C.3 Workshop – Track 2:

Sizing Calculations and
Design Considerations for
LID Treatment Measures
Jill Bicknell, P.E., EOA, Inc.
Santa Clara Valley Urban Runoff Pollution Prevention Program

Presentation Overview
ƒ Determining Water Quality Design Flow
and Volume (“QBMP” and “VBMP”)
ƒ Sizing Bioretention and Flow-Through
Planters
ƒ Sizing Pervious Paving and Infiltration
Trenches
ƒ Sizing Rainwater Harvesting Cisterns
ƒ Sizing Non-LID Components

C.3.d Sizing Criteria
ƒ Volume-based sizing criteria:
• URQM Method - use formula and volume capture
coefficients in “Urban Runoff Quality Management”,
WEF/ASCE MOP No. 23 (1998), pages 175-178

• CASQA BMP Handbook Method - Determine
volume equal to 80% of the annual runoff, using
methodology in Appendix D of the CASQA BMP
Handbook (2003) using local rainfall data
– Sizing curves specific to Santa Clara Valley
provided in Appendix B of C.3 Handbook

Unit Basin Storage Volume
for 80% Capture (inches)
San Jose Rain Gage, 1% Slope

Percent Imperviousness

C.3.d Sizing Criteria
ƒ Flow-based sizing criteria:
• Factored Flood Flow - 10% of the 50-year peak flow
rate, determined using Intensity-Duration-Frequency
curves published by the local flood control agency

• Percentile Rainfall Intensity - Flow of runoff
produced by a rain event equal to two times the 85th
percentile hourly rainfall intensity
– Data for Santa Clara Valley rain gages in Sizing
Worksheets (Appendix B of C.3 Handbook)

• Uniform Intensity - Flow of runoff resulting from
a rain event equal to 0.2 inches per hour intensity

Intensity-Duration-Frequency Curve
(50-Year Return Period)

C.3.d Sizing Criteria
ƒ 85th Percentile Rainfall Intensity Data:
Reference Rain 85th Percentile Design Rainfall
Gages
Hourly Rainfall Intensity (in/hr)*
Intensity (in/hr)
San Jose Airport

0.087

0.17

Palo Alto

0.096

0.19

Morgan Hill

0.12

0.24

*Design rainfall intensity = 2 X 85th percentile hourly rainfall intensity

ƒ By comparison, Uniform Intensity = 0.2 in/hr

C.3.d Sizing Criteria
ƒ Flow-based sizing criteria:
• Simplified Sizing Approach – Variation of Uniform
Intensity Method (0.2 in/hr)
– The surface area of a biotreatment measure is sized to be
4% of the contributing impervious area
– Based on a runoff inflow of 0.2 in/hr (assume equal to the
rainfall intensity), with an infiltration rate through the
biotreatment soil of 5 in/hr
(0.2 in/hr ÷ 5 in/hr = 0.04)
– Conservative approach because does not account for
surface ponding – good for planning purposes

C.3.d Sizing Criteria
ƒ Combination Flow & Volume Design Basis:
• Treatment systems can be sized to treat “at least
80% of total runoff over the life of the project”
• Option 1: Use a continuous simulation hydrologic
model (typically not done for treatment measures)
• Option 2: Show how treatment measure sizing
meets both flow and volume-based criteria
– Used for bioretention and flow-through planters
– Appropriate where drainage area is mostly impervious

Flow- or Volume-Based Sizing
for Treatment Measures?
Table 5-1
Flow and Volume Based Treatment Measure Sizing Criteria
Type of Treatment Measure

LID?

Hydraulic Sizing Criteria

Bioretention area

Yes

Flow-through planter box

Yes

Tree well filter
Infiltration trench
Subsurface infiltration system
Rainwater harvesting and use

Yes
Yes
Yes
Yes

Flow- or volume-based or
combination
Flow- or volume-based or
combination
Flow-based
Volume-based
Volume-based
Volume-based

Media filter
Extended detention basin

No
No

Flow-based
Volume-based

Sizing Criteria Worksheets
ƒ Appendix B of SCVURPPP C.3 Handbook
• Worksheets for determining water quality design
flow and volume
• Figure B-1: Soil Texture and Mean Annual
Precipitation (MAP) Depths
• Figures B-2 – B-7: Unit Basin Storage Volume for
80% Capture (3 gages, 1% and 15% slopes)
• Figure B-8: Intensity-Duration-Frequency Curves for
50-year Return Period (4 gages)

Figure B-1: Soil Texture and Mean
Annual Precipitation (MAP) Depth

Sizing Example #1
ƒ Parking lot in Santa Clara
• Area = 35,000 sq. ft.
(0.80 acres)
• 100% impervious
• Slope = 1%
• Mean annual precipitation
(MAP) = 15 inches

35,000 sq. ft.

ƒ Use the sizing worksheets
to determine QBMP and VBMP
ƒ Answer: VBMP = 1,819 cu. ft.; QBMP = 0.103 cfs

Sizing Bioretention Facilities
ƒ Simplified Sizing Approach
• Surface area is 4% of contributing impervious area
• Does not consider storage in surface ponding area

ƒ Volume Based Approach
• Store VBMP in just surface ponding area
• Store VBMP in ponding area, soil media & drain rock

ƒ Combination Flow and Volume Approach
• Compute both QBMP and VBMP
• Route through facility, allowing ponding

Sizing Bioretention Facilities:
Volume-Based Approach

V1
V2
V3

Sizing Bioretention Facilities:
Volume-Based Approach
Method 1: Store entire volume in surface ponding area
V1

Depth
(ft)

Porosity

Volume per sq. ft.
(cubic feet)

0.5

1.0

0.5

Surface Area = VBMP (cu.ft.) ÷ 0.5 cu.ft./sq.ft.

Sizing Bioretention Facilities:
Volume-Based Approach
Method 2: Store volume in ponding area and media
Depth
(ft)

Porosity

Volume per sq. ft.
(cubic feet)

V1

0.5

1.0

0.5

V2

1.5

0.30

0.45

V3

0.5*

0.40

0.20

Total

1.15

*Depth below bottom of underdrain

Surface Area = VBMP (cu.ft.) ÷ 1.15 cu.ft./sq.ft.

Sizing Bioretention Facilities:
Flow & Volume Approach
ƒ “Hydrograph Approach”
• Runoff is routed through the treatment measure
• Assume rectangular hydrograph that meets both flow and
volume criteria

Sizing Bioretention Facilities:
Flow & Volume Approach

5 in/hr

ƒ Determine VBMP
ƒ Assume constant rainfall intensity of
0.2 in/hr continues throughout the
storm (rectangular hydrograph)
ƒ Calculate the duration of the storm
by dividing the Unit Basin Storage
by the rainfall intensity
ƒ Calculate the volume of runoff that
filters through the biotreatment soil
at a rate of 5 in/hr over the duration
of the storm and the volume that
remains on the surface

Sizing Bioretention Facilities:
Flow & Volume Approach
5 in/hr

ƒ To start the calculation, you have to
assume a surface area “AS” -- use
3% of the contributing impervious
area as a first guess

ƒ Determine volume of treated water “VT” during storm:
VT = AS x 5 in/hr x duration (hrs) x 1 in/12 ft
ƒ Determine volume remaining on the surface “VS”:
VS = VBMP – VT
ƒ Determine depth “D” of ponding on the surface:
D = VS ÷ AS
ƒ Repeat until depth is approximately 6 inches

Sizing Example #1, continued
ƒ Parking lot in Santa Clara
•
•
•
•

Area = 35,000 sq. ft. (0.8 acres)
100% impervious
VBMP = 1,819 cu. ft.
UBS Volume = 0.63 in.

35,000 sq. ft.

ƒ Use the combination flow
and volume sizing worksheet
to determine the bioretention surface area
ƒ Answer: 1,000 sq. ft. (depth of 0.5 ft.)

Sizing Bioretention Facilities:
Comparison of Methods
Example: 35,000 sq. ft. parking lot in Santa Clara
MAP= 15 inches, 100% impervious
VBMP = 1,819 cu. ft. (80% of annual runoff)
Sizing Method

Surface Area (sq. ft.)

Simplified Method (flow-based)

1,400

Volume ponded on surface

3,638

Volume stored in unit (V1+V2+V3)

1,580

Combination flow & volume

1,000

Sizing Pervious Paving and
Infiltration Trenches
ƒ General Principles
• Store the WQD Volume in void
space of stone base/subbase and
infiltrate into subgrade
• Surface allows water to infiltrate at a
high rate
• Any underdrains must be placed
above the void space needed to
store and infiltrate the WQD volume

Sizing Pervious Paving and
Infiltration Trenches
ƒ Pervious Paving
• May be self-treating area or self-retaining area (accept
runoff from other areas)
• Can only be considered a “pervious area” if stone
base/subbase sized to store the WQD volume
• Can work where native soils have low infiltration rates
(stored water depths are relatively small)
• Surface area is usually predetermined
• Base and subbase thickness usually determined by
expected traffic load and saturated soil strength
• Slope should be ≤ 1% (or use cutoff trenches)

Pervious Paving
Typical Section
Paving surface
Bedding No. 8 stone
4 in.

Thickness
varies

Base No. 57 stone
Subbase No. 2 stone

ƒBase and subbase layers available for water storage
ƒBoth typically have 40% void space

Pervious Paving
ƒ Approach to Sizing Pervious Paving
• Self-Treating
– Check the depth of the WQD volume in base/subbase:
UBS volume (in.) ÷ 0.40 = Depth (in.)
Example: UBS volume = 1.0 in., depth = 2.5 in.
(Minimum depth for vehicular traffic is 10 in.)
– Check the time required for stored water to drain:
UBS Vol. (in.) ÷ Infiltration rate (in/hr) = Drain time (hrs)
( recommend < 48 hrs)

Pervious Paving
ƒ Approach to Sizing Pervious Paving
• Self-Retaining
– Check the depth of the WQD volume in base/subbase:
UBS volume (in.) ÷ 0.40 = Depth (in.)
Example: UBS volume = 1.0 in., depth = 2.5 in.
(Minimum depth for vehicular traffic is 10 in.)
– Check the time required for stored water to drain:
UBS Vol. (in.) ÷ Infiltration rate (in/hr) = Drain time (hrs)
( recommend < 48 hrs)

Sizing Rainwater Harvesting
Cisterns
ƒ Rainwater Harvesting and Use
• Types of Demands
– Irrigation
– Toilet flushing
– Other non-potable

•

Volume based sized criteria in C.3.d is 80%
capture of the annual runoff

•

Key concept is drawdown time

•

Barriers: lack of plumbing codes, treatment,
recycled water preference

Storage values are
per one acre of
impervious surface

Estimate Actual Demand
Daily Use Rates for Toilets and Urinals1
Land Use Type

User Unit

User Unit
Factor2

Daily Use/Unit
(gal/day/unit)

Residential

Resident

2.9 residents per
dwelling unit

8.6

Office or Retail

Employee
(non-visitor)

200 SF per
employee

6.9

Schools

Employee
(not including
students)

50 SF per
employee

33.9

1References:

CCCWP Stormwater C.3 Guidebook, 6th edition, 2012; BASMAA
LID Feasibility Report, 2011; California Plumbing Code, 2010.
2Use project-specific data if available

Example:
2-story Office Building
3,000 SF

10,000 SF
(Interior floor area
= 20,000 SF)
4,000 SF

Screening Worksheet Results
ƒ Potential rainwater capture area = area of one
building roof = 10,000 SF
ƒ Convert to acres:
10,000 SF ÷ 43,560 SF/acre = 0.23 acres
ƒ Demand for commercial building:
Interior floor area = 20,000 SF
ƒ Minimum floor area to meet toilet flushing demand =
70,000 SF per acre of impervious surface
ƒ Minimum floor area for this project to meet demand =
70,000 SF/ac X 0.23 acres = 16,100 SF
ƒ 20,000 SF > 16,100 SF B Building will have minimum
toilet flushing demand

Determine Building Toilet
Flushing Demand
ƒ Building interior floor area = 20,000 SF
ƒ Estimate no. of employees:
• 200,000 SF ÷ 200 SF/employee = 100 employees
• 100 employees × 6.9 gpd/employee = 690 gpd

ƒ Convert to equivalent demand per impervious acre
(to allow use of sizing curves):
• 10,000 SF roof area ÷ 43,560 SF/ac = 0.23 ac.
• 690 gpd ÷ 0.23 = 3,000 gpd per impervious acre

Determine Required Cistern Size
ƒ From sizing curves, find right combination of
drawdown time, tank size and required demand:
• 480-hr (20-day) drawdown B 49,000 gallon tank B 2,450 gpd
• 360-hr (15-day) drawdown B 40,000 gallon tank B 2,667 gpd
• 240-hr (10-day) drawdown B 32,000 gallon tank B 3,200 gpd
• 288-hr (12-day) drawdown B 36,000 gallon tank B 3,000 gpd √

ƒ Adjust tank size back to actual impervious area:
• 36,000-gallon tank per 1 acre impervious area
• 36,000 × 0.23 acres = 8,300-gallon

tank

Sizing Non-LID Components
Media Filters (cartridge type)
ƒ Flow-based Treatment Measure
ƒ Determine QBMP
ƒ From manufacturer’s specifications,
determine the design flow rate per
cartridge
ƒ Divide QBMP by the cartridge flow
rate to calculate the number of
cartridges required (round up)

Sizing Non-LID Components
High Flow Rate Tree Box Filters
ƒ Flow-based Treatment Measure
ƒ Determine QBMP
ƒ From manufacturer’s specifications,
determine the appropriate size of
unit or combination of units
ƒ A tree box filter that uses biotreatment soil can be sized like
a bioretention area or flow-through
planter

Sizing Non-LID Components
Detention Basin
ƒVolume-based Treatment Measure (can only be
used in treatment train)
ƒDetermine VBMP
ƒDesign outlet for 48-hour
detention time
ƒIf sizing for hydromodification
management, use Bay Area
Hydrology Model to determine
size to meet HM standards

??? Questions ???
Contact Information:
Jill Bicknell
408-720-8811, X 1
jcbicknell@eoainc.com
www.scvurppp.org



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Format                          : application/pdf
Title                           : Microsoft PowerPoint - C3 Workshop_Track 2_Sizing Calcs_6-5-12.ppt [Compatibility Mode]
Creator                         : qlu
Create Date                     : 2012:07:16 15:37:29-07:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2012:07:16 15:37:29-07:00
Producer                        : Acrobat Distiller 8.3.1 (Windows)
Document ID                     : uuid:18e7bd49-758b-4e71-b18d-24d11a989be3
Instance ID                     : uuid:8804ce0a-69d4-403c-8871-0dc7abf70570
Page Count                      : 38
Author                          : qlu
EXIF Metadata provided by EXIF.tools

Navigation menu