CARRIER Package Units(both Units Combined) Manual L0604564
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 28
Download | |
Open PDF In Browser | View PDF |
HEATING & COOLING 3-Phase Visit Single-Packaged 50JS, 50JX Heat Pumps www.carrier.com Installation, Start-Up, and Service Instructions NOTE: Read installation. the entire instrdction TABLE SAFETY RECEIVING before starting the OF CONTENTS CONSIDERATIONS INTRODUCTION manual ..................................................... 1 .......................................................................... AND INSTALLATION 2 .......................................... 2 Check Equipment ...................................................................... IDENTIFY UNIT ................................................................ INSPECT SIMPMENT 2 2 ........................................................ 2 Provide Unit Support ................................................................ ROOF CURB ....................................................................... SLAB MOUNT ................................................................... 2 2 2 GROUND MOUNT ............................................................ Provide Clearances .................................................................... 2 2 Rig and Place Unit .................................................................... INSPECTION ...................................................................... 2 2 INSTALLATION ................................................................ Select and Install Ductwork ..................................................... 2 4 CONVERTING DOWNFLOW HORIZONTAL (VERTICAL) DISCHARGE DISCHARGE UNITS TO UNITS ......... 5 Provide for Condensate Disposal ............................................. Install Electrical Connections ................................................... HIGH-VOLTAGE CONNECTIONS ................................ ROUTING POWER LEADS INTO UNIT ...................... CONNECTING GROUND LEAD TO GROUND C99001 7 8 Fig. 1--Model 50JS/50JX I0 10 LUG.10 ROUTING CONTROL POWER WIRES (24-V) ............ 13 SPECIAL PROCEDURES FOR 208-V OPERATION ...15 PRE-START-UP START-UP .......................................................................... 17 ................................................................................... Check for Refrigerant Leaks .................................................. Start-Up Adjustments .............................................................. CHECKING COOLING AND HEATING CONTROL OPERATION ................................................. CHECKING AND ADJUSTING TROUBLESHOOTING START-UP 17 REFRIGERANT NOTE 18 19 MAINTENANCE ......................................................................... Air Filter .................................................................................. 25 -- READ THESE INSTRUCTIONS before installing this unit. and Service Instructions are SAFETY CONSIDERATIONS Installation 20 21 hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service air-conditioning equipment. 21 CONDENSATE DRAIN PAN ............................................... Outdoor fan ............................................................................. 22 23 Electrical controls and wiring ................................................ Refrigerant circuit ................................................................... Indoor airflow ......................................................................... 23 24 25 Metering device ...................................................................... 25 line strainers ................................................................ 25 and servicing of air-conditioning equipmem can be Untrained personnel can perform ba._ic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, attached to the unit, and other safety precautions tags, and labels that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations. Manufacturer reserves the right to discontinue, or change at any time, specifications Printed in U.S.A. 25 ............................................................ I9 Indoor blower and motor ........................................................ OUTDOOR COIL, INDOOR COIL, AND PC 101 TO INSTALLER ............................................................... CAREFULLY AND COMPLETELY Also, make sure the Owner's Manual CHARTS .................. 19 AIRFLOW ADJUST- .............................................................................. CHECKLIST left with the unit after installation. NO CHARGE .................................................................... LOW CHARGE COOLING ............................................. Liquid 25 25 25 25 17 17 18 18 MENTS 25 Time-delay relay ..................................................................... Loss of charge switch ............................................................. Check defrost thermostat ........................................................ Defrost Thermostat ................................................................. 17 CHARGE ........................................................................... REFRIGERANT CHARGE .............................................. TO USE COOLING CHARGING INDOOR AIRFLOW AND High Flow Valves ................................................................... Catalog No. 50JS,JX-6SI or designs without notice and without incurring obligations, Pg 1 2-06 Replaces: New IMPORTANT: Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electric shock, or Curb should be level to within 1/4 in. (See Fig. 6). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information a-s service agency for information or assistance. The qualified installer or agency must use only factory-authorized kits or when modifying of the unit to the roof curb is critical and poor unit performance. other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or accessories The gasketing for a watertight seal. Install gaskeling material supplied with the roof curb. Improperly applied gasketing also can result in air leaks required. this product. SLAB MOUNT Recognize safety information. This is the safety-aler_ symbolAx. When you see this symbol on the product or in instructions or manuals, be alert to the potential for personal Place the unit on a solid, level concrete 4 in. thick with 2 in. above injury. pad that is a minimum of grade (See Fig. 7). The slab should Understand the signal words -- DANGER, WARNING, CAUTION, and NOTE. Danger identifies the most serious hazards, extend approximately 2 in. beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab except when required by local codes. which will result in severe personal injury or death. indicates a condition that could cause serious personal GROUND Warning injury or The unit may be installed death. Caution is used to identify unsafe practices, which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which enhanced installation, reliability, or operation. result in 1. The power supply (volts, phase, and hertz) must correspond that specified on unit rating plate. to 2. The electrical to handle supply provided load imposed will either on a slab or placed directly on the ground if local codes permit. Place the unit prepared with gravel for condensate discharge. on level The required minimum service clearances are shown in Figs. 2 and 3. Adequate ventilation and ouUloor air must be provided. The by die utility must be sufficient outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance by this unit. or waste water codes and other applicable and and under a partial overhang (such as a normal house overhang) in. above the unit top. The maximum horizontal extension local partial overhang must not exceed 48 in. For extended provide a minimum clearance of 48 in. IMPORTANT: Do not restrict at either the outdoor-air detrimental to compressor severe ground Step 3---Provide Clearances 3. This installation must confurm with local building codes with NEC (National Electrical Code). Refer to provincial local plumbing codes. MOUNT inJUry or death. outdoor inlet life. or airflow. die fan is 36 of a overhangs, An air restriction discharge may be Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units INTRODUCTION The 50JS and 50JX heat pumps are fully self-contained and designed for outdoor installation (See Fig. 1). Standard units are should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water. shipped in a horizontal-discharge configuration for installation on a ground-level slab, Units can be converted to downflow (vertical) Step 4--Rig discharge configurations for rooftop applications. Rigging and handling of this equipment reasons due to the installation location etc.) RECEIVING AND INSTALLATION Step 1--Check Equipment IDENTIFY identification pers. INSPECT plate. and serial number are stamped Check this information against on the unit shipping When pa- SHIPMENT it examined by transportation working with this equipment, observe support precautions staff in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply. Follow gloves. Inspect for shipping damage while unit is still on shipping pallet. If ualt appears to be damaged or is torn loose from its anchorage, have can be hazardous for many (roofs, elevated structures, Only trained, qualified crane operators and ground should handle and install this equipment. UNIT The unit model number and Place Unit inspectors before all applicable safety codes. Wear safety shoes and work INSPECTION removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the Prior to initial use, and at monthly nearest Carder Air Conditioning office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation. should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded. Step 2--Provide INSTALLATION Unit Support ROOF CURB Install accessory intervals, all rigging brackets and straps should be visually inspected for any damage, of wear, structural deformation, or cracks, particular evidence attention 1. Remove unit from shipping carton. Leave top shipping skid on roof curb in accordance with instructions with curb (See Fig. 5). Install insulation, cant strips, flashing. Ductwork must be attached to curb. shipped roofing, the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood skid is not available, use a spreader bar of sufficient length to protect unit from damage. and 2 /_[V_P0eAT0e C01t _lllllllllllllllllll_ HIIIIIIIIIIIII!lllml_ I t FEG_J_) a_-iilLll/iC_S Ti_ C{Ji_'I]HUE M_., U TOP VIEW W._'ia- , t3 ,s_ _ WILLIWETER$ {IN) 355¸6 {14.00} 50 8 [2 00} _55.6 (1_ 00} 121 {0.50) _14 4 [3_ 001 FOP OF UNIT ................................... DU¢1 S_O[ OF UNIT ............................. _ID[ OPPOSIT[ OUCTS............................ BOTTOll OF _iHI1 ............................... ELECTRIC H_AT PANEL .......................... iUPPL_ _UCT OPEW_WG, _O? [_5 8_1 _ . DL_T OpEwiWG REAR VIEW ROR _l_fl /€_ _ MILLtM[TER_ { INI 9_4.0 [3_ 001 9_4 0 [3_ 001 [VAp COIL ACC[$$ $1D[ ..................... P_[_ [HIR_ $rD[ .......................... ([ICEPT FOR HEC R[OUIREWEWTS} uHrT TOp ............................. SID[ OPPO_IT[ DLiCIS ...................... _U_T PAN[L .......................................... 914.0 _;4.0 304¸8 [3_ 001 {3_.001 [1_.00]_ CLF.AdUdiC_ BETWEEH UNITS, POI[R [#TRf SI{)[ ....................... UHIT kWD UN_ROUNO[_ SURF_C[$, pO,ie[R [NIRY SlOE .... UWIT _WD BLOCK Oe _Oe_:R[TE WALL_ AHD OI_ER GROUNDEDSURFAC_S, POi[R[RTR_51D[ .............. W_LLIW[T[RS [IN] _065 8 [_ 00) 91_ 0 {35 00] _066.814_.00] ,_IHIHUW DIMENSIONS DISTAHC[S:_F _HIT IS PLACID LESS THAH _Od8 [1_ 0_1 FR{_,dWALL $_STEW,TH[N S_ST[W PERFORWAHC[ WkYBE ¢_PROWIS[D. [N [] IN ARE INCHES t ,I,Ll l!llllll . • I , , i . t IL_3]_ RIGHT SIDE VIEW FRONT VIEW C00137 UNIT ELECTRICAL CHARACTERISTICS 50JS03O 208/230-3-60 UNIT WEIGHT Ib kg UNiT HEIGHT IN. (MM) "A" 287 130.2 39.02 (991.1) X CENTER OF GRAVITY IN.(MM) Y Z 50JS036 208/230-3-60, 460-3-60 291 132.0 37.02 (940.3) 19.5 (495.3) 19.5 (495.3) 208/230-3-60, 460-3-60 323 146.5 37.02 (940.3) 19.7 (500.4) 13.7 (348.0) 14.0 (355.6) 13,0(330.2) 50JS042 50JXO30 37.02 (940.3) 37.02 (940.3) 14.0 (355.6) 208/230-3-60, 145.2 148.8 19,7 (500.4) 50JX036 320 328 19.7 (500.4) 14.0 (355.6) 17.6 (447.0) 16.5 (419.1) 263/230-3-60 460-3-66 Fig. 2--50JS030-O42/50JX030-036 2. Position the lifting bracket assembly around the ba._e of the unit. Be sure the strap does not twist. 3. Place each of the 4 metal tiffing brackets in the composite a. Open lever of tension buckle (ratchet type). c. Pull strapping through perimeter of buckle as shown in Fig. 8. tension buckle 5. Tighten the tension buckle until it is taut. Lifting brackets 7. Attach the 2 safety strops directly to the clevis or hook at the 4 rigging brackets. DO NOT attach the safety straps to the tiffing brackets (See Fig. 8). bottom tension Unit Dimensions 6. Attach field-supptied clevis or hook of sufficient hole in the tiffing bracket (See Fig. 8). around through 13.0 (330.2) into the rigging holds strapping b. Feed strapping 15.0 (381 .o) must be secure in the rigging holds. pan. 4. Thread lifting bracket unit as follows: 13,7 (348.0) unit taut. d. Snap lever down to lock strap in tension buckle. To release strapping, squeeze safety latch, lift lever, and pull webbing outward. 8. Position lifting point directly over the unit's strength to center of gravity. 9. Lift unit. When unit is directly over the roof curb, remove the 2 safety straps. Lower the equipment onto the roof curb. Step S--Select and Install Ductwork The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of JllllllllJllllllll lll!lllllllllllllII _UPPL_ " , . 402 [15 _3] rm[NlUG I I --34_3 / FdmLIFS) CLF.ARANC_$ TO _ TOP VIEW MEC. REGUFa) I _ REAR VIEW IM_TL FIEaLIR_D _ MELLIM[T[RS [[g] 35S.6 [14 00] S08 [Z 00] 355 6 [14 00] I_ 7 [0 S01 914¸4 (3_C0] TOP OF UNIT ........................................ DUCT $1D[ OF UNIT ................................... SIO_ OPPOSIIE DUCTS ......................... 80TIll Or • ELECTRIC _[k7 PkNEL ........................ NETUNN FOR _'noN _ MILLIMETERS {IN] 9140 [36001 914_ [360_} EVAP. COIL ACC[S$ SlOE ............................ POiE_ [NTEY SID[ ................................. I[X_PI FOR gEC REOUIR[_[NTS} SI_E OPFOSIT£ DUCIS _ll_T pkNEL ....................... ................. 914¸0 304¸8 [3600] [1_00]* C_JOUNCEI BETWE[N UNITS, POM[R [RTR? SII)[ ................ Ugll kND IINGROUND[D SUBFkC[S. POiER [NTRy SJ[JE UNII kND BL_ OR CO_RETE WkLLS kND OTN[R 61tOUNOED $UItFkC[S. pOW[It ENTRY SI_[ ............... MILLIMETERS {IK] J066.8 [42 00] 914.0 [3G 01_] ........ 10668 [_2 IMIRIMUW 00] DISIANC[_IF DIM[NSIONS [41 IN [] UNI[ I_ PLAC[O LESS fNkN 304 8 [12 00] FBO_ WALL SY$1EM.IN[N $_$T[N p[R_OENkNC[ N_O[ _OgPgOMIS[O. A_E IW INC_[S 00) / ittttttft ttl t, i ililllllliillllltti tttttttlt{ttt{l. Jllllltllllllllllh IIjIIIIIIIIII IlU PONE_ E_IN_ ,!llllll!l, llllltlill 184 6 ' =i=, _' i_--_ lilt I LEFT SIDE UNIT _ "i" .i' • =_ _ii_, VIEW 5o [4 81] ,_ ........... ELECTRICAL CHARACTERISTICS FRONT VIEW UNIT WEIGHT RIGHT SIDE VIEW UNIT HEIGHT IN. (MM) Ib kg 5_S_8 208/230-3-60, 460-3-60 353 160.1 "A" 5_S_0 208/230-3-60, 460-3-60 418 189.6 5_X_2 5_X_8 208/230-3-60, 460-3-60 350 158.8 40.98 208/230-3-60, 468-3-60 315 170.1 40.98 5_X_0 208/230-3-60,460-3-60 428 194.1 42.98 38.96 38.98 Fig. 3---50JS048-060/50JX042-060 4 X C00136 CEWrER OF GRAVITY IN. (MM) Y z (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) (990.2) 19.9 (505,5) 19.9 (505.6) 15.7 (398.8) 15.7 (398.8) 17.0 (431.8) (1040.9) (1040.9) 19.9 (505.5) 15.7 (398.8) 16.6 (421.6) 18.0 (457.2) (1091.7) 19.9 (505.5) 15.7 (398.6) 17.6 (447,0) Unit Dimensions 1 2 Y 4 3 X G00071 CORNER WEIGHTS (SMALL CABINET) Unit 30 36 O) o tt_ o O 287 291 323 Corner Weight 1 66 67 83 Corner Weight 2 54 55 55 Corner Weight 3 Corner Weight 4 62 105 63 106 78 107 x U3 13 0 42 Total Weight CORNER WEIGHTS (SMALL CABINET) Unit 30 36 320 328 -- Corner Weight 1 Corner Weight 2 63 74 64 76 --- Corner Weight 3 56 58 -- Corner Weight 4 127 130 -- Fig. 4_Corner Select and size ductwork, supply-air o 0 X o o "D o -- When designing For vertical and installing ductwork, consider 90 Corner Weight 2 Corner Weight 3 49 96 58 114 Corner Weight 4 132 156 60 Total Weight 350 375 428 Corner Weight 1 75 81 92 Corner Weight 2 Corner Weight 3 49 95 52 102 60 116 Corner Weight 4 131 140 160 unit to prevent Use flexible transmission ensure weather tight installed, use fireproof and return air grilles and return-air 418 76 IMPORTANT: connectors of vibration. between ductwork Use suitable and gaskets to and airtight seal. When electric heat is canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations. The unit has duct flanges on the supplythe side of the unit. 353 Weights (in Pounds) and ventilating systems, NFPA 90B and/or local codes and registers, Total Weight Corner Weight 1 CORNER WEIGHTS (LARGE CABINET) Unit 42 48 -- Total Weight non-residence type air conditioning 90A or residence type, NFPA ordinances. CORNER WEIGHTS (LARGE CABINET) Unit 48 60 resistant duct connector (or sheet metal sleeve) from electric heater element. openings on 3. Size ductwork die following: for cooling air quantity must extend 24-in. (cfm). The minimum air quantity for proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended. supply and return units, tools or parts could drop 4. Seal, insulate, and weatherproof all external ductwork. Seal, into ductwork and cause serious injury or death. Install a 90 degree turn in the return ductwork between the unit and the insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential hearing and air space. Units with electric supply duct. conditioning heaters require 90 degree elbow in 5. Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to I. All units should have field-supplied filters or accessory falter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Tables 1 and 2. 2. Avoid change abrupt duct size increases and reductions. in duct size adversely affects air performance. systems. good construction Abrupt 5 practices. VACunit / ou .a. Rashing field • Wood nailer* I_:11 _¢ Insulation (field field supplied -- -Duct work Cant strip field supplied field supplied Roof Curb for Small Cabinet Roof Note A:When unit mounting screw is used retainer bracket must also be used. Curb for Large Cabinet Note A:When unit mounting screw is used retainer bracket must also be used. SUpp opening IBx_ \/ /\ \ R/A \ Insulated deck pan S/A _-Gasket around duct Gasket around outer edge _ Long Returnopemng (exc) C00076 UNIT SIZE 50JS030-042 50JS048-060 50JX030-036 50JX042-060 ODS CATALOG NUMBER A B IN.(MM) C D IN. (MM) IN. (MM) CPRFCURBO06AO0 6 (203) 11(279) 151/2 (419) 28-3/4 IN. (MM) CPRFCURBOO7AO0 14 (356) 11(279) 161/2 (419) 28-3/4 CPRFCURB008AO0 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (730) (730) (1022) CPRFCURB069A00 14 (356) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) NOTES: 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied, as required, to unit being installed. 3. Dimensions in ( ) are in millimeters. 4. Roof curb is made of 16-gauge steel. 5. Table lists only the dimensions, per pad number, that have changed. 6. Attach ductworb to curb (flanges of duct rest on curb). 7. Insulated panels: 1-in. thick fiberglass 1 Ib density. 8. Dimensions are in inches. 9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl. Fig. 5_Roof Curb Dimensions 6 MAXIMUM ALLOWABLE DIFFERENCE(in.) B A-B 1/4 A-c 1'4 C99065 Fig. 6--Unit Leveling Tolerances COND. COrL EVAR COIL C99096 Fig. 7--Slab Mounting Detail CONVERTING DOWNFLOW HORIZONTAL (VERTICAL) DISCHARGE DISCHARGE UNITS TO The units dispose of condensate through a 3/4 in. NPT female fitting that exits on the compressor end of the unit. Condensate UNITS water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installa- M_ Before performing service system, turn off main power or maintenance operations to unit and install lockout Turn off accessory heater power switch if applicable. trical shock could cause serious injury or death. 1. Open all electrical disconnects starting any service work. and install lockout 2. Remove side duct covers to access bottom knock outs. NOTE: These panels electrical knockout. are held in place return with water. When using a gravel apron, make sure it slopes away from the unit. and supply If the installation requires draining from the unit, install a field-supplied 4. Ensure the side duct covers horizontal air openings. to block Avoid abrupt duct size increases in duct size adversely Step 6--Provide affects for Condensate and reductions. as an accessory or is field-supplied. Make sure that the outlet of the trap is at learnt I in. lower than the unit drain-pan condensate in the connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field-supplied 3/4 -in. PVC or field-supplied 3/4 -in. copper pipe at outlet end of the 2 -in. trap (See Fig. 11). Do not undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. every l0 ft. of horizontal run. off the Abrupt Be sure to check the drain trough for leaks. Prime the trap at the beginning Disposal methods trap is available to an air performance. NOTE: Ensure that condensate-water disposal with local codes, restrictions, and practices. the condensate water away 2-in. trap at the condensate connection to ensure proper drainage. Condensate the panels change the trap is at lea_st 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap tag before 3. U_ a ,screwdriver and hammer to remove bottom of the composite unit base. NOTE: tag. Elec- with tabs similar are in place tions. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of on comply 7 of the cooling season start-up. Table 1--Physical 50JS03O UNIT SIZE Data 50JS036 50JS042 50JS048 5OJS060 NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) COMPRESSOR QUANTITY TYPE 287 291 323 353 418 1 RECIPROCATING COMPRESSOR SCROLL REFRIGERANT REFRIGERANT COMPRESSOR R-22 METERING DEVICE Refrigerant (R-22) Quantity (lb.) ORIFICE ID (in.) ORIFICE OD (in.) OUTDOOR COIL Rows... Fins/in. Face Area (sq, ft.) OUTDOOR FAN Nominal Airflow (CFM) Diameter Motor HP (RPM) INDOOR COIL Rows... Fins/in. Face Area (sq. ft,) INDOOR BLOWER Nominal Airflow (CFM) Size (in.) Motor HP (RPM) AccuRater_ 5.6 7.6 8.0 7,85 9.3 0.068 0.078 0.078 0.088 0.093 0.046 (2) 0.052 (2) 1...17 12.0 2,,.17 10.3 2.,.17 10.3 2...17 11.6 2...17 11.6 2400 22 2800 22 3300 22 3300 22 1/8 (825) 1/4 (1100) 2400 22 1/8 (825) 1/4 (1100) 1/4 (1100) 3-.15 3.7 3...15 3.7 4...15 3.7 3...18 4.7 4,..15 4.7 1000 10X10 1200 11X10 1250 11X10 1600 11XI0 2000 11X10 1/4 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075) 1 (1100) 20X20X1 20X24X1 24X30X1 0.042 RETURN-AIR FILTERS (in.) throwaway (2) Table 2--Physical 0.057 (2) 24X30X1 0.061 (2) 24X30X1 Data UNIT SIZE 50JX030 2-1/2 50JX036 3 50JX042 3-1/2 50JX048 NOMINAL CAPACITY (ton) 4 50JX060 5 OPERATING WEIGHT (lb.) COMPRESSOR QUANTITY TYPE 32O 328 350 375 428 1 SCROLL COMPRESSOR REFRIGERANT REFRIGERANT R-22 AccuRater_ METERING DEVICE Refrigerant (R-22) Quantity (lb.) 6.4 7.0 10.8 ORIFICE ID (in.) ORIFICE OD (in.) OUTDOOR COIL Rows... Fins/in. Face Area (sq, ft,) OUTDOOR FAN Nominal Airflow (CFM) Diameter Motor HP (RPM) 0.073 0.076 0.080 10.1 0.088 0.093 0.043 (2) 0.040 (2) 0.052 (2) 01057 (2) 0.063 (2) 2...17 10.3 2...17 10.3 2...17 13.7 2...17 13.7 2..,17 15.7 2350 22 2800 22 114 (1100) 2800 22 1/8 (825) 3300 22 1_ (1100) 3300 22 1/4 (1100) 1/8(825) 12.3 INDOOR COIL Rows... Fins/in. Face Area (sq. ft.) INDOOR BLOWER Nominal Airflow (CFM) Size (in.) Motor HP (RPM) 3...15 3.7 4...15 3.7 4...15 4.7 4._15 4.7 4...15 5.7 1000 10X10 1/4 (1075) 1200 10X10 1/2 (1075) 1400 11X10 1/2 (1075) 1450 11X10 1/2 (1075) 1750 11X10 1 (1040) RETURN-AIR FILTERS (in.) throwaway 20X20X1 20X24X1 24X30X1 24X30Xl 24X30X1 NOTE;Air filter pressure dropfor non-standardfiriers mustnotexceed 0.08 in. wg. Table 3_Minimum Airflow for Reliable Electric Heater Operation (Cfm) SIZE 50JS030 50JS036 50JS042 50JS048 50JS06O AIRFLOW (CFM) 1000" 1200 1400 1600 2000 * The 030 siZemodels mustbe run on mediumor highspeedwhen usedin coniunction with 15 kwelectric heataccessory Table 4---Minimum Airflow for Reliable Electric Heater Operation (Cfm) SIZE 50JX03O 50JX036 50JX042 50JX048 50JX060 AIR FLOW (C FM) 13O0" 1200 1400 1600 2000 • The 030 size models mustbe runon mediumor highspeedwhen usedin conjunction with 15 kwelectricheataccessory DETAIL A ( SEEDETAILA_' A05179 UNIT Size MAXIMUM WEIGHT (INCLUDES SHIPPING SKID) Lb Kg A B In. Mm. In. in3. 50JS030 50JS036 3O9 313 140.2 19.5 495.3 17,50 444.5 142,0 19.5 50JS042 345 19.5 495.3 495.3 17.75 17.75 450.9 450.9 50JS048 50JS060 375 156.4 170.1 20.5 520.7 20.62 523.8 440 199.6 495.3 19.75 501.7 50JXO30 50JX036 342 155.2 19.5 20.0 508 19,25 489 350 159.8 20.0 372 377 45O 168.8 171.0 21.O 20.0 19.0 20.5 482.6 50JX042 50JX048 508 533.4 204.2 21.0 508 533.4 21.25 20.0 50JX060 Fig. &--Suggested 520.7 539.8 508,0 Rigging C00139 Fig. 9_Typical Installation Failure to follow these precautions the unit being installed: 1. Make all electrical connections ANSI/NFPA (latest could result in damage in accordance edition) and local to with NEC electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part I and applicable codes. Refer to unit wiring diagram. 2. Use only copper conductor for field-supplied electrical disconnect NOT USE ALUMINUM WIRE. local connections between switch mad unit. DO 3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On all 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance. 4. Insulate Horizontal Duct Covers c99030 Fig. 10--50JX with Duct Covers On (Unit Shown with Optional Louvered Grille) HIGH-VOLTAGE + + TRAP OUTLET _ F'_ --""""7 _ The unit Trap have a separate electrical service with a field- If the unit has an electric heater, a second disconnect required. Consult the Installation, Start-Up, and Service may be Instruc- tions provided tions. connec- Operation with the accessory of unit on improper may cause unit damage an uninterrupted, unbroken the possibility of personal ROUTING POWER for electrical line voltage service constitutes abuse and that could affect warranty. LEADS INTO UNIT Use only copper wire between disconnect and unit. The highvoltage leads should be in a conduit until they enter the duct panel; injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit approved for electrical conduit termination at the duct panel must be watertight. Run the high-voltage leads through the power entry knockout on the power entry side panel. See Fig. 2 and 3 for location and size. When the ground when installed in accordance with NEC, ANSI/NFPA= American National Standards Institute/National Fire Protec- leads are inside the unit, pJn leads up the high-voltage tion Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.l) and local electrical codes. Failure to adhere to this warning must (ampacity) for wire sizing (See Tables 5 and 6 for electrical data). The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole (See Fig. 2 and 3). ¥!_ |','l:%q_,1I_ must have to minimize CONNECTIONS supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes 2" 50mm) MIN . ]-or maximum fuse/c rcu breaker size and minimum circuit amps Electrical Connections The unit cabinet electrical ground contained control wires are in same T j_ C99013 Fig. 11--Condensate wires for lfighest voltage 5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. 1" (25ram) MIN. Step 7--Install low-voltage within conduit when low-voltage conduit as high-voltage wires. raceway to the line wiring splice box (See Fig. 12-17). On all 3-phase units, connect the leads to the black, yellow, and blue wires (See Fig. 16). could result in serious injury or death. CONNECTING Connect GROUND the ground LEAD TO GROUND lead to the chassis LUG using the ground lug in the wiring splice box (See Fig. 16). ROUTING CONTROL Form a drip-hiop POWER WIRES with the thermostat (24-V) leads before routing them into the unit. Route the thermostat leads through grommeted, low-voltage hole provided in unit into unit control power splice box (See Fig. 2 and 3). Connect thermostat leads to unit control power leads as shown in Fig. 15. The unit transformer supplies 24-v power for complete system including accessory electrical heater. An automatic-reset circuit breaker (See Fig. 17) is provided in die 24-v circuit; see the caution label on the transformer or Fig. 18. Transformer is factory wired for 230-v operation. If supply voltage is 208-v, rewire transformer primary section. 10 as described in Special Procedures for 208-v Operation Table 5_Electrical UNIT 50JS SIZE O3O _PH-HZ 208/230-340 208/230-3-80 VOLTAGE RANGE COMPRESSOR MIN MAX RLA LRA 187 253 9.9 78 187 253 OFM FLA 0.9 IFM FLA 208/230-3-60 414 187 506 253 5.5 12.4 40 90 20/20 30/35 45/50 60/- -/70 18.0/18.0 31.0/33.0 44.0/48.0 57.1/63.1 25/25 35/35 45/50 60/- -/70 ./. 6 10 15 ./. 3.8/5,0 7.5/10.0 11.3/15.0 15.0/19.9 -/6.0 12.0 16.0 -/10.4/12.0 20.8/24.1 31.3/36.1 41.6/48.0 9.6 17.1 24.6 32.1 15 20 25 35 20.2/20.2 33.2/35.2 46.3/50.3 59.5/65.3 72.2/80.2 25/25 40/40 50/60 60/- 1.8 -/5 10 15 20.0 ./o 6.0 12.0 18.0 24.1 11.0 18.5 26.0 33.5 41.0 15 20 30 35 45 3,5 ./. 3.8/5.0 7.5/10.0 11.3/15.0 15.0/20.0 ./. 10.4/12.0 20.8/24.1 31.3/36.1 41.6/48.0 22.6/22.6 35.7/37.7 48.7/52.7 61,7/67.7 74.6/82,6 30/30 40/40 50/60 -/- . 5 10 15 26 -/3.3/5.0 7,5/10.0 11,3/15,0 15.0/19.9 6,0 12.0 18.0 24.1 -/10.4/12.0 20.8/24.1 31,3/36.1 41.6/48.0 11.5 19,0 26.5 34.0 41.5 15 20 30 35 45 32.0/32.0 45.0/47.0 58.0/62.1 71.1/77.1 83.9/91.9 40/40 50/50 14.0 21.5 29.0 36.6 44.1 20 25 30 40 45 3.8 O42 460-3_60 208/230_3_0 414 187 506 253 6.7 14,1 45 105 0.8 1.5 048 460-3-50 208/230-,3-60 414 187 506 253 7.1 19.4 53 125 0.8 1.8 1.5 -/3.8/5.0 7.5/10,0 11,3/15.0 ./. 3.8/5.0 7.5/10.0 11,3/15.0 15.3/15.3 28.3/30.3 41.3/45.3 54.4/60.4 1.9 0.9 FLA -/10.4/12 .0 20.8/24,1 31.3/36.1 -/10,4/12,0 31.3/36.1 36.1/41.7 4.1 0,8 Nominal kW* 5,2 O60 -/- 460_._-80 414 506 8.0 63 0.8 3.2 It SINGLE POINT POWER SUPPLY FUSE OR CKT BKR 036 460-3-60 ELECTRIC HEAT MCA 2.0 1.5 9.9 Data--50JS 5 10 15 20 ° 6.0 12.0 18.0 24,1 MOCP ° -/70 80/90 7o o 80/90 60/70 80/80 90/100 Table 6--Electrical UNIT 5OJX SIZE O30 V-PH-HZ VOLTAGE RANGE MIN 208/230-3--60 208/230_60 187 187' MAX 253 253 COMPRESSOR RLA 10.4 11.2 LRA 63 75 OFM IFM FLA FLA 0.9 1.6 208/230-3_0 414 187 506 253 5.4 12.4 37.5 88 0.9 0.9 208/230-3-60 414 187 506 253 5.8 13.0 44 93 0.9 1.6 460_3_0 208/230_3_30 414 187 506 253 6.4 17.3 46.5 123 0.9 2,1 -/10.4/12.0 20.8/24.1 31.3/36.1 16.0/16.0 29.0/31.0 42.1/46.1 55.1/61,1 20/20 35/35 45/50 3.6 -/3.8/5.0 7.5/10.0 11.3/15.0 -/10.4/12.0 36.1/41.7 31.3/36.1 19.2119.2 32.0/34.2 45.2/49.3 58.3/64.3 25/25 35/35 50/50 1.9 -/5 10 15 46 12 18 9.6 17.1 24.6 32.1 15 20 25 35 4.1 -/3.8/5.0 7.5/10,9 11.0/15.0 15.0/20.0 -/10.4/12.0 29.8/24.1 31.0/36.1 41.6/48.0 20.5/20.5 33,5/35.5 46.6/50.6 59.6/65.6 72,5/80.5 25/25 40/40 59/60 2.9 -/5 10 15 20 -/6 12 18 24.1 10.2 17.7 25.2 32.7 40.2 15 20 30 35 46 4.1 -/3.6/5.0 7.5/10,0 11.3/15,0 15.0/20.0 410.4/12.0 20.8/24.1 31.3/36.1 41.5/48.0 21.9/21.9 34.9/36.9 47.9/51.9 60.9/67.0 73.8/81.8 30/30 40/40 50/60 45 10 15 20 -/6 12 18 24.1 10.8 18.3 25.8 33.3 40.8 -/3.8/5.9 7.5/10.0 11.3/15.0 15.9/19.9 -/5 10 15 20 -/10.4/12,0 20.6/24.1 31.3/36.1 41.6/48.0 -/6 12 18 24.1 29.2/29.2 42.3/44.3 55,2/59.4 68.3/74.3 81.2/89.2 15.4 22.9 30.4 37.9 45.4 1.4 2.0 6.2 O60 460-3_0 414 506 9.0 62 0.9 3.2 12 kW* FUSE OR CKT BKR -/3.8/5.0 7.5/10.0 11.3/15.0 048 Nominal SINGLE POINT POWER SUPPLY MCA 042 460-3_0 ELECTRIC HEAT FLA 036 460-:_60 Data--50JX MOCP 60/70 60/70 60/70 80/90 70/70 80/90 15 20 30 35 45 35/35 50/50 60/60 70i80 90/90 20 25 35 40 50 fII_L_IELO _1 _L E- -- ,,EL i _ SUPPLY --WI2I I- 8LU EOUIP.GNO ACCCSSORV USED WITH OPTION ONLY ELECT.EkI US£1) WITH N[AT[R _I_-- - _" BL --I__ -! Pmm_H' _ [024 (042 060) _ 0601 kWP S B 30 L lO HIR MAXWIldE2 Ai(G i '___= _ (50 Ak(P FOE 15 KI_ ) IFUI 3 /_ 5) TO US 0 IVT I _HI_ ACCESSORY _ Iuz MI i_ LCI Hkl I 30,kMPSB _ OPTION ON Y _ TO USED WIIH _ GO AMP S 8 HTR HEATER OPTIONS _YEL-- 19 9 KW BLU RED SPED _ I • 15 K W [CONNECT -RED OPTIONSN 060) _ L FOR 50JX030 ONLY) VEL W128 BLK-- BLK-- i I_ GRN-YEL_26 GEN-YEL i _euect (20 -- GRN YEL_ GRN-y[[ BLU-TRANI K W SHOV_,_} MA,UAL 3 2 AMP RESEl_ C_,.,-_ WIT BR_ _)6 GRN q SEE NOTE 15_ ON NIT F RED R -- C)ll AUTO S _19 ORN _W _20 -------_18 WHT YE_ _ _;.PPLT._ uPL.E_t = _ _131 pN_ W2-_y2 rlEL_ SEE i_ _ THERMO_IAT NOTE#2 WHI _'130 I VIO _133 I-- GRA_ _21BRN--- HRI _12o 2(V SPLICE UNIT COWPONENI _70 RN 2 3 _ _ [20 BRN 5RN-- KWI_ I BOX ARRANGEWENT iouI_ F_N _SECIIOU rl{Lo S_LIC( _H_ _BJUST_BL( W_*_ _NT_I_I_ ru fUS{ O_W OUt_ IDN (L)k r_I _EOUEN¢[ CLOSES T_T OENS r_ _tO_ ,_r_ost / FOI IIII_ II iZ _ SOJS04_I SDa%04_'O_O 0_I !50JS5OOOOG(? 0 GO( 134 Fig. 12--Wiring Schematics (208/230-3-60) 13 c _AXIMU_ SIZE WIR[ 2 AWG _ _ -- _2 FIEL_ il m 50-1BVIATIC BLK YEL--_ / - _,. TEL-- CApZ YEL OFM _o_ [OUIP _ND ACCESSORY ELECT HEAT OPTION ONLY HEATER 5,10,15 AWG[ WAXWIR -- OPTIDNS _ _0 KW _ Y[L g_ L-L_--BE _25 GRN YEL_?6 GRN Y[L GRN-YEL_ GRN _z --W16 YEL # GRN SEE NOTE PLI-I UNIT COMPONENT ARRANGEMENT Te_ (I _ [WEmOIZED _D _ILI_ DE-ENEe_Ep COWpRES_ORDELay F:_ _F_OS _ _ J _W_ [ou_e O_W_ _m _ffs_I iF_ llW[ D[L_ ffL*_ m IM{OlI_,_L II_[_F_m=Is.[_ _( e[eL_:E_ 150JS50000717 0 C00135 Fig. 13--Wiring Schematics (460-3-60) 14 EXAMPLE: Supply voltage is 460-3-60. FLA -- Full Load Amps LEGEND LRA -- Locked Rotor Amps MCA -- Minimum Circuit Amps MOCP -- Maximum Overcurrent Protection RLA -- Rated Load Amps CKT BKR -- Circuit Breaker C US AB =452v Average Voltage = (_ BC = 464 v 452 + 464 + 455 3 = 1371 3 = 457 NOTES: 1. In compliance with NEC (National Electrical Code) requirements for muitimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. Canadian units may be fuse or circuit breaker. 2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase tmbalance in supply voltage is greater than 2%, Use the following formula to determine the percentage of voltage imbalance. Determine maximum deviation (AB) 457 452=5v (BC) 464 457=7v (AC) 457 455=2v Maximum deviation is 7 v. from average voltage. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. % Voltage imbalance = 100 x AC = 455 v ,, o o max voltage deviation from average voltage average voltage IMPORTAN]_ If the supply voltage phase imbalance is] more than 2%, contact your local electric utility company/ immediately. Fig. 1€--Electrical © Q--- L.-- _.__ / C99024 Data Legend BRN_- ----L---- o.N_ RED -- _ GRN -- THERMOSTAT UNIT CONTROL POWER SPLICE BOX AND SUBBASE C99056 Fig. 15---Control Connections 24 V Circuit Breaker GROUND LUG IN SLPICEBOX) C99070 GROUND "L_AS- _ Fig. 17--Control SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC L2 Wiring Plate _BLK-- L1 ........ _YEL-- TRANSFORMER CONTAINS A MANUAL RESET OVERCURRENT PROTECTOR L3 ........ _C_-"-BLU -3-PHASE CONNECTIONS NOTE: Use copper wire only. LEGEND NEC - National Ele_rical Code - - Field Wiring _ Splice Conne_ions IT WILL NOT AUTOMATICALLY RESET DISCONNECT POWER AND INSTALL LOCKOUT TAG PRIOR TO SERVICING THIS COMPARTMENT MUST BE CLOSED EXCEPT WHEN SERVICING C99057 Fig. 16---Line Power Connections C99058 Fig. 18_Transformer 15 Label SPECIAL PROCEDURES 1. Disconnect FOR 208-V the yellow primary unit wiring blower-motor operation. b. Make speeds lead to the transformer sure that condensate 5. Compressors remove for 208-v Refer to indoor airflow and airflow adjustments pan and trap are filled c. Make sure that all tools and miscellaneous been removed. terminal may need to be changed drain with water to ensure proper drainage. See label (See Fig. 12). 2. Connect the yellow primary labeled 200-v. Indoor OPERATION lead from the transformer. section. 6. Each unit Schrader Schrader PRE-START-UP are internally compressor system loose parts have spring mounted. holddown Do not loosen or bolts. has 2 Schrader-type port.s, one low-side fitting located on the suction line, and one high-side fitting located on the compressor discharge line. Be sure that caps on the ports are tight. Failure serious to observe the following personal injury or death: 1. Follow goggles warnings recognized safety practices when checking or servicing 2. Do not operate compressor unit unless secured. result and wear refrigerant in the field. Ensure possibility protective system. the plastic caps axe in place and tight or the or refrigerant leakage could occur. or provide any electric power to compressor 3. Do not remove could 7. High flow valves are located on the compressor hot gas and suction tubes. These valves can not be accessed for service in terminal compressor cover is in place and terminal cover until all electri- cal sources are disconnected and tagged. 4. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor 5. Never attempt to repair soldered erant system is under pressure. connection C99009 Fig. 19_Fan Blade Clearance wear protective System goggles START-UP Using the Start-Up proceed as follows: and Step 1--Check a. Shut off electrical power to unit and install lockout tag. b. Relieve and reclaim all refrigerant from system using both high- and low-pressure ports. c. Cut component connecting tubing with tubing remove component from unit. d. Carehiliy unsweat remaining MOTORSHAFT while refrig- 6. Do not use torch to remove any component. contains oil and refrigerant under pressure. To remove a component, proceed as follows: MOTORAND FANHUB terminals. tubing sary. Oil can ignite when exposed Checklist supplied for Refrigerant Locate and repair refrigerant at the end of this book, Leaks leaks and charge the unit as follows: I. Use both high- and low-pressure ports to relieve pressure and reclaim remaining refrigerant. cutter and 2. Repair stubs when neces- NOTE: to torch flame. leak following Instal] a bi-fhiw accepted system practices. filter drier whenever the system has been opened for repair. Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial 3. Check system start-up: 4. Reclaim refrigerant and evacuate refrigerant microns if no additional leaks are found. system 5. Charge a volumetric- 1. Remove access panel. 2. Read and follow instructions CAUTION, shipped and on all DANGER, INFORMATION labels WARNING, attached to, a. Inspect or inspections: for shipping lines, loose Step 2---Start-Up and handling parts, disconnected damages Complete tubing connections erant leak is detected, Leaks section. or liquid-soap see following refrigerant, solution. and on low-ambient If a refrig- the Adjustments required procedures kit is installed). Allow 5 minute damage. Check for Refrigerant c. Inspect all field and factory-wiring connections. that connections are completed and tight. given between touch e. Inspect coil fins. If damaged carefully straighten 4. Verify the following refrigerant tubing during shipping cycles the compressor. to prevent compressor operation as follows: or sharp I. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down within 60 sec. when FAN and handling, switch is placed conditions: blade is correctly the Pre-Start-Up CHECKING COOLING AND HEATING CONTROL OPERATION Be sure Pms with a fin comb. a. Make sure that outdoor-fan fan orifice (See Fig. 19). in Do not rapid-cycle "on" Start and check the unit for proper control d. Ensure wires do not sbeetmetal edges. using section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in Cooling mode when the outdoor temperature is below 40 ° F (unless accessory unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using leak detector, R-22 to 500 such as broken wires, etc. b. Inspect for oil at all refrigerant electronic with method. charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refrigerant to compensate for internal volume of filter drier. with, unit. 3. Make the following unit for leaks using an approved positioned 2. Place SYSTEM AUTO position. in in AUTO position. switch in COOL position and FAN switch in Set control below room temperature. Observe that cooling cycle shuts down when control setting is satisfied. 16 _rF OUTDOOR COIL INDOOR COIL Bypass Position LCS Metering Position LEGEND HPS - High Pressure Switch LCS - Loss of Charge Switch _j_ ] Accurater e Metering Device Arrow indicates direction of flow C00095 Fig. 20--Typical Heat Pump Operation, Heating Mode INDOOR COIL Metering Position LCS OUTDOOR Bypa_ Pos_ion LEGEND HPS - High Pressure Switch LCS - Loss of Charge Switch "_ Accurate# Metering Device ] Arrow indicates direction of flow C00096 Fig. 21--Typical Heat Pump Operation, Cooling Mode CHECKING 3. Place system switch in HEAT position. Set control above room temperature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that heating down when control setting is satisfied. REFRIGERANT of 15 minutes 4. When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Ob- NOTE: before checking Adjustment or adjusting of the refrigerant control physical internal protector IMPORTANT: When evaluating cated adjustment to the specified power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressors emit elevated noise levels, and the difference between may be dramatically compressor suction lower than normal. and discharge is not required label is attached to the outside of the service access door. If charge level is suspect in Heating mode, reclaim all refrigerant and charge to nameplate amount. (This information may be obtained from the IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minute, the The 3-phase charge. charge unless the unit is suspected of not having the proper R-22 charge. The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging serve that unit operates in Cooling mode when temperature control is set to "call for Cooling" (below room temperature), will shut off the compressor. CHARGE The refrigerant system is fully charged with R-22 refrigerant and is tested and factory sealed. Allow system to operate a minimum cycle shuts and unit operates in Heating mode when temperature is set to "call for Heating" (above room temperature). AND ADJUSTING data table also.) the refrigerant charge, an indifactory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils. pressures 17 Balance Point Worksheet 7O 6O so mg _o m_ ,0 m_ 80 :z:o_ 30 _._ 20 lO -10 0 10 17 20 30 40 47 50 6O OutdoorAir Temp (Deg F) C00093 Rev 2 Fig. 22--50JX Balance Point Worksheet REFRIGERANT CHARGE INDOOR AIRFLOW AND AIRFLOW The amount of refrigerant charge is Listed on the unit nameplate and/or the physical data table. Refer to the Refrigeration Service Techniques Manual, Refrigerants ¥_ [__.'luhnl[.]H Section. For heating and cooling operation, the recommended is 350 to 450 cfm for each 12,000 Btuh of rated NO CHARGE CHARGE 4. Failure the unit. Tables COOLING external to maintain these airflows 7 and 8 shows both heating static pressures. Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until the conditions of the chart are met. Note that charging charts are airflow for the system different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gauge and temperature _nsnig devices are from obstructions, NOTE: Indoor air CFM must be within the normal CHARGING operating should at various Refer to these tables to determine Be sure that all supply-and For 2081230-v follows: 3-SPEED CHARTS Black Take the outdoor ambient temperature and read the suction pressure gauge. Refer to the chart to determine what the suction temperature and cooling airflows to the and adjusted return-air grilles are open, free properly. by changing the lead connection of the Unit 50JS and 50JX three-speed motors (except 50JX 030) are factory wired for low speed operation. Unit 50JX 030 is factory wired for medium speed. range of the unit. TO USE COOLING could result in damage being installed. Airflow can be changed blower motor. required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the reading. airflow cooling capacity. For units with optional electric heat, the airflow must not be reduced below the levels stated in Tables 3 and Check for leak. Use standard evacuating techniques. ARer evacuating system to 500 microns, weigh in the specified amount of refrigerant (refer to system data plate). LOW ADJUSTMENTS Motors:-- The motor leads are color-coded as = high speed Blue = medium speed Red = low speed be. To change the speed of the indoor fan motor (IFM), remove NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section. die fan motor speed leg lead from the Time Delay Relay (TDR). This wire is attacbed to TDR-3 for 3-phase units. To change the speed, remove and replace with lead for desired blower motor speed. ln,Tulate the removed lead to avoid contact with chassis parts. 18 Balance Point Worksheet 70 Based on Indoor Entering Air of 70 F and Rated CFM 60 i- ca 50 _o o_ go ...__ 40 C 30 Im _q:3 ca_ _E 2o lO -10 0 10 17 20 Outdoor 30 40 47 50 6O Air Temp (Deg F) C00094rev2 For 460-v follows: GE Motors_The motor leads Fig. 23_50JS Balance Point Worksheet are color as coded 3-SPEED The ability to properly perform ment requires certain expertise, Black = high Violet = jumper equipment. If you do not possess these, do not perform any maintenance on this equipment, other procedures recommended in the User's Manual. TO HEED THIS WARNING COULD RESULT Orange = medium Red = low To change die speed of the indoor fan motor motor speed lead from the Time (IFM), remove fan OUS INJURY OR DEATH THIS EQUIPMENT. Delay Relay (TDR) and replace with the lead for the desired blower motor speed. The motor speed lead is attached to terminal TDR-3. For low and medium speeds, black must be connected to the jumper wire. Insulate removed lead end to avoid contact with chassis parts. To select high speed on 460-v GE motors, separate die black female quick connect (QC) from the jumper lead male quick connect black lead to the BR. Insulate the jumper chassis parts. (QC) and connect maintenance on this equipmechanical skills, tools and AND POSSIBLE Failure to follow these warnings or death: the attempt to than those FAILURE IN SERI- DAMAGE TO could result in serious injury I. Turn off electrical power to die unit and install lockout tag before performing any maintenance or service on this unit. 2. Use extreme caution when removing panels and parts. As to avoid contact with any with any mechanical equipment, personal injury can result from sharp edges. 3. Never place anything combustible either on, or in contact with, the unit. MAINTENANCE To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on tiffs equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11. NOTE TO EQUIPMENT OWNER: about the availability of a maintenance Consult your local dealer contract. ing when servicing. The minimum follows: 19 maintenance requirements for this equipment are _.s Table 7--Wet Coil Air Delivery Unit 50JS 030-060 (Deduct 10 percent for 208-V)* MOTOR SPEED UNIT Low 3O Med High Low 36 Med High Med High Low 48 Med High Low 6O 0.1 0.2 Watts 295 292 289 802 Med 0.8 0.9 1.0 I I Cfm 928 882 388 383 377 372 366 361 Cfm W_ts Cfm 1203 1120 1062 1004 930 469 1141 838 458 1027 449 924 442 828 W_ts Cfm 592 1499 552 1281 538 1207 525 1125 512 1034 499 936 Watts 660 636 617 603 592 581 Cfm WaRs Cfm 1475 1371 1274 776 1452 1186 761 1356 1105 744 1254 1024 725 i ] 928 706 1145 ] 1030 550 1146 537 1066 581 1421 606 1464 567 1351 596 1399 586 1341 575 1282 563 1218 I WaRs 680 665 649 635 622 611 600 590 Cfm 1608 1535 1461 1387 1316 1247 1180 1111 Watts Cfm 768 1656 755 1576 742 1508 730 1447 718 1396 797 1331 596 1268 684 1198 671 1119 552 1384 WaRs 741 724 709 690 664 631 594 562 Cfm 1994 1937 1869 1797 1722 1645 1566 1480 566 1 1 I 543 1269 773 744 715 667 662 640 625 Cfm WaRs Cfm 1957 1867 1787 799 1914 1719 782 1842 1653 773 1774 1575 1463 756 1686 704 1538 WaRs 742 723 698 666 629 591 559 540 Cfm W_ts 2197 838 2141 822 2103 803 2057 760 1988 752 1894 721 1783 689 1674 661 Cfm 2485 2406 2269 2127 2012 1937 1894 1855 934 2483 913 2391 691 2283 666 2170 837 2061 806 1960 776 1868 689 910 i WaRs WaRs Cfm High EXTERNAL STATIC PRESSURE (IN. WG) 0.3 0.4 0.5 0.6 0.7 WaRs WaRs Cfm Low 42 0.0 [ I 639 632 1770 750 ] [ 1571 735 1780 i 1687 * Air delivery values are based on operating voltage of 230_v or 460-v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure available for ducting. NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point. 2. Dashes indicate podions of table that are beyond the blower motor capacity or are not recommended. 3. Deduct 10 percent for 208-v. 1. Inspect air filter(s) each month. Clean or replace Step 2--Indoor when necessary. 2. Inspect indoor coil, drain pan, cooling season for cleanliness. and condensate electrical connections proper sary. operation each cooling season. and controls Service refrigerant for or sha_ the unit without Always replace Inspect month at least once each Inspect (See Tables and tag electrical power Step 3--OUTDOOR COIL, INDOOR CONDENSATE DRAIN PAN a suitable air filter the fiker with the installed and to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause serious injury or death. Filter filter(s) efficiency, wheel and when neces- tubing same dimensional size and type a_soriginally I and 2 for recommended fdter sizes.) air to lubricate For longer life, operating economy, and continuing clean accumulated dirt and grease from the blower each cooling Disconnect IMPORTANT: Never operate in the return-air duct system. Do not attempt motor annually. for tightness 5. Ensure wires are not contacting sheet metal edges. Step 1--Air for cleanliness and motor NOTE: All motors are prelubricated. these motors. each Clean when necessary. 3. Inspect blower motor and wheel season. Clean when necessary. 4. Check drain blower the condenser coil, evaporator pan at least once each heating conditions require. replace COIL, AND coil, and condensate and cooling season drain or sooner if The coils are easily cleaned when dry; therefore, inspect and dean the coils either before or after each cooling season. Remove all (throwaway-type) or clean (cleanable-type) at lea.st twice during each cooling season or whenever the f-alterbecomes clogged with dust and tint. obstructions, including weeds and shrubs, airflow through the condenser coil. 20 that interfere with the Table 8_Wet Coil Air Delivery Unit 50JX 030-060 (Deduct 10 percent for 208-V)* MOTOR SPEED UNIT Low 3O Med High Low 36 Med High Low 42 Med High Low 48 Med High Low Med 60 High Watts Cfm 0.O 0.1 0.2 276 963 276 929 272 781 EXTERNAL STATIC PRESSURE (IN. WG) 0.3 0.4 0.5 0.6 0.7 Watts 375 377 371 362 354 350 Cfm 1202 1170 1079 976 884 807 469 1174 449 988 Wa_s Cfm 435 828 WaHs 462 451 431 411 394 381 Cfm 1374 1290 1205 1116 1020 916 Watts 523 506 499 471 449 426 Cfm Watts Cfm 1500 1408 645 1474 1301 628 1369 1190 610 1267 1082 595 1169 977 584 1069 575 962 Watts Cfm 620 1662 600 1621 586 1581 574 1540 562 1496 548 1447 530 1392 0.8 0.9 1.0 428 718 510 1331 487 462 439 1263 1186 1103 Wa_s 686 661 634 606 577 547 517 Cfm 1722 1662 1594 1515 1427 1330 1227 757 1669 730 704 682 1577 1486 1402 1331 1263 WaHs Cfm WaSs 620 600 586 574 562 548 530 Cfm 1662 1621 1581 1540 1496 1447 1392 487 Watts 763 747 729 709 686 661 634 606 577 547 517 Cfm 1917 1868 1822 1774 1722 1662 1594 1515 1427 1330 1227 852 1982 832 1914 809 1839 784 1757 757 1669 730 704 682 1577 1486 1402 Wa_s Cfm I I Watts 597 592 578 526 460 452 445 Cfm 2265 2190 2101 2033 1974 1869 1614 Watts Cfm 754 2383 730 2282 707 2202 687 2134 671 2070 658 2005 646 1935 630 1858 603 558 486 1771 1667 1576 Wa_s Cfm 901 2480 876 2383 856 2301 836 2233 813 2175 785 2122 755 2066 723 1998 696 681 687 1910 1788 1619 * Air delivery values are based on operating voltage of 230-v or 460-v, wet coil, without filter or elect nc heater. Deduct filter and electdc heater pressure drops to obtain static pressure available for ducting. NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point. 2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended. 3. Deduct 10 percent for 208-v. Straighten bent fins with a fin comb. If coated Step 4---Outdoor fan with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best result.s, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush ail dirt and debris from the unit 1. Inspect the fan blades for cracks 2. If fan needs to be removed, base. intake grille and remove 3. Loosen Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all the setscrew or bends. remove screws holding outdoor air grille. and slide the fan off the motor shaft. foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, 4. When replacing fan blade, position blade so that die hub is 1/8 in. (See Fig. 19) away from the motor end (1/8 in. of motor shaft will be visible) . or air filter(s). 5. Ensure If the drain trough is restricted, clear it with a "plumbers snake" or similar probe device. Ensure that the auxiliary drain port above the drain trough is also clear. that setscrew engages the flat area on the motor shaft when tightening. 6. Replace grille. Step f--Electrical controls and wiring Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. 2t (030) 60HZ CHARGING 200 , 30.0 400 -1 4 SUCTION panel 10 700 16 LIN E TEMPERATURE Fig. 24_Cooling access 60.0 F SUCTION L,NETEMPERATURE_T -7 Remove 50.0 CHART 21 (°C) (036) 60HZ CHARGING C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 I 30.0 40.0 50.0 60.0 SUCTION LINE TEMPERATURE I°Fq ] ...... J I I -7 -1 4 10 16 80.0 20.0 r 27 50JS500089 SUCTION LINE TEMPERATURE C00028 Fig. 25_Cooling Charging Chart, 50JSO30 to locate all the electrical controls CHART Step 8--Metering and 70.0 B0.0 21 I 27 (_C) 50JS500090 Charging Chart, 50JS 036 uncial _ 29 device wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are Refrigerant metering devices are fixed orifices and are located in the inlet header to the indoor and outdoor coils. noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely. Step 9_Liquid After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at lea_st one complete cooling label when making NOTE: Refer to the Sequence of Operation determining proper control operation. Step 6---Rsfrigerant Step 10_High as an aid in circuit thermostat is satisfied. This delay enables residual cooling in coil after compression leak-test sec., fan relay is energized. all leaks are found and low performance and Adjusting Step 7--1ndoor airflow The indoor performance airflow does is suspected. Refrigerant Charge When thermostat is satisfied, an off during this delay, TDR is reset and fan relay remains energized. TDR is a 24-v device that operates within a range of 15-v to 30-v and draws about 0.5 amps. If the blower runs continuously instead of cycling off when the fan switch is set on AUTO, the TDR is probably defective and must be replaced. Leaks section. refer to Checking blower to remove shutdown, thereby delay is initiated. When fixed delay of 60_+5 sec. is completed, fan relay is de-energized and fan motor stops. If wall thermostat closes refrigerant tubing using an electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for If no refrigerant control, recycle for 60 sec. after improving efficiency of system. The sequence of operation is that on closure of wall thermostat and at end of a fixed on delay of 1 serious injury or death. Use all service ports and open all flow-control devices, including solenoid valves. is suspected, hot gas and these valves relay The Time-Delay Relay (TDR) is a solid-state delay timer which keeps indoor blower operating System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid Refrigerant Flow Valves Step 11--Time-delay YT_'_L3,zP211] _ or if low performance are made of with O-rings located inside the caps. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur. Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak. If oil is detected devices) High flow valves are located on the compressor suction tubes. Large black plastic caps distinguish these checkouts. section (to protect metering wire mesh and are located in the liquid lines on the inlet side of the metering devices. cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring line strainers The liquid line strainers is suspected, section. Step 12--4.oss of charge switch The loss of charge switch is located on the outdoor liquid line. This switch contains a Schrader core depressor. psig and closes at 22 psig. No adjustment not require checking unless improper If a problem exists, be sure that all This switch opens at 7 is necessary. supply- and return-air grilles are open and free from obstructior_;, and that the air filter is clean. When necessary, refer to Indoor NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for Airflow airflow. troubleshooting unless you are re;_onably exists. If switch must be removed, remove and Airflow AdjustmenL_ section to check the system 22 certain that a problem and recover all system (042.) 60HZ CHARGING CHART (048) 60HZ CHARGING CHART ,4Jq 6891 100 125 115 52 46 I 105 41 I J. -4.._ 95 35 I 8s 29 I 7s 241 65 18 I 55 131 45 71 i i i i i : I I i I I I I lU) I I ! [ I!111 i 3°° ,oo SUCTION -7 LiNE TEMPERATURE -1 SUCTION Fig. 26--Cooling 4 10 16 LINE TEMPERATURE (°C) Charging Chart, 20.0 r (°F_ 21 I _7 27 50JS50009 300 I I I I I : I 400 500 61_0 SUCTION LIN E TEMPERATURE !_F) ! I I I -1 4 10 16 SUCTION Fig. 27--Cooling 50JS 042 unC_l_ °3° I I Illil 207! ,o.o 8o.0 i I LINE TEMPERATU RE 70.o so.o J i ! 21 (°C) i 27 i I 50JS5000921 Charging Chad, 50JS 048 Un_=_31 (D60) 60HZ CHARGING CHART 20.0 I 7 30.0 400 SUC_ONL_ETEMPERATURE°_( I I I 1 4 10 Fig. 28--Cooling charge so that pressure gauges read 0 psi. Never without breaking vacuum with dry nitrogen. Step 13_Check defrost open system NOTE: The defrost thermostat must be located on the liquid side of the outdoor coil on the bottom circuit and as close to the coil as possible. is a 3/8-in. OD stub tube approximately 3 in. long (See Fig. 35). The defrost thermostat should be located on this stub tube. Note TROUBLESHOOTING and on most Refer to the Cooling and Heating Troubleshooting 11 ) for troubleshooting information. are right for Use the Start-Up Checklist followed. Thermostat Defrost thermostat defrost or that conditions START-UP signals heat pump that conditions have changed I 27 a thermally actuated switch clamped to outdoor coil to sense its temperature. Normal temperature range is closed at 30 ° +/- 3°F and open at 80 ° +/- 5°F. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of I of the feeder tubes, there Step 14--Defrost J 21 _ 32 Charging Chart, 50JS 060 UnCi_= thermostat that there is only 1 stub tube used with liquid header, units it is the bottom circuit. 80.0 ! 16 to terminate defrost. It is 23 Chart (Table CHECKLIST to ensure proper start-up procedures are Fig. 29_Cooling Fig. 30_Cooling Charging Charging Chart, 50JX 030 Un_tl_32 Chart, 50JX 036 Un_ 33 c s_ II......_)_=_=_=_ = ill , I 4 i io _ ............ ; *_ _x_o_23 C99035 Fig, 32--Cooling Charging Chart, 50JX C99036 048 Units Fig. 33_Cooling 24 Charging Chart, 50JX 060 Units Table 9---FILTER PRESSURE DROP (In. wg) FILTER SIZE 20X20X1 1300 CFM 1400 1500 0.13 0.14 0.15 0.16 0,07 0.08 0,09 0,10 500 600 700 800 900 1000 1100 1200 0.05 0.07 0.08 0.10 0.12 0.13 0,14 0.15 0.09 0.10 0.11 20 X 24 X 1 24 X 30 X 1 Table 10_ELECTRIC 1600 1700 1800 1900 2000 2100 2200 2300 0,11 0.12 0,13 0.14 0.15 0.16 0,17 0,18 HEAT PRESSURE DROP TABLE Small Cabinet STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0.O0 0.O0 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07 10 kW 0,00 0.00 0,00 0,00 0,00 0.02 0,04 0,06 0.07 0.09 0.10 0.11 15 kW 0,00 0.00 0,00 0.02 0,04 0,06 0.08 0,10 0.12 0,14 0.16 0,18 20 kW 0.00 0.00 0.02 0.04 0,06 0,08 0,09 0,11 0,13 0.15 0.17 0.10 I I Large Cabinet STATIC CFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 5 kW 0.00 0.00 0.0O 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.09 0.10 0.11 0,12 10 kW 0.00 0,00 0.01 0,02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 15 kW 0.00 0.02 0.03 0,04 0,05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 20 kW 0.02 0,03 0.04 0,05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 DEFROST THERMOSTAT Fig. 35---Defrost Thermostat Fig. 34_Refrigerant Circuit C99097 25 C99092 Table 11--Cooling and Heating Troubleshooting Chart CAUSE SYMPTOM Compressor and outdoor fan will not start Compressor will not start but condenser fan runs Three-phase scroll compressor (size 030060 units) makes excessive noise, and there may be a low pressure differential Call power company Fuse blown or circuit breaker tripped Defective thermostat, contractor, transformer, control relay or detrost board Replace fuse or reset circuit breaker Insufficient line voltage Determine cause and correct Incorrect or faulty wiring Check wiring diagram and rewire correctly Thermostat setting too high Lower thermostat setting below room temperature Units have a 5-minute time delay DO NOT bypass this compressor time delay-waft for 5 minute until time,delay relay is de-energized Faulty wiring or loose connections in compressor circuit Check wiring and repair or replace Compressor motor burned out, seized, or internal overload open Determine cause. Replace compressor Defective run capacitor, overfoad, or PTC (positive temperature coefficient) thermistor Determine cause and replace Defective run capacitor, overload, or PTC (positive temperature coefficient) thermistor Determine One leg of 3-phase power dead Replace f,Jse or reset Determine cause Scrst] compressor is rotating in the wrong direction Correct the direction of rotation by reversing the 3-phase power leads to the unit Refrigerant overcharge or undercharge Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate Dateetive compressor Determine Defective run/start capacitor, ovedoad or start relay Defective thermostat Faulty outdoor-fan motor or capacitor and correct Determine cause and replace Replace thermostat Replace Replace filter Thermostat set too low Reset thermostat Low refrigerant charge Locate leak, repair, and recharge Replace compressor Decrease load or increase unit size Check defrost time settings Reset as necessary Check defrost temperature switch Replace as necessary Recover refrigerant, evacuate system, and recharge Clean coil or remove restdcgon Dirty air tiger low cause Locate restriction and remove Outdoor coil didy or restricted too circuit breaker Dirty air filter Unit undersized for load Air in system pressure replace Determine cause and correct Frosted coil with incorrect defrost operation Head and Restriction in refggerant system operates continuously Excessive head pressure cause Damaged reversing valve Leaking valves in compressor Compressor Replace component Replace and determine cause Determine cause and correct Insufficient line voltage Blocked outdoor coft Compressor cycles (other than normally satisfying thermostat) REMEDY Power Failure Dirty indoor or outdoor coil Replace filter Clean coil Refrigerant overcharged Recover excess refrigerant Air in system Recover refrigerant, evacuate system, and recharge (Heat) Indoor air restricte_ or recirculating Determine cause and correct indoor or outdoor air restdcted or air short_ycling Determine cause and correct Low refrigerant charge Check for leaks, repair and recharge Compressor valves leaking Restriction in liquid tube Replace compressor Remove restriction (Heat) Outdoor coft frosted Move timer on control board to 30 minute between defrost cycles Check for source and eliminate Excessive suction pressure Compressor valves leaking Replace compressor Reversing valve hung up or leaking intemafty Replace valve Recover excess refrigerant (Continued next page) 26 Table 11--Cooling and Heating Troubleshooting Chart (Cont'd) SYMPTOM CAUSE REMEDY (Cool) Dirty air filter RepIace filter (Heat) Outdoor coil frosted Move timer on control board to 30 minute between defrost cycles Low refrigerant charge Check for leaks, repair and reCharge Remove source of restriction Metering device or low side restricted Suction pressure too low Increase air quantity Check filter-replace if necessary Beset thermostat (Cool) Insufficient coil airflow (Cool) Temperature too low in conditioned area Compressor runs but outdoor fan does not IFM* does not run IFM* runs when it should be off IFM* operaSon is intermittent * IFM4ndoor (Cool) Outdoor ambient below 40 ° F Field-installed filter-drier restricted Install Iow-_.mbient kit NC (normally closed) contacts on defrost beard open Check condition of relay on board Replace if necessary Blower wheel not secured to shaft insufficient voltage at motor Properly tighten blower wheel to shaft I_etermine cause and correst RepLace Power connectors not properly sea{ed Connectors should snap easily; do not force Motor programmed with a delay profile Allow a few minute for motor 1o shut off With thermostat in off state, the voltage on G, Y1 ,Y, Y2, W with respect to common, should be 1/2 of actual low voltage supply It measured voltage is more than 1/2, the thermostat is incompatible with motor If voltage is less than 1/2, the motor has failed Water ddpping into motor Verify proper drip loops in connector wires Connectors not firmly sealed Gently pull wires individually to be sure they are crimped into the housing Fan Motor Start-up checklist (REMOVE AND STORE IN JOB FILE) I. PRELIMINARY INFORMATION Model No ............................................................................................................................................................. Serial No .............................................................................................................................................................. Date ..................................................................................................................................................................... Technician ........................................................................................................................................................... Job Location ........................................................................................................................................................... II. PRE-START-UP __ Verify -- Remove that an packing -- Verify all shipping materials holddown that condensate __ Check all electrical -- Check that indoor -- Verify -- Check connection connections propeller and brackets is installed from unit per installation per installation and terminals (evaporator) that unit installation fan wheel have been removed bolts instructions instructions for tightness air filter is clean and in place is level for location in housing and setscrew tightness Ul, START-UP Supply Voltage: Compressor Indoor L1-L2 -- Amps: L2-L3 -- L1 L3-L1 L2 L3 Fan Amps: TEMPERATURE Outdoor-Air Return-Air Heat Pump Electric PRESSURES Temperature: Temperature: __ DB -- DE} WR Supply Air: Heater Supply Air: Refrigerant Suction Refdgerant Discharge psig psig -- Verify Refrigerant charge using charging tables -- Verify that 3-phase scroll compressor is rotating in correct direction 37 Copyright 2006 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Manufacturer reserves the right to discontinue, or change at any time, specifications Book 1 4 Tab 6 8 PC 101 Printed in U.S.A. Catalog No. 50JS,JX-6Sl or designs without notice and without incurring obligations. Pg 26 2-0_ Replaces: New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 28 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:16:22 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools