CARRIER Furnace/Heater, Gas Manual L0503144
User Manual: CARRIER CARRIER Furnace/Heater, Gas Manual CARRIER Furnace/Heater, Gas Owner's Manual, CARRIER Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 48
Download | |
Open PDF In Browser | View PDF |
4-Way HEATUNG 88MSA Fixed-Capacity MuMtipoise Condensing & COOUNG Gas Furnace \isit _ v_w carrier.corn Installation, Start-Up, and Operating For Sizes 040--120 Series t50 I mlCI[NCY I$O 9001:2000 @ A93040 NOTE: Read the entire instl_action manual be%re starting the installation This symbol -->indicates a change since the last issue, Index Page DIMENSIONAL DRAWING 3 SAFETY CONSIDERATIONS 2 (learances to ( ombustibles 4 CODES AND STANDARDS ........................................................ 5 ELE< TROSTATIC DISr ¢AIRFLOW _ _ _ AIRFLOW HO _II_C_NTALN'NI 0 © AIRFLOW A93041 Fig. 1--NuRipoise Orientations Condensate Drain .................................................................... General ....................................... Application ....................................... Condensate Drain Protection ...................... START°UP, ADJL STMENTS AND SAFETY (HECK ....... General .......................................... Prime ( ondensate Trap With Warm .................... Purge Gas Lines ................................... Sequence of Operation ............................. Heating Mode ................................. Cooling Mode ................................ Continuous Blowe* Mode ........................ Heat Pump Mode .............................. Component Test ............................... Adjustments ....................................... Set Gas Input Rate .............................. Set Temperature Rise ................................ Blower Off"Delay (Heat Mode) .................... Set Thermostat Heat Anticipator .................... at any time, specifications Printed in U.S.A. HORLIZOTNTA _ Form or designs 58MSA-11SI without notice Pg 1 and without 2-05 35 35 35 36 37 37 37 38 38 38 38 38 39 39 39 39 44 44 45 incurring obligations. Replaces: 58MSA-10SI Check Safhty Controls Check Prima_ Limit Control Check Pressure Switch CHECKLIST ...................................... 45 45 45 45 Understand personal could SAFETY CONSIDERATIONS these signal words DANGER, injury result identify Improper installation quire excessive failm'e Application attention HAZARD of this fm'nace should given to vent sizing temperature rise, of fml_ace o1" cause premature may re= with (fbm_erly special gas input rate, air Muhipoise gases (see ftmmce attics, basements, The and unit sizing. Improper nance, sion, ELECTRICAL POISONING to follow this warning firQ personal or use can cause fire, electrical cause personal installer, carbon tor or branch shock, must Installing and servicing gas electrical should Untrained personnel such as cleaning heating fi/rnace rating by trained These instructions cover especially distribu- The qualified and heating with due to working unit and requirements other these on safety and confoml resider> instrnctions safety available calls, glasses during and work start=up gloves. Have and adjustment a fire as a extinguisher procedures such and service to %tlow this caution may result in personal Sheet metal parts may have sharp edges or bun's wear appropriate protective clothing injury. Use care and and gloves when ban= dling parts. Recognize safety information. When you see this symbol manuals, This is the safety=alert symbol Z_ on the unit and in instructions or be alert to the potential for personal injury. NOT gas. A CSA furnace for use with material and controls. floor materials this on carpeting, base and wood Nmace In MUST be flooring. is installed on Part No. CD5 or CK5, or when Coil is used. The design for of this fi/rnace continuous with a night setback line is fbr instalhomes, or return-air operation mininmm down to 55°F db thermometer. Return-air db. Failure to follow these of heat exchangers, motors, (See Fig. 4.) These Nrnaces are shipped with the connected for UPFLOW applications. required directly AGA and CGA) designocertified vehicles, manufi_ctured mobile is designed air requirements. accessow of 60_>F db or intermittent used to supply fiom the fimaace. other than wood flooring. when (:oil Assembly as when materials horizontally be installed required when used in DOWNFLOW, HORIZONTAL LEFT as shown HORIZONTAL (supply=air in Fig. drain and pressure Minor modifications discharge 1. See details robes are RIGHT, direction) in Applications or applica- section. --€ Install this Nmace only in a location and position as specified in LOCATION and INSTALLATION sections of these instnlctions. furnace products must be discharged to an approved Combustion --€ Always --> When sections as specified a Nrnace the return which is installed within the space air shall also be handled and terminating Use a commercially for detection PIPING the fitrnace's has an external so that supply outside outside of leaks to section of intended static pressure TEMPERA- ducts carry air circulated containing by ducts the space this in the of d_ese instructions. flame. range as specified in the SET of these instructions. to areas Connect as specified in the GAS to operate with a duct system the allowable RISE section outdoors. only, made specifically install the furnace by tl_e fi/rnace casing system Air and Vent piping soap solution rise range within TURE vent test for gas leaks with an open check all connections these instructions. HAZARD in alcoves, and garages. to combustibles. temperature must not exceed 80°F return-air limits may affect reliability tions are CSA and propane natural to convert on combustible is not furnace available Failure erawlspaces, fbr use with factory NOT CSA (formerly lation in recreation outdoors. --€ Never CUT installed base temperature must Furnaces fbr installation code fbr further SHALL installations, --€ Combustion Wear reliability, for natural fiom combustible 90B or local furnaces --€ This on tags, and those that may not have kept up with changing require is used to highlight installation, and of 36 inches Box Part No. KCAKC fimctions When for a distance manufacturer's equipment. in literature, ductwork Special standards and safkty codes In some instances, exceed certain local codes and ordinances, tial construction practices. We minimum ibr a saf_ installation NOTE rooms, clearances a l-in. clearance used when qualified maintenance personnel. the minimum personal gas. downflow and All other operations precautions attached to or shipped that may apply to existing national these instructions or your plate) utility tile, or any other combustible may can be hazardous basic service observe to in minor Gas-Fired kit is required Maintain These a qualified trained air filters which is used result design-certified is factory=shipped See NFPA this product. or service perform which [itctory=authorized Only repair, can equipment, on labels precautions only equipment and replacing explo= Consult when modi_)ing instMl, poisoning, or assistance. use heating mainte° gas supplier, components. persomiel be performed shock, service, conditions damage. fbr information or agency alteration, or other local listed kits or accessories and AND in electrical monoxide Jr!ire'y.,-or property smwice agency, installer SHOCK HAZARD could result adjustment, hazards CAUTION in enhanced Condensing closets, listed gas conversion ir!inry, or death, installation, ma? damage will result See Fig. 3 for required Failure signifies or death. which AGA and (GA) propane FIRE, EXPLOSION, CARBON MONOXIDE WARNING injury and property which The 58MSA component be indoors and material, unit leveling, and (AU° or operation. or misapplication servicing death. practices or product suggestions RELIABILITY or in personal unsafe injury FURNACE WARNING, TION These words are used with the safkty=alert symbol. DANGER identifies the most serious hazards which will result in severe sealed containing the f:umace, to the Nrnace the fhrnace. © A_RFLOW TYP t OaT HORIZONTAL POWER LEFT) {DOWNFLOW& HORIZONTALRIGHT) ORALTERNATE gqN DIAGAS CONN CONN 1 P 22 2qN POWERENTRY ACCESSORY T I4 _" TYP qN DIA THERMOSTAT ENTRY 30 _;" _"_ [ J VENT CONN 2] DRAINTRAP LODATION _ (ALTERNATE CONDENSATE UPFLOW) SIDE INLET i 24 i i i i 17 :,i_" TiP 9/6" SIDE iNLET ! CONDENSATE DRA_N DRAIN S{OEiNLET 26 _,e"TVp LO CATION LOCATION (UPFLO\M) (UPFLOW) DIMPLE LOCATORS FOR HORIZONTAL HANGING NOTES: BOTTOM iNLET 1. Minimum return-air openings at furnace, based on metal duct if flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters 2 Minimum return-air opening at furnace: a, For 800 CFM-16-in, round or 14/_ x 12-in rectangle b For 1200 CFM-20qn, round or 14'h x 19 Lqn, rectangle c, For 1600 CFM-22qn, round or 14/;, x 23 L-in, rectangle d For airflow requirements above 1800 CFM see Air Delivery table in Product Data literature for specific use of single side inlets The use of both side inlets a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM at 0_5 WC ESP A02149 Dimensions UNIT SIZE (In.) D E 040-08 17-I/2 A 15-7/8 16 040-t2 17-I/2 15-7/8 16 080-08 17-I/2 15-7/8 16 080-t2 17-I/2 15-7/8 16 080-t6 17-I/2 15-7/8 16 080-t2 17-I/2 15-7/8 16 080-t6 17-I/2 15-7/8 16 080_20 21 19-3/8 19-1/2 100-16 21 19-3/8 19-1/2 100-20 21 19-3/8 19-1/2 120_20 24-I/2 22-7/8 23 Fig. 2--Dimensional Drawing --->A gas-fired fire, ace %1"installation in a residential garage must be installed as specified in the Hazardous Locations section of these insm/etions, Installer Packet includes: --> The [:urnaee is not to be used %r tempora U heating of buildings or structures under construction unless the furnace installation and User's Information operation complies with the first CAUTION section of these instructions, in the LOCATION These fi.u'naces are shipped materials proper furnace blower installation, with the %llowing These materials Installation, Startup, and Operating instructions Service and Maintenance instructions Warranty Certificate Loose Parts Bag includes: Pressure tube extension Quantity 1 Collector Box or condensate to assist in are shipped Manual in the main compartment, trap extension tube 1 Inducer housing drain tube 1/2-in CPVC street elbow 1 2 Drain tube coupling 1 Drain tube coupiing grommet 1 Vent and combustion-air 2 Condensate pipe support trap hole filler plug Vent and combustion-air Combustion-air 3 intake hole filler ptug pipe perforated 2 disk assembly 1 Vent Pipe Extension 1" * ONLY supplied with some furnaces. e ¢ o ® e ® o e ® This forced air lurnace is equipped for use with natural gas at altitudes 0 - 10.000 ff (0 - 3,050m), except 140 size _rnaces are only approved for altitudes 0 - 7.000 ft. (0 - 2,135m). An accessory kit, supptied by tbe manufacturer, shall be used to convert to propene gas use or rr_ay be required for some natural gas apptications. This furnace is for indoor installation in a building constructed on site. This furnace may be ins"tailed in a manufactiJred (mobile) home when stated on rating plate and using factory authorked kit.. This furnace may be tilstalled on combustible floodng in alcove or closet at Minimum Inches Clearance To Combustible Construction as described below. This furnace requires a special venting system Refer to the installation instructions for parts list and method of installation. This furnace is for use with schedule-40 PVC. PVC-DW%L CPVC. or ABS-DWV pipe, and must not be vented in common with other gas-tired apptiances. Construction tbrough which vent/air intake pipes may be installed is maximum 24 inches (600 ram), minimum 3/4 inches (19 ram) thickness (including roofing materials) Cetta fournalse & air puls6 est 6quip6e peur utitisation avec gaz naturel et altitudes compdees entre 0 - 3.050m (0 - 10,000 pi),except6 queles sont pour altitudes comprises entre 0 - 2,135m 0 - 7,000pi). Ut set une trousse de cenvers on. fourn e par e fabr can, pour passer au gaz propane ou pour certaines installations au gaz natureL Cetta fournaise a air puls6 es"t pour installation a Fint6rieur darts un bNiment construit sur place. Cetta fournalse a air pulse peut 6tre install6e pr6fabdqu6e (maison mobile) si prescht par la plaque signN6tique et si r on utitise une trousse specifi6e par le labdcant. C'etta fournaise peut _tre instati6e sur un plancher combustible darts un enfoncement ou un placard en observant les D_gagement Minimum Elements De Construction Combustibles, fournaises dens de 140 taille une maison En Pouces Ave¢ Cetta fournaise n6cessite un systeme d'evaoJation special La m6thede d'installation et la tiste des pieces n6cessaires figurent dens les instructions d'instatiation. Cetle fournalse doit s'u!itiser avec la tuyautede des nomendatures 40 PVC. PVC-DWV, CPVC, oN ABS-DVW et elle ne peut pas 6tre ventil6e conjointment avec d'autres appereils a gaz. Epalsseur de la construction au travers de laquetie il est pcesible de laire passer les tuyaux d'a6ration (admlssion/6vacuation): 24 po ('600 ram) maximum. 3/4 po (19ram) minimum (y cornprls la toiture) For uptiow and downtiow applications, furnace mu_t be installed level, or pitched within 1/2" of level For a horizontal apptication, the furnace must be pitched minimum 1/4" to maximum of 1/2" forward for proper draina:je. See Installation Manual for IMPORTANT unit supped details on horizontal apptications, M IN 1/4" TO 1/2" MAX Pour des appticatises de flux ascendent et descendant. _ fournaise ddt 8tre install6e de niveau ou indti%,e pes plus de 1/2" du niveau. Pour une apptication hodzontale, la fournalse doit g,tre inciinde entre minimum 1/4" et maximum 1/2" du nNeau pour le drainage appropd6. En _ d'instatiation en position beCEontale. consulter les renseignements tMPORTANTS sur le support dens le manuel d'instatiation. HORIZON NtNINUN iNCHES CLEARANCE TO CONBUSTtBLE CONSTRUCTION ALL POSITIONS: Minimum front clearance ? ? 140 size furnaces DOWNFLOW POSITIONS: t For ir_stallation 24 inches floors only when to combustible installed Part No, CD5 or CKS, or Coil Casing, on special materials, Cleat_nce base No, KGASB0201ALL, arrows do not change with furnace onentation Part No, KCAKC, POSITIONS: Line contact furnace is permissible jacket, and shown only between building § Clearance O 120 and 140 size furnaces joists, lines formed studs, of top and two sides ne change pas avec I'odentation de la gen@aIeur d'air cbaud. of or framing, is for air inlet and air outlet require by intersections aed Cette toumaise est approuv¢e pour Iinstallaflon HORIZONTALE e! la circulaJion d'air VERS LE HAUT et VERS LE BAS (610mm), 1 inch back clearance on cembustible Coil Assembly HORIZONTAL for service require TNs furnace is approved for UPFLOW, DOWNFLOW HORIZONTAL instNlations, TAL ends. 1 inch bottom clearance to combustible materials, DEGAGEMENT MINIMUM EN POUCESAVEC _LEMENTS DE CONSTRUCTIONCOMBUSTIBLES POUR TOUS LES POSITIONS: Degagen_ent tt avant minimum de 610mm (24 po ) pour l'entretien, Pourlesfoumaissede 140taille,1 po (25mm)degagen-entdes n_t@iauxcombustiblseest requis au-arriere. POUR LA POSITION COURANT DESCENDANT: 1 Pour Iinstallation sur le plancher combustible seulement quand on utilise la base speciale, piece n ° KGASB0201ALL, I'sesemble serpentin, piece n° CD5 ou CKS, ou le carter de serpentin, piece n° KCAKC. POUR LA POSITION HORIZONTALE: Le contact deuxoStes b4,timent, § La distance d 'air, n'est pem?is qdentre les ligses forages par les intersections de la chemise de la foumaise et des selives, des n_ntan% indiquee cenceme I'extr@mit6 Pour Ise foumaises de 120 et 140 taille est requis au CARBON MONOXIDE Failure to fbllow or death. Casing when hole filler condensate 4. Install POISONING this warning cap must be installed condensate trap into stubs condensate TRAP trap casing in loose until holes with plastic label on main furnace door collector box connections. drain robe (blue Tube plug fi'om LOWER and white removed striped label). was connected collector box to condensate PRESSURE SWITCH TUBING One collector box pressure switch applications. densate collector box drain connection to con= trap. trap This switch Condensate Trap Located Ca3 Connect LOWER on Left Side of Casing collector box &ain and white striped label) to condensate does not need to be cut. (2.) Clamp tube to prevent Condensate Trap Located Ca3 Install drain robe loose parts (blue and white bag) any condensate on Right coupling into collector label) in DOVv_TLOW box Connect larger supplied piing, in loose extending connection (c.) Route diameter parts &ain bag) collector tlap. Tube Relocate robes as described pressure 2. Use drain 2. Inducer Determine (e.) Connect (f.) Clamp Housing appropriate robe as shown parts label) which 5. Route inducer b. Remove &ain and cap and clamp from LOWER inducer housing drain connection. discard robe which applications. label on main fhrnace door robe (pink label) attached to robe collector (factor-supplied box pressure connected to in loose tube (green condensate box pressure robe (green labeled "collector box." smaller diameter bag) to extend robe collector was previously tube (pink t_ap label) relief port to pressure (factmT-supplied box pressure connected parts label) which to pressure label) to condensate in robe (pink switch. trap relief appropriate robe to relief CONDENSATE TRAP length, cut, and connect robe. port connection. FREEZE PROTECTION Tube fhctoEyoinstalled housing box pressure this extended 6. Determine leakage. to the pressure RIGHT port connection. 7. Clamp any condensate to the condensate below. diameter remaining loose Refer a Remove smaller 4. Use in Fig. 9. and cut. collector 3. Connect collector switch connection for trap. robe to prevent Drain tube cou° box drain robe between length to condensate drain (_tctory° for the box pressure connections was previously connection. robe was previ= to switch bag) to extend in trap. collector gas valve and inlet housing (d.) to &ain box to condensate extended robe or HORIZONTAL fbr proper ously plugged. (b.) connected be connected See Fig. 8 or 9 or robe routing connected and used MUST and in UPFLOW collector was f_ctory to check Side of Casing which which NOTE: (fhctow-supplied striped be disconnected robe (blue leakage. is factory is installed port robe. The other port connection 1. Disconnect (b.) tube (pink label) robe MUST label) relief fbr connection fbr recommendations fbr use when furnace trap relief robe (green LOWER section TRAP FIELD DRAIN ATTACHMENT Drain section condensate tlap. c. Connect Switch Tubing Refer to Condensate procedures, the pressure clamp and plug into [PPER &ain robe (blue label) which (1.) Refkr to Pressure procedure CONDENSATE fbr proper fimtory=installed (d) Clamp robe to prevent any condensate teakage. filler TUBING Box Drain (c.) Connect robe to condensate trap. hole by inserting hole and rotating parts bag) See Fig 8 or 9 or robe routing b. Install hole 3 Relief Port Tube to check a Remove casing casing NOTE: 1. Collector shelf Ca.) Route inducer housing drain tube (violet 1abel) between gas valve and inlet housing behind collector box drain tube position. caps (*i_ctory=supplied CONDENSATE in blower in}ury (b) Determine appropriate length and cut desired through tabs snap into locking unused in personal trap is relocated. tube connection 5. Fill (20 Condensate Trap Located on Right Side of Casing HAZARD could result UPPER was previously (molded) connected to condensate t_ap. c Install cap and clamp on UPPER inducer housing connection where molded &ain robe was removed. to Condensate Step 4--Horizontal Applications A horizontal &ain Drain Protection Left (Supply-Air section for recommenda- tions and procedures located left fhrnace application to the right of combustion and conditioned air is discharged Discharge) is where and controls to the left. fhrnace section blower of' furnace, is PLUG AUXILIARY COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) 'U" BOX O o CONDENSATE TRAP COLLECTOR BOX TUBE (GREEN) HOUSING DRAIN TUBE (VIOLET) BOX EXTENSION DRAtNTUBE BOX DRAIN TUBE (BLUE) COLLECTOR BOX EXTENSION TUBE DRAIN TUBE COUPLING COLLECTOR BOX TUBE (PINK) RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR 040,060, AND 080 HEATING INPUT FURNACES A00215 Fig. 10--Horizontal CONDENSATE TRAP The condensate blower tlap as shown LOCATION 1. Collector must be removed shelf location Left Tube Configuration and relocated from the factor-installed in selected application a location To relocate location, condensate perform trap from 3 robes connected 2. Remove tlap flora blower 3. Install the blower shelf to desired casing large to condensate shelf by gently pushing tabs inward c shelf cap (factov-supplied hole where in loose parts 2. Inducer CARBON MONOXIDE POISONING Failure to _bllow this warning or death. Casing when hole filler condensate 4. Install Housing condensate unused trap NOTE: check into casing through casing position. condensate caps (fi_ctory=supplied CONDENSATE TRAP trap in loose hole by hole with to condensate Drain (factoryextend- trap and cut leakage. Tube LOWER (molded) was previously inducer connected inserting until inducer &ain connection d. (lamp tabs plastic filler housing to condensate housing smaller diameter bag) to extend TUBING previously label on main fl/rnace appropriate robe to prevent door to b. Route connections. length, robe (violet label and to connect LOWER bag) to the condensate cuL and connect any condensate trap. robe. leakage. c. Detem_ine d. (lamp robe (factov-supplied collector connected extended connection 10 parts Port Tube a. Use parts bag) &ain extension in loose c. Detem_ine tube housing factoryosupplied 3. Relief holes clamp injury shelf hole and rotating casing See Fig. 10 or tube routing for proper in blower and any condensate and discard b. Use inducer cap must be installed was trap. in personal trap is relocated. connection stubs snap into locking 5. Fill could result robe robe (blue label) drain robe which HAZARD which trap length robe to prevent a. Remove -9 drain in loose parts label) box &ain robe Route extended d. (lamp tlap was removed. to condensate diameter to appropriate hole filler tube (blue in loose parts bag) to drain robe coupling, ing collector trap. (factory-supplied box drain connected supplied trap. bag) into blower &ain tube coupling b. Connect the Ibllowing: Tube into collector previously 1. Remove and rotating Install bag) in Fig. 2 or 10. Box Drain box tube (green to the condensate collector box pressure on the condensate appropriate robe to prevent length, in loose label) trap. robe to relief trap. cuL and connect any condensate parts which was leakage. robe. port A 3-IN. MINIMUMCLEARANCE TO COMBUSTION-AIRINTAKE IS REQUIRED. _VENT INTAKE , A 12-tN. MIN HORIZONTAL PIPE SECTION tS RECOMMENDED WITH SHORT (5 TOEXCESSIVE 8 FT) VENT SYSTEMS TO REDUCE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. 30-IN. MtN SHUTOFF GAS VALVE ACCESS OPENING FOR TRAP DRAIN SEDIMENT TRAP NOTE: CONDENSATE TRAP LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS. A96184 Fig. 11--Attic CONDENSATE Refer TRAP FIELD to Condensate Drain DRAIN section Location and Working ATTACHMENT %r (ONSTRU(T recommendations and (onstruct procedures SWIT(H The LOWER connected extended, collector rerouted, NOTE: check box pressure switch applications. HORIZONTAL smaller 3. Route extended a. Behind tube c. Behind pressure CONDENSATE be disconnected, to the pressure switch in label on main Nmace tube door to NOTE: tube (pink label) attached (factory-supplied in item clearances in loose motor to parts in intem_ittent unit be installed The drain below See sloped connection furnace to condensate to an open drain. is restricted to a minimum of 5 It. (See 8.) NOTE: A mended with short (5 to 8 f_) vent systems. is to reduce 1. housing. 12-in. minimum excessive pipe. (See Fig. Step 5--Horizontal A horizontal located and pressure length, FREEZE Drain trap MUST Vent pipe length Table bracket. connection TRAP may result horizontal condensate pipe droplets section is recom- This recommendation fi'om exiting the vent 11 or 38.) Right (SupplyoAir Discharge) Applications shelf and inducer motor inducer to Condensate furnace OPERATE this caution nap must also be properly box pressure appropriate NOT to fbltow Fig. 5 [br dimensions. housing. blower switch where all required operation. robe: inducer d. Between 4. Detem_ine MUST MAY Failure The condensate tube disconnected inducer b. Between INIT below. diameter bag) to extend plat%m_ (See Fig. 3 and 11) is fhctory connections. robe as described 2. Use label) applications. 1. Disconnect collector pressure switch. Refkr This See Fig. 10 or tube routing Modify tube (pink for use when [_urnace is installed and then reconnected LEFT for proper PLATFORM TUBING to the pressure in UPFLOW A WORKING working are met PRESSURE Platform cut, labeled and conditioned switch. and reconnect COLLE(TOR robe section application air is discharged is where and controls furnace section blower of fi/mace, to the right. to BOX. MINOR PROTECTR)N Protection right furnace to the tel} of combustion Failure for recommenda° PROPERTY to fbllow DAMAGE this caution may result in minor property damage tions and procedures. Local 11 codes may require condensate trap when application or over a drain pan under a condensing a finished ceiling_ entire furnace fi/rnace is used and in attic is BOX DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) CAP BOX EXTENSION TUBE PLUG COLLECTOR BOX TUBE (PINK) BOX RELOCATED HERE CONDENSATE TRAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR EXTENSION BOX TUBE A00214 Fig. 12--Horizontal NOTE: current In (anada, NSCNGPIC NOTE: installations shall be in accordance Installation Codes andor local codes. The auxilial_- junction box (J°Box) opposite side of _/rnace casing. (See Connection section _br J-Box relocation. CONDENSATE TRAP MUST Fig. (ONDENSATE with NOTE: be relocated 12.) Right Tube Configuration to check See Electrical See Fig for proper 1. Collector a LOCATION TRAP TL BING 12 or robe routing Box Drain The condensate tlap must be removed shelf location as shown and relocated from the factor-installed in selected application Remove b. Install location _ctoryoinsta!led plug from LOWER To relocate location, condensate perform condensate trap 3 tubes 2. Remove tlap fi'om blower 3. Install from the blower shelf to desired c. Connect the fbllowing: 1. Remove and rotating connected to condensate striped cut. trap. shelf by gently pushing tabs inward d. (lamp trap. casing 2. Inducer hole filler bag) into blower removed shelf cap (factov-supplied hole where in loose collector box and plug into UPPER collector box which connected parts LOWER (ARBON MONOXIDE Failure to follow or death. Casing when this warning hole filler condensate 4. Install POISONING could result cap must be installed trap into unused condensate caps (_Sctoryosupplied trap in loose hole by shelf fhctoryoinstalled with leakage. cap and clamp from LOWER inducer housing drain connection. and discard UPPER was previously until tube tabs (molded) connected plastic filler inducer &ain connection _ Clamp 3. Relief Refer to condensate housing appropriate parts length, tube (violet bag) to connect to condensate cuk and connect &ain label and LOWER trap. robe trap. robe to prevent any condensate leakage. Port Tube to procedure. 12 &ain extension in loose e. Detem?ine parts bag) housing factory-supplied condensate holes any condensate Tube c. Install cap and clamp on UPPER inducer housing connection where molded &ain robe was removed. hole inserting hole and rotating casing Drain housing d. Use inducer casing connection stubs through casing snap into locking position. 5. Fill in3u D' trap is relocated. condensate trap. Tube does not need to be tlap. in personal in blower to box drain robe (blue and white &ain robe which HAZARD was previously collector robe to prevent inducer label). to condensate Housing a. Remove tlap was remo_ ed. striped tlap. label) b. Remove --> clamp &ain tube (blue label) in Fig. 2 or 12. door to Tube drain robe (blue and white blower label on main furnace connections Pressure Switch Tubing section _br connection to (ONDENSATE TRAP Ref?r FIELD to Condensate DRAIN Drain section ATTA(HMENT %r recommendations and procedures PRESSURE SWITCH One collector box pressure the pressure switch applications. trap relief robe (green port was connection in DOW2qFLOW check furnace be disconnected fhctory MUST connected or HORIZONTAL Relocate tubes as described 2. Use collector smaller A02146 applications. Fig. 13--Furnace then LOCATION (factory-supplied to in loose robe (green condensate box pressure between label) trap to robe behind inducer motor diameter to extend was previously this extended tube collector tube (pink label) * port (g_ctoryosupplied TRAP to Condensate FREEZE Drain Construct (refkr platfbrm to condensate robe. for recommendao Nrnace be attached MAY NOT to an air distribution For upflowidownflow it is level or pitched operation. For horizontal naaximum OPERATE a furnace may result and be located as possible in intem_ittent applications _bnvard forward within meet as close Refer to Air is installed pitch to ensure proper and terminating outside ensure there be a negative room 1/4-in. so that hmaace minimum condensate containing by &lct(s) tl_e space containing pressure the fine, ace. sealed to filmace the fitrnace condition Fig trap MUST 5 £br dimensions. The trap must also be properly NOTE: Table Vent or space. unit drain sloped below fire, ace. See connection to condensate UNIT to an open &ain Failure is restricted to a n_ininmm A mended with is to reduce 12-in. minimum horizontal short (5 to 8 f0 vent systems. excessive (See Fig. condensate droplets pipe of 5 ft. (See section exiting HAZARD to _bllow this caution furnace may result in a con'osive sphere Make sure all combustion nlents are met is recomo This recomn_endation from DAMAGE operation. Do not install 8.) NOTE: pipe pipe length be installed the vent 11 or 38) 13 in intermittent or contaminated and circulating to within operation. The condensate to &ainage ducts car_- air circulated the space air shall also be handled not fhrnace (See Fig. 13.) so that supply to areas outside will install 1/2Gin. for proper applications casing equipment this caution system system heat exchangers. by the filmace the return Failure to follow lengths be provided with ample space fi_r servicing and cleaning. Always comply with mininmm fire protection clearances shown on the Nrnace clearance4oocombustibles label. When clearances are met. (See Fig. 3 and 11.) UNIT other than * from secondaw all required material CONSIDERATIONS). be located where available eteca'ic power and gas supplies specifications on the furnace rating plate NOTE: section on any combustible to SAFETY trap relief PLATFORM where flooring * li2oin, A WORKING working directly wood be located so combustion-air and vent pipe maximun_ are not exceeded. Refkr to Table 8 switch. tiGriS and procedures. CONSTRUCT not be installed to the center of the distribution Ducts section PROTECTION Protection from in tube (pink to pressure cut, and connect are protected to pressure robe to relief port connection. CONDENSATE Refer length, components * * appropriate so the electrical pressure port connection. 8. (lamp be installed water. inducer and box pressure connected This furnace must parts which relief box pressure tube (green label) labeled COLLECTOR BOX. smaller parts bag) 7. Detem_ine Location for Proper Condensate Drainage door to tube (pink label) attached box pressure collector remaining which robe connected 4. Connect collector switch connection 6. Route RIGHT belom collector motor bracket switch. label) HORIZONTAL to the pressure label on main furnace box pressure diameter extended loose UPFLOW OR DOWNFLOW to the condensate Step l--General was previously connection 5. Use V2" MAX switch. bag) to extend 3. Route for the box pressure connections. 1. Disconnect pressure to in UPFLOW and used be connected See Fig. 12 or robe routing for proper connected is installed port robe. The other collector label) which trap relief NOTE: tube (pink label) is fhctory fbr use when This robe MUST condensate switch TUBING unit atmoo air require° _32°F BACK / MINIMUM INSTALLED AMBIENT OR FREEZE A93043 _\\ Fig. 14_Prohibit Installation _! PROTECTION REQUIRED on Back A93058 --€ UNIT DAMAGE HAZARD Fig. 15--Freeze This gas fire, ace may be used %r construction that: heat provided -The all electrical ducting installed hu'nace wiring, is permanently piping, according air filters, installed venting to these installation is provided, outside sealed the space negative pressure blower, causing products to the instructions. furnace containing A return casing, and the Nrnace. condition a flame with and as created rollout air duct tem_inated This prevents a by the circulating and/or &awing INJURY OR DEATH HAZARD Failure to %llow this warning could iajury, or death not install is controlled wired" to provide heat thermostatic control. constr_ction dwwall by a thermostat. continuously combustion materials. of furnace -The temperature between sethack It also prevents 55_T (13%) or shutdown. and The is under per our installation entrainment of and is deemed rise is within and the firing nameplate plate, used cleaned to clean process connect ambient Step ductwork remove &ywall system -After components construction conditions rate has been circulating be either venting, according and filters are cleaned on the must ignition, When or thoroughly debris tiom the burners to all HVA( input rate, temperatt_re to the manufhcturer's parallel with If dampers 51mace is in fi/ll-heat 15.) OR DEATH protection is installed HAZARD could result in fire must be located must be located the floor. The filrnace avoid physical damage in a public a hazardous in accordance in a residential sources above having rise and exchanger. or other to prevent are manually to prevent INJURY or inadequate and ignition installed by vehicles. garage, airplane atmosphere, with the NFG( garage_ at least the 18 in. or protected When to the 141mace is hangar, or other building the fi/rnace must be installed or NSCNGPIC. COMBUSTION operation operated, of either * When means chilled (See Fig. 16.) AND VENTILATION used to they must be * unless U.S. Ins_alla{ions: or fi/tl=cool position. (anadian Systems having 14 combustion, in accordance tion and Ventilation building codes air tiom unit fbr adequate must he provided with or on downstleam in heat with a f:tmaace, dampers a means (See Fig where protection to Cooling parallel condensation flow of air shall be adequate filrnace. space instructions. Relative coil must be installed to avoid in an unconditioned or explosion the as necessary location Provisions side of furnace or Locations EXPLOSION, Improper Equipment _he cooling property may be 32_>For lower, fieeze be taken. 3--Hazardous FIRE, after construction is completed. is complete, verii}' fhmace operating Location is installed temperatt_res AIR FOR 2--Furnace in minor [] set to the air during changed dust and construction including may result to be intem_ittent prior to occupancy. -The fi/rnace, this caution is maintained the rated rise range the nmst to [bllow If this f_/rnace value. filters construction damper 14.) Safety Never instructions. fm'nace equipped Fig. affected unit damage. 80°F (27%), with no evening use of the filrnace while the construction HAZARD measures air to the fhrnace -The air temperature rating the DAMAGE Failure components. operation entering (See its back. without air, which can cause fouling of the retmn structure control in fire, personal It may not be "hot to the structure [N[T dust into combustion plugging installed on control operation will be adversely return-air ducts to back of fi/rnace. -Clean omside air is provided for combustion. This is to minimize the con'osive eff)cts of adhesives, sealers and other Step t'umace result into d-_estructure. -The t\lmace -The FIRE, Do air Protection Section and Installations: and Air Supply jurisdiction ventilation, and dilution air with: 8.3 of the NFGC, applicable Air for Combuso provisions of the local Part 7 of the NS(NGPI(, Venting for Appliances and all authorities CARBON The MONOXIDE operation of POISONING exhaust fans, clothes &yers, attic exhaust NEGATIVE PRESSURE Make-up air MUST addition to that required Monoxide Poisoning make=up air is available. The requirements whether 18-IN. MINIMUM TO BURNERS A93044 Fig. 16--1nstNtation for the ventilation by the fl/rnace. Hazard instructions warning to determine for combustion or not the fl/mace of at least 50 cubic appliances installed 1,000 _ms, create a furnace. devices, in the venting section amount of air depend in a space having Bmh in to the (arbon and ventilation input rating upon a volmne ibr all gas in the space. Spaces having less d-_an 50 cubic the O[ TDOOR (OMB[ STION in a Garage Refer if an adequate is located feet per ventilation fans or fireplaces could (ONDITION at the be provided of these HAZARD kitchen feet per 1,000 Bmh AIR METHOD. require Spaces having at least 50 cubic feet per 1,000 Btuh may use the INDOOR ( OMBUSTION AIR, STANDARD or KNOWNAIR INFILTRATION METHOD. F[ RNA(E CORROSION Air _br con_bustion compounds, iodide. shorten which include detergents, fresheners, be contaminated fluoride, bleaches, types Outdoor halogen bromide, and solvents, salts, installations may require due to chemical (ombustion 1. Provide heat exchangers and are found in aerosol zontal air Commercial ° Buildings with ° LaundQ- rooms * Hobby * Chemical 2_ OUT° Fig. 17 illustrates indoor pools storage and for combustion tion: air, and outdoor air may be required Permanent wave Chlorinated waxes based swimming chemicals d_ pool chemicals Cleaning solvents inks, paint OPEN- and ventilation air to the outdoors. removers, and ducts 12" (300 MUST mm) of commence per Fig. 17 and Table 1. in the space per Fig. 17 and varnishes, in the space etc. shall commence within 12" (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1" (25 ram) from the sides and back and 6" (150 mm) acid washing _br clothes dQ'ers fiom the front. with the outdoors materials or horizontal equipment must air must be supplied be provided with air fbr Net to avoid air fi'om the burner area and from The opening negative Indoor Standard &aft safeguard Combustion duct to the outdoors 15 directly Air_) communicate through or spaces (crawl a vertical or attic) with the outdoors. NFPA & AGA and Known-Air-InfiRration Indoor air is permitted %r combustion, if the Slandard or Known-Air-InfiRration opening. shall or shall communicate that fl-eely communicate pressure in the equipment room or space. A positive seal must be made between the Nmace cabinet and the returnoair duct to pulling within TWO OPEND._GS OR VERTI(AL DUCTS require 1 square inch of flee area per 4,000 Btuh (550 ram2 kW) _br combined input of all gas appliances in the space per Fig. 17 and Table 1 The opening _hbric softeners Sufficient commence b. Not tess than the sum of the areas of all vent connectors (such as perchloroethylene) acid fuel=burning MUST a. 1 square inch of flee area per 3,000 Btnh (734 n'lnl2ikW) for combined input of all gas appliances in the space per Table 1 and and glues Antistatic prevent OUTDOOR with 3. ONE OUTDOOR OPENING requires: tetrachloride type refrigerants combustion. TWO hori- comnmnicat- communicate combustion input fi_r all gas appliances Table 1. _br eombus° salts or chemicals Hydrochloric All directly that freely congbustion, pem_anent c. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm2ikW) of combined not be used and cleaners Halogen Masonry it should solutions sokening Cements or spaces how to provide b. Size openings areas substances, Printing or opening(s) the ceiling and the second opening within 12" (300 mm) of the floor. to the fbllowing Carbon using buildings or craft rooms, Deqcing air %r proper of flue gases INGS, one inlet and one outlet exposures: If air is exposed Water sufficient duct(s) ing with the outdoors the outdoors a. One opening Chlorine with and dilution or vertical openings ° Air Method the space ventilation, products. of fl_mace AIR fbr combustion by chloride, cleaning and other household following DOOR not These elements could corrode fhmace life. Air contaminants sprays, The HAZARD must Rate Methods ventilation, Method and dilution, is used Table 1--Minimum Free Area Required TWO HORIZONTAL FURNACE iNPUT {1 SQ. IN.I2,000 BTUH) {t,100 Free Area of (BTUH) for Each Combustion DUCTS Opening and Duct (sq. in.) Air Opening or Duct to Outdoors SINGLE DUCT OR OPENING SO. MMtKW) TWO OP_=N_NGS OR VI=RTICAL (1 SQ. IN.t3,000 BTUH) (734 SO. MM/KW) Free Area of Round Duct Opening and Duct (in. Dia) (sq In.) 14.7 5 Round Duct (in. Dia) DUCTS {1 SQ. IN.14,000 BTUH) (550 SO. MMiKW) Free Area of Round Duct Opening and Duct (In. Dia) (Sq In.) 11 4 44,000 22 6 66,000 33 7 22 6 16.5 5 88,000 44 8 29.3 7 22 6 110,000 55 9 36.7 7 27.5 6 132,000 66 10 44 8 33 7 154,000 77 10 51.3 9 38.5 8 EXANPLES: Determining FURNACE Free Area WATER HEATER TOTAL INPUT t10,000 + 30,000 = (140,000 divided by 4,000) 66,000 + 40,000 = (t06,000 88,000 + 30,000 = (t 18,000 divided by 2,000) Table 2--Minimum Space Volumes 35.3 Sq. In. for a Single Duct or Opening 59.0 Sq. tn. for each of two Horizontal Ducts for 100% Combustion, OTHER THAN FAN-ASSISTED ACH 35.0 Sq. In. for each two Vertical Ducts or Openings divided by 3,000) TOTAL [ INPUT 30 {1,000'S I BTUH GAS 40 I RATE)50 / Ventilation and Dilution FAN-ASSISTED Air from Outdoors TOTAL {1,000'S BTUH GAS 44 166 I 88 1110 INPUT RATE) 1132 Space Volume (ft s) 1154 0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850 0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960 4,620 0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950 5,775 0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700 0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550 0.t0 0.00 6,390 NP 8,400 NP 10,500 NP 6,600 NP 9,900 NP 13,200 NP 16,500 NP 19,800 NP 23,100 NP Table CARBON MONOXIDE Failure to supply in death and/or Many homes ftlrnace POISONING outdoor require combustion, HAZARD air via grilles personal or dncts air to be supplied flora and dilution has no less volume of the n_axinmm installed in the space 2. The air infiltration changes than input 2. Equal to or greater fan-assisted water by using the Gas appliances, such Co&_ A:\%7 as a draft heater: for be provided 'Volume in ether 21ft3 ACH A04002 f)et per 1,go0 2, for all gas appliances For fan-assisted rates required such as this _hrnace: to be less than 0.40 air Volume Fan - AOH 15ft3f- 00(_If_, B-_u/hr Method shall be used, if the and than 0.10 ACH greater than volume the mininmna appliances A04003 0.60 ACH shall of tl_e space varies and shall be determined Determine than F_el and rate is not known than 0.40 ACH ACH outdoors per hour (A(H) 1. Less minimum ether were detem_ined of flue gases. 50 cubic ratings The Known Air Infiltration Rate infiltration rate is known to be: Infiltration 1. For Volumes flora the Yationa/ 54-2002,&3.2.2: Method: 1. The space Btuh Space hoodoequipped The _b.mace combustion air supply must accordance with this instruction manual. The Standard could result i11iury. ventilation, 2:Minimum following equations Z223.J-2002/YFP.t per Table required volume space and add the volumes together required volume %r the space. not be used. The with the number 2 or Equations to get the total combined in Bmihr I_.,, combined input of all other than fan-assisted appli- of 1 and 2. for each appliance Iom_ ances input of all fan-assisted appliances in Bm&r in the ACH mininmm air changes per hour (ACH The following requirements the Known Air Infiltration 16 shall not exceed apply to the Standard Rate Method. 0.60.) Method and to 1 SQ IN. PER4000 BTUH* TO OUTDOORS VENT THROUGH ROOF CIRCULATING[ DUCTS AIR _ I 12"MAX I 12" MAX 1 SQ IN. PER2000 BTUH* T 1 SQ IN. PER 4000 BTUH* Fco D ca :_ O o m O co o o DUCTS TO OUTDOORS a INTERIOR HEATED SPACE S o 1 SQ IN. PER 4000 BTUH* UNCONFINED SPACE o a: m z 6" MtN (FRONT)t Ld o z< a: <: LU 12 "_ MAX t 12"*MAX 1 SQ IN. PER 1000 BTUH* IN DOOR ORWALL kZ 1 SQ IN. PER2000 BTUH T _ 1 SQtN. PER 1000 BTUH* IN DOOR S ORWALL o L12" MAX CIRCULATING AIR DUCTS 1SQ IN PER4000 BTUH* TO OUTDOORS *Minimum NOTE: dimensions - l CIRCULATING AIR DUCTS of 3 in. Use any of the following combinations of openings: A&B C&D D&E F&G * Minimum minimum opening size is 100 sq in. with dimensions of 3 in. 'Minimum of 3 in when type-B1 vent is used A03175 A03174 Fig. 17--Air for Combustion, Ventilation, for Outdoors 1. Adjoining a There rooms can be considered are no closable b. Combining spaces doors between Each of the total input rating of all gas appliances less than commence second 100 in. 2 (0.06 within opening 12" (300 shall commence the floor. The mininmm at least spaces on space floor communicating spaces nest openings in doors 2 in.S/l,000 a. Walls and ceilings shall ous, sealed and in the space, within opening ceiling floor levels and openable c. Other openings around shall be floors, between if connected Bmh (4,400 levels. The volumes considered NOTE: as ef_kct of the louvers, free fi'ee area of at least of total input rating communicates *nay be considered permanent ventilation openings fi'ee area of at least 1-in.2/4,000 3. In spaces that of louvers provided a space there that freely When directly to outdoors having Bmh of total input rating for d_e Indoor or grilles Air buildings with tight electrical have a 60 percent and gas lines, is unknown, Louvers construction, additional using the methods described Air Method section. at etc. the blocking must be considered. If the it may be fi'ee area, and metal fi'ee area. Screens, than 1i4oin. mesh. and wal! panels, of an opening, design joints sole plates between have a 20 percent so they cannot combustion between joints, and include when used, and grilles must be be closed. air ducts are used, they nmst be of the same cross sectional area as d-*eflee area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 Method, should be adequate to provide air for combustiom ventilation and diludon of flue gases. However, in unusually louvers These in. (80mm). Combustion infiltration permanent MUST be provided Outdoor Combustion that wood or sealed are weatherstripped and screens or grille have a continu_ are gasketed or sealed. the fi'ee area grilles, of a louver constructed are adequate in the space. use area must not be smaller wit}* the outdoors all gas appliances In detem_ining assumed all gas appliances. 2. An attic or crawlspace fbr plumbing, of by one or more permao or floors having ramS&W) be to the outdoors and door frames, wall-ceiling and Dilution as Openings windows are caulked window penetrations shall exposed b. Doors of is defined bare'let. shall 12" (300 ram) of air openings vapor and the (See Fig. 18.) on dif£)rent different of the dimension 3 in. (80 ram). c. Combining nrm) opening Bmh (2,000 mm2&W) m 2) One for Combustion, Ventilation, from Indoors L nusually tight construction ( onstr_/ction with: rooms. on same floor level 1 in.2/1,000 not Fig. 18--Air part of a space ik have free area of at least but and Ditution Combination of Indoor and Outdoor 1. [ndoor openings shall compy Air Method below and, air 2. Outdoor in the openings Combustion 17 with shall be located Air Method mentioned Air the Indoor as required previously Combustion in the Outdoor and, 3. Outdoor openings a. (alculate shall be sized the Ratio required below. volume fbr Indoor Space volume (ombustion divided Air 3. (onstruct 20. by Method plenum 4. If downflow to dimensions subbase (KGASB) specified in Table is used, install 1 and Fig. as shown in Fig. 2!. b. Outdoor opening size Ratio in a. above. c. Minimum size required of rednction Factor is 1 minus the If (oil Assembly KCAKC Outdoor in Outdoor openings Combus{ion multiplied by reduction dimension of air openings 111111) as %llows: of all Indoor Factor shall Air be the Method in b. above. size NOTE: above Remove they interfere The mininlnnl To remove shall be not tess than 3 in. (80 install t:umace flanges perforated, or dtlct flange it breaks as shown perR_rated, with mating fi/rnace duct pliers 0 Part No. CD5 or CK5 or Coil Box Part No is used, off_ Be carefld in Fig. 22. discharge duct flanges on coil on downflow discharge tool to bend of sharp duct flange edges. when subbase. flange, use wide back and forth until (See Fig. 23.) BNSTALLATION Step l--Leveling When furnace Legs (If Desired) is used in opflow position with side inlet(s), leveling UNIT legs may be desired. (See Fig. 19.) Install field-supplied, corrosion-resistant 5/16-im machine bolts and nuts. NOTE: The nlaximmll 1. Position flmaace diameter Holes length on in hole. (Install corner not exceed and drill of furnace. could result in intermittent unit 1- 1/2 in. Do not bend a 5/16=in. will affect (See Fig. 19.) cycling locations. duct flanges airflow or premature flange shown inward as shown across heat exchangers completely in Fig, 23 heat or bend in Fig 23 This arid may cause limit exchanger fifilure. it inward a nlininlnm Remove duct of 2!0 ° as if desired.) nut on other side of fl/mace outside nut to provide nut to secure base. (Install Step flat desired height, and tighten 3--hstaHation in Horizontal Applications inside tNIT arrangement. NOTE: Bottom closure must be used when leveling See Bottom Closure Panel section 2--_nstaHation in Upfiow and legs are used NOTE: For downflow applications, use on combustible flooring when manufacturer) not required Part No. KGASB0201ALL when dlis fhmace Part No. CD5 or CK5, 1. Determine 2. (onstruct application being hole in floor per is used. is installed is approved for (available fl'om Special or (;oil Box Part No. KCAKC from Table dimensions specified is draining. When 3 and Fig. 20. Step flmlace suspended, shelf When in intermittent MUST in a horizontal or pad should be position bottom brace supported when to ensure proper supports unit is supported support unit sides and fi'om file ground, sides and center blower shelf 4-==Air Ducts GENERAL The REQUIREMENTS duct system accepted American Society- of Heating, Engineers (ASHRAE) duct system CFM a furnace circulated Nrnace, Secure ductwork supply° approved 18 casing tape (ACCA), Sheet to by: Air Metal arid (SMACNA) or and Air Conditioning The Ai_' 5)',slems DesNr_ Gzddelocal the required distributor. system The design pressure. is installed the remm according published Association fi'om your be sized to handle static sized those Refrigerating available by the furnace the furnace furnace Seal should and as National or consult tables at the design When designed such Association ContIactors [i_ves refkrence Legs be standards Contractors Air Conditioning A89014 should national Conditioning Fig, 19--Leve{ing of may result These furnaces can be installed horizontally in either horizontal left or right discharge position. In a crawlspace, fmnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended flora each corner by hanger bolts and angle iron supports. (See Fig. 24.) (Jut hanger bolts (4 each 3i8=im all=thread rod) to desired length. Use 1 X 3i8=im flat washers. 3/%in. lockwashers, and 3/8=in. nuts on hanger rods as shown in Fig. 24. Dimples are provided for hole locations. (See Fig. 2.) 3. in Table is used blocks area. (?oil OPERATE tllis caution length furnace center blower base in on manufacturer's installed NOT to %llow operation. The entire Downflow this fhrnace special base MAY Failure Applications Assenlbly used, OPERATE this caution if desired.) 4. Adjust Step NOT to follow operation. nut on bolt and then install bolt and nut flat washer another Locate closure panel may be used as guide 2. For each hole. install washer of bolt should back. hole in each bottom in bottom 3. Install its MAY Failure so that the to areas outside supply air shall also be handled and temlinating with proper and return-duct or duct sealer. outside fasteners ducts caia T air _he space containing by a duct(s) the space containing for type of ductwork connections to furnace the sealed with to the used. code A96283 Fig. 20--Floor and Plenum Opening Dimensions FURNACE CD5 OR CK5 COIL ASSEMBLY OR KCAKC COIL BOX FLOORING SUBBASE -- SHEET METAL PLENUM PLENUM FLOOR -OPENING __ FLOOR OPENING __ A96284 A96285 Fig. 22--Furnace, Plenum, and CoN Assembly or Coil Box Installed on a Combustible Floor Fig. 21--Furnace_ Plenum, and Subbase Installed on a Combustible Floor Table 3--Opening FURNACE CASING WIDTH Dimensions (In.) PLENUM OPENING Upflow Applications Downflow Applications t7ot/2 Flooring B C D 24-1/8 16-5/8 24-3/4 15-7/8 19 16-1/2 19-5/8 20-3/8 15-1/8 19 16-3/4 Downflow Applications on Combustible Ftooring NOT Using KGASB Subbase Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box 15-1/2 19 16-1/2 20 Upflow Applications 19-1/2 24-1/8 20-1/8 24-3/4 19-3/8 19 20 19-5/8 18-5/8 19 20-1/4 20-8/8 on Non-Combustible Flooring Downflow Applications on Combustible Ftooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box Downflow Applications on Combustible Ftooring NOT Using KGASB Subbase Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box 19 19 20 20 Upflow Applications 23 24-1/8 23-5/8 24-3/4 22W/8 19 23-1/2 19-5/8 Downflow Applications on Combustible Ftooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembty or KCAKC Coil Box 22-1/8 19 23-3/4 20-3/8 Downflow Applications on Combustible Ftooring NOT Using KGASB Subbase Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box 22-1/2 19 23-1/2 20 Downflow Applications 24ott2 on Non-Combustible A 16 Downflow Applications on Combustible Ftooring Using KGASB Subbase Furnace with or without CD5 or CK5 Coil Assembty or KCAKC Coil Box Downflow Applications 21 FLOOR OPENING APPLICATION on Non-Combustible Flooring 19 Horizontal DISCHARGE FLANGE Furnaces (onnect DUCT supply-air supply-air NO &ct to supply duct attachment supply/outlet must air opening ONLY or air conditioning on ftm_ace be connected coil casing The to ftmaace (when used) DO NOT cut main f_rnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to fhrnace main casing. RETETRN AIR (ONNECTIONS YES The t:t_rnace installed I 210 ° MIN a£f_ct another of combustion ..................... another _;,/rnace to prevent through transmission unconditioned system barrier perforn_ance. When is recommended. Maintain a l-in. clearance ductwork fbr a distance NFPA 90B or local For a fhmace between of vibration space should air be ductwork conditioning FIRE and A failure is use& a vapor Jr{jury, or death Never connect return-air to supply upflow air fiom the t_urnace. See Upflow The coil, the outlet duct shall light assistance stream. can be viewed or a probe The cover %r possible can be inserted attachment openings for sampling shall prevent using Metal ACOUSTICAL duct systems of main &ct the air TREATMENT branch rake-off elbow may construction acoustical lining 90B as tested SUPPLY standard and fibrous on fibrous ductwork by UL Standard 181%r glass ducts shall comply with NFPA (lass 1 Rigid air ducts. --9 Furnaces Connect supply-air duct to 3/4-in flange on _hrnace supply-air outlet. The supply-air duct attachment must ONLY be connected to fbrnace supply-/outlet-air duct flanges or air conditioning coil casing (when used) DO NOT supply side air duct, humidifier, ries MUST be connected Downflow Furnaces (onnect supply-air supply-air cut main fhmace casing or other accessories. external to ft_rnace main duct attachment to supply-air must opening ONLY nected material, supply-air to an accesso_- duct attachment subbase nmst be connected external to fi/rnace main in fire, personal to the back of the t'umace side(s) pem_itted to bottom, sides in duct must be connected (left or air portion any portion of return-air and Horizontal return-air duct of the furnace casing. DO NOT duct to back of furnace casing. Furnaces must be connected to return-air opening as shown in Fig. 2 DO NOT cut into casing sides or back any portion of return-air duct Bypass humidifier connecbe made 5--FHter at ductwork or coil casing sides exterior to Arrangement FIRE, CARBON HAZARD MONOXIDE Failure to %11ow this warning injury, or death Never operate unit without AND POISONING could a filter result in fire, personal or with blower access to attach casing be connected or _i_ctory approved could result All accessoFactory-supplied ONLY washable Determine framed location filters %r are shipped filter to t'umace location, location be con- air conditionto attach supply All accessories casing. 2O and quantity- shipped and size of bottom with this _hmace. and side return-air in blower and relocate retaining wire if necessaDSee Table 4 to determine size %r desired filter location. Table 4 indicates on t_urnace. The ing coil casing. DO NOT cut main fhmace casing side air duct, humidifier, or other accessories. MUST is in panel removed. supply/outlet or air conditioning coil casing (when used), when installed on non-comhustible material. When installed on comhustible in the on ducts only side remm comparm_ent duct air plenum on ftm_ace connect Step Both AIR (ONNECTIONS L pflow type, shall be an opening or a combination of bottom and side(s) of main furnace as shown in Fig 2 Bypass humidifier may be attached into tions should ft_rnace internal acoustical lining As an ahernative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA applications return-air provided to attach and 10 fi require ducts duct connections Downflow leaks. that do not have a 90 degree to the first to %11ow this warning unused The DU(TWORK not of the direct-vent or panel covering with Furnaces right), casing be provided with a removable access panel. This opening shall be accessible when the ft,.mace is installed and shall be of such a size that the heat exchanger fan communicating HAZARD passing materials with a cooling fan or act to mix products air, and that the air circulating or in a return enhance code fbr _hrther requirements. not equipped and position. Return-air of 36 in. horizontally air supply appliance to Ductwork insulated fi'om comhustible designed A93029 Flanges used be by the air circulating in an enclosure any door fan compartment the closed be if installed only when ft_rnace should shall created appliance's fhel-burning operable connections air system pressure with circulating of the fhrnace, YES Flexible its remm I cannot Fig. 23--Duct and so that negative correct filter filter filter size, See Fig. 2 for openings. A3-1N MINIMUM CLEARANCE TO INTAKE IS REQUIRED 3/8-1 N. ROD ANGLE --_ IRON OR EQUIVALENT ALTERNATE SUPPORT LOCATION 4-IN MIN 8-IN MAX "_ (B) (A) (B) (A) ROD LOCATION USING DIMPLE LOCATORS tSEE DWG 3/8-1N DIMENSIONAL FOR LOCATIONS) NOTES: (A) PREFERRED ROD (B) ALTERNATE 13/16-1N. MAX ALTERNATE SUPPORT LOCATION FROM BACK (B) & WASHER (4) REQD PER ROD ROD 1 A 1 In. clearance minimum between top of furnace and combustibIe material. 2 The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage. 3 Bottom side combustion-air entry cannot be used when furnace is installed with hangers as shown LOCATION LOCATION A96209 Fig. 24_Crawlspace TaNe 4--Filter FURNACE CASING W{DTN (IN.} FILTER SIZE (IN.l* (1)16X25X1 24_1/2 FILTER Bottom Return (1) 16 X 25 X 11- 21 (1 or 2 / 16 X 25 X 1 WASHABLE FILTER \ TYPE FRAMED (1) 16 X 25 X 11- Cleanable (1)20 X 25 X It C_eanab_e (1 / 24 X 25 X 11- * Filters can be field modified by cutting to the desired can be ordered from your distributor or dealer ? Factory-provided with furnace. (UT Application information Side Return 17-1t2 HorizontN C_eanable RETAINER SPRING size. Alternate sizes \ HAZARD Failure to %llow this caution may result in minor personal A00217 injury Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, and appropriate protective clothing. gloves, Bottom Fig. 25--Filter Installed return-air may opening be used Filter may need to be cut to fit some as shown UNIT MAY Failure NOT OPERATE to fk_llow this caution may result in intem_ittent unit operation. For airflow requirements above 1800 CFM, openings or the bottom for airflow see Air Deliveo- only will ensm'e adequate requirements above remm Step 6--Bottom These _i/rnaces To remove Cmosure are shipped bottom closure 1. Tilt or raise furnace air panel. 1800 CFM. 2. Rotate NOTE: Side returnoair openings can ONLY be used in 1_PFLOW configurations, Install _ter(s) as shown in Fig, 25, 3. Remove 2i with all 4 orientations. I:tmaace widths Install filter 26. in bottom return-air opening. side return air is used. table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, in Fig for Side Inlet Panel with bottom enclosure This panel MUST panel, perfbm_ and remove panel installed be in place when the following: 2 screws holding fiont filler (See Fig. 27.) fiont filler panel bottom closure downward panel. to release holding tabs. 21-IN.WIDE CASINGS ONLY: SUPPORT RODS (3) EXTEND 1/4" ON EACH SIDE OF FILTER AND REST ON CASING FLANGE 171/2oIN.WIDE CASINGS ONLY: INSTALL FELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER. PI( and all authorities having jurisdiction. Gas supply line should be a separate line running directly fi'om meter to t:urnace, if possible. Refer to Table 5 fbr recommended gas pipe sizing. Risers mnst be used to connect to fhrnace piping with appropriate hanger ever?" 6 ft. Joint compound sparingly and only resistant to propane FIRE stlaps, to male and to meter. hangers, (pipe dope) should of joints. Pipe dope threads all gas of 1 be applied must be gas. OR EXPLOSION HAZARD Failure to %llow personal ir!iury, -Connect gas pipe to t:m'nace using a backup damaging Support etc. l_se a minimum this warning could result in fire, explosion, or death wrench to avoid gas controls -Gas vah'e shutoff switch MUST be thcing _:bp,vard or tilted upward. -Never purge a gas line into test tbr gas leaks with a combustion an open flame. available soap solution made specifically leaks to cheek all connections. • WASHABLE FILTER -Use proper manit'old, length -It" a flexible connector having jurisdiction, fl/rnace gas valve flul_ace casing. Install a sediment installed by FILTER SUPPORT in riser a tee section manifold If local codes FILTER RETAINER always iron and extend end of tee leading Trap gas shutoff so a capped extend union valve can be to fimaace should joint at outside Then connect nipple a ground another installed of 2 in to flmaace the use of a flexible served by authori w be a n_ininmm use a new listed connector. has previously shall to riser of on gas control or allowed pipe Capped Place and manual allow stress leading Never a commercially for the detection of tee is vertical. of gas controls. control is required black trap into lower level to avoid connecting straight-through nipple of pipe chamber. Use below between gas (See Fig. 28) gas appliance connector, Do not use a connector which gas appliance. A00290 Fig. 26--Bottom Filter ,i Arrangement FIRE 4, Reinstall fiont filler panel and screws Step 7--Gas Piping Gas piping must be installed in accordance with national and local codes Refer to current edition of NFGC in the United States Canadian installations must be made in accordance OR EXPLOSION Failure to %llow serious injury, death test £_r gas leaks with cially available An accessible flul_ace plugged soap causing manual casing tapping, shutoff made property : NOMINAL IRON PIPE SIZE result in Use a commer- tbr test gauge personal be installed the injury or external A 1iS=in connection, Capacity £_r A fire or explo= 6 fi of furnace to NPT MUST be of Pipe* LENGTH OF PiPE (F7) INTERNAL DIAMETER {BN.) damage, valve MLST Table 5--Maximum i could specifically all connections. and within accessible exactly damage. an open flame. solution of leaks to check sion could result toss of lit). the or property Never detection with NSCNG° HAZARD the safety warnings 10 20 30 40 50 (BN.) BOTTOM CLOSURE PANEL FRONT PANEL FILLER Bottom Closure 0.622 175 120 97 82 73 314 0.824 360 250 200 170 151 1 1.049 680 465 375 320 285 1-114 1.380 1400 950 770 660 580 1-tl2 1.610 2100 1460 1180 990 900 * Cubic fl of gas per hr for gas pressures of 05 psig (14-in. wc) or less, and a pressure drop of 05qn. wc (based on a 060 specific gravity gas). Ref: Table 12-2 NFPA 54-2002. A93047 Fig. 2g--Removing tl2 Pane{ 22 Step 8--Electrical GAS A SUPPLY MANUAL J See Fig 30 £;orfield wiring diagram showing typical field 115=v and 24-v wiring Check all _hctory and field electrical connections for tighmess II V A" J Connections Field=supplied wiring shall conform with the limitations of 63_T (35°C) rise ELECTRICAL Failure death. SHOCK HAZARD to follow this warning Blower access control center. panel bypass or close could result door switch No component in serious opens operation switch with panel injury or l l5-v can power occur to Do not removed. A93324 Fig, 28--Typical Gas Pipe Arrangement F[ RNACE Failure installed immediately ftm_ace and downstleam NOTE: upstream of gas supply of manual shutoff valve. The gas valve inlet pressure use as test gauge exceed connection maxin_um 0.5 psig tap connection providing (14-in. connection is suitable test pressure wc) stated to DOES on gas valve. NFGC in the United national be pressure plumbing connected. check After States and and exceeds leak gas codes at furnace tested or NSCNGPI( all connections for leakage If pressure in accordance in Canada, bei:ore the t_urnace have been made, prior to operating purge to and water Furnace control electric manual shutoff shutoff gas switch located on furnace valve before test. supply pressure shall be local, and rating plate has been supply lines and Refkr to rating cations minimum inlet supply pressures marked the f£maace burners ON and OFF. on the rating plate all Electrical 040-08 040-12 OPERATING VOLTAGE RANGE[ operation cold weather _br proper operation and with Max* Min* MAX UNIT AMPS 115--60--1 127 104 115--60--1 127 104 060-08 115--60--1 127 06042 115--60--1 08048 make or to handle toad or Table 6 for equipment plate (NEC) connections ANSI provided imposed in NFPA certain to that specified check to be sure that service electrical Code connections, correspond by this by power electrical accordance 70°2002 that on unit equipment. with specifiNational and any local codes (7ode CSA C22.1 or authorities having jurisdiction. Use a separate, filsed branch electrical circuit containing sized Nse or circuit breaker [br this furnace. See Table size Table 6--ElectricN VOLTS-HERTZ-PHASE in furnace during or ordinances that might apply For (anadian installations, all electrical connections must be made in accordance with Canadian and located UNIT SIZE Also, electrical and phase is sufficient Make pipe nmst be n_axinmm may result fi'eezing be grounded with fi'equency, Electrical the must proceeding voltage, with gas valve and accessible within pipes 115°V WIRING (See furnace. 0.5 psig (14oin. wc), gas supply OPERATE NOT disconnected fiom _i_rnace and capped be_bre pressure test. If test pressure is equal to or less than 0.5 psig (14=in. wc), turn off The stopping Befbre should NOT contlol will lock out (ontrol is grounded through green yellow wire routed to gas valve and burner box screw Fig. 460 Piping MAY to _bllow this caution fuse within specifications. sight fiom A disconnecting and readily accessible means must be to Nmace. Data AMPACBTY? MBN WIRE SRZE 6.1 8.4 14 44 15 7.3 10.0 14 37 15 104 6.1 8.4 14 44 15 127 104 7.1 9.8 14 38 15 115--60--1 127 104 9.5 12.8 14 29 15 08042 115--60--1 127 104 7.6 10.4 14 36 15 08048 115--60--1 127 104 10.0 13.4 14 28 15 080-20 115--60--1 127 104 14.1 18.4 12 31 2O 10048 115--60--1 127 104 10.2 13.5 14 27 15 tOO-20 115--60--1 127 104 14.8 19.3 12 30 20 120-20 115--60--1 127 104 14.6 19.1 12 30 2O UNiT MAX WRRE LENGTH {FT)_ * Permissible limits of voltage range at which unit will operate satisfactorily. t Unit ampacity = 125 percent of largest operating component's fu{I load amps plus 100 percent of all other potential operating components' load amps $ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended. 23 a properly 6 for wire MAX FUSE OR CKT BKR AMPS** (EAC, humidifier, etc.) full Table 7--Approved Combustion-Air ASTM SPECBFJOATION (MARKED ON MATER_AL) D1527 MATERIAL PiPE ABS Pipe -- PVC Pipe -- D1788 FITTINGS and Vent Pipe, Fitting and Cement Materials SOLVENT CEMENT AND PRBMI=RS DESCRIPTBON Schedule-40 Schedule-40 Solvent Cement D2235 For ABS -- -- For ABS D2241 PVC Pipe -- SDR-21 & SDR-26 D2466 PVC -- Fittings Schedule-40 D2468 ABS -- Fittings Schedule-40 Solvent Cement D2564 For PVC -- -- D2881 ABS Pipe Fittings For PVC DWV at Schedule-40 D2665 PVC Pipe Fittings DWV F438 CPVC -- Fittings Schedule-40 F441 CPVC Pipe -- Schedule-40 F442 CPVC Pipe -- F493 For CPVC F628 -- ABS For PVC Pipe -- --- F891 PVC Pipe -- NOTE: Proper polarity is incorrect, flash rapidly polarity must control be maintained center fault and Alrnace will NOT SDR Solvent Cement -- F656 For CPVC Cellular Core DWV at Schedule-40 Primer Cettular Core Schedule-40 for 115-v wiring code indicator If ELECTRICAL operate. HAZARD select to %11ow this warning death, or property damage. Do not connect aluminum and furnace. could wire Use only copper result between & DWV light will to follow SHOCK AND FIRE this warning death, or property damage, If manual disconnect switch Failure IPS sizes For PVC Failure FIRE tPS sizes in serious injury, disconnect a location electrical where HAZARD may result in serious is to be mounted a drill or fhstener will inju W, on furnace, not contact or gas components. 24-V WIRING switch Make field 24-v thermostat connections at 24-v terminal block on fm'nace control For proper cooling operation, Y wire from thermostat MUST be connected to ¥ terminal on filrnace connol, as shown in Fig. 30. The 24=v terminal block is marked fbr easy connection of field wiring. (See Fig. 320 The 24=v circuit contains a 3=amp, automotive4ype fuse located on fi/mace control. (See Fig. 33.) Any electrical shorts of 24-v wiring during installation, service, or maintenance may cause lime to blow. If filse replacemerit is required, use only a time of identical size (3 amp) and type. The control will flash code 24 when fuse needs replacement. wire. (See Fig. 29.) ELECTRIC DISCONNECT SWITCH NOTE: Use AWG No. 18 color-coded copper thermostat wire fbr lengths up to 100 it. For wire lengths over 100 ft, use AWG No. 16 wire. A93033 A( CESSORIES Fig. 29--Disconnect ELECTRICAL SHOCK Failure to fbllow death, or property to NEC trical (7ode CSA injury FIRE could and Furnace l. Electronic Air Cleaner (EAC) Two quick-connect terminals marked EAC-I and EAC°2 are provided for EAC connection. (See Fig 33) These terminals are energized with 115v (1 0-amp maximum) during blower motor operation. HAZARD result in serious inju W, damage. have an unintemlpted ANSI C22.1 if an electrical NFPA 70-2002 or local codes fimlt should electrical wire or conduit installed in accordance use gas piping AND this warning The cabinet MUST according Switch or unbroken and Canadian to minimize for electrical with existing electrical as an electrical Elec= personal occur. This may consist approved ground codes. NOTE: DO NOT connect f:urnace control HI_M tem_inal to HUM (humidifier) terminal on Thermidistat-f_L Zone Controller or simitar device See Thermidistat TM, Zone Controller, thermostat, or controller manufi_cturer's instructions fbr proper connection. ground of when Do not ground. J-Box Relocation 1. Remove 2 screws holding auxiliaQ' J-box. (See Fig 31.) 2. Rotate J=box 180 ° and attach box to leit side, using holes provided. 24 -+ Table 8--Maximum ALTITUDE UNiT SRZE 3 4 5 6 1 5 NA NA NA NA NA 1-1/2 70 70 65 60 60 55 2 70 70 70 70 70 7O 060-08 036060 060-16 1-1/2 20 15 10 5 NA NA 2 70 70 70 70 70 7O 080-12 080-16 080-20 1-1/2 10 NA NA NA NA NA 2O 120-20 2001 to 3000 ALTITUDE 3001 to 4000 ALTITUDE 4001 to 5000t NUMBER OF 90 ° ELBOWS 2 100-16 100-20 ALTITUDE Vent Pipe Length (Ft) 1 040-08 040-12 0 to 2000 Allowable VENT PIPE DIAMETER (IN.) 2 55 50 35 30 30 2-1/2 70 70 70 70 70 7O 2 5 NA NA NA NA NA 2-1/2 40 30 20 20 10 NA 3 70 70 70 70 70 7O 2-1/2 10 NA NA NA NA NA 3* 70 70 70 70 70 7O NUMBER OF 00 ° ELBOWS VENT PIP _= DIAMETER (iN.) 1 2 3 4 5 6 040-08 040-12 1-1/2 67 62 57 52 52 47 2 70 70 70 70 70 70 060-08 036060 060-16 1-1/2 17 12 7 NA NA NA 2 70 67 66 61 61 61 080-12 080-16 080-20 2 49 44 30 25 25 15 2-1/2 70 70 70 70 70 70 100-16 100-20 2-1/2 35 26 16 16 6 NA 3 70 70 70 70 66 61 120-20 3* 63 62 62 61 61 61 UNiT SBZE UNiT SRZE NUMBER VENT PIPE OF 00° ELBOWS I 2 3 4 5 6 040-08 040-12 1-1/2 64 59 54 49 48 43 2 70 70 70 70 70 70 060-08 036060 060-16 1-1/2 16 11 6 NA NA NA 2 68 63 62 57 57 56 080-12 080-16 080-20 2 46 41 28 23 22 13 DIAMETER (iN.) 2-1/2 70 70 70 70 70 70 100-16 100-20 2-1/2 33 24 15 14 5 NA 3 70 70 70 66 61 56 120-20 3* 59 59 58 57 57 56 UNiT SBZE NUMBER VENT PIPE I 2 3 4 5 6 040-08 040-12 1-1/2 60 55 50 45 44 39 2 70 70 70 70 70 70 060-08 036060 060-16 1-1/2 15 10 5 NA NA NA 2 64 59 58 53 52 52 080-I2 080-16 080-20 DIAMETER (iN.) OF 00° ELBOWS 2 44 39 26 21 20 11 2-1/2 70 70 70 70 70 70 100-16 100-20 2-1/2 31 22 13 12 NA NA 3 70 70 67 62 57 52 120-20 3* 56 55 54 53 52 52 * Wide radius elbow ? Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA--Not Allowed; pressure switch will not make NOTES: 1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur. 2. Assume two 45 ° elbows equal one 90 ° elbow Long radius elbows are desirable and may be required in some cases 3. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count. 4. The minimum pipe length is 5 fl for all applications 25 -+ Table8--1Vlaxirnum AllowableVent PipeLength(Ft) Continued ALTITUDE 500t to 6000t ALTITUDE 600t to 7000t ALTITUDE UNiT SiZE ALTITUDE 2 3 4 5 6 040-08 040-12 1-1/2 57 52 47 42 4O 35 2 7O 70 70 70 7O 7O 060-08 036060 060-16 1-1/2 14 9 NA NA NA NA 2 6O 55 54 49 48 47 080-12 080-16 080-20 2 41 36 23 18 17 8 2-1/2 7O 70 70 70 7O 7O 100-16 100-20 2-1/2 29 21 12 11 NA NA 3 7O 67 62 57 52 47 120-20 3* 53 52 50 49 48 47 UNiT SIZE NUMBER VENT PIPE OF 90 ° ELBOWS OIAIVIETER (IN.) 1 2 3 4 5 6 040-08 040-12 1-1/2 53 48 43 38 37 32 2 70 70 68 67 66 64 060-08 036060 060-16 1-1/2 13 8 NA NA NA NA 2 57 52 5O 45 44 43 080-12 080-16 080-20 2 38 33 21 16 15 6 2-1/2 70 70 68 67 66 64 100-16 100-20 2-1/2 27 19 10 9 NA NA 3 68 63 58 53 48 43 120-20 3* 49 48 47 45 44 43 1 2 3 4 5 6 040-08 040-12 1-1/2 49 44 39 34 33 28 2 66 65 63 62 60 59 060-08 036060 060-16 1-1/2 12 7 NA NA NA NA 2 53 48 46 41 40 38 NA UNIT SiZE 080-12 080-16 080-20 NUMBER VENT P_PE (IN.) OF 90 ° ELBOWS 2 36 31 19 14 12 2-1/2 66 65 63 62 60 59 100-16 100-20 2-1/2 25 17 8 7 NA NA 3 63 58 53 48 43 38 120-20 3* 46 44 43 41 40 38 UNIT SIZE 040-08 040-12 800t to 9000? OF 90 ° ELBOWS 1 OIAMETER 700t to 800Ot NUMBER VENT PIPE DIAIVIETER (IN.) NUMBER VENT PIPE OF 90° ELBOWS DIAIVIETER (IN.) 1-1/2 1 2 3 4 5 6 46 41 36 31 29 24 2 62 6O 58 58 55 53 060-08 036060 060-16 1-1/2 11 6 NA NA NA NA 2 49 44 42 37 35 34 080-12 080-16 080-20 2 33 28 17 12 10 NA 2-1/2 62 6O 58 56 55 53 100-16 100-20 2-1/2 23 15 7 5 NA NA 3 59 54 49 44 39 34 120-20 3* 43 41 39 37 35 34 Wide radius elbow i- Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA--Not Allowed pressure switch will not make NOTES: 1 Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur 2 Assume two 45 ° elbows equal one 90 ° e@ow Long radius elbows are desirable and may be required in some cases. 3 Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count. 4 The minimum pipe length is 5 ft for all applications 26 -_ Tab{e8--MaximumAllowableVent PipeLength(Ft) Continued ALTITUDE 2 3 4 5 6 1-1/2 42 37 32 27 25 2O 2 57 55 53 51 49 47 2 45 40 38 33 31 29 2 30 25 14 9 7 NA 060-08 036060 060-I6 080-12 080-16 080-20 OF 90 ° ELBOWS 1 DIAMETER 040-08 040-12 9001 to 10,000t NUMBER VENT PIPE UNiT S_ZE (BN.) 2-1/2 57 55 53 51 49 47 100-16 100-20 2-1/2 21 13 5 NA NA NA 3 54 49 44 39 34 29 120-20 3* 39 37 35 33 31 29 * Wide radius elbow ? Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA--Not Allowed; pressure switch will not make NOTES: 1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur. 2. Assume two 45 ° elbows equal one 90 ° elbow Long radius elbows are desirable and may be required in some cases 3. Elbows and pipe sections within the furnace casing and at the vent termination should not be induded in vent length or elbow count. 4. The minimum pipe length is 5 fl for all applications .... .... --- 24-V TERMINAl BLOCK FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WiRiNG FACTORY 115-V WIRING WiRE NOTES: FURNACE 1. Connect YZterminal in furnace as shown for proper blower operation. 2. Some thermostats require a "C" terminal connection as shown. 3. if any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A02174 Fig. 30--Typical 2. Humidifier and screw 33) HUM terminal is energized EAC dttring terminal connection with 24v (0.5-amp ((oM (See Fig When maximum) tem_inals blower may be added controlled relay if humidifier connected operation I venting to spillage operation adjacent Furnaces require vent system. to t\_rnace, outdoor atmosphere. accordance to these a dedicated, (one All air for combustion and all flue The venting inst_,_ctions. gases system 58MSA t\mlace is taken t'rom the are shall discharged be installed to in 27 < ategory system attached system £t_rnace and vent, is desired 9--Venting only) sealed venting the remaining 115-v Wiring Diagram an existing original gas valve is energized A field=supplied, The 5SMSA area (HErM) for 24-v humidifier when Step terminal 24°v) are provided Application REMOVAL OF EXISTING EL RNACES FROM (OMMON VENT SYSTEMS (HUM) A quick-connect NOTE: Heating and Cooling appliances could cause leakage of combustion I furnace may no longer be sized An improperly the formation of condensate products is removed or replace& to properly sized (ategory of condensate and combustion into the living space, the vent in the products, etc. CARBON MONOXIDE Failure to follow connected in carbon following connected while outlined to the venting could result The POISONING the steps system shall to the venting fbr each appliance placed poisoning be being connected In Canada, construct all cornhustion-air and vent pipes [br this unit of CSA or UL( listed schedule-40 PVC, PV(-DWV or ABS= DWV pipe and pipe cement. SDR pipe is NOT approved in Canada into operation or death fbllowed system all other appliances HAZARD below being rnonoxide steps standards See Table 7 for approved rnaterials %r use in the U.S.A. See Table 8 fPr nlaxinmm pipe lengths and Fig 39, 40, and 41 fbr exterior piping arrangements for each placed appliance into operation, to the venting system Vent pipe re*ruination must be installed with adequate clearances to building openings and equipment to comply with national and tocal codes, are not in operation: 1. Seal any unused 2. Inspect openings t!-_e venting pitch, as required Z223A=2002NFPA Installation 3. As far as practical, and all doors connected deficiencies, close between which all building doors system are UNIT leakage, could the space in which to the venting fireplace cause an other and any appliance the venting system. range and bathroom hoods at maximum 6 Follow speed. t!-_etighting inspected into 7 Test for spillage hood operation. Turn on any such a summer the thermostat relief opening venting being so appli= after appliances 5 minutes of a match is observed Installation burner or candle. during the venting system outlined above, fireplace previous dampers and any other gas-fired conditions of use. Vent system other appliances system doors, or vent connectors when or connector determined NGPIC. remm vents using vent must be sized COMBUSTION=AIR AND windows, tested exhaust systems appliance VENT fbund combustion-air pool and swimming bleaches, paint, cleaning and other solvents, household inlet as fbr as possible pool pump fi'om house NOTE: All pipe joints must be cemented except attachment of comhustion-air inlet pipe to inlet housing connection, since it may be necessary to remove pipe for servicing. to their Install combustion air inlet pipe as fbllows: 1. Assemble combustion-air For any or vent connectors, to approach table as fans, rnay need to be resizcd. resizing appropriate connected when adhesives, that include fluo= elements are Combustion-air pipe must terminate outside of f:urnace casing with 1 elbow Orient elbow so that opening faces down fbr upflow or downf]ow applications Orient elbow so that it faces sideways (left or right) for horizontal left or horizontal right applications (See Fig 34,) Maintain a 3-in. mininmnt clearance between the opening of' the comhustion-air inlet pipe and any object, any of the above that each appliance properly Locate detergents, which These Furnace combustion°air connection must be attached as shown in Fig 34 Combustion-air intake housing plug may need to be relocated in some applications, Code. 9 After it has been deternrined to air fresheners, by halogens, and iodides See Table 10 fbr required clearances, at the of main air may NOTE: Furnace combustion°air connections are sized fPr 2°in. pipe. The combustion=air pipe will be 2=in. diameter in all installations. tim. tests, the venting system must be con'ected in accordance with the National Fuel Gas (ode, ANSI Z223.1= 2002 NFPA 54-2002 and/or (SA B 149.1, Natural Gas and Propane in aerosols, salts, swimming continuously flora drak hood equipped congt_ustion as exhaust Ptace the appliance Adjust Use the flame 8. If improper fans, to so they are operating Do not operate instructions not connected exhaust exhausts, operation. is operating found products. dryers to contaminated is fi'equently contaminated rides, chlorides, bromides, the appliance(s) and HAZARD exposure result in safety and perfbrmance related problems. Combustion air must not be taken front inside a structme and windows located CORROSION Excessive dampers. 5. Turn on clothes draft or restriction, of the building. 4. (?lose ance Combustion Air Pipe size and horizontal (?ode and these instructions. that there is no blockage corrosion and other unsafe condition. spaces system. for proper in the National Fuel Gas Code, ANSI 54°2002 or the CSA B149.1, Natural Gas and Propane Determine in venting system mininmm in the NFGC inlet pipe. a. Permanently install perforated disk assembly (factorysupplied in loose parts bag) in combustion°air elbow using RTV or by cementing. (See Fig. 35.) size as or NSC= For 120,990 Btuh size unRs only: Separate the 2 halves of perfPrated disk assembly and use only the shouldered disk half, PIPING General b. Determine length of straight portion of combustion°air pipe fi'om table in Fig. 35. FIRE Failure AND EXPLOSION to %llow damage, personal injuw, Solvent cements are sparks, Avoid and open breathing HAZARD this warning could flame. c. (ut field°supplied length. in fire, property Use only Keep away fiom in well°ventilated or allowing contact with d, Permanently attach elbowiperfbrated disk assembly to straight portion of' pipe using RTV or by cementing. (See Fig. 35) heat, areas. skin or 2, Attach con-{bustion-air inlet pipe eyes. ( ombustion°air conform dards 2-in diameter PVC pipe to detem_ined or death combustible. in vapor result inlet and vent pipe, fittings, to American and American National Society printers, Standards for Testing and solvents Institute (ANSI) and Materials a Detem_ine tocation of combustion-air intake pipe connec° tion to combustion-air intake housing as shown in Fig 34 fbr application. must stan= (ASTM) b. Reposition combustion°air intake housing plug fitting in appropriate unused intake housing connection. 28 TaNe 9--Maximum Allowable FURNACE SRZE Exposed Vent Pipe Length {ft) With and Without Temperature Ambient* WINTER DESIGN TEMPERATURE (°F) 20 MAX PBPE DIAMETER (BN.} 1.5 040 100 120 WITHOUT in Winter THICKER INSULATIONt 70 0 1.5 28 70 1.5 16 70 20 2 45 70 0 2 22 70 -20 2 10 58 20 2 65 70 0 2 35 70 -20 2 20 70 20 2 55 55 0 2 48 55 -20 2 30 55 20 2.5 70 70 0 2.5 47 70 -20 2.5 28 70 20 2.5 40 40 0 2.5 40 40 -20 2.5 38 40 20 3 70 70 0 3 50 70 -20 3 28 70 20 3 70 70 0 3 61 70 -20 3 37 70 20 4 70 70 0 4 48 70 -20 4 23 * Pipe length (fi) specified for maximum pipe lengths located Jn unconditioned as specified in Table 9. ? Insulation thickness based on R value of 35 per in. 70 spaces. Pipes located in unconditioned e. Make space cannot exceed total allowable sure elbow is oriented that the minimum 34.) in an acceptable clearance hole in intake =FACTORY INSTALLED LOCATION g. Install h housing a field-supplied Install filler hole inlet pipe using No. 6 or No. 8 sheet metal pipe casing in unused and (See Fig. as a guide into combustion-air parts bag) pipe length direction of 3 in is observed. L Drill a 1/8-in. hole in 2=in. combustion=air FIELD LOCATION Design W_TH 3t8=lN. OR INSULATION 51 -20 060 080 Insulation cap (factow-supplied) combustion-air pipe casing screw in loose hole I NOTE: Do not attach combustion-air combustion-air intake honsing pipe for service of igniter (OMBUSTION=AIR intake pipe permanently since it may be necessaw or flame sensor. INTAKE HOUSING to to remove PLUG FITTING The combustion-air unused attached fitting, by using using field-supplied Fig. 31--Relocating c Install pipe into selected support d. Insert support should assembled &Box (_ilctow-supplied fimaace casing be positioned in loose combustion-air at bottom combustion-air A00212 inlet parts bag) pipe hole. Pipe of casing pipe into hole. intake housing. 29 intake combustion-air NOTE: DO NOT housing or fitting hole plug intake RTV sealant, in intake fitting housing must be installed in This fitting be or by &illing housing a 1i%im hole in as a guide. No. 6 or No. 8 sheet metal screw. OVERTIGHT]EN Breakage SCREW. may cause air leakage to occur. must Install of intake a 25-24-65-2 E_ (_AIR VENT TERMINAL SUPPLY INLET Item Clearance Descriptions A Clearance above grade, veranda, porch, deck, bafaony, or anticipated snow level 12 (3Ocm) # E Clearancetoawindowordoorthatmaybeopened 6" (15cm)forapplia_ices E_ AREAWHERE TERMINAL Canadian fastaHaflon (1) C Clearance to a permanently dosed window D Vertical clearance to a ventilated soffit located above the IS NOT PERMITED U.S fastallation (2) 12" (36 cm) 10,OOOBTUH(3kW),12 (30 4"(12m)belowortothesideoftheopenfag'l(3Ocm) cm) for appliances > 10,OOOStut'd3 kW) and 100,OOO Btuh (36 kW)j'36 (91 cm)for appliances > 100.000 Btuh (30 kW) above the opening termina_ within a horizontal distance of 2'(61 cm) from the centedine of the terminal E Clearance to an unventilated soffit F Clearance to an outside cornet G Clearance to an inside corner H Clearance to each side of the centedine extended above _ (91 cm) within 15"(4.5 m) above the meter/regulator 3" (91 cm) withih 15 (45 m) above the meter/regulator electrical meter or gas service regulator assembly assembly assembly Clearance to service regulator vent outlet _ (91 cm) Clearancetonon-mechanicalairsupplyin_ettobuildfagor 6" (15cm)forapplia_ces the combustion air inlet to any other appliance cm) for appliances > 1O,OOOBtuh_3 kW) and 1OO,6OOEtuh (36 kW)j'36 (91 cm) for appliances > 100,660 Etuh (30 kW) opening K Clearance to a mechanical air supply inlet 6 3 (91 cm) above if withfa 10'(3m horizontally) L Clearance under a verand& porch, deck, or balcony 12" (30 cm) + M Clearance to each side of the centedine extended above or J 10,OOOBTUH(3kW),12 (30 (1 83 m) 4" (12m)belowortothesideofdpening:1 (3Ocm)above below vent terminal of the furnace to a dryer or water heater vent, or other appliance's direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent, water heater vent, or other appliances direct vent intake or exhaust O Clearance from a plumbing vent stack p Clearance above paved sidewalk or paved driveway located on public property 7' (2 13m)** (1) In accordance with the current CSA B149.1, Natural Gas and Propane fastallaflon (2) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code 7' (2.13m) Code # 18" (46 cm) above roof surface + Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor * For clearances not specified in ANSI Z223 t/NFPA 54 or CSA E149.1, clearances shall be in accordance with Iocat installation codes and the requirements of the gas supplier and the Manufacturer's installation instructions ** A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings Notes: 1 The vent for this appliance shall not terminate a Over public walkways: or b c 2 Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard or property damage; or Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment. When locating vent terminations, Recircuiation 3 consideration can cause poor combustion, must be given to prevailing winds, location, and other conditions which may cause recirculafion inlet condensate problems, Avoid venting under a deck or large overhang Recirculafion and accelerated could occur and cause performance -_ Table 10--Other of the combus6ob products of adjacent vents corrosion of the heat exchangers or system problems than Direct Vent Termination Clearance 30 A05013 TO 115VAC FIELD DISCONNECT SCHEMATIC DIAGRAM PCB NOTE #2 IL 2 GNDi_ SPARE-2 -" L1D@R_ H}ILO (NATURALGAS & PROPANE) 7 EQUI[t%IBXq GROUND M[DLO CAP-1 SPAREq L2 I HEAT COOL ..NOTE #10 PL4 V_ff BRN EAC_ BRN PL1 _HT CRN/YEI,, CAP ]DM BLK SPARE 2 R® / w®/t/ EAC-1 ¢THT (OOM) _SCONNECT S/._ITCH (lAdEN ___NOTE_#2 I NOTE #10 BLK RED (LO) ILK-- BLU (MED LOJ I ILK ---........ PU2 BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR RELAY, SPST-(N O) BLOWER MOTOR¸ PERMANENTSPUTCAPACITOR CAPACITOR MICROPROCESSOR AND CIRCUITRy ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1 0 AMP MAX¸) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SW -MANUAL RESET SPST-(N C ) FLAME-PROVING ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FU 2 GND FUSE OR CIRCUIT BREAKER CURRENT (FIELD INSTALLED & SUPPUED) EOUIPMENT GROUND GV GAS MALVE_REDUN DANT GMR 1 2 HSI HSIR HUM IDM IDR ILK J1 J2 JB LED GAS VALVE RELAY, DPS_-(N O ) HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY SPS_, (N O) 24VAC HUMIDIFIER CONNECTION (0 5 AMP MAX¸) INDUCED DRAFT MOTOR¸ PSC INDUCED DRAFT MOTOR RELAY, SPST (NO) BLOVlJER ACCESS PANEL IN]ERLOCK SWITCH, SPST (N O) BLOWER - OFF DELAY JUMPER SELECTOR COOLING - OFF DELAY JUMPER JUNCTION BOX LIGH*PEMITTING DIODE FOR STATUS CODES - RED LGPS LS LOWGAS PRESSURE SM/ITCH, SPS]:(N O) LIMIT SWITCH, AUTO-RESET SPST (NC) INTERRUPT PCB PL1 PL2 PL3 PL4 PRS TE SPPRA/IN TRAM DEVICE G_D I -I 1 I REQ'D} L1 PRESSURE SWITCH, SPST-(N O ) COMPONENT TEST & _RMN TERMIRAL TRANSFORMER-115VAC!24_,AC m PCB CONTROL TERMINAL TERMINAL NOTES: 1 2 3 If ar_y of the onginal eq_ #_leqt '_'_re is iet:Jaced use '_re lated for 105 C Use only copper '_re bet_,een the disconr_ct s,_tde and the fun'ace jul_ction box (JB) This _._.4remust de cor_ected to furnace sheet met_ for control to prove flame Syrdeols elec_]cal repiesenta_on Solid linesare ir_ide PCB are printed circ_tonl _oard conductors FACTORY tMRING (115VAC) 6 7 8 9 FIELD WIRING (115VAC) FIELD WIRING (24MAC) apd are not ir_,luded in legend Replace ctly with a 3 amp f_se Inducer (IDM) a_d blower (BL_M) motc_s centaln intem_ ad_o-reset therm_ overlead Neutral connections _ e interchangeaNe _thin the NEUTRAL conr_cto_ block BloweI" moto_ speed selec_or_ ale for avetage condtions see ii_st_lation instrucqons optimum speed selection YELLOWlead i'_€ on all r_'oto_ s PCB 10 FIELD WIRING SCREW TERMINAL 11 12 Fantol 3, connected whel LGPS is not used lgnitiol_-Iockout w_ll OCCUr after four consecutive auto4-eset alter _ree houis 13 14 Blower-ct_ delay: gas dealsng 60 seconds, cooling c{ hea_ pt,rnp 2 seconds Blower-off delay: gas dealing selections are 90 120,150 or 180 seconds, coding 90 see_nds Or 5 seconds when J2 is cut CONDUCTOR ON CONTROL FIELD EARTH GROUND EQUIPMENT GROUND FIELD SPLICE )_ I 2_CIRCUIT CONNECTOR 2_IRCUIT HSI, CONNECTOR 3dSIRCUIT IDM EXTENSION CONNECTOR FACTORY WIRING (24VAC) _ PRS 1 [EMPERATURE SWITCH (NC) PRINTED CIRCUIT BOARD CONTROL 11 _31RCUIT PCB CONNECTOR UNMARKED Q L i,_{_#11_ I JUNCTION -- -- -.... i MOTOR OVERLOAD Q m I M1 .E.osJ I BLK---_OI" AUTO RESET INTERNAL BHT/CLR BLWR BLWM CAP 1,2 CPU EAC-1 EAC_ FRS FSE FU 1 I _JM BLK JB : unsuccessful trials-for4gn_tion PLUG RECEPTACLE Control S',Mtches (OL) for details on w_ll or heat p_rrlp 328150-101 RE1L A ./ A02271 Fig. 32--Wiring Diagram BLOWER TWINNING AND/OR COMPONENT TEST TERMINAL OFF-DELAY J2 JUMPER HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) 24-V THERMOSTAT TERMINALS TRANSFORMER 24-VAC CONNECTIONS 3-AMP FUSE ob LED OPERATION & DIAGNOSTIC LIGHT PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR 115-VAC(L2) CONNECTIONS A02100 A plugged drain connection fbr use when moisture and combustion box &ill out fitting's field-supplied condensate tIapped. Vent intake tap plug with a 3/16-in. &ill and connect robe. This tube should for furnace pipe be routed and AiC (if used), UNIT is desired, When and should be in vertical pipe. condensate. Detem_ine Table 8 Furnace should are sized be made outside furnace &ainage is used described in Table casing An abandoned of vent properly diameter and maximm_a housing alternate must be attached pipe lengths using ft upward as shown in Fig. vent cap may need to be relocated slope vent pipe a minimum to termination(s) with unit to temperatures through below an unheated as a raceway, pipe must 9 with Am_aflex-type fi'eezing, space or when be insulated a as insulation masonry insulated and chimney supported may be used vent no sags pipe as a raceway Each individually, furnace %r must as shown in gas appliances wit}* their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the curt'out edition of d_e National Fuel Gas (7ode and the vent or liner manufi_cmrer's installation instl-uctions. Care must in be taken at furnace, in intem_ittent Fig. 41. applications. linear chimney Other Starting it passes have its own vent pipe and be terminated vent pipe connection NOTE: may result for 2-in. pipe. (See Fig. 37.) This allows proper vent pipe 34. Inducer some connections OPERATE this caution vent pipe is exposed such as when vent pipe Any vent pipe size change NOT to %ltow operation. to open (See Fig. 36.) Furnace MAY Failure a Pipe NOTE: per on this fitting If use of this drain connection 3/8-in. &ain has been provided is fbund in combustion-air of 1/4 in to prevent contaminating between hangers. 32 the exhaust the combustion gases fi'om one appliance air of other gas appliances. from NOTE: Select 1 vent pipe connection and I combustion-air pipe connection. FIELD-SUPPLIED 2-IN. DIAMETER ,,--- F ELD-SUPPL ED PVC 90" ELBOW/ 2-IN. DIAMETER /_" PVC PIPE NOTE: Select 1 vent pipe connection and 1 combustion-air pipe connection. AIR AIRCOMBUSTION- _ COMBUSTION-AIR V_NT VENT _ j_[ VENT _ _]_ _2 72227 t AIR UPFLOW AIR FLOW II _1 A I, AIR _LCOMBUSTION-AIR DOWNFLOW DISC (FACTORY-SUPPLIED IN LOOSE PARTS BAG) COMBUSTIONAIR COMBUSTIONAiR A96211 VENT Length VENT of Straight Combustion-Air HORIZONTAL-RIGHT HOUSING PLUG DISCHARGE (In.) A 8-112+ 112 10-1/2 + 1/2 12 + 1/2 Fig. 38--Combustion-Air DISCHARGE of 1Net Pipe Assembly CASBNGWIDTH 17-112 21 24-112 "t HORIZONTAl-LEFT Pipe Portion Inlet Pipe AssemNy INTAKE HOUSING BURNER BOX A96188 [NIT MAY NOT OPERATE Failu*e to follow this caution may result m intemlittent unit operation. Make sure there is adequate clearance (3°in. minhmma) to any fixed or toose objects in orde* to ensure an adequate combustion-air supply E_COMBUSTIONAIR PIPE Fig. 34_Combustion-Air and Vent Pipe Connections A96190 HHHH,_, CARBON MONOXIDE DAMAGE HAZARD t: POISONING Fig. 36--Air IIII Intake Housing Plug Fitting Drain AND PROPERTY Failure to fbltow this warning could result damage, personal ir_juW, or death. Vent pipes must be airtight and watertight in property • FURNACE NOTE: The mh_imum vent pipe length for these fm'naces is 5 f_ Short pipe lengths (5=8 ft) may discharge water droplets These droplets may be undesirable, and a 12=in mininmn_ of_get pipe section is recommended to reduce excessive droplets flora exiting vent pipe outtet. (See Fig 3g.) • £j_ NOT IN HORIZONTAL SECTION NOTE: Do not count elbows or pipe sections in tem_inations or within t:umace. See shaded areas in Fig. 40, TRANSITION iN VERTICAL SECTION A93034 Fig. 33 37--Vent Pipe Diameter Transition and Elbow Configuration Location VENT PIPE VENT PIPE i.,,,,_t_ HORIZONTAL 12" MIN HORIZONTAL TO ROOF F TO SIDEWALL VENT PIPE 12" MIN VENT PIPE VERTICALTO ROOF VERTICAL TO SIDEWALL NOTE: A 12-1n. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. A96189 Fig. 38--Short Vent (8 to 8 Ft) System 1 EXAMPLE: An 080-12 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed in an application requiring 3 elbows and 32 ft of vent pipe Table 8 indicates this application would allow a 2-in. diameter vent pipe. At 0°2000 k elevation, 2-in. pipe is good fbr up to 35 ft with 3 elbows. If same installation were in Albuquerque, elevation 5250 ft above sea level installation would require 2° 1/2 in. vent pipe. At 500I- to 6000-_ elevation, 2-in. pipe is allowed for up to 23 f_ with 3 elbows, but 2-!/2 in. pipe can be used for up to 70 ft with 3 elbows --€ UNIT DAMAGE Failure HAZARD to follow this caution may result in unit component damage. Inducer housing outlet cap must against inducer housing. Clamp any condensate leakage. 3, Install pipe support selected furnace positioned ___> Install vent pipe as _bllows: l. Determine location of vent pipe connection to inducer housing as shown in Fig 34 fbr application at bottom MONOXIDE DAMAGE HAZARD Failure (factowosupplied casing (ARBON to fPllow be installed and thlly seated must be tightened to prevent in loose parts vent pipe hole, Pipe support of casing be hole POISONING this warning bag) into shoutd could AND [NIT result in personal injury or death and unit damage 2. Reposition elastomeric (rubber) inducer housing oudet cap and clamp to appropriate unused inducer housing connection Tighten clamp. Vent pipe must be installed and fully seated housing must be tightened internal condensate NOTE: casing elastomeric against inducer to prevent any leakage. A 2=in. diameter Make 4. Be certain 34 stop. Clamp pipe must all pipe diameter that mating coupling, be used transitions surfaces and 2-in within outside of inducer diameter the furnace [:urnace casing. housing connection vent pipe are clean and&y. Assemble theelastomeric (rllbber) ventcoupling (with2loose clamps) ontoinducer housing connection. Insert the2-in.diameter ventpipethrough theelastomeric (rllbber) coupling and_hllyintoinducer housing connection untilit bottoms ontheinternal stop. Tighten both clamps to secure the pipe to inducer housing. Tighten the clamp screws to 15 inMb. casing hole bag) in unused VENT Some filrnaces (2-in. diameter vent NOTE: are supplied by vent a PVC vent extension tong). This condensate pipe disposal. a built-in When this vent inducer housing on ALL pipe for proper if an elbow robe to field-installed is used installation to connect When vent vent pipe. fi/rnace to and outside 8. Chamfer outside and cement. 9. Clean and d_ 10. Check NOTE: outside, cut pipe to all surfitces It is recommended 11. After pipes that have been to insertion of primer insertion all pipes depth Apply be cut, prepared, cementing to pipe fitting Quickly second cement apply and any joint. pipe joints 15. Support vent piping or -26 PVC) fiom joint. apply socket approved generous 17. Use carefidly cement passes a minimum Extended Exposed Sidewall vent length to end of in a light, of excess metal to seal trap is shipped located length Pipe may ambient trap is not required hanging Nrnace of 1/4 spaces or in the blower shelf and [itctory be used for all applications. when connecting the field drain to 1i2=im (condensate to ASTM D2564 In Canada, pipe, CPV(, flap or drain robe coupling) and must 1/2-in. fittings, or 5/8=in. must conform listed schedule to ASTM 40 CPV( or and cement. pump tbr condensing select PVC, or F493. Primer use CSA or ULC a condensate UNIT hangers. openings MAY Failure where be extended vent pipe is required, furnace a pump select a pump applications. which To avoid with an overflow is conden- switch. NOT OPERATE to _bllow this caution beyond temperature temperature area &ain fbr cannot l\)r maximum exceed pipe pipe &ops operated, structure and then mined doting to 32°F and below line have adequate Instructions [i'eeze off and cold weather unless protection. drain when trap See Service _Br winterizing procedures. and and (See condensate pH neutralizing authorities to determine filter may be desired. if a pH neutralizer Check of a with local is required APPLICATION lengths total allowable unit Furnace condensate is mildly acidic, typically in the pH range 32 to 4.5 Due to cotl'osive nature of unneutralized condensate, and furnace exposed in intem_ittent Fig. 15.) (used in load calcula= thickness may result operation. pipe as indicated fPr your application specified in Table vent shap. a minimum as stated above, using total pipe insulation (ft) common Drain pipe and fitdngs must conform to ANSI standards ASTM D1785, D2466 or D2846. CPVC or PV( cement sate spillage, of elbows. design near each other, each NEVER trap. Maintenance temperature in unconditioned are not robe The as specified vent vapors where ID approved sets. by insulating vent pipe diameter, length balls, are vented installed An external When made joint. lengths. NOTE: it will not be dan> such as stones, applications. Condensate trap must be in DOVv_TLOW and HORIZONTAL trap MUST F656. Pipes tem?ination required will not Drain left in an unconditioned winter where vented (ondensate conform tions). 3. Detem_ine Furnaces Unit must not be installed, and number vent vapors 10. equipment. objects be positioned Sidewall pipe using should roof or sidewall. 2. Find appropriate model to foreign in Table of every 5 ft (3 ft for SDR=2! toward methods shown in Fig. 40 in outside in Table 9. 1. Detemline cement ft with no sags between through where be positioned lO--Condensate is sized fPr connection. bead of cement of a properly until using perforated appropriate stated or air conditioning The field drain connection and end of pipe A continuous perimeter 16. Slope vent pipe downward in. per linear requirements be positioned should this condensate coat. around 14. Handle should plants/shrubs 2 or more 58MSA PVC drain will be visible be made when determining applications. 12. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is [:ully inserted into fitting socket. 13. Wipe excess should with all clearance Condensate on pipe. pipe and fitdng socket Cover primer). Apply cement uni[bm_ coat on inside of socket to prevent buildup cement. See 41 _br for tem_ination: connected _br UPFLOW RELOCATED _br use cut and preassembled, primer mark. distribution to be joined. pem?anently layer of cement 40, and GENERAL edge of pipe for better before or sidewall. 39, required of pipe. &y fit of pipe and mark preassembled location fitmace must be individually breach vent 58MSA fiu_aces Step inside roof See Fig objectionable. length(s). 7. Deburr through MULTIVENTING This pipe may be shortened fiom of the _Pllowing 4. Termination and applications. 5. Working Consideration aged by or subjected etc. the field upflow either clearances. an'angements 3. Tem_ination pipe has it must be used to connect See label on vent extension extension piping 2. Termination hole. with 12=in. to filrnace downflow exterior 1. (omply parts terminate 10 _br required damage pipe is supplied, pipe in loose pipe must Table PIPE to assist extension cap (fhctolT-supplied vent pipe casing EXTENSION channel filler Vent TERMINATION an appropriate of torque. 5. Install VENT f_lrnace, drained pipe A/C, together. and humidifier The Ai( drain drains may be combined retest have an external, and field- supplied trap prior to the fi/rnace drain connection. Al! drain connections (furnace, A/C, or humidifier) must be tem_inated into 8. 35 ROOF OPEN STAND --7 PiPE FOR / A/COR/ HUMIDIFIER _[ DRAIN A94054 Fig. 42--Example of Field Drain Attachment an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment's drain, See Fig 42 for example of possible field drain attachment using li2-in (PVC or PV( tee for vent and AiC or humidifie* &ain connection, Outdoor draining codes. Caution of the ihmace should pipe and prohibit J 12-1N. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER. PERSONAL Caunon be taken to prevent could cause personal Excessive condensate draining conditions which result Freezing cause protection is required, shielded, draining may where cause in damage left in condensate water trap damage use condensate slippew saturated soil to plants. and drain may occur. freeze protection 3 to 6 watt per ft at 120v and 40°F and waterproof with accessory 2. Locate drain injuries heat tape. heat tape between line may If fieeze accessow sel[:regutating, See Installation or heat tape manufhcmrer's 1. Fold heat tape in half and wrap PIPE LENGTH by local may fieeze DRAIN PROTECTION and possible or equivalent supplied tions could condensate cracks, if allowed ambient IN J[ RY HAZARD CONDENSATE PIPE. 10-1N.MAXIMUM Freezing draining should conditions is permissible be taken Instructions recommenda- on itself 3 times. sides of condensate trap back. (See Fig. 43) 12-IN. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER. 3. Use wire Termination with Straight in notches heat tape of condensate 4. Wrap field drain pipe with remaining 1 wrap A96210 Fig. 41--Sidewall ties to secure positioned 5. When Pipe trap Wire sides. ties can be (See Fig. 43j heat tape, approximately per ft. using _Scturer's 36 in place. field=supplied instractions heat rope, fbllow for all other installation heat rope manu= guidelines. CONDENSATE WIRE TIE (3 WRAPS HEAT MINIMUM) Fig. 43--Condensate START-UP, Step l--General 1. Furnace A93036 Trap Heat Tape ADJUSTMENTS AND SAFETY CHECK ......7 mast have a 115-v power and grounded. Proper polarity supply properly connected must be maintained A99118 fbr con'ect Fig. 44_[nducer operation. NOTE: Proper polarity must be maintained polarity is incorrect, ft/rnace rapidly and furnace will not operate. control 2. Them_ostat wire connections must be made at 24-v terminal 3. Natural gas service we), but must pressure fault indicator wiring. Housing Drain Tube Cap If light will flash at terminals R, W, G, and Y block on thmace control center. must not exceed 0.5 psig (14oin. be no tess than 0.16 psig (4.5-in. 4. Blower access panel must electrical circuit to furnace. FIRE for l15-v be in place wc). to complete l15-v HAZARD Failure to follow this caution may result in intermittent unit operation. These thrnaces are equipped with a manual reset limit switch in burner box. This switch will open and shut offpower control vah'e if an overheat condition (flame rollout) in burner enclosure. ply or improper jumper Befbre operating 2--Prime UNIT Failure inadequate condition combustion-air and reset switch sup° DO NOT this switch for continuity. Step Correct venting to gas occurs MAY f_/mace, check flame If necessa_, Condensate NOT to follow rollout press button Trap manual reset switch to reset switch with Water OPERATE this caution may result in intermittent unit operation. Condensate occur trap must be PRIMED The condensate ONLY be primed of condensate or proper draining trap has 2 internal by pouring charnbers water into the inducer A99119 may not which can Fig. 45--FHffng drain side 3 trap. Insert 4. Pour field-supplied 1 quart 1, Remove upper inducer housing drain connection cap (See Fig. 44) through 2, (onnect field-supplied 1i2oin ID robe to upper inducer housing &ain connection, 5. Remove inducer into open field funnel drain connection 37 Condensate fhnnel of water housing, Trap into tube into funnel/robe. overfill Water condensate should tIap, run and flow drain. (See Fig. 45.) and robe fiom cap and clamp. inducer housing and replace Step 3--Purge Gas Lines proved within two seconds, the control CPU will close the gas valve GV, and the control CPU will repeat the ignition sequence fbr up to three more Trials-For-Ignition befbre FIRE AND EXPLOSION Failure to %llow personal injury, Never for purge gas going HAZARD this warning could result in a fire, explosion, a gas line into a combustion with an open chamber. flame. Use available soap solution made specifically leaks to check all connections. Never after power test Step done, purge for leaks. 4--Sequence lines after all connections of to the furnace, If flame is proved fhmace control have been Failure to %llow blower and water Furnace control control will [sing must through diagram be grounded out. for proper Control is grounded in Fig. 32, fbllow the diffkrent modes or through If a power control seconds will interalpfion start after power gas heating. 90-second The a 90-second is restored, red period, occurs LED of the wiring light will flash ON period two is still calling for 12 during the the LED will be ON continuous, as are detected. flul_ace will respond blower-only Afier code the 90-second to the thermostat period, motor (PU, transl\_rmer TRAN, BLWM, hot-surface igniter motor IDM, HSI, and gas valve 30 fbr thermostat thermostat wall circuit. The fl/mace pressure switch motor IDM. a. Inducer contacts blower up to speed, 24 vac power the HUM prepurge the pressure is supplied terminal and Warm-Up- Hot-Surfi_ce period close the inducer switch contacts the control a 15-second begins Igniter warm-up HSI is energized fbr to energize When the gas valve The gas valve GV pemaits the igniter gas flow to the burners by the Hot Surfhce Igniter HSL Five seconds the GVR closes, flame period a 2-second will remain energized the 2-second flame until proving begins. d-_e flame period flame-proving CPU begins When sensor the burner electrode it after the blower-ON hold the gas valve delay period GV open. is proved the fl/mace If the burner flame with as HEAT at the flmction is not 38 allowing will operate the blower motor circuit operating requires blower seconds), and fhmace heat the at the end of speed speed running after fbr cooling", speed speed. BLWM befbre J2 can be can the R-to-G will stop during (7 CPU will continue at (OOL to 5 seconds. as the the selected is completed. "calls on COOL is energized then restarts at HEAT at HEAT delay period the continuous-blower BLWM seconds), control themlostat, EAC-! ignition BLWM Jumper the cooling is energized the blower delay period thermostat the seconds), (65 the furnace will continue to (17 by Terminal BLWM to heat up more quickly, When contlol speed) motor exchangers 90 seconds speed fbr on delay the on the COOL J2 to reduce operate blower-ON motor are blower is closed will wam_-up speed. and continues speed. is energized and the t\trnace operating circuit % call for heat(' satisfied, or stop, Cut jumper BLWM igniter BLWM begins. flame FSE, on COOL EAC-1 Mode R-to-G motor offtdelay d. Flame-Proving- The R-to-Y and Y circuits (See Fig. 33.) During When The HSI is sensed circuits. BLWM terminal will continue blower-OFF opens. where flu'hate blower-OFF and the R-to-G unit will Blower the blower GVR GV, the gas valve The wilt connections) motor to 5 seconds. In heating, warm-up is ignited igniter the a 17-second the main gas valve relay contacts the will (depend- The for a 120-second unit, blower the blower-ON Sequence- the period. EAC-I selection). closes the R-to-G-and-Y long as ff*e blower period. is completed, is fitctory-set 90 seconds. speed (same at period, delay air cleaner BLWM blower PRS close, humidifier is satisfied, the gas valve GV, fbr 90, 120, 150, or 180 seconds the outdoor Continuous IDM fbr a field installed the thermostat de-energizing to the burclers, and de-energizing HLM. The inducer motor IDM The outdoor off'delay the motor At tl-_eend of the prepurge c. Trial-Nr-Ignition until starts an additional period. b. Igniter igniter As When blower-OFF CPU EAC-! Mode When Period- terminal as tong as the blower 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y circuits the R to W verifies the The electronic GV. a self-check, air cleaner energized is opened, start the t\lrnace PRS are open, and starts the inducer Prepurge comes perfbm_s closing the after is energized. Delay- The thermostat motor for heat", contlol the electronic (See Fig. 30 fbr them_ostat the connections.) "calls is proven, 66 seconds energized on opened. The flame speed remain Cooliug 1. Heating (See Fig on HEAT delay. for power to be condtlcted switch ILK to the furnace inducer the mode IDM until flame is no longer energized for a 15-second post=purge motor BLWM and air cleaner terminal circuit control not be present, of Gas-Heating the burner and remains circuit control normally The blower door must be installed through the blower door interlock should remain blower ing a call for heat (W), if the thermostat after which as no faults during motor If stopping gas flow humidifier terminal box screw Read and fbltow 24 vac CPU (not at GV is energized. BLWM R-to-W the sequence flame is energized f_ Blower-Off operation, to gas valve and burner diagram motor cold weather. very- carefully. NOTE: long during auto- or by interrupting will lock out Delay- motor is energized may result in t:urnace operation freezing wire routed the schematic operation the pipes lock green/yellow OPERATE this caution stopping when CPU Simultaneously, NOT reset interrupting to the [:urnace control the inducer e. Blower-On of Operation MAY be proved. the gas valve FURNA(E will by momentarily W, G, R, etc.) a commercially for the detection Lockout hours, at SEC1 or SE(2 and operate [f not previously made and check three 115 vac power or death leaks to Ignition-Lockout. matically the blower When will operate reverting motor the d_em_ostat is an additional back to HEAT be cut to reduce the cooling (See Fig. 33.) is opened, the blower for an additional motor BLWM motor BLWM 5 seconds, operation. if no other 4. HeatPumpMode Wheninstalled witha heatpump, thefl/mace control automatically changes thetimingsequence toavoidlongblower offtimesduring demand defrost cycles. When theR-to-Wand-Yor R-to=W-and-Y-and-G circuitsareenergized the Nmace control CPU willcontinue toturnontheblower motor BLWMat HEATspeed, andbegina heating cycle.The blower motor prepurge BLWM period, on at HEAT Nrnace speed. control the blower will remain on until the end then shut off %r 24 seconds When begins switches the W input a normal to (OOL 8 post-purge Step pear, delay period. leaving continue If the R=to-W-and=Y the G signal, running the the blower after the selected blower motor blower-OFF signals motor BLWM delay period BLWM NOTE: The control terminal HUM terminal is energized helps diagnose The component signal component time; except rating is completed. are not energized when a system test is present test allows for safety problem all compo= reasons. The is energized. at the control a not operate all time thermostat setting above input rate must plate adjusted be within 2 percent of input on furnace fbr altitode. natural gas orifice size and manifold pressure fbr input Obtain average gas heat value (at installed altitude) from EAC-1 b f_ilure. delays Obtain average gas specific c Verif) furnace model. 58MSA furnaces if any thermostat and not until by raising local gas supplier This feature in case of a component fcatu, e will that flmaace restarts Determine the gas valve and humidifier the blower setting temperature. correct furnace thermostat 5--Adjustments Furnace TEST nents to run for a short lowering will speed 1 ( OMPONENT by In Canada, the input ratings must be de*ated by 5 percent fbr ahimdes of" 2000 ft to 4500 ft above sea level, disap- at HEAT down In the [,SA, the input ratings fbr ahitudes above 2000 ft must be reduced by 2 pc*cent %* each 1000 ft above sea tevel, If the R=to-W-and-Y-and=G signals disappear at the same time, the blower motor BLWM will remain on for d-_e selected blower-OFF shut temperature Furnace gas input rate on rating plate is %r installations at ahimdes up to 2000 It, and delay. flmaace SET GAS INPUT RATE the period after a 3 second Verify room of the disappears, Verify below room then come back signal inducer speed 7 are Table gravity flora local gas supplier. 11 can only be used fbr model d Find installation ahimde in Table 11 completed. To Begin Component NOTE: For Canadian altitudes of 2001 to 4500 It, use USA, altitudes of" 2001 to 3000 ft in Table 11, Self=Test: e ELECTRICAL SHOCK Failure d_is warning to %ltow personal injury, or death. Blower access panel control center HAZARD could result door switch No component must be taken when opens operation manually in electrical closing l15=v can occur. this switch £ Follow shocL power Find closest Table 11 heat intersection settings to natural gas heat value value and specific to find for proper orifice size and specific gravity and lines gravity on to point of mani%ld pressure operation Caution for service purposes. 1. Remove blower 2. Disconnect access the fl-_ermostat R lead from furnace 3. Manually close blower 4. For approximately on control terminals. longer door control. switch. 2 sec, short 0umper) to the TEST/TWIN hal on control NOTE: door. _SEAL the COM-24V terminal 3/16=inch quick-connect until the LED goes out. Remover termi= jumper REGULATOR /_ADJUSTMENT from (See Fig. 33.) If TEST/TWIN SCREW and than 2 sec, LED will (o_,>24v terminals flash rapidly are jumpered and ignore component REGULATOR test request Component REGULATOR CAP (PROPANE test sequence a. LED will b. Inducer display motor component c. After NATURAL is as fbllows: previous starts status code 4 dines. and continues to run until ADJUSTMENT INLET PRESSURE the hot surfSce igniter is energized - SILVER TAP for 15 sec_ then off'. d. Blower motor operates on HEAT speed for 10 sec. e. Blower motor operates on (OOL speed for 10 sec. £ Inducer motor stops. 5. iReconnect R lead to furnace contiot, remove door switch, and re=install blower door. 6. Operate thmace per instruction 6 TURNS 10 TURNS) GAS PRESSURE REGULATOR Step g of test sequence 7 seconds SPRING - WHITE, tape from blower A03142 Fig. 4g--Redundant on outer door. 39 Automatic Gas VNve Table11--Mode{g8MSA (Tabulated ALTITUDE RANGE (FT) OF NATURAL GAS 0.82 0.64 0.55 (BTUICU FT) Manifotd Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 85O 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 875 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 9OO 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7 925 44 3.5 44 3.7 44 3.8 43 3.4 43 3.5 95O 44 3.4 44 3.5 44 3.6 44 3.7 44 3.8 975 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6 1000 45 3.7 45 3.8 44 3.2 44 3.4 44 3.5 1025 45 3.5 45 3.5 45 3.7 44 3.2 44 3.3 1050 45 3.3 45 3.4 45 3.5 45 3.7 45 3.8 O% 1075 45 3.2 45 3.3 45 3.4 45 3.5 45 3.5 derate 1t00 47 3.6 47 3.7 45 3.2 45 3.4 45 3.5 to SPECIFIC GRAVITY OF NATURAL GAS AVG GAS HEAT VALUE AT ALTITUDE (BTUICU FT) Orifice No. Manifotd Pressure Orifice No. Manifold Pressure Orifice No. Manifotd Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 0.58 0.50 0.52 0.64 0.55 U.S.A. 775 43 3.8 42 3.2 42 3.3 42 3.4 42 3.5 Altitudes 8O0 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3 200i to 825 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8 3000 850 44 3.6 44 3.7 44 3.8 43 3.5 43 3.6 or Canada 875 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4 90O 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6 Altitudes 925 45 3.7 45 3.8 44 3.2 44 3.3 44 3.4 2001 to 950 45 3.5 45 3.5 45 3.7 48 3.8 44 3.3 4500 975 45 3.3 45 3.4 45 3.5 45 3.5 45 3.8 5% 1000 45 3.1 45 3.2 45 3.4 45 3.5 45 3.5 derate 1025 45 3.0 45 3.t 45 3.2 45 3.3 45 3.4 SPECIFIC GRAVITY OF NATURAL GAS AVG GAS HEAT VALUE AT ALTITUDE (BTUICU FT) Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 750 43 3.7 43 3.8 42 3.3 42 3.4 42 3.5 775 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 80O 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7 825 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5 85O 44 3.3 44 3.4 44 3.5 44 3.7 44 3.8 875 45 3.8 44 3.2 44 3.3 44 3.5 44 3.6 9OO 45 3.5 45 3.7 45 3.8 44 3.3 44 3.4 925 45 3.4 45 3.5 45 3.5 45 3.7 44 3.2 950 45 3.2 45 3.3 45 3.4 45 3.5 45 3.7 7% 975 45 3.0 45 3.2 45 3.3 45 3.4 45 3.5 derate iO00 45 2.9 45 3.0 45 3.t 45 3.2 45 3.3 ALTITUDE RANGE (FT) 300i C o < 0.50 Orifice No. ALTITUDE RANGE (FT) 7 SPECIFIC GRAVITY 0.58 Manifotd Pressure 20OO o AVG GAS NEAT VALUE AT ALTITUDE Orifice No. o 7 Orifice Size and Manifold Pressure for Correct input Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)* to 4000 0.58 0.50 0.52 _Odfice numbers 45 are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges. 4O 0.64 0.55 Table 11--Model 58MSA Orifice Size and Manifold Pressure for Correct Input Continued (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Levem)* ALTITUDE RANGE (FT) SPECIFIC GRAVITY 0.58 0.80 OF NATURAL GAS 0.82 8.84 8.85 (BTUiCU FT) Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifotd Pressure Orifice No. Manifotd Pressure Orifice No. Manifold Pressure 725 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 750 43 3.4 43 3.5 43 3.7 43 3.8 42 3.2 775 44 3.7 44 3.8 43 3.4 43 3.5 43 3.7 800 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4 825 44 3.2 44 3.4 44 3.5 44 3.6 44 3.7 850 45 3.7 48 3.8 44 3.3 44 3.4 44 3.5 875 45 3.5 48 3.8 48 3.7 44 3.2 44 3.3 5000 900 45 3.3 45 3.4 48 3.5 48 3.8 45 3.8 9% 925 45 3.1 48 3.2 48 3.3 45 3.4 45 3.8 derate 950 45 3.0 45 3.t 48 3.2 45 3.3 45 3.4 4001 O <." AVG GAS HEAT VALUE AT ALTITUDE to ALTBTUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE SPECIFIC GRAVITY 0.58 0.80 OF NATURAL GAS 0.82 8.84 8.88 (BTUiCU FT) Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifotd Pressure Orifice No. Manifotd Pressure 700 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4 725 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 750 44 3.6 44 3.7 43 3.4 43 3.5 43 3.6 775 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4 800 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6 O 825 45 3.8 48 3.7 44 3.2 44 3.3 44 3.4 _ to 850 48 3.4 48 3.8 48 3.8 48 3.8 44 3.2 875 48 3.2 48 3.3 48 3.4 48 3.8 45 3.7 D 6000 900 48 3.0 48 3.1 48 3.3 48 3.4 45 3.8 925 48 2.9 48 3.8 48 3.1 48 3.2 45 3.3 950 48 2.7 48 2.8 45 2.9 48 3.0 45 3.t 975 48 2.8 45 2.7 45 2.8 45 2.9 45 2.9 iO00 48 2.5 48 2.8 45 2.8 48 2.7 45 2.8 500t 11% derate OF NATURAL GAS AVG GAS HEAT VALUE AT ALTITUDE (BTUICU FT) Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 650 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6 675 43 3.6 43 3.7 43 3.8 42 3.2 42 3.3 700 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8 725 44 3.6 44 3.7 44 3.8 43 3.4 43 3.5 750 44 3.3 44 3.4 44 3.6 44 3.7 44 3.8 775 48 3.8 44 3.2 44 3.3 44 3.4 44 3.5 800 48 3.5 45 3.7 48 3.8 44 3.2 44 3.3 7000 825 48 3.3 48 3.4 48 3.8 48 3.7 45 3.8 t3% 850 45 3.1 48 3.2 48 3.4 48 3.8 45 3.6 derate 875 48 3.8 48 3.t 45 3.2 48 3.3 45 3.4 ALTITUDE RANGE (FT) 6001 O _ SPECIFIC GRAVITY to 0.58 0.88 0.82 *Orifice numbers 45 are factory installed Percents of derate are based on midpoints of U.S. altitude ranges 41 8.84 0.85 Table 11--Model 58MSA Orifice Size and Manifold Pressure for Correct Input Continued (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Levem)* ALTITUDE RANGE (FT) GAS 0.5.4 0.99 (BTUICU FT) Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 929 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 990 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3 975 44 3.8 43 3.4 43 3.5 43 3.6 43 3.7 700 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5 799 44 3.3 44 3.4 44 3.5 44 3.6 44 3.7 750 49 9.7 45 3.8 44 3.3 44 3.4 44 3.5 775 49 9.9 45 9.9 49 9.7 45 9.8 44 3.3 8000 800 49 3.3 49 9.4 49 9.5 49 9.9 49 3.7 19% 895 49 3.t 45 3.2 45 3.3 49 9.4 49 3.5 derate 890 49 2.9 49 3.0 45 3.1 49 9.2 49 3.9 to AVG GAS NEAT VALUE AT ALTITUDE SPECIFIC GRAVITY 0.58 0.90 OF NATURAL GAS 0.92 0.64 0.69 (BTUiCU FT) Orifice No. Manifold Pressure Orifice No. Manifotd Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 900 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 929 43 3.5 43 3.6 43 3.8 42 3.2 42 3.3 990 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7 975 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4 700 44 3.2 44 3.3 44 3.4 44 3.6 44 3.7 799 49 9.9 45 3.8 44 3.2 44 3.3 44 3.4 9000 750 49 9.4 49 9.5 45 9.9 49 3.8 44 3.2 17% 779 49 9.2 45 3.3 45 3.4 45 9.9 49 3.9 8OO 49 3.0 49 9.t 49 3.2 49 9.9 49 3.4 800t o to derate SPECIFIC GRAWTY OF NATURAL GAS AVG GAS NEAT VALUE AT ALTITUDE (BTUICU FT) Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure 979 43 3.8 42 3.2 42 3.3 42 3.5 42 3.6 900 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3 929 44 3.7 44 3.8 43 3.5 43 3.6 43 3.7 950 44 3.4 44 3.5 44 3.7 44 3.8 43 3.4 975 45 9.8 44 3.3 44 3.4 44 3.5 44 3.6 700 45 3.9 45 9.7 45 9.8 44 3.3 44 3.4 t0,000 795 45 3.3 45 3.4 45 3.9 49 9.7 49 3.8 19% 750 49 3.1 45 3.2 45 3.3 49 3.4 49 3.5 derate 779 49 2.9 49 3.0 49 9.1 49 3.2 49 3.9 ALTITUDE RANGE (FT) 900t C 4 OF NATURAL 0.92 Orifice No. ALTITUDE RANGE (FT) o 0.90 Manifold Pressure o 4 SPI=CIFIC GRAVITY 0.58 Orifice No. 700t 4 AVG GAS NEAT VALUE AT ALTITUDE to 0.58 0.90 0.92 *Orifice numbers 45 are factory installed. Percents of derate are based on U.S. altitude ranges. 42 0.54 0.99 EXAMPLE: Heating (0 2000 value altitude) 1050 Bmicu ft Specific gravity 062 Therefore: Orifice No. 45 Manifold pressure 3 6=in wc * Furnace is shipped with No. 45 orifices. In this example all main burner orifices are the correct size and do not need to be changed Check to obtain and verify7 burner ORIFI(E SIZE; 2. Adjust NOTE: the proper orifice ALWAYS maniibld pressure Manifold pressure input rate. size in fhnaace. NEVER CHECK always burner b. Remove cap that conceals regulator. c Jumper enclosure (See Fig be measured with burner always A93059 be clocked Fig. 47--Burner adjustment manifold screw, pressure a. Calculate connections on control United to start counterclockwise or clockwise (out) to decrease (in) to increase multiplier manifbld has been approved for a manifold of 32 in. wc to 3.8 in. wc when installed at ahimdes For ahimdes pressure from 22 range, above 2000 ft, the manil:bld in. wc to 3.8 in. wc. If manifold change burner orifices to obtain is outside (if required). ft. 100,000 Btuh input furnace installed at 4300 ft. Furnace input Rate at Sea Level X Derate Multiplier Factor = Furnace Input Rate at Installation Altitude 100,000 X 0.91 = 91,000 can be adjusted pressure pressure pressure up to 2000 adjustment ihctor. EXAMPLE: This furnace high-altitude States At altitudes above 2000 R, this Nrnace has been approved for a 2% &rate for each 1000 R above sea level. See Table 12 ibr &rate pressure NOTE: Orifice screw fk_r gas valve 46.) operation. d. Turn adjusting ORIFICE flout. R and W thermostat f_/rnace ---- input rate enclosure fiont REMOVED Gas meter must with burner enclosure front INSTALLED. a Remove % BURNER ASSUME AND VERIFY to obtain must \ this in this range. Canada --> tNIT DAMAGE HAZARD to ibllow this caution Failure tifc DO NOT bottom out may result gas valve This can result in unregulated excess NOTE: been regulator manit\_ld overfire and heat exchanger If orifice hole appears re&illed, correct size. aligned orifice check Never orifice re&ill e. Replace screw b Reinstall burner box cover. and result in c. Gas valve failures. or it is suspected hole with an orifice. a numbered A burr=fi'ee for proper gas valve regulator furnace adjusting pressure damaged hole is essential in reduced At installation altitudes fiom 200! to 4500 it, this _:_/macemust be &rated 5% by an aud_orized Gas (;onve*sion Station. To determine con'ect input rate for ahimd< see example above and use 095 as derate multiplier fhctor. flame adjustment to have &ill and bit of squarely d Turn e Start furnace seal cap MUST off all other gas appliances and let operate be installed and pilots. for 3 minutes i_ Measure time (in sec) ibr gas meter revolution characteristics. screw regulator test dial to complete 1 cap. g. Reibr to Table 13 %r cuft of gas per hr. i\ Replace burner enclosure fi'ont input rate using method outlined [TNTT DAMAGE and veri/_ in item 3. adjusted gas h. Multiply gas rate (cu flihr) X heating value (Bmicu it) using natural gas heating value from local gas utility/supplier HAZARD Failure to follow damage due to t_is caution flame may result impingement in component of burners and heat Table 12--Ntitude Derate MuNplier for U.S.A. exchangers. DO NOT round re&ill holes, misdirection orifices. etc.) of burner g. Look through burner flame. tlansparent. h. Remove pipes, Be &illing excessive flames. (burrs. burner ALTITUDE out=of = noise {FT} 0--2000 and (See Fig. 47.) jumper sure fiom R and W. gas input rate by clocking all pressure robing, gas meter. cornbustion=air and vent front are in place when checking input % OF BERATE DI=RATE MULTiPLiER FACTOR FOR U.S.A* 0 1.00 4--6 0.95 3001--4000 6--8 0.93 4001--5000 8--10 0.91 8001--6000 10--12 0.89 6001--7000 12--14 0.87 7001--8000 14--16 0.85 8001--9000 16--18 0.83 9001--10,000 18--20 0.81 2001--3000 sight glass in burner enclosure and check Burner flame should be clear blue, ahnost and bunaer enclosure by clocking Improper cause (See Fig. 480 3. Verii}- natural NOTE: can * Derate multiplierfactoris based on midpoint altitude for altitude range. gas meter. 43 BURNER FLAME'-_ _ EXAMPLE: BURNER Furnace (0 input Bm heating 2000 fi altitude) fi'om rating input Heating value of gas Time for 1 revolution Gas rate 975 Btuicu 1:i of 2-cu fl dial 70 sec input adjustment Table 103 X 975 example, the is within orifice !2 SET TEMPERATURE Bmh. ft X cu ftihr 103 cu ftihr (f?om Bm heating In this plate is 100,000 Bmicu 11) 100,425 size percent and Btuh manifbld pressure of the fl/mace input rate. RISE MANIFOLD J A89020 Fig. 48--Burner Table 13--Gas SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL I 2 5 cuff cu fl cu fl Flame [NIT DAMAGE Failure Rate {Cu Ft/Hr) SECONDS FOR 1 REVOLUTION SIZE heat exchangers OF TEST 2 5 cu fl cu fl cu fl this caudon rise must rating plate. Recommended range or slightly 360 327 300 277 257 720 655 600 555 514 1800 1636 1500 1385 1286 50 51 52 53 54 72 144 360 71 141 355 69 138 346 68 136 340 67 133 333 15 16 17 18 19 240 225 212 200 189 480 450 424 400 379 1200 1125 1059 1000 947 55 56 57 58 59 65 131 327 64 129 321 63 126 316 exchanger 62 124 310 practice 61 122 305 20 21 22 23 24 180 171 164 157 150 360 343 327 313 300 900 857 818 783 750 60 62 64 66 68 60 58 120 116 300 290 56 112 281 54 53 109 106 273 265 25 26 144 138 288 277 720 692 70 72 51 103 257 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 37 100 97 200 195 500 486 92 94 39 38 78 76 196 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 terminal 44 82 164 409 108 33 67 167 original 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367 124 29 58 145 Determine be within limits as possible and supply Be sure thermon_eters so that radiant tlaern_ometer readings fl'om supply-air perature rise. 3. Acliust temperature blower speed speed to increase heat does important perature stabilize, SHOCK Failure to %llow or death. this warning 115-v electrical readings stlaight-run subtract blower temperature temperature as close rise. return-air Follow speed BLOWER The blower this same speed. Increase Decrease blower HAZARD could result in personal power before changing injury speed tap 14 for lead color identification. Reconnect terminal procedure %r proper selection of (OOL selection OFF DELAY offdelay (HEAT MODE) has 4 adjustable Table 14--Speed COLOR Black (When Present) Blue Red White 44 mode, termi- blower motor speed lead and relocate it to HEAT settings h'om 90 sec to 180 sec. (See Table 15.) The blower off delay jumpers the fl/rnace control board (See Fig. 33) To change Yellow tern: air tem- rise. nal. (See Fig 33) Select desired fi'om 1 of the other motor leads See Table This ducts. 4. To change blower motor speed selections for heating remove blower motor lead J:'rom control center HEAT lead on SPARE to do not see heat to detemaine rise by adjusting to redtlce ducts not affect with temperature ELECTRICAL Disconnect of rise rise as fbllows: in return is particularly 2. When on hlmace is at mi@oint above. thermometers fi/rnace d-xe exchanger specified operation and ac[iust air temperature 1. Place in overheating flue gases in heat for condensate. Temperature 10 11 12 13 14 may result or condensing areas not designed DIAL 1 HAZARD to fbllow are located on the blower off Selector SPEED FACTORYSHIPPED CONNECTION High Cool Medium High Medium Low Spare Heat Low Common Spare Corn Table18--BlowerOff DelaySetupPosition 2 PiNS 1 AND 2 2 AND 3 3 AND 4 4 AND 8 Time (in sec) 90 120 150 180 board move the jumper to the pins used blower off delay SET THERMOSTAT When using anticipator circuit. thermostat method HEAT amp subbase be taken after Connect ammeter Factoiw should measurements be has obtained and furnace in Fig. 49. manufacturer's raving instructions heating should for adjusting covers set cycle SAFETY the safety is complete. pressure were all checked switch as part of nom_al operation. Step l--Check Primary This control shuts off blower The anticipator of checking limit gas opening should be unblocked this method to check be_bre valve, system and overheats control energizes is to gradually air- block off of at least return-air to pem_it nora?HI air circulation. limit control, it can be established this test, cause Step 2--Check This control operation must be determined Pressure pIoves By that and con'ected. Switch opeiation of draf_ inducer (heel< switch as fbllows: 1. Turn off 115-v power to furnace. TERMINALS WITH THERMOSTAT REMOVED FROM UNIT 24-VOLT TERMINAL BLOCK EXAMPLE: 5 0 AMPS 10 TURNS ON AMMETER AROUND JAWS = 0.5 AMPS FOR THERMOSTAT SETTING A80201 Fig. 49--Amp Review 7. Leave section limit is t\mctioning properly and operates if there is a restricted return-air duct or motor _i_ilure. If limit control does not [hnction during Verify 6 and Recommended return air aker furnace has been operating for a period 5 minutes. As soon as limit control has shut offburners, using Put away 2 5. Check lions. Control control it" fm'nace this per hour. in the Start=up procedure Limit gas motor 1 immediately. Determine properly and correct to _i/rnace. leads, reinstall main furnace door, supply. tools and instruments. flame 3. Verify that installed. and for that must be checked sensor, down did not function CHECKUST See thermostat rate for 3 cycles flame furnace motor thermostat CONTROLS controls the installation method heat inducer is heating. The 4. Cycle thermostat, CHECK circulating measurement. igniter status and mm on 115=v power cycle tengd_. For an electronic This section cun'ent When surface motor 6. Reconnect anticipator should NOT be in the circuit while measuring current. If them_ostat has no subbase, the them?ostat must be disconnected from R and W wires during status 1 minute hot code LED flashes 5. Turn off 115=v power at an easy The anap reading started as shown lead in R-W R and W. Fig. 49 illustrates motor wires can heat and wait properly, and control them_ostat, these measurements. blower NOT glow, shut them_ostat motor code 31 _imlt. [f hot sur_itce igniter g!ows when inducer switch the for heat" is _imctioning reason pressure condition. draw terminals switch is disconnected, amp draw of components inducer to furnace. to "call ANTI(IPATOR a nonelectronic of obtaining off delay. Set them_ostat pressure is 120 sec. must be set to match Accurate blower door and disconnect 3. Turn on 115-v power flora one set of pins on the conhol for the desired setting main fi/rnace wires flora wire harness. 4 delay setting, Remove Draw Check w{th Ammeter 45 rollout manual blower test fi_rnace operation User's literature and (lean up debris. reset switch main access with room them_ostat. of accessories per Guide with packet owner near furnace. has continuity. doors are manufacturer's properly instl_ac- CH ECKL[ST--BNSTALLAT[ON LOAD CALCULATION Condensate Drain Heating Load (Btuh) Unit Level or Pitched Forward Cooling Load (Btuh) Internal Tubing Connections and Traps Free of Kinks Furnace Model Selection External Drain Connection Sloped VENT PIPING Termination Condensate Location CHECKLIST--START-UP Vent Pipe Length Gas Input Rate (Set Within 2 percent of Rating Plate) Vent Pipe Elbow Quantity from Sizing Table Temperature Pipe Sloped To Furnace Thermostat Pipe Insulation Rise Adjusted Anticipator Anticipator Setting Adjusted or Over Ceitings Low-Ambient Trap Primed before Start-Up Heat Tape Installed if Required Roof or Sidewall Pipe Diameter Determined Leak Tight and Cycte Rate (3 Cyctes per Hr) Setected Exposed Pipes Safety Controls Check Primary Limit Pressure Switch 4d Operation 47 Copyright 2005 CARRIER Manufacturer Book Tab 1 4 6a 8a reserves PC 101 Corp. the _ 7310 right Catalog W. Morris St to discontinue, No 535-80154 • Indianapolis, or change Printed IN 46231 at any time, in U.S.A. 58msa1 specifications Form or designs 58MSA-11SI without notice Pg 48 and without 2-05 incurring Replaces: obligations, 58MSA-10SI lsi
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 48 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 16:30:50 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools