Electrical network management

PowerLogic System
Energy management, revenue metering and power quality monitoring

Catalogue
2013

PowerLogic System is…

PowerLogic technology forms one part of your total energy
management solution from Schneider Electric. As the global
energy management specialist, we offer end-to-end power,
building and process management solutions that help you
optimise energy use and costs, improve performance,
enhance comfort and safety, and deliver uninterrupted service
while taking responsible care of our planet.
Our expert services can help you audit your energy use and
build your energy action plan. From power factor correction
systems, harmonic filtering and variable speed drives to HVAC
and lighting controls, we offer a complete range of energy
efficient technologies.

Schneider Electric believes every business can increase
productivity while consuming less and achieving energy
savings of 10% to 30%.
Saving energy reduces costs and pollution, but you need the
tools to uncover all opportunities, avoid risks, track progress
against goals, and verify success. Schneider Electric
provides these tools via the world’s most advanced energy
intelligence technology: PowerLogic.
The PowerLogic range of meters and software help manage
all energy assets, every second of the day. A PowerLogic
system enables all stakeholders, from CEO to facility and
engineering managers, to respond quickly to potential
problems and manage energy in financial and environmental
terms.
PowerLogic technology delivers the key performance
indicators and analytics that you need to strategically balance
emissions, efficiency, reliability and cost.

General contents

Gain energy insight and control with PowerLogic™
Market segments
Panorama of the PowerLogic range
General information on power-monitoring software
Index of catalogue numbers

4
6
8
13
14

Current transformers

17

Basic panel meters

21

iAMP iVLT

iFRE

AMP/VLT

iCH/iCI

Basic energy meters

iEM2000

iEM3000

31

iME1

Power-monitoring units specification guide

38

Multi-circuit metering

42

BCPM

EM4800

Basic multi-function metering

iON6200

PM3000

PM5000

Intermediate metering

PM800

78

ION7330/7350

Advanced metering

ION7550/ION7650

94

CM4000T

Advanced utility metering

ION8650

108

ION8800

Communications

Energy Server Com'X 200 EGX100/300

Monitoring software

StruxureWare Power Monitoring Expert

2013

53

123

ION7550 RTU

StruxureWare PowerSCADA Expert

137

Gain energy insight and control with PowerLogic™
PowerLogic energy and power management systems

Energy insight = energy control
PowerLogic solutions help energy consumers and suppliers world-wide make the most of their energy. They enable businesses to improve their
competitiveness by giving them a complete understanding their organisation's unique energy landscape. PowerLogic technology also provides
hands-on tools to improve energy efficiency, reduce operating costs, enhance productivity, and increase power system reliability. Comprising
metering, communication hardware and advanced analysis software, a PowerLogic solution acts like a layer of intelligence across all of your
energy assets. It monitors key energy points and inputs 24 hours a day, then processes and delivers that data as timely and relevant information to
everyone that needs it.

•	 processes
•	 onsite generation

Industry

•	 power distribution

•	 generating stations
•	 transmission substations
•	 distribution substations

Utility

Critical
infrastructure
Utilities
Buildings

•	 servers
•	 branch circuits
•	 UPS
Intelligent energy
and power quality
meters

•	 tenants
•	 service entrance
•	 HVAC

PowerLogic
software

The PowerLogic advantage
PowerLogic solutions are the world’s largest and most advanced range of energy management products.
Thousands of organisations world-wide choose PowerLogic systems because of key advantages:
bb A fast, quantifiable return on investment through both a low total cost of ownership and
rich functionality that returns multiple financial benefits
bb A comprehensive portfolio of modular, scalable components that enable
	affordable system expansion as needs dictate and budgets allow
bb End-to-end interoperability offering seamless integration with business, accounting, BAS and SCADA applications
bb A complete range of compatible, complementary, single-sourced Schneider Electric power and automation solutions
bb Support for numerous global metering accuracy and power quality monitoring standards.

4

2013

Gain energy insight and control with PowerLogic™
(cont.)
Cutting-edge technology to increase profitability
PowerLogic technology converts the complex dynamics governing the relationship between power generation and distribution on the utility
side, and energy consumption, cost and reliability on the consumer side, into timely, easily understood information. Businesses can use this
powerful to improve tactical actions and strategic decision making.
From a single facility to an entire enterprise, PowerLogic meters monitor key distribution points 24 hours a day. Whether from generators,
substations, service entrances, mains, feeders, loads or 3rd party equipment and systems, PowerLogic technology tracks, records and reports
all real-time conditions and historical performance data. Intuative web-based interfaces give stakeholders access to this data as well as
advanced analytics, alarm annunciation and control capabilities. It supports comprehensive energy management programs by tracking
performance and empowering you to make effective decisions.

Applications

Energy availability
and reliability

Power availability
and reliability

bb Improve T&D network
	reliability

bb Validate that power quality
 	 complies with the energy contract

bb Enhance substation
	automation

bb Verify the reliable operation of
	 power and mitigation equipment

bb Maximise the use of your
	 existing infrastructure

bb Improve response to power	 related problems
bb Leverage existing infrastructure
	 capacity and avoid over-building

Revenue metering 
and power quality

bb Support proactive maintenance
	 to prolong asset life

bb Maximise metering accuracy
	 at all interchange	 points

Energy efficiency
and cost savings

bb Verify compliance with new
	 power quality standards

bb Measure efficiency, reveal
	 opportunities and verify
	savings

bb Analyse and isolate the source
	 of power quality problems

bb Manage green house gas
	emissions
bb Allocate energy costs to
	 departments or processes
bb Reduce peak demand and
	 power factor penalties
bb Enable participation in load
	 curtailment programs
	 (e.g. demand response)
bb Strengthen rate negotiation
	 with energy suppliers
bb Identify billing discrepancies
bb Sub-bill tenants for energy
	costs

2013

5

Market	segments

Industry
From finance to engineering, PowerLogic technology gives industry professionals
the energy intelligence and control they need to support strategic decisions and
establish best energy practices. It will help you reduce operational costs and meet
new emissions standards without compromising production schedules or product
quality. Key points are monitored throughout your power distribution, building and
backup systems. Enterprise-level software helps you maximise the use of your
existing energy assets, increase energy efficiency and avoid demand or power
factor penalties. Use it to uncover hidden power problems that can shorten
equipment life or cause costly downtime.

•	 cost allocation
•	 procurement optimisation
•	 power factor correction

•	 measurement and
verification
•	 infrastructure optimisation
•	 power quality analysis

Buildings
Building managers through operations staff can cut energy and maintenance costs
without effecting the comfort or productivity of their tenants, employees, students,
patients or customers. A PowerLogic system will track all utilities and equipment
conditions, and enterprise-level software will help you analyse and improve electrical
reliability. You can forecast energy requirements, optimise multi-site contracts and
accurately allocate or sub-bill costs. Key performance indicators help you find and
sustain energy savings, reduce emissions and meet “green” building standards in
order to increase asset value and attract or retain tenants.

•	 tenant sub-billing

•	 procurement optimisation

•	 cost allocation

•	 power availability

•	 energy efficiency /
benchmarking

•	 demand response / load
curtailment

6

2013

Market	 segments (cont.)

Critical infrastructure
PowerLogic technology helps keep your systems operating continuously and
securely with an economical supply of energy. Whether you manage data,
communication, transportation or environmental services, minimising the risk of
power-related downtime and keeping costs under control is a priority. A
PowerLogic solution monitors all power and cooling systems and accurately tracks
their energy consumption. Enterprise-level software delivers insightful diagnostics
and metrics to help verify the reliability of your backup systems and maximise the
use of existing capacity to defer new capital investments. You can also reveal
energy inefficiencies and strengthen energy procurement across multiple sites.

•	 infrastructure optimisation

•	 energy efficiency

•	 power quality analysis compliance •	 cost allocation
•	 alarming and event notification

•	 procurement
optimisation

Utilities
Today’s energy market is more complex than ever before. Whether you generate,
transmit or distribute electricity, more stakeholders need shared access to timely,
accurate energy data from more exchange points and you need to maintain power
availability and reduce price volatility in the face of rising demand and transmission
congestion. A PowerLogic energy information system helps you meet all of these
challenges by:
bb Metering all key interchange points with the highest possible accuracy
bb Improving the quality of power delivered to your customers
bb Essuring the reliability and efficiency of your network and equipment.
From advanced energy and power quality metering systems to enterprise-level
analytic software, PowerLogic solutions deliver business-critical information that
conventional metering, SCADA and billing systems cannot. It gives you the energy
intelligence and control needed to track performance, stay informed of critical
conditions and empower you to make strategic decisions. It will help you increase
reliability, maximise the use of resources and improve service.

•	 revenue metering
•	 power availability and reliability

2013

7

Panorama of the PowerLogic
range

Product selection guide

Current transformers

Basic panel meters

CT

Name

iAMP / iVLT

current transformer

Function

ammeter, voltmeter

Installation
b�insulated cable,
diameter 21 to 35 mm,
through transformer
b�busbar through transformer
b�cable connections

AMP / VLT

Applications
Panel instrumentation
I/U

Panel instrumentation

I/U

Energy efficiency and cost
Sub billing and cost allocation
Demand and load management
Billing analysis

Power availability and reliability
Compliance monitoring
Sag/swell, transient
Harmonics

Revenue metering
Revenue meter

Characteristics
b�transformation ratio:
40/5 A to 6000/5 A
b�accuracy: class 0.5 to 3
b�maximum rated
operational voltage: 720 V AC
b�tropicalised

Characteristics
Measurement accuracy

class 1.5

± 0.5 % ± 1 digit

class 1.5

Installation

DIN rail
4 x 18 mm modules

DIN rail
2 x 18 mm modules

flush mounted
72 x 72 mm
96 x 96 mm

Voltage measurement

VLT:
500 V AC direct
or external VT

VLT:
600 V AC direct
or external VT

VLT:
500 V AC direct
or external VT

Current measurement

AMP:
30 A direct
or external CT

AMP:
10 A direct
or external CT

AMP:
external CT

Communication ports
Inputs / Outputs
Memory capacity

page 17

8

page 21

2013

page 22

page 23

Panorama of the PowerLogic
range (cont.)

Product selection guide

Basic energy meters

iFRE

iCH / iCI

iEM2000 Series

frequency meter

hour counter
pulse counter

kilowatt-hour meters

F

hours /pulses

E

± 0.5 % ± 1 digit
DIN rail
2 x 18 mm modules

iME1

iEM3000 Series

class 1
CI, CH: DIN rail
2 x 18 mm modules
CH: flush mount

400 V AC direct

DIN rail
1.2 or 4 x 18 mm modules
400 V AC direct

40 to 63 A direct
or external CT

page 22

page 27

page 31

page 31

2013

page 34

9

Panorama of the PowerLogic
range (cont.)

Product selection guide

Multi-circuit metering

Basic multi-function metering

Name

BCPM

EM4800

ION6200

Function

branch circuit monitor
IEC 61036 Class 1

multi-circuit energy
meter
Class 0.5 ANSI C12.1,
C12.20
Class 0.5S IEC
62053-22

metering & sub-metering metering & sub-metering
Class 0.5S
Class 0.5S IEC 62053-22
IEC 60687
Class 1 IEC 62053-21
Class 2IEC 62053-23

metering & sub-metering
Class 0.5S
IEC 62053-22
Class 0.2S (PM55xx)
IEC 62053-22
Class 1/2 IEC 62053-24

I, U, F, P, Q, S, PF, E
(Power demand and
current demand)

I, U, F, P, Q, S, PF, E
(Power demand and
current demand)

I, U, F, P, Q, S, PF, E
(Power demand and
current demand)

I, U, F, P, Q, S, PF, E
(Power demand and
current demand)

I, U, F, P, Q, S, PF, E
(Power demand and
current demand)

Measurement accuracy
(active energy)

class 1 (mains active
energy)

Class 0.5S

Class 0.5

Class 0.5

Class 0.2S (PM55xx)
Class 0.5S

Installation

Installed in panel or
enclosure

Installed in panel or
enclosure

Flush mount
106.7 mm x 106.7 mm

DIN rail

Flush mount
96 mm x 96 mm

Voltage measurement

90 – 277 V Line to
Neutral voltage Inputs

80 - 480 V AC L-L without
PTs, Up to 999 kV with
external PTs

60 - 400 V AC L-N

50V to 330V AC (Ph-N)
80V to 570V AC (Ph-Ph)
up to 1MV AC (ext VT)

20 V L-N / 35 V L-L to
277 V L-N /480 V L-L
/600 V L-L (PM55xx)

Current measurement

CT strips for branch
Split- or solid-core CTs
circuits and external CTs
for mains

external CT

external CT

external CT

Communication ports

1 for main

2

1

1

2

2

2

PM3000 Series

PM5100/PM5300/
PM5500

Applications
Panel instrumentation
Panel instrumentation

Energy efficiency and cost
Sub billing and cost allocation
Demand and load management
Billing analysis

Power availability & reliability
Harmonics
Dip/swell, transient
Compliance monitoring

Revenue metering
Revenue metering

Characteristics

Inputs / Outputs

4 I/O
6 I/O (PM55xx)

Memory capacity

256 kb
1.1 MB (PM55xx)

page 42
10

page 50

2013

page 53

page 60

page 71

Panorama of the PowerLogic
range (cont.)

Product selection guide

Intermediate metering

Advanced metering

Advanced utility metering

ION7330/7350

ION7550 ION7650 CM4000T

ION8650
A
B

energy and basic PQ power meter
IEC 61557-12
PMD/SD/K70/0.5
PMD/SS/K70/0.5
ANSI 12.20 Class 0.2S real energy

energy and basic PQ power
meter
IEC 61557-12
PMD/SD/K70/0.5
PMD/SS/K70/0.5
ANSI 12.20 Class 0.2S real
energy

energy and power quality
meter
IEC 62052-11
IEC 62053-22/23
Class 0.2S
IEC 61000-4-30 Class A

I, U, F, P, Q, S, PF, E, THD, Min/Max,
harm, alarm, I/O (I, U unbalance,
demand, clock/cal (PM810 w/
PM810LOG))

I, U, F, P, Q, S, PF, E, THD,
harm, alarm, I/O
(Power demand and
current demand)

I, U, F, P, Q, S, PF, E (demand, minimum
and maximum values)

I, U, F, P, Q, S, PF, E (demand, minimum and
maximum values)

ANSI 62053-22 Class 0.5S
ANSI 12.20 Class 0.2S

Class 0.5S

Class 0.2S

Class 0.2S

Class 0.2S

Flush & DIN rail mount
96 mm x 96 mm

Flush & DIN rail mount
96 mm x 96 mm
TRAN 60 x 100 x 164.5 mm

600 V AC L-L / 347 V AC L-N

50-347 VAC L-N 3P (87-600 L-L)
50-300 VAC L-N 1P (100-600 L-L)

DIN 192
standard cutout
(186 x 186 mm)
57-347V L-N AC or
100-600V L-L AC

0 to 600 V AC
0 to 1200 kV
AC (ext. VT)

ANSI socket mount 9S,
DIN 43862 rack
35S, 36S, 39S and 76S;
FT21 switchboard case
57-277V L-N AC
57-288V L-N AC or
(9S, 36S);
99-500V L-L AC
120-480 V L-L AC (35S)

PM810

PM820/
PM850

PM870

energy and
power quality
meter
IEC 62053-22
ANSI 12.20
Class 0.2S real
energy

C

energy and power
quality meter
IEC 62052-11
IEC 62053-22/23
Class 0.2S
IEC 61000-4-30 Class A

ION8800
A
B

C

energy and power quality
meter
IEC 62052-11
IEC 62053-22/23
Class 0.2S
IEC 61000-4-30

w/PM810LOG

dip/swell
PM850 only

Class 0.2S

external CT

external CT

external CT

external CT

external CT

external CT

external CT

external CT

external CT

3

3

3

3

3

5

3

5

5

18 I/O

18 I/O

18 I/O

8 I/O

8 I/O

up to 32 I/O

up to 25 I/O

up to 22 I/O

up to 16 I/O

80 kbytes with
PM810 LOG

80 / 800 kbytes 800 kbytes

300 kbytes

300 kbytes

up to 10 MB

up to 32 MB

10 MB

page 78

page 86

page 94

2013

page 101

4 MB

2 MB

page 108

up to 10 MB

page 116
11

Panorama of the PowerLogic
range (cont.)

Product selection guide

Communications

Monitoring Software

Name

Com'X 200

EGX100

EGX300

ION7550 RTU

StruxureWare
StruxureWare
Power Monitoring PowerSCADA
Expert
Expert

Function

Ethernet GPRS
data logger

Ethernet gateway

Integrated
gateway-server

Ethernet
gateway-server +
onboard I/O

Power management

Network protection
and control

Devices supported

EM3000 Series,
iEM3000 Series,
PM800 Series,
ION6200,
ION7300,
Acti 9 Smartlink
Masterpact,
PM5000 Series,
Compact NSX,
iEM1,
iEM2000,
iEM3000,
PM3000 Series

PM800 Series,
CM4000 Series,
Sepam Series

Acti 9 Smartlink,
BCPM Series,
CM Series
PM800 Series,
CM4000 Series,
DM6000, DM6300,
iEM3000 Series,
ION6200, ION8600,
ION8800,
ION7550/7650,
PM1000, PM200,
PM300, PM5350,
PM700,
PM800,Sepam
Series,
Compact NSX,
Vigilohm IM20/
IM20-H

ION8800,
ION7550/7650,
ION6200,
Modbus devices

ION8800,
ION8650,
ION7550/7650,	
ION7550RTU,
ION6200,
PM800 Series,
EM1200,
EM5600,
CM4000 Series,
BCPM,
Sepam Series,
Compact NSX,
Vigilohm IM20,
Modicon Mementum M1
- TR8,
Twido Modular	 PLC

Sepam Series 40
PM800 Series
BCPM/BCM42
CM4000 Series

Web server with
standard HTML pages

(Configuration only) (Configuration only)

10/100 Base
TX port

10/100 Base
TX port

10/100 Base
TX port

RS485 (2-wire / 4-wire) ports 1
Modbus protocol

1

1

1

Number of devices
connected directly

32

64

64

1

1

1

Features

RS485 / Ethernet gateway

Web server with
custom HTML pages
Real time data
Historical data

Export to Internet
database server

Automatic notification
Alarm and event logs
Waveform display
Custom animated graphics
Manual/automatic reports

Characteristics

Ethernet ports
Modbus TCP/IP protocol

2

32 modbus
devices
6 pulse meters (or
dry contacts) – 2

RS232 configuration ports
Miscellaneous

Connectivity: WiFi, Serial line to
GPRS,or Ethernet Ethernet
connectivity

Entry-level Energy modem port
Management in a I/O (24 I/30 O max)
box

Installation

DIN rail

DIN rail

page 125
12

DIN rail

page 127

DIN 192 cutout
(186 x 186 mm)

page 129

2013

page 139

page 145

Product selection guide

General information on
power-monitoring software

Software, a tool serving site operation.
A site can be compared to a living organism.
The power system manager has no control over the
changes that affect this organism, but must ensure that
it continues to receive the energy it requires.
Similar to a doctor, the power system manager must
carry out preventive measures and diagnose and
remedy any problems that occur. The goal is to
maintain the site in a healthy state, without generating
any secondary effects.
Software enables managers to diagnose the causes of
most problems encountered on electrical systems.

More and more devices are capable of communicating.
The number of available measurements is also on the rise, creating the need for a
tool to successfully manage all the information.
The main purpose of software is to simplify complex sites so that they can be
managed by humans:
bb make the site and its operation intelligible
bb make the power system tangible and visible.

The role of software
All measurements at a single location
All measured values may be accessed via a PC.

Organisation and use of measurements

Before they may be used, certain measurements must be organised, processed or
integrated in special tools.

PE86194

Device setup
Simple devices may be set up on their front panels.
For devices with advanced functions, local setup is often difficult and even
impossible for some functions.
Software greatly facilitates device setup.

Automatic tasks

Software can execute tasks automatically, triggered by:
b�a date
b�an event
b�an alarm.
These tasks may concern devices (reset, start of a particular function) or system
users (transmission of an e-mail, etc.).

Manual commands

Power-monitoring software can also be used to control devices (e.g. open or close a
circuit breaker).
Certain control/monitoring functions (automatic action on electrical-distribution
system) are carried out by PLCs integrated in the PowerLogic System architecture.

Access via the Web

Information must be adapted to user needs and then made available to them.
Software can handle the adaptation by preparing custom reports.
These reports can then be accessed by any PC on the site using a standard
Web browser.

Software and architecture

Software must be capable of meeting a large number of needs:
b�single-user or multi-user operation
b�data organisation according to user profiles
b�adaptation to different site topologies
b�data exchange with other systems, etc.
This set of constraints means that a single product is not sufficient; a range of
software products is required.

2013

13

Index of catalogue numbers

Cat. no.

Description

Page

15125
15126

CMV voltmeter selector switch, DIN rail
CMA ammeter selector, DIN rail

25
25

15201
15202
15208
15209

iVLT digital voltmeter, DIN rail
iAMP direct reading digital ammeter, DIN rail
iFRE digital frequency meter, DIN rail
iAMP multi-rating digital ammeter, DIN rail

22
22
22
22

15440
15443

iCH hour counter, DIN rail (230 V AC)
iCI impulse counter, DIN rail

27
28

15607
15608
15609

CH hour counter, 48 x 48 (24 V AC)
CH hour counter, 48 x 48 (230 V AC)
CH hour counter, 48 x 48 (12 to 36 V DC)

27
27
27

16003

AMP analogue ammeter, 72 x 72, for motor feeders
(delivered without dial)
AMP analogue ammeter, 72 x 72, for standard
feeders (delivered without dial)
VLT analogue voltmeter, 72 x 72
Dial, 0-30-90 A, for AMP 16003
Dial, 0-75-225 A, for AMP 16003
Dial, 0-200-600 A, for AMP 16003
Dial, 0-50 A, for AMP 16004
Dial, 0-100 A, for AMP 16004
Dial, 0-200 A, for AMP 16004
Dial, 0-400 A, for AMP 16004
Dial, 0-600 A, for AMP 16004
Dial, 0-1000 A, for AMP 16004
Dial, 0-1250 A, for AMP 16004
Dial, 0-1500 A, for AMP 16004
CMA ammeter selector switch, 48 x 48
CMV voltmeter selector switch, 48 x 48
Dial, 0-2000 A, for AMP 16004
iAMP analogue ammeter for direct connection, DIN
rail
iAMP analogue ammeter for connection to TC
(delivered without dial), DIN rail
Dial, 0-5 A, for iAMP 16030
Dial, 0-50 A, for iAMP 16030
Dial, 0-75 A, for iAMP 16030
Dial, 0-100 A, for iAMP 16030
Dial, 0-150 A, for iAMP 16030
Dial, 0-200 A, for iAMP 16030
Dial, 0-250 A, for iAMP 16030
Dial, 0-300 A, for iAMP 16030
Dial, 0-400 A, for iAMP 16030
Dial, 0-500 A, for iAMP 16030
Dial, 0-600 A, for iAMP 16030
Dial, 0-800 A, for iAMP 16030
Dial, 0-1000 A, for iAMP 16030
Dial, 0-1500 A, for iAMP 16030
Dial, 0-2000 A, for iAMP 16030
iVLT analogue voltmeter (0-300 V), DIN rail
iVLT analogue voltmeter (0-500 V), DIN rail
AMP analogue ammeter, 96 x 96, for motor feeder
(delivered without dial)
AMP analogue ammeter, 96 x 96, for standard feeder
(delivered without dial)
VLT analogue voltmeter, 96 x 96
Dial, 0-30-90 A, for AMP 16073
Dial, 0-75-225 A, for AMP 16073
Dial, 0-200-600 A, for AMP 16073
Dial, 0-50 A, for AMP 16074
Dial, 0-100 A, for AMP 16074
Dial, 0-200 A, for AMP 16074
Dial, 0-400 A, for AMP 16074
Dial, 0-600 A, for AMP 16074

23

15100
15200

15400
15600

16000
16004
16005
16006
16007
16008
16009
16010
16011
16012
16013
16014
16015
16016
16017
16018
16019
16029
16030
16031
16032
16033
16034
16035
16036
16037
16038
16039
16040
16041
16042
16043
16044
16045
16060
16061
16073
16074
16075
16076
16077
16078
16079
16080
16081
16082
16083

14

Cat. no.
16084
16085
16086
16087
16088
16089
16090
16091
16092

Description
Dial, 0-1000 A, for AMP 16074
Dial, 0-1250 A, for AMP 16074
Dial, 0-1500 A, for AMP 16074
Dial, 0-2000 A, for AMP 16074
Dial, 0-2500 A, for AMP 16074
Dial, 0-3000 A, for AMP 16074
Dial, 0-4000 A, for AMP 16074
Dial, 0-5000 A, for AMP 16074
Dial, 0-6000 A, for AMP 16074

Page
24
24
24
24
24
24
24
24
24

16451
16452
16453
16454
16455
16456
16459
16460
16461
16462
16463
16464
16465
16468
16469
16470
16471
16473
16474
16476
16477
16478
16479
16480
16481
16482
16483

TC 50/5 tropicalised transformer for cables
TC 75/5 tropicalised transformer for cables
TC 100/5 tropicalised transformer for cables
TC 125/5 tropicalised transformer for cables
TC 150/5 tropicalised transformer for cables
TC 200/5 tropicalised transformer for cables
TC 150/5 tropicalised transfo. for cables and busbars
TC 200/5 tropicalised transfo. for cables and busbars
TC 250/5 tropicalised transfo. for cables and busbars
TC 300/5 tropicalised transformer for cables
TC 400/5 tropicalised transfo. for cables and busbars
TC 500/5 tropicalised transfo. for cables and busbars
TC 600/5 tropicalised transfo. for cables and busbars
TC 250/5 tropicalised transfo. for cables and busbars
TC 300/5 tropicalised transfo. for cables and busbars
TC 400/5 tropicalised transfo. for cables and busbars
TC 500/5 tropicalised transfo. for cables and busbars
TC 500/5 tropicalised transformer for busbars
TC 600/5 tropicalised transformer for busbars
TC 200/5 tropicalised transformer for busbars
TC 250/5 tropicalised transformer for busbars
TC 300/5 tropicalised transformer for busbars
TC 400/5 tropicalised transformer for busbars
TC 500/5 tropicalised transformer for busbars
TC 600/5 tropicalised transformer for busbars
TC 800/5 tropicalised transformer for busbars
TC 1000/5 tropicalised transformer for busbars

18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18

24

16500
16534
16535
16537
16538
16540
16541
16542
16543
16544
16545
16546
16547
16548
16549
16550
16551
16552
16553

TC 40/5 tropicalised transformer for cables
TC 1250/5 tropicalised transformer for busbars
TC 1500/5 tropicalised transformer for busbars
TC 1250/5 tropicalised transformer for busbars
TC 1500/5 tropicalised transformer for busbars
TC 1250/5 tropicalised transformer for busbars
TC 1500/5 tropicalised transformer for busbars
TC 2000/5 tropicalised transformer for busbars
TC 2500/5 tropicalised transformer for busbars
TC 3000/5 tropicalised transformer for busbars
TC 2500/5 tropicalised transformer for busbars
TC 3000/5 tropicalised transformer for busbars
TC 4000/5 tropicalised transformer for busbars
TC 5000/5 tropicalised transformer for busbars
TC 6000/5 tropicalised transformer for busbars
Cylinder Ø 8.5 mm for TC transformer
Cylinder Ø 12.5 mm for TC transformer
Lead-sealable cover for TC transformer
Lead-sealable cover for TC transformer

18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18

24
24
24
24
24
24
24
24
24

A9M17065
A9M17066
A9M17067
A9MEM2000T
A9MEM2000
A9MEM2010
A9MEM3100
A9MEM3110
A9MEM3115

ME1 digital kilowatt-hour meter
iME1z digital kilowatt-hour meter
iME1zr digital kilowatt-hour meter
iME2000T single-phase kilowatt-hour meter
iME2000 single-phase kilowatt-hour meter
iME2010 single-phase kilowatt-hour meter
iEM3100 basic energy meter
iEM3110 energy meter with pulse output
iEM3115 multi-tariff energy meter

31
31
31
31
31
31
37
37
37

23
23
23
23
23
23
23
23
23
23
23
23
23
25
25
25
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
26
24

16400

16500

A

2013

Index of catalogue numbers
(cont.)

Cat. no.
A9MEM3135
A9MEM3150
A9MEM3155
A9MEM3165
A9MEM3175
A9MEM3200
A9MEM3210
A9MEM3215
A9MEM3235
A9MEM3250
A9MEM3255
A9MEM3265

Description
iEM3135 advanced multi-tariff energy meter &
electrical parameter plus M-Bus comm port
iEM3150 energy meter & electrical parameter
plus Modbus RS485 comm port

iEM3155 advanced multi-tariff energy meter & electrical
parameter plus Modbus RS485 comm port
iEM3165 advanced multi-tariff energy meter & electrical
parameter plus Modbus, BACnet MS/ TP comm port
iEM3175 advanced multi-tariff energy meter & electrical
parameter plus LON TP/FT-10 comm port

iEM3200 basic energy meter
iEM3210 energy meter with pulse output
iEM3215 multi-tariff energy meter
iEM3235 advanced multi-tariff energy meter &
electrical parameter plus M-Bus comm port
iEM3250 energy meter & electrical parameter plus
RS485 comm port
iEM3255 advanced multi-tarrif energy meter &
electrical parameter plus RS485 comm port

Page
37
37

37
37
37
37
37
37
37

EBX200
EBXA-USB-WIFI
EBXA-GPRS-SIM
EBXA-GPRS
EBXA-ANT-5M
EGX100MG
EGX300

Com'X 200 Ethernet data logger
Com'X 200 WiFi USB stick
Com'X 200 GPRS modem with SIM card
Com'X 200 GPRS modem without SIM card
Com'X 200 External GPRS antenna
EGX100 Ethernet gateway
EGX300 Ethernet server

125
125
125
125
125
127
127

IE7PRIMARY

StruxureWare Power Monitoring Primary server
(DVD, includes all available languages)

147

IE7DLS

Individual Device Licence for High-End Devices.
Compatible with all device types.
IE7DLM
Individual Device Licence for Mid-Range Devices.
Compatible with Mid- and Entry-range devices.
IE7DLE
Individual Device Licence for Entry-Range
Devices. Compatible with Entry range devices.
IE7ENGCLIENT Engineering Client Licence (DVD) - Access to
Management Console, Vista, Designer, Reporter
and Web applications; one licence per user.

37

BCPMA042S
BCPMA084S

42 circuit BCPM 3/4" CT spacing - Advanced
84 circuit BCPM 3/4" CT spacing - Advanced

45
45

BCPMA142S
BCPMA184S
BCPMB042S
BCPMB084S
BCPMB142S
BCPMB184S
BCPMC042S
BCPMC084S
BCPMC142S
BCPMC184S
BCPMCOVERS
BCPMSCA30S
BCPMSCA42S
BCPMSCA60S
BCPMSCA84S
bcpmscadpbs
BCPMSCB30S
BCPMSCB42S
BCPMSCB60S
BCPMSCB84S
BCPMSCC30S
BCPMSCC42S
BCPMSCC60S
BCPMSCC84S
BCPMSCCT0
BCPMSCCT0R20
BCPMSCCT1
BCPMSCCT1R20
BCPMSCCT3
BCPMSCCT3R20

44 circuit BCPM 1" CT spacing - Advanced
84 circuit BCPM 1" CT spacing - Advanced
42 circuit BCPM 3/4" CT spacing - Intermediate
84 circuit BCPM 3/4" CT spacing - Intermediate
42 circuit BCPM 3/4" CT spacing - Intermediate
84 circuit BCPM 1" CT spacing - Intermediate
42 circuit BCPM 3/4" CT spacing - Basic
84 circuit BCPM 3/4" CT spacing - Basic
42 circuit BCPM 1" CT spacing - Basic
84 circuit BCPM 1" CT spacing - Basic
Circuit board cover BCPM
30 split-core CTs, Advanced BCPM
42 split-core CTs, Advanced BCPM
60 split-core CTs, Advanced BCPM
84 split-core CTs, Advanced BCPM
Adapter bord, for split core BCPM
30 split-core CTs, Intermediate BCPM
42 split-core CTs, Intermediate BCPM
60 split-core CTs, Intermediate BCPM
84 split-core CTs, Intermediate BCPM
30 split-core CTs, Basic BCPM
42 split-core CTs, Basic BCPM
60 split-core CTs, Basic BCPM
84 split-core CTs, Basic BCPM
Split core CTs, BCPM 50 A
Split core CTs, BCPM 50 A
Split core CTs, BCPM 100 A
Split core CTs, BCPM 100 A
Split core CTs, BCPM 200 A
Split core CTs, BCPM 200 A

45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45
45

CAB4
CAB12
CAB30
CBL008
CBL016
CBL017
CBL018
CBL019
CBL020
CBL021
CBL022
CBL023
CBL024
CD-TECHDOC

PM/CM <-> display connection cable (1.25 m)
PM/CM <-> display connection cable (3.65 m)
PM/CM <-> display connection cable (9.14 m)
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Fiat Ribbon cable for BCPM
Round Ribbon cable for BCPM
Round Ribbon cable for BCPM
Round Ribbon cable for BCPM
Latest version of technical documentation for
StruxureWare Power Monitoring

85
85
85
49
49
49
49
49
49
49
49
49
49
143

C

Page
101
101

I

37

B

Description
Circuit monitor CM4000T
Circuit monitor CM4000T

E

37

iEM3265 advanced multi-tariff energy meter & electrical
parameter plus Modbus, BACnet MS/ TP comm port
iEM3275 advanced multi-tariff energy meter & electrical
parameter plus LON TP/FT-10 comm port

A9MEM3275

Cat. no.
CM4MA
CNV100

37

147
147
147
147

IE7WEBCLIENT Web Client Licence - Access to Diagrams, Tables,
Alarms, Reports, Dashboard; one licence per user.
IE7UNLCLIENT Unlimited Licence for unlimited number of users
(Engineering or Web applications); mandatory for
public displays or Internet hosting.

147

IE7OPCSERVER
IE7SECONDARY

147
147

147

OPC DA Server for StruxureWare Power Monitoring
Secondary Server for StruxureWare Power Monitoring
Upgrades from earlier versions
IE7PRIMARYUPG StruxureWare Power Monitoring UPGRADE
software (DVD, includes all available languages)
IE7DLSUPG
Upgrade DL-S device licence
IE7DLMUPG
Upgrade DL-M device licence

147
147

IE7DLEUPG

147

Upgrade DL-E device licence

147

IE7ENGCLIENTUPG Engineering Client Upgrade Licence - Access to
Management Console, Vista, Designer, Reporterand
Web applications; one licence per user.

147

IE7WEBCLIENTUPG Web Client Upgrade Licence - Diagrams, Tables,
Alarms, Reports; one licence per user

147

IE7UNLCLIENTUPG Unlimited Client Upgrade Licence for unlimited
number of users (Engineering or Web applications);
mandatory for public displays or internet hosting.

147

IE7SECONDARYUPG

Secondary Server Upgrade for StruxureWare
Power Monitoring Technical Documentation

147

LVCT00102S
LVCT00202S
LVCT00302S
LVCT00403S
LVCT00603S
LVCT00803S
LVCT00804S
LVCT01004S
LVCT01204S
LVCT01604S
LVCT02004S
LVCT02404S

100 A
200 A
300 A
400 A
600 A
800 A
800 A
1000 A
1200 A
1600 A
2000 A
2400 A

46
46
46
46
46
46
46
46
46
46
46
46

M7550

ION7550 energy and power quality meter

M6200T1A0B0A0A0R
M6200T1A0B0A0A0P
M6200R1A0B0A0B0R
M6200M0A0B0A0B0R
M6200M0A0B0A0A0R
M6200A0A0B0Z0A0P
M6200A0A0B0Z0A0N
M6200A0A0B0A0B0R
M6200A0A0B0A0A0R
M6200A0A0B0A0A0P

ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter
ION6200 energy meter

98,
129
53
53
53
53
53
53
53
53
53
53

L

M

2013

15

Index of catalogue numbers

Cat. no.
M620DR1
M620DN1
M7330
M7350
M7550
M7650
M8650A
M8650B
M8650C
M8800A
M8800B
M8800C
METSEEM480525
METSEEM483325
METSEEM488025
METSEEM480516
METSEEM483316
METSEEM488016
METSEEM480526
METSEEM483326
METSEEM488026
METSEPM3200
METSEPM3210
METSEPM3250
METSEPM3255
METSEPM5100
METSEPM5110
METSEPM5111
METSEPM5310
METSEPM5320
METSEPM5330
METSEPM5331
METSEPM5340
METSEPM5341
METSEPM5560
METSEPM5561
METSEPM5563

O

Description
ION6200 energy meter
ION6200 energy meter
ION7330 energy and power quality meter
ION7350 energy and power quality meter
ION7550 energy and power quality meter
ION7650 energy and power quality meter
ION8650A energy and power quality meter
ION8650B energy and power quality meter
ION8650C energy and power quality meter
ION8800A energy and power quality meter
ION8800B energy and power quality meter
ION8800C energy and power quality meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PowerLogic E4800 multi-circuit energy meter
PM3200 basic power meter
PM3210 power meter with pulse output
PM3250 power meter with RS485 port
PM3255 power meter with 2 DI, 2 DO, RS485 port
PM5100 power meter
PM5110 power meter
PM5111 power meter
PM5310 power meter
PM5320 power meter
PM5330 power meter
PM5331 power meter
PM5340 power meter
PM5341 power meter
PM5560 power meter
PM5561 power meter
PM5563 power meter

OPTICAL-PROBE Optical communication interface

P

PLS101110-11
PLS101111
PLS101111-12
PLS101112
PLS101112-13
PLS101113
PLS101113-14
PLS101114
PLS101114-15

PowerSCADA Expert 75-150 Server Lic. pt expansions

PLS101115
PLS101115-99

PowerSCADA Expert 15000 Server licences

PLS101199
PLS102010
PLS102010-11
PLS102011-12
PLS102012
PLS102012-13
PLS102013
PLS102013-14
PLS102014
PLS102014-15
PLS102015
PLS102015-99
PLS102088

16

Page
57
57
95
95
98
98
112
112
112
120
120
120
50
50
50
50
50
50
50
50
50
60
60
60
60
71
71
71
71
71
71
71
71
71
71
71
71
113

153
153
PowerSCADA Expert 150-500 Server Lic. pt expansions
153
PowerSCADA Expert 500 Server licences
153
PowerSCADA Expert 500-1500 Server Lic. pt expansions
153
PowerSCADA Expert 1500 Server licences
153
PowerSCADA Expert 	 1500-5000 Server Lic. pt expansions 153
PowerSCADA Expert 5000 Server licences
153
PowerSCADA Expert 	 5000-15000 Server Lic. pt
153
PowerSCADA Expert 150 Server licences

expansions

PowerSCADA Expert 	
expansions

15000-unlimtd. Server Lic. pt

153
153

PowerSCADA Expert unlimited Server licences
PowerSCADA Expert 75 Control Client licences

153
153
PowerSCADA Expert 	 75-150 Control Lic. pt expansions
153
PowerSCADA Expert 	 150-500 Control Lic. pt expansions
153
PowerSCADA Expert 500 Control Client licences
153
PowerSCADA Expert 	 500-1500 Control Lic. pt expansions 153
PowerSCADA Expert 1500 Control Client licences
153
PowerSCADA Expert 	 1500-5000 Control Lic. pt
153
expansions

PowerSCADA Expert 5000 Control Client licences
PowerSCADA Expert 	
expansions

5000-15000 Control Lic. pt

PowerSCADA Expert 	

unlimited Control Lic. pt expansions

PowerSCADA Expert 15000 Control Client licences
PowerSCADA Expert Redundant (CC floating
licence)

Cat. no.
PLS102099

PM810MG
PM810RDMG
PM810UMG
PM820MG
PM820RDMG
PM820UMG
PM850MG
PM850RDMG
PM850UMG
PM870MG
PM870RDMG
PM870UMG
PM8ECC
PM8M22
PM8M26
PM8M2222
PM8RDA
PM8RDMG

Description
PowerSCADA Expert unlimited Control Client
licences
PowerSCADA Expert 75 Web Control licences
75 - 150 Serveur licence point expansion
PowerSCADA Expert 150 Web Control licences
150 - 500 Serveur licence point expansion
PowerSCADA Expert 500 Web Control licences
500 - 1500 Serveur licence point expansion
PowerSCADA Expert 1500 Web Control licences
1500 - 5000 Serveur licence point expansion
PowerSCADA Expert 5000 Web Control licences
5000 - 15000 Serveur licence point expansion
PowerSCADA Expert 15000 Web Control licences
15000 unlimited Serveur licence point expansion
PowerSCADA Expert Redundant (WC floating
licence)
PowerSCADA Expert unlimited Web Control licences
PowerSCADA Expert Redundant (VOC
floatingLicence)
PowerSCADA Expert View Only Client Licence
PowerSCADA Expert Redundant WVOC (floating
licence)
PowerSCADA Expert Web View Only Client Licence
Gold 1 year support, renewal
Silver 1 year support, first year, compulsory
Gold 1 year support, first year
Silver 1 year support, renewal
Subscription 1 year support renewal
Reprogramming free - Authorisation code
PowerSCADA Expert additional Parallel key
PowerSCADA Expert box with DVD and Parallel key
PowerSCADA Expert additional USB key
PowerSCADA Expert box with DVD and USB key
Optional logging module for on-board data recording
for PM810
PM810 Power Meter with integrated display
Meter and remote display kit
PM810 Power Meter without display
PM820 Power Meter with integrated display
Meter and remote display kit
PM820 Power Meter without display
PM850 Power Meter with integrated display
Meter and remote display kit
PM850 Power Meter without display
PM870 Power Meter with integrated display
Meter and remote display kit
PM870 Power Meter without display
PM8ECC module for PM Series 800
PM8M22 module for PM Series 800
PM8M26 module for PM Series 800
PM8M2222 module for PM Series 800
Remote display and adapter alone
Remote display and adapter with a 3.55 m cable

83

RJ11EXT

RJ11 Extender kit to mount RJ11 jack in panel door

85

PLS102210
PLS102210-11
PLS102211
PLS10211-12
PLS102212
PLS102212-13
PLS102213
PLS102213-14
PLS102214
PLS102214-15
PLS102215
PLS102215-99
PLS102288
PLS102299
PLS103088
PLS103099
PLS103288
PLS103299
PLS109101
PLS109102
PLS109103
PLS109122
PLS109139
PLS109401
PLS109911
PLS109912
PLS109921
PLS109922
PM810LOG

R

153
153
153
153
153

2013

Page
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83

CT current transformers

Current transformers

Function
056853NMD-2

The Ip/5A ratio current transformers deliver at the secondary a current of 0 to 5 A that
is proportional to the current measured at the primary. They are available in two
major families:
bb cable current transformers
bb bar current transformers.
This allows them to be used in combination with measurement instruments:
ammeters, kilowatt-hour meters, measurement units, control relays, etc.

Common technical data

16453.

056854NMD-2

bb Secondary current: 5 A
bb Max. voltage rating Ue: 720 V
bb Frequency: 50/60 Hz
bb Safety factor (sf):
vv 40 to 4000 A: sf y 5
vv 5000 to 6000 A: sf y 10.
bb Degree of protection: IP20
bb Operating temperature: tropicalised range, -25°C to +60°C, relative
humidity > 95 %
bb Compliance with standards: IEC 60044-1 and VDE 0414
bb Secondary connection (as per model):
vv by terminals for lug
vv by tunnel terminals
vv by screws.

056852NMD-2

16462.

DB114269

DB114266

Connection

PB100316

16542.

DB114268

056855MD-2

16453 + 16550.

DB114267

CT with let-through primary.

Sealable cover.

CT with primary connection by screw and nut.
Use of cylinder 16550 or 16551.
The three references 16482, 16483 and 16534 have a double connection output at the
secondary: twice S1 and twice S2. The terminals are in parallel, as there is only one secondary
winding.
The unused secondary outputs must not be connected.

2013

17

CT current transformers (cont.)

Current transformers

Catalogue numbers
Rating
Ip/5 A

40 A
50 A
75 A
100 A
125 A
150 A
200 A

250 A

300 A

400 A

500 A

600 A

800 A
1000 A
1250 A

1500 A

2000 A
2500 A
3000 A
4000 A
5000 A
6000 A

Power (VA)
Accuracy class:
0.5
2
2.5
3
1.5
4
4
6
2.5
1
7.5
4
1.5
10.5
8
4
12
10
2

1
1.25
1.5
2.5
3.5
4
5.5
5.5
7
2
9
5
4
11
8
6
15
12
8
18
12
4

3
1
1.5
2.5
3.5
4
5
6.5
6
8.5
5
11
8
6
13.5
12
7
18
15
10
22
15
6

8
14.5
4

10
21.5
6

8
12
15
15
12
8
20
15
10
15
20
30
25
40
50
60
70

12
15
20
20
15
12
25
20
15
20
25
50
30
60
60
120
120

Insulated cable:
Dimension Weight (g) Cat. no.
maximum
opening for
Tropicalised CT
maximum
cross-section (1) bars
diameter (1)
(mm)
(mm2)
21
21
21
21
21
21
22
21
22
22
35
22
35
22
35
22
35
-

120
120
120
120
120
120
150
120
150
150
240
150
240
150
240
150
240
-

12
26
8

22
-

150
-

15
20
25
25
20
30
25
60
60
60
-

-

-

30 x 10
30 x 10
65 x 32
30 x 10
40 x 10
65 x 32
30 x 10
40 x 10
65 x 32
30 x 10
40 x 10
65 x 32
30 x 10
40 x 10
64 x 11
51 x 31
65 x 32
30 x 10
64 x 11
51 x 31
65 x 32
65 x 32
65 x 32
65 x 32
84 x 34
127 x 38
65 x 32
84 x 34
127 x 38
127 x 38
127 x 38
127 x 52
127 x 38
127 x 52
127 x 52
165 x 55
165 x 55

Cylinder (2)

Sealable cover

200
200
200
200
200
200
270
200
270
600
270
430
600
270
430
600
270
430
600
270
430
500

16500
16451
16452
16453
16454
16455
16459
16456
16460
16476
16461
16468
16477
16462
16469
16478
16463
16470
16479
16464
16471
16473

16550 (3)
16550
16550
16550
16550
16550
16551 (4)
16550
16551
16551
16551
16551
16551
-

built-in
built-in
built-in
built-in
built-in
built-in
16552
built-in
16552
built-in
16552
16553
built-in
16552
16553
built-in
16552
16553
built-in
16552
16553
built-in

600
270
500

16480
16465
16474

16551
-

built-in
16552
built-in

600
600
600
600
700
1500
600
700
1000
1000
1000
1300
1000
1300
1300
5000
5000

16481
16482
16483
16534
16537
16540
16535
16538
16541
16542
16543
16545
16544
16546
16547
16548
16549

-

built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in
built-in

(1) Cable(s) that can be routed through the CT
(2) For CT with primary connection by screw and nut.
(3) Cylinder with inner dia. 8.5 mm, L = 32 mm
(4) Cylinder with inner dia. 12.5 mm, L = 62 mm

Fastening mode
CT cat. no.
16451...16456
16459...16471
16473 and 16474
16476...16483
16500
16534...16549

18

2013

Adapter for
DIN rail
b
b
b
-

Mounting
plate
b
b
b
b
-

Insulated locking screw
b
b
b
b

Current transformers

CT current transformers (cont.)

Choosing a current transformer
Choice of a CT depends on 2 criteria:
bb the Ip/5 A ratio
bb the installation type.

The Ip/5 A ratio
We recommend that you choose the ratio immediately higher than the maximum
measured current (In).
Example: In = 1103 A; ratio chosen = 1250/5.
For small ratings from 40/5 to 75/5 and for an application with digital devices, we
recommend that you choose a higher rating, for example 100/5.
This is because small ratings are less accurate and the 40 A measurement, for
example, will be more accurate with a 100/5 CT than with a 40/5 CT.
The installation type
Choice of a CT model depends on the installation type:
bb insulated cables
bb mounting on bars.

Important precaution

Never open the secondary circuit of a current transformer when the primary circuit is
energised.
Prior to working on the secondary circuit, the secondary terminals of the current
transformer must be short-circuited.

Determining the accuracy class of a CT

The accuracy class depends on the apparent power (VA) of the transformer and on
consumption of the complete measurement system.
The latter allows for consumption of all the devices and the connecting cables.
For a given accuracy class, consumption of the measurement system must not
exceed apparent power (VA) of the CT transformer.
Copper cable cross-section (mm2)
1
1.5
2.5
4
6
10
16

Power in VA per doubled meter at 20°C
1
0.685
0.41
0.254
0.169
0.0975
0.062

For each temperature variation per 10°C bracket, the power drawn up by the cables increases by
4 %.
Schneider Electric device
Ammeter 72 x 72 / 96 x 96
Analogue ammeter
Digital ammeter
PM800, CM4000

Consumption of the current input in VA
1.1
1.1
0.3
0.15

Example: consumption of a measurement system at 20°C
PM800
4 meters of 2.5 mm2 doubled wires
i.e. a measurement system consumption

+
=

0.15 VA
1.64 VA
1.79 VA

Based on the result, the CT accuracy class is determined (see previous page):
bb class 3 for a 75/5 ratio CT
bb class 0.5 for a 100/5 ratio CT

2013

19

CT current transformers (cont.)

Current transformers

Specific case of the motor starter
To measure motor starter current, you must choose a CT with primary current
Ip = Id/2 (Id = motor starting current).

Practical advice

DB109835

DB109834

Use a current transformer to measure a nominal current of 50 A.

50/5 A CT: Imax = 50 A

100/5 A CT, 2 cable openings: Imax = 50 A

To divide by 2 the nominal current of a transformer, you only need to pass the current
to be measured twice through this transformer.

Cat. no. 16540 to 16544

DB109816

DB109815

DB109819

Cat. no. 16468 to 16471

Cat. no. 16534 to 16535, 16476 to 16483

Cat. no. 16537 and 16538
DB114270

DB109820

Cat. no. 16473 and 16474

Cat. no. 16459 to 16465
DB109818

DB109817

Cat. no. 16500, 16451 to 16456

DB109821

DB109814

Dimensions

Cat. no. 16545 to 16547

Cat. no. 16548 and 16549

DB109824

DB109823

Cylinders

Cat. no. 16550

20

2013

Cat. no. 16551

Basic panel meters

DIN rail analogue ammeters and
voltmeters
0

Function
DB119006

iAMP
Ammeters measure the current flowing through an electric circuit in amps.
iVLT
Voltmeters measure the potential (voltage) difference of an electric circuit in volts.

Common technical data

DB119005

iAMP.

iVLT.

Accuracy: class 1.5.
bb Complies with standards IEC 60051-1, IEC 61010-1 and IEC 61000-4.
bb Ferromagnetic device.
bb Pseudo-linear scale over 90°.
bb Ammeters (except catalogue number 16029):
vv connection on CT, ratio In/5, to be ordered separately
vv interchangeable dials.
bb Temperature:
vv operating temperature: -25°C to +55°C.
vv reference temperature: 23°C.
bb Influence of temperature on accuracy: ±0.03 % /°C.
bb Utilisation frequency: 50/60 Hz.
bb Consumption:
vv AMP: 1.1 VA
vv VLT catalogue number 15060: 2.5 VA
vv VLT catalogue number 16061: 3.5 VA.
bb Permanent overload:
vv AMP: 1.2 In
vv VLT: 1.2 Un.
bb Maximum overload for 5 s:
vv AMP: 10 In
vv VLT: 2 Un.
bb Connection: tunnel terminals for 1.5 to 6 mm2 rigid cables.

Catalogue numbers
Type

Scale

Connection
with CT

Width in mod. Cat. no.
of 9 mm

0-30 A

no

8

16029

X/5

8

16030

iAMP with direct connection
iAMP with connection on CT
Basic device
(delivered without dial)
Dial

0-5 A
0-50 A
0-75 A
0-100 A
0-150 A
0-200 A
0-250 A
0-300 A
0-400 A
0-500 A
0-600 A
0-800 A
0-1000 A
0-1500 A
0-2000 A

16031
16032
16033
16034
16035
16036
16037
16038
16039
16040
16041
16042
16043
16044
16045

50/5
75/5
100/5
150/5
200/5
250/5
300/5
400/5
500/5
600/5
800/5
1000/5
1500/5
2000/5

iVLT
0-300 V
0-500 V

21

2013

8
8

16060
16061

21

Basic panel meters

DIN rail digital ammeters,
voltmeter and frequency meter
Function

059623N-40_c

iAMP
Ammeters measure in amps the current flowing through an electric circuit.
iVLT
Voltmeters measure in volts the potential (voltage) difference of an electric circuit.
iFRE
The frequency meter measures in hertz the frequency of an electric circuit from 20 to
600 V AC.

Common technical data

059624N-40_c

iAMP.

Supply voltage: 230 V.
Operating frequency: 50/60 Hz.
Display by red LED: 3 digits, h = 8 mm.
Accuracy at full-scale: 0.5 % ±1 digit.
Consumption: max. 5 VA or rated 2.5 VA.
Degree of protection:
v	 IP40 on front face
v	 IP20 at terminal level.
Connection: tunnel terminals for 2.5 mm2 cables.

Specific data
iVLT.

10 A direct reading ammeter
Minimum value measured: 4 % of rating.
Measurement input consumption: 1 VA.

059625N-40_c

Multi-rating ammeter
Ratings:
v	 in direct reading: 5 A
v	 by CT (not supplied) configurable on the front face of the ammeter: 10, 15, 20, 25,
40, 50, 60, 100, 150, 200, 250, 400, 500, 600, 800, 1000, 1500, 2000, 2500, 4000,
5000 A.
Minimum value measured: 4 % of rating.
Measurement input consumption: 0.55 VA.

iFRE.

Voltmeter
Direct measurement: 0...600 V.
Input impedance: 2 MW.
Minimum value measured: 4 % of rating.
Frequency meter
Minimum value measured: 20 Hz.
Maximum value measured: 100 Hz.
Full-scale display: 99.9 Hz.
Compliance with standards
Safety: IEC/EN 61010-1.
EMC electromagnetic compatibility: IEC/EN 65081-1 and IEC/EN 65082-2.

Catalogue numbers
Type

Scale

Connection
with CT

Width in mod.
of 9 mm

Cat. no.

0-10 A

No

4

15202

0-5000 A

As per rating

4

15209

0-600 V

4

15201

20-100 Hz

4

15208

Direct reading iAMP
Multi-rating iAMP
iVLT
iFRE

22

2013

Basic panel meters

72 x 72 analogue ammeters and
voltmeter
Function

PB101118-30_c

The 72 x 72 measurement devices are designed for flush-mounted installation on
doors, wicket doors and front plates of enclosures and cubicles.
AMP
The ammeters measure in amps the current flowing through an electrical circuit.
VLT
The voltmeter measure in volts the potential difference (voltage) of an electrical
circuit.

PB101119-30_c

AMP for standard feeder.

AMP for motor feeder.

Common technical data

bb Accuracy: class 1.5.
bb Compliance with standard IEC 60051-1, IEC 61010-1 and IEC 61000-4.
bb Ferromagnetic device.
bb Scale length: 62 mm over 90°.
bb Mounting in enclosure or in cubicle.
bb Degree of protection: IP52.
bb Maximum operating position: 30° / vertical.
bb Temperature:
vv operation: -25°C to +50°C
vv reference: 23°C.
bb Influence of temperature on accuracy: ±0.003 % /°C.
bb Utilisation frequency: 50/60 Hz.

AMP specific technical data

PB101116-30_c

bb Needs a In/5 CT to be ordered separately.
bb Interchangeable dials to be ordered separately.
bb Consumption: 1.1 VA.
bb Permanent overload: 1.2 In.
bb Maximum overload for 5 s: 10 In.

VLT specific technical data
VLT.

bb Consumption: 3 VA.
bb Permanent overload: 1.2 Un.
bb Maximum overload for 5 s: 2 Un.

Catalogue numbers
Type

Scale

AMP for standard feeder
Basic device (delivered without dial)
1.3 In dial

AMP for motor feeder
Basic device (delivered without dial)
3 In dial

Connection
on CT

Cat. no.

0-50 A
0-100 A
0-200 A
0-400 A
0-600 A
0-1000 A
0-1250 A
0-1500 A
0-2000 A

X/5
50/5
100/5
200/5
400/5
600/5
1000/5
1250/5
1500/5
2000/5

16004
16009
16010
16011
16012
16013
16014
16015
16016
16019

0-30-90 A
0-75-225 A
0-200-600 A

X/5
30/5
75/5
200/5

16003
16006
16007
16008

VLT
0-500 V

2013

16005

23

Basic panel meters

96 x 96 analogue ammeters and
voltmeter

Function
PB101118-40_c

The 96 x 96 measurement devices are designed for flush-mounted installation on
doors, wicket doors and front plates of enclosures and cubicles.
AMP
The ammeters measure in amps the current flowing through an electrical circuit.
VLT
The voltmeter measure in volts the potential difference (voltage) of an electrical
circuit.

Common technical data

PB101119-40_c

AMP for standard feeder.

bb Accuracy: class 1.5.
bb Compliance with standard IEC 60051-1, IEC 61010-1 and IEC 61000-4.
bb Ferromagnetic device.
bb Scale length: 80 mm over 90°.
bb Mounting in enclosure or in cubicle.
bb Degree of protection: IP52.
bb Maximum operating position: 30° / vertical.
bb Temperature:
vv operation: -25°C to +50°C
vv reference: 23°C.
bb Influence of temperature on accuracy: ±0.003 % /°C.
bb Utilisation frequency: 50/60 Hz.

AMP specific technical data

PB101116-40_c

AMP for motor feeder.

bb Needs a In/5 CT to be ordered separately.
bb Interchangeable dials to be ordered separately.
bb Consumption: 1.1 VA.
bb Permanent overload: 1.2 In.
bb Maximum overload for 5 s: 10 In.

VLT specific technical data
bb Consumption: 3 VA.
bb Permanent overload: 1.2 Un.
bb Maximum overload for 5 s: 2 Un.

Catalogue numbers
Type
VLT.

Scale

AMP for standard feeder
Basic device (delivered without dial)
1.3 In dial

AMP for motor feeder
Basic device (delivered without dial)
3 In dial

Connection
on CT

Cat. no.

0-50 A
0-100 A
0-200 A
0-400 A
0-600 A
0-1000 A
0-1250 A
0-1500 A
0-2000 A
0-2500 A
0-3000 A
0-4000 A
0-5000 A
0-6000 A

X/5
50/5
100/5
200/5
400/5
600/5
1000/5
1250/5
1500/5
2000/5
2500/5
3000/5
4000/5
5000/5
6000/5

16074
16079
16080
16081
16082
16083
16084
16085
16086
16087
16088
16089
16090
16091
16092

0-30-90 A
0-75-225 A
0-200-600 A

X/5
30/5
75/5
200/5

16073
16076
16077
16078

VLT
0-500 V

24

2013

16075

48 x 48 CMA and CMV
selector switches

Basic panel meters

0

Function
050740-25_c

The 48 x 48 selector switches are designed for flush-mounted installation on doors,
wicket doors and front plates of enclosures and cubicles.
CMA
The ammeter selector switch uses a single ammeter (by means of current
transformers) for successive measurement of the currents of a three-phase circuit.
CMV
The voltmeter selector switch uses a single voltmeter for successive measurement
of the voltages (phase-to-phase and phase-to-neutral) of a three-phase circuit.

CMA.

Common technical data
050741-25_c

bb Durability:
vv electrical: 100 000 operations
vv mechanical: 2 000 000 operations.
bb AgNi contact.
bb Operating temperature: -25°C to +50°C.
bb Compliance with standards IEC/EN 60947-3.
bb Degree of protection:
vv IP65 on front face
vv IP20 at terminal level.

CMV.

Catalogue numbers
Type

Rating
(A)
20

CMA
CMV

Voltage
(V)
500

Number of Cat. no.
positions
4
16017
7
16018

DB117274

Connection

DB114275

CMA.

CMV.

Reading 3 phase-to-earth voltages + 3 phase-to-phase voltages.
Note: when connecting do not remove the pre-cabling.

2013

25

DIN rail iCMA and iCMV selector
switches

Basic panel meters

0

Function
059197_c

iCMA
This 4-position ammeter selector switch uses a single ammeter (using current
transformers) for successive measurement of the currents of a three-phase circuit.
iCMV
This 7-position voltmeter selector switch uses a single voltmeter for successive
measurement of voltages (phase-to-phase and phase-to-neutral) of a three-phase
circuit.

Common technical data

iCMA.

059198_c

bb Rotary handle.
bb Maximum operating voltage: 440 V, 50/60 Hz.
bb Nominal thermal current: 10 A.
bb Operating temperature: -20°C to +55°C.
bb Storage temperature: -25°C to +80°C.
bb Mechanical durability (AC21A-3 x 440 V): 2 000 000 operations.
bb Degree of protection:
vv IP66 on front face
vv IP20 at terminal level.
bb Electrical durability: 1 000 000 operations.
bb Connection: jumper terminals with captive screws, for cables up to 1.5 mm2.
bb Complies with standards: IEC/EN 60947-3.

iCMV.

Catalogue numbers
Type
iCMA
iCMV

DB114272

Connection

DB114273

iCMA.

iCMV.

26

2013

Rating
(A)

Voltage
(V AC)

Width in
mod. of 9 mm

Cat. no.

10
10

415
415

4
4

15126
15125

iCH hour counters

Basic panel meters

Function
DB119002

Electromechanical counter that counts the operating hours of a machine or piece of
electrical equipment. Giving a precise indication of operating time, the counter is
used to decide when to carry out preventive maintenance.

Common technical data

bb Electromechanical display.
bb Maximum display: 99999.99 hours.
bb Display accuracy: 0.01 %.
bb Without reset.
bb Storage temperature: -25°C to +85°C.
bb Connection: tunnel terminals for 2.5 mm2 cable.

Specific technical data

iCH "DIN".

DB119003

iCH "DIN"
bb Consumption: 0.15 VA.
bb Operating temperature: -10°C to +70°C.
bb Mounting on DIN rail.
CH "48 x 48"
bb Consumption:
vv 15607: 0.25 VA
vv 15608: 0.15 VA
vv 15609: 0.02 VA to 12 V and 0.3 VA to 36 V.
bb Operating temperature: -20°C to + 70°C.
bb Degree of protection: IP65 on front face.
bb Mounting on front face of monitoring switchboards.

Catalogue numbers

CH "48 x 48".

Type
iCH "DIN"
CH "48 x 48"

Voltage
Width in mod.
(V)
of 9 mm
230 V AC ± 10 %/50 Hz 4
24 V AC ± 10 %/50 Hz
230 V AC ± 10 %/50 Hz
12 to 36 V DC

Cat. no.
15440
15607
15608
15609

DB114263

DB114262

Connection

load

load

iCH "DIN".

CH "48 x 48".

2013

27

iCI impulse counter

Basic panel meters

Function
DB119004

Electromechanical counter designed to count impulses emitted by: kilowatt hour
meters, temperature overrun detectors, people meters, speed meters, etc.

Common technical data

bb Supply and metering voltage: 230 V AC ± 10 %, 50/60 Hz.
bb Consumption: 0.15 VA.
bb Maximum display: 9 999 999 impulses.
bb Without reset.
bb Metering data:
vv minimum impulse time: 50 ms
vv minimum time between 2 impulses: 50 ms.
bb Storage temperature: -25°C to +85°C.
bb Operating temperature: -10°C to +70°C.
bb Connection: tunnel terminals for 2.5 mm2 cable.

Catalogue number
Type

Width in mod.
of 9 mm
4

iCI

DB114271

Connection

load

load

28

2013

Cat. no.
15443

Dimensions

Basic panel meters

Capot de protection
Ammeters, voltmeters,
selector switches,
impulse counter, hour counters

DB103473

Analogue ammeters and voltmeters

Capot de protection

DB103474 converti

Digital ammeters, voltmeter and frequency meter

DB103475 converti

iCMA and iCMV selector switches

DB103476

72 x 72 analogue ammeters and voltmeter
Protection cover
Terminal
M4

DB103481

96 x 96 analogue ammeters and voltmeter
Protection cover
Terminal
M4

2013

29

Dimensions (cont.)

Basic panel meters

Ammeters, voltmeters, selector switches,
impulse counter, hour counters

DB103477

48 x 48 CMA and CMV selector switches
3.2 (or 4.8)

24.1 (or 33)

(with adapter)

DB103479 converti

iCI impulse counter and iCH hour counter

DB109825 converti

48 x 48 CH hour counters

30

2013

22.3 (or 30.5)

Basic energy meters

Kilowatt-hour meters

PB110836

Function

Digital kilowatt-hour meters designed for sub-metering of active energy (rms)
consumed by a single-phase or three-phase electric circuit with or without distributed
neutral.
iEM2000T
40 A single-phase kilowatt-hour meter without display, with remote transfer of
metering impulses (static output).
iEM2000
40 A single-phase kilowatt-hour meter.
iEM2010
40 A single-phase kilowatt-hour meter with remote transfer of metering impulses
(static output).
PB108401

PB108400

iEM2000T

iME1
Single-phase kilowatt-hour meter.
iME1z
Single-phase kilowatt-hour meter with partial meter.
iME1zr
Single-phase kilowatt-hour meter with partial meter and remote transfer of metering
impulses (relay output).

iEM2000

iEM2010

Catalogue numbers
Type

Rating
(A)

iME1_IMAGE.eps

Single-phase circuit (1L + N)
iEM2000
40
iEM2010
40
iEM2000T
40
iME1
63
iME1z
63
iME1zr
63

iME1zr.

Voltage
(V AC)

Tolerance Width in Cat. no.
(V AC)
mod. of 
9 mm

230
230
230
230
230
230

±20
±20
±20
±20
±20
±20

A9MEM2000
A9MEM2010
A9MEM2000T
A9M17065
A9M17066
A9M17067

2
2
2
4
4
4

Main technical data
Accuracy class
Frequency
Consumption
Operating temp
Connection by
tunnel terminals
Compliance
with standard

Sealable screw
shield
MID Compliance

2013

iEM2000T

iEM2000/iEM2010

iME

IEC 62053-21
(accuracy)
Yes

IEC 62053-21
(accuracy)
Yes

IEC 62053-21 (accuracy)

No

Yes

No

1
48/62 Hz
<10VA
-10°C to +55°C
Top terminals: 4 mm2
Bottom terminals:
10 mm2
IEC 61557-12 :
- PMD/DD/K55/1

1
48/62 Hz
<10VA
-10°C to +55°C
Top terminals: 4 mm2
Bottom terminals:
10 mm2
IEC 61557-12 :
- PMD/DD/K55/1

1
48/62 Hz
2.5 VA
-25°C to +55°C
Top terminals: 6 mm2
Bottom terminals:
16 mm2
IEC 61557-12 :
- PMD/DD/K55/1

Yes

31

Basic energy meters

Kilowatt-hour meters (cont.)

DB115816

Description
iEM2000, iEM2010, iEM2000T
1 	 Remote transfer pulse output (iEM2000T, iEM2010).
2 	 Green power-on indicator light.
3 	 Yellow metering indicator light (flashing).
4 	 Display unit (iEM2000, iEM2010).
5 	 Seal.
6 	 Allow the comb busbar to pass.

iEM2010
DB118760_i

iME1, iME1z, iME1zr
1 	 Pulse output for remote transfer (iME1zr).
2 	 Flashing meter indicator.
3 	 Total or partial meter display (iME1z, iME1zr).
4 	 Wiring error indicator.
5 	 Push-button: total or partial meter display, reset partial meter (ME1z, ME1zr).
6 	 Sealing connection.

Installation

DB118815

iME1zr.

Circuit-breaker

Circuit-breaker

Contactor

Kilowatt-hour meter

Kilowatt-hour meter

Contactor

Load

Load

Example: meter on a load switching

32

bb The front panel of the product is IP40 and its housing is IP20.
bb Its installation must be appropriate to the operating conditions.
bb The protection must not be less than IP65 for outdoor use.

Use with a contactor

A measurement instrument is normally continually supplied.
For a non-continuous supply (load switching), we recommend that you place the
breaking device downstream from the measurement instrument to limit disturbances
on the module inputs.
These disturbances, particularly on inductive loads, may result in early ageing of the
device.
You must also place the measurement instrument at a distance from the breaking
device to limit the risk of disturbance.

2013

Kilowatt-hour meters (cont.)

Basic energy meters

Specific technical data
iEM2000, iEM2010, iEM2000T, iME1, iME1z and iME1zr specific technical data
iEM2000

iEM2010

iEM2000T

iME1

iME1z

iME1zr

Direct measurement
Metering and activity indicator light
(yellow)
Wiring error indicator
Total meter (max. capacity) on one
phase
Total meter display

Up to 40 A
3,200 flashes per kWh

Up to 63 A
1,000 flashes per kWh

Yes
999 999.9 kWh

999.99 MWh

Partial meter (max. capacity) on one
phase with RESET
Partial meter display

-

In kWh or MWh with 5 significant digits. No decimal point in
kWh; 2 digits after the decimal point in MWh
99.99 MWh

-

-

In kWh or MWh with 4 significant digits. No
decimal point in kWh; 2 digits after the decimal
point in MWh

Remote transfer

-

-

-

In kWh with 7 significant digits (not for iEM2000T)

By static output:
- ELV insulation voltage: 4 kV, 50 Hz
- 20 mA/35 V DC max.
- 100 impulses of 120 ms per kWh

By NO impulse contact:
- ELV insulation voltage: 4 kV, 50 Hz
- 18 mA/24 V DC, 100 mA/230 V AC
- 1 impulse of 200 ms (contact
closing) per kWh

Connection

iME1 / iME1z / iME1zr.

iEM2010

Caution
bb Do not earth the CT secondary (S2).

bb You must comply with the routing direction of power cables in the current
transformer primary. Cables enter in "P1" and leave in "P2" to the loads.
DB114264

DB114265

to impulse meter
(iME1zr)

DB118858

DB118858

Single-phase circuit

1

2013

33

Basic energy meters

Acti 9 iEM3000 Series Energy Meters
Functions and characteristics

PB108410

b The Acti 9 iEM3000 Energy Meter Series offers a cost-attractive, competitive range of
DIN rail-mounted energy meters ideal for sub-billing and cost allocation applications.
Combined with communication systems, like Smart Link, the Acti 9 iEM3000 Series
makes it easy to integrate electrical distribution measurements into customer’s facility
management systems. It’s the right energy meter at the right price for the right job.
Two versions are available: 63A direct measure (iEM3100 models) and current
transformers associated meter (iEM3200 models). For each range, eight versions
are available to satisfy basic to advanced applications:

PB108432

Acti 9 iEM3100 energy meter

Acti 9 iEM3255 energy meter

b iEM3100/iEM3200: kWh meter with partial counter
b iEM3110/iEM3210: kWh meter with partial counter and pulse output. MID certified.
b iEM3115/iEM3215: multi-tariff meter controlled by digital input or internal clock, MID
certified.
b iEM3135/iEM3235: energy meter, four quadrant, multi-tariffs with partial counter
and current, voltage, power measurement. M-Bus communication, digital I/O and MID
certified.
b iEM3150/iEM3250: kWh meter with partial counter and current, voltage, power
measurement. Modbus communication.
b iEM3155/iEM3255: energy meter, four quadrant, multi-tariffs with partial counter
and current, voltage, power measurement. Modbus communication, digital I/O, MID
certified.
b iEM3165/iEM3265: energy meter, four quadrant, multi-tariffs with partial counter
and current, voltage, power measurement. BACnet communication, digital I/O and
MID certified.
b iEM3175/iEM3275: energy meter, four quadrant, multi-tariffs with partial counter
and current, voltage, power measurement. LON communication, digital input and
MID certified.
Innovative design makes the meters smart and simple:
b Easy to install for panel builders
b	 Easy to commission for contractors and installers
b	 Easy to operate for end users

Applications
Cost management applications

b�Bill verification
b�Sub-billing, including WAGES view (four user-defined tariffs)
b�Cost allocation, including WAGES view

Network management applications

b�Basic electrical parameters like current, voltage and power
b Onboard overload alarm to avoid circuit overload and trip
b Easy integration with PLC systems by input/output interface

Market segments

b�Buildings & Industry
b�Data centres and networks
b�Infrastructure (airports, road tunnels, telecom)
Front of meter parts
1 Configuration mode
2 Values and parameters
3 Unit
4 Cancellation
5 Confirmation
6 Selection
7 Date and time
8 Tariff currently used (iEM3235,
iEM3255, iEM3265, iEM3275)
9 Functions/Measurements

34

Characteristics

b�Self-powered meters
b�Chain measurement (meters + CTs) accuracy class 1
b�Compliance with IEC 61557-12, IEC 62053-21/22, IEC 62053-23, EN50470-3
b Compact, 5 module width
b Graphical display for easy viewing
b�Onboard Modbus, LON, M-Bus or BACnet communication
b�Easy wiring (without CTs) Acti 9 iEM3100 models
b�Double fixation on DIN rail (horizontal or vertical)
b�Anti-tamper security features ensure the integrity of your data
b�MID compliant (selected models) providing certified accuracy and data security

2013

Basic energy meters

Acti 9 iEM3000 Series Energy Meters
Functions and characteristics

b

b

b
b
b

b

4
4
b

4
2
b

b
b

b
b
b

b
b
b

b
b
b

b

4
2
b

4
2
b

4
2
b

1

1

1

1

b

b

b

b

b

b

b
b
b
b
b

b

4
4
b

4
2
b

b

2

b
b
b
b

b
b
b
b
b

b
b
b
b
b

b
b
b
b
b

b

4
2
b

4
2
b

4
2
b

1

1

1

1

1

1

1

b
b

b

b

2
1

1

iEM3275

b

iEM3265

iEM3175

b

iEM3255

iEM3165

b

iEM3250

iEM3155

b

iEM3235

iEM3150

b

iEM3215

iEM3135

b

iEM3210

iEM3115

b

b
Direct measurement (up to 63 A)
Measurement inputs through CTs (1 A, 5A)
Measurement inputs through VTs
b
Active energy measurements class (total & partial kWh)
Four Quadrant Energy measurements
Electrical measurements (I, V, P, etc.)
Multi-tariff (internal clock)
Multi-tariff (external control)
b
Measurement display (number of lines)
Digital inputs
Programmable (Tariff control or WAGES input)
Tariff control only
Digital ouputs Programmable (kWh pulse or kW alarm)
kWh pulse only
kW overload alarm
M-Bus
Modbus
BACnet
LON
MID (legal metrology certification)
Width (18 mm module in DIN Rail mounting)
5

iEM3200

iEM3110

iEM3100

Function guide

1

b
b

b
b

1
b

1

b

b

b

b

b
b

b

b

5

5

5

5

b

b

b

b

b
b

5

5

5

5

b

b

b

5

5

5

5

b

b

b
b

5

5

5

PB108410

Connectivity advantages
Programmable digital input

External tariff control signal (4 tariffs)
Remote Reset partial counter
External status, e.g. breaker status
Collect WAGES pulses

Programmable digital output

kWh overload alarm (iEM3135, iEM3155, iEM3165
iEM3235, iEM3255, iEM3265)
kWh pulses

Graphic LCD display

Scroll energies
Current, voltage, power, frequency, power factor

Communication

Serial communication options are available with M-Bus,
Modbus, BACnet or LON protocols

Standards

PB108424

Acti 9 iEM3100 models direct connected (63 A)

IEC standards

IEC 61557-12, IEC 61036, IEC 61010, IEC 62053-21/22
Class 1 and Class 0.5S, IEC 62053-23

MID

EN 50470-1/3

Multi-tariff capability
The Acti 9 iEM3000 Series allows arrangement of kWh consumption in four different
registers. This can be controlled by:
b Digital Inputs. Signal can be provided by PLC or utilities
b Internal clock programmable by HMI
b Through communication
This function allows users to:
b Make tenant metering for dual source applications to differentiate backup source or
utility source
b Understand well the consumption during working time and non working time, and
between working days and weekends
b Follow up feeders consumption in line with utility tariff rates

Acti 9 iEM3200 models (1 A / 5 A CT connected)

2013

35

Acti 9 iEM3000 Series Energy Meters

Basic energy meters

Functions and characteristics

Specification guide

iEM3100 Models
iEM3100

iEM3110

iEM3115

iEM3135

Current (max.) Direct connected
Meter constant LED
Up to
1000p/kWh

Multi-tariff
Communication

Up to
1000p/kWh
4 tariffs
M-bus

4 tariffs

DI/DO
MID (EN50470-3)

0/1
b

Network
Accuracy class

2/0
b

Modbus

1/1
b

1/1
b

LON
1/0
b

16 mm²
LCD 99999999.9kWh
3 x 100/173 Vac to 3 x 277/480 Vac (50/60 Hz)
IP40 front panel and IP20 casing
-25°C to 55°C (K55)
10 steps of 9mm

Overvoltage and
measurement

Category III, Degree of pollution 2
b

b

b

b

b

b
b
b
b
b
b

kVARh
Active power
Reactive power
Currents and voltages
Overload alarm
Hour counter

iEM3200

iEM3210

b
b

iEM3200 Models

iEM3215

iEM3235

1 A / 5 A CTs (max current)

iEM3250

b

b

b

b
b
b
b
b
b

b
b
b
b
b
b

b
b
b
b
b
b

iEM3265

iEM3275

iEM3255

6A

Meter constant LED

5000/kWh

Pulse output frequency

Up to
500p/kWh

Multi-tariff
Communication
DI/DO
MID (EN50470-3)

0/1
b

Network

Up to
500p/kWh
4 tariffs

4 tariffs

2/0
b

M-bus
1/1
b

Up to 500p/kWh
4 tariffs
Modbus

Modbus
1/1
b

BACnet
1/1
b

LON
1/0
b

b

b

b

b
b
b
b
b
b

b
b
b
b
b
b

b
b
b
b
b
b

1P+N, 3P, 3P+N
1P+N, 3P, 3P+N
support CTs
support CTs & VTs
Class 0.5S (IEC 62053-22 and IEC61557-12) Class C (EN50470-3)(1)

Accuracy class
Wiring capacity

6 mm² for currents and 4 mm² for voltages

Display max.
Voltage (L-L)
IP protection
Temperature
Product size

LCD 99999999.9kWh or 99999999.9MWh
3 x 100/173 Vac to 3 x 277/480 Vac (50/60 Hz)
IP40 front panel and IP20 casing
-25°C to 55°C (K55)
10 steps of 9mm

Overvoltage & measurement

Category III, Degree of pollution 2
b

b

kVARh
Active power
Reactive power
Currents and voltages
Overload alarm
Hour counter
(1) For 1 A CTs Class 1 (IEC6253-21 and IEC61557-12 Class B (EN50470-3)

b
b
b
b
b
b

36

iEM3175

1P+N, 3P, 3P+N
Class 1 (IEC 62053-21 and IEC61557-12) Class B (EN50470-3)

Display max.
Voltage (L-L)
IP protection
Temperature
Product size

kWh

iEM3165

Up to
1000p/kWh
4 tariffs
Modbus
BACnet

1/1
b

Wiring capacity

Specification guide

iEM3155

500/kWh

Pulse output

kWh

iEM3150
63 A

b

b

2013

b
b
b

Basic energy meters

Acti 9 iEM3000 Series Energy Meters
Functions and characteristics

PB105306

PB105305

Acti 9 iEM3000 Series front flaps open and closed

PB1053241

Acti 9 iEM3000 Series parts
1. Digital inputs for tariff control (iEM3115 / iEM3215)
2. Display for measurement and configuration
3. Pulse out for remote transfer (iEM3110 / iEM3210)
4.
Cancellation
5.
Confirmation
6.
Selection
7. Flashing yellow meter indicator to check accuracy
8. Green indicator: on/off, error

PB105303

PB105302

PB105313

iEM3000 series dimensions

Meter model and description

iEM3x50 and iEM3x55 Comm./terminal parts
1. Digital input for tariff control (iEM3155 / iEM3255)
2. Digital output (iEM3155/iEM3255)
3. Communication port
4. Yellow indicator for communication diagnosis
5. Display for measurement and configuration
6.
Cancellation
7.
Confirmtion
8.
Selection
9 Flashing yellow meter indicator to check accuracy
10 Green indicator: on/off, error

Note: For further information please see the Installation Guide
and User Guide documents for these products.

Current measurement

Part no.

iEM3100 basic energy meter

Direct connected 63 A

A9MEM3100

iEM3110 energy meter with pulse output
iEM3115 multi-tariff energy meter

Direct connected 63 A
Direct connected 63 A

A9MEM3110
A9MEM3115

iEM3135 advanced multi-tariff energy meter &
Direct connected 63 A
electrical parameter plus M-Bus comm port
iEM3150 energy meter & electrical parameter
Direct connected 63 A
plus Modbus RS485 comm port
iEM3155 advanced multi-tariff energy meter &
Direct connected 63 A
electrical parameter plus Modbus RS485 comm
port

A9MEM3135

iEM3165 advanced multi-tariff energy meter &
electrical parameter plus BACnet MS/TP comm
port
iEM3175 advanced multi-tariff energy meter &
electrical parameter plus LON TP/FT-10 comm
port
iEM3200 basic energy meter

Direct connected 63 A

A9MEM3165

Direct connected 63 A

A9MEM3175

iEM3210 energy meter with pulse output
iEM3215 multi-tariff energy meter
iEM3235 advanced multi-tariff energy meter &
electrical parameter plus M-Bus comm port
iEM3250 energy meter & electrical parameter
plus Modbus RS485 comm port
iEM3255 advanced multi-tariff energy meter &
electrical parameter plus Modbus RS485 comm
port
iEM3265 advanced multi-tariff energy meter &
electrical parameter plus BACnet MS/TP comm
port
iEM3275 advanced multi-tariff energy meter &
electrical parameter plus LON TP/FT-10 comm
port

Transformer connected 5 A A9MEM3210
Transformer connected 5 A A9MEM3215
Transformer connected 5 A A9MEM3235

2013

A9MEM3150
A9MEM3155

Transformer connected 5 A A9MEM3200

Transformer connected 5 A A9MEM3250
Transformer connected 5 A A9MEM3255
Transformer connected 5 A A9MEM3265
Transformer connected 5 A A9MEM3275

37

Product selection according
to measurement functions

Power-monitoring units
specification guide

Multi-circuit Metering

Basic multi-function Metering

BCPM

EM4800

ION6200

PM3200/PM3210/
PM3250/PM3255

General selection criteria
Installation

PM5100/PM5300/ PM810/PM820/
PM5500
PM850/PM870

Inside panel

On DIN rail

Flush mount

Flush mount

Flush mount

Flush or DIN rail
mount

Use on LV distribution systems
Use on LV and HV distribution systems
Current / voltage accuracy

b

b

b

b

1%

0.5 %

0.5 %

1%

b
b

b
b

Power / active energy accuracy

1%

1%

Class 1 IEC 62053-21
Class 1 IEC 61557-12

Class 1
IEC 62053-21
Class 2
IEC 62053-23
Class 0.5 S
IEC 62053-22

For PM55xx:
Class 0.2 S
IEC 62053-22
For PM51/53xx:
Class 0.5 S
IEC 62053-22

Class 0.5S IEC
62053-22
Class 0.2S ANSI
12.20

b
b
-

b
b
-

b
b

b
b

b
b

b
b

-

-

-

-

b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
-

b
b
b
b
b
b
b
b
b
b
b

b
b

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
b
b

b
-

b
b
-

b
b
b
-

b
-

b
b
b
-

In/Out
In/Out
b
b

b
b

b (3)

b
b

b
b

b
b

b
b

-

b (3)

b

b

b

b

-

b (3)

b

b

b

b

-

-

-

1 parameter

b

b
b
b

-

b

b

iEM31552and
iEM3255

b

b

Instantaneous rms values
Current 	
b Phases
	
b Neutral
	
b Extended
Measurement
range
3 - Phase Voltage
Voltage per phase
Frequency
Total power
b Active
b Reactive
b Apparent
Power per phase
b Active
b Reactive
b Apparent
Power factor
b Total
b Per phase
Energy values
Active energy
Reactive energy
Apparent energy
User-set accumulation mode
Demand values
Current - Present and maximum values
Total active power - Present and
maximum values
Total reactive power - Present and
maximum values
Total apparent power - Present and
maximum values
Total predicted demand - kW, kVAR, kVA
Synchronisation of calculation window
User-set calculation mode
Other measurements
Hour counter

b
b
b
b
b
b
b
b
b
b
b

(1) Measurement sensors included.
(2) Available with Micrologic E associated to Compact NS630b...3200, Masterpact NT, Masterpact NW.
(3) Active power or reactive power or apparent power.

38

2013

Intermediate Metering

0.5 % current
0.2 % voltage

Product selection according
to measurement functions
(cont.)

Power-monitoring units
specification guide

Advanced Metering

Advanced Utility Metering

ION7330/7350

ION 7550

ION8650
A

Flush mount

DIN 192 standard
cutout–186x186 mm

Backplate mount

ANSI socket, mount 9S, 35S, 36S;
FT21switchboard case

DIN 43862 rack

b
b
0.5 % reading

b
b
0.1 % reading

b
b
0.07 %

b
b
0.1 % reading

b
b
0.1 % reading

0.5 %

0.20 %

0.20 %

0.20 %

0.20 %

b
b
-

b
b
b

b
b
b

b
b
-

b
b
-

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b

b
b

b
b

b
b

b
b

b

b

b

b

b

b

b

b

b

b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

-

-

-

-

-

ION 7650 CM4000T

2013

B

C

ION8800
A

B

C

39

Product selection according
to measurement functions
(cont.)

Power-monitoring units
specification guide

Power quality measurement
Interharmonics
Total harmonic
Voltage
distortion
Current
Individual harmonic content
(current & voltage)
Waveform capture

Multi-circuit Metering

Basic multi-function Metering

Intermediate Metering

BCPM

EM4800

ION6200

PM3200/PM3210/
PM3250/PM3255

PM5100/PM5300/ PM810/PM820/
PM5500
PM850/PM870

-

-

b
b

b
b

b

b
b

-

-

-

-

b

31 (1)

-

-

0.5 %

1%

Detection of voltage sags and swells

-

-

Class 1 IEC 62053-21
Class 1 IEC 61557-12

-

b

-

Programmable (logic and mathematical
functions)
Detection & capture of transients
Flicker
EN 50160 compliance checking
IEC 61000-4-30 compliance
True rms measurement
Maximum harmonic number
Sampling rate
Points per cycle
Data recording
Min/Max of instantaneous values
Data logging
Event logging
Trend curves
Alarms
Alarm notification via email

-

-

b

-

b

-

-

15

-

b

b

b
b
b

b
b
b

63

-

-

b

32

b

128

b
-

-

b
b
b

b
b

-

b
-

b
b
b
-

-

-

-

-

256 kB / 1.1 MB

b
2 (1)
b
b
Optional with
PM8ECC Card
b (1)
b (1)
80 kB (1)

-

b
-

b
b

b
b

b
b

b
-

-

2

b

b

2/4

-

1 (PM9P)
-

2
2

b
-

1
2

277 V L-N
480 V L-L

277 V L-N
480 V L-L

400 V L-N
690 V L-L

-

277 V L-N
400 V L-L

13 digit. / 4
analogue
1
5 digit. / 4
analogue
347 V L-N
600 V L-L

90 - 277 V

100 - 240 V

-

110 - 300 V

20 V L-N / 35 V L-L 115 to 415 ±10 %
to 277 V L-N /480 V V AC, 15 VA
L-L
45-67 Hz or
350-450 Hz
100 - 300 V
125-250V DC
±20%

115 to 415 ±10 %
V AC, 15 VA
45-67 Hz or
350-450 Hz
125 to 250 ±20 %
V DC, 10W

-

-

-

-

Sequence of Events Recording
Date and time stamping
GPS time synchronisation
Storage capacity
Display, sensors, inputs/outputs
Front-panel display
Built-in current and voltage sensors
Digital or analogue inputs
(max. number)
Pulse outputs
Digital or analogue outputs (max. number
including pulse outputs)
Direct voltage connections
without external VT
Power supply
AC/DC version
AC

DC

-

DC version
Communication

-

-

RS 485 port

b

-

Option

b

b

2- wire (on board)

Infra-red port

-

-

-

-

-

-

RS 232 port

-

-

-

-

-

With remote
display
M

Modbus (M)
M
M
M
M
M
(1) With PM810LOG
(4) Maximum only.
(2) Configurable.
(5) Self-powered.
(3) Except for interharmonics, signalling voltage, flicker and transients.meter's (6) The ION8600 and ION8800 do trending with software but not from the meter's front panel.
front panel.

40

2013

Product selection according
to measurement functions
(cont.)

Power-monitoring units
specification guide

Advanced Metering

Advanced Utility Metering

ION7330/7350

ION 7550

ION 7650

CM4000T

ION8650
A

b

b

b

b
b
b

b
b
b

b
b
b

0.5 % reading

-

b

0.07 %

b

0.5 %

b

0.20 %

b

b

b

b

b

b

b

b
b
b
b

63

20 µs
b
b
b

b
b
b
b
b

78 µs
b
b
63

b

256

1024

b

256

1024

b
b
b
b
b
b

b
b
b
b
b
b

b
b
b
-

b
b
b
- (6)
b
b

b
b
b
b
b

b
b
b
300 kB

b
b
b

-

b
b
b

b (7
b
b

10 MB

b
b

b

b
b

b

b

-

-

-

4

20

b

11

3

4
4

1
12

b
b

2
14

1
13

347 V L-N
600 V L-L

347 V L-N
600 V L-L

b

277 V L-N (9S, 36S)
480 V L-L (35S)

288 V L-N
500 V L-L

95 - 240 VAC (+ 10%),
(47 - 440 Hz)

85 to 240 V

-

120 to 227 V, 120 to 480 V (35S) /
57 to 70 V / 65 to 120 V / 160 to 277 V

85 to 240 V (+/- 10 %)
47-63 Hz

120 - 310 VDC (+ 10%)
110 to 300 V
0.2 A worst case loading
(12 W) at 100 VAC at 25°C

-

80 to 160 V / 200 to 350 V

110 to 270 V (+/- 10 %)

-

-

-

-

Up to 10 MB

-

B

C

ION8800
A

C

b
b
b
b
-

b

-

4 MB

20 µs
b
b
b
63

2 MB

-

Up to 10 MB

1/2

b

-

b

Option

b

b

-

b

b

-

b

-

b

Option

M

M

-

M

M

2013

B

41

Multi-circuit metering

PowerLogic BCPM

Functions and characteristics

PE86166

The ideal solution for data centre managers, engineers and operational executives
who are responsible for delivering power to critical applications. In corporate and
hosted data centre facilities, this technology helps you plan and optimise the critical
power infrastructure to meet the demands of continuous availability.
The PowerLogic BCPM is a highly accurate, full-featured metering product designed
for the unique, multi-circuit and minimal space requirements of a high performance
power distribution unit (PDU) or remote power panel (RPP).
The BCPM monitors up to 84 branch circuits with a single device and also monitors
the incoming power mains to provide information on a complete PDU. Full alarming
capabilities ensure that potential issues are dealt with before they become problems.
Unlike products designed for specific hardware, the flexible BCPM will fit any PDU or
RPP design and supports both new and retrofit installations. It has exceptional
dynamic range and accuracy, and optional feature sets to meet the energy
challenges of mission critical data centres.

PE86281

PowerLogicTM BCPM board

Applications

Data Centre load monitoring and alarming
Comprehensive monitoring of lighting control panels
Maximise uptime and avoid outages.
Optimise existing infrastructure.
Effectively plan future infrastructure needs.
Improve power distribution efficiency.
Track usage and allocate energy costs.
Enable accurate sub-billing.

Main characteristics
Monitor up to 84 branch circuits with a single BCPM.
Ideal for installation in both new PDUs and retrofit projects
New installations: BCPM with solid core CTs monitors up to 84 branch circuits
using 2 or 4 CT strips. Solid core CTs are rated to 100 A CTs and are mounted on
strips to simplify installation. CT strips are available with 12, 15 or 21 CTs per strip on
18 mm spacings. 21 CT strips with 3/4” or 1” spacings are also available.

PowerLogicTM BCPM split core 12, 18, and 21 CTs strips

Retrofit projects: BCPMSC with split core CTs is ideal for retrofits. Any number of
split core CTs, up to 84 maximum, can be installed with a single BCPM. Three sizes
of CT are supported (50 A, 100 A, and 200 A) and all three CT sizes can be used on a
single BCPM. Adapter boards with terminals for split-core CTs can be mounted using
DIN-rail, Snaptrack or on a common mounting plate with the main board (42 ch Y63
models only).
IEC Class 1 metering accuracy
Accurately monitor very low current levels, down to a quarter-Amp.
Easily differentiate between the flow of low current and a trip where no current flows.
Designed to fit any PDU or RPP design
Lowers your total installation costs as well as the cost per meter point by supporting
both new and retrofit installations.
Modbus RTU protocol
Integrates easily into existing networks using Modbus communications. Optional
Ethernet interfaces:
Optional Ethernet interfaces
Add Modbus TCP support with a Modbus gateway (EGX) or BACnet IP (and MS/TP)
with the E8950*.
Compatible with PowerLogic power monitoring software
Easily turn the large amount of data collected by the devices into useful decisionmaking information.
Flexible Configuration capability
Set the ordering and orientation of CT strips, assign individual CT size and phases,
support for 1, 2, and 3-pole breakers.

PowerLogicTM BCPM split core CT

42

2013

Multi-circuit metering

PowerLogic BCPM

Functions and characteristics (cont.)

Selection guide
General

Use on LV systems

Power and energy measurements

Mains
Branch circuits

BCPMA

BCPMB

BCPMC

b

b

b

b
b

b
-

-

Instantaneous rms values

b
Current, voltage, frequency
Active power
Total and per phase b
Power factor
Total and per phase b

Energy values
Active energy

Demand values
Total active power

PE86168

PowerLogic BCPM
1	 50-pin ribbon cable connectors (data acquisition board).
2	 Auxiliary inputs.
3	 Control (mains) power connection.
4	 Control power fuse.
5	 Alive LED.
6	 Voltage taps.
7	 Communications address DIP switches.
8	 Communications settings DIP switch.
9	 RS-485 2 connection.
10	 RS-485 LEDs.

BCPM

A

0 84 S

Example BCPM with solid core CTs part number.
1	
2	
3	
4	
5	

Model.
Feature set.
CT spacing (solid-core models only)
Number of circuits.
Brand.

Present and max.
values

Power quality measurements

b

b (mains only) -

b

b (mains only) -

b

b

2560 Hz

2560 Hz

2560 Hz

b

b

b

AC version

90-277 V ac

90-277 V ac

90-277 V ac

RS 485 port
Modbus protocol
Modbus RTU (Ethernet) optional, add EGX
BACnet IP (Ethernet) optional, add E8950
BACnet MS/TP (RS 485) optional, add E8950

1
b
b
b
b

1
b
b
b
b

1
b
b
b
b

Detection of over-voltage/under-voltage
Sampling rate Points per cycle

Alarming
Alarms

Power supply
Communication

BCPM part numbers
Item

Code

1 Model

BCPM

2 Feature set

A

3 CT spacing

5 Brand

C
0
1
2
84
72
42
S

26 mm CT spacing
18 mm CT spacing
84 circuits, (4) 21CT strips
72 circuits, (4) 18CT strips (18 mm spacing only)
42 circuits, (2) 21CT strips
Schneider Electric

BCPM with split core CTs
Model

2 Feature set

4 Number of circuits

BCPMSC

BCPM with split core CTs. Highly accurate
meter that monitors branch circuits and the
incoming power mains and includes full
alarming capabilities

A

Advanced - Monitors power and energy per
circuit and mains

B

Intermediate - Monitors current per circuit,
power and energy per mains

C

Basic - Monitors current only per circuit and mains

1
2
Y63

42 circuits (no CTs, order separately)
84 circuits (no CTs, order separately)
42 circuits with main and adapter boards on
single mounting plate
30 split core CTs (50 A)
42 split core CTs (50 A)
60 split core CTs (50 A)
84 split core CTs (50 A)
Schneider Electric

30
42
60
84
S

5 Brand

2013

Description
BCPM with solid core CTs. Highly accurate
meter that monitors branch circuits and the
incoming power mains and includes full
alarming capabilities
Advanced - Monitors power & energy per
circuit & mains
Intermediate - Monitors current per circuit,
power and energy per mains
Basic - Monitors current only per circuit & mains
19 mm CT spacing

B

4 Number of circuits

The PowerLogic BCPM uses .333 VAC output split-core
CTs for the auxiliary inputs. These CTs are ordered
separately from the BCPM.

b
b (mains only) b (mains only) -

43

Multi-circuit metering

PowerLogic BCPM

Functions and characteristics (cont.)

PowerLogic BCPM specifications
Electrical characteristics
Type of measurement
Accuracy
Power/energy
Voltage
Solid Core CT:
50A Split-Core CT:
100A Split-Core CT:
200A Split-Core CT:
Data update rate
Input-voltage
Measured voltage
characteristics

Power supply

IEC 62053-21 Class 1, ANSI C12.1-2008
±0.5% of reading 90-277V line-to-neutral
±0.5%
±1%
±0.5%
±1%
1.8 seconds
150 – 480 V ac L-L (1)
– 277 V ac L-N (1)

Measurement range

150 – 480 V ac L-L (1)
– 277 V ac L-N (1)

AC

90 – 277 V ac (50/60 Hz)

90
90

Mechanical characteristics
Weight
Dimensions

Circuit board

1.5 kg
288 x 146 mm

Environmental conditions
Operating temperature
Storage temperature
Installation category

0 to 60ºC
-40ºC to 70ºC
CAT III

Safety
Europe
U.S. and Canada

Communication

IEC 61010
UL 508 Open type device

RS 485

Baud rate: DIP-switch selectable 9600, 19200,
38400
DIP-switch selectable 2-wire or 4-wire RS-485

Protocol

Modbus RTU. Modbus TCP can be added with
optional gateway (EGX). BACnet MS/TP and
BACnet IP available with optional gateway
(E8950) (2)

Firmware characteristics

Detection of over-voltage/under-voltage
Alarms

Firmware update

User-defined alarm thresholds for over-voltage
and under-voltage detection
Four alarm levels: high-high, high, low and
low-low (users define the setpoints for each).
Each alarm has a latching status to alert the
operator that an alarm has previously occurred.
High and Low alarms have instantaneous status
to let the operator know if the alarm state is still
occurring.
Update via the RS-485 port

(1) Feature sets ‘A’ and ‘B’ only.
(2) E8950 supports the BCPMAxx42,BCPMBxxx, BCPMCxxxx, BCPMSCBxx, and
BCPMSCCxx - (BCPMAx84 and BCPMSCAxx models are not supported).

1/3 V low-voltage CT (LVCT) specifications
Electrical characteristics
Accuracy

1% from 10% to 100% of rated current

Frequency range

50/60 Hz

Leads

18 AWG, 600 V ac, UL 1015 twisted pair, 1.8m
standard length

Max. voltage L-N sensed conductor

600 V ac

Environmental conditions
Operating temperature
Storage temperature
Humidity range

44

2013

-15ºC to 60ºC
-40ºC to 70ºC
0 to 95% non-condensing

Multi-circuit metering

PowerLogic BCPM

Functions and characteristics (cont.)

BCPM part numbers for solid and split core CTs (contd.)

PE86284

Part number

cbl022.jpg

Flat ribbon cable

BCPMA084S
BCPMA184S
BCPMA042S
BCPMA142S
BCPMA224S
BCPMA236S
BCPMA242S
BCPMA248S
BCPMA272S
BCPMA284S
BCPMB084S
BCPMB184S
BCPMB042S
BCPMB142S
BCPMB224S
BCPMB236S
BCPMB242S
BCPMB248S
BCPMB272S
BCPMB284S
BCPMC084S
BCPMC184S
BCPMC042S
BCPMC142S
BCPMC224S
BCPMC236S
BCPMC242S
BCPMC248S
BCPMC272S
BCPMC284S

Description

BCPM Advanced feature set, 84 solid core 100 A CTs, 19 mm CT spacing
BCPM Advanced feature set, 84 solid core 100 A CTs, 26 mm CT spacing
BCPM Advanced feature set, 42 solid core 100 A CTs, 19 mm CT spacing
BCPM Advanced feature set, 42 solid core 100 A CTs, 26 mm CT spacing
BCPM Advanced feature set, 24 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Advanced feature set, 36 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Advanced feature set, 42 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Advanced feature set, 48 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Advanced feature set, 72 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Advanced feature set, 84 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Intermediate feature set, 84 solid core 100 A CTs, 19 mm CT spacing
BCPM Intermediate feature set, 84 solid core 100 A CTs, 26 mm CT spacing
BCPM Intermediate feature set, 42 solid core 100 A CTs, 19 mm CT spacing
BCPM Intermediate feature set, 42 solid core 100 A CTs, 26 mm CT spacing
BCPM Intermediate feature set, 24 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Intermediate feature set, 36 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Intermediate feature set, 42 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Intermediate feature set, 48 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Intermediate feature set, 72 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Intermediate feature set, 84 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Basic feature set, 84 solid core 100 A CTs, 19 mm CT spacing
BCPM Basic feature set, 84 solid core 100 A CTs, 26 mm CT spacing
BCPM Basic feature set, 42 solid core 100 A CTs, 19 mm CT spacing
BCPM Basic feature set, 42 solid core 100 A CTs, 26 mm CT spacing
BCPM Basic feature set, 24 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Basic feature set, 36 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Basic feature set, 42 solid core 100 A CTs (2 strips), 18 mm CT spacing
BCPM Basic feature set, 48 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Basic feature set, 72 solid core 100 A CTs (4 strips), 18 mm CT spacing
BCPM Basic feature set, 84 solid core 100 A CTs (4 strips), 18 mm CT spacing

BCPM with split core
Round ribbon cable

Cabling and connection
Round ribbon cable is recommended for use
when
the BCPM printed circuit board will be mounted
outside of the PDU that is being monitored.
Round ribbon cable is the prefered choice when
the ribbon cable will be threaded through
conduit.
Flat ribbon cable is recommended for projects
where the BCPM printed circuit board will be
installed inside of the PDU that is being
monitored.

BCPMSCA1S

BCPM feature set A, 42 circuit split core CT power and energy meter, CTs sold
separately

BCPMSCA2S

BCPM feature set A, 84 circuit split core CT power and energy meter, CTs sold
separately

BCPMSCA30S
BCPMSCA42S
BCPMSCA60S
BCPMSCAY63S

BCPM feature set A, 30 circuit split core CT power and energy meter, CTs rated to 50 A
BCPM feature set A, 42 circuit split core CT power and energy meter, CTs rated to 50 A
BCPM feature set A, 60 circuit split core CT power and energy meter, CTs rated to 50 A
BCPM feature set A, 42 circuit split core power and energy meter - all boards on
backplate, 50A CTs

BCPMSCA84S
BCPMSCB1S
BCPMSCB2S
BCPMSCB30S
BCPMSCB42S
BCPMSCB60S
BCPMSCBY63S
BCPMSCB84S

BCPM feature set A, 84 circuit split core CT power and energy meter, CTs rated to 50 A
BCPM feature set B, 42 circuit split core CT branch current, mains power meter, no CTs
BCPM feature set B, 84 circuit split core CT branch current, mains power meter, no CTs
BCPM feature set B, 30 circuit split core CT branch current, mains power meter, 50 A CTs
BCPM feature set B, 42 circuit split core CT branch current, mains power meter, 50 A CTs
BCPM feature set B, 60 circuit split core CT branch current, mains power meter, 50 A CTs
BCPM feature set B, 42 circuit split core CT branch current, mains - all boards on backplate,
50 A CTs
BCPM feature set B, 84 circuit split core CT branch current, mains power meter, 50 A CTs

BCPMSCC1S

BCPM feature set C, 42 circuit split core CT current meter, CTs sold separately

BCPMSCC2S

BCPM feature set C, 84 circuit split core CT current meter, CTs sold separately

BCPMSCC30S

BCPM feature set C, 30 circuit split core CT current meter, CTs rated to 50 A

BCPMSCC42S

BCPM feature set C, 42 circuit split core CT current meter, CTs rated to 50 A

BCPMSCC60S

BCPM feature set C, 60 circuit split core CT current meter, CTs rated to 50 A

BCPMSCCY63S BCPM feature set C, 42 circuit split core CT current meter , all boards on backplate,
50A CTs 50 A

Flat ribbon cable is more flexible than round
ribbon cable and is the preferred choice if the
ribbon cable will not be threaded through conduit. BCPMSCC84S

BCPM feature set C, 84 circuit split core CT current meter, CTs rated to 50 A

2013

45

Multi-circuit metering

PowerLogic BCPM

Functions and characteristics (cont.)

BCPM split core accessories

PE86183

BCPMSCADPBS

BCPMSCCT0
BCPMSCCT0R20
BCPMSCCT1
BCPMSCCT1R20
BCPMSCCT3
BCPMSCCT3R20

BCPM adapter boards, quantity 2, for split core BCPM
BCPM 50 A split core CTs, Quantity 6, 1.8 m lead lengths
BCPM 50 A split core CTs, quantity 6, 6 m lead lengths
BCPM 100 A split core CTs, Quantity 6, 1.8 m lead lengths
BCPM 100 A split core CTs, Quantity 6, 6 m lead lengths
BCPM 200 A split core CTs, Quantity 1, 1.8 m lead lengths
BCPM 200 A split core CTs, Quantity 1, 6 m lead lengths

Additional accessories for use with BCPM products

E682small

PowerLogicTM BCPM split core CTs

BCPMCOVERS
BCPMREPAIR
H6803R-0100
E8950
CBL008
CBL016
CBL017
CBL018
CBL019
CBL020
CBL021
CBL022
CBL023
CBL024
CBL033

BCPM circuit board cover
CT repair kit for solid core BCPM (includes one CT)
Additional 108 split core CT for use with solid core repair kit
Modbus to BACnet protocol converter
Flat Ribbon cable (quantity 1) for BCPM, length = 0.45 m
Flat Ribbon cable (quantity 1) for BCPM, length = 1.2 m
Flat Ribbon cable (quantity 1) for BCPM, length = 1.5 m
Flat Ribbon cable (quantity 1) for BCPM, length = 1.8 m
Flat Ribbon cable (quantity 1) for BCPM, length = 2.4 m
Flat Ribbon cable (quantity 1) for BCPM, length = 3.0 m
Flat Ribbon cable (quantity 1) for BCPM, length = 6.1 m
Round Ribbon cable (quantity 1) for BCPM, length = 1.2 m
Round Ribbon cable (quantity 1) for BCPM, length = 3 m
Round Ribbon cable (quantity 1) for BCPM, length = 6.1 m
Round Ribbon cable (quantity 1) for BCPM, length = 2.4 m

E682large

E682medium

1/3 V low-voltage CT part numbers

PowerLogicTM BCPM solid core CTs (small, medium, large)

The PowerLogicTM BCPM uses .333 VAC output
split-core CTs for the auxiliary inputs. These
CTs are ordered separately from the BCPM.

46

Part number

Amperage rating Inside dimensions
100 A
200 A
300 A
400 A
600 A

31 mm x 100 mm
31 mm x 100 mm
31 mm x 100 mm
62 mm x 132 mm
62 mm x 132 mm

LVCT00803S
LVCT00804S
LVCT01004S
LVCT01204S
LVCT01604S
LVCT02004S
LVCT02404S

800 A
800 A
1000 A
1200 A
1600 A
2000 A
2400 A

62 mm x 132 mm
62 mm x 201 mm
62 mm x 201 mm
62 mm x 201 mm
62 mm x 201 mm
62 mm x 201 mm
62 mm x 201 mm

LVCT00102S
LVCT00202S
LVCT00302S
LVCT00403S
LVCT00603S

Solid core CT part numbers
Part number

E682A051V3
E682A101V3
E682C201V3
E682D401V3

2013

Amperage rating Inside dimensions

50A
100A
200A
400A

10 mm
10 mm
25 mm
33 mm

Multi-circuit metering

PowerLogic BCPM

0

Dimensions and connection

PowerLogic BCPM dimensions

Solid core CT dimensions

PE86183

1/3 V low-voltage CT form factor

Small form factor
100/200/300 Amp
A = 96 mm
B = 30 mm
C = 31 mm
D = 30 mm
E = 100 mm
F = 121 mm

2013

Medium form factor Large form factor
400/600/800 Amp
800/1000/1200/
A = 125 mm
1600/2000/2400 Amp
B = 73 mm
A = 125 mm
C = 62 mm
B = 139 mm
D = 30 mm
C = 62 mm
E = 132 mm
D = 30 mm
F = 151 mm
E = 201 mm
F = 151 mm

47

PowerLogic BCPM

Multi-circuit metering

0

Dimensions and connection

PowerLogic BCPM dimensions
211 mm

PE86286

1.0”
(26 mm)

2.75”
(70 mm)

1.0”
(26 mm)

146 mm
122 mm

4.6”
(117 mm)
PowerLogic BCPM adapter board (one board
per 21 split core branch CTs)

184 mm

PE86183

228 mm

48

2013

PowerLogic BCPM

Multi-circuit metering

0

PE86171

Dimensions and connection

PowerLogic BCPM with solid core CT strips installation details
Circuit monitoring
4 CT strips monitor 84 circuits
Mains monitoring
(CTs ordered separately)

Transducers (1/3 Vac)

BCPM PCB

PE86287

PowerLogic BCPM with split core CTs installation details

2013

49

Multi-circuit energy meters

EM4800 series

PE86325

Functions and characteristics

The compact PowerLogic EM4800 series multi-circuit energy meter from Schneider
Electric enables reliable metering of individual tenants with a low installation
cost-per-point by combining revenue-accurate electricity sub-metering with
advanced communications technology.
The EM4800 is ideal for multi-tenant or departmental metering applications within
office towers, condominiums, apartment buildings, shopping centres and other
multi-user environments.
The PowerLogic EM4800 series meters monitor up to 24 tenants with a single
device. Multiple meters can be combined to support an unlimited number of suites.
Three meter models offer a choice of CT secondary ratings and installation options:
PowerLogic EM4805: 5 A, split- or solid-core CTs
PowerLogic EM4833: 0.333 V, split- or solid-core CTs
PowerLogic EM4880: 80 mA, solid-core CTs

PE86326

EM4800 series multi-circuit energy meter
front (above), installed in panel (below)

Applications

Multi-tenant metering.
Energy management.
Energy cost allocation.
Utility bill verification.

Main characteristics
Compact, maintenance-free design
Requires no floor space.
Hi-density, flexible connection
From single-pole to single- or three-phase metering -- supports up to 24 circuits.
Select the connection type using an intuitive configuration tool.
Direct connection
For 100 - 300 V ac L-N electrical distribution systems:
120/240 V, 120/208 V, 230/240 V, 220/380 V, 240/415 V, 277/480 V
Multiple CT types
Support a variety of needs in both new and retrofit installations.
1/3 V output CT option does not require shorting blocks, making it the ideal choice for
retrofit installations.
No rewiring required
Use existing wiring to connect to existing panels.
Integrated communications
Onboard Ethernet and modem allows for easy integration into existing
communications networks.

Part numbers

Model Description
EM4805 24 x 5 A inputs, 230/240 V control power, 50 Hz
24 x 5 A inputs, 120 V control power, 60 Hz

METSEEM480516

24 x 5 A inputs, 230/240 V control power, 60 Hz

METSEEM480526

EM4833 24 x 333 mV inputs, 230/240 V control power, 50 Hz

METSEEM483325

24 x 333 mV inputs, 120 V control power, 60 Hz

METSEEM483316

24 x 333 mV inputs, 230/240 V control power, 60 Hz

METSEEM483326

EM4880 24 x 80 mA inputs, 120 V control power, 60 Hz
24 x 80 mA inputs, 230/240 V control power, 60 Hz

50

Part number
METSEEM480525

2013

METSEEM488016
METSEEM488026

Multi-circuit energy meters

EM4800 series

Functions and characteristics (cont.)

PE86327A

Selection guide

EM4805 EM4833 EM4880

General

b
b
b

b
b
b

b
b
b

b

b

b

b
b

b
b

b
b

b
b
b
b
b
b

b
b
b
b
b
b

b
b
b
b
b
b

real, kWh received/delivered
reactive, kvarh received/
delivered

b
b

b
b

b
b

apparent, VAh

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b
b

b
b
b
b

b
b
b
b

Use on LV systems
Accuracy

+/- 0.5%

Accuracy compliance

ANSI C12.1 and C12.20 Class
0.5;
IEC 62053-22, Class 0.5S

Maximum circuits:
single-pole / single phase /
three-phase

24 / 12 / 8

Instantaneous rms values
Energy

PowerLogic EM4800 series digital panel meter.

real, kWh received/delivered
reactive, kvarh received/
delivered
apparent, VAh

Voltage
Pulse counts
Voltage and current
Power
Power factor

V rms, I rms per phase
real, reactive, apparent

Measurements available for data logging

Energy

Voltage

Display

Backlit LCD display
2 lines of 16 characters
Optional remote modular display available

Communication

Ethernet port
V.90 modem port
Pulse inputs
2
Protocols: Modbus TCP/IP, HTTP, BACnet/IP, FTP, and SNTP

Installation options

5 A CTs
0.333 V CTs
80 mA CTs
Split core CT
Solid core CT
Remore modular display

2013

b
b
b
b
b
b

b
b
b

b
b

51

Multi-circuit energy meters

EM4800 series

Functions and characteristics (cont.)

Electrical characteristics

Input-voltage
characteristics

Inputs

V1, V2, V3, Vn

Measured voltage

80 - 480 V AC L-L without PTs
Up to 999 kV with external PTs
50/60 Hz

Frequency range

Mechanical characteristics
Weight
Dimensions

EM4805
EM4833 / EM4880
EM4805

approx. 5.4 kg
approx. 4.0 kg
33.5 cm x 44 cm x 5.5 cm
(13.125 in x 17 in x 2.125 in)

EM4833 / EM4880

33.5 cm x 30.5 cm x 5.5 cm
(13.125 in x 12 in x 2.125 in)

Environmental conditions
Operating temperature
Storage temperature
Humidity rating
Enclosure
Altitude
Pollution degree

-40°C to +70°C
-40°C to +70°C
0% to 90 % RH non-condensing
Type 1 (indoor or enclosed outdoor use)
3000 m
2

Safety and standards
UL Certified to IEC/EA/CSA 61010-1
CSA-C22.2 No 61010-1-04
FCC Part 15 Class B
ICES-003 EN55022, IEC 6100-4-5
ANSI/TIA968-A: 2002

Communication
Ports

Ethernet
V.90 modem

Pulse inputs

2

Protocols: Modbus TCP/IP, HTTP, BACnet/IP,
FTP, and SNTP

Display characteristics
Integrated backlit LCD display

52

2013

2 ines, 16 digits per line display;
R / L arrow buttons select metering point;
Display button cycles through measurements
per point.

Basic multi-function metering

ION6200

PE86127

Functions and characteristics

The PowerLogic ION6200 meter offers outstanding quality, versatility, and
functionality in a low-cost, ultra-compact unit. The meter is simple to use and offers a
big, bright LED display for superior readability in poor lighting conditions.
Complete with four-quadrant power, demand, energy, power factor, and frequency
measurements, this versatile unit is easy to wire and mount. It offers an excellent
upgrade path that lets you start with a low-cost base model and add enhanced
functionality over the long term.
The ION6200 meter lets you upgrade functionality in the field by activating the base
unit. Rather than carry a large inventory of pre-configured meters, genset and
electrical equipment manufacturers, panel shops, EMS manufacturers and energy
service providers can each adapt meter functionality to specific applications as
required.

PowerLogic ION6200.

Applications

Class 0.5S metering and sub-metering
Replace multiple analogueue meters
Basic metering
Cost allocation
Substation monitoring

Main characteristics
High visibility front panel display
The ION6200 displays all basic power parameters on a bright LED display with
twelve 19 mm high digits.
Megawatt option
The Megawatt option displays all power and energy values in millions (e.g.
megawatts) and volts in thousands (kilovolts), using a different front panel faceplate
than the standard meter, with labels for kV, MW, MVA, Mvar, MWh, MVAh and Mvarh.
Complete communications
Optional RS 485 port with standard Modbus RTU and ION compatible protocol; data
rates from 1,200 bps to 19,200 bps.
Modularity
The ION6200’s modular construction allows for simple retrofit, allowing you to save
money by making a low initial investment that can be upgraded to meet future needs.
Easy to use
Fast setup via display or software; free configuration software; and a bright, easy to
read LED display make the ION6200 easy to use.
Accuracy certification
This meter offers IEC 60687 Class 0.5S accuracy for use as a tariff meter.
Revenue metering option
Provides power and energy measurements that are certified for revenue metering
and protection against unauthorized alteration of these measured quantities.
Flexible architecture
Patented ION® technology provides a modular, flexible architecture that offers
extensive user programmability. It uniquely addresses complex monitoring and
control applications, and adapts to changing needs, avoiding obsolescence.
Multiple installation options
Supports Direct 4-wire Wye, 3-wire Wye, 3-wire Delta, Direct Delta and
single phase configurations

Part numbers

PowerLogic ION6200 meters

PowerLogic ION6200
See page 56 for part number descriptions and options.

2013

M6200

53

Basic multi-function metering

ION6200
Functions and characteristics (cont.)

PE86079

Selection guide
1

2

3

4

5

6

ION6200 ION6200 ION6200
Standard EP #1*
EP #2*

General

(N)

Use on LV and HV systems
Current and voltage accuracy(1)
Energy and power accuracy
Number of samples per cycle

Instantaneous RMS values
Current and voltage(2)
Frequency
Active power
Reactive and apparent power
Power factor

b

b

(P)

(R)

0.3%
0.5%
64

0.3%
0.5%
64

0.3%
0.5%
64

b

b
b
b

b
b
b
b
b
b

Total
per phase
Total
per phase

-

Total
per phase

-

Energy values
Active energy(3)
Reactive, apparent energy(3)

1	
2	
3	
4	
5	
6	

Current inputs
COM1 port
Power supply
D2: Form A digital out
Voltage inputs
D1: Form A digital out

Reactive and apparent power

Present and max.
Present
Max.
Present and max.

b

-

b

-

b
b
b
b

-

-

b

b
b

b
b

b
b

400/690

400/690

400/690

b
b
b

b
b
b

b
b
b

-

b

Power quality measurements
Harmonic distortion(2)

Display and I/O
LED display
Pulse output
Direct voltage connection (V ac)

Communication
RS-485 port
ION compatibility
Modbus RTU protocol

Current, voltage

b
b

-

Demand values
Current
Active power

b

b

b
b

(*) EP = ’Enhanced package.’
(1) For L-N only. L-L = 0.5% reading accuracy.
(2) Some values not available when Volts Mode is set to Delta or Delta Direct.
(3) Additional energy values available on Standard and EP#1 models through pulse output.

54

2013

Basic multi-function metering

ION6200
Functions and characteristics (cont.)

PE86127

Electrical characteristics
Type of measurement
Measurement
accuracy

Current

Voltage
Power

≥ 5% of full scale:
< 5% of full scale
I4 derivation

Frequency
Power factor
Energy
Harmonic distortion

PowerLogic ION6200.

Input-voltage Measured voltage(1)
characteristics
Measurement range
Impedance
Inputs
Overload
Dielectric withstand
Input-current
Rated Inputs(1)
characteristics

Power supply

Permissible overload
Starting current
Burden
Inputs
Dielectric withstand
AC
DC

Input/outputs

Digital outputs

RS-485 port

Mechanical characteristics

Weight
IP degree of protection (IEC 60529)
Dimensions

Environmental conditions

Operating temperature
Storage temperature
Humidity rating
Pollution degree
Installation category
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Surge immunity
Conducted immunity
Electromagnetic compatibility for industrial
environments

Safety

Communications

RS 485 port

Display characteristics

True rms electrical parameters
Up to 64 samples/cycle
0.3% reading
0.3% reading + 0.05% full scale
0.6% reading + 0.05% full scale
L-N 0.3% reading, L-L 0.5% reading
IEC 60687 Class 0.5
ANSI 12.20 Class 0.5
0.1% reading
1.0% reading
IEC 60687 Class 0.5
ANSI 12.20 Class 0.5
Total harmonic distortion + 1.0%
60-400 LN (103.5-690 LL) V ac RMS (3 phase)
60-400 LN V ac (single phase)
60-400 LN V ac
2 MW /phase
V1, V2, V3, Vref
1500 V ac RMS continuous
>3250 V ac RMS; 60 Hz for 1 minute
5 A nominal /10 A full scale RMS (+20%
overrange with full accuracy, 300 V RMS to
ground)
120 A RMS for 1 second, non-recurring
0.005 A RMS
0.05 VA (typical) @ 5 A RMS
I1, I2, I3
3000 V RMS for 1 minute
Standard: 100-240 V ac, 50-60 Hz
480 V: 480 V ac +/- 5%, 60 Hz
Standard: 110-300 V dc
Low Voltage DC: 20-60 V dc
2 optically isolated digital outputs for KY pulsing
or control
Max forward current: 150 mA
Max voltage: 200 V
Max current: 150 mA
Optically isolated
0.68 kg (shipping)
Meter with display: front IP 65, back IP 30;
Transducer unit (no integrated display): IP 30
Remote display unit: front IP 65; back IP 30
Basic unit installed depth: 106.7x106.7x40.6 mm
Remote display: 106.7x106.7x22.9 mm
-20°C to 70°C ambient air
-40°C to 85°C
5% to 95% non-condensing
2
III (Distribution)
IEC 61000-4-2 (EN61000-4-2/IEC801-2)
IEC 61000-4-3 (EN61000-4-3/IEC801-3)
IEC 61000-4-4 (EN61000-4-4/IEC801-4)
IEC 61000-4-5 (EN61000-4-5/IEC801-5)
IEC 61000-4-6 (EN61000-4-6/IEC801-6)
IEC 61000-6-2

cUL compliant to CSA C22.2 No. 1010-1
IEC1010-1 (EN61010-1)
UL 3111-1
Up to 19 200 bps, Modbus RTU, ION compatible
protocol

Bright LED display

19 mm high digits
Displays all basic power parameters
Easy setup for common configuration
parameters
Password protection on setup parameters
Password protection for demand reset
(1) The meter inputs can be used with PTs that have secondaries rated between 50 V ac and
347 V ac +25%. Use CTs that are compliant with the electrical safety code in your region.

2013

55

Basic multi-function metering

ION6200
Functions and characteristics (cont.)

Part Numbers
Item

Description

Model

M6200

ION6200 Meter Kit: ION6200 Meter base, Options Card and
Power Supply

2

Form Factor

A0
R1

Integrated display model
Transducer model with DIN rail mount, Remote Display and
14-ft cable (RJ11, 6 conductor, 26 gauge)
Transducer model with DIN rail mount, Remote Display and
6-ft cable (RJ11, 6 conductor, 26 gauge)
Transducer model DIN rail mount, Remote Display and 30-ft
cable (RJ11, 6 conductor, 26 gauge)
Transducer model with DIN rail mount (requires Comms or
pulse outputs)
10 Amp current inputs (12 Amp max)
Autoranging (57-400 V ac L-N / 99-690 V ac L-L)
Calibrated for use with 50 Hz or 60 Hz systems
No communications
Single RS-485 port (supports Modbus RTU protocol and
ION-compatible PML protocol)
No I/O
This option activates the two Form A digital outputs for kWh,
kvarh energy pulsing
No hardware lock (setup is password protected)
RMANSI: Revenue Meter approved for use in the United
States (ANSI C12.16 approved; meets ANSI C12.20 class 0.5
accuracy at 23°C; 10A current inputs only)
RMICAN: Measurement Canada approved revenue meter for
use in Canada (10A current inputs only)
**RMICAN-SEAL: Factory-sealed and Measurement Canada
approved revenue meter
Standard Measurements (Volts/Amps per phase and avg)
Enhanced Package #1 (Standard Measurements plus
Energy/Power total, Frequency, Power Factor total, Neutral
Current
Enhanced Package #2 (all measurements)

PE86080

Code

1

Example product part number.
1	 Model.
2	 Form factor.
3	 Current inputs.
4	 Voltage inputs.
5	 Power supply.
6	 System frequency.
7	 Communications.
8	 Onboard inputs/outputs.
9	 Security.
10	Measurement package.

R2
R3
T1
3
4
6
7

Current Inputs
Voltage Inputs
System Frequency
Communications

A
0
0
Z0
A0

8

I/O

A
B

9

Security

0
2
3
4

10 Measurement
package

N
P
R

PE86081

Power supply
Power supply

P620PB Standard plug-in power supply (100-240 V ac / 50-60 Hz or
110-300 V dc)
P620PC Low voltage DC plug-in power supply (20-60 V dc)
P620PD 480V power supply (480 VAC, 60 Hz)

56

2013

Basic multi-function metering

ION6200
Functions and characteristics (cont.)

PE86082

MegaWatt options
MegaWatt option on meter base with integrated display. Not available for
RMICAN or RMICAN-sealed meters

M0

MegaWatt option on Transducer model with DIN rail mount, Remote Display N1
and 14-ft cable (RJ11, 6 conductor, 26 gauge). Not available with Security
options RMICAN or RMICAN-SEAL.
MegaWatt option on Transducer model with DIN rail mount, Remote Display N2
and 6-ft cable (RJ11, 6 conductor, 26 gauge). Not available with Security
options RMICAN or RMICAN-SEAL.
MegaWatt option on Transducer model with DIN rail mount, Remote Display N3
and 30-ft cable (RJ11, 6 conductor, 26 gauge). Not available with Security
options RMICAN or RMICAN-SEAL.

PE86083

Options card
1
2
3
4
5
6
7
8
9
10
11
12

Standard Measurements
Enhanced Package #1
Enhanced Package #2
Standard Measurements, two pulse outputs
Enhanced Package #1, two pulse outputs
Enhanced Package #2, two pulse outputs
Standard Measurements, RS-485
Enhanced Package #1, RS-485
Enhanced Package #2, RS-485
Standard Measurements, two pulse outputs, RS-485
Enhanced Package #1, two pulse outputs, RS-485
Enhanced Package #2, two pulse outputs, RS-485

Z0A0N
Z0A0P
Z0A0R
Z0B0N
Z0B0P
Z0B0R
A0A0N
A0A0P
A0A0R
A0B0N
A0B0P
A0B0R

Remote modular display (RMD)
Model
Display Type

Cable Length

Standard Display
MegaWatt option - for use with Transducer meter base with
MegaWatt option
No Cable
14-ft cable for connecting Remote Display Unit to the
ION6200 Transducer meter base
6-ft cable for connecting Remote Display Unit to the
ION6200 Transducer meter base
30-ft cable for connecting Remote Display Unit to the
ION6200 Transducer meter base

M620D
R
N
0
1
2
3

Cables for remote modular display
14-ft cable for connecting Remote Display Unit to the ION6200 transducer
meter base.
6-ft cable for connecting Remote Display Unit to the ION6200 transducer
meter base.
30-ft cable for connecting Remote Display Unit to the ION6200 transducer
meter base.

2013

P620C1
P620C2
P620C3

57

Basic multi-function metering

ION6200
Dimensions and connections

PE86085

PE86084

ION6200 integrated model dimensions

PE86087

PE86086

ION6200 TRAN model dimensions

58

PE86085

PE86088

ION6200 RMD dimensions

2013

ION6200
Dimensions and connections (cont.)

PE86089

Mounting integrated model - ANSI 4” (4 1/2” Switchboard)
85.7 mm
4.67 mm
diameter

101.6 mm
diameter

screw &
washer
85.7 mm

mounting
surface

Mounting integrated model - DIN 96
PE86090

screws fit in corners;
holes not required

92 mm x 92 mm

Mounting the TRAN model
RMD port faces up

PE86091

Basic multi-function metering

2013

59

Basic multi-function metering

Power Meter Series PM3200
Functions and characteristics

PB108433

This PowerLogic Power meter offers basic to advanced measurement capabilities.
With compact size and DIN rail mounting, the PM3200 allows mains and feeders
monitoring in small electrical cabinets. Combined with current transformers and
voltage transformers, these meters can monitor 2-, 3- and 4-wire systems. The
graphic display has intuitive navigation to easily access important parameters.

PB108435

Power Meter Series PM3200

Power Meter Series PM3255

Four versions are available offering basic to advanced applications:
b PM3200
v Electrical parameters I, In, U, V, PQS, E, PF, Hz
v Power/current demand
v Min/max.
b PM3210
v Electrical parameters I, In, U, V, PQS, E, PF, Hz, THD
v Power/current demand, peak demand
v Min/max.
v 5 timestamped alarms
v kWh pulse output
b PM3250
v Electrical parameters I, In, U, V, PQS, E, PF, Hz, THD
v Power/current demand, peak demand
v Min/max.
v 5 timestamped alarms
v LED to indicate communications
v RS485 port for Modbus communication
b PM3255
v Electrical parameters I, In, U, V, PQS, E, PF, Hz, THD
v Power/current demand and peak demand
v Min/max. and 15 timestamped alarms
v LED to indicate communications
v Up to 4 tariffs management
v 2 digital inputs, 2 digital outputs
v Memory for load profile (demand 10mn to 60mn)
v RS485 port for Modbus communication
b	 Innovative design makes the meters smart and simple:
b	 Easy to install for panel builders
b	 Easy to commission for contractors and installers
b	 Easy to operate for end users

Applications
Cost management applications

b�Bill checking
b	 Sub-billing, including WAGES view
b	 Cost allocation, including WAGES view

Network management applications

b	 Panel instrumentation
b	 Up to 15 onboard timestamped alarms to monitor events
b	 Easy integration with PLC system by input/output interface

Market segments

Front of meter parts
1 Control power
2 Display with white backlit
3 Flashing yellow meter indicator (to check accuracy)
4 Pulse output for remote transfer (PM3210)
5
Cancellation
6
Confirmation
7
Up
8
Down

b	 Buildings
b	 Industry
b	 Data centres and networks
b	 Infrastructure (airports, road tunnels, telecom)

Part numbers
Meter model and description

Performance

Part no.

PM3200 basic power meter

Basic power meter

METSEPM3200

PM3210 power meter with pulse output

Power, current, THD, peak demand METSEPM3210

PM3250 power meter with RS485 port

Power, current, THD, peak demand METSEPM3250

PM3255 power meter plus 2 digital inputs, Power, current, THD, peak demand, METSEPM3255
2 digital outputs with RS485 port
memory for load profile

60

2013

Power Meter Series PM3200

Basic multi-function metering

Functions and characteristics (cont.)

Function guide

PM3200 Range
PM3200

PM3210

PM3250

PM3255

b

b

b

b

Performance standard
IEC61557-12 PMD/Sx/K55/0.5

General

Use on LV and HV systems

b

b

b

b

Number of samples per cycle
CT input 1A/5A

32
b

32
b

32
b

32
b

VT input

b

b

b

b

Multi-tariff

4
b

4
b

4
b

4
b

Multi-lingual backlit display

Instantaneous rms values
Current, voltage

Per phase and average

b

b

b

b

Active, reactive, apparent power

Total and per phase

b

b

b

b

Power factor

Total and per phase

b

b

b

b

b

b

b

b

Energy values

Active, reactive and apparent energy; import and export

Demand value

Current, power (active, reactive, apparent) demand; present

b

Current, power (active, reactive, apparent) demand; peak

Power quality measurements

THD Current and voltage

Data recording

b

Min/max of the instantaneous values

b

b

b

b

b

b

b

b

b

b

b

b
b

Power demand logs

b

Energy consumption log (day, week, month)
Alarms with time stamping

5

Digital inputs/digital outputs

0/1

Communication

5

15
2/2

RS-485 port

b

b

Modbus protocol

b

b

PB108434

Connectivity advantages
Programmable digital input

External tariff control signal (4 tariffs)
Remote Reset partial counter
External status like breaker status
Collect WAGES pulses

Programmable digital output

Alarm (PM3255)
kWh pulses

Graphic LCD display

Backlit graphic display allows smart navigation in relevant
information and in multi languages

Communication

Modbus RS485 with screw terminals allows connection to a
daisy chain

Power Meter Series PM3210

2013

61

Basic multi-function metering

Power Meter Series PM3200

Functions and characteristics (cont.)

Specifications
Type of measurement

PM3200 Range
True rms up to the 15th harmonic on three-phase (3P,3P+N) and single-phase
AC systems. 32 samples per cycle

Measurement accuracy
Current with x/5A CTs

0.3% from 0.5A to 6A

Current with x/1A CTs

0.5% from 0.1A to 1.2A

Voltage

0.3% from 50V to 330V (Ph-N), from 80V to 570V (Ph-Ph)

Power factor

±0.005 from 0.5A to 6A with x/5A CTs; from 0.1A to 1.2A with x/1A CTs and from
0.5L to 0.8C

Active/Apparent Power with x/5A CTs

Class 0.5

Active/Apparent Power with x/1A CTs

Class 1

Reactive power

Class 2

Frequency

0.05% from 45 to 65Hz

Active energy with x/5A CTs

IEC62053-22 Class 0.5s

Active energy with x/1A CTs

IEC62053-21 Class 1

Reactive energy

IEC62053-23 Class 2

Data update rate
Update rate

1s

Input-voltage characteristics
Measured voltage

50V to 330V AC (direct / VT secondary Ph-N)
80V to 570V AC (direct / VT secondary Ph-Ph)
up to 1MV AC (with external VT)

Frequency range

45Hz to 65Hz

Input-current characteristics
CT primary

Adjustable from 1A to 32767A

CT secondary

1A or 5A

Measurement input range with x/5A CTs

0.05A to 6A

Measurement input range with x/1A CTs

0.02A to 1.2A

Permissible overload

10A continuous, 20A for 10s/hour

Control Power
AC

100/173 to 277/480V AC (+/-20%), 3W/5VA; 45Hz to 65Hz

DC

100 to 300V DC, 3W

Input

Digital inputs (PM3255)

Output

62

11 to 40V DC, 24V DC nominal, <=4mA maximum burden, 3.5kVrms insulation

Digital output (PM3210)

Optocoupler, polarity sensitive, 5 to 30V, 15mA max, 3.5kVrms insulation

Digital outputs (PM3255)

Solid state relay, polarity insensitive, 5 to 40V, 50mA max, 50Ω max,
3.5kVrms insulation

2013

Basic multi-function metering

Power Meter Series PM3200

Functions and characteristics (cont.)

Specifications (continued)

PM3200 Range

Mechanical characteristics
Weight

0.26kg

IP degree of protection (IEC60529)

IP40 front panel, IP20 meter body

Dimension

90 x 95 x 70mm

Environmental conditions
Operating temperature

-25 ºC to +55 ºC

Storage temperature

-40 ºC to +85 ºC

Humidity rating

5 to 95% RH at 50ºC (non-condensing)

Pullution degree

2

Metering category

III, for distribution systems up to 277/480VAC

Dielectric withstand

As per IEC61010-1, Doubled insulated front panel display

Altitude

3000m max

Electromagnetic compatibility
Electrostatic discharge

Level IV (IEC61000-4-2)

Immunity to radiated fields

Level III (IEC61000-4-3)

Immunity to fast transients

Level IV (IEC61000-4-4)

Immunity to surge

Level IV (IEC61000-4-5)

Conducted immunity

Level III (IEC61000-4-6)

Immunity to power frequency magnetic fields

0.5mT (IEC61000-4-8)

Conducted and radiated emissions

Class B (EN55022)

Safety

CE as per IEC61010-1 (1)

Communication
RS485 port

Half duplex, from 9600 up to 38400 bauds, Modbus RTU (double insulation)

Display characteristics
Dimensions (VA)

43mm x 34.6mm

Display resolution

128 x 96 dots

Standard compliance
IEC61557-12, EN61557-12
IEC61010-1, UL61010-1
IEC62052-11, IEC62053-21, IEC62053-22, IEC62053-23
EN50470-1, EN50470-3
(1) Protected throughout by double insulation

Multi-tariff capability
The PM3200 range allows arrangement of kWh
consumption in four different registers. This can be
controlled by:
b Digital Inputs. Signal can be provided by PLC or utilities
b Internal clock programmable by HMI
b Through communication
This function allows users to:
b Make tenant metering for dual source applications to
differentiate backup source or utility source
b Understand well the consumption during working time
and non working time, and between working days and
weekends
b Follow up feeders consumption in line with utility tariff
rates
Power Meter Series PM3250

2013

63

Power Meter Series PM3200

Basic multi-function metering

Dimensions and connection

PB105302

PM3200 series dimensions

PM3200 series easy installation
PB105446

PM3200 top and lower flaps

64

2013

Basic multi-funtional metering

PM5350

Functions and characteristics

PE86278

The PowerLogic PM5350 power meter offers all the measurement capabilities
required to monitor an electrical installation in a single 96 x 96 mm unit extending only
44 mm behind the mounting surface.
With its large display, all three phases and neutral can be monitored simultaneously.
The bright, anti-glare display features large characters and powerful backlighting
for easy reading even in extreme lighting conditions and viewing angles. The meter
menus are understood by all, with the availability of two languages (English/Chinese)
included standard in the PM5350.
Its compact size and high performance make the PowerLogic PM5350 suitable for
many applications.
Applications
Panel instrumentation.
Cost allocation or energy management.
Electrical installation remote monitoring.
Alarming with under/over, digital status, control power failure, meter reset,
self diagnostic issue.
Circuit Breaker monitoring and control with relay outputs and whetted digital inputs.
Main characteristics
Easy to install
Mounts using two clips, no tools required. Ultra compact meter with 44mm depth
connectable up to 480 VL-L without voltage transformers for installations compliant
with category III, as per IEC 61010-1. See specification table for UL voltage limits.
PowerLogic PM5350.

Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four
concurrent values. Two LEDs on the meter face help the user confirm normal
operation (heartbeat/communications indicator LED: green and other LED orange,
customizable either for alarms or energy pulse outputs).
Easy circuit breaker monitoring and control
The PM5350 provides two relay outputs (high performance) with capability to
command most of the circuit breaker coils directly. In addition, monitored switches
can be wired directly to the meter without external power supply.
System status at a glance
Bright, anti-glare, backlit display plus two LEDs; orange for energy pulse or alarm
and green for heartbeat/communications indication.
IEC 62053-22 class 0.5S accuracy for active energy
Accurate energy measurement for cost allocation.
Power Quality analysis
The PM5350 offers THD and TDD measurements as standard. Total Demand
Distortion is based on a point of common coupling (PCC), which is a common point
that each user receives power from the power source. The TDD compares the
contribution of harmonics versus the maximum demand load.
Load management
Peak demands with time stamping are provided. Predicted demand values can be
used in basic load shedding applications.
Alarming with time stamping
Over 30 alarm conditions, such as under/over conditions, digital input changes, and
phase unbalance inform you of events. A time-stamped log maintains a record of the
last 40 alarm events.
Load timer
Load timer setpoint adjustable to monitor and advise maintenance requirements.
Performance Standard Meets IEC 61557-12 PMD/S/K70/0.5.

2013

65

Basic multi-funtional metering

PM5350

Functions and characteristics (cont.)

PE86323

General
Use on LV and MV systems

b

Basic metering with THD and min/max readings

b

Instantaneous rms values
Current

Total, Phases and neutral

b

Voltage

Total, Ph-Ph and Ph-N

b

Frequency
Real, reactive, and
apparent power

Total and per phase

b
Signed

True Power Factor

Total and per phase

Signed, Four Quadrant

Displacement PF

Total and per phase

Signed, Four Quadrant

Unbalanced I, VL-N, VL-L

b

PE86324

Energy values

Stored in
non-volatile
memory
Received/Delivered;
Net and absolute;

b

Current average

Present, Last, Predicted,
Peak, & Peak Date Time

b

Active power

Present, Last, Predicted,
Peak, & Peak Date Time
Present, Last, Predicted,
Peak, & Peak Date Time

b

Present, Last, Predicted,
Peak, & Peak Date Time

b

Accumulated Active, Reactive and Apparent Energy

Demand values

Reactive power
Apparent power

b

Peak demand with timestamping D/T for current & powers b

b

b

b

b

b

I/O timer

b

b

Operating timer

b

b

Active load timer

b

b

Alarm counters

b

b

Demand calculation

Sliding, fixed and rolling block,
thermal

Synchronization of the measurement window

Other measurements

PM5350 meter parts
A Retainer clips.
B Control power supply connector.
C Voltage inputs.
D Digital outputs.
E Rs485 port (COM1).
F Digital outputs.
G Optical revenue switch.
H Current inputs.

Power quality measurements
THD, thd (Total Harmonic Distortion)

I,VLN, VLL

TDD, thd (Total Demand Distortion)

b

Data recording
Min/max of instantaneous values, plus phase
identification

b

Alarms with 1s timestamping

Standard 29; Unary 4;
Digital 4

Alarms stored in non-volatile memory

40 events

Inputs/Outputs
Digital inputs

4 (DI1, DI2, DI3, DI4)

Digital outputs

2 relay outputs (DO1,
DO2)

Display
White backlit LCD display, 6 lines, 4 concurrent values

b

IEC or IEEE visualization mode

b

Communication

66

Modbus RTU, Modbus ASCII, Jbus Protocol

b

Firmware update via RS485 serial port
(DLF3000 via the Schneider Electric website:
www.schneider-electric.com)

b

2013

b

b

Basic multi-funtional metering

PM5350

Functions and characteristics (cont.)

Electrical characteristics

Current, Phase (1)
Voltage, L-N (1)

True rms up to the 15th harmonic on three-phase
(3P, 3P + N)
32 samples per cycle, zero blind
±0.30%
±0.30%

Power Factor (1)

±0.005

Power, Phase

IEC 61557-12 Class 0.5; For 5 A nominal CT (for 1
A nominal CT when I > 0.15A)
±0.5% from 0.25 A to 9.0 A at COS φ = 1
±0.6% from 0.50 A to 9.0 A at COS φ = 0.5 (ind or cap)

Frequency (1)

±0.05%
IEC 62053-22 Class 0.5S; IEC 61557-12 Class 0.5;
For 5 A nominal CT (for 1 A nominal CT when I > 0.15A)
±0.5% from 0.25 A to 9.0 A at COS φ = 1
±0.6% from 0.50 A to 9.0 A at COS φ = 0.5 (ind or cap)
IEC 61557-12 Class 0.5
IEC 62053-23 Class 3, IEC 61557-12 Class 2
For 5 A nominal CT (for 1 A nominal CT when I > 0.15A)
±2.0% from 0.25 A to 9.0 A at SIN φ = 1
±2.5% from 0.50 A to 9.0 A at SIN φ = 0.5 (ind or cap)

PE86292

Type of measurement
Measurement
accuracy

Real Energy

Reactive Energy

Data update rate
Input-voltage

VT primary
U nom

Front screen view of PM5350.
Input-current

AC control
power

DC control
power

Measured voltage with
overrange & Crest Factor
Permanent overload
Impedance
Frequency range
CT ratings
Primary
Secondary

1 second nominal (50/60 cycles)
1.0 MV AC max, starting voltage depends on VT ratio.
277 V L-N
IEC: 20 to 690 V AC L-L; 20 to 400 V AC L-N
UL: 20 to 300 V AC L-L
700 Vac L-L, 404 Vac L-N	
10 M W
45 to 70 Hz
Adjustable 1 A to 32767 A
1A, 5 A nominal

Measured voltage with
overrange & Crest Factor

5 mA to 9 A

Withstand
Impedance
Frequency range
Burden
Operating range

Continuous 20 A,10 sec/hr 50 A,1 sec/hr 500 A

Burden

4.1 VA / 1.5 W typical, 6.7 VA / 2.7 W max at 120 V AC
6.3 VA / 2.0 W typical, 8.6 VA / 2.9 W max at 230 V AC
9.6 VA / 3.5 W maximum at 265 V AC

Frequency
Ride-through time

45 to 65 Hz
100 mS typical at 120 V AC and maximum burden
400 mS typical at 230 V AC and maximum burden

Operating range

100 to 300 V DC

Burden

1.4 W typical, 2.6 W maximum at 125 V DC
1.8 W typical, 2.7 W maximum at 250 V DC
3.2 W maximum at 300 V DC
50 mS typical at 125 V DC and maximum burden

Ride-through time

< 0.3 mW
45 to 70 Hz
< 0.024 VA at 9 A
85 - 265 V AC

Real time clock Ride-through time

30 seconds

Digital output

Number/Type

2 - Mechanical Relays

Output frequency

Isolation

0.5 Hz maximum (1 second ON / 1 second OFF minimum times)
250 V AC at 2.0 Amps, 200 k cycles, resistive
250 V AC at 8.0 Amps, 25 k cycles, resistive
250 V AC at 2.0 Amps, 100 k cycles, COSΦ=0.4
250 V AC at 6.0 Amps, 25 k cycles, COSΦ=0.4
30 V DC at 2.0 Amps, 75 k cycles, resistive
30 V DC at 5.0 Amps, 12.5 k cycles, resistive
2.5 kVrms

Voltage ratings

ON 18.5 to 36 V DC, OFF 0 to 4 V DC

Input Resistance

110 k W

Maximum Frequency

2 Hz (T ON min = T OFF min = 250 ms)

Response Time

10 ms

Switching Current

Status Digital
Inputs

Isolation
Whetting output Nominal voltage

2.5 kVrms
24 V DC

Allowable load

4 mA

Isolation

2.5 kVrms

(1) Measurements taken from 45 Hz to 65 Hz, 0.5 A to 9 A, 57 V to 347 V & 0.5 ind to 0.5 cap
power factor with a sinusoidal wave.

2013

67

Basic multi-funtional metering

PM5350

Functions and characteristics (cont.)

Mechanical characteristics
Weight
IP degree of protection (IEC 60529)
Dimensions
WxHxD

250 g
IP51 front display, IP30 meter body
96 x 96 x 44 mm (depth of meter from housing
mounting flange)

Mounting position
Panel thickness

Vertical
6.35 mm maximum

96 x 96 x 13 mm (protrusion of meter from housing flange)

Environmental characteristics
Operating
temperature

Meter

-25 °C to 70 °C

Display

-20 °C to +70 °C
(Display functions to -25°C with reduced performance)

Storage temp.
Humidity rating
Pollution degree
Altitude

Meter + display

-40 °C to +85 °C
5 to 95 % RH at 50 °C (non-condensing)
2
3000 m max.

Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields

IEC 61000-4-2(2)
IEC 61000-4-3(2)

Immunity to fast transients

IEC 61000-4-4(2)

Immunity to impulse waves

IEC 61000-4-5(2)

Conducted immunity

IEC 61000-4-6(2)

Immunity to magnetic fields

IEC 61000-4-8(2)

Immunity to voltage dips

IEC 61000-4-11(2)

Radiated emissions

FCC part 15 class A, EN 55011 Class A

Conducted emissions

FCC part 15 class A, EN 55011 Class A

Harmonics

IEC 61000-3-2(2)

Flicker emissions

IEC 61000-3-3(2)

Safety
Europe

e, as per IEC 61010-1

U.S. and Canada

cULus as per UL61010-1, IEC 61010-1 (2nd Edition)

Measurement category (Voltage and current Per IEC 61010-1:
inputs)
CAT III, 277 V L-N / 480 V L-L (1) nominal;
CAT II 400 V L-N / 690 V L-L (1) nominal
Per UL 61010-1 and CSA C22.2 No. 61010-1:
CAT III, 300 V L-L

Dielectric

CAT III
As per IEC 61010-1
Double insulated front panel display

Protective Class

II

Overvoltage Category (Control power)

Communication
RS 485 port

2-Wire, 9600,19200 or 38400 baud, Parity - Even,
Odd, None, 1 stop bit if parity Odd or Even, 2 stop bits if
None; Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS

Firmware and language file update

Update via comunication port using DLF3000 software

Isolation

2.5 kVrms, double insulated

Human machine interface
Display type

Monochrome Graphics LCD

Resolution

128 x 128

Backlight

White LED

Viewable area (W x H)

67 x 62.5 mm

Keypad

4-button

Indicator Heartbeat / Comm activity

Green LED

Energy pulse output / Active alarm indication (configurable)
Type

Optical, amber LED

Wavelength

590 to 635 nm

Maximum pulse rate

2.5 kHz

(1) V L-L is limited to 700 V AC
(2) As per IEC 61557-12

68

2013

PM5350 Power Meter

Basic multi-funtional metering

Dimensions and connection

PE86279

Rear of meter - open

PE86274

Rear view retainers - installation

For detailed installation instructions see the product's Installation guide.

2013

69

PM5350 Power Meter

Basic multi-funtional metering

Dimensions and connection (cont.)

PE86275

Rear view retainers - users

For detailed installation instructions see the product's Installation guide.

70

2013

Basic multi-function metering

PM5000 Series

Functions and characteristics

PB111776

PowerLogic™ PM5100, PM5300 and PM5500 series
The PowerLogic™ PM5000 power meter is the ideal fit for cost management
applications. It provides the measurement capabilities needed to allocate energy usage,
perform tenant metering and sub-billing, pin-point energy savings, optimize equipment
efficiency and utilization, and perform a high level assessment of the power quality of the
electrical network.
In a single 96 x 96 mm unit, with a graphical display, all three phases, neutral and
ground can be monitored simultaneously.
The bright, anti-glare display features large characters and powerful backlighting
for easy reading even in extreme lighting conditions and viewing angles.
Easy to understand menus, text in 8 selectable languages, icons and graphics create
a friendly environment to learn about your electrical network.
Highly accurate devices with global billing certifications.
Applications

PowerLogic™ PM5000 Series meter

Commercial reference numbers
PM5100

METSEPM5100

PM5110

METSEPM5110

PM5111

METSEPM5111

PM5310

METSEPM5310

PM5320

METSEPM5320

PM5330

METSEPM5330

PM5331

METSEPM5331

PM5340

METSEPM5340

PM5341

METSEPM5341

PM5560

METSEPM5560

PM5561

METSEPM5561

PM5563

METSEPM5563

Cost management: Cost saving opportunities becomes clear once you understand
how and when your facility uses electricity. These meters are ideal for:
bb Sub billing / tenant metering: allows a landlord, property management firm,
condominium association, homeowners association, or other multi-tenant property to
bill tenants for individual measured utility (electricity) usage. MID approved meters for
billing applications across Europe.
bb Cost allocation: allocate energy costs between different departments (HVAC,
indoor and outdoor lighting, refrigeration, etc), different parts of an industrial process
or different cost centres. Cost allocation systems can help you save money by making
changes to your operation, better maintaining your equipment, taking advantage of
pricing fluctuations, and managing your demand.
Network management: Improving reliability of the electrical network is key for
success in any business. Monitoring values such as voltage levels, harmonic
distortion and voltage unbalance will help you to ensure proper operation and
maintenance of your electrical network and equipment. PowerLogic™ PM5000 series
meters are the perfect tool for:
bb Basic Power Quality monitoring: power quality phenomena can cause
undesirable effects such as heating in transformers, capacitors, motors, generators
and misoperation of electronic equipment and protection devices.
bb Min/ Max monitoring (with timestamp): understanding when electrical
parameters, such as voltage, current and power demand, reach maximum and
minimum values will give you the insight to correctly maintain your electrical network
and assure equipment will not be damaged.
bb Alarming: alarms help you to be aware of any abnormal behavior on the electrical
network in the moment it happens.
bb WAGES monitoring: take advantage of the input metering on PM5000 meters to
integrate measurements from 3rd party devices such as water, air, gas, electricity or
steam, meters.
Main characteristics
Easy to install
Mounts using two clips, in standard cut out for DIN 96 x 96mm, no tools required.
Compact meter with 72mm (77mm for PM5500) depth connectable up to 690 VL-L
without voltage transformers for installations compliant with category III.
Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four
concurrent values. Two LEDs on the meter face help the user confirm normal
operation with a green LED - heartbeat/communications indicator, and the amber LED
- customizable either for alarms or energy pulse outputs.
Easy circuit breaker monitoring and control
The PM5300 provides two relay outputs (high performance Form A type) with
capability to command most of the circuit breaker coils directly. For Digital Inputs,
monitored switches can be wired directly to the meter without external power supply.
PM5500 series have 4 status inputs (digital) and 2 digital output (solid state) to use for
WAGES monitoring, control and alarm annunciation.

Accurate energy measurement for precise cost allocation:
PM5100

PM5300

PM5500

IEC 62053-22 (Active Energy)

Class 0.5S

Class 0.5S

Class 0.2S

IEC 62053-24 (Reactive Energy)

Class 2

Class 2

Class 1

2013

71

Basic multi-function metering

PM5000 Series

Functions and characteristics (cont.)

Direct metering of neutral current
The PM5500 has a fourth CT for measuring neutral current. In demanding IT
applications, where loads are non-linear (i.e. switching power supplies on computers/
servers), measuring neutral current is essential to avoid overload and resulting
outage. In addition, the PM5500 provides a calculated ground current value, not
available in meters with 3 CTs.
Power Quality analysis
The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand
Distortion (TDD) measurements and individual harmonics (odd) magnitudes and
angles for voltage and current:

Individual Harmonics

PowerLogic™ PM5500 meter

PM5100

PM5300

PM5500

magnitudes
up to 15th

magnitudes
up to 31st

magnitudes
& angles
up to 63rd

These types of power quality parameters help to identify the source of harmonics
that can harm transformers, capacitors, generators, motors and electronic
equipment.
Load management
Peak demands with time stamping are provided. Predicted demand values can be
used in combination with alarms for basic load shedding applications.
Alarming with time stamping
A different combination of set point driven alarms and digital alarms with 1s time
stamping are available in the PM5000 family:
PM5100

PM5300

PM5500

Set point driven alarms

29

29

29

Unary

4

4

4

Digital

2

2

4

Boolean / Logic

–

–

10

Custom defined

–

–

5

PowerLogic™ PM5300 meter

Alarms can be visualized as Active (the ones that have picked up and did not drop out
yet) or Historical (the ones that happened in the past).
Alarms can be programmed and combined to trigger digital outputs and mechanical
relays (PM5300).
The PM5000 series keeps an alarm log with the active and historical alarms with date
and time stamping.
Load timer
A load timer can be set to count load running hours based on a minimum current
withdraw, adjustable to monitor and advise maintenance requirements on the load.

PowerLogic™ PM5100 meter

High Performance and accuracy
IEC 61557-12 Performance measuring and monitoring devices (PMD)
Defines the performance expectation based on classes. It defines the allowable
error in the class for real and reactive power and energy, frequency, current, voltage,
power factor, voltage unbalance, voltage and current harmonics (odds), voltage
THD, current THD, as well as ratings for temperature, relative humidity, altitude, startup current and safety. It makes compliant meters readings comparable - they will
measure the same values when connected to the same load.
Meets IEC 61557-12 PMD/S/K70/0.5 for PM5100 and PM5300

Certified
according
to
MID
Directive, Annex "B" + Annex "D" for
legal metrology relevant to active
electrical energy meters (see Annex MI-003 of
MID). Can be used for fiscal (legal) metrology.

MID

Meets IEC 61557-12 PMD/S/K70/0.2 for PM5500
Legal billing compliance
MID compliance is compulsory for billing applications across Europe.
In addition to billing applications, for facility managers responsible for energy cost
MID means same level of quality as a billing meter.
MID ready compliance, EN50470-1/3 – Class C

72

2013

Basic multi-function metering

PM5000 Series

Functions and characteristics (cont.)

General

PM5100

PM5300

Use on LV and MV systems

b

Basic metering with THD and min/max readings

b

Instantaneous rms values

PM5500

Current

per phase, neutral and ground
(PM5500)

b

Voltage

Total, per phase L-L and L-N

b

Frequency
Real, reactive, and
apparent power

Total and per phase

b
Signed, Four Quadrant

True Power Factor

Total and per phase

Signed, Four Quadrant

Displacement PF

Total and per phase

Signed, Four Quadrant
b

% Unbalanced I, VL-N, VL-L
Direct monitoring of neutral current

b

Energy values*
Accumulated Active, Reactive and Apparent Energy

Received/Delivered; Net and absolute; Time Counters

Demand values*
Current average

Present, Last, Predicted, Peak, and Peak Date Time

Active power

Present, Last, Predicted, Peak, and Peak Date Time

Reactive power

Present, Last, Predicted, Peak, and Peak Date Time

Apparent power

Present, Last, Predicted, Peak, and Peak Date Time

Peak demand with time stamping D/T for current and powers

b

Demand calculation

Sliding, fixed and rolling block,
thermal methods

b

Synchronization of the measurement window to input,
communication command or internal clock

b

Settable Demand intervals

b
b

Demand calculation for Pulse input (WAGES)

Other measurements*
I/O timer

b

Operating timer

b

Load timer

b

Alarm counters and alarm logs

b

Power quality measurements

I,VLN, VLL

THD, thd (Total Harmonic Distortion) I, VLN, VLL per phase

b

TDD (Total Demand Distortion)
Individual harmonics (odds)

15th

31st

63rd
b

Neutral Current metering with ground current calculation

Data recording
Min/max of instantaneous values, plus phase identification*

b

Alarms with 1s timestamping*

b

Data logging

Memory capacity
b

Min/max log
Maintenance, alarm and event logs

2 fixed parameters kWh and
kVAh with configurable interval
and duration (e.g. 2 parameters
for 60 days at 15 minutes
interval)
256 kB

Up to 14 selectable parameters
with configurable interval and
duration (e.g. 6 parameters for 90
days at 15 minutes interval)

b

b

b

b

1.1 MB

b

Customizable data logs

Inputs/Outputs/Relays

2 (SI1, SI2)

Digital inputs
Digital outputs

1 (kWh only)

4 (SI1, SI2, SI3, SI4) with WAGES
support
2 (configurable)

2

Form A Relay outputs
Timestamp resolution in seconds

1

Whetting voltage

b

*Stored in non-volatile memory

2013

73

Basic multi-function metering

PM5000 Series

Functions and characteristics (cont.)

Electrical characteristics*

PM5100

64 samples per cycle

Type of measurement: True rms on three-phase
(3P, 3P + N), zero blind
Measurement IEC 61557-12
accuracy
IEC 62053-22 Active Energy

Active Power

PMD/[SD|SS]/K70/0.2

Class 0.5S

Class 0.2S

Class 2S

Class 1S

±0.5%
±2%
Class 0.5 as per IEC 61557-12

±0.2%
±1%
Class 0.2 as per IEC 61557-12

Apparent Power

Class 0.5 as per IEC 61557-12

Current, Phase

Class 0.5 as per IEC 61557-12

±0.15%

Voltage, L-N

Class 0.5 as per IEC 61557-12

±0.1%

Frequency

±0.05%

MID Directive EN50470-1, EN50470-3
Input-voltage
(up to 1.0
MV AC max,
with voltage
transformer)

Nominal Measured Voltage range

Input-current
(configurable
for 1 or 5 A
secondary
CTs)

I nom

AC control
power

Annex B and Annex D (Optional model references) Class C
20 V L-N / 35 V L-L to 400 V L-N /690 V L-L
absolute range 35 V L-L to 760 V L-L

absolute range 20 V L-L to 828 V L-L

50 or 60 Hz ±5%

F nom
Measured Amps with over range and
Crest Factor

5 mA to 8.5 A

Starting current: 5m A
Operating range: 50 mA to 10 A

Continuous 20 A,10 sec/hr 50 A

Withstand
Impedance
F nom
Burden
Operating range

< 0.3 mΩ
50 or 60 Hz ±5%

50 or 60 Hz ±10%

< 0.024 VA at 10 A
100- 415 V AC L-L ±10%
CAT III 300V class per IEC 61010
<5 W,11 VA at 415V L-L

Operating range

35 ms typical at 120 V L-N and
maximum burden
129 ms typical at 230 V L-N and
maximum burden

125-250 V DC ±20%

Burden

<4 W at 250 V DC

typical 3.1W at 125 V DC, max. 5W

50 mS typical at 125 V DC and maximum burden

Mechanical Max output frequency

0.5 Hz maximum (1 second ON /
1 second OFF - minimum times)
250 V AC at 8.0 Amps, 25 k
cycles, resistive
30 V DC at 2.0 Amps, 75 k cycles,
resistive 30 V DC at 5.0 Amps,
12.5 k cycles, resistive
2.5 kV rms

Switching current

Isolation
Digital
outputs

100-480 V AC ±10%
CAT III 600V class per IEC 61010
<5W/16.0 VA at 480 V AC

45 to 65 Hz
80 mS typical at 120V AC and maximum burden.
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden

Ride-through time

2

1

2

Max load voltage

40 V DC (AC not available)

30 V AC / 60 V DC

Max load current

20 mA

125 mA

On Resistance

50 Ω max

8Ω

Meter constant

from 1 to 9,999,999 pulses per kWh

Pulse width for Digital
Output
Pulse frequency for Digital
Output
Leakage current

50% duty cycle
25 Hz max.

Isolation
Optical outputs
Pulse width (LED)
Pulse frequency
Meter constant

74

50 or 60 Hz ±10%
5A

Frequency
Ride-through time

Outputs

20 V L-N / 20 V L-L to 400 V L-N
/690 V L-L

5MΩ

Impedance

Burden

DC control
power

PM5500

128 samples per cycle

PMD/S/K70/0.5

IEC 62053-24 Reactive Energy
Active Energy
Reactive Energy

PM5300

0.03 micro Amps

1 micro Amps

5 kV rms

2.5 kV rms

200 ms
50 Hz. max.
from 1 to 9,999,999 pulses per k_h

2013

2.5 kHz. max

Basic multi-function metering

PM5000 Series

Functions and characteristics (cont.)

Electrical characteristics* (cont'd)
Status Inputs

PM5100

ON Voltage

PM5300

PM5500

18.5 to 38 V DC

30 V AC / 60 V DC max

OFF Voltage

0 to 4 V DC

Input Resistance
Maximum Frequency
Response Time
Opto Isolation
Whetting output

110 k Ω

100 k Ω

2 Hz (T ON min = T OFF min =
250 ms)
20 ms

25 Hz (T ON min = T OFF min =
20 ms)
10 ms

5 kV rms

2.5 kV rms

24 V DC/ 8mA max

Input Burden

2 mA @ 24 V AC/DC

Mechanical characteristics
Weight

380 g

IP degree of protection (IEC 60529)
Dimensions W x H x D [protrusion from cabinet]

430 g

450 g

IP52 front display, IP30 meter body
96 x 96 x 72mm (77mm for PM5500) (depth of meter from housing mounting flange) [13mm]

Mounting position
Panel thickness

Vertical
6 mm maximum

Operating
temperature

Meter

-25 °C to 70 °C

Display (Display functions to -25º with
reduced performance)

-25 °C to +70 °C

Environmental characteristics

Storage temp.

-40 °C to +85 °C

Humidity range

5 to 95 % RH at 50 °C (non-condensing)

Polution degree

2

Altitude

2000 m CAT III / 3000 m CAT II

3000 m max. CAT III

Electromagnetic compatibility
Harmonic current emissions
Flicker emissions

IEC 61000-3-2
IEC 61000-3-3

Electrostatic discharge

IEC 61000-4-2

Immunity to radiated fields

IEC 61000-4-3

Immunity to fast transients

IEC 61000-4-4

Immunity to surge

IEC 61000-4-5

Conducted immunity 150kHz to 80MHz

IEC 61000-4-6

Immunity to magnetic fields

IEC 61000-4-8

Immunity to voltage dips

IEC 61000-4-11

Radiated emissions

FCC part 15, EN 55022 Class B

Conducted emissions

FCC part 15, EN 55022 Class B

*Electrical Characteristics still under verification at time of printing of the catalogue, may be subject to change.

2013

75

Basic multi-function metering

PM5000 Series

Functions and characteristics (cont.)

Safety

PM5100

PM5300

Europe

PM5500

CE, as per IEC 61010-1 Ed. 3 and IEC 62052-11

U.S. and Canada

cULus as per UL61010-1 (3rd Edition)

Measurement category (Voltage and Current inputs)

CAT III up to 277 V L-N / 480 V L-L ; CAT II up to 400 V L-N / 690 V L-L

Dielectric

CAT III up to 400 V L-N / 690
V L-L

As per IEC/UL 61010-1 Ed. 3

Protective Class

II, Double insulated for user accessible parts

Communication
RS 485 port Modbus RTU, Modbus ASCII
(7 or 8 bit), JBUS

2-Wire, 9600,19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity Odd or Even, 2 stop bits if
None; (Optional in PM51x and PM53x)

Ethernet port: 10/100 Mbps; Modbus TCP/IP

1 Optional

Firmware and language file update

2 (for daisy chain only, one IP
address)

Meter firmware update via the communication ports

Isolation

2.5 kVrms, double insulated

Human machine interface
Display type

Monochrome Graphics LCD

Resolution

128 x 128

Backlight

White LED

Viewable area (W x H)

67 x 62.5 mm

Keypad

4-button

Indicator Heartbeat / Comm activity

Green LED

Energy pulse
output / Active
alarm indication
(configurable)

Optical, amber LED

Wavelength

590 to 635 nm

PE86288

Maximum pulse rate

Features and Options
Installation

2.5 kHz

PM5100
PM5100
PM5110

PM5310

PM5300
PM5320
PM5330

PM5340

PM5500
PM5560 PM5563

b

b

b

b

b

b

b

–

–

–

–

–

–

–

–

b

CI 0.5

CI 0.5

CI 0.5

CI 0.5

CI 0.5

CI 0.5

CI 0.2

CI 0.2

3-phase voltage, current, power, demand,
energy, frequency, power factor

b

b

b

b

b

b

b

b

Multi-tariff

–

–

4

4

4

4

8

8

Fast installation, panel mount with integrated
display
Fast installation, DIN rail mountable

Accuracy Display
Display
Backlit LCD, multilingual, bar graphs, 6 lines,
4 concurrent values

b

b

b

b

b

b

b

b

Power and energy metering

Power quality analysis
THD, thd, TDD
Harmonics, individual (odd) up to

b

b

b

b

b

b

b

b

15th

15th

31st

31st

31st

31st

63rd

63rd

1DO

1DO

2DI/2DO

2DI/2DO

0

0

2DI/2DO
2

4DI/2DO

0

2DI/2DO
2

4DI/2DO

0

0

0
52

I/Os and relays
I/Os
Relays

Alarms and control
Alarms

33

33

35

35

35

35

52

Set point response time, seconds

1

1

1

1

1

1

1

1

Single and multi-condition alarms

–

–

b

b

b

b

b

b

Boolean alarm logic

–

–

–

–

–

–

b

b

–
–

1

1

1
–

1

1

–

–
1

–

–

1

2**

2**

PM5331

PM5341

PM5561

Communications
Serial ports with modbus protocol
Ethernet port with Modbus TCP protocol

MID ready compliance,
EN50470-1/3, Annex B and Annex D
Class C

PM5111

** 2 Ethernet ports for daisy chain, one IP address.

76

2013

PM5000 Series

Basic multi-function metering

Dimensions and connection

PB111276

PM5000 Series meter flush mounting

PB111279

PM5000 Series meter dimensions

PM5500

PB111278

PB111277

PM5100 / PM5300

PM5500
PM5000 meter parts
A Menu selection buttons
B LED indicators
C Navigation or menu selections
D Maintenance and alarm
notification area

PM5500 meter parts
E Voltage inputs
F RS-485 comms
G Digital inputs
H Current inputs
I Digital outputs
J Ethernet ports
K Control power

PM5100 / PM5300 meter parts
E Relay output (PM5300 only)
F Voltage inputs
G Control power
H Current inputs
I Status inputs/digital outputs
J Communications port:
Ethernet (PM5300 only) or
RS-485)

Please see the Installation Guide for accurate and complete information on the installation of this product.

2013

77

Intermediate metering

PM800 series

Functions and characteristics

PE86134

The PowerLogic PM800 series meters offers many high-performance capabilities
needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit.
All models include an easy-to-read display that presents measurements for all three
phases and neutral at the same time, an RS-485 Modbus communication port, one
digital input, one KY-type digital output, total harmonic distortion (THD) metering,
and alarming on critical conditions. Four models offer an incremental choice of
custom logging and power quality analysis capabilities. Expand any model with
field-installable option modules that offer a choice of additional digital inputs and
outputs, analogue inputs and outputs, and Ethernet port.

Applications

b Panel instrumentation
b Sub-billing, cost allocation and energy management
b Remote monitoring of an electrical installation
b Power quality analysis
b Utility bill verification, utility contract optimization and load preservation.
Front view of PowerLogic PM800 series meter with
integrated display.

Characteristics
Easy to install
Mounts using two clips, with no tools required. Direct connect the voltage inputs, with
no need for potential transformers (PTs) up to 600 VAC.

PB101823-50

Easy to operate
Intuitive navigation with self-guided, language-selectable menus.
System status at a glance
Large, anti-glare display with back-light provides summary screens with multiple
values. Bar charts graphically represent system loading and I/O.
Custom alarming with time stamping
Over 50 alarm conditions, including over or under conditions, digital input changes,
phase unbalance and more. The models PM850 and PM870 offer boolean logic that
can be used to combine up to four alarms.

Rear view of PowerLogic PM800 series meter.

Power quality analysis
The PM800 series offers an incremental range of features for troubleshooting and
preventing power quality related problems. All models offer THD metering. The
PM810 with PM810LOG option and PM820 offer individual current and voltage
harmonics readings. The PM850 and PM870 offer waveform capture (PM870 is
configurable) and power quality compliance evaluation to the international EN50160
-ITI(CBEMA)/SEMI F-47 standards. The PM870 offers voltage and current
disturbance (sag/swell) detection.
Extensive on-board memory
All models offer billing (energy and demand), maintenance, alarm and customizable
data logs, all stored in non-volatile memory (PM810 requires PM810LOG option).

PE86229

ANSI 12.20 Class 0.2S and IEC 62053-22 Class 0.5S accuracy for active energy
Accurate energy measurement for sub-billing and cost allocation.
IEC61557-12 performance standard
Meets PMD/SD/K70/0.5 and PMD/SS/K70/0.5 requirements for combined
Performance Measuring and monitoring Devices (PMD).
Trend curves and short-term forecasting
The models PM850 and PM870 offer trend logging and forecasting of energy and
demand readings to help compare load characteristics and manage energy costs.

PowerLogic PM800 series meter display
screen showing bar graphs.

Expandable I/O capabilities
Use the on-board or optional digital inputs for pulse counting, status/position
monitoring, demand synchronisation or control (gating) of the conditional energy
metering. Use the on-board or optional digital outputs for equipment control or
interfacing, controllable by internal alarms or externally through digital input status.
Use the optional analogue inputs and outputs for equipment monitoring or
interfacing.
Metering of other utilities (WAGES)
All models offer five channels for demand metering of water, air, gas, electricity or
steam utilities (WAGES) through the pulse counting capabilities of the digital inputs.
Pulses from multiple inputs can be summed through a single channel.
Modular and upgradeable
All models offer easy-to-install option modules (memory, I/O and communications)
and downloadable firmware for enhanced meter capabilities.
Remote display
The optional remote display can be mounted as far as 10 m from the metering unit.
The adapter includes an additional 2- or 4-wire RS-485/RS-232 communication port.

78

2013

Intermediate metering

PM800 series

Functions and characteristics (cont.)

PB101814 -36

Part Numbers
Description

Meter without display
Use the base meter unit without display to comply with voltage limitations for local regulations
when door mounting is not possible, or when meter voltage exceeds regulations, or when local
display is not required. When the meter is used without a display, configuration of the
communications port is limited to the default (address 1, 9600 baud, parity even). Requires
software to read data.

PE86134

PowerLogic PM800 series meter without display.

PM810 meter unit only, no display,
basic instrumentation, THD, alarming, 80 kB logging
(with PM810LOG)
PM820 meter unit only, no display,
basic instrumentation, THD, alarming, 80 kB logging

PM810UMG

PM850 meter unit only, no display,
basic instrumentation, THD, alarming, 800 kB
logging, waveform capture

PM850UMG

PM870 meter unit only, no display,
basic instrumentation, THD, alarming, 800 kB
logging, configurable waveform capture and
disturbance detection.

PM870UMG

PM820UMG

Meter with integrated display
Use the meter with integrated display for panel mounting when door space is available and when
voltage usage is within the local regulation limits.

PB101822 -68

PowerLogic PM800 series meter with integrated display.

PM810 meter with integrated display,

PM810MG

PM820 meter with integrated display

PM820MG

PM850 meter with integrated display

PM850MG

PM870 meter with integrated display

PM870MG

Meter with remote display
Conveniently packaged kit consist of a base meter (810, 820, 850 or 870) with a remote display,
remote display adapter, and remote display cable 3 m (9.ft 10 inches).
PM810 meter with remote display

PM810RDMG

PM820 meter with remote display

PM820RDMG

PM850 meter with remote display

PM850RDMG

PM870 meter with remote display

PM870RDMG

PE86135

PowerLogic PM800 series meter with remote display.

Parts and accessories

PB101819 -32

Remote display adapter with display and cable.

Remote display adapter with remote display and PM8RDMG
a 3 m (9 ft 10 inch) cable
Use this combination of remote display, adapter, and
3 m cable to equip a base meter unit for use with a
remote display. In addition, the display can be carried
from meter to meter, enabling you to purchase one
display for multiple meters. Each base unit meter
must be equipped with a remote display adapter
(PM8RDA).
Remote display adapter alone
PM8RDA
When added to the front of the base unit (PM8xxU),
the adapter brings two additional communication
ports: one for the remote display and one 4-wire/2wire RS 485/RS 232.
Part number list continued on next page.

Remote display adaptor alone.

2013

79

Intermediate metering

PM800 series

Functions and characteristics (cont.)

DB119011

Part Numbers - continued

Description

Optional modules
Ethernet communication module provides a 10/100BaseTx UTP port,
an RS-485 Modbus serial master port, Ethernet-to-serial line gateway
functionality, and an embedded web server that is fully compliant with
Transparent Ready - Level 1 (TRe1) systems.

DB119013

DB119012

PowerLogic PM870 with ECC module (bottom view
showing connectors and configuration switches).

ECC module (side view
showing LED indicators).

The PM8ECC supports a private host PM8ECC MIB. Use of this MIB allows
the reading of Basic Metering Data, Configuration and Status of I/Os and
Configuration and Status of Alarms, plus SNMP Trap generation in response
to any PM8 on-board alarms.
2 relay outputs, 2 digital inputs

PM8M22

2 relay outputs, 6 digital inputs

PM8M26

2 relay outputs, 2 digital inputs, 2 analogue outputs,
2 analogue inputs

PM8M2222

PM810 optional logging module for on-board data recording, uses a
non-volatile, battery-backed internal clock

PM810LOG

RJ11 Extender kit to mount RJ11 jack in panel door
(for use with PM800, CM3000, and CM4000 series meters)

RJ11EXT

Cable for remote display adapter 1.25 m (4 ft)

CAB4

Cable for remote display adapter 3 m (9 ft 10 inch)

CAB12

Cable for remote display adapter 9.14 m (30 ft)

CAB30

PB1018216 -34

ECC module (front view)

PB101824 -50

PowerLogic PM8M26 module.

PowerLogic PM800 with PM8M22 and
PM8M26 modules.

80

PM8ECC

2013

Intermediate metering

PM800 series

Functions and characteristics (cont.)

Selection guide

PM810

PM820

PM850

PM870

Performance standard
ANSI 12.20 Class 0.2S

b

b
b

IEC 61557-12 PMD/SD/K70/0.5 and PMD/SS/K70/0.5 b

b
b

b
b

General

Use on LV and HV systems
b
b
b
b
Current and voltage accuracy
0.5 %/0.2% 0.5 %/0.2% 0.5 %/0.2% 0.2 %/0.2%
Active energy accuracy (5% to 200% of load) 0.2 %
0.2 %
0.2%
0.2%
Number of samples per cycle
128
128
128
128

Instantaneous rms values

Current, voltage, frequency
Active, reactive,apparent power Total & per phase

b
b

b
b

b
b

b
b

Power factor

b

b

b

b

Active, reactive, apparent energy

b

b

b

b

Configurable accumulation mode

b

b

b

b

Current

b
b

b
b

b
b

b
b

Predicted active, reactive, apparent power
Synchronisation of the measurement window
Demand calculation modeBlock, sliding, thermal

b
b
b

b
b
b

b
b
b

b
b
b

Hour counter

b

b

b

b

Energy values

Demand values

Active, reactive, apparent
power

Total & per phase

Present & max.
Present & max.

Other measurements

Power quality measurements
Harmonic distortion

Current & voltage

Individual harmonics

Current & voltage

b

b

63

63

-

-

b

b (2)
b
b

-

-

-

Min/max of instantaneous values
Data logs
Event logs

b
2 (1)
-

b
2
b

b
4
b

b
4
b

Trending / forecasting
GPS synchronisation
Alarms
Time stamping

-

b
b
b

b
b
b
b

b
b
b
b

b
b

b
b

b
b

b

b (1)
b
b (1)

Display and I/O

b
White backlit LCD display
b
Multilingual
Digital input (standard/optional)
1/12
Digital output (standard/optional)
1 KY/4 RY
Analogue inputs (standard/optional)
0/4
Analogue outputs (standard/optional)
0/4
Input metering capability (number of channels) 5

Communication

RS 485 port
Modbus protocol
RS 232/RS 485, 2- or 4-wire Modbus RTU/
ASCII (with addition of PM8RDA module)
Ethernet 10/100Base Tx UTP port and RS485
Modbus serial master port with PM8ECC

DB109269

b
31

Waveform capture
EN50160 - ITI(CBEMA)/SEMI F-47
Sag and swell detection

Data recording

PowerLogic PM800 series connectors.
1. Control power.
2. Voltage inputs.
3. Digital input/output.
4. RS 485 port.
5. Option module connector.
6. Current inputs.
7. Mounting clips.

b
31 (1)

2-wire
b
b
b

(4)

1/12
1 KY/4 RY
0/4
0/4
5

1/12
1 KY/4 RY
0/4
0/4
5

1/12
1 KY/4 RY
0/4
0/4
5

2-wire
b
b

2-wire
b
b

2-wire
b
b

b

b

b

Option modules selection guide

The PM800 can be fitted with 2 optional modules, unless otherwise indicated (3)

PM8ECC module

10/100BaseTx UTP port, RS-485 Modbus serial master port, Ethernet to serial line gateway,
embedded web server

Input/Output modules

PowerLogic PM800 series meter with I/O module.

PM8M22 PM8M26* PM8M2222

Relay outputs
2
2
2
Digital inputs
2
6
2
Analogue outputs 4-20 mA
2
Analogue inputs 0-5 Vdc or 4-20 mA
2
* Includes a 24 Vdc Power Supply that can be used to power the digital inputs
(1) With PM810LOG, battery-backed internal clock and 80 kB memory. (2) Configurable. (3) Series 800
Power Meters supports up to two option modules. When PM8M2222 & PM8ECC are mounted together
with control power>370 V AC temperature rating must be reduced to -25°C to 50°C. Same applies when
using two PM8M2222. (4) PM850 does not include sag or swell detection.

2013

81

Intermediate metering

PM800 series

Functions and characteristics (cont.)

Electrical characteristics

63rd harmonic, 128 samples per cycle
Type of measurement
Measurement accuracy standard IEC 61557-12 compliant
Current
Voltage
Power Factor
Active Power

0.5% from 0.5 A to 10 A
0.2% 10 V - 277 V
+/- 0.002 from 0.500 leading to 0.500 lagging
0.2%

Frequency

+/- 0.01 Hz at 45 to 67 Hz
+/- 0.01 Hz at 350 to 450 Hz
IEC 62053-22 Class 0.5S and
ANSI C12.20 Class 0.2S

Active Energy
Reactive Energy
Data update

IEC 62053-23 Class 2

1s
0 to 600 V AC (direct L-L)
0 to 347 V AC (direct L-N)
up to 3.2 MV AC (with external VT)
Metering over-range
1.5 Un
Impedance
5 MW
Frequency measurement range 45 to 67 Hz and 350 to 450 Hz

Input-voltage
Measured voltage
characteristics

Input-current
CT ratings
characteristics

Control Power

Primary

Inputs/Outputs (2)
Standard
1 digital KY pulse output
(meter unit)
1 digital input
PM8M22
option

2 relay outputs (1)
2 digital inputs

PM8M26
option

2 relay outputs (1)

PM8M2222
option

Switching
frequency
(digital I/O)

6 digital inputs
24 V internal supply

20 - 34 V DC, 10 mA max. (feeds 6 digital inputs)

6 to 240 V AC, 6 to 30 V DC
2 A rms, 5 A max. for 10 seconds per hour
2 digital inputs
20 to 150 V AC/DC, 2 mA max.
2 analogue outputs
4 to 20 mA dc into 600 ohms maximum
2 analogue inputs
Adjustable from 0 to 5 V DC or 4-20 mA
Standard
Input/output 25 Hz, 50 % duty cycle (20 ms ON/OFF)
PM8M22
Input/output 1 Hz, 50 % duty cycle (500 ms ON/OFF)
PM8M26 and
Input
25 Hz, 50 % duty cycle (20 ms ON/OFF)
PM8M2222
Output
1 Hz, 50 % duty cycle (500 ms ON/OFF)
2 relay outputs (1)

Weight (meter with integrated display)
IP degree of protection (IEC 60529)
Without options	
With 1 option

Environmental conditions
Operating
temperature

6 to 220 V AC ± 10% or 3 to 250 V DC ± 10%,
100 mA max. at 25 °C, 1350 V rms isolation
24 to 125 V AC/DC ±10 %, < 5 mA maximum
burden, 1350 Vrms isolation
6 to 240 V AC or 6 to 30 V DC
2 A rms, 5 A max. for 10 seconds per hour
19 to 30 V DC, 5 mA max. at 24 V DC
6 to 240 V AC, 6 to 30 V DC
2 A rms, 5 A max. for 10 seconds per hour
20 to 150 V AC/DC, 2 mA max.

Mechanical characteristics

Dimensions

Adjustable from 5 A to 32767 A

Secondary 1 A or 5 A
Measurement input range
5 mA to 10 A AC
15 A continuous
Permissible overload
50 A for 10 seconds per hour
500 A for 1 second per hour
Impedance
< 0.1 W
Load
< 0.15 VA
AC
115 to 415 ±10 % V AC, 15 VA with options at
45 to 67 Hz or 350 to 450 Hz
DC
125 to 250 ±20 % V DC, 10 W with options
Ride-through time
45 ms at 120 V AC or 125 V DC

Meter
Display
Meter + display

0.6 kg
IP52 integrated display. Type 12 compliant
remote display (with gasket). IP30 meter body
96 x 96 x 70 mm (mounting surface)
96 x 96 x 90 mm (mounting surface)
-25 °C to +70 °C (2)

-10 °C to +50 °C
-40 °C to +85 °C
5 to 95 % RH at 40 °C (non-condensing)
2
III, for distribution systems up to 347 V L-N /
600 V AC L-L
Dielectric withstand
As per EN 61010, UL508
Altitude
3000 m max.
(1) Mechanical endurance: 15 million operations, Electrical endurance:25000 commutations at
2 A / 250 V AC (2) Series 800 Power Meters supports up to two option modules. When
PM82222 & PM8ECC are mounted together with control power >370 V AC temperature rating
must be reduced to -25°C to 50°C. Same is true when using two PM8M2222.
Storage temp.
Humidity rating
Pollution degree
Installation category

82

2013

Intermediate metering

PM800 series

Functions and characteristics (cont.)

Electromagnetic compatibility
Electrostatic discharge

Level III (IEC 61000-4-2)

Immunity to radiated fields

Level III (IEC 61000-4-3)

Immunity to fast transients

Level III (IEC 61000-4-4)

Immunity to impulse waves

Level III (IEC 61000-4-5)

Conducted immunity

Level III (IEC 61000-4-6)

Immunity to magnetic fields

Level III (IEC 61000-4-8)

Immunity to voltage dips

Level III (IEC 61000-4-11)

Conducted and radiated
emissions
Harmonics emissions

e industrial environment/FCC part 15 class A EN 55011

Flicker emissions

IEC 61000-3-3

Surge immunity

IEC 61000-4-12

IEC 61000-3-2

Surge withstand capability (SWC) ANSI C37.90.1.2002

Safety
Europe

e, as per IEC 61010-1 i (1)

U.S. and Canada

cULus (UL508 and CAN/CSA C22.2 No. 14-M95, Industrial
Control Equipment)

Onboard communications
RS 485 port

2-wire, up to 38400 baud, Modbus

Model-dependent characteristics
Data Logs

Min./max.

One event log
Trend curves
(PM850 and PM870 only)

Hour counter
Energy per shift
Forecasting
(PM850 and PM870 only)
PM850 waveform capture
PM870 enhanced waveform
capture
Alarms

Memory available for logging
and waveform capture (2)
Firmware update (all models)
Bar graphs (all models)

PM810 with PM810LOG, PM820, PM850 and PM870:
- 1 billing log
- 1 customisable log
PM850 and PM870 only: 2 additional custom logs
Worst min. and max. with phase indication for Voltages,
Currents, Voltage unbalance, and THD. Min. and max. values
for power factor (True and Displacement), power (P, Q, S) and
frequency
Time stamping to 1 second
Four trend curves: 1 minute, 1 hour, 1 day and 1 month. Min./
max./avg. values recorded for eight parameters:
- every second for one minute for the 1-minute curve
- every minute for one hour for the 1-hour curve
- every hour for one day for the 1-day curve
- every day for one month for the 1-month curve
Load running time in days, hours and minutes
Up to three user-defined intervals per day
Available for all models (the PM810 requires the PM810LOG
module)
Forecasting of the values for the trended parameters for the
next four hours and next four days
Triggered manually or by alarm, 3-cycle, 128 samples/cycle on
6 user configurable channels
From 185 cycles on 1 channel at 16 samples per cycle up to
3 cycles on 6 channels at 128 samples per cycle
Adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of alarm
Historical and active alarm screens with time stamping
Response time: 1 second
Boolean combination of four alarms is possible using
the operators NAND, AND, OR, NOR and XOR on PM850 and
PM870
Digital alarms: status change of digital inputs
80 kbytes in PM810 with PM810LOG and PM820
800 kbytes in PM850 and PM870
Update via the communication ports
File download available free from www.powerlogic.com
Graphical representation of system performance

Display characteristics
Languages

English, French, Spanish, German, Russian, Turkish and
Portuguese.

Display screen

Back-lit white LCD (6 lines total, 4 concurrent values)

Dimensions

Display screen viewable area

73 x 69 mm

Integrated display Overall

96 x 96 mm

Depth meter + display 69.4 mm + 17.8 mm
Remote display
Weight

2013

Overall

96 x 96 x 40 mm

Meter with remote display adapter

0.81 kg

Remote display

0.23 kg

83

Power Meter Series 800

Intermediate metering

Dimensions and connection

Power meter with integrated display

DB111766

DB111767

DB111765

Dimensions

DB111768

Front-panel mounting (meter with integrated display)

84

DB111770

DB111769

Spacing between units

2013

Power Meter Series 800

Intermediate metering

Dimensions and connection (cont.)

Remote display door mounting

DB111792

Flush mounting

DB111793

Surface mount

DB111794

Mounting in a Ø102 cutout (replace analogue device: ammeter, voltmeter, etc.)

2013

85

Intermediate metering

ION7300 Series

PE86151a

Functions and characteristics

Used in enterprise energy management applications such as feeder monitoring and
sub-metering, ION7300 Series meters offer unmatched value, functionality, and
ease of use. ION7300 Series meters interface to PowerLogic StrxureWare software
or other automation systems to give all users fast information sharing and analysis.
ION7300 Series meters are an ideal replacement for analogue meters, with a
multitude of power and energy measurements, analogue and digital I/O,
communication ports, and industry-standard protocols. The ION7330 meter has
on-board data storage, emails of logged data, and an optional modem. The ION7350
meter is further augmented by more sophisticated power quality analysis, alarms and
a call-back-on-alarm feature.

Applications
PowerLogic™ ION 7300 Series meter.

Power monitoring and control operations.
Power quality analysis.
Cost allocation and billing.
Demand and power factor control.
Load studies and circuit optimisation.
Equipment monitoring and control.
Preventive maintenance.

Main characteristics
Accurate metering
Ensure metering accuracy with compliance to IEC 60687 class 0,5S standard.
Multiple communications options: Ethernet - Serial - Modem
Gateway functionality simplifies communications architecture and reduces leased
line or connection costs. Concurrent, independent ports communicate with a variety
of protocols such as ION, DNP 3.0, Modbus RTU, and Modbus TCP.
Easy to read display
An easy-to-read front panel with a back-lit LCD screen supports local data display
and basic setup.
Set automatic alarms
Use configurable event priorities, logical operators, and setpoints to define alarm
conditions and set alarms.
Integrate with software
Easily integrate ION7300 Series meters with an energy management or SCADA
system to provide remote display at a PC workstation, as well as remote
configuration and manual control capabilities.
Notification of alarms via email
Alarm notifications sent via email to any workstation, cell phone, pager, or PDA.
Server for custom HTML pages
An on-board Web server combined with an Ethernet port offers quick and easy
access to real-time energy and basic power quality information without special
software.
Monitor dips and swells (ION7350)
Detect dips and swells on any voltage channel.
Interoperability expands existing networks
The ION7330/ION7350 concurrently communicates via multiple protocols, allowing
you to extend an existing Modbus, DNP, or Enterprise network.
Memory
Non-volatile memory (300kB) ensures that valuable information can be preserved
between intervals.

Part numbers

ION7300 series
ION7330
ION7350
Refer to the part number section for further explanations.

86

2013

M7330
M7350

ION7300 Series

Intermediate metering

Functions and characteristics (cont.)

2

3

4

5

6

7

8

9

10 11

PE86057

1

Selection guide

ION7330 ION7350

General

Use on LV and HV systems
Current and voltage accuracy
Power accuracy
Real (kW)
Apparent (kVA)
Reactive (kvar)
Energy accuracy
Real (kWh)
Apparent (kVAh)
Reactive (kvarh)
Number of samples per cycle

Instantaneous rms values
Current, voltage, frequency
Active, reactive, apparent power
Power factor

Total and per phase
Total and per phase

Energy values
PowerLogic ION7330/ION7350

Active, reactive, apparent energy
Settable accumulation modes

Demand values

1	 Chassis Ground
2	 Analogue Inputs
3	 Internal Modem Port
4	 Voltage Inputs
5	 Digital Outputs
6	 Current Inputs
7	 Digital Inputs
8	 RS-485 Bus
9	 Power Supply
10	Ethernet Port
11	IR Port

Current
Present and max.
Active, reactive, apparent power Present and max.
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Setting of calculation mode
Block, sliding

Power quality measurements
Harmonic distortion
Current, voltage
Individual harmonics
Waveform capture
Detection of voltage dips and swells

Data recording
Min/max of instantaneous values
Historical logs
max. # of channels
Waveform logs
max. # of channels
Trending / forecasting
Alarms
Time stamp resolution (s)
300 Kbyte memory

Display and I/O
Display
Wiring self-test
Analogue inputs / analogue outputs
Digital status inputs/counter
Digital relay outputs

b

b

0.25% + 0.05 % full scale
0.5% reading
0.5% + 0.1%
1.5% reading
0.5% reading
1.0% reading
1.5% reading
32
64
b
b
b

b
b
b

b
b

b
b

b
b
b
b
b

b
b
b
b
b

b

b

15th
-

31st
b
b

b

b

32
b

96
48
b
b

0.001
b

0.001
b

b
b

b
b

4/4
4
4

4/4
4
4

2
b

2
b

1
b

1
b

1
b

1
b

1
b
b

1
b
b

Communication
Disturbance waveform capture and power quality report.

RS-485 port
Modbus protocol
Ethernet (Modbus/TCP/IP protocols)
Ethernet gateway (EtherGate)
Internal modem
Modem gateway (ModemGate)
Infrared optical port
DNP 3.0 via serial, modem, IR ports
HTML page web server (WebMeter)

2013

87

Intermediate metering

ION7300 Series

Functions and characteristics (cont.)

Electrical characteristics

PE86236

Type of measurement
Measurement
accuracy

PowerLogic ION7300 Series remote terminal display.

Current and voltage

True rms up to the 15th harmonic (31st for ION7350)
32 samples/cycle (64 for ION7350)
0.25% + 0.05%

Power

Real: 0.5% reading
Apparent: 0.5% + 0.1%
Reactive (>5% FS): 1.5% reading
+ 0.01 Hz
Frequency
Power factor (at Unity PF) + 1.5% reading
kWh: 0.5% reading
Energy(1)
kVAh: 1.0% reading
kvarh: 1.5% reading
Data update rate
1 second
Input-voltage
Measured voltage
50 - 347 VAC L-N 3-phase (87-600 L-L)
characteristics
50 - 300 VAC L-N single phase (100 - 600 L-L)
Metering over-range
25%
Overload withstand
1500 VAC continuous
3250 VAC for 1 second non-recurring
Impedance
>2 M Ohms/phase (phase - Vref)
Frequency range
40 - 70 Hz
Input-current
CT ratings
5 A nominal / 10 A full scale
characteristics Measurement range
20 mA - 10 A rms (+20%, 300 V rms to ground)
Overload withstand
20 A continuous
500 A for 1 second non-recurring
Burden
Worst case (at 10 A): 0.0625 VA
Impedance
> 2 M Ohms/phase (phase-Vref)
Power supply AC
95 - 240 VAC (+ 10%), (47 - 440 Hz)
120 - 310 VDC (+ 10%)
DC
0.2 A worst case loading (12 W) at 100 VAC at 25°C
20 to 60 VDC (+ 10%)
P24 option
Input/outputs
4 Digital status inputs
Self-excited (internal 30 VDC supply); Min pulse width:
(7330/7350)
25 msec; Max 40 transitions/sec
4 digital outputs
4 optional analogue
inputs

4 optional analogue
outputs

Form A Solid State; Max forward current: 80 mA
Max voltage: 30 V
0-20 mA (scalable to 4-20 mA) option
Input impedence: 24.3 Ohms; Accuracy: < + 0.3% of
full-scale; Update rate: 1 second; Max common mode
voltage: 30 V; Sample rate: 16 samples/second
0-1 mA option same as above except:
Input impedence: 475 Ohms
0-20 mA (scalable to 4-20 mA) option
Max load drive capability: 500 Ohms; Accuracy: +
0.3% of full-scale; Max common mode voltage: 30 V
0-1 mA option same as above except:
Max load drive capability: 10 kOhms

Mechanical characteristics
Weight
IP degree of protection
Dimensions

Standard model
TRAN model

1.8 kg
Integrated display: front IP 50; back IP 40
Transducer unit (no display): IP 40
96 x 96 x 162.2 mm
60 x 100 x 164.5 mm

Environmental conditions
Operating temperature
Storage temperature
Humidity rating
Altitude
Installation category
Pollution degree
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to electromagnetic HF fields
Immunity to fast transients
Conducted and radiated emissions

-20 to +60° C ambient air
-30 to +85°C
5% to 95% non-condensing
Less than 2000 m above sea level
III, for distribution systems
2
As per IEC 61010, UL3111
EN 60687:1993
EN 60687:1993
IEC 61000-4-4
EN 55014-1:1993

Safety
Europe
IEC 1010-1
USA and Canada
UL 3111 and CSA C22.2 No. 1010-1
(1) Accuracy complies with IEC 687 class 0.5S and ANSI 12.20 class 0.5 at 25ºC.

88

2013

Intermediate metering

ION7300 Series

Functions and characteristics (cont.)

Communication
PE86004

RS-485 ports
Ethernet port (Modbus TCP
protocol)
Infrared optical port
Internal modem

Optically isolated
Up to 19,200 bauds
Protocols: ION, DNP 3.0, Modbus RTU, GPS
Up to 10 Mbps
With EtherGate
Optional 10Base-T
Front panel ANSI Type 2
Up to 19,200 bauds
Protocols: ION, Modbus RTU, DNP 3.0
From 300 to 33,600 bauds
ModemGate
Call-back feature(1)

Firmware characteristics
Data logs

Example WebMeter page showing realtime values.

Scheduled or event driven
7330: Maximum of 2 data logs, 32 parameters
7350: Maximum of 6 data logs, 96 parameters

Harmonic distortion

Individual and total up to the 15th harmonic (31st for 7350)

Sag/swell detection (1)

Detects dips and swells on any voltage channel

Instantaneous

True rms, per phase, and total for:
-	 Voltage and current
-	 Active (kW), reactive (kvar), and apparent (kVA) power
-	 Power factor and frequency
-	 Voltage and current unbalance
Perform on any parameter, over any time interval
Min and max values for all basic power parameters:
-	 Voltage per phase
-	 Current per phase
-	 Active (kW), reactive (kvar), apparent (kVA) power
-	 Power factor & frequency
-	 Rolling block demand for kW, kvar, kVA
Simultaneous capture of events on all channels. up to 48
cycles each, 64 samples/cycle. Maximum of 6,900 cycles
for contiguous waveform capture
Single- and multi-condition alarms, call-out on alarms,
define alarms conditions with configurable event priorities
300 kB standard

Min/max logging

Waveform captures
Alarms
Memory

Display characteristics
Integrated display
Languages
(1) Available on ION7350 only.

2013

4-parameter to single parameter large character displays,
back-lit LCD with adjustible contrast
English

89

Intermediate metering

ION7300 Series

Functions and characteristics (cont.)

Part numbers

6

Code Description
M7350 ION7350: Advanced power meter with basic sag/swell
detection, waveform recording, harmonics (up to the 31st),
high-speed data logging and automatic modem dial-out,
multi-port communications, 4 digital inputs and 4 digital
outputs.
M7330 ION7330: Advanced power meter with over 200 highaccuracy, 3-phase measurements, data logging, multiport
communications, 4 digital inputs and 4 outputs
Form factor
A0
Integrated display, with front optical port
R0
Transducer with RMD (remote display), with front optical port.
DOES NOT support Analogue Input and/or Analogue Output
options. Not available with Security options RMICAN or
RMICAN-SEAL.
R1
Same as R0, but with DIN rail mounts on the transducer. DOES
NOT support Analogue Input and/or Analogue Output options.
T0
Transducer (no display). Note you cannot use an RMD on this
meter if you order the Analogue Input and/or Analogue Output
options. Not available with Security options RMICAN or
RMICAN-SEAL.
T1
Transducer (no display) with DIN rail mount. Note you cannot
use an RMD on this meter if you order the Analogue Input and/
or Analogue Output options. Not available with Security
options RMICAN or RMICAN-SEAL.
Current inputs
B
5 Amp nominal, 10 Amp full scale current input
Voltage inputs
0
Autoranging (50 to 347 VAC +25%)
Power supply
B
P240 power supply (95-240 VAC/47-4f40 Hz/120-310 VDC)
C
P24 power supply (20 to 65 VDC)
System frequency 0
Autoranging (50 and 60 Hz)

7

Communications

PE86059

1

Example and explanation of product part number.
2

3
4
5

8

9

Item
Model

Inputs/Outputs

Security

10 Special order

Z0

No communications.

A0

Two RS-485 ports

C1

One RS-485 EtherGate port, one RS-485 ModemGate port,
10Base-T Ethernet (RJ45), 33.6k universal internal modem.
DOES NOT support Analogue Input and/or Analogue Output
options.

M1

One 33.6k universal internal modem (RJ11) port, one RS-485
port, one RS-485 ModemGate port.

E0

One RS-485 port, one 10Base-T Ethernet (RJ45)

A

No analogue inputs/outputs. You must choose this option if
ordering Display-only or RMD remote display options (Form
Factor types “D” or “R”), or Ethernet option (Communications
options “E0”).

M

Four 0 to 1 mA analogue inputs & four 0 to 1 mA analogue
outputs. NOT AVAILABLE with RMD or Ethernet options

N

Four 0 to 20 mA analogue inputs & four 0 to 20 mA analogue
outputs. NOT AVAILABLE with RMD or Ethernet options

0

Password protected, no hardware lock

2

Password protected with hardware lock enabled

3

(ION7330 model only) RMICAN Measurement Canada
approved

4

(ION7330 model only) RMICAN-SEAL Measurement Canada
approved, factory sealed(1)

6

Password protected with security lock enabled, terminal cover
and UK OFGEM labels

A
B

None
Pre-set to MODBUS (available for Form Factor T0, T1, T2 and
T3 only). Not available with Security options RMICAN or
RMICAN-SEAL.

C

Tropicalisation treatment applied

D

Tropicalisation treatment applied and pre-set to MODBUS
(available for Form Factor T0, T1, T2 and T3 only). Not
available with Security options RMICAN or RMICAN-SEAL.

(1)
A completed ION7300 series RMICAN-SEAL checklist must accompany each RMICANSEAL meter order.

90

2013

Intermediate metering

ION7300 Series

Functions and characteristics (cont.)

Part numbers (cont’d)
Transducer unit
ION7330 TRAN
ION7350 TRAN

Communications
ION7330

ION7350

No display
With DIN rail mount
No display
With DIN rail mount

T0
T1
T0
T1

Two RS-485 ports
One RS-485 EtherGate port, one RS-485
ModemGate port, 10Base-T Ethernet (RJ45),
33.6k universal internal modem1
One 10Base-T Ethernet (RJ45) port, one
RS-485 port, one RS485 EtherGate port1
One 33.6k universal internal modem (RJ11)
port, one RS-485 port, one RS-485 ModemGate
port
Two RS-485 ports
One RS-485 EtherGate port, one RS-485
ModemGate port, 10Base-T Ethernet (RJ45),
33.6k universal internal modem (RJ11)1
One 10Base-T Ethernet (RJ45) port, one
RS-485 port, one RS-485 EtherGate port1
One 33.6k universal internal modem (RJ11)
port, one RS-485 port, one RS-485 ModemGate
port

A0
C1
E0
M1
A0
C1
E0
M1

Remote modular display
Remote Modular Display with 6 foot DB25 cable

RMD-7330

Remote Modular Display with 6 foot DB25 cable

RMD-7350

Terminal strip cover
Terminal strip cover

TERMCVR-73XX

DB9 optical probe
Terminal strip cover.

Optical probe (DB-9) for use with ION7300 Series meters

OPTICALPROBE

Water resistant gasket
Water resistant gasket

GSKT

(1) Does NOT support Analogue Input and/or Analogue Output options.

2013

91

ION7300 Series

Intermediate metering

0

Dimensions and connection

PE86064

PE86063

ION7300 Series dimensions

86

96

162

96

PE86066

PE86065

ION7300 Series TRAN dimensions

60

86

6

100

164

PE86067

PE86063

ION7300 Series RMD dimensions

86

96

37

96

PE86068

Ethernet port location (if equipped)
17

73

14

57

Internal modem port location (if equipped)
PE86069

14

13

31

34

92

2013

ION7300 Series

Intermediate metering

0

Dimensions and connection (cont.)

PE86070

Front panel mounting

2013

93

Advanced metering

ION7550 / ION7650

Functions and characteristics

Used at key distribution points and sensitive loads, PowerLogic™ ION7550 and
ION7650 meters offer unmatched functionality including advanced power quality
analysis coupled with revenue accuracy, multiple communications options, web
compatibility, and control capabilities. Customise metering or analysis functions at your
work station, without hard wiring. Just link drag-and-drop icons or select default
settings. Integrate the meters with StruxureWare Power Monitoring software or share
data with SCADA systems via multiple communication channels and protocols.

Applications

Reduce energy costs.
Increase equipment utilisation.
Comply with environmental and regulatory requirements.
Improve power quality and reliability.
Improve customer satisfaction and retention.
Monitor and control equipment.
Integrated utility metering.
Allocate or sub-bill energy costs to departments, processes or tenants.

Main characteristics
Anticipate, diagnose and verify to increase efficiency
Reveal energy inefficiencies or waste and optimise equipment operation to increase
efficiency. Isolate reliability risks, diagnose power-related equipment issues and
verify reliable operation.
Summarise power quality, set targets, measure and verify results
Consolidate all the power quality characteristics into a single trendable index.
Benchmark power quality and reliability and compare against standards, or compare
facilities or processes.
Easy to use, multilingual, IEC/IEEE configureable display
Bright LCD display with adjustable contrast. Screen-based menu system to
configure meter settings including IEC or IEEE notations. Multilingual support for
English, French, Spanish and Russian. 12/24 hour clock support in multiple formats.
Modbus Master functionality
Read information from downstream Modbus devices and view it via the front panel or
store in memory until you upload to the system level.
IEC 61850 protocol
Increase interoperability and decrease engineering time using standard protocol.
Gateway functionality
Access through the meter’s Ethernet port (EtherGate) or telephone network
(ModemGate) to Modbus communicating devices connected to meter serial ports.
Detect and capture transients as short as 20µs at 50Hz (17µs at 60 Hz)
Identify problems due to short disturbances, e.g. switching of capacitors, etc.
Power quality compliance monitoring
Monitor compliance with international quality-of-supply standards (IEC 61000-4-30
class A ed. 2(1), EN50160(1), IEC 61000-4-7(1), IEC 61000-4-15(1), IEEE 519, IEEE 1159,
and CBEMA/ITIC). Evaluate flicker based on IEC 61000-4-15(1) and IEEE 1453(1).
Detect waveshape changes
Detection of phase switching phenomena (for example during the transfer of a
high-speed static switch) not detected by classical threshold-based alarms.
Record ultra-fast electrical parameters every 100 ms or every cycle
Preventive maintenance: acquisition of a motor startup curve, etc.
Trend curves and short-term forecasting
Rapid trending and forecasting of upcoming values for better decision making.
Disturbance direction detection
Determine disturbance location and direction relative to the meter. Results captured
in the event log, along with a timestamp and certainty level.
Alarm setpoint learning
The meter analyses the circuit and recommends alarm setpoints to minimise
nuisance or missed alarms.
Notify alarms via email
High-priority alarms sent directly to the user’s PC. Instant notification of power quality
events by email.(1) ION7650 only

Part numbers

ION7550 / ION7650
ION7550
ION7650
SE remote display
SE remote display w/power supply

M7550
M7650
M765RD
M765RDPS

(1) ION7650 only

94

2013

ION7550 / ION7650

Advanced metering

Functions and characteristics (cont.)

PE86288

1

1

2

3

Selection guide

ION7550 ION7650

General

Use on LV and HV systems
Current accuracy (1A to 5A)
Voltage accuracy (57V to 288V)
Energy accuracy
Nbr of samples/cycle or sample frequency

4

Instantaneous rms values
Current, voltage, frequency
Active, reactive, apparent power
Total and per phase
Power factor
Total and per phase
Current measurement range (autoranging)

5

Energy values

6
7

8

9

PowerLogic™ ION7550 / ION7650 rear view.

Active, reactive, apparent energy
Settable accumulation modes

Demand values
Current
Present and max. values
Active, reactive, apparent power
Present and max. values
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Setting of calculation mode
Block, sliding

Power quality measurements
1	
2	
3	
4	
5	
6	
7	
8	
9	

Current/voltage inputs
Digital inputs
Analogue inputs
Analogue outputs
Communications card
Power supply
Form C digital outputs
Digital inputs
Form A digital outputs

b
0.1 % reading
0.1 % reading
0.2 %
1024

b
b
b

b
b
b

0.01 - 20A

0.01 - 20A

b
b

b
b

b
b
b
b
b

b
b
b
b
b

b

b

63
127
b
b

63
511
b
b

-

20 µs(1)

b
b

b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

10

10

b
b

b
b

1
20
12

1
20
12

RS 485 port
RS 485 / RS 232 port
Optical port
Modbus protocol
IEC 61850 protocol

1
1
1
b
b

1
1
1
b
b

Ethernet port (Modbus/TCP/IP protocol, IEC 61850 (2))
Ethernet gateway (EtherGate)
Alarms (optional automatic alarm setting
Alarm notification via email
HTML web page server (WebMeter)
Internal modem
Modem gateway (ModemGate)
DNP 3.0 through serial, modem, and I/R ports
(1) For 50 Hz line frequency; 17µs for 60 Hz line frequency.

1
1
b
b
b

1
1
b
b
b

1
b
b

1
b
b

Harmonic distortion
Individual harmonics

Current and voltage
Via front panel
Via ION Enterprise

Waveform capture
Detection of voltage swells and sags
Detection and capture of transients
Flicker
Fast acquisition of 100 ms or 20 ms data
EN50160 compliance checking
Programmable (logic and math functions)

Data recording
Min/max of instantaneous values
Data logs
Event logs
Trending/forecasting
SER (Sequence of event recording)
Time stamping
GPS synchronisation (1 ms)
Memory (in Mbytes)

Display and I/O
Front panel display
Wiring self-test
Pulse output
Digital or analogue inputs(max)
Digital or analogue outputs (max, including pulse output)

PE86002

b
0.1 % reading
0.1 % reading
0.2 %
256

Communication

Disturbance waveform capture and power quality report

2013

95

Advanced metering

ION7550 / ION7650

Functions and characteristics (cont.)

PE86126

Electrical characteristics

PowerLogic ION7650

Type of measurement
Measurement
Current and voltage
accuracy
Power
Frequency
Power factor
Energy:
Data update rate
Input-voltage
Measurement range
characteristics
Impedance
Frequency measurement
range
Input-current
Rated nominal current
characteristics
Measurement range
Permissible overload
Impedance
Burden
Power supply

AC
DC
DC low voltage (optional)
Ride-through time
Burden

Input/outputs(1)

Standard
Optional

True rms to 1024 samples per cycle (ION7650)
±0.01% of reading + ±0.025% of full scale
±0.075% of reading + ±0.025% of full scale
±0.005Hz
±0.002 from 0.5 leading to 0.5 lagging
IEC62053-22 0,2S, 1A and 5A
1/2 cycle or 1 second
Autoranging 57V through 347V LN / 600V LL
5 MW/phase (phase - Vref)
42 to 69Hz
1A, 2A, 5A, 10A
0.005 - 20 A autoranging (standard range)
0.001 - 10 A autoranging (optional range)
500 A rms for 1 s, non-recurring (5A)
50 A rms for 1s, non-recurring (1A)
0.002 W per phase (5A)
0.015 W per phase (1A)
0.05 VA per phase (5 A)
0.015 VA per phase (1 A)
85-240 V AC ±10% (47-63 Hz)
110-300 V DC ±10%
20-60 V DC ±10%
100 ms (6 cycles at 60 Hz) min.
Standard: typical 20 VA, max 45 VA
Low voltage DC: typical 15 VA, max 20 VA
8 digital inputs (120 V DC)
3 relay outputs (250 V AC / 30 V DC)
4 digital outputs (solid state)
8 additional digital inputs
4 analogue outputs, and/or 4 analogue inputs

Mechanical characteristics
Weight
IP degree of protection (IEC 60529)
Dimensions

Standard model
TRAN model

1.9 kg
Integrated display, front: IP 50; back: IP 30
Transducer unit (no display): IP 30
192 x 192 x 159 mm
235.5 x 216.3 x 133.1 mm

Environmental conditions
Operating
temperature

Standard power supply
Low voltage DC supply
Display operating range
Display, TRAN

Storage
temperature
Humidity rating
Installation category
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to surges
Conducted and radiated emissions

-20 to +70 ºC
-20 to +50 ºC
-20 to +60 ºC
-40 to +85 ºC
5 to 95% non-condensing
III (2000m above sea level)
As per EN 61010-1, IEC 62051-22A(2)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
CISPR 22

Safety
Europe

IEC 61010-1

Communication
RS 232/485 port (1)
RS 485 port (1)
Infrared port(1)
Ethernet port
Fibre-optic Ethernet link

Up to 115,200 bauds (57,600 bauds for RS 485),
ION, DNP 3.0, Modbus, GPS, EtherGate,
ModemGate, Modbus Master
Up to 57,600 bauds, ION, DNP 3.0, Modbus,
GPS, EtherGate, ModemGate, Modbus Master
ANSI type 2, up to 19,200 bauds, ION, Modbus,
DNP 3.0
10Base-T/100Base-TX, RJ45 connector, 100 m link
100 Base FX, SC duplex connector, 1300 nm,
FO multimode with gradient index 62.5/125 µm
or 50/125 µm, 2000 m link

(1) Consult the ION7550 / ION7650 installation guide for complete specifications.
(2) IEC 62051-22B with serial ports only.

96

2013

Advanced metering

ION7550 / ION7650

Functions and characteristics (cont.)

PE86004

Communication (cont.)
Protocol

ION, Modbus, TCP/IP, DNP 3.0, Telnet, IEC 61850(2)

EtherGate

Communicates directly with up to 62 slave devices via
available serial ports
Communicates directly with up to 31 slave devices
10Base-T/100Base-TX, RJ45 connector, 100 m link
5 customisable pages, new page creation capabilities,
HTML/XML compatible

ModemGate
Ethernet port
WebMeter

Firmware characteristics
High-speed data recording

Harmonic distortion
Sag/swell detection

Disturbance direction detection

Instantaneous

Load profiling

Trend curves
Waveform captures

PE86005

Alarms

Advanced security
Transformer correction
Memory
Firmware update

Down to 5ms interval burst recording, stores detailed
characteristics of disturbances or outages. Trigger
recording by a user-defined setpoint, or from external
equipment.
Up to 63rd harmonic (511th for ION7650 via ION Enterprise
software) for all voltage and current inputs
Analyse severity/potential impact of sags and swells:
-	 magnitude and duration data suitable for plotting on
voltage tolerance curves
-	 per phase triggers for waveform recording, control
Determine the location of a disturbance more quickly and
accurately by determining the direction of the disturbance
relative to the meter. Analysis results are captured in the
event log, along with a timestamp and confidence level
indicating level of certainty.
High accuracy (1s) or high-speed (1/2 cycle)
measurements, including true rms per phase / total for:
-	 voltage and current
-	 active power (kW) and reactive power (kvar)
-	 apparent power (kVA)
-	 power factor and frequency
-	 voltage and current unbalance
-	 phase reversal
Channel assignments (800 channels via 50 data
recorders) configurable for any measurable parameter,
including historical trend recording of energy, demand,
voltage, current, power quality, or any measured
parameter. Trigger recorders based on time interval,
calendar schedule, alarm/event condition, or manually.
Access historical data at the front panel. Display, trend
and continuously update historical data with date and
timestamps for up to four parameters simultaneously.
Simultaneous capture of all voltage and current channels
-	 sub-cycle disturbance capture
-	 maximum cycles is 214,000 (16 samples/cycle x 96
cycles, 10Mbytes memory)
-	 256 samples/cycle (ION7550)
-	 512 samples/cycle standard, 1024 samples/cycle
optional (ION7650)
COMTRADE waveform format available direct from the
meter (Ethernet port option only)
Threshold alarms:
-	 adjustable pickup and dropout setpoints and time
delays, numerous activation levels possible for a given
type of alarm
-	 user-defined priority levels
-	 boolean combination of alarms is possible using the
operators NAND, OR, NOR and XOR
Up to 16 users with unique access rights. Perform resets,
time syncs, or meter configurations on user privileges
Correct for phase / magnitude inaccuracies in current
transformers (CTs), potential transformers (PTs)
5 to 10 Mbytes (specified at time of order)
Update via the communication ports

Display characteristics

Example showing instantaneous values and alarm.

Integrated display
Languages
Notations

Back lit LCD, configurable screens
English, French, Spanish, Russian
IEC, IEEE

(1) All the communication ports may be used simultaneously.
(2) Only available with 5MB memory meters.

2013

97

ION7550 / ION7650

Advanced metering

Functions and characteristics (cont.)

Part numbers

PE86020

1

Item

Code

Description

Model

M7650

Advanced meter with wide-range voltage inputs (57-347V
line-neutral or 100-600V line-line), transient detection, data and
waveform recording, IEC 61000-4-30 Class A & EN50160.
Supports ION, IEC 61850 (only for meters with 5MB memory and
Ethernet comm card) Modbus-RTU, and DNP 3.0.

M7550

Advanced meter with wide-range voltage inputs (57-347V
line-neutral or 100-600V line-line), sag/swell detection, data and
waveform recording. Supports ION, IEC 61850 (only for meters
with 5MB memory and Ethernet comm card) Modbus-RTU, and
DNP 3.0.
Integrated display with front optical port, 5 MB logging memory,
and 512 samples/cycle resolution (ION7650) or 256 samples/
cycle (ION7550).

M

Example ION7650 product part number.

2

Form Factor

1	 Model.
2	 Form factor.
3	 Current Inputs.
4	 Voltage Inputs.
5	 Power supply.
6	 System frequency.
7	 Communications.
8	 Inputs/outputs.
9	 Security.
10	Special order.

A0

A1

ION7650 only. Integrated display with front optical port, 5 MB
logging memory, and 1024 samples/cycle resolution.

B0

Integrated display with front optical port, 10 MB logging memory,
and 512 samples/cycle resolution (ION7650) or 256 samples/
cycle (ION7550).
ION7650 only. Integrated display with front optical port, 10 MB
logging memory, and 1024 samples/cycle resolution.

B1
T0
T1
U0
U1
3

Current Inputs

C
E
F
G

4
5

Voltage Inputs
Power Supply

0
B

6

System
Frequency

7

Communications

C
5
6
A0
C1
D7

E0
F1
M1
8

I/O

Standard I/O plus Expansion I/O card (8 additional digital inputs &
four 0 to 20 mA analogue inputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs &
four 0 to 20 mA analogue outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs &
four 0 to 20 mA analogue inputs and four 0 to 20 mA outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs &
four 0 to 1 analogue inputs and four -1 to 1 mA analogue outputs)
Password protected, no hardware lock
Password protected, hardware lockable (enabled/disabled via
jumper on comm card)
Password protected with security lock enabled, terminal cover and
UK OFGEM labels

0
1
6

2013

Standard communications plus 10Base-T/100Base-TX (RJ45).
Ethernet gateway function uses a serial communications port.
Standard communications plus 10Base-T/100Base-TX Ethernet
(RJ45) and 100Base-FX (SC male Fiber Optic connection).
Ethernet gateway function uses a serial port.
Standard communications plus 56k universal internal modem
(RJ11). Modem gateway function uses a serial port.
Standard I/O (8 digital ins, 3 Form C relays, 4 Form A solid-state out)

P

98

5 Amp nominal, 20 Amp full scale current input
1 Amp nominal, 10 Amp full scale current input
Current Probe Inputs (for 0-1 VAC current probes; sold separately)
Current Probe Inputs with three Universal Technic 10A clamp on
CTs; meets IEC 1036 accuracy
57 to 347 VAC line-to-neutral / 100 to 600 VAC line-to-line
Standard power supply (85-240 VAC, ±10%/47-63 Hz / 110-300
VDC, ±10%)
Low voltage DC power supply (20-60 VDC)
Calibrated for 50 Hz systems
Calibrated for 60 Hz systems
Standard communications (1 RS-232/RS-485 port, 1 RS-485 port).
Integrated display models include 1 ANSI Type 2 optical port.
Standard communications plus 10Base-T/100Base-TX Ethernet
(RJ45), 56k universal internal modem (RJ11). Ethernet and
modem gateway functions each use a serial communications port.
Standard communications plus 10Base-T/100Base-TX Ethernet
(RJ45) and 100BaseFX Ethernet Fiber, 56k universal internal
modem (RJ11). Ethernet/modem gateway uses serial port.

E

N

Security

Transducer (no display) version, with 10 MB logging memory, and
512 samples/cycle resolution (ION7650) or 256 samples/cycle
(ION7550).
ION7650 only. Transducer (no display) version, with 10 MB
logging memory, and 1024 samples/cycle resolution.

A

K

9

Transducer (no display) version, with 5 MB logging memory, and
512 samples/cycle resolution (ION7650) or 256 samples/cycle
(ION7550).
ION7650 only. Transducer (no display) version, with 5 MB logging
memory, and 1024 samples/cycle resolution.

ION7650 / ION7550

Advanced metering

Functions and characteristics (cont.)

Part numbers (cont’d)
10

Item
Other options

Code
A
C
E
F

Communications Card (1)

PE86021

Item

P

C1

Description
None
Tropicalisation treatment applied
ION7650 only. EN50160 compliance monitoring,
IEC61000-4-30 Class A measurements
ION7650 only. EN50160 compliance monitoring, with
tropicalisation treatment, IEC61000-4-30 Class A measurements

Code

Description

1 Comm card

P765C

2

A0

ION7550 / ION7650 communication card for field retrofit
installations
Standard communications (1 RS-232/RS-485 port, 1 RS-485
port). Front optical port support for meters with integrated
display.
Standard communications plus 10Base-T/100Base-TX Ethernet
(RJ45), 56k universal internal modem (RJ11; the modem port is
shared with the front optical port). Ethernet and modem gateway
functions each use a serial communications port. IEC 61850
protocol (depending on firmware version).

Type

Example order code. Use this group of codes when ordering
the PowerLogic™ ION7550/7650 communications or I/O
cards.

C1

1	 Communications or I/O card.
2	 Type
3	 Special order.

D7

E0
F1

M1
3

Special order

A
C

Standard communications plus 10Base-T/100Base-TX Ethernet,
100BaseFX Ethernet Fiber, 56k universal internal modem (RJ11;
the modem port is shared with the front optical port).
Ethernet and modem gateway functions each use a serial
communications port.IEC 61850 protocol (depending on
firmware version).
Standard communications plus 10Base-T/100Base-TX Ethernet.
Ethernet gateway function uses a serial communications port.
IEC 61850 protocol (depending on firmware version).
Standard communications plus 10Base-T/100Base-TX Ethernet,
100BaseFX Ethernet Fiber (SC male Fiber Optic connection).
Ethernet gateway function uses a serial communications port.
IEC 61850 protocol (depending on firmware version).
Standard communications plus 56k universal internal modem
(RJ11; the modem port is shared with the front optical port).
Modem gateway function uses a serial communications port.
None
Tropicalization treatment applied

Input/Output expansion card
Item

I/O card
Type

Code

Description

P760A
D

Expansion I/O for field retrofit installations.
Expansion I/O card with eight digital inputs, four 0 to 1 mA
analogue inputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue inputs
Expansion I/O card with eight digital inputs, four -1 to 1 mA
analogue outputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue outputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue inputs & four 0 to 20 mA outputs
Expansion I/O card with eight digital inputs, four 0 to 1 analogue
inputs and four -1 to 1 mA analogue outputs
None
Tropicalization treatment applied

E
H
K
N
P

PE86019

Special Order

A
C

ION7550 / ION7650 related items
Code

Description

ADPT-37XX-7500
TERMCVR-7500
M1UB10A1V-10A
P32UEP813-1000A
P32UEP815-3000A
SCT0750-005-5A
SCT1250-300-300A

Adapter plate to fit meter into a 3710 or 3720 ACM panel cutout
Terminal strip cover for the ION7550 or ION7650
10 A / 1 VAC Universal Technic Clamp On Current Probe
1000 A / 1 VAC Universal Technic Clamp On Current Probe
3000 A / 1 VAC Universal Technic Clamp On Current Probe
5 A / 0.333 VAC Magnelabs Split Core Current Probe
300 A / 0.333 VAC Magnelabs Split Core Current Probe

PowerLogic™ ION7550 TRAN
(1) Firmware version 350 or higher required.

2013

99

ION7550 / ION7650

Advanced metering

Dimensions and connection

PE86023

PE86022

ION7550/ION7650 dimensions

PE86025

PE86026

PE86024

ION7550 / ION7650 TRAN dimensions

100

PE86027

Front-panel mounting
ION7550 and ION7650 meter can have integrated or remote
display. The meter with integrated display is designed to fit DIN
standard 192 cutout (186 mm by 186 mm) . The remote display
is intalled through a circular cutout (22.5 mm diameter) at the
panel door and it has a front and a back module that is
connected to the meter mounted in a DIN rail at the back.

2013

Advanced metering

Circuit Monitor Series 4000
Functions and characteristics

PE86140

The PowerLogic Circuit Monitor Series 4000 offers high-performance digital
instrumentation, data acquisition and control capabilities. The products can integrate
easily in power monitoring and control systems due to their optional Ethernet
connections and embedded web server. They are Transparent Ready.
These devices are designed for applications where power quality and availability are
critical factors. They are generally used at service entrances and interconnection
points or on circuits feeding sensitive equipment. Due to their very wide range of
features, including transient detection (CM4000T only), it is possible to rapidly solve
problems related to poor power quality. EN 50160 compliance checking capability
makes these products ideal to meet new needs related to market deregulation.
The Circuit Monitor Series 4000 is available in two versions:
bb CM4250, with detection of voltage sags, swells and other power quality indices
bb CM4000T, with detection of voltage sags and swells together with transient
detection and flicker measurements.

Applications

Panel instrumentation.
Sub-billing / cost allocation.
Remote monitoring of an electrical installation.
Extensive power-quality monitoring.
Contract and load curve optimisation.
EN 50160 electrical supply compliance checking.
Metering of other utilities.

Main characteristics
CM4000 + vacuum fluorescent display (VFD).

Disturbance direction detection
Indication of whether the source of a specific power quality event is upstream or
downstream from the meter.
Power quality summary
Consolidation of all the power quality characteristics into a single trendable index.
Adaptive waveform capture
Capture of long-duration events.
Shift energy summary
Indication of energy usage per shift up to three shifts a day.
Detection and capture of voltage sags and swells
Fast identification of problems causing production shutdown.
Detection and capture of short transients less than 1 µs
(optional, CM4000T only)
Identification of problems due to short disturbances, e.g. switching of capacitors, etc.
Flicker evaluation based on IEC 61000-4-15 and IEEE 1453 (CM4000T only)
Measurement of rapid voltage variations.
Electrical quality checking in compliance with EN 50160
Fast standardised check on the quality of the electricity supplied.
Detection of major waveform changes
Detection of phase switching phenomena (for example during the transfer of a
high-speed static switch) not detected by classical threshold-based alarms.
Ultra-fast recording of electrical parameters every 100 ms or every cycle
Preventive maintenance: acquisition of a motor startup curve, etc.
Trend curves and short-term forecasting
Rapid trending and forecasting of upcoming values for better decision making.
Automatic alarm setting
Alarm setpoint learning feature for optimum threshold settings.
Up to 32 Mbytes of memory (16 Mbytes standard)
For archiving of data and waveforms.
Ethernet 10/100 Mbits/s card and server for HTML pages
(with optional Ethernet card)
Rapid data transfers over an intranet or the internet, simply using a web browser.
Alarm notification via email
High-priority alarms sent directly to the user’s PC.
Instant notification of power quality events by email.
Up to 25 inputs/outputs to monitor the electrical installation
(with optional I/O cards)
Status of circuit breakers, as well as metering of other commodities, e.g. gas, water, etc.
IEC 62053-22 and ANSI C12.20 Class 0.2S for energy
Verification of consumption and load curves.

2013

101

Advanced metering

Circuit Monitor Series 4000

Functions and characteristics (cont.)

Part numbers

Circuit Monitor Series 4000
CM4250
CM4000T

Circuit Monitor CM4250
Circuit Monitor CM4000T

Selection guide
DB108168

General

Use on LV and HV systems
Current and voltage accuracy
Energy and power accuracy
Nbr of samples/cycle or sample frequency

CM4250

CM4000T

b
0.07 %
0.2 %
512

b
0.07 %
0.2 %
5 MHz

b
b
b

b
b
b

b
b

b
b

b
b
b
b
b

b
b
b
b
b

b
b
63
255
b
b
b
b
b
b

b
63
255
b
b
b
b
b
b
b
b

Instantaneous rms values
Current, voltage, frequency
Active, reactive, apparent power
Power factor

Total and per phase
Total and per phase

Energy values
Active, reactive, apparent energy
Settable accumulation modes

Demand values

CM4000 series.
1	 Current/voltage module.
2	 Control power-supply connector.
3	 Maintenance LED indicator.
4	 Power LED indicator.
5	 RS 485 port with transmit and receive LED indicators.
6	 Display communication port.
7	 Slots for optional cards.
8	 RS 232 port with transmit and receive LED indicators.
9	 KYZ pulse output.
10	Sealable access door.

Current
Present and max. values
Active, reactive, apparent power
Present and max. values
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Setting of calculation mode
Block, sliding

Power quality measurements
Interharmonics
Harmonic distortion
Individual harmonics

Current and voltage
Via monitor
Via SMS

Waveform capture
Detection of voltage swells and sags
Adaptive waveform capture (up to 64 s)
Detection and capture of transients (< 1 µs)
Flicker
Fast acquisition of 100 ms or cycle by cycle data
EN 50160 compliance checking (1)
Programmable (logic and math functions)

Data recording
E87306

Min/max of instantaneous values
Data logs
Event logs
Trending/forecasting
Alarms (optional automatic alarm setting)
Alarm notification via email
SER (Sequence of Event Recording)
Time stamping
GPS synchronisation (1 ms)
Memory expandable up to

b
b
b
b
b

b
b
b
b
b
ECC21 option
b
b
b
b
IOC44 option
32 Mbytes
32 Mbytes

Display and I/O

Disturbance waveform capture: detection of a voltage sag.

Display
Multilingual: English, French, Spanish, German, Italian, Polish
Wiring self-test
Pulse output
Maximum number of I/Os
Input metering capability (number of channels)
Direct voltage connection

CMDLC or CMDVF option
b
b
b
b
b
b
25
25
10
10
690 V
600 V

Communication
RS 485 port
2/4 wires
2/4 wires
b
b
RS 232 port
b
b
Modbus protocol
Ethernet card (Modbus/TCP/IP protocol)
ECC21 option
HTML-page web server
ECC21 option
Ethernet gateway for third-party products
ECC21 option
(1) Except for interharmonics, signalling voltages, flicker and transients.

102

2013

Advanced metering

Circuit Monitor Series 4000

Functions and characteristics (cont.)

The Circuit Monitor has two optional display units, an LCD display and a vacuum
fluorescent display (VFD). They may be used for local circuit-monitor setup and
operation.

PE86143

CMDLC display

Back-lit LCD display with four lines and 20 characters per line. The display unit has
four navigation buttons, a contrast button and a red alarm LED.
It connects to the Circuit Monitor via a CAB12 cable, 4.2 metres long, supplied with
the display.

Part numbers
LCD display supplied with the CAB12 cable
Connection cables:
1.25 m (4 ft)
Circuit Monitor <-> display
3.65 m (12 ft)
9.14 m (30 ft)

CMDLC
CAB4
CAB12
CAB30

PE86142

CMDVF display

Vacuum fluorescent display (VFD) with four lines and 20 characters per line.
The display unit has four navigation buttons, a contrast button, a red alarm LED.
The display comes with a cable for connection to the Circuit Monitor (CAB12 cable,
4.2 m long).

Part numbers
VFD supplied with the CAB12 cable
Connection cables:
Circuit Monitor <-> display

E87288

1	
2	
3	
4	
5	
6	
7	

1.25 m (4 ft)
3.65 m (12 ft)
9.14 m (30 ft)

CMDVF
CAB4
CAB12
CAB30

Display screen.
Alarm LED.
Arrow buttons.
Menu button.
Proximity sensor (VFD display only).
Enter button.
Contrast button.

Display.

2013

103

Advanced metering

Circuit Monitor Series 4000

Functions and characteristics (cont.)

Electrical characteristics
PE86141

Type of measurement

Measurement
accuracy

Current and voltage
Power
Frequency
Power factor
Energy:
CM4250/CM4000T

Data update rate
Input-voltage
Measured voltage
characteristics

CM4000 + options: ECC21, IOC44 and IOX2411.

Input-current
characteristics

Power supply

Input/outputs

Measurement range
Impedance
Frequency measurement
range
CT ratings
Measurement range
CM4250/CM4000T
Permissible overload
Impedance
Load
AC
DC
Ride-through time
Pulse output
IOC44 card (optional)
IOX extender (optional)
IOX08 (optional)
IOX0404 (optional) (1)
IOX2411 (optional) (1)

True rms up to the 255th harmonic
On three-phase AC system (3P, 3P + N)
Up to 512 samples per cycle
Up to 5 MHz for transient events (CM4000T only)
±0.04 % of reading + ±0.025 % of full scale
±0.075 % of reading + ±0.025 % of full scale
±0.01 Hz from 45 to 67 Hz
±0.1 Hz from 350 to 450 Hz
±0.002 from 0.5 leading to 0.5 lagging
IEC 62053-22 and ANSI C12.20 Class 0.2S
1 s in normal mode
0 to 600 V AC on CM4000T (direct)
0 to 690 V AC on CM4250 (direct)
0 to 1200 kV AC (with external VT)
0 to 1.5 Un
> 2 MW
45 to 67 Hz and 350 to 450 Hz
Adjustable from 5 A to 30 000 A
5 mA to 10 A
15 A continuous
50 A for 10 seconds per hour
500 A for 1 second per hour
< 0.1 W
< 0.15 VA
100 to 275 V AC (±10 %), 50 VA
125 to 250 V DC (±20 %), 30 W
100 ms at 120 V DC
Static output (240 V AC max, 96 mA max)
4 digital inputs (20-138 V AC/DC),
3 relay outputs (5 A to 240 V AC)
1 static output (96 mA max to 240 V AC)
Slots for 8 I/Os
8 digital inputs 120 V AC
4 dig. inputs 120 V AC, 4 analogue outputs 4-20
mA
2 dig. outputs 120 V AC, 4 dig. inputs 32 V DC,
1 analogue input 0-5 V, 1 analogue output 4-20
mA

Mechanical characteristics
Weight
IP degree of protection (IEC 60529)
Dimensions
Without IOX accessory
CM4250/
With IOX accessory
CM4000T

1.9 kg
IP52
235.5 x 165.6 x 133.1 mm
235.5 x 216.3 x 133.1 mm

Environmental conditions
Operating
temperature

Circuit Monitor
CMDLC display
CMDVF display
CM + displays

Storage
temperature
Humidity rating
Pollution degree
Installation
CVM42
category
CVMT
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to impulse waves
Conducted and radiated emissions

-25 °C to +70 °C
-20 °C to +60 °C
-20 °C to +70 °C
-40 °C to +85 °C
5 to 95 % RH at 40 °C
2
IV
II
As per EN 61010, UL508, CSA C22.2-2-4-M1987
Level 3 (IEC 61000-4-2)
Level 3 (IEC 61000-4-3)
Level 3 (IEC 61000-4-4)
Level 4 (IEC 61000-4-5)
e industrial envir./FCC part 15 class A

Safety
Europe
e, as per CEI 61010
USA and Canada
UL508 and CSA C22.2-2-4-M1987
(1) Operating limits: 0° C to +60 °C. Storage limits: -25 °C to +85 °C.

104

2013

Advanced metering

Circuit Monitor Series 4000

Functions and characteristics (cont.)

Communication
2/4 wires, up to 38400 bauds, Modbus
Up to 38400 bauds, Modbus, direct connection to a PC
or modem
Ethernet ECC21 card with HTML server (optional) (1)
Copper Ethernet link
10/100 BaseTX, RJ45 connector, 100 m link
Fiber-optic Ethernet link
100 Base FX, LC duplex connector, 1300 nm, FO
multimode with gradient index 62.5/125 µm or 50/125 µm,
2000 m link
Protocol
Modbus/TCP/IP
Gateway function for products
Master Modbus port, 31 daisy-chained slaves,
connected to the ECC21
63 with repeater, 2/4 wires, 1200 to 38400 bauds,
also compatible with the PowerLogic protocol
HTML server
1 standard page, 5 customisable pages

E87307

RS 485 port (1)
RS 232 port (1)

Firmware characteristics

E87308

Adaptive waveform capture: transformer inrush current.

14 data logs

Up to 96 different parameters, factory-set logs ready
to use

One 100 ms data log
One 20 ms (50 Hz) or 16 ms (60 Hz)
data log
One min/max log
One min/max/avg. log

Parameters recorded every 100 ms for events
Parameters recorded every 20 ms or 16 ms for events

One event log
Trend curves

Forecasting
Waveform captures

Adaptive waveform capture: motor start, rms value.

E87309

Alarms

Example CM4250 HTML page showing instantaneous values.
Memory
Firmware update

Min/max/avg. values recorded for 23 parameters at
regular intervals from 1 to 1440 minutes
Time stamping to 1 ms, synchro. 1 ms by GPS
Four trend curves: 1 minute, 1 hour, 1 day and 1 month.
Min./max./avg. values recorded for eight parameters:
- every second for one minute for the 1-minute curve
- every minute for one hour for the 1-hour curve
- every hour for one day for the 1-day curve
- every day for one month for the 1-month curve
Forecasting of the values for the eight parameters
for the next four hours and next four days
Standard: manual launch, 1 cycle, 512 samples, 255th
harmonic
Disturbance: manual launch or by alarm, adjustable from
512 samples/cycle over 28 cycles to 16 samples/cycle
over 915 cycles, response time less than 0.5 cycle,
number of cycles before alarm settable from 2 to 10
Adaptive: manual launch or by alarm, adjustable from
512 samples/cycle over 8 seconds to 16 samples/cycle
over 264 seconds, capture takes place during a set
duration or as long as an alarm is active (to save memory),
number of cycles before alarm settable from 2 to 10
Transient: voltage sampling at 5 MHz (83 333 samples/
cycle) over 2 ms to capture transient peaks < 1 µs
Threshold alarms:
- adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of
alarm
- 4 priority levels
- 4 response times: standard 1 s, fast 100 ms,
disturbance < 1/2 cycle, transient < 1µs
- boolean combination of four alarms is possible using the
operators NAND, OR, NOR and XOR
Automatic alarm setting: after a learning phase, the alarm
thresholds are set automatically. The alarms will trip in the
event of drift with respect to reference values determined
during the learning period.
Digital alarms: logic input transitions
Waveform alarms: alarm tripping by a special algorithm
when the current or voltage waveform is distorted beyond
an adjustable level. Makes it possible to detect
disturbances that cannot be detected by classical
threshold alarms (e.g. phase switching).
8 Mbytes standard, expandable up to 32 Mbytes
Update via the communication ports

Display characteristics
CMDLC (optional)
Back lit LCD
CMDVF (optional)
Vacuum fluorescent display (VFD) with IR port
Languages
English, French, Spanish, German, Italian, Polish
(1) All the communication ports may be used simultaneously.

2013

105

Circuit Monitor Series 4000

Advanced metering

Dimensions and connection

E94394
E94392

E94393

CM4250 / CM4000T dimensions

DB108169

Mounting on a backplate

106

2013

Circuit Monitor Series 4000

Advanced metering

Dimensions and connection

DB108005
DB108006

DB108007

Mounting possibilities

Vertical mounting.

Horizontal mounting.

E87285

E87286

CMDLC/CMDVF dimensions

E94377

Mounting on a backplate

2013

107

Advanced utility metering

ION8650

PB107500

Functions and characteristics

Used to monitor electric energy provider networks, service entrances and
substations, PowerLogic ION8650 meters are ideal for independent power
producers and cogeneration applications that need to accurately measure energy
bi-directionally in both generation and stand-by modes. These meters give utilities
the tools to manage complex energy supply contracts that include commitments to
power quality. Integrate them with our StruxureWare Power Monitoring (ION
Enterprise™) operations software or other energy management and SCADA
systems through multiple communication channels and protocols, including Itron
MV-90, Modbus, DNP, IEC 61850.

Applications

PowerLogic ION8650 socket meter

Revenue metering.
Co-generation and IPP monitoring.
Compliance monitoring.
Power quality analysis.
Demand and power factor control.
Load curtailment.
Equipment monitoring and control.
Energy pulsing and totalisation.
Instrument transformer correction.

Main characteristics
ANSI Class 0.2 and IEC 62053-22/23 Class 0,2S metering
For interconnection points on medium, high, and ultra-high voltage networks; twice
as accurate as current IEC and ANSI Class 0.2 standards over all conditions and
including single wide range current measurement.
Power quality compliance monitoring
Monitor compliance with international quality-of-supply standards (IEC 61000-4-30
Class A/S, EN50160, IEC 61000-4-7, IEC 61000-4-15, IEEE 1159, IEEE 519).
Digital fault recording
Simultaneous capture of voltage and current channels for sub-cycle disturbance.
Complete communications
Multi-port, multi-protocol ports including serial, infrared, modem and ethernet.
Simultaneously supports multiple industry standard protocols including: Itron MV-90,
Modbus, Modbus Master, DNP 3.0 and IEC 61850.
Multiple tariffs and time-of-use
Apply tariffs, seasonal rate schedules to measure energy and demand values for
time periods with specific billing requirements.
Multiple setpoints for alarm and functions
Use up to 65 setpoints for single/multi-condition alarms and I/O functions with
response times down to 1/2 cycle.
Multiple setpoints for alarm and functions
Use up to 65 setpoints.
Instrument transformer correction
Save money and improve accuracy by correcting for less accurate transformers.
Alarm notification via email
High-priority alarms, data logs sent directly to the user’s PC. Instant notification of
power quality events by email.

Part numbers
ION8650 meters

M8650A
M8650B
M8650C

ION8650A
ION8650B
ION8650C

108

2013

Advanced utility metering

ION8650
Functions and characteristics (cont.)

PE86302-95

Selection guide

ION8650 ION8650 ION8650
A
B
C

General
Use on LV, MV and HV systems
Current accuracy
Voltage accuracy
Power accuracy
Samples/cycle

Instantaneous values
Current, voltage, frequency
Active, reactive, apparent power
Power factor
Current measurement range

Total & per phase
Total & per phase

Energy values
Active, reactive, apparent energy
Settable accumulation modes

Demand values

PowerLogic ION8650 socket meter.
1	
2	
3	
4	
5	
6	
7	
8	

Terminals
Optical port
Main display status bar
Watt LED
Navigation, ALT/Enter buttons
VAR LED
Nameplate label
Demand reset switch

Present & max. values
Current
Active, reactive, apparent power Present & max. values
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Demand modes: Block (sliding), thermal (exponential)

Power quality measurements
Harmonic distortion
Current & voltage
Individual harmonics
Via front panel
Waveform / transient capture
Harmonics: magnitude, phase, and interharmonics
Detection of voltage sags and swells
IEC 61000-4-30 class A /S
IEC 61000-4-15 (Flicker)
High speed data recording (down to 10 ms)
EN50160 compliance reporting
Programmable (logic and math functions)

b

b

b

0.1 %
0.1 %
0.1 %
1024

0.1 %
0.1 %
0.1 %
1024

0.1 %
0.1 %
0.1 %
1024

b
b
b

b
b
b

b
b
b

0 - 20A

0 - 20A

0 - 20A

b
b

b
b

b
b

b
b
b
b
b

b
b
b
b
b

b
b
b
b
b

b

b

b

63
b/b
50
b

63
-/b
40
b

31
-/b

A
b
b
b
b

S
b
b
b
b

b

128
b
b
b
b
b
b
b
b

64
b
b
b
b
b

32
b
b
b
b
b

b
b

b
b

b
b

b
b

b
b

2
11
16

2
11
16

2
11
16

Data recording
PE86002

Onboard Memory (in Mbytes)
Revenue logs
Event logs
Historical logs
Harmonics logs
Sag/swell logs
Transient logs
Time stamping to 1 ms
GPS synchronisation (IRIG-B standard)

Display and I/O

Disturbance waveform capture and power quality report

Front panel display
Wiring self-test (requires PowerLogic ION Setup)
Pulse output (front panel LED)
Digital or analogue inputs(1) (max)
Digital or analogue outputs(1) (max, including pulse output)

Communication
Infrared port
1
1
1
RS 485 / RS 232 port
1
1
1(3)
RS 485 port
1
1
1(3)
Ethernet port (Modbus/TCP/IP protocol) with gateway
1
1
1(3)
Internal modem with gateway (ModemGate)
1
1
1(3)
b
b
b
HTML web page server
IRIG-B port (unmodulated IRIG B00x time format)
1
1
1
Modbus TCP Master / Slave (Ethernet port)
b/b
b/b
-/b
Modbus RTU Master / Slave (Serial ports)
b/b
b/b
-/b
b
b
b
DNP 3.0 through serial, modem, and I/R ports
(1) With optional I/O Expander.
(2) For 9S, and 36S only. For 35S system up to 480V line-to-line.
(3) C model limited to IR + 2 other ports at one time. Ports can be enabled/disabled by user.

2013

109

Advanced utility metering

ION8650

Functions and characteristics (cont.)

PE86041

Electrical characteristics

PowerLogic ION8650 front panel harmonic display.

Type of measurement

True rms 1024 samples per cycle

Measurement
accuracy

0.1 % Reading
0.1%
±0.001 Hz
0.1%
0.1%, twice as accurate as ANSI Class 0.2 and
IEC 62053-22/23 (0,2S)
0.5 cycle or 1 second (depending on value)
57V to 277VLN rms
100V to 480VLL rms (35S)
347 VLN rms, 600 VLL rms (9S)

Current and voltage
Power
Frequency
Power factor
Energy

Data update rate
Input-voltage
Nominal voltage
characteristics (1)
Maximum voltage

Input-current
characteristics

Impedance
Inputs
Rated nominal/current
class
Accuracy range

5 MW /phase (phase-Vref/Ground)
V1, V2, V3, VREF
1A, 2 A, 5 A and/or 10 A (Class 1/2/10/20)

Measurement range

0.001 - 24 A

Permissible overload

500A rms for 1 second, non-recurring

Burden per phase

Socket: Typical: 3 W, 8 VA/phase, 3-phase
operation; Maximum: 4 W, 11 VA/phase,
3-phase operation
Switchboard: 0.05VA at 1A (0.05 Ω max)
120-277 VLN RMS (-15%/+20%) 47-63 Hz or
120-480 VLL RMS (-15%/+20%) 47-63 Hz (35S)
AC: 65-120 (+/- 15%) VLN RMS, 47-63 Hz
DC: 80-160 (+/- 20%) VDC
AC: 160-277 (+/- 20%) VLN RMS, 47-63 Hz
DC: 200-300 (+/- 20%) VDC
Socket: min guaranteed: 6 cycles at nominal
frequency (minimun 50 Hz), at 120 V L-N rms
(208 V L-L rms) 3-phase operation
Switchboard: min guaranteed: `6 cycles at
nominal frequency (minimun 50 Hz), at 120 V
L-N rms (208 V L-L rms) 3-phase operation

Power supply

Standard power supply,
blade powered
Auxiliary powered low
voltage
Auxiliary powered high
voltage
Ride-through time,
(Standard power supply)

Input/outputs

Digital outputs (Form C)
Digital outputs (Form A)
Digital inputs

0.01 - 20 A (standard range)

4 Solid state relays (130 V AC/ 200 V DC)
50 mA AC/DC
4 Solid state relays (via optional I/O Expander)
4 Solid state inputs (via optional I/O Expander)

Mechanical characteristics
PE86042

Weight
IP degree of
protection

Socket
Switchboard
Socket
Switchboard

Dimensions

7.0 kg
Front IP65, back IP51
Front IP50, back IP30
178 x 237 mm
285 x 228 x 163 mm

Environmental conditions
ION8650 front panel phasor display and table.

Operating temperature
Display operating range
Storage temperature
Humidity rating
Pollution degree
Installation category
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to surge
Immunity conducted
Damped oscillatory waves immunity
Conducted and radiated emissions

-40°C to +85°C
-20°C to +60°C
-40°C to +85°C
5 to 95 % RH non-condensing
2
Cat III
2.5kV
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC61000-4-6
IEC61000-4-12
CISPR 22 (class B)

Safety
Europe
North America

As per IEC62052-11
As per ANSI C12.1

(1)Specifications are limited by the operating range of the power supply if a non-aux power supply is used.

110

2013

Advanced utility metering

ION8650

Functions and characteristics (cont.)

PE86004-C

Communication
RS 232 / RS 485 port (COM1)

Internal modem port (COM2)

User-selectable RS 232 or RS 485.
300 - 115,200 bauds (RS485 limited to 57,600 bps);
protocols: ION, Modbus/RTU/Mastering, DNP 3.0,
GPSTRUETIME/DATUM.
300-57,600 bps

ANSI 12.18 Type II optical port
(COM3)
RS 485 port (COM4)

Up to 19200 bps

Ethernet port

10/100 BaseT, RJ45 connector, protocols:
DNP, ION, Modbus/TCP/Mastering, IEC 61850
Up to 31 slave devices via serial ports
Up to 31 slave devices

EtherGate
ModemGate

Up to 57,600 bauds, Modbus, direct connection to a PC
or modem

Firmware characteristics
High-speed data recording

Up to 1/2-cycle interval burst recording, stores detailed
characteristics of disturbances or outages. Trigger
recording by a user-defined setpoint, or from external
equipment.

Harmonic distortion

Up to 63rd harmonic for all voltage and current inputs

Dip/swell detection

Analyse severity/potential impact of sags and swells:
-	 magnitude and duration data suitable for plotting on
voltage tolerance curves
-	 per phase triggers for waveform recording or control
operations
High accuracy measurements with 1s or 1/2 cycle update
rate for:
-	 voltage and current
-	 active power (kW) and reactive power (kVAR)
-	 apparent power (kVA)
-	 power factor and frequency
-	 voltage and current unbalance
-	 phase reversal
Channel assignments are user configurable:
-	 800 channels via 50 data recorders (feature set A),
-	 720 channels via 45 data recorders (feature set B),
-	 64 channels via 4 data recorders (feature set C).
Configure for historical trend recording of energy,
demand, voltage, current, power quality, other measured
parameter. Recorders can trigger on time interval basis,
calendar schedule, alarm/event condition, manually.
Simultaneous capture of all voltage and current channels
-	 sub-cycle disturbance capture (16 to 1024 samples/
cycle)

Example embedded webserver page (WebMeter) showing
realtime values.

Instantaneous

Load profiling

Waveform captures

Threshold alarms:
-	 adjustable pickup and dropout setpoints and time
delays, numerous activation levels possible for a given
type of alarm
-	 user-defined priority levels
-	 boolean combination of alarms

Advanced security

Up to 16 users with unique access rights. Perform resets,
time syncs, or meter configurations based on user
priviledges.
Correct for phase / magnitude inaccuracies in current
transformers (CTs), potential transformers (PTs)
128 Mbytes (A), 64 Mbytes (B), 32 Mbytes (C)
Update via the communication ports

PE86005-C

Alarms

Transformer correction
Memory
Firmware update

Display characteristics
Type
Backlight
Languages

2013

FSTN transreflective LCD
LED
English

111

Advanced utility metering

ION8650
Functions and characteristics (cont.)

PE86043-C

Part Numbers
Item

Code

Description

1 Model
2 Feature Set

M8650
A

Schneider Electric energy and power quality meter.
128MB Memory Class A power quality analysis, waveforms and
transient capture with 1024 samples/cycle.

B

64MB memory, energy meter Class S EN50160 power quality
monitoring.
32MB memory, basic tariff/energy metering (4 data recorders,
64 channels).
Form 9S/29S/36S Base, 57-277 VLN (autoranging)
3-Element, 4-Wire / 2 1/2-Element, 4-Wire
Form 35S Base - 120-480 VLL (autoranging) 2-Element,
3-Wire
Form 9/29/35/36S FT21 Switchboard (meter + case) with break
out panel
Form 9/29/35/36S FT21 Switchboard (meter + case) with break
out cable
1, 2 or 5 Amp nominal, 20 Amp full scale (24 Amp fault
capture, start at 0.001 A)

Example product part number.
3 Form Factor (1)

0
1
4
7

4 Current Inputs

C

5 Voltage Inputs
6 Power Supply

0
E

Standard (see Form Factor above)
Form 9/29/35/36S, (socket) and Form 9, 36 (FT21
switchboard): 120-277 VAC. Form 35S (socket) and Form 35
(FT21 switchboard): 120-480 VAC. Powered from the meter’s
voltage connections.

H

Auxiliary Power Pigtail: 65-120 VAC or 80-160 VDC
(power from external source)
Auxiliary Power Pigtail: 160-277 VAC or 200-300 VDC
(power from external source)
Calibrated for 50 Hz systems.
Calibrated for 60 Hz systems.
Infrared optical port, RS 232/RS 485 port, RS 485 port

PB107507

1	 Model.
2	 Feature set.
3	 Form factor.
4	 Current Inputs.
5	 Voltage inputs.
6	 Power supply.
7	 System frequency.
8	 Communications.
9	 Input/output options.
10	 Security.
11	Special order options.

C

J
7 System Frequency 5
6
8 Communications
A0
C1
C7

E0

PowerLogic ION8650 meter with switchboard case

E1

Infrared optical port. RS 232/485 port (note this port is not
available with feature set C), Ethernet (10BaseT), 56k
universal internal modem (RJ11),
Infrared optical port, Ethernet (10 BaseT), RS 232/485 port,
RS 485 port (note: in addition to infrared optical port, Feature
Set C can use any two ports (configurable)), 56k universal
internal modem (RJ11)
Infrared optical port, RS 485 port (note this port is not
available with feature set C) Ethernet (10BaseT), RS 232/485
port,
Infrared optical port, Ethernet (10 BaseT), RS 232/485 port,
RS 485 port (note: in addition to infrared optical port, Feature
Set C can use any two ports (configurable))

M1

Infrared optical port, RS 232/485 port, RS 485 port (note: in
addition to infrared optical port, Feature Set C can use any
two ports (configurable)), 56k universal internal modem
(RJ11).

9 Onboard I/O

A
B
C

10 Security

0
1

None.
4 Form C digital outputs, 3 Form A digital inputs.
4 Form C digital outputs, 1 Form A digital output, 1 digital
input.
Password protected, no security lock
Password protected with security lock enabled (requires
removal of outer cover to configure billing parameters)
RMICAN (Measurement Canada approved)
RMICAN-SEAL (Measurement Canada approved, and factory
sealed)**

3
4
11 Special Order

A

None

(1)Specifications are limited by the operating range of the power supply if a non-aux power supply is used.

112

2013

Advanced utility metering

ION8650
Functions and characteristics (cont.)

Part numbers (cont.)
PE86044

I/O Expander

Digital/Analogue I/O P850E

P850E A 2

Example order code. Use this group of codes when ordering
the I/O Expander.
1	 Digital / Analogue I/O.
2	 I/O option.
3	 Cable option.

I/O option

A
B
C

PE86131

D
Cable option

0

Schneider Electric I/O Expander for ION8600 meters: Inputs and
Outputs for energy pulsing, control, energy counting, status
monitoring, and analogue interface to SCADA.
External I/O box with 8 digital inputs and 8 digital outputs
(4 Form A, 4 Form C)
External I/O box with 8 digital inputs and 4 digital outputs
(4 Form C) and 4 analogue outputs (0 to 20mA)
External I/O box with 8 digital inputs and 4 digital outputs
(4 Form C) and 4 analogue outputs (-1mA to 1mA)
External I/O box with 8 digital inputs and 4 digital outputs
(4 Form C) and 4 analogue outputs (two -1 to 1 mA, and two 0 to
20 mA outputs)
No cable - cables for the I/O box are no ordered as a separate
part number. Refer to part numbers: CBL-8X00IOE5FT,
CBL-8X00IOE15FT and CBL-8XX0-BOP-IOBOX under
Connector cables, below.

A-base adapters
A-BASE-ADAPTER-9
A-BASE-ADAPTER-35

Form 9S to Form 9A adapter
Form 35S to Form 35A adapter

OPTICAL-PROBE

Optical communication interface

CBL-8X00BRKOUT

5’ extension cable, mates with 24-pin male Molex connector from
the meter to the 24-pin Molex connector on the I/O expander box
(not for use with breakout panel E8, F8 & G8 form factors)
15’ extension cable, mates with 24-pin male Molex connector
from the meter to the 24-pin Molex connector on the I/O
expander box (not for use with breakout panel E8, F8 & G8 form
factors)
15’ extension cable, mates with 24-pin male Molex connector
from the meter to the 24-pin female Molex connector on the I/O
Expander box (not for use with breakout panel E8, F8 & G8 form
factors)
6’ connector cable, 24-pin male to 14-pin male Molex connector
for connecting an ION8000Series meter with breakout panel to
an I/O Expander Box

Optical communication interface
Connector cables

CBL-8X00IOE5FT

CBL-8X00IOE15FT

CBL-8XX0-BOP-IOBOX

2013

113

ION8650

Advanced utility metering

Dimensions and connections

PE86304

PE86303

ION8650 socket dimensions

PE86306

PE86305

ION8650 switchboard dimensions

114

PE86308

PE86307

I/O Expander dimensions

2013

ION8650

Advanced utility metering

Dimensions and connections (cont.)

PE86052

ION8650 suggested switchboard mounting dimensions

PE86309

ION8650 switchboard mounting

2013

115

Advanced utility metering

ION8800

PE86176

Functions and characteristics

PowerLogic™ ION8800 meter

Providing high accuracy and a wide range of features for transmission and
distribution metering, the PowerLogic ION8800 advanced revenue and power quality
meter has the flexibility to change along with your needs. The meter provides the
tools necessary to:
b manage energy procurement and supply contracts
b perform network capacity planning and stability analysis’
b monitor power quality compliance, supply agreements, and regulatory
requirements.
Integrate the PowerLogic ION8800 meter with your existing wholesale settlement
system, use StruxureWare Power Monitoring (PowerLogic ION Enterprise™)
software, or share operations data with SCADA systems through multiple
communication channels and protocols.

Applications

Transmission and distribution metering.
Settlements, customer billing, cost allocation.
Extensive power quality monitoring and analysis.
Contract optimisation and compliance verification.

Main characteristics
IEC 19-inch rack mount design to DIN 43862 standard
Use Essailec connectors with common measurement and energy pulsing pin-out to
easily retrofit into existing systems.
Accurate metering
Interconnection points on medium, high, and ultra-high voltage networks are in
compliance with IEC 62053-22/23 Class 0,2S.
Power quality compliance monitoring
Monitor compliance with international quality-of-supply standards (IEC 61000-4-30
Class A/S, EN50160, IEC 61000-4-7, IEC 61000-4-15, IEEE 1159, IEEE 519).
Power quality summary
Consolidate power quality characteristics into easily viewable reports indices.
Digital fault recording
Capture voltage and current channels simultaneously for sub-cycle disturbances.
Complete communications
Use the IEC1107 optical port or the optional communications module that supports
concurrent Ethernet, serial, and modem communications.
Multiple tariffs and time-of-use
Apply tariffs and seasonal rate schedules to measure energy and demand values for
time periods with specific billing requirements.
Alarms and I/O functions
Use up to 65 setpoints for single/multi-condition alarms and I/O functions with
response times down to 1/2 cycle.
Alarm notification via email
High-priority alarms, data logs sent directly to the user’s PC. Instant notification of
power quality events by email.
Software integration
Easily integrate the meter with StruxureWare Power Monitoring (ION Enterprise) or
other utility software; MV-90, Pacis and third-party SCADA packages.
Transformer/line loss compensation
Compensate for system losses in real time directly in the meter.
Instrument transformer correction
Save money and improve accuracy by correcting for less accurate transformers.

Part numbers(1)

PowerLogic ION8800 meters

PowerLogic ION8800A
M8800A
PowerLogic ION8800B
M8800B
PowerLogic ION8800C
M8800C
(1)
Representative part numbers only. See page 120 for complete part number descriptions.

116

2013

Advanced utility metering

ION8800
Functions and characteristics (cont.)

PE86001

Selection guide
General
Use on LV, MV and HV systems
Current accuracy
Voltage accuracy
Power accuracy
Samples/cycle

Instantaneous rms values
Current, voltage, frequency (Class 0,2S)
Active, reactive, apparent power
Total and per phase
Power factor
Total and per phase
Current measurement range
Current measurement range

Energy values
PowerLogic ION8800 meter

Active, reactive, apparent energy
Settable accumulation modes

1	
2	
3	
4	
5	
6	
7	

Current
Active, reactive, apparent
Predicted active, reactive, apparent
Demand modes (block, sliding, thermal, predicted)

Optional communications module.
Essailec connectors.
Internal modem.
Optional Ethernet communications.
Selectable RS 485 serial port.
Selectable RS 232 or RS 485 serial port.
Ground terminal.

Demand values

PE86235

b

b

0.1 %
0.1 %
0.2 %
1024

0.1 %
0.1 %
0.2 %
1024

b
b
b

b
b
b

0.001 - 10A
0.001 - 10A

0.001 - 10A
0.001 - 10A

b
b

b
b

b
b
b
b

b
b
b
b

10 ms
b

10 ms
20 (1)
63rd
40th

Power quality measurements
Detection of voltage dips (sags) and swells
Symmetrical components: zero, positive, negative
Transient detection, microseconds (50 Hz)
Harmonics: individual, even, odd, total up to
Harmonics: magnitude, phase and inter-harmonics
EN 50160 compliance
IEC 61000-4-30 class A
IEC 61000-4-30 class S
IEC 61000-4-15 (Flicker)
Configurable for IEEE 519 - 1992, IEEE1159-1995
Programmable (logic and math functions)

Data recording
Min/max logging for any parameter
Historical logs
Maximum # of records
Waveform logs
Maximum # of records
Timestamp resolution in seconds
Setpoints, minimum response time
Number of setpoints
GPS time synchronisation (IRIG-B)
Could add transient logs. COMTRADE fault records.
User configurable log memory

Display and I/O
Front panel display
Active/reactive energy pulser, LED and IEC 1107 style port
Digital pulse outputs, optional
Solid state Form A
Digital pulse outputs
Solid state Form C
Alarm relay output
Form C
Digital inputs (optional)
Display screen examples: KWh disk simulator, voltage
harmonics histogram, phasor diagram, and name plate1.

ION8800A ION8800C
ION8800B

20 (1)
63rd
50th
b
b
b (2)
b
b(1)
b

b

b

b

800(1) 640(2)
96 (1)
0.001
½ cycle
65
b
b

32
0.001
½ cycle
65
b
b

10 Mbytes

10 Mbytes

b
b

b
b

8
4
1
3

8
4
1
3

1
1
1
1
1
b

1
1
1
1
1
b

b/b
b/b
b
b
b
b
b

-/b
-/b
b
b
b
b
b

Communications
RS 232/485 port
RS 485 port
Ethernet port
IEC 1107 optical port
Internal modem
3-port DNP 3.0 through serial, modem, Ethernet and I/R ports
Modbus RTU master / slave (serial, modem and I/R ports)
Modbus TCP master / slave (via Ethernet port)
Data transfer between Ethernet and RS 485 (EtherGate)
Data transfer between internal modem, RS 485 (ModemGate)
Alarms, single or multi-condition
Alarm notification & logged data via email
Embedded web server (WebMeter)
(1) ION8800A only.
(2) ION8800B only.

2013

117

Advanced utility metering

ION8800
Functions and characteristics (cont.)

PE86003

Electrical characteristics
Type of measurement
Measurement
accuracy

Current and voltage
Power
Frequency
Power factor
Energy

Data update rate
Input-voltage
Inputs
characteristics
Measurement range

PowerLogic ION8800 with optional communications module.

Input-current
characteristics

Power supply

Dielectic withstand
Impedance
Rated nominals
Permissible overload

3320 VAC rms

Impedance
Burden
AC
DC
Burden

10 mW /phase
0.01 VA per phase (1A), 0.25 VA per phase (5 A)
85 - 240 VAC (+/- 10%), 47-63 Hz
110 - 270 VDC (+/- 10%)
Typical (without comm module): 13 VA, 8 W
Typical (with comm module): 19 VA, 12 W
Max (without comm module): 24 VA, 10 W
Max (with comm module): 32 VA, 14 W
Typical: 0.5 s to 5 s depending on configuration
Min: 120 ms (6 cycles @ 50 Hz)
2000 VAC
1 Form C digital output (250 V AC / 125 V DC,
1 A AC / 0.1 A DC max)
4 Solid state relay outputs (210 V AC / 250 V DC)
100 mA AC/DC
8 Solid state relay outputs (210 V AC / 250 V DC)
100 mA AC/DC
3 Solid state digital inputs (low-voltage inputs 15
to 75 V AC/DC; high-voltage inputs 75 to 280 V
AC/DC; 3 mA max.)
20 Hz maximum

Ride-through time

Input/outputs

True rms
1024 samples per cycle
0.1 %
0.2 %
±0.005 Hz
0.1%
IEC 62053-22/23 Class 0.2 S
½ cycle or 1 second
U1, U2, U3, Uref
57-288 LN VAC rms (99-500 LL VAC rms)

Dielectric withstand
Mechanical alarm relay
Digital outputs (Form C)
Digital outputs (Form A)
Digital inputs
Pulse rate

5 MW /phase (phase-Uref/Ground)
5 A, 1 A, 2 A
200A rms for 0.5s, non-recurring (IEC 62053-22)

Mechanical characteristics
Weight
IP degree of protection (IEC 60529)
Dimensions

6.0 kg
(6.5 kg with optional communications module)
IP51
202.1 x 261.51 x 132.2 mm

Environmental conditions
Mounting location
Maximum altitude
Limit range of operation
Specified operating temperature
Display operating range
Storage temperature
Humidity rating
Pollution degree
Installation category
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to surge waves
Conducted immunity
Damped oscillatory waves immunity
Conducted and radiated emissions

Indoor
2000 m above sea level
-25°C to +70°C
-10°C to +45°C (as per 62052-11)
-10°C to +60°C
-25°C to +70°C
5 to 95 % RH non-condensing
2

Power supply (II) Metering inputs (III)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-12
CISPR 22 (class B)

Safety
Europe
International

As per IEC 62052-11
As per IEC 60950

Utility approval

EGR, GOST, ESKOM, NMI

118

2013

Advanced utility metering

ION8800
Functions and characteristics (cont.)

PE86234

Communication
IEC 1107 optical port
RS 485 port

2/4 wires, up to 19200 bauds
Up to 57600 bauds, direct connection to a PC or modem,
protocols: ION, Modbus RTU, Modbus Master, DNP 3.0,
GPSTRUETIME/DATUM, DLMS

Communications module (optional)
RS 232/485 port
300 - 115,200 bauds (RS 485 limited to 57,600 bauds);
protocols: same as RS 485 port
Ports on the optional communications module.

Internal modem port
Ethernet port
Fiber-optic Ethernet link
EtherGate
ModemGate

300 bauds - 56000 bauds, RJ11 connector
10 BaseT, RJ45 connector, 100 m link; protocols: DNP
TCP, ION, Modbus TCP, Modbus Master, IEC 61850
10 Base FL, ST connector, 1300 nm, FO multimode with
gradient index 62.5/125 µm or 50/125 µm, 2000 m link;
protocols: same as Ethernet port
Communicates directly with up to 62 slave devices via
available serial ports
Communicates directly with up to 31 slave devices

Firmware characteristics
PE86233

High-speed data recording

Harmonic distortion
Dip/swell detection

Instantaneous

Example embedded webserver page (WebMeter) showing
realtime values.

Load profiling

Modbus Master

Waveform captures

PE86002

Alarms

Advanced security
Transformer correction
Memory
Firmware update

Up to ½-cycle interval burst recording, stores detailed
characteristics of disturbances or outages
Trigger recording by a user-defined setpoint, or from
external equipment.
Up to 63rd harmonic for all voltage and current inputs
Analyse severity/potential impact of sags and swells:
-	 magnitude and duration data suitable for plotting on
voltage tolerance curves
-	 per phase triggers for waveform recording or control
operations
High accuracy measurements with 1s or 1/2 cycle update
rate for:
-	 voltage and current
-	 active power (kW) and reactive power (kvar)
-	 apparent power (kVA)
-	 power factor and frequency
-	 voltage and current unbalance
-	 phase reversal
Channel assignments (800 channels via 50 data
recorders) are configurable for any measureable
parameter, including historical trend recording of
energy, demand, voltage, current, power quality, or any
measured parameter
Trigger recorders based on time interval, calendar
schedule, alarm/event condition, or manually.
Master up to 32 slave devices per serial channel and store
their data at programmable intervals. Use this data to
aggregate and sum energy values and perform complex
totalization.
Simultaneous capture of all voltage and current channels
-	 sub-cycle disturbance capture
-	 maximum cycles is 214,000
(16 samples/cycle x 96 cycles, 10 Mbytes memory)
-	 1024 samples/cycle
Threshold alarms:
-	 adjustable pickup and dropout setpoints and time
delays, numerous activation levels possible for a given
type of alarm
-	 user-defined priority levels
-	 boolean combination of alarms possible
Up to 16 users with unique access rights. Perform resets,
time syncs, or meter configurations based on user
priviledges.
Correct for phase / magnitude inaccuracies in current
transformers (CTs), potential transformers (PTs)
5 -10 Mbytes (specified at time of order)
Update via the communication ports

Display characteristics

Sample power quality report.

Type
Backlight
Languages

2013

FSTN transreflective LCD
LED
English

119

Advanced utility metering

ION8800
Functions and characteristics (cont.)

Part Numbers
Item

1	 Model.
2	 Feature set.
3	 Memory / form factor.
4	 Current Inputs.
5	 Voltage inputs.
6	 Power supply.
7	 System frequency.
8	 Communications.
9	 Onboard inputs/outputs.
10	Security.
11	Special order.

Description

Model

M8800 ION8800 IEC/DIN 43862 19” rack mount energy and power
quality meter.

2

Feature Set

A

PE86006

Example product part number.

Code

1

B

Class A power quality analysis, waveforms and transient capture
with 1024 samples/cycle.
Energy meter Class S EN50160 power quality monitoring.

3

Memory/Form
Factor

C
1
2

Basic tariff/energy revenue meter with sag/swell monitoring.
10 MB logging memory, Essailec connectors.
5 MB logging memory, Essailec connectors, with IEC61850
protocol

4

Current Inputs

C

(I1-I3): Configured for 5 A nominal, 10 A full scale, 14 A fault
capture, 0.001 A starting current.
(I1-I3): Configured for 1 A nominal, 10 A full scale, 14 A fault
capture, 0.001 A starting current.
(V1-V3): Autoranging (57-288 VAC L-N or 99-500 VAC L-L)
Single phase power supply: 85-240 VAC ±10% (47-63 Hz) or
110-270 VDC.
Calibrated for 50 Hz systems.
Calibrated for 60 Hz systems.
No communications module - meter includes Base Onboard I/O
and comms (see below for details).
Standard communications: 1 RS 232/RS 485 port, 1 RS 485
port (COM2) (1).
Standard communications plus 10Base-T Ethernet (RJ45), 56 k
universal internal modem (RJ11).
Standard communications plus 10Base-T Ethernet (RJ45) /
10Base-FL Ethernet Fiber, 56 k universal internal modem
(RJ11).
Standard communications plus 10Base-T Ethernet (RJ45).
Standard communications plus 10Base-T Ethernet (RJ45) /
10Base-FL (ST male Fiber Optic connection).
Standard communications plus 56k universal internal modem
(RJ11).
Base option AND 8 Form A digital outputs (2), 1 RS-485 (COM2)
port (1).
Base Option AND 8 Form A digital outputs (2), 3 digital inputs
(20-56 VDC/AC).
Base Option AND 8 Form A digital outputs (2), 3 digital inputs
(80-280 VDC/AC).
Base Option AND 1 IRIG-B time sync port (2), 1 RS-485 port
(COM2), 3 digital inputs (20-56 V DC/AC) (1).
Base Option AND 1 IRIG-B time sync port (2), 1 RS-485 port
(COM2), 3 digital inputs (80-280 V DC/AC) (1).
Password protected, no security lock.
Password protected with security lock enabled.
None.
Tropicalisation treatment applied.

E
5
6

Voltage Inputs
Power Supply

0
B

7

System
Frequency

8

Communications
module (field
serviceable)

5
6
Z0
A0
C1
D1
E0
F0
M1

9

Onboard I/O and
communications
(not field
serviceable, part
of base unit)

A
B
C
D
E

10 Security
11 Special Order
Related products
RACK-8800-RAW

0
1
A
C

IEC/DIN 34862 19” Rack with female mating voltage/current
and I/O blocks unassembled.
IEC-OPTICAL-PROBE
Optional IEC 1107 compliant Optical Probe for use with
ION8800 meters.
BATT-REPLACE-8XXX
Replacement batteries for the ION8600 or ION8800,
quantity 10.
ION-SETUP
Free configuration software for the ION8800. Ships on a CD.
(1) Channel COM2 is available on the port at the back of the meter OR on the Comm Module
(if installed). You must select which connectors your communications wiring is connected to
during meter setup.
(2) All Onboard I/O and Comms (Base Option) options include: 4 Form C solid-state digital
outputs, 1 Form C mechanical relay output, one IEC 1107 optical communications port,
two IEC 1107 style optical pulsing ports.

120

2013

Advanced utility metering

ION8800

Functions and characteristics (cont.)

Part Numbers (cont.)

ION8800 communications module for field retrofit installations

Item

Code Description

P880C

A0

PE86007

C1
D1
E0
F0
M1
Special Order
Optional ION8800 communications module.

A
C

Standard communications: 1 RS-232/RS-485 port, 1 RS-485 port
(COM2) (1).
Standard communications plus 10Base-T Ethernet (RJ45), 56k
universal internal modem (RJ11).
Standard communications plus 10Base-T Ethernet (RJ45) /
10Base-FL Ethernet Fiber, 56k universal internal modem (RJ11).
Standard communications plus 10Base-T Ethernet (RJ45).
Standard communications plus 10Base-T Ethernet (RJ45) /
10Base-FL Ethernet Fiber (ST male Fiber optic connection).
Standard communications plus 56k universal internal modem
(RJ11).
None.
Tropicalisation treatment applied.

(1) Channel COM2 is available on the port at the back of the meter OR on the Comm Module
(if installed). You must select which connectors your communications wiring is connected to
during meter setup.
Note: The part number above should conform to the following format: P880C A0 A.

2013

121

ION8800

Advanced utility metering

Dimensions and connections

PE86009

PE86008

ION8800 dimensions

PE86010

ION8800 Essailec rack dimensions

PE86011

Rack mounting the ION8800

PE86012

ION8800 communication module dimensions

122

2013

Communications

Communication interfaces
and associated services
0

	
Serial link
With communication technology, it is no longer necessary to be physically present at
the site to access information. Data is transmitted by networks.
In all architectures, the communication interface serves as the link between
the installation devices and the PC running the operating software. It provides
the physical link and protocol adaptation. Adaptation is required because the
communication systems used by the PC (Modbus via RS232 and/or Ethernet) are
generally not those used by the installation devices (e.g. the Modbus protocol via
RS485).

DB111316

Dedicated application software prepares the information for analysis under the best
possible conditions.

Modbus communication architecture.

In addition, an EGX100 in serial port slave mode allows a serial Modbus master
device to access information from other devices across a Modbus TCP/IP network.

DB111317

Switchboard-data acquisition and monitoring
make it possible to anticipate events. In this way,
they reduce customer costs in terms of
operation, maintenance and investment.

Modbus master device

EGX100
serial slave mode

Modbus communication across Ethernet network

2013

123

Communication interfaces
and associated services (cont.)

Communications

	
Ethernet link
Using modern Web technologies, the operator can access information from
monitoring and protection devices using any PC connected to the network, with all
the required security.

DB111313a

The Ethernet EGX100 gateway or the EGX300 integrated gateway-servers provide
connectivity between Modbus RS485 and Ethernet Modbus TCP/IP.

EGX100

EGX300

Ethernet communication architecture.

The services available with these technologies considerably simplify the creation,
maintenance and operation of these supervision systems.
The application software is now standardised: the web interface into the system does
not require custom web pages to be created. It is personalised by simply identifying
the components in your installation and can be used as easily as any internet
application.
The first step in this approach is the EGX300 integrated gateway-server with HTML
pages. Power management software (StuxureWare Power Monitoring Expert and
StruxureWare PowerSCADA Expert), running on a PC, provide broader coverage for
more specific needs.

124

2013

Communications

Energy Server Com'X 200
Functions and characteristics

PB112041

Ethernet GPRS data logger function
The Energy Server Com'X 200 collects and stores wages consumptions (Water,
Air, Gas, Electricity, Steam) and environmental parameters such as temperatures,
humidity, and CO2 levels in a building. Data is periodically transmitted as a report to
an Internet database server.
Data processing and display
Once received by the server, the data is ready to be processed and displayed as web
pages through web services provided by Schneider Electric, such as StruxureWare
Energy Operation and StruxureWare Energy On Line.
bb Energy Operation
bb Energy Online
or by any private energy management platform.
Energy Server Com'X 200

Architecture
Access to the web: choice of 3 media

Features
bb From a simple metering installation with 1 device to large metering systems,
Com'X 200 collects data from any Modbus TCP or serial devices, from any pulse
meters, actuators and analogue sensors
bb Automatic discovery of connected Modbus devices
bb Connectivity to the cloud through Ethernet, Wi-Fi and GPRS
bb 2 Ethernet ports to separate upstream cloud connection from field devices network
bb Protocols: HTTP, HTTPS, FTP, SMTP with Proxy management
bb Data export: Native connection to Schneider Electric Service platforms (Energy
Operation, Energy Online)– CSV file export for other database servers
bb Setup through convenient built-in web pages
bb Compliant with electrical switchboard environment (Temperature , electro
magnetic compatibility)
bb Storage of data in case of communication failure
bb Local backup of the configuration parameters
When associated with SE Services:
bb Remotely managed (firmware upgrade, configuration backup, troubleshooting,
parameters setting
bb GPRS contract management with SIM card provided
Part Numbers
Energy Server Com'X 200
Com'X 200 Ethernet data logger

EBX200

Wi-Fi USB stick

EBXA-USB-WiFi

GPRS modem with SIM card

EBXA-GPRS-SIM

GPRS modem without SIM card

EBXA-GPRS

External GPRS antenna

EBXA-ANT-5M

2013

125

Communications

Energy Server Com'X 200

Functions and characteristics (cont.)

PB112041

Ethernet GPRS data logger
Characteristics
Inputs

6 Digital inputs
Max impulse frequency 25 Hz (min duration 20ms) IEC 62053-31 Class A
Power Supply

Provided by Com'X 200: 12 V DC – 60 mA
External: from 10 to 30 V DC

2 Analogue inputs
Sensor
compatibility

PT100 – PT1000 2-wires probes (accuracy 1%)
Sensors with 4 -20 mA or 0-10 V output (accuracy
0.5%)

Power supply

Provided by Com'X 200: 24 V DC - 50 mA per input

Communication

PB112050

Energy Server Com'X 200

Meter Network

1 RS485 Modbus serial port, RJ45 connector, for 32
Modbus components maximum

Configuration / Data transfer

2 Ethernet ports RJ45 10/100 Base, DPWS ready

Ethernet 1

PoE class 3 (802.3af), DHCP client

Ethernet 2

DHCP client or server

Protocols

IPv4, IPv6 – HTTP, HTTPS, Modbus TCP/IP

USB Ports

2
For memory stick

USB port on front face

For Wi-Fi stick

USB port 2 behind cover

LED indicators

11
Power/ Boot status
GPRS modem status and signal level
Modbus communication
Ethernet communication
Wi-Fi communication mode (Access point /
Infrastructure) and status
Digital inputs status and pulse reception

Power Supply
AC

100-277 V (+/- 15%)(50-60Hz)

DC

24 V (+/- 10%)

Max power

26 W max

Mechanical
Energy Server Com'X 200 with the front face in Open position,
GPRS modem and Wi-Fi USB stick are connected.

IP

Front face IP40, terminals IP20

Dimensions (HxWxD)

91 x 144 x 65.8 mm

Weight

450 g

PB112042

Environment
Operating temperature

-25 to +70°C (-13 to +158°F)

Storage temperature

-40 to +85°C (-40 to +185°F)

Humidity

5 to 95% relative humidity (without condensation) at
+55ºC

Pollution

Class III

Safety standards / regulation

GPRS modem (antenna in folded position)

International (CB scheme)

IEC 60950

USA

UL508/UL60950

Canada

cUL (complies with CSA C22.2, no. 60950)

Europe

EN 60950

440800021

Quality Brands

PB112044

CE, UL

Wi-Fi USB stick
External GPRS antenna
126

2013

Communications

PowerLogic EGX100
Ethernet gateway
	

PE86138

Function

The EGX100 serves as an Ethernet gateway for PowerLogic system devices and
for any other communicating devices utilising the Modbus protocol. The EGX100
gateway offers complete access to status and measurement information provided by
the connected devices via PowerLogic software installed on a PC.
PowerLogic software compatibility
PowerLogic software is recommeded as a user interface because they provide access
to all status and measurement information. They also prepare summary reports. The
EGX100 is compatible with:
StruxureWare Power Monitoring Expert software
StruxureWare PowerSCADA Expert.

PowerLogic EGX100

Architecture

PowerLogic
software

Ethernet Modbus TCP/IP

EGX100 gateway

Modbus RS485 serial link

ION6200

PM800

Micrologic

Sepam

Setup
Setup via an Ethernet network
Once connected to an Ethernet network, the EGX100 gateway can be accessed by a
standard internet browser via its IP address to:
specify the IP address, subnet mask and gateway address of the EGX gateway
configure the serial port parameters (baud rate, parity, protocol, mode, physical
interface and timeout value)
create user accounts
create or update the list of the connected products with their Modbus or PowerLogic
communication parameters
configure IP filtering to control access to serial devices
access Ethernet and serial port diagnostic data
update the firmware
specify the user language.
Setup via a serial connection
Serial setup is carried out using a PC connected to the EGX100 via an RS232 link.	
This setup:
b specifies the IP address, subnet mask and gateway address of the EGX gateway
specifies the language used for the setup session.

Part numbers
Powerlogic EGX100

Schneider Electric
EGX100MG

EGX100

2013

127

Communications

PowerLogic EGX100
Ethernet gateway (cont’d)

Characteristics

PE86138

EGX100
Weight

170 g

Dimensions (HxWxD)

80.8 x 72 x 65.8 mm

Mounting

Din rail

Power-over-Ethernet (PoE)

Class 3

Power supply

24 V DC if not using PoE

Maximum burden

4W

Operating temperature

-25 to 70ºC

Humidity rating

5 to 95 % relative humidity (without condensation) at
+55ºC

Regulatory/standards compliance for electromagenetic interference
PowerLogic EGX100

Emissions (radiated and conducted)

EN55022/EN55011/FCC class A

Immunity for industrial environments:
electrostatic discharge
radiated RF
electrical fast
transients

EN 61000-6-2
EN 61000-4-2
EN 61000-4-3

surge
conducted RF
power frequency
magnetic field

EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8

Regulatory/standards compliance for safety
International (CB scheme)
USA
Canada

IEC 60950
UL508/UL60950
cUL (complies with CSA C22.2, no. 60950)

Europe
Australia/New Zealand

EN 60950
AS/NZS25 60950

Serial ports
Number of ports
Types of ports

1
RS232 or RS485 (2-wire or 4-wire), depending on
settings

Protocol

Modbus RTU/ASCII, PowerLogic (SY/MAX), Jbus

Maximum baud rate

38400 or 57600 baud depending on settings

Maximum number of connected
devices

32 (directly)
247 (indirectly)

Ethernet port
Number of ports
Type of port

1
10/100 Base TX (802.3af) port

Protocol

HTTP, Modbus TCP/IP, FTP, SNMP (MIB II)

Installation
Din rail mounting
65.8

72

35

57.9

80.8

45.2
90.7

49.5
68.3

128

2013

2.5

Communications

ION7550 RTU

PE86117

Functions and characteristics

The PowerLogic ION7550 RTU (remote terminal unit) is an intelligent web-enabled
device ideal for combined utilities metering of water, air, gas, electricity and steam
(WAGES). When combined with PowerLogic software, the ION7550 RTU offers a
seamless, end-to-end WAGES metering solution. Featuring a large, high-visibility
display and overall versatility of the PowerLogic system, the ION7550 RTU provides
extensive analogue and digital I/O choices and is a cost-effective dedicated WAGES
solution when compared to a traditional meter. The device automatically collects,
scales and logs readings from a large number of connected meters or transducers
and delivers information to one or more head-end systems through a unique
combination of integrated Ethernet, modem or serial gateways. As part of a complete
enterprise energy management solution, the ION7550 RTU can be integrated with
PowerLogic ION Enterprise software, or other SCADA, information and automation
systems.

Applications
PowerLogic ION 7550 RTU.

WAGES metering.
Data concentration through multi-port, multi-protocol communications.
Equipment status monitoring and control.
Programmable setpoints for out-of-limit triggers or alarm conditions.
Integrated utility metering with advanced programmable math functions.

Main characteristics
Increase efficiency
Reduce waste and optimise equipment operation to increase efficiency.
Easy to operate
Screen-based menu system to configure meter settings. Bright LCD display with
adjustable contrast.
Integrate with software
Easily integrated with PowerLogic or other energy management enterprises,
including SCADA systems.
Transducer and equipment condition monitoring
Versatile communications, extensive I/O points, clock synchronization, event
logging and sequence of events recording capabilities for transducer and equipment
condition and status monitoring at utility substations.
Set automatic alarms
Alarm setpoint learning feature for optimum threshold settings.
Up to 10 Mbytes of memory
For archiving of data and waveforms.
Notify alarms via email
High-priority alarms sent directly to the user’s PC. Instant notification of power quality
events by email.
Modbus Master functionality
Aggregate and store data from downstream Modbus devices using serial or Ethernet
connections.

Part numbers

ION7550 RTU
ION7550
See page 133 for order code explanations.

2013

M7550

129

Communications

ION7550 RTU

Functions and characteristics (cont.)

Selection guide
PE86124

Data recording

Min/max of instantaneous values
Data logs
Event logs
Trending
SER (Sequence of event recording)
Time stamping
GPS synchronisation (1 ms)
Memory (in Mbytes)

ION7550 RTU

10

Display and I/O
Front panel display
Pulse output
Digital or analogue inputs(max)
Digital or analogue outputs (max, including pulse output)

1
24
30

Communication

PowerLogic® ION7550 RTU.
1	
2	
3	
4	
5	
6	
7	
8	
9

I/O expansion card.
Digital inputs.
Analogue inputs.
Analogue outputs.
Communications card.
Power supply.
Form C digital outputs.
Digital inputs.
Form A digital outputs.

130

RS 485 port
RS 485 / RS 232 port
Optical port
Modbus TCP Master / Slave (Ethernet port)
Modbus RTU Master / Slave (Serial port)
Ethernet port (Modbus/TCP/IP protocol)

1
1
1

Ethernet gateway (EtherGate)
Alarms (optional automatic alarm setting

1

Alarm notification via email (Meterm@il)
HTML web page server (WebMeter)
Internal modem
Modem gateway (ModemGate)
DNP 3.0 through serial, modem, and I/R ports

2013

1
b

1

Communications

ION7550 RTU

Functions and characteristics (cont.)

Electrical characteristics
PE86117

Data update rate
Power supply
AC
DC
DC low voltage (optional)
Ride-through time
Burden
Input/outputs(1)

Standard
Optional

1/2 cycle or 1 second
85-240 V AC ±10% (47-63 Hz)
110-300 V DC ±10%
20-60 V DC ±10%
100 ms (6 cycles at 60 Hz) min. at 120 V DC
Standard: typical 15 VA, max 35 VA
Low voltage DC: typical 12 VA, max 18 VA
8 digital inputs (120 V DC)
3 relay outputs (250 V AC / 30 V DC)
4 digital outputs (solid state)
8 additional digital inputs
4 analogue outputs, and/or 4 analogue inputs

Mechanical characteristics

PowerLogic ION7550 RTU.

Weight
IP degree of protection (IEC 60529)
Dimensions
Standard model
TRAN model

1.9 kg
IP52
192 x 192 x 159 mm
235.5 x 216.3 x 133.1 mm

Environmental conditions
Operating
temperature

Standard power supply
Low voltage DC supply
Display operating range
Display, TRAN

Storage
temperature
Humidity rating
Installation category
Dielectric withstand
Electromagnetic compatibility
Electrostatic discharge
Immunity to radiated fields
Immunity to fast transients
Immunity to surges
Conducted and radiated emissions

-20 to +70ºC
-20 to +50ºC
-20 to +70ºC
-40 to +85ºC
5 to 95% non-condensing
III (2000m above sea level)
As per EN 61010-1, IEC 62051-22A(2)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
CISPR 22

Safety
Europe
IEC 61010-1
(1) Consult the ION7550 / ION7650 installation guide for complete specifications.
(2) IEC 62051-22B with serial ports only.

2013

131

Communications

ION7550 RTU

Functions and characteristics (cont.)

Communication
RS 232/485 port (1)
RS 485 port (1)
Infrared port(1)
Ethernet port
Fibre-optic Ethernet link
Protocol
EtherGate
ModemGate
WebMeter

Up to 115,200 bauds (57,600 bauds for RS 485), ION,
DNP 3.0, Modbus, GPS, EtherGate, ModemGate,
Modbus Master
Up to 115,200 bauds, ION, DNP 3.0, Modbus, GPS,
EtherGate, ModemGate, Modbus Master
ANSI type 2, up to 19,200 bauds, ION, Modbus, DNP 3.0
10BaseT, 100BaseTX. RJ45 connector, 10/100 m link
100Base FX, SC duplex connector, 1300 nm, FO
multimode with gradient index 62.5/125 µm or 50/125
µm, 2000 m link
ION, Modbus, Modbus Master, TCP/IP, DNP 3.0, Telnet
Communicates directly with up to 62 slave devices via
available serial ports
Communicates directly with up to 31 slave devices
5 customisable pages, new page creation capabilities,
HTML/XML compatible

Firmware characteristics
High-speed data recording

Load profiling

Trend curves
Alarms

Advanced security
Memory
Firmware update

Down to 5ms interval burst recording, stores detailed
characteristics of disturbances or outages. Trigger
recording by a user-defined setpoint, or from external
equipment.
Channel assignments (800 channels via 50 data
recorders) are configurable for any measurable
parameter. Trigger recorders based on
time interval, calendar schedule, alarm/event condition,
or manually.
Access historical data at the front panel. Display, trend
and continuously update historical data with date and
timestamps for up to four parameters simultaneously.
Threshold alarms:
adjustable pickup and dropout setpoints and time delays,
numerous activation levels possible for a given type of
alarm
user-defined priority levels
boolean combination of alarms is possible using the
operators NAND, OR, NOR and XOR
Up to 16 users with unique access rights. Perform
resets, time syncs, or meter configurations based on
user privileges
5 to 10 Mbytes (specified at time of order)
Update via the communication ports

Display characteristics
Integrated display
Back lit LCD, configurable screens
Languages
English
(1) All the communication ports may be used simultaneously.

132

2013

ION7550 RTU

Communications

Functions and characteristics (cont.)

Part numbers
Item

Code

Description

1

Model

7550

ION7550 device

2

Form Factor

A0

Integrated display with front optical port, 5 MB logging memory,
and 512 samples/cycle resolution.
Integrated display with front optical port, 10 MB logging memory,
and 512 samples/cycle resolution.
Transducer (no display) version, with 5 MB logging memory.
Transducer (no display) version, with 10 MB logging memory.

PE86118

4

M

5

N9

B0

Sample ION7550 RTU part number.

T0
U0
3
4

RTU option
Power Supply

N9
B

5
6

Internal use
Communications

C
9
A0
C1
D7

E0
F1
M1
7

I/O

A
D
E
H
K
N
P

8
9

Security
Special Order

2013

0
A
C

RTU option
Standard power supply (85-240 VAC, ±10%/47-63 Hz / 110-330
VDC, ±10%)
Low voltage DC power supply (20-60 VDC)
This field for internal use only
Standard communications (1 RS-232/RS-485 port, 1 RS-485
port). Integrated display models also include 1 ANSI Type 2
optical communications port.
Standard communications plus 10BASE-T/100BASE-TX
Ethernet (RJ-45), 56k universal internal modem (RJ-11).
Ethernet, modem gateway functions each use a serial port.
Standard comms plus 10BASE-T/100BASE-TX Ethernet (RJ45) and 100BASE-FX Ethernet Fiber, 56k universal internal
modem (RJ-11). Ethernet and modem gateway functions each
use a serial communications port.
Standard communications plus 10BASE-T/100BASE-TX
Ethernet (RJ-45). Ethernet gateway function uses serial port.
Standard communications plus 10BASE-T/100BASE-TX
Ethernet (RJ-45) and 100BASE-FX (SC fiber optic connection).
Ethernet gateway uses a serial port.
Standard communications plus 56k universal internal modem
(RJ-11). Modem gateway uses serial communications port.
Standard I/O (8 digital inputs, 3 Form C relays, 4 Form A solidstate outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four 0 to 1 mA analogue inputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four 0 to 20 mA analogue inputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four -1 to 1 mA analogue outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four 0 to 20 mA analogue outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four 0 to 20 mA analogue inputs and four 0 to 20 mA outputs)
Standard I/O plus Expansion I/O card (8 additional digital inputs
& four 0 to 1 analogue inputs and four -1 to 1 mA analogue
Password protected, no hardware lock
None
Tropicalisation treatment applied

133

ION7550 RTU

Communications

Functions and characteristics (cont.)

PE86021

Communications Card

P

C1

Item

Code

Description

1

Comm card

P765C

ION7550 RTU communication card for field retrofit installations

2

Type

A0

Standard communications (1 RS-232/RS-485 port, 1 RS-485
port). Front optical port support for meters with integrated
display.
Standard communications plus 10BASE-T/100BASE-TX
Ethernet (RJ-45), 56k universal internal modem (RJ-11; the
modem port is shared with the front optical port). Ethernet and
modem gateway functions each use a serial communications
port.

Example order code. Use this group of codes when ordering the
PowerLogic ION7550 RTU communication or I/O card.

C1

1	 Communications or I/O card.
2	Type.
3	 Special order.

D7

E0
F1

M1

3

134

Special order

2013

A
C

Standard communications plus 10BASE-T/100BASE-TX
Ethernet, 100BASE-FX Ethernet Fiber, 56k universal internal
modem (RJ-11; the modem port is shared with the front optical
port). Ethernet and modem gateway functions each use a serial
communications port.
Standard communications plus 10BASE-T/100BASETX Ethernet. Ethernet gateway function uses a serial
communications port.
Standard communications plus 10BASE-T/100BASETX Ethernet, 100BASE-FX Ethernet Fiber (SC fiber optic
connection). Ethernet gateway function uses a serial
communications port.
Standard communications plus 56k universal internal modem
(RJ-11; the modem port is shared with the front optical port).
Modem gateway function uses a serial communications port.
None
Tropicalization treatment applied

Communications

ION7550 RTU

Functions and characteristics (cont.)

Part numbers (cont’d)
Input/Output expansion card

Item

Code

Description

I/O card
Type

P760A
D

Expansion I/O for field retrofit installations.
Expansion I/O card with eight digital inputs, four 0 to 1 mA
analogue inputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue inputs
Expansion I/O card with eight digital inputs, four -1 to 1 mA
analogue outputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue outputs
Expansion I/O card with eight digital inputs, four 0 to 20 mA
analogue inputs & four 0 to 20 mA outputs
Expansion I/O card with eight digital inputs, four 0 to 1 analogue
inputs and four -1 to 1 mA analogue outputs
None
Tropicalization treatment applied

E
H
K
N
P
Special Order

A
C

OpenDAC rack, controllers, power supply
70LRCK16-48
OpenDAC rack. Holds up to 8 OpenLine modules to provide up
to 16 I/O points. Requires communications controller
72-MOD-4000
OpenDAC OpenDAC RS-485 serial module. Communications
controller for use in a Modbus RTU network. Supports up to 2
70LRCK16-48 OpenDAC racks
72-ETH-T000
PS-240-15W

OpenDAC Ethernet network module for use on an Modbus/TCP
Ethernet network. Supports up to 2 OpenDAC racks
85-264VAC/110-370VDC 15 Watt power supply. Required for
applying power to the racks and controllers

OpenLine digital I/O modules
70L-IAC
digital input, 120VAC
70L-IACA
digital input, 220VAC
70L-IDC
digital input, 3-32VDC
70L-IDCB
digital input, fast switching
70L-IDCNP
digital input, 15-32VAC/10-32VDC
70L-IDC5S
dry contact closure-sensing DC input
70L-ISW
input test module
70L-OAC
digital output, 120VAC
70L-OACL
digital output, 120VAC inductive loads
70L-OACA
digital output, 220VAC
70L-OACAL
digital output, 220VAC inductive loads
70L-ODC
digital output, 3-60VDC fast
70L-ODCA
digital output, 4-200 VDC
70L-ODCB
digital output, fast switching
70L-ODC5R
digital output, dry contact
OpenLine analogue I/O modules
73L-II020
analogue input, current, 0-20mA
73L-II420
analogue input, current, 4-20mA
73L-ITCJ
analogue input, temperature, J-type TC
73L-ITCK
analogue input, temperature, K-type TC
73L-ITCT
analogue input, temperature, T-type TC
73L-ITR100
analogue input, temperature, RTD
73L-ITR3100
analogue input, temperature, 3wire RTD
73L-ITR4100
analogue input, temperature, 4wire RTD
73L-IV1
analogue input, voltage, 0-1VDC
73L-IV10
analogue input, voltage, 0-10VDC
73L-IV10B
analogue input, voltage, -10 to 10VDC
73L-IV100M
analogue input, voltage, 0-100VDC
73L-IV5
analogue input, voltage, 0-5VDC
73L-IV5B
analogue input, voltage, -5 to 5VDC
73L-IV50M
analogue input, voltage, 0-50mV
73L-OI020
analogue output, current, 0-20mA
73L-OI420
analogue output, current, 4-20mA
73L-OV10
analogue output, voltage, 0-10VDC
73L-OV10B
analogue output, voltage, -10 to 10VDC
73L-OV5
analogue output, voltage, 0-5VDC
73L-OV5B
analogue output, voltage, -5 to 5VDC

2013

135

ION7550 RTU

Communications

Dimensions and connection

PE86023

PE86022

ION7550 RTU dimensions

PE86027

Front-panel mounting

PE86123

Power supply

Note: the current and voltage terminal strip (I52, I51, I42, I41, I32, I31, I22,
I21, I12, I11, V4, V3, V2, V1, Vref) is not present on the RTU.

136

2013

Software introduction and
comparison

Monitoring software

PE86230

A choice of powerful, effective solutions
StruxureWare software offerings give you desktop access to your entire electrical
network. They convert energy-related data into timely, actionable information and
give you the control to act on your decisions. The depth of different offerings makes it
easy to match a product to your goals, your business and your budget.
vv StruxureWare Power Monitoring Expert software is a complete power
management solution that helps you maximise energy efficiency, cut energy-related
costs and avoid power-quality related equipment failures and downtime.
StruxureWare software

PE86202

vv StruxureWare PowerSCADA Expert software is a power monitoring and control
solution with high reliability and performance for helping reduce the risk of power
outages and increase network-wide efficiency.

Extensive reach and flexibility
StruxureWare software forms an important part of your overall energy efficiency and
reliability solutions from Schneider Electric. A PowerLogic system can grow with your
business, giving you the level of energy intelligence and control you need to reduce
energy consumption and costs, minimise environmental impacts, and assure power
availability, uptime and safety.
Each product collects energy-related data from a variety of sources, including
PowerLogic or third-party meters and sensors. Some products offer integration with
other Schneider Electric or third-party automation systems, and other energyrelevant information feeds.

StruxureWare Power Monitoring
Expert software

PE86231

Choosing your solution
This section provides a brief overview of the types of environments and applications
each software offer is best suited for. See the following product sections for more
detail on specific product features and compatibilities. Your Schneider Electric
representative can help you design the best solution by choosing the best product
and associated services for your needs.
StruxureWare PowerSCADA
Expert monitoring and control software

Environment

Software

Industry

Buildings

Application category

Data
centres

Infrastructure

Electric
utilities

Energy
efficiency
& cost

Power
availability
& reliability

Network
protection
& control

bbb bbbb
b
bb bbbb

StruxureWare
Power Monitoring Expert
StruxureWare PowerSCADA
Expert
The number of square bullets indicates the relative strength of feature set for the noted application category.

2013

137

Software introduction and
comparison

Monitoring software

Applications for industry, buildings, data centres and infrastructure
Category

Application

StruxureWare
Power Monitoring
Expert

StruxureWare
PowerSCADA
Expert

bb
b
b
bbb
bbb
bbb
bbb
bbb
bbbb
bbb
bb
b

b

Energy usage analysis
Cost allocation

Energy efficiency
& cost

Procurement optimisation
Peak demand reduction
Demand response and curtailment
Power factor correction
Electrical distribution (ED) asset optimisation

Power availability
& reliability

Power quality analysis and compliance
ED commissioning, monitoring, and troubleshooting
ED alarming and events
ED automation and control

Network protection
& control

Load management and shedding

bb
bb
b
b
bbb
bbb
bbbb
b
bbbb
bbbb

Redundancy
High reliability and time performance

The number of square bullets indicates the relative strength of feature set for the noted application.

Applications for electric utilities
Category

Application

StruxureWare

Power Monitoring

Expert
Power quality analysis and compliance

Power availability
& reliability

Redundancy

bbbb
bbb
bbbb
bb
bbbb

High reliability and time performance

bbbb

Electrical distribution (ED) commissioning, monitoring and
troubleshooting
ED alarming and events
ED automation and control

Network protection
& control

Load management and shedding

The number of square bullets indicates the relative strength of feature set for the noted application.

138

bbb
b
bb
b
b

StruxureWare
PowerSCADA
Expert

2013

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)
Functions and characteristics

EB100263

StruxureWare Power Monitoring is an operations-level supervisory software that
provides a complete power management solution for industry, large commercial and
institutional buildings, data centres, healthcare facilities, and utilities. Engineering and
management personnel can cut energy-related costs, avoid downtime, and optimise
equipment operations by using the information provided by StruxureWare Power
Monitoring software.
StruxureWare Power Monitoring also enables tracking of real-time power conditions,
analysis of power quality and reliability, and quick response to alarms to avoid critical
situations. The software forms a layer of energy intelligence across your facility,
campus or service area, acting as a unified interface to all electrical and piped utilities.
StruxureWare Power Monitoring dashboard (sample)

Typical applications

StruxureWare Power Monitoring software has many applications:
b Monitor the facility electrical network and verify reliable operation
b Improve response to power-related events and restore operations quickly
b Analyze and isolate the source of power quality problems
b Analyze energy use to identify waste and reduce cost
b Estimate utility bills to verify accuracy and identify errors
b Allocate energy costs to departments to drive accountability and awareness
b Reduce peak demand surcharges and power factor penalties
b Idenfity excess capacity in existing infrastructure and avoid over-building
b Support proactive maintenance to prolong asset life.

EB100264

For electric utilities:
b Improve T&D network reliability
b Enhance substation automation
b Maximise the use of existing infrastructure
b Verify compliance with new power quality standards
b Analyse and isolate the source of power quality problems
b Help customers manage reliability using operational and power quality data.

Scalable, flexible architecture
Functional components

Provides operators with a rich environment to view and navigate real-time displays of
measurements and status indicators; perform power quality and reliability analysis;
historical trending; alarms; and manual control.

EB100283

Dashboard - Energy Summary

Engineering Client Applications

Web Clients
b Reports - generate or edit historical reporst for energy cost, consumption, and
power quality (requires Microsoft SQL Server Standard Edition)
b Access power monitoring system from anywhere on your network using a web
browser. Day-to-day functionality including system status, alarm response, or viewing
dashboards. Web client provides authenticated access to common functions:
b Diagrams – navigate network displays to check system status and analyze trends
b Tables – quickly compare multiple devices in your network in real-time
b Reports – generate or edit historical reports for energy cost, consumption, and power
quality
b Alarms – quickly identify alarm states in your system and investigate root causes
b Dashboards – share information from your power monitoring system with any occupant.
Engineering Workstations
Client software to allow engineers and power users access to administrative and
configuration functions of the software, and real-time display, control, and historical
analysis functions. The Engineering Workstation includes:
b Management Console – use this component to configure your StruxureWare Power
Monitoring network, including communication paths, devices and logical groups
bb Vista – build and edit custom graphical displays to represent your facility. One-line
diagrams, campus maps, equipment plan views and mimic diagrams can be created
using Vista graphical objects and imported graphic files
bb Designer – use this interface to program ION devices and create system
applications with ION Technology and Virtual ION Processors
bb Reporter - generate or edit historical reporst for energy cost, consumption, and
power quality.

2013

139

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)
Functions and characteristics

PB86097

Scalable, flexible architecture (cont.)
Data acquisition and management
bb Device Support Library
bb Virtual ION Processor
bb Site server
bb SQL ODBC-compliant databases
bb SQL Server 2008 R2. Log device data, system data and events with accurate
meter synchronisation (+/- 16 ms or +/-1 ms using GPS) for precise event
timestamping, power quality analysis and revenue billing. This data is accessible
using industry-standard database tools and you can add distributed databases
and servers for load balancing
bb OPC DA Client (included) OPC DA Server (optional).

Functions
StruxureWare Power Monitoring offers a wide range of functions:

EB100266

bb Data acquisition and integration
bb Real-time monitoring
bb Trend analysis
bb Power quality analysis
bb Alarms and events
bb Reporting
bb Dashboards
bb Manual and automated control
bb Patented ION® technology.
Data acquisition and integration
Integrate WAGES (water, air, gas, electricity, steam) metering. Native, out-of-thebox support for dozens of devices (See Supported Devices section for details).
Enables access to real-time and timestamped historical meter data, control of onboard relays and digital outputs, and server time synchronization. Communicate
over Internet, Ethernet, wireless. Interface with third-party meters, transducers,
PLCs, RTUs and power distribution or mitigation equipment through Modbus or
OPC. Add and configure direct communications with remote devices over Modbus
RTU or Modbus TCP protocols using easy-to-use device templates.
One Line example - Diagrams

EB100265

Scalable platform enables remote device and user client addition as needs grow
while maintaining original investment. Integrate other energy management or
automation systems (e.g. SCADA, BAC, DCS, ERP) through ODBC, XML, OPC,
email, FTP, CSV and PQDIF compliance; integrate with web services through
XML.

Equipment Status example - Diagrams

140

Real-time monitoring
bb View the status of your electrical network from any workstation
bb See numeric values, status indicators, gauges, and trends, all with intuitive
graphical navigation
bb Extend comprehensive out-of-the-box displays and create custom graphical
diagrams to represent your facility; one-line diagrams, campus maps, equipment
plan views and mimic diagrams can be created using embedded graphical
objects and imported graphic files
bb Quickly compare multiple devices in your network in real-time in a tabular
display
bb Choose from a library of pre-built tables, or create your own. Save your
favorites for quick access later.

2013

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)
Functions and characteristics

EB100268

Trend analysis
bb Trend any parameter to reveal demand peaks and track system-wide energy
costs.
bb Graph any combination of measured parameters
bb Plot time-series or scatter charts
bb Perform calculations, obtain statistics, and display historical data
bb Identify dangerous trends and redistribute loads
bb Optimise network capacity and avoid over-building
bb View operating parameters and determine when maintenance is required
bb Avoid peak demand surcharges and power factor penalties.

EB100269

The Diagrams web application allows users to easily view
create trend plots and analyze historical data.

Power quality analysis
bb StruxureWare Power Monitoring software allows continuous, wide-area
monitoring and data capture for power quality and reliability conditions.
bb Power quality events automatically detected by PQ-capable metering devices are
uploded to the system automatically. Analyze waveforms to determine source and
cause of issue
bb Determine if power quality events are upstream or downstream (requires
PowerLogic meter with Disturbance Direction Detection feature)
bb IEC 61000-4-30 and EN50160 compliance reporting verifies power quality
performance to international standards and allows you to quickly review power
quality indices as numeric charts or graphic profiles (requires PowerLogic meters
that support compliance monitoring)
bb Display harmonic histograms, odd/even harmonics, THD, K-factor, crest factor,
phasor diagrams, and symmetrical components
bb Plot waveforms of up to many seconds in duration, with overlays that correlate
phase-to-phase relationships between voltages, currents, and cascading failures
bb Plot sags, swells, short duration transients and other disturbance events on
industry-standard voltage tolerance curves, including ITIC (CBEMA) and SEMI
bb For any event, you can display a list of associated time-stamped incidents, then
click on any incident to see more detailed information.
Alarms and events
StruxureWare Power Monitoring software allows you to receive alerts to outages or
impending problems that could lead to equipment stress, failures, or downtime.

EB100270

The Diagrams web application allows users to view and
analyze waveforms captured by devices.

bb Quickly filter on active or unacknowledged alarms
bb Acknowledge alarms from anywhere in your facility
bb Trigger on complex conditions
bb Log all relevant data sequence of events for diagnosis
bb Flag & avert potential problems
bb Alert key personnel 24/7
bb Optimise maintenance scheduling.
Dashboards
bb Create engaging dashboard displays of your power monitoring system information
and easily share information with anyone in your facility
bb Make power monitoring information visible and engaging
bb Promote education and drive behaviour
bb Display as an interactive kiosk, on a corporate intranet, or as a slideshow on a
large wall-mounted display
bb Replace hard to maintain home-grown portals and dashboards
bb Chart or trend any quantity in your power monitoring database
bb Simple conversions into other units (e.g. dollars, emissions, normalizations, etc.)
bb Compare multiple time-ranges
bb Show impact of temperature, occupancy, or production values on energy usage
bb Add eye-catching backgrounds to enhance presentation value
bb User authentication for configuration, and both authenticated and unauthenticated
modes available for display.

2013

141

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)

EB100279

Functions and characteristics

Reporting
bb The powerful, intuitive reporting options let users see critical information exactly
how, where, and when they need it
bb Reports can be generated manually and saved as Excel, HTML and other formats
or scheduled to automatically distribute to a printer or via email
bb There are two different report engines that may be used (Reporter and web-based
Reports). See the table below to compare their features.

Feature Set

SPM7
Reporter

SPM7
Web Reporter

Energy Cost Management
Energy and Demand

n

n

Load Profile

n

n

Multi-Device Energy Usage

-

n

Energy Usage by Shift

-

n

Single Device Energy Usage

-

n

Network Management

EB100280

The Reports web application provides many different
report templates to allow users to easily display and deliver
the information they need .

Power Quality

n

n

EN50160 Compliance

n

n

IEC-61000-4-30 10 Mins

n

n

IEC-61000-4-30 2 Hours

n

n

IEC-61000-4-30 3 Secs

n

n

100ms Report

-

n

Alarm History

-

n

Generic data query

n

-

Tabular Report

-

n

Trend Report

-

n

n

n

Generic Reports

Feature Set
Excel 2003 support

Power Quality Summary Report example - Reports

142

Excel 2007 support

n

n

Excel 2010 support

n

n

Export to Excel

n

n

Export to PDF

-

n
n

Export to HTML

n

Export to XML

-

n

Email

n

n

Print

n

n

Run on a Schedule

n

n

Run on Alarm

-

n

Accessible via Web Browser

-

n

Report Configuration Save

n

n

Report Edit

n

n

Custom Reports

n

n

Data Validation

n

-

n

TOU

n

User Administration

-

n

Translatable Reports

n

n

2013

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)
Functions and characteristics

PE86125

Manual and automated control
bb Perform fast, manual control operations by clicking on-screen trigger buttons, and
operate remote breakers, relays, and other power distribution and mitigation
equipment
bb Perform manual or setpoint-triggered functions
bb Coordinate control of multiple loads, generators, relays, etc.
bb Support energy-saving applications
bb Manage distributed energy assets
bb Automate substations & reduce service time.
bb Interoperability
bb Integrate all energy management and automation systems (SCADA, BAC, DCS,
ERP, etc.)
bb Share data with third-party SCADA, automation, and accounting systems
bb Comply with ODBC, OPC, and PQDIF standards

Custom graphics screen example - Diagrams

Patented ION technology
StruxureWare Power Monitoring software and a variety of PowerLogic ION metering
products feature the unique ION architecture. This modular, flexible architecture
offers extensive customisation of functionality using a simple .building block.
approach. The technology uniquely addresses advanced monitoring and control
applications and adapts to changing needs, avoiding obsolescence.

EB100281

Software is available in English, French, Spanish, German, and Chinese. Other
languages may be available - contact your Schneider Electric representative.
Part numbers*
New systems &
add-ons

IE7PRIMARY

StruxureWare Power Monitoring Primary server
(DVD, includes all available languages)
Individual Device Licence for High-End Devices.
Compatible with all device types.
Individual Device Licence for Mid-Range Devices.
Compatible with Mid- and Entry-range devices.
Individual Device Licence for Entry-Range
Devices. Compatible with Entry range devices
Engineering Client Licence (DVD) - Access to
Management Console, Vista, Designer, Reporter
and Web applications; one licence per user.
Web Client Licence - Access to Diagrams, Tables,
Alarms, Reports, Dashboard; one licence per user
Unlimited Licence for unlimited number of users
(Engineering or Web applications); mandatory for
public displays or Internet hosting.

(1)

IE7DLS

(1)
IE7DLM )

IE7DLE

(1)

IE7ENGCLIENT

(2)

IE7WEBCLIENT
IE7UNLCLIENT
Campus map example - Diagrams

(2)

(3)

IE7OPCSERVER

OPC DA Server for StruxureWare Power Monitoring

IE7SECONDARY
Upgrades from
earlier versions

Secondary Server for StruxureWare Power Monitoring
(4)

IE7PRIMARYUPG
IE7DLSUPG

StruxureWare Power Monitoring UPGRADE
software (DVD, includes all available languages)
Upgrade DL-S device licence

(1)

IE7DLMUPG

(1)

Upgrade DL-M device licence

(1)

IE7DLEUPG
(2)
IE7ENGCLIENTUPG
(2)

IE7WEBCLIENTUPG

(3)

IE7UNLCLIENTUPG

IE7SECONDARYUPG
Technical
documentation

CD-TECHDOC

Upgrade DL-E device licence
Engineering Client Upgrade Licence - Access to
Management Console, Vista, Designer, Reporter
and Web applications; one licence per user.
Web Client Upgrade Licence - Diagrams, Tables,
Alarms, Reports; one licence per user
Unlimited Client Upgrade Licence for unlimited
number of users (Engineering or Web applications);
mandatory for public displays or internet hosting.
Secondary Server Upgrade for StruxureWare
Power Monitoring
Latest version of technical documentation for
StruxureWare Power Monitoring

(1) An appropriate device licence (DL-S, DL-M, DL-E) is required for each device added to your system in Management
Console. A minimum order value may apply.
(2) Each user of the system must have an appropriate Client Licence. An Engineering Client Licence permits access to
Management Console, Vista, Designer, Reporter and the Web applications.This includes remote access through Terminal
Services or other methods. A Web Client licence only permits access to web applications - Dashboards, Diagrams, Tables,
Alarms, Reports. Contact your sales representative for more information.
(3) An Unlimited Client Licence provides access to all software applications (including Management Console, Vista,
Designer, Reporter, Dashboards, Diagrams, Tables, Alarms, Reports) for an unlimited number of users. This type of
Client License is required when accounting for individual users is not possible (applications available in public areas,
internet hosting, etc). Engineering Client or Web Client Licenses are not required when an Unlimited Client License is in
place. Please note that performance limitations of your installation may affect the practical number of concurrent users.
(4) Upgrade part numbers apply to PowerLogic ION Enterprise 5.6 and later, and PowerLogic SMS v4.x. Technical
upgrades from earlier versions may be possible - contact your sales representative for more information.
* Please consult a Schneider Electric sales representative for full pricing and part numbers information.

2013

143

Monitoring software

StruxureWare Power Monitoring 7

(PowerLogic ION Enterprise™)
Functions and characteristics
Features

Included
b
b
b
b
b
b
b
b
b

Dashboards
Diagrams
Tables
Alarms
Reports*
Modbus Device Importer
Designer
EGX300 Log File Importer
SQL Server 2008 R2 Express Edition
SQL Server 2008 R2 Standard Edition
OPC client
OPC server

b
-

Optional
b
b

Minimum system requirements
Please consult your local Schneider Electric representative for complete system
requirements and commissioning information for StruxureWare Power Monitoring.

*Note: There are two different report engines that may be used: Reporter and web-based
Reports. The Reporter application is always available as an Engineering Client tool. The web-based Reports
feature is only available when the system has been installed using SQL Server Standard Edition.

EB100282

Supported devices
PowerLogic power and energy meters:

bb ION8800 Series
bb ION8650 Series
bb ION7650/7550
bb ION7550RTU
bb ION6200
bb PM5350
bb PM3000 Series (PM3250, PM3255)
bb PM1200
bb PM800 Series (PM810, PM820,
PM850, PM870)
bb PM700 Series (PM710, PM750)

bb PM600 Series (PM600, PM620,
PM650)
bb PM210
bb PM9C
bb DM6200
bb DM6300
bb EM1200
bb EM5600
bb iEM3000 Series (iEM3150,
iEM3155, iEM3250, iEM3255)
bb EM1200 Series

PowerLogic circuit monitors:

bb CM2000 Series (CM2050, CM2150, CM2250, CM2350, CM2450)
bb CM3000 Series (CM3250, CM3350)
bb CM4000 Series (CM4150, CM4250, CM4000T).
PowerLogic branch circuit power meters:

bb BCPM (A, B, C models).
Circuit breaker trip units

bb Micrologic A, E, P and H devices
bb Micrologic Compact NSX Type A and Type E.
Protective relays

bb Sepam Series 10, 20, 40, 48, 80.
Insulation monitors

bb Vigilohm IM20.
Power Measurement power and energy meters:

bb ION8000 Series (ION8300, ION8400, ION8500, ION8600, )
bb ION7000 Series (ION7500, ION7600, ION7700)
bb ION7500RTU
bb ION7300 Series (ION7300, ION7330, ION7350)
bb ACM3000 Series (ACM3300 , ACM3710, ACM3720).
PLCs for WAGES applications

bb Modicon Momentum M1 - TR (A8, D10, D16)
bb Twido Modular PLC (D12,D28, D44).
Communications Interfaces

bb Acti9 Smartlink.

“Limited Edition” (LE) drivers available for download from website

bb Modbus-compatible devices
bb Other devices through OPC.

144

2013

StruxureWare PowerSCADA Expert

Monitoring software

Functions and characteristics

PBS100001

StruxureWare PowerSCADA Expert (previously known as PowerLogic SCADA) is a
reliable, flexible and high performance monitoring and control solution designed to
reduce outages and increase power efficiency. It is built to handle user requirements
from the smallest to the most demanding enterprises, while still providing high time
performance and reliability. Easy-to-use configuration tools and powerful features
enable faster development and deployment of any size of application.
Object-based, standard graphics and symbols provide operators with an interactive
and user-friendly interface. Intuitive commands and controls increase efficiency
of operators to interact with the system interface. StruxureWare PowerSCADA
Expert controls your system with high reliability, performance and data integrity
through the use of advanced architectures, such as hot/warm redundant I/O device
configurations, self-healing ring communications, and primary and standby server
configurations. Comprehensive user-based security is integrated into all interface
elements, ensuring a secure control system.
StruxureWare PowerSCADA Expert.

Typical applications

StruxureWare PowerSCADA Expert software has the following applications:
bb Network protection and control
bb Operate distribution network safely and reliably
bb Improve continuity of electrical service
bb Equipment monitoring and control
bb Energy availability and reliability
bb Verify the reliable operation of equipment
bb Support proactive maintenance to prolong asset life.

PE86178

ECS Engineer workstation

ECS Operator workstation

System architecture

Optical converters
Master clock

Human machine interface (HMI)
StruxureWare PowerSCADA Expert offers secure, operator-dedicated, multi-user
data and control access through a local server interface, full control client and also
through web clients.

Redundant ECS server

Ethernet optical ring
Optical converter

Optical converter

PLC
EGX 400

Clock

PLC

EGX 400

Islanding
PLC

EGX 400

Remote I/O
rack

Compatible devices

Compatible devices
Compatible devices

Functional components of StruxureWare PowerSCADA Expert.

Main components
bb SCADA software
vv Drivers, libraries and communication tools.
vv Use these components to configure your SCADA network, including
communication paths, devices and logical groups.
bb Communication hardware
vv Includes gateways, PLCs, RTUs, switches, etc.
vv Redundant, self-healing ring, double-ring technology
bb Design reference guide
vv Design of architectures to achieve time performance & reliability
bb Schneider Services
vv Pro-active assistance to facility maintenance team for sensitive electrical
distribution maintenance operations.
Data acquisition and management
vv Redundant I/O server
vv Hot/warm standby: data acquisition is never interrupted even if one server fails.
vv Distributed, multiple server architecture
vv I/O servers, with corresponding configuration tools
vv IEC61850 compliant databases
vv Designed for interoperable exchange of data for distributed substation automation
systems and third-party devices.
vv Supports data import/export with compliant devices and systems.

2013

145

Monitoring software

StruxureWare PowerSCADA Expert
Functions and Characteristics (cont.)

Functions
PB100005

StruxureWare PowerSCADA Expert offers a wide range of functions:
bb Data acquisition and integration.
bb Alarms and events with 1ms timestamp support.
bb Electrical distribution control.
bb Real-time monitoring.
bb Analysis.

PB100004

Monitor the whole communications network. Connect to
switches, IEDs, RTUs, control and monitoring devices.
Extract values for dynamic power and energy readings.

View all alarm conditions at a glance.

Data acquisition and integration
Integrate electrical distribution devices with PLCs, RTUs, Controllers and other
intelligent energy devices. Native, out-of-the-box support for all SEPAM Series 20,
40, 80, and SEPAM 2000 (S36), Micrologic 5.0P and 6.0P, Micrologic A, Micrologic
A FW v2, Micrologic H, PowerLogic CM4000 series, PM800 series, PM710, PM750,
ION7650 and BCPM/BCM42. Enables access to meter data, control of protection
relays and digital outputs and remote configuration. Interface with PLCs, RTUs and
power distribution equipment. Quickly add and configure devices with easy-to-use
Profile Wizard and Profile Editor. Scalable platform enables remote devices and
user clients to be added as needs grow while maintaining your original investment.
Integrate with other energy management or automation systems through Modbus
TCP/IP.

Alarms and events
StruxureWare PowerSCADA Expert software allows you to receive alerts to outages
or impending problems that could lead to equipment stress, failures, or downtime.
Configure alarms to trigger on events, power thresholds, or equipment conditions.
The software logs complete information on an event, including related coincident
conditions, all with accurate 1ms timestamping.
bb Easily discriminate between alarm criticality levels.
bb High speed alarm response. Capture and log every single alarm or event.
bb Organise, filter and print by any alarm property. Configure specific alarm
occurrences to change symbol color or flash an icon on a page.
bb View the five most recent alarms from every page, providing detailed information
in easy-to-understand formats.
bb Event log for all PC-based and on-board field events, alarms.
bb Easily configure to annunciate based on alarm type.
Standards supported
bb IEC61850
bb DNP3

PBS100006

Electrical distribution control
Perform fast, manual control operations by clicking on-screen trigger buttons, and
operate remote breakers, protection relays, and other power distribution equipment.

System Supervision displays such as this let the user see the
real-time status of all devices and provide detailed information
for best decision making.

146

2013

Monitoring software

StruxureWare PowerSCADA Expert 
Functions and Characteristics (cont.)

PBS100002

Real-time monitoring
View all distribution points across your network. Secure display of real-time power
and energy measurements, historical trends and data logs, alarm conditions,
equipment status (on/off, temperature, pressure, etc.), control triggers, and
analysis tools.
bb Single line diagrams with real-time monitoring and control of devices, objects
and distribution points. Point-and-click navigation reveals deeper layers of detail.
bb IEC- and ANSI-standard symbols and templates that are fully animated and
interactive, to blend control and display functionality.
bb Dynamic colouring is easily configured using the default set or user-defined
colours and voltage levels.
bb True color, easy-to-use human machine interface (HMI) that provides operators
with intuitive and consistent screens.
Desktop access to power system information from any
department, building or of relevant, realtime data.

PBS100003

Analysis
Trend and analyse on any measured parameter, allowing operators to recognise
patterns that may lead to disturbances. Display millisecond-accurate historical
alarms and trends to help determine the sequence of events or root cause
analysis. Unite trend and alarm data for sophisticated disturbance views and
analysis. User-defined colour coding and overlays clearly highlight data series,
time ranges, thresholds and limits. View waveforms via ActiveX tool (waveforms
from the ION8650 are captured via IEC61850 only). Record, save or export trends
to archives.

Optimise equipment use by maximising capacity or balancing
loads. Reveal critical trends, expensive processes or energy
waste.

PE86189

Configuration tools
StruxureWare PowerSCADA Expert is supplied with a package of configuration
tools designed to make set up uniquely easy and quick.
bb Designed to help make project set up and network configuration fast and easy.
bb Profile Editor provides standard device types and their associated profiles
and allows engineers to easily customise the profiles of the devices specific to
the project. New export/import capability allows easier sharing of profiles.
vv Standardized tags per device profile (configurable), XML file.
vv Creates, adds, edits device types, tags and profiles.
bb Profile Wizard provides a standard interface for quick SCADA data base
generation:
vv Instantiation of devices, on a per object basis.
vv Creates tags, trends, alarms and events when devices are added to system.
vv Batch editing supported by automation interface.
Use the Profile Editor and Profile Wizard to design and configure
your network. Customise device profiles specific to your project.

2013

147

StruxureWare PowerSCADA Expert

Monitoring software

Functions and Characteristics (cont.)

Device Wizard

PE86190

Device Profile Editor

Database

Add/configure
single device
PowerLogic SCADA

Add/configure
multiple devices

Automation interface
(Spreadsheet)

rs

Drive

Generators

PLCs

Compatible devices

PowerLogic SCADA files and data flow configuration steps.

Minimum system requirements
Please consult your local Schneider Electric representative for complete system
requirements and commissioning information for StruxureWare PowerSCADA
Expert. The following are minimum support requirements with factory default
settings.
bb Runs on standard PCs or servers, and supports the following operating systems:
vv Windows 2003 Server (32-bit)
vv Windows XP Professional (32-bit)
vv Windows Vista Business
vv Windows XP SP3 (32-bit)
vv Windows 2003 Server SP2 (32-bit)
vv Windows Vista SP2 (32- and 64-bit)
vv Windows Server 2008 SP2 (32- and 64-bit)
vv Windows 7 (32- and 64-bit)

PE86191

Supported devices and protocols
PowerLogic electrical network protection:
bb Sepam series 20, 40, 80, SEPAM 2000 (S36)
PowerLogic power and energy meters:
bb PM800 series
bb PM710, PM750
bb CM4000 series
bb ION 7650
Circuit breaker control units
bb Micrologic 5.0P
bb Micrologic 6.0P
bb Micrologic A, and Micrologic A FW v2
bb Micrologic H
Branch circuit monitors
bb BCPM
bb BCM42
Native device protocol support
bb IEC 61850 Edition 1 (New)
bb DNP3
bb ModBus TCP/IP
bb RS-485
bb SNMP
Optional support
bb IEC 80750-5-104
bb BCM42
Data access (Other protocols support)
bb OPC DA Version 1 & 2 Client Server
bb ODBC
Other:
bb Any PLC or other device via Modbus protocol

148

2013

Monitoring software

StruxureWare PowerSCADA Expert
Functions and Characteristics (cont.)

Part Numbers
Description
StruxureWare PowerSCADA Expert Software and one (1) key in a box
PowerLogic SCADA box with DVD and USB key
PowerLogic SCADA box with DVD and Parallel key
PowerLogic SCADA additional USB key
PowerLogic SCADA additional Parallel key

PLS109922
PLS109912
PLS109921
PLS109911

Server Licences (includes server Control Client)

Server Licence

75

PLS101110

150

PLS101111

500

PLS101112

1500

PLS101113

5000

PLS101114

15000

PLS101115

Unlimited

PLS101199

75

PLS102010

150

PLS102011

500

PLS102012

1500

PLS102013

5000

PLS102014

15000

PLS102015

Unlimited

PLS102099

Redundant (floating licence)

PLS102088

75

PLS102210

150

PLS102211

500

PLS102212

1500

PLS102213

5000

PLS102214

15000

PLS102215

Unlimited

PLS102299

Redundant (floating licence)

PLS102288

Independent of points

PLS103099

Redundant (floating licence)

PLS103088

Independent of points

PLS103299

Redundant (floating licence)

PLS103288

75 - 150

PLS101110-11

150 - 500

PLS101111-12

500 - 1500

PLS101112-13

1500 - 5000

PLS101113-14

5000 - 15000

PLS101114-15

15000 - unlimited

PLS101115-99

75 - 150

PLS102010-11

150 - 500

PLS102011-12

500 - 1500

PLS102012-13

1500 - 5000

PLS102013-14

5000 - 15000

PLS102014-15

15000 - unlimited

PLS102015-99

75 - 150

PLS102210-11

150 - 500

PLS102211-12

500 - 1500

PLS102212-13

1500 - 5000

PLS102213-14

5000 - 15000

PLS102214-15

15000 - unlimited

PLS102215-99

Control Client Licences

Control Client Licence

Web Control Client Licences

Web Control Client Licence

View Only Client Licences
View Only Client Licence
Web View Only Client Licences
Web View only Client Licence
Point Expansions

Server licence point expansion

Control licence point expansion

Web control licence point expansion

2013

149

Monitoring software

StruxureWare PowerSCADA Expert
Functions and Characteristics (cont.)

Part Numbers
Description
Key Reprogramming
Reprogramming fee - Authorisation Code1

PLS109401

Tech Support2
Silver 1 year support, first year, compulsory

PLS109102

Silver 1 year support, renewal

PLS109122

Gold 1 year support, first year

PLS109103

Gold 1 year support, renewal

PLS109101

Service Levels
Level

Service Description
No access to a new version;
Tech support business hours;
Hot Fix
12 months access to a new version;
Tech support business hours;
Hot Fix

Silver
Gold

1: Reprogramming fee is required for any key modifications: addition of a new licence or point
expansion
2: First year Tech Support is not included in licence. First year Tech Support is compulsory.
Subscription level is not available for 1st year, minimum level is Silver or above. Support
reinstatement applies 3 year backwards maximum.

150

2013

2013

151

152

2013

2013

153

154

2013

2013

155

35, rue Joseph Monier
CS 30323
F - 92506 Rueil-Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776 €

http://www.schneider-electric.com
PLSED309005EN

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
Printed on ecological paper

Layout: Schneider Electric
Photos: Schneider Electric
Printing:
05-2013

ART837220 © 2013 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Create Date                     : 2013:05:17 14:47:51-07:00
Creator                         : Adobe InDesign CS5 (7.0.4)
Modify Date                     : 2013:05:28 09:16:14-07:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Metadata Date                   : 2013:05:28 09:16:14-07:00
Creator Tool                    : Adobe InDesign CS5 (7.0.4)
Page Image Page Number          : 1, 2
Page Image Format               : JPEG, JPEG
Page Image Width                : 256, 256
Page Image Height               : 256, 256
Page Image                      : (Binary data 9688 bytes, use -b option to extract), (Binary data 7129 bytes, use -b option to extract)
Instance ID                     : uuid:9828d57f-a69c-490b-8d02-6d6a77cfff44
Document ID                     : xmp.did:D3C2FB1628B7E2119FA4FF30D34869CE
Original Document ID            : adobe:docid:indd:4f930914-376b-11df-987a-928eb614efb9
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:69D2510C28B7E2119FA4FF30D34869CE
Derived From Document ID        : xmp.did:2BD57A7F082068118083EA6E69E5CE87
Derived From Original Document ID: adobe:docid:indd:4f930914-376b-11df-987a-928eb614efb9
Derived From Rendition Class    : default
History Action                  : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved
History Instance ID             : xmp.iid:32911A74072068118083EA6E69E5CE87, xmp.iid:33911A74072068118083EA6E69E5CE87, xmp.iid:DDFE895A082068118083EA6E69E5CE87, xmp.iid:DEFE895A082068118083EA6E69E5CE87, xmp.iid:2BD57A7F082068118083EA6E69E5CE87, xmp.iid:E475D718092068118083A3E4ECF6A2CA, xmp.iid:2839140E752168118083EC5E0BBE2699, xmp.iid:F0CC17A0102068118083DA831038235A, xmp.iid:92439C2EA82068118083DA831038235A, xmp.iid:1386D8B8D12068118083DA831038235A, xmp.iid:59469038582168118083DA831038235A, xmp.iid:F26D739A8E2168118083DA831038235A, xmp.iid:965D3C91912168118083DA831038235A, xmp.iid:1494494CA42168118083DA831038235A, xmp.iid:70D356F9192368118083DA831038235A, xmp.iid:CBB8B1B41A2368118083DA831038235A, xmp.iid:0F9241D12C2368118083DA831038235A, xmp.iid:B8557FBE2D2368118083DA831038235A, xmp.iid:C25B6F11352368118083DA831038235A, xmp.iid:03A00EE83A2368118083DA831038235A, xmp.iid:6C9B76A14D2368118083DA831038235A, xmp.iid:3E30C6E7BA2368118083DA831038235A, xmp.iid:BEA4868EBF2368118083DA831038235A, xmp.iid:D5883180C02368118083DA831038235A, xmp.iid:29EA1B74072068118083D3F34A4019F2, xmp.iid:1B6A54301D20681180838CF4714479A6, xmp.iid:20D2B5951D20681180838CF4714479A6, xmp.iid:EC56C3BA1D20681180838CF4714479A6, xmp.iid:44CA1D461F20681180838CF4714479A6, xmp.iid:69D2510C28B7E2119FA4FF30D34869CE, xmp.iid:D3C2FB1628B7E2119FA4FF30D34869CE, xmp.iid:D4C2FB1628B7E2119FA4FF30D34869CE, xmp.iid:C9AA8DD82AB7E2119FA4FF30D34869CE, xmp.iid:EC17D4036BB7E2119FA4FF30D34869CE, xmp.iid:D664D26870B7E2119FA4FF30D34869CE, xmp.iid:2A49CD6771B7E2119FA4FF30D34869CE, xmp.iid:648A93E4CEB8E211951AE04C265012BC, xmp.iid:44917902F7B8E21192BA8FE6BBD6D8A4, xmp.iid:B4F377AE96B9E2119C03A58D5329291F, xmp.iid:2DACEC2697B9E2119C03A58D5329291F, xmp.iid:EEFF9D2AADB9E21197DCAC388649AB68, xmp.iid:BCDD484CAEB9E21197DCAC388649AB68, xmp.iid:BAEFDAECAFB9E21197DCAC388649AB68, xmp.iid:1EEEF76EBBB9E21197DCAC388649AB68, xmp.iid:4D7C365DE1BCE211BBAEB43DDBFE9BF1, xmp.iid:70061101A0BDE2119AF9D1AEF262E1D1, xmp.iid:2CD58D51A6BDE2119AF9D1AEF262E1D1, xmp.iid:DBBA791334BFE2118D7DDB803E5AF62B, xmp.iid:10904B0536BFE2118D7DDB803E5AF62B, xmp.iid:9AA8526C38BFE2118D7DDB803E5AF62B, xmp.iid:AFD67B983ABFE2118D7DDB803E5AF62B, xmp.iid:E1146A4A3BBFE2118D7DDB803E5AF62B
History When                    : 2013:04:23 12:02:02-07:00, 2013:04:23 12:02:02-07:00, 2013:04:23 12:08:28-07:00, 2013:04:23 12:09:30-07:00, 2013:04:23 12:09:30-07:00, 2013:04:23 12:33:19-07:00, 2013:04:25 08:35:33-07:00, 2013:04:28 17:28:40-07:00, 2013:04:29 11:33:35-07:00, 2013:04:29 16:30:57-07:00, 2013:04:30 08:33:45-07:00, 2013:04:30 15:03:02-07:00, 2013:04:30 15:24:15-07:00, 2013:04:30 17:38:20-07:00, 2013:05:02 14:13:16-07:00, 2013:05:02 14:18:30-07:00, 2013:05:02 16:28:09-07:00, 2013:05:02 16:34:47-07:00, 2013:05:02 17:27:13-07:00, 2013:05:02 18:09:01-07:00, 2013:05:02 20:23:03-07:00, 2013:05:03 09:25:17-07:00, 2013:05:03 09:58:35-07:00, 2013:05:03 10:05:20-07:00, 2013:05:03 10:33:50-07:00, 2013:05:03 13:16:28-07:00, 2013:05:03 13:19:18-07:00, 2013:05:03 13:20:20-07:00, 2013:05:03 13:31:24-07:00, 2013:05:07 08:09-07:00, 2013:05:07 08:09:18-07:00, 2013:05:07 08:19:50-07:00, 2013:05:07 08:29:02-07:00, 2013:05:07 16:08:22-07:00, 2013:05:07 16:47-07:00, 2013:05:07 16:54:07-07:00, 2013:05:09 10:35:51-07:00, 2013:05:09 15:23:01-07:00, 2013:05:10 10:25:59-07:00, 2013:05:10 10:29:21-07:00, 2013:05:10 13:06:57-07:00, 2013:05:10 13:15:03-07:00, 2013:05:10 13:26:42-07:00, 2013:05:10 14:49:04-07:00, 2013:05:14 14:58:09-07:00, 2013:05:15 13:42:48-07:00, 2013:05:15 14:28-07:00, 2013:05:17 13:55:16-07:00, 2013:05:17 14:09:11-07:00, 2013:05:17 14:26:23-07:00, 2013:05:17 14:41:56-07:00, 2013:05:17 14:46:54-07:00
History Software Agent          : Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0
History Changed                 : /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata
Doc Change Count                : 1710
Format                          : application/pdf
Producer                        : Adobe PDF Library 9.9
Trapped                         : False
Page Count                      : 156
EXIF Metadata provided by EXIF.tools

Navigation menu