Fluke 975 Application Note

2015-09-09

: Fluke Fluke-975-Application-Note-808552 fluke-975-application-note-808552 fluke pdf

Open the PDF directly: View PDF PDF.
Page Count: 3

DownloadFluke Fluke-975-Application-Note-  Fluke-975-application-note
Open PDF In BrowserView PDF
Monitoring temperature,
humidity, and airflow
in data centers
A market in need of measurement

Application Note

Using a Fluke Ti20 Thermal Imager and a
Fluke 975V AirMeter ™ test tool, customers
protect their servers by monitoring environments in rented data centers.
The international law firm
depicted in this story owns no
data centers, despite the large
amount of data it stores and
retrieves. Like many other hightech companies, it rents space for
its servers in data centers owned
by others. “The sites we use are
just hosts,” says the law firm’s
data center support analyst. “The
racks we have there are ours, but
we rent the environment, power
and the bandwidth.”
Each of the firm’s offices has
one or two racks of servers in a
local data center to service that
site’s needs. In addition, the
company has a centralized U.S.
server location, a secondary center for backup and redundancy,
and plans for new locations
overseas.

Fluke instruments used
At present, the analyst uses two
Fluke instruments to monitor the
firm’s data centers and the status
of its servers in those centers:
The Fluke 975 AirMeter can
record ten fundamental parameters associated with indoor air
quality. Of special importance to
data centers are air temperature,
relative humidity, and airflow (air
velocity). Since servers generate
considerable heat, they must be
cooled to manufacturer-specified
temperatures and subjected to no
more than 45 to 50 percent relative humidity.

From the Fluke Digital Library @ www.fluke.com/library

are told by the data centers,” the
analyst says. “Then, if necessary,
we can suggest corrective measures to keep our servers functioning efficiently.”
The support analyst cites the
local data center as an example:
“The way the room is set up
right now greatly restricts the air
flow going to some of the devices
positioned across the room from
the air-conditioning unit. Using
the Ti20, we were able to take
temperature readings of surfaces
in each area of the room. Then,
using those readings, we were
able to plot out where the cool
air travels. We found that while
one area of the room is cold,
as we worked our way around
the room, areas were gradually
warmer and warmer.”
He says that the Fluke 975
AirMeter used in conjunction
with the Ti20 allowed for a
Using the Ti20 to scan
more in-depth analysis of the
heat output from the
local data center: “Temperature
backside of blade servers.
and humidity readings indicated
that the hot air that should be
exhausted from the room is actually being dumped back into the
virtual servers onto a single
The Fluke Ti20 Thermal
room in an endless cycle. The
blade. An enclosure or rack
Imager makes two-dimensional
air-conditioner cools itself down
holds eight blades, but each full
representations of the surface
and shuts off. But the circulation
enclosure requires a lot of power. fans keep working. They actutemperatures of objects in an
Many data centers simply can’t
infrared image. The support
ally kick the hot air back into the
analyst uses the Ti20 to monitor
supply that power. They want
room. Overall, it’s a very poorly
us to use an older technology so designed room. We’re looking to
data centers for general cooling efficiency and to inspect law they can support our needs.”
the data center to restructure the
Blade servers also produce
firm’s servers in those centers.
cooling system.”
considerable heat and require
Software that comes with the
Finding faulty cooling
imager allows him to change key more cooling than many cenarrangements for the law firm’s
parameters, optimize images, and ters can supply. In such cases,
servers is another of the analyst’s
the analyst uses the Fluke Ti20
extract maximum details from
uses for the Ti20. “Because of the
and Fluke 975 to 1) map coolcollected data.
cooling requirements for blade
ing patterns in data centers, 2)
servers, we have been using the
Problems and solutions
find faulty cooling arrangements Ti20 to monitor the temperatures
and 3) determine when cooling,
of the air flowing into the fronts
As the law firm seeks to expand
air
flow
and
air
temperatures
and out the backs of our blade
its data handling capabilities,
are inadequate to guard against
racks,” he says.
the biggest problem the support
breaches
of
server
warranties.
A common problem experianalyst faces is that data centers
Mapping cooling patterns
enced by their blade servers is
lack the required power and
allows company personnel to
hot air entering the front of the
cooling capabilities to support
see
the
overall
effects
of
cooling
blades. Only cooling air should
new technologies.
within a data center. This may
be entering the rack fronts.
“We want to take advantage
seem like a duplication of effort,
Two situations that lead to this
of the latest blade servers, but
since
data
centers
themselves
problem are 1) missing blanks
it’s difficult to find data centers
monitor the environmentals—
on empty rack slots and 2)
that can support them,” he says.
power,
air,
humidity,
cooling,
etc.
server aisles set up with servers
“Blade servers are much more
However, “our primary use for
arranged front to back.
efficient [than traditional servthese tools is to check what we
ers]. We can pack six or seven

 Fluke Corporation Monitoring temperature, humidity, and airflow in datacenters

The first situation usually
occurs because a user of the data
center does not need all eight
slots in a rack or because the
data center lacks the capability
to provide power to a full rack.
In either case, there are empty
slots. Blanking panels should
cover those unused slots so that
they are not open to the environment.
The analyst says that he has
documented instances of missing blanking panels at the firm’s
secondary center. “There were
empty spaces on the top four
slots,” he says. “Nobody could
believe it, but hot air from the
backs of the servers was circulating over the tops of the racks
and coming right back in the
front. That greatly increased the
temperature of the blades and
decreased their efficiency. We
needed to fill the tops of those
racks with blanking plates.”
The best strategy for a data
center—especially a data center
with blade servers—is to install
servers back-to-back in rows
facing the fronts of servers in
adjacent rows. This creates alternating cold aisles and hot aisles.
“A lot of data centers are set
up with one row of servers after
another—back to front, back to
front, back to front,” he says disapprovingly. “The hot air from
one row of servers blows onto
the fronts of the next row, and
that’s continued throughout the
center. In Europe, we are looking
for a center with alternating hot
and cold aisles.”
Safeguarding server warranties is the analyst’s principal
impetus for monitoring the law
firm’s servers. “Our blade manufacturer has a recommended
maximum temperature that servers can reach. If a server gets
above that threshold, it is no longer covered under our warranties
and contracts. That would be a
huge problem for us.”
Because of these warranty
considerations, company personnel need to verify what data
center owners tell them about
the cooling in their facilities. And
while the blades themselves

have internal monitors that track
their temperatures, the analyst
needs know how effectively the
cooling supplied by the data center is doing the job.
He uses the Ti20 to collect
thermal images of the fronts
of the blades to determine the
temperature of the air flowing
in. Then, he compares this temperature to the temperature of
the air coming out the back of
the rack. Finally, he compares
these temperatures to the blade
manufacturer’s recommended
temperature threshold for the
servers.
“If necessary,” he says, “we
can go back to a data center’s
owners and say, ‘This is the airflow that you are telling us we’re
getting, and this is what we see.
You’re not meeting our requirements. We need you to upgrade
your systems to make sure you
meet our specifications.’”

Additional capabilities
with the Fluke 975
The Fluke 975 AirMeter allows
the analyst to precisely measure
air temperatures and convert the
air-meter data into reports for
superiors or data center operators. Using the Ti20 Thermal
Imager and the 975 AirMeter
together “provides results from
different angles,” he says. “If we
use the imager to reveal the surface temperatures, then we can
use the airflow meter to register
the actual temperature of the air
going into racks.”
The 975 AirMeter also measures relative humidity (RH)
and airflow. Excessive humidity in a data center can lead
to condensation on equipment
and places an undue load on
the air-conditioning system. RH
readings played a significant
role in uncovering difficulties at
the local data center. Regarding airflow, “In our primary and
secondary data centers, the air
comes in through the floors,”
he says. “We can use the airflow sensor on the 975 to make
sure that airflow is at the rate
required by our servers.”

 Fluke Corporation Monitoring temperature, humidity, and airflow in datacenters

Creating tracking
databases
The analyst’s job includes creating and maintaining tracking
databases. To do this, he periodically uses the Ti20 to make
images at specific points in the
primary and secondary data centers. He then logs the data into
the database for review as necessary. “We can graph the data
for each location and see if the
temperature is rising, falling or
staying the same over time,” he
explains.
Equipment frequently moves
within data centers, as clients
expand their server capacity or
stop using the center altogether.
If the law firm brings a new
piece of equipment into a data
center or reacts to a temperature
problem by moving an existing
server, the tracking database
allows them to assess how the
change affected ambient temperatures.
From such findings, the support analyst, in cooperation with
data center personnel, can determine when the center needs
more cooling or when equipment is packed in too densely.
In general, the database lets the
law firm and data center personnel pinpoint areas where the
air is more or less cool or where
there is more or less airflow. The
analyst speculates that as he
becomes more familiar with the
975 AirMeter and its data logging
capabilities, it will play a greater
role in his tracking databases.

Fluke.	Keeping your world
	
up and running.®
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2007 Fluke Corporation. All rights reserved.
Specifications subject to change without notice.
Printed in U.S.A. 5/2007 3034678 A-EN-N Rev A



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
XMP Toolkit                     : 3.1.1-111
About                           : cb320f2b-bd86-11da-8cc6-f4f804469fde
Create Date                     : 2007:05:14 10:31:36-07:00
Metadata Date                   : 2007:05:14 10:31:49-07:00
Modify Date                     : 2007:05:14 10:31:49-07:00
Creator Tool                    : Adobe InDesign CS2 (4.0.5)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 11801 bytes, use -b option to extract)
Instance ID                     : uuid:ff37d6d6-0240-11dc-9655-000a95b26bba
Document ID                     : adobe:docid:indd:5c6213e5-037d-11dc-8f74-f3a063224905
Rendition Class                 : proof:pdf
Derived From Instance ID        : 00c77386-f895-11db-91e0-9994c60fbe60
Derived From Document ID        : adobe:docid:indd:00c77385-f895-11db-91e0-9994c60fbe60
Manifest Link Form              : ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 300.00, 300.00
Manifest Placed Y Resolution    : 300.00, 300.00
Manifest Placed Resolution Unit : Inches, Inches
Manifest Reference Instance ID  : uuid:5CF2798BA93711DB9B74BA2D4B57F9DE, uuid:AA6C9B4EE0B1DB119958F070F76F6024
Manifest Reference Document ID  : uuid:5CF2798AA93711DB9B74BA2D4B57F9DE, uuid:A96C9B4EE0B1DB119958F070F76F6024
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 3
Creator                         : Adobe InDesign CS2 (4.0.5)
EXIF Metadata provided by EXIF.tools

Navigation menu