COLEMAN / EVCON IND. Furnaces/Heaters Manual L0601021

DGAM075BDD DGAM075BDD COLEMAN EVCON FURNACES/HEATERS - Manuals and Guides L0601021 View the owners manual for your COLEMAN EVCON FURNACES/HEATERS #DGAM075BDD.

User Manual: COLEMAN COLEMAN / EVCON IND. Furnaces/Heaters Manual COLEMAN / EVCON IND. Furnaces/Heaters Owner's Manual, COLEMAN / EVCON IND. Furnaces/Heaters installation guides

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadCOLEMAN  / EVCON IND. Furnaces/Heaters Manual L0601021
Open PDF In BrowserView PDF
035-20530-001

Rev. B (0804)

DGAT PROGRAM KIT 37323712001
INS TALLA TION INSTRUCTIONS
Heating

_ Air Conditioning

FOR MODELS:
DGAM075BDD

DGAT075BDD

DGAM075BDE

DGAT075BDE

DGAM075BDF

DGAT075BDF

DGAT070BDD

DLAS075BDD

DGAT070BDE

DLAS075BDE

DGAT070BDF

DLAS075BDF

Use of this instruction
factured

is intended

housing

heating

Fire or explosion

hazard.

Failure to properly
loss of life.

for qualified

individuals

experienced

in the proper

installation

and service

of manu-

appliances.

inspect

and restore

appliance

to proper

operation

may cause

property

damage,

personal

injury

or

General Information
A.

Before You Start

Once

you have read this instruction
1.

Thoroughly

review

Program

Inspect
a.

Auxiliary

limit switch

d.

Card

Packet

board

assembly
Natural

4.

Unitary

and

assembly.

with instructions

"shoehorn"

gas

and labels

for auxiliary

bag

assembly,

assembly,
and

limit

Digital

b.

5/16" Hex head

c.

Flashlight

or droplight

d.

Inspection

mirror

Phillipshead

f.

Two (2) crescent

Tools needed

bag

C.

Set the thermostat

3.

Remove

4.

Move gas control

control

Operating
instructions

1 Part

you To Turn Off Gas to Appli-

to lowest

instructions
is
are as follows:

setting.

to the appliance.
access

panel.

switch

will direct

The Operating

Instructions

to "OFF"

position.

you to follow

the Operating

are as follows:

1.

Set the thermostat

2.

Turn off all electric

3.

This

appliance

to lowest

power to the appliance.

lights

Remove

5.

Move
force.

6.

Wait five (5) minutes

7.

with

an

the burner.

ignition

device

Do NOT

try to

by hand.

4.

control

gas

setting.

is equipped

automatically

access

control

gas, determine
Kit

- Source

Instructions

light the burner

Program

Silicone

Instructions
to place the appliance
in operation.
A label with
the Operating
Instructions
is located inside the lower door.

wrenches
DGAT

will direct

Turn off all power

which

screwdriver

Group

instructions

1.

driver

to install

High temperature
RTV
Number MA-HTSS-R

2.

Thermometer

e.

Products

switch

LP/Propane
hardware

test equipment.

a.

c.

To Turn Off Gas to Appliance

These

orifice
bag

11/32" Nut driver

ance during the inspection.
A label with these
located inside the lower door. The instructions

holes.

Wire clamps

Gather

four (4)

installation.

gas orifice
assembly.

3.

B.

liner assembly
hooks

1/2" Wrench

b.

at dgatpro-

These
heat exchanger

Part A has two (2) curved
stainless
steel bolts.

Customer

f.

DGAT

if you have any questions.

(3) piece

c.

e.

Contact

or on line

ii. Parts B and C have slotted
b.

tape.

kit contents

Three
i.

instruction.

at: 1-888-665-4640

gram@york.com,
2.

this

view the video

a.

switch

to "OFF"

position.

Do not

to clear out any gas. If you smell

source

Move gas control

panel.

and repair

to "ON" position.

as necessary.
Do not force.

035-20530-001Rev.
B(0804)
8. Replace
control
access
panel.
9. Turnonallelectrical
power
totheappliance.
10. Setthermostat
to the desiredsetting.Burnerwill
light,whichmaytake30-60seconds.
11. Afterthree(3)trials,iftheappliance
willnotoperate,
followthe instructions
TO TURNOFFGASTO
APPLIANCE
andrefertotroubleshooting
guideinthe
Installation
Instructions
orOwner's
Manual.

D.

Product

Specifications

Model

No.

DGAT070

DGAT075

Input

70,000

Btu/hr

75,000

Btu/hr

Output

57,000

Btu/hr

61,000

Btu/hr

Air Temperature
Rise Range
Maximum

45_75OF

Outlet

165°F

Tem peratu re
Maximum

External

0.30" wc

Static Pressure

Part 1: Basic Information
Record

the following

Record

information

on the DGAT Program
clearly

Most of this information

Claim

2.

Form.

and legibly.

should

g.

be available

before

travelling

to the job site.

A.

Rating
1.

Plate Data

Serial

Number

Customer

Data

1.

Customer
code.

name,

2.

Customer

telephone

street

address,

city, state

and

zip

number.

Model Number

Part 2: Inspection
A.

Inspect
1.

Verify

Roof Jack
the proper

is approved

Roof Jack is being used.

for use with

only. See Figure

4000

the

4000

The DGAT

Series

SERIES

The 7900

2.

3.

2

Roof

inspect

Roof

or shows

FIGURE
Roof Jack

can be converted

Jack by replacing

Jack.

Remove

bird

crown.

to a

1.

Replace

if

damaged,

or other

obstructions

2: Turn
Follow

power

instructions

switch

to off

TO TURN

position.
OFF

GAS

TO APPLI-

ANCE.

Use pin

Disconnect

wires to gas valve,

igniter,

and flame sen-

sor.

tilted,

deterioration.

screens

air inlet.

Burner

roof jack

2.

crooked,

bustion

Assembly

7900 SERIES

Series

4000 Series
4000-6941tC.

Remove

1.

FIGURE 1: Roof Jack
NOTE:

B.

3.

Turn off gas supply
to furnace
by closing
shut-off valve. Disconnect
gas supply piping.

4.

Remove

to com-

gas valve.

See Figure

manual

3.

Unitary

Products

Group

035-20530-001
Rev.B(0804)
C.

Inspect

Heat Exchanger

1.

inspection

Insert

flashlight

mirror

or droplight

entire

interior

dition

per following

a.

Typical
i.

through

perimeter

of heat exchanger.

heat

pattern

gray discoloration.

5.
When

Remove
burner

the burner

is removed,

the end of the burner
Reference
halves

Figure

to insure

mounting
should

check

to insure

5. Check

See Figure

the ribbon

porting,

it is concentric

the seams

entire

4.

feel.

located

in

closed

may

include

light to dark

any deforof

the

heat
the

of the heat exchanger

by

any

or burn through,

the heat exchanger

through

then you need to check

surface

If you feel

no bumps

6.

does not reveal

or burn

surface,

inside

crack

and square.

between

that they are completely

The flame spreader
ment and to insure
these

assembly.

crack,

exchanger

Note con-

shape with

See Figure

inspection

mation,

Use

Inspect

Pattern

Surface must be smooth
or indentations.

iii. If visual

opening.

surface.

guidelines.

Discoloration

ii. Normal

FIGURE 3: Gas valve removal

burner

to illuminate

roughness,

deformation,

proceed

with replacing

with 37323713001.

the burner
and tight.

needs to be checked for proper alignthat it is not distorted and the burner

legs should

items are found

also be checked

for distortion.

to be out of alignment,

If any of

the burner

be replaced..

FIGURE

6: Typical

discoloration

pattern

b. Cracked. See Figure 7.

FIGURE 4: Burner assembly removal

FIGURE

7: Cracked
c.

heat exchanger

Deformed. See Figure 8.

FIGURE 5: Burner inspection

Unitary

Products

Group

3

035-20530-001Rev.
B(0804)
replaced.

FIGURE

8: Deformed
d.

heat exchanger

Burn Through. See Figure 9.

FIGURE 10: Overflame baffle located in top of heat
exchanger assembly (cut-away view).
D,

Corrective
1.

Heat

Actions
Exchanger

or 1 or more

missing.

Replace

Replacement
provided
2.

cracked,

through

Heat

If heat exchanger

burn through

furnace

you are feeling

check

the integrity

the inside

pushing

against

you should

of the rivets that secure

fle to the heat exchanger
the rivets

surface,

drum.

the overflame

You can check

each of the four (4) mounting

are missing,

the heat exchanger

also
baf-

the rivets by

Heat Exchanger
with no defects.
a.

casing

casing,

burned
rivets

are

with 37323713001
Follow

instructions

has resulted

insulation

you

will

to

exhibits

Install DGAT Program
instructions
in Part 3.

in dama breach

to contact

the

or on line at dgat-

receive

normal

and/or

need

at: 1-888-665-4640

program@york.com
replace furnace.
3.

While

pop

with kit.

DGAT program

FIGURE 9: Burned through heat exchanger

Exchanger.

or

baffle

heat exchanger

age to the furnace
in the

deformed

overflame

authorization

to

discoloration

pattern

Kit 37323712001.

Follow

legs. If any of

will need to be

Part 3: DGAT Program Kit Installation
A.

Install Heat Exchanger

Liner

FIGURE 11: Remove pressure switch tube.

4

FIGURE 12: Remove burner inlet pan 12 screws as
marked and remove burner inlet pan.

Unitary

Products

Group

035-20530-001
Rev.B(0804)

FIGURE 13: Remove bottom screw from air vane,
loosen top screw and rotate air vane counterclockwise.
Use caution when rotating air vane so that foil faced
insulation is not damaged.

FIGURE 16: Rotate liner upward to hook on overflame
baffle.

FIGURE 17: Make sure the hooks on Part A straddle
the rear right-hand leg of overflame baffle.
FIGURE 14" Remove burner chute mounting screws
(4) and remove burner chute.

FIGURE 15: Insert stainless steel liner piece (Part A)
with clips first.

Unitary

Products

Group

FIGURE 18: Push Part A of liner as far forward as leg
will allow.

5

035-20530-001Rev.
B(0804)
insert

Part C and rotate

Place

Part C over stud bolts

install

stainless

steel

upwards.
in Part A.

nuts.

FIGURE 19: Insert Part B and rotate upwards.
FIGURE 22: Again push assembled liner as far to front
as )ossible and tighten all (4) stainless steel nuts.

FIGURE 20: Place Part B over stud bolts in Part A.
FIGURE 23: Inspect with light to make sure Part A, B,
and C are pushed outward against drum.

FIGURE 21: Install stainless steel nuts found in
hardware bag. Do not tighten.

6

FIGURE 24: Reinstall burner chute to original position.

Unitary

Products

Group

035-20530-001Rev.
B(0804)

FIGURE 25: Reposition air vane to original position.
Reinstall bottom screw and tighten top screw.

FIGURE 28: Reinstall burner.

FIGURE 26: Install burner inlet pan with 12 screws. If
needed, re-seal pan with high temperature RTV
silicone.

FIGURE 29: Reinstall gas valve and gas piping.

FIGURE 27: Remove old gas orifice, install new per
chart.

FIGURE 30: Reconnect pressure tube to pressure
switch and wiring connectors to gas valve, igniter and
sensor.

7

Unitary

Products

Group

035-20530-001Rev.
B(0804)

FIGURE 31: Install warning label directly below rating
plate on vestibule panel.
B.

Install Auxiliary

FIGURE 34: Remove blower support shelf (7 screws).

Limit Switch Assembly

FIGURE 35: Remove blower support shelf.

FIGURE 32: Remove Blower Assembly Mounting
Screws (4). Unplug blower motor from control box.
Remove wire clamp. Remove blower assembly.

FIGURE 33: Remove wires from upper limit.

8

FIGURE 36: To protect side wall insulation insert
cardboard sheet as a "shoe horn" to insert auxiliary
limit switch assembly between insulation and heat
exchanger.

Unitary

Products

Group

035-20530-001
Rev.B(0804)

FIGURE 37: Bow back plate of auxiliary limit switch
assembly to insert on right-hand side of blower
compartment.

FIGURE 38: Compress stainless loop in middle to slide
past heat exchanger. Do not skin or scrape foil from
insulation while sliding switch down side of heat
exchanger.

FIGURE 39: Remove "shoe horn".

Unitary

Products

Group

FIGURE 40: Outer plate should compress against side
casing foil (Cut-away view).

FIGURE 41 : Push flange in until clearance holes line
up with holes in blower shelf support bracket
(Cut-away view).

FIGURE 42: Reinstall blower shelf. Pass wires up
through back slot of blower shelf before locating to final
position.

9

035-20530-001Rev.
B(0804)

FIGURE 43: Install new wire clamp in blower shelf hole
on rear left-hand side of shelf. Reinstall (7) screws to
secure blower shelf.

FIGURE 44: Install new auxiliary limit switch leads in
series with upper limit per wiring diagram.

FIGURE 45" Install and secure blower on shelf. Plug
blower motor into control box.

10

FIGURE 46" Install new wiring diagram over existing
diagram.

FIGURE 47: Install danger label on vestibule panel just
below upper limit switch.

FIGURE 48: Turn gas supply back on and leak check
gas valve piping connection.

Unitary

Products

Group

035-20530-001
Rev.B(0804)

FIGURE 50: Install Consumer Notice on top front
furnace door and instruct the consumer on how to
FIGURE 49: Turn electrical back on.

DGAT Field Inspection
Gas Orifice

Selection

properly maintain their furnace.

Program

Chart
Natural

Gas

L P/Propane

Elevation
Diameter

Drill Size

Part No.

Diameter

Drill Size

Part No.

Sea Level

.1520

24

9951-1521

.0935

42

9951-0931

2,000

.1495

25

9951-1491

.0935

42

9951-0931

3,000

.1495

25

9951-1491

.0890

43

9951-0891

4,000

.1470

26

9951-1471

.0890

43

9951-0891

5,000

.1440

27

9951-1441

.0890

43

9951-0891

6,000

.1440

27

9951-1441

.0860

44

9951-0861

7,000

.1405

28

9951-1401

.0860

44

9951-0861

8,000

.1360

29

9951-1361

.0820

45

9951-0821

9,000

.1360

29

9951-1361

.0810

46

9951-0810

.1285

30

.0785

47

9951-0781

10,000

Unitary

Products

Group

9951-1281

11

035-20530-001
Rev.B(0804)

Part 4: Checkout
A.

Furnace
1.

Data

Checkout

Verify

Cardboard

an overtired
Pad "Shoehorn"

was removed.

furnace.

make

sure that

found

to

meter

be okay,

to

Once

your

again,

you will

gas pressure
you

determine

should

the

need

to

is set properly.

then

units

also

firing

If

clock

rate,

the

and

if

needed,
check the supply duct system static pressure. Refer to Part 5 for information
on how to measure
Remove

Cardboard

Pad

"Shoehorn"

before

operat-

gas

pressure,

measure

supply

determine

static

the

firing

rate

and

pressure.

ing furnace.
If any
Fire Hazard.
Failure
sonal

to remove
injury

items

parameters
may cause property

damage,

tested
listed

of application/installation

per-

Since

or loss of fife.

Check
a.

b.

c.

Air Temperature

Make sure
minutes.

furnace

has

operated

for at least

5

charges
4.

Measure

return

openings

of top furnace

air

temperature

Measure

supply

at

top

B.

air temperature

at the closet

reg-

1.

the return

ply air temperature
3.

If measured
furnace

air temperature
to obtain

ATR is outside

rating

plate,

from

the sup2.

the ATR.

parameters

shown

then you will need

on the

to determine

why unit is operating
beyond its design parameters.
If
the ATR is too low, it is an indication of an underfired

12

Verify
mal

Subtract

furnace.

Make

properly.

If the ATR

sure

that
is too

your

gas

pressure

of

be

ATR

3.

must

for

covering

any

design

parameters,

your on-site

pro-

visit.

Visit
appliances

Follow

manufacturer.

Complete

the DGAT

are returned

instructions

Program

Claim

a.

Record

your name

and company

b.

Obtain

homeowner's

signature.

c.

Sign

Review

under
with the

found.

is within

appliance

claim

design

be addressed.

this situation

responsible

all gas-fueled
operation.

the

it is an indication

are not covered

to discuss

On-Site

properly

is set

high, it is an indication

will

If measured

that

problems

any problems

Complete

ister/grille.
d.

they

outside

plate,

ceed to step B and complete

louver

door.

as

to correct

rating

problems

you will need

homeowner

Rise (ATR).

in findings

application/installation

the warranty,
2.

result

on the units

form

to certify

provided

to norby the

Form.
information.

the furnace

has

been

upgraded.

the Consumer

Notice

with the customer.

Unitary

Products

Group

035-20530-001
Rev.B(0804)

Part 5: Additional
A.

Measure
a.

Testing Procedures

Gas Pressure

Remove gas valve
3/16" Alien wrench.
ting. See Figure

OUT PRESS TAP plug using
Install 1/8 NPT hose barb fit-

3.

Allow

4.

Measure time required (in seconds)
for gas meter 2
cubic
foot dial to rotate one complete
turn (or 1/2

51.

cubic
5.

burner

C.

Calculate

2.

FIGURE 51 : Pressure tap

4 complete

turns).

input:

[Gas Heating

Value] 2 x 7200
Time

Assume 1030 BTU per cubic foot for natural gas if gas
supplier cannot provide exact value.

Measure
1.

5 minutes.

foot dial to rotate

Input
2.

to operate

Static

Pressure

Verify upper door is installed and furnace
blower are operating
in heating speed.
Supply
a.

Static

Remove

burner

and

Pressure.
top screws

from coil cabinet

cover plates

(3 total).
b.

Connect
fitting

c.

d.

manometer

to OUT

Follow

OPERATING

furnace

in operation.

Allow

burner

Outlet

positive

PRESS

hose
b.

barb fitting.

INSTRUCTIONS

to

place
c.

to operate

(Manifold)

(+) pressure

TAP hose

Gas

30-60

seconds.

Measure

Adjust

pressure

Pressure.

to 3.5" + 0.2 w.c. for natural

gas, or 10.0"

Connect

manometer

positive

fitting

to Static Pressure

Insert
Insert

static pressure
probe straight

level

(horizontal)

Figure

(+) pressure

hose

Probe.

probe into each screw hole.
into hole 6". Probe must be

for proper

measurement.

See

52.

_+0.2

w.c. for LPipropane.
e.

Follow

instructions

TO

TURN

OFF

GAS

TO

APPLIANCE.
f.
4.

Remove

Follow

hose barb from gas valve.

OPERATING

Install plug.

INSTRUCTIONS

to place

fur-

nace in operation.
5.

Operate
heating

B,

Measure
1.

Adjust
prevent

furnace
cycle

through

to confirm

Input

at least
proper

one

(1) complete

operation.

Rate

controls

on all other

operation.

Follow instructions
facturer.

Extinguish
provided

gas-fired

appliances

pilot(s),

to

if applicable.

by the appliance

manu-

FIGURE 52: Measuring supply static pressure
2.

Follow

OPERATING

INSTRUCTIONS

to place

fur-

nace in operation.

Part 6: Submit
A.

Claim

Mail Documentation
1.

Submit

original

DGAT Program

Claim

to:

York International
Attn: Warranty Dept.
P.O. Box 385
Norman, OK 73070

Unitary

Products

Group

13

035-20530-001Rev.
B(0804)
NOTES

14

Unitary

Products

Group

035-20530-001
Rev.B(0804)
NOTES

Unitary

Products

Group

15

NOTES

Subject to change without notice. Printed in U.S.A.
Copyright t7 by York International Corp. 2004. All rights reserved.

Unitary
Products
Group

Supersedes:

RO.
Box
19014

035-20530-001
035-20530-001

Rev. B (0804)
Rev. A (0804)

Wichita
KS
67204-901



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 16
Page Layout                     : SinglePage
Page Mode                       : UseNone