TRANE Air Conditioner/heat Pump(outside Unit) Manual L0903228
User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
2TTBO-IN-2 18-AC52D1-2 Condensing Un 2TTB0 & 23-[B2 ALL phases of this installation IMPORTANT -- This Document pack upon completion of work. must comply is customer with NATIONAL, property STATE and is to remain These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor. AND LOCAL with this unit. CODES Please return to service information 5 FT. ABOVE UNff=UNRESTRICTED A. GENERAL The following instructions ing Units. cover 2TTB0 & 2TTB2; Condens- NOTICE: These outdoor units may be used with indoor units equipped with Thermostatic Expansion Valve or Accutron rM Flow Control Check Valve (E C.C. V) assembly for refrigerant flow control only. Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit. To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate. B. LOCATION & PREPARATION 1. When removing unit from the pallet, the basepan. Remove tabs by cutting shown in Figure 2 (see page 2). OFTHE UNIT notice the tabs on with a sharp tool as 2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin "Trane APB2001-02". 3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) & any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s). 4. The top discharge area must be unrestricted five (5) feet above the unit. for at least 5, When the outdoor unit is mounted on a roof, be sure the roof will support the unit's weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure. 6, The maximum length of refrigerant lines from outdoor indoor unit should NOT exceed sixty (60) feet. to 7. If outdoor unit is mounted above the air handler, maximum lift should not exceed sixty (60) f_et (suction line). If air handler is mounted above condensing unit, maximum lift should not exceed sixty (60) feet (liquid line). NOTE: Refer to "Refrigerant Piping Software" Pub. No. 32=3312=02. 8. Locate and install indoor coil or air handler in accordance with instruction included with that unit. |nsta||er's @ Guide BASEPAN TAB REMOVAL 4. Provide a pull-thru hole of sufficient liquid and gas lines. 5. Be sure the tubing 6. Uncoil the tubing is of sufficient size to allow both length. --- do not kink or dent. 7. Route the tubing making all required bends and properly secure the tubing before making connections. 8. To prevent a noise within the building structure due to vibration transmission from the refrigerant lines, the following precautions should be taken: a. When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers. C. ACCUTRON TM FLOW CONTROL b. Isolation hangers should also be used -when refrigerant lines are run in stud spaces or enclosed ceilings. VALVE If the indoor unit System Refrigerant Flow control is an Accutron TM orifice and check valve assembly, an orifice size change may be necessary. See Figure 3. The outdoor model determines the required orifice size. Check the listed orifice size on nameplate of the selected outdoor model. If the indoor unit is factory shipped with a diffhrent orifice size, the orifice must be changed to obtain system rated performance. iMPORTANT: The outdoor unit is shipped with the proper size orifice and a stick-on orifice size label in an envelope attached to the outdoor unit. Outdoor unit nameplate will have correct orifice size specified as BAYFCCV---A for rated performance. D. INSTALLING REFRIGERANT if using existing refrigerant are brazed, not soldered. Condensing units LINES lines make certain that all joints have provisions for braze connections. Pressure taps are provided on the service valves unit for compressor suction and liquid pressures. of outdoor The indoor end of the recommended refrigerant line sets may be straight or with a 90 degree bend, depending upon situation requirements° This should be thoroughly checked out before ordering refrigerant line sets. The gas line must always be insulated. c. Where the refrigerant lines run through they should be insulated and isolated. d. Isolate the lines from all ductwork. E. SERVICE VALVE OPERATION BRASS LIQUID AND GAS LINE SERVICE VALVES The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below). Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock= wise only until the stem contacts the rolled edge. (See Figure 4) No torque is required. BRASS GAS LiNE BALL SERVICE VALVE The Brass Gas Line Ball Service Valve is shipped in the closed position to hold the factory refrigerant charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position. The Gas Line Ball Service Valve is full open with a 1/4 turn. See Figure 5. BRAZING REFRIGERANT LINES 1. Remove lower access cover to access service valves. 2. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing. In scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning. ® BRAZE TYPE iNDOOR END SEALING The units are factory charged with the system charge required when using fifteen (15) feet of connecting line. nameplate charge is the same. Final refrigerant charge adjustment is necessary. the Charging Charts in the outdoor unit Service Facts. 1. Determine 2. Consider the most practical ACOUTRON Use types of bends to be made and space limitations. to rebend once # 3. Determine the best starting point for routing the refrigerant tubing- -INSIDE OR OUTSIDE THE STRUCTURE. © 2003 American Standard inc. All Rights Reserved CAP TM Unit way to run the lines. NOTE: Large diameter tubing will be very difficult has been shaped. a wall or sill, C%v"°L £ AS SHIP_PE i __L _ LIQUID LINE FIELD SUPPLIED 18-AC52D1-2 |nsta||er's © LIQUID LINE SERVICE VALVE Guide GAS LiNE SERVICE VALVE ROLLED EDGE TO CAPTIVATE STEM ROLLED EDGE TO CAPTIVATE STEM CAP-_=-- CAP'_ _-_./ _,..a..._ sdv"g s,oE oF SERVICE PORT _ .EX .EADgEM _ HEADED VALVE SYSTEM SERVICE PORT / -- _HEX UNIT SIDE OF SERVICE VALVE / / LIQUID LINE CONNECTION 3. Cut and fit tubing, minimizing 4. Insulate GAS LINE CONNECTION the use of sharp 90 ° bends. the entire gas line and its fittings. 5. Do NOT allow uninsulated contact with bare gas line. liquid line to come in direct 6. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body. NOTICE: Use care to make sure that no moisture port, while wet rag is being used. enters pressure 7. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing. good brazing 3. Attach center techniques. IMPORTANT: Replace pressure tap port valve core before attaching hoses for evacuation. After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak-free! If not, release pressure; then repair! hose of manifold gauges to vacuum 4. Evacuate until the micron gauge reads 350 microns. no higher pump. than 5, Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute., then evacuation is incomplete, or system has a leak. 6, If vacuum gauge does not rise above 500 microns (1) minute, the evacuation should be complete. tap NOTICE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan. 8. Braze using accepted LEAK CHECK NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC=22 and vacuum pump. in one 7. With vacuum pump and micron gauge blanked off; open valve on HCFC-22 cylinder and charge refrigerant lines and indoor coil with vapor to tank pressure of HCFC-22 supply. NOTE: DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE. 8. Close valve on HCFC-22 supply cylinder. Close valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas pressure tap ports. GAS LiNE BALL SERVICE 114 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN CAP UNIT VALVE SIDE OF VALVE # PRESSURE TAP PORT / SYSTEM EVACUATION NOTE: Since the outdoor unit has a refrigerant liquid line valves must remain closed. GAS LINE CONNECTION charge, the gas and CAP _ 1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves. 2. Attach appropriate hoses from manifold and liquid line pressure taps. 18-AC52D1-2 gauge to gas 3 |nsta||er's Guide NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A 1/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap. 9. The liquid line shut-offvalve can now be opened. Remove shut-off valve cap. Fully insert hex wrench into the stem and backout counte.rclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 2. See Figure 4. 10. Replace liquid service pressure tap port cap and valve stem cap. These caps MIJST BE REPLACED to prevent leaks. Replace valve stem cap and pressure tap cap finger tight, then tighten an additional 116turn. 8. Mount the indoor thermostat in accordance with instruction included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions). G. COMPRESSOR START UP After all electrieal wiring is complete, SET THE THERMOSTAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up. H. OPERATIONAL PROCEDURES AND CHECKOUT 11. The gas valve can now be opened. For a ball type gas valve, open the gas valve by removing the shut-off'valve cap and turning the valve stem 1/4 turn counterclockwise, using 1/4" Open End or Adjustable wrench. See Figure 5. For brass gas line service valve opening, follow 9 and 10 above. See Figure 4. Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction (see page 8). To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts. 12. The gas valve is now open for refrigerant flow. Replace valve stein cap to prevent leaks. Again, these caps MUST BE REPLACED to prevent leaks. Replace valve stem cap and pressure tap cap finger tight, then tighten an additional 116turn. See Figure 5. Electric heaters, if used, are to be installed in the air handling device according to the instructions accompanying the air handler and the heaters. If refrigerant lines are longer than 15 feet and/or a diffhrent size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See unit Service Facts. F. ELECTRICAL CONNECTIONS I. ELECTRIC J. START CONTROL Some models have quick start components which are factory installed. For models that do not have factory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit. K. OUTDOOR When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock. 1. Power -wiring and grounding with local codes. of equipment 2. Power supply must agree with equipment 3. Install 4. Ground a separate the outdoor disconnect switch must comply nameplate. at the outdoor unit. unit per local code requirements. 5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure. 6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit. HEATERS THERMOSTAT An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat. L. SEACOAST SHIELD BAYSEAC001 (Seacoast Kit) is available for application units installed -within one mile of salt water, including seacoasts and inland waterways. on M. TROUBLESHOOTING TROUBLESHOOTING CHART -- WHAT TO CHECK SYSTEMFAULTS Table 1 -- NEC Class II Control Wiring 24 VOLTS WIRE SIZE MAX. WIRE LENGTH 18 AWG 150 FT 16 AWG 225 FT. 14 AWG 300 FT. Compressor &OD FanDoNotStart 7. Table 1 defines maximum total length of low voltage wiring from outdoor unit, to indoor unit, and to thermostat. P- PrimaryCauses S-SecondaryCauses 4 18-AC52D 1-2 |nstal|er's TYPICAL Guide FIELD HOOK=UP DIAGRAMS 'STAT A FRANDL R AIR CONDIT ONER _- ..... R fi _ .... ...... G y ODT _i ....w2 .... W3 PRINTEDFROMB152901P02 ISFAGE OR 2-STAGE FURNACE 'STAT AIR CONDITIONER E] ..... y I4 NOTE J_ ...... B PRINTED FROM B152903 P02 -kW2 present only on 2 stage thermostat and furnace Notes: LEGEND 1. Be sure power supply agrees with equipment nameplate. 2. Power wiring and grounding of equipment must comply with local codes. 3. Low voltage wiring to be No. 18 AWG minimum conductor. 4. ODT-B must be set lower than ODT-A. ..... FACTORY WIRING 5. If outdoor thermostats _ FIELD WIRING 18-AC52D1-2 (ODT) are not used, connect Wl to W2 and W3. 5 |nsta||er's Guide 2TTB0 & 2TTB2 OUTLINE Note: All dimensions SE /i¢ 'J I(}IRiC:',L ¢or4PONENT P_ DRAWING are in IVllVl(Inches). F .......................... ,'_ iF IOIRA CL EAR,NOES i UNIT SiiOULB, BE PLACED SO ROOF RUN OfF WAI_R DOES NOT POUR 9iRECYL¥ ON UNi_, AND $_()[J[D iiE £r [EAS_ 305 (12} F_ON WAIL £ND Ati SURROUNDING SIiRUBBERY ON tWO SIDES OTii_ TWO SIDES UNREStRiCteD .................... i T o Ei{{]iRICAi P,_NE{ I { SSUR( 222 (?/8) T F I T[ #( DiA ii01 E [OW VOklAGE 28 6 (I i18) DiA K O 22 2 (i/8} D[A iiO[E iN ¢ONIROL _OX BOTTOM FOR _{ECTRICA_ POWER SUPPLY OUiD ,{ SE:_7 CE _i,I rE, ¢C,!iNi¢]iON WlIN i,4 Ft,:,RE PRESSURE _,? ¸¸ SA_ F IJlI_G M F{ I FIG. 1 J G \ \ '_6AS [iNE /4 IURN BAiL S_RVJOE VAiVE, '=D" i O FEMALE BRAZED ¢ONNi[C[ION Wi[ii 1/4 SA[ FLA_E II_ESSURE £ fill k_: D E F G H J K 2TTBOO30A 2 2 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 127 (5) 57 (2 1/4) 181 (7-1/8) 44 (1-3/4) 457 (18) 2TTBOO36A 2 2 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 7/8 3/8 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18) 2TTBOO42A 2 2 730 (28-3/4) 724 (28-1/2) 651 (25-5/8) 7/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTBOO48A 2 2 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 1-1/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTBOO60A 3 1 832 (32-3/4) 829 (32-5/8) 756 1-1/8 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 2TTB2018A 2 2 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 5/8 1/4 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18) 2TTB2024A 2 2 730 (28-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTB2030A 2 2 730 (28-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTB2036A 2 2 832 (32-3/4) 724 (28-1/2) 651(25-5/8) 7/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTB2042A 3 2 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 7/8 3/8 137 (5-3/8) 86 (3-3/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 2TTB2048A 3 1 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) 2TTB2060A 3 1 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20) MODELS BASE FIG. B A C (29-3/4) From Dwg. 21 D153074 6 Rev. 5 18-AC52D 1-2 |nstal|er's MOUNTING Guide HOLE LOCATION Note: All dimensions are in IVllVl(Inches). 265 (10.43) _1 523 3_7 (20.58) ( 2,49) 2O5 (8.0Y) 517 (20,34) BASE 2 I 294 I 56) ! 171 (6.74) 688 599 (23 NOTE: For model base size, see table on page 6. 18-AC52D1-2 (2709) 58) BASE 3 From Dwg. 21 D152637 Rev. 1 7 |nsta||er's Guide CHECKOUT After installation 1. Refrigerant 2. Suction has been completed, Line, Leak checked Lines and Fittings it is recommended that .................................. properly insulated ........... 3. Have all Refrigerant Lines been secured and isolated properly? ........................................................ ] [ ] [ [ 5. Verify tightness [ connects ................... 6. Observe outdoor fan during on cycle for clearance and smooth operation ................................................. [ 7. Indoor coil drain line drains freely. Pour water into drain pan .............................................................. [ CHECKOUT PROCEDUREWITH the entire [ 4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coining into direct contact with copper tubing ........................ of all electrical PROCEDURE ] ] system be checked 1 TO CHECK @ CoN Off @ Heat [ ] 9. Return [ ] 10. Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per instructions with thermostat ...................................... air filter installed 2 Indoor Fan Operation 3 Cooling Operation 4 Checking Performance & Charge ............................................ [ ] 11. Is correct speed tap being used? (Indoor blower motor) ................................................. [ ] 12. Operate complete system in each mode to insure safe operation ................................................... [ ] MAiN P( )WER DISCONNECTS CLOSED (ON) COMPONENTOPERATION Outdoor Fan Runs indoor Blower Runs Fan Switch Auto On X Sump Heat the following list: 8. Supply registers and return grilles open and unobstructed ............................................................... iNDOOR THERMOSTAT SWITCH SETTING Step No. against Compressor Runs @ Comp. Sump Heater X X x x I x x Ix Furnace Heat Comes On X x Ix I x I x x X x x X USECHARTSATTACHEDTO O.D. UNiT Ix!xl ! x I I 5 Heating @ 6 Informowner on howto operatesystem andwhat to expectof it. At the same time deliverOwner'sUseand Care Booklet. Ix Ix D, @ Also set thermostat dial to call for cooling or heating as necessary. @ Check only necessary if heating unit is used for indoor section and wiring has been disturbed during installation of cooling equipment. @ When applicable. C Trane A business Literature Order Number 2TTBO-IN-2 File Number SV-UN-S/S-2TTBO-IN-2 RI. Supersedes New Stocking Location PI Louisville & Webb/Mason-Houston 2/03 of American Standard Companies www.trane.com Trane has a policy of continuous product and product data improvement design and specifications without notice. and it reserves the right to change
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Mar 23 04:18:18 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools