Trane H V Wshp 5 To 25 Tons Installation And Maintenance Manual Axiom Horizontal/Vertical Water Source Comfort System S GEH GEV; SVX01N EN September 2014

2015-04-02

: Trane Trane-H-V-Wshp-5-To-25-Tons-Installation-And-Maintenance-Manual-684244 trane-h-v-wshp-5-to-25-tons-installation-and-maintenance-manual-684244 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 132

DownloadTrane Trane-H-V-Wshp-5-To-25-Tons-Installation-And-Maintenance-Manual- Axiom Horizontal/Vertical Water-Source Comfort System S GEH And GEV; WSHP-SVX01N-EN September 2014  Trane-h-v-wshp-5-to-25-tons-installation-and-maintenance-manual
Open PDF In BrowserView PDF
Installation, Operation,
and Maintenance

Water Source Heat Pump
Axiom™ Horizontal/Vertical
GEHE/GEVE, EXHF/EXVF
½ to 25Tons, 50/60 Hz

Model Numbers

GEHE 006-060 - 50/60 Hz
GEHE 072-120 - 50/60 Hz
EXHF 006-070 - 60 Hz

GEVE 006-060 - 50/60 Hz
GEVE 072-300 - 50/60 Hz
EXVF 006-070 - 60 Hz

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

September 2014

WSHP-SVX01N-EN

Introduction
Read this manual thoroughly before operating or servicing
this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.

The three types of advisories are defined as follows:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
CAUTIONs situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.

WARNING

NOTICE

WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.

WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•

Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.

•

When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.

•

If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.

Indicates a situation that could result in
equipment or property-damage only
accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.

Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.

© 2014Trane All rights reserved

Failure to follow instructions could result in death or
serious injury.

WSHP-SVX01N-EN

Introduction

Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.

Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Axiom, ReliaTel,TOPSS,Tracer,Trane, and theTrane logo
are trademarks or registered trademarks ofTrane in the
United States and other countries.Trane is a business of
Ingersoll Rand. All trademarks referenced in this
document are the trademarks of their respective owners.
LonTalk is a registered trademark of Echelon Corporation.
BACnet is a registered trademark of ASHRAE.

Revision History
WSHP-SVX01N-EN (12 Sep 2014)
•

Edited Model Number, Electrical Data, Fan
Performance - 2 speed motor change

WSHP-SVX01N-EN

3

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2

Supply/Return Pipe Connections . . . . . . .60

Important Environmental Concerns . . . . . 2

Cleaning and Flushing the Water Loop . .61

Important Responsible Refrigerant Practices
2

Field Installed Power Wiring . . . . . . . . . . .61

Types of Hose Connections . . . . . . . . . . . .60

Main Unit Power Wiring . . . . . . . . . . . . . .61

Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Control Power Transformer . . . . . . . . . . .62

Model Number Description . . . . . . . . . . . . . . . 5
½ to 5 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Thermostat Location . . . . . . . . . . . . . . . . .62
Controls Using 24 VAC . . . . . . . . . . . . . . .62

Model Number Description . . . . . . . . . . . . . . . 6
6 to 25 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Blower Motor Speed-Tap Retrofit . . . . . . .63

Model Number Description . . . . . . . . . . . . . . . 7
½ to 6 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Air Flow Adjustment . . . . . . . . . . . . . . . . .64

Overview of Manual . . . . . . . . . . . . . . . . . . . . . 8
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . 8

Waterside Economizer Installation for GEH
and GEV 6 to 25 Ton Models . . . . . . . . . . .68

Compressor Nameplate . . . . . . . . . . . . . . . 8

Waterside Economizer Start-Up Sequence .70

Model Number Description . . . . . . . . . . . . 8

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . .72

General Information . . . . . . . . . . . . . . . . . . . . . 9

Pre-Start Checklist . . . . . . . . . . . . . . . . . . . . . . .92

Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Inspection Checklist . . . . . . . . . . . . . 13

Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
Initial Unit Start-up . . . . . . . . . . . . . . . . . . . .93

Jobsite Inspection Checklist . . . . . . . . . . 13

Start-Up Checklist and Log . . . . . . . . . . . .93

Jobsite Storage . . . . . . . . . . . . . . . . . . . . 13

Operating Pressures . . . . . . . . . . . . . . . . .93

Unit Dimensions and Weights . . . . . . . . . . . 14

Water Pressure Drop . . . . . . . . . . . . . . . .115

GEH and EXH Clearance Dimensions . . . 14

Water Volume . . . . . . . . . . . . . . . . . . . . . .117

GEV ½ to 5 tons and EXV ½ to 6 tons clearance dimensions . . . . . . . . . . . . . . . . . . . 15

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .118

Weight Distribution for Hanging the GEH and
EXH Model . . . . . . . . . . . . . . . . . . . . . . . . 55

Condensate Trap . . . . . . . . . . . . . . . . . . .118

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
General Installation Checks . . . . . . . . . . . 56
Main Electrical . . . . . . . . . . . . . . . . . . . . . 56
Supply-Air Ductwork . . . . . . . . . . . . . . . . 57
Return-Air Ductwork . . . . . . . . . . . . . . . . . 57

Hole Plug Installation . . . . . . . . . . . . . . . . .64
Waterside Economizer Installation . . . . . .65

Preventive Maintenance . . . . . . . . . . . . .118

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .119
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . .121
Warranty Information . . . . . . . . . . . . . . . . . . .131
Standard Warranty . . . . . . . . . . . . . . . . . .131
Extended Warranty . . . . . . . . . . . . . . . . .131

Ducted Panel . . . . . . . . . . . . . . . . . . . . . . . 57
Ducted Filter Rack . . . . . . . . . . . . . . . . . . . 58
Dual Filtration (GEH ½-5 ton and EXH ½-6
ton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Sound Attenuation Pad . . . . . . . . . . . . . . 59
Hanging the Horizontal Unit . . . . . . . . . . 59
Condensate Drain Connection . . . . . . . . . 59
4

WSHP-SVX01N-EN

Model Number Description
½ to 5 Ton
G

E

H

E

0

0

6

1

1

*

0

1

B

0

B

R

D

0

1

0

0

0

0

1

0

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26-36

Digits 1-3 — Unit Configuration
GEH = Standard Efficiency Horizontal
GEV = Standard Efficiency Vertical

Digit 16 — Return-Air
Arrangement

Digit 4 — Development Sequence

L = Left Return-Air Arrangement
R = Right Return-Air Arrangement

E = R-410A

Digit 17 — Control Types

Digits 5-7 — Nominal Capacity

0 = Basic 24V Controls
D = Deluxe 24V Controls
B =Tracer ZN524 Controls
F = UC400
G = UC400 w/ Wireless Comm

006 = ½Ton
009 = ¾Ton
012 = 1Ton
015 = 1¼Ton
018 = 1½Ton
024 = 2Ton

030 = 2½Ton
036 = 3Ton
042 = 3½Ton
048 = 4Ton
060= 5Ton

0 = Wall Mounted Location

Digit 8 — Voltage (Volts/Hz/
Phase)
0 = 115/60/1
1 = 208/60/1
2 = 230/60/1
3 = 208/60/3
4 = 460/60/3

Digit 18 — Tstat/Sensor
Location

5 = 575/60/3
6 = 220-240/50/1
7 = 265/60/1
8 = 230/60/3
9 = 380-415/50/3

Digit 9 — Heat Exchanger
1 = Copper-Water Coil
2 = Cupro-Nickel Water Coil
7 = Insulated Copper-Water Coil
8 = Insulated Cupro-Nickel Water Coil

Digit 10 — Current Design
Sequence
Digit 11 — Refrigeration Circuit

Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor
3 = Condensate Overflow and Filter
MaintenanceTimer
6 = Condensate Overflow and Fan Status
J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor

Digit 20 — Temperature Sensor
0 = None
1 = Entering Water Sensor

Digit 21 — Open
Digit 22 — Electric Heat
0 = No Electric Heat
1 = Internal Boilerless Electric Heat
4 = External Boilerless Electric Heat

Digit 23 — Open

0 = Heating and Cooling Circuit
2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer

Digit 24 — Filter Type

Digit 12 — Blower Configuration

Digit 25 — Acoustic
Arrangement

1 = Standard Blower Motor
2 = High Static Blower Motor

Digit 13 — Freeze Protection
A= 20°F Freezestat (extended range
geothermal)
B= 35°F Freezestat

Digit 14 —Open Digit = 0

1 = 1"Throwaway Filter
2 = 2"Throwaway Filter
4 = MERV 8
5 = MERV 13

0 = Enhanced Sound Attenuation
1 = Deluxe Sound Attenuation

Digits 26-36 — Does Not Apply
to GEH or GEV
00000000000 = Digits 26-36 are not
applicable to the GEH or GEV products

Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement
F = Front Supply-Air Arrangement
L = Left Supply-Air Arrangement
R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement

WSHP-SVX01N-EN

5

Model Number Description
6 to 25 Ton
G

E

H

E

0

7

2

1

1

*

0

A

0

0

A

B

D

0

0

0

0

0

0

1

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25-36

Digits 1-3 - Unit Configuration

Digit 13 - Freeze Protection

GEH = High Efficiency Horizontal
GEV = High Efficiency Vertical

A = 20°F Freezestat
B = 35°F Freezestat

Digit 4 - Development Sequence

Digit 14 - Open Digit = 0

E = R-410A

Digits 5-7 - Nominal Capacity

Digit 15 - Supply-Air
Arrangement

072 = 6Ton
090 = 7½Ton
120 = 10Ton
150 = 12½Ton

B = Back Supply-Air Arrangement
F = Front Supply-Air Arrangement
L = Left Supply-Air Arrangement
R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement

180 = 15Ton
240 = 20Ton
300 = 25Ton

Digit 8 - Voltage (Volts/Hz/
Phase)
1 = 208/60/1
2 = 230/60/1
3 = 208/60/3
4 = 460/60/3
5 = 575/60/3
6 = 220-240/50/1
7 = 265/60/1
8 = 230/60/3
9 = 380-415/50/3

B = Back Return-Air Arrangement
F = Front Return-Air Arrangement
L = Left Return-Air Arrangement
R = Right Return-Air Arrangement

Digit 17 - Control Types
D = Deluxe 24V Controls
B = Tracer ZN524 Controls
F = UC400
G = UC400 w/ Wireless Comm

Digit 18 - Open

1 = Copper-Water Coil
2 = Cupro-Nickel Water Coil
7 = Insulated Copper-Water Coil
8 = Insulated Cupro-Nickel Water Coil

0 = Wall Mounted Location

Digit 19 - Fault Sensors

0 = Heating and Cooling Circuit
2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
4 = Heating and Cooling Circuit with
HGR and WSE

0 = No Fault Sensor
1 = Condensate Overflow Sensor
2 = Filter MaintenanceTimer
3 = Condensate Overflow and Filter
MaintenanceTimer
4 = Fan Status Sensor
6 = Condensate Overflow and Fan
Status
H = Fan Status and Filter
MaintenanceTimer
J = Fan Status, Filter Maintenance
Timer and Condensate Overflow
Sensor

Digit 12 - Blower Configuration

Digit 20 - Open

A = Drive Package A (GEH/GEV)
B = Drive Package B (GEH/GEV)
C = Drive Package C (GEH/GEV)
D = Drive Package D (GEH/GEV)
E = Drive Package E (GEH/GEV)
F = Drive Package F (GEH/GEV)
G = Drive Package G (GEH/GEV)
H = Drive Package H (GEH/GEV)
J = Drive Package J (GEH/GEV)
1 = 2 Speed Drive Package A (GEH/GEV)
2 = 2 Speed Drive Package B (GEH/GEV)
3 = 2 Speed Drive Package C (GEH/GEV)
4 = 2 Speed Drive Package D (GEH/GEV)
5 = 2 Speed Drive Package E (GEH/GEV)
6 = 2 Speed Drive Package F (GEH/GEV)
7 = 2 Speed Drive Package G (GEH/GEV)
8 = 2 Speed Drive Package H (GEH/GEV)
9= 2 Speed Drive Package J (GEH/GEV)

0 = No AdditionalTemperature Sensor

Digit 11 - Refrigeration Circuit

6

00000000000 = Digits 25-36 are not
applicable to the GEH or GEV products

Digit 16 - Return-Air
Arrangement

Digit 9 - Heat Exchanger

Digit 10 - Current Design
Sequence

Digit 25-36 - Does Not Apply to
GEH or GEV

Digit 21 - Open
Digit 22 - Electric Heat
0 = No Electric Heat
4 = External Boilerless Electric Heat
5 = External Supplemental Electric
Heat

Digit 23 - Open
Digit 24 - Filter Type
1 = 1 in.Throwaway Filter
2 = 2 in.Throwaway Filter

WSHP-SVX01N-EN

Model Number Description
½ to 6 Ton
E

X

H

F

0

0

6

1

1

*

0

3

B

0

B

R

D

0

1

0

0

0

0

1

0

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26-36

Digits 1-3 — Unit Configuration
EXH = High Efficiency Horizontal
EXV = High Efficiency Vertical

Digit 16 — Return-Air
Arrangement

Digit 4 — Development Sequence

L = Left Return-Air Arrangement
R = Right Return-Air Arrangement

F

Digit 17 — Control Types

Digits 5-7 — Nominal Capacity
006 - 1/2 ton
009 - 3/4 ton
012 - 1 ton
015 - 1 ¼ ton
018 = 1½Ton
024 = 2Ton

030 = 2½Ton
036 = 3Ton
042 = 3½Ton
048 = 4Ton
060= 5Ton
070= 6Ton

Digit 8 — Voltage (Volts/Hz/
Phase)
1 = 208/60/1
2 = 230/60/1
3 = 208/60/3

4 = 460/60/3
7 = 265/60/1
8 = 230/60/3

D = Deluxe 24V Controls
B = Tracer™ ZN524 Controls
F = UC400
G = UC400 w/ Wireless Comm

Digit 18 — Tstat/Sensor
Location
0 = Wall Mounted Location

Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor
3 = Condensate Overflow and Filter
MaintenanceTimer
6 = Condensate Overflow and Fan Status
J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor

Digit 9 — Heat Exchanger

Digit 20 — Temperature Sensor

1 = Copper-Water Coil
2 = Cupro-Nickel Water Coil
7 = Insulated Copper Water
Coil/Suction Line
8 = Insulated Cupro-Nickel Water
Coil/Suction Line

0 = No AdditionalTemperature Sensor
1 = Entering Water Sensor

Digit 10 — Current Design
Sequence
Digit 11 — Refrigeration Circuit

Digit 21 — Open Digit
Digit 22 — Electric Heat
0 = No Electric Heat
1 = Internal Boilerless Electric Heat
4 = External Boilerless Electric Heat

Digit 23 — Open Digit

0 = Heating and Cooling Circuit
2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer

Digit 24 — Filter Type

Digit 12 — Blower Configuration

Digit 25 — Acoustic
Arrangement

3 = ECM Motor

Digit 13 - Freeze Protection
A = 20°F freezestat
B = 35°F freezestat

Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement

1=
2=
4=
5=

1"Throwaway Filter
2"Throwaway Filter
MERV 8
MERV13

0 = Enhanced Sound Attenuation
1 = Deluxe Sound Attenuation

Digits 26-36 — Does not Apply
to EXH or EXV
00000000000 Digits 26-36 are not
applicable to the EXH or EXV products

B = Back Supply-Air Arrangement
L = Left Supply-Air Arrangement
R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement

WSHP-SVX01N-EN

7

Overview of Manual
Note: One copy of this document ships with each unit and
is customer property. It must be retained by the
unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for HVAC systems. By carefully
reviewing the information within this manual and
following the instructions, the risk of improper operation
and/or component damage will be minimized.
Service and maintenance work should be performed by a
qualified technician and all electrical service and
maintenance work should be performed by a qualified
licensed electrician.

Unit Nameplate

Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.

Model Number Description
All products are identified by a multiple-character model
number that precisely identifies a particular type of unit. Its
use will enable the owner/operator, installing contractors,
and service engineers to define the operation, specific
components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial
number printed on the unit nameplate.

The unit nameplate is located on the outside of the control
box access panel at the front of the unit. It includes the unit
model number, serial number, electrical characteristics,
refrigerant charge, and other pertinent unit data.

8

WSHP-SVX01N-EN

General Information
Unit Description

Basic 24V Controls

Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and run tested for proper control
operation.

Safety devices for equipment containing the basic 24V
control option include a low-pressure switch to prevent
compressor operation during low temperature or low
suction activity.The switch is set to activate at refrigerant
pressure of 40 psig to fit most applications.

Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.

Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak
tested to assure there is no cross leakage between the
water tube (copper/cupro-nickel) and refrigerant gas (steel
tube).
Table 1.

High/Low pressure switch
Trip

Recover

Unit

LP

40 +/-4

56 +/-4

psig

HP

650 +/-10

550 +/-10

psig

A high pressure switch prevents compressor operation
during high or excessive discharge pressures exceeding
650 psig.
The lockout relay will disable the compressor on a high or
low pressure condition. For units that contain a
condensate overflow switch option, a condensate
overflow condition will also disable the compressor
through the lockout relay.The relay may be reset at the
thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay.
This feature will drive dry contacts only, and cannot be
used to drive field installed control inputs.Trane provides
a 3½-minute time delay for compressor control.

Deluxe 24V Controls (option)
Controls
Basic 24V control is available for the GEH/V ½ -5 ton
models and the Deluxe 24V control option is available for
all unit sizes.Tracer™ ZN524, LonTalk® certified control
option is available for all unit sizes. UC400 and UC400 with
wireless comm BACnet is available in all unit sizes.
All power wiring to the equipment is made at the unit
contactor for ½- 5 ton, 1-phase units. For 3-phase units all
power wiring to the equipment is made to the contactor or
power block. For EXH/V070 units all power wiring to the
equipment is made to the power block. For the GEH/V 6-25
tons units all power wiring is made to the high voltage
terminal block. All low-voltage wiring is made at the unit’s
low voltage terminal board. EXH and EXV 460V units
require a neutral wire.

System Input Devices and Functions
A thermostat, zone sensor, or building automation system
is required to operate the water-source heat pump.The
flexibility of having several mode capabilities depends
upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V
control systems may be located in the back of this manual.
All digital control troubleshooting tips and connection
diagrams are located in WSHP-PRB002-EN (ZN524).

Units containing the Deluxe 24V control design will
incorporate a microprocessor-based control board.The
Trane® microprocessor board is factory wired to a
terminal strip to provide all necessary terminals for field
connection.The deluxe board is equipped with a random
start relay, anti-short cycle timer, brown out protection,
compressor disable, condensate overflow, unit safety
control, diagnostics, and a generic relay (which may be
available for field use). See Table 65, p. 119 for diagnostic
information and Figure 59, p. 62 and Figure 60, p. 63 for
thermostat connections.

Tracer™ UC400
TheTracer™ UC400 is a BTL Listed BACnet® controller
that can operate stand- alone or within a Building
Automations system such asTracer™ SC.

Tracer ZN524 Controls (option)
The digital ZN524 controller is designed to support the ½
to 25 ton water-source heat pumps in either a standalone,
peer-to-peer with aTracer Loop Controller, or as a full
building automation (open protocol) system.
For installation, operation and diagnostics see WSHPPRB002-EN (ZN524).

Pump Module (field installed accessory)
The pump module shall consist of either a single or dual 1/
6 HP bronze pump and a brass three-way shut-off valve.
Cast iron pumps are also acceptable.The pump module
kits shall contain the necessary components for the
installation, operation and maintenance of the water
circuit of a closed-loop distributed pumping application.

WSHP-SVX01N-EN

9

General Information
Waterside Economizer (Option)

Hot Gas Reheat (option)

Instructions for mechanical connection of the waterside
economizer to the water-source heat pump may be found
in the dimensional section of this manual.

With the reheat option, the return-air from the space is
conditioned by the air-to-refrigerant coil, then reheated by
the reheat coil to control not only the space temperature,
but to also reduce the relative humidity of the space.When
operating in the reheat mode (meaning the sensible
temperature has been met in the space), the humidistat
signals the reheat relay coil to energize, allowing the high
pressure refrigerant gas to flow from the compressor
through the reheat valve, into the reversing valve, or
reheat coil.

The waterside economizer is designed to begin
economizing mode when water temperatures fall below
the field adjustable temperature of 25, 35, 45, 55 or 60°F
(for the Deluxe control option), or below the programmed
set-point (for the ZN524 control option).
When the temperature is less than the setpoint, fluid will
flow into the economizing coil, while simultaneously
halting mechanical operation of the compressor.
Mechanical cooling will continue on a call for a second
stage from the thermostat or system control. Entering
water temperature sensor is factory provided for field
installation on the entering water side of the coil.

Boilerless Control/Electric Heat (Option)
Systems that do not contain a boiler may contain a
boilerless control with electric heat.Trane® offers both a
factory mounted electric heat option, and a field mounted
duct heater option.
If the ½-5 ton GEH, GEV and EXH/V070 unit incorporates
the factory mounted option, the unit will ship from the
factory with an internally mounted nichrome open wire
heating element, designed to start-up electric heat as the
systems primary heat in the event entering water
temperature falls below 55°F. Once the entering water
temperature rises above 60°F, the boilerless controller
returns the unit to normal compressor heating operation,
and locks out the electric heater.
For units comprised of the field installed duct heater
option, the unit will ship from the factory with controls
available to interface with the field provided electric heat
selection.
Note: For geothermal applications, the boilerless
controller has an adjustable setting of 25, 35, 45, 55,
and 60 degrees.

Supplemental or Boilerless Electric Heat
(option)
The GEH/V 6-25 ton models which contain boilerless
control electric heat or supplemental electric heat will
contain the controls interface ONLY for field provided
electric heat selection.The heater for this model shall be
external to the equipment by the contractor for ease of
installation. All power connections for the electric heater
will be completely separate from the unit for field supplied
electric heat.

A switching relay has been provided for the reheat
application to adjust the blower motor from normal
operation to low speed when the hot gas reheat is
energized (for ½ -5 ton and EXH/V070 equipment only).
Note: A high static blower motor is required to support
the hot gas reheat option for the GEH/V ½ -5 ton.
Note: Units containing the hot gas reheat option should
not be used as a make-up air unit.

2 Speed Blower Motor (option)
The 6-25 ton GEH/V models have indoor blowers that are
available with 2 speed motors, selectable in the model
number (Digit 12, drive packages one to nine). High speed
airflow matches the single speed motor airflow,
referenced in the Fan Performance tables. Low fan speed
airflow is approximately 50% of high fan speed airflow.
The 6-25 ton GEH/V two-speed blower motors are
available with the following options: Deluxe 24V or UC400
controls, Heat Pump (HP) or HP w/Hot Gas Reheat or HP w/
Waterside Economizer. Not available with Boilerless or
Supplemental Electric Heat.
Table 2.

6 to 25 ton GEH/V fan speed for two-speed
drive packages one to nine
Compresso Compresso
r1
r2
Fan Speed

RV State

Fan

Heat

OFF

OFF

OFF

OFF

Heat

ON

OFF

OFF

HIGH

Heat

ON

ON

OFF

HIGH

Heat

ON

ON

ON

HIGH

Cool

OFF

OFF

OFF

OFF

Cool

ON

OFF

OFF

LOW

Cool

ON

ON

OFF

LOW

Cool

ON

ON

ON

HIGH

Note: When the unit has boilerless control, the electric
heat is not used as supplemental electric heat, but
as a primary heat.

10

WSHP-SVX01N-EN

General Information
Table 3.

Refrigerant charge

Model
(60 Hz)

Heat Pump
(oz)/(Kg)

Heat Pump w/HGR
(oz)/(Kg)

Circuit 1

Circuit 2

Circuit 1

GEHE006

25.3 / .717

-----

26.8 / .760

Circuit 2
-----

GEHE009

26.0 / .737

-----

27.5 / .780

-----

GEHE012

28.5 / .808

-----

30.5 / .865

-----

GEHE015

29.0 / .822

-----

30.5 / .865

-----

GEHE018

36.5 / 1.035

-----

39.5 / 1.120

-----

GEHE024

39.0 / 1.106

-----

42.0 / 1.191

-----

GEHE030

44.0 / 1.247

-----

46.5 / 1.318

-----

GEHE036

50.0 / 1.417

-----

53.5 / 1.517

-----

GEHE042

57.0 / 1.616

-----

60.5 / 1.715

-----

GEHE048

61.0 / 1.729

-----

65.5 / 1.857

-----

GEHE060

73.0 / 2.070

-----

77.5 / 2.197

-----

GEVE006

25.7 / .789

-----

27.2 / .771

-----

GEVE009

26.5 / .751

-----

28.0 / .794

-----

GEVE012

29.5 / .836

-----

31.5 / .893

-----

GEVE015

27.5 / .780

-----

29.5 / .836

-----

GEVE018

37.0 / 1.049

-----

40.0 / 1/134

-----

GEVE024

39.0 / 1.106

-----

41.5 / 1.177

-----

GEVE030

44.5 / 1.262

-----

47.0 / 1.332

-----

GEVE036

51.0 / 1.446

-----

54.5 / 1.545

-----

GEVE042

54.0 / 1.531

-----

57.5 / 1.630

-----

GEVE048

61.0 / 1.729

-----

66.0 / 1.871

-----

GEVE060

74.0 / 2.098

-----

79.5 / 2.254

-----

GEHE072

55 / 1.559

55 / 1.559

59 / 1.673

55 / 1.559

GEHE090

64 / 1.814

54 / 1.531

68 / 1.928

54 / 1.531

GEHE120

86 / 2.438

86 / 2.438

90 / 2.551

86 / 2.438

GEHE150

136 / 3.856

136 / 3.856

144 / 4.082

136 / 3.856

GEHE180

126 / 3.572

126 / 3.572

134 / 3.799

126 / 3.572

GEVE072

58 / 1.644

58 / 1.644

62 / 1.758

58 / 1.644

GEVE090

83 / 2.353

75 / 2.126

87 / 2.466

75 / 2.126

GEVE120

88 / 2.495

88 / 2.495

92 / 2.608

88 / 2.495

GEVE150

122 / 3.459

122 / 3.459

130 / 3.685

122 / 3.459

GEVE180

128 / 3.629

128 / 3.629

136 / 3.856

128 / 3.629

GEVE240

284 / 8.051

284 / 8.051

292 / 8.278

284 / 8.051

GEVE300

260 / 7.371

260 / 7.371

267 / 7.569

260 / 7.371

EXHF006

25.3 / 0.717

-----

26.8 / 0.760

-----

EXHF009

26.0 / 0.737

-----

27.5 / 0.780

-----

EXHF012

28.5 / 0.808

-----

30.5 / 0.865

-----

EXHF015

29.0 / 0.822

-----

30.5 / 0.865

-----

EXHF018

45.0 / 1.276

-----

48.0 / 1.361

-----

EXHF024

50.5 / 1.432

-----

53.0 / 1.503

-----

EXHF030

53.0 / 1.503

-----

56.0 / 1.588

-----

EXHF036

70.0 / 1.984

-----

73.0 / 2.070

-----

EXHF042

81.0 / 2.296

-----

85.5 / 2.424

-----

EXHF048

83.0 / 2.353

-----

87.5 / 2.481

-----

continued on next page

WSHP-SVX01N-EN

11

General Information
Table 3.

Refrigerant charge (continued)

Model
(60 Hz)

12

Heat Pump
(oz)/(Kg)

Heat Pump w/HGR
(oz)/(Kg)

EXHF060

114.0 / 3.232

-----

118.5 / 3.359

-----

EXHF070

122.0 / 3.459

-----

127.0 / 3.600

-----

EXVF006

25.7 / 0.729

-----

27.2 / 0.771

-----

EXVF009

26.5 / 0.751

-----

28.0 / 0.794

-----

EXVF012

29.5 / 0.836

-----

31.5 / 0.893

-----

EXVF015

30.0 / 0.850

-----

32.0 / 0.907

-----

EXVF018

45.0 / 1.276

-----

48.0 / 1.361

-----

EXVF024

52.0 / 1.474

-----

54.5 / 1.545

-----

EXVF030

53.0 / 1.503

-----

56.0 / 1.588

-----

EXVF036

70.0 / 1.984

-----

73.0 / 2.070

-----

EXVF042

81.0 / 2.296

-----

86.0 / 2.438

-----

EXVF048

83.0 / 2.353

-----

88.5 / 2.509

-----

EXVF060

114.0 / 3.232

-----

119.5 / 3.388

-----

EXVF070

122.0 / 3.459

-----

128.0 / 3.629

-----

WSHP-SVX01N-EN

Pre-Installation
Jobsite Storage
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers may also cause
respiratory, skin or eye irritation.

Unit Inspection Checklist
•

Unpack all components of the kit.

•

Check carefully for any shipping damage. If any
damage is found it must be reported immediately and
a claim made against the transportation company.

Important:

Equipment is shipped FOB (Free on Board)
at the manufacturer.Therefore, freight
claims for damages against the carrier must
be initiated by the receiver.

•

Visually inspect the components for shipping damage
as soon as possible after delivery, before it is stored.
Concealed damage must be reported within 15 days.

•

If concealed damage is discovered, stop unpacking the
shipment.

•

Do not remove damaged material from the receiving
location.Take photos of the damage, if possible.The
owner must provide reasonable evidence that the
damage did not occur after delivery.

•

Notify the carrier’s terminal of damage immediately by
phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.

•

WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification
site for microbial growth (mold), which may cause odors
and serious health related indoor air quality problems. If
there is evidence of microbial growth (mold) on the
interior insulation, remove or replace the insulation prior
to operating the system. Failure to remove microbial
growth could result in serious health problems.
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources from growing, the unit should be
stored indoors. If indoor storage is not possible, the
following provisions for outdoor storage must be met:
•

Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.

•

Cover the unit(s) with a water proof tarp to protect
them from the elements.

•

Make provisions for continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces. Wet interior unit insulation can become an
amplification site for microbial growth (mold) which
has been determined to be a cause of odors and
serious health related indoor air quality problems.

•

Store units in the normal UP orientation to maintain oil
in the compressor.

•

Horizontal units may be stacked no more than three
units high. Do not stack the vertical unit configurations.

Do not attempt to repair any damaged parts until the
parts are inspected by the carrier’s representative.

Jobsite Inspection Checklist
Always perform the following checks before
accepting a unit:
•

Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).

•

Verify that the power supply complies with the unit
nameplate specifications.

•

Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once the bill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.

WSHP-SVX01N-EN

13

Unit Dimensions and Weights
GEH and EXH Clearance Dimensions
Access to the unit for service purposes should be provided
at installation. All ½-5 tons and EXH070 configurations
(see Figure 1, p. 14) require an 18 in. (457 mm) surround
clearance from other mechanical and electrical equipment
(where shown) to enable panel removal from the unit for
service/maintenance ability. NEC requires 36 in. clearance
on the control panel side of the unit. Some local codes

require a greater service clearance than listed below.
Check all code requirements prior to unit installations.
Equipment containing a same-side supply/return
combination requires a 3 in. (229 mm) limitation on one
side. Access to theTXV may not be possible with this 3 in.
(229 mm) clearance.This configuration is typically applied
in a corridor installation, where space limitations force the
left or right side of the unit against a wall.

Figure 1. GEH ½ to 5 tons and EXH ½ to 6 tons clearance

18" (457)
(3-SIDES)

18" (457)
(3-SIDES)

18" (457)
(3-SIDES)

LEFT RETURN
RIGHT SUPPLY

LEFT RETURN
BACK SUPPLY

LEFT RETURN
LEFT SUPPLY

3"
(76)

UNIT FRONT

RIGHT RETURN
BACK SUPPLY

36"
(914)

18" (457)
(3-SIDES)

36"
(914)

UNIT FRONT

36"
(914)

UNIT FRONT

18" (457)
(3-SIDES)

18" (457)
(3-SIDES)

RIGHT RETURN
LEFT SUPPLY

RIGHT RETURN
RIGHT SUPPLY

Figure 2.

UNIT FRONT
36"
(914)

Service clearance dimensions for the GEH 6-15 tons
horizontal (see Figure 2, p. 14) includes a two side access
appropriate for control and blower motor/wheel access.
Some local codes require a greater service clearance than
listed below. Check all code requirements prior to unit
installations.

GEH 6-15 tons clearance

CONTROL BOX

36"
(914)
SERVICE
CLEARANCE

20"
(508)
SERVICE
CLEARANCE

14

UNIT FRONT
36"
(914)

UNIT FRONT
36"
(914)

3"
(76)

TOP VIEW

BLOWER ACCESS
PANEL

WSHP-SVX01N-EN

Unit Dimensions and Weights

GEV ½ to 5 tons and EXV ½ to 6 tons
clearance dimensions
Access to the unit for service purposes should be provided
at installation. A 24 in. surround clearance (see Figure 3,
p. 15) from other mechanical and electrical equipment
(where shown) is recommended for all configurations.
This will enable panel removal from the unit for service/
maintenance. Some local codes require a greater service
clearance than listed below. Check all code requirements
prior to unit installations. Units in a free return application
will require more than a 12 in. minimum clearance to
provide proper air flow to the units air-to-refrigerant coil.
Pictured in Figure 3, p. 15 minimum 1” clearance on return
side with properly attached duct work.

A 36 in. service clearance is required for all configurations
at the unit front. It is recommended that 20 in of service
clearance for the sides (see Figure 4, p. 15) from other
mechanical and electrical equipment (where shown).The
unit may be serviced through the front access panel or
remaining open sides. Some local codes require a greater
service clearance than listed below. Check all code
requirements prior to unit installations.
Figure 4. GEV 6–10 tons clearance

FRONT RETURN
TOP SUPPLY

GEV ½-5 tons and EXV ½-6 tons clearance
dimensions
1"
(25.4)

Figure 3.

GEV 6–10 Tons Clearance Dimensions

ACCESS PANEL FOR
SHEAVES AND BELTS

20"
(508)
SERVICE
CLEARANCE

36"
(914)
SERVICE
CLEARANCE

GEV 12½–25 Tons Clearance Dimensions

24"
(610)

Figure 5, p. 15 outlines service clearances. A 36 in. service
clearance is required for all configurations at the unit front.
A 24 in. service clearance (see Figure 3, p. 15) from other
mechanical and electrical equipment (where shown) is
recommended for all configurations.The unit may be
serviced through the front access panel. Some local codes
require a greater service clearance than listed below.
Check all code requirements prior to unit installations.

UNIT FRONT

36"
(914)

RIGHT RETURN
TOP/BACK SUPPLY

1"
(25.4)

Figure 5. GEV 12½–25 tons clearance

1"
(25.4)

18" (457)

FRONT RETURN-AIR
BACK SUPPLY-AIR

CONTROL BOX
NEC REQ.
MIN. 36" (914)
C.B. TO WALL
CLEARANCE

1"
(25.4)

WSHP-SVX01N-EN

36"
(914)

UNIT FRONT

UNIT FRONT

16" (406) TO
FILTER FRAME
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 22" (559). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

24"
(610)

LEFT RETURN
TOP/BACK SUPPLY

15

Unit Dimensions and Weights
Figure 6. Left return/left supply (GEH/EXH)

P

B

TOP
R

S

N
A
FXG
OPENING

H

Q

PANEL

HI VOLT

L (W.O.)

WCI mounting location
LO VOLT

1/2"
(13)

3/4" (19) NPTI

J

H

BACK

LEFT SIDE
D

M (W.I.)
1" (25.4)

K

DRAIN

7"
(178)

ACCESS

FRONT

1 3/8" (35)

C

REFRIG
AND
CONTROL
ACCESS

6 3/4"
(171)

1" (25.4)

BLOWER

E

14"
(356")

RIGHT SIDE

Table 4.
GEH
Unit

Left return/left supply (GEH/EXH)
A

B

Hi-048,
060

40
(1016)
40
(1016)
46
(1168)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

EXH
Unit

A

B

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

006, 009
012, 015
018
024, 030
036, 042
Std-048

006-009
012-015
018-024
030-036
042-070
070

C

D(a)

E

FxG

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
6-7/8 x 9-7/8
(381) (508) (381)
(175) x (251)
18
23
18
8-1/4 x 9-3/4
(457) (584) (457)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

C

D(a)

E

FxG

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
8-1/4 x 9-3/4
(381) (508) (381)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
3/4
(19)
1-3/8
(35)
1-3/8
(35)
1
(25)
1-1/2
(38)
1-1/2
(38)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/4
(108)
4-1/4
(108)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
3/4
(19)
1-3/8
(35)
1
(25)
1-1/2
(38)
1-1/2
(38)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
access on either side of the filter.
(a) Return air opening dimension
(b) Filter rack dimension

16

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 7.

Left return/back supply (GEH/EXH)

P

B

TOP
S

R

A

1"(25.4)

C

BLOWER
H

REFRIG
AND
CONTROL
ACCESS

ACCESS

Q

PANEL

L (W.O.)

HI VOLT
WCI mounting location
LO VOLT

BACK

LEFT SIDE
D

1/2"
(13)

M (W.I.)

1" (25.4)

J

K

H
DRAIN
3/4" (19) NPTI

7"
(178)

OPENING

FRONT

E

1 3/8" (35)

N

6 3/4"
(171)

FXG

14"
(356)

RIGHT SIDE

Table 5.
GEH
Unit

Left return/back supply (GEH/EXH)
A

40
(1016)
40
012, 015
(1016)
46
018
(1168)
46
024, 030
(1168)
50
036, 042
(1270)
58
Std-048
(1473)
58
Hi-048, 060
(1473)
006, 009

EXH Unit
006-009
012-015
018-024
030-036
042-070
070

B
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

A

B

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

C

D(a)

E

FxG

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
6-7/8 x 9-7/8
(381) (508) (381)
(175) x (251)
18
23
18
8-1/4 x 9-3/4
(457) (584) (457)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

C

D(a)

E

FxG

15
20
15
6 -7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
8-1/4 x 9-3/4
(381) (508) (381)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 231/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
3/4
(19)
1-3/8
(35)
1-3/8
(35)
1
(25)
1-1/2
(38)
1-1/2
(38)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4
(102)
9-3/4
(248)
9-3/4
(248)

1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension

WSHP-SVX01N-EN

17

Unit Dimensions and Weights
Figure 8. Left return/right supply (GEH/EXH)

P

B

TOP
S

R
N
A

BLOWER
ACCESS
PANEL

REFRIG
AND
CONTROL
ACCESS

Q
L (W.O.)

HI VOLT

7"
(178)

1" (25.4)

D

6 3/4"
(171)

E

WCI mounting location

1" (25.4)

BACK

1/2"
(13)

DRAIN
3/4" (19) NPTI

LEFT SIDE
FXG
OPENING

C

1 3/8" (35)

M (W.I.)

LO VOLT

FRONT

H
14"

RIGHT SIDE
K

H

Table 6.

Left return/right supply (GEH/EXH)

GEH Unit

A

40
006, 009
(1016)
40
012, 015
(1016)
46
018
(1168)
46
024, 030
(1168)
50
036, 042
(1270)
58
Std-048
(1473)
58
Hi-048, 060
(1473)

EXH Unit
006-009
012-015
018-024
030-036
042-070
070

J

B
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

A

B

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

C

D(a)

E

FxG

15
20
15
(381) (508) (381)
15
20
15
(381) (508) (381)
18
23
18
(457) (584) (457)
18
23
18
(457) (584) (457)
19
25
20
(483) (635) (508)
21 29-1/2 23-1/2
(533) (597) (749)
21 29-1/2 23-1/2
(533) (597) (749)

6-7/8 x 8 (175) x
(203)
6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)
13-1/8 x 11-3/8
(333) x (289)
13-7/8 x 13-7/8
(352) x (352)

D(a)

FxG

C

E

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
8-1/4 x 9-3/4
(381) (508) (381)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21 29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21 29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

H

J

11-1/2 4-1/2
(292) (114)
11-1/2 4-1/4
(292) (108)
13-1/2 4-3/4
(343) (121)
13-1/2 4-3/4
(343) (121)
17
4 (102)
(432)
18
5-1/4
(457) (133)
18
5-1/4
(457) (133)

K
1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be
possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension

18

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 9. Right return/left supply (GEH/EXH)
S

R

P

B

TOP

N
A

1" (25.4)

BLOWER
ACCESS
PANEL

D

FXG
OPENING

H

REFRIG
AND
CONTROL
ACCESS

6 3/4"
(171)

E

Q

HI VOLT
WCI mounting location

LEFT SIDE

C

L (W.O.)

FRONT
M (W.I.)

7" (178)

DRAIN
3/4" (19) NPTI

1/2"
(13)

J

BACK

1"(25.4)

K

LO VOLT

H

14"
(356)

1 3/8"(35)

RIGHT SIDE

Table 7.
GEH Unit

Right return/left supply (GEH/EXH)
B

C

D(a)

20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

15
(381)
15
(381)
18
(457)
18
(457)
19
(483)
21
(533)
21
(533)

20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)

A

B

C

D(a)

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

15
(381)
15
(381)
18
(457)
19
(483)
21
(533)
21
(533)

20
(508)
20
(508)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)

A

40
006, 009
(1016)
40
012, 015
(1016)
46
018
(1168)
46
024, 030
(1168)
50
036, 042
(1270)
58
Std-048
(1473)
58
Hi-048, 060
(1473)

EXH Unit
006-009
012-015
018-024
030-036
042-070
070

E

FxG

15
6-7/8 x 8
(381)
(175) x (203)
15
6-7/8 x 9-7/8
(381)
(175) x (251)
18
8-1/4 x 9-3/4
(457)
(210) x (248)
18
8-1/4 x 11-3/8
(457)
(210) x (289)
20
10-1/2 x 13-1/2
(508)
(267) x (343)
23-1/2 13-1/8 x 11-3/8
(749)
(333) x (289)
23-1/2 13-7/8 x 13-7/8
(749)
(352) x (352)

E

FxG

15
6-7/8 x 8
(381)
(175) x (203)
15
8-1/4 x 9-3/4
(381)
(210) x (248)
18
8-1/4 x 11-3/8
(457)
(210) x (289)
20
10-1/2 x 13-1/2
(508)
(267) x (343)
23-1/2 13-1/8 x 11-3/8
(749)
(333) x (289)
23-1/2 13-7/8 x 13-7/8
(749)
(352) x (352)

H
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

J

K

4-1/2
1-3/4
(114)
(45)
4-1/4
3/4 (19)
(108)
4-3/4
1-3/8
(121)
(35)
4-3/4
1-3/8
(121)
(35)
4
1
(102)
(25)
5-1/4
1-1/2
(133)
(38)
5-1/4
1-1/2
(133)
(38)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
3/4
(19)
1-3/8
(35)
1
(25)
1-1/2
(38)
1-1/2
(38)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension

WSHP-SVX01N-EN

19

Unit Dimensions and Weights
Figure 10. Right return/back supply (GEH/EXH)
S

R

P

B

TOP

N
A

FXG
OPENING

1" (25.4)

C

E

D

BLOWER
ACCESS
PANEL

HI VOLT

REFRIG
AND
CONTROL
ACCESS

14"
(356)

Q

WCI mounting location

L (W.O.)

J

DRAIN
3/4" (19) NPTI

BACK

LEFT SIDE

FRONT

M (W.I.)

1" (25.4)
6 3/4" (171)
1/2" (13)

LO VOLT

H

K

1 3/8" (35)

RIGHT SIDE

7"
(178)

H

Table 8.
GEH
Unit

Right return/back supply (GEH/EXH)
A

B

C

D(a)

E

FxG

H

J

K

Hi-048,
060

40
(1016)
40
(1016)
46
(1168)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

15
(381)
15
(381)
18
(457)
18
(457)
19
(483)
21
(533)
21
(533)

20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)

15
(381)
15
(381)
18
(457)
18
(457)
20
(508)
23-1/2
(749)
23-1/2
(749)

8 x 6-3/4
(203) x (171)
9-1/2 x 6-3/4
(241) x (171)
9-1/2 x 8-1/8
(241) x (206)
11-1/4 x 8-1/4
(286) x (210)
13-1/2 x 10-1/2
(343) x (267)
13-1/8 x 11-1/4
(333) x (286)
13-1/2 x 13-3/4
(343) x (349)

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/2
(114)
4-3/4
(121)
4-3/4
(121)
4
(102)
5-1/8
(130)
5-1/8
(130)

1-5/8
(41)
1-5/8
(41)
3-1/4
(83)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

EXH
Unit

A

B

C

D(a)

E

FxG

H

J

K

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4
(102)
9-3/4
(248)
9-3/4
(248)

1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

006,009
012,015
018
024,030
036,042
Std-048

006-009
012-015
018-024
030-036
042-070
070

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
8-1/4 x 9-3/4
(381) (508) (381)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension
(b) Filter rack dimension

20

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 11. Right return/right supply (GEH/EXH)
S

R

P

B

TOP

N
A

BLOWER
ACCESS
PANEL

D

6 3/4" (171)

1" (25.4)

E

C

REFRIG
AND
CONTROL
ACCESS

Q

HI VOLT
WCI mounting location
LO VOLT

FRONT

L (W.O.)
M (W.I.)

1/2"
(13)

DRAIN
3/4" (19) NPTI

FXG
OPENING

1"
(25.4)

LEFT SIDE

BACK

H

Table 9.

A

40
006, 009
(1016)
40
012, 015
(1016)
46
018
(1168)
46
024, 030
(1168)
50
036, 042
(1270)
58
Std-048
(1473)
58
Hi-048, 060
(1473)

EXH Unit

012-015
018-024
030-036
042-070
070

J

Right return/right supply (GEH/EXH)

GEH Unit

006-009

H

RIGHT SIDE

K

7" (178)
1 3/8" (35)

14"
(356)

B
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)

A

B

40
(1016)
40
(1016)
46
(1168)
50
(1270)
58
(1473)
58
(1473)

20
(508)
20
(508)
23
(584)
25
(635)
33
(838)
39
(991)

C

D(a)

E

FxG

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
6-7/8 x 9-7/8
(381) (508) (381)
(175) x (251)
18
23
18
8-1/4 x 9-3/4
(457) (584) (457)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

C

D(a)

E

FxG

15
20
15
6-7/8 x 8
(381) (508) (381)
(175) x (203)
15
20
15
8-1/4 x 9-3/4
(381) (508) (381)
(210) x (248)
18
23
18
8-1/4 x 11-3/8
(457) (584) (457)
(210) x (289)
19
25
20
10-1/2 x 13-1/2
(483) (635) (508)
(267) x (343)
21
29-1/2 23-1/2 13-1/8 x 11-3/8
(533) (597) (749)
(333) x (289)
21
29-1/2 23-1/2 13-7/8 x 13-7/8
(533) (597) (749)
(352) x (352)

H

J

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4-3/4
(121)

K

1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
3-1/4
(83)
1
4 (102)
(25)
5-1/4 1-1/2
(133) (38)
5-1/4 1-1/2
(133) (38)

H

J

K

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
17
(432)
18
(457)
18
(457)

4-1/2
(114)
4-1/4
(108)
4-3/4
(121)
4
(102)
5-1/4
(133)
5-1/4
(133)

1-3/4
(45)
2-3/4
(70)
3-1/4
(83)
1
(25)
1-1/2
(38)
1-1/2
(38)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

L
M
NPTI NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25)
1
(25)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

N

P

Q

R(b)

S

38-3/4
(984)
38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)
56-3/4
(1441)

18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)

13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)

18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)

3-1/4
(83)
3-1/4
(83)
4-1/4
(108)
3-1/4
(83)
5-1/2
(140)
5-1/2
(140)

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. 2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clearance from
other mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
access on either side of the filter.
(a) Return air opening dimension
(b) Filter rack dimension

Note: It is recommended to order a bottom access filter rack with right return/right supply combination due to potential
problem with return air filter removal.

WSHP-SVX01N-EN

21

Unit Dimensions and Weights
Figure 12. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
D
L

F

K
D

E
M

J
TOP

BLOWER
ACCESS
H

B
COMP/CONTROL
ACCESS

W.O.

WCI mounting location

DRAIN

HI VOLT
8 3/4"
(222)

12"
9 1/2"
(305) (241)
G
3 5/8"
(92)

LO VOLT
3 5/8"
(92)

LEFT SIDE

W.I.

A

C

FRONT

RIGHT SIDE

Table 10. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I. W.O. Drain
NPTI NPTI FPT

GEV Unit

A

B

C

D

E

F

G

H

J

K

L

M

006-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

4
(102)

5-3/4
(146)

9-1/2
(241)

15
(381)

17
(432)

6-7/8
(175)

8
(203)

3/4
(19)

1/2
(12.7)

1/2
(12.7)

3/4
(19)

018, 024, 030

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

4
(102)

4
(1021)

9-1/2
(241)

23-3/4
(603)

17
(432)

8-1/4
(368)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

036, 042

24-1/2
(622)

41-7/8
(1064)

26-1/2
(673)

18
(457)

3-1/4
(83)

5-3/4
(146)

9-1/2
(241)

19
(483)

23
(584)

10-1/2
(267)

13-1/2
(343)

1/4
(6)

3/4
(19)

3/4
(19)

3/4
(19)

Std-048

26-1/2
(673)

46-7/8
(1191)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-7/8
(352)

13-7/8
(352)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

Hi-048, 060

26-1/2
(673)

46-7/8
(1191)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-1/8
(333)

11-3/8
(289)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

EXV Unit

A

B

C

D

E

F

G

H

J

K

L

M

006-009

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

4
(102)

5-3/4
(146)

9-1/2
(241)

15
(381)

17
(432)

6-7/8
(175)

8
(203)

3/4
(19)

1/2
(13)

1/2
(13)

3/4
(19)

012-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

5-1/2
(140)

5-5/8
(142)

9-1/2
(241)

15
(381)

17
(432)

8-1/4
(210)

9-3/4
(248)

3/4
(19)

1/2
(13)

1/2
(13)

3/4
(19)

018-024

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

4
(102)

4
(1021)

9-1/2
(241)

23-3/4
(603)

17
(432)

8-1/4
(368)

11-3/8
(289)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

030-036

24-1/2
(622)

41-7/8
(1064)

26-1/2
(673)

18
(457)

3-1/4
(83)

5-3/4
(146)

9-1/2
(241)

19
(483)

23
(584)

10-1/2
(267)

13-1/2
(343)

1/4
(6)

3/4
(19)

3/4
(19)

3/4
(19)

042-060

26-1/2
(673)

46-7/8
(1191)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-7/8
(352)

11-3/8
(289)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

070

26-1/2
(673)

50-7/8
(1292)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-1/8
(333)

11-3/8
(289)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

9-3/4
(248)
11-3/8
(289)

W.I. W.O. Drain
NPTI NPTI FPT

Notes:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

22

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 13. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence

D

E
M

j
TOP

F

BLOWER
ACCESS

D
H

B

COMP/CONTROL
ACCESS

WCI mounting location

W.O.
DRAIN

HI VOLT
8 3/4"
(222)

12"
(305)

LO VOLT
3 5/8"
(92)

9 1/2"
(241)
G
3 5/8"
(92)

W.I.

A

LEFT SIDE

C

FRONT

RIGHT SIDE

Table 11. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
GEV Unit

A

B

C

D

E

F

006-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

4
1-3/4
(102)
(44)
006-009
006-009
11-1/2
(292)
4-3/4
3-3/4
(121)
(95)
012-015 012-015

018, 024,
030

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

24-1/2
(622)
26-1/2
Std-048
(673)
26-1/2
Hi-048, 060
(673)

41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)

26-1/2
18 (457)
(673)
30-1/2
18 (457)
(775)
30-1/2
18 (457)
(775)

036, 042

EXV Unit
006-009
012-015
018-024
030-036
042-060
070

G

H

J

K

L

M

9-1/2
(241)

15 (381)

17
(432)

6-7/8
(175)

8
(203)

3/4
(19)

4
(102)

3-7/8
(98)

9-1/2
(241)

3-1/4
(83)
4-1/4
(108)
4-1/4
(108)

1-7/8
(48)
2
(51)
2
(51)

9-1/2
(241)
9-1/2
(241)
9-1/2
(241)

23-3/4
17 (432)
(603)
19 (483) 23 (584)
27-7/8
(708)
27-7/8
29 (737)
(708)

29 (737)

W.I.
NPTI

W.O. Drain
NPTI FPT

1/2 (13) 1/2 (13)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

10-1/2
(267)
13-7/8
(352)
13-1/8
(333)

9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)

1/4
(6)
1/2
(13)
1/2
(13)

3/4
(19)

3/4
(19)

3/4
(19)
3/4
(19)
3/4
(19)

8-1/4
(368)

1 (25.4) 1 (25.4)
1 (25.4) 1 (25.4)

A

B

C

D

E

F

G

H

J

K

L

M

W.I.
NPTI

W.O. Drain
NPTI FPT

19-1/2
(495)
19-1/2
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)

31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8
(1064)
46-7/8
(1191)
50-7/8
(1292)

21-1/2
(546)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)
30-1/2
(775)
30-1/2
(775)

11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
18
(457)
18
(457)
18
(457)

4
(102)
5-1/4
(133)
4
(102)
3-1/4
(83)
4-1/4
(108)
4-1/4
(108)

1-3/4
(44)
3-3/4
(95)
3-7/8
(98)
1-7/8
(48)
2
(51)
2
(51)

9-1/2
(241)
9-1/2
(241)
9-1/2
(241)
9-1/2
(241)
9-1/2
(241)
9-1/2
(241)

15
(381)
15
(381)
23-3/4
(603)
19
(483)
29
(737)
29
(737)

17
(432)
17
(432)
17
(432)
23
(584)
27-7/8
(708)
27-7/8
(708)

6-7/8
(175)
8-1/4
(210)
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)

8
(203)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)

3/4
(19)
3/4
(19)
3/4
(19)
1/4
(6)
1/2
(13)
1/2
(13)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25.4)
1
(25.4)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25.4)
1
(25.4)

3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)

Note:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

WSHP-SVX01N-EN

23

Unit Dimensions and Weights
Figure 14. Right return/top supply: GEVE—“A” and later design sequence; EXV—”A” and later design sequence)
F

D
L

K
D

E
J

M

TOP

BLOWER
ACCESS

H

B
COMP/CONTROL
ACCESS
W.O.

WCI mounting location

DRAIN

HI VOLT

LO VOLT
3 5/8"
(92)

8 3/4"
(222)

W.I.

C

3 5/8"
(92)

12"
9 1/2"
(305)
(241)
G

A
FRONT

LEFT SIDE

RIGHT SIDE

Table 12. Right return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I. W.O. Drain
NPTI NPTI FPT

GEV Unit

A

B

C

D

E

F

G

H

J

K

L

M

006-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

4
(102)

5-3/4
(146)

9-1/2
(241)

15
(381)

17
(432)

6-7/8
(175)

8
(203)

3/4
(19)

1/2
(13)

1/2
(13)

3/4
(19)

018, 024, 030

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

4
(102)

4
(1021)

9-1/2
(241)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

036, 042

24-1/2
(622)

41-7/8
(1064)

26-1/2
18 (457)
(673)

3-1/4
(83)

5-3/4
(146)

9-1/2
(241)

19
(483)

23 (584)

10-1/2
(267)

13-1/2
(343)

1-3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

Std-048

26-1/2
(673)

46-7/8
(1191)

30-1/2
18 (457)
(775)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-7/8
(352)

13-7/8
(352)

1/2
(13)

1
(25)

1
(25)

3/4
(19)

Hi-048, 060

26-1/2
(673)

46-7/8
(1191)

30-1/2
18 (457)
(775)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-1/8
(333)

11-3/8
(289)

1/2
(13)

1
(25)

1
(25)

3/4
(19)

EXV Unit

A

B

C

D

E

F

G

H

J

K

L

M

006-009

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

4
(102)

5-3/4
(146)

9-1/2
(241)

15
(381)

17
(432)

6-7/8
(175)

8
(203)

3/4
(19)

1/2
(13)

1/2
(13)

3/4
(19)

012-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

11-1/2
(292)

2-1/2
(64)

5-5/8
(143)

9-1/2
(241)

15
(381)

17
(432)

8-1/4
(210)

9-3/4
(248)

3/4
(19)

1/2
(13)

1/2
(13)

3/4
(19)

018-024

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

4
(102)

4
(102)

9-1/2
(241)

23-3/4
(603)

17
(432)

8-1/4
(368)

11-3/8
(289)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

030-036

24-1/2
(622)

41-7/8
(1064)

26-1/2
(673)

18
(457)

3-1/4
(83)

5-3/4
(146)

9-1/2
(241)

19
(483)

23
(584)

10-1/2
(267)

13-1/2
(343)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

042-060

26-1/2
(673)

46-7/8
(1191)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-7/8
(352)

11-3/8
(289)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

070

26-1/2
(673)

50-7/8
(1292)

30-1/2
(775)

18
(457)

4-1/4
(108)

2
(51)

9-1/2
(241)

29
(737)

27-7/8
(708)

13-1/8
(333)

11-3/8
(289)

1/2
(13)

1
(25.4)

1
(25.4)

3/4
(19)

23-3/4
17 (432)
(603)

8-1/4
(368)

9-3/4
(248)
11-3/8
(289)

W.I. W.O. Drain
NPTI NPTI FPT

Note:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.

24

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 15. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
F

D
L

K
D

E
J

M

TOP

BLOWER
ACCESS

H

B
COMP/CONTROL
ACCESS
W.O.

WCI mounting location

DRAIN

HI VOLT

LO VOLT
3 5/8"
(92)

8 3/4"
(222)

W.I.

C

3 5/8"
(92)

12"
9 1/2"
(305)
(241)
G

A
FRONT

LEFT SIDE

RIGHT SIDE

Table 13. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
GEV Unit

A

B

C

D

E

F

006-015

19-1/2
(495)

31-1/4
(794)

21-1/2
(546)

4
1-3/4
(102)
(44)
11-1/2 006-009 006-009
(292)
6
1-1/4
(152)
(32)
012-015 012-015

018, 024,
030

21-1/2
(546)

39-1/4
(997)

21-1/2
(546)

13-1/2
(343)

24-1/2
(622)
26-1/2
Std-048
(673)
26-1/2
Hi-048, 060
(673)

41-7/8
(1064)
46-7/8
(1191)
46-7/8
(1191)

26-1/2
18 (457)
(673)
30-1/2
18 (457)
(775)
30-1/2
18 (457)
(775)

036, 042

EXV Unit

A

19-1/2
(495)
19-1/2
012-015
(495)
21-1/2
018-024
(546)
24-1/2
030-036
(622)
26-1/2
042-060
(673)
26-1/2
070
(673)
Note: All dimensions
006-009

WSHP-SVX01N-EN

B

C

D

G

H

J

K

L

M

8
(203)

3/4
(19)

9-1/2
(241)

15 (381) 17 (432)

6-7/8
(175)

23-3/4
17 (432)
(603)

8-1/4
(368)

4
(102)

3-7/8
(98)

9-1/2
(241)

3-1/4
(83)
4-1/4
(108)
4-1/4
(108)

1-7/8
(48)
2
(51)
2
(51)

9-1/2
(241)
9-1/2
(241)
9-1/2
(241)

19
(483)
29
(737)
29
(737)

E

F

G

31-1/4 21-1/2 11-1/2
4
1-3/4
9-1/2
(794)
(546)
(292)
(102)
(44)
(241)
31-1/4 21-1/2 11-1/2
2
1-1/4
9-1/2
(794)
(546)
(292)
(51)
(32)
(241)
39-1/4 21-1/2 13-1/2
4
3-7/8
9-1/2
(997)
(546)
(343)
(102)
(98)
(241)
41-7/8 26-1/2
18
3-1/4
1-7/8
9-1/2
(1064)
(673)
(457)
(83)
(48)
(241)
46-7/8 30-1/2
18
4-1/4
2
9-1/2
(1191)
(775)
(457)
(108)
(51)
(241)
50-7/8 30-1/2
18
4-1/4
2
9-1/2
(1292)
(775)
(457)
(108)
(51)
(241)
are in inches followed by millimeters in parenthesis.

9-3/4
(248)

W.I.
NPTI

W.O. Drain
NPTI FPT

1/2 (13) 1/2 (13)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

3/4
(19)

27-7/8
(708)
27-7/8
(708)

10-1/2
(267)
13-7/8
(352)
13-1/8
(333)

11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)

1-3/4
(19)
1/2
(13)
1/2
(13)

3/4
(19)
1
(25)
1
(25)

3/4
(19)
1
(25)
1
(25)

3/4
(19)
3/4
(19)
3/4
(19)

H

J

K

L

M

W.I.
NPTI

W.O. Drain
NPTI FPT

15
(381)
15
(381)
23-3/4
(603)
19
(483)
29
(737)
29
(737)

17
(432)
17
(432)
17
(432)
23
(584)
27-7/8
(708)
27-7/8
(708)

6-7/8
(175)
8-1/4
(210)
8-1/4
(368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)

8
(203)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)

3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25.4)
1
(25.4)

1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1
(25.4)
1
(25.4)

23 (584)

3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)

25

Unit Dimensions and Weights
Figure 16. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—right return/left supply
20"
(508)
SERVICE
CLEARANCE

36"
(914)
SERVICE
CLEARANCE
4 5/8"
(117)

79"
(2007)
74 1/2"
(1892)

1 3/4"
(44)

36"
(914)

2 1/8"
(54)

23 7/8"
(606)

BLOWER ACCESS
PANEL

40 5/8"
(1032)

7 5/8"
(194)

TOP VIEW

18 3/8"
(467)
81"
(2057)
85"
(2159)

1 1/4"
(32)

5/8"
(16)

W.O. "D" NPTI
1"
(25.4)

24 VOLT
1 1/8" (28.6) DIA.

A

1 1/2"
(38)

)

4 7/8"
(124)

14 1/2"
(368)

18 3/4"
(476)

23 1/4"
16 1/2" (591)
(419)

WCI mounting location

B

BACK SIDE

2 1/4"
(57)

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

HIGH VOLTAGE
7/8" (22.2) DIA.

W.I. "D" NPTI

6 1/2"
(165)

3 1/8"
(79)

C

LEFT SIDE

(79

RETURN AIR
OPENING

1" (25.4) DIA.
MOUNTING HOLE
4X'S

SUPPLY OPENING
1" (25.4) DUCT FLANGE

Table 14. GEH 6–10 tons (072-120) 60 Hz; GEH 6–7½ tons (072-090) 50 Hz—right return/left supply
GEH (60 Hz)

26

GEH (50 Hz)

A

B

C

D

072

—

36-1/4 in.
(921 mm)

15-5/8 in.
(397 mm)

6-5/8 in.
(168 mm)

1-1/4 in.
(32 mm)

090

072

36-1/8 in.
(917 mm)

12-3/4 in.
(324 mm)

6-3/4 in.
(171 mm)

1-1/4 in.
(32 mm)

120

090

36-1/8 in.
(917 mm)

13 in.
(330 mm)

7-1/4 in.
(184 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 17. GEH 6–10 tons (072–120) 60 Hz; GEH 6–7½ tons (072–090) 50 Hz—right return/back supply
36"
(914)
SERVICE
CLEARANCE

74 1/2"
(1892)

1 3/4"
(44)

36"
(914)

18 3/8"
(467)

81"
(2057)
85"
(2159)

6 1/8"
(156)

2 1/8"
(54)

23 7/8"
(606)

4 5/8"
(117)

79"
(2007)

BLOWER ACCESS
PANEL

40 5/8"
(1032)

20"
(508)
SERVICE
CLEARANCE

TOP VIEW

4 7/8"
(124)

1 1/4"
(32)

5/8"
(16)

W.O. "D" NPTI
24 VOLT
1 1/8" (28.6) DIA.

A

14 1/2"
(368)

18 3/4"
(476)

1 1/2"
(38)

23 1/4"
16 1/2" (591)
(419)

WCI mounting location

B

HIGH VOLTAGE
7/8" (22.2) DIA.

W.I. "D" NPTI

6 1/2"
(165)

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

2 1/4"
(57)

3 1/8"
(79)

C

LEFT SIDE
RETURN AIR
OPENING

1" (25.4) DIA.
MOUNTING HOLE
4X'S

SUPPLY OPENING
1" (25.4) DUCT FLANGE

Table 15. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—right return/back supply
GEH (60 Hz)

GEH (50 Hz)

A

B

C

D

072

—

36-1/4 in.
(921 mm)

15-5/8 in.
(397 mm)

6-5/8 in.
(168 mm)

1-1/4 in.
(32 mm)

090

072

36-1/8 in.
(917 mm)

12-3/4 in.
(324 mm)

6-3/4 in.
(171 mm)

1-1/4 in.
(32 mm)

120

090

36-1/8 in.
(917 mm)

13 in.
(330 mm)

7-1/4 in.
(184 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

27

Unit Dimensions and Weights
Figure 18. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz - left return/right supply
36"
(914)
SERVICE
CLEARANCE

79"
(2007)

4 5/8"
(117)

40 5/8"
(1032)

20"
(508)
SERVICE
CLEARANCE

74 1/2"
(1892)

1 3/4"
(44)

36"
(914)

24 3/4"
(629)

1 1/4"
(32)

7 5/8"
(194)

TOP VIEW

BLOWER ACCESS
PANEL

18 3/8"
(467)
81"
(2057)
85"
(2159)

23 1/4"
(591) 16 1/2"
(419)

A

1"
(25.4)

5/8"
(16)

24 VOLT
1 1/8" (28.6) DIA.

1 1/4"
(32)

W.O. "D" NPTI
1 1/2"
(38)

4 7/8"
(124)

14 1/2"
(368)

WCI mounting location

18 3/4"
(476)

B

HIGH VOLTAGE
7/8" (22.2) DIA.

3 1/8"
(79)

6 1/2"
(165)

2 1/4"
(57)

C

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

W.I. "D" NPTI

LEFT SIDE

BACK SIDE

RETURN AIR
OPENING

SUPPLY OPENING
1" (25.4) DUCT FLANGE

1" (25.4) DIA.
MOUNTING HOLE
4X'S

Table 16. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/right supply
GEH (60 Hz)

28

GEH (50 Hz)

A

B

C

D

072

—

36-1/8 in.
(917 mm)

17 in.
(432 mm)

8 in.
(203 mm)

1-1/4 in.
(32 mm)

090

072

36-1/8 in.
(917 mm)

13-3/4 in.
(349 mm)

7-3/4 in.
(197 mm)

1-1/4 in.
(32 mm)

120

090

36-1/8 in.
(917 mm)

13 in.
(330 mm)

7-1/4 in.
(184 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 19. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/back supply
36"
(914)
SERVICE
CLEARANCE

1 3/4"
(44)

36"
(914)

18 3/8"
(467)

81"
(2057)
85"
(2159)

20"
(508)
SERVICE
CLEARANCE

6 1/8"
(156)

40 5/8"
(1032)

74 1/2"
(1892)

24 3/4"
(629)

1 1/4"
(32)

4 5/8"
(117)

79"
(2007)

TOP VIEW
BLOWER ACCESS
PANEL

23 1/4"
(591) 16 1/2"
(419)

A

5/8"
(16)

24 VOLT
1 1/8" (28.6) DIA.

1 1/4"
(32)

W.O. "D" NPTI
1 1/2"
(38)

4 7/8"
(124)

14 1/2"
(368)

WCI mounting location

18 3/4"
(476)

B

HIGH VOLTAGE
7/8" (22.2) DIA.

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

W.I. "D" NPTI

LEFT SIDE

3 1/8"
(79)

2 1/4"
(57)

6 1/2"
(159)

C

RETURN AIR
OPENING
1" (25.4) DIA.
MOUNTING HOLE
4X'S

SUPPLY OPENING
1" (25.4) DUCT FLANGE

Table 17. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/back supply
GEH (60 Hz)

GEH (50 Hz)

A

B

C

D

072

—

36-1/8 in.
(917 mm)

17 in.
(432 mm)

8 in.
(203 mm)

1-1/4 in.
(32 mm)

090

072

36-1/8 in.
(917 mm)

13-3/4 in.
(349 mm)

7-3/4 in.
(197 mm)

1-1/4 in.
(32 mm)

120

090

36-1/8 in.
(917 mm)

13 in.
(330 mm)

7-1/4 in.
(184 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

29

Unit Dimensions and Weights
Figure 20. GEH 12½-15 tons (150-180) 60 Hz; GEH 10-12½ tons (120-150) 50 Hz—right return/left supply
20"
(508)
SERVICE
CLEARANCE

36"
(914)
SERVICE
CLEARANCE
4 5/8"
(117)

79"
(2007)
74 1/2"
(1892)

1 3/4"
(44)

36"
(914)

2 1/8"
(54)

23 7/8"
(606)

BLOWER ACCESS
PANEL

40 5/8"
(1032)

7 5/8"
(194)

TOP VIEW

18 3/8"
(467)
81"
(2057)
85"
(2159)

24 VOLT
1 1/8" (28.6) DIA.

A

1 1/2"
(38)

)

4 7/8"
(124)

1 1/4"
(32)

5/8"
(16)

W.O. "D" NPTI
1"
(25.4)

14 1/2"
(368)

18 3/4"
(476)

23 1/4"
16 1/2" (591)
(419)

WCI mounting location

B

BACK SIDE

HIGH VOLTAGE
7/8" (22.2) DIA.

W.I. "D" NPTI

6 1/2"
(165)

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

2 1/4"
(57)

3 1/8"
(79)

C

LEFT SIDE

(79

RETURN AIR
OPENING

1" (25.4) DIA.
MOUNTING HOLE
4X'S

30

SUPPLY OPENING
1" (25.4) DUCT FLANGE

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 21. GEH 12½-15 tons (150-180) 60 Hz; GEH 10-12½ tons (120-150) 50 Hz—right return/back supply
36"
(914)
SERVICE
CLEARANCE

74 1/2"
(1892)

2"
(41)

46 5/8"
42"
(1184)
(1067)

21 3/8"
(543)

87"
(2210)
91"
(2311)

7 1/8"
(181)

2 1/4"
(57)

29 3/4"
(756)

4 5/8"
(117)

85"
(2159)

20"
(508)
SERVICE
CLEARANCE

TOP VIEW

W.O. 1 1/2" (38)
NPTI
24 VOLT
1 1/8" (28.6) DIA.

61 1/4"
(1556)

16 3/4"
(425)

23 3/4"
(603)

1 1/2"
(38)

30 1/4"
22 3/4" (768)
(578)

WCI mounting location

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

W.I. 1 1/2" (38)
NPTI

HIGH VOLTAGE
7/8" (22.2) DIA.

2 1/4"
(57)

3 1/8"
(79)

24 7/8"
(632)
5 5/8"
(143)

9 1/8"
(232)

4 7/8"
(124)

2"
(51)

1 3/8"
(35)

BLOWER ACCESS
PANEL

LEFT SIDE
RETURN AIR
OPENING

1" (25.4) DIA.
MOUNTING HOLE
4X'S

WSHP-SVX01N-EN

SUPPLY OPENING
1" (25.4) DUCT FLANGE

31

Unit Dimensions and Weights
Figure 22. GEH 12½-15 tons (150-180) 60 Hz; GEH 10-12½ tons (120-150) 50 Hz—left return/right supply
36"
(914)
SERVICE
CLEARANCE

85"
(2159)

4 5/8"
(117)

74 1/2"
(1892)

2"
(51)

42"
(1067)

29 3/4"
(756)

7 1/8"
(181)

TOP VIEW

2 1/4"
(57)

46 5/8"
(1184)

20"
(508)
SERVICE
CLEARANCE

BLOWER ACCESS
PANEL

21 3/8"
(543)
87"
(2210)

1"
(25.4)

4 7/8"
(124)

16 3/4"
(425)

WCI mounting location

23 3/4"
(603)

24 7/8"
(632)

HIGH VOLTAGE
7/8" (22.2) DIA.

LEFT SIDE

3 1/8"
(79)

5 5/8"
(143)
2 1/4"
(57)

9 1/8"
(232)

30 1/4"
(768) 22 3/4"
(578)

39 1/2"
(1003)

1 3/8"
(35)

2 1/8"
(54)

W.O. 1 1/2" (38)
NPTI
24 VOLT
1 1/8" (28.6) DIA.

2"
(51)

91"
(2311)

W.I. 1 1/2" (38)
NPTI

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

BACK SIDE

RETURN AIR
OPENING

SUPPLY OPENING
1" (25.4) DUCT FLANGE

1" (25.4) DIA.
MOUNTING HOLE
4X'S

32

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 23. GEH 12½-15 tons (150-180) 60 Hz; GEH 10-12½ tons (120-150) 50 Hz—left return/back supply
36"
(914)
SERVICE
CLEARANCE

2"
(51)

42"
(1067)

21 3/8"
(543)

87"
(2210)
91"
(2311)

20"
(508)
SERVICE
CLEARANCE

29 3/4"
(756)

7 1/8"
(181)

46 5/8"
(1184)

74 1/2"
(1892)

2 1/4"
(57)

4 5/8"
(117)

85"
(2159)

TOP VIEW
BLOWER ACCESS
PANEL

4 7/8"
(124)

16 3/4"
(425)

WCI mounting location

23 3/4"
(603)

24 7/8"
(632)

HIGH VOLTAGE
7/8" (22.2) DIA.

LEFT SIDE

W.I. 1 1/2" (38)
NPTI

DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC

3 1/8"
(79)

5 5/8"
(143)
2 1/4"
(57)

9 1/8"
(232)

30 1/4"
(768) 22 3/4"
(578)

39 1/2"
(1003)

1 3/8"
(35)

24 VOLT
1 1/8" (28.6) DIA.

2 1/8"
(54)

2"
(51)

W.O. 1 1/2" (38) NPTI

RETURN AIR
OPENING
1" (25.4) DIA.
MOUNTING HOLE
4X'S

WSHP-SVX01N-EN

SUPPLY OPENING
1" (25.4) DUCT FLANGE

33

Unit Dimensions and Weights
Figure 24. GEV 6-10 tons (072-120) 60 Hz; 6 and 7½ tons (072 and 090) 50 Hz—front return/back supply(a)
15 3/4
(400)
ACCESS PANEL FOR
SHEAVES AND BELTS

SUPPLY OPENING
1" (25.4) DUCT FLANGE

13 18"
(333)

36"
(914)
SERVICE
CLEARANCE

39 5/8"
(1006)
42"
(1067)

20"
(508)
SERVICE
CLEARANCE

4 7/8"
(124)

31 3/8"
36 1/4"
(797)
(921)

1
(25.4)

13 1/2"
(343)
38 7/8"
(987)

62 5/8"
(1591)

W.O. "C" NPTI
24 VOLT
1 1/8" (28.6)

DRAIN 3/4" NPTI

46 1/2"
(1181)
WCI mounting location

22 3/8"
(568)
A

3/4"
(19)

HIGH VOLTAGE
7/8" (22.2) DIA.

5"
(127)

15"
(381)

11 1/2"
(292)

B

W.I. "C" NPTI
1 7/8"
(48)

1 5/8"
(41)

RETURN AIR
OPENING

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 18. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ tons (072 and 090) 50 Hz—front return/back supply
Unit (60 Hz)

34

Unit (50 Hz)

A

B

C

6 ton

—

6-5/8 in.
(168 mm)

18-3/8 in.
(467 mm)

1-1/4 in.
(32 mm)

7½ ton

6 ton

6-5/8 in.
(168 mm)

18-3/8 in.
(403 mm)

1-1/4 in.
(32 mm)

10 ton

7½ ton

6-1/2 in.
(165 mm)

18-1/2 in.
(470 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 25. GEV 6–10 tons (072–120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—front return/top supply(a)
ACCESS PANEL FOR
SHEAVES AND BELTS

1 1/8"
(29)

15 5/8
(397)
13 1/4"
(337)

13 3/8"
(343)

36"
(914)
SERVICE
CLEARANCE

39 5/8"
(1006)
42"
(1067)

1"
(25.4)

20"
(508)
SERVICE
CLEARANCE

4 7/8"
(124)

31 3/8"
36 1/4"
(797)
(921)

63"
(1600)

38 7/8"
(987)
W.O. "C" NPTI

24 VOLT
1 1/8" (28.6)

HIGH VOLTAGE
7/8" (22.2) DIA.

5"
(127)

15"
(381)

22 3/8"
(568)
A

3/4"
(19)

WCI mounting location

DRAIN 3/4" NPTI

1 5/8"
(41)

11 1/2"
(292)

62 5/8"
(1591)

B

W.I. "C" NPTI
1 7/8"
(48)
SUPPLY OPENING
1" (25.4) DUCT FLANGE

RETURN AIR
OPENING

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 19. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—front return/top supply
Unit (60 Hz)

Unit (50 Hz)

A

B

C

6 ton

—

6-5/8 in.
(168 mm)

18-3/8 in.
(467 mm)

1-1/4 in.
(32 mm)

7½ ton

6 ton

6-5/8 in.
(168 mm)

18-3/8 in.
(403 mm)

1-1/4 in.
(32 mm)

10 ton

7½ ton

6-1/2 in.
(165 mm)

18-1/2 in.
(470 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

35

Unit Dimensions and Weights

4 7/8"
(124)

Figure 26. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—back return/front supply(a)
39 5/8"
(1006)

ACCESS PANEL FOR
SHEAVES AND BELTS

13 1/8"
(333)
20"
(508)
SERVICE
CLEARANCE

15 3/4
(400)

1 1/8"
(29)

36 1/4"
31 3/8" (921)
(797)

36"
(914)
SERVICE
CLEARANCE

42"
(1067)

13 1/2"
(343)

1" (25.4)

38 7/8"
(987)
W.O. "C" NPTI
24 VOLT
1 1/8" (28.6)

DRAIN 3/4" NPTI

WCI mounting location

15"
(381)
HIGH VOLTAGE
7/8" (22.2) DIA.

5"
(127)

3/4"
(19)

22 3/8"
(568)

62 5/8"
(1591)

11 1/2"
(292)

A

46 1/2"
(1181)

B

W.I. "C" NPTI
1 7/8"
(48)

1 5/8"
(41)
RETURN AIR
OPENING

SUPPLY OPENING
1" (25.4) DUCT FLANGE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 20. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—back return/front supply
Unit (60 Hz)

36

Unit (50 Hz)

A

B

C

6 ton

—

6-5/8 in.
(168 mm)

18-3/8 in.
(467 mm)

1-1/4 in.
(32 mm)

7½ ton

6 ton

6-5/8 in.
(168 mm)

18-3/8 in.
(403 mm)

1-1/4 in.
(32 mm)

10 ton

7½ ton

6-1/2 in.
(165 mm)

18-1/2 in.
(470 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights

4 7/8"
(124)

Figure 27. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—back return/top supply(a)
39 5/8"
(1006)

ACCESS PANEL FOR
SHEAVES AND BELTS

36 1/4"
31 3/8"
(921)
(797)
13 1/2"
(343)

1 1/8"
(29)

13 1/4"
(337)
15 5/8
(397)

20"
(508)
SERVICE
CLEARANCE

36"
(914)
SERVICE
CLEARANCE

1"
(25.4)

42"
(1067)

38 7/8"
(987)
W.O. "C" NPTI
63"
24 VOLT
(1600)
1 1/8" (28.6)

WCI mounting location

15"
(381)
HIGH VOLTAGE
7/8" (22.2) DIA.

A

5"
(127)

3/4"
(19)

22 3/8"
(568)

DRAIN 3/4" NPTI

11 1/2"
(292)

62 5/8"
(1591)

B

W.I. "C" NPTI
1 7/8"
(48)

1 5/8"
(41)
RETURN AIR
OPENING

SUPPLY OPENING
1" (25.4) DUCT FLANGE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 21. GEV 6–10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz—back return/top supply
Unit (60 Hz)

Unit (50 Hz)

A

B

C
1-1/4 in.
(32 mm)

6 ton

—

6-5/8 in.
(168 mm)

18-3/8 in.
(467 mm)

7½ ton

6 ton

6-5/8 in.
(168 mm)

18-3/8 in.
(403 mm)

1-1/4 in.
(32 mm)

10 ton

7½ ton

6-1/2 in.
(165 mm)

18-1/2 in.
(470 mm)

1-1/2 in.
(38 mm)

WSHP-SVX01N-EN

37

Unit Dimensions and Weights
Figure 28. GEV 12½–15 tons (150–180) 60 Hz; GEV 10 and 12½ ton (120 and 150) 50 Hz—front return/back supply(a)

31 1/2"
(800)

36 1/4"
(921)

10"
(254)

74 1/2"
(1892)

4 3/4"
(121)

81 5/8"
(2073)
TOP VIEW
18 5/8"
(473)
31 1/2"
(800)
24 VOLT
1 1/8" (29) O.D.

15 7/8"
(403)

38 7/8"
(987)

W.O. 1 1/2"
(38) NPTI

67 5/8"
(1718)
6 7/8" (175)

DRAIN 3/4"
(19) NPTI

49 1/8"
(1248)
WCI mounting
location

20 1/2"
(521)

HIGH VOLTAGE
7/8" (22) O.D.

27 1/8"
(537)

23 1/2
(597)

12 1/2"
(318)

1"
(25.4)

SIDE VIEW

CONTROL
BOX ACCESS

FRONT VIEW

2 3/8"
(60)

W.I. 1 1/2"
(38) NPTI

2 5/8"
(67)
4 1/4"
(108)

RETURN AIR
OPENING
MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

38

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 29. GEV 12½–15 tons (150–180) 60 Hz; GEV 10 and 12½ ton (120 and 150) 50 Hz—back return/front supply(a)
81 5/8"
(2073)
4 3/4"
(121)

36 1/4"
(921)

74 1/2"
(1892)

31 1/2"
(800)
10"
(254)

TOP VIEW
18 5/8"
(473)
31 1/2"
(800)

15 7/8"
(403)
38 7/8"
(987)

W.O. 1 1/2"
(38) NPTI

1"
(25.4)

24 VOLT
1 1/8"
(29) O.D. WCI mounting
location

DRAIN 3/4"
(19) NPTI

49 1/8"
(1248)
20 1/2"
2
(521)

27 1/8"
(537)

6 7/8" (175)

67 5/8"
(1718)

HIGH VOLTAGE
7/8" (22) O.D.

CONTROL
BOX ACCESS
12 1/2"
(318)

W.I. 1 1/2"
(38) NPTI

FRONT VIEW

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)

SIDE VIEW

23 1/2
(597)

RETURN AIR
OPENING

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

WSHP-SVX01N-EN

39

Unit Dimensions and Weights
Figure 30. GEV 12½–15 tons (150-180) 60 Hz; GEV 10 and 12½ ton (120 and 150) 50 Hz—front return/top supply(a)

15 7/8"
(403)
31 1/2"
(800)

36 1/4"
(921)

10"
(254)

14 3/8"
(365)

74 1/2"
(1892)

4 3/4"
(121)

81 5/8"
(2073)
TOP VIEW
18 5/8"
(473)
31 1/2"
(800)

38 7/8"
(987)
(98

W.O. 1 1/2"
(38) NPTI

WCI mounting
location

20 1/2"
(521)

24 VOLT
1 1/8"
(29) O.D.

6 7/8" (175)

68"
(1727)

HIGH VOLTAGE
7/8" (22) O.D.

CONTROL
BOX ACCESS

27 1
1/8"
(53
(537)

12 1/2"
(318)

1"
(25.4)

SIDE VIEW

DRAIN 3/4"
(19) NPTI

FRONT VIEW

W.I. 1 1/2"
(38) NPTI

23 1/2
(597)

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)
SUPPLY OPENING
WITH 1" (25.4) DUCT
FLANGE

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

RETURN AIR
OPENING

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

40

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 31. GEV 12½–15 ton (150–180) 60 Hz; GEV 10 and 12½ ton (120 and 150) 50 Hz—back return/top supply(a)
81 5/8"
(2073)
4 3/4"
(121)

74 1/2"
(1892)

14 3/8"
(365)
36 1/4"
(921)

31 1/2"
(800)
10"
(254)

15 7/8
7/8"
(403
(403)

TOP VIEW
18 5/8"
(473)
31 1/2"
(800)

38 7/8"
(987)

W.O. 1 1/2"
(38) NPTI

68"
(1727)

1"
(25.4)

6 7/8" (175)

24 VOLT
1 1/8"
WCI mounting
(29) O.D.
location

HIGH VOLTAGE
7/8" (22) O.D.

SIDE VIEW

CONTROL
BOX ACCESS

20 1/2"
2
(521)

7 1/8"
27
(537)

DRAIN 3/4"
(19) NPTI

12 1/2"
(318)

FRONT VIEW

W.I. 1 1/2"
(38) NPTI

23 1/2
(597)

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)
RETURN AIR
OPENING

SUPPLY OPENING
WITH 1" (25.4) DUCT
FLANGE

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

WSHP-SVX01N-EN

41

Unit Dimensions and Weights
Figure 32. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—front return/back supply(a)

31 1/2"
(800)

36 1/4"
(921)

6 1/4"
(159)

74 1/2"
(1892)

4 3/4"
(121)

81 5/8"
(2073)
TOP VIEW
C

19 1/8"
(486)

A

A

24 VOLT
1 1/8" (29) O.D.
B
38 7/8"
(987)

W.O. 2"
(51) NPTI

67 5/8"
(1718)

6 7/8" (175)

DRAIN 3/4"
(19) NPTI

D
WCI mounting
location

CONTROL
BOX ACCESS

27 1/8"
(537)

20 1/2"
(521)

E
12 1/2"
(318)

HIGH VOLTAGE
7/8" (22) O.D.

1"
(25.4)

FRONT VIEW

W.I. 2"
(51) NPTI

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)

SIDE VIEW

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

RETURN AIR
OPENING

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 22. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—front return/back supply
Unit (60 Hz)

42

Unit (50 Hz)

A

B

C

D

E

20 ton

15 ton

15-5/8 in.
(397 mm)

13-1/2 in.
(341 mm)

12 in.
(305 mm)

51-5/8 in.
(1310 mm)

20-7/8 in.
(530 mm)

25 ton
Std Static

20 ton
Std Static

14-3/4 in.
(375 mm)

15-7/8 in.
(403 mm)

13-7/8 in.
(352 mm)

49-1/8 in.
(1248 mm)

23-1/2 in.
(597 mm)

25 ton
High Static

20 ton
High Static

15-5/8 in.
(397 mm)

13-1/2 in.
(343 mm)

12 in.
(305 mm)

51-5/8 in.
(1311 mm)

23-1/2 in.
(597 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 33. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz - back return/front supply(a)
81 5/8"
(2073)
4 3/4"
(121)

36 1/4"
(921)

74 1/2"
(1892)

31 1/2"
(800)
6 1/4"
(159)
TOP VIEW
C

19 1/8"
(486)

A

A

B
38 7/8"
(987)

W.O. 2"
(51) NPTI

27 1/8"
537)
(537)

1"
(25.4)

24 VOLT
1 1/8" WCI mounting
(29) O.D.
location

6 7/8" (175)

6 5/8"
67
(
(1718)

DRAIN 3/4"
(19) NPTI

D
CONTROL
BOX ACCESS

20 1/2"
(521)

E
12 1/2"
(318)

HIGH VOLTAGE
7/8" (22) O.D.

W.I. 2"
(51) NPTI

FRONT VIEW

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)

SIDE VIEW

RETURN AIR
OPENING

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 23. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—back return/front supply
Unit (60 Hz)

Unit (50 Hz)

A

B

C

D

E

20 ton

15 ton

15-5/8 in.
(397 mm)

13-1/2 in.
(341 mm)

12 in.
(305 mm)

51-5/8 in.
(1310 mm)

20-7/8 in.
(530 mm)

25 ton
Std Static

20 ton
Std Static

14-3/4 in.
(375 mm)

15-7/8 in.
(403 mm)

13-7/8 in.
(352 mm)

49-1/8 in.
(1248 mm)

23-1/2 in.
(597 mm)

25 ton
High Static

20 ton
High Static

15-5/8 in.
(397 mm)

13-1/2 in.
(343 mm)

12 in.
(305 mm)

51-5/8 in.
(1311 mm)

23-1/2 in.
(597 mm)

WSHP-SVX01N-EN

43

Unit Dimensions and Weights
Figure 34. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—front return/top supply(a)

6 1/4"
(159)

1 1/4" (32)

B
31 1/2"
(800)

36 1/4"
(921)

74 1/2"
(1892)

4 3/4"
(121)

81 5/8"
(2073)
TOP VIEW

C
19 1/8"
(486)

A

A

38 7/8"
(987)
(98

W.O. 2"
(51) NPTI

WCI mounting
location

20 1/2"
(521)

24 VOLT
1 1/8"
(29) O.D.

6 7/8" (175)

68"
(1727)

HIGH VOLTAGE
7/8" (22) O.D.

CONTROL
BOX ACCESS

1/8"
27 1
(537)
(53

D
12 1/2"
(318)

1"
(25.4)

SIDE VIEW

DRAIN 3/4"
(19) NPTI

FRONT VIEW

W.I. 2"
(51) NPTI

MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)
SUPPLY OPENINGS
WITH 1" (25.4) DUCT
FLANGE

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

RETURN AIR
OPENING

SERVICE CLEARANCE

(a) NEC requires that the GEV072-300 front return must be a non-ducted return.

Table 24. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—front return/top supply
Unit (60 Hz)

44

Unit (50 Hz)

A

B

C

D

20 ton

15 ton

15-5/8 in.
(397 mm)

13-1/2 in.
(341 mm)

12 in.
(305 mm)

20-7/8 in.
(530 mm)

25 ton
Std Static

20 ton
Std Static

14-3/4 in.
(375 mm)

15-7/8 in.
(403 mm)

13-7/8 in.
(352 mm)

23-1/2 in.
(597 mm)

25 ton
High Static

20 ton
High Static

15-5/8 in.
(397 mm)

13-1/2 in.
(343 mm)

12 in.
(305 mm)

23-1/2 in.
(597 mm)

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 35. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—back return/top supply(a)
81 5/8"
(2073)
4 3/4"
(121)

1 1/4
1/4" (32)

36 1/4"
(921)

74 1/2"
(1892)

31 1/2"
(800)
B
6 1/4"
(159)

TOP VIEW

C
19 1/8"
(486)

A

A

38 7/8"
(987)

W.O. 2"
(51) NPTI

68"
(172
(1727)

1"
(25.4)

6 7/8" (175)

24 VOLT
1 1/8"
(29) O.D.

WCI mounting
location

CONTROL
BOX ACCESS

20 1/2"
(521)

27 1/8"
(537)

DRAIN 3/4"
(19) NPTI

HIGH VOLTAGE
7/8" (22) O.D.

SIDE VIEW
MIN. SERVICE ON BACK
FOR COMPRESSOR ACCESS IS 24”

CONTROL BOX
NEC REQ. UNIT FRONT
36" (914)
16" (406) TO
C.B.TO WALL
FILTER FRAME
CLEARANCE
FOR RETURN-AIR

D
12 1/2"
(318)

FRONT VIEW

W.I. 2"
(51) NPTI

2 5/8"
(67)
4 1/4"
(108)

2 3/8"
(60)
RETURN AIR
OPENING

SUPPLY OPENING
WITH 1" (25.4) DUCT
FLANGE

MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.

SERVICE CLEARANCE

(a) NEC requires GEV072-300 front return must be non-ducted return.

Table 25. GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and 240) 50 Hz—back return/top supply
Unit (60 Hz)

Unit (50 Hz)

A

B

C

D

12 in.
(305 mm)

20-7/8 in.
(530 mm)

20 ton

15 ton

15-5/8 in.
(397 mm)

13-1/2 in.
(341 mm)

25 ton
Std Static

20 ton
Std Static

14-3/4 in.
(375 mm)

15-7/8 in.
(403 mm)

13-7/8 in.
(352 mm)

23-1/2 in.
(597 mm)

25 ton
High Static

20 ton
High Static

15-5/8 in.
(397 mm)

13-1/2 in.
(343 mm)

12 in.
(305 mm)

23-1/2 in.
(597 mm)

WSHP-SVX01N-EN

45

Unit Dimensions and Weights

5/8" (16)

1 1/2" (38)

Figure 36. GEH and EXH waterside economizer(a)

G

N

TOP VIEW

5/8"(16)

M

H

20"
(508)
A = TO FIELD
SUPPLY PIPING

E

5"
(127)
J

2 1/2" (64)

L

K

FRONT VIEW

D
C

F

B = TO FIELD
RETURN PIPING

(a) Waterside economizer installation requires field piping.

Table 26. GEH and EXH waterside economizer
GEH
GEH
(60 Hz) (50 Hz) A NPTI B NPTI

C

D

E

F

G

H

J

K

L

M

N

1/2
(12.7)

16-1/8
(410)

13-5/8
(346)

1-1/2
(38)

10-3/4
(273)

23
(584)

2-1/4
(57)

7-1/2
(191)

1/2
(12.7)

1
(25.4)

4
(102)

18-1/2
(470)

006-015

006-012

1/2
(12.7)

018-030

015-024

3/4
(19)

3/4
(19)

18-1/2
(470)

15-5/8
(397)

1-1/2
(38)

13-3/4
(349)

26
(660)

3-1/4
(83)

6-7/8
(175)

1/2
(12.7)

1
(25.4)

4
(102)

18-1/2
(470)

036-042

030-036

3/4
(19)

3/4
(19)

21
(533)

17-5/8
(448)

2-1/4
(57)

16-1/2
(419)

30
(762)

3-3/4
(95)

6-1/4
(159)

1-1/4
(32)

2
(50.8)

4-1/2
(114)

23-1/2
(597)

048-060

042-060

1
(25.4)

1
(25.4)

23-1/8
(587)

19-5/8
(498)

2-1/2
(64)

19-1/2
(495)

34
(864)

5-1/4
(133)

5-7/8
(149)

1-1/4
(32)

2
(50.8)

4-1/2
(114)

23-1/2
(597)

EXH
GEH
(60 Hz) (50 Hz) A NPTI B NPTI

C

D

E

F

G

H

J

K

L

M

N

006-015

----

1/2
(12.7)

1/2
(12.7)

16-1/8
(410)

13-5/8
(346)

1-1/2
(38)

10-3/4
(273)

23
(584)

2-1/4
(57)

7-1/2
(191)

1/2
(12.7)

1
(25.4)

4
(102)

18-1/2
(470)

018-024

----

3/4
(19)

3/4
(19)

18-1/2
(470)

15-5/8
(397)

1-1/2
(38)

13-3/4
(349)

26
(660)

3-1/4
(83)

6-7/8
(175)

1/2
(12.7)

1
(25.4)

4
(102)

18-1/2
(470)

030-036

----

3/4
(19)

3/4
(19)

21
(533)

17-5/8
(448)

2-1/4
(57)

16-1/2
(419)

30
(762)

3-3/4
(95)

6-1/4
(159)

1-1/4
(32)

2
(50.8)

4-1/2
(114)

23-1/2
(597)

042-070

----

1
(25.4)

1
(25.4)

23-1/8
(587)

19-5/8
(498)

2-1/2
(64)

19-1/2
(495)

34
(864)

5-1/4
(133)

5-7/8
(149)

1-1/4
(32)

2
(50.8)

4-1/2
(114)

23-1/2
(597)

46

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 37. GEH and EXH hanging unit waterside economizer

Table 27. GEH and EXH hanging unit waterside economizer
GEH Unit
(60 Hz)

GEH Unit
(50 Hz)

006-015

006-012

018-030

015-024

036-042

030-036

048-060

042-048

EXH Unit
(60 Hz)

EXH Unit
(50 Hz)

006-015

—

018-024

—

030-036

—

042-070

—

A

B

C

D

E

Hanging
Weight

Shipping
Weight

38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)

18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)

21-3/4
(552)
24-3/4
(629)
28-3/4
(730)
32-3/4
(832)

17
(432)
21
(553)
21
(533)
25
(635)

0
(0)
1
(25)
2
(51)
1
(25)

54 lbs
(25 kg)
65 lbs
(30 kg)
76 lbs
(35 kg)
97 lbs
(44 kg)

84 lbs
(38 kg)
95 lbs
(43 kg)
106 lbs
(48 kg)
127 lbs
(58 kg)

A

B

C

D

E

Hanging
Weight

Shipping
Weight

38-3/4
(984)
44-3/4
(1137)
48-3/4
(1238)
56-3/4
(1441)

18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)

21-3/4
(552)
24-3/4
(629)
28-3/4
(730)
32-3/4
(832)

17
(432)
21
(553)
21
(533)
25
(635)

0
(0)
1
(25)
2
(51)
1
(25)

54 lbs
(25 kg)
65 lbs
(30 kg)
76 lbs
(35 kg)
97 lbs
(44 kg)

84 lbs
(38 kg)
95 lbs
(43 kg)
106 lbs
(48 kg)
127 lbs
(58 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

WSHP-SVX01N-EN

47

Unit Dimensions and Weights
Figure 38. GEH 6-10 tons (072-120) 60 Hz, right return; GEH 6-7½ tons (072-090) 50 Hz, right return, waterside
economizer(a)(b)

9 7/8"
(251)
18 1/2"
(470)
50 5/8"
(1286)
36"
(914)

2 1/8"
(54)

23 7/8"
(606)

C

"B" OD COPPER TO
FIELD SUPPLY PIPING

"A" NPTI FOR
FIELD RETURN PIPING
D

E

(a) Entering water is on the AB port.
(b) Field piping required on waterside economizer.

48

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 39. GEH 6-10 tons (072-120) 60 Hz, left return; GEH 6-7½ tons (072-090) 50 Hz, left return, waterside economizer(a)(b)

9 7/8"
(251)
18 1/2"
(470)
50 5/8"
(1286)
36"
(914)

1 1/4"
(32)

24 3/4"
(629)

C

"B" OD COPPER TO
FIELD SUPPLY PIPING

"A" NPTI FOR
FIELD RETURN PIPING
D

E

(a) Entering water is on the AB port.
(b) Field piping required on waterside economizer.

Table 28. GEH 6-10 tons (072-120) 60 Hz, left return; GEH 6-7½ tons (072-090) 50 Hz, left return, waterside economizer
GEH (60 Hz)

GEH (50 Hz)

072

—

090

072

120

090

C

Hanging Shipping
Weight
Weight

A

B

D

E

1-1/4

1-3/8

(32)

(35)

31

9-7/8

3-7/8

138 lbs

168 lbs

(787)

(251)

(98)

(63 kg)

(76 kg)

1-1/4

1-3/8

(32)

(35)

31

9-7/8

3-7/8

144 lbs

174 lbs

(787)

(251)

(98)

(65 kg)

(79 kg)

1-1/2

1-5/8

30-3/4

12-1/2

4-1/2

166 lbs

196 lbs

(38)

(41)

(781)

(318)

(114)

(75 kg)

(89 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

WSHP-SVX01N-EN

49

Unit Dimensions and Weights
Figure 40. GEH 12½-15 tons (150-180) 60 Hz, right return; GEH 10-12½ tons (120-150) 50 Hz, right return, waterside
economizer(a)(b)

9 7/8"
(251)
18 1/2"
(470)
56 1/2"
(1435)
42"
(1067)

2 1/4"
(57)

29 3/4"
(756)

48 3/4"
(1238)

1 5/8" (42) OD COPPER TO
FIELD SUPPLY PIPING

1 1/2" (38) NPTI FOR
FIELD RETURN PIPING
12"
(305)

5 3/8"
(137)

(a) Entering water is on the AB port.
(b) Field piping required on waterside economizer.

Table 29. GEH 12½-15 tons (150-180) 60 Hz, right return; GEH 10-12½ tons (120-150) 50 Hz, right return, waterside
economizer
GEH (60 Hz)

GEH (50 Hz)

150

120

180

150

Hanging Weight

Shipping Weight

138 lbs

168 lbs

(63 kg)

(76 kg)

144 lbs

174 lbs

(65 kg)

(79 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

Table 30. GEH 12½-15 tons (150-180) 60 Hz, right return; GEH 10-12½ tons (120-150) 50 Hz, left return, waterside
economizer
GEH (60 Hz)
150 - 180

GEH (50 Hz)
120-150

Hanging Weight

Shipping Weight

213 lbs

243 lbs

(97 kg)

(110 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

50

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 41. GEH 12½-15 tons (150-180) 60 Hz, left return; GEH 10-12½ tons (120-150) 50 Hz, left return, waterside
economizer(a)(b)

9 7/8"
(251)
18 1/2"
(470)
56 1/2"
(1435)
42"
(1067)

2 1/4"
(57)

29 3/4"
(756)

1 5/8" (42) OD COPPER TO
FIELD SUPPLY PIPING

27 1/8"
(689)

1 1/2" (38) NPTI FOR
FIELD RETURN PIPING
12"
(305)

5 3/8"
(137)
(a) Entering water is on the AB port.
(b) Field piping required on waterside economizer.

WSHP-SVX01N-EN

51

Unit Dimensions and Weights
Figure 42. GEV 6-10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz, waterside economizer(a)

(a) Entering water is on the AB port.

Table 31. GEV 6-10 tons (072-120) 60 Hz; 6 and 7½ ton (072 and 090) 50 Hz, waterside economizer
Unit (60 Hz)

Unit (50 Hz)

072

—

090

072

120

090

C

Hanging
Weight

Shipping
Weight

A

B

1-1/4

1-3/8

4

148 lbs

178 lbs

(32)

(35)

(102)

(67 kg)

(81 kg)

1-1/4

1-1/4

4

168 lbs

198 lbs

(32)

(32)

(102)

(76 kg)

(90 kg)

1-1/2

1-5/8

4-3/8

207 lbs

237 lbs

(38)

(41)

(111)

(94 kg)

(108 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

52

WSHP-SVX01N-EN

Unit Dimensions and Weights
Figure 43. GEV 12½-25 tons (150-300), waterside economizer(a)

(a) Entering water is on the AB port.

Table 32. GEV 12½-25 tons (150-300), waterside economizer
GEV (60 Hz)

GEV (50 Hz)

150-180

120-150

240

180

300

240

A
NPTI

B
I.D.

C

D

1-1/2

1-5/8

15-7/8

4-3/8

275 lbs

305 lbs

(38)

(41)

(403)

(111)

(125 kg)

(138 kg)

Hanging Weight Shipping Weight

2

2-1/8

16-1/4

4-7/8

310 lbs

340 lbs

(51)

(54)

(413)

(124)

(141 kg)

(154 kg)

2

2-1/8

16-1/4

4-7/8

395 lbs

425 lbs

(51)

(54)

(413)

(124)

(179 kg)

(193 kg)

Note: All dimensions are in inches followed by millimeters in parenthesis.

Table 33. Unit weights GEH ½-5 ton (60 Hz)
GEH

006

009

012

015

018

024

030

036

042

048

Net Weight (lbs.)

165

165

173

173

248

253

253

288

288

398

060
398

Ship Weight (lbs.)

195

195

203

203

268

285

285

318

318

428

428

Table 34. Unit weights GEV ½-5 ton (60 Hz)
Model GEV

006

009

012

015

018

024

030

036

042

048

060

Net Weight (lbs.)

165

165

173

173

248

253

253

288

288

348

349

Ship Weight (lbs.)

195

195

203

203

268

285

285

308

308

396

396

WSHP-SVX01N-EN

53

Unit Dimensions and Weights
Figure 44. Waterside economizer coil piping diagram
Note: (applicable only to 6 to 25 ton models)

Unit
Water
Outlet

Unit Heat
Exchanger

WSE Coil
Outlet

Unit
Water
Inlet

WSE Coil
Inlet
WSE
Coil

TEE

Port A
Port AB
3 Way Valve

Please match the
entering water
port marking with
the marking label
on the valve prior
to using this
diagram.

54

Port B
Entering Water

WSHP-SVX01N-EN

Unit Dimensions and Weights
Table 35.

Figure 45. Weight distribution ½-6 ton GEH/EXH

Unit weights EXV ½-6 ton

EXV (60 Hz)

Shipping Weight
with pallet (lbs)

Unit Weight without
pallet (lbs)

006

195

165

009

195

165

012

203

173

015

203

173

018

284

264

024

301

269

030

319

299

036

333

313

042

402

381

048

422

374

060

442

394

070

482

434

Figure 46. Weight distribution GEH 6-15 ton
Table 36.

Unit weights EXH ½-6 ton

EXH (60 Hz)

Shipping Weight
with pallet (lbs)

Unit Weight without
pallet (lbs)

006

195

165

009

195

165

012

203

173

015

203

173

018

284

264

024

301

269

030

329

299

036

343

313

042

461

431

048

454

424

060

474

444

070

514

484

Weight Distribution for Hanging the GEH
and EXH Model
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
Approximate weight distribution for proper hanging of the
GEH and EXH unit is indicated by weight distribution ½-6
ton GEH/EXH Figure 45, p. 55.
Tolerance on the weights determined are ±15%.
Total weights for each unit size are listed in Table 33,
p. 53,Table 34, p. 53 and Table 35, p. 55.

WSHP-SVX01N-EN

55

Installation
Main Electrical
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.

General Installation Checks
The checklist below is a summary of the steps required to
successfully install a commercial unit.This checklist is
intended to acquaint the installing personnel with what is
required in the installation process. It does not replace the
detailed instructions that are in the applicable sections of
this manual.
1. Remove packaging and inspect the unit. Check the unit
for shipping damage and material shortage; file a
freight claim and notify appropriate sales
representation.
The GEH/V ½-5 ton and EXH/V ½-6 ton units have been
anchored to the skid by (2) shipping bolts.The removal of
these bolts will require a 3/8 (9.7 mm) ratchet with a ½ (12.7
mm) socket.
The GEV 6–25 ton units have been anchored to the skid
with (4) angle brackets. Remove these brackets before
lifting unit into place.
The GEH 6–15 ton units are anchored to the cross brace of
the skid with (4) wood screws. Remove these screws prior
to lifting the unit into place.
2. Verify the correct model, options and voltage from the
unit nameplate.
3. Pull out all field attached parts (i.e. filter rack, duct
collar, filter and mounting screws) from the unit
packaging for field mounting.
4. Verify the installation location of the unit will provide
the required clearance for proper operation.
5. Remove refrigeration access panel and inspect the
unit. Be certain the refrigerant tubing has clearance
from adjacent parts.
6. Fabricate and install duct work
7.

Install and connect a condensate drain line and trap to
the drain connection.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
1. Verify the power supply complies with the unit
nameplate specifications.
2. Inspect all control panel components; tighten any
loose connections.
3. Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect switch
and to the main compressor contactor/power block
1K1 (compressor contactor on the ½-5 ton) for GEH/V
½-5 ton and EXH/V ½-6 ton units or 1TB1 for GEH/V 625 ton equipment in the unit control panel.
4. Install proper grounding wires to an earth ground. EXH
and EXV 460 V units require a neutral (a four wire
system).
Note: All field-installed wiring must comply with NEC
and applicable local codes.

Electric Heat Requirements
5. Verify that the power supply complies with the electric
heater specifications on the unit and heater nameplate.
6. Inspect the heater junction box and control panel;
tighten any loose connections.
7.

Check electric heat circuits for continuity.

Low Voltage Wiring Requirements
8. Install the zone sensor or thermostat.
9. Connect properly sized control wiring to the proper
termination points between the zone sensor or
thermostat and the unit control panel.

Filter Installation
Each unit ships with 1"(25.4 mm) or 2"(50.8 mm)
throwaway filters. 2" MERV 8 or 2" MERV 13 filters are also
available options.The quantity of filters is determined by
unit size.The GEH 1/2-5 ton and EXH units require field
installation of the 1" or 2" ducted filters rack. All sheet
metal bracket, filter and hardware are in a box located on
the side of the unit within the unit packaging. All ½-25 ton
verticals and GEH 6–15 ton horizontal units ship with the
filter rack and filters factory installed.
Note: Do not operate the unit without filters.

56

WSHP-SVX01N-EN

Installation

Supply-Air Ductwork

Figure 48. Flexible return-air connector (field provided)

Horizontal ½-5 ton and EXHF units require duct flanges to
be field installed.The duct flange ships in a box on the side
of the unit. Install the flange with (8) 3/8 in. (213 mm)
factory supplied screws.

SUPPLY-AIR

Install the 1 in. (25.4 mm) supply-air duct flange to the
vertical and horizontal equipment with the
(8) 5/16 in. (7.94 mm) factory-supplied screws.The duct
collar assembly for each unit is shipped with the unit in the
same box where the IOM manual is located.

RETURN

AIR

When attaching the field ductwork to the unit, provide a
watertight flexible connector at the unit to prevent
operating sounds from transmitting through the
ductwork. See Figure 47, p. 57.

RETURN-AIR BOOT
(FIELD PROVIDED)

DUCT COLLAR
(FACTORY PROVIDED)

Elbows with turning vanes or splitters are recommended
to minimize air noise due to turbulence and to reduce static
pressure.
Figure 47.

Flexible supply-air connector (field provided)

SUPPLY-AIR
BOOT (FIELD
SUPPLIED)

1-INCH DUCT COLLAR
(FACTORY PROVIDED)

Ducted Panel
The return-air arrangement may be easily converted from
a free return-air system, to a ducted return-air system with
the addition of a return-air side panel. By replacing the
filter racks with the return-air panel, a complete seal from
the duct to the unit is possible.The 1½ duct flange
facilitates ease of field connection to the duct system.This
accessory is typically used when the return-air filter is
placed in a built-in ceiling grille, or placed within a field
provided filter rack assembly.
Figure 49. Return-air duct panel

Return-Air Ductwork
Install the 1”-2” (25.4 mm/50.8 mm) adjustable filter rack to
the horizontal equipment only with the use of (4) 5/16 in.
(7.94 mm) factory supplied screws.The vertical equipment
factory ships with the filter rack and filter(s) installed.
When attaching the field ductwork to the unit, provide a
water-tight flexible connector at the unit to prevent
operating sounds from transmitting through the
ductwork.
Elbows with turning vanes or splitters are recommended
to minimize air noise due to turbulence and to reduce static
pressure.
Table 37.

WSHP-SVX01N-EN

Opening size and part number GEH

Unit Size
(60 Hz)

Unit Size
(50 Hz)

006-015

006-012

17½ in.
13 in.
(445 mm) (330 mm)

4474 1133 0100

018-030

015-024

20½ in.
16 in.
(521 mm) (406 mm)

4474 5628 0100

036-042

030-036

22½ in. 17 in. (432
(572 mm)
mm)

4474 1135 0100

048-060

042-060

26½ in. 19 in. (483
(673 mm)
mm)

4474 1136 0100

A

B

Duct Collar
Part Number

57

Installation
Table 39. Ducted filter opening size

Figure 50. Install return-air duct panel

1"

Unit Top

op
it T

Unit Side

Un

Install the returnair duct panel to
the return-air
opening with the
six screws
provided for the
filter rack
assembly.

A

3 3/4"

Unit Side

B

B (in.)

C (in.)

30.7

26.6

5.5

EXH 006-015

21.1

15.4

5.4

EXH 018-030

24.5

18.4

5.6

EXH 036-042

26.4

19.4

5.5

EXH 048-070

30.7

21.4

5.5

EXV 006-015

20.7

17.1

5.5

EXV 018-030

20.7

23.1

5.5

EXV 036-042

25.7

22.4

4.3

EXV 048-070

30.7

26.6

5.5

Dual Filtration (GEH ½-5 ton and EXH ½-6
ton)
Note: The dual-filtration design is typically used in a freereturn application.

Opening size and part number EXH

EXH (60 hz)

A (in.)

B (in.)

Duct Collar Part
Number

006-015

17-1/2

13

447411330100

018-024

20-1/2

16

447456280100

030-036

22-1/2

17

447411350100

042-070

26-1/2

19

447411360100

Ducted Filter Rack

The horizontal, GEH and EXH model, allows the installer
flexibility in design applications such as a dual filtration
option.With the dual filtration design, the unit will contain
a lower static which translates into a decrease in filter
maintenance. For installation of a dual filtration accessory
for the GEH and EXH model, verify that an extra set of
return-air filter racks and filter have been ordered from the
factory.This accessory will be shipped separate from the
unit, and should be located in a separate box than the unit.
1. Remove the return-air side panel from the GEH and
EXH unit.This panel is held in place by screws.

When it is necessary
to have filter access at
the unit in a ducted
return, a ducted filter
rack is available.This
option allows access
to the filter at the unit.
Vertical unit filter
racks are available in
right or left access
configurations.
Horizontal units are
available in top,
bottom or side access
configurations.

Figure 51.

Table 39. Ducted filter opening size
Unit Size

A (in.)

B (in.)

C (in.)

GEH 006-015

21.1

15.4

5.4

GEH 018-030

24.5

18.4

5.6

GEH 036-042

26.4

19.4

5.5

GEH 048-060

30.7

21.4

5.5

GEV 006-015

20.7

17.1

5.5

GEV 018-030

20.7

23.1

5.5

GEV 036-042

25.7

22.4

4.3

58

A (in.)

Note: All dimensions in inches

DUCT PANEL
with 1 1/2"-FLANGE

Table 38.

Unit Size
GEV 048-060

Side panel

2. Install the top/bottom filter rack at the new opening.
The adjustable filter rack is held in place with four
screws that once held the panel.

WSHP-SVX01N-EN

Installation
Figure 52. Install top/bottom filter rack

3. Slope horizontal units in two directions.The unit
should contain a dual ¼-12 pitch toward the drain
connection.This will insure proper drainage of the
unit. All plumbing to the unit should conform per
national and local codes and is the responsibility of the
contractor.
Figure 54. Hanging the unit

3. Install the 1”or 2”(25.4 mm/50.8 mm) filter.
RETURN-AIR

SUPPLY-AIR

Figure 53. Install filter

3/8" ALL-THREAD
(BY OTHERS)
3/8" WASHER / NUT
(BY OTHERS)

Condensate Drain Connection
Figure 55. Negative pressure system

Sound Attenuation Pad
For sound-sensitive installations, a vibration pad (field
provided) should be placed beneath the horizontal or
vertical equipment. For the horizontal unit, the pad should
be approximately twice the size of the unit foot print. For
the vertical unit, the pad should be ½ in. (12.7 mm) thick,
and equal to the overall unit foot print.

Hanging the Horizontal Unit
WARNING
Risk of Unit Dropping!
You MUST mount the unit to an area of the ceiling
strong enough to support the weight of that unit. If
unsure, you MUST confirm with a structural engineer.
Failure to do so could result in unit dropping from the
ceiling which could result in death or serious injury, and
equipment damage.
To hang the horizontal configuration (see Figure 54, p. 59):
1. Install the hanging isolators (located in the return-air
section of the unit) into the four hanging brackets.
2. Secure the equipment to a joist, concrete, etc. with the
use of 3/8 in. (9.7 mm) field provided (all-thread) rod.
Each corner should contain field provided nuts and
washers to complete the hanging installation.

WSHP-SVX01N-EN

Install proper trapping to the equipment.The unit drain
connection is ¾ in. NPT for all GEV ½-25 ton and GEH ½5 ton and EXH/V ½-6 ton models. For 6-15 ton GEH models,
the drain connection is ½ in. PVC schedule 40 pipe.
When designing the condensate trap for the water-source
system, it is important to consider the unit draw-thru
design requiring negative pressure trapping.
In a properly trapped system, when condensate forms
during normal operation, the water level in the trap rises
until there is a constant flow. It is imperative to maintain
water in the trap and not allow the trap to dry out during
heating season. Keeping trap primed at all times will
enable the water to flow properly. See Figure 55, p. 59 for

59

Installation
appropriate dimensions required in a negative pressure
system.

Supply/Return Pipe Connections

A steel braided hose without a shut-off device is the least
expensive means of connecting the heat pump to the
supply/return water loop.

Deluxe ball valve hose kit
Figure 56. Supply/return pipe connections
Actuator
Ball Valve w/PT
Valve Body

RETURN
TO
LOOP

WATER-OUT

Ball Valve w/PT

SUPPLY
FROM
CENTRAL
PUMP

WATER-IN
AUTOMATIC BALANCING
HOSE KIT

Optional
Strainer/
Blowdown Valve
w/Hose Connector

Connect the supply and return hoses to the water-inlet
(from supply) and water-outlet (to return) of the unit. For
vibration isolation, it is recommended that flexible steel
braided hoses be installed instead of hard piping the
equipment to the main loop system. Figure 56, p. 60
shows connection of a Hays Measurflo® balancing hose
kit to the water-in and water-out of a vertical unit.

With the addition of a shut-off device on the supply and
return of the system, the unit may be isolated during
service or maintenance situation.This system may be
installed as a wide open (full water flow to the equipment)
design, or manually balanced by utilizing the pressure/
temperature ports on the top of the ball valve/shut-off
device.

Note: Figure 56, p. 60 example incorporates the Hays
Measurflo® balancing hose kit and a
2-position isolation valve into the system design.
An isolation valve is often used in variable speed
pumping applications.The isolation valve is
designed to stop water flow to the unit during non
operation times.This allows the loop water pumps
to run only when a requirement for pumping is
needed for greater energy efficiency of the overall
system design.

Manual balance hose kit

Types of Hose Connections
Whether installing the units in a central pump (main/
auxiliary pump for the entire zone) design, or as a
distributed pump (1-pump per unit) design, a shut-off
device and flexible hose is recommended to transition
from the hard piping of the closed or open loop water
system to the unit.There are multiple hose combinations
which may be used to fit the design or specification criteria
for the installation.

Flexible hoses

Mesurmeter
w/PT’s

Actuator

Valve Body

Ball Valve w/PT
Ball Valve w/PT

Optional
Strainer/
Blowdown Valve
w/Hose Connector

A circuit setter provides a means of manually balancing
the water flow to the heat pump.This manual in-line
balancing method is accurate up to ±20%. In order to
determine flow rate, the user must record both handle
position, and differential pressure drop.Then, the user
must consult a chart containing both pieces of information
and make the necessary adjustments to the circuit setter.

Return

Supply

60

WSHP-SVX01N-EN

Installation
6. Shut down pumps and supplementary heat system.
Reconnect the hoses placing the water-to-refrigerant
heat exchanger in the water circulating system.

Automatic balance hose kit
Actuator
Inline Mesurflo
Balance Valve
Ball Valve
Valve Body

Note: Vents should be open when the pumps and
supplementary heat system are shut down.

Field Installed Power Wiring

Ball Valve w/PT

Optional
Strainer/
Blowdown Valve
w/Hose Connector

For self balancing flow control, a Hays Measurflo®
balancing hose kit provides a constant flow rate over the
pressure differential range of 2 – 80 psid. As system
pressures change (through the addition of heat pumps, for
example) each individual flow control valve will
automatically adjust to the new system conditions.
Additional accessories, such as a strainer are
recommended for use to eliminate contaminants from
entering the co-axial water-to-refrigerant heat exchanger.

Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose
connectors should be doubled back to complete the water
circuit external to the unit (avoiding trash settle-out in the
condenser). An extra pipe may be necessary to connect
the hose kits.
1. Water circulation system should be filled with clean
water using the water make up connections.
Note: Air vents should be open during filling.
2. With the air vents closed, start the circulating pump
and then crack the air vents to bleed off the trapped air,
assuring circulation through all components of the
system.
Note: Make up water must be available to the system to
replace the volume formerly occupied by the air
that is bled off.
3. With the air vented and the water circulating, the entire
system should be checked for leaks with repairs made
as required.
4. Operate the supplementary heat system (boiler)
making checks per manufacturer’s instructions. During
this operation, visual checks should be made for leaks
that may have occurred due to increased heat. Repair
as required.
5. Open the system at the lowest point for the initial blow
down (making sure the make up water is equal to the
water being dumped). Continue blow down until the
water leaving the drain runs clear, but not less than 2
hours.

WSHP-SVX01N-EN

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.

NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
Verify that the power supply available is compatible with
the unit’s nameplate. Use only copper conductors to
connect the power supply to the unit.

Main Unit Power Wiring
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.
A field supplied disconnect switch must be installed at or
near the unit in accordance with the National Electric Code
(NEC latest edition).
Location of the applicable electric service entrance for
HIGH (line voltage) may be found in the Dimensions
section of this manual.
The high-voltage connection is made at the 1K1 contactor
or 1TB1 power block inside the unit control box. See
Figure 57, p. 62. Refer to the customer connection diagram
that is shipped with the unit for specific termination points.
Provide proper grounding for the unit in accordance with
the local and national codes.

61

Installation
Figure 57.

In air-flows from adjacent zones or other units.

Power wiring example

Controls Using 24 VAC
Before installing any wire, refer to the electrical access
locations in the “Unit Dimensions and Weights,” p. 14 of
this manual.
Ensure that the AC control wiring between the controls
and the unit termination point does not exceed 3 Ohms/
conductor for the length of the run.

NOTICE:
Component Failure!
Control Power Transformer
The 24 V control power transformers are to be used only
with the accessories called out in this manual. A 50 VA
transformer is externally fused.Transformers rated
greater than 50 VA are equipped with circuit breakers. If a
circuit breaker trips, turn OFF all power to the unit before
attempting to reset it.

WARNING
Hazardous Voltage!

Resistance in excess of 3 Ohms per conductor could
result in component failure due to insufficient AC
voltage supply.
Check all loads and conductors for grounds, shorts, and
mis-wiring.
Use copper conductors unless otherwise specified.
Do not run the AC low-voltage wiring in the same conduit
with the high voltage power wiring.
Table 40.

Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
The transformer is located in the control panel.

Thermostat Location

24V AC conductors

Distance from unit to
control

Recommended wire size

000-460 ft

18 gauge

461-732 ft

16 gauge

733-1000 ft

14 gauge

Figure 59. Low-voltage connection (GEH/V ½-5 ton and
EXH/V(a) ½-6 ton equipment)
Basic Controls Wall Mounted Thermostat

Figure 58. Thermostat/sensor location

NO
NO

5 Feet

YES
NO
O

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Deluxe Controls Wall Mounted Thermostat
1TB1

1TB1
24 VAC
FAN
REVERSING VALVE (COOL)
COMPRESSOR & VAR SPD PUMP SOLENOID
24 VAC GENERAL ALARM OUTPUT
24 VAC COMMON & VAR SPD PUMP SOLENOID

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

24 VAC
FAN
REVERSING VALVE (COOL)
COMPRESSOR & VAR SPD PUMP SOLENOID
24 VAC COMMON & VAR SPD PUMP SOLENOID
ELECTRIC HEAT
24 VAC COMPRESSOR DISABLE INPUT
24 VAC COMPRESSOR DISABLE INPUT

ALARM CONTACT OUTPUT
ALARM CONTACT OUTPUT

Deluxe Controls with Reheat
1TB1

Location of the thermostat or zone sensor is an important
element of effective room control.
Areas where the thermostat or zone sensor should not be
located include:
•

Behind doors or corners

•

Near hot or cold air ducts

•

Near radiant heat (heat emitted from appliances or the
sun)

•

Near concealed pipes or chimneys

•

On outside walls or other non conditioned surfaces

62

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

24 VAC
FAN
REVERSING VALVE (COOL)
COMPRESSOR
24 VAC COMMON & VAR SPD PUMP SOLENOID

24 VAC COMPRESSOR DISABLE INPUT
24 VAC COMPRESSOR DISABLE INPUT
HUMIDISTAT
VAR SPD PUMP SOLENOID

ALARM CONTACT OUTPUT
ALARM CONTACT OUTPUT

(a) Basic controls not available on EXH/V units

Low-voltage connection diagrams for basic and deluxe 24
V control packages mounted on ½-6 ton equipment sizes
are shown in Figure 59, p. 62.
WSHP-SVX01N-EN

Installation
Figure 60. Low-voltage connection (GEH/V 6-25 ton)
Deluxe Controls with
-all Heat Pump Units w/ Reheat
using X13511090010 (T8511)
1TB2

1TB2
24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1)
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
WATER ISOLATION VALVE
3RD STAGE HEAT (W3)
NOT USED

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Deluxe Controls with
-all Heat Pump Units w/ Reheat
using X13511091010/X13511092010 (T7300)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1)
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
WATER ISOLATION VALVE
3RD STAGE HEAT (W1)
NOT USED

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.
1. Remove service access panel at the unit front.

Figure 61. Service access panel
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511090010 (T8511)
1TB2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511091010/X13511092010 (T7300)
1TB2

24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
NOT USED
3RD STAGE HEAT (W3)
NOT USED

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

24 VAC (R)
FAN (G)
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
COMPRESSOR DISABLE
ALARM
ALARM
ELECTRIC HEAT
ELECTRIC HEAT
HUMIDISTAT
NOT USED
3RD STAGE HEAT (W1)
NOT USED

Low-voltage connection diagrams for deluxe 24V control
packages for these thermostats mounted on 6-25 ton
equipment sizes are shown in Figure 60, p. 63.

2. Find the blower motor relay.The relay is located in
Figure 62, p. 63.The relay location is consistent in all
control configurations.
Figure 62. Relay location

For controls using DC analog input/outputs, see
appropriate installation, operation and diagnostic
manuals for connection, WSHP-PRB002-EN (ZN524).

Blower Motor Speed-Tap Retrofit
Note: For GEH/V ½-5 ton units only.
Motors installed in the unit include 4-speed or 3-speed
configurations. All voltages include a 4-speed
configuration, with the exception of 380V, 415V, 460V
which contain a 3-speed arrangement and 575V which
contains a 2-speed arrangement.To modify the rpm of the
motor, the following steps must be followed.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

WSHP-SVX01N-EN

Removing Speed-tap Wire
3. For units w/o Hot Gas Reheat: Remove undesired
speed-tap wire from 1K4 relay at spade 3. Wire tie the
lead, to eliminate a short.
4. For units with Hot Gas Reheat: Remove undesired
speed-tap wire from 1K8 relay at spade 6. Wire tie the
lead, to eliminate a short. Hot Gas Reheat requires both
speed taps to be adjusted to enable reheat as the lower
speed tap.

63

Installation

Hole Plug Installation

Figure 63. Wiring change

Figure 65. Hole plug installation

Connecting Desired Speed-tap Wire
5. For units without Hot Gas Reheat: Select desired
speed-tap wire. Connect desired speed tap wire to 1K4
relay at spade 3.
6. For units with Hot Gas Reheat Select desired
speed-tap wire. Connect desired speed tap wire to 1K8
relay at spade 6.
Figure 64. Connecting speed-tap wire

1. Locate two Hayco plastic plugs enclosed with the
Installation, Operation, and Maintenance manual.
2. Use these plugs to plug the two shipping bolt holes in
the bottom of the GEVE/EVXVE units after shipping
bolt removal.

Air Flow Adjustment
Note: GEH/V 6-25 ton units only.
To increase cfm, loosen the turns open set screw on the
sheave, and turn the sheave clockwise.To decrease cfm,
Loosen the turns open set screw on the sheave, and turn
the sheave counterclockwise.
To increase belt tension, loosen the adjustment bolt and
pull motor mounting plate back until the belt is tight.
Tighten the adjustment bolt after the belt has reached the
desired tension.
See Figure 66, p. 65 for fan motor and sheave adjustment

7.

Install service front panel. Reconnect power to the unit.

Table 41.

4-speed motor (115, 208, 230, 265)
Lead Colors

Lead

Black

Blue

Orange

Red

Speed

High

Medium High

Medium Low

Low

Table 42.

WARNING
Rotating Components!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

3-speed motor (380, 415, 460)
Lead Colors

Lead

Black

Blue

Orange

Speed

High

Medium

Low

Note: When using the medium or low speed tap, the purple wire must be
jumpered to the high speed tap (blk).

Table 43.

2-speed motor (575)
Lead Colors

64

Lead

Black

Blue

Speed

High

Low

WSHP-SVX01N-EN

Installation
Figure 66. Fan motor and sheave adjustment
1.Belt

setting. Connect the power to the unit. If the power is not
disconnected when the DIP switch is set, the motor will not
be programmed to the new setting.

2.Adjustment Bolt and
Plate

Profile A = 110% of rated air flow

3.Sheave

Profile C = 90% of rated air flow

Profile B = 100% of rated air flow
Profile D = 80% of rated air flow

1

Waterside Economizer Installation
2

Note: GEH ½-5 and EXH ½-6 ton units.

WARNING
Hazardous Voltage!
3

Figure 67.

ECM control board and dip switch setting

Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

WARNING
Proper Field Wiring and Grounding
Required!
Dip switch to
select profile

All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.
The following steps were sequenced to aid in the
installation and mating of a water side economizer to a
water-source heat pump (GEH ½-5 ton) and (EXH 1½-6
ton).
1. Remove the control side service panel of the watersource heat pump unit.
2. Remove rubber isolation grommets from the return-air
section. Place them in a convenient location.
3. Attach ducted panel to the water-source heat pump
unit with six factory provided screws.This panel is
shipped loose with the water-source heat pump but
must be field installed to the unit.

Note: EXH/V ½ -6 ton high efficiency units only:
Units are shipped from the factory on profile
setting B.
To adjust the cfm, disconnect the power to the unit. Set the
DIP switch located in the control box to the desired profile
WSHP-SVX01N-EN

65

Installation
Figure 68. Step 3

6. Install the SUPPLY and RETURN hoses to the:
a. 2-position valve’s threaded connection
b. water-out threaded connection of the water-source
heat pump
Figure 71.

Step 6

4. Attach the water side economizing unit to the ducted
panel of the water-source heat pump with 10-factory
provided screws.The economizing package fits to the
outside of the of the water-source heat pump.Trane
recommends the mating of the systems be made via 3screws spaced evenly across the top, 3-screws spaced
evenly across the bottom (installed immediately after
hanging the unit), and 2-screws on each side.
Note: Waterside economizer option is configured for
right return. Left return requires additional field
piping.
Figure 69. Step 4

7. Verify the control board for the water side economizer
is located at the back of the control box.The
temperature rating of this board is factory set to 55ºF.
For units with boilerless (electric heat) control and
water side economizer, the boilerless control board is
factory set to 45ºF.
Figure 72. Step 7

5. Install the 18-inch steel braided hose between the
upper most piping connection of the economizer, and
the water-in of the heat pump.The hose is shipped
loose with the water-side economizer.
Figure 70. Step 5

8. Thread the bulb and wire through the low voltage hole
of the water-source heat pump. See Figure 73, p. 67.

66

WSHP-SVX01N-EN

Installation
Figure 73. Step 8

9. Wire-tie the sensor to the water SUPPLY side of the
piping (ON, or BEFORE) the 2-position valve. See
Figure 74, p. 67.
Figure 74.

Step 9

Figure 76. Step 11

12. Wire the valve to the terminal strip according to the
unit wire diagram located on the service control panel.
RED = 1TB1-14
BLK = 1TB1-18
WHT = 1TB1-15
See Figure 77, p. 67.
Figure 77.

Step 12

10. Bundle excess sensor wire, and wire tie the bundle
neatly. See Figure 75, p. 67.
Figure 75. Step 10

13. Bundle excess valve wire, and wire tie the bundle
neatly. See Figure 78, p. 67.
Figure 78. Step 13

11. Thread the valve’s wire lead through the low voltage
hole of the heat pump. See Figure 76, p. 67.
14. Install control side service panel.

WSHP-SVX01N-EN

67

Installation
15. Install the hanging isolation grommets (see Figure 79,
p. 68) into the hanging bracketsThe unit isolators were
located in the return-air section of the unit. See Step 2.
Isolators for the economizing package are located with
the economizer.

Table 44.

Economizer part numbers

GEH Unit 60
Hz

GEH Unit 50
Hz

Waterside Economizer Part
Number

006-015

006-012

4474 1690 0100

018-030

015-024

4474 7072 0100

036-042

030-036

4474 1692 0100

048-060

042-048

4474 1693 0100

EXH Unit 60
hz

EXH Unit 50
Hz

Waterside Economizer Part
Number

006-015

—

4474 1690 0100

018-024

—

4474 7072 0100

030-036

—

4474 1692 0100

042-070

—

4474 1639 0100

Note: GEH ½-5 ton and EXH ½-6 ton.
Figure 79. Step 15

Waterside Economizer Installation for GEH
and GEV 6 to 25 Ton Models
16. Insulate the economizing piping package and the
supply/return/by-pass hoses (3-hoses) via field
provided pipe insulation. Insulating the piping will stop
condensation from forming on the pipe and dripping
onto the ceiling tiles.
Note: Trane does not provide insulation on the
economizing piping package.This insulation must
be field provided and field installed.
Note: Trane does not provide condensate overflow
protection of the waterside economizer.This must
be field provided and installed.
17. Install filter rack (top and bottom) to the economizing
package.The filter rack is located in the unit’s
packaging along with the filter.
18. Hang unit. See Figure 54, p. 59 for hanging of the
packaged unit. Bottom screws referenced in Step 4
must be installed at this time.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow codes could result in death or serious injury.

19. Field pipe the drain lines of the waterside economizer
and water-source heat pump together prior to
installing a condensate trap (see Figure 80, p. 68. See
Figure 55, p. 59 for proper trapping of condensation.

1. Remove the filter frame from the unit.

Figure 80. Step 19

3. Remove the control box service panel from the unit.

2. Remove the waterside service panel from the unit.
4. Remove the economizer and miscellaneous mounting
parts from it’s packaging.
5. GEV ONLY: Mount the economizer support angle (4475
1637 0100) found in the economizer packaging in the
same holes of the return air filter frame removed in
Step 1.The support angle screws into the unit roof.
6. GEV ONLY: Hang the economizer assembly from the
economizer support angle mounted in Step 5.
7.

68

Secure the economizer to the unit using the four plates
(4475 1630 0100) found in the economizer packaging.
Two plates should be applied to each economizer side.
GEV ONLY: Secure the bracket on the bottom of the

WSHP-SVX01N-EN

Installation
economizer cabinet to the unit compressor
compartment center post.
8. Install the field portion of the water piping and the 3way valve together.
Note: Entering water is on the AB port.
9. Verify the control board for the waterside economizer
is located at the back of the control box.The
temperature rating of this board is factory set to 55ºF.

being sucked through the drain line causing
condensate to spit or build-up in the economizer or unit
drain pans. Field pipe the drain lines of the waterside
economizer and water-source heat pump together
prior to installing a condensate trap. See page
“Condensate Drain Connection,” p. 59 for proper
trapping of condensation.

10. Thread the economizer’s entering water temperature
sensor (4RT1) through the water-in line of the watersource heat pump upstream from the valve.This
sensor is used by the economizer’s 3-way valve to
determine if water flow should be directed through the
waterside economizing coil.
11. Tie wrap the thermistor to the water line (supply side)
upstream of the water pipe to the economizer.The
thermistor must be situated so that the thermistor is
capable of reading the actual entering water
temperature regardless of the economizer’s on or off
situation.
12. Insulate the thermistor with tubing insulation.
13. Tie wrap each end of the tubing insulation to prevent
air filtration.The tie wraps and insulation are located in
a bag and shipped inside of the unit.
14. Thread the factory wire harness through the low
voltage hole of the heat pump to the 3-way valve’s wire
harness.
15. Connect the factory installed wire harness to the to the
wire harness supplied with the 3-way valve (see
Table 45, p. 69).
Table 45.

Actuator/factory harness wire table

Actuator Wire # Color

Factory Harness Wire # Color

1 BLK

=

25L-Black

2 WHT

=

23T-White

3 WHT

=

73A-White

16. Bundle excess valve wire, and wire tie the bundle
neatly.
17. Install control side service panel to the heat pump.
18. Install the unit filter frame to the economizing inlet.
19. Insulate the economizing piping package with field
supplied pipe insulation. Insulating the piping will help
stop condensation from forming on the pipe.
Note: Trane does not provide insulation on the
economizing piping package.This insulation must
be field provided and field installed.
Note: Trane does not provide condensate overflow
protection of the waterside economizer.This must
be field provided and field installed.
20. Install waterside service panel to the heat pump.
21. The economizer condensate line must be trapped prior
to the unit’s drain line.This helps prevent air from
WSHP-SVX01N-EN

69

Waterside Economizer Start-Up Sequence
1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan
control to AUTO.The compressor should NOT run.
3. Reduce the thermostat setting until the compressor,
reversing valve, solenoid valve, and loop pump are
energized. Adjust water flow utilizing pressure/
temperature plugs and comparing to tables contained
in specification sheet data. Water leaving the heat
exchanger should be warmer than the entering water
temperature (approximately 9-12ºF); blower operation
should be smooth; compressor and blower amps
should be within data plate ratings; the suction line
should be cool with no frost observed in the refrigerant
circuit.
4. Check the cooling refrigerant pressures against values
in Table 54, p. 94.
Note: If cooling mode is activated, and the entering water
temperature of the heat pump falls below 55ºF, the
2-position, water side economizing valve will
become energized (open) and compressor
operation will halt allowing for free cooling in the
space.
5. Turn the thermostat system switch to the OFF position.
Unit should stop running and the reversing valve
should de-energize.

70

6. Leave unit off for approximately FIVE minutes to allow
for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is
energized. Warm air should blow from the register. A
water temperature decrease of approximately 5-9°F
leaving the heat exchanger should be noted.The
blower and compressor operation should be smooth
with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values
in Table 54, p. 94.
Note: For units with boilerless electric heat option: In
heating mode, if the entering water temperature of
the heat pump falls below 45ºF, the electric heater
will be energized, and compressor operation will
halt. Once the entering water temperature rises
above 50ºF, the boilerless controls returns the unit
to normal operation.
11. Set the thermostat to maintain the desired space
temperature.
12. Instruct the owner on system operation.

WSHP-SVX01N-EN

Waterside Economizer Start-Up Sequence
Table 46. Waterside economizing three-way valve specifications
Unit Size (60 Hz) Unit Size (50 Hz)

Valve Conn.
Size

Valve Pres.
Rating

"Valve Closeoff pressure

Valve Temp.
Range

Actuator

GEH006-015

GEH006-012

1/2 FPT

600 psi

200 psi

"0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
10 Cv at full port

GEH018-042

GEH015-036

3/4 FPT

600 psi

200 psi

"0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
30 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
23 Cv at full port

GEH048-060

GEH042-060

1 FPT

600 psi

200 psi

"0ºF to 212ºF
-18ºC to 121ºC

GEV/GEH
6-7½ Ton

GEV
6 Ton

1¼ FPT

600 psi

200 psi

0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
33 Cv at full port

GEV/GEH
10-15 Ton

GEV/GEH
7½-12½ Ton

1½ FPT

600 psi

200 psi

0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
37 Cv at full port

GEV
20 & 25 Ton

GEV
15 & 20 Ton

2 FPT

600 psi

200 psi

0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
57 Cv at full port

EXH006-015

—

1/2 FPT

600 psi

200 psi

0ºF to 212ºF
-18ºC to 121ºC

Non-spring return type
24 VAC +/- 20%
135 second stroke time
10 Cv at full port

200 psi

0°F to 212°F
-18°C to 121°C

Non-spring return type
24 VAC +/- 20%
135 second stroke time
30 Cv at full port

200 psi

0°F to 212°F
-18°C to 121°C

Non-spring return type
24 VAC +/- 20%
135 second stroke time
23 Cv at full port

EXH 018-036

EXH 042-070

—

—

3/4 FPT

1 FPT

600 psi

600 psi

Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information
pertaining to the economizing water valve, see the valve’s data plate.

WSHP-SVX01N-EN

71

Electrical Data
Table 47.

Electrical data: standard static motors, ½ to 5 tons GEH*/GEV*
Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor
Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps

Model No.

Volts

GEH/GEV006

115/60/1

6.8

5.6

30.0

1

7.5

1.20

1/12

1

8.20

15

0.0

0.0

GEH/GEV006

208/60/1

3.9

3.3

14.0

1

4.2

0.60

1/12

1

4.73

15

0.0

0.0

GEH/GEV006

208/60/1

4.5

3.3

14.0

1

4.2

0.60

1/12

1

5.68

15

0.8

3.9

GEH/GEV006

230/60/1

3.8

3.2

15.0

1

4.2

0.60

1/12

1

4.60

15

0.0

0.0

GEH/GEV006

230/60/1

4.9

3.2

15.0

1

4.2

0.60

1/12

1

6.18

15

1.0

4.3

GEH/GEV006 220-240/50/1

3.4

2.9

17.0

1

4.0

0.52

1/12

1

4.15

15

0.0

0.0

GEH/GEV006 220-240/50/1

7.4

2.9

17.0

1

4.0

0.52

1/12

1

9.19

15

1.6

6.8

GEH/GEV006

265/60/1

3.0

2.5

11.0

1

3.5

0.52

1/12

1

3.65

15

0.0

0.0

GEH/GEV006

265/60/1

5.5

2.5

11.0

1

3.5

0.52

1/12

1

6.92

15

1.3

5.0

GEH/GEV009

115/60/1

7.6

6.4

36.0

1

8.6

1.20

1/12

1

9.20

15

0.0

0.0

GEH/GEV009

208/60/1

4.3

3.7

16.0

1

4.8

0.60

1/12

1

5.23

15

0.0

0.0

GEH/GEV009

208/60/1

6.5

3.7

16.0

1

4.8

0.60

1/12

1

8.14

15

1.2

5.9

GEH/GEV009

230/60/1

4.1

3.5

17.0

1

4.8

0.60

1/12

1

4.98

15

0.0

0.0

GEH/GEV009

230/60/1

7.1

3.5

17.0

1

4.8

0.60

1/12

1

8.90

15

1.5

6.5

GEH/GEV009 220-240/50/1

6.0

5.3

23.0

1

7.4

0.72

1/8

1

7.35

15

0.0

0.0

GEH/GEV009 220-240/50/1

9.8

5.3

23.0

1

7.4

0.72

1/8

1

12.20

15

2.2

9.0

GEH/GEV009

265/60/1

3.3

2.8

13.0

1

3.7

0.52

1/12

1

4.02

15

0.0

0.0

GEH/GEV009

265/60/1

8.1

2.8

13.0

1

3.7

0.52

1/12

1

10.08

15

2.0

7.5

GEH/GEV012

115/60/1

13.7

12.1

58.0

1

16.9

1.57

1/8

1

16.70

25

0.0

0.0

GEH/GEV012

208/60/1

7.0

6.3

30.0

1

8.8

0.70

1/8

1

8.58

15

0.0

0.0

GEH/GEV012

208/60/1

8.5

6.3

27.0

1

8.8

0.70

1/8

1

10.67

15

1.6

7.8

GEH/GEV012

230/60/1

7.0

6.3

30.0

1

8.8

0.70

1/8

1

8.58

15

0.0

0.0

GEH/GEV012

230/60/1

9.4

6.3

30.0

1

8.8

0.70

1/8

1

11.74

15

2.0

8.7

7.4

6.7

30.0

1

9.4

0.72

1/8

1

9.10

15

0.0

0.0

GEH/GEV012 220-240/50/1 12.0

6.7

30.0

1

9.4

0.72

1/8

1

14.96

15

2.7

11.3

GEH/GEV012

265/60/1

5.7

5.0

23.0

1

7.0

0.72

1/8

1

6.97

15

0.0

0.0

GEH/GEV012

265/60/1

10.7

5.0

23.0

1

7.0

0.72

1/8

1

13.40

15

2.7

10.0

GEH/GEV015

208/60/1

8.6

7.9

36.0

1

11.1

0.70

1/8

1

10.58

15

0.0

0.0

GEH/GEV015

208/60/1

10.3

7.9

36.0

1

11.1

0.70

1/8

1

12.89

15

2.0

9.6

GEH/GEV015

230/60/1

8.6

7.9

36.0

1

11.1

0.70

1/8

1

10.58

15

0.0

0.0

GEH/GEV015

230/60/1

11.6

7.9

36.0

1

11.1

0.70

1/8

1

14.46

15

2.5

10.9

9.0

8.2

36.0

1

11.5

0.80

1/8

1

11.05

15

0.0

0.0

GEH/GEV015 220-240/50/1 14.5

8.2

36.0

1

11.5

0.80

1/8

1

18.08

20

3.3

13.7

GEH/GEV015

265/60/1

7.1

6.4

30.0

1

9.0

0.72

1/8

1

8.72

15

0.0

0.0

GEH/GEV015

265/60/1

13.2

6.4

30.0

1

9.0

0.72

1/8

1

16.47

20

3.3

12.5

GEH/GEV018

208/60/1

10.5

9.6

42.0

1

13.4

0.90

1/8

1

12.90

20

0.0

0.0

GEH/GEV018

208/60/1

12.7

9.6

42.0

1

13.4

0.90

1/8

1

15.91

20

2.5

11.8

GEH/GEV018

230/60/1

10.5

9.6

42.0

1

13.4

0.90

1/8

1

12.90

20

0.0

0.0

GEH/GEV018

230/60/1

13.9

9.6

42.0

1

13.4

0.90

1/8

1

17.43

20

3.0

13.0

GEH/GEV018 220-240/50/1 11.1

9.6

54.0

1

15.0

1.53

1/3

1

13.53

20

0.0

0.0

GEH/GEV018 220-240/50/1 19.7

9.6

54.0

1

15.0

1.53

1/3

1

24.57

25

4.4

18.1

GEH/GEV018

7.7

35.0

1

10.8

0.80

1/8

1

10.43

15

0.0

0.0

GEH/GEV012 220-240/50/1

GEH/GEV015 220-240/50/1

265/60/1

8.5

continued on next page

72

WSHP-SVX01N-EN

Electrical Data
Table 47.

Electrical data: standard static motors, ½ to 5 tons (continued)GEH*/GEV*

Model No.

Volts

GEH/GEV018

265/60/1

Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor
Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps
15.9

7.7

35.0

1

10.8

0.80

1/8

1

19.87

20

4.0

15.1

GEH/GEV018 380-415/50/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV018 380-415/50/3

7.0

3.6

28.0

1

5.6

0.95

1/3

1

8.75

15

4.4

6.1

GEH/GEV024

208/60/1

14.9

12.8

58.3

1

20.0

2.10

1/3

1

18.10

30

0.0

0.0

GEH/GEV024

208/60/1

17.8

12.8

58.3

1

20.0

2.10

1/3

1

22.22

30

3.3

15.7

GEH/GEV024

230/60/1

14.9

12.8

58.3

1

20.0

2.10

1/3

1

18.10

30

0.0

0.0

GEH/GEV024

230/60/1

19.5

12.8

58.3

1

20.0

2.10

1/3

1

24.36

30

4.0

17.4

GEH/GEV024 220-240/50/1 12.7

11.2

60.0

1

17.5

1.53

1/3

1

15.53

25

0.0

0.0

GEH/GEV024 220-240/50/1 24.0

11.2

60.0

1

17.5

1.53

1/3

1

30.04

35

5.4

22.5

GEH/GEV024

265/60/1

11.1

9.6

54.0

1

15.0

1.53

1/3

1

13.53

20

0.0

0.0

GEH/GEV024

265/60/1

21.5

9.6

54.0

1

15.0

1.53

1/3

1

26.91

30

5.3

20.0

GEH/GEV024

208/60/3

9.2

7.7

53.7

1

12.0

1.53

1/3

1

11.16

15

0.0

0.0

GEH/GEV024

208/60/3

10.6

7.7

53.7

1

12.0

1.53

1/3

1

13.22

15

3.3

9.0

GEH/GEV024

230/60/3

9.8

7.7

53.7

1

12.0

2.10

1/3

1

11.73

15

0.0

0.0

GEH/GEV024

230/60/3

12.1

7.7

53.7

1

12.0

2.10

1/3

1

15.18

20

4.0

10.0

GEH/GEV024 380-415/50/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV024 380-415/50/3

8.5

4.2

28.0

1

6.5

0.95

1/3

1

10.58

15

5.4

7.5

GEH/GEV024

460/60/3

4.6

3.6

28.0

1

5.6

0.95

1/3

1

5.45

15

0.0

0.0

GEH/GEV024

460/60/3

7.6

3.6

28.0

1

5.6

0.95

1/3

1

9.50

15

5.3

6.7

GEH/GEV030

208/60/1

16.2

14.1

73.0

1

22.0

2.10

1/3

1

19.73

30

0.0

0.0

GEH/GEV030

208/60/1

21.8

14.1

73.0

1

22.0

2.10

1/3

1

27.26

30

4.1

19.7

GEH/GEV030

230/60/1

16.2

14.1

73.0

1

22.0

2.10

1/3

1

19.73

30

0.0

0.0

GEH/GEV030

230/60/1

23.8

14.1

73.0

1

22.0

2.10

1/3

1

29.80

30

5.0

21.7

GEH/GEV030 220-240/50/1 19.5

16.7

79.0

1

26.0

2.77

1/2

1

23.65

40

0.0

0.0

GEH/GEV030 220-240/50/1 29.9

13.5

72.0

1

21.0

2.77

1/2

1

37.42

40

6.5

27.2

GEH/GEV030

265/60/1

12.7

11.2

60.0

1

17.5

1.53

1/3

1

15.53

25

0.0

0.0

GEH/GEV030

265/60/1

26.4

11.2

60.0

1

17.5

1.53

1/3

1

33.04

35

6.6

24.9

GEH/GEV030

208/60/3

11.0

8.9

58.0

1

13.9

2.10

1/3

1

13.23

20

0.0

0.0

GEH/GEV030

208/60/3

13.5

8.9

58.0

1

13.9

2.10

1/3

1

16.85

20

4.1

11.4

GEH/GEV030

230/60/3

11.0

8.9

58.0

1

13.9

2.10

1/3

1

13.23

20

0.0

0.0

GEH/GEV030

230/60/3

14.7

8.9

58.0

1

13.9

2.10

1/3

1

18.31

20

5.0

12.6

7.5

GEH/GEV030 380-415/50/3

5.8

38.0

1

9.0

1.70

1/2

1

8.95

15

0.0

0.0

GEH/GEV030 380-415/50/3 10.8

5.8

38.0

1

9.0

1.70

1/2

1

13.46

15

6.5

9.1

GEH/GEV030

460/60/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV030

460/60/3

9.2

4.2

28.0

1

6.5

0.95

1/3

1

11.54

15

6.6

8.3

GEH/GEV036

208/60/1

20.3

16.7

79.0

1

26.0

3.60

1/2

1

24.48

40

0.0

0.0

GEH/GEV036

208/60/1

27.2

16.7

79.0

1

26.0

3.60

1/2

1

33.95

40

4.9

23.6

GEH/GEV036

230/60/1

20.3

16.7

79.0

1

26.0

3.60

1/2

1

24.48

40

0.0

0.0

GEH/GEV036

230/60/1

29.7

16.7

79.0

1

26.0

3.60

1/2

1

37.11

40

6.0

26.1

GEH/GEV036

265/60/1

16.3

13.5

72.0

1

21.0

2.77

1/2

1

19.65

30

0.0

0.0

GEH/GEV036

265/60/1

32.8

13.5

72.0

1

21.0

2.77

1/2

1

40.96

45

8.0

30.0

GEH/GEV036

208/60/3

14.0

10.4

73.0

1

16.3

3.60

1/2

1

16.60

25

0.0

0.0

GEH/GEV036

208/60/3

17.2

10.4

73.0

1

16.3

3.60

1/2

1

21.50

25

4.9

13.6

GEH/GEV036

230/60/3

14.0

10.4

73.0

1

16.3

3.60

1/2

1

16.60

25

0.0

0.0

continued on next page

WSHP-SVX01N-EN

73

Electrical Data
Table 47.

Electrical data: standard static motors, ½ to 5 tons (continued)GEH*/GEV*

Model No.

Volts

GEH/GEV036

230/60/3

GEH/GEV036 380-415/50/3

Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor
Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps
18.7

10.4

73.0

1

16.3

3.60

1/2

1

7.7

23.33

25

6.0

15.1
0.0

6.0

44.0

1

9.3

1.70

1/2

1

9.20

15

0.0

GEH/GEV036 380-415/50/3 11.6

6.0

44.0

1

9.3

1.70

1/2

1

14.56

15

7.2

9.9

GEH/GEV036

460/60/3

7.5

5.8

38.0

1

9.0

1.70

1/2

1

8.95

15

0.0

0.0

GEH/GEV036

460/60/3

11.7

5.8

38.0

1

9.0

1.70

1/2

1

14.60

15

8.0

10.0

GEH/GEV042

208/60/1

21.5

17.9

112.0

1

28.0

3.60

1/2

1

25.98

40

0.0

0.0

GEH/GEV042

208/60/1

31.0

17.9

112.0

1

28.0

3.60

1/2

1

38.75

40

5.7

27.4

GEH/GEV042

230/60/1

21.5

17.9

112.0

1

28.0

3.60

1/2

1

25.98

40

0.0

0.0

GEH/GEV042

230/60/1

34.0

17.9

112.0

1

28.0

3.60

1/2

1

42.54

45

7.0

30.4

GEH/GEV042

208/60/3

17.1

13.5

88.0

1

21.1

3.60

1/2

1

20.48

30

0.0

0.0

GEH/GEV042

208/60/3

19.4

13.5

88.0

1

21.1

3.60

1/2

1

24.28

30

5.7

15.8

GEH/GEV042

230/60/3

17.1

13.5

88.0

1

21.1

3.60

1/2

1

20.48

30

0.0

0.0

GEH/GEV042

230/60/3

21.2

13.5

88.0

1

21.1

3.60

1/2

1

26.46

30

7.0

17.6

7.7

6.3

55.0

1

9.9

1.40

1/2

1

9.28

15

0.0

0.0

6.3

55.0

1

9.9

1.40

1/2

1

16.71

20

8.6

12.0

GEH/GEV042 380-415/50/3

GEH/GEV042 380-415/50/3 13.4
GEH/GEV042

460/60/3

7.7

6.0

44.0

1

9.3

1.70

1/2

1

9.20

15

0.0

0.0

GEH/GEV042

460/60/3

13.4

6.0

44.0

1

9.3

1.70

1/2

1

16.72

20

9.3

11.7

GEH/GEV042

575/60/3

6.2

4.9

34.0

1

7.7

1.31

1/2

1

7.44

15

0.0

0.0

GEH/GEV048

208/60/1

24.2

21.4

135.0

1

33.4

2.80

1/2

1

29.55

50

0.0

0.0

GEH/GEV048

208/60/1

34.1

21.4

135.0

1

33.4

2.80

1/2

1

42.56

50

6.5

31.3

GEH/GEV048

230/60/1

24.2

21.4

135.0

1

33.4

2.80

1/2

1

29.55

50

0.0

0.0

GEH/GEV048

230/60/1

37.6

21.4

135.0

1

33.4

2.80

1/2

1

46.98

50

8.0

34.8

GEH/GEV048

208/60/3

17.3

14.5

98.0

1

22.6

2.80

1/2

1

20.93

35

0.0

0.0

GEH/GEV048

208/60/3

20.8

14.5

98.0

1

22.6

2.80

1/2

1

26.05

35

6.5

18.0

GEH/GEV048

230/60/3

17.3

14.5

98.0

1

22.6

2.80

1/2

1

20.93

35

0.0

0.0

GEH/GEV048

230/60/3

22.9

20.1

14.5

98.0

1

22.6

2.80

1/2

1

28.60

35

8.0

GEH/GEV048 380-415/50/3 10.5

7.8

52.0

1

12.1

2.70

1

1

12.45

20

0.0

0.0

GEH/GEV048 380-415/50/3 14.7

7.8

52.0

1

12.1

2.70

1

1

18.33

20

8.6

12.0

GEH/GEV048

460/60/3

7.7

6.3

55.0

1

9.9

1.40

1/2

1

9.28

15

0.0

0.0

GEH/GEV048

460/60/3

14.7

6.3

55.0

1

9.9

1.40

1/2

1

18.38

20

10.6

13.3

GEH/GEV048

575/60/3

7.4

6.0

41.0

1

9.4

1.40

1/2

1

8.90

15

0.0

0.0

GEH/GEV060

208/60/1

31.7

26.3

134.0

1

41.0

5.40

1

1

38.28

60

0.0

0.0

GEH/GEV060

208/60/1

36.7

26.3

134.0

1

41.0

5.40

1

1

45.81

60

6.5

31.3

GEH/GEV060

230/60/1

31.7

26.3

134.0

1

41.0

5.40

1

1

38.28

60

0.0

0.0

GEH/GEV060

230/60/1

40.2

26.3

134.0

1

41.0

5.40

1

1

50.23

60

8.0

34.8

GEH/GEV060

208/60/3

21.0

15.6

110.0

1

24.4

5.40

1

1

24.90

40

0.0

0.0

GEH/GEV060

208/60/3

23.4

15.6

110.0

1

24.4

5.40

1

1

29.30

40

6.5

18.0

GEH/GEV060

230/60/3

21.0

15.6

110.0

1

24.4

5.40

1

1

24.90

40

0.0

0.0

GEH/GEV060

230/60/3

25.5

15.6

110.0

1

24.4

5.40

1

1

31.85

40

8.0

20.1

GEH/GEV060 380-415/50/3 12.3

9.6

75.0

1

15.0

2.70

1

1

14.70

20

0.0

0.0

GEH/GEV060 380-415/50/3 14.7

9.6

75.0

1

15.0

2.70

1

1

18.33

20

8.6

12.0

GEH/GEV060

460/60/3

10.5

7.8

52.0

1

12.1

2.70

1

1

12.45

20

0.0

0.0

GEH/GEV060

460/60/3

16.0

7.8

52.0

1

12.1

2.70

1

1

20.01

25

10.6

13.3

GEH/GEV060

575/60/3

8.0

5.8

38.9

1

9.1

2.20

1

1

9.45

15

0.0

0.0

74

WSHP-SVX01N-EN

Electrical Data
Table 48.

Electrical data - high static motors - ½ to 5 tons GEH*/GEV*

Model No.

Volts

Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps
GEHE/GEVE

GEH/GEV006

115/60/1

6.8

5.6

30.0

1

7.5

1.20

1/12

1

8.20

15

0.0

0.0

GEH/GEV006

208/60/1

3.9

3.3

14.0

1

4.2

0.60

1/12

1

4.73

15

0.0

0.0

GEH/GEV006

208/60/1

4.5

3.3

14.0

1

4.2

0.60

1/12

1

5.68

15

0.8

3.9

GEH/GEV006

230/60/1

3.8

3.2

15.0

1

4.2

0.60

1/12

1

4.60

15

0.0

0.0

GEH/GEV006

230/60/1

4.9

3.2

15.0

1

4.2

0.60

1/12

1

6.18

15

1.0

4.3

GEH/GEV006

220-240/50/1

3.4

2.9

17.0

1

4.0

0.52

1/12

1

4.15

15

0.0

0.0

GEH/GEV006

220-240/50/1

7.4

2.9

17.0

1

4.0

0.52

1/12

1

9.19

15

1.6

6.8

GEH/GEV006

265/60/1

3.0

2.5

11.0

1

3.5

0.52

1/12

1

3.65

15

0.0

0.0

GEH/GEV006

265/60/1

5.5

2.5

11.0

1

3.5

0.52

1/12

1

6.92

15

1.3

5.0

GEH/GEV009

115/60/1

7.6

6.4

36.0

1

8.6

1.20

1/12

1

9.20

15

0.0

0.0

GEH/GEV009

208/60/1

4.3

3.7

16.0

1

4.8

0.60

1/12

1

5.23

15

0.0

0.0

GEH/GEV009

208/60/1

6.5

3.7

16.0

1

4.8

0.60

1/12

1

8.14

15

1.2

5.9

GEH/GEV009

230/60/1

4.1

3.5

17.0

1

4.8

0.60

1/12

1

4.98

15

0.0

0.0

GEH/GEV009

230/60/1

7.1

3.5

17.0

1

4.8

0.60

1/12

1

8.90

15

1.5

6.5

GEH/GEV009

220-240/50/1

6.0

5.3

23.0

1

7.4

0.72

1/8

1

7.35

15

0.0

0.0

GEH/GEV009

220-240/50/1

9.8

5.3

23.0

1

7.4

0.72

1/8

1

12.20

15

2.2

9.0

GEH/GEV009

265/60/1

3.3

2.8

13.0

1

3.7

0.52

1/12

1

4.02

15

0.0

0.0

GEH/GEV009

265/60/1

8.1

2.8

13.0

1

3.7

0.52

1/12

1

10.08

15

2.0

7.5

GEH/GEV012

115/60/1

13.7

12.1

58.0

1

16.9

1.57

1/8

1

16.70

25

0.0

0.0

GEH/GEV012

208/60/1

7.0

6.3

30.0

1

8.8

0.70

1/8

1

8.58

15

0.0

0.0

GEH/GEV012

208/60/1

8.5

6.3

27.0

1

8.8

0.70

1/8

1

10.67

15

1.6

7.8

GEH/GEV012

230/60/1

7.0

6.3

30.0

1

8.8

0.70

1/8

1

8.58

15

0.0

0.0

GEH/GEV012

230/60/1

9.4

6.3

30.0

1

8.8

0.70

1/8

1

11.74

15

2.0

8.7

GEH/GEV012

220-240/50/1

7.4

6.7

30.0

1

9.4

0.72

1/8

1

9.10

15

0.0

0.0

GEH/GEV012

220-240/50/1

12.0

6.7

30.0

1

9.4

0.72

1/8

1

14.96

15

2.7

11.3

GEH/GEV012

265/60/1

5.7

5.0

23.0

1

7.0

0.72

1/8

1

6.97

15

0.0

0.0

GEH/GEV012

265/60/1

10.7

5.0

23.0

1

7.0

0.72

1/8

1

13.40

15

2.7

10.0

GEH/GEV015

208/60/1

8.6

7.9

36.0

1

11.1

0.70

1/8

1

10.58

15

0.0

0.0

GEH/GEV015

208/60/1

10.3

7.9

36.0

1

11.1

0.70

1/8

1

12.89

15

2.0

9.6

GEH/GEV015

230/60/1

8.6

7.9

36.0

1

11.1

0.70

1/8

1

10.58

15

0.0

0.0

GEH/GEV015

230/60/1

11.6

7.9

36.0

1

11.1

0.70

1/8

1

14.46

15

2.5

10.9

GEH/GEV015

220-240/50/1

9.7

8.2

36.0

1

11.5

1.53

1/3

1

11.78

15

0.0

0.0

GEH/GEV015

220-240/50/1

15.2

8.2

36.0

1

11.5

1.53

1/3

1

19.00

20

3.3

13.7

GEH/GEV015

265/60/1

7.1

6.4

30.0

1

9.0

0.72

1/8

1

8.72

15

0.0

0.0

GEH/GEV015

265/60/1

13.2

6.4

30.0

1

9.0

0.72

1/8

1

16.47

20

3.3

12.5

GEH/GEV018

208/60/1

11.7

9.6

42.0

1

13.4

2.10

1/3

1

14.10

20

0.0

0.0

GEH/GEV018

208/60/1

13.9

9.6

42.0

1

13.4

2.10

1/3

1

17.41

20

2.5

11.8

GEH/GEV018

230/60/1

11.7

9.6

42.0

1

13.4

2.10

1/3

1

14.10

20

0.0

0.0

GEH/GEV018

230/60/1

15.1

9.6

42.0

1

13.4

2.10

1/3

1

18.93

20

3.0

13.0

GEH/GEV018

220-240/50/1

11.1

9.6

54.0

1

15.0

1.53

1/3

1

13.53

20

0.0

0.0

GEH/GEV018

220-240/50/1

19.7

9.6

54.0

1

15.0

1.53

1/3

1

24.57

25

4.4

18.1

GEH/GEV018

265/60/1

9.2

7.7

35.0

1

10.8

1.53

1/3

1

11.16

15

0.0

0.0

continued on next page

WSHP-SVX01N-EN

75

Electrical Data
Table 48.

Electrical data - high static motors - ½ to 5 tons GEH*/GEV* (continued)
Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps

Model No.

Volts

GEH/GEV018

265/60/1

16.6

7.7

35.0

1

10.8

1.53

1/3

1

20.78

25

4.0

15.1

GEH/GEV018

380-415/50/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV018

380-415/50/3

7.0

3.6

28.0

1

5.6

0.95

1/3

1

8.75

15

4.4

6.1

GEH/GEV024

208/60/1

14.9

12.8

58.3

1

20.0

2.10

1/3

1

18.10

30

0.0

0.0

GEH/GEV024

208/60/1

17.8

12.8

58.3

1

20.0

2.10

1/3

1

22.22

30

3.3

15.7

GEH/GEV024

230/60/1

14.9

12.8

58.3

1

20.0

2.10

1/3

1

18.10

30

0.0

0.0

GEH/GEV024

230/60/1

19.5

12.8

58.3

1

20.0

2.10

1/3

1

24.36

30

4.0

17.4

GEH/GEV024

220-240/50/1

12.7

11.2

60.0

1

17.5

1.53

1/3

1

15.53

25

0.0

0.0

GEH/GEV024

220-240/50/1

24.0

11.2

60.0

1

17.5

1.53

1/3

1

30.04

35

5.4

22.5

GEH/GEV024

265/60/1

11.1

9.6

54.0

1

15.0

1.53

1/3

1

13.53

20

0.0

0.0

GEH/GEV024

265/60/1

21.5

9.6

54.0

1

15.0

1.53

1/3

1

26.91

30

5.3

20.0

GEH/GEV024

208/60/3

9.2

7.7

53.7

1

12.0

1.53

1/3

1

11.16

15

0.0

0.0

GEH/GEV024

208/60/3

10.6

7.7

53.7

1

12.0

1.53

1/3

1

13.22

15

3.3

9.0

GEH/GEV024

230/60/3

9.8

7.7

53.7

1

12.0

2.10

1/3

1

11.73

15

0.0

0.0

GEH/GEV024

230/60/3

12.1

7.7

53.7

1

12.0

2.10

1/3

1

15.18

20

4.0

10.0

GEH/GEV024

380-415/50/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV024

380-415/50/3

8.5

4.2

28.0

1

6.5

0.95

1/3

1

10.58

15

5.4

7.5

GEH/GEV024

460/60/3

4.6

3.6

28.0

1

5.6

0.95

1/3

1

5.45

15

0.0

0.0

GEH/GEV024

460/60/3

7.6

3.6

28.0

1

5.6

0.95

1/3

1

9.50

15

5.3

6.7

GEH/GEV030

208/60/1

16.2

14.1

73.0

1

22.0

2.10

1/3

1

19.73

30

0.0

0.0

GEH/GEV030

208/60/1

21.8

14.1

73.0

1

22.0

2.10

1/3

1

27.26

30

4.1

19.7

GEH/GEV030

230/60/1

16.2

14.1

73.0

1

22.0

2.10

1/3

1

19.73

30

0.0

0.0

GEH/GEV030

230/60/1

23.8

14.1

73.0

1

22.0

2.10

1/3

1

29.80

30

5.0

21.7

GEH/GEV030

220-240/50/1

19.5

16.7

79.0

1

26.0

2.77

1/2

1

23.65

40

0.0

0.0

GEH/GEV030

220-240/50/1

29.9

13.5

72.0

1

21.0

2.77

1/2

1

37.42

40

6.5

27.2

GEH/GEV030

265/60/1

12.7

11.2

60.0

1

17.5

1.53

1/3

1

15.53

25

0.0

0.0

GEH/GEV030

265/60/1

26.4

11.2

60.0

1

17.5

1.53

1/3

1

33.04

35

6.6

24.9

GEH/GEV030

208/60/3

11.0

8.9

58.0

1

13.9

2.10

1/3

1

13.23

20

0.0

0.0

GEH/GEV030

208/60/3

13.5

8.9

58.0

1

13.9

2.10

1/3

1

16.85

20

4.1

11.4

GEH/GEV030

230/60/3

11.0

8.9

58.0

1

13.9

2.10

1/3

1

13.23

20

0.0

0.0

GEH/GEV030

230/60/3

14.7

8.9

58.0

1

13.9

2.10

1/3

1

18.31

20

5.0

12.6

GEH/GEV030

380-415/50/3

7.5

5.8

38.0

1

9.0

1.70

1/2

1

8.95

15

0.0

0.0

GEH/GEV030

380-415/50/3

10.8

5.8

38.0

1

9.0

1.70

1/2

1

13.46

15

6.5

9.1

GEH/GEV030

460/60/3

5.2

4.2

28.0

1

6.5

0.95

1/3

1

6.20

15

0.0

0.0

GEH/GEV030

460/60/3

9.2

4.2

28.0

1

6.5

0.95

1/3

1

11.54

15

6.6

8.3

GEH/GEV036

208/60/1

20.3

16.7

79.0

1

26.0

3.60

1/2

1

24.48

40

0.0

0.0

GEH/GEV036

208/60/1

27.2

16.7

79.0

1

26.0

3.60

1/2

1

33.95

40

4.9

23.6

GEH/GEV036

230/60/1

20.3

16.7

79.0

1

26.0

3.60

1/2

1

24.48

40

0.0

0.0

GEH/GEV036

230/60/1

29.7

16.7

79.0

1

26.0

3.60

1/2

1

37.11

40

6.0

26.1

GEH/GEV036

265/60/1

16.3

13.5

72.0

1

21.0

2.77

1/2

1

19.65

30

0.0

0.0

GEH/GEV036

265/60/1

32.8

13.5

72.0

1

21.0

2.77

1/2

1

40.96

45

8.0

30.0

GEH/GEV036

208/60/3

14.0

10.4

73.0

1

16.3

3.60

1/2

1

16.60

25

0.0

0.0

GEH/GEV036

208/60/3

17.2

10.4

73.0

1

16.3

3.60

1/2

1

21.50

25

4.9

13.6

GEH/GEV036

230/60/3

14.0

10.4

73.0

1

16.3

3.60

1/2

1

16.60

25

0.0

0.0

continued on next page

76

WSHP-SVX01N-EN

Electrical Data
Table 48.

Electrical data - high static motors - ½ to 5 tons GEH*/GEV* (continued)

Model No.

Volts

GEH/GEV036

230/60/3

GEH/GEV036
GEH/GEV036

Maximum
Total Comp Comp
Blower Blower Fan Minimum Overcurrent Electric Electric
Unit RLA
LRA No. of Cmp Motor Motor Motor Circuit
Protective
Heat
Heat
FLA (ea) (ea) Comp. MCC
FLA
hp
Num. Ampacity
Device
kW
Amps
18.7

10.4

73.0

1

16.3

3.60

1/2

1

23.33

25

6.0

15.1

380-415/50/3

7.7

6.0

44.0

1

9.3

1.70

1/2

380-415/50/3

11.6

6.0

44.0

1

9.3

1.70

1/2

1

9.20

15

0.0

0.0

1

14.56

15

7.2

GEH/GEV036

460/60/3

7.5

5.8

38.0

1

9.0

1.70

9.9

1/2

1

8.95

15

0.0

0.0

GEH/GEV036

460/60/3

11.7

5.8

38.0

1

9.0

1.70

1/2

1

14.60

15

8.0

10.0

GEH/GEV042

208/60/1

21.5

17.9

112.0

1

GEH/GEV042

208/60/1

31.0

17.9

112.0

1

28.0

3.60

1/2

1

25.98

40

0.0

0.0

28.0

3.60

1/2

1

38.75

40

5.7

27.4

GEH/GEV042

230/60/1

21.5

17.9

112.0

GEH/GEV042

230/60/1

34.0

17.9

112.0

1

28.0

3.60

1/2

1

25.98

40

0.0

0.0

1

28.0

3.60

1/2

1

42.54

45

7.0

30.4

GEH/GEV042

208/60/3

17.1

13.5

GEH/GEV042

208/60/3

19.4

13.5

88.0

1

21.1

3.60

1/2

1

20.48

30

0.0

0.0

88.0

1

21.1

3.60

1/2

1

24.28

30

5.7

15.8

GEH/GEV042

230/60/3

17.1

GEH/GEV042

230/60/3

21.2

13.5

88.0

1

21.1

3.60

1/2

1

20.48

30

0.0

0.0

13.5

88.0

1

21.1

3.60

1/2

1

26.46

30

7.0

17.6

GEH/GEV042

380-415/50/3

GEH/GEV042

380-415/50/3

9.0

6.3

55.0

1

9.9

2.70

1

1

10.58

15

0.0

0.0

14.7

6.3

55.0

1

9.9

2.70

1

1

18.33

20

8.6

12.0

GEH/GEV042

460/60/3

GEH/GEV042

460/60/3

7.7

6.0

44.0

1

9.3

1.70

1/2

1

9.20

15

0.0

0.0

13.4

6.0

44.0

1

9.3

1.70

1/2

1

16.72

20

9.3

11.7

GEH/GEV042

575/60/3

6.2

GEH/GEV048

208/60/1

26.8

4.9

34.0

1

7.7

1.31

1/2

1

7.44

15

0.0

0.0

21.4

135.0

1

33.4

5.40

1

1

32.15

50

0.0

GEH/GEV048

208/60/1

36.7

0.0

21.4

135.0

1

33.4

5.40

1

1

45.81

50

6.5

31.3

GEH/GEV048

230/60/1

26.8

21.4

135.0

1

33.4

5.40

1

1

32.15

50

0.0

0.0

GEH/GEV048
GEH/GEV048

230/60/1

40.2

21.4

135.0

1

33.4

5.40

1

1

50.23

60

8.0

34.8

208/60/3

19.9

14.5

98.0

1

22.6

5.40

1

1

23.53

35

0.0

0.0

GEH/GEV048

208/60/3

23.4

14.5

98.0

1

22.6

5.40

1

1

29.30

35

6.5

18.0

GEH/GEV048

230/60/3

19.9

14.5

98.0

1

22.6

5.40

1

1

23.53

35

0.0

0.0

GEH/GEV048

230/60/3

25.5

14.5

98.0

1

22.6

5.40

1

1

31.85

35

8.0

20.1

GEH/GEV048

380-415/50/3

10.5

7.8

52.0

1

12.1

2.70

1

1

12.45

20

0.0

0.0

GEH/GEV048

380-415/50/3

14.7

7.8

52.0

1

12.1

2.70

1

1

18.33

20

8.6

12.0

GEH/GEV048

460/60/3

9.0

6.3

55.0

1

9.9

2.70

1

1

10.58

15

0.0

0.0

GEH/GEV048

460/60/3

16.0

6.3

55.0

1

9.9

2.70

1

1

20.01

25

10.6

13.3

GEH/GEV048

575/60/3

8.2

6.0

41.0

1

9.4

2.20

1

1

9.70

15

0.0

0.0

GEH/GEV060

208/60/1

31.7

26.3

134.0

1

41.0

5.40

1

1

38.28

60

0.0

0.0

GEH/GEV060

208/60/1

36.7

26.3

134.0

1

41.0

5.40

1

1

45.81

60

6.5

31.3

GEH/GEV060

230/60/1

31.7

26.3

134.0

1

41.0

5.40

1

1

38.28

60

0.0

0.0

GEH/GEV060

230/60/1

40.2

26.3

134.0

1

41.0

5.40

1

1

50.23

60

8.0

34.8

GEH/GEV060

208/60/3

21.0

15.6

110.0

1

24.4

5.40

1

1

24.90

40

0.0

0.0

GEH/GEV060

208/60/3

23.4

15.6

110.0

1

24.4

5.40

1

1

29.30

40

6.5

18.0

GEH/GEV060

230/60/3

21.0

15.6

110.0

1

24.4

5.40

1

1

24.90

40

0.0

0.0

GEH/GEV060

230/60/3

25.5

15.6

110.0

1

24.4

5.40

1

1

31.85

40

8.0

20.1

GEH/GEV060

380-415/50/3

12.3

9.6

75.0

1

15.0

2.70

1

1

14.70

20

0.0

0.0

GEH/GEV060

380-415/50/3

14.7

9.6

75.0

1

15.0

2.70

1

1

18.33

20

8.6

12.0

GEH/GEV060

460/60/3

10.5

7.8

52.0

1

12.1

2.70

1

1

12.45

20

0.0

0.0

GEH/GEV060

460/60/3

16.0

7.8

52.0

1

12.1

2.70

1

1

20.01

25

10.6

13.3

GEH/GEV060

575/60/3

8.0

5.8

38.9

1

9.1

2.20

1

1

9.45

15

0.0

0.0

WSHP-SVX01N-EN

77

Electrical Data

Table 49.

Electrical data - ECM motors - ½ to 6 tons EXH*/EXV*
Maximum
Overcurrent
Protective
Device

Model
No.

Volts

Total
Unit
FLA

EXH006

208/60/1

3.70

3.3

14.0

0.40

1/3

4.53

15

0.0

0.0

EXH006

208/60/1

4.34

3.3

14.0

0.40

1/3

5.43

15

0.8

3.9

EXH006

230/60/1

3.60

3.2

15.0

0.40

1/3

4.40

15

0.0

0.0

EXH006

230/60/1

4.75

3.2

15.0

0.40

1/3

5.93

15

1.0

4.3

EXH006

265/60/1

2.90

2.5

11.0

0.40

1/3

3.53

15

0.0

0.0

EXH006

265/60/1

5.42

2.5

11.0

0.40

1/3

6.77

15

1.3

5.0

EXH009

208/60/1

4.30

3.7

16.0

0.60

1/3

5.23

15

0.0

0.0

EXH009

208/60/1

6.51

3.7

16.0

0.60

1/3

8.14

15

1.2

5.9

EXH009

230/60/1

4.10

3.5

17.0

0.60

1/3

4.98

15

0.0

0.0

EXH009

230/60/1

7.12

3.5

17.0

0.60

1/3

8.90

15

1.5

6.5

EXH009

265/60/1

3.40

2.8

13.0

0.60

1/3

4.10

15

0.0

0.0

EXH009

265/60/1

8.15

2.8

13.0

0.60

1/3

10.18

15

2.0

7.5

EXH012

208/60/1

7.02

6.3

30.0

0.72

1/3

8.60

15

0.0

0.0

EXH012

208/60/1

8.56

6.3

27.0

0.72

1/3

10.70

15

1.6

7.8

EXH012

230/60/1

7.02

6.3

30.0

0.72

1/3

8.60

15

0.0

0.0

EXH012

230/60/1

9.42

6.3

30.0

0.72

1/3

11.77

15

2.0

8.7

EXH012

265/60/1

5.72

5.0

23.0

0.72

1/3

6.97

15

0.0

0.0

EXH012

265/60/1

10.72

5.0

23.0

0.72

1/3

13.40

15

2.7

10.0

EXH015

208/60/1

8.79

7.9

36.0

0.89

1/3

10.77

15

0.0

0.0

EXH015

208/60/1

10.51

7.9

36.0

0.89

1/3

13.13

15

2.0

9.6

EXH015

230/60/1

8.79

7.9

36.0

0.89

1/3

10.77

15

0.0

0.0

EXH015

230/60/1

11.76

7.9

36.0

0.89

1/3

14.70

15

2.5

10.9

EXH015

265/60/1

7.29

6.4

30.0

0.89

1/3

8.89

15

0.0

0.0

EXH015

265/60/1

13.34

6.4

30.0

0.89

1/3

16.68

20

3.3

12.5

EXH018

208/60/1

11.10

9.6

42.0

1.50

1/2

13.50

20

0.0

0.0

EXH018

208/60/1

13.33

9.6

42.0

1.50

1/2

16.66

20

2.5

11.8

EXH018

230/60/1

11.10

9.6

42.0

1.50

1/2

13.50

20

0.0

0.0

EXH018

230/60/1

14.54

9.6

42.0

1.50

1/2

18.18

20

3.0

13.0

EXH018

265/60/1

9.00

7.7

35.0

1.30

1/2

10.93

15

0.0

0.0

EXH018

265/60/1

16.39

7.7

35.0

1.30

1/2

20.49

25

4.0

15.1

EXH024

208/60/1

15.70

13.5

58.3

2.20

1/2

19.08

30

0.0

0.0

EXH024

208/60/1

17.87

13.5

58.3

2.20

1/2

22.34

30

3.3

15.7

EXH024

230/60/1

15.70

13.5

58.3

2.20

1/2

19.08

30

0.0

0.0

EXH024

230/60/1

19.59

13.5

58.3

2.20

1/2

24.49

30

4.0

17.4

EXH024

265/60/1

10.10

9.0

54.0

1.10

1/2

12.35

20

0.0

0.0

EXH024

265/60/1

21.10

9.0

54.0

1.10

1/2

26.38

30

5.3

20.0

EXH030

208/60/1

17.30

14.1

77.0

3.20

1/2

20.83

30

0.0

0.0

EXH030

208/60/1

26.76

14.1

77.0

3.20

1/2

33.45

35

4.9

23.6

EXH030

230/60/1

17.30

14.1

77.0

3.20

1/2

20.83

30

0.0

0.0

EXH030

230/60/1

29.29

14.1

77.0

3.20

1/2

36.61

40

6.0

26.1

EXH030

265/60/1

13.70

10.9

60.0

2.80

1/2

16.43

25

0.0

0.0

EXH030

265/60/1

32.80

10.9

60.0

2.80

1/2

41.00

45

8.0

30.0

Comp
RLA
(ea)

Comp
LRA
(ea)

Blower
Motor
FLA

Blower
Motor
hp

Minimum
Circuit
Ampacity

Electric Electric
Heat kW Heat Amps

EXH - Horizontal Units

continued on next page

78

WSHP-SVX01N-EN

Electrical Data
Table 49.

Electrical data - ECM motors - ½ to 6 tons EXH*/EXV* (continued)
Maximum
Overcurrent
Protective
Device

Model
No.

Volts

Total
Unit
FLA

EXH036

208/60/1

18.10

14.1

77.0

4.00

3/4

21.63

35

0.0

0.0

EXH036

208/60/1

27.56

14.1

77.0

4.00

3/4

34.45

35

4.9

23.6

EXH036

230/60/1

18.10

14.1

77.0

4.00

3/4

21.63

35

0.0

0.0

EXH036

230/60/1

30.09

14.1

77.0

4.00

3/4

37.61

40

6.0

26.1

EXH036

265/60/1

15.70

12.2

72.0

3.50

3/4

18.75

30

0.0

0.0

EXH036

265/60/1

33.50

12.2

72.0

3.50

3/4

41.88

45

8.0

30.0

EXH036

208/60/3

13.00

9.0

71.0

4.00

3/4

15.25

20

0.0

0.0

EXH036

208/60/3

17.60

9.0

71.0

4.00

3/4

22.00

25

4.9

13.6

EXH036

230/60/3

13.00

9.0

71.0

4.00

3/4

15.25

20

0.0

0.0

EXH036

230/60/3

19.06

9.0

71.0

4.00

3/4

23.83

25

6.0

15.1

EXH036

460/60/3

9.10

5.6

38.0

3.50

3/4

10.50

15

0.0

0.0

EXH036

460/60/3

13.48

5.6

38.0

3.50

3/4

16.85

20

8.0

10.0

EXH042

208/60/1

22.30

17.9

112.0

4.40

3/4

26.78

40

0.0

0.0

EXH042

208/60/1

35.65

17.9

112.0

4.40

3/4

44.56

45

6.5

31.3

EXH042

230/60/1

22.30

17.9

112.0

4.40

3/4

26.78

40

0.0

0.0
34.8

Comp
RLA
(ea)

Comp
LRA
(ea)

Blower
Motor
FLA

Blower
Motor
hp

Minimum
Circuit
Ampacity

Electric Electric
Heat kW Heat Amps

EXH - Horizontal Units

EXH042

230/60/1

39.18

17.9

112.0

4.40

3/4

48.98

50

8.0

EXH042

208/60/3

17.60

13.2

88.0

4.40

3/4

20.90

30

0.0

0.0

EXH042

208/60/3

22.44

13.2

88.0

4.40

3/4

28.05

30

6.5

18.0

EXH042

230/60/3

17.60

13.2

88.0

4.40

3/4

20.90

30

0.0

0.0

EXH042

230/60/3

24.48

13.2

88.0

4.40

3/4

30.60

35

8.0

20.1

EXH042

460/60/3

9.80

6.0

44.0

3.80

3/4

11.30

15

0.0

0.0

EXH042

460/60/3

17.10

6.0

44.0

3.80

3/4

21.38

25

10.6

13.3

EXH048

208/60/1

25.00

19.9

109.0

5.10

3/4

29.98

45

0.0

0.0
31.3

EXH048

208/60/1

36.35

19.9

109.0

5.10

3/4

45.44

50

6.5

EXH048

230/60/1

25.00

19.9

109.0

5.10

3/4

29.98

45

0.0

0.0

EXH048

230/60/1

39.88

19.9

109.0

5.10

3/4

49.85

50

8.0

34.8

EXH048

208/60/3

18.20

13.1

83.1

5.10

3/4

21.48

30

0.0

0.0

EXH048

208/60/3

23.14

13.1

83.1

5.10

3/4

28.93

30

6.5

18.0

EXH048

230/60/3

18.20

13.1

83.1

5.10

3/4

21.48

30

0.0

0.0

EXH048

230/60/3

25.18

13.1

83.1

5.10

3/4

31.48

35

8.0

20.1

EXH048

460/60/3

10.50

6.1

41.0

4.40

3/4

12.03

15

0.0

0.0

EXH048

460/60/3

17.70

6.1

41.0

4.40

3/4

22.13

25

10.6

13.3

EXH060

208/60/1

34.40

26.4

134.0

8.00

1

41.00

60

0.0

0.0

EXH060

208/60/1

39.25

26.4

134.0

8.00

1

49.06

60

6.5

31.3

EXH060

230/60/1

34.40

26.4

134.0

8.00

1

41.00

60

0.0

0.0
34.8

EXH060

230/60/1

42.78

26.4

134.0

8.00

1

53.48

60

8.0

EXH060

208/60/3

24.00

16.0

110.0

8.00

1

28.00

40

0.0

0.0

EXH060

208/60/3

26.04

16.0

110.0

8.00

1

32.55

40

6.5

18.0

EXH060

230/60/3

24.00

16.0

110.0

8.00

1

28.00

40

0.0

0.0
20.1

EXH060

230/60/3

28.08

16.0

110.0

8.00

1

35.10

40

8.0

EXH060

460/60/3

14.70

7.8

52.0

6.90

1

16.65

20

0.0

0.0

EXH060

460/60/3

20.20

7.8

52.0

6.90

1

25.26

30

10.6

13.3

EXH070

208/60/1

37.10

30.1

158.0

7.00

1

44.63

70

0.0

0.0

continued on next page

WSHP-SVX01N-EN

79

Electrical Data
Table 49.

Electrical data - ECM motors - ½ to 6 tons EXH*/EXV* (continued)
Maximum
Overcurrent
Protective
Device

Model
No.

Volts

Total
Unit
FLA

EXH070

208/60/1

38.25

30.1

158.0

7.00

1

47.81

70

6.5

EXH070

230/60/1

37.10

30.1

158.0

7.00

1

44.63

70

0.0

0.0

EXH070

230/60/1

41.78

30.1

158.0

7.00

1

52.23

70

8.0

34.8

Comp
RLA
(ea)

Comp
LRA
(ea)

Blower
Motor
FLA

Blower
Motor
hp

Minimum
Circuit
Ampacity

Electric Electric
Heat kW Heat Amps

EXH - Horizontal Units
31.3

EXH070

208/60/3

27.50

20.5

155.0

7.00

1

32.63

50

0.0

0.0

EXH070

208/60/3

27.50

20.5

155.0

7.00

1

32.63

50

6.5

18.0

EXH070

230/60/3

27.50

20.5

155.0

7.00

1

32.63

50

0.0

0.0

EXH070

230/60/3

27.50

20.5

155.0

7.00

1

33.85

50

8.0

20.1

EXH070

460/60/3

15.70

9.6

75.0

6.10

1

18.10

25

0.0

0.0

EXH070

460/60/3

19.40

9.6

75.0

6.10

1

24.26

25

10.6

13.3

EXV006

208/60/1

3.76

3.3

14.0

4.59

15

0.0

0.0

EXV - Vertical Units
0.46

1/3

EXV006

208/60/1

4.40

3.3

14.0

0.46

1/3

5.50

15

0.8

3.9

EXV006

230/60/1

3.66

3.2

15.0

0.46

1/3

4.46

15

0.0

0.0

EXV006

230/60/1

4.81

3.2

15.0

0.46

1/3

6.01

15

1.0

4.3

EXV006

265/60/1

2.96

2.5

11.0

0.46

1/3

3.59

15

0.0

0.0

EXV006

265/60/1

5.48

2.5

11.0

0.46

1/3

6.85

15

1.3

5.0

EXV009

208/60/1

4.31

3.7

16.0

0.61

1/3

5.24

15

0.0

0.0

EXV009

208/60/1

6.52

3.7

16.0

0.61

1/3

8.15

15

1.2

5.9

EXV009

230/60/1

4.11

3.5

17.0

0.61

1/3

4.99

15

0.0

0.0

EXV009

230/60/1

7.13

3.5

17.0

0.61

1/3

8.91

15

1.5

6.5

EXV009

265/60/1

3.41

2.8

13.0

0.61

1/3

4.11

15

0.0

0.0

EXV009

265/60/1

8.16

2.8

13.0

0.61

1/3

10.20

15

2.0

7.5

EXV012

208/60/1

6.91

6.3

30.0

0.61

1/3

8.49

15

0.0

0.0

EXV012

208/60/1

8.45

6.3

27.0

0.61

1/3

10.56

15

1.6

7.8

EXV012

230/60/1

6.91

6.3

30.0

0.61

1/3

8.49

15

0.0

0.0

EXV012

230/60/1

9.31

6.3

30.0

0.61

1/3

11.63

15

2.0

8.7

EXV012

265/60/1

5.61

5.0

23.0

0.61

1/3

6.86

15

0.0

0.0

EXV012

265/60/1

10.61

5.0

23.0

0.61

1/3

13.26

15

2.7

10.0

EXV015

208/60/1

8.73

7.9

36.0

0.83

1/3

10.71

15

0.0

0.0

EXV015

208/60/1

10.45

7.9

36.0

0.83

1/3

13.06

15

2.0

9.6

EXV015

230/60/1

8.73

7.9

36.0

0.83

1/3

10.71

15

0.0

0.0

EXV015

230/60/1

11.70

7.9

36.0

0.83

1/3

14.62

15

2.5

10.9

EXV015

265/60/1

7.23

6.4

30.0

0.83

1/3

8.83

15

0.0

0.0

EXV015

265/60/1

13.28

6.4

30.0

0.83

1/3

16.60

20

3.3

12.5

EXV018

208/60/1

11.10

9.6

42.0

1.50

1/2

13.50

20

0.0

0.0

EXV018

208/60/1

13.33

9.6

42.0

1.50

1/2

16.66

20

2.5

11.8

EXV018

230/60/1

11.10

9.6

42.0

1.50

1/2

13.50

20

0.0

0.0

EXV018

230/60/1

14.54

9.6

42.0

1.50

1/2

18.18

20

3.0

13.0

EXV018

265/60/1

9.00

7.7

35.0

1.30

1/2

10.93

15

0.0

0.0

EXV018

265/60/1

16.39

7.7

35.0

1.30

1/2

20.49

25

4.0

15.1

EXV024

208/60/1

15.70

13.5

58.3

2.20

1/2

19.08

30

0.0

0.0

EXV024

208/60/1

17.87

13.5

58.3

2.20

1/2

22.34

30

3.3

15.7

EXV024

230/60/1

15.70

13.5

58.3

2.20

1/2

19.08

30

0.0

0.0

continued on next page

80

WSHP-SVX01N-EN

Electrical Data
Table 49.

Electrical data - ECM motors - ½ to 6 tons EXH*/EXV* (continued)
Minimum
Circuit
Ampacity

Maximum
Overcurrent
Protective
Device

Model
No.

Volts

Total
Unit
FLA

EXV024

230/60/1

19.59

13.5

58.3

2.20

1/2

24.49

30

4.0

EXV024

265/60/1

10.10

9.0

54.0

1.10

1/2

12.35

20

0.0

0.0

EXV024

265/60/1

21.10

9.0

54.0

1.10

1/2

26.38

30

5.3

20.0

EXV030

208/60/1

17.30

14.1

77.0

3.20

1/2

20.83

30

0.0

0.0

EXV030

208/60/1

26.76

14.1

77.0

3.20

1/2

33.45

35

4.9

23.6

EXV030

230/60/1

17.30

14.1

77.0

3.20

1/2

20.83

30

0.0

0.0

EXV030

230/60/1

29.29

14.1

77.0

3.20

1/2

36.61

40

6.0

26.1

EXV030

265/60/1

13.70

10.9

60.0

2.80

1/2

16.43

25

0.0

0.0

EXV030

265/60/1

32.80

10.9

60.0

2.80

1/2

41.00

45

8.0

30.0

EXV036

208/60/1

18.10

14.1

77.0

4.00

3/4

21.63

35

0.0

0.0

EXV036

208/60/1

27.56

14.1

77.0

4.00

3/4

34.45

35

4.9

23.6

EXV036

230/60/1

18.10

14.1

77.0

4.00

3/4

21.63

35

0.0

0.0

EXV036

230/60/1

30.09

14.1

77.0

4.00

3/4

37.61

40

6.0

26.1

EXV036

265/60/1

15.70

12.2

72.0

3.50

3/4

18.75

30

0.0

0.0

EXV036

265/60/1

33.50

12.2

72.0

3.50

3/4

41.88

45

8.0

30.0

EXV036

208/60/3

13.00

9.0

71.0

4.00

3/4

15.25

20

0.0

0.0

EXV036

208/60/3

17.60

9.0

71.0

4.00

3/4

22.00

25

4.9

13.6

EXV036

230/60/3

13.00

9.0

71.0

4.00

3/4

15.25

20

0.0

0.0

EXV036

230/60/3

19.06

9.0

71.0

4.00

3/4

23.83

25

6.0

15.1

EXV036

460/60/3

9.10

5.6

38.0

3.50

3/4

10.50

15

0.0

0.0

EXV036

460/60/3

13.48

5.6

38.0

3.50

3/4

16.85

20

8.0

10.0

Comp
RLA
(ea)

Comp
LRA
(ea)

Blower
Motor
FLA

Blower
Motor
hp

Electric Electric
Heat kW Heat Amps

EXV - Vertical Units
17.4

EXV042

208/60/1

22.30

17.9

112.0

4.40

3/4

26.78

40

0.0

0.0

EXV042

208/60/1

35.65

17.9

112.0

4.40

3/4

44.56

45

6.5

31.3

EXV042

230/60/1

22.30

17.9

112.0

4.40

3/4

26.78

40

0.0

0.0

EXV042

230/60/1

39.18

17.9

112.0

4.40

3/4

48.98

50

8.0

34.8

EXV042

208/60/3

17.60

13.2

88.0

4.40

3/4

20.90

30

0.0

0.0

EXV042

208/60/3

22.44

13.2

88.0

4.40

3/4

28.05

30

6.5

18.0

EXV042

230/60/3

17.60

13.2

88.0

4.40

3/4

20.90

30

0.0

0.0

EXV042

230/60/3

24.48

13.2

88.0

4.40

3/4

30.60

35

8.0

20.1

EXV042

460/60/3

9.80

6.0

44.0

3.80

3/4

11.30

15

0.0

0.0

EXV042

460/60/3

17.10

6.0

44.0

3.80

3/4

21.38

25

10.6

13.3

EXV048

208/60/1

25.00

19.9

109.0

5.10

3/4

29.98

45

0.0

0.0

EXV048

208/60/1

36.35

19.9

109.0

5.10

3/4

45.44

50

6.5

31.3

EXV048

230/60/1

25.00

19.9

109.0

5.10

3/4

29.98

45

0.0

0.0

EXV048

230/60/1

39.88

19.9

109.0

5.10

3/4

49.85

50

8.0

34.8

EXV048

208/60/3

18.20

13.1

83.1

5.10

3/4

21.48

30

0.0

0.0

EXV048

208/60/3

23.14

13.1

83.1

5.10

3/4

28.93

30

6.5

18.0

EXV048

230/60/3

18.20

13.1

83.1

5.10

3/4

21.48

30

0.0

0.0

EXV048

230/60/3

25.18

13.1

83.1

5.10

3/4

31.48

35

8.0

20.1

EXV048

460/60/3

10.50

6.1

41.0

4.40

3/4

12.03

15

0.0

0.0

EXV048

460/60/3

17.70

6.1

41.0

4.40

3/4

22.13

25

10.6

13.3

EXV060

208/60/1

34.40

26.4

134.0

8.00

1

41.00

60

0.0

0.0

EXV060

208/60/1

39.25

26.4

134.0

8.00

1

49.06

60

6.5

31.3

continued on next page

WSHP-SVX01N-EN

81

Electrical Data
Table 49.

Electrical data - ECM motors - ½ to 6 tons EXH*/EXV* (continued)
Maximum
Overcurrent
Protective
Device

Model
No.

Volts

Total
Unit
FLA

EXV060

230/60/1

34.40

26.4

134.0

8.00

1

41.00

60

0.0

0.0

EXV060

230/60/1

42.78

26.4

134.0

8.00

1

53.48

60

8.0

34.8

EXV060

208/60/3

24.00

16.0

110.0

8.00

1

28.00

40

0.0

0.0
18.0

Comp
RLA
(ea)

Comp
LRA
(ea)

Blower
Motor
FLA

Blower
Motor
hp

Minimum
Circuit
Ampacity

Electric Electric
Heat kW Heat Amps

EXV - Vertical Units

EXV060

208/60/3

26.04

16.0

110.0

8.00

1

32.55

40

6.5

EXV060

230/60/3

24.00

16.0

110.0

8.00

1

28.00

40

0.0

0.0

EXV060

230/60/3

28.08

16.0

110.0

8.00

1

35.10

40

8.0

20.1

EXV060

460/60/3

14.70

7.8

52.0

6.90

1

16.65

20

0.0

0.0

EXV060

460/60/3

20.20

7.8

52.0

6.90

1

25.26

30

10.6

13.3

EXV070

208/60/1

37.10

30.1

158.0

7.00

1

44.63

70

0.0

0.0

EXV070

208/60/1

38.25

30.1

158.0

7.00

1

47.81

70

6.5

31.3

EXV070

230/60/1

37.10

30.1

158.0

7.00

1

44.63

70

0.0

0.0
34.8

EXV070

230/60/1

41.78

30.1

158.0

7.00

1

52.23

70

8.0

EXV070

208/60/3

27.50

20.5

155.0

7.00

1

32.63

50

0.0

0.0

EXV070

208/60/3

27.50

20.5

155.0

7.00

1

32.63

50

6.5

18.0

EXV070

230/60/3

27.50

20.5

155.0

7.00

1

32.63

50

0.0

0.0
20.1

EXV070

230/60/3

27.50

20.5

155.0

7.00

1

33.85

50

8.0

EXV070

460/60/3

15.70

9.6

75.0

6.10

1

18.10

25

0.0

0.0

EXV070

460/60/3

19.40

9.6

75.0

6.10

1

24.26

25

10.6

13.3

Table 50.

Electrical data: 6 to 25 tons - single speed blower motor
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH072

208/60/1

39.9

16.7

79

2

26

6.5

1.0

1

44.08

60

GEH072

230/60/1

39.9

16.7

79

2

26

6.5

1.0

1

44.08

60

GEH072

208/60/1

42.7

16.7

79

2

26

9.3

1.5

1

46.88

60

GEH072

230/60/1

42.3

16.7

79

2

26

8.9

1.5

1

46.48

60

GEH072

208/60/1

44.6

16.7

79

2

26

11.2

2.0

1

48.78

60

GEH072

230/60/1

43.6

16.7

79

2

26

10.2

2.0

1

47.78

60

GEH072

380-415/50/3

13.9

7.1/5.1

48/35

2

11/8

1.7

0.75

1

15.68

20

GEH072

208/60/3

24.3

10.4

73

2

16.3

3.5

1.0

1

26.90

35

GEH072

230/60/3

24.6

10.4

73

2

16.3

3.8

1.0

1

27.20

35

GEH072

460/60/3

13.4

5.8

38

2

9

1.8

1.0

1

14.85

20

GEH072

380-415/50/3

14.3

7.1/5.1

48/35

2

11/8

2.1

1.0

1

16.08

20

GEH072

208/60/3

26.4

10.4

73

2

16.3

5.6

1.5

1

29.00

35

GEH072

230/60/3

25.6

10.4

73

2

16.3

4.8

1.5

1

28.20

35

GEH072

380-415/50/3

15.2

7.1/5.1

48/35

2

11/8

3.0

1.5

1

16.98

20

GEH072

460/60/3

14.0

5.8

38

2

9

2.4

1.5

1

15.45

20

GEH072

208/60/3

27.9

10.4

73

2

16.3

7.1

2.0

1

30.50

40

GEH072

230/60/3

27.0

10.4

73

2

16.3

6.2

2.0

1

29.60

40

GEH072

380-415/50/3

15.6

7.1/5.1

48/35

2

11/8

3.4

2.0

1

17.38

20

No. of
Comp.

GEH - Horizontal Units

continued on next page

82

WSHP-SVX01N-EN

Electrical Data
Table 50.

Electrical data: 6 to 25 tons - single speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH072

460/60/3

14.7

5.8

38

2

9

3.1

2.0

1

16.15

20

GEH072

380-415/50/3

17.4

7.1/5.1

48/35

2

11/8

5.2

3.0

1

19.18

25

GEH090

208/60/3

28.4

14.5/10.4

98/73

2

22.6/16.3

3.5

1.0

1

32.03

45

GEH090

230/60/3

28.7

14.5/10.4

98/73

2

22.6/16.3

3.8

1.0

1

32.33

45

GEH090

460/60/3

13.9

6.3/5.8

55/38

2

9.9/9

1.8

1.0

1

15.48

20

GEH090

208/60/3

30.5

14.5/10.4

98/73

2

22.6/16.3

5.6

1.5

1

34.13

45

GEH090

230/60/3

29.7

14.5/10.4

98/73

2

22.6/16.3

4.8

1.5

1

33.33

45

GEH090

380-415/50/3

22.2

9.6

64

2

15

3.0

1.5

1

24.60

30

GEH090

460/60/3

14.5

6.3/5.8

55/38

2

9.9/9

2.4

1.5

1

16.08

20

GEH090

208/60/3

32.0

14.5/10.4

98/73

2

22.6/16.3

7.1

2.0

1

35.63

50

GEH090

230/60/3

31.1

14.5/10.4

98/73

2

22.6/16.3

6.2

2.0

1

34.73

45

GEH090

380-415/50/3

22.6

9.6

64

2

15

3.4

2.0

1

25.00

30

GEH090

460/60/3

15.2

6.3/5.8

55/38

2

9.9/9

3.1

2.0

1

16.78

20

GEH090

575/60/3

12.1

6/3.8

41/36.5

2

9.4/5.9

2.3

2.0

1

13.60

15

GEH090

208/60/3

34.3

14.5/10.4

98/73

2

22.6/16.3

9.4

3.0

1

37.93

50

GEH090

230/60/3

33.1

14.5/10.4

98/73

2

22.6/16.3

8.2

3.0

1

36.73

50

GEH090

380-415/50/3

24.4

9.6

64

2

15

5.2

3.0

1

26.80

35

GEH090

460/60/3

16.7

6.3

55

2

9.9

4.1

3.0

1

18.28

20

GEH090

575/60/3

13.1

6/3.8

41/36.5

2

9.4/5.9

3.3

3.0

1

14.60

20

GEH120

380-415/50/3

23.3

10.6

74

2

16.5

2.1

1.0

1

25.95

35

GEH120

208/60/3

37.6

16

110

2

24.9

5.6

1.5

1

41.60

50

GEH120

230/60/3

36.8

16

110

2

24.9

4.8

1.5

1

40.80

50

GEH120

380-415/50/3

24.2

10.6

74

2

16.5

3.0

1.5

1

26.85

35

GEH120

460/60/3

18.0

7.8

52

2

12.1

2.4

1.5

1

19.95

25

GEH120

208/60/3

39.1

16

110

2

24.9

7.1

2.0

1

43.10

50

GEH120

230/60/3

38.2

16

110

2

24.9

6.2

2.0

1

42.20

50

GEH120

380-415/50/3

24.6

10.6

74

2

16.5

3.4

2.0

1

27.25

35

GEH120

460/60/3

18.7

7.8

52

2

12.1

3.1

2.0

1

20.65

25

GEH120

575/60/3

13.7

5.7

38.9

2

8.9

2.3

2.0

1

15.13

20

GEH120

208/60/3

41.4

16

110

2

24.9

9.4

3.0

1

45.40

60

GEH120

230/60/3

40.2

16

110

2

24.9

8.2

3.0

1

44.20

60

GEH120

380-415/50/3

26.4

10.6

74

2

16.5

5.2

3.0

1

29.05

35

GEH120

460/60/3

19.7

7.8

52

2

12.1

4.1

3.0

1

21.65

25

GEH120

575/60/3

14.7

5.7

38.9

2

8.9

3.3

3.0

1

16.13

20

GEH120

208/60/3

46.0

16

110

2

24.9

14.0

5.0

1

50.00

60

GEH120

230/60/3

45.0

16

110

2

24.9

13.0

5.0

1

49.00

60

GEH120

460/60/3

22.1

7.8

52

2

12.1

6.5

5.0

1

24.05

30

GEH120

575/60/3

16.7

5.7

38.9

2

8.9

5.3

5.0

1

18.13

20

GEH150

208/60/3

50.4

22.4

149

2

35

5.6

1.5

1

56.00

70

No. of
Comp.

GEH - Horizontal Units

GEH150

230/60/3

49.6

22.4

149

2

35

4.8

1.5

1

55.20

70

GEH150

380-415/50/3

27.4

12.2

101

2

19

3.0

1.5

1

30.45

40

GEH150

460/60/3

23.6

10.6

75

2

16.5

2.4

1.5

1

26.25

35

GEH150

575/60/3

17.3

7.7

54

2

12

1.9

1.5

1

19.23

25

continued on next page

WSHP-SVX01N-EN

83

Electrical Data
Table 50.

Electrical data: 6 to 25 tons - single speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH150

208/60/3

51.9

22.4

149

2

35

7.1

2.0

1

57.50

70

GEH150

230/60/3

51.0

22.4

149

2

35

6.2

2.0

1

56.60

70

GEH150

380-415/50/3

27.8

12.2

101

2

19

3.4

2.0

1

30.85

40

GEH150

460/60/3

24.3

10.6

75

2

16.5

3.1

2.0

1

26.96

35

GEH150

575/60/3

17.7

7.7

54

2

12

2.3

2.0

1

19.63

25

GEH150

208/60/3

54.2

22.4

149

2

35

9.4

3.0

1

59.80

80

GEH150

230/60/3

53.0

22.4

149

2

35

8.2

3.0

1

58.60

80
40

No. of
Comp.

GEH - Horizontal Units

GEH150

380-415/50/3

29.6

12.2

101

2

19

5.2

3.0

1

32.65

GEH150

460/60/3

25.3

10.6

75

2

16.5

4.1

3.0

1

27.95

35

GEH150

575/60/3

18.7

7.7

54

2

12

3.3

3.0

1

20.63

25

GEH150

208/60/3

58.8

22.4

149

2

35

14.0

5.0

1

64.40

80

GEH150

230/60/3

57.8

22.4

149

2

35

13.0

5.0

1

63.40

80

GEH150

380-415/50/3

32.6

12.2

101

2

19

8.2

5.0

1

35.65

45

GEH150

460/60/3

27.7

10.6

75

2

16.5

6.5

5.0

1

30.35

40

GEH150

575/60/3

20.7

7.7

54

2

12

5.3

5.0

1

22.63

30

GEH180

208/60/3

57.1

25

164

2

39

7.1

2.0

1

63.35

80

GEH180

230/60/3

56.2

25

164

2

39

6.2

2.0

1

62.45

80

GEH180

460/60/3

27.5

12.2

100

2

19

3.1

2.0

1

30.56

40

GEH180

575/60/3

20.3

9

78

2

14

2.3

2.0

1

22.55

30

GEH180

208/60/3

59.4

25

164

2

39

9.4

3.0

1

65.65

90

GEH180

230/60/3

58.2

25

164

2

39

8.2

3.0

1

64.45

80

GEH180

460/60/3

28.5

12.2

100

2

19

4.1

3.0

1

31.55

40

GEH180

575/60/3

21.3

9

78

2

14

3.3

3.0

1

23.55

30

GEH180

208/60/3

64.0

25

164

2

39

14.0

5.0

1

70.25

90

GEH180

230/60/3

63.0

25

164

2

39

13.0

5.0

1

69.25

90

GEH180

460/60/3

30.9

12.2

100

2

19

6.5

5.0

1

33.95

45

GEH180

575/60/3

23.3

9

78

2

14

5.3

5.0

1

25.55

30

GEH180

208/60/3

70.0

25

164

2

39

20.0

7.5

1

76.25

100

GEH180

230/60/3

69.4

25

164

2

39

19.4

7.5

1

75.65

100

GEH180

460/60/3

34.1

12.2

100

2

19

9.7

7.5

1

37.15

45

GEH180

575/60/3

26.0

9

78

2

14

8.0

7.5

1

28.25

35

GEV072

208/60/1

40.0

16.7

79

2

26

6.6

1.0

1

44.13

60

GEV072

230/60/1

39.9

16.7

79

2

26

6.5

1.0

1

44.08

60

GEV072

208/60/1

42.7

16.7

79

2

26

9.3

1.5

1

46.88

60

GEV072

230/60/1

42.3

16.7

79

2

26

8.9

1.5

1

46.48

60

GEV072

208/60/1

44.6

16.7

79

2

26

11.2

2.0

1

48.78

60

GEV072

230/60/1

43.6

16.7

79

2

26

10.2

2.0

1

47.81

60

GEV072

380-415/50/3

13.9

7.1/5.1

48/35

2

11/8

1.7

0.75

1

15.68

20

GEV072

208/60/3

24.3

10.4

73

2

16.3

3.5

1.0

1

26.90

35

GEV072

230/60/3

24.6

10.4

73

2

16.3

3.8

1.0

1

27.20

35

GEV072

460/60/3

13.4

5.8

38

2

9

1.8

1.0

1

14.85

20

GEV072

380-415/50/3

14.3

7.1/5.1

48/35

2

11/8

2.1

1.0

1

16.08

20

GEV - Vertical Units

continued on next page

84

WSHP-SVX01N-EN

Electrical Data
Table 50.

Electrical data: 6 to 25 tons - single speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEV072

208/60/3

26.4

10.4

73

2

16.3

5.6

1.5

1

29.00

35

GEV072

230/60/3

25.6

10.4

73

2

16.3

4.8

1.5

1

28.20

35

GEV072

380-415/50/3

15.2

7.1/5.1

48/35

2

11/8

3.0

1.5

1

16.98

20

GEV072

460/60/3

14.0

5.8

38

2

9

2.4

1.5

1

15.45

20

GEV072

208/60/3

27.9

10.4

73

2

16.3

7.1

2.0

1

30.50

40

GEV072

230/60/3

27.0

10.4

73

2

16.3

6.2

2.0

1

29.60

40

GEV072

380-415/50/3

15.6

7.1/5.1

48/35

2

11/8

3.4

2.0

1

17.38

20

GEV072

460/60/3

14.7

5.8

38

2

9

3.1

2.0

1

16.16

20

GEV072

380-415/50/3

17.7

7.1/5.1

48/35

2

11/8

5.5

3.0

1

19.48

25

GEVE090 380-415/50/3

21.3

9.6

64

2

15

2.1

1.0

1

23.70

30

3.5

1.0

1

32.03

45

No. of
Comp.

GEV - Vertical Units

GEV090

208/60/3

28.4

14.5/10.4

98/73

2

22.6/16.3

GEV090

230/60/3

28.7

14.5/10.4

98/73

2

22.6/16.3

3.8

1.0

1

32.33

45

GEV090

460/60/3

13.9

6.3/5.8

55/38

2

9.9/9

1.8

1.0

1

15.48

20

GEV090

208/60/3

30.5

14.5/10.4

98/73

2

22.6/16.3

5.6

1.5

1

34.13

45

GEV090

230/60/3

29.7

14.5/10.4

98/73

2

22.6/16.3

4.8

1.5

1

33.33

45

GEV090

380-415/50/3

22.2

9.6

64

2

15

3.0

1.5

1

24.60

30

GEV090

460/60/3

14.5

6.3/5.8

55/38

2

9.9/9

2.4

1.5

1

16.08

20

GEV090

208/60/3

32.0

14.5/10.4

98/73

2

22.6/16.3

7.1

2.0

1

35.63

50

GEV090

230/60/3

31.1

14.5/10.4

98/73

2

22.6/16.3

6.2

2.0

1

34.73

45

GEV090

380-415/50/3

22.6

9.6

64

2

15

3.4

2.0

1

25.00

30

GEV090

460/60/3

15.2

6.3/5.8

55/38

2

9.9/9

3.1

2.0

1

16.79

20

GEV090

575/60/3

12.1

6/3.8

41/36.5

2

9.4/5.9

2.3

2.0

1

13.60

15

GEV090

208/60/3

34.3

14.5/10.4

98/73

2

22.6/16.3

9.4

3.0

1

37.93

50

GEV090

230/60/3

33.1

14.5/10.4

98/73

2

22.6/16.3

8.2

3.0

1

36.73

50

GEV090

380-415/50/3

24.4

9.6

64

2

15

5.2

3.0

1

26.80

35

GEV090

460/60/3

16.2

6.3/5.8

55/38

2

9.9/9

4.1

3.0

1

17.78

20

GEV090

575/60/3

13.1

6/3.8

41/36.5

2

9.4/5.9

3.3

3.0

1

14.60

20

GEV120

208/60/3

37.6

16

110

2

24.9

5.6

1.5

1

41.60

50

GEV120

230/60/3

36.8

16

110

2

24.9

4.8

1.5

1

40.80

50

GEV120

460/60/3

18.0

7.8

52

2

12.1

2.4

1.5

1

19.95

25

GEV120

208/60/3

39.1

16

110

2

24.9

7.1

2.0

1

43.10

50

GEV120

230/60/3

38.2

16

110

2

24.9

6.2

2.0

1

42.20

50

GEV120

460/60/3

18.7

7.8

52

2

12.1

3.1

2.0

1

20.66

25

GEV120

575/60/3

13.7

5.7

38.9

2

8.9

2.3

2.0

1

15.13

20

GEV120

208/60/3

41.4

16

110

2

24.9

9.4

3.0

1

45.40

60

GEV120

230/60/3

40.2

16

110

2

24.9

8.2

3.0

1

44.20

60

GEV120

460/60/3

19.7

7.8

52

2

12.1

4.1

3.0

1

21.65

25

GEV120

575/60/3

14.7

5.7

38.9

2

8.9

3.3

3.0

1

16.13

20

GEV120

208/60/3

46.0

16

110

2

24.9

14.0

5.0

1

50.00

60

GEV120

230/60/3

45.0

16

110

2

24.9

13.0

5.0

1

49.00

60

GEV120

460/60/3

22.1

7.8

52

2

12.1

6.5

5.0

1

24.05

30

GEV120

575/60/3

16.7

5.7

38.9

2

8.9

5.3

5.0

1

18.13

20

GEV120

380-415/50/3

24.2

10.6

74

2

16.5

3.0

1.5

1

26.85

35

continued on next page

WSHP-SVX01N-EN

85

Electrical Data
Table 50.

Electrical data: 6 to 25 tons - single speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEV120

380-415/50/3

24.6

10.6

74

2

16.5

3.4

2.0

1

27.25

GEV120

380-415/50/3

26.4

10.6

74

2

16.5

5.2

3.0

1

29.05

35

GEV150

208/60/3

51.9

22.4

149

2

35

7.1

2.0

1

57.50

70

GEV150

230/60/3

51.0

22.4

149

2

35

6.2

2.0

1

56.60

70

GEV150

380-415/50/3

27.8

12.2

101

2

19

3.4

2.0

1

30.85

40

GEV150

460/60/3

24.3

10.6

75

2

16.5

3.1

2.0

1

26.96

35

GEV150

575/60/3

17.7

7.7

54

2

12

2.3

2.0

1

19.63

25

GEV150

208/60/3

54.2

22.4

149

2

35

9.4

3.0

1

59.80

80

GEV150

230/60/3

53.0

22.4

149

2

35

8.2

3.0

1

58.60

80

GEV150

380-415/50/3

29.6

12.2

101

2

19

5.2

3.0

1

32.65

40

GEV150

460/60/3

25.3

10.6

75

2

16.5

4.1

3.0

1

27.95

35

GEV150

575/60/3

18.7

7.7

54

2

12

3.3

3.0

1

20.63

25

GEV150

208/60/3

58.8

22.4

149

2

35

14.0

5.0

1

64.40

80

GEV150

230/60/3

57.8

22.4

149

2

35

13.0

5.0

1

63.40

80

GEV150

380-415/50/3

32.6

12.2

101

2

19

8.2

5.0

1

35.65

45

GEV150

460/60/3

27.7

10.6

75

2

16.5

6.5

5.0

1

30.35

40

GEV150

575/60/3

20.7

7.7

54

2

12

5.3

5.0

1

22.63

30

GEV180

208/60/3

59.4

25

164

2

39

9.4

3.0

1

65.65

90

GEV180

230/60/3

58.2

25

164

2

39

8.2

3.0

1

64.45

80

GEV180

380-415/50/3

38.6

16.7

111

2

26

5.2

3.0

1

42.78

50

GEV180

460/60/3

28.5

12.2

100

2

19

4.1

3.0

1

31.55

40

GEV180

575/60/3

21.3

9

78

2

14

3.3

3.0

1

23.55

30

GEV180

208/60/3

64.0

25

164

2

39

14.0

5.0

1

70.25

90

GEV180

230/60/3

63.0

25

164

2

39

13.0

5.0

1

69.25

90

GEV180

380-415/50/3

41.6

16.7

111

2

26

8.2

5.0

1

45.78

60

GEV180

460/60/3

30.9

12.2

100

2

19

6.5

5.0

1

33.95

45

GEV180

575/60/3

23.3

9

78

2

14

5.3

5.0

1

25.55

30

GEV180

208/60/3

70.0

25

164

2

39

20.0

7.5

1

76.25

100

GEV180

230/60/3

69.4

25

164

2

39

19.4

7.5

1

75.65

100

GEV180

380-415/50/3

44.9

16.7

111

2

26

11.5

7.5

1

49.08

60

GEV180

460/60/3

34.1

12.2

100

2

19

9.7

7.5

1

37.15

45

GEV180

575/60/3

26.0

9

78

2

14

8.0

7.5

1

28.25

35

GEV240

380-415/50/3

42.4

18.6

118

2

29

5.2

3.0

1

47.05

60

GEV240

208/60/3

74.2

30.1

225

2

47

14.0

5.0

1

81.73

110

GEV240

230/60/3

73.2

30.1

225

2

47

13.0

5.0

1

80.73

110

GEV240

380-415/50/3

45.4

18.6

118

2

29

8.2

5.0

1

50.05

60

GEV240

460/60/3

39.9

16.7

114

2

26

6.5

5.0

1

44.08

60

GEV240

575/60/3

29.7

12.2

80

2

19

5.3

5.0

1

32.75

40

GEV240

208/60/3

80.2

30.1

225

2

47

20.0

7.5

1

87.73

110

GEV240

230/60/3

79.6

30.1

225

2

47

19.4

7.5

1

87.13

110

GEV240

380-415/50/3

48.7

18.6

118

2

29

11.5

7.5

1

53.35

70

GEV240

460/60/3

43.1

16.7

114

2

26

9.7

7.5

1

47.28

60

GEV240

575/60/3

32.4

12.2

80

2

19

8.0

7.5

1

35.45

45

No. of
Comp.

GEV - Vertical Units
35

continued on next page

86

WSHP-SVX01N-EN

Electrical Data
Table 50.

Electrical data: 6 to 25 tons - single speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEV240

208/60/3

86.2

30.1

225

2

47

26.0

10.0

1

93.73

110

GEV240

230/60/3

85.2

30.1

225

2

47

25.0

10.0

1

92.73

110

GEV240

460/60/3

45.9

16.7

114

2

26

12.5

10.0

1

50.08

60

GEV240

575/60/3

34.4

12.2

80

2

19

10.0

10.0

1

37.45

45

GEV240

208/60/3

97.2

30.1

225

2

47

37.0

15.0

1

106.45

125

GEV240

230/60/3

96.2

30.1

225

2

47

36.0

15.0

1

105.20

125

GEV240

380-415/50/3

52.2

18.6

118

2

29

15.0

10.0

1

56.85

70

GEV240

460/60/3

51.4

16.7

114

2

26

18.0

15.0

1

55.90

70

GEV240

575/60/3

38.5

12.2

80

2

19

14.1

15.0

1

42.03

50

GEV300

208/60/3

110.2

48.1

245

2

75

14.0

5.0

1

122.23

150

GEV300

230/60/3

109.2

48.1

245

2

75

13.0

5.0

1

121.23

150

GEV300

460/60/3

43.7

18.6

125

2

29

6.5

5.0

1

48.35

60

GEV300

575/60/3

34.7

14.7

100

2

23

5.3

5.0

1

38.38

50

GEV300

208/60/3

116.2

48.1

245

2

75

20.0

7.5

1

128.23

175

GEV300

230/60/3

115.6

48.1

245

2

75

19.4

7.5

1

127.63

175

GEV300

460/60/3

46.9

18.6

125

2

29

9.7

7.5

1

51.55

70

GEV300

575/60/3

37.4

14.7

100

2

23

8.0

7.5

1

41.08

50

GEV300

208/60/3

122.2

48.1

245

2

75

26.0

10.0

1

134.23

175

GEV300

230/60/3

121.2

48.1

245

2

75

25.0

10.0

1

133.23

175

GEV300

460/60/3

49.7

18.6

125

2

29

12.5

10.0

1

54.35

70

GEV300

575/60/3

39.4

14.7

100

2

23

10.0

10.0

1

43.08

50

GEV300

208/60/3

133.2

48.1

245

2

75

37.0

15.0

1

145.23

175

GEV300

230/60/3

132.2

48.1

245

2

75

36.0

15.0

1

144.23

175

GEV300

460/60/3

55.2

18.6

125

2

29

18.0

15.0

1

59.85

70

GEV300

575/60/3

43.5

14.7

100

2

23

14.1

15.0

1

47.18

60

No. of
Comp.

GEV - Vertical Units

Table 51.

Electrical data: 6 to 25 tons - two speed blower motor
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH072

208/60/3

24.1

10.4

73

2

16.3

3.3

1.0

1

26.70

35

GEH072

230/60/3

23.8

10.4

73

2

16.3

3.0

1.0

1

26.40

35

GEH072

460/60/3

13.1

5.8

38

2

9

1.5

1.0

1

14.55

20

GEH072

208/60/3

25.7

10.4

73

2

16.3

4.9

1.5

1

28.30

35

GEH072

230/60/3

25.2

10.4

73

2

16.3

4.4

1.5

1

27.80

35

GEH072

460/60/3

13.8

5.8

38

2

9

2.2

1.5

1

15.25

20

GEH072

208/60/3

27.5

10.4

73

2

16.3

6.7

2.0

1

30.10

40

GEH072

230/60/3

26.9

10.4

73

2

16.3

6.1

2.0

1

29.50

35

GEH072

460/60/3

14.7

5.8

38

2

9

3.1

2.0

1

16.15

20

GEH090

208/60/3

28.2

14.5/10.4

98/73

2

22.6/16.3

3.3

1.0

1

31.83

45

GEH090

230/60/3

27.9

14.5/10.4

98/73

2

22.6/16.3

3.0

1.0

1

31.53

45

No. of
Comp.

GEH - Horizontal Units

continued on next page

WSHP-SVX01N-EN

87

Electrical Data
Table 51.

Electrical data: 6 to 25 tons - two speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH090

460/60/3

13.6

6.3/5.8

55/38

2

9.9/9

1.5

1.0

1

15.18

20

GEH090

208/60/3

29.8

14.5/10.4

98/73

2

22.6/16.3

4.9

1.5

1

33.43

45

GEH090

230/60/3

29.3

14.5/10.4

98/73

2

22.6/16.3

4.4

1.5

1

32.93

45

GEH090

460/60/3

14.3

6.3/5.8

55/38

2

9.9/9

2.2

1.5

1

15.88

20

GEH090

208/60/3

31.6

14.5/10.4

98/73

2

22.6/16.3

6.7

2.0

1

35.23

45

GEH090

230/60/3

31.0

14.5/10.4

98/73

2

22.6/16.3

6.1

2.0

1

34.63

45

GEH090

460/60/3

15.2

6.3/5.8

55/38

2

9.9/9

3.1

2.0

1

16.78

20

GEH090

208/60/3

33.7

14.5/10.4

98/73

2

22.6/16.3

8.8

3.0

1

37.33

50

GEH090

230/60/3

32.9

14.5/10.4

98/73

2

22.6/16.3

8.0

3.0

1

36.53

50

GEH090

460/60/3

16.6

6.3

55

2

9.9

4.0

3.0

1

18.18

20

GEH120

208/60/3

36.9

16

110

2

24.9

4.9

1.5

1

40.90

50

GEH120

230/60/3

36.4

16

110

2

24.9

4.4

1.5

1

40.40

50

GEH120

460/60/3

17.8

7.8

52

2

12.1

2.2

1.5

1

19.75

25

GEH120

208/60/3

38.7

16

110

2

24.9

6.7

2.0

1

42.70

50

GEH120

230/60/3

38.1

16

110

2

24.9

6.1

2.0

1

42.10

50

GEH120

460/60/3

18.7

7.8

52

2

12.1

3.1

2.0

1

20.65

25

GEH120

208/60/3

40.8

16

110

2

24.9

8.8

3.0

1

44.80

60

GEH120

230/60/3

40.0

16

110

2

24.9

8.0

3.0

1

44.00

60

GEH120

460/60/3

19.6

7.8

52

2

12.1

4.0

3.0

1

21.55

25

GEH120

208/60/3

46.6

16

110

2

24.9

14.6

5.0

1

50.60

60

GEH120

230/60/3

45.2

16

110

2

24.9

13.2

5.0

1

49.20

60

GEH120

460/60/3

22.2

7.8

52

2

12.1

6.6

5.0

1

24.15

30

GEH150

208/60/3

49.7

22.4

149

2

35

4.9

1.5

1

55.30

70

GEH150

230/60/3

49.2

22.4

149

2

35

4.4

1.5

1

54.80

70

GEH150

460/60/3

23.4

10.6

75

2

16.5

2.2

1.5

1

26.05

35

GEH150

208/60/3

51.5

22.4

149

2

35

6.7

2.0

1

57.10

70

GEH150

230/60/3

50.9

22.4

149

2

35

6.1

2.0

1

56.50

70

GEH150

460/60/3

24.3

10.6

75

2

16.5

3.1

2.0

1

26.95

35

GEH150

208/60/3

53.6

22.4

149

2

35

8.8

3.0

1

59.20

80

GEH150

230/60/3

52.8

22.4

149

2

35

8.0

3.0

1

58.40

80

GEH150

460/60/3

25.2

10.6

75

2

16.5

4.0

3.0

1

27.85

35

GEH150

208/60/3

59.4

22.4

149

2

35

14.6

5.0

1

65.00

80

GEH150

230/60/3

58.0

22.4

149

2

35

13.2

5.0

1

63.60

80

GEH150

460/60/3

27.8

10.6

75

2

16.5

6.6

5.0

1

30.45

40

GEH180

208/60/3

56.7

25

164

2

39

6.7

2.0

1

62.95

80

GEH180

230/60/3

56.1

25

164

2

39

6.1

2.0

1

62.35

80

GEH180

460/60/3

27.5

12.2

100

2

19

3.1

2.0

1

30.55

40

GEH180

208/60/3

58.8

25

164

2

39

8.8

3.0

1

65.05

90

GEH180

230/60/3

58.0

25

164

2

39

8.0

3.0

1

64.25

80

GEH180

460/60/3

28.4

12.2

100

2

19

4.0

3.0

1

31.45

40

GEH180

208/60/3

64.6

25

164

2

39

14.6

5.0

1

70.85

90

GEH180

230/60/3

63.2

25

164

2

39

13.2

5.0

1

69.45

90

GEH180

460/60/3

31.0

12.2

100

2

19

6.6

5.0

1

34.05

45

No. of
Comp.

GEH - Horizontal Units

continued on next page

88

WSHP-SVX01N-EN

Electrical Data
Table 51.

Electrical data: 6 to 25 tons - two speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEH180

208/60/3

72.1

25

164

2

39

22.1

7.5

1

78.35

100

GEH180

230/60/3

70.0

25

164

2

39

20.0

7.5

1

76.25

100

GEH180

460/60/3

34.4

12.2

100

2

19

10.0

7.5

1

37.45

45

GEV072

208/60/3

24.1

10.4

73

2

16.3

3.3

1.0

1

26.70

35

GEV072

230/60/3

23.8

10.4

73

2

16.3

3.0

1.0

1

26.40

35

GEV072

460/60/3

13.1

5.8

38

2

9

1.5

1.0

1

14.55

20

GEV072

208/60/3

25.7

10.4

73

2

16.3

4.9

1.5

1

28.30

35

GEV072

230/60/3

25.2

10.4

73

2

16.3

4.4

1.5

1

27.80

35

GEV072

460/60/3

13.8

5.8

38

2

9

2.2

1.5

1

15.25

20

GEV072

208/60/3

27.5

10.4

73

2

16.3

6.7

2.0

1

30.10

40

GEV072

230/60/3

26.9

10.4

73

2

16.3

6.1

2.0

1

29.50

35

GEV072

460/60/3

14.7

5.8

38

2

9

3.1

2.0

1

16.15

20

GEV090

208/60/3

28.2

14.5/10.4

98/73

2

22.6/16.3

3.3

1.0

1

31.83

45

GEV090

230/60/3

27.9

14.5/10.4

98/73

2

22.6/16.3

3.0

1.0

1

31.53

45

GEV090

460/60/3

13.6

6.3/5.8

55/38

2

9.9/9

1.5

1.0

1

15.18

20

GEV090

208/60/3

29.8

14.5/10.4

98/73

2

22.6/16.3

4.9

1.5

1

33.43

45

GEV090

230/60/3

29.3

14.5/10.4

98/73

2

22.6/16.3

4.4

1.5

1

32.93

45

GEV090

460/60/3

14.3

6.3/5.8

55/38

2

9.9/9

2.2

1.5

1

15.88

20

GEV090

208/60/3

31.6

14.5/10.4

98/73

2

22.6/16.3

6.7

2.0

1

35.23

45

GEV090

230/60/3

31.0

14.5/10.4

98/73

2

22.6/16.3

6.1

2.0

1

34.63

45

GEV090

460/60/3

15.2

6.3/5.8

55/38

2

9.9/9

3.1

2.0

1

16.78

20

GEV090

208/60/3

33.7

14.5/10.4

98/73

2

22.6/16.3

8.8

3.0

1

37.33

50

GEV090

230/60/3

32.9

14.5/10.4

98/73

2

22.6/16.3

8.0

3.0

1

36.53

50

GEV090

460/60/3

16.1

6.3/5.8

55/38

2

9.9/9

4.0

3.0

1

17.68

20

GEV120

208/60/3

36.9

16

110

2

24.9

4.9

1.5

1

40.90

50

GEV120

230/60/3

36.4

16

110

2

24.9

4.4

1.5

1

40.40

50

GEV120

460/60/3

17.8

7.8

52

2

12.1

2.2

1.5

1

19.75

25

GEV120

208/60/3

38.7

16

110

2

24.9

6.7

2.0

1

42.70

50

GEV120

230/60/3

38.1

16

110

2

24.9

6.1

2.0

1

42.10

50

GEV120

460/60/3

18.7

7.8

52

2

12.1

3.1

2.0

1

20.65

25

GEV120

208/60/3

40.8

16

110

2

24.9

8.8

3.0

1

44.80

60

GEV120

230/60/3

40.0

16

110

2

24.9

8.0

3.0

1

44.00

60

GEV120

460/60/3

19.6

7.8

52

2

12.1

4.0

3.0

1

21.55

25

GEV120

208/60/3

46.6

16

110

2

24.9

14.6

5.0

1

50.60

60

GEV120

230/60/3

45.2

16

110

2

24.9

13.2

5.0

1

49.20

60

GEV120

460/60/3

22.2

7.8

52

2

12.1

6.6

5.0

1

24.15

30

GEV150

208/60/3

51.5

22.4

149

2

35

6.7

2.0

1

57.10

70

GEV150

230/60/3

50.9

22.4

149

2

35

6.1

2.0

1

56.50

70

GEV150

460/60/3

24.3

10.6

75

2

16.5

3.1

2.0

1

26.95

35

GEV150

208/60/3

53.6

22.4

149

2

35

8.8

3.0

1

59.20

80

GEV150

230/60/3

52.8

22.4

149

2

35

8.0

3.0

1

58.40

80

GEV150

460/60/3

25.2

10.6

75

2

16.5

4.0

3.0

1

27.85

35

No. of
Comp.

GEH - Horizontal Units

GEV - Vertical Units

continued on next page

WSHP-SVX01N-EN

89

Electrical Data
Table 51.

Electrical data: 6 to 25 tons - two speed blower motor (continued)
Maximum
Blower Blower Fan Minimum Overcurrent
Motor Motor Motor Circuit
Protective
Cmp MCC
FLA
HP
No. Ampacity
Device

Model
No.

Volts

Total
FLA

Comp RLA
(ea)

Comp
LRA
(ea)

GEV150

208/60/3

59.4

22.4

149

2

35

14.6

5.0

1

65.00

80

GEV150

230/60/3

58.0

22.4

149

2

35

13.2

5.0

1

63.60

80

GEV150

460/60/3

27.8

10.6

75

2

16.5

6.6

5.0

1

30.45

40

GEV180

208/60/3

58.8

25

164

2

39

8.8

3.0

1

65.05

90

GEV180

230/60/3

58.0

25

164

2

39

8.0

3.0

1

64.25

80

GEV180

460/60/3

28.4

12.2

100

2

19

4.0

3.0

1

31.45

40

GEV180

208/60/3

64.6

25

164

2

39

14.6

5.0

1

70.85

90

GEV180

230/60/3

63.2

25

164

2

39

13.2

5.0

1

69.45

90

GEV180

460/60/3

31.0

12.2

100

2

19

6.6

5.0

1

34.05

45

GEV180

208/60/3

72.1

25

164

2

39

22.1

7.5

1

78.35

100

GEV180

230/60/3

70.0

25

164

2

39

20.0

7.5

1

76.25

100

GEV180

460/60/3

34.4

12.2

100

2

19

10.0

7.5

1

37.45

45

GEV240

208/60/3

74.8

30.1

225

2

47

14.6

5.0

1

82.33

110

GEV240

230/60/3

73.4

30.1

225

2

47

13.2

5.0

1

80.93

110

GEV240

460/60/3

40.0

16.7

114

2

26

6.6

5.0

1

44.18

60

GEV240

208/60/3

82.3

30.1

225

2

47

22.1

7.5

1

89.83

110

GEV240

230/60/3

80.2

30.1

225

2

47

20.0

7.5

1

87.73

110

GEV240

460/60/3

43.4

16.7

114

2

26

10.0

7.5

1

47.58

60

GEV240

208/60/3

87.8

30.1

225

2

47

27.6

10.0

1

95.33

125

GEV240

230/60/3

85.2

30.1

225

2

47

25.0

10.0

1

92.73

110

GEV240

460/60/3

46.4

16.7

114

2

26

13.0

10.0

1

50.58

60

GEV240

460/60/3

53.4

16.7

114

2

26

20.0

15.0

1

58.40

70

GEV300

208/60/3

110.8

48.1

245

2

75

14.6

5.0

1

122.83

150

GEV300

230/60/3

109.4

48.1

245

2

75

13.2

5.0

1

121.43

150

GEV300

460/60/3

43.8

18.6

125

2

29

6.6

5.0

1

48.45

60

GEV300

208/60/3

118.3

48.1

245

2

75

22.1

7.5

1

130.33

175

GEV300

230/60/3

116.2

48.1

245

2

75

20.0

7.5

1

128.23

175

GEV300

460/60/3

47.2

18.6

125

2

29

10.0

7.5

1

51.85

70

GEV300

208/60/3

123.8

48.1

245

2

75

27.6

10.0

1

135.83

175

GEV300

230/60/3

121.2

48.1

245

2

75

25.0

10.0

1

133.23

175

GEV300

460/60/3

50.2

18.6

125

2

29

13.0

10.0

1

54.85

70

GEV300

460/60/3

57.2

18.6

125

2

29

20.0

15.0

1

62.20

80

No. of
Comp.

GEV - Vertical Units

90

WSHP-SVX01N-EN

Electrical Data
Table 52.

Electrical minimum and maximum

Digit 8

Rated Voltage

Hz

Ph

Min Utiliz. Volts

0

115

60

1

104

Max Utiliz. Volts
126

1

208

60

1

197

229

2

230

60

1

207

253

3

208

60

3

187

229

4

460

60

3

414

506

5

575

60

3

518

633

6

220-240

50

1

198

264

7

265

60

1

239

292

8

230

60

3

207

253

9

380-415

50

3

342

456

WSHP-SVX01N-EN

91

Pre-Start Checklist
Before energizing the unit, the following system devices
must be checked:

•

Are the low/high-side pressure temperature caps
secure and in place?

•

Is the high voltage power supply correct and in
accordance with the nameplate ratings?

•

Are all the unit access panels secure and in place?

•

Is the thermostat in the OFF position?

•

Is phasing of the unit correct per compressor rotation
(scroll compressor only)?

•

Is the water flow established and circulating through
all the units?

•

Is the field wiring and circuit protection the correct
size?

•

Is the duct work correctly sized, run, taped, insulated
and weather proofed with proper unit arrangement?

•

Is the low voltage control circuit wiring correct per the
unit wiring diagram?

•

Is the condensate line properly sized, run, trapped,
pitched and primed?

•

Is the piping system clean/complete and correct? (A
recommendation of all system flushing of debris from
the water-to-refrigerant heat exchanger, along with air
purging from the water-to-refrigerant heat exchanger
be done in accordance with the Closed-Loop/Ground
Source Heat Pump Systems Installation Guide).

•

Is the zone sensor correctly wired and in a good
location?

•

Does the indoor blower turn freely without rubbing?

•

Has all work been done in accordance with applicable
local and national codes?

•

Is vibration isolation provided? (i.e. unit isolation pad,
hose kits)

Has heat transfer fluid been added in the proper mix to
prevent freezing in closed system application?

•

Is unit serviceable? (See clearance specifications in
“Unit Dimensions and Weights,” p. 14).

92

WSHP-SVX01N-EN

Start-Up
Initial Unit Start-up

Table 53.

Note: Start-up with the heat pump thermostat is included
below:
1. Set the thermostat to the highest position.

Checklist
MODE

Pressure Differential

Heat

Cool

_________PSI _________PSI
G
G

COMPRESSOR

2. Set the thermostat system switch to COOL with the fan
control to AUTO.The compressor should NOT run.

Amps

3. Reduce the thermostat setting until the compressor,
reversing valve, solenoid valve, and loop pump are
energized. Adjust water flow utilizing pressure/
temperature plugs and comparing to tables contained
in specification sheet data.

Discharge line temperature (after 10
minutes)

Water leaving the heat exchanger should be warmer
than the entering water temperature (approximately 912ºF); blower operation should be smooth;
compressor and blower amps should be within data
plate ratings; the suction line should be cool with no
frost observed in the refrigerant circuit.

Volts
_______F

_______F

Start-Up Checklist and Log
Installing Contractor: Use this checklist to thoroughly
check-out the system and units before and during start-up.
(This form need not be returned to the factory unless
requested during technical service support).
Job Name:________________________
Model Number:____________________

4. Check the cooling refrigerant pressures against values
in Table 54, p. 94.

Date:______________________________

5. Turn the thermostat system switch to the OFF position.
Unit should stop running and the reversing valve
should de-energize.

In order to minimize troubleshooting and costly system
failures, complete the following checks and data entries
before the system is put into full operation.

6. Leave unit off for approximately FIVE minutes to allow
for pressure equalization.

Operating Pressures

7. Turn the thermostat to the lowest setting.

There are many variables (airflow, air temperatures) in an
air conditioning system that will affect operating
refrigerant pressures and temperatures.The charts below
shows approximate conditions and is based on air flow at
the rated SCFM, entering air at 80.6°F(DB), 66.2°F(WB) in
cooling, 68°F(DB) in heating. (+)Heating data with 35°F
EWT is based on the use of an anti-freeze solution having
a freezing point 20°F lower than the minimum expected
entering temperature.

8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is
energized. Warm air should blow from the register. A
water temperature decrease of approximately 5-9ºF
leaving the heat exchanger should be noted.The
blower and compressor operation should be smooth
with no frost observed in the refrigeration circuit.

Serial Number:_____________________

10. Check the heating refrigerant pressures against values
in Table 54, p. 94.
11. Set the thermostat to maintain the desired space
temperature.
12. Instruct the owner on system operation.
Table 53.

Checklist
MODE

Heat

Cool

Entering fluid temperature

_______F

_______F

Leaving fluid temperature

_______F

_______F

Temperature differential

_______F

_______F

Return-air temperature DB/WB

_______F

_______F

Supply-air temperature DB/WB

_______F

_______F

Temperature differential

_______F

_______F

Water coil heat exchanger (Water
Pressure IN)

________PSIG ________PSIG

Water coil heat exchanger (Water
Pressure OUT)

________PSIG ________PSIG

WSHP-SVX01N-EN

93

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units
Operating Data
Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

006 (60 Hz)

35

1.4

—

—

—

—

94-108

279-355

6-8

23-29

006 (60 Hz)

35

1.7

—

—

—

—

96-110

281-357

5-6

23-29

006 (60 Hz)

45

1.4

143-165

190-243

13-16

24-30

110-127

297-377

7-9

26-34

006 (60 Hz)

45

1.7

143-164

184-235

11-13

24-31

113-130

300-382

6-8

27-34

006 (60 Hz)

55

1.4

145-167

217-277

13-16

23-30

128-147

317-404

8-10

30-39

006 (60 Hz)

55

1.7

144-166

210-268

11-13

24-30

131-151

320-407

7-9

31-39

006 (60 Hz)

68

1.4

148-171

254-324

12-15

23-29

154-177

345-439

10-12

35-45

006 (60 Hz)

68

1.7

147-170

244-312

10-13

23-29

158-182

349-444

8-10

36-45

006 (60 Hz)

75

1.4

148-171

281-358

12-15

23-29

169-195

361-459

10-13

38-48

006 (60 Hz)

75

1.7

148-170

273-348

10-13

23-29

175-201

366-466

9-11

38-48

006 (60 Hz)

86

1.4

149-172

328-418

12-15

22-28

197-226

388-494

11-15

41-52

006 (60 Hz)

86

1.7

149-172

320-407

10-13

23-29

203-234

395-502

10-12

41-52

006 (60 Hz)

95

1.4

151-173

373-474

12-15

22-28

—

—

—

—

006 (60 Hz)

95

1.7

150-173

363-462

10-13

22-28

—

—

—

—

009 (60Hz)
006 (50 Hz)

35

1.7

—

—

—

—

93-107

272-346

6-7

20-26

009 (60Hz)
006 (50 Hz)

35

2.1

—

—

—

—

95-110

274-348

5-6

21-27

009 (60Hz)
006 (50 Hz)

45

1.7

142-164

187-238

13-16

22-28

109-126

288-366

7-9

24-30

009 (60Hz)
006 (50 Hz)

45

2.1

142-164

181-230

11-14

22-27

112-129

291-370

6-7

24-31

009 (60Hz)
006 (50 Hz)

55

1.7

144-166

214-272

12-15

21-27

127-146

305-388

8-10

27-34

009 (60Hz)
006 (50 Hz)

55

2.1

144-166

207-263

10-13

21-27

130-150

309-393

7-8

27-35

009 (60Hz)
006 (50 Hz)

68

1.7

146-168

258-328

12-15

20-26

153-176

330-420

9-12

31-39

009 (60Hz)
006 (50 Hz)

68

2.1

146-168

250-318

10-12

21-26

157-181

335-427

8-10

32-40

009 (60Hz)
006 (50 Hz)

75

1.7

147-169

286-363

12-15

20-25

168-193

345-439

10-13

33-42

009 (60Hz)
006 (50 Hz)

75

2.1

147-169

277-352

9-12

20-26

174-200

350-446

8-11

34-43

009 (60Hz)
006 (50 Hz)

86

1.7

149-171

336-427

12-15

19-25

195-224

370-471

11-14

36-46

009 (60Hz)
006 (50 Hz)

86

2.1

148-171

326-415

9-12

20-25

202-232

375-477

9-12

37-47

009 (60Hz)
006 (50 Hz)

95

1.7

149-172

386-491

12-15

19-24

—

—

—

—

009 (60Hz)
006 (50 Hz)

95

2.1

149-172

375-477

9-12

19-24

—

—

—

—

012 (60Hz)
009 (50 Hz)

35

2.2

—

—

—

—

92-106

288-367

10-13

21-27

012 (60Hz)
009 (50 Hz)

35

2.8

—

—

—

—

95-109

290-370

8-11

21-27

GEH*/GEV*

94

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*/GEV*
012 (60Hz)
009 (50 Hz)

45

2.2

142-163

183-233

12-15

22-28

108-125

304-387

12-15

24-30

012 (60Hz)
009 (50 Hz)

45

2.8

142-163

175-223

9-12

23-29

111-128

307-391

9-12

24-31

012 (60Hz)
009 (50 Hz)

55

2.2

143-164

212-270

12-15

21-27

126-145

322-410

13-16

26-33

012 (60Hz)
009 (50 Hz)

55

2.8

143-164

204-260

9-12

22-27

130-149

325-413

10-13

27-34

012 (60Hz)
009 (50 Hz)

68

2.2

144-166

257-327

12-15

21-26

152-174

346-441

14-18

29-37

012 (60Hz)
009 (50 Hz)

68

2.8

144-166

248-316

9-12

21-26

157-180

352-448

11-15

29-37

012 (60Hz)
009 (50 Hz)

75

2.2

145-167

284-361

12-15

20-26

167-192

361-460

15-19

30-38

012 (60Hz)
009 (50 Hz)

75

2.8

145-167

274-349

9-12

20-26

173-199

366-466

12-15

30-39

012 (60Hz)
009 (50 Hz)

86

2.2

146-168

332-422

12-15

19-25

194-223

384-489

16-21

32-40

012 (60Hz)
009 (50 Hz)

86

2.8

146-168

321-409

9-12

20-25

201-231

390-497

13-17

32-41

012 (60Hz)
009 (50 Hz)

95

2.2

147-170

376-478

12-15

19-24

—

—

—

—

012 (60Hz)
009 (50 Hz)

95

2.8

147-170

365-465

9-12

19-24

—

—

—

—

015 (60Hz)
012 (50 Hz)

35

2.8

—

—

—

—

91-105

296-377

6-7

20-25

015 (60Hz)
012 (50 Hz)

35

3.5

—

—

—

—

93-107

299-380

5-6

20-26

015 (60Hz)
012 (50 Hz)

45

2.8

138-159

180-230

11-14

22-28

107-123

313-398

7-8

23-29

015 (60Hz)
012 (50 Hz)

45

3.5

138-158

174-221

9-11

22-27

109-126

316-402

5-7

23-30

015 (60Hz)
012 (50 Hz)

55

2.8

139-159

210-267

11-14

21-27

124-143

332-423

8-10

26-33

015 (60Hz)
012 (50 Hz)

55

3.5

138-159

203-258

9-11

21-27

128-147

336-427

6-8

27-34

015 (60Hz)
012 (50 Hz)

68

2.8

140-161

254-324

11-14

20-26

150-172

358-456

9-11

30-38

015 (60Hz)
012 (50 Hz)

68

3.5

140-161

246-313

9-11

21-26

154-178

364-463

7-9

30-39

015 (60Hz)
012 (50 Hz)

75

2.8

141-162

281-358

11-14

20-25

165-190

373-475

10-12

32-40

015 (60Hz)
012 (50 Hz)

75

3.5

140-162

272-347

9-11

20-26

171-196

379-483

8-10

32-41

015 (60Hz)
012 (50 Hz)

86

2.8

142-163

328-417

11-14

19-25

191-220

399-508

11-14

34-43

015 (60Hz)
012 (50 Hz)

86

3.5

142-163

318-405

9-11

20-25

198-228

405-515

9-11

34-44

WSHP-SVX01N-EN

95

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*/GEV*
015 (60Hz)
012 (50 Hz)

95

2.8

143-165

371-472

11-14

19-24

—

—

—

—

015 (60Hz)
012 (50 Hz)

95

3.5

143-165

361-459

9-11

19-24

—

—

—

—

018 (60Hz)
015 (50 Hz)

35

3.3

—

—

—

—

89-102

276-351

6-7

21-26

018 (60Hz)
015 (50 Hz)

35

4.2

—

—

—

—

91-105

279-354

5-6

21-27

018 (60Hz)
015 (50 Hz)

45

3.3

142-163

186-237

12-15

23-29

104-120

292-372

7-9

24-30

018 (60Hz)
015 (50 Hz)

45

4.2

142-163

179-227

9-12

23-29

107-123

295-376

5-7

24-31

018 (60Hz)
015 (50 Hz)

55

3.3

142-163

216-275

12-15

23-29

121-139

310-395

8-10

27-34

018 (60Hz)
015 (50 Hz)

55

4.2

142-163

207-264

9-12

23-29

125-143

313-399

6-8

27-35

018 (60Hz)
015 (50 Hz)

68

3.3

142-163

262-333

12-15

22-28

146-168

334-425

9-12

31-39

018 (60Hz)
015 (50 Hz)

68

4.2

142-163

252-321

9-12

22-28

151-174

338-430

7-9

32-40

018 (60Hz)
015 (50 Hz)

75

3.3

142-164

289-368

12-15

21-27

161-185

347-441

10-13

33-42

018 (60Hz)
015 (50 Hz)

75

4.2

142-164

280-356

9-12

21-27

167-192

351-447

8-10

34-43

018 (60Hz)
015 (50 Hz)

86

3.3

143-165

338-430

12-15

20-26

188-216

365-464

11-14

36-46

018 (60Hz)
015 (50 Hz)

86

4.2

143-165

327-416

9-12

20-26

195-225

370-471

9-11

37-47

018 (60Hz)
015 (50 Hz)

95

3.3

144-166

383-488

12-15

19-24

—

—

—

—

018 (60Hz)
015 (50 Hz)

95

4.2

144-166

372-473

9-12

19-25

—

—

—

—

GEH*024

96

024 (60Hz)
018 (50Hz)

35

—

—

—

—

—

76-88

279-355

6-7

21-30

024 (60Hz)
018 (50Hz)

35

—

—

—

—

—

78-89

280-357

5-6

21-31

024 (60Hz)
018 (50Hz)

45

4.5

114-131

172-219

12-16

20-26

89-103

290-369

7-9

24-34

024 (60Hz)
018 (50Hz)

45

5.6

114-131

165-211

10-13

20-26

91-105

292-371

6-7

24-34

024 (60Hz)
018 (50Hz)

55

4.5

115-132

200-255

12-15

20-26

106-122

307-390

8-10

27-37

024 (60Hz)
018 (50Hz)

55

5.6

115-132

193-246

10-12

20-26

108-125

309-394

6-8

28-38

024 (60Hz)
018 (50Hz)

68

4.5

120-139

239-304

12-15

19-25

124-143

326-415

9-12

31-42

024 (60Hz)
018 (50Hz)

68

5.6

120-138

231-294

10-12

20-25

129-148

330-420

7-9

32-43

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*024
024 (60Hz)
018 (50Hz)

75

4.5

121-140

264-336

12-15

19-25

139-159

340-432

10-13

34-44

024 (60Hz)
018 (50Hz)

75

5.6

121-139

256-325

9-12

19-25

143-165

343-437

8-10

34-45

024 (60Hz)
018 (50Hz)

86

4.5

124-143

305-389

12-15

18-24

163-188

363-462

11-14

38-49

024 (60Hz)
018 (50Hz)

86

5.6

124-143

297-378

9-12

19-24

169-195

368-468

9-12

39-50

024 (60Hz)
018 (50Hz)

95

4.5

126-145

344-437

12-15

18-24

—

—

—

—

024 (60Hz)
018 (50Hz)

95

5.6

126-145

335-426

9-12

18-24

—

—

—

—

GEV*024
024 (60Hz)
018 (50Hz)

35

—

—

—

—

—

76-87

270-344

6-7

21-30

024 (60Hz)
018 (50Hz)

35

—

—

—

—

—

78-89

272-346

5-6

21-31

024 (60Hz)
018 (50Hz)

45

4.5

114-132

173-221

12-16

20-26

88-102

283-360

7-9

24-34

024 (60Hz)
018 (50Hz)

45

5.6

114-131

167-212

10-12

20-26

90-104

285-362

6-7

24-34

024 (60Hz)
018 (50Hz)

55

4.5

116-133

202-258

12-15

20-25

105-121

299-381

8-10

27-37

024 (60Hz)
018 (50Hz)

55

5.6

116-133

195-249

10-12

20-26

107-124

301-384

6-8

28-38

024 (60Hz)
018 (50Hz)

68

4.5

122-140

242-308

12-15

20-26

123-141

315-401

9-12

31-41

024 (60Hz)
018 (50Hz)

68

5.6

122-140

234-298

10-12

20-26

127-146

318-405

7-9

32-42

024 (60Hz)
018 (50Hz)

75

4.5

123-141

268-341

12-15

19-25

137-158

327-417

10-13

34-44

024 (60Hz)
018 (50Hz)

75

5.6

123-141

259-330

10-12

20-25

142-163

331-421

8-10

34-45

024 (60Hz)
018 (50Hz)

86

4.5

126-145

310-394

12-15

19-25

161-186

349-444

11-14

38-49

024 (60Hz)
018 (50Hz)

86

5.6

125-144

301-383

9-12

19-25

167-193

353-449

9-12

39-50

024 (60Hz)
018 (50Hz)

95

4.5

127-146

349-445

12-15

19-25

—

—

—

—

024 (60Hz)
018 (50Hz)

95

5.6

127-146

340-433

9-12

19-25

—

—

—

—

GEH*030
030 (60 Hz)
024 (50 Hz)

35

—

—

—

—

—

77-89

276-351

6-7

21-30

030 (60 Hz)
024 (50 Hz)

35

—

—

—

—

—

79-90

277-352

4-6

21-30

030 (60 Hz)
024 (50 Hz)

45

5.6

120-138

171-218

12-15

22-27

91-104

290-369

7-8

24-34

030 (60 Hz)
024 (50 Hz)

45

7.0

120-138

165-210

10-12

22-28

93-107

292-371

5-7

24-34

WSHP-SVX01N-EN

97

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*030
030 (60 Hz)
024 (50 Hz)

55

5.6

121-140

200-254

12-15

21-27

108-124

307-390

8-10

27-37

030 (60 Hz)
024 (50 Hz)

55

7.0

121-139

193-245

9-12

22-27

111-127

309-393

6-8

28-38

030 (60 Hz)
024 (50 Hz)

68

5.6

122-140

249-317

12-15

20-26

128-148

329-419

9-11

32-42

030 (60 Hz)
024 (50 Hz)

68

7.0

122-140

241-306

9-12

20-26

133-152

333-423

7-9

32-43

030 (60 Hz)
024 (50 Hz)

75

5.6

123-141

275-350

12-15

20-26

143-164

342-436

10-12

34-45

030 (60 Hz)
024 (50 Hz)

75

7.0

123-141

267-340

9-12

20-26

148-170

346-440

8-10

35-46

030 (60 Hz)
024 (50 Hz)

86

5.6

126-146

310-395

11-14

20-26

168-193

365-465

11-14

38-49

030 (60 Hz)
024 (50 Hz)

86

7.0

126-145

302-384

9-11

20-26

174-200

370-470

9-11

39-50

030 (60 Hz)
024 (50 Hz)

95

5.6

128-148

350-446

11-14

19-25

—

—

—

—

030 (60 Hz)
024 (50 Hz)

95

7.0

128-147

341-434

9-11

19-25

—

—

—

—

GEV*030
030 (60 Hz)
024 (50 Hz)

35

—

—

—

—

—

76-88

266-338

6-7

21-30

030 (60 Hz)
024 (50 Hz)

35

—

—

—

—

—

78-90

268-341

5-6

22-31

030 (60 Hz)
024 (50 Hz)

45

5.6

115-132

172-218

12-15

21-27

87-100

275-351

6-8

24-33

030 (60 Hz)
024 (50 Hz)

45

7.0

115-132

165-210

9-12

21-27

90-103

278-354

5-7

24-34

030 (60 Hz)
024 (50 Hz)

55

5.6

116-134

201-256

12-15

20-26

104-119

292-371

8-10

27-37

030 (60 Hz)
024 (50 Hz)

55

7.0

116-134

194-247

9-12

21-26

107-123

295-375

6-8

28-38

030 (60 Hz)
024 (50 Hz)

68

5.6

121-139

242-308

11-15

20-26

122-141

311-396

9-11

31-41

030 (60 Hz)
024 (50 Hz)

68

7.0

120-138

234-298

9-12

20-26

126-145

314-400

7-9

32-42

030 (60 Hz)
024 (50 Hz)

75

5.6

122-140

268-341

11-14

20-26

136-157

324-412

9-12

34-44

030 (60 Hz)
024 (50 Hz)

75

7.0

122-140

260-331

9-12

20-26

141-162

328-418

8-10

34-45

030 (60 Hz)
024 (50 Hz)

86

5.6

124-142

311-396

11-14

19-25

161-185

345-439

11-14

38-49

030 (60 Hz)
024 (50 Hz)

86

7.0

123-142

303-385

9-11

19-25

167-192

350-445

9-11

39-50

030 (60 Hz)
024 (50 Hz)

95

5.6

125-144

351-447

11-14

19-25

—

—

—

—

030 (60 Hz)
024 (50 Hz)

95

7.0

125-144

342-436

9-11

19-25

—

—

—

—

98

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*036
036 (60 Hz)
030 (50 Hz)

35

—

—

—

—

—

76-88

294-375

6-8

21-30

036 (60 Hz)
030 (50 Hz)

45

6.7

115-132

174-222

12-15

20-26

89-102

306-390

7-9

24-34

036 (60 Hz)
030 (50 Hz)

45

8.4

115-132

168-214

9-12

20-26

91-105

309-394

6-7

24-34

036 (60 Hz)
030 (50 Hz)

55

6.7

117-134

203-259

11-15

19-25

106-122

327-416

8-11

27-37

036 (60 Hz)
030 (50 Hz)

55

8.4

116-134

196-250

9-12

20-25

108-125

329-419

7-9

28-38

036 (60 Hz)
030 (50 Hz)

68

6.7

120-138

244-311

11-14

19-25

126-145

351-446

10-12

32-42

036 (60 Hz)
030 (50 Hz)

68

8.4

119-137

237-301

9-11

19-25

130-150

354-450

8-10

32-43

036 (60 Hz)
030 (50 Hz)

75

6.7

121-139

270-343

11-14

19-25

141-162

367-468

10-13

34-45

036 (60 Hz)
030 (50 Hz)

75

8.4

121-139

262-333

9-11

19-25

145-167

372-473

9-11

35-46

036 (60 Hz)
030 (50 Hz)

86

6.7

124-142

312-397

11-14

18-24

165-190

395-503

12-15

39-50

036 (60 Hz)
030 (50 Hz)

86

8.4

124-142

303-386

9-11

19-24

172-197

399-508

10-12

40-51

036 (60 Hz)
030 (50 Hz)

95

6.7

126-145

351-447

11-14

18-24

—

—

—

—

036 (60 Hz)
030 (50 Hz)

95

8.4

126-144

342-435

9-11

18-24

—

—

—

—

GEV*036
036 (60 Hz)
030 (50 Hz)

35

—

—

—

—

—

77-88

286-364

6-8

22-31

036 (60 Hz)
030 (50 Hz)

35

—

—

—

—

—

78-90

288-366

5-6

22-31

036 (60 Hz)
030 (50 Hz)

45

6.7

116-134

169-215

12-15

20-26

89-103

296-377

7-9

25-34

036 (60 Hz)
030 (50 Hz)

45

8.4

116-134

163-208

10-12

21-26

91-105

298-380

6-7

25-35

036 (60 Hz)
030 (50 Hz)

55

6.7

118-136

198-251

12-15

20-26

106-122

315-401

8-10

28-38

036 (60 Hz)
030 (50 Hz)

55

8.4

118-135

191-243

10-12

20-26

109-125

318-404

7-8

29-39

036 (60 Hz)
030 (50 Hz)

68

6.7

121-139

238-303

12-15

20-25

128-147

341-434

10-12

33-43

036 (60 Hz)
030 (50 Hz)

68

8.4

121-139

231-294

10-12

20-26

132-151

344-437

8-10

33-44

036 (60 Hz)
030 (50 Hz)

75

6.7

122-141

263-335

12-15

19-25

143-164

357-454

10-13

36-46

036 (60 Hz)
030 (50 Hz)

75

8.4

122-140

255-325

9-12

19-25

147-169

360-458

9-11

36-47

036 (60 Hz)
030 (50 Hz)

86

6.7

125-144

304-387

12-15

19-25

168-193

383-488

12-15

40-51

WSHP-SVX01N-EN

99

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEV*036
036 (60 Hz)
030 (50 Hz)

86

8.4

125-143

296-377

9-12

19-25

174-200

387-492

10-12

41-52

036 (60 Hz)
030 (50 Hz)

95

6.7

127-146

342-436

11-15

19-24

—

—

—

—

036 (60 Hz)
030 (50 Hz)

95

8.4

127-146

334-425

9-12

19-25

—

—

—

—

GEH*042
042 (60 Hz)
036 (50 Hz)

35

—

—

—

—

—

74-86

269-342

6-7

20-30

042 (60 Hz)
036 (50 Hz)

35

—

—

—

—

—

76-87

270-344

5-6

21-30

042 (60 Hz)
036 (50 Hz)

45

7.8

116-134

173-220

12-16

21-27

86-99

281-358

7-8

23-33

042 (60 Hz)
036 (50 Hz)

45

9.8

116-134

167-212

10-13

21-27

88-101

283-360

5-7

24-33

042 (60 Hz)
036 (50 Hz)

55

7.8

118-135

201-256

12-15

21-26

102-118

298-379

8-10

27-36

042 (60 Hz)
036 (50 Hz)

55

9.8

118-135

194-247

10-12

21-26

105-121

300-382

6-8

27-37

042 (60 Hz)
036 (50 Hz)

68

7.8

122-140

242-308

12-15

20-26

121-140

317-403

9-11

31-41

042 (60 Hz)
036 (50 Hz)

68

9.8

121-140

235-299

10-12

21-26

125-144

321-408

7-9

31-42

042 (60 Hz)
036 (50 Hz)

75

7.8

123-141

267-340

12-15

20-26

135-156

331-422

10-12

33-44

042 (60 Hz)
036 (50 Hz)

75

9.8

123-141

259-330

9-12

20-26

140-161

336-427

8-10

34-45

042 (60 Hz)
036 (50 Hz)

86

7.8

125-144

308-392

12-15

20-25

159-183

355-451

11-14

38-49

042 (60 Hz)
036 (50 Hz)

86

9.8

125-144

300-382

9-12

20-26

165-190

359-457

9-12

39-50

042 (60 Hz)
036 (50 Hz)

95

7.8

127-146

346-441

11-15

19-25

—

—

—

—

042 (60 Hz)
036 (50 Hz)

95

9.8

127-146

338-430

9-12

19-25

—

—

—

—

GEV*042
042 (60 Hz)
036 (50 Hz)

35

—

—

—

—

—

75-86

268-341

6-7

20-30

042 (60 Hz)
036 (50 Hz)

35

—

—

—

—

—

76-87

268-341

5-6

21-30

042 (60 Hz)
036 (50 Hz)

45

7.8

116-133

173-220

12-16

21-26

86-99

283-360

7-9

23-33

042 (60 Hz)
036 (50 Hz)

45

9.8

116-133

167-212

10-12

21-27

88-102

283-360

6-7

24-33

042 (60 Hz)
036 (50 Hz)

55

7.8

117-135

201-256

12-15

20-26

103-118

298-380

8-10

27-37

042 (60 Hz)
036 (50 Hz)

55

9.8

117-135

194-247

10-12

20-26

105-121

301-383

6-8

27-37

100

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEV*042
042 (60 Hz)
036 (50 Hz)

68

7.8

122-140

242-308

12-15

20-26

122-140

318-404

9-12

31-41

042 (60 Hz)
036 (50 Hz)

68

9.8

121-140

234-298

9-12

20-26

126-144

321-409

7-9

31-42

042 (60 Hz)
036 (50 Hz)

75

7.8

123-141

267-340

12-15

20-25

136-156

331-422

10-13

33-44

042 (60 Hz)
036 (50 Hz)

75

9.8

122-141

259-330

9-12

20-26

140-161

336-427

8-10

34-45

042 (60 Hz)
036 (50 Hz)

86

7.8

126-144

307-390

11-15

19-25

160-184

355-452

11-14

38-49

042 (60 Hz)
036 (50 Hz)

86

9.8

125-144

299-380

9-12

19-25

166-190

359-457

9-12

39-50

042 (60 Hz)
036 (50 Hz)

95

7.8

127-147

345-439

11-14

18-24

—

—

—

—

042 (60 Hz)
036 (50 Hz)

95

9.8

127-146

337-428

9-11

18-24

—

—

—

—

GEH*048
048 (60 Hz)
042 (50 Hz)

35

—

—

—

—

—

74-85

263-334

6-8

20-29

048 (60 Hz)
042 (50 Hz)

35

—

—

—

—

—

76-87

265-337

5-6

20-29

048 (60 Hz)
042 (50 Hz)

45

9.0

120-138

184-234

13-16

23-29

85-98

273-348

7-9

23-32

048 (60 Hz)
042 (50 Hz)

45

11.2

120-138

176-225

10-13

23-29

87-100

275-350

6-7

23-33

048 (60 Hz)
042 (50 Hz)

55

9.0

121-140

214-273

13-16

23-28

101-117

289-368

8-10

26-36

048 (60 Hz)
042 (50 Hz)

55

11.2

121-139

206-262

10-13

23-28

104-120

292-372

6-8

26-36

048 (60 Hz)
042 (50 Hz)

68

9.0

125-144

256-326

13-16

22-28

117-135

305-388

9-12

30-40

048 (60 Hz)
042 (50 Hz)

68

11.2

125-144

247-315

10-13

23-28

122-140

310-394

7-10

30-41

048 (60 Hz)
042 (50 Hz)

75

9.0

126-146

282-359

12-16

22-28

131-151

318-405

10-13

32-43

048 (60 Hz)
042 (50 Hz)

75

11.2

126-145

273-348

10-13

22-28

136-156

322-410

8-10

33-44

048 (60 Hz)
042 (50 Hz)

86

9.0

129-148

324-412

12-15

21-27

154-177

339-431

11-14

36-47

048 (60 Hz)
042 (50 Hz)

86

11.2

128-147

314-400

10-12

22-27

160-184

344-437

9-12

37-48

048 (60 Hz)
042 (50 Hz)

95

9.0

130-150

364-463

12-15

21-27

—

—

—

—

048 (60 Hz)
042 (50 Hz)

95

11.2

130-149

354-451

10-12

21-27

—

—

—

—

WSHP-SVX01N-EN

101

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEV*048
048 (60 Hz)
042 (50 Hz)

35

—

—

—

—

—

63-73

248-315

5-7

19-28

048 (60 Hz)
042 (50 Hz)

35

—

—

—

—

—

64-74

249-316

4-5

19-28

048 (60 Hz)
042 (50 Hz)

45

9.0

120-138

184-234

13-16

22-28

72-82

257-327

6-8

21-30

048 (60 Hz)
042 (50 Hz)

45

11.2

119-137

177-225

10-13

22-28

73-84

259-329

5-6

21-30

048 (60 Hz)
042 (50 Hz)

55

9.0

121-139

214-272

13-16

22-27

86-99

270-344

7-9

24-33

048 (60 Hz)
042 (50 Hz)

55

11.2

121-139

206-262

10-13

22-27

88-101

272-347

6-7

24-34

048 (60 Hz)
042 (50 Hz)

68

9.0

125-144

255-325

12-16

21-27

102-118

287-366

8-10

27-37

048 (60 Hz)
042 (50 Hz)

68

11.2

125-144

246-314

10-13

21-27

105-120

290-369

7-8

28-38

048 (60 Hz)
042 (50 Hz)

75

9.0

126-145

281-358

12-16

21-27

114-131

299-381

9-11

30-40

048 (60 Hz)
042 (50 Hz)

75

11.2

126-145

272-346

10-13

21-27

117-135

302-384

7-9

30-41

048 (60 Hz)
042 (50 Hz)

86

9.0

129-149

323-412

12-16

20-26

136-156

318-405

10-13

34-44

048 (60 Hz)
042 (50 Hz)

86

11.2

129-148

314-399

10-12

21-26

140-161

321-409

8-10

34-45

048 (60 Hz)
042 (50 Hz)

95

9.0

131-151

363-462

12-15

20-26

—

—

—

—

048 (60 Hz)
042 (50 Hz)

95

11.2

131-150

353-449

10-12

20-26

—

—

—

—

GEH*060
060(60 Hz)
048 (50 Hz)

35

—

—

—

—

—

69-79

265-337

6-7

20-30

060(60 Hz)
048 (50 Hz)

35

—

—

—

—

—

70-81

267-339

5-6

21-30

060(60 Hz)
048 (50 Hz)

45

11.2

111-128

176-225

13-16

21-26

79-91

274-348

6-8

23-32

060(60 Hz)
048 (50 Hz)

45

14.0

108-124

170-217

10-13

21-27

81-93

275-350

5-7

23-32

060(60 Hz)
048 (50 Hz)

55

11.2

113-129

205-261

12-16

20-26

95-109

290-369

7-9

26-36

060(60 Hz)
048 (50 Hz)

55

14.0

112-129

198-252

10-13

20-26

97-111

291-371

6-8

26-36

060(60 Hz)
048 (50 Hz)

68

11.2

117-135

243-309

12-16

20-26

115-132

311-396

9-11

30-40

060(60 Hz)
048 (50 Hz)

68

14.0

117-134

235-300

10-12

20-26

118-136

314-399

7-9

31-41

060(60 Hz)
048 (50 Hz)

75

11.2

118-136

268-342

12-15

20-25

128-147

324-412

10-12

33-43

060(60 Hz)
048 (50 Hz)

75

14.0

118-136

260-331

10-12

20-26

132-152

327-416

8-10

33-44

102

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*060
060(60 Hz)
048 (50 Hz)

86

11.2

121-139

309-393

12-15

19-25

151-174

347-442

11-14

37-48

060(60 Hz)
048 (50 Hz)

86

14.0

121-139

301-383

10-12

19-25

157-180

351-447

9-11

38-49

060(60 Hz)
048 (50 Hz)

95

11.2

123-141

348-442

12-15

19-25

—

—

—

—

060(60 Hz)
048 (50 Hz)

95

14.0

122-141

339-431

9-12

19-25

—

—

—

—

GEV*060
060(60 Hz)
048 (50 Hz)

35

—

—

—

—

—

70-81

261-332

6-7

20-30

060(60 Hz)
048 (50 Hz)

35

—

—

—

—

—

72-82

262-333

5-6

20-30

060(60 Hz)
048 (50 Hz)

45

11.2

115-133

178-227

13-16

21-27

80-92

269-342

6-8

23-32

060(60 Hz)
048 (50 Hz)

45

14.0

115-132

172-219

10-13

21-27

82-94

270-344

5-7

23-32

060(60 Hz)
048 (50 Hz)

55

11.2

117-134

207-264

12-16

20-26

95-110

284-362

7-10

26-36

060(60 Hz)
042 (50 Hz)

55

14.0

117-134

200-255

10-13

21-26

97-112

286-364

6-8

26-36

060(60 Hz)
048 (50 Hz)

68

11.2

122-140

248-315

12-16

20-26

116-134

304-387

9-11

31-41

060(60 Hz)
048 (50 Hz)

68

14.0

121-140

240-305

10-13

21-26

120-138

308-392

7-9

31-42

060(60 Hz)
048 (50 Hz)

75

11.2

123-141

273-347

12-16

20-26

129-149

318-404

10-12

33-44

060(60 Hz)
048 (50 Hz)

75

14.0

123-141

265-337

10-12

20-26

134-154

321-408

8-10

34-45

060(60 Hz)
048 (50 Hz)

86

11.2

125-144

313-399

12-15

20-25

153-176

341-434

11-14

38-49

060(60 Hz)
048 (50 Hz)

86

14.0

125-144

305-388

10-12

20-25

158-182

344-438

9-12

38-50

060(60 Hz)
048 (50 Hz)

95

11.2

127-146

352-447

12-15

19-25

—

—

—

—

060(60 Hz)
048 (50 Hz)

95

14.0

127-146

343-436

9-12

19-25

—

—

—

—

072 (60 Hz)

32

12

—

—

—

—

67 - 77

250 - 319

6-8

20 - 24

072 (60 Hz)

32

18

—

—

—

—

70 - 80

253 - 322

4-5

20 - 25

072 (60 Hz)

45

12

129 - 148

176 - 224

15 - 18

25 - 30

85 - 97

266 - 338

8 - 10

24 - 29

072 (60 Hz)

45

18

128 - 148

163 - 208

10 - 12

25 - 31

89 - 103

269 - 342

5-7

25 - 30

072 (60 Hz)

55

12

130 - 150

205 - 260

14 - 18

24 - 30

102 - 117

281 - 357

8 - 11

28 - 35

072 (60 Hz)

55

18

130 - 149

191 - 243

10 - 12

24 - 30

107 - 123

285 - 362

6-7

29 - 35

072 (60 Hz)

68

12

133 - 153

247 - 314

14 - 18

23 - 29

125 - 144

300 - 382

10 - 13

34 - 42

072 (60 Hz)

68

18

132 - 152

232 - 296

9 - 12

24 - 29

133 - 153

305 - 388

7-9

35 - 43

072 (60 Hz)

77

12

134 - 155

286 - 363

15 - 18

23 - 28

139 - 160

311 - 396

11 - 14

37 - 45

GEH*/GEV*

WSHP-SVX01N-EN

103

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

072 (60 Hz)

77

18

134 - 154

268 - 341

10 - 12

23 - 29

148 - 170

317 - 403

8 - 10

38 - 47

072 (60 Hz)

86

12

136 - 156

317 - 403

14 - 17

22 - 28

163 - 188

329 - 419

13 - 16

41 - 50

072 (60 Hz)

86

18

135 - 155

300 - 382

9 - 12

23 - 28

175 - 201

335 - 427

9 - 11

43 - 53

072 (60 Hz)

95

12

137 - 158

356 - 453

13 - 17

22 - 27

—

—

—

—

072 (60 Hz)

95

18

137 - 157

340 - 432

9 - 11

22 - 27

—

—

—

—

090 (60 Hz)
072 (50 Hz)

32

15

—

—

—

—

65 - 75

245 - 312

6-8

22 - 27

090 (60 Hz)
072 (50 Hz)

32

22.5

—

—

—

—

68 - 78

248 - 316

4-5

23 - 28

090 (60 Hz)
072 (50 Hz)

45

15

125 - 144

183 - 233

15 - 19

24 - 30

83 - 95

260 - 331

8 - 10

26 - 31

090 (60 Hz)
072 (50 Hz)

45

22.5

124 - 143

170 - 216

10 - 12

24 - 30

87 - 101

263 - 335

5-7

26 - 32

090 (60 Hz)
072 (50 Hz)

55

15

126 - 145

213 - 271

14 - 18

24 - 29

100 - 115

274 - 348

8 - 11

29 - 36

090 (60 Hz)
072 (50 Hz)

55

22.5

126 - 145

198 - 252

10 - 12

24 - 29

105 - 121

277 - 353

6-7

30 - 37

090 (60 Hz)
072 (50 Hz)

68

15

128 - 148

257 - 327

14 - 18

23 - 28

123 - 142

291 - 370

10 - 13

34 - 42

090 (60 Hz)
072 (50 Hz)

68

22.5

128 - 147

241 - 307

9 - 12

23 - 29

131 - 150

296 - 376

7-9

35 - 43

090 (60 Hz)
072 (50 Hz)

77

15

130 - 150

298 - 379

15 - 19

23 - 28

137 - 158

301 - 383

11 - 14

37 - 45

090 (60 Hz)
072 (50 Hz)

77

22.5

130 - 149

279 - 355

10 - 12

23 - 28

146 - 168

306 - 390

8 - 10

38 - 47

090 (60 Hz)
072 (50 Hz)

86

15

131 - 151

328 - 418

14 - 17

22 - 27

161 - 185

317 - 403

13 - 16

40 - 50

090 (60 Hz)
072 (50 Hz)

86

22.5

131 - 151

311 - 396

9 - 12

22 - 28

173 - 199

324 - 412

9 - 11

42 - 52

090 (60 Hz)
072 (50 Hz)

95

15

133 - 153

370 - 471

13 - 17

22 - 27

—

—

—

—

090 (60 Hz)
072 (50 Hz)

95

22.5

133 - 153

352 - 448

9 - 11

22 - 27

—

—

—

—

120 (60 Hz)
090 (50 Hz)

32

20

—

—

—

—

65 - 75

246 - 313

6-7

25 - 30

120 (60 Hz)
090 (50 Hz)

32

30

—

—

—

—

68 - 79

248 - 316

4-5

25 - 31

120 (60 Hz)
090 (50 Hz)

45

20

124 - 143

174 - 221

14 - 18

23 - 29

84 - 96

259 - 330

7-9

28 - 34

120 (60 Hz)
090 (50 Hz)

45

30

123 - 142

162 - 206

9 - 12

23 - 29

88 - 101

263 - 335

5-6

28 - 34

120 (60 Hz)
090 (50 Hz)

55

20

125 - 144

202 - 258

14 - 18

23 - 29

101 - 116

274 - 349

8 - 10

30 - 37

120 (60 Hz)
090 (50 Hz)

55

30

125 - 144

189 - 241

9 - 12

23 - 29

106 - 122

279 - 355

6-7

31 - 38

120 (60 Hz)
090 (50 Hz)

68

20

127 - 146

244 - 311

13 - 17

23 - 28

124 - 143

292 - 372

10 - 12

34 - 42

120 (60 Hz)
090 (50 Hz)

68

30

127 - 146

230 - 293

9 - 11

23 - 28

132 - 152

297 - 378

7-8

35 - 43

120 (60 Hz)
090 (50 Hz)

77

20

129 - 148

281 - 358

14 - 18

23 - 28

139 - 159

303 - 385

10 - 13

37 - 45

GEH*/GEV*

104

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*/GEV*
120 (60 Hz)
090 (50 Hz)

77

30

128 - 148

265 - 337

9 - 12

23 - 28

147 - 170

308 - 392

7-9

37 - 46

120 (60 Hz)
090 (50 Hz)

86

20

130 - 150

311 - 396

13 - 16

22 - 27

163 - 187

320 - 407

12 - 15

40 - 50

120 (60 Hz)
090 (50 Hz)

86

30

130 - 150

296 - 376

9 - 11

22 - 27

174 - 200

326 - 415

8 - 11

41 - 51

120 (60 Hz)
090 (50 Hz)

95

20

132 - 152

348 - 443

13 - 16

22 - 27

—

—

—

—

120 (60 Hz)
090 (50 Hz)

95

30

132 - 152

333 - 423

8 - 11

22 - 27

—

—

—

—

150 (60 Hz)
120 (50 Hz)

32

25

—

—

—

—

66 - 75

256 - 326

7-8

23 - 29

150 (60 Hz)
120 (50 Hz)

32

37.5

—

—

—

—

69 - 79

258 - 329

5-6

24 - 30

150 (60 Hz)
120 (50 Hz)

45

25

120 - 138

187 - 238

15 - 19

22 - 29

84 - 96

272 - 346

8 - 10

26 - 32

150 (60 Hz)
120 (50 Hz)

45

37.5

120 - 138

172 - 219

10 - 12

22 - 29

88 - 102

275 - 350

6-7

26 - 32

150 (60 Hz)
120 (50 Hz)

55

25

122 - 140

216 - 275

14 - 18

22 - 28

101 - 116

290 - 369

9 - 11

28 - 35

150 (60 Hz)
120 (50 Hz)

55

37.5

121 - 140

200 - 255

10 - 12

22 - 28

107 - 123

293 - 372

6-8

29 - 37

150 (60 Hz)
120 (50 Hz)

68

25

124 - 143

259 - 329

14 - 18

22 - 28

124 - 143

310 - 395

11 - 14

32 - 40

150 (60 Hz)
120 (50 Hz)

68

37.5

124 - 142

242 - 308

9 - 12

22 - 28

132 - 152

315 - 401

7-9

33 - 42

150 (60 Hz)
120 (50 Hz)

77

25

126 - 145

300 - 382

14 - 18

22 - 28

138 - 159

323 - 411

12 - 15

34 - 43

150 (60 Hz)
120 (50 Hz)

77

37.5

125 - 144

280 - 356

10 - 12

22 - 28

148 - 170

328 - 418

8 - 10

36 - 45

150 (60 Hz)
120 (50 Hz)

86

25

128 - 147

328 - 417

13 - 17

21 - 27

162 - 187

344 - 438

13 - 17

37 - 47

150 (60 Hz)
120 (50 Hz)

86

37.5

127 - 146

309 - 393

9 - 11

22 - 27

174 - 201

351 - 446

9 - 12

39 - 49

150 (60 Hz)
120 (50 Hz)

95

25

129 - 149

366 - 466

13 - 17

21 - 27

—

—

—

—

150 (60 Hz)
120 (50 Hz)

95

37.5

129 - 148

348 - 442

9 - 11

21 - 27

—

—

—

—

180 (60 Hz)
150 (50 Hz)

32

30

—

—

—

—

62 - 71

260 - 331

7-9

23 - 29

180 (60 Hz)
150 (50 Hz)

32

45

—

—

—

—

65 - 75

263 - 334

5-6

24 - 30

180 (60 Hz)
150 (50 Hz)

45

30

119 - 136

189 - 240

15 - 19

22 - 29

79 - 91

277 - 352

8 - 10

26 - 32

180 (60 Hz)
150 (50 Hz)

45

45

118 - 136

172 - 219

10 - 13

22 - 29

84 - 97

280 - 356

6-7

27 - 33

180 (60 Hz)
150 (50 Hz)

55

30

120 - 138

220 - 280

15 - 19

22 - 28

96 - 111

294 - 375

9 - 11

29 - 36

180 (60 Hz)
150 (50 Hz)

55

45

120 - 138

205 - 261

10 - 12

22 - 28

102 - 117

297 - 378

6-8

30 - 37

180 (60 Hz)
150 (50 Hz)

68

30

122 - 140

266 - 338

14 - 18

22 - 28

119 - 137

316 - 402

11 - 14

32 - 41

WSHP-SVX01N-EN

105

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*/GEV*
180 (60 Hz)
150 (50 Hz)

68

45

121 - 140

249 - 317

10 - 12

22 - 28

127 - 146

320 - 407

7-9

34 - 43

180 (60 Hz)
150 (50 Hz)

77

30

123 - 142

308 - 392

15 - 19

22 - 28

133 - 153

329 - 419

12 - 15

35 - 43

180 (60 Hz)
150 (50 Hz)

77

45

123 - 141

288 - 367

10 - 13

22 - 28

142 - 163

334 - 425

8 - 10

36 - 46

180 (60 Hz)
150 (50 Hz)

86

30

124 - 143

340 - 432

14 - 18

21 - 27

156 - 179

351 - 447

13 - 17

38 - 48

180 (60 Hz)
150 (50 Hz)

86

45

124 - 143

321 - 409

9 - 12

21 - 27

167 - 192

357 - 455

9 - 12

40 - 50

180 (60 Hz)
150 (50 Hz)

95

30

126 - 145

381 - 485

14 - 17

21 - 27

—

—

—

—

180 (60 Hz)
150 (50 Hz)

95

45

126 - 145

363 - 461

9 - 12

21 - 27

—

—

—

—

240 (60 Hz)
180 (50 Hz)

32

40

—

—

—

—

64 - 73

256 - 326

6-8

25 - 31

240 (60 Hz)
180 (50 Hz)

32

60

—

—

—

—

67 - 77

259 - 329

4-5

26 - 32

240 (60 Hz)
180 (50 Hz)

45

40

126 - 145

178 - 226

15 - 19

23 - 29

82 - 94

270 - 344

7-9

27 - 34

240 (60 Hz)
180 (50 Hz)

45

60

125 - 144

165 - 210

10 - 12

23 - 29

86 - 99

274 - 349

5-7

28 - 35

240 (60 Hz)
180 (50 Hz)

55

40

127 - 146

208 - 265

14 - 18

23 - 29

99 - 113

285 - 362

8 - 10

29 - 37

240 (60 Hz)
180 (50 Hz)

55

60

127 - 146

194 - 247

10 - 12

23 - 29

104 - 120

289 - 368

6-7

30 - 38

240 (60 Hz)
180 (50 Hz)

68

40

129 - 148

253 - 321

14 - 18

22 - 29

122 - 140

303 - 386

10 - 13

33 - 41

240 (60 Hz)
180 (50 Hz)

68

60

129 - 148

237 - 301

9 - 12

23 - 29

129 - 149

309 - 394

7-9

34 - 42

240 (60 Hz)
180 (50 Hz)

77

40

131 - 150

294 - 374

15 - 19

22 - 28

135 - 156

315 - 400

11 - 14

34 - 43

240 (60 Hz)
180 (50 Hz)

77

60

130 - 150

275 - 350

10 - 12

22 - 28

144 - 166

322 - 409

8 - 10

36 - 45

240 (60 Hz)
180 (50 Hz)

86

40

132 - 152

325 - 414

14 - 17

22 - 28

159 - 183

334 - 425

12 - 16

37 - 47

240 (60 Hz)
180 (50 Hz)

86

60

132 - 152

308 - 392

9 - 12

22 - 28

170 - 196

342 - 436

9 - 11

39 - 49

240 (60 Hz)
180 (50 Hz)

95

40

134 - 154

367 - 467

13 - 17

22 - 27

—

—

—

—

240 (60 Hz)
180 (50 Hz)

95

60

134 - 154

349 - 444

9 - 11

22 - 28

—

—

—

—

300 (60 Hz)
240 (50 Hz)

32

50

—

—

—

—

62 - 71

275 - 350

6-8

24 - 30

300 (60 Hz)
240 (50 Hz)

32

75

—

—

—

—

65 - 75

279 - 355

4-6

25 - 31

300 (60 Hz)
240 (50 Hz)

45

50

120 - 138

181 - 231

15 - 19

22 - 28

80 - 92

291 - 370

8 - 10

26 - 33

300 (60 Hz)
240 (50 Hz)

45

75

119 - 137

169 - 215

10 - 13

22 - 28

84 - 97

295 - 376

5-7

27 - 34

300 (60 Hz)
240 (50 Hz)

55

50

121 - 140

209 - 267

14 - 18

22 - 28

96 - 111

309 - 394

8 - 11

29 - 36

106

WSHP-SVX01N-EN

Start-Up
Table 54.

Operating pressures in cooling/heating for GE* units (continued)
Operating Data

Model No.

Entering
Water
Temp
(°F)

Water
Flow
(GPM)

Cooling

Heating

Suction Discharge
Water
Air Temp
Pressure Pressure Temp Rise
Drop
(psig)
(psig)
(°F)
(°F DB)

Suction Discharge
Water
Air Temp
Pressure Pressure
Temp
Rise
(psig)
(psig)
Drop (°F) (°F DB)

GEH*/GEV*
300 (60 Hz)
240 (50 Hz)

55

75

121 - 139

196 - 249

10 - 12

22 - 28

102 - 117

314 - 399

6-8

30 - 37

300 (60 Hz)
240 (50 Hz)

68

50

124 - 142

251 - 320

14 - 18

22 - 27

119 - 137

330 - 420

10 - 13

32 - 40

300 (60 Hz)
240 (50 Hz)

68

75

123 - 142

236 - 301

9 - 12

22 - 27

127 - 146

335 - 427

7-9

33 - 42

300 (60 Hz)
240 (50 Hz)

77

50

126 - 145

289 - 368

15 - 18

21 - 27

133 - 153

342 - 435

11 - 14

34 - 43

300 (60 Hz)
240 (50 Hz)

77

75

125 - 144

272 - 346

10 - 12

21 - 27

142 - 163

348 - 443

8 - 10

35 - 45

300 (60 Hz)
240 (50 Hz)

86

50

127 - 147

319 - 406

13 - 17

21 - 27

156 - 180

362 - 461

13 - 16

37 - 46

300 (60 Hz)
240 (50 Hz)

86

75

127 - 146

302 - 385

9 - 11

21 - 27

168 - 193

371 - 472

9 - 11

39 - 49

300 (60 Hz)
240 (50 Hz)

95

50

130 - 149

357 - 454

13 - 17

21 - 26

—

—

—

—

300 (60 Hz)
240 (50 Hz)

95

75

129 - 148

340 - 433

9 - 11

21 - 26

—

—

—

—

Table 55.

Operating pressures in cooling/heating for EX* units
Operating Data
Cooling

Model

EXH*006
(60 Hz)

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

1.4

35

1.7

—

—

—

45

1.4

143-165

190-243

13-16

45

1.7

143-164

184-235

11-13

55

1.4

145-167

217-277

55

1.7

144-166

68

1.4

148-171

68

1.7

75

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)
—

—

—

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)
94-108

279-355

6-8

23-29

—

96-110

281-357

5-6

23-29

24-30

110-127

297-377

7-9

26-34

24-31

113-130

300-382

6-8

27-34

13-16

23-30

128-147

317-404

8-10

30-39

210-268

11-13

24-30

131-151

320-407

7-9

31-39

254-324

12-15

23-29

154-177

345-439

10-12

35-45

147-170

244-312

10-13

23-29

158-182

349-444

8-10

36-45

1.4

148-171

281-358

12-15

23-29

169-195

361-459

10-13

38-48

75

1.7

148-170

273-348

10-13

23-29

175-201

366-466

9-11

38-48

86

1.4

149-172

328-418

12-15

22-28

197-226

388-494

11-15

41-52

86

1.7

149-172

320-407

10-13

23-29

203-234

395-502

10-12

41-52

95

1.4

151-173

373-474

12-15

22-28

—

—

—

—

95

1.7

150-173

363-462

10-13

22-28

—

—

—

—

35

1.7

—

—

—

—

93-107

272-346

6-7

20-26

WSHP-SVX01N-EN

—

Air temp
drop
(ºF DB)

107

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXH*009
(60 Hz)

EXH*012
(60 Hz)

EXH*015
(60 Hz)

108

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

2.1

—

—

—

—

95-110

274-348

5-6

21-27

45

1.7

142-164

187-238

13-16

22-28

109-126

288-366

7-9

24-30

45

2.1

142-164

181-230

11-14

22-27

112-129

291-370

6-7

24-31

55

1.7

144-166

214-272

12-15

21-27

127-146

305-388

8-10

27-34

55

2.1

144-166

207-263

10-13

21-27

130-150

309-393

7-8

27-35

68

1.7

146-168

258-328

12-15

20-26

153-176

330-420

9-12

31-39

68

2.1

146-168

250-318

10-12

21-26

157-181

335-427

8-10

32-40

75

1.7

147-169

286-363

12-15

20-25

168-193

345-439

10-13

33-42

75

2.1

147-169

277-352

9-12

20-26

174-200

350-446

8-11

34-43

86

1.7

149-171

336-427

12-15

19-25

195-224

370-471

11-14

36-46

86

2.1

148-171

326-415

9-12

20-25

202-232

375-477

9-12

37-47

95

1.7

149-172

386-491

12-15

19-24

—

—

—

—

95

2.1

149-172

375-477

9-12

19-24

—

—

—

—

35

2.2

—

—

—

—

92-106

288-367

10-13

21-27

35

2.8

—

—

—

—

95-109

290-370

8-11

21-27

45

2.2

142-163

183-233

12-15

22-28

108-125

304-387

12-15

24-30

45

2.8

142-163

175-223

9-12

23-29

111-128

307-391

9-12

24-31

55

2.2

143-164

212-270

12-15

21-27

126-145

322-410

13-16

26-33

55

2.8

143-164

204-260

9-12

22-27

130-149

325-413

10-13

27-34

68

2.2

144-166

257-327

12-15

21-26

152-174

346-441

14-18

29-37

68

2.8

144-166

248-316

9-12

21-26

157-180

352-448

11-15

29-37

75

2.2

145-167

284-361

12-15

20-26

167-192

361-460

15-19

30-38

75

2.8

145-167

274-349

9-12

20-26

173-199

366-466

12-15

30-39

86

2.2

146-168

332-422

12-15

19-25

194-223

384-489

16-21

32-40

86

2.8

146-168

321-409

9-12

20-25

201-231

390-497

13-17

32-41

95

2.2

147-170

376-478

12-15

19-24

—

—

—

—

95

2.8

147-170

365-465

9-12

19-24

—

—

—

—

35

2.8

—

—

—

—

91-105

296-377

6-7

20-25

35

3.5

—

—

—

—

93-107

299-380

5-6

20-26

45

2.8

138-159

180-230

11-14

22-28

107-123

313-398

7-8

23-29

45

3.5

138-158

174-221

9-11

22-27

109-126

316-402

5-7

23-30

55

2.8

139-159

210-267

11-14

21-27

124-143

332-423

8-10

26-33

55

3.5

138-159

203-258

9-11

21-27

128-147

336-427

6-8

27-34

68

2.8

140-161

254-324

11-14

20-26

150-172

358-456

9-11

30-38

68

3.5

140-161

246-313

9-11

21-26

154-178

364-463

7-9

30-39

75

2.8

141-162

281-358

11-14

20-25

165-190

373-475

10-12

32-40

75

3.5

140-162

272-347

9-11

20-26

171-196

379-483

8-10

32-41

86

2.8

142-163

328-417

11-14

19-25

191-220

399-508

11-14

34-43

86

3.5

142-163

318-405

9-11

20-25

198-228

405-515

9-11

34-44

95

2.8

143-165

371-472

11-14

19-24

—

—

—

—

95

3.5

143-165

361-459

9-11

19-24

—

—

—

—

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

WSHP-SVX01N-EN

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXH*018
(60 Hz)

EXH*024
(60 Hz)

EXH*030
(60 Hz)

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

3.3

—

—

—

—

91-104

282-357

6-7

21-26

35

4.2

—

—

—

—

93-107

285-360

5-6

21-27

45

3.3

143-164

158-206

12-15

23-29

106-122

306-385

7-9

24-30

45

4.2

142-164

151-197

9-12

23-29

109-125

309-388

5-7

24-31

55

3.3

142-164

186-242

12-15

23-29

123-141

323-407

8-10

27-34

55

4.2

143-164

179-233

9-12

23-29

127-146

326-411

6-8

27-35

68

3.3

143-164

226-294

12-15

22-28

148-171

357-447

9-12

31-39

68

4.2

142-164

218-283

9-12

22-28

153-176

361-452

8-10

32-40

75

3.3

143-164

252-326

12-15

21-27

164-188

370-464

10-13

33-42

75

4.2

143-164

243-315

9-12

21-27

169-195

375-470

8-10

34-43

86

3.3

143-165

295-382

12-15

20-26

191-219

389-488

11-14

36-46

86

4.2

143-165

286-370

9-12

20-26

198-228

392-492

9-11

37-47

95

3.3

144-166

336-433

12-15

19-24

—

—

—

—

95

4.2

144-166

326-421

9-12

19-25

—

—

—

—

35

4.4

—

—

—

—

84-97

276-348

5-7

21-27

35

5.6

—

—

—

—

86-99

278-350

4-5

22-28

45

4.4

134-154

164-214

12-15

23-30

99-114

296-372

6-8

25-32

45

5.6

132-152

157-205

9-12

23-30

101-116

298-375

5-6

26-32

55

4.4

134-154

191-249

12-15

22-28

115-132

311-391

7-9

29-36

55

5.6

134-154

184-239

9-12

22-29

118-136

314-395

6-7

29-37

68

4.4

135-156

231-300

12-15

21-27

139-160

342-428

9-11

33-42

68

5.6

135-155

224-290

9-12

22-28

143-165

346-433

7-9

33-42

75

4.4

136-157

256-331

12-15

21-27

153-176

355-444

9-12

35-44

75

5.6

136-156

248-321

9-12

21-27

159-182

360-450

8-10

35-45

86

4.4

137-158

298-385

11-14

20-26

178-205

376-471

11-13

37-47

86

5.6

137-158

289-374

9-11

20-26

185-213

380-476

9-11

38-48

95

4.4

139-160

336-434

11-14

19-25

—

—

—

—

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

95

5.6

138-159

328-422

9-11

20-25

—

—

—

—

35

5.5

—

—

—

—

88-102

269-342

5-7

20-25

35

7.0

—

—

—

—

91-105

271-344

4-6

20-26

45

5.5

138-159

164-214

12-15

22-28

104-120

287-364

7-8

23-29

45

7.0

140-161

157-205

10-12

22-27

107-123

290-367

5-7

23-30

55

5.5

142-164

191-249

12-15

21-27

121-139

303-384

8-10

26-33

55

7.0

142-163

184-240

9-12

21-27

125-144

307-388

6-8

27-34

68

5.5

144-165

230-299

12-15

20-26

146-168

333-420

9-11

30-38

68

7.0

143-165

222-289

9-12

21-26

151-174

337-426

7-9

30-39

75

5.5

144-166

255-331

12-15

20-25

161-185

347-438

10-13

32-40

75

7.0

143-165

248-322

9-12

20-26

167-192

352-444

8-10

32-41

86

5.5

146-168

297-384

11-15

19-25

187-215

368-465

11-14

34-43

86

7.0

145-167

288-373

9-11

20-25

194-223

374-473

9-11

34-44

95

5.5

147-169

336-434

11-14

19-24

—

—

—

—

95

7.0

146-169

327-423

9-11

19-24

—

—

—

—

WSHP-SVX01N-EN

109

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXH*036
(60 Hz)

EXH*042
(60 Hz)

EXH*048
(60 Hz)

110

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

6.6

—

—

—

—

88-102

289-364

6-7

19-24

35

8.4

—

—

—

—

90-104

291-366

5-6

19-24

45

6.6

135-156

168-217

12-15

21-26

103-119

307-386

7-8

23-29

45

8.4

135-155

161-209

9-12

21-26

106-122

309-388

5-7

23-29

55

6.6

136-157

196-252

12-15

20-26

120-139

324-408

8-10

26-33

55

8.4

136-157

189-244

9-12

21-26

124-143

327-411

6-8

26-34

68

6.6

138-159

234-302

12-15

20-25

145-167

359-450

9-12

30-39

68

8.4

138-159

226-292

9-12

20-26

150-173

363-454

7-9

31-39

75

6.6

140-161

259-333

11-15

20-25

160-184

373-468

10-13

33-42

75

8.4

139-160

251-323

9-11

20-26

166-191

377-472

8-10

33-42

86

6.6

141-163

300-386

11-14

20-25

185-213

398-499

11-14

35-45

86

8.4

141-162

292-375

9-11

20-26

193-222

402-505

9-12

36-45

95

6.6

143-164

338-434

11-14

20-25

—

—

—

—

95

8.4

143-164

329-423

9-11

20-26

—

—

—

—

35

7.8

—

—

—

—

86-99

281-353

6-7

22-27

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

35

9.8

—

—

—

—

88-101

282-354

4-6

22-28

45

7.8

138-159

161-212

12-15

21-27

101-116

297-372

7-8

25-31

45

9.8

138-159

155-204

10-12

21-27

103-119

299-375

5-7

25-32

55

7.8

139-160

190-249

12-15

21-27

117-135

312-392

8-10

28-35

55

9.8

139-160

183-240

10-12

21-27

120-139

314-395

6-8

29-35

68

7.8

140-161

230-300

12-15

21-26

142-163

348-434

9-11

32-40

68

9.8

140-161

222-290

9-12

21-26

146-168

351-438

7-9

33-41

75

7.8

141-162

255-332

12-15

20-26

156-180

361-450

10-12

35-43

75

9.8

141-162

247-322

9-12

20-26

161-186

365-456

8-10

35-44

86

7.8

143-164

298-387

11-14

19-25

181-209

384-480

11-14

37-46

86

9.8

142-164

290-376

9-12

19-25

188-216

388-485

9-11

37-47

95

7.8

144-166

337-437

11-14

19-24

—

—

—

—

95

9.8

144-165

329-426

9-11

19-24

—

—

—

—

35

8.8

—

—

—

—

88-101

287-362

6-7

20-25

35

11.2

—

—

—

—

90-103

289-364

5-6

20-26

45

8.8

136-156

173-224

12-15

21-27

103-118

303-382

7-9

23-29

45

11.2

136-156

167-215

10-12

22-28

106-122

305-385

5-7

23-30

55

8.8

137-158

202-261

12-15

21-27

120-138

319-402

8-10

26-33

55

11.2

137-158

195-251

9-12

21-27

123-142

323-407

6-8

27-34

68

8.8

139-160

245-315

12-15

20-26

145-166

353-443

9-12

30-38

68

11.2

139-160

237-305

9-12

21-26

150-172

357-448

7-9

31-39

75

8.8

140-161

270-347

12-15

20-25

159-183

367-461

10-13

32-40

75

11.2

140-161

262-337

9-12

20-26

165-190

371-466

8-10

32-41

86

8.8

142-163

312-401

11-14

19-25

185-213

392-492

11-14

33-42

86

11.2

142-163

303-390

9-11

19-25

192-221

398-500

9-12

34-43

95

8.8

144-165

351-451

11-14

19-24

—

—

—

—

95

11.2

143-165

342-440

9-11

19-24

—

—

—

—

WSHP-SVX01N-EN

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXH*060
(60 Hz)

EXH*070
(60 Hz)

EXV*006
(60 Hz)

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

11.6

—

—

—

—

88-102

314-395

6-7

21-27

35

14.0

—

—

—

—

90-103

315-397

5-6

21-27

45

11.6

130-150

171-221

12-15

21-27

103-119

340-426

7-8

24-31

45

14.0

130-150

166-214

10-13

21-26

106-122

341-428

6-7

24-31

55

11.6

132-152

199-256

12-15

20-26

121-139

360-452

8-10

27-35

55

14.0

132-151

193-249

10-12

21-26

123-142

364-457

6-8

28-35

68

11.6

134-154

237-306

11-15

20-26

146-168

398-499

9-12

31-40

68

14.0

134-154

231-298

9-12

20-26

150-172

402-503

8-10

32-40

75

11.6

135-155

262-337

11-14

20-25

161-185

416-521

10-12

33-42

75

14.0

135-155

256-330

9-12

20-26

165-190

421-528

8-11

34-43

86

11.6

137-157

304-391

11-14

20-25

186-214

449-564

11-14

36-45

86

14.0

137-157

298-383

9-12

20-25

192-221

454-570

9-12

36-46

95

11.6

138-159

342-440

11-14

19-24

—

—

—

—

95

14.0

138-159

335-431

9-11

19-25

—

—

—

—

35

12.3

—

—

—

—

85-98

296-373

6-7

20-25

35

15.4

—

—

—

—

87-100

298-375

5-6

20-26

45

12.3

132-151

167-216

12-16

22-28

100-115

322-403

7-8

23-29

45

15.4

132-151

161-209

10-12

22-28

103-118

324-406

5-7

23-30

55

12.3

132-152

195-252

12-15

21-27

117-134

341-427

8-10

26-33

55

15.4

132-152

188-244

10-12

21-27

120-138

343-431

6-8

26-34

68

12.3

134-154

235-304

12-15

21-27

141-162

374-468

9-12

30-39

68

15.4

134-154

228-294

10-12

21-27

145-167

378-473

8-10

31-39

75

12.3

135-155

259-335

12-15

21-26

155-179

390-488

10-13

33-42

75

15.4

135-155

252-325

9-12

21-26

160-185

395-494

8-10

34-43

86

12.3

136-157

297-384

12-15

20-26

180-207

418-524

11-15

37-47

86

15.4

136-157

289-374

9-12

20-26

186-215

423-530

9-12

38-48

95

12.3

138-159

334-431

11-15

20-25

—

—

—

—

95

15.4

138-159

326-421

9-12

20-25

—

—

—

—

35

1.4

—

—

—

—

94-108

279-355

6-8

23-29

35

1.7

—

—

—

—

96-110

281-357

5-6

23-29

45

1.4

143-165

190-243

13-16

24-30

110-127

297-377

7-9

26-34

45

1.7

143-164

184-235

11-13

24-31

113-130

300-382

6-8

27-34

55

1.4

145-167

217-277

13-16

23-30

128-147

317-404

8-10

30-39

55

1.7

144-166

210-268

11-13

24-30

131-151

320-407

7-9

31-39

68

1.4

148-171

254-324

12-15

23-29

154-177

345-439

10-12

35-45

68

1.7

147-170

244-312

10-13

23-29

158-182

349-444

8-10

36-45

75

1.4

148-171

281-358

12-15

23-29

169-195

361-459

10-13

38-48

75

1.7

148-170

273-348

10-13

23-29

175-201

366-466

9-11

38-48

86

1.4

149-172

328-418

12-15

22-28

197-226

388-494

11-15

41-52

86

1.7

149-172

320-407

10-13

23-29

203-234

395-502

10-12

41-52

95

1.4

151-173

373-474

12-15

22-28

—

—

—

—

95

1.7

150-173

363-462

10-13

22-28

—

—

—

—

WSHP-SVX01N-EN

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

111

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXV*009
(60 Hz)

EXV*012
60 Hz)

EXV*015
(60 Hz)

112

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

1.7

—

—

—

—

93-107

272-346

6-7

20-26

35

2.1

—

—

—

—

95-110

274-348

5-6

21-27

45

1.7

142-164

187-238

13-16

22-28

109-126

288-366

7-9

24-30

45

2.1

142-164

181-230

11-14

22-27

112-129

291-370

6-7

24-31

55

1.7

144-166

214-272

12-15

21-27

127-146

305-388

8-10

27-34

55

2.1

144-166

207-263

10-13

21-27

130-150

309-393

7-8

27-35

68

1.7

146-168

258-328

12-15

20-26

153-176

330-420

9-12

31-39

68

2.1

146-168

250-318

10-12

21-26

157-181

335-427

8-10

32-40

75

1.7

147-169

286-363

12-15

20-25

168-193

345-439

10-13

33-42

75

2.1

147-169

277-352

9-12

20-26

174-200

350-446

8-11

34-43

86

1.7

149-171

336-427

12-15

19-25

195-224

370-471

11-14

36-46

86

2.1

148-171

326-415

9-12

20-25

202-232

375-477

9-12

37-47

95

1.7

149-172

386-491

12-15

19-24

—

—

—

—

95

2.1

149-172

375-477

9-12

19-24

—

—

—

—

35

2.2

—

—

—

—

92-106

288-367

10-13

21-27

35

2.8

—

—

—

—

95-109

290-370

8-11

21-27

45

2.2

142-163

183-233

12-15

22-28

108-125

304-387

12-15

24-30

45

2.8

142-163

175-223

9-12

23-29

111-128

307-391

9-12

24-31

55

2.2

143-164

212-270

12-15

21-27

126-145

322-410

13-16

26-33

55

2.8

143-164

204-260

9-12

22-27

130-149

325-413

10-13

27-34

68

2.2

144-166

257-327

12-15

21-26

152-174

346-441

14-18

29-37

68

2.8

144-166

248-316

9-12

21-26

157-180

352-448

11-15

29-37

75

2.2

145-167

284-361

12-15

20-26

167-192

361-460

15-19

30-38

75

2.8

145-167

274-349

9-12

20-26

173-199

366-466

12-15

30-39

86

2.2

146-168

332-422

12-15

19-25

194-223

384-489

16-21

32-40

86

2.8

146-168

321-409

9-12

20-25

201-231

390-497

13-17

32-41

95

2.2

147-170

376-478

12-15

19-24

—

—

—

—

95

2.8

147-170

365-465

9-12

19-24

—

—

—

—

35

2.8

—

—

—

—

91-105

296-377

6-7

20-25

35

3.5

—

—

—

—

93-107

299-380

5-6

20-26

45

2.8

138-159

180-230

11-14

22-28

107-123

313-398

7-8

23-29

45

3.5

138-158

174-221

9-11

22-27

109-126

316-402

5-7

23-30

55

2.8

139-159

210-267

11-14

21-27

124-143

332-423

8-10

26-33

55

3.5

138-159

203-258

9-11

21-27

128-147

336-427

6-8

27-34

68

2.8

140-161

254-324

11-14

20-26

150-172

358-456

9-11

30-38

68

3.5

140-161

246-313

9-11

21-26

154-178

364-463

7-9

30-39

75

2.8

141-162

281-358

11-14

20-25

165-190

373-475

10-12

32-40

75

3.5

140-162

272-347

9-11

20-26

171-196

379-483

8-10

32-41

86

2.8

142-163

328-417

11-14

19-25

191-220

399-508

11-14

34-43

86

3.5

142-163

318-405

9-11

20-25

198-228

405-515

9-11

34-44

95

2.8

143-165

371-472

11-14

19-24

—

—

—

—

95

3.5

143-165

361-459

9-11

19-24

—

—

—

—

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

WSHP-SVX01N-EN

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXV*018
(60 Hz)

EXV*024
(60 Hz)

EXV*030
(60 Hz)

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

3.3

—

—

—

—

91-104

280-353

6-8

21-26

35

4.2

—

—

—

—

92-106

281-355

5-6

21-27

45

3.3

142-163

158-206

11-15

23-29

106-122

301-379

7-9

24-30

45

4.2

141-163

151-197

9-11

23-29

108-125

304-383

6-7

24-31

55

3.3

141-162

187-243

12-15

23-29

123-142

319-401

8-10

27-34

55

4.2

141-162

179-233

9-12

23-29

126-145

322-405

6-8

27-35

68

3.3

141-163

227-295

12-15

22-28

149-171

352-441

10-12

31-39

68

4.2

141-163

219-284

9-12

22-28

153-176

356-446

8-10

32-40

75

3.3

142-163

253-328

12-15

21-27

165-189

364-456

10-13

33-42

75

4.2

142-163

245-317

9-12

21-27

170-196

368-461

8-10

34-43

86

3.3

143-165

298-385

12-15

20-26

192-221

383-480

11-14

36-46

86

4.2

143-164

288-372

9-12

20-26

199-229

386-484

9-11

37-47

95

3.3

144-166

339-437

12-15

19-24

—

—

—

—

95

4.2

144-166

329-424

9-12

19-25

—

—

—

—

35

4.4

—

—

—

—

85-98

278-351

6-7

21-27

35

5.6

—

—

—

—

87-100

280-353

4-6

22-28

45

4.4

136-156

165-215

12-15

23-30

100-115

299-375

7-8

25-32

45

5.6

135-156

158-206

10-12

23-30

103-118

301-378

5-7

26-32

55

4.4

137-158

193-251

12-15

22-28

117-134

314-395

8-10

29-36

55

5.6

137-157

186-241

9-12

22-29

120-138

318-399

6-8

29-37

68

4.4

138-159

234-304

12-15

21-27

141-162

346-433

9-11

33-42

68

5.6

138-159

226-293

9-12

22-28

145-167

350-438

7-9

33-42

75

4.4

139-160

260-336

12-15

21-27

155-179

358-449

10-12

35-44

75

5.6

139-160

251-325

9-12

21-27

161-185

363-454

8-10

35-45

86

4.4

141-162

303-391

12-15

20-26

180-207

380-476

11-14

37-47

86

5.6

141-162

294-379

9-12

20-26

187-215

385-482

9-11

38-48

95

4.4

142-164

343-442

11-15

19-25

—

—

—

—

95

5.6

142-163

334-430

9-11

20-25

—

—

—

—

35

5.5

—

—

—

—

87-101

266-337

6-7

20-25

35

7.0

—

—

—

—

89-103

267-340

4-6

20-26

45

5.5

137-158

164-214

12-15

22-28

102-118

284-359

7-8

23-29

45

7.0

137-157

158-206

9-12

22-27

105-121

286-362

5-7

23-30

55

5.5

138-159

192-250

12-15

21-27

119-137

299-379

8-10

26-33

55

7.0

138-159

185-241

9-12

21-27

122-141

302-382

6-8

27-34

68

5.5

140-161

231-301

11-15

20-26

143-165

328-413

9-12

30-38

68

7.0

140-161

223-291

9-11

21-26

148-170

332-419

7-9

30-39

75

5.5

141-162

257-334

11-14

20-25

158-182

341-430

10-13

32-40

75

7.0

141-162

249-323

9-11

20-26

164-188

346-436

8-10

32-41

86

5.5

143-164

300-388

11-14

19-25

183-211

364-460

11-14

34-43

86

7.0

142-164

291-377

9-11

20-25

190-219

368-465

9-11

34-44

95

5.5

144-165

340-440

11-14

19-24

—

—

—

—

95

7.0

144-165

331-428

9-11

19-24

—

—

—

—

WSHP-SVX01N-EN

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

113

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXV*036
(60 Hz)

EXV*042
(60 Hz)

EXV*048
(60 Hz)

114

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

6.6

—

—

—

—

88-101

292-368

6-7

19-24

35

8.4

—

—

—

—

89-103

293-369

5-6

19-24

45

6.6

133-153

169-218

12-15

20-26

103-118

310-390

7-8

23-29

45

8.4

132-152

162-210

9-12

21-26

105-121

311-392

5-7

23-29

55

6.6

134-154

197-254

12-15

20-26

119-137

327-412

8-10

26-33

55

8.4

134-154

190-245

9-12

20-26

122-141

330-415

6-8

26-34

68

6.6

136-156

236-304

12-15

20-25

144-166

362-454

9-12

30-39

68

8.4

136-156

228-295

9-12

20-25

148-171

365-457

7-9

31-39

75

6.6

137-158

261-336

11-14

20-25

159-183

378-474

10-13

33-42

75

8.4

137-158

253-326

9-11

20-25

164-189

382-479

8-10

33-42

86

6.6

139-160

303-390

11-14

19-24

184-212

403-506

11-15

35-45

86

8.4

139-160

295-379

9-11

19-24

191-219

409-514

9-12

36-45

95

6.6

141-162

342-439

11-14

19-24

—

—

—

—

95

8.4

141-162

333-428

9-11

19-24

—

—

—

—

35

7.8

—

—

—

—

84-97

285-358

5-7

19-24

35

9.8

—

—

—

—

86-99

286-359

4-6

19-25

45

7.8

134-155

160-210

12-15

21-27

99-114

300-377

6-8

22-28

45

9.8

134-154

153-202

10-12

21-27

101-116

302-379

5-7

22-29

55

7.8

135-156

189-247

12-15

21-27

115-132

315-396

7-9

25-32

55

9.8

135-156

182-238

9-12

21-27

118-136

319-400

6-8

26-32

68

7.8

137-158

229-299

12-15

21-26

139-160

352-438

9-11

29-37

68

9.8

137-158

221-289

9-12

21-26

143-165

354-442

7-9

30-38

75

7.8

138-159

255-332

12-15

20-26

154-177

365-456

10-12

32-40

75

9.8

138-159

247-322

9-12

20-26

158-182

369-460

8-10

32-41

86

7.8

140-161

299-389

11-15

19-25

179-205

388-485

11-14

34-43

86

9.8

140-161

291-379

9-12

19-25

184-212

392-490

9-11

34-44

95

7.8

142-163

341-442

11-14

19-24

—

—

—

—

95

9.8

142-163

332-430

9-11

19-24

—

—

—

—

35

8.8

—

—

—

—

87-101

285-359

6-7

20-25

35

11.2

—

—

—

—

90-103

287-362

5-6

20-26

45

8.8

135-156

172-222

12-15

21-27

103-118

300-378

7-8

23-29

45

11.2

135-155

165-214

9-12

22-28

105-121

303-382

5-7

23-30

55

8.8

136-157

201-259

12-15

21-27

120-138

316-398

8-10

26-33

55

11.2

136-157

193-249

9-12

21-27

123-142

320-403

6-8

27-34

68

8.8

138-159

243-313

12-15

20-26

144-166

348-437

9-12

30-38

68

11.2

138-159

235-303

9-12

21-26

149-171

352-442

7-9

31-39

75

8.8

139-160

269-345

11-15

20-25

159-183

363-455

10-13

32-40

75

11.2

139-160

260-334

9-11

20-26

165-189

367-461

8-10

32-41

86

8.8

141-162

310-399

11-14

19-25

184-212

386-485

11-14

33-42

86

11.2

141-162

301-387

9-11

19-25

191-220

392-493

9-12

34-43

95

8.8

143-164

349-448

11-14

19-24

—

—

—

—

95

11.2

143-164

340-437

9-11

19-24

—

—

—

—

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

WSHP-SVX01N-EN

Start-Up
Table 55.

Operating pressures in cooling/heating for EX* units (continued)
Operating Data
Cooling

Model

EXV*060
(60 Hz)

EXV*070
(60 Hz)

Heating

Entering
water
temp (ºF)

Water
flow
(GPM)

35

11.6

—

—

—

—

89-102

300-377

6-7

21-27

35

14.0

—

—

—

—

90-104

301-379

5-6

21-27

45

11.6

132-152

169-219

12-15

21-27

104-120

324-406

7-9

24-31

45

14.0

132-152

164-212

10-13

21-26

106-122

325-407

6-7

24-31

55

11.6

133-153

197-254

12-15

20-26

121-139

343-430

8-10

27-35

55

14.0

133-153

192-247

10-12

21-26

124-142

344-432

7-8

28-35

68

11.6

135-156

235-303

12-15

20-26

146-168

377-472

9-12

31-40

68

14.0

135-156

229-296

10-12

20-26

150-172

380-476

8-10

32-40

75

11.6

136-157

260-335

11-14

20-25

161-185

394-493

10-13

33-42

75

14.0

136-157

253-326

9-12

20-26

165-190

398-499

9-11

34-43

86

11.6

138-159

302-388

11-14

20-25

186-214

424-532

12-15

36-45

86

14.0

138-159

295-379

9-12

20-25

192-221

429-538

10-12

36-46

95

11.6

140-161

339-436

11-14

19-24

—

—

—

—

95

14.0

140-161

332-427

9-12

19-25

—

—

—

—

35

12.32

—

—

—

—

86-100

294-371

6-7

20-26

Suction Discharge
Water
pressure pressure temp rise
(psig)
(psig)
(ºF)

Air temp
drop
(ºF DB)

Suction Discharge
Water
Air temp
pressure pressure Temp drop
rise
(psig)
(psig)
(ºF)
(ºF DB)

35

15.4

—

—

—

—

88-102

296-373

5-6

21-26

45

12.32

131-150

166-216

12-15

21-27

101-117

320-401

7-9

23-29

45

15.4

131-150

160-208

10-12

21-27

104-119

322-404

6-7

24-30

55

12.32

131-151

194-252

12-15

21-27

118-136

338-424

8-10

26-33

55

15.4

131-151

188-243

10-12

21-27

121-139

340-427

6-8

27-34

68

12.32

133-153

235-303

12-15

20-26

142-164

374-467

9-12

31-39

68

15.4

133-153

228-294

9-12

21-26

146-168

376-470

8-10

31-40

75

12.32

134-154

259-335

12-15

20-26

157-180

389-487

10-13

33-42

75

15.4

134-154

252-325

9-12

20-26

162-186

393-492

8-11

34-43

86

12.32

136-156

297-384

11-15

20-25

181-209

417-523

12-15

37-47

86

15.4

136-156

289-374

9-12

20-25

188-216

422-529

9-12

38-48

95

12.32

137-158

335-432

11-14

19-25

—

—

—

—

95

15.4

137-158

327-422

9-12

19-25

—

—

—

—

Water Pressure Drop

Table 56.

Cooling water pressure drops (WPD) in feet of
head for GE* units - ½- 6 ton (continued)

Table 56, p. 115 should be used to define feet of head/
pressure drop. Please note the feet of pressure (ft/head)
provided is at ARI/ISO standard.

Unit Size
(60 Hz)

Unit Size
(50 Hz)

EWT °F

GPM

Ft.
Pressure

To calculate feet of head, when using gauges that read in
PSIG, multiply PSI by 2.31.

GEH024

GEH018

86

5.6

13.2

GEH030

GEH024

86

7.0

11.1

GEH036

GEH030

86

8.4

11.5

GEH042

GEH036

86

9.8

13.6

Table 56.

Cooling water pressure drops (WPD) in feet of
head for GE* units - ½- 6 ton

GEH048

GEH042

86

11.2

6.8

GEH060

GEH048

86

14.0

12.3

GPM

Ft.
Pressure

—

GEH060

86

14.0

11.4

1.8

3.9

GEH072

—

86

18.0

12.0

86

2.1

3.7

GEH090

GEH072

86

22.5

13.8

GEH009

86

2.8

3.8

GEH120

GEH090

86

30.0

14.1

GEH015

GEH012

86

3.5

5.4

GEH150

GEH120

86

37.5

13.4

GEH018

GEH015

86

4.2

6.8

GEH180

GEH150

86

45.0

18.2

Unit Size
(60 Hz)

Unit Size
(50 Hz)

EWT °F

GEH006

—

86

GEH009

GEH006

GEH012

WSHP-SVX01N-EN

115

Start-Up
Table 56.
Unit Size
(60 Hz)

Cooling water pressure drops (WPD) in feet of
head for GE* units - ½- 6 ton (continued)

Table 57.

Cooling water pressure drops (WPD) in feet of
head for EX* units (continued)

Unit Size
(50 Hz)

EWT °F

GPM

Ft.
Pressure

Unit Size
(60 Hz)

Unit Size
(50 Hz)

EWT °F

GPM

Ft.
Pressure

GEV006

—

86

1.8

3.0

EXV060

—

86

14

7.4

GEV009

GEV006

86

2.1

3.9

EXV070

—

86

15.4

6.6

GEV012

GEV009

86

2.8

3.8

GEV015

GEV012

86

3.5

5.3

GEV018

GEV015

86

4.2

6.3

GEV024

GEV018

86

5.6

12.9

GEV030

GEV024

86

7.0

12.2

GEV036

GEV030

86

8.4

12.5

GEV042

GEV036

86

9.8

14.5

GEV048

GEV042

86

11.2

5.7

GEV060

GEV048

86

14.0

12.0

—

GEV060

86

14.0

10.8

GEV072

—

86

18.0

12.0

GEV090

GEV072

86

22.5

13.4

GEV120

GEV090

86

30.0

14.1

GEV150

GEV120

86

37.5

13.4

GEV180

GEV150

86

45.0

18.2

GEV240
GEV300

Table 57.
Unit Size
(60 Hz)
EXH006
EXH009

GEV180
GEV240

86
86

60.0
75.0

14.0
13.2

—
—

EWT °F
86
86

GPM
1.8
2.1

Unit Size
(60 Hz)

Heating water pressure drops (WPD) in feet of
head for GE* units
Unit Size
(50 Hz)

EWT °F

GPM

Ft.
Pressure

GEH006

—

68

1.8

4.2

GEH009

GEH006

68

2.1

3.9

GEH012

GEH009

68

2.8

4.1

GEH015

GEH012

68

3.5

5.7

GEH018

GEH015

68

4.2

7.2

GEH024

GEH018

68

5.6

14

GEH030

GEH024

68

7.0

11.8

GEH036

GEH030

68

8.4

12.1

GEH042

GEH036

68

9.8

14.5

GEH048

GEH042

68

11.2

7.2

GEH060

GEH048

68

14.0

13.1

—

GEH060

68

14.0

12.1

GEH072

—

68

18.0

13.9

GEH090

GEH072

68

22.5

15.7

GEH120

GEH090

68

30.0

16.0

GEH150

GEH120

68

37.5

14.8

3.9

GEH180

GEH150

68

45.0

20.3

3.7

GEV006

—

68

1.8

3.2

GEV006

68

2.1

4.2

Cooling water pressure drops (WPD) in feet of
head for EX* units
Unit Size
(50 Hz)

Table 58.

Ft.
Pressure

EXH012

—

86

2.8

3.8

GEV009

EXH015

—

86

3.5

5.4

GEV012

GEV009

68

2.8

4.1

4.1

GEV015

GEV012

68

3.5

5.6

6.1

GEV018

GEV015

68

4.2

6.7

GEV018

68

5.6

13.7

EXH018
EXH024

—
—

86
86

4.2
5.6

EXH030

—

86

7

9.2

GEV024

EXH036

—

86

8.4

5.5

GEV030

GEV024

68

7.0

12.9

GEV030

68

8.4

13.2

EXH042

—

86

9.8

7.8

GEV036

EXH048

—

86

11.2

8.2

GEV042

GEV036

68

9.8

15.4

GEV042

68

11.2

6.1
12.7

EXH060

—

86

14

7.2

GEV048

EXH070

—

86

15.4

6.3

GEV060

GEV048

68

14.0

3.0

—

GEV060

68

14.0

11.5

—

68

18.0

13.9

EXV006

—

86

1.8

EXV009

—

86

2.1

3.9

GEV072

EXV012

—

86

2.8

3.8

GEV090

GEV072

68

22.5

15.3

EXV015

—

86

3.5

5.3

GEV120

GEV090

68

30.0

16.0

3.7

GEV150

GEV120

68

37.5

14.8

6.5

GEV180

GEV150

68

45.0

20.3

GEV180

68

60.0

16.0

GEV240

68

75.0

14.8

EXV018
EXV024

—
—

86
86

4.2
5.6

EXV030

—

86

7

8.5

GEV240

EXV036

—

86

8.4

6.3

GEV300

EXV042

—

86

9.8

8.5

EXV048

—

86

11.2

7.9

116

WSHP-SVX01N-EN

Start-Up
Table 59.

Heating water pressure drops (WPD) in feet of
head for EX* units

Unit Size
(60 Hz)

Unit Size
(50 Hz)

EWT °F

GPM

Ft.
Pressure

EXH006

—

68

1.8

4.2

EXH009

—

68

2.1

3.9

EXH012

—

68

2.8

4.1

EXH015

—

68

3.5

5.7

EXH018

—

68

4.2

5.0

EXH024

—

68

5.6

7.9

EXH030

—

68

7.0

11.2

EXH036

—

68

8.4

6.5

EXH042

—

68

9.8

9.4

EXH048

—

68

11.2

9.4

EXH060

—

68

14.0

7.1

EXH070

—

68

15.4

7.2

EXV006

—

68

1.8

4.2

EXV009

—

68

2.1

3.9

EXV012

—

68

2.8

4.1

EXV015

—

68

3.5

5.7

EXV018

—

68

4.2

4.5

EXV024

—

68

5.6

8.2

EXV030

—

68

7.0

10.2

EXV036

—

68

8.4

7.5

EXV042

—

68

9.8

9.8

EXV048

—

68

11.2

9.1

EXV060

—

68

14.0

7.2

EXV070

—

68

15.4

7.6

Water Volume
Table 60, p. 117 is provided for use in calculating glycol
requirements for the unit.
Table 60.

Water volume for GE* units
Water Side Water Side Water Side
Volume
Volume
Volume
(ft3)
(gallons)
(in3)

Unit Size
(60 Hz)

Unit Size
(50 Hz)

006

—

13.6

0.008

0.059

009

006

13.6

0.008

0.059

012

009

28.2

0.016

0.122

015

012

36.0

0.021

0.156

018

015

28.2

0.016

0.122

024

018

37.8

0.022

0.164

030

024

49.1

0.028

0.213

036

030

70.4

0.041

0.305

042

036

79.0

0.046

0.342

048

042

71.7

0.041

0.310

060

048

91.8

0.053

0.397

—

060

91.8

0.053

0.397

072

—

181

0.105

0.783

WSHP-SVX01N-EN

Table 60.

Water volume for GE* units (continued)
Water Side Water Side Water Side
Volume
Volume
Volume
(ft3)
(gallons)
(in3)

Unit Size
(60 Hz)

Unit Size
(50 Hz)

090

072

214

0.125

0.927

120

090

390

0.227

1.690

150, 180

120, 150

508

0.296

2.201

240

180

779

0.453

3.374

300

240

1057

0.615

4.576

Table 61. Water volume for EX* units
Water Side Water Side Water Side
Volume
Volume
Volume
(ft3)
(gallons)
(in3)

Unit Size
(60 Hz)

Unit Size
(50 Hz)

EXH006

—

13.6

0.008

0.059

EXH009

—

13.6

0.008

0.059

EXH012

—

28.4

0.016

0.123

EXH015

—

36.0

0.021

0.156

EXH018

—

89.8

0.052

0.389

EXH024

—

89.8

0.052

0.389

EXH030

—

89.8

0.052

0.389

EXH036

—

171.2

0.099

0.741

EXH042

—

200.8

0.116

0.869

EXH048

—

200.8

0.116

0.869

EXH060

—

331.2

0.192

1.434

EXH070

—

331.2

0.192

1.434

EXV006

—

13.6

0.008

0.059

EXV009

—

13.6

0.008

0.059

EXV012

—

28.4

0.016

0.123

EXV015

—

36.0

0.021

0.156

EXV018

—

89.8

0.052

0.389

EXV024

—

89.8

0.052

0.389

EXV030

—

89.8

0.052

0.389

EXV036

—

171.2

0.099

0.741

EXV042

—

200.8

0.116

0.869

EXV048

—

200.8

0.116

0.869

EXV060

—

331.2

0.192

1.434

EXV070

—

331.2

0.192

1.434

117

Maintenance
WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. When possible, disconnect all electrical
power including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. When
necessary to work with live electrical components, have
a qualified licensed electrician or other individual who
has been trained in handling live electrical components
per these tasks. Failure to follow all of the
recommended safety warnings provided, could result in
death or serious injury.

Preventive Maintenance
Maintenance on the unit is simplified with the following
preventive suggestions:
Filter maintenance must be performed to assure proper
operation of the equipment. Filters should be inspected at
least every three months, and replaced when it is evident
they are dirty. Filter sizing is shown in Table 62, p. 118:
Table 62.

Filter sizing

Size (60 Hz)

Filter Size (Actual)
inches (mm)

Size (50 Hz)
GEH

006-015

006-012

14 5/8 x 20 1/4 (371 x 514)

A strainer (60 mesh or greater) must be used on an open
loop system to keep debris from entering the unit heat
exchanger and to ensure a clean system.
For units on well water, it is important to check the
cleanliness of the water-to-refrigerant heat exchanger.
Should it become contaminated with dirt and scaling as a
result of bad water, the heat exchanger will have to be back
flushed and cleaned with a chemical that will remove the
scale.This service should be performed by an experienced
service person.

WARNING
Hazardous Chemicals!
Cleaning agents can be either acidic or highly alkaline.
Handle chemical carefully. Proper handling should
include goggles or face shield, chemical resistant
gloves, boots, apron or suit as required. For personal
safety, refer to the cleaning agent manufacturers
Materials Safety Data Sheet and follow all
recommended safe handling practices. Failure to follow
all safety instructions could result in death or serious
injury.
It should be noted that the water quality should be checked
periodically. See Table 63, p. 118.
Table 63.

Water quality
Scaling

Amount
Less than 350 ppm

018-030

015-024

17 7/8 x 23 7/8 (454 x 607)

Calcium and magnesium (total hardness)

036-042

030-036

18 5/8 x 25 3/8 (473 x 645)

Corrosion

048-060

042-060

20 5/8 x 29 3/4 (524 x 755)

pH

7-9.5

072-120

072-090

20 x 25 (3) (508 x 508)

Hydrogen Sulfide

Less than 1 ppm

150-180

120-150

25 x 25 (3) (635 x 635)

GEV
006-015

006-012

15 7/8 x 19 7/8 (403 x 504)

018-030

015-024

19 7/8 x 19 7/8 (505 x 505)

036-042

030-036

19 7/8 x 24 7/8 (504 x 632)

048-060

042-060

23 7/8 x 29 7/8 (606 x 759)

GEV 072-120

090

20 x 20 (4) (508 x 508)

150-300

120-240

19 5/8 x 24 5/8 (6) (498 x 625)‘

Sulfates

Less than 25 ppm

Chlorides

Less than 125 ppm

Carbon Dioxide

Less than 75 ppm

Total dissolved solids (TDS)

Less than 1000 ppm

Biological Growth
Iron Bacteria

006-015

—

14 5/8 x 20 1/4 (371 x 514)

018-024

—

17 7/8 X 23 7/8 (454 X 607)

030-036

—

18 5/8 x 25 3/8 (473 x 645)

042-070

—

20 5/8 x 29 3/4 (524 x 755)

006-015

—

15 7/8 x 19 7/8 (403 x 504)

018-024

—

19 7/8 x 19 7/8 (505 x 505)

030-036

—

19 7/8 x 24 7/8 (504 x 632)

042-060

—

23 7/8 x 29 7/8 (606 x 759)

070

—

27 7/8 x 29 7/8 (708 x 759)

EXV

Low

Erosion
Suspended Solids

EXH

118

Check the contactors and relays within the control panel at
least once a year. It is good practice to check the tightness
of the various wiring connections within the control panel.

Low

Condensate Trap
For units incorporating a negative trap design, ensure that
the condensate system is primed with water at all times.
Allowing a negative, pressure condensate system to run
dry could cause a break in the condensate seal allowing
the fan to draw water from the condensate line to spray
moisture into the mechanical system. By maintaining a
primed condensate trap, a seal will be created and will
help prevent these complications.
WSHP-SVX01N-EN

Troubleshooting
Deluxe Controls

WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. When possible, disconnect all electrical
power including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. When
necessary to work with live electrical components, have
a qualified licensed electrician or other individual who
has been trained in handling live electrical components
per these tasks. Failure to follow all of the
recommended safety warnings provided, could result in
death or serious injury.
Table 64.

Troubleshooting units which contain the deluxe control
option may be made easy by using the three LEDs (light
emitting diodes).These LEDs are provided for indicating
the operating mode of the controller.The LEDs are
intended to aid in troubleshooting.The LEDs are labeled
on the circuit board with numbers as referenced in
Table 64, p. 119.

Diagnostic LEDs

Color: Green
LED1

Color: Red
LED2

Controller
Mode

LED3

OFF

OFF

OFF

Control OFF

ON

OFF

OFF

Normal/Compressor OFF

ON

OFF

FLASH

Anti-short cycle

ON

OFF

ON

Normal/Compressor ON

FLASH

ON

OFF

Brownout Condition

ON

FLASH

ON

Soft Lockout (low pressure)

ON

FLASH

FLASH

Soft Lockout (high pressure)

ON

ON

ON

Manual Lockout (low pressure)

ON

ON

FLASH

Manual Lockout (high pressure)

ON

FLASH

OFF

Manual Lockout (condensate overflow)

ON

ON

OFF

Compressor Disable

Table 65.

Troubleshooting table

Problem
No response to any
thermostat setting

Unit short cycles
Blower runs, but compressor
does not

WSHP-SVX01N-EN

Heating Cooling

Cause

Correction

X

X

Main power off

Check fuses

X

X

Defective control transformer

Replace

X

X

Broken or loose connection

Repair

X

X

Defective thermostat

Replace

X

X

Transformer

Reset Transformer

X

X

Thermostat or sensor improperly located

Relocate

X

X

Defective compressor overload

Replace (if external)

X

X

Defective compressor contactor

Replace

X

X

Supply Voltage too low

Correct

X

X

Defective compressor capacitor

Replace

X

X

Defective windings

Replace

X

X

Limit switches open

Check cause/Replace or repair

119

Troubleshooting
Table 65.

Troubleshooting table (continued)

Problem
Insufficient capacity

Heating Cooling

Cause

Correction

Dirty filter

Replace/clean

X

Blower RPM too low

Correct

X

Loss of conditioned air due to leaks in
ductwork

Repair leaks

X

X

X
X

X
X

Low on refrigerant charge

X

X

Restricted thermal expansion valve

Replace

X

X

Defective reversing valve

See WSHP-IOM-# for touch test chart

X

X

Thermostat improperly located

Relocate

X

X

Unit undersized

Recalculate heat gains/losses

X

X

Inadequate water flow

Increase GPM

X

X

Scaling in heat exchanger

Clean or replace

Water too hot

Decrease temperature

Water too cold

Increase temperature

X

X

Filter drier blocked

Replace

X

X

Defective reversing valve

Check or replace

X

Inadequate GPM

Increase water flow to unit

X

Water too hot

Decrease temperature

Inadequate air flow

Check, clean blower and coil

High pressure switch open
X
X

Dirty filter

Clean/replace

X

X

Overcharged with refrigerant

Decrease charge

X

X

Defective pressure switch

Check or replace

X

Trash in heat exchanger

Backflush

X

Low water flow

Increase GPM

High head pressure
X

X

Overcharge of refrigerant

Decrease charge

X

X

Non-condensable in system

Evacuate and recharge by weight

X

X

Water too hot

Decrease temperature

X

Dirty filter

Clean / replace

X

Inadequate air flow

Check, clean blower and coil
Locate leak, repair and recharge

X

X

Undercharged

X

X

Restricted thermal expansion valve

Repair / replace

X

Inadequate air flow

Check, clean blower and coil

X

120

Locate leak, repair and recharge by
weight (not by superheat)

X

X

Low pressure switch open

Correct
Correct

X

X

Low suction pressure

Introduction of excessively hot return-air
Introduction of excessively cold return-air

Dirty filter

Clean/replace

X

Inadequate GPM

Increase GPM

X

Inadequate GPM

Increase GPM

X

Water too cold

Increase temperature

X

Inadequate air flow

Increase CFM

X

Dirty filter

Clean/replace
Increase charge

X

X

Undercharged with refrigerant

X

X

Defective pressure switch

Replace

X

X

Heat transfer fluid too cold

Raise water temperature

WSHP-SVX01N-EN

Wiring Diagrams
This section contains wiring diagrams (Figure 81, p. 121–
Figure 87, p. 127) and isolation valve wiring connections
(Table 66, p. 121).

Table 66.
Control
type
Basic 24V

Figure 81.

Isolation valve wiring
3-wire Honeywell isolation valve connections
Blue

Brown

Black

1TB1-6

1TB1-1

1TB1-4

Deluxe 24V

1TB1-6

1TB1-1

1TB1-4

ZN524

1TB1-18

1TB2-3

1TB1-16

GEH_V (½-5 tons) - basic-208V - 60 Hz - 1 ph(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

WSHP-SVX01N-EN

121

Wiring Diagrams
Figure 82. GEH_V (½-5 tons) - basic 24V - 460V-60 Hz - 3 ph(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

122

WSHP-SVX01N-EN

Wiring Diagrams
Figure 83. GEH_V (6-25 tons) - deluxe-380-420V - 50 Hz - 3 ph(a)

1U2

1U1

ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE
WHEN CONTROL 1U1 AND 1U2 GOES INTO MANUAL LOCKOUT MODE.
CONTACTS RATED FOR CLASS 2 24V. TERMINAL 1TB2-9 AND 10.
VERIFY TEST JUMPER HAS BEEN REMOVED TO PREVENT
CONTROL TIMING ERRORS.
CONNECTION FOR 24VAC CLASS 2 COMPRESSOR DISABLE
INPUT. TERMINAL 1TB2-7 AND 1TB2-8

CONNECT TERMINAL 11 TO 1TB2-1&2 AND TERMINAL 10 TO 1TB2-3&4
IF USING ZONE SENSOR X13790886010.

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

WSHP-SVX01N-EN

123

Wiring Diagrams
Figure 84. GEH_V (6-25 tons) - deluxe 24V - 460V-60 Hz - 3 ph(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

124

WSHP-SVX01N-EN

Wiring Diagrams
Figure 85. EXH/EXV - deluxe 24V - 460V-60 Hz - 3 ph(a) - (ECM motor wiring diagram)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

WSHP-SVX01N-EN

125

Wiring Diagrams
Figure 86. GEH_V (6-25 tons) - Tracer™ ZN524-460V - 60 Hz - 3 ph(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

126

WSHP-SVX01N-EN

Wiring Diagrams
Figure 87.

EXH_V - Tracer™ ZN524 460V-60 Hz - 3 ph(a) - (ECM motor wiring diagram)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

WSHP-SVX01N-EN

127

Wiring Diagrams
Figure 88. GEH_V (½-5) tons - UC400(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

128

WSHP-SVX01N-EN

Wiring Diagrams
Figure 89. GEH_V (6-25 tons) - UC400(a)

(a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.

WSHP-SVX01N-EN

129

Wiring Diagrams

130

WSHP-SVX01N-EN

Warranty Information
Standard Warranty

Extended Warranty

The standard water-source heat pump warranty isTrane’s
parts-only warranty, running 12 months from startup, not
to exceed 18-months from shipment.

The optional extended warranty is a second through fifth
year warranty.The time starts at the end of the standard 1
year coverage through the fifth year.
These extended warranties apply only to new equipment
installed in domesticTrane Commercial Systems Group
sales territories and must be ordered prior to start-up.

131

WSHP-SVX01N-EN

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2014Trane All rights reserved
WSHP-SVX01N-EN 12 Sep 2014

We are committed to using environmentally

Supersedes WSHP-SVX01M-EN (15 Dec 2013)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Language                        : en
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Copyright                       : ? 2014 Trane
Job Ref                         : Title 24
Producer                        : Acrobat Distiller 10.1.10 (Windows)
Keywords                        : Axiom Horizontal/Vertical Water-Source  Heat Pump, GEH, GEV, WSHP-SVX01N-EN September 2014
Modify Date                     : 2014:09:12 10:21:51-05:00
Creator Tool                    : FrameMaker 10.0.2
Create Date                     : 2014:09:12 09:08:39Z
Metadata Date                   : 2014:09:12 10:21:51-05:00
Format                          : application/pdf
Title                           : Axiom Horizontal/Vertical Water-Source Comfort System Models GEH and GEV; WSHP-SVX01N-EN September 2014
Creator                         : Unitary Technical Literature
Description                     : Axiom Horizontal/Vertical Water-Source Comfort System Models GEH and GEV, 1/2-25 Tons (R-410A); WSHP-SVX01N-EN September 2014
Document ID                     : uuid:14a5651b-b678-4248-bbbf-21b6bf4435ff
Instance ID                     : uuid:736d9a6a-ffa8-4493-a3d0-3091372c0695
Page Layout                     : OneColumn
Page Mode                       : UseOutlines
Page Count                      : 132
Author                          : Unitary Technical Literature
Subject                         : Axiom Horizontal/Vertical Water-Source Comfort System Models GEH and GEV, 1/2-25 Tons (R-410A); WSHP-SVX01N-EN September 2014
EXIF Metadata provided by EXIF.tools

Navigation menu