Open PDF In BrowserView PDF
PowerMatic® Low Energy Power Operator
ELS Upgrade Kit
Installation Instructions
80-9369-0170-020 (01-09)

The ELS Upgrade Kit may be used on 6600 POR/PAS and 6700 POR/PAS Series Low Energy
Power Operator regardless of arm application.
Upgraded Units will have the new user friendly features of a 6900 PowerMatic while eliminating
the components associated with the L1 and L2 Limit switches.
It is suggested the unit be installed to door frame and door and functioning properly in a manual mode. Door
should be able to be manually opened to the desired opening position and fully close under closer spring force.

6700 Series Unit
Shown

Same Unit with 6900 ELS
Upgrade installed

L2
L2 Switch
Cam

L1 Switch
Lever
L1 Switch
(Not Visible)

ELS
Dip
Switches

A

B

4 PAS
3 DN
2 T2
1 T1

ELS Board
LED

Pinion
Pulley
Timing Belt

L1 Switch
Adjustment
Screw

ELS Board w/
Potentiometer
X

X

Solenoid
L2 Cam
Hub

X

X

X

X

XX

Hand
Marking

Hand
Marking
Solenoid

L2 Cam
Screw

Door Calibrate Door Calibrate
11/16” Power Open Position Close Position
Adjustment Nut

11/16" Power
Adjustment Nut

ELS Modes and Functions:
Activation Modes (Modes are configured during installation.)
• Selectively Activated Mode - unit depends upon external
switches or scanners for activation of functions.
• Automatically Activated Mode - unit will operate with a slight
movement of the door toward the open position utilizing on-board
ELS switching that automatically activates the functions. External
switches or scanners may also be used for activation.
Functions (Functions are configured during installation.)
• Power Operator function (POR) – The unit performs as a low
energy power door operator. Field settings allow for following two
functions:
1. Selectively Activated Mode (See Above).
2. Automatically Activated Mode (See Above).

XX
XX

AmericansWith Disabilities Act (A.D.A.)
These door operators should be installed and adjusted to conform with
A.D.A. regulations.
ANSI Standards
ANSI A117.1 – These door operators permit door
assemblies to conform to the requirements of this
specification "for buildings and facilities – providing
accessibility and usability for physically handicapped
people".
• ANSI A156.19 – These products are designed to conform to this
specification "for power assist and low energy power operated
doors".
– "PAS" Mode is designed to meet or exceed all of the requirements for
the "Power Assist Door".
– "POR" Mode is designed to meet or exceed all of the requirements for
the "Low Energy Power Operated Door".
U.L. Listing

WARNING
120 VOLT POTENTIAL MAKE SURE POWER IS
TURNED OFF DURING INSTALLATION
PROCEDURE.

80-9369-0170-020 (01-09)

UL
®

US

Underwriters Laboratories, Inc. listed for use on fire
and smoke barrier door assemblies when the 120VAC
(60Hz) power input is supplied through the normally
closed alarm contacts of a compatible U.L. Listed
alarm system or alarm panel.
An incorrectly installed or improperly
adjusted door operator can cause property
damage or personal injury. These
instructions should be followed to avoid the
possibility of misapplication or
misadjustment.

CAUTION

NOTE: The ELS Dip Switches are factory set in the Selectively
Activated Mode as a Power Operator.

C

CAUTION

• Power Assist function (PAS) – The unit operates as a standard
door closer unless activated. Upon activation the door opening
resistance is reduced, for a selected period of time, well below
A.D.A. guidelines. When the time period expires, the door closes
under normal door closer spring power.

Kit Contents
Installation Instructions
ELS Board “TIMING”
ELS Board “Teaching”, Functions and Modes
Troubleshooting

2
2-3
4
7
8

Kit Contents:
Wiring Harness

Shrink Tube

4 Pin
Connector

Timing Belt
Wire
Connectors

Red

Black
6 Pin
Connector

Washer
Pinion
Screw
ELS Board
w/ Pulley

Pinion
Pulley

Installation Instructions:

!

DISCONNECT POWER INPUT TO UNIT AND PLACE THREE
POSITION SELECTOR SWITCHTOTHE“OFF”POSITION.

Fig. 1

JP2 Terminal
Strip Connector
Four Pins

1. Remove the Shrink tube from the Red, Black and Yellow Wires shown
in Fig. 1. Carefully cut tie wrap.
2. Unplug the 4-pin connector from the Main Board at JP2 terminal strip
that leads to the L2 and L1 switches as shown in Fig.2. Note, 6600’s
have a L2 Cam Switch only, 6700’s have both L1 and L2 switches.
3. Remove L2 Cam Screw with 5/32” hex wrench and remove L2 Cam
and L1 Switch Lever (if equipped).
4. Remove Two (2) #8-32 phillips head screws and remove L2 metal
switch plate and L1 switch assembly (if so equipped). DO NOT
DISCARD #8-32 Screws.
5. Note. You may cut the L1 and L2 wiring harness if this aids in
removing the metal L2 switch plate and switch assembly. The red 4pin connector plug disconnected in the step 2 will not pass under
existing tie wraps.
6. Assemble ELS Board to PowerMatic closer body with #8-32 screws
removed in step 4 but DO NOT TIGHTEN screws at this time.

Fig. 2

7. Plug the 6-pin connector of the ELS wiring harness to the ELS board
as shown in Fig. 3. This plug is keyed to facilitate assembly. Plug the
4-pin connector of the ELS wiring harness to the JP2 terminal strip on
the Main board, replacing the connector removed in step 2.

6 Pin
Connector

8. Splice the two remaining RED and BLACK wires of the ELS wiring
harness with the RED and BLACK wire removed from the shrink tube
in step 1. Splice the RED to RED and the BLACK to BLACK using the
two wire connectors supplied with the ELS Upgrade Kit. Slip Joint
Pliers or similar tool will be required to seat the connector button.
Button should be FLUSH with connector when properly seated. Fig. 4

Wire Connectors

Fig. 3
Fig. 4

2

Four Pin
Connector

Wires
See Step 8

4 Pin Connector
ELS wiring harness

80-9369-0170-020 (01-09)

Installation Instructions (cont.):
9. Assemble timing belt to the Pinion Pulley then slip loop of timing
belt over the pulley located on the ELS Board. Fig. 5

Fig. 5

10. Place wave washer first then the Pinion Pulley onto the Closer
Body Pinion. See Fig. 6. Assemble flat head pinion screw
supplied using a 5/32” hex wrench. Turn screw until it is close to
contacting the Pinion Pulley. Pulley should be able to rotate
independent of pinon. DO NOT TIGHTEN at this time.
11. Carefully slide the ELS board assembly in the direction that will
put tension on the timing belt. The proper amount of tension
has been achieved when you can deflect the belt 1/16” to 1/8”.
When the proper tension is present, TIGHTEN the two (2) #832 phillips head screws used to attach the ELS board to the
closer body in step 6. See Fig. 7.

Fig. 6

12. The ELS board assembly is now finished and the board is ready
to be “timed”.
NOTE: The Pinion Pulley should still be able to rotate independent
of pinion at this time. Be sure Pinion Pulley screw is not
tightened before proceeding. POWER INPUT SHOULD
REMAIN DISCONNECTED.
13. Proceed to the ELS Board Timing Instructions found on page 4
of this booklet.

Wave
Washer

Fig.7
Belt Deflection 1/16” – 1/8”

80-9369-0170-020 (01-09)

3

ELS Board Timing Instructions:

Timing Chart

Before the ELS Board can function properly, the ELS Board Pulley must
be “timed” to give the board a starting position.

Hand of Unit

Direction of Rotation To
Hard Stop

READ STEPS COMPLETELY BEFORE PROCEEDING.

LH-PUSH

Clockwise CW

RH-PUSH

Counter clockwise CCW

LH-PULL

Clockwise CW

RH-PULL

Counter clockwise CCW

!

*

WARNING: Make sure Dip Switch #3 on ELS board is in the
“A” position and the Selector Mode Switch is in the “OFF”
position when timing the ELS board.

Power input to unit should be OFF.
A

NOTE: IF UNIT IS MOUNTED TO FRAME AND DOOR DURING THE
“TIMING” PROCEDURE, THE DOOR MUST BE IN THE FULLY
CLOSED POSITION. IF UNIT IS BEING “TIMED” ONTHE BENCH
(OFF OF FRAME AND DOOR), THE PINION MUST BE IN THE AT
REST POSITION (NO PRE-LOAD).

Pinion
Timing Pulley
Screw

1. Determine hand of unit. See hand marking found on unit manifold.
(See front Page) This information is need to properly time the ELS
board.

CCW
LED
Pinion
Pulley

3. Rotate ELS Board Pulley in the direction shown in the Timing Chart
based on the Hand of Unit (Step 1) you are Upgrading. Rotate pulley
until a Hard Stop is felt. The pinion pulley should have been rotating
as well due to the timing belt.

**Depress and hold Black Button on the ELS Board.

While
depressing button, turn power input to unit “ON”. Continue
depressing button until the ELS Board LED flashes three(3) times.
The installer then has three (3) seconds to release the button after
LED flashes.

5. Slowly rotate ELS Board Pulley in opposite direction from step 3
(away from Hard Stop) until ELS board LED lights. The amount of
rotation required to light the LED should be less than 1/8 th of a turn;
if not repeat step 3. The lighted LED indicates the board is in the
“timed” zone for that Hand of Unit.
6. Hold the Pinion Pulley stationary while tightening the pinion screw
with a 5/32” hex wrench. If LED turns off during this tightening
procedure without significant movement of pulley (less than1/8 turn),
this is not a problem. The timing zone range in larger than the zone
that keeps the LED lit.

4 PAS
3 DN
2 T2
1 T1

CW

2. Remove Pre-Load from arm. See instructions based on Hand of
Unit. See Page 5 and 6

4.

B

ELS Board
Pulley

Fig.8

Timing Belt

Disconnecting Power to Unit
*If power
input does not have a interrupt switch near by, power
may be terminated at unit by unseating Fuse F2.
Choose a flat blade screw driver that will fit snugly into slot on
fuse holder

!
!

!

Carefully push on Fuse Holder cap while turning CounterClockwise 1/4 turn to unseat fuse holder cap. Gently pull cap
out slightly and note if LED on Main Board is Lit. If there is no
Light, Power input to unit has been disrupted.
To reseat fuse, Carefully push fuse holder cap into holder and
turn Clockwise 1/4 turn.

7. Pre-Load arm. See instructions based on Hand of Unit.
See Page 5 and 6

Fuse F2
Holder

8. The ELS Board is now Timed. Proceed to the Teaching Closed and
Open Door Positions found on page 7 of this booklet.

**NOTE:
When performing Step 4 of ELS Timing Instructions,
you may push on Fuse Holder Cap with screw driver to
temporarily engage power so that attention can be
directed at the ELS LED. Once the LED has flashed 3
times and the BLACK button released, then the
installer may properly reseat the fuse per instructions
above.

4

80-9369-0170-020 (01-09)

LH-PUSH / RH-PUSH – PRE-LOAD INSTRUCTIONS
REMOVING PRE-LOAD.

!

Loosen 1/4-20 located on Arm Slide.
Allow main arm to rotate toward the hinge until main arm is 90° with
door frame.

Arm Mark

Z

!

R

Left Hand Door Shown
Viewed from ceiling
Looking down on Unit

Shoe

S

Pinion
Flat

Y

Door should be in the fully closed position.

Fig.10

L

!

Fig.10 shown here for reference is case main arm is removed for
some reason during upgrade. Fig.10 shows proper Main Arm and
Pinion configuration.

Door

Fig.9
Arm
Slide
Main
Arm
Adjusting
Rod
Non
Pre-Load
Position

Pre-Load
Position

ADDING PRE-LOAD TO PUSH TYPE ARM.

!
!
!

Door should be in the fully closed position.
Rotate the Main Arm away from the hinge until the adjusting rod
and arm slide are perpendicular (at a 90° angle) to the door frame.
Tighten the 1/4-20 screw located on the Arm Slide.

80-9369-0170-020 (01-09)

5

LH-PULL / RH-PULL – PRE-LOAD INSTRUCTIONS
REMOVING PRE-LOAD.

!
!
!
!
!

Right Hand Door Shown
Looking Down On Unit

Door should be in the fully closed position.
Close Valves “S” and “L” located on bottom side of Manifold using
1/8” hex wrench, turn valves clockwise until interference is felt.

Fig.12

Open door to gain access to top of slide track. Using a flat blade
screw driver, extend the retaining clip approximately 3/8” and pull
up on arm until arm stud in free of Slider. (Fig.14)
Loosen and remove the Main Arm screw and washer using a #3
Phillips drive and remove Main Arm.
Open Valves “S” and “L” located on Manifold. Turn valves counterclockwise until head of valve is flush with Manifold. Once the Pinion
has stopped rotating the pre-load has been removed.

Right Hand Door Shown
Looking Down On Unit

Fig.13
Right Hand Door Shown
Looking Down On Unit

Fig.11

Arm Stud
Facing Down

Arm
Arm Stud

Fig.14

ADDING PRE-LOAD TO PULL TYPE ARM

!
!
!
!

!
!

!

6

Slider

Close Valves “S” and “L” located on bottom side of Manifold using
1/8” hex wrench, turn valves clockwise until interference is felt.
Place closer arm on the closer pinion with arm at a 45° angle to
frame face and the arm stud away from hinge. (Fig.11)
Rotate arm toward hinge to a position approximately a 100° from
frame face. (Fig.12)

Retainer Clip
(Extended)

Remove arm and reinstall it on the pinion with the arm almost
parallel to the frame face, this should be done before the pinion
shaft can rotate far enough to create arm interference with the
frame face. (Fig.13)

Retainer Clip
(Flush)

Install and tighten Main Arm Washer and Screw (1/4-20 x ½” long
No. 3 Phillips Drive).
Open door to gain access to top of slide track. Check to see if
retaining clip is extended approximately 3/8”. Insert Arm Stud into
Slider until it clicks in place. And secure arm by pushing on the
retaining clip until it is flush with the slider. (Fig.14 & Fig.15)
Adjust valves "S" and "L". Using 1/8" hex wrench, turn valves
counter clockwise. Do Not Remove Valves from Manifold. Adjust
valve "S" first and then valve "L" until desired speeds are achieved.
A.D.A. requires that from an open position of 70° the door will take
at least 3 seconds to move to a point 3" (76mm) from the latched
position, measured at the leading edge of the door.

!
!

Fig.15

IMPORTANT
Power Operator Function Only: The opening speed of the door
from closed position to 80 degrees must be 3 seconds or longer
and 4 seconds or longer to the fully open position.
Power Operator Function Only: The force required to prevent a
door from opening or closing must not exceed a 15lbf. (67N)
applied 1" (25mm) from the latch edge of the door at any point in
the opening or closing cycle.

80-9369-0170-020 (01-09)

TEACHING CLOSED AND OPEN DOOR POSITIONS:

Adjustments for the PowerMatic Product

Before operating, the PowerMatic ELS must be “taught” the fully
closed and fully open door positions.

The following adjustments mechanical, hydraulic and electrical are
listed in a suggested sequence.
NOTE: Make sure that power to unit is OFF.

1. With the door fully closed, press and release the BLACK pushbutton
on the ELS board. The ELS system will store this position as closed
and begin the 10 second “Teaching Mode”.
2. Within the 10 second time frame, manually open the door to the
desired fully open position. While holding the door open in this
position, press and release the WHITE pushbutton on the ELS board.
The ELS system will store this position as open.
3. Let the door close hydraulicly to the closed position. This will end the
“Teaching Mode” whether or not the 10 seconds have elapsed.

MECHANICAL ADJUSTMENT
• Set Closing Power. Use 11/16" wrench or socket. Turn Power
Adjustment Nut clockwise to increase door closing power. Door
control is shipped set at midpoint of power setting. Maximum
closing power can be achieved with 5 (360°) turns of the power
adjustment nut for a regular PowerMatic, 7 turns if unit is a
Barrier Free (BF) unit.
HYDRAULIC ADJUSTMENT – Use 1/8" hex wrench
• Closing Cycle – Make adjustments, as necessary, to the Sweep
Speed "S" valve and Latch Speed "L" valve. See illustration on
Page 2. Turn valves clockwise to reduce speed, counter
clockwise to increase speed.
ange
pR
Slower
Closing

S

WARNING: Verify that dip switch #3 on the ELS board is in the
“A”position to disable the Push and Go Feature.
Three position Selector Switch should be in the“OFF”position.

1/8"
Hex
Key

4. Turn the three position selector switch to the “ON” position for normal
operation or the “H\O” position for infinite Hold Open.

Latch R
ang
e

!

Faster
Closing

e
we

10°
Closed

Closing Cycle

• Opening Cycle – Adjust Backcheck, "B" valve, as necessary, for
hydraulic resistance to door opening in the backcheck range. See
illustration on Page 2.
Backch
ec

Activation Mode – (Push and Go)

k

ELS Dip SW 3
A
B

Function

ELS Board Dip Sw 4

Main Board Dip SW 1

Power Operator

B

OFF

Power Assist

A

ON

• Rotate the “SC”Valve Counter-Clockwise to adjust opening force.
• Rotate the “PA”Valve Clockwise if needed to adjust pressure.
Adjust the “SC and “PA” valves so the the door does not open when
activated, but opening force is reduced below A.D.A requirements for
Power Assisted Opening.
(See illustrations on page 2 for locations of Dip Switches and Valves.

Obstruction Operation:
Obstruction During Opening:
The unit will shut down and the door will close.
Obstruction During Closing:
The unit will reopen the door. If the Obstruction During Closing is
detected a second time, the door will not attempt to reopen and will
close.

Dip Switch T2
B
B
A
A

NOTE: Too much Backcheck, "B" valve, can affect the
operation of the units pump, preventing units from fully
opening the door. This valve may require fine tuning after all
other adjustments have been made.
• Backcheck Position "P" valve is closed. Open by turning counter
clockwise, only if backcheck cushioning is required to begin at a
greater degree of door opening than the approximately 75° it is
set for.
ELECTRICAL:
Turn power input to unit on.
Selector Mode Switch – Set to the “ON” Position for normal use.
– Adjust "CL/AS DLY" Rotary Switch/Timer Pot on the printed
circuit board as necessary using a standard screwdriver with a
1/8" wide blade. Adjustable for 0 to 30 seconds (see chart
below).
– Power Assist Function Only:
Adjusts the length of time the motor will assist with opening
from the time the motor is activated.
– Power Operator Function Only:
Adjusts the length of time the door remains at the fully open
position after the operator function shuts off.
CL/AS DLY
4 5 6

7

80-9369-0170-020 (01-09)

Opening Cycle

3 2

Obstruction Sensitivity
The sensitivity of the obstruction feature can be adjusted in the field as
required. The unit has been factory-configured to respond immediately
to an obstruction. In certain applications where excessive wind or
excessive stack pressure is present, a delay of 1, 3, or 5 seconds can be
selected by toggling dip switches #1and #2 on the ELS board.
Dip Switch T1
B
A
B
A

1/8"
Hex
Key

g

Decrease
Cushion

Functions – Power Operator / Power Assist:

Time
Immediate
1 Sec.
3 Sec.
5 Sec.

Increase
Cushion

Op
en
in

Push And Go
DISABLED
ENABLED

1

8

Mode
Selectively Activated
Automatically Activated

0 9

S2

Illustration for CL/AS DLY
Rotary Switch/Timer Pot
From Printed Circuit Board

Length of Time
(Seconds)

Setting

0
2
5
10
15
20
25
30

0
1
2
3
4
5
6
7

• If desired, install No. 668 Security Plate over notch in cover to
conceal the Selector Mode Switch when cover is installed.
• Install cover with mounting screws removed at beginning of
installation.

7

Troubleshooting
1. After installation; PowerMatic does not respond to input signal to
open door i.e. wall switch, card reader, etc.
a. Verify unit’s input power is connected
(LED lit on Main Board)
b. Verify unit’s 3 position switch is in the “ON” position.
c. Verify that the splices made during installation are indeed
RED to RED and BLACK to BLACK. See page 2.
c. Verify follow: Look at terminal JP2 on Main Board
1. Verify that Terminal “G” has a Black wire
2. Verify that Terminal “E” has a Red wire.
If the wire colors are not correct, swap the wires.
2. The PowerMatic’s motor turns on and opens the door if the door is
slightly pushed or pulled without any external devices i.e. wall
switch sending a signal to open.
a. The 6600 series unit didn’t have this feature. The 6900
upgrade gives you the “push and go” feature that used to be
present on the 6700 series only. If this feature is not wanted,
set the DIP Switch SW3-3 DN on the ELS board to the “A”
position.

7. If the unit does not respond to taught positions; is not
responsive to different hold open times and troubleshooting
step 4 did not solve the issue, the potentiometer connected to
the ELS board pulley may have been damaged during the
upgrade.
a. Verify the hard stop that was discussed during the
ELS Board Timing Instructions (page 4 step 2) has not
been broken.
1. Place the 3 Position Switch in the “OFF” position.
Disconnect power input to unit. (See page 4).
Hold the Pinion Pulley securely and loosen the
Pinion pulley screw so that the pulley is free to turn
independent of the pinion.
2. Proceed to the ELS Board Timing Instructions on
page 4 and re-time unit. If hard stop is not
present contact factory.

3. PowerMatic “Push and GO” feature is not operational.
a. Verify that Dip Switch SW3-3 DN on ELS Board is in the
“B” position.
4. PowerMatic does not respond to taught positions i.e. door does not
stop at the taught “Fully Open” position, but continues to travel until
it hits a stop; motor than continues to run for a few seconds after
stop is hit.
a. Was unit properly taught. See page 7.
b. Verify that RED and BLACK wires were properly spliced as
per instruction 8 on page 2. If wires are spliced, check
continuity of Red and Black wires across splice with meter.
5. PowerMatic Motor shuts off and door closes before reaching full
open position.
a. This could be caused by the unit sensing an obstruction
on Opening.
1.Verify door can be mechanically opened; check for frame
interference.
2. Check Backcheck setting on closer body. If Backcheck
is too strong, unit may be seeing this as an obstruction.
3. Check “SC” (Speed Control) Valve setting. Door may be
opening too slowly. Turn “SC” valve clockwise to increase
speed.
4. There may be wind or some other positive pressure
present. Adjust Obstruction Sensitivity to a longer time
setting. See page 7.
6. PowerMatic Motor turns on and re-activates door before it reaches
jamb or closed position.
a. This could be caused by the unit sensing an obstruction
on Closing.
1. Check for frame interference.
2. Verify the transition from sweep speed to latch speed is
smooth. If there is an abrupt change in speed or if door
stops as it transitions from sweep to latch, the unit wil
see this as an obstruction.
4. There may be a wind or some other positive pressure
present. Adjust Obstruction Sensitivity to a longer time
setting. See page 7.

ASSA ABLOY
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2003, 2009 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.

8

3000 Highway 74 East • Monroe, NC 28112
Tel: (877)-974-2255 • Fax: (800)-338-0965
www.nor tondoorcontrols.com

80-9369-0170-020 (01-09)



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Creator Tool                    : AdobePS5.dll Version 5.0.1
Modify Date                     : 2009:01:27 10:28:18-05:00
Create Date                     : 2009:01:27 10:28:18-05:00
Format                          : application/pdf
Title                           : 80-9369-0170-020 (01-09).cdr