Rosemount RM2510 Wireless HART Industrial Process Management Produc User Manual

Rosemount Inc Wireless HART Industrial Process Management Produc

User manual

Download: Rosemount RM2510 Wireless HART Industrial Process Management Produc User Manual
Mirror Download [FCC.gov]Rosemount RM2510 Wireless HART Industrial Process Management Produc User Manual
Document ID920146
Application ID5fOHUfOzsKBMb4G3+HEfiQ==
Document DescriptionUser manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize12.9kB (161300 bits)
Date Submitted2008-03-27 00:00:00
Date Available2008-03-27 00:00:00
Creation Date2008-03-19 11:07:13
Producing SoftwareAcrobat Distiller 8.1.0 (Windows)
Document Lastmod2008-03-19 11:07:13
Document TitleMicrosoft Word - RM2510 Radio Module Manual Rev 2.doc
Document CreatorPScript5.dll Version 5.2
Document Author: merrpul

Confidential
RM2510 Wireless HARTTM
2.4 GHz Radio Module
Product Description
Rosemount Inc.’s RM2510 Wireless HARTTM 2.4GHz Radio Module has been specifically designed to interface with industrial and
process control equipment designed and marketed by the Emerson family of companies. The RM2510 is designed to be fully compliant
with the wireless HARTTM specification. It uses a DSSS modulation type and multiple channel selection for optimum interference
rejection and >99% communication reliability. The RM2510 utilizes the global license-free 2.4GHz band at output power levels that are
compatible with government regulations throughout the world.
The RM2510’s very low power consumption characteristics make it perfect for battery powered equipment. The multi-functional interface
of the RM2510 is flexible enough for it to be integrated into many types of sensors. From pressure, temperature, and flow monitoring to
machinery health and valve position control, the RM2510 is the best choice for wireless HARTTM compatible communications.
Key Features
Reliable Networking
•
•
•
Mesh networking for redundancy and high reliability (> 99.9%
typical network reliability)
Dynamic channel selection for interference rejection
Every RM2510 acts as both an endpoint and a router, increasing
network reliability.
Automatic self-organizing mesh-networking capability built-in
•
Easy Integration
•
•
•
Well-defined multi-functional interfaces
High-level Data Link Control (HDLC) serial interface with
bidirectional flow control
Industrial temperature range –40 °C to +85 °C
802.15.4 Standard Radio
•
•
•
+8 dBm (6.3 mW) conducted RF output power
–90 dBm receiver sensitivity
300 m outdoor range (typical)
RM2510 Datasheet
Rosemount Inc.
Confidential
Table of Contents
1.0
Absolute Maximum Ratings ................................................................................3
2.0
Normal Operating Conditions .............................................................................3
3.0
Electrical Specifications .....................................................................................4
4.0
Radio..................................................................................................................4
4.1 Detailed Radio Specifications ................................................................................ 4
4.2 Antenna Specifications......................................................................................... 5
5.0
Pinout ................................................................................................................5
6.0
Physical Drawing................................................................................................7
7.0
Regulatory and Standards Compliance ...............................................................8
RM2510 Datasheet
Rosemount Inc.
2 of 8
Confidential
1.0
Absolute Maximum Ratings
The absolute maximum ratings shown below should under no circumstances be violated. Permanent damage to the device may be caused by
exceeding one or more of these parameters.
Table 1
Absolute Maximum Ratings
Max
Units
Supply voltage (VDD to VSS)
Parameter
Min
–0.3
Typ
3.6
Voltage on any digital I/O pin
–0.3
VDD + 0.3
Comments
up to 3.6
Input RF level
Storage temperature range
–40
VSWR of antenna
10
dBm
+85
°C
Input power at antenna
connector
3:1
ESD protection
Antenna pad
All other pads
±250
HBM
±2
kV
HBM
±200
CDM
* All voltages are referenced to VSS
Caution! ESD sensitive device. Precaution should be used when handling the device in order to prevent permanent damage.
2.0
Table 2
Normal Operating Conditions
Normal Operating Conditions
Parameter
Min
Typ
Max
Units
Operational supply voltage
range (between VDD and VSS)
2.75
3.0
3.3
Voltage on analog input pins
Voltage supply noise
Comments
Including noise and load
regulation
1.8
100
mVp-p
85
mA
Flash write 35 ms max
18
mA
TX, 5 ms maximum
mA
Searching for network, 60
minutes maximum
12
mA
RM2510 boot, see
section Error! Reference
source not found..
50 Hz to 2 MHz
Peak current
Operating temperature range
–40
Maximum allowed temperature
ramp during operation
Operating relative humidity
10
+85
°C
°C/min
–40 °C to +85 °C
90
% RH
Non-condensing
Unless otherwise noted, Table 3 assume VDD is 3.0 V and temperature is 25 °C.
Table 3
RM2510 Current Consumption
Parameter
Min
Typ
Max
Units
Transmit
18
mA
Receive
mA
2.5
µA
Sleep
RM2510 Datasheet
Rosemount Inc.
Comments
3 of 8
Confidential
3.0
Table 4
Electrical Specifications
Device Load
Parameter
Min
Typ
Total capacitance
Max
Units
0.5
µF
Comments
Unless otherwise noted, VDD is 3.0 V and temperature is –40 °C to +85 °C.
Table 5
Digital I/O Type 1
Digital Signal
Min
Typ
Max
Units
VIL (low-level input voltage)
–0.3
0.6
VIH (high-level input voltage)
0.8 x VDD
VDD + 0.3
0.4
VOL (low-level output voltage)
VOH (high-level output voltage)
2.4
Comments
Digital current*
Output source (single pin)
3.7
mA
25 °C
Output sink (single pin)
2.0
mA
25 °C
50
nA
Input leakage current
This current level guarantees that the output voltage meets VOH and VOL specifications above.
Table 6
Digital I/O Type 2
Digital Signal
Min
Typ
Max
Units
Comments
VIL (low-level input voltage)
–0.3
0.6
VIH (high-level input voltage)
0.8 x VDD
VDD + 0.3
VOL (low-level output voltage, multifunction I/O configured as
output)
0.6
IOL < 0.6 mA, 85 °C
VOH low-level output voltage, multifunction I/O configured as
output)
VDD – 0.6
VDD
IOH > –0.4 mA, 85 °C
Digital current*
Output source (single pin,
multifunction I/O configured as
output)
0.4
mA
25 °C
Output sink (single pin,
multifunction I/O configured as
output)
0.6
mA
25 °C
50
nA
Input leakage current
This current level guarantees that the output voltage meets VOH and VOL specifications above.
4.0
Radio
4.1
Detailed Radio Specifications
Table 7
Radio Specifications
Parameter
Operating frequency
Min
Typ
2.4000
Max
Units
2.4835
GHz
Number of channels
15
Channel separation
MHz
2.7
MHz
Occupied channel bandwidth
RM2510 Datasheet
Rosemount Inc.
Comments
At –20 dBc
4 of 8
Confidential
Parameter
Min
Frequency Accuracy
Typ
-50
Max
Units
+50
kHz
Modulation
Comments
IEEE 802.15.4 DSSS
Raw data rate
250
kbps
dBm
–92.5
dBm
At 50% PER, VDD = 3 V,
25 °C
–90
dBm
At 1% PER, VDD = 3 V,
25 °C, (inferred from 50%
PER measurement)
dBm
VDD = 3 V, 25 °C
Receiver operating maximum
input level
Receiver sensitivity
Output power, conducted
+8
Range*
Indoor
100
Outdoor
300
25 °C, 50% RH, 1 meter
above ground, +2 dBi
omni-directional antenna
* Actual RF range performance is subject to a number of installation-specific variables including, but not
restricted to ambient temperature, relative humidity, presence of active interference sources, line-of-sight
obstacles, near-presence of objects (for example, trees, walls, signage, and so on) that may induce
multipath fading. As a result, actual performance varies for each instance.
4.2
Antenna Specifications
The antenna must meet specifications in Table 8.
Table 8
Antenna Specifications
Parameter
Value
Frequency range
2.4–2.4835 GHz
50 Ω
Impedance
Maximum VSWR
3:1
Antenna Connector
MMCX
When the RM2510 is placed inside an enclosure, the antenna should be mounted such that the radiating portion of the antenna protrudes from the
enclosure, and connected using a coaxial cable. For optimum performance, allow the antenna to be positioned vertically when installed.
5.0
Pinout
The following is the pinout for the RM2510 module.
Table 9
Pinout Assignments for the RM2510
Pin Number
Pin Description
I/O (relative to radio)
1-1
Circuit Common/Ground
Input
1-2
Power Supply (2.75 V to 3.3 V)
Input
1-3
Keying Pin (no function)
N/A
1-4
Data Transmit (Sensor Board to Radio)
Input
1-5
Data Receive (Radio to Sensor Board)
Output
1-6
Diagnostics LED
Output
1-7
Radio Ready-to-Send (also DIM wake-up)
Output
1-8
Radio Clear-to-Send
Output
1-9
Sensor Board Clear-to-Send
Input
1-10
Radio Time Packet
Input
1-11
Radio Baud Rate Input
Input
RM2510 Datasheet
Rosemount Inc.
5 of 8
Confidential
2-1
Radio Reset Line
Input
2-2
SPI Chip Select
Input
2-3
Keying Pin (no function)
N/A
2-4
SPI Bus (MISO)
Output
2-5
SPI Bus (MOSI)
Input
2-6
SPI Bus (Clock)
Input
2-7
JTAG (TCK)
Input
2-8
JTAG (TDO)
Output
2-9
JTAG (TDI)
Input
2-10
JTAG (TMS)
Input
2-11
Flash Enable
Input
RM2510 Datasheet
Rosemount Inc.
6 of 8
Confidential
6.0
Physical Drawing
Figure 1
RM2510 Datasheet
Rosemount Inc.
RM2510 Mechanical Drawing
7 of 8
Confidential
7.0
Regulatory and Standards Compliance
The RM2510 has achieved modular radio certification on a reference design for the United States, Canada and the Europe. The reference design
has been certified for Part 15.247 (Intentional Radiator) of the FCC rules an regulations, Industry Canada RSS-210, ETSI EN 300 328 and ETSI
EN 301-489-17.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause
undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
The RM2510 complies with Part 15.247 modular (Intentional Radiator) FCC rules and regulations. Changes or
modifications not expressly approved by Rosemount Inc. could void the user's authority to operate the equipment.
7.1
FCC Testing
In order to fulfill FCC certification requirements, products incorporating the RM2510 must comply with the following:
1. An external label must be provided on the outside of the final product enclosure specifying the FCC identifier as
described in 7.3 below.
2. The antenna must be electrically identical to the FCC-approved antenna specifications for the RM2510 as described in
7.2 with the exception that the gain may be lower than specified in Table 14.
3. The device integrating the RM2510 may not cause harmful interference, and must accept any interference received,
including interference that may cause undesired operation.
4. An unintentional radiator scan must be performed on the device integrating the RM2510, per FCC rules and
regulations, CFR Title 47, Part 15, Subpart B. See FCC rules for specifics on requirements for declaration of conformity.
7.2
FCC-approved Antenna
The FCC-approved antenna specifications for the RM2510 is an antenna with a Maximum gain of +2dBi, vertical polarization, and
frequency of 2.4 to 2.485GHz.
7.3
Final FCC Labeling Requirements
The outside of the final product enclosure must have a label with the following (or similar) text specifying the FCC identifier. The
FCC ID and
certification code must be in Latin letters and Arabic numbers and visible without magnification.
Contains transmitter module FCC ID: LW2RM2510
Or
Contains FCC ID: LW2RM2510
7.4
IC Testing
The RM2510 is certified for modular Industry Canada (IC) RSS-210 approval. The OEM is responsible for its product to
comply with IC ICES-003 and FCC Part 15, Sub. B - Unintentional Radiators. The requirements of ICES-003 are equivalent
to FCC Part 15 Sub. B and Industry Canada accepts FCC test reports or CISPR 22 test reports for compliance with ICES-003.
7.5
Final IC Labeling Requirements
The Original Equipment Manufacturer (OEM) must ensure that IC labeling requirements are met. The outside of the final
product enclosure must have a label with the following (or similar) text specifying the IC identifier. The IC ID and
certification code must be in Latin letters and Arabic numbers and visible without magnification
Contains IC: 2731A-RM2510
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
RM2510 Datasheet
Rosemount Inc.
8 of 8

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Format                          : application/pdf
Title                           : Microsoft Word - RM2510 Radio Module Manual Rev 2.doc
Creator                         : merrpul
Create Date                     : 2008:03:19 11:07:13-05:00
Creator Tool                    : PScript5.dll Version 5.2
Modify Date                     : 2008:03:19 11:07:13-05:00
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Document ID                     : uuid:9595f46e-6fcd-48b2-9a48-058ca8cd225f
Instance ID                     : uuid:69fe8e08-574b-459f-be06-754718af0e3f
Page Count                      : 8
Author                          : merrpul
EXIF Metadata provided by EXIF.tools
FCC ID Filing: LW2RM2510

Navigation menu