ICP Furnace/Heater, Gas Manual L0502541
User Manual: ICP ICP Furnace/Heater, Gas Manual ICP Furnace/Heater, Gas Owner's Manual, ICP Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 20
Download | ![]() |
Open PDF In Browser | View PDF |
MULTI POSITION WARM AIR FURNACE Save these instructions for future reference. 02/05/22 Printed in Canada X40094 Rev. A 445 01 4094 00 PART 1 INSTALLATION 2) SAFE INSTALLATION REQUIREMENTS Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with codes or, in the absence of local codes, with codes of the country having jurisdiction. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments. 1) SAFETY LABELLING 1.1) Danger, Warning and Caution: AND SIGNAL WORDS The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used in product labels to signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product. 1.2) Signal Words: DANGER - Immediate hazards which WILL result in death or serious Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, property damage, personal injury and/or death. Fire hazard The furnace must be installed in a level position, never where it will slope to the front. If the furnace were installed in that position, oil could drain into the furnace vestibule and create a fire hazard, instead of draining properly into the combustion chamber. injury. WARNING - Hazards or unsafe practices which COULD death or injury. result in CAUTION - Hazards or unsafe practices which personal injury or product or property damage. result in 1.3) COULD NOTE: It is the personal responsibility and obligation of the customer to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances. a. This furnace is NOT approved for installation in mobile homes, trailers or recreation vehicles. b. You must have a sufficient supply of fresh air for combustion and ventilation to the area in which the furnace is located, Do NOT use this furnace as a construction heater or to heat a building that is under construction, Use only the Type of fuel oil approved for this furnace (see Rating Plate on unit). Overfiring wilt result in failure of heat exchanger and cause dangerous operation. Visually check all oil line joints for signs of wetness, which would indicate a leak, Connect furnace to the chimney, The points in Part 2 "Operation" are vital to the proper and safe operation of the heating system, Take the time to be sure they are all done. Follow the rules of the NFPA Pamphlet No.31 (for USA) and 13139 (for Canada) or local codes for locating and installing the oil storage tank. Follow a regular service and maintenance schedule for efficient and safe operation. Signal Words in Manuals: The signal word WARNING following manner: is used throughout this manual in the c, d. The signal word CAUTION following manner: is used throughout CAUTION this manual in the e, f, g. h. i. j. k. I. m. n. Before servicing, allow furnace tocool.Always shut offelectricity andfueltofurnace whenservicing. ThiswilIprevent electrical shock orburns. Seal supply andreturn airducts. Theventsystem MUST bechecked todetermine thatitisthe correct typeandsize. Install correct filtertypeandsize. UnitMUST be installed so electrical components are protected from direct contact with water. 2.1) Safety Rules: Your unit is equipped with safety devices that may keep it from operating if sensors detect abnormal conditions such as clogged exhaust flues. If the structure will be unattended during cold weather you should take these precautions. a. Turn off main water supply into the structure and drain the water lines if possible. Open faucets in appropriate areas. b. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Suggest they call a qualified service agency, if required. Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner. 2.3) The U.S. Consumer Product Safety Commission recommends that users of oil-burning appliances install carbon monoxide detectors. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas-fired fireplaces, wood fireplaces, and several other items. Carbon monoxide can cause serious bodily injury and/or death. Therefore, to help alert people d potentially dangerous carbon monoxide levels, you should have carbon monoxide detectors listed by a nationally recognised agency (e.g. Underwriters Laboratories or International Approval Services) installed and maintained in the building or dwelling (see Note). b. There can be numerous sources of fire or smoke in a building or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire and smoke detectors listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below). and makes no representations regarding any brand or type of I NOTE: detector.The manufacturer of your furnace does not test any detectors All local and national code requirements governing the installation of oil burning equipment, wiring and flue connections MUST be followed. Some of the codes that may be applicable are: CSA B139 INSTALLATION CODE BURNING EQUIPMENT FOR NFPA31 INSTALLATION EQUIPMENT BURNING ANSI/NFPA90B WARM AIR HEATING AND CONDITIONING SYSTEMS ANSI/NFPA 70 NATIONAL ELECTRICAL CODE CSA C22.2 No3 CANADIAN ELECTRICAL CODE ANSI/NFPA CHIMNEYS, FIREPLACES, AND SOLID FUEL BURNING APPLIANCES 2.2) Freezing Temperature Structure: and Your Freeze warning. Turn off water system. If your unit remains shut offduring cold weather the water pipes could freeze and burst, resulting in serious water damage. 211 OF OIL OIL AIR VENTS Only the latest issues of the above codes should be used. 3) Insure that the area around the combustion air intake I terminal is free of snow, CAUTION ice and debris. Installation regulation: LOCATING THE FURNACE CAUTION Check carefully your furnace upon delivery for any evidence of damage that may have occurred during shipping and handling. Any claims for damages or lost parts must be made with the Transport Company. As this unit may be installed as an upflow, counterflow or horizontal furnace (right or left), it may be located in a basement, on the same level as the area to be heated, suspended, or in a crawlspace. In any case, the unit should always be installed level. In a basement, or when installed on the floor (as in a crawlspace), it is recommended that the unit be installed on a concrete pad that is 1" to 2" thick. When installed in the counterflow position, this furnace must not be installed on combustible flooring, unless the approved sub-base is used (Model # DFB-101). The flue pipe must exit the cabinet through one of the panel opening, then extended up the side of the furnace. Care must be taken to insure that the clearances from the 4) VENTING Poison carbon monoxide hazard. gas, fire and explosion Read and follow all instructions in this section. Failure to properly vent this furnace can result in property damage, personal injury and/or death. flue pipe to combustible construction are maintained. Also, it is recommend to use the flue pipe guard kit (Model # FPG-101 or # FPG102) to insure that condition does not exist. a fire hazard When installed in a horizontal position, the furnace may be suspended by using an angle iron frame, as long as the total weight of both the furnace and the frame are allowed for in the support calculations. (Other methods of suspending are acceptable.) When installed in the Horizontal Position, this furnace must not be installed on combustible flooring, unless the approved sub-base is used (Model # HFB-101). This furnace construction. enclosure. is approved for reduced clearances to combustible Therefore, it may be installed in a closet or similar The required minimum clearances for this positions are specified in tables # 3.2 and 3.3. furnace in all The furnace should be located as close as possible to the chimney or vent in order to keep vent connections shorts and direct. The furnace should also be located as near as possible to the center of CAUTION When the furnace (chimney installation) is co-vented with other combustion appliances such as a water heater, the allowable venting materials (i.e. L-Vent etc.) for use with those appliances should also be investigated. Poison carbon monoxide gas hazard Never install a hand operated damper in the vent pipe. However, any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired. Be sure to follow instructions provided with vent damper. Read and follow all instructions in this section. the air distribution system. Failure to properly vent this furnace or other appliances can result in property damage, personal injury and/or death. Do NOT operate furnace in a corrosive atmosphere or any other damaging I containing chlorine, fluorine CAUTION chemicals. Refer to Part 1, section 5.2. Venting of the furnace should be to the outside and in accordance with local codes or requirements d the local utility. OIL FIRED APPLIANCES SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE. Electrical shock hazard. This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect the electrical components from water. Outdoor installation would lead to a hazardous electrical condition and to premature furnace failure, property damage, bodily injury or death. For additional venting information refer to ANSl/NFPA 211 Chimney, Fireplaces, Vents and Solid Fuel Burning Appliances and/or CSA B 139 Installation Code. This furnace is certified for use with Type '%" vent (maximum flue gas temperature 575°F). The flue pipe clearance knockout in the front top or side panel should be removed. Install the flue elbow so that it exits the furnace cabinet through that opening. Pre-instatlation vent system inspection: Before this furnace is installed, it is highly recommended existing vent system be completely inspected. that any For any chimney or vent, this should include the following: a. Inspection for any deterioration in the chimney or vent. If deterioration is discovered, the chimney must be repaired or the vent must be replaced. b. Inspection to ascertain that the vent system is clears and free of obstructions. Any blockage must be cleared before installing this furnace. ¢. Clearing the chimney or vent if previously solid fuel burning appliance or fireplace. d. Confirming that all unused properly sealed. e. Verification that the chimney is properly lined and sized per the applicable codes, (Refer to list of codes on page 3.) used for venting a Poison carbon monoxide gas hazard. chimney or vent connections are Masonry Chimney: Comply with ANSI/NFPA (in U.S.) or CSA (in Canada) standard for the installation of Oil Burning Equipment and applicable provision of local building codes to provide combustion and ventilation air. This furnace can be vented into an existing masonry chimney. This furnace must not be vented into a chimney servicing a solid fuelburning appliance. Before venting this furnace into a chimney, the chimney must be checked for deterioration and repaired if necessary. The chimney must be properly lined and sized per local or national codes. Failure to provide adequate combustion and ventilation air can result in personal injury and/or death. If the furnace is vented into a common chimney, the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into the chimney. 5.1) General: C. Never reduce the pipe size below the outlet size of the furnace. Oil furnaces must have an adequate supply of combustion air. It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace. However, home improvements such as new windows, doors, and weather stripping have dramatically reduced the volume of air leakage into the home. d. All pipes should be supported using the proper clamps and/or straps. These supports should be at least every four (4) feet. When this furnace e. All horizontal runs of pipe should have at least a 1/4" per foot of upward slope. ventilation openings are required for combustion f. All runs d possible. enclosure g. h. Seams should be tightly joined and checked for leaks. The flue pipe must not extend into the chimney but be flush with the inside wall. i. The chimney must extend three (3) feet above the highest point where it passes through a roof of a building and at least two (2) feet higher than any portion of a building within a horizontal distance of ten (10) feet. It shall also be extended at lest five (5) feet above the highest connected equipment flue collar. The following requirements are provided for a safe venting system: a. b. j. Ensure that the chimney flue is clear of any dirt or debris. Ensure that the chimney is not servicing an open fireplace. pipe be as short as possible with as few turns as should be located is installed in a closet or enclosure, air. two (2) The openings about 6" from the top and the bottom of the at the front of the furnace. Table # ! indicates the minimum ventilation openings dimensions required. TABLE # 1 Input (MBTUH) 75- 105 120-155 Check local codes for any variance. Length (in,) 16 20 Height (in,) 8 10 Factory Built Chimneys: May use listed factory built chimneys. Refer to chimney manufacturer's instructions for proper installation. 4.1) BAROMETRIC Home air exhausters are common. Bathroom and kitchen fans, power vented clothes dryers, and water heaters all tend to create a negative pressure in the home. Should this occur, the chimney become less and Iess effective and can easily downdraft. DRART CONTROL The barometric draft control shipped with furnace MUST be used with furnace to ensure proper operation. Instructions for installing control are packed with control. Heat recovery ventilation (HRV) systems are gaining in popularity. The HRVs are not designed to supply combustion air. If not properly balanced, a serious negative pressure condition could develop in the dwelling. 5) 5.2) AIR FOR COMBUSTION Contaminated Combustion Air : Installation in certain areas or types of structures will increase the exposure to chemicals or Halogens which may harm the furnace. These instances will require that only outside air for combustion. The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion. a. b. c. Commercial building. Building with indoor pools. Furnaces installed near chemical storage areas. Exposure tothese substances: a. Permanent wave solutions forhair. b. Chlorinated waxes andcleaners. c. Chlorine based swimming poolchemicals. d. Water softening chemicals. e. De-icing salts orchemicals. f. Carbon tetrachloride. g. Halogen typerefrigerants. h. Cleaning solvent (such asperchloroethylene). i. Printing inks, paint removers, varnishes, etc.. j. Hydrochloric acid. k. Solvent cements andglues. I. Antistatic fabric softeners forclothes dryers. m. Masonery acid washing materials. a. b. c. d. Set your voltmeter to line voltage. Place one prong on your grounded electric entry box and one prong on the black wire. Read the voltage. If the voltage is zero, check the white wire. If Iine voltage shows. Reverse the 115-volt leads entering the furnace junction box. FIGURE # 1 BLACK 6) OIL TANKS AND LINES Check your local codes for the installation of the tank and accessories. A manual shut-off valve and an oil filter shall follow sequence from tank to burner. Be sure that the oil line is clean before connecting to the burner. The oil Iine should be protected to eliminate any possible damage. Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel pump (more than 8' lift use 2 stage pump and more than 16' an auxiliary pump). Follow the pump instructions to determine the size of tubing you need in relation of the lift, or the horizontal distance. At the beginning of each heating season or each year, verify the complete oil distribution system for oil leak. At the beginning of each heating season or each year, verify the complete oil distribution system for oil leak. 7) V C A o \ o BLACK RED Nozzles: The burners are provided with the highest capacity USGPH nozzle installed. If another size nozzle, or replacement nozzle is required, use the nozzle spray angle, type and manufacturer recommended in Table #3. Note that all nozzle-marked sizes are based on a pump pressure of 100 psi. Always select nozzle sizes by working back from the actual desired flow rate at operating pressure, and not by the nozzle marking. BURNER INSTALLATION Air and turbulator settings: I upright IMPORTANT: always be on installed position Burner with themust ignition control top. in the Before starting the burner for the first time, adjust the air and turbulator settings to those listed in the Table #3. Once the burner becomes operational, final adjustment will be necessary. Fuel supply system: Mounting the burner: Fuel Specifications a. b. The warm air furnace burner mounting plate has a four bolts configuration. Position the mounting gasket between the mounting flange and the appliance burner mounting plate. Line up the holes in the mounting flange with the studs on the appliance mounting plate and securely bolt in place. After the burner is mounted: a. b. c. d. e. Remove drawer assembly or air tube combination Install nozzle (see specifications) Confirm electrode settings Make the electrical connections Complete oil line connections Do not turn on the burner until you have checked the I polarity CAUTION Checking the polarity: The oil burners used on the furnaces have solid state control systems which makes them sensitive to the proper connections of the hot and neutral power lines. The controls will be damaged if the two lines are reversed. I No.! NOTE:or Use No.2 No.1 Furnace or No.2 Oil. Heating Oil (ASTM D396) or in Canada, use Before starting the burner be sure the fuel tank is adequately filled with clean oil. NOTE: THE BACK SHOULD NOT BE CUT OUT FOR RETURN AIR Fire and explosion hazard. Provision is also made on this furnace for a bottom return air duct. Use only approved heating type oil in this furnace. DO NOT USE waste oil, used motor oil, gasoline or kerosene. Knockouts are provided on the floor of the furnace to facilitate the cut out requirement to assembly d air filter rack and return ductwork. (We recommend the use of this opening for horizontal installations). Use of these will result in death, personal and/or property damage. When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space. injury operated. This will soon disappear. It is only the oil used on the parts I NOTE: You may notice a slight odor the first time your furnace is during manufacturing. 8) INSTALLING Install air conditioning cooling coil (evaporator) on downstream (in the supply air plenum) or furnace. If separate evaporator and blower unit is used, install good sealing dampers for air flow control. Cold air from the evaporator coil going through the furnace could cause condensation and shorten furnace life. ACCESSORIES I Dampers (purchased locally) CAUTION MUST be automatic. Electrical shock hazard. Turn OFF electric power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage. Failure to do so could result in property damage, bodily injury or death. 8.1) Air conditioning: An air conditioning coil may be installed on the _side only. Also, a minimum clearance must be allowed between the bottom of the coil drain pan, and the top of the heat exchanger according to the coil manufacturer instruction. Wire the thermostat and condensing unit contactor as indicated in the wiring diagram (figures # 4 and # 4.! ). 8.2) Ductwork and Filter: Installation: Design and install air distribution system to comply with Air Conditioning Contractors of America manuals or other approved methods that conform to local codes and good trade practices. Knockouts are provided on both sides of the furnace to cut the required size opening for the installation of the return ductwork. This can be done on either the right or the left side of the furnace. See Figure # 3 and 3.1 for location and dimensions. Poison carbon monoxide gas hazard. Do NOT draw return air from inside a closet or utility room. Return air duct MUST be sealed to furnace casing. Failure to properly seal duct can result in death, personal injury and/or property damage. Poison carbon monoxide gas hazard. Install evaporator furnace ducting. coil on the supply side of the Evaporator coil installed in return side ducting can cause condensation to form inside heat exchanger resulting in heat exchanger failure. This could result in death, personal injury and/or property damage. PART 2 OPERATION 1) SEQUENCE OF OPERATION 1.1) Sequence of operation - Beckett AFG: 1. Normally open contact (T-T) thermostat calls for heat. on primary relay closed when 2. The motor starts and spark is established. The pump pressure builds and the poppet valve opens admitting fuel to the nozzle. Pressure builds and poppet valve opens, allowing oil to flow through nozzle. 3. Spark ignites oil droplets. 4. Cad cell senses flame and burner continues to fire. 5. After 60 sec., the fan control starts the circulating air blower and electronic air cleaner. 6. The circulating air blower and burner motor remain on until the thermostat is satisfied. The ignition transformer continues to spark. IMPORTANT The burner must be put in operation for at least 10 minutes before any test readings are taken. For new installations, set up the burner to the settings (see table # 3), before firing. These are rough adjustments but they will ensure that the burner will start and run smokefree in advance of the fine adjustments being made. Open the oil bleed port screw and start the burner. Allow the oil to flush into a portable container for at least 10 seconds. Slowly close the bleed screw - the oil should flow absolutely free of white streaks or bubbles to indicate that no air is being drawn into the suction side of the oil piping and pump. Tighten the bleed screw and the burner wilI fire. Adjust the oil pressure as indicated in Table # 3. 2.2) 7. Thermostat is satisfied. 8. Primary relay contacts open and the burner fan motor down. The ignition transformer ceases sparking. 9. CHECKS AND ADJUSTMENTS 2.1) General: During initial start-up and subsequent furnace must be thoroughly tested. yearly maintenance 1. Set thermostat lower than the room temperature. 2. Press the reset button on the burner primary control (relay). 3. Set thermostat higher than the room temperature. 4. If the burner motor does not start or ignition fails, turn off the disconnect switch and CALL YOUR SERVICEMAN shuts Depend on the delay of setting of the fan control, the circulating air blower stop after 60, 90, !20 or 150 seconds. (See part 2, section 2.4). 2) Restart if Burner Should Stop: calls, the CAUTION Do not attempt to start the burner when excess oil has accumulated, when the furnace is full of vapour, or when the combustion chamber is very hot. 2.3) Perform the smoke / CO2 test: 1. Pierce a test hole in the smoke pipe near the furnace breech. Insert the smoke test instrument probe into the open hole. 2. Starting with a zero smoke reading, gradually reduce the burner air setting until just a trace (#1 on Bacharach Scale) of smoke results. 3. Take a CO2 sample at the same test location where the smoke sample was taken. Note the CO2 reading associated with the #! smoke condition. 4. Adjust the burner air setting to obtain a CO2 reading !% lower than the reading associated with the #1 smoke. 5. This method of adjusting the CO2 will allow adequate excess air to ensure that the burner will burn clean for the entire heating season. 2.4) FAN ADJUSTMENT Remove the restriction and the burner should come back on in a few minutes. CHECK This furnace is equipped with a 4 speed direct drive motor to deliver a temperature rise within the range specified on the rating plate, between the return and supply pressure at the external duct static pressure noted on the rating label. Adjust the fan speed ACCORDING TO THE OIL INPUT SELECTED so that the temperature rise is within the rise specified on the rating plate (see table # 3). Consult the wiring diagram for speed changes on the direct drive motor. To adjust fan OFF time, the DIP switches on the control board adjusted to obtain the desired timing (See figure # 2). For year round air conditioning: The furnace is designed for use in conjunction with cooling equipment to provide year round air conditioning. The blower has been sized for both heating and cooling, however, the fan motor speed may need to be changed to obtain the necessary cooling air flow. Heating: The blower speed is factory set to deliver the required normal duct static pressure. airflow at Cooling: FIGURE # 2 Delay off setting The blower speed may be adjusted in the field to deliver the required airflow, for cooling application, as outlined in table # 3 Constant Blower Switch: This furnace is equipped with a constant low speed blower option. Whenever the room thermostat is not calling for heating or cooling, the blower will run on low speed in order to provide air circulation. 60 Sec. 90 Sec. 120 Sec. 150 Sec. side of the control box can be used to 'turn off" the constant speed. DIP switchs DNS-0378 If this constant blower option is not desired, the rocker switch on the Rev. A 2.5) Vent temperature test: 1. Place a thermometer in the test hole located in the breech pipe. 2. The vent temperature should be between 400 and 575°F. If not, check for improper air temperature rise, pump pressure, nozzle size, or for a badly sooted heat exchanger. 2.6) Limit control check After the furnace has been in operation restrict the return air supply by blocking return registers and allow the furnace to The burner will shut OFF and the main run. for at least 15 minutes, the filters or closing the shut down on high limit. blower should continue to PART 3 MAINTENANCE 1) Preventive GENERAL Maintenance: "Preventive maintenance" is the best way to avoid unnecessary expense and inconvenience, Have your heating system and burner inspected at regular intervals by a qualified service man. After inspection, a complete combustion test must be performed after each annual service of the unit to maintain optimum performance and reliability. Electrical shock hazard. Turn OFF power to furnace before any disassembly or servicing. Failure to do so can result in property bodily injury and/or death. 10 damage, Do not tamper technician, with the unit or controls. Call your service Before calling for service, check the following. a. b. c. d. e. Check oil tank gauge and check if the oil tank valve is open. Check fuse or circuit breaker. Check if shut-off switch is 'ON". Reset thermostat above room temperature. If ignition does not occur turn off the disconnect switch and call your qualified service technician. When ordering replacement parts, specify model number and serial number. 1.1) the complete furnace Heat exchanger cleaning: Ordinarily, it is not necessary to clean the heat exchanger or flue pipe every year, but it is advisable to have your oil burner serviceman check the unit before each heating season to determine whether cleaning or replacement of parts is necessary. CAUTION Be sure the blower is adequately supported when sliding out of the mounting rails, especially in the horizontal, in order to prevent dropping the blower and injuring yourself or damaging the blower! To remove the blower from the furnace: 1. Turn 'OFF" all utilities upstream of the furnace. 2. Remove the burner access door and blower door. 3. 4. Remove the blower retaining screw (on the blower partition panel). Remove cover from control box and disconnect the thermostat and power wires from the board. 5. Slide the blower forward on the rails toward the front of the unit. 6. Reverse the above steps to reinstall the blower. (Refer to wiring diagram figures # 4 a 4.1 of this instruction or the diagram located on the inside of the blower door to properly rewire the unit.) If cleaning is necessary, the following steps should be perfomed: 1. Turn 'OFF" atl utilities upstream of the furnace. 2. Disconnect the flue pipe. 3. Remove the flue cellar panel located in the front part of the warm air furnace. 4. Remove the radiator baffles. 5. Disconnect furnace. 6. Clean the secondary tubes, and the primary cylinder with stiff brush and vacuum cleaner. 1.3) the oil Iine and remove the Remove the drawer assembly. Clean all foreign matter from the retention head and electrodes. If a Beckett AFG burner has been installed, the burner will have to be removed to check the retention head and to check for proper "Z" dimension with the Beckett "T" gauge supplied with every burner. Check for any sign of oil boiling out d the nozzle and caulking - the solenoid valve could be leaking (if applicable). oil burner from the 1.4) 7. 8. After cleaning, replace the radiator baffles, flue collar plate and oil burner. Readjust burner for proper operation. Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil, or if the burner has been operating in a severely fouled condition. 1.2) Burner drawer assembly: BLOWER REMOVAL To remove the blower from the furnace: Nozzle: Replace the nozzle with the one specified in table # 3. 1.5) Oil filter: Tank filter: The tank filter should be replaced as required. Secondary filter: The 10 micron (or less) filter cartridges should be replaced annually. 1.6) Air filters: Air filters are the disposable types. The disposable filters should be replaced on at least an annual basis. Dusty conditions, presence of animat hair etc. may demand much more frequent filter changes. Dirty filters will impact furnace efficiency and increase oil consumption. 1. Turn 'OFF" all utilities upstream of the furnace. 2. Remove the burner access door and blower door. 3. Remove the blower retaining screw (on the blower rails). 1.7) 4. Remove cover from control box and disconnect the thermostat and power wires from the board. Do not lubricate the oil burner motor or the direct drive blower motor as they are permanently lubricated. 5. Slide the blower forward on the rails toward the front of the unit. 6. Reverse the above steps to reinstall the blower. (Refer to wiring diagram figures # 4 a 4.1 of this instruction or the diagram located on the inside of the blower door to properly rewire the unit.) Motor lubrication: 11 PART 4 INFORMATION Model: Seria! number: Date of installation of the furnace : Service telephones - day : Night : Dealer's name and address : RESULT OF START-UP TEST Nozzle: Burner adjustments Pressure : : psi Primary air Fine air Draw Assembly 002 : Smoke scale : (Bacharach) Gross stack temperature: oF Ambiant temperature: oF Chimney draft: "C.E. Overfire draft : "C.E. Test made by : 12 TABLE# 3 Technicalspecifications, Model : NOMF RATING AND PERFORMANCE .1 Firing rate (USGPH) 75 J 90 0.5 [ 105 [ 120 ..[ 140 J 155 0.75 0.85 1 1. ! Input (BTU/h) 70 000 91 OOO 105 0go 119 O00 140 0go 154 O00 Heating capacity (BTU/h) 57 00O 74 OOO 85 00O 97 OOO 1!5 0go 126 O00 80 80 80 80 80 80 AFUE % 0.65 NOMF Heating temperature rise (Degr. F) 55 - 85 Degr. F BECKETr BURNER; MODEL AFG (3450 rpm) AFG-F3 AFG-F3 YES YES YES 3 3/8" # 31646 2 3/4" # 3383 2 3/4" # 3383 Low firing rate baffle Static disc, model Nozzle - 100 PSIG pump pressure (Detavan) Combustion air adjustment (band/shutter) ELECTRICAL SYSTEM 55 - 85 Degr. F AFG-F6 0.50 - 7OW 0.65 - 70W 0.75 - 7OB 0.85 - 70B I 1.00 - 7OW 1.!0 - 70W O/ 5 0/7 O/ 8 1/ 8 / 4/4 2/8 Volts - Hertz - Phase 115-60-1 115-60- ! Operating voltage range 104 - ! 32 104 - 132 Rated current (Amps) 12.2 15.7 Minimum ampacity for wiring sizing 13.7 18. ! Max. w ire Ienght (ft) 26 26 Max. fuse size (Amps) 15 20 40 VA 40 VA 40 VA 40 VA 30 VA 30 VA Control transformer External control pew er available Heating Cooling BLOWER DATA Blow erspeepat0.5"W.C, static pressure MED-LOW Motor (HP) / number of speeds I MED-HIGH I HIGH MED-LOW I MED-HIGH I 1/3 HP / 4 speeds 3/4 HP / 4 speeds Blow er w heel size (in) 10 X !0 12 X 10 Filter quantity and size 16 X 24 20 X 30 HIGH DIMENSIONS Overall W x L x H ( in ) 20 x 35 x 48.75 Shipping w eight (Lbs) 20 x 39.50 220 250 Supply air duct (in) 19 x 20 19 x 24 Return air duct ( in ) 15 x 23 17 x 29 TABLE x 53 # 3.1 Air delevery - CFM with air filter NOM F105D12A EXTERNAL STATIC PRESSURE WITH AIR FILTER SPEED 0.2 0.3 0.4 0.5 HIGH 1425 1350 1305 1250 MED- HIGH 1130 1045 1000 950 MED-LOW 840 810 770 740 NOM F155E19A EXTERNAL STATIC PRESSURE WITH AIR FILTER SPEED 0.2 0.3 0.4 0.5 HIGH 2080 2041 1965 1864 MED- HIGH 1892 1859 1770 1675 MED-LOW 1556 1475 1394 1318 13 (n 8o Be VERSION EN FRANCAIS D'INSTALLATION. ,,ll_ INCLUS DANS MANUEL L° ML MH _z 115 FIoAPAc, oR VAC (FUSEO I_/60HZ GND _L pOWER DISCONNECT ,llll<_ ON SUPPLY HOT LEO] N_ o HI J c ED MOT ]6_1 LEAE _> _ ON CN6 2 CN6 4 Q. BLACK BLUE 3 RED OIL BLUE INPU COOLINO to 3 TONS l : 2 "11 LIMIT 1/2 .,,& r,a ,1_ tD o" c I tD STANDARD HEAT / COOL WIRING DIAGRAM WITH ST9103 ELECTRONIC FAN TIMER OIL INPUT : 0.75 COOLING CAPACITY °b USGPH ; 3 UNUSED TONS MAX Jumper : USE JUMPER ONLY WHEN THE COOLING AND HEATING SPEEDS ARE SAME FOR HUMIDIFIER FOR HUMIDIFIER AND EAC, REMOVE THE DUMMY TERMINAL OR EAC FOR ELECTRONIC AIR CLEANER MARKED HUM OIL INPUT : 0.50 USGPH COOLING CAPACITY : 2 TONS MOT LEAD>> "_J_BLFoCLwE LAqqON co VERSION cu EN FRANCAIS INCLUS BANS MANUEL 115 D'INSTALLATION. ,lll_ I CAPAC'TOR GND CAPACITOR LO 8 Oz LI L2 ML I VAC (FUSED 1_' 60HZI DISCONNECT pOICI_R ON HOT SUPPLY LFG] 2 (H) (N) 120 VAC POWER SUPPLY BLACK MH 120 BLACK HI LOMNN,MLc c 1 TRA_ R99GO01 : 3 BT91 BLACK BLUE ( im LIMIT(S) BLUE a ___ RED CN6 8_CN6 5 OIL INPUT : 1,00 USGPH COOLINO CAPACITY : 4 to 5 RED TONS MAX tF < 5 LO CAPACITOR Oz _ < OL ML _, _+ MH _ I CAD WHITE CELL ON _m_ LEAD>> Sl O UNUSED M STANDARD HEAT / COOL WIRING DIAGRAM WITH ST9105 ELECTRONIC FAN TIMER OIL INPUT : 0.85 USGPH COOLING CAPACITY ; 4 TONS MAX * Jumper : USE JUMPER SPEEDS ARE SAME FOR HUMIDIFIER FOR HUMIDIFIER ONLY WHEN THE COOLING AND AND EAC, REMOVE THE DUMMY TERMINAL OR EAC ELECTRONIC AIR CLEANER L HEATING BLACK BLUE COOL *Jumper MARKED HUM OIL INPUT " 1.10 USGPH COOLING CAPACITY : 5 TONS L_ [__@ LEAD UNUSED MOT IRCULAllON >_ x"_B LRoCwUL_ FIGURE # 3 Model: NOMF105D12A J I I DNS-0832 Rev 2O 7 I I I ,I 3 o 1663 35 A TABLE # 3.2 Minimum clearances - combustion materials (in), MODEL: NOMF105D12A LOCATION SIDE APPLICATION UPFLOW DOWNFLOW FURN ACE 0 2 2 SUPPLY 1 2 1 0 1 0 PLENUM WITHIN 6 FT OF FURNACE BACK FURN ACE TOP FURNACE OR PLENUM 2 2 2 HORIZONTAL 2 2 3 0 **0 **0 4 4 4 9 9 9 8 8 24 BOTTOM FLUE PIPE FRONT WARM AIR DUCT WITHING 6 FT OF FURNACE FURNACE (**COMBUSTIBLE HORIZONTALLY VERTICALLY 16 HORIZONTAL FURN ACE FLOOR WITH THE SUBBASE) OR BELOW FLUE PIPE ABOVE FLUE PIPE FIGURE # 3.1 Model: NOMF155E19A FOR6_ DIA FLUE TCPKN0CK OUT 1_oo 2_00 2900 _=_1259-- --19.00---j _F '#_J l 5&00 01LINLET _(BOTH SIDE) I laD_ 1_.75 DNS-0833 | R@v. A TABLEAU # 3.3 Minimum clearances - combustion materials (in), MODEL: NOMF155E19A LOCATION UPFLOW DOWNFLOW HORIZONTAL F U RN AC E 1 2 2 SUPPLY PLENUM WITHIN 6 FT OF FURNACE 1 2 1 BACK F U RN AC E 0 1 0 TOP FURNACE 2 2 2 2 2 3 0 **0 **0 4 4 4 9 9 9 8 8 24 SIDE APPLICATION OR PLENUM HORIZONTAL BOTTOM FLUE PIPE FURNACE (**COMBUSTIBLE HORIZONTALLY VERTICALLY FRONT WARM AIR DUCT WITHING 6 FT OF FURNACE F U RN AC E FLOOR WITH THE SUBBASE) OR BELOW FLUE PIPE ABOVE FLUE PIPE 17 ModUle : NOMF105D12A PARTS LIST I =] =_._"_e,,] ;.41M/ [e] _ _[I LV_l:!--;.i Heat exchanger B01667 2 Back panel ass'y B01728 3 Back panel insulation B01526-11 4 Left 5 Right back 6 Right 7 Right side panel baffle back baffle [.e,[e]Lv_ I Lv_ I --_ I Er_ INCLUDES PANEL, INSULATION AND BAFFLE INCLUDES PANEL, INSULATION AND BAFFLE AND LABELS B01686-02 baffle B01686-01 side panel ass'y B01885-01 insulation B01645-01 8 Right side 9 Front top panel B01679-01 B01861 INCLUDES PANELAND 10 Front divider panel ass'y B01727 INCLUDES PANEL, 11 Front divider panel insulation B01646 12 Flue 13 Front 14 Recess handle 15 Radiator baffle 16 17 Blow er compartiment Junction box cover 18 Junction box 19 Junction box holder 20 Blow er slides B01681 21 Floor B01687 22 Blower 23 Blow er divider 24 Left side baffle 25 Left side panel ass'y B01885-02 26 Left side panel insulation B01645-02 27 Hi limit 175-20 28 Gasket, flue pipe cover B01214 29 Gasket, burner flange N01Z026 30 Beckett Burner AFG-F3 3t Hexagon 32 Capacitor 33 5 MF capacitor 34 1/3 HP direct ass'y pipe cover access ass'y LATCHES INSULATION B01697 door B40011-06 DOOR, LATCHE AND HANDLE INCLUDED Z99F050 ass'y slides door ass'y plate B01676 INCLUDES BAFFLES B01883 B01684 INCLUDES DOOR AND AND B01683 BOX ONLY INSULATION LABELS B01682 2 REQUIRED support B01680 2 REQUIRED panel B01846 PANEL ONLY B01679-02 F, 1,75" nut 3/8-16NC INCLUDES PANEL, INSULATION AND AND BAFFLE R02R003 B01536-01 zinc holder F07F011 B01024 L011001 drive B01890-01 INCLUDES MOTOR 35A 35B Blower Blower ass'y 10 X 10 B01405-01 Z011004 INCLUDES INCLUDES BLOWER, MOTOR, CAPACITOR BLOWER WHEEL AND HOUSING 36 Blower weel Z01L002 37 Motor mounting, band 38 Motor mounting, leg 39 Screw 40 Washer 41 Nut for motor 42 Bolt for 43 Motor 44 Hi limit 140-20 45 Observation 46 47 F-lectrical insulating barrier Rocker sw itch SPST 10 X 10 for motor for motor motor mount Z01F012 mount motor leg mount leg Z01 F013 3 REQUIRED F03F023 3 REQUIRED F03F010 3 REQUIRED mount band F07J001 mount band F05F015 ass'y B01888 F, 7" door R02R002 ass'y B01842 A00284 L07F003 48 F-lectronic 49 Transformer fan timer 50 Female 5t Male latche 52 Filter rack U frame B01695 53 Filter B01696 54 55 Paper filter 16 x 24 x 1 F-lectrical kit 120/24 R99G002 VAC latche rack LEGS / 40 VA K03040 Z99F003 Z99F038 access Z04F007 B00203 19 DETAIL " ,7, L,O o DETAIL "A" 8 PARTS LIST ModUle : NOMF155E19A 1l]2_"[e_:ltUl [el _ !LIJLVil=!2=• Heat exchanger B01787 2 Back panel ass'y B01877 3 Back panel insulation B0!526-25 4 Left back 5 Right back 6 Right side panel 7 Right side panel 8 Right 9 Front top panel baffle =KO]Lv_ hV_l=l_ i IK INCLUDES PANEL, INSULATION AND BAFFLES INCLUDES PANEL, INSULATION AND BAFFLES AND LABELS B0!806-02 baffle B0!806-01 ass'y B0!875-01 insulation B0!800-01 side baffle B01805 ass'y B01874 INCLUDES PANEL 10 Front divider panel ass'y B01878 INCLUDES PANEL, INSULATION 11 Front divider panel insulation B01853 12 Flue 13 Front INCLUDES PANEL, HANDLE 14 Recess handle 15 Radiator baffle B01751 INCLUDES INSULATION 16 Blow er compartiment B01873 INCLUDES DOOR 17 Junction box cover 18 Junction box 19 Junction box holder 20 B!ow er slides B01681 21 Floor B01804 22 Blow er slides 23 Blower 24 Left side baffle 25 Left side panel ass'y B0!875-02 26 Left side panel insulation B0!800-02 27 Hi limit 175-20 28 Gasket, flue pipe 29 Gasket, burner 30 Beckett burner 31 Hexagon 32 Capacitor pipe cover access ass'y B40014-06 AND LATCHES Z99F050 ass'y door ass'y AND AND BAFFLE LABEL B01684 B01683 plate BOX ONLY B01682 2 REQUIRED support B01794 2 REQUIRED panel B01795 PANEL divider ONLY B01805 F, !.75" INCLUDES PANEL, INSULATION AND BAFFLES R02R005 cover B00205 flange N04Z026 B0!537-01 nut 3/8-16NC zinc holder F07F0! I B01024 33 15 MF capacitor L011005 34 3/4 HP direct L061004 MOTOR B0!406-01 INCLUDES BLOWER, Z011008 INCLUDES WHEEL drive motor 35A Blower 35B Blow er 12 X !0 ass'y 36 B!ow er w eel 12X10 Z01L003 37 Motor mounting, band Z0! F012 38 Motor mounting, leg 39 Screw 40 Washer 41 Nut for motor mount 42 Bolt for motor 43 Motor 44 Hi limit 45 Observation 46 Electrical 47 Rocker 48 Electronic 49 Transformer 50 Female 51 Mate latche 52 Filter rack 53 Filter rack access 54 Paper filter 55 Electrical for motor leg F03F023 3 REQUIRED F03F0!0 3 REQUIRED band F07J001 3 REQUIRED band F05F015 mount mount leg ass'y MOTOR, AND CAPACITOR HOUSING B01889 F, 7" door ONLY Z01 !009 mount for motor 140-20 LATCHES B01747 door mount AND RO2R002 ass'y insulating B01842 barrier A00284 sw itch SPST L07F003 fan timer 120/24 R99GO02 VAC / 40 VA Iatche L01 F003-2 Z99F003 Z99F038 U frame kit (for 20" X 30" filter) (for 20 x 30 x 1 20" X 30" filter) B01809 B01808 Z04F013 B00203 21
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 20 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Thu Apr 05 13:12:23 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools