Sm580j 01 580J*04 12
User Manual: 580J*04--12
Open the PDF directly: View PDF .
Page Count: 73
Download | |
Open PDF In Browser | View PDF |
580J*04--12 NOMINAL 3 TO 10 TONS WITH PURONr (R--410A) REFRIGERANT Service and Maintenance Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1 UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . 2 SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . 4 COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 PURONR (R-- 410A) REFRIGERANT . . . . . . . . . . . . . . 8 COOLING CHARGING CHARTS . . . . . . . . . . . . . . . . . 9 CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . 15 SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . . 16 SENSOR AND CONTROLLER TESTS . . . . . . . . . . . 19 PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . 22 GAS HEATING SYSTEM . . . . . . . . . . . . . . . . . . . . . . 23 ECONOMIZER SYSTEMS . . . . . . . . . . . . . . . . . . . . . 33 PRE START-- UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 START-- UP, GENERAL . . . . . . . . . . . . . . . . . . . . . . . . 42 OPERATING SEQUENCES . . . . . . . . . . . . . . . . . . . . . 43 FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . 45 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . 46 APPENDIX I. MODEL NUMBER SIGNIFICANCE . 48 APPENDIX II. PHYSICAL DATA . . . . . . . . . . . . . . . . 49 APPENDIX III. FAN PERFORMANCE . . . . . . . . . . . 55 APPENDIX IV. ELECTRICAL DATA . . . . . . . . . . . . . 65 APPENDIX V. WIRING DIAGRAM LIST . . . . . . . . . 70 APPENDIX VI. MOTORMASTER SENSOR LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . . 73 SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filters. Trained service personnel should perform all other operations. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-- alert . When you see this symbol on the unit and in symbol instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. ! WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Refer to the User’s Information Manual provided with this unit for more details. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. What to do if you smell gas: DO NOT try to light any appliance. DO NOT touch any electrical switch, or use any phone in your building. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department. ! WARNING FILTER ACCESS PANEL ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock and rotating equipment could cause injury. 580J ! COMPRESSOR ACCESS PANEL (04-07 only) OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL WARNING Fig. 1 - Typical Access Panel Locations ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-- out this switch, if necessary. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. Puron (R-- 410A) refrigerant systems operate at higher pressures than standard R-- 22 systems. Do not use R-- 22 service equipment or components on Puron refrigerant equipment. ! WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s). C08449 BLOWER ACCESS PANEL CONTROL BOX COMPRESSOR (08-12 only) Fig. 2 - Blower Access Panel Location C08450 Routine Maintenance These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: Quarterly Inspection (and 30 days after initial start) S Return air filter replacement S Outdoor hood inlet filters cleaned S Belt tension checked S Belt condition checked S Pulley alignment checked S Fan shaft bearing locking collar tightness checked S Condenser coil cleanliness checked S Condensate drain checked Seasonal Maintenance UNIT ARRANGEMENT AND ACCESS General Fig. 1 and Fig. 2 show general unit arrangement and access locations. These items should be checked at the beginning of each season (or more often if local conditions and usage patterns dictate): Air Conditioning S Condenser fan motor mounting bolts tightness S Compressor mounting bolts S Condenser fan blade positioning S Control box cleanliness and wiring condition 2 S Wire terminal tightness S Refrigerant charge level S Evaporator coil cleaning S Evaporator blower motor amperage Heating washing with hot low-- pressure water and soft detergent and replace all screens before restarting the unit. Observe the flow direction arrows on the side of each filter frame. Economizer Inlet Air Screen This air screen is retained by spring clips under the top edge of the hood. (See Fig. 3.) S Heat exchanger flue passageways cleanliness 17 1/4” S Gas burner condition S Gas manifold pressure S Heating temperature rise Economizer or Outside Air Damper S Inlet filters condition DIVIDER S Check damper travel (economizer) S Check gear and dampers for debris and dirt HOOD Air Filters and Screens CLEANABLE ALUMINUM FILTER Each unit is equipped with return air filters. If the unit has an economizer, it will also have an outside air screen. If a manual outside air damper is added, an inlet air screen will also be present. Return air filters are disposable fiberglass media type. Access to the filters is through the small lift-- out panel located on the rear side of the unit, above the evaporator/return air access panel. (See Fig. 1.) To remove the filters: 1. Grasp the bottom flange of the upper panel. 2. Lift up and swing the bottom out until the panel disengages and pulls out. 3. Reach inside and extract the filters from the filter rack. 4. Replace these filters as required with similar replacement filters of same size. FILTER BAROMETRIC RELIEF FILTER CLIP Each of these filters and screens will need to be periodically replaced or cleaned. Return Air Filters 580J OUTSIDE AIR Fig. 3 - Filter Installation C06027 To remove the filter, open the spring clips. Re-- install the filter by placing the frame in its track, then closing the spring clips. Manual Outside Air Hood Screen This inlet screen is secured by a retainer angle across the top edge of the hood. (See Fig. 4.) To re-- install the access panel: 1. Slide the top of the panel up under the unit top panel. 2. Slide the bottom into the side channels. 3. Push the bottom flange down until it contacts the top of the lower panel (or economizer top). IMPORTANT: DO NOT OPERATE THE UNIT WITHOUT THESE FILTERS! Outside Air Hood Outside air hood inlet screens are permanent aluminum-- mesh type filters. Check these for cleanliness. Remove the screens when cleaning is required. Clean by C07156 Fig. 4 - Screens Installed on Outdoor-- Air Hood (Sizes 7-- 1/2 to 12-- 1/2 Tons Shown) To remove the screen, loosen the screws in the top retainer and slip the retainer up until the filter can be removed. 3 Re-- install by placing the frame in its track, rotating the retainer back down and tighten all screws. SUPPLY FAN (BLOWER) SECTION ! WARNING 580J ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on the fan system, shut off all unit power and tag-- out the unit disconnect switch. Do not reach into the fan section with power still applied to unit. Supply Fan (Belt--Drive) The supply fan system consists of a forward-- curved centrifugal blower wheel on a solid shaft with two concentric type bearings, one on each side of the blower housing. A fixed-- pitch driven pulley is attached to the fan shaft and an adjustable-- pitch driver pulley is on the motor. The pulleys are connected using a “V” type belt. (See Fig. 5.) Fig. 5 - Belt Drive Motor Mounting C07087 Belt Check the belt condition and tension quarterly. Inspect the belt for signs of cracking, fraying or glazing along the inside surfaces. Check belt tension by using a spring-- force tool (such as Browning’s Part Number “Belt Tension Checker” or equivalent tool); tension should be 6-- lbs at a 5/8-- in. deflection when measured at the centerline of the belt span. This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft. new belt, do not use a tool (screwdriver or pry-- bar) to force the belt over the pulley flanges, this will stress the belt and cause a reduction in belt life. 2. Loosen the motor mounting plate front bolts and rear bolts. 3. Push the motor and its mounting plate towards the blower housing as close as possible to reduce the center distance between fan shaft and motor shaft. 4. Remove the belt by gently lifting the old belt over one of the pulleys. 5. Install the new belt by gently sliding the belt over both pulleys and then sliding the motor and plate away from the fan housing until proper tension is achieved. 6. Check the alignment of the pulleys, adjust if necessary. 7. Tighten all bolts. 8. Check the tension after a few hours of runtime and re-- adjust as required. Adjustable-- Pitch Pulley on Motor The motor pulley is an adjustable-- pitch type that allows a servicer to implement changes in the fan wheel speed to match as-- installed ductwork systems. The pulley consists of a fixed flange side that faces the motor (secured to the motor shaft) and a movable flange side that can be rotated around the fixed flange side that increases or reduces the pitch diameter of this driver pulley. (See Fig. 6.) As the pitch diameter is changed by adjusting the position of the movable flange, the centerline on this pulley shifts laterally (along the motor shaft). This creates a requirement for a realignment of the pulleys after any adjustment of the movable flange. Also reset the belt tension after each realignment. Check the condition of the motor pulley for signs of wear. Glazing of the belt contact surfaces and erosion on these surfaces are signs of improper belt tension and/or belt slippage. Pulley replacement may be necessary. To change fan speed: 1. Shut off unit power supply. 2. Loosen belt by loosening fan motor mounting nuts. (See Fig. 5.) 3. Loosen movable pulley flange setscrew. (See Fig. 6.) 4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified. 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew to torque specifications. NOTE: Without the spring-- tension tool, place a straight edge across the belt surface at the pulleys, then deflect the belt at mid-- span using one finger to a 1/2-- in. deflection. Adjust belt tension by loosening the motor mounting plate front bolts and rear bolt and sliding the plate toward the fan (to reduce tension) or away from fan (to increase tension). Ensure the blower shaft and the motor shaft are parallel to each other (pulleys aligned). Tighten all bolts when finished. To align fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting. 3. Tighten fan pulley setscrews and motor mounting bolts to torque specifications. 4. Recheck belt tension. To replace the belt: 1. Use a belt with same section type or similar size. Do not substitute a “FHP” type belt. When installing the 4 Before changing pulleys to increase fan wheel speed, check the fan performance at the target speed and airflow rate to determine new motor loading (bhp). Use the fan performance tables or use the Packaged Rooftop Builder software program. Confirm that the motor in this unit is capable of operating at the new operating condition. Fan shaft loading increases dramatically as wheel speed is increased. To reduce vibration, replace the motor’s adjustable pitch pulley with a fixed pitch pulley (after the final airflow balance adjustment). This will reduce the amount of vibration generated by the motor/belt-- drive system. ! Bearings WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. This system uses PuronR refrigerant which has higher pressures than R-- 22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer. This fan system uses bearings featuring concentric split locking collars. The collars are tightened through a cap screw bridging the split portion of the collar. The cap screw has a Torx T25 socket head. To tighten the locking collar: Hold the locking collar tightly against the inner race of the bearing and torque the cap screw to 65-- 70 in-- lb (7.4-- 7.9 Nm). See Fig. 7. Condenser Coil The condenser coil is fabricated with round tube copper hairpins and plate fins of various materials and/or coatings (see Model Number Format in the Appendix to identify the materials provided in this unit). The coil may be one-- row or composite-- type two-- row. Composite two-- row coils are two single-- row coils fabricated with a single return bend end tubesheet. Fig. 7 - Tightening Locking Collar C08121 Motor When replacing the motor, also replace the external-- tooth lock washer (star washer) under the motor mounting base; this is part of the motor grounding system. Ensure the teeth on the lock washer are in contact with the motor’s painted base. Tighten motor mounting bolts to 120 +/-- 12 in-- lbs. Changing fan wheel speed by changing pulleys: The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units). Do not install a replacement motor pulley with a smaller pitch diameter than provided on the original factory pulley. Change fan wheel speed by changing the fan pulley (larger pitch diameter to reduce wheel speed, smaller pitch diameter to increase wheel speed) or select a new system (both pulleys and matching belt(s)). Condenser Coil Maintenance and Cleaning Recommendation Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil. Remove Surface Loaded Fibers Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-- metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins. NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more 5 580J Fig. 6 - Supply-- Fan Pulley Adjustment COOLING C07075 difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse. Periodic Clean Water Rinse 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 7. Secure inner and outer coil rows together with a field-- supplied fastener. 8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws. A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with a very low velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended. 580J Routine Cleaning of Coil Surfaces Periodic cleaning with TotalineR environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from Bryant Replacement Components Division as part number P902-- 0301 for a one gallon container, and part number P902-- 0305 for a 5 gallon container. It is recommended that all coils, including standard aluminum, pre-- coated, copper/copper or E-- coated coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment. Fig. 8 - Cleaning Condenser Coil C08205 Avoid use of: S coil brighteners S acid cleaning prior to painting S high pressure washers S poor quality water for cleaning Totaline environmentally sound coil cleaner is nonflammable, hypo allergenic, non bacterial, and a USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non-- recommended coil cleaners is strongly discouraged since coil and unit durability could be affected. Fig. 9 - Propping Up Top Panel C08206 One-- Row Coil Wash coil with commercial coil cleaner. It is not necessary to remove top panel. Two-- Row Coils Clean coil as follows: 1. Turn off unit power, tag disconnect. 2. Remove top panel screws on condenser end of unit. 3. Remove condenser coil corner post. See Fig. 8. To hold top panel open, place coil corner post between top panel and center post. See Fig. 9. 4. Remove screws securing coil to compressor plate and compressor access panel. 5. Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 10. Fig. 10 - Separating Coil Sections Totaline Environmentally Sound Coil Cleaner Application Equipment S 2-- 1/2 gallon garden sprayer S Water rinse with low velocity spray nozzle 6 C08207 CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in accelerated corrosion of unit parts. Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner. ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in reduced unit performance or unit shutdown. High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. Totaline Environmentally Sound Coil Cleaner Application Instructions 1. Proper eye protection such as safety glasses is recommended during mixing and application. 2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above. 3. Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins. 4. Mix Totaline environmentally sound coil cleaner in a 2-- 1/2 gallon garden sprayer according to the instructions included with the cleaner. The optimum solution temperature is 100_F. NOTE: Do NOT USE water in excess of 130_F, as the enzymatic activity will be destroyed. 5. Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers. 6. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-- and-- down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage. 7. Ensure cleaner thoroughly penetrates deep into finned areas. 8. Interior and exterior finned areas must be thoroughly cleaned. 9. Finned surfaces should remain wet with cleaning solution for 10 minutes. 10. Ensure surfaces are not allowed to dry before rinsing. Reapplying cleaner as needed to ensure 10-- minute saturation is achieved. 11. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle. Evaporator Coil Cleaning the Evaporator Coil 1. Turn unit power off. Install lockout tag. Remove evaporator coil access panel. 2. If economizer or two-- position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws. 3. Slide filters out of unit. 4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-- flush toward return-- air section to remove foreign material. Flush condensate pan after completion. 5. Reinstall economizer and filters. 6. Reconnect wiring. 7. Replace access panels. Evaporator Coil Metering Devices The metering devices are multiple fixed-- bore devices (Acutrolt) swedged into the horizontal outlet tubes from the liquid header, located at the entrance to each evaporator coil circuit path. These are non-- adjustable. Service requires replacing the entire liquid header assembly. To check for possible blockage of one or more of these metering devices, disconnect the supply fan contactor (IFC) coil, then start the compressor and observe the frosting pattern on the face of the evaporator coil. A frost pattern should develop uniformly across the face of the coil starting at each horizontal header tube. Failure to develop frost at an outlet tube can indicate a plugged or a missing orifice. Refrigerant System Pressure Access Ports There are two access ports in the system - on the suction tube near the compressor and on the discharge tube near the compressor. These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4 SAE Male Flare couplings. The brass fittings are two-- piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring-- closed check valve core screwed into the base. (See Fig. 11.) This check valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the check valve core’s bottom o-- ring. Install the fitting body with 96 +/-- 10 in-- lbs of torque; do not overtighten. 7 580J ! SEAT CORE (Part No. EC39EZ067) 1/2-20 UNF RH 0.596 45 o o 30 WASHER O-RING 5/8” HEX .47 DEPRESSOR PER ARI 720 +.01/-.035 FROM FACE OF BODY 1/2" HEX 7/16-20 UNF RH 580J This surface provides a metal to metal seal when torqued into the seat. Appropriate handling is required to not scratch or dent the surface. C08453 Fig. 11 - CoreMax Access Port Assembly PURONR (R--410A) REFRIGERANT This unit is designed for use with Puron (R-- 410A) refrigerant. Do not use any other refrigerant in this system. Puron (R-- 410A) is provided in pink (rose) colored cylinders. These cylinders are available with and without dip tubes; cylinders with dip tubes will have a label indicating this feature. For a cylinder with a dip tube, place the cylinder in the upright position (access valve at the top) when removing liquid refrigerant for charging. For a cylinder without a dip tube, invert the cylinder (access valve on the bottom) when removing liquid refrigerant. Because Puron (R-- 410A) is a blend, it is strongly recommended that refrigerant always be removed from the cylinder as a liquid. Admit liquid refrigerant into the system in the discharge line. If adding refrigerant into the suction line, use a commercial metering/expansion device at the gauge manifold; remove liquid from the cylinder, pass it through the metering device at the gauge set and then pass it into the suction line as a vapor. Do not remove Puron (R-- 410A) from the cylinder as a vapor. Refrigerant Charge Amount of refrigerant charge is listed on the unit’s nameplate. Refer to GTAC2-- 5 Charging, Recovery, Recycling and Reclamation training manual and the following procedures. required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-- air cfm must be within the normal operating range of the unit. To Use Cooling Charging Charts Take the outdoor ambient temperature and read the suction pressure gauge. Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted. SIZE DESIGNATION 04A,B,C 05A,B,C 06A,B,C 07A,C 08A,C 09A,C 12A,C NOMINAL TONS REFERENCE 3 4 5 6 7.5 8.5 10 EXAMPLE: Model 580J*04A (3 ton) Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C) Suction Pressure . . . . . . . . . . . . . . . . . 140 psig (965 kPa) Suction Temperature should be . . . . . . . . . . 60_F (16_C) Unit panels must be in place when unit is operating during the charging procedure. No Charge Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant. Low-- Charge Cooling Using Cooling Charging Charts, Fig. 12, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing device are 8 580J COOLING CHARGING CHARTS C08203 Fig. 12 - Cooling Charging Charts 9 C08204 580J COOLING CHARGING CHARTS (cont) C08228 Fig. 12 - Cooling Charging Charts (cont.) 10 C08229 580J COOLING CHARGING CHARTS (cont.) C08437 Fig. 12 - Cooling Charging Charts (cont.) 11 C08438 580J COOLING CHARGING CHARTS (cont.) C08439 Fig. 12 - Cooling Charging Charts (cont.) 12 Compressor The suction and discharge pressure levels should now move to their normal start-- up levels. The compressor is charged with the correct amount of oil at the factory. ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to components. The compressor is in a PuronR refrigerant system and uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere. NOTE: When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling. Filter Drier Replace whenever refrigerant system is exposed to atmosphere. Only use factory specified liquid-- line filter driers with working pressures no less than 650 psig. Do not install a suction-- line filter drier in liquid line. A liquid-- line filter drier designed for use with Puron refrigerant is required on every unit. Condenser--Fan Location See Fig. 13. 1. Shut off unit power supply. Install lockout tag. 2. Remove condenser-- fan assembly (grille, motor, and fan). 3. Loosen fan hub setscrews. 4. Adjust fan height as shown in Fig. 13. 5. Tighten setscrews. 6. Replace condenser-- fan assembly. Replacing Compressor The compressor used with Puron refrigerant contains a POE oil. This oil has a high affinity for moisture. Do not remove the compressor’s tube plugs until ready to insert the unit suction and discharge tube ends. Compressor mounting bolt torque is 65-- 75 ft-- lbs. Compressor Rotation On 3-- phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gauges to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-- up. NOTE: If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 4. Note that the evaporator fan is probably also rotating in the wrong direction. 5. Turn off power to the unit. 6. Reverse any two of the unit power leads. 7. Reapply power to the compressor. Conduit 0.14 in + 0.0 / -0.03 Fig. 13 - Condenser Fan Adjustment C08448 Troubleshooting Cooling System Refer to Table 1 for additional troubleshooting topics. 13 580J Lubrication Table 1 – Cooling Service Analysis PROBLEM Compressor and Condenser Fan Will Not Start. Compressor Will Not Start But Condenser Fan Runs. CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Faulty wiring or loose connections in compressor circuit. Compressor motor burned out, seized, or internal overload open. Defective run/start capacitor, overload, start relay. 580J One leg of three--- phase power dead. Refrigerant overcharge or undercharge. Compressor Cycles (other than normally satisfying thermostat). Compressor Operates Continuously. Excessive Head Pressure. Head Pressure Too Low. Excessive Suction Pressure. Suction Pressure Too Low. Evaporator Fan Will Not Shut Off. Compressor Makes Excessive Noise. Defective compressor. Insufficient line voltage. Blocked condenser. Defective run/start capacitor, overload, or start relay. Defective thermostat. Faulty condenser--- fan motor or capacitor. Restriction in refrigerant system. Dirty air filter. Unit undersized for load. Thermostat set too low. Low refrigerant charge. Leaking valves in compressor. Air in system. Condenser coil dirty or restricted. Dirty air filter. Dirty condenser coil. Refrigerant overcharged. Air in system. Condenser air restricted or air short--- cycling. Low refrigerant charge. Compressor valves leaking. Restriction in liquid tube. High head load. Compressor valves leaking. Refrigerant overcharged. Dirty air filter. Low refrigerant charge. Metering device or low side restricted. REMEDY Call power company. Replace fuse or reset circuit breaker. Replace component. Determine cause and correct. Check wiring diagram and rewire correctly. Lower thermostat setting below room temperature. Check wiring and repair or replace. Determine cause. Replace compressor. Determine cause and replace. Replace fuse or reset circuit breaker. Determine cause. Recover refrigerant, evacuate system, and recharge to nameplate. Replace and determine cause. Determine cause and correct. Determine cause and correct. Determine cause and replace. Temperature too low in conditioned area. Outdoor ambient below 25˚F. Replace thermostat. Replace. Locate restriction and remove. Replace filter. Decrease load or increase unit size. Reset thermostat. Locate leak; repair and recharge. Replace compressor. Recover refrigerant, evacuate system, and recharge. Clean coil or remove restriction. Replace filter. Clean coil. Recover excess refrigerant. Recover refrigerant, evacuate system, and recharge. Determine cause and correct. Check for leaks; repair and recharge. Replace compressor. Remove restriction. Check for source and eliminate. Replace compressor. Recover excess refrigerant. Replace filter. Check for leaks; repair and recharge. Remove source of restriction. Increase air quantity. Check filter and replace if necessary. Reset thermostat. Install low--- ambient kit. Time off delay not finished. Wait for 30--- second off delay. Compressor rotating in wrong direction. Reverse the 3--- phase power leads. Insufficient evaporator airflow. 14 CONVENIENCE OUTLETS ! when the unit disconnect or HACR switch is open. See Fig. 15. WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-- out this switch, if necessary. 580J Two types of convenience outlets are offered on 580J models: Non-- powered and unit-- powered. Both types provide a 125-- volt GFCI (ground-- fault circuit-- interrupter) duplex receptacle rated at 15-- A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 14. CO8283 Fig. 15 - Powered Convenience Outlet Wiring Pwd-CO Transformer Conv Outlet GFCI Pwd-CO Fuse Switch Fig. 14 - Convenience Outlet Location C08128 Non-- powered type: This type requires the field installation of a general-- purpose 125-- volt 15-- A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-- v power supply conductors into the bottom of the utility box containing the duplex receptacle. Unit-- powered type: A unit-- mounted transformer is factory-- installed to stepdown the main power supply voltage to the unit to 115-- v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 14. The primary leads to the convenience outlet transformer are not factory-- connected. Selection of primary power source is a customer-- option. If local codes permit, the transformer primary leads can be connected at the line-- side terminals on a unit-- mounted non-- fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-- energized UNIT VOLTAGE 208, 230 CONNECT AS 460 480 575 600 240 PRIMARY CONNECTIONS L1: RED +YEL L2: BLU + GRA L1: RED Splice BLU + YEL L2: GRA L1: RED L2: GRA TRANSFORMER TERMINALS H1 + H3 H2 + H4 H1 H2 + H3 H4 H1 H2 Duty Cycle: The unit-- powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-- amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-- amps (i.e., limit loads exceeding 8-- amps to 30 minutes of operation every hour). Maintenance: Periodically test the GFCI receptacle by pressing the TEST button on the face of the receptacle. This should cause the internal circuit of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition. Fuse on powered type: The factory fuse is a Bussman “Fusetron” T-- 15, non-- renewable screw-- in (Edison base) type plug fuse. Using unit-- mounted convenience outlets: Units with unit-- mounted convenience outlet circuits will often require that two disconnects be opened to de-- energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-- energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets. 15 SMOKE DETECTORS Sensor Smoke detectors are available as factory-- installed options on 580J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-- provided and mounted. The unit is factory-- configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements. 580J System The sensor (see Fig. 17) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left-- side of the housing). The smoke detector system consists of a four-- wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device. Duct smoke sensor Controller Exhaust tube The controller (see Fig. 16) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face). Exhaust gasket Sensor housing and electronics See Detail A Intake gasket Cover gasket (ordering option) TSD-CO2 (ordering option) Sensor cover Plug Sampling tube (ordered separately) Coupling Detail A Duct smoke sensor controller Conduit nuts (supplied by installer) Magnetic test/reset switch Conduit support plate Alarm Trouble Terminal block cover Controller housing and electronics Power Dirty Cover gasket (ordering option) Fig. 17 - Smoke Detector Sensor Controller cover Conduit couplings (supplied by installer) Fastener (2X) Trouble Alarm Power Test/reset switch Fig. 16 - Controller Assembly C08208 C08209 Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc. The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, 16 For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Smoke Detector Locations Supply Air — The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 18. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-- off filter panel. Return Air with Economizer — The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 20. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-- mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.) 580J such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not. Return Air Sampling Tube C08129 Fig. 20 - Return Air Sampling Tube Location Smoke Detector Sensor C08245 Completing Installation of Return Air Smoke Sensor: Fig. 18 - Typical Supply Air Smoke Detector Sensor Location Screws Return Air without Economizer — The sampling tube is located across the return air opening on the unit basepan. See Fig. 19. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-- mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.) Flexible Exhaust Tubes Sample Tube C08126 Fig. 21 - Return Air Detector Shipping Position 1. Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 21. Save the screws. 2. Remove the Return Air Sensor and its detector plate. 3. Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 22. 4. Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 22. 5. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan. 6. For units with an economizer, the sampling tube is integrated into the economizer housing but the connec- Return Air Detector module (shipping position shown)* Controller module Return Air Detector Sampling Tube *RA detector must be moved from shipping position to operating position by installer C07307 Fig. 19 - Typical Return Air Detector Location 17 tion of the flexible tubing to the sampling tube is the same. condition is detected. See Fig. 23, Smoke Detector Wiring. Highlight A: JMP 3 is factory-- cut, transferring unit control to smoke detector. Highlight B: Smoke detector NC contact set will open on smoke alarm condition, de-- energizing the ORN conductor. Highlight C: 24-- v power signal via ORN lead is removed at Smoke Detector input on LCTB; all unit operations cease immediately. C08127 580J Fig. 22 - Return Air Sensor Operating Position FIOP Smoke Detector Wiring and Response All units: FIOP smoke detector is configured to automatically shut down all unit operations when smoke Using Remote Logic: Five conductors are provided for field use (see Highlight D) for additional annunciation functions. Additional Application Data — Refer to Catalog No. HKRNKA-- 1XA for discussions on additional control features of these smoke detectors including multiple unit coordination. See Fig. 23. B C D A Fig. 23 - Typical Smoke Detector System Wiring 18 C08435 SENSOR AND CONTROLLER TESTS Sensor Alarm Test OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses. The sensor alarm test checks a sensor’s ability to signal an alarm state. This test requires that you use a field provided SD-- MAG test magnet. CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test. Sensor Alarm Test Procedure 1. Hold the test magnet where indicated on the side of the sensor housing for seven seconds. 2. Verify that the sensor’s Alarm LED turns on. 3. Reset the sensor by holding the test magnet against the sensor housing for two seconds. 4. Verify that the sensor’s Alarm LED turns off. Dirty Controller Test Procedure 1. Press the controller’s test/reset switch for two seconds. 2. Verify that the controller’s Trouble LED flashes. Dirty Sensor Test The dirty sensor test provides an indication of the sensor’s ability to compensate for gradual environmental changes. A sensor that can no longer compensate for environmental changes is considered 100% dirty and requires cleaning or replacing. You must use a field provided SD-- MAG test magnet to initiate a sensor dirty test. The sensor’s Dirty LED indicates the results of the dirty test as shown in Table 2. ! OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. Holding the test magnet against the sensor housing for more than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses. Controller Alarm Test The controller alarm test checks the controller’s ability to initiate and indicate an alarm state. ! CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. This test places the duct detector into the alarm state. Disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test. Controller Alarm Test Procedure 1. Press the controller’s test/reset switch for seven seconds. 2. Verify that the controller’s Alarm LED turns on. 3. Reset the sensor by pressing the test/reset switch for two seconds. 4. Verify that the controller’s Alarm LED turns off. CAUTION Table 2 – Dirty LED Test FLASHES DESCRIPTION 1 0--- 25% dirty. (Typical of a newly installed detector) 2 25--- 50% dirty 3 51--- 75% dirty 4 76--- 99% dirty Dirty Sensor Test Procedure 1. Hold the test magnet where indicated on the side of the sensor housing for two seconds. 2. Verify that the sensor’s Dirty LED flashes. ! CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses. Before changing dirty sensor test operation, disconnect all auxiliary equipment from the controller and notify the proper authorities if connected to a fire alarm system. Dirty Controller Test The dirty controller test checks the controller’s ability to initiate a dirty sensor test and indicate its results. 19 580J ! CAUTION ! 580J Changing the Dirt Sensor Test 12 By default, sensor dirty test results are indicated by: S The sensor’s Dirty LED flashing. S The controller’s Trouble LED flashing. S The controller’s supervision relay contacts toggle. The operation of a sensor’s dirty test can be changed so that the controller’s supervision relay is not used to indicate test results. When two detectors are connected to a controller, sensor dirty test operation on both sensors must be configured to operate in the same manner. To Configure the Dirty Sensor Test Operation 1. Hold the test magnet where indicated on the side of the sensor housing until the sensor’s Alarm LED turns on and its Dirty LED flashes twice (approximately 60 seconds). 2. Reset the sensor by removing the test magnet then holding it against the sensor housing again until the sensor’s Alarm LED turns off (approximately 2 seconds). TB3 3 Auxiliary equipment 14 19 Wire must be added by installer SD-TRK4 5 18 Vdc ( +) Power 4 Alarm 15 1 2 3 Reset/Test 20 18 Vdc ( −) 2 C08247 Fig. 24 - Remote Test/Reset Station Connections ! CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. If the test/reset station’s key switch is left in the RESET/TEST position for longer than seven seconds, the detector will automatically go into the alarm state and activate all automatic alarm responses. OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test. The test/reset station dirty sensor test checks the test/reset station’s ability to initiate a sensor dirty test and indicate the results. It must be wired to the controller as shown in Fig. 24 and configured to operate the controller’s supervision relay. For more information, see “Changing sensor dirty test operation.” + Trouble CAUTION Remote Test/Reset Station Dirty Sensor Test − 2 13 The remote station alarm test checks a test/reset station’s ability to initiate and indicate an alarm state. SD-- TRK4 Remote Alarm Test Procedure 1. Turn the key switch to the RESET/TEST position for seven seconds. 2. Verify that the test/reset station’s Alarm LED turns on. 3. Reset the sensor by turning the key switch to the RESET/TEST position for two seconds. 4. Verify that the test/reset station’s Alarm LED turns off. 1 Supervision relay contacts [3] Remote Station Test ! Smoke Detector Controller 1 ! CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. Holding the test magnet to the target area for longer than seven seconds will put the detector into the alarm state and activate all automatic alarm responses. Dirty Sensor Test Using an SD-- TRK4 1. Turn the key switch to the RESET/TEST position for two seconds. 2. Verify that the test/reset station’s Trouble LED flashes. Detector Cleaning Cleaning the Smoke Detector Clean the duct smoke sensor when the Dirty LED is flashing continuously or sooner if conditions warrant. 20 Table 3 – Detector Indicators Magnetic test/reset switch Alarm LED Trouble LED Dirty LED Power LED ! DESCRIPTION Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in the normal state. Indicates the sensor is in the alarm state. Indicates the sensor is in the trouble state. Indicates the amount of environmental compensation used by the sensor (flashing continuously = 100%) Indicates the sensor is energized. CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. If the smoke detector is connected to a fire alarm system, first notify the proper authorities that the detector is undergoing maintenance then disable the relevant circuit to avoid generating a false alarm. 1. Disconnect power from the duct detector then remove the sensor’s cover. (See Fig. 25.) 2. Using a vacuum cleaner, clean compressed air, or a soft bristle brush, remove loose dirt and debris from inside the sensor housing and cover. Use isopropyl alcohol and a lint-- free cloth to remove dirt and other contaminants from the gasket on the sensor’s cover. 3. Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the printed circuit board. 4. Gently remove dirt and debris from around the optic plate and inside the optic housing. 5. Replace the optic housing and sensor cover. 6. Connect power to the duct detector then perform a sensor alarm test. Sampling tube HVAC duct Sensor housing Retainer clip Optic housing Fig. 25 - Sensor Cleaning Diagram S The contacts on the controller’s two auxiliary relays switch positions. S The contacts on the controller’s alarm initiation relay close. S The controller’s remote alarm LED output is activated (turned on). S The controller’s high impedance multiple fan shutdown control line is pulled to ground Trouble state. The SuperDuct duct smoke detector enters the trouble state under the following conditions: S A sensor’s cover is removed and 20 minutes pass before it is properly secured. S A sensor’s environmental compensation limit is reached (100% dirty). S A wiring fault between a sensor and the controller is detected. An internal sensor fault is detected upon entering the trouble state: S The contacts on the controller’s supervisory relay switch positions. (See Fig. 26.) S If a sensor trouble, the sensor’s Trouble LED the controller’s Trouble LED turn on. Optic plate Airflow Alarm State The smoke detector enters the alarm state when the amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 3.) Upon entering the alarm state: S The sensor’s Alarm LED and the controller’s Alarm LED turn on. S If 100% dirty, the sensor’s Dirty LED turns on and the controller’s Trouble LED flashes continuously. S If a wiring fault between a sensor and the controller, the controller’s Trouble LED turns on but not the sensor’s. Trouble C07305 Alarm Power Indicators Normal State The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke. In the normal state, the Power LED on both the sensor and the controller are on and all other LEDs are off. Test/reset switch Fig. 26 - Controller Assembly 21 C07298 580J CONTROL OR INDICATOR 580J NOTE: All troubles are latched by the duct smoke detector. The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state. Resetting Alarm and Trouble Condition Trips: Manual reset is required to restore smoke detector systems to Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Check each sensor for Alarm or Trouble status (indicated by LED). Clear the condition that has generated the trip at this sensor. Then reset the sensor by pressing and holding the reset button (on the side) for 2 seconds. Verify that the sensor’s Alarm and Trouble LEDs are now off. At the controller, clear its Alarm or Trouble state by pressing and holding the manual reset button (on the front cover) for 2 seconds. Verify that the controller’s Alarm and Trouble LEDs are now off. Replace all panels. Troubleshooting Controller’s Trouble LED is On 1. Check the Trouble LED on each sensor connected to the controller. If a sensor’s Trouble LED is on, determine the cause and make the necessary repairs. 2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as required. Controller’s Trouble LED is Flashing 1. One or both of the sensors is 100% dirty. 2. Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section. Sensor’s Trouble LED is On 1. Check the sensor’s Dirty LED. If it is flashing, the sensor is dirty and must be cleaned. 2. Check the sensor’s cover. If it is loose or missing, secure the cover to the sensor housing. 3. Replace sensor assembly. Sensor’s Power LED is Off 1. Check the controller’s Power LED. If it is off, determine why the controller does not have power and make the necessary repairs. 2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as required. Controller’s Power LED is Off 1. Make sure the circuit supplying power to the controller is operational. If not, make sure JP2 and JP3 are set correctly on the controller before applying power. 2. Verify that power is applied to the controller’s supply input terminals. If power is not present, replace or repair wiring as required. Remote Test/Reset Station’s Trouble LED Does Not flash When Performing a Dirty Test, But the Controller’s Trouble LED Does 1. Verify that the remote test/station is wired as shown in Fig. 23. Repair or replace loose or missing wiring. 2. Configure the sensor dirty test to activate the controller’s supervision relay. See “Changing sensor dirty test operation.” Sensor’s Trouble LED is On, But the Controller’s Trouble LED is OFF Remove JP1 on the controller. PROTECTIVE DEVICES Compressor Protection Overcurrent The compressor has internal linebreak motor protection. Overtemperature The compressor has an internal protector to protect it against excessively high discharge gas temperatures. High Pressure Switch The system is provided with a high pressure switch mounted on the discharge line. The switch is stem-- mounted and brazed into the discharge tube. Trip setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when hot. Reset is automatic at 505 psig (3482 kPa). Low Pressure Switch The system is protected against a loss of charge and low evaporator coil loading condition by a low pressure switch located on the suction line near the compressor. The switch is stem-- mounted. Trip setting is 54 psig +/-- 5 psig (372 +/-- 34 kPa). Reset is automatic at 117 +/-- 5 psig (807 +/-- 34 kPa). Evaporator Freeze Protection The system is protected against evaporator coil frosting and low temperature conditions by a temperature switch mounted on the evaporator coil hairpin. Trip setting is 30_F +/-- 5_F (-- 1_C +/-- 3_C). Reset is automatic at 45_F (7_C). Supply (Indoor) Fan Motor Protection Disconnect and lockout power when servicing fan motor. The standard supply fan motor is equipped with internal overcurrent and overtemperature protection. Protection devices reset automatically. The High Static option supply fan motor is equipped with a pilot-- circuit Thermix combination overtemperature/overcurrent protection device. This device resets automatically. Do not bypass this switch to correct trouble. Determine the cause and correct it. Condenser Fan Motor Protection The condenser fan motor is internally protected against overtemperature. Relief Device A soft solder joint at the suction service access port provides pressure relief under abnormal temperature and pressure conditions (i.e., fire in building). Protect this joint during brazing operations near this joint. 22 Control Circuit, 24--V Limit Switch and Shield The control circuit is protected against overcurrent conditions by a circuit breaker mounted on control transformer TRAN. Reset is manual. GAS HEATING SYSTEM 580J unit heating systems are referenced here according to unit Gas Heat Option (defined in the unit model number Position#8) and Heat Level (input capacity, defined in Positions #9-- 10-- 11). See Appendix 1 for a complete unit model number nomenclature chart. POSITION #8 A B C GAS HEAT OPTION Nat. Gas / Standard HX and Heat Nat. Gas / SS HX and Low NOx Heat Nat. Gas / SS HX and Standard Heat General The heat exchanger system consists of a gas valve feeding multiple inshot burners off a manifold. The burners fire into matching primary tubes. The primary tubes discharge into combustion plenum where gas flow converges into secondary tubes. The secondary tubes exit into the induced draft fan wheel inlet. The induced fan wheel discharges into a flue passage and flue gases exit out a flue hood on the side of the unit. The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control (IGC) board. Safety switches include a Rollout Switch (at the top of the burner compartment) and a limit switch (mounted through the fan deck, over the tubes). (See Fig. 27 and Fig. 28.) INDUCEDDRAFT MOTOR MOUNTING PLATE BURNER SECTION INDUCEDDRAFT MOTOR MANIFOLD PRESSURE TAP Fuel Types and Pressures Natural Gas — The 580J unit is factory-- equipped for use with Natural Gas fuel at elevation under 2000 ft (610 m). See section Orifice Replacement for information in modifying this unit for installation at elevations above 2000 ft (610 m). Gas line pressure entering the unit’s main gas valve must be within specified ranges. Adjust unit gas regulator valve as required or consult local gas utility. Table 4 – Natural Gas Supply Line Pressure Ranges 580J SIZE GAS HEAT OPT HEAT LEVEL MIN MAX All All All 4.0 in. wg (996 Pa) 13.0 in. wg (3240 Pa) Manifold pressure is factory-- adjusted for NG fuel use. Adjust as required to obtain best flame characteristic. Table 5 – Natural Gas Manifold Pressure Ranges ROLLOUT SWITCH FLUE EXHAUST HEAT LEVEL A, C All B All HIGH FIRE LOW FIRE 3.5 in. wg (872 Pa) 3.5 in. wg (872 Pa) 1.7 in. wg (423 Pa){ NA RANGE 2.0--- 5.0 in. wg (Hi) (498--- 1245 Pa) 2.0--- 5.0 in. wg (Hi) (498--- 1245 Pa) NA: Not Available { 3 Phase models only VESTIBULE PLATE BLOWER HOUSING GAS VALVE Fig. 27 - Burner Section Details GAS HEAT OPT C06152 Liquid Propane — Accessory packages are available for field-- installation that will convert the 580J unit (except low NOx model) to operate with Liquid Propane (LP) fuels. These kits include new orifice spuds, new springs for gas valves and a supply line low pressure switch. See section on Orifice Replacement for details on orifice size selections. Low NOx models include specially-- sized orifices and use of different flue flow limits and tube baffles. Because of these extra features, conversion of these models to LP is not recommended. Fuel line pressure entering unit gas valve must remain within specified range. 23 580J C08284 Fig. 28 - Limit Switch Location Table 6 – Liquid Propane Supply Line Pressure Ranges 580J SIZE GAS HEAT OPT HEAT LEVEL All A, C All All B All MIN MAX 11.0 in. wg (2740 Pa) NA 13.0 in. wg (3240 Pa) NA Manifold pressure for LP fuel use must be adjusted to specified range. Follow instructions in the accessory kit to make initial readjustment. 580J Table 7 – Liquid Propane Manifold Pressure Ranges GAS HEAT OPT HEAT LEVEL A, C All B All HIGH FIRE LOW FIRE 10.0 in. wg (2490 Pa) NA 5.0 in. wg (1245 Pa){ NA Flue Gas Passageways To inspect the flue collector box and upper areas of the heat exchanger: 1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-- Air Blower section. See Fig. 31. 2. Remove the flue cover to inspect the heat exchanger. 3. Clean all surfaces as required using a wire brush. Combustion--Air Blower NA: Not Available { 3 Phase models only Supply Pressure Switch — The LP conversion kit includes a supply low pressure switch. The switch contacts (from terminal C to terminal NO) will open the gas valve power whenever the supply line pressure drops below the setpoint. See Fig. 29 and Fig. 30. If the low pressure remains open for 15 minutes during a call for heat, the IGC circuit will initiate a Ignition Fault (5 flashes) lockout. Reset of the low pressure switch is automatic on rise in supply line pressure. Reset of the IGC requires a recycle of unit power after the low pressure switch has closed. Fig. 29 - LP Low Pressure Switch (Installed) Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-- monthly to determine proper cleaning frequency. To access burner section, slide the sliding burner partition out of the unit. To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows: 1. Slide burner access panel out. 2. Remove the 7 screws that attach induced-- draft motor housing to vestibule plate. (See Fig. 31.) 3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5. 4. To remove blower from the motor shaft, remove 2 setscrews. 5. To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate. 6. To reinstall, reverse the procedure outlined above. C08238 LP LPS IGC BRN C NO BRN J2-11 MGV IGC TSTAT C GRA J2-12 W2 This switch also prevents operation when the propane tank level is low which can result in gas with a high concentration of impurities, additives, and residues that have settled to the bottom of the tank. Operation under these conditions can cause harm to the heat exchanger system. Contact your fuel supplier if this condition is suspected. PNK C08285 Fig. 30 - LP Supply Line Low Pressure Switch Wiring 24 Regulator Regulator Gasket Seal Strips, Sponge Rubber Heater Tube Assembly Retainer Support Insulation Assembly 580J Wind Cap Assembly (shown inverted, as shipped) Inducer Fan-Motor Assembly Burner Assembly C08227 Fig. 31 - Heat Exchanger Assembly Burners and Igniters ! Orifice CAUTION 1.00-in (25.4 mm) EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. When working on gas train, do not hit or plug orifice spuds. Manifold Pipe Fig. 32 - Orifice Projection Main Burners To access burners, remove burner access panel and slide out burner partition. At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary. Orifice projection — Refer to Fig. 32 for maximum projection dimension for orifice face to manifold tube. Removal and Replacement of Gas Train See Fig. 27, Fig. 31 and Fig. 33. 1. 2. 3. 4. Shut off manual gas valve. Shut off power to unit. Slide out burner partition. Disconnect gas piping at unit gas valve. C08211 5. Remove wires connected to gas valve. Mark each wire. 6. Remove igniter wires and sensor wires at the Integrated Gas Unit Controller (IGC). (See Fig. 34.) 7. Remove the 2 screws that attach the burner rack to the vestibule plate (Fig. 27). 8. Slide the burner tray out of the unit (Fig. 33). 9. To reinstall, reverse the procedure outlined above. Cleaning and Adjustment 1. Remove burner rack from unit as described in Removal and Replacement of Gas Train section, above. 2. Inspect burners; if dirty, remove burners from rack. (Mark each burner to identify its position before removing from the rack.) 3. Use a soft brush to clean burners and cross-- over port as required. 4. Adjust spark gap. See Fig. 35 and Fig. 36. 5. If factory orifice has been removed, check that each orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum valve. See Fig. 32 25 580J 6. Reinstall burners on rack in the same locations as factory-- installed. (The outside crossover flame regions of the outermost burners are pinched off to prevent excessive gas flow from the side of the burner assembly. If the pinched crossovers are installed between two burners, the flame will not ignite properly.) Fig. 33 - Burner Tray Details RACEWAY C06153 INTEGRATED GAS UNIT CONTROLLER (IGC) 1. Remove manifold pressure tap plug from manifold and connect pressure gauge or manometer. (See Fig. 33) 2. Turn on electrical supply. 3. Turn on unit main gas valve. 4. Set room thermostat to call for heat. If unit has two-stage gas valve, verify high-- stage heat operation before attempting to adjust manifold pressure. 5. When main burners ignite, check all fittings, manifold, and orifices for leaks. 6. Adjust high-- stage pressure to specified setting by turning the plastic adjustment screw clockwise to increase pressure, counter-- clockwise to decrease pressure. 7. For Two-- Stage Gas Valves set room thermostat to call for low-- stage heat. Adjust low-- stage pressure to specified setting. 8. Replace regulator cover screw(s) when finished. 9. With burner access panel removed, observe unit heating operation in both high stage and low stage operation if so equipped. Observe burner flames to see if they are blue in appearance, and that the flames are approximately the same for each burner. 10. Turn off unit, remove pressure manometer and replace the 1/8 in. pipe fitting on the gas manifold. See Fig. 33. Limit Switch Remove blower access panel. Limit switch is located on the fan deck. See Fig. 28. Burner Ignition HOLE IN END PANEL (HIDDEN) Fig. 34 - Unit Control Box/IGC Location C08454 7. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above. Gas Valve — All three-- phase models (except Low NOx) are equipped with 2-- stage gas valves. Single-- phase models and all Low NOx models are equipped with single-- stage gas valves. See Fig. 37 for locations of adjustment screws and features on the gas valves. To adjust gas valve pressure settings: IMPORTANT: Leak check all gas connections including the main service connection, gas valve, gas spuds, and manifold pipe plug. All leaks must be repaired before firing unit. Check Unit Operation and Make Necessary Adjustments NOTE: Gas supply pressure at gas valve inlet must be within specified ranges for fuel type and unit size. See Tables 4 and 5. Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box. See Fig. 34. The IGC contains a self-- diagnostic LED (light-- emitting diode). A single LED (see Fig. 38) on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED error code can be observed through the viewport. During servicing refer to the label on the control box cover or Table 8 for an explanation of LED error code descriptions. If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds. 26 LOW HEAT 580J 72,000 BTUH INPUT AND 60,000 BTUH INPUT MEDIUM AND HIGH HEAT 115,000 BTUH INPUT, 150,000 BTUH INPUT, 90,000BTUH INPUT AND 120,000 BTUH INPUT Fig. 35 - Spark Adjustment, 04-- 07 C06154 125,000/90,000 BTUH INPUT 180,000/120,000 BTUH INPUT 240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT Fig. 36 - Spark Adjustment, 08-- 12 27 C08447 580J Table 8 – LED Error Code Description* IMPORTANT: Refer to Troubleshooting Table 13 and Table 14 for additional information. LED INDICATION ERROR CODE DESCRIPTION ON Normal Operation OFF Hardware Failure 1 Flash{ Evaporator Fan On/Off Delay Modified Orifice Replacement 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced --- Draft Motor Fault 7 Flashes Rollout Switch Fault 8 Flashes Internal Control Fault 9 Flashes Software Lockout This unit uses orifice type LH32RFnnn (where nnn indicates orifice reference size). When replacing unit orifices, order the necessary parts via RCD. See Table 10 for available orifice sizes. See Table 11 and Table 12 for orifice sizes for Natural Gas and LP fuel usage at various elevations above sea level. Check that each replacement orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum value. See Fig. 32. LEGEND LED --- Light Emitting Diode * A 3--- second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence. { Indicates a code that is not an error. The unit will continue to operate when this code is displayed. 2 Stage Single Stage Fig. 37 - Gas Valves 28 C08210 580J Red LED-Status C08452 Fig. 38 - Integrated Gas Control (IGC) Board Table 9 – IGC Connections TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O CONNECTION PIN NUMBER INPUTS RT, C Input power from TRAN 1 control box 24 VAC SS Speed sensor gas section analog input FS, T1 Flame sensor gas section switch input W Heat stage 1 LCTB 24 VAC J2, 2 RS Rollout switch gas section switch input J2, 5-6 LS Limit switch fan section switch input J2, 7-8 CS Centrifugal switch (not used) switch input J2, 9-10 L1, CM Induced draft combustion motor gas section line VAC IFO Indoor fan control box relay J2, 1 GV Gas valve (heat stage 1) gas section relay J2, 11-12 — — J1, 1-3 — OUTPUTS 29 580J Table 10 – Orifice Sizes ORIFICE DRILL SIZE #30 1/8 #31 #32 #33 #34 #35 #36 #37 #38 #39 #40 #41 #42 #43 #44 #45 #46 #47 #48 #49 #50 #51 #52 #53 #54 #55 #56 #57 #58 BRYANT PART NUMBER LH32RF129 LH32RF125 LH32RF120 LH32RF116 LH32RF113 LH32RF111 LH32RF110 LH32RF105 LH32RF104 LH32RF102 LH32RF103 LH32RF098 LH32RF096 LH32RF094 LH32RF089 LH32RF086 LH32RF082 LH32RF080 LH32RF079 LH32RF076 LH32RF073 LH32RF070 LH32RF067 LH32RF065 LH32RF060 LH32RF055 LH32RF052 LH32RF047 LH32RF043 LH32RF042 DRILL DIA. (in.) 0.1285 0.1250 0.1200 0.1160 0.1130 0.1110 0.1100 0.1065 0.1040 0.1015 0.0995 0.0980 0.0960 0.0935 0.0890 0.0860 0.0820 0.0810 0.0785 0.0760 0.0730 0.0700 0.0670 0.0635 0.0595 0.0550 0.0520 0.0465 0.0430 0.0420 Table 11 – Altitude Compensation* (04-- 07) - Small Chassis ELEVATION ft (m) 0 --- 2000 (610) 2000 (610) 3000 (914) 4000 (1219) 5000 (1524) 6000 (1829) 7000 (2134) 8000 (2438) 9000 (2743) 10000 (3048) 11000 (3353) 12000 (3658) 13000 (3962) 14000 (4267) 72,000 BTUH Nominal NG Orifice Size 331 351 351 361 361 372 382 392 †40 †41 †42 †43 †43 442 LP Orifice Size 514 514 524 524 524 524 534 534 534 544 544 544 554 †56 115,000 BTUH Nominal NG LP Orifice Size Orifice Size 331 503 1 35 514 1 35 514 361 514 361 514 372 524 2 38 524 392 524 †40 534 †41 534 †42 534 †43 544 †43 544 442 554 30 150,000 BTUH Nominal NG LP Orifice Size Orifice Size †30 463 †30 473 1 31 473 311 483 311 483 311 483 1 32 493 331 493 341 503 351 503 1 36 514 2 37 514 382 524 †40 534 ELEVATION ft (m) 0 --- 2000 (610) 2000 (610) 3000 (914) 4000 (1219) 5000 (1524) 6000 (1829) 7000 (2134) 8000 (2438) 9000 (2743) 10000 (3048) 11000 (3353) 12000 (3658) 13000 (3962) 14000 (4267) 125,000 BTUH Nominal NG Orifice LP Orifice Size Size 311 493 321 503 1 32 503 1 33 503 331 514 341 514 1 35 514 1 36 524 372 524 382 524 2 39 534 †41 534 †42 544 †43 544 250,000 BTUH Nominal NG Orifice LP Orifice Size Size †30 463 †30 473 1 31 473 1 31 483 311 483 311 483 1 32 493 1 33 493 341 503 351 503 1 36 514 2 37 514 382 524 †40 534 180,000, 224,000 BTUH Nominal NG Orifice LP Orifice Size Size 311 483 321 493 1 32 493 1 33 493 331 503 341 503 1 35 503 1 36 514 372 514 382 524 2 39 524 †41 534 †42 534 †43 544 Table 12 – Altitude Compensation* (04-- 06) - Low NOx Units ELEVATION ft (m) 0 --- 2000 (610) 2000 (610) 3000 (914) 4000 (1219) 5000 (1524) 6000 (1829) 7000 (2134) 8000 (2438) 9000 (2743) 10000 (3048) 11000 (3353) 12000 (3658) 13000 (3962) 14000 (4267) 60,000, 90,000 BTUH Nominal NG Orifice Size LP Orifice Size 2 38 534 2 39 544 †40 544 †41 544 †41 544 †42 544 †42 544 †43 554 †43 554 2 44 554 442 554 452 †56 473 †56 483 †56 120,000 BTUH Nominal NG Orifice Size LP Orifice Size 1 32 503 1 33 514 341 514 351 514 1 35 514 1 36 524 361 524 372 524 2 38 534 †40 534 †41 534 †42 544 †43 544 †43 554 LEGEND: NG = Natural Gas LP = Liquid Propane 1 = CRLPELEV001A00 * As the height above sea level increases, there is less oxygen per cubic 2 = CRLPELEV002A00 ft. of air. Therefore, heat input rate should be reduced at higher altitudes. 3 = CRLPELEV003A00 { Not included in kit. May be purchased separately through dealer. 4 = CRLPELEV004A00 Minimum heating entering air temperature When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers. To operate at lower mixed-- air temperatures, a field-- supplied outdoor-- air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation. Wire the outdoor-- air thermostat (part no. HH22AG106) in series with the second stage gas valve as shown below. Set the outdoor-- air thermostat at 35_F for stainless steel heat exchangers or 45_F for standard heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat setpoint. Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise. Thermostat TH1 LCTB W1 W1 OALT TH2 W2 W2 C08442 Troubleshooting Heating System Refer to Table 13 and Table 14 for additional troubleshooting topics. 31 580J Table 11 (cont.) - Altitude Compensation* (A08-- A12) Table 13 – Heating Service Analysis PROBLEM CAUSE Misaligned spark electrodes. No gas at main burners. 580J Burners Will Not Ignite. Water in gas line. No power to furnace. No 24 v power supply to control circuit. Miswired or loose connections. Burned ---out heat anticipator in thermostat. Broken thermostat wires. Dirty air filter. Gas input to unit too low. Inadequate Heating. Unit undersized for application. Restricted airflow. Blower speed too low. Limit switch cycles main burners. Too much outdoor air. Poor Flame Characteristics. Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO, sooting flame, or floating flame. Burners Will Not Turn Off. Unit is locked into Heating mode for a one minute minimum. REMEDY Check flame ignition and sensor electrode positioning. Adjust as needed. Check gas line for air, purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes before attempting to relight unit. Check gas valve. Drain water and install drip leg to trap water. Check power supply, fuses, wiring, and circuit breaker. Check transformer. Transformers with internal overcurrent protection require a cool down period before resetting. Check all wiring and wire nut connections. Replace thermostat. Run continuity check. Replace wires, if necessary. Clean or replace filter as necessary. Check gas pressure at manifold. Clock gas meter for input. If too low, increase manifold pressure, or replace with correct orifices. Replace with proper unit or add additional unit. Clean filter, replace filter, or remove any restrictions. Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units. Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. Adjust minimum position. Check economizer operation. Check all screws around flue outlets and burner compartment. Tighten as necessary. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Wait until mandatory one ---minute time period has elapsed or reset power to unit. 32 Table 14 – IGC Board LED Alarm Codes On Off DESCRIPTION Normal Operation ACTION TAKEN BY CONTROL RESET METHOD — — — Loss of power to the IGC. Check 5 amp fuse on IGC, power to unit, 24V circuit breaker, transformer, and wiring to the IGC. Hardware Failure No gas heating. 2 Flashes Limit Switch Fault Gas valve and igniter Off. Limit switch closed, or Indoor fan and inducer heat call (W) Off. On. 3 Flashes Flame Sense Fault Indoor fan and inducer On. Flame sense normal. Power reset for LED reset. The IGC sensed a flame when the gas valve should be closed. Check wiring, flame sensor, and gas valve operation. 4 Flashes Four Consecutive Limit Switch Fault No gas heating. Heat call (W) Off. Power reset for LED reset. 4 consecutive limit switch faults within a single call for heat. See Limit Switch Fault. Ignition Fault No gas heating. Heat call (W) Off. Power reset for LED reset. Unit unsuccessfully attempted ignition for 15 minutes. Check igniter and flame sensor electrode spacing, gaps, etc. Check flame sense and igniter wiring. Check gas valve operation and gas supply. Check gas valve connections to IGC terminals. BRN lead must be on Pin 11. 6 Flashes Induced Draft Motor Fault If heat off: no gas heating. If heat on: gas valve Off and inducer On. Inducer sense normal, or heat call (W) Off. Inducer sense On when heat call Off, or inducer sense Off when heat call On. Check wiring, voltage, and operation of IGC motor. Check speed sensor wiring to IGC. 7 Flashes Rollout Switch Lockout Gas valve and igniter Off. Indoor fan and inducer Power reset. On. Rollout switch has opened. Check gas valve operation. Check induced-draft blower wheel is properly secured to motor shaft. 8 Flashes Internal Control Lockout No gas heating. Power reset. IGC has sensed internal hardware or software error. If fault is not cleared by resetting 24 v power, replace the IGC. 9 Flashes Temporary Software Lockout No gas heating. 1 hour auto reset, or power reset. Electrical interference is disrupting the IGC software. 5 Flashes — PROBABLE CAUSE High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is within the range on the unit nameplate. Check wiring and limit switch operation. LEGEND IGC --- Integrated Gas Unit Control LED --- Light--- Emitting Diode NOTES: 1. There is a 3--- second pause between alarm code displays. 2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence. 3. Alarm codes on the IGC will be lost if power to the unit is interrupted. ECONOMIZER SYSTEMS ECONOMI$ER IV CONTROLLER The 580J units may be equipped with a factory-- installed or accessory (field-- installed) economizer system. Two types are available: with a logic control system (EconoMi$er IV) and without a control system (EconoMi$er2). See Fig. 39 and Fig. 40 for component locations on each type. See Fig. 41 and Fig. 42 for economizer section wiring diagrams. WIRING HARNESS ACTUATOR OUTSIDE AIR TEMPERATURE SENSOR LOW AMBIENT SENSOR Both economizers use direct-- drive damper actuators. C06021 Fig. 39 - EconoMi$er IV Component Locations 33 580J LED FLASH CODE OUTDOOR AIR HOOD ECONOMI$ER2 PLUG HOOD SHIPPING BRACKET GEAR DRIVEN DAMPER BAROMETRIC RELIEF DAMPER 580J Fig. 40 - EconoMi$er2 Component Locations C06022 FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK 8 7 LEGEND DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT — Potentiometer RAT — Return-Air Temperature Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting NOTES: 1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb. 2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded. 3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position. Fig. 41 - EconoMi$er IV Wiring 34 C06028 BLACK 4 TRANSFORMER GROUND 3 5 BLUE 500 OHM RESISTOR 2 8 VIOLET 6 NOTE 1 PINK 7 RUN OAT SENSOR RED NOTE 3 1 24 VAC 10 YELLOW 11 9 DIRECT DRIVE ACTUATOR 4-20mA SIGNAL WHITE 12 4-20 mA position input signal ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor. Fig. 42 - EconoMi$er2 with 4 to 20 mA Control Wiring C08436 Table 15 – EconoMi$er IV Input/Output Logic Demand Control Ventilation (DCV) Below set (DCV LED Off) Above set (DCV LED On) INPUTS Enthalpy* Outdoor Return High (Free Cooling LED Off) Low Low (Free Cooling LED On) High High (Free Cooling LED Off) Low Low (Free Cooling LED On) High Y1 Y2 On On Off On On Off On On Off On On Off On Off Off On Off Off On Off Off On Off Off OUTPUTS Compressor N Terminal† Occupied Unoccupied Stage Stage 1 2 Damper On On On Off Minimum position Closed Off Off On Off Modulating** (between min. Modulating** (between position and full-open) closed and full-open) Off Off Off Off Minimum position Closed On On Modulating†† (between min. Modulating†† (between position and DCV closed and DCV On Off maximum) maximum) Off Off On Off Off Off Modulating*** Modulating††† Off Off * † ** †† *** For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint. Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). Modulation is based on the supply-air sensor signal. Modulation is based on the DCV signal. Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal). ††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal). 35 580J 50HJ540573 ACTUATOR ASSEMBLY 580J C06053 Fig. 43 - EconoMi$er IV Functional View EconoMi$er IV Table 16 – Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Supply Air Temperature Sensor, and Outdoor Air Temperature Sensor Table 15 provides a summary of EconoMi$er IV. Troubleshooting instructions are enclosed. A functional view of the EconoMi$er is shown in Fig. 43. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Bryant to help with EconoMi$er IV training and troubleshooting. TEMP (C) --- 40 --- 35 --- 30 --- 25 --- 20 --- 15 --- 10 --- 5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 EconoMi$er IV Standard Sensors Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. (See Fig. 44.) The operating range of temperature measurement is 40_ to 100_F (4_ to 38_C). Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. (See Fig. 44.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F (-- 18_ to 70_C). See Table 16 for sensor temperature/resistance values. 36 TEMP (F) --- 40 --- 31 --- 22 --- 13 --- 4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 149 158 RESISTANCE (Ohms) 335,651 242,195 176,683 130,243 96,974 72,895 55,298 42,315 32,651 25,395 19,903 15,714 12,494 10,000 8,056 6,530 5,325 4,367 3,601 2,985 2,487 2,082 1,752 SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION SUPPLY AIR TEMPERATURE SENSOR C06034 Fig. 45 - EconoMi$er IV Controller Potentiometer and LED Locations 19 LED ON 18 D 17 LED OFF 16 LED ON C 15 mA The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture. Outdoor Air Lockout Sensor The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42_F (6_C) ambient temperature. (See Fig. 38.) EconoMi$er IV Control Modes IMPORTANT: The optional EconoMi$er2 does not include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing field-supplied controller. See Fig. 42 for wiring information. Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. (See Table 17.) The EconoMi$er IV is supplied from the factory with a supply-- air temperature sensor and an outdoor-- air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit. Outdoor Dry Bulb Changeover The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable setpoint selected on the control. If the outdoor-air temperature is above the setpoint, the EconoMi$er IV will adjust the outside air dampers to minimum position. If the outdoor-air temperature is below the setpoint, the position of the outside air dampers will be controlled to provided free cooling using outdoor air. When in this mode, the LED next to the free cooling setpoint potentiometer will be on. The changeover temperature setpoint is controlled by the free cooling setpoint potentiometer located on the control. (See Fig. 45.) The scale on the potentiometer is A, B, C, and D. See Fig. 46 for the corresponding temperature changeover values. 14 LED OFF 13 12 LED ON B LED OFF LED ON A 11 10 LED OFF 9 40 45 50 55 60 65 70 75 80 DEGREES FAHRENHEIT 85 90 100 95 C06035 Fig. 46 - Outside Air Temperature Changeover Setpoints 30 25 20 15 10 5 0 0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50 STATIC PRESSURE (in. wg) Fig. 47 - Outdoor-- Air Damper Leakage C06031 Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 48.) Wiring is 37 580J C06033 FLOW IN CUBIC FEET PER MINUTE (cfm) Fig. 44 - Supply Air Sensor Location provided in the EconoMi$er IV wiring harness. (See Fig. 38.) outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 39.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover setpoint, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. The setpoints are A, B, C, and D. (See Fig. 46.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. Differential Enthalpy Control For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling. Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 39.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 48.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 41.) The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. ECONOMI$ERIV CONTROLLER ECONOMI$ERIV 580J GROMMET RETURN AIR SENSOR RETURN DUCT (FIELD-PROVIDED) C07085 Fig. 48 - Return Air Temperature or Enthalpy Sensor Mounting Location In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. (See Fig. 45.) Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard 46 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) 44 CONTROL CONTROL POINT CURVE APPROX. deg. F (deg. C) 80 (27) 42 AT 50% RH IDI UM EH TIV R LA 32 PE RE 30 80 22 60 70 24 65 (18) 10 0 90 TH 26 EN 70 (21) 28 AL PY BT U 75 (24) 34 PO UN TY 38 (% RY ) 40 AI R 73 (23) 70 (21) 67 (19) 63 (17) 36 D D 20 50 60 (16) A 40 16 18 55 (13) B 14 50 (10) 12 45 (7) 30 A B C D C 20 D 40 (4) 10 35 (2) B A D C 35 (2) 40 (4) 45 (7) 50 (10) HIGH LIMIT CURVE 55 60 65 70 75 80 85 90 95 100 105 110 (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43) APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C) Fig. 49 - Enthalpy Changeover Setpoints 38 C06037 N TR1 24 Vac HOT 24 Vac COM Set 10V 2V EXH P1 TR P Min Pos T1 T DCV 2V AQ1 + _ 1 2 Open Max 10V 5 DCV AQ SO+ SO SR+ SR 2V DCV Set 10V Free Cool B C A D 3 4 EF EF1 C06038 Fig. 50 - EonoMi$er IV Control Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. (See Fig. 51.) CO2 SENSOR MAX RANGE SETTING RANGE CONFIGURATION (ppm) 6000 5000 4000 Exhaust Setpoint Adjustment The exhaust setpoint will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The setpoint is modified with the Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig. 45.) The setpoint represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload. Minimum Position Control There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 45.) The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting, perform the following procedure: 1. Calculate the appropriate mixed air temperature using the following formula: 800 ppm 900 ppm 1000 ppm 1100 ppm 3000 2000 (TO x 0 3 4 5 6 7 x RA ) =TM 100 TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60_F, and return-air temperature is 75_F. (60 x .10) + (75 x .90) = 73.5_F 2. Disconnect the supply air sensor from terminals T and T1. 3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 41 and that the minimum position potentiometer is turned fully clockwise. 4. Connect 24 vac across terminals TR and TR1. 1000 2 OA + (TR ) 100 8 DAMPER VOLTAGE FOR MAX VENTILATION RATE C06039 Fig. 51 - CO2 Sensor Maximum Range Settings If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. 39 580J EXH N1 580J 5. Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value. 6. Reconnect the supply air sensor to terminals T and T1. Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 terminals on the EconoMi$er IV controller. (See Fig. 41.) Damper Movement Damper movement from full open to full closed (or vice versa) takes 2-- 1/2 minutes. Thermostats The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box. Occupancy Control The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-- supplied timeclock function in place of the jumper between TR and N. (See Fig. 41.) When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-- v signal from terminal N), the EconoMi$er IV will be in unoccupied mode. Demand Control Ventilation (DCV) When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air. Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria. A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 setpoint has not been reached. By the time the CO2 level reaches the setpoint, the damper will be at maximum ventilation and should maintain the setpoint. In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures. (TO x OA + (TR ) 100 x RA ) =TM 100 TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 51 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 51 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels. CO2 Sensor Configuration The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 17.) Use setting 1 or 2 for Bryant equipment. (See Table 17.) 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET Menu will appear. 40 APPLICATION Outdoor Air Dry Bulb Differential Dry Bulb Single Enthalpy Differential Enthalpy CO2 for DCV Control using a Wall-Mounted CO2 Sensor CO2 for DCV Control using a Duct-Mounted CO2 Sensor ECONOMI$ER IV WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required None. The outdoor air dry bulb sensor is factory installed. CRTEMPSN002A00* HH57AC078 HH57AC078 and CRENTDIF004A00* 33ZCSENCO2 33ZCSENCO2† and 33ZCASPCO2** O R CRCBDIOX005A00†† * CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. † 33ZCSENCO2 is an accessory CO2 sensor. ** 33ZCASPCO2 is an accessory aspirator box required for ductmounted applications. †† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories. 3. Use the Up/Down button to select the preset number. (See Table 17.) 4. Press Enter to lock in the selection. 5. Press Mode to exit and resume normal operation. The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings: 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET Menu will appear. 3. Use the Up/Down button to toggle to the NONSTD menu and press Enter. 4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached. 5. Press Mode to move through the variables. 6. Press Enter to lock in the selection, then press Mode to continue to the next variable. Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered. EconoMi$er IV Preparation 2. Disconnect device at P and P1. 3. Jumper P to P1. 4. Disconnect wires at T and T1. Place 5.6 kilo-- ohm resistor across T and T1. 5. Jumper TR to 1. 6. Jumper TR to N. 7. If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-- ohm 4074EJM checkout resistor across terminals SO and +. 8. Put 620-- ohm resistor across terminals SR and +. 9. Set minimum position, DCV setpoint, and exhaust potentiometers fully CCW (counterclockwise). 10. Set DCV maximum position potentiometer fully CW (clockwise). 11. Set enthalpy potentiometer to D. 12. Apply power (24 vac) to terminals TR and TR1. Differential Enthalpy To check differential enthalpy: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Place 620-- ohm resistor across SO and +. 3. Place 1.2 kilo-- ohm resistor across SR and +. The Free Cool LED should be lit. 4. Remove 620-- ohm resistor across SO and +. The Free Cool LED should turn off. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. Single Enthalpy To check single enthalpy: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit. 3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off. 4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. DCV (Demand Controlled Ventilation) and Power Exhaust To check DCV and Power Exhaust: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed. 3. Connect a 9-- v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open. 4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position. 5. Turn the DCV setpoint potentiometer CW until the DCV LED turns off. The DCV LED should turn off This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9-- v battery, 1.2 kilo-- ohm resistor, and a 5.6 kilo-- ohm resistor which are not supplied with the EconoMi$er IV. IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting. 1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open. 41 580J Table 17 – EconoMi$er IV Sensor Usage when the potentiometer is approximately 9-- v. The actuator should drive fully closed. 6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on. 7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. DCV Minimum and Maximum Position 580J To check the DCV minimum and maximum position: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Connect a 9-- v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed. 5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open. 7. Remove the jumper from TR and N. The actuator should drive fully closed. 8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. Supply-- Air Sensor Input 7. Remove jumper from TR to N. 8. Remove jumper from TR to 1. 9. Remove 5.6 kilo-- ohm resistor from T and T1. Reconnect wires at T and T1. 10. Remove jumper from P to P1. Reconnect device at P and P1. 11. Apply power (24 vac) to terminals TR and TR1. WIRING DIAGRAMS See Fig. 52 and Fig. 53 for typical wiring diagrams. PRE--START--UP ! PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death. 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 3. Do not remove compressor terminal cover until all electrical sources are disconnected. 4. Relieve all pressure from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals. 5. Never attempt to repair soldered connection while refrigerant system is under pressure. 6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power and then gas to unit. b. Recover refrigerant to relieve all pressure from system using both high-- pressure and low pressure ports. c. Cut component connection tubing with tubing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. To check supply-- air sensor input: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open. 3. Remove the 5.6 kilo-- ohm resistor and jumper T to T1. The actuator should drive fully open. 4. Remove the jumper across T and T1. The actuator should drive fully closed. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. EconoMi$er IV Troubleshooting Completion This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure. 1. Disconnect power at TR and TR1. 2. Set enthalpy potentiometer to previous setting. 3. Set DCV maximum position potentiometer to previous setting. 4. Set minimum position, DCV setpoint, and exhaust potentiometers to previous settings. 5. Remove 620-- ohm resistor from terminals SR and +. 6. Remove 1.2 kilo-- ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +. WARNING Proceed as follows to inspect and prepare the unit for initial start-- up: 1. Remove all access panels. 2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires, etc. 42 START--UP, GENERAL Internal Wiring Check all electrical connections in unit control boxes. Tighten as required. Refrigerant Service Ports Each unit system has two 1/4” SAE flare (with check valves) service ports: one on the suction line, and one on the compressor discharge line. Be sure that caps on the ports are tight. Compressor Rotation On 3-- phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gauges to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-- up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 1. Note that the evaporator fan is probably also rotating in the wrong direction. 2. Turn off power to the unit and install lockout tag. 3. Reverse any two of the unit power leads. 4. Re-- energize to the compressor. Check pressures. Unit Preparation Make sure that unit has been installed in accordance with installation instructions and applicable codes. Gas Piping Check gas piping for leaks. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could result in personal injury or death. Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field-- supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve. Return--Air Filters Make sure correct filters are installed in unit (see Appendix II - Physical Data). Do not operate unit without return-- air filters. Outdoor--Air Inlet Screens Outdoor-- air inlet screen must be in place before operating unit. Compressor Mounting Compressors are internally spring mounted. Do not loosen or remove compressor hold down bolts. The suction and discharge pressure levels should now move to their normal start-- up levels. NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not provide cooling. Cooling Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor. Check unit charge. Refer to Refrigerant Charge section. Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after a 30-- second delay. To shut off unit, set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Main Burners Main burners are factory set and should require no adjustment. To check ignition of main burners and heating controls, move thermostat setpoint above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, then lower the thermostat 43 580J b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-- test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-- soap solution. c. Inspect all field-- wiring and factory-- wiring connections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges. d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 4. Verify the following conditions: a. Make sure that condenser-- fan blade are correctly positioned in fan orifice. See Condenser-- Fan Adjustment section for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed. setting below the room temperature and verify that the burners and evaporator fan turn off. Refer to Table 11 and Table 12 for the correct orifice to use at high altitudes. 580J Heating 1. Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding. 2. Turn on electrical supply and manual gas valve. 3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature. 4. The induced-- draft motor will start. 5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-- second delay before another 5-- second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1. 6. The evaporator-- fan motor will turn on 45 seconds after burner ignition. 7. The evaporator-- fan motor will turn off in 45 seconds after the thermostat temperature is satisfied. 8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate. NOTE: The default value for the evaporator-- fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the LED is observed, the evaporator-- fan on/off delay has been modified. If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-- fan on delay for the next cycle will occur at 25 seconds.) To prevent short-- cycling, a 5-- second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating. The evaporator-- fan off delay can also be modified. Once the call for heating has ended, there is a 10-- minute period during which the modification can occur. If the limit switch trips during this period, the evaporator-- fan off delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator-- fan off delay to 180 seconds. To restore the original default value, reset the power to the unit. To shut off unit, set system selector switch at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting. Ventilation (Continuous Fan) Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-- fan selector switch is turned to the OFF position, there is a 30-- second delay before the fan turns off. OPERATING SEQUENCES Cooling, Unit Without Economizer When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-- fan contactor (IFC) and compressor contactor are energized and indoor-- fan motor, compressor, and outdoor fan start. The outdoor fanmotor runs continuously while unit is cooling. Heating, Unit Without Economizer When the thermostat calls for heating, terminal W1 is energized. To prevent thermostat short-- cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-- draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-- fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-- second time-- off delay. Cooling, Unit With EconoMi$er IV For Occupied mode operation of EconoMi$er IV, there must be a 24-- v signal at terminals TR and N (provided through PL6-- 3 from the unit’s IFC coil). Removing the signal at N places the EconoMi$er IV control in Unoccupied mode. During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a Cooling (by free cooling) or DCV demand is received. Integrated EconoMi$er IV operation on 580J single compressor model requires a 2-- stage thermostat (Y1 and Y2 switches). When free cooling using outside air is not available, the unit cooling sequence will be controlled directly by the space thermostat as described above as Cooling, Without Economizer. Outside air damper position will be closed or Minimum Position as determined by occupancy mode and fan signal. When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55_F. Compressor will not run. 44 Should 100% outside air not be capable of satisfying the space temperature, space temperature will rise until Y2 is closed. The economizer control will call for compressor operation. Dampers will modulate to maintain SAT at 50 to 55_F concurrent with compressor operation. The Low Ambient Lockout Thermostat will block compressor operation with economizer operation below 42_F outside air temperature. When space temperature demand is satisfied (thermostat Y1 opens), the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off. If accessory power exhaust is installed, the power exhaust fan motors will be energized by the economizer control as the dampers open above the PE-- On setpoint and will be de-- energized as the dampers close below the PE-- On setpoint. Damper movement from full closed to full open (or vice versa) will take between 1-- 1/2 and 2-- 1/2 minutes. Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a DCV demand is received. When the room temperature calls for heat (W1 closes), the heating controls are energized as described in Heating, Unit Without Economizer above. Demand Controlled Ventilation If a field-- installed CO2 sensor is connected to the EconoMi$er IV control, a Demand Controlled Ventilation strategy will operate automatically. As the CO2 level in the space increases above the CO2 setpoint (on the EconoMi$er IV controller), the minimum position of the dampers will be increased proportionally, until the Maximum Ventilation setting is reached. As the space CO2 level decreases because of the increase in fresh air, the outdoor-- damper will follow the higher demand condition from the DCV mode or from the free-- cooling mode. DCV operation is available in Occupied and Unoccupied periods with EconoMi$er IV. However, a control modification will be required on the 580J unit to implement the Unoccupied period function. FASTENER TORQUE VALUES See Table 18 for torque values. Heating With EconoMi$er IV During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Table 18 – Torque Values Supply fan motor mounting Supply fan motor adjustment plate Motor pulley setscrew Fan pulley setscrew Blower wheel hub setscrew Bearing locking collar setscrew Compressor mounting bolts Condenser fan motor mounting bolts Condenser fan hub setscrew 120 +/--- 12 in--- lbs 120 +/--- 12 in--- lbs 72+/--- 5 in--- lbs 72+/--- 5 in--- lbs 72+/--- 5 in--- lbs 65--- 70 in--- lbs 65--- 75 in--- lbs 20 +/--- 2 in--- lbs 84 +/--- 12 in--- lbs 45 580J During free cooling operation, a supply air temperature (SAT) above 50_F will cause the dampers to modulate between Minimum Position setpoint and 100% open. With SAT from 50_F to 45_F, the dampers will maintain at the Minimum Position setting. With SAT below 45_F, the outside air dampers will be closed. When SAT rises to 48_F, the dampers will re-- open to Minimum Position setting. 580J Fig. 52 - 580J Typical Unit Wiring Diagram - Power (06A, B, C 208/230-- 3-- 60) 46 C08308 47 Fig. 53 - 580J Unit Wiring Diagram - Control (06A, B, C) 580J C08317 APPENDIX I. MODEL NUMBER SIGNIFICANCE Model Number Nomenclature 1 2 3 4 5 8 0 J E 0 5 ____________ 6 7 8 9 6 A 0 ______ 10 11 12 13 14 15 16 17 18 7 2 A 1 A 0 A A -- ________ ______ Unit Type 580J = Std Eff gas heat RTU Design Revision 580J Voltage E = 460--- 3--- 60 J = 208/230--- 1--- 60 P = 208/230--- 3--- 60 T = 575--- 3--- 60 Cooling Tons 04 = 3 Ton 05 = 4 Ton 06 = 5 Ton 07 = 6 Ton --- = First Revision Packaging A = Standard B = LTL Factory Installed Options 08 = 7.5 Ton 09 = 8.5 Ton 12 = 10 Ton Outdoor Air Options A = None B = Temp econo w/ baro relief E = Temp econo w/ baro relief & CO21 H = Enthalpy econo w/ baro relief L = Enthalpy econo w/ baro relief & CO21 Q = Motorized 2 pos damper w/ baro relief Refrig. System/Gas Heat Options A = Standard refrig system coil/Nat gas heat B = Standard refrig system coil/Low NOx heat C = Standard refrig system coil/SS HX heat Heat Level 060 = 60,000 072 = 72,000 090 = 90,000 115 = 115,000 120 = 120,000 150 = 150,000 Indoor Fan Options 1 = Standard static option 2 = Medium static option 3 = High static option Coil Options (Indoor Coil --- Outdoor Coil) A = Al/Cu --- Al/Cu B = Precoat Al/Cu --- Al/Cu C = E--- coat Al/Cu --- Al/Cu D = E--- coat Al/Cu --- E--- coat Al/Cu E = Cu/Cu --- Al/Cu F = Cu/Cu --- Cu/Cu M = Al/Cu --- Al/Cu --- Louvered hail guards N = Precoat Al/Cu --- Al/Cu --- Louvered Hail Guards P = E coat Al/Cu --- Al/Cu --- Louvered Hail Guards Q = E coat Al/Cu --- E coat Al/Cu --- Louvered Hail Guards R = Cu/Cu --- Al/Cu --- Louvered Hail Guards A = Cu/Cu --- Cu/Cu --- Louvered Hail Guards 1 Future availability Serial Number Format POSITION NUMBER TYPICAL 1 1 POSITION 1--- 2 3--- 4 5 6--- 10 2 2 3 0 4 8 5 G 6 1 7 2 8 3 DESIGNATES Week of manufacture (fiscal calendar Year of manufacture (“08” = 2008) Manufacturing location (G = ETP, Texas, USA) Sequential number 48 9 4 10 6 APPENDIX II. PHYSICAL DATA 580J*05 580J*06 580J*07 1 / 1 / Scroll 5.6 25 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 8.5 42 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 10.7 42 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 14.1 56 Acutrol 630 / 505 54 / 117 Cu / Al 3/8” RTPF 2 / 15 5.5 3/4” Cu / Al 3/8” RTPF 2 / 15 5.5 3/4” Cu / Al 3/8” RTPF 4 / 15 5.5 3/4” Cu / Al 3/8” RTPF 4 / 15 7.3 3/4” Standard Static 1 phase Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.2 560--- 854 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 560--- 854 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 770--- 1175 48 1 / Centrifugal 10 x 10 ------------- Standard Static 3 phase Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.2 560--- 854 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 560--- 854 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 770--- 1175 48 1 / Centrifugal 10 x 10 1 / Belt 2.4 1073--- 1457 56 1 / Centrifugal 10 x 10 Medium Static 1 phase Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.2 770--- 1175 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 770--- 1175 56 1 / Centrifugal 10 x 10 1 / Belt 1.5 1035--- 1466 56 1 / Centrifugal 10 x 10 ------------- Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.2 770--- 1175 48 1 / Centrifugal 10 x 10 1 / Belt 1.2 770--- 1175 48 1 / Centrifugal 10 x 10 1 / Belt 2.4 1035--- 1466 56 1 / Centrifugal 10 x 10 1 / Belt 2.9 1173--- 1788 56 1 / Centrifugal 10 x 10 Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 2.4 1035--- 1466 56 1 / Centrifugal 10 x 10 1 / Belt 2.4 1035--- 1466 56 1 / Centrifugal 10 x 10 1 / Belt 2.9 1303--- 1687 56 1 / Centrifugal 10 x 10 1 / Belt 3.7 1474--- 1788 56 1 / Centrifugal 10 x 10 Material Coil type Rows / FPI Total Face Area (ft2) Cu / Al 3/8” RTPF 1 / 17 14.6 Cu / Al 3/8” RTPF 2 / 17 12.6 Cu / Al 3/8” RTPF 2 / 17 16.5 Cu / Al 3/8” RTPF 2 / 17 21.3 Qty / Motor Drive Type Motor HP / RPM Fan diameter (in) 1/ Direct 1/4 / 1100 22 1/ Direct 1/4 / 1100 22 1/ Direct 1/4 / 1100 22 1/ Direct 1/4 / 1100 22 2 / 16 x 25 x 2 1 / 20 x 24 x 1 2 / 16 x 25 x 2 1 / 20 x 24 x 1 2 / 16 x 25 x 2 1 / 20 x 24 x 1 4 / 16 x 16 x 2 1 / 20 x 24 x 1 Refrigeration System # Circuits / # Comp. / Type Puron (R--- 410A) charge A/B (lbs) Oil A/B (oz) Metering Device High--- press. Trip / Reset (psig) Low--- press. Trip / Reset (psig) Evap. Coil Material Coil type Rows / FPI Total Face Area (ft2) Condensate Drain Conn. Size Evap. Fan and Motor Cond. Coil Cond. fan / motor Filters RA Filter # / Size (in) OA inlet screen # / Size (in) 49 580J 580J*04 Medium Static 3 phase 3 -- 6 TONS -- Standard Refrigeration System High Static 3 phase Physical Data (Cooling) APPENDIX II. PHYSICAL DATA (cont.) 580J*08 580J*09 580J*12 1 / 1 / Scroll 13.75 60 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 15.25 85 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 20.0 110 Acutrol 630 / 505 54 / 117 Cu / Al 3/8” RTPF 3 / 15 8.9 3/4” Cu / Al 3/8” RTPF 3 / 15 11.1 3/4” Cu / Al 3/8” RTPF 4 / 15 11.1 3/4” Standard Static 3 phase Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 1.7 489--- 747 56 1 / Centrifugal 15 x 15 1 / Belt 1.7 518--- 733 56 1 / Centrifugal 15 x 15 1 / Belt 2.4 591--- 838 56 1 / Centrifugal 15 x 15 Medium Static 3 phase Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 2.9 733--- 949 56 1 / Centrifugal 15 x 15 1 / Belt 2.4 690--- 936 56 1 / Centrifugal 15 x 15 1 / Belt 3.7 838--- 1084 56 1 / Centrifugal 15 x 15 Motor Qty / Drive Type Max BHP RPM Range Motor Frame Size Fan Qty / Type Fan Diameter (in) 1 / Belt 5.25 909--- 1102 145TY 1 / Centrifugal 15 x 15 1 / Belt 3.7 838--- 1084 56 1 / Centrifugal 15 x 15 1 / Belt 5.25 1022--- 1240 145TY 1 / Centrifugal 15 x 15 Material Coil type Rows / FPI Total Face Area (ft2) Cu / Al 3/8” RTPF 2 / 17 20.5 Cu / Al 3/8” RTPF 2 / 17 21.4 Cu / Al 3/8” RTPF 2 / 17 25.1 Qty / Motor Drive Type Motor HP / RPM Fan diameter (in) 2 / Direct 1/4 / 1100 22 2 / Direct 1/4 / 1100 22 2 / Direct 1/4 / 1100 22 4 / 16 x 20 x 2 1 / 20 x 24 x 1 4 / 20 x 20 x 2 1 / 20 x 24 x 1 4 / 20 x 20 x 2 1 / 20 x 24 x 1 Refrigeration System Evap. Coil 580J 7.5 -- 10 TONS -- Standard Refrigeration System High Static 3 phase Physical Data (Cooling) Evap. Fan and Motor Cond. Coil Cond. fan / motor Filters # Circuits / # Comp. / Type Puron (R--- 410A) charge A/B (lbs) Oil A/B (oz) Metering Device High--- press. Trip / Reset (psig) Low--- press. Trip / Reset (psig) Material Coil type Rows / FPI Total Face Area (ft2) Condensate Drain Conn. Size RA Filter # / Size (in) OA inlet screen # / Size (in) 50 APPENDIX II. PHYSICAL DATA (cont.) Physical Data (Heating) 3 -- 6 TONS 580J*04 580J*05 580J*06 580J*07 Gas Connection # of Gas Valves 1 1 1 1 Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT Nat. gas supply line press (in. w.g.)/(PSIG) 5--- 13 / 0.18--- 0.47 5--- 13 / 0.18--- 0.47 5--- 13 / 0.18--- 0.47 5--- 13 / 0.18--- 0.47 LP supply line press (in. w.g.)/(PSIG) 11--- 13 / 0.40--- 0.47 11--- 13 / 0.40--- 0.47 11--- 13 / 0.40--- 0.47 11--- 13 / 0.40--- 0.47 1st stage 0.14 0.14 0.14 0.14 2nd stage 0.14 0.14 0.14 0.14 # of stages / # of burners (total) 1/2 1/2 1/2 1/2 195 / 115 195 / 115 195 / 115 195 / 115 25 / 55 25 --- 55 25 --- 55 25 --- 55 Heat Anticipator Setting (Amps) HIGH MED Rollout switch opens / Closes Temperature rise # of stages / # of burners (total) 1 or 2 / 3 1/3 1/3 1/3 Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115 55 / 85 35 / 65 35 / 65 35 / 65 Temperature rise # of stages / # of burners (total) --- 1 or 2 / 3 1 or 2 / 3 1 or 2 / 3 Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115 Temperature rise --- 50 / 80 50 / 80 50 / 80 HIGH MED LOW Liquid Propane Heat # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise 1/2 1/2 1/2 1/2 195 / 115 195 / 115 195 / 115 195 / 115 25 / 55 25 --- 55 25 --- 55 25 --- 55 # of stages / # of burners (total) 1 or 2 / 3 1 or 2 / 3 1 or 2 / 3 1 or 2 / 3 Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115 55 / 85 35 / 65 35 / 65 35 / 65 Temperature rise # of stages / # of burners (total) --- 1 or 2 / 3 1 or 2 / 3 1 or 2 / 3 Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115 Temperature rise --- 50 / 80 50 / 80 50 / 80 HIGH MED LOW Low NOx Gas Heat # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise # of stages / # of burners (total) 1/2 1/2 1/2 --- 195 / 115 195 / 115 195 / 115 --- 20 / 50 20 / 50 20 / 50 --- 1/3 1/3 1/3 --- 195 / 115 195 / 115 195 / 115 --- 30 / 60 30 / 60 30 / 60 --- # of stages / # of burners (total) --- 1/3 1/3 --- Rollout switch opens / Closes --- 195 / 115 195 / 115 --- Temperature rise --- 40 / 70 40 / 70 --- Rollout switch opens / closes Temperature rise 51 580J LOW Natural Gas Heat APPENDIX II. PHYSICAL DATA (cont.) Physical Data (Heating) 7.5 -- 10 TONS 580J*04 580J*05 580J*06 580J*07 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 1 4--- 13 / 0.18--- 0.47 11--- 13 / 0.40--- 0.47 0.14 0.14 0.14 0.14 0.14 0.14 0.14 0.14 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT 1/2 195 / 115 25 / 55 1/2” NPT 1/2 195 / 115 25 --- 55 1/2” NPT 1/2 195 / 115 25 --- 55 1/2” NPT 1/2 195 / 115 25 --- 55 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT 1 or 2 / 3 195 / 115 55 / 85 1/2” NPT 1/3 195 / 115 35 / 65 1/2” NPT 1/3 195 / 115 35 / 65 1/2” NPT 1/3 195 / 115 35 / 65 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT ------- 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT 1/2 195 / 115 25 / 55 1/2” NPT 1/2 195 / 115 25 --- 55 1/2” NPT 1/2 195 / 115 25 --- 55 1/2” NPT 1/2 195 / 115 25 --- 55 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT 1 or 2 / 3 195 / 115 55 / 85 1/2” NPT 1 or 2 / 3 195 / 115 35 / 65 1/2” NPT 1 or 2 / 3 195 / 115 35 / 65 1/2” NPT 1 or 2 / 3 195 / 115 35 / 65 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT ------- 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 1/2” NPT 1 or 2 / 3 195 / 115 50 / 80 Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT 1/2 195 / 115 20 / 50 1/2” NPT 1/2 195 / 115 20 / 50 1/2” NPT 1/2 195 / 115 20 / 50 1/2” NPT ------- Connection size # of stages / # of burners (total) Rollout switch opens / closes Temperature rise (min/max) 1/2” NPT 1/3 195 / 115 30 / 60 1/2” NPT 1/3 195 / 115 30 / 60 1/2” NPT 1/3 195 / 115 30 / 60 1/2” NPT ------- Connection size # of stages / # of burners (total) Rollout switch opens / Closes Temperature rise (min/max) 1/2” NPT ------- 1/2” NPT 1/3 195 / 115 40 / 70 1/2” NPT 1/3 195 / 115 40 / 70 1/2” NPT ------- Gas Connection # of Gas Valves Nat. gas supply line press (in. w.g.)/(PSIG) LP supply line press (in. w.g.)/(PSIG) Heat Anticipator Setting (Amps) 1st stage 2nd stage LOW MED HIGH HIGH MED LOW Liquid Propane Heat MED LOW Low NOx Gas Heat HIGH 580J Natural Gas Heat 52 APPENDIX III. FAN PERFORMANCE General Fan Performance Notes: 580J 1. Interpolation is permissible. Do not extrapolate. 2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories. 3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses. 4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Bryant recommended the lower horsepower option. 5. For information on the electrical properties of Bryant’s motors, please see the Electrical information section of this book. 53 APPENDIX III. FAN PERFORMANCE (cont.) 580J*04 CFM 580J 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 1 Phase 3 Ton Horizontal Supply 0.2 RPM BHP Field---Supplied Drive1 553 0.14 575 0.16 597 0.18 620 0.21 643 0.23 667 0.27 691 0.30 715 0.34 740 0.38 1.2 RPM BHP 1019 1036 1053 1071 1089 1107 1126 1144 1163 0.64 0.69 0.74 0.79 0.84 0.90 0.96 1.03 1.10 RPM 681 700 720 741 762 783 805 827 849 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 0.22 782 0.32 870 0.42 948 0.25 801 0.35 888 0.46 965 0.28 820 0.38 906 0.49 983 0.31 839 0.42 925 0.54 1001 0.34 859 0.46 944 0.58 1020 0.38 879 0.50 963 0.63 1038 0.42 900 0.55 983 0.68 1057 0.47 920 0.60 1002 0.74 1076 0.52 941 0.66 1023 0.80 1096 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option Field---Supplied Drive2 1084 0.76 1146 0.89 1203 1.02 1258 1101 0.81 1162 0.94 1219 1.08 --1118 0.86 1179 1.00 1236 1.14 --1135 0.92 1196 1.06 1253 1.20 --1153 0.98 1213 1.12 ------1171 1.04 1231 1.19 ------1189 1.11 ----------1208 1.18 ------------------------- BHP 0.53 0.57 0.61 0.66 0.71 0.76 0.82 0.88 0.95 BHP 1.16 ----------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039). 2. Recommend using field --- supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035). 580J*04 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 1 Phase 0.2 RPM BHP Field---Supplied Drive1 567 0.15 591 0.17 615 0.20 641 0.23 666 0.26 693 0.29 719 0.33 746 0.38 773 0.42 1.2 RPM BHP 1016 1034 1053 1073 1093 1113 1133 1154 1175 0.51 0.57 0.63 0.70 0.77 0.85 0.92 1.01 1.09 3 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 688 0.22 786 0.30 871 0.37 947 710 0.26 807 0.34 891 0.42 966 732 0.29 828 0.38 911 0.47 985 755 0.33 849 0.42 931 0.52 1005 778 0.37 871 0.47 952 0.57 1025 802 0.41 893 0.53 974 0.63 1046 826 0.46 916 0.58 995 0.70 1067 850 0.51 939 0.64 1017 0.76 1088 875 0.57 963 0.70 1040 0.84 1110 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option Field---Supplied Drive2 1080 0.57 1139 0.64 1195 0.71 1249 1098 0.64 1157 0.72 1213 0.79 1266 1116 0.71 1176 0.79 1231 0.87 1284 1135 0.79 1194 0.87 1250 0.96 1302 1155 0.87 1213 0.96 1268 1.05 1321 1174 0.95 1232 1.05 1287 1.15 --1194 1.03 1252 1.14 ------1215 1.12 ------------------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039). 2. Recommend using field --- supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035). 54 BHP 0.44 0.49 0.55 0.61 0.67 0.74 0.81 0.89 0.96 BHP 0.77 0.86 0.95 1.04 1.14 --------- APPENDIX III. FAN PERFORMANCE (cont.) CFM 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 3 Phase 0.2 RPM BHP Field---Supplied Drive1 553 0.14 575 0.16 597 0.18 620 0.21 643 0.23 667 0.27 691 0.30 715 0.34 740 0.38 1.2 RPM BHP 1019 1036 1053 1071 1089 1107 1126 1144 1163 0.64 0.69 0.74 0.79 0.84 0.90 0.96 1.03 1.10 3 Ton Horizontal Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 681 0.22 782 0.32 870 0.42 948 700 0.25 801 0.35 888 0.46 965 720 0.28 820 0.38 906 0.49 983 741 0.31 839 0.42 925 0.54 1001 762 0.34 859 0.46 944 0.58 1020 783 0.38 879 0.50 963 0.63 1038 805 0.42 900 0.55 983 0.68 1057 827 0.47 920 0.60 1002 0.74 1076 849 0.52 941 0.66 1023 0.80 1096 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 1084 0.76 1146 0.89 1203 1.02 1258 1101 0.81 1162 0.94 1219 1.08 1274 1118 0.86 1179 1.00 1236 1.14 1290 1135 0.92 1196 1.06 1253 1.20 1307 1153 0.98 1213 1.12 1270 1.27 1324 1171 1.04 1231 1.19 1287 1.34 1341 1189 1.11 1249 1.26 1305 1.42 1358 1208 1.18 1267 1.34 1323 1.50 1376 1226 1.25 1285 1.41 1341 1.58 1394 BHP 0.53 0.57 0.61 0.66 0.71 0.76 0.82 0.88 0.95 BHP 1.16 1.22 1.28 1.35 1.42 1.50 1.58 1.66 1.75 NOTE: For more information, see General Fan Performance Notes on page 53. 1. Recommend using field --- supplied drive (part number KR11AG006) and belt (part number KR30AE039) 580J*04 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 3 Phase 0.2 RPM BHP Field---Supplied Drive1 567 0.15 591 0.17 615 0.20 641 0.23 666 0.26 693 0.29 719 0.33 746 0.38 773 0.42 1.2 RPM BHP 1016 1034 1053 1073 1093 1113 1133 1154 1175 0.51 0.57 0.63 0.70 0.77 0.85 0.92 1.01 1.09 3 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 688 0.22 786 0.30 871 0.37 947 710 0.26 807 0.34 891 0.42 966 732 0.29 828 0.38 911 0.47 985 755 0.33 849 0.42 931 0.52 1005 778 0.37 871 0.47 952 0.57 1025 802 0.41 893 0.53 974 0.63 1046 826 0.46 916 0.58 995 0.70 1067 850 0.51 939 0.64 1017 0.76 1088 875 0.57 963 0.70 1040 0.84 1110 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 1080 0.57 1139 0.64 1195 0.71 1249 1098 0.64 1157 0.72 1213 0.79 1266 1116 0.71 1176 0.79 1231 0.87 1284 1135 0.79 1194 0.87 1250 0.96 1302 1155 0.87 1213 0.96 1268 1.05 1321 1174 0.95 1232 1.05 1287 1.15 1339 1194 1.03 1252 1.14 1307 1.25 1358 1215 1.12 1272 1.24 1326 1.35 1378 1235 1.22 1292 1.34 1346 1.46 1397 NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039). 55 BHP 0.44 0.49 0.55 0.61 0.67 0.74 0.81 0.89 0.96 BHP 0.77 0.86 0.95 1.04 1.14 1.25 1.35 1.46 1.58 580J 580J*04 APPENDIX III. FAN PERFORMANCE (cont.) 580J*05 CFM 580J 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 1 Phase 4 Ton Horizontal Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.23 762 0.34 859 0.46 944 0.58 0.28 790 0.40 886 0.52 969 0.65 0.33 819 0.45 913 0.58 996 0.72 0.38 849 0.52 941 0.66 1023 0.80 0.45 879 0.59 970 0.73 1050 0.88 0.52 910 0.67 999 0.82 1078 0.98 0.59 942 0.75 1029 0.91 1106 1.08 0.68 974 0.85 1059 1.02 1135 1.19 0.77 1006 0.95 1090 1.13 1165 1.31 0.2 RPM 643 675 707 740 773 807 841 875 910 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP RPM BHP Medium Static Option Field---Supplied Drive1 0.84 1153 0.98 1213 1.12 ----0.92 1177 1.06 --------1.01 1201 1.15 --------1.10 ------------1.20 --------------------------------------------------------------------- 1.0 RPM BHP 1020 1044 1070 1096 1123 1150 1177 1205 1234 0.71 0.78 0.86 0.95 1.04 1.14 1.25 1.37 1.49 1.2 RPM 1089 1113 1138 1163 1189 --------- 2.0 RPM BHP ------------------- ------------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035). 580J*05 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 1 Phase 4 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.26 778 0.37 871 0.47 952 0.57 0.31 810 0.43 901 0.54 981 0.65 0.36 842 0.49 931 0.62 1010 0.74 0.42 875 0.57 963 0.70 1040 0.84 0.49 909 0.65 994 0.79 1070 0.94 0.57 943 0.73 1027 0.89 1101 1.05 0.66 978 0.83 1060 1.00 1133 1.16 0.75 1014 0.94 1093 1.11 1165 1.29 0.85 1049 1.05 1127 1.24 1198 1.42 0.2 RPM 666 701 737 773 810 847 885 923 962 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP RPM BHP Medium Static Option Field---Supplied Drive1 0.77 1155 0.87 1213 0.96 1268 1.05 0.87 1181 0.98 1239 1.08 1294 1.18 0.98 1208 1.09 --------1.09 ----------------------------------------------------------------------------------- 1.0 RPM BHP 1025 1053 1081 1110 1140 1170 1200 1231 1263 0.67 0.76 0.86 0.96 1.08 1.20 1.32 1.46 1.61 1.2 RPM 1093 1119 1147 1175 ----------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035). 56 2.0 RPM BHP 1321 ----------------- 1.14 ----------------- APPENDIX III. FAN PERFORMANCE (cont.) CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 3 Phase 4 Ton Horizontal Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.23 762 0.34 859 0.46 944 0.58 0.28 790 0.40 886 0.52 969 0.65 0.33 819 0.45 913 0.58 996 0.72 0.38 849 0.52 941 0.66 1023 0.80 0.45 879 0.59 970 0.73 1050 0.88 0.52 910 0.67 999 0.82 1078 0.98 0.59 942 0.75 1029 0.91 1106 1.08 0.68 974 0.85 1059 1.02 1135 1.19 0.77 1006 0.95 1090 1.13 1165 1.31 0.2 RPM 643 675 707 740 773 807 841 875 910 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 0.84 1153 0.98 1213 1.12 1270 1.27 0.92 1177 1.06 1237 1.21 1293 1.36 1.01 1201 1.15 1261 1.31 1317 1.47 1.10 1226 1.25 1285 1.41 1341 1.58 1.20 1252 1.36 1310 1.53 1365 1.70 1.31 1277 1.48 1335 1.65 1390 1.83 1.42 1303 1.60 1361 1.78 1415 1.96 1.55 1330 1.73 1387 1.92 1441 2.11 1.68 1357 1.87 1414 2.07 1467 2.26 1.0 RPM BHP 1020 1044 1070 1096 1123 1150 1177 1205 1234 0.71 0.78 0.86 0.95 1.04 1.14 1.25 1.37 1.49 1.2 RPM 1089 1113 1138 1163 1189 1216 1242 1270 1297 2.0 RPM BHP 1324 1347 1370 1394 1418 1442 1467 1493 --- 1.42 1.52 1.63 1.75 1.87 2.01 2.15 2.30 --- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041). 580J*05 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 3 Phase 4 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.26 778 0.37 871 0.47 952 0.57 0.31 810 0.43 901 0.54 981 0.65 0.36 842 0.49 931 0.62 1010 0.74 0.42 0.57 963 0.70 1040 0.84 875 0.49 909 0.65 994 0.79 1070 0.94 0.57 943 0.73 1027 0.89 1101 1.05 0.66 978 0.83 1060 1.00 1133 1.16 0.75 1014 0.94 1093 1.11 1165 1.29 0.85 1049 1.05 1127 1.24 1198 1.42 0.2 RPM 666 701 737 773 810 847 885 923 962 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 0.77 1155 0.87 1213 0.96 1268 1.05 0.87 1181 0.98 1239 1.08 1294 1.18 0.98 1208 1.09 1265 1.21 1320 1.32 1.09 1235 1.22 1292 1.34 1346 1.46 1.21 1263 1.35 1320 1.48 1373 1.61 1.34 1292 1.49 1348 1.63 1401 1.77 1.48 1321 1.64 1376 1.79 1428 1.94 1.63 1350 1.79 1405 1.96 1457 2.12 1.79 1380 1.96 1434 2.13 1486 2.31 1.0 RPM BHP 1025 1053 1081 1110 1140 1170 1200 1231 1263 0.67 0.76 0.86 0.96 1.08 1.20 1.32 1.46 1.61 1.2 RPM 1093 1119 1147 1175 1204 1233 1262 1293 1323 2.0 RPM BHP 1321 1346 1371 1397 1424 1451 1479 1506 --- 1.14 1.28 1.43 1.58 1.74 1.91 2.09 2.28 --- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041). 57 580J 580J*05 APPENDIX III. FAN PERFORMANCE (cont.) 580J*06 CFM 580J 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 1 Phase 5 Ton Horizontal Supply 0.2 RPM BHP RPM 800 849 899 950 1001 1053 1106 1159 --- 0.39 0.48 0.59 0.70 0.84 0.99 1.16 1.34 --- 904 947 992 1038 1085 1133 1182 1231 --- 1.2 RPM BHP RPM 1247 1276 1308 1342 ----------- 0.98 1.10 1.22 1.37 ----------- 1320 1348 1377 ------------- AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.49 999 0.60 1087 0.59 1038 0.70 1122 0.70 1078 0.82 1159 0.82 1120 0.95 1198 0.96 1163 1.09 1238 1.12 1208 1.26 1280 1.29 1254 1.44 --1.49 --------------AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM Medium Static Option 1.13 1390 1.28 1457 1.24 1416 1.40 --1.38 ------------------------------------------------------- BHP 0.72 0.83 0.95 1.08 1.23 1.40 ------- 1.0 RPM BHP Medium Static Option 1169 0.85 1201 0.96 1235 1.08 1271 1.22 1309 1.38 ----------------2.0 BHP RPM BHP 1.44 ----------------- ------------------- ------------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 580J*06 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 1 Phase 0.2 RPM BHP 848 897 947 997 1048 1100 1152 1205 --- 0.42 0.51 0.61 0.72 0.85 1.00 1.16 1.34 --1.2 RPM BHP 1312 1350 1390 ------------- 1.07 1.21 1.36 ------------- 5 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 968 0.55 1069 0.68 1158 0.80 1238 1013 0.65 1111 0.79 1198 0.93 1277 1059 0.76 1155 0.91 1240 1.06 1318 1105 0.89 1199 1.05 1283 1.21 1359 1153 1.03 1244 1.20 1326 1.37 --1201 1.19 1290 1.37 ------1250 1.36 --------------------------------------AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option Field---Supplied Drive1 1380 1.20 1445 1.34 1506 1.48 --1418 1.35 1482 1.50 --------------------------------------------------------------------------------------------------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039). 58 BHP 0.94 1.07 1.21 1.37 ----------- BHP ------------------- APPENDIX III. FAN PERFORMANCE (cont.) CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 3 Phase 5 Ton Horizontal Supply 0.2 RPM BHP RPM 800 849 899 950 1001 1053 1106 1159 1212 0.39 0.48 0.59 0.70 0.84 0.99 1.16 1.34 1.55 904 947 992 1038 1085 1133 1182 1231 1281 1.2 RPM BHP RPM 1247 1276 1308 1342 1377 1414 1452 1492 1533 0.98 1.10 1.22 1.37 1.53 1.71 1.91 2.12 2.36 1320 1348 1377 1409 1442 1477 1514 1551 1591 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.49 999 0.60 1087 0.59 1038 0.70 1122 0.70 1078 0.82 1159 0.82 1120 0.95 1198 0.96 1163 1.09 1238 1.12 1208 1.26 1280 1.29 1254 1.44 1323 1.49 1300 1.64 1367 1.70 1348 1.86 1412 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM Medium Static Option 1.13 1390 1.28 1457 1.24 1416 1.40 1481 1.38 1444 1.53 1507 1.52 1473 1.69 1536 1.69 1505 1.86 1565 1.87 1538 2.04 1597 2.08 1573 2.25 1630 2.30 1609 2.48 1665 2.54 1647 2.73 --- BHP 0.72 0.83 0.95 1.08 1.23 1.40 1.59 1.80 2.02 BHP 1.44 1.56 1.70 1.86 2.03 2.22 2.43 2.66 --- 1.0 RPM BHP Medium Static Option 1169 0.85 1201 0.96 1235 1.08 1271 1.22 1309 1.38 1348 1.55 1389 1.74 1430 1.96 1473 2.19 2.0 RPM BHP High Static Option 1522 1.61 1544 1.73 1569 1.87 1596 2.03 1624 2.21 1654 2.40 1686 2.62 1719 2.85 ----- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042). 580J*06 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 3 Phase 0.2 RPM BHP 848 897 947 997 1048 1100 1152 1205 1258 0.42 0.51 0.61 0.72 0.85 1.00 1.16 1.34 1.54 1.2 RPM BHP 1312 1350 1390 1430 1471 1513 1555 1598 1642 1.07 1.21 1.36 1.53 1.72 1.92 2.13 2.37 2.63 5 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 968 0.55 1069 0.68 1158 0.80 1238 1013 0.65 1111 0.79 1198 0.93 1277 1059 0.76 1155 0.91 1240 1.06 1318 1105 0.89 1199 1.05 1283 1.21 1359 1153 1.03 1244 1.20 1326 1.37 1401 1201 1.19 1290 1.37 1370 1.55 1444 1250 1.36 1336 1.55 1415 1.75 1487 1299 1.55 1384 1.76 1460 1.96 1532 1349 1.76 1431 1.98 1506 2.20 1576 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 1380 1.20 1445 1.34 1506 1.48 1564 1418 1.35 1482 1.50 1542 1.64 1600 1457 1.51 1520 1.67 1580 1.83 1637 1496 1.69 1559 1.86 1618 2.02 1675 1536 1.89 1598 2.06 1657 2.24 1713 1577 2.10 1638 2.28 1696 2.47 1752 1619 2.33 1679 2.52 1736 2.72 --1661 2.57 1720 2.78 ------1704 2.84 ----------- BHP 0.94 1.07 1.21 1.37 1.54 1.73 1.94 2.17 2.41 BHP 1.62 1.79 1.98 2.19 2.41 2.65 ------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042). 59 580J 580J*06 APPENDIX III. FAN PERFORMANCE (cont.) 580J*07 CFM 580J 1800 1950 2100 2250 2400 2550 2700 2850 3000 CFM 1800 1950 2100 2250 2400 2550 2700 2850 3000 3 Phase 6 Ton Horizontal Supply 0.2 RPM BHP Field---Supplied Drive1 913 0.64 972 0.78 1032 0.95 1093 1.14 1155 1.36 1217 1.60 1280 1.87 1343 2.17 1406 2.50 RPM 1010 1065 1120 1177 1234 1293 1352 1412 1472 1.2 RPM BHP RPM 1322 1366 1411 1457 1505 1554 1604 1656 --- 1.56 1.75 1.97 2.21 2.48 2.78 3.10 3.46 --- 1388 1430 1473 1518 1564 1612 1660 ----- AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.80 1098 0.98 1178 0.96 1148 1.14 1226 1.14 1200 1.33 1275 1.34 1254 1.55 1325 1.57 1308 1.78 1377 1.82 1363 2.05 1430 2.10 1420 2.34 1484 2.42 1477 2.67 1539 2.76 1535 3.03 1595 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM Medium Static Option 1.77 1451 1.98 1510 1.97 1491 2.20 1550 2.20 1533 2.43 1590 2.45 1576 2.69 1632 2.73 1621 2.98 1676 3.03 1667 3.30 1721 3.37 1715 3.64 ------------------- BHP 1.16 1.34 1.54 1.76 2.01 2.28 2.59 2.93 3.29 BHP 2.21 2.43 2.67 2.94 3.24 3.57 ------- 1.0 RPM BHP Medium Static Option 1252 1.35 1298 1.54 1345 1.75 1393 1.98 1443 2.24 1494 2.53 1546 2.84 1599 3.19 1653 3.57 2.0 RPM BHP High Static Option 1568 2.44 1606 2.67 1645 2.92 1686 3.20 1729 3.51 ----------------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number KR29AF035). 580J*07 CFM 1800 1950 2100 2250 2400 2550 2700 2850 3000 CFM 1800 1950 2100 2250 2400 2550 2700 2850 3000 3 Phase 0.2 RPM BHP 967 1029 1091 1154 1218 1283 1348 1414 1479 0.63 0.77 0.93 1.11 1.32 1.55 1.80 2.09 2.40 6 Ton Vertical Supply AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM Standard Static Option Medium Static Option 1075 0.80 1170 0.97 1255 1.13 1333 1132 0.96 1223 1.14 1306 1.32 1382 1189 1.14 1278 1.33 1358 1.52 1433 1248 1.33 1333 1.55 1411 1.75 1484 1308 1.55 1390 1.78 1466 2.01 1537 1369 1.80 1448 2.05 1521 2.29 1590 1431 2.07 1507 2.33 1578 2.59 1645 1493 2.37 1566 2.65 1636 2.92 1701 1556 2.70 1627 3.00 1694 3.29 1757 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 1.43 1475 1.58 1540 1.72 1601 1.87 1.65 1521 1.82 1585 1.98 1645 2.13 1.89 2.07 1631 2.25 1690 2.42 1568 2.15 1617 2.35 1678 2.54 1737 2.73 2.44 1666 2.65 1727 2.86 1784 3.06 2.75 1717 2.98 1776 3.20 1833 3.42 3.09 1769 3.33 1827 3.57 ----3.45 --------------------------- 1.2 RPM 1406 1454 1502 1552 1603 1655 1709 1763 --- BHP 1.28 1.49 1.71 1.96 2.23 2.52 2.84 3.19 3.57 2.0 RPM BHP 1660 1703 1747 1793 1839 1887 ------- 2.00 2.29 2.59 2.92 3.26 3.64 ------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR29AF042). 60 APPENDIX III. FAN PERFORMANCE (cont.) CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 3 PHASE 7.5 TON HORIZONTAL SUPPLY 0.2 RPM BHP RPM 505 533 562 591 621 652 682 713 745 0.52 0.62 0.74 0.88 1.03 1.21 1.40 1.61 1.85 586 610 635 661 688 715 743 772 801 1.2 RPM BHP 838 854 872 890 910 930 951 973 996 1.81 1.96 2.12 2.31 2.51 2.74 2.99 3.26 3.55 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.73 657 0.97 722 0.85 679 1.09 742 0.98 701 1.23 762 1.13 725 1.39 783 1.29 749 1.57 806 1.48 774 1.77 829 1.68 800 1.98 853 1.91 826 2.22 878 2.15 853 2.48 903 BHP 1.22 1.36 1.51 1.68 1.87 2.07 2.30 2.55 2.82 1.0 RPM BHP Medium Static Option 782 1.50 800 1.65 819 1.81 839 1.98 859 2.18 881 2.40 903 2.63 927 2.89 951 3.18 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 891 2.12 941 2.46 988 2.82 1033 906 2.28 955 2.63 1001 2.99 1046 922 2.46 970 2.81 1016 3.17 1060 940 2.65 986 3.01 1031 3.38 1074 958 2.86 1004 3.23 1048 3.61 1090 977 3.10 1022 3.47 1065 3.86 1107 997 3.35 1041 3.74 1083 4.13 1124 1018 3.63 1061 4.02 1103 4.43 1143 1040 3.93 1082 4.34 1122 4.75 1162 BHP 3.19 3.37 3.56 3.77 4.01 4.26 4.54 4.85 5.18 NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054). 580J*08 CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 CFM 2250 2438 2625 2813 3000 3188 3375 3563 3750 3 PHASE 7.5 TON VERTICAL SUPPLY 0.2 RPM BHP RPM 513 541 570 600 629 660 690 721 752 0.54 0.65 0.77 0.91 1.07 1.25 1.45 1.67 1.91 595 620 645 672 699 726 754 783 812 1.2 RPM BHP 839 858 878 899 920 942 964 988 1011 1.86 2.02 2.20 2.40 2.62 2.86 3.12 3.41 3.71 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.76 665 1.01 728 0.89 688 1.14 750 1.02 712 1.29 772 1.18 736 1.46 794 1.35 761 1.64 818 1.54 787 1.85 842 1.75 813 2.07 867 1.98 840 2.32 892 2.24 867 2.59 918 BHP 1.27 1.42 1.58 1.76 1.95 2.17 2.41 2.67 2.95 1.0 RPM BHP Medium Static Option 786 1.56 806 1.71 827 1.88 848 2.07 871 2.28 894 2.51 917 2.76 941 3.03 966 3.32 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 889 2.18 935 2.52 980 2.87 1022 907 2.35 953 2.70 997 3.06 1039 926 2.54 972 2.89 1015 3.26 1056 946 2.75 991 3.11 1033 3.49 1074 966 2.98 1010 3.35 1052 3.74 1093 987 3.23 1031 3.61 1072 4.01 1112 1009 3.50 1052 3.89 1093 4.30 1132 1032 3.80 1074 4.20 1114 4.61 1152 1054 4.11 1096 4.53 1135 4.95 --- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054). 61 BHP 3.23 3.43 3.64 3.88 4.14 4.42 4.72 5.04 --- 580J 580J*08 APPENDIX III. FAN PERFORMANCE (cont.) 580J*09 CFM 580J 2550 2763 2975 3188 3400 3613 3825 4038 4250 CFM 2550 2763 2975 3188 3400 3613 3825 4038 4250 3 PHASE 8.5 TON HORIZONTAL SUPPLY 0.2 RPM BHP Field---Supplied Drive1 497 0.48 524 0.58 551 0.70 580 0.84 609 1.00 638 1.17 668 1.37 698 1.59 728 1.83 1.2 RPM BHP 833 849 865 883 902 921 941 963 984 1.21 1.36 1.52 1.70 1.90 2.13 2.37 2.63 2.92 RPM 579 602 626 651 677 703 730 758 786 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.61 651 0.75 717 0.72 671 0.87 735 0.86 693 1.01 754 1.00 716 1.17 775 1.17 739 1.35 797 1.35 763 1.54 819 1.56 788 1.76 842 1.79 813 2.00 866 2.04 839 2.26 890 BHP 0.90 1.03 1.18 1.34 1.53 1.73 1.96 2.20 2.47 1.0 RPM BHP Medium Static Option 777 1.05 794 1.19 812 1.35 831 1.52 851 1.71 871 1.93 893 2.16 915 2.42 938 2.70 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 886 1.38 936 1.56 984 1.74 1029 900 1.53 950 1.72 996 1.90 1041 916 1.70 964 1.89 1010 2.09 1054 933 1.89 980 2.09 1025 2.29 1068 950 2.10 996 2.30 1041 2.51 1083 969 2.33 1014 2.54 1057 2.76 1099 988 2.58 1032 2.80 1075 3.02 1116 1008 2.86 1051 3.08 1093 3.31 1133 1029 3.15 1071 3.39 1112 3.63 1152 BHP 1.93 2.10 2.29 2.50 2.73 2.98 3.25 3.55 3.87 NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AF055). 2. Recommend using field --- supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054). 580J*09 CFM 2550 2763 2975 3188 3400 3613 3825 4038 4250 CFM 2550 2763 2975 3188 3400 3613 3825 4038 4250 3 PHASE 8.5 TON VERTICAL SUPPLY 0.2 RPM BHP RPM 526 557 588 621 653 687 720 754 788 0.51 0.62 0.75 0.90 1.06 1.25 1.45 1.69 1.94 600 627 655 684 714 744 775 807 839 1.2 RPM BHP 836 855 875 897 919 943 967 992 1018 1.20 1.37 1.56 1.77 1.99 2.24 2.51 2.80 3.11 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.65 666 0.79 727 0.77 690 0.92 749 0.91 716 1.08 772 1.07 743 1.25 797 1.25 770 1.44 822 1.45 798 1.65 849 1.67 827 1.88 876 1.91 856 2.13 904 2.17 886 2.41 932 BHP 0.93 1.08 1.24 1.42 1.62 1.84 2.09 2.35 2.64 1.0 RPM BHP Medium Static Option 783 1.07 804 1.23 825 1.40 848 1.60 872 1.81 897 2.04 922 2.30 949 2.57 976 2.88 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 886 1.34 934 1.48 979 1.61 1022 904 1.52 950 1.67 995 1.82 1037 923 1.72 968 1.88 1012 2.04 1053 943 1.94 987 2.11 1030 2.29 1071 964 2.18 1007 2.36 1049 2.55 1089 986 2.44 1029 2.63 1069 2.83 1108 1010 2.71 1051 2.92 1090 3.13 1129 1034 3.02 1074 3.24 1112 3.46 1150 1058 3.34 1097 3.57 ------- BHP 1.74 1.97 2.20 2.46 2.73 3.02 3.34 3.68 --- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054). 62 APPENDIX III. FAN PERFORMANCE (cont.) CFM 3000 3250 3500 3750 4000 4250 4500 4750 5000 CFM 3000 3250 3500 3750 4000 4250 4500 4750 5000 3 PHASE 10 TON HORIZONTAL SUPPLY 0.2 RPM BHP Field---Supplied Drive1 579 0.70 613 0.85 648 1.03 683 1.23 719 1.45 756 1.71 792 1.99 830 2.31 867 2.66 RPM 660 690 721 753 786 819 853 888 923 1.2 RPM BHP RPM 917 938 961 985 1011 1037 1064 1091 1120 1.70 1.93 2.18 2.46 2.76 3.09 3.46 3.85 4.28 970 991 1013 1035 1059 1084 1110 1137 1164 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.89 732 1.09 799 1.06 760 1.27 823 1.25 788 1.48 850 1.47 817 1.71 877 1.71 848 1.97 905 1.98 879 2.26 934 2.28 910 2.57 964 2.62 943 2.92 995 2.98 976 3.30 1026 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM Medium Static Option 1.91 1021 2.13 1070 2.16 1041 2.38 1089 2.42 1062 2.66 1108 2.71 1083 2.97 1129 3.03 1106 3.30 1151 3.38 1130 3.66 1174 3.76 1155 4.06 1198 4.16 1180 4.48 1222 4.61 1207 4.94 --- BHP 1.29 1.49 1.71 1.96 2.23 2.53 2.87 3.23 3.63 BHP 2.34 2.61 2.91 3.23 3.58 3.95 4.36 4.80 --- 1.0 RPM BHP Medium Static Option 860 1.50 883 1.71 907 1.95 933 2.21 959 2.50 987 2.81 1015 3.16 1044 3.54 1074 3.95 2.0 RPM BHP High Static Option 1117 2.56 1134 2.85 1153 3.15 1173 3.49 1194 3.85 1216 4.24 1239 4.66 1263 5.12 ----- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051). 2. Recommend using field --- supplied motor pulley (part no. KR11HY410). 580J*12 CFM 3000 3250 3500 3750 4000 4250 4500 4750 5000 CFM 3000 3250 3500 3750 4000 4250 4500 4750 5000 3 PHASE 10 TON VERTICAL SUPPLY 0.2 RPM BHP RPM 616 655 695 736 777 818 860 902 944 0.79 0.96 1.17 1.41 1.68 1.98 2.32 2.69 3.11 689 724 760 797 834 873 912 951 991 1.2 RPM BHP 939 962 987 1014 1042 1072 1103 1135 1167 1.79 2.03 2.30 2.60 2.93 3.30 3.70 4.14 4.63 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM Standard Static Option 0.97 757 1.16 821 1.16 788 1.37 849 1.38 821 1.60 879 1.63 855 1.86 910 1.91 889 2.16 942 2.23 925 2.49 976 2.58 962 2.85 1010 2.97 999 3.26 1046 3.40 1037 3.70 1082 BHP 1.36 1.58 1.83 2.10 2.41 2.75 3.13 3.55 4.00 1.0 RPM BHP Medium Static Option 882 1.57 907 1.80 934 2.06 963 2.35 993 2.67 1025 3.02 1057 3.41 1091 3.84 1125 4.31 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM Medium Static Option High Static Option 994 2.01 1047 2.24 1098 2.47 1147 1015 2.26 1066 2.50 1115 2.75 1163 1038 2.54 1088 2.80 1135 3.05 1181 1063 2.86 1111 3.12 1157 3.39 1202 1090 3.20 1136 3.48 1180 3.76 1224 1118 3.58 1162 3.87 1205 4.16 1247 1147 4.00 1190 4.29 1232 4.60 1273 1177 4.45 1219 4.76 1259 5.08 --1209 4.95 ----------- NOTE: For more information, see General Fan Performance Notes on page 53. Boldface indicates field --- supplied drive is required. 1. Recommend using field --- supplied motor pulley (part no. KR11HY410). 63 BHP 2.71 3.00 3.32 3.66 4.04 4.46 4.91 ----- 580J 580J*12 APPENDIX III. FAN PERFORMANCE (cont.) Pulley Adjustment 1 phase 3 phase 05 3 phase 3 phase 3 phase 3 phase 3 phase 06 07 08 09 12 580J 1 phase 3 phase 04 1 phase UNIT MOTOR/DRIVE COMBO 0.0 0.5 1.0 MOTOR PULLEY TURNS OPEN 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Standard Static 854 825 795 766 736 707 678 648 619 589 560 Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Static --- --- --- --- --- --- --- --- --- --- --- Standard Static 854 825 795 766 736 707 678 648 619 589 560 Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035 Standard Static 854 825 795 766 736 707 678 648 619 589 560 Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Static --- --- --- --- --- --- --- --- --- --- --- Standard Static 854 825 795 766 736 707 678 648 619 589 560 Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035 Standard Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 Medium Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035 High Static --- --- --- --- --- --- --- --- --- --- --- Standard Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 Medium Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035 High Static 1687 1649 1610 1572 1533 1495 1457 1418 1380 1341 1303 Standard Static 1457 1419 1380 1342 1303 1265 1227 1188 1150 1111 1073 Medium Static 1518 1484 1449 1415 1380 1346 1311 1277 1242 1208 1173 High Static 1788 1757 1725 1694 1662 1631 1600 1568 1537 1505 1474 Standard Static 747 721 695 670 644 618 592 566 541 515 489 Medium Static 949 927 906 884 863 841 819 798 776 755 733 High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909 Standard Static 733 712 690 669 647 626 604 583 561 540 518 Medium Static 936 911 887 862 838 813 788 764 739 715 690 High Static 1084 1059 1035 1010 986 961 936 912 887 863 838 Standard Static 838 813 789 764 739 715 690 665 640 616 591 Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838 High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022 NOTE: Do not adjust pulley further than 5 turns open. --- Factory settings 64 APPENDIX IV. ELECTRICAL DATA 3 TONS V ---Ph---Hz VOLTAGE RANGE MIN MAX 208--- 1--- 60 187 230--- 1--- 60 COMP (ea) OFM (ea) RLA LRA WATTS FLA 253 16.6 79 325 1.5 187 253 16.6 79 325 1.5 208--- 3--- 60 187 253 10.4 73 325 1.5 230--- 3--- 60 187 253 10.4 73 325 1.5 460--- 3--- 60 414 506 5.8 38 325 0.8 575--- 3--- 60 518 633 3.8 37 325 0.6 580J*05 TYPE Std Static Med Static Std Static Med Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Max WATTS 1000 1000 1000 1000 1000 1000 2120 1000 1000 2120 1000 2120 2120 1000 2120 2120 IFM Max AMP Draw 5.1 5.1 5.1 5.1 5.1 5.1 5.5 5.1 5.1 5.5 2.2 2.7 2.7 2.0 2.1 2.1 Max WATTS 1000 1850 1000 1850 1000 1000 2120 1000 1000 2120 1000 2120 2120 1000 2120 2120 IFM Max AMP Draw 5.1 7.4 5.1 7.4 5.1 5.1 5.5 5.1 5.1 5.5 2.2 2.7 2.7 2.0 2.1 2.1 EFF at Full Load FLA 70% 70% 70% 70% 70% 70% 80% 70% 70% 80% 70% 80% 80% 71% 80% 80% 4.9 4.9 4.9 4.9 4.9 4.9 5.2 4.9 4.9 5.2 2.1 2.6 2.6 1.9 2.0 2.0 EFF at Full Load FLA 70% 78% 70% 78% 70% 70% 80% 70% 70% 80% 70% 80% 80% 71% 80% 80% 4.9 7.0 4.9 7.0 4.9 4.9 5.2 4.9 4.9 5.2 2.1 2.6 2.6 1.9 2.0 2.0 4 TONS V ---Ph---Hz VOLTAGE RANGE MIN MAX 208--- 1--- 60 187 230--- 1--- 60 COMP (ea) OFM (ea) RLA LRA WATTS FLA 253 21.8 117 325 1.5 187 253 21.8 117 325 1.5 208--- 3--- 60 187 253 13.7 83 325 1.5 230--- 3--- 60 187 253 13.7 83 325 1.5 460--- 3--- 60 414 506 6.2 41 325 0.8 575--- 3--- 60 518 633 4.8 37 325 0.6 TYPE Std Static Med Static Std Static Med Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static 65 580J 580J*04 APPENDIX IV. ELECTRICAL DATA (cont.) 580J 580J*06 5 TONS V ---Ph---Hz VOLTAGE RANGE MIN MAX 208--- 1--- 60 187 230--- 1--- 60 COMP (ea) OFM (ea) RLA LRA WATTS FLA 253 26.2 134 325 1.5 187 253 26.2 134 325 1.5 208--- 3--- 60 187 253 15.6 110 325 1.5 230--- 3--- 60 187 253 15.6 110 325 1.5 460--- 3--- 60 414 506 7.7 52 325 0.8 575--- 3--- 60 518 633 5.8 39 325 0.6 580J*07 TYPE Std Static Med Static Std Static Med Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Max WATTS 1000 1850 1000 1850 1000 2120 2615 1000 2120 2615 2120 2615 2615 2120 3775 3775 IFM Max AMP Draw 5.1 7.4 5.1 7.4 5.1 5.5 7.9 5.1 5.5 7.9 2.7 3.6 3.6 2.1 2.9 2.9 Max WATTS 2120 2615 3775 2120 2615 3775 2120 2615 3775 2120 3775 3775 IFM Max AMP Draw 5.5 7.9 10.7 5.5 7.9 10.7 2.7 3.6 5.0 2.1 2.9 2.9 EFF at Full Load FLA 70% 78% 70% 78% 70% 80% 81% 70% 80% 81% 80% 81% 81% 80% 81% 81% 4.9 7.0 4.9 7.0 4.9 5.2 7.5 4.9 5.2 7.5 2.6 3.4 3.4 2.0 2.8 2.8 EFF at Full Load FLA 80% 81% 81% 80% 81% 81% 80% 81% 81% 80% 81% 81% 5.2 7.5 10.2 5.2 7.5 10.2 2.6 3.4 4.8 2.0 2.8 2.8 6 TONS V ---Ph---Hz VOLTAGE RANGE MIN MAX 208--- 3--- 60 187 230--- 3--- 60 COMP (ea) OFM (ea) RLA LRA WATTS FLA 253 19.0 12 325 1.5 187 253 19.0 12 325 1.5 460--- 3--- 60 414 506 9.7 62 325 0.8 575--- 3--- 60 518 633 7.4 50 325 0.6 TYPE Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static 66 APPENDIX IV. ELECTRICAL DATA (cont.) V ---Ph---Hz 7.5 TONS VOLTAGE RANGE COMP (ea) OFM (ea) RLA LRA WATTS FLA MIN MAX 208--- 3--- 60 187 253 25.0 164 325 1.5 230--- 3--- 60 187 253 25.0 164 325 1.5 460--- 3--- 60 414 506 12.2 100 325 0.8 575--- 3--- 60 518 633 9.0 78 325 0.6 580J*09 V ---Ph---Hz TYPE Max WATTS Max AMP Draw Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static 1448 2278 4559 1448 2278 4559 1448 2278 4559 1379 3775 1870 5.5 7.9 15.8 5.5 7.9 15.8 2.7 3.6 7.8 2.5 2.9 5.9 Max WATTS 1448 2120 2694 1448 2120 2694 1448 2120 2694 1379 1390 3775 Max AMP Draw 5.5 5.5 10.5 5.5 5.5 10.5 2.7 2.7 4.6 2.5 2.1 2.9 EFF at Full Load 80% 81% 81% 80% 81% 81% 80% 81% 81% 80% 81% 81% FLA 5.2 7.5 15.0 5.2 7.5 15.0 2.6 3.4 7.4 2.4 2.8 5.6 8.5 TONS VOLTAGE RANGE MIN MAX COMP (ea) RLA LRA OFM (ea) WATTS FLA 208--- 3--- 60 187 253 29.5 195 325 1.5 230--- 3--- 60 187 253 29.5 195 325 1.5 460--- 3--- 60 414 506 14.7 95 325 0.8 575--- 3--- 60 518 633 12.2 80 325 0.6 580J*12 V ---Ph---Hz IFM IFM TYPE Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static EFF at Full Load FLA 80% 80% 80% 80% 80% 80% 80% 80% 80% 80% 80% 81% 5.2 5.2 10.0 5.2 5.2 10.0 2.6 2.6 4.4 2.4 2.0 2.8 EFF at Full Load FLA 80% 81% 81% 80% 81% 81% 80% 81% 81% 80% 81% 81% 5.2 10.0 15.0 5.2 10.0 15.0 2.6 4.4 7.4 2.0 2.8 5.6 10 TONS VOLTAGE RANGE COMP (ea) OFM (ea) MIN MAX RLA LRA WATTS FLA 208--- 3--- 60 187 253 30.1 225 325 1.5 230--- 3--- 60 187 253 30.1 225 325 1.5 460--- 3--- 60 414 506 16.7 114 325 0.8 575--- 3--- 60 518 633 12.2 80 325 0.6 IFM TYPE Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static Std Static Med Static High Static 67 Max WATTS 2120 3775 4559 2120 3775 4559 2120 3775 4559 1390 3775 1870 Max AMP Draw 5.5 10.5 15.8 5.5 10.5 15.8 2.7 4.6 7.8 2.1 2.9 5.9 580J 580J*08 APPENDIX IV. ELECTRICAL DATA (cont.) UNIT MCA/MOCP Determination No C.O. or UNPWRD C.O. NOM. V ---Ph---Hz 208/230--- 1--- 60 580J*04 208/230--- 3--- 60 460--- 3--- 60 580J 575--- 3--- 60 208/230--- 1--- 60 580J*05 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 208/230--- 1--- 60 580J*06 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 580J*07 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 IFM TYPE STD MED STD MED HIGH STD MED HIGH STD MED HIGH STD MED STD MED HIGH STD MED HIGH STD MED HIGH STD MED STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH COMBUSTION POWER FAN MOTOR EXHAUST FLA FLA 0.48 1.9 0.48 1.9 0.25 1.0 0.24 1.9 0.48 1.9 0.48 1.9 0.25 1.0 0.24 1.9 0.48 1.9 0.48 1.9 0.25 1.0 0.24 1.9 0.48 1.9 0.25 1.0 0.24 1.9 MCA 27.2 27.2 19.4 19.4 19.7 10.2 10.2 10.7 7.3 7.3 7.4 33.7 33.7 23.5 23.5 23.8 10.7 10.7 11.2 8.5 8.5 8.6 39.2 41.3 25.9 26.2 28.5 12.5 13.0 13.8 9.8 9.9 10.7 30.5 32.8 32.8 15.5 16.3 17.3 11.9 12.7 12.7 NO C.O. or UNPWRD C.O. NO P.E. w/ P.E. (pwrd fr/ unit) DISC. SIZE DISC. SIZE MOCP MCA MOCP FLA LRA FLA LRA 40.0 26 95 29.1 45.0 29 97 40.0 26 95 29.1 45.0 29 97 25.0 19 89 21.3 30.0 22 91 25.0 19 89 21.3 30.0 22 91 30.0 20 107 21.6 30.0 22 109 15.0 10 46 11.2 15.0 11 47 15.0 10 46 11.2 15.0 11 47 15.0 11 55 11.7 15.0 12 56 15.0 7 44 9.2 15.0 9 46 15.0 7 44 9.2 15.0 9 46 15.0 7 50 9.3 15.0 10 52 50.0 32 133 35.6 50.0 35 135 50.0 32 133 35.6 50.0 35 135 30.0 23 99 25.4 30.0 25 101 30.0 23 99 25.4 30.0 25 101 30.0 23 117 25.7 30.0 25 119 15.0 10 49 11.7 15.0 12 50 15.0 10 49 11.7 15.0 12 50 15.0 11 58 12.2 15.0 12 59 15.0 8 44 10.4 15.0 11 46 15.0 8 44 10.4 15.0 11 46 15.0 9 50 10.5 15.0 11 52 60.0 37 150 41.1 60.0 40 152 60.0 40 175 43.2 60.0 42 177 30.0 25 126 27.8 40.0 27 128 40.0 26 144 28.1 40.0 28 146 40.0 29 170 30.4 45.0 30 172 20.0 12 60 13.5 20.0 13 61 20.0 13 69 14.0 20.0 14 70 20.0 14 82 14.8 20.0 15 83 15.0 10 46 11.7 15.0 12 48 15.0 10 52 11.8 15.0 13 54 15.0 11 63 12.6 15.0 13 65 45.0 30 157 32.4 50.0 32 159 50.0 32 183 34.7 50.0 34 185 50.0 32 183 34.7 50.0 34 185 25.0 15 79 16.5 25.0 16 80 25.0 16 92 17.3 25.0 17 93 25.0 17 101 18.3 25.0 18 102 15.0 12 63 13.8 20.0 14 65 20.0 12 74 14.6 20.0 15 76 20.0 12 74 14.6 20.0 15 76 See notes on next page. 68 APPENDIX IV. ELECTRICAL DATA (cont.) UNIT NOM. V ---Ph---Hz IFM TYPE 580J*08 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 580J*09 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 580J*12 208/230--- 3--- 60 460--- 3--- 60 575--- 3--- 60 1Fuse STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH STD MED HIGH COMBUSTION FAN MOTOR FLA POWER EXHAUST FLA 0.48 3.8 0.25 1.8 0.24 3.8 0.48 3.8 0.25 1.8 0.24 3.8 0.48 3.8 0.25 1.8 0.24 3.8 NO C.O. or UNPWRD C.O. NO P.E. DISC. SIZE MCA MOCP FLA LRA 39.5 60 38 191 41.8 60 41 228 49.3 60 49 254 19.5 30 19 113 20.3 30 20 132 24.3 30 24 145 14.9 20 14 89 15.3 20 15 104 18.1 25 18 118 45.1 60 43 222 45.1 60 43 233 49.9 60 49 276 22.6 30 22 108 22.6 30 22 114 24.4 30 24 136 18.9 30 18 91 18.5 30 18 95 19.3 30 19 106 45.8 60 44 263 50.6 60 50 306 55.6 80 55 315 25.1 30 24 133 26.9 40 26 155 29.9 45 30 159 18.5 30 18 95 19.3 30 19 106 22.1 30 22 120 or breaker NO C.O. or UNPWRD C.O. w/ P.E. (pwrd fr/ unit) DISC. SIZE MCA MOCP FLA LRA 43.3 60 43 195 45.6 60 45 232 53.1 60 54 258 21.3 30 21 115 22.1 30 22 134 26.1 30 26 147 18.7 25 19 93 19.1 25 19 108 21.9 30 23 122 48.9 60 48 226 48.9 60 48 237 53.7 80 53 280 24.4 30 24 110 24.4 30 24 116 26.2 30 26 138 22.7 30 23 95 22.3 30 22 99 23.1 30 23 110 49.6 60 48 267 54.4 80 54 310 59.4 80 60 319 26.9 40 26 135 28.7 45 28 157 31.7 45 32 161 22.3 30 22 99 23.1 30 23 110 25.9 30 26 124 Example: Supply voltage is 230-3-60 LEGEND: CO --- Convenient outlet DISC --- Disconnect FLA --- Full load amps IFM --- Indoor fan motor LRA --- Locked rotor amps MCA --- Minimum circuit amps MOCP --- Maximum over current protection PE --- Power exhaust UNPWRD CO --- Unpowered convenient outlet NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. AB = 224 v BC = 231 v AC = 226 v Average Voltage = = (224 + 231 + 226) 3 = 681 3 227 Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 4 227 = 1.76% % Voltage Imbalance = 100 x max voltage deviation from average voltage average voltage This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 69 580J MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. APPENDIX V. WIRING DIAGRAM LIST Wiring Diagrams SIZE 04 05 580J 06 07 08 09 12 VOLTAGE 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---3---60 460---3---60 575---3---60 208/230---3---60 460---3---60 575---3---60 208/230---3---60 460---3---60 575---3---60 208/230---3---60 460---3---60 575---3---60 580J CONTROL 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500213.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 48TM500929.05 NOTE: Component arrangement on Control; Legend on Power Schematic 70 POWER 48TM500749.08 48TM500748.08 48TM500748.08 48TM500215.08 48TM500749.08 48TM500748.08 48TM500748.08 48TM500215.08 48TM500749.08 48TM500748.08 48TM500748.08 48TM500215.08 48TM500748.08 48TM500748.08 48TM500215.08 48TM500803.05 48TM500803.05 48TM500804.05 48TM500803.05 48TM500803.05 48TM500804.05 48TM500803.05 48TM500803.05 48TM500804.05 580J APPENDIX VI. MOTORMASTER SENSOR LOCATIONS C08259 Fig. 54 - 580J*04(A, B, C) Outdoor Circuiting Fig. 56 - 580J*07(A, C) Outdoor Circuiting C08260 Fig. 55 - 580J*05/06(A, B, C) Outdoor Circuiting Fig. 57 - 580J*08(A, C) Outdoor Circuiting 71 C08261 C08262 580J APPENDIX VI. MOTORMASTER SENSOR LOCATIONS (cont.) Fig. 58 - 580J*09/12(A, C) Outdoor Circuiting E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 07/08 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 72 C08263 Catalog No. SM580J---01 Replaces: NEW START-UP CHECKLIST I. (Remove and Store in Job File) PRELIMINARY INFORMATION MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: BUILDING LOCATION: II. PRE-START-UP (insert checkmark in box as each item is completed) j VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT j VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS 580J j VERIFY THAT FLUE HOOD IS INSTALLED j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS j CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES j CHECK GAS PIPING FOR LEAKS j CHECK THAT RETURN-- AIR FILTER IS CLEAN AND IN PLACE j VERIFY THAT UNIT INSTALLATION IS LEVEL j CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT j VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT III. START-UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR FAN AMPS L1-L2 L1 L1 L2-L3 L2 L2 L3-L1 L2 L2 TEMPERATURES OUTDOOR-AIR TEMPERATURE RETURN-AIR TEMPERATURE COOLING SUPPLY AIR GAS HEAT SUPPLY AIR DB DB DB DB WB WB WB PRESSURES GAS INLET PRESSURE GAS MANIFOLD PRESSURE REFRIGERANT SUCTION REFRIGERANT DISCHARGE IN. WG IN. WG (LOW FIRE) PSIG PSIG IN. WG (HI FIRE) TEMP _F TEMP _F j VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS j VERIFY THAT 3-- PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 07/08 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 73 Catalog No. SM580J---01 Replaces: NEW
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:08:07 14:16:12-04:00 Create Date : 2008:08:07 14:16:12-04:00 Format : application/pdf Title : sm580j-01 Creator : bact625 Producer : Acrobat Distiller 8.1.0 (Windows) Document ID : uuid:f414eff1-70fc-4731-ae1a-3f728c618240 Instance ID : uuid:23728f60-cd6e-48c8-81b1-5813d835985a Page Count : 73 Author : bact625EXIF Metadata provided by EXIF.tools