Users Manual
The Quick Install Guide for MGate W5x08 Gateway --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Connecting the Power The MGate W5X08 series gateway can be powered by connecting a power source to the terminal block, as follows: 1. Loosen or remove the screws on the terminal block. 2. Turn off the power source and then connect a 12–48 VDC power line to the terminal block. 3. Tighten the connections using the screws on the terminal block. 4. Turn on the power source. Note that the unit does not have an on/off switch. It automatically turns on when it receives power. The PWR LED on the top panel will glow to indicate that the unit is receiving power. Connecting Modbus/DNP3 Serial Devices The unit’s Modbus/DNP3 port(s) are located on the front panel. Use a Modbus/DNP3 serial cable to connect the unit directly to the Modbus/DNP3 devices. Before connecting or removing the Modbus/DNP3 connection, first make sure the power source is off. Connecting Modbus/DNP3 Network Devices The MGate W5X08 can be connected to the network via Ethernet port and WiFi with different IP addresses. The default IP addresses of Ethernet and WiFi are 192.168.126.254 and 192.168.127.254, respectively. Since your system may be using more than one MGate device and all MGate devices are configured with the same factory default IP address, you will first need to configure the MGate’s network settings. The MGate’s Ethernet ports are located on the front panel. The MGate will indicate a valid connection to the Ethernet in the following ways: • The Ethernet LED will glow a solid green color when connected to a 100 Mbps Ethernet network. • The Ethernet LED will glow a solid amber color when connected to a 10 Mbps Ethernet network. The Ethernet LED will flash when Ethernet packets are being transmitted or received. In General Settings, users can choose the routing criteria by Bridge mode setting when Ethernet and WiFi are both connected. When disable the bridge mode, Ethernet port will be the default routing path even WiFi is also connected. When enable the bridge mode, WiFi connection will be the default routing path even Ethernet port is connected. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com WLAN Settings The MGate W5X08 supports IEEE 802.11 a/b/g/n wireless function. The wireless function provides more convenient deployment of industrial equipments connecting to network. It has better scalability to meet the requirement of a variety of topologies according to user’s needs of wireless LAN system. Connection Settings The WLAN settings are classified into two types. The first one is “WLAN” setting which includes IP address/Network/Gateway and the method of acquiring IP address. The setting is for user to specify network address to run in the system. The second one is “Profile” which is used to configure the wireless connection settings including security parameters. There are two network types which is “Infrastructure” and “Adhoc mode.” When configured to “Adhoc mode”, it automatically detects and communicates directly with each other and do not require a wireless access point (AP) or gateway. If the MGate is configured to “Infrastructure”, it is accessed through a wireless access point. In the “Operation mode”, you can choose the MGate to operate in which wireless standard. The SSID is used to configure the SSID of access point. You can also get the SSID by “Site survey” button which will automatically search and list the SSID of APs nearby. The fast roaming is used for roaming among two APs with the same SSID when the wireless signal strength is stronger than the original attached one. The “Scan channel” is configured for fast roaming function to do the scanning of wireless signal. It is selectable only if “Fast roaming” is enabled. The list of selectable channels is different according to different operation mode. Security Settings For the security setting of “Infrastructure” mode, it must be the same as access point for authorization of communication. The authentication field specifies how wireless devices will be authenticated. Only authenticated devices will be allowed to communicate with the access point. The security setting of the wireless devices which are configured to “Adhoc mode” must be the same to communicate with each other. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com First Time Use Firstly, user can connect with the MGate device and search the unit by using the Device Search Utility. And then configure the MGate through web console. 1. Device Search Utility (called DSU in this instruction) In most situations, users do not know the IP address when setting up a new gateway or configuring an existing gateway. In these cases, users can use an Ethernet cable to connect a host computer and the gateway directly. If connecting the devices under the same Ethernet switch, make sure there is no router between them. The DSU can detect the network settings of the connected gateway for users properly. Once you found the device in the DSU’s device list, you can assign IP to the device, or export/import the configuration file, or upgrade the firmware to the device. For other gateway configuration, double-click the target device in the DSU and the web browser will pop-up for further setting. 2. Web Console Use the Web Console to configure the MGate or to verify the status of the MGate from a web browser. You may use Microsoft Internet Explorer or Google Chrome to connect to the MGate. To use this method, the IP address of the MGate must be configured correctly. Starting Device Search Utility The Device Search Utility (called DSU in this instruction) is a Windows-based utility that is used to configure MGate W5X08 series gateway units. Before running DSU, first connect your MGate W5X08 series gateway unit to your PC. To start DSU, from the Windows Start menu click Start Programs MOXA DSU DSU. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com The DSU window will appear as shown below. Search the Unit Two methods are available for establishing a connection with MGate: and 錯誤! 找 Search can be used to locate any connected MGate series units in the same network. Use the 錯誤! 找 錯誤! 找不到參照來源。 不到參照來源。. 不到參照來源。 option if you know the IP address of the unit. For example, the default IP of MGate W5X08 series gateway is 192.168.126.254 of the Ethernet interface and 192.168.127.254 of the WiFi interface when user receives a new unit. And this function is also useful when the MGate unit is not located on the same subnet as the PC, such as across a router. By executing the Search function, you will see the devices that is connected with you network. Once a device is been chosen, the executable functions will become choosable. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com To login to the intended device, double-click the device and a web browser will pop-out for detail setting. Type-in the Account name and password to login to the device. The default Account name and Password are “admin” and “moxa”. ATTENTION If 錯誤! 找不到參照來源。 fails to locate the MGate unit, the IP address that you entered might be incorrect. In this case, re-enter the IP address and try searching again. Another possibility is that the MGate unit could be located on the same LAN as your PC, but on a different subnet. In this case, you can modify your PC’s IP address and or netmask so that it is on the same subnet as the MGate unit. After your PC and the MGate are on the same subnet, DSU will be able to find the unit. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Configuration Once your login to the MGate unit through web console, you will see the overview of this MGate unit including the Model name, Serial No., Ethernet IP Address, WLAN IP Address, etc. Users can click the different configuration functions by the main menu in the left hand side. Protocol Setting The MGate W5X08 gateway has built-in with two serial ports, and users can define the protocol run on each serial port independently. There is three operation protocols can be chosen: Modbus, DNP3, and RAW TCP. Once you determine the protocol, click Submit to activate the change. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Protocol Settings The sub-clause Protocol Setting function shows the detail of the chosen protocol for each port. The shown web page will be different according to protocol assignment you choose. Example below is with Modbus protocol runs on serial port 1, and DNP3 protocol runs on serial port 2. Modbus setting There are four options can be chosen for Modbus setting: Mode, Slave ID, Priority Control, and Advanced Setting. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Mode Click the currently shown Modbus mode (RTU Master shown in previous figure) for each port for further setting. It includes the mode of the Connected serial device, Response timeout, Inter-character timeout, and Inter-frame delay. Parameter Connected serial device Response timeout Inter-character timeout Inter-frame delay Value RTU Slave, RTU Master, ASCII Slave, ASCII Master 10 – 120000 ms 10 – 500 ms, 0 for auto 10 – 500 ms, 0 for auto Default RTU Slave 1000 ms Connected serial device This field is to assign the role of the connected serial device, please refer to the manual of the serial devices for the setting. Response timeout This field is used to configure how long the gateway will wait for a response from a Modbus ASCII or RTU slave. This field is set independently for each serial port, which is selected through the “Protocol Assignment” field. Please refer to your device manufacturer’s documentation to manually set the response time-out. The MGate W5X08 series gateway also provides automatic calibration of the response timeout. Instead of manually figuring out the appropriate setting, you can click “Auto Detection” to have the MGate automatically figure out the time-out setting. Once a value has been recommended, you can fine-tune it for best performance. Inter-Character Timeout Use this function to determine the timeout interval between characters for Modbus devices that cannot receive Rx signals within an expected time interval. If the response is timed out, all received data will be discarded. Note that this timeout mechanism only works in RTU slave mode. The MGate W5X08 gateway will automatically determine the timeout interval if the timeout value is set to 0. Inter-Frame Delay In Modbus RTU slave mode, user can determine the time-delay to transmit the data frame received from the slave device to the upstream. The MGate W5X08 gateway will automatically determine the time interval if it is set to 0. Slave ID The Slave ID Map tab is where slave IDs are managed. The definitions on this tab determine how requests will be routed by the unit. Parameter Remote IP address TCP Port Slave ID Start Slave ID End Slave ID Offset Value (Max 40 characters) 0 - 65535 0 – 255 0 - 255 -255 ~ 255 --------------------------------------------------------------------------------------------------------------------------------- Default null null www.moxa.com info@moxa.com How Slave IDs are Mapped on the MGate W5X08 When a Modbus master requests information from a Modbus slave, the request is addressed to the desired slave's ID, which must be unique on the network. When Modbus networks are integrated by a Modbus gateway, complications can arise if the same slave ID is being used on different networks. If this is not properly addressed, a request sent to that slave ID would receive more than one response, causing communication problems. With the MGate MB3000, this situation is addressed by using a slave ID map. While configuring the MGate, users set up a range of "virtual" slave IDs that are mapped to slave devices on a specific Modbus network. To send a request to a slave that is on a different Modbus network, a master would address the request to the appropriate virtual slave ID. The MGate then routes that request as specified by the slave ID map. For example, if a TCP master needs information from an ASCII slave, it addresses the request to the corresponding virtual slave ID as defined on the MGate's slave ID map. The MGate identifies the request as within its virtual slave ID range and forwards the request to the Modbus ASCII network, this time addressed to the device's actual slave ID. Virtual slave IDs must not conflict with each other or with other TCP slave IDs. With the slave ID map, smart routing is achieved for units with multiple serial ports. Since each virtual slave ID is routed to a specific Modbus network, requests are not broadcast over all serial ports. This keeps communication efficient and prevents devices on one port from slowing down the whole system. How Slave ID Map is Defined The slave ID map consists of entries (channels) that specify a range of virtual IDs, the destination, and the offset value. The offset value is used to convert the virtual ID to the actual ID. Setting Value Virtual Slaves ID Range (numeric range from 1 to 254) Slave ID Offset (number between -253 and 253) Notes This specifies the range of IDs that will be routed to the selected set of slave devices. For example, you can specify that IDs between 8 and 24 be routed to the devices on Port 3. The ID 255 is reserved for the gateway itself This specifies the difference between the virtual slave ID and the actual slave ID. If a slave's virtual ID is 16 and the actual ID is 5, you would set the offset to -11. This offset is applied to the entire range of virtual slave IDs. When a serial port is set to RTU slave or ASCII slave mode, a virtual ID range will already be created for you. Simple select the entry in the table and modify the range and offset as needed. For TCP slaves, you can add an entry that assigns a range of virtual IDs to a specific IP address, using the Remote TCP Slave IP setting. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Slave ID Map Example Suppose you have two ASCII slave devices on port 1 assigned to slave IDs 3 and 5. The MGate will automatically create a virtual ID range for port 1, which you will need to modify. If slave IDs 3 and 5 are already in use by TCP slaves, the virtual ID range should be set to IDs that are not in use, such as 20 through 22. In that case, you would specify a slave ID offset of -17, since that is the difference between the virtual ID range and the actual slave IDs. The formula is as follows: (Real Slave ID) (Virtual Slave ID) (Slave ID Offset) 20 -17 With the slave ID map configured, a master that wants information from one of the ASCII slaves would address the request to slave ID 20 or 22. The MGate would identify that the request was addressed to a virtual slave ID in the slave ID map. The MGate would then forward the request to port 1, applying the -17 offset to obtain the actual ID of the desired device. Priority Control Priority control is designed for requests that are sent to Modbus RTU/ASCII slaves. Since Modbus RTU/ASCII slaves cannot handle multiple requests, the Modbus gateway must send each request individually and wait for the response before sending the next request. As requests stack up, the response time can suffer. This can cause problems for certain critical requests that require an immediate response. With priority control, you can specify that certain requests are sent to the front of the queue for more immediate response times. Priority requests can be specified by master (IP address or serial port), TCP port, or command type (slave ID, function code, or data). When the Modbus gateway identifies a priority request, the request will immediately be placed at the front of the queue. Parameter Specified TCP port TCP Port Specified Master Add Master Serial Port IP Address Specified request Slave ID Function code Data (RTU Format in Hex) Value Enable Disable 1024-65535 Enable Disable Serial Port (RTU/ASCII Master) IP Address (TCP Master) 1-2 Max 40 characters Enable Disable 0 - 255 0 - 255 Max 254 bytes Default Disable 7502 Disable Serial Port (RTU/ASCII master) null null Disable null null Advanced Settings Parameter Initial delay Modbus TCP exception Modbus TCP listen port Modbus TCP response timeout Slave ID Value 0 ~ 30000 ms Enable Disable 0 ~ 65535 10 ~ 120000 ms Default Disable 1 ~ 255 247 --------------------------------------------------------------------------------------------------------------------------------- 502 1000 www.moxa.com info@moxa.com DNP3 Settings There are three fields can be chosen for DNP3 setting: Mode, Address Table, and Advanced Setting. The default DNP3 listen port is 20000, and user can change it to other ports. In general, the MGate passively accepts connections from DNP3 masters or outstations; meanwhile, the MGate also supports actively connections to DNP3 masters or outstations. Mode Parameter Mode Value Outstation, Master Default Outstation Description Role of the DNP3 serial device. Address Table Address Table provides user to add the destination IP address and the DNP3 start/end address for the station to be communicated. When a DNP3 packet is received from network or serial side to the MGate, the MGate will route it to the defined destination according to the Address Table. If the destination is on serial side, the packet is sent to the corresponding serial port. If the destination is on network side, and the TCP connection to the destined station is already established, the DNP3 packet will be routed to that station. If the connection is not yet established, the MGate will establish a connection to the destined station and then send DNP3 packet to that station. The MGate will automatically generate the setting of serial port in address table. Users have to modify the setting of serial port by one clicking on the current shown DNP3 serial column and click Edit for modification. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Parameter Remote IP address TCP Port DNP3 address start DNP3 address end DNP3 address offset Advanced Settings Parameter Listen port Value Max 40 characters 1 - 65535 0 – 65519 0 - 65519 -65519 ~ 65519 Value 1 - 65535 Default null 20000 Default 20000 DI/DO The MGate W5X08 is built-in with 1 digital input and 1 digital output. The I/O connection methods are listed as below. Digital Input (Source Type) Dry Contact level ON State Short to GND OFF State Open Wet Contact level (COM to DI) ON State +10 ~ 30VDC OFF State 0 ~ +3V Digital Output (Sink Type) Driver current: Max.200 mA per Channel. On-state voltage: Max.30 VDC The wiring diagram is as shown below. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Configuration DI/DO can be monitored and controlled through Modbus command. The related Modbus parameters are listed below. Users can access the DI/DO through Modbus-based utility. Slave ID DI/DO Modbus Address (Base 0) Modbus Address (Base 1) Data Size Function Code DI1 0x0000 0x0001 1 bit 01: Read coils DO1 0x0010 0x0011 1 bit 255 05: Write single coil 15: Write multiple coils We use Modbus Poll shareware for demonstration. Related settings. DI --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com DO Users can change the slave ID or check the status of current DI/DO values via web console. Note that the latest version of MGate W5X08 will built-in with 2 DI and 2 DO. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com LED Indicator Type Color Green PWR1/PWR2 Off Green Ready Ethernet Link WLAN Red Off Green Amber Off Green RF (signal strength) Green P1/P2 (Serial signal) Green Amber Off Meaning Power is being supplied to power input PWR1, PWR2. Power is off, or power error condition exists. Steady On: Power is on and the gateway is functioning normally. Blinking: The gateway has been located by MGate Manager’s Location function. Steady On: Power is on and gateway is booting up. Blinking: Indicates an LAN IP conflict, or DHCP or BOOTP server did not respond properly. System power is off 100Mbps Ethernet connection 10Mbps Ethernet connection Ethernet cable is disconnected or has a short Steady on: Wireless enabled Blinking: Indicates a WLAN IP conflict, or that the DHCP or BOOTP server did not respond properly 3 LED = signal strength reach between 66%~100% 2 LED = signal strength reach between 33%~66% 1 LED = signal strength reach between 0%~33% Serial port is transmitting data Serial port is receiving data No data is communicating --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com Appendix --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com D. Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. CAUTION: Any changes or modifications not expressly approved by the grantee of this device could void the user’s authority to operate the equipment. Labeling requirements This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. RF exposure warning This equipment must be installed and operated in accordance with provided instructions and the antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter. End-users and installers must be provide with antenna installation instructions and transmitter operating conditions for satisfying RF exposure compliance. This radio transmitter FCCID: SLE-W5x08 has been approved by FCC to operate with the antenna types listed below with the maximum permissible gain and required antenna impedance for each antenna type indicated. Antenna types not included in this list, having a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with this device. Antenna List No. Manufacturer 1 KINSUN Part No. Antenna Type Peak Gain 6602D03081 Dipole 1.21 dBi for 2.4 GHz 1.73 dBi for 5 GHz Note: The antenna connector is Reverse SMA type. --------------------------------------------------------------------------------------------------------------------------------- www.moxa.com info@moxa.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 18 Producer : doPDF Ver 8.4 Build 935 Create Date : 2015:10:13 19:10:06+08:00EXIF Metadata provided by EXIF.tools