S and C Electric TSIICONTRL2 TripSaver Service Center Configurable Controller2 User Manual Module Integration Instruction

S&C; Electric Company TripSaver Service Center Configurable Controller2 Module Integration Instruction

Contents

Module Integration Instruction

Download: S and C Electric TSIICONTRL2 TripSaver Service Center Configurable Controller2 User Manual Module Integration Instruction
Mirror Download [FCC.gov]S and C Electric TSIICONTRL2 TripSaver Service Center Configurable Controller2 User Manual Module Integration Instruction
Document ID3162865
Application IDEpN8speiI3Rlyl4fOt7rWg==
Document DescriptionModule Integration Instruction
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize7.86kB (98252 bits)
Date Submitted2016-10-13 00:00:00
Date Available2016-10-13 00:00:00
Creation Date2016-07-11 10:00:05
Producing SoftwareAcrobat Distiller 11.0 (Windows)
Document Lastmod2016-07-11 10:00:05
Document TitleMicrosoft Word - TSII Module Integration Instructions.doc
Document CreatorPScript5.dll Version 5.2.2
Document Author: muhammad.tabani

6601 North Ridge Boulevard
Chicago, Illinois 60626-3997
Telephone (773) 338-1000
Fax (773) 338-3657
Module Integration Instructions
To integrate the TSIICONTRL2 module in a host product the following instructions need to be
followed
Power requirements:
When powering the unit from the CT terminals, the maximum input current
should not exceed 1.6Arms @50/60 Hz continuously.
Note:

Once the module is fully charged the CT input terminals will be shorted
as a virtue of this design. The charging level can be controlled by
software
When powering the unit from the SEPIC terminals, the input voltage limits should
not exceed 25V (upper limit) or be lower than 5V (lower limit). The module can
draw currents as high as 1A. Input voltage polarity is not critical for the proper
functionality of the module.
The module’s box is metalized and connected to the ground reference of the
electronics.
Current sensing terminals are floating with respect to the internal grounds
(differential input). Special care should be taken to reduce induced noise in the
system ( sensor and CT shielding is recommended)
Environment requirements:
The module is not sealed from the environment point of view. It relies on the host
product to provide protection against water entry and condensation. Host
equipment is fully tested at all environmental conditions to protect control module
residing inside.
Communication requirements:
This module is designed operate in the presence of interface
This module is also designed to coexist with other 2.4GHz products, even
multiple modules in the nearby area
Input/output signals:
This module can take up to 105Arms @50/60Hz input surge current up
to 0.5 seconds
Grounding requirements:

Sensing signals

Only the current sensing have a differential input and its input should not
exceed +/-10V

All other sensing signals are single ended.
Drivers: The main two drives can put out voltage in the +/-225V range (peak
voltage of the PWM technique) with currents as high as 10A
Display:
When handling the module, avoid applying any pressure on the LCD
Protect the LCD against 380 nm UV wavelengths.
6601 North Ridge Boulevard
Chicago, Illinois 60626-3997
Telephone (773) 338-1000
Fax (773) 338-3657
Connections: The module has 4 connectors distributes as follows
Signal Name
Current sensor input
Current sensor input
Connector
J12/TE Connectivity
J12/TE Connectivity
Pin
CT input terminal
CT input terminal
J2/TE Connectivity
J2/TE Connectivity
Driver 1_P
Position Sensor
Drive 1 N
J8/Molex
J8/Molex
J8/Molex
Driver 2 P
Driver 2 N
J9/Molex
J9/Molex
J10/TE Connectivity
J10/TE Connectivity
J10/TE Connectivity
J10/TE Connectivity
J10/TE Connectivity
13V
External Sensor
AGND
SEPIC input
SEPIC input
This module is primarily designed to work with S&C’s host products.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : muhammad.tabani
Create Date                     : 2016:07:11 10:00:05-05:00
Modify Date                     : 2016:07:11 10:00:05-05:00
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Creator Tool                    : PScript5.dll Version 5.2.2
Producer                        : Acrobat Distiller 11.0 (Windows)
Format                          : application/pdf
Title                           : Microsoft Word - TSII Module Integration Instructions.doc
Creator                         : muhammad.tabani
Document ID                     : uuid:19574dfa-4d9c-44d4-8fe8-8d599749719d
Instance ID                     : uuid:38fff24c-130a-4dfc-8e9d-a5680874b1a4
Page Count                      : 2
EXIF Metadata provided by EXIF.tools
FCC ID Filing: U3D-TSIICONTRL2

Navigation menu