Datasheet for Bard models including: LC6000 Series, PLC Lead Controller, Lead Controller, Lag Controller, Controller

7960-791(E) (2020 12)

LC6000

7960-791(E) (2020 12)

Manual: 7960-791E Supersedes: 7960-791D Date: 12-14-20. Modbus Supplemental Manual for LC6000 Controller SUPPLEMENTAL INSTRUCTIONS. 5. Press ENTER key to scroll down the screen (see Figure 1). Press the UP or DOWN keys to change . the value of each parameter to match the setting . required for the network the LC will be added to. 6.

Modbus Supplemental Manual for LC6000 Controller. This Modbus list is valid for LCS6000.3.2.0. ... Wall Unit Software Version Y. Name. Manual 7960-791E. Page.

Modbus Supplemental Manual for LC6000 Controller - Bard ...

This Modbus list is valid for LCS6000.3.2.0. 7960-791 is valid for LCS6000.1.1.0. 7960-791A is valid for LCS6000.2.000 through.

Not Your Device? Search For Manuals / Datasheets:

File Info : application/pdf, 19 Pages, 2.56MB

Document
7960-791
SUPPLEMENTAL INSTRUCTIONS

Modbus Supplemental Manual for LC6000 Controller

This Modbus list is valid for LCS6000.3.2.0
7960-791 is valid for LCS6000.1.1.0
7960-791A is valid for LCS6000.2.000 through LCS6000.2.1.0
7960-791B is valid for LCS6000.3.000 through LCS6000.3.1.0
The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will respond to Modbus commands allowing access to setpoints, alarms, temperature measurements and humidity measurements for each zone.
The controller has the following connection settings:
Protocol: Modbus TCP/IP
Address: 1
Timeout: 3000 ms
IP Address: 192.168.0.14
Subnet: 255.255.255.0
The IP settings are defaulted to the values listed above; however, in general for remote monitoring of these values the IP settings will have to be adjusted to match the shelter network settings.
To change the IP settings of the LC6000:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 1313.
3. Press UP or DOWN keys to scroll to Settings; press ENTER key.
4. Press UP or DOWN keys to scroll to Network Config; press ENTER key.

5. Press ENTER key to scroll down the screen (see Figure 1). Press the UP or DOWN keys to change the value of each parameter to match the setting required for the network the LC will be added to.
6. Once settings have been entered, change Update Config? from No to Yes to save the settings. Figure 1
The units of the values retrieved during communication are determined by the controller unit of measure setting. This is configured onsite and cannot be changed remotely. The values on the Modbus list are in degrees Fahrenheit. When the unit of measure is changed by the user, the temperature values in the Modbus will change to degrees Celsius. For more information about how to use each of these values, please refer to the latest version of the 2100-669 LC6000 Service Instructions manual.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com

Manual:

7960-791E

Supersedes: 7960-791D

Date:

12-14-20

Page

1 of 19

Unit Status Message

Unit Status Message
Orphan Mode th_Tune_Online LC Online N/A Continuous Blower Off by th_Tune Power Loss Mode Inverter Mode Freecooling Optimized Mode Cooling Heating Active Dehum Self Test PT Online Off by Alarm Off by BMS Off by Time Band Off by Digital Input Off by LC N/A Off by Keypad Manual Mode Emergency Vent Emergency Cool Emergency Off Passive Dehum Standalone Mode Model Invalid Off by Standalone Display Comfort Mode

ID

MULTI- FUSION- MEGA-

TEC

TEC

TEC

1

X

X

X

2

X

-

-

3

X

X

X

4

-

-

-

5

X

X

X

6

X

-

-

7

-

X

-

8

-

X

-

9

X

X

X

10

X

X

X

11

X

X

X

12

X

X

X

13

X

X

X

14

X

X

X

15

X

X

X

16

X

X

X

17

-

X

-

18

-

X

-

19

-

X

-

20

X

X

X

21

-

-

-

22

X

X

X

23

-

X

-

24

X

X

X

25

X

X

X

26

X

X

X

27

X

X

X

28

-

-

X

29

X

X

X

30

-

-

X

31

-

-

X

Manual 7960-791E Page 2 of 19

Unit of Measure BMS

ID

NC

0

SI

1

USA

2

UK

3

CANADA

4

LON

5

Continuous Blower

ID

No Units

0

Lead Unit

1

All Units

2

Custom

3

Rotation Type

ID

FIFO

0

LIFO

1

Demand

2

Dehum Type

ID

None

0

Electric Reheat

1

Mechanical Reheat

2

Cyclic Reheat

3

Humidity Setup

ID

None

0

Zone 1

1

Zones 1 & 2

2

Zones 1, 2 & 3

3

Humidity Type

ID

Relay

0

Comm

1

LC6000 Unit of Measure

ID

NC

0

SI

1

USA

2

UK

3

CANADA

4

LON

5

Unit Type

ID

None

0

MULTI-TEC

2

MEGA-TEC

4

WR

5

Compressor Status

ID

Compressor Off

0

Compressor Start-Up

1

Compressor On or at 25%

2

Compressor at 50%

3

Compressor at 75%

4

Compressor at 100%

5

Compressor Forced Off

6

Compressor Limited to 25%

7

Compressor Limited to 50%

8

Compressor Limited to 75%

9

Compressor Off by Alarm

10

Compressor Off by Time

11

Compressor On by Time

12

Manual Mode

13

Compressor On by Pump-Down 14

Manual 7960-791E

Page

3 of 19

Modbus Register List ­ LC6000

The Modbus Register List table beginning on page 5 describes all of the Modbus points that are available through the LC6000.
Coil (Read/Write) ­ The LC6000 only has one coil available and it is used to turn off the system remotely.
Holding Register (Read/Write) ­ The holding registers are used to change settings on the controller remotely that alter the way the controller functions.
Discrete Input and Input Registers (Read Only) ­ These points are used to monitor the status or value of the LC6000 and/or wall units.

Register Range
0-99 100-199 200-299 300-399 1000-1999 2000-2999 3000-3999 4000-4999 5000-5999 6000-6999 7000- 7999 8000-8999 9000-9999 10000-10999 11000-11999 12000-12999 13000-13999 14000-14999

Group
General Zone 1 Zone 2 Zone 3 Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 Unit 8 Unit 9 Unit 10 Unit 11 Unit 12 Unit 13 Unit 14

Manual 7960-791E Page 4 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

System Off/On

Coil

Generator Alarm

DiscreteInput

Emergency Off Input Status

DiscreteInput

Generator Inputs Status DiscreteInput

Emergency Vent Input Status

DiscreteInput

LC6000 Outdoor Temperature Sensor Failure

DiscreteInput

LC6000 Outdoor Humidity Sensor Failure

DiscreteInput

Bard Guard Alarm

DiscreteInput

Unit 1 Offline

DiscreteInput

Unit 2 Offline

DiscreteInput

Unit 3 Offline

DiscreteInput

Unit 4 Offline

DiscreteInput

Unit 5 Offline

DiscreteInput

Unit 6 Offline

DiscreteInput

Unit 7 Offline

DiscreteInput

Unit 8 Offline

DiscreteInput

Unit 9 Offline

DiscreteInput

Unit 10 Offline

DiscreteInput

Unit 11 Offline

DiscreteInput

Unit 12 Offline

DiscreteInput

Unit 13 Offline

DiscreteInput

Unit 14 Offline

DiscreteInput

Zone 1 Emergency Off Alarm

DiscreteInput

Zone 1 Emergency Ventilation Alarm

DiscreteInput

Zone 1 Indoor Temperature Sensor Failure

DiscreteInput

Zone 1 Remote Temperature Sensor Failure

DiscreteInput

0-1

Off / On = 0 / 1

0

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

0

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

3

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 4

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 5

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 7

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 8

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 9

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 10

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 11

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 12

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 13

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 14

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 15

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 16

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 17

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 18

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 19

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 20 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 100 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

### = ### 101 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

102

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0-1

Off / On = 0 / 1

103

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Manual 7960-791E

Page

5 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 6 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Zone 1 Humidity Sensor Failure

DiscreteInput

0-1

### = ### 104 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Low Temperature Alarm

DiscreteInput

0-1

### = ### 105 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Temperature Alarm

DiscreteInput

0-1

### = ### 106 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Temperature 2 Alarm

DiscreteInput

0-1

### = ###

107

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Low Humidity Alarm

DiscreteInput

0-100%

###.# = ###

108

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Humidity Alarm

DiscreteInput

0-1

### = ###

109

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 No temperature sensors present

DiscreteInput

0-1

### = ###

110

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Emergency Off Alarm

DiscreteInput

0-1

### = ###

200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Emergency Ventilation Alarm

DiscreteInput

0-1

### = ###

201

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Indoor Temperature Sensor Failure

DiscreteInput

0-1

Off / On = 0 / 1

202

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Humidity Sensor Failure

DiscreteInput

0-1

### = ###

204

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Low Temperature Alarm

DiscreteInput

0-1

### = ###

205

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Temperature Alarm

DiscreteInput

0-1

### = ###

206

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Temperature 2 Alarm

DiscreteInput

0-1

### = ###

207

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Low Humidity Alarm

DiscreteInput

0-100%

###.# = ###

208

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Humidity Alarm

DiscreteInput

0-1

### = ###

209

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 No temperature sensors present

DiscreteInput

0-1

### = ###

210

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Emergency Off Alarm

DiscreteInput

0-1

### = ###

300

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Emergency Ventilation Alarm

DiscreteInput

0-1

### = ###

301

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Indoor Temperature Sensor Failure

DiscreteInput

0-1

Off / On = 0 / 1

302

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Humidity Sensor Failure

DiscreteInput

0-1

### = ###

304

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Zone 3 Low Temperature Alarm

DiscreteInput

0-1

### = ###

305

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Temperature Alarm

DiscreteInput

0-1

### = ###

306

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Temperature 2 Alarm

DiscreteInput

0-1

### = ###

307

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Low Humidity Alarm

DiscreteInput

0-100%

###.# = ###

308

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Humidity Alarm

DiscreteInput

0-1

### = ###

309

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 No temperature sensors present

DiscreteInput

0-1

### = ###

310

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Modbus List Unit of Measure

HoldingRegister

0-5

### = ###

0

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE UNIT OF MEASURE TABLE

Zone 1 Cooling Setpoint HoldingRegister (HeatSP + 8)-95

###.# = ###

100

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Heating Setpoint HoldingRegister 32 - (CoolSp - 8)

###.# = ###

101

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Humidity Setpoint

HoldingRegister

0-100%

###.# = ###

102

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Dehumidification Off Sepoint

HoldingRegister

46-99%

###.# = ###

103

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Low Temperature Alarm Setpoint

HoldingRegister

28-65

###.# = ###

104

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Temperature Alarm Setpoint

HoldingRegister

70-120

###.# = ###

105

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Temperature 2 Alarm Setpoint

HoldingRegister

70-120

###.# = ###

106

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Low Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

107

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 High Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

108

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Continuous Blower Setting

HoldingRegister

0-3

### = ###

109

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE CONT BLOWER TABLE

Zone 1 Rotation Setting HoldingRegister

0-2

### = ###

110

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- SEE ROTATION TABLE

Zone 1 Dehumidification Type Setting

HoldingRegister

0-3

### = ###

111

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE DEHUM TYPE TABLE

Zone 1 Passive Dehumidification Setpoint

HoldingRegister

46-99%

###.# = ###

112

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Manual 7960-791E

Page

7 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 8 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Zone 1 Active Dehumidification Setpoint

HoldingRegister

46-99%

###.# = ###

113

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Freecooling On Delay

HoldingRegister

N/A

### = ###

114

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Freecooling Off Delay

HoldingRegister

N/A

### = ###

115

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Cooling On Delay HoldingRegister

N/A

### = ###

116

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Cooling Off Delay

HoldingRegister

N/A

### = ###

117

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Heating On Delay

HoldingRegister

N/A

### = ###

118

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 1 Heating Off Delay

HoldingRegister

N/A

### = ###

119

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Cooling Setpoint HoldingRegister (HeatSP + 8)-95

###.# = ###

200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Heating Setpoint HoldingRegister 32 - (CoolSp - 8)

###.# = ###

201

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Humidity Setpoint

HoldingRegister

0-100%

###.# = ###

202

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Dehumidification Off Sepoint

HoldingRegister

46-99%

###.# = ###

203

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Low Temperature Alarm Setpoint

HoldingRegister

28-65

###.# = ###

204

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Temperature Alarm Setpoint

HoldingRegister

70-120

###.# = ###

205

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Temperature 2 Alarm Setpoint

HoldingRegister

70-120

###.# = ###

206

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Low Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

207

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 High Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

208

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Continuous Blower Setting

HoldingRegister

0-3

### = ###

209

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE CONT BLOWER TABLE

Zone 2 Rotation Setting HoldingRegister

0-2

### = ###

210

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- SEE ROTATION TABLE

Zone 2 Dehumidification Type Setting

HoldingRegister

0-3

### = ###

211

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE DEHUM TYPE TABLE

Zone 2 Passive Dehumidification Setpoint

HoldingRegister

46-99%

###.# = ###

212

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Zone 2 Active Dehumidification Setpoint

HoldingRegister

46-99%

###.# = ###

213

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Freecooling On Delay

HoldingRegister

N/A

### = ###

214

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Freecooling Off Delay

HoldingRegister

N/A

### = ###

215

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Cooling On Delay HoldingRegister

N/A

### = ###

216

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Cooling Off Delay

HoldingRegister

N/A

### = ###

217

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Heating On Delay

HoldingRegister

N/A

### = ###

218

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 2 Heating Off Delay

HoldingRegister

N/A

### = ###

219

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Cooling Setpoint HoldingRegister (HeatSP + 8)-95

###.# = ###

300

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Heating Setpoint HoldingRegister 32 - (CoolSp - 8)

###.# = ###

301

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Humdity Setpoint

HoldingRegister

0-100%

###.# = ###

302

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Dehumidification Off Sepoint

HoldingRegister

46-99%

###.# = ###

303

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Low Temperature Alarm Setpoint

HoldingRegister

28-65

###.# = ###

304

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Temperature Alarm Setpoint

HoldingRegister

70-120

###.# = ###

305

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Temperature 2 Alarm Setpoint

HoldingRegister

70-120

###.# = ###

306

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Low Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

307

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 High Humidity Alarm Setpoint

HoldingRegister

0-100%

###.# = ###

308

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Zone 3 Continuous Blower Setting

HoldingRegister

0-3

### = ###

309

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE CONT BLOWER TABLE

Zone 3 Rotation Setting HoldingRegister

0-2

### = ###

310

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- SEE ROTATION TABLE

Zone 3 Dehumidification Type Setting

HoldingRegister

0-3

### = ###

311

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE DEHUM TYPE TABLE

Zone 3 Passive Dehumidification Setpoint

HoldingRegister

46-99%

###.# = ###

312

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Manual 7960-791E

Page

9 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 10 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Zone 3 Active Dehumidification Setpoint
Zone 3 Freecooling On Delay
Zone 3 Freecooling Off Delay

HoldingRegister HoldingRegister HoldingRegister

Zone 3 Cooling On Delay HoldingRegister

Zone 3 Cooling Off Delay
Zone 3 Heating On Delay
Zone 3 Heating Off Delay

HoldingRegister HoldingRegister HoldingRegister

Number of Units

InputRegister

Humidification Setup

InputRegister

Humidifier Type

InputRegister

LC6000 User Interface Unit of Measure

InputRegister

Zone 1 Indoor Humidity InputRegister

Zone 1 Indoor Temperature
Zone 1 Remote Temperature

InputRegister InputRegister

Zone 2 Indoor Humidity InputRegister

Zone 2 Indoor Temperature

InputRegister

Zone 3 Indoor Humidity InputRegister

Zone 3 Indoor Temperature

InputRegister

Filter Switch Status 1 DiscreteInput

Filter Switch Status 2 DiscreteInput

Blower 1 Status

DiscreteInput

46-99% N/A N/A N/A N/A N/A N/A 1-14 0-3 0-1 0-5
0-100% N/A NA
0-100% N/A
0-100% N/A 0-1 0-1 0-1

###.# = ###

313

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

314

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

315

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

316

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

317

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

318

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

319

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

0

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- SEE HUM TYPE TABLE

### = ###

2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

### = ###

3

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEE UNIT OF MEASURE TABLE

###.# = ###

100

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

101

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

102

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

201

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

300

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

###.# = ###

301

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Off / On = 0 / 1

-

1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 X

X

X

Off / On = 0 / 1

-

1001 2001 3001 4001 5001 6001 7001 8001 9001 10001 11001 12001 13001 14001

-

-

X

Off / On = 0 / 1

-

1003 2003 3003 4003 5003 6003 7003 8003 9003 10003 11003 12003 13003 14003 X

X

X

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Blower 2 Status

DiscreteInput

Low Pressure Switch 1 Status

DiscreteInput

Damper Switch 1 Status DiscreteInput

Damper Switch 2 Status DiscreteInput

Damper Switch 3 Status DiscreteInput

Damper Switch 4 Status DiscreteInput

Reheat Valve 1

DiscreteInput

Electric Heat Stage 1

DiscreteInput

Electric Heat Stage 2

DiscreteInput

Freecooling Availability DiscreteInput

Dirty Filter Indicator Light Status
Compressor Cooling Stage 1
Compressor Cooling Stage 2
Compressor Cooling Stage 3

DiscreteInput DiscreteInput DiscreteInput DiscreteInput

Airflow Switch 1 Status DiscreteInput

Airflow Switch 2 Status DiscreteInput

High Pressure 1 / CCM Alarm Status 1
High Pressure 2 / CCM Alarm Status 2
Power Loss Input Status

DiscreteInput DiscreteInput DiscreteInput

Unit Disable Status

DiscreteInput

Error in the number of retain memory writings

DiscreteInput

0-1

Off / On = 0 / 1

-

1004 2004 3004 4004 5004 6004 7004 8004 9004 10004 11004 12004 13004 14004

-

-

X

0-1

Off / On = 0 / 1

- 1005 2005 3005 4005 5005 6005 7005 8005 9005 10005 11005 12005 13005 14005 X

-

-

0-1

Off / On = 0 / 1

- 1007 2007 3007 4007 5007 6007 7007 8007 9007 10007 11007 12007 13007 14007 X

X

X

0-1

Off / On = 0 / 1

- 1008 2008 3008 4008 5008 6008 7008 8008 9008 10008 11008 12008 13008 14008

-

-

X

0-1

Off / On = 0 / 1

-

1009 2009 3009 4009 5009 6009 7009 8009 9009 10009 11009 12009 13009 14009

-

-

X

0-1

Off / On = 0 / 1

-

1010 2010 3010 4010 5010 6010 7010 8010 9010 10010 11010 12010 13010 14010

-

-

X

0-1

Off / On = 0 / 1

- 1012 2012 3012 4012 5012 6012 7012 8012 9012 10012 11012 12012 13012 14012 X

-

-

0-1

Off / On = 0 / 1

- 1029 2029 3029 4029 5029 6029 7029 8029 9029 10029 11029 12029 13029 14029 X

X

X

0-1

Off / On = 0 / 1

- 1030 2030 3030 4030 5030 6030 7030 8030 9030 10030 11030 12030 13030 14030 X

-

X

0-1

Off / On = 0 / 1

- 1033 2033 3033 4033 5033 6033 7033 8033 9033 10033 11033 12033 13033 14033 X

X

X

0-1

Off / On = 0 / 1

-

1034 2034 3034 4034 5034 6034 7034 8034 9034 10034 11034 12034 13034 14034

-

X

X

0-1

Off / On = 0 / 1

-

1035 2035 3035 4035 5035 6035 7035 8035 9035 10035 11035 12035 13035 14035 X

X

X

0-1

Off / On = 0 / 1

-

1036 2036 3036 4036 5036 6036 7036 8036 9036 10036 11036 12036 13036 14036 X

-

X

0-1

Off / On = 0 / 1

- 1037 2037 3037 4037 5037 6037 7037 8037 9037 10037 11037 12037 13037 14037

-

-

X

0-1

Off / On = 0 / 1

- 1039 2039 3039 4039 5039 6039 7039 8039 9039 10039 11039 12039 13039 14039

-

X

X

0-1

Off / On = 0 / 1

- 1040 2040 3040 4040 5040 6040 7040 8040 9040 10040 11040 12040 13040 14040

-

-

-

0-1

Off / On = 0 / 1

-

1041 2041 3041 4041 5041 6041 7041 8041 9041 10041 11041 12041 13041 14041 X

X

X

0-1

Off / On = 0 / 1

-

1042 2042 3042 4042 5042 6042 7042 8042 9042 10042 11042 12042 13042 14042

-

-

X

0-1

Off / On = 0 / 1

-

1043 2043 3043 4043 5043 6043 7043 8043 9043 10043 11043 12043 13043 14043

-

X

-

0-1

Off / On = 0 / 1

- 1044 2044 3044 4044 5044 6044 7044 8044 9044 10044 11044 12044 13044 14044 X

X

X

0-1

Off / On = 0 / 1

- 1500 2500 3500 4500 5500 6500 7500 8500 9500 10500 11500 12500 13500 14500 X

X

X

Manual 7960-791E

Page

11 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 12 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Error in retain memory writings

DiscreteInput

Circuit 1 Return Air Temp Sensor Fault

DiscreteInput

Circuit 1 High Return Air Temperature

DiscreteInput

Circuit 1 Mixed Air Temp Sensor Fault

DiscreteInput

Circuit 1 Mixed Air High Temperature

DiscreteInput

Circuit 1 Mixed Air Low Temperature

DiscreteInput

Circuit 1 Supply Air Temp Sensor Fault

DiscreteInput

Circuit 1 High Supply Air Temperature

DiscreteInput

Circuit 1 Low Supply Air Temperature

DiscreteInput

Outdoor Air Temp Sensor Fault

DiscreteInput

Outdoor Air Humidity Sensor Fault

DiscreteInput

Circuit 1 Dust Sensor Fault

DiscreteInput

Circuit 1 High Dust Levels Detected

DiscreteInput

Circuit 1 Liquid Line Temp Sensor Fault

DiscreteInput

Circuit 1 Liquid Line Pressure Sensor Fault

DiscreteInput

Circuit 1 Suction Temperature Sensor Fault

DiscreteInput

Circuit 1 Suction Pressure Sensor Fault

DiscreteInput

Circuit 1 Low Pressure DiscreteInput

Circuit 1 High Pressure DiscreteInput

Damper 1 Failed to Open
Damper 1 Failed to Close

DiscreteInput DiscreteInput

0-1

Off / On = 0 / 1

-

1501 2501 3501 4501 5501 6501 7501 8501 9501 10501 11501 12501 13501 14501 X

X

X

0-1

Off / On = 0 / 1

-

1502 2502 3502 4502 5502 6502 7502 8502 9502 10502 11502 12502 13502 14502 X

X

X

0-1

Off / On = 0 / 1

-

1503 2503 3503 4503 5503 6503 7503 8503 9503 10503 11503 12503 13503 14503 X

X

X

0-1

Off / On = 0 / 1

-

1504 2504 3504 4504 5504 6504 7504 8504 9504 10504 11504 12504 13504 14504 X

-

X

0-1

Off / On = 0 / 1

-

1505 2505 3505 4505 5505 6505 7505 8505 9505 10505 11505 12505 13505 14505 X

-

X

0-1

Off / On = 0 / 1

- 1506 2506 3506 4506 5506 6506 7506 8506 9506 10506 11506 12506 13506 14506 X

-

X

0-1

Off / On = 0 / 1

- 1507 2507 3507 4507 5507 6507 7507 8507 9507 10507 11507 12507 13507 14507

-

X

X

0-1

Off / On = 0 / 1

- 1508 2508 3508 4508 5508 6508 7508 8508 9508 10508 11508 12508 13508 14508

-

X

-

0-1

Off / On = 0 / 1

- 1509 2509 3509 4509 5509 6509 7509 8509 9509 10509 11509 12509 13509 14509

-

X

-

0-1

Off / On = 0 / 1

- 1510 2510 3510 4510 5510 6510 7510 8510 9510 10510 11510 12510 13510 14510 X

X

X

0-1

Off / On = 0 / 1

-

1511 2511 3511 4511 5511 6511 7511 8511 9511 10511 11511 12511 13511 14511 X

X

X

0-1

Off / On = 0 / 1

-

1512 2512 3512 4512 5512 6512 7512 8512 9512 10512 11512 12512 13512 14512

-

X

X

0-1

Off / On = 0 / 1

- 1513 2513 3513 4513 5513 6513 7513 8513 9513 10513 11513 12513 13513 14513

-

X

X

0-1

Off / On = 0 / 1

- 1514 2514 3514 4514 5514 6514 7514 8514 9514 10514 11514 12514 13514 14514

-

X

X

0-1

Off / On = 0 / 1

- 1516 2516 3516 4516 5516 6516 7516 8516 9516 10516 11516 12516 13516 14516

-

X

X

0-1

Off / On = 0 / 1

-

1517 2517 3517 4517 5517 6517 7517 8517 9517 10517 11517 12517 13517 14517 X

X

X

0-1

Off / On = 0 / 1

-

1518 2518 3518 4518 5518 6518 7518 8518 9518 10518 11518 12518 13518 14518 X

X

X

0-1

Off / On = 0 / 1

-

1519 2519 3519 4519 5519 6519 7519 8519 9519 10519 11519 12519 13519 14519 X

X

X

0-1

Off / On = 0 / 1

-

1520 2520 3520 4520 5520 6520 7520 8520 9520 10520 11520 12520 13520 14520 X

X

X

0-1

Off / On = 0 / 1

-

1521 2521 3521 4521 5521 6521 7521 8521 9521 10521 11521 12521 13521 14521 X

X

X

0-1

Off / On = 0 / 1

-

1522 2522 3522 4522 5522 6522 7522 8522 9522 10522 11522 12522 13522 14522 X

X

X

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Circuit 1 Freeze Temperature Sensor Fault
Circuit 1 Freeze Condition
Circuit 1 No Airflow Alarm
Dirty Filter 1

DiscreteInput DiscreteInput DiscreteInput DiscreteInput

Emergency Ventilation DiscreteInput

Emergency Cooling

DiscreteInput

Unit Disable Input Active

DiscreteInput

Power Loss Detected

DiscreteInput

Circuit 1 EEV Low SuperHeat

DiscreteInput

Circuit 2 Mixed Air Temp Sensor Fault

DiscreteInput

Circuit 2 Mixed Air High Temperature

DiscreteInput

Circuit 2 Mixed Air Low Temperature

DiscreteInput

Circuit 2 Supply Air Temp Sensor Fault

DiscreteInput

Circuit 2 High Supply Air Temperature

DiscreteInput

Circuit 2 Low Supply Air Temperature

DiscreteInput

Circuit 2 Liquid Line Temp Sensor Fault

DiscreteInput

Circuit 2 Liquid Line Pressure Sensor Fault

DiscreteInput

Circuit 2 Suction Temperature Sensor Fault

DiscreteInput

Circuit 2 Suction Pressure Sensor Fault

DiscreteInput

Circuit 2 Low Pressure DiscreteInput

Circuit 2 High Pressure DiscreteInput

0-1

Off / On = 0 / 1

-

1523 2523 3523 4523 5523 6523 7523 8523 9523 10523 11523 12523 13523 14523 X

-

-

0-1

Off / On = 0 / 1

-

1524 2524 3524 4524 5524 6524 7524 8524 9524 10524 11524 12524 13524 14524 X

X

X

0-1

Off / On = 0 / 1

-

1525 2525 3525 4525 5525 6525 7525 8525 9525 10525 11525 12525 13525 14525

-

X

X

0-1

Off / On = 0 / 1

- 1526 2526 3526 4526 5526 6526 7526 8526 9526 10526 11526 12526 13526 14526 X

X

X

0-1

Off / On = 0 / 1

-

1528 2528 3528 4528 5528 6528 7528 8528 9528 10528 11528 12528 13528 14528 X

X

X

0-1

Off / On = 0 / 1

-

1529 2529 3529 4529 5529 6529 7529 8529 9529 10529 11529 12529 13529 14529 X

X

X

0-1

Off / On = 0 / 1

-

1531 2531 3531 4531 5531 6531 7531 8531 9531 10531 11531 12531 13531 14531 X

X

X

0-1

Off / On = 0 / 1

-

1532 2532 3532 4532 5532 6532 7532 8532 9532 10532 11532 12532 13532 14532

-

X

-

0-1

Off / On = 0 / 1

- 1533 2533 3533 4533 5533 6533 7533 8533 9533 10533 11533 12533 13533 14533 X

X

X

0-1

Off / On = 0 / 1

- 1548 2548 3548 4548 5548 6548 7548 8548 9548 10548 11548 12548 13548 14548

-

-

X

0-1

Off / On = 0 / 1

-

1549 2549 3549 4549 5549 6549 7549 8549 9549 10549 11549 12549 13549 14549

-

-

X

0-1

Off / On = 0 / 1

- 1550 2550 3550 4550 5550 6550 7550 8550 9550 10550 11550 12550 13550 14550

-

-

X

0-1

Off / On = 0 / 1

- 1551 2551 3551 4551 5551 6551 7551 8551 9551 10551 11551 12551 13551 14551

-

-

X

0-1

Off / On = 0 / 1

- 1552 2552 3552 4552 5552 6552 7552 8552 9552 10552 11552 12552 13552 14552

-

-

X

0-1

Off / On = 0 / 1

- 1553 2553 3553 4553 5553 6553 7553 8553 9553 10553 11553 12553 13553 14553

-

-

X

0-1

Off / On = 0 / 1

- 1556 2556 3556 4556 5556 6556 7556 8556 9556 10556 11556 12556 13556 14556

-

-

X

0-1

Off / On = 0 / 1

- 1557 2557 3557 4557 5557 6557 7557 8557 9557 10557 11557 12557 13557 14557

-

-

X

0-1

Off / On = 0 / 1

- 1561 2561 3561 4561 5561 6561 7561 8561 9561 10561 11561 12561 13561 14561

-

-

X

0-1

Off / On = 0 / 1

- 1562 2562 3562 4562 5562 6562 7562 8562 9562 10562 11562 12562 13562 14562

-

-

X

0-1

Off / On = 0 / 1

- 1563 2563 3563 4563 5563 6563 7563 8563 9563 10563 11563 12563 13563 14563

-

-

X

0-1

Off / On = 0 / 1

- 1564 2564 3564 4564 5564 6564 7564 8564 9564 10564 11564 12564 13564 14564

-

-

X

Manual 7960-791E

Page

13 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 14 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Damper 2 Failed to Close
Damper 2 Failed to Open
Damper 3 Failed to Open
Damper 3 Failed to Close
Damper 4 Failed to Open
Damper 4 Failed to Close
Circuit 2 Freeze Temperature Sensor Fault
Circuit 2 Freeze Condition
Circuit 2 No Airflow Alarm
Dirty Filter 2

DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput

Dirty Filter 3

DiscreteInput

Dirty Filter 4
Circuit 2 EEV Low SuperHeat
c.pCOe Offline

DiscreteInput DiscreteInput DiscreteInput

Blower 1 Offline
Blower 1 Trouble Alarm
Blower 2 Offline
Blower 2 Trouble Alarm Condenser Fan 1 Offline
Fan 1 Trouble Alarm
Condenser Fan 2 Offline

DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput DiscreteInput

0-1

Off / On = 0 / 1

-

1565 2565 3565 4565 5565 6565 7565 8565 9565 10565 11565 12565 13565 14565

-

-

X

0-1

Off / On = 0 / 1

- 1566 2566 3566 4566 5566 6566 7566 8566 9566 10566 11566 12566 13566 14566

-

-

X

0-1

Off / On = 0 / 1

- 1567 2567 3567 4567 5567 6567 7567 8567 9567 10567 11567 12567 13567 14567

-

-

X

0-1

Off / On = 0 / 1

- 1568 2568 3568 4568 5568 6568 7568 8568 9568 10568 11568 12568 13568 14568

-

-

X

0-1

Off / On = 0 / 1

-

1569 2569 3569 4569 5569 6569 7569 8569 9569 10569 11569 12569 13569 14569

-

-

X

0-1

Off / On = 0 / 1

- 1570 2570 3570 4570 5570 6570 7570 8570 9570 10570 11570 12570 13570 14570

-

-

X

0-1

Off / On = 0 / 1

- 1571 2571 3571 4571 5571 6571 7571 8571 9571 10571 11571 12571 13571 14571

-

-

X

0-1

Off / On = 0 / 1

- 1572 2572 3572 4572 5572 6572 7572 8572 9572 10572 11572 12572 13572 14572

-

-

X

0-1

Off / On = 0 / 1

- 1573 2573 3573 4573 5573 6573 7573 8573 9573 10573 11573 12573 13573 14573

-

-

X

0-1

Off / On = 0 / 1

- 1574 2574 3574 4574 5574 6574 7574 8574 9574 10574 11574 12574 13574 14574

-

-

X

0-1

Off / On = 0 / 1

- 1575 2575 3575 4575 5575 6575 7575 8575 9575 10575 11575 12575 13575 14575

-

-

X

0-1

Off / On = 0 / 1

- 1576 2576 3576 4576 5576 6576 7576 8576 9576 10576 11576 12576 13576 14576

-

-

X

0-1

Off / On = 0 / 1

- 1579 2579 3579 4579 5579 6579 7579 8579 9579 10579 11579 12579 13579 14579

-

-

X

0-1

Off / On = 0 / 1

- 1596 2596 3596 4596 5596 6596 7596 8596 9596 10596 11596 12596 13596 14596

-

-

X

0-1

Off / On = 0 / 1

- 1597 2597 3597 4597 5597 6597 7597 8597 9597 10597 11597 12597 13597 14597

-

-

X

0-1

Off / On = 0 / 1

- 1598 2598 3598 4598 5598 6598 7598 8598 9598 10598 11598 12598 13598 14598

-

-

X

0-1

Off / On = 0 / 1

- 1599 2599 3599 4599 5599 6599 7599 8599 9599 10599 11599 12599 13599 14599

-

-

X

0-1

Off / On = 0 / 1

- 1600 2600 3600 4600 5600 6600 7600 8600 9600 10600 11600 12600 13600 14600

-

-

X

0-1

Off / On = 0 / 1

- 1601 2601 3601 4601 5601 6601 7601 8601 9601 10601 11601 12601 13601 14601

-

-

X

0-1

Off / On = 0 / 1

- 1602 2602 3602 4602 5602 6602 7602 8602 9602 10602 11602 12602 13602 14602

-

-

X

0-1

Off / On = 0 / 1

- 1603 2603 3603 4603 5603 6603 7603 8603 9603 10603 11603 12603 13603 14603

-

-

X

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Fan 2 Trouble Alarm DiscreteInput

Circuit 1 Low Return Air Temperature

DiscreteInput

Blower or Fan Panel Open

DiscreteInput

Compressor 1 Status

InputRegister

Compressor 2 Status

InputRegister

Mixed Air Temperature 1 InputRegister

Mixed Air Temperature 2 InputRegister

Zone

InputRegister

Outdoor Air Temperature 1

InputRegister

Return Air Temperature 1

InputRegister

Outdoor Air Humidity 1 InputRegister

Evaporator Temperature 1

InputRegister

Blower 1 Speed

InputRegister

Blower 2 Speed

InputRegister

Dust Sensor 1

InputRegister

Liquid Temperature 1

InputRegister

Liquid Temperature 2

InputRegister

Liquid Pressure 1

InputRegister

Liquid Pressure 2

InputRegister

Suction Pressure 1

InputRegister

Suction Pressure 2

InputRegister

Suction Temperature 1 InputRegister

0-1 0-1 0-1 0-14 0-14 N/A N/A 1-3 N/A N/A N/A N/A 0-100% 0-100% 0-100% N/A N/A N/A N/A N/A N/A N/A

Off / On = 0 / 1

-

1604 2604 3604 4604 5604 6604 7604 8604 9604 10604 11604 12604 13604 14604

-

-

X

Off / On = 0 / 1

- 1605 2605 3605 4605 5605 6605 7605 8605 9605 10605 11605 12605 13605 14605

-

-

X

Off / On = 0 / 1

- 1607 2607 3607 4607 5607 6607 7607 8607 9607 10607 11607 12607 13607 14607

-

-

X

### = ###

- 1003 2003 3003 4003 5003 6003 7003 8003 9003 10003 11003 12003 13003 14003 X

X

X

SEE COMPRESSOR STATUS TABLE

### = ###

- 1004 2004 3004 4004 5004 6004 7004 8004 9004 10004 11004 12004 13004 14004 -

-

X

SEE COMPRESSOR STATUS TABLE

###.# = ####

- 1011 2011 3011 4011 5011 6011 7011 8011 9011 10011 11011 12011 13011 14011 X

-

X

###.# = ####

- 1013 2013 3013 4013 5013 6013 7013 8013 9013 10013 11013 12013 13013 14013 -

-

X

# = #

- 1014 2014 3014 4014 5014 6014 7014 8014 9014 10014 11014 12014 13014 14014 X X X

###.# = ####

- 1015 2015 3015 4015 5015 6015 7015 8015 9015 10015 11015 12015 13015 14015 X

X

X

###.# = ####

- 1019 2019 3019 4019 5019 6019 7019 8019 9019 10019 11019 12019 13019 14019 X

X

X

###.# = ####

- 1023 2023 3023 4023 5023 6023 7023 8023 9023 10023 11023 12023 13023 14023 X

X

X

###.# = ####

- 1027 2027 3027 4027 5027 6027 7027 8027 9027 10027 11027 12027 13027 14027 X

-

-

### = ###

- 1034 2034 3034 4034 5034 6034 7034 8034 9034 10034 11034 12034 13034 14034 - X X

### = ###

- 1035 2035 3035 4035 5035 6035 7035 8035 9035 10035 11035 12035 13035 14035 -

-

X

### = ###

- 1040 2040 3040 4040 5040 6040 7040 8040 9040 10040 11040 12040 13040 14040 - X X

###.# = ####

- 1044 2044 3044 4044 5044 6044 7044 8044 9044 10044 11044 12044 13044 14044 -

X

X

###.# = ####

- 1045 2045 3045 4045 5045 6045 7045 8045 9045 10045 11045 12045 13045 14045 -

-

X

###.# = ####

- 1046 2046 3046 4046 5046 6046 7046 8046 9046 10046 11046 12046 13046 14046 -

X

X

###.# = ####

- 1047 2047 3047 4047 5047 6047 7047 8047 9047 10047 11047 12047 13047 14047 -

-

X

###.# = ####

- 1048 2048 3048 4048 5048 6048 7048 8048 9048 10048 11048 12048 13048 14048 X

-

X

###.# = ####

- 1049 2049 3049 4049 5049 6049 7049 8049 9049 10049 11049 12049 13049 14049 -

-

X

###.# = ####

- 1050 2050 3050 4050 5050 6050 7050 8050 9050 10050 11050 12050 13050 14050 X

X

X

Manual 7960-791E

Page

15 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 16 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Suction Temperature 2 InputRegister

Supply Air Temperature 1
Supply Air Temperature 2

InputRegister InputRegister

Condenser Fan Speed 1 InputRegister

Condenser Fan Speed 2 InputRegister

Damper Position 1

InputRegister

Damper Position 2

InputRegister

Damper Position 3

InputRegister

Damper Position 4
Electronic Expansion Valve 1 Position
Electronic Expansion Valve 2 Position
Number of Cooling Stages
Number of Heating Stages
Number of Freecooling Stages
Outdoor Air Dewpoint

InputRegister InputRegister InputRegister InputRegister InputRegister InputRegister InputRegister

Dehumidification Type InputRegister

Subcooling 1

InputRegister

Superheat 1

InputRegister

Superheat 2

InputRegister

Subcooling 2
Wall Unit Software Version X

InputRegister InputRegister

N/A N/A N/A 0-100% 0-100% 0-100% 0-100% 0-100% 0-100% 0-100% 0-100% 0-3 0-2 0-1 N/A 0-3 N/A N/A N/A N/A N/A

###.# = ####

- 1051 2051 3051 4051 5051 6051 7051 8051 9051 10051 11051 12051 13051 14051 -

-

X

###.# = ####

- 1052 2052 3052 4052 5052 6052 7052 8052 9052 10052 11052 12052 13052 14052 -

X

X

###.# = ####

- 1053 2053 3053 4053 5053 6053 7053 8053 9053 10053 11053 12053 13053 14053 -

-

X

### = ###

- 1056 2056 3056 4056 5056 6056 7056 8056 9056 10056 11056 12056 13056 14056 - X X

### = ###

- 1057 2057 3057 4057 5057 6057 7057 8057 9057 10057 11057 12057 13057 14057 -

-

X

### = ###

- 1058 2058 3058 4058 5058 6058 7058 8058 9058 10058 11058 12058 13058 14058 X X X

### = ###

- 1059 2059 3059 4059 5059 6059 7059 8059 9059 10059 11059 12059 13059 14059 -

-

X

### = ###

- 1060 2060 3060 4060 5060 6060 7060 8060 9060 10060 11060 12060 13060 14060 -

-

X

### = ###

- 1061 2061 3061 4061 5061 6061 7061 8061 9061 10061 11061 12061 13061 14061 -

-

X

### = ###

- 1062 2062 3062 4062 5062 6062 7062 8062 9062 10062 11062 12062 13062 14062 X X X

### = ###

- 1063 2063 3063 4063 5063 6063 7063 8063 9063 10063 11063 12063 13063 14063 -

-

X

### = ###

- 1064 2064 3064 4064 5064 6064 7064 8064 9064 10064 11064 12064 13064 14064 X X X

### = ###

- 1065 2065 3065 4065 5065 6065 7065 8065 9065 10065 11065 12065 13065 14065 X X X

### = ###

- 1066 2066 3066 4066 5066 6066 7066 8066 9066 10066 11066 12066 13066 14066 X X X

###.# = ####

- 1067 2067 3067 4067 5067 6067 7067 8067 9067 10067 11067 12067 13067 14067 X

X

X

### = ###

- 1068 2068 3068 4068 5068 6068 7068 8068 9068 10068 11068 12068 13068 14068 X X X SEE DEHUM TABLE

### = ###

- 1071 2071 3071 4071 5071 6071 7071 8071 9071 10071 11071 12071 13071 14071 - X X

### = ###

- 1072 2072 3072 4072 5072 6072 7072 8072 9072 10072 11072 12072 13072 14072 X X X

### = ###

- 1073 2073 3073 4073 5073 6073 7073 8073 9073 10073 11073 12073 13073 14073 -

-

X

### = ###

- 1076 2076 3076 4076 5076 6076 7076 8076 9076 10076 11076 12076 13076 14076 -

-

X

### = ###

- 1080 2080 3080 4080 5080 6080 7080 8080 9080 10080 11080 12080 13080 14080 X X X

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Wall Unit Software Version Y

InputRegister

N/A

Wall Unit Software Version Z

InputRegister

N/A

Unit Runtime

InputRegister

N/A

Unit Starts

InputRegister

N/A

Fan 1 Runtime

InputRegister

N/A

Fan 1 Starts

InputRegister

N/A

Fan 2 Runtime

InputRegister

N/A

Fan 2 Starts

InputRegister

N/A

Blower 1 Runtime

InputRegister

N/A

Blower 1 Starts

InputRegister

N/A

Blower 2 Runtime

InputRegister

N/A

Blower 2 Starts

InputRegister

N/A

Freecooling 1 Runtime InputRegister

N/A

Freecooling 1 Starts

InputRegister

N/A

Freecooling 2 Runtime InputRegister

N/A

Freecooling 2 Starts

InputRegister

N/A

Compressor Stage 1 Runtime

InputRegister

N/A

Compressor Stage 1 Starts

InputRegister

N/A

Compressor Stage 2 Runtime

InputRegister

N/A

Compressor Stage 2 Starts

InputRegister

N/A

Compressor Stage 3 Runtime

InputRegister

N/A

### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###

- 1081 2081 3081 4081 5081 6081 7081 8081 9081 10081 11081 12081 13081 14081 X X X - 1082 2082 3082 4082 5082 6082 7082 8082 9082 10082 11082 12082 13082 14082 X X X - 1083 2083 3083 4083 5083 6083 7083 8083 9083 10083 11083 12083 13083 14083 X X X - 1084 2084 3084 4084 5084 6084 7084 8084 9084 10084 11084 12084 13084 14084 X X X - 1085 2085 3085 4085 5085 6085 7085 8085 9085 10085 11085 12085 13085 14085 X X X - 1086 2086 3086 4086 5086 6086 7086 8086 9086 10086 11086 12086 13086 14086 X X X - 1087 2087 3087 4087 5087 6087 7087 8087 9087 10087 11087 12087 13087 14087 X X X - 1088 2088 3088 4088 5088 6088 7088 8088 9088 10088 11088 12088 13088 14088 X X X - 1089 2089 3089 4089 5089 6089 7089 8089 9089 10089 11089 12089 13089 14089 X X X - 1090 2090 3090 4090 5090 6090 7090 8090 9090 10090 11090 12090 13090 14090 X X X - 1091 2091 3091 4091 5091 6091 7091 8091 9091 10091 11091 12091 13091 14091 X X X - 1092 2092 3092 4092 5092 6092 7092 8092 9092 10092 11092 12092 13092 14092 X X X - 1093 2093 3093 4093 5093 6093 7093 8093 9093 10093 11093 12093 13093 14093 X X X - 1094 2094 3094 4094 5094 6094 7094 8094 9094 10094 11094 12094 13094 14094 X X X - 1095 2095 3095 4095 5095 6095 7095 8095 9095 10095 11095 12095 13095 14095 X X X - 1096 2096 3096 4096 5096 6096 7096 8096 9096 10096 11096 12096 13096 14096 X X X - 1097 2097 3097 4097 5097 6097 7097 8097 9097 10097 11097 12097 13097 14097 X X X - 1098 2098 3098 4098 5098 6098 7098 8098 9098 10098 11098 12098 13098 14098 X X X - 1099 2099 3099 4099 5099 6099 7099 8099 9099 10099 11099 12099 13099 14099 X X X - 1100 2100 3100 4100 5100 6100 7100 8100 9100 10100 11100 12100 13100 14100 X X X - 1101 2101 3101 4101 5101 6101 7101 8101 9101 10101 11101 12101 13101 14101 X X X

Manual 7960-791E

Page

17 of 19

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Manual 7960-791E Page 18 of 19

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Compressor Stage 3 Starts

InputRegister

N/A

Compressor 4 Runtime InputRegister

N/A

Compressor 4 Starts

InputRegister

N/A

Electric Heat Stage 1 Runtime

InputRegister

N/A

Electric Heat Stage 1 Starts

InputRegister

N/A

Electric Heat Stage 2 Runtime

InputRegister

N/A

Electric Heat Stage 2 Starts

InputRegister

N/A

Electric Heat Stage 3 Runtime

InputRegister

N/A

Electric Heat Stage 3 Starts

InputRegister

N/A

Electric Heat Stage 4 Runtime

InputRegister

N/A

Electric Heat Stage 4 Starts

InputRegister

N/A

Unit Lifetime Hours

InputRegister

N/A

Blower 1 Lifetime Hours InputRegister

N/A

Blower 2 Lifetime Hours InputRegister

N/A

Fan 1 Lifetime Hours

InputRegister

N/A

Fan 2 Lifetime Hours

InputRegister

N/A

Compressor Stage 1 Lifetime Hours

InputRegister

N/A

Compressor Stage 2 Lifetime Hours

InputRegister

N/A

Compressor Stage 3 Lifetime Hours

InputRegister

N/A

Compressor Stage 4 Lifetime Hours

InputRegister

N/A

Electric Heat Stage 1 Lifetime Hours

InputRegister

N/A

### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###

- 1102 2102 3102 4102 5102 6102 7102 8102 9102 10102 11102 12102 13102 14102 X X X - 1103 2103 3103 4103 5103 6103 7103 8103 9103 10103 11103 12103 13103 14103 X X X - 1104 2104 3104 4104 5104 6104 7104 8104 9104 10104 11104 12104 13104 14104 X X X - 1105 2105 3105 4105 5105 6105 7105 8105 9105 10105 11105 12105 13105 14105 X X X - 1106 2106 3106 4106 5106 6106 7106 8106 9106 10106 11106 12106 13106 14106 X X X - 1107 2107 3107 4107 5107 6107 7107 8107 9107 10107 11107 12107 13107 14107 X X X - 1108 2108 3108 4108 5108 6108 7108 8108 9108 10108 11108 12108 13108 14108 X X X - 1109 2109 3109 4109 5109 6109 7109 8109 9109 10109 11109 12109 13109 14109 X X X - 1110 2110 3110 4110 5110 6110 7110 8110 9110 10110 11110 12110 13110 14110 X X X - 1111 2111 3111 4111 5111 6111 7111 8111 9111 10111 11111 12111 13111 14111 X X X - 1112 2112 3112 4112 5112 6112 7112 8112 9112 10112 11112 12112 13112 14112 X X X - 1113 2113 3113 4113 5113 6113 7113 8113 9113 10113 11113 12113 13113 14113 X X X - 1115 2115 3115 4115 5115 6115 7115 8115 9115 10115 11115 12115 13115 14115 X X X - 1117 2117 3117 4117 5117 6117 7117 8117 9117 10117 11117 12117 13117 14117 X X X - 1119 2119 3119 4119 5119 6119 7119 8119 9119 10119 11119 12119 13119 14119 X X X - 1121 2121 3121 4121 5121 6121 7121 8121 9121 10121 11121 12121 13121 14121 X X X - 1123 2123 3123 4123 5123 6123 7123 8123 9123 10123 11123 12123 13123 14123 X X X - 1125 2125 3125 4125 5125 6125 7125 8125 9125 10125 11125 12125 13125 14125 X X X - 1127 2127 3127 4127 5127 6127 7127 8127 9127 10127 11127 12127 13127 14127 X X X - 1129 2129 3129 4129 5129 6129 7129 8129 9129 10129 11129 12129 13129 14129 X X X - 1131 2131 3131 4131 5131 6131 7131 8131 9131 10131 11131 12131 13131 14131 X X X

LC6000 MULTI-TEC WR FUSION-TEC MEGA-TEC

Name

Type

Range

Format

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Notes

Electric Heat Stage 2 Lifetime Hours
Electric Heat Stage 3 Lifetime Hours
Electric Heat Stage 4 Lifetime Hours
Freecooling 1 Lifetime Hours
Freecooling 2 Lifetime Hours
Unit Type

InputRegister InputRegister InputRegister InputRegister InputRegister InputRegister

Unit Status

InputRegister

N/A N/A N/A N/A N/A 2-5 0-31

### = ###
### = ###
### = ###
### = ###
### = ###
### = ###
### = ###

- 1133 2133 3133 4133 5133 6133 7133 8133 9133 10133 11133 12133 13133 14133 X X X - 1135 2135 3135 4135 5135 6135 7135 8135 9135 10135 11135 12135 13135 14135 X X X - 1137 2137 3137 4137 5137 6137 7137 8137 9137 10137 11137 12137 13137 14137 X X X - 1139 2139 3139 4139 5139 6139 7139 8139 9139 10139 11139 12139 13139 14139 X X X - 1141 2141 3141 4141 5141 6141 7141 8141 9141 10141 11141 12141 13141 14141 X X X - 1143 2143 3143 4143 5143 6143 7143 8143 9143 10143 11143 12143 13143 14143 X X X - 1154 2154 3154 4154 5154 6154 7154 8154 9154 10154 11154 12154 13154 14154 X X X

Manual 7960-791E

Page

19 of 19

