Emerson Liebert Gxt3 Ups 120V 208V 500Va 3000Va Users Manual

Emerson-Liebert-Gxt3-On-Line-Ups-500-3000Va-User-Guide-679636 emerson-liebert-gxt3-on-line-ups-500-3000va-user-guide-679636

Manual-UPS-Liebert-G.. Manual-UPS-Liebert-GXT3-500-3000-VA-Ingles

Manual-UPS-Liebert-G.. Manual-UPS-Liebert-GXT3

Manual-UPS-Liebert-G.. Manual-UPS-Liebert-GXT3

208V to the manual aed2cb3b-1de0-499e-982b-7636b691ce0f

2015-01-05

: Emerson Emerson-Liebert-Gxt3-Ups-120V-208V-500Va-3000Va-Users-Manual-165402 emerson-liebert-gxt3-ups-120v-208v-500va-3000va-users-manual-165402 emerson pdf

Open the PDF directly: View PDF PDF.
Page Count: 48

DownloadEmerson Emerson-Liebert-Gxt3-Ups-120V-208V-500Va-3000Va-Users-Manual-  Emerson-liebert-gxt3-ups-120v-208v-500va-3000va-users-manual
Open PDF In BrowserView PDF
AC Power
For Business-Critical Continuity™

Liebert® GXT3™ UPS 120V/208V 500VA-3000VA
User Manual

TABLE OF CONTENTS
IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.0

PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

1.1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.2

Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.3

Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.1
1.3.2

Front Panel and Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.4

Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.5

Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.1
1.5.2
1.5.3
1.5.4
1.5.5

Utility (AC) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2.0

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.1

Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.2

What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.3

Preparation for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.1

2.4

Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4.1
2.4.2

2.5

Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.1
2.5.2

2.6

Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Connecting Input Plug and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.6.1
2.6.2

Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing the Optional Liebert IntelliSlot® Card and Communication Cables . . . . . . . . . . . 18

3.0

CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3.1

Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.1
3.1.2

3.2

On/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.1
3.2.2

Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

i

4.0

OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

4.1

Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4.2

Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4.3

Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4.4

Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4.5

Shut Down the Liebert® GXT3™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

4.6

Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

5.0

COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

5.1

Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.1.1

5.2

USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2.1

5.3

Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.1
5.3.2
5.3.3
5.3.4

Any-Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

26
27
27
27

6.0

MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

6.1

Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.1.1

Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

6.2

Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

6.3

Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

6.4

Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

6.5

Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

7.0

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

7.1

UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.1.1
7.1.2

Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

7.2

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

8.0

BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

9.0

SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

9.1

Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

ii

FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26

Liebert GXT3 rack/tower models—front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Liebert GXT3 minitower—front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Liebert® GXT3™ 120V rack/tower models—rear panel components . . . . . . . . . . . . . . . . . . . . . . . . 6
Liebert® GXT3™ 208V rack/tower models—rear panel components . . . . . . . . . . . . . . . . . . . . . . . . 7
Liebert GXT3-1000MT120™—rear panel components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Pulling inner member from each slide rail assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing rear member of each slide rail assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing front member of each slide rail assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fastening rear member and front member together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installing inner members . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installing rack-mount handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Insert the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Load level indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Terminal block communication pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Removing the front bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . 29
Pull out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15

UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Input circuit breaker specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Functions of On/Alarm Silence/Manual battery test button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Functions of Standby/Manual Bypass button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Output voltage option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Replacement internal battery pack model number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Specifications of GXT3-500RT120 - GXT3-1000RT120 and GXT3-1000MT120 UPS . . . . . . . . . . 35
Specifications of GXT3-1500RT120 - GXT3-3000RT120 and GXT3-3000RT208 UPS . . . . . . . . . 36
Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

iii

iv

IMPORTANT SAFETY PRECAUTIONS

! WARNING
Observe all cautions and warnings in this manual. Failure to do so may result in serious

injury or death.
Refer all UPS and battery service to properly trained and qualified service personnel. Do not
attempt to service this product yourself.
Opening or removing the cover may expose you to lethal voltages within this unit even when
it is apparently not operating and the input wiring is disconnected from the electrical source.
Never work alone.

SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or
operate this UPS.

UPS Safety Notes
This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass
push button does not electrically isolate internal parts. Under no circumstances attempt to gain
internal access other than to replace the batteries due to risk of electric shock or burn. Do not
continue to use the UPS if the front panel indications are not in accordance with these operating
instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Emerson
Network Power representative or Emerson Network Power Channel Support.
This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even
if the UPS is not connected to utility input power.
Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure
that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage,
presenting an electric shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, a short-circuit protection device must
be installed on the neutral line.
Install and use the Liebert® GXT3™ in the following environments:
• Temperature: 32°F - 104°F (0°C - 40°C), relative humidity: 0% ~ 95% non-condensing
• Out of direct sunlight
• Away from heat sources
• Stable surface, not subject to vibrations or shocks
• Away from dust and other particulates
• Away from corrosive substances, salts and flammable gases
Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal
temperature of the UPS and can adversely affect the UPS and its batteries.
Keep liquid and foreign objects away from the UPS.
In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher
may cause electric shock.
This UPS is not intended for use with life support and other designated critical devices. Maximum
load must not exceed that shown on the UPS rating label. This UPS is designed for data processing
equipment. If uncertain, consult your local dealer or Emerson representative.
This UPS is not for use in a computer room as defined in the standard for the Protection of Electronic
Computer/Data Processing Equipment, ANSI/NFPA 75.
The Liebert® GXT3-3000RT120™ was tested under 30A branch circuit in accordance with the
National Electrical Code, ANSI/NFPA 70. To reduce the risk of fire, connect only to a circuit provided
with 30A maximum branch overcurrent protection.

1

The Liebert® GXT3™-3000RT208 was tested under 20A branch circuit in accordance with the
National Electrical Code, ANSI/NFPA 70. To reduce the risk of fire, connect only to a circuit provided
with 20A maximum branch overcurrent protection.

Battery Safety

! CAUTION
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is toxic and is harmful to skin and
eyes.
Dispose of used batteries according to the instructions.

! CAUTION
A battery can present a risk of electrical shock and high short circuit current. The following

precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove
the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during
installation and maintenance (applicable to a UPS and a remote battery supply not having
a grounded supply circuit).

ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 complies with the limits for a
CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Operating this device in a residential area is likely to cause harmful interference that users must
correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the
published technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Emerson.

Information for the Protection of the Environment
UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards,
electronic components). The components removed must be taken to specialized collection and disposal
centers.

2

GLOSSARY OF SYMBOLS
Risk of electrical shock

!

Indicates caution followed by important instructions

AC input

AC output

i
-

Requests the user to consult the manual

+

Indicates the unit contains a valve-regulated lead acid battery

PbH2SO4

R

Recycle

DC voltage

Equipment grounding conductor

Bonded to ground

AC voltage

ON/Alarm Silence/Battery Test

OFF/Bypass

WEEE

3

Product Description

1.0

PRODUCT DESCRIPTION
The Liebert® GXT3™ is a compact, online uninterruptible power system (UPS) that continuously
conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers
and other sensitive equipment with clean sine wave input power.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is
subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause
data loss and damage equipment.
The Liebert GXT3 protects equipment from these disturbances. The Liebert GXT3 continuously
charges its batteries from utility power, enabling it to supply power to connected loads, even when
utility power fails.
This sections describes the UPS, its features, models, appearance and components, operating
principles and operating mode.

1.1

Features
• Intelligent battery management to extend the battery life
• Operation and display panel with LED for monitoring load percentage and battery capacity independently
• Flexible network management with Liebert MultiLink™ software
• Fan fault self-inspection and automated diagnostic function
• Intelligent fan operation, automatically changing rotation speed depending on system requirements, to decrease power consumption and noise
• Input circuit breaker to ease recovery from overloads
• Safety approval from UL and cUL
• Communication options: USB port, Liebert IntelliSlot® port and terminal block communication
• Dry contacts for remote monitoring
• Input power factor greater than 0.99
• Output voltage selection function

1.2

Available Models
Eight UPS models are available.
Table 1

UPS models, power ratings

Model

Nominal Power Rating

GXT3-500RT120

500VA/450W

GXT3-700RT120

700VA/630W

GXT3-1000RT120

1000VA/900W

GXT3-1000MT120

1000VA/900W, minitower

GXT3-1500RT120

1500VA/1350W

GXT3-2000RT120

2000VA/1800W

GXT3-3000RT120

3000VA/2700W

GXT3-3000RT208

3000VA/2700W

4

Product Description

1.3

Appearance and Components

1.3.1

Front Panel and Controls
The Liebert® GXT3™ rack/tower and minitower models in various power ratings have the same
general appearance, controls and features (see Figure 1). The various rack/tower and minitower
models differ largely in the type of receptacles each has.

Figure 1

Liebert GXT3 rack/tower models—front view

Ventilation Slots

Operation and
Display Panel

The Liebert GXT3-1000MT120™ has the same controls and features in a minitower arrangement (see
Figure 2).
Figure 2

Liebert GXT3 minitower—front view
Operation and
Display Panel

Ventilation Slots

1.3.2

Rear Panel Features
The rear panel of the Liebert GXT3 has these features:
•
•
•
•
•
•
•

USB port
Cooling fan
Power output receptacles
Input circuit breaker
Liebert IntelliSlot® port
Communication terminal block
Input power cable

5

Product Description

Figure 3

Liebert® GXT3™ 120V rack/tower models—rear panel components
500VA, 700VA, 1000VA, 1500VA Models

Input Power Plug
and Cable 5-15P

Input Circuit
Breaker

USB Port

Liebert
IntelliSlot
Port

Output
Receptacles,
5-15R

Terminal Block
Communication

Cooling
Fan

External
Battery
Connector

2000VA Model

Input Power Plug
and Cable, 5-20P
Input Circuit
Breaker

USB Port

Liebert
IntelliSlot
Port

Output
Receptacles,
5-15/20R

Terminal Block
Communication

Cooling
Fan

External
Battery
Connector

3000VA Model

USB Port

Input Power Plug
and Cable, L5-30P
Input Circuit
Breaker

Liebert
IntelliSlot
Port

Output
Circuit
Breakers

Terminal Block
Communication

Cooling
Fan

External
Battery
Connector

Output Receptacles,
5-15/20R
Output Receptacle,
L5-30R

6

Product Description

Figure 4

Liebert® GXT3™ 208V rack/tower models—rear panel components
3000VA Model
Input Power Plug
and Cable, L6-20P

USB Port

Output
Circuit
Breakers

Input Circuit
Breaker

Output
Receptacle,
L6-20R

Liebert
IntelliSlot
Port

Terminal Block
Communication

Cooling
Fan

External
Battery
Connector
Output
Receptacles,
L6-15R

Figure 5

Liebert GXT3-1000MT120™—rear panel components
Input Power Plug
and Cable, 5-15P

1000VA Model

Terminal Block
Communication

Input Circuit
Breaker

Liebert IntelliSlot Port

USB Port

Cooling Fan
Output
Receptacles,
5-15R

7

Product Description

1.4

Major Components
The operating principle of the UPS is illustrated in Figure 6.

Figure 6

Operating principle diagram

Input

TVSS & EMI/
RFI Filters

L1

Output

Dynamic
Bypass

Rectifier /
PFC

Inverter

L1

DC-to-DC
Converter

Battery
Charger

Battery

L2/N

L2/N

G

G

The UPS is composed of utility input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery
charger, DC-to-DC converter, battery, dynamic bypass and UPS output.

Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
The Liebert® GXT3™ has surge protection and filters that protect the connected load from power
surges, electromagnetic interference (EMI) and radio frequency interference (RFI). These features
can minimize any surges or interference present in the utility power. The filters also prevent surges
or interference generated by the UPS from adversely affecting devices connected on the same branch
as the UPS.

Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts utility
power to regulated DC power for use by the inverter while ensuring that the wave shape of the input
current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• Efficient power use by the UPS
• Reduced reflected harmonics
This results in cleaner power being available to other devices in the building not being protected by
the Liebert GXT3.

Inverter
In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC to produce
precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from
the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously
generating clean, precise, regulated AC output power.
8

Product Description

Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the Liebert® GXT3™ is plugged
in, even when the UPS is not turned On.

DC-to-DC Converter
The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for
the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage,
thus increasing reliability.

Battery
The Liebert GXT3 uses valve-regulated, nonspillable, lead acid batteries. To maintain battery design
life, operate the Liebert GXT3 in an ambient temperature of 32°F to 77°F (0°C to 25°C).
Optional external battery cabinets are available to extend battery run times.

Dynamic Bypass
The Liebert GXT3 provides an alternate path for utility power to the connected loads in the unlikely
event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature or UPS
failure condition, the UPS automatically transfers the connected loads to bypass.
NOTE
The bypass power path does not protect the connected loads from disturbances on the utility.

1.5

Operating Mode
The UPS operation modes include: Utility (AC) mode, bypass mode, battery mode, battery recharge
mode and frequency converter mode.
For the descriptions of indicators and control buttons in this section, refer to 3.0 - Controls and
Indicators.

1.5.1

Utility (AC) Mode
During Utility (AC) Mode, utility power provides energy to the Liebert GXT3. The filters, PFC circuit
and the inverter process this power to provide computer-grade power to connected loads. Meanwhile,
the UPS maintains the batteries in a fully charged state.

1.5.2

Manual Bypass Mode
Manual Bypass Mode occurs when the Standby/Manual bypass button is pressed and held for about
2 seconds while the Liebert GXT3 is in Utility (AC) Mode. Bypass operation is indicated by an audible
alarm and illuminated amber bypass indicator (If other indicators are illuminated, refer to 7.0 Troubleshooting). During manual bypass mode, utility power bypasses the inverter and provides
energy to the connected load.

NOTICE
Turning Off the UPS in bypass mode will result in loss of output power and dropped loads.

9

Product Description

1.5.3

Battery Mode
The Liebert® GXT3™ enters Battery Mode when utility power fails or is outside acceptable values.
The battery system supplies power through the DC-to-DC converter to the inverter to generate clean
AC power for the connected loads.
When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second
intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to
warn that the battery is getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the AC Input indicator goes Off and the Battery Level indicators illuminate. Each
battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain
illuminated. Refer to 7.0 - Troubleshooting.
For approximate battery run times, refer to 9.0 - Specifications.

NOTICE
Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power.
If the UPS is turned Off manually, it must be manually restarted after utility power returns.
If the UPS is turned Off by a communication signal or because the batteries are depleted, it
will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 Configuration Program).

1.5.4

Battery Recharge Mode
Once utility power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.

1.5.5

Frequency Converter Mode
All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can
be selected using the configuration program. Allowable frequency operating modes include:
•
•
•
•

Auto Sensing - 50Hz or 60Hz – Bypass Enabled
Auto Sensing - 50Hz or 60Hz – Bypass Disabled
Frequency Converter - 50Hz – Bypass Disabled
Frequency Converter - 60Hz – Bypass Disabled

The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60Hz – Bypass Enabled.”

10

Installation

2.0

INSTALLATION

2.1

Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and
your local dealer or your Emerson representative immediately.
• Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Emerson representative immediately.

2.2

What’s Included
With GXT3 UPS
• Compact Disk with:
• Liebert MultiLink®
• Configuration Program
• User Manual
• Terminal Block Communication terminals
• USB Cable: one, 6-1/2 ft. (2m) long
• Mounting hardware, including screws and handles
• Plastic tower stand sets: 2 (four pieces)
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE
The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
spacers for tower configuration and one DC power cable.

2.3

Preparation for Installation

2.3.1

Installation Environment
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.
The installation environment should meet the specifications listed in 9.0 - Specifications).
• Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids,
gases, corrosives, and conductive contaminants. Avoid direct sunlight.
NOTE
Operating the Liebert GXT3™ in temperatures above 77°F (25°C) reduces battery life.

Installation Clearances
Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not
obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
ventilation and heat dissipation, shortening the service life of the Liebert GXT3.

11

Installation

2.4

Mechanical Installation
The Liebert® GXT3™ may be installed as a tower or in a rack, depending on space and use
considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery
cabinets.
NOTE
When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards

2.4.1

Tower Installation
To install the Liebert GXT3 as a tower:
1. Take out support bases from the accessories (see Figure 7).

Figure 7

Support bases
Connectors

Spacers

Support Bases

2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the
spacers shipped with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 7. Each Liebert GXT3 needs two
assembled support bases, one in the front and one in the rear.
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3.
a. Remove the front plastic bezel cover as shown in Figure 8.
Figure 8

Remove the front plastic bezel cover

Front Plastic
Bezel Cover

b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back
into position, as shown in Figure 9.

12

Installation

Figure 9

Rotate the operation and display panel

Operation and Display Panel
Rotated Clockwise 90 Degrees

c.

Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it
back into position. The rotated front plastic bezel cover is shown in Figure 10.
d. Replace the front plastic bezel cover on the Liebert® GXT3™. At this point, the UPS operation
and display panel and logo have been rotated 90 degrees clockwise, which provides upright
viewing for users.
5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs
two support assemblies, as shown in Figure 10.
Figure 10 Tower installation
Liebert
GXT3 UPS

Liebert GXT3
UPS and
External
Battery
Cabinet

Operation and
Display Panel
Rotated for
Tower Operation
Support Bases

13

Installation

2.4.2

Rack Installation
NOTE
• When the Liebert® GXT3™ is installed in a rack, it must be supported by a shelf, fixed
rails or slide rails on each side. The factory-supplied rack mount handles cannot support the weight of the UPS. They are used to move the UPS into and out of the rack and
attach the UPS to the rack.
• Mounting hardware and slide rails are sold separately. Contact your local Emerson
representative for these options and any assistance.
• GXT3-1000MT120 cannot be installed in a rack. The unit is a minitower only.
To install a Liebert GXT3 rack/tower UPS in a rack:
1. Unpack the two slide rails assemblies and mounting hardware from the rack-mounting kit
(P/N: RMKIT18-32).
Slide rail assembly includes inner member and front and rear members. They are interchangeable between left-hand or right-hand. Mounting hardware includes M4 screws and M5 screws.
2. Remove inner member of each slide rail assembly by extending it to its outermost position,
depressing the retaining latch and then pulling inner member from slide rail assembly (see
Figure 11).

Figure 11

Pulling inner member from each slide rail assembly

ut
ll o
u
P

Slide rail assembly
Retaining latch
Inner member

3. Determine the Liebert GXT3’s mounting position inside the racks vertical rails.

! CAUTION
Reduce the risk of tipping the rack by installing the Liebert GXT3 as low as possible in the
rack.

4. Attach the rear member of each slide rail assembly to the rack’s rails with two factory-supplied
M5 screws (see Figure 12).
Figure 12 Installing rear member of each slide rail assembly

Vertical pole
M5 screw (4 pcs)
Rear member
Front member

14

Installation

5. Extend the slide rail assembly by sliding the front member forward until it touches the rack’s
front vertical rails (adjustable length: 18 to 32 inches [457-813mm]). Use two M5 screws to fix
each front member onto the front vertical rails through the installation holes. Make sure that
slide rail assemblies are at the same mounting height on all four rack rails, as shown in
Figure 13.
Figure 13 Installing front member of each slide rail assembly
Front
Vertical
Pole

Slide

Front
Member
M5 Screw
4 pieces

Rear
Member

6. Fasten rear member and front member together using four M4 screws and four M4 nuts (M4 nuts
have been factory-installed on the rear member) per slide rail assembly, as shown in Figure 14.
Figure 14 Fastening rear member and front member together

Rear Member
M4 Screw, 8 pieces
Front member

M4 Nut, 8 pieces

7. Fasten inner members pulled from the slide rail assemblies in Step 2 to the UPS on both sides
with eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of
the UPS, as shown in Figure 15.
Figure 15 Installing inner members

Liebert GXT3 UPS
Inner Member
Retaining Latch

M4 screw, 8 pieces

8. Use M4 screws to install ears of accessories on both sides of the UPS, as shown in Figure 16.

15

Installation

Figure 16 Installing rack-mount handles

Liebert GXT3 UPS

Rack-Mount Handles, 2 pieces
M4 Screw, 8 pieces

9. Insert the UPS, with inner members attached, into slide rail assemblies by inserting top and
bottom edges of inner members into the top and bottom, curved tracks of front members and
sliding the UPS into rack, as shown in Figure 17.
Figure 17 Insert the UPS

Insert

Front Member

Inner Member

NOTE
Ends of inner members are tapered to allow rear of the UPS to be angled upward before
insertion, if space allows.
The UPS should move smoothly into slide rail assemblies. If not, recheck alignment of front
and rear members from Steps 4 through 6.
Factory-supplied rack handles are not intended to be used to lift the UPS. These are intended
to be used to slide the UPS into and out of the rack.
10. Through the rack mount handles, use M5 screws provided in this kit to secure front of the UPS to
rack EIA rails to prevent the UPS from sliding out of position.
11. If optional Liebert® external battery cabinets are connected to the UPS, they can be placed all on
one side of the UPS or stacked beneath the UPS. The installation procedures are the same as
those of the UPS.

16

Installation

2.5

Cable Connection
The Liebert® GXT3™ rear panel has an input cable and plug, output receptacles and output cable(s)
(Output cables are on GXT3-3000 models only). Refer to 1.3.2 - Rear Panel Features for details.
The battery cables are supplied with the battery cabinet.

2.5.1

Connecting Input Plug and Loads
NOTE
Ensure that all the loads are turned Off.
Prepare an input power supply that is properly protected by a circuit breaker in accordance
with national and local electrical codes. The wall receptacle must be grounded.
The plug on the power supply cord is intended to serve as the disconnect device. The
socket-outlet must be installed near the equipment and must be easily accessible.
Emerson recommends installing an upstream circuit breaker of the same series as the Liebert
GXT3’s input circuit breaker.
The specification of input circuit breaker on the rear panel of UPS is given in Table 2.
Table 2

Input circuit breaker specification

Model

Rated Circuit
Breaker

GXT3-500RT120

8A

GXT3-700RT120

10A

GXT3-1000RT120

15A

GXT3-1000MT120

15A

GXT3-1500RT120

15A

GXT3-2000RT120

20A

GXT3-3000RT120

30A

GXT3-3000RT208

20A

1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.
NOTE
1. Distribute loads evenly across all receptacles to prevent overloading individual receptacles.
2. Output cable length should not exceed 32.8 ft (10m).
3. Insert the input plug of Liebert GXT3 into the input power connection.

2.5.2

Connecting Battery Cables
1. Switch Off the input breaker of the battery cabinet.
2. Take out the battery cable included with the battery cabinet.
3. Connect one end of the battery cable to the external battery connector on the rear panel of the
UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.
4. Switch On the battery breaker on the rear of the external battery cabinet.
5. Use the Configuration Program included with the UPS to specify the number of external battery
cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.

17

Installation

2.6

Connecting Communication Cables
Communication cable connection includes: USB and cables for option cards.

2.6.1

Connecting USB Communication Cables
1. Take the USB communication cables out of the accessories box.
2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert®
GXT3™ (see Figures 3 and 5).
3. Insert the other end of the USB communication cable to the USB port of the computer.

2.6.2

Installing the Optional Liebert IntelliSlot® Card and Communication Cables
1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside.
2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws.
3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided
with the card.
To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual.
Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site:
www.liebert.com

18

Controls and Indicators

3.0

CONTROLS AND INDICATORS
The operation and display panel, shown in Figure 18, is on the front panel of the Liebert® GXT3™
(see Figures 1 and 2).

Figure 18 Operation and display panel
Battery Level Indicators

Load Level Indicators
Fault Indicator

Bypass Indicator

AC Input Indicator

Inverter Indicator

Liebert® GXT3
AC Power System
3000VA

On/Alarm Silence/Manual
Battery Test Button
Standby/Manual Bypass Button

3.1

Battery Indicator

Control Buttons
The operation and display panel has two control buttons: On/Alarm Silence/Manual Battery Test and
Standby/Manual bypass.

3.1.1

On/Alarm Silence/Manual Battery Test Button
The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and
has three functions (see Table 3).
Table 3

Functions of On/Alarm Silence/Manual battery test button

Function

Operation

ON
Alarm Silence

1

Manual Battery Test

Description

Press the button once for 3 seconds

To start the UPS

Press the button for at least half a second

To silence alarms 2

Press the button for at least half a second while
operating in Utility (AC) Mode with no alarms present.

To initiate a manual battery test

1. The low battery and bypass reminder alarms cannot be silenced.
2. After the alarm is silenced, UPS will reactivate the alarm system to alert of additional problems

3.1.2

Standby/Manual Bypass Button
The Standby/Manual Bypass button controls output power to connected load(s) and has two functions
(see Table 4).
Table 4

Functions of Standby/Manual Bypass button

Function

Operation

Description

Manual Bypass

Press the button once and hold it for about
2 seconds 1

To initiate a manual transfer of the connected
loads to the internal bypass, if available

Standby

Press the button twice within four seconds while
the UPS is in Manual Bypass or Battery Mode 2

To shut down the UPS and shut Off all power
to the connected loads

1. If the bypass is not available due to voltage or frequency, pressing this button once will be ignored.
2. Perform all necessary shutdown procedures on connected loads before turning Off the Liebert GXT3.

19

Controls and Indicators

3.2

Indicators
The operation and display panel has seven indicators (see Figure 18). The indicators can be divided
into two groups according to the applications: level indicators and UPS status indicators.

3.2.1

Level Indicators
Battery Level Indicators
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate
the battery capacity level. The Liebert® GXT3™ battery capacity level is shown in 20% increments
(±5%). The battery level indicators will illuminate as shown in Figure 19.

Figure 19 Battery level indicators

Charging

Discharging

0 - 20%
Flash OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

OFF

OFF

OFF

Flash OFF

OFF

ON

ON

ON

OFF

OFF

21 - 40%
ON

Flash

ON

ON

41 - 60%
61 - 80%
ON

ON

ON

Flash OFF

ON

ON

ON

ON

OFF

81 - 100%
ON

ON

ON

ON

Flash

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

Fully
Charged

Load Level Indicators
The load level indicator is composed of five LED bars that illuminate to indicate the relative load on
the UPS output in 25% increments (± 5%). The load level indicator will illuminate as shown in
Figure 20.
Figure 20 Load level indicators

0 - 25%
ON

OFF

OFF

OFF

OFF

ON

ON

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

ON

ON

ON

ON

OFF

ON

ON

ON

ON

ON

26 - 50%
51 - 75%
76 - 100%
Overload

20

Controls and Indicators

3.2.2

UPS Status Indicators
UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator,
inverter indicator and bypass indicator. Table 5 shows the symbols and their meaning.
Table 5

UPS status indicators

UPS Status
Indicator
Fault Indicator

Icon

Color
Red

Description
On if the UPS has detected a fault; Off if there is no fault

AC Input Indicator

Green

On when the utility input power is normal; Off during utility failure; flashing
when utility power is outside specifications

Battery Indicator

Amber

On when the battery is supplying power; Off when the battery is not
supplying power

Inverter Indicator

Green

On when the inverter is supplying power; Off when the inverter is not
supplying power

Bypass Indicator

Amber

On when the bypass is supplying power; Off when the inverter is not
supplying power; and flashing when utility power is outside specifications

21

Operation

4.0

OPERATION
This section describes checks to be made before starting the UPS, how to start the UPS, manual
battery test, manual bypass, shutting down the UPS and disconnecting the utility power from the
UPS.
NOTE
The Liebert® GXT3™’s battery has been fully charged before delivery, but some charge will be
lost during storage and shipping. To ensure that the battery has adequate reserve power to
protect the connected load, charge the battery for three hours before putting the UPS into
service.

4.1

Startup Checklist for the Liebert GXT3
Before starting the UPS, perform these checks:
___ 1. Check that the input plugs and loads are connected properly and reliably.
___ 2. Check that all of the battery cables are connected properly.
___ 3. Check that the communication cables are connected properly.

4.2

Starting the UPS
1. Turn On the input circuit breaker—see Figures 3 and 5 for its location.
2. Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three
seconds.
After the button is pressed, the LEDs on the display will signal that the unit has initiated the
startup process.
3. Once the inverter LED has been illuminated, turn On the connected loads.
4. Check the status indicators to determine whether the Liebert GXT3 is operating normally.
5. Check the load level indicators to verify that the connected load does not exceed the UPS’ rated
capacity.
The UPS is now providing conditioned power to the load.

4.3

Manual Battery Test
To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least
half a second while operating from utility power with no alarm conditions present.
• If only first two of the five LED segments illuminate, allow the UPS to recharge the batteries for
24 hours.
• Retest the batteries after 24 hours of charging the batteries.
• After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact
your local Emerson representative or Emerson Channel Support.
• If none of the five Battery LEDs illuminate during a manual battery test, check the battery connection and allow the UPS to recharge the batteries for 1 hour and initiate a manual battery test
again.
• If none of the five Battery LEDs illuminate during the manual battery test a second time, replace
the batteries, and contact your local Emerson representative or Emerson Channel Support.

4.4

Manual Bypass
Press the Standby/Manual Bypass button once while the UPS is in utility (AC) mode and hold it for
about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal
bypass is not available due to utility power problems, pressing this button once will be ignored.
Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. If other
indicators are illuminated, refer to 7.0 - Troubleshooting.

22

Operation

4.5

Shut Down the Liebert® GXT3™
1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding
it for about 2 seconds.
If manual bypass is not available, disregard the first step.
2. Press the Standby/Manual Bypass button twice within four seconds to shut down the UPS. The
UPS will shut down about 30 seconds after the button is pressed.
Power to the connected loads is now Off.

4.6

Disconnecting Input Power from the Liebert GXT3

1. Once the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert® GXT3™,
disconnect the input cable plug.
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this
indicates that the power-off is complete.
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external
battery cabinet.
After powering Off the UPS, the UPS ceases output and the load is powered Off.

23

Communication

5.0

COMMUNICATION
This section describes UPS communication over the three types of communication connections on the
rear of the Liebert® GXT3™:
• Liebert IntelliSlot® port
• USB port (standard B-type)
• Terminal Block Communication

! CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables.

5.1

Liebert IntelliSlot Communication Cards
The Liebert IntelliSlot port accepts three optional cards:
• Liebert IntelliSlot SNMP Card
• Liebert IntelliSlot Relay Card
• Liebert IntelliSlot 485 Card.
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the
network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications
and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the
UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at
multilink.liebert.com

5.1.1

Liebert MultiLink
Liebert MultiLink monitors the UPS continuously and can shut down your computer or server in the
event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.
Liebert’s MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot
SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS. An optional Liebert MultiLink
License Kit permits shutting down the UPS over a network.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and
Liebert MultiLink license kits, visit the Liebert Web site (www.liebert.com) or contact your local
Emerson representative.

24

Communication

5.2

USB Port Communication
The standard B-type USB port is used to connect the UPS and network server or other computer
system using Liebert® MultiLink®. Configuration program can be accessed through the
communication port.

5.2.1

Configuration Program
Accessing the Configuration Program via USB is a new feature of the Liebert GXT3™. For most users,
the factory default settings will be adequate. This section illustrates the features available for
modification, as well as the factory default setting.
The USB configuration program allows these features of the Liebert GXT3 to be changed:
• Enable/Disable Auto-Restart
• Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled
• Set the Low Battery Warning alarm time from 2 to 30 minutes
• Enable/Disable the Auto-Battery test
• Enable/Disable Auto-Restart after removing Remote Shutdown
• Set the wiring mode of Remote Shutdown
• Set the Auto-Enable output
• Set the Auto-Battery test to 7, 14, 21 or 28 days
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculated by Liebert software products
• Select one of multiple output voltages to match various voltages, see Table 6.
Table 6

Output voltage option
Factory
Default, VAC

Output Voltage Option, VAC

GXT3-500RT120 - GXT3-3000RT120
GXT3-1000MT120

120

110, 115, 120 and 127

GXT3-3000RT208

208

208 / 220 / 230 / 240

UPS Model

NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
NOTE
For all 120V models, when the output voltage is programmed for 110VAC, the UPS will be
automatically derated as follows (refer to 9.0 - Specifications for VA and watt ratings):
• 500VA - 1000VA: derated to 95% of both the VA and Watt ratings
• 1500VA - 3000VA: derated to 90% of both the VA and Watt ratings
NOTE
• This program is compatible with UPS models beginning with ‘GXT3’, as in ‘GXT33000RT120.’ It is not compatible with earlier versions of the Liebert GXT UPS.
• A computer running Windows 2000®, XP® or Vista® is required to set up and run the
configuration program.

25

Communication

5.3

Terminal Block Communication
The Terminal Block includes eight pins, as shown in Figure 21.

Figure 21 Terminal block communication pin layout

5.3.1

1
2

Any Mode
Shut Down

3
4

Battery Mode
Shut Down

5
6

Battery Mode

7
8

Low Battery

Any-Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,
inverter and bypass so that there is no power to the loads.
Any Mode Shutdown can be operated locally and remotely, as described as follows:
• Local Any Mode Shutdown can be performed by shorting Pin1 and Pin2,
• Remote Any Mode Shutdown can be performed by a switch connected to Pin1 and Pin2 and
mounted at a remote location.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring
regulations.

! WARNING
When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1
and Pin 2, the Liebert® GXT3™’s output can turn On automatically and without warning if
the Pin 1 and Pin 2 connection is changed.

26

Communication

5.3.2

Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and
bypass so that there is no power to the load when the UPS is On Battery.
Battery Mode Shutdown can be performed locally or remotely:
• Local Any Mode Shutdown can be performed by shorting Pin 3 and Pin 4
• Remote Any Mode Shutdown can be achieved by a switch connected to Pin 3 and Pin 4 and
mounted at a remote location.
NOTE
Remote Power Off will be performed by NO contact.
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert® GXT3™ for remote connection will be via terminal block
connector.
Battery mode shutdown wiring must conform to all national, regional and local wiring
regulations.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2 minute shut
down timer. This timer cannot be stopped once triggered. If utility power returns during this
countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds.
Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

5.3.3

On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery this dry contact will be closed.

5.3.4

Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery and has reached the Low Battery Warning time selected in the configuration
program, this dry contact will be closed.
NOTE
The rated values for the dry contacts for the On Battery and Low Battery signals are:
• Rated Voltage: 30V (AC or DC)
• Rated Current: 300mA

27

Maintenance

6.0

MAINTENANCE
This section describes replacing the internal battery pack, precautions, checking the Liebert® GXT3’s
status and checking UPS functions.

! WARNING
The battery can present a risk of electrical shock and high short circuit current. The following

precautions should be observed before replacing the battery pack:
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
• Do not lay tools or other metal objects on the batteries.
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.

6.1

Replacing the Internal Battery Pack
The Liebert® GXT3™ is designed to allow the user to replace the internal battery pack safely. Refer to
Table 7 for internal battery pack part numbers for Liebert GXT3™ UPS:
Table 7

Replacement internal battery pack model number

UPS Model Number

Replacement Internal Battery
Pack Model Number

Quantity
Required

Liebert GXT3-500RT120

GXT3-5A48BATKIT

1

Liebert GXT3-700RT120

GXT3-5A48BATKIT

1

Liebert GXT3-1000RT120

GXT3-5A48BATKIT

1

Liebert GXT3-1000MT120

GXT3-1MTBATKIT

1

Liebert GXT3-1500RT120

GXT3-7A48BATKIT

1

Liebert GXT3-2000RT120

GXT3-9A48BATKIT

1

Liebert GXT3-3000RT120

GXT3-9A72BATKIT

1

Liebert GXT3-3000RT208

GXT3-9A72BATKIT

1

Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to
obtain the part number and pricing of the appropriate replacement battery pack.

! CAUTION
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.

6.1.1

Battery Replacement Procedures
1. Remove the front plastic bezel cover from the UPS.
2. Loosen and remove the six screws on the battery door, as shown in Figure 22.
3. Lay the battery door and screws aside for reassembly.

28

Maintenance

Figure 22 Removing the front bezel cover and battery door
Battery Door
Screws, 6
Front Bezel

4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown
in Figure 23.
Figure 23 Disconnecting the battery plug and battery receptacle (front view)

Battery Connector

Battery Receptacle

5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in
Figure 24.
Figure 24 Pull out the battery
Internal Battery Pack

Battery
Handle
Pull Out with Battery Handle

6. Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery pack to make sure they are the same type and model. If
so, proceed with Step 7; if they are different, stop and contact your local Emerson representative,
or Emerson Channel Support.
7. Line up and slide in the new internal battery pack.
8. Reconnect the battery plug and battery receptacle
9. Push the battery wire and internal battery pack back into the UPS.
10. Reattach the front battery door with the six screws.
11. Reattach the front plastic bezel cover to the UPS.
NOTE
The internal battery pack is hot-swappable. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages. Do not
replace the battery while the UPS is operating in Battery Mode. This will result in a loss of
output power and will drop the connected load.
29

Maintenance

6.2

Battery Charging
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their
design life. The Liebert® GXT3™ charges the batteries continuously when it is connected to the utility
input power.
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input
power for at least 24 hours every four to six months to ensure full recharge of the batteries.

6.3

Precautions
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper
use can result in electrical shock or fire. To ensure safety, observe the following precautions:
•
•
•
•

6.4

Turn Off and unplug the Liebert GXT3 before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the Liebert GXT3.
Do not place the Liebert GXT3 power cord where it might be damaged.

Checking UPS Status
Emerson recommends checking the UPS operation status every six months.
• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode; if it
is operating in Bypass Mode, stop and contact your local Emerson representative or Emerson
Channel Support.
• Check if the battery is discharging: When the utility input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel Support.

6.5

Checking UPS Functions
NOTE
UPS function check procedures may interrupt power supply to the connected load.
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
are On and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode;
the UPS should initiate battery self-test. Check to determine whether the battery is operating
normally. If not, stop and contact your local Emerson representative or Emerson Channel
Support.

30

Troubleshooting

7.0

TROUBLESHOOTING
This section indicates various UPS symptoms a user may encounter and troubleshooting steps in the
event the UPS develops a problem. Use the following information to determine whether external
factors caused the problem and how to remedy the situation.

7.1

UPS Symptoms
The following symptoms indicate the Liebert® GXT3™ has malfunctions.
• The related indicators will illuminate, indicating the UPS detected a problem.
• An alarm will sound, indicating that the UPS requires attention.

7.1.1

Indicators
In addition to the fault indicator being illuminated, one or more of LED segments of battery level
indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 25. The
descriptions are listed in Table 8.

Figure 25 Battery level indicator

A
Table 8

B

C

D

E

Indicator descriptions

Indicator
A-E
A

Diagnosis/Audible alarm
On bypass from output overload (half-second beep every half-second)
On bypass due to overtemperature condition (1-second beep every 4 seconds)

B

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

C

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

D

On bypass due to PFC failure (1-second beep every 4 seconds)

E

On bypass due to inverter failure (1-second beep every 4 seconds)

A&B

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery
charger failure) and continuous alarm

A&C

UPS failed battery test (2-second beep every60 seconds)

A&E

Bypass feedback (1-second beep every 4 seconds)

B&E

Short circuit on the output

C&E

UPS shutdown by command from communication (USB port or Liebert IntelliSlot™ port) (no
audible)

Utility LED flash

L-N reverse

Battery Indicator
Flashing

Battery not connected (continuous horn); check battery connection, power down and restart
UPS

Bypass Indicator
Flashing

Utility power voltage or frequency is out of tolerance; bypass is unavailable

Indicators A - E are shown in Figure 25.
If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload
ends.

31

Troubleshooting

7.1.2

Audible Alarm
An audible alarm will be used in conjunction with the visual indicators to indicate to the user a
change in UPS operating status. The audible alarm will enunciate as given in Table 9.
Table 9

Audible alarm description
Condition

7.2

Alarm

Battery discharge

half-second beep every 10 seconds

Low battery

Two half-second beeps every 5 seconds

UPS fault, load on bypass

1-second beep every 4 seconds

UPS fault, no power to load

Continuous

Overload

half-second beep every half second

Battery replacement

2-second beep every 60 seconds

Battery loss

Continuous

Wiring problem (including line-to-neutral reversal
or a loss of proper grounding for UPS)

Continuous

Bypass reminder

1-second beep every 2 minutes

Troubleshooting
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the
issue persists, contact Emerson Channel Support.

Table 10

Troubleshooting
Problem

Cause

Solution

UPS is short-circuited or overloaded

Ensure UPS is Off. Disconnect all loads and
ensure nothing is lodged in output receptacles.
Ensure loads are not defective or shorted
internally.

UPS not plugged in

UPS is operating from battery mode, ensure
UPS is securely plugged into the wall
receptacle.

UPS input protection circuit breaker
has opened

UPS is operating from battery mode. Save data
and close applications. Reset UPS input
breaker, then restart UPS.

Utility power is out of tolerance

UPS is operating from battery mode. Save data
and close applications. Ensure utility supply
voltage is within acceptable limits for UPS.

Batteries are not fully charged

Keep UPS plugged in continuously at least 24
hours to recharge batteries.

UPS is overloaded

Check load level indicator and reduce the load
on the UPS.

Batteries may not be able to hold a
full charge due to age

Replace batteries. Contact your local dealer,
Emerson representative or Emerson Channel
Support for replacement battery kit.

Fault and Bypass indicators and
all LED segments of battery
level indicator are illuminated

UPS overloaded or load is faulty

Check load level indicator and remove nonessential loads. Recalculate the load and reduce
number of loads connected to UPS. Check load
for faults.

Fault and Bypass indicators and
diagnostic A indicator are
illuminated

UPS shutdown due to
overtemperature condition. Load is
on bypass power

Ensure UPS is not overloaded, ventilation holes
not blocked, or room ambient temperature is not
excessive. Wait 30 minutes to allow UPS to cool,
then restart UPS. If UPS will not restart, contact
your local dealer, Emerson representative or
Emerson Channel Support.

UPS fails to start when the
On/Alarm Silence/Manual
Battery Test button is pressed

Battery indicator is illuminated

UPS has reduced battery
backup time

32

Troubleshooting

Table 10

Troubleshooting (continued)
Problem

Cause

Solution

Fault and Bypass indicators and
diagnostic B indicator are
illuminated

UPS internal DC bus overvoltage

UPS requires service. Contact Emerson
Channel Support.

Fault and Bypass indicators and
diagnostic C indicator are
illuminated

UPS DC/DC fault

UPS requires service. Contact Emerson
Channel Support

Fault indicator and diagnostic D
indicator are illuminated

UPS PFC (Power Factor Correction
Circuit) fault

UPS requires service. Contact Emerson
Channel Support

Fault and Bypass indicators and
diagnostic E indicator are
illuminated

UPS inverter fault

UPS requires service. Contact Emerson
Channel Support

Fault indicator and diagnostic A
and C indicators are illuminated

UPS failed the battery test

Replace batteries. Contact your local dealer,
Emerson representative or Emerson Channel
Support

Fault and Bypass indicators and
diagnostic C and E indicators
are illuminated

UPS shut down by a command from
the communications port(s)

Your UPS has received a signal or command
from the attached computer. If this was
inadvertent, ensure the communication cable
used is correct for your system. For assistance,
contact your local dealer, Emerson
representative or Emerson Channel Support

Fault indicator and diagnostic A
and B indicators are illuminated

UPS Failure (Includes Dual Fan
failure, single fan failure under certain
condition and Battery Charger
Failure) and continuous alarm

Ensure fan is not blocked. If the fault is not
removed, contact your local dealer, Emerson
representative or Emerson Channel Support

AC input indicator is flashing

UPS detected a line-to-neutral
reversal or a loss of proper grounding
for UPS; continuous alarm and UPS
will not start in standby status. This is
active only when power is first
applied to the input. Once the UPS is
running, the AC input indictor will
flash, unless the input wiring is
correctly changed

Contact a qualified electrician to verify site wiring

Battery indicator is flashing

Battery source is not available;
continuous alarm

Check battery connections, completely power
down and restart UPS.
NOTE: If the battery circuit opens while the UPS
is running, it will be detected when the next
battery test is performed

Because the voltage or frequency is
outside acceptable limits, the bypass
is disabled

The AC input powers the PFC input and serves
as the bypass source. If the AC is present but
the voltage or frequency exceeds the acceptable
range for safe operation with a load, the bypass
will be disabled and this indicator will flash,
indicating that the bypass is unavailable

Bypass indicator is flashing

When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the
top panel of the Liebert® GXT3™.

33

Battery Cabinet

8.0

BATTERY CABINET
Optional battery cabinets are available for the Liebert® GXT3™. The battery connectors and input
breaker are on the battery cabinet’s rear panel, as shown in Figure 26. For battery cabinet
specifications, refer to Table 13. The Liebert GXT3 may be equipped with a maximum of four
extension battery packs.
For battery run times, refer to Table 15.

Figure 26 Battery cabinet

Input Breaker
Battery Connectors

! WARNING
Do not contact the battery connectors and ground without wearing protective gloves and

clothing and taking other precautions against electrical shock. The battery loop and AC input
are not insulated, which may cause a dangerous voltage between the battery connectors and
ground.

NOTE
External Battery Connectors are wired in parallel. Either connector can be connected to the
UPS or to another battery cabinet.

34

Specifications

9.0

SPECIFICATIONS

Table 11

Specifications of GXT3-500RT120 - GXT3-1000RT120 and GXT3-1000MT120 UPS
Product Model
GXT3-500RT120
(500VA/450W)

Parameters

GXT3-700RT120
(700VA/630W)

GXT3-1000RT120
(1000VA/900W)

GXT3-1000MT120
(1000VA/900W)

Dimensions, D × W × H, in. (mm)
Unit

19.7 x 16.9 x 3.4
(497 × 430 × 85)

15.4 x 6.9 x 8.9
(390 × 175 × 225)

Shipping

25.5 x 23.9 x 10.6
(647 x 607 x 270)

22.1 x 12.9 x 14
(562 × 327 × 355)

Unit

37 (16.8)

37.5 (17)

Shipping

44.1 (20)

36 (16.5)

Weight, lb (kg)

Input AC
Voltage Range (typical)

120VAC nominal; variable based on output load

90% ~ 100% loading

90VAC/140VAC

70% ~ 90% loading

86VAC/140VAC

30% ~ 70% loading

77VAC/140VAC

0 ~ 30% loading

60VAC/140VAC

Frequency

40Hz ~ 70Hz; Auto Sensing

Input Power Cord

10 ft. attached w/ NEMA 5-15P plug

Output AC
Output Receptacles
Voltage

5-15R × 6
110/115/120VAC (user-configurable); ±3%

Waveform
Utility (AC) Mode Overload

Sine wave
200% for 2 seconds; 150% for 50 seconds with transfer to bypass

Battery
Type

Valve-regulated, nonspillable, lead acid

Qty × V× Rating
Battery Mfr./Part #

4 × 12V × 5.0Ah
YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245

Backup Time
Recharge Time

See Table 15
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)

Environmental Requirements
Operating Temperature, °F (°C)

32 to 104 (0 to 40); see Table 14 - Operating temperature parameters

Storage Temperature, °F (°C)

5ºF to 122ºF (-15ºC to 50ºC)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating

Storage Elevation
Audible Noise

50,000 ft. (15000m) maximum
<43dBA max @ 3ft. (1m) front and sides
<46dBA max @ 3ft. (1m) rear

< 50 dBA, at 3ft. (1m) rear
< 45 dBA, at 3ft. (1m) front and sides

Agency
Safety
RFI/EMI

UL 1778, cUL Listed
FCC Part 15, Class A=CISPR22 Class B

Surge Immunity

IEC 62040-2 2nd Ed

Transportation

ISTA Procedure 1A

35

Specifications

Table 12

Specifications of GXT3-1500RT120 - GXT3-3000RT120 and GXT3-3000RT208 UPS
Product Model
GXT3-1500RT120
(1500VA/1350W)

Parameters

GXT3-2000RT120 GXT3-3000RT120
(2000VA/1800W) (3000VA/2700W)

GXT3-3000RT208
(3000VA/2700W)

Dimensions, D × W × H, in. (mm)
Unit

19.7 x 16.9 x 3.4
(497 × 430 × 85)

23.7 x 16.9 x 3.4
(602 × 430 × 85)

Shipping

25.5 x 23.9 x 10.6
(647 x 607 x 270)

29.4 x 23.4 x 10.6
(747 x 607 x 270)

Weight, lb. (kg)
Unit
Shipping

51.1 (23.2)

56.1 (25.5)

71.4 (32.4)

57.3 (26)

61.7 (28)

77 (35)

Input AC
120VAC nominal; variable based on output load

208VAC nominal;
variable
based on output load

90 - 100% loading

102VAC/140VAC

177VAC/280VAC

70 - 90% loading

96VAC/140VAC

168VAC/280VAC

30 - 70% loading

84VAC/140VAC

150VAC/280VAC

0 - 30% loading

60VAC/140VAC

115VAC/280VAC

Voltage Range (typical)

Frequency
Input Power Cord

40 - 70Hz; Auto Sensing
10 ft. attached w/
NEMA 5-15P plug

10 ft. attached w/
10 ft. attached w/
NEMA 5-20P plug NEMA L5-30P plug

10 ft. attached w/
NEMA L6-20P plug

Output AC
Output Receptacles
Voltage

5-15R × 6

5-20R × 6

L6-20R×1+L6-15R×2
208/220/230/240 VAC
(user-configurable); ±3%

110/115/120VAC (user-configurable); ±3%

Waveform
Utility (AC) Mode Overload

L5-30R×1+5-20R×6

Sine wave
200% for 2 seconds
150% for 50 seconds

200% for 2 seconds
150% for 10 seconds

Battery
Type
Qty×V×Rating
Battery Mfr./Part #

Valve-regulated, nonspillable, lead acid
4 × 12V × 7.2Ah

4 × 12V × 9.0Ah

Panasonic/UP-RW1236
CSB/GP 1272

6 × 12V × 9.0Ah

Panasonic/UP- RW1245; CSB/HR 1234W F2

Backup Time
Recharge Time

6 × 12V × 9.0Ah

See Table 15
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)

Environmental
Operating Temperature, °F (°C)

+32 to +104 (0 to 40); see Table 14 - Operating temperature parameters

Storage Temperature, °F (°C)

5 to +122 (-15 to 50)

Relative Humidity
Operating Elevation

0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating

Storage Elevation

50,000 ft. (15000m) maximum

< 45dBA at 3ft (1m) rear
Audible Noise < 46 dBA at 3ft. (1m)
front and side

<48dBA max @ 3ft (1m) front and side
<48dBA max @ 3ft. (1m) rear

Agency
Safety
RFI/EMI

UL 1778, c-UL Listed
FCC Part 15, Class A=CISPR22 Class B

Surge Immunity

IEC 62040-2 2nd Ed

Transportation

ISTA Procedure 1A
36

Specifications

Table 13

Battery cabinet specifications
Model Number
Parameter

GXT3-48VBATT

GXT3-72VBATT

Used w/UPS Model

GXT3-500RT120,GXT3-700RT120
GXT3-1000RT120,GXT3-1500RT120,
GXT3-2000RT120

GXT3-3000RT120
GXT3-3000RT208

Unit

19.7 x 16.9 x 3.3
(497 × 430 × 85)

23.7 x 16.9 x 3.3
(602 × 430 × 85)

Shipping

24.3 x 22.4 x 10.3
(617 x 570 x 262)

28.2 x 22.4 x 10.3
(717 x 570 x 262)

Unit

57.3 (26)

83.8 (38)

Shipping

61.7 (28)

92.6 (42)

Dimensions, D × W × H, in (mm)

Weight, lb (kg)

Battery parameters
Type
Qty × V× Rating
Battery Mfr./Part #

Valve-regulated, nonspillable, lead acid
2 × 4 × 12V × 9.0Ah

2 × 6 × 12V × 9.0Ah

Panasonic/UP-RW1245; CSB/HR 1234W F2

Backup Time

See Table 15

Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)

32 to 104 (0 to 40)
19 to 122 (-15 to 50)
High ambient temperatures will reduce battery life.

Relative Humidity
Operating Elevation

0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104ºF (40ºC) without derating

Storage Elevation

50,000 ft. (15000m) maximum

Agency
Safety
RFI/EMI

Table 14

UL 1778, c-UL Listed
FCC Part 15, Class A=CISPR22 Class B

Surge Immunity

IEC 62040-2 2nd Ed

Transportation

ISTA Procedure 1A

Operating temperature parameters

Ambient Temperature, °C (°F)
Maximum Output
Power Factor Derating
@ Maximum Load

25-30 (77-86)

30-35 (86-95)

35 - 40 (95-104)

100%-93%

93%-86%

86%-79%

37

Specifications

Table 15

Battery run times

Number of
Batteries/Cabinets

Internal Battery

Internal Battery
+ 1 External
Battery Cabinet

Internal Battery
+ 2 External
Battery Cabinets

Internal Battery
+ 3 External
Battery Cabinets

208 VAC RT
Model

120VAC RT Models

Load Percent
of Capacity

500VA

700VA

1000VA

1500VA

2000VA

3000VA

3000VA

10%

128

105

90

77

77

74

77

20%

82

61

37

35

33

36

37

30%

41

37

30

23

21

21

21

40%

38

32

23

16

15

15

15

50%

34

27

17

11

11

11

11

60%

31

22

14

10

8

8

8

70%

27

18

11

6

6

6

6

80%

23

15

9

5

5

5

5

90%

20

13

8

4

4

4

4

100%

17

11

7

4

3

3

3

10%

328

306

212

199

183

166

183

20%

209

182

151

133

124

121

123

30%

166

149

123

97

80

79

79

40%

152

130

100

72

41

53

53

50%

139

109

80

41

38

46

45

60%

125

98

68

38

34

39

38

70%

109

81

41

35

30

31

31

80%

100

72

39

32

25

26

26

90%

92

63

37

27

21

21

22

100%

79

41

35

23

17

18

18

10%

480

373

336

314

311

307

311

20%

334

313

214

188

161

159

160

30%

309

211

166

148

134

133

133

40%

216

185

151

126

105

105

104

50%

197

159

137

103

80

81

80

60%

167

149

122

82

67

68

67

70%

159

139

105

72

40

52

52

80%

152

128

95

62

38

47

47

90%

144

112

80

40

36

43

43

100%

137

104

73

38

33

38

38

10%

480

480

480

341

335

332

335

20%

401

341

321

227

206

203

205

30%

338

318

218

185

157

157

157

40%

322

224

191

154

139

139

138

50%

306

205

162

139

120

120

113

60%

219

186

152

123

99

100

100

70%

205

163

141

105

80

81

81

80%

191

155

131

93

70

71

71

90%

167

148

120

79

60

62

62

100%

162

140

106

71

40

51

51

38

Specifications

Table 15

Battery run times (continued)

Number of
Batteries/Cabinets

Internal Battery
+ 4 External
Battery Cabinets

208 VAC RT
Model

120VAC RT Models

Load Percent
of Capacity

500VA

700VA

1000VA

1500VA

2000VA

3000VA

3000VA

10%

480

480

480

480

480

346

480

20%

480

480

339

317

304

301

303

30%

398

337

315

216

188

187

187

40%

340

321

220

183

156

156

155

50%

328

304

199

157

141

142

141

60%

316

217

167

145

126

127

126

70%

304

202

159

133

107

108

108

80%

221

186

151

120

95

97

97

90%

210

164

143

105

79

81

81

100%

199

158

134

96

71

73

73

Times in this table are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature
of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery
cabinets.

9.1

Product Warranty Registration
To register for warranty protection, visit the Quick Links section of the Liebert® Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, contact Emerson Channel Support at:
North America: 800-222-5877
Outside North America: 00-800-1155-4499
liebert.upstech@emerson.com

39

Specifications

40

Ensuring The High Availability
Of Mission-Critical Data And Applications.

Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
Compromise™ by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.

Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246

Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572

While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2010 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.

SL-23180_REV3_04-12

Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
AC Power
Connectivity

Embedded Computing
Embedded Power

DC Power

Infrastructure Management & Monitoring

Outside Plant
Power Switching & Controls
Precision Cooling

EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection

Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Create Date                     : 2012:04:13 16:00:49Z
Creator                         : FrameMaker 9.0
Modify Date                     : 2012:04:13 16:40:33-04:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Creator Tool                    : FrameMaker 9.0
Metadata Date                   : 2012:04:13 16:40:33-04:00
Producer                        : Acrobat Distiller 9.5.1 (Windows)
Document ID                     : uuid:6e41b1e1-0b85-4b14-840e-a77567b20096
Instance ID                     : uuid:a7ee6da5-0d21-4c41-9a1e-be504c23a39c
Format                          : application/pdf
Page Mode                       : UseOutlines
Page Count                      : 48
EXIF Metadata provided by EXIF.tools

Navigation menu