Signify North America SNSS Ceiling Luminaire mounted light sensor User Manual QIG EasySense SNS441 A03 rev

Philips Lighting North America Corporation Ceiling Luminaire mounted light sensor QIG EasySense SNS441 A03 rev

Contents

QIG_EasySense SNS441_A03_rev

Download: Signify North America SNSS Ceiling Luminaire mounted light sensor User Manual QIG EasySense SNS441 A03 rev
Mirror Download [FCC.gov]Signify North America SNSS Ceiling Luminaire mounted light sensor User Manual QIG EasySense SNS441 A03 rev
Document ID3981596
Application IDhBe1b5UZre+3l1QWskkU0w==
Document DescriptionQIG_EasySense SNS441_A03_rev
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize124.98kB (1562235 bits)
Date Submitted2018-08-28 00:00:00
Date Available2018-08-28 00:00:00
Creation Date2018-08-28 14:44:08
Producing SoftwareAdobe PDF Library 15.0
Document Lastmod2018-08-28 15:16:30
Document TitleQIG_EasySense SNS441_A03_rev
Document CreatorAdobe InDesign CC 13.1 (Macintosh)

Note: Below data applicable
SNS200CMP.
to partner
documentation
for informationfor
Note:
applicable only
onlyfor
forSNS102CMP
SNS102CMP,and
SNS200CMP
and Refer
SNS441CMP.
Refer
to partner documentation
applicable toapplicable
SNS300CMP.
information
to SNS300CMP.
Electrical Information
Input Voltage
Current Consumption
Nominal Power Consumption
Standby Power
Environment & Approbation
Operating Ambient Temperature Range
Operating Humidity
Storage Temperature
Storage Humidity
Max Case Temperature (Tcase)
Agency Approbations
Certification
Limited Warranty
Digital Interface
Other
Status Indicators
No. Drivers per Sensor
Field Configuration
Powered by SR driver low-voltage interface
13mA
200mW
< 1 W on luminaire level, including driver standby power
0°C to 55°C
0 – 95% non condensing
-25°C to 85°C
0-95% non condensing
55°C
UL, CSA; Tested and approved for use in plenums; For use in
non-fire-rated installations only
California Title 20
5 years
Xitanium SR
None
Four drivers per sensor maximum; Wiring polarity must be maintained
via NFC ior IR. Parameters set via Philips field apps
Operation and Configuration via Mobile App
EasySense operates immediately upon installation and energization without further commissioning. If changes from
default settings are desired, EasySense can be configured via Philips field apps through NFC or IR. For a complete
description of the features and default settings—as well as details on the app—refer to www.philips.com/easysense.
Transceiver
EasySense
Ceiling-Mount
Philips EasySense Quick Installation Guide
FCC and IC Statement
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS
standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. Any
changes or modifications not expressly approved by Philips could void the user’s authority to operate this equipment.
This product is intended for commercial use only.
Sensor Part Number
This equipment should be installed and operated with a minimum distance of 20cm between the radiator and your body.
Commercial Product Name
Order Code
EasySense Ceiling-Mount Sensor
SNS102CMP (514851)
SNS200CMP (516666)
SNS300CMP (517839)
SNS441CMP
Déclaration De Conformité À La Fcc/Ic
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et
d’Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes
: (1) Ce dispositif ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris
le brouillage pouvant entraîner un mauvais fonctionnement. Tous les changements ou modifications non expressément
approuvés par Philips, sont susceptibles d’annuler le droit de l’utilisateur à se servir de cet équipement. Ce produit est
exclusivement destiné à un usage commercial.
Cet équipement doit être installé et utilisé avec une distance minimale de 20 cm entre le radiateur et votre corps.
Compatible LED Drivers
Driver Model Number
Description
XI040C110V054VPT1
Xitanium 40W 0.1-1.1A 27-54V 120-277V SR
XI075C200V054VPT1
Xitanium 75W 0.1-2.0A 27-54V 120-277V SR
Specifications available at www.philips.com/XitaniumSR.
Wiring Diagram
Connectors
EASYSENSE
WHITE
RED
SRSR+
GROUND
LINE
NEUTRAL
© 2018 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right to make changes in specifications
and/or to discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.
philips.com/easysense
PLt-1621QG_EasySenseCMP QIG
08/18
Document #: 4435 290 61451 REV. C
Philips Lighting North America Corporation
10275 W. Higgins Road, Rosemont IL 60018
Tel: 800-322-2086 Fax: 888-423-1882
Customer/Technical Service: 800-372-3331
OEM Support: 866-915-5886
Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
36-inch 18AWG solid lead wires in
plenum-rated jacket from sensor stripped
to 3/8". Connect white wire to brown (SR-)
and red wire to purple (SR+) on driver.
Four drivers per sensor maximum.
Polarity must be maintained.
NC
LED+
LED+
LEDLEDRSET2
SGND
XITANIUM SR
LED DRIVER
NFC ANTENNA
Connection
Color
Connection
Color
White
Neutral
Red
LED+
Black
Line
Blue
LED-
Green
Ground
Orange
RSET2
Purple
SR+
Green
SGND
Brown
SR-
Transceiver Dimensions (in/mm)
Installation
Notes:
1. For use in non-fire-rated installations only.
2. Remove power from fixtures/drivers before performing any electrical work.
3. Up to (4) drivers maximum can be connected to (1) EasySense. Polarity must be maintained.
1.240 (31.5) REF.
Step 1: Drill 2.5-inch hole in ceiling. It may be
more practical to remove the ceiling tile and
drill from the backside depending on material.
Step 2: Feed wires from sensor into ceiling
hole. Wire length provided is 36-inches.
Cable jacket provided is plenum-rated.
Add additional wire length if necessary
(18AWG solid wire recommended).
Step 3: Compress spring clips on sensor and
insert into ceiling hole.
Step 4: Sensor will clamp into place. Turn
sensor to appropriate position.
1.811 (46) REF.
EF
)R
Ø
48
2.
(6
EF
)R
74
3(
Ø
2.9
Step 5: Connect the wires from the sensor to the LED Driver in the fixture. Connect the white
wire from the sensor to the brown (SR-) terminal on the driver. Connect the red wire from the
sensor to the purple (SR+) terminal on the driver. Follow fixture manufacturer’s instructions for
accessing the driver.
Configuring Sensor Parameters
EasySense operates upon energization with
no further commissioning. See Transceiver
datasheet for sensor presets and
parameters that can be changed during
installation. Refer to “Operation and
Configuration via Mobile App” on last page
for further details.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : Yes
Create Date                     : 2018:08:28 14:44:08+02:00
Creator                         : Adobe InDesign CC 13.1 (Macintosh)
Modify Date                     : 2018:08:28 15:16:30+02:00
Language                        : en-US
XMP Toolkit                     : Adobe XMP Core 5.4-c006 80.159825, 2016/09/16-03:31:08
Metadata Date                   : 2018:08:28 15:16:30+02:00
Creator Tool                    : Adobe InDesign CC 13.1 (Macintosh)
Instance ID                     : uuid:c6f8c30d-e567-4906-8452-955ecb4c4fe4
Original Document ID            : xmp.did:cda8f468-0299-4fd5-ba3a-9c03fef308ae
Document ID                     : xmp.id:3043b3df-8f44-4446-b0ef-863a60176033
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:45ba1640-48f6-4fb3-99de-3af4f3411735
Derived From Document ID        : xmp.did:d59c54b3-372d-46b3-a656-e9f742bfa612
Derived From Original Document ID: xmp.did:cda8f468-0299-4fd5-ba3a-9c03fef308ae
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 13.1 (Macintosh)
History Changed                 : /
History When                    : 2018:08:28 14:44:08+02:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 15.0
Trapped                         : False
Page Count                      : 2
EXIF Metadata provided by EXIF.tools
FCC ID Filing: 2AF2N-SNSS

Navigation menu