Air=cooled Generator
tery C
Installation Guidelines

TABLE

Table of Contents

o___F
CONTENTS

Table of Contents ................................inside Front Cover

1.1

Section | - General information ............................... IFC
1.1 Introduction ..........................................................
IF(;

This battery charger supplies a trickle charging current and voltage to maintain
the charge on the generator starting battery inside the generator
enclosure.
The charger will not replenish
a fully discharged
battery. It is intended
to be connected
to a 120VAC generator backed-up
circuit only. If it is not connected
to a generator
backed-up
circuit the battery could go
"dead" while the generator
is running
for extended
periods of time.

1.2

Battery
1.2.1

Charger

Compatibility

Determination
Switch

.................................

1

of Generator/Translkr

Model

Type

........................................

1

Section 2 - Load Shed Transfer Switch
Installation
2.1

Load
2.1.1

Shed

....................................................

Transl_r

Wiring

and

Translkr

Switch

Switch

2.1.2

Wiring

2.1.3

Operational

(RTSS)

Connections

and

Installation

......

2

at the

.............................................

Connections
Testing

2

iNTRODUCTiON

at the

Generator

2
......

.......................................

Figure

2

1.1 -- Charger as Supplied
indicating
input and Output
Wiring

2

Section 3 - Standard or Service Entrance Transfer
Switch installation
3.1

Standard

Transl_r

Entrance

Rated

3.1.1

Wiring

Switch
Transl_r

and

Translkr
Charger

3.1.3

Wiring

3.1.4

Operational

4.1.1

Wiring

and

Translkr
4.1.2

Charger

4.1.3

Wiring

4.1.4

Operational

at the

Generator

4
......

Testing

5
6

................................. 6
at the

AC Input

.............................................

at the

Generator

DC Output

6

..........................................

Connections

3

3

.......................................

Connections

Mounting
and

Service
...........

..........................................

installation

Switch

(RTSE)

3

at the

Connections
Testing

Section 4 - GenReady

or

Installation

.............................................

Mounting
and

(RTSN)
Switch

Connections

Switch

3.1.2

......................................

7
......

.......................................

7
8

Section 5 - Interconnection Diagrams ..........................9
Section 6 - Notes .............................................................16

_

WARNING

_"

Z_ This battery charger must be properly installed
and wired for correct operation of all 2008
model line Air-cooled Standby Generators.
Failure to do so will result in a dead battery
condition at the generator.
NOTE:

For authorized service, reference
the dealer Iocator number found
in the generator owner's manual
or on the generator.

This installation
guide should be used in conjunction with the "Installation
and Owner's
Manual"
that
is furnished
with the Air-cooled
Standby
Generator
and the Installation
and appropriate
transfer
switch manual.
Please review all manuals
prior to installation
of the generator
and transfer
switch. This battery charger is not required
with
the Liquid-cooled
Generator
product
line. This
battery
charger
is not required
for Air-cooled
Standby
Generators
prior to the 2008 model line.
This unit is not compatible
with other generator
manufacturer's
products.

Section 1 - General Information
GENERAL

Battery ChargerInstallation Guidelines
NFORMATON

Future
product
reflected
in the

updates
written

BATTERY CHARGER

1.2

These
Installation
Guidelines
are designed
to familiarize personnel
with the installation
process
for the
battery
charger
required
for the air-cooled
generator
only. It does not replace
or supersede
any information
contained
in any of the written
documents
shipped
with the unit.
This booklet
should
only be used
in
conjunction
with
the Owner's
Manual,
Installation
Guide
and other
technical
documents
shipped
with
the unit.

COMPATiBiLiTY
This

battery

all

2008

For

all

generators
switch

enclosure

For

these

•

Type

Switch

Description

RTSD

Pre-wire
center

with

8 circuit

RTSF

Pre-wire

with

10 circuit

ST100R10C

load

Pre-wire
load

RTSP

Pre-wire

ST100R14C

load

with

12 circuit

14 circuit

Pre-wire
with
load center

RTSS
KGALT0101200
SR200RDPM

Power
Shed
center

16 circuit

Manager
LTS
with 16 circuit

- Load
load

Standard

KGATX
RTSE
SRXXXRD
KGATD

Service

005448-0
005449-0
KGATD0101RSP
NOTE:

Switch

Entrance

Rated

GenReady
Type

is the

first

four

(4) digits

and
that

MUST

be

with

a transfer

already
this

installed
charger

were

NOT

the

supplied

charger

installed

is NOT

according

DETERMiNATiON OF GENERATOR/
TRANSFER SWITCH MODEL TYPE

1.2.1

to Section

Stop

Here

Battery
charger
is included
and pre-wired
the translkr
switch.
Discard
this charger.
further
installation
is required

with
No

Stop

Here

No

Stop

Here

Battery
charger
is included
and pre-wired
the translkr
switch.
Discard
this charger.
further
installation
is required

with
No

Stop

Here

Battery
charger
is included
and pre-wired
the translkr
switch.
Discard
this charger.
further
installation
is required

with
No

Stop

Here

charger

is included

charger
Proceed

and

pre-wired

Discard
this
is required

is included
with
with connections.

with

charger.

the

transikr

The
and

included
connected

battery

charger

must

be installed

The

included

battery

charger

must

be installed

and

connected

The
and

included
connected

battery

charger

must

be installed

of the

model

to

guidelines.

with
No

Battery
switch.

in
is not

Battery
charger
is included
and pre-wired
the translkr
switch.
Discard
this charger.
further
installation
is required

Battery

with

Generators.

Proceed

the translkr
switch.
further
installation

center

RTSW
ST100R16C
KGATX0216100

RTSN
SRXXXR

load

center

with

and

is

center,

Notes

center

RTSH

generators

installed

supplied

charger

switch!load

required

Standby

The Battery
charger
included
with this manual
only
needs to be used with certain
transfer
switch
configurations.
Some transfer
switch
configurations
already
have
the battery
charger
installed
in the transfer
switch.
Before
proceeding
it is necessary
to select the
transfer
switch
used from the following
table.

This
device
should
be installed
with all local
electrical
codes and/or
the latest edition
of the
National
Electrical
Code. All wiring
must be the
correct size and type, and must conform to local
codes, standards,
and regulations.
Switch

all

a transfer

already

estabHealth
to all

were

the

NOTE:

It is essential
to comply with all regulations
lished
by the Occupational
Safety
and
Administration
(OSHA) and strict adherence
local, state and national
codes is mandatory.

that
the

transfer

and

Air-cooled

center,

needed.

the equipment.
Always
read all accompanying
documentation
carefully
before
attempting
to install
any
generator,
transfer
switch
or related
equipment.

is compatible,

line

switch/load

with

and/or
modifications
will be
documentation
included
with

charger
model

number

and

can

be

found

on

the

2

3

3

4

data

label

inside

the

switch.
q

INSTALLATION

Section 2 - Load Shed Transfer Switch Installation
Battery Charger Installation Guidelines

2.]

LOAD SHED TRANSFERSWITCH

•

2.1.2 WIRING AND CONNECTIONS
_ENERATO_

1.

Crimp
spade lugs onto all three low voltage wires,
15B, 0, and 23 (Purchased
or supplied
separately).
Connect
the low voltage
wires,
15B, 0, and 23 to
the terminal
strip on the controller
(Figure
2.2).

(RTSS) INSTALLATION
•

2.1.]

WIRING

AND CONNECTIONS

AT THE

TRAN_
2.
Connect
the 15B, 0, and 23 low voltage
control
wires
to the load shed controller
connector
J5 per the wiring diagram.
Wires should
be sized according
to the
following
table.

Figure

2.2 -Wires

AT THE

Connection
of Charger DC Output
in Generator
Control Panel

CHARGER
DC OUTPUT
{TRANSFER
SWITCH
TO GENERATOR)
WIRE SIZE CHART
Maximum
Wire
Length

Run

Recommended
Size (stranded

Wire
copper)

35

feet

(10.67m)

No.

16 AWG.

60

feet

(18.29m)

No.

14 AWG.

90

feet

(27.43m)

No.

12 AWG.

NOTE:
The
charger
switch
(Figure

is

already
2, I).

mounted

in

the

transfer

NOTE:
See
RTSS
"Interconnection
tions.

Figure

Installation/Wiring
Diagrams"

2.1 --

Diagram
section
for

in the
connec-

2.].
Wiring

Connections
Switch

at the Transfer

1.

2.
3.

If already
connected,
disconnect
the battery
in
the generator.
Remove the negative cable first followed by the positive cable. Take care not to short
the cables together.
Ensure
power is applied
to the battery charger
input.
Connect
a volt meter across
the battery
leads.
The voltage reading should be between 12.8 VDC
and 13.8 VDC (Figure 2.3).

Figure

Charger

2

PERATI NAL TE TiN

2.3 -- Measurement
of Charger
with Battery Disconnected

Output

Section 3 = Standard or Service Entrance Transfer Switch Installation

iNSTALLATiON

Battery ChargerInstallation Guidelines

4.

If the voltage is within range installation
of the
battery charger is complete.
If the voltage is not
within
range verify all wiring
and sizing and
retest.

5.

Re-connect
the battery cables. Positive
followed by the negative cable.

cable

3.

Run the other side of the fuse holder
120VAC
Hot) along with the neutral from the neutral
lug
to the generator
(see Figures 3.1 and 3.5).
NOTE:

first

See the appropriate
RTSN or RTSE
Wiring Diagram for connections,

Installation/

STANDARD TRANSFER SWITCH

3.1

Figure

(RTSN)
OR(RTSE)
SERVICE

3.1 -- RTSN Fuse Block installation
Neutral Connection

and

ENTRANCE RATED TRANSFER
SWITCH INSTALLATION
•

3.]A

WiRiNG

AND CONNECTIONS

AT THE

TRANSFER SWITCH
Choose

the appropriate

option.
NOTE:

See the appropriate
RTSN or RTSE
Wiring Diagram in the "Interconnection
section for connections.

Installation/
Diagrams"

Option ] - Protected Load Provided in Load
Center
1.

2.

)

Install a 15Abreaker
in the load center (Purchased
or supplied
separately).
The breaker
must be on
a generator
backed-up
circuit or the battery
in
the generator
will not maintain
its charge during
extended
run periods.
Run the 120VAC hot wire and neutral wires to the
generator.
NOTE:

See the appropriate
RTSN or RTSE
Wiring Diagram in the "Interconnection
section
for connections.

Figure

3.2 -- RTSN Fuse Block installation
Connection

T1

Installation/
Diagrams"

Option 2 - Protected Load Provided in the RTS,
Fuse Block Installation
NOTE:
This section
is only appropriate
RTSE transfer
switches,

1.

2.

for 2008

RTSN

or

Mount the optional 5amp 600V fuse and holder
in the transfer
switch.
(Purchased
or supplied
separately).
Pre-2008
transfer
switches will not
have holes pre-drilled
for the fuse holder. In this
case, it is necessary
to drill holes in the enclosure
to mount the fuse holder (see Figures
3.1 and
3.4).
Connect one side of the fuse to terminal
(T1) of
the transfer
switch using a spade lug. Pre-2008
transfer
switches
will not have the spade
lug
attached
to terminal
T1. The spade terminal
is
available
separately
if required
(see Figures 3.2
and 3.4).
3

iNSTALLATION

Section 3 - Standard or Service Entrance Transfer Switch installation
Battery Charger Installation Guidelines

Figure

3.3 --

Figure

RTSN Fuse Block installation
Completed

3.4 --

Figure

RTSE Fuse Block installation
Connection

3.5 -- RTSE Neutral

Connection

When

Figure

RTSE Fuse Block Installation
Completed

When

T1

•

3.1.2

1.

Remove
erator

2.

The battery
charger
can be located
anywhere
within the controls
area on the generator.
It is
convenient
to mount
the charger
on the verticat surface
on right-hand
side of the controller
(Figure 3.7).
Clean the surface
where the charger
is to be
mounted
prior to mounting
with a damp cloth
and wait for the area to dry.
Remove the adhesive
covering
on the backside
of the charger and firmly press the charger into
place as shown. Once mounted
the charger may
be removed for inspection
by separating
the hook
& loop mounting
(Figure 3.8).

3.

4.

4

3.6 --

CHARGER MOUNTING
the cover

over the controller

in the gen-

iNSTALLATiON

Section 3 = Standard or Service Entrance Transfer Switch Installation
Battery ChargerInstallation Guidelines

Figure

3.7 -- Mounting
Location
Generator

of Charger

in

Figure

.

Figure

3.8Removal of Adhesive
Covering
Hook and Loop for Mounting

on

3.1.3

WIRING AND CONNECTIONS AT THE
_ENERATOR

.

Attach
the positive
and negative
battery
charger
leads
to the terminal
strip in the controller.
The
positive
lead is either a red wire or is marked
with
a (+) or (15B)
designation.
The negative
lead is
black and/or
marked
with a (-) or (0) designation.
The positive
lead attaches
to the terminal
labeled
"15B".
Note that there will be two wires
attached
to the "15B" terminal
when
the full installation
is completed.
one for the
switch.
labeled

One
common

for

Dress

Figure

Identify
the DC output
wires
on the battery
charger and crimp
spade
lugs onto both the positive
and negative
lead (purchased
or supplied
separately)
(see Figure
1.1).

1.

4.

the battery
charger
and
connection
to the transfer

The negative
lead
"0" (Figure
3.9).

attaches

to the

terminal

Connection
of Charger DC Output
in Generator
Centre/Panel

Using wire nuts
attach
the 120VAC
input
wires
from the battery
charger
to the generator
backedup
120VAC
circuit
from
the
transfer
switch
(Figure 3.10).

Figure

•

3.9 -Wires

3.10 -- Connection
Wires in Generator

all wires

neatly

of Charger AC Input
Control Pane/

(Figure

3.11).

3.11 -- Completed
Charger Connections
on Generator
Control Panel
Q_

INSTALLATION

Section 4 - GenReady Installation
Battery Charger installation Guidelines

4.1

NOTE:
See the appropriate
RTSN
or RTSE
Wiring
Diagram
in the "Interconnection
section
for connections.

Installation/
Diagrams"

3.

4.

5.

If already
connected,
disconnect
the battery
in
the generator.
Remove the negative cable first followed by the positive cable. Take care not to short
the cables together.
Ensure
power is applied to the battery charger
input.
Connect
a volt meter across
the battery
leads.
The voltage reading should be between 12.8VDC
and 13.8VDC (Figure 3.12).
If the voltage is within range installation
of the
battery charger is complete.
If the voltage is not
within
range verify all wiring
and sizing and
retest.
Re-connect
the battery cables. Positive
followed by the negative cable.

Figure

3.12

-- Measurement
of Charger
with Battery Disconnected

NOTE:
See the GenReady
the "Interconnection
nections.

OPERATIONAL TESTING

2.

cable

4.1.1

WiRiNG

Installation/Wiring
Diagram
in
Diagrams"
section
for con-

AND CONNECTIONS

AT THE

TRAN_
1.

2.
3.

Install a 15A breaker in the bottom portion of the
load center (Purchased
or supplied
separately).
The breaker
must be on a generator
backed-up
circuit or the battery
in the generator
will not
maintain
its charge during extended
run periods
(Figure 4.1 ).
Run the 120VAC hot wire and neutral wires to the
generator.
Run the low voltage wires, 15B, 0, and 23 to the
generator
(Figure 4.2)

first
Figure

4.1 --

GenReady
Battery

Breaker
Charger

Installation

Output

Figure

6

GENREADY INSTALLATION

4.2 --

GenReady

Charger

Connections

for

Section 4 - GenReady Installation

iNSTALLATiON

Battery ChargerInstallation Guidelines

O

4.1.2

1.

Remove the cover over the controller
in the generator
The battery
charger
can be located
anywhere
within the controls
area on the generator.
It is
convenient
to mount
the charger
on the vertical surface
on right-hand
side of the controller
(Figure 4.3).

2.

Figure

CHARGER MOUNTING

4.3 -- Mounting
Location
Generator

Figure

of Charger

4.4 -- Removal of Adhesive
Covering
Hook and Loop for Mounting

on

in

4.1.3

WIRING

AND CONNECTIONS

AT THE

GENERATOR
1.

.

.

4.

Clean
the surface
where
the charger
is
mounted
prior
to mounting
with a damp
and wait for the area to dry.

to be
cloth

Remove
the adhesive
covering
on the backside
of the charger
and firmly
press
the charger
into
place as shown.
Once mounted
the charger
may
be removed
for inspection
by separating
the hook
& loop mounting
(Figure
4.4).

Identify
the DC output
wires
on the battery
charger and crimp
spade
lugs onto both the positive
and negative
lead (see Figure
1.1).
Attach
the positive
and negative
battery
charger
leads to the terminal
strip in the controller.
The
positive
lead is either
a red wire or is marked
with a (+) or (15B) designation.
The negative
lead
is black
and/or
marked
with a (-) or (0) designation. The positive
lead attaches
to the terminal
labeled
"15B".
The negative
lead attaches
to the
terminal
labeled
"0". Note that there
will be two
wires
attached
to both
the "0" and
the "15B"
terminals
when
the full installation
is completed
(Figure
4.5).

Figure

4.5 -Wires

Connection
of Charger DC Output
in Generator
Control Panel

7

INSTALLATION

Section 4 - GenReady Installation
Battery Charger instaUation Guidelines

.

Using wire nuts
attach
the 120VAC
input
wires
from the battery
charger
to the generator
backedup
120VAC
circuit
from
the
transfer
switch
(Figure
4.6).

Figure

4.6 -- Connection
wires in generator

of charger AC input
control panel

_J_DPERATI
1.

2.
3.

4.

5.

If already
connected,
disconnect
the battery
in
the generator.
Remove the negative cable first followed by the positive cable. Take care not to short
the cables together.
Ensure
power is applied
to the battery charger
input.
Connect
a volt meter across
the battery
leads.
The voltage reading should be between
12.8VDC
and 13.8VDC (Figure 4.8.
If the voltage is within range installation
of the
battery charger is complete.
If the voltage is not
within
range verify all wiring and sizing and
retest.
Re-connect
the battery cables. Positive
followed by the negative cable.

Figure

4.

Dress

all wires

neatly

(Figure

4.7).

NOTE:
See the GenReady
connections.
Figure

8

Installation/Wiring

Diagram

4.7 -- Completed
Charger Connections
on Generator
Control Panel

for

NAL TE TIN

4.8 -- Measurement
of Charger
with Battery Disconnected

cable

first

Output

Section

5 -

Interconnection

iNSTALLATION

Diagrams

Battery Charger installation

Guidelines

RTSS Diagram - Drawing No. 0G8774-A



oo
co

<[z
co I

--

D
_w

DZ

Wz_
Z_

_zS_

z>-

_
WH_

W
D

D_Z_

03;

x.

\

D_
_wZ_
_

0dW

_w_W

o_ w_

O
_W

wo

z

z_

LoW

z

_Z
_W_
_W_
z_WD

W

_

D
Z

_

Ow_O
_w_

z_O_
o
_oWw
--D
_w
_

w _

o

L_d

z

i'

W

t4

!

Section

5 -

Interconnection

iNSTALLATiON

Diagrams

Battery CEarger instaUation Guidelines
GenReady Diagram - Drawing No. 0G4744-C

L5
z
<_

Od
0
L
Z
<[ 

oo
co

d

QI

L
z
z
r-

Wz_

sS

0

s_

_z_B

zW_
0_

S_d
_z
_W

_W

s3_
@
o
z

w

%

W

_

Section 6 -

Notes

Battery Charger instaUation Guidelines

t6

Section 6 -- Notes
Battery ChargerinstaUation Guidelines

t7



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 20
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sat Nov 01 04:16:08 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu