Trane Vertical Stack Fan Coil Catalogue

2015-04-02

: Trane Trane-Vertical-Stack-Fan-Coil-Catalogue-684304 trane-vertical-stack-fan-coil-catalogue-684304 trane pdf

Open the PDF directly: View PDF PDF.
Page Count: 40

DownloadTrane Trane-Vertical-Stack-Fan-Coil-Catalogue-  Trane-vertical-stack-fan-coil-catalogue
Open PDF In BrowserView PDF
UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 1 Wednesday, July 17, 2013 9:37 AM

Catalog

Vertical Stack Fan Coil Units
Model RSG
3/4 through 4 ton capacity

July 2013

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 2 Wednesday, July 17, 2013 9:37 AM

Vertical Stack Fan Coil Units
Trane vertical stack fan coil units are used in high-rise hotels, condominiums, dormitories, military
barracks, and residential buildings. Trane specializes in flexible response to customers’ needs.
We work closely with engineers at the design stage to ensure optimum use of the units within the
HVAC system.
Figure 1.

Fan coil - Model RSG

Figure 2.

Furred-in fan coil

18 ga. galvanized cabinet with acoustical liner
Direct-drive centrifugal fan - PSC fan motor
with sealed bearings standard
Piping package factory installed (HW preheat)

8

CW/HW coils - 2-pipe or 4-pipe

1

Drain pan - galvanized, positively sloped to
outlet - standard

7

Optional electric heater (behind panel)
Optional electrical box for unit-mounted
thermostat
Supply air opening (multiple openings
available)

6
2

Also available but not shown:

3
4

•

Risers

•

Double deflection supply air grille/
registers

•

Return air panel

•

Filter

•

Fan shield/motor cover

5

Grille and return air panel
standard color is white.

2

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 3 Wednesday, July 17, 2013 9:37 AM

Table of Contents
Vertical Stack Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Raised Base Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supply Air Grille/Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Components and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fans Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Tracer ZN521 Zone Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Tracer UC400 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Vertical Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-Pipe Chilled Water Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-Pipe Chilled Water Cooling Unit with Electric Heat . . . . . . . . . . . . . . . .
4-Pipe Chilled Water Cooling and Hot Water Heating Unit . . . . . . . . . . .
Fan Coil Units Without Risers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22
24
26
28

Riser Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Raised Base Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Raised Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Raised Base with Condensate Pump and Front Access Panel . . . . . . . . . 32

Return Air Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Return Air Panel with Flush Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Return Air Panel with Framed Out Drywall with Hinged Filter Access . . 34

Fan Coil Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNT-PRC019-EN

36
36
36
36
36
36
3

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 4 Wednesday, July 17, 2013 9:37 AM

Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Return Air Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply Air Grilles and Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Raised Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

36
37
37
37
38
38
38

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 5 Wednesday, July 17, 2013 9:37 AM

Model Number Description
The following is a complete description of
the vertical stack fan coil model number.
Each digit in the model number has a
corresponding code that identifies
specific unit options. Example of model
number:
RS-GF05-86MKX-WWX-R1PDABCDEFGA

Digits 1, 2 – Finished Goods
Identifier
Must always be “RS”

Digit 3 – Spacer
Digits 4, 5 – Unique Part
Identifier - Reserved
Must always be “GF”
Digits 6, 7 – Cabinet Footprint
05 = 17-in. x 17-in. Cabinet footprint (350
and 450 CFM models)
08 = 20-in. x 20-in. Cabinet footprint (600
and 800 CFM models)
12 = 20-in. x 24-in. Cabinet footprint (1000
and 1200 CFM models)

Digit 8 – Spacer
Digits 9, 10 – Unique Part
Identifier - Reserved
Must always be digits “86”

Digits 11, 12, 13 – Unique Part
Identifier – Reserved
Must always be entered as “MKX”

Digit 14 – Spacer
Digit 15 – Primary Cooling Means
C = Chilled Water (Single Purpose Coil)
W = Chilled Water (2-pipe Changeover
Coil - requires a change-over sensor)
X = No Cooling Coil

Digit 16 – Primary Heating Means
H = Hot Water (Single Purpose Coil)
W = Hot Water (2-pipe Changeover Coil)
E = Electric Resistance
X = No Heating Coil

Digit 17 – Auxiliary Heating
Means
E = Electric Resistance (requires
additional change-over sensor)
X = No Heating Coil

Digit 18 – Spacer
Digit 19 – Cabinet Nominal CFM
E = 350
G = 450
K = 600
M = 800
P = 1000
R = 1200

UNT-PRC019-EN

Digit 20 – Unit Connection
Voltage

Digit 24 – Hot Water Piping
Packages

1 = 120/1/60
2 = 208/1/60
3 = 240/1/60
4 = 277/1/60

Note: Manual air vent, drain cock,
flexible braided hoses and unions
on supply and return are standard
features. Control valves are
mounted on coil return.
A = 2-way control valve, shutoff valves on
supply and return
B = 3-way control valve, shutoff valves on
supply and return
C = 2-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
D = 3-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
E = 2-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
F = 3-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
G = 2-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
H = 3-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return

Digit 21 – Motor Type
P = PSC
D = ECM (Discrete speed)
V = ECM (Variable Speed)

Digit 22 – Water Coil and Fins
Per Inch (FPI)
Note: X/Y format, where X = Number of
Cooling rows and Y = Number of
Heating rows. Function (cooling
only, changeover, etc) is handled
in positions 15 and 16 of the model
number.
3 row coils
K = 3/0 (2-pipe), 12 FPI
L = 3/1 (4-pipe), 12 FPI
M = 3/2 (4-pipe), 12 FPI
N = 3/0 (2-pipe), 14 FPI
P = 3/1 (4-pipe), 14 FPI
Q = 3/2 (4-pipe), 14 FPI
4-row coils
U = 4/0 (2-pipe), 12 FPI
V = 4/1 (4-pipe), 12 FPI
W = 4/2 (2-pipe), 12 FPI
X = 4/0 (2-pipe), 14 FPI
Y = 4/1 (4-pipe), 14 FPI
Z = 4/2 (4-pipe), 14 FPI

Digit 23 – Chilled Water Piping
Packages
Note: Manual air vent, drain cock,
flexible braided hoses and unions
on supply and return are standard
features. Control valves are
mounted on coil return.
A = 2-way control valve, shutoff valves on
supply and return
B = 3-way control valve, shutoff valves on
supply and return
C = 2-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
D = 3-way control valve, shutoff valve on
supply, manual balancing valve with
shutoff on return.
E = 2-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
F = 3-way control valve, combo strainer/
shutoff valve on supply, manual
balancing valve with shutoff on return
G = 2-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return
H = 3-way control valve, combo strainer/
shutoff valve on supply, automatic
balancing valve with shutoff on return

Digit 25 – Electric Heat
Note: Must operate at supply voltage,
subject to cabinet size and airflow.
0 = No Electric Heating Coil
A = 0.75 kW
B = 1.0 kW
C = 1.5 kW
D = 2.0 kW
E = 2.5 kW
F = 3.0 kW
G = 3.5 kW
H = 4.0 kW
J = 4.5 kW
K = 5.0 kW
M = 6.0 KW
P = 7.0 KW
R = 8.0 KW

Digit 26 – Control Type
(Provided and installed by factory unless
otherwise noted)
0 = Low-voltage control by Others,
Installed by Others, Terminal Strip
provided.
A = Auto Changeover, NonProgrammable, Fan Speed Switch
B = Auto Changeover, Programmable, Fan
Speed Switch
C = Auto Changeover, NonProgrammable, No Fan Speed Switch
D = Auto Changeover, Programmable, No
Fan Speed Switch
E = Manual Changeover, NonProgrammable, Fan Speed Switch
F = Manual Changeover, Programmable,
Fan Speed Switch
5

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 6 Wednesday, July 17, 2013 9:37 AM

Model Number Description

G = Manual Changeover, NonProgrammable, No Fan Speed Switch
H = Manual Changeover, Programmable,
No Fan Speed Switch
1 = Tracer™ ZN521 (zone sensor ordered
separately)
2 = Tracer™ UC400 (zone sensor ordered
separately)

Digit 27 – Actuator Operation
(Provided and installed by factory unless
otherwise noted)
0 = None, Low Voltage, installed by
others, outside of unit
C = Control Contractor Supplied, Low
Voltage, installed by factory
L = Line Voltage, 2-position
B = 24 V 2-position (normally closed
spring return)
F = 3-Wire Floating Point
M = 0-10 or 2-10 V Modulating

Riser Package

Raised Base Package

Digit 1, 2, 3 – Riser Package
Must always be “YRP”

Digit 1, 2, 3, 4 – Raised Base
Package

Digit 4 – Configuration

Must always be “YRBP”

A = 2-pipe system
S = 4-pipe system

Digit 5 – Spacer

Digit 5 – Spacer
Digit 6 – Riser Type
1 = Single
2 = Master

Digit 7 – Copper Pipe Type
1 = All risers - type “M”
2 = All risers - type “L”
3 = Supply, Return - type “L”, Condensate type “M”
4 = Supply, Return - type “M”, No
Condensate

Digit 28 – Cabinet Type/
Thermostat Location/Insulation

Digit 8, 9, 10 – Riser Insulation
Type*

1 = Flush Mounted RA panel, remote
mounted thermostat (Fiberglass
insulation)
2 = Flush Mounted RA panel unit
mounted thermostat (Fiberglass
insulation)
3 = Hinge Mounted RA panel, remote
mounted thermostat (Fiberglass
insulation)
4 = Hinge Mounted RA panel unit
mounted thermostat (Fiberglass
insulation)
5 = Flush Mounted RA panel, remote
mounted thermostat (Closed Cell
Insulation)
6 = Flush Mounted RA panel unit
mounted thermostat (Closed Cell
Insulation)
7 = Hinge Mounted RA panel, remote
mounted thermostat (Closed Cell
Insulation)
8 = Hinge Mounted RA panel unit
mounted thermostat (Closed Cell
Insulation)

0 = None
1 = Closed cell polyolefin
2 = Closed cell elastomeric
4 = Fiberglass
X = n/a

Digit 29 – Drain Pan
0 = None (Heating Only Unit)
1 = Acrylic coated galvanized steel double
sloped drain pan
2 = Acrylic coated galvanized steel double
sloped drain pan CW float switch
3 = Stainless Steel double sloped drain
pan
4 = Stainless Steel double sloped drain
pan CW float switch

Digit 11 – Spacer
Digit 12, 13, 14 – Riser Insulation
Thickness*
0 = None
2 = 1/2 inch
4 = 1 inch
X = n/a
Note: *For a 2-pipe system:
First character: Use to describe the
cooling supply and return (or
heating supply and return)
Second character: Enter “X”
Third character: use to describe
condensate

Digit 6 – Unit Foot Print
1 = 350/450 (17 in. x 17 in.)
2 = 600/800 (20 in. x 20 in.)
3 = 1000/1200 (24 in. x 20 in.)

Digit 7, 8 – Raised Base Height
04 = 4 inches
08 = 8 inches
12 = 12 inches

Digit 9 – Access Panel**
0 = None
1 = Yes, front

Digit 10 – Condensate Pump*
(Voltages are connection
voltages)
0 = No pump
1 = 120V
2 = 208V
3 = 240V
4 = 277V (c/w Transformer)
Note: Raised base is not insulated.
Optional access panel only
available on the front side.
Note: *If condensate pump is required,
raised base with condensate
pump must be factory installed.
Electrical connections to the pump
are by Trane.
Note: **Access panel is only available
with a 12-inch raised base.

Note: *For a 4-pipe system:
First character: Use to describe
cooling supply and return.
Second character: Use to describe
heating supply and return.
Third character: Use to describe
condensate.

Digit 30 – Design Sequence
Current design sequence is “A”

6

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 7 Wednesday, July 17, 2013 9:37 AM

Model Number Description

Supply Air Grille/
Registers
Digit 1, 2, 3 – Grille Supply
GSS = Grille Supply Steel
GSR = Grille Supply Steel with Register
GSA = Grille Supply Aluminum
GSB = Grille Supply Aluminum with
Register

Table 1.

Return Air Grille Part
Numbers

Return Air Panel Type

Standard White
Size 350/450/600/800
Size 1000/1200

Flush Mounted
Hinge Mounted

FSM 0145XA
GRS 14152W

Flush Mounted
Hinge Mounted

FSM 0145XAC
GRS 14152C

FSM 0145XB
GRS 16154W

Custom Color
FSM 0145XBC
GRS 16154C

Digit 4 – Spacer
Digit 5, 6 – Width**
XX = Round inches

Digit 7 – Type
0= Double deflection, horizontal front
blades with mounting clips
1 = Double deflection, horizontal front
blades with mounting holes

Digit 8, 9 – Height**
XX = round inches

Digit 10 – Color/Finish

Table 2.

Register/Grille Quick
Reference

Nominal
Size
14 x 5
14 x 8
14 x 10
14 x 12
14 x 14
16 x 12
16 x 14

Clips
Grilles
GSS
GSS
GSS
GSS
GSS
GSS
GSS

14005W
14008W
14010W
14012W
14014W
16012W
16014W

Screw Holes
Grilles
Registers

Registers
GSR
GSR
GSR
GSR
GSR
GSR
GSR

14005W
14008W
14010W
14012W
14014W
16012W
16014W

GSS
GSS
GSS
GSS
GSS
GSS
GSS

14105W
14108W
14110W
14112W
14114W
16112W
16114W

GSR
GSR
GSR
GSR
GSR
GSR
GSR

W = Nailorhart White
C = Custom color

Note: For custom color grille, replace “W” with “C” at the end of the part number.
Registers and grilles are only available in the sizes listed in this table.

Note: * Mounting holes are on front
flange of supply grille.

Filters

Note: ** Dimensions given for nominal
frame size. These correspond to
the nominal unit opening.

Table 3.

Filter Part Numbers

Filter Type
Pleated - MERV 13
Pleated - MERV 10
Throwaway Wire Frame - for Units with
Hinged Access Panel
Throwaway Cardboard Frame - for Units
with Flush Mounted Access Panel
Note: All filters are 1-inch thick.

UNT-PRC019-EN

14105W
14108W
14110W
14112W
14114W
16112W
16114W

Filter Part Numbers
Size 350/450/600/800
Size 1000/1200
14 x 25 nominal size
16 x 25 nominal size
FPH 14125
FPY 14125

FPH 16125
FPY 16125

FWX 14125A

FWX 16125

FRX 14125

FRX 16125

7

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 8 Wednesday, July 17, 2013 9:37 AM

Performance Data
Cooling Capacities
AHRI-certified cooling performance is based on ANSI/AHRI Standard 440-2008: Performance
Rating of Room Fan-Coils: 80/67°F entering air temperature, 45°F entering chilled water
temperature with a 10°F delta T. All performance measured on high speed tap using a 120 V AC
motor, 0.05 inches ESP without filters or grilles.
Table 4.
Size

350
450
600
800
1000
1200

AHRI-certified ratings for cooling capacities
Coil

Airflow
(cfm)

3HC

300

Cooling

8.5

Power Input (W)
Water Flow
(GPM)

WPD
(ft H2O)

PSC

5.3

2.3

5.2

132
132

Total Capacity Sensible Capacity
(MBh)
(MBh)

4HC

300

9.2

5.6

2.4

5.3

3HC

470

11.8

7.7

3.1

10.0

175

4HC

470

12.9

8.3

3.4

7.5

175
259

3HC

620

19.8

12.6

4.7

18.6

4HC

620

22.4

13.7

5.3

19.1

259

3HC

700

21.6

13.8

5.1

19.7

290

4HC

700

24.6

15.1

5.8

17.9

290
446

3HC

1010

31.6

20.0

7.4

18.9

4HC

1010

36.3

22.1

8.5

16.5

446

3HC

1140

34.3

22.1

8.0

20.4

621

4HC

1140

39.7

24.4

9.3

18.9

621

Note: EC motor also available.

8

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 9 Wednesday, July 17, 2013 9:37 AM

Performance Data

Heating Capacities
Heating performance is based on 70°F entering air temperature, and listed entering water
temperatures. All performance data measured on high speed tap using a 120 V AC motor, 0.05
inches ESP without filters and grilles. 1-row and 2-row coils are in the preheat configuration as part
of a 4-pipe system. 3-row and 4-row coils are only available as part of a 2-pipe system.
Table 5.

Heating capacities
Entering Water Temp. 160°F

Rows
Size Heating

1-row
Preheat
350
2-row
Preheat
1-row
Preheat
450
2-row
Preheat
1-row
Preheat
600
2-row
Preheat
1-row
Preheat
800
2-row
Preheat
1-row
Preheat
1000
2-row
Preheat
1-row
Preheat
1200
2-row
Preheat

Total
Capacity WPD
(MBh) (ft H20)

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

0.5 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

1.0 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

2.0 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

3.0 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

4.0 GPM

LWT
(°F)

5.0 GPM

10.2

0.5

118

13.1

1.8

133

15.3

6.7

144

16.2

14.5

149

-

-

-

-

-

-

12.5

0.2

109

17.2

0.7

125

20.8

2.6

139

22.3

5.7

145

-

-

-

-

-

-

11.5

0.5

113

15.6

1.8

128

19.0

6.7

141

20.4

14.5

146

-

-

-

-

-

-

14.1

0.2

102

20.6

0.7

118

26.6

2.6

133

29.3

5.7

140

-

-

-

-

-

-

-

-

-

19.5

0.6

120

25.2

2.3

134

27.9

5.1

141

29.5

8.8

145

-

-

-

-

-

-

26.6

0.9

106

35.9

3.3

123

40.3

7.1

133

42.8

12.2

138

-

-

-

-

-

-

20.2

0.6

119

26.4

2.3

133

29.4

5.1

140

31.2

8.8

144

32.4

13.6

147

-

-

-

27.5

0.9

104

38.0

3.3

121

43.0

7.1

131

45.9

12.2

137

-

-

-

-

-

-

24.5

0.4

110

33.6

1.6

126

38.3

3.4

134

41.1

5.8

139

43.0

8.8

142

-

-

-

32.0

0.8

95

47.2

2.7

112

55.3

5.7

122

60.2

9.7

129

63.5

14.7

134

-

-

-

25.3

0.4

108

35.3

1.6

124

40.5

3.4

132

43.7

5.8

138

45.8

8.8

141

-

-

-

33.0

0.8

93

49.6

2.7

109

58.9

5.7

120

64.6

9.7

127

68.5

14.7

132

Entering Water Temp. 140°F

Size
350

450

600

800

1000

1200

Rows
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating
3-row
Heating
4-row
Heating

Total
Capacity WPD
(MBh) (ft H20)

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

0.5 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

1.0 GPM

Total
Capacity WPD
(MBh) (ft H20)

2.0 GPM

10.5

0.2

97

14.7

0.9

110

18.0

11.9

0.1

92

16.1

0.5

107

11.7

0.2

93

17.6

0.9

104

13.2

0.1

86

19.2

0.5

101

UNT-PRC019-EN

LWT
(°F)

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

3.0 GPM

LWT
(°F)

Total
Capacity WPD
(MBh) (ft H20)

4.0 GPM

LWT
(°F)

5.0 GPM

3.3

122

19.3

7.2

127

-

-

-

-

-

-

19.7

2.0

120

20.9

4.5

126

-

-

-

-

-

-

23.3

3.3

116

25.9

7.2

122

-

-

-

-

-

-

25.7

2.0

114

28.6

4.5

121

-

-

-

-

-

-

-

-

-

22.9

0.6

93

31.8

2.2

108

36.0

4.7

116

38.2

8.2

121

-

-

-

-

-

-

24.5

0.4

90

34.7

1.7

105

39.3

3.8

113

41.6

6.6

119

-

-

-

-

-

-

23.7

0.6

92

33.7

2.2

106

38.5

4.7

114

41.3

8.2

119

43.0

12.6

123

-

-

-

25.3

0.4

89

36.7

1.7

103

42.2

3.8

111

45.1

6.6

117

46.9

10.2

121

-

-

-

27.0

0.4

85

41.5

1.4

98

49.4

3.0

107

54.3

5.1

112

57.4

7.7

117

-

-

-

28.4

0.2

82

44.9

0.9

94

54.2

1.9

103

59.7

3.3

110

63.1

5.1

114

-

-

-

27.7

0.4

84

43.6

1.4

96

52.7

3.0

104

58.4

5.1

110

62.3

7.8

115

-

-

-

29.0

0.2

81

47.2

0.9

92

57.7

2.0

101

64.4

3.3

107

68.7

5.1

112

9

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 10 Wednesday, July 17, 2013 9:37 AM

Performance Data

Sound Data
Table 6.

Sound data for vertical stack fan coils
Unit Size
350

450

600

800

1000

1200

CFM

Fan Speed

Sound Pressure Level dBA

325

High

31

275

Medium

29

225

Low

28

500

High

37

425

Medium

34

325

Low

31

650

High

39

500

Medium

37

425

Low

35

725

High

41

600

Medium

39

500

Low

37

1050

High

45

950

Medium

43

800

Low

41

1175

High

50

1100

Medium

47

1000

Low

44

Note: Sound level is measured at a distance of 8 ft. from the return air grille. Measurements are for a typical furnished and
carpeted hotel suite. CFM in the above chart is approximate. Airflow is dependent on the number of coil rows, coil fins
per inch, the amount of condensate on the fins, supply voltage, motor manufacturer, supply air configuration, filter
cleanliness and altitude.

10

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 11 Wednesday, July 17, 2013 9:37 AM

Components and Options
Electric Heat
Table 7.

Kilowatts (kW) per model
kW

Model

0.75

120V/1/60
350/450

2.0

2.5

3.0

3.5

4.0

4.5

5.0

6.0

24.0

28.8

7.0

8.0

Heater Amps
6.3

8.3

12.5

16.7

4.8

7.2

9.6

12.0

14.4

16.8

240V/1/60

4.2

6.3

8.3

10.4

12.5

14.6

277V/1/60

3.6

5.4

7.2

9.0

10.8

12.6

14.4

16.8

19.2

21.6

6.3

8.3

12.5

16.7

4.8

7.2

9.6

12.0

240V/1/60

4.2

6.3

8.3

10.4

12.5

14.6

16.7

18.8

20.8

25.0

277V/1/60

3.6

5.4

7.2

9.0

10.8

12.6

14.4

16.2

18.1

21.7

8.3

12.5

16.7

208V/1/60

120V/1/60
1000/1200

1.5

208V/1/60

120V/1/60
600/800

1.0

Volts/ph/Hz

6.3

208V/1/60

4.8

7.2

9.6

12.0

14.4

16.8

19.2

21.6

24.0

28.8

33.7

38.5

240V/1/60

4.2

6.3

8.3

10.4

12.5

14.6

16.7

18.8

20.8

25.0

29.2

33.3

277V/1/60

3.6

5.4

7.2

9.0

10.8

12.6

14.4

16.2

18.1

21.7

25.3

28.9

•

Heaters are wired for single stage operation.

•

An auto-reset high limit device is included.

•

Power connection is single point.

•

The heater is located in the reheat position relative to the cooling coil.

•

The fan coil unit does not include a fuse or fusible type disconnect. Motor sub-fusing as per
electrical code.

Amps = Watts
Volts
Air temp. rise (Delta T) = kW x 3160 = MBH x 925
CFM

CFM

S.A. = Supply Air
FLA = Full Load Amps
= S.A. fan motor Amps + Electric Heater Amps
MCA = Minimum Circuit Ampacity
= FLA x 1.25
MOP = Rating of maximum overcurrent protection device
= (2.25 x S.A. fan motor Amps) + Electric Heater Amps

UNT-PRC019-EN

11

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 12 Wednesday, July 17, 2013 9:37 AM

Components and Options

Requirements of Standards: UL 1995 and CSA C22.2 No.236

12

•

If the value of the calculated rating does not equal a standard current rating of overcurrent
protective device, the marked maximum rating shall be the next lower standard rating.

•

Exception No. 1: The marked maximum rating of the overcurrent protective device shall be the
standard rating next higher than the computed value if the next lower standard ratings is less
than 125 percent of the current rating of an electric heater load, when the unit includes an
electric heater.

•

Exception No. 2: if the computed value of the overcurrent protective device is less than the
minimum ampacity of the supply circuit, the marked rating of the device shall be increased to
the largest standard overcurrent protective device rating appropriate for the marked minimum
circuit ampacity.

•

Exception No. 3: If the marked minimum circuit ampacity does not correspond to a standard
protective device rating, the next higher standard rating of the protective device may be
marked.

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 13 Wednesday, July 17, 2013 9:37 AM

Components and Options

Fans Curves
Figure 3.

Unit size 350

External Static Pressure (in. wg.)

0.5

0.4
Low

Medium

High

0.3

0.2

6 Row
5 Row
4 Row
3 Row

0.1

0
0

100

200

300

400

500

600

Supply Air Volume (SCFM)

Figure 4.

Unit size 450

External Static Pressure (in. wg.)

0.5

0.4
Low

Medium

High

300

400

0.3

0.2

0.1

6 Row
5 Row
4 Row
3 Row

0
200

Supply Air Volume (SCFM)

UNT-PRC019-EN

13

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 14 Wednesday, July 17, 2013 9:37 AM

Components and Options

Figure 5.

Unit size 600

External Static Pressure (in. wg.)

0.5

0.4
Low

Medium

High

400

500

0.3

0.2

0.1
6 Row
5 Row
4 Row
3 Row

0
300

600

700

Supply Air Volume (SCFM)

Figure 6.

Unit size 800

External Static Pressure (in. wg.)

0.5

0.4
Low

Medium

High

0.3

0.2

0.1

6 Row
5 Row
4 Row
3 Row

0
300

400

500

600

700

800

Supply Air Volume (SCFM)

14

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 15 Wednesday, July 17, 2013 9:37 AM

Components and Options

Figure 7.

Unit size 1000

External Static Pressure (in. wg.)

0.5

0.4
Low

High

Medium

0.3

0.2

0.1

6 Row
5 Row
4 Row
3 Row

0
600

700

800

900

1000

1100

1200

Supply Air Volume (SCFM)

Figure 8.

Unit size 1200

External Static Pressure (in. wg.)

0.5

0.4
Low

High

Medium

0.3

0.2

6 Row
5 Row
4 Row
3 Row

0.1

0
800

900

1000

1100

1200

1300

Supply Air Volume (SCFM)

Fan curves are based on 120V AC PSC motor at high, medium and low fan speed settings. The
following test conditions apply:

UNT-PRC019-EN

•

Centrifugal direct drive fan with double inlet and forward curved impeller.

•

Cooling coil is dry.

•

One-inch throwaway filter is clean.
15

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 16 Wednesday, July 17, 2013 9:37 AM

Components and Options

Motor Data
Table 8.

Motor data

Size
350

450

600

800

1000

1200

Connection Voltage
Volts/ph/Hz
120V/1/60
208-240V/1/60
277V/1/60
120V/1/60
208-240V/1/60
277V/1/60
120V/1/60
208-240V/1/60
277V/1/60
120V/1/60
208-240V/1/60
277V/1/60
120V/1/60
208-240V/1/60
277V/1/60
120V/1/60
208-240V/1/60
277V/1/60

PSC
Max. Plate Ratings
HP
Amps
1/20
1/14
1/12
1/6
1/12
1/12
1/6
1/12
1/12
1/6
1/6
1/6
1/4
1/4
1/4
1/3
1/3
1/3

ECM
Max. Plate Ratings
HP
Amps

1.2
0.6
0.6
1.7
0.8
0.6
2.6
0.8
0.6
2.6
1.4
0.9
4.6
2.2
1.6
6.4
3.1
2.1

1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/2
1/2
1/2

4.8
2.8
2.6
4.8
2.8
2.6
4.8
2.8
2.6
4.8
2.8
2.6
4.8
2.8
2.6
6.8
4.1
3.6

Note: EC motors have been programmed for three (3) discrete speed operation. Variable speed also available (not shown.) Motor nameplate data is shown
in table. Fan motors are single phase and have a minimum of three speeds. Trane has several fan motor suppliers in order to ensure availability. Amp
draws may differ between motors from different manufacturers. Trane reserves the right to change motor HP and therefore amp draws without notice

Control Packages
Trane offers a range of standard thermostats and controllers for the vertical stack fan coil units. For
applications where a larger BAS is to be installed, Trane can provide factory mounting of the ZN521
or UC400 controllers.

Thermostats
Table 9.

Thermostat information

Thermostat
Voltage

Manufacturer

Model

Heat/Cool
Changeover

Fan Operation

Available Fan
Speeds

24

Honeywell

TB8575A1000

Automatic or Manual

User Selectable

3

24

Honeywell

TB7100A10001

Automatic or Manual

User Selectable

3

120/208/240

Honeywell

TB6575A1000

Automatic or Manual

User Selectable

24
24
120
208-230
277

HotelTech
HotelTech
HotelTech
HotelTech
HotelTech

LT24A
LT24A3
LT120A
LT220A
LT277A

Automatic
Automatic
Automatic
Automatic
Automatic

see
see
see
see
see

Note
Note
Note
Note
Note

2
2
2
2
2

3
2
3
2
2
2

Application
Residential or
Hospitality
Residential
Residential or
Hospitality
Hotel
Hotel
Hotel
Hotel
Hotel

1. The Honeywell TB7100A1000 is a 7-day programmable thermostat.
2. The HotelTech thermostats feature automatic fan speed switching between the available speeds and off. The thermostat selects speed based on
deviation of the room temperature from set point. The occupant can also manually select between the available speeds.

16

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 17 Wednesday, July 17, 2013 9:37 AM

Components and Options

Residential applications include: Condominiums, apartments, student residences/dormitories,
assisted living/retirement facilities, and military barracks.
Trane recommends the remote mounting of low voltage (24V) thermostats to achieve optimal zone
control. When thermostats are remote mounted, a terminal strip is provided inside the unit for field
connection to the remote thermostat. Unit mounting of thermostat is also available, however all
thermostats are shipped loose for field installation after the unit is installed, drywall is applied and
the walls are painted.
The standard standalone thermostats listed above cycle a two position (on/off) valve and feature
discrete speed fan speed operation. If modulating (0-10V DC or 3-wire floating point) valve
actuators or modulating or 0-10V DC EC motors are a requirement, a thermostat or controller with
the necessary analog outputs must be used.

Tracer ZN521 Zone Controller
The Tracer ZN521 is a factory-installed LonTalk® control board designed to provide control of the
fan-coil products (see Figure 9).
Figure 9. Tracer ZN521 controller
Features include:
• Automatic fan-speed reset
• Automatic ventilation reset
• Manual output test
• Filter maintenance
• Master slave
• Water valve override
• Freeze avoidance
• Interoperability
• Three generic I/O ports

The Tracer ZN521 controller is designed to be used in the following applications:
• As part of the Trane Tracer Summit building automation system, the Tracer ZN521 becomes an
important part of the Trane Integrated Comfort system (ICS).
• The Tracer ZN521 can function as a completely standalone controller in situations where a
building automation system (BAS) is not present.
• For situations when a non-Trane BAS is present, the Tracer ZN521 can be where ever a LonTalk
front-end system is present.
Through building management of the HVAC system, optimizing energy consumption becomes
possible at a zone level. Each unit is capable of functioning independently of one another during
occupied and unoccupied hours of the day. This allows the temperature setpoint and ventilation
setting to be changed automatically based on zone usage (see Figure 10).

UNT-PRC019-EN

17

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 18 Wednesday, July 17, 2013 9:37 AM

Components and Options

Figure 10. Tracer ZN521 System

Rover™
(optional)

Tracer
Summit®
System

Fan
coil

Fire safety
system

Lighting
system

Fan
coil

Security
system

To other
building products

To other
Trane products

Two Systems in One
In an ICS environment, the Tracer ZN521 is pre-designed to install quickly and easily into the
system. Since the controller is mounted on the unit, the start-up time for the entire system is
minimized. Trane becomes the single source of responsibility for the equipment, unit controls, and
building automation system.
Once power is applied to the controller, it will automatically start up and run based upon the
setpoint on the local zone sensor. The Tracer ZN521 is certified to the interoperable LONMARK®
Space Comfort Controller profile. This allows the controller to be used with another vendor’s BAS
and thereby still provide the high quality of factory installation. In addition, the Tracer ZN521
provides one of the most extensive interoperable data lists of any controller of its type in the
industry.

Automatic Fan and Ventilation Reset
With the Tracer ZN521 controller, a multi-speed fan control for the fan coil delivers the airflow
output customized to support the cfm space needs. When less cfm is necessary to meet the load
of the zone (typically 75 to 80 percent of the time), the equipment operates on low speed. However,
if the room temperature rises, the controller will switch to high speed.

Manual Output Test
The Tracer ZN521 controller includes a manual output test function. This function may be initiated
from the blue test push button on the controller or through the Rover™ service tool. This feature
is used to manually exercise the outputs in a defined sequence.
The purpose of this test sequence is to verify output and end device operation. The manual output
test function may also be used in the following situations:

18

•

Reset latching diagnostics

•

Verify output wiring and operation

•

Force the water valve(s) open to balance the hydronic system during installation set-up or
service.
UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 19 Wednesday, July 17, 2013 9:37 AM

Components and Options

Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller
compares the amount of fan run time against an adjustable fan run hour (stored in the controller)
to determine when maintenance is recommended for the unit. The run-hours value may be user
edited as required (through Rover). The valid range for the fan run hours limit is 0 to 5000 hours
with a default of 600 hours. Once the run hours limit has been exceeded, the controller generates
a maintenance required diagnostic (unit will not shut-down). The user will be notified of this
diagnostic through the building automation system or when a Trane Service Tool is communicating
with the controller.

Master Slave (Data Sharing)
Because the Tracer ZN521 controller utilizes LONWORKS® technology, the controller can send or
receive data (setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other
controllers on the communication link with or without the existence of a building automation
system. This applies to applications where multiple units might share one zone sensor for both
stand-alone (with communication wiring between units) and a building automation system.

Water Valve Override
The Tracer ZN521 can be commanded via the Rover service tool to open all hydronic valves
100 percent. This allows for the faster water balancing of each unit and the entire system when the
command is sent globally to all controllers. A properly balanced system is essential for proper and
efficient operation.

Hydronic Coil Freeze Protection (Freeze Avoidance)
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The
Tracer ZN521 does this from three different aspects. Any of these methods of protections will result
in the unit fan being disabled, the outside air damper being shut, and the hydronic valves being
opened 100 percent.
The three methods of freeze avoidance include:
1. A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and
if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and
the valves are fully opened.
3. When in the unoccupied mode the Tracer ZN521 has an adjustable freeze avoidance setpoint.
If the outside air temperature is below the setpoint the unit will open the valves to allow water
to flow through the coils.

Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With
this advantage, the owner can choose the best products, the best application, and the best service
from a variety of suppliers to meet their evolving building control needs in a cost effective manner.

Generic Binary Input/Output
The three generic binary inputs/outputs are not part of the normal control, but are actually
controlled through the Tracer Summit system (when present) to issue commands to the Tracer
ZN521 control to turn the generic inputs/outputs of add-on equipment (such as baseboard heating,
exhaust fans, occupancy sensor, lighting, etc.) on and off. This binary port is not affected when
other binary diagnostics interrupt unit operation.

UNT-PRC019-EN

19

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 20 Wednesday, July 17, 2013 9:37 AM

Components and Options

Tracer UC400 Controller
The Tracer UC400 is a factory-installed BACnet® MS/TP control designed to provide control of the
fan coil (see Figure 11). The Tracer UC400 controller is designed to be used in the following
applications: as stand-alone operation, part of the Trane Tracer SC building automation system, or
part of another BACnet MS/TP Building Automation System. The Tracer UC400 can function as a
completely standalone controller in situations where a building automation system (BAS) is not
present.
Figure 11. Tracer UC400 Controller
Features include:
•

Single Zone VAV

•

Automatic ventilation reset

•

Filter maintenance

•

Water valve override

•

Freeze avoidance

•

Interoperability

•

Unused I/O can be used as generic I/O

The Tracer UC400 is designed to install quickly and easily into the system. Trane becomes the single
source of responsibility for the equipment, unit controls, and building automation system. As a
standalone controller, the Tracer UC400 is ideally suited for fix-on-fail replacement of units with old
pneumatic controllers, or in situations where a BAS will be added at a later date. Once power is
applied to the controller, it will automatically start up and run based upon the setpoint on the local
zone sensor. An individual time clock can be added to the unit for local scheduling. The Tracer
UC400 is BTL listed as B-ASC profile. This ensures the controller to be used with other BACnet®
building automation systems.
The Tracer UC400 controller delivers single zone VAV control and can be used in a stand-alone
application or as part of a Trane Integrated Comfort™ System (ICS).
In the stand-alone configuration, Tracer UC400 receives operation commands from the zone sensor
and/or the auto changeover sensor (on auto changeover units). The entering water temperature is
read from the auto changeover sensor and determines if the unit is capable of cooling or heating.
The zone sensor module is capable of transmitting the following information to the controller:
•

Timed override on/cancel request

•

Zone setpoint

•

Current zone temperature

•

Fan mode selection (off-auto-high-med-low)

For optimal system performance, fan coils can operate as part of an ICS building automation
system controlled by Tracer Summit. The controller is linked directly to the Summit control panel
via a twisted pair communication wire, requiring no additional interface device (i.e., a command
unit). The Trane ICS system can monitor or override Tracer UC400 control points. This includes such
points as temperature and output positions.

20

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 21 Wednesday, July 17, 2013 9:37 AM

Components and Options

Single Zone VAV with Fully Modulating Fan Speed
With a single zone VAV with fully modulating fan speed, and EDM with modulating signal is
required. The Tracer UC400 will minimize fan speed, and in turn energy usage, by only delivering
the air flow needed. See Figure 12.

Fan speed command (%)

Discharge temp setpoint (°F)

Figure 12. Cool mode nominal hydronic cooling control

Filter Maintenance
Filter status for the controller is based on the cumulative run hours of the unit fan. The controller
compares the amount of fan run time against an adjustable fan run hour (stored in the controller)
to determine when maintenance is recommended for the unit. The run-hours value may be user
edited as required. The valid range for the fan run hours limit is 0 to 5000 hours with a default of
600 hours. Once the run hours limit has been exceeded, the controller generates a maintenance
required diagnostic (unit will not shut-down). The user will be notified of this diagnostic through
the building automation system or when a Trane® service tool is communicating with the
controller.

Hydronic Coil Freeze Protection (Freeze Avoidance)
Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The
controller does this from three different aspects. Any of these methods of protections will result
in the unit fan being disabled, the outside air damper being shut, and the hydronic valves being
opened 100 percent.
The three methods of freeze avoidance include:
1. A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic
if the coil temperature falls below 35°F.
2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and
if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and
the valves are fully opened.
3. When in the unoccupied mode, the controller has an adjustable freeze avoidance setpoint. If the
outside air temperature is below the setpoint, the unit will open the valves to allow water to flow
through the coils.

Interoperability
Interoperability allows the owner freedom to select multiple vendors, and multiple products. With
this advantage, the owner can choose the best products, the best application, and the best service
from a variety of suppliers to meet their evolving building control needs in a cost effective manner.

UNT-PRC019-EN

21

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 22 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights
Vertical Fan Coil Units
2-Pipe Chilled Water Cooling Unit
Figure 13. 2-pipe chilled water cooling unit - hot water changeover coil optional

16

C
B
TOP VIEW

1 1/2 in.

1/2 in.

2 1/8 in.

D
6

6

1

13
4 in.
10
14
15

86 in. 2
7
11

E
8
47 in.

3

9
36 in.

9

4
5

12

6 in.

F.F.L.

A
SIDE SECTION
(Flush Mounted Panel Option)

22

SIDE VIEW
(Hinged Panel Option)

FRONT VIEW

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 23 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 10. 2-pipe chilled water cooling unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.

1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.

Direct-drive centrifugal fan and PSC motor; EC motor
optional.

7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.

Chilled water coil; hot water changeover optional.

Hinged return air grille/access panel (optional).

Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.

2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.
Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
Top supply air opening (knock out) for attachment of
ductwork.

Flush mounted return air grille/access panel
attached by quarter turn fasteners.
One inch disposable filter.

Table 11. 2-pipe chilled water cooling unit dimensions (inches)

UNT-PRC019-EN

Size

A

B

C

E

350
450
600
800
1000
1200

17
17
20
20
20
20

17
17
20
20
24
24

14
14
14
14
16
16

52
52
52
52
54
54

23

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 24 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

2-Pipe Chilled Water Cooling Unit with Electric Heat
Figure 14. 2-pipe chilled water cooling unit with electric heat

17

C
B
1 1/2 in.

TOP VIEW

2 1/8 in.

1/2 in.
D

7

7
1
4 in.

14
2

11
15

86 in.

16

3
8
12

E
9
9

47 in.

4

36 in.
10

5
6

13

6 in.

F.F.L.

A
SIDE SECTION
(Flush Mounted Panel Option)

24

SIDE SECTION
(Hinged Panel Option)

FRONT VIEW

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 25 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 12. 2-pipe chilled water cooling unit with electric heat callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.

1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.

Electric heater (primary or auxiliary).

7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.

Direct-drive centrifugal fan and PSC motor; EC motor
optional.

Hinged return air grille/access panel (optional).

Chilled water coil; hot water changeover optional.

2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.

Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel
attached by quarter turn fasteners.

Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
Top supply air opening (knock out) for attachment of
ductwork.

One inch disposable filter.

Table 13. 2-pipe chilled water cooling unit with electric heat dimensions (inches)

UNT-PRC019-EN

Size

A

B

C

E

350
450
600
800
1000
1200

17
17
20
20
20
20

17
17
20
20
24
24

14
14
14
14
16
16

52
52
52
52
54
54

25

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 26 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

4-Pipe Chilled Water Cooling and Hot Water Heating Unit
Figure 15. 4-pipe chilled water cooling and hot water heating unit

17

C
B
1 1/2 in.

TOP VIEW

2 1/8 in.

1/2 in.
D
7

7

4 in.

1

14
11
15

86 in.

16

2
8
12

E

3

9
9

47 in.
4

36 in.
10

5
6

13

6 in.

F.F.L.

A
SIDE SECTION
(Flush Mounted Panel Option)

26

SIDE SECTION
(Hinged Panel Option)

FRONT VIEW

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 27 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 14. 4-pipe chilled water cooling hot water heating unit callouts
18 ga. steel cabinet, lined with 1/2-inch fiberglass
insulation coated on air side; 3/8-inch closed-cell
foam optional.

1/2-inch flange on front of unit. Allows direct
application of drywall to the unit.

Direct-drive centrifugal fan and PSC motor; EC motor
optional.

7/8-inch hole on each side of cabinet for power and
control cable entry points on all units. See CLCHSVX021A-EN installation manual for details.

Chilled water coil.

Hinged return air grille/access panel (optional).

Hot water coil.

2 1/8-inch flange on front of unit. Drywall to be
framed out in front of unit.

Acrylic coated galvanized steel drain pan, pitched in
two directions, insulated on the underside; stainless
steel optional.
Drain hose from drain pan to condensate riser. The
flexible hose forms a running trap.
Double deflection steel supply air grille at front, left,
right or back or any combination when there are
multiple openings. Dimension “D” varies with CFM:
5, 8, 10, 12, or 14 inches.
Flush mounted return air grille/access panel
attached by quarter turn fasteners.

Unit mounting location for thermostat/controller.
Fan shield, acoustically lined. Identification and
safety caution labels are affixed to this panel.
Vertical centerline of coil connection run outs.
Connections are at the back, left or right sides of the
unit.
Top supply air opening (knock out) for attachment of
ductwork.

One inch disposable filter.

Table 15. 4-pipe chilled water cooling and hot water heating unit dimensions (inches)

UNT-PRC019-EN

Size

A

B

C

E

350
450
600
800
1000
1200

17
17
20
20
20
20

17
17
20
20
24
24

14
14
14
14
16
16

52
52
52
52
54
54

27

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 28 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Fan Coil Units Without Risers
Figure 16. Fan Coil Units Without Risers

BK

BK

5
6
1 1/2 in.

5 1/4 in.
3 3/4 in.

3 3/4 in.

7"

Supply and return
connections
1/2 in. or 3/4 in. nom.
Copper pipe

CWR
CWS

HWS
HWR

86 in.

36 in.

1
R

2

3

S

Condensate
connection
5/8 in. I.D. hose

4
Inside
unit

Outside
unit

Stub-out detail - typical

C

C
2 5/8 in.

4-pipe slave unit
with BK connection

2-pipe slave unit
with BK connection

Table 16. Fan coil units without risers - 2-pipe and 4-pipe slave units callouts
1/2-inch or 3/4-inch supply and return coil branch copper pipe
Union fitting
Ball valve (shut-off valve)
1/2-inch or 3/4-inch copper tail piece soldered into valve body at factory
Insulation lining on interior surface of fan coil cabinet
Fan coil cabinet

28

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 29 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Riser Packages
Figure 17.

Riser 2-Pipe Package

RC S
3 1/2 in. 3 1/2 in.

R
C
S

RA

TOP VIEW

RA

RA

RCS
Right risers (RT)

Back risers (BK)

Left risers (LT)
CL

SC R
S = Supply riser
R = Return riser
C = Condensate riser

S
C
R

RA

TOP VIEW

RA

RA

SCR
Reverse left risers (RL)

Reverse right risers (RR)

Reverse back risers (RB)

2 5/8 in. 2 5/8 in.
3 3/4 in.
3 3/4 in.
RA
HWS
HWR
Cond.
CWR
CWS

Back risers (BK)

Left risers (LT)

CL

TOP VIEW

RA

Right risers (RT)

CWS
CWR
Cond.
HWR
HWS

RA

CWS
CWR
Cond.
HWR
HWS

HWS = Hot Water Supply Riser
HWR = Hot Water Return Riser
CWS = Chilled Water Supply Riser
CWR = Chilled Water Return Riser
Reverse left risers (RL)
Cond. = Condensate Riser

RA

CWS
CWR
Cond.
HWR
HWS

TOP VIEW

HWS
HWR
Cond.
CWR
CWS

HWS
HWR
Cond.
CWR
CWS

Figure 18. Riser 4-Pipe Package

RA

RA

Reverse right risers (RR)

Reverse back risers (RB)

Reverse Riser orientations are used to aid in eliminating cross over piping when units on a riser
stack change position from floor to floor or when two units share a common riser (Master/Slave).
TOP VIEW

TOP VIEW
Back risers (BK)

Right risers (RT)

R
C
S

R
C
S

Reverse right risers (RR)

S
C
R

S
C
R

Reverse back risers (RB)

UNT-PRC019-EN

29

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 30 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Figure 19. Riser Installation Dimensions (inches)

Standard Installation Using
Spool Pieces

Standard Installation

F

F
92 in.
92 in.

L

L

F - L + 4 in.

F
92 in.

F
L
92 in.
L

L = F + 2 inches
Spool Piece Length = F - L + 4 inches
L = F - Spool Length + 4 inches

30

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 31 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Raised Base Options
Raised Base
Figure 20. Raised base - no access panel

12 in.

12 in.

A

B

Front View

Side View

Available in 4-inch, 8-inch and 12-inch heights (shown)

Table 17. Raised base dimensions (inches)

UNT-PRC019-EN

Size

A

B

350
450
600
800
1000
1200

17
17
20
20
24
24

17
17
20
20
20
20

31

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 32 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Raised Base with Condensate Pump and Front Access Panel
Figure 21.

Raised base with condensate pump and front access panel

Front View

Side View
Drywall

1

2
6
7
3

12 in.

3

4

8
F.F.L.

5
Front View

Left Side View

Available only with 12 inch raised base.

Table 18. Raised base with condensate pump and front access panel callouts
Condensate riser (if applicable)

120V - 208V condensate pump

Drain tube factory installed

Front access panel (350 - 800 - 16 in. x 10 in.,
1000, 1200 - 18 in. x 10 in.

3/8-inch I.D. outlet tube by contractor

Screws for front access panel

12 inch raised base

Opening for condensate hose running in and out

Note: If the supply is 277V, an appropriately sized step-down transformer is included for condensate pump.

32

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 33 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Return Air Panels
Return Air Panel with Flush Mount
Figure 22. Return air panel - flush mount with quarter turn fasteners

3

10

5
4

6

7

Up arrow indicates
locked position

8

1

Top side section

2
2

9
3
10
Bottom side section

Table 19. Return air panel - flush mount with quarter turn fasteners callouts
Return air grille/access panel with quarter turn
fasteners

Pawl lock screw

Throwaway 1-inch filter.

Plastic washer

1/2-inch deep collar around return air opening on fan
coil unit

Spring retainer

1/4 turn fastener with slotted head and square shaft

Bottom hook of access panel

Pawl of the 1/4 turn fastener

1/2-inch drywall

Features

UNT-PRC019-EN

•

Drywall attached directly to front of the unit

•

Industry standard

•

Fast access with quarter turn fasteners

•

Easily removable for filter changing

33

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 34 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Return Air Panel with Framed Out Drywall with Hinged Filter Access
Figure 23. Return air panel - framed out drywall with hinged filter access

Fan coil unit

1

Front of
fan coil
unit
2-in. collar on
front of fan coil unit
Drywall stud
by others

6
2

6

3

Drywall
by others

6
Return air panel

4
5

Table 20. Return air panel with framed out drywall with hinged access filter access callouts
Hinged filter access door
Access panel retaining clip
Throwaway 1-inch filter
Grille frame
Filter channel
Sheet metal screw by contractor

Features
No exposed fasteners
Improved aesthetics
Easy filter changing - no tools required
Drywall is framed out around two-inch collar/flange

34

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 35 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Fan Coil Weights
Table 21. Weights for fan coil units
Size

Weight

350
450
600
800
1000
1200

140 lbs (63 kg)
150 lbs (68 kg)
170 lbs (77 kg)
180 lbs (82 kg)
210 lbs (95 kg)
220 lbs (100 kg)

The weights are approximate. Risers, external sheet metal accessories and supply air grilles are not
included in the weight.

UNT-PRC019-EN

35

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 36 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications
Certifications
Performance: Unit performance is certified by AHRI in accordance with ANSI/AHRI 440-2008:
Performance Rating of Room Fan-Coils.
Safety: All standard units are agency listed in the United States and Canada and comply with the
requirements of the current editions of UL 1995/CSA C22.2 No. 236.

Construction
The cabinets shall be fabricated from 18 gage steel lined with ½-inch fiberglass insulation bonded
with a thermosetting resin and coated on the airstream side with an acrylic facing. In addition, there
is an option available for 3/8-inch closed cell cabinet insulation.
The drain pan shall be an acrylic (black polyester powder) coated 20 gauge galvanized steel
positively sloped in two directions towards the outlet. The drain pan shall be insulated on the
underside with ½-inch fiberglass insulation (same as cabinet). The drain hose from the outlet to the
condensate riser shall form a running trap. An optional Stainless Steel drain pan is also available.
A drain pan float switch is also available. The float switch will close CW control valve upon detection
of high water level in condensate drain pan.

Fan
The galvanized metal fan wheels are centrifugal forward-curved and double-width. Fan wheels and
housings are corrosion resistant.

Motors
The fan motor shall be a three speed P.S.C. type with internal thermal protection and sealed
bearings. All motors have a maximum ambient operating temperature of 104°F and are
permanently lubricated.
An optional ECM type brushless fan motor is available. The motor is available, programmed at the
factory for three (3) discrete speed operation. A variable speed EC motor is also available for use
with a 2-10V DC signal.
An unfused service disconnect switch shall be included, mounted inside the unit behind the motor
cover.

Coils
The coil shall have aluminum fins mechanically bonded to ½-inch copper tube. The coil shall be
factory pressure tested at not less than 300 psig. A manual air vent shall be incorporated at the high
point, and a drain cock at the low point of the connecting pipework to the coil.

Piping Packages
The piping package shall include: Ball type shut-off valves on the coil supply and returns (combined
with balancing valves or strainers when used), and a two- or three-way control valve with twoposition actuator. Chilled water and hot water valves are normally closed.
Control valves are also available in 3 wire floating point or 2-10V DC modulating valves.
Additionally balancing valves (manual or automatic) and strainers supplied as riser system
dictates. These devices are provided as combo-valves with the shut-off on supply and return and
can be equipped with PT ports.

Electric Heat
Units with electric heat shall be wired for single-stage operation with an open wire nickel-chrome
element. An auto-reset high limit device shall be included.

36

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 37 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications

Filters
A one-inch disposable filter shall be shipped loose with the return air access panel.
Units equipped with one inch MERV 10 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with
ASHRAE 52.1 atmospheric dust spot method.
Units equipped with one inch MERV 13 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and greater
than 90 percent efficiency on 3–10 micron particles when tested in accordance with ASHRAE Test
Standard 52.2.

Controls
Thermostat (option)
The fan coil manufacturer shall supply a low voltage (24V) thermostat for remote mounting, or
optionally unit mounted. Remote mounted thermostats are connected to a terminal strip that is
mounted inside the unit. The thermostat is shipped loose for installation after the unit is installed,
dry-wall is applied and the walls are painted.
Line voltage controls for unit mounting is also available. Thermostat quick-connect plug provided;
thermostat ships loose for installation after drywall is applied and walls are painted.

Tracer ZN521 (option)
The Tracer ZN521 discrete speed controller can be used in a stand-alone application or used as part
of a Trane Integrated Comfort System (ICS) with LonTalk® communication. The Tracer ZN521 offers
the combined advantages of simple and dependable operation. Standard control features include
options normally available on more elaborate control systems. All control options are available
factory-mounted and can be field-configured using a service tool.

Tracer UC400 (option)
The Tracer UC400 controller delivers single zone VAV control in a stand-alone application or as part
of a Trane Integrated Comfort system with BACnet® communication. Standard control features
include options normally available on more elaborate control systems.

Riser Package
Risers are available in both type “L” and type “M” copper for supply, return and condensate pipes.
Riser insulation is available in ½-inch and one-inch wall thickness for closed cell foam (polyolefin),
closed cell elastomeric (similar to Armaflex®) and fiberglass (wrapped with vapor barrier).
Riser diameter and insulation thickness are subject to physical limitations. Contact Trane when
risers are larger than 2 1/2 inches in diameter. The risers shall have an approximately 2 1/2 inch
swaged expansion at the top end to allow a 2 inch insertion of the riser from above without the use
of couplings. Risers may be provided plain ended in lieu of swaged for field supplied/installed
fittings (similar to Pro-Press®).
The riser insulation shall have a flame spread rating of 25 or less and a smoke developed rating
of 50 or less in compliance with ASTM E 84. The insulation shall be continuous over the riser length
within the height of the cabinet. Provision for insulation beyond the ends of the cabinet shall be
the responsibility of the installing contractor.
The specification of riser anchoring, expansion loops and fire stopping requirements are not
detailed in this specification and are not part of the Trane fan coils scope. Trane can provide
expansion loops installed on the risers at the factory as per the engineers specification.
Hot water risers which are continuous over twelve or more floors may incorporate expansion
compensation loops within the fan coil cabinet, location and spacing of expansion joints are the
responsibility of the design engineer.

UNT-PRC019-EN

37

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 38 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications

Return Air Access Panel
The return air access panel shall have a fixed blade return air grille in the lower portion with filter
access achieved by removal of the panel. The panel installs flush on to the drywall which has been
applied directly to the front of the unit. The panel is of stamped steel construction and shall be
finished in standard white baked enamel. The panel secures to the unit by a hook on the bottom
edge and two quarter-turn fasteners in the upper corners. The panel is shipped loose for installation
after the unit is installed, dry-wall is applied and the walls are painted.
There is also a return air access panel with hinged filter access as an option. Stamped steel
construction with return air grille in lower portion of grille and hinged filter access in the top
portion. Secured to the two-inch flange on the front of the unit with sheet metal screws. Drywall
is framed out in front of the unit and is not applied directly to the unit face.

Supply Air Grilles and Registers
Supply air grilles and registers shall be provided for unit mounting locations. The grilles shall be
steel, have double deflection airfoil blades and shall be finished in standard white baked enamel.
The grilles shall attach to the collar of the fan coil unit by spring clips. When a unit has more than
one supply air opening a balancing damper (horizontal in the front) is included with the grille
(register) to balance the air flow (screw holes optional). Any supply air grilles which are part of
supply air ductwork shall be provided by the sheet metal contractor. Grilles are shipped loose for
installation after the unit is installed, dry-wall applied and the walls are painted.
A line of sight baffle with acoustical wrap shall be included in units which have left and right or front
and back supply air openings.
There is also an option to upgrade the supply air grille material to aluminum as well as the option
to provide custom colors for return air panels and supply air grilles/registers.

Raised Bases
Raised bases are available in heights of 4 inches, 8 inches or 12 inches. An access panel is available
only in the 12-inch height option. If a condensate pump is required, 12-inch high raised base with
access panel is required.

38

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 39 Wednesday, July 17, 2013 9:37 AM

Notes

Notes

UNT-PRC019-EN

39

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 40 Wednesday, July 17, 2013 9:37 AM

ETL LISTED
CONFORMS TO
UL STD 1995
CERTIFIED TO
CSA STD C22.2 NO. 236
4008161

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2013 Trane All rights reserved
UNT-PRC019-EN 15 July 2013

We are committed to using environmentally

(NEW)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Create Date                     : 2013:07:17 09:35:04Z
Creator                         : FrameMaker 10.0.2
Modify Date                     : 2013:07:17 09:35:04Z
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Title                           : untitled
Creator Tool                    : FrameMaker 10.0.2
Producer                        : Acrobat Distiller 10.1.4 (Windows)
Document ID                     : uuid:66debc4a-22d0-4578-ab88-91f6dfdb9979
Instance ID                     : uuid:bc848c6a-e99c-46bf-9b24-89b0e5278875
Page Mode                       : UseNone
Page Count                      : 40
EXIF Metadata provided by EXIF.tools

Navigation menu