Lutron Electronics 0118 Dimmer Module User Manual 20180912 v1 11 Install 041675a

Lutron Electronics Company Inc Dimmer Module 20180912 v1 11 Install 041675a

User Manual_20180912_v1 - 11_Install_041675a

Download: Lutron Electronics 0118 Dimmer Module User Manual  20180912 v1   11 Install 041675a
Mirror Download [FCC.gov]Lutron Electronics 0118 Dimmer Module User Manual  20180912 v1   11 Install 041675a
Document ID4007742
Application IDgilwMgxahPGxUKvngwe4NA==
Document DescriptionUser Manual_20180912_v1 - 11_Install_041675a
Short Term ConfidentialYes
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize120.1kB (1501274 bits)
Date Submitted2018-09-17 00:00:00
Date Available2018-09-21 00:00:00
Creation Date2018-08-09 08:48:58
Producing SoftwareAdobe PDF Library 10.0.1
Document Lastmod2018-08-09 14:48:04
Document TitleVive CE PowPak Dimming Module With 0-10 V Install 041610
Document CreatorAdobe InDesign CS6 (Windows)

Required Components
PowPak | Installation
Control Module with EcoSystem
041588
041675
Rev.
Rev.AA
08/2018
08/2018
Part of the Vive Family
Top LED
RMJS-ECO32-SZ
Customer Assistance www.lutron.com/support
For each system, ensure that you have:
One PowPak Control Module
At least one Wireless Transmitter
At least one EcoSystem LED Driver or Fluorescent Ballast
Consult third-party DALI fixtures installation guide for fixture-specific wiring. This device can
be installed on a fixture / troffer, junction box, or marshalling box using the conduit nut or with
mounting screws. The device must NOT be mounted inside a fixture / troffer or other metallic
enclosure. Improper installation can result in degraded wireless communication, intermittent or
sustained communication failures, and will not be covered under warranty. For mounting and
wiring best practices see Lutron Application Note #620 (P/N 048620).
Raise
120 – 277 V~ 50 / 60 Hz 80 mA
Toggle
Lower
EcoSystem Control: 18 V- 64 mA
Cal.
Link
Test
Bottom LED
•
•
•
PowPak Control Module with EcoSystem
(1 maximum)
Radio Powr Savr Occupancy/Vacancy Sensor
(10 maximum)
Mount, Wire, and Install EcoSystem
Devices and Lighting Fixtures
(1 maximum)
64 mA for the control lines. May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must comply with the
limits for a Class A device, pursuant to Part 15 of the FCC rules.
E1
E2
To additional EcoSystem fixtures
PowPak
Control
Module
EcoSystem to Fixtures
C Use the Toggle “ u” , Raise “▲” and Lower “ ” buttons to verify
Sample LED
driver shown
DALI
E2
HOT
MAINS
–
E2 (Violet/White)
B Once installed, energize the PowPak Control Module with EcoSystem.
NEU
Line/Hot
Radio Powr
Savr Occupancy
Sensor
E1 (Violet)
fixture / troffer, junction box, or marshalling box using the conduit nut
(provided) or with mounting screws (not provided). Please consult local
and national electric codes for proper installation.
B Connect EcoSystem control to each fixture.
E1
Neutral (White)
A The PowPak Control Module with EcoSystem can be installed on a
A Connect mains wiring (hot, neutral) to each fixture.
Line / Hot (Black)
Install PowPak Control Module with
EcoSystem
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
Install in center of room
to maximize RF coverage.
English
Consult third-party device installation guide
PowPak
Control Module
Pico
Remote
Control
(10 maximum)
Radio Powr Savr Daylight Sensor
Start Here
Neutral
9m
maximum
Pico Remote Control
Δ
•
•
•
•
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 0 °C and 40 °C (32 °F and 104 °F) ambient.
0% to 90% humidity, non-condensing.
For indoor use only.
control wiring.
Wire Gauge
Maximum DALI-compliant
Bus Wire Length
1.5 mm2 (14 AWG)
0.75 mm2 (18 AWG)
0.5 mm2 (20 AWG)
300 m
150 m
100 m
Programming with a Vive Hub
A Use an iOS or Android compatible device.
Vive
B Download the Lutron Vive app.
C Open the app and follow the instructions.
vive.lutron.com
All Wireless Transmitters must be installed within
9 m (30 ft) of the PowPak Control Module with
EcoSystem.
Note: For further information on set up, programming, and troubleshooting with a Vive
system, please refer to the installation instructions included with the Vive hub or visit
www.lutron.com/vive
Note: For programming the PowPak Control Module with EcoSystem without a Vive hub
see reverse side.
Default Functionality
Occupancy Sensors
Occupied: All lights 100%.
Unoccupied: All lights off.
Troubleshooting
Ballasts cannot be controlled locally from PowPak Control Module
with EcoSystem.
Daylight Sensor
All lights dim in response to daylight.
Cal.
Link
Test
Wireless Controls
On
All lights 100%
Favorite All lights 50%
Off
All lights off
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
www.lutron.com /vive
• Ensure that the breaker(s) to the PowPak Control Module are energized.
• Ensure that the EcoSystem control lines are wired to the lighting fixture(s).
Reset to factory defaults.
Lights do not dim as expected.
• Ensure that EcoSystem control lines are wired properly.
Lights do not respond to Wireless Transmitter(s).
• Ensure that the breaker(s) to the PowPak Control Module with EcoSystem and drivers/ballasts are energized.
• Ensure that Wireless Transmitters are associated to the PowPak Control Module with EcoSystem.
Reset to factory defaults.
Lights are unstable at low‑end or flash/flicker at turn-on or turn-off. • Adjust the low-end trim.
Wireless Transmitter(s) cannot be associated to PowPak Control
Module with EcoSystem.
• The maximum number of Wireless Transmitters have been associated to the PowPak Control Module with EcoSystem. To remove a previously set up Wireless
Transmitter, tap a Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
A
Part of the Vive Family
Start Here
Associate Wireless Transmitters to
PowPak Control Module with EcoSystem
Before beginning this step, make sure that there are no
other PowPak modules being set up within the same
building. It is possible that wireless transmitters from other
systems can be incorrectly associated to this module.
A On PowPak Control Module with
EcoSystem, hold Toggle button
“ u” for 6 seconds until lights
flash.
Daylight Sensor will control all wired fixtures equally.
Press and release the “Cal.” button on the Daylight Sensor.
Set lights in room to desired light level.
Press and hold the “Cal.” button for 6 seconds.
Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Control Module with EcoSystem must be used.
For detailed setup refer to the tuning section of the Radio Powr Savr Daylight Sensor installation
guide.
Test
• Select the PowPak Control Module with EcoSystem that you want to adjust by pressing the Toggle button.
Both LEDs will begin flashing
twice per second.
Set a Favorite Light Level (Optional)
For Pico remote controls with a Favorite Button.
Raise
Lower
A Adjust lights to desired level:
Use the Raise button “ ” or Lower button “ ” on the Pico remote
control.
B Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will flash
3 times to confirm that the Favorite level is saved.
B Hold the indicated button on each transmitter for
6 seconds. Lights will flash to show that wireless
transmitters have been associated. LEDs also flash on
successful association.
Favorite
Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before performing the
following procedures.
		 Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim may
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the
PowPak Control Module with EcoSystem and connected
devices back to factory default settings. Before beginning,
make sure that all devices are connected and powered.
A Triple-tap the Toggle button “ u” on the PowPak Control
Module with EcoSystem and hold until both LEDs begin to
flash slowly; release button.
B Within 3 seconds of the start of flashing, triple‑tap the same
button again and the LEDs will flash rapidly indicating that the
unit has been reset to factory defaults.
Note: Any associations or programming previously set
up with the PowPak will be erased and will need to be
re‑programmed.
		 Low-End Trim
A	Enter low-end trim adjustment mode:
		Press and hold the Lower button “ ” on the fixture control for 12 seconds.
		 The lights will flash and the bottom LED will begin flashing.
B Adjust the low-end trim:
		 Use the Raise button “▲” and Lower button “ ” on the control module to adjust and set the lights
to the desired low-end (0.1 to 45%).
C	Save the low-end trim:
		Press and hold the Toggle button “ u” for 6 seconds to save setting.
		 The bottom LED will begin flashing and then turn solid to indicate new level has been saved.
		 High-End Trim
A Enter high-end trim adjustment mode:
		Press and hold the Raise button “▲” on the fixture control for 12 seconds.
The lights will flash and the top LED will begin flashing.
B	Adjust the high-end trim:
		 Use the Raise button “▲” and Lower button “ ” on the control module to adjust and set the lights
to the desired high-end (55 to 100%).
C Save the high-end trim:
		 Press and hold the Toggle button “ u” for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Δ
C On PowPak Control Module with EcoSystem, hold
Toggle button “ u” for 6 seconds to save association.
Lights will return to high end and LEDs will stop
flashing.
D Permanently install wireless transmitters
(consult individual component installation guides for
information).
Δ
Test
need to be adjusted.
• T
 rim low-end to ensure a stable light level because some loads will flicker or drop out
if trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any abnormal
operation.
• The factory default high-end trim is suitable for most applications but can be adjusted
as desired.
Set Occupancy Light Levels (Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
A Set desired occupancy light levels:
Use Raise/Lower buttons “▲/ ” on the PowPak Control Module with EcoSystem or Raise/
Lower buttons “ / ” on all associated Pico Remote Controls.
B Save occupancy light levels:
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor
without a Lights On button. Release when Sensor lens starts to flash.
Δ
Cal.
Link
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas,
activate Minimum Light Level mode.
A Enter minimum light level adjustment mode:
Press and hold Toggle button “ u” and Lower button “ ” for 12 seconds. Lights will flash
high‑low‑high and both LEDs will begin flashing.
If lights stop flashing and turn off, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
B Change the minimum light level:
Press Raise button “▲” to set minimum light level to low-end.
Press Lower button “ ” to set minimum light level to OFF.
C Save the minimum light level:
Press and hold Toggle button “ u” for 6 seconds. Both LEDs will quickly flash to indicate that new
level has been saved.
Cal.
Link
Set Minimum Light Level (Optional)
Δ
Calibrate the Radio Powr Savr Daylight Sensor
Δ
Control Module with EcoSystem
Customer Assistance www.lutron.com/support
Δ
PowPak | Installation
Programming without a Vive Hub
Customer Assistance:
TEL: +1.844.LUTRON1
FAX: +1.610.282.1243
www.lutron.com/support
Limited Warranty: www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause
undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Lutron, Pico, and PowPak are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. App Store is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license.
Android, Google Play and the Google Play logo are trademarks of Google Inc. DALI is a trademark of ZVEI. ©2013 – 2018 Lutron Electronics Co., Inc.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Create Date                     : 2018:08:09 08:48:58-04:00
Creator                         : Adobe InDesign CS6 (Windows)
Modify Date                     : 2018:08:09 14:48:04-04:00
Has XFA                         : No
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.4-c006 80.159825, 2016/09/16-03:31:08
Format                          : application/pdf
Title                           : Vive CE PowPak Dimming Module With 0-10 V Install 041610
Description                     : Vive CE PowPak Dimming Module With 0-10 V
Subject                         : Lutron, Vive, PowPak, Dimming, Module, With 0-10 V, Instal, RMJS-8T-DV-B, URMJS-8T-DV-B, Radio Powr Savr, Pico, Occupancy, Vacancy, Toggle, 041610, 041-6108
Metadata Date                   : 2018:08:09 14:48:04-04:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:9d08ce8e-103d-4a7f-970d-4d1e284857a9
Original Document ID            : xmp.did:02AB66CE700AE71187AAEF8587D1D504
Document ID                     : xmp.id:4337EF74D29BE811AC2880A3FB279971
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:4237EF74D29BE811AC2880A3FB279971
Derived From Document ID        : xmp.did:014168C48649E8118368BAE9A4D5A1B8
Derived From Original Document ID: xmp.did:02AB66CE700AE71187AAEF8587D1D504
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2018:08:09 08:48:58-04:00
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 2
EXIF Metadata provided by EXIF.tools
FCC ID Filing: JPZ0118

Navigation menu