Installation Guide for Bard models including: Bard Air Condition System, LC6000-200, Wall Mount Air Conditioner

2100-705(E) (2021 07)

W090APB, W090APC, W090APE, W090APV, W090APQ, W120APB, W120APC, W120APE, W120APN, W120APV, W120APQ, W120AEB, W120AEC, W120AEE, W120AEN, W120AEV, W120AEQ, W150APB, W150APC, W150APE, W150APN, W150APV, W150APQ, W150AEB, W150AEC, W150AEE, W150AEN, W150AEV, W150AEQ, LC6000

Bard Air Conditioning System

Manual 2100-705E Page 4 of 46 Wall-Mount Air Conditioner Units. MEGA-TEC units operate on VAC power. If equipped . with an economizer, the units will supply 100% of . rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.

Jul 06, 2021 ยท Manual 2100-705E Page 4 of 46 Wall-Mount Air Conditioner Units. MEGA-TEC units operate on VAC power. If equipped . with an economizer, the units will supply 100% of . rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.

2100-705 - Bard HVAC

General Information ....................................................3. List of Necessary Materials/Tools .............................6.

Not Your Device? Search For Manuals / Datasheets:

File Info : application/pdf, 46 Pages, 2.78MB

Document
2100-705
INSTALLATION INSTRUCTIONS
Bard Air Conditioning System

MEGA-TEC® Wall-Mount Air Conditioner

LC6000-200 Supervisory Controller

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

Manual:

2100-705E

Supersedes: 2100-705D

Date:

7-6-21

Page

1 of 46

CONTENTS

General Information .................................................... 3 List of Necessary Materials/Tools.............................6 Site Preparation............................................................7
Model Identification ..............................................7 New Shelter Installation vs. Retrofit Installation .......7 Minimum Clearance ..............................................7 Clearance to Combustibles .....................................8 Wall-Mount Unit Mounting.........................................9 Mounting the Units ...............................................9 Wall-Mount Unit Wiring ............................................14 Main Power Wiring ..............................................14 Unit Control Voltage Wiring ..................................14
230/208V Wiring..........................................14 460V Wiring.................................................14 Crankcase Heater Start Up ............................18 Preliminary Start Up..................................................19 Running in Orphan Mode .....................................19 LC6000 Controller Installation.................................20 LC6000 Controller ..............................................21 Mounting the LC6000 Controller....................21 Installing Remote Indoor Temperature/Humidity Sensor(s) ....................22 Installing Optional Outdoor Temperature/ Humidity Sensor...........................................24
FIGURES AND TABLES
Figure 1 MEGA-TEC Model Nomenclature...................6 Figure 2 Clearance Required for Service Access
and Adequate Condenser Airflow...................7 Figure 3 Unit Dimensions .........................................8 Figure 4 Lifting Lug Plates........................................9 Figure 5 Mounting Instructions................................10 Figure 6 Electric Heat Clearance .............................11 Figure 7 Wall Mounting Instructions.........................11 Figure 8 Wall Mounting Instructions.........................12 Figure 9 Common Wall Mounting Installations...........13 Figure 10 WIRING: VAC Supply Wiring Landing Points .. 14 Figure 11 Side Communication and Power Wire
Entrances (Recommended) ........................17 Figure 12 Rear Communication and Power Wire
Entrances (Optional)..................................17 Figure 13 Cooling and Heating Setpoints....................19 Figure 14 Typical LC6000-200 Component Location ...20 Figure 15 LC6000 Fused Power Supply Terminal ........21 Figure 16 Remote Indoor Temperature/Humidity
Sensor Installation ....................................22 Figure 17 Additional Remote Sensor Installation .........23 Figure 18 Remote Outdoor Temperature/Humidity
Sensor Installation ....................................24 Figure 19 Emergency Off, Emergency Ventilation
and Generator Run Connections..................25 Figure 20 Communication Wiring (Daisy Chain)...........26 Figure 21 Communication Wiring (Alt. Method)...........26 Figure 22 Placement of Communication Filters ...........27 Figure 23 Communication Wiring: Termination at the
Controller .................................................28 Figure 24 Communication Wiring: Termination at the
First Wall-Mount Unit ................................29 Figure 25 Communication Wiring: Termination at
Additional Wall-Mount Units.......................30 Figure 26 LC6000 Controller Circuit Install ................31 Figure 27 Controller Grounding Posts .........................31 Figure 28 WIRING: LC6000-200 Wiring Diagram........33 Figure 29 TEC-EYE Connection to Unit Control ...........34 Figure 30 TEC-EYE Display and Interface ...................34 Figure 31 Unit Configuration .....................................35
Manual 2100-705E Page 2 of 46

Emergency Off, Emergency Vent and Generator Run Connections ...........................25 Communication Wiring ..................................26 Supply Wiring...............................................31 System Set Up .............................................................34 TEC-EYE Hand-Held Diagnostic Tool .....................34 TEC-EYE Status Screen.................................35 Setting Up Wall-Mount Units for Operation ............35 1. Address Each Wall-Mount Unit...................35 2. Execute a Self Test on Each Unit ...............35 3. Clear Unit Alarm Logs on Each Unit ...........36 Setting Up LC6000 for Operation .........................36 4. Set LC Controller Date and Time ................37 5. Configure Sensors.....................................37 6. Enter Total Number of Units ......................40 7. Verify Units are Online ..............................40 8. Select Economizer Type for Each Zone........40 9. Clear Controller Alarm Logs .......................41 10. Complete Installation ..............................41 Additional Information.............................................42 Menu Screens and Password Levels ......................42 Setpoints............................................................43 Calibrating Sensors .............................................43 A/C Circuit Information ........................................45 Remote Indoor Temperature/Humidity Sensor Orientation .........................................................46

Figure 32 Executing Self Test....................................36 Figure 33 Clearing Unit Alarm Logs ...........................36 Figure 34 LC6000 Controller Display and Interface .......37 Figure 35 Setting Controller Date and Time ................37 Figure 36 Enable/Disable Zone 1 Indoor Humidity
Sensor .....................................................38 Figure 37 Enable/Disable Zone 2 Indoor Humidity
Sensor .....................................................38 Figure 38 Enable/Disable Zone 3 Indoor Humidity
Sensor .....................................................38 Figure 39 Enable/Disable Zone 1 Indoor Temperature
Sensor .....................................................38 Figure 40 Enable/Disable Zone1 Remote Temperature
Sensor .....................................................39 Figure 41 Enable/Disable Zone 2 Remote Temperature
Sensor .....................................................39 Figure 42 Enable/Disable Zone 3 Remote Temperature
Sensor .....................................................39 Figure 43 Enable/Disable Outdoor Air Humidity Sensor .. 40 Figure 44 Enable/Disable Outdoor Air Temperature
Sensor .....................................................40 Figure 45 Total Units Displayed.................................40 Figure 46 Selecting Economizer Type.........................41 Figure 47 Clearing LC6000 Alarm Logs......................41 Figure 48 Adjusting Sensor Offset Value.....................43 Figure 49 MEGA-TEC Refrigeration Circuits ................45 Figure 50 Current Sensor Orientation .........................46 Figure 51 Earlier Sensor Orientation ..........................46

Table 1
Table 2A Table 2B Table 3 Table 4 Table 5 Table 6 Table 7 Table 8

Miniumum Clearances Required to Combustible Materials .................................8 Electrical Specifications ­ W***AP Series....15 Electrical Specifications ­ W***AE Series....16 LC6000-200 Terminal Block Index .............32 LC6000/TEC-EYE Passwords (Default) ........34 TEC-EYE Menu Structure ...........................42 LC6000 Controller Menu Structure .............42 Unit Status Messages ................................44 LC6000 Status Messages...........................45

GENERAL INFORMATION

Air Conditioning System
This Bard air conditioning system is comprised of MEGA-TEC wall-mounted air conditioners matched with an LC6000 supervisory controller or Bard PGD/ PGDx stand-alone display. If only one wall-mounted air conditioner is being used, it can be matched with either the LC6000 supervisory controller or stand-alone controller (see Single Unit Operation on page 4 for information on the PGD and PGDx). If more than one wall mount is installed, the LC6000 controller must be matched with the air conditioning units. The wallmount units are specifically engineered for telecom/ motor control center rooms.

NOTE: The LC6000 supervisory controller or standalone display and MEGA-TEC wall-mount units are designed specifically to work together. The controller or stand-alone display cannot run other brands of systems, nor can other controllers run the MEGA-TEC wall-mount units. They are a complete system, and must be used together.
Controller
LC6000 controller and accessories shown below.

LC6000-200 Series Controller and Accessories Included with Controller

+

(1) TEC-EYETM Hand-Held Diagnostic Tool Bard P/N 8301-059
(1) Remote Temperature/Humidity Sensor1 Bard P/N 8403-079

(1) LC6000 Programmable Logic Controller

(1) 35' 5-Wire 18 Gauge Shielded Cable

NOTE: The 2-wire, 18 gauge shielded cable used to communicate between the controller and wall-mount units is not included and must be field supplied.

(2) Communication EMI Filters Bard P/N 8301-055

Optional Sensors:

Outside Air Temperature/Humidity Sensor
Bard P/N 8301-090

Remote Temperature/Humidity Sensor1
Bard P/N 8403-079

Remote Temperature Only Sensor
Bard P/N 8301-058

1 One remote temperature/humidity sensor is included with the LC6000 controller. If the site in which the LC6000 controller will be used has more than one zone (maximum three zones), additional remote temperature/humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One additional temperature-only sensor (Bard P/N 8301-058) may also be used in Zone 1 but will also need to be purchased separately. Additional temperature/humidity sensors require field-supplied 5-wire 18 gauge shielded cable. Temperature-only sensors require field-supplied 2-wire 18 gauge shielded cable.

Manual 2100-705E

Page

3 of 46

Wall-Mount Air Conditioner Units
MEGA-TEC units operate on VAC power. If equipped with an economizer, the units will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
MEGA-TEC units are fully charged with refrigerant and are available with optional electric heat and/or electric reheat dehumidification.
NOTE: 575V models take incoming field power and stepdown secondary to 460V which supplies most components except compressors and electric heat which remain 575V. Reference wiring diagrams for more information.
NOTE: 400V models have only two stages of capacity rather than three and are identical in size. Take note of this when reading this manual.
Single Unit Operation
A PGD or PGDx stand-alone display can be used in place of the LC6000 controller when only one MEGATEC wall-mount air conditioner is being installed. If using a PGD or PGDx stand-alone display instead of the LC6000 controller, the alarm logging and remote communication capabilities of the LC6000 controller will not be available. See PGD manual 2100-734 or PGDx manual 2100-740 for information on installing and setting up a stand-alone display for single unit operation.
General
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications for information on codes and standards.

Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to methods of Air Conditioning Contractors of America (ACCA). The supply flange should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier's agent.
These units must remain in upright position at all times; do not lay on side. Do not stack units.
Additional Publications
These publications can help when installing the air conditioner. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation of Air Conditioning and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

Manual 2100-705E Page 4 of 46

ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. The signal word "DANGER" is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to "NOTICE" the word "CAUTION" without the safety alert symbol may be used to indicate a message not related to personal injury.

! WARNI NG
Electrical shock hazard. Have a properly trained individual perform these tasks. Failure to do so could result in electric shock or death.
! WARNI NG
Fire hazard. Maintain minimum 1/4" clearance between the supply air duct and combustible materials in the first 3' of ducting. Failure to do so could result in fire causing damage, injury or death.
! WARNI NG
Heavy item hazard. Use more than one person to handle unit. Failure to do so could result in unit damage or serious injury.

! CAUTI ON
Cut hazard. Wear gloves to avoid contact with sharp edges. Failure to do so could result in personal injury.

IMPORTANT
When connecting this product from a remote location, ensure that the network connection is secure and reliable.

Manual 2100-705E

Page

5 of 46

LIST OF NECESSARY MATERIALS/TOOLS

Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must be sourced before installation. This list also includes tools needed for installation.

List of Materials/Tools
· Personal protective equipment/safety devices/ anti-static wrist straps
· SG-10W supply grille and RG-10W return grille · Field-fabricated sleeves (if necessary) · Fasteners sufficient for mounting the units such as
5/16" diameter anchor/lag bolts · 7/8" diameter washers · Fasteners appropriate for the shelter wall
construction to attach the controller to the wall · Commercial grade outdoor silicone sealant · Miscellaneous hand and power tools and jobsite or
shop materials · Lifting equipment with the necessary capacity and
rigging to safely move/install the systems. The unit is supplied with lifting lug plates on each side at top of unit. Remount in upright position for use (see page 9).

· Electrical supplies
- Various size circuit breakers for the shelter AC breaker box (see Tables 2A or 2B on pages 15 or 16)
- High-voltage wire of various gauges (see Tables 2A or 2B)
- 16 gauge minimum, 14 gauge maximum power wire to connect controller to shelter power source
- 5-wire, 18 gauge shielded cable for remote temperature and humidity sensors (2-wire, 18 gauge shielded cable for temperature-only sensors)
- Communication wire: 2-wire, 18 gauge, shielded with drain
- 18 gauge non-shielded wire for connecting emergency off, emergency vent and/or generator relays, if applicable, to controller
- CAT 6 Ethernet cable of field-determined length (for remote communication, if applicable)
- 2 hole grounding lug (to be used with supplied 1/4" bolts and nuts for grounding controller box)
- Miscellaneous electrical supplies including rigid/ flexible conduit and fittings, 2" x 4" junction boxes (one per temperature/humidity sensor), wire connectors and supports

FIGURE 1 MEGA-TEC Wall-Mount Unit Model Nomenclature

W 120 A P B 0Z E P X X X X

MODEL SERIES
NOMINAL TOTAL CAPACITY 090 ­ 7.5 Ton 3 Stage Capacity 120 ­ 10 Ton 3 Stage Capacity 150 ­ 12.5 Ton 3 Stage Capacity

PACKAGING OPTIONS X ­ None, Standard Wood Skid 1 ­ White Steel Skid/Platform 2 ­ Wood Skid with Crate 3 ­ White Steel Skid/Platform with Crate 6 ­ Gray Steel Skid/Platform 7 ­ Gray Steel Skid/Platform with Crate

REVISION
CONTROL LOGIC AND CLIMATE OPTIONS P ­ Programmable Logic Board
E ­ Electric Reheat Dehumidification

B ­ 230/208-60-3 C ­ 460-60-3
E ­ 240/220-50-3

VOLTS & PHASE N ­ 400-60-3 Q ­ 575-60-3
V ­ 415/380-50-3

KW 0Z ­ Okw with Circuit Breaker 09 ­ 9kw with Circuit Breaker 18 ­ 18kw with Circuit Breaker 36 ­ 36kw with Circuit Breaker
(Q Voltage Only)

VENT B ­ No Vent E ­ Economizer (DB and WB)

COIL AND UNIT COATING OPTIONS X ­ Standard 1 ­ Coated Evaporator 2 ­ Coated Condenser 3 ­ Coated Evaporator and Condenser
OUTLET X ­ Standard
COLOR X ­ Beige Baked Enamel Finish 1 ­ White Baked Enamel Finish 4 ­ Gray Baked Enamel Finish
FILTER OPTIONS M ­ MERV11 Disposable P ­ MERV8 2" Pleated N ­ MERV13 2" Pleated

Manual 2100-705E Page 6 of 46

SITE PREPARATION

Model Identification
Identify the specific model using the model nomenclature information found in Figure 1 and the model/serial tag found on the unit. See Figure 3 on page 8 for dimensions and critical installation requirements.
New Shelter Installation vs. Retrofit Installation
These installation instructions cover both new shelter installations and retrofit installations. Each installation is unique and may require special accommodations and modifications. Although Bard Manufacturing follows a long-established tradition of manufacturing equipment using industry standard dimensions for building penetration, it is occasionally necessary to move or enlarge supply and return openings when replacing non-standardized equipment in a retrofit application.

Minimum Clearance
To maintain full service access and adequate condenser airflow, side-by-side installations require 28" of clearance between units for access to the economizer (20" of clearance between units without economizers) and proper airflow of the outdoor coil (see Figure 2). Additional clearance may be required to meet local or national codes.
Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, such as these wall-mount units, it is recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.

FIGURE 2 Clearance Required for Service Access and Adequate Condenser Airflow

SHELTER EQUIPMENT

SHELTER EQUIPMENT

5ft*

SUPPLY AIR

  

4412"

UNIT #1

SUPPLY AIR
  
UNIT #2

OUTDOOR

10ft

CLEARANCE AREA

20"

5058"

20" NON-ECONO 28" WITH ECONO

5058"

* Recommended distance between return air opening and equipment in room. Supply airstream must be able to provide adequate air circulation throughout the room.
All national, state and local codes must be observed and followed during installation.

5ft*

4412"

10ft 20" MIS-3962

Manual 2100-705E

Page

7 of 46

Clearance to Combustibles
The supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. See Figure 5 on page 10 for details on opening sizes.

TABLE 1 Minimum Clearances Required to
Combustible Materials

Model Supply Air Duct (1st 3')

All Models

1/4"

Cabinet 0"

FIGURE 3 Unit Dimensions

Model

Width Depth Height (W) (D) (H)

Supply AB

Return CB

E

F

G

I

K

L MN O

P

R

S

T

U

All Models

50.64 43.19

94.22 15.81 42.67 21.82 42.74 54.24 12.27 34.95 25.98 28.65 23.73 21.48 11.68 52.24 19.48 2.73 16.00 11.49 67.65

All dimensions are in inches. Dimensional drawings are not to scale.

Side Wall Mounting Brackets (Built In)
26.00
21.00 H
F

U W
1 Filter Access Panel Heater Access Panel
Blower Access Panel
Control Access Panel

Built In Rain Hood
.5° Pitch C. Breaker/ Disconnect Access Panel (Lockable)
Communication Electrical Entrance
High Voltage Electrical Entrance

G

Condenser Outlet Air

Hood for ECON models only

3.75

Front View

55.00

Optional steel platform adds 3-3/4" hight to vertical

37.18

D 1.63
Ventilation Air

Top Rain Flashing Shipping Location 1.97
R

A

S

S I
S
C S

E O
1.00 Supply Air Opening
B
Return Air Opening

Side View
48.00 45.00

K

S

T

Optional Electrical Entrances
Drain
Back View

M PL
N

Removable bumper for leaving Steel Platform on unit when mounting unit to the wall.

MIS-3945 B

Manual 2100-705E Page 8 of 46

WALL-MOUNT UNIT MOUNTING

Mounting the Units
! WARNI NG
Unit falling hazard. Use only sufficiently rated mechanical lifting means with proper rigging to raise the unit for mounting. Failure to follow this warning could result in injury or death.

NOTE: It may be best to spot some electrical knockouts (such as those located on the side and rear of the wall-mount unit) before units are mounted and access is unavailable or limited (see Figure 3 to locate pre-punched knockouts).
Heavy duty lifting lug plates are installed on each side of the unit to allow the unit to be lifted and installed on a structure. The plates must be removed and reinstalled in upright position (see Figure 4) for use and can be removed after installation.
The filter access panel handle is shipped with the unit. Attach handle to front of filter access panel using the screws included with the handle as shown in Figure 4.

FIGURE 4 Lifting Lug Plates

Lifting Plate (in upright position)

Lifting Plate (in shipping position)

Filter Access Panel Handle
3"
2" Diameter 2"
27"

MIS-3964
5" 5°
2-1/4"

Two holes for the supply and return air openings must be cut through the wall as shown in Figure 5 on page 10. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. All walls must be thoroughly inspected to ensure that they are capable of carrying the weight of the installed unit.
In retrofit (unit replacement) installations, the openings cut for the original equipment may not line up exactly with needs of this installation. Modifications may need to be made, such as increasing or decreasing the size of the wall cutouts. The existing bolt placement may not line up in which case the original bolts would need to be removed or cut away.
1. These units are secured by full-length mounting flanges built into the cabinet on each side which secure the unit to the outside wall surface.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. See Figure 5 for details on opening sizes.
3. Locate and mark lag bolt locations and location for optional bottom mounting bracket, if desired (see Figure 5).
4. If desired, hook top rain flashing (attached to frontright of supply flange for shipping) under back bend of top.
5. Position unit in opening and secure with fasteners sufficient for the application such as 5/16" lag/ anchor/carriage bolts; use 7/8" diameter flat washers on the lag bolts. It is recommended that a bead of silicone caulking be placed behind the side mounting flanges.
NOTE: For economizer models, mount hoods after unit is installed so as to not block unit flange holes.
6. Secure optional rain flashing to wall and caulk across entire length of top (see Figure 5).
7. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
8. A plastic drain hose extends from each drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hoses to pass through.
NOTE: Ensure hose doesn't kink inside of unit when pulling hose through holes in base. This could prevent proper drainage.

Manual 2100-705E

Page

9 of 46

Additional openings exist in the condenser fan panel section for front drainage. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 5 Mounting Instructions
SEAL WITH BEAD OF CAULKING ALONG
ENTIRE LENGTH OF TOP.

7 8

"

16"

16"

16"

16"

*43

3 8

"

42

7 8

"

SUPPLY OPENING

1 4

"

RETURN OPENING

WALL

TOP

16"

*16

1 2

"

25

7 8

"

22"

16"

4

11 16

"

42

7 8

"

17"

52

1 4

"

* INCLUDES 0.25" CLEARANCE TO COMBUSTIBLE MATERIALS

Wall Opening and Hole Location View

Right Side View

RAIN FLASHING
FOAM AIR SEAL
WALL STRUCTURE 0.250" CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTIBLE MATERIALS SUPPLY AIR DUCT
RETURN AIR OPENING
NOTE:
IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION.
MIS-3946

Manual 2100-705E Page 10 of 46

FIGURE 6 Electric Heat Clearance

SUPPLY AIR OPENING

FIGURE 7 Wall Mounting Instructions
FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT
BEFORE INSTALLATION
SUPPLY AIR OPENING

WALL STRUCTURE
SUPPLY AIR DUCT

RETURN AIR OPENING

RETURN AIR OPENING

RETURN AIR OPENING

WOOD OR STEEL SIDING
CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION

SIDE VIEW

MIS-3947

Manual 2100-705E

Page

11 of 46

INTERIOR FINISHED WALL OVER FRAME
EXTERIOR FINISH WALL OVER FRAME

FIGURE 8 Wall Mounting Instructions
ATTACH TO TOP PLATE OF WALL

See Figure 3, Unit Dimensions, for actual dimensions.
E + 1.000 B

0.250" CLEARANCE ALL AROUND DUCT
1/4"

SUPPLY DUCT OPENING

A

I

RETURN DUCT

OPENING

C

K

MIS-3948

FRAMING MATERIAL 2 x 4's, 2 x 6's &/OR
STRUCTURAL STEEL

ATTACH TO BOTTOM PLATE OF WALL

THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.

Manual 2100-705E Page 12 of 46

FIGURE 9 Common Wall Mounting Installations

RAIN FLASHING

RAFTERS

RAIN FLASHING

FINISHED CEILING SURFACE
SUPPLY AIR DUCT WITH GRILLE
WALL SLEEVE

RAFTERS SUPPLY AIR
DUCT
FINISHED CEILING SURFACE

RETURN AIR DUCT WITH GRILLE
WALL SLEEVE

RETURN AIR DUCT WITH GRILLE
WALL SLEEVE

OUTSIDE WALL
FREE AIR-FLOW NO DUCT

OUTSIDE WALL
DUCTED SUPPLY RETURN AT UNIT

RAIN FLASHING

RAFTERS
SUPPLY AIR DUCT

RAIN FLASHING

RAFTERS
SUPPLY AIR GRILLE

FINISHED WALL SURFACE
WALL SLEEVE

FINISHED CEILING
CLOSET WALLS

FALSE WALL

OUTSIDE WALL

RETURN GRILLE

FAALLSSE WALL INSTALLATITION

WALL SLEEVE
RAISED FLOOR

OUTSIDE WALL

RETURN GRILLE

CLOSET INSTALLATION

MIS-3954

Manual 2100-705E

Page

13 of 46

WALL-MOUNT UNIT WIRING
! WARNI NG
Electrical shock hazard. Have a properly trained individual perform these tasks. Failure to do so could result in electric shock or death.

FIGURE 10 VAC Supply Wiring Landing Points

Main Power Wiring
Refer to the unit rating plate or Tables 2A or 2B for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a "Minimum Circuit Ampacity". The field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit rating plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked "Use Copper Conductors Only". These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The unit rating plate and Tables 2A and 2B list fuse and wire sizes (75°C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a maximum circuit breaker or fuse that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
The main unit circuit breaker disconnect access is located on the front panel of the unit.
Route all field power wires in channel under the control panel. See Figure 10 to reference VAC landing points.
Route wires into unit through recommended side entrances (see Figure 11 on page 17). Optional rear entry points are also available (see Figure 12 on page 17).
NOTE: Field wires enter at bottom for line side connection.
When running wires to unit from shelter, be careful to not place wiring and conduit where it will interfere with opening filter access doors.

230/208V

460V

Unit Control Voltage Wiring

NOTE:

The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.

230/208V Wiring

230/208V 3 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. It is very important that the correct voltage tap is used. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are: 240V tap (253 ­ 216) and 208 tap (220 ­ 197).

460V Wiring

460V 3 phase equipment use triple primary voltage transformers. All equipment leaves the factory wired on 480V tap. It is very important that the correct voltage tap is used. The acceptable operating voltage range for the 480V, 415V and 380V taps are: 480V tap (429 and above), 415 Tap (395 ­ 428) and 380 tap (below 395). For 400V N models, use the 415V tap.

NOTE: 575V models take incoming field power and stepdown secondary to 460V which supplies most components except compressors and electric heat which remain 575V. Reference wiring diagrams for more information.

For communication wiring, a 2-wire, 18 gauge colorcoded shielded cable with drain is recommended.

Manual 2100-705E Page 14 of 46

TABLE 2A Electrical Specifications ­ W***AP Series

Single Circuit

Dual Circuit

Model

Rated Volts & Phase

No. Field Power Circuits

 Minimum
Circuit Ampacity

 Maximum External Fuse or Ckt.
Brkr.

 Field Power Wire Size

 Ground
Wire

 Minimum
Circuit Ampacity

 Maximum External Fuse or Ckt. Breaker

 Field Power
Wire Size

 Ground Wire Size

Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

W090APB0Z B09 B18

230/20860-3

1 1 1

46 46 59

60

8

10

60

8

10

60

6

10

W090APC0Z

1

21

C09 460-60-3

1

21

C18

1

30

30

10

10

30

10

10

35

8

10

W090APE0Z E09 E18

220/20050-3

1 1 1

46 46 59

W090APQ0Z

1

19

Q09 Q18

575-60-3

1 1

19 25

Q36

1

55

W090APV0Z

1

23

V07 415-50-3

1

23

V14

1

29

60

8

10

60

8

10

60

6

10

25

10

10

25

10

10

30

10

10

60

6

10

35

8

10

35

8

10

40

8

10

W120APB0Z B09 B18

230/20860-3

1 or 2 1 or 2 1 or 2

56 56 59

70

6

8

32 25 40 40

8

8

10 10

70

6

8

32 28 40 40

8

8

10 10

70

6

8

32 28 40 40

8

8

10 10

W120APC0Z

1

27

C09 460-60-3

1

27

C18

1

30

40

8

10

40

8

10

40

8

10

W120APE0Z E09 E18

220/20050-3

1 or 2 1 or 2 1 or 2

55 55 59

70

6

8

32 25 40 40

8

8

10 10

70

6

8

32 25 40 40

8

8

10 10

70

6

8

32 28 40 40

8

8

10 10

W120APN0Z

1

32

N09 400-60-3

1

32

N18

1

32

W120APQ0Z

1

24

Q09 Q18

575-60-3

1 1

24 27

Q36

1

57

W120APV0Z

1

27

V07 415-50-3

1

27

V14

1

30

40

6

8

40

6

8

40

6

8

35

8

10

35

8

10

35

8

10

60

6

10

40

8

10

40

8

10

40

8

10

W150APB0Z B09 B18

230/20860-3

1 or 2 1 or 2 1 or 2

67 67 67

80

4

8

39 34 50 40

8

8

10 10

80

4

8

39 34 50 40

8

8

10 10

80

4

8

39 37 50 40

8

8

10 10

W150APC0Z

1

32

C09 460-60-3

1

32

C18

1

32

40

8

10

40

8

10

40

8

10

W150APE0Z E09 E18

220/20050-3

1 or 2 1 or 2 1 or 2

67 67 67

80

4

8

39 29 40 40

8

8

10 10

80

4

8

39 29 50 40

8

8

10 10

80

4

8

39 29 50 40

8

8

10 10

W150APN0Z

1

34

N09 400-60-3

1

34

N18

1

34

40

8

10

40

8

10

40

8

10

W150APQ0Z

1

24

Q09 Q18

575-60-3

1 1

24 30

Q36

1

58

W150APV0Z

1

32

V07 415-50-3

1

32

V14

1

32

35

8

10

35

8

10

40

8

10

60

6

10

40

8

10

40

8

10

40

8

10

 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.

 Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.

NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum calculated value or Minimum Circuit Ampacity (MCA) listed.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.

Manual 2100-705E

Page

15 of 46

Model W090AEB18

TABLE 2B Electrical Specifications ­ W***AE Series

Rated Volts & Phase

Single Circuit

Dual Circuit

No. Field Power Circuits

 Minimum
Circuit Ampacity

 Maximum External
Fuse or Ckt. Brkr.

 Field Power Wire Size

 Ground
Wire

 Minimum
Circuit Ampacity

 Maximum External Fuse or Ckt. Breaker

 Field Power
Wire Size

 Ground Wire Size

Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

230/208-60-3 1 or 2

100

100

3

8

56 46 60 50 6

8 10 10

W090AEC18

460-60-3

1

53

60

6

10

W090AEE18

220/200-50-3 1 or 2

100

100

3

8

56 46 60 50 6

8 10 10

W090AEQ18

575-60-3

1

43

45

8

10

W090AEV14

415-50-3

1

53

60

6

10

W120AEB18

230/208-60-3 1 or 2

110

120

2

6

59 52 60 60 6

6 10 10

W120AEC18

460-60-3

1

54

60

6

10

W120AEE18

220/200-50-3 1 or 2

110

120

2

6

59 51 60 60 6

6 10 10

W120AEN18

400-60-3

1

45

50

8

10

W120AEQ18

575-60-3

1

43

45

8

10

W120AEV14

415-50-3

1

53

60

6

10

W150AEB18

230/208-60-3 1 or 2

120

120

1

6

59 55 60 60 6

6 10 10

W150AEC18

460-60-3

1

54

60

6

10

W150AEE18

220/200-50-3 1 or 2

113

120

2

6

51 59 60 60 6

6 10 10

W150AEN18

400-60-3

1

54

60

6

10

W150AEQ18

575-60-3

1

43

45

8

10

W150AEV14

415-50-3

1

53

60

6

10

 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.  Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.

Manual 2100-705E Page 16 of 46

FIGURE 11 Side Communication and Power Wire Entrances (Recommended)
HIGH VOLTAGE POWER WIRE ENTRANCE
COMMUNICATION WIRE ENTRANCE

Route communication wiring and power supply wiring in their own separate conduits. They must not be run together. Use 2-wire, 18 gauge shielded cable with drain for communication wire.
FIGURE 12 Rear Communication and Power Wire Entrances (Optional)

MIS-3955

MIS-3956

OPTIONAL REAR POWER ENTRANCE

OPTIONAL REAR COMMUNICATION ENTRANCE

Route communication wiring and power supply

wiring not be

irnunthteoigr eotwhenr.sMeUpIsSae-r3a29t-e5w6ciroen,d1u8itsg.aTuhgeeyshmieulsdted

cable with drain for communication wire.

Manual 2100-705E

Page

17 of 46

Crankcase Heater Start Up
All units covered in this manual are provided with compressor crankcase heat. This crankcase heater is a band-type heater located around the bottom of the compressor. This heater is controlled by the crankcase heater relay. The heater is only energized when the compressor is not running. Crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor, preventing oil pump out on compressor start up and possible bearing or scroll vane failure due to compressing a liquid. IMPORTANT: The following procedure must be followed at initial start-up and at any time power has been removed for 12 hours or longer. To prevent compressor damage which may result from the presence of liquid refrigerant in the compressor crankcase: 1. Make certain the room thermostat is in the "off"
position (the compressor is not to operate). 2. Apply power by closing the system disconnect
switch. This energizes the compressor heater which evaporates the liquid refrigerant in the crankcase. 3. Allow 4 hours or 60 minutes per pound of refrigerant in the system as noted on the unit rating plate, whichever is greater. 4. After properly elapsed time, the thermostat may be set to operate the compressor. 5. Do not open system disconnect switch except as required for safety while servicing.
Manual 2100-705E Page 18 of 46

PRELIMINARY START UP

Running in Orphan Mode
With the AC breakers turned on, each MEGA-TEC wallmount unit has the capability to run without the LC6000 controller connected--this feature is called orphan mode. This keeps the shelter between 60°F and 77°F (factory default settings) by the use of the factory-installed return air sensor in each wall-mount unit. In orphan mode, the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room temperature.
The wall-mount unit can be turned on and off with the TEC-EYE hand-held diagnostic tool. When ON is chosen, the wall-mount unit will heat or cool. When set to OFF using the TEC-EYE, the wall-mount unit will not heat, cool or ventilate.
To turn the unit on or off with TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control board located in the unit.
2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter USER password 2000.
4. Press UP or DOWN keys to scroll to On/Off; press ENTER key.
5. Press UP or DOWN keys to change value from ON to OFF or from OFF to ON.
6. Press ESCAPE key several times to return to Main Menu screen.
To verify or change the wall-mount unit cooling and heating setpoints in orphan mode:
1. Connect the TEC-EYE diagnostic tool to the control board located in the unit.
2. From the Status screen, press UP or DOWN key until Quick Menu displays Setpoints (SET) icon. Press ENTER key.
3. Press ENTER key to scroll to the selected choice (see Figure 13).
4. Press UP or DOWN key on desired value until value displays correctly.
5. Press ENTER key to save and scroll to next parameter.
6. Press ESCAPE key until Main Menu screen is displayed.

FIGURE 13 Cooling and Heating Setpoints
During installation, the ability to run in orphan mode allows deactivation of one of the existing, older wallmount units, while keeping the shelter cool with the other unit still operating. Once the first of the Bard MEGA-TEC wall-mount units is installed, orphan mode can be enabled early in the installation--keeping the climate inside the shelter stable and the installers comfortable while the remainder of the older equipment is removed and the remaining Bard MEGA-TEC wallmount units and LC6000 controller are installed. Additionally, should any or all of the MEGA-TEC wallmount units lose communication with the LC6000 controller (such as during maintenance), they will continue to serve the shelter's needs until a repair can be made.

Manual 2100-705E

Page

19 of 46

LC6000 CONTROLLER INSTALLATION
FIGURE 14 Typical LC6000-200 Component Location

Transformer
RJ11 Cable to Display
Ethernet Cable Connection
Four Fused Power Supply
Terminals Emergency Off Alarm Jumper Emergency Vent Alarm Jumper Generator Run Alarm Jumper

Control Board USB Male A to Micro Male B Cable
Terminal Block

Manual 2100-705E Page 20 of 46

! WARNI NG
Electrical shock hazard. Disconnect VAC power supplies before servicing. Failure to do so could result in electric shock or death.
IMPORTANT: When working with circuit board components, Bard recommends the use of an anti-static wrist strap to prevent static electricity shorts to electronic controls.
LC6000 Controller
The LC6000 controller is part of this air conditioning system. It is used to control up to fourteen (14) wall-mount air conditioners from one controller. The microprocessor control provides an easy-to-read interface with large LCD graphical display. It provides control for redundancy for the structure and equal wear on all units.
Conduit is recommended for all wiring. Route communication wiring and power supply wiring in their own separate conduits.
The LC6000 controller is not weatherproof and is intended for use in a weathertight structure.

Mounting the LC6000 Controller
The dimensions of the LC controller are 16" x 12" x 6".
Because the LC6000 controller utilizes a remote temperature sensor as opposed to one located in the controller box, the controller itself can be installed in any indoor location that is suitable, preferably at eye level. Four (4) mounting holes are provided for mounting to the wall and holes for conduit connections are provided in the base, sides and top of the controller.
The LC6000 controller includes four fused power supply terminals in the terminal block. Before connecting wires to the terminal block, confirm that the fuse in each of the four fuse holders is in the proper position (active) as shown in Figure 15.

FIGURE 15 LC6000 Fused Power Supply Terminal

Fuse in Active Position

Shipping Position

Manual 2100-705E

Page

21 of 46

Installing Remote Indoor Temperature/Humidity Sensor(s)
One remote indoor temperature/humidity sensor and 35' of 18 gauge 5-conductor shielded cable is included with the controller. This sensor must be installed for proper operation. Mount the temperature/humidity sensor in a location least likely to be affected by open doors, rack-mounted fans, radiant heat sources, etc. Locating the sensor between both return grilles is often the best location, but every installation is unique. Location height should be approximately 60" above the floor. The sensor is best mounted on a 2" x 4" junction box and it is recommended that the cable be in conduit. Use shielded cable to connect to controller. The maximum cable length to connect the temperature/humidity sensor to the LC6000 is 98'.
FIGURE 16 Remote Indoor Temperature/Humidity Sensor Installation
1. Connect wires from the 18 gauge shielded cable to terminals #12, #13, #18, #19 and #22.

TB#

Wire Mark

Sensor

Description

18 B6 NTC OUT Indoor Remote Sensor (Zone 1)

19 GND NTC OUT Ground

12 B2 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 1)

13 GND M (GO) Ground 22 +VDC + (G) Power for B2

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 4142 43 44 45 46 47

2. Connect the other end of the shielded cable to the sensor terminals. Be sure wires are connected to proper terminals as shown in table above. Sensor jumpers need to be positioned for 0-1 V. With sensor oriented as shown in image to right, move both jumpers to right position (DP1 and DP2 set to OFF). This applies to all indoor temperature/humidity sensors connected to the LC controller. See illustration mounted inside of sensor cover for further detail on jumper position. Earlier versions of this sensor may be mounted in a different orientation which would affect the positioning of the sensor jumpers. See page 45 for additional information on sensor orientation.
Manual 2100-705E Page 22 of 46

Jumper
DP1 DP2

For proper operation, the remote indoor temperature/humidity sensor (and any additional sensors) must be configured properly with the controller as shown in Step 2 on page 22. An additional remote indoor temperatureonly sensor can be purchased and installed in Zone 1. If the site in which the LC6000 controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/humidity sensors (one per zone) will need to be purchased and installed in the additional zones. All installed sensors must be enabled in the controller menu (see Configure Sensors beginning on page 36).
FIGURE 17 Additional Remote Indoor Temperature and Temperature/Humidity Sensor Installation
One additional temperature sensor can be added to Zone 1 and additional temperature/humidity sensors may be added to Zones 2 and 3 (one per zone). Be sure the sensors are connected to the proper terminals on the terminal block and sensor as listed below. The maximum cable length to connect temperature or temperature/humidity sensors to the LC6000 is 98'.

Zone 1: Optional Remote Temperature Sensor Terminals 20 & 21*

TB#

Wire Mark

Description

20 B7 Indoor Remote Sensor (Zone 1 ­ optional)

21 GND Ground

* The two wire connections for the optional remote temperature sensor are not polarity sensitive.

Zone 2: Optional Remote Temperature/Humidity Sensor Terminals 26, 27, 14, 15 & 23
IMPORTANT: Note jumper position in Figure 16

TB#

Wire Mark

Sensor

Description

26 B8 NTC OUT Indoor Remote Sensor (Zone 2)

27 GND NTC OUT Ground

14 B3 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 2)

15 GND M (GO) Ground

23 +VDC + (G) Power for B3

Zone 3: Optional Remote Temperature/Humidity Sensor Terminals 28, 29, 16, 17 & 24
IMPORTANT: Note jumper position in Figure 16

TB#

Wire Mark

Sensor

Description

28 B9 NTC OUT Indoor Remote Sensor (Zone 3)

29 GND NTC OUT Ground

16 B4 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 3)

17 GND M (GO) Ground

24 +VDC + (G) Power for B4

Zones 2 and 3 can also use temperature-only sensors in place of the temperature/humidity sensors. Zone 2 will connect to TB# 26 and 27. Zone 3 will connect to TB# 28 and 29. The wire connections for the temperature-only sensors are not polarity sensitive.

Manual 2100-705E

Page

23 of 46

Installing Optional Outdoor Temperature/Humidity Sensor
One optional outdoor temperature/humidity sensor (8301-090) can be installed. Follow the manufacturer's mounting instructions. Use 18 gauge 5-conductor shielded cable to connect to controller. The maximum cable length to connect the temperature/humidity sensor to the LC6000 is 98'.

FIGURE 18 Remote Outdoor Temperature/Humidity Sensor Installation
1. Connect wires from the 18 gauge shielded cable to terminals #65, #66, #67, #70 and #71.

TB#

Wire Mark

70 B12

71 ND

Sensor

Description

4

Remote Outdoor Temperature Sensor

5

Ground

67 B11

1

Remote Outdoor Humidity Sensor: 0-10 VDC

66 GND 65 +VDC

3

Ground

2

+VDC

47 48 49 50 51 52 53 54 55 56 57 58 59 60 62 61 64 63 66 65 68 67 70 69 72 71

2. Connect the other end of the shielded cable to the sensor terminals. Be sure wires are connected to proper terminals as shown in table above.
Manual 2100-705E Page 24 of 46

Emergency Off, Emergency Ventilation and Generator Run Connections The LC6000-200 controller is shipped with emergency off, emergency ventilation and generator run contacts. There are factory-installed jumpers across terminals #6 and #7 (emergency off), #8 and #9 (emergency ventilation) and #10 and #11 (generator run). Remove the factory-installed jumpers before making the connections.
FIGURE 19 LC6000-200 Series Connection for Emergency Off, Emergency Ventilation and Generator Run (If Applicable)

3

45

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Generator Run*
Emergency Ventilation*
Emergency Off*
* Normally closed (NC) contacts required. By default: Closed = No Alarm Open = Alarm

Manual 2100-705E

Page

25 of 46

Communication Wiring
Connect the field-supplied communication wiring from the wall-mount units to the controller in the manner shown in Figures 20, 21 or 22. The daisy chain does not need to follow the addressing order. The communication wire should be 2-wire, 18 gauge shielded cable with drain. Any color can be used. Be sure to match "+" and "-" symbols on controller terminal blocks to prewired unit control terminal block (see Figures 24 and 25 on pages 29 and 30). Attach communication wire filters as shown in Figures 20, 21 or 22. Do not run communication wiring in same conduit as supply wiring. Route communication wiring and power supply wiring in their own separate conduits.
FIGURE 20 Communication Wiring (Daisy Chain Method)

Filter

Wall-Mount Unit

Wall-Mount Unit

Filter LC6000 Controller

In addition to the "daisy chain" method of connecting the field-supplied communication wiring shown in Figure 20, the wall-mount units can also be connected in the manner shown in Figure 21. If connecting wall-units this way, be sure to place the communication wire filters in the positions shown in Figure 21. See Figure 22 for more information on the correct placement of the communication wire filters depending on the wiring method used.

Wall-Mount Unit

FIGURE 21 Communication Wiring (Alternate Method)
LC6000 Controller

Filter

Filter

Manual 2100-705E Page 26 of 46

Wall-Mount Unit

FIGURE 22 Placement of Communication Wire Filters (Daisy Chain and Alternate Methods)

Place filter here

Daisy Chain Wiring

Place filter here (end unit)

LC6000
Place filter here (end unit)

Unit 1

Unit 2

Alternate Wiring

Unit 3

Unit 4...up to 14 units

Place filter here (end unit)

Unit 1

LC6000*

Unit 2

Unit 3

Unit 4...up to 14 units

* LC6000 can be in any position other than start and end with filters placed on end units.

NOTE: Line filters can be on either the unit or controller, whichever device is on the end of the chain. No matter how many units there are, the two end devices will only have ONE communication cable, whereas the center devices will all have TWO (as shown above). Maximum two wires in each terminal. Filters go inside the unit or controller; shown out of unit above for identification only.

Manual 2100-705E

Page

27 of 46

The steps outlined on the following pages show how to connect the field-supplied communication wiring using the daisy chain method shown in Figure 20. If using the alternate method (as shown in Figure 21), the connections to the controller and each wall-mount unit will be the same but the filters need to be placed in the positions shown in Figure 22.
FIGURE 23 Communication Wiring: Termination at the Controller 1. Using the field-provided shielded cable, make a small service loop after entering the controller and attach the provided EMI filter at the intersection of the loop.
2. Connect one wire to terminal #56 (negative), the other wire to terminal #57 (positive) and the drain wire to ground terminal #60.
34 35 36 37 38 39 40 4142 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 62
+ ­
To Wall-Mount Unit 1 Control Board Terminal Block
Manual 2100-705E Page 28 of 46

FIGURE 24 Communication Wiring: Termination at the First Wall-Mount Unit

Wall-Mount Unit 1
1. From the controller, extend the field-supplied shielded cable through a separate conduit and route to terminal #1 (positive) and terminal #2 (negative) on the upper terminal block next to the wall-mount control board on the unit control panel. These connections are polarity-sensitive. Two-wire communication from control board is prewired to terminal block. Make sure to match "+" and "-" symbols on the Field Wiring label above the terminal block.

2. Connect the wires matching the terminal designations (+/-) of the Field Wiring label. Leave the drain wire loose.

Unit 1 Terminal Block

From LC6000 Controller

­+ ­+

3. Connect another cable in a similar fashion ("daisy chain") to route in conduit to the second wall-mount unit. Connect both drain wires with wire nut. Maximum two wires per terminal.

To Wall-Mount Unit 2 From LC6000 Controller
Unit 1 Terminal Block

Manual 2100-705E

Page

29 of 46

FIGURE 25 Communication Wiring: Termination at Additional Wall-Mount Units
From Wall-Mount Unit 1

Unit 2 ­ 14 Terminal Block

1. Route the cable from the first wall-mount unit to the terminal block of the second wall-mount unit. If this is the last unit to be connected, make a small service loop and attach EMI filter as shown.

Wall-Mount Unit 2

2. Connect the wires matching the terminal designations (+/-) on the Field Wiring label above the terminal block. Cap the loose drain with a wire nut or electrical tape.

­+

From Wall-Mount Unit 1
Unit 2 ­ 14 Terminal Block

3. Continue daisy chaining units by connecting "+" to "+", "-" to "-" and wire nutting drain together until last unit which is capped with a wire nut. Attach EMI filter as shown above at last unit. Up to 14 wall-mount units can be connected and controlled by one LC6000 controller.
NOTE: Terminals #3 and #4 are dry contacts to be used for the unit disable option. WARNING: Do not apply voltage to daisy chain connection terminals #1 or #2 or terminals #3 or #4. If 24V or any voltage
is applied to these terminals or to the daisy chain connection, board damage may occur.
Manual 2100-705E Page 30 of 46

Supply Wiring The LC6000 controller is powered by 120, 208 or 230 volts from the shelter. Field-supplied supply wiring should be minimum 16 gauge, maximum 14 gauge (see Figure 26). A reliable earth ground must be connected in addition to any grounding from conduit. Grounding bolts and nuts are included with the controller for this purpose; a 2 hole grounding lug must be field supplied. Install as shown in Figure 27. Failing to ground the controller box properly could result in damage to the equipment.
FIGURE 26 LC6000 Controller Circuit Install

Power

1

2

3

4 5 Input6 7 8 9 10 11 12 13 14 15 16 17 18

Ground

120 VAC Input (L1)

208V VAC Input (L1)

230V VAC Input (L1)

Power Input Common (L2 or N)

FIGURE 27 Controller Grounding Posts

A field-supplied, reliable earth ground must be connected in addition to any grounding from conduit. Attach earth ground to side of controller box using bolts and nuts supplied with controller and fieldsupplied 2-hole grounding lug. Failing to ground the controller box properly could result in damage to the equipment.

Manual 2100-705E

Page

31 of 46

TABLE 3 LC6000-200 Terminal Block Index

TB#

Wire Mark

Description

1

- 120 VAC Input

2

- 208 VAC Input

3

- 230 VAC Input

4

- Power Input Common

5

- Power Input Ground

6

DI1 Emergency Off Input

7 GND Emergency Off Common

8

DI2 Emergency Vent Input

9 GND Emergency Vent Common

10 DI3 Generator Run Input

11 GND Generator Run Common

12 B2 Zone 1 Indoor Remote Humidity Sensor

13 GND Ground

14 B3 Zone 2 Indoor Remote Humidity Sensor

15 GND Ground

16 B4 Zone 3 Indoor Remote Humidity Sensor

17 GND Ground

18 B6 Zone 1 Indoor Temperature Sensor

19 GND Ground

20 B7 Zone 1 Indoor Remote Temperature Sensor

21 GND Ground

22 VDC+ Power for B2 (Z1 Humidity)

23 VDC+ Power for B3 (Z2 Humidity)

24 VDC+ Power for B4 (Z3 Humidity)

25 VDC+ Power for B10 (Pressure)

26 B8 Zone 2 Indoor Remote Temperature Sensor

27 GND Ground

28 B9 Zone 3 Indoor Remote Temperature Sensor

29 GND Ground

30 B10 Indoor Space Pressure

31 GND Ground

32 NO1 Humidifier 1

33 C1 Common

34 NO2 Humidifier 2

35 C1 Common

36 NO3 Humidifier 3

37 C1 Common

38 NO4 Emergency Off Alarm

TB#

Wire Mark

Description

39 C4 Common

40 NO5 Emergency Vent Alarm

41 C4 Common

42 NO6 Generator Run Alarm

43 C4 Common

44 NO7 Indoor Humidity Alarm

45 C7 Common

46 NO8 High Indoor Temperature Alarm

47 C8 Common

48 NO9 Low Indoor Temperature Alarm

49 C8 Common

50 NO10 Zone 1 Unit Alarm

51 C8 Common

52 NO11 Zone 2 Unit Alarm

53 C8 Common

54 NO12 Zone 3 Unit Alarm

55 C8 Common

56

FB1R-

RS485 RX- / TX- (Fieldbus 1) UNIT CONNECTION

57

FB1R+

RS485 RX+ / TX- (Fieldbus 1) UNIT CONNECTION

58 FB2R- RS485 RX- / TX- (Fieldbus 2)

59 FB2R+ RS485 RX+ / TX- (Fieldbus 2)

60

-- Power Input Ground

61 24 VAC+ 24 VAC Supply

62

-- Not Used

63 24 VAC+ 24 VAC Supply

64 24 VAC- 24 VAC Ground

65 24 VAC+ 24 VAC Supply for Outdoor Humidity Sensor

66 24 VAC- 24 VAC Ground for Outdoor Humidity Sensor

67 B11 Signal for Outdoor Humidity Sensor

68 24 VAC+ 24 VAC Supply

69 D14 Bard Guard Alarm Signal

70 B12 Signal for Outdoor Temperature Sensor

71 GND Ground for Outdoor Temperature Sensor

72 GND Ground for Bard Guard Alarm Signal

73

G Orange Power Connector

74 24 VAC+ 24 VAC Supply

75 G0 Orange Power Connector

76 24 VAC- 24 VAC Ground

Manual 2100-705E Page 32 of 46

FIGURE 28 LC6000-200 Wiring Diagram

74 73 76 75

LC6000 TERMINAL BLOCK

(L1) 12012V0VININ (L1) 20820V8VININ (L1) 23023V0VININ (L2 OR N) COMCOMMOMNONININ
POWER GGNNDD
EMER OFF JUMPER
EMER VENT JUMPER GEN JUMPER
UNIT MODBUS CONNECTORS
GROUND

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

45

3

2

1

WHITE

RED

ORANGE

BLACK GREEN

RED

DI1

RED

DI2

RED

DI3

RED

B2

RED

B3

RED

B4

RED

B6

TB 6 TB 8 TB 10 TB 69

RED

B7

GREEN

BLK/RED

RED

B8

RED

B9

GND +Vdc

TB 12 TB 14 TB 16
TB 18 TB 20

GND

RED GREEN BLUE/BLK

B10 NO1

BLUE/BLK NO2

BLUE/BLK BLACK BLUE/BLK

NO3 C1 NO4

BLUE/BLK NO5

TB 26 TB 28 TB 30 TB 67 TB 70

BLUE/BLK BLACK BLUE/BLK BLACK BLUE/BLK

NO6 C4 NO7 C7 NO8

GND

BLUE/BLK NO9

BLUE/BLK NO10

BLUE/BLK NO11

BLUE/BLK NO12

BLACK

C8

ORANGE/BLK 1-RX-TX-

ORANGE

1-RX+TX+

BROWN/BLK

2-RX-TX-

BROWN

2-RX+TX+

GROUND

EMPTY YELLOW BLUE

G 24 VAC TB74 G0 24 VAC TB76

RED

B11

RED

B12

RED

DI4

GREEN

TB 61 TB 64

YELLOW G YELLOW BLUE G0 BLUE

120V/208V/230VAC TRANSFORMER
24VAC

YELLOW BLUE

TB74 TB76

G G0
24VAC INPUT
TO BOARD

R X-TXR X+ TX+ GND R X-TXR X+TX+ GND

TB 59 TB 58
TB 57 TB 56

TB 37 TB 32 TB 34 TB 36

C4

TB 43

TB 38

TB 40

TB 42

PLC BOARD

TB 44 TB 45
TB 55 TB 46 TB 48 TB 50 TB 52 TB 54

NOTE:
Wire indexes are identified such that even numbered index numbers are on the lower wire entries of the terminal block and odd numbered index numbers are on the top wire entries. Since terminal block 60 is a ground block, terminal blocks 61 thru 72 shift while still maintaining the same top and bottom configuration.

62 61 64 63 66 65 68 67 70 69 72 71

Manual 2100-705E

Page

33 of 46

SYSTEM SET UP

NOTE: Screenshots shown in this manual reflect default settings (when applicable).
The LC6000 controller and TEC-EYE hand-held diagnostic tool will both be used to set up the Bard free cooling system (the TEC-EYE is only used to set up the wall-mount units). If installing a single MEGATEC wall-mount unit with a PGD or PGDx stand-alone display, refer to PGD manual 2100-734 or PGDx manual 2100-740 for information on setting up a stand-alone display for single unit operation.
TABLE 4 LC6000/TEC-EYE Passwords (Defaults)

User

2000

Technician

1313

Engineer

9254

Use UP or DOWN keys and ENTER key to enter password

Main Menu. The menus permit the user to easily view, control and configure the unit. See the latest version of MEGA-TEC Service Manual 2100-671 for more information on using the TEC-EYE.
The TEC-EYE connects to the wall-mount unit control board via an RJ11 modular connector as shown in Figure 29.
When not being used, the TEC-EYE hand-held diagnostic tool should be stored inside or near the LC6000 controller. Do not let the TEC-EYE leave the shelter.
FIGURE 29 TEC-EYE Connection to Unit Control

TEC-EYE Hand-Held Diagnostic Tool
The microprocessor control used in the MEGA-TEC wall-mount air conditioners allows for complete control and monitoring through the use of the provided TECEYE hand-held monitor.
The menu driven interface provides users the ability to scroll through two menu levels: Quick Menu and

Modular Connector for TEC-EYE Hand-Held Diagnostic Tool

FIGURE 30 TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)

MIS-3953

ALARM KEY

UP KEY

MENU KEY

ENTER KEY

ESCAPE KEY
ALARM KEY Allows viewing of active alarms Silences audible alarms Resets active alarms MENU KEY Allows entry to Main Menu ESCAPE KEY Returns to previous menu level Cancels a changed entry
Manual 2100-705E Page 34 of 46

DOWN KEY
UP KEY Steps to next screen in the display menu Changes (increases) the value of a modifiable field ENTER KEY Accepts current value of a modifiable field Advances cursor DOWN KEY Steps back to previous screen in the display menu Changes (decreases) the value of a modifiable field

TEC-EYE Status Screen
The Status screen is the default start-up screen and also the return screen after 5 minutes of no activity. The screen can be accessed any time by pressing the ESCAPE key repeatedly.
The wall-mount unit address is displayed in the upper right corner on the Status screen (see Figure 30). The Status screen also shows the current date, time, return air temperature, mixed air temperature, supply air temperature, outdoor air temperature and outdoor air humidity. Blower speed, condenser fan speed, damper position and unit status are also displayed. See Table 5 on page 42 for wall-mount unit status messages.

can only be used once per LC6000 regardless of number of zones. Bard also recommends physically labeling each unit for ease in identification.
FIGURE 31 Unit Configuration

NOTI CE
It is important to check the software version during installation to ensure that the latest version has been installed. Current software versions and installation instructions are available on the Bard website at http://www. bardhvac.com/software-download/
Setting Up Wall-Mount Units for Operation
The TEC-EYE hand-held diagnostic tool is needed to set up the wall-mount unit(s).
1. Address Each Wall-Mount Unit
Each unit must have a unique address for the system to operate correctly with the LC controller (Ex: 1, 2, 3, ...14 depending on the number of units). The unit only needs the address to be changed for the communication to work properly. The wall-mount unit address is displayed in the upper right corner on the Status screen on the TEC-EYE display (see Figure 30).
To change the unit address:
1) Press MENU key to access the Main Menu screen.
2) Press UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4) Press ENTER key to scroll to Unit Address (see Figure 31).
5) Press UP or DOWN keys to change the address to a value between 1 and 14.
NOTE: Each unit must have a unique address for the communication to work properly. Unit addresses

In addition to setting up the address, the user may also want to set the unit zone and unit of measure.
To change these settings:
1) Press MENU key to access the Main Menu screen.
2) Press UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4) Press ENTER key to scroll to Unit Zone (see Figure 31).
5) If desired, press UP or DOWN keys to change value to desired zone.
6) Press ENTER scroll to UOM.
7) If desired, press UP or DOWN keys to change the value from USA to SI, NC, LON, CAN or UK. Units are preconfigured for each selection.
8) Press ENTER key to save.
Basic wall unit parameter settings are now set and the unit is ready to communicate with the LC.
2. Execute a Self Test on Each Unit
Execute a self test on each unit to verify the equipment is functioning correctly. The self test parameters are not adjustable.
The self test will automatically skip sections of the test based on the model number entered into the controller. If position 10 of the model number is B (to indicate a blank off economizer option), the test steps associated with the economizer will be skipped. If positions 8 and 9 of the model number indicate a 0Z (0 kW) option, test steps associated with heating will be skipped. If positions 8 and 9 indicate a 09 (9 kW) option,second stage heat tests will be skipped.

Manual 2100-705E

Page

35 of 46

1) Press MENU key to access the Main Menu screen.
2) Press UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Self Test A11 screen.
5) Press ENTER key to scroll to Enable parameter (see Figure 32).
6) Press UP or DOWN key to change value to Yes. The self test will begin.
FIGURE 32 Executing Self Test

3. Clear Unit Alarm Logs on Each Unit
The wall-mount unit may have generated some alarms during startup and should be cleared after installation.
To clear the wall-mount unit alarm logs:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to Settings; press ENTER key.
4) Press UP or DOWN keys to scroll to Initialization; press ENTER key.
5) Press UP or DOWN keys to scroll to Initialization; press ENTER key.
6) Press ENTER key to scroll to Delete alarm logs? (see Figure 33).
7) Press UP or DOWN key to change NO to YES.
8) Press ENTER key to clear all alarm logs.
FIGURE 33 Clearing Unit Alarm Logs

Self Test Parameter Descriptions Damper Time: This is the time (in seconds) allowed for both the opening sequence and closing sequence. Heat/Cool Time: This is the time (in seconds) allowed for cooling sequence and heating sequence. Status: This will display what the unit is doing as the self test progresses. The following messages may appear: Self Test Off Initializing... Opening Economizer Closing Economizer Compressor 1 On Compressor 1 & 2 On C1 Full Load + C2 On Turning Comp. Off.... Electric Heat 1 On Electric Heat 1 & 2 On Turning Heat Off... End The unit will determine which items to test based on the unit model number.

After each of the wall-mount units have been addressed, had a self test performed and had the alarm logs cleared, the rest of the system set up can proceed.
Setting Up LC6000 for Operation
The LC6000 controller will be used for the remaining steps in the set up process.
LC6000 Status Screen
The Status screen is the default start-up screen and also the return screen after 5 minutes of no activity on the LC6000. The screen can be accessed any time by pressing the ESCAPE key repeatedly.
The Status screen on the LC6000 displays the current date, time, unit displayed, zones and system status (see Figure 34).

Manual 2100-705E Page 36 of 46

FIGURE 34 LC6000 Controller Display and Interface (Status Screen Shown)

ALARM KEY MENU KEY ESCAPE KEY

UP KEY ENTER KEY DOWN KEY

LC6000 interface key functions are the same as those shown for the TEC-EYE in Figure 30 on page 34.

4. Set LC Controller Date and Time
1) Press MENU key to access the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 1313.
3) Press the UP or DOWN keys to scroll to the Settings menu; press ENTER key.
4) Press UP or DOWN keys to scroll to Date/Time menu; press ENTER key.
5) Press UP or DOWN keys to scroll to Date/Time change.
6) Press ENTER key to scroll to the desired value to be changed (see Figure 35).
7) Press UP or DOWN keys to change the value.
8) Press ENTER key to save and to scroll to top of screen.
9) Press UP or DOWN keys to scroll to Timezone (if applicable). Follow steps 6-8 to change timezone.
10) Press ESCAPE key several times to return to Main Menu screen.
FIGURE 35 Setting Controller Date and Time

NOTE: The LC6000 will sync the time and date configured to each of the wall-mount units once communication is established.
5. Configure Sensors
The system will need to be configured for the number of temperature and humidity sensors installed. The system is shipped with one combination temperature and humidity sensor. Additional combination sensors may be purchased or alternatively, temperature-only sensors may be purchased instead. The LC is capable of supporting up to four indoor temperature sensors (two in zone 1, one in zone 2 and one in zone 3), three indoor humidity sensors (one per zone ), one outdoor temperature sensor and one outdoor humidity sensor. The system will need to be configured for the various configurations.
If necessary, the sensors could be calibrated at this time too. For information on calibrating the sensors (adjusting the offset), see page 42.
To enable/disable Zone 1 Indoor Humidity:
1) Press MENU key to go to the Main Menu screen.
2) Press UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z1 Indoor Hum C4.
5) Press ENTER key to scroll to Enable (see Figure 36 on page 38).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).

Manual 2100-705E

Page

37 of 46

FIGURE 36 Enable/Disable Zone 1 Indoor Humidity Sensor

5) Press ENTER key to scroll to Enable (see Figure 38).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 38 Enable/Disable Zone 3 Indoor Humidity Sensor

To enable/disable Zone 2 Indoor Humidity:
1) Press MENU key to go to the Main Menu screen.
2) Press UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z2 Indoor Hum C5.
5) Press ENTER key to scroll to Enable (see Figure 37).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 37 Enable/Disable Zone 2 Indoor Humidity Sensor

To enable/disable Zone 1 Indoor Temperature:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z1 Indoor Temp C7.
5) Press ENTER key to scroll to Enable (see Figure 39).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 39 Enable/Disable Zone 1 Indoor Temperature Sensor

To enable/disable Zone 3 Indoor Humidity: 1) Press MENU key to go to the Main Menu
screen. 2) Press UP or DOWN keys and ENTER key to
enter USER password 2000. 3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4) Press UP or DOWN keys to scroll to Z3 Indoor
Hum C6.
Manual 2100-705E Page 38 of 46

To enable/disable Zone 1 Remote Temperature:
1) Press MENU key to go to the Main Menu screen.

2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z1 Remote Temp C8.
5) Press ENTER key to scroll to Enable (see Figure 40).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 40 Enable/Disable Zone 1 Remote Temperature Sensor

To enable/disable Zone 3 Remote Temperature:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z3 Remote Temp C10.
5) Press ENTER key to scroll to Enable (see Figure 42).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 42 Enable/Disable Zone 3 Remote Temperature Sensor

To enable/disable Zone 2 Remote Temperature:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Z2 Remote Temp C9.
5) Press ENTER key to scroll to Enable (see Figure 41).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).
FIGURE 41 Enable/Disable Zone 2 Remote Temperature Sensor

To enable/disable Outdoor Air Humidity:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Outdoor Air Humid C11.
5) Press ENTER key to scroll to Enable (see Figure 43 on page 40).
6) Press UP or DOWN key to change value to ON to enable sensor (or change value to OFF to disable sensor).

Manual 2100-705E

Page

39 of 46

FIGURE 43 Enable/Disable Outdoor Air Humidity Sensor

5) Press ENTER key to scroll to Total Units (see Figure 45).
6) Press UP or DOWN keys to adjust value to correct number of units.
7) Press ENTER key to save value. 8) Press the ESCAPE key several times to return
to Main Menu screen.
FIGURE 45 Total Units Displayed

To enable/disable Outdoor Air Temperature: 1) Press MENU key to go to the Main Menu
screen. 2) Use UP or DOWN keys and ENTER key to
enter USER password 2000. 3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key. 4) Press UP or DOWN keys to scroll to Outdoor
Air Temp C12. 5) Press ENTER key to scroll to Enable (see
Figure 44). 6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to disable sensor).
FIGURE 44 Enable/Disable Outdoor Air Temperature
6. Enter Total Number of Units 1) Press MENU key to go to the Main Menu screen. 2) Press UP or DOWN keys and ENTER key to enter USER password 2000. 3) Press UP or DOWN keys to scroll to Sys Config; press ENTER key. 4) Press UP or DOWN keys to scroll to General; press enter key.

7. Verify Units Are Online

Once a unit is uniquely addressed, communication can be verified at the LC controller.

With the correct number of units set at the LC controller, each unit can be remotely viewed from the controller information screen.

To view these screens:

1) Press ESCAPE key to view the Status screen. (May need to be pressed more than once.)

2) Press UP or DOWN key until the Quick Menu in

the lower right corner of the screen displays the

Information icon (

); press ENTER key.

3) Press UP or DOWN keys to scroll through the Information screens until the desired unit Information screen appears.

In addition to being able to remotely view the units, an alarm will be generated on the LC controller for units not communicating.

8. Select Economizer Type for Each Zone

Each zone can be configured to operate the economizers with different considerations. For more information on the different economizer choices, reference the most recent version of MEGA-TEC Service Instructions 2100-671.

The type of consideration can be set to none, dry bulb, temperature and humidity or enthalpy. These settings will be communicated to the wall units while connected to the LC6000 to ensure all units operate the same.

Manual 2100-705E Page 40 of 46

To select economizer type for each zone:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter password 1313.
3) Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4) Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.
5) Press UP or DOWN keys to scroll to Zone FC Settings A2-4 (Zone 1), Zone FC Settings A3-4 (Zone 2) or Zone FC Settings A4-4 (Zone 3).
6) Press ENTER key to scroll to Type (see Figure 46).
7) Press UP or DOWN keys to change economizer type to None, Drybulb, TempHum or Enthalpy.
8) Press ENTER key to save.
FIGURE 46 Selecting Economizer Type

FIGURE 47 Clearing LC6000 Alarm Logs
10. Complete Installation Once all the installation steps have been completed, all alarms and alarm logs have been cleared and system verification and self test results were satisfactory, the installation can now be considered "complete". Additional programming information can be found in MEGA-TEC Service Instructions 2100-671 and LC6000 Service Instructions 2100-669.

9. Clear Controller Alarm Logs
The LC6000 may have generated some alarms during startup and should be cleared after installation. Controller alarm logs must be cleared at time of installation.
To clear the LC controller alarm logs:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to enter USER password 2000.
3) Press UP or DOWN keys to scroll to Settings; press ENTER key.
4) Press UP or DOWN keys to scroll to Initialization; press ENTER key.
5) Press ENTER key to scroll to Delete alarm logs? (see Figure 47).
6) Press UP or DOWN key to value to YES; press ENTER key.
7) Press ESCAPE key several times to return to Main Menu screen.

Manual 2100-705E

Page

41 of 46

ADDITIONAL INFORMATION

Menu Screens and Password Levels
TABLE 5 TEC-EYE Menu Structure

Menu/Screen Structure
Quick Menu Setpoints (Orphan Mode Temperature Control) Information Alarm Log
Main Menu System Config Adv. Sys. Config I/O Config
Digital Inputs Digital Outputs Analog Inputs Analog Outputs Fan/Blowers Manual EEV On/Off Alarm Logs Settings Date/Time Initialization Change Passwords Logout

Password Level Required
None None None
User Technician Technician Technician Technician Technician Technician Technician Technician
User User
-Technician Technician
Varies --

TABLE 6 LC6000 Controller Menu Structure

Menu/Screen Structure
Quick Menu Setpoints (Comfort Mode) Information
System Unit 1 Unit 2 Unit 3...14 Alarm Log
Main Menu System Config Adv. Sys. Config I/O Config On/Off Alarm Logs Settings
Date/Time Language Network Config Serial Config Initialization Logout

Password Level Required
None None None None None None None
User Technician Technician
User User
-Technician
User Technician Technician
Varies --

Manual 2100-705E Page 42 of 46

Setpoints
The LC6000 setpoints will determine the cooling and heating setpoints when communicating with the wallmount units. The unit cooling and heating setpoints will determine the cooling and heating setpoints when in orphan mode. It is important to note that once the wall-mount unit establishes communication with the LC6000, the setpoints from the LC will override the wall-mount unit setpoints. If a unit returns to orphan mode after communicating with LC, it will operate with last communicated setpoints from the LC.
If at any time the unit(s) loses communication with the LC6000 controller, the unit(s) will go into orphan mode.
Calibrating Sensors
1. Press MENU key on LC controller interface to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to sensor to be adjusted.
5. Press ENTER key to scroll to Offset (see Figure 48).
6. Press UP or DOWN keys to add or subtract to the sensor offset value.
7. Press ENTER key to save.
FIGURE 48 Adjusting Sensor Offset Value

Manual 2100-705E

Page

43 of 46

TABLE 7 Unit Status Messages

Message

Description

Orphan Mode

This message will be shown when unit is not connected to the LC or stand-alone display. The unit is not operating when this message is shown but is ready to heat or cool based on the return air temperature. Blower will run continuously in this mode.

This message will be shown when the unit is communicating with stand-alone display. The unit Standalone Mode is not operating when this message is shown but is ready to heat or cool based on the display
temperature sensor.

LC Online
Cont. Blower
Comfort Mode Freecooling
Passive Dehum Cooling Heating
Optimized

This message will be shown when the unit is communicating with the LC6000. The unit is not operating when this message is shown but is ready to respond to any call or event from the LC.
The message will be shown when the unit has been commanded to run the blower continuously by the LC6000 or the stand-alone display.
This message will be shown when the unit has been put into comfort mode by the stand-alone display.
This message will be shown when the unit is utilizing the economizer to cool the space.
This message will be shown when the unit is connected to the LC6000 or stand-alone display and the economizer is disabled and blower speeds have been lowered to optimize moisture removal.
This message will be shown when the unit is operating the air conditioning system to cool the space.
This message will be shown when the unit is operating the electric heaters to warm the space.
This message will be shown when the unit is operating both the economizer and the air conditioning simultaneously to cool the space.

Active Dehum

This message will be shown when the unit is connected to the LC6000 or stand-alone display, no heating or cooling calls are required and the air conditioner and electric heat are being used together to remove moisture from the space.

Self Test

This message will be shown when the self test has been activated and component operations are being verified.

Off by Alarm

This message will be shown when the blower, fan or expansion module are no longer communicating with the main controller. Also, when unit disable, emergency off or no return sensor is detected in orphan mode.

Emergency Vent
Emergency Cool
Emergency Off Off by LC
Off by PGDx Off by Keyboard
Model Invalid

This message will be shown when connected to a LC6000 and the emergency vent input is activated.
This message will be shown when the space temperature is above the high temperature setpoint. This can be active in orphan mode, stand-alone mode or when connected to the LC6000.
This message will be shown when unit disable input is active, or when connected to LC6000 and emergency off input is active.
This message will be shown when connected to the LC6000 and the system is turned off.
This message will be shown when connected to the stand-alone display and the unit is turned off.
This message will be shown when unit has been turned off at unit.
This message will be shown when a valid model number is not entered into the controller.

Manual 2100-705E Page 44 of 46

TABLE 8 LC6000 Status Messages

Message

Description

On

The LC6000 is ready and functioning properly.

The LC6000 is being turned off by the Off by BMS Building Management System through
Modbus TCP/IP.

Off by Keyboard

The LC6000 is turned off using the (D. On/Off) Menu on the PGD. All communicating units will be inactive.

Comfort Mode

The LC6000 is set to Comfort Mode. This mode is used to temporarily override heating/cooling setpoints and maintain a default temperature of 72°F for 60 minutes.

Emergency Cooling

A high temperature has been sensed in one or more zones. All available units in that zone are sent a command for emergency cooling. (Refer to unit manual for emergency cooling sequence.)

Emergency Vent

Input signal from an external device at terminal DI2 (e.g., hydrogen detector). Units that are equipped with a ventilation option and configured will open the dampers at 100% with the blower at full speed.

A/C Circuit Information
MEGA-TEC Series wall-mounted air conditioners have two separate refrigeration circuits: Circuit 1 is the two stage system located on the left side of the unit and circuit 2 is the single stage system on the right side (see Figure 49).
NOTE: 400V models have only two stages of capacity rather than three and are identical in size. Take note of this when reading this manual.
For more information on the MEGA-TEC dual A/C circuits, see the latest version of Service Instructions 2100-671.

FIGURE 49 MEGA-TEC Refrigeration Circuits

CIRCUIT 1
LEFT HAND

CIRCUIT 2
RIGHT HAND

FRONT VIEW

MIS-4034

Manual 2100-705E

Page

45 of 46

Remote Indoor Temperature/Humidity Sensor Orientation
Current versions of the remote indoor temperature/ humidity sensor need to be installed with the shielded cable wires entering the bottom of the back of the sensor to connect to the sensor terminals (see Figure 50). Earlier versions of this sensor were installed so that the sensor wires entered through the top of the back of the sensor (see Figure 51). The orientation of the sensor affects the position of the DP1/DP2 jumpers. Depending on how the sensor is installed, be sure to confirm that the jumpers are in the proper position for the 0-1 V setting as shown in the figures below.
This applies to all indoor temperature/humidity sensors connected to the LC controller. See illustration mounted inside of sensor cover for further detail on jumper position.
FIGURE 50 Current Sensor Orientation (Shielded Cable Wires Enter from Bottom)

FIGURE 51 Earlier Sensor Orientation (Shielded Cable Wires Enter from Top)

Jumper
DP1 DP2
DP1 and DP2 Jumpers Positioned for 0-1V (Current Orientation)
Manual 2100-705E Page 46 of 46

Jumper
DP1 DP2
DP1 and DP2 Jumpers Positioned for 0-1V (Earlier Orientation)



References