

6 (0.24)

45 (1.77)

101 (3.98) 96 (3.74) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

10 (0.39)

10 (0.39)

For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

102

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Figure 45 - 100-E26...100-E38 3-Pole Contactors with Standard Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

119.5 (4.70) (4-Pole aux. contact) 111.5 (4.39) (2-Pole aux. contact)
80 (3.15) 5.5 (0.22)

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 49 - 100-E26...100-E38 3-Pole Contactors with Lowconsumption Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

119.5 (4.70) (4-Pole aux. contact) 111.5 (4.39) (2-Pole aux. contact)
80 (3.15) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 46 - 100-E26...100-E38 4-Pole Contactors with Standard Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

135.5 (5.33) (4-Pole aux. contact) 127.5 (5.02) (2-Pole aux. contact)
96 (3.74) 5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 50 - 100-E26...100-E38 4-Pole Contactors with Lowconsumption Coils and Front-mounted Auxiliary Contact

6 (0.24)

45 (1.77)

135.5 (5.33) (4-Pole aux. contact) 127.5 (5.02) (2-Pole aux. contact)
96 (3.74) 5.5 (0.22)

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 47 - 100-E26...100-E38 3-Pole Contactors with Standard Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

86 (3.39) 80 (3.15) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

80 (3.15)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 51 - 100-E26...100-E38 3-Pole Contactors with Lowconsumption Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

86 (3.39) 80 (3.15) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 48 - 100-E26...100-E38 4-Pole Contactors with Standard Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

101 (3.98) 96 (3.74) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

5.5 (0.22)

For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth
Rockwell Automation Publication 100-TD013J-EN-P - April 2021

10 (0.39)
103

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 52 - 100-E26...100-E38 4-Pole Contactors with Lowconsumption Coils and Side-mounted Auxiliary Contact

12 (0.47)

45 (1.77)

6 (0.24)

101 (3.98) 96 (3.74) 5.5 (0.22)

69.4 (2.73)

80 (3.15)
35 mm EN/IEC 60715

5.5 (0.22)

10 (0.39)
For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

Figure 53 - 104-E26...104-E38 Reversing Contactors with Cat. No. 100-EMCA02 Mechanical and Electrical Interlock

90 (3.54)

111.5 (4.39) 80 (3.15) 5.5 (0.22)

91.5 (3.60)

35 mm EN/IEC 60715

5.5 (0.22)

43 (1.69) 10 (0.39)

Figure 54 - Drilling Template for 26...38 A Contactors

35 (1.38) ø 4.2 (0.17)

2 x M4 8...32 UNC

80 (3.15)

2 x M4 8...32 UNC

60 (2.36)

70 (2.76)

60 (2.36)

70 (2.76)

5 (0.20)

5 (0.20)

Non reversing contactors

ø 4.2 (0.17)

5 (0.20)

Reversing contactors

5 (0.20)

40...65 A Contactors

Figure 55 - 100-E40...100-E65 3-Pole Contactors

6 (0.24)

55 (2.17)

111 (4.37)

7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

Figure 56 - 100-E40...100-E65 3-Pole Contactors with Frontmounted Auxiliary Contact

6 (0.24)

55 (2.17)

7 (0.28)

144 (5.67) (4-Pole auxiliary contact) 136 (5.35) (2-Pole auxiliary contact) 111 (4.37)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

43 (1.69)

10 (0.39)

10 (0.39)

104

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Figure 57 - 100-E40...100-E65 3-Pole Contactors with Sidemounted Auxiliary Contact

12 (0.47)

55 (2.17)

6 (0.24)

7 (0.28)

111 (4.37)

69.4 (2.73)

119.5 (4.70)
5.5 (0.22) 35 mm EN/IEC 60715

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 60 - 100-E40...100-E52 4-Pole Contactors

6 (0.24)

70 (2.76)

113.5 (4.47)

7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

Figure 58 - 104-E40...104-E65 Reversing 3-Pole Contactors

110 (4.34)

7 (0.28)

111 (4.37)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

Figure 61 - 100-E40...100-E52 4-Pole Contactors with Frontmounted Auxiliary Contact

6 (0.24)

70 (2.76)

7 (0.28)

147 (5.79) (4-Pole auxiliary contact) 139 (5.47) (2-Pole auxiliary contact)
113.5 (4.47)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

43 (1.69)

10 (0.39)

Figure 59 - Drilling Template for 40...65 A 3-Pole Contactors

35 (1.38) ø 4.2 (0.17)

2 x M4 8...32 UNC

80 (3.15)

2 x M4 8...32 UNC

60 (2.36)

70 (2.76)

60 (2.36)

5 (0.20)

5 (0.20)

Non reversing contactors

70 (2.76)

ø 4.2 (0.17)

5 (0.20)

Reversing contactors

5 (0.20)

10 (0.39)

Figure 62 - 100-E40...100-E52 4-Pole Contactors with Sidemounted Auxiliary Contact

70 (2.76)

6 (0.24)

113.5 (4.47)

12 (0.47)

7 (0.28)

69.4 (2.73)

119.5 (4.70)
5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

Figure 63 - Drilling Template for 40...52 A 4-Pole Contactors

60 (2.36) ø 6.4 (0.25)

2 x M6 1/4...20 UNC

110 (4.33)
100 (3.94)

4.6 (0.18)
5 (0.20)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

105

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

80...96 A Contactors

Figure 64 - 100-E80...100-E96 3-Pole Contactors

6 (0.24)

70 (2.76)

116 (4.57) 7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

Figure 66 - 100-E80...100-E96 3-Pole Contactors with Sidemounted Auxiliary Contact

12 (0.47)

70 (2.76)

6 (0.24)

116 (4.57) 7 (0.28)

69.4 (2.73)

119.5 (4.70)
5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

Figure 65 - 100-E80...100-E96 3-Pole Contactors with Frontmounted Auxiliary Contact

6 (0.24)

70 (2.76)

149 (5.87) (4-Pole auxiliary contact) 116 (4.57)
7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

43 (1.69)

10 (0.39)

Figure 67 - 104-E80...104-E96 Reversing 3-Pole Contactors

6 (0.24)

140 (5.51)

116 (4.57) 7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

10 (0.39)

Figure 68 - Drilling Template for 80...96 A 3-Pole Contactors

60 (2.36)

2 x M6 1/4...20 UNC

130 (5.12)

M6 1/4...20 UNC

110 (4.33)
100 (3.94)

110 (4.33)
100 (3.94)

ø 6.4 (0.25)

5 (0.20)

4.6 (0.18)

Non reversing contactors

4.6 (0.18)

ø 6.4 (0.25)

5 (0.20)

Reversing contactors

Figure 69 - 100-E80 4-Pole Contactors

6 (0.24)

90 (3.54)

116 (4.57) 7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)

Figure 70 - 100-E80 4-Pole Contactors with Front-mounted Auxiliary Contact

6 (0.24)

90 (3.54)

149 (5.87) (4-Pole auxiliary contact)
116 (4.57) 7 (0.28)

119.5 (4.70)

5.5 (0.22) 35 mm EN/IEC 60715

43 (1.69) 10 (0.39)

106

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Figure 71 - 100-E80 4-Pole Contactors with Side-mounted Auxiliary Contact

12 (0.47)

90 (3.54)

6 (0.24)

116 (4.57) 7 (0.28)

119.5 (4.70)

69.4 (2.73)

5.5 (0.22) 35 mm EN/IEC 60715

10 (0.39)
116...2650 A Contactors
Figure 73 - Mounting Position for 100-E116...100-E2650 Devices-- AC/DC and AC/DC with PLC input
30°

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 72 - Drilling Template for 80 A 4-Pole Contactors

80 (3.15) ø 6.4 (0.25)

2 x M6 1/4...20 UNC

110 (4.33)
100 (3.94)
4.6 (0.18) 5 (0.20)
Non reversing contactors

Figure 76 - 104-E116E..., 104-E146E... Reversing Contactors with Cat. No. 100-EM... Mechanical Interlock

180 (7.09)

126 (4.96)

180° 120°

180°

150 (5.91)

Figure 74 - 100-E116K..., 100-E146K... Contactors

10 (0.39)

90 (3.54)

126 (4.96)

150 (5.91)

D 55.5 (2.18)

19.5 (0.77)

Figure 77 - Drilling Template for 116...146 A 3-Pole Contactors

30 (1.18) M4 (8...32 UNC)

8 x M4 30 (1.18) 60 (2.36) 30 (1.18) (8...32 UNC)

100 (3.94)

100 (3.94)

30 (1.18)
Figure 75 - 100-E116E..., 100-E146E... Contactors with PLC Input

10 (0.39)

90 (3.54)

142.5 (5.61)

150 (5.91)

D 55.5 19.5 (2.18) (0.77)

Non reversing contactors

Reversing contactors

30 (1.18)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

107

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 78 - 100-E190, 100-E205 Contactors

10 (0.39)

105 (4.13)

ø 8.5 (0.33)

35.5 (1.40)

152 (5.98) 5 (0.20)

Figure 81 - Drilling Template for 190...205 A 3-Pole Contactors

35 (1.36) M5 (10...24 UNC)

6 x M5 35 (1.36) 70 (2.76) 35 (1.36) (10...24 UNC)

165 (6.50)

165 (6.50)

196 (7.72) 83.5 (3.29) 29.5 (1.16)

35 (1.38)

Figure 79 - 100-E190E, 100-E205E Contactors with PLC Input

10 (0.39)

105 (4.13)

ø 8.5 (0.33)

35.5 (1.40)

169.5 (6.67) 5 (0.20)

Non reversing contactors

Reversing contactors

Figure 82 - 100-E265...100-E370 Contactors

10 (0.39)

140 (5.51) 19.5 (0.77)

ø 10.5 (0.41)

35.5 (1.40)

180 (7.09) 5 (0.20)

94.7 (3.73) 33.4 (1.31)

83.5 (3.29) 29.5 (1.16) 225 (8.86)

196 (7.72)

35 (1.38)

Figure 80 - 104-E190, 104-E205 Reversing Contactors with Cat. No. 100-EM... Mechanical Interlock

210 (8.27)

152 (5.98)

43.75 (1.72)

Figure 83 - 100-E265E...100-E370E Contactors with PLC Input

10 (0.39)

140 (5.51) 19.5 (0.77)

ø 10.5 (0.41)

35.5 (1.40)

195.5 (7.70) 5 (0.20)

94.7 (3.73) 33.4 (1.31)

225 (8.86)

196 (7.73)
43.75 (1.72)

108

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 84 - 104-E265...104-E370 Reversing Contactors with Cat. No. 100-EM... Mechanical Interlock

210 (8.27)

152 (5.98)

196 (7.73)

Figure 85 - Drilling Template for 265...370 A 3-Pole Contactors

43.75 (1.72) M5 (10...24 UNC)

8 x M5 43.75 (1.72) 96.25 (3.79) 43.75 (1.72) (10...24 UNC)

187 (7.36) 187 (7.36)

Non reversing contactors

Reversing contactors

Figure 86 - 100-E400, 100-E460 Contactors with PLC Input

186 (7.32)
25(0.98) 22.5 (0.89) ø 6.5 (0.26)

ø 10.5 (0.41)

48.5 (1.91)

216 (8.5) 6 (0.24)

268 (10.55) 11.5 (0.45)
278 (10.94)

63 (2.48)

248 (9.76)

63 (2.48)
332 (13.1) M5 (10-24 UNC)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

109

273 (10.75) 11.5 (0.45)
283 (11.14) 249 (9.8)
347 (13.7)

344 (13.54) 313 (12.32) 263 (10.35)
249 (9.8) 249 (9.8)

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 87 - 100-E580...100-E750 Contactors with PLC Input

40 (1.57)

210 (8.27) 22.5 (0.89)

ø 6.5 (0.26)

ø 12.5 (0.49)

48.5 (1.91)

242 (9.53) 6 (0.24)

72 (2.83)

Figure 88 - 100-E1260 Contactors with PLC Input

50 (1.97)

27

72 (2.83)

ø 7 (0.28)

242 (9.53)

ø 7 (0.28)

72 (2.83) 72 (2.83) 210 (8.27)

46.5 8 (0.31) (18.3)

72 (2.83) M6 (1/4-20 UNC)
72 (2.83) M6 (1/4-20 UNC)

110

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions

Figure 89 - 100-E860, 100-E1060, 100-E2050, 100-E2650 Contactors with PLC Input

13 (0.51)

40 (1.57) 27 (1.06)
E860, E1060

ø 13 (0.51)
17 (0.67) 30 (1.18) 10 (0.39)

40 (1.57)

17 (0.67) 40 (1.57)

E2050, E2650

136 (5.35)

136 (5.35)

A B C
244 (9.61) BC

E860, E1060, E2050 392 (15.43 47 (1.85) 10 (0.39)

E2650 422 (16.61 53(2.09) 25 (0.98)
136 (5.35)

312 (12.28)

312 (12.3)

A

80 (3.15)
101 (3.98)

136 (5.35) 438 (17.24)

ø 9 (0.35)

4 0 (1.57)

M8 (5/16-18 UMC)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

111

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions
Notes:

112

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

IEC Contactor Specifications Technical Data

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

Resource
Rockwell Automation Global SCCR Tool, rok.auto/sccr
UL Standards Listing for Industrial Control Products, publication CMPNTS-SR002 American Standards, Configurations, and Ratings: Introduction to Motor Circuit Design, publication IC-AT001 Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002
Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control, publication SGI-1.1
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications.

Description
Provides coordinated high-fault branch circuit solutions for motor starters, soft starters, and component drives.
Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure that they conform to the requirements of Underwriters Laboratories.
Provides an overview of American motor circuit design based on methods that are outlined in the NEC.
Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solid-state components.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 100-TD013J-EN-P - April 2021

113

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC)

Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.

rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature
rok.auto/pcdc

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.

Allen-Bradley, expanding human possibility, FactoryTalk, Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.. Kar Plaza  Merkezi E Blok Kat:6 34752, çerenköy, stanbul, Tel: +90 (216) 5698400 EEE Yönetmeliine Uygundur

Publication 100-TD013J-EN-P - April 2021
Supersedes Publication 100-TD013I-EN-P - February 2021

Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.


Acrobat Distiller 21.0 (Windows)