System Sensor 2151 Users Manual

2151 to the manual 7df93305-a70e-4c46-aeb2-15604cdc538e

2015-02-02

: System-Sensor System-Sensor-2151-Users-Manual-490716 system-sensor-2151-users-manual-490716 system-sensor pdf

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadSystem-Sensor System-Sensor-2151-Users-Manual-  System-sensor-2151-users-manual
Open PDF In BrowserView PDF
INSTALLATION AND MAINTENANCE INSTRUCTIONS

2151 Low Profile
Photoelectronic Plug-in
Smoke Detector
Specifications
Size	
Height:	
Diameter:	
Weight:	
Operating Temperature Range:	
Operating Humidity Range:	
Latching Alarm:	

3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com

1.7 inches (43 mm)
4.0 inches (101 mm)
3.6 oz. (102 g)
0°C to 49°C (32°F to 120°F)
10% to 93% Relative Humidity noncondensing
Reset by momentary power interruption.

Before Installing
Please thoroughly read the System Sensor manual A051003, Applications Guide for System Smoke Detectors,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor.

this smoke detector, including 2-wire applications with and
without relays and/or current limiting resistors, 4-wire and
120VAC applications.
All bases are provided with screw terminals for power,
ground, remote annunciator connections and relay contact
connections, if applicable. The electrical ratings for each
detector-base combination are also included in the base
installation instructions.

NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 requirements. The detector used with this base should be cleaned
at least once a year.

Installation
NOTE:	 All wiring must conform to applicable local codes,
ordinances, and regulations.
NOTE:	 Verify that all detector bases are installed, that
the initiating-device circuits have been tested, and
that the wiring is correct. (Refer to detector base
manual for testing procedure.)

General Description
The 2151 low-profile photoelectronic detector uses a stateof-the-art optical sensing chamber. This detector is designed
to provide open area protection and to be used with compatible UL listed control panels only. The capability of plugging this detector into a variety of special bases makes it
more versatile than equivalent direct-wired models.

WARNING

Remove power from initiating-device circuits before installing detectors.

Two LEDs on each detector provide local 360° visible
alarm indication. They flash every ten seconds indicating
that power is applied and the detector is working properly.
The LEDs latch on in alarm. Remote LED annunciator
capability is standard and may be implemented through
an optional accessory RA400Z. The alarm can be reset
only by a momentary power interruption. This detector
may be tested by activating the internal reed switch with
a magnet.

1.	Install detectors:
	 a.	 Place the detector into the detector base.
	 b.	Turn the detector clockwise until the detector drops
into place.
	 c.	 Continue turning detector clockwise to lock it in
place.
2.	Tamper Resistance: The detector bases can be made tamper resistant. When capability is enabled, detectors cannot be removed from the base without the use of a tool.
See the detector base installation manual of the detector
base for details in using this capability.
3.	After all detectors have been installed, apply power to
the control unit.

Base Selection And Wiring Guide
Refer to the installation instructions for the Plug-in
Detector Bases for base selection and wiring instructions.
System Sensor has a variety of detector bases available for
D100-04-00	

1	

I56-581-07R

A.	Test Magnet (p/n M02-04-01 or M02-09-00)
	 1.	Place the magnet against the cover in the location
designated by the raised mark to activate the test feature (see Figure 1).
	 2.	The LEDs should latch ON within 5 seconds indicating alarm and annunciating the panel.

4.	Test the detector using the magnet as described under
TESTING.
5.	Reset the detector at the system control panel.
6.	Notify the proper authorities that the system is back on
line.
CAUTION

Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity.

B.	Test Module ( MOD400R)
	 Use the MOD400R with a DMM or voltmeter to check
the detector sensitivity as described in the MOD400R
manual.
C.	Aerosol Generator (Gemini 501)
	 Set the generator to represent 4% to 5%/ft. obscuration
as described in the Gemini 501 Manual. Using the bowlshaped applicator, apply aerosol until unit alarms.

Be sure to remove the dust covers from any sensors that
were left in place during construction as part of returning
the system to service.

Notify the proper authorities that the system is back on
line.

CAUTION

Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found	
suitable for that purpose.

Detectors that fail these tests should be cleaned as described
under MAINTENANCE and retested. If the detectors still
fail these tests, they should be returned for repair.

Testing
Before testing, notify the proper authorities that the smoke
detector system is undergoing maintenance and will temporarily be out of service. Disable the zone or system
undergoing maintenance to prevent unwanted alarms.
Detectors must be tested after installation and as part of
periodic maintenance. Test the 2151 as follows:

Maintenance
It is recommended that the detector be removed from
its mounting base to facilitate cleaning. The detector is
cleaned as follows:
NOTE:	 Before removing the detector, notify the proper
authorities that the smoke detector system is
undergoing maintenance and will be temporarily
out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

NOTE:	 Before testing the detector, check to ensure the
LEDs blink.  If they do not,  the detector has lost
power  (check the wiring) or it is defective (return
it for repair).

Figure 1. Bottom and side views showing position of test magnet:
LED

TEST MODULE
SOCKET
PAINTED
SURFACE
T
MA EST
GN
ET

C0627-00

LED
D100-04-00	

2	

I56-581-07R

Figure 2:
1.	 Remove the detector cover by prying away the four
side tabs with a small-bladed screwdriver, and then
pulling the cover from the base.
2.	 Vacuum the screen carefully without removing it. If
further cleaning is required continue with Step 3, otherwise skip to Step 8.
3.	 Remove the screen assembly by pulling it straight out
(see Figure 2).
4.	 Remove the sensing chamber cover by pulling it
straight out.
5.	 Clean the vaned chamber piece by vacuuming or
blowing out dust and particles.
6.	 Replace the sensing chamber cover, aligning the arrow
on the top with arrow on the printed circuit board.
7.	 To replace the screen, place it over the chamber
assembly, turning it until it snaps into place.
8.	 Replace the cover using the test module socket and
LEDs to align the cover and then gently pushing it
until it locks into place.
9.	 Reinstall the detector.
10.	 Test the detector as described in TESTING.
11.	 Reconnect disabled circuits.
12.	 Notify the proper authorities that the system is back
on line.

SENSOR
COVER

COVER	REMOVAL
TABS

SENSOR
SCREEN

SENSING
CHAMBER
COVER

SENSING
CHAMBER

C0253-00

Special Note Regarding Smoke Detector Guards
Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found	
suitable for that purpose.

D100-04-00	

3	

I56-581-07R

Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to repair or replace units
which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In
no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This Warranty gives you specific legal rights, and
you may also have other rights which vary from state to state.

System Sensor warrants its enclosed smoke detector to be free from
defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any
part of the smoke detector which is found to be defective in materials or
workmanship under normal use and service during the three year period
commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Repair
D100-04-00	

	

4	

I56-581-07R

©2004 System Sensor



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : 3.1-701
Create Date                     : 2005:10:27 13:23:49-05:00
Modify Date                     : 2005:10:27 13:24-05:00
Metadata Date                   : 2005:10:27 13:24-05:00
Creator Tool                    : Adobe InDesign CS2 (4.0.1)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 7597 bytes, use -b option to extract)
Document ID                     : adobe:docid:indd:48afd75b-5c7e-11d8-b3f5-95050bea16b1
Version ID                      : 1
Instance ID                     : uuid:d86c28ea-4716-11da-a78d-000393ae83b8
Rendition Class                 : proof:pdf
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 4
Creator                         : Adobe InDesign CS2 (4.0.1)
EXIF Metadata provided by EXIF.tools

Navigation menu