english
AM-PREMIUM / AM-PREMIUM-W
Part.-No. 349046 / 349051
Universal control module for ECblue fans
Operating Instructions
Software version: D1727A / D2263A from version 4.00
L-BAL-E095-GB 1203 Index 004
Part.-No.
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Content
General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Signal connection or sensor connection to analog inputs (Analog In 2, Analog In 3) . .
5.3 Output voltage 0 - 10 V (Analog Out) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Voltage supply for external devices (+24V, GND) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Connection external terminal type A-G-247NW or AXG-1A(E) . . . . . . . . . . . . . . . . . . .
5.6 Digital inputs (D1, E1 = D2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 Relay output (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8.1
5.8.2
5.8.3
5.9
Networking via MODBUS-RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS-485 - network design and interface parameter . . . . . . . . . . . . . . . . . . . . . . . .
AM-PREMIUM-W Wireless Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Operating by terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Hand held terminal type A-G-247-NW for several members . . . . . . . . . . . . . . . . . . . . .
12
12
6.1.1
6.1.2
6.2
6.3
6.4
6.5
Display and operating elements of the terminal . . . . . . . . . . . . . . . . . . . . . . . . . .
Establish connection to member . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
13
Terminal type AXG-1A(E) for one member . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example for programming mode 2.01 in “Base setup” . . . . . . . . . . . . . . . . . . . . . . . .
14
14
15
15
Base setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Select operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 External Setpoint / External speed setting in manual operation . . . . . . . . . . . . . . . . . .
16
16
17
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Procedure for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 Menu Mode 1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
18
18
18
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1 Speed controller 1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
19
9.1.1
9.1.2
9.2
Base setup 1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting for operation 1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature control 2.01 ... 2.05
9.2.1
9.2.2
9.2.3
.........................................
Basic setting 2.01 ... 2.05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings for operation modes 2.01 ... 2.05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional diagrams temperature control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L-BAL-E095-GB 1203 Index 004
Part.-No.
2/68
19
19
20
20
21
22
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.2.4
9.2.5
9.2.6
9.3
Pressure control for condensers refrigeration 3.01 ... 3.04
9.3.1
9.3.2
9.3.3
9.4
Base setup 4.01 ... 4.03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting for operation modes 4.01 ... 4.03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic setting 5.01 and 5.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting for operation modes 5.01 ... 5.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air velocity control 6.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.6.1
9.6.2
9.7
9.8
9.9
...............................
Volume control 5.01 ... 5.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.5.1
9.5.2
9.6
.....................
Base setup 3.01 ... 3.04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting for operation modes 3.01 ... 3.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional diagrams pressure control condensers . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure control airconditioning 4.01 ... 4.03
9.4.1
9.4.2
9.5
Additional for mode 2.03 : Signal output 0 - 10 V . . . . . . . . . . . . . . . . . . . . . . . . .
For mode 2.03 : Relay output for Heating or Cooling . . . . . . . . . . . . . . . . . . . . . .
For mode 2.03 Relay output for temperature monitoring . . . . . . . . . . . . . . . . . . . .
Base setup 6.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings for operation modes 6.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
24
25
26
26
27
28
29
29
30
32
32
32
34
34
35
Menu group Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu group Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
37
38
9.9.1
9.9.2
9.9.3
9.9.4
9.9.5
9.9.6
9.9.7
9.9.8
9.9.9
9.9.10
9.9.11
38
38
38
38
39
39
40
40
41
41
41
PIN protection activate, PIN 0010 . . . . . .
PIN protection activate, PIN 1234 . . . . . .
Save user settings restore with PIN 9090
Sensor Alarm ON / OFF . . . . . . . . . . . .
Limit . . . . . . . . . . . . . . . . . . . . . . . . . .
Minimum speed cut off . . . . . . . . . . . . .
Second Group . . . . . . . . . . . . . . . . . . .
Reverse action of the control function . . .
Controller configuration . . . . . . . . . . . . .
Data on the total control deviation . . . . .
LED Mode . . . . . . . . . . . . . . . . . . . . . .
9.10 IO Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.1
9.10.2
Analog-Output “A” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital inputs “D1” / “D2” (E1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.1 Menu overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.2 Enable ON/OFF function |1D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.3 External fault Function |2D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.4 Limit ON / OFF, Function |3D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.5 Switch over Input signal “E2” / “E3”, Function |4D | . . . . . . . . . . . . . . .
9.10.2.6 Set 1/2 or Setpoint 1/2, Function |5D | . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.7 Intern / Extern Function |6D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.8 Automatic control / speed manual, Function |7D | (mode 2.01 ) . . . . . . .
9.10.2.9 Reverse action of control function ( 2.01 ), Function |8D | . . . . . . . . . . .
9.10.2.10 Reset, Function |10D | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.11 Setting Max. Speed ON / OFF function |11D | . . . . . . . . . . . . . . . . . . .
9.10.2.12 Direction of rotation, Function |13D | . . . . . . . . . . . . . . . . . . . . . . . . .
9.10.2.13 “Freeze function” = maintain momentary modulation value, Function |14D |
9.10.3
Configuration of analog inputs “E1”and “E3” . .
9.10.3.1 Signal adaption E2 and E3 . . . . .
9.10.3.2 Inverting analog inputs “E2” / “E3”
Function and inverting for relay outputs “K1” .
Networking via MODBUS . . . . . . . . . . . . . .
9.10.4
9.10.5
9.11 Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.11.1
9.11.2
9.11.3
Limit indication depending on modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limit indication depending on setting or sensor signal . . . . . . . . . . . . . . . . . . . . . .
Limit indication depending on (offset) to Setpoint . . . . . . . . . . . . . . . . . . . . . . . . .
9.12 Motor Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.12.1
9.12.2
Setting for Rampup time and Rampdown time . . . . . . . . . . . . . . . . . . . . . . . . . . .
Suppression of speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L-BAL-E095-GB 1203 Index 004
Part.-No.
3/68
42
42
43
43
44
44
45
45
45
46
47
47
47
48
48
48
49
49
50
51
52
52
53
53
55
56
56
57
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
10
Menu tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1 Menues of operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Possible allocation of the IOs, PINs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
58
62
11
Diagnostics menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
12
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.2 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.3 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.4 Service information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
66
67
68
68
L-BAL-E095-GB 1203 Index 004
Part.-No.
4/68
1.3 FCC / IC Statements (for AM-PREMIUM-W Modules only)
FCC
Compliance
(US)
The
FCC
/ IC warnings
and statements are valid only for the AM-PREMIUM-W modules,
because they have only installed the integrated submodule EM-W, that enhances the AMThis device
complies
Part 15
of the FCC Rules.
Operation
subject to the following
PREMIUM
module
withwith
the radio
communication
function
to allowiscommunication
over
two
conditions:
(1)
this
device
may
not
cause
harmful
interference,
and
(2)
this
device
must
radio frequencies with other Ziehl-Abegg devices (only).
accept any interference received, including interference that may cause undesired
operation.
Note:
Only the submodule EM-W installed in the AM-PREMIUM-W module is tested for
compliancy according to the relevant FCC and IC standards (for more information see
Note: Thisinstruction
equipmentofhas
been tested band found to comply with the limits for a Class A
installation
EM-W).
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
FCC Warning
Changes or modifications not expressly approved by the party responsible for compliance
could void the user's authority to operate the equipment.
IC Compliance (Canada)
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is
subject to the following two conditions: (1) this device may not cause interference, and (2)
this device must accept any interference, including interference that may cause undesired
operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils
radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1)
l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter
tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en
compromettre le fonctionnement.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Note: The AM-PREMIUM-W module is strictly limited for the integration
and usage in host devices (fans and converters) of Ziehl-Abegg AG.
AM-Premium-W module
be mounted
a an
fanconverter
or converter
When the AM-PREMIUM-W
will be will
mounted
in a faninor
of of
Ziehl-Abegg AG, the FCC/IC label (EM-W inside) has to be stick on the
housing of the fan
converter
or converter.
Sticking the FCC/IC label (EM-W inside) on the housing of the fan.
Sticking the FCC/IC label (EM-W inside) on the
housing of the fan.
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
5.1
Electrical installation
Electrical installation
Safety precautions
Danger due to electric current
• Work on electric components may only be carried out by trained electricians or by
persons instructed in electricity under the supervision of an electrician in accordance
with electrical engineering regulations.
• It is forbidden to carry out work on electrically live parts.
5.2
Signal connection or sensor connection to analog inputs (Analog In 2, Analog In 3)
The unit has two analog inputs: Analog In 2 |E2 | and Analog In 3 |E3 |
The connection is independent of the programmed operating mode and from the sensor signal
employed.
• When connecting passive temperature sensorsTF.. (KTY81-210) or PT1000 at terminals “E2 /
T2” and/or “E3 / T3” must be paid attention to no polarity.
For a high interference immunity a capacitor must be connected directly to the sensor (1 nF
parallel). With Ziehl-Abegg temperature sensors type TF.. (KTY81-210) the capacitor is integrated.
• When connecting aktive sensors at the terminals “E2 / GND” and/or “E3 / GND” attention must
be paid to correct polarity, a 24 V DC power supply is integrated.
• For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the “E1 / 24
V” and/or “E3 / 24 V”, “GND” terminal is omitted.
Attention!
Never apply line voltage to analog inputs!
5.3
Output voltage 0 - 10 V (Analog Out)
The analogoutputs 0 - 10 V can be allocated with various functions ( IO Setup: Analog output “A”).
Connection to terminal “A” - “GND” = “Analog Out” (Imax 10 mA).
It is not permissible to connect outputs of several devices to each other!
5.4
Voltage supply for external devices (+24V, GND)
There is an integrated power supply for external devices, e.g. a sensor. Terminal +24 V, output voltage
tolerance +/- 20%. Max. load current 70 mA.
It is not permissible to connect outputs of several devices to each other!
In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse).
The device performs a “Reset” and continues operation.
L-BAL-E095-GB 1203 Index 004
Part.-No.
7/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
5.5
Electrical installation
Connection external terminal type A-G-247NW or AXG-1A(E)
If necessary an external terminal can be connected. This can be e.g. necessary to adapt the presetting during start-up. For information about the current operating condition a terminal can be
permanent attached.
• The connection is made via a 4-strand line at the terminals (D-, D+ and GND).
• e.g., telephone flex e.g. J-Y (St) Y 2x2x0.6 (or similar), maximum line length ca. 250 m.
• Signal “D+” and “D-” (RS 485)
• Type A-G-247NW, Part.-No. 380070, handheld terminal
A-G-247NW
+ 3,3 V
IRDA-RXD
IRDA-TXD
IRDA-SD
(D+)
(D-)
GND
+5V
AM-PREMIUM
(D+)
(D-)
24V
GND
E2
T2
GND
E3
T3
A1
15.09.2010
v_prem_modul_link_terminal.vsd
The voltage supply of the terminal is made by the accumulators inserted there or the plug power supply unit.
• Model AXG-1A, Part-No. 349034 for wall mounting
• Model AXG-1AE, Part-No. 349008 for panel mounting
13.07.2007
v_terminal_anschluss.vsd
DD+
GND
+24 V
Voltage supply: Terminal “24 V”, “GND”, (Imax, for terminal approx. 50 mA)
L-BAL-E095-GB 1203 Index 004
Part.-No.
8/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
5.6
Electrical installation
Digital inputs (D1, E1 = D2)
In the case of use of the module AM-PREMIUM two digital inputs can be programmed. When inserting
the module the analog input “E1” becomes automatically to the second digital input “D2”.
D1: contact at Terminals “D1” - “24 V”
D2: contact at Terminals “E1” - “24 V”
Various functions can be allocated to the digital inputs “D1”and “D2” ( IO Setup: Functions summary
of the digital inputs). Activation via floating contacts (a low voltage of ca. 24 V DC is connected).
Attention!
Never apply line voltage to the digital input!
It is not permissible to connect inputs of several devices to each other!
5.7
Relay output (K1)
The relay output “K1”can have different functions assigned to it ( IO Setup: Function and inversion
of relay output). Max. contact load ECblue: Technical data and connection diagram.
Connection of the floating contacts of relay “K1” to the terminals 11, 14.
factory setting |1K | = Operating indication ( IO Setup).
5.8
Communication
5.8.2
RS-485 - network design and interface parameter
Please ensure the correct connection; i.e. "A (D+)" must always be connected to "A (D+)" of the
next devices. The same applies to "B (D-)" .
In addition, a "GND" connection must be established, as dissimilar potential (over 10 V!) will lead to
the destruction of the RS-485 interface (e.g. lightning).
GND
D+
D-
Networking via MODBUS-RTU
The device comes equipped with a RS-485 interface for networking via MODBUS. Conntection at: “A
(D+)”, “B (D-)” and “GND”.
A maximum of 64 members can be directly connected to one another, and another 63 members
via a repeater.
The address must be set in the “IO Setup” menu.
GND
D+
D-
5.8.1
16.04.2008
v_modbus_geraete_anschluss.vsd
general example for MODBUS device connection
The data line must be connected from one device to the next. No other type of wiring is allowed!
Always use only two wires of one lead (twisted pair) for the connection.
L-BAL-E095-GB 1203 Index 004
Part.-No.
9/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Electrical installation
Examples for MODBUS connection
Recommended wire types
1. CAT5 / CAT7 cables
2. J-Y (St) 2x2x0.6 (telephone wire)
3. AWG22 (2x2 twisted pair)
When using telephone flex with four cable cores, we recommend the following allocation:
“A (D+)” = red, “B (D-)” = black, “GND” = white
Information
• Pay attention to sufficient distance from powerlines and motor wires (min. 20 cm)
• Do not use wire shield
• Except the data link "A (D+)", "B (D-)" and "GND"- connection may no further cable cores
of the data line be used.
• Max. allowed wire length 1000 m (CAT5/7 500 m)
Default interface parameter
Baudrate
Bits
Patity
Stop bits
Handshake
19200
Even (None, exception of devices agriculture)
none
Information
If any matters are unclear, please contact our V-STE support department for control systems ventilation technology. The information sheet "Network structure of MODBUS" R-TIL08_01 contains
detailed information about "MODBUS".
L-BAL-E095-GB 1203 Index 004
Part.-No.
10/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
5.8.3
Electrical installation
AM-PREMIUM-W Wireless Communication
The type A-G-247NW hand-held terminal can communicate wireless with the type AM-PREMIUM-W
communications module.
In a hard-wired system, wireless communication is primarily designed in order to have a second
interface for communicating with the device (e.g., for configuration and diagnostics).
In the A-G-247NW, for wireless communication with an EC fan type ECblue Basic use the |AMPREMIUM-W | menu item.
Wireless communication is also used by the MODBUS protocol, so it is necessary to assign an
address. Wireless and hard-wired communications use the same address. The address can be
hard-wire assigned via an RS-485.
For pure, wireless communication, it is recommended to assign the address manually.
• Switch on the device you want to re-address and establish a connection with address 247.
• In “IO Setup”, change the address and then switch this device off again.
• Apply the same procedure to the next device.
Radio control key (0 - 9999)
Different from RS-485 communication, wireless communication also has a radio control key (0 9999). This radio control key is used to encode the messages and ensures that several networks can
be operated in mutually overlapping radio ranges.
For that reason, every wireless MODBUS network should have its own radio control key if there is
another wireless MODBUS network in the vicinity.
The factory setting is |9999 | .
A radio control key with the value |0 | switches off encoding.
The ECblue must be switched off to save the new radio control key.
The radio control key must be assigned in the same manner as the assignment of the MODBUS
address. The radio control key can be found in the ECblue basic menu in the “IO Setup” menu item.
Technical data for wireless Communication:
5.9
Radio communication
standard:
IEEE 802.15.4
Frequency:
2.4 GHz (not licensed wireless band, like WLAN, Bluethooth)
16 wireless channels, default wierless channel 0
Communications range:
Short-distance radio, within buildings max. 8 m typically 3 - 5m, free field to 25 m,
generally strongly dependent on interferences
Type of communication:
Bi-directional, half dublex
Application protocol:
MODBUS-RTU (max. protocol length 125 Bytes and/or 50 register)
Coding:
Proprietary through 4-digit number
Network structure:
Point - to - point or point - to- mulit point - communication
Potential at control voltage connections
The control voltage connections (< 50 V) relate to the joint GND potential (Exception: Relay contacts
are potential free). There is a potential separation between the control voltage connections and the
protective earth. It must be ensured that the maximum external voltage at the control voltage
connections cannot exceed 50V (between “GND” terminals and “PE” protective earth). If necessary, a
connection to the protective earth potential can be established, install bridge between “GND” terminal
and the “PE” connection (terminal for screening).
L-BAL-E095-GB 1203 Index 004
Part.-No.
11/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
6.1
6.1.1
Operating by terminal
Operating by terminal
Hand held terminal type A-G-247-NW for several members
Display and operating elements of the terminal
Hand held terminal type A-G-247NW
OFF
7 6 5
Mainmenu
>>> IXI
ECblue
AXG Mode
USB Filetransfer
A-G-247NW Setup
1 ON
10
15.09.2010
v_bed_men_a-g-247nw_2nd.vsd
Switch on terminal
Program key and open menu
Menu selection, increase value
Menu selection, reduce value
From each menu (member) directly back to the display for “Speed”
Escape = exit menu for settings (user), cancel input
- Select type of user
- back to selection of user (exit application)
- Switch off terminal (keep key pressed for a few seconds)
8 "Main menu" = momentarily active menu level ( |>>> | = batteries being charged, |====- | = full)
9 Selection option of the sub-menu (display in menu language English)
10 Key not assigned (soft key, program-dependent function)
Explanation of display (menu User)
2 3 4 5 6 7 8 9 10
11
12
13
04.05.2009
v_display_erkl_A-G-247NW.vsd
L-BAL-E095-GB 1203 Index 004
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Part.-No.
12/68
Numeric display 5 digit
Moon-Symbol for set point 2
Current derating active
list of fault indications)
Alarm-symbol (
Brake motor or motor heating active
Fire-Symbol (heating operation)
temperature managment active (power reduction)
No connection to Modul (only AM-MODBUS)
not used
STOP-Symbol (enable)
Bargraph Fanlevel
Text line 3 figures (display unit, etc.)
Text line 16 figures (display text menu.)
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
6.1.2
Operating by terminal
Establish connection to member
1. Open drop-down menu |ECblue | with the P key.
2. Select type of user with the ▼ + ▲ keys and confirm with the P key.
Setting kind of member
Explanation
Display
Main menu IXI
ECblue
ECblue Apps
Setting kind of member
AM-MODBUS
ECblue fan with integrated communication module.
Type AM-MODBUS, Part.-no. 349045
Communication via cable.
AM-MODBUS-W
ECblue fan with integrated communication module.
Type AM-MODBUS-W, Part.-no. 349050
Communication wireless.
AM-PREMIUM
ECblue fan with integrated universal control module.
Type AM-PREMIUM, Part.-no. 349046
Communication via cable.
AM-PREMIUM-W
ECblue fan with integrated universal control module.
Type AM-PREMIUM-W, Part.-no. 349051
Communication wireless.
Confirm address
Netzwerkschlüssel
IXI ◄
For communication wireless:
Set network key an confirm withP-key.
9999
Select device
IXI ◄
The device address (Device-ID) of the members is factory set to the highest available MODBUS
address: 247
Set address with the ▼ + ▲ keys and confirm this with the P key to establish the first connection.
247
◄
ZATerminal support
ECblue-247
IXI
☻
ECblue-246
Successful connection!
IXI
No connection!
Settings are not possible!
In the display the two symbols for alarm and antenna appear (only for AM-MODBUS).
Cause: wrong address, no connection via wire and/or radio (only AM-MODBUS-W).
L-BAL-E095-GB 1203 Index 004
Part.-No.
13/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
6.2
Operating by terminal
Terminal type AXG-1A(E) for one member
With terminal type AXG-1A(E) connection only to one member possible.
▼
▲
▼+▲
Program key and open menu
Menu selection, reduce value
Menu selection, increase value
ESC-key combination, Escape = leave menu
16.09.2009
v_terminal_axg.vsd
explaining display
6.3
terminal A-G-247NW
Menu operation
Display after turning on the mains voltage.
description for menu language English = “GB” (delivery status).
Switch over between “Start” and *Actual value with Escape |Esc | .
Example for mode 1.01 (speed controller).
*actual value depending device type:
- "Speed" / rpm,- "Frequency" / Hz, - "Fanlevel" / %
P↓ ↑ ESC
▲▼
By pushing the P key one reaches the menu item “START”.
One moves up and down within the menu group using the arrow keys.
In the menu point “Language” display language can be selected.
One returns to the menu group “Start” using the ESC (▼ + ▲) shortcut keys.
L-BAL-E095-GB 1203 Index 004
Part.-No.
14/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
6.4
Operating by terminal
Menu structure
PIN 0010
STOP
Service → → → →
← ← ← ← User
▼
▲
Start
▼
▲
Info
Setting
▼
▲
▼
▲
Events
Base setup
P↓ ↑ ESC
P↓ ↑ ESC
P↓ ↑ ESC
P↓ ↑ ESC
P↓ ↑ ESC
PIN input
Frequency
Set Intern1
Motor fault
Mode
▲▼
▲▼
▲▼
▲▼
▲▼
Language
Set external1
Set Intern2
E1 Analog In
Menu dependent on device type
Selection of the menu group (e.g. Base setup) to the right through the ▼-key, to the left through the
▼-key.
You can go to the menu items in the menu groups (e.g. mode of operation) by using the P key. Use
the arrow keys to move up and down within the menu group.
The menu groups consist of one area for the user (user menu) and one area for installation (service).
The service area can be protected against unauthorized access by using a PIN.
In order to simplify the initial start-up operation, the service level is enabled at first (i.e., not protected
by the PIN 0010 ( see Controller Setup, PIN protection = OFF). If PIN protection is activated (ON),
the service menu remains enabled after input of PIN 0010 as long as one is pressing keys. If no keys
are pressed for ca. 15 minutes, the PIN is automatically erased, i.e. the service level is blocked.
To make adjustments, press the P key after selecting the menu item. If the previously set value starts
to ash
, it can be adjusted with the ▼ + ▲ keys and then saved with the P key. To exit the menu
without making any changes, use the “Esc” short-key, i.e., the originally set values remain.
Information
After installation of the device has been carried out, PIN protection should be activated (
Setup)!
6.5
Example for programming mode 2.01 in “Base setup”
Mode
L-BAL-E095-GB 1203 Index 004
Mode
Part.-No.
15/68
▲
Mode
Mode
Controller
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
7.1
Base setup
Base setup
Select operation mode
Information
Simple installation is possible through the selection of the preprogrammed mode of operation.
This determines the basic function of the device; factory setting 1.01 = speed controller
(activation via 0 - 10 V signal). The controller configuration is automatically carried out during
selection of the application related mode of operation. The factory presets in accordance with
the mode of operation are based on many years of experience, which is suitable for many
applications. Under special circumstances, these can be individually adapted ( Controller
Setup: “Controller Configuration”).
The purpose of the device is to reach and maintain the target values set. To accomplish this, the
measured actual value (sensor value) is compared with the adjusted target value, and the controlled
value (modulation) is deduced from this.
Mode
1.01
Signal or Sensor
(input)
Signal 0 - 10 V
Function
Speed controller, two step operation (factory setting)
Sensor KTY81-210 / PT1000 (E2)
Temperature control airconditioning and refrigeration.
(preset set-point 20.0 °C, P-band 5.0 K)
Sensor KTY81-210 / PT1000 (E3)
Temperature control depending on outdoor temperature
(preset set-point 5.0 °C, - P-band 20.0 K)
2.03
Sensor KTY81-210 / PT1000 (E2)
Temperature control with additional functions (shutter and heating)
2.04
1x Sensor KTY81-210 / PT1000 (E2)
1x Sensor KTY81-210 / PT1000 (E3)
Temperature control with two sensors, comparison or average
2.05
1x Sensor KTY81-210 / PT1000 (E2)
1x Sensor KTY81-210 / PT1000 (E3)
Temperature control with two sensors differential temperature
3.01
Sensor MBG.. (E2)
Pressure control condensers (refrigeration)
3.02
Sensor MBG..(E2)
Pressure control for condensers with input for refrigerant
3.03
1x Sensor MBG..(E2)
1x Sensor MBG..(E3)
Pressure control for two circuit condensers
3.04
1x Sensor MBG..(E2)
1x Sensor MBG..(E3)
Pressure control for two circuit condensers with input for refrigerant
4.01
Sensor DSG.. / MPG.. (E2)
Pressure control for ventilation systems
4.02
1x Sensor DSG.. / MPG.. (E2)
1x Sensor KTY81-210 / PT1000 (E3)
Pressure control depending on outdoor temperature
4.03
1x Sensor DSG.. / MPG.. (E2)
1x BUS RS 485
Pressure control depending on outdoor temperature, MODBUS for outdoor temperature and remote control by central operating device type
AXE-200AX
5.01
Sensor DSG.. / MPG.. (E2)
Volume control (constant) for ventilation systems
5.02
1x Sensor DSG.. / MPG.. (E2)
1x Sensor KTY81-210 / PT1000 (E3)
Volume control with setpoint depending on outdoor temperature
6.01
Sensor MAL..(E2)
Air velocity control e.g. clean room
2.01
2.02
L-BAL-E095-GB 1203 Index 004
Part.-No.
16/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Base setup
Mode and Signal to E1, E3
2.01 .. 2.03
1.01
0 - 10 V
E2
GND
E2
T2
4.01 + 5.01
MBG..-I
24V
E2
DSG 0 - 10 V
GND
24V
E2
GND
BN
YE
WH
0-10 V
10 k
BN
GN
DSG.. / MPG..
MBG..
(0 - 10 V)
(4 - 20 mA)
2.04 + 2.05
MAL 0 - 10 V
24V
E2
GND
T3
24V
E3
TF..
BN
GN
MAL1/10
(0 - 10 V)
4.02 + 5.02
MBG..-I
TF..
GND
E3
KTY81-210
PT 1000
E3
KTY81-210
PT 1000
A1
Rext
E2
3.03 + 3.04
TF..
10 V PWM
GND
6.01
KTY81-210
PT 1000
A1
3.01 + 3.02
TF..
T3
TF..
MBG..
(4 - 20 mA)
f = 1...10 kHz @ Rext = 1 k2
f = 1 kHz @ Rext = 10 k2
t = 0...100 %
4.03
GND
D+
D-
Data
RS-485
7.2
16.01.2012
v_e2_e3_signal_sensor_pwm.vsd
External Setpoint / External speed setting in manual operation
External setpoint setting or external manual operation are possible using a 0 - 10 V (0 - 20 mA, 4 - 20 mA) signal at the “E3” and
“GND” terminals. Configure “E3” in Base setup. For potentiometers, program Analog Out 1 (terminal “A1”) to the function |1A | =
“+10 V” (as factory setting
IO Setup).
E3 Analog In = factory setting 0 - 10 V
A1
E3
GND
Signal 0-10 V
10 k
16.01.2012
v_extern_poti_e3.vsd
External Setpoint via external signal instead of “Setpoint 1”. The “external Setpoint” function must be activated in base setup
|1E | for “E3 function”. The active external Setpoint value is displayed in the “info” menu group.
External speed setting in manual operation. The “external manual operation” function must be activated in the basic settings
|2E | for “E3 function”. Switchover between settings on the device and external manual operation via the digital input ( IO
Setup: “Control / manual operation” |7D | ).
L-BAL-E095-GB 1203 Index 004
Part.-No.
17/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
8.1
Start-up
Start-up
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. Make sure that no persons or objects are in the fan's hazardous area.
8.2
Procedure for commissioning
Sequence
Setting
If necessary, set the menu language in Menu group “Start”.
(Factory setting Englisch: “Language GB”)
Set the operating mode in the Base setup menu group (factory settings 1.01 = speed controllers).
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in “Motor Setup” are lost. An exception: the menu language setting remains
preserved.
8.3
Menu Mode 1.01
Start
Info
Setting
Events
Base
setup
Controller
Setup
---PIN input
0 rpm
Speed
200 rpm
Set Intern1
-0Factory
sett.
1.01
Mode
OFF
|1A |
PIN ProtecA Function
tion
IO Setup
Limits
Motor
Setup
OFF
Level.
Function
20 sec
Rampup
time
Diagnostic
OTC
00012:56:15
GB Language
0.0 A
----Motor curSet Intern2
rent
-1Sensor 1
0 - 10 V
OFF
E2 Analog Set protecIn
tion
0.0 V
A min.
20 sec
OTM
----Rampdown 00010:56:Level min
time
11
OFF
Reset
0 rpm
0 rpm
Set exterMin. Speed
nal1
-3ext. Fault
OFF
E3 Function
OFF
Save User
Setup
10.0 V
A max.
----Level max.
OFF
Suppression1
585 V
DC-Voltage
----E3 Analog
In
----Limit
OFF
----A Inverting Level Delay
----Range1
min.
244 V
Line voltage
----Range1
max.
29.5 °C
Heatsink
OFF
Suppression1
29.5 °C
Capacitor
1.01
Mode
1800 rpm
Max.
Speed
4.00
ECblue
Premium
ON
Set external1
1.01
Basic Version
L-BAL-E095-GB 1203 Index 004
----Group 2
ON value
----nmin at
Group2
Part.-No.
18/68
OFF
D1 Function
OFF
Lmt E2
Function
---------D1 InvertLmt E2 min
ing
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.1
9.1.1
Programming
Programming
Speed controller 1.01
Base setup 1.01
Base setup
Base setup
Mode
Factory setting Mode: 1.01
Mode
E2 Analog In
E3 Function
E3 Analog In
9.1.2
E2 Analog In
Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting
Factory setting: 0 - 10 V
IO Setup)
E3 Function (only for special applications)
Analog input 2 “E3 function”factory set at “OFF”.
For operation with a second signal and switch over via floating contact set function for
IO Setup: function |4D | ).
“E3” to |1E | (
For operation with a second signal and automatic control at the higher level. Set “E3”
Function to |4E | .
E3 Analog In
As long as no allocation has been carried out display: | - - - - - |
Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting
IO Setup)
Factory setting: 0 - 10 V
Setting for operation 1.01
Setting
Setting
Set Intern1
Set Intern2
Min. Speed
Max. Speed
Set external1
L-BAL-E095-GB 1203 Index 004
Set Intern1
Setting range manual speed setting: 0 rpm... “Max. Speed”
Factory setting: 200 rpm
Set Intern2
Setting “Set Intern 2” e.g. reduced value for night operation.
Switch over intern 1/2 by external contact (as long as no allocation is carried out:
IO Setup).
Display: | - - - - - |
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Set external1
“ON” (factory setting) = speed setting by external Signal
“OFF” = Setting “Set Intern1”
Part.-No.
19/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Diagram setting signal and output voltage (Idealized principle diagram)
nM
100 %
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
50 %
Min.
Si
10
20
18
5,6
16
7,2
14
8,8
12
10,4
10
10
12
12
14
16
18
13,6 15,2 16,8 18,4
20
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
10
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
09.05.2007
v_nmotor_101.vsd
100 % = Rated speed
nM Motor speed
Si Signal
9.2
9.2.1
Temperature control 2.01 ... 2.05
Basic setting 2.01 ... 2.05
Base setup
Base setup
Mode
Mode selection e.g. 2.01
Mode
E2 Analog In
E2 Analog In
In all group 2 operating modes (2.01, 2.02, 2.03, ....)
“E2 Analog In” factory set to “KTY” (sensors type TF..) at terminals “E2” and “T2”
(measuring range: -50.0...+140 °C).
Alternative selection sensor
• PT1000 to Terminals “E2” and “T2” (Measuring range -50.0...+140 °C)
• MTG-120V active sensor with 0 - 10 V output at terminals “E2” and “GND”
(measuring range: -10...+120 °C)
Alternative selection signal at terminals “E2” and “GND”: 0 - 10 V, 0 - 20 mA, 4 - 20 mA.
The sensor measurement range must be entered in order to display the actual value
correctly.
Example with a 0 - 10 V sensor and 0 - 100 °C measurement range:
E2 Analog In = 0 - 10 V, E2 Min. = 0.0 °C, E2 Max. = 100.0 °C, E2 Decimally = 1, E2
Unit = °C
E2 Offset
Sensor calibration with calibrated comparison device
E2 Offset
L-BAL-E095-GB 1203 Index 004
Part.-No.
20/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
E3 Function (only for special applications)
E3 Function
•
Function |1E | = External Setpoint e.g. via external signal (0 - 10 V) instead of
“Setpoint1”
– For sensor type “E2 Analog In” = “KTY or PT1000”: 0 - 10 V -50.0...+140
°C.
– For sensors with active signal: 0 - 10 V
E3 Analog In
•
•
0 - 100 % sensor measuring range.
Function |2E | = External manual operation via external signal (0 - 10 V). Switch
over between settings on the device and external manual operation via digital
input (
IO Setup: function |7D | ).
Function |7E | Measurement value = Measurement value e.g. for limit indication,
display in Info menu “E3 Actual”.
Modes with two sensors
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
• 2.04 E3 Function at |4E | preprogrammed = comparison value with control to
higher temperature. Alternative: average of 2 measuring points for this must be
reprogrammed on function |3E | preprogrammed sensor type “KTY”.
• 2.05 E3 Function at |5E | preprogrammed = regulation on difference temperature between sensor 1 and sensor 2. Preprogrammed sensor type “KTY”.
9.2.2
Settings for operation modes 2.01 ... 2.05
2.01 Temperature control simple
2.02 Temperature control depending on outdoor temperature (Special function: Sensor connection at “E3”,
display and setting under “E2”).
2.03 Temperature control with pre-programmed additional functions (heating, shutter, temperature monitoring).
2.04 Temperature control with 2 sensors
Comparison with control to higher value “E3 Function” set to comparison |4E | . Display during operation:
“Control value ”
Alternative: Average calculation of 2 measuring places “E3 Function” set to |3E | . Display during operation: “Average E2 / E3 ”
2.05 Temperature control with 2 sensors, regulation on difference temperature.
Display during operation: “Value of E2 - E3” in K, “E2” = reference temperatur, “E3” causes positiv (E3 <
E2) or negative (E3 >E2) difference.
Setting
Setting
Setpoint1
Setpoint2
L-BAL-E095-GB 1203 Index 004
Setpoint1
Setting range: with passive sensor type “KTY”, “PT1000” : -50.0...150.0 °C
Factory setting: 2.01 , 2.03 , 2.04 : 20.0 °C
at 2.02 : 5.0 °C
at 2.05 : 0.0 °C
Setting range: at active sensor type “MTG-120V”: -10.0...+120.0 °C
Factory setting: 2.01 - 2.05 : 55.0 °C
Setpoint2
Setting “Setpoint 2” e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
IOSetup).
Display: | - - - - - |
Part.-No.
21/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Pband
Passive sensor type “KTY”, “PT1000”
Setting range: 0 - 200.0 K (Kelvin)
Factory setting: 5.0 K, (at 2.02 : 20.0 K)
active Sensor type “MTG-120V”
Setting range: 0.0...+130.0 K
Factory setting: 65.0 K
Min. Speed
Max. Speed
Manual mode
Speed man.
9.2.3
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Manual mode
“OFF” = automatic control as function of the set parameters (Factory setting)
“ON” = automatic control without function, speed setting in menu “Speed manual”
Speed Manual mode
Manual speed setting without influence by the external signal.
Activation by menu “Manual mode” or external contact at digital input (
IO Setup).
Setting range: 0 rpm...Rated speed, Factory setting: 200 rpm
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Functional diagrams temperature control
Example 1: Temperature control in factory setting “Cooling function” (Idealized principle diagram)
nM
100 %
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
50 %
Min.
20 °C
10 K
30 °C
09.05.2007
v_tempcontrol_cool_nmotor.vsd
(Controller Setup: “Val > Set = n+” to “ON”)
nM Motor speed
S Setpoint
R Pband
I Actual value
L-BAL-E095-GB 1203 Index 004
Part.-No.
22/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Example 2: Temperature control in “Heating function” (Idealized principle diagram)
nM
100 %
Min. 0 %
Max. = 100 %
Max.
50 %
Min.
Min. 35 %
Max. = 85 %
10 °C
10 K
20 °C
09.05.2007
v_tempcontrol_heat_nmotor.vsd
(Controller Setup: “Val > Set = n+” to “OFF”)
nM Motor speed
S Setpoint
R Pband
I Actual value
9.2.4
Additional for mode 2.03 : Signal output 0 - 10 V
The 0 - 10 V output signal can, e.g., be used for triggering a shutter or heating.
Offset AnalogOut
Offset AnalogOut
Pband AnalogOut
Min. AnalogOut
Max. AnalogOut
L-BAL-E095-GB 1203 Index 004
The target value for this output is the target value (Setpoint) for the ventilation “offset”
setting.
Adjustment: range +/- 10 K relative to the active Setpoint.
Example for triggering a shutter servomotor:
At factory setting “0 K” = synchronous operation.
The analog output is factory set to increasing activation during increasing temperature.
Reprogramming to “Heating function”, i.e., increasing modulation during decreasing
temperature is possible ( IO Setup).
Pband AnalogOut
Pband AnalogOut = separately adjustable range of control (P-band) for 0 - 10 V output
Setting range: 0...102.0 K
Factory setting: 2.0 K
Min. AnalogOut
Min. AnalogOut = Minimal output voltage
Setting range: 0...100 % = 0 - 10 V
Factory setting: 0 %
Max. AnalogOut
Max. AnalogOut = Maximal output voltage,
Setting range: 100...0 % = 10 - 0 V
Factory setting: 0.0 K
Part.-No.
23/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Example for signal out 0 - 10 V (IO Setup: “A function” = |6A | )
10 V
100 %
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
Max. Analog Out
50 %
Min. Analog Out
20 °C
30 °C
10 K
09.05.2007
v_signal_ausgang_0_10_v.vsd
Example: Setpoint ventilation 25.0°C, Offset -5.0 K, Pband 10.0 K
S Setpoint Ventilation +/- Offset
R Pband
I Actual value
9.2.5
For mode 2.03 : Relay output for Heating or Cooling
OffsetDigitalOut
Offset Digital Out = Offset for relay output (“K1” has to be reprogrammed to function
|9K | ).
The relay operating point deviates by the adjusted offset of the Setpoint of the ventilation.
Setting range: -10.0...+10.0 K
Factory setting: -1.0 K
OffsetDigitalOut
• “0.0 K” set, i.e. heating “ON” when: actual value = Setpoint
• During negative offset value heating “ON” when: actual value = Setpoint - offset
• During positive offset value heating “ON” when: actual value = Setpoint + offset
Hyst.DigitalOut
Switching hysteresis of the relay
Setting range: 0...10 K, Factory setting: 1.0 K (Kelvin)
Hyst.DigitalOut
Temperature variation with setting |9K | for K1 function in IO Setup e. g. for controlling a
Heating.
If the ambient temperature is lower than the set operating point, the heating remains switched on. If
the ambient temperature exceeds the set operating point of the heating by 2 K (Kelvin), the heating is
switched off. I.e., the release point is situated at the hysteresis value over the operating point.
11
13
15
17
19
21
23
25
27
[min]
ON
ON
ON
29
[°C]
16.03.2007
v_relais_heizen_9k_pos_offset.vsd
[°C]
30
28
26
24
22
20
18
16
14
12
10
OFF = 15°C + 2 K = 17 °C
OFF = 20°C + 2 K = 22 °C
ON = 15°C + 5 K = 20 °C
Example:
Setpoint 20.0 °C, Offset -5.0 K, Hysteresis 2.0 K
ON = 20°C - 5K = 15 °C
30
28
26
24
22
20
18
16
14
12
10
11
13
15
17
[min]
19
21
ON
The activated heating is indicated over the fire symbol in the display.
E2 Actual
L-BAL-E095-GB 1203 Index 004
Part.-No.
24/68
23
25
27
ON
29
16.03.2007
v_relais_heizen_9k_neg_offset.vsd
Example:
Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Temperature variation with setting |10K | for “K1” function in IO Setup e. g. for activation of the
cooling.
Example:
Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
[°C]
30
28
26
24
22
20
18
16
14
12
10
11
13
15
17
19
21
[min]
ON
9.2.6
ON
ON
23
25
27
29
16.03.2007
v_relais_kuehlen_10k_pos_offset.vsd
OFF = 20°C - 2 K = 18 °C
ON = 15°C + 5 K = 20 °C
If the ambient temperature is higher than the set operating point, the cooling remains switched on. If the ambient
temperature falls below the set operating point of the
cooling by 2 K (Kelvin), it is switched off. I.e., the OFF
point is situated at the hysteresis value under the ON
point.
For mode 2.03 Relay output for temperature monitoring
If the set value for the “minimum alarm” is not reached or the set value for the “maximum alarm” is
exceeded, a message is generated via the alarm symbol in the display. In addition, „Lmt E1 min“ is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the „Maximum
alarm“. An external message follows via the factory-assigned “K1” relay. (IO Setup: K1 function =
|2K | ).
Alarm Minimum
Alarm Maximum
Alarm Minimum
Setting range: OFF / -26.9...75.0 °C
Factory setting: 0.0 °C
Alarm Maximum
Setting range: OFF / -26.9...75.0 °C
Factory setting: 40.0 °C
Example for display if falling below setting “Alarm Minimum” alternating to the actual
value display.
Relay “K1” disengages (if not inverted).
Lmt E2 min.
Example for display if exceeding setting “Alarm Maximum” alternating to the actual
value display
Relay “K1” disengages (if not inverted).
Lmt E2 max.
L-BAL-E095-GB 1203 Index 004
Part.-No.
25/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.3
9.3.1
Programming
Pressure control for condensers refrigeration 3.01 ... 3.04
Base setup 3.01 ... 3.04
Base setup
Base setup
Mode
Mode selection e.g. 3.01
Mode
E2 Analog In
E2 Analog In
For all Modes in Group 3 ( 3.01 , 3.02 , 3.03 , ...)
“E2 Analog In” factory setting to “MBG-30I”.
(measuring range 0..30 bar) proportional output 4 - 20 mA
Selection sensor: MBG-30I, MBG-50I, DSF2-25
Alternative selection signal: 0 - 10 V, 4 - 20 mA. The sensor measurement range must
be entered in order to display the actual value correctly.
Example 0 - 10 V sensor and measuring range 0 - 20 bar:
E2 Analog In = 0 - 10 V, E2 Min. = 0.0 bar, E2 Max. = 20.0 bar, E2 Decimals = 1, E2
Unit = bar
E2 Offset
Sensor calibration with calibrated comparison device
E2 Offset
E2 Refrigerant
E3 Function
E2 Refrigerant
With 3.02 and 3.04 operating modes with input of the refrigerant, the device automatically calculates the corresponding temperature for the measured pressure. The settings for offset, target value and the controlling range are then carried out in °C or K.
Calculation for relative pressure (differential measurement of pressure relative to ambient pressure). No further settings are necessary for pressure sensors model e.g.
“MBG-30I” or “MBG-50I” (measurement range 0 - 30 bar or 0 - 50 bar). In the case of
sensors with other measurement ranges, the “E2 Min. value” and the “E2 Max. Value”.
Setting in “bar” although unit display is in “°C”!
E3 Function (only for special applications)
• External setpoint = Function |1E | by external signal (0 - 10 V) instead of
0 - 100 % sensor measuring range.
“Setpoint 1”. 0 - 10 V
External
manual
operation
via external signal (0 - 10 V) = Function |2E | Switch
•
over between settings on the device and external manual operation via digital
IO Setup: fuction |7D | ).
input (
• Measurement value = function |7E | e.g. for limit indication, display in Info menu
“E3 Actual”.
Modes 3.03 and 3.04 with two sensors
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
With 3.03 and 3.04 E3 Function at |4E | preprogrammed = comparison value with
control to higher value (two circuit condensers).
Selection of the refrigerants:
R12
R13
R13b1
R22
R23
R32
R114
R134a
R142B
R227
R401
R401A
R401B
R402
R402A
R402B
R404A
R407A
R407B
R407C
R410A
R500
R502
R503
R507
R717
L-BAL-E095-GB 1203 Index 004
Part.-No.
26/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.3.2
Programming
Setting for operation modes 3.01 ... 3.02
3.01 Pressure control condensers, setting Setpoint in bar
3.02 Pressure control for condensers with input for refrigerant, Setpoint in °C
Setting
Setting
Setpoint1
Setpoint1
3.01 Setting range: in measuring range of sensor, factory setting: 12.0 bar
3.02 Setting range: dependent on the selected refrigerant, factory setting: 35.0 °C
Setpoint1
Setpoint2
Pband
Setpoint2
Setting “Setpoint 2” e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
IOSetup).
Display: | - - - - - |
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
3.01 Setting range: in measuring range of sensor, factory setting: 5.0 bar
3.02 Setting range: dependent on the selected refrigerant and in measuring range of
sensor, factory setting 7.0 K
Pband
Min. Speed
Max. Speed
Manual mode
Speed man.
L-BAL-E095-GB 1203 Index 004
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Manual mode
“OFF” = automatic control as function of the set parameters (Factory setting)
“ON” = automatic control without function, speed setting in menu “Speed manual”
Speed Manual mode
Manual speed setting without influence by the external signal.
Activation by menu “Manual mode” or external contact at digital input (
IO Setup).
Setting range: 0 rpm...Rated speed, Factory setting: 200 rpm
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Part.-No.
27/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.3.3
Programming
Functional diagrams pressure control condensers
Functional diagram for Mode 3.01 and 3.03 (Idealized principle diagram)
nM
100 %
Min. 0 %
Max. = 100 %
50 %
Min.
12 bar
5 bar
17 bar
09.05.2007
v_diagramm_301_303_bar.vsd
nM Motor speed
S Setpoint
R Pband
I Actual value
Functional diagram for Mode 3.02 and 3.04 (Idealized principle diagram)
nM
100 %
Min. 0 %
Max. = 100 %
50 %
35 °C
7K
42 °C
09.05.2007
v_diagramm_302_304_c.vsd
nM Motor speed
S Setpoint
R Pband
I Actual value
Information
The factory default presets must be adapted to match the system conditions by a competent
person.
L-BAL-E095-GB 1203 Index 004
Part.-No.
28/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.4
9.4.1
Programming
Pressure control airconditioning 4.01 ... 4.03
Base setup 4.01 ... 4.03
Base setup
Base setup
Mode
Mode selection e.g. 4.01
Mode
E2 Analog In
E2 Analog In
In all group 2 operating modes 4 ( 4.01 , 4.02 , 4.03 , ....) “E2 Analog In” factory setting
“DSG200 ”.
Selection sensor type: “DSG 50”, “DSG100*”, “DSG200”, “DSG300”*, “DSG500”,
“DSG1000”, “DSG2000”, “DSG4000”, “DSG6000 ”
(* no standard type).
With the use of not pre-programmed sensor types further settings are necessary.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range (proportional
output signal):
E2 Analog In = 0 - 10 V, E2 Min. = 0.0 Pa, E2 Max. = 400 Pa, E2 Dezimal = 1, E2
Einheit = Pa
E2 Offset
Sensor calibration with calibrated comparison device
E2 Offset
E3 Function
E3 Function (only for special applications)
• External setpoint = Function |1E | by external signal (0 - 10 V) instead of
“Setpoint 1”. 0 - 10 V
0 - 100 % sensor measuring range.
External
manual
operation
via external signal (0 - 10 V) = Function |2E | Switch
•
over between settings on the device and external manual operation via digital
input (
IO Setup: fuction |7D | ).
• Measurement value = function |7E | e.g. for limit indication, display in Info menu
“E3 Actual.”
Modes 4.02 and 4.03 with two sensors
The function is automatically jointly programmed in operating modes using 2 sensors.
The second analog input is thus allocated and additional function allocations are not
possible.
For 4.02 E3 Function at |6E | preprogrammed = sensor for setpoint lowering. Preprogrammed sensor type “KTY ”
For 4.03 |E3 | Function at |6E | preprogrammed = sensor for setpoint lowering.
- preprogrammed sensor type “BUS”
- measuring range -35.0...+65.0 °C
In “IO Setup”:
For enable “ON” / “OFF” via Bus:
- D1 function = |1D |
- D1 Busmode = “ON”
For switch over setpoint 1 /2 via Bus:
- D2 function = |5D | ,
- D2 Busmode = “ON”
L-BAL-E095-GB 1203 Index 004
Part.-No.
29/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.4.2
Programming
Setting for operation modes 4.01 ... 4.03
• 4.01 pressure control, setpoint in Pa
• 4.02 and 4.03 Pressure control for ventilation systems setpoint depending on outdoor temperature
Setting
Setting
Setpoint1
Setpoint2
Pband
Min. Speed
Max. Speed
Manual mode
Speed man.
L-BAL-E095-GB 1203 Index 004
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Setpoint2
Setting “Setpoint 2” e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display: | - - - - - |
IO Setup).
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Manual mode
“OFF” = automatic control as function of the set parameters (Factory setting)
“ON” = automatic control without function, speed setting in menu “Speed manual”
Speed Manual mode
Manual speed setting without influence by the external signal.
IO Setup).
Activation by menu “Manual mode” or external contact at digital input (
Setting range: 0 rpm...Rated speed, Factory setting: 200 rpm
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Part.-No.
30/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Additional menu item for mode 4.02 and 4.03 with outside-temperature dependent targetsetpoint.
Outside-temperature dependent target-setpoint
Sollwert 1
[Pa]
Sollwert 2
[Pa]
P-min SA
[Pa]
An outside temperature compensation can be
activated (sensor connection “E2” = “Analog In
2”) when being operated as a pressure regulation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active “Setpoint 1” or “Setpoint 2” is
automatically changed proportional to the
measured outside temperature (
Info: “Setpoint control”).
Außentemperatur
-15 °C
min. Temperatur
30 °C
T-Start
07.02.2007
v_sollwert_aussentemp_abhaengig_pa.vsd
S1 Setpoint1
S2 Setpoint2
P-Min SA Minimum pressure
T-min Minimum temperature
T-Start Setpoint reducing will start below this outside temperature
AT Outdoor temperature
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Band SA
T-Start SA
Setpoint reducing will start below this outside temperature
T-Start SA
P-Min SA
Minimum pressure for very low outside temperature
P-Min SA
L-BAL-E095-GB 1203 Index 004
Part.-No.
31/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.5
9.5.1
Programming
Volume control 5.01 ... 5.02
Basic setting 5.01 and 5.02
Base setup
Setting
Mode
Mode selection e.g. 5.01
Base setup
E2 Analog In
K Factor
E2 Analog In
In all group operating modes 5 ( 5.01 and 5.02 ) “E2 Analog In” factory setting
“DSG200.”
Selection sensor measuring range: “DSG 50”, * “DSG100”, “DSG200”, * “DSG300”,
“DSG500”, “DSG1000”, “DSG2000”, “DSG4000”, “DSG6000”
(* no standard type).
K Factor
Input of the “K factor” dependent on the fan (inlet duct).
setting range: 0...7.000
Factory setting: 75
E2 Offset
Sensor calibration with calibrated comparison device
E2 Offset
E3 Function
E3 Function (only for special applications)
• External setpoint = Function |1E | by external signal (0 - 10 V) instead of
0 - 100 % setting range
“Setpoint 1”. 0 - 10 V
External
manual
operation
via
external signal (0 - 10 V) = Function |2E | Switch
•
over between settings on the device and external manual operation via digital
input (
IO Setup: fuction |7D | ).
• Measurement value = function |7E | e.g. for limit indication, display in Info menu
“E2 Actual”
Modes 5.02 with two sensors
Modes with two sensors The function is automatically jointly programmed in operating
modes using 2 sensors. The second analog input is thus allocated and additional
function allocations are not possible. For 5.02 E3 Function at |6E | preprogrammed =
sensor for setpoint lowering. Pre-programmed sensor type “KTY”.
9.5.2
Setting for operation modes 5.01 ... 5.02
• 5.01 Volume control, Setpoint in m3/h
• 5.02 Volume control for ventilation systems setpoint depending on outdoor temperature.
Setting
Setting
Setpoint1
Setpoint2
L-BAL-E095-GB 1203 Index 004
Setpoint1
Setpoint in m3/h (m3/s)
Setting range: depending on measuring range of sensor and “K factor”
Factory setting: 530 m3/h
Setpoint2
Setting “Setpoint 2” e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
IO Setup).
Display: | - - - - - |
Part.-No.
32/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: depending on measuring range of sensor and “K factor”
Factory setting: 530 m3/h
Pband
Min. Speed
Max. Speed
Manual mode
Speed man.
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Manual mode
“OFF” = automatic control as function of the set parameters (Factory setting)
“ON” = automatic control without function, speed setting in menu “Speed manual”
Speed Manual mode
Manual speed setting without influence by the external signal.
IO Setup).
Activation by menu “Manual mode” or external contact at digital input (
Setting range: 0 rpm...Rated speed, Factory setting: 200 rpm
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Additional menu item for mode 5.02 with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
Sollwert 1
[m3/h]
Sollwert 2
[m3/h]
An outside temperature compensation can be
activated (sensor connection “E2” to “Analog In
2”) when being operated as a air volume regulation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active Setpoint 1/2 is automatically
changed proportional to the measured outside
Info: “Setpoint control”).
temperature (
P-min SA
[m3/h]
Außentemperatur
-15 °C
min. Temperatur
30 °C
T-Start
07.02.2007
v_sollwert_aussentemp_abhaengig_m3h.vsd
S1 Setpoint1
S2 Setpoint2
P-Min SA Minimum air volume
T-min Minimum temperature
T-Start Setpoint reducing will start below this outside temperature
AT Outdoor temperature
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Band SA
T-Start SA
Setpoint reducing will start below this outside temperature
T-Start SA
P-Min SA
Minimum pressure for very low outside temperature
P-Min SA
L-BAL-E095-GB 1203 Index 004
Part.-No.
33/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.6
9.6.1
Programming
Air velocity control 6.01
Base setup 6.01
Base setup
Base setup
Mode
Mode selection 6.01
Mode
E2 Analog In
E2 Analog In
For mode 6.01 “E2 Analog In” factory setting to “MAL1”
Selection sensor measuring range: MAL1, MAL10
Alternative selection signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA.
The sensor measurement range must be entered in order to display the actual value
correctly. Example with a 0 - 10 V sensor and 0 - 5 m/s measurement range (proportional output signal).
E2 Analog In = 0 - 10 V, E2 Min. = 0.0 m/s, E2 Max. = 5.0 m/s, E2 Decimals = 1, E2
Unit = m/s
Sensor calibration with calibrated comparison device
E2 Offset
E3 Function
E3 Function (only for special applications)
• External setpoint = Function |1E | by external signal (0 - 10 V) instead of
0 - 100 % setting range
“Setpoint 1”. 0 - 10 V
• External manual operation via external signal (0 - 10 V) = Function |2E | Switch
over between settings on the device and external manual operation via digital
input (
IO Setup: fuction |7D | ).
• Measurement value = function |7E | e.g. for limit indication, display in Info menu
“E3 Actual.”
L-BAL-E095-GB 1203 Index 004
Part.-No.
34/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.6.2
Programming
Settings for operation modes 6.01
Setting
Setting
Setpoint1
Setpoint2
Pband
Min. Speed
Max. Speed
Manual mode
Speed man.
L-BAL-E095-GB 1203 Index 004
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Setpoint2
Setting “Setpoint 2” e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
IOSetup).
Display: | - - - - - |
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Min. Speed
Setting range: 0 rpm... “Max. Speed”
Factory setting: 0 rpm
Max. Speed
Setting range: Rated speed...0 rpm (takes priority over setting “Min. Speed”)
Factory setting: Rated speed
Manual mode
“OFF” = automatic control as function of the set parameters (Factory setting)
“ON” = automatic control without function, speed setting in menu “Speed manual”
Speed Manual mode
Manual speed setting without influence by the external signal.
Activation by menu “Manual mode” or external contact at digital input (
IO Setup).
Setting range: 0...100 %, Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Part.-No.
35/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.7
Programming
Menu group Start
Start
Start
PIN input
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN 0010
Opening “service menu”, if PIN-protection activated Menu (
PIN 1234
Opening “setting”.
if “set protection” = “ON” (
menu structure).
Controller Setup).
PIN 9090
Restore user setting.
PIN 9091
Save user setting (corresponds function “Save user setup” = “ON”
Controller Setup).
PIN 9095
Restore factory setting = delivery status.
Exception, the following parameters are not set back: Min. Speed, Max. Speed, all
settings in Motor Setup.
Language
Menu language by the factory set to English.
In this menu different national languages can be selected (GB = English, D = German
...).
Reset
Complete re-start of the device.
Reset
Mode
Query of the operating mode (e.g. 1.01 for speed controller).
Mode
ECblue Premium
Software version Modul.
ECblue Premium
Basic Version
software version motorcontroller.
Basic Version
Individual unit number.
SN: 09303459d336
L-BAL-E095-GB 1203 Index 004
Part.-No.
36/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.8
Programming
Menu group Info
Menu group Info
Info
Info for mode speed controller 1.01
Speed
Speed
Display of motor current, different from the input current (metering precision approx.
+/-10%)
Motor current
Set external1
The percentage corresponds to the internal actuation of the power component under
consideration of the settings “Min. speed” and “Max. speed”.
0 - 10 V, 10 - 0 V, 0 - 20 mA, 20 - 0 mA, 4 - 20 mA, 20 - 4 mA
0 - 100 %
Display:
The device operates at:
Set “external1”
Signal to “E2” / “GND”
Set “External2”
Signal to “E3” / “GND”
Set “Intern1”
Menu “Set Intern1”
Set “Intern2”
Menu “Set Intern2”
Info for mode controller 2.01 ... 6.01
Current actual value measured on the sensor 1.
Depending sensor-type in: mbr, m3/s, m/s, Pa, %, bar, m3/h, °C, V, mA, etc.
E2 Actual
For operation with two sensors display for “2 actual”.
If function not active, display | - - - - - |
E3 Actual
Setpoint1
Display of the active target value at which the device operates.
“Setpoint1” Menu “Setting”
“Setpoint2” Menu “Setting”
“Ext. Setpoint” = setting by external signal 0 - 10 V. With activated manual mode the
display constantly changes between actual value and value for manual mode.
Speed
Speed
Motor current (deviating to input current)
Motor current
Min. speed cut off
L-BAL-E095-GB 1203 Index 004
Momentarily status for minimum speed cut off
“ON” = switch off, if Setpoint (+/- “Min. speed cut off”) is reached.
“OFF” = no switch off that means operation with minimum rate of air.
Part.-No.
37/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.9
Programming
Controller Setup
Controller Setup
Controller Setup
9.9.1
PIN protection activate, PIN 0010
PIN Protection
The adjustments for the installation in the service level can be protected against
unintentional modifications. To do this, activate the “PIN protection” = “ON”.
In order to simplify the initial start-up operation, the service level in the factory setting is
free = “OFF” i.e. accessible without PIN 0010.
Information
After installation of the device has been carried out, “PIN-Protection” should be activated = “ON”
9.9.2
PIN protection activate, PIN 1234
Set protection
The “Settings” menu for the user’s basic settings (Setpoint, default value, min, max ..)
are freely accessible when using the factory settings (i.e. without “PIN”).
If necessary, these can also be protected against unauthorized modifications by using
a “PIN 1234” . For this, the settings protection must be programmed to “ON”. The
settings menu is then no longer visible without inputting a PIN!
Function only in combination with activated PIN-Protection!
9.9.3
Save user settings restore with PIN 9090
Save User Setup
The individually made device configurations (User Settings) can be saved and, with the
corresponding PIN input (9091), can be reestablished.
By entering PIN 9090 the individually made device configurations can be reestablished
Start - PIN Input).
Information
By entering “PIN 9095” in the “PIN” menu in the “start” menu-group, the device is entirely
reset to the pre-delivery condition.
Any changes that have been made to the settings are thus lost!
9.9.4
Sensor Alarm ON / OFF
Function only in controller mode ( 2.01 )!
For “E2 Analog In” and if activated for sensor 2 “E3 Analog In”.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the device’s measurement range, a time-delayed fault indication takes place.
With “Alarm Sensors” = “OFF” (factory setting). Indicated
sensor disturbances are displayed as “Message” alternating
to the actual value and stored in the menu of “Events”.
Alarm sensors
Alarm sensors
L-BAL-E095-GB 1203 Index 004
Sensor 1
With “AlarmSensors” = “ON” areindicated sensor disturbances as “Alarm” alternating to the actual value and stored in
the menu of “Events”.
Indication via relays is possible ( IO Setup / function relay
outputs).
Part.-No.
38/68
Sensor 1
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.9.5
Programming
Limit
Limit
IO Setup) an adjustable limitation of the modulation
After allocation of a digital input (
can be activated via a digital input (“D1”, “D2”, ..).
As long as no allocation has been carried out “IO Setup”. Display: | - - - - |
“Limit value” = max. possible modulation (e.g.
speed reduction during night operation by
time switch).
Setting range: “Limit” = “n-max” up to “n-min”.
max. modulation, i.
Factory setting: 100 %
e. no limit.
Setting depending on device tye in: % or rpm.
nM
L= 70% Min.= 0 % Max. = 100 %
100 %
L = 70% Min. = 35 % Max. = 85 %
50 %
Min.
10.05.2007
v_limit.vsd
0%
50 %
100 % D
Limit (idealized principle diagram)
nM Motor speed
L Limit
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
9.9.6
Minimum speed cut off
This function is primarily significant for installation of the device as a pure P Controller
in refrigeration and air-conditioning technology.
For operation mode speed controller 1.01 without function!
Min. speed cut off
Msco = OFF (factory setting)
If no “Min. speed” is adjusted, the fan stops with
reaching the desired value.
If “Min. speed” is adjusted (e.g. 20%), then no disconnection of the fan takes place. I.e., always a
minimum ventilation is ensured (fan does not go
under setting “Min. speed”).
nM
100 %
50 %
Msco. e.g. -2.0 K
It takes place a disconnection from setting “Min.
speed”to “0”, if the given difference is reached related to the desired value.
At a plus value (+) before reaching the desired value
At a minus value (-) after falling below the desired
value.
Min. 35 %
Max. = 100 %
-2.0 K
Min.
20 °C
7K
27 °C
10.05.2007
v_min_luft_abschalt.vsd
Minimum speed cut off (idealized principle diagram)
nM Motor speed
S Setpoint
R Pband
I Actual value
L-BAL-E095-GB 1203 Index 004
Part.-No.
39/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.9.7
Programming
Second Group
Group 2 ON value
nmin at Group2
Second group “indirectly controlled” (picture A)
Analog output “AnalogOut 1” in IO Setup function |5 A | = group control is programmed.
This output is employed as the default signal for a speed controller. If the default signal
or the regulation deviation exceeds the group 2 switch-on point, group 1 is reduced to
“n-min group 2”. Starting here, both groups run parallel at maximum power.
Second group “100 % energized” (picture B)
Relay output (K1 or K2) in IO Setup function |8K | = group control is programmed. A
contactor is triggered via this relay contact, which directly switches the fans of the
second group to mains voltage. If the default signal or the regulation deviation exceeds
the “Group 2 ON value” switch-on point, the relay for the second group switches on and
the speed of the first group is lowered to an adjustable minimum value. After that, the
speed of the first group increases back up to maximum.
Controller
0 .. 100 %
Controller
Master
0 .. 100 %
Master
Si/ Se
Si/ Se
ON / OFF
Si 0-10 V
Controller
0 .. 100 %
0 / 100 %
Slave
10.05.2007
v_zweite_gruppe.vsd
N Line
Si Signal
Se Sensor
C Contactor
9.9.8
Reverse action of the control function
Val>Set=n+
For the effect of the regulation there are two functions:
• ON for “Val > Set = n+” increasing Fanlevel for increasing actual value over
Setpoint.
• OFF for “Val > Set = n+” increasing Fanlevel for decreasing actual value
below Setpoint.
For special applications an external switch over of the control function is possible (
IO Setup).
Factory setting depending
on selected mode
Mode
Controller
function
1.01
non
2.01 ...
ON
3.01 ...
ON
4.01 ...
OFF
5.01 ...
OFF
6.01 ...
OFF
Example for temperature control (Idealized principle diagram)
nM
100 %
OFF
ON
nM Motor speed
R Pband
S Setpoint
I Actual value
OFF for Val > Set = n+ = heating function
ON for Val > Set = n+ = cooling function
L-BAL-E095-GB 1203 Index 004
Part.-No.
40/68
10.05.2007
v_umkehr_regelfunktion.vsd
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.9.9
Programming
Controller configuration
The “controller configuration” is automatically carried out during selection of the application related
mode of operation (Base setup). The factory presets in accordance with the mode of operation are
based on many years of experience, which is suitable for many applications. Under special circumstances, these can be individually adapted ( Menu group “setting”).
Type of control
The type of control determines the method with which the controlled value behaves in
case of a difference between the target and current values. For this, the control
technology has standard algorithms, which consist of a combination of three methods:
Selection P, PID:
• P control (Proportional component, proportion of the absolute deviation)
• I control (Integral component, proportion of the sum of all deviations)
• D control (Differential component, proportion of the last difference)
With pure P controllers (controller type P), the following described settings do not have any function.
If needed, the most suitable combination for the respective control system can be determined from these
proportions.
KP
KI
KD
TI
P-component = reaction time
Setting range: 0 - 200 %
smaller = more slowly
bigger = faster
I-component = accuracy, correction time
Setting range: 0 - 200 %
bigger = faster
smaller = more slowly
D-component
More “D-component” causes more stability by a clean actual value signal with shorter
correction times
By a actual value signal with a superposition should be done to attitude without “Dcomponent” → 0 %
Setting range: 0 - 200 %
value smaller = less “D-component”
value higher = more “D-component”
Integration time = correction time
Setting range: 0 - 200 %
smaller = faster
bigger = more slowly
9.9.10
Data on the total control deviation
The total control deviation is comprised of the sum of the control deviations for performance quantities
and work quantities combined and refers to the specified areas.
In direct reference to the acquired input and controlled variables, the maximum deviation to the target
value is < ± 5 %. By activating the menu-assisted adjustment, the total control deviation can be
reduced to a value of < ± 1 %.
For indirect reference of the acquired input value to the controlled variable, i.e., two physical variables
still need to be converted, the deviation can be reduced to < ± 5 % through adjustment.
In the case of an internal default value through the integrated or external terminal, the control deviation
remains at < ±0.5%.
9.9.11
LED Mode
For motor sizes “D” and “G” there is a status LED in the cover of the controller housing.
|ON |
Status LED in ECblue active i.e. operating conditions are indicated by flash
code (factory setting).
|OFF |
Status LED not active, i.e. always OFF.
LED Mode
L-BAL-E095-GB 1203 Index 004
Part.-No.
41/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.10
Programming
IO Setup
IO Setup
IO Setup
9.10.1
Analog-Output “A”
The analog outputs 0 - 10 V can be allocated with various functions.
Terminals “A” - “GND” = Analog Out (Imax 10 mA)
A Function
With the attitudes “A min” and “A max” the characteristic of the output voltage can be
adapted.
Setting range: “A min.” = 0 - 5 V, “A max.” = 10 - 5 V
Factory setting: “A min.” = 0 V, “A max.” = 10 V
A min.
A max.
With the attitudes “A Inverting” the output voltage can inverted.
Factory setting: “A Inverting” = “OFF”
A Inverting
Function
OFF
Description
without function
1A
Constant voltage +10 V (factory setting)
2A
Proportional the internal control of modulation with consideration “Min. speed” and “Max.
speed” setting.
• for enable “OFF” it goes back to 0 V
• for motor fault the output signal remains for a slave controller (“Master-Slave”
combination).
3A
proportional input “E2”
4A
proportional input “E3”
5A
Group control (
6A
Control output 2 increasing modulation at actual value > Set = cooling (only mode 2.03
temperature controller with additional functions).
7A
Control output 2 incresing modulation at actual value < Set (Heating) only mode 2.03 temperature controller with additional functions).
9A
Output speed
ratio: actual speed / rated speed (for 10 V actual speed = rated speed)
L-BAL-E095-GB 1203 Index 004
Controller Setup - second group)
Part.-No.
42/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
A1 Function | 3A | / | 4A |
A1 Function “A min.” and “A max.”
Analog
Out
10 V
10 V
A max: 10 – 5V
5V
5V
A min: 0 – 5V
Funktion
Signal
50
100 0 -100 %
16.03.2007
v_a1_funktion_amin_amax.vsd
10
10
20
18
5,6
16
7,2
14
8,8
12
10,4
10
10
12
12
14
16
18
13,6 15,2 16,8 18,4
20
20
20
-27
-16.8
18,4 16,8 15,2 13,6
-6.6 3.6 13.8
12
24
10,4 8,8 7,2 5,6
34,2 44.4 54.6 64.8
+75
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
TF.. (KTY)
16.03.2007
v_a1_funktion_3a_4a.vsd
9.10.2
9.10.2.1
Digital inputs “D1” / “D2” (E1)
Menu overview
The digital inputs Digital In 1 (D1) and Digital In 2 (D2) can be allocated with various
functions.
Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
D1 Function
Inverting “D1” and “D2” possible
D1 Inverting
With networking the digital inputs can be replaced by control over bus.
With mode of operation 4.03 pre-setting of “D1” and “D2” is |ON | .
D1 Busmode
Attention!
Never apply line voltage to the digital input!
Function
Description
OFF
No function
1D
Enable (remote control) “ON” / “OFF”
2D
External error
3D
“Limit” ON / OFF
4D
Switch over “E1” / “E3”
5D
Switch over “Setpoint Intern1” / “Setpoint Intern2”
6D
Switch over “Intern” / “Extern”
For mode speed controller 1.01
For modes as controller higher 2.01
5D
Switch over “Setpoint1” / “Setpoint2”
6D
Switch over “Intern” / “Extern”
7D
Switch over “automatic control” / “Speed manual”
8D
Switch over control function (e.g. “heating” / “cooling”)
L-BAL-E095-GB 1203 Index 004
Part.-No.
43/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
10D
9.10.2.2
Programming
“Reset”
11D
Setting Max. Speed “ON” / “OFF”
13D
Switch over direction of rotation “right” / “ left”
14D
“Freeze function” = maintain momentary modulation value
Enable ON/OFF function |1D |
Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via floating contact.
The power section is electronically disconnected. Operation of the device is still possible after
pressing the “ESC” hotkey combination in switched-off condition. Signal- in and outputs remain active.
• A programmed alarm relay (factory set “K1 function” = |2 K | ) does not report the switch-off.
• A programmed operation indicator relay ( |1K | ) reports the switch-off.
Display STOP for switch OFF
• Controller “ON” for closed contact
(factory setting).
• Controller “OFF” with opened contact
When inverting in reverse i.e. equipment
“OFF” with closed contact.
Digital IN 1
24V
D1
Digital IN 1
24V
D1
25.06.2007
v_1d_24v_freigabe.vsd
ON
OFF
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4 §6)!
9.10.2.3
External fault Function |2D |
Connecting an external alarm indication (via floating contact). The device continues to work unchanged during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1) ( IO Setup function K1).
• Indication during closed contact (factory setting): “D1 Inverting” = “OFF ”
• Indication during opened contact: “D1 Inverting” = “ON ”
Alarm symbol for indication “External fault”
Actual value
L-BAL-E095-GB 1203 Index 004
Part.-No.
44/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.10.2.4
Programming
Limit ON / OFF, Function |3D |
The value for “Limit” adjusted in the Controller Setup, is activated over a digital input.
Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
For “D1” Inverting“OFF”, limitation active at closed contact.
-----
Controller
1 n = 0- 80 %
0 n = 0- 100 %
24V
D1 D1
10.05.2007
v_3d_limit.vsd
0 1
9.10.2.5
Setting “Limit” (depending on device type in: %, Hz, rpm)
Switch over Input signal “E2” / “E3”, Function |4D |
Switch over between Input signal 1 (Analog In 1 terminal “E2”) and input signal 2 (Analog In 3 terminal
“E3”).
Contact at digital input e.g. “Digital In 1”= terminals “D1” - “24 V”
Si 1
Si 2
Controller
E2
Si 1
GND
E3
n = 0- 100 %
Si 2
GND
24V D1
17.09.2009
v_4d_umschaltung_e2_e3.vsd
0 1
Si 1
Si 2
Signal 1
Signal 2
For mode speed controller ( 1.01 ) Base setup for “E3 Analog In”: |1E | necessary.
For modes controller (higher 2.01 ..) Base setup for “E3 Analog In”: |7E | necessary (as far as
otherwise does not occupy).
9.10.2.6
Set 1/2 or Setpoint 1/2, Function |5D |
Switch over between “Set Intern1” and “Set Intern2” (for speed controller 1.01 )
Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
• “D1 Inverting” = “OFF”: “Set Intern1” at
-----
Controller
n = 40 %
n = 80 %
•
24V
D1 D1
-----
11.05.2007
v_5d_vorgabe_intern_1_2.vsd
0 1
Setting “Set Intern1” (depending on device type in: %, Hz, rpm)
Setting “Set Intern2” (depending on device type in: %, Hz, rpm)
L-BAL-E095-GB 1203 Index 004
Part.-No.
45/68
opened contact / “Set Intern2” at closed
contact.
“D1 Inverting” = “ON”: “Set Intern1” at
closed contact / “Set Intern2” at opened
contact.
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Operation with “Set Intern2” is signalized by the moon symbol for reduced operation.
“Set extern1” under “settings” must be programmed to “OFF”.
Frequency
Switch over between “Setpoint1” and “Setpoint2” (for modes as controller higher 2.01 )
Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
• “D1 Inverting” = “OFF”: “Setpoint1” =
-----
Controller
n = 0 – 100 %
•
24V
D1 D1
-----
Sensor
18 °C at opened contact / “Setpoint2” =
25 °C at closed contact.
“D1 Inverting” = “ON”: “Setpoint1” = 18
°C at closed contact / “Setpoint2” = 25
°C at opened contact.
11.05.2007
v_5d_sollwert_1_2.vsd
0 1
Setting “Setpoint1”
Setting “Setpoint2”
Operation with “Setpoint2” is signalized by the moon symbol for reduced operation.
E1 Actual
9.10.2.7
Intern / Extern Function |6D |
Switch over between Set Intern and Set Extern (for mode speed controller 1.01 ). “Set extern1”
under settings must be programmed to “OFF”.
Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
• “D1 Inverting” = “OFF”: “Set Intern1” at
E2
Si 40 %
Controller
n = 40 %
n = 80 %
•
24V
D1 D1
-----
opened contact / “Setting Extern” at
closed contact.
“D1 Inverting” = “ON”: “Set Intern1” at
closed contact / “Set Extern” at opened
contact.
16.11.2009
v_6d_vorgabe_intern_extern_e2.vsd
0 1
Si Signal
1 Setting “Set Intern1” (depending on device type in: %, Hz, rpm)
“Setpoint1” / “external Setpoint” (modes 2.01 )
Under Base setup “E3 function” programmed to function |1E | for “external setpoint” .
Contact at digital input e. g. “Digital In 1” = “D1” - “24 V”
• “D1 Inverting” = “ON”: Setting at the unit
-----
ES
Controller
n = 0 – 100 %
•
E3
24 V D1
Se
16.09.2009
v_6d_sollwert1_externer_sollwert_e3.vsd
0 1
1 Setting “Setpoint1”
ES External Setpoint e.g. 5 V
Se Sensor
L-BAL-E095-GB 1203 Index 004
23.8°C
Part.-No.
46/68
at opened contact / Signal Extern at
closed contact
“D1 Inverting” = “OFF”: Setting at the
unit at closed contact / Signal Extern at
opened contact
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.10.2.8
Programming
Automatic control / speed manual, Function |7D | (mode 2.01 )
Switch over between automatic control to set target value (depending on the activation: “Setpoint1”,
“Setpoint2”) and the default for “manual operation” set at the device.
If for Analog In 2 “E3 function” is programmed to |2E | switch over between “Setpoint1” or “Setpoint2”
and external manual operation. With activated manual mode the display constantly changes between
“actual value” and value for “manual mode”.
Contact at digital input e.g. “Digital In 1”
• “D1 Inverting” = “OFF” Automatic
•
-----
-----
-----
Controller
1 n = 0 -100 %
ES
control at opened contact / manual
operation at closed contact.
“D1 Inverting” = “ON”: Automatic control
at closed contact / manual operation at
opened contact.
n = 80 %
E3
24 V D1 E2
Se
16.09.2009
v_7d_regelung_hand_e2_e3.vsd
0 1
1 Setting “Setpoint1”
2 Setting “Setpoint2”
3 Setting “Speed manual” (depending on device type in: %, Hz, rpm)
EH Signal for Manual mode extern, E3 Function = |2E |
Se Sensor
9.10.2.9
Reverse action of control function ( 2.01 ), Function |8D |
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the “Control function” are dependent on the selected mode of operation (
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function than the one set
there!
Settings in Controller Setup
Val>Set=n+
9.10.2.10
Reset, Function |10D |
Complete re-start of the device.
•
Contact at digital input e.g. “Digital In 1”
L-BAL-E095-GB 1203 Index 004
Part.-No.
47/68
For “D1 Inverting” = “OFF” both
terminals “D1”- “24 V” in normal
operation interrupted. Reset after fault by
short close.(For “Inverting” = “ON”
reverse function).
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.10.2.11
Programming
Setting Max. Speed ON / OFF function |11D |
The value for “Max Speed” adjusted in menu “Settings”, is activated over a digital input. I.e. the unit
works independently of the controller function firm with this value.
Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” “24 V”).
• “D1 Inverting” = “OFF”: “Max. Speed”
active at closed contact
• “D1 Inverting” = “ON”: “Max. Speed”
-----
Controller
active at opened contact
= 80 %
= 0 .. 100 %
24V
D1 D1
15.05.2009
v_11d_max_drehzahl.vsd
0 1
9.10.2.12
Setting “Max. Speed” (depending on device type in: %, Hz, rpm)
Direction of rotation, Function |13D |
Switch over “clockwise” rotation and “counterclockwise” rotation. When switching over via a digital
input, the device works with the opposite function than the one set in motorsetup.
Information
If the rotary direction is reversed with an available modulation, it is initially reduced to “0”
(disconnected) and subsequently increased back to the default value.
Contact e.g. by digital input “Digital In 1” for factory setting “ clockwise rotation.”
• “D1 Invertierung” = “OFF”: “Clockwise” at opened contact / “Counterclockwise” at closed
contact.
• “D1 Invertierung” = “ON ”: “Counterclockwise” at opened contact / “Clockwise” at closed contact.
9.10.2.13
“Freeze function” = maintain momentary modulation value, Function |14D |
The device continues to work so long independently of the controller function with the momentary
value of the modulation and / or speed as activated over the digital input.
Message indicated alternating with the active value “Freeze Function”
Freeze
Contact at digital input e.g. “Digital In 1”
“D1 Inverting” = “OFF”: “Freeze function” at closed contact activ
“D1 Inverting” = “ON”: “Freeze function” at opened contact activ
L-BAL-E095-GB 1203 Index 004
Part.-No.
48/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.10.3
9.10.3.1
Programming
Configuration of analog inputs “E1”and “E3”
Signal adaption E2 and E3
If required, an adaptation of the specification signal / speed characteristic curve is possible
Information
These settings are mostly practical for the operating mode 1.01 with rotational speed specification
over an external signal. In operating modes (as of 2.01) this setting is not suited for influencing the
regulation process.
E2 Mode
E2 min.
E2 max.
E2 Mode
E2 min.
E2 max.
L-BAL-E095-GB 1203 Index 004
E2 Mode
|0 | = E2 min. / E2 max. without function (factory setting)
|1 | = Offset / turn
|2 | = signal range
E2 min.
Setting range: 0 - 100 %
Factory setting: 0 %
E2 max.
Setting range: 0 - 100 %
Factory setting: 100 %
E3 Mode
|0 | = E2 min. / E2 max. without function (factory setting)
|1 | = Offset / turn
|2 | = signal range
E3 min.
Setting range: 0 - 100 %
Factory setting: 0 %
E3 max.
Setting range: 0 - 100 %
Factory setting: 100 %
Part.-No.
49/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Example for Mode “1.01” with speed setting signal 0 - 10 V
Modus 1
Example: “E2 min.” = 20 %
The controller begins only at approx. 20% higher
signal with minimal speed.
Modus 1
n [%]
100
80
60
E2 min. = 0 %, E2 max. = 100 %
E2 min. = 0 %, E2 max. = 80 %
E2 min. = 25 %, E2 max. = 100 %
E2 min. = 20 %, E2 max. = 80 %
Example: “E2 max.” = 80 %
Speed rises linear to 100% speed with 80% setting
signal.
40
20
Si E
10
0 – 10 V
16.11.2009
v_e2_modus_1_prz.vsd
Modus 2
Example: “E2 min.” = 30 %
Only with approx. 30 % setting signal the controller
begins with approx. 30% speed.
Modus 2
n [%]
100
80
60
E2 min. = 0 %, E2 max. = 100 %
E2 min. = 0 %, E2 max. = 80 %
E2 min. = 40 %, E2 max. = 100 %
E2 min. = 30 %, E2 max. = 90 %
Example: “E2 max.” = 80 %
Over 80 % setting signal the speed is switched to
100 %.
40
20
Si E
10
0 – 10 V
16.11.2009
v_e2_modus_2_prz.vsd
n = speed of motor, Si E = setting signal input
Idealized principle diagrams for setting:
“Min. Speed” = 0 % and “Max. Speed” = 100 %
9.10.3.2
Inverting analog inputs “E2” / “E3”
After programming the signal or sensor type, an inversion of the inputs can be carried out.
E2 Inverting
Factory setting for Inverting inputs = “OFF” (if input activated) (signal: 0 - 10 V, 0 - 20
mA, 4 - 20 mA).
For activation using inverted default signals or sensors with inverted output signals
proportional to the measurement range, switch inverting to “ON” (Signal: 10 - 0 V, 20 - 0
mA, 20 - 4 mA).
E3 Inverting
L-BAL-E095-GB 1203 Index 004
Part.-No.
50/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Programming
Example: mode 1.01 speed controller, setting by external signal
n Motor
100 %
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
50 %
Min.
Signal
10
20
18
5,6
16
7,2
14
8,8
12
10,4
10
10
12
12
14
16
18
13,6 15,2 16,8 18,4
20
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
10
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
Invertierung
OFF
Invertierung
ON
15.03.2007
v_invertierung_anlaog_eingaenge.vsd
nM Motor speed
Si Signal
OFF Inverting = OFF
ON Inverting = ON
9.10.4
Function and inverting for relay outputs “K1”
Various functions can be allocated to the relay outputs “K1”.
This is preset at the factory for fault indication.
K1 Function
K1 Inverting
Function
OFF
The relay inversion “K1” is set at the factory to “OFF” (when a function is programming).
Switch to “ON” for inversion (switch-time response depends on the allocated function).
Fundamentally, the relay can only become operative if the electronic’s voltage supply is
functioning. At least 2 current phases must be present!
Description
No function
Relays remain always de-energized
1K
Operating indication.
Operation without fault, reports enable “OFF”
2K
Fault indication (factory setting for “K1”, non inverting).
Energized for operation without fault, for enable “OFF” not energized. De-energized at line,
motor and controller fault, Sensor fault dependent on programming, external fault at digital
input.
3K
External fault separate with message at digital input (factory setting if terminals bridged)
4K
Limit modulation
Over or falling below limits for modulation
5K
Limit “E2”
When over or falling below limits for input signal “E2”
6K
Limit “E3”
When over or falling below limits for input signal “E3”
7K
For modes as controller higher 2.01
Setpoint Offset
Deviation between actual value and setpoint to high
8K
Switching on second group
For modes as temperature controller with additional functions 2.03
L-BAL-E095-GB 1203 Index 004
Part.-No.
51/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9K
Heating function
Switch ON point: temperature = Setpoint +/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
10K
Cooling function
Switch ON point: temperature = Setpoint +/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
Programming
K1
1 = energized, terminals 11 - 14 bridged
0 = de-energized 11 - 14 not bridged
11
14
17.09.2009
v_relais_k1_11_14.vsd
K1
Function Status Controller
K1
1 = energized
0 = de-energized
Inverting
9.10.5
OFF
ON
1K
Operation without fault, line supply okay
2K
Fault with indication by relay
3K
Ext. Fault at digital input for external fault
4K
Over or falling below limits for modulation
5K
over or falling below limits for input signal “E2”
6K
over or falling below limits for input signal “E3”
7K
setpoint deviation to high
Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
The device address (Device-ID) is factory set to the highest available MODBUS address: 247
This address is reserved for operation with an external terminal model AXG.. and should not be
occupied with anything else.
Bus Address
Bus Address
The addresses of the individual units must be continuously numbered beginning with
“1”. No address may be allocated twice. MODBUS address adjustable from 1-247.
Address 247 = preprogrammed for an external terminal.
Addressing
Switch addressing to “ON” before setting “address”.
Addressing
Reading and writing parameters
The device supports reading and writing processes for MODBUS Holding Registers. The start address
is 0; the number of registers depends on the device. If the allowable start address or number is
exceeded, the device answers with an exception code. The description of the register is device
dependent and can be requested from service for the device/version concerned.
9.11
Limits
Menu group Limits
Limits
L-BAL-E095-GB 1203 Index 004
Part.-No.
52/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.11.1
Programming
Limit indication depending on modulation
Following functions can be allocated to the limit indication
Level. Function
OFF
without function
1L
Indication with the centralized fault of a programmed relay (IO allocation
Function |2K | ).
Warning symbol in display, “AL” code in events memory.
2L
Is merely displayed in the events menu as message “msg”.
In the IO setup, a separate relay can be allocated independent of these settings.
If the modulation exceeds the set “Level max” value, this is reported until the set value
“Level min” has been undercut.
The indication is delayed by the time set in “Display delay”.
Level min.
Level max.
Time delay exceeding “Level max.” up to indication by relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Level Delay
Example indication by relay “K1”:
Inverting
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
not inverted
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
min
max
100 %
min
100 %
max
max
min
100 %
max
11.05.2007
v_grenzwert_ausst_k1_ni.vsd
Modulation
min
100 %
11.05.2007
v_grenzwert_ausst_k1_i.vsd
Modulation
If “Level min.” is higher than “Level max.”, the “Level max.” switching point is without hysteresi.
9.11.2
Limit indication depending on setting or sensor signal
Following functions can be allocated to the limit indication
Lmt E2 Function
OFF
without function
1L
Indication with the centralized fault of a programmed relay (IO allocation
Function |2K | ).
Warning symbol in display, “AL” code in events memory.
2L
Is merely displayed in the events menu as message “msg”.
In the IO setup, a separate relay can be allocated independent of these settings.
L-BAL-E095-GB 1203 Index 004
Part.-No.
53/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Lmt E2 min.
Lmt E2 max
Programming
Both values for E2 (“E2 min” and “E2 max”) can be set independent of each other and
act on a relay together if correspondingly programmed. If a function is activated or if a
relay is allocated, both settings (“min” and “max”) are initially at “OFF”.
Work can be carried out with one as well as with both limit indicators.
The same setting applies to “E3 Min.” and “E3 Max.”, described below for “E2”.
Undercutting the signal (“E2 min”).
If the signal undercuts the set value “E2 min”, this is reported until the set value (plus
adjustable hysteresis) has been exceeded once again.
Exceeding the signal (“E2 max”).
If the signal exceeds the set value “E2 max”, this is reported until the set value (minus
hysteresis) has been undercut once again.
E2 Hysteresis
Hysteresis adjustment in the unit of measure of the programmed input signal.
Lmt E2 Hyst.
Lmt E2 Del.
E2 Delay
Time delay exceeding “Level max.” up to indication by relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Information
Always adjust the value for the maximum input signal higher than the value for the minimum input
signal!
E2 Max. > E2 Min.
Example for a limit indication of default signal or sensor signal to “Analog In 1”
Analog IN
50 %
100 %
11.05.2007
v_grenzwert_signal_k1_1.vsd
Analog IN
50 %
100 %
Analog IN
50 %
100 %
Settings:
- E2 Min.: 20 %
- E2 Max.: OFF
- switching hysteresis 5 % (from
100 %)
11.05.2007
v_grenzwert_signal_k1_2.vsd
Settings:
- E2 Max.: 80 %
- E2 Min.: OFF
- switching hysteresis 5 % (from
100 %)
Settings:
- E2 Min.: 20 %
- E2 Max.: 80 %
- switching hysteresis 5 % (from
100 %)
11.05.2007
v_grenzwert_signal_k1_3.vsd
Terminal “E2” and “GND” alarm via relay “K1” (non-inverted) IO Setup → K1 function: |5 K | = limit
indicators
L-BAL-E095-GB 1203 Index 004
Part.-No.
54/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.11.3
Programming
Limit indication depending on (offset) to Setpoint
In operating modes as a controller (via 2.01 ), two limit indicators can be carried out based on the set
target value (Setpoint) and measured actual value (on E2).
Following functions can be allocated to the limit indication
Offset Function
OFF
without function
1L
Indication with the centralized fault of a programmed relay (IO allocation
function |2K | ) warning symbol in display, “AL” code in events memory.
2L
Is merely displayed in the events menu as message “msg”.
In the IO setup, a separate relay can be allocated independent of these settings.
Offset 1, Offset 2
Both values for Offset 1 and Offset 2 can be set independent of each other and act on
a relay together if correspondingly programmed. If a function is activated or if a relay is
allocated both settings (Offset 1 and Offset 2) are initially at “OFF”.
Work can be carried out with one as well as with both limit indicators.
Offset 1
“Offset 1” for alarm in case of an exceeding of the max. deviation between actual and
target.
Switch ON point: actual value = Setpoint +/- offset
Swtich OFF point: Actual value by hysteresis under the switch-on point
Offset 2
“Offset 2” for alarm in case of an undercutting of the max. deviation between actual and
target
Switch ON point: actual value = Setpoint +/- offset
Swtich OFF point: Actual value by hysteresis over the switch-on point
Offset Hysteresis
Hysteresis switch-on point: In temperature regulation + / - 10 K, otherwise sensors 10
% of measurement range
Offset Hyst.
Offset Delay
Time delay until indication through relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Offset Del.
Example for temperature regulation; for other modes of operation settings in corresponding sensor
unit.
Offset 2 for alarm during undercutting
OFF = 20°C - 2 K = 18 °C
11
13
15
17
19
21
23
25
27
[min]
ON
ON
ON
Example: Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
L-BAL-E095-GB 1203 Index 004
29
[°C]
30
28
26
24
22
20
18
16
14
12
10
OFF = 15°C + 2 K = 17 °C
16.03.2007
v_relais_kuehlen_10k_pos_offset.vsd
[°C]
ON = 15°C + 5 K = 20 °C
ON = 20°C - 5K = 15 °C
30
28
26
24
22
20
18
16
14
12
10
11
ON
13
15
17
[min]
19
21
23
25
27
ON
Example: Setpoint 15.0° C, Offset -5.0 K, Hysteresis 2.0 K
Part.-No.
55/68
29
16.03.2007
v_relais_heizen_9k_neg_offset.vsd
Offset 1 for alarm during exceeding
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.12
Programming
Motor Setup
Menu group Motorsetup
Motor Setup
9.12.1
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Rampdown time
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 2...250 sec.
Factory setting depending on motor
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 2...250 sec.
Factory setting depending on motor
0 .. 100 %
09.05.2007
v_hochlaufzeit_ruecklaufzeit.vsd
external Signal
Setting
Rampup time
Rampdown time
L-BAL-E095-GB 1203 Index 004
Part.-No.
56/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
9.12.2
Programming
Suppression of speeds
Suppression of up to three speed ranges.
Under certain circumstances, it is possible to prevent disturbing noises that can arise at certain
speeds due to resonances.
Example for suppression of 2 ranges (Idealized principle diagram)
100 %
50 %
35 % max
Setting depending on device type in: %, Hz,
rpm
15 % min
09.05.2007
v_ausblendung_prz.vsd
0%
100 % D
50 %
A Modulation
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
→
Factory setting no suppression active = “OFF”
→
Suppression1
Suppression1
→
Setting for “Range1 min.”
→
Range1 min.
Range1 min.
→
Setting for “Range1 max.”
→
Range1 max.
Range1 max.
→
Identical procedures for Suppression2 and Suppression3, as far as desired
Suppression2
L-BAL-E095-GB 1203 Index 004
Part.-No.
57/68
→
etc.
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
10
10.1
Menu tables
Menu tables
Menues of operating modes
Mode
1.01
2.01
2.03
2.04
2.02
2.05
Parameter
PIN input
3.03
3.04
4.01
4.02
4.03
5.01
5.02
6.01
-----
-----
-----
-----
3.01
3.02
Factory setting
-----
-----
-----
Start
-----
-----
Language
GB
GB
GB
GB
GB
GB
GB
GB
GB
Reset
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Mode
1.01
2.01
2.03
2.04
2.02
2.05
3.01
3.02
3.03
3.04
4.01
4.02
4.03
5.01
5.02
6.01
ECblue Premium
4.00
4.00
4.00
4.00
4.00
4.00
4.00
4.00
4.00
10.01
10.01
10.01
10.01
10.01
10.01
10.01
10.01
10.01
Basic Version
SN:
1727393- 1727393- 1727393- 1727393- 1727393- 1727393- 1727393- 1727393- 17273936FF33
6FF33
6FF33
6FF33
6FF33
6FF33
6FF33
6FF33
6FF33
Info
Actual value E2E3
-2.4 °C
Control value
(only 2.04, 3.03,
3.04)
30.0 °C
E2 Actual
30.0 °C
E3 Actual
(only 2.04, 2.05,
3.03, 3.04, 4.02,
4.03, 5.02)
30.0 °C
Setpoint1
20.0 °C
12.0 bar
22.6 °C
30.0 °C
30.0 °C
10.0 bar
9.5 °C
30.0 °C
5.0 °C
0.0 °C
12.0 bar
35.0°C
10.0 bar
9.5 °C
88.7 Pa 712 m3h
10.0 bar
9.5 °C
21.0 °C
21.0 °C
12.0 bar
35.0°C
100 Pa
530 m3h
100 Pa
530 m3h
Setpoint control
(only 4.02, 4.03,
5.02)
Speed
0.45 m/s
0.50 m/s
0 rpm
0 rpm
0 rpm
0 rpm
0 rpm
0 rpm
0 rpm
0 rpm
0 rpm
Motor current
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
Set external1
0 rpm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Msco
Setting
Set Intern1
200 rpm
Set Intern2
- - - - --
Setpoint1
20.0 °C
5.0 °C
0.0 °C
12.0 bar
35.0°C
12.0 bar
35.0°C
100 Pa
530 m3h
0.50 m/s
Setpoint2
-----
-----
-----
-----
-----
-----
-----
-----
Pband
5.0 K
20.0 K
5.0 K
5.0 bar
7.0 °C
5.0 bar
7.0 °C
100 Pa
530 m3h
0.50 m/s
0 rpm
0 rpm
0 rpm
0%
0%
0 rpm
0 rpm
0 rpm
Min. Speed *
Max. Speed *
Set external1
Manual mode
Speed man.
0 rpm
1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
200 rpm
200 rpm
200 rpm
200 rpm
200 rpm
200 rpm
200 rpm
200 rpm
L-BAL-E095-GB 1203 Index 004
Part.-No.
58/68
User Setting
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Mode
4.01
4.02
4.03
5.01
5.02
T-Band SA
4.02 +
4.03 =
30.0 K
5.02 =
30.0 K
T-Start SA
4.02 +
4.03 =
15.0 °C
5.02 =
15.0 °C
P-Min SA
4.02 +
5.02 =
4.03 =
70.0 m3h
70.0 Pa
1.01
2.01
2.03
2.04
Menu tables
2.02
3.01
3.02
2.05
Parameter
3.03
3.04
6.01
Factory setting
Offset AnalogOut
2.03 =
0.0 K
Pband AnalogOut
2.03 =
2.0 K
Min. AnalogOut
2.03 =
0%
Max. AnalogOut
2.03 =
100 %
OffsetDigitalOut
2.03 =
-1.0 K
Hyst.DigitalOut
2.03 =
1.0 K
Alarm Minimum
2.03 =
0.0 °C
Alarm Maximum
2.03 =
40.0 °C
Events
Base setup
Mode
E2 Analog In
1.01
0 - 10 V
2.01
2.03
2.04
KTY
2.02
KTY
3.01
3.02
2.05
KTY
E2 Refrigerant
(only 3.02 and
3.04)
3.03
3.04
0-30
MBG
0-30
MBG
R503
R503
-----
-----
4.01
4.02
4.03
5.01
5.02
6.01
DSG200
DSG200
0-1 MAL
E2 K-Factor
75
E2 Min.
-----
-----
-----
-----
-----
-----
E2 Max.
-----
-----
-----
-----
-----
-----
-----
-----
E2 Decimals
-----
-----
-----
-----
-----
-----
-----
-----
E2 Unit
-----
-----
-----
-----
-----
-----
-----
-----
0.0 bar
0.0 K
0.0 Pa
0.0 Pa
0.0 m/s
E2 Offset
E3 Function
E3 Analog In
E3 Refrigerant
(only 3.04)
OFF
-----
0.0 K
0.0 K
0.0 K
0.0 bar
0.0 K
OFF
2.04 =
4E
OFF
5E
OFF
4E
4.02 +
4.03 = 6E
5.02 =
6E
OFF
-----
0-30
MBG
4.02 =
TF
4.03 =
Bus
5.02 =
TF
OFF
-----
-----
R503
E3 K-Factor
L-BAL-E095-GB 1203 Index 004
75
Part.-No.
59/68
User Setting
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Mode
1.01
2.01
2.03
2.04
2.02
3.01
3.02
2.05
Parameter
Menu tables
3.03
3.04
4.01
4.02
4.03
5.01
5.02
6.01
Factory setting
E3 Min.
-----
-----
-----
4.03 = 35.0 °C
-----
-----
E3 Max.
-----
-----
-----
4.03 =
65.0 °C
-----
-----
E3 Decimals
-----
-----
-----
-----
-----
-----
E3 Unit
-----
-----
-----
4.03 = °C
-----
-----
0.0 bar
0.0 K
4.02 +
4.03 =
0.0 K
5.02 =
0.0 K
-----
E3 Offset
-----
-----
PIN Protection
OFF
OFF
OFF
Controller Setup
OFF
OFF
OFF
OFF
OFF
OFF
Set protection
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Save User Setup
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
-----
-----
-----
-----
-----
-----
-----
-----
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Alarm sensors
Limit
-----
Min. speed cut off
OFF
Group 2 ON
value
-----
-----
-----
-----
-----
-----
-----
-----
-----
nmin at Group2
-----
-----
-----
-----
-----
-----
-----
-----
-----
ON
ON
ON
ON
ON
OFF
OFF
OFF
Pid
Pid
Pid
50 %
50 %
50 %
50 %
50 %
50 %
50 %
50 %
Val > Set=n+
Type of control
KP
KI
50 %
50 %
50 %
50 %
50 %
50 %
50 %
50 %
KD
50 %
50 %
50 %
50 %
50 %
50 %
50 %
50 %
TI
0%
0%
0%
0%
0%
0%
0%
0%
ON
ON
ON
ON
ON
ON
ON
ON
ON
1A
1A (2.03
= 6A)
1A
1A
1A
1A
LED Mode
IO Setup
A Function
1A
1A
1A
A min.
0.0 V
0.0 V
0.0 V
0.0 V
0.0 V
0.0 V
0.0 V
0.0 V
0.0 V
A max.
10.0 V
10.0 V
10.0 V
10.0 V
10.0 V
10.0 V
10.0 V
10.0 V
10.0 V
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
A Inverting
D1 Function
OFF
OFF
OFF
OFF
OFF
OFF
OFF
4.03 =
1D
D1 Inverting
-----
-----
-----
-----
-----
-----
----4.03 =
OFF
-----
-----
D1 Busmode
-----
-----
-----
-----
-----
-----
----4.03 =
ON
-----
-----
D2 Function
OFF
OFF
OFF
OFF
OFF
OFF
OFF
4.03 =
5D
OFF
OFF
D2 Inverting
-----
-----
-----
-----
-----
-----
----4.03 =
OFF
-----
-----
D2 Busmode
-----
-----
-----
-----
-----
-----
----4.03 =
ON
-----
-----
L-BAL-E095-GB 1203 Index 004
Part.-No.
60/68
User Setting
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Mode
1.01
2.01
2.03
2.04
2.02
2.05
Parameter
E2 Mode
3.01
3.02
3.03
3.04
Menu tables
4.01
4.02
4.03
5.01
5.02
6.01
Factory setting
E2 min.
0%
0%
0%
0%
0%
0%
0%
0%
0%
E2 max.
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
E2 Inverting
E3 Mode
E3 min.
0%
0%
0%
0%
0%
0%
0%
0%
0%
E3 max.
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
E3 Inverting
-----
-----
-----
-----
-----
-----
-----
-----
-----
K1 Function
1K
1K (2.03
= 2K)
1K
1K
1K
1K
1K
1K
1K
K1 Inverting
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Bus Address
247
247
247
247
247
247
247
247
247
Addressing
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Level Function
OFF
OFF
OFF
OFF
Limits
OFF
OFF
OFF
OFF
OFF
-----
-----
-----
-----
-----
-----
-----
-----
-----
Level min.
Level max.
-----
-----
-----
-----
-----
-----
-----
-----
-----
Level Delay
-----
-----
-----
-----
-----
-----
-----
-----
-----
OFF
OFF
(2.03 =
1L)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Lmt E2 min.
-----
----2.03 =
0.0 °C
-----
-----
-----
-----
-----
-----
-----
Lmt E2 max.
-----
----2.03 =
40.0 °C
-----
-----
------
-----
-----
-----
-----
Lmt E2 Hyst.
-----
----2.03 =
1.0 K
-----
-----
-----
-----
-----
-----
-----
Lmt E2 Del.
-----
----2.03 = 2
sec.
-----
-----
-----
-----
-----
-----
-----
Lmt E3 Function
-----
-----
-----
-----
-----
-----
-----
-----
-----
Lmt E3 min.
-----
-----
-----
-----
-----
-----
-----
-----
-----
Lmt E3 max.
-----
-----
-----
-----
-----
-----
-----
-----
-----
GW E3 Hysteresis
-----
-----
-----
-----
-----
-----
-----
-----
-----
Lmt E3 Del.
-----
-----
-----
-----
-----
-----
-----
-----
-----
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Offset 1
-----
-----
-----
-----
-----
-----
-----
-----
Offset 2
-----
-----
-----
-----
-----
-----
-----
-----
Lmt E2 Function
Offset Function
Offset Hyst.
-----
-----
-----
-----
-----
-----
-----
-----
Offset Del.
-----
-----
-----
-----
-----
-----
-----
-----
Rampup time*
10 sec
10 sec
10 sec
Motor Setup
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
Rampdown time*
2 sec
2 sec
2 sec
2 sec
2 sec
2 sec
2 sec
2 sec
2 sec
Suppression1 *
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Range1 min. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
Range1 max. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
L-BAL-E095-GB 1203 Index 004
Part.-No.
61/68
User Setting
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Mode
1.01
2.01
2.03
2.04
2.02
3.01
3.02
2.05
Parameter
3.03
3.04
Menu tables
4.01
4.02
4.03
5.01
5.02
6.01
Factory setting
Suppression2 *
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Range2 min. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
Range2 max. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
Suppression3 *
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Range3 min. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
Range3 max. *
-----
-----
-----
-----
-----
-----
-----
-----
-----
Diagnostic
000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:46:13
46:13
46:13
46:13
46:13
46:13
46:13
46:13
46:13
OTC
000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:- 000056:46:13
46:13
46:13
46:13
46:13
46:13
46:13
46:13
46:13
OTM
DC-Voltage
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
415 V
Line voltage
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
240 V
Heatsink
28.8 °C
28.8 °C
28.8 °C
28.8 °C
28.8 °C
28.8 °C
28.8 °C
28.8 °C
28.8 °C
Capacitor
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
E2-KTY
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
E2-Current
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
E2-Voltage
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
E3-KTY
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
20.0 °C
E3-Current
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
9.0 mA
E3-Voltage
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
4.0 V
D1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
D2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
K1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
* Factory setting depending on motor, changed settings are not put back on activation of factory setting!
10.2
Possible allocation of the IOs, PINs
Analog output A
Function
OFF
Description Function A
without function
1A
Constant voltage +10 V
2A
proportional level control
3A
proportional input E2
4A
proportional input E3
5A
Group control
6A
only 2.03 Cooling function
7A
only 2.03 Heating function
9A
proportionally to speed
L-BAL-E095-GB 1203 Index 004
Part.-No.
62/68
User Setting
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Digital inputs D1 + D2
Function
OFF
Description Function D1 + D2
No function
1D
Enable (remote control) “ON” / “OFF”
2D
External error
3D
“Limit” ON / OFF
4D
Switch over “E1” / “E3”
For mode speed controller 1.01
5D
Switch over “Setpoint Intern1” / “Setpoint Intern2”
6D
Switch over “Intern” / “Extern”
5D
Switch over “Setpoint1” / “Setpoint2”
For modes as controller from 2.01
6D
Switch over “Intern” / “Extern”
7D
Switch over “automatic control” / “Speed manual”
8D
Switch over control function (e.g. “heating” / “cooling”)
10D
“Reset”
11D
Setting Max. Speed “ON” / “OFF”
13D
Switch over direction of rotation “right” / “ left”
14D
“Freeze function” = maintain momentary modulation value
Analog input E2 / E3 (IO Setup)
Mode
Description E2 Modus
E2 min. / E2 max. without function (factory setting)
Offset / turn
Signal range
Analog input E3 (Base setup)
Function
OFF
Description Function E3
No function
1E
external Setpoint
2E
external Manual mode (from 2.01 )
3E
Sensor average to E2 (from 2.01 )
4E
Sensor comparison to E2
5E
Sensor difference to E2 (from 2.01 )
6E
Sensor for Setpoint (from 2.01 )
7E
Measurement value (from 2.01 )
L-BAL-E095-GB 1203 Index 004
Part.-No.
63/68
Menu tables
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Menu tables
Digital output K1
Function
Description Function K1 (not inverted)
OFF
No function
Relay remains always, i.e. de-energized
1K
Operating indication
Operation without fault, reports enable “OFF”
2K
Fault indication
Energized for operation without fault, for enable “OFF” not energized. De-energized at line,
motor and controller fault, Sensor fault dependent on programming, external fault at digital
input.
3K
External fault separate with message at digital input (factory setting if terminals bridged)
4K
Limit modulation
Over or falling below limits for modulation
5K
Limit “E2”
When over or falling below limits for input signal “E2”
6K
Limit “E3”
When over or falling below limits for input signal “E3”
7K
8K
For modes as controller from 2.01
Setpoint Offset
Deviation between actual value and setpoint to high
Group control
Switching on fans depending on modulation
For modes as temperature controller with additional functions 2.03
9K
Heating function
Switch ON point: temperature = Setpoint +/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
10K
Cooling function
Switch ON point: temperature = Setpoint +/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
Limits GW E2, GW E3
Function
OFF
Description Function GW E2, GW E3
without function
1L
Indication with the centralized fault of a programmed relay (IO allocation Function |2K | ).
Warning symbol in display, “AL” code in events memory.
2L
Is merely displayed in the events menu as message “msg”.
PIN
Function
PINs
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
Opening “setting”.
if “set protection” = “ON” (
Controller Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function “Save user setup” = “ON”
PIN 9095
Restore factory setting = delivery status
L-BAL-E095-GB 1203 Index 004
Part.-No.
64/68
Controller Setup)
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
11
Diagnostics menu
Diagnostics menu
The diagnostics menu supplies information about the momentary operating condition
of the device.
Diagnostic
00056:46:13
O = Operation, T = Time, C = Controller
The time counting runs, as soon as mains voltage is connected (without fault).
If events step on (Motor fault, External Error, etc.), the period of operation is stored at
Events).
this time (
O = Operation, T = Time, M = Motor
The time counting runs as soon as a modulation of the controller is present
00056:46:13
DC-Voltage
DC-Voltage
For 1 ~ types
ZK voltage constant at approx. 400 V
The PFC (Power Factor Controller) makes it mostly independent of the mains voltage.
For 3 ~ types
The intermediate circuit voltage without load is the peak value of the input voltage.
In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 V
results. This voltage sinks slightly under load.
Line voltage
Line voltage
Display of DC-Choke or Capacitor temperature. In case of temperature increase above
predetermined threshold value (from 90 °C) the output power will be automatic reduced.
Heatsink
Display of DCLink Elco temperature. During impermissibly high levels (from 75 °C on),
the output power is automatically reduced.
At 90 °C switch off.
Capacitor
E2-KTY
Signal height at analog input E2 (Analog In 2)
E2-Current
E2-Voltage
E3-KTY
Signal height at analog input E3 (Analog In 3)
E3-Current
E3-Voltage
L-BAL-E095-GB 1203 Index 004
Part.-No.
65/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
Enclosure
Status digital input 1 (Digital In 1)
OFF = terminals D1 - 24 V bridged ↔ ON = terminals D1 - 24 V not bridged
D1
Status digital input 2 (Digital In 2)
OFF = terminals E1 - D24 bridged ↔ ON = terminals D2 (E2) - 24 V not bridged
D2
OFF = relay K1 de-energized: terminals 11 - 14 not bridged
ON = relay K1 energized: terminals 11 - 14 bridged
K1
12
12.1
Enclosure
Connection diagram
KTY 81-210 / PT 1000
MODBUS 24 V GND
(RS-485)
TF..
MOSI11K0
21.03.2011
T3
(Imax = 6 mA)
T2 GND E3
Analog Out 1
Analog In 3
KTY 81-210 / PT 1000
Analog In 2
24V GND E2
DC Out
(D+) (D-)
(Imax = 70 mA)
AM-PREMIUM
A1
Ausgang
Output
0...10 V
TF..
Eingang Eingang
Input
Input
0...10 V (Ri > 100 kΩ)
0...20 mA (Ri = 250 Ω)
4...20 mA (Ri = 250 Ω)
Further connections
connection diagram in operating instructions ECblue Basic
L-BAL-E095-GB 1203 Index 004
Part.-No.
66/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
12.2
Enclosure
Index
address
Average calculation
52
21
Base setup
41
41
65
43
29
3, 57
terminal
two-wire-technology
44
17
user settings
38
group control
40
Holding Registers
52
I-component
41
K Factor
32
Limit
Limits
39
52
MAL1, MAL10
MBG-30I, MBG-50I
Minimum speed cut off
MODBUS
Mode
34
26
39
16
outputs 0 - 10 V
P-component
pin code
PIN input
PIN protection
PT1000
41
36
36
38
Rampdown time
L-BAL-E095-GB 1203 Index 004
Enable
External Setpoint
56
27
44
57
Suppression
D-component
diagnostics menu
Digital inputs
DSG
Rampup time
refrigerant
Relay output
Reset
resonances
56
Part.-No.
67/68
Operating Instructions AM-PREMIUM / AM-PREMIUM-W – model series
12.3
Index
Manufacturer reference
Our products are manufactured in accordance with the relevant international regulations. If you have
any questions concerning the use of our products or plan special uses, please contact:
Ziehl-Abegg AG
Heinz-Ziehl-Straße
74653 Künzelsau
Telephone: +49 (0) 7940 16-0
Telefax: +49 (0) 7940 16-504
info@ziehl-abegg.de
http://www.ziehl-abegg.de
12.4
Service information
If you have any technical questions while commissioning or regarding malfunctions, please contact
our V-STE support department for control systems - ventilation technology.
Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany.
www.ziehl-abegg.com.
If you make returns for inspections or repairs we need certain information in order to facilitate focused
trouble shooting and fast repair. Please use our repair tickets for this. It is provided to you after you
have consulted our support department.
In addition, you can download it from our homepage. Download - Ventilation Technology - Topic:
Control Engineering - Document type: General documents.
L-BAL-E095-GB 1203 Index 004
Part.-No.
68/68

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Author                          : Verwendete Zähler:
Modify Date                     : 2012:08:30 14:33:38+02:00
Subject                         : 
Keywords                        : j:, Bookmark-Zähler, ("titel")
Create Date                     : 2012:01:31 08:59:40+01:00
PXC Viewer Info                 : PDF-XChange Viewer;2.5.205.0;Aug 14 2012;17:23:22;D:20120830143338+02'00'
Page Count                      : 69
XMP Toolkit                     : XMP Core 4.1.1
Producer                        : GPL Ghostscript  9.0
Creator Tool                    : WebX Systems - UltraXML
Metadata Date                   : 2012:02:01 15:30:13+01:00
Document ID                     : 06b1fb5f-4e3d-11e1-0000-92942fd34491
Instance ID                     : uuid:d7b2f865-4409-4982-ba95-01f0b95a5fc7
Format                          : application/pdf
Title                           : a bis e: Kapitelzähler ("titel")
Creator                         : Verwendete Zähler:
Description                     : 
Description (x-repair)          : 
EXIF Metadata provided by EXIF.tools
FCC ID Filing: Z48-EMW

Navigation menu