Lifeline Systems 90-2359 Smoke Alarm User Manual Installation instructions

Lifeline Systems, Inc. Smoke Alarm Installation instructions

Contents

Installation instructions

Download: Lifeline Systems 90-2359 Smoke Alarm User Manual Installation instructions
Mirror Download [FCC.gov]Lifeline Systems 90-2359 Smoke Alarm User Manual Installation instructions
Document ID107654
Application ID/oKESOToUgfT+KMX03BT0A==
Document DescriptionInstallation instructions
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize11.87kB (148412 bits)
Date Submitted2000-07-04 00:00:00
Date Available2000-09-08 00:00:00
Creation Date2000-05-02 15:47:07
Producing SoftwareAcrobat Distiller 4.0 for Windows
Document Lastmod2000-05-02 15:47:08
Document TitleInstallation instructions

ESL 560 Series
3V Standalone Smoke Alarm
Installation Instructions
UL

CSFM
4300 Series
Wireless Smoke Alarm
LISTED
Description
Sounder vent
Optional temperature sensor
The ESL 560 Series smoke alarm is designed to be used
as a standalone smoke alarm.
Depending on the model, the smoke alarm provides the
following features:
Smoke Alarm/base lock discourages unauthorized
removal of the smoke alarm by requiring a screwdriver
to remove the alarm from the base.
Optional integrated fixed 135°F temperature and
rate of rise heat alarm trips an alarm based on temperature detected.
Test/Silence button
LED
CleanMe™ Self-diagnostics (when UL listed with a
transmitter) monitors its own sensitivity and operational
status. If the smoke alarm drifts out of the UL listed
sensitivity range or fails internal diagnostics, it extinguishes its LED.
Figure 1 - Smoke Alarm Features
Selecting a Location
Selecting a suitable location is critical to the operation of
smoke alarms. This equipment should be installed in
accordance with the National Fire Protection
Association’s (NFPA) Standard 72. See Figure 2.
Internal Signal Outputs
When the smoke alarm is listed with a transmitter it
provides the following signals for interfacing:
•
•
•
•
•
Alarm
Alarm restore
Low battery
CleanMe™
Maintenance alert
TV Room
Bedroom
Dining
Room
A-8-1.2.1.C Are More Smoke Alarms Desirable?
The required number of smoke alarms might not provide
reliable early warning protection for those areas separated by a door from the areas protected by the required
smoke alarms. For this reason, it is recommended that
the householder consider the use of additional smoke
alarms for those areas for increased protection. The
additional areas include the basement, bedrooms, dining
room, furnace room, utility room, and hallways not
protected by the required smoke alarms. The installation
of smoke alarms in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these
locations occasionally experience conditions that can
result in improper operation.
Kitchen Bedroom
Bedroom
Living Room
Bedroom
Dining
Room
Living
Room
Important: Regulations pertaining to smoke alarm
installations vary from state to state. For more information, contact your local fire department or local authority
having jurisdiction.
Bedroom
Basement
= Required smoke alarms
= Additional smoke alarms required for new construction
Figure 2 - Smoke Alarm Placement
In addition to NFPA 72, use the following location
guidelines to optimize performance and reduce the
chance of false alarms from the alarm:
• Locate ceiling-mounted smoke alarms in the center of
a room or hallway at least 4 inches from any walls or
partitions.
• Locate wall-mounted smoke alarms so the top of the
alarm is 4 to 12 inches below the ceiling.
Knockout
• Locate in a suitable environment as follows:
- Temperature between 40°F (4.4°C) and 100°F (37.8°C)
- Humidity between 0 and 95% non-condensing
• Locate away from air conditioners, heating registers
and any other ventilation source that may interfere
with smoke entering the alarm.
Knockout
Figure 3 - Base Lock Knockouts
• Mount smoke alarms on a firm permanent surface.
• Locate away from large metallic objects when listed
with a transmitter.
Tab
Installing the Alarm
Slot
1. If you are using the alarm/base lock, remove the two
knockouts on the mounting base. See Figure 3.
2. Slide the battery compartment cover away from the
alarm to unsnap it and lift it off. See Figure 4.
Battery
compartment
3. Observing proper polarity, insert two 3V lithium
batteries into the alarm battery compartment and
replace the battery compartment cover.
Figure 4 - Smoke Alarm-to-Base Alignment
smoke entry openings.
4. Remove the red plastic dust cover from the alarm.
The alarm is shipped with a dust cover for protection
on construction sites with dusty environments.
2. Gently direct the smoke into the alarm for 20 seconds
or until an alarm is indicated.
5. Using the two screws and anchors provided, mount
the base.
BE SURE TO PROPERLY EXTINGUISH THE
SMOKE SOURCE AFTER TESTING! The alarm LED
should remain on and the alarm will sound a temporal
rhythm until the Test/Silence button is pressed. The
alarm automatically resets when smoke is no longer
present.
6. Attach the alarm to the mounting base as follows:
- Line up the raised tab on the lip of the alarm with
the slot on the lip of the mounting base. See
Figure 4.
- Insert the smoke alarm into the base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
Understanding the Test/Silence Button
The Test/Silence button on the alarm performs three
functions as follows:
Important: The alarm cannot be attached to the
mounting base if no batteries are installed.
Testing = Press the Test/Silence button for 2 seconds.
The alarm performs a sounder test and a sensitivity test.
7. Test the alarm (see Smoke Testing the
Alarm).
Silence alarm = Press to silence the sounder during an
alarm. After a few minutes, the sounder and alarm
resume if smoke is still present.
Smoke Testing the Smoke Alarm
Smoke alarms should be tested in place annually using
smoke or canned aerosol simulated smoke. Follow the
instructions on the canned smoke or use the following
steps to test the alarm with smoke:
Silence trouble chirp = Press to silence a trouble chirp.
The trouble chirp resumes after 24 hours if the trouble
condition is not corrected.
1. Hold a smoldering punk or cotton wick close to the
Testing the Alarm Sensitivity
The smoke alarm provides a sensitivity level test mode that allows you to check the smoke alarm sensitivity using the
Test/Silence button and the LED indicator on the alarm as follows:
1. Press the Test/Silence button on the smoke alarm for 2 seconds. Once the test starts, the alarm LED flashes one to
nine times.
2. Count the number of times the LED flashes and use the following table to determine the status of the smoke alarm
sensitivity and what action to take, if any.
Flashes
Obscuration
%/ft (approx)
Indication
Action
N/A
Reset unit and rerun sensitivity test. If the error persists, replace the unit.
2, 3
N/A
8, 9
3.1
2.6
2.1
1.6
N/A
Unserviceable hardware
fault detected.
Detector is not sensitive
enough.
Detector is within normal
sensitivity range.
Detector is too sensitive.
Verify that the smoke chambers is snapped down securely. Clean the unit and replace the
smoke chamber.
Clean the unit. Reset unit and rerun sensitivity test. If the error persists, replace the unit.
N/A
After the flashes, if the sensitivity is within limits and all other tests pass, the alarm goes into alarm and
resets after 5 seconds.
If the sensitivity is not within limits, or an unserviceable hardware fault has been detected, the smoke alarm LED
extinguishes until the alarm is serviced.
Attaching and Removing the Smoke
Alarm
To remove the smoke alarm from the mounting
base, grasp the alarm and turn it counterclockwise
approximately 15 degrees. The smoke alarm should snap
off of the mounting base.
To remove the alarm from the mounting base when
the alarm/base lock is used, insert a small screwdriver
into the locking tab slot on the side of the base and press
in while simultaneously turning the alarm counterclockwise 15 degrees. See Figure 5.
Alarm/base lock
Attach the smoke alarm to its mounting base as
follows:
- Line up the raised tab on the lip of the smoke alarm
with slot on the lip of the mounting base. See
Figure 4.
Figure 5 - Smoke Alarm/Base Lock
- Insert the smoke alarm into the base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
When to Replace the Batteries
The 560 Series smoke alarm requires two 3V lithium A
batteries as listed on the battery compartment cover.
The required batteries are available where other batteries
are sold.
Understanding the LED
The LED on the alarm indicates the status of the alarm
as follows:
Battery life is a minimum of 1 year and varies depending
on how often the alarm is tested. When the batteries are
low, the alarm extinguishes its LED and chirps every 30
seconds until the batteries are replaced. The sounder
can be silenced for 24 hours by pushing the Test/Silence
button.
FLASHING = Flashes every 9 seconds to indicate
normal operation.
ON = Detects smoke.
OFF = Trouble or maintenance is required.
Replacing the Batteries
Use only 3V lithium A batteries as listed on the battery
compartment cover.
1. Remove the alarm from the mounting base. See
Attaching and Removing the Alarm.
2. Slide the battery compartment cover away from the
alarm to unsnap it and lift it off. See Figure 4.
3. Remove the batteries and dispose of properly.
Figure 6 - Removing Alarm Cap
4. Observing correct polarity, insert two new 3V lithium
batteries into the battery compartment and replace the
cover.
5. Reattach the alarm to the mounting base. See Attaching and Removing the Alarm.
Smoke
chamber
latch
6. Test the alarm (see Smoke Testing the Alarm).
Cleaning the Alarm
HE
RE
Clean the alarm cover with a dry or damp (water) cloth as
needed to keep it free from dust and dirt.
SQ
UE
EZ
Optical base
When necessary, clean the alarm interior and replace the
smoke chamber as follows:
Indentation
Smoke
chamber
Alarm
cap
1. Remove the alarm from its mounting base. See Attaching and Removing the Alarm.
Figure 7 - Alarm Parts
2. Remove the batteries. See Replacing the Batteries.
3. Slide a flat-blade screwdriver in the slot on the alarm
cap and gently push the handle down to pry the cap up
and off. See Figure 6.
Maintaining the Alarm
The 560 Series smoke alarms are designed for easy field
service and maintenance. When installed and used
properly, they require minimal maintenance.
4. Press in on the sides of the smoke chamber and pull it
up and away from the alarm and discard. See
Figure 7.
The smoke alarm should be tested weekly. See Testing
the Alarm Sensitivity and Smoke Testing the Alarm.
When a 560 Series alarm listed with a transmitter
requires maintenance, it extinguishes its LED and
initiates the external signals described in the following
table.
5. Blow out or use a soft-bristled brush to remove dust and
dirt from the smoke chamber base.
6. Line the new smoke chamber up with the smoke
chamber base and snap down into place.
7. Replace the alarm cap as follows:
-Line the cap up with the smoke alarm.
-Insert the cap into the smoke alarm and turn
clockwise approximately 15 degrees. It should
snap firmly into place.
8. Observing the proper polarity, put the batteries back in
the alarm and replace the battery compartment cover.
9. Reattach the alarm to its mounting base. See Attaching
and Removing the Alarm.
Signal
Maintenance required
CleanMe
Smoke detector sensitivity is out of range and
needs cleaning. See Cleaning the Detector.
Maintenance aler t
Detector failed to power up on self test. Perform a
sensitivity test. See Testing the Detector
Sensitivity. If the problem persists, replace the
detector.
Low battery
Batteries in the detector are low. Replace the
batteries.
If the 560 alarm is used as a standalone detector, refer to
Testing the Alarm Sensitivity.
10.Test the alarm sensitivity (See Testing the Alarm
Sensitivity).
✄
Fire Prevention and Escape
The purpose of an early warning smoke alarm is to detect the presence of fire in its early stages and sound an alarm
giving the occupants time to exit the premises safely.
Be Prepared
Practice the following steps to prepare you and your
family in the event of a fire:
Avoid Fire Hazards
No detection device can protect life in all situations.
Therefore, safeguards should be taken to avoid potentially dangerous situations as follows:
• Perform fire drills regularly. Use them to assure
recognition of an alarm signal.
• Do not smoke in bed
• Do not leave children home alone
• Draw a floor plan and show two exits from each
room. It is important that children be instructed
carefully, because they tend to hide in times of crisis.
• Never clean with flammable liquids such as gasoline.
Detach and leave with the end user
• Properly store materials. Use general good housekeeping techniques to keep your home neat and tidy.
A cluttered basement, attic, or other storage area is
an open invitation to fire.
• Establish one meeting place outside the home. Insist
that everyone meet there during an alarm. This will
eliminate the tragedy of someone reentering the house
for a missing member who is actually safe.
• Use combustible materials and electrical appliances
carefully and only for their intended uses. Do not
overload electrical outlets
• If you have children and/or physically challenged
people residing in your household, use window decals
to help emergency personnel identify the sleeping
quarters of these individuals.
• Do not store explosive and/or fast burning materials
in your home.
• Even after proper precautions have been taken, fires
can start. Be prepared.
In Case of Fire
In the event of a fire, you should do the following:
• Leave immediately. Don’t stop to pack or search for
valuables.
Smoke alarms CANNOT provide warnings
for fires resulting from explosions, smoking
in bed or other furniture, ignition of flammable liquids, vapors and gases, children
playing with matches or lighters.
• In heavy smoke, hold your breath and stay low, crawl
if necessary. The clearest air is usually near the floor.
• If you have to go through a closed door, carefully feel
the door and door knob to see if undue heat is present.
If they seem cool, brace your foot against the bottom
of the door with your hip against the door and one
hand against the top edge. Open it slightly. If a rush
of hot air is felt, slam the door quickly and latch it.
Unvented fire tends to build up considerable pressure.
Be sure all members of the household realizes and
understands this danger.
• Use your neighbor’s phone or a street fire alarm box
to call the fire department. The job of extinguishing
the fire should be left to the professionals.
✄
WARNING
ESL is a brand name of Sentrol. The manufacturer warrants
this smoke alarm (except batteries) to be free from defects in
material and workmanship under conditions of normal use for
a term of 3 years from the date of manufacture.
During the warranty period, if a Sentrol product or any of its
components becomes defective, it will be repaired or replaced
without charge.
Out-of-warranty units will be repaired at the discretion of the
manufacturer, if not, a card will be forwarded to the customer
suggesting a replacement unit and the cost of that unit.
✄
LASTS, OR THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO
THE ABOVE LIMITATIONS AND EXCLUSIONS
MAY NOT APPLY TO YOU. UNLESS A LONGER
PERIOD IS REQUIRED BY APPLICABLE LAW, ANY
ACTION AGAINST MANUFACTURER IN CONNECTION WITH THIS SMOKE ALARM MUST BE
COMMENCED WITHIN ONE YEAR AFTER THE
CAUSE OF ACTION HAS OCCURED.
Limited Warranty
No agent, employee or representative of the Manufacturer
nor any other person is authorized to modify this warranty in
any respect. Repair or replacement as stated above is the
exclusive remedy of the purchase hereunder. This warranty gives you specific legal rights and you also have other
rights which vary from state to state.
This warranty does not apply to units which have been
subject to abuse, misuse, negligence or accident, or to which
any modifications, alterations or repairs have been made or
attempted.
WARNING! LIMITATIONS OF SMOKE ALARMS
This warranty is extended only to the original purchaser of the
smoke alarm and may be enforced only by such person.
During the warranty period, if the alarm or any warranted
components thereof becomes defective, at the
manufacturer’s discretion, it will be replaced or repaired
without charge if returned in accordance with the following
instructions:
Wireless smoke alarms are very reliable, but may not work
under all conditions. No fire alarm provides total protection
of life or property. Smoke alarms are not a substitute for
life insurance.
Obtain a Return Authorization Number by calling 1-800-6487422 or 503-692-4052, then carefully pack it in a well padded
and insulated carton and return, postal charges prepaid to:
Smoke alarms may not be heard. A sound sleeper or
someone who has taken drugs or alcohol may not may not
awaken if the alarm is installed outside a bedroom. Closed
or partially closed doors and distance can block sound. This
alarm is not designed for the hearing impaired.
Customer Service
Sentrol
12345 SW Leveton Drive
Tualatin, OR 97062-9938
A note should be included advising the nature of the malfunction. Care must be exercised in the proper packing of alarms
returned under this warranty as Sentrol will not be responsible
for warranty repairs to equipment damaged because of
improper packing.
Smoke alarms may not always activate and provide
warning early enough. Smoke alarms only activate when
enough smoke reaches the alarm. If a fire starts in a
chimney, wall, roof, on the other side of closed doors, or on
a different level of the property enough smoke may not
reach the alarm for it to alarm.
THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER
EXPRESS WARRANTIES, AND IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE LIMITED IN DURATION FOR A PERIOD OF 3 YEARS FROM THE DATE
OF MANUFACTURE. UNDER NO CIRCUMSTANCES
SHALL MANUFACTURER BE LIABLE TO THE
PURCHASER OR ANY OTHER PERSON FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY
NATURE, INCLUDING WITHOUT LIMITATION
DAMAGES FOR PERSONAL INJURY OR DAMAGES
TO PROPERTY, AND HOWEVER OCCASIONED,
WHETHER ALLEGED AS RESULTING FROM
BREACH OF WARRANTY BY MANUFACTURER,
THE NEGLIGENCE OF MANUFACTURER OR OTHERWISE. MANUFACTURER’S LIABILITY WILL IN
NO EVENT EXCEED THE PURCHASE PRICE OF THE
PRODUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
Detach and leave with the end user
Smoke alarms require a source of power to work.
This smoke alarm will not operate and the alarm will not
sound if batteries are dead or not installed properly.
✄
SMOKE ALARMS ARE A SIGNIFICANT HELP IN
REDUCING LOSS, INJURY AND EVEN DEATH.
HOWEVER, NO MATTER HOW GOOD A DETECTION DEVICE IS, NOTHING WORKS PERFECTLY
UNDER EVERY CIRCUMSTANCE AND WE MUST
WARN YOU THAT YOU CANNOT EXPECT A
SMOKE ALARM TO ENSURE THAT YOU WILL
NEVER SUFFER ANY DAMAGE OR INJURY.
7
Specifications
Voltage..............................................................3VDC
Typical average standby current .......................... 25m A
Typical test current.............................................. 2mA
Typical alarm current ......................................... 70mA
Battery life................................................1 year (min)
Battery type ...3V lithium, DuracellÒ DL123A, MN1500
..............SanyoÒ and PanasonicÒ CR123A
..........................Eveready EnergizerÒ E91
Low battery threshold.......... low battery signal at 2.70V
Sounder ........................... 85dB at 10' temporal pattern
Low battery beep rate ...............1 every 30 sec. ± 2 sec.
Sensitivity ............................................... 2.3% ±0.8%
Operating temperature ................40°-100°F (4.4°-37.8°C)
Operating humidity..................... 0-95% non-condensing
Color ..................................................................white
Alarm dimensions ........ 5.5" x 2.3" (14 cm x 5.6 cm)
Base dimensions ........4.88" x 0.38" (12.3 cm x 0.95 cm)
Drift compensation adjustment ................ 0.5%/ft. max.
Heat alarm specifications (T models):
Rate of rise........15°F/min>105°F (8.3°C/min>40.6°C)
Fixed ...........................135°F ± 5°F (57.2°C ± 2.8°C)
Listings ................................................UL 217, CSFM
# of Batteries
Sounder
Series
UL Listing Category
Heat Type
Product Ordering
Model
Description
560S
3V standalone smoke alar m, 85dB sounder UL217 (OEM customers call for wireless compatibility)
562S
3V standalone smoke alar m, two 3V lithium batteries, 85dB sounder UL217 (OEM customers call for wireless
compatibility)
560ST
3V standalone smoke alar m, 85dB sounder, 135 degree fixed/rate of rise heat detector UL217 (OEM customers call for
wireless compatibility)
562ST
3V standalone smoke alar m, two 3V lithium batteries, 85dB sounder, 135 degree fixed/rate of rise heat detector
RL217 (OEM customers call for wireless compatibility)
Accessories
SM-200
Smoke! in a Can (canned smoke) for functional testing of smoke alar ms
SM-EXT 1
Smoke! in a Can extension tube
211
Replacement smoke chambers (set of 10)
SENTROL
ESL
product
of
sentrol
12345 SW Leveton Dr., Tualatin, OR 97062
Tel.: 503.692.4052 Fax: 503.691.7566
http://www.sentrol.com
Sentrol reserves the right
to change specifications
without notice.
©2000 Sentrol
U.S. & Canada: 800.547.2556
Technical Service: 800.648.7424
FaxBack: 1.800.483.2495
15515 Rev B 0400

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Create Date                     : 2000:05:02 15:47:07
Producer                        : Acrobat Distiller 4.0 for Windows
Modify Date                     : 2000:05:02 15:47:08-07:00
Page Count                      : 8
EXIF Metadata provided by EXIF.tools
FCC ID Filing: JOK90-2359

Navigation menu