Schneider Electric IndustrieS NX2TO7 Control Units User Manual Micrologic X Control Unit User Guide 05 2016

Schneider Electric Industrie SAS Control Units Micrologic X Control Unit User Guide 05 2016

Users Manual-2.pdf

Download: Schneider Electric IndustrieS NX2TO7 Control Units User Manual Micrologic X   Control Unit   User Guide   05 2016
Mirror Download [FCC.gov]Schneider Electric IndustrieS NX2TO7 Control Units User Manual Micrologic X   Control Unit   User Guide   05 2016
Document ID3264268
Application IDq/6QqbA0OGit3avswYsxyg==
Document DescriptionUsers Manual-2.pdf
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize229.02kB (2862729 bits)
Date Submitted2017-01-19 00:00:00
Date Available2017-01-19 00:00:00
Creation Date2016-05-02 11:47:47
Producing SoftwareAcrobat Elements 11.0 (Windows)
Document Lastmod2016-10-18 23:05:37
Document TitleMicrologic X - Control Unit - User Guide - 05/2016
Document CreatorMiramo 9.2 (www.miramo.com)
Document Author: Schneider Electric

Metering Functions
For Masterpact MTZ devices, the sensors are embedded in the device for applications up to 690 Vac and
the overall uncertainty is equal to the operating uncertainty.
DOCA0102EN-00 05/2016
101
Metering Functions
Measurement Characteristics
Presentation
The following tables indicate the measurements available and specify the following information for each
measurement:
 Unit
 Measurement range
 Accuracy
 Accuracy range
Current
Measurement
Unit
Range
Accuracy
Accuracy range
 RMS current on phases 1, 2, 3
0–20 In
+/-0.5%
MTZ1 : 40–1600 x 1.2 In
MTZ2 : 40–4000 x 1.2 In
MTZ3 : 80–6300 x 1.2 In
0–20 In
+/-1%
MTZ1 : 40–1600 x 1.2 In
MTZ2 : 40–4000 x 1.2 In
MTZ3 : 80–6300 x 1.2 In
0–20 In
+/-0.5%
MTZ1:40–1600 x 1.2 In
MTZ2:40–4000 x 1.2 In
MTZ3:80–6300 x1.2 In
0–20 In
5%
MTZ1:40–1600 x 1.2 In
MTZ2:40–4000 x 1.2 In
MTZ3:80–6300 x1.2 In
0–30 A
10%
0.1–30 A
 Maximum RMS current on phases 1, 2, 3 (I1 MAX, I2
MAX, I3 MAX)
 Maximum value (MAXMAX) of all phase currents
 Minimum RMS current on phases 1, 2, 3 (I1 MIN, I2 MIN,
I3 MIN)
 Minimum value (MINMIN) of all phase currents
 RMS current on neutral 1
 Maximum RMS current on neutral IN MAX
 Minimum RMS current on neutral IN MIN 1
 Average of 3 phase RMS currents
 Maximum average of 3 phase RMS currents Iavg MAX
 Minimum average of 3 phase RMS currents Iavg MIN
 RMS current on ground 2
 Maximum/minimum RMS current on ground 2
 Earth-leakage current measurement 3
 Maximum/minimum value of the earth-leakage current
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENCT wired and configured.
2 Applies to Micrologic 6.0 X control unit
3 Applies to Micrologic 7.0 X control unit
NOTE: The accuracy range is for the current range: 0.2–1.2 In.
Current Unbalance
Measurement
Unit
Range
Accuracy
Accuracy
range
 Phase current unbalance on phase 1, 2, 3 (I1 unbal, I2 unbal, I3
0–100%
+/-5
0–100%
unbal)
 Maximum of 3 phase current unbalances (l1 unbal MAX,
I2 unbal MAX, I3 unbal MAX)
 Maximum of maximum of 3 phase current unbalances (MAXMAX)
NOTE: The accuracy range is for the current range: 0.2–1.2 In.
102
DOCA0102EN-00 05/2016
Metering Functions
Voltage
Measurement
 RMS phase-to-phase V12, V23, V31 voltage measurements
Unit
Range
0–1,150 V +/-0.5%
Accuracy
Accuracy range
208–690 x 1.2 V
0–660 V
+/-0.5%
120–400 x 1.2 V
0–1,150 V +/-0.5%
208–690 x 1.2 V
 Maximum RMS phase-to-phase voltages V12 MAX L-L,
V23 MAX L-L, V31 MAX L-L 1
 Minimum RMS phase-to-phase voltages V12 MIN L-L,
V23 MIN L-L, V31 MIN L-L1
 Maximum of the maximum phase-to-phase voltages (V12,
V23, V31)
 Minimum of the minimum phase-to-phase voltages (V12, V23,
V31)
 RMS phase-to-neutral V1N, V2N, V3N voltage
measurements
 Maximum RMS phase-to-neutral voltages V1N MAX L-N, V2N
MAX L-N, V3N MAX L-N 1
 Minimum RMS phase-to-neutral voltages V1N MIN L-N, V2N
MIN L-N, V3N MIN L-N 1
 Maximum of the maximum phase-to-neutral voltages (V1N,
V2N, V3N) 1
 Minimum of the minimum phase-to-neutral voltages (V1N,
V2N, V3N) 1
 Average of 3 RMS phase-to-phase voltages Vavg:
(V12+V23+V31)/3
 Maximum of average of 3 RMS phase-to-phase voltages
Vavg MAX: (V12+V23+V31)/3
 Minimum of average of 3 RMS phase-to-phase voltages
Vavg MIN: (V12+V23+V31)/3
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
Voltage Unbalance
Measurement
Unit
Range
Accuracy
Accuracy
range
 Phase-to-phase voltage unbalances V12unbal L-L, V23unbal L-
0–100%
+/-0.5
0–10%
 Phase-to-neutral voltage unbalances V1Nunbal L-N, V2Nunbal L- %
0–100%
+/-0.5
0–10%
L, V31unbal L-L 1
 Maximum of 3 phase-to-phase voltage unbalances
V12unbal MAX L-L, V23unbal MAX L-L, V31unbal MAX L-L1
 Maximum of maximum (MAXMAX) of 3 phase-to-phase voltage
unbalances 1
N, V3Nunbal L-N unbalance measurements 1
 Maximum of 3 phase-to-neutral voltage unbalances
V1Nunbal MAX L-L, V2Nunbal MAX L-L, V3Nunbal MAX L-L 1
 Maximum of maximum (MAXMAX) of 3 phase-to-neutral voltage
unbalances1
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
NOTE: The accuracy range is for the voltage range: 208–690 x 1.2 Vac.
DOCA0102EN-00 05/2016
103
Metering Functions
Power
Measurement
Unit
Range
Accuracy
Accuracy
range
 Active power on phase 1, phase 2, phase 3 1
kW
-16,000–
16,000 kW
+/-1%
kW
-16,000–
16,000 kW
+/-1%
kVAR
-16,000–
16,000 kVAR
+/-2%
kVAR
-16,000–
16,000 kVAR
+/-1%
kVA
0–16,000 kVA
+/-1%
kVA
0–16,000 kVA
+/-1%
kVAR
-16,000–
16,000 kVAR
+/-1%
kVAR
-16,000–
16,000 kVAR
+/-1%
 Maximum active power on phase 1, phase 2, phase 3 P1 MAX,
P2 MAX, P3 MAX1)
 Minimum active power on phase 1, phase 2, phase 3 P1 MIN,
P2 MIN, P3 MIN 1
 Total active power Ptot
 Maximum total active power Ptot MAX
 Minimum total active power Ptot MIN
 Reactive power on phase 1, phase 2, phase 3 Q1, Q2, Q3 1
 Maximum reactive power on phase 1, phase 2, phase 3 Q1 MAX,
Q2 MAX, Q3 MAX 1
 Minimum reactive power on phase 1, phase 2, phase 3 Q1 MIN,
Q2 MIN, Q3 MIN 1
 Total reactive power Qtot
 Maximum total reactive power Qtot MAX
 Minimum total reactive power Qtot MIN
 Apparent power on phase 1, phase 2, phase 3 S1, S2, S3 1
 Maximum apparent power on phase 1, phase 2, phase 3 S1 MAX,
S2 MAX, S3 MAX 1
 Minimum apparent power on phase 1, phase 2, phase 3 S1 MIN,
S2 MIN, S3 MIN 1
 Total apparent power Stot
 Maximum total apparent power Stot MAX
 Minimum total apparent power Stot MIN
 Fundamental reactive power on phase 1, phase 2, phase 3
Qfund 1, Qfund 2, Qfund 31
 Maximum fundamental reactive power on phase 1, phase 2,
phase 3 Qfund 1 MAX, Qfund 2 MAX, Qfund 3 MAX 1
 Minimum fundamental reactive power on phase 1, phase 2, phase
3 Qfund 1 MIN, Qfund 2 MIN, Qfund 3 MIN 1
 Total fundamental reactive power Qfundtot
 Maximum total fundamental reactive power Qfundtot MAX
 Minimum total fundamental reactive power Qfundtot MIN
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
2 The power measurement range according to IEC 61557-12 is defined by current range, voltage, and power factor
values.
NOTE: The power measurement range according to IEC 61557-12 is defined by current range, voltage,
and power factor values.
Power Factor PF and cos ϕ
Measurement
Unit
Range
Accuracy
Accuracy
range
 Total power factor PF
–
-1.00–
1.00
+/-0.02
0.5 ind 0.8 cap
–
-1.00–
1.00
+/-0.02
0.5 ind 0.8 cap
 Maximum total power factor PF MAX
 Minimum total power factor PF MIN
 Power factors on phase 1, phase 2, phase 3 PF1, PF2, PF3 1
 Maximum power factor on phase 1, phase 2, phase 3 PF1 MAX,
PF2 MAX, PF3 MAX 1
 Minimum power factor on phase 1, phase 2, phase 3 PF1 MIN,
PF2 MIN, PF3 MIN 1
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
104
DOCA0102EN-00 05/2016
Metering Functions
Measurement
Unit
Range
Accuracy
Accuracy
range
 Total fundamental power factor cos ϕ
–
-1.00–
1.00
+/-0.02
0.5 ind 0.8 cap
–
-1.00–
1.00
+/-0.02
0.5 ind 0.8 cap
 Maximum total fundamental power factor cos ϕ MAX
 Minimum total fundamental power factor cos ϕ MIN
 cos ϕ 1, cos ϕ 2, cos ϕ 3 on phase 1, phase 2, phase 3 1
 Maximum cos ϕ 1 MAX, cos ϕ 2 MAX, cos ϕ 3 MAX on phase
1, phase 2, phase 31
 Minimum cos ϕ 1 MIN, cos ϕ 2 MIN, cos ϕ 3 MIN on phase 1,
phase 2, phase 31
1 Applies to 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
NOTE: The accuracy for the power factor measurement range according to IEC 61557-12 is defined by
current range and voltage values.
Total Harmonic Distortion of Currents and Voltages
Measurement
Unit
Range
Accuracy
Accuracy range
 Total harmonic distortion (THD) of current on phase 1,
0–1,000%
+/-1.5
0–100%
when I > 80 A
+/-1.5 x THD/100
100–200%
phase 2, phase 3 THD(I1), THD(I2), THD(I3)
 Maximum total harmonic distortion (THD) of current
on phase 1, phase 2, phase 3 THD(I1) MAX, THD(I2)
MAX, THD(I3) MAX
 Minimum total harmonic distortion (THD) of current on
phase 1, phase 2, phase 3 THD(I1) MIN, THD(I2)
MIN, THD(I3) MIN
 Total harmonic distortion (THD) of phase-to-phase
0–1,000%
+/-0.6
0–20%
when V > 208 V
0–1,000%
+/-0.6
0–20%
when V > 120 V
voltage THD(V12) L-L, THD(V23) L-L, THD(V31) L-L
 Maximum total harmonic distortion (THD) of phase-tophase voltage THD(V12) MAX L-L, THD(V23) MAX LL, THD(V31) MAX L-L
 Minimum total harmonic distortion (THD) of phase-tophase voltage THD(V12) MIN L-L, THD(V23) MIN LL, THD(V31) MIN L-L
 Total harmonic distortion (THD) phase-to-neutral
voltage THD(V1N) L-N, THD(V2N) L-N, THD(V3N) LN1
 Maximum total harmonic distortion (THD) phase-toneutral voltage THD(V1N) MAX L-N, THD(V2N) L-L
MAX L-N, THD(V3N) MAX L-N 1
 Minimum total harmonic distortion (THD) phase-toneutral voltage THD(V12) MIN L-N, THD(V2N) MIN LN, THD(V31) MIN L-N 1
Frequency
Measurement
Unit
Range
Accuracy
Accuracy
range
 Frequency
Hz
15–440 Hz
+/-0.2%
45–65 Hz
 Maximum frequency
 Minimum frequency
Energy Meters
Measurement
Unit
Range
Accuracy
Accuracy range
Active energy Ep, EpIn delivered, and EpOut
received
kWh
-10,000,000 to
10,000,000
+/-1%
-10,000,000 to
10,000,000
+/-2%
Reactive energy Eq, EqIn delivered, and EqOut kVARh
received
1 The energy measurement range according to IEC 61557-12 is defined by current range, voltage, and power factor
values.
DOCA0102EN-00 05/2016
105
Metering Functions
Measurement
Unit
Range
Accuracy
Accuracy range
Apparent energy Es
kVAh
-10,000,000 to
10,000,000
+/-1%
1 The energy measurement range according to IEC 61557-12 is defined by current range, voltage, and power factor
values.
NOTE: The energy measurement range according to IEC 61557-12 is defined by current range, voltage,
and power factor values.
106
DOCA0102EN-00 05/2016
Metering Functions
Measurement Availability
Presentation
Measurements can be displayed through the following interfaces:
 The Micrologic X display screen
 The Masterpact MTZ mobile App
 The FDM128
 The Ecoreach software
 The communication network
The following tables indicate which measurements are displayed on each interface.
Current
Measurement
Masterpact
MTZ mobile
App
FDM128
Ecoreach
software
Communication
Phase I1, I2, I3 current measurements X
Maximum phase current values I1
MAX, I2 MAX, I3 MAX
Maximum value (MAXMAX) of all
phase currents
–
–
Minimum phase current values I1 MIN, –
I2 MIN, I3 MIN
–
Minimum value (MINMIN) of all phase
currents
–
–
Neutral IN current measurement 1
–
Maximum neutral current value IN
MAX1
–
Minimum neutral current value IN MIN1 –
–
Average current Iavg measurements
Maximum average current value Iavg
MAX
–
Minimum average current value Iavg
MIN
–
–
Ground-fault current measurement 2
–
–
Maximum/minimum value of the
–
–
Earth-leakage current measurement 3
–
–
Maximum/minimum value of the earth- –
leakage current 3
–
ground-fault current 2
Micrologic X
HMI
1 With 4-pole circuit breakers or 3-pole circuit breakers with ENCT wired and configured.
2 Applies to Micrologic 6.0 X control unit
3 Applies to Micrologic 7.0 X control unit
Current Unbalance
DOCA0102EN-00 05/2016
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
Phase current unbalance
measurements I1 unbal, I2 unbal,
I3 unbal
Maximum values of phase current
unbalances l1 unbal MAX,
I2 unbal MAX, I3 unbal MAX
Maximum value (MAXMAX) of all
phase current unbalances
FDM128
Ecoreach
software
Communication
–
107
Metering Functions
Voltage
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
Phase-to-phase V12, V23, V31 voltage
measurements1
Maximum values of phase-to-phase
voltages V12 MAX L-L, V23 MAX L-L,
V31 MAX L-L 1
Minimum values of phase-to-phase
voltages V12 MIN L-L, V23 MIN L-L,
FDM128
Ecoreach
software
Communication
Maximum value of the maximum phase- –
to-phase voltages (V12, V23, V31
Minimum value of the minimum phaseto-phase voltages (V12, V23, V31)
–
Phase-to- neutral V1N, V2N, V3N
Maximum values of phase-to-neutral
voltages V1N MAX L-N, V2N MAX L-N,
Minimum values of phase-to-neutral
voltages V1N MIN L-N, V2N MIN L-N,
V3N MIN L-N 1
Maximum value of the maximum phase- –
–
V31 MIN L-L (1)
voltage measurements 1
V3N MAX L-N 1
to-neutral voltages (V1N, V2N, V3N) 1
Minimum value of the minimum phaseto-neutral voltages (V1N, V2N, V3N) 1
Average voltage Vavg measurements
Maximum average voltage value
Vavg MAX
–
Minimum average voltage Vavg MIN
–
Ecoreach
software
Communication
1 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
Voltage Unbalance
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
FDM128
Phase-to-phase voltage V12unbal L-L, X
V23unbal L-L, V31unbal L-L and
phase-to-neutral voltage V1Nunbal LN, V2Nunbal L-N, V3Nunbal L-N
Maximum values of phase-to-phase
voltage unbalances V12unbal MAX LL, V23unbal MAX L-L,
V31unbal MAX L-L and phase-toneutral voltage unbalances
V1Nunbal MAX L-L, V2Nunbal MAX LL, V3Nunbal MAX L-L 1
Maximum values (MAXMAX) of all
phase-to-phase and phase-to-neutral
voltage unbalances
–
Maximum values of phase-to-phase
voltage unbalances V12unbal MAX LL, V23unbal MAX L-L,
unbalance measurements 1
V31unbal MAX L-L1
1 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
108
DOCA0102EN-00 05/2016
Metering Functions
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
Maximum values (MAXMAX) of the
maximum of the phase-to-phase
–
Phase-to-neutral voltage V1Nunbal LN, V2Nunbal L-N, V3Nunbal L-N
unbalance measurements 1
FDM128
Ecoreach
software
Communication
Maximum values of phase-to-neutral
voltage unbalances V1Nunbal MAX LL, V2Nunbal MAX L-L,
V3Nunbal MAX L-L1
Maximum values (MAXMAX) of the
maximum of the phase-to-neutral
–
Ecoreach
software
Communication
voltage unbalances 1
voltage unbalances 1
1 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
Power
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
Active power measurements for each
–
Maximum values of active powers for
each phase P1 MAX, P2 MAX, P3 MAX
Minimum values of active powers for
–
Total active power measurement Ptot
Maximum value of total active power
Ptot MAX
Minimum value of total active power
Ptot MIN
–
Reactive power measurements for
Maximum values of reactive powers for
each phase Q1 MAX, Q2 MAX,
Q3 MAX 1
–
Minimum values of reactive powers for –
each phase Q1 MIN, Q2 MIN, Q3 MIN 1
phase P1, P2, P3 1
FDM128
each phase P1 MIN, P2 MIN, P3 MIN 1
each phase Q1, Q2, Q3 1
Total reactive power measurement Qtot X
Maximum value of total reactive power
Qtot MAX
Minimum value of total reactive power
Qtot MIN
–
Apparent power measurements for
Maximum values of apparent powers
for each phase S1 MAX, S2 MAX,
–
Minimum values of apparent powers for –
Total apparent power measurement
Stot
each phase S1, S2, S3 1
S3 MAX 1
each phase S1 MIN, S2 MIN, S3 MIN 1
1 With 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
DOCA0102EN-00 05/2016
109
Metering Functions
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
FDM128
Ecoreach
software
Communication
Maximum value of total apparent power X
Stot MAX
Minimum value of total apparent power
Stot MIN
–
Fundamental reactive power
–
measurements for each phase Qfund 1,
Maximum values of fundamental
reactive powers for each phase
Qfund 1 MAX, Qfund 2 MAX,
Qfund 3 MAX 1
–
Minimum values of fundamental
reactive powers for each phase
Qfund 1 MIN, Qfund 2 MIN,
–
Total fundamental reactive power
measurement Qfundtot
–
Maximum value of total fundamental
reactive power Qfundtot MAX
–
Minimum value of total fundamental
reactive power Qfundtot MIN
–
Qfund 2, Qfund 3 1
Qfund 3 MIN 1
1 With 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
Operating Indicators
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
FDM128
Ecoreach
software
Communication
Operating quadrant measurement
???
Type of load measurement
???
Power Factor PF and cos ϕ
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
Total power factor PF
FDM128
Ecoreach
software
Communication
Maximum value of the total power factor –
PF MAX
Minimum value of the total power factor –
PF MIN
Power factors PF1, PF2, PF3 for each
phase 1
–
Maximum values of the power factors
PF1 MAX, PF2 MAX, PF3 MAX for
each phase 1
–
Minimum values of the power factors
PF1 MIN, PF2 MIN, PF3 MIN for each
–
phase 1
Total cos ϕ
Maximum value cos ϕ MAX
–
Minimum value cos ϕ MIN
–
cos ϕ 1, cos ϕ 2, cos ϕ 3 for each
–
phase 1
1 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
110
DOCA0102EN-00 05/2016
Metering Functions
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
FDM128
Ecoreach
software
Communication
Maximum values cos ϕ 1 MAX, cos ϕ –
2 MAX, cos ϕ 3 MAX for each phase 1
–
Ecoreach
software
Communication
Minimum values cos ϕ 1 MIN, cos ϕ 2
MIN, cos ϕ 3 MIN for each phase 1
1 4-pole circuit breakers or 3-pole circuit breakers with ENVT wired and configured.
Total Harmonic Distortion of Currents and Total Harmonic Voltages
Measurement
Micrologic X
HMI
Masterpact
MTZ mobile
App
FDM128
Total harmonic distortion (THD) of
current for each phase THD(I1),
THD(I2), THD(I3)
Maximum values of the total harmonic
distortion (THD) of current for each
phase THD(I1) MAX, THD(I2) MAX,
THD(I3) MAX
–
Minimum values of the total harmonic
distortion (THD) of current for each
phase THD(I1) MIN, THD(I2) MIN,
THD(I3) MIN
–
Total harmonic phase-to-phase voltage
THD(V12) L-L, THD(V23) L-L,
THD(V31) L-L distortion
–
Maximum values of the total harmonic
–
phase-to-phase voltage THD(V12) MAX
L-L, THD(V23) MAX L-L, THD(V31)
MAX L-L distortion
Minimum values of the total harmonic
phase-to-phase voltage THD(V12) MIN
L-L, THD(V23) MIN L-L, THD(V31) MIN
L-L distortion
–
Total harmonic phase-to-neutral voltage
THD(V1N) L-N, THD(V2N) L-N,
THD(V3N) L-n distortion 1
–
Maximum values of the total harmonic
phase-to-neutral voltage THD(V1N)
MAX L-N, THD(V2N) L-L MAX L-N,
–
Minimum values of the total harmonic
phase-to-neutral voltage THD(V12) MIN
L-N, THD(V2N) MIN L-N, THD(V31) MIN
L-N distortion 1
THD(V3N) MAX L-N distortion 1
Frequency
Measurement
DOCA0102EN-00 05/2016
Micrologic X HMI
Masterpact MTZ
mobile App
FDM128
Ecoreach
software
Communication
Frequency measurement X
Maximum frequency
Minimum frequency
111
Metering Functions
Energy Meters
Measurement
112
Micrologic X HMI
Masterpact
MTZ mobile
App
FDM128
Ecoreach
software
Communication
Active energy measurements: Ep, X
EpIn supplied, and EpOut
consumed
Reactive energy measurements:
Eq, EqIn supplied, and EqOut
consumed
Apparent energy measurement
Es
DOCA0102EN-00 05/2016
Metering Functions
Network Settings
Presentation
The following settings are related to the characteristics of the local network. They are used by the
measurement functions of the Micrologic X control unit.
Rated Voltage
Available settings include: 208 V / 220 V / 230 V / 240 V / 380 V / 400 V / 415 V / 440 V / 480 V / 500 V /
525 V / 550 V / 575 V / 600 V / 660 V / 690 V / 1000 V.
Default = 400 V.
The rated voltage can be set in the following ways:
 On the Micrologic X display screen, at Home → Configuration → Network → Nominal Voltage
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network.
Rated Frequency
Available settings are:
 50 Hz
 60 Hz
The rated frequency can be set in the following ways:
 On the Micrologic X display screen, at Home → Configuration → Network → Nominal Frequency
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network.
VT Ratio
The VT ratio is the ratio between the primary and the secondary rated voltages as measured by a voltage
transformer (VT).
The value range for the primary voltage (VT in) is from 100–1250 in increments of 1.
The value range for the secondary voltage (VT out) is from 100–690 in increments of 1.
The primary and secondary voltages can be set in the following ways:
 On the Micrologic X display screen, at Home → Configuration → Network → VT Ratio
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network.
DOCA0102EN-00 05/2016
113
Metering Functions
Real-Time Measurements
Presentation
Micrologic X control units perform the following real-time tasks:
 Measure the following currents in real time and as an rms value:
 Current for each phase and the neutral (if present)
 Ground-fault current
 Earth-leakage current (Micrologic 7.0 X)




Calculate the average current in real time
Determine the maximum and minimum values for these electrical quantities
Measure the phase-to-phase and phase-to-neutral voltage (if present), in real time and as an rms value
Calculate the associated electrical quantities from the rms values of the currents and voltages:
 Average phase-to-phase voltage and phase-to-neutral voltage (if present)
 Current unbalances
 Phase-to-phase voltage unbalances and phase-to-neutral voltage unbalances (if present)

Calculate the associated electrical quantities from the current and voltage samples:
 Powers (see page 117)
 Quality indicators: frequency, THD(I) and THD(V) (see page 124), and power factor PF and cos ϕ
measurement (see page 126)

Display operating indicators: quadrants, and type of load
Determine the maximum and minimum values for these electrical quantities
Increment in real time three energy meters (active, reactive, apparent) using the total power real-time
values (see page 117)


The sampling method uses the values of the harmonic currents and voltages up to the fifteenth order. The
sampling process tracks the fundamental frequency and provides 40 samples per fundamental cycle.
The values of the electrical quantities, whether measured or calculated in real time, update once a second
at rated frequency.
System Type Setting
On 3-pole circuit breakers, the system type setting allows the activation of:
 The ENCT (external neutral current transformer)
 The ENVT (external neutral voltage tap)
The system type can be set as follows:
On the Micrologic X display screen, at Home → Configuration → Measures → System Type.
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network

Measuring the Neutral Current
4-pole circuit breakers or 3-pole circuit breakers with the ENCT wired and configured measure the neutral
current:
 For a 3-pole circuit breaker, the neutral current is measured by adding a current transformer on the
neutral conductor for the transformer information. Refer to the Masterpact Catalog
 For a 4-pole circuit breaker, the neutral current is measured systematically
The neutral current is measured in the same way as the phase currents.
Measuring the Ground-Fault Current
The ground-fault current is calculated or measured in the same way as the phase currents, according to
the circuit breaker configuration, as shown in the following table.
114
Circuit breaker configuration
Ig ground-fault current
3P
Ig = I1 + I2 + I3
4P
Ig = I1 + I2 + I3 + IN
3P + ENCT
Ig = I1 + I2 + I3 + IN (ENCT)
3P or 4P + SGR
Ig = ISGR
DOCA0102EN-00 05/2016
Metering Functions
Measuring the Earth-Leakage Current (Micrologic 7.0 X)
The earth-leakage current is measured by a rectangular sensor encompassing the three phases or the
three phases and neutral.
Measuring the Phase-to-Neutral Voltages
4-pole circuit breakers or 3-pole circuit breakers with the ENVT wired and configured measure the phaseto-neutral (or line-to-neutral) voltages V1N, V2N, and V3N:
 For a 3-pole circuit breaker, it is necessary to:
 Connect the wire from the ENVT to the neutral conductor
 Declare the ENVT in the system type setting

For 4-pole circuit breakers, the phase-to-neutral voltages are measured systematically
The phase-to-neutral voltages are measured in the same way as the phase-to-phase voltages.
Calculating the Average Current and Average Voltage
Micrologic X control units calculate the:
 Average current Iavg, the arithmetic mean of the 3-phase currents:
Iavg = (I1 + I2 + I3)/3

Average voltages:
 Phase-to-phase Vavg, the arithmetic mean of the 3 phase-to-phase voltages:
Vavg = (V12 + V23 + V31)/3

Phase-to-neutral Vavg, the arithmetic mean of the 3 phase-to-neutral voltages (4-pole circuit
breakers or 3-pole circuit breakers wired and configured with the ENVT):
Vavg = (V1N + V2N + V3N)/3
Measuring the Current and Voltage Phase Unbalances
Micrologic X control units calculate the current unbalance for each phase (3 values).
The current unbalance is a percentage of the average current:
I1- Iavg
<0
I1
I2
I3
I2 - Iavg
>0
I3 - Iavg
<0
Iavg
Micrologic X control units calculate:
 The phase-to-phase voltage unbalance for each phase (3 values)
 The phase-to-neutral (if present) voltage unbalance for each phase (3 values)
The voltage unbalance is expressed as a percentage compared to the average value of the electrical
quantity (Vavg):
Vjk - Vavg
Vjk unbalance (%) = ------------------------- × 100 where jk = 12, 23, 31
Vavg
DOCA0102EN-00 05/2016
115
Metering Functions
Maximum/Minimum Values
The Micrologic X control unit determines in real time the maximum (MAX) and minimum (MIN) value
reached by the following electrical quantities for the period from the last reset to the present time:
 Current: phase and neutral currents, average currents and current unbalances
 Voltage: phase-to-phase and phase-to-neutral voltages, average voltages, and voltage unbalances
 Power: total power and phase power (active, reactive, and apparent)
 Total harmonic distortion: the total harmonic distortion THD for both current and voltage
 Frequency
 The maximum value (MAXMAX) of all phase currents
 The minimum value (MINMIN) of all phase currents
Resetting Maximum/Minimum Values
The maximum and minimum values can be reset:
 On the Micrologic X display screen, at:
 Home → Measures → Current




Home → Measures → Voltage

Home → Measures → Power

Home → Measures → Frequency

Home → Measures → I Harmonics

Home → Measures → V Harmonics
With Ecoreach software
With Masterpact MTZ mobile App
By sending a command using the communication network. This function is password-protected.
NOTE: The maximum and minimum power factors and cos Φ can be reset only:
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a command using the communication network. This function is password protected.
All maximum and minimum values for the group of electrical quantity selected are reset.
Resetting maximum and minimum generates a low severity event, which is logged in the Metering history,
as follows:
User message
116
History
Severity
Reset Min/Max currents
Metering
Low
Reset Min/Max voltages
Metering
Low
Reset Min/Max power
Metering
Low
Reset Min/Max frequency
Metering
Low
Reset Min/Max harmonics
Metering
Low
Reset Min/Max power factor
Metering
Low
DOCA0102EN-00 05/2016
Metering Functions
Power Metering
Presentation
The control unit calculates the electrical quantities required for power management:
 The real-time values of the:
 Active powers (total Ptot and per phase) in kW
 Reactive powers (total Qtot and per phase) in kVAR
 Apparent powers (total Stot and per phase) in kVA



The maximum and minimum values for each of these powers
The cos ϕ and power factor (PF) indicators
The operating quadrant and type of load (leading or lagging)
All these electrical quantities are continuously calculated and their value is updated once a second at rated
frequency.
Principle of Power Metering
The control unit calculates the power values from the current and voltage samples.
The calculation principle is based on:
 Definition of the powers
 Algorithms depending on the type of circuit breaker (4-pole or 3-pole)
 Set value of the power sign (circuit breaker powered from the top or underside)
The calculation algorithm is explained in the specific topic (see page 120).
Calculations use harmonics up to the fifteenth.
Total Power Calculation Method
The total reactive and apparent power can be calculated by one of the two following methods:
 Vector
 Arithmetic
NOTE: The total active power is calculated as a sum of the phase powers: Ptot = P1 + P2 + P3
The calculation method can be set in the following ways:
 On the Micrologic X display screen, at Home → Configuration → Measures → Total P Calcul
 With Ecoreach software
 With Masterpact MTZ mobile App
3-Pole Circuit Breaker, 4-Pole Circuit Breaker
The calculation algorithm depends on the presence or absence of voltage metering on the neutral
conductor.
4-pole or 3-pole with ENVT: 3-wattmeter method
3-pole without ENVT: 2-wattmeter method
W2
W1
I1
DOCA0102EN-00 05/2016
V1N
I2
V2N
I3
V3N
I1
U12
I2
I3
U32
117
Metering Functions
4-pole or 3-pole with ENVT: 3-wattmeter method
3-pole without ENVT: 2-wattmeter method
When there is voltage metering on the neutral (4-pole or 3pole circuit breaker with ENVT wired and configured), the
control unit measures the power by using 3 single-phase
loads downstream.
When there is no voltage metering on the neutral (3pole circuit breaker), the control unit measures the
power:
 Using the current from 2 phases (I1 and I3) and
composite voltages from each of these 2 phases in
relation to the third (V12 and V23)
 using the fact that by definition the current in the
neutral conductor is zero:
I1 + I2 + I3 = 0
The following table lists the metering options:
Method
3-pole circuit
breaker, nondistributed neutral
3-pole circuit
breaker, distributed
neutral
3-pole circuit breaker,
distributed neutral
(ENVT wired and
configured)
4-pole circuit breaker
2 wattmeters
X1
–
–
3 wattmeters
–
–
1 The measurement is incorrect once there is current circulating in the neutral.
3-Pole Circuit Breaker, Distributed Neutral
Declare the ENVT in the system type setting (see page 114).
NOTE: Declaration of the ENVT alone does not result in correct calculation of the powers. It is essential to
connect the wire from the ENVT to the neutral conductor.
Power Sign and Operating Quadrant
By definition, the active powers are:
 Signed + when they are consumed by the user, that is, when the device is acting as a receiver.
 Signed - when they are supplied by the user, that is, when the device is acting as a generator.
By definition, the reactive powers have:
The same sign as the active energies and powers when the current lags behind the voltage, that is,
when the device is inductive (lagging).
 The opposite sign to the active energies and powers when the current is ahead of the voltage, that is,
when the device is capacitive (leading).

These definitions therefore determine 4 operating quadrants (Q1, Q2, Q3, and Q4):
Q2
P<0
Q>0
P>0
Q1
Q>0
Lead
(Ahead)
Lag
(Delay)
Lag
(Delay)
Lead
(Ahead)
P<0
Q3
Q<0
P>0
Q<0
Q4
NOTE: The power values are:
Signed when read using the communication network.
 Not signed when displayed on the Micrologic X display screen.

118
DOCA0102EN-00 05/2016
Metering Functions
Power Sign Convention
The sign for the power running through the circuit breaker depends on the type of connection:
 Circuit breakers with the active power flowing from upstream (top) to downstream (bottom) should be
set with the power sign P+
 Circuit breakers with the active power flowing from downstream (bottom) to upstream (top) should be
set with the power sign PSet the power sign convention as follows:
 On the Micrologic X display screen, on the screens Home → Configuration → Network → Power sign.
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network (password-protected)
DOCA0102EN-00 05/2016
119
Metering Functions
Power Calculation Algorithm
Presentation
The algorithms are given for both calculation methods (2 wattmeters and 3 wattmeters). The power
definitions and calculation are given for a network with harmonics.
With the 2-wattmeter calculation method, it is not possible to deliver power metering for each phase.
All the calculated quantities are displayed:
 On the Micrologic X display screen, on the screens Home → Measures → Power
 On the Ecoreach software
 On the Masterpact MTZ mobile App
 By a remote controller using the communication network
Active Powers
Metering on a 3-pole or 4-pole circuit breaker with ENVT
wired and configured
Metering on a 3-pole circuit breaker without ENVT wired
and configured
The active power for each phase and total active power is Only the total active power can be calculated.
calculated.
–
Pp =
Vp(t)Ip(t)dt
T ∫
Where p=1, 2, 3 (phase)
Ptot = P1 + P2 + P3
Ptot = Pw1 + Pw2
PW1 and PW2 are the fictitious powers calculated by the 2-wattmeter method.
Reactive Power
Metering on a 3-pole or 4-pole circuit breaker with ENVT
wired and configured
Metering on a 3-pole circuit breaker without ENVT wired
and configured
The reactive power with harmonics for each phase and
total reactive power is calculated.
Only the total reactive power can be calculated.
–
Qi = ± Si 2− Pi 2
Where i=1, 2, 3 (phase)
 With vector method:
 With arithmetic method:
Qtot V= Q1 + Q2 + Q3
 With arithmetic method:
QtotA=
Stot 2 − Ptot
QtotA=
Stot 2 − Ptot
Apparent Power
Metering on a 3-pole or 4-pole circuit breaker with ENVT
wired and configured
Metering on a 3-pole or 4-pole circuit breaker without
ENVT wired and configured
The apparent power for each phase and total apparent
power is calculated
Only the total apparent power can be calculated.
Sp = (Vp. Ip) where p = 1, 2, 3 (phase)
–
 With vector method:
 With vector method:
Stotv =
120
Ptot + Qtot
Stotv =
Ptot 2 + Qtot 2
 With arithmetic method:
 With arithmetic method:
Stot A= S1 + S2 + S3
StotA= S1 + S2 + S3
DOCA0102EN-00 05/2016
Metering Functions
Energy Metering
Presentation
The control unit calculates the different types of energy using energy meters and provides the values of:
 The total active energy Ep, the active energy supplied EpOut, and the active energy consumed EpIn
 The total reactive energy Eq, the reactive energy supplied EqOut, and the reactive energy consumed
EqIn
 The total apparent energy Es
The energy values are calculated, and shown as an hourly consumption. Values update once a second at
rated frequency. Values are stored in non-volatile memory once an hour.
NOTE: To ensure reliable energy measurement across the current range the control unit must be powered
with an external 24 Vdc power supply or VPS module (see page 23).
NOTE: The energies per phase are available as an option (see page 129). They are calculated using the
same principles as total energies.
Principle of Energy Calculation
By definition energy is the integration of the real-time power over a period T. The integration period T is
equal to a number of cycles equal to the rated frequency.
Partial Energy Meters
For each type of energy, active or reactive, a partial consumed energy meter and a partial supplied energy
meter calculate the accumulated energy by incrementing once a second:
 The contribution of the consumed power to the consumed energy meter
Ein(t)(consumed) = Ein(t - 1) + (Gin(t))/3600 where Gin = Ptot or Qtot consumed
 The contribution as an absolute value of the supplied power for the supplied energy meter (supplied
power is always counted negatively)
Eout(t)(supplied) = Eout(t - 1) + (|Gout(t)|)/3600 where Gin = Ptot or Qtot supplied
For each partial energy meter two types of counter are available: one which can be reset and one which
cannot be reset.
Energy Meters
From the partial energy meters and for each type of energy, active or reactive, an energy meter provides
either of the following measurements once a second:
 The absolute energy, by adding the consumed and supplied energies together. The energy
accumulation mode is absolute.
E(t)absolute = Ein(t) + Eout(t)
 The signed energy, by differentiating between consumed and supplied energies. The energy
accumulation mode is signed.
E(t)signed = Ein(t) - Eout(t)
The apparent energy Es is always counted positively.
Selecting Energy Calculation
The information sought determines calculation selection:
 The absolute value of the energy that has crossed the poles of a circuit breaker or the cables of an item
of electrical equipment is relevant for maintenance of an installation.
 The signed values of the energy supplied and the energy consumed are required to calculate the
economic cost of an item of equipment.
By default, absolute energy accumulation mode is configured.
Select the energy calculation mode using any of the following methods:
 On the Micrologic X display screen, on the screens Home → Configuration → Measures → E calcul
 With Ecoreach software
 With Masterpact MTZ mobile App
 By or sending a setting command using the communication network.This function is passwordprotected.
DOCA0102EN-00 05/2016
121
Metering Functions
Resetting Energy Meters
The energy meters can be reset:
 On the Micrologic X display screen, on the screens Home → Measures → Energy → Reset Counter
 With Ecoreach software
 With Masterpact MTZ mobile App
 By writing a reset command using the communication network. This function is password-protected.
All energy meters are reset together, except the 2 active energy accumulation meters (EpIn and EpOut)
that cannot be reset.
Resetting the energy meters generates a low severity event, which is logged in the Metering history.
Presetting Energy Meters
122
DOCA0102EN-00 05/2016
Metering Functions
Harmonic Currents and Voltages
Origin and Effects of Harmonics
Many nonlinear loads present on an electrical network create harmonic currents in the electrical network.
These harmonic currents:
 Distort the current and voltage waves.
 Degrade the quality of the distributed energy.
These distortions, if they are significant, can result in:
 Malfunctions or degraded operation in the powered devices.
 Unwanted heat rise in the devices and conductors.
 Excessive power consumption.
These various problems increase the system installation and operating costs. It is therefore necessary to
control the energy quality carefully.
Definition of a Harmonic
A periodic signal is a superimposition of:
 The original sinusoidal signal at the fundamental frequency (for example, 50 Hz or 60 Hz)
 Sinusoidal signals whose frequencies are multiples of the fundamental frequency called harmonics
 Any DC component
This periodic signal is broken down into a sum of terms:
where:
 y0: value of the DC component
 yn: rms value of the nth harmonic
 ω: pulsation of the fundamental frequency
 ϕn: phase displacement of harmonic component n
NOTE: The first harmonic is called the fundamental.
Example of a current wave distorted by a harmonic component:
Irms
H1 (50 Hz)
H3 (150 Hz)
H5 (250 Hz)
DOCA0102EN-00 05/2016
Irms: rms value of the harmonic waveform
I1: fundamental current
I3: third order harmonic current
I5: fifth order harmonic current
123
Metering Functions
Power Quality Indicators
Presentation
The control unit calculates total harmonic distortion for voltages and currents.
Total harmonic distortions related to the fundamental value (THD(V), THD(I)) are displayed on the
Micrologic X display screen.
In addition, total harmonic distortions related to rms values (THD-R(V), and THD-R(I)) can be displayed
with Ecoreach software
Displaying the Total Harmonic Distortion
The total harmonic distortion THD can be displayed in the following ways:
 On the Micrologic X display screen:
 THD(I) at Home → Measures → I Harmonics
 THD(V) at Home → Measures → V Harmonics



With Ecoreach software
On Masterpact MTZ mobile App
Through the communication network
Current THD
The current THD is a percentage of the rms value of harmonic currents of ranks greater than 1 in relation
to the rms value of the fundamental current (first order). The control unit calculates the total harmonic
current distortion THD up to the fifteenth harmonic:
15
∑ Inrms
THD (I) = 100 n = 2
I1rms
The current THD can be higher than 100%.
Use the total harmonic distortion THD(I) to assess the distortion of the current wave with a single number.
The table below shows the THD limit values.
THD(I) Value
Comments
THD(I) < 10%
Low harmonic currents: little risk of malfunctions.
10% < THD(I) < 50%
Significant harmonic currents: risk of heat rise, oversizing of supplies.
50% < THD(I)
High harmonic currents: the risks of malfunction, degradation, and dangerous heat rise
are almost certain unless the installation is calculated and sized with this restriction in
mind.
Distortion of the current wave created by a nonlinear device with a high THD(I) can lead to distortion of the
voltage wave, depending on the level of distortion and the source impedance. This distortion of the voltage
wave affects all of the devices powered by the supply. Sensitive devices on the system can therefore be
affected. A device with a high THD(I) may not be affected itself but could cause malfunctions on other,
more sensitive devices on the system.
NOTE: THD(I) metering is an effective way of determining the potential for problems from the devices on
electrical networks.
Voltage THD
The voltage THD is the percentage the rms value of harmonic voltages greater than 1 in relation to the rms
value of the fundamental voltage (first order). The control unit calculates the voltage THD up to the fifteenth
harmonic:
15
THD (V) =
∑ Vnrms
n=2
V1rms
This factor can in theory be higher than 100% but is in practice rarely higher than 15%.
124
DOCA0102EN-00 05/2016
Metering Functions
Use the total harmonic distortion THD(V) to assess the distortion of the voltage wave with a single number.
The limit values below are commonly evaluated by energy distribution companies:
THD(V) Value
Comments
THD(V) < 5%
Insignificant distortion of the voltage wave: little risk of malfunctions.
5% < THD(V) < 8%
Significant distortion of the voltage wave: risk of heat rise and malfunctions.
8% < THD(V)
Significant distortion of the voltage wave: there is a high risk of malfunction unless the
installation is calculated and sized based on this distortion.
Distortion of the voltage wave affects all devices powered by the supply.
NOTE: Use the THD(V) indication to assess the risks of disturbance of sensitive devices supplied with
power.
Current THD-R
The current THD-R is a percentage of the rms value of harmonic currents of ranks greater than 1 in relation
to the total harmonic current. The control unit calculates the total harmonic current distortion THD-R up to
the fifteenth harmonic using the following equation:
The current THD-R cannot be higher than 100%.
Use the total harmonic distortion THD-R(I) to assess the distortion of the current wave with a single
number. The table below shows the THD-R limit values.
THD-R(I) Value
Comments
THD-R(I) < 10%
Low harmonic currents: little risk of malfunctions.
10% < THD-R(I) < 50%
Significant harmonic currents: risk of heat rise, oversizing of supplies.
50% < THD-R(I)
High harmonic currents: the risks of malfunction, degradation, and dangerous heat rise
are almost certain unless the installation is calculated and sized with this restriction in
mind.
Distortion of the current wave created by a nonlinear device with a high THD-R(I) can lead to distortion of
the voltage wave, depending on the level of distortion and the source impedance. This distortion of the
voltage wave affects all of the devices powered by the supply. Sensitive devices on the system can
therefore be affected. A device with a high THD-R(I) may not be affected itself but could cause
malfunctions on other, more sensitive devices on the system.
NOTE: THD-R(I) metering is an effective way of determining the potential for problems from the devices
on electrical networks.
Voltage THD-R
The voltage THD-R is the percentage the rms value of harmonic voltages greater than 1 in relation to the
total harmonic voltage. The control unit calculates the total harmonic voltage distortion THD-R up to the
fifteenth harmonic.
Use the total harmonic distortion THD-R(V) to assess the distortion of the voltage wave with a single
number. The limit values below are commonly evaluated by energy distribution companies:
THD-R(V) Value
Comments
THD-R(V) < 5%
Insignificant distortion of the voltage wave: little risk of malfunctions.
5% < THD-R(V) < 8%
Significant distortion of the voltage wave: risk of heat rise and malfunctions.
8% < THD-R(V)
Significant distortion of the voltage wave: there is a high risk of malfunction unless the
installation is calculated and sized based on this distortion.
Distortion of the voltage wave affects all devices powered by the supply.
NOTE: Use the THD-R(V) indication to assess the risks of disturbance of sensitive devices supplied with
power.
DOCA0102EN-00 05/2016
125
Metering Functions
Power Factor PF and cos ϕ Measurement
Power Factor PF
The control unit calculates:
 The power factor per phase PF1, PF2, PF3, from the phase active and apparent powers
 The total power factor PF from the total active power Ptot and the total apparent power Stot
NOTE: Stot is the vector or arithmetic total apparent power, depending on the setting (see page 120).
This indicator qualifies:
The oversizing necessary for the installation power supply when harmonic currents are present
 The presence of harmonic currents by comparison with the value of the cos ϕ (see below)

cos ϕ
The control unit calculates:
The cos ϕ per phase from the phase active and apparent powers of the fundamental
 the cos ϕ from the total active power Pfundtot and the total apparent power Sfundtot of the fundamental
(first order)

This indicator qualifies use of the energy supplied.
Power Factor PF and cos ϕ when Harmonic Currents are Present
If the supply voltage is not too distorted, the power factor PF is expressed as a function of the cos ϕ and
the THD(I) by:
cos ϕ
PF ≈ -----------------------------------1 + THD ( I ) 2
The graph below specifies the value of PF/cos ϕ as a function of the THD(I):
FP/cos J
1.2
0.8
0.6
0.4
0.2
50
100
150 THD(I) %
By comparing the 2 values, it is possible to estimate the level of harmonic deformation on the supply.
Sign for the Power Factor PF and cos ϕ
2 sign conventions can be applied for these indicators:
IEC convention: The sign for these indicators complies strictly with the signed calculations of the powers
(that is, Ptot, Stot, Pfundtot, and Sfundtot).
 IEEE convention: The indicators are calculated in accordance with the IEC convention but multiplied by
the inverse of the sign for the reactive power (Q).

126
DOCA0102EN-00 05/2016
Metering Functions
The figures below define the sign for the power factor PF and cos ϕ by quadrant (Q1, Q2, Q3 and Q4) for
both conventions:
IEC Convention
Operation in all quadrants (Q1, Q2, Q3, Q4)
Q2
Q>0
PF < 0
P>0 Q>0
Inductive
Q<0
Q1
cos J > 0
PF > 0
Inductive
Capacitive
P<0
0+
Q1
P<0
Values of cos ϕ in receiver operation (Q1, Q4)
-1
Capacitive
PF < 0
P>0
Q<0
+1
cos J > 0
PF > 0
Q3
Q4
Q4
0+
IEEE Convention
Operation in all quadrants (Q1, Q2, Q3, Q4)
Q2
Q>0
P>0
PF > 0
Q>0
Leading
Q<0
Q1
cos J < 0
PF < 0
Lagging
Lagging
P<0
0-
Q1
P<0
Values of cos ϕ in receiver operation (Q1, Q4)
-1
Leading
P>0
PF < 0
Q<0
+1
cos J > 0
PF > 0
Q3
Q4
0+
Q4
NOTE: For a device, a part of an installation which is only a receiver (or generator), the advantage of the
IEEE convention is that it adds the type of reactive component to the PF and cos ϕ indicators:
 Lead: positive sign for the PF and cos ϕ indicators
 Lag: negative sign for the PF and cos ϕ indicators
Managing the Power Factor PF and cos ϕ: Minimum and Maximum Values
Managing the PF and cos ϕ indicators consists of:
 Defining critical situations
 Implementing monitoring of the indicators in accordance with the definition of critical situations
Situations are considered critical when the values of the indicators are around 0. The minimum and
maximum values of the indicators are defined for these situations.
The figure below illustrates the variations of the cos ϕ indicator (with the definition of the cos ϕ MIN/MAX)
and its value according to IEEE convention for a receiver application:
-0
Q1
-0
Q1
MIN cos J
-1
+1
-1
+1
cos J
cos J
+0
DOCA0102EN-00 05/2016
Q4
+0
Q4
MAX cos J
Arrows indicating the cos ϕ variation range for the load in operation
Critical zone + 0 for highly capacitive devices (shaded green)
127
Metering Functions
Critical zone - 0 for highly inductive devices (shaded red)
Minimum position of the load cos ϕ (lagging): red arrow
Variation range of the value of the load cos ϕ (lagging): red
Maximum position of the load cos ϕ (leading): green arrow
Variation range of the value of the load cos ϕ (leading): green
PF MAX (or cos ϕ MAX) is obtained for the smallest positive value of the PF (or cos ϕ) indicator.
PF MIN (or cos ϕ MIN) is obtained for the largest negative value of the PF (or cos ϕ) indicator.
NOTE: The minimum and maximum values of the PF and cos ϕ indicators are not physically significant:
they are markers which determine the ideal operating zone for the load.
Monitoring the cos ϕ and Power Factor PF Indicators
According to the IEEE convention, critical situations in receiver mode on a capacitive or inductive load are
detected and discriminated (2 values).
The table below indicates the direction in which the indicators vary and their value in receiver mode.
IEEE Convention
Operating quadrant
Q1
Q4
Direction in which the cos ϕ (or PFs) vary over the operating range
MIN
Value of the cos ϕ (or PFs) over the operating range
MAX
0...-0.3...-0.8...-1
MIN
MAX
+1...+0.8...+0.4...0
The quality indicator MAX and MIN indicate both critical situations.
According to the IEC convention, critical situations in receiver mode on a capacitive or inductive load are
detected but not discriminated (one value).
The table below indicates the direction in which the indicators vary and their value in receiver mode.
IEC Convention
Operating quadrant
Q1
Q4
Direction in which the cos ϕ (or PFs) vary over the operating range
MAX
Value of the cos ϕ (or PFs) over the operating range
MIN
0...+0.3...+0.8...+1
MIN
MAX
+1...+0.8...+0.4...0
The quality indicator MAX indicates both critical situations.
Selecting the Sign Convention for the cos ϕ and Power Factor PF
Set the sign convention for the cos ϕ and PF indicators as follows:
 With Ecoreach software
 With Masterpact MTZ mobile App
 By sending a setting command using the communication network.This function is password-protected.
The IEEE convention is applied by default.
The selection is displayed on the Micrologic X display screen, at Home → Configuration → Measures →
PF/VAR Conv.
128
DOCA0102EN-00 05/2016
Metering Functions
Section 4.2
Optional Metering Functions
Optional Metering Functions
Energy per Phase
Presentation
The Energy per Phase Digital Module enables the analysis of energy consumption per phase. It is
especially recommended for low voltage installations having a large amount of unbalanced loads. At the
point of measurement, it allows the calculation of and displays the consumed and supplied energy on each
phase of the network. It calculates and displays active, reactive and apparent energy per phase.
The energy per phase is calculated using the method described for calculating energy (see page 121).
Prerequisites
The Energy per Phase Digital Module is an optional Digital Module, which can be purchased and installed
on a Micrologic X control unit (see page 20).
The prerequsites are:
 The Masterpact MTZ mobile App must be installed on a smartphone
 The smartphone must be connected to the Micrologic X control unit through:
 Bluetooth: the control unit must be powered
 NFC: the control unit does not need to be powered

The Micrologic X date and time must be up to date
Measurement Availability
The measurements can be consulted in the following ways:
 With Masterpact MTZ mobile App
 With Ecoreach software
 By sending a command using the communication network
DOCA0102EN-00 05/2016
129
Metering Functions
Examples of Screens in the Masterpact MTZ mobile App
The following table shows examples of screens from the Masterpact MTZ mobile App:
75%
13:52
ÅEnergy Per Pha...
75%
13:52
ÅEnergy Per Pha...
MTZ2 10 MAIN
MTZ2 10 MAIN
Phase A
Active Delivered
Reactive Received
4001
4002
kWh
kVArh
Reactive Delivered
4003
kVArh
Apparent
4004
kVAh
Active Received
5000
kWh
Active Delivered
5001
kWh
Reactive Received
5002
kVArh
Reactive Delivered
5003
kVArh
Apparent
5004
kVAh
Active Received
6000
kWh
Active Delivered
6001
kWh
Reactive Received
6002
kVArh
Reactive Delivered
6003
kVArh
Apparent
6004
kVAh
Active Received
4000
kWh
Active Delivered
4001
kWh
Reactive Received
4002
kVArh
Reactive Delivered
4003
kVArh
Apparent
4004
kVAh
Phase B
Phase B
Active Received
5000
kWh
Active Delivered
5001
kWh
Reactive Received
5002
kVArh
Reactive Delivered
5003
kVArh
Apparent
5004
kVAh
Phase C
Phase C
Active Received
Active Delivered
6000
6001
kWh
kWh
Characteristics
Measurement
Range
Accuracy range
Active energy IN per phase
-10,000,000–10,000,000
kWh
+/-1 %
Active energy OUT per phase
-10,000,000–10,000,000
kWh
+/-1 %
Reactive energy IN per phase
-10,000,000–10,000,000
kVARh
+/-1 %
Reactive energy OUT per phase
-10,000,000–10,000,000
kVARh
+/-1 %
Apparent energy per phase
0–10,000,000
kVARh
+/-1 %
Resetting Energy Per Phase
Energy per phase can be reset and preset as other energy measurements (see page 122).
130
DOCA0102EN-00 05/2016
Micrologic X
Diagnostic and Maintenance Functions
DOCA0102EN-00 05/2016
Chapter 5
Diagnostic and Maintenance Functions
Diagnostic and Maintenance Functions
What Is in This Chapter?
This chapter contains the following sections:
Section
DOCA0102EN-00 05/2016
Topic
Page
5.1
Maintenance Assistance
132
5.2
Standard Diagnostic Functions
135
5.3
Optional Diagnostic Functions
144
131
Diagnostic and Maintenance Functions
Section 5.1
Maintenance Assistance
Maintenance Assistance
What Is in This Section?
This section contains the following topics:
Topic
132
Page
Maintenance Schedule
133
Circuit Breaker Overview
134
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Maintenance Schedule
Presentation
The maintenance schedule function records the date of the last maintenance operation.
Operating Principle
The date of the last maintenance operation is either recorded automatically after a secondary injection test
or configured manually.
Function Settings
Manual configuration can be made in the following ways:
 With Ecoreach software
 By sending a setting command using the communication network
DOCA0102EN-00 05/2016
133
Diagnostic and Maintenance Functions
Circuit Breaker Overview
Presentation
The overview function displays a description of the circuit breaker, including:
 Name
 Rating
 Performance
 Number of poles
Function Output
The information is available as follows:
 On the Micrologic X display screen at Home → Maintenance → CB overview
 With Ecoreach software
 With Masterpact MTZ mobile App
 On a remote controller using the communication network
134
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Section 5.2
Standard Diagnostic Functions
Standard Diagnostic Functions
What Is in This Section?
This section contains the following topics:
Topic
DOCA0102EN-00 05/2016
Page
Health Monitoring
136
Circuit Breaker Monitoring
137
Monitoring the Tripping Function
138
Monitoring the Opening/Closing Function
139
Monitoring the Contact State
140
Monitoring the Internal Functioning of the Micrologic X control unit
141
Monitoring the ULP Modules
142
Monitoring the Circuit Breaker Service Life
143
135
Diagnostic and Maintenance Functions
Health Monitoring
Presentation
The health of the Micrologic X control unit is assessed by an internal analysis of the following indicators:
 Circuit breaker monitoring state
 Contact state (see page 140)
 Circuit breaker lifespan (see page 143)
Health is presented with one of the following icons:

OK if no high- or medium-level event is detected

Orange icon if at least one medium-level event is detected

Red icon if at least one high-level event is detected
NOTE: Quick View on the Micrologic X display screen displays health with the OK icon
is detected. When an event is detected a pop-up screen is displayed (see page 169).
when no event
Function Outputs
Details about health can be accessed:
 With Ecoreach software
 With Masterpact MTZ mobile App through Bluetooth
 On a remote controller using the communication network
136
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Circuit Breaker Monitoring
Presentation
The Micrologic X control unit assesses the health of the circuit breaker by an internal monitoring of the
following functions:
 Tripping function
 Closing and opening function
 Earth-leakage function (for Micrologic 7.0 X)
 Control unit state
Circuit Breaker Monitoring Outputs
The circuit breaker monitoring state is presented with one of the following icons:

if no high- or medium-level event is detected

if at least one medium-level event is detected

if at least one high-level event is detected
The circuit breaker monitoring state is displayed:
On Ecoreach software
 On Masterpact MTZ mobile App through Bluetooth
 On a remote controller using the communication network

DOCA0102EN-00 05/2016
137
Diagnostic and Maintenance Functions
Monitoring the Tripping Function
Presentation
The Micrologic X control unit provides constant monitoring of the internal circuit of the circuit breaker, from
the current sensors to the tripping actuator (Mitop).
Operating Principle
The result of the monitoring is indicated by the ready LED on the front face of the Micrologic X control unit,
as follows:
 The ready LED is flashing
 The circuit breaker is closed and the internal current is greater than 50 A (if the Micrologic X control
unit is not powered by an auxiliary source)
 The internal circuit of the circuit breaker is functioning correctly

The ready LED is off: a malfunction detected in the internal circuit
Tripping Data
The following data about the tripping function is logged by the Micrologic X control unit:
 Total number of trips
 The name and date of the last test trip
The tripping data is displayed:
With Ecoreach software
 With the Masterpact MTZ mobile App through Bluetooth
 With the Masterpact MTZ mobile App through NFC
 On a remote controller using the communication network

Predefined Events
The function generates the following events:
138
Event message
History
Severity
Micrologic self-test major malfunction
Diagnostic
High
Internal current sensors (CT) disconnected
Diagnostic
High
External neutral current sensor (ENCT)
disconnected
Diagnostic
High
Earth leakage (Vigi) sensor disconnected
Diagnostic
High
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Monitoring the Opening/Closing Function
Presentation
The Micrologic X control unit monitors communicating voltage releases.
It also counts the number of charging sequences performed by the MCH gear motor.
Monitoring the Communicating Voltage Releases
The function monitors the presence and functioning of the following:
 The communicating MN undervoltage release
 The communicating MX opening voltage release
 The communicating XF closing voltage release
Events are generated for a detected malfunction or when the presence of a communicating voltage release
is no longer detected.
Counting MCH Gear Motor Charging Sequences
The Micrologic X control unit counts the number of charging sequences performed by the MCH gear motor
to rearm the closing mechanism after each circuit breaker closure.
Events are generated when the number reaches 80% and 100% of the maximum.
Predefined Events
The function generates the following events:
Event
DOCA0102EN-00 05/2016
History
Severity
MX1 opening release malfunction
Diagnostic
Medium
MX1 opening release is no longer detected.
Diagnostic
Medium
MX2/MN opening release malfunction
Diagnostic
Medium
MX2/MN opening release is no longer detected.
Diagnostic
Medium
XF closing release malfunction
Diagnostic
Medium
XF closing release is no longer detected.
Diagnostic
Medium
MCH has reached 80% of the maximum number of operations
Diagnostic
Medium
MCH has reached the maximum number of operations
Diagnostic
High
139
Diagnostic and Maintenance Functions
Monitoring the Contact State
Presentation
The pole contacts undergo wear due to the number of operating cycles with current and interrupted current
during short circuits. It is recommended to check them at periodic intervals to decide whether the contacts
must be changed or not. To avoid regular inspection of the contacts and the arc chute, the contact wear
estimate helps with the planning of visual inspections based on the estimated wear (from 0% - new contact
- to 100% - totally worn contact).
The contact wear increases every time the circuit breaker interrupts or establishes the circuit with current.
Function Outputs
The function displays the contact wear on Ecoreach and Masterpact MTZ mobile App:

OK if wear < 60%

Medium level alarm if wear > 60% or > 95%

High-level alarm if wear > 99%
Predefined Events
The function generates the following events:
140
User message
History
Severity
Contact 60% worn out
Diagnostic
Medium
Contact 95% worn out
Diagnostic
Medium
Contact 100% worn out
Diagnostic
High
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Monitoring the Internal Functioning of the Micrologic X control unit
Presentation
The Micrologic X control unit carries out a series of autotests to monitor:
 Correct internal functioning
 The state of the internal battery for power for power supply to trip-cause LEDs and red service LED
 The external sensors (ENCT)
 Wireless communication
Operating Principle
The ready LED and fault-trip indication LEDs provide visual information on the health of the Micrologic X
control unit. Detected malfunctions can be classified as high or medium severity events:
 Medium severity event indicating minor malfunction detected
 All fault-trip LEDs are lit
 The ready LED is flashing
 An orange pop-up screen is displayed
 Current (LSI G/V) protection unaffected

High severity event indicating major malfunction detected:
 All fault-trip LEDs are lit
 The ready LED is off
 A red pop-up screen is displayed
 Current (LSI G/V) protection can be affected
 Control unit must be replaced
An event is generated each time a malfunction is detected.
Predefined Events
The function generates the following events:
DOCA0102EN-00 05/2016
User message
History
Severity
Current protection reset to default settings
Diagnostic
High
Reading accessing protection settings error
Diagnostic
Medium
Product self-test minor malfunction
Diagnostic
Medium
Metering and advanced protection malfunction
Diagnostic
Medium
Display screen or wireless malfunction
Diagnostic
Medium
Replace battery
Diagnostic
Medium
Minor- Corrected ASIC internal error warning
Diagnostic
Medium
FW internal error
Diagnostic
Medium
Sensor plug reading error
Diagnostic
High
Discrepancy ASIC configuration
Diagnostic
High
Critical hardware module discrepancy
Diagnostic
Medium
Critical firmware module discrepancy
Diagnostic
Medium
Non-critical hardware module discrepancy
Diagnostic
Medium
Non-critical firmware module discrepancy
Diagnostic
Medium
ULP module address conflict
Diagnostic
Medium
Firmware discrepancy within product
Diagnostic
Medium
NFC malfunction
Diagnostic
Medium
Bluetooth malfunction
Diagnostic
Medium
IEEE 802.15.4 malfunction
Diagnostic
Medium
141
Diagnostic and Maintenance Functions
Monitoring the ULP Modules
Presentation
The Micrologic X control unit monitors the connection and compatibility of settings of the following ULP
modules:
 IO modules
 IFE Ethernet Interface
Predefined Events
The function generates the following events:
142
User message
History
Severity
IO1 module connection lost
Diagnostic
Medium
IO2 module connection lost
Diagnostic
Medium
IFE connection lost
Diagnostic
Medium
Conflict with IO module configuration
Configuration
Medium
ULP module address conflict
Diagnostic
Medium
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Monitoring the Circuit Breaker Service Life
Presentation
Circuit breaker service life depends on the daily number of operating cycles with or without current. The
maximum service life depends on the number of operating cycles indicated in the catalog under
mechanical and electrical durability. The service life indicator helps anticipate the replacement of the
breaking block before mechanical or electrical breakdown.
Operating Principle
Each time the circuit breaker operates (performs an open and close cycle with or without current), the
corresponding mechanical or electrical operating counter is incremented. The Micrologic X control unit
calculates the number of cycles performed as a percentage of the maximum number of operations. The
percentage of lifetime remaining for the device is calculated.
Function Outputs
The circuit breaker service life is presented as one of the following:

OK if remaining life > 20%

Medium level alarm if remaining life < 20%

High-level alarm if remaining life = 0%
It is displayed in the following ways:
With Ecoreach software
 With Masterpact MTZ mobile App through Bluetooth
 On a remote controller using the communication network

Predefined Events
The function generates the following events:
User message
History
Severity
Circuit breaker operations has passed 80% of
service life
Diagnostic
Medium
Circuit breaker operations has passed the service life Diagnostic
DOCA0102EN-00 05/2016
High
143
Diagnostic and Maintenance Functions
Section 5.3
Optional Diagnostic Functions
Optional Diagnostic Functions
What Is in This Section?
This section contains the following topics:
Topic
144
Page
Power Restoration Assistant Digital Module
145
Masterpact Operation Assistant Digital Module
146
Waveform Capture on Trip Event Digital Module
147
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Power Restoration Assistant Digital Module
Presentation
The Power Restoration Digital Module helps to reduce the time without a power supply for critical load
(mean time to recovery (MTTR)) after a trip, an opening, or a loss of upstream supply.
The Digital Module provides the following assistance to help in the decision to restore power:
 Displays information on events and circuit breaker status
 Assists in determining the cause of events
Prerequisites
The Power Restoration Digital Module is an optional Digital Module, which can be purchased and installed
on a Micrologic X control unit (see page 20).
The prerequsites are:
 The Masterpact MTZ mobile App must be installed on a smartphone
 The smartphone must be connected to the Micrologic X control unit through:
 Bluetooth: the control unit must be powered
 NFC: the control unit does not need to be powered

The Micrologic X date and time must be up to date
Availability of Assistance
Availability of features differs depending on the type of connection to the Digital Module:
 Through Bluetooth
 Through NFC (connection can be made when control unit is not powered)
Examples of Screens
Some examples of the screens available on the Digital Module are provided:
Orange F
4G
100% 13:25
ÅHelp to restore power
MTZ2 10 MAIN
Orange F
4G
100% 13:25
ÅCheck Trip
MTZ2 10 MAIN
Check circuit breaker state
OFF
ON
Pull
Circuit breaker is tripped
Check mechanical indicator
if in or out
None of these states
OUT
DOCA0102EN-00 05/2016
IN
145
Diagnostic and Maintenance Functions
Masterpact Operation Assistant Digital Module
Presentation
The Masterpact Operation Assistant Digital Module helps to close the circuit breaker after a trip or opening.
The following features are available:
 Ready-to-close status
 Reset (if applicable)
 Spring charging (if applicable)
 Diagnostics on related reclosing information, for example, no power supply to MX, MN, or MCH
Prerequisites
The Masterpact Operation Assistant Digital Module is an optional Digital Module, which can be purchased
and installed on a Micrologic X control unit (see page 20).
The prerequsites are:
 The Masterpact MTZ mobile App must be installed on a smartphone
 The smartphone must be connected to the Micrologic X control unit through:
 Bluetooth: the control unit must be powered
 NFC: the control unit does not need to be powered

The Micrologic X date and time must be up to date
Availability of Assistance
Availability of features differs depending on the type of connection to the Digital Module:
 Through Bluetooth: all features are available
 Through NFC (connection can be made when control unit is not powered): ???
Examples of Screens
81%
12:13
ÅHelp to close circuit breaker
Step 01
12:13
ÅHelp to close circuit breaker
Step 02
Check Circuit breaker state
Closing Breaker
Please check the actual state of the breaker
click on the corresponding illustration
Locally (Mechanical):
Press the mechanical ON Push Button
CHARGED
OFF
OFF
OFF
OK
CHARGED
OK
DISCHARGED
ON
DISCHARGED
Select the new state of the Circuit Breaker
ON
DISCHARGED
CHARGED
ON
146
81%
OK
DOCA0102EN-00 05/2016
Diagnostic and Maintenance Functions
Waveform Capture on Trip Event Digital Module
Presentation
The Waveform Capture on Trip Event Digital Module allows five cycles of phase and neutral currents to be
logged after a trip on LSI or G protection, with a sampling period of 512 ms. One cycle before and four after
the trip are logged.
In addition, the waveform capture function records the digital status of the following:
 Circuit breaker trip orders
 ZSI-IN signal
 SDE
 Open position of circuit breaker
One waveform capture is available at any one time. Generating a new waveform capture replaces the
previous one.
At delivery no waveform capture is available. A waveform capture is only available after the device has
tripped due to overcurrent or ground-fault protection. Trips due to tests run in Ecoreach software are not
recorded.
Prerequisites
The Waveform Capture on Trip Event Digital Module is an optional Digital Module, which can be purchased
and installed on a Micrologic X control unit (see page 20).
The prerequsites are:
 The Masterpact MTZ mobile App must be installed on a smartphone
 The smartphone must be connected to the Micrologic X control unit through Bluetooth:
 The Micrologic X date and time must be up to date
Availability of Data
The waveform capture is displayed in the following ways:
 On the Masterpact MTZ mobile App from the Logs menu
 In Ecoreach software
 As a COMTRADE file exported through the Masterpact MTZ mobile App or Ecoreach software, for use
with Schneider Electric Wavewin-SE software
DOCA0102EN-00 05/2016
147
Diagnostic and Maintenance Functions
Examples of Screens
The following screens give examples of the type of information available on the Waveform Capture on Trip
Event Digital Module:
76%
13:51
ÅWaveform Capture
76%
13:51
ÅWaveform Capture
MTZ2 10 MAIN
DETAIL
DIGITAL
DETAIL
ct_wfc1
Trip date
14/1/2000
Station
Electropole
13:51
MTZ2 10 MAIN
ANALOGIC
DIGITAL
DETAIL
17.4
Name
76%
ÅWaveform Capture
MTZ2 10 MAIN
ANALOGIC
ANALOGIC
34.8
52.2
DIGITAL
69.6
87.0
104.4
DLO
name
File type
binary
TRIP
SDE
OPEN
ZSI_out
ZSI_in
148
DOCA0102EN-00 05/2016
Micrologic X
Operation Functions
DOCA0102EN-00 05/2016
Chapter 6
Operation Functions
Operation Functions
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0102EN-00 05/2016
Page
Control Modes
150
Closing Function
151
Opening Function
152
149
Operation Functions
Control Modes
Control Mode Settings for Micrologic X
The following table summarizes the available control modes for operating Masterpact MTZ circuit breakers
with Micrologic X control units:
Control Modes
Description
Manual
Only manual opening and closing of the circuit breaker by local
mechanical buttons is accepted.
Auto
Local
In addition to accepting manual orders, enables open/close
commands to be sent through Bluetooth, USB or IO module1
Remote
In addition to accepting manual orders, enables open/close
commands to be sent through Modbus/TCP, IFE/EIFE webpages
or IO module1
1 According to IO input mode setting
Operation According to Control Mode Configured
The following table summarizes the opening and closing operations available, depending on the control
mode configured:
Type of order
Delivery
Manual
Auto
Local
Remote
Mechanical
Pushbutton
Electrical
BPFE
Through
Communication
BPFET
Point to point (voltage release)
–
IO module
–
X1
Ecoreach software through USB
connection
–
–
Masterpact MTZ mobile App
through Bluetooth
–
–
Ethernet Modbus/TCP
–
–
Webpages
–
–
1 According to IO input mode setting
Configuring the Control Mode
The function can be set in the following ways:
 With Masterpact MTZ mobile App running the Masterpact Operation Assistant Digital Module
 On the Micrologic X display screen, at Home → Configuration → Communication → Control Mode →
Mode (Manual or Auto)
 With Ecoreach software
Predefined Events
The following events are generated when control mode settings are changed:
150
Event message
History
Severity
Manual mode enabled
Operation
Low
Local mode enabled
Operation
Low
DOCA0102EN-00 05/2016
Operation Functions
Closing Function
Presentation
Micrologic X control units receive and process electrical closing orders. An event is generated on closure.
Operating Principle
Closing orders can be sent in the following ways:
 Through a voltage release (direct electrical closing order)
 Through a local or remote order, which is managed by the Micrologic X control unit
Management of Closing Function
Micrologic X control units manage closing orders issued by the following means:
 BPFET connected to Micrologic X control unit
 IO module breaker operation
 Ecoreach via USB connection
 Masterpact MTZ mobile App via Bluetooth
 TCP via Ethernet Modbus
 IFE/EIFE webpages
Inhibiting the Closing Function
The closing functions can be inhibited by sending a command through:
 The communication network via Ethernet Modbus/TCP
 The IO module
Predefined Events
The following events are generated by the closing function:
DOCA0102EN-00 05/2016
Event message
History
Severity
Circuit breaker moved from open to close position
Operation
Low
Circuit Breaker failed to open/close
Diagnostic
Medium
Close inhibited by communication
Operation
Low
Close inhibited by wired input
Operation
Low
151
Operation Functions
Opening Function
Presentation
Micrologic X control units receive and process electrical opening orders. An event is generated on opening.
Operating Principle
Management of Opening Function
Micrologic X manages closing orders issued by the following means:
 IO module breaker operation
 Ecoreach via USB connection
 Masterpact MTZ mobile App via Bluetooth
 TCP via Ethernet Modbus
 IFE/EIFE web pages
Predefined Events
The following events are generated by the opening function:
152
Event message
History
Severity
Circuit breaker moved from close to open position
Operation
Low
Circuit Breaker failed to open/close
Diagnostic
Medium
DOCA0102EN-00 05/2016
Micrologic X
Communication Functions
DOCA0102EN-00 05/2016
Chapter 7
Communication Functions
Communication Functions
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0102EN-00 05/2016
Page
Bluetooth Low Energy Communication
154
NFC Communication
156
IEEE 802.15.4 Communication
157
USB Connection
159
Cybersecurity Recommendations
160
153
Communication Functions
Bluetooth Low Energy Communication
Description
Using Bluetooth Low Energy (BLE communications, you can access the Micrologic X control unit from a
smartphone running Masterpact MTZ mobile App (see page 15). This application offers a task-oriented
interface with the control unit. In particular, you can:
 Consult an overview of the main parameters of the circuit breaker
 Get detailed information on measurements, alarms and events, health state and current status of the
circuit breaker
 Consult and modify protection settings
 Set the date and time parameters
 Set the protection parameters
 Share data by email
You can establish a Bluetooth connection with only one Micrologic X control unit at the same time. During
the connection, the control unit is identified by the last digits of its serial number.
Note that you can consult data and send orders but you cannot download and save data on your
smartphone.
Digital modules allow you to extend the features of the Micrologic X control unit and Masterpact MTZ
mobile App.
Prerequisites for Using Bluetooth
The prerequisites for establishing a Bluetooth connection are:
The Micrologic X control unit must be powered.
 Bluetooth communication must be enabled on the control unit.
 You must have a smartphone with Masterpact MTZ mobile App installed.
 You must have access to the Micrologic X control unit, and be physically within range (usually within 20
to 30 meters or yards) for the duration of the connection.

NOTE: If using a backup power supply for the Micrologic X control unit, some functions such as operating
the circuit breaker might not be available.
Enabling and Disabling Bluetooth Communication
By default, Bluetooth communication is disabled.
You can enable or disable Bluetooth communication as follows:
On the Micrologic X display screen, go to Configuration → Communication → Bluetooth, and set
Bluetooth to ON or OFF.
 With Ecoreach software, go to Configuration → Communication → Bluetooth, and set
Bluetooth activation to OFF.

An event is generated each time Bluetooth communication is enabled or disabled.
Setting the Bluetooth Disconnection Timer
When Bluetooth communication is enabled, there is a timer on the connection with a smartphone that ends
the communication after a period of idle time. By default, this automatic disconnection timer is set to 15
minutes.
You can change the setting for the Bluetooth disconnection timer as follows:
On the Micrologic X display screen, go to Configuration → Communication → Bluetooth, set Bluetooth
to ON, and then set the BLE timer (min) value.
 With Ecoreach software, go to Configuration → Communication → Bluetooth, and set
Bluetooth time out delay (min) to the appropriate value.

You can set the value from 5 to 60 minutes (default = 15 minutes) in increments of 1.
Establishing a Bluetooth Connection
Follow the steps below to establish a Bluetooth connection from your smartphone to the Micrologic X
control unit.
Step
154
Action
Start Masterpact MTZ mobile App on your smartphone.
Select Connect to device through Bluetooth.
DOCA0102EN-00 05/2016
Communication Functions
Step
Action
On the Micrologic X control unit, press the Bluetooth activation pushbutton. The Bluetooth LED
lights up. If it does not, you must enable the Bluetooth communication feature first.
On your smartphone, Masterpact MTZ mobile App starts scanning and displays a list of
Bluetooth devices in the neighborhood.
Select the Micrologic X control unit to which you want to connect.
A 6-digit pairing code is displayed on the Micrologic X display screen.
Enter the pairing code in Masterpact MTZ mobile App within 30 seconds.
 If the pairing code is incorrect, or if more than 30 seconds have elapsed, Bluetooth
communication is deactivated (the LED turns off), and you must start the connection
procedure again at Step 3.
 If the connection is established, the Bluetooth LED starts blinking.
To end the connection, you can either:
 Press the Bluetooth pushbutton on the Micrologic X control unit.
 Disconnect from Masterpact MTZ mobile App.
While your smartphone remains within the communication range (20 to 30 meters or yards from the
Micrologic X control unit), the Bluetooth connection remains active and the information displayed is
refreshed.
NOTE: Each connection is unique, you cannot save the connection parameters for your next Bluetooth
connection.
Bluetooth LED
The Bluetooth LED on the front face of the Micrologic X control unit can be:
 ON: A Bluetooth connection procedure is in progress.
 OFF: Bluetooth is in idle mode or disabled.
 Blinking: A Bluetooth connection is established and active.
NOTE: The Bluetooth LED does not indicate whether the Bluetooth communication feature is enabled or
disabled in the Micrologic X control unit. When this feature is disabled, the LED does not light up when you
press the Bluetooth activation button.
About Bluetooth Low Energy in Micrologic X Control Unit
Troubleshooting Bluetooth Commmunication Issues
The table below lists the common problems you might meet when establishing a Bluetooth connection to
the Micrologic X control unit.
Problem description
Probable causes
The LED does not light up when you
press the BLE pushbutton on the
Micrologic X control unit
 The Bluetooth function is not
Solutions
The Bluetooth connection was
established but the signal is lost
 The smartphone has been moved
 Place the smartphone within the
out of range
 Perturbation in electromagnetic
compatibility
range for Bluetooth and establish a
new connection
 Check whether another
Micrologic X control unit within
range is also activated. If so,
deactivate it and establish a new
connection
 Enable Bluetooth communication
enabled in the Micrologic X control
in the Micrologic X control unit
 Check the power supply of the
unit
 The Micrologic X control unit is not
Micrologic X control unit
powered
A smartphone is already connected to
the Micrologic X control unit
DOCA0102EN-00 05/2016
155
Communication Functions
NFC Communication
Description
Using near field communication (NFC), you can access the Micrologic X control unit from a smartphone
running Masterpact MTZ mobile App. With NFC, you can access the control unit and download data to your
smartphone, even when the control unit is not powered.
You can establish an NFC connection with only one Micrologic X control unit at the same time.
NOTE: NFC communication is only accessible from the Android version of the Masterpact MTZ mobile
App.
NFC communication is always enabled and cannot be disabled.
Prerequisites for Using NFC
The prerequisites for establishing an NFC connection are:
 You must have a smartphone with Masterpact MTZ mobile App installed.
 You must have physical access to the Micrologic X control unit.
Establishing an NFC Connection
Follow the steps below to establish an NFC connection from your smartphone to the Micrologic X control
unit.
Step
Action
Start Masterpact MTZ mobile App on your smartphone.
Select Connect to device through NFC.
Place your smartphone against the Micrologic X display screen, in the NFC wireless
communication zone.
A beep indicates that the communication is established. The Masterpact MTZ mobile App then
starts downloading data. Another beep indicates that the data download is complete.
If the operation fails, a message is displayed. Start the procedure again.
Remove your smartphone from the Micrologic X display screen.
NOTE: You must not remove your smartphone from the Micrologic X display screen while the data
download is in progress or you will lose the NFC connection.
NFC data downloaded from the Micrologic X control unit is not automatically refreshed. To get updates,
you must establish a new NFC connection. Be aware that each new set of data downloaded overwrites the
previous data. You can use the Masterpact MTZ mobile App to consult downloaded data.
About NFC in Micrologic X Control Unit
156
DOCA0102EN-00 05/2016
Communication Functions
IEEE 802.15.4 Communication
Description
When your installation includes the Com’X data logger and Ethernet gateway, you can set up wireless
IEEE 802.15.4 communication between this gateway and the Micrologic X control unit. When the
communication is set up, data about key Micrologic X parameters is automatically transferred to theCom’X
every minute. Data transferred over IEEE 802.15.4 is crypted using AES 128 bit encryption.
You can connect up to two Micrologic X control units to one Com’X gateway.
IEEE 802.15.4 communication between the Com’X gateway and the Micrologic X control unit can replace
an Ethernet LAN for monitoring your industrial network. The Com’X gateway is accessible from anywhere
over the Ethernet LAN.
Prerequisites for Using IEEE 802.15.4
The prerequisites for establishing an IEEE 802.15.4 connection are:
 The Micrologic X control unit must be powered. The power supply modes are:
 CPS high
 VPS
 USB
 Vaux


IEEE 802.15.4 communication between the Micrologic X control unit and the Com’X gateway must be
commissioned.
You must have access to the Com’X gateway over an Ethernet LAN.
Commissioning IEEE 802.15.4 Communication
The IEEE 802.15.4 connection between the Micrologic X control unit and the Com’X gateway is set up
once at the time of commissioning and is valid thereafter. You can pair up to two Micrologic X control units
with one Com’X gateway.
Follow the steps below to commission IEEE 802.15.4 communication between the Com’X gateway and the
Micrologic X control unit.
Step
Action
From the Com’X web page, create the IEEE 802.15.4 network.
Activate the IEEE 802.15.4 signal and launch the discovery of IEEE 802.15.4 emitting devices.
Start Ecoreach on a laptop connected to the USB port of the Micrologic X control unit.
On the Configuration tab, under the Communication section, click Start scanning IEEE 802.15.4
devices to start the scan to detect the Com’X unit.
IEEE 802.15.4 is automatically activated in the Micrologic X control unit, the scan begins, and
Ecoreach displays the list of detected IEEE 802.15.4 networks within the radio range.
From the list, select the Extended PAN ID corresponding to the Com’X device and click Pair to
confirm pairing.
A popup box is displayed to report that IEEE 802.15.4 pairing was successful. The Micrologic X
control unit joins the IEEE 802.15.4 network of the Com’X, and starts sending data over the
network.
In Ecoreach, check the link quality indicator (LQI) for the IEEE 802.15.4 signal.
On the Com’X web page, check the pairing and IEEE 802.15.4 indicators. You can also consult
the data sent by the Micrologic X control unit over the IEEE 802.15.4 connection.
Decommissioning IEEE 802.15.4 Communication
The IEEE 802.15.4 connection between the Micrologic X control unit and the Com’X gateway is valid until
it is removed by unpairing the devices.
Follow the steps below to decommission IEEE 802.15.4 communication between the Com’X gateway and
the Micrologic X control unit.
Step
DOCA0102EN-00 05/2016
Action
Start Ecoreach on a laptop connected to the USB port of the Micrologic X control unit.
On the Configuration tab, under the Communication section, click Unpair in the IEEE 802.15.4
area. Click Yes in the popup window to confirm unpairing.
IEEE 802.15.4 is automatically disabled in the Micrologic X control unit.
157
Communication Functions
Step
Action
Check the network status indicator for IEEE 802.15.4, and the link quality indicator (LQI).
On the Com’X web page, check the unpairing.
Enabling and Disabling IEEE 802.15.4 Communication
By default, IEEE 802.15.4 communication is disabled in the Micrologic X control unit. when it is delivered.
After commissioning, you can enable or disable IEEE 802.15.4 communication at any time as follows:
 On the Micrologic X display screen, go to Configuration → Communication → IEEE 802.15.4, and set
IEEE 802.15.4 to ON or OFF.
 With Ecoreach software, go to Configuration → Communication → IEEE 802.15.4, and set
IEEE 802.15.4 activation to ON or OFF.
Note that:
 You cannot enable IEEE 802.15.4 on the Micrologic X control unit if IEEE 802.15.4 communication has
not been commissioned as explained previously.
 Even when you disable IEEE 802.15.4 communication, the pairing between the Micrologic X control unit
and the Com’X gateway remains valid until you decommission or unpair the devices.
 When you disable IEEE 802.15.4 communication, data transfers between the Micrologic X control unit
and the Com’X gateway stop.
An event is logged in the Com’X log book each time IEEE 802.15.4 communication is enabled or disabled.
IEEE 802.15.4 Network Status
IEEE 802.15.4 network status is displayed in Ecoreach at Configuration → Trip unit functioning → Wireless
communication access.
The following IEEE 802.15.4 states can be displayed in the IEEE 802.15.4 network status field:
Network None: indicates that the Micrologic X control unit is not commissioned, and not in the process
of being commissioned
 Network Discovering: indicates that a scan is in progress to detect IEEE 802.15.4 devices within range
 Network Discovery Complete: indicates that the scan is complete and a list of discovered devices is
displayed
 Networking: indicates that the pairing process is in progress
 Networked: indicates that IEEE 802.15.4 the Micrologic X control unit is commissioned

About IEEE 802.15.4 in Micrologic X Control Unit
The characteristics of IEEE 802.15.4 communication are:
Radio frequency 2.4 GHz, IEEE 802.15.4
 Encryption and authentication AES 128 bits
 “Listen before talk” (carrier sense multiple access with collision avoidance CSMA/CA)

Troubleshooting IEEE 802.15.4 Commmunication Issues


158
DOCA0102EN-00 05/2016
Communication Functions
USB Connection
Description
From a PC that runs Ecoreach software, you can access all of the monitoring and control functions of the
Micrologic X control unit. You can connect a laptop directly to the mini USB port of the control unit.
Connecting a PC with Ecoreach to USB Port
Follow the steps below to connect to the Micrologic X control unit using the mini USB port. This procedure
assumes that you have the appropriate cable (reference LV850067).
Step
Action
Connect your laptop PC to the mini USB port of the Micrologic X control unit using a cable with
reference LV850067.
The PC provides power to the Micrologic X control unit if necessary.
Start Ecoreach on the PC and log in.
...
About Mini USB in Micrologic X Control Unit
Troubleshooting USB Connection Issues
DOCA0102EN-00 05/2016
159
Communication Functions
Cybersecurity Recommendations
Overview
The Masterpact MTZ circuit breaker with its Micrologic X control unit is a key component of your
installation. The multiple communication features it offers bring greater efficiency and flexibility in
managing your installation, however they also make it potentially vulnerable to cyber attacks.
This section lists some of the elementary precautions that you must take to protect the communications
paths that give access to information about your installation, and control over it.
The communication paths to protect include:
 Wireless Bluetooth communication
 Wireless NFC communication
 Wireless IEEE 802.15.4 communication
 The mini USB port
 The Ethernet LAN when the EIFE or IFE interface is present
For more detailed information on cybersecurity for the Masterpact MTZ, refer to Masterpact MTZ - Cyber
Security Guide.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY




Change default passwords to help prevent unauthorized access to device settings and information.
Disable unused ports and default accounts to help minimize pathways for malicious attackers.
Place networked devices behind multiple layers of cyber defenses (such as firewalls, network
segmentation, and network intrusion detection and protection).
Use industry-accepted Informational Technology (IT) and Operational Technology (OT) cybersecurity
practices to help prevent loss or exposure of data, modification or deletion of logs and data, and
interruption of services.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For general guidelines on securing remote access to your network and for implementing a secure
operating environment, refer to How Can I... Reduce Vulnerability to Cyber Attacks?.
Cybersecurity Recommendations for Bluetooth Communication
To protect access to functions accessible through Bluetooth, it is recommended to:
 Disable Bluetooth communications, as explained in Enabling or Disabling Bluetooth Communication
(see page 154).
 Set the Bluetooth automatic disconnection timer to 5 minutes.
 Keep locked the enclosure where the Masterpact MTZ is located, so that no unauthorized person can
change the settings on the Micrologic X control unit.
 Limit the number of users allowed to have the Masterpact MTZ mobile App installed on their
smartphones.
 Make sure that the smartphones that have the Masterpact MTZ mobile App are password protected and
used for work only.
 Do not give away information about the smartphone (telephone number, MAC address) if it is not
necessary.
 Disconnect the smartphone from the Internet during a Bluetooth connection with the Micrologic X
control unit.
 Do not store confidential or sensitive information on smartphones.
Cybersecurity Recommendations for NFC Communication
To protect access to data accessible through NFC, it is recommended to:
 Keep locked the enclosure where the Masterpact MTZ is located, so that no unauthorized person can
change the settings on the Micrologic X control unit.
 Limit the number of users allowed to have the Masterpact MTZ mobile App installed on their
smartphones.
 Make sure that the smartphones that have the Masterpact MTZ mobile App are password protected and
used for work only.
160
DOCA0102EN-00 05/2016
Communication Functions
Cybersecurity Recommendations for IEEE 802.15.4 Communication
Data transfers using IEEE 802.15.4 communication are crypted, therefore, the risk of an unauthorized
person gaining access to confidential information during transmission is limited. Mostly, if IEEE 802.15.4
is the only way of accessing information about the Micrologic X remotely, you must protect the
IEEE 802.15.4 connection itself.
It is recommended to:
 Keep locked the enclosure where the Masterpact MTZ is located, so that no unauthorized person can
disable IEEE 802.15.4 communication on the Micrologic X control unit.
 Protect the Micrologic X control unit from electromagnetic interference that could perturb the
IEEE 802.15.4 communication.
 Design and implement security rules for remote access to your network, in particular to the Com’X.
Cybersecurity Recommendations for USB Connection
To protect access to functions accessible through a USB connection on the Micrologic X control unit, it is
recommended to:
 Keep locked the enclosure where the Masterpact MTZ is located, so that no unauthorized person can
access the Micrologic X control unit.
 Limit the number of users allowed to use Ecoreach or other monitoring software.
 Make sure that the PCs running the monitoring software are hardened following the guidelines provided
in Masterpact MTZ - Cyber Security Guide, and the most up-to-date hardening methods for the
operating system running on your PCs.
Cybersecurity Recommendations for an Ethernet LAN
When the Micrologic X IMU includes the EIFE module or the IFE module to connect it to the Ethernet LAN,
to protect access to the Micrologic X control unit, it is recommended to:
 Limit the number of users allowed to use Ecoreach or other monitoring software.
 Make sure that the PCs running the monitoring software are hardened following the guidelines provided
in Masterpact MTZ - Cyber Security Guide, and the most up-to-date hardening methods for the
operating system running on your PCs.
 ...
DOCA0102EN-00 05/2016
161
Communication Functions
162
DOCA0102EN-00 05/2016
Micrologic X
Event Management
DOCA0102EN-00 05/2016
Chapter 8
Event Management
Event Management
What Is in This Chapter?
This chapter contains the following topics:
Topic
DOCA0102EN-00 05/2016
Page
Event Management
164
Event Status Overview
165
Event Notifications
169
Event Status Table
170
Event History
171
Event List
173
163
Event Management
Event Management
Definition
An event is a change in state of digital data, or any incident detected by the Micrologic X control unit, IFE
or EIFE Ethernet interface, or IO modules.
Events are time stamped and logged in the event history of each module.
Events are categorized according to a level of severity:
 High
 Medium
 Low
All high and medium-level events generate an alarm and a pop-up notification screen (see page 169) on
the Micrologic X control unit display screen.
Low-level events are information-type events. They can be consulted through Ecoreach software.
Alarms and trips are events that require specific attention from the user:
 A trip is an event generated when the circuit breaker trips.
 An alarm is an event with medium or high severity.
The information in this chapter is valid for events detected by the Micrologic X control unit. Refer to the
following documents for events detected by the IFE or EIFE Ethernet interface, or by IO modules:

For information about IFE events, refer to the IFE Ethernet Interface for LV Circuit Breaker - User Guide
For information about EIFE events, refer to the EIFE Embedded Ethernet Interface for One

For information about IO events, refer to the IO Input/Output Application Module for One Circuit

Masterpact MTZ Drawout Circuit Breaker - User Guide
Breaker - User Guide
Management of Events by Micrologic X Control Unit
The following diagram gives an overview of how events are managed by the Micrologic X control unit.
Event Time Stamping
Each event is time stamped with the date and time of the Micrologic X internal clock.
164
DOCA0102EN-00 05/2016
Event Management
Event Status Overview
Event Status Definition
The status of an event is active, inactive, or held. It depends on the event type and whether it is latched or
unlatched. The status of all events can be consulted at any time (see page 170).
Event Type
Events can be the following types:
 Occurrence/completion (on/off): Events which have a defined beginning and end, representing the
beginning or end of a system state. The occurrence and completion are both time-stamped and logged
in a history. For example, control unit overheating is an occurrence/completion event.
 Instantaneous: Events with no duration. For example, the reception of an opening order, a change to
settings, or a circuit breaker trip are instantaneous events.
The event type cannot be customized.
Latched or Unlatched Events
An event can be unlatched or latched:
 Unlatched: The event status is active while the cause of the event is present. It automatically returns to
inactive when the cause of the event disappears or is resolved.
 Latched: The event status does not automatically return to inactive when the cause of the event
disappears or is resolved. It stays in the held state until it is reset by the user.
The latched/unlatched mode for certain events (see page 173) can be customized on Ecoreach software.
Disabling Events
Certain events can be disabled so that the event is not taken into consideration by the Micrologic X control
unit. In this case the event is not logged in a history and does not generate an alarm.
Events can be disabled through Ecoreach software. For more information about which events can be
disabled, refer to the event list (see page 173). Events can be enabled again after being disabled.
Unlatched Occurrence/Completion Events
The following graph shows the event status for an unlatched occurrence/completion event.
DOCA0102EN-00 05/2016
Event inactive
Event active
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event completion: event is time stamped and logged in a history
165
Event Management
Latched Occurrence/Completion Events
The following graph shows the event status for a latched occurrence/completion event.
Event inactive
Event active
Event held
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event completion: event is time stamped and logged in a history
Event reset: reset command is time stamped and logged in operation history. All held events are reset.
The following graph shows the event status for a latched event where a reset is attempted before
completion of the event.
Event inactive
Event active
Event held
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event reset: reset command is time-stamped and logged in the operation history but has no effect on Micrologic
event 1 as external event is not completed
Event completion: event is time stamped and logged in a history
Event reset: reset command is time stamped and logged in the operation history. All held events are reset.
The following graph shows the event status for a latched, recurring occurrence/completion event.
166
Event inactive
DOCA0102EN-00 05/2016
Event Management
Event active
Event held
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event completion: event is time stamped and logged in a history
Event reset: reset command is time stamped and logged in the operation history. All held events are reset.
Unlatched Instantaneous Events
The following graph shows the event status for an unlatched instantaneous event.
Event inactive
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Latched Instantaneous Events
The following graph shows the event status for a latched instantaneous event.
Event inactive
Event held
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event reset: reset command is time stamped and logged in the operation history. All held events are reset.
The following graph shows the event status for a latched, recurring instantaneous event.
DOCA0102EN-00 05/2016
Event inactive
Event held
Event occurrence: event is time stamped, logged in a history and notified, depending on severity
Event reset: reset command is time stamped and logged in the operation history. All held events are reset.
167
Event Management
Resetting Events
Events can be reset in the following ways:
 By pressing the Test/Reset button on the front of the Micrologic X control unit for 3–15 seconds.
 With Ecoreach software.
 With Masterpact MTZ mobile App.
 By sending a reset command using the communication network. This function is password protected.
Reset commands do not target specific events. All held event states managed by the Micrologic X control
unit are reset, and all trip cause LEDs are cleared.
Reset commands target a specific module. For example, pressing the Test/Reset button for 3–15 seconds
resets the events of the Micrologic X control unit but does not reset the events of the IO module.
The reset command generates an event and it is logged in the operation history.
168
DOCA0102EN-00 05/2016
Event Management
Event Notifications
Presentation
Events that are notified in the following ways cannot be configured:
 By a pop-up screen on the Micrologic X control unit (high and medium-level events).
 By SDE1 standard fault-trip indication contact and SDE2 optional fault-trip indication contact (Trip
events).
All events can be configured to be notified in the following ways:
 By optional M2C module.
 By optional IO module.
 By email from IFE or EIFE Ethernet interface.
Pop-up Screen
All high and medium-level events generate a pop-up screen on the Micrologic X display screen
(see page 57).
 A red pop-up screen indicates a trip or high-level event, needing immediate attention.
 An orange pop-up screen indicates a medium-level alarm, recommending action.
SDE Fault-Trip Indication Contacts
M2C Notifications
Ecoreach software allows the assignment of one or more events to each M2C output.
The M2C output remains on as long as one of the events assigned is active or held.
Ecoreach software also enables the status of the M2C outputs to be forced.
Forcing or unforcing a M2C output generates the following events:
 M2C output 1 unforced / forced change.
 M2C output 2 unforced / forced change.
IO Module Notifications
Ecoreach software allows the assignment of one or more events to IO module outputs available according
to the IO module predefined or user-defined applications selected. The IO module output remains on as
long as one of the events assigned is active or held. The operating mode of the IO module output must be
set as non-latching. Refer to the IO Input/Output Application Module for One Circuit Breaker - User Guide.
Email Notification
The occurrence of an event is notified by email, if configured to do so.
Email notifications have to be configured through the IFE or EIFE web pages. The notification by email is
not configured by default.
Refer to the IFE Ethernet Interface for LV Circuit Breaker - User Guide and the EIFE Embedded Ethernet
Interface for One Masterpact MTZ Drawout Circuit Breaker - User Guide
DOCA0102EN-00 05/2016
169
Event Management
Event Status Table
Introduction
The event status table contains the status of all events at the time of consultation. The status can be
inactive, active or held.
Event status for active and held events is displayed:
 On the Micrologic X display screen.
 With Ecoreach software.
 With the Masterpact MTZ mobile App.
The status of an event can be checked using the communication network.
Displaying the Event Status Table on the Micrologic X Display Screen
Display the event status table on the Micrologic X display screen at Home → Alarms/History → Alarms.
High and medium-level active and held events are displayed.
The events are displayed in no specific order, with the description of the event and the time it occurred.
If the event is completed while the screen is open, the message Completed is displayed on the screen.
Displaying the Event Status Table on Ecoreach Software
High and medium-level active and held events are displayed.
By default, events are sorted chronologically.
Events can be filtered by:
Severity:
 Alarms: High-level events
 Warnings: Medium-level events


Topic (History)
Once filtered, events can be sorted by other parameters, such as date, status, or message.
Displaying the Event Status Table on Masterpact MTZ mobile App
By default, events are sorted chronologically. They can be sorted by other parameters such as status,
history, message, date, or severity.
170
DOCA0102EN-00 05/2016
Event Management
Event History
Overview
All events are logged in one of the histories of the Micrologic X control unit:
 Trip
 Protection
 Diagnostic
 Metering
 Configuration
 Operation
 Communication
All severities of events are logged, including low-level events.
The occurrence and completion of an event are logged as two separate events.
Events logged in histories are displayed as follows:
 On the Micrologic X display screen
 With Ecoreach software
 With Masterpact MTZ mobile App
The event histories can be downloaded using the communication network.
The following information is logged in a history for each event:
 Event ID: name or code or user message
 Event type: occurrence/completion or pulse
 Time stamp: date and time of occurrence/completion
 Context data (only for certain events)
Number of Events in Each History
Each history has a predefined maximum size. When a history is full, each new event overwrites the oldest
event in the relevant history.
Event history
Number of events stored in history
Trip
50
Protection
100
Diagnostic
300
Metering
300
Configuration
100
Operation
300
Communication
100
Displaying Event History on Micrologic X Display Screen
Only high-level and medium-level events logged in histories are displayed on the Micrologic X display
screen:
 Display events logged in the trip history at Home → Alarms/History → Trip History
 Display events logged in other histories at Home → Alarms/History → Alarm History
Events are displayed in chronological order, with the event name and time stamp, starting with the most
recent.
Only occurrences of occurrence/completion events are displayed.
Displaying Event History on Ecoreach Software
All events logged in histories are displayed on the Ecoreach software.
Events in histories are displayed in chronological order, starting with the most recent event.
Events can be sorted by using filters for the following criteria:
 Date and time
 Severity
 History
Displaying Event History on Masterpact MTZ mobile App
All events logged in histories are displayed on the Masterpact MTZ mobile App.
DOCA0102EN-00 05/2016
171
Event Management
Events in histories are displayed in chronological order, starting with the most recent event.
Events can be sorted by the following criteria:
 Date and time
 Severity
 History
Erase History Content
The content of all histories can be erased with Ecoreach software.
Erasing the history generates the following event: Event history deleted
172
DOCA0102EN-00 05/2016
Event Management
Event List
Event Characteristics
The events are listed according to the history in which they are logged (see page 171).
Each event is defined by the following characteristics:
 User message: message displayed on Ecoreach software.




Type (see page 165): not customizable
 On/off: occurrence/completion event.
 Instant: instantaneous event.
Latched (see page 165): can be customized with Ecoreach software
 Yes: the event is latched and the user must reset the event status.
 No: the event is unlatched.
Activity (see page 165):
 Enabled: the event is always enabled.
 Enabled1: the event is enabled by default and can be disabled with Ecoreach software.
 Disabled1: the event is disabled by default and can be enabled with Ecoreach software.
Severity:
 High-level trips and alarms.
 Medium-level alarms.
 Low-level events.
Trip Events
User message
History
Type
Latched
Activity
Severity
Ir trip (see page 65)
Trip
Instant
Yes
Enabled
High
Isd trip (see page 68)
Trip
Instant
Yes
Enabled
High
Ii trip (see page 70)
Trip
Instant
Yes
Enabled
High
Ig trip (see page 72)
Trip
Instant
Yes
Enabled
High
IΔn trip (see page 74)
Trip
Instant
Yes
Enabled
High
Ultimate self-protection trip (Sellim)
Trip
Instant
Yes
Enabled
High
(see page 62)
Internal failure trip
Trip
Instant
Yes
Enabled
High
Ultimate self-protection trip (DIN/DINF)
Trip
Instant
Yes
Enabled
High
IΔn / Ig test trip (see page 73)
Trip
Instant
Yes
Enabled
High
User message
History
Type
Latched
Activity
Severity
Ultimate self-protection (DIN/DINF) operate
Protection
On/off
No
Enabled
Medium
Ultimate self-protection (Sellim) operate
Protection
On/off
No
Enabled
Medium
Thermal memory reset order (see page 65)
Protection
Instant
No
Enabled
Low
Ir prealarm (I>90%Ir) (see page 67)
Protection
On/off
No
Enabled
Low
Ir start (I>105%Ir) (see page 67)
Protection
On/off
No
Enabled
Medium
Ir operate (see page 67)
Protection
On/off
No
Enabled
Medium
Isd start (see page 69)
Protection
On/off
No
Enabled
Low
Isd operate (see page 69)
Protection
On/off
No
Enabled
Medium
Ii operate (see page 70)
Protection
On/off
No
Enabled
Medium
Ig start (see page 72)
Protection
On/off
No
Enabled
Low
Ig operate (see page 72)
Protection
On/off
No
Enabled
Medium
IΔn start (see page 74)
Protection
On/off
No
Enabled
Low
IΔn operate (see page 74)
Protection
On/off
No
Enabled
Medium
(see page 62)
Protection Events
(see page 62)
(see page 62)
1 Customizable with Ecoreach software
DOCA0102EN-00 05/2016
173
Event Management
User message
History
Type
Latched
Activity
Severity
B curve active (see page 78)
Protection
On/off
No
Enabled
Low
Protection settings on local screen is
unlocked (see page 63)
Protection
On/off
No1
Enabled
Low
Remote lock for protection settings is
unlocked (see page 63)
Protection
On/off
No1
Enabled
Low
Protection setting change (display screen)
Protection
Instant
No1
Enabled
Low
Protection setting changed (Bluetooth, USB Protection
or IFE) (see page 62)
Instant
No1
Enabled
Medium
Activity
(see page 62)
1 Customizable with Ecoreach software
Diagnostic Events
User message
Type
Latched
IO 1 module connection lost (see page 142) Diagnostic
Instant
Yes
Enabled
Medium
IO 2 module connection lost (see page 142) Diagnostic
Instant
Yes
Enabled1
Medium
IFE connection lost (see page 142)
Diagnostic
Instant
Yes
Enabled1
Medium
Product in test mode
Diagnostic
On/off
No
Enabled
Low
Injection test
Diagnostic
On/off
No
Enabled
Low
Test aborted by user
Diagnostic
Instant
No
Enabled
Low
Product self test major malfunction
Diagnostic
On/off
No
Enabled
High
Internal current sensors (CT) disconnected
Diagnostic
On/off
No
Enabled
High
ENCT disconnected (see page 138)
Diagnostic
On/off
No
Enabled
High
Earth leakage (Vigi) sensor disconnected
Diagnostic
On/off
No
Enabled
High
Current protection reset to default settings
Diagnostic
On/off
No
Enabled
High
Reading accessing protection settings error
Diagnostic
On/off
No
Enabled
Medium
Metering and advanced protection
malfunction (see page 141)
Diagnostic
On/off
No
Enabled
Medium
NFC malfunction (see page 141)
Diagnostic
On/off
No
Enabled1
Medium
Display screen or wireless malfunction
Diagnostic
On/off
No
Enabled
Medium
IEEE 802.15.4 malfunction (see page 141)
Diagnostic
On/off
No
Enabled1
Medium
Bluetooth malfunction (see page 141)
Diagnostic
On/off
No
Enabled1
Medium
Replace battery (see page 141)
Diagnostic
On/off
No
Enabled1
Medium
Minor- Corrected ASIC internal error
warning (see page 141)
Diagnostic
On/off
No
Enabled
Medium
FW internal error (see page 141)
Diagnostic
On/off
No
Enabled
Low
(see page 138)
(see page 138)
(see page 138)
(see page 141)
(see page 141)
(see page 141)
History
Severity
Sensor plug reading error (see page 141)
Diagnostic
On/off
No
Enabled
High
Minor-Open/Close coils failure
Diagnostic
On/off
No
Enabled
Medium
Discrepancy ASIC configuration
Diagnostic
On/off
No
Enabled
High
Critical hardware module discrepancy
Diagnostic
On/off
No
Enabled
Medium
Critical firmware module discrepancy
Diagnostic
On/off
No
Enabled
Medium
Non-critical hardware module discrepancy
Diagnostic
On/off
No
Enabled
Medium
(see page 141)
(see page 141)
(see page 141)
(see page 141)
(see page 141)
1 Customizable with Ecoreach software
174
DOCA0102EN-00 05/2016
Event Management
User message
History
Type
Latched
Activity
Severity
Non-critical firmware module discrepancy
Diagnostic
On/off
No
Enabled
Medium
ULP module address conflict
Diagnostic
On/off
No
Enabled
Medium
Firmware discrepancy within product
Diagnostic
On/off
No
Enabled
Medium
IΔn/Ig test trip failed (IΔn (see page 74) Ig
(see page 73))
Diagnostic
Instant
No
Enabled
High
IΔn/Ig test button pressed (IΔn
(see page 74) Ig (see page 73))
Diagnostic
Instant
No
Enabled
Low
ZSI Test (see page 81)
Diagnostic
Instant
No
Enabled
Low
Contact 60% worn out (see page 140)
Diagnostic
On/off
No
Enabled1
Medium
(see page 141)
(see page 141)
(see page 141)
Contact 95% worn out (see page 140)
Diagnostic
On/off
No
Enabled
Medium
Contact 100% worn out (see page 140)
Diagnostic
On/off
No
Enabled
High
CB operations has passed 80% of service
life (see page 143)
Diagnostic
On/off
No
Enabled1
High
CB operations has passed the service life
Diagnostic
Instant
No
Enabled
Low
MX1 opening release malfunction
Diagnostic
On/off
No
Enabled
Medium
MX1 opening release is no longer detected
Diagnostic
On/off
No
Enabled
Medium
MCH has reached 80% of the max nb of
operations (see page 139)
Diagnostic
On/off
No
Enabled
Medium
MCH has reached the max nb of operations
Diagnostic
On/off
No
Enabled
Medium
XF closing release malfunction
Diagnostic
On/off
No
Enabled
Medium
XF closing release is no longer detected
Diagnostic
On/off
No1
Enabled1
Medium
MX2 / MN opening release malfunction
Diagnostic
On/off
No
Enabled
High
MX2 / MN opening release is no longer
detected (see page 139)
Diagnostic
On/off
No
Enabled
Medium
Circuit Breaker failed to Open/Close
Diagnostic
Instant
Yes
Enabled
Medium
Event history deleted (see page 172)
Diagnostic
Instant
No
Enabled
Low
User message
History
Type
Reset Min/Max currents (see page 116)
Metering
Reset Min/Max voltages (see page 116)
(see page 143)
(see page 139)
(see page 139)
(see page 139)
(see page 139)
(see page 139)
(see page 139)
(see page 139)
1 Customizable with Ecoreach software
Metering Events
Activity
Severity
Instant
No
Enabled
Low
Metering
Instant
No1
Enabled
Low
Reset Min/Max power (see page 116)
Metering
Instant
No
Enabled
Low
Reset Min/Max frequency (see page 116)
Metering
Instant
No1
Enabled
Low
Reset Min/Max harmonics (see page 116)
Metering
Instant
No
Enabled
Low
Reset Min/Max power factor (see page 116) Metering
Instant
No
Enabled
Low
Reset energy counters (see page 122)
Instant
No1
Enabled
Low
Metering
Latched
1 Customizable with Ecoreach software
DOCA0102EN-00 05/2016
175
Event Management
Operation Events
User message
History
Type
Latched
Activity
Severity
CB moved from close to open position
Operation
Instant
No1
Enabled1
Low
CB moved from open to close position
Operation
Instant
No1
Enabled1
Low
Closing release activation (see page 151)
Operation
Instant
No
Enabled
Low
Opening release activation (see page 152)
Operation
Instant
No
Enabled
Low
Manual mode enabled (see page 150)
Operation
On/off
No
Enabled
Low
Local mode enabled (see page 150)
Operation
On/off
No
Enabled
Low
Close inhibited by communication
Operation
On/off
No
Enabled
Low
Close inhibited by wired input (see page 151) Operation
On/off
No
Enabled
Low
M2C output 1 forced (see page 169)
Operation
On/off
No
Enabled
Low
M2C output 2 forced (see page 169)
Operation
On/off
No
Enabled
Low
Alarm reset (trip and non-trip) (see page 168) Operation
Instant
No
Enabled
Low
(see page 152)
(see page 151)
(see page 151)
1 Customizable with Ecoreach software
Configuration Events
User message
History
Type
Latched
Activity
Severity
Conflict with IO module configuration
Configuration
On/off
No
Enabled
Medium
(see page 142)
Product in upgrade mode
Configuration
On/off
No
Enabled
Low
Product upgrade failed
Configuration
Instant
No
Enabled
Medium
Clock setup (see page 22)
Configuration
Instant
No
Enabled
Low
License installed (see page 21)
Configuration
Instant
No
Enabled
Low
License uninstalled (see page 21)
Configuration
Instant
No
Enabled
Low
User message
History
Type
Latched
Activity
Severity
USB connection (see page 159)
Communication
On/off
No
Enabled
BLUETOOTH communication enabled
Communication
On/off
No
Enabled
Low
IEEE 802.15.4 communication enabled
Communication
On/off
No
Enabled1
Low
Communication Events
(see page 154)
(see page 157)
Low
1 Customizable with Ecoreach software
176
DOCA0102EN-00 05/2016
Micrologic X
DOCA0102EN-00 05/2016
Appendices
DOCA0102EN-00 05/2016
177
178
DOCA0102EN-00 05/2016
Micrologic X
Abbreviated title of Chapter
DOCA0102EN-00 05/2016
Appendix A
Title of Chapter
Title of Chapter
DOCA0102EN-00 05/2016
179

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : No
Encryption                      : Standard V2.3 (128-bit)
User Access                     : Print, Extract
Page Mode                       : UseOutlines
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Format                          : application/pdf
Creator                         : Schneider Electric
Title                           : Micrologic X - Control Unit - User Guide - 05/2016
Create Date                     : 2016:05:02 11:47:47Z
Creator Tool                    : Miramo 9.2 (www.miramo.com)
Modify Date                     : 2016:10:18 23:05:37+08:00
Metadata Date                   : 2016:10:18 23:05:37+08:00
Producer                        : Acrobat Elements 11.0 (Windows)
Document ID                     : uuid:84950dc5-76f2-4676-afd6-23cd39293545
Instance ID                     : uuid:dc8f0a15-6694-47e5-8320-71929eed47c0
Has XFA                         : No
Page Count                      : 79
Author                          : Schneider Electric
EXIF Metadata provided by EXIF.tools
FCC ID Filing: 2AH7L-NX2TO7

Navigation menu