Siemens RF350R02 RFID Reader 13.56 MHz User Manual SIMATIC RF300

Siemens AG RFID Reader 13.56 MHz SIMATIC RF300

Users manual 4

ISO transponder
8.13 MDS D339
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 303
8.13
MDS D339
8.13.1
Characteristics
MDS D339
Characteristics
Area of application Applications in production automation with high
temperature demands (up to +220 °C)
Typical application areas:
Paintshops and their preparatory treatments
Primer coat, electrolytic dip area, cataphoresis
with the associated drying furnaces
Top coat area with drying furnaces
Washing areas at temperatures > 85 °C
Other applications with higher temperatures
Memory size 992 bytes of EEPROM user memory
Write/read range See section Field data of ISO transponders (MDS D)
(Page 52).
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP68/IPx9K
8.13.2
Ordering data
Table 8- 31 Ordering data for MDS D339
Article number
MDS D339
6GT2600-3AA10
Table 8- 32 Ordering data for MDS D339 accessories
Article number
Spacer
6GT2690-0AA00
Quick change holder
(Ø x H): 22 x 60 mm
6GT2690-0AH00
Quick change holder
(Ø x H): 22 x 47 mm
6GT2690-0AH10
ISO transponder
8.13 MDS D339
SIMATIC RF300
304 System Manual, 07/2016, C79000-G8976-C345-0x
8.13.3
Mounting on metal
Direct mounting of the MDS D139/D339 on metal is not allowed. A distance of ≥ 30 mm is
recommended. This can be achieved using spacers (see "Ordering data (Page 303)").
Mounting on metal
h
≥ 30 mm
Figure 8-28 Mounting the MDS D139/D339 on metal with spacer
Flush-mounting
It is possible to mount the MDS D139/D339 in metal. With large antennas, for example ANT
D5, this leads to a reduction of ranges.
h
≥ 30 mm
a
≥ 100 mm
Figure 8-29 Flush-mounting of the MDS D139/D339 in metal with spacer
ISO transponder
8.13 MDS D339
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 305
Note
Going below the distances
If the distances (a and h) are not observed, a reduction of the field data results. It is possi
ble
to mount the MDS with metal screws (M5). This has no tangible impact on the range. It is
recommended that a test is performed in critical applications.
8.13.4
Cleaning the mobile data memory
Note
Do not clean the transponder with mechanical tools, sand
-blasting or pressure hose. These
cleaning methods result in damage to the transponder.
Clean the transponder only with the cleaning agents listed in the section "Chemical
resistance of the MDS".
8.13.5
Technical specifications
Table 8- 33 Technical specifications of MDS D339
6GT2600-3AA10
Product type designation
SIMATIC MDS D339
Memory
Memory configuration
UID 8 bytes
User memory 992 bytes EEPROM
OPT memory 16 bytes (EEPROM)
Read cycles (at < 40 ℃) > 1014
Write cycles (at < 40 ℃) > 106
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.13 MDS D339
SIMATIC RF300
306 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-3AA10
Mechanical specifications
Housing
Material PPS
Color Black
Recommended distance to metal
≥ 30 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +220
from +125 ℃: 20% reduction in the limit dis-
tance
from +140 ℃: No processing possible
at +200 ℃: Tested up to 5000 hours or
6000 cycles
at +220 ℃: Tested up to 2000 hours or
2000 cycles
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to EN 60721-3-7 class 7M3
50 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
85 x 15 mm
Weight
50 g
Type of mounting 1 x M5 screw 2)
1.5 Nm
1
The values for shock and vibration are maximum values and must not be applied continuously.
2)
For mounting with the spacer (6GT2690-0AA00), use a stainless steel M5 screw to avoid damag-
ing the MDS in high temperatures (expansion coefficient).
ISO transponder
8.13 MDS D339
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 307
8.13.6
Use of the MDS D339 in hazardous areas
The MDS D339 mobile data memory is classed as a piece of simple, electrical equipment
and can be operated in Protection Zone 2, Device Group II, Category 3G.
The following requirements of the 94/9/EC directive are met:
EN 60079-0:2006
EN 60079-15:2005
EN 61241-0:2006
EN 61241-1:2004
Identification
II 3 G Ex nA II T6
Ii 3 D Ex tD A22 IP68 T 210°C
KEMA 09 ATEX 0133 X
WARNING
Gefahr durch elektrostatische Entladungen
Potential electrostatic charging hazard
Danger potentiel de charges électrostatiques
ISO transponder
8.13 MDS D339
SIMATIC RF300
308 System Manual, 07/2016, C79000-G8976-C345-0x
Note
Installations- und Betriebsbedingungen für den Ex-Schutzbereich:
a) Der Einsatz des Gerätes in der Nähe von stark ladungserzeugenden Prozessen ist
untersagt.
b) Das Gerät ist mechanisch geschützt zu montieren.
c) Die Montage muss auf einem geerdeten, leitenden Untergrund erfolgen.
d) Die Reinigung darf nur mit f
euchtem Tuch erfolgen.
Installation and operating conditions for hazardous areas:
a) Use of the equipment in the vicinity of processes generating high charges is not allowed.
b) The equipment must be mechanically protected when installed.
c) Installation
must be performed on a grounded and conductive mounting surface.
d) Cleaning only with a wet cloth
Conditions d'installation et de mise en oeuvre pour la zone de protection Ex :
a) L'utilisation de l'appareil près de processus générant de fortes charges e
st interdite.
b) L'appareil doit être monté de manière à être protégé mécaniquement.
c) Le montage doit être effectué sur un socle conducteur mis à la terre.
d) Nettoyage uniquement avec un chiffon humide
ISO transponder
8.13 MDS D339
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 309
8.13.7
Dimensional drawing
MDS D339
Figure 8-30 Dimension drawing of the MDS D339
Dimensions in mm
ISO transponder
8.14 MDS D400
SIMATIC RF300
310 System Manual, 07/2016, C79000-G8976-C345-0x
8.14
MDS D400
8.14.1
Features
MDS D400
Characteristics
Area of application Simple identification such as electronic barcode re-
placement/supplements, from warehouse and distribu-
tion logistics right through to product identification.
Memory size 2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)"
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP67
8.14.2
Ordering data
Table 8- 34 Ordering data of MDS D400
Article number
MDS D400
6GT2600-4AD00
Table 8- 35 Ordering data of MDS D400 accessories
Article number
Spacer
(in conjunction with fixing pocket 6GT2190-0AB00)
6GT2190-0AA00
Fixing pocket
(in conjunction with spacer 6GT2190-0AA00)
6GT2190-0AB00
Fixing pocket
(not suitable for fixing directly onto metal)
6GT2390-0AA00
ISO transponder
8.14 MDS D400
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 311
8.14.3
Mounting on metal
Mounting on metal
It is possible to mount the MDS D400 on metal.
h
≥ 20 mm
Transponder
Metal
Non-metal
Figure 8-31 Mounting of the MDS D400 on metal with spacer
ISO transponder
8.14 MDS D400
SIMATIC RF300
312 System Manual, 07/2016, C79000-G8976-C345-0x
Flush-mounted in metal
a
≥ 20 mm
h
≥ 20 mm
Transponder
Metal
Non-metal
Figure 8-32 Flush-mounting of MDS D400 in metal with spacer
Note
If the minimum guide values (h) are not observed, this will result in a reduction of the field
data.
8.14.4
Technical specifications
Table 8- 36 Technical specifications for MDS D400
6GT2600-1AD00-0AX0
Product type designation
SIMATIC MDS D400
Memory
Memory configuration
UID 8 bytes
User memory 256 bytes FRAM
OPT memory 16 bytes FRAM
ISO transponder
8.14 MDS D400
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 313
6GT2600-1AD00-0AX0
Read cycles (at < 25 ℃)
> 10
12
Write cycles (at < 25 ℃)
> 10
12
Data retention time (at < 25 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material PVC
Color White
Recommended distance to metal
≥ 20 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -20 to +60
During transportation and storage -20 to +60 ℃
Degree of protection to EN 60529
IP67
Vibration-resistant to EN 60721-3-7, class 7M3
ISO 10373 / ISO 7810
1)
Torsion and bending load
ISO 10373/ISO 7816-1
Design, dimensions and weight
Dimensions (L x W x H)
85 x 54 x 0.8 mm
Weight
5 g
Type of mounting Fixing lug
Glued
1) The values for vibration are maximum values and must not be applied continuously.
ISO transponder
8.14 MDS D400
SIMATIC RF300
314 System Manual, 07/2016, C79000-G8976-C345-0x
8.14.5
Dimension drawing
Figure 8-33 Dimensional drawing MDS D400 (dimensions in mm)
ISO transponder
8.15 MDS D421
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 315
8.15
MDS D421
8.15.1
Characteristics
MDS D421
Characteristics
Area of application The MDS D421 is designed for tool coding in accordance
with DIN 69873.
It can be used wherever small data carriers and exact posi-
tioning are required, e.g. tool identification, workpiece hold-
ers.
The rugged housing of the MDS D421 means that it can
also be used in a harsh industrial environment without prob-
lems.
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)"
Mounting on metal
Yes, flush-mounted in metal
ISO standard
ISO 15693
Degree of protection
IP67/IPx9K
8.15.2
Ordering data
Table 8- 37 Ordering data of MDS D421
Article number
MDS D421
6GT2600-4AE00
ISO transponder
8.15 MDS D421
SIMATIC RF300
316 System Manual, 07/2016, C79000-G8976-C345-0x
8.15.3
Mounting on metal
Mounting on metal
Figure 8-34 Mounting of MDS D421/D521/E623 on metal
Flush-mounting
Figure 8-35 Mounting of MDS D421/D521/E623 in metal
ISO transponder
8.15 MDS D421
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 317
Flush-mounting of the MDS in metal with tools
Figure 8-36 Flush-mounting of MDS D421/D521/E623 in metal with tools
b
1
0.5 x 45°
b
2
0.3 x 45° or R0.3
d1
10 (-0.04... -0.13)
d2
10 (+0.09... 0)
t
1
4.5 (-0 ... -0.1)
t
2
4.6 (+0.2 ... 0)
All dimensions in mm
Note
Installation instruction
The MDS sh
ould not protrude out of the locating hole; it must be flush with the outside
contour.
The mounting instructions of the MDS and the conditions associated with the application
(e.g. peripheral speed, temperature, and use of coolant) must be observed during
the
installation.
Mounting information for adhesion
Drill installation hole
The adhesive surfaces must be dry, free from dust, oil, stripping agents and other
impurities
Apply adhesive according to the manufacturer's processing instructions
Press in transponder using your fingers; with antenna side to the outside (see figure
above)
Remove residues of adhesive
Allow to cure according to the manufacturer's instructions
Flush-mounting of the transponder in metal with tools
ISO transponder
8.15 MDS D421
SIMATIC RF300
318 System Manual, 07/2016, C79000-G8976-C345-0x
Installation examples
Figure 8-37 Installation example of MDS D421/D521/E623 in a steep cone
Figure 8-38 Installation example of MDS D421/D521/E623 in a stud bolt
8.15.4
Technical specifications
Table 8- 38 Technical specifications for the MDS D421
6GT2600-4AE00
Product type designation
SIMATIC MDS D421
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.15 MDS D421
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 319
6GT2600-4AE00
Mechanical specifications
Housing
Material Epoxy resin
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP67
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to EN 60721-3-7 class 7M3
100 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
10 x 4.5 mm
Weight
Approx. 1 g
Type of mounting
Glued
2)
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2) The manufacturer's processing instructions must be observed.
ISO transponder
8.15 MDS D421
SIMATIC RF300
320 System Manual, 07/2016, C79000-G8976-C345-0x
8.15.5
Dimension drawing
Figure 8-39 Dimension drawing of MDS D421
All dimensions in mm
ISO transponder
8.16 MDS D422
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 321
8.16
MDS D422
8.16.1
Characteristics
MDS D422
Characteristics
Area of application Identification of metallic workpiece holders, workpieces or
containers
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52).
Mounting on metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68
8.16.2
Ordering data
Table 8- 39 Ordering data of MDS D422
Article number
MDS D422
A screw-in aid is included in the scope of supply per packaging
unit
6GT2600-4AF00
ISO transponder
8.16 MDS D422
SIMATIC RF300
322 System Manual, 07/2016, C79000-G8976-C345-0x
8.16.3
Mounting in metal
Flush-mounting
Figure 8-40 Mounting of MDS D422 in metal
Mounting information for screws
You can screw the transponder into a pre-drilled threaded hole using the screw-in aid.
Mounting information for adhesion
Drill installation hole
The adhesive surfaces must be dry, free from dust, oil, stripping agents and other
impurities
Apply adhesive according to the manufacturer's processing instructions
Press in MDS D422 using your fingers; with antenna to the outside
Remove residues of adhesive
Allow to cure according to the manufacturer's instructions
Flush-mounting of MDS D422 in metal with tools
ISO transponder
8.16 MDS D422
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 323
8.16.4
Technical specifications
Table 8- 40 Technical specifications for the MDS D422
6GT2600-4AF00
Product type designation
SIMATIC MDS D422
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
285 years
Mechanical specifications
Housing
Material Plastic PA 6.6 GF; brass nickel plated
Color Black/silver
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
Shock-resistant to EN 60721-3-7 class 7M3
50 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load Not permitted
ISO transponder
8.16 MDS D422
SIMATIC RF300
324 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-4AF00
Design, dimensions and weight
Dimensions (Ø x H)
20 x 6 mm
Weight
13 g
Type of mounting Glued
1 x transponder thread M20
≤ 1 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
8.16.5
Dimension drawing
Dimensions in mm
Figure 8-41 Dimensional drawing of MDS D422
ISO transponder
8.17 MDS D423
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 325
8.17
MDS D423
8.17.1
Characteristics
MDS D423
Characteristics
Area of application Identification of metallic workpiece holders, work-
pieces or containers, production automation
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS
D) (Page 52)"
Mounting on metal
Yes, flush-mounted in metal
ISO standard
ISO 15693
Degree of protection IP68/IPx9K
8.17.2
Ordering data
Table 8- 41 Ordering data of MDS D423
Article number
MDS D423 6GT2600-4AA00
Table 8- 42 Ordering data of MDS D423 accessories
Article number
Fixing hood RF330T / MDS D423
6GT2690-0EA00
ISO transponder
8.17 MDS D423
SIMATIC RF300
326 System Manual, 07/2016, C79000-G8976-C345-0x
8.17.3
Mounting on metal
Mounting on metal
Direct mounting of the MDS D423 on metal is possible.
Figure 8-42 Mounting the MDS D423 on metal
Flush-mounted in metal
It is possible to mount the MDS D423 in metal.
a
≥ 10 mm
Figure 8-43 Flush-mounting of the MDS D423 in metal with 10 mm clearance
ISO transponder
8.17 MDS D423
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 327
Figure 8-44 Flush-mounting of the MDS D423 in metal without clearance
Note
Reduction of the write/read range
Note that when the device is flush
-mounted in metal without a surrounding clearance ≥ 10
mm, the write/read range is significantly reduced.
8.17.4
Technical specifications
Table 8- 43 Technical specifications of MDS D423
6GT2600-4AA00
Product type designation
SIMATIC MDS D423
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃) > 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.17 MDS D423
SIMATIC RF300
328 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-4AA00
Mechanical specifications
Housing
Material Plastic PPS
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to EN 60721-3-7 class 7M3
50 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Pressure resistance Low pressure resistant
vacuum dryer: up to 20 mbar
High pressure resistant
(see degree of protection IPx9K)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
30 x 8 mm
Weight
15 g
Type of mounting 1 x M4 screw 2)
≤ 1 Nm
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2 ) To prevent it loosening during operation, secure the screw with screw locking varnish.
ISO transponder
8.17 MDS D423
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 329
8.17.5
Dimensional drawing
Dimensions in mm
Figure 8-45 Dimension drawing for MDS D423
ISO transponder
8.18 MDS D424
SIMATIC RF300
330 System Manual, 07/2016, C79000-G8976-C345-0x
8.18
MDS D424
8.18.1
Characteristics
MDS D424
Characteristics
Area of application Production and distribution logistics as well as in
assembly and production lines,
can also be used in a harsh industrial environment
without problem
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS
D) (Page 52)."
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP67; IPx9K
8.18.2
Ordering data
Table 8- 44 Ordering data of MDS D424
Article number
MDS D424
6GT2600-4AC00
Table 8- 45 Ordering data of MDS D424 accessories
Article number
Spacer
6GT2690-0AK00
ISO transponder
8.18 MDS D424
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 331
8.18.3
Mounting on metal
Mounting on metal
h
≥ 15 mm
Figure 8-46 Mounting the MDS D124/D324/D424/D524/E624 and RF320T on metal with spacer
Flush-mounting
h
≥ 15 mm
a
≥ 25 mm
Figure 8-47 Flush-mounting of the MDS D124/D324/D424/D524/E624 and RF320T in metal with
spacer
ISO transponder
8.18 MDS D424
SIMATIC RF300
332 System Manual, 07/2016, C79000-G8976-C345-0x
Note
Going below the distances
If the distances (a and h) are not observed, a reduction of the field data results. It is possible
to mount the MDS with metal screws (M3 countersunk head screws). This ha
s no tangible
impact on the range.
8.18.4
Technical specifications
Table 8- 46 Technical specifications for the MDS D424
6GT2600-4AC00
Product type designation
SIMATIC MDS D424
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Epoxy resin
Color Black
Recommended distance to metal
≥ 15 mm
Power supply
Inductive, without battery
ISO transponder
8.18 MDS D424
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 333
6GT2600-4AC00
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP67
IPx9K
Shock-resistant to EN 60721-3-7 class 7M3
100 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
27 x 4 mm
Weight
5 g
Type of mounting Glued
1 x M3 screw 2)
≤ 1 Nm
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2 ) To prevent it loosening during operation, secure the screw with screw locking varnish.
8.18.5
Dimension drawing
Figure 8-48 Dimension drawing of MDS D424
All dimensions in mm
ISO transponder
8.19 MDS D425
SIMATIC RF300
334 System Manual, 07/2016, C79000-G8976-C345-0x
8.19
MDS D425
8.19.1
Characteristics
MDS D425
Characteristics
Area of application Compact and rugged ISO transponder; suitable for screw
mounting
Use in assembly and production lines in the powertrain
sector; ideal for mounting on motors, gearboxes, and work-
piece holders
Rugged packaging of the MDS D425; can therefore also be
used under extreme environmental conditions without prob-
lem
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)".
Mounting on metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68/IPx9K
8.19.2
Ordering data
Table 8- 47 Ordering data of MDS D425
Article number
MDS D425
6GT2600-4AG00
ISO transponder
8.19 MDS D425
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 335
8.19.3
Application example
Figure 8-49 Application example
8.19.4
Technical specifications
Table 8- 48 Technical specifications for the MDS D425
6GT2600-4AG00
Product type designation SIMATIC MDS D425
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃) > 1012
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.19 MDS D425
SIMATIC RF300
336 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-4AG00
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +125 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
24 x 10 mm (without set screw)
Weight
35 g
Type of mounting 1x transponder set screw M6
SW 22; ≤ 6 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.19 MDS D425
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 337
8.19.5
Dimension drawing
Dimensions in mm
Figure 8-50 Dimension drawing of MDS D425
ISO transponder
8.20 MDS D426
SIMATIC RF300
338 System Manual, 07/2016, C79000-G8976-C345-0x
8.20
MDS D426
8.20.1
Characteristics
MDS D426
Characteristics
Area of application Compact and rugged ISO transponder; suitable for identification of
transport units in production-related logistics; can also be deployed in
harsh conditions
Memory size 2000 bytes of FRAM user memory
Write/read range
See section Field data of ISO transponders (MDS D) (Page 52)
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP68
8.20.2
Ordering data
Table 8- 49 Ordering data of MDS D426
Article number
MDS D426
6GT2600-4AH00
Table 8- 50 Ordering data of MDS D426 accessories
Article number
Spacer
6GT2690-0AL00
ISO transponder
8.20 MDS D426
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 339
8.20.3
Mounting on metal
Mounting on metal
h
≥ 25 mm
Figure 8-51 Mounting the MDS D126 / D426 / D526 on metal with spacer
Flush-mounted in metal
h
≥ 25 mm
a
≥ 50 mm
Figure 8-52 Flush installation of the MDS D126 / D426 / D526 in metal with spacer
ISO transponder
8.20 MDS D426
SIMATIC RF300
340 System Manual, 07/2016, C79000-G8976-C345-0x
8.20.4
Technical specifications
Table 8- 51 Technical specifications for the MDS D426
6GT2600-4AH00
Product type designation
SIMATIC MDS D426
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 25 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load Not permitted
ISO transponder
8.20 MDS D426
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 341
6GT2600-4AH00
Design, dimensions and weight
Dimensions (Ø x H)
50 x 3.6 mm
Weight
13 g
Type of mounting 1 x M4 screw 2)
≤ 1 Nm
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2 ) To prevent it loosening during operation, secure the screw with screw locking varnish.
8.20.5
Dimension drawing
Dimensions in mm
Figure 8-53 Dimension drawing of MDS D426
ISO transponder
8.21 MDS D428
SIMATIC RF300
342 System Manual, 07/2016, C79000-G8976-C345-0x
8.21
MDS D428
8.21.1
Characteristics
MDS D428
Characteristics
Area of application Compact and rugged ISO transponder; suitable for screw
mounting.
Use in assembly and production lines in the powertrain
sector.
The rugged housing of the MDS D428 means that it can
also be used in extreme environmental conditions without
problems.
Memory size
2000 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)"
Mounting on metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68/IPx9K
8.21.2
Ordering data
Table 8- 52 Ordering data of MDS D428
Article number
MDS D428
6GT2600-4AK00-0AX0
ISO transponder
8.21 MDS D428
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 343
8.21.3
Application example
Figure 8-54 Application example
8.21.4
Technical specifications
Table 8- 53 Technical specifications for the MDS D428
6GT2600-4AK00
Product type designation SIMATIC MDS D428
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃) > 1012
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.21 MDS D428
SIMATIC RF300
344 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-4AK00
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +125 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
24 x 20 mm (without set screw)
Weight
35 g
Type of mounting 1x transponder set screw M8
SW 22; ≤ 8 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.21 MDS D428
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 345
8.21.5
Dimension drawing
Dimensions in mm
Figure 8-55 Dimension drawing of MDS D428
ISO transponder
8.22 MDS D460
SIMATIC RF300
346 System Manual, 07/2016, C79000-G8976-C345-0x
8.22
MDS D460
8.22.1
Characteristics
MDS D460
Characteristics
Area of application Identification in small assembly lines; can also be used in a harsh in-
dustrial environment
Memory size
2000 bytes of FRAM user memory
Write/read range
See section "Field data of ISO transponders (MDS D) (Page 52).
Mounting on metal Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP67/IPx9K
8.22.2
Ordering data
Table 8- 54 Ordering data of MDS D460
Article number
MDS D460
6GT2600-4AB00
Table 8- 55 Ordering data of MDS D460 accessories
Article number
Spacer
6GT2690-0AG00
ISO transponder
8.22 MDS D460
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 347
8.22.3
Mounting on metal
Mounting option on metal with spacer
Transponder
Metal
Spacer
h
≥ 10 mm
Figure 8-56 Mounting the MDS D460 on metal with spacer
Note
If the minimum guide values (h) are not obser
ved, a reduction of the field data results.
In critical applications, it is recommended that a test is performed.
Flush-mounting
Flush-mounting of the MDS D460 in metal is not permitted!
8.22.4
Technical specifications
Table 8- 56 Technical specifications for MDS D460
6GT2600-4AB00
Product type designation
SIMATIC MDS D460
Memory
Memory configuration
UID 8 bytes
User memory 2000 bytes FRAM
OPT memory 16 bytes FRAM
ISO transponder
8.22 MDS D460
SIMATIC RF300
348 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-4AB00
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Epoxy resin
Color Black
Recommended distance to metal
≥ 10 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP67
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
16 x 3 mm
Weight 3 g
Type of mounting Glued
With spacer
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.22 MDS D460
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 349
8.22.5
Dimension drawings
Dimensional drawing of MDS D460
Dimensions in mm
Figure 8-57 Dimensional drawing of MDS D460
Dimensional drawing of spacer
Dimensions in mm
Figure 8-58 Dimensional drawing of spacer
ISO transponder
8.23 MDS D521
SIMATIC RF300
350 System Manual, 07/2016, C79000-G8976-C345-0x
8.23
MDS D521
8.23.1
Characteristics
MDS D521
Characteristics
Area of application The MDS D521 is designed for tool coding according to DIN
69873.
It can be used wherever small data carriers and exact positioning
are required, e.g. tool identification, workpiece holders.
The rugged housing of the MDS D521 means that it can also be
used in a harsh industrial environment without problems.
Memory size
8192 bytes of FRAM user memory
Write/read range
See section "Field data of ISO transponders (MDS D) (Page 52)"
Mounting on metal
Yes, flush-mounted in metal
ISO standard
ISO 15693
Degree of protection
IP67/IPx9K
8.23.2
Ordering data
Table 8- 57 Ordering data for MDS D521
Article number
MDS D521
6GT2600-5AE00
8.23.3
Mounting on metal
Mounting on metal
Figure 8-59 Mounting of MDS D421/D521/E623 on metal
ISO transponder
8.23 MDS D521
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 351
Flush-mounting
Figure 8-60 Mounting of MDS D421/D521/E623 in metal
Flush-mounting of the MDS in metal with tools
Figure 8-61 Flush-mounting of MDS D421/D521/E623 in metal with tools
b
1
0.5 x 45°
b
2
0.3 x 45° or R0.3
d
1
10 (-0.04... -0.13)
d
2
10 (+0.09... 0)
t1
4.5 (-0 ... -0.1)
t2
4.6 (+0.2 ... 0)
All dimensions in mm
Note
Installation instruction
The MDS should not protrude out of the locating hole; it must be flush with the outside
contour.
The mounting instructions of the MDS and the conditions associated with the application
(e.g. peripheral speed,
temperature, and use of coolant) must be observed during the
installation.
ISO transponder
8.23 MDS D521
SIMATIC RF300
352 System Manual, 07/2016, C79000-G8976-C345-0x
Mounting information for adhesion
Drill installation hole
The adhesive surfaces must be dry, free from dust, oil, stripping agents and other
impurities
Apply adhesive according to the manufacturer's processing instructions
Press in transponder using your fingers; with antenna side to the outside (see figure
above)
Remove residues of adhesive
Allow to cure according to the manufacturer's instructions
Flush-mounting of the transponder in metal with tools
Installation examples
Figure 8-62 Installation example of MDS D421/D521/E623 in a steep cone
Figure 8-63 Installation example of MDS D421/D521/E623 in a stud bolt
ISO transponder
8.23 MDS D521
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 353
8.23.4
Technical specifications
Table 8- 58 Technical specifications for MDS D521
6GT2600-5AE00
Product type designation
SIMATIC MDS D521
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Epoxy resin
Color Black
Recommended distance to metal
> 25 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP67
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to EN 60721-3-7 class 7M3
100 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
ISO transponder
8.23 MDS D521
SIMATIC RF300
354 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-5AE00
Design, dimensions and weight
Dimensions (Ø x H)
10 x 4.5 mm
Weight
4 g
Type of mounting
Glued
2)
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2) The manufacturer's processing instructions must be observed.
8.23.5
Dimension drawing
Figure 8-64 Dimension drawing of MDS D521
All dimensions in mm
ISO transponder
8.24 MDS D522
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 355
8.24
MDS D522
8.24.1
Characteristics
MDS D522
Characteristics
Area of application Identification of metallic workpiece holders, work-
pieces or containers
Memory size
8192 bytes of FRAM user memory
Write/read range See "Field data of ISO transponders (MDS D)
(Page 52)."
Mounting in metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68
8.24.2
Ordering data
Table 8- 59 Ordering data for MDS D522
Article number
MDS D522
Units in a package: 10 units
A mounting aid is included in the scope of supply per packaging
unit.
6GT2600-5AF00
8.24.3
Mounting in metal
Flush-mounting
Figure 8-65 Mounting of MDS D522 in metal
ISO transponder
8.24 MDS D522
SIMATIC RF300
356 System Manual, 07/2016, C79000-G8976-C345-0x
Mounting information for screws
You can screw the transponder into a pre-drilled threaded hole using the screw-in aid.
Mounting information for adhesion
Drill installation hole
The adhesive surfaces must be dry, free from dust, oil, stripping agents and other
impurities
Apply adhesive according to the manufacturer's processing instructions
Press in MDS D522 using your fingers; with antenna to the outside
Remove residues of adhesive
Allow to cure according to the manufacturer's instructions
Flush-mounting of MDS D522 in metal with tools
8.24.4
Technical specifications
Table 8- 60 Technical specifications for MDS D522
6GT2600-5AF00
Product type designation
SIMATIC MDS D522
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
285 years
Mechanical specifications
Housing
Material Plastic PA 6.6 GF; brass nickel plated
Color Black/silver
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
ISO transponder
8.24 MDS D522
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 357
6GT2600-5AF00
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
Shock-resistant to EN 60721-3-7 class 7M3
50 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
20 x 6 mm
Weight
13 g
Type of mounting Glued
1 x transponder thread M20
≤ 1 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
8.24.5
Dimension drawing
Figure 8-66 Dimensional drawing of MDS D522
All dimensions in mm
ISO transponder
8.25 MDS D522 special variant
SIMATIC RF300
358 System Manual, 07/2016, C79000-G8976-C345-0x
8.25
MDS D522 special variant
8.25.1
Characteristics
MDS D522 special version
Characteristics
Area of application Identification of metallic workpiece holders or work-
pieces
Memory size
8192 bytes of FRAM user memory
Write/read range See "Field data of ISO transponders (MDS D)
(Page 52)."
Mounting in metal
Yes
ISO standard
ISO 15693
Degree of protection IP68
8.25.2
Ordering data
Table 8- 61 MDS D522 special version
Article number
MDS D522 special version
Units in a package: 10 units
A mounting aid is included in the scope of supply per packaging
unit.
6GT2600-5AF00-0AX0
ISO transponder
8.25 MDS D522 special variant
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 359
8.25.3
Mounting in metal
Flush-mounting
Figure 8-67 Flush installation of the MDS D522 special version in metal without clearance
8.25.4
Installation instructions
The transponder MDS D522 special version is designed to be mounted once.
Note the following instructions when mounting the MDS D522 in a workpiece to avoid
damaging the transponder:
Prepare the workpiece according to the following drawing.
Using the accompanying mounting aid, press the transponder with uniform and evenly
distributed pressure into the drilled hole until the transponder locks in place. Make sure
that the transponder does not become tilted.
ISO transponder
8.25 MDS D522 special variant
SIMATIC RF300
360 System Manual, 07/2016, C79000-G8976-C345-0x
Figure 8-68 Dimension drawing: Workpiece drill hole for mounting the MDS D522 special version
ISO transponder
8.25 MDS D522 special variant
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 361
8.25.5
Technical specifications
Table 8- 62 Technical data of MDS D522 special version
6GT2600-5AF00-0AX0
Product type designation
SIMATIC MDS D522 special version
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
Shock-resistant to EN 60721-3-7 class 7M3 50 g 1)
Vibration-resistant to EN 60721-3-7, class 7M3 20 g 1)
Torsion and bending load Not permitted
Design, dimensions and weight
Dimensions (Ø x H) 18 (+0.1) × 5.2 mm
Weight
Approx. 1.2 g
Type of mounting
Clipping in once (with accompanying tool)
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.25 MDS D522 special variant
SIMATIC RF300
362 System Manual, 07/2016, C79000-G8976-C345-0x
8.25.6
Dimensional drawing
Figure 8-69 Dimension drawing MDS D522 special version
All dimensions in mm
ISO transponder
8.26 MDS D524
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 363
8.26
MDS D524
8.26.1
Characteristics
MDS D524
Characteristics
Area of application Production and distribution logistics as well as in assem-
bly and production lines,
can also be used in a harsh industrial environment without
problem
Memory size
8192 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)."
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP67; IPx9K
8.26.2
Ordering data
Table 8- 63 Ordering data for MDS D524
Article number
MDS D524
6GT2600-5AC00
Table 8- 64 Ordering data of MDS D524 accessories
Article number
Spacer
6GT2690-0AK00
ISO transponder
8.26 MDS D524
SIMATIC RF300
364 System Manual, 07/2016, C79000-G8976-C345-0x
8.26.3
Mounting on metal
Mounting on metal
h
≥ 15 mm
Figure 8-70 Mounting the MDS D124/D324/D424/D524/E624 and RF320T on metal with spacer
Flush-mounting
h
≥ 15 mm
a
≥ 25 mm
Figure 8-71 Flush-mounting of the MDS D124/D324/D424/D524/E624 and RF320T in metal with
spacer
ISO transponder
8.26 MDS D524
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 365
Note
Going below the distances
If the distances (a and h) are not observed, a reduction of the field data results. It is possible
to mount the MDS with metal screws (M3 countersunk head screws). This has no tangible
impact on the range.
8.26.4
Technical specifications
Table 8- 65 Technical specifications for MDS D524
6GT2600-5AC00
Product type designation
SIMATIC MDS D524
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Epoxy resin
Color Black
Recommended distance to metal
≥ 25 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
ISO transponder
8.26 MDS D524
SIMATIC RF300
366 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-5AC00
Degree of protection to EN 60529 IP67
IPx9K
Shock-resistant to EN 60721-3-7 class 7M3
100 g
1)
Vibration-resistant to EN 60721-3-7, class 7M3
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
27 x 4 mm
Weight
5 g
Type of mounting Glued
1 x M3 screw 2)
≤ 1 Nm
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2 ) To prevent it loosening during operation, secure the screw with screw locking varnish.
8.26.5
Dimension drawing
Figure 8-72 Dimensional drawing of MDS D524
All dimensions in mm
ISO transponder
8.27 MDS D525
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 367
8.27
MDS D525
8.27.1
Characteristics
MDS D525
Characteristics
Area of application Compact and rugged ISO transponder; suitable for screw
mounting
Use in assembly and production lines in the powertrain
sector; ideal for mounting on motors, gearboxes, and work-
piece holders
Rugged packaging of the MDS D525; can therefore also be
used under extreme environmental conditions without prob-
lems
Memory size
8192 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)".
Mounting on metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68/IPx9K
8.27.2
Ordering data
Table 8- 66 Ordering data for MDS D525
Article number
MDS D525
6GT2600-5AG00
ISO transponder
8.27 MDS D525
SIMATIC RF300
368 System Manual, 07/2016, C79000-G8976-C345-0x
8.27.3
Application example
Figure 8-73 Application example
8.27.4
Technical specifications
Table 8- 67 Technical specifications for MDS D525
6GT2600-5AG00
Product type designation SIMATIC MDS D525
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
OPT memory 16 bytes FRAM
Read cycles (at < 40 ℃) > 1012
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.27 MDS D525
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 369
6GT2600-5AG00
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
> 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +125 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
24 x 10 mm (without set screw)
Weight
35 g
Type of mounting 1x transponder set screw M6
SW 22; ≤ 6 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.27 MDS D525
SIMATIC RF300
370 System Manual, 07/2016, C79000-G8976-C345-0x
8.27.5
Dimension drawing
Figure 8-74 Dimensional drawing of MDS D525
All dimensions in mm
ISO transponder
8.28 MDS D526
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 371
8.28
MDS D526
8.28.1
Characteristics
MDS D526
Characteristics
Area of application Compact and rugged ISO transponder; suitable for identification
of transport units in production-related logistics; can also be de-
ployed in harsh conditions
Memory size 8192 bytes of FRAM user memory
Write/read range
See section "Field data of ISO transponders (MDS D) (Page 52)."
Mounting on metal
Yes, with spacer
ISO standard
ISO 15693
Degree of protection
IP68
8.28.2
Ordering data
Table 8- 68 Ordering data for MDS D526
Article number
MDS D526
6GT2600-5AH00
Table 8- 69 Ordering data for MDS D526 accessories
Article number
Spacer
6GT2690-0AL00
ISO transponder
8.28 MDS D526
SIMATIC RF300
372 System Manual, 07/2016, C79000-G8976-C345-0x
8.28.3
Mounting on metal
Mounting on metal
h
≥ 25 mm
Figure 8-75 Mounting the MDS D126 / D426 / D526 on metal with spacer
Flush-mounted in metal
h
≥ 25 mm
a
≥ 50 mm
Figure 8-76 Flush installation of the MDS D126 / D426 / D526 in metal with spacer
ISO transponder
8.28 MDS D526
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 373
8.28.4
Technical specifications
Table 8- 70 Technical specifications for MDS D526
6GT2600-5AH00
Product type designation
SIMATIC MDS D526
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
OTP ???
Read cycles (at < 40 ℃)
> 10
12
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 25 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +100 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load Not permitted
ISO transponder
8.28 MDS D526
SIMATIC RF300
374 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2600-5AH00
Design, dimensions and weight
Dimensions (Ø x H)
50 x 3.6 mm
Weight
13 g
Type of mounting 1 x M4 screw 2)
≤ 1 Nm
1)
The values for shock and vibration are maximum values and must not be applied continuously.
2 ) To prevent it loosening during operation, secure the screw with screw locking varnish.
8.28.5
Dimension drawing
Figure 8-77 Dimensional drawing of MDS D526
All dimensions in mm
ISO transponder
8.29 MDS D528
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 375
8.29
MDS D528
8.29.1
Characteristics
MDS D528
Characteristics
Area of application Compact and rugged ISO transponder; suitable for screw
mounting
Use in assembly and production lines in the powertrain
sector
The rugged housing of the MDS D528 means that it can
also be used in extreme environmental conditions without
problems.
Memory size
8192 bytes of FRAM user memory
Write/read range See section "Field data of ISO transponders (MDS D)
(Page 52)"
Mounting on metal
Yes
ISO standard
ISO 15693
Degree of protection
IP68/IPx9K
8.29.2
Ordering data
Table 8- 71 Ordering data for MDS D528
Article number
MDS D528
6GT2600-5AK00
ISO transponder
8.29 MDS D528
SIMATIC RF300
376 System Manual, 07/2016, C79000-G8976-C345-0x
8.29.3
Application example
Figure 8-78 Application example
8.29.4
Technical specifications
Table 8- 72 Technical specifications for MDS D528
6GT2600-5AK00
Product type designation SIMATIC MDS D528
Memory
Memory configuration
UID 8 bytes
User memory 8192 bytes FRAM
OTP ???
Read cycles (at < 40 ℃) > 1012
Write cycles (at < 40 ℃)
> 10
12
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (Sg) Dependent on the reader used, see section "Field
data of ISO transponders (MDS D) (Page 52)"
MTBF (Mean Time Between Failures)
228 years
ISO transponder
8.29 MDS D528
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 377
6GT2600-5AK00
Mechanical specifications
Housing
Material Plastic PA 6.6 GF
Color Black
Recommended distance to metal
≥ 0 mm
Power supply
Inductive, without battery
Permitted ambient conditions
Ambient temperature
During operation -25 to +85
During transportation and storage -40 to +125 ℃
Degree of protection to EN 60529 IP68
2 hours, 2 bar, +20 °C
IPx9K
steam jet: 150 mm; 10 to 15 l/min; 100 bar; 75
°C
Shock-resistant to IEC 68-2-27
50 g
1)
Vibration-resistant to IEC 68-2-6
20 g
1)
Torsion and bending load
Not permitted
Design, dimensions and weight
Dimensions (Ø x H)
24 x 20 mm (without set screw)
Weight
35 g
Type of mounting 1x transponder set screw M8
SW 22; ≤ 8 Nm
1) The values for shock and vibration are maximum values and must not be applied continuously.
ISO transponder
8.29 MDS D528
SIMATIC RF300
378 System Manual, 07/2016, C79000-G8976-C345-0x
8.29.5
Dimension drawing
Figure 8-79 Dimensional drawing of MDS D528
All dimensions in mm
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 379
System integration
9
The communication modules (interface modules) are links between the RFID components
(reader and transponder) and the higher-level controllers (e.g. SIMATIC S7), or PCs or
computers.
9.1
Introduction
The readers are connected to the controller via the following interface or communications
modules:
ASM 456
ASM 475
SIMATIC RF120C
SIMATIC RF160C
SIMATIC RF170C
SIMATIC RF180C
SIMATIC RF182C
RFID 181EIP
Function blocks, interface modules/communication modules and readers
Function blocks are used for integration into the SIMATIC. You will find information on the
following blocks on the Internet in "Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/14971)".
Ident profile and Ident blocks, standard function for RFID systems
The Ident library linked into the TIA Portal as of STEP 7 Basic / Professional V14 SP 1
RFID standard profile; standard functions for RFID systems
FB 45 for MOBY U, MOBY D, RF200, RF300
FB 55
RF160C communications module with FC 44
System integration
9.1 Introduction
SIMATIC RF300
380 System Manual, 07/2016, C79000-G8976-C345-0x
Interface modules/communication modules and function blocks
The following table shows the most important characteristics of the interface
modules/communications modules.
Table 9- 1 Overview of interface modules/communication modules
ASM/
communications
module
Interfaces to the
application
(PLC)
Interfaces to the
reader
Reader con-
nections
Dimensions
(W x H x D)
Temperature
range
Degree of
protection
ASM 456 PROFIBUS DP-
V1
2 x 8-pin connector
socket, M12
2 (parallel) 60 x 210 x 54
or 79 mm
0 ℃ to +55
IP67
ASM 475 S7-300 (cen-
tral), ET200M
(PROFIBUS)
Via screw terminals
in front connector
2 40 x 125 x 120 mm 0 ℃ to +60
IP20
SIMATIC
RF120C
S7-1200 (cen-
tral)
9-pin D-sub socket 1 30 x 100 x 75 mm 0 ℃ to +55
IP20
SIMATIC
RF160C
PROFIBUS DP
/ DP-V0
2 x 8-pin connector
socket, M12
2 (parallel) 60 x 210 x 30 mm 0 ℃ to +55
IP67
SIMATIC
RF170C
PROFIBUS DP-
V1
PROFINET IO
2 x 8-pin connector
socket, M12
2 (parallel) 90 x 130 x 60 mm -25 °C to
+55 °C
IP67
SIMATIC
RF180C
PROFINET IO 2 x 8-pin connector
socket, M12
2 (parallel) 60 x 210 x 54 mm 0 °C to
+60° C
IP67
SIMATIC
RF182C
TCP/IP 2 x 8-pin connector
socket, M12
2 (parallel) 60 x 210 x 30 mm 0 ℃ to +60
IP67
RFID 181EIP Ethernet IP 2 x 8-pin connector
socket, M12
2 (parallel) 60 x 210 x 54 mm 0 °C to
+60° C
IP67
The following table shows the program blocks compatible with the interface
modules/communications modules.
System integration
9.1 Introduction
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 381
Table 9- 2 Compatible program blocks
ASM/
communications mod-
ule
Compatible program blocks in conjunction with ...
S7-300 / S7-400 and
STEP 7 Classic V5.5
S7-300 / S7-400 and
STEP 7 Basic/Professional
S7-1200 / S7-1500 and
STEP 7 Basic/Professional
ASM 456
FB 45
FB 55
Standard profile V1.19
Ident profile
FB 45
FB 55
Ident profile
Ident profile
Ident blocks
PIB_1200_UID_001KB
PIB_1200_UID_032KB
ASM 475
FB 45
FB 55
FB 45
FB 55
--
SIMATIC RF120C
-- -- Ident profile
Ident blocks
PIB_1200_UID_001KB
PIB_1200_UID_032KB
SIMATIC RF160C
FC 44
Application blocks for RF160C
FC 44
Application blocks for RF160C
Application blocks for RF160C
SIMATIC RF170C
FB 45
FB 55
FB 45
FB 55
--
SIMATIC RF180C
FB 45
FB 55
Standard profile V1.19
Ident profile
FB 45
FB 55
Ident profile
Ident profile
Ident blocks
PIB_1200_UID_001KB
PIB_1200_UID_032KB
System integration
9.2 ASM 456
SIMATIC RF300
382 System Manual, 07/2016, C79000-G8976-C345-0x
9.2
ASM 456
Configured with ASM 456
Figure 9-1 Configuration of ASM 456
For more detailed information, please refer to ASM 456 Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/view/32629442).
9.3
ASM 475
9.3.1
Features
Area of application
The ASM 475 interface module acting as the link between all RF300 systems and SIMATIC
S7-300 performs the functions of a communication module. It can be operated centrally in
the S7-300 or decentrally in an ET200M.
As many as eight ASM 475 interface modules can be plugged into one SIMATIC S7-300
rack and operated. In a configuration with several racks (max. four), the ASM 475 can be
plugged into and operated on any rack. This means that as many as 32 ASMs can be
operated in the maximum configuration of a SIMATIC S7-300. The ASM can also be
operated in the ET 200M distributed I/O on PROFIBUS. Operation in an S7-400 environment
is therefore problem-free. Up to 7 ASMs can be operated on each ET 200M.
Error messages and operating statuses are indicated by LEDs.
Since there is electrical isolation between the read/write device and the SIMATIC S7-300
bus, a configuration that is immune to interference is possible.
System integration
9.3 ASM 475
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 383
Figure 9-2 Interface module ASM 475
The ASM 475 with the article number 6GT2002-0GA10 is a module that can be set in the
parameters. The basic functions of the module are then already specified when the module
is configured in HW Config (e.g. standard addressing).
The data in the MDS is accessed direct by means of physical addresses using the ASM 475.
Operation in a SIMATIC S7 is controlled by the function block FB 45.
ASM 475 and FB 45 form a unit that is used for reading the data of the MDS simply and at
optimal speed.
9.3.2
Ordering data
Table 9- 3 Ordering data for ASM 475
Article number
ASM 475 interface module for SIMATIC S7
2 x RF3xxR reader with RS-422 can be connected in paral-
lel, without front connector
6GT2002-0GA10
Table 9- 4 Ordering data for ASM 475 accessories
Article number
Front connector (1 x per ASM)
6ES7392-1AJ00-0AA0
Connecting cable ASM 475 ↔ RF3xxR
Plug-in cable, pre-assembled, length: 2 m (standard length)
6GT2891-0EH20
Plug-in cable, pre-assembled, length: 5 m
6GT2891-0EH50
Terminal element (1 x per reader cable)
6ES7390-5BA00-0AA0
Shield connecting element
6ES7390-5AA00-0AA0
The plug-in cables 6GT2891-4Fxx can be used as extension cables.
System integration
9.3 ASM 475
SIMATIC RF300
384 System Manual, 07/2016, C79000-G8976-C345-0x
9.3.3
Indicators
Bezel and indicator elements
The figure below illustrates the bezel of the ASM 475 and the inside of the front door
complete with the associated connection diagram. The read/write devices must be
connected to the ASM in accordance with the connection diagram.
Figure 9-3 Bezel and inside of the front door of the ASM 475
System integration
9.3 ASM 475
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 385
Display elements on the ASM
Table 9- 5 Function of the LEDs on the ASM 475
Light emitting diode
Meaning
SF
System fault (hardware error on ASM)
DC 5V 24 V are connected to ASM and the 5 V voltage on ASM is OK.
ACT_1, ACT_2
The corresponding reader is active in processing a user command.
ERR_1, ERR_2 A flashing pattern indicates the last error to occur. This display can be reset
using the parameter Option 1.
PRE_1, PRE_2
Indicates the presence of a transponder.
RxD_1, RxD_2 Indicates live communication with the reader. In the event of a fault on the
reader, this display may also be lit.
On the ASM 475, further operating states are indicated with the LEDs PRE, ERR and SF:
Table 9- 6 Operating status display on ASM 475 via LEDs
SF
PRE_1
ERR_1
PRE_2
ERR_2
Meaning
ON OFF/ON ON
(perm.)
OFF/ON ON
(perm.)
Hardware is defective (RAM, Flash, etc.)
ON OFF ON OFF OFF Charger is defective (can only be repaired in
the factory).
OFF 2 Hz OFF 2 Hz OFF Firmware loading is active or no
 firmware
detected
Firmware download
ASM must not be switched off
OFF 2 Hz 2 Hz 2 Hz 2 Hz Firmware loading
terminated with errors
Restart required
Load firmware again
Check update files
Any
value
5 Hz 5 Hz 5 Hz 5 Hz Operating system error
Switch ASM off/on
OFF OFF 1 flash
every 2 s
OFF 1 flash
every 2 s
ASM has booted and is waiting for a RESET
(init_run) from the user.
System integration
9.3 ASM 475
SIMATIC RF300
386 System Manual, 07/2016, C79000-G8976-C345-0x
9.3.4
Configuration
Centralized configuration with SIMATIC S7-300
Figure 9-4 Configuration of ASM 475 central
Distributed configuration with ET200M
Figure 9-5 Configuration of ASM 475 distributed
Reader connection system
You will find more information on the reader connector technology in the section "Reader
RF3xxR (RS422) with ASM 475 (Page 419)".
System integration
9.3 ASM 475
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 387
Cable installation
Signal
Pin on
M12 connect-
or
Cable
Labeling
24 VDC 1 white 1 Reader 2
8 -16
TX - 2 brown 1 Reader 2
7-15
GND 3 Green 1 Reader 2
9-17
TX + 4 Yellow 1 Reader 2
6-14
RX + 5 Gray 1 Reader 2
4-12
RX - 6 Pink 1 Reader 2
5-13
Shield
8 +
-
Cable assignment for connection of an RF300 reader to ASM 475
System integration
9.3 ASM 475
SIMATIC RF300
388 System Manual, 07/2016, C79000-G8976-C345-0x
9.3.5
Shield connection
When the reader is connected to the ASM 475, the cable shield must be connected to a
shield terminal. Shield terminals and holding clips are standard components of the product
spectrum of S7-300.
Holding bracket
Cable to 2nd reader
Cable to 1st reader
Shield terminal
Figure 9-6 Shield terminal ASM 475
System integration
9.3 ASM 475
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 389
9.3.6
Technical data
Table 9- 7 Technical specifications for ASM 475
6GT2002-0GA10
Product type designation
ASM 475 communications module
Interfaces
Design of the interface
point-to-point link
RS-422
Number of connectable readers
2
Electrical connector design
Backplane bus S7-300 backplane bus
PROFIBUS interface (according to the head module)
Industrial Ethernet interface (according to the head module)
Supply voltage Screw-type or spring-loaded terminals
Design of the interface
to the reader for communication
Screw-type or spring-loaded terminals
Mechanical specifications
Housing
Material Noryl
Color Anthracite
Supply voltage, current consumption, power loss
Supply voltage
24 VDC
Typical current consumption
Without connected devices 0.1 A
Including connected devices 1.0 A
Power dissipation of the module, typ.
2 Watts
Current consumption from I/O bus, max.
80 mA
Electrical isolation between S7-300 and RF300
Yes
Fuse 24 V for the reader
Yes, electronic
System integration
9.3 ASM 475
SIMATIC RF300
390 System Manual, 07/2016, C79000-G8976-C345-0x
6GT2002-0GA10
Permitted ambient conditions
Ambient temperature
During operation (horizontal installation) 0 ... +60 ℃
During operation (vertical installation) 0 ... +40 ℃
During transportation and storage -40 ... +70 ℃
Degree of protection
IP20
Shock-resistant to IEC 61131-2
150 m/s
2
Vibration-resistant to IEC 61131-2
10 m/s
2
Design, dimensions and weight
Dimensions (L x W x H)
120 x 40 x 125 mm
Weight
0.2 kg
Type of mounting
S7-300 rack
Cable length for RS-422 interface, maximum
1000 m
Product properties, functions, components general
LED display design 4 LEDs per reader connector
2 LEDs for device status
Product function transponder
file handler addressable
Yes
Protocol supported
S7 communication
Yes
Product functions management, configuration, engineering
Type of parameter assignment Object manager, GSD
Type of programming FB 45, FB 55, FC 56
(FC 45/55 with restricted functionality)
Type of computer-based communication
2 words cyclic, 238 bytes acyclic
Transponder addressing Direct access via addresses
Commands Initialize transponder, read data from transpond-
er, write data to transponder
Standards, specifications, approvals
Proof of suitability
CE, FCC, UL/CSA
System integration
9.4 RF120C
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 391
9.4
RF120C
Configuration with RF120C
Figure 9-7 Configuration RF120C
For more detailed information, refer to the section " RF120C communications module
(https://support.industry.siemens.com/cs/ww/en/view/77485950)".
9.5
RF160C
Configuration with RF160C
Figure 9-8 Configuration RF160C
For more detailed information, refer to Operating Instructions RF160C
(https://support.industry.siemens.com/cs/ww/en/view/42788808).
System integration
9.6 RF170C
SIMATIC RF300
392 System Manual, 07/2016, C79000-G8976-C345-0x
9.6
RF170C
Configuration with RF170C
Figure 9-9 Configuration RF170C
For more detailed information, please refer to SIMATIC RF170C Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/view/32622825).
System integration
9.7 RF180C
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 393
9.7
RF180C
Configured with RF180C
Figure 9-10 Configuration of RF180C
For more detailed information, refer to SIMATIC RF180C Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/view/30012157).
System integration
9.8 RF182C
SIMATIC RF300
394 System Manual, 07/2016, C79000-G8976-C345-0x
9.8
RF182C
Configuration with RF182C
Figure 9-11 Configuration with RF182C
For more detailed information, refer to SIMATIC RF182C Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/view/38507897).
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 395
System diagnostics
10
10.1
Error codes
Error codes of the RF300 readers
Note
Validity of the error codes
The followin
g error codes apply only to RF300 readers with an RS-422 interface (except for
Scanmode).
You can identify the error code in different ways:
Directly on the reader/interface module by counting the flashing pattern of the red error
LED
In the Ident profile with the output variable "Status"
with FB 45 / FB 55 variable "error_MOBY".
System diagnostics
10.1 Error codes
SIMATIC RF300
396 System Manual, 07/2016, C79000-G8976-C345-0x
Table 10- 1 Error codes of the readers
Flashing of the
red
LED operating
display on the
reader
Error code
(hexa-
decimal)
Description
00
00
No error
02 01 Presence error; possible causes:
The active command was not carried out completely
The transponder left the antenna field while the command was
being processed
Communication problem between reader and transponder
05 05 Parameter assignment error, possible causes:
Unknown command
Incorrect parameter
Function not allowed
06
06
Air interface faulty
11
0B
The MDS E transponder could not be successfully authenticated.
12 0C The transponder memory cannot be written, possible causes:
Hardware fault (memory faulty)
Memory write-protected (corresponding OTP area has already
been written)
13 0D Error in the specified memory address (access attempted to non-
existent or non-accessible memory areas).
19 13 Buffer overflow: Insufficient buffer available in the reader for saving
the command
20
14
Major system fault (hardware fault)
21
15
Parameter assignment error: bad parameter in RESET command
24
18
Command was sent to a reader that has not yet been initialized
25
19
Previous command is still active
28 1C Antenna is not identified Possible causes:
Antenna is not connected.
Antenna cable is defective.
30
1E
Incorrect number of characters in frame
31
1F
Running command cancelled by "RESET" command
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 397
10.2
Diagnostics functions - STEP 7 Classic
10.2.1
Overview
Extended diagnostic functions with SIMATIC RF300
With SIMATIC RF300, extended diagnostics functions are available which simplify
commissioning and maintenance.
This diagnostics data is accessed using the SIMATIC function blocks via the SLG Status and
MDS Status commands. These two commands can each be called in various modes
(subcommands) for which corresponding data structures (UDTs) are defined.
Table 10- 2 In RF300 mode
Command
Mode
(subcommand)
Meaning
SLG-STATUS
01
Hardware and firmware configuration, parameterization status
06 Communication error counter, current command status
MDS-STATUS 01 Serial number of the transponder (UID), memory configura-
tion.
EEPROM write-protection status
02 Serial number of the transponder (UID), HF field strength
value, communication error counter, presence counter (dura-
tion)
Overview of the diagnostic functions
Table 10- 3 In ISO mode
Command
Mode
(subcommand)
Meaning
SLG-STATUS
01
Hardware and firmware configuration, parameterization status
MDS-STATUS 03 Serial number of the transponder (UID), recognized tran-
sponder type number in the field (number = tag - type, see
reset parameter "ftim"), memory configuration, write protect
status (OTP), size and number of blocks in the user memory
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
398 System Manual, 07/2016, C79000-G8976-C345-0x
10.2.2
Reader diagnostics with SLG STATUS
The SLG STATUS command can be used to scan the status and diagnostics data of the
reader.
SLG STATUS (mode 01), corresponds to UDT 110
Name
Type
Possible Hex
values
Comment
hardware
char
(31 … 38)
Type of hardware
hardware_version word
0 ... FF
0 ... FF
HW version
= Version (high byte): Unused
= Version (low byte)
loader_version word
0 ... FF
0 ... FF
Version of loader
= Version (high byte)
= Version (low byte)
firmware
char
0 ... FF
Type of firmware
firmware_version word
0 ... FF
0 ... FF
Firmware version
= Version (high byte)
= Version (low byte)
driver char
31
Type of driver
3964R
driver_version word
0 ... FF
0 ... FF
Version of driver
= Version (high byte)
= Version (low byte)
interface byte
01
02
Interface type
= RS422
= RS232 (only RF380R)
baud byte
01
03
05
Transmission speed
= 19.2 Kbaud
= 57.6 Kbaud
= 115,2 Kbaud
distance_limiting_SLG byte This variable is only provided for the RF380R. Users are therefore able to check
the output power actually set. An incorrect value in the parameter "dis-
tance_limiting" of the RESET message frame results in the default setting "05".
Transmit power
02
0.5 W
03
0.75 W
04
1.0
05
1.25 W (default)
06
1.5 W
07
1.75 W
08
2.0 W
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 399
Name
Type
Possible Hex
values
Comment
multitag_SLG byte
01
Number of transponders (Multi/Pulk) that can be processed in
the antenna field
= Single tag mode
field_ON_time_SLG byte 00
01
03
04
05
06
07
08
0E
10
20
31
FF
= RF300 transponder
= ISO transponder (non-specific)
= ISO transponder (Infineon, MDS D300)
= ISO transponder (Fujitsu, MDS D400)
= ISO transponder (NXP, MDS D100)
= ISO transponder (Texas Instruments, MDS D200)
= ISO transponder (ST, LRI2K)
= ISO transponder (Fujitsu, MDS D500)
= ISO (setting with "scanning_time" and "fcon")
= RF300 transponder
= MDS E transponder
= General Mode
= Setting with "scanning_time" and "fcon"
status_ant byte
01
02
Status of the antenna
= Antenna On
= Antenna Off
MDS_control byte
00
01
04
Presence mode
= Operation without presence message
= Operation with presence message
= Operation with presence message (antenna is off. The an-
tenna is turned on only when a Read or Write command is
sent.)
SLG STATUS (mode 06), corresponds to UDT 280
Name
Type
Possible Hex
values
Comment
FZP byte 0 ... FF = Error counter, passive (errors during idle time)
ABZ
= Abort counter
CFZ
= Code error counter
SFZ
= Signature error counter
CRCFZ
= CRC error counter
BSTAT
= Current command status
ASMFZ = Interface problems to host (ASM/PC) parity, BCC, frame
error
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
400 System Manual, 07/2016, C79000-G8976-C345-0x
Note
Counter values are deleted.
All counter values are deleted after reading out (= execute
"SLG STATUS" command).
Explanations:
"FZP": counts interference pulses when communication with a transponder is not taking
place (e.g. electromagnetic interference caused by contactors, motors, etc.). Counter
values can, however, also be generated when a transponder is located at the edge of the
field even when there is no external interference.
"ABZ", "CFZ", "SFZ" and "CRCFZ" are counters for protocol errors which may occur
during reader-transponder communication. This can be caused by unsuitable
reader/transponder positioning (e.g. transponder on field boundary, several transponders
in the antenna field) or external EMC interference.
To ensure clear diagnosis of the quality of communication, it is recommended that an SLG
STATUS command (mode 06) is executed following receipt of the presence command to
reset the error counter.
The protocol error counters are not mutually independent. If a code error (CFZ) occurs, this
will cause a signature (SFZ) or CRC- (CRCFZ) error.
"BSTAT" is the status for the most recently executed command. A value other than 0
means that the previous command was repeated by the reader due to faults (see above).
"ASMFZ" signals line-conducted communication interference between the
communications module and the reader. Faults of this type can be caused by contact
problems on the connector or the cable connection.
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 401
10.2.3
Transponder diagnostics with MDS STATUS
The MDS STATUS command can be used to scan the status and diagnostics data of the
transponder that is located within the antenna field.
MDS STATUS (mode 1), corresponds to UDT 260 (only for RF300 transponders)
Name
Type
Possible Hex values
Comment
UID array[1…8] byte
000000005555555 ...
00000000FFFFFFFF
Unique identifier
= b0-31: 4 byte TAG ID, b32-63: 0
MDS_type byte
01
02
03
04
Transponder memory configuration
= Transponder without FRAM
= Transponder with FRAM 8 KB
= Transponder with FRAM 32 KB
= Transponder with FRAM 64 KB
Lock_state byte 0 ... FF EEPROM write protection status
MDS STATUS (mode 02), corresponds to UDT 270, only for RF300 transponders
Name
Type
Possible Hex values
Comment
UID array[1…8] byte
0000000055555555 ...
00000000FFFFFFFF
Unique identifier
= b0-31: 4 byte TAG ID, b32-63: 0
LFD
byte
0 ... FF
= Value for field strength determined in the transponder
FZP
byte
0 ... FF
= Error counter (passive) ➙ errors during idle time
FZA
byte
0 ... FF
= Error counter (active)
ANWZ
byte
0 ... FF
= Presence counter
System diagnostics
10.2 Diagnostics functions - STEP 7 Classic
SIMATIC RF300
402 System Manual, 07/2016, C79000-G8976-C345-0x
Note
Counter values are deleted.
All counter values are deleted when the transponder exits the antenna field or when the
antenna is switched off.
Explanations:
"LFD" is a measured value for the field strength that is determined in the transponder.
The lower the value, the higher the field strength.
"FZP" counts interference pulses when communication with a transponder is not taking
place (e.g. electromagnetic interference caused by contactors, motors, etc.). Counter
values can also be generated when a transponder is located at the edge of the field even
when there is no external interference.
"FZA" counts errors that can occur during reader-to-transponder communication. This can
be caused by unsuitable reader/transponder positioning (e.g. transponder on field
boundary, several data carriers in the field) or external electromagnetic interference.
"ANWZ" is the value for the time that the transponder remains in the field before the MDS
STATUS command (mode 02) is executed. A time step is 10 ms. The maximum time that
can be recorded is therefore 2.5 s.
MDS STATUS (mode 03), corresponds to UDT 230
Name
Type
Possible Values
Comment
UID array[1…8] byte
0000000000000000 ...
FFFFFFFFFFFFFFFF
Unique identifier
=8 byte UID, MSB first
MDS_type byte
00
03
04
05
06
07
08
11
12
13
14
15
16
21
22
23
Transponder type (vendor, identification)
= ISO transponder (non-specific)
= ISO transponder (Infineon, MDS D300)
= ISO transponder (Fujitsu, MDS D400)
= ISO transponder (Philips, MDS D100)
= ISO transponder (Texas Instruments, MDS D200)
= ISO transponder (ST, LRI2K)
= ISO transponder (Fujitsu, MDS D500)
= RF300 transponder (0 kB)
= RF300 transponder (8 kB)
= RF300 transponder (32 kB)
= RF300 transponder (64 kB)
= RF300 transponder (128 kB)
= RF300 transponder (256 kB)
= ISO transponder (NXP, 1 kB, MDS E)
= ISO transponder (Infineon, 1 kB, MDS E)
= ISO transponder (NXP, 4 kB)
System diagnostics
10.3 Diagnostics functions STEP 7 Basic / Professional
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x 403
Name
Type
Possible Values
Comment
binary
0 ... 255
Vendor-specific value
IC_version byte 0 ... FF Chip version
size byte 0 ... FF Memory size in bytes
Depending on transponder type, e.g. my-d: 992 bytes
lock_state byte 0 ... FF Lock state, OTP information:
One bit is used per block (4 x 4 bytes or 2 x 8 bytes)
(bit = 1: block is locked)
Example:
01 = Block 1 of address FF80 ... FF83 is locked or
03 = Block 1 and 2 of address FF80 ... FF87 are
locked,
e.g. for the Philips SL2 ICS20 (MDS D124, D160 or
D100).
This chip provides a usable memory with 112 bytes
EEPROM from address 0000 - 006F (total OTP area
"0060 ... 006F"). In this memory, the locked area corre-
sponds to the addresses 0060 ... 0063 or 0060 ... 0067
block_size byte 0 ... FF Block size of the transponder
Depending on transponder type, e.g. my-d: 4 bytes
nr_of_blocks byte 0 ... FF Number of blocks
Depending on transponder type, e.g. my-d: 248 bytes
10.3
Diagnostics functions STEP 7 Basic / Professional
Extensive diagnostics functions for the SIMATIC RF300 readers with STEP 7 Basic /
Professional are being planned. With the aid of the Ident profile and the Ident blocks, you
can make different diagnostics queries.
System diagnostics
10.3 Diagnostics functions STEP 7 Basic / Professional
SIMATIC RF300
404 System Manual, 07/2016, C79000-G8976-C345-0x