CARRIER Package Units(both Units Combined) Manual L0703136
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 16
| Download | |
| Open PDF In Browser | View PDF |
Turn to the Expertg_
Installation
IMPORTANT:
installation
This
installation
information
instruction
including
contains
installation
devices. For information
on unit start-up,
service,
refer to the unit Controls, Start- Up, Operation,
Troubleshooting
Instructions
also enclosed
basic
of field
Instructions
unit
control
Z_.
and operation,
Service, and
in the unit literature
SAFETY
INSTALLATION
........................
Unit Support
Step 2 - Rig and Place Unit
Step 3 - Field Fabricate
......................
........................
Ductwork
Step 5 - Install Flue Hood
Step 6 - Install External
Step 9 - Make Electrical
Drain
.....
8
10
...............
10
13
Step 11 - Install All Accessories
13
SAFETY
Controls
....................
air-conditioning
Untrained
personnel
of cleaning
coils
operations
should
the
words
to the
......................
potential
the basic maintenance
and filters and replacing
be performed
by trained
filters.
service
functions
All other
personnel.
When
working
on
air-conditioning
equipment,
observe
precautions
in the literature, tags and labels attached to the unit,
and other safety precautions
and
in
for personal
injury.
signal
DANGER,
WARNING.
severe
personal
injury
or death.
WARNING
signifies
and
a hazard
reliability,
is used to
installation.
or operation.
ELECTRICAL
Failure
injury
SHOCK
to follow
HAZARD
this warning
could
cause
personal
or death.
Before performing
service or maintenance
operations
on unit, turn off main power switch to unit and install
lockout
tag. Ensure electrical
service to rooftop unit
agrees with voltage and amperage
listed on the unit
rating plate.
13
equipment.
can perform
symbol
furnace
CONSIDERATIONS
Installation
and servicing of air-conditioning
equipment
can be
hazardous
due to system
pressure
and electrical components.
Only trained and qualified service personnel should install, repair,
or service
be alert
the
injury or product
and property
damage.
NOTE
highlight
suggestions
which will result in enhanced
Step 10 - Install Outdoor-Air
Hoods (Units with
Economizer
............................
Step 12 - Configure
or manuals,
on
2
9
........................
Connections
is the safety-alert
2
6
...........................
Step 8 - Install Gas Piping
This
symbol
6
.............
Trap for Condensate
Change
this
6
................
and Inlet Hood
see
which could result in personal injury or death. CAUTION
is used
to identify unsafe practices which may result in minor personal
2
...................
Step 4 - Make Unit Duct Connections
Step 7 - Orifice
1
...................................
Step 1 - Provide
instructions
information.
you
CAUTION.
These words are used with the safety-alert
symbol.
DANGER
identifies the most serious hazards which win result in
OF CONTENTS
CONSIDERATIONS
safety
When
Understand
packet.
TABLE
Recognize
that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
UNIT
OPERATION
AND SAFETY
Failure to follow this warning
could
injury, death and/or equipment damage.
HAZARD
cause
personal
Puron (R-410a)
refrigerant
systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment
or components
on Puron refrigerant
equipment.
IMPORTANT:
The
gasketing
critical
for a watertight
shown
in Fig. 1. Improperly
of the unit
seal. Install
applied
FIRE,EXPLOSION
HAZARD
Failure
tofollowthiswarning
couldresult
inpersonal
injury,
death
and/or
property
damage.
Improper
installation,
adjustment,
alteration,
service,
or
maintenance
cancause
property
damage,
personal
inju_,orlossof life.Refer
totheUser's
Information
Manual
provided
withthisunitformore
details.
Donotstore
orusegasoline
orother
flammable
vapors
andliquids
inthevicinityofthisoranyother
appliance.
leaks and poor unit performance.
roof curb.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical
switch, or use any
phone in your building.
3. IMMEDIATELY
call your gas supplier
from a
neighbor's
phone.
Follow
the
gas
supplier's
instructions.
data. File any claim with transportation
4. If you cannot
reach
your
gas supplier,
Alternate
When
minimum
of 3 equally
Step 2 --Rig
Inspect
spaced
limits are
compressor
Units
could cause
closing
have
damage.
DAMAGE
HAZARD
in personal
and lifting.
Use wooden
ambient
operating
near
limits.
If
top skid or spreader
must
vents
unit
operation,
be
provided
rigging
in Fig.
with
instructions
shipped
with this accessory.
(See Fig. 1.) Install
insulation,
cant strips, roofing,
and counter flashing as shown.
Ductwork can be installed to roof curb before unit is set in place.
Ductwork must be attached to curb and not to the unit. Curb must
be level. This is necessary
to permit
unit drain to function
properly. Unit leveling tolerance is -+ 1/16 in. per linear ft in an 5,
direction. Refer to Accessory
Roof Curb Installation
Instructions
for additional information
as required. When accessory roof curb
is used, unit may be installed on class A. B, or C roof covering
material. Carrier roof curb accessories
are for flat roofs or slab
or other
and above unit to provide
materials,
proper airflow,
location.
sources
Do not locate
air
of contaminated
adequate
combustion
in accordance
with
inlets
air. For
and ventilation
Section
5.3
air
(Air
for
Code,
Although
higher
unit is weatherproof,
guard
against
water from
and overhangs.
mechanical
any opening
in accordance
Unit
Combustion
and Ventilation)
of the National
Fuel Gas
ANSI Z223.1 (American National Standards Institute).
Locate
curb
information.
per Fig. 3. around
from combustible
exhaust
level runoff
Unit Support
roof
additional
Do not install unit in an indoor
Roof Curb
mounting.
result
must be in place when rigging
Maintain clearance,
minimum
distance
and service access.
the gas valve(s).
high
accessory
1 for physical
Positioning
INSTALLATION
or install
See Table
agency.
Rigging holes are provided in the unit base rails as shown
2. Refer to rigging instructions on unit.
restart the compressor.
Assemble
on
and Place Unit
direction.
See Fig. 2 for
weight is shown in Fig. 2.
death and/or
exceeded,
the units will automatically
lock the
out of operation.
Manual reset will be required
to
Step 1 --Provide
in air
bars over unit to prevent sling or cable damage.
Rollers may be
used to move unit across a roof. Level by using unit rail as a
reference:
leveling tolerance
is -+ 1/16 in. per linear fl in any
proper
IMPORTANT:
can also result
4-in. x 4-in. pads on each side.
Failure to follow this warning could
injury, death and property damage.
call the fire
HAZARD
by manually
gasket
install unit on a noncombustible
unit for transportation
PROPERTY
Disconnect
gas piping from unit when leak testing at
pressure greater than 1/2 psig. Pressures greater than 1/2
psig will cause gas valve damage resulting in hazardous
condition.
If gas valve is subjected to pressure greater
than 1/2 psig, it must be replaced before use. When
pressure testing field-supplied
gas piping at pressures of
1/2 psig or less, a unit connected
to such piping must
be isolated
is
as
Unit Support
a curb cannot be used.
All panels
Failure to follow this warning
property damage.
to the roof
Do not slide unit to position
Do not drop unit; keep upright.
EXPLOSION
curb
with the roof curb
surface. Support unit with sleepers, using unit curb support area.
If sleepers cannot be used. support long sides of unit with a
department.
FIRE,
gasket
through
draft system
flue assembly
which combustion
at least 4 ft from
products
could
enter the
building, and at least 4 ft from any adjacent building (or per local
codes). When unit is located adjacent to public walkways,
flue
assembly must be at least 7 ft above grade. Locate unit at least 10
ft away from adjacent units.
Roof Mount
Check building
codes for weight distribution
operating weight is shown in Table 1.
requirements.
Unit
UNIT
BACK
AT
]_
SIZEi
ROOF CURB
_[[127]
BASK
48PGl'6
I"
2
i
2"_3561
"A"
0" [6_0]
CRRPCURBOS_AOG
ACCESSOR_
CRRECURBOSSAOB
[635]
\
:1
UNiT SIZEi
48PG
i
RETURN ENB
i
!6
OASKEI
{SUPPLIED
_NSIDE
[]007
91
MAX CURB LEVELING
2
_
NAL
CO:P,TE R LAS iNG
(r LD S pPLI_O)
[520
9]
_
/ ¸ 4
I/B '¸
4
/
3/4 ¸
B I_
iB34 71
_
O S_¸
SUPPLY A_R
ITDR}
OPENING
_
SHIPPED UNASSE_DLED
CANT STR P
(FFIELO
[LD SgPPLi
DI
_
S PLIED
_
ROOFING MA ERIA
810
269
OUT
BOLT iIEADS TO BE OR INSiB£ OF FLANGE
CLEARANCE IS [_ii g O7116"
TYP ALL CORNERS
DIMENSIONS
IN [
] ARE IN M_LLIMETERS
ROOF CURB IS GALVANIZED SIEEi
_OOr NG FEL
0 ¸3¸'
[76 2]
CRGASSDRBBBAOO
C_RB_
TOLERAS,CES
_
_
! !" NPT
NOTES
I ROOF CURB ACCESSORY iS
_IT_
CONNECIOR
ACCESSORY
PACKAGE
'C"
AiiACR DUCTWORK i0 CBRB
REST ON CURB)
SERVICE
CLEARANCE
(_LANGES ON OUCT
4 F_ ON EACH SIDE
GAS SERVICE RLME IS PAR/ OF _ SEPARA?ELY
S_IPPDD ACCESSORY PACKAGE
1
_
1731
GAS SERVICE PLATE CAN BE USED _IT_
ACCESSOR_ RODE CURB
3}
EITHER
J
J
!J
i
T
ff
__
O
L
0
AiR FLOW
/
ELECTRICA_
SERVICE
_4B.
i406 Bl
OUTSIDE
RETURN i
AiR
i_ ¸- I_
8 ¸'
[587 B]
}71/B'
[494
SE BETAiE_
DEAIL
DIRECTION
6 /8'
2
SE
II_
RIGID ]NSUL#TIOR
O 2 7!8
[1081
_\\
7]
ALT GAS SERVICE
O 2 3_8'
\
\W
OPDNING
FOR
IB_ B]
37
1/_'
[IO98 87
O o 1/41
o o l/B,,
_Eb_BR_ICE
_C'
DETAIL
D
SCALE /:5
DEAi
SCALE
18 GAUGE STEEL> _IT_ i/B
INCH NEOPRENE INSBiATION
SEE NODE 7 _ B
SERVICE
l:S
C06228
Fig. 1 -
Roof Curb Details
Table
l--Physical
Data
BASE UNIT 48RG
NOMINAL
16
CAPACITY
OPERATING
Unit*
(Tons)
WEIGHT
15
(Ib)
1895
Economizer
Ver[ica_
Horizontal
149
149
Humidi-MiZer
Roof Curb
14-in
TM
System
64
24O
24qn
36O
COMPRESSOR
Fully Hermetic
5
Quantity
Oil Type
Sys A
Sys B
Sys C
Number
of Refrigerant
Oil (oz)
Sys A
Sys B
Circuits
Device
Operating
Charge
Copeland
3MA
Copeland
Copeland
3
3MA
3MA
66
68
66
Sys C
REFRIGERANT
TYPE
Expansion
R-4t 0A (Puron®
(Ib) Sys A
15.5
15.0
15.0
Charge Total All Systems
(tb)
45.5
Unit with Humidi-MiZer
System
Operating Charge (Ib) Sys A
Total Ati Systems
CONDENSER
Sys B
18.8
18.7
Sys C
18.8
(Ib)
54.3
COIL
Enhanced
Copper
Tubes, Aluminum
Condenser
A (Outer)
Rows.Fins/in
28.6
Condenser
B (Inner)
Rows.Fins/in
217
30.2
Face Area (sq ft)
HumidFMiZer
Coi_
Copper
Fins/in
Face Area (sq ft)
CONDENSER
FAN
Quantity
Nominal
Motor
Size
Enhanced
22.2
1. 15x15, 1 ..12x12
1. 15x15, 1 ..12x12
Belt
High
Cfm
High
Low
Frame Size
Mid-Low
High
Low
Fan Rpm Range
Mid-Low
High
Motor
Bearing Type
Motor
Pulley Pitch Diameter
Pulley Pitch Diameter
Low
Max (in.)
High
Low
Mid-Low
Fan Pulley Pitch Diameter
High
Low
(in.)
Mid-Low
Motor Shaft Diameter
(in)
High
Low
Mid-Low
Pitch Length (in)
Center Line Distance
7t0-
Min
(in)
Max
(in)
4.2
4.2
4.2
5.2
5.2
6.2
10.2
8.5
8.5
7/8
7/8
47.8
43.8
High
Low
High
Low
Mid-Low
High
879
872-1066
1068-1280
Mid-Low
Mid-Low
Pulley
58
56
S215T
t3!_
49.3
Mid-Low
Center Line Distance
75
High
Low
High
Low
Belt. Type
Pulley
57
525
Ball
Min (in.)
Mid-Low
Belt.
Belt
Belt
8000
Low
Bhp
Mid-Low
Nominal
Type, Belt Drive
1. 15x15, 1 ..12x12
Mid-Low
High
Low
Continuous
Double-Wavy
Low
Mid-Low
Maximum
Copper Tubes, A_uminum
315
Centrifugal
(in)
Type Drive
Nominal
Fins
_/3
1100
Fins/in.
Quantity
Lanced
12,500
Face Area (sq ft)
EVAPORATOR
FAN
Motor
Tubes with Atuminum
1 17
22.2
Propeller
324
Diameter
(in)
Cfm {Total, all fans)
Nominal Rpm
EVAPORATOR
COIL
Motor
Enhanced
Hp
Rows
Lanced Fins, Face Split
217
Face Area (sq ft)
Rows
Refrigerant)
TXV
Sys B
Sys C
Operating
Scroll
AX
BX
BX
14.2
18.8
8.6
10.8
14.2
12
Fins, Face Sp_it
Table
1 -- Physical
Data (cont)
BASE UNIT 48PG
Speed
16
Change
Movab{e
(rpm)
Low
34
Mid-Low
41
41
High
Low
Turns
5
Mid-Low
Factory
Pulley Setting
5
5
High
Low
(rpm)
812
Mid-Low
983
1191
High
Fan Shaft Diameter
GAS HEAT SECTION
Rollout Switch
at Rutiey (in.)
Open Temperature
Closed
13/16
(F)
Temperature
Low
195
Med
195
195
High
Low
(F)
115
Med
115
115
High
Gas Input (Btuh)
Stage l/Stage
2
PGD/L
PGE/M
176,000/220,000
248,000/310,000
320,000/400,000
PGF/N
Burner Orifice Diameter
Natural Gas
Liquid
(in..drill
size)t
Std
AIt
Propane
Thermostat
Heat Anticipator
Setting
0.1285.30
0.1015.88
(amps)
First Stage
14
Second Stage
Manifo{d Pressure
Natural Gas
20
(in wg)
Std
AIt
Liquid Propane
Gas Valve Quantity
Gas Supply Pressure
30
80
1
Range (in wg)
5.0-13.0
Field Gas Connection
Size (in.)
HIGH-PRESSURE
SWITCH (psig)
Cutout
3/4
660 + 10
Reset (Auto.)
RETURN-AIR
FILTERS
Quantity
Size
505 + 20
Throwaway
8 .20x20x2
(in)
LEGEND
TXV
*Aluminum
tFor
Thermostatic Expansion Valve
Evaporator
applications
Coil/Aluminum
Condenser
Coil.
less than 2000 ft elevation.
Hook
rigging
shackles
DetailA.
Holes
in base
center
prevent
of
gravity.
rigging
UNIT
SIZE
16
Use
straps
A
in,
100.4
through
rails
wooden
top
from
damaging
B
mm
2550
in.
36 54
holes
in
centered
are
skid,
C
mm
914 1371
in,
52.4
base
rail,
around
when
unit.
rigging,
D
mm
1331
in.
5%0
as
the
E
mm
1295
in.
350
shown
unit
to
MAX,
mm
889
in
Ib
1959
WEIGHT
k_
890
(;06229
Fig. 2 - 48PG
Rigging
Label
Installation
Onto
Curb
The 48PG units are designed to fit on the accessory full perimeter
curb. Correct placement
of the unit onto the curb is critical to
operating
performance.
To aid in correct positioning,
place unit
on roof curb to maintain 1/4-in. gap between the inside of rail and
roof curb on long sides and a l/2-in, gap between the inside of rail
and roof curb on both duct and condenser
ends.
and 3, to assure proper duct opening alignment.
NOTE:
Before
connection
Condensate
UNIT
positioning
Refer to Fig. 1
unit on curb. make sure bottom
drain
plug is tight. See Step 6 -- Install External Trap for
Drain concerning
bottom drain connection plug.
DAMAGE
this
caution
may
result
cause
equipment
For vertical supply and return units, tools or parts could
drop into ductwork
and cause an injury.
Install a
90-degree
turn in the return ductwork between the unit
and the conditioned
space. If a 90-degree
elbow cannot
be installed,
then a grille of sufficient
strength and
density
should be installed
to prevent
objects from
falling into the conditioned
space.
Applications
Fabricate
all external
flashing
Ductwork
ductwork,
and mastic
ordering, the unit will be shipped withe the vertical duct openings
blocked off from the factory, ready for side supply installation.
If
the horizontal
supply/return
option
ordering the unit, a field-installed
convert
joints,
and building
Insulate
and
and roof
in accordance
with
Ducts
passing
through
an unconditioned
insulated and covered with a vapor barrier.
space
clearance
is not required
around
ductwork.
the vertical
NOTE:
Follow
was not specified at time of
accessory
kit is required
to
unit into a horizontal
instructions
provided
of the
applicable
prior to
available.
placing the
A minimum
must
any obstruction
to install the duct block-off
ductwork to horizontal duct flange connections
openings
be
Cabinet
duct block-off
supply
Step 5 --Install
configuration.
with accessory
Installation
If a plenum return is used on a vertical unit, the return should be
ducted through
the roof deck to comply with applicable
fire
codes.
A minimum
could
INJURY
Horizontal
units are shipped with an outer panel that allows for
side by side horizontal
duct connections.
If specified
during
On vertical
units, secure all ducts to roof curb
structure.
Do not connect
ducm'ork
to unit.
with counter
codes.
PERSONAL
to follow this warning
and/or personal injury.
Horizontal
in equipment
Do not slide unit to position when it is sitting on the curb.
Curb gasketing
material may be damaged
and leaks may
result.
weatherproof
Failure
damage
AND
HAZARD
Failure to follow
damage.
Step 3 --Field
UNIT
DAMAGE
HAZARD
covers
should
kit.
be completed
unit unless sufficient
side
of 66 in. is required between
clearance
is
the unit and
covers.
Install
on side of unit.
Flue Hood and Inlet Hood
Flue hood (smaller hood), inlet hood (larger hood), and screens
are shipped inside the unit in the gas section. To install, open the
heat section door. The flue hood is attached to the heat section
return-air static pressure (a negative condition)
shall not exceed
0.35 in. wg with economizer
or 0.45 in. wg without economizer.
panel from the outside
These
The inlet hood is installed by inserting the hood through the back
of the heat panel. Attach the hood by inserting
the screws
units
are designed
for a minimum
continuous
return-air
temperature
in heating of 50°F (dry bulb), or an intermittent
operation
down to 45°F (dry bulb), such as when used with a
night set-back thermostat.
To
operate
outdoor-air
stages of
at lower
return-air
temperatures,
temperature
control must
heat when the temperature
a field-supplied
be used to initiate both
is below
45°F. Indoor
comfort may be compromised
when these lower air temperatures
are used with insufficient heating temperature
rise.
Step 4 --Make
Vertical
Unit Duct Connections
Supply/Return
Configuration
Unit is shipped in vertical supply/return
configuration.
Ductwork
openings are shown in Fig. 1 and 3. Attach the ductwork
to the
roof curb. Do not attach duct directly
to the unit.
using the screws provided.
(See Fig. 4 and
5.)
provided through
the intake hood.
NOTE:
When
the combustion
the clearance
properly
installed,
fan housing.
holes
in the heat panel
and into
the flue hood will line up with
(See Fig. 6.)
_OIES
I
WE:6HTS SHOWN ARE FOR 48PG I_I ilEAT) UN[T
W:TH ALU_[NU_ CO:LSAND
STANDARR DRIVE
EOR WRIGHTS OR OPTIONAL [OU:PMEN:¸ CONSULT
PRODUCT DAIA BOOK
R
BO NOT LOCATE ADJACENT UNITS W[TIi ELUE B[SCHARGE
EARING ECO_ONIZER [I_[E:
R 5M6"
{135 O]
3
_INIMUN CLSARANCE ([ORAL CODES OR JUSISO[CTIONS MAT PRRVAI])
:RONT 48 INCHES TO CO_RUST:CL_ SURFACES [18 [NC_ES _RN
US:NG ACCESSORY ELD[ RiSCHARGR REFLECTOR)¸
_HEC ROT USINO ROOf CURB I: I_CH} RO[lO_ OF BASE RAN lO
CO_BUST:B[R RDREACES
_HER NO: USINB ROOF CURB {0 INCHES1 i0 ROTTO_ OF BASE RA:L
R:BRT S:D[FRBNT
AND _AC_ SIDES 136 :NCiIESI :OR PROPER
CONDENSER A:RFEOW
d OVERHEAR 160 INCHES)iO ARSUR_ PRORER CONDENSER AIRFLOW
_ REIWREN UN[_S, CONIROL BOX SIDE, 4Z IN PER NEC
[ BETWI:_N UN[i A_B UNOROUNCED SURFACE CONTROL BOX SERE
136 INCHES PER NEC)
g RETW[RN UNIT ANO BROCK BE RBNCRETR _ALI ANR OTHER
GROUN_ER SURFACES CONTROL _OX S:RE 142 INRFRSI PER NEC
_ CLEARANCE IN FRONT OT INDOOR _0iOR ACCESS FOR BLOWER SLED
RfMBVAL 8_ _
: CIRARANC[ fOR CONPLRTE CONDENSATE PAN RR_OVAL 7"8
_ ON UNITS WITH _CONO_[RER AL{BW 4"0" IRO_ LEfl SlOE
EOR SERVICE ACCESS TO ECONOMIZER¸
m IIORIZONTA[ SUPPL¥ AND REtURN,TO INCHES)
b
4
DOWN SilOT DUCTS RESIGNED TO BR ATTACHE_ TO ACCESSORT
ROOF CRRO ONLY¸ if UNII :S MOUNI[_ SlOE SUPPLY [[
[S RRCOMMRNDED THE _UCIS _USI BE SDPPORIED BY
CROSS BRACES AS RONE ON ACCESSORY ROOF CURB
R
D:_ENS:ONS IN I
_
_IIIL T_I[E_CERI:ON OT CLEARANCE FOR :_[ CO_OENSER COIL,
COM_DSTI_IE SURTACRS AND TI4EDAMPER/POWER EXHAUST AS
STATRD IN NOTR _R A REMOVAC[{ FENCE OR _ARR[CADR
REQUIRES NO CleARANCE
f
OIMENS:ONS ARE iROM OUISIOE OE CASE RAIL
ALIO_ O ¸ 5/16 [81 ON EACH SlOE FOR tOP COVER DRIP EBGR
8
UNITS _AY BE [NS:AIIED ON CO_B_ST[BLE E[OORS _AR_ IRO_
CLASS A,B,C ROOF COVERING MATERIAL :F SET ON CASE RAILS¸
ARE [N _ILI[_ETE£S OR _ILOGRAMS
4" 5 IWl_"
1_363 51
797/8"
[86141
:"
I
1:
CONBENSAIE
I_ARRERS
ROVER
@[59 81
POWRRRUP£17
_NOR_OUT
(THRU CURB}
R
R 3/4'
65/8"
{168 O}
[6DO 0}
TTR
IINCL@E8
WITH UNTil
53/4'
11
CENTER O_ GRAVIIT
REAR
134993]
Im4_I_[RECT[ON
55/S"
[4480]r-
OF A[R FIO_
£
4 1/2"
{114 7]_
4 9/16"
l
9 1/4"
[2568 O]
TYR
1 3//G"
6 1/4"
[/586]_
[30
8i
l
8114"
[513
8]
/ //_
{18S 61
ACCESS DOOR
_
_
15
_/611
4'
i
l'flP
gg_
[380
R
............
............. CONIT{NSER COlE
8]
;OO
/_'f
!'3/16'<
i
:::=::::::3"
_
Z 1R/16 ¸¸
[:2934]
OOi)
[<,OR
T:7/C_
'
'
?
6 7/8'
[1_4/173]
RETURN
7 13//6"
[183 3]_
R RIB"
[5_6]
SUPPIf
_N
AT S CTION
:7P
R 1R/T6'
[2234 l]
.....................
[NSIOE RAILS
LEFT SIDE
BAROMRTRIC REIEIE
(:NCLUDED W:TH UNIT)
POWER _XBAUST
_POWER
SUPPLY
ORERAIING POS:FION
ACCESS COVER
(OPiION)
ACCRSS DOOR
L A:R
C 1 51}6'
......................................... [R7Z7 O]
:NSIOE RAILS
AC(ESS
DOOR
RICHT SIDE
FRONT
(107056
Fig. 3 - Base
Unit Dimensions
FLUE HOOD
When
INLET HOOD
plug
°1
using
(red)
the standard
in the
side drain
alternate
bottom
installing the unit. (See Fig. 7.)
To use the bottom drain connection
connection,
connection
make
sure the
is tight
before
for a roof curb installation.
relocate
the factory-installed
plug
(red)
from the bottom
connection
to the side connection.
A 1/2-in. socket extension can
be used to remove the plug. (See Fig. 7.) The piping for the
condensate
drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate
drainage.
Install a trap at least 4-in. deep and protect against freeze-up. If
drain line is installed downstream
from the external trap, pitch the
GAS SECTION
ACCESS DOOR
C06230
Fig. 4 -
Flue and Inlet Hood
Locations
line away from the unit at 1 in. per 10 ft of run. Do not use a pipe
size smaller than the unit connection
(3/4-in.). (See Fig. 8 and 9.)
The 48PG units are provided with a removable
condensate
pan
for ease of cleaning.
It is recommended
that a union be placed
between the unit and condensate
drainage to ease the removal of
the pan during servicing. Adequate clearance should be allowed if
Drain
The unit's
3/4-in. condensate
Step
--Install
bottom 6and
side of
determine
drain connections
are located
on the
theExternal
unit. Unit Trap
dischargefor Condensate
connections
do
the use of drain
can be used with vertical
connections:
applications.
either
drain
not
connection
removal of condensate
condensate
pan access
removal.
pan is required.
Allow 64-in. between
panel and any obstruction
for complete
See Fig. 3 for locations.
ECON( ,MIZER HOODS
CONDENSER
COIL ACCESS
PANEL
OUTDOOR
AIR
SCREENS
ELECTRIC
HEAT ACCESS
PANEL
BAROMETRIC
RELIEF DAMPER
HOODS
ELECTRICAL"
OPTIONS
PANEL
FILTER
ACCESS DOOR
BASEPAN
CONTROL
CONNECTIONS
AND
ACCESS
ACCESS
PANEL
BOX
COMPRESSOR
DOOR
C06309
Fig. 5 -
Panel and Filter
Locations
Table
HEAT
EXCHANGER
SECTION
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
30
31
31
31
31
32
32
32
35
36
37
38
39
GAS
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
1-Orifices available through your Carrier dealer.
COMBUSTION
MAIN
FAN
BURNER
SECTION
HOUSING
Table
Gas Heating
3--Orifice
Quantity
ORIFICE
QUANTITY
UNIT
C06232
Fig. 6 - Typical
Compensation*
NATURAL GAS ORIFICE1"
30
MOTOR
MAIN
2--Altitude
ELEVATION (ft)
0-1,999
Low Heat (48PGD/L)
Medium Heat (48PGE/M)
High Heat (48PGF/N)
Section
Conversion
SIDEDRAIN
PLUG
to Propane
5
7
9
Gas
Use accesso_
propane gas conversion
kit when converting
this
unit for use with propane fuel usage for elevations up to 7000 ft.
For elevations
correct orifice
above 7000 ft, refer to Table 4 to identify the
size for the elevation.
See Table 3 for the number
of orifices required for each unit size. Purchase these orifices from
your local Carrier
dealer. Follow
instructions
in accesso_
Installation Instructions
to install the correct orifices.
Table
222................
ELEVATION
BOTTOM
DRAIN
PLUG
C06233
Fig. 7 -
Step 7 --Orifice
Condensate
Drain
Pan
Change
This unit is factory assembled for heating operation using natural
gas at an elevation from sea level to 2000 ft. This unit uses orifice
type LH32RFnnn,
drill size diameter
High
Elevation
where "nnn" indicates the orifice
in thousands of an inch.
(Above
size based
on
2000 ft)
Use accessory
high altitude kit when installing
this unit at an
elevation of 2000 to 7000 ft. For elevations
above 7000 ft, refer
to Table 2 to identify the correct orifice size for the elevation. See
Table 3 for the number
of orifices required for each unit size.
Purchase
these orifices from your local Carrier
instructions
in accessory
Installation
Instructions
correct orifices.
dealer. Follow
to install the
0-1,999
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
4--Propane
(ft)
Gas Conversion*
PROPANE GAS
ORIFICE1"
38
40
40
41
41
42
42
43
43
44
44
45
46
47
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher attitudes. Includes a 4% input reduction per each 1000 ft.
1-Orifices available through your Carrier dealer.
Step 8 --Install
Gas Piping
Step 9 --Make
Connections
(For more details, refer to the Controls,
troubleshooting
manual)
year and addendum
Canada,
installation
Field Power
CAN1.B149.1
burning
Support
example,
Z223.1A-latest
year entitled
must
be
in
accordance
and
CAN1.B149.2
installation
HFGC.
with
codes
for
In
the
gas piping
as shown
in the table in Fig.
a 3/4-in. gas pipe must have one field-fabricated
Install field-supplied
manual
gas shutoff
have a
valve with a l/8-in.
NPT
piping must include
Install a field-supplied
and union.
(See
Fig.
and
units are factory wired for 230-v power supply. If
unit is to be connected
to a 208-v power supply,
on the primary
side of the transformer.
Refer to unit label diagram
provided
at unit. The pressure tap is
to the gas valve. Field gas
sediment
trap
gas regulator.
terminal
pipe guide
pressure tap for test gage connection
located on the gas manifold,
adjacent
operation,
transformers
(TRAN1 and TRAN2)
must be rewired by moving
the black wire with the l/4-in, female quick connect from the
230-volt
connection
and moving
to the 200-volt
l/4-in, male
10. For
support
an 18-ft long gas pipe would
minimum of 3 support beams. See Fig. 10 for typical
and locations of external manual gas shutoff valve.
start-up,
Supply
All 208/230-v
the 208/230-v
gas
appliances.
beam every 8 ft. Therefore.
n
Electrical
Unit is equipped for use with natural gas. Refer to local building
codes, or in the absence of local codes, to ANSI Z223.1-1atest
for field
Laboratories)
When
wire
approved
installing
for additional
connections.
information.
Use
copper/aluminum
units,
provide
UL
Leads
connector.
disconnect
per
NEC
(National
Electrical
Code) Article
440 or local codes. For non-fused
disconnects,
size the disconnect
according
to the sizing data
provided in the electrical data tables. If a fused disconnect is used,
determine
the minimum
size for the switch
based
on the
11.)
disconnect
sizing data provided in the electrical data tables
then coordinate the disconnect
housing size to accommodate
UNIT
DAMAGE
HAZARD
AND
PERSONAL
INJURY
Failure to follow this warning could result in damage
equipment and/or personal injury.
Maximum
Natural
gas pressure
not be less than 5.0 in. wg or greater
sizes.
to
at unit gas connection
Overcurrent
Protection
on the unit informative
plate.
wiring must comply with NEC
(MOCP)
and
the
device size as marked
(See Tables 5 and 6.) All field
and local codes. Size wire based
on MCA (Minimum
Circuit Amps) on the unit informative plate.
See Fig. 12 for power wiring connection
to the unit leads and
Do not pressure test gas supply while connected to unit.
Always
disconnect
union
before
servicing.
High
pressures
can cause gas valve damage resulting
in a
hazardous condition.
IMPORTANT:
are
(Underwriters
equipment
Route
ground.
power
and ground
lines through
control
box end panel or
unit basepan (see Fig. 3) to connections
as shown on unit wiring
diagram and Fig. 12. Factory leads may be wired directly to the
disconnect.
must
than 13.0 in. wg for all heat
Size gas-supply
piping for 0.5-in. wg maximum
pressure
Do not use supply pipe smaller than unit gas connection.
drop.
UNIT
DAMAGE
HAZARD
Failure
to follow
this caution
may result in damage
to unit.
The correct power phasing is critical to the operation
of the
scroll compressors.
An incorrect phasing will result in an
alarm being generated
and compressor
operation
lockout.
Should this occur, power phase correction
must be made to
the incoming power.
OPTIONALUNIONS
TOALLOWFORCONDENSATE
_
PANREMOVAL
_
CONDENSATE
PAN ACCESS
PANEL
C06234
Fig. 8 -
External
Trap
for Condensate
10
Drain
C.A1
Jm[
MINIMUM
PITCH
_-'_t.
I
I
--
FIELD
_
FACTOR
POWER
I
zLU
Z Z
OCt
©LU
£3
I
SEE
>/
WIR!_G
I
I
I
NOTE
I I _
WIRING ff:_
r
EQUIP GND
I
_..ROOF
C06237
CURB
DRAINPLUG
Fig. 12 - Field
Power Wiring
Connections
NOTE: Trap should be deep enough to offset maximum unit static difference
A 4-in. trap is recommended.
n
C06291
Fig. 9 -
Condensate
F
Drain
Piping
X
9" MINIMUM
CLEARANCE
SHuToPANEL
REMOVAL
MANUAL
GAS
_
FF VALVE*
BASE
ELECTRICAL
*,-{
GAS
GAS
minimize
I
--
Field
National
*Field
supplied.
NOTE:
Follow
all
Fuel
local
Gas
Code
P,PE
NOMINAL STIEEL
DIAMETER
OF
SPACING
OF SUPPOBTS
X DIMENSION
(ft)
Unit failure
3/4
Or
1/2
11/4
Or
1
8
_
larger
coud result
in electrical
injury
must
conform
field
if an electrical
fault
should
of electrical wire or conduit
ground
when
installed
in
electrical codes. Do not use
ground.
to temperature
wiring
must
limitations
comply
with
for type
NEC
and local
Operating
voltage to compressor
nmst be within voltage range
indicated on unit nameplate.
Voltages between
phases must be
balanced within 2%.
SUPPORTS
]{
(in.)
wiring
"T" wire. All
requirements.
codes.
SPACING
personal
occur. This may consist
approved
for electrical
accordance
with existing
gas piping as an electrical
LEGEND
NFGC
AND FIRE HAZARD
The cabinet MUST have an uninterrupted
or unbroken
ground according to NEC ANSI/NFPA
70-2002
and
Canadian Electrical (:ode CSA C22.1 or local codes to
.d
REGULATOR_
SHOCK
Failure to follow this warning
shock, fire. or death.
ROOF
DRIPCURB
LEG PER NFGC_
FIELD-FABRICATED
SUPPORT*
METER
R__
FROM
Details
as a result
of operation
on improper
excessive
phase imbalance
constitutes
damage to electrical components.
6
10
abuse
line voltage
and
may
or
cause
C06115
Fig. 10 - Gas Piping
Thru-the-Curb
Guide
Service
Field Control
Humidi-MiZer
(With Accessory
Connections)
MANUAL SHUTOFF
(FIELD SUPPLIED) "_
thermostat
accessory.
r'F1
according to the installation
instructions
included with
Locate thermostat
assembly
or space temperature
sensor on a solid interior
average temperature.
SUPPLY
Route
PRESSURETAP
(1/8" NPT PLUG)
thermostat
wall in the conditioned
or space temperature
sensor
NOTE:
diagram
insulated
For 50 to 75 ft, use
wire (35°C
For over 75 ft, use
a junction
Set heat anticipator
settings
Fig. 11 - Field Gas Piping
minimum).
minimum).
connected
All wire larger
at the thermostat
box and splice at the thermostat.
as follows:
VOLTAGE
STAGE 1
(Wl) ON
STAGE 1 AND 2
(Wl AND W2) ON
All
0.14
0.20
Settings
may be changed
comfort
for a particular
11
(American
wire (35 °C minimum).
no. 14 AWG insulated
wire (35°C
than no. 18 AWG cannot be directly
and will require
through
on unit
and in Fig. 13 or 14.
no. 16 AWG insulated
C06236
to sense
terminals
as shown
For wire runs up to 50 ft. use no. 18 AWG
Wire Gauge)
'_----- SEDIMENT TRAP
space
cable or equivalent
single leads of colored wire from subbase
conduit into unit to low-voltage
connections
label wiring
_-
TM
Unit can be controlled
with either a Carrier-approved
accessory
thermostat or a Carrier-approved
space temperature
sensor. Install
_'_
LINIT UNO__N
Wiring (Units Without Optional
Adaptive Dehumidification
System)
slightly
installation.
to provide
a greater
degree
of
:::
):
NOTE:
:,
For wire runs up to 50 ft, use no. 18 AWG
Wire Gauge)
insulated
no. 16 AWG insulated
For 50 to 75 ft, use
wire (35°C
For over 75 ft, use
minimum).
no. 14 AWG insulated
wire (35"_C minimum).
than no. 18 AWG cannot be directly connected
and will require
a junction
Set heat anticipator
::C('
(American
wire (35 °C minimum).
settings
All wire larger
at the thermostat
box and splice at the thermostat
as follows:
T( :: t,,t
C06292
Fig. 13 - Field Control Thermostat
VOLTAGE
Wiring
All
STAGE 1
(Wl) ON
0.14
STAGE 1 AND 2
(Wl AND W2) ON
0.20
T-56 SPT
SEN
Settings may be changed slightly to provide a greater degree of
comfort for a particular installation.
Humidity Control
SET
Unit can be controlled with either a Carrier accessory
Thermidistat device or a Carrier-approved accessory humidistat
(switch output). The input for an accessory humidity sensor with
4 to 20 mA output is another option available when an
economizer board is installed. Install the humidity control device
according to the installation instructions included with the
accessory. Locate the device on a solid interior wall in the
conditioned space to sense average humidity. Carrier Thermidistat
device wiring connections are shown in Fig. 15. General
humidistat
wiring
connections
are shown
in Fig. 16.
Configuration of the unit control is required to specify the control
input type before unit operation. Refer to the controls, start-up,
operation and troubleshooting manual for configuration.
JUMPER
SPT -- Space Temperature Sensor
C06239
Fig. 14 -
Field Control
Sensor
Space
Temperature
Wiring
Units with the Humidi-MiZer option receive a discrete input from
a field-installed device (such as from the Carrier humidi-stat or
Thermidistat device). The discrete input is connected to the TB1
terminal strip points labeled Humidistat 1 and 2. As this is a
discrete input, one of the connection points is for power to the
switch and the other is the return path. (See Fig. 16.)
A space relative humidity sensor input (SP.RH) is only available
if an economizer board (ECB) is installed in the unit and then the
sensor can be connected to the OAQ point TB1-4. (See Fig. 16.)
This input is used instead of the discrete humidistat or
thermidistat inputs. The input controls the Humidi-MiZer using
the 4-20mA as percent humidity. The relative humidity value
(measured by the relative humidity sensor) can be displayed on
the Scrolling Marquee, in the space through a System PiloU"
device, or can be read by other CCN devices where it can be used
to perform more advanced functions. The humidity sensor must
be configured correctly; refer to the Controls, start-up, operation,
and troubleshooting manual for details.
If the customer also wishes to install a smoke detector into a
Humidi-MiZer
equipped
48PG unit. the fire shutdown
connection points are on Plug PL-19, located in the economizer
section. See the unit wiring schematic for wiring. For third-party
smoke detector, refer to Fig. 17.
Point 19-3 is the 24 vac power source for the detector. Point 19-4
is 24 vac power for the indoor fan contactor control. Point 19-5 is
the 24 vac signal input for fire shutdown. If an immediate fan
shutdown is desired, install a normally closed contactor between
19-3 and 19-4.
Field Control Wiring (Units With Optional Humidi-MiZer
Adaptive Dehumidification System)
Units require temperature control inputs for cooling and heating
operation and humidity control inputs for Humidi-MiZer
operation.
TM
Temperature Control
The unit can be controlled with either a Carrier-approved space
temperature sensor, a Carrier accessory Thermidistat
device, or
a Carrier-approved accessory thermostat. Install the temperature
control device according to the installation instructions included
with the accessory. Locate the device on a solid interior wall in
the conditioned space to sense average temperature. Carrier space
temperature sensor wiring connections are shown in Fig. 14.
General thermostat field control wiring connections are shown in
Fig. 13. Carrier Thermidistat device wiring connections are
shown in Fig. 15. Configuration of the unit control is required to
specify the control input type before unit operation.
TM
Route thermostat or space temperature sensor cable or equivalent
single leads of colored wire from subbase terminals through
conduit into unit to low-voltage connections as shown on unit
label wiring diagram and in Fig. 13-15.
THERMIDISTAT
DUE c DDD
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
TBI
RUMIDISTAT
ROOFTOP
UNIT
C07055
Fig. 15 - Field Control Thermidistat
Wiring
12
I I
I I
J
I
OR
HUMIDITY
SENSOR
OR
HUMIDISTAT
C07045
Fig. 16 -
Humidi-MiZer
Low-Voltage
Terminal
Strip
3. The
48PG_
Humldi;-MiZer
RTU
Pk19
- Humidity
Sensor/Humidistat
barometric
_[-:
@
(SPOT)
; _ )-
N
should
Smoke
Detector
Outdoor-Air
the following
procedure
Hoods
relief hoods
of
2. Remove
complete
assembly
from
screws
relief/power
Discard
that
secure
exhaust
or recycle wooden
the
in the
hoods
to
the
from
economizer
panel.
exhaust
hood on the
panel. Secure hood to
Step 2. Repeat
for second
Rotate hood
hood until
the bent
until hood
top flange of the
flange
on the
is flush with the
(See Fig. 19 and 21.)
screws
securing
clip on top of the flange
of each
form Step 1. (See Fig. 19.)
Step 11 --Install
All Accessories
After all of the factory-installed
options have been adjusted,
install all field-installed
accessories.
Refer to the accessory
installation
condenser
economizer
saved
panel by rotating
hood
engages
instructions
Step 12 --Configure
the
barometric
railing.
Slide
operation.
the flange and letting filter drop behind bracket holding
barometric
relief hoods.
Repeat for second hood. Install
baffle between the outdoor air hoods with screws saved
condenser
section under the slanted cnil fnr shipping. (See
Fig. 18.) Barometric
relief/power
exhaust
hoods
are
shipped inside of economizer
hoods. Remove screws that
secure the wooden rails of the hood assemblies to the unit.
Save screws.
section.
open during
opening.
Rotate clip 180 degress
and tighten
screw.
Install l-in. filter provided by inserting under the clip on
hoods:
are located
screws
economizer
economizer
6. Loosen
(Units with
to install the outdoor-air
and barometric
the
hole in flange of economizer
panel with left edge of
Hang economizer
hood on the top flange of the
hood.
More information
is available in the third party control section
the controls, start-up, operation, and troubleshooting
manual.
1. Economizer
to
economizer
panel. Hood will support itself from flange.
Align holes in hood with holes in panel and secure
hood
to panel with screws saved from Step 2. Repeat for second
C07046
Perform
secured
(See Fig. 19 and 20.)
5. Align
hood.
Step 10 --Install
Economizer)
be free to swing
4. Hang the barometric
relief/power
mounting flange on the economizer
hood.
Third-Party
are
(See Fig. 19.)
panel with
Fig. 17 -
dampers
economizer
panel for shipping. Remove the screw holding
the barometric
relief damper to the panel for each damper.
Dampers
smoke
Detector'
relief
Wiring
Refer to unit Controls
and
on configuring
wooden
rails. Save screws.
13
controls.
included
with each accessory.
Controls
and Troubleshooting
book
for information
POWER EXHAUST/
BAROMETRIC
POWER
EXHAUST/
BAROMETRIC
RELIEF
MOUNTING
FLANGE
n
WOODEN
Fig. 20 -
Relief/Power
Economizer
Exhaust
Barometric
Hood
C06290
Fig. 18 -
/
/
(;06262
ECONOMIZER
HOOD
RAILS
HOOD
Relief/Power
Exhaust
Flange
and Barometric
Hoods
Shipping
Positions
MOUNTING
FLANGE
ECONOMIZER
HOOD
BAFFLE
J
ECONOMIZER
HOODS
XHAUST/
ECONOMIZER
PANEL
_
BAROMETRIC
i
BAROMETRIC
RELIEF
DAMPER
SCREW
(TYP)
RELIEF
HOODS
C06261
Fig. 19 - Hood
(;06263
Installation
Fig. 21 -
14
Economizer
Flange
Table
5--Electrical
NOMINAL
UNIT
48PG
VOLTAGE
RANGE
POWER
SUPPLY
Min
(V-Ph-Hz)
208/230-3-60
187
COMPRESSOR
No. 1
No. 1
Max
RLA
253
LRA
18.1
Data --
RLA
137
18.1
LRA
137
Units Without
No. 1
RLA
17.6
LRA
123
OFM
FLA
FLA
Qty (ea)
3
Optional
Convenience
COMBUTION
FAN
MOTOR
FLA
1.9
PWR
EXH
FLA*
0.52
3.0
Outlet
460-3-60
414
506
9.0
62
9.0
62
7.7
50
3
1.0
0.30
1.2
575-3-60
518
633
6.8
50
6.8
50
6.1
40
3
0.8
0.24
3.0
LEGEND
Example:
FLA
-
Full Load
HACR
-
Reating,
IFM
-
indoor
LRA
MCA
-
Looked
Rotor Amps
MinimumCircuitAmps
MOCPNEC
-
MaximumOvercurrentProtection
National
E]eotdcal
Code
OFM
-
Outdoor
RLA
-
Rated
*
Power
NOTES:
1
exhaust
MOCP
FLA
LRA
Low
10.2
74.2/74.2
90/90
_'_
Hioh
15.0
19.4
79.0/79.0
83.8/63.8
90/90
100/100
Low
10.2
77.2/77.2
90/90
_'_
High
15.0
82.0/82.0
100/100
19.4
4 8
86.8/66.8
35 8
100/100
40
80/80
86/86
91/91
84/84
89/89
94/94
39
42
44
40
43
46
29
32
34
39
35
38
482/482
491/491
529/529
486/486
495/495
533/533
917
221
940
220
224
243
168
182
197
179
186
201
and
FLA is the
Determine
Fan Motor
sum
or HACR
Never operate
a motor
2%
Use the following
Imbalance
7.4
Hinh
9
Lo_w
4.8
37
45
_
7.4
39.6
45
High
9,7
42
50
Low
_V_dA]
High
2.8
5.6
7.8
26.6
29.4
31.9
30
35
35
35
38.4
7
40
45
8
50
I ow
P 8
P9
_
5.6
32.4
6
35
Hiah
7,6
34,9
40
is 460-3-60
c
of the
breaker
Supply
where
formula
maximum
(AB) 227
(BC) 231
FLA of two
power
exhaust
Canadian
units
may
motors
combination
protective
be fuse
load
device
or circuit
equipfor the
223
227
deviation
from
average
voltage
3 v
4v
(AO) 227
226
Maximum
deviation
1 v
is 4 v
Determine
of voltage
percent
imbalance
4
breaker
% Voltage
imbalance
= 1 go x
Voltage
227
a phase imbalance
to determine
the
in supply
percentage
max voltage
% Voltage
_ni$
Refrigeration
NED requirements
for multimotor
and
Articles
430 and 440), the overcurrent
3-Phase
B
vo{tage
MCA
Fan Motor
(Condenser)
In compliance
with
ment (refer to NEC
Unbalanced
,_
Condltioning
Load Amps
unit shall be fuse
2
Amps
Air
(Evaporator)
Supply
DISCONNECT
SIZE
IFM
FLA
I ow
16
POWER
SUPPLY
IFM
TYPE
voltage
is greater
than
of voltage
imbalance
deviation
from
average
= 1 76%
This
voltage
= 1 go x
amount
IMPORTANT:
average
voltage
utility
15
company
of phase
imbalance
If the supply
immediately
voltage
is satisfactory
phase
as it is below
imbalance
is more
the maximum
than
allowable
2%, contact
your
2%
local
electric
!!
Table
NOMINAL
POWER
SUPPLY
UNIT
48PG
VOLTAGE
RANGE
16
208/230-3-80
187
Data
COMPRESSOR
No. 1
-- Units With
Optional
Convenience
OFM
COMBUTION
FLA
FAN
FLA
MOTOR
RLA LRA RLA LRA RLA LRA Qty (ea)
FLA
No. 1
Min Max
(V-Ph-Hz)
6---Electrical
253
18.1
137
18.1
137
No. 1
17.6
123
3
1.9
PWR
EXH
FLA*
0.52
3,0
16
460-3-80
414
506
9,0
82
9,0
82
7.7
50
3
1.0
0.30
1,2
16
575-8-80
518
883
8,8
50
8.8
50
8.1
40
3
0.8
Outlet
IFM
TYPE
MCA
DISCONNECT
SIZE
MOCP
Low
Mid-Low
10,2
15,0
79.0/79.0
83.8/83.8
90/90
100/100
High
Low
Mid-Low
High
Low
Mid-Low
19,4
10,2
15,0
19,4
4,8
7,4
88.8/88.8
82.0/82.0
86.8/86.8
91.8/91.8
38,0
40,6
100/100
100/100
100/100
100/100
45
45
High
Low
Mid-Low
9,7
4,8
7,4
43,0
39,2
41,8
50
45
50
High
Low
Mid-Low
9,7
2,8
5,6
44,2
28,3
31,1
50
35
35
7,8
2.8
33,6
31,3
40
35
5,6
7,8
34,1
36,6
40
40
High
Low
0.24
3,0
POWER
SUPPLY
IFM
FLA
Mid-Low
Hiqh
FLA
86/
91/
96/
89/
95/
!00/!00
41
44
47
42
45
48
31
34
38
34
37
40
LRA
86
91
98
89
95
487/487
498/496
534/534
491/491
500/500
538/538
219
223
242
222
228
245
170
184
199
174
188
203
Example: Supply vo{tage is 460-3-60
FLA
-
Full Load
HACR
-
Heating,
LEGEND Air
IFM
-
indoor
LRA
MCA
-
Locked
Rotor Amps
MinimumCircuitAmps
MOCPNEC
-
MaximumOvercurrentProtaction
National
Eleotdcal
Code
OFM
-
Outdoor
RLA
-
Rated
*
Power
NOTES:
1
exhaust
and
(Condenser)
FLA. is the
3-Phase
Never operate
a motor
2%
Use the following
sum
of the
FLA of two
power
breaker
Supply
where
formula
Canadian
units
Imbalance
exhaust
may
combination
protective
be fuse
2007 Cartier Corp
Manufacturer
reserves
load
device
or circuit
equipfor the
4
breaker
% Voltage
imbalance
1 go x
227
a phase imbalance
to determine
the
in supply
percentage
voltage
is greater
than
of voltage
imbalance
deviation
from
average
1 76%
This
voltage
1 go x
° 7310 W Morris
amount
IMPORTANT:
average
Copyright
motors
Voltage
max voltage
% Voltage
Determine maximum deviation from average voltage
(AB) 227 223
3v
(BC) 231 227
4v
(AO) 227 226
1v
Maximum deviation is 4 v
Determine percent of voltage imbalance
Fan Motor
NEC requirements
for multimotor
and
Articles
430 and 440), the overcurrent
or HACR
c
Refrigeration
Far) Motor
Load Amps
in compliance
with
ment (refer to NEC
Unbalanced
,_ e
Conditioning
(Evaporator)
unit shall be fuse
2
Amps
St • Indianapolis,
voltage
IN 46231
the right to change_ at any tirne_ specifications
and designs
utility
company
of phase
If the supply
voltage
is satisfactory
phase
as it is below
imbalance
is more
the maximum
than
Catalol_
notice and without
ld
allowable
2%, contact
your
2%
local electric
immediately
]_dnted ta USA
without
imbalance
obligations.
No:48PG-26SI
Replaces:48PG
- 23SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 16 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Jun 29 00:18:07 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools