2pv 20_PV_I Series Service
User Manual: 20_PV_I
Open the PDF directly: View PDF .
Page Count: 32
Download | |
Open PDF In Browser | View PDF |
Price - $3.00 INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS SERIES 2PV GAS BOILER For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial Number as shown on Rating Label. Boiler Model Number 20_PV_I-_ _ _ _ Boiler Serial Number 6_ _ _ _ _ _ _ Heating Contractor Phone Number Address 8141775R9-11/99 Installation Date 1 The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life. CAUTION DANGER Indicate s a po tentia lly haz ardous s ituat ion w hich, if n ot avoided, may re sult in mod erate o r minor in jury or prope rty damage . Indicates an imminently hazardous situation wh ic h, if n ot a voi de d, will re sult in de at h, serious injury or substantial property damage. NOTICE WARNING Indicates spec ial ins tru ctions on ins tallatio n, ope ra tion, or maintenanc e whi ch are importan t but not re late d to persona l injury ha zards . In dic at es a pot ent ia ll y ha za rdo us s itu ation which, if not avoide d, could result in death, serious injury or substantial property damage. Table of Contents I. Pre-Installation ..................................... 4 II. Unpack Boiler ....................................... 5 III. Water Piping ......................................... 6 IV. Gas Piping ............................................ 8 V. Venting ................................................. 9 VI. Electrical ............................................. 12 VII. System Start-up .................................. 13 VIII. Service Instructions ............................ 20 IX. Repair Parts ........................................ 23 2 NOTICE USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially orificed to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F. Canadian boilers’ orifice sizing is indicated on the rating label. High altitude boiler models are identifiable by the second digit in the model number suffix on the rating label: 20_PV_I-__2: Less than 2000 ft. elevation 20_PV_I-__4: 2000 ft. and higher elevation, Canada 20_PV_I-__5: 2000 ft. and higher elevation, USA Figure 1: Elevation Views Dimensions [in inches] A B C D Water Content [Gallons] 203PV 20‰ 14‰ 10-1/16 15-5/8 3.2 265 204PV 23 17 11 15-5/8 4 309 Boiler Model Ap prox. Shippin g Weight (lb.) 205PV 27 21 13‰ 15… 4.7 357 206PV 30… 24… 15-1/8 15… 5.5 419 3 I. Pre-Installation C. Appliance is design certified for installation on WARNING combustible flooring. The boiler must not be installed on carpeting. Carefully read all instructions before installing boiler. Failure to follow all instructions in proper order can cause personal injury or death. D. Provide clearance between boiler jacket and combustible material in accordance with local fire ordinance. See Figure 2 for minimum clearance from combustible material for closet installation. For alcove installation provide top clearance of 27 inches and right side clearance of 6 inches. Recommended service clearance is 24 inches from left side, right side and front. Service clearances may be reduced to minimum clearances to combustible materials. A. Inspect shipment carefully for any signs of damage. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim for damage or shortage in shipment must be filed immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment. E. Install on level floor. For basement installation provide solid base, such as concrete, if floor is not level or if water may be encountered on floor around boiler. B. Installation must conform to the requirements of the F. Install near outside wall for through wall venting. authority having jurisdiction. In the absence of such requirements, installation must conform to National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/ CGA B149 Installation Codes. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Refer to Section V: Venting. Certified for minimum vent length of 2 feet with one (1) elbow and maximum vent length of 15 feet with one (1) or two (2) elbows. WARNING Certified as Category III appliance. Install vent system in accordance with Section V: Venting. Do not vent using masonry chimney, Type B gas vent, or other Category I venting system. G. Protect gas ignition system components from water (dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.). H. Provide combustion and ventilation air in accordance with applicable provisions of local building codes, or National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation, or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 Installation Codes. WARNING Adequate combustion and ventilation air must be provided to assure proper combustion. The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1. 1. Determine volume of space (boiler room). Rooms communicating directly with space (through openings not furnished with doors) are considered part of space. Figure 2: Minimum Clearances to Combustible Construction for Closet Installation 4 Volume [ft³] = Length [ft] x Width [ft] x Height [ft] 2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh). a. Direct communication with outdoors. Minimum free area of 1 square inch per 4,000 Btu per hour input of all equipment in space. 3. Determine type of space. Divide Volume by Total Input. b. Vertical ducts. Minimum free area of 1 square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area. a. If result is greater than or equal to 50 ft³ per 1,000 Btuh, space is considered an unconfined space. c. Horizontal ducts. Minimum free area of 1 square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area. b. If result is less than 50 ft³ per 1,000 Btuh, space is considered a confined space. 4. Determine building type. A building of unusually tight construction has the following characteristics: Alternate method for boiler located within confined space. Use indoor air if two permanent openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches. a. Walls and ceiling exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and; b. Weather-stripping has been added on openable windows and doors, and; c. Caulking or sealants applied in joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings. 7. Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and grilles must be fixed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh. 5. For boiler located in an unconfined space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors. Consider the blocking effect of louvers, grilles and screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area. 6. For boiler located within unconfined space in building of unusually tight construction or within confined space, provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following: I. Do not install boiler where gasoline or other flammable vapors or liquids, or sources of hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored. II. Unpack Boiler CAUTION D. Remove all boiler hold-down fasteners. Do not drop boiler. Do not bump boiler jacket against floor. E. Tilt the boiler to one side and slide a wooden slat under the two raised feet. A. Move boiler to approximate installed position. F. Tilt the boiler to the other side and slide another B. Remove all crate fasteners. wooden slat under the two raised feet. C. Lift outside container and remove with all other inside G. Slide the boiler forward or backward off the skid using protective spacers and bracing. Save two of the wooden slats from the container sleeve for use in Steps E and F. the two wooden slats as runners. H. Move boiler to its permanent location. 5 III. Water Piping and Trim F. Space heating and domestic water heating with Alliance CAUTION water heater. Install Alliance water heater as a separate heating zone. Refer to Alliance Installation, Operating and Service Instructions for additional information. Failure to properly pipe boiler may result in improper operation and damage to boiler or building. G. If boiler is used in connection with refrigeration systems, boiler must be installed with chilled medium piped in parallel with the heating boiler using appropriate valves to prevent chilled medium from entering boiler, see Figure 4. Also consult I=B=R Installation and Piping Guides. A. Design and install boiler and system piping to prevent oxygen contamination of boiler water. H. If boiler is connected to heating coils located in air CAUTION handling units where they may be exposed to refrigerated air, boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during operation of cooling system. Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. Burnham’s standard warranty does not cover problems caused by oxygen contamination of boiler water. I. Use a boiler bypass if the boiler is to be operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.). Oxygen contamination sources are system leaks requiring addition of makeup water, fittings, and oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system leaks, repairing fittings, and using nonpermeable materials in distribution system. Install pipe tee between circulator and boiler return along with second tee in supply piping as shown in Figure 5. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated in Figure 5 in order to regulate water flow to maintain higher boiler water temperatures. B. Connect system supply and return piping to boiler. See After the boiler is operational (reference Section VII. System Start-Up) set by-pass and boiler supply valves to half throttle position to start. Operate boiler until system water temperature reaches normal operating range. Adjust valves to provide 180° to 200°F supply water temperature. Opening the boiler supply valve will raise system temperature, while opening the by-pass valve will lower system supply temperature. Figure 3. Also consult I=B=R Installation and Piping Guides. Maintain minimum ½ inch clearance from hot water piping to combustible materials. C. Install Circulator with flanges, gaskets and bolts provided. Five foot circulator harness allows circulator to be mounted on supply or return. Connect harness to circulator and secure any excess conduit. J. A hot water boiler installed above radiation level must be D. Install Safety Relief Valve. See Figure 3. Safety Relief provided with a low water cutoff device as part of installation. Valve must be installed with spindle in vertical position. Installation of the relief valve must be consistant with the ANSI/ASME Boiler and Pressure Vessel Code, Section IV. K. Oil, grease, and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out, and then thoroughly flushed. A qualified water treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations. WARNING Safety relief valve discharge piping must be piped near floor to eliminate potential of severe burns. Do not pipe in any area where freezing could occur. Do not install any shut-off valves. L. After the boiler and system have been cleaned and flushed, and before refilling the entire system add appropriate water treatment chemicals, if necessary, to bring the pH between 7 and 11. E. Install Drain Valve in ¾" NPT connection in tee provided. See Figure 1. 6 Figure 3: Recommended Boiler Piping For Series - Loop Hot Water Heating Systems Figure 4: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems Figure 5: Recommended Bypass Piping 7 IV. Gas Piping A. Size gas piping. Design system to provide adequate 3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve and outside jacket. See Figure 6. gas supply to boiler. Consider these factors: 1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is listed on rating label. 4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, ANSI/NFPA 70 and/or CSA C22 Electrical Code. 2. Maximum gas demand. Table 1 lists boiler input rate. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment). C. Pressure test. The boiler and its gas connection must be leak tested before placing boiler in operation. 1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler's individual manual shutoff valve. Table 1: Rated Input Input Rate [cubic feet per hour] Boiler Model Number Natural Gas 203PV 62 24 ‰ 204PV 96 38‰ ‰ 205PV 130 52 ‰ 206PV 164 LP/Propane Gas Connection Size 65 2. Locate leaks using approved combustible gas detector, soap and water, or similar nonflammable solution. Do not use matches, candles, open flames, or other ignition source. ‰ 3. Length of piping and number of fittings. Refer to Table 2 for maximum capacity of Schedule 40 pipe. Table 3 lists equivalent pipe length for standard fittings. 4. Specific gravity of gas. Gas piping systems for gas with a specific gravity of 0.70 or less can be sized directly from Table 2, unless authority having jurisdiction specifies a gravity factor be applied. For specific gravity greater than 0.70, apply gravity factor from Table 4. If exact specific gravity is not shown choose next higher value. For materials or conditions other than those listed above, refer to National Fuel Gas Code, NFPA 54/ ANSI Z223.1, or size system using standard engineering methods acceptable to authority having jurisdiction. B. Connect boiler gas valve to gas supply system. 1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CGA B149 Installation Codes. 2. Use thread (joint) compounds (pipe dope) resistant to action of liquefied petroleum gas. Figure 6: Recommended Gas Piping 8 Table 2: Maximum Capacity of Schedule 40 Pipe in CFH For Gas Pressures of 0.5 psig or Less 0.3 inch w.c. Pressure Drop Length [Feet] ‰ 10 132 20 0.5 inch w.c. Pressure Drop 1 1… ‰ 1 1… 278 520 1,050 175 360 680 1,400 92 190 350 730 120 250 465 950 30 73 152 285 590 97 200 375 770 40 63 130 245 500 82 170 320 660 50 56 115 215 440 73 151 285 580 60 50 105 195 400 66 138 260 530 70 46 96 180 370 61 125 240 490 80 43 90 170 350 57 118 220 460 90 40 84 160 320 53 110 205 430 100 38 79 150 305 50 103 195 400 Table 3: Fitting Equivalent Lengths Table 4: Specific Gravity Correction Factors Nominal Pipe Size Fitting ‰ 1 1… 45 Ell 0.7 1 1.2 1.6 90 Ell 1.6 2.1 2.6 3.5 Tee (As Elbow) 3.1 4.1 5.2 6.9 Specific Gravity Correction Factor Specific Gravity Correction Factor 0.50 1.10 1.30 1.07 0.55 1.04 1.40 1.04 0.60 1.00 1.50 1.00 0.65 0.96 1.6 0.97 0.7 0.93 1.7 0.94 0.75 0.9 0.8 0.87 V. Venting A. General Guidelines. 1. Vent system installation must be in accordance with National Fuel Gas Code, NFPA 54/ANSI Z221.3, Part 7, Venting of Equipment; and/or CAN/CGA B149 Installation Codes, Section 7, Venting Systems and Air Supply for Appliances; or applicable provisions of local building codes. Contact local building or fire officials about restrictions and installation inspection in your area. Saf-T-Vent, Flex-L International Inc., - Star-34, Protech Systems, Inc. - FasNSeal™, and Z-Flex U. S., Inc. - Z-Vent. The use of these alternate manufacturer's venting systems will require adapters to connect to the Burnham supplied vent connector and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of the alternate manufacturer's venting system. See Table 5 for complete list of Burnham Vent System Components. 2. This appliance requires a Special Gas Vent. Use Vent Connector and Vent Terminal in Vent Accessory Carton provided with boiler (See Repair Parts, Key No. 8). The product is designed to use Burnham supplied AL 29-4C® Stainless Steel vent system components. The following manufacturers offer similar AL 29-4C® components and are approved for use with this product: Heat-Fab Inc. - WARNING Do not use this appliance with nonmetallic vent systems such as Hart & Cooley Ultravent, Plexco Plexvent, or Selkirk-Metalbestos Sel-Vent. 9 continuously. Table 5: Burnham Vent System Components Vent System Component Burnham *Car toned Part Number Burnham Component Part Number 3" Dia. P ipe x 1 Ft 611 60112 8116135 3" Dia. P ipe x 3 Ft 61160101 8116058 3" Dia. P ipe x 4 Ft ** 8116176 3" Dia. P ipe x 5 Ft 6116 0111 8116059 3" Dia . 90 E lbow 61160121 8116060 3" Dia . 45 E lbow 61160131 8116061 (e) Test for spillage at the drafthood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe. (f) After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use. (g) Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1. * Com plete with Locking B and(s ) * * 61160 33 Contains (4 ) 4 ft. l engths 61160 40 Contains (2 ) 4 ft. l engths 3. Minimum vent length requirement is 2 feet of pipe and one (1) elbow. Maximum vent length is 15 feet with one (1) or two (2) elbows. B. C. Install Vent Connector. 4. Do not install venting system components on the exterior of the building except as specifically required by these instructions. Removal of Existing Boiler. For installations not involving the replacement of an existing boiler, proceed to Step C. 1. Remove vent connector from vent accessory carton. 2. Remove gaskets, orifice plate and hardware from blower outlet flange. 3. Assemble orifice plate gaskets, orifice plate, and vent connector. See Figure 7. When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation: 4. Secure vent connector with washers and locknuts. (a) Seal any unused openings in the common venting system. (b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other deficiencies which could cause an unsafe condition. (c) Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. (d) Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate Figure 7: Vent Connector Installation 10 D. Install Vent Pipe, General. 2. Vent terminal location restricted per following: a. Minimum 12 inches above grade or normally expected snow accumulation level, or 7 feet above grade if located adjacent to public walkway. Do not install over public walkway where local experience indicates condensate or vapor from Category III appliances creates a nuisance or hazard. 1. Start at vent connector. Work toward vent terminal. 2. Use ¾ inch pipe strap to support horizontal runs, maintain vent location and slope, and prevent sags. Do not restrict thermal expansion movement. Maximum support spacing is 5 feet. 3. Provide minimum 5 inch clearance to combustible materials. Use thimble when penetrating combustible wall. a. 203PV and 204PV - Single wall thimble, Burnham Part No. 8116116. Other wall thimble manufacturers are American Metal Products, Hart & Cooley, and Metal Fab. b. 205PV and 206PV - Double wall thimble, Burnham Part No. 8116115 (accomodates 5" to 8¾" wall thickness). Another wall thimble manufacturer is Hart & Cooley. 4. Cut pipe to length using hacksaw with minimum 32 teeth per inch or circular saw with metal abrasive wheel. Remove bead end only - bell end accepts next fitting or pipe. Cut must be square with pipe. Scrape off burrs with sharp edged tool. Figure 8: Typical Joint Detail Note: If remaining pipe (less bell) must be used, beaded end of mating pipe/fitting must be crimped. b. Minimum 3 feet above any forced air inlet located within 10 feet. c. Minimum 4 foot below, 4 foot horizontally from, or 1 foot above any door, window, or gravity air inlet. d. Minimum 4 feet horizontally from, and in no case above or below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment. e. Minimum 12 inches from overhang or corner. 5. Seal all joints using Dow Corning Silastic 732 RTV, Dow Corning Silastic 736 RTV, Polybac #500 RTV, or Sil-bond RTV 4500 (Acetoxy). Do not use other adhesives or sealants. 6. Procedure for joining pipe and fittings. See Figure 8. a. Clean pipe or fitting. Remove all dirt and grease. b. Slip locking band over pipe/fitting bell. 3. Use wall thimble when passing through combustible outside wall (thimble use optional for noncombustible wall). Insert thimble through wall from outside. Secure outside flange to wall with nails or screws, and seal with adhesive material. Install inside flange to inside wall, secure with nails or screws, and seal with adhesive material. c. Apply continuous ¼ inch bead of sealant around bead end of pipe/fitting no more than 1/8 inch from end. d. Insert pipe/fitting into bell. Smooth sealant for continuous seal around gap between bead and bell. Apply additional sealant if necessary. e. Slip locking band over joint and tighten. Do not secure joint with sheet metal screws or pop rivets. 4. For noncombustible wall when thimble is not used, size opening such that bell with locking band attached cannot pass through. E. Horizontal (Through Wall) Vent Installation. 5. Join vent terminal to vent pipe. Cut vent pipe to locate vent terminal 3 inches (minimum) and 6 inches (recommended) from wall when joined to inside vent piping. See Figure 9. Vent terminal clearance to vinyl wall surfaces is 6 inches. 1. Maintain minimum ¼ inch per foot slope in horizontal runs. Slope pipe down toward vent terminal. CAUTION 6. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal. Moisture and ice may form on surfaces around vent terminal. To prevent deterioration, surfaces should be in good repair (sealed, painted etc.) 11 Figure 9: Recommendations for Thimble and Wall Penetration VI. Electrical A. General. Install wiring and ground boiler in Instructions. accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electric Code. 1. Zoning with Circulators, Domestic Hot Water Priority. Provide DPDT relay (included with PAL). Connect coil to Alliance thermostat (prewired with PAL). Connect normally open contacts (red and white wires in PAL control harness) to transformer terminals 'R' and 'Y'. Disconnect yellow circulator wire. Connect normally closed contacts (violet wires in PAL boiler harness) to yellow relay wire and yellow circulator wire. B. Install thermostat. Locate on inside wall approximately 4 feet above floor. Do not install on outside wall, near fireplace, or where influenced by drafts or restricted air flow, hot or cold water pipes, lighting fixtures, television, or sunlight. Allow free air movement by avoiding placement of furniture near thermostat. 2. Zoning with Circulators, Nonpriority. Connect Alliance circulator zone control (or red and white wires in PAL control harness) to transformer terminals 'R' and 'Y'. C. Wire thermostat. Provide Class II circuit between thermostat and boiler. Run wires through grommet in Jacket Left Side Panel. Set thermostat heat anticipator to 0.6 amps. See Figure 10. 3. Zoning with Zone Valves. Connect Alliance thermostat to zone valve. Connect zone valve end switch to relay terminals 'R' and 'G'. See Paragraph F. D. Wire boiler. Boiler is rated for 120 VAC, 60 hertz, less than 12 amperes. Provide individual branch circuit with fused disconnect. Connect to black and white wires and green ground screw. See Figure 10. F. For installations using zone valves provide separate transformer for zone valve wiring. Consult zone valve manufacturer for assistance. E. Alliance water heater (if used). See Figure 10. Also refer to Alliance Installation, Operating and Service 12 Figure 10: Wiring Diagram VII. System Start-up A. Safe operation and other performance criteria were 8. Open zone valve to second zone to be purged, then close first. Repeat this step until all zones have been purged, but always have one zone open. At completion, open all zone valves. met with gas manifold and control assembly provided on boiler when boiler underwent tests specified in American National Standard for Gas-Fired LowPressure Steam and Hot Water Boilers, ANSI Z21.13. 9. Close bib cock, continue filling system until pressure gauge reads 12 psi. Close fill valve. B. Fill heating system with water and vent air from system. Use the following procedure on a Series Loop System equipped with zone valves. See Figure 3. Note: If makeup water line is equipped with pressure reducing valve, system will automatically fill to 12 psi. Leave globe valve open. 1. Close isolation valve in boiler supply piping. 10.Open isolation valve in boiler supply piping. 2. Isolate all circuits by closing zone valves or balancing valves. 11.Remove hose from bib cock. 3. Attach hose to bib cock located just below isolation valve in boiler supply piping. Terminate hose in five gallon bucket at a suitable floor drain or outdoor area). C. Check main burners. See Figure 11. Rear of burner must be in vertical slot in rear of burner tray. Front of burner must be seated on orifice. 4. Starting with one circuit, open zone valve. 5. Open bib cock. 6. Open fill valve. Makeup water line should be located directly above isolation valve in boiler supply piping. 7. Allow water to overflow from bucket until discharge from hose is bubble free for 30 seconds. 13 Figure 11: Main Burner Installation Figure 12: Gas Valve Pressure Tap D. Prepare to check operation. 1. Obtain gas heating value (in Btu per cubic foot) from gas supplier. 2. Connect manometer to pressure tap on gas valve. See Figure 12. 3. For natural gas fired boiler, temporarily turn off all other gas-fired appliances. E. Follow Operating Instructions to place boiler in operation. See Figure 17. F. Sequence of Operation. See Figure 14. If boiler fails to operate properly, see Troubleshooting Tree on pages 17-18. G. Check gas piping and connections between Gas Valve and Manifold, Orifices and Pilot Tubing. Use soap solution or other approved method. See Figure 13. H. Check pilot burner flame. See Figure 15. Flame should be steady, medium hard blue enveloping 3/8 to ½ inch of sensing probe. I. Check main burner flame. See Figure 16. Flame should have clearly defined inner cone with no yellow tipping. Orange-yellow streaks should not be confused with true yellow tipping. Figure 13: Schematic Pilot and Gas Piping Figure 14: Sequence of Operation 14 Figure 15: Pilot Burner Flame Table 6: Gas Flow Rate in Cubic Feet per Hour Size of Gas Meter Dial Seconds for One Revolution One-Half Cu. Ft. One Cu. Ft. Two Cu. Ft. 30 60 120 240 32 56 113 225 34 53 106 212 36 50 100 200 38 47 95 189 40 45 90 180 42 43 86 172 44 41 82 164 temperature setting to start and stop boiler operation. 46 39 78 157 K. Check ignition control module shut-off. Disconnect 48 37 75 150 50 36 72 144 52 35 69 138 54 33 67 133 56 32 64 129 58 31 62 124 60 30 60 120 Figure 16: Main Burner Flame J. Check thermostat operation. Raise and lower igniter/sensor cable from Terminal 9 (SPARK). Gas valve should close and pilot and main burners should extinguish. L. Check low water cutoff (if used). Drain boiler water below LWCO set point. Burners should extinguish. M. Check limit. 1. Adjust thermostat to highest setting. a. Boiler must not be overfired. Reduce input rate by decreasing manifold pressure. Do not reduce more than 0.3 inch w.c. If boiler is still overfired, contact your Burnham distributor or Regional Office for replacement Gas Orifice. 2. Observe temperature gauge. When temperature is indicated, adjust limit to setting below observed temperature. Main burners and pilot burner should extinguish and blower stop. 3. Adjust limit to setting above observed temperature. Ignition sequence should begin. b. Increase input rate if less than 98% of rating label input. Increase manifold gas pressure no more than 0.3 inch w.c. If measured input rate is still less than 98% of rated input: 4. Adjust thermostat to lowest setting. Adjust limit to desired setting. N. Adjust gas input rate to boiler (Natural Gas). i. 1. Adjust thermostat to highest setting. Remove Main Burners per procedure in Section VIII: Service. ii. Remove gas orifices. Drill one (1) drill size larger (drill size is stamped on orifice, or see Key No. 4D). 2. Check manifold gas pressure. Manifold pressure is listed on rating label. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure can not be attained, check gas valve inlet pressure. If less than minimum gas supply pressure listed on rating label, contact gas supplier for assistance. iii. Reinstall gas orifices and main burners. Measure input rate. 6. Recheck Main Burner Flame. 7. Adjust thermostat to normal setting. 8. Return other gas-fired appliances to previous conditions of use. 3. Clock gas meter for at least 30 seconds. Use Table 6 to determine gas flow rate in Cubic Feet per Hour. O. Adjust gas input rate to boiler (LP/Propane). 4. Determine Input Rate. Multiply gas flow rate by gas heating value. 1. Adjust thermostat to highest setting. 2. Check manifold pressure. Adjust gas valve pressure regulator to obtain 10 inches w.c. manifold 5. Compare measured input rate to input rate listed on rating label. 15 Figure 17: Operating Instructions pressure. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure can not be attained, check gas valve inlet pressure. If less than minimum gas supply pressure listed on rating label, contact gas supplier for assistance. subsequent boiler operation. 2. Ventilate the boiler room, set the high limit to its maximum setting, set the thermostat to call for heat. Allow the boiler to fire for at least an hour or until the odor from the cornstarch has dissipated. 3. Return the high limit and thermostat to their desired settings. 3. Recheck Main Burner Flame Q. Review User's Information Manual and system 4. Adjust thermostat to normal setting. operation with owner or operator. P. COMBUSTION CHAMBER BURN-OFF R. Post instructions near boiler for reference by owner 1. The mineral wool combustion chamber panels contain a cornstarch based binder that must be burned out at installation to prevent odors during and service personnel. Maintain instructions in legible condition. 16 17 18 19 VIII. Service A. General. Inspection and service should be conducted 5. Using flashlight, examine all flue passageways. annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figure 17. a. If passageways are free of soot and obstruction, replace canopy, secure and seal using kit available from Burnham Distributors, Part No. 6111716. b. If passageways need cleaning, remove burners as described in Paragraph F below. Using long handle wire or bristle flue brush and vacuum, brush flueways thoroughly from top of boiler as illustrated in Figure 19. Replace canopy and seal using kit available from Burnham Distributors, Part No. 6111716. CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. B. Inspect Housekeeping. Boiler area must be clear and WARNING free from combustible materials, gasoline and other flammable vapors and liquids. Remove obstructions to the flow of combustion and ventilation air. Canopy must be resealed with RTV-732 Silicone Rubber Sealant (500 F Intermittent Duty). C. Service Low water cutoff (if so equipped). Follow 6. Reinstall jacket top panel, vent pipe and vent connector in reverse manner. Reconnect electrical connector to blower. instructions provided with low water cutoff D. Inspect Vent System for obstructions in vent pipe, soot accumulation, deterioration of pipe or joints, and proper support: F. Clean Main Burners and Firebox. 1. To remove burners for cleaning, changing orifice plugs, or repairs: 1. Remove vent connector and vent pipe. See Figure 19. a. Remove jacket Front Panel. 2. Remove all obstructions. Check and clean vent terminal screens. b. Disconnect pilot tubing at gas valve. 3. Remove soot accumulations with wire brush and vacuum. c. Disconnect igniter/sensor cable and ground wire at Ignition Module. 4. Replace deteriorated parts. d. Disconnect Flame Rollout Switch wires. 5. Repair deteriorated joints. See Section V: Venting, Paragraph D.6. e. Remove Burner Access Panel. f. Mark Pilot Main Burner location on Manifold. E. Inspect Boiler Flue Passages for blockage or soot g. Hold burner on throat. Lift slightly to clear orifice. Pull burner from combustion chamber. See Figure 11. Pilot Main Burner can only be removed by lifting at 45° angle after adjacent burner to right is removed. accumulation. See Figure 19. 1. Disconnect vent connector from blower discharge flange. 2. Remove sheet metal screws securing Jacket Top Panel. Lift panel and rotate about relief valve piping until top of boiler is exposed. If piping or wall prevent full rotation of top panel for access to canopy, cut slot into relief valve opening and remove top panel. 2. Brush top of burners with a soft bristle brush. See Figure 19. Vacuum burners. 3. Check orifices. Drilled passageways must be free of lint or dirt. 4. Vacuum tip of Pilot Burner. 3. Disconnect blower connection from wiring harness in vestibule. 5. Clean firebox by vacuuming. Exercise care not to disturb insulation inside base. 4. Remove bolts securing canopy to boiler sections. Cut silastic sealant around base of canopy, pry canopy from boiler sections and remove canopy/ blower assembly from boiler. 6. Install burners by reversing procedure used to remove burners. Burner with pilot assembly must be in same location as original installation. See Table 7. Burners must be properly located on 20 Table 7: Pilot Burner Location Boiler Model Main Burner with 60 Pilot Bracket * Pilot Burner Located Between Main Burners * 203PV 1 1&2 204PV 2 2&3 205PV 3 3&4 206PV 4 4&5 Figure 18: Spark Gap Setting * Main burners numbered left to right as viewed from front of boiler support bracket at rear of burner. See Figure 11. Slide burner over orifice. 7. Reconnect pilot gas supply, igniter/sensor cable, and ground wire. Reinstall Burner Access Panel. Reconnect Flame Rollout Switch wires. G. Check operation. Follow steps D through O from Section VII: System Start-up. H. Removal or replacement of pilot assembly or pilot assembly parts. If pilot assembly, sensor or pilot orifice need replacing, remove main burner with pilot using procedure described in Paragraph F.1. 1. To replace orifice. a. Disconnect pilot tubing. Pilot orifices screw into Pilot Burner. Replace with Honeywell 388146NE (Natural Gas) or Honeywell 388146KP (LP/Propane). b. Reconnect pilot tubing and check for leaks. 2. To adjust or check spark gap between electrode and hood on Honeywell Q348A intermittent pilot. See Figure 18. a. Use round wire gauge to check spark gap. b. Spark gap should be 1/8 inch for optimum performance. 3. To replace complete pilot assembly. a. Remove two machine screws holding pilot burner to pilot bracket. b. Disconnect pilot tubing. c. Disconnect all other leads to pilot. d. Select pilot assembly with identical model number, reconnect leads and pilot tubing. Resecure to pilot bracket. 4. Reinstall main burner following procedure described in Paragraph F. Figure 19: Flueway Cleaning 21 Table 8: Minimum Suction Pressure Boiler Model Minimum Suction Pressure 203PV -0.50 inches w.c. 204PV -0.50 inches w.c. 205PV -0.80 inches w.c. 206PV -0.80 inches w.c. I. Lubrication. There are no parts requiring lubrication by service technician or owner. Circulator bearings are water lubricated. Blower motor bearings are factory sealed. Figure 20: Procedure for Measuring Fan Suction Pressure 22 IX. Repair Parts All Series 2PV Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed below. B urnh am Corpo rati on Regional Offices A. B urnham Cor poration - Centr al & Wes tern R egio ns C. Burnham Corporation - M etropolitan Region P.O. Box 3079 P.O. Box 3079 La ncast er, PA 17604 -3079 Lancas ter, PA 17604-3079 P hone: (717) 481 -8400 Phone: (717) 481-8400 FAX : (717) 481 -8408 FA X: (717) 481-8409 B. B urnham S ales Cor poration - Nort heast Region 19 -27 M yst ic Av enue Som erv ille, M A 02145 P hone: (617) 625 -9735 FAX : (617) 625 -9736 D. B urnham Co rporat ion - Mid-A tlant ic Region P.O. Box 3079 La ncast er, PA 17604 -3079 P hone: (717) 481 -8400 FAX : (717) 481 -8409 Contact Regional Office Indicat ed f or y our S tate Al abam a A Ne bra ska A Oreg on A Ala ska A N eva da A P enns yl van ia D Arizo na A New Ha mps hire B Rh ode Isla nd B Arkan sas A Ne w Jersey S outh Caroli na A Cal iforn ia A Atlan tic, Burlin gton, Camd en, S outh Dakota A Col ora do A Ca pe May, C umbe rla nd, Tennes s ee A Conn ecticut B Glou cester, M erc er, Te xas A Del aware D Monm outh, Oce an, S ale m Utah A Fl ori da A Co unties Ve rm ont B Ge org ia A A ll other Co unties Hawa ii A New Mexico Ida ho A Ne w York Ill inois A Alb any, Fulton , M ontgom ery, India na A Re nss ela er, S ara to ga, D C A Virgin ia Arling to n,Acco mac k,Cl arke, Fairfax,Frederick,Fauq uier, D Lo udoun ,North ampto n a nd Prince Wil liam Co unties B Io wa A S ch enec tady, S cho harie, Kan sas A Warre n, Was hingto n Co unties K entuc ky A All Other Co unties Loui sia na A Mai ne A ll other Co unties A Was hing ton A C Wash ington , D.C. D N orth Caroli na A West Virgin ia D B No rth Dak ota A Wisc onsin A M aryla nd D Oh io Wyomi ng A Ma ss ach use tts B A th ens , B elm ont, Gall ia, Michig an A J effe rson, Lawrenc e, M eig s, Min nes ota A Mo nro e, an d Was hing ton M issis sip pi A Co unties M iss ouri A A ll other Co unties Monta na A Cana da A D Okl ahom a A A 23 1. Section Assembly ............................... 25 2. Canopy/Blower Assembly .................. 25 3. Base Assembly Group ........................ 26 4. Manifold and Main Burners ............... 27 5. Pilot Burner and Gas Valve ............... 28 6. Jacket .................................................. 29 7. Miscellaneous Trim and Controls ...... 31 8. Vent Accessory Carton ....................... 31 SERVICE SCHEDULE DATE SERVICE PERFORMED 24 Key No. [Quantity] Part Number Descr iption 1. Section Assembly 203PV 204PV 205PV 206PV 617 170321 617 170421 617 170521 617 170621 2. Canopy/Blower Assembly 2A Cano py [1] 61117034 [1] 61117044 [1] 61117054 [1] 61117064 2B Carriage Bolt, …-20 x 1" 2C Wash er, …, SA E 2D Nut,…-20, Heav y Hex 2E Blower Mou ntin g Gasket [Inc luded in Key No. 2F] [1] 8 206048 [1] 8 206049 2F Blo wer [1] 6111714 [1] 6111715 2G Orific e Plate Gas ket [(2) Inc luded in Key No. 2F] [2] 8 206042 [2] 8 206035 2H Orifice Plate 2J Pressure Fitting, Dwy er A 308 2K Hex Nut, 1/4-20, B rass [(4) Included in Key No. 2F] 2L Hex Loc knut, …-20 2M Flue B affle [2] Common Hardwa re [10] Common Hardwa re [2] Common Hardwa re [1] 71117035 [1] 71117045 [1] 71117055 [1] 71117065 [1] 822657 [4] 80 860424 [4] Common Hardwa re No t Applicable 25 Key No. [Quantity] Part Number Description 203PV 204PV 205PV 206PV Bas e A ssem bly, Complete [1] 618 600391 [1] 618 600491 [1] 618 600591 [1] 618 600691 3A Base Tray Assemb ly [1] 718 600391 [1] 718 600491 [1] 718 600591 [1] 718 600691 3B Ba se Wrapp er [1] 7186 00311 [1] 7186 00411 [1] 7186 00511 [1] 7186 00611 3B1 B ase End Insulation 3B2 B ase Rear Ins ulation 3C 3. Base Assembly Group 3 [2] 720601 [1] 72 060035 [1] 72 060045 [1] 72 060055 [1] 72 060065 Ba se Fr ont Panel As semb ly [1] 618 600341 [1] 618 600441 [1] 618 600541 [1] 618 600641 3D Burner Tray [1] 718 600305 [1] 718 600405 [1] 718 600505 [1] 718 600605 3E Base Leg Assemb ly 3E1 B ase Leg 3E2 Nylo n Glide [4] 6 186001 [4] 71 860021 8 186006 3F Bu rner Ac cess P anel [1] 718 600361 [1] 718 600461 [1] 718 600561 3G J ack et Attachme nt Bracket, Le ft [1] 704 60011 3H Jac ket A ttac hment B rac ket, Right [1] 70 460012 3J Cerafelt Gas ket, ‰" x 2" Johns-Mans ville CRF-400 3K Scr ew, S elf-Ta pping Ty pe F, Phill ips Pan Head, …-20 x ‰", Plated 3L Sc rew, Self Tapping, 5/16-18 x 1…" 3M Washer, 5/16, US S [4] Common Hardwa re 3N Washer, Loc k, US S [4] Common Hardwa re 3P Nut, Hex, 5/16-18, B ras s 3R Sc rew, S heet M etal , Phillips Head, #8 x ‰" [1] 6 206002 [20] 80 860700 [4] 80 860717 [4] 80 860403 [2] Common Hardwa re 26 [1] 718 600661 [ Quant ity] Part Num ber K ey No. Description 203PV 204PV 205PV 206PV [2] 8 236099 [4] 8 236099 [6] 8 236099 [8] 8 236099 4 . Ma n ifo ld a n d Ma in Bu rn e rs 4A Main Burn er 4B Mai n Bur ner with 60 Pilot Brac ket 4C M anifold [1] 8 236098 [1] 82 260033 [1] 82 260043 [1] 82 260053 [1] 82 260063 4D (Natural Ga s Only ) Main Burner Orifice, #44, Orange 4D (LP/Propane Only ) Main Burner Orifice, #55 , Green 4E S crew, Ma chine, #1 0-32 x 3/16" [2] 80 860800 4F Scr ew, S elf-Ta pping Ty pe F, Phill ips Pan Head, 1/4-20 x 1/2", Plated [4] 80 860700 M ain B urner Orific e, #45, Pi nk Main Burner Or ifi ce, 1.25mm , Purple 27 [3] 822712 ----- ----- ----- ----- [5] 8 22711 [7] 8 22711 [9] 8 22711 [3] 822708 ----- ----- ----- ----- [5] 822705 [7] 822705 [9] 822705 [Quantity] Part Number Key Des cription No. 203PV 204PV 205PV 206PV 5 . Pi lo t Bu r n e r a nd G a s Va l v e P ilo t A sse mb ly, N atural Ga s, Ho ney we ll Q34 8A133 3 [1] 8 236104 Pil ot As sem bly, LP Ga s, Ho ney we ll Q34 8A 134 1 [1] 8 236107 5A P ilo t Or ifi ce , N atural Ga s Ho neywe ll 38 814 6NE 5B Incl uded with Key No.5A Pi lo t Or ific e, L P/P ro pan e Hon ey wel l 388 146 KP 5C Co mp re ssio n Nut/Fi tting , 1 /8" OD x … NP T 5D Pi lot Tu bin g, 1/8 " OD x 3 0" Included with Key No.5A and 5E [1] 82 36110 Gas Va lv e, ‰ x ‰, Natura l Ga s, Ho ney we ll V R82 04C 600 0 [1] 81 660176 Gas Va lv e, ‰ x ‰, LP/Pr opa ne, Ho neywe ll V R82 04C 601 8 [1] 81 660180 5E 5F Ig nite r/S en so r Ca ble , 3 6", Hon ey wel l 394 800 -3 6 [1] 8 236084 5G Gr ound Wire As semb ly [1] 6 136054 28 Key No. [ Quant ity] Part Number Description 203PV 204PV 205PV 206PV [1] 604 170312 [1] 604 170412 [1] 604 170512 [1] 604 170612 6. Jacket 6A Jac ket Wrap-A-Rou nd Pan el (1) 6B Jac ket Uppe r Ves tibu le Pan el (1) [1] 6041 703221 [1] 6041 704221 [1] 6041 705221 [1] 6041 706221 6C Ja cket Lower Ves tibule P anel [1] 6041 703222 [1] 6041 704222 [1] 6041 705222 [1] 6041 706222 6D J ack et Top Panel (1) (2) [1] 604 170334 [1] 604 170434 [1] 604 170534 [1] 604 170634 6E Jac ket Fr ont Remov able Do or [1] 604 170344 [1] 604 170444 [1] 604 170544 [1] 604 170644 6F Jack et Lower Front P anel [1] 604 170313 [1] 604 170413 [1] 604 170513 [1] 604 170613 6G Screw, S heet M etal, #8 x ‰" 6H S nap B ushing , Heyc o SB -1093-15 [2] 8 136257 6J S nap B ushing , Heyc o SB -2000-26 [1] 8 136266 6K Snap Bushi ng, Heyco S B-437 -5 [1] 8 136048 6L B urnham Logo Plate [20] Common Hardwa re [1] 81 460107 (1) For boilers installed in Canada , indicate ’For Canada’ whe n ord ering. (2) For bo ilers ins tall ed in California, in dicate ’For California’ whe n ord ering. 29 30 [Quantity] Part Number Key No. Description 203PV 204PV 205PV 206PV 7. Miscellaneous Trim and Controls 7A Safety Relief Valve, 30 psi, Conbraco 10-408-05 7B Limit, Honeywell L40 80D1036 7B1 Im mersion Well, ‰ NPT 7B2 Im mersion Well, (Dual Limit Only) 7B3 Lim it Honeywell L4080 B1212 (Dual Limit Only ) 7C Transformer/Relay, Honeywell R82 85D5001 [1] 80 160155U 7C1 Relay, DPS T, Honeywell R82 22U1006 [1] 80 160096U 7C2 Junc tio n Box, 4" x 4" x 1‰" [1] 8 136259 7D Flame Rollout Switch [1] 80 160044 7D1 Flam e Rollout Switch Bracket [1] 7 186018 7E NPT, [1] 81 660319 [1] 80 160156 Included with 7B NPT, Honeywell 1238 70A [1] 80 160426 [1] 80 160474 Suction Pressure S witch [1] 80 160180 [1] 80 160181 Sili cone Tubing, 1/8" x 11" Silicone Tubing, 1/8" x 12‰" 7E1 9016001 (Specify L ength) Silicone Tubing, 1/8" x 13-5 /8" Silicone Tubing, 1/8" x 15…" 7F Ignition Module, Ho neywell S8670E1007 [1] 80 160108 7G Temperatu re-Pres sure Gauge [1] 8 056164U Circu lator with Gaskets, Bell & Gossett NFR-22 [1] 8 056174 Circulator with Gaskets, Grun dfos UP 15-42F [1] 8 056173 Circulator with Ga skets , Taco 007F [1] 8 056170 Circulator with Gaskets, Taco 0010 [1] 8 056176 7H Ga sket, B ell & Gossett NFR-22 (SLC-3 0) [2] 806 602029 Gasket, Grundfos 510179 [2] 806 602016 Gasket, Taco ’00 ’ Seri es [2] 806 602006 7J Flange, 1… NPT [2] 806 602013 7 J1 Screw, Cap Hex Head, 7/16-14 x 1‰" [4] Common Hardwa re 7 J2 Nut, Hex, 7 /16-14 [4] Common Hardwa re 7K Drain Valve, 7H1 NP T, Conbraco 31-606-02 [1] 8066 03011 [Quant ity] Part Num ber K ey No. Description 203PV 8. Vent Accesso ry Carto n 204PV 205PV 611170322 611170522 [1] 8116102 [1] 8116103 8A Vent Connector 8B Vent Terminal [1] 8116063 8C Locking Band [1] 8116101 8D Silico ne Se alant, 3 oz . tube, Dow Corning Silastic 732 RTV, or Sil-Bond RTV 4500 (Ac etoxy) [1] 8 056052 31 206PV 32
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Create Date : 2000:04:06 11:29:55 Producer : Acrobat Distiller 4.0 for Windows Title : 2pv Subject : 2pv Author : SDePugh Creator : Adobe PageMaker 6.52 Modify Date : 2000:04:06 15:45:59-04:00 Page Count : 32 Page Mode : UseOutlinesEXIF Metadata provided by EXIF.tools