DUNKIRK Boiler Manual L0611511

User Manual: DUNKIRK DUNKIRK Boiler Manual DUNKIRK Boiler Owner's Manual, DUNKIRK Boiler installation guides

Open the PDF directly: View PDF PDF.
Page Count: 67

DownloadDUNKIRK  Boiler Manual L0611511
Open PDF In BrowserView PDF
GAS-FIRED,

DIRECT VENT,

CONDENSING,

HOT WATER

BOILERS
INSTALLATION
These instructions

INSTRUCTIONS

must be affixed on or adjacent to the boiler
WARNING

Improper installation, adjustment, alteration, service,
property
damage. Refer to this manual. For assistance
qualified installer, service agency, or gas supplier.

or maintenance
can cause injury or
or additional information consult a

@@
DUNKIRK BOILERS
DUNKIRK,

NEW YORK

14048 - 716 366-5500

Member: The Hydronics Institute

TABLE

OF CONTENTS

BOILER
RULES
BEFORE

RATINGS

INTRODUCTION

AND CAPACITIES

FOR SAFE INSTALLATION
INSTALLING

.............................................................................
..................................................................................

AND OPERATION

THE BOILER

.......................................................

....................................................................................

3
4
7
7

A. codes ...............................................................................................................................

7

B. boiler sizing ......................................................................................................................
C. considerations
for boiler location .....................................................................................

8
8

D. locating the boiler ............................................................................................................
E. combustion air and vent pipe requirements .....................................................................

8
9

F. condensate

drain requirements

G. foundation

requirements

H. removing
PLACING

existing

................................................................................................

boiler from common

THE BOILER

NEAR BOILER

......................................................................................

PIPING

venting system .................................................

10
11
11

.......................................................................................................

11

........................................................................................................

12

A. supply and return lines ...................................................................................................

12

B. pressure

16

relief valve .......................................................................................................

C. expansion

tank and make-up

D. condensate

water ...............................................................................

drain piping ................................................................................................

E. filling condensate

16
19

trap ....................................................................................................

19

F. chilled water piping ........................................................................................................

20

COMBUSTION

AIR AND VENT PIPE ..................................................................................

A. connections

and terminations

B. installation

........................................................................................

21
21

......................................................................................................................

22

PIPING ..........................................................................................................

25

A. check gas supply ...........................................................................................................

25

B. connecting the gas piping ..............................................................................................
C. checking the gas piping .................................................................................................
ELECTRICAL
WIRING .........................................................................................................

25
26
27

GAS SUPPLY

A.
B.
C.
D.

electric power supply .....................................................................................................
install your thermostat ....................................................................................................
field wiring connections
.................................................................................................
schematic wiring diagram ..............................................................................................

E. ladder wiring diagram .....................................................................................................
CONTROLS

AND ACCESSORIES

A. UT 1013-10

integrated

......................................................................................

boiler control ............................................................................

27
28
29
30
31
32
32

B. gas control valve ............................................................................................................

32

C. hot surface

32

D. L4006A

igniter ..........................................................................................................

high limit aquastat

E. draft inducer temperature

control

................................................................................

safety switch .........................................................................

32
32

F. casting temperature

safety switch ..................................................................................

33

G. differential

air proving switch ..........................................................................

33

pressure

1

H. draft inducer ......................................................................................................................

33

I. circulator pump ..................................................................................................................
J. drain valve .........................................................................................................................
K. relief valve ........................................................................................................................

33
33
34

L. flame rollout safety shutoff ................................................................................................

34

M. external

34

START-UP

condensate

pump ...............................................................................................

..............................................................................................................................

A. water treatment

and freeze

34

protection ..............................................................................

B. filling boiler with water and purging

air with diaphragm

C. filling boiler with water and purging air with conventional

type expansion

34

tanks ..................

closed type expansion

35

tanks .... 35

D. boiler in placing ..................................................................................................................

36

I. for your safety read before operating
II. operating instructions
III. to turn off gas to appliance
CHECK-OUT
PROCEDURES
AND ADJUSTMENTS
A.
B.
C.
D.
E.
F.
G.
H.

............................................................

verify proper sequence of operation ..................................................................................
inspect venting and air intake system ................................................................................
inspect condensate drain ...................................................................................................
inspect system piping .........................................................................................................
test ignition system safety shutoff ......................................................................................
test high limit control and adjust .........................................................................................
test other safety controls ....................................................................................................
set thermostat heat ............................................................................................................

1. measure the gas input rate ................................................................................................
J. set thermostat to desired room temperature ......................................................................
K. review all instructions ........................................................................................................
L. installation and check-out certificate ..................................................................................
MAINTENANCE
AND CLEANING ..........................................................................................
A.
B.
C.
D.
E.

beginning of each season ..................................................................................................
daily during heating season ...............................................................................................
monthly during heating ......................................................................................................
periodically during heating .................................................................................................
end of each heating season -annual shut down procedure ...............................................

F. annual examination
SERVICE

of boiler components

....................................................

HINTS ......................................................................................................................

A flow chart/detailed
B. trouble

sequence

of operation .........................................................................

shooting .................................................................................................................

C. differential
REPAIR

and cleaning

air pressure

switch check .................................................................................

PARTS .......................................................................................................................

37
37
38
38
38
38
38
39
39
39
41
41
41
43
43
43
44
44
44
44
47
47
50
58
59

A. jacket and base ..................................................................................................................

59

B. condensate

61

drain trap assembly

.......................................................................................

C. block and piping assembly .................................................................................................

62

D. mixer and air pressure

64

E. flue adapter

switch assembly ............................................................................

and exhauster

assembly ................................................................................

66

This appliance is a gas-fired
revolutionary cast aluminum

direct vent hot water boiler with cast aluminum boiler sections. A
heat exchanger means better heat transfer and thermal storage than

similarly sized cast iron boilers, which results in higher efficiency. The heating system water absorbs
amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing
condensation.
Sealed combustion,
premix gas burner, and low flame temperature means drastically
reduced CO and NOx emissions, which contribute to a cleaner and healthier environment.

large

This appliance, unlike normal residential atmospheric
and induced draft units, takes its combustion air
directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh
air. Sealed combustion
(also known as "direct vent") is the safest and best way to obtain plenty of clean
combustion air. The induced draft fan draws in the outside combustion air, then takes the cooler flue
gases from the boiler unit and provides a positive removal of the flue gases from the building through
inexpensive

and readily available

PVC and CPVC pipes.

-- 19 3/_:-_
(5021nrn}
4"

_

.oSL
ALTERNATE
RETURN

(1-_./l"

SUPPLY

0PENINGN
NPT (31.75_)

_

/_

ALTEI_NATE
OPENING
FOR
GAS SUPPLY

V
0

1

--

28"

--

(711ram)

---

&

PRESS1TI_E

GAUCcE

------------

_5"

t*RONT

pROVIDBD IN_ION

I

I

I (76,Stun:t)

PANEL

DOOR

PULL ............... --

_©
VENT

....
/

I I I
ACCESS

PANfL

(127ram)

_

_

I

[

I •

-I
SIDE

(_o.a=_)

o i/s"

FRONT

I\
\__

LEFT

CONNECTION
cpvc)

(Z4LSmm

i) J

(l_Tmm)

(g"

ALTEERATE

BOILER

WATER

RETb_N
(f-l/4
pR0_ED

_

NPT

(fll.7_mm)

_IONNE_IDNS

_tS]DE

TOP

FIGURE

1

CONDENSATE

TABLE
Model
5O
75

1

SEA LEVEL

RATINGS

-NATURAL

AND PROPANE

++ Heating

Net I=B=R

Input *(MBH)

Capacity

Rating

Weight

50
75

*(MBH)
45
68

*(MBH)
39
59

(tbs.)
220
220

100
100
* 1 MBH = 1,000 Btuh

90

78

Shipping

GASES
Flue
Dia.
2" C PVC & PVC
2" C PVC & PVC

220
2" C PVC & PVC
Btuh = British Thermal Units Per Hour

These low pressure gas-fired hot water boilers are design certified by CSA International for use
with natural and propane gases. The boilers are constructed and hydrostatically
tested for a
maximum working pressure of 50 psig (pounds per square inch gage) in accordance with
AS.ME
(American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section
IV Standards for heating boilers.
++ AFUE (Annual Fuel Utilization Efficiency)
(Department of Energy) test procedure.

and Heating Capacity

is based on the D.O.E.

The Boilers are certified in accordance with ANSI (American National Standards
Z21.13 standards as gas-fired, direct vent, condensing, hot water boilers.

Institute)

The Heating Capacity indicates the amount of heat available after subtracting the losses up the
stack. Most of this heat is available to heat water. A small portion is heat from the jacket and
surfaces of the boiler, and it is assumed that this heat stays in the structure. The Net I=B=R
Rating represents the portion of the remaining heat that can be applied to heat the radiation or
terminal units (i.e. finned tube baseboard, cast iron radiators, radiant floor, etc.). The difference
between the Heating Capacity and the Net I=B=R Rating, called the piping and pickup
allowance, establishes a reserve for heating the volume of water in the system and offsetting
heat losses from the piping. The Net I=B R Ratings shown are based on a piping and pickup
factor of 1.15 in accordance with the I=B=R Standard as published by the Hydronics Institute.
The Net I=B=R Rating of the boiler selected should be greater than or equal to the calculated
peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot
water heating systems. The manufacturer
should be consulted before selecting a boiler for
installations having unusual piping and pickup requirements.
BOILERS

FOR USE AT HIGH ALTITUDE

The boilers are factory equipped for operation at altitudes ranging from 0-2,000 feet above sea
level. For use of these boilers at altitudes above 2,000 feet above sea level, the gas input
ratings (MBH) must be reduced.

U.S.A. ONLY: For altitudes above 2,000 feet above sea level, input ratings should be reduced
as shown in tables IA, C, & E for natural gas boilers or in tables 1B, D & F for propane fired
boilers. Reduced input ratings are achieved by the natural deration of the gas at higher
elevations and fine tuned by adjusting the manifold pressure.
CANADA ONLY: For altitudes in the range of 2,000-4,500 feet above sea level, boilers may be
field equipped for use at high altitude by using a certified high altitude conversion kit. The change
in main burner orifice size results in a 10% reduction of the boiler gas input rating (MBH).
The conversion shall be carried out by a manufacturer's
authorized representative,
in
accordance with the requirements of the manufacturer,
provincial or territorial authorities having
jurisdiction, and in accordance with the requirements of the CSA-B 149.1 and CSA-B 149.2
Installation Codes. The certified field conversion kit includes a conversion data plate, indicating
that the boiler has been converted for high altitude use. The correct conversion information must
be entered on the conversion data plate.

TABLE

1A MODEL-50

ELEVATION
NOMINAL

(FEET)
INPUT

HEAT CAPCITY

(MBH)
(MBH)

NET I=B=R RATING
GAS ORIFICE
MANIFOLD
(INCHES

PRESSURE

PRESSURE

TABLE

WATER

INPUT

MANIFOLD

PROPANE

(MBH)
(MBH)

NET I=B=R RATING
GAS ORIFICE

(MBH)

DRILL SIZE

PRESSURE
WATER

PRESSURE

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

50.0

48.0

47.8

47.5

46.0

44.0

43.5

42.0

450

43.2

43.0

42.8

41.4

39.6

39.2

37.8

39.0

37.4

37.3

37.1

35.9

34.3

34.0

32.8

.0615

.0615

.0615

.0615

.0615

.0615

.0615

.0615

2.5

2.7

3.0

3.2

3.1

3.0

2.8

2.7

1.55

1.55

1.55

1.55

1.55

1.55

1.55

1.55

GAS HIGH ALTITUDE

RATINGS

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

50.0

49.0

49.0

49.0

48.0

46.5

46.0

44.0

450

44.1

44.1

44.1

43.2

41.9

41.4

39.6

39.0

38.2

38.2

38.2

37.4

36.3

35.9

34.3

.0492

.0492

.0492

.0492

.0492

.0492

.0492

.0492

2.5

2.8

3.1

3.4

3.4

3.5

3.5

3.5

1.55

1.55

1.55

1.55

1.55

1.55

1.55

1.55

COLUMN)

SWITCH

WATER

RATINGS

COLUMN)

(FEET)

HEAT CAPCITY

(INCHES

SETPOINT

1B MODEL-50

NOMINAL

GAS HIGH ALTITUDE

COLUMN)

SWITCH

ELEVATION

(INCHES

(MBH)

DRILL SIZE

WATER

(INCHES

NATURAL

SETPOINT

COLUMN)

TABLE lC

MODEL-75

ELEVATION
NOMINAL

(FEET)
INPUT

HEAT CAPClTY
NET I=B=R

(INCHES

DRILL SIZE

1D

HEAT CAPClTY

DRILL SIZE

INPUT

NET I=B=R

(INCHES

(MBH)
(MBH)

DRILL SIZE

PRESSURE
WATER

PRESSURE
(INCHES

(MBH)

RATING

GAS ORIFICE
MANIFOLD

NATURAL

(FEET)

HEAT CAPClTY

COLUMN)

SWITCH

WATER

SETPOINT

NOMINAL

HEAT CAPClTY
NET I=B=R

(MBH)
(MBH)

RATING

GAS ORIFICE
MANIFOLD

PROPANE

(FEET)
INPUT

(MBH)

DRILL SIZE

PRESSURE
WATER

PRESSURE

COLUMN)

SWITCH

WATER

GAS HIGH ALTITUDE

RATINGS

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

75.0

70.0

69.0

68.0

63.5

58.0

56.5

52.0

68.0

63.0

62.1

61.2

57.2

52.2

50.9

46.8

58.9

54.6

53.8

53.0

49.6

45.2

44.1

40.6

.0760

.0760

.0760

.0760

.0760

.0760

.0760

.0760

2.5

2.7

2.8

3.0

2.8

2.6

2.3

2.1

1.35

1.35

1.35

1.35

1.35

1.35

1.35

1.35

GAS HIGH ALTITUDE

RATINGS

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

75.0

70.0

69.0

67.0

66.0

64.5

64.0

62.0

68.0

63.0

62.1

60.3

59.4

58.1

57.6

55.8

58.9

54.6

53.8

52.3

51.5

50.4

49.9

48.4

.0605

.0605

.0605

.0605

.0605

.0605

.0605

.0605

2.5

2.4

2.3

2.2

2.2

2.2

2.3

2.3

1.35

1.35

1.35

1.35

1.35

1.35

1.35

1.35

GAS HIGH ALTITUDE

RATINGS

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

100.0

97.0

96.0

95.0

90.0

84.0

82.0

76.0

90.0

87.3

86.4

85.5

81.0

75.6

73.8

68.4

78.0

75.7

74.9

74.1

70.2

65.5

64.0

59.3

.0860

.0860

.0860

.0860

.0860

.0860

.0860

.0860

2.5

2.9

3.3

3.7

3.4

3.2

2.9

2.6

1.17

1.17

1.17

1.17

1.17

1.17

1.17

1.17

COLUMN)

1F MODEL-100

ELEVATION

(INCHES

SETPOINT

COLUMN)

1E MODEL-100

NOMINAL

(INCHES

COLUMN)

SWITCH

WATER

ELEVATION

TABLE

(MBH)

PRESSURE

PRESSURE

TABLE

(MBH)

WATER

(INCHES

PROPANE

(MBH)

RATING

GAS ORIFICE
MANIFOLD

COLUMN)

(FEET)
INPUT

NET I=B=R

SETPOINT

MODEL-75

ELEVATION
NOMINAL

COLUMN)

SWITCH

WATER

(INCHES

(MBH)

PRESSURE

PRESSURE

TABLE

(MBH)

WATER

(INCHES

(MBH)

RATING

GAS ORIFICE
MANIFOLD

NATURAL

SETPOINT

COLUMN)

GAS HIGH ALTITUDE

RATINGS

0-2,000

3,000

4,000

5,000

6,000

7,000

7,500

8,500

100.0

95.0

94.0

92.0

92.0

91.5

91.5

91.0

90.0

85.5

84.6

82.8

82.8

82.4

82.4

81.9

78.0

74.1

73.3

71.8

71.8

71.4

71.4

71.0

.0670

.0670

.0670

.0670

.0670

.0670

.0670

.0670

2.5

2.7

2.9

3.1

3.2

3.3

3.4

3.5

1.17

1.17

1.17

1.17

1.17

1.17

1.17

1.17

I.

2.

3.

Read the entire installation manual before beginning the installation. Failure to follow these
rules for safe installation and operation and these instructions could cause a malfunction of
the boiler and result in death, serious bodily injury, and/or property damage.
Check all applicable state and local building codes and utility company requirements
before installation. The installation must conform with these requirements
in their
entirety. In the absence of these codes, use NFPA Installation Codes and good
industry practice.
Before servicing the boiler - allow the boiler to cool. Always shut off any electricity and
gas supply connected to the boiler prior to servicing.

4.

Inspect gas line for leaks.

5.

Be certain gas input rate is correct. Over firing may result in early failure of the boiler
sections. This may cause dangerous operation. Under firing may result in too much air
for the pre-mix burner causing poor or loss of combustion.

6.

Never vent the products of combustion from this boiler to an enclosed space. Always
vent to the outdoors. Never vent to another room or to inside a building.

7.

Be sure there is adequate

8.

Follow a regular service and maintenance schedule for efficient and safe operation.
Keep boiler area clean of debris and free of combustible and flammable materials.

outdoor

air supply to boiler.for

complete

combustion.
9.

10. Proper through the wall or through the roof combustion venting shall be in accordance with the
materials and methods described in this manual. Installation must comply with local codes.
11. This boiler and related hot water heating systems are not do it yourself
must be installed and serviced by qualified professionals.

items. They

WARNING
This boiler has been equipped for residential installations. If used for commercial applications, any
additional code requirements must be adhered to for installation. This may require additional
controls including but not limited to a low water cut off, a manual reset high temperature limit, and
wiring and/or piping modifications. The manufacturer
is not responsible for any field installation
changes made to a boiler installation which are not described or acknowledged
in this manual.

Complete
A=

all of the following

prior to installing

the boiler.

CODES
This boiler product is a gas-fired, direct vent, condensing boiler and must be installed in
accordance with all applicable federal, state and local building codes including, but not
limited to the following:
United
Canada

States
-

-Installation shall conform with National Fuel Gas Code (NFPA-54/ANSl
Z223. l-latest edition)
Installation shall be in accordance with CSA B 149.1 and .2. installation
codes.

Where required by the authority having jurisdiction, the installation must conform to the
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices
for Automatically Fired Boilers, No.CSD-1.
The installationmust conform to the requirementsof the authorityhavingjurisdiction or, in the
absence of such requirements,to the NationalFuel Gas Code,ANSI Z223.1 - latest revision.
Installers -

Follow local regulations with respect to installation of CO (Carbon
Monoxide) Detectors. Follow maintenance recommendations in this manual.

Techniciens -Veuillez vous conformer a la reglementation en vigueur concernant 1'
installations des detecteurs d'oxyde de carbone. Suivre les consignes
d'entretien figurant dans le manuel d'instruction ci-joint.
B. BOILER

SIZING

Check to be sure you have selected the boiler with the proper capacity before starting
the installation. The I=B R Rating of the boiler selected should be greater than or equal
to the calculated peak heating load (heat loss) for the building or area(s) served by the
boiler and associated hot water heating systems. See the table "BOILER RATINGS
AND CAPACITIES".
•

Heat loss calculations

C. CONSIDERATIONS

should be based on approved

FOR BOILER

Before selecting
considered.

industry methods.

LOCATION

a location for the boiler, the following

with the correct type of gas (natural

should be considered.

Each boiler

•

Supplied

•

Connected to a suitable combustion air intake piping system to supply the correct
amounts of fresh (outdoor) air for combustion.
(maximum length 80' for the Model-100
boiler, and maximum length 100' for the Model-75 and Model-50 boilers).

•

Connected
to a suitable venting system to remove the hazardous
products of gas
combustion (maximum length 80' for the Model-100 boiler, and maximum length 100' for
the Model-75 and Model-50 boilers).

•

Connected

•

Supplied

•

Connected
boiler)

•

Placed on level surface

•

Condensate drain line must be pitched down to floor drain or external condensate
pump with reservoir at ¼" per foot (wood frame or blocks may be used to raise boiler).

to a suitable
with a suitable
to a properly

gas or propane).

hot water heating system
electrical

supply for all boiler motors and controls.

located thermostat

or operating

(must NOT be installed

control.

(not included

with

on carpeting)

D. LOCATING
TABLE

THE BOILER

2

BOILER
UNIT

CLEARANCES

COMBUSTIBLE

ACCESSIBILITY/

CONSTRUCTION

CLEANING

SERVICING

TOP

1"

8"

8"

LEFT SIDE

1"

1"

1"

RIGHT SIDE

8"

BASE

1"

FRONT

0"

24"

24"

BACK

1"

INTAKE/VENT

PI PI NG

0"

NEAR BOI LER HOT WATER
WATER

PIPING

1"

1. Select a location which is level, central to the piping systems served and as close to the
vent and air intake terminals as possible.
2. Accessibility clearances, if more stringent (i.e. larger clearances) than required fire protection
clearances, must be used for the boiler installation. Accessibility clearances may be achieved
with the use of removable walls or partitions.
3. The boiler is approved for installation in closets and on combustible floors. This boiler
shall NOT be installed on carpeting.
4. The clearances shown in Table 2 indicate required clearances per IAS listing. A minimum
1" clearance must be maintained between combustible construction and each of the left,
top and back surfaces of the boiler. A minimum 8" clearance is required on the right side,
to allow room for the inlet air pipe. An 18" clearance must be maintained at a side where
passage is required to access another side for cleaning or servicing, inspection or
replacement of any parts that normally may require such attention. Allow at least 24" at
the front and left side and 8" at the top for servicing. No clearances are required to
venting or combustion air intake piping.
5. Equipment shall be installed in a location which facilitates the operation of venting and
combustion air intake piping systems as described in this manual.
6. Advise owner of boiler to keep venting and combustion air intake passages free of obstructions.
both the venting and combustion air intake piping systems connected to the outdoors must
permit flow through the piping systems without restrictions for the boiler to operate.
7. The boiler shall be installed such that the automatic gas ignition system components are
protected from water (dripping, spraying, rain, etc.) during operation and service
(circulator replacement,
control replacement, etc.).
E. COMBUSTION

AIR AND VENT

PIPE REQUIREMENTS

This boiler requires a dedicated direct vent system. In a direct vent system, all air for
combustionis taken directly from outside atmosphere, and all flue products are discharged
outside atmosphere.

to

Combustion air and vent pipe connections must terminate together in the same atmospheric
pressure zone, either through the roof or sidewall (roof termination preferred). See Fig.9 & 10
for required clearances.

CAUTION
KEEP BOILER
MATERIALS,

AREA CLEAN
VAPORS

OF DEBRIS

AND FREE OF FLAMABLE

AND COMBUSTIBLE

AND LIQUIDS

WARNING
When vent pipe is exposed to temperatures
below freezing, such as when it passes through an
unheated space or when a chimney is used as a raceway, vent pipe must be insulated with 1/2"
Armafiex or equivalent. In extreme cold climate areas, use 3/4" Armafiex or equivalent.
Combustion

air must be clean outdoor

air. Combustion

air must not be taken from inside struc-

ture because that air frequently is contaminated
by halogens, which include fluorides, chlorides,
phosphates, bromides and iodides. These elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, paints, adhesives and other household products.
Locate combustion
pump house.

air inlet as far away as possible

from swimming

All combustion air and vent pipes must be airtight and watertight.
piping must also terminate exactly as shown in Fig.9 or 10.

pool and swimming
Combustion

pool

air and vent

Vent connections serving appliances vented by natural draft shall not be connected
portion of mechanical draft systems operating under positive pressure.

into any

Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in
well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
FAILURE TO FOLLOW
PROPERTY DAMAGE,

F. CONDENSATE

THE AFOREMENTIONED
WARNINGS
PERSONAL INJURY, OR DEATH.

COULD

RESULT

IN FIRE,

DRAIN REQUIREMENTS

Condensate drain line to be pitched down to floor drain at a minimum of I/4" per foot. An external
condensate pump (not furnished) may be used if floor drain is not available. The condensate
pump must be designed for flue gas condensate application
NOTE:I.

Condensate
be used.

trap is built into the boiler, an external

trap is not required

and should not

2. Wood frame or blocks may be used to raise the boiler to maintain drain pitch or to be
above external condensate pump reservoir.
3. There is a 115 volt AC receptacle provided on the service switch junction box which
is located at the boiler right side, to provide power for an external condensate
pump (if needed).
G. FOUNDATION

REQUIREMENTS

Boiler must be placed on level surface.

Boiler is NOT to be installed

10

on carpeting.

NOTE:

1. If boiler is not
feet are located
2. Wood frame or
above external

H. REMOVAL

OF EXISTING

level condensate drain lines will not function properly. Adjustable
on the boiler to make up for minor surface irregularities or tilt.
blocks may be used to raise boiler to maintain drain pitch or to be
condensate pump reservoir.
BOILER

FROM COMMON

VENT SYSTEM

When an existing boiler is removed from a common venting system, the common venting
system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each
appliance remaining connected to the common venting system placed in operation, while the
other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings

in the common

venting system.

2. Visually inspect the venting system for proper size and horizontal pitch and determine
there is no blockage, or restrictions, leakage, corrosion and other deficiencies which could
cause an unsafe condition.
3. Insofar as is practical, close all. building doors and windows and all doors between the
space in which the appliances remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes dryer and any appliance not
connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fire dampers.
4. Place in operation the appliance being inspected.
thermostat so appliances will operate continuously.

Follow

the lighting

instructions.

Adjust

5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation.
Use the flame of a match or candle, or the smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting
system properly vents when tested as outlined above, return doors, windows, exhaust fans
and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the
installation conforms with the National Fuel Code, NFPA-54/ANSI
-Z223. l-latest revision,
or section 5 of CSA-B 149 for Canadian standards. When resizing any portion of the
common venting system, the common venting system should be resized to approach the
minimum size as determined using the appropriate tables in part 11 in the National Fuel
Gas Code, NFPA-54/ANSIZ223.1-1atest revision, or section 5 of CSA-B 149 for
Canadian standards.

The boiler should be placed to provide the most direct connections
and system piping as possible.
Place
boiler
truck
short

to the combustion

air, vent

crated boiler as close to selected location as possible and uncrate boiler. The uncrated
may be moved into position with an appliance dolly or 2-wheel hand truck. The dolly or hand
should be inserted under the left hand side of the boiler. It is possible to slide the boiler for a
distance on a smooth floor or surface.

NOTE:

Refer to manual section
ing and maintenance.

"LOCATING

THE BOILER"

for required

clearances

for servic

CAUTION
Copper supply and return piping, must NOT be installed directly into aluminum boiler section
casings due to galvanic corrosion between dissimilar metals. Iron or steel bushings or pipe
nipples should be used between copper system piping and boiler to make final connection to
boiler. Also, the use of dielectric unions is acceptable. The packaged boiler is furnished with iron
piping in the front boiler section for the supply and return connections.

When the installation of the boiler is for a new heating system, first install all of the radiation
units (panels, radiators, baseboard, or tubing) and the supply and return mains. After all heating
system piping and components have been installed, make final connection of the system piping
to the boiler. A hot water boiler installed above radiation level must be equipped with a low water
cut off device. A periodic inspection is necessary us is flushing of float type devices, per low
water cut off manufacturers
specific instructions.

A. SUPPLY AND RETURN LINES
The packaged boiler unit is set up to receive 1 1/4" NPT supply and return piping from top
access. The boiler unit can also be piped from the left side by turning the supply elbow, and
from the rear of the unit by removing plugs in the rear boiler section.

NOTE: The circulator pump and isolation valves are furnished within a carton inside the boiler
cabinet and can be installed at the installer preferred location.

12

SERVICE
VALVE

SUPPLY
SYSTEM

\

'_

_/_

CIRCULATOR

RETURN
SYSTEM

PURGE
VALVE

SERVICE
VALVE

FIGURE

2

SINGLE

TO

ZONE BOILER

13

PIPING

FROM

(DRAIN)

//--

ZONE
VALVE

VALvEZONE
SERVICE

/

SUPPLY
ZONES

TO

ZONE SERVICE
VALVE

CIRCULATOR
RETURN
ZONES

FROM

PURGE
(DRAIN)
VALVE S

SERVICE

//
_-/ZONE
VALVE

¢P

FIGURE

3

MULTI ZONE BOILER

14

PIPING WITH ZONE VALVES

////-

ZONE
SERVICE
VALVE
SUPPLY

-_7

TO

ZONES
ZONE
SERVICE
VALVE

CIRCULATORS

FLOW CHECK
VALVE

FROM
ZONES

PURGE
VALVES

(DRAIN)

SERVICE

ZONE
VALVE

_9

jJ
j"

J

j_

jJ
J

NOTE: When zoning with circulators, the furnished circulator pump should be used as one of the
zone pumps. Each stripped end of the electrical wires for the circulator pump inside the junction
box should be taped or wire nutted to prevent short circuits. Unplug the circulator pump wiring at
the integrated

boiler control.

FIGURE

4

MULTI ZONE

BOILER

15

PIPING

WITH CIRCULATORS

RELIEF VALVE _._
DISCHARGE
PIPING

'\.

)

"\\

\\

FIGURE
B. PRESSURE

5

SINGLE

ZONE BOILER

PIPING

RELIEF VALVE

The boiler is furnished with a factory installed relief valve in the top of the boiler. Provide ¾"
piping from the supplied relief valve to a local floor drain, but leave an air gap between piping
and drain. No shutoff of any description shall be placed between safety relief valve and the
boiler, or on the discharge pipes between such safety valve and the atmosphere.
Installation
of the safety relief valve shall conform to ANSl/ASME
Boiler and Pressure Vessel Code,
Section IV. The manufacturer
is not responsible for any water damage.
C. EXPANSION

TANK AND MAKE-UP

WATER

Determine required system fill pressure, system design temperature,
and system water
content. Boiler contains 2.6 gallons (U.S.). Size expansion tank accordingly.
Consult
expansion tank manufacturer
for proper sizing information.
Connect properly sized
expansion tank (not furnished) as shown in Fig. 6 for diaphragm type expansion tank and
Fig. 7 for conventional closed type expansion tanks. For diaphragm type expansion tanks,
adjust the tank air pressure to match the system fill pressure.
Install air vent (furnished) as
shown for diaphragm type expansion tank system only. Install make-up water connections
as shown per local codes. If a pressure reducing valve is used, adjust to match the system
fill pressure.
In connecting the cold make-up water supply to the boiler, make sure that clean
water supply is available. When the water supply is from a well or pump, sand strainer
should be installed at the pump.

16

_---- MANUAL
VALVE

FILL

////

AUTOMATIC
VENT*

AIR

3/4"

TEE*

3//4 '' NIPPLE
(FURNISHED
AND INSTALLED
ON
PACKAGED BOILER)

COLD WATER
FILL

3/4"

* -

STREET

FURNISHED
IN
PARTS BAG.

/

/
//

/

_JDIAPHRAGM
EXPANSION

TYPE
TANK

/
//

COMBINATION
QUICK FILL
VALVE, STRAINER,
CHECK
VALVE AND PRESSURE
REDUCING
VALVE

FIGURE

6

DIAPHRAGM

TYPE EXPANSION

17

TANK

ELL*

PIPING

CLOSED
/_

/_--_-'_

"\\

_'f

EXPANSION

TYPE
TANK

/
j_

_EXPANSION
TANK
SERVICE
VALVE
(GATE
VALVE
OR
FULL PORT
BALL VALVE)

MANUAL
VALVE

COLD
FILL

L_

FILL

WATER=_
\

CHECK
AND PRESSURE
REDUCING
VALVE

FIGURE

7

CONVENTIONAL

(closed type) EXPANSION

18

TANK PIPING

_

OPEN
DRAIN PIPE TO
BE PITCHED
DOWN
TO FLOOR DRAIN
AT A MINIMUM
1/4"
PER FOOT

"'- .....

TO
DRAIN

THREADED
NIPPLE
(INSTALLED)

FIGURE
D. CONDENSATE

CONDENSATE

drain and fittings.

½" PVC tee to overflow

The ½" diameter

/2"SLIPxl
!2"NPT
IN PARTS BAG

- DRAIN PIPING

trap is not required

Condensate

and should NOT be used.

drain to be pitched down to floor drain at

schedule

fitting as shown in Fig. 8.

40 PVC or CPVC condensate

and ASTM D 1785 or D2846.

to ASTM D2564 or F493.
cement.
A condensate
(sanitary

8

PVC TEE
1/2"SLIPxI
FURNISHED

of ¼" per foot.

Install furnished

standards

/

trap is built into the boiler, an external

½" PVC condensate

a minimum

(PVC)

DRAIN PIPING

The condensate
Provide

CONDENSATE
DRAIN

In Canada,

pump with a reservoir

Schedule

drain and pipe fittings

40 PVC or CPVC cement

use CSA or ULC certified

(not furnished)

to ANSI

40 PVC or CPVC drain pipe

may be used to remove

line) above boiler if a floor drain is not available

19

schedule

must conform

and primer must conform

or its in accessible.

condensate

to a drain line

E. FILLING CONDENSATE
TRAP WITH WATER ON THE INITIAL
SATE TRAP MUST BE MANUALLY FILLED WITH WATER

START

UP THE CONDEN

The following are the steps required to initially fill the condensate trap for start up, these steps
are only required at the initial start up or if maintenance requires draining of the condensate trap:
1. Disconnect

the vent condensate

drain line from the bottom of the vent tee on the boiler.

2. Pour about 1 cup of cold tap water into the vent drain line with a proper funnel.
3. Excess water should go through the overflow and out through the condensate drain line.
Verify proper operation of the drain line (or external condensate pump if used).
4. Reinstall
F. CHILLED

the vent drain line.
WATER

PIPING

The boiler, when used in connection with a refrigeration system, must be installed so the
chiller medium is piped in parallel with the boiler with appropriate valves to prevent the chilled
medium from entering the boiler.
The boiler piping system of a hot water boiler connected to heating coils is located in air
handling units where they may be exposed to refrigerated air circulation must be equipped
with flow control valves or other automatic means to prevent gravity circulation of the boiler
water during cooling cycle.

A. CONNECTIONS

AND TERMINATION

For boilers connected to gas vents or chimneys, vent installations shall be in accordance with
part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI 2223. l-latest revision,
CAN/CGA-B
149.1 and B 149.2, and applicable provisions of the local building codes.
Provisions for combustion and ventilation air must be in accordance with section 5.3, Air For
Combustion and Ventilation, of the National Fuel Gas Code,ANSI 2223. l-latest revision,
CAN/CGA-B

149.1 and B 149.2, or applicable

provisions

of the local building code.

These boilers require a dedicated direct vent system. All air for combustion
is taken directly
from outdoors through the combustion air intake pipe. All flue products are discharged to the
outdoors through the vent pipe.
.

.

See Fig.9 & 10 for combustion air and vent pipe roof and sidewall termination. (Roof termi
nation is preferred) Combustion air and vent pipes must terminate together in same atmo
spheric pressure zone as shown. Construction through which vent and air intake pipes
may be installed is a maximum 24 inches, minimum I/4" thickness.

Combustion air and vent pipe fittings must conform to American National Standards Insti
tute (ANSI) standards and American Society for Testing and Materials (ASTM) standards
D1784 (schedule-40
CPVC), D1785 (schedule-40 PVC), D2665 (PVC-DWV), D2241
(SDR-21 and SDR-26 PVC), D2661 (ABS-DWV), or F628 (schedule-40 ABS). Pipe cement
and primer must conform to ASTM standards D2564 (PVC) or D2235 (ABS).

20

In Canada construct all combustion air and vent pipes for this unit of CSA or ULC certified
schedule-40 CPVC, schedule-40 PVC, PVC-DVVV or ABS-DVVV pipe and pipe cement.
SDR pipe is NOT approved in Canada.
.

Combustion air and
change (to 3") must
for proper drainage
155°F, the first five
PVC. If any elbows
Two (2) - 30" pieces

vent piping connections on boiler are sized for 2" pipe. Any pipe size
be made outside of the boiler casing in a vertical run of pipe to allow
of vent condensate. Due to potential for flue gas temperatures
over
(5) feet of vent pipe must be CPVC, the remaining vent pipe can be
are employed within the first 5 feet of vent, they must be CPVC too.
of 2" CPVC pipe are furnished with the boiler.

NOTE: The transition
4.

Combustion

from 2" pipe to 3" pipe must be made in a vertical run.

air and vent piping lengths,

2 FEET

IN

LENGTH

20 FEET IN
LENGTH

20 FEET IN
LENGTH

100 FEET IN
LENGTH

+

AND UP TO

+

AND UP TO

4-90 °

4-90 °

4-90 °

4-90 °

ELBOWS

ELBOWS

ELBOWS

ELBOWS

The first 5 feet of "TOTAL

EQUIVALENT

LENGTH"

of vent piping run must

be CPVC:

The length of pipe is counted from the boiler jacket (air intake pipe) or from vent tee (vent
pipe).For additional elbows, reduce the maximum vent length as shown:
2" 90 degree elbow -1 ½ feet per additional elbow.
3" 90 degree elbow - 3 feet per additional elbow.
Example: To add 2 additional 90 degree elbows to a 3" pipe for a 75 boiler.
Each elbow is 3 additional feet per 90 degree elbow for a total of 6 feet. (1 elbow @ 3
feet + 1 elbow @ 3 feet = 6 additional feet of pipe) The total additional pipe is then
subtracted from the maximum allowable pipe length to give the new maximum length
of 94 feet with 6, 90 degree elbows. ("TOTAL EQUIVALENT
LENGTH":
Original 100
feet max. - 6 feet for 2 additional elbows = new 94 feet maximum length).
.

Combustion air and vent piping to be pitched back to boiler at minimum ¼" per foot from
intake and vent terminals so that all moisture in combustion air and vent piping drains to
boiler. Pipes must be pitched continuously with no sags or low spots where moisture can
accumulate and block the flow of air or flue gas. Combustion air and vent pipes must be
airtight and watertight.

21

.

Consideration
for termination

for the following should be used when determining
of combustion air and vent piping.

• Comply with all clearances
• Termination
conditioning

required

should be positioned
equipment.

as stated in paragraph

where vent vapors will not damage

• Termination should be positioned where it will not be subjected
foreign objects, such as stones, balls, etc..
should be positioned

location

7.

• Termination should be positioned so that it will not be effected
leaves, snow, or recirculated flue gases.

• Termination

an appropriate

plants/shrubs

or air

by wind eddy, air born
to potential

damage

by

where vent vapors are not objectionable.

• Put vent on a wall away from the prevailing winter wind. Locate or guard the vent to
prevent accidental contact with people or pets.
• Terminate the vent above normal snowline. Avoid locations where snow may drift and
block the vent. Ice or snow may cause the boiler to shut down if the vent becomes
obstructed.
• Under certain conditions, flue gas will condense, forming moisture, and may be corrosive.
In such cases, steps should be taken to prevent building materials at the vent from being
damaged by exhaust of flue gas.
.

The venting system shall terminate at least 3 feet above any forced air inlet (except the
boiler's combustion air inlet) within 10 feet. The venting system shall terminate at least 12
inches from any air opening into any building. The bottom of the vent shall be located at
least 12 inches above grade. Termination of the vent shall be not less than 7 feet above an
adjacent public walkway. The vent terminal shall not be installed closer than 3 feet from the
inside corner of an L shaped structure. Termination of the vent should be kept at least 3
feet away from vegetation. The venting system shall terminate at least 4 feet horizontally
from, and in no case above or below, unless a 4 foot horizontal distance is maintained, from
electric meters, gas meters,

VERTICAL
BETWEEN

regulators,

and relief equipment.

COMBUSTION

8" MINIMUM
SEPERATION
COMBUSTION

AIR INTAKE AND VENT

MAINTAIN
12" MINIMUM
CLEARANCE
ABOVE HIGHEST
ANTICIPATED
SNOW LEVEL

FIGURE

9 ROOF VENT/INTAKE

22

TERMINATIONS

J
MAINTAIN
12" MINIMUM
CLEARANCE
ABOVE
HIGHEST
.

_

ANTICIPATED
GRADE

J'_

SNOW

MAXIMUM
SEPERATION
15"

.----," J_MAXIMUM
18"
MAXIMUM

I

LESS THAN 12" CLEARANCE

I

12" MINIMUM

__"

j_,

12" SEPERATION

j-

_'90o_

// 0_AOKET--_I_

OOMBUST_ON
AIR
INTAKE_

J

BETWEEN

BOTTOM

OF

AND
BOTTOM
O_
VE__

/

f/J

MAINTAIN
_-_

/

MAXIMUIvl

-'_

SEPERATION
J

CLEARAN

12" MINIMUM
CE A BOVE

ANTICIPATED
GRADE

SNOW

H IGHEST
LEVEL

OR

18"
_

MAXIMUM

I
FIGURE

12" OR MORE CLEARANCE
10 SIDEWALL

VENT/INTAKE
23

I
TERMINATIONS

LEVEL

OR

VENT/INTAKE
2"

(50.8ram)

COMBUSTION
INTAKE

AIR
PIPING

S

"\_

_/]7
/
/

TERMINATIONS

/
2"

(50.8mm)

CPVC

VENT

PIPING

(FURNISHED)

--x
\
x

2"

(50.8ram)

CPVC

COUPLING

(FURNISHED)

\\

2" (50.8mm)

DIAMETER

COMBUSTION

/_/s/\\\\\\

PIPING

-

15' (4.57m)
WITH
5'

VENTAND

AIR INTAKE

MAXIMUM

LENGTH

4 - 900 ELBOWS

TOTAL

FOR Kg0-100

20' (6.10m) MAXIMUM
LENGTH TOTAL WITH
4 - 90 ° ELBOWS
FOR K90 - 75 AND K90 - 50

1.52m

2' (.61m) MINIMUM
LENGTH TOTAL
WITH 4 - 90 ° ELBOWS
FORALL

\
4

EXHAUST

TEE

(FURNISHED)

3" (76.2mm) COMBUSTION
INTAKE PIPING

AIR

/?
,/ /
/
/
/
/
/
/

_\
_.
\
\,

2" (50.8mm) CPVC VENT PIPING
(FURNISHED)

/_

VENT/INTAKE
TERMINATIONS

_--

3" (76.2mm)

_
_
2" (50.8mm)

CPVC

COUPLING

VENT

PIPING

_

\

_

TRANSITION
2" (5O.8mm)
VERTICAL

FITTING
O TO 3" (76.2mm)

O IN

RUN

(FURNISHED)
3" (7B.2mm)
COMBUSTION
FOR

K90 - 100

80' (24,38m)
WITH

5'
1.52m

MINIMUM

K90

lOB'

(30.48m)

- 75 AND

TRANSITION
2" (50.8ram)
VERTICAL

\_
/i

LENGTH
K90

MAXIMUM

11

COMBUSTION

24

TOTAL

- 50
LENGTH

MINIMUM

LENGTH

4 - 90 _ ELBOWS

FITTING
!21TO
RUN

3" (76.2mm)

O IN

EXHAUST TEE
(FURN SHED)

/-

FIGURE

TOTAL

TOTAL

4 -90 ° ELBOWS

20' (6.10m)
WITH

LENGTH

4 -90 ° ELBOWS

FOR

WITH

MAXIMUM

4 - 90 ° ELBOWS

15' (6.10m)
WITH

DIAMETER
VENT AND
AIR INTAKE
PIPING

AIR AND VENT PIPING

TOTAL

B. INSTALLATION
1.

Attach combustion air intake piping to supplied Fernco 2" coupling on mixer. Attach
vent piping to furnished 2" CPVC vent tee on draft inducer outlet.
NOTE: All pipe joints are to be water tight.
2.
Working from the boiler to the outside, cut pipe to required length(s).
3. Deburr inside and outside of pipe.
4.
Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
6.
Check dry fit of pipe and mark insertion depth on pipe.
NOTE: It is recommended
that all pipes be cut, prepared, and pre-assembled
before
permanently cementing any joint.
7. After pipes have been cut and pre-assembled,
apply cement primer to pipe fitting
socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe
and fitting socket (over primer). Apply cement in light, uniform coat on the inside of
socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, insert pipe into socket with a'/a turn twist. Be sure pipe is fully
inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around
perimeter of a properly made joint.
10. Handle pipe joint carefully until cement sets.
11. Support combustion air and vent piping a minimum of every 5 feet using pre-formed
metal hanging straps. Do not rigidly support pipes. Allow movement due to expansion
and contraction.
12. Slope combustion air and vent pipes toward boiler a minimum of I/4" per linear foot with
no sags between hangers.
13. Use appropriate methods to seal openings where vent and combustion air pipes pass
through roof or side wall.

A. CHECK

GAS SUPPLY

The gas pipe to your boiler must be the correct size for the length of run and for the total
BTU per hour input of all gas utilization equipment connected to it. See Table 3 for the
proper size. Be sure your gas line complies with local codes and gas company
requirements.
The boiler and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of '/z psig (3.5kpa).
The boiler must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than '/z psig (3.50ka).
NATURAL
MAXIMUM

GAS SUPPLY

MINIMUM

GAS SUPPLY

PRESSURE
PRESSURE
25

GAS

PROPANE

10" w.c.

14" w.c.

7" w.c.

10" w.c.

GAS

B. CONNECTING

THE GAS PIPING

Refer to Fig.12 for
The gas line enters
supply pipe through
and pipe assembly.
supply piping. The
1.

the general layout at the boiler. It shows the basic fittings you will need.
the boiler from the right side jacket panel. The boiler may receive the gas
the left side, or rear jacket panel by relocating the gas valve connector
The boiler is equipped with a '/z" NPT connection on the gas valve for
following rules apply:

Use only those piping materials and joining methods listed as acceptable by the authority
having jurisdiction, or in the absence of such requirements, by the National Fuel Gas
Code, ANSI Z223.1- latest revision. In Canada, follow the CSA- B 149.1 and .2

Installation Codes for Gas Burning Appliances and Equipment.
2.
Use pipe joint compound suitable for liquefied petroleum gas on male threads only.
3. Use ground joint unions.
4.
Install a sediment trap upstream of gas controls.
5. Use two pipe wrenches when making the connection to the gas valve to keep it from
turning.
6.
Install a manual shutoff valve in the vertical pipe about 5 feet above floor.
7. Tighten all joints securely.
8. Propane gas connections should only be made by a licensed propane installer.
9. Two stage regulation should be used by the propane installer.
10. Propane gas piping should be checked out by the propane installer.
C. CHECKING

THE GAS PIPING

After all connection have been made, check immediately for leaks. Open the manual shutoff
valve. Test for leaks by applying soap suds (or a liquid detergent) to each joint. Bubbles forming
indicate leak. CORRECT EVEN THE SMALLEST
LEAK AT ONCE.

WARNING
NEVER

USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

TABLE

3 GAS PIPE SIZES
NATURAL

Length

of

Pipe Capacity-

GAS

BTU Per Hourlnputlncludes

FiRings

Pipe - Ft.
20
40

1/2"
92,000
63,000

3/4"
190,000
130,000

1"
350,000
245,000

1 1/4"
625,000
445,000

60

50,000

105,000
PROPANE GAS

195,000

365,000

Length

of

Pipe - Ft.

Pipe CapacityCopper Tubing*

BTU Per Hourlnputlncludes

Fittings
Iron Pipe

5/8"

3/4"

1/2"

20

131,000

216,000

189,000

393,000

40
60
* Outside diameter

90,000
72,000

145,000
121,000

129,000
103,000

267,000
217,000

26

3/4"

The length of pipe or tubing should be measured

from the gas meter or propane

second stage regulator.

GAS SUPPLY

"

,/

PIP ING

//z

SHIrT-OFF
VALVE

J

SEDIMENT
TRAP

GROUND
UNION

JOINT

/-

FIGURE

12

GAS PIPING

WARNING
TURN OFF ELECTRICAL
POWER AT FUSE BOX BEFORE MAKING ANY LINE
VOLTAGE CONNECTIONS.
FOLLOW LOCAL ELECTRICAL
CODES.
All electrical

work must conform

to local codes as well as the National

NFPA70, latest revision. In Canada,
Codes, CSAC22.1 and .2
A.

ELECTRIC

POWER

electrical

Electrical

Code, ANSI/

wiring shall comply with the Canadian

Electrical

SUPPLY

Prior to making any line voltage connections, service switch at boiler should be in the off
position and the power turned off at the fuse box
Run a separate 120 volt circuit from a sperate over current protection device in the
electrical service entrance panel. This should be a 15 ampere circuit. A service switch has
been pre-wired and located on the exterior boiler jacket. See Fig. 13 for diagram showing
location of service switch junction box and power supply connection points. Connect black
(hot) lead from the power supply
27

to either of the unused brass screws on the service switch. Connect the white (neutral) lead from
the power supply to the white screw on the service switch. Connect the green (ground) lead
from the power supply to the ground (green) screw on the service switch. The receptacle on the
service switch is always powered regardless of whether the switch is on or off, and could be
used as a power supply for an external condensate pump if one is used.
The boiler, when installed, must be electrically grounded in accordance with the requirements of
the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA-70,
latest revision. In Canada, electrical wiring shall comply with the
Canadian Electrical Codes, CSA-C22.1 and .2.
Run a 14 gauge or heavier copper wire from the boiler to a grounded
panel or a properly driven and electrically grounded ground rod.
B. INSTALL

connection

in the service

YOUR THERMOSTAT

The thermostat location has an important effect on the operation of your boiler system.
SURE TO FOLLOW THE INSTRUCTIONS
INCLUDED WITH YOUR THERMOSTAT.

BE

Locate the thermostat about five feet above the floor on an inside wall. It may be mounted directly on the wall or on a vertical mounted outlet box. It should be sensing average room temperature. Avoid the Following:
DEAD SPOTS:
Behind doors
Comers and alcoves

COLD SPOTS:

HOTSPOTS:

Concealed pipes or ducts
Stairwells - drafts
Unheated rooms on
other side of wall

Concealed
Fireplace
TV sets
Radios

pipes

Lamps
Direct sunlight
Kitchens

Set heat anticipator at 0.7 amps. Connect 24 volt thermostat leads to the two(2) yellow wires
located in service switch junction box, located on outer jacket of boiler. See Fig. 13 for service
switch junction box and thermostat field wiring connections.

C. Connect

Circulator

Pump Wiring

See Fig.13 for service switch junction box and circulator pump field wiring connections. A 5 feet
wiring harness with flexible metal conduit is supplied to connect the circulator pump to the service switch junction box. If the two 120 volt circulator wire terminals inside the junction box are
not used, please leave the two wire nuts to prevent the short circuit.
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION
WHEN SERVICING CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION.
VERIFY PROPER
OPERATION AFTER SERVICING.

28

J
WIRE
120 VOLT
CIRCULATOR
Y
ZzzzD--Y

24 VOLT
THERMO STAT
W

BOILER
WIRING
IN

BK

J-BOX

G

CODE

NEUTRAL
HOT

--120
VOLTS
60 HZ i O
POWER SUPPLY

GROUND

--i
SERVICE

COLOR

BK -- BLACK
W = WHITE
G -- GREEN
Y = YELLOW

SWITCH

FIELD

WIRING

\

CONNECTIONS

\

\

\
SERVICE
//_
/

\

J

jJ
_jJ

C_

FIGURE

13

FIELD WIRING
29

CONNECTIONS

/

JUNCTION

SB_TCH
BOX

z

_2

D"
@
®,
D

If any of the original wire as supplied with this appliance
with type 150°C Thermoplastic
wire or its equivalent

D=

FIGURE 14 SCHEMATIC
30

must be replaced,

WIRING

DIAGRAM

it must be replaced

120 VOLT
POWER
SUPPLY
L1
L2

HOT
I

ON/OFF

i
BLK

SWITCH

WHT

P7-2
P7-1

P7-3

2K1

P4-I

CIRCULATOR

MOTOR
P5-3

DRAFT

)>
PI0-2

INDUCER
ROT

5K1

P6-1

SURFACE

P12-1

IGNITER

P12-2

120

PB-2

5K2
H

P1-3
TRANSFORMER

CASTING
TEMPERATURE
SAFETY
SWITCH
(MANUAL
RESET)

,

4K1

3K1

2
GAS VALVE
VRB205A

P3-5

P9-3_

<(
P3-2

P9-2

r

0_c4
• P3-1
@
@

k_ICROPR OCESSOR
ELECTRONIC
LOGIC
_ ]I_ER S

l

DIFFERENTIAL _jR

@

_

PR EESU RE S_5_lmH

P3-3

A;:L
UM,T

P3-9

_}

POWEN

O

PURGE
IGNITER
M_LVE
INDICATOR
LIGHTS
F LA _,'IE

O
O

5__

QUASTAT
CONTROL
_

P3-7

1013-10 CONIROL

BLOWER

../.!_ POWER SUPPLY. PROVIDE
DISCONNECT
MEANS AND
OVERLOAD
PROTECTION AS
REQUIRED USE ONLY COPPER

_" P3-4

THERMOSTAT

WIRE BETWEEN
AND THE UNIT

DISCONNECT

NOTE: "P" LABEL REFERENCE
LOCATION OF CONNECTOR
PLUG
BETWEEN SCHEMATIC AND
LADDER

* CAUTION:

RECEPTACLE
BOILER

--÷_---

DIAGRAM

REFERENCES

FIGURE 15 LADDER WIRING

31

IS LIVE WHEN

SWITCH

IS OFF

PLUG CONNECTION

DIAGRAM

This section provides

a brief description

See the Troubleshooting
sequences of operation
locations

and accessories

found in this boiler.

section of the Service Hints chapter of this installation manual for detailed
and troubleshooting
procedures. See the Repair Parts chapter of this manual

of all control components

A. INTEGRATED

of the key controls

BOILER

and accessories

CONTROL

for

described.

(IBC)

The Integrated Boiler Control (IBC) is a microprocessor
based controller for a high efficiency gas
boiler that monitors all safety controls and which controls the operation of the combustion air blower,
circulator pump, burner, and a combination hot surface igniter/flame
sensor. This controller is not
intended for use with a vent damper. This controller is mounted on the control panel inside of the
boiler and contains four (5) diagnostic indicator lights.

B. GAS CONTROL

VALVE

The electrically controlled 24 Volt Honeywell Model VR8205 Combination Gas Control Valve is
designed to meet the requirements
for use with hot surface ignition systems found in this boiler.
The valve is piped to the gas/air mixer.

C. HOT SURFACE

IGNITER

The 120 volt Hot Surface Igniter heats up to 1800
The igniter is mounted next to the burner through
means for proving the main burner flame by flame
on three (3) consecutive trials for ignition, the IBC

°F to initiate combustion of the gas in the burner.
the gas/air mixer. The igniter also serves as a
rectification. In the event of a lack of flame signal
will lockout. The "VALVE" and "FLAME" diagnostic

indicator lamps (lamp "D" and "E" on the IBC, See Fig. 16) wilt blink indicating the failure mode as a
lack of flame signal. The IBC is manually reset from lockout by either removing and reestablishing
the
thermostat's
call for heat, or by turning the service switch off, then back on.

D. HIGH LIMIT AQUASTAT

CONTROL

The High Limit Aquastat Control determines the maximum boiler water temperature and also
provides a means for protecting the boiler and heating system from unsafe operating conditions
which could damage the boiler. The aquastat is mounted in the ½" NPT control well and ¾"x½"
bushing on the top of the front boiler section at the hot water outlet. The aquastat is tied in with the
IBC and is factory set at 180 °F water temperature.
The high limit setpoint is field adjustable and may
be set anywhere between 100 °F and 200 °F. The field setpoint adjustment for each installation
depends on heating system requirements.
The aquastat automatically
resets when the boiler water
temperature
decreases (5-30 °F adjustable differential). The differential can be adjusted with the
(white) Differential Adjustment Wheel on the aquastat and gives the flexibility
larger the differential, the longer the run cycle of the boiler.
NOTE: The maximum

E. DRAFT

INDUCER

setpoint

of the Aquastat

TEMPERATURE

The Draft Inducer Temperature

SAFETY

must not exceed

for boiler operation.

The

200 °F.

SWITCH

Safety Switch is a disc thermostat

(180 °F setpoint)

located

on the

induced draft fan outlet port. The switch protects the inducer and vent pipe from a potential high
temperature
condition for the discharging flue gases. This condition would typically be a result of
higher aquastat setting or over firing. The temperature
safety switch automatically
resets when the

32

higher aquastat setting or over firing. The temperature safety switch automatically
when the vent temperature decreases. (15 °F switch differential).
F. CASTING

TEMPERATURE

SAFETY

resets

SWITCH

In the event of lack of or loss of water in the boiler, the Casting Temperature
Safety Switch
(300 °F setpoint) installed on the top of the aluminum boiler section shuts off the boiler by
shutting off power to the Integrated Boiler Control (IBC) and causes the Power Indicator Light
to go out. This fault requires manual reset of the casting temperature
safety switch to restart
the boiler. Verify that the boiler is properly filled with water before resetting this switch.
WARNING-Never
run cold water into a hot empty boiler.
G. DIFFERENTIAL

PRESSURE

AIR PROVING

SWITCH

The diaphragm type differential pressure switch is connected by vinyl tubing to the pressure
signal hose adapters. The pressure switch monitors air flow by sensing the diffential
pressure measured in inches of water(" w.c.). The factory settings on these switches are
1.00 "w.c. for Model-100, 1.35 "w.c. for Model-75 and 1.55 "w.c. for Model-50. The contacts
are normally open, and close when the draft inducer is running and causing the diffential
pressure at the switch to exceed the setting. The closed switch proves there is adequate air
flow for combustion. The pressure switch shuts off the main burner if the differential pressure
is inadequate due to a blocked vent pipe or a blocked air intake or blocked boiler sections or
blocked draft inducer. After five (5) minutes of lack of the adequate differential pressure, the
IBC will lockout. The "PURGE" indicator light will blink, indicating a failure to prove adequate
combustion air flow or flue gas flow. The IBC is manually reset from lockout as described in
the Sequence of Operation section of this chapter.
H. DRAFT INDUCER
The draft inducer (blower) provides a means for pulling combustion air into and through the
mixer, the burner, the flue ways of the cast aluminum boiler sections and the flue adapter
before being discharged through the vent piping to the outdoors. See applicable sections for
proper sizing and installation of combustion air and vent piping in this manual.
CIRCULATOR

PUMP

Every forced hot water system requires at least one circulating pump. The circulating pump
imparts the necessary energy to move the water through the closed loop supply and return
piping systems, terminal heating equipment (i.e. finned tube radiators, etc.) and back
through the boiler for reheating. To provide the required hot water flow rates, the circulator
pump must be properly sized to overcome frictional losses (usually measured in feet of
water, also referred to as "pump head loss") of the supply and return piping systems and
boiler. The circulator pump is furnished in a carton within the boiler cabinet for a single zone
or zone valve controlled heating system and should be correctly located on the downstream
(i.e., pumping away) side of the expansion tank. For a pump controlled system (where there
is a circulator for each zone) the circulator provided with the boiler can work for one zone.
For more details on piping and circulators, see Near Boiler Piping section of this manual.
J. DRAIN VALVE
The manual drain valve provides a means of draining the water in the heating system, including
the boiler and hot water supply and return piping systems installed above the drain valve. This
drain valve is installed in the 3/4" tapping at the bottom of the front boiler section. Any piping
installedbelow the elevation of this drain valve will require additional drain valves to be installed
at low points in the piping systems in order to drain the entire system.
33

K. A.S.M.E.

RATED

PRESSURE

RELIEF

VALVE

Each boiler must have a properly sized and installed American Society of Mechanical Engineers rated pressure relief valve. Water expands as it is heated by the burner/boiler sections.
If there is no place for the water to expand its volume, (i.e. a properly sized and properly
functioning expansion tank) pressure on the inside of the boiler and heating system will
increase. The furnished relief valve will automatically open at 30 psig pressure to relieve the
strain on the boiler and heating system from the increasing pressure. The pressure relief
valve discharge must be piped with piping same size as the valve discharge opening to an
open drain, tub or sink, or other suitable drainage point not subject to freezing, in accordance
with A.S.M.E. specifications.
Failure to provide the pressure relief valve with piping as herein
described may cause water damage and/or serious bodily injury. The boiler manufacturer
is
not responsible for any water damage or personal injury.
L. FLAME

ROLLOUT

SAFETY

SHUTOFF

As required, this boiler is equipped with a manual reset flame rollout safety shutoff means,
which shuts off main burner gas in the event that the flow of combustion products through
the flueways is reduced. In the event of blocked flueways, enough air will not be available to
support combustion,
and the $9301 Integrated Boiler Control (IBC) will lockout due to loss of
adequate air flow (after 3 trials for ignition). The "PURGE" diagnostic indicator lamp (lamp "B"
on the IBC, see Fig.16) will blink indicating the failure mode as a lack of adequate air flow.
The IBC is manually reset from lockout by either removing and reestablishing the
thermostat's call for heat, or by turning the service switch off, then back on. If the boiler
cannot be restored to normal operating condition by resetting the control, contact a qualified
service agency to check heat exchanger flueways for blockage.
M. (OPTIONAL)

EXTERNAL

CONDENSATE

PUMP

For installations where there is no floor drain or other appropriate drainage receptacle available to receive condensate from the boiler, an external float activated condensate pump with
integral sump is required. This unit can be installed to pump the condensate to a remote tie
in point to a sanitary sewer system. For this application, the boiler must be installed so that
proper pitch of piping to the external condensate reservoir (sump) can be accomplished.
Use
wood frame or blocks to raise boiler as required for proper installation.

A. WATER
.

TREATMENT

AND FREEZE

PROTECTION

When filling the boiler and heating system, water treatment is generally not required or
desired. For localities where the water is unusually hard (above 7 grains hardness) or for
low pH water conditions (below 7.0), consult a local water treatment specialist.
a. This boiler is designed for use in a closed hydronic heating system ONLY!
b. Excessive feeding of fresh make-up water to the boiler may lead to premature
of the boiler sections.

.

Use clean fresh tap water for initial fill and make-up
a.
b.

failure

of boiler.

A sand filter must be used if fill and make-up water from a well is to be used.
Consideration
should be given to cleaning the heating system, particularly in
retrofit situations, where a new boiler is being installed in an older piping system.
34

c.

In older system, obviously discolored, murky, or dirty water, or a pH reading
indications that the system should be cleaned.
A pH reading between 7 and 8 is preferred.

d.
3.

below 7, are

Antifreeze if needed, must be of a type specifically designed for use in closed hydronic
systems and with aluminum.
a. Choice and use of antifreeze must be in accordance with local plumbing codes.

heating

b

Only INTERCOOL
NFP-50 is approved for use.
• Use of any antifreeze other than INTERCOOL
NFP-50 will void warranty.
• Antifreeze must be maintained per manufacturers
specifications,
failure to do so will
result in the warranty being voided.

c.

Do not use automotive antifreeze as the type of corrosion inhibitors used will coat the boiler's
heat transfer surfaces and greatly reduce capacity and efficiency.
Consult antifreeze manufacturer's
literature for compatibility
of antifreeze with
aluminum
boiler.
For approved manufactured
antifreeze (INTERCOOL
NFP-50 Coolant)
please contact Interstate Chemical Co. New York Customer Service at 1-800-422-2436.

d.

Some brands have corrosion inhibitors that break down more rapidly or become ineffective at
higher operating temperatures
when used with aluminum.
Follow the antifreeze manufacturers
instructions on determining
the proper ratio of antifreeze to water for the expected low
temperature conditions, and for maintaining the quality of the antifreeze solutions from year to
year.
Use of antifreeze in any boiler will reduce capacity by as much as 10 to 20%, due to differing
heat transfer and pumping characteristics.
This must be taken into consideration when sizing
the heating system, pump(s), and expansion tank. Consult antifreeze manufacturer's
literature
for specific information on reduced capacity.
Water content of the boiler is 2.6 gallons. (10 liters)

e.

f.
B.

FILLING
TYPE

BOILER
EXPANSION

WITH

WATER

AND

PURGING

ARE

FOR

Refer to appropriate
"Near Boiler Piping" diagrams.
1. Close all zone service valves on the supply and return piping.

2.

3.
4.
5.
C.

BOILER

Refer to appropriate

Open the feed valve and fill boiler

WITH

WATER

CLOSED

TYPE

AND

PURGING

EXPANSION

AIR

FOR

SYSTEMS

valves

WITH

TANKS

"Near Boiler Piping" diagrams.

Close all zone service valves on the supply and return piping and close the expansion tank service
valve. Drain expansion tank. Open the feed valve and fill boiler with water. Hold relief valve open
until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve
snap shut.
Open the zone service valve on the SUDDIv pipe for the first zone. Open the purge valve on the
first zone. Feed water will fill the zone, pushing air out the purge valve.
when the water runs air free. Close the zone service valve.

3.

DIAPHRAGM

Repeat step 2 for all remaining zones.
Open all service valves. Any air remaining trapped in the return lines between the service
and the boiler will be pushed towards the air vent when the boiler is placed in operation.
Inspect piping system. Repair any leaks immediately.

CONVENTIONAL

2.

WITH

with water. Make sure air vent is open. Hold relief valve open until water runs air free for five
seconds to rapidly bleed air from boiler, then let the relief valve snap shut.
Open the zone service valve on the SUDDIv pipe for the first zone. Open the purge valve on the
first zone. Feed water wilt fill the zone, pushing air out the purge valve. Close the purge valve
when the water runs air free. Close the zone service valve.

FILLING

1.

SYSTEMS

TANKS.

Repeat

step 2 for all remaining

zones.

35

Close the purge valve

4. Open the expansion tank service valve and the tank vent. Fill the tank to the proper level
and close the tank vent. Remove the handle from the expansion tank service valve so
the homeowner doesn't accidentally close it.
5. Open all service valves. Any air remaining trapped in the return lines between the
service valves and the boiler will be pushed towards the expansion tank when the boiler
is placed in operation.
6.

Inspect piping system.

NOTE:

Repair any leaks immediately.

DO NOT use stop leak compounds.
Leaks in threaded
aluminumboiler
sections must be repaired immediately.
seal themselves.

D. PLACING

BOILER

connections in the
Aluminum threads

will not

IN OPERATION

FOR YOUR

SAFETY

READ BEFORE

OPERATING
I

WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life
This appliance

is equipped

automaticaJly

with an ignition device which

lights the pilot

If you cannot reach

Do not try to light the pilot

I

your gas supplier,

call the fire

department

by hand

Use only your hand to move the system control switch

BEFORE

OPERATING

smefl a]l around

the appliance

Never use tools

If the switch wifl not move by hand,

area for gas Be sure to smell next to the floor because

don't try to repair it, call a qualified

some gas is heavier than air and will setfle on the floor

Force

WHAT

explosion

TO DO IF YOU SMELL

GAS

or attempted

repair

Do not try to ]ight any appliance

Do not use this appliance

Do not touch any electrical

water

switch: do not use any phone

in your building
Immediately
phone

call your gas supplier

Follow the gas supplier's

1

STOP!

2

Set thermostat

Read

3

Turn off all electric

the safety information

from a neighbor's

automatically

control

instructions

is equipped

above on this label

and any gas control

5

technician

any part of the
which

has been

Remove the front jacket panel

7 Wait five (5) minutes

DONOT

service

and to replace

6 Turn the gas control knob clockwise

with an ignition

the burner

or

INSTRUCTIONS

power to the appliance

lights

technician
in a fire

if any part has been under

call a qualified

the appliance

system

service

may result

under water

to lowest setting

4 This appliance

Immediately

to inspect

OPERATING

burner

I

device

gas, including

which

try to light the

near the floor

to "OFF"
Then smell for

If you smell

Follow "B" in the safety information

by hand

_

to clear out any gas

gas, STOP!

above on this label

If

you don't smell gas go on to next step
8

Turn the gas control knob

counter

clockwise

_

to

"ON"
9

Replace front jacket panel

10 Turn on all electrical
11 Set the thermostat
12 If the appliance

power to the appliance
to desired

wifl not operate

Turn Off Gas To Appliance"

setting
foNowthe instructions

"To

and call your service t echnician

or gas supplier

TO TURN OFF GAS TO APPLIANCE
1

Set the thermostat

to lowest setting

2

Turn off all electric

power to the appliance

4 Turn gas control knob clockwise
if service

is to

5

Replace

__

to "OFF"

the front jacket panel

be preformed
3

Remove

the front jacket panel

Safe lighting and other performance criteria were met with the gas manifold and control assembly
provided on the boiler when the boiler underwent tests specified in ANSI Z21.13-latest revision.
36

DIAGNOSTIC

®
©
®
®

INDICATOR
VALVE /

LAMPS
FLAME

IGN_ER
PURGE
POWER

CONTROL PANEL
MR PRESSURE

SWITCH

TRANSFORMER

FIGURE
A. VERIFY

PROPER

SEQUENCE

16

INDICATOR

LAMPS

OF OPERATION

The sequence can be followed via the diagnostic indicator lamps on the Honeywell $9301A
integrated boiler control in Fig. 16. This is the normal sequence of operation.
A more detailed
sequence

of operation

containing

potential

SEQUENCE

faults can be found in the service

calls for heat, energizing

Integrated boiler control goes through
and energizes draft inducer

DIAGNOSTIC
INDICATOR
LAMPS

OF OPERATION

Power ON, boiler standing by. Lamp A is illuminated
being supplied to the integrated control.

Thermostat

hints section.

indicating

2 volt power is

system circulator

A. •
B O
C.O
DO
E O

self check of internal circuitry

Draft inducer comes up to speed and establishes

combustion

(1-2 seconds)

airflow, causing the

normally open differential pressure air proving switch contacts to close. Lamp B is
illuminated indicating that combustion airflow is proved and the 15 second pre purge
cycle is under way.
37

A. •
B. O
C.O
DO
E O

A. •
B. O
C.O
DO
E O
A. •
B. •
C. o
DO
E. O

After pre purge, Lamp B goes out and Lamp C illuminates,
igniter is powered

for the 20 second

glow of the hot surface
front boiler section

igniter

igniter warm-up

can be observed

indicating

the hot surface

A.O
B.O
C.O
D.O
E.O

period. The bright yellow orange

through

the observation

port in the

just above the igniter.

After igniter warm-up, the gas valve is energized, and opens on the normal firing rate
regulator (2.5" w.c.) for a 6 second trial for ignition. Lamp D illuminates. The blue orange
glow of the burner can be seen through the observation port.

A.O
B.O
C.O
D.O
E.®

Two seconds later, Lamp C
During the last two seconds
proven by flame rectification
rectification to the integrated
remains energized, and the

goes out as power is turned off to the hot surface igniter.
of the 6 seconds trial for ignition, main burner flames is
through the hot During surface igniter, providing flame
boiler control and fully illuminating Lamp E.. The gas valve
boiler runs.

A.O
B.O
C.O
D.O
E.O

Thermostat ends call for heat, de-energizing gas valve and system circulator. Burner
stops firing, and Lamp D goes out. Draft inducers remains powered. Lamp B illuminates,
indicating draft inducer is running for 30 second postpurge.

A.O
B.O
C.O
D.O
EO

After 30 seconds, draft inducer is de-energized
next call for heat.

A.O
B.O
C.O
D.O
E.O

NOTE:

Lamp B goes out. Boiler stands by for

First couple of cold starts may be rough due to gas line not being completely
of air, causing low firing rate and high excess air levels..

B. INSPECT

VENTING

AND AIR INTAKE

SYSTEM

Operate the boiler and verify that all vent/air
Repair any leaks immediately.
C. INSPECT

CONDENSATE

Verify that all connections
immediately.
D. INSPECT

SYSTEM

intake connections

are gastight

and watertight.

DRAIN
are watertight,

and that condensate

flows freely. Repair any leaks

PIPING

Verify that all connections
E. TEST IGNITION

purged

SYSTEM

are watertight.
SAFETY

Repair any leaks immediately.

SHUTOFF

DEVICE

1.
2.

Turn off manual gas valve
Set thermostat to call for heat

3.
4.

Boiler begins normal sequence of operation
After approximately 40 seconds (pre purge and igniter warm-up period), lamp D illumi
nates, indicating gas valve is powered
After 6 seconds, gas valve closes, lamp D goes out as integrated boiler control senses
that flame is not present
To restart system, follow operating instructions under "START-UP PLACE IN OPERATION"

5.
6.

38

F. TEST HIGH LIMIT CONTROL

AND ADJUST

While burner is operating, move indicator on high limit control below actual boiler water
temperature.
Burner should go off while circulator continues to operate. Raise limit setting
above boiler water temperature and burner should reignite after pre purge and igniter warmup period. Set the high limit control to the design temperature
requirements of the system.
Maximum high limit setting is 200°F. Minimum high limit setting is 100°F.
G. TEST OTHER

SAFETY

CONTROLS

If the boiler is equipped with a low water cut off, a manual reset high limit, or additional safety
controls, test for operation as outlined by the control manufacturer.
Burner should be operating and should go off when controls are tested. When safety controls are restored, burner
should reignite.
H. SET THERMOSTAT HEAT ANTICIPATOR (IF USED) AND VERIFY THERMOSTAT OPERATION
For a single thermostat connected to the yellow thermostat lead wires in the furnished field
wiring junction box, the heat anticipator should be set at 0.7 amps. For other wiring configurations, refer to the instructions provided by the thermostat manufacturer
regarding adjustment
of heat anticipator. Cycle boiler with thermostat. Raise the thermostat to the highest setting
and verify boiler goes through normal start up cycle. Lower thermostat to lowest setting and
verify boiler goes off.
MEASURE

THE NATURAL

GAS INPUT RATE

Correct input rate is essential for proper and efficient
1. Determine elevation at installation site.

operation

of the burner and boiler.

2. See page 4 and 5 of this manual to determine the correct input rate for the local elevation.
3. Obtain the yearly average heating value of the local gas supply from the gas utility. At sea
level elevation, it should be approximately
1000 Btu's per standard cubic foot.
4. Operate boiler for 5 minutes.
5. Turn off all other gas appliances, extinguishing standing pilots where applicable.
6. At gas meter, measure time in seconds required to use one cubic foot of gas.
7. Calculate input rate according to the following formula:
3600xheatinq

B tuh input rate
.

=

value
time

from step 3

from

step

6

Measured input rate should be within +/-2% of the input rating from step 2. If within 2%, go
to step 9. If not, adjustment is required, proceed as follows:
a. Turn boiler off
b. Set up U-tube manometer
sure, see FIG. 17.

or differential

pressure

gauge for measuring

manifold

pres

c. Manometer or gauge must be able to read at least 0.0 to 3.0 inches water column of
pressure, and resolve to at least 0.1 inches water column.
d. Turn boiler on.
e. Manifold pressure has been nominally set at 2.5 inches w.c. Manifold pressure and input
rate must always be measured with pressure regulator cover screw installed..Cover
screw
must be removed for adjustment. Manifold pressure reading will change (increase) when
cover screw is removed.

39

PRESSURE
(UNDER

REGULATOR

ADJUSTMENT_
COVER SCREW)

_--GAS

VALVE

VENT

j/

",

OUTLET PRESSURE TAP
(1/8" PLUG)

_

J

4-WAY CONNECTOR

PRESSURE

WHITE TRANSPARENT
VINYL TUBING

\

/

REFERENCE

PRESSURE

...._DIFFERENTIAL

:

%'

PRESSURE

U-TUBE
MANOMETER

GAUGE

THE FOLLOWING
POINTS

STEPS AND DIAGRAM

REQUIRED

THE MANIFOLD
DIFFERENTILA
MEASURING
PRESSURE•
© REMOVE

TO MEASURE

PRESSURE
PRESSURE

DEVICES

INDICATE

THE MANIFOLD

MAY BE MEASURED

REFER TO "CHECK
MANIFOLD
WHEN

OUT PROCEDURE

SEALANT

TO MEASURE

GAUGE.

BARBED FITTING AND CONECT

OR THE DIFFERENTIAL

AND ADJUSTMENTS"

APPROVED

IS COMPLETE,

DISCONNECT

BE SURE TO REINSTALL
FOR USE WITH

FIGURE

THE PRESSURE

PRESSURE

GAUGE.

IN THIS MANUAL

WHEN

17 MANIFOLD

U-TUBE

MANOMETER

READING

OR DIFFERENTIAL

1/8" PLUG, USING APPROPRIATE

NATURAL

AND LIQUIFIED

PRESSURE

PETROLEUM

MEASUREMENT
Top view

NOTE:

OF BOTH

THE MANIFOLD

PRESSURE.

MEASUREMENT

PRESSURE

OR A

SHOWS THE CONNECTION

IS REQUIRED

THE PLUG• INSTALL APPROPRIATE

SIDE LINE FROM THE U-TUBE MANOMETER

OF THE CONNECTION

USING A U-TUBE MANOMTERE

GAUGE. THE DIAGRAM

BUT ONLY ONE DEVICE

THE LOCATION
PRESSURE•

Regulator cover screw must be installed
at all times unless adjusting manifold
pressure. Firing rate and manifold
pressure must only be measured with
cover screw firmly installed.

PIPE THREAD
GASES.

DETAIL
of gas control
VR8205

PRESSURE

REGUAITOR
WIRING

ADJUSTMENTIUNDER

TERMINALS

CAPSCREW)

PRESSURE

PRESSURETAP
TAP

INLET i_

:

_ OUTLET
?

GAS

FIGURE

18 GAS

40

(2)
OUTLET

INLET

VALVE

CONTROl

KNOB

I.

Remove regulator cover screw on top of gas valve, and insert an appropriate screwdriver into adjustment screw.
II. Turn adjustment screw clockwise to increase input rate, or counter clockwise to decrease input rate.
III. Replace cover screw, or cover hole temporarily with your finger to check new manifold pressure setting. Do not set manifold pressure lower than 2.0 inches w.c. or
higher than 3.0 inches w.c. when adjusting input rate.
IV. Measure new input rate (cover screw must be installed). Repeat steps I.-IV until the
input rate is within +/-2% of the nameplate input rating.
V. If the actual input rate can not be set to within 2% of the correct input rating by adjusting manifold pressure, a change in gas orifice size is required. Consult the boiler
manufacturer
for information on correct orifice sizing. The specific gravity (G) and the
higher heating value (HHV) of the local natural gas must be obtained from the local
gas utility in order to determine the proper orifice size.
f. After adjusting input rate, turn boiler off, remove manometer or pressure gauge, reinstall
1/8" plug on gas valve. Turn boiler on.
9.Restore all gas appliances that may have been shut off (while measuring boiler input
rate) to normal operating conditions.
J. SET THERMOSTAT
Observe

TO DESIRED

several operating

K REVIEW

ROOM TEMPERATURE

cycles to verify proper operation.

ALL INSTRUCTIONS

Review all instructions

shipped with this boiler with owner or maintenance

must be affixed on or adjacent

person.

Instructions

to the boiler.

L. COMPLETE AND SIGN THE INSTALLATION
FOLLOWING
PAGE.

AND CHECK-OUT

41

CERTIFICATE

ON THE

INSTALLATION

Boiler Model

Measured

Serial #

BTU/HR

©

Installation

©

Checkout

©

Maintenance

©

Installation

Installer

AND CHECK-OUT

Date Installed

input

instructions
procedure

and adjustments

and Service
booklet

have been followed
performed

issues reviewed

affixed on or adjacent

(Company)

Address

Phone

Installer's

CERTIFICATE

Name

Signature

42

with owner/maintenance
to boiler

person

Maintenance

as outlined

below can be performed

by the owner unless otherwise

noted.

The acidic nature of flue gasses condensing on the aluminum boiler sections will cause the
formation of aluminum oxide. This oxide formation is normal, is generally uniform throughout the
boiler sections, and represents a negligible mass of aluminum that is consumed by oxidation
during the life of the boiler. If left unchecked, this buildup may eventually cause blockage of the
flue gas passages in the boiler sections, reducing efficiency, and ultimately shutting down the
boiler due to lack of combustion air flow. Regular service and maintenance by a qualified service
agency must be performed to assure safe trouble free operation and maximum efficiency.
A. BEGINNING
,

Annual

OF EACH

HEATING

SEASON

service call by a qualified

service

agency, which includes:

a. Examine flue passages between boiler sections, burner, and condensate lines, and
clean if necessary following the annual examination
and cleaning instructions in para
graph "F" on the next page.
b. Visually inspect venting and air intake system for proper function, deterioration
or
leakage. If the vent or air intake show any signs of deterioration or leakage, repair or
replace them, immediately. Insure proper reassembly and resealing of the vent and air
intake system, c.Check for and remove any obstruction to the flow of combustion air
or venting of flue gases. Check the air baffle located inside 1 1/2"x2" flexible coupling
on the mixer, clean it if necessary and make sure to put it back. Refer to repair parts
diagram of mixer and pressure switch assembly for exact location.
d. Follow instructions
e. Follow instructions
f.

for "PLACING

BOILER

IN OPERATION".

for" CHECK OUT PROCEDURE

AND ADJUSTMENTS".

Visually inspect condensate drain line for proper operation
for plugged condensate drain line.

and deterioration.

Check

g. Check the silicone rubber seals between boiler sections. Insure that there are no
leaks. Use RTV silicone rubber adhesive sealant (available in caulking gun tubes)
rated for at least 400 ° F to replace or repair seals in locations where original seals
have deteriorated.
h. Check all gasketed
i.

joints for leakage, and tighten bolts or replace gaskets if necessary.

Remove jacket front and top panels and check for piping leaks around relief valve and
other fittings. Repair, if found. DO NOT use stop leak compounds.

2. Check that boiler area is free from combustible
vapors and liquids.

materials,

gasoline,

3. Circulator pump and blower motor furnished with boiler are permanently
factory and require no further lubrication. Additional

and other flammable
lubricated from

or non-factory supplied pumps and/or

motors should be lubricated according to the pump and/or motor manufacturer's
B. DAILY DURING

HEATING

instruction.

SEASON

1. Check for and remove any obstruction

to the flow of combustion

2. Check that boiler area is free from combustible
vapors and liquids.
43

materials,

air or venting of flue gases.

gasoline,

and other flammable

C. MONTHLY

DURING

HEATING

SEASON

1. Remove jacket front and top panels and check for piping leaks around relief valve and
other fittings. If found, contact a qualified service agency to repair. DO NOT use stop leak
compounds.
2. Test relief valve. Refer to valve manufacturers

instructions

packaged

with relief valve.

3. Visually inspect venting and air intake system for proper function, deterioration,
or
leakage. If the vent or air intake show any signs of deterioration or leakage, contact a
qualified service agency to repair or replace them immediately and to insure proper
reassembly and resealing of the vent and air intake system.
4. Visually inspect the clear vinyl condensate lines and the PVC condensate drain pipe for
proper operation, leakage, and deterioration.
If the condensate lines or drain pipe show
any signs of blockage, leakage, or deterioration
contact a qualified service agency to
clean, repair, or replace them immediately.
5. Check the air baffle located inside 1 1/2"x 2" flexible coupling, clean it if necessary and
make sure to put it back. Refer to repair parts diagram, mixer and pressure switch
assembly.
D. PERIODICALLY

DURING

HEATING

SEASON

1. Where low water cut offs are used, a periodic inspection of the low water cut off is
necessary, including flushing of float type devices. Refer to low water cut off
manufacturer's
specific instructions.
E. END OF EACH HEATING

SEASON

- ANNUAL

SHUTDOWN

PROCEDUR

1. Follow instructions "TO TURN OFF GAS TO APPLIANCE".
2. If heating system is to remain out of service during freezing weather, and does not contain
antifreeze, drain system completely. If boiler will be exposed to freezing temperatures,
drain condensate lines. Otherwise, do not drain system or boiler.
F. ANNUAL

EXAMINATION

AND CLEANING

OF BOILER

COMPONENTS

The following service procedures must be performed only by a qualified
agency. Boiler owner should not attempt these procedures.

service

1. Before Servicing, turn off electrical power to boiler at service switch. Close manual
valve to turn off gas supply to boiler.
2. Cleaning

Flue passages

between

gas

boiler sections.

&Any buildup of sediment or aluminum oxide (white powdery
flue passages must be cleaned as follows:

or flaky substance)

in the

b.Remove jacket front and top panels. Disconnect condensate drain line from the barbed
fitting on the bottom of the boiler. Keep the open end of the drain line above the water
level in the condensate trap to prevent the trap from draining. Disconnect pressure switch
hose from barbed fitting on gas valve. Disconnect 11/=x 2" flexible coupling from air inlet.
Disconnect air by-pass (½" transparent vinyl tube) from the bottom of the mixer.

44

c,

d,

e,

f.

Remove air baffle from 1%z" x2" flexible coupling and clean air baffle if necessary.
Refer to repair parts diagram, mixer and pressure switch assembly.
Confirm that manual gas valve is closed and disconnect
Disconnect wires to gas valve, and igniter.

gas line to gas valve at union.

Loosen but do not remove five (5) nuts attaching mixer assembly to boiler. Remove
two (2) igniter screws and very carefully remove the igniter. Use care when removing
the igniter, it is very brittle!!
Remove five (5) nuts and remove mixer assembly.

Remove

burner and mixer gasket.

g. Aluminum oxide deposits are water soluble and may be rinsed away with spraying
running water. Before rinsing, connect a '/z" I.D. hose to the barbed fitting on the
bottom of the boiler and run the hose to a bucket or drain.
h. After rinsing, remove any remaining
snorkel attachment.

loosened

sediment

or

using a shop vacuum with a

Inspect burner for any foreign matter in the flame ports or inside the burner. Any foreign matter should be removed by blowing with compressed air or vacuuming.
J,

Inspect interior of mixer for any signs of sediment or aluminum oxide and clean if necessary.

k. Reinstall burner and mixer gasket and position mixer assembly over studs. Install five
(5) nuts but do not tighten. Reinstall igniter and igniter gasket and fasten with two (2)
screws. Use care when installing the igniter. It is very brittle!! Tighten five (5) nuts
holding mixer assembly.
Connect:
•
•

,

gas line to gas valve
condensate drain line to boiler

•

pressure

switch hose to gas valve

•

air by-pass to mixer

•

1 1/2" x2" flexible coupling to air inlet and make sure to put air baffle back to
correct position

•

igniter wires

•

gas valve wires

Visually inspect condensate lines leading from the boiler sections and the vent tee to the
condensate trap. Refer to repair parts diagrams. Any foreign material or debris that is
visible in the condensate lines needs to be cleaned out as follows:.
a.

Raise condensate

trap and drain condensate

lines completely.

b.

Once the condensate trap is emptied of water, disconnect condensate
fittings on the boiler, the vent tee, and the condensate outlet.

c.

Remove the condensate trap and run cold water through
thoroughly flush out any sediment or debris in the lines.

45

the condensate

lines from the

lines to

d. Reinstall and connect the condensate trap, using the hose clamps to secure the various
condensate lines to their fittings.
e. Follow the instructions under "NEAR BOILER PIPING" for"filling condensate trap with
water"
4.

Inspection
a.

requires the following

steps (Refer to the repair parts diagram.)

Loosen the clamp on the draft inducer end of the 2" flexible coupling that connects the
vent tee to the draft inducer. Disconnect (unplug) wiring harness from draft inducer motor
and draft inducer temperature
safety switch. Remove four (4) bolts that attach draft in
ducer to flue connector.

b. Remove
C.

of the flue connector

draft inducer and gasket from top of flue connector.

Inspect interior of flue connector. Any buildup of sediment or aluminum oxide on the
inside surface must be cleaned. Position the draft inducer gasket and the draft inducer
and fasten with four (4) screws. Be sure to connect ground wire from draft inducer motor
to one of the four mounting screws.

d. Connect wiring harness
ture safety switch.
e. Connect

leads to the draft inducer motor and the draft inducer tempera

the 2" flexible coupling

to the draft inducer outlet.

46

P O_ll ER ON
STA ND BY

4,
THERMOSTAT
CALLS
FOR HEAT
IF MAIN

CIRCULATOR
ENERGIEES

BURNER

DOESNOTPROVE

FLAME
IN 3 TRIALS,
LOCKOUT
VALVEIFLAME

CONTROL
LIGHT RLINKS

,

RESET
IS REQUIRED
THIS PROBLEMISA
RESULT
OF NOT ESTABLISHINGFLAME
SIG1"_AL

THRU

2K1 CONTACTS

4,
ISC

SELFCHECK

INTERNAL

OF

CONTROL
A DDITTIONAL

CIRCUITRY'
1-2 SEC

//

CHECKS

E/_

POSITIVE
PROOF

",

SURNER

BED

FLAME

SWITCH
CONTACTS

f

\

DURING
THE LAST
TRIAL MAIN
BURNER
\

RECTIFICATION

WAITS
FOR
UP TO 5 MINUTES

A

REMAINS

2 SEC

INTO

IS-[URNED

"\.

ENERGIZED

THE

IGNITION
BY FLAME

SIGNALTOIBC

5 SEC

BOILER

IGNITION

GASVALVE
RUNS

TRIAL

PC¢_llER

OFF TOTHE
HOT SURFACEIGNITER.
1G;t ITER LIGHT IS OFF.

/
GAS
OPEN

CONTROL
BLI;1KS,

2 BEG OFTHE5SEC
FLAME IS PROVED

FLAME

/
"--..

RESET

LOCKOUT
REQUIRED

_V
PURGE

VALVE

IGNI]ION.
CAN

OPENS

FOR

5SEGTR_LFOR

BLUE
ORANGE
GLOW C_]HE
BE SEEN THRU OBSERVATION

BURNER
PORT

LIGHT

CIRCULATOR

GAS

VALVE

ENERGEED

CONTADTS,

REMAINS
ENERGEED
AS LONG AS
TH ER M OSTAT C ONTIN URES TO CA LL FOR
HEAT

PURGE

LIGHT

GOES

VALVE

OUT

1NR

U 3}<,1 AN D 4K 1.

LIGHTtS

ON.

HQTSURFACEIG_ITER

POWERED
THRU 5KI 5K2CONTACTSFOR2O
SEC IGNITER
WARMUP
BRIGHTYELLOW
PURGE
LIGHT
ISO;1, AIRFLOW
PROVED.
DRAFT
INDUCER
RUNS FOR I5 SEC PREPURGE

\\YEB_

/

DRAFTINDUBER
ENERGEES
THRU
IKI CONTACTS

IBC

PROVE

WITHIN
INITIAL /,,;_
TRIAL
FOR
/
IGNITION
/

PEN

//

\

",,

PRESSURE
'_

PREPURGE

MAIN

OF

N O. AIR

",,

WITH

!F2""-,

\
J

WILL A F]'EMPT 2
IGNITION
SEQUENSES

STA RTING

ORANGE
GLOW OF THE
HOT SURFACEIGNITER
CAN BE OBSERVED
THRU THE OBSERVATION
PORT

IN FRONT

ABOVE

47

IGNITER,

OF BOILER
IG;11TOR

SECTION

JUST

LIG;1TIS

O;1

[

NORMAL
OPERATION

DRAFT INDUCER TEMPERATURE

CASTING

SAFETY SWITCH

TEMPERATURE

IF BURN ER OPERATES
IF DRAFTINDUCER

TEMPERATURE

REACHES

WATER=

TE_,'IPERATURE
SAFETY" SWITCH SETPOINT,
SAFETY SWITCH CONTACTS
OPEN IMMEDIATELY
CLOSING

GAS VALVE (LIGHT

CASTING TEMPERATURE
SAFETY SWITCH
CONTACTS
WILL OPEN BR EAKING 24 VOLT POWER TO IBC
POWER INDICATOR
REQUIRES
MANUAL

INDUCER RUNS THRU 30 SECOND POST
PURGE AN])
S_,JZTCHES
OFF.

CONTAC]S_

4,
CIRCULATOR

WHEN BOILER HAS NO

ALUMINUM
BOILER SEC]IONS
HEAT UP RAPIDLY

GOES OUT)

4,
DRAFT

SAFETY SWITCH

CALLR
UN SONFoR
W ITH
HEAT
]HER k'IOSTAT

LIGHT GOES OUT
RESEI'TO RE+CLOSE

POWER

LIGHTGOES

OUT_

]

WHEN TEMPERATURE
SAFETY SWITqH
CONTACTS
REMAKE BEFORE END OF CALL

HI LIMIT CONTROL

FOR HEAT= CONTROL GOES INTO NORMAL
LIGHT+OFF SEQUENCE
IF BOILER

WATER TEMPERA]URE

REACHES

HI Ltk'11T (AQUASTAT)
SETPOINT HI LIke]IT
NC CONTACTS
OPEN tMMEDLATELY,
CLOSING GASVALVE
VALVE LIGHTGOESOUT.

LOSS OF FLAME SIGNAL

DRAFT

INDUCER

SECOND
tF AN ESTABLISHED

CONTINUES

WHILE CONTROL
EXPECTS]HATTHEBURNER
IS OPERATING
CONTROLWILLIMMEDIA]tELY
DE=ENERGIZE
GAS_'ZALVE VALVE LIGHTGOESOUT

CIRCULATOR

RUNS
CALLS

4,
DRAFT

INDUCER

RUNS THRU 3C_SECOND POST
PURGE

4,
CONTROL

WILL ,ATTEMPT

TO RE-UGHT BOILER

3 TIMES IF FLAME IS NOTPROVEN, CONTROL
LOCKOUT - PROBLEM ES]:ABL]SHING A
FLAME

SIGNAL,

TO RUN FOR 30

POST PUR GE ,AND SWI]_2-H OFF

FLAME SIGNAL IS LOST

VALVE

LIGHT

ISBIJI_IqNG,

1

l

,AS LONG
FOR

ASTHERMOS]AT

HEAT

WHEN HI LIMIT CONTACTS
REM,AKEBEFORE END
OF GALL FOR HEAT- CONTROL GOES INTO
A NORMAL LIGHT OFFSEQUENCE

CIRCULATOR

PUMP

CIRCULATOR WILL BE ENERGIZED .AS LONG ,AS
TH ER MOST,AT CALLS FOR HEAT DURING LOCKOUT

LOSS OF COMBUSTION

AIRFLOW
RECOVERY

IF COMBUSTtON
IS FtRING

,AIRFLOW

_SLOSTWHILE

(DIFFERENTIALAIR

PRESSURE

SWITCH CONTACTS
OPEN) GASVALVEWILL
BE DE-ENERGIZED
VALVE LIGHTGOESDUT.

4,
DRAFT

INDUCER

RUNS THRU 30 SECOND POST
PURGE

IF CALL FOR HEAT REMAINS IBC ,5/AITS
5 MINUTES
FOR AIRFLOW TO BE RE-ESTABLISHED

4,
IF ,AIR FLOW DOES NOTRE+ES]:ABL]SH
CONTROL LOCKOUT - PROBLEM WITH
COMBUSTION

AIRFLOW

PURGE

LIGHTBU_KS

FR O_,_1
ANY LOCKOUTREQUIRES

RESET

WHICH I S ACCOMPL] SH ED BY REMOVING AND
R EA P PYI NG TH E TH ER M O STAT CALL FOR HEAT
OR POWER TO CONTROL

BURNER

1
48

END OF NORMAL SEQUENCE

THERMOSTAT

GAS VALVE

BLOWER

ENDS CALL FOR HEAT.

AND CIRCULATOR

RUNS FOR 30 SECOND

PURGE,

OF OPERATION

PURGE

PUMP

POST

LIGHT IS ON.

4,
AFTER

BOILER

BLOWER IS DE-ENERGIZED
30 SECONDS,
PURGE LIGHT SHUTS OFF.

STANDS

BY FOR NEXT CALL FOR HEAT.

49

!!WARNING!!
FIRE, EXPLOSION
OR SHOCK HAZARD MAY CAUSE
PROPERTY DAMAGE, SEVERE INJURY OR DEATH.
DO NOT ATTEMPT TO MODIFY THE PHYSICAL OR ELECTRICAL
CHARACTERISTICS
OF THIS BOILER IN ANY WAY.

IMPORTANT
.

IN A RESET FROM LOCKOUT CONDITION, ALL ELECTRICAL METER READINGS AT THE GAS
CONTROL VALVE (24 VAC) MUST BE TAKEN WITHIN THE TRIAL FOR IGNITION PERIOD.

2.

IFANY COMPONENT DOES NOT FUNCTION PROPERLY, MAKE SURE IT IS CORRECTLY INSTALLED
AND WIRED BEFORE REPLACING IT.

3.

STATIC ELECTRICITY DISCHARGE CAN DAMAGE THE INTEGRATED BOILER CONTROL (IBC).
TOUCH METAL SURFACE TO DISCHARGE STATIC ELECTRICITY BEFORE TOUCHING IBC.

4.

THE IBC CANNOT BE REPAIRED.

5.

ONLY TRAINED, EXPERIENCED SERVICE TECHNICIANS SHOULD SERVICE THE IBC SYSTEMS.
FOLLOWING TROUBLESHOOTING,
CHECK OUT THE SYSTEM FOLLOWING THE SEQUENCE OF
OPERATION SECTION OF THIS CHAPTER FOR A NORMAL LIGHT OFF SEQUENCE.

IF IT MALFUNCTIONS

IT MUST BE REPLACED.

ALL CONTROLS ARE FACTORY TESTED IN THE ASSEMBLY PROCESS AND A DEFECTIVE
CONTROL IS GENERALLY THE LEAST LIKELY CAUSE. IF YOU SUSPECT YOU HAVE A DEFECTIVE
CONTROL, READ THROUGH THE TROUBLESHOOTING CHART BEFORE YOU REPLACE IT.
IT IS EXTREMELY UNLIKELY THAT THE TWO CONSECUTIVE CONTROLS ARE DEFECTIVE. IF IT
SEEMS TO BE HAPPENING, CHANCES ARE THAT EITHER THERE IS NOTHING WRONG WITH THE
CONTORL OR IT IS BEING DAMAGED BY SOME OTHER PROBLEM (AN ELECTRICAL SHORT
BURNING OUT A TRANSFORMER, FOR EXAMPLE).

INITIAL

SERVICE

CHECKS

BEFORE TROUBLESHOOTING:
A. MAKE SURE THAT CIRCUIT BREAKER IS ON OR FUSE IS OKAT ELECTRICAL PANEL.
B. MAKE SURE THAT SERVICE SWITCH IS ON.
C. MAKE SURE THAT GAS IS ON AT THE GAS METER, AT ALL APPROPRIATE MANUAL
SHUTOFF VALVES AND AT THE GAS CONTROL VALVE.
D. MAKE SURE THAT THE THERMOSTAT IS CALLING FOR HEAT.
E. CHECK THAT WIRE CONNECTORS AT THE INTEGRATED BOILER CONTROL AND AT THE
ORIGINATING CONTROL ARE SECURELY PLUGGED IN OR CONNECTED.
F. CHECK THAT HOSES ARE SECURELY CONNECTED AND ARE NOT PLUGGED IN OR
DAMAGED.
2. TROUBLESHOOTING TOOLS:
A. VOLTMETER TO CHECK 120 VAC AND 24 VAC
B. CONTINUITY TESTER.
C. INCLINED MANOMETER OR PRESSURE GAUGE WITH 0-2.0" RANGE (0.01" SCALE) FOR
MEASURING SUCTION PRESSURES AT PRESSURE SWITCH.
D. U-TUBE MANOMETER OR DIFFERENTIAL PRESSURE GAUGE WITH 0-14" RANGE (0.1"
SCALE) FOR MEASURING INLET AND MANIFOLD GAS PRESSURES.
3. WHAT IS SYSTEM STATUS?
A. CONSULT THE CHART ON THE FOLLOWING PAGE.
B. FIGURE 15 ON PAGE 29 SHOWS THE LOCATION ON THE BOILER OF THE DIAGNOSTIC
INDICATOR LAMPS.

5O

SYSTEM STATUS
THE INDICATOR LIGHTS TRACK THE OPERATING

SEQUENCE.

IF THE SYSTEM LOCKS

OUT, THE LIGHTS INDICATE THE POINT IN THE SEQUENCE OF OPERATION
LOCKOUT OCCURS.
BOILER MALFUNCTION

IF THIS TABLE DOES NOT READILY PROVIDE THE REASON FOR
OR NON-OPERATION,

REFER TO THE FOLLOWING

MORE DETAILED TROUBLESHOOTING

LIGHT

STATUS
ON

POWER

OFF
BLINKING
ON

WHERE

PAGES FOR

PROCEDURES.

INDICATES
IBC IS ENERGIZED THROUGH 24 VOLT TRANSFORMER.
IBC IS NOT ENERGIZED.
IBC RECEIVES MORE THAN 40 VAC
IBC IS ENERGIZING THE DRAFT INDUCER AND AIR FLOW IS PROVEN.
OFF DURING PURGE CYCLE-DRAFT INDUCER IS NOT POWERED OR AIR FLOW
IS NOT PROVEN.

PURGE

OFF
OFF DURING IGNITER AND RUN CYCLE-NORMAL OPERATION, PURGE
CYCLE COMPLETE.
BLINKING

IGNITER

OF AIR FLOW. BLOCKED VENT OR INTAKE AIR PIPE OR FLUE WAY.

ON

IBC IS ENERGIZING IGNITER

OFF

IGNITER IS NOT ENERGIZED

ON

IBC IS ENERGIZING GAS CONTROL VALVE TO OPEN.

OFF

GAS CONTROL VALVE IS CLOSED.

VALVE

IBC IS LOCKED OUT. PROBLEM IS FLAME HAS NOT BEEN PROVEN IN
BLINKING

FLAME

IBC IS LOCKED OUT. PROBLEM COULD INDICATE FALSE POSITIVE PROOF

THREE (3) IGNITION A-I-TEMPTS. MAY BE DUE TO BROKEN IGNITER OR
LACK OF OR LOW FLAME SIGNAL, OR NO GAS.

ON

FLAME PROVEN

OFF

FLAME UNPROVEN

51

TROUBLESHOOTING

!!WARNING!!

CHART 1

GREEN

POWER

INDICATOR

ILLUMINATED

LIGHT IS

NO

ON THE IBC,

ELECTRICAL SHOCK HAZARD MAY CAUSE
SERIOUS INJURY OR DEATH.
YES

THE FOLLOWING PROCEDURES MAY EXPOSE YOU TO
DANGEROUS LINE VOLTAGE. USE CAUTION TO AVOID
TOUCHING LIVE ELECTRICAL CONTACTS. SERVICE
MUST BE PERFORMED BY A TRAINED, EXPERIENCED
SERVICE TECHNICIAN.

CHECK SYSTEM STATUS.
IF LOCKED
OUT NOTE FAILURE
MODE. WHICH
INDICATOR

LIGHT

IS BLINKING?

RESET SYSTEM BY TURNING SERVICE
SWITCH OFF THEN ON, IF NOT
LOCKED

WHAT TO DO IF YOU SMELL GAS:
•
DO NOT TRY TO LIGHT ANY APPLIANCE
•
DO NOT TOUCH ANY ELECTRICAL SWITCH; DO
NOT USE ANY PHONE IN YOUR BUILIDNG.
•
IMMEDIATLEY
CALL YOUR GAS SUPPLIER
FROM A NEIGHBOR'S PHONE. FOLLOW THE GAS
SUPPLIER'S INSTRUCTION.
"
IF YOU CAN NOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.

OUT, SET THERMOSTAT
CALL FOR HEAT.

TO

NO
CIRCULATOR

STARTS?
YES

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY
FAIL TO SHUT OFF, DO NOT TURN OFF OR DISCONNECT
THE ELECTRICAL
SUPPLY TO THE PUMP. INSTEAD,
SHUT OFF THE GAS AT A LOCATION EXTERNAL TO THE
APPLIANCE.
DO NOT USE THE BOILER IF ANY PART OF THE GAS
CONTROL
SYSTEM
HAS BEEN UNDER WATER A
QUALIFIED SERVICE TECHNICIAN SHOULD INSPECT THE
BOILER AND REPLACE ANY PART OF THE CONTROL
SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN
UNDER WATER.
USE ONLY YOUR HAND TO TURN THE
KNOB. NEVER USE TOOLS. IF THE KNOB
BY HAND. DON'T TRY TO REPAIR
ATTEMPTED
REPAIR MAY RESULT
EXPLOSION.

GAS CONTROL
WILL NOT TURN
IT. FORCE OR
IN A FIRE OR

CHART2
v

FALSE

POSITIVE

PROOF

OFAIRFLOW.

CHECK
IBC CHECKS

AIR PRESSURE
SWITCH CONTACTS,
IF CONTACTS
ARE CLOSED WITH NO
AIRFLOW,

REPLACE

PRESSURE

SWITCH,

PRESSURE
t

NORMALLY
SWITCH

OPEN AIR

CONTACTS

CLOSED

OPER
CHART3

52

TROUBLESHOOTING

cHA

CHART 2

CHECK THAT CIRCUIT BREAKER IS ON OR
FUSES ARE OK ATTHE ELECTRICAL PANEL
OK

CHECK THAT SERVICE

SWITCH IS ON

OK

CHECK CASTING TEMPERATURE

SAFETY

SWITCH. PUSH RESET BUTTON ON SWITCH.
CONTACTS OPEN (BUTTON UP) OR CLOSED
(BUTTON

CHECK WATER LEVEL IN BOILER. CHECK
FOR AIR TRAPPED IN TOP OF BOILER
CONTACTS WILL NOT STAY CLOSED UNTIL
BOILER COOLS OFF.

OPEN

DOWN)?
CLOSED

CHECK WIRING TO IBC 120 VAC BE'C_NEEN
TERMINAL
1 AND 3ATWIRINGRARNESS
PLUG CN7?

NO

REPLACE/RE

PAl R W IRI NG FROM S ERV ICE
SWITCH TO IBC

YES

120VAC

BETWEENTERMINALS
1 AND 3 AT
CONNECTOR
CN3 ON tBC?

NO
REELACEIBC

YES

120 VAC AT TRANSFORMER
TERMINALS?

PRIMARY

NO
REPAIR WIRING TO TRANSFORMER

YES

24 VAC AT TRANSFORMER
TERMIRALS?

SECONDARY

NO
REPLACE

TRANSFORMER

YES
NO
24 VAC AT WIRING

HARNESS PLUG CN2?

PUSH RESET BUTTON ON CASTING TEMP,
SAFETY SWITCH.

YES

REPLACE

CHECK CONTINUITY OF CASTINGTEMP.
SAFETY SWITCH COBITACTS, COi'_ITACTS
OPEN OR CLOSED?

IBC

V

REPLACE CAST, TEMF,
SAFETY SWITCH,
'4F OEEN

CLOSED

REPLACE/REPAIR
"_ IRING FROM
TRANSFORMER TO IBC

CHECK FOR 120 VAC B E"PA EEN TERMIRALS
1 AND 3 AT CONNECTOR CN5 ON IBC?

REPLACE

NO

IBC

CHART 1
YES
NO
CHECK FOR 120 VAC AT CIRCULATOR
YES

REFAtPJ REPLACE CIRCULATOR

53

,I

REPLACE/REPAIR
WIRING FROM
IBC TO CIRCULATOR

TROUBLESHOOTING

CHART 3

CHART I
OPEN

,l
REPLACE

BLOWER STARTS
YES

tBC

YES

CHECK FOR 120VACAT
BLOWER LEA D S ON I/IIIRING
HARNESS

NO

I

REPAIR/REPLCE
WIRING
TO

FR OMIIBC
BLOWER

YES
R EPAIR/REPLACE
SLOWER

CONTACTS

IBC WAITS

UPTO5

NO

FOR NOR_,'IALL"t
OPEN AIR
PRESSURE SWITCH
CON TA CTS TO CLOSE,
INDICATING BLOW ER
SUCTION IS
PRESENT

CLEAN OUT VENT PIPE
AND/OR AIR INTAKE PIPE
CHECK FOR SAGS OR
LOW SPOTSWHERE
CONDENSATE _'IAY
PUDDLEAND
BLOCK
THEVENT

MINUTES

ARE VENT PIPE AND AIR
OPENINTAKE PIPE CLEAR
(NO BLOCKAGE)

1

4,
CHECK AIR
PRESSURE SWITCH PER
INSTRUCTIONS ON
FOLLOWING PA GES.ARE
SA _'IPLtN G LINES CL_f_R
AND CONNECTED
PROPERLY'?

CLEAN OUT SAMPLING
LINES OR REPLACE
DEFECTIVE SWITCH

YES

CHECK FLUE PASSAGES
IN BOILER PER

CLEAN BOILER FLUE
PASSAGES PER
MAINTENANCE AND
CLEANING INSTRUCTIONS

"k_INTENA CE AND
CLEANING"
ARE FLUE
PASSAGES IN BOILER CLSAN?

YES

MOTOR RPM. BIT
CHECK 3400-3600?
DRAFTINDUCER
YES

CHECK FOR BROKEN OR
LOOSE IMPELLER ON DRAFT
INDUCER AND REPLACE
BLOWER IF FOUND TO
BE BROKEN OR LOOSE

15 SECOND PRE PURGE COMPLETE
PURGE
IGNITOR

LIGHT IS OFF SIk4ULTANEOUSL"t
LIGHT tS ON AS IGNITOR CIRCUIT
tS ENERGIZED.

REPLACE IBC

54

t_

REPLACE
BLOWER

TROUBLESHOOTING
CI_RT
"_"

CHART 4

3

YES
CHECK FOR 120VAC

UP AND GLOWS
Y ELLOW/ORA HGE

B E_A_E EN T E RMli',IALS 1
AND 2 AT CONNECTOR

DURING 20 SECOND
IGNITER/SENSOR
WARMS
WARM UP

CN1 ON tBC (DURING
IGNITER WARM UP)

REPLACE

IBC

]

YES
I_YES
CHECK

FOR 12C*VAC AT

IGNITER/SENSOR
ON WIRING

LEADS

REPAIPJ REP LACE WIRING
FROM IBC

HARNESS

(DURING

IGNITER

WARM

TO IGNITE _ SENSOR

UP)

YESI

REPLACE

IGNITEPJ SENSOR

AFTER 20 SECOND
IGNITER WARM UP, GAS
VALVE IS ENERGIZED
VALVE

LIGHT

1 SECOND

LATER POWER

IS REMOVED
IGNITERtS

IS ON

FROM

ENSOR

CHE CK FOR 24 VAC
ACROSS TERMINALS
MV

CHECK FOR 24VAC
ACROSS TERMINALS

OH THE GAS CONTROL.
WHILE VALVE/FLAME
INDICATOR

POWER LIGHT IS OFF
DOES MAIN BURNER

CN8-2

AND CN6-5 ON

REPLACE

IBC

IBC, WHILE THE VALVE/
FLAME LED IS LIT

LIGHT IS ON

YES
yYES

LIGHT?

REPAIR/REPLACE

WIRING

BETWEEN IBC AND
GAS CONTROL

YES

CHECK IF IGNITER/
SENSOR POSITION IS OK?
TIP SHOULD
TOWARDS

BE SLANTED

TO CORRECT POSITION.
RESTORE
IGNITER/SENSOR
DO NOT
RELOCATE

BURNER
YES

CHECK GAS SUPPLY
PRESSURE AT INLET

SHUT-OFFS

PRESSURE TAPPING ON
GAS CONTROL IS GAS
PRESSURE

GREATER

IN THE GAS

SUPPLY LINE AND ON
THE GAS CONTROL IN
N_

THAN 4,0" W,C.?

THE
OR ON
ARE OPEN
ALL MANUAL
POSITION?

YES
YES
CONTACT

THE GAS UTILITY

TO TURN THE GAS ON

CH& RT 5

CHART

5

55

OPEN OR TURN ON ALL
MANUAL SHUTOFFS

TROUBLESHOOTING

CHART 5

CHART4
YES

CHART4
YES

POSSIBLY
CHECK

GAS

MIXTURE

LINES

VALVE
ARE

FOR

GAS

LEAN!
CLEAN/REPLACE

CLEAR?

VALVE

REPAIR

OF GAS

BLOCKAGE.

LINES

IS GAS/VENTURI
SEE

TOO

DOWNSTREAM

BE SURE

CORRECT

PARTS

TO

USE

GAS

CORRECT

LINES.

GAS/VENTURI

VALVE

SIZE.

SIZE?

DIAGRAM,

_r YES

POSSIBLY
CHECK

MITURE

FLUE

"MA INTENANCE
FLUE

TOO

PASSAGES
AND

PASSAGES

RICH!

IN BOILER
CLEANING",

iN BOILER

PER

CLEAN

BOILER

ARE

FLUE

AND

PASSAGES

CLEANING

PER

MAINTENANCE

INSTRUCTIONS

CLEAN?

_IF YES
CHECK

MIXER

BLOCKAGE

AND

PER

CLEANING

BURNER

INSTRUCTIONS

PASSAGES

FOR

MAINTENANCE

IN MIXER

AND

CLEAN

AREAIR

AND

MIXER

AND

BURNER

CLEANING

PER

iVIAINTENANCE

AND

INSTRUCTIONS

BURNER

CLEAN?

CHECK
FOR

AIR

ORIFICE

CORRECT

DIAGRAM

SIZE,

AT BURNER

INLET

SEE

PARTS

IS ORIFICE

REPAIR

CORRECT

REPLACE

BURNER

SIZE?

NO#1
RUNS
DOES
RUN

MAiN
UNTIL

HEAT

CALL

ENDS

NO #2

OR HI

POOR

CHECK

ABOUT

SHUTS

5

OFF,

FLAME

RESTORE

SIGNAL,

IGNITER/SENSOR

IGN JTER/SENSOR

POSITION.
SLANTED

OPEN?

FOR

THEN

INDICATES

FOR

LIM IT AQUASTAT
CONTACTS

SMOOTHLY

SECONDS

BURNER

TIP SHOULD
TOWARDS

TO
BE

CORRECT
POSITION,
DO NOT RELOCATE

BURNER

NO ,#,3

q

IF YES

* IF THE ANSWER
CHOOSE

THE

CHECK

IS NO,

APPROPRIATE

PATH
(#1, #2, OR #3) BASED
SYMPTOMS
SHOWN,

FLAME

CONSULT
ON

SIGNAL

BOILER

SPECIFIC
REQUIRES

OXIDE

>O,6uA?

MFGR.

FLAME

INSTRUCTIONS.
SPECIAL

TOOLS.

CHART6

CHART

6

CHART

6

56

IBC

J

ON

PREVENTING
SIGNAL

REPLACE
IGNITER/SENOR

YES
REPLACE

COATING

IGNITER

FOR

TROUBLESHOOTING

CHART5
YES

CHART 6

CHART

CHART
NO#3

5
CLEAN

_
RUNS

FOR
THEN

MANIFOLD
PER FIGURE

+

]

CHECK
REPAIR
PARTSLISTFOR
CORRECT
ShEE IS GAS ORIFICE
CLEAN OF BLOCK_,GE?

17

PRESSURE
TO OBE_IN NOR_,_t_L
FIRING
RATE¸
CAN GASVALVE
BE
A OJ USTE D TO N OR _IAL INPUT RAIE?

L

GASORIFICE

_¢_JRE
TOO LE_N NOT ENOUGH
GAS CHECK
GAS ORIFICESIZE
IS GAS ORIFICE
SIZE CORRECT?

_

AND "CHECK
OUT PROCEDURES
AN [3 ADJ U STME N TS" PARAGRAPH
1 B ADJUST_,_NIFOLO

[

REPLACE
rYES

25 50 SECONDS
TURNS OFF

CHECK
PRESSURE

OR

NO#2

REPLACE

GAS CONTROL

J

YES

SIZE¸ SEE REPAIR
PARIS
DIAGRAk_I
CHISECK
AIR A_R
BAFFLE
BAFFLE
CORRECTSI_?
FOR CORRECT

CHECK
AIR ORIFICEATSURNER
INLET
FOR CORRECTSI,_
SEE REPAIRS
IS AIR ORIFICE

REPLACE_IR WITH
CORRECT
S_FFLE_

_

]

_

DIAGRAk&
CORRECT_

REPLACE

BURNER

1

REPLACE

BURNER

1

IG RITER/SENSOR

1

/
CHECN
BURNER
FOR ANYO_R_OR_A_ON
IN THE FLA_E
PORTB_ _ARE SURNER
PORTS
IN GOOO CONDI1]OR?

_

CHECK FLAME SIGNAL
> _ 6uA?
CON SU LT BOI LER MFGR
FO R
SPECIFIC
INSTRUCTIONS¸
REQUIRES
SPECIFIC
I'OOLS

N_2_

REPLACE

R EPLZ_CE

IBO

]

'F
BOILER
SHUTS
OFF
CALL
FOR HEAT
AQ UAETAT

BEFOREENDOF
.ARE HI LIMIT

CONTACTS

BO_LER

I NO

OFF

ON

HIGH

LIkSIT _S

ACTU'_L
BOILER
WATER TEk_P
GREATER
THAN
HI LIMITSETPOINT
k,ll N U S 30 _F CON TR OL DIFFER EN_AL?

CLOSED?

N_

A_ U_S_T

1

REPLACE

]

oK

YES
INDUCER
ARE
INDUCER
TEMP
_FE3-_ r
SWITCH
CONTACTS
CLOSED?

I I_u

SAFEIS"SWITCH

TR I PP ED CH ECK FLU E GAS (VENT)
TEMP
IS IT > 1B0_F LE_.VING FAN?

_

_,¥ES

__)'ES
SEE

TEMP

ii_

TROUBLESHOO]]NG
#2 '_B OVE

P_TH

L

CHECK
SURFACES

J

ALL HEATTRANEFER
PER "_,_AIN_I_NANCE £_

CLEANER G" INSTR U CTIONS ARE HE_,T
TRANSFER
S U R FACES FOULED','

SETTHERMOSTATBELOWROOM
TEMPERATURE
TO END
HEAT

4,"EB
_ALL

FOR

CLEAN

ALL

BOILER

INDUCER
TR_P
REPLACE
S_ETY
SWITCH

CHECK
BOILER
INPUT
RATE PER
"CHECKOUT
PROCEDURE
AND
ADJ U STM EATS"
PARAGRARH
1

HEATTRANSFER

SURFACES
PER "MAINTLNANCE
CLEANING"
INSTR UC_ ORS

@,

YES

ODE S CIR CU L _TOR

PUMP S]I%}P?

_

ES

[

VALE

LIGHT I_ OFF
_
"€'ES

ARE

TH ER _,,_OS_'_,T CONT_',CTS

OPEN?

4 ES

R EPL'_.CE IBC

_

CONWECTION
ON9 FR O_._ GAS
CON1N OL DOES GAS CON/NOL
REMOVE
WIRING
HARNESS
CLOSE?

_

REPL_.CE

R EPLa, CE GAS CONTROL
_

IBC

_

7

YES
S'f STE_°I OK

57

]

1

__YES
STOP
AFTER 30
DOES
DRAFT
SECOND
POST BLOWER
PURGE?

R EP L,'_.CE TH ER _._OSEAT

]

1

\
\

The following
indicate
the

steps and diagram
locations
of the

\
\
\
\

connection points required to check
the differential air pressure.

VINYL TUBING
WHITE TRANSPARENT_
\\

TO SIGHT GLASS
SUCTION PORT

The differential air pressure switch is
a safety device which will prevent the
boiler from firing if there is an air
intake, boiler heat exchanger or vent
blockage.

DIFFERENTIALAIR
PRESSURE SWITCH

SILICONE TUBING

/

/

WRITE TRANSPANZNT
VINYL TUBING
_

f
TO GAS
.....
VALVE VSRT

.........

--

_

TRANSPARENT VINYL TUBN6
4-WAY CONNER[ON
/
/

TO AIR INLET
SUCTION PORT

WHITE TRANSPARENT
VHYZ TUBING

Turn

off service

thermostat

switch,

or lower
_ VINYL CAP
(EYP. 2)

setting.
i_

Remove

_

TESTING

LINES

vinyl caps from Tee and 4-

way connector.
J

INCLINED _AROMETER
(OR DIFFERENTIALPRESSURE GAUGE)

Install testing
lines as shown to
inclined manometer
or differential
pressure gauge with the ability
read 0.01" to 2.0" w.c.
Turn

on service

thermostat

switch

and

to

/

set
/

to call for heat.

Boiler Status

Differential

Not Running

0 _

Setpoint

1.00" for Model-100
1.35" for Model-75
1.55" for Model-50

Running Without
Blockage

Greater

Running With
Blockage

Less Than or Equal to
Setpoints

If manometer
-

/

readings

Pressure

(w.c.)

Than Setpoints

do not correspond

Pressure

Switch Connects

Normally

Open

Closed

Open

to the chart above, check for possible causes:

Blockage or moisture in suction lines
Blockage in air intake or vent pipes
Undersized air intake or vent pipes
Loose blower wheel or motor shaft

- Inncorect

pressure

switch or pressure

switch setpoint

When pressure reading is proper and the pressure switch is operating
lines and reinstall vinyl caps to Tee and 4-way connector.
C,

58

properly,

remove testing

0
TYP

OF

4 _>/

//

.......................................

A.

JACKET

> ......

__J

AND BASE ASSEMBLY

59

J

//

JACKET

AND

BASE ASSEMBLY

QUANTITY

KEY #

ITEM NUMBER

DESCRIPTION

1

750001020

FRONT

2

750001021

RIGHT PANEL

3

750001022

LEFT PANEL

4

750001023

BACK

5

750001024

TOP PANEL

6

750001025

BASE

7

750001026

CONTROL

8

14662801

AT140B1016

9A

14631312

PPS10111-2680

AIR PRESSURE

SWITCH

(100)

AIR PRESSURE

SWITCH

(75)

1

PANEL

1
1
1
1

PANEL

1
1

PANEL
TRANSFORMER

24 VAC

1
1
1
1

9B

14631010

PPS10111-2681

9C

14631044

10

14662803

PPS10111-2682
AIR PRESSURE SWITCH (50)
UT 1013-10 INTEGRATED
BOILER CONTROL

11

14631091

C0_2366

12

14631120

HEYCO OCB-1500

13

14631316

RACO 232 4"4"2 BOX

1

15

14631319

P&S SWITCH

1

16

14631318

COVER

17

14631174

419-1AA1

2½" PLUG

2

18

14631171

415-1AA1

1½" PLUG

3

19

14631176

BPF 3 ½" PLUG

1

20

14631175

421-1AA1

2

21

750001027

LOWER

22

CI-001.03

TACO CIRCULATING

14626043

TACO ISOLATION

CI-006.01

GRUNDFOS

CIRCULATING

14626043

GRUNDFOS

ISOLATION

43300826

CIRCULATING

14631315

WIRING

HARNESS

750001002

JACKET

COMPLETE

GLIDE

1
4
1

BUSHING

14
691-1

PLATE

RACO 902-802

1

3" PLUG
FRONT PANEL

- BLUE

1

PUMP

VALVE

1

SET

1

PUMP

VALVE

PUMP HARNESS

SET

1
1
1
1

6O

TO THE DRAIN PORT AT
THE BOTTOM OF BOILER

CONNECT
TO THE DRAIN
AT THE EXHAUSTER

PORT

O

CONDENSATE

B=

DRAIN TRAP ASSEMBLY

CONDENSATE

DRAIN TRAP ASSEMBLY

KEY #

ITEM NUMBER

DESCRIPTION

1

14631035

59019

½"lDxl/8"

2

14631141

57134

¾" SNAP GRIP CLAMP

6

3

14631320

62067

½"ID HOSE TEE

1

4
5

14631101
14631321

62017

½"NPTx ½"ID TUBE STRAIGHT

1
1

6

14631306

7

14631020

½"'4" PVC NIPPLE, SCH 80
½"ID" ½"ID" ½"NPTTUBE TEE

8

14631323

S. S. CLAMP, SIZE 16 (13/16"~1

QUANTITY

THK VINYL TUBING

½" PVC COUPLING, SCH 80

61

AS REQUIRED

1
1
½")

1

!
I
TYP OF 5

TYP

OF 5

TYP

TYP

OF

OF d

8

TYP

OF 4

TYP OF 4

C,

BOILER

BLOCK AND PIPING

62

ASSEMBLY

BOILER

BLOCK AND PIPING ASSEMBLY

KEY #

ITEM NUMBER

DESCRIPTION

QUANTITY

1

14631156

HOFFMAN VENT #77

1

2

14693001

¾"x 1/8" BUSHING

1

3

14693076

¾" BLACK TEE

1

4

14693040

¾" x 90 ° STREET ELBOW

2

5

14607002

¾" x 6½" NIPPLE

2

6

14622011

¾" ASME RELIEF VALVE

1

7

14607201

¾"x 2" NIPPLE

1

8

14695810

¼"-20 HEX NUT W/SERRATED

WASHER

HEAD

9

9

14695802

8-32 x 3/16" SOC HD CAP SCREW

2

10

14631000

36T26-42930

1

11

14695801

¼"-20 x 1½" SOC HD CAP SCREW

5

12

14695805

¼"-20 x 1¼" STUD THREADED

9

13

41800910

TESTED BLOCK (INCLUDES

14

14695040

¼"x 1¼" CARRIAGE

15

14631101

62017 ½" NPT x ½" ID TUBE STRAIGHT

1

16

14607044

1¼" x2½"

NIPPLE BLACK

2

17

1510001

1¼" x¾"x

1¼" TEE

2

18

14622000

¾" DRAIN VALVE

CASTING TEMP. SAFETY SWITCH

8,11,14 AND 20,22)

BOLT

1
4

1

19

14693056

1" SQ SOCKET PLUG

20

14619002

EMPI RE SIGHT GLASS

12
1

21

14693058

¾" SQ HD PLUG

1

22

14693004

¾" x ½" BUSHING

1

23

14662804

123869A CONTROL WELL ½" NPT

1

24

14631324

L4006A 2155B HI LIMIT AQUASTAT

1

25

14693001

¾"x 1/8" BUSHING

1

26

1260006

TEMP & PRESSURE

27

14631004

SIGHT GLASS ADAPTER

1

28

14631005

1/8" NPT ¼" HOSE ID BRASS BARB FI-FFING

1

GAUGE

63

1

TO SIGHT
GLASS ADAPTER

D,

MIXER AND AIR PRESSURE

84

SWITCH

ASSEMBLY

KEY #
1
2A
2B
2C
3
4
5
6
7A
7B
7C
8
9
10
11A
11B
12
13
14
15
16
17
18
19
2O
21
22
23
24
25A
25B
25C
26
27A
27B
27C
27D
27E
27F

ITEM NUMBER
14631023
14631006
14631007
14631008
14631025
14695810
12101008
14631311
42531100
42531101
42531102
42531103
14631015
14695809
43800013
43800014
14631024
14631309
14607301
14693805
14631307
14631308
14631104
14631313
14631143
14631151
14631033
14631314
14629003
14631312
14631010
14631044
14631103
14631310
14631029
14631030
14631032
14631036
14631037

MIXER AND AIR PRESSURE SWITCH ASSEMBLY
DESCRIPTION
BURNER GASKET
100 BURNER IBSI!
75 BURNER !BSI)
50 BURNER IBSI)
MIXER GASKET
¼"-20 HEX NUT W/SERRATED WASHER HEAD
MIXER CASTING MACHINED
2'"1½" FLEXIBLE COUPLING
100 AIR BAFFLE
75 AIR BAFFLE
50 AIR BAFFLE
AIR INLET
2" FERNCO COUPLING
10-32"x3/8" MACHINE SCREW
HOT SURFACE IGNITER IFOR 50/75)
HOT SURFACE IGNITER !FOR 100)
HOT SURFACE IGNITER GASKET
MIXER BUSHING
½"" 3" STD BLACK NIPPLE
1/8" NPT BRASS PLUG - 3/16" HEX SOCKET
HONEYWELL GAS VALVE VR8205
5/16-24"1/4 HOSE ID BRASS BARB FITTING
62064 ¼"ID TUBE TEE
¼"ID TUBE 4-WAY CONNECTOR
3/8" HOSE CLAMP HC-6ST
PC250-12Vl NYL CAP
59006 ¼"IDx3/8"OD VINYL TUBING
1/4"lg'3/8"og VINYL TUBING IRED)
1/4" ID SILICONE TUBING
PPS10111-2680 AIR
PPS10111-2681 AIR
PPS10111-2682 AIR
62043 ½" NPT'I/2"ID
GAS
GAS
GAS
GAS
GAS
GAS

ORIFICEORIFICE ORIFICEORIFICE ORIFICE ORIFICE -

PRESSURE SWITCH !100)
PRESSURE SWITCH !751
PRESSURE SWITCH 150)
TUBE ELBOW

NATURAL,
NATURAL,
NATURAL,
PROPANE,
PROPANE,
PROPANE,

65

100N !0.0860, #44)
75N I0.0760, #48)
50N I0.0615)
100P !0.0670, #51)
75P I0.0605)
50P (0.0492)

QUANTITY
1
1
1
1
1
5
1
1
1
1
1
1
1
2
1
1
1
1
1
3
1
1
1
1
10
2
AS REQUIRED
AS REQUIRED
AS REQUIRED
1
1
1
1
1
1
1
1
1
1

TO

MIXER

FLUE ADAPTER

E,

AND EXHAUST

ASSEMBLY

FLUE ADAPTER AND EXHAUSTER ASSEMBLY

14683301

KEY#

ITEM NUMBER

1
1A

182009002
14631101

1B

DESCRIPTION

QUANTITY

EXHAUST TEE ASSEMBLY - 1-A,B,C,D,E & F
82017 1/2"NPTxl/2"ID TUBE STRAIGHT

1
1

14631013

PVC 1 1/2" MALE SLIP x 1/2" FEMALE NPT

1

1C

14631014

PVC SCH 40 2"x1-1/2" REDUCER

1

1D

14695815

3/4" ALUMINUM FLAT WASHER

1

1E
1F
2

14631305
14631304
14631028

2" CPVC TEE, SCH 80
2" CPVC PIPE'2-1/2", SCH 40
VENT SWITCH GASKET

1
1
1

3

14631303

36TXll-22491

4
5

14695808
14631077

#-4-20xl/4" HWH PLAST FORM SCREW
116516-11 INDUCED DRAFT BLOWER

INDUCER TEMP SAFETY SWITCH

2
1

1

6

14631026

BLOWER GASKET

1

7

12101021

FLUE CONNECTOR

1

8

14631027

RECOVERY COIL GASKET

1

9

14695810

1/4"-20 HEX NUT W/SERRATED WASHER BLOCK

4

10
11

14693804
14631103

1/8" NPT 1/4" HOSE ID BRASS BARB FI-FRNG
62043 1/2" NPT'I/2" ID TUBE ELBOW

1
1

12

14631141

57134 3/4" SNAP GRIP CLAMP

13

14631035

59019 ½" ID'1/8 THK VINYL TUBE

14
15
16

14631301
14631302
14631151

HOSE, 3" LONG 2-3/8" ID X 2-3/4" OD
S.S. CLAMP, SIZE 44
PC250-12 VINYL CAP

1
2
2

17

14631143

3/8" HOSE CLAMP HC-6ST

2

66

2
AS REQUIRED

Rev. 3, August 2003



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 67
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 15:48:18 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu