Product Catalog

Packaged Rooftop Air Conditioners
Voyager™ – Heat Pump
12½ – 20 Tons – 60 Hz

June 2014

PKGP-PRC012M-EN

Introduction
Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
products available in the market today. Trane was the first to introduce the Micro—microelectronic
unit controls—and has continued to improve and revolutionize this design concept.
The ReliaTel control platform offers the same great features and functionality as the original Micro,
with additional benefits for greater application flexibility.
Voyager continues to provide the highest standards in quality and reliability, comfort, ease of
service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance
requirements, and are competitively priced. Trane delivers all of this with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel
controls, computer-aided run testing, and Integrated Comfort™ Systems.
So whether you’re the contractor, the engineer or the owner, you can be certain Voyager Products
are built to meet your needs.
It’s Hard To Stop A Trane®.

Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any person
of such revision or change.

Trademarks
Trane and the Trane logo, Frostat, Integrated Comfort, ReliaTel, Tracer, are trademarks of Trane in
the United States and other countries. All trademarks referenced in this document are the
trademarks of their respective owners.

Revision Summary
PKGP-PRC012M-EN (12 Jun 2014)
•

Updated Low Leak Economizer Factory and Field Installed Option

•

Updated Features & Benefits, Model Number Description, Performance Data, Weights, and
Mechanical Specifications

© 2014 Trane All rights reserved

PKGP-PRC012M-EN

Table of Contents
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard and Optional Features at a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4
5
5
5
6

Outstanding Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Model Number Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Field Installed Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Zone Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

PKGP-PRC012M-EN

3

Features and Benefits
Voyager has the features and benefits that make it first class in the light commercial rooftop market.
Designed with input from field contractors and engineers, its U-shaped airflow performance is
outstanding.
Figure 1. Voyager features

Q

C

E
F

D

J

K

B
G

N
A

I

M

H
A

Foil-Faced Insulation

J

B

Quick Adjust Idler Pulley

K Smoke Detector

C

ReliaTel™ Microprocessor Controls

D Colored and Numbered Wiring

L

Single Side Service

Fan Failure Switch

Low Ambient Cooling to Zero° F

N Through-the-Base Electrical

F

High and Low Pressure Switches

O Disconnect Switch or Circuit Breaker

G Scroll Compressors (R-410A)
Available in R-410A refrigerant

I

Hinged Access Doors

O

M Clogged Filter Switch

E

H

L

P

Convenience Outlet

Q Variable Frequency Drive

P

Standard and Optional Features at a Glance
Standard Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
4

2” throwaway filters
5 year Limited Compressor Warranty
1 year Limited Parts Warranty
Anti-Short Cycle Timer
Belt Drive Motors
Colored and Numbered Wiring
Crankcase Heaters
Dedicated Airflow
Easy Access Low Voltage Terminal Board (LTB)
Foil-Faced and Edge Captured Insulation
High Pressure Cutout
IAQ Sloped Condensate Drain Pan
Liquid Line Refrigerant Drier
Low Ambient Cooling to 0°F
Operating Charge of R-410A
Patented Hybrid Condenser Coil for Easy Cleaning
Phase Monitor
Quick Access Panels
Quick Adjust Idler Arm Pulley
ReliaTel™ Microprocessor Controls
Single Point Power
Single Side Service
Standardized Components
PKGP-PRC012M-EN

Features and Benefits

•
•

U-shaped Airflow Pattern
Variable Frequency Drive (Multispeed Indoor Fan and Single Zone VAV)

Factory Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

2” MERV 8 or MERV 13 Filters5 with Filter Removal Tool
Black Epoxy Pre-Coated Coils
CO2 Sensor Wiring (Wiring Only)15
Condensate Overflow Switch
Fault Detection & Diagnostics (FDD)
High Efficiency Motors5
High Short Circuit Current Rated (SCCR) Electrical Subsystem16
Hinged Access Doors
Human Interface - 5 inch Color Touchscreen
Multi-Speed Fan
Powered or Unpowered Convenience Outlet4
Single Zone Variable Air Volume (SZVAV)
Stainless Steel Drain Pan
Supply and/or Return Air Smoke Detector2, 9
Through the Base Electrical with Circuit Breaker10, 11
Through the Base Electrical With Disconnect Switch6, 10, 11
Through the Base Utilities Access

Factory or Field Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

BACnet™ Communication Interface1
Barometric Relief1
Clogged Filter/Fan Failure Switch2, 5
Discharge Air Sensing Kit2, 5
Economizer - Standard, Downflow1
Electric Heaters5, 7, 11
Frostat™2, 5
Indoor Fan Motor Shaft Grounding Ring14
LonTalk® Communications Interface5
Low Leak Economizer - Downflow
Oversized Motors5
Reference or Comparative Enthalpy3, 5
ReliaTel Options Module8
Tool-less Hail Guards5
Trane Communications Interface (TCI)5, 13

Field Installed Options
•
•
•
•
•
•
•
•
•
•
•
PKGP-PRC012M-EN

CO2 Sensor
Digital Display Zone Sensor
Dual Thermistor Remote Zone Sensor
Economizer - Standard, Horizontal
High Static Drive
Low Leak Economizer - Downflow
Manual Outside Air Damper
Motorized Outside Air Dampers
Powered Exhaust
Roof Curb (Downflow only)
Remote Potentiometer
5

Features and Benefits

•
•

Ventilation Override Accessory2
Zone Sensors and Remote Zone Sensors

Note: Explanation of Note1 - Note16 located in “Model Number Description,” p. 19.

Other Benefits
•
•
•
•
•
•
•
•

Cabinet Design Ensures Water Integrity
Ease of Service, Installation and Maintenance
Mixed Model Build Enables “Fastest in the Industry” Ship Cycle Times
Outstanding Airflow Distribution
ReliaTel Controls Benefits
Rigorous Testing
Unmatched Product Support
Varitrac

Outstanding Standard Features
Anti-Short Cycle Timer
Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance
compressor reliability by assuring proper oil return.

Colored and Numbered Wiring
Save time and money tracing wires and diagnosing the unit.

Compressors
Voyager contains the best compressor technology available to achieve the highest possible
performance. Dual compressors are outstanding for humidity control, light load cooling conditions
and system back-up applications. Dual compressors are available on all models.

Condenser Coil
Voyager boasts a patent-pending 1+1+1 condenser
coil (pictured right), permanently gapped for easy
cleaning.

Controls—ReliaTel
ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing
input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel
also provides outputs for building automation systems and expanded diagnostics. For a complete
list of ReliaTel offerings, refer to “Other Benefits,” p. 13.

Conversion-less Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration
time to convert in the field — a major cost savings during installation. Horizontal units come
complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct
flanges are a time and cost saver.

Crankcase Heaters
These band or insertion heaters provide improved compressor reliability by warming the oil to
prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager
models.
6

PKGP-PRC012M-EN

Features and Benefits

Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as a standard feature on the discharge line
of each system. This standard feature provides extra protection to the compressors against high
discharge temperatures in case of loss of charge, extremely high ambient and other conditions
which could drive the discharge temperature higher.

Easy Access Low Voltage Terminal Board

Foil Faced Insulation

Voyager’s Low Voltage Terminal Board is
external to the electrical control cabinet. It is
extremely easy to locate and attach the
thermostat wire and test operation of all unit
functions. This is another cost and time saving
installation feature.

All panels in the evaporator section of the unit
have cleanable foil-faced insulation. All edges
are either captured or sealed to ensure no
insulation fibers get into the airstream.

Low Ambient Cooling
All Voyager microprocessor units have cooling capabilities down to 0°F as standard.

Low Voltage Connections
The wiring of the low voltage connections to the unit and
the zone sensors is as simple as 1-1, 2-2, and 3-3. This
simplified system makes it easy for the installer to wire.

Motors
All indoor fan motors are belt drive as standard.

Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.

Phase Monitor
The phase monitor provides 100% protection for motors and compressors against problems
caused by phase loss, phase imbalance, and phase reversal. It is also equipped with an LED that
provides an ON or FAULT indicator.

Quick-Access Panels
Remove three or fewer screws for access to the standardized internal components and wiring.

PKGP-PRC012M-EN

7

Features and Benefits

Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm (pictured right), the
belt and sheaves can be quickly adjusted without
moving the mounted fan motor. The result is a major
savings in time and money.

Single Point Power
A single electrical connection powers the unit.

Single Side Service
Single side service is standard on all units.

Sloped Drain Pans
Standard on every unit.

Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one
Voyager and you are familiar with every Voyager. Due to standardized components throughout the
Voyager line, contractors/owners can stock fewer parts.

U-Shaped Airflow Pattern
The U-shaped airflow allows for improved static capabilities.

Variable Frequency Drives - VFD (Multispeed Indoor Fan and SZ VAV Only)
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed
modulation, as well as modulating gas heat. VFDs on the supply fan, as compared to inlet guide
vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs
are designed to allow bypass if required. Bypass control will simply provide full nominal airflow
in the event of drive failure. Modulating gas heat models with VFDs allow tighter space temperature
control with less temperature swing.

Variety of Options
Factory Installed Options
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical option for protection in mildly corrosive environments.

CO2 Sensor Wiring
This unit wiring for field installed C02 sensors. Factory-installed C02 sensor wiring saves time and
ensures proper unit connections for the field installed C02 sensor kits.

Condensate Overflow Switch
A condensate overflow switch is available to shut the unit down in the event that the condensate
drain line becomes clogged. This option protects the unit from water overflowing from the drain
pan and entering the base of the units.

Fault Detection & Diagnostics (FDD)
This offering meets the mandatory requirement of CA Title 24 of fully configurable diagnostics
allowing fault history and reading fault codes at the unit.This option provides detection of the

8

PKGP-PRC012M-EN

Features and Benefits

following faults: Air temperature sensor failure/fault and notification of acceptable economizer
mode.The FDD system shall be certified by the Energy Commission as meeting the requirements.

High Efficiency Filtration
Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters
provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when
MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.

High Efficiency Motors
This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

High Short Circuit Current Rating (SCCR)
Voyager rooftop units now have an optional high short circuit current rated electrical subsystem
for units with an MOP above 60A. This option is a perfect fit for applications that need protection
against high potential fault currents. This option also includes individual over current protection
for each compressor and the indoor fan, as well as a dedicated over current protection to the
condenser fan motor(s). When the high SCCR is ordered, the control box will have components
separated into two sections - high and low voltage components.

Hinged Access Doors
These doors permit easy access to the filter, fan/heat, and compressor/control sections. They
reduce the potential roof damage from screws or sharp access door corners.

Human Interface
The 5 inch Color Touchscreen Human Interface provides
an intuitive user interface to the rooftop unit that speeds
up unit commissioning, shortens unit troubleshooting
times, and enhances preventative maintenance
measures. The human interface includes several
features such as:
•

Data trending capabilities by means of time series
graphs

•

Historical alarm messages

•

Real-time sensor measurements

•

On board system setpoints

•

USB port that enables the downloading of
component runtime information as well as trended
historical sensor data

•

Customizable reports

Multi-Speed Indoor Fan System
Multi-speed indoor fan system is designed for use in applications for meeting the minimum
requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed
of the fan to 67% of full airflow based off compressor stages.

Powered or Unpowered Convenience Outlet
This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered. This
option can only be ordered when Through the Base Electrical with either the Disconnect Switch or
Circuit Breaker option is ordered. This option is available on all models.

PKGP-PRC012M-EN

9

Features and Benefits

Single Zone VAV - One Zone Variable Air Volume Mode
Note: Single Zone VAV is designed to be used with a zone sensor. If a unit is configured for Single
Zone VAV operation but is connected to a thermostat, the control will revert to multi-speed
(2-Speed) indoor fan control. (See "Multi-Speed Indoor Fan System" above.)
Single Zone VAV is designed for use in single zone applications like gymnasiums, auditoriums,
manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of
diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to "yesterday's"
constant volume (CV) systems, by reducing operating costs while improving occupant comfort. SZ
VAV systems combine Trane application, control and system integration knowledge to exactly
match fan speed with cooling and heating loads, regardless of the operating condition. Trane
algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those
of CA Title 24. The result is an optimized balance between zone temperature control and system
energy savings. Depending on your specific application, energy savings can be as much as 20%.
Note: Building system modeling in energy simulation software like TRACE is recommended to
evaluate performance improvements for your application.
SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the
simplest and fastest commissioning in the industry through proven factory-installed, wired, and
tested system controllers. All control modules, logic and sensors are factory installed, and tested
to assure the highest quality and most reliable system available. This means no special
programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be
installed in the field. Single Zone VAV is a quick and simple solution for many applications and is
available from your most trusted rooftop VAV system solution provider- Trane.

Stainless Steel Drain Pan
For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a
cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8
or 13), and demand control ventilation (CO2).

Supply, Return, and Plenum Air Smoke Detector
With this option (pictured right) installed, if smoke is detected,
all unit operation will be shut down. Reset will be manual at the
unit. Return Air Smoke Detectors require minimum allowable
airflow when used with certain models.
Supply and/or Return Smoke Detectors may not be used with
the Plenum Smoke Detector.

Through the Base Electrical/Horizontal Side Access with Circuit Breaker
This option is a factory installed thermal-magnetic, molded case, HACR Circuit Breaker with
provisions for through the base electrical connections.

Through the Base Electrical/Horizontal Side Access with Disconnect Switch
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base
electrical connections are available.

Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of the unit. This option will allow for field
installation of liquid-tight conduit and an external, field-installed disconnect switch.

10

PKGP-PRC012M-EN

Features and Benefits

Factory or Field Installed Options
BACnet™ Communications Interface
The BACnet communications interface allows the unit to communicate directly with a generic open
protocol BACnet MS/TP Network Building Automation System Controls.

Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving
excess building pressure.

Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or
clogged filter indication.

Discharge Air Sensing Kit
Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel™
Options Module.

Economizer - Standard, Downflow
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These
economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure
proper installation.
Note: Factory-installed economizers require some field set-up.

Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3
cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air
supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired
with powered exhaust for additional building pressure relief. This option can be paired with or
without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.
Available on downflow units only. The economizers come with three control options, dry bulb and
reference or comparative enthalpy (optional).

Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical
option with an Electrical Heater, the heater must be factory installed.

Frostat™
This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to
prevent evaporator icing and protect the compressor. Recommended for applications with low
leaving air temperatures, low airflow and/or high latent load applications.

Indoor Fan Motor Shaft Grounding Ring
Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path
away from the motor bearings to ground. Bearing Protection Rings shall be maintenance free
circumferential rings of conductive micro fibers that discharge voltages to ground.

LonTalk® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™ LCI-V device
or directly with generic LonTalk Network Building Automation System Controls.

Oversized Motors
Factory or field installed oversized motors are available for high static applications.
PKGP-PRC012M-EN

11

Features and Benefits

Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.

ReliaTel Options Module (RTOM)
The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan
setpoint, dehumidification setpoint, supply air tempering, Frostat™ and smoke detector.

Tool-less Hail Guards
Tool-less, hail protection quality coil guards (pictured right) shall be
either factory or field-installed for condenser coil protection. This
option protects the condenser coil from vandalism and/or hail
damage.

Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the
ReliaTel™ easily interfaces with Trane’s Integrated Comfort™ System.

Field Installed Options
CO2 Sensor - Demand Control Ventilation (DCV)
Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand
(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the
building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (Carbon
Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet
the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed
accessory. Two field installed kits are offered; C02 sensor and wiring or C02 sensor only. The C02
Sensor only kit should be ordered with factory installed C02 sensor wiring. Factory installed C02
sensor wiring saves set-up time and ensures proper unit connections for the C02 sensor.

Dampers
0–25 percent manual or 0–50 percent motorized outside air dampers are available.

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone
sensors.

Economizer - Standard, Horizontal
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.
These economizers provide free cooling as the outdoor temperature and/or humidity decreases.
Correctly installed, they offer a valuable energy savings.

Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3
cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air
supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired
with powered exhaust for additional building pressure relief. Available on downflow units only.

High Static Drive Accessory
Available on many models, this high static drive accessory extends the capability of the standard
motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

Powered Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a
downflow economizer, to maintain proper building pressurization. Great for relieving most
building overpressurization problems.
12

PKGP-PRC012M-EN

Features and Benefits

Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote
variable resistance to enable the operator to adjust the minimum damper position.

Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb
selection.

Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different
pre-programmed sequences for Smoke Purge, Pressurization and Exhaust. The transition occurs
when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay
output from a smoke detector or fire control panel. The ventilation override kit is available as a field
installed accessory.

Zone Sensors/Thermostats
Available in programmable, automatic and manual styles.
Note: Zone sensors required for units configured for Single Zone VAV indoor fan system control
to enable Single Zone VAV functionality.

Other Benefits
Cabinet Integrity
For added water integrity, Voyager has a raised 1-1/8” lip around the supply and return of the
downflow units to prevent water from blowing into the ductwork.

Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance,
Voyager was designed with direct input from service contractors. This valuable information helped
to design a product that would get the serviceman off the job quicker and save the owner money.
Voyager does this by offering outstanding standard features enhanced by a variety of factory and
field installed options, multiple control options, rigorously tested proven designs and superior
product and technical support.

Outstanding Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many
cases, improve the comfort through better air distribution.

ReliaTel™ Controls Benefits
ReliaTel controls provide unit control for heating, cooling
and ventilating by utilizing input from sensors that
measure outdoor and indoor temperature.
Quality and Reliability are enhanced through ReliaTel
control and logic:
– Prevents the unit from short cycling, considerably
improving compressor life.
– Ensures the compressor will run for a specific
amount of time which allows oil to return for better
lubrication, enhancing the reliability of the
compressor.

PKGP-PRC012M-EN

13

Features and Benefits

Voyager with ReliaTel reduces the number of components required to operate the unit, thereby
reducing possibilities for component failure.

ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays.
ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer
has to purchase these controls as options and pay to install them. The wiring of the low voltage
connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system
makes wiring easier for the installer.

ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run Voyager unit through its paces. Simply place a jumper
between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk
through its operational steps automatically.
The unit automatically returns control to the zone sensor after stepping through the test mode a
single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light
indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™
Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in
and possible diagnostic information (dirty filters for example).

Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control
functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by
staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant.
If a component goes astray, the unit will continue to operate at predetermined temperature
setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone
sensor(s) work together in harmony to provide much tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits all Packaged Gas/Electric, Cooling, and Heat Pump models. This
provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.

Rigorous Testing
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Voyager
units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top (either two
or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges
are gasketed and sealed to ensure superior water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test
shipped around the country to determine the best packaging. Factory shake and drop tests were
used as part of the package design process to help assure that the unit arrives at the job site in top
condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting
lugs and rails hold up under stress.
We perform a 100% coil leak test at the factory. All coils are pressure and leak tested at a minimum
of 450 psig. The completely assembled refrigerant system is leak tested at a minimum of 240 psig
with a refrigerant and nitrogen mixture.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
immediately. Every unit receives a 100 percent unit run test before leaving the production line to
make sure it lives up to rigorous Trane requirements.
14

PKGP-PRC012M-EN

Features and Benefits

Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
•

Product

•

Special Applications

•

Application

•

Specifications

•

Service

•

Computer Programs and much more

•

Training

VariTrac
When Trane’s changeover VAV System for light commercial applications is coupled with Voyager,
it provides the latest in technological advances for comfort management systems and can allow
thermostat control in every zone served by VariTrac.
Note: Varitrac is not recommended for SZ VAV and Multi-speed indoor fan applications.

VariTrac TM

PKGP-PRC012M-EN

15

Application Considerations
Application of this product should be within the catalogued airflow and cooling considerations.

Low Ambient Cooling
This Voyager line features, as a standard, low ambient cooling down to 0°F. Contact your local Trane
Representative for more assistance with low ambient cooling applications.

Barometric Relief
This product line offers an optional barometric relief damper included in the downflow economizer
accessory. This accessory consists of gravity dampers which open with increased pressure. As the
building air pressure increases, the pressure in the unit return air section also increases, opening
the dampers and relieving the conditioned space.
Important:

THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING
OPERATION IS SYSTEM RELATED. PRESSURE DROP OF THE RETURN AIR SYSTEM
SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZATION.

Power Exhaust Accessory
The power exhaust accessory is available on all downflow units. This accessory can be field
installed and will assist in relieving a building’s pressurization.

Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the
cooling cycle.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure
adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which
appear inadequate should be reviewed with the local Trane sales personnel.

Unit Pitch
These units have sloped condensate drain pans. Units must be installed level, any unit slope must
be toward access side of unit.

VariTrac
Varitrac is not recommended for SZ VAV and Multi-speed indoor fan applications.

16

PKGP-PRC012M-EN

Selection Procedure
Cooling Capacity
Step 1
Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane
calculation form or any other standard accepted method.

Step 2
Given the following building requirements:

A. Electrical Characteristics: 460/60/3
B. Summer Design Conditions: Entering Evaporator Coil: 80 DB/ 67 WB
Outdoor Ambient: 95 DB

C. Total Cooling Load: 172 MBh
D. Sensible Cooling Load: 122 MBh
E. Airflow: 6000 cfm
F. External Static Pressure: 0.50 in. w.g.
G. Rooftop - downflow configuration.
H. Accessories, Economizer, Supplementary Electric Heat
I. Heating Capacity 100 MBh
460 volt/3 phase Electric Supplemental Heat - at 6000 cfm
Size the equipment using Table 3, p. 24. As a starting point, a rough determination of the size of the
unit must be made. This selection will then be confirmed after examining the performance at the
given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then
round up to the nearest unit size. 172 MBh/12 MBh = 14.33 (approx. 15 tons.)

Step 3
Table 3, p. 24 shows that a WSD180E4 has a gross cooling capacity of 186.2 MBh and 138.9 MBh
sensible capacity at 95°F ambient and 6000 cfm with 80 DB/67 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions
When the design conditions are between two numbers that are in the capacity table, interpolation
is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.

Step 4
Verify that there will be enough capacity by determining net capacity. In order to select the correct
unit which meets the building’s requirements, the fan motor heat must be deducted from the gross
cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by
the motor CFM and static pressure. To determine the total unit static pressure, add the following:
External Static: 0.50 in.
Standard Filter 1 in: 0.05 in. (from Table 12, p. 29)
Economizer Return Air: 0.04 in. (from Table 12, p. 29)
Electric Heater Size 18 kW: 0.06 in.
Total Static Pressure: 0.65 in.
Note: The Evaporator Fan Performance Table 6, p. 27 has already accounted for the pressure drop
for standard filters and wet coils.

PKGP-PRC012M-EN

17

Selection Procedure

Therefore, the actual Total Static Pressure is 0.65 - 0.05 = 0.6. With 6000 CFM and 0.60 inches,
Table 6, p. 27 shows 2.17 Bhp.
The note below Table 6, p. 27 gives a formula to calculate Fan Motor Heat:
3.15 x bhp = MBh
3.15 x 2.17 = 6.835 MBh
Now subtracting the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity =
186.2 - 6.835 = 179.36 MBh
Net Sensible Cooling Capacity =
138.9 - 6.385 = 132.065 MBh

Step 5
If the performance will not meet the required load of the building, try a selection at the next higher
size unit.

Heating Capacity
Step 1
Calculate the building heating load using the Trane calculation form or other standard accepted
method.

Step 2
Size the equipment using Table 14, p. 31 to match the heating loads at design conditions.

A. Total Heating Load: 100 MBh
B. Outdoor Ambient (Winter) 17 DB
C. Indoor Return Temperature: 70 DB
D . Airflow: 6000 CFM
Use the integrated portion of Table 14, p. 31 for the WSD180E4 to determine capacity at winter
design conditions. The mechanical heating portion of the heat pump will provide 85.4 MBh.

Step 3
Because 45 MBh is less than the building’s required heating capacity at winter design conditions,
a supplementary heater must be selected.
100.0 - 85.54 = 14.46 MBh
From Table 17, p. 32, at 480 volts, the 18 kW Heater will be adequate to do the job.
18 kW 61 MBh
From Table 17, p. 32 select heater AYDHTRK418A (18 kW 460/60/3).

18

PKGP-PRC012M-EN

Model Number Description
W

S

D

1

5

0

E

3

R

G

B

*

*

1

2

3

4

5

6

7

8

9

10

11

12

13

Digit 1 — Unit Type

7
8

=
=

9
A

=
=

B

=

Digit 4, 5, 6 — Nominal Gross
Cooling Capacity (MBh)

C

=

150 =
180 =
240 =

D

W =

Packaged Cooling, Electric Heat

Digit 2 — Efficiency
S

=

Standard Efficiency

Digit 3 — Airflow Configuration
D
H

=
=

Downflow
Horizontal

12½ Tons
15 Tons
20 Tons

Digit 7 — Major Design
Sequence
E

=

R-410A Refrigerant

Digit 8 — Voltage Selection
3 =
4 =
W =

208-230/60/3
460/60/3
575/60/3

Digit 9 — Unit Controls
R

=

Reliatel

Digit 10 — Heating Capacity
0
G
N
P
R

=
=
=
=
=

No Heat
18 kW Electric Heat
36 kW Electric Heat
54 kW Electric Heat
72 kW Electric Heat

Digit 11 — Minor Design
Sequence
Digit 12, 13 — Service Sequence
Digit 14 — Fresh Air Selection
0
A
B
D

=
=
=
=

F

=

H

=

K

=

M =
P

=

No Fresh Air
Manual Damper
Motorized Damper
Econ Dry Bulb w/ Barometric
Relief1
Econ Reference Enthaply w/
Barometric Relief1
Econ Comparative Enthaply w/
Barometric Relief1
Low Leak Econ w/ Barometric
Relief1
Low Leak Econ Reference
Enthalpy w/ Barometric Relief1
Low Leak Econ Comparative
Enthalpy w/ Barometric Relief1

Digit 15 — Supply Fan/Drive
Type/Motor
0
1
3
6

=
=
=
=

Standard Motor
Oversized Motor5
High Efficiency Motor5
Single Zone Variable Air Volume
Standard Motor

PKGP-PRC012M-EN

Multi-Speed Standard Motor
Single Zone Variable Air Volume
Oversized Motor
Multi-Speed Oversized Motor
Single Zone Variable Air Volume
Standard Motor w/ Shaft Ground
Ring
Multi-Speed Standard Motor w/
Shaft Ground Ring
Single Zone Variable Air Volume
Oversized Motor w/ Shaft Ground
Ring
Multi-Speed Oversized Motor w/
Shaft Ground Ring

Digit 22 — Refrigeration System
Option
0

=

Standard refrigeration system

Digit 23 — Refrigeration
Controls
0
1

=
=

Without Refrigeration Controls
Frostat™

Digit 24 — Smoke Detector2,9
0
A
B
C

=
=
=
=

Digit 16 — Hinged Service
Access / Filters5

D

=

0

=

Digit 25 — System Monitoring
Controls2

A
B
C
D
E

=
=
=
=
=

=

Standard Panels/Standard
Filters17
Hinged Access/Standard Filters17
Standard Panels/2" MERV 8 Filters
Hinged Access/2" MERV 8 Filters
Standard Panels/MERV 13 Filters
Hinged Access/MERV 13 Filters

Digit 17 — Condenser Coil
Protection
0
1
2
3

=
=
=
=

Standard Coil
Standard Coil With Hail Guard
Black Epoxy Pre-Coated Coil
Black Epoxy Pre-Coated Coil with
Hail Guard

0
1
2
3
4

=
=
=
=
=

5

=

6

=

7

=

A

=

Digit 18 — Through The Base
Provisions

B

=

0
A
D

C

=

D

=

E

=

Digit 20 — Convenience Outlet
Option

F

=

0
A
B

G

=

H

=

=
=
=

No Through The Base Provisions
Through The Base Electric11
Through The Base Utilities Access

Digit 19 — Disconnect Switch/
Circuit Breaker10
0
1

=
=

2

=

=
=
=

No Disconnect/circuit break
Unit Mounted Non-Fused
Disconnect Switch
Unit Mounted Circuit Breaker

Without Convenience Outlet
Unpowered Convenience Outlet4
Powered Convenience Outlet4

Digit 21 — Communications
Options
0

=

1

=

2

=

6

=

Without Communications
Options
Trane Communications
Interface5, 13
Lontalk Communications
Interface5
Building Automation Control
Network Communications
Interface

Without Smoke Detector
Return Air Smoke Detector
Supply Air Smoke Detector
Return/Supply Air Smoke
Detector
Plenum Smoke Detector

No Monitoring Controls
Clogged Filter Switch
Fan Failure Switch
Discharge Air Sensing
Clogged Filter Switch and Fan
Failure
Clogged Switch and Discharge Air
Sensing
Fan Failure Switch and Discharge
Air Sensing
Clogged Filter Switch, Fan Failure
Switch and Discharge Air Sensing
Condensate Drain Pan Overflow
Switch
Clogged Filter Switch and
Condensate Drain Pan Overflow
Switch
Fan Failure Switch and
Condensate Drain Pan Overflow
Switch
Discharge Air Sensing and
Condensate Drain Pan Overflow
Switch
Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
Overflow Switch
Clogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing
and Condensate Drain Pan
Overflow Switch

Digit 26 - System Monitoring
Controls
0
A

=
=

B

=

No Monitoring Controls
Demand Control Ventilation
(CO2)15
FDD (Fault Detection and
Diagnostics)
19

Model Number Description

C

=

FDD (Fault Detection Diagnostics)
& Demand Control Ventilation
(CO2)15

Digit 27 - Unit Hardware
Enhancements
0
1

=
=

No Enhancements
Stainless Steel Drain Pan

Digit 28 - Short Circuit Current
Rating
0
A

=
=

Standard SCCR
65kA SCCR Option16

Digit 31 - Advanced Unit
Controls
0
1

=
=

Standard Unit Controls
Human Interface18

Note: Most Factory Installed Options
available for Downflow Air
Discharge units only. Please verify
with ordering system for
availability.

Model Number Notes
1. Some field set up required.
2. Requires ReliaTel Options Module.
3. Requires Economizer.
4. Must be ordered with Throughthe-Base Electrical option or
Horizontal-Side Access and either
Unit Mounted Disconnect or
Circuit Breaker.
5. Available factory installed on
downflow AND horizontal units.
Verify with ordering system.

accessories (such as bolt on heat
wheels, economizers, and power
exhaust). Do not order the return
air smoke detectors when using
this type of accessory.
10. Unit mounted disconnect and
circuit breakers are mutually
exclusive of each other.
11. Through-the-base electrical
option or Horizontal-Side Access
must be ordered with either unit
mounted disconnect or circuit
breaker. When adding heat, you
must order Trane Electric Heat.
12. All Factory Installed Options are
Built-to-Order. Check order
services for estimated production
cycle.
13. TCI is for use with non-VariTrac
systems and VariTrac systems.
14. For use with multi-speed and
SZVAV units only.
15. Demand Control Ventilation
Option includes wiring only. The
C02 sensor is a field-installed only
option.
16. 575 VAC option is 25kA.
17. Standard filters are not available
with Low Leak Economizers.
18. Human Interface is standard with
FDD (Fault Detection Diagnostics).

6. Cannot be fused.
7.

Must be factory installed when
using Through-the-Base Options.

8. ReliaTel Options Module is
required when ordering the
following accessories: Clogged
Filter Switch, Fan Fail Switch,
Condensate Overflow Switch,
Discharge Air Sensing Kit, Frostat,
Ventilation Override, and Smoke
Detector.
9. Option cannot be ordered in
conjunction with field installed
economizer on downflow units.
Must be factory installed. The
return air smoke detector may not
fit up or work properly on the
Voyager units when used in
conjunction with 3rd party

20

PKGP-PRC012M-EN

General Data
Table 1.

General data — 12½ - 20 tons
12½ Tons
Downflow &
Horizontal Units

15 Tons
Downflow &
Horizontal Units

20 Tons
Downflow &
Horizontal Units

WS*150E3,4,W

WS*180E3,4,W

WS*240E3,4,W
249,000

Cooling Performance(a)
Gross Cooling Capacity

148,000

177,000

EER(b)

10.6

10.6

9.7

Nominal Airflow/ARI Rated Airflow (CFM)

5000

6000 / 5300

8000 / 6400

ARI Net Cooling Capacity

146,000

170,000

240,000

IEER(c) (One Speed Fan / Two or Variable
Speed Fan)

12/13.5

12/13.5

11.5/12.0

13.77

16.04

25.47

136,000

170,000

210,000

3.2

3.2

3.2

12.46

15.57

19.23

75,000

90,000

120,000

2.1

2.1

2.1

10.47

12.56

16.75

2 / Scrolls

2 / Scrolls

2 / Scrolls

9.2

9.2

9.4

Outdoor Coil — Type

Hi-Performance

Hi-Performance

Hi-Performance

Refrigerant Control

Expansion Valve

Expansion Valve

Expansion Valve

Tube Size (in.) OD

0.3125

0.3125

0.3125

Face Area (sq. ft.)

35.20

35.20

42.53

Rows/FPI

3 / 16

3 / 16

3 / 16

System Power (kW)

Heating Performance(a)
High Temp. Btuh Rating
COP
System Power (kW)
Low Temp. Btuh Rating
COP
System Power (kW)

Compressor
Number/Type

ARI Sound Rating (BELS)(d)

Indoor Coil — Type

Hi-Performance

Hi-Performance

Hi-Performance

Tube Size (in.) ID

0.3125

0.3125

0.3125

Face Area (sq. ft.)

26.00

26.00

31.42

Rows/FPI

3 / 15

4 / 15

4 / 15

Short Orifice

Short Orifice

Short Orifice

1/1.00 NPT

1/1.00 NPT

1/1.00 NPT

Propeller

Propeller

Propeller

2 / 26

2 / 26

2 / 28

Direct / 1

Direct / 1

Direct / 1

CFM

11,100

10,800

14,800

Number Motors/HP

2 / 0.5

2 / 0.5

2 / 1.0

Motor RPM

1,100

1,100

1,125

Refrigerant Control
Drain Connection Number/Size (in.)

Outdoor Fan — Type
Number Used/Diameter (in.)
Drive Type/No. Speeds

PKGP-PRC012M-EN

21

General Data

Table 1.

General data — 12½ - 20 tons (continued)
12½ Tons
Downflow &
Horizontal Units

15 Tons
Downflow &
Horizontal Units

20 Tons
Downflow &
Horizontal Units

WS*150E3,4,W

WS*180E3,4,W

WS*240E3,4,W

FC Centrifugal

FC Centrifugal

FC Centrifugal

1 / 18x18

1 / 18x18

1 / 18x18

Belt / 1

Belt / 1

Belt / 1

1

1

1

3.0 / 5.0

3.0 / 5.0

5.0 / 7.5

Motor RPM (Standard/Oversized)

1740 / 3,450

1740 / 3,450

3450 / 3,470

Motor Frame Size (Standard/Oversized)

145T / 145T

145T / 145T

145T / 184T

Filters - Type Furnished

Throwaway

Throwaway

Throwaway

Downflow

(4)20x20x2
(4)20x25x2

(4)20x20x2
(4)20x25x2

(8)20x20x2
(4)20x16x2

Horizontal

(8)20x25x2

(8)20x25x2

(12)20x20x2

Downflow

14 / 14.5

16.5 / 15.9

20.0 / 20.7

Horizontal

13.2 / 13.3

17 / 15.9

Indoor Fan - Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor HP (Standard/Oversized)

Number Size Recommended

Refrigerant Charge Pounds of
R-410A(e)

(a) Cooling Performance is rated at 35°C (95°F) ambient, 26.7°C (80°F) entering dry bulb, 19.4°C (67°F) entering wet bulb.
Heating Performance is rated at 20°C (68°F) ambient, 8.3°C (47°F) entering dry bulb, 6.1°C (43°F) entering wet bulb.
Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat.
Units are suitable for operation to ±20% of nominal airflow. Rated in accordance with ARI Standard 210/240 or 340/360.
(b) EER is rated at ARI conditions and in accordance with DOE test procedures.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 360.
(d) Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

22

PKGP-PRC012M-EN

Performance Data
Table 2.

Gross cooling capacities (MBh) 12½ tons three phase WS*150E
Ambient Temperature (°F)
85

Air
Flow
CFM

4000

4500

5000

5500

6000

Ent
DB
°F

95

105

Entering Wet Bulb (F)
61

67

73

61

67

73

61

67

73

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

75

140.4 110.8 152.3

74.7

156.2

39.1

131.7 108.1 146.6

75.2

153.1

35.5

118.1 103.1 138.7

73.6

148.3

33.9

80

146.6 139.5 156.7

99.7

160.5

60.9

135.0 131.4 148.6

98.4

155.7

59.5

123.4 123.4 140.6

97.0

150.9

58.0

85

148.1 148.1 156.5 121.3 161.4

85.3

141.9 141.9 150.7 121.6 158.5

83.4

135.0 135.0 142.6 120.3 153.1

81.9

90

155.8 155.8 159.4 144.5 163.7 106.3 150.5 150.5 153.8 145.1 160.6 107.3 144.0 144.0 146.2 143.6 156.0 105.8

75

144.5 117.5 156.4

157.1

37.5

136.4 115.5 149.0

154.1

36.7

125.1 111.9 141.7

149.6

33.1

80

147.8 143.2 158.8 103.5 159.8

61.1

139.9 139.6 151.2 102.9 157.1

63.3

131.5 131.5 143.7 102.3 152.3

60.1

85

153.8 153.8 158.8 127.9 162.4

85.0

148.2 148.2 153.8 128.8 159.9

89.0

141.3 141.3 146.4 129.1 155.0

86.6

90

160.1 160.1 161.6 152.9 165.3 108.6 156.0 156.0 157.4 153.7 162.5 113.9 150.0 150.0 150.9 150.8 157.6 113.0

75

147.7 123.7 154.9

157.8

33.9

139.8 122.3 150.7

154.7

36.9

129.6 119.6 143.9

150.9

33.7

80

151.6 150.4 160.1 107.3 160.2

60.0

144.2 144.2 153.1 107.3 158.0

64.7

136.9 136.9 146.1 107.3 153.1

63.5

85

157.3 157.3 160.3 135.3 162.7

86.8

152.6 152.6 156.4 136.0 160.8

91.1

146.2 146.2 149.3 136.4 156.5

92.2

90

162.3 162.3 163.0 158.0 165.4 112.7 159.4 159.4 159.9 159.1 163.6 116.5 154.2 154.2 154.2 154.2 159.3 120.2

75

149.9 129.7 155.6

158.0

31.8

142.5 128.7 151.9

155.5

34.1

133.3 126.6 145.6

153.0

36.3

80

154.1 154.0 158.4 112.6 160.5

62.6

148.3 148.3 154.5 111.6 158.7

63.3

141.2 141.2 148.2 112.6 154.5

66.6

85

159.4 159.4 161.0 140.5 163.3

91.2

155.8 155.8 157.9 142.7 160.9

90.9

150.0 150.0 151.8 143.2 157.3

96.9

90

163.8 163.8 164.2 160.8 165.7 118.4 161.1 161.1 161.4 161.2 164.1 119.0 157.1 157.1 157.2 157.2 160.3 125.5

75

153.7 136.6 156.6

159.3

32.9

145.0 134.8 152.1

155.8

31.7

136.2 132.9 147.0

151.9

35.3

80

156.4 156.4 159.2 116.6 161.8

65.1

151.2 151.2 155.4 116.6 159.2

63.2

144.6 144.6 149.8 117.7 155.3

68.4

85

160.3 160.3 161.9 143.5 163.7

95.1

157.8 157.8 159.0 148.8 164.6

97.9

152.7 152.7 156.1 154.1 158.2

99.2

90

164.7 164.7 164.9 162.7 166.3 122.2 162.7 162.7 164.7 164.7 164.5 123.4 158.7 158.7 158.6 158.6 161.3 128.5

77.9

78.7

82.5

85.7

77.1

78.4

80.6

83.2

76.3

79.1

81.1

83.8

Ambient Temperature (°F)
115
Air
Flow
CFM

4000

4500

5000

5500

Ent
DB
°F

61

67

73

MBH SHC

MBH SHC

MBH SHC

75

104.6

129.1

71.4

141.4

33.8

80

114.1 114.1 130.8

94.5

143.9

58.3

85

127.1 127.1 132.8 118.1 145.8

82.1

90

136.7 136.7 136.9 136.9 148.1 105.6

75

111.4 107.2 132.2

143.0

32.2

80

122.5 122.5 134.1 100.7 145.4

59.5

85

133.6 133.6 137.3 127.3 147.8

85.6

90

142.8 142.8 142.9 142.9 150.6 112.4

75

116.2 114.7 134.8

144.4

31.3

80

128.8 128.8 136.9 106.9 146.7

60.7

85

138.6 138.6 140.6 135.6 149.5

90.1

90

147.3 147.3 147.5 147.5 152.6 119.3

75

121.4 121.1 136.7

80

133.0 133.0 139.2 112.5 148.0

63.8 Notes:

142.5 142.5 143.5 142.0 150.9

95.4

98.2

74.6

77.8

80.5

144.9

32.0

80

1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not
applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
150.4 150.4 150.5 150.5 153.8 126.7 2. All capacities shown are gross and have not considered indoor fan heat. To obtain net
cooling subtract indoor fan heat.
125.5 125.5 138.4 83.4 145.6 32.6
3. MBH = Total Gross Capacity
136.5 136.5 141.1 117.9 148.8 66.6 4. SHC = Sensible Heat Capacity

85

145.6 145.6 146.1 145.9 151.8 100.4 * stands for both downflow and horizontal unit.

90

152.7 152.7 152.6 152.6 155.0 132.6

85
90
75

6000

Entering Wet Bulb (F)

PKGP-PRC012M-EN

23

Performance Data

Table 3.

Gross cooling capacities (MBh) 15 tons three phase WS*180E
Ambient Temperature (°F)
85

Air
Flow
CFM

4800

5400

6000

6600

7200

Ent
DB
°F

95

105

Entering Wet Bulb (F)
61

67

73

61

67

73

61

67

73

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

75

172.4 137.8 185.0

190.7

51.2

157.4 132.2 181.5

189.5

52.1

141.1 123.6 169.8

185.3

54.1

80

175.2 164.2 185.9 124.4 191.5

97.2

73.3

165.6 159.0 182.5 125.2 190.5

98.1

80.5

151.3 150.2 179.0 126.0 186.2

95.1

82.1

85

182.7 182.4 204.9 161.7 192.5

98.7

176.3 176.3 183.4 152.4 190.9 107.9 167.0 167.0 161.9 143.1 187.8 110.5

90

186.4 187.2 188.2 173.6 192.9 123.3 185.2 185.2 186.8 175.9 191.9 134.5 178.6 178.6 180.1 173.1 188.8 137.3

75

176.7 146.7 186.4

192.2

43.3

163.9 141.3 183.8 102.8 190.8

53.1

148.9 134.8 174.0

187.4

51.8

80

185.0 177.6 187.1 128.6 192.7

68.8

173.2 169.4 185.4 133.4 191.9

82.7

161.4 161.2 175.2 130.2 188.4

82.7

85

185.9 186.3 188.2 157.9 193.7

99.4

183.4 183.4 186.4 163.3 192.8 110.9 171.2 171.2 178.2 160.1 188.9 112.5

97.4

99.6

90

189.2 190.2 189.9 181.4 193.9 129.3 188.2 188.7 188.9 182.3 193.7 138.7 183.8 183.8 185.0 181.5 190.0 143.1

75

180.7 154.7 186.9 103.2 193.2

37.0

169.6 151.6 186.2 105.9 192.0

51.1

154.9 143.9 177.5 103.9 189.4

51.7

80

184.3 179.0 193.7 140.1 193.9

70.8

179.0 177.4 186.2 138.9 193.4

81.3

163.3 163.3 178.8 137.7 190.0

85.0

85

187.7 188.5 189.9 165.8 194.6 104.4 186.5 186.5 188.1 168.9 194.3 111.2 171.3 172.9 182.7 169.1 190.4 119.4

90

191.3 192.2 191.6 184.4 194.5 135.3 190.5 191.3 190.7 187.4 195.1 140.8 187.5 187.7 187.4 186.9 191.8 152.7

75

189.8 168.9 188.4 106.3 193.8

36.5

175.1 160.4 186.7 106.8 193.3

46.9

160.4 151.9 180.2 109.6 189.7

51.0

80

185.9 182.8 189.6 140.4 194.2

73.1

182.9 182.6 195.4 150.8 194.5

77.7

152.3 152.3 181.8 146.4 190.7

88.8

85

188.8 189.7 190.9 168.8 195.1 108.9 188.3 188.7 189.2 174.2 195.3 110.6 181.0 181.0 185.1 175.2 191.4 125.5

90

192.3 193.5 192.7 186.1 195.8 141.0 191.3 192.3 192.4 191.2 196.0 145.8 189.6 190.1 189.5 190.0 192.9 158.2

75

184.1 166.8 189.6 107.7 193.7

36.2

177.0 165.0 187.4 110.1 194.3

40.6

165.9 159.8 185.2 112.5 191.1

51.1

80

187.8 187.0 190.5 141.8 194.6

73.2

185.5 185.5 188.5 148.8 195.4

76.1

156.3 157.7 183.6 152.6 191.9

91.6

85

190.2 191.0 191.1 170.0 195.6 113.4 189.8 190.4 190.4 180.2 196.5 115.6 186.6 186.6 187.3 180.0 192.9 129.7

90

193.5 194.7 193.5 190.5 196.5 145.2 193.2 194.0 194.0 193.4 196.2 152.3 191.5 192.2 191.4 192.1 194.0 161.4

Ambient Temperature (°F)
115
Air
Flow
CFM

4000

4500

5000

5500

Ent
DB
°F

67

73

MBH SHC

MBH SHC

125.9 115.6 153.3

177.8

55.8

80

137.6 137.6 154.4 115.9 179.0

83.1

85

88.3

154.5 154.5 158.9 143.5 179.8 110.1

90

168.6 168.6 169.3 167.4 180.8 137.7

75

132.7 125.6 158.2

180.4

54.5

80

147.7 147.7 159.7 125.2 181.4

84.8

85

164.1 164.1 166.5 155.1 182.2 116.3

94.1

90

176.1 176.1 176.4 176.3 183.2 146.8

75

139.5 135.4 162.3

182.0

52.6

80

155.6 155.6 164.6 134.3 182.9

87.6

85

170.4 170.4 171.8 163.3 183.6 121.0

90

180.9 180.9 180.9 180.9 184.7 153.1

75

145.6 143.4 165.6 104.6 183.0

51.6

80

162.2 162.2 168.3 142.1 183.9

89.0 Notes:

99.8

80

1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not
applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
184.1 184.1 184.2 184.2 186.5 161.7 2. All capacities shown are gross and have not considered indoor fan heat. To obtain net
cooling subtract indoor fan heat.
150.4 149.6 168.3 108.5 184.1 51.5
3. MBH = Total Gross Capacity
167.2 167.2 171.0 148.6 184.8 93.7 4. SHC = Sensible Heat Capacity

85

179.5 179.5 179.9 177.1 186.0 132.8 * stands for both downflow and horizontal unit.

90

185.5 185.7 186.3 186.4 187.8 168.8

85
75

24

61
MBH SHC

75

90

6000

Entering Wet Bulb (F)

175.2 175.2 176.2 170.7 184.8 126.0

PKGP-PRC012M-EN

Performance Data

Table 4.

Gross cooling capacities (MBh) 20 tons three phase WS*240E
Ambient Temperature (°F)
85

Air
Flow
CFM
6400

7200

8000

8800

9600

Ent
DB
°F

95

105

Entering Wet Bulb (F)
61

67

73

61

67

73

61

67

73

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

MBH SHC

75

231.1 183.1 268.4 137.9 289.8

80

235.6 220.5 270.5 174.4 293.4 114.9 213.9 209.8 254.8 169.7 282.0 114.4 194.5 194.4 233.8 162.8 266.8 111.7

77.1

208.1 173.6 253.0 133.2 279.2

76.0

183.1 163.6 232.4 126.5 264.7

75.0

85

247.9 247.9 273.1 211.7 297.1 153.0 233.1 233.1 256.8 206.6 284.9 152.1 217.4 217.4 236.3 199.8 269.0 149.2

90

266.0 266.0 276.3 249.1 300.8 190.8 253.6 253.6 260.8 244.3 288.0 189.7 238.1 238.1 241.6 236.3 271.5 186.7

75

242.5 197.1 274.8 142.3 292.9

80

247.6 238.6 277.5 183.8 297.1 115.8 227.3 226.2 261.8 179.8 286.4 115.6 209.7 209.7 241.8 174.2 271.7 114.5

85

262.8 262.8 280.9 225.7 301.5 158.1 248.8 248.8 265.0 221.7 290.1 158.4 233.0 233.0 245.7 216.1 274.7 156.5

73.3

219.0 187.9 259.9 138.5 283.2

74.2

194.4 178.4 239.9 132.8 269.1

72.5

90

279.8 279.8 286.0 268.1 305.8 200.4 267.3 267.3 270.9 263.1 294.0 200.7 253.1 253.1 254.3 253.2 278.1 199.5

75

251.1 209.8 279.7 146.5 295.4

80

258.3 254.4 283.0 192.7 299.9 117.4 240.8 240.6 267.8 189.7 289.8 117.8 222.4 222.4 249.6 185.1 275.6 117.0

85

274.0 274.0 287.2 239.1 304.5 164.0 260.7 260.7 271.9 236.4 294.0 164.5 245.2 245.2 253.4 231.5 279.0 163.6

70.6

229.7 202.0 265.1 143.6 285.9

70.7

204.3 192.2 247.0 139.0 272.5

70.2

90

290.9 290.9 293.8 284.4 309.4 210.2 278.4 278.4 279.8 277.3 298.5 210.9 263.8 263.8 264.2 264.2 283.2 210.9

75

258.4 222.0 283.4 150.7 297.2

80

266.2 265.3 287.2 201.2 302.1 120.4 251.2 251.2 272.7 199.1 292.5 120.1 233.8 233.8 254.5 195.4 278.7 120.1

85

283.3 283.3 292.2 251.8 307.1 170.5 270.0 270.0 277.7 250.1 296.9 170.3 254.9 254.9 260.0 246.0 282.6 171.1

69.0

237.8 214.9 269.4 148.5 288.1

69.4

212.9 204.9 251.4 144.7 275.1

69.2

90

298.9 298.9 300.3 296.3 312.4 219.9 287.3 287.3 288.0 287.6 302.1 221.9 273.0 273.0 273.3 273.3 287.4 222.7

75

263.4 233.2 286.3 154.9 298.8

80

273.7 273.6 290.6 209.2 303.9 123.4 259.6 259.6 276.6 208.6 294.5 123.2 242.4 242.4 258.5 205.2 281.0 123.0

85

290.4 290.4 296.3 263.8 309.1 176.8 277.9 277.9 282.6 263.4 299.2 177.8 262.7 262.7 265.5 258.0 285.3 178.3

90

304.8 304.8 305.5 304.1 314.5 229.2 294.2 294.2 294.4 294.4 304.9 232.6 280.3 280.3 280.6 280.6 290.7 234.1

68.8

243.6 226.7 272.9 153.4 289.9

67.5

220.3 216.0 255.4 150.4 277.1

68.5

Ambient Temperature (°F)
115
Air
Flow
CFM
6400

7200

8000

8800

Ent
DB
°F

61

67

73

MBH SHC

MBH SHC

MBH SHC

75

158.5 152.9 206.9 118.1 246.1

80

177.1 177.1 208.6 154.5 247.1 108.6

85

201.1 201.1 212.3 192.1 249.1 144.9

90

71.0

222.0 222.0 223.1 223.0 251.3 182.3

75

168.6 165.4 216.4 125.7 251.0

80

191.7 191.7 218.4 166.8 252.7 111.5

85

214.8 214.8 223.1 209.0 255.1 153.3

90

70.1

236.2 236.2 236.5 236.5 257.9 195.5

75

179.2 177.5 223.0 132.4 254.7

80

204.0 204.0 225.4 178.2 257.0 115.2

85

227.3 227.3 230.9 223.5 259.6 161.8

90

68.8

247.3 247.3 247.7 247.7 263.3 208.7

75

188.7 188.1 227.6 138.7 257.4

80

214.2 214.2 230.3 189.1 260.3 118.2 Notes:

67.5

80

1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not
applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
256.1 256.1 256.3 256.3 267.8 221.7 2. All capacities shown are gross and have not considered indoor fan heat. To obtain net
cooling subtract indoor fan heat.
197.1 197.0 231.8 145.0 259.8 67.1
3. MBH = Total Gross Capacity
223.4 223.4 235.9 200.1 262.9 122.0 4. SHC = Sensible Heat Capacity

85

245.1 245.1 246.0 245.3 266.7 178.3 * stands for both downflow and horizontal unit.

90

263.4 263.4 263.6 263.6 271.7 234.3

85
90
9600

Entering Wet Bulb (F)

75

237.3 237.3 239.4 236.4 263.6 170.1

PKGP-PRC012M-EN

25

Performance Data

Table 5.

Evaporator fan performance 12½ tons WS*150E downflow or horizontal
External Static Pressure (Inches of Water)
0.10

CFM

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor & Drive

4000

—

—

382

0.56

420

0.66

459

0.79

496

0.91

531

1.05

564

1.19

595

1.34

625

1.50

654

1.67

4500

—

—

410

0.73

446

0.85

479

0.97

514

1.11

548

1.26

578

1.40

610

1.56

639

1.72

666

1.89

5000

400

0.80

440

0.95

473

1.07

504

1.20

534

1.34

566

1.50

597

1.66

625

1.81

653

1.98

681

2.16

5500

431

1.03

470

1.19

502

1.34

531

1.48

559

1.62

586

1.77

615

1.95

643

2.12

670

2.30

695

2.47

6000

463

1.30

500

1.48

531

1.65

559

1.80

585

1.95

611

2.11

636

2.28

662

2.46

689

2.66

714

2.85

3HP Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor & High Static Drive Accessory

4000

682

1.83

708

1.99

734

2.16

758

2.32

782

2.49

804

2.66

826

2.83

847

3.01

867

3.19

886

3.38

4500

693

2.07

719

2.25

745

2.44

769

2.62

793

2.80

815

2.99

838

3.17

859

3.36

880

3.55

900

3.74

5000

707

2.34

732

2.53

757

2.72

780

2.92

804

3.13

826

3.33

848

3.54

870

3.74

891

3.95

911

4.15

5500

721

2.66

747

2.86

771

3.05

794

3.26

816

3.46

838

3.68

860

3.90

881

4.13

902

4.36

922

4.58

6000

738

3.04

760

3.22

784

3.43

808

3.65

831

3.86

852

4.08

873

4.30

893

4.53

913

4.77

933

5.01

5HP Oversized Motor & Drive
Notes:
1. Fan motor heat (MBH) = 3.15 x Fan BHP.
2. Data includes pressure drop due to wet coils and filters.
3. No accessories or options are included in pressure drop data.
4. Refer to Table 12, p. 29 to determine add’l static pressure drop due to other options/accessories.
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabulated data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.

26

PKGP-PRC012M-EN

Performance Data

Table 6.

Evaporator fan performance 15 tons WS*180E downflow or horizontal
External Static Pressure (Inches of Water)
0.10

CFM

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & Low Static Drive Accessory

3HP Standard Motor Drive

4800

397

0.75

435

0.88

469

1.00

501

1.13

533

1.28

566

1.43

596

1.59

625

1.74

655

1.92

682

2.09

5400

435

1.02

473

1.18

504

1.32

533

1.46

562

1.60

590

1.76

620

1.94

648

2.11

674

2.28

700

2.46

723 2.92(a)

6000

475

1.36

510

1.53

541

1.70

568

1.85

594

2.01

620

2.17

645

2.34

672

2.53

698

2.73

6600

514

1.76

549

1.96

578

2.15

604

2.33

629

2.49

653

2.66

676

2.84

699

3.02

722

3.23

747

3.44

7200

555

2.25

588

2.46

616

2.68

641

2.89

665

3.06

687 3.24(b) 709

3.43

730

3.62

751

3.82

772

4.02

5HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3HP Standard Motor & High Static Drive Accessory

5HP Oversized Motor & Drive

4800

708

2.27

734

2.46

758

2.66

782

2.86

806

3.06

829

3.25

850

3.45

872

3.65

893

3.85

913

4.04

5400

727

2.65

752

2.85

776

3.05

799

3.25

821

3.47

843

3.69

865

3.91

886

4.13

907

4.36

927

4.58

6000

747

3.11

770

3.30

794

3.51

817

3.73

839

3.95

861

4.17

881

4.40

902

4.63

922

4.87

942

5.12

6600

770

3.66

793

3.87

815

4.08

835

4.28

857

4.51

879

4.74

900

4.98

—

—

—

—

—

—

7200

794

4.25

817

4.49

839

4.73

860

4.96

—

—

—

—

—

—

—

—

—

—

—

—

Notes:
1. Fan motor heat (MBH) = 3.15 x Fan BHP.
2. Data includes pressure drop due to wet coils and filters.
3. No accessories or options are included in pressure drop data.
4. Refer to Table 12, p. 29 to determine add’l static pressure drop due to other options/accessories.
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabulated data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
(a) 3HP Standard Motor & High Static Drive Accessory
(b) 5-hp Oversized Motor & Field Supplied Fan Sheave BK160 x 1 3/16 with BX75 (DF) or BX90 (HZ) Belt Required.

PKGP-PRC012M-EN

27

Performance Data

Table 7.

Evaporator fan performance 20 tons WS*240E downflow or horizontal
External Static Pressure (Inches of Water)
0.10

CFM

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor Drive & low Static Drive Accessory

5HP Standard Motor Drive

6400

—

—

—

—

507

1.72

535

1.88

560

2.07

584

2.27

607

2.46

631

2.66

654

2.86

677

3.07

7200

—

—

519

2.10

549

2.30

576

2.48

600

2.67

623

2.88

644

3.10

665

3.32

686

3.54

707

3.76

8000

531

2.50

563

2.77

592

3.00

617

3.21

641

3.41

663

3.62

684

3.86

704

4.10

723

4.34

742

4.58

8800

578

3.26

607

3.56

634

3.83

659

4.08

683

4.31

704

4.54

724

4.77

744

5.01

762

5.27

779

5.54

9600

626

4.19

653

4.51

679

4.81

703

5.10

725

5.36

746

5.62

765

5.85

784

6.11

802

6.36

819

6.64

7.5HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
CFM

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5HP Standard Motor Drive

6400

699

3.30

721

3.52

742

3.75

762

3.98

780

4.20

798

4.42

815

4.66

832

4.89

849

5.12

866

5.36

7200

727

3.98

748

4.22

768

4.46

789

4.71

808

4.97

827

5.22

845

5.48

861

5.73

878

5.98

893

6.24

8000

760

4.82

779

5.07

798

5.32

816

5.57

834

5.83

853

6.11

871

6.38

889

6.67

906

6.95

923 7.23(a)

8800

797

5.81

814

6.07

831

6.34

848

6.60

865

6.88

882

7.15

898

7.42

—

—

—

—

—

—

9600

836

6.93

852

7.22

868

7.51

—

—

—

—

—

—

—

—

—

—

—

—

—

—

7.5HP Oversized Motor & Drive
Notes:
1. Fan motor heat (MBH) = 3.15 x Fan BHP.
2. Data includes pressure drop due to wet coils and filters.
3. No accessories or options are included in pressure drop data.
4. Refer to Table 12, p. 29 to determine add’l static pressure drop due to other options/accessories.
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabulated data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
6. For multi-speed or single zone VAV applications, minimum "full" speed airflow must be set to 6800 cfm or higher to prevent VFD overheating during
heating operation.
(a) 7.5-hp Oversized Motor & Field Supplied Motor Sheave 1VP50 x 1 1/8 Required.

Table 8.

Standard motor & drive/fan speed (Rpm)
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
Open
Open
Open
Open
Open

1Turn
Open

Tons

Unit Model No.

12½

WS*150E3,4,W

500

537

574

611

648

685

Closed
N/A

15

WS*180E3,4,W

500

537

574

611

648

685

N/A

20

WS*240E3,4,W

605

650

695

739

784

829

N/A

1Turn
Open

Closed

Note: Factory set at 3 turns open.

Table 9.
Tons

28

Standard motor & low static fan drive
Unit Model No.

6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
Open
Open
Open
Open
Open

12½

WS*150E3,4,W

379

407

435

463

491

519

N/A

15

WS*180E3,4,W

379

407

435

463

491

519

N/A

20

WS*240E3,4,W

506

544

581

619

656

694

N/A

PKGP-PRC012M-EN

Performance Data

Table 10. Standard motor & high static drive accessory/fan speed (rpm)
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
Open
Open
Open
Open
Open

Tons

Unit Model No.

12½

WS*150E3,4,W

685

722

759

796

15

WS*180E3,4,W

685

722

759

796

1Turn
Open

Closed

833

870

N/A

833

870

N/A

1Turn
Open

Closed

Table 11. Oversized motor & drive/fan speed (rpm)
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
Open
Open
Open
Open
Open

Tons

Unit Model No.

12½

WS*150E3,4,W

695

747

798

850

901

953

N/A

15

WS*180E3,4,W

695

747

798

850

901

953

N/A

20

WS*240E3,4,W

694

739

784

829

874

919

N/A

Table 12. Static pressure drops through accessories (inches water column)
Standard
Economizer
with OA/RA
Dampers(c)

Tons
12½

15

Unit Model
No.
WS*150E

WS*180E

WSH240E
20
WSD240E

CFM

Low Leak
Economizer
with OA/RA
Dampers(d)

2”
2”
Standard MERV 8 MERV 13 100% 100% 100% 100%
Filters(a) Filters(b) Filters(b)
OA
RA
OA
RA
5-12

Electric Heater
Accessory (KW)(e)
1423

36

54

72

4000

0.02

0.04

0.08

0.20

0.02

0.16

0.10

—

0.03

0.03

0.04

—

5000

0.03

0.05

0.11

0.26

0.03

0.24

0.16

—

0.04

0.05

0.06

—

6000

0.05

0.07

0.14

0.35

0.04

0.33

0.24

—

0.06

0.07

0.09

—

4800

0.03

0.05

0.10

0.24

0.03

0.22

0.15

—

0.04

0.04

0.05

—

6000

0.05

0.07

0.14

0.35

0.04

0.33

0.24

—

0.06

0.07

0.08

—

7200

0.07

0.09

0.17

0.42

0.05

0.45

0.35

—

0.09

0.10

0.12

—

6400

0.04

0.01

0.11

0.22

0.04

—

—

—

—

0.06

0.08

0.09

8000

0.06

0.09

0.14

0.31

0.05

—

—

—

—

0.10

0.12

0.14

9600

0.09

0.12

0.18

0.44

0.07

—

—

—

—

0.14

0.17

0.20

6400

0.05

0.08

0.12

0.22

0.04

0.37

0.27

—

—

0.06

0.08

0.09

8000

0.08

0.10

0.15

0.31

0.05

0.54

0.43

—

—

0.10

0.12

0.14

9600

0.11

0.14

0.19

0.44

0.07

0.75

0.62

—

—

0.14

0.17

0.20

(a) Tested with: 2” filters 12 - 20 tons.
(b) Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
(c) OA = Outside Air and RA = Return Air.
(d) OA = Outside Air and RA = Return Air.
(e) Nominal KW ratings at 240, 480, 600 volts.

PKGP-PRC012M-EN

29

Performance Data

Table 13. 12½ tons three phase heating capacities (net) WS*150E3, E4, EW at 5000 CFM
Outdoor
Temp (°F)
70% RH

Integrated Heating Capacity (MBh/1000)
at Indicated Dry Bulb Temp (°F)

Total Power in Kilowatts at Indicated
Dry Bulb Temp (°F)

60

70

75

80

60

70

75

80

-8

50.9

48.5

47.2

45.9

9.6

10.3

10.8

11.3

-3

56.9

54.5

53.4

52.1

9.7

10.4

10.9

11.4

2

63.3

60.6

59.3

58.0

9.7

10.5

10.9

11.4
11.5

7

69.7

66.6

65.5

64.0

9.8

10.6

11.0

12

76.1

72.5

71.7

70.2

9.9

10.7

11.1

11.6

17

82.0

79.0

77.3

76.9

10.0

10.8

11.3

11.8

22

89.7

86.5

84.8

83.5

10.1

10.9

11.3

11.9
12.0

27

96.8

93.5

91.8

90.2

10.1

11.0

11.5

32

104.6

100.8

99.1

97.2

10.2

11.1

11.6

12.1

37

112.0

108.1

106.1

104.3

10.3

11.2

11.7

12.2

42

129.1

124.4

122.2

120.0

10.5

11.4

11.9

12.5

47

148.4

142.8

140.1

137.4

10.7

11.6

12.1

12.7

52

156.7

151.0

148.0

145.2

10.8

11.7

12.2

12.8

57

166.0

159.8

156.8

153.6

10.9

11.9

12.4

12.9

62

175.5

168.6

165.3

162.0

11.0

12.0

12.5

13.1

67

185.2

177.6

174.5

170.0

11.2

12.1

12.7

13.2

72

193.6

185.7

181.6

177.6

11.3

12.3

12.8

13.4

Notes:
1. For other airflow conditions, see heating capacity correction factor Net Heating Capacity and Power Input include indoor fan heat at
nominal CFM and 0.35 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Heating capacities and powers are integrated to include the effects of defrost in the frost region.
3. All heating capacities and power (kW) are at 70% OD relative humidity.

30

PKGP-PRC012M-EN

Performance Data

Table 14. 15 tons three phase heating capacities (net) WS*180E3, E4, EW at 6000 CFM
Outdoor
Temp (°F)
70% RH

Integrated Heating Capacity (MBh/1000)
at Indicated Dry Bulb Temp (°F)

Total Power in Kilowatts at Indicated
Dry Bulb Temp (°F)

60

70

75

80

60

70

75

80

-8

56.3

54.8

54.0

53.2

10.5

11.5

12.0

12.5

-3

62.8

61.1

60.2

59.4

10.7

11.7

12.1

12.7

2

69.5

67.6

66.7

65.7

10.9

11.8

12.4

12.9

7

76.2

71.1

69.9

70.8

11.1

12.0

12.5

14.0

12

82.9

73.0

76.9

77.0

12.0

12.1

12.7

13.7

17

88.2

85.4

84.0

82.7

11.4

12.4

12.9

13.5

22

95.9

92.8

91.4

89.9

11.6

12.5

13.1

13.7

27

103.8

100.6

98.9

97.3

11.8

12.7

13.3

13.9

32

112.3

109.0

107.1

105.5

11.9

13.0

13.5

14.1

37

120.8

117.1

115.4

113.7

12.1

13.2

13.8

14.4

42

148.0

143.6

141.4

139.1

12.2

13.3

13.9

14.5

47

179.2

173.8

170.8

168.0

12.6

13.6

14.2

14.8

52

190.8

185.3

182.3

179.0

12.8

13.9

14.4

15.0

57

204.1

197.7

194.2

191.5

13.1

14.1

14.7

15.3

62

217.8

210.6

207.5

203.7

13.4

14.4

15.0

15.6

67

233.5

225.5

221.1

217.0

13.7

14.8

15.4

16.0

72

247.8

239.7

235.5

231.2

14.1

15.2

15.8

16.4

Notes:
1. For other airflow conditions, see heating capacity correction factor Net Heating Capacity and Power Input include indoor fan heat at
nominal CFM and 0.35 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Heating capacities and powers are integrated to include the effects of defrost in the frost region.
3. All heating capacities and power (kW) are at 70% OD relative humidity.

PKGP-PRC012M-EN

31

Performance Data

Table 15. 20 tons three phase heating capacities (Net) WS*240E3, E4, EW at 8000 CFM
Outdoor
Temp (°F)
70% RH

Integrated Heating Capacity (MBh/1000)
at Indicated Dry Bulb Temp (°F)

Total Power in Kilowatts at Indicated
Dry Bulb Temp (°F)

60

70

75

80

60

70

75

80

-8

80.6

78.4

77.6

76.8

15.1

15.9

16.4

16.9

-3

87.5

85.3

84.5

83.4

15.3

16.0

16.5

17.0

2

96.3

93.9

92.8

91.7

15.4

16.2

16.7

17.2

7

106.0

103.2

102.3

101.0

15.5

16.3

16.8

17.3

12

118.3

116.2

115.5

114.7

15.7

16.5

17.0

17.5

17

131.1

128.2

127.4

126.3

15.9

16.7

17.2

17.7

22

142.9

140.3

138.8

137.2

16.1

16.9

17.4

17.9

27

154.1

151.3

150.0

148.6

16.4

17.3

17.8

18.3

32

165.5

162.4

161.2

159.6

16.5

17.4

17.9

18.4

37

180.9

177.6

175.7

174.5

16.8

17.7

18.2

18.7

42

196.5

191.9

189.8

188.2

17.0

17.9

18.4

18.9

47

213.3

209.1

207.0

205.4

17.1

18.0

18.5

19.0

52

228.9

224.2

221.4

219.8

17.4

18.3

18.8

19.3

57

243.4

237.7

235.6

233.0

17.8

18.8

19.3

19.8

62

261.9

255.7

252.6

250.0

20.0

21.1

21.6

22.1

67

279.6

272.0

268.9

265.3

20.1

21.2

21.7

22.2

72

298.5

291.1

287.9

283.8

20.4

21.5

22.0

22.6

Notes:
1. For other airflow conditions, see heating capacity correction factor Net Heating Capacity and Power Input include indoor fan heat at
nominal CFM and 0.35 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Heating capacities and powers are integrated to include the effects of defrost in the frost region.
3. All heating capacities and power (kW) are at 70% OD relative humidity.

Table 16. Heating capacity correction factors
% Variation of Nominal CFM

- 20

- 10

0

+ 10

+ 20

Total Gross Capacity Multiplier

0.96

0.98

1.0

1.01

1.02

Table 17. Auxiliary electric heat capacity
Total(a)

Tons

12½, 15

20

Unit

KW

Model No.

Input(b)
18.00

WS*150E3, E4, EW
WS*180E3, E4, EW

WS* 240E3, E4, EW

MBh

Stage 1
No. of

KW

Output
61.00

36.00

Stage 2
MBh

KW

MBh

Stages

Input(b)

Output

Input(b)

Output

1

18.00

61.00

123.00

2

18.00

61.00

18.00

61.00

54.00

184.00

2

36.00

123.00

18.00

61.00

36.00

123.00

2

18.00

61.00

18.00

61.00

54.00

184.00

2

36.00

123.00

18.00

61.00

72.00

246.00

2

36.00

123.00

36.00

123.00

-

-

(a) Heaters are rated at 240v,380v,480v and 600v. For other than rated voltage, CAP= (voltage/rated voltage)2 x rated cap.
(b) For all input/output categories, does not include fan power or heat.

32

PKGP-PRC012M-EN

Performance Data

Table 18. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal

Distribution

Capacity

Voltage

Voltage

Multiplier

208

0.75

230

0.92

240

1.00

440

0.84

240

480

600

460

0.94

480

1.00

540

0.81

575

0.92

600

1.00

Table 19. Air temperature rise across electric heaters (°F)

KW

Stages

12½ Ton
5000 CFM

15 Ton
6000 CFM

20 Ton
8000 CFM

Three Phase
WS*150E

Three Phase
WS*180E

Three Phase
WS*240E

9.00

1

-

-

-

17.30

1

-

-

-

18.00

1

11.4

9.5

-

27.00

2

-

-

-

36.00

2

23.0

19.0

14.2

54.00

2

34.1

28.4

21.3

72.00

2

-

-

28.5

Table 20. Electric heater temperature rise correction factors

PKGP-PRC012M-EN

% Variation From Nominal CFM

- 20

- 15

- 10

-5

0

+5

+10

+15

+20

Temperature Rise Multiplier

1.25

1.17

1.11

1.05

1.00

0.95

0.91

0.87

0.83

33

Controls
Field Installed Control Options
Zone Sensors
Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control
to enable Single Zone VAV functionality.
Zone Sensors are the building occupant’s comfort control devices forVoyager™ units with
ReliaTel:

Manual Changeover

Manual/Automatic
Changeover

Manual/Automatic
Changeover

Heat, Cool or Off System
Switch. Fan Auto or Off
Switch. One temperature
setpoint lever

Auto, Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
Two temperature setpoint
levers

Auto, Heat, Cool or Off System
Switch. Fan Auto or Off
Switch. Two temperature
setpoint levers. Status
Indication LED lights, System
On, Heat, Cool, or Service.

Manual/Automatic
Changeover

Remote Sensor

Integrated Comfort™
System

Auto, Heat, Cool or Off System
Switch. Fan Auto or Off
Switch. Two temperature
setpoint levers

Sensor(s) available for all zone
sensors to provide remote
sensing capabilities

Sensor(s) available with
optional temperature
adjustment and override
buttons to provide central
control through a Trane
Integrated Comfort™system.

RA Remote Sensor
Return Air Remote Sensor which can be mounted in the return air duct to report return air
temperature.

34

PKGP-PRC012M-EN

Controls

Programmable Night
Setback

Touchscreen
Programmable
Thermostat (2H/2C)
MON

TUE

WED

THU

FRI

SAT

FAN
ON
AUTO
CIRC

Auto or manual changeover
with seven-day
programming. Keyboard
selection of Heat, Cool, Fan,
Auto, or On. All
programmable sensors have
System On, Heat, Cool,
Service LED/indicators as
standard. Night Setback
Sensors have one (1)
Occupied, one (1) Unoccupied, and one (1)
Override program per day.

CO2 Sensor

SUN

HEAT

SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO

RESET

DONE

EDIT

CANCEL
PERIOD

DEHUMIDIFIER

COOL

PM

WAKE

LEAVE

RETURN

SLEEP

CANCEL

Two Heat/Two Cool
programmable thermostat
with touch screen digital
display. Menu-driven
programming. Effortless setup. Program each day
separately with no need to
copy multiple days. All
programming can be done on
one screen. Easy to read and
use. Large, clear backlit digital
display.

The CO2 sensor shall have
the ability to monitor the
concentration (parts per
million, ppm) of CO2 (Carbon
Dioxide) in the air. As the CO2
concentration changes, the
outside air damper
modulates to meet the
current ventilation needs of
the zone.

Digital Display Programmable
Thermostat (3H/2C)

Digital Display Thermostat
(3H/2C)

Two Heat/Two Cool auto changeover digital
display thermostat. 7-day programmable
stat with night setback shall be available

Three Heat, Two Cool auto changeover digital
display thermostat.

Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to reduce the total number of remote sensors to obtain space
temperature averaging. This sensor should be utilized with ReliaTel controls.

Room Remote Sensor
Space Remote Sensor which can be mounted on the wall to report/control from a remote location
in the space.

PKGP-PRC012M-EN

35

Electrical Data
Table 21. Unit wiring
Standard Indoor Motor

Tons

Unit Model #

12½

15

20

Oversize Indoor Fan Motor

Max Fuse Size or
Max Fuse Size or
Unit Operating Minimum Circuit
Max Circuit
Minimum Circuit
Max Circuit
Voltage Range
Ampacity
Breaker(a)
Ampacity
Breaker(a)

WS*150E3

187-253

68

80

74

WS*150E4

414-506

32

40

35

90
45

WS*150EW

517-633

25

30

27

30

WS*180E3

187-253

74

90

80

100

WS*180E4

414-506

36

45

39

50

WS*180EW

517-633

30

35

32

40

WS*240E3

187-253

116

150

124

150

WS*240E4

414-506

56

70

59

70

WS*240EW

517-633

45

60

48

60

(a) HACR type circuit breaker per NEC.

Table 22. Unit wiring with electric heat (single point connection) — standard refrigeration system (downflow and
horizontal)
Standard Indoor Motor Oversize Indoor Motor

Tons

Unit Model
Number

Heater Model
Number(a)

Heater kW
Rating

Control
Stages

MCA

Max Fuse Size
or Max Circuit
Breaker

MCA

Max Fuse Size
or Max Circuit
Breaker(b)

208/230 Volts Three Phase

12½

15

20

WS*150E3

WS*180E3

WS*240E3

AYDHTRK318/AYHHTRM318

13.5/18.0

1

115/123

125/125

121/129

125/150

AYDHTRK336/AYHHTRM336

27.0/36.0

2

168/183

175/200

174/189

175/200

AYDHTRK354/AYHHTRM354

40.5/54.0

2

209/198

225/200

215/204

225/225

AYDHTRK318/AYHHTRM318

13.5/18.0

1

121/129

125/150

127/135

150/150

AYDHTRK336/AYHHTRM336

27.0/36.0

2

168/183

175/200

174/189

175/200

AYDHTRK354/AYHHTRM354

40.5/54.0

2

215/204

225/225

221/210

225/225

AYDHTRL336/AYHHTRN336

27.0/36.0

2

210/225

225/225

218/233

225/250

AYDHTRL354/AYHHTRN354

40.5/54.0

2

257/246

300/250

265/254

300/300

AYDHTRK372/AYHHTRN372

54.0/72.0

2

267/290

300/300

275/298

300/300

70

460 Volts Three Phase

12½

15

20

36

WS*150E4

WS*180E4

WS*240E4

AYDHTRK418/AYHHTRM418

18

1

60

60

63

AYDHTRK436/AYHHTRP436

36

2

87

90

90

90

AYDHTRK454/AYHHTRM454

54

2

97

100

100

100

AYDHTRK418/AYHHTRM418

18

1

64

70

67

70

AYDHTRK436/AYHHTRM436

36

2

91

100

94

100

AYDHTRK454/AYHHTRM454

54

2

101

110

104

110

AYDHTRL436/AYHHTRN436

36

2

111

125

114

125

AYDHTRL454/AYHHTRN454

54

2

121

125

125

125

AYDHTRK472/AYHHTRN472

72

2

143

150

146

150

PKGP-PRC012M-EN

Electrical Data

Table 22. Unit wiring with electric heat (single point connection) — standard refrigeration system (downflow and
horizontal) (continued)
Standard Indoor Motor Oversize Indoor Motor

Tons

Unit Model
Number

Heater Model
Number(a)

Heater kW
Rating

Control
Stages

MCA

Max Fuse Size
or Max Circuit
Breaker

MCA

Max Fuse Size
or Max Circuit
Breaker(b)

575 Volts Three Phase

12½

15

20

WS*150EW

WS*180EW

WS*240EW

AYDHTRKW18 (AYDHTRLW18)(a)
/AYHHTRMW18 (AYHHTRPW18)

18

1

47

50

49

50

AYDHTRKW36/AYHHTRMW36
(AYHHTRRW36)(a)

36

2

69

70

71

80

AYDHTRKW54/AYHHTRMW54

54

2

77

80

79

80

AYDHTRKW18 (AYDHTRMW18)(a)
/AYHHTRMW18 (AYHHTRQW18)

18

1

52

60

54

60

AYDHTRKW36/AYHHTRMW36
(AYHHTRSW36)(a)

36

2

74

80

76

80

AYDHTRKW54/AYHHTRMW54

54

2

82

90

84

90

AYDHTRLW36/AYHHTRNW36

36

2

89

90

92

100

AYDHTRLW54/AYHHTRNW54

54

2

97

110

100

110

AYDHTRKW72/AYHHTRNW72

72

2

115

125

118

125

(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.
(b) Values do not include power exhaust accessory.
* Indicates both downflow and horizontal units.

Table 23. Electrical characteristics - power exhaust accessory
Tons

Accessory Operating
Voltage

Phase

HP

RPM

208-230

1

3/4

1040

6.6

460

1

3/4

1040

3.2

8.4

575

1

3/4

1040

2.1

5.2

12½, 15, 20

Amps FLA LRA
13.5

Table 24. Electrical characteristics - evaporator fan motors - 60 cycle
Standard Evaporator Fan Motor

Oversized Evaporator Fan Motor

Amps
Tons
12½

15

20

Amps

Unit Model
No.

No.

Volts

Phase

HP

FLA

LRA

No.

Volts

Phase

HP

FLA

LRA

WS*150E3

1

208-230

3

3.00

10.6

81.0

1

208-230

3

5.00

16.7

109.8

WS*150E4

1

460

3

3.00

4.8

40.5

1

460

3

5.00

7.6

54.9

WS*150EW

1

575

3

3.00

3.9

31.0

1

575

3

5.00

6.1

41.6

WS*180E3

1

208-230

3

3.00

10.6

81.0

1

208-230

3

5.00

16.7

109.8

WS*180E4

1

460

3

3.00

4.8

40.5

1

460

3

5.00

7.6

54.9

WS*180EW

1

575

3

3.00

3.9

31.0

1

575

3

5.00

6.1

41.6
120.4

WS*240E3

1

208-230

3

5.00

16.7

109.8

1

208-230

3

7.50

24.2

WS*240E4

1

460

3

5.00

7.6

54.9

1

460

3

7.50

11.0

74.0

WS*240EW

1

575

3

5.00

6.1

41.6

1

575

3

7.50

9.0

60.0

PKGP-PRC012M-EN

37

Electrical Data

Table 25. Electrical characteristics — compressor motor and condenser motor — 60 cycle
Compressor Motors

Condenser Fan Motors
Amps(a)

Tons
12½

15

20

Amps

Unit Model
Number

No.

Volts

Phase

HP(b)

RPM

RLA

LRA

No.

Phase

HP

FLA

LRA

WS*150E3

2

208-230

3

5.6

3450

22.4

149

2

1

0.5

3.2

8.8

WS*150E4

2

460

3

5.6

3450

10.6

75

2

1

0.5

1.6

3.8

WS*150EW

2

575

3

5.6

3450

7.9/7.7

54

2

1

0.5

1.3

3.2

WS*180E3

2

208-230

3

6.9

3450

25

164

2

1

0.5

3.2

8.8

WS*180E4

2

460

3

6.9

3450

12.5/12.2

100

2

1

0.5

1.6

3.8

WS*180EW

2

575

3

6.9

3450

10.3/10.1

78

2

1

0.5

1.3

3.2

WS*240E3

2

208-230

3

10.4

3450

39.1

267

2

1

1

5.0

14.4

WS*240E4

2

460

3

10.4

3450

17.3

142

2

1

1

2.5

5.8

WS*240EW

2

575

3

10.4

3450

15.4

103

2

1

1

2

5.1

(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
(b)HP for each compressor.
*Indicates both downflow and horizontal units.

38

PKGP-PRC012M-EN

Dimensional Data
Figure 2.

Heat pump models - 12½ - 20 tons

85 5/16"
2167MM
122 5/16"
3107MM

13/16"
20MM

FILTER
ACCESS DOOR
HORIZONTAL

54" (1372MM) - 12.5-15T UNITS
64 1/8" (1629MM) - 20T UNITS

1"
25.4MM
6 7/16"
163.51MM

DOWNFLOW CONDENSATE
DRAIN CONN 1" (25.4MM) NPT

48 1/2"
1231.90MM
56"
1422MM

SINGLE POINT
POWER ENTRY

33 3/16"
843MM
7/8" (22.23MM) DIA. HOLE
(UNIT CONTROL WIRE)

6 13/16"
173MM

121 11/16"
3091MM

8 15/16"
227MM
2 11/16"
68.26MM

84 3/16"
2154MM

SERVICE GAUGE
PORT ACCESS

3" (76MM) DIA HOLE
(UNIT POWER WIRE)

* All dimensions are in inches/millimeters.

PKGP-PRC012M-EN

39

Dimensional Data

Figure 3.

Heat pump models - 12½ - 20 tons

* All dimensions are in inches/millimeters.

Figure 4.

Heat pump models - 12½ - 20 tons

* All dimensions are in inches/millimeters.

40

PKGP-PRC012M-EN

Dimensional Data

Figure 5.

Heat pump models - 12½ - 20 tons

9

1”
25.4 MM
CURB FLANGE
LONG SIDES
SHORT SIDES

* Duct flanges mount 7-7/16" down inside the curb on the 1-1½ curb flanges.
Roofcurb is intended for downflow use only.
* All dimensions are in inches/millimeters.

Figure 6.

Heat pump models - 12½ - 20 tons

* All dimensions are in inches/millimeters.

PKGP-PRC012M-EN

41

Dimensional Data

Figure 7.

Downflow & horizontal condensate locations

Table 26. Heat pump units
Condensate Drain Location
Downflow Only
Tons

A

B

C

D

F

12½, 15, 20

26 7/16

28 3/4

19 15/16

4 1/4

4 1/4

G

H

76 5/16 68 11/16

Condensate
Drain Size

Downflow
J

Horizontal
K

1 NPT

26 3/4

5 3/8

Table 27. Swing clearances
Unit Model #

A

B

C

D

E

WSD 150-240

29 1/2

56

38 1/2

18 1/2

N/A

WSH 150-240

29 1/2

N/A

38 1/2

18 1/2

14

Note: All dimensions are in inches.

TOP VIEW SHOWING THROUGH THE BASE
ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

B

6 7/8"
SWING RADIUS (E)
HORIZONTAL FILTER
ACCESS PANEL

SWING RADIUS (A)
ID SECTION
ACCESS PANEL
SWING RADIUS (D)
ID FAN SECTION
ACCESS PANEL

42

THROUGH THE
BASE ELECTRICAL

SWING RADIUS (C)
OD SECTION
ACCESS PANEL

PKGP-PRC012M-EN

Dimensional Data

Figure 8. Fresh air hood (horizontal units)

Figure 9. Fresh air hood (downflow units)

Figure 10. Power exhaust - downflow economizers

Figure 11. Power exhaust - downflow economizers - side view

C
POWER EXHAUST with DOWNFLOW
ECONOMIZERS only, SIDE VIEW

Figure 12. Economizer - horizontal units

Figure 13. Economizer - downflow units

Note: When applying economizer to horizontal units, connected
ductwork must be run full size to allow proper operation of
economizer damper.

Table 28. Power exhaust dimensions
Unit Model #

A

B(a)

C(b)

WS* 150-240

19½

64¾

39

(a) Horizontal dimension only. Downflow economizer is width of
end panel.
(b)Power exhaust is applied on downflow economizer only.

PKGP-PRC012M-EN

43

Weights
Table 29. Accessory net weights (lbs)
Std
Economizer
(a)

Unit Model
No.

Tons

Low Leak
Economizer

Outside Air
Damper

Power
Oversized High
Moto- Exhaust Roof
Motor
Static
(b)
Manual rized
Curb
Adder
Drive

Net

Ship

Net

12½, 15,
WSD150-240E
20

80

265

250

32

75

95

235

5

10

12½, 15,
WSH150-240E
20

65

210

-

32

75

-

-

5

15

(a) Net weight should be added to unit weight when ordering factory installed economizer or oversize motor.
(b) Downflow only.

Table 30. Electric heaters weights
Electric Heaters(a)(b)
Tons

Unit Model No.

All Zone
Sensors

5-18 kW
240/480V

23-36 kW
240/480V

54 kW
240/480V

72 kW
240/480V

12½-20

WS*150E, 180E, 240E

1

28/22

33/27

40/32

43/34

(a) For 600V heaters net weights are same as 480V heaters.
(b) To estimate shipping weight add 5 lbs to net weight.

Table 31. Variable frequency drive weights
Motor Size

WSD150-240E

WSH150-240E

3(a) & 5 HP

32

34

63

65

7.5

HP(b)

(a) 3 HP motors not applicable to WS*240E units.
(b) WS*240E units only.

Figure 14. Center of gravity

44

PKGP-PRC012M-EN

Weights

Table 32. Maximum unit & corner weights (lbs) and center of gravity dimensions (In.)
Maximum Weights
(Lbs)
Tons

Unit Model No. Shipping

Corner Weights (Lbs)

Center of Gravity (In.)

Net

A

B

C

D

Length

Width

12½

WS*150E

2430

1978

633

514

376

455

56

36

15

WS*180E

2435

1982

634

515

377

456

56

36

20

WS*240E

2566

2107

674

485

400

590

57

35

Table 33. Factory installed options (FIOPS) net weights (lbs)(a)(b)(c)
Accessory

High Efficiency Motors(d)

Weight

Unit Model No.

49

WS*150-180 standard size motor

36

WS*240 standard size motor
WS*150-180 oversized motor

0

WS*240 oversized size motor

Hinged Doors

27

All WS* units

Powered Convenience Outlet

38

All WS* units

Through the Base Electrical

23

All WS* units

5

All WS* units except those with 54&72 kW heaters & 208/230V

Unit Mounted Circuit Breaker

Unit Mounted Disconnect
Smoke Detectors (Supply/Return)
Tool-less Hail Guard
Stainless Steel Drain Pan

10

All WS* units with 54&72 kW heaters & 208/230V

5

All WS* units except those with 54&72 kW heaters & 208/230V

10

All WS* units with 54&72 kW heaters & 208/230V

5

All WS* units

43

WS*150,180

51

WS*240

8.1

All WS* units

(a) Weights for FIOP accessories not listed are < 5 lbs.
(b) Net weight should be added to unit weight when ordering factory installed accessories.
(c) See Table 29, p. 44 for standard factory installed economizer and oversized motors.
(d) Standard factory installed motors are already included in unit net and shipping weights. Values shown for high
efficiency motors are in addition to the standard motor weight.
* Indicates both downflow and horizontal units.

PKGP-PRC012M-EN

45

Typical Wiring

46

PKGP-PRC012M-EN

Typical Wiring

PKGP-PRC012M-EN

47

Typical Wiring

48

PKGP-PRC012M-EN

Typical Wiring

PKGP-PRC012M-EN

49

Jobsite Connections
Table 34. Zone sensors - typical number of wires
Zone
Sensors
A

Manual Changeover.....................................................................4
Manual/Auto Changeover.............................................................5
Manual/Auto Changeover with Status Indication LED’s....................10
Programmable Night Setback with Status Indication LED’s...............7

Thermostats
B

3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)

DISCONNECT
SWITCH
(BY OTHERS)

B
ZONE SENSOR OR
THERMOSTAT

A
ROOFTOP
UNIT

Notes:

50

•

For specific wiring information, see the installation instructions.

•

All wiring except power wires is low voltage.

•

All customer-supplied wiring should be copper and must conform to NEC or CEC and local
electrical codes.

•

Wiring shown dotted is to be furnished and installed by the customer.

•

Zone sensors are required for units configured for Single Zone VAV indoor fan system control
in order to enable Single Zone VAV functionality.

PKGP-PRC012M-EN

Mechanical Specifications
General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between
115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be
rated in accordance with ARI testing procedures. All units shall be factory assembled, internally
wired, fully charged with R-410A, and 100% run tested to check cooling operation, fan and blower
rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be
colored and numbered for simplified identification. Units shall be UL listed and labeled, classified
in accordance to UL 1995/C 22.2, 236-05 3rd Edition.

Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces
shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit’s
surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet
construction shall allow for all maintenance on one side of the unit. In order to ensure a water and
air tight seal, service panels shall have lifting handles and no more than three screws to remove.
All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch,
1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the
downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The
downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than
the raised 11/8 inch high supply/return openings to provide an added water integrity precaution,
if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane
lifting.

Unit Top
The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to
prevent water leakage.

Filters
Two inch standard filters shall be factory supplied on all units. Optional two inch pleated MERV 8
and MERV 13 filters with filter removal tool shall be available.

Compressors
External high pressure cutout shall be provided on all 15 and 20 models. Low pressure switches
shall be standard. All units shall have direct-drive, hermetic, scroll type compressors with
centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization
range of plus or minus 10% of nameplate voltage. Internal overloads shall be provided with the
scroll compressors. Crankcase heaters shall be utilized with all scroll compressors.

Refrigerant Circuits
Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices,
service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall
be provided for replacement suction line driers.

Evaporator and Condenser Coils
Internally finned, 5/16” copper tubes mechanically bonded to a configured aluminum plate fin shall
be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. All coils are
pressure and leak tested at minimum of 450 psig. The completely assembled refrigerant system
is leak tested at a minimum of 240 psig with a refrigerant and nitrogen mixture. All dual compressor
units shall have intermingled evaporator coils. Sloped condensate drain pans are standard. Patentpending 1+1+1 condenser coil, permanently gapped for easy cleaning is available.

PKGP-PRC012M-EN

51

Mechanical Specifications

Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the
vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have builtin thermal overload protection.

Indoor Fan
Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with
standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and
motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for
high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).

Controls
Unit shall be completely factory- wired with necessary controls and contactor pressure lugs or
terminal block for power wiring. Unit shall provide an external location for mounting a fused
disconnect device. ReliaTel controls shall be provided for all 24-volt control functions. The resident
control algorithms shall make all heating, cooling, and/or ventilating decisions in response to
electronic signals from sensors measuring indoor and outdoor temperatures. The control
algorithm maintains accurate temperature control, minimizes drift from set point, and provides
better building comfort. A centralized control shall provide anti-short cycle timing and time delay
between compressors to provide a higher level of machine protection.

Defrost Controls
Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin
to significantly reduce unit capacity.

Discharge Line Thermostat
A bi-metal element discharge line thermostat is installed as a standard option on the discharge line
of each system. This standard option provides extra protection to the compressors against high
discharge temperatures in case of loss of charge, extremely high ambient and other conditions
which could drive the discharge temperature higher. Discharge line thermostat is wired in series
with high pressure control. When the discharge temperature rises above the protection limit, the
bi-metal disc in the thermostat switches to the off position, opening the 24 VAC circuit. When the
temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit,
providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel
control must be manually reset to resume operation on that stage.

Phase Monitor
The Phase Monitor is a 3 phase line monitor module that protects against phase loss, phase
reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has
an operating input voltage range of 190-600 VAC, and LED indicators for ON and FAULT. There are
no field adjustments and the module will automatically reset from a fault condition.

Variable Frequency Drive
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed
modulation. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are
quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass
if required. Bypass control will simply provide full nominal airflow in the event of drive failure.

52

PKGP-PRC012M-EN

Mechanical Specifications

Factory Installed Options
Black Epoxy Pre-Coated Coils
The black epoxy coils have a thermoset vinyl coating that is bonded to the aluminum fin stock prior
to the fin-stamping process. The pre-coated coils are an economical option for protection in mildly
corrosive environments.

Condensate Overflow Switch
This option shall shut the unit down in the event that a clogged condensate drain line prevents
proper condensate removal from the unit.

Fault Detection & Diagnostics (FDD)
This offering meets the mandatory requirement of Title 24. This option provides detection of the
following faults: Air temperature sensor failure/fault, not economizing when it should,
economizing when it should not, damper not modulating, and excessive outdoor air. The FDD
system shall be certified by the Energy Commission as meeting the requirements.

High Efficiency Motors
This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

High Short Circuit Current Rating
Unit shall be provided with electrical subsystem that will withstand fault currents up to 65kA (208/
230, 460 VAC) or 25kA (575 VAC) compliant with UL 1995 and NEC 440.4 (B). Each compressor circuit
and the indoor fan shall have dedicated overcurrent protection. Three phase motors shall be
protected by Class J time delay fuses. Single phase motors shall be protected by Class CC time
delay fuses. All transformers shall also be protected with Class CC time delay fuses. Contactors
shall be din rail mounted.

Hinged Access Doors
Sheet metal hinges are available on the Filter, Evaporator, ID Fan and Compressor/Control Access
Doors. This option is available on all models.

Horizontal Side Access with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through
the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the
unit with access through a swinging door. Factory wiring will be provided from the switch to the
unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized
per NEC and UL guidelines, and be agency recognized by UL/CSA.

Horizontal Side Access with Disconnect Switch
Three-pole, molded case, disconnect switch with provisions for through the base electrical
connections are available. The disconnect switch will be installed in the unit in a water-tight
enclosure with access through a swinging door. Factory wiring will be provided from the switch to
the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place
of unit overcurrent protection. This option is available on all models.

Human Interface
The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15
Class B with an Ingress Protection Rating of IP24. The display text shall be readable by a person
with 20/20 vision at a distance of 3 feet and 60° angle at lighting levels ranging from 100 lux - 25,000
lux. Also, the display shall operate at temperatures of -40° C to 70° C. Firmware and unit
configurations shall be able to be restored via a USB storage device.

PKGP-PRC012M-EN

53

Mechanical Specifications

Multi-Speed Indoor Fan System
Multi-speed indoor fan system is designed for use in applications for meeting the minimum
requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed
of the fan to 67% of full airflow based off of compressor stages.

Powered or Unpowered Convenience Outlet
This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When
the convenience outlet is powered, a service receptacle disconnect will be available. The
convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore
will not be affected by the position of the disconnect or circuit breaker. This option can only be
ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker,
option is ordered. This option is available on all models.

Single Zone VAV
SZVAV systems combine Trane application, control and system integration knowledge to exactly
match fan speed with cooling and heating loads, regardless of the operating condition.

Stainless Steel Drain Pan
This option provides excellent corrosion and oxidation resistance. Drain pan shall be constructed
of 304 stainless steel.

Supply, Return and Plenum Air Smoke Detector
With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be
manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with
certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models
affected and the minimum allowable airflow required. This option is available on all downflow
models. Supply and/or Return Detectors may not be used with the Plenum Smoke Detector.

Through the Base Electrical with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through
the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the
unit with access through a swinging door. Factory wiring will be provided from the switch to the
unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized
per NEC and UL guidelines, and be agency recognized by UL/CSA.

Through the Base Electrical with Disconnect Switch
Three-pole, molded case, disconnect switch with provisions for through the base electrical
connections are available. The disconnect switch will be installed in the unit in a water-tight
enclosure with access through a swinging door. Factory wiring will be provided from the switch to
the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place
of unit overcurrent protection. This option is available on all models.

Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of downflow units, and through the front
of the horizontal units. Option will allow for field installation of liquid-tight conduit and an external
field-installed disconnect switch.

Two-Inch Pleated Filters
Two inch pleated MERV 8 or MERV 13 filters with filter removal tool shall be available on all models.

54

PKGP-PRC012M-EN

Mechanical Specifications

Factory or Field Installed Options
BACnet™ Communications Interface
This option shall be provided to allow the unit to communicate directly with a generic open protocol
BACnet MS/TP Network Building Automation System Controls.

Barometric Relief
This option shall provide a pressure operated damper for the purpose of space pressure
equalization and be gravity closing to prohibit entrance of outside air during the equipment “off”
cycle.

Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or
clogged filter indication. These indications will be registered with either a zone sensor with status
indication lights or an Integrated Comfort™ System.

Differential Pressure Switches
These options allow for individual fan failure and dirty filter indication. The fan failure switch will
disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will
light the Service LED on the zone sensor and will allow continued unit operation.

Discharge Air Sensing Kit
This kit provides true discharge air sensing in heating models. This sensor is a status indicator
readable through Tracer™or Tracker™. The kit is functional only with the ReliaTel Options Module.

Economizer - Standard, Downflow
The assembly includes fully modulating 0-100% motor and dampers, barometric relief, minimum
position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator.
The barometric relief damper shall be standard with the downflow economizer and shall provide
a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air
during the equipment “off” cycle. Solid state enthalpy and differential enthalpy control shall be
field-installed.

Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3
cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air
supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired
with powered exhaust for additional building pressure relief.This option can be paired with or
without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.
Available on downflow units only. The economizers come with three control options, dry bulb and
reference or comparative enthalpy (optional).

Electric Heaters
Electric heat modules shall be available for installation within the basic unit. Electric heater
elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each
heater package shall have automatically reset high limit control operating through heating element
contactors. All heaters shall be individually fused from the factory, where required, and shall meet
all NEC and CEC requirements when properly installed. Power assemblies shall provide singlepoint connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through
the Base Electrical option with an Electric Heater, the heater must be factory installed.

PKGP-PRC012M-EN

55

Mechanical Specifications

Frostat™
This option is to be utilized as a safety device. The Frostat opens when temperatures on the
evaporator coil fall below 10°F. The temperature will need to rise to 50°F before closing. This option
should be utilized in low airflow or high outside air applications.

Indoor Fan Motor Shaft Grounding Ring
Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path
away from the motor bearings to ground. Bearing Protection Ring shall be maintenance free
circumferential ring of conductive micro fibers that discharges voltages to ground.

LonTalk® Communications Interface
The LonTalk communications interface, when installed in a Voyager unit, allows the unit to
communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building
Automation System Controls.

Oversized Motors
Oversized motors shall be available for high static applications.

Reference or Comparative Enthalpy
Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and
uses this information to provide improved comfort cooling while using the economizer.
Comparative Enthalpy measures and communicates humidity for both outdoor and return air
conditions and return air temperature. The unit receives and uses this information to maximize use
of economizer cooling, and to provide maximum occupant comfort control. Reference or
Comparative Enthalpy option shall be available when a factory or field installed Downflow
Economizer is ordered. This option is available on all downflow models.

Tool-less Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.

Trane Communication Interface
This factory or field-installed option shall be provided to interface ReliaTel™ controlled units with
the Trane Integrated Comfort™ systems.

Field Installed Options
CO2 Sensor
The CO2 sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO2
(Carbon Dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates
to meet the current ventilation needs of the zone.
Note: Choose factory-installed CO2 sensor wiring option to save time and ensure proper unit
connections for the field installed CO2 sensor kits.

Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone
sensors. This sensor includes a digital display of set point adjustment and space temperature in
°F (Fahrenheit) or °C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions
of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC
(Volts AC). This sensor should be utilized with ReliaTel™ controls.

Economizer - Standard, Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.

56

PKGP-PRC012M-EN

Mechanical Specifications

Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3
cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air).This option allows 100% outdoor air
supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired
with powered exhaust for additional building pressure relief. Available on downflow units only.

High Static Drive
The high static drive option shall allow the standard motor on the 12½ and 15 ton units to operate
with improved external static capabilities.

Manual Outside Air Damper
The rain hood and screen shall provide up to 25% outside air.

Motorized Outside Air Dampers
Manually set outdoor air dampers shall provide up to 50% outside air. Once set, outdoor air
dampers shall open to set position when indoor fan starts. The damper shall close to the full closed
position when indoor fan shuts down.

Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain
better building pressurization.

Roof Curb - Downflow
The roof curb shall be designed to mate with the downflow unit and provide support and a water
tight installation when installed properly. The roof curb design shall allow field-fabricated
rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply
with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include
wood nailer strips.

Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.

Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition up to three
different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition
occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired
relay output from a smoke detector or fire control panel.

Zone Sensors
This option shall be provided to interface with Voyager units and shall be available in either manual,
automatic, programmable with night setback, with system malfunction lights or remote sensor
options.
Note: Zone sensors are required for units configured for Single Zone VAV indoor fan system
control to enable Single Zone VAV functionality.

PKGP-PRC012M-EN

57

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2014 Trane All rights reserved
PKGP-PRC012M-EN 12 Jun 2014

We are committed to using environmentally

Supersedes PKGP-PRC012L-EN (10 Jan 2014)

conscious print practices that reduce waste.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : TCS - Unitary
Copyright                       : ? 2014 Trane All rights reserved
Create Date                     : 2014:06:12 15:00:15Z
Keywords                        : Packaged Heat Pumps, Voyager, catalog, PKGP-PRC012M-EN
Modify Date                     : 2014:06:12 15:05:05Z
Subject                         : Packaged Heat Pumps-Voyager 12 1/2 - 20 Tons - 60 Hz
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Producer                        : Acrobat Distiller 10.1.10 (Windows)
Format                          : application/pdf
Title                           : Voyager 12 1/2 - 20 Tons - 60 Hz
Creator                         : TCS - Unitary
Description                     : Packaged Heat Pumps-Voyager 12 1/2 - 20 Tons - 60 Hz
Creator Tool                    : FrameMaker 10.0.2
Document ID                     : uuid:062b6632-2a4c-482e-809e-213109ba8b5e
Instance ID                     : uuid:2d614318-3844-4317-8512-7e053a4e36ed
Page Mode                       : UseOutlines
Page Count                      : 60
EXIF Metadata provided by EXIF.tools

Navigation menu