Trane Series R Helical Rotary Rtac Installation And Maintenance Manual SVX01M EN (01/2015)

2015-04-02

: Trane Trane-Series-R-Helical-Rotary--Rtac-Installation-And-Maintenance-Manual-684182 trane-series-r-helical-rotary--rtac-installation-and-maintenance-manual-684182 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 130

DownloadTrane Trane-Series-R-Helical-Rotary--Rtac-Installation-And-Maintenance-Manual- RTAC-SVX01M-EN (01/2015)  Trane-series-r-helical-rotary--rtac-installation-and-maintenance-manual
Open PDF In BrowserView PDF
Installation, Operation,
and Maintenance

Series R® Air-Cooled
Helical Rotary Liquid Chillers

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.

January 2015

RTAC-SVX01M-EN

Introduction
Read this manual thoroughly before operating or servicing
this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.

The three types of advisories are defined as follows:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
CAUTIONs situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.

WARNING

NOTICE

WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.

WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•

Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.

•

When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.

•

If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.

Indicates a situation that could result in
equipment or property-damage only
accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.

Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.

© 2015Trane All rights reserved

Failure to follow instructions could result in death or
serious injury.

RTAC-SVX01M-EN

Introduction

Factory Warranty Information
Compliance with the following is required to preserve the
factory warranty:

All Unit Installations
Startup MUST be performed byTrane, or an authorized
agent ofTrane, to VALIDATE this WARRANTY. Contractor
must provide a two-week startup notification toTrane (or
an agent ofTrane specifically authorized to perform
startup).

Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.

Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.

Revision History
RTAC-SVX01M-EN (30 Jan 2015)
•

Correction to Model Number digit 5-7.

•

Addition of seismic isolator option.

•

Removal of duplicated information found in other
locations (nameplate, catalog, submittal).

•

Removal of detailed communication system
information found in controls documents.

RTAC-SVX01M-EN

3

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Description . . . . . . . . . . . . . . .
Outdoor Unit Nameplate . . . . . . . . . . . . . . .
Compressor Nameplate . . . . . . . . . . . . . . . .
Unit Model Number . . . . . . . . . . . . . . . . . . . .
Compressor Model Number . . . . . . . . . . . .
Compressor Serial Number . . . . . . . . . . . . .

6
6
6
7
8
8

General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Description . . . . . . . . . . . . . . . . . . . . . . . 9
Accessory/Option Information . . . . . . . . . . . 9

Isolator Selection and Mounting
Locations . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Evaporator Water Piping . . . . . . . . . . . . . . .47
Entering Chilled Water Piping . . . . . . . . . .48
Leaving Chilled Water Piping . . . . . . . . . .48
Evaporator Drain . . . . . . . . . . . . . . . . . . . .48
Evaporator Flow Switch . . . . . . . . . . . . . .48

Water Pressure Gauges . . . . . . . . . . . . . . . .52
Water Pressure Relief Valves . . . . . . . . . . . .52
Freeze Avoidance . . . . . . . . . . . . . . . . . . . . . .53

Isolator Shipping Location . . . . . . . . . . . . . 9

Low Evaporator Refrigerant Cutout, Glycol
Recommendations . . . . . . . . . . . . . . . . . . . . .54

Pre-installation . . . . . . . . . . . . . . . . . . . . . . . . . 20

Procedure . . . . . . . . . . . . . . . . . . . . . . . . . .54

Unit Inspection . . . . . . . . . . . . . . . . . . . . . 20

Specials . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

Inspection Checklist . . . . . . . . . . . . . . . . . 20

Installation - Mechanical
Remote Evaporator Option . . . . . . . . . . . . . . .56
System Configuration and Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . .56

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Installation Responsibilities . . . . . . . . . . . 20

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Dimensions and Weights . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . .
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21
21
21
24

Non-Seismically Rated Units . . . . . . . . . . 24
Seismically Rated Unit Weights . . . . . . . 26
Remote Evaporator Unit Weights . . . . . . 27

Installation - Mechanical . . . . . . . . . . . . . . . . 28
Location Requirements . . . . . . . . . . . . . . . . 28
Noise Considerations . . . . . . . . . . . . . . . . 28
Foundation . . . . . . . . . . . . . . . . . . . . . . . . 28
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . 28

Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Lifting Procedure . . . . . . . . . . . . . . . . . . . 28

Isolation and Sound Emission . . . . . . . . . . 34
Mounting and Leveling . . . . . . . . . . . . . . . . 34
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . 34
Elastomeric Isolators
(Optional for units without seismic rating) 34
Unit Isolation for Seismically Rated Units 35
4

Line Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Liquid Line Sizing Steps . . . . . . . . . . . . . .60
Suction Line Sizing Steps . . . . . . . . . . . . .61
Suction Accumulator Sizing . . . . . . . . . . .61

Piping Installation Procedures . . . . . . . . . . .62
Refrigerant Sensors . . . . . . . . . . . . . . . . . . . .62
Refrigerant Pressure Relief Valve Venting .62
Leak Test and Evacuation . . . . . . . . . . . . . . .63
Refrigerant and Additional Oil Charge . . . .64
Refrigerant Charge Determination . . . . . .64
Oil Charge Determination . . . . . . . . . . . . .64

Installation - Electrical . . . . . . . . . . . . . . . . . . . .65
General Recommendations . . . . . . . . . . . . .65
Installer-Supplied Components . . . . . . . . . .66
Power Supply Wiring . . . . . . . . . . . . . . . . .66

Control Power Supply . . . . . . . . . . . . . . . . . .67
Heater Power Supply and Convenience
Outlet (Packaged Units Only) . . . . . . . . . .67

Interconnecting Wiring . . . . . . . . . . . . . . . . .68
Chilled Water Pump Control . . . . . . . . . . .68

Alarm and Status Relay Outputs
RTAC-SVX01M-EN

Table of Contents
(Programmable Relays) . . . . . . . . . . . . . . . 68

TechView . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83

Relay Assignments Using TechView . . . . 69

Unit View . . . . . . . . . . . . . . . . . . . . . . . . . .85

Low Voltage Wiring . . . . . . . . . . . . . . . . . . . 69

Compressor Service View . . . . . . . . . . . . .85

Emergency Stop . . . . . . . . . . . . . . . . . . . . 69

Status View . . . . . . . . . . . . . . . . . . . . . . . . .85

External Auto/Stop . . . . . . . . . . . . . . . . . . 70

Setpoint View . . . . . . . . . . . . . . . . . . . . . . .85

External Circuit Lockout – Circuit #1 and #2
70

Diagnostics View . . . . . . . . . . . . . . . . . . . .86

Ice Building Option . . . . . . . . . . . . . . . . . . 70

Software View . . . . . . . . . . . . . . . . . . . . . .89

External Chilled Water Setpoint
(ECWS) Option . . . . . . . . . . . . . . . . . . . . . 70

Binding View . . . . . . . . . . . . . . . . . . . . . . .89

External Current Limit Setpoint
(ECLS) Option . . . . . . . . . . . . . . . . . . . . . . 71
Chilled Water Reset (CWR) . . . . . . . . . . . 71

Communications Interface Options . . . . . 72
Tracer Communications Interface
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
LonTalk™ Interface (LCI-C) . . . . . . . . . . . 72

Operating Principles . . . . . . . . . . . . . . . . . . . .
Refrigeration Cycle . . . . . . . . . . . . . . . . . . .
Refrigerant R-134a . . . . . . . . . . . . . . . . . . . .
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . .
Condenser and Subcooler . . . . . . . . . . . . .
Expansion Valve . . . . . . . . . . . . . . . . . . . . . .
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil System . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controls Interface . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controls Interface . . . . . . . . . . . . . . . . . . . . .
DynaView Display . . . . . . . . . . . . . . . . . . . .

73
73
73
73
74
74
74
74

Configuration View . . . . . . . . . . . . . . . . . .86

Replacing or Adding Devices . . . . . . . . . .89

Pre-Start Checkout . . . . . . . . . . . . . . . . . . . . . . .92
Start-Up and Shutdown . . . . . . . . . . . . . . . . . .93
Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . .93
Temporary Shutdown and Restart . . . . . . .94
Extended Shutdown Procedure . . . . . . . . . .94
Seasonal Unit Start-Up Procedure . . . . . . .95
System Restart After Extended Shutdown 95
Sequence of Operation . . . . . . . . . . . . . . . . .96
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Weekly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Refrigerant and Oil Charge Management 100
Lubrication System . . . . . . . . . . . . . . . . . . .101

75

Oil Sump Level Check . . . . . . . . . . . . . . .101

75

Condenser Maintenance . . . . . . . . . . . . . . .101

75

Condenser Coil Cleaning . . . . . . . . . . . . .101

75

Travel Restraint . . . . . . . . . . . . . . . . . . . . . .102

Key Functions . . . . . . . . . . . . . . . . . . . . . . 75

Setpoint Screen . . . . . . . . . . . . . . . . . . . . 82

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
Legend to Diagnostics Table . . . . . . . . . . .103
Starter Diagnostics . . . . . . . . . . . . . . . . . . .103
Main Processor Diagnostics . . . . . . . . . . . .108
Communication Diagnostics . . . . . . . . . . .116
Main Processor Boot Messages
and Diagnostics . . . . . . . . . . . . . . . . . . . . . .121

Diagnostic Screen . . . . . . . . . . . . . . . . . . 83

Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .122

Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . 83

Log and Check Sheet . . . . . . . . . . . . . . . . . . .124

Display Screens . . . . . . . . . . . . . . . . . . . . 76
Modes Screen . . . . . . . . . . . . . . . . . . . . . . 77
Chiller Screen . . . . . . . . . . . . . . . . . . . . . . 81
Compressor Screen . . . . . . . . . . . . . . . . . 81
Refrigerant Screen . . . . . . . . . . . . . . . . . . 81

Display Formats . . . . . . . . . . . . . . . . . . . . . . 83
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Languages . . . . . . . . . . . . . . . . . . . . . . . . . 83
RTAC-SVX01M-EN

5

Model Number Description
Nameplates

of typical unit model number and the coding system for
each.

The RTAC outdoor unit nameplates are applied to the
exterior of the Control Panel. A compressor nameplate is
located on each compressor. When the unit arrives, if unit
is not covered with a tarp, compare all nameplate data with
ordering, submittal, and shipping information.

Each position, or group of positions, in the model number
is used to represent a feature. For example, in the first
table, position 08 of the unit model number, Unit Voltage,
contains the number “4”.A 4 in this position means that the
unit voltage is 460/60/3.

Outdoor Unit Nameplate

Unit Model Number. An example of a typical unit
model number (M/N) is:

See Figure 1, p. 6 for a typical unit nameplate.The outdoor
unit nameplate provides the following information:

RTAC 350A UA0N NAFN N1NX 1TEN NN0N N01N
Model number digits are selected and assigned in
accordance with the definitions as listed in “Unit Model
Number,” p. 7.

•

Unit model and size description.

•

Unit serial number.

•

Identifies unit electrical requirements.

•

Lists correct operating charges of R-134a and
refrigerant oil (Trane OIL00048).

•

Lists unit test pressures.

•

Identifies installation, operation and maintenance and
service data literature (Pueblo).

•

Compressor model number. See “Compressor Model
Number,” p. 8.

•

Lists drawing numbers for unit wiring diagrams
(Pueblo).

•

Compressor serial number. See“Compressor Serial
Number,” p. 8.

•

Compressor electrical characteristics.

•

Utilization range.

•

Recommended refrigerant.

Model Number Coding System
The model numbers for the unit and the compressor are
composed of numbers and letters that represent features
of the equipment. Shown in the following table is a sample
Figure 1.

6

Compressor Nameplate
The compressor nameplate provides following
information:

Typical unit nameplate

RTAC-SVX01M-EN

Model Number Descriptions
Unit Model Number
Digits 1, 2 - Unit Model

Digit 15 - Evaporator
Application

Digit 25 - Control Input
Accessories/Options

F
G

=
=

N
R

=
=

Digit 4 - Development Sequence

R

=

C

Digit 16 - Evaporator
Configuration

C
B

=
=

RT =

Rotary chiller

Digit 3 - Unit Type
A

=
=

Air-cooled
Development sequence

Digits 5, 6 & 7 - Nominal
Capacity
120
130
140
155
170
185
200
225
250
275
300
350
375
400
450
500

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

120 Nominal tons
130 Nominal tons
140 Nominal tons
155 Nominal tons
170 Nominal tons
185 Nominal tons
200 Nominal tons
225 Nominal tons
250 Nominal tons
275 Nominal tons
300 Nominal tons
350 Nominal tons
375 Nominal tons
400 Nominal tons
450 Nominal tons
500 Nominal tons

Digit 8 - Unit Voltage
A
C
J
D
4
5

=
=
=
=
=
=

200/60/3
230/60/3
380/60/3
400/50/3
460/60/3
575/60/3

Digit 9 - Manufacturing
Location
U

=

Water Chiller Business Unit,
Pueblo, CO USA

Digits 10, 11 - Design Sequence
XX =

Factory Input

N
P
Q
R

=
=
=
=

Standard (40-60 F) leaving temp
Low (Less than 40 F) leaving
temp
Remote (40-60 F) leaving temp

2 pass, 0.75” insulation
3 pass, 0.75” insulation
2 pass, 1.25” insulation
3 pass, 1.25” insulation

Digit 17 - Condenser
Application
N
H
L
W

=
=
=
=

Standard ambient (25-115°F)
High ambient (25-125°F)
Low ambient (0-115°F)
Wide ambient (0-125°F)

Digit 18 - Condenser Fin
Material
1
2
4

=
=
=

Standard aluminum slit fins
Copper fins
CompleteCoat™ epoxy coated
fins

Digit 19 - Condenser Fan/Motor
Configuration
T =
W =

STD fans withTEAO motors
Low noise fans

Digit 20 - Compressor Motor
Starter Type
X
Y

=
=

Across-the-line
Wye-delta closed transition

Digit 21 - Incoming Power Line
Connection
1
2

=
=

Single point power connection
Dual point power connection

No remote inputs
Ext. evaporator leaving water
setpoint
Ext. current limit setpoint
Ext. leaving water and current
limit setpoint

Digit 26 - Control Output
Accessories/Options
N
A
C
D

=
=
=
=

No output options
Alarm relay outputs
Ice making I/O
Alarm relay outputs and ice
making I/O

Digit 27 - Electrical Protection
Options
0
5
6

=
=
=

No short circuit rating
Default short circuit rating
High amp short circuit rating

Digit 28 - Flow Switch
T

=

U

=

Factory installed flow switch water
Factory installed flow switch
glycol

Digit 29 - Control Panel
Accessories
N
A

=
=

No convenience outlet
15A 115V convenience outlet
(60Hz)

Digit 30 - Service Valves
1

=

With suction service valves

Digit 31 - Compressor Sound
Attenuation Option
0

=

1

=

No compressor sound
attenuation
Factory installed compressor
sound attenuation

Digit 12 - Unit Basic
Configuration

Digit 22 - Power Line
Connection Type

N
H
A

Digit 32 - Appearance Options

T
D
C

N
A
C

=
=
=

Standard efficiency/performance
High efficiency/performance
Extra efficiency/performance

Digit 13 - Agency Listing
N
U
S
R

=
=
=
=

No agency listing
C/UL listing
Seismic rated - IBC and OSHPD
C/UL listed and seismic rated

Digit 14 - Pressure Vessel Code
A
C
D
L

=
=
=
=

ASME pressure vessel code
Canadian code
Australian code
Chinese code

RTAC-SVX01M-EN

=
=
=

Terminal block connection
Non-fused disconnect switch(es)
Circuit breaker(s)

=
=
=

No appearance options
Architectural louvered panels
Half louvers

Digit 23 - Unit Operator
Interface

Digit 33 - Installation
Accessories

D

N
F
R
G
E

=
=
=
=
=

S

=

=

DynaView operator interface

Digit 24 - Remote Operator
Interface
N
C
B
L

=
=
=
=

No remote interface
Tracer™ Comm 3 interface
BACnet® interface
LonTalk® compatible (LCI-C)
interface

No installation accessories
Flange kit for water connections
Neoprene in shear unit isolators
Neoprene isolators and flange kit
Seismic elastomeric isolation
pads
Seismic spring isolators

7

Model Number Descriptions
Digit 34 - Factory Testing
Options
0
C

=
=

C

=

E

=

Standard functional test
Customer-witnessed
performance
test with report
Customer-witnessed
performance
test plus Rapid Restart test
Non-witnessed performance test
with report

Digit 35 — Control, Label &
Literature
C
E
F

=
=
=

Spanish
English
French

Digit 36 — Special Order
X
S

=
=

Standard unit configuration
Unit has special order feature

Digit 37 — Safety Devices
N

=

Standard

Compressor Model
Number

Compressor Serial
Number

Digits 1-3 — Compressor Family

Digits 1-2 — Year

CHH=

YY = Last two digits of year of
manufacture

Positive displacement,
refrigerant, helical rotary,
hermetic compressor

Digits 3-4 — Week

Digit 4— Compressor Type

WW =

T

Digit 5 — Day

=

GP2+

Digit 5
0

=

All compressors

Digit 6 — Frame Size
K
L
M
N

=
=
=
=

K Frame
L Frame
M Frame
N Frame

Digit 7 — Compressor Capacity
3
4

=
=

GP2+ Smaller capacity (minor)
GP2+ Larger capacity (major)

1
2
3
4
5
6
7

=
=
=
=
=
=
=

Week of build, from 00 to 52
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
sunday

Digits 6-8 — Coded Time Stamp
TTT =

Used to ensure uniqueness of
serial number

Digit 9 — Assembly Line
L

=

Varies with facility

Digit 10— Build Location
A

8

=

Monterrey

RTAC-SVX01M-EN

General Data
Unit Description

Accessory/Option Information

The 140 - 500 ton Model RTAC units are helical-rotary type,
air-cooled liquid chillers designed for installation
outdoors.The compressor circuits are completely
assembled, hermetic packages that are factory-piped,
wired, leak-tested, dehydrated, and tested for proper
control operation before shipment.

Check all the accessories and loose parts which are
shipped with the unit against the shipping list. Included in
these items will be water vessel drain plugs, rigging and
electrical diagrams, and service literature, which are
placed inside the control panel and/or starter panel for
shipment.

Chilled water inlet and outlet openings are covered for
shipment. Each compressor has a separate compressor
motor starter.The RTAC series featuresTrane’s exclusive
Adaptive Control ™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive Control logic can adjust capacity variables to
avoid chiller shutdown when necessary, and keep
producing chilled water.The units feature two
independent refrigerant circuits. Compressor unloaders
are solenoid actuated and oil pressure operated. Each
refrigerant circuit is provided with filter, sight glass,
electronic expansion valve, and charging valves.The
shell-and-tube type evaporator is manufactured in
accordance with ASME standards or other international
codes. Each evaporator is fully insulated and is equipped
with water drain and vent connections. Packaged units
have heat tape protection to - 20°F (-28.9°C) as standard.
As an option, a convenience outlet can be supplied.

Isolator Shipping Location
If optional neoprene isolators (model number digit 33) are
ordered with unit, they are shipped mounted on the unit.
See Figure 3 and Figure 4.
Figure 3.

Isolator shipping locations 140-250T units

Note: Packaged units are factory charged with refrigerant
and oil.
Neoprene Isolator Shipping Location

Figure 2.

Typical RTAC packaged unit and components

Figure 4.

Isolator shipping locations 275-500T units

Neoprene Isolator Shipping Location

RTAC-SVX01M-EN

9

General Data
Table 1.

General Data - 60 hz units - standard efficiency - IP

Size

140

155

170

185

200

225

250

275

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

2

2

2

2

100/
70/70 85/70 85/85
85

2

2

2

100/
100

120/
100

120/
120

Evaporator
Water storage

300

350

400

450

500

3

3

4

4

4

Screw
3

85-85/ 100-100/ 120-120/ 100-100/ 120-120/ 120-120/
100
100
100
100-100 100-100 120-120
Flooded

(gal)

29

32

34

36

40

39

43

62

67

72

83

86

91

Min flow

(gpm)

193

214

202

217

241

217

241

309

339

375

404

422

461

Max flow

(gpm)

709

785

741

796

883

796

883

1134

1243

1374

1483

1548

1690

4

4

6

6

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(gpm)

129

143

135

145

161

145

161

206

226

250

270

282

307

Max flow

(gpm)

473

523

494

531

589

531

589

756

829

916

989

1032

1127

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

4

4

8

8

8

8

8

8

Coil length

(in)

156/
156

180/
156

180/
180

216/
180

216/
216

252/
216

252/
252

180/
108

216/108

252/108

216/216

252/216

252/252

Coil height

# of rows
Fins per foot

(in)

42

42

42

42

42

42

42

42

42

42

42

42

42

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

192

192

14/6

12/12

14/12

14/14

Fan

Direct drive propeller
Quantity
Diameter

Air flow per fan
Power/motor

#

4/4

5/4

5/5

6/5

6/6

7/6

7/7

10/6

12/6

(in)

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

30.0

(cfm)

9625

9394

9209

9209

9209

9210

9210

9209

9209

9208

9209

9210

9214

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

Tip speed (Ft/min) 8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

Fan speed

General Unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

15

15

Refrigerant charge

(lb)

165/
165

175/
165

175/
175

215/
210

215/
215

225/
215

225/
225

365/
200

415/200

460/200

415/415

460/415

460/460

Oil charge

(gal)

1.3/
1.3

1.3/
1.3

1.3/
1.3

1.9/
1.3

1.9/
1.9

1.9/
1.9

1.9/
1.9

4.2/1.9

4.6/2.9

4.6/1.9

4.6/4.6

4.6/4.6

4.6/4.6

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

0

0

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

10

RTAC-SVX01M-EN

General Data

Table 2.

General Data - 60 hz units - high efficiency - IP

Size

140

155

170

185

200

225

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2
100/85

2

2

100/100 120/100

Evaporator
Water storage

250

275

300

350

400

Screw
2

3

3

4

4

120/120

85-85/
100

100-100/
100

85-85/
85/85

100-100/
100-100

72

72

83

91

Flooded
(gal)

34

36

40

39

43

43

43

Min flow

(gpm)

202

217

241

217

241

241

241

375

375

404

461

Max flow

(gpm)

741

796

883

796

883

883

883

1374

1374

1483

1690

6

6

6

6

6

6

6

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(gpm)

135

145

161

145

161

161

161

250

250

270

307

Max flow

(gpm)

494

531

589

531

589

589

589

916

916

989

1127

4

4

4

4

4

4

4

6

6

8

8

8

8

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

Coil length

(in)

144/144

216/144

Coil height

(in)

42

42

42

42

42

42

42

42

42

42

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

5/5

6/5

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(in)

30

30

30

30

30

30

30

30

30

30

30

(cfm)

9199

9199

9199

9200

9201

9783

9203

9652

9605

9199

9201

Number of rows
Fins per foot

4

4

4

4

4

8

180/180 216/180 216/216 252/216 252/252 144/144

Fan

252/144 216/216

252/252
42

Direct drive propeller

Air flow/fan
Power/motor
Fan speed

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

1140

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

8954

Tip speed (Ft/Min)

General unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

175/175 215/205 215/215 225/215 225/225

235/235

235/235

415/200 460/200 415/415

460/460

Refrigerant charge

(lb)

Oil charge

(gal)

1.3/1.3

1.3/1.3

1.3/1.3

1.9/1.3

1.9/1.9

1.9/1.9

1.9/1.9

2.1-2.1/
1.9

2.3-2.3/
1.9

2.1-2.1/
2.1-2.1

2.3-2.3/
2.3-2.3

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

RTAC-SVX01M-EN

11

General Data

Table 3.

General Data - 60 hz units - extra efficiency - IP

Size

140

155

170

185

200

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2

275

3

3

4

4

70-70/85

85-85/85

70-70/
70-70

85-85/
85-85

72

72

83

91

2

100/85

Evaporator
Water storage

250

300

350

Screw

100/100
Flooded

(gal)

40

39

43

43

43

Min flow

(gpm)

241

217

241

241

241

375

375

404

461

Max flow

(gpm)

883

796

883

883

883

1374

1374

1483

1690

6

6

6

6

6

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(gpm)

161

145

161

161

161

250

250

270

307

Max flow

(gpm)

589

531

589

589

589

916

916

989

1127

4

4

4

4

4

6

6

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

8

8

8

8

8

8

Coil length

(in)

216/216

252/216

252/252

144/144

144/144

216/144

252/144

216/216

252/252

Coil height

(in)

42

42

42

42

42

42

42

42

42

#

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

Quantity

#

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(in)

30

30

30

30

30

30

30

30

30

(cfm)

9199

9200

9201

9783

9203

9652

9605

9199

9201

Number of rows
Fins per foot

Fan

Direct drive propeller

Air flow/fan
Power/motor
Fan speed

(hp)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

(rpm)

1140

1140

1140

1140

1140

1140

1140

1140

1140

8954

8954

8954

8954

8954

8954

8954

8954

8954

Tip speed (Ft/Min)

General unit

HFC-134a

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

Refrigerant charge

(lb)

215/215

225/215

225/225

235/235

235/235

415/200

460/200

415/415

460/460

Oil charge

(gal)

1.3/1.3

1.9/1.3

1.9/1.9

1.9/1.9

1.9/1.9

2.1-2.1/
2.1-2.1

2.1-2.1/
2.1-2.1

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

2.1-2.1/1.9 2.1-2.1/1.9

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

12

RTAC-SVX01M-EN

General Data

Table 4.

General Data - 60 hz units - standard efficiency - SI

Size

140

155

170

185

200

225

250

275

Compressor
Quantity

#

Nominal size
(tons) @60Hz

2
70/70

2
85/70

2

2

2

100/
85/85 100/85
100

2

2

120/
100

120/
120

350

400

450

500

3

3

3

4

4

4

85-85/ 100-100/ 120-120/ 100-100/ 120-120/ 120-120/
100
100
100
100-100 100-100 120-120

Evaporator
Water storage

300

Screw

Flooded
(L)

110.0

121

129

136

151

148

163

235

254

273

314

326

344

Min flow

(L/s)

12

14

13

14

15

14

15

19

21

24

25

27

29

Max flow

(L/s)

45

50

47

50

56

50

56

72

78

87

94

98

107

4

4

6

6

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(L/s)

8

9

9

9

10

9

10

13

14

16

17

18

19

Max flow

(L/s)

30

33

31

34

37

34

37

48

52

58

62

65

71

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

Coil length

(mm)

3962/
3962

4572/
3962

Coil height

(mm)

1067

# of rows

#

3

4

8

8

8

8

8

8

4572/ 5486/ 5486/ 6400/
4572 4572 5486 5486

6400/
6400

4572/
2743

5486/
2743

6400/
2743

5486/
5486

6400/
5486

6400/
6400

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

3

3

3

3

3

3

3

3

3

3

3

(fpf)

3

192

192

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

4/4

5/4

5/5

6/5

6/6

7/6

Diameter

7/7

10/6

12/6

14/6

12/12

14/12

14/14

(mm)

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

726.0

Air flow per fan (m³/hr) 16351 15958 15644 15644 15644 15646 15647

Fins per foot

4

4

4

4

Fan

Direct drive propeller

15644

15645

15642

15645

15646

15653

Power/motor

(kW)

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

45

45

45

45

# Refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

15

15

Refrigerant
charge

(kg)

75/75

79/75

102/
102

166/91

188/91

209/91

188/188

209/188

209/209
9-9/9-9

General Unit

Oil charge

HFC-134a

79/79 98/95 98/98 102/98

(L)

5/5

5/5

5/5

7/5

7/7

7/7

7/7

8-8/7

9-9/11

9-9/11

9-9/9-9

9-9/9-9

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

RTAC-SVX01M-EN

13

General Data

Table 5.

General Data - 60 hz units - high efficiency - SI

Size

140

155

170

185

200

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2
100/85

2

250

2

2

100/100 70-70/85 85-85/85

Evaporator
Water storage

225

275

300

350

400

Screw
4

4

4

4

70-70/
70-70

85-85/
85-85

85-85/
85/85

100-100/
100-100

344

Flooded
(L)

129

136

151

148

163

163

163

273

273

314

Min flow

(L/s)

13

14

15

14

15

15

15

24

24

25

29

Max flow

(L/s)

47

50

56

50

56

56

56

87

87

94

107

6

6

6

6

6

6

6

8

8

8

8

2 Pass arrangement

Water conn (NPS-in)
3 Pass arrangement
Min flow

(L/s)

9

9

10

9

10

10

10

16

16

17

19

Max flow

(L/s)

31

34

37

34

37

37

37

58

58

62

71

4

4

4

4

4

4

4

6

6

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

8

8

8

8

8

8

Coil length

(mm)

4572/
4572

5486/
4572

5486/
5486

6400/
5486

6400/
6400

3657/
3657

3657/
3657

5486/
3657

6400/
3657

5486/
5486

6400/
6400

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

5/5

6/5

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(mm)

762

762

762

762

762

762

762

762

762

762

762

Number of rows
Fins per foot

Fan

Direct drive propeller

15628

15628

15628

15629

15631

16619

15634

16397

16317

15628

15631

Power/motor

Air per fan (m³/hr)
(kW)

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

45

45

# refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

(kg)

79/79

98/93

98/98

102/98

188/91

209/91

188/188

209/209
9-9/9-9

General unit

Refrig charge
Oil charge

HFC-134a

102/102 107/107 107/107

(L)

5/5

5/5

5/5

7/5

7/7

7/7

7/7

8-8/7

9-9/7

8-8/8-8

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

14

RTAC-SVX01M-EN

General Data

Table 6.

General Data - 60 hz units - extra efficiency - SI

Size

140

155

170

185

200

250

275

300

350

2

2

2

2

2

3

3

4

4

85-85/100

100-100/
100

85-85/85/
85

100-100/
100-100

344

Compressor
Quantity
Nominal size
@60Hz

#
(tons)

85/85

100/85

100/100

120/100

Evaporator
Water storage

120/120
Flooded

(L)

151

148

163

163

163

273

273

314

Min flow

(L/s)

15

14

15

15

15

24

24

25

29

Max flow

(L/s)

56

50

56

56

56

87

87

94

107

6

6

6

6

6

8

8

8

8

2 Pass arrangement

Water conn (NPS-in)
3 Pass arrangement
Min flow

(L/s)

10

9

10

10

10

16

16

17

19

Max flow

(L/s)

37

34

37

37

37

58

58

62

71

4

4

4

4

4

6

6

8

8

8

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

Coil length

(mm)

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

Quantity

#

6/6

7/6

7/7

8/6

8/8

12/6

14/6

12/12

14/14

Diameter

(mm)

762

762

762

762

762

762

762

762

762

15628

15629

15631

16619

15634

16397

16317

15628

15631
1.12

Number of rows
Fins per foot

4

4

4

8

8

5486/5486 6400/5486 6400/6400 3657/3657 4572/2743 5486/3657 6400/3657 5486/5486

Fan

6400/6400
1067

Direct drive propeller

Air per fan (m³/hr)
Power/motor

(kW)

1.12

1.12

1.12

1.12

1.12

1.12

1.12

1.12

Fan speed

(rps)

19

19

19

19

19

19

19

19

19

Tip speed

M/S

45

45

45

45

45

45

45

45

45

General unit

HFC-134a

# refrig ckts

#

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

(kg)

98/98

102/98

102/102

107/107

107/107

188/91

209/91

188/188

209/209
8-8/8-8

Refrig charge

(L)

5/5

7/5

7/7

7/7

7/7

8-8/7

8-8/7

8-8/8-8

Min ambient-std

Oil charge

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

RTAC-SVX01M-EN

15

General Data

Table 7.

General Data - 50 hz units - standard efficiency - IP

Size

140

155

170

185

200

Compressor
Quantity
Nominal
size@50Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2
100/85

2

3

100/100

70-70 /
100

Evaporator
Water storage

250

275

300

3

3

350

375

400

4

4

Screw

85-85 / 100-100/
100
100

4
85-85/
85-85

100-100/ 100-100/
85-85
100-100

Flooded
(gal)

29

32

34

36

40

56

62

67

75

79

83

Min flow

(gpm)

193

214

202

217

241

265

309

339

351

381

404

Max flow

(gpm)

709

785

741

796

883

970

1134

1243

1287

1396

1483

4

4

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(gpm)

129

143

135

145

161

176

206

226

234

254

270

Max flow

(gpm)

473

523

494

531

589

647

756

829

858

930

989

3.5

3.5

4

4

4

6

6

6

8

8

8

8

8

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

Coil length

(in)

216/180

216/216

Coil height

(in)

42

42

42

42

42

42

42

42

42

42

42

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

4/4

5/4

5/5

6/5

6/5

8/6

10/6

12/6

10/10

12/10

12/12

Diameter

(in)

30

30

30

30

30

30

30

30

30

30

30

(cfm)

7918

7723

7567

7567

7567

7764

7566

7567

7567

7567

7567

Number of rows
Fins per foot

4

4

4

4

4

8

156/156 180/156 180/180 216/180 216/216 156/108 180/108 216/108 180/180

Fan

Direct drive propeller

Air flow per fan
Power per motor
Fan speed

(hp)

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

(rpm)

950

950

950

950

950

950

950

950

950

950

950

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

Tip speed (Ft/min)

General unit

HFC-134a

# refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

Refrig charge

(lb)

175/175

215/205 215/215

225/215 225/225

235/235 235/235 415/200 460/200

415/415

460/460

Oil charge

(gal)

1.3/1.3

1.3/1.3

1.3/1.3

1.9/1.3

1.9/1.9

2.1-2.1/
1.9

2.3-2.3/
2.1-2.1

2.3-2.3/
2.3-2.3

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

2.1-2.1/ 2.3-2.3/ 2.1-2.1/
1.9
1.9
2.1-2.1

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

16

RTAC-SVX01M-EN

General Data

Table 8.

General Data - 50 hz units - high efficiency - IP

Size

120

130

140

155

170

185

200

250

Compressor
Quantity
Nominal
size@50Hz

275

300

350

3

4

375

400

4

4

Screw
#
(tons)

2
60/60

2
70/60

2
70/70

2
85/70

2

2

85/85 100/85

2

3

100/
100

3

70-70 / 85-85 / 100-100/ 85-85 /
100
100
100
85-85

Evaporator

100-100/ 100-100/
85-85
100-100

Flooded

Water storage

(gal)

29

32

34

36

40

39

43

67

72

72

83

86

91

Min flow

(gpm)

193

214

202

217

241

217

241

339

375

375

404

422

461

Max flow

(gpm)

709

785

741

796

883

796

883

1243

1374

1374

1483

1548

1690

4

4

6

6

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(gpm)

129

143

135

145

161

145

161

226

250

250

270

282

307

Max flow

(gpm)

473

523

494

531

589

531

589

829

916

916

989

1032

1127

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

8

8

8

8

252/216

252/252
42

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

4

4

Coil length

(in)

156/
156

180/
156

180/
180

216/
180

216/
216

252/
216

252/
252

Coil height

(in)

42

42

42

42

42

42

42

42

42

42

42

42

#

3

3

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

4/4

5/4

5/5

6/5

6/6

7/6

7/7

10/6

12/6

14/6

12/12

14/12

14/14

Diameter

(in)

30

30

30

30

30

30

30

30

30

30

30

30

30
7559

Number of rows
Fins per foot

Fan

8

8

180/108 216/144 252/144 216/216

Direct drive propeller

Air flow per fan

(cfm)

7558

7557

7557

7558

7559

7561

7943

7906

7557

7490

Power/motor

(hp)

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

(rpm)

950

950

950

950

950

950

950

950

950

950

950

950

950

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

7461

Fan speed

Tip speed (Ft/min)

62484 68819

General unit

HFC-134a

# refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

15

15

Refrig charge

(lb)

165/
165

175/
165

175/
175

215/
205

215/
215

225/
215

415/
200

460/
200

415/
415

460/
415

460/
460

Oil charge

(gal)

2.1-2.1/
2.1-2.1

2.3-2.3/
2.3-2.3

2.3-2.3/
2.3-2.3

225/
365/200
225

1.3/1.3 1.3/1.3 1.3/1.3 1.3/1.3 1.3/1.3 1.9/1.3 1.9/1.9

2.1-2.1/ 2.1-2.1/ 2.3-2.3/
1.9
1.9
1.9

Min ambient-std

(°F)

25

25

25

25

25

25

25

25

25

25

25

25

25

Min ambient-low

(°F)

0

0

0

0

0

0

0

0

0

0

0

0

0

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

RTAC-SVX01M-EN

17

General Data

Table 9.

General Data - 50 hz units - standard efficiency - SI

Size

140

155

170

185

200

250

Compressor
Quantity
Nominal
size@50Hz

#
(tons)

2
70/70

2
85/70

2
85/85

2
100/85

2

3

100/100

70-70 /
100

Evaporator
Water storage

275

300

3

3

350

375

400

4

4

Screw

85-85 / 100-100/
100
100

4
85-85/
85-85

100-100/ 100-100/
85-85
100-100

Flooded
(L)

110

121

129

136

151

212

235

254

284

299

314

Min flow

(L/s)

12

14

13

14

15

17

19

21

22

24

25

Max flow

(L/s)

45

50

47

50

56

61

72

78

81

88

94

4

4

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(L/s)

8

9

9

9

10

11

13

14

15

16

17

Max flow

(L/s)

30

33

31

34

37

41

48

52

54

59

62

3.5

3.5

4

4

4

6

6

6

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

8

8

8

8

8

8

Coil length

(mm)

3962/
3962

4572/
3962

4572/
4572

5486/
4572

5486/
5486

3962/
2743

4572/
2743

5486/
2743

4572/
4572

5486/
4572

5486/
5486

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

4/4

5/4

5/5

6/5

6/6

8/6

10/6

12/6

10/10

12/10

12/12

Diameter

(mm)

762

762

762

762

762

762

762

762

762

762

762
12855

Number of rows
Fins per foot

Fan

Direct drive propeller

13452

13120

12855

12855

12855

13190

12853

12856

12854

12855

Power per motor

Air flow per fan (m³/hr)
(kW)

.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

Fan speed

(rps)

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

Tip speed

M/S

38

38

38

38

38

38

38

38

38

38

38

# refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

(kg)

79/79

98/93

98/98

102/98

107/107

188/91

209/91

188/188

209/209
9-9/9-9

General unit

Refrig charge
Oil charge

HFC-134a

102/102 107/107

(L)

5/5

5/5

5/5

7/5

7/7

8-8/7

8-8/7

8-8/7

8-8/8-8

9-9/8-8

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

18

RTAC-SVX01M-EN

General Data

Table 10.

General Data - 50 hz units - high efficiency - SI

Size

120

130

140

155

170

185

200

Compressor
Quantity
Nominal
size@50Hz

#
(tons)

2
60/60

2
70/60

2
70/70

2
85/70

2

2

2

275

300

350

375

400

3

3

4

4

4

85/85 100/85

3

100/
100

Evaporator
Water storage

250

Screw

70-70 / 85-85 / 100-100/ 85-85 / 100-100/ 100-100/
100
100
100
85-85
85-85
100-100

Flooded
(L)

110

121

129

136

151

148

163

254

273

273

314

326

344

Min flow

(L/s)

12

14

13

14

15

14

15

21

24

24

25

27

29

Max flow

(L/s)

45

50

47

50

56

50

56

78

87

87

94

98

107

4

4

6

6

6

6

6

8

8

8

8

8

8

2 pass arrangement

Water conn (NPS-in)
3 pass arrangement
Min flow

(L/s)

8

9

9

9

10

9

10

14

16

16

17

18

19

Max flow

(L/s)

30

33

31

34

37

34

37

52

58

58

62

65

71

3.5

3.5

4

4

4

4

4

6

6

6

8

8

8

Water conn (NPS-in)

Condenser

Fin and tube

Qty of coils

#

4

4

4

4

4

4

4

8

8

8

8

8

8

Coil length

(mm)

3962/
3962

4572/
3962

4572/
4572

5486/
4572

5486/
5486

6400/
5486

6400/
6400

4572/
2743

5486/
3657

6400/
3657

5486/
5486

6400/
5486

6400/
6400

Coil height

(mm)

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

1067

#

3

3

3

3

3

3

3

3

3

3

3

3

3

(fpf)

192

192

192

192

192

192

192

192

192

192

192

192

192

Quantity

#

4/4

5/4

5/5

6/5

6/6

7/6

7/7

10/6

12/6

14/6

12/12

14/12

14/14

Diameter

(mm)

762

762

762

762

762

762

762

762

762

762

762

762

762
12841

Number of rows
Fins per foot

Fan

Direct drive propeller

Air flow per fan (m?/hr)

13430

12838

12724

Power/motor

(kW)

62484 68819 12839 12839 12839 12840 12842 12844 13493
.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

.74

Fan speed

(rps)

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

15.8

Tip speed

M/S

38

38

38

38

38

38

38

38

38

38

38

38

38

# refrig ckts

#

2

2

2

2

2

2

2

2

2

2

2

2

2

% min load

%

15

15

15

15

15

15

15

15

15

15

15

15

15

(kg)

75/75

79/75

79/79

98/93

209/
91

188/
188

209/
188

209/
209

(L)

5/5

5/5

5/5

5/5

8-8/
7

8-8/
8-8

9-9/
9-9

9-9
9-9

General unit

Refrig charge
Oil charge

HFC-134a

98/98 102/95
5/5

7/5

102/
102
7/7

166/91 188/91
8-8/
7

8-8/
7

Min ambient-std

(°C)

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

-3.9

Min ambient-low

(°C)

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

-17.8

1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.

RTAC-SVX01M-EN

19

Pre-installation
Unit Inspection
When unit is delivered, verify it is the correct unit and is
properly equipped.

•

•

If unit is covered with optional tarp, confirm unit was
ordered with a tarp. Inspect tarp for any visible damage.
If unit does not have optional tarp, compare information
on unit nameplate with ordering and submittal
information. Inspect all exterior components for visible
damage.
Report any apparent damage or material shortage to
carrier and make a “unit damage” notation on carrier’s
delivery receipt. Specify extent and type of damage found
and notifyTrane Sales Office. Do not proceed with
installation of a damaged unit without sales office
approval.

•
•

•
•

Inspection Checklist

•

To protect against loss due to damage in transit, complete
this checklist upon receipt of unit.
• Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
• Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored.
Concealed damage must be reported within 15 days.
• If concealed damage is discovered, stop unpacking the
shipment. Do not remove damaged material from the
receiving location.Take photos of the damage, if
possible.The owner must provide reasonable
evidence that the damage did not occur after delivery.
• Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an
immediate, joint inspection of the damage with the
carrier and the consignee.

•

NotifyTrane sales representative and arrange for repair.
Do not repair unit until damage is inspected by the carrier’s
representative.

•
•

•
•

Install unit on a flat foundation, level (within 1/4” [6
mm] across the length and width of the unit), and
strong enough to support unit loading.
Install unit per the instructions contained in the
Installation-Mechanical and Installation-Electrical
sections of this manual.
Install any optional sensors and make electrical
connections at the CH530.
Where specified, provide and install valves in water
piping upstream and downstream of evaporator water
connections to isolate evaporator for maintenance,
and to balance/trim system.
Furnish and install pressure gauges in inlet and outlet
piping of the evaporator.
Furnish and install a drain valve to the bottom of the
evaporator waterbox.
Supply and install a vent cock to the top of the
evaporator waterbox.
Furnish and install strainers ahead of all pumps and
automatic modulating valves, and at inlet of
evaporator.
Provide and install field wiring.
Install heat tape and insulate the chilled water lines and
any other portions of the system, as required, to
prevent sweating under normal operating conditions
or freezing during low ambient temperature
conditions.
Install evaporator drain plug.The plug ships in unit
control panel.
Start unit under supervision of a qualified service
technician.

General
Report any damage incurred during handling or
installation to theTrane sales office immediately.

Storage
Extended storage of outdoor unit prior to installation
requires these precautionary measures:
• Store the outdoor unit in a secure area.
• At least every three months (quarterly), check the
pressure in the refrigerant circuits to verify that the
refrigerant charge is intact. If it is not, contact a
qualified service organization and the appropriate
Trane sales office.
• Close the discharge and liquid line isolation valves.

Installation Responsibilities
Generally, the contractor must do the following when
installing an RTAC unit:

20

RTAC-SVX01M-EN

Dimensions and Weights
Dimensions
See unit submittals for specific unit dimensions and water
connection locations.

Clearances
Provide enough space around the outdoor unit to allow the
installation and maintenance personnel unrestricted

access to all service points. Refer to submittal drawings for
the unit dimensions. A minimum of 4 feet (1.2 m) is
recommended for compressor service. Provide sufficient
clearance for the opening of control panel doors. See
Figure 5, p. 21 through Figure 9, p. 23 for minimum
clearances. In all cases, local codes which require
additional clearances will take precedence over these
recommendations.

Figure 5. Recommended unit clearance — 15 foot bases

Figure 6. Recommended unit clearances 18-21 foot bases

RTAC-SVX01M-EN

21

Dimensions and Weights

Figure 7.

Recommended unit clearances 30-45 foot bases

Tube Removal
Clearance Area
(Non DynaView
Control Panel End)

Figure 8. Recommended remote evaporator unit clearances — 15-30 foot bases

22

RTAC-SVX01M-EN

Dimensions and Weights

Figure 9. Recommended evaporator clearance

148”
(3760 mm)

Unobstructed flow of condenser air is essential to
maintain chiller capacity and operating efficiency. When
determining unit placement, give careful consideration to
assuring a sufficient flow of air across the condenser heat
transfer surface.Two detrimental conditions are possible
and must be avoided if optimum performance is to be
achieved: warm air recirculation and coil starvation.
Warm air recirculation occurs when discharge air from the
condenser fans is recycled back to the condenser coil inlet.
Coil starvation occurs when free airflow to (or from) the
condenser is restricted.
Both warm air recirculation and coil starvation cause
reduction in unit efficiency and capacity due to the
increased head pressures.
Debris, trash, supplies etc. should not be allowed to
accumulate in the vicinity of the unit. Supply air movement
may draw debris into the condenser coil, blocking spaces
between coil fins and causing coil starvation. Special
consideration should be given to low ambient units.
Condenser coils and fan discharge must be kept free of
snow or other obstructions to permit adequate airflow for
satisfactory unit operation.
In situations where equipment must be installed with less
clearance than recommended, such as frequently occurs
in retrofit and rooftop applications, restricted airflow is
common.The Main Processor will direct the unit to make
as much chilled water as possible given the actual installed
conditions. Consult yourTrane sales engineer for more
details.
Note: If the outdoor unit configuration requires a
variance to the clearance dimensions, contact your
Trane Sales Office Representative. Also refer to
Trane Engineering Bulletins for application
information on RTAC chillers.

RTAC-SVX01M-EN

23

Dimensions and Weights

Weights
Non-Seismically Rated Units
Table 11.

Weight - packaged units - 60 Hz - aluminum or CompleteCoat coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

10832

4913

11146

5056

10859

4926

11160

5062

12171

5521

12585

5708

155

10910

4949

11146

5056

12114

5495

12445

5645

13984

6343

14293

6483

170

10877

4934

11218

5088

12171

5521

12585

5708

14454

6556

14721

6677

185

12479

5660

12899

5851

13984

6343

14293

6483

15915

7219

16413

7445

200

12884

5844

13193

5984

14454

6556

14721

6677

16016

7265

16413

7445

225

14635

6638

14966

6788

15915

7219

16413

7445

250

14916

6766

15191

6890

16016

7265

16413

7445

20476

9288

21048

9547

275

19025

8630

19685

8929

20393

9250

21048

9547

21667

9828

22160

10052

300

20699

9389

21214

9622

21667

9828

22160

10052

24073

10919

24700

11204

350

21550

9775

22005

9981

24073

10919

24700

11204

27136

12309

27750

12587

400

25409

11525

25854

11727

27136

12309

27750

12587

450

26816

12163

27393

12425

n/a

n/a

500

27136

12309

27912

12661

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

Table 12. Weight - packaged units - 60 Hz - copper coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

13407

6081

13734

6230

13426

6090

13734

6230

15590

7071

15998

7257

155

13420

6087

13734

6230

15647

7097

15854

7191

18250

8278

18613

8443

170

13442

6097

13733

6229

15590

7071

15998

7257

18701

8483

18958

8599

185

15870

7198

16253

7372

18250

8278

18613

8443

20794

9432

21290

9657

200

16304

7395

16630

7543

18701

8483

18958

8599

20881

9471

21290

9657

225

18739

8500

18156

8235

20794

9432

21290

9657

250

18905

8575

19223

8719

20881

9471

21290

9657

26017

11801

26558

12046

275

23905

10843

24608

11162

26017

11801

26558

12046

27660

12546

28182

12783

300

26039

11811

26580

12056

27660

12546

28182

12783

30848

13992

31431

14257

350

27395

12426

27920

12664

30848

13992

31431

14257

35166

15951

35688

16188

400

32216

14613

32723

14843

35014

15882

35688

16188

450

32682

14824

33178

15049

n/a

n/a

500

35014

15882

35787

16233

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

24

RTAC-SVX01M-EN

Dimensions and Weights

Table 13. Weight - packaged units - 50 Hz - aluminum or CompleteCoat coils
Unit
Size
(tons)

Standard Efficiency
Shipping
lb

High Efficiency

Operating
kg

lb

Shipping
kg

Operating

lb

kg

lb

kg

120

n/a

10832

4913

11146

5056

130

n/a

10910

4949

11146

5056

140

10844

4919

11146

5056

10871

4931

11160

5062

155

11131

5049

11397

5170

12466

5654

12786

5800

170

11426

5183

11632

5276

12742

5780

12990

5892

185

12797

5805

13111

5947

14383

6524

14754

6692

200

12962

5879

13304

6035

14516

6584

14967

6789

250

18051

8188

19186

8703

19176

8698

20483

9291

275

19715

8943

20240

9181

21944

9954

21532

9767

300

20242

9182

21027

9538

22272

10102

22185

10063

350

23231

10537

23799

10795

24924

11305

25812

11708

375

24360

11049

25213

11436

26298

11929

26963

12230

400

25222

11440

25854

11727

27120

12301

27751

12588

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

Table 14. Weight - packaged units - 50 Hz - copper coils
Unit
Size
(tons)

Standard Efficiency
Shipping
lb

High Efficiency

Operating
kg

120

lb

Shipping
kg

n/a

130

n/a

Operating

lb

kg

lb

kg

13407

6081

13734

6230

13426

6090

13734

6230

140

13417

6086

13734

6230

13446

6099

13734

6230

155

13851

6283

13962

6333

15772

7154

16192

7345

170

13856

6285

14366

6516

16162

7331

17421

7902

185

16216

7355

16463

7467

18570

8423

18979

8609

200

16381

7430

16721

7584

18833

8542

19223

8719

250

22058

10005

21837

9905

24015

10893

24056

10912

275

24584

11151

25095

11383

26617

12073

27135

12308

300

25893

11745

26336

11946

27617

12527

28182

12783

350

29084

13192

29527

13393

32037

14532

32712

14838

375

30432

13804

30971

14048

32463

14725

32971

14955

400

32112

14566

32787

14872

34982

15867

35525

16114

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

RTAC-SVX01M-EN

25

Dimensions and Weights

Seismically Rated Unit Weights
Table 15. Weight - seismically rated - packaged units - 60 Hz - aluminum or CompleteCoat coils
Standard Efficiency

High Efficiency

Extra Efficiency

Unit
Size
(tons)

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

140

11374

5159

11646

5283

11402

5172

11711

5312

12780

5797

13185

5981

155

11456

5196

11703

5308

12720

5770

13067

5927

14683

6660

15021

6813

170

11421

5180

11779

5343

12780

5797

13214

5994

15177

6884

15433

7000

185

13103

5943

13544

6143

14683

6660

15008

6807

16711

7580

17234

7817

200

13528

6136

13853

6284

15177

6884

15457

7011

16817

7628

17234

7817

225

15367

6970

15714

7128

16711

7580

17234

7817

250

15662

7104

15951

7235

16817

7628

17234

7817

21500

9752

22100

10025

275

19976

9061

20669

9375

21413

9713

22100

10025

22750

10319

23268

10554

300

21734

9858

22275

10104

22750

10319

23268

10554

25277

11465

25935

11764

350

22628

10264

23105

10480

25277

11465

25935

11764

28493

12924

29138

13216

400

26679

12102

27147

12313

28493

12924

29138

13216

450

28157

12772

28763

13046

n/a

n/a

500

28493

12924

29308

13294

n/a

n/a

Shipping

Operating

Shipping

Operating

Shipping

Operating

n/a

n/a

1. Operating weight includes refrigerant and water.
2. Shipping weight includes refrigerant.
3. All weights +/- 3%.

26

RTAC-SVX01M-EN

Dimensions and Weights

Remote Evaporator Unit Weights
Table 16. Weights - condensing unit - 60 Hz
Standard Efficiency

Unit
Size
(tons)

Shipping
lb

High Efficiency

Operating
kg

lb

Shipping
kg

lb

Operating
kg

lb

kg

8292

3761

8624

3912

Aluminum or CompleteCoat™ coils

140

8359

3792

8624

3912

155

8299

3764

8624

3912

9460

4291

9931

4505

170

8304

3767

8624

3912

10610

4813

9944

4510

185

10944

4964

10226

4638

11060

5017

11512

5222

200

11179

5071

10625

4819

11443

5190

11886

5391

225

11531

5230

11997

5442

-

-

-

-

250

11623

5272

12126

5500

-

-

-

-

Copper Coils

140

10956

4970

11200

5080

10751

4877

11200

5080

155

10973

4977

11200

5080

12916

5859

13340

6051

170

10877

4934

11200

5080

13451

6101

13375

6067

185

13610

6173

13645

6189

15326

6952

15778

7157

200

13665

6198

14048

6372

15707

7125

16148

7325

225

15795

7164

16252

7372

-

-

-

-

250

15888

7207

16386

7433

-

-

-

-

1. Operating weight includes refrigerant and water.
2. Shipping weight includes nitrogen holding charge.
3. All weights +/- 3%.

Table 17.
Nominal
Tonnage

Weights - remote evaporator - 60 Hz
Standard Efficiency

High Efficiency

Shipping
Weight (lb)

Shipping
Weight (kg)

Operating
Weight (lb)

Operating
Weight (kg)

Shipping
Weight (lb)

Shipping
Weight (kg)

Operating
Weight (lb)

Operating
Weight (kg)

140

2486

1128

2730

1238

2528

1147

2805

1272

155

2525

1145

2790

1266

2556

1159

2850

1293

170

2528

1147

2805

1272

2600

1179

2920

1325

185

2556

1159

2850

1293

2797

1269

3114

1413

200

2600

1179

2920

1325

2846

1291

3192

1448

225

2797

1269

3114

1413

-

-

-

-

250

2846

1291

3192

1448

-

-

-

-

1. Operating weight includes refrigerant and water.
2. Shipping weight includes nitrogen holding charge.
3. All weights +/- 3%.

RTAC-SVX01M-EN

27

Installation - Mechanical
Location Requirements

Rigging

Noise Considerations

Lifting Procedure

Locate outdoor unit away from sound sensitive areas. If
required, install rubber vibration isolators in all water
piping and use flexible electrical conduit. Consult an
acoustical engineer for critical applications. Also refer to
Trane Engineering Bulletins for application information on
RTAC chillers.

Foundation
A base or foundation is not required if unit location is level
and strong enough to support unit’s operating weight as
listed in “General Data,” p. 9, Table 1, p. 10 through
Table 10, p. 19. Provide rigid, non-warping mounting pads
or concrete foundation of sufficient strength and mass to
support unit operating weight (including piping, and full
operating charges of refrigerant, oil and water). Once in
place, outdoor unit must be level within 1/ 4" (6 mm) over
its length and width.
Trane Company is not responsible for equipment
problems resulting from an improperly designed or
constructed foundation.
Note: To allow for cleaning under the condensing coil, it
is recommended that an opening be left between
the unit base and the concrete pad.

Clearances
Provide enough space around the outdoor unit to allow the
installation and maintenance personnel unrestricted
access to all service points. Refer to submittal drawings for
the unit dimensions. A minimum of 4 feet (1.2 m) is
recommended for compressor service. Provide sufficient
clearance for the opening of control panel doors. See
Figure 5, p. 21 through Figure 9, p. 23 in “Dimensions and
Weights,” p. 21 for minimum clearances. In all cases, local
codes which require additional clearances will take
precedence over these recommendations.

WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.

WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in unit dropping and
possibly crushing operator/technician which could
result in death or serious injury and possible
equipment or property-only damage.

WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
Important:

Do not fork lift unit.

See Table 18, p. 30 through Table 22, p. 32 for lifting
weights and Table 23, p. 33 and Table 24, p. 33 for center of
gravity (CG) dimensions.

28

RTAC-SVX01M-EN

Installation - Mechanical
Rigging
See Figure 10 through Figure 12, p. 29 for lifting point
references, Table 19 through Table 21 for lifting weights,
and unit submittals lift point dimensions.
Figure 10. Lifting the unit (packaged and remote) 15-21 foot base

Figure 11. Lifting the unit (packaged and remote) 30-36 foot base

Control Panel

W1 - near side
W2 - far side

W3 - near side
W4 - far side

W5 - near side
W6 - far side

Figure 12. Lifting the unit (packaged and remote) 39-45 foot base

RTAC-SVX01M-EN

29

Installation - Mechanical
Figure 13. Lifting the remote evap

W1 - Near Side
W2 - Far Side

W3 - Near Side
W4 - Far Side

25”
(625mm)

30”
(762mm)

SIDE VIEW

Lifting Weights Tables
Table 18.

Lifting weights (lbs) - packaged units - 60 Hz

Size
(tons)

Lifting Location
W1

W2

W3

W4

W5

W6

W7

W8

Aluminum Coils - Standard Efficiency
140

2443

2814

2622

2953

-

-

-

-

155

2446

2881

2627

2956

-

-

-

-

170

2447

2831

2633

2966

-

-

-

-

185

3244

3584

2656

2995

-

-

-

-

200

3285

3701

2741

3157

-

-

-

-

225

3943

4177

3183

3332

-

-

-

-

250

3657

4167

3518

3574

-

-

-

-

275

3376

2957

3372

2975

3377

2968

-

-

300

3470

3099

3640

3258

3814

3418

-

-

350

3389

3023

3787

3382

4187

3782

-

-

400

3448

3315

3226

3205

3123

3102

3026

2964

450

3440

3419

3324

3303

3154

3133

3032

4011

500

3373

3299

3405

3331

3452

3378

3486

3412

Aluminum Coils - High Efficiency
140

2446

2820

2630

2963

-

-

-

-

155

3114

3508

2549

2943

-

-

-

-

170

3124

3524

2561

2962

-

-

-

-

185

3469

4059

2933

3523

-

-

-

-

200

3657

4139

3135

3523

-

-

-

-

225

2581

2904

2489

2812

2400

2729

-

-

250

2607

2904

2518

2825

2433

2729

-

-

275

3272

2884

3592

3204

3915

3526

-

-

300

2974

2647

2911

2584

2801

2514

2785

2451

350

2936

2876

3003

2943

3075

3015

3143

3082

400

3373

3299

3405

3331

3452

3378

3486

3412

Aluminum Coils - Extra Efficiency
140

3124

3524

2561

2962

-

-

-

-

155

3469

4059

2933

3523

-

-

-

-

170

3657

4139

3135

3523

-

-

-

-

185

2581

2904

2489

2812

2400

2729

-

-

200

2607

2904

2518

2825

2433

2729

-

-

250

3272

2884

3592

3204

3998

3526

-

-

275

2974

2647

2911

2584

2801

2514

2785

2451

300

2936

2876

3003

2943

3075

3015

3143

3082

350

3373

3299

3405

3331

3452

3378

3486

3412

30

END VIEW

Table 18.

Lifting weights (lbs) - packaged units - 60 Hz

Size
(tons)

Lifting Location
W1

W2

W3

W4

W5

W6

W7

W8

Copper Coils - Standard Efficiency
140

2916

3405

3346

3740

-

-

-

-

155

2919

3405

3352

3744

-

-

-

-

170

2920

3412

3357

3753

-

-

-

-

185

3991

4450

3500

3929

-

-

-

-

200

4032

4567

3585

4120

-

-

-

-

225

4593

5261

4101

4784

-

-

-

-

250

4639

5261

4149

4856

-

-

-

-

275

4319

3898

4170

3772

4078

3668

-

-

300

4513

3980

4552

4169

4618

4207

-

-

350

4289

3892

4769

4363

5244

4838

-

-

400

4220

4198

4100

4078

3975

3953

3857

3835

450

4549

4526

4290

4268

3909

3887

3638

3615

500

4369

4293

4395

4319

4434

4358

4461

4385

Copper Coils - High Efficiency
140

2919

3410

3354

3743

-

-

-

-

155

3973

4374

3393

3907

-

-

-

-

170

3870

4390

3405

3925

-

-

-

-

185

4404

5144

3981

4721

-

-

-

-

200

4593

5223

4101

4784

-

-

-

-

225

3189

3625

3247

3685

3303

3745

-

-

250

3214

3625

3276

3685

3336

3745

-

-

275

4235

3898

4522

4132

4810

4420

-

-

300

3818

3527

3708

3379

3545

3216

3398

3069

350

4054

4035

3930

3911

3800

3781

3678

3659

400

4369

4293

4395

4319

4434

4358

4461

4385

Copper Coils - Extra Efficiency
140

3870

4390

3405

3925

-

-

-

-

155

4404

5144

3981

4721

-

-

-

-

170

4593

5223

4101

4784

-

-

-

-

185

3189

3625

3247

3685

3303

3745

-

-

200

3214

3625

3276

3685

3336

3745

-

-

250

4235

3898

4522

4132

4810

4420

-

-

275

3818

3527

3708

3379

3545

3216

3398

3069

300

4054

4035

3930

3911

3800

3781

3678

3659

350

4521

4293

4395

4319

4434

4358

4461

4385

RTAC-SVX01M-EN

Installation - Mechanical

Table 19.
Size
(tons)

Lifting weights (lbs) - packaged units - 50 Hz

Table 20.

Lifting Location
W1

W2

W3

W4

W5

W6

W7

W8

Size
(tons)

Lifting weights (lbs) - seismically rated units
Lifting Location
W1

Aluminum Coils - Standard Efficiency

W2

W3

W4

W5

W6

W7

W8

Aluminum Coils - Standard Efficiency

140

2445

2817

2625

2957

-

-

-

-

140

2565

2955

2753

3101

-

-

-

-

155

2556

2837

2750

2988

-

-

-

-

155

2568

3025

2758

3104

-

-

-

-

170

2554

2946

2793

3133

-

-

-

-

170

2569

2973

2765

3114

-

-

-

-

185

3287

3708

2690

3112

-

-

-

-

185

3406

3763

2789

3145

-

-

-

-

200

3302

3721

2760

3179

-

-

-

-

200

3449

3886

2878

3315

-

-

-

-

250

2972

2538

3254

2825

3446

3016

-

-

225

4140

4386

3342

3499

-

-

-

-

275

4084

3574

3618

3109

2920

2410

-

-

250

3840

4375

3694

3753

-

-

-

-

300

3340

2929

3576

3165

3814

3418

-

-

275

3545

3105

3541

3124

3546

3116

-

-

350

3043

3023

2958

2939

2869

2849

2785

2765

300

3644

3254

3822

3421

4005

3589

-

-

375

3347

3315

3135

3101

2911

2878

3005

2668

350

3558

3174

3976

3551

4396

3971

-

-

400

3311

3291

3226

3192

3123

3089

3026

2964

400

3620

3481

3387

3365

3279

3257

3177

3112

450

3612

3590

3490

3468

3312

3290

3184

4212

120

2443

2814

2622

2953

-

-

-

-

500

3542

3464

3575

3498

3625

3547

3660

3583

130

2446

2881

2627

2956

-

-

-

-

140

2448

2822

2634

2967

-

-

-

-

140

2568

2961

2762

3111

-

-

-

-

155

3230

3537

2696

3003

-

-

-

-

155

3270

3683

2676

3090

-

-

-

-

170

3253

3666

2705

3118

-

-

-

-

170

3280

3700

2689

3110

-

-

-

-

185

3589

4139

3053

3602

-

-

-

-

185

3642

4262

3080

3699

-

-

-

-

200

3703

4139

3100

3574

-

-

-

-

200

3840

4346

3292

3699

-

-

-

-

250

3376

2957

3406

2975

3446

3016

-

-

225

2710

3049

2613

2953

2520

2865

-

-

275

4322

3018

3710

3304

3998

3592

-

-

250

2737

3049

2644

2966

2555

2865

-

-

300

2974

2647

2911

2584

2831

3089

2785

2451

275

3436

3028

3772

3364

4111

3702

-

-

350

3311

3291

3204

3184

3100

2847

3005

2982

300

3123

2779

3057

2713

2941

2640

2924

2574

375

3412

3391

3297

3276

3154

3105

3679

2984

350

3083

3020

3153

3090

3229

3166

3300

3236

400

3373

3299

3389

3331

3452

3378

3486

3412

400

3542

3464

3575

3498

3625

3547

3660

3583

Aluminum Coils - High Efficiency

Aluminum Coils - High Efficiency

Copper Coils - Standard Efficiency

Aluminum Coils - Extra Efficiency

140

2918

3407

3349

3743

-

-

-

-

140

3280

3700

2689

3110

-

-

-

-

155

3030

3428

3474

3919

-

-

-

-

155

3642

4262

3080

3699

-

-

-

-

170

3027

3536

3518

3775

-

-

-

-

170

3840

4346

3292

3699

-

-

-

-

185

4033

4574

3534

4075

-

-

-

-

185

2710

3049

2613

2953

2520

2865

-

-

200

4048

4586

3604

4143

-

-

-

-

200

2737

3049

2644

2966

2555

2865

-

-

250

3550

3120

3934

3504

4190

3760

-

-

250

3436

3028

3772

3364

4198

3702

-

-

275

4632

4157

4297

3822

4078

3598

-

-

275

3123

2779

3057

2713

2941

2640

2924

2574

300

4387

4130

4488

4076

4618

4194

-

-

300

3083

3020

3153

3090

3229

3166

3300

3236

350

3803

3782

3700

3679

3591

3570

3490

3469

350

3542

3464

3575

3498

3625

3547

3660

3583

375

4351

4317

4003

3969

3637

3603

3293

3259

400

4207

4185

4087

4065

3962

3940

3844

3822

Copper Coils - High Efficiency
120

2916

3405

3346

3740

-

-

-

-

130

2919

3405

3352

3750

-

-

-

-

140

2921

3413

3358

3754

-

-

-

-

155

3863

4403

3540

3966

-

-

-

-

170

4000

4532

3549

4081

-

-

-

-

185

4525

5223

4101

4721

-

-

-

-

200

4639

5261

4149

4784

-

-

-

-

250

4319

3898

4204

3772

4127

3695

-

-

275

4387

3980

4639

4232

4893

4486

-

-

300

3845

3517

3698

3369

3535

3206

3388

3059

350

4198

4177

4078

4057

3952

3930

3833

3812

375

4521

4498

4263

4240

3882

3860

3611

3588

400

4369

4293

4395

4319

4418

4358

4461

4369

RTAC-SVX01M-EN

31

Installation - Mechanical

Table 21.

Lifting weights (lbs) - remote evaporator
condensing units - 60 Hz
Standard Efficiency

High Efficiency

Lifting Location

Lifting Location

Size
(tons)

W1

W2

W3

140

1993

2303

1899

2164

155

1996

2236

1903

2164

170

1994

2239

1903

185

2682

2920

200

2713

3025

225

3025

250

W4

W1

W2

W3

W4

1993

2236

1899

2164

1552

2844

1904

3160

2168

2551

2848

1903

3308

2011

3331

2837

3315

2215

2693

2083

3358

3025

3390

2335

2693

3430

2335

2741

-

-

-

-

3071

3430

2381

2741

-

-

-

-

140

2466

2827

2624

3039

2466

2711

2624

2950

155

2569

2827

2627

2950

3298

3710

2748

3160

170

2467

2829

2627

2954

3417

3845

2881

3308

185

3474

3913

2892

3331

3773

4399

3264

3890

200

3489

3891

2927

3358

3960

4474

3383

3890

225

3960

4514

3383

3938

-

-

-

-

250

4006

4514

3430

3938

-

-

-

-

Aluminum Coils

Copper Coils

Table 22.

Lifting weights (lbs) - remote evaporators
Standard Efficiency

High Efficiency

Lifting Location

Lifting Location

Size
(tons)

W1

W2

W3

140

621

621

622

622

155

632

631

631

631

170

632

632

632

185

639

639

200

650

650

225

699

250

711

W4

W1

W2

W3

W4

632

632

632

632

639

639

639

639

632

650

650

650

650

639

639

699

699

699

700

650

650

711

711

712

712

699

699

700

-

-

-

-

711

712

712

-

-

-

-

Aluminum Coils

32

RTAC-SVX01M-EN

Installation - Mechanical
Center of Gravity
Table 23.
Unit Size
(tons)

Table 23.

Center of gravity (in) - 60 Hz
Packaged
X

Y

Z

Remote
X

Y

Remote Evap
Z

X

Y

Z

Aluminum Coils - Standard Efficiency
140

88

45

35.5

85

45

37.25

39

30

25

155

88

45

35.5

85

45

37.25

39

30

25

170

88

45

35.5

85

45

37.25

39

30

25

185

106

44

35.5

103

44

39

53

30

25

200

106

45

35.5

107

45

39

53

30

25

225

124

45

35.5

121

45

41.5

53

30

25

250

124

45

35.5

121

45

41.5

53

30

25

275

176

42

35.5

-

-

-

-

-

-

300

199

42

35.5

-

-

-

-

-

-

350

205

42

35.5

-

-

-

-

-

-

400

234

44

35.5

-

-

-

-

-

-

450

266

44

35.5

-

-

-

-

-

-

500

274

44

35.5

-

-

-

-

-

-

Aluminum Coils - High Efficiency

Unit Size
(tons)

Center of gravity (in) - 60 Hz (continued)
Packaged
X

Y

Remote

Z

Y

Remote Evap
Z

X

Y

Z

Copper Coils - High Efficiency
140

90

45

38

88

45

37.25

39

30

25

155

108

45

38

106

45

39

53

30

25

170

108

45

38

106

45

39

53

30

25

185

126

46

38

125

46

41.5

53

30

25

200

126

45

38

124

45

41.5

53

30

25

225

170

45

38

-

-

-

-

-

-

250

170

45

38

-

-

-

-

-

-

275

201

42

38

-

-

-

-

-

-

300

219

42

38

-

-

-

-

-

-

350

234

44

38

-

-

-

-

-

-

400

273

44

38

-

-

-

-

-

-

Copper Coils - Extra Efficiency
140

108

45

38

-

-

-

-

-

-

155

126

46

38

-

-

-

-

-

-

170

126

45

38

-

-

-

-

-

-

185

170

45

38

-

-

-

-

-

-

200

170

45

38

-

-

-

-

-

-

250

201

42

38

-

-

-

-

-

-

275

219

42

38

-

-

-

-

-

-

300

234

44

38

-

-

-

-

-

-

350

273

44

38

-

-

-

-

-

-

140

88

45

35.5

85

45

37.25

39

30

25

155

106

45

35.5

103

45

39

53

30

25

170

106

45

35.5

103

45

39

53

30

25

185

124

46

35.5

122

46

41.5

53

30

25

200

124

45

35.5

121

45

41.5

53

30

25

225

167

45

35.5

-

-

-

-

-

-

250

167

45

35.5

-

-

-

-

-

-

275

203

42

35.5

-

-

-

-

-

-

300

222

42

35.5

-

-

-

-

-

-

350

234

44

35.5

-

-

-

-

-

-

400

274

44

35.5

-

-

-

-

-

-

Unit Size
(tons)

140

106

45

35.5

-

-

-

-

-

-

120

-

-

155

124

46

35.5

-

-

-

-

-

-

130

-

-

170

124

45

35.5

-

-

-

-

-

-

140

88

185

167

45

35.5

-

-

-

-

-

-

155

200

167

45

35.5

-

-

-

-

-

-

250

203

42

35.5

-

-

-

-

-

-

275

222

42

35.5

-

-

-

-

-

-

300

234

44

35.5

-

-

-

-

-

-

350

274

44

35.5

-

-

-

-

-

Table 24.

Center of gravity (in) - packaged units - 50 Hz
Standard Efficiency

Y

Z

-

88

45

35.5

-

88

45

35.5

45

35.5

88

45

35.5

88

44

35.5

106

44

35.5

170

89

45

35.5

106

45

35.5

185

106

45

35.5

124

45

35.5

200

106

45

35.5

124

45

35.5

250

182

41

35.5

177

41

35.5

-

275

172

41

35.5

202

42

35.5

300

201

42

35.5

222

42

35.5

350

235

44

35.5

234

44

35.5

375

229

44

35.5

266

44

35.5

400

234

44

35.5

274

44

35.5

Copper Coils - Standard Efficiency
140

90

45

38

88

45

37.25

39

30

25

155

90

45

38

88

45

37.25

39

30

25

170

90

45

38

88

45

37.25

39

30

25

185

108

44

38

106

44

39

53

30

25

200

108

45

38

107

45

39

53

30

25

225

126

45

38

125

45

41.5

53

30

25

250

126

45

38

125

45

41.5

53

30

25

275

174

42

38

-

-

-

-

-

-

300

195

43

38

-

-

-

-

-

-

350

204

43

38

-

-

-

-

-

-

400

235

44

38

-

-

-

-

-

-

450

261

44

38

-

-

-

-

-

-

500

273

44

38

-

-

-

-

-

-

X

Y

Z

High Efficiency
X

Aluminum Coils - Extra Efficiency

RTAC-SVX01M-EN

X

Aluminum Coils

Copper Coils
120

-

-

-

90

45

38

130

-

-

-

90

45

38

140

90

45

38

90

45

38

155

90

44

38

108

44

38

170

90

45

38

108

45

38

185

108

45

38

126

45

38

200

108

45

38

126

45

38

250

183

42

38

174

42

38

275

171

42

38

200

42

38

300

197

42

38

220

42

38

350

235

44

38

235

44

38

375

227

44

38

261

44

38

400

235

44

38

273

44

38

33

Installation - Mechanical

Isolation and Sound Emission

Mounting and Leveling

The most effective form of isolation is to locate the unit
away from any sound sensitive area. Structurally
transmitted sound can be reduced by elastomeric
vibration eliminators. Spring isolators are not
recommended for non-seismically rated applications.
Consult an acoustical engineer in critical sound
applications.

For additional reduction of sound and vibration, install the
optional elastomeric isolators, seismic isolation pads or
seismic spring isolators. See “Unit Isolation,” p. 34 for
details.

For maximum isolation effect, isolate water lines and
electrical conduit. Wall sleeves and rubber isolated piping
hangers can be used to reduce the sound transmitted
through water piping.To reduce the sound transmitted
through electrical conduit, use flexible electrical conduit.

Level the unit using the base rail as a reference.The unit
must be level within 1/4-in (6 mm) over the entire length
and width. Use shims as necessary to level the unit.

State and local codes on sound emissions should always
be considered. Since the environment in which a sound
source is located affects sound pressure, unit placement
must be carefully evaluated. Sound power levels forTrane
air-cooled Series R® chillers are available on request.

Construct an isolated concrete pad for the unit or provide
concrete footings at the unit mounting points. Mount the
unit directly to the concrete pads or footings.

Unit Isolation
Elastomeric Isolators
(Optional for units without seismic rating)
See Figure 14 and Table 25 for description of elastomeric
isolators (model number digit 33 = R or G).

Figure 14. RTAC elastomeric isolator
L
L
C
C

Isolator mounting holes
to outside, and under unit

1/2-13NC-2B

B

D
D

M

Unit Base Rail

W
W

Mounting molded in Neoprene

A

H

H

Isolator Installation Orientation

E

Table 25. RTAC elastomeric isolator details
EXT

Max Load Each
(lbs)

Color

61

1500

BROWN

62

2250

RED

63

3000

GREEN

64

4000

GRAY

Maximum
Deflection (in)

A

B

C

D

E

H

L

M

W

Type

0.50

3.00

0.50

5.00

0.56

0.38

2.75

6.25

1.60±
.25

4.63

RDP-4

\

See “Elastomeric Isolator Mounting Units without Seismic
Rating,” p. 37 for isolator selection, placement and point
weights.
1. Secure the isolators to the mounting surface using the
mounting slots in the isolator base plate. Do not fully
tighten the isolator mounting bolts at this time.
Important:

34

For proper operation, isolator must be
oriented as shown in Figure 14. Mounting
holes must be to the outside, and under the
unit.

2. Align the mounting holes in the base of the unit with
the threaded positioning pins on the top of the
isolators.
3. Lower the unit onto the isolators and secure the
isolator to the unit with a nut.
4. Level the unit carefully. Fully tighten the isolator
mounting bolts.

RTAC-SVX01M-EN

Installation - Mechanical

Unit Isolation for Seismically Rated Units
Seismic Elastomeric Isolation Pads
Elastomeric pads are provided with an isolation washer
and 3/4” free hole in the center of the plate. Isolation pads
are shipped inside the unit control panel. See Table 26 for
pad specifications.
Table 26.

Seismically rated elastomeric isolation pad

Set isolation pads on mounting surface, ensuring that all
isolator centerlines match the submittal drawing.
Place unit on pads, and secure as shown in Figure 15 using
provided isolation washer and additional hardware
obtained locally.
Figure 15. Seismic isolation pad — installed(a)

Dimension (in)
Model

Max Load

Length

Width

Height

B-36

2520

6

6

.625

Grade 8 Bolt

See Table 27 for quantity of isolation pads required and
“Seismic Isolator Mounting,” p. 44 or unit submittal for
isolator placement dimensional information.
Table 27.

Unit Base Rail

Grade 8 Washer
Fender Washer

Steel
Plate

Isolation
Washer

Isolation Pad

Seismic elastomeric isolation pad quantities
Building Support Structure

Efficiency
Unit Size (tons)

Std

High

Extra

120

-

-

-

130

-

-

-

140

8

8

8

155

8

8

10

170

8

8

10

185

8

10

10

Fender Washer
Grade 8 Washer

Nut

(Washers under support structure recommended
if job site has an I-beam or C-channel.)

(a) Not to scale.

•

With the exception of the isolation washer, hardware is
not included.

200

8

10

10

•

Recommended use of Grade 8 hardware

225

10

10

-

•

250

10

10

12

Units have a tapered base rail that requires a tapered
washer

275

10

12

12

•

Support structure may vary

300

12

12

12

350

12

12

14

375

-

-

-

400

12

14

-

450

14

-

-

500

14

-

-

• If job site has an I-beam or C-channel, a fender
washer and grade 8 washer should be installed
under the support structure.

NOTICE:
Replace Isolation Pads and Hardware
after Seismic Event!
If unit experiences a seismic event, isolation pads and
hardware must be replaced. Failure to replace isolation
pads and hardware would compromise the installation
and could result in equipment damage during future
seismic events.

RTAC-SVX01M-EN

35

Installation - Mechanical
Seismic Spring Isolators
See “Seismic Isolator Mounting,” p. 44 for mounting
locations, isolator selection and point weights.
Seismically rated isolators are optional for IBC and OSHPD
seismically rated units.

Install the optional seismically rated isolators at each
mounting location specified in section “Seismic Isolator
Mounting,” p. 44.
Figure 17.

MSSH Seismic isolator installation reference

Table 28.

("H")

("I")

Isolators are identified by part number and color as shown
in Table 28. For dimensions, see Figure 16.

("E")

CUSTOMER
EQUIPMENT

("A")

("G")

RTAC seismically rated isolator

("E")
GROMMET

Model

Rated Rated
Spring
Load Deflection Rate
(lbs) (in)
(lbs/in) Color Code

MSSH-1E-2000

2000

1.11

1800

White

MSSH-1E-2575N

2575

1.11

2313

White/Dk Purple

MSSH-1E-2990N

2990

1.11

2682

White/Dk Green

1/4 - 3/8

WASHER
("F")

Figure 16. MSSH seismically rated isolator
8

1 1/8
5/8 EQUIPMENT
CLAMP DOWN NUT

CUSTOMER
EQUIPMENT
("E")

("A")

(BASE PLATE)
3/4 DIA HOLE FOR
ATTACHMENT TO
STEEL (4 TYP)
(VIEW CUT AWAY FOR CLARITY)

2 1/4
6 1/4

("B")

("H")

("I")
13/16 DIA HOLE FOR
ATTACHMENT TO
CONCRETE (4 TYP)

("F")

2 7/8
7/8
1 1/2

7 1/4
CUSTOMER
EQUIPMENT

STEEL SHIM
(REMOVE AFTER
SPRING ADJUSTMENT)

5/8 ADJUSTING
NUT

ELASTOMERIC
SNUBBER

1/4 - 3/8
PVC
BUSHING
8
FREE &
OPERATING
HEIGHT

TOP
COMPRESSION
CUP

ELASTOMERIC
CUP

10 1/4

5 3/4

("C")

("D")

("C")

3/8 GAP

1. Set isolators on mounting surface, ensuring that all
isolator centerlines match the submittal drawing. All
isolator base plates (B) must be installed on a level
surface. Shim or grout as required, leveling all isolat(or
base plates at the same elevation.
2. Anchor all isolators to the surface using thru holes (C)
for concrete or (D) for steel as require. Welding to steel
is permitted providing the weld achieves the required
strength.
3. Remove clamp down nut (H) and washer (I). Isolators
are shipped with (2) removable spacer shims (E)
between the top plate and the housing.

CUSTOMER
EQUIPMENT

Important: These shims MUST be in place when the
equipment is positioned over the isolators.

(1/2)

SHIPPING SPACER
REMOVAL STRAP
(NOT SHOWN
IN OTHER VIEW
FOR CLARITY)
1/2 LIMIT STOP
(NOT SHOWN
IN TOP VIEW
FOR CLARITY)

(3/8)

4. With all shims (E) in place, place the equipment onto
the top plate (A) of the isolators.
5. Bolt equipment securely to the isolators using washer
(I) and nut (H).
Important: The following adjustment process can only
begin after the equipment or machine is at
its full operating weight.

8

36

RTAC-SVX01M-EN

Installation - Mechanical
6. Back off each of the (2) or (4) limit stop locknuts (F) per
isolator 1/4-3/8”.
7. Adjust each isolator in sequence by turning adjusting
nut(s) (G) one full clockwise turn at a time. Repeat this
procedure on all isolators, one at a time. check the limit
stop locknuts (F) periodically to ensure that clearance
between the washer and rubber grommet is
maintained. Stop adjustment of an isolator only when
the top plate (A) has risen just above the shim (E).
8. Remove all spacer shims (E).
9. Fine adjust isolators to level equipment.

Table 29.

Mounting locations —
60 Hz units without seismic rating (continued)
Dimension (in)

Size
(tons)

A

B

C

D

E

185

15.13

39

69

64

64

200

15.13

39

69

64

64

225

15.59

56

95

75

105

250

15.59

56

95

75

105

275

18.70

71

90

100

140

300

18.70

87

110

125

115

350

18.70

139

103

67

128

10. Adjust all limit stop locknuts (F) per isolator to obtain 3/
8” gap. the limit stop nuts must be kept at this 3/8” gap
to ensure uniform bolt loading during uplift.

400

18.70

127

127

127

127

140

15.08

48

76

76

-

Isolator Selection and Mounting Locations

155

15.08

39

69

64

64

170

15.08

39

69

64

64

185

15.59

56

95

75

105

200

15.59

56

95

75

105

250

18.70

71

90

100

140

275

18.70

87

110

125

115

300

18.70

139

103

67

128

350

18.70

128

127

127

127

Elastomeric Isolator Mounting
Units without Seismic Rating
Figure 18. Mounting locations (without seismic rating)
B

C

D

E

CONTROL PANEL (CKT 1 PANEL)

A

Table 29.
Size
(tons)

1.0”

Extra Efficiency

Table 30.
Size
(tons)

Mounting locations —
50 Hz units without seismic rating
Dimension (in)
A

B

C

D

E

Standard Efficiency

1.0”

Mounting locations —
60 Hz units without seismic rating
Dimension (in)
A

B

C

D

E

Standard Efficiency

140

15.13

46

53

53

-

155

15.13

46

53

53

-

170

15.13

46

53

53

-

185

15.08

48

76

76

-

200

15.08

48

76

76

-

250

18.70

76

90

90

75

275

18.70

76

90

90

75

300

18.70

71

90

100

140

140

15.13

46

53

53

-

375

18.70

139

103

67

128

155

15.13

46

53

53

-

350

18.70

139

103

67

128

170

15.13

46

53

53

-

400

18.70

139

103

67

128

185

15.08

48

76

76

-

200

15.08

48

76

76

-

120

15.13

46

53

53

-

225

15.08

39

69

64

64

130

15.13

46

53

53

-

250

15.08

39

69

64

64

140

15.13

46

53

53

-

275

18.70

76

90

90

75

155

15.13

48

76

76

-

300

18.70

71

90

100

140

170

15.13

48

76

76

-

15.13

39

69

64

64
64

High Efficiency

350

18.70

71

90

100

140

185

400

18.70

139

103

67

128

200

15.13

39

69

64

250

15.59

76

90

90

75

275

15.59

71

90

100

140

300

18.70

87

110

125

115

350

18.70

139

103

67

128

375

18.70

128

127

127

127

400

18.70

128

127

127

127

450

18.70

128

127

127

127

500

18.70

128

127

127

127

High Efficiency
140

15.13

46

53

53

-

155

15.13

48

76

76

-

170

15.13

48

76

76

-

RTAC-SVX01M-EN

37

Installation - Mechanical
Elastomeric Isolator Selection
Table 31.
Size
(tons)

Elastomeric isolator selections - packaged units - 60 Hz
Location
1

2

3

4

5

6

7

8

9

10

Standard Efficiency
140

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

155

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

170

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

185

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

200

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

225

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

250

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

275

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

300

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

350

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

400

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

450

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

500

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

High Efficiency
140

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

155

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

170

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

185

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

200

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

225

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

250

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

275

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

300

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

350

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

400

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Extra Efficiency

38

140

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

155

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

170

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

185

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

200

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

250

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

275

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

300

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

350

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

RTAC-SVX01M-EN

Installation - Mechanical

Table 32.
Size
(tons)

Elastomeric isolator selections - packaged units - 50 Hz
Location
1

2

3

4

5

6

7

8

9

10

Standard Efficiency
140

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

155

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

170

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

185

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

200

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

250

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

275

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

300

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

350

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

400

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

High Efficiency
120

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

130

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

140

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

155

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

170

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

-

-

185

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

200

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

Red 62

250

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

275

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

300

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

350

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

400

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

Gray 64

6

7

8

9

10

Table 33.
Size
(tons)

Elastomeric isolator selections - remote units - 60 Hz
Location
1

2

3

4

5
Standard Efficiency

140

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

155

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

170

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

185

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

200

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

225

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

250

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

High Efficiency
140

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

155

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

170

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

-

-

185

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

200

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

Brown 61

RTAC-SVX01M-EN

39

Installation - Mechanical

Point Weights (Units without Seismic Rating)
See Table 34, p. 40 through Table 36, p. 43 for point
weights of units that are NOT seismically rated.
Table 34.
Size
(tons)

See Table 40, p. 46 for seismically rated units (unit model
number digit 13 = S or E).

Point weights (lbs) - packaged units - 60 Hz- units not seismically rated
Isolator Location
W1

W2

W3

W4

W5

W6

W7

W8

W9

W10

Aluminum Coils - Standard Efficiency
140

1402

1450

1383

1430

1361

1408

1333

1379

-

-

155

1402

1450

1383

1430

1361

1408

1333

1379

-

-

170

1461

1450

1383

1430

1361

1408

1339

1386

-

-

185

1657

1673

1734

1638

1564

1584

1519

1530

-

-

200

1674

1733

1646

1701

1604

1658

1561

1616

-

-

225

1521

1571

1503

1554

1472

1522

1443

1494

1413

1473

250

1539

1601

1522

1584

1493

1522

1465

1527

1438

1500

275

1925

2188

1887

2148

1870

2082

1787

2062

1750

1986

300

1936

2173

1974

2198

1994

2230

2029

2266

2080

2334

350

1907

2144

1977

2213

2065

2301

2163

2399

2300

2536

400

2744

2758

2667

2646

2584

2564

2531

2510

2428

2422

450

2812

2774

2791

2753

2770

2733

2750

2712

2729

2569

500

2777

2719

2787

2744

2812

2768

2836

2792

2860

2817

Aluminum Coils - High Efficiency
140

1402

1450

1383

1430

1361

1408

1339

1387

-

-

155

1588

1648

1565

1609

1505

1558

1465

1507

-

-

170

1657

1652

1565

1622

1515

1579

1465

1530

-

-

185

1419

1523

1405

1510

1381

1496

1358

1466

1335

1400

200

1497

1552

1479

1539

1446

1496

1417

1466

1389

1440

225

1661

1686

1649

1674

1629

1654

1613

1639

1591

1617

250

1661

1686

1649

1674

1629

1654

1613

1639

1591

1617

275

1829

2070

1891

2134

1960

2201

2093

2282

2193

2395

300

2147

2392

2120

2391

2087

2357

2049

2319

2014

2284

350

2647

2629

2535

2517

2452

2434

2512

2380

2294

2300

400

2744

2705

2773

2729

2797

2754

2822

2778

2846

2802

Aluminum Coils - Extra Efficiency
140

1657

1652

1565

1622

1515

1579

1465

1530

-

-

155

1419

1523

1405

1510

1381

1496

1358

1466

1335

1400

170

1497

1552

1479

1539

1446

1496

1417

1466

1389

1440

185

1661

1686

1649

1674

1629

1654

1613

1639

1591

1617

200

1661

1686

1649

1674

1629

1654

1613

1639

1591

1617

250

1829

2070

1891

2134

1960

2201

2093

2282

2193

2395

275

2147

2392

2120

2391

2087

2357

2049

2319

2014

2284

300

2647

2629

2535

2517

2452

2434

2512

2380

2294

2300

350

2744

2705

2773

2729

2797

2754

2822

2778

2846

2802

40

RTAC-SVX01M-EN

Installation - Mechanical
Table 34.

Point weights (lbs) - packaged units - 60 Hz- units not seismically rated (continued)
Isolator Location

Size
(tons)

W1

W2

W3

W4

140

1658

1720

1675

1737

1695

155

1658

1720

1675

1737

1695

170

1658

1720

1675

1737

185

2025

2061

2012

200

2042

2121

2040

225

1868

1954

250

1891

275
300

W5

W6

W7

W8

W9

W10

1757

1715

1777

-

-

1757

1715

1777

-

-

1695

1757

1715

1776

-

-

2052

1997

2098

1984

2024

-

-

2114

2038

2129

2036

2110

-

-

1865

1945

1861

1951

1859

1049

1857

1947

1961

1890

1960

1887

1957

1885

1956

1883

1953

2505

2768

2458

2700

2358

2589

2215

2501

2130

2384

2550

2787

2458

2786

2547

2784

2545

2782

2543

2798

350

2467

2704

2548

2785

2651

2888

2765

3003

2946

3163

400

3474

3498

3372

3350

3272

3207

3207

3184

3082

3077

450

3576

3602

3465

3468

3332

3199

3199

3202

3066

3069

500

3552

3513

3575

3536

3597

3620

3620

3580

3642

3552

Copper Coils - Standard Efficiency

Copper Coils - High Efficiency
140

1658

1720

1675

1737

1695

1757

1715

1777

-

-

155

1956

2029

1958

2022

1949

2011

1928

2001

-

-

170

1965

2040

1958

2035

1949

2098

1939

2014

-

-

185

1788

1914

1792

1916

1796

1951

1800

1924

1804

1928

200

1868

1928

1865

1936

1861

1932

1859

1928

1853

1928

225

2077

2125

2090

2135

2105

2152

2118

2166

2137

2185

250

2077

2125

2090

2135

2105

2152

2118

2166

2137

2185

275

2410

2652

2458

2700

2519

2761

2587

2828

2720

2923

300

2825

3097

2766

3037

2690

2962

2605

2876

2526

2798

350

3377

3357

3241

3221

3139

3074

3074

3054

2948

2946

400

3531

3498

3561

3521

3583

3606

3606

3566

3628

3588

Copper Coils - Extra Efficiency
140

1965

2040

1958

2035

1949

2098

1939

2014

-

-

155

1788

1914

1792

1916

1796

1951

1800

1924

1804

1928

170

1868

1928

1865

1936

1861

1932

1859

1928

1853

1928

185

2077

2125

2090

2135

2105

2152

2118

2166

2137

2185

200

2077

2125

2090

2135

2105

2152

2118

2166

2137

2185

250

2410

2652

2458

2700

2519

2761

2587

2828

2720

2923

275

2825

3097

2766

3037

2690

2962

2605

2876

2526

2798

300

3377

3357

3241

3221

3139

3074

3074

3054

2948

2946

350

3531

3498

3561

3521

3583

3606

3606

3566

3628

3588

RTAC-SVX01M-EN

41

Installation - Mechanical
Table 35.
Size
(tons)

Point weights (lbs) - packaged units - 50 Hz
Isolator Location
W1

W2

W3

W4

W5

W6

W7

W8

W9

W10

Aluminum Coils - Standard Efficiency
140

1402

1450

1383

1430

1361

1408

1333

1379

-

-

155

1461

1457

1444

1435

1414

1411

1389

1386

-

-

170

1402

1503

1444

1491

1431

1478

1418

1465

-

-

185

1674

1733

1646

1699

1586

1645

1532

1596

-

-

200

1674

1742

1662

1716

1621

1675

1580

1634

-

-

250

1936

1642

1963

2356

1997

1703

2030

1736

2059

1764

275

2059

2353

1973

2266

1870

2201

1787

2062

1683

1986

300

1936

2104

1890

2198

1994

2196

2029

2266

2080

2334

350

2539

2520

2451

2421

2368

2349

2320

2301

2230

2300

375

2437

2386

2491

2440

2519

2678

2562

2511

2620

2569

400

2744

2758

2667

2646

2584

2564

2531

2510

2428

2422

Aluminum Coils - High Efficiency
120

1402

1450

1383

1430

1361

1408

1333

1379

-

-

130

1402

1450

1383

1430

1361

1408

1333

1379

-

-

140

1402

1450

1383

1430

1361

1408

1339

1387

-

-

155

1657

1648

1617

1622

1585

1579

1541

1537

-

-

170

1597

1712

1629

1684

1586

1645

1541

1596

-

-

185

1468

1552

1455

1539

1446

1522

1417

1494

1389

1472

200

1521

1571

1503

1554

1472

1522

1443

1494

1414

1473

250

1926

2187

1888

2685

1833

2100

1786

2063

2000

2015

275

1907

2174

1973

2209

2022

2273

2093

2244

2193

2444

300

2147

2417

2120

2391

2087

2357

2049

2319

2014

2284

350

2392

2340

2522

2470

2591

2538

2695

2643

2837

2784

375

2755

2718

2735

2698

2715

2678

2695

2658

2674

2637

400

2744

2705

2773

2729

2797

2754

2822

2779

2846

2802

Copper Coils - Standard Efficiency
140

1658

1720

1675

1737

1695

1757

1715

1777

-

-

155

1717

1728

1737

1742

1748

1750

1765

1775

-

-

170

1717

1774

1737

1798

1765

1827

1893

1855

-

-

185

2042

2121

2034

2112

2020

2038

2006

2090

-

-

200

2056

2130

2055

2130

2055

2112

2054

2129

-

-

250

2078

2332

2089

1669

2118

2385

2146

2413

2170

2437

275

2638

2933

2529

2805

2358

2653

2215

2501

2079

2384

300

2462

2718

2477

2732

2495

2784

2545

2782

2543

2798

350

3158

3137

3039

3018

2951

2894

2894

2873

2784

2779

375

3576

3579

3291

3255

3083

2948

2948

2912

2689

2690

400

3538

3498

3372

3350

3272

3207

3207

3184

3082

3077

Copper Coils - Standard Efficiency
120

1658

1720

1675

1737

1695

1757

1715

1777

-

-

130

1658

1720

1675

1737

1695

1757

1715

1777

-

-

140

1658

1720

1675

1737

1695

1757

1715

1777

-

-

155

2025

2040

2012

2035

2009

2033

2007

2031

-

-

170

2025

2100

3034

2098

2020

2038

2016

2090

-

-

185

1839

1954

1842

1945

1846

1920

1859

1956

1857

1961

200

1891

1961

1890

1960

1887

1957

1885

1956

1883

1953

250

2506

2767

2418

2134

2321

2588

2224

2491

2170

2437

275

2488

2740

2529

2805

2581

2833

2639

2828

2720

2972

300

2825

3097

2766

3037

2690

2962

2605

2876

2526

2798

350

3000

2934

3184

3118

3281

3214

3429

3362

3628

3562

375

3576

3579

3442

3445

3309

3176

3176

3179

3043

3046

400

3445

3396

3516

3467

3587

3538

3658

3609

3628

3681

42

RTAC-SVX01M-EN

Installation - Mechanical
Table 36.

Point weights (lbs) - condensing units - 60 Hz
Isolator Location

Size (tons)

1

2

3

4

5

6

7

8

9

10

Aluminum Coils - Standard Efficiency
140

1150

1183

1095

1128

1032

1065

969

1002

-

-

155

1150

1183

1095

1128

1032

1065

969

1002

-

-

170

1150

1183

1095

1128

1032

1065

969

1002

-

-

185

1381

1384

1325

1331

1241

1246

1156

1162

-

-

200

1397

1437

1351

1391

1279

1318

1206

1246

-

-

225

1251

1307

1222

1279

1172

1229

1126

1190

1081

1140

250

1274

1312

1246

1283

1196

1233

1149

1190

1103

1140

Aluminum Coils - High Efficiency
140

1150

1183

1095

1128

1032

1065

969

1002

-

-

155

1321

1361

1270

1301

1190

1230

1109

1149

-

-

170

1321

1361

1270

1314

1190

1230

1109

1149

-

-

185

1175

1267

1151

1242

1107

1199

1067

1159

1027

1118

200

1251

1295

1222

1259

1172

1207

1122

1159

1081

1118

Copper Coils - Standard Efficiency
140

1406

1454

1388

1435

1366

1414

1345

1392

-

-

155

1406

1454

1388

1435

1366

1414

1345

1392

-

-

170

1406

1454

1388

1435

1366

1414

1345

1392

-

-

185

1749

1772

1718

1744

1675

1700

1631

1656

-

-

200

1768

1825

1745

1805

1713

1772

1680

1740

-

-

225

1622

1697

1608

1686

1587

1665

1568

1645

1549

1625

250

1644

1702

1633

1690

1611

1668

1591

1648

1571

1628

Copper Coils - High Efficiency
140

1406

1454

1388

1435

1366

1414

1345

1392

-

-

155

1689

1749

1664

1714

1624

1673

1583

1644

-

-

170

1689

1749

1664

1727

1624

1695

1583

1644

-

-

185

1546

1657

1537

1649

1523

1634

1509

1621

1495

1607

200

1622

1686

1608

1666

1587

1642

1568

1621

1549

1599

RTAC-SVX01M-EN

43

Installation - Mechanical
Seismic Isolator Mounting
Figure 19. Mounting locations — seismic spring isolators or seismic elastomeric pads
B

CONTROL PANEL
(CKT 1 PANEL)

A

Table 37.
Size
(tons)

C

D

C

G

1.19”

4

6

8

10

12

14

1

3

5

7

9

11

13

Table 38.

Dimension (in)
B

F

2

Mounting locations —
60 Hz units with seismic rating
A

E

D

E

F

G

Size
(tons)

1.19”

Mounting locations —
50 Hz units with seismic rating
Dimension (in)
A

B

Standard Efficiency

C

D

E

F

G

Standard Efficiency

140

17

46

53

53

-

-

-

140

17

46

53

53

-

-

-

155

17

46

53

53

-

-

-

155

17

46

53

53

-

-

-

170

17

46

53

53

-

-

-

170

17

46

53

53

-

-

-

185

17

48

76

76

-

-

-

185

17

48

76

76

-

-

-

200

17

48

76

76

-

-

-

200

17

48

76

76

-

-

-

225

17

39

69

64

64

-

-

250

17

76

90

90

75

-

-

250

17

39

69

64

64

-

-

275

17

76

90

90

75

-

-

275

17

76

90

90

75

-

-

300

17

80.25

80.25

80.25

80.25

80.25

-

300

17

80.25

80.25

80.25

80.25

80.25

-

375

17

87.5

87.5

87.5

87.5

87.5

-

350

17

80.25

80.25

80.25

80.25

80.25

-

350

17

87.5

87.5

87.5

87.5

87.5

-

400

17

87.5

87.5

87.5

87.5

87.5

-

400

17

87.5

87.5

87.5

87.5

87.5

-

450

17

84.85

84.85

84.85

84.85

92.75

78

500

17

84.85

84.85

84.85

84.85

92.75

78

High Efficiency

High Efficiency
120

17

46

53

53

130

17

46

53

53

140

17

46

53

53

-

-

-

140

17

46

53

53

-

-

-

155

17

48

76

76

-

-

-

155

17

48

76

76

-

-

-

170

17

48

76

76

-

-

-

170

17

48

76

76

-

-

-

185

17

39

69

64

64

-

-

185

17

39

69

64

64

-

-

200

17

39

69

64

64

-

-

200

17

39

69

64

64

-

-

225

17

56

95

75

105

-

-

250

17

76

90

90

75

-

-

250

17

56

95

75

105

-

-

275

17

80.25

80.25

80.25

80.25

80.25

-

275

17

80.25

80.25

80.25

80.25

80.25

-

300

17

87.5

87.5

87.5

87.5

87.5

-

300

17

87.5

87.5

87.5

87.5

87.5

-

350

17

87.5

87.5

87.5

87.5

87.5

-

350

17

87.5

87.5

87.5

87.5

87.5

-

375

17

84.85

84.85

84.85

84.85

92.75

78

400

17

84.85

84.85

84.85

84.85

92.75

78

400

17

84.85

84.85

84.85

84.85

92.75

78

Extra Efficiency
140

17

48

76

76

-

-

-

155

17

39

69

64

64

-

-

170

17

39

69

64

64

-

-

185

17

56

95

75

105

-

-

200

17

56

95

75

105

-

-

250

17

80.25

80.25

80.25

80.25

80.25

-

275

17

87.5

87.5

87.5

87.5

87.5

-

300

17

87.5

87.5

87.5

87.5

87.5

-

350

17

84.85

84.85

84.85

84.85

92.75

78

44

RTAC-SVX01M-EN

Installation - Mechanical
Seismic Spring Isolator Selection
Table 39.
Size
(tons)

Seismic spring isolator selections (MSSH-1E-xxxx)
Location
1

2

3

4

5

6

7

8

9

10

11

12

13

14

Standard Efficiency
140

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

155

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

170

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

185

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

-

-

-

-

200

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

-

-

-

-

225

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

250

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

-

-

275

2990N

2990N

2990N

2990N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

-

-

300

2990N

2990N

2990N

2990N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

350

2990N

2990N

2990N

2990N

2575N

2575N

2575N

2575N

2575N

2575N

2000

2000

-

-

400

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

-

-

450

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

500

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N
-

High Efficiency
140

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

155

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

170

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

185

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

200

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

225

2575N

2575N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

-

-

250

2575N

2575N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

-

-

275

2990N

2990N

2990N

2990N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

300

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

350

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

-

-

400

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

140

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

-

-

155

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

170

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

-

-

-

-

185

2575N

2575N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

-

-

200

2575N

2575N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

-

-

250

2990N

2990N

2990N

2990N

2575N

2575N

2575N

2575N

2000

2000

2000

2000

-

-

275

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

2575N

-

-

300

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

-

-

350

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

2990N

Extra Efficiency

RTAC-SVX01M-EN

45

Installation - Mechanical
Point Weights (Units with Seismic Rating)
Table 40.

Point weights (lbs) - seismically rated units
Isolator Location

Size
(tons)

W1

W2

W3

W4

W5

140

1465

1515

1445

1494

1422

1471

1393

1441

-

155

1472

1522

1452

1501

1429

1478

1400

1448

-

170

1534

1523

1452

1502

1429

1478

1406

1455

185

1740

1757

1821

1720

1642

1663

1595

200

1758

1820

1728

1786

1684

1741

1639

225

1597

1650

1578

1632

1546

1598

250

1616

1681

1598

1663

1568

275

2360

2250

2251

2140

300

2387

2287

2220

2120

350

2357

2254

2224

400

2322

2410

450

2143

500

1738

W6

W7

W8

W9

W10

W11

W12

W13

W14

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1607

-

-

-

-

-

-

1697

-

-

-

-

-

-

1515

1569

1484

1547

-

-

-

-

1598

1538

1603

1510

1575

-

-

-

-

2122

2011

1993

1882

1885

1774

-

-

-

-

2008

1909

1772

1673

1607

1508

1442

1343

-

-

2122

2058

1954

1871

1768

1741

1638

1611

1507

-

-

2280

2368

2239

2327

2197

2286

2156

2245

2115

2203

-

-

2223

2111

2191

2079

2159

2015

2095

1951

2031

1918

1999

1887

1967

1821

1814

1896

1937

2019

2050

2132

2163

2245

2276

2358

2389

2471

Aluminum Coils - Standard Efficiency

Aluminum Coils - High Efficiency
140

1471

1522

1451

1501

1428

1478

1405

1455

-

-

-

-

-

-

155

1667

1730

1643

1689

1580

1636

1538

1582

-

-

-

-

-

-

170

1740

1735

1643

1703

1591

1658

1538

1606

-

-

-

-

-

-

185

1490

1599

1475

1586

1450

1571

1426

1539

1402

1470

-

-

-

-

200

1572

1630

1553

1616

1518

1571

1488

1539

1458

1512

-

-

-

-

225

1701

1846

1683

1828

1652

1796

1627

1771

1592

1737

-

-

-

-

250

1701

1846

1683

1828

1652

1796

1627

1772

1592

1737

-

-

-

-

275

2293

2193

2153

2054

1976

1877

1780

1680

1642

1543

1504

1406

-

-

300

2308

2204

2181

2077

2055

1950

1927

1824

1801

1697

1674

1571

-

-

350

2218

2302

2179

2263

2139

2223

2100

2184

2060

2144

2021

2105

-

-

400

2043

2125

2043

2124

2043

2123

2041

2122

2039

2121

2038

2120

2037

2119

140

1736

1731

1640

1699

1587

1654

1535

1603

-

-

-

-

-

-

155

1491

1601

1477

1587

1451

1572

1427

1541

1403

1471

-

-

-

-

170

1569

1627

1551

1613

1516

1568

1486

1537

1456

1510

-

-

-

-

185

1701

1846

1683

1828

1651

1796

1627

1772

1592

1737

-

-

-

-

200

1697

1850

1679

1831

1648

1800

1623

1776

1589

1741

-

-

-

-

250

2292

2194

2153

2054

1976

1877

1779

1681

1642

1543

1504

1405

-

-

275

2307

2203

2181

2077

2055

1951

1928

1824

1801

1697

1674

1570

-

-

300

2218

2302

2178

2262

2139

2223

2099

2184

2059

2145

2021

2105

-

-

350

2044

2125

2043

2124

2042

2124

2041

2122

2039

2120

2038

2119

2037

2118

Aluminum Coils - Extra Efficiency

46

RTAC-SVX01M-EN

Installation - Mechanical

Drainage

Evaporator Water Piping

Provide large capacity drain for use during shutdown or
repair. Evaporator is provided with drain connection. All
local and national codes apply. Vent on top of evaporator
waterbox prevents vacuum by allowing air into evaporator
for complete drainage.

RTAC units are available with 2- or 3-pass evaporator
configurations.

Figure 20. Evaporator pass configurations - 2 compressor units
Water Connections

2-Pass
Evaporator

Control Panel End

(see End View for details)

Outlet Water
Connection
Inlet Water
Connection

Top View
(Condenser removed for clarity)

End View
(Non-control panel end)

3-Pass
Evaporator

Control Panel End

Inlet Water
Connection

Outlet Water
Connection

Figure 21.

Top View
(Condenser removed for clarity)

Evaporator pass configurations - 3 or 4 compressor units
Water Connections

2-Pass Evaporator
Circuit 2 Control Panel

Circuit 1 Control Panel

(see End View for details)

Top View
(Condenser removed for clarity)

Outlet
Inlet

End View
(Circuit 1 control panel end
Panel removed for clarity)

Circuit 2 Control Panel

Circuit 1 Control Panel

3-Pass Evaporator

Inlet Water
Connection

Outlet Water
Connection

Top View
(Condenser removed for clarity)

RTAC-SVX01M-EN

47

Installation - Mechanical
Thoroughly flush all water piping to the unit before making
the final piping connections to the unit.
Components and layout will vary slightly, depending on
the location of connections and the water source.

NOTICE:
Evaporator Damage!
The chilled water connections to the evaporator are to
be “victaulic” type connections. Do not attempt to
weld these connections, as the heat generated from
welding can cause microscopic and macroscopic
fractures on the cast iron waterboxes that can lead to
premature failure of the waterbox. To prevent damage
to chilled water components, do not allow evaporator
pressure (maximum working pressure) to exceed 150
psig (10.5 bar).
Provide shutoff valves in gauge lines to isolate them from
system when not in use. Use rubber vibration eliminators
to prevent vibration transmission through water lines. If
desired, install thermometers in lines to monitor entering
and leaving water temperatures. Install a balancing valve
in leaving water line to control water flow balance. Install
shutoff valves on both entering and leaving water lines so
evaporator can be isolated for service.

NOTICE:
Evaporator Damage!
To prevent evaporator damage, pipe strainers must be
installed in the water supplies to protect components
from water born debris. Trane is not responsible for
equipment-only-damage caused by water born debris.
“Piping components” include all devices and controls
used to provide proper water system operation and unit
operating safety.These components and their general
locations are given below.

Entering Chilled Water Piping
•
•
•
•
•
•

Air vents (to bleed air from system).
Water pressure gauges with shutoff valves.
Vibration eliminators.
Shutoff (isolation) valves.Thermometers (if desired).
Clean-out tees.
Pipe strainer.

Leaving Chilled Water Piping
•
•
•

Air vents (to bleed air from system).
Water pressure gauges with shutoff valves.
Vibration eliminators.

•
•
•
•

Shutoff (isolation) valves.
Thermometers.
Clean-out tees.
Balancing valve.

48

Evaporator Drain
A 1/2” drain connection is located under outlet end of
evaporator waterbox for drainage during unit servicing. A
shutoff valve must be installed on drain line.

Evaporator Flow Switch
The flow switch is factory-installed and programmed
based on the operating conditions submitted with the
order.The leaving evaporator temperature, fluid type and
fluid concentration affect the selected flow switch. If the
operating conditions on the job site change, the flow
switch may need to be replaced.
The sensor head includes 3 LEDs, two yellow and one
green.Wait 15 seconds after power is applied to the sensor
before evaluating LEDs for flow status. When wired
correctly and flow is established, only the green LED
should be lit. Following are the LED indicators:
•

Green ON, both yellow OFF — Flow

•

Green and outside yellow ON — No Flow

•

Center yellow ON continuously — Miswire

Factory installed jumper wire W3 must be removed if
using auxiliary contacts and/or additional proof of flow.
See schematics in RTAC-SVE01*-EN for more details.

NOTICE:
Equipment Damage!
Incorrect wiring of auxiliary contacts could result in
equipment damage.
Note: Use caution when connecting auxiliary contacts.
Terminals 1TB6-3 and 1TB6-5 are to be used for
field connections. Inadvertent use of 1TB6-5 and
1TB6-4 will result in a FALSE FLOW indication.
If using auxiliary flow sensing, both yellow LEDs come on
initially when flow is stopped. Center yellow LED will turn
off after approximately 7 seconds. LED indicators are
otherwise same as indicated above.

NOTICE:
Proper Water Treatment!
The use of untreated or improperly treated water in this
equipment could result in scaling, erosion, corrosion,
algae or slime. It is recommended that the services of a
qualified water treatment specialist be engaged to
determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated
water, or saline or brackish water.
Important:

If using an acidic commercial flushing
solution, construct a temporary bypass
around the unit to prevent damage to
internal components of the evaporator.

RTAC-SVX01M-EN

Installation - Mechanical
Dirt, scale, products of corrosion and other foreign
material will adversely affect heat transfer between the
water and system components. Foreign matter in chilled
water system can also increase pressure drop and reduce
water flow. Proper water treatment must be determined
locally, depending on system and local water
characteristics.
Neither salt nor brackish water is recommended. Use of
either will lead to a shortened life to an indeterminable
degree.TheTrane Company encourages the service of a
reputable water treatment specialist, familiar with local
water conditions, to assist in this determination and in
establishment of a proper water treatment program.
Using untreated or improperly treated water in these units
may result in inefficient operation and possible tube
damage. Consult a qualified water treatment specialist to
determine whether treatment is needed.

Indexing Flow Switch
To properly index flow switch, the following requirements
must be met:
•

Dot must be at a position no greater than 90° off Index.

•

Torque must be between 22 ft-lb min and 74 ft-lb max.

•

A minimum distance of 5x pipe diameter must be
maintained between flow switch and any bends,
valves, changes in cross sections, etc.

Figure 22. Proper flow switch indexing

Top View
Flow
Index

RTAC-SVX01M-EN

The flow switch
must have the dot
in the shaded area
to the left of this line
for proper indexing
(±90° off Index)

49

Installation - Mechanical

Figure 23. Evaporator water pressure drop— 2-pass evaporator —120-250 ton
100.00

50.00

140S, 120H(50Hz)

Pressure Drop ( H2O)
Pressure Drop (ft H2O)

155S, 130H(50Hz)
170S, 140H
185S, 155H
200S, 170H
10.00

225S, 185H
250S(60Hz), 200H,
225H, 250H(60Hz)

5.00

1.00
100

200

300

400

500

700

1000

Flow Rate (GPM)
Fl
R t (GPM)

Figure 24. Evaporator water pressure drop — 2-pass evaporator — 250-500 ton
100.00

50.00

250S(50Hz)

Pressure Drop ( H2O)
Pressure Drop (ft H2O)

275S
300S, 250H(50Hz)
350S(60Hz), 275H, 300H
350S(50Hz)

10.00

400S, 350H
375S(50Hz)
450S(60Hz), 375H(50Hz)

5.00

500S(60Hz), 400H

1.00
100

200

300

400

500

700

1000

Flow Rate
(GPM)
Flow
Rate (GPM)

50

RTAC-SVX01M-EN

Installation - Mechanical

Figure 25. Evaporator water pressure drop — 3-pass evaporator — 140-250T
100.00

50.00
140S, 120H(50Hz)

Pressure Drop (ft H2O)

155S, 130H(50Hz)

170S, 140H
10.00

185S, 155H

200S, 170H

5.00
225S, 185H

250S(60Hz), 200H,
225H, 250H(60Hz)

1.00

200

100

300

400

500

600

700

Flow Rate (GPM)

Figure 26. Evaporator water pressure drop — 3-pass evaporator — 250-500T
80.00
60.00
40.00

250S(50Hz)

20.00

275S

Pressure Drop (ft H2O)

300S, 250H(50Hz)
350S(60Hz), 275H, 300H
10.00

350S(50Hz)
400S, 350H
375S(50Hz)

5.00

450S(60Hz), 375H(50Hz)
500S(60Hz), 400H

1.00
100

200

300

400

500

600

800

1000

1200

Flow Rate (GPM)

RTAC-SVX01M-EN

51

Installation - Mechanical

Water Pressure Gauges
Figure 27. Suggested piping for typical RTAC evaporator

Flow Switch
(Factory Installed)

Install field-supplied pressure components as shown in
Figure 27, p. 52. Locate pressure gauges or taps in a
straight run of pipe; avoid placement near elbows, etc. Be
sure to install the gauges at the same elevation on each
shell if the shells have opposite-end water connections.
Note: Once the unit is installed at a site, one vertical or
one diagonal unit support can be permanently
removed if it creates an obstruction for water
piping.
To read manifolded pressure gauges, open one valve and
close the other (depending upon the reading desired).This
eliminates errors resulting from differently calibrated
gauges installed at unmatched elevations.

Water Pressure Relief Valves
NOTICE:
Evaporator Damage!
To prevent shell damage, install pressure relief valves in
the evaporator water system.
Install a water pressure relief valve in the evaporator inlet
piping between the evaporator and the inlet shutoff valve,
as shown in Figure 27, p. 52. Water vessels with closecoupled shutoff valves have a high potential for
hydrostatic pressure buildup on a water temperature
increase. Refer to applicable codes for relief valve
installation guidelines.

52

RTAC-SVX01M-EN

Installation - Mechanical

Freeze Avoidance
One or more of the ambient freeze avoidance methods in
Table 41 must be used to protect the RTAC chiller from
ambient freeze damage.
Table 41.

Note: A secondary set of pump interlock is strongly
recommended, but not required.

RTAC freeze avoidance methods

Method

Protects to
ambient
temperature

Notes
• Heaters alone will provide low ambient protection down to -20°F (-29°C), but will NOT
protect the evaporator from freezing as a result of charge migration. Therefore, it is
required that water pump control be used in conjunction with heaters.
• Heaters are factory-installed on the evaporator and water piping and will protect them from freezing
• Install heat tape on all water piping, pumps, and other components that may be damaged if exposed
to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat
tape selection should be based on the lowest expected ambient temperature.
• CH530 controller can start the pump when freezing conditions are detected. For this option the pump
must to be controlled by the RTAC unit and this function must be validated.
• Water circuit valves need to stay open at all times.
• Water pump control and heater combination will protect the evaporator down to any
ambient temperature provided power is available to the pump and the CH530 controller.
This option will NOT protect the evaporator in the event of a power failure to the chiller
unless backup power is supplied to the necessary components.
• When no chiller operation is possible and the pump is already off, CH530 pump control for freeze
protection will command the pump to turn:
ON if liquid level > -0.83” AND evap sat temp < LWTC for 30°F-sec (17°C-sec)
OFF again if evaporator saturated temperature > LWTC OR liquid level < -0.83” for 30 minutes.
ON if entering OR leaving water temperature< LWTC for 30°F-sec (17°C-sec)
OFF again if water temperature > LWTC for 30 min
(where LWTC is leaving water temperature cutout)

Water Pump Control
AND Heaters

Down to -20°F

Freeze Inhibitor

• Freeze protection can be accomplished by adding sufficient glycol to protect against freezing below
Varies.
the lowest ambient expected.
See “Low
Evaporator
• Use of glycol type antifreeze reduces the cooling capacity of the unit and must be
Refrigerant Cutout,
considered in the design of the system specifications.
Glycol
Recommendations,”
p. 54

Drain Water Circuit

Below -20°F

• Shut off the power supply to the unit and to all heaters.
• Purge the water circuit.
• Blow out the evaporator to ensure no liquid is left in the evaporator.

NOTICE:
Evaporator Damage!
If insufficient concentration or no glycol is used, the
evaporator water flow must be controlled by the CH530
AND heaters must be used to avoid catastrophic
damage to the evaporator due to freezing. It is the
responsibility of the installing contractor and/or the
customer to ensure that a pump will start when called
upon by the chiller controls.
Even with water pump control, a power loss of as little
as 15 minutes under freezing conditions can damage
the evaporator. Only the proper addition of freeze
inhibitor or complete drainage of the water circuit can
ensure no evaporator damage in the event of a power
failure. See Table 42, p. 54 for correct concentration of
glycol.

RTAC-SVX01M-EN

53

Installation - Mechanical

2. LRTC is 4 deg F below freeze point.

Procedure
1. Is operating condition contained within Table 42,
p. 54? If no, see “Specials,” p. 54.
2. For leaving fluid temperatures greater than 40 deg F,
use settings for 40 deg F.
3. Select operating conditions from Table 42.
4. Read off recommended % glycol.
5. Go to Table 43, p. 55 using the % glycol determined
above.
Important: Additional glycol beyond the
recommendations will adversely effect unit
performance. Unit efficiency and saturated
evaporator temperature will be reduced.
For some operating conditions this effect
can be significant.
6. If additional glycol is used, then use the actual % glycol
to establish the low refrigerant cutout setpoint.
7. The minimum low refrigerant cutout setpoint allowed
is -5 deg F.The minimum is established by the
solubility limits of the oil in the refrigerant.

Specials
Any of the following conditions are considered special
applications that must be calculated by engineering:
1. Freeze inhibitor other than ethylene glycol, propylene
glycol, calcium chloride or methanol.
2. Fluid deltaT outside the range 4 to 16 deg F.
3. Unit configuration other than Standard, Standard with
extra pass, and Premium.
4. % Glycol greater than maximum in column in Table 43.

Glycol recommendations
Ethylene Glycol

DT
Leaving Water Temperature °F (°C)

1. Solution freeze point is 4 deg F below operating point
saturation temperature.

Table 42.
°F

4

6

8

10

12

14

16

°C

15

-14

-13

-12

-11

-10

-9

38 (3)

--

5

5

5

5

6

--

34 (1)

--

11

11

11

12

--

--

30 (-1)

--

15

16

17

18

--

--

28 (-2)

--

18

18

19

--

--

--

26 (-3)

--

20

21

22

--

--

--

24 (-4)

--

22

23

26

--

--

--

22 (-6)

--

24

26

--

--

--

--

20 (-7)

--

26

30

--

--

--

--

18 (-8)

--

29

--

--

--

--

--

16 (-9)

--

31

--

--

--

--

--

14 (-10)

30

--

--

--

--

--

--

12 (-11)

32

--

--

--

--

--

--

10.4 (-12)

34

--

--

--

--

--

--

Propylene Glycol
DT
Leaving Water Temperature °F (°C)

Low Evaporator Refrigerant
Cutout, Glycol Recommendations

°F

4

6

8

10

12

14

16

°C

-15

-14

-13

-12

-11

-10

-9

38 (3)

--

6

6

7

7

8

--

34 (1)

--

13

13

15

17

--

--

30 (-1)

--

19

21

--

--

--

--

28 (-2)

--

22

--

--

--

--

--

26 (-3)

--

25

--

--

--

--

--

24 (-4)

--

--

--

--

--

--

--

22 (-6)

--

--

--

--

--

--

--

20 (-7)

--

--

--

--

--

--

--

18 (-8)

--

--

--

--

--

--

--

16 (-9)

--

--

--

--

--

--

--

14 (-10)

--

--

--

--

--

--

--

12 (-11)

--

--

--

--

--

--

--

10.4 (-12)

--

--

--

--

--

--

--

Notes:
1. These tables represent the MINIMUM RECOMMENDED glycol
percentages for each operating condition
2. Operation is not recommended at certain operating conditions as
some chillers may not satisfy maximum or minimum velocity
requirements or minimum performance requirements. Contact Trane
Sales Representative for more information regarding the operating
limits of a particular chiller.

Special should all be calculated by engineering.The
purpose of calculating is to make sure that design
saturation temperature is greater than 3 deg F.
Additionally, the calculation must verify that the fluid
freeze point is a minimum of 4 deg. F lower that the design
saturation temperature.The low evaporator temperature
cutout will be 4 deg F below the freeze point or -5 deg F,
whichever is greater.
Important: When using glycol,Techview Setpoint View
setting for “Freeze Inhibitor Present” must
be set to “Yes” to prevent nuisance high
approach diagnostic.

54

RTAC-SVX01M-EN

Installation - Mechanical
Table 43.

% Glycol

Recommended low evaporator refrigerant
cutout and percent glycol
Low Refrig. Temp
Cutout
°F

Solution Freeze Point

°C

°F

°C

Ethylene
0

28.0

-2.2

32

0

5

25.0

-3.9

29

-1.7

10

21.5

-5.8

25.5

-3.6

15

17.5

-8.1

21.5

-5.8

20

12.8

-10.7

16.8

-8.4

25

7.4

-13.7

11.4

-11.4

30

1.1

-17.2

5.1

-15.0

35

-5.0

-20.6

-2.3

-19.1

40

-5.0

-20.6

-10.8

-23.8

45

-5.0

-20.6

-20.7

-29.3

50

-5.0

-20.6

-32.1

-35.6

54

-5.0

-20.6

-42.3

-41.3

Propylene Glycol
0

28.0

-2.2

32.0

0

5

25.3

-3.7

29.3

-1.5

10

22.4

-5.3

26.4

-3.1

15

19.1

-7.2

23.1

-4.9

20

15.3

-9.3

19.3

-7.1

25

10.8

-11.8

14.8

-9.6

30

5.3

-14.8

9.3

-12.6

35

-1.3

-19.5

2.7

-16.3

40

-5.0

-20.6

-5.2

-20.7

45

-5.0

-20.6

-14.6

-25.9

50

-5.0

-20.6

-25.8

-32.1

54

-5.0

-20.6

-36.1

-37.8

Chilled Water Temperature Cutout should be set to 5°F below the
lowest allowable Chilled Water Set Point bases on the %Glycol.

RTAC-SVX01M-EN

55

Installation - Mechanical
Remote Evaporator Option
The RTAC 140-250 ton outdoor unit with the Remote
Evaporator option is shipped as two pieces: the outdoor
unit (condensing) and the evaporator. Short suction line
connections are provided with the outdoor condensing
unit.The remote evaporator is shipped complete, with
factory-mounted electronic expansion valves, water
temperature sensors, suction pressure transducers, liquid
level control sensors, evaporator flow switch, all factory
wired to a ribbon cable. Solenoid valves and drain valves
are wired to a relay board in the terminal box.The
installing contractor is required to provide and install the
following:

NOTICE:
Equipment Damage!
If the circuits are crossed, serious equipment damage
could occur.
3. Piping between the evaporator and outdoor unit can
not exceed 200 actual feet and/or an equivalent length
of 300 feet.
Note: The latter includes the equivalent length of all
associated field installed fittings, valves,
accessories and straight lengths of interconnecting
piping.

•

2-wire, twisted shielded communication line between
the remote evaporator terminal box and the
Condensing Unit’s control panel

•

4-wire connection from evaporator terminal box to
condensing unit control panel for flow switch wiring
(see Figure 32, p. 64)

4. Horizontal portions of suction lines must be downward
sloping toward the compressor at least 1/2 inch for
each 10 feet run.This promotes the movement of oil in
the direction of gas flow.

•

115 VAC single phase power supply to the remote
evaporator terminal box

5. Suction lines must be insulated.

•

2 liquid lines

•

2 suction lines

6. The line sizes defined are to be used only for 40-60 F
leaving water temperature and/or full load ice-making
applications.

•

Suction accumulator as specified

7.

Note: A unit ordered as a remote evaporator must also be
ordered with either the wide or low ambient option.
The fan inverters are necessary for proper control.

System Configuration and
Interconnecting Refrigerant
Piping
The system may be configured in any of the four
arrangements shown in Figure 28, p. 57.The
configurations and their associated elevations, along with
the total distance between the remote evaporator and the
compressor/condenser section, play a critical role in
determining suction and liquid line sizes.This will also
affect field refrigerant and oil charges. Consequently, there
are physical limits which must not be violated if the system
is to operate as designed. Please note the following
requirements for field installation:
1. The remote evaporator MUST be matched with its
respective outdoor condensing unit.
2. The circuit number on the outdoor condensing unit
must match the circuit number on the evaporator, i.e.
circuit #1 on the outdoor condensing unit must be
connected with circuit # 1 on the remote evaporator
and likewise for circuit #2. RTAC Circuit Capacities are
shown in General DataTables.

56

Figure 28, p. 57, drawing 1 depicts an installation
where the remote evaporator elevation is the same as
that of the outdoor condensing unit.The suction and
liquid lines are horizontal or down flowing only.
The suction and liquid lines can be put under ground or
in a trench.The temperature of the suction lines must
never exceed the temperature of the compressor.The
line can be below the compressors a maximum of 15 ft.

8. Figure 28, p. 57, drawing 2 shows a variation to
drawing 1.The remote evaporator and outdoor
condensing unit are at the same elevation but
interconnecting piping may be installed up to 15 feet
above the base elevation. Refer to Table 46, p. 60 to
determine the required length of the suction
accumulator line. A full size suction accumulator is
required at the evaporator and 50% of the value is
required at the condensing unit.
9. A refrigerant drain valve is installed at the bottom of
the evaporator for freeze protection.This drain valve is
a normally open, pilot operated valve which remains
closed unless there is a potential freezing situation
detected via low evap temperatures or low water
temperatures or a power failure. If the drain valve is
opened the installed suction accumulator must be
capable of holding the entire evaporator charge. Refer
to Table 46, p. 60 for sizing.
10. For installations where the remote evaporator is at a
lower elevation than the outdoor condensing unit as
shown in Figure 28, p. 57, drawing 3, the elevation
difference is not to exceed 100 feet. An inverted liquid
RTAC-SVX01M-EN

Installation - Mechanical Remote Evaporator Option
line trap at the condensing unit is required to prevent
unwanted free cooling.The apex of the liquid line trap
should be at a height above the condenser coils. A
suction accumulator must be installed at the
evaporator. Refer to Table 46, p. 60 for sizing.

and operation of the chiller, that the elevation
requirements given in Table 44, p. 59 are not
exceeded. It should also be noted that in this
configuration the suction accumulator is installed at
the condensing section.

11. When the elevation of the remote evaporator exceeds
that of the outdoor condensing unit as shown in
Figure 28, p. 57, drawing 4, the elevation difference is
determined by Table 44, p. 59.The suction
accumulator line must be installed according to
Table 46, p. 60. It is very important, for proper control

Note: The height is limited by the available subcooling.
12. Compressor & oil separator heaters must be on at least
24 hours prior to compressor start.

Figure 28. Remote evaporator installations

RTAC-SVX01M-EN

57

Installation - Mechanical Remote Evaporator Option
Figure 29. Circuit identification

58

RTAC-SVX01M-EN

Installation - Mechanical Remote Evaporator Option

Table 44. Liquid line sizing(a) - 140-250T remote evaporator
Leaving water
40-50°F

Height (ft)
0

1-5

6-10

Leaving water
50-60°F

11-15 16-20 21-25 26-30 31-35

Height (ft)
0

1-5

6-10

11-15 16-20 21-25 26-30

70-ton circuit
25

1.375

1.375

1.375

1.375

1.375

1.375

1.375

n/a

25

1.375

1.375

1.375

1.375

1.375

1.375

2.125

50

1.375

1.375

1.375

1.375

1.375

1.375

1.375

n/a

50

1.375

1.375

1.375

1.375

1.375

1.625

2.125

75

1.375

1.375

1.375

1.375

1.375

1.375

1.625

n/a

75

1.375

1.375

1.375

1.375

1.375

1.625

n/a

100 1.375

1.375

1.375

1.375

1.375

1.375

1.625

n/a

100 1.375

1.375

1.375

1.375

1.625

2.125

n/a

125 1.375

1.375

1.375

1.375

1.375

1.625

1.625

n/a

125 1.375

1.375

1.375

1.625

1.625

2.125

n/a

1.375

1.375

1.375

1.375

1.625

n/a

n/a

1.375

1.375

1.625

1.625

2.125

n/a

1.375

1.375

1.375

1.625

1.625

n/a

n/a

1.375

1.375

1.375

1.625

1.625

n/a

225 1.375

1.375

1.375

1.625

1.625

1.625

250 1.375

1.375

1.375

1.625

1.625

275 1.375

1.375

1.625

1.625

300 1.375

1.375

1.625

1.625

Total
150 1.375
Equivalent
Length (ft) 175 1.375
200 1.375

1.375

1.625

1.625

1.625

2.125

n/a

n/a

Total
150 1.375
Equivalent
Length (ft) 175 1.375
200 1.375

1.625

1.625

1.625

2.125

2.125

n/a

n/a

n/a

225 1.375

1.625

1.625

1.625

2.125

2.125

n/a

n/a

n/a

n/a

250 1.625

1.625

1.625

1.625

2.125

2.125

n/a

1.625

n/a

n/a

n/a

275 1.625

1.625

1.625

2.125

2.125

2.125

n/a

1.625

n/a

n/a

n/a

300 1.625

1.625

1.625

2.125

2.125

2.125

n/a

85-ton circuit
25

1.375

1.375

1.375

1.375

1.375

1.375

2.125

n/a

25

1.375

1.375

1.375

1.375

2.125

n/a

n/a

50

1.375

1.375

1.375

1.375

1.375

1.625

n/a

n/a

50

1.375

1.375

1.375

1.625

2.125

n/a

n/a

75

1.375

1.375

1.375

1.375

1.375

1.625

n/a

n/a

75

1.375

1.375

1.625

1.625

n/a

n/a

n/a

100 1.375

1.375

1.375

1.375

1.625

1.625

n/a

n/a

100 1.375

1.625

1.625

2.125

n/a

n/a

n/a

125 1.375

1.375

1.375

1.625

1.625

2.125

n/a

n/a

125 1.375

1.625

1.625

2.125

n/a

n/a

n/a

1.375

1.375

1.625

1.625

2.125

n/a

n/a

1.625

1.625

2.125

n/a

n/a

n/a

1.625

2.125

2.125

n/a

n/a

n/a

1.625

2.125

2.125

n/a

n/a

n/a

Total
150 1.375
Equivalent
Length (ft) 175 1.375
200 1.375

1.375

1.625

1.625

1.625

2.125

n/a

n/a

1.625

1.625

1.625

2.125

2.125

n/a

n/a

Total
150 1.625
Equivalent
Length (ft) 175 1.625
200 1.625

225 1.375

1.625

1.625

1.625

2.125

2.125

n/a

n/a

225 1.625

2.125

2.125

2.125

n/a

n/a

n/a

250 1.625

1.625

1.625

1.625

2.125

2.125

n/a

n/a

250 1.625

2.125

2.125

2.125

n/a

n/a

n/a

275 1.625

1.625

1.625

1.625

2.125

2.125

n/a

n/a

275 1.625

2.125

2.125

2.125

n/a

n/a

n/a

300 1.625

1.625

1.625

2.125

2.125

2.125

n/a

n/a

300 2.125

2.125

2.125

2.125

n/a

n/a

n/a
1.625

100-ton circuit
25

1.625

1.625

1.625

1.625

1.625

1.625

1.625

1.625

25

1.625

1.625

1.625

1.625

1.625

1.625

50

1.625

1.625

1.625

1.625

1.625

1.625

1.625

1.625

50

1.625

1.625

1.625

1.625

1.625

1.625

1.625

75

1.625

1.625

1.625

1.625

1.625

1.625

1.625

1.625

75

1.625

1.625

1.625

1.625

1.625

1.625

2.125

100 1.625

1.625

1.625

1.625

1.625

1.625

1.625

2.125

100 1.625

1.625

1.625

1.625

1.625

1.625

2.125

125 1.625

1.625

1.625

1.625

1.625

1.625

1.625

2.125

125 1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

2.125

2.125

2.125

1.625

1.625

1.625

1.625

2.125

2.125

2.125

Total
150 1.625
Equivalent
Length (ft) 175 1.625
200 1.625

1.625

1.625

1.625

2.125

2.125

2.125

2.125

225 1.625

1.625

1.625

1.625

1.625

2.125

2.125

2.125

225 1.625

1.625

1.625

2.125

2.125

2.125

2.125

250 1.625

1.625

1.625

1.625

1.625

2.125

2.125

2.125

250 1.625

1.625

2.125

2.125

2.125

2.125

2.625

275 1.625

1.625

1.625

1.625

2.125

2.125

2.125

2.125

275 1.625

1.625

2.125

2.125

2.125

2.125

2.625

300 1.625

1.625

1.625

1.625

2.125

2.125

2.125

n/a

300 1.625

2.125

2.125

2.125

2.125

2.125

2.625
1.625

Total
150 1.625
Equivalent
Length (ft) 175 1.625
200 1.625

120-ton circuit
25

1.625

1.625

1.625

1.625

1.625

1.625

1.625

2.125

25

1.625

1.625

1.625

1.625

1.625

1.625

50

1.625

1.625

1.625

1.625

1.625

1.625

1.625

2.125

50

1.625

1.625

1.625

1.625

1.625

1.625

1.625

75

1.625

1.625

1.625

1.625

1.625

1.625

2.125

2.625

75

1.625

1.625

1.625

1.625

1.625

1.625

2.125

100 1.625

1.625

1.625

1.625

1.625

1.625

2.125

2.625

100 1.625

1.625

1.625

1.625

1.625

1.625

2.125

125 1.625

1.625

1.625

1.625

1.625

2.125

2.125

2.625

125 1.625

1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

1.625

2.125

2.125

2.625

1.625

1.625

1.625

1.625

2.125

2.125

1.625

1.625

1.625

2.125

2.125

2.125

2.625

1.625

1.625

1.625

2.125

2.125

2.125

1.625

1.625

1.625

2.125

2.125

2.125

2.625

1.625

1.625

2.125

2.125

2.125

2.125

225 1.625

1.625

1.625

2.125

2.125

2.125

2.125

n/a

225 1.625

1.625

1.625

2.125

2.125

2.125

2.125

250 1.625

1.625

1.625

2.125

2.125

2.125

2.625

n/a

250 1.625

1.625

2.125

2.125

2.125

2.125

2.625

275 1.625

1.625

2.125

2.125

2.125

2.125

2.625

n/a

275 1.625

1.625

2.125

2.125

2.125

2.125

2.625

300 1.625

2.125

2.125

2.125

2.125

2.125

2.625

n/a

300 1.625

2.125

2.125

2.125

2.125

2.125

2.625

Total
150 1.625
Equivalent
Length (ft) 175 1.625
200 1.625

Total
150 1.625
Equivalent
Length (ft) 175 1.625
200 1.625

(a) Typical type L copper O.D.

RTAC-SVX01M-EN

59

Installation - Mechanical Remote Evaporator Option

Line Sizing

3. See Table 44, p. 59 to determine outside diameter
corresponding to equivalent length computed in step
2 for height and leaving water temperature of interest.

To determine the appropriate outside diameter for field
installed liquid and suction lines, it is first necessary to
establish the equivalent length of pipe for each line. It is
also necessary to know the capacity (tons) of each circuit.
Circuit capacities for each RTAC unit are listed in Table 1,
p. 10 through Table 10, p. 19.

Note: If condenser is at same elevation or above evap,
use 0 ft. column.
4. With the outside diameter found in step # 3, use
Table 45, p. 60 to determine the equivalent lengths of
each fitting in the field installed piping.

Table 45. Equivalent lengths of non-ferrous valves and
fittings (feet)

5. Add equivalent lengths of all field installed elbows and
valves.

Line Size
Globe
Inches OD Valve

Short Angle
Valve

Long
Short Radius Radius
ELL
ELL

6. Add the length found in step # 5 to the actual length
from step # 1.This is your new equivalent line length.

1-1/8

87

29

2.7

1.9

7.

1-3/8

102

33

3.2

2.2

1-5/8

115

34

3.8

2.6

2-1/8

141

39

5.2

3.4

2-5/8

159

44

6.5

4.2

3-1/8

185

53

8

5.1

3-5/8

216

66

10

6.3

4-1/8

248

76

12

7.3

Using Table 44, p. 59 again, find the outside diameter
that corresponds to the new equivalent line length
from step # 6. If it is the same as step #3, this is the final
equivalent length. Otherwise, proceed to the next step.

8. Using Table 45, p. 60 and the new outside diameter
found in step # 7, find the equivalent line length of each
valve and fitting, and sum them.
9. Add the length found in step # 8 to the actual length
from step # 1.This is the new equivalent line length.
10. With the equivalent line length found in step # 9, use
Table 44, p. 59 to select the proper outside diameter for
the liquid lines. If the same as in step #7, this is your
final equivalent line length. Otherwise, repeat step #7.

Liquid Line Sizing Steps
The steps to compute liquid line size are as follows:
1. Compute the actual length of field installed piping.

Note: Location and quantity of suction accumulator is
dependent upon the unit configuration.

2. Multiply the length from step # 1 by 1.5 to estimate the
equivalent length.

Table 46. Required length of field installed suction line accumulator (ft)
Actual Feet
of field
installed
liquid line

70 Ton Circuit(a)

85 Ton Circuit

100 Ton Circuit

120 Ton Circuit

O.D. of Field Installed Liquid Line
1 3/8”

1 5/8”

2 1/8”

1 3/8”

1 5/8”

2 1/8”

1 5/8”

2 1/8”

2 5/8”

1 5/8”

2 1/8”

2 5/8”

Length of 3 5/8” Suction Length of 3 5/8” Suction Length of 4 1/8” Suction Length of 4 1/8” Suction
Accumulator
Accumulator
Accumulator
Accumulator

10

43

44

45

52

52

53

43

44

46

52

53

54

20

45

46

49

53

54

57

45

47

50

53

55

58

30

46

48

52

54

56

60

46

49

53

55

58

62

40

48

50

55

56

58

63

48

52

57

56

60

66

50

49

52

59

57

60

67

49

55

61

58

63

70

60

51

54

62

59

62

70

51

57

65

59

66

74

70

52

56

65

60

64

73

53

60

69

61

68

78

80

53

58

69

62

66

77

54

62

73

62

71

81

90

55

60

72

63

68

80

56

65

77

64

73

85

100

56

62

75

64

70

83

57

68

81

66

76

89

110

58

64

79

66

72

87

59

70

85

67

79

93

120

59

66

82

67

74

90

60

73

89

69

81

97

130

61

68

85

69

76

93

62

75

93

70

84

101

140

62

70

89

70

78

97

63

78

97

72

86

105

150

64

72

92

72

80

100

65

81

101

73

89

109

160

65

74

95

73

82

103

67

83

105

75

92

113

170

66

76

99

75

84

107

68

86

108

76

94

117

180

68

78

102

76

86

110

70

88

112

78

97

121

190

69

79

105

77

88

113

71

91

116

80

99

125

200

71

81

109

79

90

117

73

94

120

81

102

129

(a) Circuit 2 of 155 ton premium unit requires ad additional 10 feet of suction accumulator length.

60

RTAC-SVX01M-EN

Installation - Mechanical Remote Evaporator Option
Example Liquid Line Sizing
Figure 30. Liquid line sizing example

The steps to compute suction line size are as follows:
For this example, refer to Table 44, p. 59, Table 45, p. 60
and Figure 30, p. 61. Assume a 70 ton circuit and a leaving
water temperature of 49 degrees F.
1. From Figure 30, p. 61, the actual length of field
installed piping is:
80 + 8 + 8 + 21 = 117 feet
2. Estimate equivalent line length:
117 feet x 1.5 = 175 feet
3. From Table 44, p. 59 for a 70 ton circuit, for 175
equivalent feet the OD is 1.375 inches.
Note: Use the 0 ft. column since the condenser is above
the evap
4. In Figure 30, p. 61, there are six long-radius elbows.
From Table 45, p. 60, for 1.375 inch elbows, the
equivalent feet is:
6 elbows x 2.2 feet = 13.2 feet
5. Adding equivalent feet from step #4 to step #1 gives:
13.2 feet + 117 feet = 130.2 feet
6. From Table 44, p. 59, for a 70 ton circuit, for 125
equivalent feet (nearest to 130.2), the O.D. is 1- 3/8
inches.

1. Break the suction line into it's Vertical/Upflow and
Horizontal/Downflow components.
2. From Table 47, p. 61, select the appropriate Vertical/
Upflow suction line outside diameter according to the
circuit tonnage.This is the diameter of the upflow
suction line and any fittings in the upflow line.
3. From Table 47, select the appropriate Horizontal/
Downflow suction line outside diameter according to
the circuit tonnage.This is the diameter of the upflow
suction line and any fittings in the upflow line.
Note: The diameters of the upflow, and horizontal or
downflow portions of the suction line may differ
depending on the application.

Example Suction Line Sizing
For this example, refer to Table 47 and Figure 30, p. 61
assume a 70 ton circuit and a leaving water temperature of
49 degrees F.
1. From Table 47 the vertical/upflow suction line is: 3 5/8”
O.D.
2. From Table 47, the horizontal/downflow line is: 3 5/8”
O.D.

Liquid Line size = 1-3/8 inches

Note: In this example, the horizontal line is pitched
downward in the direction of flow.

Suction Line Sizing Steps

Suction Accumulator Sizing

Table 47. Suction line sizes

Use Table 46, p. 60 to calculate length and size of the
required suction accumulator(s).

Vertical/Upflow and Horizontal/Downflow Suction Lines
O.D. (Type L Copper)
LWT (F)

70 ton
circuit

85ton
circuit

100 ton
circuit

120 ton
circuit

40 - 60

3 5/8”

3 5/8”

4 1/8”

4 1/8”

RTAC-SVX01M-EN

Example of Suction Accumulator Line Sizing
Use Figure 30, p. 61 and the same assumptions from the
liquid line sizing example to calculate the suction
accumulator line size and length.
In this case the accumulator is installed at the evaporator.
61

Installation - Mechanical Remote Evaporator Option
1. Use the 70 ton circuit column.
2. From the liquid line sizing example, use a field installed
liquid line of:
1.375 (1 3/8”) inches
3. The actual feet of liquid line installed is: 117 feet
4. The size of the suction accumulator is: 3 5/8 inches
5. The length of the suction line accumulator is: 59 feet

Piping Installation Procedures
WARNING
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.

NOTICE:
Equipment Damage!
Do not use a saw to remove end caps, as this may
allow copper chips to contaminate the system. Use a
tubing cutter or heat to remove the end caps.
The outdoor unit and the evaporator are shipped with a 25
psig holding pressure of dry nitrogen. Do not relieve this
pressure until field installation of the refrigerant piping is
to be accomplished.This will require the removal of the
temporary pipe caps.
Note: UseType L refrigerant-grade copper tubing only.
The refrigerant lines must be isolated to prevent line
vibration from being transferred to the building. Do not
secure the lines rigidly to the building at any point.
All horizontal suction lines should be pitched downward,
in the direction of flow, at a slope of 1/2 inch per 10 feet of
run.
Important:

Field installed liquid line service valves are
recommended for installation. Liquid line
service valves are not provided by the
factory.

Note: Although packaged unit condensers and
evaporators are sized to hold complete refrigerant
charge, units with a remote evaporator may not
have the same capability, due to additional piping
requirements.
62

Refrigerant Sensors
All necessary refrigerant devices, transducers and
solenoids are factory installed and wired to the evaporator
terminal box.

Refrigerant Pressure Relief Valve
Venting
WARNING
Confined Space Hazards!
Do not work in confined spaces where refrigerant or
other hazardous, toxic or flammable gas may be
leaking. Refrigerant or other gases could displace
available oxygen to breathe, causing possible
asphyxiation or other serious health risks. Some gases
may be flammable and or explosive. If a leak in such
spaces is detected, evacuate the area immediately and
contact the proper rescue or response authority. Failure
to take appropriate precautions or to react properly to
such potential hazards could result in death or serious
injury.
Vent pipe size must conform to the ANSI/ASHRAE
Standard 15 for vent pipe sizing. All federal, state, and
local codes take precedence over any suggestions stated
in this manual.
All relief valve venting is the responsibility of the installing
contractor.
All RTAC remote evaporator units use evaporator pressure
relief valves (see Figure 31, p. 63) that must be vented to
the outside of the building.
Relief valve connection sizes and locations are shown in
the unit submittals. Refer to local codes for relief valve vent
line sizing information.

NOTICE:
Equipment Damage!
Do not exceed vent piping code specifications. Failure
to comply with specifications could result in capacity
reduction, unit damage and/or relief valve damage.
Relief valve discharge setpoints and capacities rates are
given in Table 48, p. 63. Once the relief valve has opened,
it will re-close when pressure is reduced to a safe level.
Once opened, relief valves may have a tendency to leak
and must be replaced.
Pressure relief valve discharge capacities will vary with
shell diameter and length and also compressor
displacement. Discharge venting capacity should be
calculated as required by ASHRAE Standard 15-94. Do not
adjust relief valve setting in the field.

RTAC-SVX01M-EN

Installation - Mechanical Remote Evaporator Option

Table 48. Pressure Relief Valve Data
Unit Sizes

Valve
Discharge
Rated Capacity per Field Connection Pipe Factory Shell Side
Location Setpoint (psi) Qty Valve (lba/min.)
Size (NPT)
Connection (in)

120H - 250S 60Hz/200H/170XE

Evap

200

2

17.3

5/8 MFL

7/8 - 14 UNF-2A

250S 50Hz/225H/185XE - 500S

Evap

200

2

28.9

3/4 NPTFI

7/8 - 14 UNF-2A

All

Oil Sep

350

2

6.3

3/8 MFL

1/4-18 NPTFE

Leak Test and Evacuation
After installation of refrigerant piping, thoroughly test the
system for leaks. Pressure test system at pressures
required by local codes.

WARNING
Hazard of Explosion!
Use only dry nitrogen with a pressure regulator for
pressurizing unit. Do not use acetylene, oxygen or
compressed air or mixtures containing them for
pressure testing. Do not use mixtures of a hydrogen
containing refrigerant and air above atmospheric
pressure for pressure testing as they may become
flammable and could result in an explosion.
Refrigerant, when used as a trace gas should only be
mixed with dry nitrogen for pressurizing units. Failure
to follow these recommendations could result in death
or serious injury or equipment or property-only
damage.
Figure 31.

For field evacuation, use a rotary-type vacuum pump
capable of pulling a vacuum of 500 microns or less. Follow
the pump manufacturer's instructions for proper use of
the pump.The line used to connect the pump to the
system should be copper and be the largest diameter that
can be practically used. A larger line size with minimum
flow resistance can significantly reduce evacuation time.
Use the ports on the suction service valves and the liquid
line shutoff valves for access to the system for evacuation.
Ensure that the suction service valve, the liquid line shutoff
valve, the oil line shutoff valve and any field installed
valves are open in the proper position before evacuating.
Insulate entire suction line and suction accumulator line.
Where line is exposed, wrap with weatherproof tape and
seal with weatherproof compound.

Remote evaporator

RTAC-SVX01M-EN

63

Installation - Mechanical Remote Evaporator Option

Figure 32. Field wiring between remote evaporator and condensing unit

Refrigerant and Additional Oil Charge
Refrigerant Charge Determination

without the field-installed piping.

The approximate amount of refrigerant charge required by
the system must be determined by referring to Table 49
and must be verified by running the system and checking
subcooling.

2. Next, determine the charge required for the
field-installed piping by referring to Table 49, p. 64.

Table 49. Field installed piping charge

Note: The amounts of refrigerant listed in Table 49, p. 64
are per 100 feet of pipe. Requirements will be in
direct proportion to the actual length of piping.

Pipe O.D. (in)

Suction Line
lbs of R134a per
100ft

Liquid Line
lbs of R134a per
100ft

1-3/8

N/A

62.4

1-5/8

N/A

88.3

2-1/8

N/A

153.6

2-5/8

N/A

236.9

3-1/8

5.0

N/A

3-5/8

6.8

N/A

4-1/8

8.8

N/A

1. To determine the appropriate charge, first refer to the
Table 1, p. 10 through Table 10, p. 19 in section
“General Data,” p. 9 to establish the required charge
64

3. Sum the values of step 1 and step 2 to determine the
circuit charge.

Oil Charge Determination
The unit is factory charged with the amount of oil required
by the system, without the field-installed piping.The
amount of the additional oil required is dependent upon
the amount of refrigerant that is added to the system for
the field installed piping.
Use the following formula to calculate the amount of oil to
be added:
Pints of Oil = [lbs of R-134a added for field-installed
piping]/100

RTAC-SVX01M-EN

Installation - Electrical
General Recommendations
As you review this manual, keep in mind that:
• All field-installed wiring must conform to National
Electric Code (NEC) guidelines, and any applicable
state and local codes. Be sure to satisfy proper
equipment grounding requirements per NEC.
• Compressor motor and unit electrical data (including
minimum circuit ampacities, motor kW, voltage
utilization range, rated load amps) is listed on the
chiller nameplate.
• All field-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
Note: Always refer to wiring diagrams shipped with
chiller or unit submittal for specific electrical
schematic and connection information.

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements
for field wiring installation and grounding as described
in NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
Important: To prevent control malfunctions, do not run
low voltage wiring (<30 V) in conduit with
conductors carrying more than 30 volts.

RTAC-SVX01M-EN

65

Installation - Electrical

Installer-Supplied Components
Customer wiring interface connections are shown in the
electrical schematics and connection diagrams that are
shipped with the unit.The installer must provide the
following components if not ordered with the unit:
•

Power supply wiring (in conduit) for all field-wired
connections.

•

All control (interconnecting) wiring (in conduit) for
field supplied devices.

•

Fused-disconnect switches or circuit breakers.

•

Power factor correction capacitors. (optional)

Power Supply Wiring
All power supply wiring must be sized and selected
accordingly by the project engineer in accordance with
NECTable 310-16.

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result in
death or serious injury.

The type and installation location(s) of the fused
disconnects must comply with all applicable codes.

NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
Cut holes into the sides of the control panel for the
appropriately-sized power wiring conduits.The wiring is
passed through these conduits and connected to the
terminal blocks, optional unit-mounted disconnects, or
HACR type breakers. Refer to Figure 33, p. 67.
To provide proper phasing of 3-phase input, make
connections as shown in field wiring diagrams and as
stated on the WARNING label in the starter panel. For
additional information on proper phasing, refer to “Unit
Voltage Phasing.” Proper equipment ground must be
provided to each ground connection in the panel (one for
each customer-supplied conductor per phase).
All 115 volt field-provided connections (either control or
power) are made through knockouts on the lower left side
of the panel, as shown on Figure 33. Additional grounds
may be required for each 115 volt power supply to the unit.
Green lugs are provided for 115V customer wiring.

Single Point Power on Dual Panel Units
(Optional)
Units which require two control panels and with single
point power option selected, are built with a power
connection junction box located in the center of the unit as
shown in Figure 34, p. 67. Customer will connect to
terminal blocks inside this panel.

For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
All wiring must comply with local codes and the National
Electrical Code.The installing (or electrical) contractor
must provide and install the system interconnecting
wiring, as well as the power supply wiring. It must be
properly sized and equipped with the appropriate fused
disconnect switches.

66

RTAC-SVX01M-EN

Installation - Electrical

Figure 33. Control panel

Incoming
Customer
Power
Location
Knockouts
for 30V

Cut holes
for power
wiring in
THIS AREA
See side view.

115V
Field
Wiring

Side View - Right

Figure 34. Single point power box - optional on dual panel units

Incoming
Customer
Power
Cut holes
Location
for power
wiring in
THIS AREA
See side view.

Single Point Power Box - Installed

Control Power Supply
The unit is equipped with a control power transformer; it
is not necessary to provide additional control power
voltage to the unit.
All units are factory-connected for appropriate labeled
voltages except for the 400V/50Hz units which need the
control power transformer (1T1) reconnected as noted
below.
Important: As shipped, a normal 400 volt unit control
power transformer is wired on the 400 volt
tap (H3). Reconnect the appropriate
transformer wire lead 126A to the tap (H2)
for 380V/50Hz power supply or lead 126A to
the tap H4 for the 415V/50 Hz power supply.
It is also necessary to adjust the “unit
voltage” setting usingTechView
(Configuration-CustomTab).
RTAC-SVX01M-EN

Side View - Right

Heater Power Supply and Convenience
Outlet (Packaged Units Only)
The evaporator shell is insulated from ambient air and
protected from freezing temperatures by two
thermostatically-controlled immersion heaters and two
strip heaters. Whenever the water temperature drops to
approximately 37°F (2.8°C), the thermostat energizes the
heaters.The heaters will provide protection from ambient
temperatures down to -20°F (-29°C).
It is required to provide an independent power source
(115V 60Hz-20 amp, 220V 50Hz-15 amp), with a fuseddisconnect.The heaters are factory-wired back to the unit
control panel.

67

Installation - Electrical

NOTICE:
Equipment Damage!
Control panel main processor does not check for loss of
power to the heat tape nor does it verify thermostat
operation. A qualified technician must verify power to
the heat tape and confirm operation of the heat tape
thermostat to avoid catastrophic damage to the
evaporator.
A convenience outlet is also optional, which shares the
same power supply as the heaters on 140-250 ton units. Be
aware that when the heater is operating, the convenience
outlet amperage draw will be reduced accordingly.
Note: The convenience outlet is optional.The heaters are
required.

Interconnecting Wiring
Chilled Water Pump Control
An evaporator water pump output relay closes when the
chiller is given a signal to go into the Auto mode of
operation from any source.The contact is opened to turn
off the pump in the event of most machine level
diagnostics to prevent the build up of pump heat.

NOTICE:
Equipment Damage!
If insufficient concentration or no glycol is used, the
evaporator water pumps must be controlled by the
CH530 to avoid severe damage to the evaporator due to
freezing. A power loss of 15 minutes during freezing
can damage the evaporator. It is the responsibility of
the installing contractor and/or the customer to ensure
that a pump will start when called upon by the chiller
controls.
Please consult Table 42, p. 54 for correct concentration
of glycol.
The warranty will be void, in case of freezing due to the
lack of use of either of these protections.
The relay output from 1U10 is required to operate the
EvaporatorWater Pump (EWP) contactor. Contacts should
be compatible with 115/240 VAC control circuit.The EWP
relay operates in different modes depending on CH530 or
Tracer commands, if available, or service pumpdown (See
maintenance section). Normally, the EWP relay follows the
AUTO mode of the chiller. Whenever the chiller has no
diagnostics and is in the AUTO mode, regardless of where
the auto command is coming from, the normally open
relay is energized. When the chiller exits the AUTO mode,
the relay is timed open for an adjustable (usingTechView)
0 to 30 minutes.The non-AUTO modes in which the pump
is stopped, include Reset (88), Stop (00), External Stop
(100), Remote Display Stop (600), Stopped byTracer (300),
68

Low Ambient Run Inhibit (200), and Ice Building complete
(101).
Regardless of whether the chiller is allowed to control the
pump on a full-time basis, if the MP calls for a pump to start
and water does not flow, the evaporator may be damaged
catastrophically. It is the responsibility of the installing
contractor and/or the customer to ensure that a pump will
start when called upon by the chiller controls.
Table 50.

Pump Relay Operation

Chiller Mode

Relay Operation

Auto

Instant close

Ice Building

Instant close

Tracer Override

Close

Stop

Timed Open

Ice Complete

Instant Open

Diagnostics

Instant Open

Note: Exceptions are listed below.
When going from Stop to Auto, the EWP relay is energized
immediately. If evaporator water flow is not established in
20 minutes (for normal transition) or 4 minutes, 15
seconds (for pump commanded ON due to an override
safety), the CH530 de-energizes the EWP relay and
generates a non-latching diagnostic. If flow returns (e.g.
someone else is controlling the pump), the diagnostic is
cleared, the EWP is re-energized, and normal control
resumed.
If evaporator water flow is lost once it had been
established, the EWP relay remains energized and a nonlatching diagnostic is generated. If flow returns, the
diagnostic is cleared and the chiller returns to normal
operation.
In general, when there is either a non-latching or latching
diagnostic, the EWP relay is turned off as though there was
a zero time delay. Exceptions (see above table) whereby
the relay continues to be energized occur with:
A Low Chilled WaterTemp. diagnostic (non-latching)
(unless also accompanied by an Evap Leaving Water
Temperature Sensor Diagnostic)
or
A starter contactor interrupt failure diagnostic, in which a
compressor continues to draw current even after
commanded to have shutdown
or
A Loss of EvaporatorWater Flow diagnostic (non-latching)
and the unit is in the AUTO mode, after initially having
proven evaporator water flow.

Alarm and Status Relay Outputs
(Programmable Relays)
A programmable relay concept provides for enunciation of
certain events or states of the chiller, selected from a list of
RTAC-SVX01M-EN

Installation - Electrical
likely needs, while only using four physical output relays,
as shown in the field wiring diagram.The four relays are
provided (generally with a Quad Relay Output LLID) as part
of the Alarm Relay Output Option.The relay’s contacts are
isolated Form C (SPDT), suitable for use with 120 VAC
circuits drawing up to 2.8 amps inductive, 7.2 amps
resistive, or 1/3 HP and for 240 VAC circuits drawing up to
0.5 amp resistive.
The list of events/states that can be assigned to the
programmable relays can be found in Table 51..The relay
will be energized when the event/state occurs.
Table 51.

Alarm and Status Relay Output Configuration
Table
Description

Alarm - Latching

This output is true whenever there is any
active diagnostic that requires a manual reset
to clear, that affects either the Chiller, the
Circuit, or any of the Compressors on a circuit.
This classification does not include
informational diagnostics.

Alarm - Auto Reset

This output is true whenever there is any
active diagnostic that could automatically
clear, that affects either the Chiller, the
Circuit, or any of the Compressors on a circuit.
This classification does not include
informational diagnostics.

Alarm

This output is true whenever there is any
diagnostic affecting any component, whether
latching or automatically clearing. This
classification does not include informational
diagnostics

Alarm Ckt 1

This output is true whenever there is any
diagnostic effecting Refrigerant Circuit 1,
whether latching or automatically clearing,
including diagnostics affecting the entire
chiller. This classification does not include
informational diagnostics.

Alarm Ckt 2

This output is true whenever there is any
diagnostic affecting Refrigerant Circuit 2
whether latching or automatically clearing,
including diagnostics effecting the entire
chiller. This classification does not include
informational diagnostics.

This output is true whenever the chiller has
been running in one of the Unloading types of
Chiller Limit Mode (with
limit modes (Condenser, Evaporator, Current
a 20 minute filter)
Limit or Phase Imbalance Limit) continuously
for the last 20 minutes.

Circuit 1 Running

This output is true whenever any compressors
are running (or commanded to be running) on
Refrigerant Circuit 1, and false when no
compressors are commanded to be running
on that circuit.

Circuit 2 Running

This output is true whenever any compressors
are running (or commanded to be running) on
Refrigerant Circuit 2, and false when no
compressors are commanded to be running
on that circuit.

Chiller Running

RTAC-SVX01M-EN

This output is true whenever any compressors
are running (or commanded to be running) on
the chiller and false when no compressors are
commanded to be running on the chiller.

Table 51.

Alarm and Status Relay Output Configuration
Table (continued)
Description

This output is true whenever the chiller has
reached maximum capacity or had reached its
maximum capacity and since that time has
Maximum Capacity
not fallen below 70% average current relative
(software 18.0 or later) to the rated ARI current for the chiller. The
output is false when the chiller falls below
70% average current and, since that time,
had not reestablished maximum capacity.

Relay Assignments Using
TechView
CH530 ServiceTool (TechView) is used to install the Alarm
and Status Relay Option package and assign any of the
above list of events or status to each of the four relays
provided with the option.The relays to be programmed
are referred to by the relay’s terminal numbers on the LLID
board 1U12.
The default assignments for the four available relays of the
RTAC Alarm and Status Package Option are:
Table 52.

Default assignments

Relay
Relay 1 Terminals J2 -12,11,10:

Alarm

Relay 2 Terminals J2 - 9,8,7:

Chiller Running

Relay 3 Terminals J2-6,5,4:

Maximum Capacity

Relay 4 Terminals J2-3,2,1:

Chiller Limit

If any of the Alarm/Status relays are used, provide
electrical power, 115 VAC with fused-disconnect to the
panel and wire through the appropriate relays (terminals
on 1U12 (EUR=A4-5)). Provide wiring (switched hot,
neutral, and ground connections) to the remote
annunciation devices. Do not use power from the chiller’s
control panel transformer to power these remote devices.
Refer to the field diagrams which are shipped with the unit.

Low Voltage Wiring
The remote devices described below require low voltage
wiring. All wiring to and from these remote input devices
to the Control Panel must be made with shielded, twisted
pair conductors. Be sure to ground the shielding only at
the panel.
Important: To prevent control malfunctions, do not run
low voltage wiring (<30 V) in conduit with
conductors carrying more than 30 volts.

Emergency Stop
CH530 provides auxiliary control for a customer specified/
installed latching trip out. When this customer-furnished
remote contact 5K14 is provided, the chiller will run
normally when the contact is closed. When the contact
opens, the unit will trip on a manually resettable
69

Installation - Electrical
diagnostic.This condition requires manual reset at the
chiller switch on the front of the control panel.

Communicated input (Tracer) to initiate and command the
Ice Building mode.

Connect low voltage leads to terminal strip locations on
1U4. Refer to the field diagrams that are shipped with the
unit.

CH530 also provides a “Front Panel IceTermination
Setpoint”, settable throughTechView, and adjustable from
20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C) increments.

Silver or gold-plated contacts are recommended.These
customer-furnished contacts must be compatible with 24
VDC, 12 mA resistive load.

Note: When in the Ice Building mode, and the evaporator
entering water temperature drops below the ice
termination setpoint, the chiller terminates the Ice
Building mode and changes to the Ice Building
Complete Mode.

External Auto/Stop
If the unit requires the external Auto/Stop function, the
installer must provide leads from the remote contacts
5K15 to the proper terminals of the LLID 1U4 on the control
panel.
The chiller will run normally when the contacts are closed.
When either contact opens, the compressor(s), if
operating, will go to the RUN:UNLOAD operating mode
and cycle off. Unit operation will be inhibited. Closure of
the contacts will permit the unit to return to normal
operation.
Field-supplied contacts for all low voltage connections
must be compatible with dry circuit 24 VDC for a 12 mA
resistive load. Refer to the field diagrams that are shipped
with the unit.

External Circuit Lockout – Circuit #1 and #2
CH530 provides auxiliary control of a customer specified
or installed contact closure, for individual operation of
either Circuit #1 or #2. If the contact is closed, the
refrigerant circuit will not operate 5K16 and 5K17.
Upon contact opening, the refrigerant circuit will run
normally.This feature is used to restrict total chiller
operation, e.g. during emergency generator operations.
Connections to 1U5 are shown in the field diagrams that
are shipped with the unit.
These customer-supplied contact closures must be
compatible with 24 VDC, 12 mA resistive load. Silver or
gold plated contacts are recommended.

Ice Building Option
CH530 provides auxiliary control for a customer specified/
installed contact closure for ice building if so configured
and enabled.This output is known as the Ice Building
Status Relay.The normally open contact will be closed
when ice building is in progress and open when ice
building has been normally terminated either through Ice
Termination setpoint being reached or removal of the Ice
Building command.This output is for use with the ice
storage system equipment or controls (provided by
others) to signal the system changes required as the chiller
mode changes from “ice building” to “ice complete”.
When contact 5K18 is provided, the chiller will run
normally when the contact is open.
CH530 will accept either an isolated contact closure
(External Ice Building command) or a Remote
70

NOTICE:
Equipment Damage!
Freeze inhibitor must be adequate for the leaving water
temperature. Failure to do so will result in damage to
system components.
Techview must also be used to enable or disable Ice
Machine Control.This setting does not prevent theTracer
from commanding Ice Building mode.
Upon contact closure, the CH530 will initiate an ice
building mode, in which the unit runs fully loaded at all
times. Ice building shall be terminated either by opening
the contact or based on the entering evaporator water
temperature. CH530 will not permit the ice building mode
to be reentered until the unit has been switched out of ice
building mode (open 5K18 contacts) and then switched
back into ice building mode (close 5K18 contacts.)
In ice building, all limits (freeze avoidance, evaporator,
condenser, current) will be ignored. All safeties will be
enforced.
If, while in ice building mode, the unit gets down to the
freeze stat setting (water or refrigerant), the unit will shut
down on a manually resettable diagnostic, just as in
normal operation.
Connect leads from 5K18 to the proper terminals of 1U7.
Refer to the field diagrams which are shipped with the unit.
Silver or gold-plated contacts are recommended.These
customer furnished contacts must be compatible with 24
VDC, 12 mA resistive load.

External Chilled Water Setpoint
(ECWS) Option
The CH530 provides inputs that accept either 4-20 mA or 210 VDC signals to set the external chilled water setpoint
(ECWS).This is not a reset function.The input defines the
set point.This input is primarily used with generic BAS
(building automation systems).The chilled water setpoint
set via the DynaView or through digital communication
withTracer (Comm3).The arbitration of the various chilled
water setpoint sources is described in the flow charts at the
end of the section.
The chilled water setpoint may be changed from a remote
location by sending either a 2-10 VDC or 4-20 mA signal to
the 1U6, terminals 5 and 6 LLID. 2-10 VDC and 4-20 mA
RTAC-SVX01M-EN

Installation - Electrical
each correspond to a 10 to 65°F (-12 to 18°C) external
chilled water setpoint.
The following equations apply:
Voltage Signal

Current Signal

As generated from
external source

VDC=0.1455*(ECWS)+ mA=0.2909(ECWS)+
0.5454
1.0909

As processed by
CH530

ECWS=6.875*(VDC)3.75

Depending on the type to be used, theTechView Service
Tool must be used to configure the LLID and the MP for the
proper input type that is being used.This is accomplished
by a setting change on the CustomTab of the
Configuration View withinTechView.
Important:

ECWS=3.4375(mA)3.75

For proper unit operation, BOTH ECLS and
ECWS settings MUST be the same (2-10
VDC or 4-20mA), even if only one input is to
be used.

If the ECWS input develops an open or short, the LLID will
report either a very high or very low value back to the main
processor.This will generate an informational diagnostic
and the unit will default to using the Front Panel
(DynaView) Chilled Water Setpoint.

The J2-3 and J2-6 terminal is chassis grounded and
terminal J2- 1 and J2-4 can be used to source 12 VDC.The
ECLS uses terminals J2-2 and J2-3. ECWS uses terminals
J2-5 and J2-6. Both inputs are only compatible with
high-side current sources.

TechView ServiceTool is used to set the input signal type
from the factory default of 2-10 VDC to that of 4-20 mA.
TechView is also used to install or remove the External
ChilledWater Setpoint option as well as a means to enable
and disable ECWS.

Figure 35. Wiring examples for ECLS and ECWS

External Current Limit Setpoint
(ECLS) Option
Similar to the above, the CH530 also provides for an
optional External Current Limit Setpoint that will accept
either a 2-10VDC (default) or a 4-20 mA signal.The Current
Limit Setting can also be set via the DynaView or through
digital communication withTracer (Comm 3).The
arbitration of the various sources of current limit is
described in the flow charts at the end of this section.The
External Current Limit Setpoint may be changed from a
remote location by hooking up the analog input signal to
the 1 U6 LLID terminals 2 and 3. Refer to the following
paragraph on Analog Input Signal Wiring Details.The
following equations apply for ECLS:
Voltage Signal

Current Signal

As generated from
external source

VDC+0.133*(%)-6.0

mA=0.266*(%)-12.0

As processed by
UCM

%=7.5*(VDC)+45.0

%=3.75*(mA)+45.0

If the ECLS input develops an open or short, the LLID will
report either a very high or very low value back to the man
processor.This will generate an informational diagnostic
and the unit will default to using the Front Panel
(DynaView) Current Limit Setpoint.
TheTechView ServiceTool must be used to set the input
signal type from the factory default of 2-10 VDC to that of
4-20 mA current.TechView must be also be used to install
or remove the External Current Limit Setpoint Option for
field installation, or can be used to enable or disable the
feature (if installed).

Chilled Water Reset (CWR)
CH530 resets chilled water temperature set point based on
either return water temperature, or outdoor air
temperature. Return Reset and Outdoor Reset are
standard.The following shall be selectable:
•

One of three ResetTypes: None, Return Water
Temperature Reset, Outdoor AirTemperature Reset, or
Constant Return WaterTemperature Reset.

•

Reset Ratio Set Points.
For outdoor air temperature reset there shall be both
positive and negative reset ratio's.

•

Start Reset Set Points.

•

Maximum Reset Set Points.

The equations for each type of reset are as follows:
Return
CWS' = CWS + RATIO (START RESET - (TWE -TWL))

ECLS and ECWS Analog Input Signal
Wiring Details:

and CWS' > or = CWS

Both the ECWS and ECLS can be connected and setup as
either a 2-10 VDC (factory default), 4-20 mA, or resistance
input (also a form of 4-2OmA) as indicated below.

Outdoor

RTAC-SVX01M-EN

and CWS' - CWS < or = Maximum Reset
CWS' = CWS + RATIO * (START RESET -TOD)
and CWS' > or = CWS
71

Installation - Electrical
and CWS' - CWS < or = Maximum Reset
where
CWS' is the new chilled water set point or the “reset CWS”

Communications Interface
Options

CWS is the active chilled water set point before any reset
has occurred, e.g. normally Front Panel,Tracer, or ECWS

Tracer Communications Interface
Option

RESET RATIO is a user adjustable gain

This option allows theTracer CH530 controller to exchange
information (e.g. operating setpoints and Auto/Standby
commands) with a higher-level control device, such as a
Tracer Summit or a multiple-machine controller. A
shielded, twisted pair connection establishes the bidirectional communications link between theTracer
CH530 and the building automation system.

START RESET is a user adjustable reference
TOD is the outdoor temperature
TWE is entering evap. water temperature
TWL is leaving evap. water temperature
MAXIMUM RESET is a user adjustable limit providing the
maximum amount of reset. For all types of reset, CWS' CWS < or = Maximum Reset.
Range
Reset
Type
Return

Reset
Ratio
10 to
120%

Increment
Start
Reset

80 to 80%

IP
Units

4 to 30 F 0 to 20 F 1%
(2.2 to
16.7 C)

Outdoor

Max
Reset

1%

Factory
Default
50%

(0.0 to
11.1 C)

50 to 130
0 to 20 F 1%
F
(10 to
54.4 C)

SI
Units

1%

Important: To prevent control malfunctions, do not run
low voltage wiring (<30 V) in conduit with
conductors carrying more than 30 volts.
Field wiring for the communication link must meet the
following requirements:
•

All wiring must be in accordance with the NEC and
local codes.

•

Communication link wiring must be shielded, twisted
pair wiring (Belden 8760 or equivalent). See the table
below for wire size selection:

10%

(0.0 to
11.1 C)

In addition to Return and Outdoor Reset, the MP provides
a menu item for the operator to select a Constant Return
Reset. Constant Return Reset will reset the leaving water
temperature set point so as to provide a constant entering
water temperature.The Constant Return Reset equation is
the same as the Return Reset equation except on selection
of Constant Return Reset, the MP will automatically set
Ratio, Start Reset, and Maximum Reset to the following.

Table 53. Wire Size
Wire Size

Maximum Length of Communication
Wire

14 AWG (2.5 mm2)
16 AWG (1.5 mm2)
18 AWG (1.0 mm2)

5,000 FT (1525 m)
2,000 FT (610 m)
1,000 FT (305 m)

•

The communication link cannot pass between
buildings.

•

All units on the communication link can be connected
in a “daisy chain” configuration.

RATIO = 100%
START RESET = Design DeltaTemp.
MAXIMUM RESET = Design DeltaTemp.
The equation for Constant Return is then as follows:
CWS' = CWS + 100% (Design DeltaTemp. - (TWE -TWL))
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
When any type of CWR is enabled, the MP will step the
Active CWS toward the desired CWS' (based on the above
equations and setup parameters) at a rate of 1 degree F
every 5 minutes until the Active CWS equals the desired
CWS'.This applies when the chiller is running.
When the chiller is not running, CWS is reset immediately
(within one minute) for Return Reset and at a rate of 1
degree F every 5 minutes for Outdoor Reset.The chiller
will start at the Differential to Start value above a fully reset
CWS or CWS' for both Return and Outdoor Reset.

LonTalk™ Interface (LCI-C)
CH530 provides an optional LonTalk Communication
Interface (LCI-C) between the chiller and a Building
Automation System (BAS). An LCI-C LLID shall be used to
provide “gateway”. functionality between a LonTalk
compatible device and the Chiller.The inputs/outputs
include both mandatory and optional network variables as
established by the LonMark® Functional Chiller Profile
8040.
Note: For more information, see ACC-SVN25*-EN.

BACnet™ Interface (BCI-C)
Optional BACnet Communication Interface for Chillers
(BCI-C) is comprised of aTracer UC400 controller with
interface software. It is a non-programmable
communications module that allows units to
communicate on a BACnet communications network.
Note: For more information, see BAS-SVP05*-EN.

72

RTAC-SVX01M-EN

Operating Principles
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.

This section contains an overview of the operation and
maintenance of RTAC units equipped with CH530 control
systems. It describes the overall operating principles of the
RTAC design.

Refrigeration Cycle
The refrigeration cycle of the RTAC chiller is similar to that
of the RTAA air cooled water chiller.The exception is that
the evaporating and condensing temperatures have been
increased to allow for optimization of the chiller and
reduced foot print.The refrigeration cycle is represented
in the pressure enthalpy diagram in Figure 36. Key state
points are indicated on the figure.The cycle for the full
load AHRI design point is represented in the plot.

R-134a is a medium pressure refrigerant. It may not be
used in any condition that would cause the chiller to
operate in a vacuum without a purge system. RTAC is not
equipped with a purge system.Therefore, the RTAC chiller
may not be operated in a condition that would result in a
saturated condition in the chiller of –15°F (-26°C) or lower.
R-134a requires the use of specific POE oils as designated
on the unit nameplate.

Figure 36. Pressure enthalpy (P-h) diagram - RTAC
R-134a

600

Important:

500

Compressor

2
137°F (58°C)

3
3b

2b

126°F (52°C)

P (psia)

200

106°F (41°C)

100

4

4b

50

1
39°F (4°C)

1b

30
0

20

40

60

80

100

120

h (btu/lb)

The RTAC chiller uses a shell and tube evaporator design
with refrigerant evaporating on the shell side and water
flowing inside tubes having enhanced surfaces (states 4 to
1).The suction lines and bolt pads are designed to
minimize pressure drop.(states 1 to 1b).The compressor is
a twin-rotor helical rotary compressor designed similarly
to the compressors offered in otherTrane Screw
Compressor Based Chillers (states 1b to 2).The discharge
lines include a highly efficient oil separation system that
virtually removes all oil from the refrigerant stream going
to the heat exchangers (states 2 to 2b). De-superheating,
condensing and sub-cooling is accomplished in a fin and
tube air cooled heat exchanger where refrigerant is
condensed in the tube (states 2b to 3b). Refrigerant flow
through the system is balanced by an electronic expansion
valve (states 3b to 4).

Refrigerant R-134a
The RTAC chiller uses environmentally friendly R134a.
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
RTAC-SVX01M-EN

Use only R-134a andTrane Oil 00048 in
RTAC chillers.

140

The compressor is a semi-hermetic, direct-drive rotary
type compressor. Each compressor has only four moving
parts: two rotors that provide compression and male and
female load-control valves.The male rotor is attached to
the motor and the female rotor is driven by the male rotor.
The rotors and motor are supported by bearings.
The helical rotary compressor is a positive displacement
device. Refrigerant vapor from evaporator is drawn into
the suction opening of the compressor (state 1b), through
a suction strainer screen across the motor (which provides
motor cooling) and into the intake of the compressor
rotors.The gas is then compressed and discharged
through a check valve and into the discharge line (state 2).
There is no physical contact between the rotors and the
compressor housing.The rotors contact each other at the
point where the driving action between the male and
female rotors occurs. Oil is injected into the rotors of the
compressor, coating the rotors and the compressor
housing interior. Although this oil does provide rotor
lubrication, its primary purpose is to seal the clearance
spaces between the rotors and compressor housing. A
positive seal between these internal parts enhances
compressor efficiency by limiting leakage between the
high pressure and low pressure cavities.
Capacity control is accomplished by means of a female
step load-control valve and a male control valve.The
female step valve is the first stage of loading after the
compressor starts and the last stage of unloading before
the compressor shuts down.The male control valve is
positioned by a piston cylinder along the length of the
male rotor. Compressor capacity is dictated by the
position of the loading valve relative to the rotors. When
the valve slides toward the discharge end of the rotors
compressor capacity is reduced.
73

Operating Principles

Condenser and Subcooler
Condenser and subcooler are similar to the condenser
used in RTAA chillers.The heat exchanger consists of 3/8”
tubes that contain refrigerant, large fins that are in the air
flow and fans that draw air through fins. Heat is transferred
from the refrigerant through the tubes and fins to the air.
High pressure gas from the compressor enters the tubes of
the condenser through a distribution header (state 2b). As
refrigerant flows through the tubes, the heat of
compression and cooling load are rejected to the air. In
this process the refrigerant is de-superheated, condensed
(states 2b to 3) and finally subcooled (states 3 to 3b) to a
temperature slightly above the ambient air temperature.
The subcooled liquid refrigerant is collected in the leaving
header where it is transferred to the liquid line (state 3b).
Controls algorithm always runs as many fans as possible
without reducing differential pressure (discharge minus
suction) below setpoint, 60 psid (4.2 bar). If a warm enough
ambient is sensed, all fans will run. If ambient is cooler,
some fans are shut off to maintain pressure differential.
Fan staging depends on chiller load, evaporator pressure,
condenser effectiveness, ambient temperature, and
numbers and sizes of fans installed on circuit.
Algorithm pre-starts fans (based on ambient and water
temperatures) when a circuit starts the compressor. (For
rare conditions such as during some pull-downs, a steady
fan state would either violate the 60 psid (4.2 bar) setpoint
or cause a high pressure cut-out; in those conditions a fan
will cycle on and off.)
For up to two minutes after chiller start-up, the setpoint is
35 psi (2.45 bar) difference, and then before the controls
adjust gradually over half a minute up to 60 psi (4.2 bar).

Expansion Valve
Pressure drop occurs in an electronic expansion valve.The
unit controller (CH530) uses the valve to regulate the flow
through the liquid line to match the flow produced by the
compressor. The valve has a variable orifice that is
modulated by a stepper motor.
High pressure, subcooled liquid refrigerant enters the
expansion valve from the liquid line. As refrigerant passes
through the valve the pressure is dropped substantially,
which results in vaporization of some of the refrigerant.
The heat of vaporization is supplied by the two phase
mixture resulting in low temperature low pressure
refrigerant which is supplied to the evaporator (state 4) to
provide cooling.

over the length of the evaporator tubes by the two-phase
distribution system. A portion of the liquid boils as it falls
by gravity from tube to tube, wetting all the tubes of the
evaporator.To ensure that the tubes at the bottom of the
evaporator do not experience “dry out,” a liquid pool is
maintained in the bottom few inches of the bundle.Tubes
located in the bottom of the evaporator will evaporate the
liquid refrigerant by boiling (pool boiling).
Heat is transferred from the water or glycol inside the
tubes to the liquid refrigerant as the film of refrigerant
evaporates on the surface of the tube.Thin film heat
transfer requires a smaller temperature difference for a
given amount of heat transfer than nucleate boiling, which
is the heat transfer process used in flooded evaporators.
Hence, efficiency is enhanced by the use of falling film
evaporation. Additionally, the evaporator requires less
refrigerant than a comparable flooded evaporator and the
evaporator boils the entire refrigerant supply at constant
pressure. Refrigerant vapor exits the evaporator through
the suction line (state 1).

Oil System
Screw compressors require large quantities of oil for
lubricating and sealing the rotors and lubricating the
bearings.This oil is mixed with refrigerant at the discharge
of the compressor.To enhance the performance of the
heat exchanger surfaces an oil separation system is placed
into the discharge line.The oil separator is located
between the compressor and the condenser. It separates
oil using highly efficient centrifugal force. Approximately
99.5% of the oil is removed from the refrigerant in the
separator.
Oil that is removed from the refrigerant falls by gravity into
the oil sump.This oil is directed back to the compressor
through the oil lines. Internal to the compressor is a high
efficiency filter to clean the oil before it is delivered to the
rotors and bearings. Once oil is injected into the
compressor rotors it mixes with the refrigerant again and
is delivered back to the discharge line.
Oil that gets past the oil separators flows through the
condenser, subcooler and expansion valve into the
evaporator.This oil is collected in the pool of refrigerant
that is maintained in the bottom of the evaporator. A small
amount of oil and refrigerant from this pool (state 4b) is
returned through a line that is connected to the
compressor down stream of the motor.This oil and
refrigerant mixes with the refrigerant vapor that was
drawn out of the evaporator, prior to injection into the
compressor rotors.

Evaporator
The evaporator is composed of a liquid-vapor distributor
and falling film evaporator.
A liquid-vapor refrigerant mixture enters the distributor
(state 4).The mixture is distributed over the length of the
evaporator tubes (state 4b). Liquid is evenly distributed
74

RTAC-SVX01M-EN

Controls Interface
Overview

languages as factory-ordered or can be easily downloaded
from www.trane.com.

RTAC units utilize theTracer™ CH530 chiller control
system which consists of several elements:

TechView can be connected to either the DynaView
module and provides further data, adjustment
capabilities, diagnostics information using downloadable
software.

•

•

•

The main processor collects data, status, and
diagnostic information and communicates commands
to the starter module and the LLID (for Low Level
Intelligent Device) bus.The main processor has an
integral display (DynaView™).
Higher level modules (e.g. starter) exist only as
necessary to support system level control and
communications.The starter module provides control
of the starter when starting, running, and stopping the
chiller motor. It also processes its own diagnostics and
provides motor and compressor protection.
Low level intelligent device (LLID) bus.The main
processor communicates to each input and output
device (e.g. temperature and pressure sensors, low
voltage binary inputs, analog input/output) all
connected to a four-wire bus, rather than the
conventional control architecture of signal wires for
each device.

•

The communication interface to a building automation
system (BAS).

•

A service tool to provide all service/maintenance
capabilities.

DynaView Display
DynaView™ display interface is made of weatherproof
and durable plastic for use as a stand-alone device on the
outside of the unit or mounted nearby. See Figure 37.
The DynaView uses a 1/4 VGA display with a resistive
touch screen and an LED backlight.The display area is
approximately 4 inches wide by 3 inches high (102mm x
60mm).
Figure 37.

DynaView

Main processor and service tool (™) software is
downloadable from www.Trane.com.The process is
discussed in section “TechView,” p. 83.
DynaView provides bus management. It has the task of
restarting the link, or filling in for what it sees as “missing”
devices when normal communications has been
degraded. Use ofTechView may be required.
The CH530 uses the IPC3 protocol based on RS485 signal
technology and communicating at 19.2 Kbaud to allow 3
rounds of data per second on a 64-device network. A
typical four-compressor RTAC will have around 50 devices.
Most diagnostics are handled by the DynaView. If a
temperature or pressure is reported out of range by a LLID,
the DynaView processes this information and calls out the
diagnostic.The individual LLIDs are not responsible for
any diagnostic functions.The only exception to this is the
Starter module.
Note: It is imperative that the CH530 ServiceTool
(TechView) be used to facilitate the replacement of
any LLID or reconfigure any chiller component.
TechView is discussed later in this section.

Controls Interface

Key Functions
In this touch screen application, key functions are
determined completely by software and change
depending upon the subject matter currently being
displayed.The basic touch screen functions are outlined
below.

Radio Buttons
Radio buttons show one menu choice among two or more
alternatives, all visible. (It is the AUTO button in Figure 37.)
The radio button model mimics the buttons used on oldfashioned radios to select stations. When one is pressed,
the one that was previously pressed “pops out” and the
new station is selected. In the DynaView model the
possible selections are each associated with a button.The
selected button is darkened, presented in reverse video to
indicate it is the selected choice.The full range of possible
choices as well as the current choice is always in view.

Each chiller is equipped with a DynaView interface.The
DynaView has the capability to display information to the
operator including the ability to adjust settings. Multiple
screens are available and text is presented in multiple
RTAC-SVX01M-EN

75

Controls Interface
Spin Value Buttons
Spin values are used to allow a variable setpoint to be
changed, such as leaving water setpoint.The value
increases or decreases by touching the increment (+) or
decrement (-) arrows.

Action Buttons
Action buttons appear temporarily and provide the user
with a choice such as Enter or Cancel.

Hot Links
Hot links are used to navigate from one view to another
view.

File Folder Tabs
File folder tabs are used to select a screen of data. Just like
tabs in a file folder, these serve to title the folder/screen
selected, as well as provide navigation to other screens. In
DynaView, the tabs are in one row across the top of the
display.The folder tabs are separated from the rest of the
display by a horizontal line.Vertical lines separate the tabs
from each other.The folder that is selected has no
horizontal line under its tab, thereby making it look like a
part of the current folder (as would an open folder in a file
cabinet).The user selects a screen of information by
touching the appropriate tab.

Display Screens
Note: Screens shown in this chapter are representative
samples only, and may not exactly match the
values, selections found on your particular unit.

Basic Screen Format

The main body of the screen is used for description text,
data, setpoints, or keys (touch sensitive areas).The Chiller
Mode is displayed here.
The double up arrows cause a page-by-page scroll either
up or down.The single arrow causes a line by line scroll to
occur. At the end of the page, the appropriate scroll bar will
disappear.
A double arrow pointing to the right indicates more
information is available about the specific item on that
same line. Pressing it will bring you to a subscreen that will
present the information or allow changes to settings.
The bottom of the screen (Fixed Display) is present in all
screens and contains the following functions.The left
circular area is used to reduce the contrast/viewing angle
of the display.The right circular area is used to increase
the contrast/viewing angle of the display.The contrast
may require re-adjustment at ambient temperatures
significantly different from those present at last
adjustment.
The other functions are critical to machine operation.The
AUTO and STOP keys are used to enable or disable the
chiller.The key selected is in black (reverse video).The
chiller will stop when the STOP key is touched and after
completing the Run Unload mode.
Touching the AUTO key will enable the chiller for active
cooling if no diagnostic is present. (A separate action must
be taken to clear active diagnostics.)
The AUTO and STOP keys, take precedence over the Enter
and Cancel keys. (While a setting is being changed, AUTO
and STOP keys are recognized even if Enter or Cancel has
not been pressed.)
The ALARMS button appears only when an alarm is
present, and blinks (by alternating between normal and
reverse video) to draw attention to a diagnostic condition.
Pressing the ALARMS button takes you to the
corresponding tab for additional information.

The basic screen format appears as

Front Panel Lockout Feature
File folder
Tabs

Page scroll
(up)

Radio buttons

Contrast control (lighter)

Tab navigator
Page scroll
(down)
Line scroll
(up/down)

Contrast control (darker)

Display and Touch Screen are Locked
Enter Password to Unlock
1

2

3

4

5

6

7

8

9

Enter

0

Cancel

:
The file folder tabs across the top of the screen are used to
select the various display screens.
Scroll arrows are added if more file tabs (choices) are
available. When the tabs are at the left most position, the
left navigator will not show and only navigation to the right
will be possible. Likewise when the right most screen is
selected, only left navigation will be possible.
76

Note: The DynaView display andTouch Screen Lock
screen is shown below.This screen is used if the
Display and touch screen and lock feature is
enabled.Thirty minutes after the last keystroke,
this screen is displayed and the Display andTouch
Screen is locked out until the sequence “159
” is pressed.
RTAC-SVX01M-EN

Controls Interface
Until the proper password is entered, there will be no
access to the DynaView screens including all reports,
setpoints, and Auto/Stop/Alarms/Interlocks.

control on the screen will return the display to
readable condition.

The password “159” is not programmable from either
DynaView orTechView.

Note: All screens shown in this section are typical. Some
screens show all display options available, only
one of which may appear on a line.

Front Panel Display During Cold Ambients

Modes Screen

If the Display andTouch Screen Lock feature is disabled,
the following screen is automatically displayed if the
DynaViewTemperature is below freezing and has been 30
minutes after the last keystroke.

The Mode Screen is only found on software revisions 18
and later.This screen provides a display for the top level
operating mode for each of the components and subcomponents of the chiller (i.e. Chiller, Circuits, and
Compressors) that exist on the Chiller as it is configured.
The modes are displayed as text only without the hex
codes.

Display and Touch Screen are Locked
Enter 159 to Unlock
1

2

3

4

5

6

7

8

9

Enter

0

Cancel

In software revisions 17.0 and earlier, the top level mode
and the sub mode for each component was displayed on
the respective component tab on the first two lines.The
mode display of the first three lines of the Compressor and
Chiller Screen tabs is eliminated with the addition of the
Mode Screen

Note: This feature is provided to avoid unintended
actuations of the keypad, which can occur due to
ice build-up on the DynaView’s exterior surfaces.
Also be aware that at extremes of temperatures,
the LCD display screen will change its contrast from
the optimal adjustment made at more normal
temperatures. It can appear washed out or blacked
out. Simply pressing the lower right contrast
Table 54. Chiller modes
Chiller Modes

Description

Top Level Mode
Sub-modes
Stopped

The chiller is not running and cannot run without intervention. Further information is
provided by the sub-mode:

Local Stop

Chiller is stopped by DynaView Stop button command- cannot be remotely overridden.

Panic Stop

Chiller is stopped by the DynaView Panic Stop (by pressing Stop button twice in succession)
- previous shutdown was manually commanded to shutdown immediately without a rununload or pumpdown cycle - cannot be remotely overridden.

Diagnostic Shutdown - Manual Reset

The chiller is stopped by a diagnostic that requires manual intervention to reset.

Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions:
Diagnostic Shutdown - Auto Reset
Start Inhibited by Low Cond Temp
Start Inhibited by Low Ambient Temp
Start Inhibited by External Source
Start Inhibited by BAS
Waiting for BAS Communications
Ice Building to Normal Transition
Ice Building is Complete
Run Inhibit

The chiller is currently being inhibited from starting (and running), but may be allowed to
start if the inhibiting or diagnostic condition is cleared. Further information is provided by
the sub-mode:

Diagnostic Shutdown - Auto Reset

The entire chiller is stopped by a diagnostic that may automatically clear.

RTAC-SVX01M-EN

77

Controls Interface
Table 54. Chiller modes (continued)
Chiller Modes

Description

Top Level Mode
Sub-modes
Start Inhibited by Low Cond Temp

The chiller is inhibited from starting by Low Condenser Temperature- Inhibit is active below
either 25°F (can be disabled with proper freeze protection) or 0°F (limit set by design, cannot
be disabled). As an exception, this will not stop a chiller already running.

Start Inhibited by Low Ambient Temp

The chiller is inhibited from starting (and running) by an outdoor air ambient temperature
lower than a specified temperature - per user adjustable settings and can be disabled.

Start Inhibited by External Source

The chiller is inhibited from starting (and running) by the "external stop" hardwired input.

Start Inhibited by BAS

The chiller is inhibited from starting (and running) by command from a Building Automation
System via the digital communication link (com 3 or com 5).

Waiting for BAS Communications

This is a transient mode - 15-min. max, and is only possible if the chiller is in the Auto Remote command mode. After a power up reset, it is necessary to wait for valid
communication from a Building Automation System (Tracer) to know whether to run or stay
inhibited. Either valid communication will be received from the Building Automation System
(e.g. Tracer), or a communication diagnostic ultimately will result. In the latter case the
chiller will revert to Local control.

Ice Building to Normal Transition

The chiller is inhibited from running for a brief period of time if it is commanded from active
ice building mode into normal cooling mode via the ice building hardwired input or Tracer.
This allows time for the external system load to "switchover" from an ice bank to the chilled
water loop, and provides for a controlled pull down of the loop's warmer temperature. This
mode is not seen if the ice making is automatically terminated on return brine temperature
per the mode below.

Ice Building is Complete

The chiller is inhibited from running as the Ice Building process has been normally
terminated on the return brine temperature. The chiller will not start unless the ice building
command (hardwired input or Building Automation System command) is removed or cycled.

Auto

The chiller is not currently running but can be expected to start at any moment given that
the proper conditions and interlocks are satisfied. Further information is provided by the
sub-mode:

Waiting For Evap Water Flow

The chiller will wait up to 4 minutes in this mode for evaporator water flow to be established
per the flow switch hardwired input.

Waiting for Need to Cool

The chiller will wait indefinitely in this mode, for an evaporator leaving water temperature
higher than the Chilled Water Setpoint plus the Differential to Start.

Starting

The chiller is going through the necessary steps to allow the lead circuit and lead compressor
to start.

No Sub Modes
Running

At least one circuit and one compressor on the chiller are currently running. Further
information is provided by the sub-mode:

Unit is Building Ice

The chiller is running in the Ice Building Mode, and either at or moving towards full capacity
available. Ice mode is terminated either with the removal of the ice mode command or with
the return brine temperature falling below the Ice Termination Setpoint.

Running - Limited

At least one circuit and one compressor on the chiller are currently running, but the operation
of the chiller as a whole is being actively limited by the controls.

Capacity Limited by
High Evap Water Temp

This mode will occur if both the OA temperature is above 40°F and the Evap Leaving Water
Temperature is above 75°F as is often the case in a high temperature pull-down. While in
this mode, no compressors will be allowed to load past their minimum load capacity step,
but it will not inhibit compressor staging. This mode is necessary to prevent nuisance trips
due to Compressor Overcurrent or High Pressure Cutout. Reasonable pull-down rates can
still be expected despite this limit.

78

RTAC-SVX01M-EN

Controls Interface

Table 55. Circuit modes
Circuit Modes

Description

Top Level Mode
Sub-modes
Stopped

The given circuit is not running and cannot run without intervention. Further
information is provided by the sub-mode:

Front Panel Lockout

The circuit is manually locked out by the circuit lockout setting - the nonvolatile
lockout setting is accessible through either the DynaView or TechView.

Diagnostic Shutdown - Manual Reset

The circuit has been shutdown on a latching diagnostic.

Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions:
Diagnostic Shutdown - Auto Reset
Start Inhibited by External Source
Start Inhibited by BAS
Run Inhibit

The given circuit is currently being inhibited from starting (and running), but may
be allowed to start if the inhibiting or diagnostic condition is cleared. Further
information is provided by the sub-mode:

Diagnostic Shutdown - Auto Reset

The circuit has been shutdown on a diagnostic that may clear automatically.

Start Inhibited by External Source

The circuit is inhibited from starting (and running) by its "external circuit lockout"
hardwired input.

Start Inhibited by BAS

The circuit is inhibited from starting (and running) by command from a Building
Automation System via the digital communication link (com 3 or com 5).

Auto

The given circuit is not currently running but can be expected to start at any
moment given that the proper conditions and interlocks are satisfied.

No Sub Modes
Starting

The given circuit is going through the necessary steps to allow the lead
compressor on that circuit to start.

No Sub Modes
Running

At least one compressor on the given circuit is currently running. Further
information is provided by the sub-mode:

Establishing Min. Cap - Low Diff pressure

Circuit is experiencing low system differential pressure and is being force loaded,
regardless of Chilled Water Temperature Control, to develop pressure sooner.

Running - Limited

At least one compressor on the given circuit is currently running, but the capacity
of the circuit is being actively limited by the controls. Further information is
provided by the sub-mode:

Capacity Limited by High Cond Press

Circuit is experiencing condenser pressures at or near the condenser limit
setting. Compressors on circuit will be unloaded to prevent exceeding limits.

Capacity Limited by Low Evap Rfgt Temp

The circuit is experiencing saturated evaporator temperatures at or near the Low
Refrigerant Temperature Cutout setting. Compressors on the circuit will be
unloaded to prevent tripping.

Capacity Limited by Low Liquid Level

The circuit is experiencing low refrigerant liquid levels and the EXV is at or near
full open. The compressors on the circuit will be unloaded to prevent tripping.

Shutting Down

The given circuit is still running but shutdown is imminent. The circuit is going
through either a compressor run-unload mode or a circuit operational pumpdown
to dry out the evaporator (cold OA ambient only). Shutdown is necessary due
to one (or more) of the following sub-modes:

Operational Pumpdown

The circuit is in the process shutting down by performing an operational
pumpdown just prior to stopping the last running compressor. The EXV is
commanded closed. Pumpdown will terminate when both the liquid level and the
evap pressure

Front Panel Lockout

The circuit has been manually locked out by the circuit lockout setting and is in
the process of shutting down - the nonvolatile lockout setting is accessible
through either the DynaView or TechView.

Diagnostic Shutdown - Manual Reset

The circuit is in the process of shutdown due to a latching diagnostic.

Diagnostic Shutdown - Auto Reset

The circuit is in the process of shutdown due to a diagnostic that may
automatically clear.

Start Inhibited by External Source

The circuit is in the process of shutdown due to a command from the external
circuit lockout hardwired input.

Start Inhibited by BAS

The circuit is in the process of shutdown due to a command from the Building
Automation System (e.g. Tracer)

RTAC-SVX01M-EN

79

Controls Interface
Table 55. Circuit modes (continued)
Circuit Modes

Description

Top Level Mode
Sub-modes
Service Override

The given circuit is in a Service Override mode

Service Pumpdown

The circuit is running with fan control, via a manual command to perform a
Service Pumpdown. Its respective EXV is being held wide open, but the manual
liquid line service valve should be closed.

Table 56. Compressor modes
Compressor Modes

Description

Top Level Mode
Sub-modes
Stopped

The given compressor is not running and cannot run without intervention. Further
information is provided by the sub-mode:

Diagnostic Shutdown - Manual Reset

The compressor has been shutdown on a latching diagnostic.

Service Tool Lockout

The compressor has been shutdown due to a command from the TechView Service Tool
to be "locked out" and inoperative. This setting is nonvolatile and operation can only be
restored by using TechView to "unlock" it.

Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions:
Diagnostic Shutdown - Auto Reset
Restart Inhibit
Run Inhibit

The given compressor is currently being inhibited from starting (and running*), but may
be allowed to start if the inhibiting or diagnostic condition is cleared. Further information
is provided by the sub-mode:

Diagnostic Shutdown - Auto Reset

The compressor has been shutdown on a diagnostic that may clear automatically.

Restart Inhibit

The compressor is currently unable to start due to its restart inhibit timer. A given
compressor is not allowed to start until 5 minutes has expired since its last start.

Auto

The given compressor is not currently running but can be expected to start at any moment
given that the proper conditions occur.

No Sub Modes
Starting

The given compressor is going through the necessary steps to allow it to start. (This mode
is short and transitory)

No Sub Modes
Running

The given compressor is currently running. Further information is provided by the submode:

Establishing Min. Capacity - High Oil Temp

The compressor is running and is being forced loaded to its step load point, without regard
to the leaving water temperature control, to prevent tripping on high oil temperature.

Running - Limited

The given compressor is currently running, but its capacity is being actively limited by the
controls. Further information is provided by the sub-mode:

Capacity Limited by High Current

The compressor is running and its capacity is being limited by high currents. The current
limit setting is 120% RLA (to avoid overcurrent trips) or lower as set by the compressor's
"share" of the active current limit (demand limit) setting for the entire chiller.

Capacity Limited by Phase Unbalance

The compressor is running and its capacity is being limited by excessive phase current
unbalance.

Shutting Down

The given compressor is still running but shutdown is imminent. The compressor is going
through either a run-unload mode or is the active compressor in the operational
pumpdown cycle for its circuit. Shutdown is either normal (no sub-mode displayed) or due
the following sub-modes:

Diagnostic Shutdown - Manual Reset

The compressor is in the process of shutdown due to a latching diagnostic.

Diagnostic Shutdown - Auto Reset

The compressor is in the process of shutdown due to a diagnostic that may clear
automatically.

Service Tool Lockout

The compressor is in the process of shutdown due to a command from the TechView
Service Tool to be "locked out" and inoperative. This setting is nonvolatile and operation
can only be restored by using TechView to "unlock" it.

80

RTAC-SVX01M-EN

Controls Interface

Chiller Screen

.

The chiller screen is a summary of the chiller activity.

Table 58. Compressor screen
Description

Table 57. Chiller screen
Description
Evap Leaving Water Temperature

Resolution
X.X

Units
F/C

Evap Entering Water Temperature

X.X

F/C

Active Chilled Water Setpoint

X.X

F/C

Active Current Limit Setpoint

X

% RLA

Out Door Temperature

X.X

F/C

Software Type

RTA

Text

Software Version

X.XX

Text

Compressor Screen
The compressor screen displays information for the one,
two, three, or four compressors in the format shown.The
top line of radio buttons allows you to select the
compressor of interest.The next three lines show the
compressor operating mode.The compressor radio
buttons and the compressor operating mode lines don’t
change as you scroll down in the menu.

Resolution

Units
Amps

Amps L1 L2 L3

XXX

% RLA L1 L2 L3

X.X

% RLA

Unit Volts

XXX

Volts

Oil Temperature

X.X

F/C

Intermediate Oil Pressure

X.X

Pressure

Suction Pressure

X.X

Pressure

Starts/ Run Hours

X, XX:XX

hr:min

Refrigerant Screen
The refrigerant screen displays those aspects of the chiller
related to the refrigerant circuits.

The top screen has no upward scroll keys.The single arrow
down scrolls the screen one line at a time. As soon as the
display is one line away from the top, the upward pointing
arrow appears.
The last screen has a single arrow to scroll upward one line
at a time. When in the last position, the single down arrow
disappears.
Each compressor has its own screen depending on which
radio key is pressed. When toggling between compressor
screens, say to compare starts and run time, the same lines
can be seen without additional key strokes. For example,
toggling from the bottom of the compressor 1A menu
accesses the top of the compressor 2A menu.

RTAC-SVX01M-EN

Table 59. Refrigerant screen
Description

Resolution

Units

Cond Rfgt Pressure Ckt1/Ckt2

X.X

Pressure

Sat Cond Rfgt Temp Ckt1/Ckt2

X.X

F/C

Evap Rfgt Pressure Ckt1/Ckt2

X.X

Pressure

Sat Evap Rfgt Temp Ckt1/Ckt2

X.X

F/C

Evap Approach Temp Ckt1/Ckt2 X.X

F/C

Rfgt Liquid Level Ckt1/Ckt2

Height

X.X

81

Controls Interface

Setpoint Screen

Table 60. Setpoint screen (continued)
Resolution or
Text

Units

Front Panel Current Limit
Setpoint

XXX

% RLA

Differential to Start

X.X

Temperature

In Screen 1 the language setpoint will always be the last
setpoint in the list.This will facilitate language changes by
placing that control in a standard position across all
CH.530 product lines.

Differential to Stop

X.X

Temperature

Condenser Limit Setpoint

Enable/Disable

Text

Low Ambient Lockout Setpoint

X.X

Temperature

Low Ambient Lockout

Enable/Disable

Text

Screen 2 displays the current value of the chosen setpoint
in the upper ½ of the display. It is displayed in a changeable
format consistent with its type. Binary setpoints are
considered to be simple two state enumeration and will
use radio buttons. Analog setpoints are displayed as spin
buttons.The lower half of the screen is reserved for help
screens.

Ice Build

Enable/Disable

Text

Front Panel Ice Termination
Setpoint

X.X

Temperature

Comp 1A Pumpdown

Pumpdown/Abort Text

Comp 1B Pumpdown

Pumpdown/Abort Text

Comp 2A Pumpdown

Pumpdown/Abort Text

Comp 2B Pumpdown

Pumpdown/Abort Text

EXV Ckt 1 Open

Auto/Open

Text

EXV Ckt 2 Open

Auto/Open

Text

Front Panel Ckt 1 Lockout

Locked Out/Not
Locked Out

Text

Front Panel Ckt 2 Lockout

Locked Out/Not
Locked Out

Text

The setpoint screen is a two-part screen. Screen 1 lists all
setpoints available to change along with their current
value.The operator selects a setpoint to change by
touching either the verbal description or setpoint value.
Doing this causes the screen to switch to Screen 2.

Description

Ext Chilled Water Setpoint

X.X

F/C

Ext Current Limit Setpoint

XXX

% RLA

Date Format

mmm dd yyyy, dd
Text
mm yyyy

Date
Time Format

Text

Time of Day

Table 60. Setpoint screen
Description

Resolution or
Text

Units

Auto Local or Remote

Remote/Local

Text

Front Panel Chilled Water
Setpoint

X.X

F/C

Table 61

Text
12 hr, 24 hr

Text

Keypad/Display Lockout

Enable/Disable

Text

Display Units

SI, English

Text

Pressure Units

Absolute, Gauge

Text

Language Selection

Downloaded from
Text
TechView

Setpoint options/conditions displayed

Option

Condition(s)

Explanation

Ice Building

Enable/Disable

If feature is installed, operation can be initiated or stopped

Cprsr Pumpdown1

Avail

Pumpdown is allowed: only with unit in Stop or when circuit is locked out

Not Avail

Pumpdown is not allowed because unit is operating or pumpdown has been completed

Pumpdown

State is displayed while pumpdown is in progress

EXV Ckt Open
Avail
(For Authorized Service Use Only2)

Ckt Lockout

Indicates EXV is closed but can be opened manually since unit is in Stop or circuit is
locked out

Not Avail

EXV is closed but cannot be opened manually since unit is operating

Open

State is displayed when EXV is open. Unit will not start with EXV manually set open,
but will initiate valve closure first.

Locked Out

Circuit is locked out at Front Panel; other circuit may be available to run

Not Locked Out

Circuit is not locked out and is available to run

Notes:
1 Pumpdown procedure are discussed in Maintenance section 10.
2 Used for liquid level control or to recover from pumpdown

82

RTAC-SVX01M-EN

Controls Interface
Table 61

Setpoint options/conditions displayed (continued)

Option

Condition(s)

Explanation

Ext. Chilled Water Setpt

Enable/Disable

Allows unit to control setpoint; otherwise another loop controller in line will control, as
optionally wired.

Ext. Current Limit Setpt

Enable/Disable

Allows unit to control setpoint; otherwise another loop controller in line will control, as
optionally wired.

Notes:
1 Pumpdown procedure are discussed in Maintenance section 10.
2 Used for liquid level control or to recover from pumpdown

Diagnostic Screen

Display Formats

The diagnostic screen (shown following) is accessible by
either pressing the blinking ALARMS key or by pressing
the Diagnostic tab on the screen tab selection.

Units

A hex code and a verbal description appears on the display
as shown typically above.This is the last active diagnostic.
Pressing the “Reset All Active Diagnostics” will reset all
active diagnostics regardless of type, machine or
refrigerant circuit. Compressor diagnostics, which hold off
only one compressor, are treated as circuit diagnostics,
consistent with the circuit to which they belong. One
circuit not operating will not shut the chiller down.Viewing
the “Compressor” screen will indicate whether a circuit is
not operating and for what reason.

Temperature settings are in °F or °C, depending on Display
Units settings. Settings can be entered in tenths or whole
degrees depending on a menu setting at theTechView.
Dashes (“-----”) appearing in a temperature or pressure
report, indicates that the value is invalid or not applicable.

Languages
English plus two alternate languages may be installed
with DynaView and will reside in the main processor.
English will always be available. Alternate languages must
be installed usingTechView, Software Download View.

TechView

A complete listing of diagnostics and codes is included in
the Diagnostic Section.

Power-Up
On Power-Up, DynaView will cycle through three screens:
•

First Screen, Version # of the Boot, full version #
displayed.
• This screen will display for 5 seconds before
moving to second screen. Contrast is adjustable
from this screen.

•

Second Screen, Application or No Application.
• This screen will display for 5 seconds “A Valid
Application Is Present” or “A Valid Application Is
Not Present”.

•

Third Screen, First screen of the Application, the Chiller
Tab

TechView™ is the PC (laptop) based tool used for servicing
Tracer CH530.Technicians that make any chiller control
modification or service any diagnostic withTracer CH530
must use a laptop running the software application
“TechView.” TechView is aTrane application developed to
minimize chiller downtime and aid the technicians
understanding of chiller operation and service
requirements.
Note: Important: Performing anyTracer CH530 service
functions should be done only by a properly
trained service technician. Please contact your
localTrane service agency for assistance with any
service requirements.

RTAC-SVX01M-EN

83

Controls Interface
the installation file in this location helps you remember
where it is stored and makes it easier for technical
support personnel to assist you.

TechView software is available viaTrane.com.
(http://www.trane.com/COMMERCIAL/DesignAnalysis/
TechView.aspx?i=1435
This download site provides a user theTechView
installation software and CH530 main processor software
that must be loaded onto your PC in order to service a
CH530 main processor.TheTechView service tool is used
to load software into theTracer CH530 main processor

2. Click the link for the latest version on theTechView
Software Download page. Enter your name, e-mail
address and other required information. Click Submit.
3. A download link will be sent to the e-mail address
provided. Before you click the link please note:
• Sent link may only be used one time.

Minimum PC requirements to install and
operate TechView

• Internet options must be set correctly to allow
download.To verify correct setting:
– Open Internet Explorer Browser
– ClickTools
– Select Internet Options
– Select Security tab
– Click on Internet zone
– Click Custom Level button
– Scroll to Downloads section
– Verify/Enable “Automatic prompting for file
downloads”
– Click OK
– ClickYES on warning window
– Click Apply, then OK

• Microsoft Windows XP Professional, Windows
Vista Business or Windows 7 Enterprise
• Internet Explorer 6.0 or higher
• USB 2.0 or higher
• Pentium II, III or higher processor
• 128Mb RAM minimum forTechView, 1G
recommended for total Windows system
• 1024 x 768 resolution of display
• CD-ROM (optional for copyingTechView install to
CD)
• 56K modem (optional for internet connection)
• 9-pin RS-232 serial connection (optional for
connection to DynaView)
Note: TechView was designed for the preceding listed
laptop configuration. Any variation will have
unknown results.Therefore, support forTechView
is limited to only those operating systems that
meet the specific configuration listed here. Only
computers with a Pentium II class processor or
better are supported; Intel Celeron, AMD, or Cyrix
processors have not been tested.

Note: If this setting is incorrect, you may or may
not receive an error message during
download attempt.
4. Click the download link in the e-mail message.
• If the download window does not open
immediately, please look for a yellow highlighted
message bar/line near the top of your browser. It
may contain a message such as “To help protect
your security, Internet Explorer blocked this site
from downloading files to your computer. Click here
for options...” Click on message line to see options.

TechView is also used to perform any CH530 service or
maintenance function. Servicing a CH530 main processor
includes:

• When dialog box appears, click Save and navigate
to the CH530 folder created in Step 1. Click OK.

• Updating main processor software

• If you do not complete the download successfully,
you will have to request another download link
(Step 2).

• Monitoring chiller operation
• Viewing and resetting chiller diagnostics
• Low Level Intelligent Device (LLID) replacement and
binding
• Main processor replacement and configuration
modifications
• Setpoint modifications
• Service overrides

TechView Software Download, Installation
This information can also be found at http://
www.trane.com/COMMERCIAL/DesignAnalysis/
TechView.aspx?i=1435.
1. Create a folder called “CH530” on your (C:\CH530) on
your hard drive.This \CH530 folder is the standard
recommended location for the installation file. Storing
84

5. Navigate to the CH530 folder created in Step 1. Doubleclick the installation (.exe) file.The License Agreement
dialog box appears.
6. Click I Agree after reviewing License Agreement.The
Choose Components dialog box appears. All
components are selected by default. (These are the
actual MP versions for all units.) Deselect any
components you do not want.
Note: Deselecting components reduces the size of the
installed application.
7.

Click Install. A progress meter dialog box appears. An
information file appears when installation is complete.

RTAC-SVX01M-EN

Controls Interface
Note: Techview requires a current version of JAVA. If
you do not have the current release,TechView
installation will be interrupted, and you will be
provided with information for required JAVA
software download. Once you have completed
the JAVA installation, return to Step 5 to restart
installation.

chiller it is automatically updated in Status View. See
Figure 40, p. 90.

Setpoint View
Setpoint view displays the active setpoints and allows you
to make changes. See Figure 41, p. 90.

Setpoint List

Unit View

The center displays the scrollable list of setpoint panels.

Unit view is a summary for the system organized by chiller
subsystem.This provides an overall view of chiller
operating parameters and gives you an “at-a-glance”
assessment of chiller operation.
The Control Panel tab displays important operating
information for the unit and allows you to change several
key operating parameters.The panel is divided into four or
more sub-panels (depending on the number of circuits in
the unit).

Setpoint Enumeration Panel
A setpoint numeric panel contains a label with the setpoint
description and a pull-down list showing the active value
and the other selections.The Default button returns the
setpoint to the product's factory setting.The text field is
updated when the change is complete.

Setpoint Numeric Panel

The Operating Mode tab displays the unit, circuit and
compressor top level operating modes.

A setpoint numeric panel contains a label with the setpoint
description, a Default button, a text field with a unit label,
and a slider.

The Hours and Starts tab displays the number a hours
(total) a compressor has run and the number of times the
compressor has started.This window plays a key role in
evaluating maintenance requirements.

The Default button changes the setpoint to the product's
factory setting.The text field and slider are updated when
the change is complete.

Upon successful Local ConnectTech View will display
UNIT VIEW, as shown in Figure 38, p. 89.

You can change a setpoint with the text field or with the
slider. When you click on the entry field, the change
setpoint dialog displays to coordinate the setpoint change.

Compressor Service View
Compressor View provides convenient access to service
functions for pumping down circuits and test starting
compressors. Various operational lockouts allow
operation of rest of chiller while others are awaiting repair.
See Figure 39, p. 90.

You can change the display units for a setpoint by clicking
on the unit label next to the entry field.

Change Setpoint
The change setpoint window allows you to enter a new
value for the setpoint into a text field. If the entered value
is outside the given range, the background turns red.

Status View
Status View displays, in real time, all non-setpoint data
organized by subsystem tabs. As data changes on the
Table 62. Setpoints view items
Tab

Text

Min
Value

Chiller

Front Panel Display Units

English, SI

Chiller

Front Panel Chilled Water Setpoint

10
(-12.22)

Chiller

Front Panel Current Limit Setpoint

60

120

120

Percent

Chiller

Differential to Stop

0.5
(0.2777)

2.5
(1.388)

2.0
(1.111)

Differential Temp
Deg F(C)

Chiller

Differential to Start

1.0
(0.555)

30
(16.666)

2
(1.111)

Differential Temp
Deg F(C)

Chiller

Leaving Water Temp Cutout

0.0
(-17.78)

36.0
(2.22)

36.0
(2.22)

Temp Deg F(C)

Chiller

Low Refrigerant Temp Cutout

-5.0
(-20.56)

36.0
(2.22)

28.0
(-2.22)

Temp Deg F(C)

Chiller

Front Panel Condenser Limit Setpoint

80

120

90

Percent

Chiller

Low Ambient Lockout Setpoint

-10
(-23.333)

70
(21.111)

25
(-3.89)

Temp Deg F(C)

Chiller

Low Ambient Lockout

Enable, Disable

Enable

Enabled / Disabled

RTAC-SVX01M-EN

Max Value
65
(18.33)

Default Value

Unit Type

English

Display Units

44
(6.67)

Temp Deg F(C)

85

Controls Interface
Table 62. Setpoints view items (continued)
Tab

Text

Min
Value

Max Value

Default Value

Unit Type

31
(-0.56)

31
(-0.56)

Temp Deg F(C)
Enabled / Disabled

Chiller

Front Panel Ice Termination Setpoint

20
(-6.67)

Chiller

External Ice Building Input

Enable, Disable

Disable

Chiller

Under/Over Voltage Protection

Enable, Disable

Disable

Enabled / Disabled

Chiller

Local Atmospheric Pressure

9.93
(68.5)

16.0
(110.3)

14.7
(101.3)

Absolute Pressure
psia(Kpa)

Chiller

Design Delta Temperature

4
(2.22)

30
(16.666)

10
(5.6)

Differential Temp
Deg F(C)

Chiller

Reset Type

None, Return, Outdoor,
Constant Return

None

RstTyp

Chiller

Return Reset Ratio

10

120

50

Percent

Chiller

Return Start Reset

4.0
(2.22)

30.0
(16.666)

10.0
(5.56)

Differential Temp
Deg F(C)

Chiller

Return Maximum Reset

0

20
(11.11)

5.0
(2.78)

Differential Temp
Deg F(C)

Chiller

Outdoor Reset Ratio

-80

80

10

Percent

Chiller

Outdoor Start Reset

50
(10)

130
(54.44)

90
(32.22)

Temp Deg F(C)

Chiller

Outdoor Maximum Reset

0

20
(11.11)

5
(2.78)

Differential Temp
Deg F(C)

Chiller

External Chilled Water Setpoint

Enable, Disable

Disable

Enabled / Disabled

Chiller

External Current Limit Setpoint

Enable, Disable

Disable

Enabled / Disabled

Chiller

Evaporator Water Pump Off Delay

0

Chiller

Chilled Water Setpoint Filter Settling Time 30

Chiller

Compressor Staging Deadband

0.4
(0.222)

Diagnostics View
See Figure 42, p. 90.This window lists the active and
inactive (history) diagnostics.There can be up to 60
diagnostics, both active and historic. For example, if there
were 5 active diagnostics, the possible number of historic
diagnostics would be 55.You can also reset active
diagnostics here, (i.e., transfer active diagnostics to
history and allow the chiller to regenerate any active
diagnostics).
Resetting the active diagnostics may cause the chiller to
resume operation.
The Active and History diagnostics have separate tabs. A
button to reset the active diagnostics displays when either
tab is selected.

30

1

Minutes

1800

200

Seconds

4.0
(2.222)

0.05
(0.2778)

Differential Temp
Deg F(C)

appropriate steps are taken to monitor required inputs and
control necessary outputs.
Any changes made in the ConfigurationView, on any of the
tabs, will modify the chiller configuration when you click
on the Load Configuration button (located at the base of
the window).The Load Configuration button uploads the
new configuration settings into the main processor.
Any changes made to the configuration will change the
unit model number and the confirmation code (CRC). If
changes are made to the unit configuration the new model
number and CRC should be recorded.
Selecting the Undo All button will undo any configuration
setting changes made during the presentTechView
connection and since the last time the Load Configuration
button was selected.

Configuration View
See Figure 43, p. 91.This view displays the active
configuration and allows you to make changes.
Configuration View allows you to define the chiller's
components, ratings, and configuration settings.These
are all values that determine the required installed
devices, and how the chiller application is run in the main
processor. For example, a user may set an option to be
installed with Configuration View, which will require
devices to be bound using Binding View. And when the
main processor runs the chiller application, the
86

RTAC-SVX01M-EN

Controls Interface
Table 63. Configuration View Items
Tab

Item

Default

Feature Basic Product Line

Unit Nominal Capacity

Description
RTAC - Air Cooled Series R Chiller
120
130
140
155
170
185
200
225
250
275
300
350
375
400
450
500

Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal

Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons
Tons

Unit Voltage

A - 200V/60Hz/3Ph power
C - 230V/60Hz/3Ph power
J - 380V/60Hz/3Ph power
D - 400V/50Hz/3Ph power
4 - 460V/60Hz/3Ph power
5 - 575V/60Hz/3Ph power

Manufacturing Location

U - Water Chiller Business Unit - Pueblo
E - Epinal Business Unit -Charmes

Design Sequence

XX - Factory/ABU Assigned

Unit Type

N - Standard Efficiency/Performance
H - High Efficiency/Performance
A - Extra Efficiency/Performance

Agency Listing

N - No agency listing
U - C/UL listing

Pressure Vessel Code

A - ASME pressure vessel code
C - Canadian code
D - Australian code
L - Chinese code
R - Vietnamese code
S - Special

Evaporator Temperature Range & Application Type

F - Standard Temperature with Freeze Protection
R - Rem Evap, Std Temp, No Freeze Protection
G - Low Temp, with Freeze Protection

Evaporator Configuration

N - Standard 2 pass arrangement, insulated
P -3 pass arrangement, insulated

Condenser Temperature Range

N - Standard ambient 25-115°F
H - High ambient 25-125°F
L - Low ambient 0-115°F
W - Wide ambient 0-125°F

Condenser Fin Material

1 - Standard aluminum slit fins
2 - Copper fins, non-slit fins
4 - Complete Coat aluminum fins

Feature Condenser Fan/Motor Configuration

T - Standard fans, TEAO motors
W - Low Noise fans

Compressor Motor Starter Type

X - Across-the-line
Y - Wye-delta closed transition

Incoming Power Line Connection

1 -Single point
2 -Dual point (1/ckt)

Power Line Connection Type

T - Terminals only
D - Non-fused disconnect switch(es)
C - Circuit Breaker(s), HACR-rated

Unit Operator Interface

D -Dyna-View

RTAC-SVX01M-EN

87

Controls Interface
Table 63. Configuration View Items (continued)
Tab

Item

Default

Remote Interface

N -No remote input
R -Remote leaving water temp setpoint
C -Remote current limit setpoint
B -Remote leaving temp setpoint and remote current limit setpoint

Control Input Accessories/Options

Control Output Accessories/Options

N -No output options
A -Alarm relay
C -Icemaking
D -Icemaking and alarm relay

Short Circuit Rating

0 - No short circuit withstand rating
5 -Default short circuit rating
6 - High amp short circuit rating

Control Panel Accessories

N - No convenience outlet
A - 15A 115V convenience outlet (60HZ)

Refrigerant Service Valves

0 - No suction services valves
1 - Suction service valves

Compressor Sound Attenuator Option

0 - No sound attenuator
1 - Factory installed sound attenuator

Appearance Options

N - No appearance options
A - Architectural louvered panels
C - Half Louvers
P - Painted unit
L - Painted unit with full louvered panels
H - Painted unit with half louvered panels
K - Painted unit with access guards
W - Painted w/access guards and half louvers
N - No installation accessories
R - Neoprene Isolators
F - Flanged water connection kit
G - Neoprene isolators and flange wtr conn kit

Features Installation Accessories
Factory Test

0 - No factory run test

Control, Label, and Literature
Language

E - English
G - Chinese

Special Order

X - Standard catalog configuration
S - Unit has special order feature

Custom Comm 3 ICS address
Status Relay #1 J2-10,11,12

Chiller Running

Status Relay #3 J2-4,5,6

Maximum Capacity

Status Relay #4 J2-1,2,3

Chiller Limit Mode

Phase Unbalance Trip

30

Phase Unbalance Grace Period

90

Starter Feature
External Chilled Water Setpoint
Detection
External Current Limit Water
Setpoint Detection
Custom Unit Voltage

88

55
Alarm - Latching

Status Relay #2 J2-7,8,9

Maximum Acceleration Time

Nameplate

Description
N - No remote interface
C - Tracer Comm 3 interface
B - BACnet communication interface
L -Lon Talk Communication interface (LCI)

3
All Enabled

1-64 REM = C
None, Alarm - Latching (Active diagnostic persistence latching), Alarm - Auto reset
(Active diagnostic persistence non-latching), Alarm (Active diagnostic persistence
latching or non-latching), Alarm Ckt1 (Active diagnostic persistence latching or nonlatching), Alarm Ckt2 (Active diagnostic persistence latching or non-latching),
Chiller Limit Mode (With 20 minute filter), Circuit 1 Running, Circuit 2 Running, Max
Capacity
COOP = A, D or X
10-50%
30-255 Sec
1-255 Sec
Contactor Integrity Test, Phase Reversal Detect, Phase Unbalance Detect

2-10 VD

2-10 VDC, 4-20 mA CIOP = C or B

2-10 VDC

2-10 VDC, 4-20 mA CIOP = C or B

400

380,400,415 VOLT = D

• The Model Number field contains the model number stored in the DynaView.
• The Confirm Code field contains the confirm code stored in the DynaView. The confirm code is a four-digit hex value that is a mathematical
calculation of the model number. This number has one to one correlation to a specific model number and is used to verify that the model
number was entered properly.
• The Serial Number field contains the serial number stored in the DynaView.
• This model number and confirmation code must be know when the main processor requires replacement.

RTAC-SVX01M-EN

Controls Interface

Software View

Replacing or Adding Devices

See Figure 44, p. 91. Software view allows you to verify the
version of chiller software currently running and
download a new version of chiller software to DynaView.

If a device is communicating but incorrectly configured, it
might not be necessary to replace it. If the problem with
the device is related to communication, attempt to rebind
it, and if the device becomes correctly configured, it will
then communicate properly.

You can also add up to two available languages to load into
the DynaView. Loading an alternate language file allows
the DynaView to display its text in the selected alternate
language, English will always be available.

Binding View
See Figure 45, p. 91. BindingView allows you to assess the
status of the network and all the devices connected as a
whole, or the status of individual devices by using status
icons and function buttons.
Binding View is essentially a table depicting what devices
and options are actually discovered on the network bus
(and their communication status) versus what is required
to support the configuration defined by the feature codes
and categories. Binding View allows you to add, remove,
modify, verify, and reassign devices and options in order
to match the configuration requirements.
Whenever a device is installed, it must be correctly
configured to communicate and function as intended.This
process is called binding. Some features of Binding View
are intended to serve a second purpose; that is diagnosing
problems with communication among the devices.

If a device that needs to be replaced is still communicating,
it should be unbound. Otherwise, it will be necessary to
rebuild the CH530 network image for Binding View to
discover that it has been removed. An unbound device
stops communicating and allows a new device to be
bound in its place.
It is good practice to turn the power off while detaching
and attaching devices to the CH530 network. Be sure to
keep power on the service tool computer. After power is
restored to the CH530 network, the reconnect function in
BindingView restores communication with the network. If
the service tool computer is turned off, you must restart
TechView and Binding View.
If a device is not communicating, the binding function
displays a window to request manual selection of the
device to be bound. Previously-selected devices are
deselected when the function starts. When manual
selection is confirmed, exactly one device must be
selected; if it is the correct type, it is bound. If the desired
device cannot be selected or if multiple devices are
accidentally selected, you can close the manual selection
window by clicking on No and repeat the bind function.

Figure 38. Unit view

RTAC-SVX01M-EN

89

Controls Interface
Figure 39. Compressor service view

Figure 40. Status view

Figure 41.

Setpoint view(a)

(a) Screenshot is representation only. Values shown may not correspond to actual min/max levels in Table 62, p. 85.

Figure 42. Diagnostic view

90

RTAC-SVX01M-EN

Controls Interface
Figure 43. Configuration view

Figure 44. Software view

Figure 45. Binding view

RTAC-SVX01M-EN

91

Pre-Start Checkout
Upon completion of installation, complete the RTAC Series
R® Air-Cooled Chiller Installation Completion Check Sheet
and Request forTrane Service checklist in chapter “Log
and Check Sheet,” p. 124.
Important:

92

Start-up must be performed byTrane or an
agent ofTrane specifically authorized to
perform start-up and warranty ofTrane
products. Contractor shall provideTrane (or
an agent ofTrane specifically authorized to
perform start-up) with notice of the
scheduled start-up at least two weeks prior
to the scheduled start-up.

RTAC-SVX01M-EN

Start-Up and Shutdown
Important:

Initial unit commissioning start-up must be
performed byTrane or an agent ofTrane
specifically authorized to perform start-up
and warranty ofTrane products. Contractor
shall provideTrane (or an agent ofTrane
specifically authorized to perform start-up)
with notice of the scheduled start-up at least
two weeks prior to the scheduled start-up.

NOTICE:
Compressor Damage!
Catastrophic damage to the compressor will occur if
the oil line shut off valve or the isolation valves are left
closed on unit start-up

The time line for sequence of operation is shown in
Figure 46, p. 96 and Figure 47, p. 98 and depicts the
nominal delays and sequences that a chiller would
experience during a typical operational cycle.The time
line begins with a power up of the main power to the
chiller.The sequence assumes a 2 circuit, 2 compressor aircooled RTAC chiller with no diagnostics or malfunctioning
components. External events such as the operator placing
the chiller in Auto or Stop, chilled water flow through the
evaporator, and application of load to the chilled water
loop causing loop water temperature increases are
depicted and the chillers responses to those events are
shown, with appropriate delays noted.The effects of
diagnostics, and other external interlocks other than
evaporator water flow proving, are not considered.

5. Press the AUTO key. If the chiller control calls for
cooling and all safety interlocks are closed, the unit will
start.The compressor(s) will load and unload in
response to the leaving chilled water temperature.

Note: Unless the CH530TechView and building
automation system are controlling the chilled
water pump, the manual unit start sequence is as
follows. Operator actions are noted.

2. Check the EXV sight glasses after sufficient time has
elapsed to stabilize the chiller.The refrigerant flow past
the sight glasses should be clear. Bubbles in the
refrigerant indicate either low refrigerant charge or
excessive pressure drop in the liquid line or a stuck
open expansion valve. A restriction in the line can
sometimes be identified by a noticeable temperature
differential between the two sides of the restriction.
Frost will often form on the line at this point. Proper
refrigerant charges are shown in the General
Information Section.

NOTICE:
Compressor Damage!
Ensure that the compressor and oil separator heaters
have been operating for a minimum of 24 hours before
starting. Failure to do so could result in equipment
damage.

Unit Start-Up
If the pre-start checkout, has been completed, the unit is
ready to start.
1. Press the STOP key on the CH530.
2. As necessary, adjust the setpoint values in the CH530
menus usingTechView.
3. Close the fused-disconnect switch for the chilled water
pump. Energize the pump(s) to start water circulation.
4. Check the service valves on the discharge line, suction
line, oil line and liquid line for each circuit.These valves
must be open (backseated) before starting the
compressors.

RTAC-SVX01M-EN

6. Verify that the chilled water pump runs for at least one
minute after the chiller is commanded to stop (for
normal chilled water systems).
Once the system has been operating for approximately 30
minutes and has become stabilized, complete the
remaining start-up procedures, as follows:
1. Check the evaporator refrigerant pressure and the
condenser refrigerant pressure under Refrigerant
Report on the CH530TechView.The pressures are
referenced to sea level (14.6960 psia).

Important: A clear sight glass alone does not mean that
the system is properly charged. Also check
system subcooling, liquid level control and
unit operating pressures.
3. Measure the system subcooling.
4. A shortage of refrigerant is indicated if operating
pressures are low and subcooling is also low. If the
operating pressures, sight glass, superheat and
subcooling readings indicate a refrigerant shortage,
gas-charge refrigerant into each circuit, as required.
With the unit running, add refrigerant vapor by
connecting the charging line to the suction service
valve and charging through the backseat port until
operating conditions become normal.

93

Start-Up and Shutdown

NOTICE:
Equipment Damage!
If both suction and discharge pressures are low but subcooling is normal, a problem other than refrigerant
shortage exists. Do not add refrigerant, as this could
result in overcharging the circuit.
Use only refrigerants specified on the unit nameplate
(HFC 134a) and Trane OIL00048. Failure to do so may
cause compressor damage and improper unit operation.

Temporary Shutdown and Restart
To shut the unit down for a short time, use the following
procedure:
1. Press the STOP key on the CH530.The compressors
will continue to operate and, after an unloading period
(which may be followed by pumpdown cycle in
outdoor ambients below 50oF), will stop when the
compressor contactors de-energize.
2. CH530 pump control will turn off the pump (after a
minimum 1 min. delay) when the STOP key is pressed
and automatically restart the pump when the unit
starts normally.
3. The unit will start normally, provided the following
conditions exist:
a. The CH530 receives a call for cooling and the
differential-to-start is above the setpoint.
b. All system operating interlocks and safety circuits
are satisfied.

Extended Shutdown Procedure
The following procedure is to be followed if the system is
to be taken out of service for an extended period of time,
e.g. seasonal shutdown:
1. Test the unit for refrigerant leaks and repair as
necessary.

is wrapped around the bundle itself.They are
energized by a klixon temperature control mounted on
the side of the evaporator, which energizes at or below
37oF. outside air temp. If there is no liquid in the
evaporator and the temp drops below 37 degrees, both
of the well heaters will burn up because they have no
liquid to transfer their heat into.
5. Open the unit main electrical disconnect and unitmounted disconnect (if installed) and lock on the
“OPEN” position. If the optional control power
transformer is not installed, open and lock the 115V
disconnect.

NOTICE:
Equipment Damage!
If insufficient concentration or no glycol is used, the
evaporator water pumps must be controlled by the
CH530 to avoid severe damage to the evaporator due to
freezing. A power loss of 15 minutes during freezing
can damage the evaporator. It is the responsibility of
the installing contractor and/or the customer to ensure
that a pump will start when called upon by the chiller
controls.
Please consult Table 42, p. 54 for correct concentration
of glycol.
The warranty will be void, in case of freezing due to the
lack of use of either of these protections

NOTICE:
Equipment Damage!
Lock the disconnects in the “OPEN” position to
prevent accidental start-up and damage to the system
when it has been setup for extended shutdown.
6. At least every three months (quarterly), check the
refrigerant pressure in the unit to verify that the
refrigerant charge is intact.

2. Open the electrical disconnect switches for the chilled
water pump. Lock the switches in the “OPEN” position.

NOTICE:
Equipment Damage!
To prevent pump damage, lock the chilled water pump
disconnects open.
3. Close all chilled water supply valves. Drain the water
from the evaporator.
4. With the water drained from evaporator, the
“customer provided” power for the 120-volt
evaporator heaters (terminated at 1TB4...terminals 1 &
2) must be must disconnect.
These heaters consist of 1 well heater in each
evaporator end (or water box), and the heat tape, which
94

RTAC-SVX01M-EN

Start-Up and Shutdown

Seasonal Unit Start-Up Procedure
1. Close all valves and re-install the drain plugs in the
evaporator.
2. Service the auxiliary equipment according to the startup/maintenance instructions provided by the
respective equipment manufacturers.
3. Close the vents in the evaporator chilled water circuits.
4. Open all the valves in the evaporator chilled water
circuits.
5. Open all refrigerant valves to verify they are in the
open condition.
6. If the evaporator was previously drained, vent and fill
the evaporator and chilled water circuit. When all air is
removed from the system (including each pass), install
the vent plugs in the evaporator water boxes.
7.

Check the adjustment and operation of each safety and
operating control.

8. Close all disconnect switches.
9. Refer to the sequence for daily unit startup for the
remainder of the seasonal startup.

System Restart After Extended
Shutdown

NOTICE:
Proper Water Treatment!
The use of untreated or improperly treated water in
this equipment could result in scaling, erosion,
corrosion, algae or slime. It is recommended that the
services of a qualified water treatment specialist be
engaged to determine what water treatment, if any, is
required. Trane assumes no responsibility for
equipment failures which result from untreated or
improperly treated water, or saline or brackish water.
4. Close the fused-disconnect switches that provides
power to the chilled water pump.
5. Start the evaporator water pump and, while water is
circulating, inspect all piping for leakage. Make any
necessary repairs before starting the unit.
6. While the water is circulating, adjust the water flows
and check the water pressure drops through the
evaporator. Refer to “Water System Flow Rates” and
“Water System Pressure Drop”.
7. Adjust the flow switch on the evaporator piping for
proper operation.
8. Stop the water pump.The unit is now ready for startup as described in “Start-Up Procedures”.

Follow the procedures below to restart the unit after
extended shutdown:
1. Verify that the liquid line service valves, oil line,
compressor discharge service valves and suction
service valves are open (backseated).

NOTICE:
Compressor Damage!
Catastrophic damage to the compressor will occur if
the oil line shut off valve or the isolation valves are left
closed on unit start-up.
2. Check the oil separator oil level (see Maintenance
Procedures section).
3. Fill the evaporator water circuit. Vent the system while
it is being filled. Open the vent on the top of the
evaporator and condenser while filling and close when
filling is completed.

RTAC-SVX01M-EN

95

Start-Up and Shutdown

Sequence of Operation
Figure 46. Sequence of operations

96

RTAC-SVX01M-EN

Start-Up and Shutdown

RTAC-SVX01M-EN

97

Start-Up and Shutdown

Figure 47.

98

Sequence of operations

RTAC-SVX01M-EN

Start-Up and Shutdown

RTAC-SVX01M-EN

99

Maintenance
Perform all maintenance procedures and inspections at
the recommended intervals.This will prolong the life of
the chiller and minimize the possibility of costly failures.
Use the “Operator’s Log”, such as that show in chapter
“Log and Check Sheet,” p. 124 to record an operating
history for unit.The log serves as a valuable diagnostic
tool for service personnel. By observing trends in
operating conditions, an operator can anticipate and
prevent problem situations before they occur. If unit does
not operate properly during maintenance inspections, see
“Diagnostics,” p. 103.
After unit has been operating for approximately 30
minutes and system has stabilized, check the operating
conditions and complete procedures below:

Weekly
While unit is running in stable conditions.
1. Check MP pressure for evaporator, condenser and
intermediate oil.

6. Clean and repaint any areas that show signs of
corrosion.
7.

Clean the condenser coils.

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN

2. Observe liquid line sight glass on EXV.
3. If liquid line sight glass has bubbles measure the
subcooling entering the EXV.The subcooling should
never be less than 4°F under any circumstances.
Important: A clear sightglass alone does not mean that
the system is properly charged. Also check
the rest of the system operating conditions.

8. Check and tighten all electrical connections as
necessary.

Refrigerant and Oil Charge
Management

4. Inspect the entire system for unusual conditions and
inspect the condenser coils for dirt and debris. If the
coils are dirty, refer to coil cleaning.

Proper oil and refrigerant charge is essential for proper
unit operation, unit performance, and environmental
protection. Only trained and licensed service personnel
should service the chiller.

Monthly

Table 64 lists baseline measurements for RTAC units
running at AHRI standard operating conditions. If chiller
measurements vary significantly from values listed below,
problems may exist with refrigerant and oil charge levels.
Contact your localTrane office.

1. Perform all weekly maintenance procedures.
2. Record the system subcooling.
3. Make any repairs necessary.

Annual

Note: Low temperature applications units will have
values that vary from Table 64. Contact your local
Trane office for more information.

1. Perform all weekly and monthly procedures.

Table 64.

Typical RTAC baselines (AHRI conditions)

2. Check oil sump oil level while unit is off.

Measurement

Baseline

Note: Routine changing of oil is not required. Use an oil
analysis to determine condition of oil.

Evaporator Pressure

49.5 psia

Evaporator Approach

3.5°F

3. Have a qualified laboratory perform a compressor oil
analysis to determine system moisture content and
acid level.This analysis is a valuable diagnostic tool.

EXV Position

45-50%

4. Contact a qualified service organization to leak test the
chiller, to check operating and safety controls, and to
inspect electrical components for deficiencies.
5. Inspect all piping components for leakage and
damage. Clean out any inline strainers.

100

Evaporator - entering

54°

Evaporator - leaving

44°

Discharge Superheat

26.6°F

Condenser Pressure

226 psia

Subcooling

18-23°F

RTAC-SVX01M-EN

Maintenance

Lubrication System

and the unit is in vacuum so that there is no refrigerant
dissolved in the oil.

The lubrication system has been designed to keep most of
the oil lines filled with oil as long as there is a proper oil
level in the oil sump.

Oil Sump Level Check

3. After the unit has run for a while, the oil level in the
sump can vary greatly. However, if the unit has run
“normal” conditions for a long time the level should
resemble the level in the above chart.
• +1” to – 4” (25 to -101mm) is acceptable

Oil system consists of the following components:
•

Compressor

•

Oil separator

•

Discharge line with service valve

•

Oil line from separator to compressor

•

Oil line drain (lowest point in system)

•

Oil cooler - optional

•

Oil temperature sensor

•

Oil line shut off valve with flare service connection

•

Oil filter (internal to compressor) with flare fitting
service connection and schrader valve

•

Oil flow control valve (internal to the compressor after
the filter)

•

Oil return line from evaporator with shut off valve and
strainer

Important:

If levels are outside these ranges, contact
your localTrane office.

Condenser Maintenance
Condenser Coil Cleaning
WARNING
Hazardous Chemicals!

Refer to Table 1, p. 10 throughTable 10, p. 19 for the
standard oil charge for each circuit.
Note: It is recommended to check the oil level in the sump
using a sight glass or a manometer, attached to
charging hoses.
Table 65. Oil charging data

Coil cleaning agents can be either acidic or highly
alkaline and can burn severely if contact with skin
occurs. Handle chemical carefully and avoid contact
with skin. ALWAYS wear Personal Protective Equipment
(PPE) including goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For
personal safety refer to the cleaning agent
manufacturer’s Materials Safety Data Sheet and follow
all recommended safe handling practices. Failure to
follow all safety instructions could result in death or
serious injury.
Clean the condenser coils at least once a year or more
frequently if the unit is in a “dirty” environment. A clean
condenser coil will help to maintain chiller operating
efficiency. Follow the detergent manufacturer's
instructions to avoid damaging the condenser coils.

Circuit
(Tons)

Approximate sump oil
level after running
“normal” conditions
(in)

Normal quantity of oil in
refrigeration system
(evaporator/
condenser)
lb (gal)

To clean the condenser coils use a soft brush and a sprayer
such as a garden pump type or a high-pressure type. A
high quality detergent such asTrane Coil Cleaner (Part No.
CHM-00255) is recommended.

70

7

1.1 (0.14)

85

6

1.1 (0.14)

Note: If detergent mixture is strongly alkaline (pH value
greater than 8.5, an inhibitor must be added).

100

7

1.8 (0.23)

120

7

1.8 (0.23)

170

8

3.5 (0.44)

200

8

3.5 (0.44)

240

8

3.5 (0.44)

1. To measure oil level, use the oil drain valve on the oil
line and a service valve on the discharge line.This
measurement can only be made when the circuit is not
running.
Note: The level is measured from the bottom of the
separator and 1” must be subtracted for the
thickness of the bottom plate.
2. The initial oil charge should be approximately at the
level in the above chart.This is the approximate oil
level if all the oil is in the oil lines, filter and oil sump
RTAC-SVX01M-EN

101

Maintenance

Travel Restraint
WARNING
Falling Off Equipment!
This unit is built with fall restraint slots located on unit
top that MUST be used during servicing. These slots are
to be used with fall restraint equipment that will not
allow an individual to reach the unit edge. However
such equipment will NOT prevent falling to the ground,
for they are NOT designed to withstand the force of a
falling individual. Failure to use fall restraint slots and
equipment could result in individual falling off the unit
which could result in death or serious injury.
This unit is built with travel restraint slots located on unit
top that must be used during servicing. See Figure 48.
Figure 48. Roof view - travel restraint slots

Travel Restraint Slots

102

RTAC-SVX01M-EN

Diagnostics
Legend to Diagnostics Table
Legacy Hex Code: 3 digit hexadecimal code used on all
past products to uniquely identify diagnostics.
Diagnostic Name and Source: Name of Diagnostic and
its source. Note that this is the exact text used in the User
Interface and/or ServiceTool displays.
Affects Target: Defines the “target” or what is affected
by the diagnostic. Usually either the entire Chiller, or a
particular Circuit or Compressor is affected by the
diagnostic (the same one as the source), but in special
cases functions are modified or disabled by the diagnostic.
None implies that there is no direct affect to the chiller, sub
components or functional operation.
Severity: Defines the severity of the above effect.
Immediate means immediate shutdown of the effected
portion, Normal means normal or friendly shutdown of
the effected portion, Special Mode means a special mode
of operation (limp along) is invoked, but without
shutdown, and Info means an Informational Note or
Warning is generated.
Persistence: Defines whether or not the diagnostic and
its effects are to be manually reset (Latched), or can be
either manually or automatically reset (Nonlatched).

Active Modes [Inactive Modes]: States the modes or
periods of operation that the diagnostic is active in and, as
necessary, those modes or periods that it is specifically not
active in as an exception to the active modes.The inactive
modes are enclosed in brackets, [ ]. Note that the modes
used in this column are internal and not generally
annunciated to any of the formal mode displays
Criteria: Quantitatively defines the criteria used in
generating the diagnostic and, if nonlatching, the criteria
for auto reset. If more explanation is necessary a hot link
to the Functional Specification is used.
Reset Level: Defines the lowest level of manual
diagnostic reset command which can clear the diagnostic.
The manual diagnostic reset levels in order of priority are:
Local or Remote. For example, a diagnostic that has a
reset level of Remote, can be reset by either a remote
diagnostic reset command or by a local diagnostic reset
command.
HelpText: Provides for a brief description of what kind of
problems might cause this diagnostic to occur. Both
control system component related problems as well as
chiller application related problems are addressed (as can
possibly be anticipated).These help messages will be
updated with accumulated field experience with the
chillers.

Starter Diagnostics
Table 66. Starter diagnostics
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]
Motor Current
Overload Compressor 1A
Motor Current
Overload Compressor 1B
Motor Current
Overload Compressor 2A
Motor Current
Overload Compressor 2B

Circuit Immediate

Latch

Cprsr
Energized

Circuit Immediate

Latch

Cprsr
Energized

Circuit Immediate

Latch

Cprsr
Energized

Circuit Immediate

Latch

Cprsr
Energized

Over Voltage

Chiller

Normal

NonLatch

Phase Loss Compressor 1A

Cprsr

Immediate

Latch

RTAC-SVX01M-EN

Reset
Level

Criteria
Compressor current exceeded overload time vs. trip
characteristic. For A/C products Must trip = 140% RLA,
hold=125%, nominal trip 132.5% in 30 seconds
Compressor current exceeded overload time vs. trip
characteristic. For A/C products Must trip = 140% RLA,
hold=125%, nominal trip 132.5% in 30 seconds
Compressor current exceeded overload time vs. trip
characteristic. For A/C products Must trip = 140% RLA,
hold=125%, nominal trip 132.5% in 30 seconds
Compressor current exceeded overload time vs. trip
characteristic. For A/C products Must trip = 140% RLA,
hold=125%, nominal trip 132.5% in 30 seconds

Must

Local

Must

Local

Must

Local

Must

Local

Pre-Start and
Nom. trip: 60 seconds at greater than 112.5%, 2.5%, Auto Reset
Any Ckt(s)
Remote
at 109% or less.
Energzd
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
Start
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
Sequence guaranteed reset on Starter Module at a minimum, 3 seconds
Local
and Run
maximum. Actual design trip point is 10%. The actual design trip
modes
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current transformer
inputs. Logic will detect and trip in a maximum of 0.3 second from
compressor start.

103

Diagnostics
Table 66. Starter diagnostics (continued)
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]

Phase Loss Compressor 1B

Cprsr

Immediate

Latch

Start
Sequence
and Run
modes

Phase Loss Compressor 2A

Cprsr

Immediate

Latch

Start
Sequence
and Run
modes

Phase Loss Compressor 2B

Cprsr

Immediate

Latch

Start
Sequence
and Run
modes

Phase Reversal Compressor 1A

Cprsr

Immediate

Latch

Phase Reversal Compressor 1B

Cprsr

Immediate

Latch

Phase Reversal Compressor 2A

Cprsr

Immediate

Latch

Phase Reversal Compressor 2B

Cprsr

Immediate

Latch

Power Loss Compressor 1A

104

Cprsr

Immediate

NonLatch

Compressor
energized to
transition
command
[All Other
Times]
Compressor
energized to
transition
command
[All Other
Times]
Compressor
energized to
transition
command
[All Other
Times]
Compressor
energized to
transition
command
[All Other
Times]

All
compressor
running
modes
[all
compressor
starting and
non-running
modes]

Reset
Level

Criteria
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trip point is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current transformer
inputs. Logic will detect and trip in a maximum of 0.3 second from
compressor start
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trip point is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current transformer
inputs. Logic will detect and trip in a maximum of 0.3 second from
compressor start
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trip point is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current transformer
inputs. Logic will detect and trip in a maximum of 0.3 second from
compressor start

Local

Local

Local

A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.

Local

A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.

Local

A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.

Local

A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.

Local

The compressor had previously established currents while
running and then all three phases of current were lost. Design:
Less than 10% RLA, trip in 2.64 seconds. This diagnostic will
preclude the Phase Loss Diagnostic and the Transition Complete
Input Opened Diagnostic from being called out. To prevent this
diagnostic from occurring with the intended disconnect of main
power, the minimum time to trip must be greater than the
guaranteed reset time of the Starter module. Note: This
Remote
diagnostic prevents nuisance latching diagnostics due to a
momentary power loss - It does not protect motor/compressor
from uncontrolled power reapplication. See Momentary Power
Loss Diagnostic for this protection. This diagnostic is not active
during the start mode before the transition complete input is
proven. Thus a random power loss during a start would result in
either a “Starter Fault Type 3" or a “Starter Did Not Transition”
latching diagnostic.

RTAC-SVX01M-EN

Diagnostics
Table 66. Starter diagnostics (continued)
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]

Power Loss Compressor 1B

Power Loss Compressor 2A

Power Loss Compressor 2B

Severe Current
Imbalance Compressor 1A
Severe Current
Imbalance Compressor 1B
Severe Current
Imbalance Compressor 2A
Severe Current
Imbalance Compressor 2B

Cprsr

Cprsr

Cprsr

Immediate

Immediate

Immediate

NonLatch

NonLatch

NonLatch

All
compressor
running
modes
[all
compressor
starting and
non-running
modes]
All
compressor
running
modes
[all
compressor
starting and
non-running
modes]
All
compressor
running
modes
[all
compressor
starting and
non-running
modes]

Criteria

Reset
Level

The compressor had previously established currents while
running and then all three phases of current were lost. Design:
Less than 10% RLA, trip in 2.64 seconds. This diagnostic will
preclude the Phase Loss Diagnostic and the Transition Complete
Remote
Input Opened Diagnostic from being called out. To prevent this
diagnostic from occurring with the intended disconnect of main
power, the minimum time to trip must be greater than the
guaranteed reset time of the Starter module.
The compressor had previously established currents while
running and then all three phases of current were lost. Design:
Less than 10% RLA, trip in 2.64 seconds. This diagnostic will
preclude the Phase Loss Diagnostic and the Transition Complete
Remote
Input Opened Diagnostic from being called out. To prevent this
diagnostic from occurring with the intended disconnect of main
power, the minimum time to trip must be greater than the
guaranteed reset time of the Starter module.
The compressor had previously established currents while
running and then all three phases of current were lost. Design:
Less than 10% RLA, trip in 2.64 seconds. This diagnostic will
preclude the Phase Loss Diagnostic and the Transition Complete
Remote
Input Opened Diagnostic from being called out. To prevent this
diagnostic from occurring with the intended disconnect of main
power, the minimum time to trip must be greater than the
guaranteed reset time of the Starter module.

Circuit Immediate

Latch

All Running A 30% Current Imbalance has been detected on one phase
Modes
relative to the average of all 3 phases for 90 continuous seconds.

Local

Circuit Immediate

Latch

All Running A 30% Current Imbalance has been detected on one phase
Modes
relative to the average of all 3 phases for 90 continuous seconds.

Local

Circuit Immediate

Latch

All Running A 30% Current Imbalance has been detected on one phase
Local
Modes
relative to the average of all 3 phases for 90 continuous seconds

Circuit Immediate

Latch

All Running A 30% Current Imbalance has been detected on one phase
Local
Modes
relative to the average of all 3 phases for 90 continuous seconds.

Starter 1A Dry Run
Test

Cprsr

Immediate

Latch

Starter 1B Dry Run
Test

Cprsr

Immediate

Latch

Starter 2A Dry Run
Test

Cprsr

Immediate

Latch

Starter 2B Dry Run
Test

Cprsr

Immediate

Latch

Starter Contactor
Interrupt Failure Compressor 2A

Chiller

Special
Mode

Latch

RTAC-SVX01M-EN

While in the Starter Dry Run Mode either 50% Line Voltage was
Starter Dry
sensed at the Potential Transformers or 10% RLA Current was
Run Mode
sensed at the Current Transformers.
While in the Starter Dry Run Mode either 50% Line Voltage was
Starter Dry
sensed at the Potential Transformers or 10% RLA Current was
Run Mode
sensed at the Current Transformers.
While in the Starter Dry Run Mode either 50% Line Voltage was
Starter Dry
sensed at the Potential Transformers or 10% RLA Current was
Run Mode
sensed at the Current Transformers.
While in the Starter Dry Run Mode either 50% Line Voltage was
Starter Dry
sensed at the Potential Transformers or 10% RLA Current was
Run Mode
sensed at the Current Transformers.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
Starter
shall be 5 second minimum and 10 seconds maximum. On
Contactor
detection and until the controller is manually reset: generate
not
diagnostic, energize the appropriate alarm relay, continue to
Energized
energize the Evap Pump Output, continue to command the
[Starter
affected compressor off, fully unload the effected compressor and
Contactor
command a normal stop to all other compressors. For as long as
Energized]
current continues, perform liquid level and fan control on the
circuit effected.

Local

Local
Local

Local

Local

105

Diagnostics
Table 66. Starter diagnostics (continued)
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]

Starter Contactor
Interrupt Failure Compressor 1A

Starter Contactor
Interrupt Failure Compressor 1B

Chiller

Chiller

Special
Mode

Special
Mode

Latch

Starter
Contactor
not
Energized
[Starter
Contactor
Energized]

Latch

Starter
Contactor
not
Energized
[Starter
Contactor
Energized]

Starter Contactor
Interrupt Failure Compressor 2B

Chiller

Special
Mode

Latch

Starter
Contactor
not
Energized
[Starter
Contactor
Energized]

Starter Did Not
Transition Compressor 1A

Cprsr

Immediate

Latch

On the first
check after
transition.

Starter Did Not
Transition Compressor 1B

Cprsr

Immediate

Latch

On the first
check after
transition.

Starter Did Not
Transition Compressor 2A

Cprsr

Immediate

Latch

On the first
check after
transition.

Starter Did Not
Transition Compressor 2B

Cprsr

Immediate

Latch

On the first
check after
transition.

Starter Fault Type I Compressor 1A

Cprsr

Immediate

Latch

Starting - Y
Delta
Starters Only

Starter Fault Type I Compressor 1B

Cprsr

Immediate

Latch

Starting - Y
Delta
Starters Only

Starter Fault Type I Compressor 2A

Cprsr

Immediate

Latch

Starting - Y
Delta
Starters Only

106

Reset
Level

Criteria
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
This is a specific starter test where 1M(1K1) is closed first and a
check is made to ensure that there are no currents detected by
the CT's. If currents are detected when only 1M is closed first at
start, then one of the other contactors is shorted.
This is a specific starter test where 1M(1K1) is closed first and a
check is made to ensure that there are no currents detected by
the CT's. If currents are detected when only 1M is closed first at
start, then one of the other contactors is shorted.
This is a specific starter test where 1M(1K1) is closed first and a
check is made to ensure that there are no currents detected by
the CT's. If currents are detected when only 1M is closed first at
start, then one of the other contactors is shorted.

Local

Local

Local

Local

Local

Local

Local

Local

Local

Local

RTAC-SVX01M-EN

Diagnostics
Table 66. Starter diagnostics (continued)
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]
Starter Fault Type I Compressor 2B

Cprsr

Immediate

Latch

Starter Fault Type II Compressor 1A

Cprsr

Immediate

Latch

Starter Fault Type II Compressor 1B

Cprsr

Immediate

Latch

Starter Fault Type II Compressor 2A

Cprsr

Immediate

Latch

Starter Fault Type II Compressor 2B

Cprsr

Immediate

Latch

Starter Fault Type III
- Compressor 1A

Cprsr

Immediate

Latch

Starter Fault Type III
- Compressor 1B

Cprsr

Immediate

Latch

Starter Fault Type III
- Compressor 2A

Cprsr

Immediate

Latch

Starter Fault Type III
- Compressor 2B

Cprsr

Immediate

Latch

Transition Complete
Input Opened Compressor 1A

Cprsr

Immediate

Latch

Transition Complete
Input Opened Compressor 1B

Cprsr

Immediate

Latch

RTAC-SVX01M-EN

Criteria

This is a specific starter test where 1M(1K1) is closed first and a
Starting - Y
check is made to ensure that there are no currents detected by
Delta
the CT's. If currents are detected when only 1M is closed first at
Starters Only
start, then one of the other contactors is shorted.
a. This is a specific starter test where the Shorting Contactor
(1K3) is individually energized and a check is made to ensure that
Starting All
there are no currents detected by the CT's. If current is detected
types of
when only S is energized at Start, then 1M is shorted. b. This test
starters
in a. above applies to all forms of starters (Note: It is understood
that many starters do not connect to the Shorting Contactor.).
a. This is a specific starter test where the Shorting Contactor
(1K3) is individually energized and a check is made to ensure that
Starting - All
there are no currents detected by the CT's. If current is detected
types of
when only S is energized at Start, then 1M is shorted. b. This test
starters
in a. above applies to all forms of starters (Note: It is understood
that many starters do not connect to the Shorting Contactor.).
a. This is a specific starter test where the Shorting Contactor
(1K3) is individually energized and a check is made to ensure that
Starting - All
there are no currents detected by the CT's. If current is detected
types of
when only S is energized at Start, then 1M is shorted. b. This test
starters
in a. above applies to all forms of starters (Note: It is understood
that many starters do not connect to the Shorting Contactor.).
a. This is a specific starter test where the Shorting Contactor
(1K3) is individually energized and a check is made to ensure that
Starting - All
there are no currents detected by the CT's. If current is detected
types of
when only S is energized at Start, then 1M is shorted. b. This test
starters
in a. above applies to all forms of starters (Note: It is understood
that many starters do not connect to the Shorting Contactor.).
As part of the normal start sequence to apply power to the
Starting
compressor, the Shorting Contactor (1K3) and then the Main
[Adaptive Contactor (1K1) were energized. 1.6 seconds later there were no
Frequency currents detected by the CT's for the last 1.2 Seconds on all three
Starter Type] phases. The test above applies to all forms of starters except
Adaptive Frequency Drives.
As part of the normal start sequence to apply power to the
Starting
compressor, the Shorting Contactor (1K3) and then the Main
[Adaptive Contactor (1K1) were energized. 1.6 seconds later there were no
Frequency currents detected by the CT's for the last 1.2 seconds on all three
Starter Type] phases. The test above applies to all forms of starters except
Adaptive Frequency Drives.
As part of the normal start sequence to apply power to the
Starting
compressor, the Shorting Contactor (1K3) and then the Main
[Adaptive Contactor (1K1) were energized. 1.6 seconds later there were no
Frequency currents detected by the CT's for the last 1.2 seconds on all three
Starter Type] phases. The test above applies to all forms of starters except
Adaptive Frequency Drives.
As part of the normal start sequence to apply power to the
Starting
compressor, the Shorting Contactor (1K3) and then the Main
[Adaptive Contactor (1K1) were energized. 1.6 seconds later there were no
Frequency currents detected by the CT's for the last 1.2 seconds on all three
Starter Type] phases. The test above applies to all forms of starters except
Adaptive Frequency Drives.
The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of
transition. This is active only for Y-Delta, Auto-Transformer,
All running
Primary Reactor, and X-Line Starters. To prevent this diagnostic
modes
from occurring as the result of a power loss to the contactors, the
minimum time to trip must be greater than the trip time for the
power loss diagnostic.
The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of
transition. This is active only for Y-Delta, Auto-Transformer,
All running
Primary Reactor, and X-Line Starters. To prevent this diagnostic
modes
from occurring as the result of a power loss to the contactors, the
minimum time to trip must be greater than the trip time for the
power loss diagnostic.

Reset
Level
Local

Local

Local

Local

Local

Local

Local

Local

Local

Local

Local

107

Diagnostics
Table 66. Starter diagnostics (continued)
Active
Modes
Diagnostic Name Affects
[Inactive
and Source
Target Severity Persistence Modes]
Transition Complete
Input Opened Compressor 2A

Cprsr

Immediate

Latch

Transition Complete
Input Opened Compressor 2B

Cprsr

Immediate

Latch

Cprsr

Immediate

Latch

Cprsr

Immediate

Latch

Cprsr

Immediate

Latch

Cprsr

Immediate

Latch

Chiller

Normal

NonLatch

Transition Complete
Input Shorted Compressor 1A
Transition Complete
Input Shorted Compressor 1B
Transition Complete
Input Shorted Compressor 2A
Transition Complete
Input Shorted Compressor 2B
Under Voltage

Reset
Level

Criteria

The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of
transition. This is active only for Y-Delta, Auto-Transformer,
All running
Primary Reactor, and X-Line Starters. To prevent this diagnostic Local
modes
from occurring as the result of a power loss to the contactors, the
minimum time to trip must be greater than the trip time for the
power loss diagnostic.
The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of
transition. This is active only for Y-Delta, Auto-Transformer,
All running
Primary Reactor, and X-Line Starters. To prevent this diagnostic Local
modes
from occurring as the result of a power loss to the contactors, the
minimum time to trip must be greater than the trip time for the
power loss diagnostic.
The Transition Complete input was found to be shorted before the
Pre-Start compressor was started. This is active for all electromechanical Local
starters.
The Transition Complete input was found to be shorted before the
Pre-Start compressor was started. This is active for all electromechanical Local
starters.
The Transition Complete input was found to be shorted before the
Pre-Start compressor was started. This is active for all electromechanical Local
starters.
The Transition Complete input was found to be shorted before the
Pre-Start compressor was started. This is active for all electromechanical Local
starters.
Pre-Start and
Nom. trip: 60 seconds at less than 87.5%, 2.8% at 200V 1.8%
Any Ckt(s)
Remote
at 575V, Auto Reset at 90% or greater.
Energzd

Main Processor Diagnostics
Table 67. Main processor diagnostics
Affects
PersistDiagnostic Name Target Severity
ence

BAS Communication
Lost

BAS Failed to
Establish
Communication

Check Clock

None

None

Chiller

Condenser Fan
All
Variable Speed
inverters
Drive Fault - Circuit on this
1 (Drive 1)
circuit

108

Special

Special

Info

Special
Mode

NonLatch

NonLatch

Latch

Latch

Active Modes
[Inactive
Modes]

All

At power-up

All

Reset
Level

Criteria

The BAS was setup as “installed” at the MP and the Comm 3 llid
lost communications with the BAS for 15 contiguous minutes
after it had been established. Refer to Section on Setpoint
Arbitration to determine how setpoints and operating modes
Remote
may be effected by the comm loss. The chiller follows the value
of the Tracer Default Run Command which can be previously
written by Tracer and stored nonvolatilely by the MP (either use
local or shutdown).
The BAS was setup as “installed” and the BAS did not
communicate with the MP within 15 minutes after power-up.
Refer to Section on Setpoint Arbitration to determine how
setpoints and operating modes may be effected. Note: The
original requirement for this was 2 minutes, but was
implemented at 15 minutes for RTAC.

Remote

The real time clock had detected loss of its oscillator at some
time in the past. Check / replace battery? This diagnostic can be
effectively cleared only by writing a new value to the chiller's Remote
time clock using the TechView or DynaView's “set chiller time”
functions.

The MP has received a fault signal from the respective condenser
fan Variable Speed Inverter Drive, and unsuccessfully attempted
Prestart and
(5 times within 1 minute of each other) to clear the fault. The 4th
Running w/
attempt removes power from the inverter to create a power up
Remote
Variable Spd Fan reset. If the fault does not clear, the MP will revert to constant
enabled
speed operation without the use of the inverter's fan. The
inverter must be manually bypassed, and fan outputs rebound,
for full fixed speed fan operation.

RTAC-SVX01M-EN

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence

Condenser Fan
All
Variable Speed
inverters
Drive Fault - Circuit on this
1 Drive 2
circuit

Condenser Fan
All
Variable Speed
inverters
Drive Fault - Circuit on this
2 (Drive 1)
circuit

Condenser Fan
All
Variable Speed
inverters
Drive Fault - Circuit on this
2 (Drive 2)
circuit

Active Modes
[Inactive
Modes]

Criteria

Reset
Level

Latch

The MP has received a fault signal from the respective condenser
fan Variable Speed Inverter Drive, and unsuccessfully attempted
Prestart and
(5 times within 1 minute of each other) to clear the fault. The 4th
Running w/
attempt removes power from the inverter to create a power up
Remote
Variable Spd Fan reset. If the fault does not clear, the MP will revert to constant
enabled
speed operation without the use of the inverter's fan. The
inverter must be manually bypassed, and fan outputs rebound,
for full fixed speed fan operation.

Latch

The MP has received a fault signal from the respective condenser
fan Variable Speed Inverter Drive, and unsuccessfully attempted
Prestart and
(5 times within 1 minute of each other) to clear the fault. The 4th
Running w/
attempt removes power from the inverter to create a power up
Remote
Variable Spd Fan reset. If the fault does not clear, the MP will revert to constant
enabled
speed operation without the use of the inverter's fan. The
inverter must be manually bypassed, and fan outputs rebound,
for full fixed speed fan operation.

Special
Mode

Latch

The MP has received a fault signal from the respective condenser
fan Variable Speed Inverter Drive, and unsuccessfully attempted
Prestart and
(5 times within 1 minute of each other) to clear the fault. The 4th
Running w/
attempt removes power from the inverter to create a power up
Remote
Variable Spd Fan reset. If the fault does not clear, the MP will revert to constant
enabled
speed operation without the use of the inverter's fan. The
inverter must be manually bypassed, and fan outputs rebound,
for full fixed speed fan operation.

Special
Mode

Special
Mode

Condenser
Refrigerant Pressure
Transducer - Circuit
1

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

Condenser
Refrigerant Pressure
Transducer - Circuit
2

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

Emergency Stop

Chiller

Immediate

Latch

All

a. EMERGENCY STOP input is open. An external interlock has
tripped. Time to trip from input opening to unit stop shall be 0.1
to 1.0 seconds.

Evaporator Entering
Water Temperature
Sensor

Chilled
Water
Reset

Info

Latch

All

Bad Sensor or LLID a. Normal operation, no effects on control.
b. Chiller shall remove any Return or Constant Return Chilled
Remote
Water Reset, if it was in effect. Apply slew rates per Chilled Water
Reset spec.

Evaporator Leaving
Water Temperature
Sensor

Chiller

Normal

Latch

All

Bad Sensor or LLID

Remote

Evaporator Liquid
Level Sensor Circuit 1

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

Evaporator Liquid
Level Sensor Circuit 2

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

Latch

Circuit nonrunning modes
[Drain Valve
commanded
closed]

This diagnostic is effective only with Remote Evap units. The
liquid level of the respective evaporator was not seen to be below
the level of -21.2 mm within 5 minutes of the commanded
Remote
opening of its Drain Valve Solenoid. The diagnostic will not be
active if the drain valve is commanded closed.

Latch

Circuit nonrunning modes
[Drain Valve
commanded
closed]

This diagnostic is effective only with Remote Evap units. The
liquid level of the respective evaporator was not seen to be below
the level of -21.2 mm within 5 minutes of the commanded
Remote
opening of its Drain Valve Solenoid Valve. The diagnostic will not
be active if the drain valve is commanded closed.

Evaporator Rfgt
Drain - Circuit 1

Circuit

NA

Evaporator Rfgt
Drain - Circuit 2

Circuit

Evaporator Water
Flow (Entering
Water Temp)

Chiller

Immediate
Latching
Shutdown

Evaporator Water
Flow (High Approach
Temperature)Circuit 1

Chiller

Immediate
Latching
Shutdown

RTAC-SVX01M-EN

NA

Any Ckt Energized The entering evaporator water temp fell below the leaving
[No Ckts
evaporator water temp by more than 2°F for 180°F-sec,
Energized]
minimum trip time 1 minute.
Ckt Energized
[Ckt Not
Energized]

Local

Remote

Large evaporator approach temps, low evap sat temps, and
presence of liquid refrigerant, suggest this circuit is running with Remote
no or reversed evaporator water flow.

109

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence
Evaporator Water
Flow (High Approach
Temperature)Circuit 2

Evaporator Water
Flow Lost

Evaporator Water
Flow Overdue

External Chilled
Water Setpoint

Chiller

Chiller

Chiller

None

Immediate
Latching
Shutdown

Active Modes
[Inactive
Modes]
Ckt Energized
[Ckt Not
Energized]

Criteria

Reset
Level

Large evaporator approach temps, low evap sat temps, and
presence of liquid refrigerant, suggest this circuit is running with Remote
no or reversed evaporator water flow.

Whenever Evap
Pump is
commanded on
Immediate NonLatch
due to Auto mode
and certain offcycle diagnostics

a. The Evaporator water flow switch input was open for more
than 6-10 sec (HV binary input) or 20-25* sec (for factory mtd
low voltage binary input) b. This diagnostic does not deenergize the evap pump output c. 6-10 seconds of contiguous
flow shall clear this diagnostic. d. Even though the pump times Remote
out in the STOP modes, this diagnostic shall not be called out in
the STOP modes, (with the exception of pump override due to
certain off-cycle diagnostics). * could be longer if water temps
are rapidly changing warmer

Whenever Evap
Pump is
commanded on
NonLatch
due to Auto mode
and certain offcycle diagnostics

Evaporator water flow was not proven within 4:15 (RTAC Rev 20
and earlier) or 20:00 (RTAC Rev 21) of the Evaporator water
pump relay being energized. With SW Rev 17.0 and earlier, the
diagnostic will de-energize the Evaporator Water Pump output.
It will be re-energized if the diagnostic clears with the return of
flow and the chiller will be allowed to restart normally (to
Remote
accommodate external control of pump) With SW Rev 18.0 and
later, the pump command status will not be effected. In the case
of certain “Off-cycle” diagnostics in which the pump is
overridden to on, the delay to callout of the diagnostic is
shortened to 4:15.

NonLatch

All

a. Function Not “Enabled”: no diagnostics. b. “Enabled “: OutOf-Range Low or Hi or bad LLID, set diagnostic, default CWS to
next level of priority (e.g. Front Panel SetPoint). This Info
Remote
diagnostic will automatically reset if the input returns to the
normal range.

All

a. Not “Enabled”: no diagnostics. b. “Enabled “: Out-Of-Range
Low or Hi or bad LLID, set diagnostic, default CLS to next level
Remote
of priority (e.g. Front Panel SetPoint. This Info diagnostic will
automatically reset if the input returns to the normal range.

Normal

Info

External Current
Limit Setpoint

None

Info

NonLatch

High Differential
Refrigerant Pressure
- Circuit 1

Circuit

Normal

Latch

The system differential pressure for the respective circuit was
Cprsr Energized above 275 Psid for 2 consecutive samples or more than 10
Remote
seconds.

High Differential
Refrigerant Pressure
- Circuit 2

Circuit

Normal

Latch

The system differential pressure for the respective circuit was
Cprsr Energized above 275 Psid for 2 consecutive samples or more than 10
Remote
seconds

Latch

The liquid level sensor is seen to be at or near its high end of
Starter Contactor range for 80 contiguous minutes while the compressor is
Energized
running. (The diagnostic timer will hold, but not clear when the Remote
[all Stop modes] circuit is off). Design: 80% or more of bit count corresponding
to +21.2 mm or more liquid level for 80 minutes)

Latch

The liquid level sensor is seen to be at or near its high end of
Starter Contactor range for 80 contiguous minutes while the compressor is
Energized
running. (The diagnostic timer will hold, but not clear when the Remote
[all Stop modes] circuit is off). Design: 80% or more of bit count corresponding
to +21.2 mm or more liquid level for 80 minutes)

High Evaporator
Liquid Level - Circuit
1

High Evaporator
Liquid Level - Circuit
2

Circuit

Circuit

High Evaporator
Chiller
Refrigerant Pressure

110

Normal

Normal

Immediate NonLatch

All

The evaporator refrigerant pressure of either circuit has risen
above 190 psig. The evaporator water pump relay will be deenergized to stop the pump regardless of why the pump is
running (and the chiller will be prevented from starting) The
diagnostic will auto reset and the pump will return to normal
control when all of the evaporator pressures fall below 185 psig. Remote
The primary purpose is to stop the evaporator water pump and
its associated pump heat from causing refrigerant side
pressures, close to the evaporator relief valve setting, when the
chiller is not running, such as could occur with Evap Water Flow
Overdue or Evaporator Water Flow Loss Diagnostics.

RTAC-SVX01M-EN

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence

Active Modes
[Inactive
Modes]

High Evaporator
Water Temperature

Only effective if
either
Info and
1)Evap Wtr Flow
Special
Overdue,
Action (Pre
2)Evap Wtr Flow
Chiller
NonLatch
RTAC
Loss, or
Refresh
3)Low Evap Rfgt
Rev 39)
Temp,-Unit Off,
diagnostic is
active.

High Evaporator
Water Temperature

Only effective if
either
1)Evap Wtr Flow
Overdue
2)Evap Wtr Flow
Loss, or
3)Low Evap Rfgt
Temp,-Unit Off,
diagnostic is
active.

High Oil
Temperature Compressor 1B

High Oil
Temperature Compressor 2B

High Oil
Temperature Compressor 1A

High Oil
Temperature Compressor 2A

High Pressure
Cutout Compressor 1A

High Pressure
Cutout Compressor 1B

RTAC-SVX01M-EN

Chiller

Immediate
Shutdown
(Beginning
with RTAC
Refresh
Rev 39)

Cprsr 1B Immediate

Cprsr 2B Immediate

Cprsr 1A Immediate

Cprsr 2A Immediate

Circuit

Circuit

Immediate

Immediate

Latch

Latch

Latch

Latch

Latch

Latch

Latch

Criteria

Reset
Level

The leaving water temperature exceeded the high evap water
temp limit (TV service menu settable -default 105F) for 15
continuous seconds. The evaporator water pump relay will be
de-energized to stop the pump but only if it is running due to one
of the diagnostics listed on the left. The diagnostic will auto reset
and the pump will return to normal control when the
temperature falls 5 F below the trip setting. The primary purpose
Remote
is to stop the evaporator water pump and its associated pump
heat from causing excessive waterside temperatures and
waterside pressures when the chiller is not running but the evap
pump is on due to either Evap Water Flow Overdue, Evaporator
Water Flow Loss, or Low Evap Temp - Unit Off Diagnostics. This
diagnostic will not auto clear solely due to the clearing of the
enabling diagnostic.
The leaving water temperature exceeded the high evap water
temp limit (TV service menu settable -default 105F) for 15
continuous seconds, with one of the three diagnostics on the left
already active. The evaporator water pump relay will be deenergized to stop the pump. The diagnostic can only be cleared
by a manual reset and will clear regardless of the temperature.
(although the diagnostic may reoccur based on the trip criteria).
The primary purpose is to stop the evaporator water pump and
its associated pump heat from causing excessive waterside
temperatures (and waterside pressures) when the chiller is not
running but the evap pump is on due to a pump override to “on”
(as can be caused by a bad flow switches failure to close and
prove flow).

Local

All

The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
Limit Mode (aka Minimum Limit), the running compressor's
Remote
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.

All

The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
Limit Mode (aka Minimum Limit), the running compressor's
Remote
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.

All

The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
Limit Mode (aka Minimum Limit), the running compressor's
Remote
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.

All

The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
Limit Mode (aka Minimum Limit), the running compressor's
Remote
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.

All

A high pressure cutout was detected on Compressor 1A; trip at
315 ± 5 PSIG. Note: Other diagnostics that may occur as an
expected consequence of the HPC trip will be suppressed from
annunciation. These include Phase Loss, Power Loss, and
Transition Complete Input Open.

Local

All

A high pressure cutout was detected on Compressor 1A; trip at
315 ± 5 PSIG. Note: Other diagnostics that may occur as an
expected consequence of the HPC trip will be suppressed from
annunciation. These include Phase Loss, Power Loss, and
Transition Complete Input Open.

Local

111

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence
High Pressure
Cutout Compressor 2A

Circuit

Immediate

Latch

Active Modes
[Inactive
Modes]

Reset
Level

Criteria

All

A high pressure cutout was detected on Compressor 1A; trip at
315 ± 5 PSIG. Note: Other diagnostics that may occur as an
expected consequence of the HPC trip will be suppressed from
annunciation. These include Phase Loss, Power Loss, and
Transition Complete Input Open.

Local

Local

Immediate

Latch

All

A high pressure cutout was detected on Compressor 1A; trip at
315 ± 5 PSIG. Note: Other diagnostics that may occur as an
expected consequence of the HPC trip will be suppressed from
annunciation. These include Phase Loss, Power Loss, and
Transition Complete Input Open.

Intermediate Oil
Pressure Transducer Cprsr 1A Immediate
- Compressor 1A

Latch

All

Bad Sensor or LLID

Remote

Intermediate Oil
Pressure Transducer Cprsr 1B Immediate
- Compressor 1B

Latch

All

Bad Sensor or LLID

Remote

Intermediate Oil
Pressure Transducer Cprsr 2A Immediate
- Compressor 2A

Latch

All

Bad Sensor or LLID

Remote

Intermediate Oil
Pressure Transducer Cprsr 2B Immediate
- Compressor 2B

Latch

All

Bad Sensor or LLID

Remote

High Pressure
Cutout Compressor 2B

Low Chilled Water
Temp: Unit Off

Circuit

Evap
Pump

Special
Mode

The leaving Evaporator water temp. fell below the leaving water
Unit in Stop Mode, temp cutout setting for 30 degree F seconds while the Chiller is
or in Auto Mode in the Stop mode, or in Auto mode with no compressors running.
NonLatch and No Ckt(s) Energize Evap Water pump Relay until diagnostic auto resets, Remote
Energzd
then return to normal evap pump control. Automatic reset
[Any Ckt Energzd] occurs when the temp rises 2°F (1.1°C) above the cutout setting
for 30 minutes.

Low Chilled Water
Temp: Unit On

Chiller

The evaporator water temp. fell below the cutout setpoint for 30
Immediate
Any Ckts] Energzd degree F Seconds while the compressor was running. Automatic
and
NonLatch
[No Ckt(s)
reset occurs when the temperature rises 2°F (1.1°C) above the Remote
Special
Energzd]
cutout setting for 2 minutes. This diagnostic shall not deMode
energize the Evaporator Water Pump Output.

Low Differential
Refrigerant Pressure
- Circuit 1

Circuit

Immediate

Latch

Cprsr Energized

The system differential pressure for the respective circuit was
below 35 Psid for more than 2000 Psid-sec with either a 1 minute
Remote
(single cprsr circuit) or 2.5 minute (manifolded cprsr circuit)
ignore time from the start of the circuit.

Low Differential
Refrigerant Pressure
- Circuit 2

Circuit

Immediate

Latch

Cprsr Energized

The system differential pressure for the respective circuit was
below 35 Psid for more than 2000 Psid-sec with either a 1 minute
Remote
(single cprsr circuit) or 2.5 minute (manifolded cprsr circuit)
ignore time from the start of the circuit.

Low Evaporator
Liquid Level - Circuit
1

None

Info

NonLatch

The liquid level sensor is seen to be at or near its low end of range
Starter Contactor
for 80 contiguous minutes while the compressor is running.
Energized
Remote
Design: 20% or less of bit count corresponding to -21.2 mm or
[all Stop modes]
less liquid level for 80 minutes)

Low Evaporator
Liquid Level - Circuit
2

None

Info

NonLatch

The liquid level sensor is seen to be at or near its low end of range
Starter Contactor
for 80 contiguous minutes while the compressor is running.
Energized
Remote
Design: 20% or less of bit count corresponding to -21.2 mm or
[all Stop modes]
less liquid level for 80 minutes)

Latch

The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the
Low Refrigerant Temperature Cutout Setpoint for 1125 F-sec
with a 8 F-sec/sec max integral rate applied during circuit
startup transient (or 4ºF-s/s if manifolded and only one cprsr
running) while the circuit was running early in the circuit's cycle.
The minimum LRTC setpoint is -5 F (18.7 Psia) the point at which
All Ckt Running
oil separates from the refrigerant. During the time that the trip Remote
Modes
integral is non zero, the unload solenoid(s) of the running
compressors on the circuit, shall be energized continuously and
the load solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps above the
cutout setpoint. The integral is held nonvolatily though power
down, is continuously calculated, and can decay during the
circuit's off cycle as conditions warrant.

Low Evaporator
Refrigerant
Temperature Circuit 1

112

Circuit

Immediate

RTAC-SVX01M-EN

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence

Low Evaporator
Refrigerant
Temperature Circuit 2

Low Evaporator
Temp - Ckt 1: Unit
Off

Low Evaporator
Temp - Ckt 2: Unit
Off

Low Oil Flow Compressor 1A

Low Oil Flow Compressor 1B

Low Oil Flow Compressor 2A

Low Oil Flow Compressor 2B

Low Suction
Refrigerant Pressure
- Circuit 1

Low Suction
Refrigerant Pressure
- Circuit 2

RTAC-SVX01M-EN

Circuit

Evap
Pump

Evap
Pump

Cprsr

Cprsr

Cprsr

Cprsr

Circuit

Circuit

Immediate

Latch

Active Modes
[Inactive
Modes]

Criteria

Reset
Level

The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the
Low Refrigerant Temperature Cutout Setpoint for 1125 F-sec
with a 8 F-sec/sec max integral rate applied during circuit
startup transient (or 4ºF-s/s if manifolded and only one cprsr
running) while the circuit was running early in the circuit's cycle.
The minimum LRTC setpoint is -5 F (18.7 Psia) the point at which
All Ckt Running
oil separates from the refrigerant. During the time that the trip Remote
Modes
integral is non zero, the unload solenoid(s) of the running
compressors on the circuit, shall be energized continuously and
the load solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps above the
cutout setpoint. The integral is held nonvolatily though power
down, is continuously calculated, and can decay during the
circuit's off cycle as conditions warrant.

Special
Mode

Any of the evap sat temps fell below the water temp cutout
setting while the respective evap liquid level was greater than Unit in Stop Mode,
21.2mm for 150 degree F seconds while Chiller is in the Stop
or in Auto Mode
mode, or in Auto mode with no compressors running. Energize
NonLatch
and No Ckt's
Remote
Evap Water pump Relay until diagnostic auto resets, then return
Energzd
to normal evap pump control. Automatic reset occurs when
[Any Ckt Energzd]
either the evap temp rises 2 F (1.1 C) above the cutout setting
or the liquid level falls below -21.2mm for 30 minutes

Special
Mode

Any of the evap sat temps fell below the water temp cutout
setting while the respective evap liquid level was greater than Unit in Stop Mode,
21.2mm for 150 degree F seconds while Chiller is in the Stop
or in Auto Mode
mode, or in Auto mode with no compressors running. Energize
NonLatch
and No Ckt's
Remote
Evap Water pump Relay until diagnostic auto resets, then return
Energzd
to normal evap pump control. Automatic reset occurs when
[Any Ckt Energzd]
either the evap temp rises 2 F (1.1 C) above the cutout setting
or the liquid level falls below -21.2mm for 30 minutes

Immediate

Latch

The intermediate oil pressure transducer for this compressor
Cprsr Energized was out of the acceptable pressure range for 15 seconds, while
and Delta P above the Delta Pressure was greater than 35 Psid.: Acceptable range
35 Psid
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,

Local

Latch

The intermediate oil pressure transducer for this compressor
Cprsr Energized was out of the acceptable pressure range for 15 seconds, while
and Delta P above the Delta Pressure was greater than 35 Psid.: Acceptable range
35 Psid
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,

Local

Latch

The intermediate oil pressure transducer for this compressor
Cprsr Energized was out of the acceptable pressure range for 15 seconds, while
and Delta P above the Delta Pressure was greater than 35Psid.: Acceptable range
35 Psid
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,.

Local

Latch

The intermediate oil pressure transducer for this compressor
Cprsr Energized was out of the acceptable pressure range for 15 seconds, while
and Delta P above the Delta Pressure was greater than 35 Psid.: Acceptable range
35 Psid
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,

Local

Latch

a. The Suction Refrigerant Pressure (or either of the compressor
suction pressures) dropped below 10 Psia just prior to
compressor start (after EXV preposition). b. The pressure fell
below 16 Psia while running after the ignore time had expired,
Cprsr Prestart and
or fell below 10 Psia (or 5 Psia in sftw prior to Oct'02) before the
Cprsr Energized
ignore time had expired. The ignore time is function of outdoor
air temperature. Note: Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic except for the trip integral
and trip point settings.

Local

Latch

a. The Suction Refrigerant Pressure (or either of the compressor
suction pressures) dropped below 10 Psia just prior to
compressor start (after EXV preposition). b. The pressure fell
below 16 Psia while running after the ignore time had expired,
Cprsr Prestart and
or fell below 10 Psia (or 5 Psia in sftw prior to Oct'02) before the
Cprsr Energized
ignore time had expired. The ignore time is function of outdoor
air temperature. Note: Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic except for the trip integral
and trip point settings.

Local

Immediate

Immediate

Immediate

Immediate

Immediate

113

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence

Low Suction
Refrigerant Pressure
- Cprsr 1B

Circuit

Immediate

Active Modes
[Inactive
Modes]

Reset
Level

Criteria

Latch

a. The Suction Refrigerant Pressure (or either of the compressor
suction pressures) dropped below 10 Psia just prior to
compressor start (after EXV preposition). b. The pressure fell
below 16 Psia while running after the ignore time had expired,
Cprsr Prestart and
or fell below 10 Psia (or 5 Psia in sftw prior to Oct'02) before the
Cprsr Energized
ignore time had expired. The ignore time is function of outdoor
air temperature. Note: Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic except for the trip integral
and trip point settings.

Local

a. The Suction Refrigerant Pressure (or either of the compressor
suction pressures) dropped below 10 Psia just prior to
compressor start (after EXV preposition). b. The pressure fell
below 16 Psia while running after the ignore time had expired,
Cprsr Prestart and
or fell below 10 Psia (or 5 Psia in sftw prior to Oct'02) before the
Cprsr Energized
ignore time had expired. The ignore time is function of outdoor
air temperature. Note: Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic except for the trip integral
and trip point settings.

Local

Low Suction
Refrigerant Pressure
- Cprsr 2B

Circuit

Immediate

Latch

MP Application
Memory CRC Error

Chiller

Immediate

Latch

All Modes

MP: Could not Store
Starts and Hours

None

Info

Latch

All

MP has determined there was an error with the previous power
down store. Starts and Hours may have been lost for the last 24 Remote
hours.

MP: Invalid
Configuration

None

Immediate

Latch

All

MP has an invalid configuration based on the current software
Remote
installed

MP: Non-Volatile
Block Test Error

None

Info

Latch

All

MP has determined there was an error with a block in the NonRemote
Volatile memory. Check settings.

MP: Non-Volatile
Memory Reformat

None

Info

Latch

All

MP has determined there was an error in a sector of the NonRemote
Volatile memory and it was reformatted. Check settings.

All

The main processor has successfully come out of a reset and
built its application. A reset may have been due to a power up,
installing new software or configuration. This diagnostic is
Remote
immediately and automatically cleared and thus can only be
seen in the Historic Diagnostic List in TechView

Memory error criteria TBD

Remote

MP: Reset Has
Occurred

None

Info

NonLatch

Oil Flow Fault Compressor 1A

Circuit

Immediate

Latch

The Intermediate Oil Pressure Transducer for this cprsr is
Starter Contactor
reading a pressure either above its respective circuit's
Energized
Condenser Pressure by 15 Psia or more, or below its respective
[all Stop modes]
Suction Pressure 10 Psia or more for 30 seconds continuously.

Local

Oil Flow Fault Compressor 1B

Circuit

Immediate

Latch

The Intermediate Oil Pressure Transducer for this cprsr is
Starter Contactor
reading a pressure either above its respective circuit's
Energized
Condenser Pressure by 15 Psia or more, or below its respective
[all Stop modes]
Suction Pressure 10 Psia or more for 30 seconds continuously.

Local

Oil Flow Fault Compressor 2A

Circuit

Immediate

Latch

The Intermediate Oil Pressure Transducer for this cprsr is
Starter Contactor
reading a pressure either above its respective circuit's
Energized
Condenser Pressure by 15 Psia or more, or below its respective
[all Stop modes]
Suction Pressure 10 Psia or more for 30 seconds continuously.

Local

Oil Flow Fault Compressor 2B

Circuit

Immediate

Latch

The Intermediate Oil Pressure Transducer for this cprsr is
Starter Contactor
reading a pressure either above its respective circuit's
Energized
Condenser Pressure by 15 Psia or more, or below its respective
[all Stop modes]
Suction Pressure 10 Psia or more for 30 seconds continuously.

Local

Oil Temperature
Sensor - Cprsr 1B

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Oil Temperature
Sensor - Cprsr 2B

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Oil Temperature
Sensor -Cprsr 1A

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Oil Temperature
Sensor -Cprsr 2A

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Outdoor Air
Temperature Sensor

Chiller

Normal

Latch

All

Bad Sensor or LLID. Note that if this diagnostic occurs,
operational pumpdown will be performed regardless of the last Remote
valid temperature

Pumpdown
Terminated - Circuit
1

None

Info

114

The pumpdown cycle for this circuit was terminated abnormally
NonLatch Pumpdown Mode due to excessive time or due to a specific set of diagnostic
Remote
criteria - but w/o associated latching diagnostics

RTAC-SVX01M-EN

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence
Pumpdown
Terminated - Circuit
2

None

Info

Active Modes
[Inactive
Modes]

Criteria

Reset
Level

The pumpdown cycle for this circuit was terminated abnormally
NonLatch Pumpdown Mode due to excessive time or due to a specific set of diagnostic
Remote
criteria - but w/o associated latching diagnostics

Software Error
1001: Call Trane
Service (beginning
with Rev 29)

All

Reported if a compressor is found to be running without chilled
water flow for three minutes. Previously, this error would be
identified after five minutes.

Software Error
1002: Call Trane
Service (beginning
with Rev 29)

All

Reported if state chart misalignment in stopped or inactive state
occurs.

Software Error
1003: Call Trane
Service (beginning
with Rev 29)

All

Reported if state chart misalignment in stopping state occurs.

Latch Software Error
power
All
Number: 1001 (Rev
Immediate down
functions
28)
reset is
reqd

All

A high level software watchdog has detected a condition in which
there was a continuous 5 minute period of compressor
operation, with neither chilled water flow nor a” contactor
interrupt failure” diagnostic active. The occurrence of this
software error message suggests an internal software state
chart misalignment has occurred. The events that led up to this
failure, if known, should be recorded and transmitted to Trane
Controls Engineering - (SW rev 24 and higher)

Starter Failed to
Arm/Start - Cprsr 1A

Cprsr

Info

Latch

All

Starter failed to arm or start within the allotted time (15
seconds).

Local

Starter Failed to
Arm/Start - Cprsr 1B

Cprsr

Info

Latch

All

Starter failed to arm or start within the allotted time (15
seconds).

Local

Starter Failed to
Arm/Start - Cprsr 2A

Cprsr

Info

Latch

All

Starter failed to arm or start within the allotted time (15
seconds).

Local

Starter Failed to
Arm/Start - Cprsr 2B

Cprsr

Info

Latch

All

Starter failed to arm or start within the allotted time (15
seconds).

Local

Starter Module
Memory Error Type 1
- Starter 2A

None

Info

Latch

All

Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.

Local

Starter Module
Memory Error Type 1
- Starter 2B

None

Info

Latch

All

Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.

Local

Starter Module
Memory Error Type
1Starter 1A

None

Info

Latch

All

Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.

Local

Starter Module
Memory Error Type
1-Starter 1B

None

Info

Latch

All

Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.

Local

Starter Module
Memory Error Type 2
- Starter 1A

Cprsr

Immediate

Latch

All

Checksum on EEPROM copy of the Starter LLID configuration
failed. Factor default values used.

Local

Starter Module
Memory Error Type 2
- Starter 1B

Cprsr

Immediate

Latch

All

Checksum on EEPROM copy of the Starter LLID configuration
failed. Factor default values used.

Local

Starter Module
Memory Error Type 2
- Starter 2A

Cprsr

Immediate

Latch

All

Checksum on EEPROM copy of the Starter LLID configuration
failed. Factor default values used.

Local

Starter Module
Memory Error Type 2
- Starter 2B

Cprsr

Immediate

Latch

All

Checksum on EEPROM copy of the Starter LLID configuration
failed. Factor default values used.

Local

All

Starter Panel High Limit Thermostat (170 F) trip was detected.
Note: Other diagnostics that may occur as an expected
consequence of the Panel High Temp Limit trip will be
suppressed from annunciation. These include Phase Loss, Power
Loss, and Transition Complete Input Open for Cprsr 1B

Local

All

Starter Panel High Limit Thermostat (170 F) trip was detected.
Note: Other diagnostics that may occur as an expected
consequence of the Panel High Temp Limit trip will be
suppressed from annunciation. These include Phase Loss, Power
Loss, and Transition Complete Input Open for Cprsr 2A

Local

Starter Panel High
Temperature Limit - Cprsr 1B
Panel 1, Cprsr 1B

Special
Mode

Starter Panel High
Temperature Limit - Cprsr 2A
Panel 1, Cprsr 2A

Special
Mode

RTAC-SVX01M-EN

NonLatch

NonLatch

115

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
PersistDiagnostic Name Target Severity
ence
Starter Panel High
Temperature Limit - Cprsr 2B
Panel 2, Cprsr 2B

Special
Mode

Active Modes
[Inactive
Modes]

NonLatch

Reset
Level

Criteria

All

Starter Panel High Limit Thermostat (170 F) trip was detected.
Note: Other diagnostics that may occur as an expected
consequence of the Panel High Temp Limit trip will be
suppressed from annunciation. These include Phase Loss, Power
Loss, and Transition Complete Input Open for Cprsr 2B

Local

Suction Refrigerant
Pressure Transducer
Special Immediate
- Circuit 1,
Compressor 1A

Latch

All

Bad Sensor or LLID Circuit target if no isolation valves,
Compressor target if isolation valves. Design Note: In the case
of manifolded compressors w/o isolation valves, the occurrence
Remote
of this diagnostic will also generate a comm loss with the
nonexistent Suction Press Cprsr 1B in order to accomplish circuit
shutdown.

Suction Refrigerant
Pressure Transducer
Cprsr 1B Immediate
- Circuit 1,
Compressor 1B

Latch

All

Bad Sensor or LLID. Design Note: For circuits with manifolded
compressors w/o isolation valve option, this diagnostic will occur
Remote
with the preceding diagnostic, even though this transducer is not
required or installed.

All

Bad Sensor or LLID Circuit target if no isolation valves,
Compressor target if isolation valves. Design Note: In the case
of manifolded compressors w/o isolation valves, the occurrence
Remote
of this diagnostic will also generate a comm loss with the
nonexistent Suction Press Cprsr 2B in order to accomplish circuit
shutdown.

All

Bad Sensor or LLID. Design Note: For circuits with manifolded
compressors w/o isolation valve option, this diagnostic will occur
Remote
with the preceding diagnostic, even though this transducer is not
required or installed

Suction Refrigerant
Pressure Transducer
Special Immediate
- Circuit 2,
Compressor 2A
Suction Refrigerant
Pressure Transducer
Cprsr 2B Immediate
- Circuit 2,
Compressor 2B

Very Low Evaporator
Refrigerant Pressure
- Circuit 1

Very Low Evaporator
Refrigerant Pressure
- Circuit 2

Chiller

Chiller

Immediate

Immediate

Latch

Latch

Latch

The evaporator pressure dropped below 8 psia (or 5 psia in sftw
prior to Oct '02)regardless of whether or not compressors are
All
running on that circuit. This diagnostic was created to prevent
[compressor or
compressor failures due to cross binding by forcing an entire
circuit in manual
chiller shutdown. If a given compressor or circuit is locked out,
lockout]
the suction pressure transducer(s) associated with it, will be
excluded from causing this diagnostic.

Local

Latch

The evaporator pressure dropped below 8 psia (or 5 psia in sftw
prior to Oct '02) regardless of whether or not compressors are
All
running on that circuit. This diagnostic was created to prevent
[compressor or
compressor failures due to cross binding by forcing an entire
circuit in manual
chiller shutdown. If a given compressor or circuit is locked out,
lockout]
the suction pressure transducer(s) associated with it, will be
excluded from causing this diagnostic.

Local

Communication Diagnostics
The following communication loss diagnostics will not
occur unless that input or output is required to be present
by the particular configuration and installed options for
the chiller.
Communication diagnostics (with the exception of
“Excessive Loss of Comm” are named by the Functional
Name of the input or output that is no longer being heard

from by the Main Processor. Many LLIDs, such as the Quad
Relay LLID, have more than one functional output
associated with it. A comm loss with such a multiple
function board, will generate multiple diagnostics. Refer to
the Chiller's wiring diagrams to relate the occurrence of
multiple communication diagnostics back to the physical
LLID boards that they have been assigned to (bound).

Table 68. Communication diagnostics

Diagnostic Name

Active
Modes
Affects
Persist- [Inactive
Target Severity
ence
Modes]

Reset
Level

Criteria

Comm Loss: Chilled
Water Flow Switch

Chiller

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Cond Rfgt
Pressure, Circuit #1

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Cond Rfgt
Pressure, Circuit #2

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

116

RTAC-SVX01M-EN

Diagnostics
Table 68. Communication diagnostics (continued)

Diagnostic Name

Active
Modes
Affects
Persist- [Inactive
Target Severity
ence
Modes]

Criteria

Reset
Level

Comm Loss: Electronic
Expansion Valve, Circuit
#1

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Electronic
Expansion Valve, Circuit
#2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Emergency
Stop

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evap Oil
Return Valve, Cprsr 1A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evap Oil
Return Valve, Cprsr 1B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evap Oil
Return Valve, Cprsr 2A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evap Oil
Return Valve, Cprsr 2B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Entering Water
Temperature

Chilled
Water
Reset

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall
remove any Return or Constant Return Chilled Water Reset, if it
was in effect. Apply slew rates per Chilled Water Reset spec.

Remote

Comm Loss: Evaporator
Leaving Water
Temperature

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Rfgt Drain Valve - Ckt 1

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Rfgt Drain Valve - Ckt 2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Rfgt Liquid Level, Circuit
#1

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Rfgt Liquid Level, Circuit
#2

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Evaporator
Circuit
Rfgt Pressure, Circuit #1

Immediate

Latch

All
Continual loss of communication between the MP and the
[Ckt/Cprsr Functional ID has occurred for a 30 second period. Note: This
lock out] diagnostic is replaced by diagnostic 5FB below with Rev 15.0

Remote

Comm Loss: Evaporator
Circuit
Rfgt Pressure, Circuit #2

Immediate

Latch

All
Continual loss of communication between the MP and the
[Ckt/Cprsr Functional ID has occurred for a 30 second period. Note: This
lock out] diagnostic is replaced by diagnostic 5FD below with Rev 15.0

Remote

Comm Loss: Evaporator
Water Pump Control

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: External
Auto/Stop

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: External
Chilled Water Setpoint

External
Chilled
Water
Setpoint

Special
Mode

NonLatch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall
Remote
discontinue use of the External Chilled Water Setpoint source and
revert to the next higher priority for setpoint arbitration

Comm Loss: External
Circuit Lockout, Circuit
#1

Circuit

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. MP will
Remote
nonvolatily hold the lockout state (enabled or disabled) that was
in effect at the time of comm loss.

Comm Loss: External
Circuit Lockout, Circuit
#2

Circuit

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. MP will
Remote
nonvolatily hold the lockout state (enabled or disabled) that was
in effect at the time of comm loss

Comm Loss: External
Current Limit Setpoint

External
Current
Limit
setpoint

Special
Mode

NonLatch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall
Remote
discontinue use of the External Current limit setpoint and revert to
the next higher priority for Current Limit setpoint arbitration

RTAC-SVX01M-EN

117

Diagnostics
Table 68. Communication diagnostics (continued)

Diagnostic Name

Active
Modes
Affects
Persist- [Inactive
Target Severity
ence
Modes]

Reset
Level

Criteria

Comm Loss: Fan Control
Circuit #1, Stage #1

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #1, Stage #2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #1, Stage #3

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #1, Stage #4

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #2, Stage #1

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #2, Stage #2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #2, Stage #3

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Control
Circuit #2, Stage #4

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Inverter
Fault, Circuit #1 or Circuit Inverter
#1, Drive 1

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Fan Inverter
Inverter
Fault, Circuit #1, Drive 2

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Fan Inverter
Fault, Circuit #2 or Circuit Inverter
#2, Drive 1

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Fan Inverter
Inverter
Fault, Circuit #2, Drive 2

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Fan Inverter
Power, Circuit #1 or
Circuit #1 Drive 1 and 2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Inverter
Power, Circuit #2 or
Circuit #2 Drive 1 and 2

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Fan Inverter
Speed Command, Circuit
Inverter
#1 or Circuit #1 Drive 1
and 2

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Fan Inverter
Speed Command, Circuit
Inverter
#2 or Circuit #2 Drive 1
and 2

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Operate the
remaining fans as fixed speed fan deck.

Remote

Comm Loss: Female Step
Load Compressor 1A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Female Step
Load Compressor 1B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Female Step
Load Compressor 2A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Female Step
Load Compressor 2B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: High
Pressure Cutout Switch,
Cprsr 1A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: High
Pressure Cutout Switch,
Cprsr 1B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

118

RTAC-SVX01M-EN

Diagnostics
Table 68. Communication diagnostics (continued)

Diagnostic Name

Active
Modes
Affects
Persist- [Inactive
Target Severity
ence
Modes]

Criteria

Reset
Level

Comm Loss: High
Pressure Cutout Switch,
Cprsr 2A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: High
Pressure Cutout Switch,
Cprsr 2B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Ice
Comm Loss: Ice-Machine
Making
Control
Mode

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall Remote
revert to normal (non-ice building) mode regardless of last state.

Comm Loss: Ice-Making
IceStatus
Machine

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Chiller shall Remote
revert to normal (non-ice building) mode regardless of last state.

Comm Loss:
Intermediate Oil
Pressure, Cprsr 1A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss:
Intermediate Oil
Pressure, Cprsr 1B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss:
Intermediate Oil
Pressure, Cprsr 2A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss:
Intermediate Oil
Pressure, Cprsr 2B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Local BAS
Interface

None

Special
Mode

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Load Compressor 1A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Load Compressor 1B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Load Compressor 2A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Load Compressor 2B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Unload Compressor 1A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Unload Compressor 1B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Unload Compressor 2A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Male Port
Unload Compressor 2B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Oil
Temperature, Circuit #1
or Cprsr 1A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Oil
Temperature, Circuit #2
or Cprsr 2A

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Oil
Temperature, Cprsr 1B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Oil
Temperature, Cprsr 2B

Cprsr

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

Comm Loss: Outdoor Air
Temperature

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Note that if this
Remote
diagnostic occurs, operational pumpdown will be performed
regardless of the last valid temperature

Comm Loss: Starter 1A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

RTAC-SVX01M-EN

Local

119

Diagnostics
Table 68. Communication diagnostics (continued)

Diagnostic Name

Active
Modes
Affects
Persist- [Inactive
Target Severity
ence
Modes]

Reset
Level

Criteria

Comm Loss: Starter 1B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Starter 2A

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Starter 2B

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Starter
Panel High Temperature
Limit - Panel 1, Cprsr 2A

None

Info

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Starter
Panel High Temperature
Limit - Panel 1, Cprsr 1B

None

Info

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Starter
Panel High Temperature
Limit - Panel 2, Cprsr 2B

None

Info

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Local

Comm Loss: Status/
Annunciation Relays

None

Info

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.

Remote

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.Circuit target if
no isolation valves, Compressor target if isolation valves or
simplex. Design Note: In the case of manifolded compressors w/ Remote
o isolation valves, the occurrence of this diagnostic will also
generate a comm loss with the nonexistent Suction Press Cprsr 1B
in order to accomplish circuit shutdown.

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Design Note:
For circuits with manifolded compressors w/o isolation valve
Remote
option, this diagnostic will occur with the preceding diagnostic,
even though this transducer is not required or installed.

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Circuit target
if no isolation valves, Compressor target if isolation valves or
simplex. Design Note: In the case of manifolded compressors w/ Remote
o isolation valves, the occurrence of this diagnostic will also
generate a comm loss with the nonexistent Suction Press Cprsr 2B
in order to accomplish circuit shutdown.

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Design Note:
For circuits with manifolded compressors w/o isolation valve
Remote
option, this diagnostic will occur with the preceding diagnostic,
even though this transducer is not required or installed.

Comm Loss: Suction
Pressure Cprsr 1A

Comm Loss: Suction
Pressure Cprsr 1B

Comm Loss: Suction
Pressure Cprsr 2A

Comm Loss: Suction
Pressure Cprsr 2B

Special Immediate

Cprsr

Immediate

Special Immediate

Cprsr

Immediate

Latch

Latch

Latch

Latch

Excessive Loss of Comm

Chiller

Immediate

Latch

All

Loss of comm with 75% or more (Rev 18 and earlier 10%) of the
llids configured for the system has been detected. This diagnostic
will suppress the callout of all subsequent comm loss diagnostics. Remote
Check power supply(s) and power disconnects - troubleshoot
LLIDS buss using TechView

Starter 1A Comm Loss:
MP

Cprsr

Immediate

Latch

All

Starter has had a loss of communication with MP for a 15 second
period.

Local

Starter 1B Comm Loss:
MP

Cprsr

Immediate

Latch

All

Starter has had a loss of communication with MP for a 15 second
period.

Local

Starter 2A Comm Loss:
MP

Cprsr

Immediate

Latch

All

Starter has had a loss of communication with MP for a 15 second
period.

Local

Starter 2B Comm Loss:
MP

Cprsr

Immediate

Latch

All

Starter has had a loss of communication with MP for a 15 second
period.

Local

120

RTAC-SVX01M-EN

Diagnostics

Main Processor Boot Messages
and Diagnostics
Table 69. Main processor boot messages and diagnostics
DynaView Display Message

Description Troubleshooting

A Valid Configuration is Present

A valid configuration is present in the MP's nonvolatile memory. The configuration is a set of variables and
settings that define the physical makeup of this particular chiller. These include: number/airflow,/and type of
fans, number/and size of compressors, special features, characteristics, and control options.
// Temporary display of this screen is part of the normal power up sequence.

App Present.
Running Selftest.…
Selftest Passed

An application has been detected in the Main Processor's nonvolatile memory and the boot code is proceeding
to run a check on its entirety. 8 seconds later, the boot code had completed and passed the (CRC) test.
// Temporary display of this screen is part of the normal power up sequence.

App Present.
Running Selftest…
Err3: CRC Failure

An application has been detected in Main Processor's nonvolatile memory and the boot code is proceeding to
run a check on its entirety. A few seconds later, the boot code had completed but failed the (CRC) test.
//Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration
information) and download the configuration if prompted by TechView. Then proceed to download the most
recent RTAC application or specific version as recommended by Technical Service. Note that this error display
may also occur during the programming process, if the MP never had a valid application any time prior to the
download. If the problem persists, replace the MP.

Boot Software Part Numbers:
LS Flash --> 6200-0318-04
MS Flash --> 6200-0319-04

The “boot code” is the portion of the code that is resident in all MPs regardless of what application code (if
any) is loaded. Its main function is to run power up tests and provide a means for downloading application
code via the MP's serial connection. The Part numbers for the code are displayed in the lower left hand corner
of the DynaView during the early portion of the power up sequence and during special programming and
converter modes. See below. For the EasyView, the extension of the boot code part number is displayed for
approximately 3 immediately following power up.
// This is normal, but you should provide this information when contacting Technical Service about power up
problems.

Converter Mode

A command was received from the Service Tool (Tech View) to stop the running application and run in the
“converter mode”. In this mode the MP acts as a simple gateway and allows the TechView service computer
to talk to all the LLIDS on the IPC3 bus.

Err2: RAM Addr Test #1 Failure

There were RAM errors detected in RAM Address Test #1. // Recycle power, if error persists, replace MP.

Err2: RAM Addr Test #2 Failure

There were RAM errors detected in RAM Address Test #2. //Recycle power, if the error persists, replace MP.

Err2: RAM Pattern 1 Failure

There were RAM errors detected in RAM Test Pattern #1. // Recycle power, if the error persists, replace MP.

Err2: RAM Pattern 2 Failure

There were RAM errors detected in RAM Test Pattern #2. //Recycle power, if the error persists, replace MP.

Err4: UnHandled Interrupt
Restart Timer:
[3 sec countdown timer]

An unhandled interrupt has occurred while running the application code. This event will normally cause a safe
shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics,
and attempt to restart the application and allow a normal restart of chiller as appropriate. // This condition
might occur due to a severe electro-magnetic transient such as can be caused by a near lightening strike. Such
events should be rare or isolated and if no damage results to the CH.530 control system, the Chiller will
experience a shutdown and restart. If this occurs more persistently it may be due to an MP hardware problem.
Try replacing the MP. If replacement of the MP proves ineffective, the problem may be a result of extremely
high radiated or conducted EMI. Contact Technical Service. If this screen occurs immediately after a software
download, attempt to reload both the configuration and the application. Failing this, contact Technical Service.

Err5: Operating System Error
Restart Timer:
[30 sec countdown timer]

An Operating System error has occurred while running the application code. This event will normally cause
a safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear
diagnostics, and attempt to restart the application and allow a normal restart of chiller as appropriate.
// See Err 4 above

Err6: Watch Dog Timer Error
Restart Timer:
[30 sec countdown timer]

A Watch Dog Timer Error has occurred while running the application code. This event will normally cause a
safe shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear
diagnostics, and attempt to restart the application allowing a normal restart of chiller as appropriate.

Err7: Unknown Error
Restart Timer:
[30 sec countdown timer]

An unknown Error has occurred while running the application code. This event will normally cause a safe
shutdown of the entire chiller. Once the countdown timer reaches 0, the processor will reset, clear diagnostics,
and attempt to restart the application allowing a normal restart of chiller as appropriate

The boot detected a key press in the center of the DynaView or both the + and - keys pressed on an EasyView
Err8: Held in Boot by User Key Press while the MP was in the boot code. Upon seeing this message the user can use Techview to connect to the
MP to perform a software download or another service tool function.
No Application Present
Please Load Application...

No Main Processor Application is present - There are no RAM Test Errors.
// Connect a TechView Service Tool to the MP's serial port, provide chiller model number (configuration
information) and download the configuration if prompted by TechView. Then proceed to download the most
recent RTAC application or specific version as recommended by Technical Service.

Programming Mode

A command was received by the MP from the Tech View Service Tool and the MP is in the process of first erasing
and then writing the program code to its internal Flash (nonvolatile) Memory. Note that if the MP never had
a prior application already in memory, the error code “Err3”will be displayed instead of this, during the
programming download process.

RTAC-SVX01M-EN

121

Unit Wiring
Table 70 provides a list of field wiring diagrams, electrical schematics and connection diagrams for 120-500 ton RTAC
units.The complete unit wiring package is documented in RTAC-SVE01*-EN. A laminated wiring diagram kit is also
shipped with each RTAC unit.
Table 70. RTAC unit wiring drawing numbers
Drawing Number

Description

Sheet 1

Table of Contents & Notes

Sheet 2

Legend

Sheet 3 (X-Line)

Compressor 1A (X-Line)

Sheet 3 (Y-Delta)

Compressor 1A (Y-delta)

Sheet 4 (X-Line)

Compressor 2A (X-Line)

Sheet 4 (Y-Delta)
2309-2097

Sheet 5

Compressor 2A (Y-delta)
Schematic - 2 Compressor Units

Sheet 6

Fans, 140 & 155 Std, 120 & 130 Prem 50 Hz

Sheet 7

Fans 225, 250 Prem 60 Hz, 185 & 200 Extra 60 Hz

Sheet 8

VSD Fans - Circuits 1 & 2

Sheet 9

Controls

Sheet 10

LLID Bus

Sheet 11

Remote Evaporator

Sheet 1

Table of Contents & Notes

Sheet 2

Devices, Descriptions & Designations

Sheet 3

Compressor Power 1A & Fan Control Ckt 1

Sheet 4
2309-4621

2309-4622

122

Fans, Std & Prem, Medium Air Cooled

Sheet 5
Sheet 6

Compressor Power 1B
Schematic - 3 Compressor Units,
X-Line

Compressor Power 2A & Fan Control Ckt 2
Fan Power Circuit 1

Sheet 7

Fan Power Circuit 2

Sheet 8

Common Control - Panel LLIDs

Sheet 9

Common Control - Panel LLIDs

Sheet 10

Common Control - Panel LLIDs

Sheet 1

Table of Contents & Notes

Sheet 2

Devices, Descriptions & Designations

Sheet 3

Compressor Power 1A & Fan Control Ckt 1

Sheet 4

Compressor Power 1B

Sheet 5
Sheet 6

Schematic - 3 Compressor, Units
Y-Delta

Compressor Power 2A & Fan Control Ckt 2
Fan Power Circuit 1

Sheet 7

Fan Power Circuit 2

Sheet 8

Common Control - Panel LLIDs

Sheet 9

Common Control - Panel LLIDs

Sheet 10

Common Control - Panel LLIDs

RTAC-SVX01M-EN

Unit Wiring
Table 70. RTAC unit wiring drawing numbers
Drawing Number

Description

Sheet 1

Table of Contents & Notes

Sheet 2

Devices, Descriptions & Designations

Sheet 3

Compressor Power 1A & Fan Control Ckt 1

Sheet 4

Compressor Power 1B

Sheet 5
2309-4623

Sheet 6

Compressor Power 2A & Fan Control Ckt 2
Schematic - 4 Compressor Units
X-Line

Fan Power Circuit 1

Sheet 8

Fan Power Circuit 2

Sheet 9

Common Control - Panel LLIDs

Sheet 10

Common Control - Panel LLIDs

Sheet 11

Common Control - Panel LLIDs

Sheet 1

Table of Contents & Notes

Sheet 2

Devices, Descriptions & Designations

Sheet 3

Compressor Power 1A & Fan Control Ckt 1

Sheet 4

Compressor Power 1B

Sheet 5
2309-4624

Compressor Power 2B

Sheet 7

Sheet 6

Compressor Power 2A & Fan Control Ckt 2
Schematic - 4 Compressor
Y-Delta

Compressor Power 2B

Sheet 7

Fan Power Circuit 1

Sheet 8

Fan Power Circuit 2

Sheet 9

Common Control - Panel LLIDs

Sheet 10

Common Control - Panel LLIDs

Sheet 11

Common Control - Panel LLIDs

2309-4871

Component Location

2 Compressor Units

2309-4874

Component Location

3 Compressor Units

2309-4873

Component Location

4 Compressor Units

2309-4872

Component Location

2309-2248

Field Layout

2 Compressor Units

Field Layout

3 or 4 Compressor Units

2309-2239
2309-2208

2 Compressor - Optional Remote Evaporator

Field Wiring; RTAC, 2 Compressor Units 2 Compressor Units

2309-2223

Field Wiring

3 or 4 Compressor Units, Single Source Power

2309-2222

Field Wiring

3 or 4 Compressor Units, Dual Source Power

2309-7572

Sequence of Operation

2 Compressor Units

2309-7581

Sequence of Operation

3 or 4 Compressor Units

RTAC-SVX01M-EN

123

Log and Check Sheet
The operator log and check sheet are included for use as
appropriate, for installation completion verification before
Trane start-up is scheduled, and for reference during the
Trane start-up.
Where the log or check sheet also exists outside of this
publication as standalone literature, the literature order
number is also listed.
•

RTAC Series R Air-Cooled Chiller Installation
Completion Check Sheet and Request forTrane Service
(RLC-ADF003*-EN)

•

Operator Log

•

Start-UpTest Log

124

RTAC-SVX01M-EN

RTAC Series R® Air-Cooled Chiller
Installation Completion Check Sheet and Request for Trane Service
Important:

A copy of this completed form must be submitted to theTrane service agency that will be responsible for the startup of the chiller. Start-up will NOT proceed unless applicable items listed in this form have been satisfactorily
completed.

To:
Trane Service Office:
S.O. Number:
Serial Numbers:
Job/Project Name:
Address:
The following items are being installed and will be completed by:
Important:

Start-up must be performed byTrane or an agent ofTrane specifically authorized to perform start-up ofTrane®
products. Contractor shall provideTrane (or an agent ofTrane specifically authorized to perform start-up) with
notice of the scheduled start-up at least two weeks prior to the scheduled start-up.

Check boxes if the task is complete or if the answer is “yes.”
1. Screw Chiller
 Installation meets foundation requirements.
 Verify service clearances meet requirements.
 In place and piped.
 Isolation pads or neoprene pads installed (optional).
2. Piping
Chilled water piping connected to:
 Evaporator
 Air handling units
 Pumps
 Flow switch or flow proving device installed
 Required strainer installed in entering evaporator water piping and cleaned
 Water supply connected to filling system (expansion tank)
 Systems filled
 Pumps run, air bled from system
 Relief valve ventilation piping installed (if applicable)
 Flow balancing valves installed in leaving chilled water
 Gauges, thermometers and air vents installed on both sides of evaporator
3. Wiring
 Wire size per submittal, NEC and applicable local electrical codes. Verify only copper conductors used.
 Full power available, and within utilization range.
 Interconnecting wiring to remote evaporator (if applicable)
 External interlocks (flow switch, pumps auxiliary, etc.)
 Chilled water pump (connected and tested)
 115 Vac power available for service tools (recommended)
 All controls installed and connected
4. Testing
 Dry nitrogen available for pressure testing (if required)
 Trace gas amounts of R-134a available for leak testing (if required)
5.  Refrigerant on job site (if required)
6.  Systems can be operated under load conditions

RLC-ADF003A-EN

1

7. Owner awareness
 If it is required by local code, is a self-contained breathing apparatus available?
 Has the owner been fully instructed on the proper use of refrigerant?
 Does the owner have a copy of the MSDS for refrigerant?
 Was the owner given a copy of the Refrigerant Handling Guidelines?
Note: Additional time required to properly complete the start-up and commissioning, due to any incompleteness of the
installation, will be invoiced at prevailing rates.
This is to certify that theTrane® equipment has been properly and completely installed, and that the applicable items listed above
have been satisfactorily completed.
Important: It is required that the chiller heaters are energized for a minimum of 24 hours prior to start up.Therefore, the chiller
should have power for this amount of time beforeTrane Service arrives to do start-up of the equipment.
Checklist completed by: ______________________________________________________________________________________________
Signed: _____________________________________________________________________
Date: _______________________________
In accordance with your quotation and our purchase order number __________________, we will therefore require the presence
ofTrane service on this site, for the purpose of start-up and commissioning, by __________________ (date).
Note: Minimum two-week advance notification is required to allow scheduling of the chiller start-up.
Additional comments/instructions: ____________________________________________________________________________________
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
Note: A copy of this completed from must be submitted to theTrane Service Office that will be responsible for start-up of chiller.
Trane and theTrane logo are trademarks or registered trademarks ofTrane in the United States and other countries.

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2015Trane All rights reserved
RLC-ADF003A-EN 21 Jan 2015

We are committed to using environmentally

New

conscious print practices that reduce waste.

Operator Log
RTAC CHILLER LOG
Job Name

Job Location

Model #

Serial #

Status View: *
Chiller Tab:

15 min

30 min

45 min

15 min

30 min

45 min

Operating Mode
Outdoor Air Temperature

F or C

Active Chill Water Setpoint

F or C

Active Current Limit Setpoint
Evaporator Entering Water Temp.

F or C

Evaporator Leaving Water Temp.

F or C
Circuit 1 Tab

Circuit 2 Tab

External Hardwired Lockout

Not Locked out/ Locked out

Not Locked out/ Locked out

Front Panel Lockout

Not Locked out/ Locked out
15 min

AirFlow

%

Inverter Speed

%

Condenser Refrigerant Pressure

psig/kPa

Saturated Condenser Rfgt. Temp.

F or C

Differential Refrigerant Pressure

psid/kPA

Evaporator Refrigerant Pressure

psig/kPa

Saturated Evaporator Rfgt.Temp.

F or C

EXV Position

%

Evaporator Rfgt Liquid Level

in/mm

30 min

Not Locked out/ Locked out
45 min

Compressor 1A Tab

15 min

30 min

45 min

Compressor 1B Tab

Operating Mode
Hours

Hrs/mins

Hrs/mins

Starts

Phase A - B Voltage

15 min

30 min

45 min

15 min

30 min

45 min

open/closed

open/closed

open/closed

open/closed

open/closed

open/closed

volts

Average Line Current

%RLA

Line 1 current

amps

Line 2 current

amps

Line 3 current

amps

Line 1 current

%RLA

Line 2 current

%RLA

Line 3 current

%RLA

Evaporator Oil Return Solenoid
Supply Oil Temperature

F or C

Intermediate Oil Pressure

psig/kPa

Female Step solenoid

load/unload

load/unload

load/unload

load/unload

load/unload

load/unload

High Pressure Cutout switch

good/tripped

good/tripped

good/tripped

good/tripped

good/tripped

good/tripped

Comments:

RTAC Operator Log

Revised: 28 Jan2014

RTAC CHILLER LOG
Compressor 2A Tab

Compressor 2B Tab

Operating Mode
Hours

Hrs/mins

Hrs/mins

Starts

Phase A - B Voltage

15 min

30 min

45 min

15 min

30 min

45 min

open/closed

open/closed

open/closed

open/closed

open/closed

open/closed

volts

Average Line Current

%RLA

Line 1 current

amps

Line 2 current

amps

Line 3 current

amps

Line 1 current

%RLA

Line 2 current

%RLA

Line 3 current

%RLA

Evaporator Oil Return Solenoid
Supply Oil Temperature

F or C

Intermediate Oil Pressure

psig/kPa

Female Step solenoid

load/unload

load/unload

load/unload

load/unload

load/unload

load/unload

High Pressure Cutout switch

good/tripped

good/tripped

good/tripped

good/tripped

good/tripped

good/tripped

Comments:

Revised: 28 Jan2014

RTAC Operator Log

RTAC Start-Up Test Log
RTAC START-UP TEST LOG
Model #
Job Name

Job Location

CRC #

Serial #

Sales Order #

Job Elevation (ft.
above sea level)

Ship Date

Starter Data:

Start-up Only

Manufacturer

Chiller Appearance on arrival:

Type: (wye-delta or x-line)

Machine gauge pressure:

ckt1/ckt2

Vendor ID #/ Model #:

Machine CH.530 pressure

ckt1/ckt2

Volts

Amps

Hz

Compressor Data:

Unit R-134a Charge

lbs

Unit oil charge (OIL00048)

gal

Pressure Test (if required)

Compressor A:
Model #:

Vacuum after leak test=

Serial #

Standing Vacuum test=

Part number ("X" code and 2-digit extension)

Volts

X

HZ

X

Model #:

X

Compressor B:

hrs

Current Transformers

RLA
KW

mm
mm rise in

X

Serial #

X

RLA

X

Summary of Options Installed

KW
Volts

Y

N

Tracer Communications Interface

HZ

Y

N

Ice Making

Y

N

Other

Model #:

Y

N

Other

Serial #

Y

N

Other

RLA

Evap Design Conditions

Compressor C:

KW

GPM

PSID

Volts

Entering Water:

Leaving Water:

HZ

% Glycol:

Compressor D:

Type of Glycol:
Model #:

Evap Actual Conditions

Serial #

GPM

PSID

RLA

Entering Water:

Leaving Water:

KW

% Glycol:

Volts

Type of Glycol:

HZ
Owner Witness Signature:

RTAC Start-UpTest Log

Revised: 28 Jan2014

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2015Trane All rights reserved
RTAC-SVX01M-EN 30 Jan 2015

We are committed to using environmentally

Supersedes RTAC-SVX01L-EN (11 Jul 2013)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : Sheryl Hill
Create Date                     : 2015:01:21 15:25:20Z
Keywords                        : RTAC, Series R, air-cooled
Modify Date                     : 2015:01:30 06:43:15-07:00
Subject                         : Series R? Air-Cooled Helical Rotary Liquid Chillers
Has XFA                         : No
Language                        : en
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Creator Tool                    : FrameMaker 10.0.2
Metadata Date                   : 2015:01:30 06:43:15-07:00
Format                          : application/pdf
Title                           : RTAC-SVX01M-EN (01/2015): Installation, Operation and Maintenance, Series R® Air-Cooled Helical Rotary Liquid Chillers
Creator                         : Sheryl Hill
Description                     : Series R? Air-Cooled Helical Rotary Liquid Chillers
Producer                        : Acrobat Distiller 10.1.13 (Windows)
Document ID                     : uuid:8147a120-1728-4f36-b732-57c87ade3071
Instance ID                     : uuid:6a5e8398-8f53-476a-84b8-c3c6413f4412
Page Mode                       : UseOutlines
Page Count                      : 130
EXIF Metadata provided by EXIF.tools

Navigation menu