Cara C 11499 Instruction Owners Manual

User Manual: Cara

Open the PDF directly: View PDF PDF.
Page Count: 46

DownloadCara C-11499 Instruction Owners Manual
Open PDF In BrowserView PDF
SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED PAPER.

PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE

Cara

BY: SHERWOOD INDUSTRIES LTD

OWNER’S MANUAL
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapours and liquids in the
vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS
• Open windows/extinguish any open flame.
• Do not try to light any appliance.
• Do not touch any electrical switch or use
any phone in your building.
• Immediately call your gas supplier from
a neighbour’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
This appliance may be installed in an aftermarket permanently located, manufactured
(mobile) home, where not prohibited by local
codes.
This appliance is only for use with the type of
gas indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certified kit is used.

WARNING: If the information in this

manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of
life. Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.

Massachusetts installations (Warning): This product must be installed by a licensed plumber
or gas fitter when installed within the Commonwealth of Massachusetts. Other Massachusetts
code requirements: Flexible connector must not be longer than 36in., a shut off valve must be
installed; only direct vent sealed combustion products are approved for bedrooms/bathrooms. A
carbon monoxide detector is required in all rooms containing gas fired direct vent appliances.

50-1630

Safety Precautions
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
•
All ENVIRO gas-fired appliances must be installed in
accordance with their instructions. Carefully read all the
instructions in this manual first. Consult the building authority
having jurisdiction to determine the need for a permit prior
to commencing the installation.
•
NOTE: Failure to follow these instructions could cause
a malfunction of the fireplace, which could result in death,
serious bodily injury, and/or property damage.
•
Failure to follow these instructions may also void your
fire insurance and/or warranty.
GENERAL
•
Installation and repair should be done by a qualified
service person. The appliance should be inspected before
the first use and, at least, annually by a qualified service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It is
imperative the control compartments, burners and circulating
air passageways of the appliance be kept clean.
•
Due to high temperatures, the appliance should be
located out of high traffic areas and away from furniture and
draperies.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away
to avoid burn or clothing ignition.

• Young children should be carefully supervised when
in the same room as the appliance. Toddlers, young
children and others may be susceptible to accidental
contact burns. A physical barrier is recommended if there
are at risk individuals in the house. To restrict access to a
fireplace or stove install an adjustable safety gate to keep
toddlers, young children and other at risk individuals out
of the room and away from hot surfaces.
•
Clothing or other flammable materials should not be
placed on or near the appliance.

WARNING
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW
CHILDREN TO TOUCH
GLASS.

2

FOR YOUR SAFETY
•
Installation and service must be performed by a qualified
installer, service agency or gas supplier.
•
This installation must conform to local codes or, in
the absence of local codes, to the current CAN/CGA-B149
installation code (Canada) or National Fuel Gas Code ANSI
Z223.1.2 (USA)
•
To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners
have gone out on their own, open the glass door and
wait 5 minutes to air out before attempting to relight the stove.
•
Always keep the area around these appliances clear of
combustible material, gasoline and other flammable liquids
and vapours.
•
These appliances should not be used as a drying rack
for clothing or for hanging Christmas stockings/decorations.
•
Due to the paint curing on the stove, a faint odor and
slight smoking will likely be noticed when the stove is first
used. Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another
room or inside the building. Make sure the specified vent
pipe is used, properly sized and of adequate height to
provide sufficient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specifically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualified service person.
•
Never use solid fuels such as wood, paper, cardboard,
coal, or any flammable liquids, etc., in this appliance.
•
Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect the
heater and to replace any part of the control or gas control
systems that have been under water.
•
Do not abuse the glass by striking it or slamming the
door shut.

Table of Contents
Safety Precautions..................................................................................................................2
Table of Contents...................................................................................................................3
Codes And Approvals..............................................................................................................4
Specifications.........................................................................................................................5
Rating Label Location.................................................................................................5
Dimensions................................................................................................................5
Operating Instructions............................................................................................................6
Pilot Lighting Instructions............................................................................................6
Air Shutter..................................................................................................................7
Remote controls (Optional).........................................................................................8
Blower Speed.............................................................................................................8
Normal Sounds During Operation................................................................................8
Maintenance And Service........................................................................................................9
Routine Maintenance..................................................................................................9
Cleaning The Painted Surfaces....................................................................................9
Check Pilot and Burner Flames....................................................................................9
Glass Door Removal....................................................................................................9
Replacing the Glass..................................................................................................10
Cleaning The Firebox................................................................................................10
Burner Removal & Installation...................................................................................10
Firebox Baffle Removal..............................................................................................11
Fuel Conversion........................................................................................................12
Initial Installation.................................................................................................................14
Preparation For Installation.......................................................................................14
Clearances to Combustibles.......................................................................................14
Planning Your Installation..........................................................................................15
Approved Vent Parts.................................................................................................16
Vent Termination Restrictions....................................................................................18
Vent Configurations and Restrictor Settings................................................................19
Restrictor Installation................................................................................................20
Horizontal Installation...............................................................................................20
Vertical Installation...................................................................................................22
Cathedral Ceiling Installation.....................................................................................25
Corner Installations...................................................................................................26
Installation of Rear Vented Appliance.........................................................................27
Converting Top Vented into Rear Vented....................................................................27
Installation of Top Vented; Horizontal Termination......................................................28
Installation of Top Vented; Vertical Termination..........................................................28
Gas Line Connection and Testing...............................................................................29
Electrical Requirements For Gas Valve and Optional Blower..........................................30
Installation of Optional Blower...................................................................................31
Commonwealth of Massachusetts Installation Adendum..............................................32
Secondary Installation..........................................................................................................34
Installation of Log Set...............................................................................................34
Installation of Rock Set.............................................................................................36
Installation of Ceramic Firebox Liner (Optional)...........................................................38
Trouble Shooting..................................................................................................................39
Parts List.............................................................................................................................40
Parts List.............................................................................................................................41
Parts Diagram......................................................................................................................42
Warranty..............................................................................................................................43
Installation Data Sheet.........................................................................................................46

3

Codes And Approvals
DIRECT VENT ONLY: This type is identified by the sufix DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
TOP VENT DV

Certified for installation from 0-4500 ft (0-1372 m)

REAR VENT DV

Certified for installation from 0-4500 ft (0-1372 m) with 36” (915 mm)
snorkel (refer to ‘Converting Top Vented into Rear Vented’).

In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certified high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
•
This appliance has been tested by INTERTEK (Warnock Hersey) and found to comply with the
established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:

VENTED GAS FIREPLACE HEATER (Cara DV; NG/LPG)
TESTED TO: ANSI Z21.88a-2003/CSA 2.33a-2003 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This ENVIRO CARA Fireplace:
• Has been certified for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be
installed with a listed wall thermostat. IN USA: see current ANSI Z223.1
for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current
installation code CAN/CGA B149 in Canada or ANSI Z223.1/NFPA 54 in the
USA.
• Must be properly connected to an approved venting system and not connected
to a chimney flue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding first fire up): When the unit is turned
on for the first time, it should be turned onto high without the fan on for
the first 4 hours. This will cure the paint, logs, gasket material and other
products used in the manufacturing process. It is advisable to open a
window or door, as the unit will start to smoke and can irritate some people.
After the unit has gone through the first burn, turn the unit off including the
pilot, let the unit get cold then remove the glass door and clean it with a
good gas fireplace glass cleaner, available at your local ENVIRO dealer.

4

Specifications
WARNING:
Operation of this heater when not connected to a properly installed and maintained venting system can
result in carbon monoxide (CO) poisoning and possible death.

Rating Label Location:
The Rating Label is located on the inside surface of the pedestal control door.

Dimensions:
Rear Vent

Top Vent
213/16”
(71mm)

173/8”
153/4”
(441mm) (400mm)

211/2”
(546mm)

167/8”
(426mm)

361/2”
(927mm)

325/16”
(821mm)

153/4”
(400mm)

211/2”
(546mm)

Figure 1: Cara Exterior Dimensions.

5

Operating Instructions
For Your Safety, Read Safety Precautions And Lighting Instructions Before Operating.
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.

Pilot Lighting Instructions:

CAUTION:

Hot while operating. Do not touch, severe burns may result.
Keep children, clothing, furniture, gasoline or other flammable vapors away.

CAUTION: Do not operate this fireplace with the glass removed, cracked or broken. Replacement of the glass should be done by a licensed
or qualified person! This appliance needs fresh air for safe operation and must be installed with provisions for combustion and ventilation air.
See installation and operating instructions manual. Keep burner and control compartment clean.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage, or loss of life. Refer
to owner's manual provided with this appliance. See installation and operating instructions accompanying appliance. Installation and service
must be performed by a qualified installer, service agency, or the gas supplier.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
C) Use only your hand to push in or turn the gas control knob; NEVER
A) This appliance is equipped with a pilot, which must be lit by hand by
use tools. If the knob will not push in or turn by hand, do not try to
following these instructions exactly.
repair it. Call a qualified service technician. Force or attempted repair
B) BEFORE LIGHTING smell all around the appliance area for gas and next to
may result in a fire or explosion.
the floor because some gas is heavier than air and will settle on the floor.
D) Do not use this appliance if any part has been under water.
WHAT TO DO IF YOU SMELL GAS:
Immediately call a qualified service technician to inspect the appliance
Do not try to light any appliance. Do not touch any electrical switch: do not
and to replace any part of the control system and any gas control
use any phone in your building. Immediately call your gas supplier from a
which has been under water.
neighbor's phone. Follow the gas suppliers instructions. If you cannot reach
your gas supplier, call the fire department.

LIGHTING INSTRUCTIONS
WARNING: This gas valve has a lockout device, which will not allow the
pilot burner to be relit until the thermocouple has cooled. If the knob does
does not pop up when released, stop and immediately call your service
technician or gas supplier. If the pilot does not stay lit after several tries,
turn the gas control knob to “OFF” and call your service technician
or gas supplier.
6. Turn the gas control knob counter clockwise
to the “ON” position.
Flip the burner switch to “ON” THEN
TURN THE “HI/LOW” knob to the
desired setting.
7. Turn on the electrical power to the unit.
OUT

TP TH

I

L

O

H

TP

O FF

PI L OT

TH

ON

STOP! Read the safety information above on this label.
Turn off all electrical power to this appliance.
Turn off the gas control knob clockwise
to the off position.
Open door. Wait fIve (5) minutes to clear out any gas. Close door. If
you smell gas STOP! Follow “B” in the above safety information.
If you do not smell gas go to the next step.
5. Find pilot-located to the left behind the side log.
Turn the gas control knob counter-clockwise
to
“PILOT”. Push the gas control in fully and hold, keep knob
depressed for about 30 seconds after the pilot is lit.
Release knob. If pilot goes out, repeat steps 4 through 5.

IN

1.
2.
3.
4.

LO
PI T

TO TURN OFF GAS TO APPLIANCE
1. Flip burner switch to “OFF”
2. Turn the gas control knob clockwise

to the “OFF” position.

3. Turn off all electrical power to the appliance if service is to be
performed.

Figure 2: Lighting Instruction Label.

1. Turn off the gas to the fireplace. If not recently done, remove the door and let the unit air out
for at least five (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints
with soapy water. NEVER USE OPEN FLAME FOR LEAK TESTING.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.
While holding the gas control knob in, press the piezo ignitor several
times until the pilot light starts. Hold the gas control knob in for 30
seconds. Check that the pilot has fully engulfed the thermocouple
assembly (refer to Figure 6).

Thermocouple
Ignitor

Pilot/Orifice

3. Start the main burner by turning the gas control knob to ON and then
turn the rocker switch to ON. Check that all burner ports have flame.
4. Leak test all gas joints again.
6

Figure 3: Pilot Assembly.

Operating Instructions
For Your Safety, Read Safety Precautions
And Lighting Instructions Before Operating
Low

High

Ignitor

On/Off

Fan

Remote Control Receiver
(optional)

Off

Cara
Figure 4: Cara Control Panel.

Air Shutter:
The air shutter is controlled by
sliding the air shutter adjustment
screw (shown in Figure 5) either
forwards or backwards. The
adjustment screw, for the primary
air, is located on the bottom of the
firebox. The air shutter nut can be
accessed by removing the control
panel. This is best done during the
initial installation.
Sliding the shutter forwards
increases the primary air while
sliding the shutter backwards
decreases the primary air.
The air shutter allows the amount
of air coming into the fireplace to be
adjusted in order to accommodate
different climates and venting
arrangements. Start the pilot and
then the burner. Make sure the pilot
flame is burning normally and none
of the burner ports are plugged. Let
the fireplace burn for roughly fifteen
(15) minutes and then examine the
flames, compare the flames to
Figure 59 or the Front Cover.

Air Shutter Adjustment Nut

Figure 5: Air Shutter Adjustment.

7

Operating Instructions
For Your Safety, Read Safety Precautions
And Lighting Instructions Before Operating
The ideal flame will be blue at the base and light orange above. The flames should be of medium height.
If the flames look like this (refer to Figure 59 or the Front Cover), no adjustment is needed. If the flames
are fairly short and mostly blue, the fireplace is getting too much air. Therefore, the air shutter should be
closed slightly until the correct flames are achieved. Flames that are very orange, with tall, dark, stringy
tips, are not getting enough air. Open the air shutter until the flames clean up. If the shutter is opened, or
closed all the way, and the correct flames cannot be attained, turn off the gas and contact the dealer.
Warning: Incorrect air shutter adjustment may lead to improper combustion, which is a safety hazard.
Contact the dealer if there is any concern about the venturi adjustment.
Table 1: Air Shutter Setting Information.

Amount Air Shutter is Open

Natural Gas

Propane

¼” (6mm) minimum

Completely Open

Remote controls (Optional):
This fireplace can use an optional remote control or an optional cordless wall thermostat. If either of
these are to be used to control the fireplace for the majority of the time, leave the ON/OFF switch (on the
rear of the unit) in the “ON” position. Consult the instructions included with the remote/wall thermostat
for operation guidelines. When insalling the Remote Control module, cut out the label along the dotted
line of the Cara Control Panel, and mount the module to the back of the panel using the two (2) provided
Torx T-20 screws and nuts.

Blower Speed:
For units equipped with blowers, the blower will come on only when the fireplace is up to temperature
(approximately 12 minutes with unit on high). The blower is equipped with a variable fan controller,
located in the front control panel. This manual control will adjust the fan speed from high to low or turn
the fan off. A remote control for the fan is available through your dealer.

Normal Sounds During Operation:
Table 2: Normal Sounds

Component
Cara
Burner
Temperature Sensor
Pilot Flame
Blower / Fan
Gas Control Valve

8

Sound & Reason
Creaking when heating up or cooling down.
Light pop or poof when turned off; this is more common with LP units.
Clicking when it senses to turn the blower on or off.
Quiet whisper while the pilot flame is on.
Air movement that increase and decreases with the speed of the blower.
The blower is pushing the heat from the fireplace into the room.
Dull click when turning on or off, this is the valve opening and closing.

Maintenance And Service
Routine Maintenance:
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot flame should be blue with little or no yellow on the tips.
Warning: Clearances must be sufficient to allow access for maintenance and service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specifically approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualified agency.

Cleaning The Painted Surfaces:
Painted faces should be wiped with a damp cloth periodically.

Check Pilot and Burner Flames:
Periodically do a visual check of the pilot flames. One flame
should encompass the ignitor and thermocouple and the
other should burn over the burner ports (see Figure 6). Also
check that the burner is operating correctly, refer to Figure
59 or the Front Cover.

Figure 6: Pilot Flame.

Glass Door Removal:
IMPORTANT: If the door is not engaged
properly on the hooks, damage to the
fireplace and/or floor, personal injury, or
even death may occur.
1. Turn the unit off and wait until it has
cooled down.
2. Remove the cast iron louvers from above
the door by lifting the louvers up and
out.
3. Pull the two (2) door hooks, on top of the
door, forward and up (see Figure 7).
4. Lift the glass door assembly straight up
and out.
Ensure the door is properly fastened before
attempting to light the appliance. To reinstalling the glass door, slide the three (3)
door hook slots, on the bottom of the door,
over the three (3) door hooks on the unit.
Pull the two (2) door hooks, on top of the
door, forward and slide them into the two
(2) door hook slots.

Door Hook
Door Hook Slots

Door Hooks

Figure 7: Door Removal / Installation.

9

Maintenance And Service
Replacing the Glass:
IMPORTANT: Do not operate with the glass front removed, cracked or broken. The glass in the
fireplace is a high temperature ceramic. If the glass is damaged in any way, a factory replacement door
is required (see Parts List). Wear gloves when handling the damaged glass door assembly to prevent
personal injury. When the glass door assembly is being transported, it must be wrapped in newsprint and
tape and/or a strong plastic bag. Removal and replacement of the glass from the door must be done by
a licensed or qualified service person. The door assembly must be purchased from an ENVIRO dealer.
No substitute materials are allowed.

Cleaning The Firebox:
With the fireplace at room temperature, carefully remove the logs. Gently remove the ceramic burner
and place on a paper towel. Vacuum the bottom of the firebox thoroughly. Carefully clean any dust off
the logs and remove any lint from the burner and pilot. At this time, inspect the burner pan for cracking
or severe warping. If a problem is suspected, contact the dealer. Check the logs for deterioration or large
amounts of soot; a small amount on the bottom side of the logs is normal. Replace the logs as in the Log
Set Installation section.

Burner Removal & Installation:
IMPORTANT: Ensure the unit is off and at room temperature.
To remove the burner:
1. Remove the glass door as shown in the Maintenance

and

Service - Glass Door Removal.

2. Carefully remove the log set.
3. Slide the burner back just far enough so the front edge of the burner does not catch on the front lip
of the firebox.
4. Lift the front of the burner up and out of the firebox.

Mixing Tube
Mixing Tube Box

Mixing Tube
Mixing Tube Box

Figure 8: Install the Log Set Burner to the Firebox.

10

Figure 9: Install the Rock Set Burner to the Firebox.

Maintenance And Service

To install the burner:
1. Insert the mixing tube into the mixing
tube box (refer to Figure 8 or 9).
2. When the burner is resting in the
firebox ensure that the front edge of
the burner is lined up with the front
lip of the firebox (see Figure 10 or
11).

Bring front lip of burner
to front edge of firebox.
Figure 10: Align Log Set Burner With Firebox.

3. Re-install the log set or rock set
(see Secondary Instalation - Log Set
Installation or Secondary Instalation Rock Set Installation) and the door.
4. Check burner for proper operation.
Bring front lip of burner
to front edge of firebox.
Figure 11: Align Rock Set Burner With Firebox.

Firebox Baffle Removal:
The firebox baffle can be remove when cleaning the venting pipe.
1. Remove the glass door as shown in the Maintenance

and

Service - Glass Door Removal.

2. Remove the two (2) Torx T-20 screws holding the front of the firebox baffle in place (refer to Figure
12). IMPORTANT: The baffle should be held in place when the screws are removed to prevent it from
falling, which could damage the firebox liner, log set, or rock set.
3. Carefully push the back of the baffle up while pulling the front down (see A’s in Figure 13) then pull
the baffle out of the firebox.
4. Re-install the firebox baffle and the door when done.

A
B
A

Figure 12: Firebox Baffle Screws Removal.

Figure 13: Firebox Baffle Removal.

11

Maintenance And Service
Fuel Conversion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualified service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a fire, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualified service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specified in the manufacturer’s
instructions supplied with the kit.
Kit Parts List:
Orifice (NG - PO512-37 DMS or LP - PO512-1/16” DMS)
Installation instruction sheet
Carefully inspect all parts supplied with this conversion kit. If
any parts have been damaged or are missing, contact your
dealer, distributor or courier company to have them replaced
before starting this installation.
Conversion Kit Installation:
1. Turn control knob on the gas valve to the “OFF” position
and shut the gas supply off at the shut-off valve upstream
of the unit. CAUTION: The gas supply must be shut off
prior to disconnecting the electrical power and before
proceeding with the conversion. Allow the valve and unit
to cool down to room temperature.
2. Remove the glass door as shown in the Maintenance and
Service - Glass Door Removal.
3. Carefully remove the log set.
4. Slide the burner back just far enough so the front edge of
the burner does not catch on the front lip of the firebox.
Lift the front of the burner up and out of the firebox. See
Maintenance and Service - Burner Removal & Installation.
5. Convert the burner orifice:
a) Remove the main burner orifice with a ⅜” socket
(refer to Figure 14).
b) Install the alternate orifice from the kit.
6. Convert the pilot injector:
a) Loosen the pilot stem a half turn using a 7/16” wrench
(refer to Figure 15).
b) Slide the tab to the other side of the pilot stem (refer
to Figures 16 & 17).
c) Tighten the pilot stem.

Figure 14: Removing the orifice.

Figure 15: Turning Pilot Stem.

Natural Gas Position:
NA Stamp Visible
.020” (0.51mm) Hole Size

L.P. Gas Position:
LP Stamp, Hole, & Red
Colour Code Visible
.014” (0.36mm) Hole Size

Figure 16: NG & LP Gas Positions on Pilot.

12

Maintenance And Service

Fuel
Conversion
Tab on Pilot

7. Convert the SIT gas valve:
a) Remove the extension knobs from the valve.
b) Remove the black protection cap from the HI/LO knob
by hand shown in Figure 18.
c) Insert a 5/32” or 4 mm Allen wrench into the hexagonal
key-way of the screw (see Figure 19), rotate it counterclockwise until it is free and extract it.
d) Check that the screw is clean and if necessary remove
dirt.

Figure 17: Fuel Conversion Tab on Pilot.

e) Flip the screw (refer to Figure 20).
f) Using the Allen wrench as shown
Loosen
Tighten
in Figure 19, rotate the screw
clockwise until a torque of 9 inch lbs.
WARNING! Do not over tighten the
screw. It is recommended that you
grip the wrench by the short side.
g) Verify that if the conversion is from
NG to LPG, the screw must be reFigure 18:
assembled with the red o-ring visible Removing valve
(refer to Figure 21). If the conversion
cap.
is from LPG to NG, the red o-ring of the
Figure 19: Removing
Figure 20: Flip
screw must be not visible.
valve screw.
valve screw.
h) Re-attach the black protection cap that
Red o-ring
Red o-ring
was removed in step a (Figure 18).
is visible
is not visible
8. Re-install the burner, ceramic panels, log
set and glass door. Also refer to Secondary
Installation - Log Set Installation. When
re-installing the burner, ensure that the
burner to pilot hood relationship is similar
LPG Configuration
to what is shown in Figure 22.
Figure 21: O-ring on valve screw.
9. Reconnect the main gas line if it was
disconnected and open the shut-off valve at the gas line to the unit.
10. Use a small brush to apply a warm soapy water solution to all gas
connections (use a half dish soap and half warm water). If a gas leak
is present, bubbling will occur. Gas leaks can be repaired by using an
approved pipe thread sealant or approved Teflon tape. NEVER USE AN
OPEN FLAME WHEN TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the main burner in both the “HI” and “LO” positions to verify
proper burner ignition and operation and proper flame appearance
(refer to Figure 59 or the Front Cover). Also refer to Secondary
Installation - Log Set Installation for a flame appearance picture.
13. MAKE SURE that the conversion label is installed on or close to the
Figure 22. Pilot assembly
rating label to signify that the unit has been converted to a different
beside the burner
fuel type.
13

Initial Installation
QUALIFIED INSTALLERS ONLY
WARNING: Operation of this heater when not connected to a properly installed and maintained venting
system can result in carbon monoxide (CO) poisoning and possible death.

Preparation For Installation:
• Remove the packaging from the appliance, and check to make sure there is no damage. If damage is
found, please report it to both the carrier and your dealer as soon as possible.
• Before beginning, carefully check the glass door and the log set
• Locate a position where the flue system of the stove can be properly installed without damaging the
integrity of the building; e.g. cutting a wall or ceiling joist.
• Check stove and flue system clearance requirements.
• Locate the stove where it can be accessed by a gas supply line.
• Locate the stove in a large and open room that is centrally located in the house. This will optimize heat
circulation and comfort.
• As the stove can be equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8
m) of the stove.
• The flow of combustion and ventilation air must not be obstructed.

Clearances to Combustibles:
CLEARANCES MUST BE SUFFICIENT TO ALLOW ACCESS FOR MAINTENANCE AND SERVICE.
Back Wall

Letter
A
B
C
D
E

Description
Sidewall to unit
Backwall to unit
Corner to unit
Ceiling to floor
Floor (on hardwood
and linoleum)

Clearance
11 inches
2.5 inches
2.5 inches
90 inches
0 inches

(279 mm)
(64 mm)
(64 mm)
(2286 mm)
(0 mm)

Side Wall

Table 3: Clearance to Walls in an Open Area, refer to Figure 23.

A

Adjacent Wall

C

Clearance
43½ inches (1105 mm)
48 inches (1219 mm)
24 inches (610 mm)

Adjacent Wall

Table 4: Clearance to Walls in an Alcove

Description
Minimum Width
Minimum Height
Maximum Depth

B

C

Figure 23: Clearance to Walls in an Open
Area, refer to Table 3.

14

Initial Installation
QUALIFIED INSTALLERS ONLY
Planning Your Installation:
Round Support
Box/Wall Thimble

Horizontal
Termination
Pipelength

Vertical
Termination

90° Elbow

Storm Collar
Flashing

Pipelength

Ceiling Firestop
Round Support
Box/Wall Thimble

Figure 24 Common Horizontal Installation.

Cathedral Ceiling
Support Box
36" (915 mm)
Snorkel

Round Support
Box/Wall Thimble

Pipelength

Pipelength

Figure 25: Common Vertical Installation.

Onto Stove
Adaptor

2 ft (610 mm)
Pipelength

Figure 26: Common Snorkel Installation.

15

Initial Installation
QUALIFIED INSTALLERS ONLY
When planning your installation, it will be necessary to select the proper length of vent pipe for your
particular requirements. It is important to note when passing through a wall, the maximum allowable
wall thickness is 10 inches (25.4 cm); 1½ inches (3.8 cm) clearance to combustibles must be maintained.
Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine
the length of vent pipe required for vertical installations, measure the distance from the appliance flue
outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow
for sufficient vent height above the roof line. For two story applications, a fire stop is required at each
floor level. If an offset is needed in the attic, additional pipe and elbows will be required. To connect the
venting system to the appliance flue outlet, a twist-lock adapter is built into the appliance at the factory.
Refer to Initial Installation - Vent Configuration and Restrictor Settings for venting parameters.
Your total vent pipe length must be within the grid area of Figures 28 and 29. If a 90° elbow is used in
the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run.
There are three (3) basic types of Direct Vent System installations. The three (3) types of installations are
shown in Figures 24 through 26.

Approved Vent Parts:
Table 5: Approved Vent Manufacturers.

Manufacturer

Trade Name

Nominal Sizes

American Metal Products

AmeriVent Direct

4” - 6 5/8”

Security Chimneys International LTD

Secure Vent

4” - 6 5/8”

Selkirk Metalbestos

Direct-Temp

4” - 6 5/8”

Simpson Dura-Vent

Direct Vent GS

4” - 6 5/8”

The Cara fireplace has been tested and certified for use with AMERICAN METAL PRODUCTS “AMERIVENT
DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S “SECURE VENT
DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available for horizontal and
vertical venting. When using Simpson Duravent, it is recommended that, before installation, a bead of
RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-Pac to each inner
joint. When planning an installation, it will be necessary to select the proper length of vent pipe for the
particular requirements.
WARNING: Do not mix parts from different vent manufacturers’ systems.
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS
starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use
of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the
Intertek WH listing of the appliance.

16

Initial Installation
QUALIFIED INSTALLERS ONLY
Table 6: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
Direct Vent GS

Direct-Temp

Secure Vent

908

4DT-6

SV4L6

Ameri Vent Direct

Description
6” pipe length

4D7

7” pipe length

907

4DT-9

9” pipe length

906

4DT-12

SV4L12

4D12

12” pipe length

904

4DT-24

SV4L24

4D2

24” pipe length

903

4DT-36

SV4L36

4D3

36” pipe length

902

4DT-48

SV4L48

4D4

48” pipe length

945

4DT-EL45

SV4EBR45

4D45B

45° elbow, black

990

4DT-EL90

SV4EBR90

4D90B

90° elbow, black

950

4DT-VS

SV4VS

942

4DT-WT

SV4RSN

4DWT

Wall thimble

953

4DT-SC

SV4FC

4DSC

Storm collar

963

4DT-FS

SV4BF

4DFSP

Fire stop

988

4DT-WS/B

SV4BM

4DWS

Wall strap/support/band

970

4DT-HKA

SV0SHK

4DHTK1

Vinyl siding standoff/sheild

911

Horizontal termination kit (SD: Basic Kit,
SEL: Kit A, SC: Standard Kit)
11” to 14 ⅝” pipe, adjustable

4DT-AJ

4D12A
SV4LA12

4” to 10” pipe , adjustable
1½” to 12” pipe , adjustable

943

4DT-AF6

4DF

Flashing, 0/12 to 6/12 roof pitch

943S

4DT-AF12

4DF12

Flashing, 7/12 to 12/12 roof pitch

943F

SV4FA

Flashing, 1/12 to 7/12 roof pitch

SV4FB

Flashing, 8/12 to 12/12 roof pitch

SV4F

Flat flashing

980

4DT-VC

SV4CGV

991

4DT-HVC

984

4DT-HC

985

4DT-HHC

978

4DT-VKC

SV0FAK

981

4DT-ST36

SV4STC36

971

4DT-HKB

SV0SHK2

4DVC

Vertical termination
High wind vertical termination

SV4CHC

4DHC

Horizontal square termination
High wind horizontal termination

4DVTK

Vertical termination kit
36” Snorkel Termination

4DHTK2

Horizontal termination kit
(SD: Kit A, SEL: Kit B, SC: Kit)

17

Initial Installation
QUALIFIED INSTALLERS ONLY
Vent Termination Restrictions:
N

O
H

D E
L

B

C

B

Fixed
Closed

F

Openable

B

B

G

Fixed
Openable Closed

M

J

A

Termination Cap

G

Air Supply Inlet

G

Gas Meter

K

I

Restriction Zone

A

(Termination not allowed)

Figure 28: Vent Termination Restrictions, refer to Table 7.
Table 7: Vent termination clearances, refer to Figure 28.
Letter

Canadian Installation 1

A
B

US Installation2

12 in (30 cm)
12 in (30 cm)

9 in (23 cm)

C

12 in (30 cm)*

D

22-3/4 in (57.8 cm)*

E

22-3/4 in (57.8 cm)*

F

12 in (30 cm)*

G
H

Description
Clearance above grade, verandah, porch, deck, or balcony.
Clearance from window or door that may be opened.
Clearance from permanently closed window (to prevent
condensation).
Vertical clearance to ventilated soffit located above the
terminal, within a horizontal distance of 2 ft (60 cm) from
center line of terminal.
Clearance to unventilated soffit.
Clearance to outside corner.

18 in (45.7 cm)*

Clearance to inside corner.

3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly

3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*

Clearance to each side of center line extended above
meter/regulator assembly.

I

3 ft (91 cm)

3 ft (91 cm)*

Radial clearance around service regulator vent outlet.

J

12 in (30 cm)

9 in (23 cm)

Clearance to non-mechanical air supply inlet to building, or
the combustion air inlet to any other appliance.

K

6 ft (1.83 m)

L

7 ft (2.13 m)t

3 ft (91 cm) above if within 10
ft (3 m) horizontally
7 ft (2.13 m)*t

M

12 in / 30 cm+

12 in / 30 cm*+

Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located
on public property.
Clearance under verandah, porch, deck, or balcony.

N

12 in (30 cm)*

Clearance horizontally to any surface (such as an exterior
wall) for vertical terminations.

O

12 in (30 cm)

Clearance above roof line for vertical terminations.

1 In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier.
t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

NOTE: Venting terminals shall not be recessed into walls or siding.
18

Initial Installation
QUALIFIED INSTALLERS ONLY
Vent Configurations and Restrictor Settings:
Figure 28 and 29 shows the range of possible vent configurations if the unit is top vented, for vertical
and horizontal terminations, any layout that remains within the grid areas is acceptable. They also show
the vent restrictor required, relative to the length of vent pipe. Longer vertical vent lengths necessitate
greater restriction.
Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is
preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.
If the unit is rear vented it may have a maximum horizontal run of 36” (91.4 cm) and must be used with
a 36” (91.4 cm) snorkel termination.
40

40

38

38

36

36

34

34

60% RESTRICTOR
UP TO 4 ELBOWS

32

32
30

28

Feet of Vent From Top of Unit

Vertical Feet of Vent (From Top of Unit)

30

26
24
22
20
18

50% RESTRICTOR
UP TO 4 ELBOWS

16
14
12

UP TO 2 ELBOWS
NO RESTRICTOR

10

28
26
24
22
20
18

70% RESTRICTOR

16
14
12

8

50% RESTRICTOR

10

6

8

4
1 ELBOW
NO RESTRICTOR

2
0

75% RESTRICTOR

2

4

6

8

10

12

14

6
16

18

20

Horizontal Feet of Vent
NOTE: For best results, 3' (76.2cm) or more of
vertical rise is recommended.

Figure 28: Possible Vent Configurations for Top Vented;
Vertical and Horizontal Terminations with Elbows.

4

NO RESTRICTOR

2
0
Figure 29: Possible Vent Configurations for Top
Vented; Straight Vertical Vent & Terminations.

19

Initial Installation
QUALIFIED INSTALLERS ONLY
Restrictor Installation:
The ENVIRO CARA has been designed for use with an add-in restrictor. The restrictor is designed to
maintain flame appearance when installing this unit with vertical chimneys as well as installations with
longer horizontal vent applications. It does this by controlling the amount of air moving through the vent
pipe.
1. Choose the appropriate restrictor for the installation (see Initial Installation - Vent Configurations and
Restrictor Settings). To avoid injury, install the restrictor when the fireplace is cool or use welder’s
gloves or oven mitts.
2. Remove the glass door (see Maintenance and Service - Glass Door Removal) and the firebox baffle (see
Maintenance and Service - Firebox Baffle Removal).
3. Remove two (2) ¼” hex head screws for the restrictor, place restrictor in the flue collar (see Figure
30) and fasten in place with the two (2) ¼” hex head screws.
4. Re-install the firebox baffle and the door.
5. Wait for the unit to warm up to operating temperature to ensure a proper and clean burning unit.

Figure 30: Flue Restrictor Installation.

Horizontal Installation:
1. Set the appliance in the desired location. Check to determine
if wall studs or roof rafters are in the way when the venting
system is attached. If this is the case, you may want to adjust
the location of the appliance.
2. Direct vent pipe and fittings are designed with special twist-lock
connections. Assemble the desired combination of black pipe
and elbows to the appliance adapter with pipe seams oriented
towards the wall or floor, as much out of view as possible.
Place a bead of Mil-Pac on the outer edge of the inner exhaust
pipe (non-flared end). Place a bead of high temperature
silicone on the male edge of the outer pipe. Push the pipe
sections completely together, then twist-lock one section
clockwise approximately ¼ turn, until the two sections are
fully locked. The female locking lugs will not be visible from
20

Female
Locking
Lugs
Sealant
Male
Locking
Lugs

Figure 31: Twist-Lock Connection.

Initial Installation
QUALIFIED INSTALLERS ONLY
the outside, on black pipe. They may be located by examining the inside of the female ends as shown
in Figure 31.
Notes:
(a) Twist-lock procedure: four (4) indentations, located on the female end of the pipes and fittings, are
designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe
indentations so they match and slide into the four entry slots on the male end.
(b) Horizontal runs of vent pipe must be supported every 36” (915mm). Wall straps are available for this
purpose, also when running horizontal pipe minimum clearances to combustibles must be maintained;
2” (51mm) at top, 1½” (38mm) at sides, 1½” (38mm) at bottom.
3. With the pipe attached to the stove in the correct location,
mark the wall for a 10” (25.4cm) x 10” (25.4 cm) square hole
(refer to Figure 32). The center of the square hole should
match the center line of the horizontal pipe. Cut and frame the
10” (25.4cm) x 10” (25.4cm) hole in the exterior wall where
the vent will be terminated. Refer to Figure 23 and Table 7. If
the wall being penetrated is constructed of non-combustible
material i.e. masonry or concrete, a 7” (17.8cm) hole is
acceptable.
4. Position the horizontal vent termination in the center of the
10” (25.4cm) x 10” (25.4cm) hole, and attach to the exterior
wall with the four screws provided. Before attaching the vent
termination to the exterior wall, run a bead of non-hardening
mastic around the edges, so as to make a seal between the
termination and the wall. The arrow on the vent termination
should be pointing up, insure that the proper clearances to
combustible materials are maintained.

10"
(254mm)

10"
(254mm)

Figure 32: Wall Framing Hole for
Horizontal Installation.

5. Before connecting the horizontal run of the vent pipe to the
vent termination, slide the black decorative wall thimble cover over the vent pipe.

6. Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the
cap assembly. It is important that the vent pipe extend into the vent cap a sufficient distance with a
minimum of 1¼” (3.2cm) overlap. Secure the connection between the vent cap pipe and the vent cap
by attaching the two sheet
metal straps extending from
11/4"
the vent cap assembly into
(3.2cm)
the outer wall of the vent
Fold strap
Woodscrews
pipe. Use the two sheet
here
metal screws provided
to connect the straps to
the vent pipe. Bend any
Sheet metal
screws
remaining portion of the
sheet metal straps back
towards the vent cap, so
the decorative wall thimble
Wall Thimble
will conceal it (see left
Strap
image in Figure 33).
Figure 33: Installing Decorative Wall Thimble.

21

Initial Installation
QUALIFIED INSTALLERS ONLY
7. Slide the decorative wall thimble up to the wall surface and attach with the screws provided. Apply
decorative brass or chrome trim if desired (see right image in Figure 33).
NOTES:
(a) The four (4) wood screws provided should be replaced with the appropriate fasteners for stucco,
brick, concrete, or other types of siding.
(b) For buildings with vinyl siding, a vinyl siding standoff, should be installed between the vent cap and
the exterior wall (see Figure 34). Attach the vinyl siding standoff to the horizontal termination. The vinyl
siding standoff prevents excessive heat from possibly melting the vinyl siding material. Note that the
horizontal vent termination bolts onto the flat portion of the vinyl siding standoff (shaded area in Figure
31), so that an air space will exist between the wall and the vent termination.
(c) The horizontal run of vent pipe must be level and should have a ¼ inch (6mm) rise for every
one foot (305mm) of run towards the termination. Never allow the vent to run downward. This
could cause high temperature and may present the possibility of a fire.
(d) The location of the horizontal vent termination on the exterior wall must not be easily blocked or
obstructed. Refer to Initial Installation - Vent Configurations and Restrictor Settings.
(e) When installing a vent pipe in a chase the minimum clearance to combustibles is 2” (51 mm).
(f) Maintain manufacturer’s clearances to combustibles with venting.

Cut vinyl siding
away to fit standoff

Wood screws (x4)

Nut (x4)
required
Wood
screw (x4)
Bolt (x4)
required

Figure 34: Installing Vent Cap with Vinyl Siding
Stand-Off.

Figure 35: Installing Horizontal Vent Termination.

Vertical Installation:
1. Check the instructions for required clearances (air spaces) to combustibles when passing through
ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. Do not pack air
spaces with insulation.
2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to the position
of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small
hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling,
mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other
framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, to avoid
cutting load bearing members.
22

Initial Installation
QUALIFIED INSTALLERS ONLY
3. To install the Round Support Box/Wall
Thimble in a flat ceiling, cut a 10” square
hole in the ceiling, centered in the hole
drilled in Step 2. Frame the hole as shown
in Figure 36.

Ceiling Joist

Framing

4. Assemble the desired lengths of black pipe
and elbows necessary to reach from the
appliance adapter up through the Round
Support Box. Insure that all pipe and
elbow connections are in their fully twistlocked position.
5. Cut hole in the roof centered on the small
10” (25.4cm) x 10” (25.4cm)
inside framing
hole placed in the roof from Step 2. The
hole should be of sufficient size to meet
minimum requirements for Clearance
1 1/2” (4cm) long
to Combustibles, as specified. Continue
wood screw (x4)
to assemble lengths of pipe and elbows
necessary to reach from the ceiling support
Figure 36: Wall Framing for Hole for Vertical Installation.
box up through the roof line. Galvanized
pipe and elbows may be utilized in the
attic, as well as above the roof line. The galvanized finish is desirable above the roof line, due to the
higher corrosion resistance.
6. Once the pipe sections have been joined, and run up through the hole in the roof, slip an elbow strap
over the exposed sections, bend the support straps outwards, and push the elbow strap down to the
roof level, as shown in Figure 34. Tighten the clamp around the pipe section. Use a level to make sure
the pipe is truly vertical. With roofing nails, secure the support straps to the roof. Seal the nails holes
heads with non-hardening
Vertical
mastic. Trim the excess
Termination
length of the support straps
that extend out beyond the
Storm Collar
Elbow Strap
edge of the flashing.
7. Slip the flashing over the
pipe
section
protruding
through the roof. Secure
the base of the flashing to
the roof with roofing nails.
Use a non-hardening sealant
between the uphill edge of
the flashing and the roof.
Insure the roofing material
overlaps the top edge of the
flashing as shown in Figure
37. Verify that you have at
least the minimum clearance
to combustibles at the roof
line.

Flashing
Roofing nails

Figure 37: Vertical Vent Termination Installation.

23

Initial Installation
QUALIFIED INSTALLERS ONLY
8. Continue to add pipe sections until the height of the vent cap meets the minimum code requirements.
Refer to Figure 38 and Table 6. Note that for steep roof pitches, the vent height must be increased. In
high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors
can result in poor draft, or down drafting. In these cases, increasing the vent height may solve the
problem.
9. Slip the storm collar over the pipe, and push it down to the top of the roof flashing as shown in Figure
37. Use the non-hardening sealant around the joint between the pipe and the storm collar.
10. Twist-lock the vent cap.

Table 8: Minimum ‘H’ for Figure 38.

Roof Pitch

Dimension ‘H’ obtained
from table below.

H

Figure 38: Height of Vertical Termination;
Reference Table 8.

Minimum Height
Feet

Meters

Flat to 7/12

1

0.3

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4

1.22

Over 12/12 to 14/12

5

1.52

Over 14/12 to 16/12

6

1.83

Over 16/12 to 18/12

7

2.13

Over 18/12 to 20/12

7.5

2.29

Over 20/12 to 21/12

8

2.44

NOTES:
(a) If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe
every 3 feet (91 cm), to avoid excessive stress on the elbows, and possible separation. Wall straps
are available for this purpose (see Figure 39).
(b) When ever possible, use 45° degree elbows instead of 90° degree elbows. The 45° degree elbow
offers less restriction to the flow of flue gases and intake air.
(c) For multi story installations. A ceiling firestop is required at the second floor, and any subsequent
floors (see Figure 40). The opening should be framed to 10” (25.4 cm) x 10” (25.4 cm) inside
dimensions, in the same manner as shown in Figure 36.
(d) Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent
passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard
building materials. However consult the appliance manufactures installation instructions for the
minimum allowable clearance between the outside of the vent pipe, and the combustible surfaces of
the enclosure. Do not fill any required air spaces with insulation.

24

Initial Installation
QUALIFIED INSTALLERS ONLY

Nails
Ceiling firestop

plumber’s tape
connected to
wall strap

Wall strap
45° elbows (x2)

Use clearances to as
defined by appliance and
vent pipe manufacturers.

Ceiling

Second floor
Figure 40: Multi-Story Vent Pipe Installation.

Figure 39: Use of Wall Straps.

Cathedral Ceiling Installation:
1. Follow installation steps 1 & 2 under Initial
Installation - Vertical Installation.
2. Using the plumb bob, mark the centerline of
the venting system on the ceiling and drill a
small hole through the ceiling and roof at this
point. From the roof, locate the drill hole and
mark the outline of the “Cathedral Ceiling
Support Box”.
3. Remove shingles or other roof coverings as
necessary to cut the rectangular hole for the
“Support Box”. Cut the hole ⅛” larger than
the “Support Box” outline.
4. Lower the “Support Box” through the hole in
the roof until the bottom of the “Support Box”
protrudes at least 2 inches (5 cm) below the
ceiling. Align the “Support Box” both vertically
and horizontally with a level as shown in
Figure 41 Temporarily tack the “Support Box”
in the place through the inside walls and into
the roof sheathing.

Figure 41: Cathedral Ceiling Support Box Leveling.

25

Initial Installation
QUALIFIED INSTALLERS ONLY
5. Using tin snips, cut the “Support Box” from the top corners
down to the roof line, and fold the resulting flaps over the
roof sheathing (Figure 42). Before nailing it in to the roof,
run a bead of non-hardening mastic around the top edges
of the “Support Box”, to make a seal between the box and
the roof. Clean out any combustible material from the
inside of the “Support Box”.
6. Complete the cathedral ceiling installation by following the
same procedures outlined in Steps 4 through 9 for Initial
Installation - Vertical Installation.
Figure 42: Cathedral Ceiling Support Box
Installation.

Corner Installations:
Do not interfere with the structural integrity of the walls.
For installations with a 36” (915 mm) snorkel refer to Figure 43 and Initial Installation - Vent Configurations
and Restrictor Settings. For other corner installations refer to Figure 44 and Initial Installation - Vent
Configurations and Restrictor Settings.
Also refer to Initial Installation - Clearances

to

Combustibles.

36” (915mm)
Snorkel

Outside
Wall

Outside
Wall

Inside Wall
Outside
Wall

21/2”
(64mm)
21/2”
(64mm)

Figure 43: Corner installation rear vented with
snorkel.

26

Figure 44: Corner installation top vented.

Initial Installation
QUALIFIED INSTALLERS ONLY
Converting Top Vented into Rear Vented:
This unit has been shipped as a 33,500 Btu/hr top-vented freestanding unit. This unit can be converted
to a rear vented unit for use with a 36” (915
mm) snorkel. Also refer to Initial Installation
- Installation of Rear Vented Appliance.
Rotate 180o
1. Carefully remove the trivet and the
stovetop. Place on a soft surface as not to
damage the finish.
2. Remove the four (4) ¼” screws that hold
the flue collar elbow to the unit body.

Venting
Gasket

3. Carefully remove the elbow being sure not
to damage the gasket that is glued to the
flue collar elbow, it seals the flue to the
firebox (see Figure 42).
4. Turn the elbow 180° to the rear vent
position and re-fasten with the screws
removed in step 2.
Figure 45: Converting Top Vented into Rear Vented.

Installation of Rear Vented Appliance:
Minimum Vent Terminal 36”
(914mm) High Snorkel Kit.

Place the unit into position.
Attach a small section of pipe on the unit and mark exterior
wall where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles. Frame hole as shown in Figure
32.
Install a wall thimble, interior finished collar, and the vent
section through the wall.

Siding
Exterior Wall
Dry Wall
Wall Thimble
Inside Finished Collar
Vent Pipe

THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL
KIT.
Seal around the vent terminal to the structure using a nonhardening mastic.
Also refer to Initial Installation - Vent Configurations and
Restrictor Settings and Initial Installation - Horizontal
Installation.

Figure 46: Installation for Rear Vented;
33,500 Btu/hr.

27

Initial Installation
QUALIFIED INSTALLERS ONLY
Installation of Top Vented; Horizontal Termination:
This is the most common type of installation style.
Set the unit in place.
Install a minimum 24” (61cm), although 36” (91.5cm) or
more vertical vent length recommended.
Install a 90° elbow, and mark the exterior wall where the
vent would pass through.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles around vent pipe. Frame the
hole as shown in Figure 32.

Inside Finished Collar
Vent Pipe
Dry Wall

Termination

Exterior Wall
Siding

Wall Thimble

Install wall thimble, interior finished collar, the vent section
through the wall, and then install the vent termination.
Seal around the termination using a non-hardening mastic.
Also refer to Initial Installation - Vent Configurations and
Restrictor Settings and Initial Installation - Horizontal
Installation.
Figure 47: Installation for Top Vented;
Horizontal Termination.

Installation of Top Vented; Vertical Termination:
Place the unit in place.

Vent Cap

Drop a plumb bob from the ceiling to the center point of the
flue outlet.

Roof Flashing

Cut a 10” (25.4 cm) hole in the ceiling and the roof. Refer
to Figure 36.

Insulation Guard

Roof Truss

Install the ceiling support and insulation guard.
Install the roof flashing. Ensure that the roof flashing is
installed under the roofing material so that a watertight
seal is created.
Install the flue pipe from the top of the unit through the
roof.

Ceiling Support
Inside Finished Collar
Flue Pipe

Ensure that all flue pipe and unit maintain required
clearances to combustibles.
Also refer to Initial Installation - Vent Configurations
and Restrictor Settings and Initial Installation - Vertical
Installation.
Figure 48: Installation for Top Vented;
Vertical Termination.

28

Initial Installation
QUALIFIED INSTALLERS ONLY
Gas Line Connection and Testing:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
Inlet
Manifold
Pressure Tap
GAS LINE CONNECTION
Pressure Tap
IN

OUT

I

L

O

H

TP

O FF
PI L OT

TH

ON
LO
PI T

• The efficiency rating of this appliance is a product
of the thermal efficiency rating determined under
continuous operating conditions and was determined
independently of any installed system.

TP TH

• This stove is equipped with a certified flexible pipe
located on the right side of the unit terminating in a ⅜”
male NPT fitting. Consult your local authorities codes or
the CAN/CGA B 149 (1 or 2) installation code in Canada,
or in the USA gas installations follow either local codes
or the current edition of the National Fuel Gas Code ANSI
Z223.1.

Pilot Adjustment
Screw

Hi/Low
Knob

Gas Control
Knob

Figure 49: Fully Labeled Gas Valve.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any
pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
½ psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
• Turn set screw 1 turn counter clockwise to loosen,
• Place 5/16” (8 mm) I.D. hose over pressure tap system.
• Check pressures using a manometer.
• When finished, release pressure, remove hose & tighten set screw.
Table 9: Pressure and BTU Information.

Main Burner
Manifold Pressure
Min. Manifold Pressure
Max Supply Pressure
Min. Supply Pressure
Max BTU/hr Input
Min. BTU/hr Input
Venturi Setting

Natural Gas
PO512-37 DMS
3.8” W.C. / 0.95KPa
1.1” W.C. / 0.27KPa
7.0” W.C. / 1.74KPa
5” W.C. / 1.24KPa
33,500 BTU/hr (9.82KW)
18,000 BTU/hr (5.28 KW)
¼” min.

Propane
PO512-1/16”
11.0” W.C. / 2.7KPa
2.9” W.C. / 0.72KPa
13.0” W.C. / 3.28KPa
12.0” W.C. / 2.98KPa
33,500 BTU/hr (9.82KW)
18,000 BTU/hr (5.28KW)
Completely Open

NEVER USE AN OPEN FLAME FOR LEAK TESTING.
29

Initial Installation
QUALIFIED INSTALLERS ONLY
Electrical Requirements For Gas Valve and Optional Blower:
The ENVIRO CARA will operate without electrical power. This model has a millivolt gas control, which
uses the pilot flame to generate enough electricity to operate the main burners. The appliance, when
equipped with a blower, must be electrically connected and grounded in accordance with local codes or
in the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE Part 1, SAFETY
STANDARDS FOR ELECTRICAL INSTALLATIONS, OR THE NATIONAL ELECTRICAL CODE ANSI / NFPA 70
in the U.S. When installing the Optional Remote Control System for the valve and the blower, refer also
to the Remote Controls section, and to Figure 4.
Table 10: Recommended Thermostat
Wire Size.

Wire Size
14 gauge
16 gauge
18 gauge
20 gauge
22 gauge

Max. Length
100 ft (30.48 m)
60 ft (18.29 m)
40 ft (12.00 m)
25 ft (7.62 m)
18 ft (5.49 m)

CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can cause
improper and dangerous operation.
Verify proper operation after
servicing.

ON/OFF
Burner Switch

Optional
Remote
Control

Blue

Thermocouple

Thermopile
Purple

Manifold
Pressure Tap

Inlet
Pressure
Tap

Gas Control
Valve

Grey

Optional
Wall Switch

70 ° F

Pilot Adjustment
Screw

UP
DOWN
COOL / HEAT

Optional
Thermostat

PROGRAM

Figure 50: Gas Control Valve and Optional Thermostat Wiring.

WARNING: Electrical grounding instructions. This appliance is equipped with a three-prong (grounding)
plug for your protection against shock hazard, and must be plugged directly into a properly grounded
three-prong outlet.
DO NOT cut or remove the grounding prong
from this plug.
ELECTRICAL INFORMATION:
Canadian Installations
The venting system must be installed in
accordance with the current CSA B149
installation code and/or local codes having
jurisdiction.
U.S.A. Installations
The venting system must be installed in
accordance with the current National Fuel
Gas Code, ANSI Z223.1, and/or local codes
having jurisdiction.

Power
Cord

Black
Black

Green/White

White
Snap Disk N/O

Green/Yellow

Black

Fan
Rheostat

Black
Black

Figure 51: Wiring Diagram for Electric Fan.

30

Initial Installation
Installation of Optional Blower:

Figure 52: Optional Blower (Fan) Installation.

1. Remove the pre-assembled blower from the packaging. Inspect the blower for damage. If damage is
noticed call your dealer, distributor or courier company and have components replaced.
2. Remove the side panel by pulling the panel up, slide the panel out of the bottom slots, and set
aside.
3. Install the temperature sensor into the holder.
IMPORTANT: The temperature sensor must be in contact with the firebox.
4. Open the pedestal door and remove the four (4) T-20 screws holding the Control Panel in place.
5. Fit the Fan Unit into the cabinet being careful to work around the gas and pilot lines. The fan will
fit up behind the gas valve. With an extension driver, fasten the Fan Unit in place with four (4) T-20
screws provided.
6. Install the Fan Controller into the provision in the Control Panel.
7. Install the Strain Relief plate into the stove back by fitting the tab on the plate into the stove back
and secure the plate with a T-20 screw provided.
8. Plug in all the electrical connections as indicated in Figure 51. This includes the Fan Controller,
Temperature sensor and Fan Unit.
9. Using the provided T-20 screw, located on the right mount below and behind the Temperature Sensor,
fasten the wire tie supplied. With the wire tie capture the fan wires including the temperature switch
wires, this will secure the wires and route them away from hot surfaces and out of the way of the fan
blades
10. Re-install the Control Panel and Side Panel.
11. Plug the fan assembly into the wall outlet and turn the unit on to ensure fan operation.
31

Initial Installation
Commonwealth of Massachusetts Installation Adendum:
These are the Special Requirements for Side-Wall Vented Appliances in Commonwealth of
Massachusetts
IMPORTANT: The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00
and 5.00 for installation of side-wall vented gas appliances as follows:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or
structure used in whole or in part for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installment of the
side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe
that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on
the floor level where the gas equipment is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling, building or structure served by the side
wall vented gas fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the installation of hard wired carbon monoxide
detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up
may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion
of installation, the owner shall have a period of thirty (30) days to comply with the above
requirements; however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required
in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior
of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign
shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled
equipment shall not approve installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.

32

Initial Installation
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential
purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting
system design or venting system components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system
components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not
provide the parts for venting the flue gases, but identifies “special venting systems”, the following
requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or
equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for
that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas
fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting
instructions shall remain with the appliance or equipment at the completion of installation.

33

Secondary Installation
Installation of Log Set:

Right Rear
Log Chunk

Left Rear
Log Chunk

The placement of the logs is not arbitrary. If
they are positioned incorrectly, the flames
can be “pinched” and will not burn correctly.
The burner has four (4) pins and four (4)
ledges which make alignment easier. Using
the pictures provided, carefully set the logs
in place.
NOTE: The logs are fragile and should
be handled gently.

Figure 53: Log Placement of Rear Log Chunks.

“Y” Log

1. Carefully remove logs from box and
check there is no damage. It is very
important to install all logs in their
proper position to ensure safe, optimum
operating conditions.
2. Place the Left Rear Log Chunk on the
two (2) left rear pins and the Right Rear
Log Chunk on the two (2) right rear pins
(refer to Figures 53 and 54).
3. Place the bottom of the “Y” Log in the
ledge at the front left of the burner and
the top of the log rests on the Right
Rear Log Chunk as shown in Figure 54
and 55.

Figure 54: Log Placement of “Y” Log.

Right Log

4. Place the bottom of the Right Log in the
ledge at the front right of the burner and
rest the top of the log against the rear
panel as shown in Figure 55 and 56.

Figure 55: Log Placement of Right Log.

34

Secondary Installation

5. Place the bottom of the Left Log in the ledge at
the front left of the burner and rest the middle
of the log against the Left Rear Log Chunk as
shown in Figure 56 and 57.

Center Log

Left Log

Figure 56: Log Placement of Left Log.

6. Place the bottom of the Center Log in the ledge
at the front center of the burner and rest the
middle of the log against the top of the “Y” Log
as shown in Figure 57 and 58.

Figure 57: Log Placement of Center Log.

7. Check that the log set is laid out as shown in
Figure 58 and install door.

Figure 58: Log Placement Complete.

35

Secondary Installation
CAUTION: NEVER OPERATE THIS APPLIANCE WITH THE GLASS DOOR REMOVED.

Important note: When the unit is
turned on for the first time, it should
be turned onto high without the fan
on for the first four (4) hours. This will
cure the paint, logs, gasket material
and the other products used in the
manufacturing process. It is advisable
to open a window or door, as the unit
will start to smoke and can irritate
some people. After the unit has gone
through the first burn turn the unit off
including the pilot, let the unit get cold
then remove the glass door and clean it
with a good gas fireplace glass cleaner,
available at your local ENVIRO dealer.
See Maintenance And Service on how to
remove door to clean glass.

Figure 59: Cara DR with a Good Flame.

Installation of Rock Set:
If the rocks are positioned incorrectly, the flames can be “pinched” and will not burn correctly. If the rocks
are broken due to handling or shipping, replace the rocks with new ones. Using the pictures provided,
carefully set the rocks in place.
NOTE: The rocks are fragile, particularly
after usage. Please handle with due care
during servicing.
1. Carefully remove rocks from box and check
there is no damage. It is very important to
install all rocks in their proper position to
ensure safe, optimum operating conditions.
2. Place the rock cluster onto the burner. There
are two (2) holes at the back corners of
the burner and two (2) aligning pins on the
bottom of the rock cluster (refer to Figures 60
& 61).
Figure 60: Installation of Rock Cluster.

36

Secondary Installation

Figure 61: Rock Placement of Four Large Rocks.

Figure 62: Rock Placement of Two Medium Rocks.

3. The four (4) large rocks are placed across front
of burner (see Figures 61 & 62). These rocks
are all the same shape, but must be rotated
in different positions to fit in the cut-aways in
the burner base. When there installed correctly,
there should be no visible gaps between the
rocks and the burner base. The gaps between
the rock cluster and the four (4) large rocks
needs to be maintained as smaller gaps will lead
to carbon deposits and build up.
4. Place the two (2) medium rocks; one on either
side of the cluster as shown in Figures 62 & 63.
These rocks can not be placed down between
the others.
Figure 63: Rock Placement of Seven Small Rocks.
5. Addition the seven (7) small rocks. These can be
added in some fashion like what’s shown in Figures 63 & 64 with three (3) on the top row with the
larger one in the center and two (2) smaller ones on either side.
7. Check that the rock set is laid out as shown in Figure 64 and install door.
8. Light the unit to enure it has a good flame (see Front Cover).

CAUTION: NEVER OPERATE THIS APPLIANCE WITH THE GLASS DOOR REMOVED.

Figure 64: Rock Placement Complete.

NOTES:
a. Some sooting on the rocks is normal. The
sooting should just be a thin covering in some
places on the center three (3) rocks of the
rock cluster. There should not be continuous
build up.
b. Surface cracks may appear after prolonged
use. This is due to the expansion and
contraction of materials during heating
cycles. Surface cracks are not a problem as
long as the assemblies are maintaining there
positions, and operation does not appear to
be altered.
37

Secondary Installation
Important note: When the unit is turned on for the first time, it should be turned onto high without the
fan on for the first four (4) hours. This will cure the paint, rockss, gasket material and the other products
used in the manufacturing process. It is advisable to open a window or door, as the unit will start to
smoke and can irritate some people. After the unit has gone through the first burn turn the unit off
including the pilot, let the unit get cold then remove the glass door and clean it with a good gas fireplace
glass cleaner, available at your local ENVIRO dealer. See Maintenance And Service on how to remove door
to clean glass.

Installation of Ceramic Firebox Liner (Optional):

Brick Panel Clip

Do not install when the unit is hot.
The firebox liner is fragile. Handle liners with
care and avoid knocking them on any object.
The Enviro Cara DR comes with a Steel Firebox Liner
installed, which must be removed if a Ceramic Firebox
Liner is to be installed.
1. Remove the glass door as shown in the Maintenance
and Service - Glass Door Removal.
2. Carefully remove the log set.
3. Slide the burner tray back just far enough so the
front edge of the burner does not catch on the
front lip of the firebox. Lift the front of the burner
up and out of the firebox.
Right Clip

Steel Firebox Liner
Left Clip
Right Panel

Figure 65: Steel Firebox Liners Installation.

4. Using a T-20 screwdriver, remove the left and right
Brick Panel Clips
5. Remove the Steel Firebox Liner by pulling the left
side of the panel in towards the center of the unit
then out a little. Repeat for the right side then pull
Rear Panel
the panel completely out.
Left Panel
6. Install the rear ceramic liner by placing it against
the back of the firebox. The top of the liner has
an angled edge, the bottom does not. Note: The
Left Brick Panel Support
Firebox Baffle must be in place for the Firebox
Figure 66: Firebox Liners Installation.
Liners to be installed.
7. While holding the rear ceramic liner from falling forward, install the left and right liners by sliding them
in against the sides of the firebox and up to the rear liner (refer to Figure 66).
8. Attach and tighten the brick panel clips with the screws provided. The side liners hold the rear liner in
place.
9. Re-install the burner (see Maintenance and Service - Burner Removal & Installation), log set (see Secondary
Installation - Log Set Installation), and the door.
38

Trouble Shooting
Problem

Possible Cause

The main burner does not The gas valve may not be on.
ignite when called for.
Thermostat is not calling for
heat.

Solution
• Check that the gas control knob is in the “ON” position.
• Adjust the thermostat several degrees above ambient
temperature.

Problem with gas valve.

• Use a DC voltmeter to measure the voltage across the
TPTH and TP terminals. Main operator voltage: Open
circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for
proper operation.
• If proper control system voltage is present, replace the
gas control.

Defective piezo ignitor.

• Check connections to ignitor.
• If ignitor connections are good but no spark, replace
ignitor.

Broken spark electrode.

• Check for broken ceramic insulation, replace electrode if
broken.

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot, loosen the
screws on the pilot base adjust and tighten.

Problem with thermocouple
circuit.

• Check for proper connection of the thermocouple to the
rear of the valve. If loose, fully tighten.
• Check pilot for full flame impingement around
thermocouple. If flame is too small, check gas pressure,
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater
than 5 mV. If low, replace thermocouple.

Air in gas line (pilot dies while
knob is depressed).

• Bleed line.
• Check gas line pressure.
• Contact dealer.

Burners will not remain lit.

Problem with thermopile
circuit.

• Check gas line pressure .
• Check for flame impingement on thermopile. If low, see
“Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is
switched on.
• Check wiring to thermostat for breaks.

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

Improper vent configuration

• Check vent configuration with manual.

Terminal may be recirculating
flue gases

• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.

Spark will not light the pilot
after repeatedly pressing the
spark ignitor.

Pilot will not remain lit.

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

Flames are burning “dirty” or
sooting

Flame impingement

• Check log positioning.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”

Remote control doesn’t work

Problem with the remote

• One or more of the batteries are dead. See remote
control instructions.

Problem with fireplace

• The on/off switch is turned to OFF.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.

39

Parts List
Reference
Number
1

Part
Number

120°F (49°C) Ceramic Fan Temperature Sensor

EC-001

Thermopile

EC-012

S.I.T. Piezo Igniter

EC-023

Domestic Power Cord - 115V

EC-042

Heyco Strain Relief

EC-044

3

Convection Blower (Fan) - 115V

EC-069

3

Cara Fan Kit

50-1545

4

Fan Controller with Knob - 115V

EF-045

Dual Bulb Door Gasket - 10 ft (3.05m)

50-634

5

S.I.T. Nova Valve Convertible

50-1421

5

S.I.T. Valve Conversion Screw with O-ring

50-1450

5

S.I.T. Valve Conversion Screw Cap

50-1451

5

Cara Valve Tray Assembly

50-1604

6

Cara Firebox Liner - Ceramic

50-1546

7

Cara Log Set & Burner

50-1563

Cara Rock Set & Burner

50-1564

Proflame Programmable Thermostat Remote Control System - NG

50-1570

Proflame Programmable Thermostat Remote Control System - LP

50-1571

Cara Log Set Only

50-1600

Cara Rock Set Only

50-1601

Cara Log Set Burner Only

50-1602

Cara Rock Set Burner Only

50-1603

Cara Conversion Kit LP to NG Convertible

50-1591

Cara Conversion Kit NG to LP Convertible

50-1592

8

Cara Door Assembly

50-1593

8

Cara Glass with Gasket - 14½” x 16¾” (368mm x 425mm)

50-1613

2

7

40

Part Description

Parts List
Reference
Number

Part Description

Part
Number

9

Cara Door Latch Assembly

50-1594

10

Cara Main Orifice NG (PO512-37)

50-1596

10

Cara Main Orifice LPG (PO512-1/16”)

50-1597

11

Cara Flue Outlet Elbow & Gasket

50-1598

11

Cara Flue Outlet Gasket Only

50-1599

12

Cara PSE Pilot Assembly (PSE-C3-505)

50-1605

12

Cara PSE Thermocouple (#019G)

50-1612

13

Cara Cast Insert Rear Vent

50-1606

14

Cara Cast Insert Top Vent

50-1607

15

Cara Cast Stove Top

50-1608

16

Cara Cast Louvers

50-1609

17

Cara Cast Stove Bottom

50-1610

Cara Leveling Legs (Set of 4)

50-1611

18

Cara Vent Restrictor - Set of 4 (50%, 60%, 70%, 75%)

50-1616

19

Pedestal Glass Door Assembly with Magnet Brackets

50-1621

20

Cabinet Side Left and Right

50-1622

21

Cabinet Side Hangers (Set of 4)

50-1623

22

Louver Brackets Left and Right

50-1624

23

Cara Firebox Liner - Steel

50-1627

Cara Owner Manual

50-1630

24

Cara Stove Back

50-1707

25
26

Cara Burner Switch
Cara Switch Box

50-1617
50-1708

26

Cara Pedestal Door Magnet

50-1709

27

Cara Control Panel

50-1710

28

Cara Firebox Baffle

50-1740

41

Parts Diagram

42

Warranty
Sherwood Industries Ltd. is the manufacturer of the VistaFlame line of heating products. At Sherwood
Industries, our commitment to the highest level of quality and customer service is the most important
thing we do. Each VistaFlame stove is built on a tradition of using only the finest materials and is backed
by our Exclusive Lifetime Limited Warranty to the original purchaser. With Enviro, you’re not just buying a
fireplace or stove, you’re buying a company with years of unequalled performance and quality.

Limited Lifetime Warranty:

Under this warranty, Sherwood Industries Ltd. covers the fireplace or stove body and accessories against
defects in materials and workmanship, for part repair or replacement for the first seven (7) years and
limited labour for the first two (2) years to the original purchaser. This Warranty covers: Firebox, Heat
Exchanger, Steel Firebox Panels, Ceramic Logs & Panels, Burner, Ceramic Glass, Pedestals, Panels and
Legs. Please see the exclusions and limitation section below as certain restrictions and exclusions apply
to this warranty.

Limited Two (2) Year Warranty:

Under this warranty, Sherwood Industries Ltd. covers: Gas Assembly, Blower, Blower control, Temperature
Sensors and Wire Harness against defects in materials and workmanship, for part repair or replacement
for the first two (2) years and limited labour for the first two (2) years to the original purchaser. Please see
the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty.

Limited One (1) Year Warranty:

Under this warranty, Sherwood Industries Ltd. covers all exterior surface finishes against defects in
materials and workmanship, for part repair or replacement and limited labour for the first (1) year to
the original purchaser. Please see the exclusions and limitations section below as certain restrictions and
exclusions apply to this warranty.
Here is how our Warranty works
If you have any concerns with your VistaFlame product, please contact the dealer where you purchased
the fireplace or stove. Your dealer shall make all claims under this warranty in writing.

To the Dealer

When filling out a warranty claim, please complete the following information on an official warranty claim
form:
Customer information: Name, address and telephone number of purchaser and date of purchase.
Dealer information: Date of installation, name of installer and dealer, serial number of the appliance,
nature of complaint, defects or malfunction, description and part numbers of any parts replaced.

To the Distributor

Sign and verify that work and information are correct.

Exclusions and Limitations:

1. This Warranty does not cover tarnish, discoloration or wear on the plating or paint.
2. This Warranty excludes wear and tear or breakage caused by cleaning, moving or service on log set
and panels.
3. A qualified installer must install this stove or fireplace. This Limited Warranty covers defects in
materials and workmanship only if the product has been installed in accordance with local building
and fire codes; in their absence, refer to the owner’s manual. If the product is damaged or broken as
a result of any alteration, willful abuse, mishandling, accident, neglect, or misuse of the product, the
Limited Warranty does not apply.

43

Warranty
4. The stove must be operated and maintained at all times in accordance with the instructions in the
Owner’s Manual. If the unit shows signs of neglect or misuse, it is not covered under the terms of
this Warranty policy. Performance problems due to operator error will not be covered by the Limited
Warranty policy.
5. As this is a heating appliance, some changes in colour of surface finishes may occur. This is not a flaw
and as such is not covered under this warranty.
6. Some minor expansion, contraction, or movement of certain parts and resulting noise, is normal and
not a defect and, therefore, is not covered under this Limited Warranty.
7. Misuse includes over-firing. Over-firing this appliance can cause serious damage and will nullify the
Limited Warranty.
8. The Limited Warranty will cover glass thermal breakage only and will not cover misuse of the stove
glass, including but not limited to glass that is struck, has surface contaminates or has had harsh or
abrasive cleaners used on it.
9. This warranty does not cover products made or provided by other manufacturers and used in
conjunction with the operation of this stove without prior authorization from Sherwood Industries
Ltd. The use of such products may nullify the Limited Warranty on this stove. If unsure as to the
extent of this Limited Warranty, contact your authorized VistaFlame dealer before installation.
10. Sherwood Industries Ltd. will not be responsible for inadequate performance caused by environmental
conditions.
11. The Limited Warranty does not cover installation and operational related problems such as use of
downdrafts or spillage caused by environmental conditions. Environmental conditions include but
are not limited to nearby trees, buildings, roof tops, wind, hills, mountains, inadequate venting
or ventilation, excessive offsets, negative air pressures or other influences caused by mechanical
systems such as furnaces, fans, clothes dryers etc.
12. The Limited Warranty is void if:
a) The stove has been operated in atmospheres contaminated by chlorine, fluorine or other damaging
chemicals.
b) The stove is subject to submersion in water or prolonged periods of dampness or condensation.
c) Any damage to the unit, combustion chamber or other components due to water, or weather
damage which is the result of, but not limited to, improper chimney/venting installation.
c) Salt air in coastal areas or high humidity can be corrosive to the finish; these environments can
cause rusting. Damage caused by salt air or high humidity is not covered by the Limited Warranty.
13. Exclusions to the Limited Warranty include: injury, loss of use, damage, failure to function due to
accident, negligence, misuse, improper installation, alteration or adjustment of the manufacturer’s
settings of components, lack of proper and regular maintenance, alteration, or act of God.
14. The Limited Warranty does not cover damage caused to the fireplace or stove while in transit. If this
occurs, do not operate the stove and contact your courier and/or dealer.
15. Limited Warranty does not extend to or include firebox paint, door or glass gaskets with damage
caused by normal wear and tear, or exterior paint discoloration or chipping, worn gaskets, etc.
16. The Limited Warranty does not include damage to the unit caused by abuse, improper installation,
or modification of the unit.
17. Damage to plated surfaces caused by fingerprints, scratches, melted items, or other external scores
and residues left on the plated surfaces from the use of abrasive cleaners or polishes is not covered
in this warranty.
18. The Limited Warranty does not cover tarnish, discoloration or wear on the plated surfaces.
19. The paint on the Metal Brick Liner may peel. This is due to the extreme conditions applied to the paint
during normal usage. It is not a flaw and is not covered under warranty.

44

Warranty
20. Sherwood Industries Ltd. is free of liability for any damages caused by the fireplace or stove, as
well as inconvenience expenses and materials. The Limited Warranty does not cover incidental or
consequential damages.
21. The Limited Warranty does not cover any loss or damage incurred by the use or removal of any
component or apparatus to or from the VistaFlame fireplace or stove without the express written
permission of Sherwood Industries Ltd. and bearing a Sherwood Industries Ltd. label of approval.
22. Any statement or representation of VistaFlame products and their performance contained in
VistaFlame advertising, packaging literature, or printed material is not part of the Limited Warranty.
23. The Limited Warranty is automatically voided if the fireplace or stove’s serial number has been
removed or altered in any way. If the stove is used for commercial purposes, it is excluded from the
Limited Warranty.
24. No dealer, distributor, or similar person has the authority to represent or warrant VistaFlame products
beyond the terms contained within the Limited Warranty. Sherwood Industries Ltd. assumes no
liability for such warranties or representations.
25. Sherwood Industries Ltd. will not cover the cost of the removal or re-installation of the stove, hearth,
facing, mantels, venting or other components.
26. Labour to replace or repair items under this Limited Warranty will be covered per our warranty service
fee reimbursement schedule. Labour rates are set per component and as such total labour costs may
not be covered.
27. Sherwood Industries Ltd. is not liable for freight or labour on any stove replaced in-field and is not
liable for travel costs for service work. In the event of in-home repair work, the customer will pay any
in-home travel fees or service charges required by the Authorized Dealer.
28. At no time will Sherwood Industries Ltd. be liable for any consequential damages which exceed the
purchase price of the unit. Sherwood Industries Ltd. has no obligation to enhance or modify any
stove once manufactured (example: as a stove evolves, field modifications or upgrades will not be
performed).
29. This Limited Warranty is applicable only to the original purchaser and it is non-transferable.
30. This warranty only covers VistaFlame products that are purchased through an authorized VistaFlame
dealer.
31. If for any reason any section of the Limited Warranty is declared invalid, the balance of the warranty
remains in effect and all other clauses shall remain in effect.
32. The Limited Warranty is the only warranty supplied by Sherwood Industries Ltd., the manufacturer
of the stove. All other warranties, whether express or implied, are hereby expressly disclaimed and
purchaser’s recourse is expressly limited to the Limited Warranty.
33. Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either
directly or indirectly, caused by improper usage, operation, installation, servicing or maintenance of
this stove.
34. Sherwood Industries Ltd. reserves the right to make changes without notice. Please complete and
mail the warranty registration card and have the installer fill in the installation data sheet in the back
of the manual for warranty and future reference.
35. Sherwood Industries Ltd. is responsible for stocking parts for a maximum of seven (7) years after
discontinuing the manufacture or incorporation of the item into its products. An exception to this
would be if an OEM supplier is not able to supply a part.

45

Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:

NAME OF DEALER:

_________________________________________

_________________________________________

ADDRESS:

ADDRESS:

_________________________________________

_________________________________________

_________________________________________

_________________________________________

_________________________________________

_________________________________________

PHONE:___________________________________

PHONE:___________________________________

MODEL:___________________________________

NAME OF INSTALLER:

SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________

DATE OF INSTALLATION:___________(dd/mm/yyyy)

� NATURAL GAS (NAT)

_________________________________________

(dd/mm/yyyy)

� PROPANE (LPG)

ADDRESS:
_________________________________________
_________________________________________
_________________________________________

INLET GAS PRESSURE:_________in wc
PHONE:___________________________________

MAIN BURNER ORIFICE:__________# DMS
PILOT ORIFICE #_________OR________in diam.
INSTALLER’S SIGNATURE:
_________________________________________

MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.

6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3

www.enviro.com
June 28, 2010
C-11499

46



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : Yes
Create Date                     : 2010:06:28 13:19:50-07:00
Creator                         : Adobe InDesign CS4 (6.0.4)
Modify Date                     : 2013:11:26 11:16:01-08:00
Trapped                         : False
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2013:11:26 11:16:01-08:00
Creator Tool                    : Adobe InDesign CS4 (6.0.4)
Format                          : application/pdf
Document ID                     : uuid:9ee0507d-542a-4efd-bed1-83334994d34a
Instance ID                     : uuid:9f4a52ad-502e-4042-aab0-dc5ff657fb64
Producer                        : Adobe PDF Library 9.0
Page Count                      : 46
EXIF Metadata provided by EXIF.tools

Navigation menu