CARRIER Package Units(both Units Combined) Manual L0604564
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 28
| Download | |
| Open PDF In Browser | View PDF |
HEATING & COOLING
3-Phase
Visit
Single-Packaged
50JS, 50JX
Heat Pumps
www.carrier.com
Installation, Start-Up,
and Service Instructions
NOTE: Read
installation.
the entire
instrdction
TABLE
SAFETY
RECEIVING
before
starting
the
OF CONTENTS
CONSIDERATIONS
INTRODUCTION
manual
.....................................................
1
..........................................................................
AND INSTALLATION
2
..........................................
2
Check Equipment ......................................................................
IDENTIFY
UNIT ................................................................
INSPECT
SIMPMENT
2
2
........................................................
2
Provide Unit Support ................................................................
ROOF CURB .......................................................................
SLAB MOUNT ...................................................................
2
2
2
GROUND MOUNT ............................................................
Provide Clearances ....................................................................
2
2
Rig and Place Unit ....................................................................
INSPECTION
......................................................................
2
2
INSTALLATION
................................................................
Select and Install Ductwork .....................................................
2
4
CONVERTING
DOWNFLOW
HORIZONTAL
(VERTICAL)
DISCHARGE
DISCHARGE
UNITS
TO
UNITS ......... 5
Provide for Condensate Disposal .............................................
Install Electrical Connections ...................................................
HIGH-VOLTAGE
CONNECTIONS
................................
ROUTING
POWER LEADS INTO UNIT ......................
CONNECTING
GROUND
LEAD
TO GROUND
C99001
7
8
Fig. 1--Model 50JS/50JX
I0
10
LUG.10
ROUTING
CONTROL POWER WIRES (24-V) ............ 13
SPECIAL PROCEDURES
FOR 208-V OPERATION ...15
PRE-START-UP
START-UP
..........................................................................
17
...................................................................................
Check for Refrigerant Leaks ..................................................
Start-Up Adjustments ..............................................................
CHECKING
COOLING
AND HEATING
CONTROL OPERATION .................................................
CHECKING
AND
ADJUSTING
TROUBLESHOOTING
START-UP
17
REFRIGERANT
NOTE
18
19
MAINTENANCE
.........................................................................
Air Filter ..................................................................................
25
--
READ
THESE
INSTRUCTIONS
before installing this unit.
and Service Instructions are
SAFETY CONSIDERATIONS
Installation
20
21
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning
equipment.
21
CONDENSATE
DRAIN PAN ...............................................
Outdoor fan .............................................................................
22
23
Electrical controls and wiring ................................................
Refrigerant circuit ...................................................................
Indoor airflow .........................................................................
23
24
25
Metering
device ......................................................................
25
line strainers ................................................................
25
and servicing
of air-conditioning
equipmem
can be
Untrained personnel can perform ba._ic maintenance
functions of
cleaning coils and filters. All other operations should be performed
by trained
service
personnel.
When
working
on air-conditioning
equipment,
observe precautions in the literature,
attached to the unit, and other safety precautions
tags, and labels
that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
Manufacturer reserves the right to discontinue, or change at any time, specifications
Printed in U.S.A.
25
............................................................
I9
Indoor blower and motor ........................................................
OUTDOOR
COIL, INDOOR COIL, AND
PC 101
TO INSTALLER
...............................................................
CAREFULLY
AND COMPLETELY
Also, make sure the Owner's Manual
CHARTS .................. 19
AIRFLOW
ADJUST-
..............................................................................
CHECKLIST
left with the unit after installation.
NO CHARGE ....................................................................
LOW CHARGE COOLING .............................................
Liquid
25
25
25
25
17
17
18
18
MENTS
25
Time-delay
relay .....................................................................
Loss of charge switch .............................................................
Check defrost thermostat ........................................................
Defrost Thermostat .................................................................
17
CHARGE ...........................................................................
REFRIGERANT
CHARGE ..............................................
TO USE COOLING CHARGING
INDOOR
AIRFLOW
AND
High Flow Valves ...................................................................
Catalog No. 50JS,JX-6SI
or designs without notice and without incurring obligations,
Pg 1
2-06
Replaces: New
IMPORTANT:
Improper installation, adjustment,
alteration, service, maintenance, or use can cause explosion, fire, electric shock, or
Curb
should
be level
to within
1/4 in. (See Fig.
6). This
is
necessary for unit drain to function properly. Refer to accessory
roof curb installation
instructions
for additional
information
a-s
service agency for information
or assistance. The qualified
installer or agency must use only factory-authorized
kits or
when modifying
of the unit to the roof curb is critical
and poor unit performance.
other occurrences, which could cause serious injury or death
or damage your property. Consult a qualified installer or
accessories
The gasketing
for a watertight seal. Install gaskeling material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
required.
this product.
SLAB MOUNT
Recognize safety information. This is the safety-aler_ symbolAx.
When you see this symbol on the product or in instructions or
manuals,
be alert to the potential
for personal
Place the unit on a solid, level concrete
4 in. thick with 2 in. above
injury.
pad that is a minimum
of
grade (See Fig. 7). The slab should
Understand
the signal words -- DANGER, WARNING,
CAUTION, and NOTE. Danger identifies the most serious hazards,
extend approximately
2 in. beyond the casing on all 4 sides of the
unit. Do not secure the unit to the slab except when required by
local codes.
which will result in severe personal injury or death.
indicates a condition that could cause serious personal
GROUND
Warning
injury or
The unit may be installed
death. Caution is used to identify unsafe practices, which would
result in minor personal injury or product and property damage.
NOTE is used to highlight
suggestions
which
enhanced installation, reliability, or operation.
result
in
1. The power supply (volts, phase, and hertz) must correspond
that specified on unit rating plate.
to
2. The electrical
to handle
supply provided
load imposed
will
either on a slab or placed directly on the
ground if local codes permit. Place the unit
prepared with gravel for condensate discharge.
on level
The required minimum service clearances are shown in Figs. 2 and
3. Adequate ventilation
and ouUloor air must be provided. The
by die utility must be sufficient
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
by this unit.
or waste water codes and other applicable
and
and
under a partial overhang (such as a normal house overhang)
in. above the unit top. The maximum horizontal extension
local
partial overhang must not exceed 48 in. For extended
provide a minimum clearance of 48 in.
IMPORTANT:
Do not restrict
at either the outdoor-air
detrimental to compressor
severe
ground
Step 3---Provide Clearances
3. This installation must confurm with local building codes
with NEC (National Electrical Code). Refer to provincial
local plumbing
codes.
MOUNT
inJUry or death.
outdoor
inlet
life.
or
airflow.
die fan
is 36
of a
overhangs,
An air restriction
discharge
may
be
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting
or other combustible
materials.
Slab-mounted
units
INTRODUCTION
The 50JS and 50JX heat pumps are fully self-contained
and
designed for outdoor installation (See Fig. 1). Standard units are
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
shipped in a horizontal-discharge
configuration
for installation on
a ground-level
slab, Units can be converted to downflow (vertical)
Step 4--Rig
discharge
configurations
for rooftop
applications.
Rigging and handling of this equipment
reasons due to the installation location
etc.)
RECEIVING AND INSTALLATION
Step 1--Check Equipment
IDENTIFY
identification
pers.
INSPECT
plate.
and serial number are stamped
Check
this information
against
on the unit
shipping
When
pa-
SHIPMENT
it examined
by transportation
working
with this equipment,
observe
support
precautions
staff
in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Follow
gloves.
Inspect for shipping damage while unit is still on shipping pallet.
If ualt appears to be damaged or is torn loose from its anchorage,
have
can be hazardous for many
(roofs, elevated structures,
Only trained, qualified crane operators and ground
should handle and install this equipment.
UNIT
The unit model number
and Place Unit
inspectors
before
all applicable
safety
codes.
Wear safety shoes
and work
INSPECTION
removal.
Forward claim papers directly to transportation
company. Manufacturer is not responsible
for any damage incurred in transit.
Check all items against shipping list. Immediately
notify the
Prior to initial use, and at monthly
nearest Carder Air Conditioning
office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing any kind of wear in these
areas must not be used and should be discarded.
Step 2--Provide
INSTALLATION
Unit Support
ROOF CURB
Install accessory
intervals,
all rigging brackets
and straps should be visually inspected for any damage,
of wear, structural deformation,
or cracks, particular
evidence
attention
1. Remove unit from shipping carton. Leave top shipping skid on
roof curb in accordance
with instructions
with curb (See Fig. 5). Install insulation, cant strips,
flashing. Ductwork must be attached to curb.
shipped
roofing,
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
and
2
/_[V_P0eAT0e
C01t
_lllllllllllllllllll_
HIIIIIIIIIIIII!lllml_
I
t
FEG_J_)
a_-iilLll/iC_S
Ti_ C{Ji_'I]HUE
M_.,
U
TOP VIEW
W._'ia-
,
t3 ,s_
_
WILLIWETER$ {IN)
355¸6 {14.00}
50 8 [2 00}
_55.6 (1_ 00}
121
{0.50)
_14 4 [3_ 001
FOP OF UNIT ...................................
DU¢1 S_O[ OF UNIT .............................
_ID[ OPPOSIT[ OUCTS............................
BOTTOll OF _iHI1 ...............................
ELECTRIC H_AT PANEL ..........................
iUPPL_
_UCT
OPEW_WG,
_O?
[_5 8_1
_
.
DL_T
OpEwiWG
REAR VIEW
ROR _l_fl
/€_
_
MILLtM[TER_ { INI
9_4.0 [3_ 001
9_4 0 [3_ 001
[VAp COIL ACC[$$ $1D[ .....................
P_[_
[HIR_ $rD[ ..........................
([ICEPT
FOR HEC R[OUIREWEWTS}
uHrT TOp .............................
SID[ OPPO_IT[ DLiCIS ......................
_U_T PAN[L ..........................................
914.0
_;4.0
304¸8
[3_ 001
{3_.001
[1_.00]_
CLF.AdUdiC_
BETWEEH UNITS, POI[R [#TRf SI{)[ .......................
UHIT kWD UN_ROUNO[_ SURF_C[$, pO,ie[R [NIRY SlOE ....
UWIT _WD BLOCK Oe _Oe_:R[TE WALL_ AHD OI_ER
GROUNDEDSURFAC_S, POi[R[RTR_51D[
..............
W_LLIW[T[RS [IN]
_065 8 [_
00)
91_ 0 {35 00]
_066.814_.00]
,_IHIHUW
DIMENSIONS
DISTAHC[S:_F
_HIT IS PLACID LESS THAH _Od8
[1_ 0_1 FR{_,dWALL
$_STEW,TH[N S_ST[W PERFORWAHC[ WkYBE ¢_PROWIS[D.
[N
[]
IN
ARE
INCHES
t
,I,Ll l!llllll
.
•
I
,
,
i
.
t
IL_3]_
RIGHT SIDE VIEW
FRONT VIEW
C00137
UNIT
ELECTRICAL CHARACTERISTICS
50JS03O
208/230-3-60
UNIT WEIGHT
Ib
kg
UNiT HEIGHT
IN. (MM)
"A"
287
130.2
39.02 (991.1)
X
CENTER OF GRAVITY
IN.(MM)
Y
Z
50JS036
208/230-3-60,
460-3-60
291
132.0
37.02 (940.3)
19.5 (495.3)
19.5 (495.3)
208/230-3-60,
460-3-60
323
146.5
37.02 (940.3)
19.7 (500.4)
13.7 (348.0)
14.0 (355.6)
13,0(330.2)
50JS042
50JXO30
37.02 (940.3)
37.02 (940.3)
14.0 (355.6)
208/230-3-60,
145.2
148.8
19,7 (500.4)
50JX036
320
328
19.7 (500.4)
14.0 (355.6)
17.6 (447.0)
16.5 (419.1)
263/230-3-60
460-3-66
Fig. 2--50JS030-O42/50JX030-036
2. Position
the lifting bracket
assembly
around
the ba._e of the
unit. Be sure the strap does not twist.
3. Place each of the 4 metal tiffing brackets
in the composite
a. Open lever of tension buckle
(ratchet
type).
c. Pull strapping
through
perimeter
of
buckle as shown in Fig. 8.
tension buckle
5. Tighten
the tension
buckle
until
it is taut. Lifting
brackets
7. Attach the 2 safety strops directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
tiffing brackets (See Fig. 8).
bottom
tension
Unit Dimensions
6. Attach field-supptied
clevis or hook of sufficient
hole in the tiffing bracket (See Fig. 8).
around
through
13.0 (330.2)
into the rigging holds
strapping
b. Feed strapping
15.0 (381 .o)
must be secure in the rigging holds.
pan.
4. Thread lifting bracket
unit as follows:
13,7 (348.0)
unit taut.
d. Snap lever down to lock strap in tension buckle. To release
strapping, squeeze safety latch, lift lever, and pull webbing
outward.
8. Position
lifting point directly
over the unit's
strength
to
center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the
2 safety straps. Lower the equipment onto the roof curb.
Step S--Select
and Install Ductwork
The design and installation
of the duct system must be in
accordance
with the standards
of the NFPA for installation
of
JllllllllJllllllll
lll!lllllllllllllII
_UPPL_ "
,
.
402
[15 _3]
rm[NlUG
I
I
--34_3
/
FdmLIFS)
CLF.ARANC_$ TO _
TOP VIEW
MEC. REGUFa)
I
_
REAR VIEW
IM_TL
FIEaLIR_D _
MELLIM[T[RS
[[g]
35S.6 [14 00]
S08
[Z 00]
355 6 [14 00]
I_ 7 [0 S01
914¸4
(3_C0]
TOP OF UNIT ........................................
DUCT $1D[ OF UNIT ...................................
SIO_ OPPOSIIE DUCTS
.........................
80TIll
Or
•
ELECTRIC _[k7 PkNEL
........................
NETUNN
FOR _'noN
_
MILLIMETERS {IN]
9140
[36001
914_
[360_}
EVAP. COIL ACC[S$ SlOE ............................
POiE_ [NTEY SID[ .................................
I[X_PI
FOR gEC REOUIR[_[NTS}
SI_E OPFOSIT£ DUCIS
_ll_T pkNEL .......................
.................
914¸0
304¸8
[3600]
[1_00]*
C_JOUNCEI
BETWE[N UNITS, POM[R [RTR? SII)[ ................
Ugll kND IINGROUND[D SUBFkC[S.
POiER [NTRy SJ[JE
UNII kND BL_
OR CO_RETE
WkLLS kND OTN[R
61tOUNOED $UItFkC[S.
pOW[It ENTRY SI_[
...............
MILLIMETERS {IK]
J066.8 [42 00]
914.0
[3G 01_]
........
10668
[_2
IMIRIMUW
00]
DISIANC[_IF
DIM[NSIONS
[41
IN
[]
UNI[ I_ PLAC[O LESS fNkN 304 8 [12 00] FBO_ WALL
SY$1EM.IN[N
$_$T[N p[R_OENkNC[ N_O[
_OgPgOMIS[O.
A_E
IW
INC_[S
00)
/
ittttttft ttl t,
i ililllllliillllltti
tttttttlt{ttt{l.
Jllllltllllllllllh
IIjIIIIIIIIII IlU
PONE_ E_IN_
,!llllll!l, llllltlill
184 6
'
=i=, _'
i_--_
lilt
I
LEFT SIDE
UNIT
_
"i"
.i'
•
=_
_ii_,
VIEW
5o
[4 81]
,_ ...........
ELECTRICAL CHARACTERISTICS
FRONT VIEW
UNIT
WEIGHT
RIGHT SIDE VIEW
UNIT HEIGHT
IN. (MM)
Ib
kg
5_S_8
208/230-3-60,
460-3-60
353
160.1
"A"
5_S_0
208/230-3-60,
460-3-60
418
189.6
5_X_2
5_X_8
208/230-3-60,
460-3-60
350
158.8
40.98
208/230-3-60,
468-3-60
315
170.1
40.98
5_X_0
208/230-3-60,460-3-60
428
194.1
42.98
38.96
38.98
Fig. 3---50JS048-060/50JX042-060
4
X
C00136
CEWrER OF GRAVITY
IN. (MM)
Y
z
(990.2)
19.9 (505.5)
15.7 (398.8)
17.0 (431.8)
(990.2)
19.9 (505,5)
19.9 (505.6)
15.7 (398.8)
15.7 (398.8)
17.0 (431.8)
(1040.9)
(1040.9)
19.9 (505.5)
15.7 (398.8)
16.6 (421.6)
18.0 (457.2)
(1091.7)
19.9 (505.5)
15.7 (398.6)
17.6 (447,0)
Unit Dimensions
1
2
Y
4
3
X
G00071
CORNER WEIGHTS (SMALL CABINET)
Unit
30
36
O)
o
tt_
o
O
287
291
323
Corner Weight 1
66
67
83
Corner Weight 2
54
55
55
Corner Weight 3
Corner Weight 4
62
105
63
106
78
107
x
U3
13
0
42
Total Weight
CORNER WEIGHTS (SMALL CABINET)
Unit
30
36
320
328
--
Corner Weight 1
Corner Weight 2
63
74
64
76
---
Corner Weight 3
56
58
--
Corner Weight 4
127
130
--
Fig. 4_Corner
Select and size ductwork,
supply-air
o
0
X
o
o
"D
o
--
When designing
For vertical
and installing
ductwork,
consider
90
Corner Weight 2
Corner Weight 3
49
96
58
114
Corner Weight 4
132
156
60
Total Weight
350
375
428
Corner Weight 1
75
81
92
Corner Weight 2
Corner Weight 3
49
95
52
102
60
116
Corner Weight 4
131
140
160
unit to prevent
Use flexible
transmission
ensure weather tight
installed, use fireproof
and return air grilles
and return-air
418
76
IMPORTANT:
connectors
of vibration.
between
ductwork
Use suitable
and
gaskets
to
and airtight seal. When electric heat is
canvas (or similar heat resistant material)
connector between ductwork
and unit discharge connection.
If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning
Engineers) recommendations.
The unit has duct flanges on the supplythe side of the unit.
353
Weights (in Pounds)
and ventilating systems, NFPA
90B and/or local codes and
registers,
Total Weight
Corner Weight 1
CORNER WEIGHTS (LARGE CABINET)
Unit
42
48
--
Total Weight
non-residence
type air conditioning
90A or residence
type, NFPA
ordinances.
CORNER WEIGHTS (LARGE CABINET)
Unit
48
60
resistant duct connector (or sheet metal sleeve)
from electric heater element.
openings on
3. Size ductwork
die following:
for cooling
air quantity
must extend 24-in.
(cfm). The minimum
air quantity for proper electric heater operation is listed in
Tables 3 and 4. Heater limit switches may trip at air quantities
below those recommended.
supply and return units, tools or parts could drop
4. Seal, insulate,
and weatherproof
all external
ductwork.
Seal,
into ductwork and cause serious injury or death. Install a 90
degree turn in the return ductwork between the unit and the
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and Air
conditioned
space. If a 90 degree elbow cannot be installed,
then a grille of sufficient
strength and density should be
installed to prevent objects from falling into the conditioned
Conditioning
Contractors National Association
(SMACNA)
and Air Conditioning
Contractors Association (ACCA) minimum installation
standards
for residential
hearing and air
space. Units with electric
supply duct.
conditioning
heaters
require
90 degree
elbow in
5. Secure all ducts to building structure. Flash, weatherproof,
and
vibration-isolate
duct openings in wall or roof according to
I. All units should have field-supplied filters or accessory falter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Tables 1 and 2.
2. Avoid
change
abrupt duct size increases
and reductions.
in duct size adversely affects air performance.
systems.
good construction
Abrupt
5
practices.
VACunit
/
ou .a.
Rashing field
•
Wood nailer*
I_:11 _¢ Insulation
(field
field supplied --
-Duct work
Cant strip
field supplied
field supplied
Roof Curb for Small Cabinet
Roof
Note A:When unit mounting screw is used
retainer bracket
must also be used.
Curb for
Large Cabinet
Note A:When unit mounting screw is used
retainer bracket must also be used.
SUpp opening
IBx_
\/
/\
\
R/A
\
Insulated
deck pan
S/A
_-Gasket
around
duct
Gasket around
outer edge _
Long
Returnopemng
(exc)
C00076
UNIT SIZE
50JS030-042
50JS048-060
50JX030-036
50JX042-060
ODS CATALOG NUMBER
A
B
IN.(MM)
C
D
IN. (MM)
IN. (MM)
CPRFCURBO06AO0
6 (203)
11(279)
151/2 (419)
28-3/4
IN. (MM)
CPRFCURBOO7AO0
14 (356)
11(279)
161/2 (419)
28-3/4
CPRFCURB008AO0
8 (203)
16 3/16 (411)
17 3/8 (441)
40-1/4
(730)
(730)
(1022)
CPRFCURB069A00
14 (356)
16 3/16 (411)
17 3/8 (441)
40-1/4 (1022)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gauge steel.
5. Table lists only the dimensions, per pad number, that have changed.
6. Attach ductworb to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 Ib density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or
seismic conditions. This bracket is available through Micrometl.
Fig. 5_Roof
Curb Dimensions
6
MAXIMUM
ALLOWABLE
DIFFERENCE(in.)
B
A-B
1/4
A-c
1'4
C99065
Fig. 6--Unit Leveling Tolerances
COND. COrL
EVAR COIL
C99096
Fig. 7--Slab Mounting Detail
CONVERTING
DOWNFLOW
HORIZONTAL
(VERTICAL)
DISCHARGE
DISCHARGE
UNITS
TO
The units dispose of condensate through a 3/4 in. NPT female
fitting that exits on the compressor
end of the unit. Condensate
UNITS
water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level installa-
M_
Before
performing
service
system,
turn off main power
or
maintenance
operations
to unit and install lockout
Turn off accessory heater power switch if applicable.
trical shock could cause serious injury or death.
1. Open all electrical disconnects
starting any service work.
and install lockout
2. Remove side duct covers to access bottom
knock outs.
NOTE: These panels
electrical knockout.
are held in place
return
with water. When using a gravel apron, make sure it slopes away
from the unit.
and supply
If the installation
requires draining
from the unit, install a field-supplied
4. Ensure the side duct covers
horizontal
air openings.
to block
Avoid
abrupt duct size increases
in duct size adversely
Step 6--Provide
affects
for Condensate
and reductions.
as an accessory or is field-supplied. Make sure that the outlet of the
trap is at learnt I in. lower than the unit drain-pan condensate
in the
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field-supplied
3/4 -in. PVC or
field-supplied 3/4 -in. copper pipe at outlet end of the 2 -in. trap
(See Fig. 11). Do not undersize the tube. Pitch the drain trough
downward at a slope of at least 1 in. every l0 ft. of horizontal run.
off the
Abrupt
Be sure to check the drain trough for leaks. Prime the trap at the
beginning
Disposal
methods
trap is available
to an
air performance.
NOTE: Ensure that condensate-water
disposal
with local codes, restrictions, and practices.
the condensate water away
2-in. trap at the condensate
connection to ensure proper drainage. Condensate
the panels
change
the trap is at lea_st 1 in. lower than the drain-pan condensate
connection to prevent the pan from overflowing.
Prime the trap
tag before
3. U_ a ,screwdriver and hammer to remove
bottom of the composite unit base.
NOTE:
tag.
Elec-
with tabs similar
are in place
tions. Install a field-supplied
condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
on
comply
7
of the cooling season
start-up.
Table 1--Physical
50JS03O
UNIT SIZE
Data
50JS036
50JS042
50JS048
5OJS060
NOMINAL CAPACITY (ton)
2-1/2
3
3-1/2
4
5
OPERATING WEIGHT (lb.)
COMPRESSOR QUANTITY
TYPE
287
291
323
353
418
1
RECIPROCATING
COMPRESSOR
SCROLL
REFRIGERANT
REFRIGERANT
COMPRESSOR
R-22
METERING DEVICE
Refrigerant (R-22) Quantity (lb.)
ORIFICE ID (in.)
ORIFICE OD (in.)
OUTDOOR COIL
Rows... Fins/in.
Face Area (sq, ft.)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
INDOOR COIL
Rows... Fins/in.
Face Area (sq. ft,)
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor HP (RPM)
AccuRater_
5.6
7.6
8.0
7,85
9.3
0.068
0.078
0.078
0.088
0.093
0.046 (2)
0.052 (2)
1...17
12.0
2,,.17
10.3
2.,.17
10.3
2...17
11.6
2...17
11.6
2400
22
2800
22
3300
22
3300
22
1/8 (825)
1/4 (1100)
2400
22
1/8 (825)
1/4 (1100)
1/4 (1100)
3-.15
3.7
3...15
3.7
4...15
3.7
3...18
4.7
4,..15
4.7
1000
10X10
1200
11X10
1250
11X10
1600
11XI0
2000
11X10
1/4 (1075)
1/2 (1075)
3/4 (1075)
3/4 (1075)
1 (1100)
20X20X1
20X24X1
24X30X1
0.042
RETURN-AIR FILTERS (in.)
throwaway
(2)
Table
2--Physical
0.057
(2)
24X30X1
0.061 (2)
24X30X1
Data
UNIT SIZE
50JX030
2-1/2
50JX036
3
50JX042
3-1/2
50JX048
NOMINAL CAPACITY (ton)
4
50JX060
5
OPERATING WEIGHT (lb.)
COMPRESSOR QUANTITY
TYPE
32O
328
350
375
428
1
SCROLL COMPRESSOR
REFRIGERANT
REFRIGERANT
R-22
AccuRater_
METERING DEVICE
Refrigerant (R-22) Quantity (lb.)
6.4
7.0
10.8
ORIFICE ID (in.)
ORIFICE OD (in.)
OUTDOOR COIL
Rows... Fins/in.
Face Area (sq, ft,)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
0.073
0.076
0.080
10.1
0.088
0.093
0.043 (2)
0.040 (2)
0.052 (2)
01057 (2)
0.063 (2)
2...17
10.3
2...17
10.3
2...17
13.7
2...17
13.7
2..,17
15.7
2350
22
2800
22
114 (1100)
2800
22
1/8 (825)
3300
22
1_ (1100)
3300
22
1/4 (1100)
1/8(825)
12.3
INDOOR COIL
Rows... Fins/in.
Face Area (sq. ft.)
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor HP (RPM)
3...15
3.7
4...15
3.7
4...15
4.7
4._15
4.7
4...15
5.7
1000
10X10
1/4 (1075)
1200
10X10
1/2 (1075)
1400
11X10
1/2 (1075)
1450
11X10
1/2 (1075)
1750
11X10
1 (1040)
RETURN-AIR FILTERS (in.)
throwaway
20X20X1
20X24X1
24X30X1
24X30Xl
24X30X1
NOTE;Air filter pressure dropfor non-standardfiriers mustnotexceed 0.08 in. wg.
Table
3_Minimum
Airflow
for
Reliable
Electric
Heater
Operation
(Cfm)
SIZE
50JS030
50JS036
50JS042
50JS048
50JS06O
AIRFLOW (CFM)
1000"
1200
1400
1600
2000
* The 030 siZemodels mustbe run on mediumor highspeedwhen usedin coniunction
with 15 kwelectric heataccessory
Table 4---Minimum Airflow for Reliable Electric Heater Operation (Cfm)
SIZE
50JX03O
50JX036
50JX042
50JX048
50JX060
AIR FLOW (C FM)
13O0"
1200
1400
1600
2000
• The 030 size models mustbe runon mediumor highspeedwhen usedin conjunction
with 15 kwelectricheataccessory
DETAIL A
(
SEEDETAILA_'
A05179
UNIT
Size
MAXIMUM WEIGHT
(INCLUDES SHIPPING SKID)
Lb
Kg
A
B
In.
Mm.
In.
in3.
50JS030
50JS036
3O9
313
140.2
19.5
495.3
17,50
444.5
142,0
19.5
50JS042
345
19.5
495.3
495.3
17.75
17.75
450.9
450.9
50JS048
50JS060
375
156.4
170.1
20.5
520.7
20.62
523.8
440
199.6
495.3
19.75
501.7
50JXO30
50JX036
342
155.2
19.5
20.0
508
19,25
489
350
159.8
20.0
372
377
45O
168.8
171.0
21.O
20.0
19.0
20.5
482.6
50JX042
50JX048
508
533.4
204.2
21.0
508
533.4
21.25
20.0
50JX060
Fig. &--Suggested
520.7
539.8
508,0
Rigging
C00139
Fig. 9_Typical
Installation
Failure to follow these precautions
the unit being installed:
1. Make all electrical connections
ANSI/NFPA
(latest
could result in damage
in accordance
edition)
and
local
to
with NEC
electrical
codes
governing
such wiring. In Canada, all electrical connections must be in accordance
with CSA standard C22.1
Canadian
Electrical
Code Part I and applicable
codes. Refer to unit wiring diagram.
2. Use only copper conductor
for
field-supplied
electrical disconnect
NOT USE ALUMINUM
WIRE.
local
connections
between
switch mad unit. DO
3. Be sure that high-voltage
power to unit is within operating
voltage range indicated on unit rating plate. On all 3-phase
units, ensure phases are balanced within 2 percent. Consult
local power company for correction
of improper voltage
and/or phase imbalance.
4. Insulate
Horizontal Duct Covers
c99030
Fig. 10--50JX with Duct Covers On
(Unit Shown with Optional Louvered Grille)
HIGH-VOLTAGE
+
+
TRAP
OUTLET
_
F'_
--""""7
_
The unit
Trap
have
a separate
electrical
service
with
a field-
If the unit has an electric heater, a second disconnect
required. Consult the Installation,
Start-Up, and Service
may be
Instruc-
tions provided
tions.
connec-
Operation
with the accessory
of unit on improper
may cause unit damage
an uninterrupted,
unbroken
the possibility
of personal
ROUTING
POWER
for electrical
line voltage
service
constitutes
abuse and
that could affect warranty.
LEADS
INTO
UNIT
Use only copper wire between disconnect and unit. The highvoltage leads should be in a conduit until they enter the duct panel;
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground lug
in the control compartment, or conduit approved for electrical
conduit termination
at the duct panel must be watertight. Run the
high-voltage leads through the power entry knockout on the power
entry side panel. See Fig. 2 and 3 for location and size. When the
ground when installed in accordance with NEC, ANSI/NFPA=
American National Standards Institute/National
Fire Protec-
leads are inside the unit, pJn leads up the high-voltage
tion Association
(latest edition) (in Canada, Canadian Electrical Code CSA C22.l) and local electrical codes. Failure to
adhere to this warning
must
(ampacity) for wire sizing (See Tables 5 and 6 for electrical data).
The field-supplied
disconnect may be mounted on the unit over the
high-voltage
inlet hole (See Fig. 2 and 3).
¥!_ |','l:%q_,1I_
must have
to minimize
CONNECTIONS
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate, NEC and local codes
2" 50mm) MIN
.
]-or maximum fuse/c rcu breaker size and minimum circuit amps
Electrical Connections
The unit cabinet
electrical ground
contained
control wires are in same
T
j_
C99013
Fig. 11--Condensate
wires for lfighest voltage
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
1" (25ram) MIN.
Step 7--Install
low-voltage
within conduit when low-voltage
conduit as high-voltage
wires.
raceway
to
the line wiring splice box (See Fig. 12-17). On all 3-phase units,
connect the leads to the black, yellow, and blue wires (See Fig.
16).
could result in serious injury or death.
CONNECTING
Connect
GROUND
the ground
LEAD
TO GROUND
lead to the chassis
LUG
using the ground
lug in the
wiring splice box (See Fig. 16).
ROUTING
CONTROL
Form a drip-hiop
POWER
WIRES
with the thermostat
(24-V)
leads before
routing
them
into the unit. Route the thermostat leads through grommeted,
low-voltage
hole provided in unit into unit control power splice
box (See Fig. 2 and 3). Connect thermostat leads to unit control
power leads as shown in Fig. 15.
The unit transformer
supplies 24-v power for complete system
including accessory electrical heater. An automatic-reset circuit
breaker (See Fig. 17) is provided in die 24-v circuit; see the caution
label on the transformer or Fig. 18. Transformer is factory wired
for 230-v operation. If supply voltage is 208-v, rewire transformer
primary
section.
10
as described
in Special
Procedures
for 208-v
Operation
Table 5_Electrical
UNIT 50JS
SIZE
O3O
_PH-HZ
208/230-340
208/230-3-80
VOLTAGE
RANGE
COMPRESSOR
MIN
MAX
RLA
LRA
187
253
9.9
78
187
253
OFM
FLA
0.9
IFM
FLA
208/230-3-60
414
187
506
253
5.5
12.4
40
90
20/20
30/35
45/50
60/-
-/70
18.0/18.0
31.0/33.0
44.0/48.0
57.1/63.1
25/25
35/35
45/50
60/-
-/70
./.
6
10
15
./.
3.8/5,0
7.5/10.0
11.3/15.0
15.0/19.9
-/6.0
12.0
16.0
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
9.6
17.1
24.6
32.1
15
20
25
35
20.2/20.2
33.2/35.2
46.3/50.3
59.5/65.3
72.2/80.2
25/25
40/40
50/60
60/-
1.8
-/5
10
15
20.0
./o
6.0
12.0
18.0
24.1
11.0
18.5
26.0
33.5
41.0
15
20
30
35
45
3,5
./.
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
./.
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
22.6/22.6
35.7/37.7
48.7/52.7
61,7/67.7
74.6/82,6
30/30
40/40
50/60
-/-
.
5
10
15
26
-/3.3/5.0
7,5/10.0
11,3/15,0
15.0/19.9
6,0
12.0
18.0
24.1
-/10.4/12.0
20.8/24.1
31,3/36.1
41.6/48.0
11.5
19,0
26.5
34.0
41.5
15
20
30
35
45
32.0/32.0
45.0/47.0
58.0/62.1
71.1/77.1
83.9/91.9
40/40
50/50
14.0
21.5
29.0
36.6
44.1
20
25
30
40
45
3.8
O42
460-3_60
208/230_3_0
414
187
506
253
6.7
14,1
45
105
0.8
1.5
048
460-3-50
208/230-,3-60
414
187
506
253
7.1
19.4
53
125
0.8
1.8
1.5
-/3.8/5.0
7.5/10,0
11,3/15.0
./.
3.8/5.0
7.5/10.0
11,3/15.0
15.3/15.3
28.3/30.3
41.3/45.3
54.4/60.4
1.9
0.9
FLA
-/10.4/12 .0
20.8/24,1
31.3/36.1
-/10,4/12,0
31.3/36.1
36.1/41.7
4.1
0,8
Nominal
kW*
5,2
O60
-/-
460_._-80
414
506
8.0
63
0.8
3.2
It
SINGLE POINT POWER SUPPLY
FUSE OR
CKT BKR
036
460-3-60
ELECTRIC HEAT
MCA
2.0
1.5
9.9
Data--50JS
5
10
15
20
°
6.0
12.0
18.0
24,1
MOCP
°
-/70
80/90
7o o
80/90
60/70
80/80
90/100
Table 6--Electrical
UNIT 5OJX
SIZE
O30
V-PH-HZ
VOLTAGE
RANGE
MIN
208/230-3--60
208/230_60
187
187'
MAX
253
253
COMPRESSOR
RLA
10.4
11.2
LRA
63
75
OFM
IFM
FLA
FLA
0.9
1.6
208/230-3_0
414
187
506
253
5.4
12.4
37.5
88
0.9
0.9
208/230-3-60
414
187
506
253
5.8
13.0
44
93
0.9
1.6
460_3_0
208/230_3_30
414
187
506
253
6.4
17.3
46.5
123
0.9
2,1
-/10.4/12.0
20.8/24.1
31.3/36.1
16.0/16.0
29.0/31.0
42.1/46.1
55.1/61,1
20/20
35/35
45/50
3.6
-/3.8/5.0
7.5/10.0
11.3/15.0
-/10.4/12.0
36.1/41.7
31.3/36.1
19.2119.2
32.0/34.2
45.2/49.3
58.3/64.3
25/25
35/35
50/50
1.9
-/5
10
15
46
12
18
9.6
17.1
24.6
32.1
15
20
25
35
4.1
-/3.8/5.0
7.5/10,9
11.0/15.0
15.0/20.0
-/10.4/12.0
29.8/24.1
31.0/36.1
41.6/48.0
20.5/20.5
33,5/35.5
46.6/50.6
59.6/65.6
72,5/80.5
25/25
40/40
59/60
2.9
-/5
10
15
20
-/6
12
18
24.1
10.2
17.7
25.2
32.7
40.2
15
20
30
35
46
4.1
-/3.6/5.0
7.5/10,0
11.3/15,0
15.0/20.0
410.4/12.0
20.8/24.1
31.3/36.1
41.5/48.0
21.9/21.9
34.9/36.9
47.9/51.9
60.9/67.0
73.8/81.8
30/30
40/40
50/60
45
10
15
20
-/6
12
18
24.1
10.8
18.3
25.8
33.3
40.8
-/3.8/5.9
7.5/10.0
11.3/15.0
15.9/19.9
-/5
10
15
20
-/10.4/12,0
20.6/24.1
31.3/36.1
41.6/48.0
-/6
12
18
24.1
29.2/29.2
42.3/44.3
55,2/59.4
68.3/74.3
81.2/89.2
15.4
22.9
30.4
37.9
45.4
1.4
2.0
6.2
O60
460-3_0
414
506
9.0
62
0.9
3.2
12
kW*
FUSE OR
CKT BKR
-/3.8/5.0
7.5/10.0
11.3/15.0
048
Nominal
SINGLE POINT POWER SUPPLY
MCA
042
460-3_0
ELECTRIC HEAT
FLA
036
460-:_60
Data--50JX
MOCP
60/70
60/70
60/70
80/90
70/70
80/90
15
20
30
35
45
35/35
50/50
60/60
70i80
90/90
20
25
35
40
50
fII_L_IELO
_1 _L E-
-- ,,EL
i
_
SUPPLY
--WI2I
I-
8LU
EOUIP.GNO
ACCCSSORV
USED WITH
OPTION ONLY
ELECT.EkI
US£1) WITH
N[AT[R
_I_--
- _"
BL
--I__
-!
Pmm_H'
_
[024
(042
060)
_
0601
kWP S B
30
L
lO HIR
MAXWIldE2
Ai(G
i
'___=
_
(50 Ak(P FOE 15 KI_ )
IFUI 3 /_ 5)
TO
US 0 IVT
I
_HI_
ACCESSORY
_
Iuz
MI i_
LCI
Hkl
I
30,kMPSB
_
OPTION
ON Y
_
TO
USED WIIH
_
GO AMP S 8
HTR
HEATER OPTIONS
_YEL--
19 9 KW
BLU RED
SPED
_
I •
15 K W
[CONNECT
-RED
OPTIONSN
060)
_
L
FOR
50JX030
ONLY)
VEL
W128
BLK--
BLK--
i
I_
GRN-YEL_26
GEN-YEL
i _euect
(20
--
GRN
YEL_
GRN-y[[
BLU-TRANI
K W
SHOV_,_}
MA,UAL
3 2 AMP
RESEl_
C_,.,-_
WIT BR_
_)6 GRN
q
SEE NOTE 15_
ON
NIT
F
RED
R
--
C)ll
AUTO S
_19
ORN
_W
_20
-------_18
WHT
YE_
_
_;.PPLT._
uPL.E_t
=
_
_131
pN_
W2-_y2
rlEL_
SEE
i_ _
THERMO_IAT
NOTE#2
WHI
_'130
I
VIO
_133
I--
GRA_
_21BRN---
HRI
_12o
2(V SPLICE
UNIT
COWPONENI
_70
RN
2
3
_
_
[20
BRN
5RN--
KWI_
I
BOX
ARRANGEWENT
iouI_
F_N
_SECIIOU
rl{Lo S_LIC(
_H_
_BJUST_BL(
W_*_ _NT_I_I_
ru
fUS{
O_W
OUt_
IDN (L)k
r_I _EOUEN¢[
CLOSES
T_T
OENS
r_ _tO_
,_r_ost
/
FOI IIII_
II iZ _
SOJS04_I
SDa%04_'O_O
0_I
!50JS5OOOOG(? 0
GO( 134
Fig. 12--Wiring Schematics (208/230-3-60)
13
c
_AXIMU_
SIZE
WIR[
2 AWG
_
_
--
_2
FIEL_
il
m
50-1BVIATIC
BLK
YEL--_ /
- _,.
TEL--
CApZ
YEL
OFM
_o_
[OUIP _ND
ACCESSORY
ELECT HEAT
OPTION ONLY
HEATER
5,10,15
AWG[
WAXWIR
--
OPTIDNS
_ _0 KW
_
Y[L
g_
L-L_--BE
_25
GRN
YEL_?6
GRN Y[L
GRN-YEL_
GRN
_z
--W16
YEL
#
GRN
SEE NOTE
PLI-I
UNIT
COMPONENT
ARRANGEMENT
Te_ (I _
[WEmOIZED
_D
_ILI_
DE-ENEe_Ep
COWpRES_ORDELay
F:_
_F_OS _
_
J
_W_
[ou_e
O_W_
_m
_ffs_I iF_
llW[ D[L_ ffL*_
m IM{OlI_,_L II_[_F_m=Is.[_
_( e[eL_:E_
150JS50000717
0
C00135
Fig. 13--Wiring Schematics (460-3-60)
14
EXAMPLE: Supply voltage is 460-3-60.
FLA
--
Full Load Amps
LEGEND
LRA
-- Locked Rotor Amps
MCA
-- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
RLA
-- Rated Load Amps
CKT BKR -- Circuit Breaker
C
US
AB
=452v
Average
Voltage =
(_
BC = 464 v
452 + 464 + 455
3
= 1371
3
= 457
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for muitimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. Canadian units may be
fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase tmbalance in supply voltage is greater than 2%, Use the following formula to determine
the percentage of voltage imbalance.
Determine
maximum
deviation
(AB) 457
452=5v
(BC) 464
457=7v
(AC) 457
455=2v
Maximum
deviation is 7 v.
from
average
voltage.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x 7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
% Voltage imbalance
= 100 x
AC = 455 v
,, o o
max voltage deviation from average voltage
average voltage
IMPORTAN]_ If the supply voltage phase imbalance is]
more than 2%, contact your local electric utility company/
immediately.
Fig. 1€--Electrical
©
Q---
L.--
_.__
/
C99024
Data Legend
BRN_-
----L----
o.N_
RED --
_
GRN
--
THERMOSTAT
UNIT CONTROL POWER
SPLICE BOX
AND SUBBASE
C99056
Fig. 15---Control Connections
24 V Circuit Breaker
GROUND LUG
IN SLPICEBOX)
C99070
GROUND
"L_AS- _
Fig. 17--Control
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
L2
Wiring Plate
_BLK--
L1
........
_YEL--
TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR
L3 ........
_C_-"-BLU -3-PHASE
CONNECTIONS
NOTE: Use copper wire only.
LEGEND
NEC - National Ele_rical Code
- - Field Wiring
_
Splice Conne_ions
IT WILL NOT AUTOMATICALLY RESET
DISCONNECT POWER AND INSTALL
LOCKOUT TAG PRIOR TO SERVICING
THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING
C99057
Fig. 16---Line Power Connections
C99058
Fig. 18_Transformer
15
Label
SPECIAL
PROCEDURES
1. Disconnect
FOR 208-V
the yellow primary
unit wiring
blower-motor
operation.
b. Make
speeds
lead to the transformer
sure that condensate
5. Compressors
remove
for 208-v
Refer to indoor airflow and airflow adjustments
pan and trap are filled
c. Make sure that all tools and miscellaneous
been removed.
terminal
may need to be changed
drain
with water to ensure proper drainage.
See
label (See Fig. 12).
2. Connect the yellow primary
labeled 200-v.
Indoor
OPERATION
lead from the transformer.
section.
6. Each
unit
Schrader
Schrader
PRE-START-UP
are internally
compressor
system
loose parts have
spring mounted.
holddown
Do not loosen or
bolts.
has 2 Schrader-type
port.s, one low-side
fitting located on the suction line, and one high-side
fitting located on the compressor discharge line. Be
sure that caps on the ports are tight.
Failure
serious
to observe the following
personal injury or death:
1. Follow
goggles
warnings
recognized
safety practices
when checking or servicing
2. Do not operate compressor
unit unless
secured.
result
and wear
refrigerant
in
the field. Ensure
possibility
protective
system.
the plastic caps axe in place and tight or the
or refrigerant
leakage
could occur.
or provide any electric power to
compressor
3. Do not remove
could
7. High flow valves are located on the compressor hot gas and
suction tubes. These valves can not be accessed for service in
terminal
compressor
cover
is in place
and
terminal cover until all electri-
cal sources are disconnected
and tagged.
4. Relieve and recover all refrigerant
from system before
touching
or disturbing
anything
inside terminal box if
refrigerant
leak is suspected
around compressor
5. Never attempt to repair soldered
erant system is under pressure.
connection
C99009
Fig. 19_Fan Blade Clearance
wear
protective
System
goggles
START-UP
Using the Start-Up
proceed as follows:
and
Step 1--Check
a. Shut off electrical power to unit and install lockout tag.
b. Relieve and reclaim all refrigerant from system using
both high- and low-pressure
ports.
c. Cut component connecting tubing with tubing
remove component from unit.
d. Carehiliy
unsweat
remaining
MOTORSHAFT
while refrig-
6. Do not use torch to remove any component.
contains oil and refrigerant under pressure.
To remove a component,
proceed as follows:
MOTORAND FANHUB
terminals.
tubing
sary. Oil can ignite when exposed
Checklist
supplied
for Refrigerant
Locate and repair refrigerant
at the end of this book,
Leaks
leaks and charge the unit as follows:
I. Use both high- and low-pressure
ports to relieve
pressure and reclaim remaining refrigerant.
cutter and
2. Repair
stubs when neces-
NOTE:
to torch flame.
leak following
Instal] a bi-fhiw
accepted
system
practices.
filter drier whenever
the system has been
opened for repair.
Use the Start-Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial
3. Check system
start-up:
4. Reclaim refrigerant and evacuate refrigerant
microns if no additional leaks are found.
system
5. Charge
a volumetric-
1. Remove
access panel.
2. Read and follow instructions
CAUTION,
shipped
and
on all DANGER,
INFORMATION
labels
WARNING,
attached
to,
a. Inspect
or
inspections:
for shipping
lines, loose
Step 2---Start-Up
and handling
parts, disconnected
damages
Complete
tubing connections
erant leak is detected,
Leaks section.
or liquid-soap
see following
refrigerant,
solution.
and on
low-ambient
If a refrig-
the
Adjustments
required
procedures
kit is installed).
Allow 5 minute
damage.
Check for Refrigerant
c. Inspect all field and factory-wiring
connections.
that connections
are completed and tight.
given
between
touch
e. Inspect coil fins. If damaged
carefully
straighten
4. Verify the following
refrigerant
tubing
during shipping
cycles
the compressor.
to prevent
compressor
operation as follows:
or sharp
I. Place room thermostat
SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down within 60 sec. when FAN
and handling,
switch is placed
conditions:
blade is correctly
the Pre-Start-Up
CHECKING
COOLING AND HEATING
CONTROL
OPERATION
Be sure
Pms with a fin comb.
a. Make sure that outdoor-fan
fan orifice (See Fig. 19).
in
Do not rapid-cycle
"on"
Start and check the unit for proper control
d. Ensure wires do not
sbeetmetal edges.
using
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in Cooling mode
when the outdoor temperature
is below 40 ° F (unless accessory
unit base. Detecting
oil generally indicates a refrigerant
leak. Leak-test
all refrigerant
tubing connections
using
leak detector,
R-22
to 500
such as broken
wires, etc.
b. Inspect for oil at all refrigerant
electronic
with
method.
charging cylinder or accurate scale. Refer to unit rating plate
for required
charge. Be sure to add extra refrigerant
to
compensate for internal volume of filter drier.
with, unit.
3. Make the following
unit
for leaks using an approved
positioned
2. Place SYSTEM
AUTO position.
in
in AUTO
position.
switch in COOL position and FAN switch in
Set control below room temperature. Observe
that cooling cycle shuts down when control setting is satisfied.
16
_rF
OUTDOOR COIL
INDOOR COIL
Bypass
Position
LCS
Metering
Position
LEGEND
HPS - High Pressure Switch
LCS - Loss of Charge Switch
_j_
]
Accurater e Metering Device
Arrow indicates direction of flow
C00095
Fig. 20--Typical Heat Pump Operation, Heating Mode
INDOOR COIL
Metering
Position
LCS
OUTDOOR
Bypa_
Pos_ion
LEGEND
HPS - High Pressure Switch
LCS - Loss of Charge Switch
"_
Accurate# Metering Device
]
Arrow indicates direction of flow
C00096
Fig. 21--Typical Heat Pump Operation, Cooling Mode
CHECKING
3. Place system switch in HEAT position.
Set control above
room temperature. Observe that compressor,
outdoor fan, and
indoor blower motors start. Observe that heating
down when control setting is satisfied.
REFRIGERANT
of 15 minutes
4. When using an automatic changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions. Ob-
NOTE:
before checking
Adjustment
or adjusting
of the refrigerant
control
physical
internal protector
IMPORTANT:
When evaluating
cated adjustment to the specified
power
leads to the unit must be reversed to correct rotation. When turning
backwards, scroll compressors emit elevated noise levels, and the
difference
between
may be dramatically
compressor
suction
lower than normal.
and discharge
is not required
label is attached to the outside of the service access door. If charge
level is suspect in Heating mode, reclaim all refrigerant and charge
to nameplate amount. (This information may be obtained from the
IMPORTANT: Three-phase,
scroll compressors
are direction oriented. Unit must be checked to ensure proper compressor 3-phase
power lead orientation.
If not corrected
within 5 minute, the
The 3-phase
charge.
charge
unless the unit is suspected of not having the proper R-22 charge.
The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging
serve that unit operates in Cooling mode when temperature
control is set to "call for Cooling" (below room temperature),
will shut off the compressor.
CHARGE
The refrigerant system is fully charged with R-22 refrigerant and
is tested and factory sealed. Allow system to operate a minimum
cycle shuts
and unit operates in Heating mode when temperature
is set to "call for Heating" (above room temperature).
AND ADJUSTING
data table also.)
the refrigerant charge, an indifactory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
pressures
17
Balance Point Worksheet
7O
6O
so
mg
_o
m_
,0
m_
80
:z:o_ 30
_._ 20
lO
-10
0
10
17
20
30
40
47
50
6O
OutdoorAir Temp (Deg F)
C00093 Rev 2
Fig. 22--50JX Balance Point Worksheet
REFRIGERANT
CHARGE
INDOOR
AIRFLOW
AND AIRFLOW
The amount of refrigerant charge is Listed on the unit nameplate
and/or the physical data table. Refer to the Refrigeration
Service
Techniques
Manual,
Refrigerants
¥_ [__.'luhnl[.]H
Section.
For heating and cooling operation, the recommended
is 350 to 450 cfm for each 12,000 Btuh of rated
NO CHARGE
CHARGE
4. Failure
the unit.
Tables
COOLING
external
to maintain these airflows
7 and 8 shows both heating
static
pressures.
Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until
the conditions of the chart are met. Note that charging charts are
airflow for the system
different from type normally used. Charts are based on charging
the units to correct superheat for the various operating conditions.
Accurate pressure
gauge and temperature
_nsnig
devices are
from obstructions,
NOTE:
Indoor
air CFM
must be within
the normal
CHARGING
operating
should
at various
Refer to these tables to determine
Be sure that all supply-and
For 2081230-v
follows:
3-SPEED
CHARTS
Black
Take the outdoor ambient temperature
and read the suction
pressure gauge. Refer to the chart to determine what the suction
temperature
and cooling airflows
to
the
and adjusted
return-air
grilles are open, free
properly.
by changing
the lead connection
of the
Unit 50JS and 50JX three-speed
motors (except 50JX 030) are
factory wired for low speed operation. Unit 50JX 030 is factory
wired for medium speed.
range of the unit.
TO USE COOLING
could result in damage
being installed.
Airflow can be changed
blower motor.
required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction
line and insulate it so that the outdoor ambient does not affect the
reading.
airflow
cooling
capacity. For units with optional electric heat, the airflow
must not be reduced below the levels stated in Tables 3 and
Check for leak. Use standard evacuating techniques. ARer evacuating system to 500 microns, weigh in the specified amount of
refrigerant (refer to system data plate).
LOW
ADJUSTMENTS
Motors:--
The
motor
leads
are color-coded
as
= high speed
Blue = medium speed
Red = low speed
be.
To change the speed of the indoor fan motor (IFM), remove
NOTE: If the problem
causing
the inaccurate
readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.
die fan
motor speed leg lead from the Time Delay Relay (TDR). This wire
is attacbed to TDR-3 for 3-phase units. To change the speed,
remove and replace with lead for desired blower motor speed.
ln,Tulate the removed lead to avoid contact with chassis parts.
18
Balance Point Worksheet
70
Based on Indoor Entering
Air of 70 F and Rated CFM
60
i-
ca 50
_o
o_
go
...__ 40
C
30
Im
_q:3
ca_
_E 2o
lO
-10
0
10
17
20
Outdoor
30
40
47
50
6O
Air Temp (Deg F)
C00094rev2
For 460-v
follows:
GE Motors_The
motor
leads
Fig. 23_50JS
Balance Point Worksheet
are color
as
coded
3-SPEED
The ability to properly perform
ment requires certain expertise,
Black = high
Violet = jumper
equipment.
If you do not possess these, do not
perform any maintenance
on this equipment, other
procedures recommended
in the User's Manual.
TO HEED THIS WARNING
COULD RESULT
Orange = medium
Red = low
To change
die speed
of the indoor fan motor
motor speed lead from the Time
(IFM),
remove
fan
OUS INJURY OR DEATH
THIS EQUIPMENT.
Delay Relay (TDR) and replace
with the lead for the desired blower motor speed. The motor speed
lead is attached to terminal TDR-3. For low and medium speeds,
black must be connected to the jumper wire. Insulate removed lead
end to avoid contact with chassis parts. To select high speed on
460-v GE motors, separate die black female quick connect (QC)
from the jumper
lead male quick connect
black lead to the BR. Insulate the jumper
chassis parts.
(QC) and connect
maintenance
on this equipmechanical skills, tools and
AND POSSIBLE
Failure to follow these warnings
or death:
the
attempt to
than those
FAILURE
IN SERI-
DAMAGE
TO
could result in serious injury
I. Turn off electrical power to die unit and install lockout tag
before performing any maintenance
or service on this unit.
2. Use extreme caution when removing panels and parts. As
to avoid contact with any
with any mechanical equipment, personal injury can result
from sharp edges.
3. Never place anything combustible either on, or in contact
with, the unit.
MAINTENANCE
To ensure continuing
high performance,
and to minimize
the
possibility of premature equipment failure, periodic maintenance
must be performed on tiffs equipment. This heat pump unit should
be inspected at least once each year by a qualified service person.
To troubleshoot
unit, refer to Table 11.
NOTE TO EQUIPMENT
OWNER:
about the availability of a maintenance
Consult your local dealer
contract.
ing when servicing.
The minimum
follows:
19
maintenance
requirements
for this equipment
are _.s
Table 7--Wet Coil Air Delivery
Unit 50JS 030-060 (Deduct 10 percent for 208-V)*
MOTOR
SPEED
UNIT
Low
3O
Med
High
Low
36
Med
High
Med
High
Low
48
Med
High
Low
6O
0.1
0.2
Watts
295
292
289
802
Med
0.8
0.9
1.0
I
I
Cfm
928
882
388
383
377
372
366
361
Cfm
W_ts
Cfm
1203
1120
1062
1004
930
469
1141
838
458
1027
449
924
442
828
W_ts
Cfm
592
1499
552
1281
538
1207
525
1125
512
1034
499
936
Watts
660
636
617
603
592
581
Cfm
WaRs
Cfm
1475
1371
1274
776
1452
1186
761
1356
1105
744
1254
1024
725
i
]
928
706
1145
]
1030
550
1146
537
1066
581
1421
606
1464
567
1351
596
1399
586
1341
575
1282
563
1218
I
WaRs
680
665
649
635
622
611
600
590
Cfm
1608
1535
1461
1387
1316
1247
1180
1111
Watts
Cfm
768
1656
755
1576
742
1508
730
1447
718
1396
797
1331
596
1268
684
1198
671
1119
552
1384
WaRs
741
724
709
690
664
631
594
562
Cfm
1994
1937
1869
1797
1722
1645
1566
1480
566
1
1
I
543
1269
773
744
715
667
662
640
625
Cfm
WaRs
Cfm
1957
1867
1787
799
1914
1719
782
1842
1653
773
1774
1575
1463
756
1686
704
1538
WaRs
742
723
698
666
629
591
559
540
Cfm
W_ts
2197
838
2141
822
2103
803
2057
760
1988
752
1894
721
1783
689
1674
661
Cfm
2485
2406
2269
2127
2012
1937
1894
1855
934
2483
913
2391
691
2283
666
2170
837
2061
806
1960
776
1868
689
910
i
WaRs
WaRs
Cfm
High
EXTERNAL STATIC PRESSURE (IN. WG)
0.3
0.4
0.5
0.6
0.7
WaRs
WaRs
Cfm
Low
42
0.0
[
I
639
632
1770
750
]
[
1571
735
1780
i
1687
* Air delivery values are based on operating voltage of 230_v or 460-v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate podions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10 percent for 208-v.
1. Inspect
air
filter(s)
each
month.
Clean
or
replace
Step 2--Indoor
when
necessary.
2. Inspect
indoor
coil, drain
pan,
cooling
season
for cleanliness.
and condensate
electrical
connections
proper
sary.
operation
each cooling
season.
and controls
Service
refrigerant
for
or sha_
the unit without
Always replace
Inspect
month
at least
once
each
Inspect
(See Tables
and
tag
electrical
power
Step 3--OUTDOOR
COIL, INDOOR
CONDENSATE
DRAIN PAN
a suitable air filter
the fiker with the
installed
and
to
the unit
before
cleaning and lubricating the blower motor and wheel. Failure
to adhere to this warning could cause serious injury or death.
Filter
filter(s)
efficiency,
wheel and
when neces-
tubing
same dimensional size and type a_soriginally
I and 2 for recommended
fdter sizes.)
air
to lubricate
For longer life, operating economy,
and continuing
clean accumulated
dirt and grease from the blower
each cooling
Disconnect
IMPORTANT:
Never operate
in the return-air duct system.
Do not attempt
motor annually.
for tightness
5. Ensure wires are not contacting
sheet metal edges.
Step 1--Air
for cleanliness
and motor
NOTE: All motors are prelubricated.
these motors.
each
Clean when necessary.
3. Inspect blower motor and wheel
season. Clean when necessary.
4. Check
drain
blower
the condenser
coil, evaporator
pan at least once each heating
conditions require.
replace
COIL, AND
coil, and condensate
and cooling
season
drain
or sooner
if
The coils are easily cleaned when dry; therefore, inspect and dean
the coils either before or after each cooling season. Remove all
(throwaway-type)
or clean (cleanable-type)
at lea.st twice during
each cooling season or whenever the f-alterbecomes clogged with
dust and tint.
obstructions,
including weeds and shrubs,
airflow through the condenser coil.
20
that interfere
with the
Table 8_Wet Coil Air Delivery
Unit 50JX 030-060 (Deduct 10 percent for 208-V)*
MOTOR
SPEED
UNIT
Low
3O
Med
High
Low
36
Med
High
Low
42
Med
High
Low
48
Med
High
Low
Med
60
High
Watts
Cfm
0.O
0.1
0.2
276
963
276
929
272
781
EXTERNAL STATIC PRESSURE (IN. WG)
0.3
0.4
0.5
0.6
0.7
Watts
375
377
371
362
354
350
Cfm
1202
1170
1079
976
884
807
469
1174
449
988
Wa_s
Cfm
435
828
WaHs
462
451
431
411
394
381
Cfm
1374
1290
1205
1116
1020
916
Watts
523
506
499
471
449
426
Cfm
Watts
Cfm
1500
1408
645
1474
1301
628
1369
1190
610
1267
1082
595
1169
977
584
1069
575
962
Watts
Cfm
620
1662
600
1621
586
1581
574
1540
562
1496
548
1447
530
1392
0.8
0.9
1.0
428
718
510
1331
487
462
439
1263
1186
1103
Wa_s
686
661
634
606
577
547
517
Cfm
1722
1662
1594
1515
1427
1330
1227
757
1669
730
704
682
1577
1486
1402
1331
1263
WaHs
Cfm
WaSs
620
600
586
574
562
548
530
Cfm
1662
1621
1581
1540
1496
1447
1392
487
Watts
763
747
729
709
686
661
634
606
577
547
517
Cfm
1917
1868
1822
1774
1722
1662
1594
1515
1427
1330
1227
852
1982
832
1914
809
1839
784
1757
757
1669
730
704
682
1577
1486
1402
Wa_s
Cfm
I
I
Watts
597
592
578
526
460
452
445
Cfm
2265
2190
2101
2033
1974
1869
1614
Watts
Cfm
754
2383
730
2282
707
2202
687
2134
671
2070
658
2005
646
1935
630
1858
603
558
486
1771
1667
1576
Wa_s
Cfm
901
2480
876
2383
856
2301
836
2233
813
2175
785
2122
755
2066
723
1998
696
681
687
1910
1788
1619
* Air delivery values are based on operating voltage of 230-v or 460-v, wet coil, without filter or elect nc heater. Deduct filter and electdc heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10 percent for 208-v.
Straighten
bent fins with a fin comb.
If coated
Step 4---Outdoor fan
with dirt or lint,
clean the coils with a vacuum
cleaner, using the soft brush
attachment.
Be careful not to bend the fins. If coated with oil or
grease,
clean the coils with a mild detergent-and-water
solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
result.s, spray condenser coil fins from inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush ail dirt and debris from the unit
1. Inspect
the fan blades
for cracks
2. If fan needs to be removed,
base.
intake grille and remove
3. Loosen
Inspect the drain pan and condensate
drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
the setscrew
or bends.
remove screws holding outdoor
air
grille.
and slide the fan off the motor shaft.
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring,
4. When replacing fan blade, position blade so that die hub is 1/8
in. (See Fig. 19) away from the motor end (1/8 in. of motor
shaft will be visible) .
or air filter(s).
5. Ensure
If the drain
trough
is restricted,
clear
it with
a
"plumbers snake" or similar probe device. Ensure that the auxiliary
drain port above the drain trough is also clear.
that setscrew
engages
the flat area on the motor shaft
when tightening.
6. Replace
grille.
Step f--Electrical
controls
and wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit and install lockout
tag.
2t
(030) 60HZ CHARGING
200
,
30.0
400
-1
4
SUCTION
panel
10
700
16
LIN E TEMPERATURE
Fig. 24_Cooling
access
60.0
F
SUCTION
L,NETEMPERATURE_T
-7
Remove
50.0
CHART
21
(°C)
(036) 60HZ CHARGING
C
125
52
115
46
105
41
95
35
85
29
75
24
65
18
55
13
45
7
I
30.0
40.0
50.0
60.0
SUCTION LINE TEMPERATURE I°Fq
] ......
J
I
I
-7
-1
4
10
16
80.0
20.0
r
27
50JS500089
SUCTION LINE TEMPERATURE
C00028
Fig. 25_Cooling
Charging Chart, 50JSO30
to locate
all the electrical
controls
CHART
Step 8--Metering
and
70.0
B0.0
21
I
27
(_C)
50JS500090
Charging Chart, 50JS 036 uncial
_ 29
device
wiring. Check all electrical connections
for tightness. Tighten all
screw connections.
If any smoky or burned connections
are
Refrigerant metering devices are fixed orifices and are located in
the inlet header to the indoor and outdoor coils.
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
Step 9_Liquid
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at lea_st one complete cooling
label when making
NOTE: Refer to the Sequence of Operation
determining proper control operation.
Step
6---Rsfrigerant
Step 10_High
as an aid in
circuit
thermostat
is satisfied.
This delay enables
residual cooling in coil after compression
leak-test
sec., fan relay is energized.
all
leaks are found and low performance
and Adjusting
Step 7--1ndoor
airflow
The indoor
performance
airflow does
is suspected.
Refrigerant
Charge
When
thermostat
is satisfied,
an off
during this delay, TDR is reset and fan relay remains energized.
TDR is a 24-v device that operates within a range of 15-v to 30-v
and draws about 0.5 amps. If the blower runs continuously
instead
of cycling off when the fan switch is set on AUTO, the TDR is
probably defective and must be replaced.
Leaks section.
refer to Checking
blower to remove
shutdown,
thereby
delay is initiated. When fixed delay of 60_+5 sec. is completed, fan
relay is de-energized
and fan motor stops. If wall thermostat closes
refrigerant tubing using an electronic leak detector, or liquid-soap
solution. If a refrigerant
leak is detected,
refer to Check for
If no refrigerant
control, recycle
for 60 sec. after
improving efficiency of system. The sequence of operation is that
on closure of wall thermostat and at end of a fixed on delay of 1
serious injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.
is suspected,
hot gas and
these valves
relay
The Time-Delay
Relay (TDR) is a solid-state
delay timer which keeps indoor blower operating
System under pressure.
Relieve pressure and recover all
refrigerant before system repair or final unit disposal to avoid
Refrigerant
Flow Valves
Step 11--Time-delay
YT_'_L3,zP211] _
or if low performance
are made of
with O-rings located inside the caps. These valves can not be
accessed for service in the field. Ensure the plastic caps are in
place and tight or the possibility of refrigerant leakage could occur.
Inspect all refrigerant tubing connections and the unit base for oil
accumulation
annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected
devices)
High flow valves are located on the compressor
suction tubes. Large black plastic caps distinguish
these checkouts.
section
(to protect metering
wire mesh and are located in the liquid lines on the inlet side of the
metering devices.
cycle to ensure proper operation. If discrepancies
are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical instrumentation. Refer to the unit wiring
line strainers
The liquid line strainers
is suspected,
section.
Step 12--4.oss
of charge
switch
The loss of charge switch is located on the outdoor liquid line. This
switch contains a Schrader core depressor.
psig and closes at 22 psig. No adjustment
not require checking unless improper
If a problem
exists, be sure that all
This switch opens at 7
is necessary.
supply- and return-air grilles are open and free from obstructior_;,
and that the air filter is clean. When necessary, refer to Indoor
NOTE: Because
these switches
are attached
to refrigeration
system under pressure, it is not advisable to remove this device for
Airflow
airflow.
troubleshooting
unless you are re;_onably
exists. If switch must be removed, remove
and Airflow
AdjustmenL_
section
to check
the system
22
certain that a problem
and recover all system
(042.) 60HZ CHARGING
CHART
(048) 60HZ CHARGING
CHART
,4Jq
6891 100
125
115
52
46
I
105
41
I
J.
-4.._
95 35 I
8s 29 I
7s 241
65
18 I
55
131
45
71
i i
i i
i
: I I
i I I
I
I
lU)
I
I !
[
I!111
i
3°° ,oo
SUCTION
-7
LiNE TEMPERATURE
-1
SUCTION
Fig. 26--Cooling
4
10
16
LINE TEMPERATURE (°C)
Charging
Chart,
20.0
r
(°F_
21
I
_7
27
50JS50009
300
I
I
I
I
I
:
I
400
500
61_0
SUCTION LIN E TEMPERATURE !_F)
!
I
I
I
-1
4
10
16
SUCTION
Fig. 27--Cooling
50JS 042 unC_l_
°3°
I
I
Illil
207!
,o.o 8o.0 i
I
LINE TEMPERATU
RE
70.o
so.o
J
i
!
21
(°C)
i
27
i
I
50JS5000921
Charging Chad, 50JS 048 Un_=_31
(D60) 60HZ CHARGING CHART
20.0
I
7
30.0
400
SUC_ONL_ETEMPERATURE°_(
I
I
I
1
4
10
Fig. 28--Cooling
charge so that pressure gauges read 0 psi. Never
without breaking vacuum with dry nitrogen.
Step 13_Check
defrost
open system
NOTE: The defrost thermostat must be located on the liquid side
of the outdoor coil on the bottom circuit and as close to the coil as
possible.
is a 3/8-in. OD stub tube approximately
3 in. long (See Fig. 35).
The defrost thermostat should be located on this stub tube. Note
TROUBLESHOOTING
and on most
Refer to the Cooling and Heating Troubleshooting
11 ) for troubleshooting
information.
are right for
Use the Start-Up Checklist
followed.
Thermostat
Defrost
thermostat
defrost
or that conditions
START-UP
signals heat pump that conditions
have changed
I
27
a thermally actuated switch clamped to outdoor coil to sense its
temperature.
Normal temperature
range is closed at 30 ° +/- 3°F
and open at 80 ° +/- 5°F.
There is a liquid header with a brass distributor and feeder tube
going into outdoor coil. At the end of I of the feeder tubes, there
Step 14--Defrost
J
21
_ 32
Charging Chart, 50JS 060 UnCi_=
thermostat
that there is only 1 stub tube used with liquid header,
units it is the bottom circuit.
80.0
!
16
to terminate
defrost. It is
23
Chart (Table
CHECKLIST
to ensure proper start-up procedures
are
Fig. 29_Cooling
Fig. 30_Cooling
Charging
Charging Chart, 50JX 030 Un_tl_32
Chart, 50JX 036 Un_
33
c
s_
II......_)_=_=_=_
=
ill
, I
4
i
io
_ ............
;
*_
_x_o_23
C99035
Fig, 32--Cooling
Charging
Chart, 50JX
C99036
048 Units
Fig. 33_Cooling
24
Charging
Chart, 50JX 060 Units
Table 9---FILTER PRESSURE DROP (In. wg)
FILTER
SIZE
20X20X1
1300
CFM
1400
1500
0.13
0.14
0.15
0.16
0,07
0.08
0,09
0,10
500
600
700
800
900
1000
1100
1200
0.05
0.07
0.08
0.10
0.12
0.13
0,14
0.15
0.09
0.10
0.11
20 X 24 X 1
24 X 30 X 1
Table 10_ELECTRIC
1600
1700
1800
1900
2000
2100
2200
2300
0,11
0.12
0,13
0.14
0.15
0.16
0,17
0,18
HEAT PRESSURE DROP TABLE
Small Cabinet
STATIC
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
5 kW
0.O0
0.O0
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
10 kW
0,00
0.00
0,00
0,00
0,00
0.02
0,04
0,06
0.07
0.09
0.10
0.11
15 kW
0,00
0.00
0,00
0.02
0,04
0,06
0.08
0,10
0.12
0,14
0.16
0,18
20 kW
0.00
0.00
0.02
0.04
0,06
0,08
0,09
0,11
0,13
0.15
0.17
0.10
I
I
Large Cabinet
STATIC
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
5 kW
0.00
0.00
0.0O
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.09
0.09
0.10
0.11
0,12
10 kW
0.00
0,00
0.01
0,02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
15 kW
0.00
0.02
0.03
0,04
0,05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
20 kW
0.02
0,03
0.04
0,05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
DEFROST
THERMOSTAT
Fig. 35---Defrost Thermostat
Fig. 34_Refrigerant
Circuit
C99097
25
C99092
Table 11--Cooling and Heating Troubleshooting Chart
CAUSE
SYMPTOM
Compressor and outdoor
fan will not start
Compressor
will not start
but condenser
fan runs
Three-phase scroll compressor (size 030060 units) makes excessive noise, and
there may be a low pressure differential
Call power company
Fuse blown or circuit breaker tripped
Defective thermostat, contractor, transformer,
control relay or detrost board
Replace fuse or reset circuit breaker
Insufficient line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
Thermostat setting too high
Lower thermostat setting below room
temperature
Units have a 5-minute time delay
DO NOT bypass this compressor time
delay-waft for 5 minute until time,delay relay is
de-energized
Faulty wiring or loose connections in compressor
circuit
Check wiring and repair or replace
Compressor motor burned out, seized, or
internal overload open
Determine cause.
Replace compressor
Defective run capacitor, overfoad, or PTC
(positive temperature coefficient) thermistor
Determine cause and replace
Defective run capacitor, overload, or PTC (positive temperature coefficient) thermistor
Determine
One leg of 3-phase power dead
Replace f,Jse or reset
Determine
cause
Scrst] compressor is rotating in the wrong
direction
Correct the direction of rotation by reversing the
3-phase power leads to the unit
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and
recharge to capacities shown on nameplate
Dateetive compressor
Determine
Defective run/start capacitor, ovedoad or start
relay
Defective thermostat
Faulty outdoor-fan
motor or capacitor
and
correct
Determine cause and replace
Replace thermostat
Replace
Replace filter
Thermostat set too low
Reset thermostat
Low refrigerant charge
Locate leak, repair, and recharge
Replace compressor
Decrease load or increase unit size
Check defrost time settings
Reset
as
necessary
Check defrost temperature switch
Replace as necessary
Recover refrigerant, evacuate system,
and recharge
Clean coil or remove restdcgon
Dirty air tiger
low
cause
Locate restriction and remove
Outdoor coil didy or restricted
too
circuit breaker
Dirty air filter
Unit undersized for load
Air in system
pressure
replace
Determine cause and correct
Frosted coil with incorrect defrost operation
Head
and
Restriction in refggerant system
operates continuously
Excessive head pressure
cause
Damaged reversing valve
Leaking valves in compressor
Compressor
Replace component
Replace and determine cause
Determine cause and correct
Insufficient line voltage
Blocked outdoor coft
Compressor cycles
(other than normally satisfying thermostat)
REMEDY
Power Failure
Dirty indoor or outdoor coil
Replace filter
Clean coil
Refrigerant overcharged
Recover excess refrigerant
Air in system
Recover refrigerant, evacuate system,
and recharge
(Heat) Indoor air restricte_ or recirculating
Determine cause and correct
indoor or outdoor air restdcted or air short_ycling
Determine cause and correct
Low refrigerant charge
Check for leaks, repair and recharge
Compressor valves leaking
Restriction in liquid tube
Replace compressor
Remove restriction
(Heat) Outdoor coft frosted
Move timer on control board to 30 minute between
defrost cycles
Check for source and eliminate
Excessive
suction
pressure
Compressor valves leaking
Replace compressor
Reversing valve hung up or leaking intemafty
Replace valve
Recover excess refrigerant
(Continued
next
page)
26
Table 11--Cooling and Heating Troubleshooting Chart (Cont'd)
SYMPTOM
CAUSE
REMEDY
(Cool) Dirty air filter
RepIace filter
(Heat) Outdoor coil frosted
Move timer on control board to 30 minute
between defrost cycles
Low refrigerant charge
Check for leaks, repair and reCharge
Remove source of restriction
Metering device or low side restricted
Suction pressure too low
Increase air quantity
Check filter-replace if necessary
Beset thermostat
(Cool) Insufficient coil airflow
(Cool) Temperature too low in conditioned area
Compressor runs but outdoor fan does not
IFM* does not run
IFM* runs when it should be off
IFM* operaSon is intermittent
* IFM4ndoor
(Cool) Outdoor ambient below 40 ° F
Field-installed filter-drier restricted
Install Iow-_.mbient kit
NC (normally closed) contacts on defrost beard
open
Check condition of relay on board
Replace if necessary
Blower wheel not secured to shaft
insufficient voltage at motor
Properly tighten blower wheel to shaft
I_etermine
cause
and correst
RepLace
Power connectors not properly sea{ed
Connectors should snap easily; do not force
Motor programmed with a delay profile
Allow a few minute for motor 1o shut off
With thermostat in off state, the voltage on G,
Y1 ,Y, Y2, W with respect to common, should be
1/2 of actual low voltage supply
It measured voltage is more than 1/2, the
thermostat is incompatible with motor
If voltage is less than 1/2, the motor has failed
Water ddpping into motor
Verify proper drip loops in connector wires
Connectors not firmly sealed
Gently pull wires individually to be sure they are
crimped into the housing
Fan Motor
Start-up checklist
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY
INFORMATION
Model No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date
.....................................................................................................................................................................
Technician
...........................................................................................................................................................
Job Location ...........................................................................................................................................................
II. PRE-START-UP
__
Verify
--
Remove
that an packing
--
Verify
all shipping
materials
holddown
that condensate
__
Check
all electrical
--
Check
that indoor
--
Verify
--
Check
connection
connections
propeller
and brackets
is installed
from
unit
per installation
per installation
and terminals
(evaporator)
that unit installation
fan wheel
have been removed
bolts
instructions
instructions
for tightness
air filter is clean
and in place
is level
for location
in housing
and setscrew
tightness
Ul, START-UP
Supply Voltage:
Compressor
Indoor
L1-L2 --
Amps:
L2-L3 --
L1
L3-L1
L2
L3
Fan Amps:
TEMPERATURE
Outdoor-Air
Return-Air
Heat Pump
Electric
PRESSURES
Temperature:
Temperature:
__
DB
--
DE}
WR
Supply Air:
Heater
Supply Air:
Refrigerant
Suction
Refdgerant
Discharge
psig
psig
--
Verify Refrigerant charge using charging tables
--
Verify that 3-phase scroll compressor is rotating in correct direction
37
Copyright 2006 CARRIER Corp. • 7310 W. Morris St. • Indianapolis,
IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications
Book 1 4
Tab 6 8
PC 101
Printed in U.S.A.
Catalog No. 50JS,JX-6Sl
or designs without notice and without incurring obligations.
Pg 26
2-0_
Replaces:
New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 28 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:16:22 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools