Itron 100G Utility Meter Transceiver User Manual 100G Installation Guide

Itron, Inc. Utility Meter Transceiver 100G Installation Guide

User Manual

Download: Itron 100G Utility Meter Transceiver User Manual 100G Installation Guide
Mirror Download [FCC.gov]Itron 100G Utility Meter Transceiver User Manual 100G Installation Guide
Document ID728189
Application IDDDn0yiHILPubrqG7lUoYEw==
Document DescriptionUser Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize271.73kB (3396589 bits)
Date Submitted2006-11-14 00:00:00
Date Available2006-11-14 00:00:00
Creation Date2006-10-30 10:17:41
Producing SoftwareAcrobat Distiller 7.0.5 (Windows)
Document Lastmod2006-10-30 10:28:31
Document Title100G Installation Guide
Document CreatorAcrobat PDFMaker 7.0.5 for Word

Natural Gas Solutions
100G Installation Guide
Revision A
Identification
100G Installation Guide -- DRAFT
Part number: PUB-0200-001 Revision A 10/06
ERT Part Numbers: ERG-aaaa-bbb, CCCC-ddd, etc.
Copyright
© 2006 Itron, Inc. All rights reserved.
Your company has the right to reproduce this contract document, provided that such reproduction shall be subject to the same use and disclosure restrictions contained in the
Confidentiality and Non-Disclosure paragraphs in the Sales Contract.
Applicable Patents
U.S. Patent Numbers: XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX????
Canadian Patent Numbers: XXXXXXXXXXX XXXXXXXXXX XXXXXXXXX?????????
Transportation Classification
Itron classifies and ships model 100G ERT modules as a non-hazardous material. The proper shipping name is Lithium Batteries contain in Equipment, Class 9, UN3091, Packing
Group II.
The Federal Aviation Administration prohibits operating transmitters and receivers on all commercial aircraft. When powered, the 100G ERT module is considered an operating
transmitter and receiver and cannot be shipped by air.
Compliance Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio or TV technician for help.
This device complies with Subpart C of Part 15 of FCC Rules. Operation of this device is subject to the following two conditions:
• This device may not cause harmful interference.
• This device must accept any interference that may cause undesirable operation.
This device must be permanently mounted such that it retains a distance of 20 centimeters (7.9 inches) from all persons in order to comply with FCC RF exposure levels.
Modification and Repairs
To ensure FCC compliance and system performance, this device and antenna shall not be changed or modified without the expressed approval of Itron. Any unauthorized modification
will void the user’s authority to operate the equipment.
Meter Installation/Removal
In the event of malfunction, all repairs should be performed by Itron. It is the responsibility of users requiring service to report the need for service to Itron.
Related Documents
EndPoint-Link ERT Programming Guide (TDC-tbd-tbd)
Trademark Notice
ERT and Itron are both registered trademarks of Itron, Inc. All other product names and logos in this documentation are used for identification purposes only and may be trademarks or
registered trademarks of their respective companies.
Suggestions
If you have comments or suggestions on how we may improve this documentation, send them to TechnicalCommunicationsManager@itron.com.
If you have questions or comments about this application, contact Itron Technical Support:
Itron, Inc.
• Mail: Itron, Inc. 2401 North State Street, Waseca, MN 56093
• E-mail: support@itron.com
• Phone: 1 800 392 3185; Fax: 507 837 4451
Table of Contents
Chapter 1 Getting Started ...........................................................................................1
Transmission Modes ...........................................................................................................................1
Specifications ......................................................................................................................................1
Meter Compatibility List .......................................................................................................................2
Chapter 2 American Meter Installation .......................................................................5
Installation Prerequisites .....................................................................................................................5
Materials Supplied By Itron .......................................................................................................5
Materials Supplied By You........................................................................................................5
Replacement Screws......................................................................................................6
Preinstallation Preparations ......................................................................................................6
Installing the 100G on an American Meter..........................................................................................6
Remove the Existing Index .......................................................................................................6
Assemble the ERT Module .......................................................................................................9
Program the ERT Module .......................................................................................................13
Attach the ERT Module to the Meter ......................................................................................15
Chapter 3 Sensus Meter Installation.........................................................................19
Introduction........................................................................................................................................19
Installation Prerequisites ...................................................................................................................19
Materials Supplied By Itron .....................................................................................................19
Materials Supplied by You ......................................................................................................19
Replacement Screws....................................................................................................19
Preinstallation Preparations ..............................................................................................................20
Installing the 100G on a Sensus Meter .............................................................................................20
Remove the Existing Index .....................................................................................................20
Assemble the ERT Module .....................................................................................................22
Program the ERT ....................................................................................................................24
Attach the ERT to the Meter ...................................................................................................25
100G Installation Guide
iii
Table of Contents
iv
100G Installation Guide
CHAPTER 1
Getting Started
The 100G is Itron's latest high-powered gas encoder-receiver-transmitter (ERT) module.
ERTs are meter-installed devices that transmit meter data using radio communications. That
information may be received by a reading device that is within transmission distance,
meaning that multiple devices may receive data from a single endpoint. Itron's 100G ERT is
a high-powered device with a wide transmission distance.
This installation guide shows you how to install the 100G ERT module on meters from a
variety of manufacturers. To ensure you have a meter that is compatible with the 100G ERT
module, please see the Meter Compatibility List on page 2.
Transmission Modes
Once installed, the 100G ERT module has two standard available transmission modes:
•
Fixed Network Mode In this mode, a 100G ERT module transmits a high-powered
RF message every 60 seconds.
•
Mobile and HandHeld Mode In this mode, a 100G ERT module transmits a
medium-powered RF message every 15 seconds.
An FCC license is not required to read 100G ERT modules.
Specifications
The functional and operational specifications for the 100G are listed below.
Functional Specifications
Description
Power Source
"A" cell lithium battery
Tamper Detection
Tilt tamper and magnetic tamper
FCC Compliance
Part 15 certified
Industry Canada Compliance
RSS-210 certified
Measurement Canada Approval
Yes
Intrinsically Safe per
Factory Mutual and UL Class I, Division 1, Groups C
and D
Product Identification
Numeric and barcoded ERT module type and serial
number
Contstruction Materials
Gray polycarbonate back plate with Santoprene®
gasket; clear polycarbonate front cover; encapsulated
electronics
100G Installation Guide
Chapter 1 Getting Started
Operational Specifications
Description
Operating Temperatures
-40° to 158° F (-40° to +70° C)
Operating Humidity
5 to 95percent relative humidity
Program Frequency
908 MHz
Transmit Frequency
Spread spectrum 908 to 924 MHz ISM band
Data Integrity
Verified in every data message
Meter Compatibility List
The following meters are compatible with the 100G. Due to continuous research, product
improvements, and enhancements, Itron reserves the right to change this list at any time.
To ensure you have the latest Meter Compatibility list available, contact your Itron
representative.
Mfgr.
Model
American/ Canadian
Desc.
Class
Comments
ERT Type
ERT Part No.
W75AL
Residential
Aluminum case
Meters Only
100G
ERG-5000-001
American/ Canadian
AL-175
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AC-175
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AT-175
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
ALC-175
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AT-210
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AL-225
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AL-250
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AR-250
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AC-250
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AT-250
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AM-250
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AL-310
Residential
Aluminum case
meters only
100G
ERG-5000-001
Canada
only
100G Installation Guide
Meter Compatibility List
American/ Canadian
AL-350
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AT-350
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AL-425
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
AC-630
Residential
Aluminum case
meters only
100G
ERG-5000-001
American/ Canadian
5B 225
Residential
Aluminum case
100G
ERG-5000-001
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
R-175
11 Tooth
Residential
Sensus/Invensys/
Equimeter/ Rockwell
R-200
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
RT-200
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
RT-230
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
R-275
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
RT-275
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
R-315
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
250
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
310
11 Tooth
Residential
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
S-110
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
S-200
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
175-S
100G
ERG-5000-002
100G
ERG-5000-004
100G
ERG-5000-002
Sensus/Invensys/
Equimeter/ Rockwell
Sensus/Invensys/
Equimeter/ Rockwell
100G Installation Guide
RT-100
S-190
11 Tooth
11 Tooth
11 Tooth
18 Tooth
11 Tooth
Compatible with 2
foot drive index; 1
foot drive has 24
teeth
Residential
Residential
Residential
Residential
Residential
Chapter 1 Getting Started
Sensus/
Invensys/ Equimeter/
Rockwell
S-120
Sensus/Invensys/
Equimeter/ Rockwell
T-120
Sensus/Invensys/
Equimeter/ Rockwell
T-110
Sensus/Invensys/
Equimeter/ Rockwell
R-415
Sensus/Invensys/
Equimeter/ Rockwell
RT-360
11 Tooth
11 Tooth
11 Tooth
18 Tooth
18 Tooth
Sensus/Invensys/
Equimeter/ Rockwell
MR8
(R-275
Metric)
16 Tooth
Sensus/Invensys/
Equimeter/ Rockwell
MR12
(R-415
Metric)
16 Tooth
Residential
100G
ERG-5000-002
100G
ERG-5000-002
100G
ERG-5000-002
100G
ERG-5000-004
100G
ERG-5000-004
100G
ERG-5000-003
100G
ERG-5000-003
Residential
Residential
Residential
Residential
Residential
Residential
100G Installation Guide
CHAPTER 2
American Meter Installation
This chapter shows you how to install a 100G gas ERT module on an American meter.
Before installing the 100G ERT module, verify that you have:
•
A compatible meter. See the the Meter Compatibility List on page 2 for more
information.
•
A compatible index. Itron 100G gas ERT modules can be used with standard dial and
direct read (odometer) indexes on American Meters.
•
The list of materials defined under Installation Prerequisites on page 5.
Installation Prerequisites
The following items are required to install Itron's 100G gas ERT.
Materials Supplied By Itron
The following items are supplied by Itron.
•
100G gas ERT modules
•
Tamper plugs
Materials Supplied By You
You must supply the following items to successfully install the 100G gas ERT on the
American Meters listed in the Meter Compatibility above.
•
Small and medium flat-blade screwdrivers Used to remove and tighten index and
index-cover screws.
•
Side-cutting plier/wire snips Used for cutting wire seals, if necessary.
•
Small putty knife Used to remove all traces of old gaskets from the meter.
•
Meter seals, wire seals, and seal press Used to secure the meter from tampering, if
necessary.
•
11/32-inch nut driver or other blunt tool Used to securely seat new tamper plugs
over screw holes.
•
FC200SR unit with EndPoint-Link or EndPoint-Link Pro software Used to
program and check ERT assembly.
•
Replacement screws Used to mount ERT assembly to meter and index to ERT
assembly backlates; see Replacement Screws on page 6 for more information).
100G Installation Guide
Chapter 2 American Meter Installation
Replacement Screws
Replacement screws used in this procedure must be slotted, zinc-plated, steel machine
screws. Sizing options are shown below.
•
Use 1/4 - 20 x 5/8-inch slotted, Fillister head screws for mounting 100G ERT module
assemblies on meters.
•
Use 8 - 32 x 3/16-inch slotted, round head screws for mounting indexes on 100G ERT
module backplates.
Preinstallation Preparations
Before installing the 100G gas ERT module on a meter, verify that:
•
All ERTs are type 100G modules for American Meter Company gas meters.
•
The model numbers of all meters on which the 100G modules will be installed are
included in the Meter Compatibility see "Meter Compatibility List" on page 2 list.
Installing the 100G on an American Meter
There are four major steps to installing the 100G gas ERT on an American Meter:
•
Remove the Existing Index
•
Assemble the ERT Module
•
Program the ERT Module
•
Attach the ERT Module to the Meter
These procedures are described in the following sections.
NOTE Be sure to properly dispose of all unused screws, old index covers,
gaskets, and other left-over materials. Do not leave any materials on customer
premises.
Remove the Existing Index
The first major step when installing a 100G gas ERT on an American meter is to remove the
existing index from the meter.
To Remove the Existing Index
1. Remove any tamper seals from the meter.
100G Installation Guide
Installing the 100G on an American Meter
2. Detach the index cover from the meter by removing the four screws holding it in
place.
3. Examine the index cover screws you just removed. Verify that they are 5/8-inch long
and are not corroded.
•
If the screws are 5/8-inch long, and are not corroded, keep them for later use.
•
If the screws are an incorrect length or are corroded, dispose of them properly.
Use 1/4 - 20 x 5/8-inch screws as described in Replacement Screws on page 6
instead.
TIP You can use the index cover you just removed as a temporary storage
location for screws.
4. Unscrew one index mounting screw completely.
Hold one hand beneath the index to catch the screw when it falls out of the index
assembly. If it does not fall out by itself, be sure to remove it.
5. Unscrew the other index mounting screw.
100G Installation Guide
Chapter 2 American Meter Installation
While removing this screw, pull the index away from the meter to keep its backplate
(1) against the back of the screwhead (2). This prevents the screw from falling out
prematurely.
6. Remove the screw from the index once it is completely free of its hole.
7. Set the index aside for the moment. Place it where it will not be damaged; get filled
with dirt, rain, or snow; or fall to the ground or floor. The index will be used later in
this procedure.
8. Examine the index screws you just removed. Verify that they are 3/16-inch long and
are not corroded.
•
If the screws are 3/16-inch long and are not corroded, keep them for later use.
•
If the screws are an incorrect length or are corroded, dispose of them properly.
Use 8 - 32 x 3/16-inch screws as described in Replacement Screws on page 6
instead.
9. Use a putty knife or similar object to completely remove the old index gasket from the
meter (if applicable). All traces of the gasket must be removed before athe ERT can be
installed.
100G Installation Guide
Installing the 100G on an American Meter
Assemble the ERT Module
When installing a 100G gas ERT, the next major step is to create the ERT module assembly
by combining the ERT backplate and cover with the meter index. Follow the procedure
below to do so.
To Assemble the ERT Module
1. Obtain a new 100G ERT and index cover.
2. Separate the ERT module backplate from the cover.
3. Set the new ERT index cover aside for the moment. Place it where it will not be
damaged; get filled with dirt, rain, or snow; or fall to the ground or floor. The ERT
index cover will be used later in this procedure.
IMPORTANT Before continuing with the installation, note the following
information about American Meter idexes:
•
100G Installation Guide
Index wrigglers on one-foot meters have drive slots.
Chapter 2 American Meter Installation
•
Index wrigglers on two-foot meters have drive posts.
•
An index may have mounting screw holes.
•
An index may have mounting screw slots.
If the index has mounting screw slots, skip steps 4 and 5 below. Continue with step 6.
If the index has mounting screw holes, perform steps 4 and 5 below, and then skip
steps 6 and 7.
10
100G Installation Guide
Installing the 100G on an American Meter
4. If the index has mounting screw holes, place an index mounting screw (1) in the righthand mounting screw hole (2). Use one 8 - 32 3/16-inch screw for this step (you can
use an original mounting screw if it was the correct size and not corroded; otherwise,
use the correct size replacement screw).
5. Attach the screw to the ERT backplate's right-hand index mounting post just far
enough to hold the screw and end of the index in place.
6. If the index has mounting screw slots, screw an index mounting screw (1) one to two
turns into the ERT backplate's right-hand index mounting post (2). Use one 8 - 32
3/16-inch screw for this step (you can use an original mounting screw if it was the
correct size and not corroded; otherwise, use the correct size replacement screw).
100G Installation Guide
11
Chapter 2 American Meter Installation
7. Place the index mounting screw slot under the screw head. Do not tighten the screw
yet.
8. Attach the wriggler to the index and backplate.
•
If the index wriggler has a drive slot (1), place the backplate wriggler's drive
post (2) in the index wriggler's drive slot.
•
If the index wriggler has a drive post (1), place the index wriggler's drive post
in the backplate wriggler's drive slot (2).
12
100G Installation Guide
Installing the 100G on an American Meter
9. Install and tighten the left-hand index mounting screw (for indexes with either
mounting screw slots or holes). Use one 8 - 32 3/16-inch screw for this step (you can
use an original mounting screw if it was the correct size and not corroded; otherwise,
use the correct size replacement screw).
10. Tighten the right-hand index mounting screw.
11. Slide the ERT cover (1) over the index and backplate, making sure the ERT label (2)
is visible through the window.
Next, program the ERT module.
Program the ERT Module
Once the ERT module has been assembled, the ERT must be programmed using the
FC200/SR with EndPoint-Link software. See the EndPoint-Link ERT Programming Guide
(TDC-tbd-xxx) for more information.
IMPORTANT You must perform the following programming procedure for
the ERT module to function properly.
100G Installation Guide
13
Chapter 2 American Meter Installation
When programming the ERT module, you must take note of the drive rate shown on the
index of American meters. Examples of 1-foot (1) and 2-foot (2) drive rates are shown
below. Be sure to program the ERT based on the indicated drive rate.
To Program the ERT Module
1. Using the FC200/SR, program the reading of the index that was on the meter into the
ERT module assembly. Be sure to hold the FC200/SR unit by the battery pack and
within a few inches of the ERT during programming and reading; this will ensure
proper communication between unit and the ERT.
During programming, the 100G ERT module is programmed to the nearest 100 cubic
feet; the last two digits (the tens and units) are programmed as zeros (0). Once
programming is complete, however, the ERT module assembly can be read to the
nearest cubic foot.
2. Slowly turn the ERT module drive wriggler two turns in the direction indicated on the
index drive rate. This lets you verify the ERT module is counting properly after
assembly.
14
100G Installation Guide
Installing the 100G on an American Meter
IMPORTANT Do not turn the drive wriggler faster than one turn per second.
3. Read the ERT module assembly using the FC200SR. Consult the EndPoint-Link ERT
Programming Guide (TDC-tbd-tbd) or other applicable instructions for details on how
to read an ERT.
•
If this reading is higher than the one you programmed in step 1 above, the ERT
module assembly is counting correctly.
•
If the ERT module assembly reading is not higher than what was programmed
in step 1, replace the ERT module with a new one.
Attach the ERT Module to the Meter
After the ERT has been programmed and is reading correctly, it must be attached to the
meter. Follow the steps below to do this.
To Attach the ERT to the Meter
1. 5B 225 Meters Only If you are installing the ERT on a 5B 225 aluminum meter, cut
1/16-inch off each post of the ERT wriggler to prevent it from rubbing on the face of
the nut that holds the wriggler in place. If you are not installing on a 5B 225 meter,
continue to step 2 below.
100G Installation Guide
15
Chapter 2 American Meter Installation
2. Set the wriggler to the desired position for mounting the ERT module assembly to the
meter.
•
For One-Foot Meters: Align the ERT module assembly wriggler with the meter
drive post (as shown below). Make sure the ERT wriggler is perpendicular to
the meter drive post.
•
For Two-Foot Meters: Align the ERT module assembly wriggler with the
meter slot (as shown below). Make sure the ERT wriggler is perpendicular to
the meter slot.
3. Gently place the ERT module assembly on the meter. Align the four screw holes on
the ERT module assembly with the holes on the meter.
16
100G Installation Guide
Installing the 100G on an American Meter
4. Install and tighten all ERT module assembly mounting screws, working in a diagonal
pattern as shown below. Tighten the mounting screws to 15 to 20 inch-pounds of
torque. Use the 1/4 - 20 x 5/8-inch screws for this step (you can use the original
mounting screws if they were the correct size and not corroded; otherwise, use the
correct size Replacement Screws on page 6).
5. Place a new tamper seal over two of the mounting screws as shown below.
6. Press the new tamper seals into place using the 11/32-inch nut driver (or another
similar blunt tool).
100G Installation Guide
17
Chapter 2 American Meter Installation
7. Complete any necessary paperwork. Make sure no excess material is left on the
customer premises; dispose of it properly.
The ERT is now installed on the meter.
18
100G Installation Guide
CHAPTER 3
Sensus Meter Installation
Introduction
This chapter shows you how to install a 100G gas ERT on a compatible Sensus meter.
Sensus meters are also known by the following names: Invensys,
Equimeter, and Rockwell. For consistency, all of these meter types will
be referred to as Sensus meters for this installation procedure.
Installation Prerequisites
Materials Supplied By Itron
The following items are supplied by Itron.
•
100G gas ERT modules
•
Tamper plugs
Materials Supplied by You
You must supply the following items to successfully install the 100G gas ERT on the
Sensus meters listed in the Meter Compatibility List on page 2.
•
Small and medium flat-blade screwdrivers (used for index and index-cover screws)
•
Side-cutting plier (used for cutting wire seals, if necessary)
•
Small putty knife (to remove old gaskets)
•
Meter seals, wire seals, and seal press (if necessary)
•
11/32-inch nut driver or other blunt tool (to securely seat new tamper plugs)
•
ReadOne Pro unit (used to program and check ERT assembly)
Replacement screws (used to mount ERT assembly to meter and index to ERT assembly
backlates; see Replacement Screws on page 19 for more information).
Replacement Screws
Replacement screws used in this procedure must be slotted, zinc-plated, steel machine
screws. Sizing options are shown below.
For mounting 100G ERT module assemblies on meters:
•
10 - 24 x5/8-inch slotted, Fillister head
100G Installation Guide
19
Chapter 3 Sensus Meter Installation
For mounting indexes on 100G ERT module backplates:
•
6 - 32 x 5/8-inch slotted, round head
Preinstallation Preparations
Before installing the 100G gas ERT module on a meter, verify that:
•
All ERTs are type 100G modules for Sensus gas meters.
•
The model numbers of all meters on which the 100G modules will be installed are
included in the Meter Compatibility List on page 2.
Installing the 100G on a Sensus Meter
There are three major steps to installing the 100G gas ERT on a Sensus meter:
•
Remove the Existing Index
•
Assemble the ERT Module
•
Program the ERT
•
Attach the ERT to the Meter
These procedures are described in the following sections.
Be sure to properly dispose of all unused screws, old index covers, gaskets, and
other left-over materials. Do not leave any materials on customer premises.
Remove the Existing Index
The first major step when installing a 100G gas ERT on a Sensus meter is to remove the
existing index from the meter.
To Remove the Existing Index
1. Remove any tamper seals from the meter.
20
100G Installation Guide
Installing the 100G on a Sensus Meter
2. Detach the index cover from the meter by removing the four screws holding it in
place.
3. Examine the index cover screws you just removed. Verify that they are 5/8-inch long
and are not corroded.
•
If the screws are 5/8-inch long and are not corroded, keep them for later use.
•
If they are an incorrect length or are corroded, dispose of them properly. Use 10
- 24 x 5/8-inch screws as described in Replacement Screws on page 19 instead.
TIP You can use the index cover you just removed as a temporary storage
location for screws.
4. Unscrew one index mounting screw completely.
5. Remove the other index mounting screw.
6. Set the index aside for the moment. Place it where it will not be damaged; get filled
with dirt, rain or snow; or fall to the ground or floor. The index will be used later in
this procedure.
7. Examine the index screws you just removed. Verify that they are 5/8-inch long and
are not corroded.
100G Installation Guide
21
Chapter 3 Sensus Meter Installation
•
If the screws are 5/8-inch long and are not corroded, keep them for later use.
•
If the screws are an incorrect length or are corroded, dispose of them properly.
Use 6 -32 x 5/8-inch screws as described in Replacement Screws on page 19
instead.
8. Use a putty knife or similar object to completely remove the old index gasket from the
meter (if applicable). All traces of the gasket must be removed before the ERT can be
installed.
Assemble the ERT Module
When installing a 100G gas ERT, the next major step is to create the ERT module assembly
by combining the ERT backplate and cover with the meter index. Follow the procedure
below to do so.
To Assemble the ERT
1. Obtain a new 100G ERT and index cover.
2. Separate the ERT module backplate from the cover.
3. Place the index drive gear (1) in the backplate wriggler gear cup (2) of the ERT
(please note that the following example uses an 11-tooth drive gear; your index may
be slightly different).
22
100G Installation Guide
Installing the 100G on a Sensus Meter
Once properly installed, the index drive gear and backplate wriggler cup should look
similar to the following example.
4. Attach the right-hand mounting screw to the index and meter, just far enough to hold
the index in place. Use one 6 - 32 x 5/8-inch screw for this step (you can use an
original mounting screw if it was the correct size and not corroded; otherwise, use the
correct size Replacement Screw see "Replacement Screws" on page 19).
5. Install and tighten the left-hand index mounting screw.
6. Tighten the right-hand index mounting screw completely.
100G Installation Guide
23
Chapter 3 Sensus Meter Installation
7. Slide the ERT cover over the index and backplate.
8. Verify that the cover is installed correctly; the cover's clear window should be over
the backplate label.
Once combined, the ERT backplate, meter index, and ERT cover create an "ERT
Module Assembly."
Next, program the ERT module.
Program the ERT
Once the ERT module has been assembled, the ERT must be programmed using the
FC200/SR with EndPoint-Link software. See the EndPoint-Link ERT Programming Guide
(TDC-tbd-xxx) for more information.
IMPORTANT You must perform the following programming procedure for
the ERT module to function properly.
When programming the ERT module, you must take note of the drive rate shown on the
index of Sensus meters. Sensus meters have a 2-foot drive rate, as indicated in the example
below (1).
To Program the ERT Module
1. Using the FC200/SR, program the reading of the index that was on the meter into the
ERT module assembly. Be sure to hold the FC200/SR unit by the battery pack and
within a few inches of the ERT during programming and reading; this will ensure
proper communication between unit and the ERT.
24
100G Installation Guide
Installing the 100G on a Sensus Meter
During programming, the 100G ERT module is programmed to the nearest 100 cubic
feet; the last two digits (the tens and units) are programmed as zeros (0). Once
programming is complete, however, the ERT module assembly can be read to the
nearest cubic foot.
2. Slowly turn the ERT module drive wriggler two turns in the direction indicated on the
index drive rate. This lets you verify the ERT module is counting properly after
assembly.
IMPORTANT Do not turn the drive wriggler faster than one turn per second.
3. Read the ERT module assembly using the FC200SR. Consult the EndPoint-Link ERT
Programming Guide (TDC-tbd-tbd) or other applicable instructions for details on how
to read an ERT.
•
If this reading is higher than the one you programmed in step 1 above, the ERT
module assembly is counting correctly.
•
If the ERT module assembly reading is not higher than what was programmed
in step 1, replace the ERT module with a new one.
Attach the ERT to the Meter
After the ERT has been programmed and is reading correctly, it must be attached to the
meter. Follow the steps below to do this.
100G Installation Guide
25
Chapter 3 Sensus Meter Installation
To Attach the ERT to the Meter
1. Gently place the ERT module assembly against the front of the meter as shown. Make
sure all four mounting screw holes in the ERT module assembly line up with the
corresponding holes on the meter.
2. Insert the top-right cover mounting screw. Tighten the screw just enough to hold the
ERT module assembly in place. Use the 10 - 24 5/8-inch screws for this and the
following step (you can use the original mounting screws if they were the correct size
and not corroded; otherwise, use the correct size as described in Replacement Screws
on page 19).
26
100G Installation Guide
Installing the 100G on a Sensus Meter
3. Install and tighten the remaining three mounting screws. Tighten the mounting screws
to 15 to 20 inch-pounds of torque.
4. Tighten the top-right mounting screw.
5. Place a new tamper seal over two of the mounting screws as shown below.
100G Installation Guide
27
Chapter 3 Sensus Meter Installation
6. Press the new tamper seals into place using the 11/32-inch nut driver (or another
similar blunt tool).
7. Complete any necessary paperwork. Make sure no excess material is left on the
customer premises.
The ERT is now installed on the meter.
28
100G Installation Guide

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Tagged PDF                      : Yes
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : Acrobat PDFMaker 7.0.5 for Word
Modify Date                     : 2006:10:30 10:28:31-08:00
Create Date                     : 2006:10:30 10:17:41-08:00
Metadata Date                   : 2006:10:30 10:28:31-08:00
Format                          : application/pdf
Title                           : 100G Installation Guide
Creator                         : 
Description                     : Natural Gas Solutions
Document ID                     : uuid:37efb1bf-fd50-4513-b1f0-5c25d9b17d79
Instance ID                     : uuid:1604055d-0290-4d52-93f9-12a507646460
Company                         : AuthorIT Software Corporation Ltd.
Comments                        : Copyright © 1996-2002 AuthorIT Software Corporation Ltd., all rights reserved.
Source Modified                 : D:20061030181701
Page Count                      : 32
Page Layout                     : OneColumn
Subject                         : Natural Gas Solutions
Author                          : 
Keywords                        : Revision, A
EXIF Metadata provided by EXIF.tools
FCC ID Filing: EO9100G

Navigation menu