AP669 Ceiling Mount Detector Installation Sheet
1.

Selecting a mounting location
Install the detector so that the expected movement of an
intruder will be across the fields of view. This is the direction
best suited for PIR detectors.

Lift off mounting plate (item 1) as shown in Figure 1.
Fasten the mounting plate to the ceiling in the required
position using mounting holes (item 2).
The detection pattern can be adjusted by up to ±15°
(30° max.) by rotation of the mounting plate prior to
tightening the screws.

Avoid possible false alarm sources such as:
•

Direct sunlight onto the detector

2.

•

Heat/cold sources in a field of view (heaters, air
conditioning, radiators, etc.)

Strip outer jacket approximately 2 inches (50 mm) and pull
it through the cable entry hole (item 3) and strain relief.

3.

Wire the detector and select the appropriate processing
options as shown in Figure 2 and replace the sensor
module (item 6).

4.

To mount the sensor module to the mounting plate use the
screw (item 7), which is placed for transport in the
mounting plate.

•

Moving objects in the field of view (fans, pets, etc.)

•

Obscuring the detector field of view with large objects,
such as furniture

Caution: Increasing mounting heights beyond the specified
range will reduce sensitivity.

The curtain directions 1 to 9 clockwise (item 8) are indicated in
the mounting plate (curtain number 5 is the center curtain.)

Mounting instructions

Connection and programming

Figure 1: Mounting

Figure 2: Connections and default DIP switch settings

Table 1: DIP switches
Switch

Description

On

Off

1

LED enable

LED on

LED off

2

Processing

Bi-curtain

Standard-4D

3

Detection pattern

180°

360°

Switch 1: Programming the LED
ON: LED enabled.
OFF: LED disabled.
Switch 2: Programming the processing
ON: Enables Bi-curtain processing designed for harsh
environment.
OFF: Provides the standard 4D processing.
Switch 3: Programming the detection pattern
ON: Provides a 180° field of view for special applications.
OFF: Gives the normal 360° field of view.

© 2016 UTC Fire & Security Americas Corporation, Inc.

1/2

P/N 14012-EN • REV G • ISS 01NOV16

Note: An arrow in the mounting plate (4) (see Figures 1 and 3)
and inside the sensor module shows the always active
coverage pattern. The coverage pattern opposite to the arrow
can be disabled by setting switch 3 in the ON position.
Figure 3: Coverage pattern

Mounting height application note
When increased mounting heights are used outside the
specified mounting height range of 8–16 ft. (2.4–4.8 m),
sensitivity will be reduced.
Figure 5: Field of view

9

1

8

2

7

3

6

4

5

5

6

4
7

3
8

2
1

An arrow inside the mounting
plate & sensor module
indicates the always
active direction.

9
Shaded area shunted when
switch 3 is ON position.

Specifications
Input power

12 VDC nom.

Peak to peak ripple

2 V max. (at 12 V)

Current consumption:
Normal operation

9 mA (at 12 V)

Alarm

15 mA max. (at 12 V)

Specified mounting height

8–16 ft. (2.4–4.8 m)

Target speed range

0.9 to 12.0 ft./s

Alarm output

50 mA at 28 V, Form C

Undo the screw (item 5) and open the sensor module (item 6)
(see Figure 1).

Alarm time

2.5 s min.

Tamper output

100 mA at 28 V

Two mirrors are accessible now.

Temperature limit

+14 to 131°F (−10 to +55°C)

Relative humidity

93% max.

30 ft.

30 ft.

Access to the mirror inside the sensor module
This access is only required when masking individual curtains.

Selecting the coverage patterns

Size

Ø5.43 in. x 2.68 in. (Ø138 mm x 68 mm)

Mask the appropriate mirror curtains with the adhesive labels
provided and reassemble the sensor module.

Weight

4.25 ounces

Number of curtains

18

For example, see Figure 4 for mirror curtain coverage pattern
corresponding to curtain 4 and 8 masked.

Max. detection range

60 ft. (18 m) diameter, 30 ft. (9 m) radius

Figure 4: Coverage pattern masking

Regulatory information
Manufacturer

UTC Fire & Security Americas Corporation, Inc.
3211 Progress Drive, Lincolnton, NC, 28092, USA
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands

Contact information
www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customersupport

2/2

P/N 14012-EN • REV G • ISS 01NOV16



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 2
Language                        : en-US
Tagged PDF                      : Yes
Title                           : AP669 Ceiling Mount Detector Installation Sheet
Author                          : Mikhail Sleptsov
Subject                         : AP669 Ceiling Mount Detector
Creator                         : Microsoft® Word 2010
Create Date                     : 2016:11:08 10:37:04+01:00
Modify Date                     : 2016:11:08 10:37:04+01:00
Producer                        : Microsoft® Word 2010
EXIF Metadata provided by EXIF.tools

Navigation menu