Digital Panel Meter DPM1 Series Instructions 3505 HUTCHINSON ROAD CUMMING, GA 30040-5860 Models: DPM1-A-LP Features Configuration Programming Keys (Bottom View) ENTER: Enters configuration and validates data and parameters. SHIFT: Selects mode or shifts blinking digit in configuration. UP: Increases value of blinking digit in configuration. Display configuration Run mode • Loop powered • 4 digit (-1999 to 9999) red LED display • Display scaling or process teaching modes • Selectable decimal point • Configuration for direct or reverse acting linear processes SCAL: InP1 and InP2 values entered manually using programming keys. tEAC: InP1 and InP2 values entered by introducing actual process values. Input signal device must be connected to meter and operational. InP1: Input signal value corresponding to desired display value dSP1. WARNING! Electric shock danger 1. Keep away from high-voltage and high-frequency environment during the installation to prevent interference. Avoid using the device in environments which contain: (a) dust or corrosive gas; (b) high humidity or high radiation; (c) shock or vibration 2. Make sure the input power is switched off when installing or uninstalling the DPM1 to prevent harm to personnel or equipment. 3. Before switching on the input power, check the signal connection, e.g. the input voltage and polarity. Voltage that is too high may cause damage to the DPM1. 4. F ront cover should be cleaned only with a soft cloth soaked in neutral • Total configuration lock out Dimensions and Mounting Fixing clip Err: Error with programmed parameter soap product. DO NOT USE SOLVENTS. DPM1 Meter 24mm SCAL: Manually enter desired value for InP1. tEAC: Drive process to actual value desired for InP1. 2 + (-) 4-20mA loop 2 (+) 4-20mA loop 40mm 48mm . Select desired decimal point position. InP2: Input signal value corresponding to desired display value dSP2. 0.08 to 2.5mm² (28 to 12 AWG) Strip length 8 to 9mm Manufacturer Wago 231-302/026-000 Insertion tool or screwdriver with 0.5 mm x 3.0 mm blade Case Material Press slightly to fasten the clip to the latching slots on the case and get the unit fully assembled and close fitted to achieve a good seal. To remove the instrument from the panel, pull the rear fixing clip latching tabs outwards until they are disengaged, then slide the fixing clip back over the case. Copyright 2016, Automationdirect.com Incorporated/All Rights Reserved Worldwide Polycarbonate UL 94 V-0 Connection Terminal Insertion Tool (included with meter) Insert wires into the proper terminal while using the insertion tool to open the clip inside the connector. Release the insertion tool to fix wire to the terminal. dSP2: Display value cooresponding to InP2. Enter desired value for dSP2. Save values Accuracy (@ 23ºC ±5ºC) Power Supply Voltage Drop on Input Loop Conversion Instructions: DPM1-A-LP 4-20mA ±0.01mA 10Ω Maximum error ±(0.1% of reading ÷3 digits) Temperature coefficient 100 ppm/ºC Warm-Up time 5 minutes Loop powered 4-20 mA <5V Technique Single slope Resolution 16 bits Conversion rate Display 62 times per second Range -1999 to 9999, selectable decimal point position Type 4 digit 10mm (0.4”), red Display refresh rate 2 times per second Display/input overrange indication Environmental Conditions 0vE Operating temperature -10ºC to +60ºC (14ºF to 140ºF) Storage temperature -25ºC to +85ºC (-13ºF to 185ºF) Relative humidity (non-condensing) <95% @ 40ºC (104ºF) Maximum altitude 2000m Frontal protection degree • For additional technical support and questions, call our Technical Support team @ 1-800-633-0405 or 770-844-4200 w Resolution IP65 Environmental Air No corrosive gases permitted Agency Approvals CE DSP 2 display2 entrada1 INP 1 entrada2 INP 2 Run mode Range display1 DSP 1 Input Signal LC 0: Access to programming unlocked. LC 1: Access to programming totally locked Parameter values can be viewed but not changed. Impedance •U se shielded cable for signal wiring. • Cable cross-section must be ≥0.25mm² Additional Help and Support Display Value Technical Specifications This instrument conforms with the following community directives: EMC 2004/108/CE. Refer to the instructions in this insert to preserve safety protections To guarantee electromagnetic compatibility, the following guidelines should followed: escala inversa Input display1 DSP 1 Reverse Acting Process SCAL: Manually enter desired value for InP2. tEAC: Drive process to actual value desired for InP2. For best accuracy InP2 value should be as far from InP1 value as possible CN1 Wire cross section Cage clamp connection To install the instrument, prepare a 45mm x 22mm panel Installation cut-out and slide the unit inwards making sure to place the Dimensions 48 x 24 x 40mm (1/32 DIN) sealing gasket between the front side panel and the front 45 x 22mm Panel Cutout (Max. panel thickness 7mm) bezel. While holding the unit in place, put the fixing clip around case and slide it until it reaches the panel at the rear side. Connector display2 DSP 2 entrada2 entrada1 INP 1 INP 2 Enter desired value for dSP1. Terminal Panel mounting surface Display Value Input Signal CN1 1 Direct Acting Process dSP1: Display value corresponding to InP1. 5 sec. CN1 1 Err: Error with programmed parameter Wiring Terminals Sealing gasket Pro: Programming mode displays if configuration menus are unlocked (LC=0). dAtA: Data mode displays if configuration menus are locked (LC=1). Parameter values can be viewed but not changed. • 48 x 24mm 1/32 DIN • Process (4-20mA DC) WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes. Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation. If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call us at 1-800-633-0405 or 770-844-4200. This publication is based on information that was available at the time it was printed. At Automationdirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without obligation. This publication may also discuss features that may not be available in certain revisions of the product. Notes Model DPM1-A-LP Example Application: 4-20mA input, 0.0 to 100.0 display (direct acting process using Scale Mode) Programming Keys (Bottom View) ENTER: Enters configuration and validates data and parameters. SHIFT: Selects mode or shifts blinking digit in configuration. UP: Increases value of blinking digit in configuration. Direct Acting Process Run mode DSP 2 100.0 Display Value Programming mode Display configuration InP1 and InP2 values entered manually using programming keys. Input signal value corresponding to desired display value dSP1. Manually enter desired value for InP1. 4mA for this example Display value corresponding to InP1. Enter desired value for dSP1. 0 for this example . Select desired decimal point position. xxx.x for this example Input signal value corresponding to desired display value dSP2. . Manually enter desired value for InP2. 20 mA for this example Display value corresponding to InP2. . Enter desired value for dSP2. 100.0 for this example Save values DSP 1 0.0 INP 1 4.0 mA INP 2 20.0 mA Input Signal Run mode Instructions: DPM1-A-LP P.2
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.7 Linearized : Yes Create Date : 2016:04:01 06:57:02-04:00 Creator : Adobe InDesign CC 2014 (Windows) Modify Date : 2016:04:01 06:58:18-04:00 Tagged PDF : Yes XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Metadata Date : 2016:04:01 06:58:18-04:00 Creator Tool : Adobe InDesign CC 2014 (Windows) Instance ID : uuid:2a682097-62a5-41fb-92ae-7ec1251a4d47 Original Document ID : xmp.did:dbf6b666-790d-244a-809c-d20c2f4b2240 Document ID : xmp.id:9b7d6cf0-5769-924c-945b-92e0900c315f Rendition Class : proof:pdf Derived From Instance ID : xmp.iid:4a26be6d-6adc-4f42-9c0a-80246514881b Derived From Document ID : xmp.did:29b375a8-dd32-6146-950e-6cac0c54b048 Derived From Original Document ID: xmp.did:dbf6b666-790d-244a-809c-d20c2f4b2240 Derived From Rendition Class : default History Action : converted History Parameters : from application/x-indesign to application/pdf History Software Agent : Adobe InDesign CC 2014 (Windows) History Changed : / History When : 2016:04:01 06:57:02-04:00 Format : application/pdf Producer : Adobe PDF Library 11.0 Trapped : False Page Count : 2EXIF Metadata provided by EXIF.tools