Trane Uni Fan Coil And Force Flo Catalogue CAB PRC001 EN (08 May 2012)

2015-04-02

: Trane Trane-Uni-Fan-Coil-And-Force-Flo-Catalogue-684301 trane-uni-fan-coil-and-force-flo-catalogue-684301 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 69

DownloadTrane Trane-Uni-Fan-Coil-And-Force-Flo-Catalogue- CAB-PRC001-EN (08 May 2012)  Trane-uni-fan-coil-and-force-flo-catalogue
Open PDF In BrowserView PDF
CAB-PRC001-EN.book Page 1 Tuesday, May 8, 2012 10:11 AM

Product Catalog

Force-Flo™ Cabinet Heater
Air Terminal Devices
Horizontal and Vertical
Sizes 02–12

May 2012

CAB-PRC001-EN

CAB-PRC001-EN.book Page 2 Tuesday, May 8, 2012 10:11 AM

Introduction
Trane has redesigned the traditional cabinet heater to lead the industry in:
•

indoor air quality (IAQ) features

•

easy installation and maintenance

•

high quality and durability

•

advanced controls

Smaller unit footprint.
Quiet operation.

Two-, three-, or
four-row coils.

Factory-assembled, -installed,
and -tested piping package
with IAQ drain pan to collect
condensate.

Factory-installed and
-tested controls.

Removable, noncorrosive,
positively-sloped drain pan
that’s easy to clean.
Build in field service tool
with real language LED
Easy-to-remove fan assembly.

16-gage steel construction.
Cleanable closed-cell
insulator (non-fiberglass).
Easy filter access
without front panel
removal.

Energy efficient
electronically
commutated motor
(ECM)

Damper allows up
to 100% fresh air.

Revision History
The revision of this literature dated 08 May 2012 includes information for Tracer™ UC400 controls,
coil performance updates, and revised performance table formats per new AHRI listing
requirements.

Trademarks
Force-Flo, Integrated Comfort, Rover, TOPSS, Tracer, Tracer Summit, Trane, and the Trane logo are
trademarks of Trane in the United States and other countries. All trademarks referenced in this
document are the trademarks of their respective owners.
© 2012 Trane All rights reserved

CAB-PRC001-EN

CAB-PRC001-EN.book Page 3 Tuesday, May 8, 2012 10:11 AM

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model A, Vertical Concealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model B, Vertical Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model C, Horizontal Concealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Model D, Horizontal Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Model E, Horizontal Recessed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model F, Vertical Wall Hung Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model H, Vertical Recessed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Model J, Vertical Cabinet Slope Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Model M, Inverted Vertical Concealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Model N, Inverted Vertical Recessed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Factory-Installed Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Horizontal Concealed, Horizontal Recessed, Vertical Recessed, Inverted
Vertical Recessed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Vertical Concealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Horizontal Cabinet, Vertical Cabinet, Inverted Vertical Cabinet . . . . . . . 25
Vertical Slope Top Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Horizontal Concealed, Horizontal Recessed, Vertical Recessed, Horizontal
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Vertical Concealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ECM Engine Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Fan Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customer Supplied Terminal Interface (CSTI) . . . . . . . . . . . . . . . . . . . . .
Tracer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zone Sensor Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tracer ZN520 and UC400 Additional Features . . . . . . . . . . . . . . . . . . . . .
End Device Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29
30
30
31
32
34
37
38
39
39

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Vertical Concealed, Model A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical Cabinet, Model B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Horizontal Concealed, Model C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Horizontal Cabinet, Model D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAB-PRC001-EN

46
47
48
49
3

CAB-PRC001-EN.book Page 4 Tuesday, May 8, 2012 10:11 AM

Horizontal Recessed, Model E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical Wall Hung Cabinet, Model F . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical Recessed, Model H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical Slope Top, Model J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inverted Vertical Cabinet, Model M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inverted Vertical Recessed, Model N . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coil Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fresh Air Opening Locations-Horizontal Units Models C, D, and E . . . .
Fresh Air Opening Locations-Vertical Units Models A, B, F, and J . . . . .
Wall Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Projection Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50
51
52
53
54
55
56
57
58
59
60

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Force-Flo Cabinet Heater Mechanical Specifications . . . . . . . . . . . . . . . . 61
Piping Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

4

CAB-PRC001-EN

CAB-PRC001-EN.book Page 5 Tuesday, May 8, 2012 10:11 AM

Features and Benefits
The Force-Flo cabinet heater meets the standards of today’s market, as well as the anticipated
needs of tomorrow’s market. The tradition that company founder Reuben Trane began in 1913
continues with the latest generation of cabinet heaters from Trane.
The Force-Flo cabinet heater is the leader in these key areas:
•

Energy Efficiency

•

Indoor Air Quality (IAQ)

•

Controls

•

Flexibility

•

Quality

•

Serviceability

Today’s HVAC market is concerned with issues such as indoor air quality (IAQ) and CFCs that
demand a change in HVAC products. In addition, renovation has overtaken new construction in the
cabinet heater market - demanding a design that caters to renovation issues. Trane is concerned
with these issues, too. That’s why we designed the Force-Flo cabinet heater as an integral part of
the company’s system solutions with standard IAQ-related features that comply with ASHRAE 62.

Energy Efficiency
Trane’s commitment to providing premium quality products has led to the exclusive use of
Electronically Commutated Motors (ECM) in all fan coil models. These brushless DC motors
incorporate the latest technology for optimized energy efficiency, acoustical abatement,
maintenance free and extended motor life. Each motor has a built-in microprocessor that allows
for programmability, soft ramp-up, better airflow control, and serial communication.
•

Trane units equipped with ECMs are significantly more efficient than the standard Permanent
Split Capacitor (PSC) motor.

•

Lower operating costs on average of 50 percent (versus a PSC motor).

•

The Reduced FLA feature allows units to ship with a nameplate FLA rating much lower than a
typical ECM unit.

IAQ Design
•

Closed-cell insulation is standard on all units to help prevent fiberglass in the airstream.

•

Easy filter access encourages frequent changing.

•

Force-Flo cabinet heaters have a blow-thru design.

Controls

CAB-PRC001-EN

•

This is the industry’s first solution that is factory mounted, wired and programmed for infinite
modulation of fan speed based on space loads, using the UC400.

•

Auto Fan Speed control with the Tracer ZN520 ramps the fan speed up and down to meet space
loads.

•

All controls are factory-mounted and tested to minimize field setup and improve reliability.

•

Controls are wired with a 24 Vac transformer to keep only a single source power connection
requirement to the unit.

•

All wall-mounted zone sensors require only low voltage control wiring from the device to the
unit control box. (No line voltage.)

•

The random startup feature helps reduce electrical demand peaks by randomly staggering
multiple units at startup.

•

Occupied/unoccupied operation allows the controller to utilize unoccupied temperature
setpoints for energy savings.

5

CAB-PRC001-EN.book Page 6 Tuesday, May 8, 2012 10:11 AM

Features and Benefits

•

Warm-up energy feature is standard with Trane controls.

•

Continuous fan or fan cycling is available with Tracer ZN010 or ZN510.

•

Monitor unit operation using Tracer SC building management system with Tracer ZN510.

•

To customize unit control, Tracer TU or Rover™ software will allow field modification of Tracer
ZN510, ZN520 and UC400 default settings.

•

Maximize cabinet heater system efficiency with modulating valves on units with Tracer ZN520
and UC400.

Flexibility
•

Two-, three-, and four row hot water coils allow greater design flexibility. Steam distributing or
electric heat coils are also available.

•

Fan motors are available for either high static (0.4-inch external static pressure) or free
discharge applications.

•

Piping is factory-assembled, -mounted, and -tested. Units are also available without piping.

•

Factory piping options include interconnecting piping, control valves, and end valves. Deluxe
piping also has unions and a strainer.

•

Control options range from a simple fan speed switch to a DDC controller that can tie into a
Tracer SC building automation system.

•

The extended end pocket option adds 8 inches (20 cm) to the piping end of cabinet style units.

•

Slope-top vertical cabinet units are an excellent application for school and dormitories to
prevent items from being placed on top of the units.

•

Vertical wall hung units are used in vestibules, bathrooms, stairwells, or other applications
when the unit cannot be installed on the floor.

•

Inverted unit models allow heating to circulate from the bottom of the unit.

Quality
•

Coils and piping packages are air and leak-tested before mounting on the unit.

•

Coil piping connections are also air and leak-tested after mounting on the unit.

•

All control end devices and moving components (fans and motors) are computer-tested after
units are complete.

Serviceability
•

6

Touch-safe control box.

•

Integrated user interface with real language LED display.

•

Built-in tachometer.

•

Filters are easily removable and changed without removing the front panel on vertical cabinet
units.

•

Motors are easy to disconnect from the fan board, allowing easy service.

•

The manual output test function is an invaluable troubleshooting tool. By simply pressing the
test button on the Tracer ZN510, ZN520, or ZN010; service personnel can manually exercise
outputs in a pre-defined sequence.

CAB-PRC001-EN

CAB-PRC001-EN.book Page 7 Tuesday, May 8, 2012 10:11 AM

Model Number Descriptions
Force-Flo Cabinet
Heater Model
Number Description

Digit 9 - Piping System/
Placement

Digit 16 - Tamperproof Locks/
Leveling Feet

A
B
E

=
=
=

Following is a complete description of
the cabinet heater model number.
Each digit in the model number has a
corresponding code that identifies
specific unit options.

F

=

0
B
C
D
F

=
=
=
=
=

J
K
L

=
=
=

G

=

Note: Some options may not be
available with all cabinet
styles. Contact your local
Trane representative for more
information.
Digit 1, 2 - Unit Type
FF =

Force-Flo

Digit 3 - Cabinet Type
A
B
C
D
E
F
H
J
M
N

=
=
=
=
=
=
=
=
=
=

Vertical Concealed
Vertical Cabinet
Horizontal Concealed
Horizontal Cabinet
Horizontal Recessed
Vertical Wall Hung Cabinet
Vertical Recessed
Vertical Cabinet Slope Top
Inverted Vertical Cabinet
Inverted Vertical Recessed

Digit 4 - Development Sequence
“B”

M =

No Piping, RH
No Piping, LH
No Piping, RH, Extended
End Pocket
No Piping, LH, Extended
End Pocket
With Piping Package, RH
With Piping Package, LH
With Piping Package, RH,
Extended End Pocket
With Piping Package, LH,
Extended End Pocket

Digit 12 - Inlets
A
B
C
D
E
F
G
H
J

=
=
=
=
=
=
=
=
=

Front Toe Space
Front Bar Grille
Front Stamped Louver
Bottom Stamped Louver
Bottom Toe Space
Back Duct Collar
Back Open Return
Back Stamped Louver
Top Duct Collar

Digit 13 - Fresh Air Damper
0
A
B
C
D

=
=
=
=
=
=
=
=
=
=

None
Manual, Bottom Opening
Manual, Back Opening
Manual, Top Opening
Auto, 2-Position, Bottom FA
Opening
Auto, 2-Position, Back FA Opening
Auto, 2-Position, Top FA Opening
No Damper, Bottom Opening
No Damper, Back Opening
No Damper, top Opening

080

060

100
120

Digit 14 - Outlets

=

115/60/1

6

=

230/60/3

=

208/60/1

7

=

480/60/3

3

=

277/60/1

8

=

110–120/50/1

4

=

230/60/1

9

=

220–240/50/1

5

=

208/60/3

A

=

220–240/50/3

B

=

380–415/50/3

A
B
C
D
E
F
G
H
J

=
=
=
=
=
=
=
=
=

Front Duct Collar
Front Bar Grille
Front Stamped Louver
Front Quad Grille
Bottom Duct Collar
Bottom Stamped Louver
Top Quad Grille
Top Bar Grille
Top Duct Collar

Digit 15 - Color
0
1
4
2
5
3
6

CAB-PRC001-EN

Free Discharge ECM
High Static ECM

G
H
J
N
U
V
W

040

2

=
=

“M0”

030

1

A
B

Digit 18 - Coil

020

Digit 8 - Unit Voltage

Digit 17 - Motor

Digit 10, 11 - Design Sequence

E
F
K
L
M

Digit 5, 6, 7 - Unit Size

None
Keylock Access Door
Keylock Panel and Access Door
Leveling Feet
Keylock Access Door w/Leveling
Feet
Keylock Panel and Access Door
w/Leveling Feet

=
=
=
=
=
=
=

No Paint (Concealed Units Only)
Deluxe Beige
Driftwood Grey
Soft Dove
Stone Grey
Cameo White
Rose Mauve

=
=
=
=
=
=
=

2-Row Hot Water
3-Row Hot Water
4-Row Hot Water
Electric Heat, Single-Stage
Electric Heat, Two-Stage
Electric Heat, Low kW, One-Stage
Steam Distributing

Digit 19 - Coil Series
1
2

=
=

108 fpf (Steam Only)
144 fpf (Hot Water Only)

Digit 20 - Coil Air Vent
A =
M =

Automatic Air Vent
Manual Air Vent

Digit 21, 22, 23 - Electric Heat
kW (208 V derate)
000 =
010 =
020 =
030 =
045 =
060 =
075 =
090 =
100 =
105 =
110 =
120 =
135 =
150 =
180 =
200 =

No Electric Heat
1.0 kW (0.75 kW)
2.0 kW (1.5 kW)
3.0 kW (2.3 kW)
4.5 kW (3.3 kW)
6.0 kW (4.5 kW)
7.5 kW (5.7 kW)
9.0 kW (6.6 kW)
10.0 kW
10.5 kW (7.9 kW)
11.0 kW (9.0 kW)
12.0 kW
13.5 kW (10.2 kW)
15.0 kW
18.0 kW (13.5 kW)
20.0 kW (15.0 kW)

Digit 24 - Not Used
0

Digit 25 - Disconnect Switch
0
D

=
=

None
Disconnect Switch

7

CAB-PRC001-EN.book Page 8 Tuesday, May 8, 2012 10:11 AM

Model Number Descriptions

Digit 26 - Filter

Digit 30 - Control Type

0
1
2
3
4
5
6
7
8
A
B
C
D

A
E
F
G
H

=
=
=
=
=

J

=

=
=
=
=
=
=
=
=
=
=
=
=
=

None
1” Throwaway Filter
1” Throwaway MERV 8 Filter
1” Throwaway, 1 Extra
1” Throwaway MERV 8, 1 Extra
1” Throwaway, 2 Extras
1” Throwaway MERV 8, 2 Extras
1” Throwaway, 3 Extras
1” Throwaway MERV 8, 3 Extras
1” Throwaway MERV 13 Filter
1” Throwaway MERV 13, 1 Extra
1” Throwaway MERV 13, 2 Extras
1” Throwaway MERV 13, 3 Extras

Digit 27 - Main Control Valve
0
1
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
X
Y
Z

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

None
Field Supplied Analog valve
2-Way, 2-Position, NO (30 psig)
3-Way, 2-Position, NO (28 psig)
2-Way, 2-Position, NC (30 psig)
3-Way, 2-Position, NC (20 psig)
2-Way, 2-Position, NO (50 psig)
3-Way, 2-Position, NO (28 psig)
2-Way, 2-Position, NC (60 psig)
3-Way, 2-Position, NC (28 psig)
2-Way, Mod., 0.7 Cv (60 psig)
3-Way, Mod., 0.7 Cv (60 psig)
2-Way, Mod., 1.5 Cv (60 psig)
3-Way, Mod., 1.5 Cv (60 psig)
2-Way, Mod., 2.5 Cv (60 psig)
3-Way, Mod., 2.5 Cv (60 psig)
2-Way, Mod., 4.0 Cv (60 psig)
3-Way, Mod., 4.0 Cv (60 psig)
Field-Supplied, NO
Field-Supplied, NC
Field-Supplied 3-Wire Modulating

Digit 28 - Not Used
0

Digit 31 - Control Option
D
K
V

=
=
=

W =
X

=

Y

=

Z

=

1

=

2

=

0
3

=
=

4

=

5

=

6
7

=
=

Digit 29 - Piping Packages
0
A

=
=

B

=

C

=

D

=

E

=

F

=

None
Basic Ball Valve supply and
Return
Basic Ball Valve Supply/Manual
Circuit Setter
Basic Ball Valve Supply and
Return w/Auto Circuit Setter
Deluxe Ball Valve Supply and
Return
Deluxe Ball Valve Supply/Manual
Circuit Setter
Deluxe Ball Valve Supply and
Return w/Auto Circuit Setter

Fan Speed Switch
Tracer ZN010
Tracer ZN510
Tracer ZN520
Customer Supplied Terminal
Interface
Tracer UC400, Single Zone VAV
Unit-Mounted Fan Mode Switch
Wall-Mounted Fan Mode Switch
Unit-Mounted Fan Speed Switch
w/Setpoint Dial Zone Sensor
Wall-Mounted Fan Speed Switch
w/Setpoint Dial Zone Sensor
Unit-Mounted Fan Speed Switch
w/Wall-Mounted Setpoint Dial
Zone Sensor
Unit-Mounted Fan Speed Switch
& Wall-Mounted Setpoint Dial
w/Comm.
Unit-Mounted Fan Speed Switch,
On/Cancel, Setpoint Dial
w/ Comm.
Wall-Mounted On/Cancel
w/ Comm.
Wall-Mounted Fan Speed Switch,
Setpoint Dial, On/Cancel
w/ Comm.
Without Control Option
Unit-Mounted Low Voltage Fan
Speed Switch (Off /Hi /Med /Low)
Wall-Mounted Digital Zone
Sensor (OALMH, Setpoint,
On/Cancel, Comm Jack)
Wall-Mounted Digital Zone
Sensor (On/Cancel, Comm Jack)
Wireless Zone Sensor
Wireless Display Sensor, UnitMounted Receiver

Digit 32 - Not Used
0

Digit 33 -FLA Motor Option
0
A

=
=

Standard FLA ECM Mode
Reduced FLA ECM Mode

Digit 34 - Future Control
Functions
0

=

None

Digit 39 - Projection Panels and
Falsebacks
0 = None
A = 5/8” Standard Recessed Panel
(Vertical Recessed Units Only)
B = 2” Projection Panel
C = 2.5” Projection Panel
D = 3” Projection Panel
E = 3.5” Projection Panel
F = 4” Projection Panel
G = 4.5” Projection Panel
H = 5” Projection Panel
J = 5.5” Projection Panel
L = 2” Falseback
K = 6” Projection Panel
M = 3” Falseback
N = 4” Falseback
P = 5” Falseback
Q = 6” Falseback
R = 7” Falseback
T = 8” Falseback

Digit 40 - Main Autoflow gpm
A

=

0.5

H

=

B

=

0.75

J

=

3.5
4.0

C

=

1.0

K

=

4.5

D

=

1.5

L

=

5.0

E

=

2.0

M =

6.0

F

=

2.5

N

=

7.0

G

=

3.0

P

=

8.0

Digit 41 - Not Used
0

Digit 42 - Subbases
0
A
B
C
D
E
F

=
=
=
=
=
=
=

None
2” Subbase
3” Subbase
4” Subbase
5” Subbase
6” Subbase
7” Subbase

Digit 43 - Recessed Flange
0
A

=
=

None
Recessed Flange

Digit 44 - Wall Boxes
0
A

=
=

None
Anodized Wall Box

Digit 35 - Control Function #3
0

=

None

Digit 36 - Control Function #4
0

=

None

Digit 37 - Control Function #5
0

=

None

Digit 38 - Control Function #6
0

8

=

None

CAB-PRC001-EN

CAB-PRC001-EN.book Page 9 Tuesday, May 8, 2012 10:11 AM

General Data
Model A, Vertical Concealed
Outlet
Top Duct Collar

Inlet
Front Toe Space

Fresh Air
Bottom or Back

Model B, Vertical Cabinet
Outlet
Top Quad Grille, Top Bar Grille

Inlet
Front Toe Space,
Front Bar Grille

Fresh Air
Bottom or Back

Outlet
Front Stamped Louver

Inlet
Front Toe Space,
Front Bar Grille

CAB-PRC001-EN

Fresh Air
Bottom or Back

9

CAB-PRC001-EN.book Page 10 Tuesday, May 8, 2012 10:11 AM

General Data

Model C, Horizontal Concealed

Outlet
Front Duct Collar

Inlet
Back Duct Collar
Fresh Air
N/A
Fresh Air
Top or Back

Outlet
Front Duct Collar
Inlet
Bottom Toe Space

Inlet
Open Return
No Filter

Outlet
Front Duct Collar
Fresh Air
N/A

10

CAB-PRC001-EN

CAB-PRC001-EN.book Page 11 Tuesday, May 8, 2012 10:11 AM

General Data

Model D, Horizontal Cabinet

Fresh Air
Top or Back

Outlet
Front Quad
Grille, Front Bar Grille

Fresh Air
N/A

Inlet
Bottom Stamped
Louver

Outlet
Front Duct Collar

Fresh Air
Top or Back

Outlet
Front Duct Collar

Inlet
Bottom Stamped
Louver

Fresh Air
N/A

Outlet
Bottom Stamped
Louver
CAB-PRC001-EN

Inlet
Back Duct
Collar

Outlet
Front Quad
Grille, Front Bar Grille

Fresh Air
N/A

Outlet
Front Quad
Grille, Front Bar Grille

Inlet
Back Stamped
Louver

Fresh Air
N/A
Inlet
Back Stamped
Louver

Fresh Air
Top or Back

Inlet
Bottom Stamped
Louver

Inlet
Back Duct
Collar

Outlet
Front Duct Collar
Fresh Air
N/A

Outlet
Bottom Stamped
Louver

Inlet
Back Duct
Collar or
Stamped
Louver

11

CAB-PRC001-EN.book Page 12 Tuesday, May 8, 2012 10:11 AM

General Data

Model E, Horizontal Recessed
Fresh Air
Top or Back

Outlet
Front Duct Collar

Inlet
Bottom Stamped
Louver
Fresh Air
N/A

Inlet
Back Duct
Collar

Inlet
Back Duct
Collar

Outlet
Front Duct Collar
Fresh Air
Top or Back

Outlet
Bottom Stamped
Louver
Outlet
Bottom Stamped
Louver

Inlet
Bottom Stamped
Louver

Model F, Vertical Wall Hung Cabinet

Outlet
Top Quad Grille,
Top Bar Grille
Outlet
Front Stamped
Louver

Inlet
Bottom & Front
Stamped Louver

12

Fresh Air
Back

Inlet
Bottom & Front
Stamped Louver

Fresh Air
Back

CAB-PRC001-EN

CAB-PRC001-EN.book Page 13 Tuesday, May 8, 2012 10:11 AM

General Data

Model H, Vertical Recessed
Outlet
Top Duct Collar

Inlet
Front Stamped
Louver

Fresh Air
Bottom or Back

Outlet
Front
Stamped
Louver

Inlet
Front
Stamped
Louver

Fresh Air
Bottom or Back

Model J, Vertical Cabinet Slope Top
Outlet
Top Quad Grille, Top Bar Grille

Inlet
Front Toe Space,
Front Bar Grille

CAB-PRC001-EN

Fresh Air
Bottom or Back

13

CAB-PRC001-EN.book Page 14 Tuesday, May 8, 2012 10:11 AM

General Data

Model M, Inverted Vertical Concealed

Inlet
Front Stamped
Louver

Outlet
Front Stamped
Louver

Inlet
Top Duct
Collar

Outlet
Top Duct
Collar

Model N, Inverted Vertical Recessed

Inlet
Front Stamped
Louver

Outlet
Front Stamped
Louver

14

CAB-PRC001-EN

CAB-PRC001-EN.book Page 15 Tuesday, May 8, 2012 10:11 AM

General Data

Table 1.

Force-Flo cabinet heater general data

Unit Size

02

03

04

06

08

10

12

0.8

0.8

1.1

1.6

2.1

3.2

3.2

2-Row

15x1.7x8

15x1.7x8

20x1.7x8

29.5x1.7x8

38x1.7x8

57x1.7x8

57x1.7x8

3-Row

15x2.6x8

15x2.6x8

20x2.6x8

29.5x2.6x8

38x2.6x8

57x2.6x8

57x2.6x8

4-Row

15x3.5x8

15x3.5x8

20x3.5x8

29.5x3.5x8

38x3.5x8

57x3.5x8

57x3.5x8

1-Row

0.06

0.06

0.08

0.11

0.14

0.21

0.21

2-Row

0.12

0.12

0.15

0.22

0.28

0.42

0.42

3-Row

0.18

0.18

0.23

0.33

0.42

0.62

0.62

4-Row

0.24

0.24

0.30

0.44

0.56

0.83

0.83

2-Row

144

144

144

144

144

144

144

3-Row

144

144

144

144

144

144

144

4-Row

144

144

144

144

144

144

144

Coil Data
Face Area-ft2
LxDxH-in.

Volume-gal.

Fins/ft

Fan/Motor Data
Fan Quantity

1

1

1

2

2

3

3

Size-Dia.” x Width”

6.31x4

6.31x6.5

6.31x7.5

6.31x6.5

6.31x7.5

(1) 6.31x7.5

6.31x7.5

(2) 6.31x6.5
Motor Quantity

1

1

1

1

1

2

2

Quantity

1

1

1

1

1

1

1

Size-in.

8-7/8x19-1/8 8-7/8x19-1/8 8-7/8x24-1/8 8-7/8x33-5/8 8-7/8x42-1/8 8-7/8x61-1/8 8-7/8x61-1/8

Filter Data
1” TA and Pleated Media

1” Fresh Air Filter (Only on Cabinet Styles D, E, and H with Bottom Return and Fresh Air Opening)
Quantity

1

Size-in.

5-1/2x19-1/8 5-1/2x19-1/8 5-1/2x24-1/8 5-1/2x33-5/8 5-1/2x42-1/8 5-1/2x61-1/8 5-1/2x61-1/8

CAB-PRC001-EN

1

1

1

1

1

1

15

CAB-PRC001-EN.book Page 16 Tuesday, May 8, 2012 10:11 AM

General Data

Table 2.

Cabinet heater air flow
ESP
FD Motor

Unit Size

Coil

02

03

04

06

08

10

12

High Static Motor

0.05

0.1

0.2

0.3

0.4

2R144

246

344

314

283

251

3R144

242

352

319

284

249

4R144

222

326

295

263

230

2R144

313

410

380

350

319

3R144

309

391

358

324

290

4R144

276

360

330

299

267

2R144

381

446

410

373

336

3R144

365

544

506

467

427

4R144

340

506

470

434

397

2R144

609

757

700

642

582

3R144

604

880

824

766

707

4R144

557

812

760

706

652

2R144

790

1014

950

885

819

3R144

724

992

927

861

794

4R144

676

930

870

808

745

2R144

1015

1284

1199

1113

1024

3R144

1052

1456

1360

1262

1162

4R144

988

1366

1276

1183

1089

2R144

1105

1424

1330

1234

1134

3R144

1074

1514

1419

1320

1219

4R144

993

1421

1330

1238

1144

Note: This is data is based on horizontal concealed model only, with duct inlet, duct outlet and no filter, dry coil, all voltages
except 208 V.

Electric Heat
All Force-Flo cabinet heaters, except inverted models M and N, are available with electric heating
coils as a standard option.

Coil Construction
Electric heat coils are open wire type with a nickel chromium element design.

Power Supply
Units have single-point power since the electric heating elements operate on line voltage. Electric
heat is available as 208/60/1, 230/60/1, 277/60/1, 208/60/3, or 480/60/3. Electric heat coils operate on
the same voltage as the unit, except for units with 480/60/3 electric heat. In this case, the unit
operates at 277/60/1, thus requiring a 4-wire supply. All fans and motors are single phase. In
addition, all control options are 24-volt, utilizing a factory-installed transformer.

Power Supply Location
All electric heat cabinet heaters have a terminal block for main power on the unit’s right-hand side.

Control Type
Single-stage electric heat units are controlled by either Tracer UC400, ZN010, ZN510, or ZN520
control options. Two-stage electric heat is controlled by the Tracer UC400, ZN520 only. Both
control options use PWM (pulse-width modulation) outputs to calculate the electric heat output
16

CAB-PRC001-EN

CAB-PRC001-EN.book Page 17 Tuesday, May 8, 2012 10:11 AM

General Data

based on the capacity request and the electric heat cycles per hour. For example, if the electric heat
cycles per hour is configured for six cycles (as Trane recommends) the controller bases the output
on or off time on six 10-minute periods. If the capacity request is 40 percent, the controller controls
the electric heat output on for approximately four minutes each period.

Safety Features
•

Fan/valve operation to ensure safe operation and to ensure that two modes of heat are not
operating simultaneously.

•

All Force-Flo units with standard electric heat are UL listed.

•

Units require only a single-point electrical connection.

•

All electric heating coils are interlocked with the fan motor switch. Therefore, electric heat
operation is only possible when the fan is running.

•

Each unit has a transformer, eliminating the need for field installation of a stepdown
transformer.

•

Unit-mounted quiet magnetic relays are supplied on all unit voltages.

•

A line-break high temperature cutout with automatic reset is provided as an integral part of the
elements to de-energize the electric heat in the event of an overheat condition.

Factory-Installed Piping Packages
Force-Flo cabinet heaters have standard piping packages available as a factory built and installed
option. Factory built assures all piping packages are fully tested under water for leaks and are built
within strict tolerances. Factory-installed means that supply and return pipes are the only field
connections required. The installer doesn’t have to sweat connect piping packages onto coil
connections in a tight end pocket. Field connections are brought to a point near the exterior of the
unit for easy access.

Piping Package Components
Force-Flo piping packages consist of a variety of components for each application. The following
section provides a detailed description of the piping components. Following this section are
additional illustrations and specifications.

Piping System/Placement
Factory piping packages are available with right or left hand connections. A simple coil connection
(a unit without a piping package) is also available in either a right or left hand configuration for
those applications requiring field piping.

Interconnecting Piping
Interconnecting piping refers to the copper piping that attaches the coil connections and all other
components such as control valves, end valves, etc. Piping is 1/2” nominal OD copper and extends
near the unit exterior to one inlet and one outlet connection.

Deluxe or Basic Piping Package
The basic piping package includes only the main components of the piping package:
interconnecting piping, control valves, and end valves.
The deluxe piping package also includes a strainer on the entering water pipe and unions at the
coil connections along with the basic components listed above. The strainer body is cast brass
construction, with a stainless steel mesh strainer that is easily removed for cleaning. The unions
are forged brass construction and close with a minimum amount of effort.

CAB-PRC001-EN

17

CAB-PRC001-EN.book Page 18 Tuesday, May 8, 2012 10:11 AM

General Data

End Valves
Each piping package includes a ball valve for the entering water pipe and one of the following end
valves on the leaving water pipe: ball valve, manual circuit setter, or an auto circuit setter. These
valves serve as the field connection points on all Force-Flo piping packages.

Ball Valves
Ball valves, also known as stop or end valves, allow the unit to be cut off for service purposes. These
valves have a two-inch handle that rotates 90° to a fully open position. The valve body is cast brass,
and the ball is polished brass with a Teflon® seat. Ball valves are available as end valves on both
the entering and leaving water pipes.

Manual Circuit Setter
In lieu of a ball valve on the leaving water pipe, a manual circuit setter, also known as a manual flow
control valve, acts as both a flow setting device and a stop valve. This valve allows water flow
through the cabinet heater to be set quickly and accurately.
The manual circuit setter includes Schrader ports in the valve body. These ports are used to
measure the pressure drop across the valve. This pressure drop can be compared to factory
supplied curves that relate the pressure drop to a specific flow rate. This valve also has a memory
stop that helps find the correct setting quickly.

Auto Circuit Setter
An auto circuit setter is an automatic flow control device available on the leaving water pipe. The
auto circuit setter includes a cartridge within the valve body that is sized to allow a specific flow
rate through the coil. This valve sets flow through the coil without any action required by a system
piping balancer. The auto circuit setter is available on the leaving water pipe with a ball valve.
The auto circuit setter also includes two P/T’s plugs in the valve body to allow measurement of the
pressure drop temperature through the valve.

Control Valves
Piping packages are available with or without control valves. All control valve options are factory
mounted and wired to the Force-Flo unit controls.

Two-Way/Two-Position Valves
These valves will either fully open or close in response to a 24 Vac signal from the Tracer controller.
Control valves are direct-acting valves. The control valve is factory mounted in the leaving water
pipe downstream of the coil. Always use some means of relieving pump head pressure with twoway valve applications. Normally open or normally closed valves are available.

Three-Way/Two-Position Valves
These valves will either allow full water flow through the coil or divert the flow through a bypass
line. The valves respond to a 24 Vac signal from the Tracer controller. Control valves are direct
acting valves. All three-way valve packages include a balance fitting in the bypass line to allow flow
balancing in the bypass position. Three-way valves are factory mounted in the leaving water pipe
downstream of the coil. Normally open or normally closed valves are available.

Two-Way Modulating Valves
These valves modulate the water flow through the coil in response to a signal from the Tracer
controller. Modulating valves are three-wire floating point equal percentage valves, and are factory
mounted in the leaving water pipe downstream of the coil.

Three-Way Modulating Valves
These valves modulate the water flow through the coil in response to a signal from the Tracer
controller. Three-way valves allow water that is directed through the coil to mix with water directed
through the bypass line. This mixture exits through the leaving water pipe. Modulating valves are
18

CAB-PRC001-EN

CAB-PRC001-EN.book Page 19 Tuesday, May 8, 2012 10:11 AM

General Data

three-wire floating point equal percentage valves, and are factory mounted in the leaving water
pipe downstream of the coil.
Figure 1. Piping package options

Auto Flow Valve (C)

CAB-PRC001-EN

19

CAB-PRC001-EN.book Page 20 Tuesday, May 8, 2012 10:11 AM

General Data

Selecting the Correct Modulating Valve Size
Modulating valves are available in any of four port sizes: 0.7, 1.5, 2.5 or 4.0 Cv (coefficient of flow
values). The coefficient of flow is defined as the volume of water flow through a control valve in
the fully open position with a 1 psig differential across the valve. Calculate the coefficient of flow
using the formula:
Cv = Q/square root ΔP where:
Cv = flow coefficient
Q = flow rate (gpm)
ΔP = pressure drop across the valve or coil (psig).
For good control, the valve Cv should be approximately equal to the Cv of the water coil.

Modulating Valve Selection Example
Assume a size 06 vertical cabinet heater is selected to operate at the following conditions:
EWT = 180°F
LWT = 150°F
EAT = 70°F
The coil selection is a four-row coil. Select the best modulating valve size for this unit.
1. Find the ΔP across the water coil. Refer to the ARI performance table to determine the ΔP across
the water coil or use the Trane Official Product Selection System, TOPSS™, selection program.
The water pressure drop is found to be 5.7’ of water at a flow rate of 3.59 gpm. This converts
to a pressure drop of 2.47 psig (1.0 feet of water = 0.4328 psig.)
2. Calculate the Cv of the water coil.
Cv = gpm/Square root ΔP.
Cv = 3.59/Square root 2.47
Cv = 2.29
Therefore, select the 2.5 Cv valve because it is closest to the water coil.
Table 3 and Table 4, p. 21 illustrate possible valve selections at ARI conditions for horizontal
concealed units with a high static motor and vertical cabinet units with a free discharge motor. For
other applications, use TOPSS to determine flowrate and make calculations using the formulas
above.
Table 3.
Unit Size

Coil

gpm

Coil WPD

Coil Cv

Valve Cv

02

2-Row

1.19

6.0

0.74

0.7

03

04

06

20

Modulating valve selections for horizontal concealed units, high static motor, 70°F EAT,
180°F EWT, 30°F ΔT

3-Row

1.52

13.8

0.62

0.7

4-Row

1.59

3.8

1.24

1.5

2-Row

1.53

10.3

0.72

0.7

3-Row

1.82

4.3

1.33

1.5
1.5

4-Row

1.98

6.2

1.21

2-Row

1.73

3.3

1.45

1.5

3-Row

2.57

9.1

1.29

1.5

4-Row

2.81

13.4

1.17

1.5

2-Row

2.87

9.9

1.39

1.5

3-Row

3.96

5.9

2.48

2.5

4-Row

4.37

8.2

2.32

2.5

CAB-PRC001-EN

CAB-PRC001-EN.book Page 21 Tuesday, May 8, 2012 10:11 AM

General Data

Table 3.
Unit Size

Coil

gpm

Coil WPD

Coil Cv

Valve Cv

08

2-Row

3.71

4.7

2.60

2.5

10

12

Table 4.

3-Row

4.74

9.1

2.39

2.5

4-Row

5.22

12.7

2.23

2.5

2-Row

4.71

8.1

2.52

2.5

3-Row

6.50

18.1

2.32

2.5

4-Row

7.13

25.3

2.15

2.5

2-Row

5.48

11.4

2.47

2.5

3-Row

7.19

14.5

2.87

2.5

4-Row

7.83

10.5

3.67

4.0

Modulating valve selections for vertical cabinet units, free discharge motor, 70°F EAT,
180°F EWT, 30°F ΔT

Unit Size

Coil

gpm

Coil WPD

Coil Cv

02

2-Row

1.06

4.8

0.74

0.7

3-Row

1.31

10.5

0.61

0.7
1.5

03

04

06

08

10

12

CAB-PRC001-EN

Modulating valve selections for horizontal concealed units, high static motor, 70°F EAT,
180°F EWT, 30°F ΔT (continued)

Valve Cv

4-Row

1.34

2.8

1.22

2-Row

1.40

8.8

0.72

0.7

3-Row

1.70

3.8

1.33

1.5

4-Row

1.81

5.3

1.20

1.5

2-Row

1.71

3.2

1.45

1.5

3-Row

2.12

6.4

1.27

1.5

4-Row

2.28

9.1

1.15

1.5

2-Row

2.70

8.9

1.38

1.5

3-Row

3.31

4.2

2.46

2.5

4-Row

3.59

5.7

2.29

2.5

2-Row

3.39

4.0

2.58

2.5

3-Row

4.11

6.9

2.38

2.5
2.5

4-Row

4.45

9.4

2.21

2-Row

4.32

6.8

2.52

2.5

3-Row

5.55

13.4

2.30

2.5

4-Row

6.00

18.3

2.13

2.5

2-Row

4.99

9.6

2.45

2.5

3-Row

6.10

10.5

2.86

2.5

4-Row

6.48

7.3

3.65

4.0

21

CAB-PRC001-EN.book Page 22 Tuesday, May 8, 2012 10:11 AM

Performance Data
Force-Flo cabinet heater performance data is grouped based on performance. Unit performance
is impacted by the unit model and the airflow inlet and outlet configuration. Table 5 summarizes
the performance groups.
Table 5.

Force-Flo performance groupings

UNIT TYPE

Motor Type

Filter

Static

Performance Tables

Horizontal Concealed

Free Discharge

NO

0.05

Table 7 & Table 8

Horizontal Recessed

Free Discharge

NO

0.05

Vertical Recessed

Free Discharge

NO

0.05

Inverted Vertical Recessed

Free Discharge

NO

0.05

Vertical Concealed

Free Discharge

NO

0.05

Table 9 & Table 10

Horizontal Cabinet

Free Discharge

YES

0.00

Table 11 & Table 12

Vertical Cabinet

Free Discharge

YES

0.00

Inverted Vertical Cabinet

Free Discharge

YES

0.00

Vertical Slope Top

Free Discharge

YES

0.00

Table 13 & Table 14

Horizontal Concealed

High Static

NO

0.20

Table 15 & Table 16

Horizontal Recessed

High Static

NO

0.20

Vertical Recessed

High Static

NO

0.20

Horizontal Cabinet

High Static

NO

0.20

Vertical Concealed

High Static

NO

0.20

Table 6.

Table 17 & Table 18

Steam properties

Steam Pressure (psig)
Saturated Temperature (°F)
Latent Heat (Btu/lb)

2
219
965

5
227
960

10
239
952

15
250
945

Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T and gpm remain
constant. To determine heating capacities at a different saturated steam or entering air
temperature, compute the new ITD and multiply it by the new Q/ITD shown.

22

CAB-PRC001-EN

CAB-PRC001-EN.book Page 23 Tuesday, May 8, 2012 10:11 AM

Performance Data

Horizontal Concealed, Horizontal Recessed, Vertical Recessed, Inverted Vertical Recessed
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.05 ESP, without
filter. Free discharge EC motor.
Table 7.

Hot water performance—free discharge EC motor
Hot Water Coils

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Q/ITD

Flow Rate
(gpm)

WPD
(ft H20)

Motor
Power (W)

020

2HC
246
16.68
0.15
1.11
5.65
37
3HC
242
20.15
0.18
1.34
2.37
37
4HC
222
21.48
0.20
1.43
3.33
37
030
2HC
313
19.63
0.18
1.31
7.53
39
3HC
309
24.17
0.22
1.61
3.30
39
4HC
276
25.69
0.23
1.71
4.61
39
040
2HC
381
24.00
0.22
1.60
2.74
58
3HC
365
30.04
0.27
2.00
5.55
58
4HC
340
32.47
0.30
2.16
8.01
58
060
2HC
609
38.29
0.35
2.55
7.70
79
3HC
604
47.34
0.43
3.15
3.74
79
4HC
557
51.54
0.47
3.43
5.09
79
080
2HC
790
48.10
0.44
3.20
3.48
122
3HC
724
58.70
0.53
3.91
6.13
122
4HC
676
63.95
0.58
4.26
8.42
122
100
2HC
1015
66.94
0.61
4.46
7.51
145
3HC
1052
86.01
0.78
5.73
9.10
145
4HC
988
94.57
0.86
6.30
10.52
145
120
2HC
1105
70.88
0.64
4.72
8.37
160
3HC
1074
87.35
0.79
5.82
9.38
160
4HC
993
94.97
0.86
6.33
10.60
160
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant.To determine
heating capacities at a different entering water or entering air temperature, compute the new ITD and multiply
it by the new Q/ITD shown.

Table 8.

Steam coil performance—free discharge EC motor
2 PSIG

SIZE
020
030
040
060
080
100
120
Note:

CAB-PRC001-EN

COIL
Steam
Steam
Steam
Steam
Steam
Steam
Steam

Airflow
(cfm)
228
275
345
544
701
933
990

Total
Capacity
(MBh)
15.13
16.59
21.77
33.92
43.58
62.02
63.85

Q/ITD
0.102
0.111
0.146
0.228
0.292
0.416
0.429

5 PSIG
Heating
LAT (°F)
131
126
128
128
127
131
129

Total
Capacity
(MBh)
16.02
17.57
23.06
35.94
46.18
65.72
67.66

Q/ITD
0.102
0.112
0.147
0.229
0.294
0.419
0.431

Heating
LAT (°F)
135
129
132
131
131
135
133

Motor
Power
(W)
37
39
58
79
122
145
160

Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different saturated steam or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

23

CAB-PRC001-EN.book Page 24 Tuesday, May 8, 2012 10:11 AM

Performance Data

Vertical Concealed
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.05 ESP, without
filter. Free discharge EC motor.
Table 9.

SIZE

Hot water performance—free discharge EC motor

COIL

Airflow (cfm)

Hot Water Coils
Total Capacity
Flow Rate
(MBh)
Q/ITD
(gpm)

WPD
(ft H20)

Motor Power
(W)

020

2HC
211
14.91
0.14
0.99
4.64
37
3HC
205
17.63
0.16
1.17
1.86
37
4HC
192
18.93
0.17
1.26
2.65
37
030
2HC
272
17.89
0.16
1.19
6.40
39
3HC
270
21.92
0.20
1.46
2.76
39
4HC
247
23.48
0.21
1.56
3.92
39
040
2HC
340
22.21
0.20
1.48
2.37
58
3HC
328
27.65
0.25
1.84
4.77
58
4HC
309
29.98
0.27
2.00
6.94
58
060
2HC
535
35.16
0.32
2.34
6.58
79
3HC
531
43.07
0.39
2.87
3.13
79
4HC
499
47.13
0.43
3.14
4.30
79
080
2HC
697
44.29
0.40
2.95
2.98
122
3HC
646
53.90
0.49
3.59
5.22
122
4HC
612
58.94
0.54
3.93
7.23
122
100
2HC
891
61.04
0.55
4.07
6.31
145
3HC
913
77.24
0.70
5.14
7.39
145
4HC
870
85.08
0.77
5.67
8.68
145
120
2HC
980
65.32
0.59
4.35
7.17
160
3HC
958
80.12
0.73
5.34
7.94
160
4HC
899
87.46
0.80
5.83
9.12
160
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different entering water or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

Table 10. Steam coil performance—free discharge EC motor
2 PSIG

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Q/ITD

5 PSIG
Heating
LAT (°F)

Total
Capacity
(MBh)

Q/ITD

Heating
LAT (°F)

Motor
Power (W)

020
Steam
203
14.27
0.096
135
15.11
0.096
139
37
030
Steam
250
15.83
0.106
128
16.76
0.107
132
39
040
Steam
317
20.90
0.140
131
22.13
0.141
134
58
060
Steam
496
32.43
0.218
130
34.35
0.219
134
79
080
Steam
642
41.72
0.280
130
44.20
0.282
134
122
100
Steam
846
59.00
0.396
134
62.52
0.398
138
145
120
Steam
909
61.19
0.411
132
64.84
0.413
136
160
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different saturated steam or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

24

CAB-PRC001-EN

CAB-PRC001-EN.book Page 25 Tuesday, May 8, 2012 10:11 AM

Performance Data

Horizontal Cabinet, Vertical Cabinet, Inverted Vertical Cabinet
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0 ESP, throwaway
filter. Free discharge EC motor.
Table 11. Hot water performance—free discharge EC motor
Hot Water Coils

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Flow Rate
(gpm)

Q/ITD

WPD
(ft H20)

Motor Power
(W)

020

2HC
222
15.46
0.14
1.03
4.94
37
3HC
217
18.46
0.17
1.23
2.02
37
4HC
204
19.96
0.18
1.33
2.92
37
030
2HC
280
18.23
0.17
1.21
6.61
39
3HC
277
22.37
0.20
1.49
2.87
39
4HC
256
24.14
0.22
1.61
4.12
39
040
2HC
349
22.63
0.21
1.51
2.46
58
3HC
338
28.30
0.26
1.89
4.98
58
4HC
320
30.86
0.28
2.06
7.31
58
060
2HC
544
35.56
0.32
2.37
6.72
79
3HC
541
43.64
0.40
2.91
3.21
79
4HC
510
48.02
0.44
3.20
4.45
79
080
2HC
706
44.67
0.41
2.98
3.02
122
3HC
659
54.74
0.50
3.65
5.38
122
4HC
627
60.13
0.55
4.01
7.51
122
100
2HC
912
62.09
0.56
4.14
6.51
145
3HC
933
78.56
0.71
5.23
7.64
145
4HC
893
86.94
0.79
5.79
9.02
145
120
2HC
996
66.08
0.60
4.40
7.32
160
3HC
976
81.29
0.74
5.41
8.16
160
4HC
921
89.25
0.81
5.95
9.47
160
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different entering water or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

Table 12. Steam coil performance—free discharge EC motor
2 PSIG

SIZE

COIL

Total
Airflow Capacity
(cfm)
(MBh)

Q/ITD

5 PSIG
Heating
LAT (°F)

Total
Capacity
(MBh)

020
Steam
203
14.27
0.096
135
030
Steam
250
15.83
0.106
128
040
Steam
317
20.90
0.140
131
060
Steam
496
32.43
0.218
130
080
Steam
642
41.72
0.280
130
100
Steam
846
59.00
0.396
134
120
Steam
909
61.19
0.411
132
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T
capacities at a different saturated steam or entering air temperature,
Q/ITD shown.

Q/ITD

Heating
LAT (°F)

Motor
Power
(W)

15.11
0.096
139
37
16.76
0.107
132
39
22.13
0.141
134
58
34.35
0.219
134
79
44.20
0.282
134
122
62.52
0.398
138
145
64.84
0.413
136
160
and gpm remain constant. To determine heating
compute the new ITD and multiply it by the new

Note: The steam coil option is not available on the Horizontal Cabinet or Horizontal Recessed
models.

CAB-PRC001-EN

25

CAB-PRC001-EN.book Page 26 Tuesday, May 8, 2012 10:11 AM

Performance Data

Vertical Slope Top Cabinet
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0 ESP, throwaway
filter. Free discharge EC motor.
Table 13. Hot water performance—free discharge EC motor
Hot Water Coils

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Flow Rate
(gpm)

Q/ITD

WPD
(ft H20)

Motor Power
(W)

020

2HC
206
14.62
0.13
0.97
4.48
37
3HC
200
17.31
0.16
1.15
1.80
37
4HC
190
18.75
0.17
1.25
2.61
37
030
2HC
262
17.42
0.16
1.16
6.10
39
3HC
260
21.31
0.19
1.42
2.63
39
4HC
242
23.05
0.21
1.54
3.79
39
040
2HC
330
21.75
0.20
1.45
2.28
58
3HC
320
27.12
0.25
1.81
4.61
58
4HC
304
29.59
0.27
1.97
6.77
58
060
2HC
512
34.09
0.31
2.27
6.22
79
3HC
508
41.67
0.38
2.78
2.94
79
4HC
483
45.89
0.42
3.06
4.09
79
080
2HC
665
42.88
0.39
2.86
2.80
122
3HC
623
52.44
0.48
3.49
4.96
122
4HC
596
57.65
0.52
3.84
6.94
122
100
2HC
856
59.29
0.54
3.95
5.97
145
3HC
873
74.56
0.68
4.97
6.91
145
4HC
839
82.51
0.75
5.50
8.21
145
120
2HC
940
63.45
0.58
4.23
6.78
160
3HC
923
77.85
0.71
5.19
7.51
160
4HC
876
85.55
0.78
5.70
8.76
160
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different entering water or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

Table 14. Steam coil performance—free discharge EC motor
2 PSIG

SIZE

COIL

Total
Airflow Capacity
(cfm)
(MBh)

Q/ITD

5 PSIG
Heating
LAT (°F)

Total
Capacity
(MBh)

020
Steam
191
13.83
0.093
137
030
Steam
237
15.42
0.103
130
040
Steam
303
20.42
0.137
132
060
Steam
472
31.62
0.212
132
080
Steam
611
40.71
0.273
131
100
Steam
801
57.40
0.385
136
120
Steam
867
59.74
0.401
134
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T
capacities at a different saturated steam or entering air temperature,
Q/ITD shown.

26

Q/ITD

Heating
LAT (°F)

Motor
Power
(W)

14.64
0.093
141
37
16.33
0.104
134
39
21.63
0.138
136
58
33.49
0.213
135
79
43.13
0.275
135
122
60.81
0.387
140
145
63.30
0.403
137
160
and gpm remain constant. To determine heating
compute the new ITD and multiply it by the new

CAB-PRC001-EN

CAB-PRC001-EN.book Page 27 Tuesday, May 8, 2012 10:11 AM

Performance Data

Horizontal Concealed, Horizontal Recessed, Vertical Recessed, Horizontal Cabinet
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.20 ESP, without
filter. High static EC motor.
Table 15. Hot water performance—high static EC motor
Hot Water Coils

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Flow Rate
(gpm)

Q/ITD

WPD
(ft H20)

Motor Power
(W)

2HC
314
19.68
0.18
1.31
7.18
84
3HC
319
24.71
0.22
1.65
3.28
84
200
4HC
295
27.07
0.25
1.80
4.83
84
2HC
380
22.14
0.20
1.47
8.85
91
3HC
358
26.79
0.24
1.78
3.80
91
300
4HC
330
29.52
0.27
1.97
5.65
91
2HC
410
25.18
0.23
1.68
2.85
110
3HC
506
37.80
0.34
2.52
8.05
110
400
4HC
470
41.89
0.38
2.79
12.12
110
2HC
700
41.80
0.38
2.78
8.63
162
3HC
824
58.43
0.53
3.89
5.36
162
600
4HC
760
65.21
0.59
4.34
7.59
162
2HC
950
53.86
0.49
3.59
4.16
298
3HC
927
69.93
0.64
4.66
8.20
298
800
4HC
870
77.84
0.71
5.19
11.67
298
2HC
1199
74.76
0.68
4.98
8.90
252
3HC
1360
103.27
0.94
6.88
12.55
252
1000
4HC
1276
113.35
1.03
7.55
9.41
252
2HC
1330
79.76
0.73
5.31
10.07
314
3HC
1418
106.27
0.97
7.08
13.26
314
1200
4HC
1330
116.96
1.06
7.79
10.00
314
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different entering water or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

Table 16. Steam coil performance—high static EC motor
2 PSIG

SIZE

COIL

Total
Airflow Capacity
(cfm)
(MBh)

Q/ITD

5 PSIG
Heating
LAT (°F)

Total
Capacity
(MBh)

020
Steam
290
17.00
0.114
124
030
Steam
348
18.52
0.124
119
040
Steam
383
22.91
0.154
125
060
Steam
653
37.03
0.249
122
080
Steam
890
48.80
0.328
121
100
Steam
1140
68.37
0.459
125
120
Steam
1252
71.49
0.480
123
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T
capacities at a different saturated steam or entering air temperature,
Q/ITD shown.

Q/ITD

Heating
LAT (°F)

Motor
Power
(W)

18.01
0.115
127
84
19.62
0.125
122
91
24.27
0.155
128
110
39.24
0.250
125
162
51.73
0.329
124
298
72.47
0.462
129
252
75.79
0.483
126
314
and gpm remain constant. To determine heating
compute the new ITD and multiply it by the new

Note: The steam coil option is not available on the Horizontal Cabinet or Horizontal Recessed
models.

CAB-PRC001-EN

27

CAB-PRC001-EN.book Page 28 Tuesday, May 8, 2012 10:11 AM

Performance Data

Vertical Concealed
Heating performance is based on 70°F entering air temperature, 180°F entering hot water
temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.20 ESP, without
filter. High static EC motor.
Table 17. Hot water performance—high static EC motor
Hot Water Coils

SIZE

COIL

Airflow
(cfm)

Total
Capacity
(MBh)

Flow Rate
(gpm)

Q/ITD

WPD
(ft H20)

Motor Power
(W)

2HC
274
17.95
0.16
1.20
6.11
84
3HC
274
22.13
0.20
1.47
2.68
84
200
4HC
258
24.31
0.22
1.62
3.97
84
2HC
341
20.70
0.19
1.38
7.86
91
3HC
319
24.76
0.23
1.65
3.29
91
300
4HC
299
27.36
0.25
1.82
4.92
91
2HC
377
23.84
0.22
1.59
2.58
110
3HC
455
35.17
0.32
2.34
7.05
110
400
4HC
429
39.04
0.35
2.60
10.66
110
2HC
632
39.23
0.36
2.61
7.68
162
3HC
733
54.10
0.49
3.60
4.63
162
600
4HC
687
60.53
0.55
4.03
6.60
162
2HC
865
50.88
0.46
3.39
3.73
298
3HC
845
65.58
0.60
4.37
7.26
298
800
4HC
800
73.06
0.66
4.87
10.36
298
2HC
1089
70.18
0.64
4.68
7.90
252
3HC
1206
95.02
0.86
6.33
10.68
252
1000
4HC
1145
104.37
0.95
6.95
8.02
252
2HC
1218
75.51
0.69
5.03
9.07
314
3HC
1291
99.64
0.91
6.64
11.71
314
1200
4HC
1223
109.80
1.00
7.31
8.85
314
Note: Q/ITD = MBh / (entering water temp - entering air temp) When Δ T and gpm remain constant. To determine heating
capacities at a different entering water or entering air temperature, compute the new ITD and multiply it by the new
Q/ITD shown.

Table 18. Steam coil performance—high static EC motor
2 PSIG

SIZE

COIL

Total
Airflow Capacity
(cfm)
(MBh)

Q/ITD

5 PSIG
Heating
LAT (°F)

Total
Capacity
(MBh)

020
Steam
257
16.06
0.108
128
030
Steam
317
17.75
0.119
122
040
Steam
356
22.12
0.148
127
060
Steam
598
35.51
0.238
125
080
Steam
820
46.97
0.315
123
100
Steam
1045
65.56
0.440
128
120
Steam
1159
68.93
0.463
125
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T
capacities at a different saturated steam or entering air temperature,
Q/ITD shown.

28

Q/ITD

Heating
LAT (°F)

Motor
Power
(W)

17.01
0.108
131
84
18.80
0.120
125
91
23.44
0.149
131
110
37.63
0.240
128
162
49.78
0.317
126
298
69.48
0.443
131
252
73.06
0.465
128
314
and gpm remain constant. To determine heating
compute the new ITD and multiply it by the new

CAB-PRC001-EN

CAB-PRC001-EN.book Page 29 Tuesday, May 8, 2012 10:11 AM

Controls
ECM Engine Controller
The Electronically Commutated Motor (ECM) engine controls and reports the performance of up
to two Trane Brushless DC (BLDC) motors.
Figure 2. ECM engine controller

•

The engine also coordinates the operation of the fan in response to electric heat behavior and
electric behavior in response to hydronic heat behavior.

•

The engine incorporates a user interface that allows adjustment of certain unit parameters and
provides constant feedback on motor operation.

•

The engine integrates service and troubleshooting tools.

•

The engine integrates a versatile configurable auxiliary temperature sensor.

•

The engine incorporates various safety and lockout features, such as maintaining proper fan
speeds if electric heat is called for.

Status Display
Figure 3. Status display

The ECM engine board contains a four-digit, seven-segment display that is used to present
information in a format close to real-world language, while having a small-form factor. Most
characters are immediately recognizable; however, please consult Table 19 and Table 20 for the
graphical representation of each alphanumeric character.
Table 19. Screen representation of alphabetical characters
A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z





















































Table 20. Screen representation of numeric characters
1

2

3

4

5

6

7

8

9

0





















CAB-PRC001-EN

29

CAB-PRC001-EN.book Page 30 Tuesday, May 8, 2012 10:11 AM

Controls

Control Options
Force-Flo cabinet heaters are available with four different control options:
•

Manual three-speed fan switch

•

Tracer ZN010

•

Tracer ZN510

•

Tracer ZN520

•

Tracer UC400

Fan speed switch

Tracer ZN010 control board

Tracer ZN510 control board

Manual Fan Mode Switch
Model Number Digit 30 = A and Digit 31 = D or K
Figure 4. Adapter board
Note: Customer Low-Voltage Interface for
Fan Speeds, Variable Fan Speed, and
24 Vac Supply

30

CAB-PRC001-EN

CAB-PRC001-EN.book Page 31 Tuesday, May 8, 2012 10:11 AM

Controls

The adapter allows direct customer interfacing through the use of terminal strips. Standard
interfacing includes:
•

Fan Speeds (H, M, L) (for wall mounted fan speed switches)

•

Variable speed (0–10V) inputs

The standard adapter board eliminates many separate wiring harnesses in the panel and allows
simple, mistake-proofed single-plug interfacing of:
•

The ECM engine controller

•

Transformers

•

Motors

•

Valves

•

Dampers

•

Electric heat control

•

Fan speed switches

•

Main power (except electric heat)

The manual fan mode switch is available for fan-coil units that do not have Trane factory-mounted
control packages. This four-position switch (off, high, medium, low) allows manual fan mode
selection and is available unit or wall mounted. The unit-mounted option (Digit 31 = D) operates
on line voltage. The wall-mounted option (Digit 31 = K) is low-voltage and has three 24-volt relays
using a factory-wired transformer and relays to control the fan motor.

Customer Supplied Terminal Interface (CSTI)
Figure 5. CSTI adapter board
Customer Low-Voltage Interface for
Valves, Electric Heat, Dampers, Fan
Speeds, Variable Fan Speed, and
24 Vac Supply

Valve(s), Electric Heat, and Changeover
Configuration Switches (Factory-Set)

CAB-PRC001-EN

31

CAB-PRC001-EN.book Page 32 Tuesday, May 8, 2012 10:11 AM

Controls

Figure 6. CSTI adapter board field connections
3

2

1

13 12 11 10

9

8

7

6

5

4

3

2

1

1.

VSP 10V

2.

VSP 0–10V

3.

VSP DC COM

1.

24 Vac Y (hot)

2.

24 Vac Y (gnd)

3.

High

4.

Medium

5.

Low

6.

V1Op/Cooling

7.

V1C1 (not std)

8.

Not used

9.

Not used

10. V2Op/EH1St/Heating
11. V2C1/EH2St (not std)
12. Damper Open
13. Dmp Cl (not std)

The control interface is intended to be used with a field-supplied, low-voltage thermostat or
controller. The control box contains a relay board which includes a line voltage to 24-volt
transformer, quiet contactors (for electric heat units), and an optional disconnect switch. All end
devices are wired to a low-voltage terminal block and are run-tested, so the only a power
connection and thermostat connection is needed to commission the unit. Changeover sensors and
controls are provided whenever a change-over coil is selected. When N.O. valves are selected,
inverting relays are provided for use with standard thermostats.
The CSTI adapter board provides all the hookups of the standard adapter board, but in addition,
provides hookups for valve control (main and auxiliary coils), electric heat control, and damper
control. Screw terminal blocks provide convenient access to fan controls and to end device control.
In addition, a courtesy 10-Vdc supply is provided for use with an external potentiometer or rheostat.
The 10-Vdc supply supports up to 10 mA draw.

Tracer Controls
The Tracer family of controllers (Tracer ZN010, ZN510, ZN520, and UC400) offer the combined
advantages of simple and dependable operation with the latest Trane-designed controller.
Standard control features include options normally available on more elaborate control systems.
All control options are available factory-configured or can be field-configured using Trane service
software. For more detailed information, refer to CNT-IOP-1 (for Tracer ZN010 or ZN510) or
CNT-SVX04A-EN (for Tracer ZN520), or UNT-SVX07D-EN (for Tracer UC400), or the most recent
version of the publication

Tracer ZN010, Model Number digit 30 = E
Tracer ZN010 is a stand-alone microprocessor controller.

Tracer ZN510, Model Number digit 30 = F
Tracer ZN510 can be used as either a stand-alone or communicating microprocessor controller.

Tracer ZN520, Model Number digit 30 = G
Tracer ZN520 controller can be used in a stand-alone application or as part of a Trane Integrated
Comfort™ System (ICS).

32

CAB-PRC001-EN

CAB-PRC001-EN.book Page 33 Tuesday, May 8, 2012 10:11 AM

Controls

In the stand-alone configuration, Tracer ZN520 receives operation commands from the zone
sensor. The zone sensor module is capable of transmitting the following information to the
controller:
•

Timed override on/cancel request

•

Zone setpoint

•

Current zone temperature

•

Fan mode selection (off-auto-high-med-low)

For optimal system performance, Force-Flo units can be linked to an Integrated Comfort System
(ICS) building automation system controlled by Tracer SC. The controller is connected to the
building automation system with a LON Talk communications network. The Trane ICS system can
monitor or override Tracer ZN520 control points. This includes such points as temperature and
output positions.

Tracer UC400, Model Number Digit 30 = J
Figure 7.

The UC400 controller can be used in a stand-alone application or as part of a Trane Integrated
Comfort™ System (ICS).
In the stand-alone configuration, UC400 receives operation commands from the zone sensor
and/or the auto changeover sensor (on auto changeover units). The entering water temperature is
read from the auto changeover sensor and determines if the unit is capable of cooling or heating.
The zone sensor module is capable of transmitting the following information to the controller:
•

Timed override on/cancel request

•

Zone setpoint

•

Current zone temperature

•

Fan mode selection (off-auto-high-med-low)

For optimal system performance, fan-coil units can operate as part of an Integrated Comfort
System (ICS) building automation system controlled by Tracer SC. The controller is linked to the
building automation system using BACnet MS/TP. The building automation system can monitor or
override UC400 control points. This includes such points as temperature and output positions.

Service Software
A windows-based software package option allows field service personnel to easily monitor, save,
download, and configure Tracer unit controllers directly or through a communication link from a
portable computer. When connected over the communication link, the service software can view
any Tracer ZN controller that is on the same communication link. See Tracer TU or Rover literature
for more details.

CAB-PRC001-EN

33

CAB-PRC001-EN.book Page 34 Tuesday, May 8, 2012 10:11 AM

Controls

Sequence of Operation
Fan Speed Switch
Off: Fan is turned off, two-position damper option spring-returns closed.
High, Medium, Low: Fan runs continuously at the selected speed. The two-position damper option
opens to an adjustable mechanical stop position.

Tracer ZN010 and ZN510
Off: Fan is off; control valves and fresh air damper option close.
Auto (Fan Cycling): Fan and fresh air damper cycle with control valve option to maintain setpoint
temperature. In heating mode it cycles from off to low (factory default that can be field-adjusted
using Rover service software). When heating is not required, the fan is off and the fresh air damper
option closes. The fan can also be field-configured (using Rover) to run at a user-defined speed
when the fan speed switch is in the auto position.
Low, Medium, High (Continuous Fan): Fan operates continuously while control valve option cycles
to maintain setpoint temperature. Fresh air damper option is open.

Tracer ZN520
Off: Fan is off; control valve options and fresh air damper options close.
Auto: Fan speed control in the auto setting allows the modulating (three-wire floating point) control
valve option and three-speed fan to work cooperatively to meet precise capacity requirements,
while minimizing fan speed (motor/energy/acoustics) and valve position (pump energy). As the
capacity requirement increases at low fan speed, the water valve opens. When the low fan speed
capacity switch point is reached, the fan switches to medium speed and the water valve repositions
to maintain an equivalent capacity. The reverse sequence takes place with a decrease in required
capacity.
Low, Medium, High: The fan will run continuously at the selected speed and the valve option will
cycle to meet setpoint.

Tracer UC400
Off: Fan is off; control valve options and fresh air damper options close.
Auto: Fan speed control in the auto setting allows the modulating (three-wire floating point) control
valve option and three-speed fan to work cooperatively to meet precise capacity requirements,
while minimizing fan speed (motor/energy/acoustics) and valve position (pump energy). As the
capacity requirement increases at low fan speed, the water valve opens. When the low fan speed
capacity switch point is reached, the fan switches to medium speed and the water valve repositions
to maintain an equivalent capacity. The reverse sequence takes place with a decrease in required
capacity.
Low, Medium, High: The fan will run continuously at the selected speed and the valve option will
cycle to meet setpoint.

Occupied Mode
In Occupied Mode, the UC400 controller maintains the space temperature based on the occupied
space temperature setpoint ± occupied offset. The controller uses the occupied mode as a default
mode when other forms of occupancy request are not present and the fan runs continuously. The
outdoor air damper, if present, will close when the fan is OFF. The temperature setpoints can be
local (hard wired), communicated, or stored default values (configurable using the Tracer TU
service tool).

Unoccupied Mode
In unoccupied mode, the UC400 controller attempts to maintain the space temperature based on
the unoccupied heating or cooling setpoint. The fan will cycle between high speed and OFF. In

34

CAB-PRC001-EN

CAB-PRC001-EN.book Page 35 Tuesday, May 8, 2012 10:11 AM

Controls

addition, the outdoor air damper remains closed, unless economizing. The controller always uses
the stored default setpoint values (configurable using the Tracer TU service tool), regardless of the
presence of a hard wired or communicated setpoint value.

Timed Override Control
If the UC400 controller has a timed override option (ON/CANCEL buttons), pushing the ON button
initiates a timed override on request. A timed override on request changes the occupancy mode
from unoccupied mode to occupied bypass mode. In occupied bypass mode, the controller
controls the space temperature based on the occupied heating or cooling setpoints. The occupied
bypass time, which resides in the UC400 controller and defines the duration of the override, is
configurable from 0 to 240 minutes (default value of 120 minutes). When the occupied bypass time
expires, the unit transitions from occupied bypass mode to unoccupied mode. Pushing the
CANCEL button cancels the timed override request. In addition, it will end the timed override
before the occupied bypass time has expired and transition the unit from occupied bypass mode
to unoccupied mode.
If the controller is in any mode other than unoccupied mode when the ON button is pressed, the
controller still starts the occupied bypass timer without changing to occupied bypass mode. If the
controller is placed in unoccupied mode before the occupied bypass timer expires, the controller
is placed into occupied bypass mode and remains in this mode until either the CANCEL button is
pressed on the Trane zone sensor or the occupied bypass time expires.

Zone Temperature Control
The UC400 controller has three methods of zone temperature control:
•

Cascade zone control—used in the occupied, occupied bypass, and occupied standby
modes. It maintains zone temperature by controlling the discharge air temperature to control
the zone temperature. The controller uses the difference between the measured zone
temperature and the active zone temperature setpoint to produce a discharge air temperature
setpoint. The controller compares the discharge air temperature setpoint with the discharge air
temperature and calculates a unit heating/cooling capacity accordingly (refer to the illustration
below). The end devices (outdoor air damper, valves, and so on) operate in sequence based on
the unit heating/cooling capacity (0–100 percent).
Active zone
temperature
setpoint

Difference

Measured
zone
temperature

Calculated
discharge air
temperature
setpoint

Difference

Calculated unit
heating/cooling
capacity

Measured
discharge air
temperature

If the discharge air temperature falls below the discharge air temperature low limit setpoint,
(configurable using the Tracer TU service tool), and the cooling capacity is at a minimum, the
available heating capacity is used to raise the discharge air temperature to the low limit.

CAB-PRC001-EN

•

Simplified zone control— if discharge air temperature failure occurs, then simplified zone
controls runs. In the unoccupied mode, the controller maintains the zone temperature by
calculating the required heating or cooling capacity (0–100%) according to the measured zone
temperature and the active zone temperature setpoint. The active zone temperature setpoint
is determined by the current operating modes, which include occupancy and heat/cool modes.

•

Discharge air temperature control— is the backup mode that runs only if there is not valid
zone temperature. In this mode, the active space temperature setpoint is used as the discharge
air temperature setpoint.
35

CAB-PRC001-EN.book Page 36 Tuesday, May 8, 2012 10:11 AM

Controls

Important: This is not a normal operating mode. The source of the invalid zone temperature
needs to be corrected to restore normal operation.
Table 21. Controller input/output summary
ZN010

ZN510

ZN520

UC400

X

X

X

X
X

2-Position Hydronic Valve
2-Position Fresh Air Damper
1-Stage Electric Heat
3-Wire Economizer Damper
3-Wire Hydronic Valve
2-Stage Electric Heat
Reheat (hydronic or electric)
Generic
Binary Inputs

X
X
X

X
X
X

X

X

Condensate Overflow Detection
Low Temperature Detection
Occupancy
Generic Input
Analog Inputs
Zone Temperature
Setpoint
Fan Mode: Auto, High, Medium, Low
Entering Water
Discharge Air
Outside Air
Generic
Analog Outputs
Variable speed fan
Field supplied analog valves

Binary Outputs
3-Speed Fan

X

X
X
X
X
X
X

X
X
X
X
X
X
X
**

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
**

X
X
X
X

X
X
X
X

X
X
X
X

X
X
X
X

X

X

X
X
X

X
X
**
X
X

Note: The generic input and output are for use with a Tracer Building Automation System only.

Table 22. Controller function summary
Control Functions
Entering Water Temp. Sampling (Purge)
Auto Changeover
Fan Cycling
Warm-Up
Pre-Cool
Data Sharing (Master/Slave)
Random Start
Dehumidification
Acoustic Mode
Efficiency Mode
Single Zone VAV Mode
Staged Capacity (2-Stage Electric Supplementary)
Other Functions
Manual Test
Maintenance Timer
Setpoint Limits

ZN010

ZN510

ZN520

UC400

X
X
X
X
X

X
X
X
X
X
X
X

X
X

X
X

X

X
X
X

X
X
X

X
X
X
X
X

X

X
X
X
X
X
X

X
X
X

in TU
X
X

** 'Generic' i/o - if there is unused i/o the user may create a new point to reference the i/o. But there is no dedicated 'generic'
i/o like on ZN
Binary inputs -- there is also a defrost and fan status (for 1,2,3 speed fans) for UC400 and ZN520.
The ECM fan does not use the Binary input for fan status but gets the info over IMC from the ECM.
ZN520 also had a binary input for fan status. ZN520 also had defrost but it was wired directly to the compressor (IOP
explains this).

36

CAB-PRC001-EN

CAB-PRC001-EN.book Page 37 Tuesday, May 8, 2012 10:11 AM

Controls

Zone Sensor Options
Zone sensors are available as either unit, wall, or split-mounted options for design flexibility. ForceFlo units with the unit-mounted zone sensor option include a thermistor in the unit’s return air path.
Wall-mounted zone sensor options have an internal thermistor. Zone sensors operate on 24 Vac.

Tracer ZN010 Options

Tracer UC400, ZN510, and ZN520 Options

Figure 8. Unit-mounted zone sensor: Digit 30 = E and
Digit 31 = V

Figure 9. Wall-mounted zone sensor: Digit 30 = F or G
and Digit 31 = 1

X13790843-01

Figure 10. Wall-mounted zone sensor: Digit 30 = E and
Digit 31 = W
X13790841-01

Figure 12. Split-mounted zone sensor, unit-mounted fan
mode and wall-mounted setpoint dial:
Digit 30 = E and Digit 31 = X
X13511529-01 (wall)
X13790849-01 (unit)

X13511530-01 (wall)
X13651467-02 (comm)

Figure 11. Wall-mounted zone sensor: Digit 30 = F or G
and Digit 31 = 2
X13790842-01 (wall)
X13651467-02 (comm)

Figure 13. Split-mounted zone sensor, unit-mounted fan
mode and wall-mounted setpoint dial:
Digit 30 = F or G and Digit 31 = Y
X13511527-01 (wall)
X13790849-01 (unit)
X13651467-02 (comm)

Figure 14. Unit-mounted zone sensor: Digit 30 = F or G
and Digit 31 = Z
X13790844-01

CAB-PRC001-EN

37

CAB-PRC001-EN.book Page 38 Tuesday, May 8, 2012 10:11 AM

Controls

Tracer UC400, ZN510, and ZN520 Options
(continued)
Figure 15. Wall-mounted digital zone sensor with
setpoint adjustment: Digit 30 = F or G and
Digit 31 = 4
X13790886-04 (wall)

Figure 16. Wireless zone sensor (setpoint adjustment, no
fan speed adjustment): Digit 30 = F or G and
Digit 31 = 6
X13790821-01 (wall)
X13790860-02 (unit)

Figure 17. Wireless zone sensor: Digit 30 = F or G and
Digit 31 = 7
X13790822-04 (wall)
X13790860-02 (unit)

Control Features
The following control functions are standard features on units with Tracer UC400, ZN010, ZN510,
ZN520, or UC400.

Occupied/Unoccupied Operation
The occupancy input utilizes a binary switch (i.e. motion sensor, timeclock, etc.) that allows the zone
sensor to utilize its unoccupied internal setpoints.

Random Start
This feature randomly staggers multiple unit startup to reduce electrical demand spikes.

Warmup
The two-position fresh air damper option closes during the occupied mode when the space
temperature is three degrees or more below the heating setpoint temperature. The damper
remains closed during warmup until the space temperature is within two degrees of the heating
setpoint temperature.
38

CAB-PRC001-EN

CAB-PRC001-EN.book Page 39 Tuesday, May 8, 2012 10:11 AM

Controls

Manual Output Test Function
This feature is an invaluable tool for troubleshooting a unit. By simply pressing the controller’s test
button, service personnel can manually exercise outputs in a pre-defined sequence.

Peer to Peer Communication (Tracer ZN510, ZN520, and UC400)
Peer to peer communication allows multiple units in one space to share the same zone sensor and
provide simultaneous heating. The Tracer ZN510 or ZN520 controller can share information
between units on the same communication link using a twisted pair wire in the field. Unit
configuration must be modified with Rover service tool. On the UC400, zone sensor data sharing
can be accomplished by use of the BAS system controller.

Tracer ZN520 and UC400 Additional Features
Filter Maintenance Status
Tracer controller has an adjustable timer that indicates through the building automation system or
the service software tool when filter maintenance is necessary. Filter maintenance status is based
on cumulative fan run hours.

Water Valve Override
Using the building automation system or the service software tool, the water valve override
function drives all water valves in every unit fully open simultaneously. This helps reduce the time
required for waterside balancing.

Cascade Control
Tracer controller maintains discharge air temperature using a cascade control algorithm. The
discharge air temperature is based on the difference between the space temperature and setpoint.
Unit capacity modulates to achieve the discharge air temperature.

Interoperability
Tracer ZN520 can be used with a Tracer Summit system or on other control systems that support
LonTalk® and the SCC profile. For more information on specific inputs and outputs, see UNT-IOM-6
(Installation, Operation, and Maintenance: UniTrane® Fan-Coil Room Conditioners - Force Flo™
Cabinet Heaters), or the most recent version.
The Tracer UC400 can be used with the Tracer SC or another BACnet MS/TP building automation
system. For more information see the Installation Operation and Programming Guide BAS-SVX48
for more information.

End Device Options
All end device options are factory-installed and -tested.

Two-Position Control Valves; Model Number Digits 27 & 28 = A–H
Two-position valve options are available with either Tracer ZN010, ZN510, ZN520, or UC400. Valves
are spring-return type, sweat connections, and available as normally open or closed. The valves
respond to a 24 V signal and have 1/2-inch sweat connections. The two-way valve option will either
fully open or close. The three-way valve option allows either full water flow through the coil or
diverts waterflow through the bypass. If the control valve loses power, the valve returns to its deenergized position. All control valve options are factory installed in the leaving water piping
downstream of the hydronic coil. The valve actuator is easily removable for service without
removing the valve body from piping.

Modulating Control Valves (Tracer ZN520 and UC400); Model Number Digits 27
& 28 = J–R
These 1/2-inch sweat connect valves are three-wire floating point valves, equal percentage type.
Modulating valves are available in four Cv sizes: 0.7, 1.5, 2.5, and 4.0. The valve responds to a 24 V
CAB-PRC001-EN

39

CAB-PRC001-EN.book Page 40 Tuesday, May 8, 2012 10:11 AM

Controls

triac signal from the controller, which determines the valve position by a control algorithm. If the
valve loses power, it remains in the position that it was in when the power loss occurred. All control
valves are factory installed in the leaving water piping downstream of the hydronic coil.

Field-Supplied Valves; Model Number Digits 27 and 28 = X, Y, Z or 1.
When using field-supplied valves, this option allows the controller to be factory-configured for the
normal position of the field-supplied valve.
Note: Trane does not recommend wild coil applications.

Two-Position Fresh Air Damper Actuator; Model Number Digit 13 = D, E, or F
(Available with all control options except Tracer ZN520)
This damper actuator uses a 24 V signal and is factory-wired and mounted to the damper assembly.
It allows zero to 50 percent fresh air. The damper will drive open to an adjustable mechanical stopposition whenever the fan is running during occupied mode and will spring-return closed when the
fan turns off.

40

CAB-PRC001-EN

CAB-PRC001-EN.book Page 41 Tuesday, May 8, 2012 10:11 AM

Electrical Data
Table 23. Two-stage electric heat (digit 18 = U)
Voltage
Wires
1st Stage kW
Total kW
Total amps/ph
208/60/1
2
0.75
2.25
10.9
240/60/1
2
1.0
3.0
12.5
277/60/1
2
1.0
3.0
10.9
208/60/3
3
0.75
2.25
6.3
240/60/3
3
1.0
3.0
7.3
480/60/3
4
1.0
3.0
3.7
03
208/60/1
2
1.5
4.5
21.7
240/60/1
2
2.0
6.0
25.0
277/60/1
2
2.0
6.0
21.7
208/60/3
3
1.5
4.5
12.6
240/60/3
3
2.0
6.0
14.5
480/60/3
4
2.0
6.0
7.3
04
208/60/1
2
1.9
5.7
27.5
240/60/1
2
2.5
7.5
31.3
277/60/1
2
2.5
7.5
27.1
208/60/3
3
1.9
5.7
15.9
240/60/3
3
2.5
7.5
18.1
480/60/3
4
2.5
7.5
9.1
06
208/60/1
2
3.4
7.9
38.0
240/60/1
2
4.5
10.5
43.8
277/60/1
2
4.5
10.5
38.0
208/60/3
3
3.4
7.9
21.9
240/60/3
3
4.5
10.5
25.3
480/60/3
4
4.5
10.5
12.7
08
208/60/1
2
4.5
10.1
48.8
240/60/1
2
6.0
13.5
56.3
277/60/1
2
6.0
13.5
48.8
208/60/3
3
4.5
10.1
28.2
240/60/3
3
6.0
13.5
32.5
480/60/3
4
6.0
13.5
16.3
10
208/60/1
2
6.0
13.5
65.0
240/60/1
2
8.0
18.0
75.0
277/60/1
2
8.0
18.0
65.0
208/60/3
3
6.0
13.5
37.6
240/60/3
3
8.0
18.0
43.3
480/60/3
4
8.0
18.0
21.7
12
208/60/1
2
6.8
15.0
72.3
240/60/1
2
9.0
20.0
83.4
277/60/1
2
9.0
20.0
72.3
208/60/3
3
6.8
15.0
41.7
240/60/3
3
9.0
20.0
48.2
480/60/3
4
9.0
20.0
24.1
Note: When both stages are on, the electric heat will operate only when fan is in high speed. All data based
on individual units.
Unit Size
02

CAB-PRC001-EN

41

CAB-PRC001-EN.book Page 42 Tuesday, May 8, 2012 10:11 AM

Electrical Data

Table 24. Single-stage, max kW electric heat (digit 18 = N)
Unit Size
02

Voltage
Wires
Heater kW
Heater amps/ph
208/60/1
2
2.25
10.9
240/60/1
2
3.0
12.5
277/60/1
2
3.0
10.9
208/60/3
3
2.25
6.3
240/60/3
3
3.0
7.3
480/60/3
4
3.0
3.7
03
208/60/1
2
4.5
21.7
240/60/1
2
6.0
25.0
277/60/1
2
6.0
21.7
208/60/3
3
4.5
12.6
240/60/3
3
6.0
14.5
480/60/3
4
6.0
7.3
04
208/60/1
2
5.7
27.5
240/60/1
2
7.5
31.3
277/60/1
2
7.5
27.1
208/60/3
3
5.7
15.9
240/60/3
3
7.5
18.1
480/60/3
4
7.5
9.1
06
208/60/1
2
7.9
38.0
240/60/1
2
10.5
43.8
277/60/1
2
10.5
38.0
208/60/3
3
7.9
21.9
240/60/3
3
10.5
25.3
480/60/3
4
10.5
12.7
Note: All data based on individual units. Electric heat will operate only with fan at high speed.

Table 25. Single stage, low kW electric heat (digit 18 = V)
Unit Size
02

Voltage
# Wires
kW
amps/ph
kW
amps/ph
208/60/1
2
0.75
3.7
1.5
7.3
240/60/1
2
1.0
4.2
2.0
8.4
277/60/1
2
1.0
3.7
2.0
7.3
03
208/60/1
2
2.25
10.9
240/60/1
2
3.0
12.5
277/60/1
2
3.0
10.9
208/60/3
3
2.25
6.3
240/60/3
3
3.0
7.3
480/60/3
4
3.0
3.7
04
208/60/1
2
2.25
10.9
240/60/1
2
3.0
12.5
277/60/1
2
3.0
10.9
208/60/3
3
2.25
6.3
240/60/3
3
3.0
7.3
480/60/3
4
3.0
3.7
06
208/60/1
2
2.25
10.9
3.3
15.9
240/60/1
2
3.0
12.5
4.5
18.8
277/60/1
2
3.0
10.9
4.5
16.3
208/60/3
3
2.25
6.3
3.3
9.2
240/60/3
3
3.0
7.3
4.5
10.9
480/60/3
4
3.0
3.7
4.5
5.5
08
208/60/1
2
2.25
10.9
3.3
15.9
240/60/1
2
3.0
12.5
4.5
18.8
277/60/1
2
3.0
10.9
4.5
16.3
208/60/3
3
2.25
6.3
3.3
9.2
240/60/3
3
3.0
7.3
4.5
10.9
480/60/3
4
3.0
3.7
4.5
5.5
10
208/60/1
2
2.25
10.9
3.3
15.9
240/60/1
2
3.0
12.5
4.5
18.8
277/60/1
2
3.0
10.9
4.5
16.3
208/60/3
3
2.25
6.3
3.3
9.2
240/60/3
3
3.0
7.3
4.5
10.9
480/60/3
4
3.0
3.7
4.5
5.5
12
208/60/1
2
2.25
10.9
3.3
15.9
240/60/1
2
3.0
12.5
4.5
18.8
277/60/1
2
3.0
10.9
4.5
16.3
208/60/3
3
2.25
6.3
3.3
9.2
240/60/3
3
3.0
7.3
4.5
10.9
480/60/3
4
3.0
3.7
4.5
5.5
Note: All data based on individual units. Electric heat will operate only with fan at high speed.

42

kW

amps/ph

4.5
6.0
6.0
4.5
6.0
6.0
5.7
7.5
7.5
5.7
7.5
7.5
6.6
9.0
9.0
6.6
9.0
9.0

21.7
25.0
21.7
12.5
14.5
7.3
27.5
31.3
27.1
15.9
18.1
9.1
31.8
37.5
32.5
18.4
21.7
10.9

CAB-PRC001-EN

CAB-PRC001-EN.book Page 43 Tuesday, May 8, 2012 10:11 AM

Electrical Data

Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations
Units with Electric Heat. HACR (heating, air conditioning, and refrigeration) type circuit
breakers are required in the branch circuit wiring for all units with electric heat. To compute MCA
and MFS, see Table 26, p. 44 through Table 29, p. 44 for motor FLAs and Table 23, p. 41 through
Table 25, p. 42 for electric heat amps.
Calculating electric heat amps:
Single stage, three phase = heat kW * 1000/1.732/volts
Two stage, three phase = total heat kW * 1000/1.732/volts
Note: Use 240 V heat voltage for 230 V units.
Calculating MCA (units with electric heat):
MCA = 1.25 * (heat amps + sum of all motor FLAs)
Calculating MFS (units with electric heat):
MFS = (2.25 * largest motor FLA) + second motor FLA, size 10-12 units only + heat amps
Use the closest larger fuse or HACR circuit breaker above the MCA. Standard fuse sizes are: 15,
20, 25, 30, 35, 40, 45, 50, 60 amps.
Electric heat MBh = heater kW * 3.413

Units without Electric Heat. To compute MCA and MFS, see Table 26, p. 44 through Table 29,
p. 44 for motor FLAs and Table 23, p. 41 through Table 25, p. 42 for electric heat amps.
Calculating MCA (units without electric heat):
MCA = (1.25) x largest motor FLA + second motor FLA, unit sizes 10 and 12 only
Calculating MFS (units without electric heat):
MFS or HACR1 type circuit breaker = 15 amps for all units without electric heat.

1

CAB-PRC001-EN

HACR (heating, air-conditioning and refrigeration) type circuit breakers are required in the branch circuit wiring for all size 10 and 12
units.

43

CAB-PRC001-EN.book Page 44 Tuesday, May 8, 2012 10:11 AM

Electrical Data

Table 26. Free discharge electrically commutated motors (ECMs) programmed to standard ECM
mode
115 Volt

208–230 Volt

FLA

HP
2

1

FLA
2

277 Volt

HP

1

2

FLA

1

2

HP

Unit Size

1

1

2

1

2

3.1

0.22

1.8

0.22

1.6

0.24

2

3

3.1

0.22

1.8

0.22

1.6

0.24

4

3.1

0.22

1.8

0.22

1.6

0.24

6

3.1

0.22

1.8

0.22

1.6

0.24

8

3.1

0.22

1.8

0.22

1.6

10

3.1

3.1

0.22

0.22

1.8

1.8

0.22

0.22

1.6

1.6

0.24

0.24

12

3.1

3.1

0.22

0.22

1.8

1.8

0.22

0.22

1.6

1.6

0.24

0.24

0.24

Table 27. High static electrically commutated motors (ECMs) on units programmed to standard
ECM mode
115 Volt
FLA
Unit Size

1

2

3.1

208–230 Volt
HP

2

1

FLA
2

0.22

277 Volt

HP

1

2

1.8

FLA

1

2

0.22

1

HP
2

1.6

1

2

0.24

3

3.1

0.22

1.8

0.22

1.6

0.24

4

3.1

0.22

1.8

0.22

1.6

0.24

6

3.1

0.22

1.8

0.22

1.6

0.24

8

3.1

0.22

1.8

0.22

1.6

0.24

10

3.1

3.1

0.22

0.22

1.8

1.8

0.22

0.22

1.6

1.6

0.24

0.24

12

3.1

3.1

0.22

0.22

1.8

1.8

0.22

0.22

1.6

1.6

0.24

0.24

Table 28. Free discharge electrically commutated motors (ECMs) programmed to reduced FLA
mode
115 Volt
FLA
Unit Size

1

2

0.6

208–230 Volt
HP

2

1

FLA
2

0.22

1

277 Volt

HP
2

0.4

1

FLA
2

0.22

1

HP
2

0.3

1

2

0.24

3

0.6

0.22

0.4

0.22

0.3

0.24

4

0.8

0.22

0.6

0.22

0.4

0.24

6

1.1

0.22

0.8

0.22

0.6

0.24

8

1.6

0.22

1.1

0.22

0.8

0.24

10

0.7

1.2

0.22

0.22

0.5

0.8

0.22

0.22

0.4

0.6

0.24

0.24

12

0.7

1.3

0.22

0.22

0.5

0.9

0.22

0.22

0.4

0.7

0.24

0.24

Table 29. High static electrically commutated motors (ECMs) programmed to reduced FLA mode
115 Volt
FLA

44

208–230 Volt

HP (kW)
2

1

2

FLA
2

2

2

1.3

0.22

0.9

0.22

0.7

0.24

3

1.3

0.22

0.9

0.22

0.7

0.24

4

1.7

0.22

1.2

0.22

0.9

0.24

6

2.3

0.22

1.6

0.22

1.2

0.24

0.22

1

HP (kW)

1

1.8

1

FLA

Unit Size

0.22

1

277 Volt

HP (kW)

2

1.5

1

2

8

3.1

10

1.4

2

0.22

0.22

1

1.4

0.22

0.22

0.7

1.1

0.24
0.24

0.24

12

1.5

2.8

0.22

0.22

1.1

1.8

0.22

0.22

0.8

1.4

0.24

0.24

CAB-PRC001-EN

CAB-PRC001-EN.book Page 45 Tuesday, May 8, 2012 10:11 AM

Electrical Data

Table 30. Unit RPM
Unit
Size
2
3
4
6
8
10
12

Unit
Size
2
3
4
6
8
10
12

Free Discharge-Units with 2-Row Coils
H
M
L
980
980
1050
1030
1080
1050
1030
1050
1080

840
780
780
780
800
780
780
780
800

655
580
580
580
600
580
580
580
600

High Static-Units with 2-Row Coils
H
M
L
1480
1400
1475
1400
1475
1475
1400
1475
1475

1110
1175
1315
1070
1285
1315
1070
1315
1285

865
860
1070
855
975
1070
855
1070
975

Free Discharge-Units with 3- and 4-Row Coils
H
M
L
980
1080
1080
1080
1080
1080
1080
1080
1080

840
800
800
800
800
800
800
800
800

655
600
600
600
600
600
600
600
600

High Static-Units with 3- and 4-Row Coils
H
M
L
1480
1500
1580
1475
1475
1580
1475
1580
1475

1110
1355
1375
1285
1285
1375
1285
1375
1285

865
1110
1240
975
975
1240
975
1240
975

Note: Actual rpm will vary with application and configuration.

CAB-PRC001-EN

45

CAB-PRC001-EN.book Page 46 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights
Vertical Concealed, Model A

Vertical Concealed Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-3 7/8”

2’-8 7/8”

3’-6 3/8”

4’-2 7/8”

5’-9 7/8”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

3’-1 5/16”

3’-9 13/16”

5’-4 13/16”

D

1’-10 13/16” 2’-3 13/16”
1’-5 5/16”

1’-10 5/16”

2’-7 13/16”

3’-4 5/16”

4’-11 5/16”

E

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-4 5/16”

5’-1 5/16”

Notes:
1. Coil connections are always opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 58 for dimensions for air openings.

46

CAB-PRC001-EN

CAB-PRC001-EN.book Page 47 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Vertical Cabinet, Model B

Vertical Cabinet Unit
Unit Size
No. of
Fans
No. of
Motors

200–300

400

600

800

1000-1200

1

1

2

2

3

1

1

1

1

2

A

2’-9 7/8”

3’-2 5/16”

3’-11 13/16”

4’-8 5/16”

6’-3 5/16”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

7 5/8”

7 1/8”

8’ 7/8”

7 1/8”

7 5/8”

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-6 5/16”

5’-1 5/16”

F

3’-5 5/16”

3’-10 5/16”

4’-7 13/16”

5’-4 5/16”

6’-11 5/16”

Notes:
1. Coil connections are always opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. See p. 58 for dimensions for air openings.

CAB-PRC001-EN

47

CAB-PRC001-EN.book Page 48 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Horizontal Concealed, Model C

Horizontal Concealed Unit
Unit Size
No. of
Fans
No. of
Motors
A
B
C

200–300

400

600

800

1000-1200

1

1

2

2

3

1

1

1

1

2

2’-4 1/16”

2’-9 1/16”

3’-6 9/16”

4’-3 1/16”

1’-10 1/16”

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

3’-1 5/16”

3’-9 13/16”

5’-4 13/16”

1’-10 13/16” 2’-3 13/16”

D

1’-7 3/8”

2’-0 3/8”

2’-9 7/8”

3’-6 3/8”

5’-1 3/8”

E

1’-6 1/8”

1’-11 1/8”

2’-8 5/8”

3’-5 1/8”

5’-0 1/8”

F

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-6 5/16”

5’-1 5/16”

Notes:
1. Coil connections are always opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 58 for dimensions for air openings.

48

CAB-PRC001-EN

CAB-PRC001-EN.book Page 49 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Horizontal Cabinet, Model D

Horizontal Cabinet Unit
Unit Size
No. of
Fans
No. of
Motors

200–300

400

600

800

1000-1200

1

1

2

2

3

1

1

1

1

2

A

2’-9 5/16”

3’-1 5/16”

3’-11 3/16”

4’-8 5/16”

6’-3 5/16”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

7 5/8”

7 1/8”

8 7/8”

7 1/8”

7 5/8”

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-5 1/4”

1’-10 1/4”

2’-7 3/4”

3’-4 1/4”

4’-11 1/4”

F

3’-5 5/16”

3’-10 5/16”

4’-7 3/16”

5’-4 5/16”

6’-11 5/16”

G

8-5/8”

8-1/8”

9-1/8”

8-1/8”

8-5/8”

H

1’-4”

1’-10”

2’-4”

3’-4”

4’-10”

J

1’-7 3/4”

1’-11 3/4”

2’-7 3/4”

3’-3 3/4”

4’-11 3/4”

Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 57 for dimensions for outside air openings.

CAB-PRC001-EN

49

CAB-PRC001-EN.book Page 50 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Horizontal Recessed, Model E

Horizontal Recessed Unit
Unit Size
No. of
Fans
No. of
Motors
A
B
C

200–300

400

600

800

1000-1200

1

1

2

2

3

1

1

2’-11 13/16” 3’-4 13/16”
1’-9 5/16”

2’-2 5/16”

1’-10 13/16” 2’-3 13/16”

1

1

2

4’-2 5/16”

4’-10 13/16”

6’-5 13/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

3’-1 5/16”

3’-9 13/16”

5’-4 13/16”
5’-1 3/8”

D

1’-7 3/8”

2’-0 3/8”

2’-9 7/8”

3’-6 3/8”

E

1’-6 1/8”

1’-11 1/8”

2’-8 5/8”

3’-5 1/8”

5’-0 1/8”

F

2’-8 7/16”

3’-1 7/16”

3’-10 15/16”

4’-7 7/16”

6’-2 7/16”

G

2’-10 5/16”

3’-3 5/16”

4’-0 13/16”

4’-9 5/16”

6’-4 5/16”

H

1’-7 3/4”

1’-11 3/4”

2’-7 3/4”

3’-3 3/4”

4’-11 3/4”

Notes:
1. Coil connections are always opposite the drain pan side.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 57 for dimensions for outside air openings.

50

CAB-PRC001-EN

CAB-PRC001-EN.book Page 51 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Vertical Wall Hung Cabinet, Model F

Vertical Wall Hung Cabinet Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-9 5/16”

3’-2 5/16”

3’-11 13/16”

4’-8 5/16”

6’-3 5/16”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

7 5/8”

7 1/8”

8 7/8”

7 1/8”

7 5/8”

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-6 5/16”

5’-1 5/16”

F

1’-7 3/4”

1’-11 3/4”

2’-7 3/4”

3’-3 3/4”

4’-11 3/4”

Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 58 for dimensions for outside air openings.

CAB-PRC001-EN

51

CAB-PRC001-EN.book Page 52 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Vertical Recessed, Model H
Vertical Recessed Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-3 7/8”

2’-8 7/8”

3’-6 3/8”

4’-2 7/8”

5’-9 7/8”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

1’-10 13/16” 2’-3 13/16”

3’-1 5/16”

3’-9 13/16”

5’-4 13/16”

2’-7 13/16”

3’-4 5/16”

3’-11 5/16”

4’-3”

5’-3”

5’-5 1/2”

7’-5 1/2”

2’-6”

2’-6”

2’-9 1/2”

2’-9 1/2”

2-3/8”

2-3/8”

2-3/8”

4-1/8”

4-1/8”

3’-6”

4’-0”

4’-9”

5’-3”

7’-3”

2’-2 1/2”

2’-2 1/2”

2’-2 1/2”

2’-3 1/2”

2’-3 1/2”

D

1’-5 5/16”

1’-10 5/16”

E

3’-11”

F

2’-6”

G
H
J

Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 57 for dimensions for outside air openings.

52

CAB-PRC001-EN

CAB-PRC001-EN.book Page 53 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Vertical Slope Top, Model J

Vertical Slope Top Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-9 5/16”

3’-2 5/16”

3’-11 13/16”

4’-8 5/16”

6’-3 5/16”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

7 5/8”

7 1/8”

8 7/8”

7 1/8”

7 5/8”

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-6 5/16”

5’-1 5/16”

F

3’-5 5/16”

3’-10 5/16”

4’-7 13/16”

5’-4 5/16”

6’-11 5/16”

Notes:
1. Coil connections are always on the drain pan side and opposite the control box
and unit control.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. See p. 58 for dimensions for outside air openings.

CAB-PRC001-EN

53

CAB-PRC001-EN.book Page 54 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Inverted Vertical Cabinet, Model M

Inverted Vertical Cabinet Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-9 5/16”

3’-2 5/16”

3’-11 13/16”

4’-8 5/16”

6’-3 5/16”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”

C

7 5/8”

7 1/8”

8 7/8”

7 1/8”

7 5/8”

D

1’-6”

2’-0”

2’-6”

3’-6”

5’-0”

E

1’-7 5/16”

2’-0 5/16”

2’-9 13/16”

3’-6 5/16”

5’-1 5/16”

F

1’-7 3/4”

1’-11 3/4”

2’-7 3/4”

3’-3 3/4”

4’-11 3/4”

Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 58 for dimensions for outside air openings.

54

CAB-PRC001-EN

CAB-PRC001-EN.book Page 55 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Inverted Vertical Recessed, Model N
Inverted Vertical Recessed Unit
Unit Size

200–300

400

600

800

1000-1200

No. of
Fans

1

1

2

2

3

No. of
Motors

1

1

1

1

2

A

2’-3 7/8”

2’-8 7/8”

3’-6 3/8”

4’-2 7/8”

5’-9 7/8”

B

1’-9 5/16”

2’-2 5/16”

2’-11 13/16”

3’-8 5/16”

5’-3 5/16”
5’-4 13/16”

C

3’-1 5/16”

3’-9 13/16”

D

1’-10 13/16” 2’-3 13/16”
2’ 3/8”

2’ 3/8”

2’ 3/8”

4’ 1/8”

4’ 1/8”

E

3’-11”

4’-3”

5’-3”

5’-5 1/2”

7’-5 1/2”

F

2’-6”

2’-6”

2’-6”

2’-9 1/2”

2’-9 1/2”

E

2’-2 1/2”

2’-2 1/2”

2’-2 1/2”

2’-3 1/2”

2’-3 1/2”

F

3’-6”

4’-0”

4’-9”

5’-3”

7’-3”

Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 56 for locations.
3. See p. 58 for dimensions for outside air openings.

CAB-PRC001-EN

55

CAB-PRC001-EN.book Page 56 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Coil Connections
Vertical Units
5-3/8" HS

HR = Hot Water Return
HS = Hot Water Supply

5-5/16" HS

5-5/16" HS

5-5/16" HS

4-7/16" HR
4-3/8" HR

4-3/8" HR

4-3/8" HR

21-13/16"
HS

23-3/8"
HS

20-13/16"
HR

22-3/8"
HR

Horizontal Units

Inverted Units

4-3/8"
HR

5-5/16"
HS

22-3/8" HS

21-3/8" HR
4-7/16"
HS
4-3/8"
HR

5-7/16"
HR

5-5/16"
HS
4-3/8" HR

5-5/16" HS
HR = Hot Water Return
HS = Hot Water Supply

HR = Hot Water Return
HS = Hot Water Supply

2-13/16"
HS

56

3-13/16"
HR

CAB-PRC001-EN

CAB-PRC001-EN.book Page 57 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Fresh Air Opening Locations-Horizontal Units Models C, D, and E

1-5/8"

1-5/8"

2-15/16"

1-5/8"

1-5/8"
1-5/8"

2-15/16"

Fresh Air Opening Dimensions, Horizontal Units
Unit Size

CAB-PRC001-EN

02–03

04

06

08

A

18”

23”

32-1/2”

41”

10–12
60”

B

21-5/16”

26-5/16”

35-13/16”

44-5/16”

63-5/16”

57

CAB-PRC001-EN.book Page 58 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Fresh Air Opening Locations-Vertical Units Models A, B, F, and J

1-5/8"

1-5/8"

2-15/16"

1-5/8"

1-5/8"

WALL HUNG

2-15/16"

Fresh Air Opening Dimensions, Vertical Units
Unit Size

58

02–03

04

06

08

A

18”

23”

32-1/2”

41”

10–12
60”

B

21-5/16”

26-5/16”

35-13/16”

44-5/16”

63-5/16”

CAB-PRC001-EN

CAB-PRC001-EN.book Page 59 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Wall Box
CONTINUOUS
MORTAR RIBS
TOP AND BOTTOM

Wall Box Dimension
Unit Size
Ref. Only

1/8”

1/8”

1/2”

Dimensions
AxB

Internal
Supports

02–03

24-3/8” x 4-3/4”

1

04

24-3/8” x 7-1/2”

1

06

33-1/8” x 7-1/2”

2

08

37-1/2” x 7-1/2”

3

10–12

58-1/4” x 7-1/2”

4

3/4”
1/2”
1-3/8”

1/8”
4”
CLEARANCE
FOR DRAINAGE

CONTINUOUS DRIP LIP
TOP AND BOTTOM

CAB-PRC001-EN

WOVEN ALUMINUM
INSECT SCREEN

ADDITIONAL INTERNAL
SUPPORTS EQUALLY SPACED.
NOT TO EXCEED 12” O.C.

5/8”

59

CAB-PRC001-EN.book Page 60 Tuesday, May 8, 2012 10:11 AM

Dimensions and Weights

Projection Panel
UNIT TO WALL-TOP VIEW

FRONT VIEW ISO

REAR VIEW ISO

Projection Panel Dimensions
Unit Size

02–03

04

06

08

10–12

A

47”

51”

63”

65-1/2”

89-1/2”

B

30”

30”

30”

339-1/2”

33-1/2”

Projection Panel Dimensions
C

2”

2-1/2”

3”

3-1/2”

4”

4-1/2”

5”

5-1/2”

6”

D

1-1/8”

1-5/8”

2-1/8”

2-5/8”

3-1/8”

3-5/8”

4-1/8”

4-5/8”

5-1/8”

E

8-5/8”

8-1/8”

7-5/8”

7-1/8”

6-5/8”

6-1/8”

5-5/8”

5-1/8”

4-5/8”

60

CAB-PRC001-EN

CAB-PRC001-EN.book Page 61 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications
Force-Flo Cabinet Heater Mechanical Specifications
Performance Data
Capacity: Unit capacities are in accordance with Industry Room Fan-Coil Air Conditioner
Certification Program under ARI Standard 440-97. Safety: All standard units are UL listed in the
United States and Canada. Units comply with NFPA90A requirements.

Construction-All Units
The unit includes a chassis, coil, fan wheel(s), fan casing(s), fan board, and motor(s). The fan board
assembly is easily removable. The fan board assembly includes a quick-disconnect motor plug. The
chassis construction is 18-gage galvanized steel, and continuous throughout the unit. The unit is
acoustically and thermally insulated with closed-cell insulation. All panels are made rigid by
channel forming.

Vertical Cabinet and Slope Top Units
Front panel fabrication is 16-gage galvanized steel. All other panels are 18-gage galvanized steel.
Hinged access door construction is 20-gage steel and is flush with top panel.

Vertical Wall Hung Unit
Front panel fabrication is 16-gage galvanized steel. All other panels are 18-gage galvanized steel.
Side panels are removable for piping access.

Horizontal Cabinet Units
All panels are 18-gage galvanized steel, including the bottom panel. The hinged access door is flush
with front panel. Bottom panels ship with tamperproof screw fasteners and safety chain.

Concealed/Recessed Units
Exposed panels on recessed units are 18-gage steel construction and ship separate from the unit.
Bottom panels on horizontal recessed models ship with tamperproof screw fasteners and safety
chain. Horizontal recessed units feature a telescoping panel to allow the panel to be adjusted to line
up flush with the ceiling. The telescoping panel extends 1.25” to 2” depending on the configuration
of airflow.

Unit Finish
All cabinet parts and exposed recessed panels are cleaned, bonderized, phosphatized, and painted
with a baked powder finish available in six decorator colors. Standard finish meets ASTM B117
specifications (salt spray test).

Fans
The galvanized metal fan wheels are centrifugal forward-curved and double-width. Fan wheels and
housings are corrosion resistant. Fan housing construction is formed sheet metal.

Motors
All motors are brushless DC (BLDC)/electronically commutated motors (ECM) factoryprogrammed and run-tested in assembled units. The motor controller is mounted in a touch-safe
control box with a built-in integrated user interface and LED tachometer. If adjustments are needed,
motor parameters can be adjusted through momentary contact switches accessible without
factory service personnel on the motor control board.
Motors will soft-ramp between speeds to lessen the acoustics due to sudden speed changes.
Motors can be operated at three speeds or with a field-supplied variable speed controller. The
motor will choose the highest speed if there are simultaneous/conflicting speed requests.
All motors have integral thermal overload protection with a maximum ambient operating
temperature of 104°F and are permanently lubricated. Motors are capable of starting at 50 percent
CAB-PRC001-EN

61

CAB-PRC001-EN.book Page 62 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

of rated voltage and operating at 90 percent of rated voltage on all speed settings. Motors can
operate up to 10 percent over voltage.

Controls
Controls options are: fan speed switch, control interface, and Tracer UC400, ZN010, ZN510, and
ZN520. A variety of inputs and outputs are available for the control interface and Tracer controller
options. A disconnect switch (for non-electric heat units), fused transformer, contactor(s), and
terminal strip are provided with the control interface and Tracer controller options. For specifics on
the Tracer UC400, ZN010, ZN510, and ZN520, please refer to “Controls,” p. 29.

Control Interface
The control interface is intended to be used with a field-supplied, low-voltage thermostat or
controller. The control box contains a relay board which includes a line voltage to 24-volt
transformer, quiet contactors (for electric heat units), and an optional disconnect switch. All end
devices are wired to a low-voltage terminal block and are run-tested, so the only a power
connection and thermostat connection is needed to commission the unit. Changeover sensors and
controls are provided whenever a change-over coil is selected. When NO valves are selected,
inverting relays are provided for use with standard thermostats.

Fan Speed Switch
The fan speed switch is available with or without the control interface option and is available as
wall-mount or unit-mount. Both the wall-mount and unit-mount FSS will employ low-voltage fan
switches. However, the low-voltage fan speed option will provide an interface to factory wiring,
including variable-speed/high-medium-low (HML) control. The control box contains a line voltage
to 24-volt transformer, ECM motor controller, and an optional disconnect switch.

Hot Water Coils
Hot water coils are proof tested at 350 psig (air under water) and leak tested at 125 psig (air under
water). Additionally a pressure decay test is conducted at 120 psig.
Maximum main coil working pressure is 300 psig. Maximum entering water temperature is 200°F.
Tubes and u-bends are 3/8”OD copper. Fins are aluminum and are mechanically bonded to the
copper tubes. Coil stubouts are 5/8”OD copper tubing.

Steam Coils
The steam heating coil is a one-row, tube-in-tube distributing type coil. Coil construction is
aluminum fins mechanically bonded with 1”OD copper tubing. Steam coils are (air) burst tested
at 250 psig. Maximum steam coil working pressure is 100 psig. Maximum entering steam
temperature is 325°F. Tubes and u-bends are 5/8” OD copper. Fins are aluminum, 9 fpi, and are
mechanically bonded to the copper tubes. Coil stubouts are 1” OD copper tubing. Piping is fieldsupplied.

Piping Packages (Hot Water Coils Only)
All piping packages are proof-tested at 350 psig (air under water) and leak-tested at 125 psig (air
under water). The maximum working pressure of the interconnecting piping is 300 psig.
Piping packages are available in either basic or deluxe configurations. The deluxe package includes
unions at the coil connections and a 20 mesh strainer on the supply side with a pressure rating on
the strainer of up to 400 psig. The basic package does not include either unions or the strainer.
End valve options available on both the basic and deluxe piping packages include ball valves,
manual circuit setters, and auto circuit setters.

Ball Valve Supply and Return
A ball-type stop valve is on the piping supply and return. The ball valve is a shutoff valve only with
a maximum working pressure of 400 psig.

62

CAB-PRC001-EN

CAB-PRC001-EN.book Page 63 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

Ball Valve Supply, Manual Circuit Setter Return
A ball valve is provided on the supply with a manual circuit setter on the return. The manual circuit
setter is a combination flow-setting device and shutoff valve that includes two Schrader ports. The
maximum working pressure of the valve is 300 psig.

Ball Valve S & R, Auto Circuit Setter Return
Ball type end valves are mounted on the supply and return, with an additional auto circuit setter
mounted on the return. The auto circuit setter is an automatic flow control valve that is sized to
allow a specific flow rate through the coil. Auto circuit setters also include two P/T plugs and have
a maximum working pressure of 400 psig.

Control Valve Options
All control valves have a maximum working pressure of 300 psig. The maximum entering water
temperature of the valve is 200°F.

Two-Way, Two-Position Control Valves
When using two-way valves, use some means such as a pump and chiller bypass to ensure the
maximum closed off DP rating of the valve is not exceeded. Two-way, two-position valves are rated
for a maximum pressure differential across the valves of 30 psig. The valves are also available with
a close-off pressure of 50 psig. The valve actuator is easily removable for service without removing
the valve body from piping.

Three-Way, Two-Position Control Valves
Normally open three-way, two-position valves are rated for a maximum 28 psig pressure
differential across the valve. Normally closed three-way two-position valves are rated for a
maximum 20 psig pressure differential across the valve. All 3-way valve piping packages include
a bypass line with a balance fitting to set flow through the bypass line. The balance fitting has a
maximum working pressure of 150 psig. The valves are also available with a maximum close-off
pressure of 50 psig. The valve actuator is easily removable for service without removing the valve
body from piping.

Modulating Control Valves
Two-way and three-way modulating valves are rated for a maximum 50 psig pressure differential
across the valve. Modulating valves are available in Cv values of 0.7, 1.5, 2.5, and 4.0.

Electric Heat Coil
A single- or dual-stage electric heating coil is provided as the total source of heat. Electric heat coils
are open-wire type. The coils are a nickel-chromium element design. The electric heat operates at
the same voltage as the unit, and only a single power connection is necessary.
All units with factory-mounted electric heat are UL-listed and interlocked with the fan motor switch.
A call for electric heat operation will turn the fan on. Motors controls are synchronized with
fan/valve operation to ensure safe operation and to ensure that two modes of heat are not
operating simultaneously. A transformer is supplied on any voltage unit, eliminating the need for
field installation of a step-down transformer. Unit-mounted quiet magnetic relays are supplied on
all voltages. A line-break high temperature cutout with automatic reset is provided as an integral
part of the elements to de-energize the electric heat in the event of a malfunction.

Filters
Filters are concealed from sight and easily removable. Filters are located behind an integral access
door on horizontal type units. Filters are either 1” throwaway, MERV 8, or MERV 13.
Units equipped with 1” MERV 8 filters have a rating based on ASHRAE Standard 52.2. The average
dust spot efficiency is no less than 35 to 40 percent when tested in accordance with ASHRAE 52.1
atmospheric dust spot method.

CAB-PRC001-EN

63

CAB-PRC001-EN.book Page 64 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

Units equipped with 1” MERV 13 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and
greater than 90 percent efficiency on 3–10 micron particles when tested in accordance with
ASHRAE Test Standard 52.2.

Fresh Air Damper
A fresh air opening with damper is a factory-installed option. Dampers are constructed of 18-gage
steel. Fresh air is sealed off with gasket material when the damper is set in the closed position.
Return and fresh air mixes when the damper is open.

Manual Damper
The manual damper is field-adjustable to allow zero to 100 percent fresh air. The automatic twoposition damper is accompanied by a factory-installed and wired two-position (spring-return)
actuator.

Auto Two-Position Damper
The auto two-position damper is factory set at 25 percent when open. The damper can be set in the
field to allow from zero to 50 percent fresh air.

Disconnect Switch
A unit mounted disconnect switch is available as a standard option on all units (except electric heat
units).

Colors
Six decorator colors are available in a baked powder finish. For a color chart, contact your local
Trane office for a copy of UNT-SLB017-EN (Color Selector: Cabinet Heaters, Fan-Coils, Unit
Ventilators, & Water-Source Heat Pump Consoles).

Extended End Pockets
On vertical or horizontal cabinet units, an 8” extended end pocket is available on the piping end.

Tamperproof Locks
Key-operated locking access doors and/or panels will help prevent nuisance tampering with unit
and/or controls. Tamperproof locks are available on vertical cabinet, horizontal cabinet, vertical
wall-hung cabinet, vertical recessed, and vertical slope-top units.

Leveling Feet
Refrigerator type screw-in bolts to level the unit are available on vertical units.

Quad Grille Outlet
Quad grilles are square multi-directional grilles that allow four different discharge directions by
rotating the grilles 90°. The quad grille is constructed of a black plastic material (NORYL-SE 1-731)
with a 15° angle on the discharge louvers. Quad grilles are available on all cabinet style units.

Bar Grille Inlet/Outlet
Bar grilles are formed steel grille options available on the discharge of all units and the return of
vertical cabinet and vertical slope tops. The grilles have a black paint finish with 18-gage steel
construction. The louvers are formed at a 15° angle. The bar grilles are fixed in one discharge
direction.

Sub-bases
Sub-bases elevate vertical cabinet or slope top cabinet units to a specified height; for example, to
reach the bottom of a window sill. The sub-base also provides a cavity through which to run piping
underneath the unit. Sub-bases are 16-gage steel construction and have the same black paint finish

64

CAB-PRC001-EN

CAB-PRC001-EN.book Page 65 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

as the unit’s base. The sub-base is available in heights between 2”–7” (5 cm–18 cm) in 1/2” (1 cm)
increments. The sub-base depth and width is identical to the unit’s dimensions.
Quad grille outlet

Bar grille inlet and outlet

Sub-base (shown turned on its side)

False Backs
False backs increase the depth of a vertical cabinet unit and provide a cavity through which to run
piping behind the unit. False backs are also an excellent application when installing a unit beneath
a window sill that extends out past the front of the unit.
False backs are 18-gage steel construction and have the same paint finish as the unit. The false back
is available in depths between 2”–8” in 1” increments, with height and width identical to the unit’s
dimensions.

Recessing Flanges
Recessing flanges have 18-gage steel construction and are painted the same finish as the unit.
Recessing flanges provide an aesthetic architectural border or frame around vertical and horizontal
cabinet units.

Aluminum Wall Boxes
Wall boxes have a clear anodized finish and include a single core wire mesh insect screen. The
frame is 10-gage extruded aluminum alloy 6063-T5 construction. Horizontal louvers have 16-gage
extruded aluminum alloy 6063-T5 construction.
Wall boxes ship separate for field installation. A field supplied duct or sleeve from the wall box to
the unit fresh air opening is required to provide fresh air. Wall boxes are sized to handle up to
100 percent of nominal airflow.

CAB-PRC001-EN

65

CAB-PRC001-EN.book Page 66 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

Projection Panels
Projection panels allow semi-recessing of vertical recessed units.
Panels are 16-gage steel construction, painted with a baked powder finish. They are available in
projection depths ranging from 2”–6” in 1/2” increments. There is a distance of 7/8” between the
projection panel and the front of the unit.
False back

Recessing flange

Wall box

Project panel

Piping Components
Ball Valve
Part

Material

lever

steel, zinc plated

seat

Teflon

Spec ASTM
VTFE

packing

Teflon

RTFE

stem

rod brass

B16

g-nut

hex brass

B16

ball

brass, chrome plated

B16

retainer

brass

B16

body

cast brass

B584-C84400

Working Pressure
400 psi

Manual Circuit Setter
Material
body-forged brass alloy
trim-forged brass alloy
all wetted parts brass
Temperature
250°F max
Working Pressure
300 psi

66

CAB-PRC001-EN

CAB-PRC001-EN.book Page 67 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

Auto Circuit Setter
Material
Body-Forged Brass
Flow Cartridge-Electroless Nickel and Stainless Steel
Temperature
250°F max
Working Pressure
400 psi
Pressure Drop
0.5–9.0 gpm = 2 psi ΔP
10.0–12.0 gpm = 5 psi ΔP
Ball valve

Manual circuit setter

Control Valve
Material
body-forged brass
drive shaft stem-chrome-plated brass (modulating) brass (2-position)
seat-stainless steel (modulating)
ball plug-Buna N rubber (2-postion)
plug-high temperature thermoplastic (modulating)
o-ring seals-EPDM rubber (2-position)
actuator-stainless steel base plate, aluminum cover
Temperature
200°F max
Working Pressure
300 psi
Pressure Drop (close-off ΔP)*
2-way, two-position, N.O. = 30 psig & 50 psig
2-way, two-position, N.C. = 30 psig & 50 psig
3-way, two-position, N.O. = 28 psig
3-way, two-position, N.C. = 20 psig
2-way modulating = 50 psig
3-way modulating = 50 psig

CAB-PRC001-EN

67

CAB-PRC001-EN.book Page 68 Tuesday, May 8, 2012 10:11 AM

Mechanical Specifications

Balance Fitting
Material
packing washer-11 ga. brass
o-ring-EPDM rubber
stem-rod brass
gland screw-hex brass
valve body-cast brass

Union
Material
nut-forged brass
body-copper
tail-copper

Strainer
Material
body-cast bronze (85-5-5-5)
cover-cast bronze (85-5-5-5)
screen-stainless steel (20 mesh)
gasket-Teflon
Pressure and Temperature
400 psi (2,758 kPa) at 150°F (66°C)

68

CAB-PRC001-EN

CAB-PRC001-EN.book Page 69 Tuesday, May 8, 2012 10:11 AM

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane All rights reserved
CAB-PRC001-EN 08 May 2012

We are committed to using environmentally

Supersedes CAB-PRC001-EN (11 Jan 2012)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Creator Tool                    : FrameMaker 10.0.2
Create Date                     : 2011:11:27 13:48:34-06:00
Modify Date                     : 2012:05:08 10:16:36-05:00
Metadata Date                   : 2012:05:08 10:16:36-05:00
Producer                        : Acrobat Distiller 10.1.3 (Windows)
Keywords                        : Force-Flo; cabinet heater; FF
Acces flag                      : F
Bw color                        : B
Date published                  : 01/12/2012
Dept id                         : 28
Topic focused id                : TRANE|EN
Price                           : 0
Cur flag                        : T
Lit class id                    : PL
Lit length                      : 66
Lit order nbr                   : CAB-PRC001-EN
Lit type id                     : PRC
Media id                        : PPI
Model                           : FFA
Prod class                      : TD
Prod family id                  : 2000411
Prod                            : CAB
Topic related id                : TRN-FLD|SYS-DSN|RRR|OWN/DEV|DSGN|CONCPT|ARCH
Restrct flag                    : F
Source date                     : nulldate
Stocking loc id                 : LAXCPY
Supceded by date                : nulldate
Unit flag                       : T
Branding                        : Trane
Lol language                    : EN
Object id                       : 090102b182a9d5f1
Object name                     : CAB-PRC001-EN_11282011
Chronicle id                    : 090102b1800794fc
Filename                        : 82a9d5f1.pdf
Abstract                        :  Trane has redesigned the traditional cabinet heater to lead the industry in  indoor air quality (IAQ) features, easy installation and maintenance, high quality and durability, advanced controls
Hist model                      : FFB|FFC|FFD|FFE|FFH|FFJ|FFM|FFN|FFA|FFAB|FFBB|FFCB|FFDB|FFEB|FFHB|FFJB|FFMB|FFNB
Startup Profile                 : Print
Marked                          : True
Format                          : application/pdf
Title                           : CAB-PRC001-EN (08 May 2012): Force-Flo Cabinet Heater Air Terminal Devices Horizontal and Vertical Sizes 02-12 / Product Catalog
Creator                         : Gayle C. Edlin, Senior Technical Writer - TCS Literature
Rights                          : © 2012 Trane  All rights reserved.
Description                     : Product Catalog for the Force-Flo Cabinet Heater
Subject                         : Force-Flo, cabinet heater, FF
Document ID                     : uuid:92d420f5-c6e4-4e0d-b01d-dcddd3bcdbc0
Instance ID                     : uuid:fcab5726-525b-4671-8a47-a4530781961b
Page Mode                       : UseOutlines
Page Count                      : 69
Author                          : Gayle C. Edlin
Acces Flag                      : F
Bw Color                        : B
Chronicle Id                    : 090102b1800794fc
Cur Flag                        : T
Date Published                  : 01/12/2012
Dept Id                         : 28
Hist Model                      : FFB|FFC|FFD|FFE|FFH|FFJ|FFM|FFN|FFA|FFAB|FFBB|FFCB|FFDB|FFEB|FFHB|FFJB|FFMB|FFNB
Lit Class Id                    : PL
Lit Length                      : 66
Lit Order Nbr                   : CAB-PRC001-EN
Lit Type Id                     : PRC
Lol Language                    : EN
Media Id                        : PPI
Object Id                       : 090102b182a9d5f1
Object Name                     : CAB-PRC001-EN_11282011
Prod Class                      : TD
Prod Family Id                  : 2000411
Restrct Flag                    : F
Source Date                     : nulldate
Stocking Loc Id                 : LAXCPY
Supceded By Date                : nulldate
Topic Focused Id                : TRANE|EN
Topic Related Id                : TRN-FLD|SYS-DSN|RRR|OWN/DEV|DSGN|CONCPT|ARCH
Unit Flag                       : T
EXIF Metadata provided by EXIF.tools

Navigation menu