ICP Package Units(both Units Combined) Manual L0522880

User Manual: ICP ICP Package Units(both units combined) Manual ICP Package Units(both units combined) Owner's Manual, ICP Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 22

DownloadICP  Package Units(both Units Combined) Manual L0522880
Open PDF In BrowserView PDF
Installation
Instructions

Contents
Unit

Dimensions

1. Safety Labeling
2. Safe Installation

............

2-3

/ Signal Words
Requirements

. 4
. 4

3. Locating the Unit ..............
4. Gas Supply and Piping ........

Three Phase 3 to 5 Ton
Direct Drive Blower

5
8

5. Electrical Wiring ..............
6. Ductwork
....................
7. Economizer
..................

11
11
12

8. Start-up

13

Procedures

..........

9. Operation ....................
10. Maintenance
................
11. Rigging

Instructions

14
15
........

20

COMBINATION
UNITS

GASHEAT/ELECTRIC
COOL
Printed in U,S.A.

509

01

1102

02

1/6/04

_ Installation

Instructions

Combination

Units

"B" CHASSIS UNIT DIMENSIONS
COMBINATION GAS/
ELECTRIC UNITS
"B" Chassis

/

(473/8 X 473/8)
,,o,Es
M,UL,M_E,8
A
B
C
D
E
F
G
H
I
J
K
L
M
N
P
Q
R
S

"C."-____"E"B"

82-i/2 828
47-3/8

I

3-1/8

1208

I

_

79

_

I

283

306

_

I

363

_

I

306

11-1/8

I

14-1/4

12

12

/

1203

I

47-3/8

14-1/4I

102
19&25

12-1/8
14-1/4

308
363

4-1/4I

/

/

1-1/2"

_.

_.

_._____________________/////
_
_t
_.
_

_

_/

"_

_
_

_

_

_

/

/

_

2-i/2" :_

I

_ _((_(_(_(_-._)_)_)_) ))))})//
__/

(_

12_1I 4318

_
/_

//

_

/t

"A"

'T'/"
_._'l"_j

_

.i'E'_'_

'D'_" _
//

"H"

-"J
_0_

/

/

I
ELECTRICAL

:,
_7o_

_

__'-._

_

/

#_

lO8

(635)

_

_

_"

363

4
3/4&1

A

POWER

_ co.o_,T_"_"
o,_.)

_
_<._ /
--.._--._._
_ .__
..>___

,_

_>_

(53975)
I
i

J

_""_
L_ 1/2"<12#)PIPE

"L''_
/

_

ROOF CURB
forunitsin
"B"Chassis

_
_

_

_..

_

/_
/._,,_,/_

"_'_'_"

\
\

PA RATg
TO
BLLU8YRAYE
BOY=TOM
# U CT
0 P E N BN G S

LY

(473/8 x 473/8)

A
B
C
D
E
F
G
H
K*

BNCHE8

42-3/4
39-3/4
18
18
3-3/4
42-3/4

MBLLBMETER8

1086
1010
457
457
95
1086

3913/4

E_

//

50901

CURB8

110202

/_....

//

_

////

/
/

_

gNg

ALSO

_

/v

_

10;O

/q_ROOF

"

//

_

AVAILANLE

IN

.././'_2..._
_

__

8"{2Q3)

AND

24"{610)

"-._'_

HN_GHT8

{K

D_MNNS_@N}=

I

I Combination

Units

Installation

Instructions

"C" CHASSIS UNIT DIMENSIONS

2-1/2"

3" (762)

("K" DIM.)
LOW VOLTAGE
1/2" (12.7) CONDUIT
1- 1/2"
"C"

21-1/4"
(539.75)

GAS CONNECTION
11-1/8"
(101.6)

COMBINATION GAS/
ELECTRIC UNITS
"C" Chassis
(473/8 x 73)
_IM.

A
B
C
D
E
F
G
H
]
J
K
L
M
N
P
Q
R
S
T

INCHES

36
47-3/8
73
4-5/8
15
12
18-3/4
18-3/4
12
4
1 &1-1/4
4-1/4
5-1/4
12-1/4
19
15
19
12-1/4
16-7/8

"G"

M_LLIM_T_RS

914
1203
1354
117
361
307
476
476
306
102
25&31
108
133
311
483
381
483
318
429

"R"

,,p,,

UNIT

BASE

TO
DUCT

ILLUSTRATE
OPENINGS

SHOWN

SEPARAT
BOTTOM

ROOF CURB
for
"C" Chassis
(473/8 x 73)
DIM.

A
B
C
D
E
F
G
H
I
J
K*

_NCHE8

MILLIMETER8

67-3/4
64 - 3/4
23
23
2-1/2
42-3/4
39 - 3/4
23
12
12
14

1721
1645
584
584
64
1086
1010
584
305
305
356

_ROOF

"F\

OURB8

ARE

AL80

AVAILABLE

IN

8"(208)

AND

Z4"(610)

HEIGHT8

(K

DIMENSION).

80-t0-11

50901

110202

E_]

I Installation Instructions

Combination Units

I

1. Safety Labeling and Signal Words
Danger, Warning

and

CAUTION - Hazards or unsafe practices which COULD result in
minor personal injury or product or property damage.

Caution

The signal words DANGER,
WARNING
and CAUTION
are used
to identify levels of hazard seriousness.
The signal word DANGER is only used on product labels to signify an immediate
hazard. The signal words WARNING
and CAUTION
will be used on
product labels and throughout
this manual and other manuals that
may apply to the product.

Signal

Words

in Manuals

The signal word WARNING is used throughout this manual in the
following manner:

Signal Words
DANGER - immediate hazards which WILL result in severe personal injury or death.
WARNING - Hazards or unsafe practices which COULD result in
severe personal injury or death.

2. Safe Installation

The signal word CAUTION
following manner:

is used throughout this manual in the

CAUTION

Requirements
NOTE: It is the personal responsibility and obligation of the customer to contact a qualified installer to ensure that the installation
is adequate and conforms to governing codes and ordinances.

Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes or, in the absence of
local codes, with the ANSI Z223.1-1990 National Fuel
Gas
Code
and the
National
Electrical
Code

It is recommended that a qualified service technician check
the heat exchanger integrity every two (2) years, after the first
four (4) years of operation.

NFPA70-1990 or in Canada the National Standard CAN/
CGA B149.1 and CSA C.22.1 - Canadian Electrical
Code Part 1.

Check Pre-existing
Furnace

The information

contained

in this manual is intended

for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools
and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in furnace malfunction, property
damage, personal injury and/or death.

CAUTION

Installation MUST conform to the most current version of
the following standards or a superseding

standard.

In the USA:
•. ANSI Z223.1-1990
•

National Fue! Gas Code

pliances
and they will not vent properly.
The venting
MUST be checked according
to the following
procedure.

National Electrical Code NFPA70-1990

NOTE: The following steps shall be followed with each appliance
remaining connected tothe common venting system placed in operation, while the other appliances remaining connected to the
common venting system are not in operation.
Seal any unused openings in the common venting system.
Visually inspect the venting system for proper size and horizontal pitch to ensure there is no blockage
or restriction,
leakage, corrosion or other deficiencies
an unsafe condition.
insofar

as is practical,

and other

•

National Standard CAN/CGA B149.1

•

CSA C.22.1 - Canadian Electrical Code Part 1.

•

Do NOT use this furnace as a construction

•

Use only the type of gas approved for this furnace (see rating plate).

•

Do NOT use open flame to test for gas leak.

•

Seal supply and return air ducts.

heater.

spaces

110202

close

which

could cause

all doors and windows

and all

of the building

Turn on clothes dryers and any appliance not connected to
the common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do NOT operate a summer
exhaust fan. Close fireplace dampers.
Follow the lighting instructions, Place the appliance being
inspected in operation. Adjust thermostat so appliance wil!
operate continuously.
Test for spillage

50901

system

doors between the space in which the appliances
remaining connected
to the common venting system are located

In Canada:

E_I

Vent From Old

If the installation
of the combination
unit involves removing an existing furnace
from a common
vent with other appliances,
the
venting system will probably be too large for the remaining
ap-

1.
•

Common

at the draft hood relief opening

utes of main burner

operation.

after 5 min-

Use the flame of a match or

I Combination

Units

Installation

candle. (see FIGURE 1). Flame or smoke should drawtowards vent pipe.

After it has been determined
connected

to the common

when

tested

fans,

fireplace

pliance

as outlined,
dampers

venting

the common

during
MUST

in Appendix

Z223.1,

vents

exhaust

gas-burning

Vent Check

WaterHeaterx

ap-

[

Draft Hood

I

I

_ v--Match

I

of use.

system

tables

properly

1

Vent Pipe--___
Typical Gas
_/

remaining

windows,

any other

is observed

ANSI

system

doors,

condition

venting

ing the appropriate
Fuel Gas Code,

venting
return
and

to their previous

If improper
tests,

that each appliance

FIGURE

Instructions

j

any of the above
be corrected

us-

G in the National

1990.

NOTE: If flame pulls towards draft hood, this indicates adequate
venting.

3. Locating the Unit
The unit is designed

for outdoor

installed

on a concrete

mounting

rooftop

with an adequate

platform

installation

only. The unit may be

base at ground

level,

or if using as a downflow

or on a

I

FIGURE 2

Access Panels

model,

with a roof curb.

CAUTION

Do NOT operate unit in a corrosive atmosphere

containing

chlorine, fluorine, or any other corrosive chemicals.

Do NOT install the unit in a location
from the condenser

Access

to recirculate

that will permit

discharged

to the condenser

inlet.

air

Panels

Clearances
See FIGU RE 2 below for a general
cess

view of unit and location

of ac-

panels.

The location MUST allow for minimum clearances and should not
be adjacent to a patio or other area where the unit's operating
sound level might be objectionable. The combustion air inlet
openings MUST not be obstructed (see FIGURE 5). In addition,
local codes MUST be observed.
Clearances
MUST be maintained
from adjacent structures to provide adequate fire protection,
adequate combustion
air, and room

Carbon

monoxide poisoning hazard.

Keep blower door closed.
Failure to keep blower door closed can result in bodily
injury and/or death.

for service

personnel.

NOTE: Filter racks need a 26" minimum clearance at front of unit
for removal of filters. See chart below if unit is going to be placed
near combustible construction or materials.
While minimum
clearances
are acceptable
for safety reasons,
they may not allow adequate
air circulation
around the unit for
proper operation in the cooling mode. Whenever
possible, it is desirable to allow additional
clearance,
especially
around the condenser inlet and discharge
openings.

50901

110202

E_]

I Installation

Instructions

FIGURE 3

Combination

I

The unit MUST be situated to provide safe access for servicing.

(C Chassisand
Shown)
Minimum Clearances
Access Panels

sk>_r _

Units

Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to support unit weight.

Pmww

Position platform separate from building foundation.

Bcm.+,m,:

Install
above

/+++++z
a_'

in well-drained
grade level.

area,

with top

surface

of platform

Platform MUST be high enough to allow for proper condensate trap installation and drainage. See Figure 9 and associated text for more information
about condensate
drainage.

Rooftop
30"

Rooftop platform requirements:

80-00-01A

Minimum

Clearances

Furnace Plenum

to Combustible

Duct Side ................
Condenser

Inlet Side

Blower Service (Rear)

...............................

30"

..............................

30"
......

Clearance between 3 Ft. Overhang and Top of Unit .....
Base (Wood or Class A, B or C

roof covering material)

...............................

•

Support for the unit MUST be level and strong enough to
carry unit weight. The support may consist of a platform or a
combination of platform and roof beams or curb.
The platform may be constructed of pressure treated wood
and may be covered with Class A, B or C roof covering.

30"
30"

The unit MUST be situated to provide safe access for servicing.
The existing roof structure MUST be adequate to support
the weight of the unit or the roof MUST be reinforced.
Check the weight of the unit in relation to the roof structure
and local building codes or ordinances and reinforce roof
structure if necessary. See FIGURE 25 on the back cover
of this manual for unit weights and corner weights.

2"

2" (6" on large chassis models)

Control Service Side (Front Combustion Air Inlet)

Combustible

•

Construction

....................................

Installation

•

Platform MUST allow for proper condensate trap installation and drainage. See FIGURE 6 and associated text for
more information about condensate drainage.

0"
NOTE: Cardboard covers on downflow supply and return duct
openings MUST be removed before starting unit.

Installation

Hoisting
CAUTION
Unit will NOT operate properly
to rear and side to side.

unless it is installed

level front

The slope MUST NOT be greater than 1/8" per foot (10mm per
meter). For side to side leveling, the control box side MUST
always be lower.

Ground Level Installation
Ground level platform requirements:

E_

50901

110202

NOTE: All access panels MUST be secured in place before hoisting.
The unit should be hoisted with two lifting slings. Attach the slings
to rigging shackles that have been hooked through holes in the
base rail.
Two spreader bars MUST be placed on top of the unit to protect
the unit from damage from the pressure exerted by the slings.
Make sure that all equipment is adequate to handle the weight of
the unit and that the slings will not allow the unit to shift.
Refer to FIGURE 25 on the back cover of this manual for illustrated rigging instructions and weight chart.

I Combination

Downflow

Units

Installation

Conversion
FIGURE 5

These units are adaptable
to downflow
flow use, follow these steps:
1.

Instructions

use. To convert

J

Heating Vent Assembly

to down-

Remove the blockoff plates found in the return air compartment and the supply air compartment.
See FIGURE 4 for
plate location.

Flue Support
(Shipped moume(:lto unit)
Flue Cover
/

NOTE: Blockoff plate in the supply air compartment only contains
one screw. If reinstalling plate, back part of plate MUST fit into
mating dimples on flange. To reinstall, slant plate into dimples,
then put plate into position and fasten with screw.
2.

Install the removed plates on the horizontal return and supply air openings.

3.

Install roof curb on your building. Be sure to follow all directions included with curb and all applicable building codes.

4.

Install

unit on the appropriate

roof curb.

NOTE: It is the installer's
personal responsibility
to follow all local
codes and ordinances
and instructions
contained
herein, as well
as instructions
included with accessory items when installing unit.

Blockoff

Plate (Return Air Compartment)

Condensate

Drain

A3/4" O.D. condensate
drain connection
is located at the front end
of the unit. A 3/4" drain line MUST be installed if required by local
codes or location of unit, and run to an open drain or other suitable
disposal point. A condensate
trap MUST be installed
as near
the unit as possible
for proper
drainage.

Condensate
Condensate
FIGURE 6,

Trap
trap MUST

FIGURE

6

]

have proper

Condensate

height

and fall as shown

Trap
25-1/2 ("B" Chassis)
("C" Chassis)

3/4" (19.1mm)
Threaded Female
PVC Fitting

_(25.4mm)

)

4-1/2

Heating Vent Assembly

The flue cover is packed with screws in the return air compartment. Refer to FIGURE 5 and assemble
as shown.

2" (50.8mm)

\
3/4" (19.1mm)
Drain Line

'

CAUTION

DO

NOT

SEMBLY

OPERATE

THE

UNIT

WITHOUT

THE

VENT

AS-

* Condensate

trap MUST be installed.

INSTALLED

50901

110202

[_]

in

I

Installation

Combination

Instructions

Units

I

4. Gas Supply and Piping
Because there are many types of liquefied petroleum
(LP) gases,
the term LP as used in this manual refers to propane gas. If you
intend to use any type of LP gas, proper precautions
MUST be
used in the handling, piping, and use ofsuch gas. NOTE: In Canada, LP installations
MUST be performed
by licensed LP installers.
The Rating Plate located on the side panel on the unit contains the
model number, type of gas and gas input rating, and other important information.

Gas Piping
The gas supply line MUST be of adequate
size to handle the Btu/
hr requirements
and length of the run for the unit being installed.
Determine
the minimum pipe size for natural gas from the table in
Figure 8 & Figure 9. Base the length of the run from the gas meter
or source to the unit.
Gas

Pipe

Size

Btu ratings of all other gas appliances
MUST be considered
for
sizing of main gas line. Check gas line to installation
for compliance with local codes or, in the absence of local codes, with the
National Fuel Gas Code ANSI Z223.1-1990
and in Canada the

Fire and/or explosion hazard.

National

Make certain the unit is equipped to operate on the type
of gas available. Models designated as natural gas are
to be used with natural gas only. Models designated for
use with liquefied petroleum (LP) gas are shipped with
orifices sized for commercially pure propane gas. They
MUST not be used with butane or a mixture of butane
and propane unless properly sized orifices are installed
by a licensed LP installer.

Standard

FIGURE 8

CAN/CGA

1.

2.

3.

minimum gas supply pressure to fall below
Doing so will decrease input to furnace. Re7 for gas supply pressures.

Gas input MUST
plate.

NOT exceed

rated input shown

PipeLength
(Includes
Fittings)

Btu/hr (in thousands)
3/4"

to exceed

the maximum

(1120 Pa)

190

350

730

1,100

2,100

130

245

500

760

1,450

60'

105

195

400

610

1,150

LP GAS

3/4"

1"

20'

189

393

732

1,496

2,299

40'

129

267

504

1,039

1,559

60'

103

217

409

834

1,275

7" W.C. (1740 Pa)

13"W.0.

(3230 Pa)

Manifold
Pressure

3.5" W.C. (870 Pa)

11/4"

11/2"

Gas Pipe Size, LengthandBtu/hr Capacityfor Schedule 40 Iron Pipe(English)

kW**

6.1m

56

1"
103

12.2m

38

18.3m

31

Fittings)

3/4"

11" W.C. (2740 Pa)

11" W.C. (2740 Pa)

13"W.C.

214

322

2"
615

72

147

223

425

57

117

179

337

11/4"

11/2"

LP GAS
Pipe Length
(includes
Fittings)

kW**
1/2"

3/4"

1"

6.1m

55

115

215

438

574

12.2m

38

78

148

305

457

18.3m

30

64

120

244

374

**kW (Kilowatts)

Inlet
Pressure

11/4"

is the metric equivalent

11/2"

of Btu/hr.

(3230 Pa)

10" W.C. (2490 Pa)

FIGURE 10
Gas Type
Natural

Orifice

Specific

Gravity

Sizes
Btu/ft 3 (k J/L)

Pilot Orifice

0.6

1000

.018#

1.53

2500

.012#

Pressures

Manifold pressures are covered in the startup procedure section.
Refer to Chapter 8, Start-Up Procedures on Page 13.

E_I

1/2"

PipeLength
(Includes

Maximum

Manifold

Btu/hr(inthousands)

LP Gas

Recom.
Inlet
Pressure

2"

NATURAL GAS

Minimum
4.5"W.C.

11/2"

40'

limits as

Gas Pressures

Inlet
Pressure

11/4"

on rating

NOTE: If gas supply pressures are not correct, contact your gas
supplier.

Natural Gas

1"

20'

FIGURE 9

Do NOT allow pressures
listed in FIGURE 7.

editions.

NATURAL GAS

PipeLength
(Includes
Fittings)

Do NOT allow
the minimums.
fer to FIGURE

current

Gas Pipe Size, LengthandBtu/hr Capacityfor Schedule 40 Iron Pipe (English)

Failure to follow this warning can result in property
damage, personal injury, and/or death.

Gas Pressures

B149.1

50901

110202

Propane
#Adjust

pilot flame as needed

Sizes

I Combination

Unite

Installation

TABLE 1: Equivalent
Orifice Sizes at High Altitudes
(Includes 4% input reduction for each 1,000 ft.

6.

Disconnect

the pilot tubing

7.

Remove the four screws
ifold brackets.

8.

Carefully

Remove the orifices
or socket wrench.

Instructions

from the gas valve.

holding

the manifold

to the man-

Natural Gas ManifoldOrifice Size Requiredby Elevation
BTU
INPUT

0'2000'

2000'
4000'

4500'
5000'

6000'

7000'

8000'

9000'

10000'

40.000to
60,00

44

45

46

47

47

48

48

49

9.

90,000to
150,000

43

44

45

45

46

47

47

48

10. Check to be sure that the size of each orifice is correct for
the Btu input desired.

remove

the manifold

with the gas valve attached.

from the manifold

with a 7/16" box end

LP Gas ManifoldOrifice Size Required by Elevation
BTU
INPUT

0'2000'

2000'
4000'

4500'
5000'

6000'

7000'

8000'

9000'

10000'

40.000to
60,000

55

56

56

56

56

56

56

57

90,000to
150,000

54

55

55

55

55

56

56

56

FIGURE ii

I

__

Manifold/Orifice

.11Ak _

_,,,,",_J
* 2-1/2
** 3-1/2

Measurement

Measure 11/16"
(27mm) from face
of orifice to back
edg I of manifold

& 3 Ton with 3 burners.
& 4 ton with 4 burners.

Orifices
Orifice

Sizes

Orifice sizes MUST be matched to the heating value of the gas
(see FIGURE 10 and Table 1). Check with your gas supplier and
the National Fuel Gas Code ANSI Z223.1 -1 990 and in Canada
the National

Standard

CAN/CGA

B149.1;

current

11.

Make sure that the orifices go in straight
right angle (90 °) to the manifold
pipe.

edition.

NOTE: An LP Conversion
Kit, which contains pilot and burner orifices, a two-stage
LP gas valve and an instruction
manual, MUST
be used for conversion
to LP gas.

so that they form a

Tighten the orifices so that there is a 11/16" (27mm) distance between the faces of the orifices to the back of the
manifold

NOTE: For elevations
above 2000 feet (610 meters), the Btu input
rating MUST be reduced by 4% for each 1000 feet (305 meters)
,
3
above sea level, unless the gas supplier s Btu/ft content has already been adjusted for altitude. See Table I for the proper orifice
sizes.

pipe.

Measure the distance with a set of calipers,
have a calipers,
you can use an adjustable
measure
between the face of the jaws.
12.

Changing

install the correct orifices. Gauge the size of the orifices
with a new twist drill bit of the correct size.

Reassemble

in reverse

if you do not
wrench and

order.

Orifices

Piping at Unit
Electrical shock, fire and/or explosion hazard.

Connections

Shut off electric power at unit disconnect or service panel and shut off gas at manual shut off
valve before beginning the following procedure.

NOTE: Refer to FIGU RE 13 for the general layout at the furnace.
The rules listed apply to natural and LP gas pipe installations.

Changing orifices requires a qualified
technician.

service

Failure to follow this warning can result in property damage, personal injury, and/or death.

1.

Shut OFF gas at manual shut off valve.

2.

Shut OFF electric power at unit disconnect or service panel.

3.

Remove the burner access pane!.

4.

Disconnect the gas line from the gas valve.

5.

Disconnect the wires from the gas valve.

1.

If installation
is for LP gas, have LP gas installer use TWOSTAGE
REGULATION
and make all connections
from
storage

2.

tank to unit.

Use black iron or steel pipe and fittings or other pipe approved by local code.

NOTE: If a flexible gas connector is used, it MUST be acceptable
to local authority. Connector MUST NOT be used inside the furnace or be secured or supported bythe furnace or ductwork. Connectors MUST comply with one of the following standards or a
superseding standard:
• ANSI Z21.24a-1983, Metal Connectors for
Gas Appliances.
• ANSI Z21.45b-1983, Flexible Connectors of
Other Than All-Metal Construction for Gas
Appliances.

50901

110202

E_]

I Installation

Instructions

Combination

Units

I

Leak Check
Fire and/or explosion

1.

Gas pressure
MUST NOT exceed 1/2 PSIG
(3450 Pa).
Checking
gas piping above 1/2 PSIG (3450 Pa) requires
the gas valve and manual shutoff valve to be disconnected
during testing.

2.

When checking gas piping to furnace, shut OFF manual
shutoff valve to furnace.

3.

Test all pipes

hazard.

Gas connector MUST be properly installed and can NOT be
used inside the furnace.
Failure to do so can result in property damage, bodily injury or death.

3.

Use pipe joint compound on external (male) threads
Joint compound
MUST be resistant to any chemical
of LP gases (FIGURE 12).

ONLY.
action

for leaks.

Fire and/or explosion hazard.

4.

Use ground joint unions and install a drip leg no less than 3
inches (76 mm) long to trap dirt and moisture before it can
enter gas valve.

Never exceed specified pressures. Higher pressures
may damage the gas valve. Such damage may result in
overfiring and possible heat exchanger failure.

5.

Use a flat jawed wrench on gas valve when making connections to prevent gas valve from turning. Do NOT use a
pipe wrench on the gas valve body.

Do NOT use a match or open flame to test for leaks.

Failure to follow this warning can result in property
damage, personal injury, and/or death.

CAUTION
Overtightening
assembly may cause damage to the gas
valve and/or wiring and may misalign the burners.
6.

Provide

a 1/8 inch (3mm)

National

Pipe Thread

for test gauge connection
immediately
supply connection
to the furnace.

FIGURE i2

J Proper

upstream

(NPT)

of the gas

Use moderate
amount of compound

7.

pipe right

Install a manual

LP Connection
1.

Leave 2 end
threads bare

length

shutoffvalve

and tighten

all joints securely.

Requirements

Have a licensed LP gas dealer make all connections at
storage tank and check all connections from tank to furnace.
If copper tubing is used, it MUST comply with limitation set
in National Fuel Gas Code or in Canada the National Standard CAN/CGA

3.

E_

Two-stage

50901

B149.1;

regulation

110202

Apply soap suds (or a liquid detergent)
Bubbles forming indicate a leak.

5.

Make sure pilot tube
leakage.

6.

Correct

plug

and

even the smallest

burner

orifices

to each joint.

are checked

leak at once.

Piping Practice

Control

Thread

4.

current

edition..

of LP gas is required.

FIGURE !3

1

Piping at Unit for Natural Gas

for

I Combination

Units

Installation

Instructions

5. Electrical Wiring
The location of the thermostat
eration of the unit. FOLLOW
WITH
THE
MOUNTING,

Electrical shock hazard.

THERMOSTAT
AND WIRING.

Set the thermostat
heat anticipator
mostat instructions.

ANSI/NFPA-No.
70-1990
or current edition. Provide line voltage
power supply from a separate protected
circuit with a disconnect
switch (when required) located within sight of the unit. Supplyvoltage, amperage,
wire, fuse and disconnect
switch sizes MUST
conform with specifications
in the Technical Support Manual and
with unit rating plate.

All exposed wiring or connections MUST be made with weatherproof cable or wire unless installed in conduit. Wiring MUST be
protected from possible mechanical damage.
Connections
for line voltage are made in the unit control box. Low
voltage connections
are made outside the control box. For access, remove the burner access panel and the control box cover.
See FIGURE 2.

Low Voltage Wiring
Low voltage wiring connections for the thermostat are made at the
24Vterminal board outside the control box. Refer to the wiring diagram for the applicable model and the instructions included with
the thermostat.

attempt

to use a thermostat

designed

use. Such thermostats

to. 58 in accordance

Do NOT complete
line voltage connections
nently grounded. All line voltage connections
nection MUST be made with copper wire.

with ther-

for

will NOT

box. For
box cov-

until unit is permaand the ground con-

Ground Connections
A ground lug is installed in the control box for the ground connection. Use a copper conductor of the appropriate
size from the unit
to a grounded
connection
in the electrical
service panel.

Line Connections
Complete the line service connections
to the contactor
'L' terminals inside the control box. Refer to applicable wiring diagram in
Technical Support Manual. Check all screw terminals
to ensure
they are tight.

Field Installed Equipment
Wiring to be done in the field between the
tached to the unit, or between
separate
installed and located, shall conform with
tions for type T wire and shall be installed
instructions
applicable
to such devices.

Final Electrical

Thermostat
heat or heat pump
the unit properly,

LOCATION,

Connections
for line voltage are made in the unit control
access, remove the burner access panel and the control
er.

NOTE: All electrical work MUST conform with the requirements
of
local codes and ordinances
and the National
Electrical
Code

Do NOT

CORRECT

Line Voltage Wiring

Failure to follow this warning can result in property
damage, personal injury, and/or death.

NOTE:

FOR

Heat Anticipator

Disconnect power at fuse box or service panel before
making any electrical connections.
Unit MUST be grounded to electrical service panel.

electric
control

has an important
effect on the opTHE INSTRUCTIONS
INCLUDED

unit and devices not atdevices which are field
the temperature
limitawith the manufacturer's

Check

Make a final wiring check to be sure system is correctly wired. Inspect field installed wiring and the routing to ensure that rubbing or
chafing due to vibration
will not occur.

6. Ductwork
Maximum
recommended
velocity in trunk ducts is 1000 feet per
minute. Velocity in branches should not exceed 800 feet per minute.

NOTE: Ductwork sizing affects temperature rise and cooling temperature differential. Be sure to properly size ductwork to the capacity and airflow characteristics of your unit. Failure to do so can
affect limit controls, compressors, motors, and other components
and will lead to premature failure of components. This will also
adversely affect day to day unit performance. Refer to rating plate
and Temperature Rise Check section in this manual.

tected against damage.
Caulking
adequate to provide a permanent

and flashings,
or other means
weather seal, should be used.

Ductwork installed in attics or other areas exposed to outside temperatures should be installed with a minimum
of 2" Fiberglas insulation and have an indoor type vapor barrier.

Ductwork

Connections

The use of flexible, non-combustible
connectors between main
trunk ducts and supply and return air plenums is recommended to
minimize vibration transmission.

Ductwork Insulation
Ductwork installed outdoors should have a minimum of 2" Fiberglas insulation and a weatherproof vapor barrier. It should be pro-

NOTE: Connect supply and return air plenums to unit in a manner
that will allow the top of the unit to be removed without removing
plenums. Plenums MUST be individually sealed to unit casing
with ducts terminating inside structure.

50901

110202

_ Installation

Instructions

Combination

Filters

cessories

All return air, including
economizer
air and outside damper air,
MUST pass through a filter before entering the evaporator.
An
electronic
air cleaner
or other accessible
filter arrangement
MUST be installed in the return air ductwork.
This can ONLY be
done when the internal filters are removed and NO outdoor air ac-

recommended

filter

based on a velocity of 300 ft/min for disposable
min for high velocity filters (washable).

are

used.

Mimimum

filters

Units

I

areas

are

and 500 ft/

CAUTION
DO NOT OPERATE THE UNIT WITHOUT A FILTER.

7. Economizer
The purpose

of an economizer

is to:

•

Provide
cooling

cool outside air to the conditioned
space during the
cycle to minimize the use of the compressors.

•

Bring outside air into the conditioned
mum fresh air requirements
whenever
er is running.

Downflow Economizer

space to meet minithe circulation
blow-

I

The economizer
is controlled
by a logic module which field connects to the unit controls through a plug harness. The logic module also controls the compressor
staging based on the thermostat
input.
The minimum
opening
position of the fresh air dampers
is field
settable. It is set on the logic module of modulating
economizers
or on the actuator motor of three-position
economizers.
The enthalpy
sensor is factory installed on the fresh air dampers
of the economizer.
The enthalpy change-over
point is adjustable
on the logic module.
A discharge
air sensor is field installed in the blower inlet. The discharge air sensor keeps the discharge
air above 56°F (13.3°C).
A positive pressure is created when the fresh air dampers open
and the return dampers close. This pressure
must be vented or
the air will not circulate properly. This is the function of the barometric relief dampers. A positive pressure forces the passive exhaust dampers
to swing open.
The fresh air dampers open to the minimum
whenever
the circulation
blower is ON.

position

for outside

air

When the thermostat
is in the FAN AUTO position, the fresh air
dampers will close completely
whenever
heating or cooling is not
called for.
When
1.

the thermostat

If Using
2.

is in the FAN ON position:

The fresh air dampers
fresh air.
a 2-Stage

will open to the minimum

On a call for cooling, if the economizer
outdoor air sensor
determines
that the outside air is cool enough (and in the
case of an enthalpy
sensor, dry enough),
the fresh air
dampers will modulate open and the return air dampers wil!
modulate
closed.
space

lected temperature,
second
module

stage cooling
at low voltage

ergizes

the Y1 anti-cycle

If Using

The economizer
has two sets of dampers that are mechanically
linked together. The fresh air dampers regulate the intake of outside air and the return air dampers regulate the flow of return air
(see FIGURE 14). When the fresh air dampers
modulate
open,
the linkage causes the return air dampers to modulate closed.

E_

50901

110202

a Single-

Stage

is not being maintained

the thermostat

gizes the condenser
assist the economizer.

of Operation

for

Thermostat

If the conditioned

Theory

position

at the se-

will make Y2 and call for

by energizing
the economizer
logic
terminal board terminal Y4. This endelay

fan and

and contactor
compressor

which

ener-

for cooling

to

Thermostat

When using a single stage thermostat,
all steps as outlined
will be followed with the exception
of the following:

above

The compressor
will only be energized
when the outside air
reaches a temperature
above the preset limit of the economizer.
When ambient conditions
are not suitable for economizer
operation, ONLY the compressor
will run, and the economizer
will NOT
be energized.

I Combination

Units

8. Start-up

Installation

Instructions

Procedures
FIGURE 15

Manifold

Pressure Settings

Fire and/or explosion hazard.

Gas Type

Do NOT attempt to light the pilot or burner with a match
or flame of any kind.

Natural

3.5 Inches Water Column (870 Pa)

Propane

10 Inches Water Column (2490 Pa)

Failure to follow this warning can result in property
damage, personal injury, and/or death.

2.

Manifold Pressure

Turn gas ON and remove adjustment
screw cover on gas
valve. Turn counterclockwise
to decrease
pressure
and
clockwise
to increase.

NOTE: Adjustment screw cover MUST be placed on gas valve
before reading manifold pressure and operating furnace.
3.

Check Before Starting
Check that the blower motor speed terminal block isset for
the correct heating and cooling speeds. Refer to the unit
wiring diagram and tech sheet label and/or Technicallnformation Manual.

2.

Check to
installed.

3.

Replace

see

that

all service

clean,

access

properly

sized

air filters

are

Set pressure to value shown in FIGURE 15, _+0.07kPa (0.3
inches) water column. Pressure is also listed on furnace
rating plate. In NO case should final manifold pressure vary
more than _+0.07kPa (0.3 inches) water column.

Circulating

Air Blower

Check the unit's operation as outlined inthe following instructions.
If any unusual sparking, odors or unusual noises are encountered, shut off electric power immediately. Recheck for wiring errors, or obstructions in or near blower motors.
NOTE: If spark wire is removed or replaced, always be certain to
remount wire on support bracket standoff.
1. Set thermostat Heat-Cool selector to OFF.

panels.

Reverse Rotation (Scroll
Compressors Only)
Three phase scroll compressor
equipped
units CAN
verse if improperly
wired. If the compressor
makes an
loud noise, or if high and low side pressures
are nearly
this indicates reverse rotation. To correct,
reverse any
at line voltage connections
ONLY. Do NOT rewire any
side the unit to attempt correction
of reverse rotation.

run in reunusually
identical,
two wires
circuits in-

Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners operating.

2.

Set thermostat

fan switch

3.

Turn electric

power

4.

Turn manual

gas valve

5.

Turn gas control

6.

Set thermostat
fan switch to ON. After 30 seconds,
culating air blower should come ON.

7.

Reset

thermostat

the circulating
running.

to AUTO.

ON. Nothing

valve

start

running.

ON.
ON.

fan switch

air blower

should

to AUTO.

should

After

the cir-

30 seconds,

go OFF. Nothing

should

be

Heating
Fire or explosion

Turn OFF gas at shut off before connecting
nometer.

U-tube

Adjust thermostat
setting above room temperature
and set
thermostat
selector to HEAT. The combustion
air blower
should come ON.

2.

The ignitor should

ma-

Do NOT adjust manifold pressure more than -+0.3 inches
water column to obtain rated input.
Failure to properly set input pressure can result in property damage, personal injury and/or death.

1.

1.
hazard.

With gas OFF, Connect
U-Tube
manometer
to tapped
opening on gas valve. Use manometer
with a 0 to 12 inches
water column range.

begin to glow and pilot flame should

light.

NOTE: On a call for heat the ignitor and pilot valve will remain energized until a flame is detected by the flame sensor.
It may take
several minutes to purge the air out of the gas lines at initial startup of the unit.
3.

Once the flame sensor detects that a flame is present, the
hot surface ignitor will de-energize
and the main burners
wil! light from the pilot.

4.

30 seconds after the burners light, the circulating blower
shuld begin to run.

50901

110202

_[]

S Installation

Instructions

Temperature

Combination

The temperature
rise must be within
tions marked on the unit rating plate.

4.

Open ALL registers and duct dampers. Operate unit AT
LEAST 15 minutes before taking readings.
If the correct amount of temperature rise is not obtained when operating on the recommended blower speed, it may be necessary
to change the blower speed. A faster blower speed will decrease
the temperature rise. A slower blower speed wil! increase the temperature rise.
NOTE: The blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate.

Adjust
ture.

Remove
relight

air restrictions.
after a cool down

Pilot
period

and

main

burners

should

of a few minutes.

setting

The circulating
air blower
100, 140 or 180 seconds.

5.

Set thermostat

below

room tempera-

air blower should

should continue
to run for 60,
This time is adjustable.

Heat-Cool

selector

to OFE

Cooling
1.

Turn electric power OFF

2.

Set thermostat

3.

Adjust thermostat

4.

Heat-Cool select to COOL.
setting to below room temperature.

Turn power ON, for approximately
one minute,
During power application
check the following:
a.

Contactor

b.
c.

Compressor
Condenser

- ON
fan motor

- ON

d.

Circulating

Air Blower

- ON after a 30

After 15 minutes of operation check the limit control
function by blocking the return air grille(s),
After several minutes the main burners and pilot should go
OFF The circulating air blower should continue to run.

the thermostat

Pilot and main burners and combustion
go OFF

the specifica-

To check the temperature rise through the unit, place
thermometers in the supply and return air ducts as
close to the unit as possible,

3,

I

NOTE: The maximum outlet air setting for all models is 175°F.

Rise Check

NOTE: Air temperature rise is the temperature difference between supply and return air. With a properly designed distribution
system, the proper amount of temperature rise will normally be
obtained when the unit is operating at rated input with the recommended blower speed.
2.

Units

second

- Contacts

then

OFF

Closing

delay

Turn power OFF, check the following:
a. Contactor contacts opening.
b. Compressor - OFF
c. Condenser fan motor - OFF
d. Circulating
delay.

blower - OFF after a 30 second

9. Operation

Electrical shock hazard.

event of a power interruption. This feature is to allow pressure
equalization throughout the system and to prevent possible reverse rotation of the scroll compressor. Three phase units do not
require this device.

High and Low Pressure Switches (Not All Models)
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
Failure to follow this warning can result in property
damage, personal injury, and/or death.

Controls

and Features

High and low pressure switches are provided on these units which
will shut down the system when high pressures exceed 420 psi
and low system pressures fall below 27 psi. The switches automatically reset after a fault. They are accessed through the compressor compartment access panel.

Fan Cycle Pressure Switch Port (optional)
If your unit will be operated in low ambient conditions
(below 40 °
F) and you elect to install a low ambient fan cycle control, you can
find the low ambient pressure
port located on the discharge
line
just inside the compressor
compartment
panel opening.

Cooling Time Delay Relay (Not All Models)

Freeze Protection Thermostat (Not All Models)

A cooling time delay relay is used on the evaporator blower motor
to increase efficiency (SEER). On a call for cooling, the blower
motor starting is delayed for 30 seconds. Also, after the thermostat is satisfied, the blower motor continues to run for 30 seconds
after the condenser fan motor and compressor have shut off.

The freeze protection thermostat
is located on the evaporator
coil
bends on the burner side ofthe unit. It is designed to shut down the
cooling circuit if the evaporator
coil temperaturefalls
below 35 ° R

Scroll Anti-cycle

A liquid line filter drier is located inside the compressor
compartment access panel opening. Be certain to replace filter driers with
the correct size and type as found in the Technical Data Sheets
available from your dealer.

Timer (Not All Models)

Single phase scroll compressor equipped units are equipped with
an anti-cycle device which delays start of the compressor in the

E_I

50901

110202

Filter Drier

I Combination Units

Installation

Economizer Plug
A pre-wired economizer plug is located just inside the return air
opening. See Page 12 for more information about the economizer.

Starting

the Unit After Shutdown

Heating
1.

Set thermostat to OFF.

2.

Remove burner compartment
access panel. Locate gas
control valve knob (NO TAG), and turn to OFF. Wait 5 minutes.

Instructions

may run continuously for several hours or longer on the initial run
because of residual heat and moisture in the house. This is normal for any air conditioning system.

CAUTION
Do not operate on cooling when outdoor temperature is below 40°F. This is necessary to prevent possible damage to
the compressor.

Turning The Unit Off

3.

Turn gas control knob to ON. (Honeywell valve must be depressed
to turn). Replace
burner
compartment
access
panel. Turn manual gas valve to supply pipe ON.

4.

Turn electric

5.

Set thermostat to HEAT and to desired temperature. Unit
will come on and operate automatically under control of the
thermostat, Never attempt to light the pilot manually.

power

1.

Set the thermostat switch and OFF fan switch to AUTO. To
restart, set to HEAT or COOL and temperature desired.

2.

To shut the unit down completely, turn electric power OFF
Turn manual gas valve off.

CAUTION

ON.

To prevent heat exchanger damage, wait at least 2 minutes
after blower stops before shutting off power to unit.

NOTE: If the furnace overheats or fails to shut off, turn OFF the
manual gas valve for the furnace then wait at least 2 minutes before turning off electric power.

Thermostat

Fan Switch Operation

Fire and/or explosion hazard
Do not operate the unit on heating (except during service checks) unless all access panels are securely fastened in place. Abnormal and possibly hazardous
burner operation could result.
Failure to follow this warning can result in property
damage, personal injury, and/or death.

With the selector switch
er will run continuously
used for cooling. In the
during each heating or

CAUTION
Some units use a lower blower speed for cooling than for
heating. Do NOT position selector switch to ON for continuous operation during heating cycle if the cooling blower
speed is lower than the heating speed. Blower speeds for
each model are listed on the units Tech Label.

Adjusting
Cooling
Set thermostat
to desired temperature
and set system switch to
COOL. The unit will come on and operate automatically
under
control of the thermostat.
Close all doors and windows. The unit

in the ON position the circulating air blow(after the 30 second delay) at the speed
AUTO position the blower will only be on
cooling cycle.

Room Temperatures

If the temperature in individual rooms is not as desired, balance
the system by adjusting the dampers in the branch ducts. Adjust a
little at a time and wait a day after each change to judge the effect.
Once the dampers are adjusted for normal weather conditions, it
is best to leave them that way. Compensate for temporary weather changes by adjusting the thermostat setting.

10. Maintenance
Monthly
Checks

Maintenance

and Inspection

rinsing

Air Filters
CAUTION
Do NOT operate without

Inspect

filters

Washable

air filters.

pointing

at least

monthly

and replace

filters may be cleaned

with cold water. Replace
in the direction

mon cause
compressor

of inadequate

by soaking

or clean

filters with the arrows

of air flow. Dirty filters
heating

or cooling

failures.

50901

as required.

in mild detergent

110202

and

on the side

are the most com-

performance,

and of

I Installation

Refer to FIGURE

19 to illustrate

access panel. Filters
this access panel.

Heating

Combination

Instructions

should

Season

location of filter racks

be removed

and

replaced

and filter
through

Refrigeration

Checks

(Monthly)
Typical

i6

Ports

This unit is equipped with refrigeration
access ports mounted on
the side of the unit. Refer to FIGURE 18 for identification
of ports.

Pilot Flame

FIGURE

Access

Units

Access Ports

Pilot Assembly

I

FIGURE

i9

Access
(Except to
"B"Built-In
Chassic)Filters

While the main burner is on, the flame should envelop the upper
part of the flame sensor, as shown in FIGURE 16.

Main Burner Flame
Flames should be stable and solid blue, (dust may cause orange
tips or they may have wisps of yellow, but they MUST not have
solid yellow tips). They should extend directly into the heat exchanger
tubes and the turbulators
should glow orange (after
about five minutes of operation).
Main burner flame should be inspected monthly.

FIGURE

Normal

Flame

Vent Assembly

Turbulator will glow
orange when hot.

Flame should be
stable and solid blue.
Burn hazard.
Flue cover may be hott Allow adequate time for flue
cover to cool.
Failure to follow this warning can result in property
damage or personal injury.

Using a light and mirror (as required) inspect the inside of the vent
hood and the inlet air opening in the burner compartment.
Look for

E_

50901

110202

I

I Combination

Units

Installation

soot and severe rust or corrosion and any obstructions
leaves, spider webs, etc. Clean as required.

Cooling

Season

Condenser

Checks

due to

(Monthly)

Coil

Keep the condenser inlet and outlet area clean and free of leaves,
grass clippings or other debris. Grass should be kept short in front
of the condenser inlet. Shrubbery MUST be trimmed back so it is
no closer than 30 inches to unit.

2.

Remove the four screws
ing. If unit has a support
securing the bracket.

3.

Remove

4.

Slide entire housing toward you. This will allow
cess to the speed tap block, motor, and wires.

5.

After

the two red wires

access,

Motor removal
Condensate

Drain

Check for condensate

drainage. Clean as required.

NOTE: When unit is operating in cooling mode under high humidity ambient conditions, condensate can form in the burner
compartment and may drip from front of the compartment. This
condition is NOT harmful to unit.

Annual

Maintenance

and Inspection

securing
bracket,

Instructions

replace

attached

all wires,

the blower motor housremove the two screws

to the limit switch.

screws,

easier

ac-

and connections.

and replacement

The blower motor may be replaced while accessing it using method 1. To replace motor, reach behind blower housing and locate
blower wheel set nut. Loosen set nut, all wires from motor, and
four pins on mounting cradle. Pull motor towards you. To replace
motor, reverse this procedure.
Method

2

This method is required to replace or repair blower wheel, blower
housing, or any unreachable components behind blower assembly.
1.

Repeat steps 1 through 4 in method 1.

2.

Remove all screws around rim of unit top, (except screws
which are inaccessible because of proximity to structure).

Electrical shock hazard.

3.

Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.

Raise unit top at corner of unit closest to blower at least 2"
and place a sturdy brace at least 2" thick between top and
unit corner. See FIGURE 20. A 2X4 piece of wood is ideal
for this.

4.

Disconnect al! wires from housing and slide housing out of
unit. Reverse this process to reinstall.

Failure to follow this warning can result in property
damage, personal injury, and/or death.

FIG uRE 20

ProppedBI°wer
AcceSSwith
2x4Sh°wing Lid

The annual inspection should include lubrication
and cleaning as
required to ensure efficient operation
of the unit. To simplify access, remove all access panels and the top from the unit if possible.

Condenser

Fan Motor

Oil the condenser fan motor after five years of operation and every
five years thereafter.
Use SAE 10W30 motor oil. To oil, remove the hole plugs from the
motor end bells and add several drops (approximately 1/2 teaspoonful) of oil with a squeeze type, flexible tube oiler. Replace
hole plugs after oiling. Do not over oil.
Clean the surrounding
area and the condenser
coils. Use caution to avoid damage to coi! fins.

and evaporator

Speed Taps

Blower Motor Access
Refer to NO TAG for a view

of blower

motor

and compartment.

Method 1

After determing necessary CFM and speed tap data on from tech
data label on the unit or in the Technicallnformation
Manualfollow
the steps below to change speeds.
1.

This method allows you to work on the motor and housing while
still in the unit. The blower motor can be replaced with this method,
but some may prefer to work on the housing assembly separately.
If this is your preference, use method 2.
1.

Remove the blower access panel

Refer to FIGURE 21 below and locate the speed tap block
on blower motor.
The yellow lead MUST always be connected
to the speed
tap block atthe common quick connect terminal. The terminal is identified as COM. Also, this is the only lead which is
1 ,
3/16"
wide. All other quick connects are /4' wide.

50901

110202

[_[]

_ Installation
3.

Instructions

Combination

If it has been determined
that cooling and heating speeds
are needed on the same speed tap, remove the red heating

lated male terminal
the insulated
black

lead from

speed

FIGURE

the speed

2i

tap block

Blower

and connect

it to the insu-

Motor Speed Taps (3-Speed

and ,-Speed

Units

I

on the black cooling lead. Then place
female quick connect to the required

tap.

Motors)

/

\\\

/

4-SPEED
MOTOR
YELLOW

BLACK

I

I

BE SURE TO CHECK BLOWER MOTOR
SPEED DATA ON UNITS TECH LABEL

RED

\\_\\\\

Circulating
Visually
Clean

inspect

the blower

the compartment

excessive
necessary

Oil the

Air Blower

on blower

after five years

and the blower

by adding
bearing.

of operation

50901

110202

wheel.

of dirt or lint.

If accumulation

or does not easily

the blower

motor

10W30 to each motor

wheel for accumulations

wheel,

to remove

blower

CAUTION

remove,

is

it will be

teaspoonful

The blower
and every

Burners / Heat Exchangers /

Flue

Gas

Passages

To inspect the burners, heat exchanger
and interior flue gas passages, use a light and small mirror on an extension
handle.

assembly.

1/2

Do not use 3 in I oil, penetrating oil, WD40 or similar oils to oil
motor bearings.

motor

(lcc)

of SAE

should

be oiled

five years thereafter.

Check the exterior of the heat exchanger
and the interior flue gas
passages
for any evidence
of deterioration
due to corrosion,
cracking or other causes. If signs of scaling or sooting exist, remove the burners and clean the heat exchanger,
as required.

I Combination

Units

Installation

Inspection And Cleaning Of Burner
Assembly/Heat
Exchangers/Flue
Gas
Passages

Instructions

Access to Burners

For Qualified Service Technician Only

See FIGURE 24 for identification of parts.
1.

Disconnect electrical power to unit.

2.

Turn OFF

3.

Remove

4.

Remove the vent assembly flue cover.

5.

Disconnect gas pipe at union.

6.

Disconnect wires from gas valve, note connections.

7.

Remove

gas at manual

burner

access

screws

gas control

valve,

shut off valve.

panel.

Burners, Valve, and Burner Box
Removed

that secure

the flame

manifold

and burners

shield

and remove

as an assembly.

8.

Remove collector box, injector plate, and restrictor plate,
including gaskets. See FIGURE 23.

9.

Hold the burner assembly vertically and lightly tap it against
a wood block. Clean also with a stiff brush.Severe
cases of
lint clogging

may require

washing

the burners

in hot water.

10.

Remove turbulators
and clean with small brush. Reinspect
after cleaning and replace turbulators
if defective.

11.

Clean flue gas passages
by using small brushes and avacuum cleaner. It may be necessary
to fabricate
handle extensions
for the brushes to reach the areas that require
cleaning.
Reinspect after cleaning and replace the heat exchanger
if defective.

EiGURE 24

12.

Reinstall parts and gaskets in reverse order. On
spark to pilot models check the spark gap. 1/8 inch is
required between the igniter and pilot hood.

13.

Turn gas on and check for leaks.

14.

Install all access panels, turn power on and check for
normal operation.

Burner Assembly

Removed

Gas Valve

50901

110202

[_

C
o"1
o
_o
o

o
o

rtl

RIGGING
INSTRUC
IONS
FAILURE
TO FOLLOW
THESE
INSTRUCTIONS
CAN RESULT
IN PROPERTY
DAMAGE,
A WARNING
BODILY
INJURY
OR DEATH.
ALL

PANELS

MUST

I}E

IN

PI ACE

WHEN

RGGING

AND

Q
Q

o

i•

Q
c
m

I-m.
m.

am

0

t_

LFTNO.
_t

HOOK RIGGNG
SHACKLES
TqROUGH
HOLES N BASE RAL,
AS SHOWN
N DETAIL A.
USE SSREADER
BARS,
WHEN RGGNG,
TO PREVENT
UNI:: DAMAGE.
BE SUR"
RIGGNG
AND SHACKL
S ARE SUFFCIENT
TO HANDLE
WEGHT
LS::ED
BELOW

o

DET AlL A

BARS

HEIGHT

LENGTH

CAB NET

_/

COOL NO
CAPAC TY
RANGE

WIDTH

ENGTq

WI/}] H
N

MM

HEGH]

N

MM

N

4S.OO

1219

48,00

1219

35.00

75.00

185£

48,00

1219

3650

MAX. WEIGH I
MM

LB

KG

838

450

204

927

700

518

0
o

B
C

1.5

55

5 6.5

TONS
TONS

3

o
C
o)

INTERNATIONAL COMFORT PRODUCTS
LIMITED WARRANTY CERTIFICATE
For Cooling
SAVE THIS CERTIFICATE.
province

It gives you specific

& Heating Products

legal rights, and you may also have other rights which

may vary from state to state and

to province,

If your unit needs servicing, contact a qualified dealer or qualified service agency of your choice. When requesting service, please have the modet and
serial number from each unit in your heating and/or cooling system readily available. If your dealer needs assistance, the distributor is available to
provide support and we, in turn, support its efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this Limited Warranty for your files.

GENERAL TERMS
Subject to the conditions and limitations stated herein, during the term of this Limited Warranty, we will provide a replacement for any functional
component part (as defined below) of your unit that fails due to defect in materials or workmanship. The term of this Limited Warranty is five years from
installation on Residential Products and one year from installation on Commercial Products or applications.
Except as otherwise stated in the
"Additional Terms" section, this Limited Warranty covers only the original purchaser and subsequent transferees, and onty while the unit remains atthe
site of the original installation (except for mobile home installations), and only if the unit is installed inside the continental United States, Puerto Rico,
Alaska, Hawaii or Canada. In addition, the Limited Warranty applies only ifthe unit is installed and operated in accordance with the printed instructions
accompanying the unit, and in compliance with all applicable installation and building codes and good trade practices. As used inthis Limited Warranty,
"installation" means the original installation of the unit.
TH ERE ARE EXCEPTIONS to this Limited Warranty as described on the reverse side of this page. All replacement parts will be warranted for the
unused portion of the warranty coverage period on the unit. The part to be replaced must be returned by the dealer to a distributor that sells products for
International Comfort Products, in exchange for the replacement part. In lieu of providing a replacement part, we may, at our sole option, refund to you
an amount equal to the distributor's component purchase price from us, or provide to you a credit equal to that amount to be applied toward the purchase
of any new unit that we distribute. If a credit for a new unit is given in tieu of a replacement part, the rating plate from the unit being replaced must be
submitted on a warranty claim, and you r dealer must make the unit being replaced available to ou r distributor for disposition. As a condition to warranty
coverage, the unit must receive yearly maintenance, as described in the owner's manual, by a dealer. Satisfactory proof of yearly service by a dealer
may be required.
"Functional component parts" include only the following: blower motor, unit-mounted sensors & timers, condenser motor, evaporator coil, condenser
coil, condenser fan, capacitor, transformer, single-phase strip heat elements, expansion device, reversing valve, solenoid valve, service valve,
electronic and electro-mechanical control board, ignitor, ignition module, draft inducer assembly, burner pilot, gas valve, limit control, pressure switch,
relays and contactors, blower wheel, interlock switch, crosslighter, pilot shield, gas & oil burners, oil pump assembly, accumulators and factory installed
driers and strainers.
This Limited Warranty DOES NOT COVER any labor, material, refractory chambers, oit nozzles, refrigerant, refrigerant inspection and refrigerant
reclaiming, freight and/or handling charges associated with any repair or replacement and such charges will be your responsibility.
To establish the installation date for any purpose under this Limited Warranty, you must retain the original records that can establish the installation date
ofyour unit. Ifyou donot providesuchdocumentsthe
start dateoftheterm ofthis LimitedWarrantywillbe
based uponthedate ofunit manufacture, ptus
thirty (30) days. In establishing that the required yearly service has occurred, you must furnish proof of yearly service by a qualified service agency.
This Limited Warranty does not cover: (a) failure or damages caused by accident, abuse, negligence, misuse, riot, fire, flood, or Acts of God (b)
damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals (other
than those found in a normal residential environment) (c) damages caused by an unauthorized alteration or repair of the unit affecting its stability or
performance (d) damages caused by improper matching or application of the unit or the unit's components (e) damages caused by failing to provide
proper maintenance and service to the unit in accordance with this Limited Warranty Certificate and the printed instructions originally provided with the
unit (f) any expenses incurred for erecting, disconnecting, or dismantling the unit (g) parts or supplies used in connection with service or maintenance,
such as refrigerant, refractory chambers, oit nozzles, filters, or belts (h) damage, repairs, inoperation or inefficiency resulting from faulty installation or
application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including additional or unusual use of supplemental electric
heat (j) units which have not had the required yearly maintenance described elsewhere in this limited warranty.
In no event shall we be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.

WE HAVE NOT MADE, DO NOT MAKE, AND HEREBY DISCLAIM ANY IMPLIED CONDITION OR IMPLIED
WARRANTY OF FITNESS FOR A PARTICULAR USE OR PURPOSE, AND ANY IMPLIED CONDITION OR
IMPLIED WARRANTY OF MERCHANTABILITY, TO THE FULLEST EXTENT ALLOWED BY LAW. WE MAKE
NO EXPRESS OR IMPLIED WARRANTIES EXCEPT AS STATED IN THIS LIMITED WARRANTY CERTIFICATE.
No one is authorized to change this Limited Warranty or to create for us any other obligation or liability in connection with this unit. Any implied
warranties that are not disctaimable shall last only for the term of the express warranty contained herein. Some states and provinces do not allow the
exclusion or limitation of incidental or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the above
limitations or exclusions may not apply to you. The provisions of this Limited Warranty are in addition to and not a modification of or subtraction from any
statutory warranties and other rights and remedies provided by law.

Please refer to reverse side of this page for additional terms.
Model No.
Serial No.

Date Installed

USA: International Comfort Products, LLC ° 650 Hell-Quaker Avenue ° P.O. Box 128 • Lewisburg, Tennessee 37091 ° (931-270-4100)
CANADA: International Comfort Products division of UTC Canada Corporation • 6060 Burnside Court, Unit 1, Mississauga, Ontario L5T 2T5
(905-795-8113).
Manufacturers of Airquest, Arcoaire, Clare, Comfortmaker, Dettson, Hell, Keeprite, Lincoln, Tempstar and other quality brand name private label
products.
Part No. 401 06 1010 24 (Orig. 11/xx/2003)

ADDITIONAL

TERMS FOR RESIDENTIAL

APPLICATIONS

ONLY

The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
Warranty coverage is limited to parts that fail due to defect in lnaterials or workmanship during the specified term.

CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS*
Gas Model Series: C9MPV, HgMPV, TgMPV, CgMPT, H9MPT_TgMPT, C9MPD, H9MPD, TgMP: Limited Lifetime Warranty on heat exchangers. If a
heat exchanger on one of these furnaces fails due to defect in the part, we witl provide a replacement part or, at our option, credit toward the purchase of
a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and lasts only for as long as the originat
purchaser tives in the home where the furnace is initially installed .** It is not transferable to any subsequent owner. Ifthe furnace was not installed in the
home owned by the original purchaser, if the original purchaser setls the home to a subsequent owner, or if proof of originat purchase cannot be
provided, then the limited warranty is only for 20 years from the date of originat installation.
Gas Model Series: T8MPV. H8MPV. C8MPV. T8MPT. H8MPT. C8MPT: A replacement heat exchanger wilI be provided for any heat exchanger that
fails in one of these furnaces due to defect for 25 years from the original date of installation.
Gas Model Series:
T8MPN. H8MPN. C8MPN. T8MPL H8MPL. C8MPL. T8DNL. H8DNL C8DNL N8MPN. N8MPL NgMPI. N9MP2: A
replacement heat exchanger will be provided for any heat exchanger that fails in one of these furnaces due to defect for 20 years from original date of
installation.
Oil Model Series: OLR(105. 160. 182L OCF. OLF. OUE NOLF. NOUF. OLB. OHB. ODH. FLU. MBO. LBO. NOMF: Limited Lifetime Warranty on
heat exchangers. Ifa heatexchangerononeofthesefumacesfailsduetodefectinthepart,
wewitl provide a replacement part or, at our option, credit
toward the purchase of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tests only for as
Iong as the original purchaser lives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. If the furnace
was not installed in the home of the original purchaser, if the original purchaser selts the home to a subsequent owner, or if proof of original purchase
cannot be provided, then the limited warranty is only for 20 years from the date of original installation.
Oil Fired Floor Furnace: NFO: A replacement heat exchanger witl be provided for any heat exchanger that faits due to defect for 10 years from
installation with the following timitatiom during the sixth through tenth year, any credit toward your purchase of a component or toward the purchase of
any new unit wilI be in an amount equal to the distributor's purchase price reduced by 20 percent for each year after the fifth year.

ADDITIONAL

TERMS FOR OIL FURNACE APPLICATIONS

ONLY

1) OIL BURNERS - A replacement for 5 years from date of original installation for Oil Burner Parts,
2) OPTIONAL ACCESSORIES AND FUNCTIONAL PARTS: A replacement for 5 years from date of original
oil nozzles not included)

GAS/ELECTRIC
Model series:

PACKAGED

installation.

(Refractory

and

UNITS HEAT EXCHANGERS

PGAD, PGAA, PGMD, PGME, PGE GPFM, PGC, GPCM:

A replacement for 10 years from original date of installation.

COMPRESSORS:*
1) Premium Model Units: HAC0. HAC2. HAC4. CAC0. CAC2. CAC4. KAC0. TCA0. TCA2. TCA4. HHP0. HHP2. HHP4. CliP0. CliP2. CliP4.
TCH0. TCH2. TCH4.HXA2.TXA2.CXA2.HXA4.TXA4.CXA4.
PGME. PYMC. PHAD. PGAD. PA95. PAPC. PAK. APK: To the original purchaser a
replacement for 10 years from original date of installation, only if the unit is installed with factory matched coiis, except air conditioner condensing units
with a nominal SEER of 10 may be matched with evaporator coils of the same nominal tonnage regardless of manufacturer and in accordance to factory
recommendations. This limited 10-year warranty is not transferable to any subsequent owner. HOWEVER, if the unit was not installed in the home
owned by the original purchaser, if the purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be provided, then the
limited warranty is onty for 5 years from the original date of installation.**
2) All Other Models: Air Conditioners.
Heat Pumps. & Combination
Gas/Electric Units: NAC0. NAC2. NHP0. NHP2. AO. A2. Ha. H2. PGF.
PGC. GPFM. GPCM. PAF. APFM. PHF. HPFM. PGAA. PGMD. PA55. PH55. PAPA. PYPA. PGS. GPSM: A replacement for 5 years from date of
original installation, only if: (a) air conditioner condensing units with SEER rating in the range of 10 to 11 SEER are matched with evaporator coits of the
same nominal tonnage regardless of manufacturer and in accordance to factory recommendations, or (b) heat pump condensing units are used with
factory matched coils, unless written approval to do otherwise is obtained from manufacturer.

ADDITIONAL

TERMS FOR COMMERCIAL

PRODUCT OR APPLICATIONS

ONLY

For purposes of this warranty a commercial product or application is one in which: the product has over 5 tons nominal cooling capacity, or
is designed for operation with 3 phase electrical power, or is installed in a commercial establishment such as a beauty or hair salon, hospital,
school, restaurant, church, hotel etc..
3-Phase Models: PGF, GPFM, GPF, PGAD, PGME, PGB, PGMG, PGMF, PGS, GPSM, PGE, APE, PAE, PAB, PAMD, PAS, PAL=,APFM, APF,
PHB, PHE, PYMD, HPB, PHS, CAC, ACC, CAE, ACE, CHC, HCC, CHE, HCE, CHB, YA:
The additional

Terms of the components

listed below are in addition to and subject to the General Terms on the reverse side of this page.

1) GAS FIRED H EAT EXCHANGERS (ALL MODELS, except PGS, GPSM 3 to 5 Ton):* A replacement for 10 years from date of original installation.
a) NOTE: PGS, GPSM 3 to 5 Ton Models:* A replacement for 15 years from date of original installation.
2) COMPRESSORS (ALL MODELS):* A replacement for 5 years from date of original installation.
3) OPTIONAL ACCESSORIES AND FUNCTIONAL COMPONENT PARTS (ALL MODELS):*
A replacement for 1 year from date of original installation.
4) COMMERCIAL OIL MODELS: OLR210, OLR350, OTF210, AMT3, AMT4, AMP3: Ten(10) Year Limited Warranty on heat exchangers.
*To receive advantage of your limited warranty, you must provide proof of yearly service by a qualified service agency.
**To receive advantage of your warranty, you must retain the original records that can establish the installation date and proof of purchase of the unit.

MINI SPLITS:
Summary - Mini Splits Warranted for one (1) year on all replacement parts.
Additional terms for Mini Splits:
The additional Terms of the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
1) Compressors
installation.

(All Models):

A replacement compressor wili be provided for atI compressors that faiI due to defect for 5 years from date of original

2) Optional Accessories and Functional Components Parts (All Models):
A replacement part will be provided for alI parts that fail due to defect for one (1) year from date of original installation.
Failure to maintain the equipment through annual maintenance by a qualified service agency shall void the warranty.
with ati warranty claims. Proof of purchase and installation date must be submitted with ali claims.

Proof of service will be required



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 22
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Thu Apr 05 04:04:37 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu