Elster Solutions RX9A AUTOMATIC METER READING SYSTEM TRANSCEIVER User Manual IL42 4026

Elster Solutions, LLC AUTOMATIC METER READING SYSTEM TRANSCEIVER IL42 4026

Contents

Installation Instructions

Download: Elster Solutions RX9A AUTOMATIC METER READING SYSTEM TRANSCEIVER User Manual IL42 4026
Mirror Download [FCC.gov]Elster Solutions RX9A AUTOMATIC METER READING SYSTEM TRANSCEIVER User Manual IL42 4026
Document ID765455
Application ID8YmszqV+WdDJqQSvFIL95A==
Document DescriptionInstallation Instructions
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize7.16kB (89490 bits)
Date Submitted2007-03-07 00:00:00
Date Available2007-03-07 00:00:00
Creation Date2003-12-16 10:51:29
Producing SoftwareAcrobat Distiller 6.0.1 (Windows)
Document Lastmod2005-08-31 10:55:24
Document TitleIL42-4026.fm
Document CreatorFrameMaker 7.1
Document Author: PAK

August 2005
IL42-4026D
IL42-4026D
REX™ Meter Installation Instructions
General
This leaflet contains installation instructions for the REX residential electronic watthour
meter with the following form factors:
■
self-contained: Forms 1S, 2S, and 12S
■
transformer-rated: Forms 3S and 4S
All meters are calibrated and sealed before shipment. For proper installation, accuracy, and
maximum life of the meters, use the following procedures.
WARNING
Use authorized utility procedures to install and service metering equipment. Dangerous
voltages are present. Equipment damage, personal injury, or death can result if safety
procedures are not followed.
WARNING
When using the REX meter with the internal service control switch, follow authorized utility
procedures to reconnect electrical service. Property damage, personal injury, or death can
result if safety precautions are not followed.
Installing the REX Meter
1. Make sure the meter to be installed matches service type (that is, form), current
class, capacity required, and service socket.
2. Check the socket and verify that the wiring is correct. See “Internal Wiring
Diagrams” on page 2 and “Installation Wiring Diagrams” on page 3 for all wiring
diagrams.
3. Make sure that the voltage disconnect or test link on the back of the meter is closed,
if installed.
4. Line up the meter blades to the socket jaws and rock the meter into place. Make
sure that the meter is in the upright position.
5. Make sure the LCD turns on and the energy use indicator flashes if load is present.
If load is applied, check that the pulse arrows on the LCD are blinking. The LCD has
two pulse arrows. The arrow pointing to the left indicates energy received; the
arrow pointing to the right indicates energy delivered. For more information, see the
technical manual for your meter.
6. Apply all seals and record any necessary information.
Elster Electricity, LLC
Raleigh, North Carolina USA
+1 800 338 5251 (US Technical Support)
+1 800 257 9754 (US Sales Support)
+1 919 212 4800 (US Main)
+1 905 634 4895 (Canada Main)
support@us.elster.com
www.elsterelectricity.com
IL42-4026D
August 2005
Internal Wiring Diagrams
WARNING
Use circuit-closing devices on current transformer secondaries used with Form 3S and
Form 4S meters. Dangerous currents and voltages are present. Equipment damage,
personal injury, or death can result if circuit-closing devices are not used.
PS
PS
Form 1S
Form 2S
Form 3S
PS
PS
Form 4S
Alternate positions of movable
potential terminal
Form 12S
31H05
PS
Alternate positions of movable
potential terminal
August 2005
IL42-4026D
Installation Wiring Diagrams
WARNING
Use circuit-closing devices on current transformer secondaries used with Form 3S and
Form 4S meters. Dangerous currents and voltages are present. Equipment damage,
personal injury, or death can result if circuit-closing devices are not used.
Service side
voltage
Service control
switch
Load side
voltage
20E01
Form 1S
1 phase, 2 wire
self–contained
Form 2S
1 phase, 3 wire with
service control swith (open)
self–contained
CIRCUIT
CLOSING
DEVICE
11G03
CIRCUIT
CLOSING
DEVICE
CIRCUIT
CLOSING
DEVICE
Form 3S
1 phase, 2 wire
1 CT, no VTs
11G03
Form 3S
1 phase, 3 wire
1 CT, no VTs
11G03
Form 2S
1 phase, 3 wire
self–contained
16L03
1 L
2 O
N D
20E01
Form 4S
1 Phase, 3 Wire
2 CTs, no VTs
IL42-4026D
August 2005
Service
control
switch
Service
side voltage
Form 12S
2 phase, 3 wire wye
self–contained
Load side
voltage
120/208 service
voltage only
25H05
29H05
120/208 service
voltage only
1 L
2 O
N D
1 L
2 O
ND
Form 12S
2 phase, 3 wire wye
self–contained
FCC and Industry Canada Compliance
Compliance Statement (Part 15.19): The REX meter complies with Part 15 of the FCC Rules and with RSS-210 of Industry
Canada. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) This device must
accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21): Changes or modifications not expressly approved by Elster Electricity, LLC could void the user’s authority to
operate the equipment.
RF Radiation Safety Guidelines per Part 2 of FCC Rules and Regulations: The meter should be installed in a location where
there will be a separation greater than 20 cm from locations occupied by humans.
User Information (Part 15.105): The REX meter has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, the
user is encouraged to try to correct the interference by one or more of the following measures:
■
Reorient or relocate the receiving antenna.
■
Move the receiving equipment farther away from the REX meter.
■
Consult the dealer or an experienced radio/TV technician for help.
Industry Canada Statement: The term “IC” before the certification/registration number only signifies that the Industry Canada
technical specifications were met.
DISCLAIMER OF WARRANTIES AND LIMITATIONS OF LIABILITY
There are no understandings, agreements, representations, or warranties either express or implied, including warranties of merchantability or fitness for a particular purpose, other than those specifically set out by any existing contract between the parties. Any such contract states the entire obligation of the seller. The contents of this document shall not become part of or modify any prior existing
agreement, commitment, or relationship.
The information, recommendations, descriptions, and safety notices in this document are based on Elster Electricity, LLC experience
and judgment with respect to operation and maintenance of the described product. This information should not be considered as allinclusive or covering all contingencies. If further information is required, Elster Electricity, LLC should be consulted.
No warranties, either expressed or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising
from the course of dealing or usage of trade, are made regarding the information, recommendations, descriptions, warnings, and cautions contained herein.
In no event will Elster Electricity, LLC be responsible to the user in contract, in tort (including negligence), strict liability or otherwise for
any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to: damage or loss of use of
equipment, cost of capital, loss of profits or revenues, or claims against the user by its customers resulting from the use of the information, recommendations, descriptions, and safety notices contained herein.
Elster Electricity, LLC
Raleigh, North Carolina USA
 
*IL42-4026D*
© 2005 by Elster Electricity, LLC.
All rights reserved.
Printed in the United States.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Copy, Extract, Print high-res
Page Count                      : 4
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:005761d5-c476-46e0-a586-a7f9750adba3
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Create Date                     : 2003:12:16 10:51:29Z
Creator Tool                    : FrameMaker 7.1
Modify Date                     : 2005:08:31 10:55:24-04:00
Metadata Date                   : 2005:08:31 10:55:24-04:00
Document ID                     : uuid:f8b0ec33-ae40-4e6b-b5c4-4a54cfc0ac0d
Format                          : application/pdf
Creator                         : PAK
Title                           : IL42-4026.fm
Author                          : PAK
EXIF Metadata provided by EXIF.tools
FCC ID Filing: QZC-RX9A

Navigation menu