Siemens WTPIWLAN-V200 SIMATIC WTP 277F IWLAN User Manual Wireless Teach Pendant F IWLAN V2
Siemens AG SIMATIC WTP 277F IWLAN Wireless Teach Pendant F IWLAN V2
Siemens >
Contents
- 1. Users Manual p1
- 2. Users Manual p2
- 3. Users Manual p3
Users Manual p3
PRELIMINARY II 1.7.2010 Commissioning a project 8.5 Commissioning an RFID tag 4. Press "Save ID". The ID is sent to the RFID tag and stored there. A check mark is set in the "Tag" list, if the configured tag ID is successfully written to the RFID tag. NOTICE Recording the ID of the RFID tag If you replace the RFID tag at a later date due to a defect, for example, you will always need the ID of the RFID tag. Therefore, record the ID of the RFID tag so that it is at hand at all times. For example, write it on the front of the RFID tag using a permanent marker. 5. Repeat steps 2 to 4 for all RDIF tags of this effective range. When all the RFID tags of an effective range have an ID, the selected effective range has a check mark in the "Effective range" list. 6. Repeat steps 1 to 5 for all effective ranges. The "Calculate" button is gray and only becomes black again, and thus enabled, when all RFID tags have successfully been assigned an ID. 7. Press "Calculate". The CRC checksum is displayed. 8. Record the checksum or enter it immediately in "Effective ranges (RIFD)" in the WinCC flexible editor. 9. Click "Exit" to close the dialog. Result You have assigned a unique identifier to all RFID tags and determined a checksum. Transfer the project with the added CRC checksum again to the HMI device. You can log onto a machine and operate the machine in fail-safe mode. See also Replacing an RFID tag (Page 202) Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 201 PRELIMINARY II 1.7.2010 Commissioning a project 8.6 Replacing an RFID tag 8.6 Requirement Replacing an RFID tag If it is not possible to log onto an effective range, the HMI device or RFID tag may be defective. This section describes the configuration work carried out after replacement of a defective RFID tag. â The defective RFID tag has been replaced. â The ID of the defective RFID tag is available. â The project, in which the RFID tag has failed, is still on the HMI device. Procedure Proceed as follows: 1. Switch on the HMI device. 2. Open the Control Panel. 3. Press the "RFID Config" icon. The following dialog appears: 4. Select the effective range ID in the "Effective range" selection box and the ID of the defective RFID tag in the "Tag" selection box. 5. Bring the HMI device into the effective range of the RFID tag. 6. Press "Save ID". The HMI device transmits the ID to the RFID tag. The new RFID tag has the ID of the previously used RFID tags. 7. Click "Exit" to close the dialog. 8. Close the Control Panel and start the project. 9. Log the HMI device onto a machine to check the new RFID tag. â When the logon is successful, you can continue working in the project. â If logon is not possible close the dialog and repeat steps 2 to 8. 202 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Commissioning the plant 9.1 Overview The acceptance of the plant involves the following: â Safety-related project â Safety program â RFID tags with effective ranges 9.2 Acceptance of the plant All of the relevant application-specific standards and the procedure described in this section must be observed in the course of final acceptance of the plant. Note This section provides a detailed description of the additional tasks required for the fail-safe operation of the HMI device. Read the detailed description provided in the "System Acceptance Test" section of the "S7 Distributed Safety, Configuring and Programming" manual when performing an acceptance procedure for the plant. The acceptance of the plant involves the following tasks: â Configure the F-CPU and F-I/O â Create a safety program Requirement â The hardware configuration has been created in HW Config. â The safety program has been created and generated. â A backup of the STEP 7 project has been created. Configuring the F-CPU and F-I/O â Printing and archiving the hardware configuration. â Check the following parameters in the hardware configuration: â Parameters of the F-CPU â Parameters of the F-I/O This includes unique PROFIsafe addresses and additional PROFIsafe parameters. â Save the hardware configuration with the STEP 7 project. A detailed description is provided in the "Acceptance test for the configuration of the F-CPU and the F-I/O" section of the "S7 Distributed Safety, Configuring and Programming" manual. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 203 PRELIMINARY II 1.7.2010 Commissioning the plant 9.3 Diagnostics Acceptance of the safety program â Print and archive the safety program. â Check the printed copy of the safety program for existence of the criteria specified in the "S7 Distributed Safety, Configuring and Programming" manual, section "Acceptance of a safety program." â Download the entire safety program to the F-CPU. â Test all functions of the safety program. A detailed description is provided in the "Acceptance test for the configuration of the F-CPU and the F-I/O" section of the "S7 Distributed Safety, Configuring and Programming" manual. See also Programming and operation manual "S7 Distributed Safety - Configuring and Programming" (http://support.automation.siemens.com/WW/view/en/22099875) 9.3 Diagnostics Use the diagnostics function to determine the following: â Does signal acquisition function without errors on the HMI device? â Does the safety-related module of the HMI device work properly? Diagnostic function of the HMI device in STEP 7 The HMI device provides diagnostics conforming to PROFINET IO standard IEC 61784-1, Ed1, CP 3/3 for standard application. The diagnostics function cannot be parameterized. The diagnostics are always enabled and information is provided automatically by the HMI device in STEP 7 in the event of an error. The diagnostic function also passes the "Communication error" message, if at all possible, for the safety-related component. The communication between the HMI device as an input and output device, and the F-CPU and IO controller is disrupted. This situation can be caused, for example, by an incorrect PROFIsafe address or the lack of a wireless network. Reading diagnostics information Open the module diagnostics in STEP 7 to determine the cause of the error. For additional information, refer to the online help for STEP 7. You also have the option of reading the diagnostic information using SFB 52 or SFB 54 in the standard user program. For additional information, refer to the "System and Standard Functions" reference manual. 204 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Commissioning the plant 9.3 Diagnostics Diagnostic information for internal errors All LEDs of the LED display go out when an internal error of the HMI device causes a failure. When a project is running on the HMI device, the following occurs: â The project is closed. â The following error code message is displayed on the HMI device: A severe problem has occurred! Date: 2010-04-30 09:18 ErrorCode: 000 0008 00006 01506 Please report this error code to your technical support http://www.siemens.de/automation/support-request Procedure Proceed as follows: 1. Record the error number â see Error Code. 2. Switch off the HMI device. 3. Restart the HMI device. Contact Technical Support (http://support.automation.siemens.com/WW/llisapi.dll?aktprim=99&lang=en&referer=%2f WW%2f&func=cslib.csinfo2&siteid=csius&extranet=standard&viewreg=WW) if the error persists. Based on the error code, Technical Support can come to a conclusion about the type of internal error. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 205 PRELIMINARY II 1.7.2010 Commissioning the plant 9.3 Diagnostics Error code for discrepancy errors The following table lists the error codes for discrepancy errors. You may be able to find a remedy for a discrepancy error yourself, depending on the situation. The first six digits of the error code are decisive for the correct identification of the error. Error code Error type Remedy 000 008 Discrepancy error at the EMERGENCY STOP button Release the EMERGENCY STOP button. 000 014 Discrepancy error at the right enabling button, Panic switch position Make sure that the button does not become askew when it is pressed. 000 015 Discrepancy error at the left enabling button, Panic switch position The terms "left" and "right" enabling buttons refer to your position facing the display of the HMI device. See also Discrepancy error during enabling (Page 258) 206 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Fail-safe operation 10.1 10 Organizational measures The HMI device should only be operated in the plant with a main rechargeable battery or in the docking station. You must adhere to the organizational measures described in this section to ensure fail-safe operation of the HMI device. WARNING EMERGENCY STOP button out of service when HMI device is removed If the HMI device is not integrated in the safety program of the F-CPU, the EMERGENCY STOP button will be out of service. To avoid confusion between HMI devices with enabled and disabled EMERGENCY STOP buttons, only one integrated HMI device should be freely accessible. If an HMI device is not integrated and not in use, store the HMI device in a location with protected access. Handling the HMI device during operation CAUTION Shutdown or global rampdown may occur with an empty main rechargeable battery An integrated HMI device with an empty main rechargeable battery triggers a communication error. This error results in the following reaction of the F-CPU: ďˇ When the HMI device is logged onto a machine â shutdown ďˇ When the HMI device is not logged onto a machine â global rampdown Check the charge of the main rechargeable battery at brief intervals using the "BAT" LED. Note It is prohibited to leave the protection zone without an HMI device while the HMI device is logged onto a machine. Log off the HMI device from the machine before you leave the protection zone. Pay attention to the LED display of the HMI device â see section "LED display (Page 85)". Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 207 PRELIMINARY II 1.7.2010 Fail-safe operation 10.2 Switch-off behavior 10.2 Switch-off behavior The shutdown reaction of the plant will vary according to cause and effect. DANGER Shutdown The shutdown response described in the next sections is only triggered in the plant if the FCPU has been programmed accordingly. Programming the F-CPU accordingly. The following types of shutdown may occur depending on the operating state of the plant: â EMERGENCY STOP â Global rampdown â Local rampdown â Shutdown The following table shows the shutdown reaction depending on the operating state and the cause: Operating state Cause of the shutdown EMERGENCY STOP button pressed Communication error â â HMI device is in the protection zone EMERGENCY STOP Shutdown HMI device is outside the protection zone EMERGENCY STOP Shutdown HMI device is logged off from the machine EMERGENCY STOP Global rampdown HMI not integrated HMI integrated See also 208 HMI device is logged onto a machine Terms for fail-safe operation (Page 32) Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Fail-safe operation 10.3 Integrating the HMI device 10.3 Integrating the HMI device During fail-safe operation, a safety program runs in the F-CPU. The HMI device is integrated into this safety program. The HMI device and F-CPU communicate via PROFINET IO. When there is a project for a safety program on the HMI device, it is automatically integrated following the start of the project. The "SAFE" LED lights up to indicate that integration is complete. The EMERGENCY STOP button is enabled as soon as the HMI device is integrated. Requirement â WLAN â PROFIsafe safety-related bus profile, as of V2.0 â The plant has been accepted. â The loader is displayed on the HMI device. Procedure Proceed as follows: 1. Start the project. PROFIsafe communication is established. While the connection is being established, the "Establishing secure connection" dialog is displayed with the following symbol. The HMI device is integrated in the safety program of the F-CPU. The "SAFE" LED lights up. The "Test enabling switch" dialog is displayed with the following symbol. 2. Fully press down both enabling buttons. The project start screen appears. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 209 PRELIMINARY II 1.7.2010 Fail-safe operation 10.4 Logging onto a machine 10.4 Logging onto a machine The following figure shows the logon of an HMI device to a machine within a protection zone. 352),VDIH â ⥠⢠⣠⤠Protection zone Machine HMI device RFID tag 1 Access monitoring Requirement â WLAN connection â RFID tags have been commissioned â The HMI device is integrated 210 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Fail-safe operation 10.4 Logging onto a machine Procedure Proceed as follows: 1. Switch to the screen that contains the "Effective range name (RFID)" button labeled "Scan". 6FDQ 2. Bring the HMI device into the effective range of the RFID tag to which you want to log on, for example, "RFID Tag 1". The following table shows how to align the HMI device to the RFID tag. Alignment Logon Possible Not supported Not supported 3. Press the button labeled "Scan". During the scan procedure, the button is yellow and displays the text, "Scanning...". 6FDQQLQJ The HMI device reads the ID from the RFID tag. After the data transfer, the name of the effective range will be briefly displayed on the "Effective range name (RFID)" operator control, for example, "Robot 1". 5RERW The "Effective range logon" dialog is then displayed with the following symbol. Note As soon as the "Effective range logon" dialog is displayed, you can remove the HMI device from the effective range of the RFID tag. 4. Enter the ID of the effective range in the text box. The ID of the effective range is located on the label of the RFID tag. 5. Confirm the entry with "OK". The dialog closes. Note A message appears if the ID of the effective range is incorrect. The corresponding dialog must be acknowledged. Repeat the logon to the effective range with a valid ID. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 211 PRELIMINARY II 1.7.2010 Fail-safe operation 10.5 Logging off the machine The "Confirmation of logon" dialog is displayed with the following symbol. 6. Confirm the logon with the enabling button. The successful logon is indicated by the "RNG" LED on the HMI device. Result You are logged onto the machine and the machine can operate within the protection zone in fail-safe mode. The "Effective range name (RFID)" operator control is shown in green and labeled with the name of the effective range. The following figure shows the "Effective range name (RFID)" object after logon to an effective range with the name "Robot 1". 5RERW 10.5 Logging off the machine You do not need to stand directly in front of the RFID tag to log off the machine you are operating in fail-safe mode. Procedure Proceed as follows: 1. Press the "Effective range name (RFID)" operator control. 5DQJHQDPH The "Effective range logoff" dialog is displayed with the following symbol. 2. Confirm the logoff from the machine with the "OK" button. The "RNG" LED goes out when the logoff is successfully completed. Result â The HMI device is logged off the machine. â The "Effective range name (RFID)" operator control is shown in white and labeled "Scan". 6FDQ 212 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Fail-safe operation 10.6 Removing the HMI device 10.6 Removing the HMI device You have the following options for removing the HMI device: â Close the project. â Press and hold the "ON/OFF" button for at least 4 seconds. WARNING EMERGENCY STOP button out of service when HMI device is removed If the HMI device is not integrated in the safety program of the F-CPU, the EMERGENCY STOP button will be out of service. To avoid confusion between HMI devices with enabled and disabled EMERGENCY STOP buttons, only one integrated HMI device should be freely accessible. If an HMI device is not integrated and not in use, store the HMI device in a location with protected access. Requirement â The project must be started. â The HMI device is integrated into the safety program of the F-CPU. â The HMI device is not logged onto a machine. Procedure Proceed as follows: 1. Close all open dialogs. 2. Close the project using the operator control designed for this purpose or press the "ON/OFF" button for more than 4 seconds. The "Start removal" dialog is displayed with the following symbol. 3. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol. 4. Press an enabling button within 60 seconds. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 213 PRELIMINARY II 1.7.2010 Fail-safe operation 10.6 Removing the HMI device NOTICE Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds. The "Confirm removal" dialog closes. â The "SAFE" LED on the HMI device goes out. â PROFIsafe communication is terminated. â The HMI device has been successfully removed from the safety program of the FCPU. â The project is closed. â If you have pressed the ON/OFF" button during step 1, the HMI device switches off. 214 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.1 11 Starting the project Note A project may demand operator actions that require in-depth knowledge of the specific plant on part of the operator. Proceed with caution, for example, when you use jog mode. Refer to your plant documentation for additional information. Requirement The following requirements have to be met to start the project: â The plant has been accepted. â The main rechargeable battery is charged and inserted in the HMI device. If no main rechargeable battery is available, place the HMI device in the docking station. â The radio signal from the WLAN is sufficiently strong. â The PROFIsafe address is configured on the HMI device. â The data channel is configured on the HMI device. â The project has been transferred to the HMI device. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 215 PRELIMINARY II 1.7.2010 Operating a project 11.1 Starting the project Procedure Proceed as follows: 1. Press the "ON/OFF" button. The HMI device performs the following tasks: â The HMI device starts. â The "PWR" LED lights up. â The "BAT" LED shows the remaining charge of the main rechargeable battery. â The WLAN connection is established. The "COM" LED flashes while the connection is being established. The "COM" LED lights up when the WLAN connection is established. The project is started. â PROFIsafe communication is established. The "Establishment of safety connection" dialog is displayed. The HMI device is integrated once the PROFIsafe connection has been successfully established. The "SAFE" LED lights up. The EMERGENCY STOP button is enabled. â The "Test enabling button" dialog is displayed. 2. Fully press down both enabling buttons. Result The HMI device displays the start screen of the project. Log onto a machine to enable the enabling button. See also Logging onto a machine (Page 210) 216 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.2 Operator input options 11.2 Operator input options A project may demand operator actions that require in-depth knowledge of the specific plant on part of the operator. Proceed with caution, for example, when you use jog mode. Refer to your plant documentation for additional information. CAUTION Unintentional action If you press several operator controls at once, you may trigger an unintentional action. Do not carry out several operations simultaneously. ďˇ When using the touch screen: Never press more than one operator control on the touch screen at once. ďˇ When using an external keyboard: Do not press more than two keys at once Operator input options Once the project is transferred to the HMI device, you can operate and monitor active processes during the process control phase. You have the following operating options: â Touch screen The operator controls shown in the configured screens are touch-sensitive. Touch objects are operated in the same way as mechanical keys. You trigger an operator control by pressing it with your finger. To double-click an operator control, you tap it twice in quick succession. â Membrane keyboard You can use the numeric area of the membrane keyboard to enter numeric values. Note Read the section "Overview (Page 83)". â USB keyboard You can operate the Windows CE interface and Control Panel with an external keyboard in the exact same way as you do with the screen keyboard of the HMI device. â USB mouse You can operate the Windows CE interface and Control Panel with an external mouse in the exact same way as you do with the touch screen of the HMI device. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 217 PRELIMINARY II 1.7.2010 Operating a project 11.2 Operator input options Feedback from an operator control The HMI device provides optical feedback as soon as it detects that an operator controls has been selected. The operator control receives the focus and is selected. The selection is independent of any communication with a PLC. Therefore this selection does not indicate whether the relevant action is actually executed or not. The selection of an operator control can deviate from the standard. Refer to your plant documentation for additional information. The type of optical operation feedback depends on the operator control: â Button If the configuration engineer has configured a 3D effect, the button appears differently depending on the "Pressed" and "Not pressed" states: â "Pressed" state â "Not pressed" state The line width and color of the button are set during the configuration. â Invisible button By default, an invisible button is displayed as not pressed when it is selected. There is no optical operation feedback. The configuration engineer may, however, configure invisible buttons so that their outline appears as lines when they are pressed. This lines will remain visible until you press another operator control. â I/O field When you select an I/O field, the content of the I/O field is displayed against a colored background. With touch operation, a screen keyboard is displayed for the entering of values. 218 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.3 Direct keys 11.3 Direct keys A direct key on the HMI device is a direct way to set a bit in the I/O area of the controller. A direct key enables an operation with a fast response time. Fast response time is essential, for example, for jogging mode. NOTICE Leaving the WLAN Note that leaving the WLAN area will cause the PROFINET IO device to fail and therefore result in a PLC stop. Determine suitable programming measures in the PLC, in order to prevent a PLC stop. Refer to your plant documentation for additional information. Pressing a direct key If you trigger an operator control with direct key functionality in an active project, the corresponding function is always executed, regardless of the screen display at the time. Avoid pressing a direct key unintentionally. Note A direct key is enabled when both of the following conditions are satisfied: ďˇ The HMI device is in the WLAN with sufficient radio signal. ďˇ The HMI device is in "Offline" mode. The following objects can be configured as a direct key: â Button â Screen number â Illuminated pushbutton â Rotary switch Note Direct keys result in additional basic load on the HMI device. Additional information is available in the "WinCC flexible, Communication" system manual. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 219 PRELIMINARY II 1.7.2010 Operating a project 11.4 Setting the project language 11.4 Setting the project language The HMI device supports multilingual projects. You must have configured a corresponding operator control which lets you change the language setting on the HMI device during runtime. The project always starts with the language set in the previous session. Requirement â The required language for the project must be available on the HMI device â The language switching function must be logically linked to a configured operator control such as a button Selecting a language You can change project languages at any time. Language-specific objects are immediately output to the screen in the new language when you switch languages. The following options are available for switching the language: â A configured operator control switches from one language to the next in a list â A configured operator control directly sets the desired language More detailed information is available in your plant documentation. 11.5 Operating the screen keyboard in the project If you do not use an external keyboard, use the screen keyboard to enter numeric and alphanumeric characters. As soon as you touch a text box, a numeric or alphanumeric screen keyboard is displayed, depending on the type of the text box. Display methods for the screen keyboard You can change the type of display for the screen keyboard and move its position on the screen. â Numerical screen keyboard 220 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.5 Operating the screen keyboard in the project â Alphanumerical screen keyboard The alphanumerical screen keyboard has the following levels. â Normal level â Shift level The shift level includes uppercase letters. â Special character level Note The ' character (button between ";" and "\") appears only when followed by a space. If the ' character is followed by a letter, then the result will be an accent, such as "ĂĄ". â Reduced screen keyboard Note When the screen keyboard is open, PLC job 51, "Select screen" has no function. The screen keyboard display is independent of the configured project language. Language switching in the project has no influence on the alphanumerical screen keyboard. This means you cannot enter Cyrillic or Asian characters. Procedure for moving the screen keyboard Proceed as follows: 1. Touch the symbol and move the screen keyboard on the touch screen. 2. When the desired position is reached, release the icon Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 221 PRELIMINARY II 1.7.2010 Operating a project 11.5 Operating the screen keyboard in the project Procedure for adjusting the size of the screen keyboard Note icon only appears on the screen keyboard if in the "Siemens HMI InputPanel" dialog The you have selected the "Show Resize button" check box. Proceed as follows: 1. Touch the symbol and drag the screen keyboard to the appropriate size. 2. When the size you want is reached, release contact with the icon. Changing the display of the screen keyboard Key Function Switching between the numerical and alphanumerical keyboard Switching between the normal level and Shift level of the alphanumerical screen keyboard Switchover to special characters Switching from full display to reduced display Switching from reduced display to full display Closing of reduced display of the screen keyboard Entering data Key Function Delete character left of cursor Delete character right of cursor Confirm entry and close the screen keyboard Cancel input 222 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.5 Operating the screen keyboard in the project Note Data input - numerical text box ďˇ Hexadecimal values When you enter a value in hexadecimal format, the alphanumerical screen keyboard opens. ďˇ Decimal places The configuration engineer can define the number of decimal places for a numerical text box. The number of decimal places is checked when you enter a value in this type of I/O field. â Decimal places in excess of the limit are ignored. â Empty decimal places are filled with "0". ďˇ Limits A tag can be configured with limits. If you enter a value outside these limits, it will be rejected. If an alarm view is configured, a system event is triggered and the original value is displayed again. Data input â date and time When entering the date and time, note that their format is determined by the configured project language. Opening the Windows CE taskbar You open the Windows CE taskbar with the key. Displaying infotext The configuration engineer uses infotext to provide additional information and operating instructions. There may be infotext for HMI screens and operator controls in the project. The infotext for an I/O field may contain, for example, information on the value to be entered. The screen keyboard appears on the HMI device touch screen when you touch an operator control that requires input. If an infotext was configured for the current operator control, call button. If no infotext is available for the current operator control, up the infotext with the the infotext for the current HMI screen will be displayed. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 223 PRELIMINARY II 1.7.2010 Operating a project 11.6 Device-specific displays Note If an infotext was configured for the current control object as well as the current HMI screen, you can switch between both infotexts by touching the infotext window. Close the infotext window with the button. Depending on the project, infotext can also be called by an operator control configured for this purpose. For additional information, refer to the online help of WinCC flexible. 11.6 Device-specific displays 11.6.1 Overview This section describes the device-specific WinCC flexible objects, which you can use in a project for the Wireless Teach Pendant F IWLAN. For a full description of all WinCC flexible objects, refer to the online help of WinCC flexible. 11.6.2 Showing the battery charge The "Battery" object indicates the remaining charge of the main rechargeable battery. Charge the main rechargeable battery in time or replace it. Read the information provided in section "Replacing and charging the main rechargeable battery (Page 72)". The amount of charge for the main rechargeable battery is shown by the "Battery" object as follows: Icon Color Meaning Charge level Green The main rechargeable battery is sufficiently charged. > 20 % The charge is low. 6% to 20 % Yellow The main rechargeable battery must be charged or replaced. Red The charge is very low. <6% The main rechargeable battery must be charged or replaced. See also 224 Displaying the charge status of the batteries (Page 138) Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.6 Device-specific displays 11.6.3 Displaying WLAN quality The "WLAN quality" object indicates the signal strength of the wireless network at the location of the HMI device. The HMI device measures the signal strength and depicts it with the "WLAN quality" object. The signal strength of wireless network is indicated by the "WLAN quality" object as follows: Icon Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Meaning Signal strength No wireless connection No signal Very poor wireless connection ⤠20% Poor wireless connection ⤠40% > 20% Wireless connection OK ⤠60% > 40% Good wireless connection ⤠80% > 60% Very good wireless connection > 80% 225 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security 11.6.4 Displaying the "Effective range name (RFID)" object The "Effective range name (RFID)" object is only available for an HMI device of the RFID tag system. The "Effective range name (RFID)" object displays the following information: â Logon status â "Scan", "Scanning..." or name of the effective range associated with the machine on which the HMI device is logged on The "Effective range name (RFID)" object can show the following operating states: Icon 6FDQ 6FDQQLQJ Operating state Logon The HMI device is not logged onto a machine. It is not possible to log onto a machine. The enabling button is not enabled. To log onto a machine, the user must press the operator control and search for effective ranges. The user has pressed the operator control to search for effective ranges. Logon can only take place when the HMI device has detected an effective range. The HMI device searches for an effective range. The enabling button is not enabled. 5RERW The HMI device has detected the effective range, "Robot 1". The logon to the machine associated with the "Robot 1" effective range is possible. 5RERW The user is logged onto the machine associated with the "Robot 1" effective range. â The enabling button is enabled. 11.7 Project security 11.7.1 Overview Design of the security system The configuration engineer can protect the operation of a project by implementing a security system. The security system is based on authorizations, user groups and users. If operator controls protected by a password are pressed, the HMI device first requests that you log on. A logon screen is displayed in which you enter your user name and password. After logging on, you can press the operator controls for which you have the necessary authorizations. The logon dialog can be set up by the configuration engineer via an individual operator control. Similarly, an operator control can be configured for logoff. After logging off, objects with password protection can no longer be operated â you need to log on again. Refer to your plant documentation for additional information. 226 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security Central user administration using SIMATIC Logon Users, user groups and authorizations can be stored on a central server. If user administration cannot contact the server, an error message is displayed. If this is the case, you can only log on locally. More detailed information is available in your plant documentation. The operation of SIMATIC Logon differs as follows: â The simple user display is not supported â Users cannot be deleted â You cannot change your logout time â When changing the password, you must enter it twice for security reasons â The domain name is also indicated in the "User" field User groups and authorizations Project-specific user groups are created by the configuration engineer. The "Administrators" and "PLC User" groups are included in all projects by default. User groups are assigned authorizations. Authorization required for an operation is specifically defined for each individual object and function in the project. Users and passwords Each user is assigned to exactly one user group. The following persons are allowed to create users and assign them passwords: â The configuration engineer during configuration â The administrator on the HMI device â A user with user management authorization on the HMI device Irrespective of the user group, each user is allowed to change his own password. Logoff times A logoff time is specified in the system for each user. If the time between any two user actions, such as entering a value or changing screens, exceeds this logoff time, the user is automatically logged off. The user must then log on again to continue to operate objects assigned password protection. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 227 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security Backup and restore Note Backup and restore is not available to central user administration with SIMATIC Logon. The user data is encrypted and saved on the HMI device to protect it from loss due to power failure. The users, passwords, group assignments and logoff times set up on the HMI device can be backed up and restored. This prevents you having to enter all of the data again on another HMI device. NOTICE The currently valid user data is overwritten in the following cases: ďˇ Depending on the transfer settings, when the project is transferred again ďˇ Upon restore of a backed-up project ďˇ Upon import of the user administration via an operator control. More detailed information is available in your plant documentation. The retransferred or restored user data and passwords are valid with immediate effect. Number of characters for user, password and user view Number of characters 11.7.2 Length of user name, maximum 40 Length of password, minimum Length of password, maximum 24 Entries in user view, maximum 50 User View The user view is used to show user accounts configured on the HMI device. â If you are an administrator or a user with administrator rights, you can see all user accounts configured on the HMI device in the user view. â If you are a user without user management rights, you can only see your personal user account. The authorizations of a user after logging on depends on the user group to which the user belongs. More detailed information is available in your plant documentation. A simple or extended user view can be configured in the project. The two user views offer the same functions. The presentation of information differs. 228 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security Simple user view If you are not logged onto the HMI device, the only entry contained in the simple user view is "". If you are logged onto the HMI device, the simple user view only displays the user name and user group. Extended user view The extended user view displays information about the users. The extended user view contains the following columns: â Users â Password â Group â Logoff time Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 229 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security 11.7.3 User logon Use the logon dialog of the HMI device to log onto the security system. Enter your user name and password in the logon dialog. The logon dialog opens in the following cases: â You press an operator control with password protection â You press an operator control that was configured for displaying the logon dialog â Select the " " entry in the simple user view â Select a blank entry in the extended user view â The logon dialog will be automatically displayed when the project is started, depending on the configuration More detailed information is available in your plant documentation. Requirement â The logon dialog is open. Procedure Proceed as follows: 1. Enter the user name and password. Touch the corresponding text box. The alphanumerical screen keyboard is displayed. Note The user name is not case-sensitive. The password is case-sensitive. 2. Select "OK" to confirm logon. Result After successful logon to the security system, you can execute password-protected functions on the HMI device for which you have authorizations. If you enter a wrong password, an error message is displayed when an alarm window has been configured. 230 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security 11.7.4 User logoff Requirement â You have logged into the security system of the HMI device. Procedure You have the following options for logging off: â Press an operator control that is configured for logging off the security system. â If you do not operate a project and exceed the logoff time, your user account will be locked. Your user account will be automatically logged off if you enter an incorrect password. Result You are no longer logged onto the project. In order to use an operator control in the security system, you need to log on again. 11.7.5 Creating users You create a user with both the simple and enhanced user display. Requirement â A configured screen with user display is shown. â You have user management authorization or you are the administrator. Note The following characters are prohibited in passwords: ďˇ Blank ďˇ Special characters * ? . % / \ ' " Procedure â Creating a user in the simple user view Proceed as follows: 1. Touch the " " entry in the user view. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 231 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security The following dialog appears: 2. Enter the desired user name and password. Touch the corresponding text box. The alphanumerical screen keyboard is displayed. 3. Touch the "OK" button. The following dialog appears: 4. Assign the user to a group. In order to do so, open the "Group" drop down list box by means of the and to scroll in the drop down list box. button. Select 5. Touch the required entry in the drop down list box. The selected entry is then accepted as input. 6. Touch the text box "Logoff time". The screen keyboard is displayed. 7. Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no automatic logoff." 8. Touch the "OK" button to confirm your entries. Procedure â Creating a user in the extended user view Proceed as follows: 1. Double-click the desired field in the blank line of the user view. The screen keyboard is displayed. 2. Enter the respective user data in the field: â Assign the user to one of the groups from the drop down list box. â Enter a value between 0 and 60 for the logoff time in minutes. The value 0 stands for "no automatic logoff." Result 232 The new user is created. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security 11.7.6 Changing user data You have opened a screen with a user view. The data you are allowed to change depends on your authorization: Requirement â You are an administrator or a user with user management authorization. In these cases you are allowed to change the data for all the users on the HMI device in the user view: â User name â Group assignment â Password â Logoff time â You are a user without user management authorization. In this case you are only allowed to change your personal user data: â Password â Logoff time, if configured Note You can only change the logoff time and password for the "Admin" user. You can only change the logoff time for the "PLC_User". This user is used for logging on via the PLC Procedure The procedure applies to simple and extended user view alike. Proceed as follows: 1. In the user view, touch the user whose user data you want to change 2. When entering the data, use exactly the same procedure as for creating a user Result The user data for the user is changed. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 233 PRELIMINARY II 1.7.2010 Operating a project 11.7 Project security 11.7.7 Deleting users Requirement â You have opened a screen with a user view. â You are an administrator or you have permission for user management. Procedure Note The "Admin" and "PLC_User" users exist by default. You cannot delete these users. 1. Delete the entered user name. Result The affected user can no longer use the operator controls with permission. 234 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Operating a project 11.8 Error cases in the project operation 11.8 Error cases in the project operation During fail-safe operation, you must be aware that the following error cases may arise: â Leaving an HMI device logged onto a machine CAUTION Shutdown possible If the HMI device is in a state where it is constantly ready for operation, the main rechargeable battery will lose its charge. A discharged main rechargeable battery causes communication failure. The F-CPU initiates a shutdown. If you do not need the HMI device: ďˇ Log off the HMI device from the machine. ďˇ Close the active project. ďˇ Switch off the HMI device or place it in the docking station. â Internal error If an internal error occurs on the HMI device, the "SAFE" and "RNG" LEDs go out. and the project is terminated immediately. The HMI device displays the error code message â see section "Diagnostics (Page 204)". Safety functions are no longer available. Contact the SIEMENS hotline. â Communication error If a communication error occurs on the HMI device, the "SAFE" LED goes out. Safety functions are no longer available. The following situations can occur with communication errors: â When the HMI device is logged onto a machine: The F-CPU initiates a shutdown. The F-CPU stops the plant unit associated with the machine. â When the HMI device is not logged onto a machine: The F-CPU initiates a global rampdown. â If communication is reestablished within 60 seconds: The EMERGENCY STOP button is enabled again. The "SAFE" LED lights up again. Acknowledge the communication error. The "RNG" LED lights up when the HMI device is logged onto a machine. â If communication remains interrupted for more than 60 seconds: The HMI device terminates the project. The "RNG" LED lights up when the HMI device is logged on to a machine. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 235 PRELIMINARY II 1.7.2010 Operating a project 11.9 Closing the project 11.9 Closing the project The procedure for closing the active project is identical to the procedure for removing the HMI device. See also Removing the HMI device (Page 213) 236 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Service and maintenance 12.1 12 Maintenance and care Read sections "Safety-related operator controls (Page 88)" and "Safety instructions (Page 72)" for information on service and maintenance. Scope of maintenance The HMI device is designed for maintenance-free operation. Remember to include accessories and peripheral equipment in the maintenance. The scope of maintenance includes: Function test Perform an annual function test for the enabling button and EMERGENCY STOP button. Proceed as follows: 1. Switch on the HMI device. 2. Press both enabling buttons when the "Test Enabling Button" dialog is shown. 3. Press the EMERGENCY STOP button. Storing the main rechargeable battery A lithium-ion rechargeable battery loses more than 50% of its charge capacity within three years . Store rechargeable batteries at 40 to 60% of their capacity to ensure optimal service life. Manufacturers recommend storage at 15° C â which is optimal for aging and self-discharge. Charge the battery every six months to 40 to 60% of its charge capacity. Scope of maintenance The scope of maintenance includes: â Cleaning the touch screen â Cleaning the membrane keypad Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 237 PRELIMINARY II 1.7.2010 Service and maintenance 12.2 Replacing the rechargeable buffer battery Procedure CAUTION Damage possible The use of compressed air, steam cleaners or aggressive solutions or scouring agents will damage the HMI device. Use a cleaning cloth dampened with a cleaning agent to clean the equipment. Only use water with a little liquid soap or a screen cleaning solution. Proceed as follows: 1. Switch off the HMI device. 2. Spray the cleaning solution onto a cleaning cloth. Do not spray directly onto the HMI device. 3. Clean the HMI device. When cleaning the display, wipe inwards from the edge of screen. 12.2 Replacing the rechargeable buffer battery The capacity of the rechargeable buffer battery is reduced by age. After about five years, the rechargeable buffer battery needs to be replaced. This section describes how to replace the rechargeable buffer battery. Procedure Note Read sections "Safety instructions (Page 66)", "Opening and closing the terminal compartment (Page 67)" and "Safety instructions (Page 72)". &RQQHFWRUV &RQQHFWLQJFDEOH (QFORVXUH 5HFKDUJHDEOHEXIIHUEDWWHU\ 238 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Service and maintenance 12.3 Spare parts and repairs Proceed as follows: 1. Remove the enclosure. The enclosure is not needed for installation. 2. Open the connection compartment. 3. Pull out the connector. 4. Slide the rechargeable buffer battery out of the guide and put it down. 5. Insert the new rechargeable buffer battery, as shown in the following illustration. 5HFKDUJHDEOHEXIIHUEDWWHU\ 3OXJDQGVRFNHW &RQQHFWLQJFDEOH 3ULQWHGFLUFXLWERDUG 6. Connect the plug. 7. Position the cable so that it cannot be pinched when you close the connection compartment. 8. Close the connection compartment. 12.3 Spare parts and repairs If the unit needs to be repaired, ship the HMI device to the Return Center in FĂźrth. The address is: Siemens AG Industry Sector Returns Center Siemensstr. 2 90766 FĂźrth Germany You can find more detailed information on the Internet at Spare parts and repairs (http://support.automation.siemens.com/WW/view/en/16611927). Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 239 PRELIMINARY II 1.7.2010 Service and maintenance 12.3 Spare parts and repairs 240 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 13 Technical specifications 13.1 Dimension drawings 13.1.1 Wireless Teach Pendant F IWLAN s s s $OOGLPHQVLRQVLQPP s Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 241 PRELIMINARY II 1.7.2010 Technical specifications 13.1 Dimension drawings 13.1.2 Docking station $OOGLPHQVLRQVLQPP r 242 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Technical specifications 13.1 Dimension drawings 13.1.3 RFID tag Fixing pocket $OOGLPHQVLRQVLQPP Spacer $OOH$QJDEHQLQPP You can additional illustrations on the Internet at Image database (http://www.automation.siemens.com/bilddb/index.aspx?att14s=35). Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 243 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications 13.2 Specifications 13.2.1 Wireless Teach Pendant F IWLAN V2 General information Weight with battery, without packaging Approx. 2 kg Drop height with main rechargeable battery, max. 0.5 m Buffer time of internal clock with battery inserted Approx. 4 days Type Color TFT LC display Display area, active 132.5 mm x 99.5 mm Display Resolution 640 x 480 pixels Colors, displayable 65536 colors Brightness control Yes Backlighting Half Brightness Life Time, typical CCFL 50000 h Pixel error class according to DIN EN ISO 13406- II Input unit Touch screen Analog, resistive Membrane keyboard Rotary switch 1, with 2 positions Illuminated pushbutton EMERGENCY STOP button Enabling button Application memory 6 MB SD memory card 2 GB Memory 244 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications Ports 2 x USB ďˇ ďˇ USB host; conforms to USB standard 1.1 Supports low-speed and full-speed USB devices. Current load per port, max. 100 mA 1 x WLAN For PROFINET WLAN 1 x RJ45 For LAN WLAN antenna Antenna type Dual port patch antenna Polarization Vertical and horizontal Antenna gain in principle ray direction, max. 2 dBi Impedance 50 Ί Fail-safe operation Note The safety characteristics in the specifications apply for a proof-test interval of 10 years and a mean repair time of 8 hours. In accordance with IEC 61508 Hardware architecture Redundant 1oo2 Hardware error tolerance Safe failure fraction 99.5 % Diagnostic test interval 10 ms Request rate High demand mode High demand (PFH â probability of a dangerous failure per hour) 8.60eâ11hâ1 Safety class, maximum achievable (SIL) Useful life 10 years According to ISO 13849-1 Mean time to failure (MTTFd) 1516 years Meantime to Restoration (MTTR) 8h Diagnostic coverage 99 % Performance level Safety category Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 245 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications Other safety-related characteristic values Acknowledgement time 13.2.2 40 ms Response time with no fault, max. 25 ms Discrepancy time â EMERGENCY STOP 500 ms Discrepancy time â enabling button ďˇ "Enabling" position ďˇ "Panic" position 2 sec 1 sec Interface description USB The figure below shows the pin assignment of the USB interface. Pin Assignment +5 VDC, out (max. 100 mA) USB-DN USB-DP GND RJ45 The figure below shows the pin assignment of the RJ45 interface. 246 Pin Assignment TD+ TDâ RD+ n. c. n. c. RDâ ICD+ ICDâ Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications WLAN Operation of a wireless interface in the frequency bands 2.4 GHz and 5 GHz. The wireless interface is compatible with the following standards: â IEEE 802.11a â IEEE 802.11h â IEEE 802.11b â IEEE 802.11g Receiver sensitivity WLAN standard Data transfer rate Receiver sensitivity IEEE 802.11a/h 54 Mbps -74 dBm 48 Mbps -75 dBm 36 Mbps -80 dBm 24 Mbps -83 dBm 18 Mbps -86 dBm 12 Mbps -88 dBm 9 Mbps -89 dBm 6 Mbps -90 dBm 54 Mbps -76 dBm 48 Mbps -77 dBm 36 Mbps -82 dBm 24 Mbps -85 dBm 18 Mbps -88 dBm 12 Mbps -91 dBm 9 Mbps -92 dBm 6 Mbps -93 dBm 11 Mbps -90 dBm 5.5 Mbps -92 dBm 2 Mbps -94 dBm 1 Mbps -98 dBm IEEE 802.11g IEEE 802.11b Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 247 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications Transmission power WLAN standard Data transfer rate Receiver sensitivity IEEE 802.11a/h (5.18 âź 5.7 GHz) 54 Mbps 13.5 dBm 48 Mbps 15 dBm 36 Mbps 16 dBm 6-24 Mbps 17 dBm 54 Mbps 11.5 dBm 48 Mbps 13 dBm 36 Mbps 14 dBm 6-24 Mbps 15 dBm 54 Mbps 16 dBm 48 Mbps 17 dBm 36 Mbps 17 dBm 6-24 Mbps 17 dBm 11 Mbps 20 dBm 5.5 Mbps 20 dBm 2 Mbps 20 dBm 1 Mbps 20 dBm IEEE 802.11a/h (4.92 âź 5.16 GHz) (5.745 âź 5.825 GHz) IEEE 802.11g (2.412 âź 2.484 GHz) IEEE 802.11b 13.2.3 Rechargeable batteries Main rechargeable battery Type Lithium ion accumulator Operation time in normal mode Approx. 4 h Operation time in stand-by mode Approx. 15 days Charging cycles 500 Charging time Approx. 4 h 1) Rechargeable buffer battery Type Bridging time 20 sec Charging cycles 500 1) 248 Lithium ion accumulator See section Charging the main rechargeable battery (Page 75), Maintenance and care (Page 237) Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications 13.2.4 Docking station Weight without packing Approx. 1.1 kg Power supply 13.2.5 Nominal voltage +24 VDC via external power supply Transients, maximum permitted 35 V (500 ms) Time between two transients, minimum 50 s Power consumption with Wireless Teach Pendant F IWLAN ďˇ Typical ďˇ Constant current, maximum ďˇ Power on current surge I2t ďˇ ďˇ ďˇ Fuse, internal Electronic Approx. 1.5 A Approx. 1.8 A Approx. 1.7 A2s Charger Weight without packing Approx. 1.1 kg Nominal voltage +24 VDC via external power supply unit Power supply Transients, maximum permitted 35 V (500 ms) Time between two transients, minimum 50 sec Power consumption with Wireless Teach Pendant F IWLAN ďˇ Typical ďˇ Constant current, maximum ďˇ Power on current surge I2t ďˇ ďˇ ďˇ Fuse, internal Electronic Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Approx. 1.5 A Approx. 1.8 A Approx. 1.7 A2s 249 PRELIMINARY II 1.7.2010 Technical specifications 13.2 Specifications 13.2.6 RFID tag Memory capacity 128 bytes Memory technology EEPROM Protocol ISO 15693 Data retention, at +40° C 10 years MTBF, at + 40° C 2 x 106 hours Read cycles Unlimited Write cycles, typical 200000 Write cycles, minimal 100000 Multitag-capable Yes Energy supply, inductive Energy transfer (without battery) Degree of protection in accordance with EN 60529 IP68 Mechanical design Material PC Color White/petrol Dimensions (L x W x H) in mm 85.6 x 54 x 0.9 Ambient temperature 13.2.7 Operation â25° C to +80° C Storage/transport â25° C to +80° C F-FBs and configuration F-FBs required in safety program F_FB_MP 1 per Wireless Teach Pendant F IWLAN, maximum 126 F_FB_RNG_4 1 per effective range, for which up to 4 HMI devices have logon permission F_FB_RNG_16 1 per effective range, for which up to 16 HMI devices have logon permission DB_STATES Configuration Number of effective ranges in a project, max. 250 127 Number of RFID tags in a project, max. 127 Number of RDIF tags per effective range, max. 127 Number of HMI devices authorized for logon per effective range, max. ďˇ ďˇ With F_FB_RNG_4: 4 With F_FB_RNG_16: 16 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.1 ESD guideline What does ESD mean? An electronic module is equipped with highly integrated electronic components. Due to their design, electronic components are highly sensitive to overvoltage and thus to the discharge of static electricity. Such electronic components are labeled as electrostatic sensitive devices (ESD). The following abbreviations are commonly used for electrostatic sensitive devices: â ESD â Electrostatic Sensitive Device â ESD â Electrostatic Sensitive Device (internationally recognized term) Electrostatic charge CAUTION Electrostatic charge ESDs may be destroyed by voltages far below the level perceived by human beings. If you are not discharged electrostatically, the voltage that you transfer when touching a component or the contact points of a module can already cause damage. The damage to an ESD caused by overvoltage is usually not recognized immediately. The damage only becomes apparent after a long period of operation. Discharge any electrostatic charge of your body before you touch the ESD. Anyone who is not connected conductively to their surroundings is subject to electrostatic charge. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 251 PRELIMINARY II 1.7.2010 Appendix A.1 ESD guideline 9ROWDJH The following diagram shows the maximum voltage values to which a person can be charged electrostatically. The values depend on the material and humidity. The shown values are in conformity with the specifications of EN 61000-4-2. >N9@ >@ 5HODWLYHKXPLGLW\ â ⥠⢠Synthetic materials Wool Antistatic materials such as wood or concrete Protective measures against discharge of static electricity CAUTION Grounding measures There is no equipotential bonding without grounding. An electrostatic charge is not discharged and may damage the ESD. When working with electrostatic sensitive devices, make sure that the person and the workplace are properly grounded. Note the following: â Only touch the ESD if it is absolutely necessary. â When you touch ESD modules, avoid touching the pins or the PCB tracks. This precaution reduces the risk of damaging an ESD. â Discharge electrostatic electricity from your body if you are performing measurements on an ESD. To do so, touch a grounded metal object before you carry out the measurement. â Always use grounded measuring instruments. 252 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2 Typical operating procedures and potential fault scenarios A.2.1 Overview This section describes typical application cases for the HMI device. The following states are graphically represented in the application cases. â LED status â Operability of the EMERGENCY STOP button and enabling buttons The used icons have the following meaning: â LED display Icon 6$)( Meaning 3:5 &20 51* %$7 Status of the LEDs that are displayed on the HMI device during the described situation. All LEDs are on. â EMERGENCY STOP button Icon Meaning Pressing the EMERGENCY STOP button triggers an EMERGENCY STOP. Pressing the EMERGENCY STOP has no effect. â Enabling button Icon Meaning The operator can release movements of the assigned machine with the enabling buttons. Pressing the enabling buttons has no effect. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 253 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.2 Switch on the HMI device. Requirement â The HMI device is switched off. â The rechargeable battery is fully charged. LED display 6$)( Procedure EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 1. Switch on the HMI device using the ON/OFF button. Communication via WLAN starts up. While the WLAN connection is being established the "COM" LED flashes. Result â WLAN communication is established. â The HMI device displays the Windows CE Desktop with the Loader. LED display 6$)( 254 EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.3 Requirement Integrating the HMI device â The HMI device is switched on. â WLAN communication is established. â The HMI device shows the Windows CE Desktop with the Loader. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Procedure 1. Start the project. â PROFIsafe communication is established. â The "Establishment of safety connection" dialog is shown with the following icon. â The HMI device is integrated in the safety program of the F CPU. â The "Test enabling button" dialog opens with the following icon. 2. Press both enabling buttons when prompted until the "Panic" switch position is reached. Result â Both enabling buttons have been tested in the "Enable" and "Panic" switch positions. â The project start screen appears. LED display 6$)( EMERGENCY STOP button 3:5 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 &20 51* Enabling button %$7 255 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.4 Communication error for the integrated HMI device Requirement â The HMI device is integrated in the safety program of the F-CPU. â The HMI device is not logged onto a machine. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Procedure 1. You are leaving the WLAN range with the HMI device. The "COM" LED flashes. The F CPU detects a communication error and initiates a global rampdown. The "SAFE" LED goes out. The user is informed that no safety functions are available. The "No safety connection" dialog is shown with the following symbol. 2. You will return to the WLAN range within 60 seconds. The "Acknowledgment of communication error" dialog opens with the following symbol. 3. Acknowledge the communication error. See Result 1. 4. You remain outside the WLAN. The "Confirm removal" dialog will be displayed after 60 seconds with the following symbol. See Result 2. Result 1 â Return to the WLAN range â The "Global rampdown" signal is canceled. PROFIsafe communication is again possible. â The HMI device is fully operable. 256 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Result 2 â No return to the WLAN range â The project will be closed immediately if you confirm the Confirm removal dialog within 60 seconds. â The active project will be closed automatically if you do not confirm the "Confirm removal" dialog within 60 seconds. â The Windows CE desktop with the loader is shown on the display. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Wireless network communication is reestablished if you later return to the WLAN range with the HMI device. Start the project again. Acknowledge the communication error in the "Acknowledgment of communication error" dialog with the following symbol. The "Global rampdown" signal is cancelled when you acknowledge the communication error. Test the enabling buttons when the "Test Enabling Button" dialog is shown with the following symbol. The HMI device is integrated again. Note Users can react to a fault on the HMI device by resetting the associated F_FB_MP to the "original state" using input "S7_MP_RES." This action sets the relevant HMI device to the "removed" state and the global rampdown signal is canceled. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 257 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.5 Discrepancy error during enabling The enabling button is two-channel. Both contacts must be closed at the same time to reach the enabled state. A discrepancy error is generated if one of the contacts is open while the other is closed. The following fault scenarios can occur: â The enabling button is askew â The enabling button is defective. A.2.5.1 The enabling button is askew Requirement The HMI device is integrated. â The HMI device is not logged onto a machine. LED display 6$)( 3:5 &20 51* EMERGENCY STOP button Enabling button EMERGENCY STOP button Enabling button %$7 â The HMI device is logged on to a machine. LED display 6$)( 3:5 &20 51* %$7 Procedure 1. Press the enabling button. If you press the edge of an enabling button, the pressure point for the contacts is not centered. The signal is therefore transmitted only through one of the two contacts. The controller detects a discrepancy. Result The enabled state is withdrawn when a discrepancy is detected. The "Discrepancy error enabling button" dialog opens with the following symbol when the discrepancy time expires. 258 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios The dialog stays open until this discrepancy is corrected. Additional information on discrepancy time is available in "Wireless Teach Pendant F IWLAN V2 (Page 244)", section "Fail-safe operation". Enabling is made possible by pressing the enabling button again from the zero position. â The HMI device is integrated but not logged onto a machine. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 â The HMI device is integrated and logged onto a machine: LED display 6$)( A.2.5.2 EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 The enabling button is defective. Requirement â The HMI device is integrated and logged onto a machine. â An enabling button is defective and not pressed. Distinguish between the two scenarios: â Scenario 1 One channel of the enabling button is opened permanently. â Scenario 2 One channel of the enabling button is closed permanently. Discrepancy is detected in this situation. The "Discrepancy error enabling button" dialog is displayed with the following symbol. LED display 6$)( EMERGENCY STOP button 3:5 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 &20 51* Enabling button %$7 259 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios Procedure 1. Press the enabling button. Result â Scenario 1 â The enabled state is not activated. The "Discrepancy error enabling button" dialog opens with the following symbol when the discrepancy time expires. The dialog stays open until the enabling button is released. This step cancels the discrepancy. A discrepancy error is displayed again when the operator presses the enabling button once again . â The device must be repaired. See section "Spare parts and repairs (Page 239)". â Press the second working enabling button to remove the HMI device. Result â Scenario 2 â The "Discrepancy error enabling button" dialog is closed and the discrepancy is cleared. The enable signal remains in deactivated state. The "Discrepancy error enabling button" dialog is displayed with the following symbol when the enabling button is released. â The device must be repaired. See section "Spare parts and repairs (Page 239)". A.2.6 Logging onto a machine Requirement â You have the HMI device at a distance of no more than 5 cm in front of an RFID tag. â The "Effective range name (RFID)" object is shown in white labeled "Scan". 6FDQ LED display 6$)( 260 EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios Procedure 1. Touch the "Effective range name (RFID)" object labeled "Scan". The HMI device searches for RFID tags, the "Effective range name (RFID)" object is shown in yellow labeled "Scanning". 6FDQQLQJ If the "Effective range name (RFID)" object is configured with password protection, enter a valid user name and a valid password. The "Effective range logon" dialog opens with the following symbol. 2. Read the effective range ID from the RFID tag. 3. Enter the effective range ID. 4. Click "Yes". The dialog closes. The "Confirmation of logon" dialog is displayed with the following symbol. 5. Confirm the logon to the RFID tag with the enabling button. Result â You have logged on the HMI device to the machine via the RFID tag. â The "Effective range name (RFID)" operator control is shown in green and labeled with the name of the effective range. The following figure shows the "Effective range name (RFID)" object after logon to an effective range with the name "Robot 1". 5RERW LED display 6$)( EMERGENCY STOP button 3:5 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 &20 51* Enabling button %$7 261 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.7 Leaving a protection zone without logging off Requirement â A security system is installed for the protection zone, for example, a photoelectric sensor or a contact pressure mat. â The HMI device has been logged on to a machine, such as "Robot 1", via an RFID tag. 5RERW LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Procedure 1. You leave the protection zone with the HMI device through the security system. The HMI device initiates a local rampdown. The "Forced logoff" dialog opens with the following symbol. 2. Close the "Forced logoff" dialog with "OK". Result The HMI device is logged off the machine. The machine is free again for logon. LED display 6$)( 262 EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.8 Communication errors with logged on HMI device Starting situation The HMI device is logged on to a machine. 5DQJHQDPH LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Fault A communication error occurs. The F-CPU initiates a shutdown and stops the machine. The "SAFE" and "RNG" LEDs are off. The operator is alerted that no safety-related communication is available. Result â Communication will be reestablished within 60 seconds If the communication is reestablished within 60 seconds, the "Acknowledgment of communication error" dialog will open. If the operator acknowledges the communication error, the shutdown signal will be cancelled. PROFIsafe communication is again possible. The machine is free again for logon. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Result â Communication remains interrupted for more than 60 seconds If communication remains interrupted for more than 60 seconds, the project will be closed. The HMI device displays the Windows CE Desktop with the loader. Wireless network communication is reestablished if you later return to the WLAN range with the HMI device. Start the project again. Acknowledge the communication error in the "Acknowledgment of communication error" dialog. The shutdown signal is revoked. The HMI device is fully operable. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 263 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios LED display 6$)( A.2.9 Requirement EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Logging off the machine â The HMI device is logged on to a machine. â The "Effective range name" object will be displayed in green. 5DQJHQDPH LED display 6$)( Procedure EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 1. Confirm the "Effective range name (RFID)" object. The "Effective range logoff" dialog opens with the following symbol. 2. Confirm the logoff from the machine with the "Yes" button. Result â The HMI device is logged off the machine. â The "Effective range name (RFID)" object is shown in white labeled "Scan". 6FDQ LED display 6$)( 264 EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios A.2.10 Removing the HMI device Requirement â The project must be started. â The HMI device is integrated in the safety program of the F-CPU. â The HMI device is not logged onto a machine. LED display 6$)( EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Procedure 1. To close the project, use the operator control designed for this purpose. The "Start removal" dialog opens with the following symbol. 2. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol. 3. Press an enabling button within 60 seconds. NOTICE Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds. Result â Safety-related communication is terminated. â The HMI device has been successfully removed from the safety program of the F-CPU. â The project is closed. â The HMI device shows the Windows CE Desktop with the loader. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 265 PRELIMINARY II 1.7.2010 Appendix A.2 Typical operating procedures and potential fault scenarios LED display 6$)( A.2.11 Requirement EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 Switching off the HMI device â The project must be started. â The HMI device is integrated in the safety program of the F-CPU. LED display 6$)( Procedure EMERGENCY STOP button 3:5 &20 51* Enabling button %$7 1. Close all open dialogs. 2. Press and hold the "ON/OFF" button for at least 4 seconds. The "Start removal" dialog opens with the following symbol. 3. Use the "Yes" button to confirm the removal. The "Confirm removal" dialog opens with the following symbol. 4. Press an enabling button within 60 seconds. NOTICE Global rampdown A global rampdown will occur, if you do not confirm the "Confirm removal" dialog within 60 seconds with the enabling button. Press an enabling button within 60 seconds. 266 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application Result â Safety-related communication is terminated. â The HMI device has been successfully removed from the safety program of the F-CPU. â The project is closed. â The HMI device will be switched off. LED display 6$)( EMERGENCY STOP button 3:5 &20 A.3 Example of an application A.3.1 Configuration and operation 51* Enabling button %$7 This application example shows one possible application with the safety features of the HMI device. Note In this example, the HMI device is logged onto a machine via an RFID tag within a protection zone. The security system of the protection zone consists of a wire mesh fence with a door and a contact pressure mat. WARNING Read the documentation for S7 Distributed Safety An incorrectly configured or programmed system can result in death or serious injuries. We highly recommend that you read the information on S7 Distributed Safety in Programming and operation manual "S7 Distributed Safety - Configuring and Programming" (http://support.automation.siemens.com/WW/view/en/22099875) and in the online help of S7 Distributed Safety. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 267 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application Configuration example The following example configuration shows a robot cell which is secured by a wire mesh fence with a contact pressure mat. 352),VDIH $ $ $ ( â ⥠⢠⣠⤠⼠⌠⧠Access point Fail-safe controller Robot Signal lamp F-I/O, PROFINET IO device HMI device RFID tag Contact pressure mat The following signals are used: 268 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application Function Symbolic name Signal Explanation Contact pressure mat "Contact_Mats" I11.0 "0": Step on contact pressure mat "1": Do not step on contact mat "Key1" button, configured as direct key on the HMI device: E0.0 "0": Button not pressed "1": Button pressed Enabling button ENABLE (F_FB_RNG_4) "0": No enable "1": Enable Power ON-OFF robot "E_Stop_Robot" O11.0 "0": EMERGENCY STOP triggered. "1": Normal operation of plant. Actuator to robot O11.1 "0": The robot is not operated with Key1 and the enabling buttons "1": The robot is operated with Key1 and the enabling buttons Signal lamp O 11.2 "0": Robot is not in use; the signal lamp is off "1": Robot is in use; the signal lamp is on Flowchart The following flowchart shows the operation sequence in the example. Start Operation in the protection zone not possible Log on to the machine? No Yes Operation in the protection zone is possible Contact with pressure mat? No Yes Forced logoff Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 269 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application A.3.2 Configuring the controller and HMI device in STEP 7 This section describes the most important parameters you need to set in "HW Config" for the F-CPU and for the HMI device. WARNING Safety category Any changes to parameters may result in the loss of the safety category. Set the parameters as described. The parameters will contribute to meeting safety category 4 PL e/SIL 3. Requirement The software for fail-safe operation has been installed, see section "Required software (Page 22)". Procedure â Configuring CPU 317F-2 PN/DP Proceed as follows: 1. Create a STEP 7 project in SIMATIC Manager. 2. Open the "HW Config" hardware configuration and insert the desired F-CPU and a PROFINET connection, as shown in the following figure: 3. Open the settings by double-clicking the F-CPU in "HW Config". The table below shows the most important settings: 270 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application Setting Explanation This is where you set the cycle time for OB35. Note If the cycle time for OB35 is set lower than the PBIO update time, the message frame may be lost and the evaluation of the "E-STOP" output of F_FB_RNG_4 or F_FB_RNG_16 may be delayed. Set the cycle time of OB35 to a value higher than the PNIO update time. Assign a password for the safety program. Set the "CPU contains safety program" check box. This setting is required to generate all the necessary F-FBs for safe operation of the fail-safe modules during compilation of "HW Config" by STEP 7. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 271 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application Procedure â Configuring Wireless Teach Pendant F IWLAN Proceed as follows: 1. Insert the Wireless Teach Pendant F IWLAN in "HW Config" as shown in the following figure. 2. Open the properties dialog of the HMI device by double-clicking the "WTPfiwlan" icon. 3. Enter the device name of the HMI device in the properties dialog. 4. Open the properties dialog of the "WTPFailsafe_IO" module by double-clicking the "WTPFailsafe_IO" entry in the detailed view of the HMI device. 5. Change to the "PROFIsafe" tab. 272 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application The table below shows the most important settings: Setting Explanation Device name Here you assign a device name to the HMI device, which is unique in the local Ethernet network segment. This name must match the name defined in the Control Panel of the HMI device under "PROFINET" in the text box "Device name:". Additional information is available in the section: "Specifying the computer name of the HMI device (Page 145)". Inputs This is where you specify the start address of the inputs and the process image associated with this address area (PII). Outputs Here you specify the start address of the outputs and the process image associated with this address area (PIQ). F_Dest_Add PROFIsafe address of the Wireless Teach Pendant F IWLAN. This address must match the address on the HMI device. F_WD_Time Monitoring time in the fail-safe IO device. A valid current safety message frame must reach the F-CPU and be returned to the HMI device within the monitoring time period. This ensures that failures and errors are detected and appropriate responses are triggered to keep the fail-safe system in a safe state or transfer it to a safe state. The monitoring time selected must be long enough that message frame delays will be tolerated by the communication system, but also that the fault reaction function responds quickly enough in the event of a fault (e.g. interruption in the communication connection). Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 273 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application A.3.3 Safety program S7 Distributed Safety In the safety program of the S7-CPU, the operation sequence of the application example is implemented by the following programming: â Once the HMI device is logged on to a machine, the signal lamp and the "Override" mode are enabled. â In the protection zone, the operator can operate the robot with the "Key1" button and the enabling button. â If the operator leaves the protection zone over the contact pressure mat, the safety program responds as follows: â The signal lamp goes out. â "Override" mode is deactivated. â The HMI device is logged off the machine. â After an EMERGENCY STOP, the plant only restarts when the operator performs an acknowledgment. â Reactions specific to a plant are initiated when a rampdown or shutdown occurs. Safety program The safety program is structured as follows: )&DOO )& )% )B)%B03 ))% )B)%B51* ))% )B(6723 ))% Symbolic names The following symbolic names are used in the networks of the sample programs Symbolic name 274 Meaning F00256_WTPFailsafe_IO Fail-safe I/O DB of HMI device MP1_FB_S7_MP_RE Input which is set when a reset of the HMI device is performed from the F-CPU. MP1_FB_S7_ACK_ERR Input which is set when a communication error is acknowledged from the F-CPU. MP1_F_DATA_PII Word 1 of the PII of the HMI device MP1_F_RANGE_PII Word 2 of the PII of the HMI device MP1_F_DATA_PIQ Word 1 of the PIQ of the HMI device MP1_F_RANGE_PIQ Word 2 of the PIQ of the HMI device Interface_DB F-DB for the data transfer of user data F_DB_States F-DB for the transfer of data between the F_FB_MP of the HMI device and the F_FB_RNG_n of the effective range Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application F-CALL (FC 1) F-CALL (FC1) is the F-run-time group and is called from the cyclic interrupt OB (OB35). F-CALL (FC1) calls the F-program block (in this case: FB1). FB1 For reasons of program modularity, all other F-FBs are called from this FB. In FB 1, you have to call the F-FBs in the following order. 1. Network 1 '% )B)%B03 )B:73)DLOVDIHB,24%$' )B:73)DLOVDIHB,2$&.B5(4 03B)%B6B03B5( 03B)%B6B$&.B(55 (1 4%$' $&.B5(4 6B03B5(6 6B$&.B(55 $&.B5(, )B:73)DLOVDIHB,2ಯ$&.B5(, 03B'$7$B4 03B)B'$7$B3,4ಯ 03B)B51*B3,4 03B)B'$7$B3,, 03B'$7$ 03B51*B4 03B)B51*B3,, 03B51* ',$* )B'%B67$7(603BB6WDWXV 03B67$7 (12 ,QWHUIDFHB'%03B)%B',$* The controller uses this F-FB to monitor the PROFIsafe communication of the HMI device. The following diagnostics information is indicated at the "DIAG" output: â Status of the HMI device: integrated or removed â A communication error has occurred. â Communication error must be acknowledged Additional information is available in F_FB_MP (Page 171). Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 275 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application 2. Network 2 '% )B)%B51*B &RQWDFWB0DWV (GJHB &RQWDFWB 0DWV 1(* (1 0B%,7 ,QWHUIDFHB'% (5B51*B%86< 51*B,' 29(55,'( 03B)B'$7$B3,, 03B'$7$ 03B)B51*B3,, 03B51* 03B)B.(< 03B'$7$ (B6723 03B51* */2%B5' 03B)B.(< 03B'$7$ /2&B5' 03B51* 6+87'2:1 03B)B.(< 03B'$7$ (1$%/( ,QWHUIDFHB'% (5B(B6723 ,QWHUIDFHB'% (5B*/2%B5' ,QWHUIDFHB'% (5B/2&B5' ,QWHUIDFHB'% (5B6+87'2:1 ,QWHUIDFHB'% (5B(1$%/( 03B51* )B.(<6 03B)B.(< )B'%B67$7(6 03BB6WDWXV 03B67$7 51*B%86< 03B67$7 ',$* 03B67$7 03B67$7 ,QWHUIDFHB'% (5B51*B%86< ,QWHUIDFHB'% (5B)%B',$* (12 The activation of the "override" mode is controlled in this network. "OVERRIDE" is set as soon as the operator has logged the HMI device on to the machine via the RFID tag. (RNG_BUSY). "OVERRIDE" is reset by a negative edge on the contact pressure mat, in other words I11.0 = "0". This is the case when the operator leaves the protection zone. At the same time, F_FB_RNG monitors the signals "EMERGENCY STOP", "Global rampdown", "Local rampdown" and "Shutdown". They are scanned in networks 3 to 6. 276 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application 3. Network 3 '% )B(6723 ,QWHUIDFHB'%(5B(B6723 (1 (B6723 $&.B1(& $&. 7,0(B'(/ 4 4B'(/$< $&.B5(4 ',$* (12 (B6WRSB5RERW In network 3, the EMERGENCY STOP signal of the HMI device is monitored via F_ESTOP1 from the F-library of S7 Distributed Safety. F_ESTOP1 ensures that the plant is only able to restart following an EMERGENCY STOP after acknowledgment by the operator via the input "ACK". Note Read also the information on FB215 in the online help for F-FBs and in the manual "SIMATIC S7-Distributed Safety, Configuring and Programming", section "FB215 "F_ESTOP1:" Emergency STOP up to Stop Category 1". 4. Networks 4, 5 and 6 *OREDOB5DPSGRZQ ,QWHUIDFHB'% (5B*/2%B5' /RFDOB5DPSGRZQ ,QWHUIDFHB'% (5B/2&B5' 6KXWGRZQ ,QWHUIDFHB'% (5B6+87'2:1 In network 4, 5 and 6 the signals for a global and a local rampdown and shutdown are processed further. As the configuration of the monitored plant determines which responses have to occur following occurrence of a particular safety state, these networks are not explained in detail in this example. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 277 PRELIMINARY II 1.7.2010 Appendix A.3 Example of an application 5. Network 7 ( $ ,QWHUIDFHB'% (5B(QDEOH If the operator simultaneously presses the Key1 key and the enabling button, the robot is activated via the output Q11.1. 6. Network 8 $ ,QWHUIDFHB'% (5B51*B%86< If the "RNG_BUSY" signal is set in F_FB_RNG, output Q11.2 is used to control the signal lamp that indicates whether or not the machine is in use. 278 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.4 Safety-related messages A.4 Safety-related messages The following safety-related messages are displayed in fail-safe mode depending on the operating situation. In contrast to system alarms, no message window needs to be configured for safety-related messages. Dialog Reaction Establishment of safety connection "Yes" button No safe connection available. Reason: ďˇ Connection not yet completed ďˇ PROFIsafe address error ďˇ Internal configuration error ďˇ Communication error (timeout) ďˇ Communication error (CRC) ďˇ CPU in STOP ďˇ PROFIsafe CRC configuration error Situation The following is reported in the warning message depending on the operating situation: ďˇ Connection not yet completed The safe connection is not yet established after the project has been started. Wait until the connection has been established. The dialog is closed on completion. ďˇ A communication error occurred after the HMI device was successfully integrated. Correct the cause of the error described by "Reason". Should the Panel be switched off? Start removal "Yes" button "No" button The "Start removal" dialog opens in the following cases: ďˇ The operator has pressed the "ON/OFF" button for more than 4 seconds. ďˇ The operator has pressed the operator control for closing the project. Press an enabling button until the "Enable" switch position is reached. The removal starts, in other word, the user has pressed the "Yes" button in the "Start removal" dialog. The removal cannot be interrupted once it has started. Do you want to start the removal? Confirm removal Please confirm the removal with the enabling button. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 279 PRELIMINARY II 1.7.2010 Appendix A.4 Safety-related messages Dialog Reaction Situation Effective range logon "Yes" button "No" button The HMI device is located directly in front of an RFID tag and is not yet logged on to the corresponding machine. The operator has activated the "Scan" object to log on. Do you want to logon to the following effective range? 6FDQ Effective range < > Please enter the effective range ID: Effective range logoff "Yes" button "No" button The HMI device is logged on to a machine. The operator has activated the "Effective range name (RFID)" object to log off. Do you want to log off from the following effective range? Effective range < > Effective range logoff (shutdown) "Yes" button "No" button The HMI device is logged on to a machine. The operator has attempted to: ďˇ Shut down the HMI device. ďˇ Close the project with the corresponding operator control. The Panel cannot be switched off. You first have to log off from the effective range. Do you want to logoff from the following effective range? Effective range < > Acknowledgment of communication error A safe connection is possible again. Please confirm the communication error. 280 "OK" button Communication was recovered after a short communication error. The operator must confirm this state. Causes: ďˇ The operator has briefly left the WLAN range and then returned. ďˇ PROFIsafe communication was briefly interrupted. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.4 Safety-related messages Dialog Reaction Situation Forced logoff "OK" button The operator has left the protection zone with a logged-on HMI device via the safety system. "OK" button The remaining charge of the main rechargeable battery is less than 20%. You are automatically logged off from the effective range. A local rampdown has been triggered! Confirm the logoff from the effective range. Low battery alarm Battery charge is less than 20 percent. Test enabling button An additional system alarm is output after the charge of the main rechargeable battery has dropped to less than 6%. Press both enabling The operator has started the project. buttons until the Perform a function test for the enabling "Panic" switch button. position is reached. Both enabling buttons must be tested to ensure they are operational. Fully press both enabling buttons until the panic position is reached. Error during effective range logon Error during effective range logon. The enabling button remains deactivated. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 "OK" button An error occurred during logon of the HMI device to a machine. The operator cannot use the enable switches to control the production process. Possible causes: ďˇ You are already logged on to the machine with your HMI device or the logon is currently in progress. ďˇ Another HMI device is already logged on to the machine. ďˇ RFID tag is defective. ďˇ RFID module in the HMI device is defective. ďˇ No ID has been assigned to the RFID tag. ďˇ The operator has entered an incorrect RFID tag ID for the logon. ďˇ F_FB_RNG missing in the STEP7 configuration. ďˇ F_FB_RNG is wired incorrectly in STEP7. 281 PRELIMINARY II 1.7.2010 Appendix A.4 Safety-related messages Dialog Reaction Situation Enabling switch discrepancy error Release both enabling buttons. The HMI device detects a discrepancy at one of the two enabling buttons in switch position "Enable". Please release the enabling button. See also Communication error for the integrated HMI device (Page 256) 282 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms A.5 System alarms Introduction System alarms on the HMI device provide information about internal states of the HMI device and PLC. The following overview shows the causes of system alarms and how to eliminate the cause of error. Some of the system alarms described in this section are relevant to individual HMI devices based on their range of features. Note System alarms are only indicated if an alarm window was configured. System alarms are output in the language currently set on your HMI device. System alarm parameters System alarms may contain encrypted parameters which are relevant to troubleshooting because they provide a reference to the source code of the runtime software. These parameters are output after the text "Error code:" Displaying the "System alarms" editor You can find the text content of the system alarm in WinCC flexible. The "System alarms" editor is not displayed by default in WinCC flexible. 1. Enable the "System alarms" editor under "Options > Setting... > Workbench > Settings for Project Window" with "Display all entries". 2. Select the "System alarms" editor under "Alarms" in the project view. The system alarms are sorted numerically in the "System alarms" editor. Configuring events for system alarms You can configure the "Incoming" event for the following system alarm in the "System alarms" editor. System alarms 10000 ďˇ 10000 to 10006 150000 ďˇ 150000 ďˇ 150001 230300 ďˇ 230300 to 230308 20000 ďˇ 20000 to 20015 160000 ďˇ 160000 ďˇ 160001 ďˇ 160010 to 160014 240000 ďˇ 240000 to 240005 30000 ďˇ 30010 to 20012 170000 ďˇ 170000 to 170004 ďˇ 170007 250000 ďˇ 250000 to 250003 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 283 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms System alarms 284 40000 ďˇ 40010 ďˇ 40011 180000 ďˇ 180000 to 180002 260000 ďˇ 260000 to 260009 ďˇ 260012 to 260014 ďˇ 260028 ďˇ 260030 ďˇ 260033 to 260045 50000 ďˇ 50000 ďˇ 50001 190000 ďˇ 190000 to 190002 ďˇ 190004 to 190013 270000 ďˇ 270000 to 270003 60000 ďˇ 60010 to 60011 190100 ďˇ 190100 to 190102 280000 ďˇ 280000 to 280004 70000 ďˇ 70010 to 70044 200000 ďˇ 200000 to 200005 290000 ďˇ 290000 to 290008 ďˇ 290010 to 290014 ďˇ 290020 to 290027 ďˇ 290040 to 290042 ďˇ 290044 ďˇ 290050 to 290065 ďˇ 290070 to 290073 ďˇ 290075 80000 ďˇ 80001 to 80035 ďˇ 80044 to 80050 200100 ďˇ 200100 to 200105 300000 ďˇ 300000 ďˇ 300001 90000 ďˇ 90024 to 90026 ďˇ 90029 to 90033 ďˇ 90040 ďˇ 90041 ďˇ 90044 210000 ďˇ 210000 to 210006 310000 ďˇ 310000 ďˇ 310001 110000 ďˇ 110000 to 110006 220000 ďˇ 220000 to 220008 600000 ďˇ 600000 120000 ďˇ 120000 to 120002 230000 ďˇ 230000 ďˇ 230002 ďˇ 200003 ďˇ 200005 620000 ďˇ 620000 130000 ďˇ 130000 to 130012 230100 ďˇ 230100 140000 ďˇ 140000 to 140020 230200 ďˇ 230200 to 230203 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 10000 - Printer alarms Number Effect/cause Remedy 10000 The print job could not be started or was canceled due to an unknown error. Faulty printer setup. Or: No authorization is available for accessing the network printer. Power supply failure during data transfer. Check the printer settings, cable connections and the power supply. Set up the printer once again. Obtain a network printer authorization. If the error persists, contact the Hotline! 10001 No printer is installed or a default printer has not been set up. Install a printer and/or select it as the default printer. 10002 Overflow of the graphics buffer for printing. Up to two graphics are buffered. Allow sufficient intervals between successive print jobs. 10003 Graphics can now be buffered again. -- 10004 Overflow of the buffer for printing lines in text mode (e.g. alarms). Up to 1000 lines are buffered. Allow sufficient intervals between successive print jobs. 10005 Text lines can now be buffered again. -- 10006 The Windows printing system reports an error. Refer to the output text and the error ID to determine the possible causes. Nothing is printed or the print is faulty. Repeat the action if necessary. 20000 - Global script alarms Number Effect/causes Remedy 20010 An error has occurred in the specified script line. Execution of the script was therefore aborted. Note the system alarm that may have occurred prior to this. Select the specified script line in the configuration. Ensure that the tags used are of the allowed types. Check system functions for the correct number and types of parameters. 20011 An error has occurred in a script that was called by the specified script. Execution of the script was therefore aborted in the called script. Note the system alarm that may have occurred prior to this. In the configuration, select the script that has been called directly or indirectly by the specified script. Ensure that the tags used are of the allowed types. Check system functions for the correct number and types of parameters. 20012 The configuration data is inconsistent. The script could therefore not be generated. Recompile the configuration. 20013 The scripting component of WinCC flexible Runtime is Reinstall WinCC flexible Runtime on your PC. not correctly installed. Therefore, no scripts can be Rebuild your project with "Project > Compiler > executed. Generate" and transfer the project to the HMI device. 20014 The system function returns a value that is not written in any return tag. Select the specified script in the configuration. Check whether the script name has been assigned a value. 20015 Too many successive scripts have been triggered in short intervals. When more than 20 scripts are queued for processing, any subsequent scripts are rejected. In this case, the script indicated in the alarm is not executed. Find what is triggering the scripts. Extend the times, e.g. the polling time of the tags which trigger the scripts. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 285 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 30000 - Alarms for IFwSetValue: SetValue() Number Effect/causes Remedy 30010 The tag could not accept the function result, e.g. when it has exceeded the value range. Check the tag type of the system function parameter. 30011 A system function could not be executed because Check the parameter value and tag type of the invalid the function was assigned an invalid value or type in parameter. If a tag is used as a parameter, check its the parameter. value. 30012 A system function could not be executed because Check the parameter value and tag type of the invalid the function was assigned an invalid value or type in parameter. If a tag is used as a parameter, check its the parameter. value. 40000 - Linear scaling alarms Number Effect/causes Remedy 40010 The system function could not be executed since Check the parameter types in the configuration. the parameters could not be converted to a common tag type. 40011 The system function could not be executed since Check the parameter types in the configuration. the parameters could not be converted to a common tag type. 50000 - Data server alarms Number Effect/causes Remedy 50000 The HMI device is receiving data faster than it is -capable of processing. Therefore, no further data is accepted until all current data have been processed. Data exchange then resumes. 50001 Data exchange has been resumed. -- 60000 - Win32 function alarms Number Effect/causes Remedy 60000 This alarm is generated by the âDisplaySystemAlarmsâ function. The text to be displayed is transferred to the function as a parameter. -- 60010 The file could not be copied in the direction defined because one of the two files is currently open or the source/target path is not available. It is possible that the Windows user has no access rights to one of the two files. Restart the system function or check the paths of the source/target files. Using Windows NT/XP: The user running WinCC flexible Runtime must be granted access rights to the files. 60011 An attempt was made to copy a file to itself. It is possible that the Windows user has no access rights to one of the two files. Check the path of the source/target file. Using Windows NT/XP with NTFS: The user running WinCC flexible Runtime must be granted access rights to the files. 286 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 70000 - Win32 function alarms Number Effect/causes Remedy 70010 The application could not be started because it could not be found in the path specified or there is insufficient memory space. Check whether the application exists in the specified path or close other applications. 70011 The system time could not be modified. The error alarm only appears in connection with area pointer "Date/time PLC". Possible causes: ďˇ An invalid time was transferred in the job mailbox. ďˇ The Windows user has no right to modify the system time. Check the time which is to be set. Using Windows NT/XP: Users running WinCC flexible Runtime must be granted the right to modify the system time of the operating system. If the first parameter in the system alarm is displayed with the value 13, the second parameter indicates the byte containing the incorrect value. 70012 An error occurred when executing the function Close all programs currently running. "StopRuntime" with the option "Runtime and operating Then close Windows. system". Windows and WinCC flexible Runtime are not closed. One possible cause is that other programs cannot be closed. 70013 The system time could not be modified because an invalid value was entered. Incorrect separators may have been used. Check the time which is to be set. 70014 The system time could not be modified. Possible causes: ďˇ An invalid time was transferred. ďˇ The Windows user has no right to modify the system time. Check the time which is to be set. Using Windows NT/XP: Users running WinCC flexible Runtime must be granted the right to modify the system time of the operating system. Windows rejects the setting request. 70015 The system time could not be read because Windows rejects the reading function. -- 70016 An attempt was made to select a screen by means of a system function or job. This is not possible because the screen number specified does not exist. Or: A screen could not be generated due to insufficient system memory. Check the screen number in the function or job with the screen numbers configured. Assign the number to a screen if necessary. Or: The screen is blocked. Check the details for the screen call and whether the screen is blocked for specific users. Or: Screen call has not been executed correctly. 70017 Date/time is not read from the area pointer because the address set in the PLC is either not available or has not been set up. Change the address or set up the address in the PLC. 70018 Acknowledgment that the password list has been successfully imported. -- 70019 Acknowledgment that the password list has been successfully exported. -- 70020 Acknowledgment for activation of alarm reporting. -- 70021 Acknowledgment for deactivation of alarm reporting. -- 70022 Acknowledgment to starting the Import Password List action. -- Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 287 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 70023 Acknowledgment to starting the Export Password List action. -- 70024 The range of values of the tag was exceeded in the system function. No calculation of the system function. Check and correct the calculation. 70025 The range of values of the tag was exceeded in the system function. No calculation of the system function. Check and correct the calculation. 70026 No other screens are stored in the internal screen memory. No other screens can be selected. -- 70027 The backup of the RAM file system has been started. -- 70028 The files from the RAM have been copied in the Flash memory. The files from the RAM have been copied in the Flash memory. Following a restart, these saved files are copied back to the RAM file system. -- 70029 Backup of the RAM file system has failed. No backup copy of the RAM file system has been made. Check the settings in the "Control Panel > OP" dialog and save the RAM file system using the "Save Files" button in the "Persistent Storage" tab. 70030 The parameters configured for the system function are faulty. The connection to the new PLC was not established. Compare the parameters configured for the system function with the parameters configured for the PLCs and correct them as necessary. 70031 The PLC configured in the system function is not an S7 PLC. The connection to the new PLC was not established. Compare the S7 PLC name parameter configured for the system function with the parameters configured for the PLC and correct them as necessary. 70032 The object configured with this number in the tab order is not available in the selected screen. The screen changes but the focus is set to the first object. Check the number of the tab order and correct it if necessary. 70033 An e-mail cannot be sent because a TCP/IP connection to the SMTP server no longer exists. This system alarm is generated only at the first attempt. All subsequent unsuccessful attempts to send an e-mail will no longer generate a system alarm. The event is regenerated when an e-mail has been successfully sent in the meantime. The central e-mail component in WinCC flexible Runtime attempts, in regular intervals (1 minute), to establish the connection to the SMTP server and to send the remaining e-mails. Check the network connection to the SMTP server and re-establish it if necessary. 70034 Following a disruption, the TCP/IP connection to the SMTP server could be re-established. The queued e-mails are then sent. -- 70036 No SMTP server for sending e-mails is configured. An attempt to connect to an SMTP server has failed and it is not possible to send e-mails. WinCC flexible Runtime generates the system alarm after the first attempt to send an e-mail. Configure an SMTP server: 288 In WinCC flexible Engineering System using "Device settings > Device settings" In the Windows CE operating system using "Control Panel > Internet Settings > E-mail > SMTP Server" Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 70037 An e-mail cannot be sent for unknown reasons. The contents of the e-mail are lost. Check the e-mail parameters (recipient etc.). 70038 The SMTP server has rejected sending or forwarding an e-mail because the domain of the recipient is unknown to the server or because the SMTP server requires authentication. The contents of the e-mail are lost. Check the domain of the recipient address or disable the authentication on the SMTP server if possible. SMTP authentication is currently not used in WinCC flexible Runtime. 70039 The syntax of the e-mail address is incorrect or contains illegal characters. The contents of the e-mail are discarded. Check the e-mail address of the recipient. 70040 The syntax of the e-mail address is incorrect or contains illegal characters. -- 70041 The import of the user management was aborted due to an error. Nothing was imported. Check your user management or transfer it again to the panel. 70042 The range of values of the tag was exceeded while executing the system function. Check and correct the calculation. The system function was not calculated. 70043 The range of values of the tag was exceeded while executing the system function. Check and correct the calculation. The system function was not calculated. 70044 An error occurred while sending the e-mails. The emails were not sent. Check the SMTP settings and the error message in the system alarm. 70045 Cannot load a file required for encrypting the e-mail. Update the operating system and Runtime. 70046 The server does not support encryption. Select an SMTP server that supports encryption. 70047 The SSL versions of the HMI device and SMTP server Contact your network administrator or the operator of may not be compatible. the SMTP server. 80000 - Log alarms Number Effect/causes Remedy 80001 The log specified is filled to the size defined (in percent) and must be stored elsewhere. Store the file or table by executing a âmoveâ or âcopyâ function. 80002 A line is missing in the specified log. -- 80003 The copying process for logging was not successful. In this case, it is advisable to check any subsequent system alarms, too. -- 80006 Since logging is not possible, this causes a permanent loss of the functionality. In the case of databases, check whether the corresponding data source exists and start up the system again. 80009 A copying action has been completed successfully. -- 80010 Since the storage location was incorrectly entered in WinCC flexible, this causes a permanent loss of the functionality. Configure the storage location for the respective log again and restart the system when the full functionality is required. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 289 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 80012 Log entries are stored in a buffer. If the values are read to the buffer faster than they can be physically written (using a hard disk, for example), overloading may occur and recording is then stopped. Archive fewer values. Or: Increase the logging cycle. 80013 The overload status no longer applies. Archiving resumes the recording of all values. -- 80014 The same action was triggered twice in quick succession. Since the process is already in operation, the action is only carried out once. -- 80015 This system alarm is used to report DOS or database errors to the user. -- 80016 The logs are separated by the system function "CloseAllLogs" and the incoming entries exceed the defined buffer size. All entries in the buffer are deleted. Reconnect the logs. 80017 The number of incoming events cause a buffer overflow. This can be caused, for example, by several copying actions being activated at the same time. All copy jobs in the buffer are deleted. Stop the copy action. 80019 The connection between WinCC flexible and all logs -were closed, for example, after executing the system function "CloseAllLogs". Entries are written to the buffer and are then written to the logs when a connection is re-established. There is no connection to the storage location and the storage medium may be replaced, for example. 80020 The maximum number of simultaneously copy operations has been exceeded. Copying is not executed. Wait until the current copying actions have been completed, then restart the last copy action. 80021 An attempt was made to delete a log which is still busy with a copy action. Deletion has not been executed. Wait until the current copying actions have been completed, then restart the last action. 80022 An attempt was made to use the system function "StartSequenceLog" to start a sequence log for a log which is not configured as a sequence log. No sequence log file is created. In the project, check ďˇ if the "StartSequenceLog" system function was properly configured. ďˇ if the tag parameters are properly provided with data on the HMI device. 80023 An attempt was made to copy a log to itself. The log is not copied. In the project, check ďˇ if the "CopyLog" system function was properly configured. ďˇ if the tag parameters are properly provided with data on the HMI device. 80024 The "CopyLog" system function does not allow copying when the target log already contains data ("Mode" parameter). The log is not copied. Edit the "CopyLog" system function in the project if necessary. Before you initiate the system function, delete the destination log file. 80025 You have canceled the copy operation. Data written up to this point are retained. The destination log file (if configured) is not deleted. The cancellation is reported by an error entry $RT_ERR$ at the end of the destination log. -- 290 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 80026 This alarm is output after all logs are initialized. Values are written to the logs from then on. Prior to this, no entries are written to the logs, irrespective whether WinCC flexible Runtime is active or not. -- 80027 The internal Flash memory has been specified as the storage location for a log. This is not permissible. No values are written to this log and the log file is not created. Configure "Storage Card" or a network path as the storage location. 80028 The alarm returns a status report indicating that the logs are currently being initialized. No values are logged until the alarm 80026 is output. -- 80029 The number of logs specified in the alarm could not be initialized. The logs are initialized. The faulty log files are not available for logging jobs. Evaluate the additional system alarms related to this alarm. Check the configuration, the ODBC (Open Database Connectivity) and the specified drive. 80030 The structure of the existing log file does not match the expected structure. Logging is stopped for this log. Delete the existing log data manually, in advance. 80031 The log in CSV format is corrupted. The log cannot be used. Delete the faulty file. 80032 Logs can be assigned events. These are triggered as soon as the log is full. WinCC flexible Runtime is started and the log is already full, the event is not triggered. The log specified no longer logs data because it is full. Close WinCC flexible Runtime delete the log, then restart WinCC flexible Runtime. Or: Configure a button which contains the same actions as the event and press it. 80033 "System Defined" is set in the data log file as the data source name. This causes an error. No data is written to the database logs, whereas the logging to the CSV logs works. Reinstall SQL Sever 2005 Express. 80034 An error has occurred in the initialization of the logs. An attempt has been made to create the tables as a backup. This action was successful. A backup has been made of the tables of the corrupted log file and the cleared log was restarted. No action is necessary. However, it is recommended to save the backup files or delete them in order to make the space available again. 80035 An error has occurred in the initialization of the logs. An attempt has been made to create backups of the tables and this has failed. No logging or backup has been performed. It is recommended to save the backups or to delete them in order to release memory. 80044 The export of a log was interrupted because Runtime was closed or due to a power failure. It was detected that the export needed to be resume when Runtime restarted. The export resumes automatically. 80045 The export of a log was interrupted due to an error in the connection to the server or at the server itself. The export is repeated automatically. Check: ďˇ The connection to the server. ďˇ If the server is running. ďˇ If there is enough free space on the server. 80046 The destination file could not be written while exporting the log. Check whether there is enough space on the server and it you have permission to create the log file. 80047 The log could not be read while exporting it. Check whether the storage medium is correctly inserted. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 291 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 80049 The log could not be renamed while preparing to export it. The job can not be completed." Check whether the storage medium is correctly inserted and if there is sufficient space on the medium. 80050 The log which shall be exported is not closed. The job can not be completed. Make sure the "CloseAllLogs" system function is called before using the "ExportLog" system function. Change the configuration as required. 80051 The log to be copied contains an invalid checksum. The log was not copied. Select a log with a valid checksum. The selected log may have been manipulated. 80052 The log cannot be read. Check the log and the specified path. 80053 The closed log cannot be read. Open the log. 90000 - FDA alarms Number Effect/causes Remedy 90024 No operator actions can be logged due to lack of space on the storage medium for log. The operator action will therefore not be executed. Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90025 No user actions can be logged because of error state of the archive. Therefore the user action will not be executed. Check whether the storage medium is correctly inserted. 90026 No operator actions can be logged because the log is Before further operator actions are carried out, the log closed. The operator action will therefore not be must be opened again using the system function executed. "OpenAllLogs". Change the configuration as required. 90028 The password you entered is incorrect. 90029 Runtime was closed during ongoing operation Ensure that you are using the correct storage medium. (perhaps due to a power failure) or a storage medium in use is incompatible with Audit Trail. An Audit Trail is not suitable if it belongs to another project or has already been logged. 90030 Runtime was closed during ongoing operation (perhaps due to a power failure). -- 90031 Runtime was closed during ongoing operation (perhaps due to a power failure). -- 90032 Running out of space on the storage medium for log. Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90033 No more space on the storage medium for log. As of now, no more operator actions requiring logging will be executed. Make more space available by inserting an empty storage medium or swapping out the log files on the server using "ExportLog". 90039 You do not have the necessary authorization to perform this action. Adapt or upgrade your authorizations. 90040 Audit Trail is switched off because of a forced user action. Activate the "Audit Trail" again using the system function "StartLog". 90041 A user action which has to be logged has been executed without a logged on user. A user action requiring logging should only be possible with permission. Change the configuration by setting a required authorization for the input object. 90044 A user action which has to be confirmed was blocked, Repeat the user action if necessary. because there is another user action pending. 292 Enter the correct password. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 90048 The Audit Trail cannot be printed while data relevant to the audit is being logged. Stop logging using the system function "StopLogging". 90049 Access to required file is not possible. Check the network connection or the storage medium. 90056 The recipe was not imported because the file contains no checksum. Select a file with a checksum. The recipe was not imported because the file contains an invalid checksum. The selected file may have been manipulated. Select a file with a valid checksum. 90057 As an alternative, disable verification of the checksum by using the system function "ImportDataRecords". 110000 - Offline function alarms Number Effect/causes Remedy 110000 The operating mode was changed. "Offline" mode is now set. -- 110001 The operating mode was changed. "Online" mode is now set. -- 110002 The operating mode was not changed. Check the connection to the PLCs. Check whether the address area for the area pointer 88 âCoordination" in the PLC is available. 110003 The operating mode of the specified PLC was changed by the system function "SetConnectionMode". The operating mode is now "offline". -- 110004 The operating mode of the specified PLC has been changed by the system function "SetConnectionMode". The operating mode is now "online". -- 110005 An attempt was made to use the system function SetConnectionMode to switch the specified PLC to "online" mode, although the entire system is in "offline" mode. This changeover is not allowed. The PLC remains in "offline" mode. Switch the complete system to "online" mode, then execute the system function again. 110006 The content of the "project version" area pointer does Check the following: not match the user version configured in WinCC ďˇ The project ID entered on the PLC. flexible. WinCC flexible Runtime is therefore closed. ďˇ The project ID entered in WinCC flexible. 120000 - Trend alarms Number Effect/causes 120000 The trend is not displayed because you configured an Change the configuration. incorrect axis to the trend or an incorrect trend. 120001 The trend is not displayed because you configured an Change the configuration. incorrect axis to the trend or an incorrect trend. 120002 The trend is not displayed because the tag assigned attempts to access an invalid PLC address. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Remedy Check whether the data area for the tag exists in the PLC, the configured address is correct and the value range for the tag is correct. 293 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 130000 - System information alarms Number Effect/causes Remedy 130000 The action was not executed. Close all other programs. Delete files no longer required from the hard disk. 130001 The action was not executed. Delete files no longer required from the hard disk. 130002 The action was not executed. Close all other programs. Delete files no longer required from the hard disk. 130003 No data medium found. The operation is canceled. Check, for example, if ďˇ The correct data medium is being accessed ďˇ The data medium is inserted 130004 The data medium is write-protected. The operation is canceled. Check whether access has been made to the correct data carrier. Remove the write protection. 130005 The file is read only. The operation is canceled. Check whether access has been made to the correct file. Edit the file attributes if necessary. 130006 Access to file failed. The operation is canceled. Check, for example, if ďˇ The correct file is being accessed ďˇ The file exists ďˇ Another action is preventing simultaneous access to the file. 130007 The network connection is interrupted. Records cannot be saved or read over the network connection. Check the network connection and eliminate the cause of error. 130008 The storage card is not available. The specified data records cannot be saved to / read from the storage card. Insert the storage card. 130009 The specified folder does not exist on the storage card. Any files saved to this directory are not backed up when you switch off the HMI device. Insert the storage card. 130010 The maximum nesting depth can be exhausted when, Check the configuration. for example, a value change in a script results in the call of another script and the second script in turn has a value change that results in the call of yet a further script etc. The configured functionality is not supported. 130013 The storage card is not available. The specified data records cannot be saved to / read from the storage card. 294 Insert the storage card. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 140000 - Connection alarms chns7: Connection + device Number Effect/causes Remedy 140000 An online connection to the PLC is established. -- 140001 The online connection to the PLC was shut down. -- 140003 No tag updating or writing is executed. Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140004 No tag update or write operations are executed Verify the connection and check whether the PLC is because the access point or the module configuration switched on. is faulty. Check the access point or the module configuration (MPI, PPI, PROFIBUS) in the Control Panel with "Set PG/PC interface". Restart the system. 140005 No tag updating or writing is executed because the HMI device address is incorrect (possibly too high). Use a different HMI device address. Verify the connection and check whether the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140006 No tag updating or writing is executed because the baud rate is incorrect. Select a different baud rate in WinCC flexible (according to module, profile, communication peer, etc.). 140007 Tags are not updated or written because the bus profile is incorrect (see %1). The following parameters could not be written to the registry: 1: Tslot 2: Tqui 3: Tset 4: MinTsdr 5: MaxTsdr 6: Trdy 7: Tid1 8: Tid2 9: Gap Factor 10: Retry Limit Check the user-defined bus profile. Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140008 No tag updating or writing is executed because baud rate is incorrect. The following parameters could not be written to the registry: 0: General error 1: Wrong version 2: Profile cannot be written to the registry. 3: The subnet type cannot be written to the registry. 4: The target rotation time cannot be written to the registry. 5: Faulty highest address (HSA). Check the connection and if the PLC is switched on. Check the parameter definitions in the Control Panel using "Set PG/PC interface". Restart the system. 140009 Tags are not updated or written because the module for S7 communication was not found. Reinstall the module in the Control Panel using "Set PG/PC interface". Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 295 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 140010 No S7 communication partner found because the PLC is shut down. DP/T: The option âPG/PC is the only masterâ is not set in the Control Panel under âSet PG/PC interface.â Switch the PLC on. DP/T: If only one master is connected to the network, disable "PG/PC is the only master" in "Set PG/PC interface". If several masters are connected to the network, enable these. Do not change any settings, for this will cause bus errors. 140011 No tag updating or writing is executed because communication is down. Check the connection and that the communication partner is switched on. 140012 There is an initialization problem (e.g. when WinCC flexible Runtime was closed in Task Manager). Or: Another application (e.g.STEP7) with different bus parameters is active and the driver cannot be started with the new bus parameters (transmission rate, for example). Restart the HMI device. Or: Run WinCC flexible Runtime, then start your other applications. 140013 The MPI cable is disconnected and, thus, there is no power supply. Check the connections. 140014 The configured bus address is in already in use by another application. Edit the HMI device address in the PLC configuration. 140015 Wrong transmission rate Or: Faulty bus parameters (e.g. HSA) Or: OP address > HSA or: Wrong interrupt vector (interrupt does not arrive at the driver) Correct the relevant parameters. 140016 The hardware does not support the configured interrupt. Change the interrupt number. 140017 The set interrupt is in use by another driver. Change the interrupt number. 140018 The consistency check was disabled by SIMOTION Scout. Only a corresponding note appears. Enable the consistency check with SIMOTION Scout and once again download the project to the PLC. 140019 SIMOTION Scout is downloading a new project to the Wait until the end of the reconfiguration. PLC. Connection to the PLC is canceled. 140020 The version in the PLC and that of the project (FWX file) do not match. Connection to the PLC is canceled. The following remedies are available: Download the current version to the PLC using SIMOTION Scout. Regenerate the project using WinCC flexible ES, close WinCC flexible Runtime and restart with a new configuration. 296 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 150000 - Connection alarms chnAS511: Connection Number Effect/causes Remedy 150000 No more data is read or written. Possible causes: ďˇ The cable is defective. ďˇ The PLC does not respond, is defective, etc. ďˇ The wrong port is used for the connection. ďˇ System overload Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. 150001 Connection is up because the cause of the interruption has been eliminated. -- 160000 - Connection alarms IVar (WinLC) / OPC: Connection Number Effect/causes Remedy 160000 No more data is read or written. Possible causes: ďˇ The cable is defective. ďˇ The PLC does not respond, is defective, etc. ďˇ The wrong port is used for the connection. ďˇ System overload Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. 160001 Connection is up because the cause of the interruption has been eliminated. -- 160010 No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check access rights. 160011 No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check, for example, if ďˇ The server name is correct. ďˇ The computer name is correct. ďˇ The server is registered. 160012 No connection to the server because the server identification (CLS-ID) cannot be determined. Values cannot be read or written. Check, for example, if ďˇ The server name is correct. ďˇ The computer name is correct. ďˇ The server is registered. Note for advanced users: Interpret the value from HRESULT. 160013 The specified server was started as InProc server. This has not been released and may possibly lead to incorrect behavior because the server is running in the same process area as the WinCC flexible Runtime software. Configure the server as OutProc Server or Local Server. 160014 Only one OPC server project can be started on a PC/MP. An alarm is output when an attempt is made to start a second project. The second project has no OPC server functionality and cannot be located as an OPC server by external sources. Do not start a second project with OPC server functionality on the computer. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 297 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 170000 - S7 dialog alarms Number Effect/causes Remedy 170000 S7 diagnostics events are not indicated because it is not possible to log on to the S7 diagnostics functions at this device. The service is not supported. -- 170001 The S7 diagnostics buffer cannot be viewed because communication with the PLC is shut down. Set the PLC to online mode. 170002 The S7 diagnostics buffer cannot be viewed because reading of the diagnostics buffer (SSL) was canceled with error. -- 170003 An S7 diagnostics event cannot be visualized. The system returns internal error %2. -- 170004 An S7 diagnostics event cannot be visualized. The system returns an internal error of error class %2, error number %3. -- 170007 It is not possible to read the S7 diagnostics buffer (SSL) because this operation was canceled with an internal error of class %2 and error code %3. -- 180000 - Misc/common alarms Number Effect/causes Remedy 180000 A component/OCX received configuration data with Install a newer component. a version ID which is not supported. 180001 System overload because too many actions running in parallel. Not all the actions can be executed, some are rejected. Several remedies are available: ďˇ Generate the alarms at a slower rate (polling). ďˇ Initiate scripts and functions at greater intervals. If the alarm appears more frequently: Restart the HMI device. 180002 The screen keyboard could not be activated. Possible causes: Install WinCC flexible Runtime again. "TouchInputPC.exe" was not registered due to a faulty Setup. 298 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 190000 - Tag alarms Number Effect/causes 190000 It is possible that the tag is not updated. -- 190001 The tag is updated after the cause of the last error state has been eliminated (return to normal operation). -- 190002 The tag is not updated because communication with the PLC is down. Select the system function "SetOnline" to go online. 190004 The tag is not updated because the configured tag address does not exist. Check the configuration. 190005 The tag is not updated because the configured PLC type Check the configuration. does not exist for this tag. 190006 The tag is not updated because it is not possible to map the PLC type in the data type of the tag. Check the configuration. 190007 The tag value is not modified because the connection to the PLC is interrupted or the tag is offline. Set online mode or reconnect to the PLC. 190008 The threshold values configured for the tag have been violated, for example, by ďˇ A value entered ďˇ A system function ďˇ A script Observe the configured or current threshold values of the tag. 190009 An attempt has been made to assign the tag a value which is outside the permitted range of values for this data type. For example, a value of 260 was entered for a byte tag or a value of -3 for an unsigned word tag. Observe the range of values for the data type of the tags. 190010 Too many values are written to the tag (for example, in a The following remedies are available: loop triggered by a script). ďˇ Increase the time interval between multiple write Values are lost because only up to 100 actions are actions. saved to the buffer. ďˇ Do not use an array tag longer than 6 words when you configure an acknowledgment on the HMI device using "Acknowledgment HMI". 190011 Remedy Possible cause 1: The value entered could not be written to the configured PLC tag because the high or low limit was exceeded. Make sure that the value entered lies within the range of values of the control tags. The system discards the entry and restores the original value. Possible cause 2: The connection to the PLC was interrupted. Check the connection to the PLC. 190012 It is not possible to convert a value from a source format to a target format, for example: Check the range of values or the data type of the tags. An attempt is being made to assign a value to a counter that is outside the valid, PLC-specific value range. A tag of the type Integer should be assigned a value of the type String. 190013 The user has entered a string that is longer than the tag. The string is automatically shortened to the permitted length. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Only enter strings that do not exceed the permitted tag length. 299 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 190100 - Area pointer alarms Number Effect/causes Remedy 190100 The area pointer is not updated because the address configured for this pointer does not exist. Type 1 Warnings 2 Errors 3 PLC acknowledgment 4 HMI device acknowledgment 5 LED mapping 6 Trend request 7 Trend transfer 1 8 Trend transfer 2 No.: Consecutive number displayed in WinCC flexible ES. Check the configuration. 190101 The area pointer is not updated because it is not possible to map the PLC type to the area pointer type. Parameter type and no.: see alarm 190100 -- 190102 The area pointer is updated after the cause of the last -error state has been eliminated (return to normal operation). Parameter type and no.: See alarm 190100. 200000 - PLC coordination alarms Number Effect/causes Remedy 200000 Coordination is not executed because the address configured in the PLC does not exist/is not set. Change the address or set up the address in the PLC. 200001 Coordination is canceled because the write access to the address configured in the PLC is not possible. Change the address or set the address in the PLC at an area which allows write access. 200002 Coordination is not carried out at the moment because the address format of the area pointer does not match the internal storage format. Internal error 200003 Coordination can be executed again because the last error state is eliminated (return to normal operation). -- 200004 The coordination may not be executed. -- 200005 No more data is read or written. Possible causes: ďˇ The cable is defective. ďˇ The PLC does not respond, is defective, etc. ďˇ System overload Ensure that the cable is plugged in and the PLC is operational. Restart the system if the system alarm persists. 300 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 210000 - PLC job alarms Number Effect/causes Remedy 210000 Jobs are not processed because the address configured in the PLC does not exist/has not been set up. Change the address or set up the address in the PLC. 210001 Jobs are not processed because read/write access to the Change the address or set up the address in the address configured in the PLC is not possible. PLC in an area which allows read/write access. 210002 Jobs are not executed because the address format of the Internal error area pointer does not match the internal storage format. 210003 The job buffer is processed again because the last error status has been eliminated (return to normal operation). -- 210004 It is possible that the job buffer will not be processed. -- 210005 A control request with an illegal number was initiated. Check the PLC program. 210006 An error occurred while attempting to execute the control Check the parameters of the control request. request. As a result, the control request is not executed. Recompile the configuration. Observe the next/previous system alarms. 220000 - WinCC channel adapter alarms Number Effect/causes Remedy 220001 The tag is not downloaded because the associated communication driver / HMI device does not support the download of Boolean/discrete data types. Change the configuration. 220002 The tag is not downloaded because the associated communication driver / HMI device does not support write access to the data type BYTE. Change the configuration. 220003 The communication driver cannot be loaded. The driver may not be installed. Install the driver by reinstalling WinCC flexible Runtime. 220004 Communication is down and no update data is transferred because the cable is not connected or defective etc. Check the connection. 220005 Communication is up. -- 220006 The connection between the specified PLC and the specified port is active. -- 220007 The connection to the specified PLC is interrupted at the Check whether specified port. ďˇ The cable is plugged in ďˇ The PLC is OK ďˇ The correct port is used ďˇ Your configuration is OK (port parameters, protocol settings, PLC address). Restart the system if the system alarm persists. 220008 The communication driver cannot access or open the specified port. The port may be in use by another application or the port used is not available on the destination device. There is no communication with the PLC. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Close all the applications which access this port and restart the computer. Use another port of the system. 301 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 230000 - View alarms Number Effect/causes 230000 The value entered could not be accepted. The system Enter a practical value or delete any unneeded users. discards the entry and restores the previous value. Either ďˇ The value range has been exceeded ďˇ Illegal characters have been entered ďˇ The maximum permitted number of users has been exceeded. 230002 The currently logged in user has not the required authorization. The system therefore discards the input and restored the previous value. 230003 Changeover to the specified screen failed because the Configure the screen and check the screen selection screen is not available/configured. The current screen function. remains selected. 230005 The value range of the tag has been exceeded in the I/O field. The original value of the tag is retained. Observe the range of values for the tag when entering a value. 230100 During navigation in the web browser, the system returned a message which may be of interest to the user. The web browser continues to run but may not (fully) show the new page. Navigate to another page. 230200 The connection to the HTTP channel was interrupted due to an error. This error is explained in detail by another system alarm. Data is no longer exchanged. Check the network connection. Check the server configuration. 230201 The connection to HTTP channel was established. Data is exchanged. -- 302 Remedy Log on as a user with appropriate authorization. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 230202 WININET.DLL has detected an error. This error is usually generated if it is not possible to connect to the server or if the server denies access because the client could not authenticate itself. A rejected server certificate could also cause a communication error in secure SSL connections. For details, refer to the error text in the alarm. This text is always output in the language of your Windows installation, as it is returned by the Windows operating system. Process values are not exchanged. The part of the alarm which is returned by the Windows operating system may not be displayed, for example "An error has occurred." WININET.DLL returns the following error: Number: 12055 Text:HTTP: ." Depending on the cause: When an attempt to connect fails or a timeout error occurs: ďˇ Check the network connection and the network. ďˇ Check the server address. ďˇ Check whether the WebServer is actually running on the destination station. Faulty authorization: ďˇ The configured user name and/or password do not match those on the server. Establish consistency When the server certificate is rejected: Certificate signed by an unknown CA ( ): ďˇ Either ignore this item in your project, or ďˇ Install a certificate that has been signed with a root certificate known to the client computer. The date of the certificate is invalid: ďˇ Either ignore this item in your project, or ďˇ Install a certificate with a valid date on the server. Invalid CN (Common Name or Computer Name): ďˇ Either ignore this item in your project, or ďˇ Install a certificate with a name that corresponds to that of the server address. 230203 Although a connection can be made to the server, the HTTP server refuses to connect because ďˇ WinCC flexible Runtime is not running on the server or ďˇ The HTTP channel is not supported (503 Service unavailable). Error 503 Service unavailable: Check if WinCC flexible Runtime is running on the server and if the HTTP channel is supported. Other errors can only occur if the Webserver does not support the HTTP channel. The language of the alarm text depends on the Webserver. Data is not exchanged. 230301 An internal error has occurred. An English text explains the error in more detail. This may be caused by insufficient memory. OCX does not work. -- 230302 The name of the remote server cannot be resolved. The attempt to connect failed. Check the configured server address. Check whether the DNS service is available on the network. 230303 The remote server is not running on the addressed computer. Wrong server address. The attempt to connect failed. Check the configured server address. Check whether the remote server is running on the target computer. 230304 The remote server on the addressed computer is incompatible with VNCOCX. The attempt to connect failed. Use a compatible remote server. 230305 The authentication has failed because the password is incorrect. The attempt to connect failed. Configure the correct password. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 303 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 230306 Error in the connection to the remote server. This may occur as a result of network problems. The attempt to connect failed. Check whether ďˇ The bus cable is plugged in ďˇ There are network problems. 230307 The connection to the remote server was shut down because ďˇ The remote server was shut down, or ďˇ The user instructed the server to close all connections. -- The connection is closed. 230308 This alarm provides information on the connection status. An attempt is made to connect. -- 240000 - Authorization alarms Number Effect/causes Remedy 240000 WinCC flexible Runtime is operating in demo mode. You have no authorization or your authorization is corrupted. Install the authorization. 240001 WinCC flexible Runtime is operating in demo mode. Too many tags are configured for the installed version. Load an adequate authorization / power pack. 240002 WinCC flexible Runtime is operating with a time-limited emergency authorization. Restore the full authorization. 240004 Error while reading the emergency authorization. WinCC flexible Runtime is operating in demo mode. Restart WinCC flexible Runtime, install the authorization or repair the authorization (see Commissioning Instructions Software Protection). 240005 The Automation License Manager has detected an internal system fault. Possible causes: ďˇ A corrupt file ďˇ A defective installation ďˇ No free space for the Automation License Manager etc. Reboot the HMI device or PC. If this does not solve the problem, remove the Automation License Manager and install it again. 250000 - S7 Force alarms Number Effect/causes Remedy 250000 The tag in the specified line in "Status Force" is not updated because the address configured for this tag is not available. Check the set address and then verify that the address is set up in the PLC. 250001 The tag in the specified line in "Status Force" is not updated because the PLC type configured for this tag does not exist. Check the set address. 304 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 250002 The tag in the specified line in "Status Force" is not updated because it is not possible to map the PLC type in the tag type. Check the set address. 250003 An attempt to connect to the PLC failed. The tags are not updated. Check the connection to the PLC. Check that the PLC is switched on and is online. 260000 - Password system alarms Number Effect/causes Remedy 260000 An unknown user or an unknown password has been entered in the system. The current user is logged off from the system. Log on to the system as a user with a valid password. 260001 The logged in user does not have sufficient authorization to execute the protected functions on the system. Log on to the system as a user with sufficient authorization. 260002 This alarm is triggered by the system function "TrackUserChange". -- 260003 The user has logged off from the system. -- 260004 The user name entered into the user view already exists in the user management. Select another user name because user names have to be unique in the user management. 260005 The entry is discarded. Enter a shorter user name. 260006 The entry is discarded. Use a shorter or longer password. 260007 The logon timeout value entered is outside the valid range of 0 to 60 minutes. The new value is discarded and the original value is retained. Enter a logon timeout value between 0 and 60 minutes. 260008 An attempt was made to read a PTProRun.pwl file created with ProTool V 6.0 in WinCC flexible. Reading the file was canceled due to incompatibility of the format. -- 260009 You have attempted to delete the user "Admin" or "PLC User". These users are fixed components of the user management and cannot be deleted. If you need to delete a user, because perhaps you have exceeded the maximum number permitted, delete another user. 260012 The passwords entered in the "Change Password" dialog and the confirmation field are not identical. The password has not been changed. User will be logged off. You have to log on to the system again. Then enter the identical password twice to be able to change the password. 260013 The password entered in the "Change Password" dialog is invalid because it is already in use. The password has not been changed. User will be logged off. You have to log on to the system again. Then enter a new password that has not been used before. 260014 You have tried unsuccessfully to log on three times in succession. You will be locked out and assigned to group no. 0. You can log on to the system with your correct password. Only an administrator can change the assignment to a group. 260024 The password you entered does not meet the necessary Enter a password that contains at least one number. security guidelines. 260025 The password you entered does not meet the necessary Enter a password that contains at least one special security guidelines. character. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 305 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 260028 Upon system start-up, an attempt to log on, or when Check the connection to the SIMATIC Logon Server trying to change the password of a SIMATIC log-on and its configuration; for example: user, the system attempts to access the SIMATIC Logon 1. Port number Server. 2. IP address If attempting to log on, the new user is not logged in. If a 3. Server name different user was logged on before, then this user is 4. Functional transfer cable logged off. Or use a local user. 260030 The SIMATIC Logon user could not change his Log in again and choose a different password. password on the SIMATIC Logon Server. The new Check the password rules on the SIMATIC Logon password may not comply with the password regulations Server. on the server or the user does not have the right to change his password. The old password remains and the user is logged off. 260033 The action change password or log on user could not be Check the connection to the SIMATIC Logon Server carried out. and its configuration; for example: 1. Port number 2. IP address 3. Server name 4. Functional transfer cable Or use a local user. 260034 The last logon operation has not yet ended. A user action or a logon dialog can therefore not be called. Wait until the logon operation is complete. The logon dialog is not opened. The user action is not executed. 260035 The last attempt to change the password was not completed. A user action or a logon dialog can therefore not be called. Wait until the procedure is complete. The logon dialog is not opened. The user action is not executed. 260036 There are insufficient licenses on the SIMATIC Logon Sever. The logon is not authorized. Check the licensing on the SIMATIC Logon Server. 260037 There is no license on the SIMATIC Logon Sever. A logon is not possible. Check the licensing on the SIMATIC Logon Server. It is not possible to log on via the SIMATIC Logon Server, only via a local user. 260040 The system attempts to access the SIMATIC Logon Server upon system start-up or when trying to change the password. If attempting to log on, the new user is not logged in. If a different user was logged on before, then this user is logged off. 260043 It was not possible to log the user on to the SIMATIC Logon Server. The user name or the password could be incorrect or the user does not have sufficient rights to log on. Check connection to the domain and its configuration in the Runtime security settings editor. Or use a local user. Try again. If necessary, check the password data on the SIMATIC Logon Server. The new user is not logged in. If a different user was logged on before, then this user is logged off. 306 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 260044 It was not possible to log the user on to the SIMATIC Logon Server as his account is blocked. Check the user data on the SIMATIC Logon Server. The new user is not logged in. If a different user was logged on before, then this user is logged off. 260045 The SIMATIC Logon user is not associated to any or several groups. The new user is not logged in. If a different user was logged on before, then this user is logged off. Check the user data on the SIMATIC Logon Server and the configuration in your WinCC flexible project. A user may only be assigned to one group. 270000 - System alarms Number Effect/causes Remedy 270000 A tag is not indicated in the alarm because it attempts to access an invalid address in the PLC. Check whether the data area for the tag exists in the PLC, the configured address is correct and the value range for the tag is correct. 270001 There is a device-specific limit as to how many alarms may be queued for output (see the operating instructions). This limit has been exceeded. The view no longer contains all the alarms. However, all alarms are written to the alarm buffer. -- 270002 The view shows alarms of a log for which there is no data in the current project. Wildcards are output for the alarms. Delete older log data if necessary. 270003 The service cannot be set up because too many devices Reduce the number of HMI devices which want to want to use this service. use the service. A maximum of four devices may execute this action. 270004 Access to persistent buffer is not possible. Alarms cannot be restored or saved. If the problems persist at the next startup, contact Customer Support (delete Flash). 270005 Persistent buffer damaged: Alarms cannot be restored. If the problems persist at the next startup, contact Customer Support (delete Flash). 270006 Project modified: Alarms cannot be restored from the persistent buffer. The project was generated and transferred new to the HMI device; The error should no longer occur when the device starts again. 270007 A configuration problem is preventing the restore (a DLL is missing, a directory is unknown, etc.). Update the operating system and then transfer your project again to the HMI device. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 307 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 280000 - DPHMI alarms Connection Number Effect/causes Remedy 280000 Connection is up because the cause of the interruption has been eliminated. -- 280001 No more data is read or written. Possible causes: ďˇ The cable is defective ďˇ The PLC does not respond, is defective, etc. ďˇ The wrong port is used for the connection ďˇ System overload Check whether ďˇ The cable is plugged in ďˇ The PLC is OK ďˇ The correct port is used. 280002 The connection used requires a function block in the PLC. The function block has responded. Communication is now enabled. -- 280003 The connection used requires a function block in the PLC. The function block has not responded. Check whether ďˇ The cable is plugged in ďˇ The PLC is OK ďˇ The correct port is used. Restart the system if the system alarm persists. Restart the system if the system alarm persists. Remedy depends on the error code: 1: The function block must set the COM bit in the response container. 2: The function block must not set the ERROR bit in the response container. 3: The function block must respond within the specified time (timeout). 4: Go online to the PLC. 280004 308 The connection to the PLC is interrupted. There is no data exchange at present. Check the connection parameters in WinCC flexible. Ensure that the cable is plugged in, the PLC is operational, the correct port is being used. Restart the system if the system alarm persists. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 290000 - Recipe system alarms Number Effect/causes Remedy 290000 The recipe tag could not be read or written. It is assigned the start value. The alarm can be entered in the alarm buffer for up to four more failed tags if necessary. After that, alarm 290003 is output. Check in the configuration that the address has been set up in the PLC. 290001 An attempt has been made to assign a value to a recipe tag which is outside the value range permitted for this type. The alarm can be entered in the alarm buffer for up to four more failed tags if necessary. After that, alarm 290004 is output. Observe the value range for the tag type. 290002 It is not possible to convert a value from a source format to a target format. The alarm can be entered in the alarm buffer for up to four more failed recipe tags if necessary. After that, alarm 290005 is output. Check the value range or type of the tag. 290003 This alarm is output when alarm number 290000 is triggered more than five times. In this case, no further separate alarms are generated. Check in the configuration that the tag addresses have been set up in the PLC. 290004 This alarm is output when alarm number 290001 is triggered more than five times. In this case, no further separate alarms are generated. Observe the value range for the tag type. 290005 This alarm is output when alarm number 290002 is triggered more than five times. In this case, no further separate alarms are generated. Check the value range or type of the tag. 290006 The threshold values configured for the tag have been violated by values entered. Observe the configured or current threshold values of the tag. 290007 There is a difference between the source and target structure of the recipe currently being processed. The target structure contains an additional data recipe tag which is not available in the source structure. The data recipe tag specified is assigned its start value. Insert the specified data recipe tag in the source structure. 290008 There is a difference between the source and target structure of the recipe currently being processed. The source structure contains an additional data recipe tag which is not available in the target structure and therefore cannot be assigned. The value is rejected. Remove the specified data recipe tag in the specified recipe from the project. 290010 The storage location configured for the recipe is not Check the configured storage location. permitted. Possible causes: Illegal characters, write protection, data carrier out of space or does not exist. 290011 The record with the specified number does not exist. Check the source for the number (constant or tag value). 290012 The recipe with the specified number does not exist. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Check the source for the number (constant or tag value). 309 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 290013 An attempt was made to save a record under a record number which already exists. The action is not executed. The following remedies are available: ďˇ Check the source for the number (constant or tag value). ďˇ First, delete the record. ďˇ Change the "Overwrite" function parameter. 290014 The file specified to be imported could not be found. Check: ďˇ The file name ďˇ Ensure that the file is in the specified directory. 290020 Alarm reporting that the download of records from the HMI device to the PLC has started. -- 290021 Alarm reporting that the download of records from the HMI device to the PLC was completed. -- 290022 Alarm reporting that the download of records from the HMI device to the PLC was canceled due to an error. Check in the configuration whether: ďˇ The tag addresses are configured in the PLC ďˇ The recipe number exists ďˇ The record number exists ďˇ The "Overwrite" function parameter is set 290023 Alarm reporting that the download of records from the PLC to the HMI device has started. -- 290024 Alarm reporting that the download of records from the PLC to the HMI device was completed. --- 290025 Alarm reporting that the download of records from the PLC to the HMI device was canceled due to an error. Check in the configuration whether: ďˇ The tag addresses are configured in the PLC ďˇ The recipe number exists ďˇ The record number exists ďˇ The "Overwrite" function parameter is set 290026 An attempt has been made to read/write a record Set the record status to zero. although the record is not free at present. This error may occur in the case of recipes for which downloading with synchronization has been configured. 290027 Unable to connect to the PLC at present. As a result, the record can neither be read nor written. Possible causes: No physical connection to the PLC (no cable plugged in, cable is defect) or the PLC is switched off. Check the connection to the PLC. 290030 This alarm is output after you selected screen which contains a recipe view in which a record is already selected. Reload the record from the storage location or retain the current values. 290031 While saving, it was detected that a record with the specified number already exists. Overwrite the record or cancel the action. 290032 While exporting records it was detected that a file with the specified name already exists. Overwrite the file or cancel the process. 290033 Confirmation request before deleting records. -- 310 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 290040 A record error with error code %1 that cannot be described in more detail occurred. The action is canceled. It is possible that the record was not installed correctly on the PLC. Check the storage location, the record, the "Data record" area pointer and if necessary, the connection to the PLC. Restart the action after a short time. If the error persists, contact Customer Support. Forward the relevant error code to Customer Support. 290041 A record or file cannot be saved because the storage location is full. Delete files no longer required. 290042 An attempt was made to execute several recipe actions simultaneously. The last action was not executed. Trigger the action again after waiting a short period. 290043 Confirmation request before storing records. -- 290044 The data store for the recipe has been destroyed and is deleted. -- 290050 Alarm reporting that the export of records has started. -- 290051 Alarm reporting that the export of records was completed. -- 290052 Alarm reporting that the export of records was canceled due to an error. Ensure that the structure of the records at the storage location and the current recipe structure on the HMI device are identical. 290053 Alarm reporting that the import of records has started. -- 290054 Alarm reporting that the import of records was completed. -- 290055 Alarm reporting that the import of records was canceled due to an error. Ensure that the structure of the records at the storage location and the current recipe structure on the HMI device are identical. 290056 Error when reading/writing the value in the specified line/column. The action was canceled. Check the specified line/column. 290057 The tags of the recipe specified were toggled from "offline" to "online" mode. Each change of a tag in this recipe is now immediately downloaded to the PLC. -- 290058 The tags of the specified recipe were toggled from "offline" to "online" mode. Modifications to tags in this recipe are no longer immediately transferred to the PLC but must be transferred there explicitly by downloading a record. -- 290059 Alarm reporting that the specified record was saved. -- 290060 Alarm reporting that the specified record memory was cleared. -- 290061 Alarm reporting that clearing of record memory was canceled due to an error. -- 290062 The record number is above the maximum of 65536. Select another number. This record cannot be created. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 311 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms Number Effect/causes Remedy 290063 This occurs with the system function "ExportDataRecords" when the parameter "Overwrite" is set to No. An attempt has been made to save a recipe under a file name which already exists. The export is canceled. Check the "ExportDataRecords" system function. 290064 Alarm reporting that the deletion of records has started. -- 290065 Alarm reporting that the deletion of records has successfully completed. -- 290066 Confirmation request before deleting records. -- 290068 Security request to confirm if all records in the recipe -should be deleted. 290069 Security request to confirm if all records in the recipe -should be deleted. 290070 The record specified is not in the import file. Check the source of the record number or record name (constant or tag value). 290071 During the editing of record values, a value was entered which exceeded the low limit of the recipe tag. The entry is discarded. Enter a value within the limits of the recipe tag. 290072 When editing record values, a value was entered which exceeds the high limit of the recipe tag. The entry is discarded. Enter a value within the limits of the recipe tag. 290073 An action (e.g. saving a record) failed due to an unknown error. The error corresponds to the status alarm IDS_OUT_CMD_EXE_ERR in the large recipe view. -- 290074 While saving, it was detected that a record with the specified number already exists but under another name. Overwrite the record, change the record number or cancel the action. 290075 A record with this name already exists. The record is not saved. Please select a different record name. 290110 The default values could not be set due to an error. -- 290111 The Recipes subsystem cannot be used. Recipe views have no content and recipe-specific functions will not be performed. Transfer the project to the device again, together with the recipes (the corresponding check box in the Transfer dialog must be checked). Possible causes: ďˇ An error occurred while transferring the recipes. ďˇ The recipe structure was changed in ES. When the project was downloaded again, the recipes were not transferred with it. This means that the new configuration data is not being transferred to the old recipes on the device. 312 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 300000 - Alarm_S alarms Number Effect/causes Remedy 300000 Faulty configuration of process monitoring (e.g. using PDiag or S7 Graph): More alarms are queued than specified in the specifications of the CPU. No further ALARM_S alarms can be managed by the PLC and reported to the HMI devices. Change the PLC configuration. 300001 ALARM_S is not registered on this PLC. Select a controller that supports the ALARM_S service. 310000 - Report system alarms Number Effect/causes Remedy 310000 An attempt is being made to print too many reports in parallel. Only one log file can be output to the printer at a given time; the print job is therefore rejected. Wait until the previous active log was printed. Repeat the print job if necessary. 310001 An error occurred on triggering the printer. The report is either not printed or printed with errors. Evaluate the additional system alarms related to this alarm. Repeat the print job if necessary. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 313 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 320000 - Alarms Number Effect/causes 320000 The movements have already been indicated by another Deselect the movements on the other display units device. and select the motion control screen on the required The movements can no longer be controlled. display unit. 320001 The network is too complex. The faulty addresses cannot be indicated. View the network in STL. 320002 No diagnosable alarm message (error) selected. The unit associated with the alarm message could not be selected. Select a diagnostics alarm from the ZP_ALARM alarm screen. 320003 No alarm message (error) exists for the selected unit. The detail view cannot visualize any networks. Select the defective unit from the overview screen. 320004 The required signal states could not be read by the PLC. Check the consistency between the configuration on The faulty addresses cannot be found. the display unit and the PLC program. 320005 The project contains ProAgent elements which are not installed. ProAgent diagnostic functions cannot be performed In order to run the project, install the optional ProAgent package. 320006 You have attempted to execute a function which is not supported in the current constellation. Check the type of the selected unit. 320007 No error-triggering addresses were found on the networks. ProAgent cannot indicate any faulty addresses. Switch the detail screen to STL layout mode and check the status of the addresses and exclusion addresses. 320008 The diagnostic data stored in the configuration are not synchronized with those in the PLC. ProAgent can only indicate the diagnostic units. Transfer the project to the HMI device again. 320009 The diagnostic data stored in the configuration are not synchronized with those in the PLC. The diagnostic screens can be operated as usual. ProAgent may be unable to show all diagnostic texts. Transfer the project to the HMI device again. 320010 The diagnostic data stored in the configuration are not synchronized with those in STEP7. The ProAgent diagnostics data is not up-to-date. Transfer the project to the HMI device again. 320011 A unit with the corresponding DB number and FB number does not exist. The function cannot be executed. Check the parameters of the "SelectUnit" function and the units selected in the project. 320012 The "Step sequence mode" dialog is no longer supported. Use the ZP_STEP step sequence screen from the corresponding standard project for your project. Instead of calling the Overview_Step_Sequence_Mode function, call the "FixedScreenSelection" function using ZP_STEP as the screen name. 320014 The selected PLC cannot be evaluated for ProAgent. The Alarm view assigned to the "EvaluateAlarmDisplayFault" system function could not be found. Check the parameters of the "EvaluateAlarmDisplayFault" system function. 314 Remedy Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 330000 - GUI alarms Number Effect/causes Remedy 330022 Too many dialogs are open on the HMI device. Close all dialogs you do not require on the HMI device. 330026 The password will expire after the number of days shown. Enter a new password. 350000 - GUI alarms Number Effect/causes Remedy 350000 PROFIsafe packages have not arrived within the necessary period. There is a communication problem with the F-CPU. Check the WLAN connection. RT is terminated. 350001 PROFIsafe packages have not arrived within the necessary period. There is a communication problem with the F-CPU. Check the WLAN connection. The PROFIsafe connection is re-established. 350002 An internal error has occurred. Internal error Runtime is terminated. 350003 Feedback concerning the connection established with the F-CPU. -- The Emergency-Off buttons are active immediately. 350004 PROFIsafe communication was set and the connection was cleared. The Runtime can be terminated. -- The Emergency-Off buttons are deactivated immediately. 350005 Incorrect address configured for the F-slave. No PROFIsafe connection. Check and modify the address of the F slave in WinCC flexible ES. 350006 The project has started. At the start of the project, the enabling buttons must be checked for functionality. Press the two enabling buttons one after another in the "Enable" and "Panic" positions. 350008 The wrong number of fail-safe buttons was configured. No PROFIsafe connection. Change the number of fail-safe buttons in the project. The device is in Override mode. Exit Override mode. 350009 It may no longer be possible to detect the location because transponder detection fails. 350010 Internal error: The device has no fail-safe buttons. Send the device back. Worldwide contact person Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 315 PRELIMINARY II 1.7.2010 Appendix A.5 System alarms 316 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Abbreviations CPU Central Processing Unit CRC Cyclic redundancy check CSV Comma Separated Values DC Direct Current DHCP Dynamic Host Configuration Protocol DNS Domain Name System DP Distributed I/O IO Input and Output EAP Extensible Authentication Protocol ESD Components and modules endangered by electrostatic discharge EMC Electromagnetic Compatibility EN European standard ES Engineering System ESD Components and modules endangered by electrostatic discharge F-CPU Fail-safe Central Processing Unit (fail-safe PLC) GND Ground HF High Frequency HMI Human Machine Interface IEC International Electronic Commission IEEE Institute of Electrical and Electronics Engineers IP Internet Protocol IWLAN Industrial Wireless Local Area Network LAN Local Area Network LED Light Emitting Diode MAC Media Access Control MPI Multipoint Interface (SIMATIC S7) MS Microsoft MTBF Mean Time Between Failures n. c. Not connected OP Operator Panel PC Personal Computer PG Programming device PELV Protective Extra Low Voltage PPI Point-to-Point Interface (SIMATIC S7) RAM Random Access Memory RJ45 Registered Jack Type 45 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 317 PRELIMINARY II 1.7.2010 Abbreviations 318 SAR Specific absorption rate SD Security Digital SIL Safety Integrity Level SP Service Pack PLC Programmable Logic Controller SSID Service set identifier TAB Tabulator TCP/IP Transmission Control Protocol/Internet Protocol TFT Thin Film Transistor TIA Totally Integrated Automation TLS Transport Layer Security UL Underwriterâs Laboratory USB Universal Serial Bus WAP Wireless Access Point WLAN Wireless Local Area Network WINS Windows Internet Naming Service Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Glossary "Transfer" mode "Transfer" is an operating mode of the HMI device in which an executable project is transferred from the configuration PC to an HMI device. Access point See Wireless access point. Ad hoc network An ad hoc network in information technology refers to a wireless network between two or more mobile devices, for which no fixed infrastructure is necessary. This technique is used with Bluetooth, for example, to spontaneously link mobile phones. Ad hoc mode is also possible for WLAN. Alarm logging Output of user-specific alarms to a printer, in parallel to their output to the HMI device screen. Alarm, acknowledging an Acknowledgment of an alarm confirms that it has been noted. Alarm, coming in Moment at which an alarm is triggered by the PLC or HMI device. Alarm, going out Moment at which the initiation of an alarm is reset by the PLC. Alarm, user-specific An alarm is configurable object. A user-specific alarm designates a certain operating status of the plant connected to the HMI device via the PLC. Automation system An automation system is a controller of the SIMATIC S7 series, such as a SIMATIC S7-300. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 319 PRELIMINARY II 1.7.2010 Glossary Bootloader Used to start the operating system. Automatically started when the HMI device is switched on. After the operating system has been loaded, the Loader opens. Configuration PC A configuration PC is a programming device or PC on which HMI projects are created for a plant with a configuration software. CRC Test values contained in a safety message frame can be backed up as follows: â The validity of the process values contained in the safety message frame â The accuracy of the assigned address relationships â The safety-related parameters Display duration Defines whether a system alarm is displayed on the HMI device and the duration of the display. Engineering software Use the configuration software to create a project for process visualization. WinCC flexible, for example, is such a configuration software. Event An event is configurable object. Functions are triggered by defined incoming events. Events which can be assigned to a button include "Press" and "Release", for example. Fail-safe Ability of a technical system to remain in a safe operating state or switch to another safe operating state immediately after certain failures occur. Fail-safe operation Operating mode of the HMI device in which safety-related communication can be performed via safety message frames. Fail-safe system, F system A fail-safe system is used to control production processes by achieving a safe operating state immediately after shutdown. In other words, fail-safe systems control processes in which an immediate shutdown does not endanger people or the environment. Fail-safe systems are used in plants requiring higher levels of safety. 320 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Glossary Field array A field is configurable object. A reserved area is used for the input and output of values. Flash memory Non-volatile memory with EEPROM chips, used as mobile storage medium or as memory module installed permanently on the motherboard. Half Brightness Life Time Time period after which the brightness reaches 50% of the original value. The specified value is dependent on the operating temperature. HMI device An HMI device is used for operation and monitoring of production processes. The operating states of the plant are visually depicted on the HMI device. Operator controls on the HMI device enable intervention in the production process of the plant. HMI device image An HMI device image is a file that can be transferred from the configuration PC to the HMI device. An HMI device image contains the operating system for a specific HMI device and the runtime components required for the executable project file. HMI screen The HMI screens on the HMI device visualize the production process. The HMI screens are configured with WinCC flexible and will be available on the HMI device once the project has been transferred to the HMI device. Infotext Infotext is configurable object. It displays information about other objects within a project. Infotext for an alarm, for example, may contain information on the cause of the fault and troubleshooting routines. Infrastructure mode An infrastructure network is a wireless LAN, which enables communication among the various devices through a central wireless access point. The terminal devices must log on with their MAC address to the wireless access point and get an IP address assigned, if a DHCP server responds to the requesting device. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 321 PRELIMINARY II 1.7.2010 Glossary IO field An IO field is configurable object. It enables values to be entered on the HMI device and transferred to the controller, and values to be output from the controller. IO field, symbolic A symbolic IO field is configurable object. It enables values to be entered on the HMI device and transferred to the controller, and values to be output from the controller. Contains a list of default entries from which one can be selected. IT system This is a particular type of ground connection in a distribution system in electrical engineering for increased resistance to isolation errors. Object An object is a configuration component of a project, for example, a screen, alarm or IO field. Operating element Component of a project used to enter values and trigger functions. A operator control is a button, for example. PLC A PLC is a general term for devices and systems with which the HMI device communicates, for example SIMATIC S7. PLC job A PLC job triggers a function for the PLC at the HMI device. Process image The process image is a memory area in the controller which the HMI device and controller access together. At the beginning of the cyclic control program the signal states of the inputs of the HMI device are transferred to the controller via the process input images, PII. At the end of the cyclic program the process image of the outputs, PIQ is transferred as a signal state to the HMI device. Process visualization Visualization of technical processes by means of text and graphic elements. Configured plant screens allow operator intervention in active production processes by means of the input and output of data. 322 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Glossary PROFINET Within the framework of Totally Integrated Automation, PROFINET represents an enhancement of the following bus systems: â PROFIBUS DP as well-established fieldbus â Industrial Ethernet as the communication bus on the device level The experience gained from both systems has been and continues to be integrated in PROFINET. PROFINET as an Ethernet-based automation standard from PROFIBUS International defines a vendor-independent communications and engineering model. PROFINET IO controller Device used to address the connected IO devices. This means the IO controller exchanges input and output signals with assigned field devices. The IO controller is often a PLC. PROFINET IO device A distributed field device that is assigned to one of the IO controllers (e.g. remote IO, valve terminals, frequency converters, switches) PROFINET IO As part of PROFINET, PROFINET IO is a communication solution that is used to implement modular, distributed applications. PROFINET IO allows you to create automation solutions of the type with which you are familiar from PROFIBUS. PROFINET IO is implemented by the PROFINET standard for automation devices on the one hand, and on the other hand by the STEP 7 engineering software. This means that you have the same application view in STEP 7 regardless of whether you configure PROFINET or PROFIBUS devices. The programming in the user program is similar for PROFINET IO and PROFIBUS DP, provided you use the expanded blocks and system status lists for PROFINET IO. PROFIsafe A fail-safe bus profile from PROFINET for communication between the safety program and the F-I/O in a fail-safe system. PROFIsafe address Every F-I/O has a PROFIsafe address. The F-I/O uses this address to receive safety message frames from the F-CPU or send safety message frames to the F-CPU. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 323 PRELIMINARY II 1.7.2010 Glossary Project A project is the result of a configuration using an configuration software. The project normally contains several HMI screens, in which plant-specific objects are embedded. If it has been configured in WinCC flexible, the project is saved in a project file with the file name extension, "hmi". You need to distinguish between the project on the configuration PC and the runtime project on an HMI device. A project on the configuration PC may have more languages than can be managed on the HMI device. The project on the configuration PC can also be set up for different HMI devices. Only the runtime project that has been generated for the respective HMI device can be transferred to it. Project file File generated from the runtime project file for use on the HMI device. The project file is usually not transferred and remains on the configuration PC. The file name extension of a project file is *.hmi. Project file, compressed Compressed format of the project file. The compressed project file can be transferred together with the runtime project file to the respective HMI device. Backtransfer must be enabled on the configuration PC for this purpose. The compressed project file is usually saved to an external storage medium. The file extension of a compressed project file is *.pdz. Proof-test interval A period after which a component must be set to a safe state. Either the component is replaced by an unused component or full, error-free operation must be demonstrated. Recipe A recipe is a configurable component of a project. A recipe assembles variables in a fixed data structure. The corresponding data structure can be filled with data in the configuration software or on an HMI device. Using a recipe ensures that all assigned data is transferred to the PLC synchronously during the transfer of a data record. Runtime You need the Runtime software to run a project you have created with WinCC flexible on a PC or HMI device. 324 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Glossary Runtime project file A runtime project file is a file that is generated from the finished project file for a specific HMI device based on the configuration. It can therefore only be run on a particular HMI device type. The runtime project file is transferred to the corresponding HMI device and used there to operate and monitor a production process. The file extension of a runtime project file is "fwx". Safe operating state An operating state of a visualization unit which achieves safety. This is define by the absence of safety-related failures. It is defined by the acceptably low risk achieved with the protective measures taken against potential safety-related failures. The basic principle of the safety concept in a fail-safe system is the existence of a safe operating state for all process variables. Safety function A safety system integrated in F-I/Os and F-CPUs, enabling them to be used in fail-safe systems. According to IEC 61508, a safety function is implemented by a safety mechanism to ensure that the plant is kept in a safe operating state or brought into a safe operating state in the event of a fault (user safety function). Safety Integrity Level Safety Integrity Level (safety class) according to IEC 61508 and prEN 50129. The higher the safety integrity level, the greater the measures required for fail-safe operation in order to avoid systematic errors and bring systematic errors and random equipment failure under control. Safety-related communication Communication used for fail-safe data communication. Screen See HMI screen. Screen object A screen object is a configurable object used to display or operate the plant, for example, a rectangle, I/O field or alarm view. STEP 7 STEP 7 is the programming software for SIMATIC S7, SIMATIC C7 and SIMATIC WinAC PLCs. Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 325 PRELIMINARY II 1.7.2010 Glossary System alarm A system alarm is assigned to the "System" alarm class. A system alarm refers to internal states on the HMI device and the PLC. Tab sequence The tab order is the configured order of the objects that are accessed by successively pressing the "TAB" key. Tag Defined memory location to which values can be written to and read from. This can be done from the PLC or the HMI device. Based on whether the tag is interconnected with the PLC or not, we distinguish between "external" tags (process tags) and "internal" tags. Transfer Transfer of a runtime project from the configuration PC to the HMI device. Transponder A transponder is a â usually wireless â communication, display or control device that receives incoming signals and automatically responds to them. The term transponder is derived from transmitter and responder. Transponders can be passive or active. Wireless access point A wireless access point is an electronic device that acts as an interface for wireless communication devices. Terminal devices provide a wireless connection to the wireless access point via wireless adapter, which in turn is connected by cable to an installed communication network. 326 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Index Acceptance, 203 F-CPU, 203 F-I/O, 203 Plant, 203 Safety program, 204 Acoustics Feedback, 132 Ad hoc network, 51 Adapting Project, 181 Address assignment TCP/IP network, 146 Admin, 233, 234 Alarm Functional scope, 23 Alarm buffer Functional scope, 23 ALARM_S, 23 Ambient condition climatic RFID tag, 50 Climatic, docking station, 50 Climatic, HMI device, 49 Mechanical, HMI device, 49 Application case Communication errors with integrated HMI device, 256 Communication errors with logged on HMI device, 263 Enabling button askew, 258 Enabling button defective, 259 Integrating the HMI device, 255 Logging off the machine, 264 Logon, 261 Switch on the HMI device., 254 Approvals Australia, 37 CE, 36 UL approval, 37 Wireless approval, 37 Authentication, 61 Authorization, 227 Automation system Fail-safe, 32 Backlighting Reducing, 128 Backtransfer, 184, 185 Backup, 156, 157, 182, 187, 188, 190, 228 Registry information, 133 Temporary files, 133 To external storage device, 156 With ProSave, 190 With WinCC flexible, 188 Band 5 GHz, 58 Battery Used, 5 Bit assignment Direct key, 94 Booting, 113 Brightness Changing, 108 Byte assignment Direct keys, 94 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Calibrating Touch screen, 111 Cancel Transfer, 81 Care, 237 Carrying strap, 14 CE approval, 36 Certificate Requesting, 37 Certificates Stores, 154 Changing Brightness, 108 User data, 233 Character repeat Screen keyboard, 109 Charge Electrostatic, 251 Charge level Rechargeable battery, 138 Charger Connecting, 75 327 PRELIMINARY II 1.7.2010 Index Specifications, 249 Checklist Configuration, 167 Fail-safe, 162 Information security, 60 Clearance Docking station, 57 Climatic Transport conditions, 46 COM LED, 85 Commissioning, 183, 199 Communication HMI device and controller, 163 Communication error, 256 Application case, 263 Communication link with controller Number, 22 Compatibility conflict, 187, 191 Computer name For network operation, 145 Unique, 145 Computers Addressing, 144 Condensation, 46 Configuration Checklist, 167 Configuration example, 268 Configuration graphic Configuration PC, 78 PLC to Teach Pendant, 77 Configuration PC, 26 Configuration graphic, 78 Connecting, 78 Configuration phase, 26 Configure Screen keyboard, 107 Connecting Charger, 75 Configuration PC, 78 PLC, 77 Power supply unit, 65 USB device, 80 Connection compartment, 68 Contact person, 5 Control Panel Open, 102 Operating, 100 Password protection, 98 Screen keyboard, Convention Style, 4 328 Term, 4 Cookie, 153 Creating Users, 231 Data channel Enabling, 142 Locking, 142 Parameter assignment, 142 Date Setting, 125 Synchronizing, 126 Date format, 127 Date/time properties, 125 Declarations of Conformity, 37 Default Gateway, 147 Degree of protection, 51 Delay time Setting, 131 Delete Certificate, 154 Users, 234 DHCP, 146 Diagnostics HMI device, 204 Internal error, 205 Reading information, 204 Direct key, 94 Bit assignment, 94 Byte assignment, 94 Configuring, 219 Functional scope, 25 Disabling SecureMode, 101 Discrepancy error Enabling button askew, 258 Enabling button defective, 259 Display HMI device, 244 Displaying Displaying information about the HMI device, 135 Infotext, 223 Memory information, 134 System information, 134 Disposal, 5 Disturbance variable Pulse-shaped, 44 Sinusoidal, 45 DNS, 147 Server, Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Index Docking station Clearance, 57 EMC-compliant installation, 44 Main dimensions, 242 Mounting location, 56 Mounting position, 64 Documentation SIMATIC complete, 5 Double-click Setting, 110 EC Declaration of Conformity, 37 Editor System alarms, 283 Effective range RFID tag, 54 Specifications, 250 Electrostatic charge, 251 EMC Guideline, 36 EMERGENCY STOP, 33 EMERGENCY STOP button Not active, 41 Not available, 41 Operating, 41, 89 Out of service, 41 Release, 90 Requirements, 41 Emission, 40, 45 Enabling SecureMode, 101 Enabling button, 258 Panic activation, 92 Switch settings, 92 Enabling device, 42 Encryption protocol, 153 Entering data, 222 Error Internal, 235 Error code Discrepancy error, 206 Error code message, 235 Internal error, 205 Error message Error code message, 235 Ethernet settings IP address, 146 Evaluation Operator control, 93 Example of an application Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Components, 270 Flowchart, 269 HW Config, 270 Safety program, 274 Extended user view, 229 F_Block_ID, 165 F_Dest_Add, 165 F_FB_MP, 171 F_FB_RGN_n, 174 F_FB_RNG_n, 175 F_Par_Version, 165 F_SIL, 165 F_Source_Add, 165 F_WD_Time, 165 Factory setting, 194 Restoring, 79 With ProSave, 197 With WinCC flexible, 195 Fail-safe Automation system, 32 Checklist, 162 Operation, 245 Fail-safe block, 166, 168 Fail-safe operation, 22, 32, 207, 253 F-application block, 168 FB Interconnect, 170 F-CPU Acceptance, 203 Feedback Acoustic, 132 Optical, 218 F-FB, 166 F-I/O Acceptance, 203 Firmware, 137 Fixing pocket Main dimensions, 243 Front view, 14 Function Additional, 25 Testing, 92 Functional scope Alarm buffer, 23 ALARM_S, 23 Alarms, 23 Device-specific, 25 Graphics list, 23 Infotext, 25 329 PRELIMINARY II 1.7.2010 Index Limit value monitoring, 23 Log, 24 Recipe, 24 RFID tag system, 26 Safety, 25 Scaling, 23 Screen, 24 Tag, 23 Text list, 23 Global rampdown, 33 Graphics list Functional scope, 23 Grip strap, 14 GSDML file, 163 Hidden SSID, 60 High frequency radiation, 36 HMI device Displaying information, 135 During operation, 207 Enabling button, 91 Holding, 95, 96 Integrating, 209, 209 LED display, 85 Logoff, 32 Logon, 32 Operating, 95 Ports, 68 Remove, 213 Restart, 113 Switch off, 82 Switching on, 81 Usage, 40 HMI device antenna, 245 HMI Input Panel Options, 107 Homepage Internet, 151 HW Config HMI device display, 163 I/O F_FB_MP, 172 F_FB_RNG_n, 176 330 I/O DB, 170 Identification, 148 Illuminated pushbutton Operating, 93 Illustration, 4 Importing Certificate, 154 Industry Portal, 5 Information For the HMI device, 135 Information security, 60 Checklist, 60 Infotext Displaying, 223 Functional scope, 25 Input F_FB_MP, 172 F_FB_RNG_n, 176 Input unit HMI device, 244 Installation EMC-compatible, 44 RFID tag, 64 Installation according to the instructions, 35 insulation resistance, 50 Integrating, 255 Application case, 255 Internal error, 205 Diagnostics, 205 Internet E-mail, 149 Homepage, 151 Internet browser, 151 Internet Explorer, 99 Internet options Advanced, 153 Connection, 152 General, 151 Privacy, 153 IP address Ethernet, 146 iPCF, 29 iPCF-MC, 29 iWLAN, 27 Keyboard External, 100, 217 Knowledge Required, 3 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Index Language change Functional scope, 25 LED BAT, 86 COM, 85 Meaning, 85 PWR, 85 RNG, 85 SAFE, 85 LED display HMI device, 85 Main rechargeable battery, 76 License information, 137 Limit value monitoring Functional scope, 23 Loader Buttons, 98 Local rampdown, 33 Log Functional scope, 24 Logoff Application case, 264 Automatic, 32 Forced, 32 HMI device, 32 Users, 231 Logoff time, 227 Logon Application case, 261 HMI device, 32 Users, 230 Logon data, 148 MAC address, 139 Main dimensions Docking station, 242 Fixing pocket, 243 Spacer, 243 Wireless Teach Pendant F IWLAN, 241 Main rechargeable battery, 76 Charge level, 138 Insert, 74 Removing, 74, 76 Replacing, 73 Temperature, 138 Maintenance, 237 Manual Scope, 3 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Transfer, 184 Measures Organizational, 207 Mechanical Transport conditions, 46 Membrane keyboard, 100 Function, 83 Memory HMI device, 244 Memory card, 16 First time use, 70 Inserting, 69 Unplug, 70 Memory information Displaying, 134 Memory management, 136 Module diagnostics, 204 moisture protection, 51 Monitoring time, 164 Mounting Intended, 35 Mounting location Docking station, 56 Selecting, 54 Signal lamp, 57 Mounting position Docking station, 64 Mouse External, 100, 217 Multi-key operation, 217 Name server, 147 Nameplate, 15 Network ID, 148 Network operation Computer name, 145 Network parameters Setting, 146 Network&Dial-Up Connections, 146 Notice of protected rights, 4 Number format, 127 Number of characters For password, 228 For user, 228 For user view, 228 Object 331 PRELIMINARY II 1.7.2010 Index Battery, 224 Effective range (RFID) name, 226 WLAN quality, 225 Office location, 5 Offline Operating mode, 181 testing, 186 Online Operating mode, 182 testing, 187 OP properties Battery, 138 Device, 113, 135 Firmware, 137 License, 137 Memory monitoring, 136 Persistent storage, 133 Touch, 111 Opening Battery compartment, 76 Operating Control Panel, 100 EMERGENCY STOP button, 41, 89 Feedback, 218 Illuminated pushbutton, 93 Project, 217 Operating instructions Purpose, 3 Operating mode Changing, 182 Offline, 181 Online, 182 Transfer, 81, 182 Operating safety Standards, 40 Operating state Safe, 32 Operating system Parameter assignment, 98 Updating, 182, 191 Updating using ProSave, 193 Updating with WinCC flexible, 192 Operation Fail-safe, 32, 207, 253 Operation feedback, 218 Operator control Evaluation, 93 Selection, 93 Optical feedback, 218 Output F_FB_MP, 173 F_FB_RNG_n, 177 332 Override Input, 177 Panic activation Enabling button, 92 Parameter assignment Data channel, 142 Operating system, 98 Password, 98 Backup, 228 Number of characters, 228 Removing, 115 Restoring, 228 Setting up, 115 Password list, 227 Password properties, 114 Password protection, 98 Setting up, 114 PII Start address, 164, 174, 179 Pin assignment RJ45 socket, 246 USB socket, 246 PIQ Start address, 164, 174, 179 Planning Number of RFID tags, 55 Plant Acceptance, 203 PLC, 77 Configuration graphic, 77 Connecting, 77 Number, 22 PLC_User, 233, 234 Ports, 68 HMI device, 245 Possible application Wireless Teach Pendant F IWLAN, 13 Power failure, 187 Power management Levels, 87 Power Save 1, 87, 127 Power Save 2, 87, 127 Power supply Charger, 249 Docking station, 249 Power supply unit Connecting, 65 PROFINET Addressing computers, 144 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Index PROFINET IO Disabling direct keys, 139 Enabling direct keys, 139 PROFIsafe, 22 Loading the address, 140 Parameter, 164 Project Adapting, 181 Offline testing, 186 Operating, 217 Reuse, 181 Screen keyboard, 220 Testing online, 187 Transferring, 182, 183 Project file Compressed, 184 Protected trademark, 4 Protection against ingress of solid foreign bodies, 51 Protection class HMI device, 50 Protection zone, 29 Planning, 53 Setting up, 52 Protective foil, 16 Protective measure Static electricity, 252 Protocol, 22 Proxy server HMI device, 152 Internet Explorer, 99 PWR LED, 85 Radiation High frequency, 36 Radio interference, 40 Emission, 45 Radio network, 51 Rampdown Global, 33 Local, 33 Reading Diagnostic information, 204 Rear view, 15 Rechargeable battery Used, 5 Rechargeable buffer battery Charge level, 138 Temperature, 138 Recipe Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Functional scope, 24 Recommissioning, 183, 199 Recycling, 5 Regional and language settings, 127 Regional setting, 127 Registered trademark, 4 Registry information Backup, 133 Remove, 213 Removing, 74, 76 Password, 115 Replacing the main rechargeable battery Blockage of USB port, 80 Reset button, 68 Response time, 164 Restoring, 79 From external storage device, 157 With ProSave, 190 With WinCC flexible, 189 Restoring factory settings, 182 RFID tag Installation, 64 planning the mapping, 55 Planning the number, 55 Testing, 141 RFID tag system, 26 Risk analysis, 40 Risk evaluation Special mode, 42 RNG LED, 85 S7 Distributed Safety, 166 SAFE LED, 85 Safety Functional scope, 25 Standards, 40 Safety program, 204 Interconnecting FBs, 170 Scaling Functional scope, 23 Scope Manual, 3 Scope of delivery, 13, 63 Screen Functional scope, 24 Screen keyboard Adjust size, 106, 222 Change layout, 106, 222 333 PRELIMINARY II 1.7.2010 Index Character repeat, 109 Configure, 107 Entering data, 222 For Control Panel, 105 For project, 220 Move, 105, 221 Representation types, 105, 220 Screen saver, 128 Setting, 128 SecureMode Disabling, 101 Enabling, 101 Security system, 29, 226 Suitable, 53 Selecting Mounting location, 54 Selection Operator control, 93 Service, 5 Setting Date, 125 Date format, 127 Delay time, 131 Double-click, 110 Language, 220 Network parameters, 146 Number format, 127 Regional data, 127 Screen saver, 128 SMTP server, 149 Storage location, 130 Time, 125 Time format, 127 Setting language, 220 Setting up Password, 115 Password protection, 114 Protection zone, 52 Shock, 48 Shutdown, 33 Shutdown response, 208 Side view, 14 Signal lamp Mounting location, 57 SIMATIC Logon, 227 SIMATIC S7, 22 Simple user view, 229 SMTP server, 149 Setting, 149 Software Fail-safe operation, 161 For fail-safe mode, 22 334 Spacer Main dimensions, 243 Special mode Risk evaluation, 42 Specifications Charger, 249 Display, 244 Docking station, 249 Effective range, 250 Fail-safe operation, 245 HMI device antenna, 245 Input unit, 244 Main rechargeable battery, 248 Memory, 244 Ports, 245 Rechargeable buffer battery, 248 SSID Hidden, 60 Standard EMC testing, 38 TĂV, 39 Start HMI device, 113 Static electricity Protective measures, 252 STEP 7 HW Config, 163 Stop Category 0, 41 Category 1, 41 Storage location Setting, 130 Storage medium Restoring from external, 157 Saving to external, 156 Subnet Mask, 147 Support Technical, 5 Support Request, 5 Switch off HMI device, 82 Switch setting Enabling button, 92 Switching on Application case, 254 HMI device, 81 Synchronizing Date and time, 126 System alarm Configuring events, 283 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 PRELIMINARY II 1.7.2010 Index Meaning, 285, 286, 286, 289, 292, 293, 294, 295, 297, 298, 299, 300, 300, 301, 302, 304, 304, 307, 308, 309, 313, 314, 315, 315 Parameters, 283 System alarms Display, 283 System function, 93 System information Displaying, 134 System properties Device name, 145 General, 134 Memory, 134 Tag, 23 Functional scope, 23 Task planner Functional scope, 25 TCP/IP address, 146 Technical support, 5 Technical Support, 5 Temperature Rechargeable battery, 138 Temporary files Backup, 133 Test For ambient conditions, 49 Testing Function, 92 RFID tag, 141 Text list Functional scope, 23 Time Setting, 125 Synchronizing, 126 Time format, 127 Time zone Setting, 125 Touch screen, 111 Calibrating, 111 Trademark, 4 Training center, 5 Transfer, 81 Cancel, 81 Manual, 184 Transfer settings, 142 Directories, 130, 131 Transfer Settings Channel, 142 Transferring Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01 Project, 182, 183 Transport conditions, 46 Transport damage, 63 Trends Functional scope, 25 UL approval, 37 Unintentional action, 217 Updating Operating system, 191 With ProSave, 193 With WinCC flexible, 192 Updating the operating system, 182 Usage In industry, 40 In residential areas, 40 With protective measures, 48 USB Connection sequence, 79 Flash drive, 16 Keyboard, 100, 217 Memory stick, 16 Mouse, 100, 217 Pin assignment, 246 USB connection sequence, 79 USB device Connecting, 80 USB host-to-host cable, 79 USB port Lockout, 80 User data Backup, 228 Changing, 233 Restoring, 228 User group, 227 User name, 148 User view, 229 Extended, 229 Number of characters, 228 Simple, 229 Users, 231 Admin, 233, 234 Creating, 231 Delete, 234 Logoff, 231 Logon, 230 Number of characters, 228 PLC_User, 233, 234 335 PRELIMINARY II 1.7.2010 Index VBScript Functional scope, 25 Vibration, 48 Volume, 132 Volume & Sounds Properties Volume, 132 Weight HMI device, 244 WinCC flexible ES Configuration, 179 WinCC flexible Internet settings E-mail, 149 Windows CE taskbar, 98 Password protection, 98 WINS, 147 Server, 144 Wireless approval, 37 Wireless Teach Pendant F IWLAN Front view, 14 Main dimensions, 241 Possible application, 13 Rear view, 15 Scope of delivery, 13 Side view, 14 WirelessHART, 58 WLAN, 241 Configuring the connection, 117 Interface, 247 Receiver sensitivity, 247 Standards, 247 Transmission power, 248 WLAN quality, 225 WTPFailsafe_IO, 163 WTPfiwlanv2, 163 WTPStandard-IO, 163 ZigBee, 58 336 Wireless Teach Pendant F IWLAN V2 Operating Instructions, 08/2010, A5E02453837-01
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes XMP Toolkit : 3.1-702 Modify Date : 2010:07:14 16:11:26+02:00 Create Date : 2010:07:14 16:11:10+02:00 Metadata Date : 2010:07:14 16:11:26+02:00 Creator Tool : Acrobat PDFMaker 9.1 für Word Format : application/pdf Title : Wireless Teach Pendant F IWLAN V2 Description : Operating Instructions Creator : Siemens AG, I IA AS SM ID 5 Document ID : uuid:f484986b-27f8-4fcd-b7a5-eb97bcd704c4 Instance ID : uuid:fbd0f7e2-dc81-426c-a802-0b32ec409bda Producer : Acrobat Distiller 9.3.0 (Windows) Has XFA : No Page Count : 136 Subject : Operating Instructions Author : Siemens AG, I IA AS SM ID 5EXIF Metadata provided by EXIF.tools