PEERLESS Boiler Manual L0308189
User Manual: PEERLESS PEERLESS Boiler Manual PEERLESS Boiler Owner's Manual, PEERLESS Boiler installation guides
Open the PDF directly: View PDF .
Page Count: 45
Download | |
Open PDF In Browser | View PDF |
MI/MIH Boilers Installation, Operation Maintenance Manual Pr=-EI_LESS _ CAST IRON BOILERS MI Model Available for Natural or LP Gas • Standit_g Pilot (3 9 sectior_) with 8(7_ AFUE • [-Ioneywell SmartValve ® Intermittent Ignition with 82% AFUE MIH Mid-E._f_ency for Natural Gas • Honeywell SmartValve • Qualifies for Natural Low Utility Draft Sections with Rebates 83% AFUE in Some Areas Venting with Draft Low Diverter Ceilings Nipples _ a Permar_ent by _Vct_'r PetroIcum Insulated • Reduces Ignition Energy to Vertical Ir_stallations • Unaffected Deluxe in 3-6 Design Push • Provici( ® Intermittent Company Horizontal for Steel Available (Chimney) Profile • Internal • Ideal Model (3-9 section) Oilier Enameled Boiler • Completely 7"(c)hl Seed alzd Heat Between Sections Contaminants Steel Jacket Loss Encloses Gas Valve and Burners Safety Controls • Vent Safety ShutoffSwitch • Flame Rollout Safety ShutoffSwitch • Standing Pilot Intermittent or Honeywell • Honeywell Operating • Taco Circulator • Elec. Operated • Grundfos l_crless in tttt_ ind_Lslr_/. I{]_'limt_ [)(y(!ll({s._; ivtlrranQj _IL'_o s I(_(__I_ I)oilt,rs. /'/(,cLs(_ Peerless All I_ (_rlt'ss Ls p¢'ovlcl_'d.]_?r provld(,s cl tlt_' ('(t_%l ilOtl IIIIlil('_l. It'll II(!(_lr _;('('lioll.% ttl(lYltllllt] (.ill of l)(t('rl_'._;:_ Ih¢" C(l.'ql IYOtl hot N(!(?liolls q['il.s Ircldt,illark Ivat_:r Heater ['(,('rli,ss Company [ ](,_ll(,_ (2)m[J(lll{/ * 231 North ]OF Coltll)l(.lt, Walnut Street it)(iFK(llll!j * Boyertown. o I llo¢letlw(tll Corporcltion. ['_[_[_-r_kl_SS ® Ix)liters I'_Si(Jt_IIli_ll l'_t _(, tz!I(1 It "_I _1_"(_r _"xt_"r_(1<'(1 t mt_rrczl iIi( ".s (ati l X ii f_ (11id I_ll)ol ar(_ _to_ v (_v(_ lied)& ". co¢l._tdt Damper Relief Valve Floor Pan i._ r_ rt,gislt_rt,d rt'sid_'llti_ll Vent Circulator q[f_,r on_ of tll_" mosl c:omprelt_.nsive wctrrarlly prof.jrarrus c_¢_t iro,_ !_oil<.rs inc'!_d_, c_ lidl one tj_!(_r Illarl€_rlltj. A limited. r_'sidt't_ticd _ Controls Automatic • 50 PSI Safety • Non-Combustible c_xStltartVah;_t SmartValve Ignition CAST IRON BOILERS it!]orlnaliorL PA 19512 1021 * 610 367 2153 * www,peerless-heater.eom FAB MI l_l Pnnled {3/02 _n U 5M) S A USING THIS MANUAL A. INSTALLATION SEQUENCE ............. 1 1 B. SPECIAL ATTENTION BOXES ........... 1 7. START-UP PROCEDURES A. COMPLETING B. CONTROL DESCRIPTIONS C. ADJUSTMENT 1. PREINSTALLATION 2 A. ACCESSIBILITY CLEARANCES .......... 2 C. AIR FOR COMBUSTION AND VENTILATION ....................... 2 D. LIQUEFIED PETROLEUM (LP) GAS E. INSTALLATION SURVEY REGULATOR 2 B. CLEARANCE FROM COMBUSTIBLE CONSTRUCTION ..................... ....... 4 ............... 4 E PLANNING THE LAYOUT ............... 4 E CHECK-OUT 8. 6 B. SAFETY RELIEF VALVE ................ 7 C. PIPING FOR ZONED SYSTEMS 8 .......... D. EXPANSION TANK .................... 9 E. INDIRECT-FIRED WATER HEATER ........ 9 E FREEZE PROTECTION 9 ................. ............. B. VENT DAMPER INSTALLATION GENERAL .......................... C. VENT PIPING AND CHIMNEY .......... D. BOILER REMOVAL FROM COMMON VENTING SYSTEM ................... A. WIRING ........................... B. ZONED SYSTEM WIRING C. CONTROLS ........................ D. SEQUENCE OF OPERATION 10 11 12 15 15 ........... 24 INPUT PROCEDURE .... ............ ............. TROUBLESHOOTING 24 24 25 26 A. SHUT-DOWN CAUSED BY PILOT OUTAGE, BLOCKED VENT SHUT-OFF SWITCH OR FLAME ROLL-OUT SAFETY SHUT-OFF SWITCH ........................... 26 GUIDES .......... 26 A. GENERAL .......................... 29 B. DAILY (WITH BOILER IN USE) .......... 29 C. WEEKLY (WITH BOILER IN USE) ........ 29 D. MONTHLY (WITH BOILER IN USE) ....... 29 E. ANNUALLY (BEFORE START OF HEATING SEASON) .......................... 30 _ _TINGS 31 !0 15 ............. 20 24 OF PILOT GAS FLOW BURNER 10. BOILER DIMENSIONS A. INTEGRAL DRAFT HOOD ............. OF GAS PRESSURE B. TROUBLESHOOTING A. BOILER SUPPLY AND RETURN .......... ...... ....................... D. ADJUSTMENT E. CHECKING 20 THE INSTALLATION 16 A. BASE/COMBUSTIBLE FLOOR PAN ....... B. MANIFOLD/GAS TRAIN ............... 32 34 C. BLOCK/DRAFT HOOD ................ D. JACKET ........................... 36 38 E. CONTROLS/CIRCULATOR/VENT DAMPER .......................... 40 Follow thetnsta[lattoninstructionspro',,'_ded ill this manual m the order shown The order ot these mstructLons has been set m order to provide the installer with a logical sequence ol steps that wdl mulmllze potenhal interferences and maximize safety, during boiler mstallatLon Throughout thLs manual you will see speoal attenuon boxes intended to supplement the mstmct=ons and make speoal nohce of potenhal hazards These categories mean m the judgment of Peerless Heater Company Indicates a condition or hazard which will cause severe personal injury, death or major property damage. indicates a condition or hazard which may cause severe personal injury, death or major property damage. Indmates a condition or hazard which will or can cause minor personal injury or property damage. indicates special attention is needed, but not directly related to potential personal injury or property damage. 1.!B INS Read carefully, study these msh-uchons before beginning This bo,le_ must be installed by a quahfled The bonler warranty work con_ac_or can be voided _t the boder Is not installed, maintained and serviced correctly The equipment must be installed m accordance with those installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54. Where requtred by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-I. r_*wr:_o,[o.]:[.."[.."] I:] I ! / ik'd_a,]l :f;1 :_r_*l_[q _ Install boiler not less than 24" between the left slde. top, and tront ot the boiler and adjacent wall or other apphance, when access is reqmred for servicing Do not install this boiler on carpeting. Boiler installation on carpeting as a fire hazard. Install this boder on non.combustible flooring or use a combustible floor pan to install thts boder on other non-carpeted flooring. The design of ths boiler _scertffled for alcove mstallatlon wlth the following clearances I 6" between 2 24" between construction 3 6" between s,des and combustible construction top of jacket and combushble Prowde adequate facflltnes for combustlon and vent]lahon a_r un accordance w_th Sechon 5 3. ALrfor Combustion and Ventilation Nanonal Fuel Gas Code ANSI -7223 1/NFPA 54, or apphcable prows_ons of the local budding code Subsechons 2 through 6 below are based on National Fuel Gas Code ANSI Z223 1!NFPA 54 requnrements draft hood and combustible COl_ls_uctlon 4 6" between 5 10" between consiluctlon vent pipe and combustLble construction rear of ]acket and combushble 2 DehnltlOnS Do not install this boiler on combusttble flooring unless it is installed on a special combustible floor pan provided by Peerless Heater Company. Boiler installation on combustible flooring without the special pan is a fire hazard. Unconfined Space: a space whose volume us not less than fifty (50) cubnc feet per 1000 Btu/hr of the total input rahng of all apphances installed Jnthat space Rooms commumeatmg dnrectly w_th the space m which the apphances are installed, through opemngs not furmshed w_th doors, are considered part of the unconfined space To order combustible floor pan, use the 5-digit stock codes listed in Section 11A of this manual. Unusually where Tight Construction: Constmchon Walls and cenlmgs exposed to the outsMe atmosphere have a continuous water vapor retarder wlth a rating of i perm or less wLth openings gasketed or sealed, and b Weatherstnppmg has been added on openable windows and doors, and CaulkLng or sealants are supphed to areas such as joints around window and door frames. between sole plates and floors, between wallceflmg joints, between wall panels, at penetratlons for plumbing, electrical and gas hnes, and at other openings 2 3 Appliances Located in Unconfined Spaces: For installations in unconfined spaces with other than unusually tight construction, the supply of air for combustion and ventilation can usually be considered adequate. 4. Unusually Tight Construction: For equipment located in buildings of unusually tight construction as defined on the previous page, provide air for combustion and ventilation using the methods described in 5a or 5b below. 5. Appliances Located in Confined i ? 12" max TWO AIR OPENINGS: Minimum Free Area Each 1 in2per 1000 Btuh at Least 100 in2 Spaces: a. All air from inside the building: Provide two permanent openings communicating directly with an additional room or rooms of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. Use the total input of all gas utilization equipment installed in the combined space in making this determination. 12" max I Figure 1: Size each opening with a minimum free area of one square inch per 1000 Btu/hr. of the total rating of all gas utilization equipment in the confined space, but not less than I00 square inches. Begin with one opening 12 inches from the top, and begin the other opening within 12 inches of the bottom of the enclosure. See Figure 1. Provide air openings with minimum dimensions not less than three (3) inches. b. BUILDING Must communicate freely with outdoors Must not be under negativepressure Air Openings - All Air from Indoors TWO AIR OPENINGS: Minimum Free Area Each 1 in_per 4000 Btuh All air from outside the building. Connect the confined space with the outdoors in accordance with methods i) or ii) below. Provide air openings with minimum dimensions not less than three (3) inches. Where ducts are used, make certain that they are the same cross-sectional area as the free area of the openings to which they connect. Provide two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. Connect the openings directly or by duets, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Figure 2: Air Openings Outdoors - All Air Directly Figure Air Openings - All Air from through Vertical Ducts from Where directly communicating with the outdoors (see Figure 2) or where communicating to the outdoors through vertical ducts (see Figure 3), size each opening with a minimum free area of one (I) square inch per 4000 Btu/hr. of total rating of all equipment in the enclosure. 3: Outdoors Where communicating ii-i with the outdoors through horizontal ducts, size each opening with a minimum free area of one (1) square inch per 2000 Btu/hr of total input rating of all equipment in the enclosure. See Figure 4. .. 12"maxl [ i , _t [jT ) TWO AIR OPENINGS: 1' Minimum Free Area Each = in _per 2000 Btuh ii) Where the equipment has clearances of at least one (1) inch from the sides and back and six (6) inches from the front of the appliance, the code allows one permanent opening, commencing within 12 inches of the top of the enclosure. Connect the opening directly with the outdoors or through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Size the opening with a minimum free area of one square inch per 3000 Btu!hr. of the total input rating of all equipment in the enclosure, and not less than the sum of the areas of all vent connectors in the confined space. 6. 7. In calculating free area of an opening, take into account the blocking affect of louvers, grilles and screens. Do not use screens smaller than i/4" mesh. If the free area is known, use this value in calculating the size of the opening required. If it is not known, assume that wood louvers provide 20-25% free area, and metal louvers and grilles provide 60-75% free area. Remove sources of hydrocarbons (bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) from the boiler area. The vapors generated by these substances can contaminate the combustion air and contribute to shortened boiler/vent system life. _ 1-| l ! min ? 12" max Figure 4: :_ Air Openings - All Air from Outdoors through Horizontal Ducts IIL_l_uf±lUHff±_ugl[e]L_l [_'q_|J;kVJ_k For new and existing installations, a Water Installation Survey is available from Peerless Heater Company. The survey will provide information on how a hot water boiler works with your specific system and will provide an overview of hot water system operation in general. You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Water Installation Survey, contact your Peerless representative. I_ff±!_l_ll_[dl|ll:lt_VLelll Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring. Liquefied Petroleum (LP) is heavier than air and may collect or "pool" in a low area in the event of a leak from defective equipment.This gas may then ignite, resulting in a fire or explosion. See the instructions below. I IJ ! [o|lJ :l ;i I :ll]'.J :Eld :{o] ! ::[IILVA |_[€-r_,_.. The following LP requirements from the Uniform Mechanical Code, section 304.6, may be in effect in your geographic area: "Liquefied peh'oleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air gas might collect. Appliances so fueled shall not be installed in an above-grade under-floor space or basement unless such location is provided with an approved means for removal of unburned gas." l_.]llF'4T_'i:i_IrJ_ Provide a sound, level foundahon Locate boiler near to the chmney or outside v_ali as possLble cennahzed v_Jth respect to the heahng system 2 Locate _movll_g 3 boiler [n front of installation pos[hon as before crate If using combushble floor pan, poslhon pan on foundat,on or flooring 4 Separate the wood shppmg pallet from the boiler base by removing two (2) hold-down bolts at each end of the boder base 5 Move boder into hnal poslhon If using combustLble floor pan, install boder on pan as outhned ,n the instructions included wlth the pan and 3. WATER PIPING AND CONTROLS "-I [:{=]ll_;l[.-llJ'J_Jl_'m_,]l_ll] 1. 2. I;l:i[IJ;|k' Size the supply and return to suit the system. A t_pical piping arrangement is shown in Figure 5. Refer also to the I-B-R Installation Guide No. 200 and the Peerless Water Survey for additional guidance during water piping installation. Return Piping: a. For boilers equipped with a factory mounted circulator, pipe the return to the inlet connection of the circulator. b. For boilers equipped with a separate, unmounted circulator, pipe the outlet connection of the circulator to a tee, provided with a drain valve, at the 1-1/4 NPT return tapping near the bottom of the left section. Pipe the return to the inlet connection of the circulator. 3 Supply Piping: Pipe the supply to the I i/2 NPT supply the top and rear of the boiler. tapping 4. When system return water temperature will be below 130°E pipe the boiler with a bypass arrangement to blend the system return and hot supply to obtain at least 130°F entering the boiler. For more information on bypass piping, consult the Peerless Water Survey. 5. If desired, install the circulator in the alternate location shown in Figure 5. Consult the Peerless Water Survey for more information on circulator location. COLD WATER FILL VAL VE TO DRAIN l i DRAIN VAI VE J ,7 Figure 5: Supply and Return Piping at 6. 7. Install this boiler so that the gas components are protected from spraying, etc ) during appliance service (circulator replacement, control replacements, etc ) If this boiler and conjunction with chilled medium the proper valve 9. C HECj VAILVEI SUPPLY LINE distribution system is used in a refrigeration system, pipe the in parallel with the boiler and install to prevent the chilled medium from entering the boiler. A drawing up is provided in Figure 6 8. ignition system water (dripping, operation and condensate trap, illustrating this hook- When the boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, install flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. If this boiler is installed above radiation level, provide a low water cutoff device, either as a part of the boiler or at the time of boiler installation. LINE WATER _HILLER THREE VALVE Figure 6: Parallel Hook-up with Water WAY Chiller SAFETY RELIEF VALVE I:m l-'f!1=:lL'd I;t=l!l=l:l krl±lLvd i I Locate safety relief valve and fittings in bag assembly. x6" NIPPLE 2. If air elimination is not required at the safety relief valve tapping, install valve and piping as shown in Figure 7. 3. For air elimination at the safety relief valve tapping, install valve and piping as shown in Figure 8. Pipe the discharge of safety relief valve to prevent injury in the event of pressure relief, Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet. Figure 7: Safety Relief Valve Hook-Up Installation with Air Elimination in System Piping TO AIR ELIMINATION DE_CE SUPPLY SAFETY RELIEF VALVE TEE X 6_ NIPPLE NIPPLE TO DRAIN 5/4" STREET ELBO_ Figure 8: Safety Relief Valve Air Elimination Hook-Up with 7 loll I'JI_IL'_[_ l;:[e];l v_[o]L'ql:lm]F.._'_"-]Ii :hVj_ 1. See Figures 9 and 10 for basic 2 Run each zone pipe down then up to zone prevent air accumulation in piping 3. If required, provide zone separately, means zoned system to isolate layouts. to and drain each FROM TO SYSTEM ZONE 5 ZONE 2 ZONE I ZONE / SYSTEbl ZONE 2 I I ZONE VALVES ZONE 3 I BAL _,NCINO VAi VES m', I ± TO SUPPLY Figure 9: Zone Piping with CONNECT TO RETURN (CIRCULATOR INLET) Zone Valves TO SYSTEM ZONE 5 FLOW CONTROL _] ZONE 2 I- FROM ZONE 1 ZONE 1 ZONE CIRCULATORS q VALVES CONNECT TO SUPPLY Figure 8 10: Zone Piping with Circulators CONNECT TO RETURN TAPPING SYSTEM ZONE 2 3 I_ 1. Consult the tank manufacturer's instructions I:l;f:l:_,l: For new or existing systems that must be freezeprotected: for specific information relating to tank installation Size the expansion tank for the required system volume and capacity. See Table 8 in Section 10 for boiler water capacity. Use only inhibited propylene glycol solutions of up to 50% by volume with water. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems. Expansion tanks are available with built-in fill valves and check valves for reducing supply water pressure and maintaining minimum system pressure. Check the design features of the tank and provide valves as 2. necessary. Refer back to Figure 5 for typical expansion I;J;{e]i:_l,]i[o]_ 1. Glycol in hydronic applications is specially formulated for this purpose. It includes inhibitors which prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level. 2. The anitfreeze solution should be tested at least once a year and as recommended by the antifreeze manufacturer. 3. Antifreeze solutions expand example, a 50% by volume in volume for a temperature 180°F, while water expands temperature rise. Allowance expansion in system design. 4. For more information, consult the Peerless Water Installation Survey and the antifreeze manufacturer. tank piping. I::m I I£qm]I:| =[o,]iI_ :ll:t ::1e]I_l,__ii =1;t I: I_,__ii ::1 If the boiler is to be used in conjunction with an indirectfired water heater, refer to Figure 11 for typical piping. Follow the instructions provided by the water heater manufacturer. Pipe the water heater as a separate zone. more than water. For solution expands 4.8% increase from 32°F to 3% with the same must be made for this SUPPLY TO SYSTEM ZONE VALVES RETURN FROM SYSTEM ] BALANCING VALVE INDIRECT FIRED WATER HEATER HOT DOMESTIC WATER SUPPLY SUPPLY i TO TANK I SYSTEM CIRCULATOR _ DRAIN COLD DOMESTIC _WATER SUPPLY Figure 1 1: Typical Piping BALANCING VALVE J with Indirect-Fired Water Heater 9 Lt/:1_/Jl_[,':t 4; VENTING |_,!1 h,'_ii::[d; 1. f_,_ II o] ;f_,_;Iil -"[o_o] g The MIiMIH boiler is equipped with a built in draft hood This device is designed to: a provide for the ready escape of flue gases from the boiler in the event of no draft. b. prevent ]. Do not use one vent damper to control two or more heating appliances. See Figure 12. 2. Follow these and the installation instructions that are included with the vent damper. Observe the cautions and warnings that accompany all instructions. 3. Make certain that minimum clearances provided in the vent damper manufacturer's instructions are maintained and that adequate space is available for damper access and service. 4. Orient the damper operator to facilitate connection of the harness with the vent damper and boiler. Note flue gas flow arrow on vent damper and orient as required. For installation with damper mounted in vertical position, see Figure 13. For installation with damper mounted in horizontal position, mount the unit as shown in Figure 14 to avoid excessive heat on the operator or condensation drips into the operator. a backdraft [Tom entering the boilen c. control stack draft during operation. These tasks are accomplished without the extra height requirements of a separate draft hood. 2. The draft hood relief opening is the large rectangular passage at the front of the boiler. Make certain that there are no obstructions to airflow in front of this opening. 3. A vent safety shut off switch is located within the draft relief opening to shut off the boiler in case of a blocked vent condition. See Section 7B for details regarding this device. See Figure 16 in Section 6 (Electrical) for spill switch location. 4. The vent damper can be mounted directly onto the round draft hood outlet (vent connector) on top of the boiler, or in vent piping close to the boiler. See the Vent Damper Installation Instructions below. BOILER INCORRECT Figure 10 12: Venting Multiple Appliances c:::::::_ c:::::::_ c:::=_ c:::::_ c:::::::_ c:::::::_ OTHER HEATING &PPLIANCE CORRECT _o,,NkVJ:h,_/ uI:J I:,,]h,1[€_V_*l_._ I D][o,]-"I hVjh._I_" 1. 2. Install vent piping in accordance with Part 7. Venting of Equipment, National Fuel Gas Code, ANSI Z223. I/NFPA 54 or applicable provisions of the local building codes. Inspect the existing chimney and lining for structural soundness, corrosion and perforations. Repair as 4. Before connection of joints, inspect the vent pipe interior for foreign objects such as tools, equipment, rags, etc. and remove if present. 5. Insert vent pipe into but not beyond the inside wall of the chimney flue. 6. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive neces_Fy. pressure. 3. Install vent pipe to slope upward at least I/4" per lineal foot between the draft hood outlet and the chimney. 7. Support horizontal portions of the venting system to prevent sagging by use of metal strapping or equivalent means. Locate supports at no more than four (4) foot intervals. flVENT TO CHIMNEY SLOPE uP A MINIMUM OF 1/4" PER FOOT VENT DAMP DRAFT HOOD RELIEF _ _ SUPPORT AS REQUIRED, f¢3 DRAFT HOOD OUTLET Figure 13: Venting with Vent Damper SLOPE UP A MINIMUM OF I/4" VENT DAMPER in Vertical Position _VENT TO CHIMNEY 11 O'CLOCK POSITION PER FOOT_,,_ i O'CLOCK POSITION HEAT SUPPORT REQUIRED ! AS _CONDENSATION ZONE r i 7 O'CLOCK POSITION _5 DO NOT OPERATOR MOUNT DAMPER IN SHADED REGION SECTION Figure 14: Venting with Vent Damper in Horizontal O'CLOCK POSIT'ON A Position 11 At the time of removal of an existing boiler, follow these steps with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation: a. Seal any unused system. b, C_ 12 openings in the common d Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously. e. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe, After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use. venting Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on any clothes dryers and any appliance not connected to common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. g. Any improper operation of the common venting system should be corrected so that the installation conforms with the current edition of the National Fuel Gas Code, ANSI 7-223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach minimum size as determined using the appropriate tables located in the chapter "Sizing of Category I Venting Systems," in the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54. SLZeand w,-_tal[the gas supply plpmg properly in ordeT to provide a supply of gas sufflc,ent to meet the maximum demand wlthout undue loss of pressure between the meter and the boder 2 3 j Determine the volume of gas to be provlded to the boller in cublc feet per hour To obtain this value, thv]de the Btu per hour rating (on the boiler rating plate) by the heating value ot the gas ]n Btu per cubic feet Obtain the heating value of the gas from the gas suppher As an alternatwe use Table 1 2 or 3 on the next page to obtain the volume of gas to be p_ovLded to the boder Use the value obtained above as the bas_s for p_pmg SLZmg SLze the gas piping m accordance w_th Table 4 Consult the Natzonal Fuel Gas Code ANSI Z223 I,'NFPA 54 for other slzlng optmns 4 Locate the drop pipe adjacent the boder 5 Install a sedlment trap See Figure 15 Locate a tee m the drop plpe at same elevatlon as the gas inlet connechon to the bo_Ler Extend the drop p_pe to a pLpe cap to, but not m front of Install a ground joint umon ahead of the gas control assembly to permit serwcmg of the control Some Local codes reqmre an additional serwce valve when using the combmat,on gas controls If your code reqmres such a valve a suggested IocatLon Lsshown in FLgure 15 Use a pipe joint sealing compound that is resistant to the action of tiquefied petroleum gas. A non-resistant compound may lose sealing ability in the presence of this gas, resulting in a gas leak and fire or explosion potential. Check pLpmg for leaks Use an approved gas detector, a non-corroslve leak detectlon flu,d or other leak detecUon method If leaks are found turn off all gas flow and repalr as _ SERVICE -----JAC K ET _GJ. UNION _ I _fSEDIMENT _/FLOOR Figure 8 15: Gas Connection TRAP LINE to Boiler Disconnect the boiler and its ]ndlwdual shut-off valve from the gas supply piping system dunng any pressure testLng of that system at test pressure m excess of i '2 psLg (3 5 kPa) Do not subject the gas valve to more than 1/2 psi pressure. Doing so may damage the valve. Isolate the boiler from the gas supply p_pmg system by closing _ts _ndw_dual serwce valve dunng any pressure testing of the gas supply plpmg system at test pressure equal to or less than i 2 pslg (3 5 kPa) 9 Mlmmum permlsslble supply pressule for purposes ,nput adjustment (Inches Water Column) MI-09 Standing Pdot Natural Gas 5 2" All other MI/MIH Natural Gas 5 0" All MI LPGas II 0" of Maximum permlsslble supply pressure to the boder (Inches Water Column) All MI/MIH Natural Gas 13 5" All MI LP Gas 13 5" necessal_j When checking for leaks, do not use matches, candles, open flames or other methods that provide a source of =gnition.This can ignite a gas leak, resulting in fire or explosion. 13 [tl :I-2 [_igl_tl Table 1: MI Boiler- Natural Model Gas Input (Cubic F_Hr) MI 03 MI-04 MI-05 MI Ofi MI 07 M] 0_ MI 09 Based on i000 Table 70 105 140 175 195 227 5 260 2: Btu/Cubic MI Ft Boiler - LP Gas Model Input (Cubic FI/Hr) Ml-03 MI 04 MI-05 MI-06 MI-07 M[ 08 MI-09 28 42 56 70 78 91 104 Based on 2500 Bt_ICubicFt Table 3: MIH Boiler - Natural Gas Model Input (Cubic FffHr) MIH-03 MIH-04 MIH 05 MIH 06 65 97.5 130 162.5 Based on 1000Btu/CubicFt, Table 4: Pipe Capacity Capacity of pipe of different diameters and lengths in cu. ft. per hour with pressure drop of 0.3 in and specific gravity of 0.60. No allowance for an ordinary number of fi_ings is required. Pipe Length Feet V4" l" 11/4" 11/2u Pipe Pipe Pipe Pipe I0 20 30 40 278 190 152 130 520 350 285 245 1,050 730 590 500 1,600 1,100 890 760 50 60 115 105 215 195 440 400 670 610 Multipliers to be used with the above table when the specific gravity of the gas is other than 060: Specific Gravity Multiplier ........ 14 . 0 5 110 055 1,04 0.60 1.00 065 0.962 070 0.926 6.*ELECTRICAL Install all elechlcal wrong m accoldance wLth the National Elecmcal Code and local requirements This umt when installed must be electrically grounded in accordance with the requirements of the authority having JUrlSdtctton or, in the absence of such requirements, with the current edlbon of the National Electrical Code, ANSI/NFPA 70. r_,! iv=,il;llL_[€ _.41 [*(o] L_iiII-'{e]I_ See Figure 16 for locatEon of wrong and conh'ols Use Figures 17 and 18 to connect the boder to a power supply and to connect components to the boiler 2 Connect the bo=le_ by a separate, permanently electrLcal supply hne with a fused switch Connect _he vent damper harness to the polarLzed connector Lnthe boder vest=bule as shown m Figure 16 4 Adjust heat antlcipator For proper locatlon of controls and accessories refer to Flgure 16 and Section I i 2 See the attached control sheets for specific details regarding the instal]atlon of the various conlzols 3 Thin boiler is supphed wlth safety dev=ces m addttlon to the hmlt For a descnpt_on of these dewces and how they work to ensure the safe operatlon of the boiler, see Secuon 7B 4 If the clrculator [s mounted m the supply plpmg, provLde longer wrong harness as requLred live 3 the thermostat 1 to 0 2 Amp See Figure 20 for typLcal wiring w=th zone valves See Figure 21 for t_pLcal wrong with zone cLrculators When wLrlng a zoned heating system, follow all apphcable codes ordinances and regulations Do not power zone limit. Doing so will transformer Use a handle the total of valves directly from the boiler greatly reduce the life of the separate transformer sized to all zone valve electrical loads i9 LIHL OL IACE _- _ TO ','EN7 DAMPEP T,:, THEPrlOST_T _ Lit IIT C, Jr I-L_IPE_ F _,r Jr JEC E JlLC_ T,)_' -_._ _ "---... _ GLC,CXED 16: Wiring, POL'I:t2ED P_ /IBLILE, Controls SWITCH i IPI3BDL DB_E_.',' LeL_t Figure _Er_T and Safety IE nbr4 CO_L_ _JCILLOU T Devices 15 CONNECTION DIAGRAM LADDER 24V THERMOSTAT .... LB148£ OIAGRAM 115/60/i pOV_ER SUPPLy (BY OTHERS) C_81NATIO_i " r..... NSTALLF_ _ 60 R LI SUPgLY eK_ L2 DISCONNECT C_ BK L2 FUSE{) DISCONNECT SER_CE S_TCH S_4TCH C2 RI pR_MAR Y SER_C£ TR ANS_Oei4 ER THESE]_TO- SZCONDARY 0{,. !B.i l L2T22_ 'i , I I CONNECTOR B2, I i I rifle RelJ_e,4JT _ERMO¢OUpI "_ F _=t__ S_l I PRS L RZ C_NEC1]ON --- UNE UNE -- -- -- VOLTAGE VOLTAGE DIAGRAM LEG{.ND _IZE _ZE _¢ A_ 16-18 LOW '_LTAGE SIZE 18 A_G LOW SIZE 16-18 VOLTAGE w 0 BL TYPE TW, TFF'N OR AWG TYPE I%V TFFN WR[ TYPE I 1EW/A_ _IRE OR I_W/A_%a V_RE TEW/AV_, TFFN LAODER _R£ 120v -- 120V 24V -- 2) IF ANY OF REPLACED, Figure I'_ 17: Wiring F.']:[olli:l_[o,]:l I. Standing MUST COMPLY V_IH APPUANC[ 1HE ORIGINAL MRE AS IT MUST B_ REPLACED CODES, ORDINANCES AND SUpPU_O _4TH THE ApPLiANCE V4T_ _RE AS SHO_ and Connection Diagram REGULATIONS MUST ---- Pilot (See Figure 17 above) c. • the vent damper operator through contact R2, provided that the high-limit switch is closed. The vent damper b. operator • the pilot thermocouple is proving flame • the blocked vent switch is closed, and • the flame rollout switch is closed. 16 EXTERNAL _IRtNG [ INI_RNAL _,tRING [XERNAL _IRINg _RING _RMtNAL Ignition) When the call for heat ends: • Limit relay R de-energizes, contacts RI and R2. which opens • The circulator shuts down. opens the damper. Once the damper is proven open, the gas valve energizes, provided that all of the following conditions are met: i IVOLT T_ERNOCOUP_ I WIRIN_ Pilot flame is monitored through the pilot thermocouple. If pilot flame is lost during a call for heat, main and pilot gas flow will be shut off. The valve must then be manually reset by following the Lighting Instructions mounted on the jacket panel and included in Section 7 of this manual. a. The vent damper is continuously powered. On a call for heat, limit relay R is energized, which energizes: contact I[G_NO INTERNAL L_I4BE Pilot (Continuous [o]d[oir,,l=l;__41/[o]_ • the circulator (when used) through R1, and 24V MIU 0 BE -Standing DIACRAM -- NOTESm I) ALL _RING , 1%. I V#_lTE ORANCE BLUE TYPE TC CABLE AWG LIMIT BvS • The gas valve de-energizes. • The vent damper d. closes. If temperature exceeds limit setting, main burners shut off and circulator continues to operate. " i:! ! ;["_e_2_ CONN£CTI_ DIAGR_ L*_[R [_AGRAM L 1 11p_o_45_LR_ 1 L2 ¢1 FUSED D'S_EC C2 RI T _5_ T_I_ T R2 .... 8 HIGH U_IIT R I B! I LAD{)_R DIAGRAM L[G[NO [ I 1_+41T_ __AM_ I -- ND I -- 120V --- -- ....... 2. and Connection Diagram - Intermittent Intermittent Ignition (see Figure 18 above) a. The vent damper is continuously powered. On a call for heat, limit relay R is energized, which energizes: • the circulator (when used) through contact RI, and • the vent damper operator through contact R2, provided that the high-limit aqu_stat switch is closed. The b. damper operator opens the vent damper. Once the damper is proven open, the ignition circuit within the gas valve energizes, provided that all of the following conditions are met: _4V iN.HAL 24V [XTERNAL _>iLOT o 18: Wiring I_IR1NG t20v [XT_RHAL_RIN_ ---- Figure INT_RN_L LO14_ I _P PILOT L _BNC)] _4RIN_ _I_IN_ _RIN@ T_R_IN_- Ignition • the blocked vent switch is closed, and • the flame rollout switch is closed. c. When the call for heat ends: • Limit relay R de-energizes, contacts R1 and R2. which opens • The circulator shuts down. • The gas valve de-energizes. • The veat damper closes. d. If temperature exceeds limit setting, main burners shut off and circulator continues to operate. 17 START APPLY24 TO APPLIANCE VAC I I THERMOSTAT CALLS FOR HEAT I FIVE-MINUTEDELAY RETRY A I FLAME SIGNALNO DETECTED_ I INTERNAL TRIAL FOR IGNITION • WAIT FOR FLAME SIGNAL TO DISAPPEAR • PILOT VALVE/IGNITER REMAIN OFF CHECK OKAY? I NO _YES POWERED I • IGNITER PILOT VALVE OPENS PILOTLIGHTSAND [ I FLAME NO IS SENSED DURING /_-_ TRIAL FOR IGNITION? THREE-SECOND FAILURE RECYCLEFLAME DELAY J / • PILOT VALVE CLOSES • IGNITER OFF L / YES MAIN BURNER OPERATION [ •" IGNITER MAIN VALVE OFF OPENS I I I • MAIN AND PILOT VALVES CLOSE FLAME SIGNAL LOST? I HEAT THERMOSTATCALL ENDS FOR FLAME LOST MORE THAN FIVE TIMES IN ONE CALL FOR HEAT? I I • MAIN AND PILOT VALVES CLOSE END L/_ Figure !8 19: I l IGNITER WILL TURN OFF ABOUT 30 SECONDS INTO THE TRIAL FOR IGNITION. IF THE PILOT FLAME HAS NOT LIT, IT WILL TURN BACK ON FOR THE FINAL 30 SECONDS OF THE 90 SECOND TRIAL FOR IGNITION. THE PILOT VALVE WILL BE ENERGIZED DURING THE ENTIRE TRIAL FOR IGNmON. THIS IS NORMAL OPERATION FOR THIS GAS IGNITION SYSTEM. Intermittent Ignition System Operating Sequence I I NI NO I I15V/60HZ _LI TO MAIN DISCONNECT _ g_TCH J (HOT} _2 // _ ZONE I /_ _ ZONE 2 \ ZONE 3 GND , _× I [ [ F I I I ' _c× I I i • F ! [ AOOASTAT dUMPER FACTORY INSTALLED-- j I 7 v I I I q L _ y I I I 7 71 y] , I RELAY (HONEYWELL LS148E) 1 1 _ l [ ZONE , VALVE ZONE 2 VALVE ZONE 3 VALVE NO_ _ AlL WIRING MUST AND PEGULATIONS COMPLY WITH APPLICABLE (_ WIRE REMAINDER OF AQUASTAT RELAY SYSTEM WIRING DIAGRAM SUPPLIED CODEg• OROLNANCES IN ACCORDANC_ WITH kkGX.N_ UN_ VOLTAGE LOW VOLTAGE Figure 20: Zone Wiring I20V/6OHZ with Zone Valves _LI (_OT)-- TO MAIN DISCONNECT L2 SWITCH L _GND ZONE m 1 THERMOSTAT _ 24V I I ZONE 2 ZON[ 3 IHERMOSTAI 24V THER_OvSTAT JUMPER FACTORy i I_ -_ INSTALLED [NSTALLE O (HONEYWELL LIMI T LBI48E) 1 # I 1I ZONE 2 CIRCULATOR BOILER CIRCULATOR (ZONE I) (_) (_ Figure ALL ',_RING MUST AND REGULATIONS _RE REMAINDER SYSTEM _R_NC ZON£ 3 CIRCULATO_ L ............. I • L ......... COMPLY '_TH APPLICABLE CODES, ORDINANCES - LINE VOLTAGE LOW VOLTAGE OF LIMIT IN ACCORDANCE DIAGRAM SUPPLIED 21: Zone Wiring I i i L S_TCHING RELAY S_ICHING RELAY with _TN Circulators 19 7. START-UP PRO_GI RES + Connect a manometer to the gas val_,e on the valve outlet (ga, manifold) Use the 1 8 NPT tappLng prowded f-'l [a"[o) L'+I"JII:IIIIh'_[€"li l -"I=IIh';F-"+l Ir-"1! l;_li to] L_ 1 Cont£rm that all water gas and electnclly are turned off 2 Inspect the boiler combu,,t]on chamber objects and remove if present 3 Check phystcal cond]tton of burners and pilot Make certain that there are no unusual bends or perforations m the burners or pilot Replace components if necessary 4 Verify that water pLpmg venting electrical wlrLng and components properly Refer back to prevtou+ mstructtons as well as egutpmen[ mstruchons as necessary 5 for foreLgn gas ptpmg and are mstalled sections of these manufacturer's Confirm that the gas supply pressure to the boiler Rs above the mlmmum and below the maximum values for the gas being used See the end of Section 5 for these values If a supply pressure check _s reqmred _solare the boiler and gas valve before performing the pressure check If the supply pressure is too high or too low contact the gas supplier i0 Turn on electrtctw and gas to boiler 11 Light the boiler by followmg the Llghnng Operating Instrucnons label mounted to the jacket panel The Lnltlal Ignition may requve several tries as the piping ts purged of atr Fill the boiler and system with water making certain to vent all air from all points in the system To check water level in the system open and close each vent m the system Water should exit from each vent when it _s opened 12 Use the sequence descnptlons The pressure reducing valve on the fill hne w=ll typically allow the system to be hlled and pressurized to 12 pm Consult the vab+,e and expansion tank manufacturer for mote specff,c reformation 13 The gas manifold and control assembly are made of Check lotnts and fitting+ throughout the system for Leaks [f leaks are found dram the system and repatr as required 2O 9 m Figures 17 18 and 19 in Section 6 (Electrical) to follow l,ght-off and shutdown sequences and to asmst m dmgnosmg problems If the boiler does not funcbon properly consult Section 8, Troubleshooting gas-tlght completely factory assembled and installed components of the base assembly See Figure 22 and 23 L4 !UUUL '_ PILOI THERMOCOUPLE LEAD SECTION A Figure 22: Gas Valve, Manifold _EAD and Burner Assembly - Standing Pilot A (Continuous Ignition) -GAS VALVE S _\ A "_ Figure 23: Gas Valve, Manifold PILOT TUBING ORIFICE SECTION A MAN,FOLD _TEST A TAPPING and Burner Assembly 7 / - Intermittent Ignition GAB PRESSURE REGULATOR ADJUSTMENT SCREW 22_BURE / _UNOER CA_ SCREW) TAP LET_ouUTLETIN L NOTE: Figure 24: Valve Tapping TLET THERMOCOUPLE CONNECTION (STANDING PILOT ONLY) LOCATIONS PILOT AND and Adjustment _ PRESSURE TAP PILOT ADJUSTMENT SCREW (UNDER CAP SCREW) ARE SIMILAR FOR STANDING INTERMITTENT IGNRION VALVES. Screw Locations 21 FOR YOUR you I causing WARNING: If property A. g. SAFETY READ BEFORE not exactly, do follow these instructions damage, personal injury, or toss of life. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. BEFORE OPERATING smell all around the OPERATING 1. STOP! label. Read the safety information above on this 2. Set the thermostat 3. Turn off all electric power to the appliance. 4. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. to the lowest setting. /--GAS CONTROL a fire or explosion result I C, Use only your hand to slide the gas control switch, Never use tools. If the switch will not slide by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D, Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water, WHAT TO DO OF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. I may • If you cannot reach your gas supplier, call the fire department. appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. _ OPERATING INSTRUCTIONS 5. If the gas valve is not visible, remove control access panel. 6. If the gas control switch is not in the "OFF" position, slide the switch to "OFF". 7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above this label. If you don't smell gas, go to the next step. 8. Slide the gas control switch to "ON". 9. Replace control access panel, if applicable. 10. Turn on all electric power to the appliance. 11. Set the thermostat to desired setting. 12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" your service technician or gas supplier. SWITCH TO TURN OFF GAS TO APPLIANCE 1. Set the thermostat 2. Turn off all electric power to the appliance if service is to be performed. 3. 22 _ 4. Slide the gas control switch to "OFF". 5. Replace control access panel, if applicable. If the gas valve is not visible, remove the control access Figure to lowest setting. and call 25: panel. Operating SV95011SV9601 Instructions 9318 I[,-']t-'; FOR YOUR SAFETY READ BEFORE • ,'_ WARNING: If you do not follow these instructions exactly, a fire or explosion result causing property damage, personal injury or loss of life. LIGHTING 1. STOP! label. Read the safety information above 2. Set the thermostat to lowest setting. 3. Turn off •11 electric power to the appllence. 4. If the gas valve is not visible, remove panel. 5. If the gas control knob is not in the "OFF" turn the knob clockwise _ to "OFF." Gas Control Knob (shown in _OFF" position) -_ F'- C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push In or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D, Do not use this appliance if any pert has been under water. Immediately cell a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. 7. _1 Find pilot--follow metal tube from gas valve. The pilot is between two burner tubes. F_ 9. Turn the gas control knob counterclockwise #"% to "PILOT." position, 10. Push In red reset button all the way and hold in. Immediately fight the pilot with • match. Continue to hold the reset button in for •bout one (1) minute after the pilot is lit. Release button and it will pop back up. Pilot should remain llt. If it goes out, repeat steps 5 through 10. A • INLET • If button does not pop up when released, stop and immediately call your service tachnici•n or gas supplier. If the pllet will not stay lit after several tries, turn the gas control knob to "OFF" and cell your service technician or gas supplier. Walt five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP; Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step. 11. Replace Remove the pilot access panel, if supplied, located below and behind the gas valve directly above burner tubes 14. Turn on all electric power to the •ppllance. _TO TURN 1. Set the thermostat If the gas valve is not visible, panel. pilot access panel, if applicable. 12. Turn gas control to "ON." 13. Replace knob counterclockwise control access panel, if applicable. 15. Set thermostat to desired OFF GAS TO APPLIANCE to lowest setting. 2. Tum off all electric power to the appliance is to be performed. 3. 8. Pilot Burner RED RESET BUTTON . 6. on this / J*o_ id 41 setting. _ 4. Turn the gas control knob clockwise (_ 26: Lighting to "OFF." 5. Replace control access panel, if applicable. if service remove control access H24V Figure may INSTRUCTIONS control aceess / "] • If you cannot reach your gas supplier, call the fire department. B. BEFORE OPERATING smell •round the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance • Do not touch any electric switch; do not u•e any phone In your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas suppller's instructions. • LIGHTING I A. This •ppU•nce has a pilotwhich must be lighted by hand. When lighting the pilot, follow these instructions exactly. B VR8200 9177R Instructions 23 IsJ V-ll_i ilJ-*t iLhl_l :]q '=*,[*]=_//;{*]n Im]:_'[*_;]lM/[*]_: See Figure 16 in Section 6 (Electrical) for locations these devices. 3, 4. 1. Turn Gas Control Knob to "Pilot" in Figure 26. Locate and remove the pilot adjustment cap screw using Figure 24. 2. Remove pilot observation port cover on base front panel. 3. Turn the pilot adjustment screw clockwise until the pilot flame extinguishes. Then increase the pilot flow just to the point that the gas valve holds in when relighting the pilot per steps 9 and 10 of Lighting Instructions in Figure 26 (turn screw no more than an i/8 turn). 2, 3. 4. The first few turns of the adjustment screw may not cause any change in the pilot flow, Subsequent partial turns of the adjustment screw may have a great impact on pilot flow. LOW WATER CUT-OFF (FOR GRAVITY SYSTEMS OR HOT WATER BOILERS INSTALLED ABOVE RADIATION LEVEL) - A level-sensing device (float or probe) located in supply piping near the boiler. If water level in the system drops below the control's position, it will shut down main burner gas. The control will automatically reset once the water level rises above its position. Using the manometer setup installed in part 7A, set manifold pressure as follows for various gases. a. Natural Gas .......... 3.5" Water Column LPGas ............ I0.0" Water Column To adjust gas pressure, turn adjusting screw of gas . pressure regulator counterclockwise to decrease pressure, clockwise to increase pressure. Refer to Figure 24 for location of gas pressure regulator. Replace the cap screw when adjustment is complete. 4. 5. Turn on electric power to the appliance. Turn Gas Control Knob to "On" position per the Lighting Instructions in Figure 26. 6. Verify pilot remains lit after shutdown from a boiler "ON" cycle of at least ten minutes. If pilot extinguishes, follow Lighting Instructions in Figure 26 and again slightly increase pilot flow. Make a final slight increase in the size of the pilot to ensure sufficient pilot signal under all operating conditions, just to the point that you observe a slight increase in the size of the flame (no more than an I/8 turn). Replace adjustment cap screw and observation port 7. 8. cover. I [*4:I=[NNh_(€4 I. 2. :|lJ:t_J_:t IIL_I'._IJ Refer to rating label mounted on the jacket top panel to obtain the rated BTU per hour input. In no case shall the input to the boiler exceed the value shown on the rating label. Check input by use of the following formula (Peerless suggests reading meter for 2 Cu.Ft.): BTU/Hr. Input=3600 In no case should the final manifold pressure vary more than ±0.3 inches water column from the above specified pressures. Any necessary major changes in the flow should be made by changing the size of the burner orifice spuds. When adjustment is complete, turn off boiler, gas flow and electricity to boiler. Remove manometer connection from valve and plug tapping with plug provided. Turn utilities back on and resume checkout. position as shown ]. LIMIT (AQUASTAT) - A thermally activated, manually adjustable switch located on the left side of the boiler, towards the top and rear. The temperature sensing element is placed in the supply and will shut down main burner gas if the supply water exceeds the preset temperature limit. This is a recycling switch that will automatically reset when the supply water falls below the preset temperature. b. 24 Turn off all electric power to the appliance. VENT SAFETY SHUT-OFF SWITCH (SPILL SWITCH) - A thermally activated, manually resetable switch located in the draft hood relief opening. If venting system becomes partially or totally blocked, the vent safety shut-off switch will sense excessive temperature caused by flue products exiting the draft hood relief opening and shut down main burner gas. 2. L:JI I[*]t 11[€1r-"!.:1 I_ K*PA To maximize thermocouple life, particularly on natural gas installations with gas supply pressures above 9" W.C.. reduce the pilot gas flow of FLAME ROLL-OUT SAFETY SHUT-OFF SWITCH (FLAME ROLL OUT SWITCH) - A thermally activated switch located between the first burner from the left and the manifold bracket. The flame roll-out safety shut-off switch will sense excessive temperature caused by continued flame roll out and shut down main burner gas. This is a non-recycling switch that must be replaced once it has been activated and the cause of the roll-out eliminated. I. i [*]; 3600 F H T 3. - x FxH T Seconds per hour Cubic Feet of Gas Registered on Meter Heat Value of Gas in BTU/Cubic Feet Time in Seconds the Meter is Read As an alternative, use Table 5. Use the heating value provided by gas supplier. Use a stopwatch to record the time it takes for 2 cubic feet of gas to pass through the meter. Read across and down to determine rate. Table 5: Meter Conversion - Natural Gas iv) Observe boiler operation complete cycle Burner inputs in Btu/hr for various meter timings and heat values. (Tables based on 2 cubic feet of gas through meter). b. Intermittent i) Time that meter is read (sec) Heat Value of Gas (Btu/cubic foot) 1000 1025 1050 25 30 288000 240000 295200 246000 302400 252000 35 40 205714 210857 216000 180000 184500 189000 45 50 160000 144000 164000 147600 168000 151200 55 130909 134182 137455 60 120000 123000 126000 65 110769 113538 116308 70 102857 105429 108000 75 96000 98400 100800 80 90000 84706 92250 86824 94500 88941 95 80000 75789 82000 77684 84000 79579 I00 72000 73800 75600 105 68571 70286 72000 110 65455 67091 68727 115 62609 64174 65739 120 60000 61500 63000 125 57600 59040 60480 85 90 I;;I 2. a. Standing i) iv) Turn gas supply on. v) Reset the boiler and conlrol by following Operating Instructions. vi) Observe boiler operation complete cycle. Low Water Cut-Off (if used) - Consult the manufacturer's instructions for the low water cut-off operational check procedure. 4. Check the system to make sure there are no leaks or overfilling problems which might cause excessive make-up water to be added. Make-up water causes liming in the boiler and brings in oxygen. Oxygen can cause severe damage to the boiler though oxygen corrosion pitting. 5. Check the expansion tank and automatic fill valve (if used) to confirm that they are operating con-ectly. If either of these components causes high pressure in the system, the boiler relief valve will weep or open, allowing fresh water to enter the system. 6. Do not allow the system controls to subject the boiler to excessively low water temperatures, which would cause condensation of flue gases and corrosion of the boiler. Operate the boiler at a temperature above 130°E Adjust the boiler limit as required to maintain boiler temperature above this level. 7. Check the general condition of the system including piping support, joints, etc. Check cleanliness of the radiators, baseboard units and!or convectors. Clean them to the extent possible. If radiators do not heat evenly, vent any remaining air from them. 8. Review operation with end-user. 9. Complete the Warranty Card and submit it to Peerless Heater Company. Pilot: ii) Extinguish the pilot flame. Pilot gas flow should stop within 2-I/2 minutes. Complete shutdown is proven since the safety shut-off valve has stopped main and pilot gas flow. through one 3. of the ignition system safety Turn the gas control knob counterclockwise "PILOT". The main burner should go out and the pilot should remain lit. Turn gas supply off iii) Igniter will continue to glow for 30 seconds, de-energize for 30 seconds, then re-energize and glow for another 30 seconds. It will then de-energize for 5 minutes before restarting the sequence. After starting the boiler, be certain all controls are working properly. Check to be sure that the limit will shut off the boiler in the event of excessive water temperature. This can be done by lowering the limit setting until the main burners shut down. When proper limit function is confirmed, return the dial to its previous setting. To check operation shut-off features: Ignition System: it) Set thermostat or controller above room temperature to call for heat. Watch for igniter glow at pilot burner. [O4:l=(O4[_eleJld :J;{ole]=lmlgl;| I. through one to and User's Information Manual i0. Hang the Installation, Operation and Maintenance Manual and User's Information Manual in an accessible position near the boiler. iii) Reset the boiler by following Lighting Instructions. 25 When servicing or replacing items that communicate with the bonier water, be certain that" In the event of a shut-down actLon of the blocked vent out safety shut-off swltch caused by a pLlot outage shut-ott sw_tch or flame Tolleffechng a shin-down of the mallq burners :! a Refer to the Lighting, Operating Instructions Ln Figures 25 and 26 to properly turn oft the gas to the boiler b Turn off all electric power to the boder c Call a qualified heatlng servlce orgamzahon or Local gas company and have the cause of the shut-down mveshgated and corrected d Refer to L_ghtlng'Operatmg re start bo_ler I |'{o]lJ :| i :_'t : [oil) i h,_[_ [_lll Instruchons to I I] :_ Use Table 6 to assist m determining causes and prowdmg corrective actions to boiler problems Refer also to Figure 27 to _oubleshoot the [merm_ttent lgnLtLOn System Control These guLdes must be used only by quahhed serwce techntoans These mdwlduals must tollow all apphcable codes and _egulat,ons ,n repair of any bo,le_ problems • There is no pressure on the boLler • The boiler us not hot. • The power is off. When servicing the gas valve or pilot, be certain that: • The gas is off. • The electricity is off. Do not use this appliance if any part has been under water. Improper or dangerous operation may result. Immedmtely call a qualified service technician to inspect the bonier and to replace any part of the control system and any gas control which has been under water. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump.This may aggravate the problem and increase the likelihood of boiler damage. Instead, shut off the gas supply at a location external to the appliance. 26 Inj ;[.luJ :_! _; Table 6: Boiler Troubleshooting Burners not functioning Guide ] No power I Check line voltage wiring and fuses. 2. Limit (aquastat) not working 2 Check wiring and contacts, relay, temperature setting. Clean and adjust as necessary 3. Flame rollout switch open 3. Replace switch Locate cause and correct. 4. Blocked vent switch open 4. Reset blocked vent switch. Locate cause and correct. .5 Gas off at boiler gas valve 5 Start boiler using Lighting/Operating Instructions. 6 Gas off external to boiler 6 Check any gas valves in the line. 7 Plugged orifice spuds 7 Check, clean and re-install. 8. Defective gas valve 8 Use Figure 27 to troubleshoot intermittent ignition gas valve. Replace if necessary. 9 Improper 9. Check and correct in accordance diagrams in Section 6. wiring 10 Vont damper Burners will not shut down Flashback or burning at orifice spuds. malfunctioning ignition. I0 2. Check and correct wiring. I. Manifold gas pressure too low I. Adjust to proper pressure. 2. Improperly 2. Install correct spuds. sized/drilled orifice spuds. 3. Leaking gas valve 3 Replace valve. 4 Burrs on orifice. 4. Remove 5 Low supply gas pressure. 5. Contact gas supplier if natural gas. Adjust regulator if LP gas. or draft problems in burrs. 6 Check air supply, ventilation and venting system. l Insufficient pilot flame 1. Increase pilot gas flow, 2. Pilot burner/orifice 2. Clean pilot burner and orifice. clogged. 3. Reduce 5 Draft problem or pilot. rate to input on rating label. 4. Realign burners in boiler room. or pilot. 5. Check air supply, ventilation system. I. Underfiring and venting I. Increase rate to input on rating label. 2. Limit (aquastat) set too low. 2. Reset aquastat 3 Vent pipe too long. 4. Inadequate chimney 3. Reposition or venting system. to higher setting. boiler to reduce length. 4. Check chimney and venting recommendations. 1. Underflring 2 Limit set too low. 1. Increase rate to input on rating label. 3. Air in system. 3. Vent air from all points in system. 4. Circulator 4. Check circulator, replace if necessa W. 6. Incorred 2. Reset aquastat malfunctioning. 5 Circulation Fumes or gas odors instructions. 2 Short circuit 4 Misaligned burners Boiler not heating properly. manufacturer's 1. Use Figure 27 to troubleshoot intermittent ignition gas valve. Replace if necessary. 30verfiring. Excessive condensation in vent. Refer to vent damper Replace if necessary. with wiring 1. Defective gas valve. 6 Excessive downdraft boiler room Delayed [oD_ ni1_L_ system clogged. thermostat heat anticipator to higher setting. 5. Shut down and cool boiler, drain and flush system. setting. 6. Adjust heat anticipator. I. Leaks in gas piping or fittings. I. Locate and repair or replace. 2. Leaks in gas service line or meter 2. Shut down boiler and notify gas provider. 3. Obstructed chimney. 3. Check, repair and/or clean chimney. 40bslructed flueways or vent. 4. Clean fiueways or vent and remove obstructions. 5 Undersized in vent chimney or vent, high draft loss 5. Check National Fuel Gas Code and vent manufacturer's recommendations. 6 Draft problem in boiler room. 7. Overfiring. 8 Vent damper 6. Check air supply, ventilation 7. Reduce malfunctioning. and venting system. rate to input on rating label. 8. Refer to vent damper Replace if necessary. manufacturer's instructions. 27 INSET A END VIEW OF 24 VOLT THERMOSTAT CONTROL HARNESS CONNECTOR START • ASSURE GAS VALVE SWITCH IS iN "ON" POSITION • DISCONNECT SYSTEM CONTROL HARNESS I •• TURN OFF GAS SUPPLY SET THERMOSTAT TO CALL FOR HEAT VOLTS 24 VOLT COMMO 24 VOLT VOLTS HOT CHECK FOR DAMAGED OR MISSING TERMINALS IN CONNECTOR INSET B I1 l CHECK FOR PROPER VOLTAGE AT CONTROL HARNESS (SEE INSET A). VOLTAGE SHOULD BE 24V BETWEEN THERMOSTAT AND 24V COMMON, 24V COMMON AND 24V BETWEEN AND 24V HOT. YES ii i: ',Fo NI NO _[ CHECK: • LINE VOLTAGE POWER • LOW VOLTAGE TRANSFORMER • LIMIT CONTROLLER • THERMOSTAT •WIRING • VENT DAMPER IS OPEN AND END SWITCH MAKES L l UNPLUG PILOT BURNER CABLE. MEASURE VOLTAGE AT GAS VALVE HSI ELEMENT OUTPUT (SEE INSET B) 24V NOMINAL I, .:W,:oW RMSUPAND Q + NOTE: iGNITER WILL CYCLE OFF AND BACK ON ONCE GURING THE 90 SECOND IGNITION TRIAL I I • PILOT BURNER IJGHTS • TURN ON GAS SUPPLY GAS VALVE I RECONNECT PILOT BURNER CABLE I YES VOLTAGE BETWEEN 24V VALVE. MUST MEASURE AT LEAST 19.5 VAC WITH IGNITER POWERED. SEE INSET A TO IDENTIFY PROPER LEAD. THIS CHECK MUST BE DONE HOT AND LEADS TO GAS WITH THE 24V GASCOMMON VALVE CONNECTED YES AND IGNITER CABLE RECONNECTPILOTBURNER I REPLACE I I • CHECK THAT PILOT GAS IS FLOWING. WAIT TO ASSURE PILOT GAS TUBING IS PURGED, _=_ • MEASURE ,NO, _ I GAS VALVE CHECK TRANSFORMER i LINE VOLT SUPPLY POWERED, YES I RE P LACE IG NITER/FLAM E ROD ASSIEMBLY ] r GOOD CONTACT FLAME ROD. BURNEROPENS LIGHTS I MAIN MAIN VALVE AND WITH PILOT BURNER • CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING •• IF BOTH OF THE ABOVE AREMAKES GOOO, CHECK THAT PILOT FLAME REPLACE IGNITER/FLAME ROO ASSEMBLY. YES I I CYCLE THERMOSTAT SYSTEM IS OKAY I Figure 27: 28 Intermittent Ignition System I YEs IREP CE'GN'TE I MEROOA--OLY I YES I ' REPLACE MAIN BURNER OFF AND BACK ON LIGHTS Troubleshooting I _1 Sequence REPLACE GAS VALVE AND I h',!_,!1_i i 4 _<'_!_,l 7[.I: 9. MAINTENANce. 5 l-*! [€l _ L'I_IP.t. 1 Disconnect this boiler from durung any pressure testing 2 Check pipes adjacent to cold walls or in unheated spaces Insulate and tape them Lfnecessary to be sure they can t freeze up Keeping the water moving at all times will reduce the likelihood of freezing See Section 3 for antifreeze instnictions Smell around the apphance alea It you smell for gas gas. follow the procedure listed m the LLghtJng, Operatlng Instructions m Section the gas supply piping of the gas system lllhll I 1 [! li'illrlll I / i I I :[o] I I 11tl li'lllll-'t 7 : Flush float-type low-water cut-off (if used) to remove sedLment from the float bowl as stated m the manufacturer's instructions Uill_'5 [oli_i / l lii'llli,_i / I: i :io] I I 1 :g h,'_lil..'ti 3 If there is considelable foreign matter in the boiler water the boiler should be shut down and allowed to cool then drained and thoroughly flushed out Use the dram valve at the bottom of the return connect,on to drain the boiler Pipe the dram cock to a suitable drain or containment dewce _f antifreeze is used Flush the system to remove remaining matter If there is evidence that hard scale has formed on the internal surfaces, the boiler should be cleaned by chemical means as prescribed by a quahhed water treatment specLal_st 1 Check boiler room floor dlalns fol proper functioning 2 Check function of the safety relief valve (monthly unless speofled otherwise by manufacturer) by performung the follo_,,ung test a Check valve pLpmg to determine that ,t is properly installed and supported There must not be signs of continuous wetness at the chimney If s_gns of continuous wetness are observed, a qual_hed service agency must be consulted to modify the vent confLguratLon to prevent the tormatlon of condensate i:II Ill7,_!ll'lllVi_li/ll c Lift the ti'y level on the safety relief valve to the full open position and hold Ltfor at least five seconds or until clean water LSdischarged :loll!!llh"lll--'l" Remove any combustible materials, gasohne and other flammable hqulds and substances that generate flammable vapors from the area where the bouler LS contained Make certain that the boiler area has ample air for combustion and venhlation and that there are no obstructions to the free flow of air to and from the boiler Observe general boiler conditions vibrations, etc ) temperature and pressure e If the valve continues to leak. it must be replaced before the boiler is returned to operation f Check that operating pressure and temperature have returned to normal g Check again to confirm that valve has closed completely and is not leaking 3 Test low-water cut-off (if used) as descnbed manufacturer 4 Test limit as described (unusual noises, Observe operatLng temperature and pressure on the combmatlon gauge located on the left side of the boiler Boiler pressure should never be higher than 5 psl below the rating shown on the safety rehef valve {25 ps_g max,mum for a 30 psLg rating, 45 pslg maximum for a 50 pslg rating) The valve rating can be found on the top of the safety relief valve (see Figure 5 for location of the safety relief valve) Boiler temperature should never be higher than 250 GF 4 Check boiler operating Release the try lever and allow the valve to close If the valve leaks, operate the lever two or thlee times to clear the valve seat of foreign matter It may take some t_me to deteu'mne _tthe valve has shut completely Daily boiler observatLon can be performed by the owner If any potential problems are found, a quahfLed installer or service techmc_an,'agency must be notffued 2 b Procedure by the in Section 7E "Check-Out " 5 Test function of gas safety shut-off features as described by gas valve and ugnution control manufacturer 6 Cycle the boiler at least once and check operation the vent damper of Check for water leaks in boiler and system piping 29 // OUTE ON [)ARK BL JL IN CC' OR i //_\ , When servicing or replacing components, be absolutely certain that the following conditions are met: • Water, gas and electricity are off. • The boiler is at room temperature. • There is no pressure in the boiler. 1. Check flueways and burners for cleanliness and dean if necessary. Use the following procedure if cleaning is required: Figure a. Refer to the Lightin_Operating Instructions in Figures 25 and 26 to properly turn off the gas to the boiler. b. Turn off all electrical power to the boiler. c. Remove burners and brush gas outlet ports lightly using a soft bristle brush. 28: Pilot and Main Burner CONE IS IN COLOR Brush flueways with wire brush. To the extent possible, inspect inside of vent pipe and vent damper for obstructions in flow or vent damper movement. Remove or replace as necessa[v. g. 3O Re-install baffles on MIH models. When replacing the flue collector/draft hood, be certain that the blanket seal between the flue collector and top section makes a tight seal to prevent leakage of the products of combustion. h. Re-install the top of the jacket, vent damper vent pipe. i. Re-install burners. Flame FLA_EB INNER BLUE d. Remove the vent pipe, vent damper, top jacket panels and flue collector/draft diverter. Remove baffles on MIH models. e. Standing and 2. Inspect entire venting system for corrosion, support and joint integrity. Repair as necessary. 3. Check the pilot and main burner flame. See Figures 28 and 29. The pilot should provide a steady flame enveloping 3/8" to i/2" of the flame sensor. If required, adjust the pilot as stated in the gas valve manufacturer's instructions. The main burner flame inner cone should be approximately 1-1/2" high and should have a very sharp, blue color characteristic. Figure 29: Intermittent Pilot and Main Burner Flame / 10. BOILER DIMENSIONS 8 RA !N GS I I. II I, i _,111 , rllt_ ii FLLIEF TEtd_" E_ - [iIPE b- _ I_IFE . l I FL ,L_= LIrL Figure 30: Boiler Views Table 7: Series MI/MIH Boiler Dimensions 111:i I 1i,.I1_ I a_ I I: I :[l] I I1_1:i 1] I_ I =1_._1[l]_p I Jacket Boiler Table 8: Left of Jacket Rear of Jacket Vent Connector to c ]ot Vent D to c ] of Vent E" Size F i A" Depth B' I Top _o F]oo_ C' ML,MIH-03 121 -/' 20_ " 31%" 61 ," 2013Le" 5 MI$4IH-04 MbMIH-05 15%" 19 _4" 26%" 31%" 7 n ,_ 20_,,J 5' M['MIH-06 22%" 26%" 26%" 31%" 31%" 9_ ' 11%." 2Ill,#" 21_'_ " 6" 6" MI-07 26" 26%" 31_ " 13" 21_q_ " MI-08 29%" 29%" 31%" 14 u =_" 235h_" MI-09 32_" 29_,_,, 31%- 16%- 24%e- .ode] / Number I Series MI/MIH Width _ ; DOE Heaung Capacity Water Efficiency Number MBH MBH3 MBHI2 (AFUE)3 M 1-04 M 05 MI-06' MIH-04 MH-05 MIH-06 I.i. MI-08 MJ-07_I]39,N/A N/A _ MI-09 N'A I05 140 175 975 130 11625 Mi I ,H 1 piping s_s[ems 8.. 86 115 143 _95 11 N,,A N/A / | 186 160 /1_ N'A I 162 260 I 211 NIA ; 183 2275 N,A i I I I having 15 _l_ 108 135_ unusual EMc[enc_ I 75 i_4 124 piping 1 _ I and pickup 70 94 117 ° 802 802 803 N/A _821 N/A 820 N/A_20 1 Content MIH I (Gal) 831 830 830 : 600 728 856 805 t N/A N,A [I 82o 820 /1 N'A N,AI_ N/A N/A 803 N A 80 1 requlrement_ I 1 _ Water (AFUE)3 :Mill, _ _ ConsulI factory before s_]e_lng boiler _or installations Net I=B=R water ratings based aon an allowance of 1 e_.[enslv_ 8- Boiler Ratings AG A Input IMIH T' I I Boiler Model .l ; such I N_A as intermittent 82 0 system N,A operahon _ ]2 98_ 12 40 L_I_I_! etc 3 Heatln9 Capacityand Annual FuelUbl_anon Efficiency (AFUE) rabngsare based on U S Governmenttest N[H ModelsAvailable asNatural Gas wn[hInlerm_ttenl IgmhonOnly 31 ]3 ;;_ EPAI R_PABTS REPAIR SERIES MI/MIH PARTS GAS BOILER Repair parts are available from your installer or by contacting Peerless Heater Company, Boyertown, PA 19512-1021. Use the figures and tables on pages 32-41 to assist in ordering parts. Note Remember to include boiler model number and serial number when ordenng 3 Figure 32 31: Base/Combustible Floor Pan parts Table 9: Base/Combustible Floor Pan Base Assembly 91518 91883 91897 91909 93561 93573 81036 2 Observation 51771 51771 51771 51771 51771 51771 81771 3 Base Blanket Seal 50867 50867 50867 50867 50867 50867 50867 90700 90701 90702 90703 90704 90705 90706 ] 4 Combustible Cover Door Floor Pan Assembly Specify length 33 ,,6) _\\ Figure Table 32: Manifold 10: Figure Manifold/Gas Train (MI - Standing Steel Burner Pilot Pilot) ! Specify quantity • t 6 _Steel i 33: Gas Valve and Pilot - Standing (Continuous Ignition) _as Burner w/Pilot Clip I per boiler - Manifold " 51263 51263 51263 51263 i 50978 " 50979 50980 50981 0954 50955 : 50894 50894 50894 50894 i 50895 50895 51263 -- I 8 _'_i Orifice Spud_48 i Natural Gas,O 2000 i elevation Natural o,ficespuZ_49 I elevation _Or_f_ce Spud, #57 Honeywell VR8200A2116 Gas Va]ve [ Nat. Gas Honeywe!! VR820(_6040 Gas Valve LP Gas ] Honeywell VR8300A4003 Gas Valve I Honeywell VR8300C4035 Gas Valve Q314A3505 50899 50899 50899 Pilot ft. i 50900 50900_ s0900 (specify qty) ! 50581 50581 50581 50221 5022i i50 21' ;0s87 ! 0587 Nat Gas 91333 i LP Gas I Nat. Gas I : 50899 i ! elevation i Honeywell _, 91333 91333 HoneYwell Q314A3703 pi!ot I HoneywellQ309A2119-24" Thin *For elevations 34 . LP Gas I over 2,000 feet above sea level contact ' 91333 51688 51688 51688 51688 51688 51688 50555 50555 50555 50555 50555 50555 i 50555 51318 ! 51318 ! 51318 51318 51318 51318 i 51318 • 11 50895 (specify qty) i LP Gas, 0-2000 i I0 ft. (specify q_)* i LP Gasl 0;2000 Orifice Spud, #56 9 (specify qty)* Gas, 0-2000 elevation ft, Peerless Heater Company. 51688 ; Figure 34: Gas Valve Table 11: and Pilot - Intermittent Manifold/Gas 5 Steel Burner 6 Steel Burner w/Pilot 7 Gas Manifold 8 Orifice Spud, #48 Train ignition (MI - Intermittent Speci_ quanfl_ Natural Gas, 0-2000 Natural Gas, 0 2000 ft. Orifice Spud, #56 LP Gas. 0-2000 SV9501M2700 Gas Valve Natural SV9501M2064 Gas Valve LP Gas Honeywell SV9601M4167 Gas Valve Honeywell SV9601M4225 Gas Valve• Honeywell Q3480B1025 Pilot Honeywell *For elevations Table 12: Q3480B1033 Pilot Manifold/Gas Steel Burner w/Pilot 7 Gas Manifold 8 Orifice Spud, #49 50894 50894 50894 , i 51537 s09 , 50956 I i 50895--50895 [ ft. 50899 50899 50899 50895 [ 50899 50900 i Natura! Gas ! 51682 i 51682 51682 J 51691 51691 i 51691 _ i LPGas 50900 I i [ ] _ Lp Gas Natural Gas 50900 i Gas ] 1 L ! 5168451684 I 51685 Train (MIH - intermittent : 51_ 81685 51685 51537 51537 _6!!_692 ;51684 51685 516_ 51685 51684 ] 51685 !51684 ] 51685 ignition) Specify quantily Clip 1 per boiler 51539 Natural Gas, 0-2000 Gas Valve Natural Gas Gas Valve Natural Gas Pilot fi. 50895 I 50895 51539 ] 50980 [ S098i 50895 Natural Gas i 50895 i (specify qty)* Honeywell SV9601M4167 Honeywell Q3480BI025 51539 5097850979 Honeywell SV9501M2700 *For elevations 51537 (specify qty) elevation I0 [ over 2,000 feet above sea level contact Peerless Heater Company• Steel Burner 9 50894 LP Gas, 0-2000 It. elevation (specify q_} Honeywell 51537 (specify qty)* elevation Honeywell 51537 : s0979 50980 fi. Orifice Spud, #49 Orifice Spud, #57 51537 i 51539i51539 51539i51539 51539!51539 i 51539 (specify qty)* elevation I0 51537 lperbo er Clip elevation 9 Ignition) 51682 51682 51682 ! 51683 , 51684 i 51684 51684 ] 51684 over 2,000 feet above sea level contact Peerless Heater Company, 35 Figure 36 35: Block/Draft Hood Table 13A: Block/Draft Hood 91280 12 Block Assembly 13 Flue CollecloriDraft Hood Flue CollectorlDraft Hood 14 Table 15 90511 _ Flue Collector Blanket Seal 13B: Flue Baffles Flue Baffle - 4" Flue Baffle - 8" 50866 Specify length 50866 for MIH Only I 1 per flue (specify qty) I 51583 1 per flue (specify qty) 37 \ Figure 36: Jacket 38 Table 14: Jacket 16 ,Jacket Assembly ]6A Left Side Panel 16B Right Side Panel 16C Rear Panel 16D Top Panel 16E Inner Front Panel 16F Baffle Panel 16G Removable 16H Upper Front Panel *Complete Jacket Consists Complete insulation jacket* with and screws 90445 90446 90447 90448 90449 90450 90451 of: Front Panel 39 I_t"-Jl_I_ 1;t I=a_l_-'] \ I i \ I Figure 4O 37: Controls/Circulator/Vent Damper Table 17 15: Controls/Circulator/Vent Circulator w/Flanges. 18 1%" x 2_//' Nipple* 19 1%" Tee* 20 11/4" x 4" Nipple* 21 IV4" x 3/4" Bushing* Damper 50736 Gaskets and Hardware* 99236 50736 99236 50736 50736 50736 50736 50735 99236 99236 99236 99236 99236 425 425 425 425 425 425 425 99967 99967 99967 99967 99967 99967 99967 1539 1539 1539 1539 1539 1539 1539 50517 50517 50517 50517 50517 50517 50517 51689 51689 51689 51689 51689 51689 51689 51774 51774 51774 51774 51774 51774 51774 50501 50501 50501 50501 50501 50501 50501 Safety Relief Valve, 50 psi*, Watts #350 99950 99950 99950 99950 99950 99950 99950 Flame Roll-Out Safety Shut Off Switch 51587 51587 51587 51587 51587 51587 51587 27 Blocked Vent Shut Off (Spill) Switch 51590 51590 51590 51590 51590 51590 51590 28 Vent Damper 90608 90608 90609 90609 90610 90611 90611 22 3/4"Drain Valve* 23 Honeywell 24 25 26 L8148E1182 Temperature-Pressure Limit w/%" Well* Gauge ! Safety Relief Valve, 30 psi*. Conbraco 10-408 05 *Available from distributor 41 Series MI/MIH Gas Boilers Installation, Operation Maintenance Manual TO THE INSTALLER: This manual be affixed TO THE This the boiler of the owner for future and must reference. OWNER: boiler Qualified HI Division is the property near should Service be inspected annually by a Agency. ASME of gama PEr-I_LESS ® CAST IRON BOILERS PEERLESS HEATER COMPANY 231 NORTH WALNUT STREET • BOYERTOWN, PA 19512-1021 • PHONE 61_367-2153 vvww.peerless-heater.com THE @2002 Peerless Heater Company PREFERRED HEATING CHOICE MI8038 R5 (12/02-10M) Printed in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 45 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Tue Apr 03 15:18:39 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools