Powerwave Technologies 5JS0097 RF Power Amplifier Frame User Manual 044 05287 PAF 0813 E0 001
Powerwave Technologies Inc RF Power Amplifier Frame 044 05287 PAF 0813 E0 001
Contents
- 1. Users Manual Part 1
- 2. Users Manual Part 2
Users Manual Part 2
PAF-0813-E0-001 Installation Instructions NOTE DO NOT remove metallic tape at frame top when connecting to Halo ground system. Removing tape voids PAF frame warranty. To Halo Ground To Halo Ground Metallic Tape Ground Sticker Figure 3-4 Frame to Halo Ground Connection Example RS-485 Alarm Interface The RS-485 alarm interface provides the BTS controller with system status via a 1 byte protocol. The baud rate is fixed at 15.6 K. Table 3-6 lists the available alarm states.. Table 3-4 RS-485 Alarm States AlarmState Definition No Alarm Minor Alarm Any or all fans fail Major Alarm Any one MCPA module disabled Critical All MCPA modules disabled MCPA Install the MCPAs as instructed in Table 3-7. CAUTION: REPLACE THIS SECTION WITH UPDATE Slamming or forcing the MCPA into the subrack may cause the pins on the 21-pin D-Sub connector to become recessed or broken. 044-05287 Rev A 3-5 Initial Start-Up and Power Setting Procedures PAF-0813-E0-001 Table 3-5 MCPA Installation Procedure Step Action 1. Inspect MCPA 21-pin connector. Verify all pins are straight, no pins are recessed, and alignment shield is not bent 2. Set MCPA power OFF/ON/RESET switch to OFF 3. Rotate MCPA quarter-turn fasteners counter-clockwise to unlock position shown in Figure 3-8 4. Install MCPA(s) into subrack. To secure each MCPA, rotate quarter-turn fasteners clockwise to lock position as shown in Figure 3-8 Quarter-Turn Fasteners Unlocked Locked LED Status Indicator RF Switch: RESET ON OFF Alcatel Lucent Alcatel Lucent ON ON OFF OFF Figure 3-5 MCPA Front Panel Features Initial Start-Up and Power Setting Procedures The following paragraphs provide initial startup, and power setting procedures. Initial Start Up To complete initial startup, perform the instructions listed in Table 3-8. CAUTION: Excessive input power may damage MCPA. Before applying power, ensure MCPA inputs and outputs are properly terminated at 50 ohms. Do not operate MCPA without a load attached. Refer to Chapter 5 for input power requirements. Table 3-6 Initial Startup Procedure Step 3-6 Action 1. Verify all input and output cables are properly connected 2. Turn on +27 VDC supply to MCPA 3. Set all MCPA front panel OFF/ON/RESET switches to ON (middle) position 4. Allow MCPAs to warm up for at least two minutes before taking power readings 044-05287 Rev A Chapter 4 Maintenance Introduction This chapter contains periodic maintenance and performance test procedures for the PAF-081X-P0-001 MultiCarrier Power Amplifier (MCPA) system. NOTE Do not break seals on equipment under warranty or warranty will be null and void. Do not return equipment for warranty or repair service until factory shipping instructions are received. Periodic Maintenance Periodic maintenance requirements are listed in Table 4-1, as well as the intervals at which the tasks should be performed. Table 4-1 Periodic Maintenance Task Interval Action Inspection: Cables and Connectors Cleaning: Fans and Equipment 12 Months Inspect signal and power cables for frayed insulation. Check RF connectors to be sure that they are tight Optional Antenna VSWR sweep Clean as required depending on equipment operating environment Troubleshooting The following paragraphs contain a list of problems that could occur and a few suggested actions that can correct the problem. If the suggested corrective action does not eliminate the problem, please contact your Powerwave field representative or the factory for further instructions. 044-05287 Rev A 4-1 System Component Part Numbers PAF-0813-E0-001 Clearing Alarm Faults Setting the MCPA front panel OFF/ON/RESET switch to RESET can clear many alarm faults. An attempt to reset the MCPA should be your first course of action. 24-Hour technical support service is available at our main phone number 888-797-9283 or 714-466-1000; select the "System Operator Technical Support" option to receive assistance from Powerwave's Applications Support Group. Refer to Table 4-2 for troubleshooting suggestions. Table 4-2 Troubleshooting Problem Suggested Action MCPA Inoperative (MCPA front panel LED red) 1. Set MCPA OFF/ON/RESET toggle switch momentarily to RESET 2. Check for proper power supply voltage 3. Verify all RF connections 4. Contact your field representative or factory System Component Part Numbers Table 4-3 lists the model/part numbers for ordering individual system components and manuals. Table 4-3 System Components Part Number List Model/Part Number Manual Number Description System Maximum Quantity G3L-830-160 160 Watt, 850 MHz MCPA 12 800-09666-001 Subrack Fan Assembly MCR40830-1-4 Subrack, 4-way combined 800-07829-002 Panel, blank, MCPA FIL-0830A Filter, 850 MHz, A-band FIL-0830B Filter, 850 MHz, B-band 800-11185-600 Panel, Circuit Breaker 1002530 Circuit Breaker, 50 A 12 1002529 Circuit Breaker, 15 A 700-18766-001 Cable, RF, 7/16 DIN-R-MA 700-18767-001 Cable, Filter, DB-15 to DB-15 700-18133-100 Cable, Filter, DC 2 per subrack as required Field Replacement Procedures The following parts and modules can be replaced in the field on site by a qualified technician with experience maintaining RF power amplifiers and similar equipment: 4-2 ❑ MCPA ❑ Fiter ❑ Cooling Fans ❑ Circuit Breaker Panel ❑ Subrack 044-05287 Rev A PAF-0813-E0-001 Field Replacement Procedures MCPA To replace an MCPA module, shown in Figure 4-1, perform the steps in Table 4-3. CAUTION: To prevent damage to MCPA rear connector, support rear of MCPA when removing from subrack. The MCPA weight is approximately 20 lbs (9.1 kg). Table 4-4 MCPA Removal and Replacement Procedure Step Action 1. Set MCPA front panel OFF/ON/RESET switch to OFF 2. Rotate MCPA module quarter-turn fasteners counterclockwise 3. With steady even pressure, use handle on front of MCPA to pull module out of enclosure as shown in Figure 4-1 4. Replace MCPA module in reverse order of removal Alcatel Luce nt Quarter-Turn Fasteners STATUS RESET Alcatel Luce nt STATUS RESET Alcatel Luce nt STATUS RESET PC I/O PC I/O PC I/O Alcatel Luce nt STATUS RESET ON OFF PC I/O MCPA Figure 4-1 MCPA Removal and Replacement 044-05287 Rev A 4-3 Field Replacement Procedures PAF-0813-E0-001 Subrack Cooling Fans Refer to Chapter 3 - Air Conditioning for cooling-fan operating parameters before replacing fans. To replace an inside or rear mounted cooling fan or change the fan mounting configuration, proceed as follows: CAUTION: To prevent damage to MCPA rear connector, support rear of MCPA when removing from subrack. MCPA weight is approximately 20 lbs (9.1 kg). Inside Mount To replace the inside mounted fan, shown in Figure 4-2, perform the steps in Table 4-4. CAUTION: The replacement fan may operate when the power connector is connected. Ensure that no objects (fingers, screwdrivers, etc.) intrude into the fan area. Table 4-5 Inside Mount Cooling Fan Removal and Replacement Procedure Step Action 1. For fan assembly located behind blank panels, rotate quarter-turn fasteners on each panel counter-clockwise to remove panels from subrack, then proceed to Step 4 2. For fan assembly located behind MCPAs, set each front panel OFF/ON/RESET switch to OFF 3. Read above Caution. Rotate quarter-turn fasteners on each MCPA counter-clockwise and remove MCPAs from subrack 4. Disconnect fan power connector and pull out snap fasteners to remove fan 5. Install replacement fan assembly in reverse order of removal Cooling Fan Assembly Snap Fasteners (4) Power/Sense Connector ANALOG RF OUT ETHERNET RS485 FILTER I/O AMPS1 AMPS2 DIGITAL CDMA1 CDMA2 CDMA3 CDMA4 Figure 4-2 Inside Mount Cooling Fan Removal and Replacement 4-4 044-05287 Rev A PAF-0813-E0-001 Field Replacement Procedures Rear Mount Rear mounted fans may be changed without shutting down the system. To replace the fans, shown in Figure 4-3, perform the steps in Table 4-5. CAUTION: The replacement fan may operate when the power connector is connected. Ensure that no objects (fingers, screwdrivers, etc.) intrude into the fan area. Table 4-6 Rear Mount Cooling Fan Removal and Replacement Procedure Step Action 1. At rear of subrack, pull out snap fasteners that secure defective fan assembly to fan-mounting bracket 2. Pull fan outward, and disconnect fan power connector 3. See Caution. Install replacement fan assembly in reverse order of removal Cooling Fan Assembly Snap Fasteners (4) Power/Sense Connector Located Inside DC POWER +27V RETURN Figure 4-3 Rear Mount Cooling Fan Removal and Replacement 044-05287 Rev A 4-5 Field Replacement Procedures PAF-0813-E0-001 Fan Inside Mount to Rear Mount Conversion To convert the subrack fan from inside mount to rear mount, as shown in Figure 4-4, perform the steps in Table 4-6. Table 4-7 Fan Conversion Procedure Step Action 1. To remove fan assembly from subrack, follow steps listed in Table 4-5 2. Disassemble inside mount fan assembly as shown in Figure 4-4 3. Reassemble inside mount fan assembly into rear mount configuration shown in Figure 4-4. Maintain orientation of fan to ensure air is exhausting out rear of subrack 4. Connect power connector, place fan assembly into mounting position, then press each snap fastener to secure fan to subrack 5. Repeat Steps 1 through 4 for second fan Air Flow Grill Inside Mount Fan Assembly Snap Fasteners Fan Mounting Bracket Power Connector Rear Mount Fan Assembly Air Flow Figure 4-4 Fan Inside Mount to Rear Mount Conversion 4-6 044-05287 Rev A PAF-0813-E0-001 Field Replacement Procedures Subrack To remove and replace the subrack, shown in Figure 4-5, perform the steps in Table 4-7. CAUTION: Support rear of Subrack when removing from rack. The subrack may disengage suddenly from the sliding brackets. Table 4-8 Subrack Removal and Replacement Procedure Step Action 1. At affected subrack, set all MCPA OFF/ON/RESET switches to OFF 2. At breaker panel, set all subrack associated circuit breakers to OFF 3. Disconnect all semi-rigid RF cables between subrack and duplexer 4. Disconnect subrack alarm cables 5. At rear of subrack, label and disconnect all breaker panel DC power connections, maintaining DC Power cable service loop 6. Remove four mounting screws from both sides of subrack 7. Slide subrack forward out of frame until completely disengaged from sliding brackets. Ensure rear of subrack is supported to prevent subrack from suddenly disengaging 8. Install new subrack in reverse order of removal Subrack Alcatel Luce nt STATUS Alcatel Luce nt STATUS RESET RESET DC power connections Alcatel Luce nt STATUS RESET Alcatel Luce nt STATUS RESET PC I/O PC I/O DC POWER PC I/O PC I/O +27V RETURN Four screws located on both sides of subrack Figure 4-5 Subrack Removal and Replacement 044-05287 Rev A 4-7 Field Replacement Procedures PAF-0813-E0-001 Filter To remove and replace the filter, shown in Figure 4-6, perform the steps in Table 4-8. Table 4-9 Filter Removal and Replacement Procedure Step Action 1. At subrack, set all MCPA OFF/ON/RESET switches to OFF 2. At breaker panel, set all circuit breakers to OFF 3. Disconnect and tag all cables from filter 4. Remove four screws securing filter to shelf 5. Install new filter in reverse order of removal Alcatel Lucent STATUS Alcatel Lucent STATUS RESET ON Alcatel Lucent STATUS RESET ON OFF Alcatel Lucent STATUS RESET ON OFF RESET ON OFF OFF PC I/O PC I/O PC I/O PC I/O 850 MHz 850 MHz 850 MHz 850 MHz Alcatel Lucent STATUS Alcatel Lucent STATUS RESET ON Alcatel Lucent STATUS RESET ON OFF Alcatel Lucent STATUS RESET ON OFF RESET ON OFF OFF PC I/O PC I/O PC I/O PC I/O 850 MHz 850 MHz 850 MHz 850 MHz Alcatel Lucent STATUS Alcatel Lucent STATUS RESET ON Alcatel Lucent STATUS RESET ON OFF Alcatel Lucent STATUS RESET ON OFF RESET ON OFF OFF PC I/O PC I/O PC I/O PC I/O 850 MHz 850 MHz 850 MHz 850 MHz Figure 4-6 Filter Removal and Replacement 4-8 044-05287 Rev A PAF-0813-E0-001 Field Replacement Procedures Circuit Breaker Panel To remove and replace the circuit breaker panel, shown in Figure 4-9, perform the steps in Table 4-11. Table 4-10 Circuit Breaker Panel Removal and Replacement Procedure Step Action 1. Turn off all +27 VDC BTS input power to PAF system 2. Label and disconnect all input and output DC power connections from top rear of circuit breaker panel 3. Remove screws from circuit breaker panel 4. Remove circuit breaker panel from PAF frame 5. Install circuit breaker panel replacement in reverse order of removal Power in from base station Power out to subracks Four screws Circuit Breaker panel Circuit breaker panel input and output DC wiring Figure 4-7 Breaker Panel Unit Removal and Replace 044-05287 Rev A 4-9 Return For Service Procedures PAF-0813-E0-001 Return For Service Procedures When returning products to Powerwave, the following procedures will ensure optimum response. Obtaining An RMA A Return Material Authorization (RMA) number must be obtained prior to returning equipment and to reduce delays in receiving repair service. Please contact our Repair Department at rma@pwav.com, (714) 466-1000 to obtain this number, or FAX your request to (714) 466-5816. For 24-hour technical support, call 1-800-4731720 and select option 3. Repackaging For Shipment To ensure safe shipment of a component, it is recommended that the original packing materials be reused. If not possible, use suitable shipping cartons and foam inserts to prevent damage in transit. 4-10 044-05287 Rev A Chapter 5 Specifications Introduction This chapter provides system specifications that support the PAF-081X-P0-001 MCPA system. The system specifications are listed in Table 5-1. Figure 5-1 System Specifications Electrical Specifications/Features Downlink Frequency Range 869-894 MHz Uplink Frequency Range Cellular (850) = 824-849 MHz RF Power Output per Antenna Port Measured @ Alpha, Beta, and Gamma Bulkheads 468 watts (56.7 dBm) per sector nominal AMPS 381 watts (55.8 dBm) per sector nominal CDMA Air Interface Compatible with most standards for: TDMA, GSM, EDGE, CDMA, W-CDMA Max Input Power Handling (Composite RF per port) 0dB peak Emissions Limits Compliant to FCC Part 15, class B, Part 22 Cellular Gain Variation vs. Frequency and Power ±0.6dB Gain Variation vs. Temperature ±0.5dB for temperatures ranging from -5 to +45 oC Input Port Return Loss 14 dB Output Port Return Loss 14 dB Operating DC Voltage Range 21 – 30 VDC Alarms RS485; Minor, Major, and Critical Mechanical Specifications/Features PAF Connectors Antenna Ports (Alpha, Beta, Gamma) Type 7/16 DIN Input Ports J1 - J6 Type - SMA Alarms, RS-486 Weight (3 sectors) Empty: 428 lbs (194 kg) Loaded: 588 lbs (267 kg) Dimensions (W x D x H) 22.75 (577.85 mm) x 26.5 (673.1 mm) X 78 (1981.2 mm) 044-05287 Rev A 5-1 Introduction PAF-0813-E0-001 Figure 5-1 System Specifications (Continued) Torques (Inch-Pounds): Metal Machine Screws 8-32 10-32 1/4-20 5/16-18 Coaxial Connectors SMA Type N Type 7/16 DIN 20 to 24 32 to 40 70 to 80 140 to 160 5 to 6 12 to 15 220 to 230 Environmental Specifications/Features Operating Temperature Range -5 - +45o C Operating Humidity Range 5 -100% RH @ +40o C, Non-Condensing Altitude -60 to 4000 meters Seismic GR-63-CORE, Section 4.4.1, Zone 4 Lightning Surge Protection 3 kA @ 10/350 us waveform 5 kA @ 8/20 us waveform Office Vibration GR-63-Section 5.4.2 Transportation Bump IEC 60068-2-29, Eb, 100 bumps per axis Transportation Shock IEC 60068-2-27, Ea, three 15 g, 11 ms, half-sine shocks, Z axis 5-2 044-05287 Rev A Powerwave Installation and Service Manual Corporate Headquarters Powerwave Technol 1801 East St. Andrew Place Santa Ana, CA 92705 USA Tel: 714-466-1000 Fax: 714-466-5800 www.powerwave.com Main European Office Antennvägen 6 SE-187 80 Täby Sweden Tel: +46 8 540 822 00 Fax: +46 8 540 823 40 Main Asia - Pacific Office 23 F Tai Yau Building 181 Johnston Road Wanchai, Hong Kong Tel: +852 2512 6123 Fax: +852 2575 4860 ©Copyright 2007, Powerwave Technologies, Inc. All Rights reserved. Powerwave, Powerwave Technologies, The Power in Wireless and the Powerwave logo are registered trademarks of Powerwave Technologies, Inc.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 15 Has XFA : No XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:bce404aa-63ce-4e8d-9755-4047a6e26b62 Producer : Acrobat Distiller 6.0 (Windows) Create Date : 2007:04:13 13:17:22-05:00 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2007:12:11 13:50:13-08:00 Metadata Date : 2007:12:11 13:50:13-08:00 Document ID : uuid:f292b3a9-b72b-466a-97e6-480d66cc64a0 Format : application/pdf Title : 044-05287 PAF-0813-E0-001.book Creator : PScript5.dll Version 5.2.2EXIF Metadata provided by EXIF.tools