Motorola Solutions 89FT4888 PIU AND PIU-XR OF DIOS User Manual Distributed I O System Owner s Manual

Motorola Solutions, Inc. PIU AND PIU-XR OF DIOS Distributed I O System Owner s Manual

Contents

Users Manual

Download: Motorola Solutions 89FT4888 PIU AND PIU-XR OF DIOS User Manual Distributed I O System Owner s Manual
Mirror Download [FCC.gov]Motorola Solutions 89FT4888 PIU AND PIU-XR OF DIOS User Manual Distributed I O System Owner s Manual
Document ID1155102
Application IDAJQYP3NkKvLjk01e4ZYODw==
Document DescriptionUsers Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize224.5kB (2806207 bits)
Date Submitted2009-08-18 00:00:00
Date Available2009-08-18 00:00:00
Creation Date2009-06-03 15:40:42
Producing SoftwareAcrobat Distiller 8.1.0 (Windows)
Document Lastmod2009-07-23 15:25:08
Document TitleDistributed I/O System Owner's Manual
Document CreatorAcrobat PDFMaker 8.1 for Word
Document Author: Motorola

Owner’s Manual
Distributed I/O
SystemPiccolo Interface
Unit (PIU) and
Piccolo-XR Unit
6802974C40-R
MOTOROLA and the Stylized M Logo are registered in the U.S.
Patent and Trademark Office. All other product or service names
are the property of their respective owners.
Copyright © 2009 Motorola
All Rights Reserved
6802974C40-R
@6802974C40@
COMMERCIAL WARRANTY (STANDARD)
Motorola radio communications products are warranted to be free from defects
in material and workmanship for a period of ONE (1) YEAR, (except for crystals
and channel elements which are warranted for a period of ten (10) years), from
the date of shipment. Parts, including crystals and channel elements, will be
replaced free of charge for the full warranty period but the labor to replace
defective parts will only be provided for one Hundred-Twenty (120) days from
the date of shipment. Thereafter purchaser must pay for the labor involved in
repairing the product or replacing the parts at the prevailing rates together with
any transportation charges to or from the place where warranty service is
provided. This express warranty is extended by Motorola Communications and
Electronics Inc., 1301 E. Algonquin Road, Schaumburg, Illinois 60196, to the
original purchaser only, and only to those purchasing for purpose of leasing or
solely for commercial, industrial, or governmental use.
THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES
EXPRESS OR IMPLIED WHICH ARE SPECIFICALLY EXCLUDED,
INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT SHALL MOTOROLA BE LIABLE
FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES TO THE FULL EXTENT
SUCH MAY BE DISCLAIMED BY LAW.
In the event of a defect, malfunction or failure to conform to specifications
established by seller, or if appropriate, to specifications accepted by Seller in
writing, during the period shown, Motorola, at its option, will either repair or
replace the product or refund the purchase price thereof, and such action on
the part of Motorola shall be the full extent of Motorola’s liability hereunder.
This warranty is void if:
a.
the product is used in other than its normal and customary manner;
b.
the product has been subject to misuse, accident neglect or damage;
c.
unauthorized alterations or repairs have been made, or unapproved parts
used in the equipment.
This warranty extends only to individual products, batteries are excluded, but
carry their own separate limited warranty. Because each radio system is
unique, Motorola disclaims liability for range, coverage, or operation of the
system as a whole under this warranty except by a separate written agreement
signed by an officer of Motorola.
Non-Motorola manufactured products are excluded from this warranty, but
subject to the warranty provided by their manufacturers, a copy of which will be
supplied to you on specific written request.
To obtain performance of this warranty, purchaser should contact a Motorola
salesperson, or Motorola at the address shown above, attention: Quality
Assurance Department.
This warranty applies only within the United States.
COMPUTER SOFTWARE COPYRIGHTS
The Motorola products described in this instruction manual may include
copyrighted Motorola computer programs stored in semi conductor memories
or other media. Laws in the United States and other countries preserve for
Motorola certain exclusive rights for copyrighted computer programs including
the exclusive right to copy or reproduce in any form the copyrighted computer
program. Accordingly, any copyrighted Motorola computer programs contained
in the Motorola products described in this instruction manual may not be copied
or reproduced in any manner without the express written permission of
Motorola. Furthermore, the purchase of Motorola products shall not be
deemed to grant either directly or by implication, estoppel, or otherwise, any
license under the copyrights, patents or patent applications of Motorola, except
for the normal non-exclusive, royalty free license to use that arises by operation
of law in the sale of a product.
EUROPEAN UNION DIRECTIVE 2002/95/EC CONFORMANCE STATEMENT
Hereby, Motorola declares that these products are in compliance with the
essential requirements and other relevant provisions of Directive 2002/95/EC Restriction of Hazardous Substances Directive.
This page left intentionally blank.
CONTENTS
CONTENTS................................................................................ I
INTRODUCTION....................................................................... 1
Scope of this Manual ......................................................................1
General Description........................................................................1
Safety Handling Instructions.........................................................5
INSTALLATION ........................................................................ 7
General ............................................................................................7
PIU Installation...............................................................................8
Mounting the PIU On A Wall Using Screws................................9
Mounting the PIU Using a Bracket.............................................10
PIU DIN Rail Mounting...............................................................11
PIU Electrical Connections..........................................................12
PIU Antenna Connection .............................................................18
Piccolo–XR Installation ...............................................................19
Piccolo–XR Screw Mounting Options ........................................20
Piccolo–XR Electrical Connections.............................................22
THE DIOS PIU AND PICCOLO-XR UNITS ............................ 27
PIU Overview................................................................................27
PIU Communication Ports...........................................................28
PIU Connectors.............................................................................29
PIU LED Operation .....................................................................29
PIU Adapter Operation ...............................................................30
Piccolo-XR Overview ...................................................................35
Piccolo-XR Communication Ports ..............................................35
Piccolo-XR Connector..................................................................36
Contents
APPENDIX A: PIU and PICCOLO-XR SPECIFICATIONS.... 37
PIU Specifications.........................................................................37
Environmental ................................................................................37
Mechanical .....................................................................................37
PIU Board.......................................................................................38
Power..............................................................................................39
PICCOLO XR Specifications ......................................................42
Environmental ................................................................................42
Mechanical .....................................................................................42
PICCOLO XR Board......................................................................42
Communication Ports .....................................................................43
Power..............................................................................................44
Regulatory Standards ..................................................................46
Radio
Network Freq Band Rated Power .......................46
APPENDIX B: MODELS and ACCESSORIES...................... 49
General ..........................................................................................49
APPENDIX C: ANTENNA ...................................................... 51
General ..........................................................................................51
Flexible Antenna Specifications ..................................................51
Pole Antenna .................................................................................52
Pole Antenna installation .............................................................53
APPENDIX D: PIU/PICCOLO–XR MOUNTING TEMPLATES
................................................................................................. 57
ii
INTRODUCTION
Scope of this Manual
This manual provides instructions for the installation and
operation of the Distributed I/O system Piccolo Interface Unit
(PIU) and Piccolo–XR units. The Distributed I/O System
includes PIUs and Piccolo–XRs. Each PIU can be linked to up
to 256 Piccolo–XRs. For more information on the PIU and
Piccolo–XR, see the online help of the DIOS Service Toolkit.
General Description
The Distributed I/O System (DIOS) is a self-sustained system
designed to function within the IRRInet irrigation control
product line.
The DIOS consists of the following components:

Piccolo Interface Unit (PIU)

Piccolo–XR Units
The PIU functions as an interface between the host application
(irrigation SW and HW) and the Piccolo–XR units. The PIU
and Piccolo-XR are portable devices, which are used in fixed
installations. The PIU uses one of its communication ports to
link to the host application and radio communication to link to
the Piccolo–XR units. Figure 1 provides a general view of the
DIOS System.
Introduction
IRRInet Field
Unit
Piccolo
Interface
Unit
RS485
or
RS232
PIU
Piccolo-XR Units
I/O's
Figure 1
DIOS –General System View
The battery-operated Piccolo–XR unit is available in various
models with different options of Inputs and Outputs. The
Piccolo–XR unit can operate DC latch solenoids (outputs), read
status and calculate flow of dry contact meters (inputs).
The units are equipped with built-in radio for communication
with the PIU.
The DIOS automatically builds communication network, using
Store and Forward (S&F) technology, enabling the DIOS to
cover areas larger than normally possible when using a single
radio to communicate with the PIU.
Using the DIOS, the IRRInet system opens and closes stations
(manually or automatically by irrigation programs), reads dry
contact input status, calculates flow rate and accumulates
pulses from water meters.
Introduction
PIU - Piccolo Interface Unit
The Piccolo Interface Unit (PIU; see Figure 2) is connected to
the IRRInet Field Unit (FU) via RS232
or RS485 serial ports.
Each PIU supports up to 256 Piccolo–XR units, with any
available I/O combination, limited by the capacity of the
IRRInet software only.
Utilizing the S&F technology and networking capabilities, the
PIU can be linked to Piccolo–XR units positioned in distances
of up to 1500-2000 meters (approx. 1 mile), depending on
topography, antenna type and antenna installation.
The PIU is an interface between the Piccolo–XR and the
IRRInet FU, which provides communication and networking
operations only. (Monitor and control features are not included
in the PIU.) That is: The control and monitor functions are
provided either locally, by the Piccolo–XR or by an upper
hierarchy unit (i.e. IRRInet FU).
The PIU is a portable device, which is used in fixed
installations enclosed in an indoor plastic housing.
The PIU must be installed by qualified and authorized
technicians, so as to meet applicable safety standards and to
ensure protection against weather hazards for the unit.
If the PIU will be connected to outdoor lines, an interface unit,
complying with Clause 6 of the UL 60950 standard must be
provided.
Introduction
Figure 2
PIU – General View
Piccolo–XR
The Piccolo–XR is an intelligent, microprocessor based unit
that can be used to monitor and control local units in a multi
unit communication network. Piccolo–XR units communicate
data to a PIU while functioning as intelligent nodes in
Distributed I/O monitor and control systems. The Piccolo–XR
is often used in irrigation and water distribution systems (i.e.
irrigation valves, water meters, fertilizing meters, various
sensors, flushing filters, and other non-irrigation devices).
The Piccolo–XR is ideal for use in applications where very low
power consumption is essential. The Piccolo–XR is also
available in an outdoor resistant housing (IP66), designed to
resist harsh environment, such as exposure to sun, dust, and
pouring rain.
Introduction
Figure 3
Piccolo XR –General View
Safety Handling Instructions
For safety handling instructions, see the Product Safety and RF
Energy Exposure Booklet for PIU and Piccolo XR Units,
Motorola publication no. 6802974C70, which is distributed
with the devices.
The radio frequency band used by the DIOS system has not
been harmonized throughout the entire European Economic
Area (EEA).
Introduction
This page left intentionally blank.
INSTALLATION
General
SAFETY SUMMARY
Caution
Caution
The PIU and Piccolo–XR must be installed by
qualified and authorized technicians, specifically
qualified to handle high voltage if the installation
involves high-voltage connections/installations.
If the PIU will be installed outdoors, an outdoor
plastic housing complying with UL60950 standard
clause 6 is required.
Note!
See Piccolo–XR Screw Mounting Options
(page 20) for mounting details.
Note!
This equipment is tested with specified length
cables and in standard enclosure. If longer cables
or a different enclosure are used, the installer is
responsible to ensure that the installation
complies with the requirements of the applicable
standards.
Installation
PIU Installation
PIU Dimensions
The unit dimensions are (see Figure 4):
 Width – 4.25" (108 mm),
Height – 4.96" (126 mm),
Height including antenna – 11.46" (291.1 mm),
Depth – 1.67" (42 .6mm),
Weight – 0.558 lb (253g) maximum.
42. .67"
6m
4.96”
126 mm
5"
4.2 m
108
11.46 "
291.1mm




Figure 4
Dimensions of PIU Unit
The PIU is enclosed in a plastic housing, allowing 3 mounting
options:

Wall mount (Screws)

Bracket mount

DIN rail mount
Installation
Before installing the PIU, verify that there is sufficient space
around the unit according to the specific installation.
Mounting the PIU On A Wall Using Screws
1. Secure two screws (not supplied) of maximum 0.37"
(9.5 mm) head size to the wall, 3.256" (82.7 mm) apart.
The wall-mounting template in Appendix D can be
used to determine the space between both screws.
2. The screws must not protrude from the wall surface by
more than 0.23” (6 mm) or by less than 0.16" (4 mm).
3. Attach the unit to the wall, fitting the two key hole
shaped cavities on the back cover of the unit over the
screws and sliding it down. (See Figure 5.)
1.19"
30.3mm
3.26"
82.7 mm
Figure 5
PIU Installation– Screw Mount dimensions
Installation
Mounting the PIU Using a Bracket
1. Using four M3x6 or M3x8 screws, attach a bracket
(not supplied) to the back of the PIU. The upper two
bracket holes must be 3.19" (81 mm) apart, and the
lower two bracket holes must be 2.40" (61 mm) apart
and 2.13" (54 mm) below the upper holes, as shown in
Figure 6.
2.13"
54mm
2. Attach the bracket to the mounting surface.
2.40"
61 mm
3.19"
81mm
Figure 6
PIU Installation– Bracket Mount dimension
10
Installation
PIU DIN Rail Mounting
To mount the PIU on a DIN rail (not supplied), slide the PIU
onto the rail at the grooves on the back of the unit. See Figure 7
and Figure 8.
Figure 7
DIN Rail Attachment – Back View
Figure 8
DIN Rail Attachment – Front View
11
Installation
PIU Electrical Connections
NOTE! Verify that all power connections are made in
accordance with the applicable local standards.
PIU Ground Connections
Use the FKN8254B cable to connect the grounding cable
directly to the TB connector of the PIU as shown in Figure 9.
NOTE! The grounding connector is also used as an
ON/OFF switch, and the unit cannot be powered on
without connecting it.
Grounding Cable
(FKN8254B)
Ground
Figure 9
PIU Ground connection
12
Installation
Power Connection
The PIU can be powered by various types of supply sources:

Internal (9VDC) battery;

External 6V or 12V DC battery;

Motorola power supplies – controllers. For example:
IRRInet XL, IRRInet XM, IRRIcom, MOSCAD;
 24VAC.
NOTE! The unit DC voltage range is 6 to 16 volts.
9VDC Internal Battery
Incorrect replacement of the battery can result in
explosion! Replace only with the same or with an
equivalent type of battery recommended by the
Caution
manufacturer.
Dispose of used batteries according to the battery
manufacturer instructions.
Place a standard 9VDC alkaline battery (not supplied) into the
PIU battery chamber (see Figure 10). Battery operation is
applicable when operating the unit in a non-radio mode, e.g.
when the PIU is used as an adapter.
13
Installation
Installation of an Internal Battery
1. Release the screw at the top of the battery chamber
door, and slide the door out, as shown in Figure 10.
2. Connect the 9V battery cable (FKN8204B) to the DC
power input connector on the back of the unit.
3. Connect the 9V DC battery to the cable.
4. Place the 9V DC alkaline battery in the chamber as
shown in Figure 10.
5.
Close the battery chamber door and secure with the
screw.
Screw Battery
Chamber Door
Figure 10
PIU Battery Chamber
14
Battery
Chamber
Battery
Installation
External Battery Power Connections
Caution
The unit must be powered by a limited power
source (12V DC) in accordance with standard
UL/IEC 60950-1. See Power in Appendix A below.
This connection is used for normal operation of the PIU, when
radio communication is required, or when RS485 or RS232
ports are used.
1. Release the screw at the top of the battery chamber
door and slide the door out, as shown in Figure 10.
2. Connect the DC Adapter board (FCN6538B) to the DC
power input connector on the back of the unit (Figure
11).
3. Connect the FKN8250B 7 ft cable to the DC Adapter
board.
4. Connect the other cable end to an external 12VDC
battery through 1A fuse (not supplied).
5. Close the battery chamber door and secure with the
screw.
DC adapter board
FCN6538B
DC power in
FKN8250B
1A Fuse
Figure 11
PIU Unit – Rear View with DC Adapter
15
Installation
External Power Supply Connections
Use the applicable cable from the V152AH PIU installation kit
to connect the PIU to Motorola standard controller power
supply.
1. Release the screw at the top of the battery chamber
door and slide the door out, as shown in Figure 10.
2. Connect one end of the cable to the DC power input
connector on the back of the unit.
3. Connect the other end of the cable to the power supply
output of a Motorola controller.
4. Close the battery chamber door and secure with the
screw.
16
Installation
24VAC Power Connections
Caution
Caution
The PIU must be connected to a power source
equivalent to one or more of the following:
a. A listed Direct plug-in unit.
b. A Class II power source (defined by the
National Electrical Code (NEC) and the
Canadian Electrical Code (CEC).
c. A power source that complies with UL1950
C1.2.1 or UL60950 C1.2.5.
The unit must be powered by a limited power
source (24V AC) in accordance with the UL/IEC
60950-1 standard. See Power in Appendix A
below.
1. Connect the FKN8264B cable to the 24 V AC PWR IN
connector as shown in Figure 12.
2. Connect the other end of the cable to the 24 V AC
connection of a 110 V AC/220 V AC transformer (not
supplied) through a 1 A fuse (not supplied).
AC Cable
FKN8264B
1A Fuse
24
AC
110/220 V AC
Figure 12
24VAC Power In Connection
17
Installation
PIU Antenna Connection
Flexible Antenna: Attach the flexible monopole antenna to the
antenna connector at the top of the unit. See Appendix C for
detailed information.
Pole Antenna: Attach the FKN8258B antenna cable to the
antenna connector at the top of the unit. Connect the other end
of the antenna cable to a customer-supplied pole antenna. See
Appendix C for detailed information.
18
Installation
Piccolo–XR Installation
Piccolo–XR Dimensions
The unit dimensions are (see Figure 13):
 Width – 4.6" (117 mm)
 Height – 5.00" (127 mm)
 Hight including antenna – 11.46" (291.1 mm)
 Depth –1.63" (41.5mm)
4.6 m
7m
11
5.00”
127 mm
1.
41. 63"
5m
11.46"
291.1mm
 Weight – 0.54 lb (240 gr) maximum.
Figure 13
Dimensions of the Piccolo–XR Unit
19
Installation
The Piccolo–XR unit can be attached to any vertical or
horizontal surface using screws. Before mounting the Piccolo–
XR, verify that sufficient clearance is left around the unit.
Allow 8" (20 cm) clearance off the bottom of the Piccolo–XR
case for the user cable and 6.3" (16 cm) off the top of the unit
for the flexible antenna.
Piccolo–XR Screw Mounting Options
Mount the Piccolo–XR on a vertical surface as follows:
Secure the unit to any vertical surface using one 0.35"
(9 mm) maximum head screw. Use the mounting hole
marked A in Figure 14 to attach it to the mounting surface.
See Figure 15 B.
Mount the Piccolo–XR on a horizontal surface as
follows:
Secure the unit to any horizontal surface using two 0.35"
(9 mm) maximum head screws. Use the mounting holes
marked B and C in Figure 14 to attach it to the mounting
surface. See Figure 15 A.
Mount the Piccolo–XR on a wide plane as follows:
Secure the unit to any plane using three 0.35" (9 mm)
maximum head screws. Use all three mounting hole marked A,
B and C in Figure 14 to attach it to the mounting surface. See
Figure 15 C.
20
Installation
54 mm
3x
4.
75
98mm
49mm
Figure 14
Piccolo–XR Mounting Screw holes – Back View
Figure 15
Piccolo–XR Mounting Options
21
Installation
Piccolo–XR Electrical Connections
NOTE! Verify that all power connections are made in
accordance with the applicable local standards.
Wire (1)-Red
Wire (2)-Black
1A Fuse
User Cable-FKN8199B
+ -
6 V DC Battery
Wire (17)-Yellow
I/O's
Ground
Figure 16
Piccolo–XR Ground and DC Power Connections
Piccolo–XR Ground Connections
Connect the yellow wire (17) of the FKN8199B user cable to
the PGND, as shown in Figure 16.
22
Installation
Power Connections
Caution
The unit must be powered by a limited power
source (6V DC) in accordance with standard
UL/IEC 60950-1. See Power in Appendix A below.
The Piccolo–XR is powered by an external 6V DC battery
source.
Use the FKN8199B cable to connect the Piccolo–XR to an
external battery. Connect Wire #1 (red) to the positive (+) pole
of the battery through a 1A fuse (not supplied) and wire #2
(black) to the battery negative (–) pole. See Figure 16.
I/O Connections
The Piccolo–XR RTU can control up to four DC Latch
Solenoids.
The solenoid operating voltage can vary in the range of +9 to
+20V DC (defined by the site configuration definition in the
DIOS Service Toolkit).
The Piccolo–XR also responds to back indication signals from
a maximum of eight different field input sensors.
The available I/O module options are as follows:

1 DI / 1 DO

2 DI / 2 DO

4 DI / 4 DO

7 DI / 1DO

8 DI / 0DO
23
Installation
User Cable-FKN8199B
Solenoids
Output
Common
Wire (9) Gray
Sensors
Input
Common
Wire (6) Green
Figure 17
Piccolo–XR I/O Connections
NOTE!
24
For proper operation, the Piccolo–XR unit must be
connected either to a flexible antenna or to a pole
antenna. See Appendix C for antenna installation
details.
Installation
Table 1: Pin assignment of the Piccolo–XR user cable
(FKN8199B) Connector
PIN No
COLOR
DESCRIPTION
Red
Battery 6V (+)
Black
Battery 6V (–)
Brown
Solenoid 2
Orange
Input 4
White
Input 6
Green
Input Common *
Blue
Solenoid 3
Violet
Solenoid 4
Gray
Solenoid Common*
10
Pink
Solenoid 1
11
Light Green
Input 1
12
Black/White
Input 2
13
Brown/White
Input 3
14
Red/White
Input 5
15
Orange/White
Input 7
16
Green/White
Input 8
17
Yellow
PGND (Chassis)*
Note! The Input Common, Output Common and Ground are
INDEPENDENT.
25
Installation
Table 2: Pin assignment of the Piccolo–XR user cable
(FKN8199B) Connector
DESCRIPTION
PIN No
COLOR
Input 1
11
Light Green
Input 2
12
Black/White
Input 3
13
Brown/White
Input 4
Orange
Input 5
14
Red/White
Input 6
White
Input 7
15
Orange/White
Input 8
16
Green/White
Input Common
Green
Solenoid 1
10
Pink
Solenoid 2
Brown
Solenoid 3
Blue
Solenoid 4
Violet
Solenoid Common
Gray
Battery 6V (+)
Red
Battery 6V (–)
Black
PGND (Chassis)
17
Yellow
26
THE DIOS PIU AND PICCOLO-XR
UNITS
PIU Overview
The PIU unit (see Figure 18) is comprised of the following:
•
Internal radio interfaces and a radio modem
•
A logic board
•
Communication ports
LEDs
24V AC PGND/
RS485
Pwr IN DC Switch
Adaptor RS232
Port
Figure 18
PIU Unit General View
27
The DIOS PIU and Piccolo-XR Units
DC Power In
Figure 19
PIU Unit DC Power Connection– Rear View
PIU Communication Ports
The PIU has four ports:
NOTE! Only one of the two RS ports (232 and 485) can be
operated at a time, i.e. they do not operate
together.
28
•
RS485: Communication between multiple PIU units
and
the FU.
•
RS232: Communication between the PIU and the FU;
Configuration Port (unit programming and
monitoring).
•
Adapter port: Communication with and programming
the Piccolo-XR units.
•
Internal Radio interface: internal DPSK modem.
The DIOS PIU and Piccolo-XR Units
PIU Connectors
The PIU connectors (see Figure 18):
•
RS232
(RJ45, 8 pin)
•
RS485
(RJ10, 4 pin)
•
Adapter port
(RJ10, 4 pin)
•
PGND And Power Switch
(TB 3 pin)
•
24 V AC PWR IN
(2 pin)
•
6, 9, 12 V DC Battery Input
(2 pin)
PIU LED Operation
Three software programmable LED indicators are located on
the PIU enclosure (see Figure 18). These indicators can be used
for diagnostics purposes.
•
Radio TX/RX (RED): ON – a valid frame is received
by the internal DPSK modem or the PIU transmits a
frame.
•
RS232/RS485 RX/TX (ORANGE): ON – a valid
frame is received or transmitted through the
RS232/RS485 port (UART1).
•
Adapter port TX/RX (GREEN): ON – a valid frame is
received or transmitted through the adapter port
(UART2), or the Radio is being programmed.
29
The DIOS PIU and Piccolo-XR Units
PIU Adapter Operation
The PIU can be used as an adapter to perform the following
functions:
•
Communicating with the Piccolo–XR for
configuration, monitoring or hardware test.
•
Downloading new software to a Piccolo–XR unit.
•
Downloading new software to a PIU unit.
Communicating With a Piccolo–XR Unit
1. Connect the PIU adapter RS232 port to the computer
with the FTN6597B cable (see Figure 20).
2. Connect the PIU adapter unit to an external 12VDC
battery or to an internal 9V battery. (See page 12 for
power options).
IMPORTANT: Ensure that there is a 20 cm safety
distance between the PIU adapter unit and the user’s
body when connecting the battery.
3. Use the Distributed I/O Service Toolkit to turn off the
radio’s power.
4. Connect the Piccolo–XR unit to an external 6VDC
power source. (See Power Connections on page 23.)
5. Use the P5 connector (communication) of the
FKN8171B cable to connect the Piccolo–XR unit to
the Adapter port of the PIU unit.
6. Use the Distributed I/O Service Toolkit to configure
and monitor the Piccolo–XR or to test its hardware.
For additional information, please refer to the online help of the
DIOS Service Toolkit.
30
The DIOS PIU and Piccolo-XR Units
Piccolo-XR
+ -
PIU Adapter
+ -
P5
P4
Communication
Cable
Toolkit PC
RS232
RS232
To PC
Connectors
GND
RS485
Adapter To
Piccolo XR
Figure 20
PIU Adapter – Piccolo–XR Communication Mode
Connections
NOTE! The grounding connector is also used as an ON/OFF
switch, and the unit cannot be powered on without
connecting it. (See Figure 9.)
31
The DIOS PIU and Piccolo-XR Units
Downloading new software to a Piccolo–XR unit
1. Connect the PIU adapter RS232 port to the computer
using the FTN6597B cable (see Figure 21).
2. Connect the PIU adapter unit to an external 12VDC
battery or to an internal 9V battery. (See page 12 for
power options).
3. Connect the Piccolo–XR unit to an external 6 V DC
power source. (See Power Connections on page 23.)
4. Use the P4 connector (programming) of the
FKN8171B cable to connect the Piccolo–XR unit to
the Adapter port of the PIU unit.
5. Use the Distributed I/O Service Toolkit Downloader.
For additional information, please refer to the online help of the
DIOS Service Toolkit.
Piccolo-XR
+ -
PIU Adapter
+ -
P4
P5
Programming
Cable
Toolkit PC
RS232
RS232
To PC
Connectors
GND
RS485
Adapter To
Piccolo XR
Figure 21
PIU Adapter – Piccolo–XR Downloading Mode
Connections
NOTE! The grounding connector is also used as an ON/OFF
switch, and the unit cannot be powered on without
connecting it. (See Figure 9.)
32
The DIOS PIU and Piccolo-XR Units
Communicating with a PIU unit
1. Connect the PIU unit RS232 port to the computer with
the FTN6597B cable (see Figure 22).
2. Connect the PIU unit to an external 12VDC battery or
to an internal 9V battery. (See page 12 for power
options.)
3. Use the Distributed I/O Service Toolkit for
configuration, monitoring or hardware test.
For additional information, please refer to the online help of the
DIOS Service Toolkit.
PIU
+-
Toolkit PC
RS232
RS232
To PC
Connectors
GND RS485 Adapter
Figure 22
PIU Adapter – PC Communication Connections
NOTE! The grounding connector is also used as an ON/OFF
switch, and the unit cannot be powered on without
connecting it. (See Figure 9.)
33
The DIOS PIU and Piccolo-XR Units
Downloading new software to a PIU
1. Connect the PIU adapter RS232 port to the computer
with the FTN6597B cable (see Figure 23).
2. Connect the PIU adapter to an external 12VDC battery
or to an internal 9V battery. (See page 12 for power
options).
3. Connect the PIU unit to an external 12VDC battery or
to an internal 9V battery. (See page 12 for power
options.)
4. Use the FKN8203B cable to connect the Adapter port
of the PIU adapter to the RS232 connector of the PIU
unit to be programmed.
5. Use the Distributed I/O Service Toolkit Downloader.
For additional information, please refer to the online help of the
DIOS Service Toolkit.
PIU unit
+ -
PIU Adapter
+ -
Programming
Cable
Toolkit PC
RS232
Connectors
GND RS485
Connectors
GND
RS485
Adapter
RS232
To PC
Adapter To RS232 of
Programmed PIU
RS232 To Adapter of
Programming PIU
Figure 23
PIU Adapter Programming Mode Connections
NOTE! The grounding connector is also used as an ON/OFF
switch, and the unit cannot be powered on without
connecting it. (See Figure 9.)
34
The DIOS PIU and Piccolo-XR Units
Piccolo-XR Overview
The Piccolo -XR Remote Terminal Unit (RTU) is comprised
of:
¾ Logic board, which includes:
• I/Os
• Radio interface
• Power supplies
• Communication ports
¾ Radio
26 pin
Connector
Figure 24
Piccolo-XR Unit
Piccolo-XR Communication Ports
The Piccolo-XR has three ports:
•
Programming port: for downloading SW.
•
UART Port: Configuration Port (for programming and
monitoring the unit)
•
Internal Radio interface: internal DPSK modem.
35
The DIOS PIU and Piccolo-XR Units
Piccolo-XR Connector
The Piccolo -XR has one D-type 26 pin connector (see
Figure 24). See Table 1 and Table 2 on pages 25–26 for more
information
Input/Output options
A variety of I/O options is available for use with the
Piccolo-XR, increasing the system flexibility.
The available Piccolo-XR I/O options are:
•
1 DI / 1 DO
•
2 DI / 2 DO
•
4 DI / 4 DO
•
7 DI / 1DO
•
8 DI / 0DO
For option numbers, see Appendix B below.
36
APPENDIX A: PIU and PICCOLO-XR
SPECIFICATIONS
PIU Specifications
Environmental
Operating Temperature
-30 C to +60 C (-22 F to +140 F)
Storage Temperature
-40 C to +85 C (-40 F to + 185 F)
Relative Operating
Humidity
Operating Altitude
0 to 95% without condensation
@ +50 C (122 F)
-400 m to +4000 m
(-1300 ft to 13,000 ft) above sea level
Mechanical
Dimensions
126x108x42.6 mm  1 mm
(4.96"x4.25"x1.67")
Weight
253 gr  25 gr (0.56 lb  0.06 lb)
User Connection
RS232
Adapter port
RS485
PGND and DC switch
24 VAC
6V, 9V, 12V DC
BAT IN
(RJ45)
(RJ10)
(RJ10)
(TB 3 PIN)
(Molex header
2 PIN)
(Straight 2 PIN)
37
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
PIU Board
Communication Ports
RS232
Serial RS-232
RS485
Multi Drop 2 Wire
Adapter
Serial interface between PIU as
adapter and PICCOLO–XR
(UART levels)
Boot-Strap
Software programming port
Internal Radio
RF Frequency
UHF 450–470 MHz (actually
450.0125-469.9875) OR
UHF 430-450 MHz (actually
430.0125-449.9875) * **
(Service Toolkit programmable)
Duty Cycle ratio
< 10% (relative to a 1 hour period
for ISM band only)
Channel spacing
12.5 KHz
Internal Modem
DPSK 1200
TX RF Low power mode:
8 – 12 mW
@+25 C (+77 F)
(10 mW typical)
5 – 16.3 mW @–30 C - +60 C
(-22 F to 140 F)
TX RF High power
mode:
80 – 108 mW @+25 C (+77 F)
(100 mW typical)
50 – 108 mW @–30 C - +60 C
Frequency Error:
 1.5 ppm
Includes unlicensed ISM (intended for industrial, scientific and
medical purposes) band: Center frequency: 433.92 MHz, Frequency
range: 433.05–434.79 MHz (actually 433.0625-434.7875 MHz) in
Region 1. See Unlicensed Frequency Restrictions below.
**
Not including 443.95 MHz and 444.8625 MHz.
38
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
TX deviation:
2KHz  15%
RX BER
LEDs
BER<1% (See Note 5 on p. 41.)
Red, Orange, Green
(SW Programmable)
Power
Input Voltage
External Source
(DC Power In)
6.00 to 16.00 VDC e.g. lead acid
battery or solar panel, typically used
in irrigation systems.
External Source
(24V ~ IN)
24VAC±20%, typically from
transformer to 110VAC or 220VAC.
Power Modes
Adapter Mode (Using the internal 9 V battery)
Normal Operation
1 – 5 mA
(See Note 4 on p. 41.)
Sleep Mode
LPM0
LPM3
250 – 400 μA (See Note 1 on p. 41.)
140 – 290 μA (See Note 1 on p. 41.)
Power Fail Mode
LPM3
270 – 850 μA (See Note 3 on p. 41.)
39
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
PIU Mode (Using a 12 V or 6 V external power source)
Radio Transmission
(TX power-10 mW)
25 – 40 mA
65 – 90 mA
(PWR IN =14 V)
(PWR IN = 6 V)
(TX power-100 mW)
30 – 65 mA
85 – 135 mA
(PWR IN =14 V)
(PWR IN = 6 V)
13 – 18 mA
30 – 38 mA
(PWR IN =14 V)
(PWR IN = 6 V)
Standby current
Radio Receives
Sleep Mode
LPM0
LPM3
200 – 320 μA (See Note 2 on p.
41.)
130 – 250 μA (See Note 2 on p.
41.)
Power Monitors
Power OK Voltage
(Service Toolkit Adjustable Default
= 12 V DC)  200 mV
LOW Power Voltage
(Service Toolkit Adjustable Default
= 11.2 V DC)  200 mV
Very Low Battery
(Service Toolkit Adjustable Default
= 10.8 V DC)  200 mV
Reverse Input Voltage
Connection
40
Protected
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Note 1: Power In = 9 V DC (Adapter), RS232 = shutdown,
RS485 = disable, Radio (On Board Circuits) = off, internal
Radio is off. RS232 cable connected.
Note 2: Power Supply = 14 V DC (PIU), RS232 = shutdown,
RS485 = disable, Radio (On Board Circuits) = off, internal
Radio is off. RS232 cable connected.
Note 3: Power In = 5.4 V DC (Power fail), RS232 =
shutdown, RS485 = disable, Radio (On Board Circuits) = off,
internal Radio is off. RS232 cable connected.
Note 4: Power In = 9 V DC (Adapter), RS232 = auto
shutdown, RS485 = disable, Radio (On Board Circuits) = off,
internal Radio is off. RS232 cable connected.
Note 5: Apply 1.2 KHz FM signal with 2 KHz Deviation,
Sensitivity @–110 dBm to the radio, and read BER. At
extreme temperatures apply –104 dBm.
PICCOLO XR Specifications
Environmental
Operating Temperature
-30 C to +60 C
(-22 F to +140 F)
Storage Temperature
-40 C to +85 C
(-40 F to + 185 F)
Relative Operating
Humidity
0 to 95% without condensation
@ +50 C (122 F)
Operating Altitude
-400 m to +4000 m (-1300 ft to
13,000 ft) above sea level
Housing
IP66
41
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Mechanical
Dimensions
127x117x41.5 mm  1 mm
(5.00"x4.60"x1.63")
Weight
240 gr  24 gr (0.54 lb  0.05 lb)
User Connection
17 pin User Cable
(26 pin D-type connector)
Wire Gauge
22 AWG
PICCOLO XR Board
INPUTS:
Number of Inputs
Modularity: 1, 2, 4, 7, 8
Dry contact Input Ratings
Open: > 45 k (OFF)
Closed: < 6 k (ON)
Minimum pulse width
100 msec
Maximum pulse rate
7200 pulses per hour
OUTPUTS:
Number of Outputs
Modularity: 1, 2, 4
Output Drive Voltage
9 - 20 Volts (± 10%) (Service
Toolkit Adjustable)2200 µF capacitor
Output Short Circuit
Protection
>5 A
Communication Ports
42
UART 1 port
Serial port uart levels (Async.)
UART 2 port
Serial port UART levels (Async.)
Bootstrap Port
Software programming port
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Internal Radio
RF Frequency
UHF 450–470 MHz or
UHF 430-450 MHz * **
(Service Toolkit programmable)
Duty Cycle ratio
< 10% (relative to a 1 hour period
for ISM band only)
Channel spacing
12.5 KHz
Internal Modem
DPSK 1200
TX RF Low power mode:
8 – 12 mW
@+25 C (+77 F)
(10 mW typical)
5 – 16.3 mW @–30 C - +60 C
(-22 F to 140 F)
TX RF High power
mode:
80 – 108 mW @+25 C (+77 F)
(100 mW typical)
50 – 108 mW @–30 C - +60 C
Frequency Error
 1.5 ppm
TX deviation
2KHz  15%
RX BER
BER<1% (See Note 10 on p. 44.)
Power
Input Voltage
External Battery Source
4 to 7.8 V DC (See Note 11 p. 45.)
Power Consumption (6 V battery operation)
Normal Operating Mode:
Includes unlicensed ISM (intended for industrial, scientific and
medical purposes) band: Center frequency: 433.92 MHz, Frequency
range: 433.05–434.79 MHz (actually 433.0625-434.7875 MHz) in
Region 1. See Unlicensed Frequency Restrictions below.
**
Not including 443.95 MHz and 444.8625 MHz.
43
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Radio Transmission
Radio Off
1.2 – 1.5 mA (See Notes 6, 7 p. 44.)
(TX power-10mW)
65 – 90 mA
(TX power-100mW)
100 – 150 mA (See Notes 8, 9 p. 44.)
Radio Receives
30 – 40 mA
(See Notes 8, 9 p. 44.)
(See Notes 8, 9 p. 44.)
Sleep Mode
LPM0
LPM3
Power Fail Mode
LPM3
190 – 250 μA (See Note 7 p. 44.)
40 – 65 μA
(See Note 7 p. 44.)
40 – 70 μA
(See Note 6 p. 44.)
Power Monitors
Power In Report
 200 mV
Power OK Voltage
Service Toolkit Adjustable
Default = 6 V DC  200 mV
Low Power Voltage
Service Toolkit Adjustable
Default = 5 V DC  200 mV
Very Low Battery
Service Toolkit Adjustable
Default = 4.8 V DC  200 mV
Reverse Input Voltage
Connection
Protected
Note 6: Power In = 4 V DC, Radio (On Board Circuits) = Off,
internal Radio is off.
Note 7: Power In = 7.8 V DC, Radio (On Board Circuits) =
Off, internal Radio is off.
Note 8: Power In = 5.5 V DC, Radio (On Board Circuits) =
On, internal Radio is On.
Note 9: Power In = 7.8 V DC, Radio (On Board Circuits) =
On, internal Radio is On.
Note 10: Apply 1.2 KHz FM signal with 2 KHz Deviation,
Sensitivity @-110 dBm to the radio, and read BER. At
extreme temperatures apply -104 dBm.
44
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Note 11: For radio functionality external Power In minimum
voltage=5 V.
Unlicensed Frequency Restrictions
(For UHF 430-450 MHz radio only) When using a frequency
in the unlicensed ISM range (433.0625-434.7875 MHz, not
including 443.95 MHz and 444.8625 MHz), certain
regulatory restrictions apply:
Maximum transmit power
10mW (See Note 12 below.)
Maximum transmission time
1 sec (See Note 13 below.)
Channel occupation duty cycle
(total transmit time in any hour)
10% per hour (360 seconds)
(See Note 14 below.)
Transmission
Limited to quiet channel (See
Note 15 below.
Override
Not allowed
When Piccolo XR / PIU units are ordered in the unlicensed
ISM range (433.0625 - 434.7875 MHz), the radio will be
shipped after being programmed to 10 mW output power.
Note 12: Please note that due to the lower transmission
power, the distance between the Piccolo and the PIU is
shorter than the distance when using a licensed frequency
with 100 mW transmission power.
Note 13: The current consumption of the Piccolo will
increase due to the fact that the Maximum transmission time
is reduced and therefore the Piccolo should wake up more
frequently.
Note 14: The maximum number of transmissions from the
PIU/Piccolo is limited to 360 per hour. When this number is
exceeded, the PIU/Piccolo will stop transmitting until the
current hour has elapsed.
Note 15: The PIU/Piccolo will not transmit on a busy
channel. Verify that the frequency you choose in the band is
not continually busy.
45
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Regulatory Standards
US and Canada Grant of Equipment Authorization
IMPORTANT: Unauthorized repairs or modifications could
result in permanent damage to the equipment and void your
warranty and your authority to operate this device under Part
15 of the FCC Rules.
FCC Grant of Equipment Authorization
FCC ID: AZ489FT4888
FCC ID: AZ489FT4871
Industry Canada Grant of Equipment Authorization
ID: 109U-89FT4888
ID: 109U-89FT4871
This Class B digital apparatus complies with Canadian ICES003.
Radio
Network Freq Band
Rated Power
FM
UHF
430-450MHz
100mW
FM
UHF
450-470MHz
100mW
FCC INTERFERENCE
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1) This device may not cause harmful interference.
2) This device must accept any interference received,
including interference that may cause undesired operation.
For detailed product safety and RF exposure, refer to the
Product Safety and RF Energy Exposure Booklet for PIU and
46
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Piccolo XR Units, Motorola publication no. 6802974C70,
which is distributed with the devices.
European Union Notification
The CE mark is the official marking required by the European
Community for all Electric and Electronic equipment that will
be sold, or put into service for the first time, anywhere in the
European community.
It proves to the buyer or user that this product fulfills all
essential safety and environmental requirements as they are
defined in the European Directives.
The product approved for unlicensed band 433.05-434.79
mark.
Mhz is marked with the
The product approved for licensed band 430-450 MHz
marked with the following CE marks,
, carries
the alert symbol
to denote that the product band range
of 430-450 MHz is not harmonized in all EU member states.
Equipment Disposal
Waste (Disposal) of
Electronic and Electric
Equipment
Please do not dispose of Electronic and Electric Equipment or
Electronic and Electric Accessories with your household
waste. In some countries or regions, collection systems have
been set up to handle waste of electrical and electronic
equipment. In European Union countries, please contact your
local equipment supplier representative or service center for
information about the waste collection system in your
country.
47
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
Conformity for RoHS Compliance
This Motorola product is in compliance with the essential
requirements and other relevant provisions of Directive
2002/95/EC, Restriction of the use of certain Hazardous
Substances (RoHS) in electrical and electronic equipment.
48
APPENDIX B: MODELS and
ACCESSORIES
General
The following tables describe the available models, options
and accessories.
∗
DIOS Models
Model
Piccolo Interface Unit (PIU)
F4604B
Piccolo–XR DC
F4614B
PIU Options
Option
ADD: RS-485 Option (indoor)
V440AD
ADD: RS-232 Cable 3 m
V666AA
ADD: Antenna for PIU, 450-470 MHz
V208AJ
ADD: Antenna for PIU, 430-450 MHz
V208AL
ADD: PIU Adapter
V345AM
ADD: PIU DIOS Application
V377AD
INT: 12.5 KHz UHF Radio,
450–470 MHz
V347CT/
FLE6036C
INT: 12.5 KHz UHF Radio,
430–450 MHz ∗ **
V347CU/
FLE5532A
Includes unlicensed ISM (intended for industrial, scientific and
medical purposes) band: Center frequency: 433.92 MHz, Frequency
range: 433.05–434.79 MHz (actually 433.0625-434.7875 MHz)in
Region 1.
**
Not including 443.95 MHz and 444.8625 MHz.
49
Appendix B: Models and Accessories
Piccolo-XR Options
Option
ADD: 1 DI / 1DO Option
V608AE
ADD: 2 DI / 2DO Option
V379AK
ADD: 4 DI / 4DO Option
V118AJ
ADD: 7 DI / 1 DO Option
V115AN
ADD: 8 DI / 0 DO
V508AF
ADD: Antenna for Piccolo–XR,
450-470 MHz
V208AH
ADD: Antenna for Piccolo–XR,
430-450 MHz
V208AK
INT: 12.5 KHz UHF Radio,
450–470 MHz
V347CT/
FLE6036C
INT: 12.5 KHz UHF Radio,
430–450 MHz ∗ **
V347CU/
FLE5532A
Accessories
Kit number
TEC Programming & Monitoring Cable
(26 pin)
FKN8171B
Pole Antenna Kit (SMA TO SMA)
FAE5534B
Pole Antenna Kit (SMA TO N-TYPE)
FLN3373B
50
APPENDIX C: ANTENNA
General
The PIU and Piccolo–XR units can be connected either to a
flexible or to a pole antenna.
The antenna connector (see Figure 25), located at the top of the
unit, is used for both antenna types.
PIU
Antenna SMA Connector
Piccolo - XR
Antenna SMA Connector
Figure 25
PIU and Piccolo–XR Antenna Connectors
Flexible Antenna Specifications
Frequency Range:
Polarization:
Nominal Impedance:
VSWR:
Power Rating
Temperature Range:
UHF
Vertical
50 ohms
1.5:1 max at resonance
50 watts
-40ºC to +85ºC
51
Appendix C: Antenna
Pole Antenna
The pole antenna installation must comply with the following
requirements in order to ensure optimal performance and
guarantee that human exposure to radio frequency
electromagnetic energy is within the guidelines set forth by the
applicable local regulations.
The antenna must be mounted outdoors, preferably on a tower,
if possible.
Building mounted antennas must be located on the building
roof.
All fixed site antenna installations, including the installation of
this pole antenna, require that, under the responsibility of the
licensee, the installation site be managed in accordance with
the applicable regulatory requirements. This may require taking
additional compliance actions such as signage and site access
restrictions in order to ensure that human exposure limits are
not exceeded.
Figure 26
PIU/Piccolo–XR Pole Antenna
52
Appendix C: Antenna
Pole Antenna installation
SMA to SMA option
Antenna
Antenna
Support
Rubber
Washer
Nut
Lock
Washer
SMA Connector
Adjustable
Straps
SMA to SMA
Antenna Cable
Rubber
Sleeve
SMA Connector
Figure 27
SMA to SMA type PIU/Piccolo–XR Pole Antenna
1. Connect a flexible antenna to the antenna support plate
using rubber washers, lock washer and a nut (see
Figure 27).
2. Connect one end of the SMA cable to the antenna
connection.
3. Connect the other end to the PIU/Piccolo–XR.
53
Appendix C: Antenna
SMA TO N-TYPE
Antenna
Antenna
Support
Rubber
Washer
Nut
Adjustable
Straps
Nut
Lock
Washer
SMA Connector
N-Type
Connector
SMA to N-Type
Antenna Cable
N-Type
Washer
Figure 28
SMA to N-Type Pole Antenna
1. Connect a flexible antenna to the antenna support plate
using rubber washers, lock washer and a nut (see
Figure 28).
2. Connect the SMA end of the cable to the antenna
connection.
3. Connect the N Type end to the PIU/Piccolo–XR.
54
Appendix C: Antenna
Pole Antenna Dimension
83mm
200mm
91.5mm
174mm
Figure 29 shows recommended dimensions for a supporting
plate for the pole antenna.
200mm
270mm
Figure 29
PIU/Piccolo–XR Pole Antenna Supporting Plate
Dimensions
55
Appendix C: Antenna
This page left intentionally blank.
56
APPENDIX D: PIU/PICCOLO–XR
MOUNTING TEMPLATES
Use the following template for PIU wall mounting.
3.26"
82.7mm
Figure 30
PIU Wall Mounting Template (Full Size)
Figure 31
PIU Back
57
Appendix D: PIU/Piccolo – XR Mounting Templates
Figure 32
Piccolo–XR Mounting Template (Full Size)
58
1.93"
49mm
2.126"
54mm
3.86"
98mm
The following is a template that can be used for mounting the
Piccolo–XR unit.
MOTOROLA and the Stylized M Logo are registered in the U.S.
Patent and Trademark Office. All other product or service names
are the property of their respective owners.
Copyright © 2009 Motorola
All Rights Reserved
6802974C40-R
@6802974C40@
August 2009

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : Motorola
Create Date                     : 2009:06:03 15:40:42+03:00
Modify Date                     : 2009:07:23 15:25:08+03:00
Tagged PDF                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Metadata Date                   : 2009:07:23 15:25:08+03:00
Creator Tool                    : Acrobat PDFMaker 8.1 for Word
Format                          : application/pdf
Title                           : Distributed I/O System Owner's Manual
Creator                         : Motorola
Document ID                     : uuid:bd30d2ef-45a6-41e8-af60-8d3107959184
Instance ID                     : uuid:7a3ca47c-cba8-491b-87de-b3bde0b8284a
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Page Mode                       : UseOutlines
Page Count                      : 68
EXIF Metadata provided by EXIF.tools
FCC ID Filing: AZ489FT4888

Navigation menu