Carrier 40VM900006 Touch screen central controller User Manual 2AMPX 40VM900006 Users Manual rev1

Carrier Corporation Touch screen central controller 2AMPX 40VM900006 Users Manual rev1

2AMPX-40VM900006_Users Manual_rev1

Download: Carrier 40VM900006 Touch screen central controller User Manual 2AMPX 40VM900006 Users Manual rev1
Mirror Download [FCC.gov]Carrier 40VM900006 Touch screen central controller User Manual 2AMPX 40VM900006 Users Manual rev1
Document ID3657968
Application IDq4v3X33ME4VbYkj8QBwwzw==
Document Description2AMPX-40VM900006_Users Manual_rev1
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize84.04kB (1050506 bits)
Date Submitted2017-11-29 00:00:00
Date Available2017-11-30 00:00:00
Creation Date2017-04-12 14:14:10
Producing SoftwareAcrobat Distiller 11.0 (Windows)
Document Lastmod2017-08-30 08:49:28
Document Title40VM-6SI Touch Screen Central Controller-40VM900006_China.fm
Document CreatorFrameMaker 2015
Document Author: cbs2108

38VM/40VM Series
VRF (Variable Refrigerant Flow) System
Touch Screen Central Controller Accessory
Installation Instructions
Part Number 40VM900006
For Commercial Use Only
CONTENTS
Page
SAFETY CONSIDERATIONS.......................................1
GENERAL..................................................................1
DIMENSIONAL DRAWINGS.......................................... 2
INSTALLATION CONSIDERATIONS.............................4
INSTALLATION..........................................................4
SETTING NETWORK ADDRESS.......................................6
BASIC CONFIGURATION....................................................6
• LOGIN........................................................................6
• BRAND CHOICE.......................................................7
• AUTO SEARCH.........................................................7
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully.
Follow all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage thermostat.
Understand the signal words — DANGER, WARNING,
and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards that could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which would result in minor personal injury or product and
property damage.
Recognize safety information. This
symbol ( ). When this symbol is displayed on the unit and in
instructions or manuals, be alert to the potential for personal
injury. Installing, starting up, and servicing equipment can be
hazardous due to system pressure, electrical components, and
equipment location.
GENERAL
The VRF (variable refrigerant flow) touch screen central
controller is a wall-mounted, low-voltage controller that
provides site-level control of multiple VRF systems. The
controller allows central management of mode, setpoint,
and scheduling of indoor units (IDUs).
The touch screen central controller is available for use
with the VRF (variable refrigerant flow) outdoor units /
systems listed in Table 1.
NOTES:
1. Changes or modifications of this product not expressly
approved by the party responsible for compliance could
void the user's authority to operate the equipment.
2. This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio
accordance with the instruction manual, may cause
harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause
harmful interference-in which case the user will be
required to correct the interference at their own expense.
This equipment should be installed and operated with a
minimum distance of 20 centimeters between the radiator
and your body.
Table 1: Touch Screen Central Controller
Accessory Usage
UNIT
SIZES
072,096,120,144,
168, 192, 216,
38VMAR Heat Recovery System
240, 264, 288, 312, 336
036, 048, 060, 072, 096, 120,
144, 168, 192, 216, 240, 264,
38VMAH Heat Pump System
288, 312, 336, 360, 384, 408,
432
Table 2: Components shipped with Unit
NAME
IMAGE
QTY
FUNCTION
Mounting
Box
Plastic mounting enclosure
Mounting
Plate
Steel plate connecting
controller to front of Mounting
Box
Screws
(Short)
Used to Install Mounting Box
to Wall
Screws
Washers
Used to install Mounting Plate
on Mounting Box
Used to install Mounting Plate
on Mounting Box
(2 extra washers for fine
adjustment if wall is uneven)
Table 3: Specifications
Power Supply
(field provided)
Dimensions
(inches)
Total Weight
Number of X/Y
Bus Lines
Max. Refrigerant
Systems/IDUs
per Line
Rated Voltage
24VAC, 60 Hz
Current Requirement
1A
7-3/8
10-7/8
1-1/4
Touch Screen Controller, Mounting Box,
Mounting Plate, & Screws: 2 lbs 12 oz
8/64
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 17-40VM9006-01
Printed in China
Form 40VM-5SIR1
Pg 1
09-17
Replaces: 40VM-5SI
DIMENSIONAL DRAWING
1-1/4
10-7/8
7-3/8
3/8
Fig. 1 — Dimensions
R
X1 E Y1 ¡ X2 E Y2 ¡ X3 E Y3
X4 E Y4 ¡ X5 E Y5 ¡ X6 E Y6
DI1 ¡ DI2
DO1 ¡ DO2
AI1 ¡ AI2
&20a
USB
'2Ɣ'2
9$&,1
LAN
',Ɣ',
$,Ɣ$,
LAN
USB
Fig. 2 — Connection Description
Table 4 — Connection Description
NAME
FUNCTION
24VAC power
24VAC common
X conductor, X/Y bus (no 1-6)
Y conductor, X/Y bus (no 1-6)
Shield conductor, X/Y bus (no 1-6)
DI1
Emergency Shutdown dry contact input*
DI2
(reserved)
DO1
(reserved)
DO2
(reserved)
AI1
(reserved)
AI2
(reserved)
LAN
Local Area Network connection, Ethernet
USB
Universal Serial Bus connection for service
*Emergency Shutdown input is not suitable for life-safety applications, such as fire or smoke sequences.
INSTALLATION CONSIDERATIONS
3. For flush-mount installation, provide a 10-1/4" by 6-5/8"
opening in drywall or mounting surface to accommodate
the mounting box.
The controller should be mounted:
• at a location that allows easy access
• on a section of wall without water or drainage pipes
The controller should NOT be mounted:
• near heat sources such as direct sunlight, heaters, dimmer
switches, and other electrical devices.
CAUTION
Over-tightening the screw will cause deformation to
the rear cover and LCD damage.
4. Pull all wires through drywall or surface opening, and
then through knockout(s) in Mounting Box.
5. Install the Mounting Box (3) into the 10-1/4” by 6-5/
8” opening in dry wall or mounting surface making
sure the box is flush with the wall surface. See Figure
3. Use the 6 short screws to fasten the plastic mounting
box. Use plastic washers as needed for alignment and
to prevent damage to components.
INSTALLATION
To install the controller, perform the following procedure:
1. Turn off all power to the outdoor units, indoor units, and
MDCs.
WARNING
Electrical shock can cause personal injury and death.
Before installing thermostat, shut off all power to this
equipment during installation. There may be more
than one power disconnect. Tag all disconnect
locations to alert others not to restore power until
work is completed.
wall
CAUTION
Failure to follow this caution may result in equipment
damage or improper operation.
Improper wiring or installation may damage the
thermostat. Check to make sure wiring is correct
before proceeding with installation or turning on unit.
Fig. 3 — Installing the Mounting Box
2. Control Wire: Use 16 to 20 AWG (American Wire Gage),
stranded twisted pair shielded 2-core wiring (copper
wire). Be sure the distance between the controller and the
furthest outdoor units is not more than 3937 ft. FieldProvided 24VAC Power Wire: Use copper wire rated
for the current requirement shown in Table 3; follow
all applicable electrical codes.
6. Install Mounting Plate:
Make sure the metal hooks are facing upward. Attach the
mounting plate (2) onto the mounting box (3) using the four
long screws (4) and four plastic washers. Do not overtighen the
screws. See Figures 4 and 5.
Fig. 4 — Installing the Back Plate Washers
wall
wall
ĸ
Äş
Fig. 5 — Installing the Back Plate to Box
7. Wire the Controller:
Control Wire: Use 16 to 20 AWG (American Wire Gage), stranded twisted pair shielded 2-core wiring (copper wire).
The controller has 6 central control bus (X/Y) lines. Each line can support up to 8 refrigerant systems and 64 indoor units,
maximum. Using control wire, connect outdoor units’ X/Y central control bus terminals in a “daisy chain” configuration;
connect terminating end to the Central Controller’s designated X/Y line (#1 through 6). For larger Heat Pump systems with dual
or triple modules on a refrigerant system, wire X/Y daisy chain only to the Header outdoor unit of each refrigerant system. See
Figure 6.
TOUCH SCREEN CONTROLLER
LAN
COM 1~6
24V ACIN
1 2 3 4 5 6
XYXYXY XYXYXY
Customer computer
(For monthly report creation)
(For air conditioning control)
Power Adapter
Hub
Power Supply
X Y
X Y
X Y
X Y
P Q
P Q
Outdoor
unit
P Q
Outdoor
unit
P Q
Outdoor
unit
P Q
P Q
P Q
Indoor unit
Indoor unit
Indoor unit
Outdoor
unit
P Q
Indoor unit
Max. 8 Refrigerant Systems
and
Max. 64 Indoor Units
Fig. 6 — System Wiring Diagram
Connect field-supplied 24VAC power (copper wire) to R and C terminals. Connect Ethernet to LAN (where applicable).
8. Install the Controller:
After wiring, install the controller (1) onto the mounting
plate. Position the holes over the metal hooks and slide down to
lock into place. See Figure 7.
wall
BLACK
wall
BLACK
GRAY
MAIN BOARD
BLUE
BLACK
CT1
ġ
Fig. 7 — Installing the Controller
Fig. 10 —Single Phase ENC2
SETTING NETWORK ADDRESS
BASIC CONFIGURATION
&1 &1
&1
&1
&1
&1
&1 &1 &1 &1 &1
&1
Once all outdoor refrigerant systems are connected and
operational, the controller may be powered up for initial login
and basic configuration.
Login — Log in from the unit's home screen with user name
“superAdmin.” The default password is 66668888. See
Figure 11.
&1
ENC1
0DLQERDUG
&1 &1
(;9% &1
(;9$ &1

67
&1
+($7 ,19
&1
75$1,1
75$1,1
&1
&1
(;9& &1
&1
21
&1
6 ENC3
ENC4
'63
&1
+($7 ,19
&1
&1
'63
&1
&1 &1 &1 &1
:KLWH 5HG  “Hardware Testing.” The following
screen will display:
2. Select “Carrier” or “Bryant.”
3. Select “Always” or “Just Once.”
One of the following screens will be displayed depending
on the user selection:
6. Select “Carrier” or “Bryant” and select “Test.”
Auto Search — The Touch Screen Central Controller can
automatically search and connect to the system's connected
units. Devices connected to the controller are automatically
searched for and registered. You can register a device
automatically as follows. See Figures 14 and 15.
1. In the main menu, click the [Install] menu icon.
2. Click the [Auto Search] button. See Figure 15.
4. Login to TSCC using the default user name and
password.
User Name: superAdmin
Password: 66668888
Fig. 15 — Auto Search
Refer to the User Manual for additional details on operation.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 17-40VM9006-01
Printed in China
Form 40VM-5SIR1
Pg 8
09-17
Replaces: 40VM-5SI

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : cbs2108
Create Date                     : 2017:04:12 14:14:10Z
Modify Date                     : 2017:08:30 08:49:28-04:00
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.150055, 2012/11/19-18:45:32
Producer                        : Acrobat Distiller 11.0 (Windows)
Creator Tool                    : FrameMaker 2015
Metadata Date                   : 2017:08:30 08:49:28-04:00
Format                          : application/pdf
Title                           : 40VM-6SI Touch Screen Central Controller-40VM900006_China.fm
Creator                         : cbs2108
Document ID                     : uuid:f8aee0db-705c-4d43-8f16-5c9d2090aee5
Instance ID                     : uuid:2c2e63ec-94a7-45a6-a9d0-b117fa9dd417
Page Mode                       : UseOutlines
Page Count                      : 8
EXIF Metadata provided by EXIF.tools
FCC ID Filing: 2AMPX-40VM900006

Navigation menu