MJ15 Megger Cable Fault Locators & Ers

User Manual: MJ15

Open the PDF directly: View PDF PDF.
Page Count: 21

DownloadMJ15 Megger Cable Fault Locators & Ers
Open PDF In BrowserView PDF
Power and industrial test equipment.
More than 20 new products
Safer working
protect yourself with CAT IV 5kV and 10kV testers
At last
a complete transformer test system
Forms based
software that works the way you do
Any time, any place, anywhere
to your specification –
The new van based
cable fault location system
Turn that noise down
New earth ground testers
with switchable frequencies

THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
The word ‘Megger’ is a registered trademark

WWW.MEGGER.COM

WWW.CABLEJOINTS.CO.UK

New products
CFL40A
Van mountable cable fault locator
The TDR and all the control functions have been installed in a newly designed remote panel,
connected to the HV unit by a flexible umbilical cable for installation in to a suitable vehicle by
the customer, or Megger.

Delta3000
10 kV automated insulation dissipation factor test set
Fully automatic 10 kV insulation dissipation factor test set for condition assessment of
electrical insulation in high voltage apparatus with PowerDB OnBoard for automatically
generating test reports.

TTR300 series
Three-phase transformer turns ratio test set
Offering stand-alone or remote-control operation to accurately measures ratio, phase
deviation and excitation current. TTR330 has PowerDB OnBoard for automatically generating
test reports.

MTO
Transformer ohmmeter
MTO series is a line-operated, field-portable instrument designed specifically to measure the
d.c. resistance of all types of magnetic windings, mainly in all types of transformer windings.

MCT1600
Current transformer test set
By performing a range of test automatically, including ratio, saturation knee point, burden,
polarity and phase deviation, MCT1600 offers huge productivity gains over conventional CT
testers reducing the cost of commissioning transformers.

DET4T2 series
Earth ground resistance testers
DET4T2 series of earth testers now offers user selectable frequency and extended measurement
ranges. To make even more attractive it is available in a number of different kits.

PA9 Wireless
Power quality analyser
Simultaneously recording power quality and power flow information PA9 Wireless
incorporates a wireless modem to allow a remote user to configure the unit, to view and
download data.

S1/2, MIT5/2 and MIT10/2 series

Contents
Taking the lead for safety!
As an essential aid to safer testing, Megger has
introduced a new and comprehensive family of test
leads for use with its insulation resistance testers.
Three metres long, and made from ultra-flexible
silicone-insulated cable to ensure long life, the new
leads cover virtually all requirements related to
insulation resistance testing at up to 10 kV.
For use in applications where the space for making
test connections is not restricted, the test leads are
fitted with large insulated clips. They have a
maximum jaw capacity of 34 mm, and an insulation
rating of 10 kV.
For applications where space is more restricted, but a
useful level of protection from the output of the
insulation tester is nevertheless required, the range
includes leads that incorporate medium-sized
insulated clips. With an insulation rating of 6 kV,
these leads have a maximum capacity of 18 mm.
In some instances, such as motor terminal boxes,
space for connecting the test leads is so restricted
that insulated clips cannot be used. For these
applications, Megger offers test leads with
uninsulated clips that have a maximum capacity
of 18 mm.
Leads with large, medium and uninsulated clips are
supplied in colour-coded sets of three – positive,
negative and guard.
Also included in Megger’s new test lead family are
leads designed to allow insulation resistance testing
to be carried out more safely on low voltage control
circuits in the vicinity of high voltage equipment.
With insulation rated at 1 kV, these leads are supplied
in sets of two, and incorporate probe-type tips with
push-on crocodile-clip adaptors.

5 kV and 10 kV insulation testers
Megger has up-rated the safety of its 5 kV and 10 kV insulation resistance testers to CATIV
600V and changed the test leads it supplies in the kit.

1965: First low-voltage insulation power factor set,
weighing less than 6.5 kg

Advanced manufacturing technology

1980: First semi-automatic 2.5 kV and 10 kV insulation
power factor test set

Megger believes that the best way to secure good quality products and intellectual property is through excellence in
engineering and its production facilities.

1990: First fully automatic 10 kV insulation power factor
test set

Advanced manufacturing technology including automated wave-solder machinery and robotic surface mount
component technology help keep costs down and quality up.
The words Megger, Programma, PowerDB, DLRO, BITE, STATES, Microsoft, Bluetooth, MS Word and Access are
trademarks or registered trademarks of their respected owners. All other trademarks acknowledged.

2

NEW PRODUCTS

2

Insulation test

4

Insulation tester guide

6

CATIII and CATIV hand-held insulation testers

7

High voltage test equipment

8

Tan delta

8

Capacitance dissipation factor and tan delta

9

Power quality

10

Automatic protection test

12

Primary injection test

14

Secondary injection test

15

Cable fault location

16

Time domain reflectometry

18

Cable trace and voltage detection

19

Transformer test

20

Transformer insulating oil testing

24

Low resistance test

26

Battery test

28

Earth ground resistance test

30

Multimeters and clampmeters

32

Hand-held electrical test tools

33

Watthour meter test

34

CATIV testing

35

Test and measurement software

36

Index

38

A history of firsts
1903: Megger trademark registered. It is jealously guarded
by the company.

Key processes and expertise are kept in-house, and engineering teams are located on-site at all the company’s
factories.

New products

2007: First portable cable fault locator with up to 2000
Joules in four ranges.
2007: Megger merges with Programma AB, a major test
and measurement products manufacturer.

Printed circuit boards are purpose designed by Megger. Components are
supplied from reel-based automatic feeders

CONTENTS

3

CATIV insulation test –
keeps you safe

Insulation test
Why CATIV?

Regular insulation resistance testing is one of the most cost effective methods of identifying
aging in electrical equipment, and with over 60% of equipment failures being ascribed to
insulation breakdown, it is a key area to monitor for high levels of customer satisfaction.

MIT520/2

New

MIT1020/2

New

5 kV diagnostic insulation resistance tester

10 kV diagnostic insulation resistance tester

MIT520/2, now with CATIV safety, offers the ability to test
insulation to 5 kV. It allows automatic IR, PI, DAR, SV and DD
tests. Measuring up to 15 TΩ means the MIT520/2 can detect
insulation deterioration earlier than other testers. Results
storage and download give you full diagnostic information
for later analysis. MIT520/2 can be powered using either
mains or its on-board rechargeable battery, now with
improved battery-life management.

MIT1020/2 gives you the ability to test insulation to 10 kV,
giving greater flexibility, and also complies with
IEEE43:2000. With CATIV safety and measuring up to 35 TΩ,
it allows automatic IR, PI, DAR, SV and DD tests. Results
storage and download give full diagnostic information for
later analysis. MIT1020/2 can be powered using either
mains or its on-board rechargeable battery
with improved battery-life
management.

S1-552/2

A small fault becomes a big problem on
Category IV high energy unfused supplies!

MIT510/2

New

5 kV insulation resistance tester
With CATIV safety, MIT510/2 is an easy to operate
insulation resistance tester that is very tough.
Measuring up to 15 TΩ, it allows automatic IR.
The built-in timer and high test ranges allow simple
and quick evaluation of the condition of the
insulation under test. The MIT510/2
is mains or battery powered,
now with improved
battery-life
management.

With a high output current 5 mA for fast charging of
capacitive loads the S1- 552/2 offers variable test voltages
from 50 to 5000 V. Measuring up to 15 TΩ, it allows
automatic IR, PI, DAR, SV and DD tests. The S1-552/2 is safety
rated at CATIV and can be powered using both mains and its
on-board re-chargeable battery, now with improved batterylife management.

Offering 4 mA noise rejection and software filtering the S1554/2 leads its class. It also offers variable test voltages from

New

A choice of 5 kV or 10 kV
insulation resistance
testers to suit needs and
budgets.

S1-5010

S1-1054/2

10 kV insulation resistance testers with high
noise rejection

With a high 5 mA output current for fast charging of
capacitive loads, the S1-1052/2 offers variable test voltages
from 50 V to 10,000 V. Measuring up to 35 TΩ, it allows
automatic IR, PI, DAR, SV and DD tests. It can be powered
using both mains and on-board re-chargeable battery with
improved battery life management. S1-1050/2 has a CATIV
safety rating.

With a high 5 mA output current S1-1054/2 offer variable test
voltages from 50 V to 10,000 V. Safety rated at CATIV and
measuring up to 35 TΩ, it allows automatic IR, PI, DAR, SV
and DD tests. It can be powered using both mains and onboard re-chargeable battery with improved battery-life
management. S1-1054/2 offers 4 mA noise rejection and
software noise filtering, and class leading performance.

INSULATION TEST

5 kV graphical
insulation resistance
tester

New

High current 10 kV insulation resistance
testers

4

CATEGORY III

TRANSFORMER

CATEGORY IV
ISOLATING
DEVICE

OUTLET
DISTRIBUTION
BOARD

The solution is simple – design the instruments
with protection and internal clearances that are
large enough to prevent transients from
establishing an arc and along with appropriate
protection devices. Guidance to this is given in
IEC61010 in order to comply with category
ratings defined in IEC60664.

5 kV insulation resistance tester with high
noise rejection

S1-1052/2

CATEGORY II

Often, that supply can deliver 1000 A or more
until the breaker or other protective device
operates. In that time, the amount of energy
liberated is easily enough to start a fire or even
cause an explosion. If the arc is within a test
instrument there is a high probability that you
will be injured or worse!

New

50 to 5000 V. Measuring up to 15 TΩ it allows automatic IR,
PI, DAR, SV and DD tests. The S1-554/2 is safety rated at CATIV
and can be powered using both mains and its on-board rechargeable battery, now with improved battery-life
management.

CATEGORY I
DISTRIBUTION LINES

The problem is that it may initiate an arc and
this arc then presents a low impedance path for
current from the mains supply.

New

High current 5 kV insulation resistance tester

S1-554/2

A distant lightning strike can produce a transient
of several kV on the supply. The transient may
only lasts for a few tens of microseconds and is
likely to do little damage.

S1-5010 is heavy duty and
mains or battery powered

The S1-5010 is a heavyduty mains/battery
powered instrument.
Offering 5 mA high
power testing, auto test,
graphical
display and results
storage, it is a stand-alone
instrument for maximum
diagnostic information and
predictive maintenance.

In practice, transients are damped quite quickly
as they pass through a typical distribution
system. As you can see from the diagram CATIV is
recommended for use outside and to the
consumer unit. Specify Megger CATIV testers to
make sure you are safe and secure. Not only
could they save your life, but they are
economical too.
Using an instrument with a higher installation
category rating does not alone create a safer
working environment. You should always follow
correct work practices to keep you and others safe.

INSULATION TEST

5

Insulation test

CATIII and CATIV hand held
insulation testers

BM15

MJ15

MIT200 series

Basic 5 kV insulation resistance tester

Basic 5 kV insulation resistance tester

Light-weight insulation and continuity tester

With four test voltages and an analogue display the BM15 is
a tough, easy-to-use “go / no go” tester. With a test current
of 1 mA and a maximum reading of 20 GΩ it can operate on
dry cells or rechargeable batteries.

MJ15 offers a unique combination of hand-cranked generator
and battery to give a “go / no go” tester with four test
voltages and an analogue display. The MJ15 is a tough and
easy to use and offers a test current of 1 mA and a maximum
reading of 20 GΩ

The MIT200 series are CATIII 600 V tested offering 250, 500
and 1000 V test voltages. They will find applications in
electrical contracting, both on domestic and industrial
systems, as well as site maintenance and service departments.

MIT300 series

Their small size and lightness make them ideal for those
engineers that need to carry them for extended periods.

MIT400 series

Insulation resistance and continuity testers
for electricians
Designed to be tough enough to soak up the treatment
meted out to testers on site the MIT300 series offer CATIV
300 V safety with flexibility. The MIT300 comes in five versions
from a basic two-test voltages digital tester to a downloading
three-test voltages tester. All the digital testers include an
analogue arc display.

New

The MIT300A is a moving coil analogue tester offering 250,
500 and 1000 V test voltages.

Insulation resistance and continuity
testers for industrial maintenance

BM15 is battery
powered, and very easy to use

MIT400 series testers offer CATIV 600 V safety in a
convenient easy to hold format. MIT400
series are true diagnostic instruments
measuring insulation resistance up
to 200 GΩ. They measure insulation
deterioration long before most
testers even offer a reading.

MJ15 has an analogue display and offers
hand crank or battery power

5 kV and 10 kV insulation tester guide

With functions such as TRMS voltage
measurement, polarisation index (PI),
dielectric absorption ratio (DAR),
capacitance measurement and high
insulation resistance ranges, makes the
MIT400 is suitable for the testing required in
manufacturing, panel building, railways,
motors, cable inspection, street lighting,
avionics as well as the electrical supply industry

Insulation resistance testing
Model
Display

Graphical
Analogue
Analogue/Digital
Mains power
Rechargeable
Hand crank
Dry cell
10.0 kV
5.0 kV
2.5 kV
1.0 kV
500 V
250 V
25 V steps 50 V to 5 kV
10 V steps 50 V to 1 kV then
25 V steps 1 kV to max
test voltage
Max reading
Min reading
Voltage
Capacitance
Leakage current
Polarisation Index
Dielectric absorption ratio
Step Voltage
Dielectric Discharge
Timer control
Timer display
4 mA max noise rejection
2 mA max noise rejection
5 mA test current
3 mA test current
2 mA test current
1 mA test current
USB output
RS232 output
RS232 control
PowerDB lite
PowerDB full version

Power Supply

Test Voltage

Measurements

Test Types

Other Features

Software

■ feature

6

BM15

MJ15

■

■


■


■
■

■
■
■
■

■
■
■
■

20 GΩ
100 kΩ
■

20 GΩ
100 kΩ
■

MIT510

MIT520

S1-552

S1-554

MIT1020

S1-1052

S1-1054

S1-5010
■

■
■
■

■
■
■

■
■
■

■
■
■

■
■
■

■
■
■

■
■
■

■
■
■

■
■
■
■
■

15 GΩ
10 kΩ
■
■
■

■

■
■

■
■
■
■
■

■
■
■
■
■
■

■
■
■
■
■
■

■
15 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■

■
15 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■

■
15 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■
■

■

■
■

■
■
■
■
■
■
■

■
■
■
■
■
■
■

■
■
■
■
■
■
■

■
35 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■

■
35 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■

■
35 TΩ
10 kΩ
■
■
■
■
■
■
■
■
■
■

■

■
■

■

■

■

■
■
■
■
■

5 TΩ
10 kΩ
■
■
■
■
■
■
■
■

■


■


■


■


■


Insulation resistance and continuity
testers for telecommunications

New

Insulation resistance and continuity testers
for special applications

MIT480 series testers offer 50 and 100 V test voltages, ideal
for the telecoms industry. They all provide CATIV 600 V safety.
MIT480 series also offers frequency, capacitance and distance
by capacitance functions and a 75 V live circuit inhibit feature
to match the special needs of telecoms engineers.

Based on the class leading MIT400 the MIT40X allows the user
to set the test voltage anywhere between 10 V and
100 V, depending on the application. It still offers CATIV
600 V safety and tests insulation resistance up to 20 GΩ.

MIT480 series is a true diagnostic instrument measuring
insulation resistance up to 200 GΩ. They measure insulation
deterioration long before most testers even offer a reading.
Light-weight
insulation and
continuity testers
MIT200
500 V insulation test

MIT210 MIT220


1000 V insulation test


250 V insulation test

Industrial maintenance
insulation and continuity
testers

Electrician’s insulation and
continuity testers
MIT230

MIT300 MIT310 MIT310A



MIT320 MIT330

MIT400 MIT410

MIT420

MIT481

MIT485



















MIT430 MIT40X



































































10 V to 100 V in 1 V steps
1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ 1000 MΩ

Continuity 0.01 to 200 Ω
Continuity 0.01 to 100 Ω
Live circuit warning

MIT480



50 V and 100 V insulation test
Resistance to

Telecommunications
insulation and continuity
testers



















25 V

25 V

25 V

25 V

25 V

25 V

25 V

25 V

25 V

20 GΩ

100 GΩ

200 GΩ

200 GΩ

20GΩ

100 GΩ

200 GΩ

200 GΩ

















50 V

50 V

75 V

50 V

50 V

75 V

75 V











■

Dielectric absorption rate DAR











■

Capacitance measurement

■
■
■


MIT40X

50 V

■
■
■

New

Polarization Index PI

■

■
■

MIT480 series

Frequency measurement

40-400 Hz 40-400 Hz 40-400 Hz


40-400 Hz 40-400 Hz



Capacitance by distance
Data storage



USB downloading







FREE calibration certificate










Bluetooth downloading
Safety




CATIII
600 V

CATIII
600 V

CATIII
600 V

CATIII
600 V

CATIV
300 V

CATIV
300 V





CATIV
300 V



CATIV
300 V

CATIV
300 V

CATIV
600 V

CATIV
600 V

CATIV
600 V

CATIV
600 V

CATIV
600 V

CATIV
600 V

CATIV
600 V

CATIV
600 V





















option

INSULATION TEST

INSULATION TEST

7

High voltage test equipment

Capacitance dissipation factor
and tan delta

681100 series

Delta 3000

50/100 kV a.c. dielectric test sets

10 kV automated insulation dissipation
factor test set

681100 series a.c. dielectric test sets are a.c. high-voltage
sources for testing electrical insulation. The standard system
includes a control/instrument cabinet, a high-voltage
transformer assembly and all necessary cables including
ground and input power.

A fully automatic 10 kV insulation dissipation factor test set
designed for condition assessment of electrical insulation in
high voltage apparatus such as transformers, bushings, circuit
breakers, cables, lightning arresters and rotating machinery.
In addition to performing insulation power factor tests, it can
be used for measuring the excitation current of transformer
windings.

220000 series
70 kV, 120 kV and 160 kV d.c. dielectric
test set
220000 series provides a dependable, safe, lightweight and
portable d.c. voltage source for testing the quality and
integrity of electrical power cables, cable installations,
motors, switchgear, insulators, transformers and capacitors.

220000 series has advanced
performance with long-term
reliability provided by filtered halfwave rectification

High voltage test equipment
Model
d.c. test sets
220005
220015
220070
220123
220164
a.c. test sets
230315
230415
230425
686100
681100
686100
681100

5 kV
15 kV
70 kV
120 kV
160 kV

5 kV

d.c. output
Continuous
Short circuit
5 mA
5 mA
2 mA
5 mA
3.5 mA
5 mA
2.5 mA
5 mA
2 mA
5 mA

–
Non-resonant
Resonant
Non-resonant
Resonant

New

17 mA

Tan delta

a.c. output
Continuous
Short circuit

3 kV
4 kV
4 kV
50/100
50/100
50/100
50/100

kV
kV
kV
kV

3 mA
80/150 mA
80/150 mA
40/75 mA
40/75 mA

DELTA 3000 allows for direct data feed into PowerDB for
automatically generating test reports. All data can be saved
in an XML file with all historical data. If a user also has a full
license of PowerDB, test sheets can be modified and
downloaded to the instrument. The unit’s intuitive, easy-touse interface allows the user to configure test sheets and
pop-up test procedures. A QWERTY keyboard makes it simple
for entering all nameplate and location information. The unit
has two USB ports. Measurements are performed
automatically, and results are displayed on a full VGA colour
display. Measured quantities include voltage, current, power

(loss), dissipation factor and capacitance. The operator has
the option of correcting the current and loss readings to 2.5
kV or 10 kV equivalents. Information can be downloaded
directly to a PC or printer. An optional 10 nF TTR capacitor in
addition to two HV reference capacitors are also available.

670000 series

CB100

2.5 and 12 kV semi-automatic capacitance
and tanδ test bridge

Low voltage capacitance and tanδ test bridge

These instruments feature automatic balancing of dissipation
factor and manual balancing of capacitance and interference
suppression, allowing use in energised HV substations. There
is direct readout of tan delta, capacitance and watts
dissipated.

Lightweight and low-cost the CB100 is ideal for workshop
use. Manually balanced it offers direct readout of tan delta
and capacitance, overcoming interference by using a test
frequency of 80 Hz or 100 Hz.

12 mA
12 mA
12.6 mA

670000 comes complete
with interference
suppression circuits for
testing in high-voltage
switchyards, automatic
balancing of dissipation
factor, and direct
readout of capacitance,
dissipation factor and
watts dissipated

CB100 lets you read
capacitance and
dissipation factor directly
from the instrument – no
calculation required

Delta 2000
10 kV fully automated capacitance and tanδ
test bridge
The ultimate instrument for dissipation factor testing,
DELTA2000 offers automatic measurement of dissipation
factor, capacitance, watts loss and leakage current. It is ideal
for the assessment of insulation in high voltage apparatus
such as transformers, bushings, circuit breakers, cables, surge
arresters and rotating machinery.

Delta 2000 is ideal for tan delta
testing on transformers

8

HIGH VOLTAGE TEST EQUIPMENT

Insulation testing
Model
Output voltage
Capacitance measuring range in µF
Dissipation factor
UST test
GST test
GST guarded test
Watts loss measurement
Current measurement
Range extension
Interference suppression
Balancing
Data storage
Bar code reader
Comlink PC software
RS232 printer output
PowerDB Onboard
USB communications

Delta 3000
12 kV
0-0.11 or
0-1 with inductor
0-90%
■
■
■
■
■
■
Automatic
Automatic
■
■
■
■
■
■

Delta 2000
12 kV
0-0.11 or
0-1 with inductor
0-90%
■
■
■
■
■
■
Automatic
Automatic
■
■
■
■

CB100
28 V
0-1.2

670025
2.5 kV
0-0.22

670065
12 kV
0-0.22

0-30%
■
■
■
■

0-200%
■
■
■
■
■

0-200%
■
■
■
■
■

Manual
Manual

Manual
Manual

■
Inherent
Manual

670070
12 kV
0-0.22 or
0-1 with inductor
0-200%
■
■
■
■
■
■
Manual
Manual

CAPACITANCE DISSIPATION FACTOR AND TAN DELTA

9

Power quality
Versatility is vital for measuring power quality.
There is a danger that by specifying an
instrument that only performs a limited number
of tests, you will need to purchase extra
equipment later. It is safest to specify a power
quality instrument that can make measurement of
frequency, flicker, dip/swell, interruption,
unbalance, and harmonics for these applications:
■ Lamp flicker measurements and recordings
■ Energy audits and forecasting
■ Capacitor bank sizing
■ Load balancing
■ Power factor surveys

SLM8 (not CE marked)

PA9 Wireless

8 channel recording volt-ammeter

Power Quality Analyser

The SLM8 is a low cost, 8 channel paperless recording voltammeter used for measuring and recording the true RMS
values of up to four voltage channels and four current
channels. It is the ideal investigative tool for utility
trouble-shooters, service
investigation groups,
meter shop technicians
and facility managers to
identify and document
the presence of threephase and single-phase
voltage problems using
associated load current
information to locate the
source.

The new Megger PA9 Wireless is the latest
innovation of the successful PA-9 Power Quality
Analyser platform. It simultaneously records power
quality and power flow information.

■ Before/after studies
■ Load profiling
■ Substation monitoring

MDP series

■ Comprehensive power quality investigations

Distribution profiler

■ Billing verification
■ Motor, generator and transformer inrush
current studies
■ Harmonic surveys, analysis, and filter design

MetReport
Power quality analysis software
MetReport is an extremely
powerful, fully functional,
and stand-alone report
generation tool for the
Megger PA-9Plus power
quality analysers. Its primary
purpose is to dramatically
improve and extend
reporting capabilities.
In today’s economy, time is
money. Power and power quality professionals sometimes
spend countless hours every year creating customized reports
supporting their analysis studies. MetReport automates this
tedious task while improving the accuracy and reliability of
the entire reporting process.
MetReport utilizes data files obtained from the PA-9 and
PA-9Plus to rapidly produce completely customizable reports
targeted to your particular applications and requirements.
Some examples include: Power quality studies, harmonics
analysis, power factor and energy consultation, tolerance
curve studies (CBEMA/ITIC, SEMI F47, User Defined), auto data
analysis pass/fail reports, EN50160 compliance, and IEEE/IEC
Flicker. The key to quickly learning and using MetReport is
the integrated wizard function. This wizard effortlessly takes
you through the entire report creation, customization, and
generation process. Several sample report templates are
included for review, and may be modified to meet your
specific needs.
All reports are output as standard Microsoft Word
documents.
10

POWER QUALITY

Power quality

With virtually unlimited data
recording capacity, easy
installation and lightweight
durable construction, MDP
gives power utilities a
convenient and accurate way
of acquiring information
needed to monitor power flow
on feeders and overhead lines.
MDP1 records actual current
RMS magnitude up to 1000 A,
with an additional 200 A overrange. MDP2 adds recording of
relative voltage RMS
magnitude together with
power and power factor.
The MDP3 provides facilities
for waveform capture as well
as the recording harmonics
and THD.

PMM-1

Power multimeter
multi-function measuring
instrument with simultaneous
measurement and display of all
three-phase system parameters

power, energy, events, flicker (PST/PLT), THD, TDD, individual
harmonics, and frequency. Operating in real-time, it graphically
displays harmonic content, power and source direction. It has
remote communications and alarm capabilities. PA9
wireless includes enhanced MEGPA9IEC software.

PA9 Wireless incorporates newly enhanced
key features including a wireless modem
for remote communication, a full 12 MB
of nonvolatile internal memory and
standard auxiliary power input
capabilities as well as an optional external
flash card for added memory.
The unique wireless modem allows the user to
configure the unit remotely, view real-time data
via the remote screen, and preview all recorded
data without downloading the data. The wireless
modem allows for remote analysis of data, remote data
retrieval capabilities and remote unit configuration. The unit
intelligently downloads, previews and retrieves only the
information of interest. It trends voltage, current, imbalance,

PA9 Wireless Starter Kit, shown
here, includes 4 voltage cables
and 3 raintight CTs.

PA9plus
Power quality analyser
The PA9plus has enhanced standard key features
including a fast digital signal processor to support
future evolving features and capabilities, a full 12
MB of internal, non-volatile memory and
incorporated auxiliary power input capabilities.
The product offers testing to the relevant
standards (EN50160, IEC61000 series,
IEEE1159, IEEE519).
Data can be downloaded from PA9 without
interrupting the instrument recording events.
The optional removable memory allows
internally recorded data to be copied to an
external compact flash card using the same
technology you see with most digital cameras.
Without a computer on site, data can be copied,
manually or unattended, from the instrument to
external memory cards, increasing the effective instrument
memory storage to the size of the memory card used. You can
program new configuration setups in the same, simple manner.

3 phase power measurement meter
Measures a.c. / d.c. voltage, a.c. primary and secondary
current, power, power factor, reactive power, phase angle and
frequency of single and three phase electrical systems with
extreme accuracy. Integral solid state timer for continuity and
voltage sensing and harmonic measurement up to 49th
harmonic. For detailed waveform analysis a high-speed
capture function allow 20
measurements per
second. An RS232
data port allows
bi-directional
communication.

New

On-site trending, analysis and data
retrieval without a computer and
intelligent downloading

Power Quality
Model
Voltage range

Crest factor
Current
Voltage/Current connection

Frequency
Power from phase A
Trigger events

Communications

■ feature

20 V to 600 V
ac or dc
True RMS through 63rd harmonic
1500 V peak
Current 1.4 of full scale at peak
Resolution 0.1% of full scale
Accuracy ± 0.25% of reading ± 0.05% of range
V = 4 colour coded pairs of safety banana jacks
I = 5 Amp miniature circular connector
Power provided for flexible CTs
Fundamental 20 Hz to 70 Hz autoranging
90 V to 600 V ac, 100 V to 600 V dc
RMS level current or voltage
Transient level current or voltage
Harmonic content current or voltage
RS232
Compact flash card
Wireless modem
Wired modem

PA9+
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■


PA9+ wireless
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■


option

POWER QUALITY

11

Automatic protection test

Automatic protection test

now with ‘Click-on-Fault’, GPS and current adaptor options!
The MPRT is already recognized around the world as a premier protective relay test
instrument. It is currently in use at hundreds of electric utilities, generating
facilities, industrial plants, OEMs and testing service companies in over 60 different
countries worldwide.

MPRT now offers click-onfault and RIO file import
capability

MPRT
Protective relay test system
Performance Proven

Click-on-Fault – gives you the ability to define the type of
operating characteristic, then “click on” the characteristic to
test the relay.
Binary Search – used with Click-on-Fault, you can easily define
maximum values and type of fault or characteristics such as
constant current, constant voltage or source impedance.
RIO File Import – allows you to import an existing RIO file into
the click-on-fault diagram and then proceed with the test.

What makes MPRT a World Class test
instrument?
There are three distinctive components of the Megger MPRT
Relay Test System that set it apart from any other. These are:

Modbus Communications – automates communication with
various relays via Modbus protocol.

By using multiple VI-Gens, the system can deliver up to four
voltages and four currents or with convertible voltage
channels eight currents.

MGTR is a small, lightweight,
field portable, GPS satellite
receiver system specifically
designed to perform end-toend tests of line protection
schemes, with Megger MPRT
relay test systems. MGTR
provides a precise

Programmed Output Pulse
(POP), with 100 nanoseconds
of resolution. This output
pulse provides a trigger
synchronization of two or
more MPRT test systems to
less than ±1 µS of the
Universal Time Coordinated
(UTC).

MGTR is a portable GPS
system designed to enable
end-to-end tests

12

AUTOMATIC PROTECTION TEST

A comprehensive range of relay tools containing over 40
specific items. The whole kit is supplied in either a
lightweight soft case or a tough lockable vinyl case.

AVTS packages have a powerful graphical interface that is
developed and continuously upgraded by Megger to simplify
fully automatic and complex relay testing. It is designed to
meet the existing and future needs of protection technicians
and engineers worldwide,
helping to improve efficiency
and reduce testing errors.

• AVTS Basic Software (Advanced Visual Test Software)

A unique modular VI-Gen Design combines the voltage and
current generator (VI-Gen) components into one amplifier
package.

MGTR

A version of AVTS can be supplied to meet individual
customers’ requirements. AVTS Basic is supplied with all MPRT
systems and can be upgraded to AVTS Advanced or the full
AVTS Professional packages. AVTS Basic allows full automatic
operation of the test set with pre-prepared test files, whilst
the Advanced and Professional options give increased
functionality for the preparation of automatic test files and
relay performance evaluation.

MPRT relay test set with touch view interface makes is easy to perform
manual and semi-automatic relay testing

Recorder Capability – Used with Dynamic Control, capture all
analogue output waveforms, binary inputs and outputs, and
more.

New

Protective relay tool kit

• A hand-held controller we call the TVI
(TouchView Interface)

The Power Box

Test Results Import – allows you to read other test set result
files and import them into the AVTS database.

Advanced visual test software

• The Power Box

Dynamic Control – provides easy set up of multi-state dynamic
tests that are normally associated with trip and reclosing
schemes. In addition it gives you a simple means to create
complex waveforms for special test applications, using a new
feature called Wave Index. Wave Index can change the
waveform “on-the-fly” by incrementing individual harmonic
values in real time.

SSI File Reader – quick, easy import of state-sequence files
from ASPEN® and CAPE® Simulation programs.

K500

Automated relay testing enables the test engineer to save a
great deal of time and money by rapidly executing the test
process and minimising any protected power system
equipment down time.

MPRT is recognized for its versatility, its impressive
power capability and an extra rugged design. Its
testing performance is proven every day in some of
the most remote areas of the world.
Plus, it keeps getting better with the addition of significant new
features and capabilities. These include:

AVTS

It’s lightweight (yet extremely rugged), with unmatched
versatility.
Constant Power Output is sustained through the entire
“power curve” of a test. With a CPO of 200 VA current and
150 VA voltage, the MPRT will test any protective relay.

AVTS can display the
voltage and current
output waveforms in
time sequence with
the binary inputs and
outputs.

Automatic protection test
Model
Input voltage
Battery simulator

The modular configuration also allows you to order the
system to fit your precise testing requirements and budget,
with an easy, flexible upgrade path.

Power output

MPRT LCA

a.c. Current amplitude

LCA Low Current Adapter
is a lightweight, field
portable unit designed
to provide multiple precise
very low current sources
with the Megger MPRT
relay test system. The
combination of MPRT and
LCA provides a very
powerful test capability. A
single LCA unit can provide
a maximum of three
currents 10 to 200 milliamps
each phase. LCA is especially
designed for testing very
sensitive extremely low
current relays with high
accuracy amplitude and
phase angle.

New

a.c. Voltage amplitude

d.c. Voltage amplitude

d.c. Current amplitude

Convertible source in
a.c. Current mode

Phase Angle

Safety, EMC, RFI, ESD conformance

With MPRT and LCA, you can test
relays which require three phase
voltage and three phase currents,
with currents as low as 7.5 mA up
to 0.20 A

Weight
GPS unit
Low current adaptor
■ feature

90 to 264 Vac, 50/60 Hz
d.c. output voltages of 24 V
d.c. output voltages of 48 V
d.c. output voltages of 125 V
d.c. output voltages of 250 V
Max phase output at 150 VA per phase
Max phase output at 200 VA per phase
Accuracy ± 0.05% typical, 0.1% guaranteed
Resolution: .001/.01
Measurements: true RMS
Accuracy: ±0.05% typical, 0.1% or ±20 mA,
whichever is greater, guaranteed
Resolution: .001/.01
Measurements: True RMS
±0.1% typical, 0.25% guaranteed.
Resolution: .001/.01
Measurements: True RMS
Accuracy: ±0.1% typical, 0.25% or ±20 mA,
whichever is greater, guaranteed
Resolution: .0001/.001
Measurements: True RMS
Accuracy: ±0.05% typical, 0.1% or ±12.5 mA,
whichever is greater, guaranteed
Resolution: .0001
Measurements: True RMS
Ranges 0.01 to 359.99 degrees, counter clockwise, or
Clockwise rotation, or ±0.01 to ±180.00 degrees
Accuracy: ± 0.02° typical ± 0.25° at 50/60 Hz max
IEC 61010-1, Amendments 1 and 2, EN 50081-2, EN 50082-2,
EN 61000-3-2, 61000-3-3, IEC 61000-4-2/3/4/5/6/8/11.
18.9 kg
MGTR GPS timing reference for synchronized end-to-end testing
maximum of three currents 10 to 200 milliamps each phase

MPRT8415





150 Volts rms
15 Amps




MPRT8430





300 Volts rms
30 Amps


















































option

AUTOMATIC PROTECTION TEST

13

Primary injection test
Circuit Breakers are one of the critical “safety-valves” of electrical systems, and basic
maintenance procedures are essential to maintain maximum reliability. As the leading
producer of circuit breaker test sets, Megger sets the standards for quality and reliability.

PCITS2000/2

DDA1600, DDA3000 and DDA6000

Primary current
injection test set

High current injection test sets
DDAs are a range of high current units capable of generating
a test current of up to 50,000 A through a circuit breaker. The
instrumentation and control system enable the operator to
vary the pulse time and firing angle of the injected signal.
They can be used for testing protection relays and low
voltage circuit breakers at the commissioning stage.

PCITS2000/P enables you to test
relay protection systems and
their current transformers
together. It has a built-in timer
to record protection
relay operation

Secondary injection test
SCITS100

SR98

Current and voltage injection sets

Voltage and current injection sets

Tough test sets suitable for general purpose relay testing.
A wide range of relays can be tested due to their operating
system flexibility. Current and voltage on the output
terminals are measured and displayed. An accurate timer
measures the relay operating time.

SR98 is a lightweight, field portable test set capable of testing
a wide range of electro-mechanical solid-state and
microprocessor-based protective relay. Offering high current
and power output and 0 to 360° phase shift capability, SR98
has a large display, RS-232 and parallel printer ports.

MS-2
Circuit breaker and overload relay test set
MS-2 is perfect for utilities, industrials and electrical service
organisations. It verifies the proper operation of thermal,
magnetic and solid-state overload relays; moulded-case
circuit breakers; and ground-fault trip devices.

MS2 is capable of
delivering 750 A
instantaneously. It is ideal
for over-current and earth
fault relays and moulded
case circuit breakers.

These tough self-contained
test sets are designed for
operation by one person
and are comparatively
light. With a separate
hand-held controller
connected by an
expandable cable it allows
the operator to work close
to a protective relay while
controlling a test.

SITS120
Lighter weight current and voltage
injection sets
A lighter weight option, this tough test set is suitable for
general purpose relay testing.
DDA-1600 is a digital data
acquisition system. It has a modular,
portable design, has variable pulse
time and firing-angle output
current control, and can test a wide
range of breakers

CB832 and CB845

A wide range of relays can be tested due to the flexibility
of its operating system. Current and voltage on the
output terminals are measured and displayed. An
accurate timer measures the relay operating time.

Current injection sets

Automatic protection testing

Capable of generating up to 1800 A and 5000 A respectively
for an instantaneous trip test, these units are ideal for
commissioning applications requiring high current injection.
The CB current injection sets offer adequate driving voltage
for all but the highest circuit impedance.

CB-832 tests thermal, magnetic or
solid-state motor overload relays;
moulded-case circuit breakers; and
ground-fault trip devices

Protection testing
Model
Output current
Voltage output
Power
Time

14

In Amps
Number of ranges
V a.c.
V d.c.
In VA
Period in S
Resolution in S
Cycles

PRIMARY INJECTION TEST

CB832
0 - 1800
3

1750
0 - 999.99
0.001
0 - 99999

PCITS2000/2
0 - 2000
2
0 - 250

0 - 600
0.01

CB845
0 - 5000
4

7200
0 - 999.99
0.001
0 - 99999

MS2
0 - 240

0 - 999.99
0.001
0 - 99999

DDA1600
0 - 19200

0 - 99999
0.0001
0 - 99999

DDA3000
0 - 35000

0 - 99999
0.0001
0 - 99999

DDA6000
0 - 50000

0 - 99999
0.0001
0 - 99999

SCITS100
0 - 100
3
0 - 120
0 - 240
2400
0 - 599.99
0.01

SCITS120
0 - 120
4
0 - 240
0 - 240
700
0 - 999.99
0.001
0 - 99999

SR98
0 -115
4
0 - 300
0 - 240
920
0 - 9999.99
0.0001
0 - 99999.9

Relay type
Time delay
Impedance
Volts per hertz
Synchronising
Directional power
Loss of excitation
Negative sequence
over-current
Negative sequence
under-voltage
Instantaneous
over-current
Over-current
Moulded case breaker
Over-voltage
Directional over-current
Reclosing
Frequency
Differential
Tripping
Auto synchronising
Voltage controlled
over-current
Under / over voltage
d.c. under / over current
Motor overload
Ground directional
over-current
**Two units required

IEEE no.
2
21
24
25
32
40

SCITS100/2
■

SITS120
■

SR98
■
■
■
■
■
■

46
47
50
51
52
59
67
79
81
87
94
25A
27
27
37
51

/
/
/
/

51
59
76
86

67N

■
■

■
■
■
■

■
■
■
■
■
■
■**
■

■

■
■

■

■

■
■
■
■
■

Customer service teams at every Megger location are there to help you
select the right product for your application

SECONDARY INJECTION TEST

15

Cable fault location
The fundamental objective of any cable fault location system is to provide quick, effective,
accurate and safe fault location, resulting in reduced system outages and “Customer
Minutes Lost”. Megger’s new PFL systems achieves all this, and more. The standard
system comes as a mobile, compact system to meet your local requirements. All systems
offer the facility to undertake cable testing.

PFL20-1500

New

Power cable fault locator system

Van mountable cable
fault locator

All important tools of cable fault locating are consolidated
into one package: dc/tester burner, surge generator, and
radar coupling. When utilized with the MTDR Cable Analysis
System, the combined instruments provide the following fault
location techniques:

Joules
Transit

16

CABLE FAULT LOCATION

■ Cable and fault diagnosis
■ Prelocation of cable faults
■ Fault conditioning

Models PFL401500 and 2000

Although not widely thought of as a fault condition method,
the A.R.M. mode can be used in pinpointing faults.

Acoustic pinpoint fault location
Accurate acoustic pinpoint location of faults is achieved with
the powerful 8/16/34 kV (4 kV is optional) surge generator
(thumper), which comes in either 1500 Joules or 2000 Joules
configurations.
Additional accuracy can be achieved by using the Megger
MPP1001 or 1002 acoustic and electromagnetic pinpointer
which easily and accurately shows the direction and distance
to a fault.

Features include:
DC testing to 40 kV
Each instrument uses DC
testing to prove the integrity
and confirm fault conditions in
cable networks with a test
voltage up to 40 kV and a
current of 25 mA.

ARC screen

Report screen

The operator selectable over-current trip levels provide
protection to the system under test in the event of the cable
under test breaking down.

PFL40 features a large, colour screen and intuitive software
which assists you in accurately tracing and locating cable
faults.

Fault pre-location

Included accessories

Each system provides a variety of methods you can use to prelocate the fault position.

Each PFL40 unit comes
complete with:

TDR mode – use a real time trace and a stored trace for
viewing simultaneously on the colour display, allowing
comparison and difference measurements to be determined.
Further, the TDR features auto-ranging, auto distance to fault
and operator assist functions that guide the operator through
the fault locating process.
A.R.M. (Arc Reflection Method) mode – the system stabilizes a
fault by creating a temporary “bridge” to earth. During this
condition a standard pulse echo measurement is taken into
what is basically a short circuit fault.
ICE (Impulse Current) and Voltage Decay methods – these are
also available and are transient analysis methods or prelocation which utilize either a linear coupler or voltage
divider.

■ High voltage shielded
output cable (15 m)
■ Supply cable (7.6 m)
■ Flexible ground cable
(15 m)
■ Ground rod
■ Interlock shorting plug
■ Cable bag and
instruction manual
Stand-alone and rackmounted cable reel
assemblies also
available.

Fault conditioning
Also use the system to stabilize flashing, unstable or high
resistance faults, by employing A.R.M. and Proof/Burn
technology.

Cable fault location systems

Voltage output

The standard system comes as a mobile, compact unit to meet
your local requirements. All systems offer the facility to
undertake cable testing.

A.R.M.

The variable output voltage
can also be used to test
sheaths requiring 5 or 10 kV
test voltages.

unit by a flexible umbilical
cable. This configuration
lends itself to installation
into a suitable vehicle by
you, your designated
contractor or by Megger.
Every installation is
different, and we show some
options to you here. Ask to
see our fully equipped
demonstration vehicle
that shows PFL40A
in action. Megger
offers a full installation
and fitting service
throughout Europe.

PFL20M is easily manoeuvred
because of its compact design
and large wheels

4kV / 8kV / 16kV / 34kV
4kV / 8kV / 16kV
16kV
40kV
20kV
1500J
2000J
Van mount
Wheeled

New

■ Pinpointing locating using acoustic methods

Email us at CFL@Megger.com
for more details.

Surge range

PFL Series Cable Fault
Locators

CLF40A has been
designed to
complement the award
winning and successful
PFL40A series of
portable fault locators.
All the control functions
are installed in a newly
designed remote panel,
connected to the HV

The PFL20-1500 emphasizes portability, featuring all of the
basic fault locating tools within one compact package. It is a
flexible stand-alone unit with a MTDR mounted in the hinged
lid.

Time Domain Reflectometry
Digital Arc Reflection
Surge Pulse
Reflection
Differential Arc
Reflection

New

Cable fault location

PFL40A










PFL20A









PFL20M










CFL40A










Proof/Burn
Following a breakdown of the cable under test, you can
employ the 40 kV dc output to apply a high current,
thus stabilizing the fault condition. This allows easier
and quicker pre-location and pinpointing of the unstable
faults.

CABLE FAULT LOCATION

17

Time domain reflectometers
Time domain reflectometry – or TDR for short – is based on the simple notion of
reflecting an electrical signal from the fault back to your instrument, and measuring the
time. Megger has taken the concept, and added easy to use diagnostic tools that help
even inexperienced staff make expert assessments.

These instruments are used to locate the exact route and
depth of metallic cables. The instruments’ capabilities are
enhanced by offering both passive and active modes. For ease
of use, and improved efficiency, the instruments can be either
inductive or conductively coupled.

Single channel cable fault locator
A state of the art TDR capable of identifying and locating
faults on metallic cables. The TDR1000 is suitable for use on
both dead or live cables without a blocking filter, up to CATIII
300 V phase-to-earth.

■ Multiple output frequencies*
■ Variable tx output power level*

How TDRs work

Problems with the dead zone
The width of the transmitted pulse affects the TDR’s
ability to identify reflections. The width of the pulse is
sometimes referred to as the dead zone. As the pulse
increases in width, it becomes more difficult to
identify reflections, because the dead zone may mask
closely spaced reflections. The TDR measures the
time it takes a pulse to travel down a cable,
encounter an impedance change, and reflect back. By
knowing the velocity of the pulse the TDR converts
this time to distance.
Velocity of Propagation
Pulses travel at different velocities on different cables.
The type of insulation and cross sectional area of a
cable will affect the velocity of a pulse. The velocity of
a cable can easily be determined by connecting onto
a sample of known length. Place the TDR’s cursor at
the reflection representing the end of the cable.
Adjust the velocity setting until the unit reports the
correct length. This setting will be the velocity of
propagation for the cable.
When the problem has been identified, it can be
corrected easily, certainly faster, and more efficiently
than rewiring the system.

L1050, L1070, L1071 Accutrace, and
Cable Route Tracer
Portable cable locators

TDR1000/2P

A TDR measures the time it takes a pulse to travel
down a cable, encounter an impedance change, and
reflect back. By knowing the velocity of the pulse the
TDR converts this time to distance. You can then
pin-point the exact location of the problem. Using a
Time Domain Reflectometer (TDR) such as
TDR1000/2 you can find the distance from the tester
to the end of the wire (up to 3,000 metres), along
with the distance to each anomaly within the circuit.
The problem could be in a terminal block, a wire
bundle, or a poor connection.

Cable trace and voltage
detectors

Capable of locating long or short
ranges, inductive or conductive,
active or passive, the L1070 delivers
quick and accurate results with a
user-friendly interface

■ Peak and null detection*

TDR2000/2P

A state of the art mono or
colour display two-channel
TDR. capable of identifying
and locating faults on
metallic cables. The
TDR2000P is suitable for use
on dead or live cables
without a blocking filter, up
to CATIII 300 V phase-toearth with a range of up to
20 km. The TDR has an
internal memory and the
TraceMaster software
supplied allows storage and
analysis of waveforms on
a PC.

MTDR1

* dependent on model

DETEX®

MPP1000 Series is available as an
electromagnetic-only detector
with acoustic detector, or with
single or dual detector
configurations.

Voltage detectors and phasing testers
The Detex range of testers is ideal for determining the
presence of voltage be it phase to earth or phase to phase.
A verification unit is available to ensure safe operation.

Dual channel cable
fault locator

As a single detector, the set
provides detection of acoustic
emission, measurement of time
delay between the acoustic and
electromagnetic signals, and
distance to the fault. If a second
detector is added, the
set will also display
the direction to the
fault.

Voltage detectors are suitable for voltages from 2.3 kV to
550 kV. Models are available with electronic LED and
audible indication or neon indication.
Phasing testers are available from 2.4 kV to 69
kV with a choice of analogue or
neon voltage indication.

TDR2000/2P can identify and locate
a wide range of faults on metallic
cables from a few metres to 20 km
depending on cable type

DETEX Voltage detectors
are available in seven models
that cover a range from
distribution class to
transmission line
voltages up
to 550 kV

Cable Fault Pinpointer
MPP1000 series locators are used
to pinpoint faults in shielded,
direct buried cables by detecting
both the electromagnetic and
acoustic pulses emitted from an
arcing fault when it is surged.

■ Push button depth measurement*
It takes less time to train users on
TDR1000/P, as each key has a
dedicated function, such as cursor
left and right, velocity factor,
range etc.

MPP1000

The MPP1000 is the accurate way to
pin-point a fault on buried cables

The
MPP1000
series of
locators can be
used with any
surge generator.

New

Single-phase time domain reflectometer
Primarily used for the pre-location of cable faults using arc
reflection, differential arc reflection and impulse current
methods, the MTDR1 offers exceptional flexibility yet is
intuitive to use with facilities such as operator assist, autoranging and auto distance to fault.
With a full built-in
keyboard and
Windows® XP
operating software
the MTDR has a
range of up to 30 km.

Megger designs and lays out its
own printed circuit boards. That
way, quality can be built into your
tester from the earliest moment

18

TIME DOMAIN REFLECTOMETERS

CABLE TRACE AND VOLTAGE DETECTORS

19

Transformer testing
It’s tough work testing transformers when it’s cold and wet. Or even if it’s hot and the
sun’s baking on your back. Don’t worry, Megger’s new hand-held transformer test
equipment is tough and lightweight, with all the functionality you need for rapid testing.

TTR25

PowerDB OnBoard - consistent and
repeatable

Hand-held TTR

PowerDB OnBoard comprises the powerful PowerDB
asset management software embedded within the
instrument, running on a Windows operating system.
Without the need for an external computer, PowerDB
OnBoard brings field based users consistent,
repeatable tests across instruments, unprecedented
data analysis (including historical trend charting) and
asset management tools, all from on-screen ‘forms
based’ views.
Also included are a number of new communication
technologies, providing a near seamless interface
between the instrument and optional peripheral
equipment, such as an “in-lid” USB full-sheet (A4 or
letter) thermal-paper printer, USB flash drive, and
external PC (via Ethernet port). For advanced users, a
USB router can be connected to the instrument to
provide simultaneous access to other equipment,
such as a mouse or a keyboard. Storage space is
provided by either the internal flash memory or
external USB flash drive - sufficient to save literally
tens of thousands of test data sets.

TTR25 is an automatic hand-held
transformer ratio test set used to
measure the turns ratio, excitation
current and polarity of windings
distribution and power
transformers, potential and current
transformers, and tapped
transformers.

TTR25 is designed to operate in
tough environments. It is extra
rugged, with a high impact, shock
resistant case, yet incredibly
lightweight at a mere 870 g

Hand-held
transformer tester

With a turn ratio of 20,000:1, the
TTR100 offers the highest turns
ratio accuracy in the industry of
0.1%. The TTR100 features special
software capabilities

Fully three-phase capable,
TTR100 is the low cost
solution for three-phase
transformer testing. The
lightest and most portable
TTR test set available, it
offers a full set of tests
including; transformer turns
ratio, excitation current,
phase angle deviation,
winding resistance and
transformer polarity, the
results can be stored on
board for later
downloading.

20

TRANSFORMER TESTING

TTR550005
TTR300
TTR310
TTR320
0.001 to 129.999
0.8 to 45,000
0.8 to 45,000
0.8 to 45,000
8V
8 V, 40 V, and 80 V 8 V, 40 V, and 80 V 8 V, 40 V, and 80 V
0 -1 A
0 to 500 mA
0 to 500 mA
0 to 500 mA







Analogue
5.7” mono
5.7” colour VGA
Text
Graphical icons
RS-232
RS-232
Ethernet






16 key
200 datasets
RS-232

Full QWERTY
10,000 datasets
RS-232

TTR330
0.8 to 45,000
8 V, 40 V, and 80 V
0 to 500 mA


8.4” colour VGA
Test forms
Ethernet



Full QWERTY
10,000 datasets
USB


120/230 V a.c.
10.4 kg


120/230 V a.c.
11.3 kg


120/230 V a.c.
11.3 kg


Hand -cranked
7.3 kg


120/230 V a.c.
9.1 kg

TTR300

New

Basic TTR test set
TTR300 is designed to be completely remote controlled via a
PC running PowerDB LITE (included) or PowerDB (full version)
PC software. TTR300 is field upgradeable to TTR310, TTR320
or TTR330 without compromise to calibration. It has built-in
capability for
storing test
results into
internal memory
in an open XML
data format via
PowerDB LITE.
You can quickly
download test
results via RS-232
serial port.

TTR310

Transformer turns ratio testers
TTR25
TTR100
Turns ratio range
0.8 to 20,000
0.8 to 20,000
Excitation voltage
0.5 V, 1.5 V and 8 V 1.5 V and 8 V
Excitation current
0 -100 mA
0 -100 mA
Single phase test


Automatic three phase test
Display Type
128 x 64 LCD
128 x 64 LCD
On-screen view
Text
Text
Remote PC control
User defined settings

Display % error

Power DB Onboard
Keypad
7 key
19 key
Internal storage
200 datasets
Printer interface
RS-232
RS-232
Software COMLINK


PowerDB LITE
Power source
6 x AA
NiMH
Weight
1.5 kg
1.5 kg

TTR320
TTR300 series three-phase transformer turns ratio
test sets are designed to measure the turns ratio of
power, instrument, and distribution transformers in
a substation or manufacturing environment. A
rugged design makes the instruments well suited for
use in a variety of harsh environments. TTR300
series testers are ideal for use by power transformer
manufacturers. Their unique testing procedures and
storage capability allows you to set up and test
difficult three phase transformers (with multiple tap
changers and bushing CTs) in a fraction of the time
than it used to take. Tests include a pass/fail limit of
individual ratios and measuring the phase deviation
of the transformer primary versus secondary. This
quickly indicates problems in the transformer such
as partial shorted turns and core faults. This
measurement is useful in verifying phase errors in all
types of PTs and CTs. Each unit comes equipped
with a remote-control switch for single person
testing. This allows the operator to test transformers
with LTCs very quickly.

TTR100

Reduced training time
A common user interface reduces the training time
needed to understand the different instruments that a
busy test engineer has to use. New instruments with
PowerDB OnBoard such as TTR330 are truly formsbased, have a large 8.4” full-VGA bright colour display,
and let you set up and control the instruments
through on-screen test form views. On-screen test
forms are exact replicas of the test forms which are
printed as a permanent test form record once testing
is complete. They are secure reports and generated
directly from instrument so no human interface is
needed.

Transformer testing

New

TTR with PowerDB lite
TTR310 has an easy-to-read, high-contrast LCD that can be
seen in bright sunlight and provides the user interface for
instrument set-up and test operation. It comes complete with
PowerDB LITE software. TTR310 can store test results, upload
results to a PC (via RS232 serial port), and/or print them in the
field via optional thermal paper printer, without the use of
an external computer. TTR310 has fully automatic operation
(either stand-alone or remote-control), is field upgradeable to
a TTR330 or TTR320 without compromise to calibration and
built-in capability for storing test results into internal memory
in an open data format for direct input into Excel® or XML
format via PowerDB LITE.

New

TTR with PowerDB lite and colour display
TTR320 has a high contrast bright 5.7” full VGA colour display
can be seen in direct sunlight. It has a full keyboard for
entering nameplate information. Communications ports
include RS-232, USB and Ethernet ports for easy on-board
printing, storage, and downloading of test results. PowerDB
LITE software is included, so you can
perform data analysis and trending
of results. TTR320 has fully
automatic operation
(stand-alone or
remote-control),
is field
upgradeable
to TTR330
without
compromise
to calibration
and has a
graphical user
interface with
easy-to-read ICON
based screens and
automated setup
and control. You can
store test results in an
open XML format, to
either internal memory or
to an external USB storage
device.

TTR330

New

Advanced TTR test set with PowerDB
onboard
TTR330 has a new user interface that lets you interact with
the PowerDB ONBOARD software system through keyboard
and navigation keypads as displayed on an 8.4” VGA brightcolour screen. PowerDB ONBOARD displays the actual test
form directly on the screen. TTR330 also lets you customise
test forms via optional full-version PowerDB. TTR330 has
three communications ports (two USB, one Ethernet). The USB
host ports can be used for connecting directly to an optional
printer (to print full size A4 or letter completed test forms)
and for data storage to a USB memory device (for later
printing, analysis, archiving, and/or trending). The Ethernet
port allows TTR330 to interface bi-directionally to a PC.
TTR330 has fully automatic operation (stand-alone or remotecontrol) with user
interface via on-screen
customizable test forms
and built-in capability
for storing test results,
in an open XML
format, to either
internal memory or to
an external USB
storage device.
TTR330 has PowerDB for rapid
report generation

See page 37 for more information on PowerDB.
TRANSFORMER TESTING

21

Transformer testing

Transformer testing

Transformer ohmmeter

MCT1600

Transformer winding resistance and
tap-change test set

Current transformer tester
A robust, portable unit to automatically or manually perform
saturation, ratio, polarity, demagnetising tests, CT burden and
insulation tests on current transformers using the voltage
comparison method. It has an integrated 1 kV insulation test
system. The colour display is viewable in daylight and shows
multiple instantaneous saturation curves with knee points.
Data is saved to a USB stick.

Field portable low resistance measuring instrument designed
to test transformer windings, motors, generators and tap
changers. The two independent measuring channels greatly
reduce the test duration of large inductive loads like
transmission transformers, where it is possible to measure
secondary and primary windings simultaneously.

MCT1600 has a manual
voltage output control
knob. The user can perform
any test required manually if
only a spot check is needed.
A lightweight, field portable unit that safely and accurately measures the
DC winding resistance of all types of transformers and rotating machines

MTO320

MCTT-10
Current transformer tester
MCTT10 is a portable unit for performing saturation and ratio
tests on current transformers using the voltage-comparison
method. It provides a variable voltage output and precision
instrument for testing single and multi-ratio CTs. Saturation
and ratio tests can be performed without changing any leads.
Current transformers can be tested in their equipment
configuration, such as being mounted in transformers, oil
circuit breakers or switchgear. However it is necessary for the
equipment to be totally isolated from the electrical system
prior to testing.

New

Transformer ohmmeter with graphical
interface

MTO210

New

Transformer ohmmeter

MCTT-10 performs saturation and ratio tests on CTs using the voltagecomparison method

New

MTO210 is a line-operated, field-portable instrument
designed specifically to measure the d.c. resistance of all types
of magnetic windings safely and accurately. It is mainly used
all types of transformer windings but can also test rotating
machine windings and perform low-current resistance
measurements on connections, contacts and control circuits.
Three features combine to make this instrument unique
■ dual measurement
■ load tap-changer testing

MTO320 provides a fully automatic six-winding resistance
measurement capability, even on 3-phase transformers with
tap changers. During tap changes, the unit also continuously
monitors for any break-before-make conditions.
The high contrast bright 5.7” full VGA colour display can be
clearly read in direct sunlight. The graphical user interface
allows automated setup and control through easy-to-read
icon based screens. The full QWERTY keyboard speeds the
entering of information such as nameplate-type data.
Communications is via RS-232, USB and Ethernet ports for
easy on-board printing and storage, and downloading of test
results.

■ safety shutdown

Once testing is complete, the unit will automatically
demagnetize the transformer.

The dual set of potential inputs measure the resistance of the
primary and secondary windings of a single- or three-phase
transformer simultaneously speeding up the measurement.

Supplied with PowerDB LITE PC software application, the
user can perform data analysis and trending of results.

To achieve a tenfold improvement in reading time, a
balancing current is applied to the secondary to attenuate
the circulating current induced when the test current is
applied to the primary winding.

TTR550005
Single-phase transformer turns
ratio test set
The single-phase TTR measures power and distribution
transformers using the manual balancing method. Deviations
in turns ratio readings indicate problems in one or both
windings or the magnetic core circuit. A hand crank provides
power for the TTR550005.

When testing the windings and contact resistance on tapchangers with make-before-break contacts and voltage
regulators, the internal shutdown circuit of MTO210, which
will be triggered by a voltage kickback of a few microseconds
if the tap-changer contacts are opened, can be used to check
for pitted or misaligned contacts as the instrument will shut
down if either condition occurs.
Users are protected by the shutdown circuit safety feature:
any inadvertent disconnection of a test lead or loss of power
to the instrument will safely discharge the energy stored in
the test sample.
Transformer Ohmmeter and Current Transformer
Model
Instrument type
Accuracy
Test voltage

The Single-phase TTR transformer
turns ratio test set measures the
turns ratio and exciting current of
windings in power, potential and
current transformers

Lead lengths
Printer paper width
Ouput range

Display

22

TRANSFORMER TESTING

MTO measures dc resistance of all
types of transformer windings
within the defined ranges of
current and resistance.

Tranformer Ohmmeter
Current Transformer test set
+/-0.25% +0.25% of FS
50V
Pre-test polarization check
Demag after test
20 metres (66 feet)
10cm (4 inches)
Field upgradable firmware
Variable 5 mA - 10 A (dc)
Open-circuit test voltage: 50 V dc
Rating: Continuous use on all ranges
8.4 in (210 mm) full colour VGA

MTO210


MTO330
























MCT1600


TRANSFORMER TESTING

23

Transformer testing

Transformer testing

Insulating oil

Karl Fischer

Oil is an efficient coolant with a high flash point and high dielectric strength when used
as an insulator in transformers. The insulation properties can change due to oxidation,
acids, sludge, gas and water absorption. These changes can be monitored using a
dielectric Megger OTS test set.

Karl Fischer testing uses the titration method to measure the amount of water in fluids
such as insulating oil. It has become a standard test done on transformer insulating oil.

KF875
Portable moisture in insulating oil test set

OTS100AF/2

Easy to use, portable one button test set with integral
printer. Can be powered from mains, internal rechargeable
battery or car battery. Ideal for on site use.

Whether you test insulating
oil on-site or in the
laboratory, one of the
Megger oil test sets will
meet your requirements.

100 kV automatic oil test
set
A laboratory instrument that
measures the dielectric strength
automatically with a test voltage up
to 100 kV. While the custom facility
allows the operator to vary the test
parameters, international test
specifications are pre-programmed,
making it easy to use.

KF-LAB
Variable specific gravity
moisture in oil test set
KF-LAB MkII analyzes
materials with a specific
gravity between 0.6 and 1.4,
plus insulating oils

KF875 uses coulometric
titrimetry technology

Moisture in insulating oil not only reduces the
efficiency of the oil as an insulator but may also be
used to detect signs of degradation in the solid
insulation in transformers and switchgear since water
is a by-product of the breakdown of this type
insulation. However oil degrades in the light and
over time, and water content should be measured at
or near the normal operating temperature of the oil.

OTS60SX
Lightweight semi-automatic 60 kV oil dielectric strength test
set which is simple to use and can be powered from a range
of mains supplies.

80 kV automatic oil test set
For laboratory use, this instrument measures the dielectric
strength automatically with a test voltage up to 80 kV. While
the custom facility allows the operator to vary the test
parameters, the international test specifications are preprogrammed, making it easy to use.

OTS60AF/2
60 kV automatic oil test set
For users wanting to test up to 60 kV, this is the ideal
laboratory instrument for automatic dielectric strength
measurement. While the custom facility allows the operator
to vary the test parameters, the international test
specifications are pre-programmed, making it easy to use.

It is now recognised that inaccuracies can occur when
oil is sent to a central laboratory or workshop for
breakdown and water content analysis. Local testing
allows decisions to be made immediately reducing the
danger of putting the equipment back into service with
inadequate oil whilst waiting for results to come
through from a central laboratory.

Polarity

Manual testing

OTS80AF/2

Easy to use test set that titrates for specific
gravities between 0.60 and 1.40. Designed
specifically for laboratory use, the KF-LAB is
mains powered only.

Polarity tester

Motor and phase rotation tester

Transformer polarity verifier
This simple device can help avoid an expensive mistake. Its
small size and reliable construction make it a useful addition
to any tool box.

OTS60PB
Portable automatic testing
The smallest lightest fully automatic portable oil test set
available with test voltage up to 60 kV. Internal rechargeable
battery for operation in remote locations. Optional printer
and fully programmed international test sequences.

A compact, rugged and portable instrument suitable for
phase sequence and motor ratio testing. Suitable for
determining the rotation direction of 1, 2 or 3-phase motors,
rotation or sequence of energized power circuits. Can also be
used to determine the polarity of instruments and power
transformers, and phase/polarity of unmarked
motor windings.

Phase sequence and continuity
indicator
Providing positive indication of phase sequence on energized
lines and which phase, if any, is faulty.

VCM100
Calibration meter
A useful device for verifying the calibration of the AF series
of oil test sets.

Transformer insulating oil dielectric strength testing
Model
Test voltage
Function
Power supply
Weight

24

TRANSFORMER TESTING

OTS100AF/2
100 kV
Automatic
Mains
40 kg

OTS80AF/2
80 kV
Automatic
Mains
40 kg

OTS60AF/2
60 kV
Automatic
Mains
40 kg

OTS60PB
60 kV
Automatic
Rechargeable battery
19 kg

OTS60SX
60 kV
Semi-automatic
Mains
17.5 kg

Motor and phase rotation tester
provides complete phase-sequence
and motor-rotation testing in one
instrument

TRANSFORMER TESTING

25

Low resistance testing
Failing to spot gaps and cracks in aircraft wings or broken rails on railways can cause
disastrous failure causing devastation to the lives of passengers. Routine maintenance
using a low resistance tester (DLRO) sometimes known as a “Ducter” test can highlight
problems before they become catastrophic.

Low resistance testing
DLRO10X

DLRO10

10 A resistance ohmmeter with test results
storage and downloading

10 A low
resistance
ohmmeter

The DLRO10X offers a 0.1 µΩ resolution with a maximum
capability of 2 kΩ. Fast testing ability means users can achieve
results in less than 3 seconds. At only 2.5 kg it is the smallest,
lightest and most sophisticated 10 A low resistance ohmmeter
available making it. Ideal for jobs like rail bond testing.
The DLRO10X has the capability of measuring inductive loads
such as transformers and motor winding. Availability of
readings can vary from a few seconds up to minutes
depending on the inductance and resistance of the test item.

DLRO600
600 A low resistance ohmmeter
Provides the operator with high resolution, 0.1 µΩ,
lightweight and portable method of performing on-site low
resistance measurements. The unit can be used to test circuit
breaker contact resistance to IEC 62271-100, switch contacts,
busbars, joints, splices and fuses. The test current is variable
from 10 A to 600 A, in 1 A steps, enabling the user to
perform all the required test with a single instrument.

The DLRO10X adds on-board
memory, RS232 download
capability, maximum
setting and manual or
automatic range control
to the features of the
DLRO10. Uses easily
interchangeable
batteries.

The DLRO10 offers a 0.1
µΩ resolution with a
maximum capability of 2
kΩ. Fast testing ability
means users can achieve
results in less than 3
seconds. At only 2.5 kg they
are the smallest, lightest
and simplest-to-use 10 A
low resistance ohmmeter
available. Uses easily
interchangeable batteries.

DLRO10 has bright 41⁄2 digit LED
display making it easy to read
under all lighting conditions

BT51
DLRO600 measures resistances
between 0.1 Ω and 1 Ω, at high
currents. It can provide test
currents from 10 amps up to 600
amps subject to the load resistance
and supply voltage. It is ideal for
testing busbars

2 A low resistance ohmmeter

DLRO200
200 A low resistance ohmmeter
Provides the operator with high resolution, 0.1 µΩ,
lightweight and portable method of performing on-site low
resistance measurements. The test current is variable from
10 A to 200 A, in 1 A steps, enabling the user to perform all
the required test with a single instrument. The unit can be
used to test small circuit breaker contact resistance to IEC
62271-100, switch contacts, busbars, joints, splices and fuses.

Why test for resistance?

A large liquid crystal display provides all the information needed to perform
a test; all test parameters and measurement results are displayed

Low resistance measurement
Model
Measurement ranges

DLRO600

0.1 µΩ to 999.9 mΩ
auto ranging

Resolution
Accuracy
Current test range
Results storage
RS232
Power source

Mains
Rechargeable battery

Weight excluding leads

26

LOW RESISTANCE TESTING

DLRO 10X has real-time
download of results and
on-board storage for later
download to a PC

Low resistance ohmmeter ideally suited for bond testing
applications, i.e. aircraft frames, electronic
discharge and fuel tanks. Four terminal
method of measurement
ranges 0-20.00mΩ
and 0-2000mΩ.
High test
current of
2A.

DLRO200

0.1 µΩ to 999.9 mΩ
auto ranging

0.1 µΩ
<1%
10 A - 600 A
300
■
■

0.1 µΩ
<1%
10 A - 200 A
300
■
■

14.5 kg

14.5 kg

DLRO10X
1.9999 mΩ
19.999 mΩ
199.99 mΩ
1.9999 Ω

DLRO10
1.9999 mΩ
19.999 mΩ
199.99 mΩ
1.9999 Ω

BT51
20.00 mΩ
2000 mΩ

19.999 Ω
199.99 Ω
1999.9 Ω
0.1 µΩ
±0.2%
0.1 mA - 10 A
700
■

19.999 Ω
199.99 Ω
1999.9 Ω
0.1 µΩ
±0.2%
0.1 mA - 10 A

10 µΩ
±1%
2.0 A

■
2.6 kg

■
2.6 kg

■
4.5 kg

Low resistance measurements are required to prevent
long term damage to existing equipment and to
minimize energy wasted as heat. They indicate any
restrictions in current flow that might prevent a
machine from generating its full power or allow
insufficient current to flow to activate protective
devices in the case of a fault. Periodic tests are made
to evaluate an initial condition or to identify
unexpected changes in the measured values, and the
trending of this data helps indicate and may forecast
possible failure conditions. Excessive changes in
measured values point to the need for corrective
action to prevent a major failure.

Ask for the free Megger
guide to low resistance
testing. This 32 page
comprehensive guide is
written in a clear, easy
to read style. The
booklet
comprehensively covers
both theory and
practise. It has chapters
on how to measure low
resistance, choosing a
low resistance tester,
and evaluation and
interpretation of results

LOW RESISTANCE TESTING

27

Battery testing

Battery testing
BITE2P

With the increasing dependency of back up systems on battery strings, and the escalating
cost of replacing failing cells; instrumentation and software systems that can measure
trend and manage the life-cycle of cells is a cost effective option.
Are batteries a waste of time and
money?
Batteries are indeed, a waste of money. This means to
say that if the power grid were 100% reliable,
batteries would not be necessary!
The many worldwide power outages over the past
several years make batteries essential as a backup
source. Who actually gives batteries a second
thought? We simply expect them to work when called
upon. Experience has shown that this expectation is
pure fiction.
Batteries are extremely important to provide
electricity to support many assets and revenue
streams during outages. For example, in a generating
station, if the turbine suffers an outage, without the
back-up battery the turbine lube oil priming pumps
would not continuously keep the bearings lubricated
causing major damage and lengthy outages. In
hospitals, who wants to be in the middle of an
operation when an a.c. outage occurs without proper
battery back-up? The applications for batteries are
innumerable and frequently unseen. In this world of
dependency upon electricity, it is impossible to
survive without battery back-up.
It is not enough to only check the voltage and
specific gravity. The sum of all of the cells’ voltages
equals the charger output. Voltage (and specific
gravity) of lead-acid batteries follows the sulphate. If a
battery is fully charged, the sulphate will be in the
acid and its voltage and specific gravity will be normal
(with few exceptions.) If it is in a discharged state,
the voltage will be low and as there will still be some
sulphate on the plates, the specific gravity will also be
low. If the battery has a normal voltage, there is no
indication of its condition. When the voltage is
abnormal, it may indicate a potential problem.
There are many failure modes for batteries. With care
and measurement these can be dramatically reduced,
especially if little to no testing is presently being
performed. The battery is installed, not to add to
work load, but to support critical electrical
equipment or revenue streams. Proper testing and
data analysis can help determine when a battery
should be replaced. Testing also helps reduce
emergency battery replacements and assists in
budgetary planning, thus reducing cost. A properly
implemented battery testing regime does not
necessarily reduce the work load but it will, most
likely, increase reliability of the entire d.c. network.
28

BATTERY TESTING

BITE 2P Battery Impedance Test
Equipment determines the
condition of lead-acid and nickelcadmium cells up to 7000 Ah

BITE® 3

A rugged durable instrument whose enhanced capabilities
make it easier to determine the true state of health of a
battery system, terminal plate to terminal plate.
The BITE2P is ideal battery systems up to 7000 Ah, used in
substations, generating stations, telephone exchange UPS
systems and cabinetised UPS batteries, railway substations,
signal and communications installations.

Battery impedance
test equipment
BITE3 battery impedance
test equipment
determines the
health of leadacid cells up to
2000 Ah by
taking
measurements of
the most
important battery
parameters, cell
impedance, an
internal ohmic test,
cell voltage, intercell
connection resistance and
ripple current.
For the first time in a battery
test instrument, BITE3
measures float current and
the harmonic content of the
ripple current. There is a
built-in spectrum analyser to
show the harmonic content
of the ripple current. It has
firmware that can be
upgraded through the
Internet and supports
English, French, German and
Spanish.

Impedance tester for up to 7000 Ah cells

PROACTIV
Battery database management software

BITE3 determines the health of
lead-acid cells up to 2000 Ah by
taking measurements of the most
important battery parameters

ProActiv is a powerful yet easy-to-use battery database
management software designed to aid the analysis and
monitoring of each individual battery in a battery system.
Failure of a battery system within environments such as
utilities, hospitals or manufacturing plants can result in
operational failure of the devices connected to it.
ProActiv assists the user to avoid battery failures, budget for
future battery string and cell replacements, and plan battery
change-outs in an orderly manner. It utilizes a standard
Microsoft Access database format allowing the user to
organize and manage battery data such as voltages,
impedance, intercell connection resistance, ripple current,
specific gravity, and IR thermographs.

Proactiv uses a standard MS Access database format. It allows users to
organise and manage battery data such as voltages, impedance, intercell
connection resistance, ripple current, specific gravity, IR thermographs
and more

BGFT
BGL (not CE marked)

Battery ground fault
tracer

BITE3 with ProActiv software offer a comprehensive data analysis system to
provide reliable evaluation of batteries in the d.c. network. The analysis
helps you avoid battery failures, budget for future battery string and cell
replacements, and plan battery changeouts in an orderly manner

Battery testing
Model
For batteries of capacity
d.c. voltage range
d.c. voltage resolution
Impedance range
Impedance resolution
Weight

BITE3
2000 Ah
0 - 30 V
1 mV
0 - 100 mΩ
1 µΩ
2.6 kg

BITE2P
7000 Ah
0 - 25 V
1 mV
0 - 100 mΩ
1 µΩ
14.5 kg

The Battery Ground-Fault Tracer is
an economical, manually-balanced
instrument that identifies, tracks
and locates ground faults in
ungrounded d.c. battery systems on-line. It is particularly effective in
a high electrical noise
environments, as the strength of
the test current can be adjusted

Battery earth fault trace

A manually balanced
instrument that identifies,
tracks and locates ground
faults in unearthed d.c.
battery systems, on-line.
Effective in high electrical
noise environments, as the
strength of test current can
be adjusted. Useful for
industries where power
supply for operating
measurement,
communication and control
equipment is critical.

This instrument detects, tracks and
locates earth faults
on battery or floating
systems by injecting a
21 Hz or 25 Hz signal
(depending on line
frequency) between the
system and earth. The
resulting current is then
traced through the
system with a clamp
accessory, knowing
that the fault current
will flow to earth
until the fault is
located. Designed for
operation on live
battery systems, hence there is
no requirement to isolate the system.
BGL simplifies fault tracing by
identifying fault characteristic
(resistive and capacitive)
magnitudes

BATTERY TESTING

29

Earth ground resistance testing
Megger has more than 50 years experience of designing and building earth resistance
testers. The latest generation is CATIV rated, and have tough moulded cases.

Earth ground resistance testing
Variable test frequency keeps noise down, reliability up.

DET3 and DET4

New

Earth ground testers
All models include these features

DET2/2

DCM300E

High resolution earth tester

Earth leakage clamp

Our top of the range earth tester. High resolution to 1 mΩ.
This level is required to measure resistivity to adequate depth
on many substation and communication sites. Measurement
of the low earth values required on many installations, to
meet Ground Potential Rise (GPR) requirements need this
resolution to ensure valid results. Superior noise filtering
greater than 40 V peak to peak to retain resolution under
real test conditions.

Measurement of leakage
current. For stable readings
down to very low current
value with a 10 mA
resolution. Current
measurement up to 300 A.

■ Extra large selector switch
■ Extra large, clear display for easier operation in outdoor
conditions
■ Simple one button operation
■ Battery powered with a bar graph that updates battery
strength
■ Noise reduction up to 40 V peak to peak
■ Safety rating of CATIV 100 V
DCM300E was designed with
safety in mind. It exceeds the
requirements of IEC1010-2-32

Earth resistance testing
Feature
Earth test technique

2-pole resistance measurement a.c.
3-pole earth measurement a.c.
4-pole earth measurement a.c.
Warnings or indicators Noise interference
P spike resistance high
C spike resistance high
Outputs
Adjustable frequency 105 –160 Hz
0.5 Hz steps
Displays
Max resolution 0.001 Ω high accuracy
Noise rejection
40 V peak to peak
Power supply
Battery status indicator
Charge from vehicle battery
Case
Weather and dust proof to IP54
Operation instructions on lid

DET2/2 has excellent noise filtering
and is ideal for big earth systems

Professional earth test kit
Megger’s Professional Earth Test Kit is designed to be as
practical as possible. Housed in a tough polyethylene carry
case, the kit is stored neatly, well-protected and easy to
transport. In use the reels are fitted and retained on the spike
handles, simply run out the test lead to the instrument and
plug in, plug the other end directly into the spike, and test.
When the test is complete, unplug the test leads and wind
them in, whilst still on the spike.

■ Ideal for use with whole range of Megger earth testers
■ 4 wires on easy-wind reels make it quick to get testing
and quick to pack away again
■ 1 croc clip test wire
■ Fibre glass measuring tape to assist accuracy
■ Auger style spikes make it easy to deploy and
to check depth
■ Tough easy store case

Everything you need for earth
ground testing, including a tough
moulded polyethylene case

DET2/2
■
■
■
■
■
■
■
■
■
■
■
■
■

■ IP54 rated (water/dust ingress) for extra protection in harsh
conditions
DET3TD offers a complete kit for customers wishing to conduct
earth electrode testing using the two and three pole techniques
DET3TA is a three pole testing solution for users who prefer an
analogue instrument
DET3TC, when used with the optional ICLAMP allows fall of
potential testing using the ART technique without needing to
disconnect the electrode under test
DET4TD2 is a complete earth testing kit for users needing the
flexibility to use either the two and three pole electrode
techniques or the four pole soil resistivity test
DET4TR2 is similar to DET4TD2, with the added advantage of
using rechargeable batteries. You can also get an adaptor to
charge your tester from your vehicle.

DET10C and DET20C
Earth resistance clamp testers

DET4TC2 is a four pole tester with extended resistance range
and variable test frequency. Use it for ART testing, two or three
pole testing, four pole resistivity testing and stakeless testing.

Earth resistance clamp testers are suitable for measuring
earth resistance of installations such as buildings, pylons and
RF transmitter sites and for inspection of lightning protection
systems.
■ Measures ground rod resistance

DET4TCR2 is similar to DET4TC2, with the added advantage of
using rechargeable batteries. You can also get an adaptor to
charge your tester from your vehicle.

Each instrument includes everything you
need to test:
■ Comes complete with test leads, stakes, batteries, calibration
certificate and rugged polypropylene carry case.

EARTH GROUND RESISTANCE TESTING

■ Measures ground leakage current
■ Automatically self calibrates
■ Auto ranging
■ High and low alarms
■ Memory and downloading

Earth ground testers
Description
Stakeless testing
Stakeless testing with optional test clamps
ART (Attached Rod Technique) with
optional clamp
Selectable test frequency
Earth voltage range 0 to 100V
2-wire testing
3-wire testing
4-wire testing
Dry cell batteries
Rechargeable batteries
Backlit display
Digital display
Analogue display
Test results storage
Downloadable test results storage
Earth current range 0.2 mA to 35 A
Earth current range 0.5 mA to 19.9 A
(with optional measuring clamp)
Resistance range
PowerDB lite
PowerDB full version
■ feature

30

DET4TC2 comes as
a bare tester or in
a full kit

DET3TD

DET3TA

DET3TC

DET4TD2

DET4TR2

■
■
■
■

■
■
■

■
■
■

■

■

■

■
■
■
■
■

■
■
■
■

DET4TC2

DET4TCR2

■

■

■
■
■
■
■
■
■

■
■
■
■
■
■

■
■

■

■

■

■
■

■
■
■

DET10C
■

DET20C
■

■

■

■

■

■

■
■
■

■

■

0.1 to 2 kΩ

0.1 to 2 kΩ

■
0.1 to 2 kΩ

0.1 to 20 kΩ
■


■
■
0.1 to 20 kΩ 0.1 to 200 kΩ 0.1 to 200 kΩ 0.025 to 1.5 kΩ 0.025 to 1.5 kΩ
■
■
■




option

EARTH GROUND RESISTANCE TESTING

31

Multimeters and clampmeters
Donald MacAdie was a Scottish engineer who first put the measurement of Amps, Volts
and Ohms together, inventing the AVOmeter multimeter. The first multimeter was
manufactured by The Automatic Coil Winder Company (predecessor to AVO, later
Megger) in 1923. By 1965, the company had already created over one million AVOmeters.
Multimeters

AVO300 series
Tough and simple multimeters offering large single
parameter display and autoranging.

M7000 series

Hand-held electrical test tools
Electrical contractors throughout the world depend on hand-held test equipment to
ensure installations are safe and function correctly. Count on Megger to produce tough
machines that are designed to surpass the requirements of wiring regulations.

MFT1500 series
Multifunction tester
Offering insulation resistance, continuity, earth loop
impedance and RCD testing in one tester. Ideal for installation
testing and periodic inspection, the top of the range model
offers Bluetooth connectivity for paperless certification.

High specification dual parameter display multimeter
offering measurement accuracies up to 0.2%.

Insulation and continuity testers

M8000 series

MIT300 series

Professional dual parameter display multimeter
offering measurement accuracies up to 0.08%. The
M8037 also offers true RMS.

Model 8 Mark7

Clampmeters

DCM series
A choice of 3 clamp meters
and a fork multimeter for
use during the installation,
maintenance and checking
of electrical systems and
equipment.

DC and AC volts
Continuity
Resistance

Maximum conductor size
Power requirement
AC current range

32

MULTIMETERS AND CLAMPMETERS

A light-weight, CATIII 600 V insulation and continuity tester
ideal for the maintenance engineer whose on the move.

MMC850

Earth loop impedance testers

MMC850 offers a unique
solution to current
measurement in multi-core
cables, without the need to
split cores. Simply clamp the
MMC850 to a multicore
cable and read the current
flowing. Not shown on
selection chart – please ask
for datasheet.

LT300
A high current loop tester that is ideal for industrial
applications with 50 V to 500 V and 16 Hz to 400 Hz
operational range.

LTW300 Series
DCM clampmeters are ideal for use
in the installation, maintenance,
monitoring or checking of electrical
systems and equipment

DCM310


DCM320


DCM330

DCM340



























2-wire non-tripping loop tester that makes measurement
close to the source of supply possible as it measure loop
impedance down to 3 decimal places.

LTW300 does not trip 30 mA
RCDs and can be used on a
wide range of voltages

Portable appliances
testing





LTW425







2-wire non-tripping loop testers that makes loop impedance
testing simple where there is no neutral present.







A range of testers are
offered for in-service
inspection and testing of
electrical equipment in
accordance with the IEE code
of practice. PAT4 series offer
a sophisticated tester with
on-board asset database for
high speed testing while the
PAT32 is a more manual
tester.

Ask for the free electrical
test instruments
catalogue. It includes a
comprehensive review of
hand-held test tools, and
has many interesting
technical articles.
The Model 8 Mk 7 being
manufactured here is a direct
descendant of MacAdie’s original
design



 



 

 



 





ical test
r electr
Megge

ents
instrum

Earth
New!
s
tester
ground better
en
with ev rejection
noise

ters
mp me
New Clat are tough
!
tha
y to use
and eas
tion
®
ltifunc
New Mu Bluetooth
n
with
tester o RCD functio
aut
and
igned
ters des soils
th tes
ky
New ear even in roc
rk
wo
to

M
ER.CO
.MEGG
WWW

DC current range

CAT III 600V
CAT III 1000V
CAT IV 600V
0 - 200.0 V range, 200.0 - 600.0 V accuracy
On < 20 W, Off >50 W, response time <50ms
Range 200.0 Ω ±1%, Accuracy ±5% digits
Range 0 - 400.0 Ω, Accuracy ±1% ±3 digits
35mm diameter
27 mm diameter
16 mm diameter
1 x PP3 9 V alkaline battery
2 x AAA 1.5 A alkaline battery
0-19.99 A
0-40.00 A
0-60.0 A
20.0-199.9 A
40.00-200.0 A
60.0 - 400.0 A
0 - 200.0 A
200-400 A
400 - 600 A
0 - 60.0A
60.0 - 400.0A
400 - 600 A

A CATIV 300 V insulation and continuity tester that comes in
five version from basic tough 2 voltage digital tester to a
downloading 3 voltage tester, there is also an analogue
3 voltage tester.

MIT200 series

MIT200 is an economical tester with
all the essential functions you need

Clampmeters and fork multimeter
Model
Safety rating

MIT300 is ergonomically designed
in landscape format to suit
electrical contractors

The multimeter that has become the industry
standard, due to its robust construction.

Megger has a complete range of analogue, digital and analogue/digital multimeters to
provide the solution to electrical and electronic fault finding and testing

MFT1553 is the
latest multifunction tester
from Megger. It includes Bluetooth
for rapid downloading of test data

The word

er’ is a
‘Megg

trademark
registered

HAND-HELD ELECTRICAL TEST TOOLS

33

Watthour meter testing
Virtually all types of ANSI socket-mounted, panel-mounted and bottom-connected (3 or 4
wire) electricity meters can be tested with PHAZER instruments, while STATES Type FMS
Semiflush-Mounted Test Switches provide a compact, versatile means to disconnect, test
or measure devices and circuits in panelboards such as relays, metering, control circuits
and other instrumentation applications.

CATIV testing
CAT IV compliant instruments
1kV insulation testers

PHAZER® (not CE marked)
Watthour meter test system

Clamp meters
Loop testers

The PHAZER family of watthour meter test sets are true
three-phase, fully automatic systems capable of testing
virtually all types of ANSI socket- mounted and bottomconnected single- and three-phase (three and four wire)
electricity meters.
The PHAZER family consists of specific models for testing
socket-mounted meters and specific models for testing panelmounted and bottom-connected meters. Offering state of the
art optical sensing and a built-in automatic calibration
routine.

Ground earth testers

5kV and 10kV insulation testers

STATES®
switches

MA10

Test switches

Portable watthour
meter standards

Covers the complete area of
panel connections from
terminal block to knife
switches. All products give
long term connection quality
and mechanical stability.

States switches are UL listed, and
CSA certified

Innovation in electrical, electronic
and physical design are
characteristics of Megger’s
engineering teams.

The MA10 watthour
standards are totally
autoranging on the
potential input, current
input and auxiliary power
input. The three summing
current inputs can be used
to perform closed link
testing. Models with
VARhour and Qhour
capabilities are available for
testing multi-function solid
state meters.

MIT400
MIT410
MIT420
MIT430
MIT480
MIT481
MIT485
MIT40X
DCM330
LT300
LTW315
LTW325
LTW335
LTW425
DET3TA
DET3TD
DET3TC
DET4TD2
DET4TR2
DET4TCR2
DET4TC2
MIT520/2
S1-552/2
S1-554/2
MIT1020/2
MIT510/2
S1-1052/2
S1-1054/2






























You have a right to safety
EN61010 - 1:2001 is very specific about transient
immunity. In the section on "Circuits or components
used as transient overvoltage limited devices", the
standard specifies the performance of components
and their applicable impulse withstand voltage.
Megger recommends that wherever possible, you
should specify CAT IV instruments that keep you and
your electrical instrumentation safe. In most cases,
Megger has doubled the impulse withstand voltage
from 4kV to 8kV. In addition nominal mains supply
has increased from 300V to 600V for your protection.

CATIV protection gives confidence when insulation testing outside

34

WATTHOUR METER TESTING

CATIV TESTING

35

Test and measurement software
PowerDB
Acceptance and Maintenance test data
management software
A powerful software package that offers a revolutionary
approach to managing electric utility and industrial electrical
testing data. The software is designed from a ground-up
approach, and is easily the most advanced package on the
market. It employs over 160 industry standard test forms that
have been developed and used by industry specialists during
the last 20 years.
The software package provides data management for electric
utility companies, electrical testing services acceptance jobs,
or maintenance testing jobs. Data entry, storage and creating
reports are all features of the software. In a single step,
PowerDB is able to quickly create entire test documentation
packages that include test reports, comment and deficiency
summaries, table of contents and field service reports.
In addition, users are able to use this flexible software to
define data forms and customize them to different
device types.
PowerDB’s test forms are designed to be used with each
of the following Centres:
Batteries
Cables
Circuit Breakers
Coordination Data
Disconnects
Generators
Ground Fault Tests
Ground Mat/Grid Tests
Instrument Transformers
Power Transformers

Insulation Fluids
Loadbreak Switches
Motor Control
Power Factor Tests
Relays
Switchboards
Transfer Switches
Watthour Meters
Transducers

Easier
Management of
Test Data
This easy-tooperate software
offers a straightforward approach
to data
management. The
first basic step in
creating this userfriendly package
was to make test
data entry screens
and printed forms identical. Users will appreciate that what
they see on the screen is what they will see in the printed
version. PowerDB also simplifies testing and data
management by allowing users to deliver reports
electronically using e-mail, CD-ROM, web server and PDF files.
The software will
also execute
several tasks for
the user,
including
equation
calculations,
temperature
correction factors
and charting.
PowerDB helps
predict possible
equipment
failure by
trending previous results, which can be stored using PowerDB
or imported from other software. This makes transitions from
other software to PowerDB easy, and users can be prepared
for possible problems with equipment.
The industry standard test form is not always what a company
needs, and because of that, the PowerDB software allows the
user to customize forms. With a drag and drop feature
anyone, even those without database experience, can create
a form simply by dragging and dropping in tables, text boxes,
images, charts and more, to create a customized form. And,
with VBScript, calculations can be defined,
tables looked up, and it can even interact
with other applications. One time definition
of common items can be used to put logos,
headers and footers on every page or in
many multiple forms. One change will
automatically update every form the
common item is used in.
There are three
ways to document
testing using the
PowerDB software.
First, the software can
communicate directly
with test and measurement
equipment produced by
Megger. This allows
these products to
enter the
results

Test and measurement software
directly into data
fields. Second,
forms can be filled
in using other
applications,
including Megger’s
Advanced Visual
Test Software,
entering data into
the fields using
information stored
in the other applications. Finally, data fields can be filled in
using manual entry. This allows the user to enter the exact
information that is desired.
Built-in Report Flexibility
PowerDB can create reports in one step, with customizable
sorting of the order of test forms. Forms can be removed, and

Computerized Maintenance Management System Support
Many electrical utilities and other company operations have
invested in sophisticated CMMS systems, such as Digital
Inspection’s Cascade and MRO Software’s MAXIMO. However,
due to test instrument specific software packages and handwritten test results, these firms often struggle to get test data
into their systems. One electric utility even referred to getting
data into the CMMS as ‘feeding the monster’. PowerDB’s
speciality IS ‘feeding the monster’.
PowerDB allows you to link easily with the CMMS system so
that the system can pre-populate the PowerDB equipment
database, send PowerDB all work orders, add forms based
on the job plans, and even return the measurement
points, obtained from a multitude of test sets, back to the
CMMS system.

page numbering will be automatically adjusted. In a single
print job, supplemental reports can also be printed at the
same time as the primary report. The supplemental reports,
including comment and deficiency summary reports, open up
the data and information for all of the equipment tested on
one job. Finally, all of the information can be generated for
the on-demand world using the optional PowerDB Web
server. All of the user’s important information is published to
the Web and can be accessed from anywhere in the world.

Furthermore, Megger will work directly with your CMMS
personnel to integrate your data into your internal CMMS
system.

well-suited for technicians who prefer to spend a
minimum amount of time writing reports and want a more
concise way to process data.

Simplifying the Compilation and Reporting
Process
The new PowerDB software package eliminates many
common paperwork and recording problems. With the
software, the number of man-hours devoted to preparing
reports will be minimal. The user can customize the reports
to be what a job requires but will not have to write the
report, which is automatically generated by the software.
Included in the reports are a table of contents, data sheets,
as well as comment and deficiency summaries. PowerDB
even comes with a built-in spell check.

Electronic records of test data can create a couple of
different problems for companies and utilities. While many
electronic records are hard to locate due to the vast
amount of records kept on one system PowerDB makes it
easier. By using its relational database it is much easier to
find present and past records. And, because it has multiple
safe guards, PowerDB prevents lost data. By saving
documents that are in progress to multiple places, the
problem of lost data is eliminated. PowerDB also
synchronizes the date to several machines, meaning that a
single crash does not create a costly loss of data.

Automatically generated professional reports means that a
testing company, for instance, is able to complete jobs
faster and in a more efficient manner. PowerDB is

Asset management system
PowerDB OnBoard
Product type
Cost options

36

TEST AND MEASUREMENT SOFTWARE

Software
Firmware
Free with selected instruments
Separate purchase




PowerDB lite


PowerDB full version





TEST AND MEASUREMENT SOFTWARE

37

Index
Page
4

Insulation test
MIT520/2
S1-552/2
S1-554/2
S1-1052/2
MIT1020/2
S1-1054/2
MIT510/2
S1-5010

Insulation test
BM15
MJ15

MIT200 series
MIT400 series
MIT480 series
MIT300 series
MIT40X

681100 series
220000 series

5

6

7

Delta 2000

10 kV fully automated capacitance and tan delta test bridge

Delta 3000
670000 series
CB100

10 kV automated insulation dissipation factor test set
2.5 and 12 kV semi-automatic capacitance and tan test bridge
Low voltage capacitance and tan test bridge

Power quality
Power quality analysis software
8 channel recording volt-ammeter
Distribution profiler
3 phase power measurement meter

PA9 Wireless
PA9plus

Power Quality Analyser
Power quality analyser

Low resistance testing

26

DLRO600
DLRO200

600 A low resistance ohmmeter
200 A low resistance ohmmeter

DLRO10X
DLRO10
BT51

10 A resistance ohmmeter with test results storage and downloading
10 A low resistance ohmmeter
2 A low resistance ohmmeter

High resolution earth tester

Advanced visual test software
Protective relay tool kit

DET3 and DET4
DET10C and DET20C

Earth ground testers
Earth resistance clamps

Earth ground resistance testing
13

14
Primary current injection test set
Current injection sets
High current injection test sets
15
Current and voltage injection sets
Circuit breaker and overload relay test set
Voltage and current injection sets
Lighter weight current and voltage injection sets
16
Power cable fault locator system
Van mountable cable fault locator

Earth leakage clamp

Time domain reflectometers

18
Single channel cable fault locator
Dual channel cable fault locator
Single-phase time domain reflectometer

32

33
Multifunction tester
Earth loop impedance testers
Earth loop impedance testers
Earth loop impedance testers
Insulation and continuity testers
Insulation and continuity testers

Watthour meter testing

19

PHAZER® (not CE marked)
STATES® switches
MA10

34
Watthour meter test system
Test switches
Portable watthour meter standards

CATIV testing

Portable cable locators
Voltage detectors and phasing testers
Cable Fault Pinpointer
20

35

Test and measurement software
PowerDB

31

Clampmeters
Multimeters
Multimeters
Multimeters
Multimeters

Hand-held electrical test tools
MFT1500 series
LT300
LTW300 Series
LTW425
Portable appliances testing
MIT300 series
MIT200 series

29

30

Multimeters and clampmeters
DCM series
AVO300 series
M7000 series
M8000 series
Model 8 Mark7
MMC850

27

28

DET2/2
Professional earth test kit
DCM300E

12

Transformer testing

INDEX

25

Battery testing
11

17

TTR25
TTR100

KF875
Portable moisture in insulating oil test set
KF-LAB
Variable specific gravity moisture in oil test set
Polarity tester
Transformer polarity verifier
Phase sequence and continuity indicator
Motor and phase rotation tester

Protective relay test system

Cable trace and voltage detectors

38

9

PFL Series Cable Fault Locators
Models PFL40-1500 and 2000

L1050, L1070, L1071 Accutrace, and
Cable Route Tracer
DETEX®
MPP1000

24

Battery database management software
Battery ground fault tracer
Impedance tester for up to 7000 Ah cells
Battery earth fault trace

Cable fault location

TDR1000/2P
TDR2000/2P
MTDR1

23

100 kV automatic oil test set
80 kV automatic oil test set
60 kV automatic oil test set
Manual testing
Portable automatic testing
Calibration meter

PROACTIV
BGFT
BITE2P
BGL (not CE marked)

Secondary injection test

PFL20-1500
CFL40A

Transformer testing

Battery impedance test equipment

Primary injection test

SCITS100
MS-2
SR98
SITS120

Transformer ohmmeter
Current transformer tester
Transformer ohmmeter with graphical interface

BITE® 3

Automatic protection test

PCITS2000/2
CB832 and CB845
DDA1600, DDA3000 and DDA6000

MTO210
MCT1600
MTO320

10

MetReport
SLM8 (not CE marked)
MDP series
PMM-1

AVTS
K500

Transformer winding resistance and tap-change test set
Current transformer tester
Single-phase transformer turns ratio test set

8
50/100 kV a.c. dielectric test sets
70 kV, 120 kV and 160 kV d.c. dielectric test set

Capacitance dissipation factor and tan delta

MPRT
MGTR
MPRT LCA

22

Transformer ohmmeter
MCTT-10
TTR550005

OTS100AF/2
OTS80AF/2
OTS60AF/2
OTS60SX
OTS60PB
VCM100

Light-weight insulation and continuity tester
Insulation resistance and continuity testers for industrial maintenance
Insulation resistance and continuity testers for telecommunications
Insulation resistance and continuity testers for electricians
Insulation resistance and continuity testers for special applications

High voltage test equipment

Basic TTR test set
TTR with PowerDB lite
TTR with PowerDB lite and colour display
Advanced TTR test set with PowerDB onboard

Transformer testing

Basic 5 kV insulation resistance tester
Basic 5 kV insulation resistance tester

Hand held insulation testers

Page
21

Transformer testing
TTR300
TTR310
TTR320
TTR330

5 kV diagnostic insulation resistance tester
High current 5 kV insulation resistance tester
5 kV insulation resistance tester with high noise rejection
High current 10 kV insulation resistance testers
10 kV diagnostic insulation resistance tester
10 kV insulation resistance testers with high noise rejection
5 kV insulation resistance tester
5 kV graphical insulation resistance tester

Index

36
Acceptance and Maintenance test data management software

Hand-held TTR
Hand-held transformer tester

INDEX

39

Local in more places
Megger has technical support offices in 14 locations, and distributors in
170 countries. Call Megger today for help with your application problems.

Megger Limited
Archcliffe Road
Dover CT17 9EN
United Kingdom
T: 01304 502101
F: 01304 207342
E: UKenquiries@megger.com
Megger
4271 Bronze Way,
Dallas, Texas 75237-1019
USA
T: 1-800-723-2861
F: 1-214-331-7399
E: sales@megger.com
PowerDB
4064 State Highway 6 South
College Station
TX 77845
USA
T: 979-690-7925
F: 979-690-0276
E: sales@megger.com

Megger Limited
110 Milner Avenue Unit 1
Scarborough Ontario M1S 3R2
Canada
T: 1 416 298 6770
F: 1 416 298 0848
E: CAenquiries@megger.com
E: CAinfos@megger.com

Megger
Valley Forge Corporate Centre
2621 Van Buren Avenue
Norristown
PA 19403
USA
T: 610 676 8500
F: 610-676-8610
E: sales@megger.com

Megger Pty Limited
Unit 26, 9 Hudson Avenue
Castle Hill
Sydney, NSW 2154
Australia
T: +61 (0)2 9659 2005
F: +61 (0)2 9659 2201
E: AUenquiries@megger.com

Megger
P.O. Box 15777
Kingdom of Bahrain
T: +973 (177) 40 620
E: MEenquiries@megger.com

Programma GmbH
Obere Zeil 2
61440 Oberursel
Deutschland
T: 06171-92987-0
F: 06171-92987-19
E: DEanfrage@megger.com

Megger SARL
23 rue Eugène Henaff
ZA du Buisson de la Couldre
78190 Trappes
France
T: 01 30 16 08 90
F: 01 34 61 23 77
E: Infos@megger.com

Programma Electric AB
Eldarvägen 4
Box 2970, SE-187 29
Täby
Sverige
T: +46 8 510 195 00
F: +46 8 510 195 95
E: SVinfo@megger.com

Megger
501 Crystal Paradise Mall
Off Veera Desai Road
Andheri(w)
Mumbai - 400053
Maharashtra
T: +91 22 26740468
F: +91 22 26740465
E: INenquiries@megger.com

Programma Electric AG
Ob. Haselweg 630
5727 Oberkulm
Aargau
Schweiz
T: +41 62 768 20 30
F: +41 62 768 20 33
E: CHanfrage@megger.com

Megger
PO Box 10044
Edenglen, 1613 Johannesburg
South Africa
T: (011) 4526287
F: (011) 6096852
E: SAenquiries@megger.com

Megger
30 / 46 Moo 13
Nongprue, Banglamung
Chonburi 20150
Thailand
T: +66 860103395
E: THenquiries@megger.com

The products featured in this catalogue are available from:

THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK

WWW.MEGGER.COM

WWW.CABLEJOINTS.CO.UK

Copyright © 2008 Megger Limited Archcliffe Road Dover CT17 9EN
Printed in the UK BP/●●●. Part No 80132



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 for Macintosh
Modify Date                     : 2009:04:16 17:15:40+01:00
Create Date                     : 2008:04:04 10:42:19+01:00
Metadata Date                   : 2009:04:16 17:15:40+01:00
Format                          : application/pdf
Title                           : untitled
Document ID                     : uuid:a4ef332c-022b-11dd-9825-000a959934e8
Instance ID                     : uuid:5db46b6b-17b7-4a2f-9942-8cb4d7689afd
Page Count                      : 21
Page Mode                       : UseNone
EXIF Metadata provided by EXIF.tools

Navigation menu