38VM/40VM Series VRF (Variable Refrigerant Flow) System Touch Screen Central Controller Accessory Installation Instructions Part Number 40VM900006 For Commercial Use Only CONTENTS Page SAFETY CONSIDERATIONS.......................................1 GENERAL..................................................................1 DIMENSIONAL DRAWINGS.......................................... 2 INSTALLATION CONSIDERATIONS.............................4 INSTALLATION..........................................................4 SETTING NETWORK ADDRESS.......................................6 BASIC CONFIGURATION....................................................6 ⢠LOGIN........................................................................6 ⢠BRAND CHOICE.......................................................7 ⢠AUTO SEARCH.........................................................7 SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage thermostat. Understand the signal words â DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage. Recognize safety information. This symbol ( ). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury. Installing, starting up, and servicing equipment can be hazardous due to system pressure, electrical components, and equipment location. GENERAL The VRF (variable refrigerant flow) touch screen central controller is a wall-mounted, low-voltage controller that provides site-level control of multiple VRF systems. The controller allows central management of mode, setpoint, and scheduling of indoor units (IDUs). The touch screen central controller is available for use with the VRF (variable refrigerant flow) outdoor units / systems listed in Table 1. NOTES: 1. Changes or modifications of this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 2. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference-in which case the user will be required to correct the interference at their own expense. This equipment should be installed and operated with a minimum distance of 20 centimeters between the radiator and your body. Table 1: Touch Screen Central Controller Accessory Usage UNIT SIZES 072,096,120,144, 168, 192, 216, 38VMAR Heat Recovery System 240, 264, 288, 312, 336 036, 048, 060, 072, 096, 120, 144, 168, 192, 216, 240, 264, 38VMAH Heat Pump System 288, 312, 336, 360, 384, 408, 432 Table 2: Components shipped with Unit NAME IMAGE QTY FUNCTION Mounting Box Plastic mounting enclosure Mounting Plate Steel plate connecting controller to front of Mounting Box Screws (Short) Used to Install Mounting Box to Wall Screws Washers Used to install Mounting Plate on Mounting Box Used to install Mounting Plate on Mounting Box (2 extra washers for fine adjustment if wall is uneven) Table 3: Specifications Power Supply (field provided) Dimensions (inches) Total Weight Number of X/Y Bus Lines Max. Refrigerant Systems/IDUs per Line Rated Voltage 24VAC, 60 Hz Current Requirement 1A 7-3/8 10-7/8 1-1/4 Touch Screen Controller, Mounting Box, Mounting Plate, & Screws: 2 lbs 12 oz 8/64 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 17-40VM9006-01 Printed in China Form 40VM-5SIR1 Pg 1 09-17 Replaces: 40VM-5SI DIMENSIONAL DRAWING 1-1/4 10-7/8 7-3/8 3/8 Fig. 1 â Dimensions R X1 E Y1 ¡ X2 E Y2 ¡ X3 E Y3 X4 E Y4 ¡ X5 E Y5 ¡ X6 E Y6 DI1 ¡ DI2 DO1 ¡ DO2 AI1 ¡ AI2 &20a USB '2Ć'2 9$&,1 LAN ',Ć', $,Ć$, LAN USB Fig. 2 â Connection Description Table 4 â Connection Description NAME FUNCTION 24VAC power 24VAC common X conductor, X/Y bus (no 1-6) Y conductor, X/Y bus (no 1-6) Shield conductor, X/Y bus (no 1-6) DI1 Emergency Shutdown dry contact input* DI2 (reserved) DO1 (reserved) DO2 (reserved) AI1 (reserved) AI2 (reserved) LAN Local Area Network connection, Ethernet USB Universal Serial Bus connection for service *Emergency Shutdown input is not suitable for life-safety applications, such as fire or smoke sequences. INSTALLATION CONSIDERATIONS 3. For flush-mount installation, provide a 10-1/4" by 6-5/8" opening in drywall or mounting surface to accommodate the mounting box. The controller should be mounted: ⢠at a location that allows easy access ⢠on a section of wall without water or drainage pipes The controller should NOT be mounted: ⢠near heat sources such as direct sunlight, heaters, dimmer switches, and other electrical devices. CAUTION Over-tightening the screw will cause deformation to the rear cover and LCD damage. 4. Pull all wires through drywall or surface opening, and then through knockout(s) in Mounting Box. 5. Install the Mounting Box (3) into the 10-1/4â by 6-5/ 8â opening in dry wall or mounting surface making sure the box is flush with the wall surface. See Figure 3. Use the 6 short screws to fasten the plastic mounting box. Use plastic washers as needed for alignment and to prevent damage to components. INSTALLATION To install the controller, perform the following procedure: 1. Turn off all power to the outdoor units, indoor units, and MDCs. WARNING Electrical shock can cause personal injury and death. Before installing thermostat, shut off all power to this equipment during installation. There may be more than one power disconnect. Tag all disconnect locations to alert others not to restore power until work is completed. wall CAUTION Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage the thermostat. Check to make sure wiring is correct before proceeding with installation or turning on unit. Fig. 3 â Installing the Mounting Box 2. Control Wire: Use 16 to 20 AWG (American Wire Gage), stranded twisted pair shielded 2-core wiring (copper wire). Be sure the distance between the controller and the furthest outdoor units is not more than 3937 ft. FieldProvided 24VAC Power Wire: Use copper wire rated for the current requirement shown in Table 3; follow all applicable electrical codes. 6. Install Mounting Plate: Make sure the metal hooks are facing upward. Attach the mounting plate (2) onto the mounting box (3) using the four long screws (4) and four plastic washers. Do not overtighen the screws. See Figures 4 and 5. Fig. 4 â Installing the Back Plate Washers wall wall ĸ Äş Fig. 5 â Installing the Back Plate to Box 7. Wire the Controller: Control Wire: Use 16 to 20 AWG (American Wire Gage), stranded twisted pair shielded 2-core wiring (copper wire). The controller has 6 central control bus (X/Y) lines. Each line can support up to 8 refrigerant systems and 64 indoor units, maximum. Using control wire, connect outdoor unitsâ X/Y central control bus terminals in a âdaisy chainâ configuration; connect terminating end to the Central Controllerâs designated X/Y line (#1 through 6). For larger Heat Pump systems with dual or triple modules on a refrigerant system, wire X/Y daisy chain only to the Header outdoor unit of each refrigerant system. See Figure 6. TOUCH SCREEN CONTROLLER LAN COM 1~6 24V ACIN 1 2 3 4 5 6 XYXYXY XYXYXY Customer computer (For monthly report creation) (For air conditioning control) Power Adapter Hub Power Supply X Y X Y X Y X Y P Q P Q Outdoor unit P Q Outdoor unit P Q Outdoor unit P Q P Q P Q Indoor unit Indoor unit Indoor unit Outdoor unit P Q Indoor unit Max. 8 Refrigerant Systems and Max. 64 Indoor Units Fig. 6 â System Wiring Diagram Connect field-supplied 24VAC power (copper wire) to R and C terminals. Connect Ethernet to LAN (where applicable). 8. Install the Controller: After wiring, install the controller (1) onto the mounting plate. Position the holes over the metal hooks and slide down to lock into place. See Figure 7. wall BLACK wall BLACK GRAY MAIN BOARD BLUE BLACK CT1 ġ Fig. 7 â Installing the Controller Fig. 10 âSingle Phase ENC2 SETTING NETWORK ADDRESS BASIC CONFIGURATION &1 &1 &1 &1 &1 &1 &1 &1 &1 &1 &1 &1 Once all outdoor refrigerant systems are connected and operational, the controller may be powered up for initial login and basic configuration. Login â Log in from the unit's home screen with user name âsuperAdmin.â The default password is 66668888. See Figure 11. &1 ENC1 0DLQERDUG &1 &1 (;9% &1 (;9$ &1 67 &1 +($7 ,19 &1 75$1,1 75$1,1 &1 &1 (;9& &1 &1 21 &1 6 ENC3 ENC4 '63 &1 +($7 ,19 &1 &1 '63 &1 &1 &1 &1 &1 :KLWH 5HGâHardware Testing.â The following screen will display: 2. Select âCarrierâ or âBryant.â 3. Select âAlwaysâ or âJust Once.â One of the following screens will be displayed depending on the user selection: 6. Select âCarrierâ or âBryantâ and select âTest.â Auto Search â The Touch Screen Central Controller can automatically search and connect to the system's connected units. Devices connected to the controller are automatically searched for and registered. You can register a device automatically as follows. See Figures 14 and 15. 1. In the main menu, click the [Install] menu icon. 2. Click the [Auto Search] button. See Figure 15. 4. Login to TSCC using the default user name and password. User Name: superAdmin Password: 66668888 Fig. 15 â Auto Search Refer to the User Manual for additional details on operation. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 17-40VM9006-01 Printed in China Form 40VM-5SIR1 Pg 8 09-17 Replaces: 40VM-5SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No Author : cbs2108 Create Date : 2017:04:12 14:14:10Z Modify Date : 2017:08:30 08:49:28-04:00 Language : en XMP Toolkit : Adobe XMP Core 5.4-c005 78.150055, 2012/11/19-18:45:32 Producer : Acrobat Distiller 11.0 (Windows) Creator Tool : FrameMaker 2015 Metadata Date : 2017:08:30 08:49:28-04:00 Format : application/pdf Title : 40VM-6SI Touch Screen Central Controller-40VM900006_China.fm Creator : cbs2108 Document ID : uuid:f8aee0db-705c-4d43-8f16-5c9d2090aee5 Instance ID : uuid:2c2e63ec-94a7-45a6-a9d0-b117fa9dd417 Page Mode : UseOutlines Page Count : 8EXIF Metadata provided by EXIF.tools